`V^ 9100 W Jewell Ave
Lakewood, CO 80232
OL ENGINEERING, INC. 720-440-9450
www.dlengineer.com
3/6/2019
Complete Basement Systems
11795 East 45th Ave.
Denver, CO 80239
RE: Job Number 2019-5883
Site Observation Visit (Lowers)
12296 W. 34th PI.
Wheat Ridge, CO 80232
DL Engineering Inc. reviewed the progress of construction for the subject project on February 8, 2018.
The following is a summary of the observations made:
New Observations:
Reviewed the helical piers. There were 4 piers installed on the northeast wall of the
garage spaced at approximately 6'-6" o.c. and 4 installed on the southwest wall of the
garage spaced at approximately 6'-6" o.c.
o The pier spacing was observed and appears to be in conformance with the
construction documents.
o The piers were installed to refusal or to a depth no less than that specified in the
construction documents.
o The helical piers appear to be installed in conformance with the structural
mitigation plan.
• Site grading around the perimeter of the house did not appear to be modified.
• Vegetation around the perimeter of the house did not appear to be modified.
• New slab around the perimeter of the house did not appear to be modified.
Volatile Soils:
The moisture around the foundation elements must be controlled for the useful life of the building.
Time has shown that Colorado soils can be unstable, and structures can experience damaging
movements due to expanding and shrinking soils, primarily when moisture changes occur. Maintaining
consistent soil moisture contents around all foundation elements is crucial to minimizing foundation
movements. Even with properly engineered/constructed foundation systems these volatile soils can still
exert excessive pressures causing damage in the residence. If the Owner would like further insight
about the on-site soil conditions and preventative measures, a Geotechnical Engineer should be
consulted.
Geotechnical Consideration:
It is possible that the piers may consolidate the soil under the piers. Because of this, periodic surveys of
the supported structures should be conducted to assure project success. The Owner should be
responsible for annual surveys certifying project success. It is recommended that a baseline survey be
conducted immediately. The Owner should report all findings and reports to the Structural Engineer. If
vertical movement of the foundation walls is discovered, the piers should be re -pressurized. A
Geotechnical Engineer should be present for the re -pressurizing of the piers.
w
�V
OL ENGINEERING, INC.
Disclaimer:
In as much as the site review of an existing structure for the purpose of observing the structure
conditions requires that certain assumptions be made regarding existing conditions and because some
of these assumptions may not be verifiable without expending additional sums of money or destroying
otherwise adequate or serviceable portions of the building, the Client agrees that , except for negligence
on the part of the Engineer, the Client will hold harmless, indemnify and defend Engineer from and
against any and all claims arising out of the professional services we have provided.
If you should have any further questions, please feel free to contact me at (720) 440-9450 or
rarp@dlengineer.com,
Sincerely,
Ryan Arp, EI
Under the direct supervision of,
Daniel LeMier, PE
D a ' Digi by Daniel U=Dw
DN: OI�Dani ier, OU=Owner,
O=DL En�InQOn
E=tllemie n com
Reason:l ;vi is
L e r document ..
Location:
V Date: 2019 *104:
35343
—,O�
FEI
�
z E
m z
EW
N
Q
07
m
U a
a`
U
A�\
J
l �
�
o
m
g�
j
CL
CD
O
W
U
0
E�
b
U
C
a
c
m
3R
U
m
m
o
m
W
N
ei
Q
m
C
c
C
W
ELD
N
cri
LL
a
2)
�
z E
m z
EW
N
Q
07
m
U a
a`
U
A�\
J
�
z E
m z
EW
N
Q
07
m
U a
a`
U
S
E
E
c
.;
w
CL
U
O
cc
LD
q
IL
O'
0)
0
J
C
0
(10
39
U)
/�L
/1
U
FRI
m
0
0
m
m
�
iR
C
=
l6 U
CL
a
c
�$
U
Cl
o
E
U
c
FRI
u
d
Q
Q
Q
�
a
4
FRI
i
F'4
7
r
m
D
E
E
c
t
0
1^1
L
f
m
D
Ci
12
ik
C
=
U
U
v
ai
CJ
o
C
0
U
m
E
z
E
�
5
O
U
a
a
a
U
1
c
U
C
m
C
W
Z
r
/0
y
W
�
F'4
7
r
m
D
E
E
c
t
0
Ci
Cl
v
�3
^C
W
C
0
U
m
E
z
E
z
�
5
E
°
U
a
a
a
U
F'4
7
r
m
D
E
E
c
5 ■
m
vi
M
v
R�
�
O
m
i
M�
E
m
C
yry
1 v
t0
m
O m
(\tea
>
m m
CL 'a
o
�N
m
vi
v
R�
�
O
m
z
E
CL
O
C
U
(\tea
a U
m
U'
'p
G
%
C
m
Z
N
Q
m
fn
a
U)
E
lLL
in
O
m
vi
z E
z
E
o m
U
U a
a U
M
��
_ILcm
V
iu
M
m �
E
E
E Z
H
E
v
o m
U a
a` U
m
it
q
C
o
=
o
CNV
as
LD
o
c
�
m
c
CD
U
m
o
ECD
t
O
«
C
m
n
l 0
L
:
�
N
o
LL
0
�
m �
E
E
E Z
H
E
v
o m
U a
a` U
ox
14
i
Fnm
m
m
U
m
0
9
cr
U)
V)
M
0
CD
Z
E Z
H
a
N
C
�?
U a
a
\
^ ,
�.
O
m
E
U
m
Er-
o
12
CD
o
c
=
cc
IL
V
CD
Z
E Z
H
a
N
C
�?
U a
a
\
^ ,
�.
O
m
E
U
�k
V
U
y
t
c
m
v
c
CD
Z
m
Q
N
cin
0
v
LL
o
�
CD
Z
E Z
H
a
N
C
�?
U a
a
U
i
2
t
E
E
C
a
r4
w
m
E
E
C
2
C
CL
U
0
cc
ED
LD
a
O
o
m
Er
°jj�
Is
to
o 0
s
a
a
o
m
Cl
o
EEC
is
m
c
m
E m
m
d
O
C
N 0
^�
ECD 12
c c
LL �
a
�
O
C'_
r
�
c3
CL
U
Z
m
E
z
V
•�
a
_a
U
a
a U
a
r4
w
m
E
E
C
2
C
CL
U
0
cc
ED
LD
a
O
0)
O
J
c-
0 O
C-
4—
CO
AE
^W
CL
U
N
2
m
CL
C
c
CD
C
m
C
CD
a
7
z
N
__r
45
E
N
Z
E
E
0
N
U
N
N
1
m
d
Er
cc
m
om
C
M
�
'
N
a
o
U
N
N
m
L
CL
a
E
m
E
C
i
MR
� �
C, VII
C)
oh
o
iu
m
L
CL
a
E
m
E
C
i
MR
i CITY OF WHEAT RIDGE
Building Inspection Division
(303) 234-5933 Inspection line
(303) 235-2855 Office • (303) 237-8929 Fax
INSPECTION NOTICE
Inspection Type: F3 r_I
Job Address: q (=� W 3 Q-24 2L
Permit Number: 7bi UU ZZ -?-
4
Z
4 V ��
Ar( Eie
❑ No one available for inspection: Time A P
Re -Inspection required: Yes WO
When corrections have been made, call for repection at 303234-5933
r r�
Date: Inspector:
DO NOT REMOVE THIS NOTICE
i CITY OF WHEAT RIDGE
Building Inspection Division
(303) 234-5933 Inspection line
(303) 235-2855 Office • (303) 237-8929 Fax
INSPECTION NOTICE
Inspection Type: ✓�'r)
Job Address:
Permit Number: C, �1 ` �-
h
3
❑ No one available for inspection: Time i - AM/PM
Re -Inspection required: Yes No
When corrections have been made, call for re -inspection at 303 -234 -
Date: Inspector:
DO NOT REMOVE THIS NOTICE
City of Wheat Ridge
Residential Plumbing PERMIT - 201900743
PERMIT NO: 201900743 ISSUED: 04/22/2019
JOB ADDRESS: 12296 W 34th Pl EXPIRES: 04/21/2020
JOB DESCRIPTION: Residential underground irrigation tap, excavation approximately 4.5 feet
deep with back flow preventer.
*** CONTACTS ***
OWNER (720)490-5865 LOWERS HEATHER
SUB (303)944-0205 MICHAEL L. SOLIDAY 018048 MICHAEL SOLIDAY
*** PARCEL INFO ***
ZONE CODE: UA / Unassigned USE: UA / Unassigned
SUBDIVISION CODE: 2403 / APPLEWOOD VILLAGES, PROSPECT V BLOCK/LOT#: 0 /
*** FEE SUMMARY *** ESTIMATED PROJECT VALUATION: 4,132.00
FEES
Total Valuation 0.00
Use Tax 86.77
Permit Fee 125.05
** TOTAL ** 211.82
*** COMMENTS ***
*** CONDITIONS ***
ALL sewer repair/replacements for which a permit is issued MUST be inspected by and receive
written approval from the City of Wheat Ridge BUILDING DIVISION, regardless of inspection
by any Sanitation District representative. Inspection and approval of work by any
Sanitation District representative DOES NOT grant authority to cover work without the
approval of the Building Division.
**For trenchless sewer replacements - The contractor will verify proper slope of new sewer
piping in conformance with the IRC and IPC of 1/4 inch per foot unless otherwise allowed
specifically by the applicable code. The plumbing contractor will provide verification of
proper slope and drainage in writing as a condition of approval of the permitted work.**
City of Wheat Ridge
Residential Plumbing PERMIT - 201900743
PERMIT NO: 201900743 ISSUED: 04/22/2019
JOB ADDRESS: 12296 W 34th P1 EXPIRES: 04/21/2020
JOB DESCRIPTION: Residential underground irrigation tap, excavation approximately 4.5 feet
deep with back flow preventer.
I, by my signature, do hereby attest that the work to be performed shall comply with all accompanying approved plans and specifications=
applicable building codes, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized
by the legal owner of the rope rty and ma uthorized to obtain this permit and perform the work described and approved in conjunction with
this enmt. I further attes that I am legally authorized to include all entities named within this document as partes to the work to be
performed nd that all work to be perf0 ed is disclosed in this document and/or its' accompanying approved plans and specifications.
Signature of OAdNER or CONTRACTOI_.(/Circle one) Date
1. This permit was issued based on the information provided in the pen -nit application and accompanyingplans and specifications and is
subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures.
2. This permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and
received prior to the date of expiration. An extension of no more than 180 days made be granted at the discretion of the Chief Building
Official and may be subject to a fee equal to one-half of the originalpermit fee.
3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard
requirements, fees androcedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of
the Chief Building Official and is not guaranteed.
4. No work of any manner shall be performed that shall results in a changeof the natural flow of water without prior and specific approval.
5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all required
inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services
Division.
5. ssuance or ting of a permit shall not be construed to be a permit for, or an approval of, an violation of any provision of any
p cab code ny ordinance or regulation of this jurisdiction. Approval of work is subject to field inspection.
Signature of Chief Building Official Date
REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY.
City of
t Wheat Pjdge
MUNITY DEVELOPMENT
Building & Inspection Services
7500 W. 2911 Ave., Wheat Ridge, CO 80033
Office: 303-235-2855 * Fax: 303-237-8929
Inspection Line: 303-234-5933
Email: permits(a)-ci.wheatridge.co.us
FOR OFFICE USE ONLY
Date:
Plan/Permit #
Plan Review Fee:
Building Permit Application
*** Complete all applicable highlighted areas on both sides of this form.
Incomplete applications may not be processed. ***
Property Address: / 9C2 9& bJ �30A 131 (' le
Property Owner (please print): /k?Q76fr Phone:X4-0 -y90 - 69 6
Property Owner Email:
Tenant Name (Commercial Projects Only)
Property Owner Mailing Address: Vf (if different than property address)
Address: l 'off a 9� (�l '3 " 1 P/0 0/c,
City, State
D �nUZ S
Arch itect/Eng1neer E-mail: Phone:
Contractor Name: /0/&V'0 I "�O/l wa
City of Wheat Ridge License #: % g� �i J Phone:l � 2W-620,5
Contractor E-mail Address: />?LS cp / rdaV Qv- /n sn .-nnM
For Plan Review Questions & Comments
-- (please print):
CONTACT NAME (please print): /ClXic° i �O�t �a (,, Phone:303 9(Ze-Ozos-
CONTACT EMAIL(p/ease print):
Sub Contractors (Must provide Wheat Ridge License No & Signed Subcontractor Authorization form):
Electrical: Plumbing: Mechanical:
W.R. City License # W.R. City License # W.R. City License #
Other City Licensed Sub: Other City Licensed Sub:
City License # City License #
Complete all highlighted fields, if applicable.
[-]COMMERCIAL
❑ RESIDENTIAL
Provide description of work: For ALL projects, provide a detailed description of work to be
performed, including current use of areas, proposed uses, square footage, existing condition and
proposed new condition, appliance size and efficiency, type and amount of materials to be used, etc.
undP1- g round i rn' 9Q -biome 4ap , ex0-0 L-?��'o- ow nox 4.s'clPeP
uJ?R baQkF1ocu Pe (1en�O
Sq. FULF
BTUs
Gallons
Amps Squares For Solar: KW # of Panels Requires Structural
For Commercial Projects Only: Occupancy Type: Construction Type:
Occupancy Load: Square Footage:
Project Value: (Contract value or the cost of all materials and labor included in the entire project)
$ 4� , / 6 o/, (%V
OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT
I hereby certify that the setback distances proposed by this permit application are accurate and do not violate applicable ordinances, rules or
regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown and allegations made are
accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance
with applicable City of Wheat Ridge codes and ordinances for work under any permit issued based on this application; that I am the legal owner
or have been authorized by the legal owner of the property to perform the described work and am also authorized by the legal owner of any
entity included on this application to list that entity on this application. I, the applicant for this building permit application, warrant the
truthfulness of the information provided on the application.
CIRCLE ONE: (OWNER) (CONTRACTOR) or (AUTHORIZED REPRESENTATIVE) of (OWNER) (CONTRACTOR)
Signature (first and last name):_ I /
Printed !Same: I U 11
ZONING COMMMENTS:
Reviewer:
BUILDING DEPARTMENT COMMENTS:
Reviewer:
PUBLIC WORKS COMMENTS:
Reviewer:
0 )" We'
DEPARTMENT USE ONLY
DATE: 14-03-19
OCCUPANCY CLASSIFICATION:
CONSTRUCTION TYPE:
Building Division Valuation:
i CITY OF WHEAT RIDGE
Building Inspection division
(303) 234-5933 Inspection line
(303) 235-2855 Office • (303) 237-8929 Fax
INSPECTION NOTICE
Inspection Type:
Job Address:
Permit Number:° ate.
❑ No one available for inspection:..Time f/__ AM/PM
Re -Inspection required: Yes No
When corrections have been made, call for re -inspection at 303 -234 -
Date: Inspector:
DO NOT REMOVE THIS NOTICE
City of Wheat Ridge
Residential Foundation Repair PERMIT - 201900222
PERMIT NO: 201900222 ISSUED: 02/05/2019
JOB ADDRESS: 12296 W 34th P1 EXPIRES: 02/05/2020
JOB DESCRIPTION: Residential foundation repair of 8 helical piers.
*** CONTACTS ***
OWNER (720)490-5865 LOWERS HEATHER
SUB (303)805-8751 Rodney Martin 060125 Complete Basement Systems
*** PARCEL INFO ***
ZONE CODE: UA / Unassigned USE: UA / Unassigned
SUBDIVISION CODE: 2403 / APPLEWOOD VILLAGES, PROSPECT V BLOCK/LOT#: 0 /
*** FEE SUMMARY *** ESTIMATED PROJECT VALUATION: 11,160.00
FEES
Total Valuation 0.00
Plan Review Fee 153.40
Use Tax 234.36
Permit Fee 236.00
** TOTAL ** 623.76
*** COMMENTS ***
*** CONDITIONS ***
Approved per plans and red -line notes on plans. Must comply with 2012 IRC, 2017 NEC and all
applicable City of Wheat Ridge Municipal Codes. Work is subject to field inspections.
I, by my signature, do hereby attest that the work to be performed shall comply with all accompanying approved plans and specifications,
applicable building codes, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized
by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with
thispermit. I further attest that I am legally authorized to include all entities named within this document as parties to the work to be
perform and that all wor o be performed is disclosed in this document and/or its' accompanying approved plans and specifications.
Signature f O or CONTRACTOR (Circle one) Date
I . This perimit was issued -the--infozmation provided in the permit application and accompanying Flans and specifications and is
subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, po Flans
and procedures.
2. This permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and
received prior to the date of expiration. An extension of no more than 180 days made be granted at the discretion of the Chief Building
Official and may be subject to a fee equal to one-half of the originalppermit fee.
3. If this permit expires, a new permit may be required to be obtained. Lssuance of a new permit shall be subject to the standard
requirements, fees and procedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of
the Chief Building Official and is not guaranteed.
4. No work of any manner shall be performed that shall results in a change of the natural flow of water without prior and specific approval.
5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all required
inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services
Division.
6. The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, any violation of any provision of any
a 5 able code or ordinance or regulation of this jurisdiction. Approval of work is subject to field inspection.
Signature of Chief Building Official Date
REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY
City of
ic e]�(��jrWheatR
OMMUN i TY DEVELOPMENT
Building & Inspection Services Division
7500 W. 29th Ave., Wheat Ridge, CO 80033
Office: 303-235-2855 * Fax: 303-237-8929
Inspection Line: 303-234-5933
Email: permitsLCcl)ci.wheatridge.co.us
FOR OFFICE USE ONLY
Date:
Plan/Permit #
1 �c
Plan Revie ee:
153`t
Building Permit Application
*** Please complete all highlighted areas on both sides of this form. Incomplete applications may not be processed. ***
Property Address: 12296 W. 34th PL
Property Owner (please print): HEATHER LOWERS Phone: 720-490-5865
Property Owner Email: HEATH ERLOWERS678(a)GMAIL.COM
Mailing Address: (if different than property address)
Address:
City, State, Zip:
Architect/Engineer: DL ENGINEERING
Architect/Engineer E-mail: KHOINESS(aD_DLENGINEER. Phone: 720-440-9450
COM
Contractor: Rod Martin's Complete Basement Systems
Contractors City License #: 60125 Phone: 303-805-8751
Contractor E-mail Address: kayla.montez(o-)_completebasementsystems.net
For Plan Review Questions & Comments (please print):
CONTACT NAME (please print): Kayla Montez Phone: 303-805-8751
CONTACT EMAIL(p/ease print):_ _kayla.montez(aD_completebasementsystems.net
Sys�u�`b Contractors:
Electrical:
W.R. City License #
Other City Licensed Sub:
City License #
City License #
Plumbing:
W.R. City License #
Other City Licensed Sub:
Mechanical:
W.R. City License #
Complete all information on BOTH sides of this form
❑ COMMERCIAL 9 RESIDENTIAL
Description of work: (Check all that apply)
❑ NEW COMMERCIAL STRUCTURE ❑ ELECTRICAL SERVICE UPGRADE
❑ NEW RESIDENTIAL STRUCTURE ❑ COMMERCIAL ROOFING
❑ COMMERCIAL ADDITION ❑ RESIDENTIAL ROOFING
❑ RESIDENTIAL ADDITION ❑ WINDOW REPLACEMENT
❑ COMMERCIAL ACCESSORY STRUCTURE (Garage, shed, deck, etc.)
❑ RESIDENTIAL ACCESSORY STRUCTURE (Garage, shed, deck, etc.)
❑ MECHANICAL SYSTEM/APPLIANCE REPAIR or REPLACEMENT
❑ PLUMBING SYSTEM/APPLIANCE REPAIR or REPLACMENT
❑ ELECTRICAL SYSTEM/APPLIANCE REPAIR or REPLACEMENT
$OTHER (Describe) Foundation Stabilization
(For ALL projects, please provide a detailed description of work to be performed, including current use of areas,
proposed uses, square footage, existing condition and proposed new condition, appliance size and efficiency, type and
amount of materials to be used, etc.)
F�vV(; wICk^ ''i b' g uC �l CCS i/-)
Sq. Ft./LF
Amps
Btu's Gallons
Squares Other
Project Value: (Contract value or the cost of all materials and labor included in the entire project)
$ 11,160
OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT
I hereby certify that the setback distances proposed by this permit application are accurate and do not violate applicable ordinances, rules or
regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown and allegations made are
accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance
with applicable City of Wheat Ridge codes and ordinances for work under any permit issued based on this application; that I am the legal owner
or have been authorized by the legal owner of the property to perform the described work and am also authorized by the legal owner of any
entity included on this application to list that entity on this application. 1, the applicant for this building permit application, warrant the
truthfulness of the information provided on the application.
CIRCLE ONE: (OWNER) (CONTRACTOR) or (AUTHORIZED REPRESENTATIVE) of (OWNER) (CONTRACTOR)
Signature (first and last name): i Og&.jmyk DATE: 02/04/2019
DEPARTMENT USE ONLY
ZONING COMMMENTS: OCCUPANCY CLASSIFICATION:
Reviewer.
BUILDING DEIARM T COMM
FTS:
Reviewer
r
0—
Building Division Valuation: $ 16-o
w N o E
Q N v I
Ln (U
N
-0 a)
a) 0 a)
3 3
aJ
.Q
y to M t1 t
Gl
0
+�+
`D —
°�
w 0 L
3 `; = t 3
3 0 v v
a) U v cO
a)
M
s C
°
O
o m
N C
+4--i
L-
++ U
i
L
M
f0 L
0 r, CU
Oa
2
'Aa M
~ E
a)
CL
N Vf v1
rn
a)
d
pp cn p
C
(0 0
d ++ 'a V
J 3
N CL
0
d 3'
O
.E
O t1
a)
L
y
°
Li
M = -,
0
�° N
ar
w 3
N
Z
0a) =
>- �
ra
L
~
N +., a)
V N V E
O
a) C
a
C
Z
(r
a LU a)
C O
0 W ��
y
V
V E N ty C
L p
W
0 t
L *'
E w
C >
Y
aj
a)
t
�
C
O
0 0 !
C '^ y 3 M
W
�. Vf `~
N
°
U a,
3
ao o
V
-e
�I L
a)
t
`L°
fl
%-
oma: - _
L3
u
a..i .0
a,
O— O
t
tw
�"
N
N C M 0z
N
Z
J
O> a)
>
L
a) (C
+'
CZ On
M a a) In,O
i
M
V a) N F C
CL
i
o
to
Q a)
N
�+ M
m C 3>
0
to .� w
x C
V
Y E
'�
c 3
a
o to On
3 ai �
CL
a
� d t o w
M
M t
E
`~ 0 M
M j �O
y
++
t eNo t M
`0
a)
t
N OA L
3
i— to
a) O—
N
3
3 t a+ 'a
'�
`L'
E
0
ate)
3 a)
o
c 3 0
0 `~ 3
t
N° O
om
t6
3 C)
E °
a)
�,
Y a 3
0 f°
°
a)
s t °
°3
o `t
(U°U
N
3
o r
;v
v
4-
CL
w
L
L
V
++
.E 3
E w C
d a)
> (O
OU -O (O
a
O a1
�o
t
r-�
_0 V
V
of E .0
4- M
4 O L
0 0°
t
C
to
cu O y
N
C
+' M s s4 E
"E �~ V
a
m
n X>
aJ
a) In
.00
0
3 •L
4-
L
a)
Y L
E a)
L L >—
a a�
is
0
0
a) t
++
C)
-p LO
on
a)
`� )
ON
a)
� 'L C
C C V
�
-1
3 +' to +� ~
0
C
N16
L
U
a)
C
0 'p
3
CL
M In4-
aa)
>
o >>>
N
M a
a)
d U
3
3
O
W
N U L
CL
U
U
U U Y
f�0
tw w 3 d
'>
00
00
fa
•a)
,tn
0
~
In M to
r-1 O
i'
N
OU +' O
c
Q
° L +-
U
L
3
t
t0 ++ V N
oo ai C
!-1
tr
�, -
H
°
OU
o
LL
°
OCA
0 o
to OCA
0 0
OCO OCo
�o
"
a) ab M .0
t
E
)
N LD
m �
C
O
a)
o
L
C
0
4, t- � N
E
—
t
!C
*C a
M a)
vi
:Z
O
3
O
a)
+� Q=
L
N
C
Y
U
1Z Y
M 1Z U
Y ,L tZ
U U tz
Y
U
y
40 +.
0 C y
V
O N L
N ri O
U t
U
° -0
°
"
N 4O+ .
. (La a)
(L6
to
E
C t "
rn -, ri
a) C 'O
! L
C
C
3
++
U
in Ln U
U U cn
U
C
0 +1 x
r" 1
C
3 O °
Cr
O
3
O
i
3 iN
°
L
N
M
i
07
E
a,
°
C14v
M
CU
CU
ai M+�
3
W
to -0 �^
L v
y
L 0Z
O
-0
0
w� N=
N w
Q m >
F— C
-,
;
H- M >
L
O
•
• • •
• • •
•
U
Q
to to 0 O.
M
r -I
Inspection by Wheat Ridge Building
Inspector required prior to backfill.
Observation letter from Engineer
required to be provided to Wheat
Ridge Building Inspector at Final
Inspection.
CIiY Of
" cWheat
CoMMUNrrY UEVELUPMENT
APPROVED
Revie for e C pliance
I /4zi z
Plans aminer Date
5Nt�4�► of oero�N 7be tssemtce of t Pwmlt or approval of plans specifkaftont
and cgtt"tallont shah not be a pemut/br, or an aWovW of, orry vrol000n to
aw of the prowslmu of the bw'V&V code or of any aty ardManwS. ptrM t
PWSW unp to phot Ow" to rtaloar or cowl the provakft of Hit #,Ai tg
Caft or othN awwwult of owmySwfw bevohal
> M Ln ODE {�.� L L >, (U QJ N Mt)D i -a t
3MD
O N •� 4--i •�- Q L L a� N
N
u a C -a fII ++ v N N ° l0 t ° O LnC
0 0 r, v o "p C E — O = C N
c
C)
3 `� > O� LL L ( U O -O -0 O
rn J3 p N GJ O 4-; m C O m M O O
v
3 4- -O Q `� } y -0 b0 L O
OD >
0 0-0 CO E E r6 C O O C O C
L1 N f6 .N > O N L L
Z C L = Ccu mO 0 7 y i p o N
U E S N to E E O p L N :
O p o N0 -Z — O N O p
O C +� U u W N u Q m Q' U
W '� O .o O tf I � J D N O N C
Z L O N i N O G1 U L 0 N .� a�
W > -O `� h0 tU0 hpD C N O aL+ V Q N C O
J > C (U N L •- L to > U id C O
N i O m +
❑ 0 3 03 0 p = U G1 U L O O O N vOi •� C M
N f0 N `~ O C L C -O N ++ C -O >• M
L 4••+ 4F C -CU M O C Q L O L N (d O w H v p 0
U C `�' L GJ > > }' N •Vf p >
`L° Y •l0J N
y
jN tf
O
N OO O Q? C N °O
0� E E u c hA m m O
Q •iO
y ° O +-O E O
NO
m dA
C GO
IrZ
N >, 4+ L -- C C .Y E f6 3 L m >� L M •C f0
N — vi
O N O a U 4-;-a 3 L 4-- Q C O >
++ O° 41 (a C � N +J N O w 7� N m -O tw Gl
O L
c E w x E E o w o w c c in m U 3 a—Ni o f in
Lii i > E E C
IA (u ME- J
N LOO m N >7 > M N6 N M
o o ° Q ' EC m °° �tai m t C
4-0
L E C1 C ++ L
d o a, o
°�° > E E a c o = o CL w
L +j
c N
(M
C
° Q ai d
oC H E .E Q"' ri • • • C7 • C9
� � L
O cu Q +O+
N C
of
`^ O c
41 E
-
Q C 41
> p Y
N 4- p
t/f
-0 O
O L N
L
N p 4O•+
L1 V1 N fC
v cu 3
L
C U o
(6 N
o
� L
N C E '_O
C L 4- 3
O N O
o
c
N O
o �a
E
� C
c L
p 0cu
C CU
L pA f6
C
U -0 X N N
p N U
X
a�
v E -o a� v
N r-+ > lC +-+
> >, O E O
N E m -a
� C N -0 C
c O L L m
(u +, O v,
L
a, -0 U
3
3 ii
O vm
E ,° u --a a
N
City Of
Wheat R: dge
Di�•iso^,,.
U
Z
Li
z
T
w
w
Z
L)
Z
w
J
M
city of
Wheat Ridge
ing
Q' N a o
O Oioo
u
3 0 a v
v v a c
o to
o N C
O1 Y
_`4 3
U
z
Li
z
It
W
W
z
LD
z
LU
J
City Of
Wheat Ridge
N a
_ o m u
3 0 v v
v U v c
O Nto
C
O O ^ d
O
Ol Y
J
Li
a
Ln
City o f
VVheat Ridge
U
z
u
z
w
w
w
z
Ll
z
w
J
T]
city of
\Nheat Ridge
U
z
u
z
it
w
w
u
z
w
J
ZZ
3
C3
C3
v
i
v
N
C
v
Y
U
i
a
Y
U
a
U
rmv
i
r
Li
n
City of
Wheat Ridge
U
z
Li
0
City of
Wheat Ridge
U
z
u
z
Fr
W
W
z
LD
z
W
J
City of ,
Wheat Ridge
O
z
Li
"
o
0
M C
\
)
6
\
/
k
/ [
/
Ln
/
§
0
7 °
#
c
[
y
ƒ
=
o
2 Q
o
Ln
O 2
»
m
2
@
� 7
�
0
3
E
S
maa�E
f
m
0
0 2¢
0
4_
0
•-
CLO
-
+
a
cu3
—
o
�
CLO
\
//E32�
£
2
® _@
k
7
®°u/
@
�2£f£
q
o
m
•-
(
2
/
/
k §
/G/q
_a
_
2 7
—
g
0
S
=
/
2
-o
/
�
/0
M
C3
//
tw
$
a)
o-0
»
M o
E
/ /
/
/
)
�
/
�
5
G
o'
_ _
aj
a)
(
0
to /
t@
3
E o
3'
°�
0-
m
2
§
£
n §
f
a %
�E°f7f7
ƒ
Ln
6
J
0
4-
E §
4-
\
2
ƒ
/
�
m
�
�
§
f
4-
c c
ai
m
�
/
/
\
4-
■
�
2
\
INDEX:
S1-1 GENERAL NOTES
S1-2 GENERAL NOTES/LEGEND
S2-1 FOUNDATION PLAN
S3-1 TYP. HELICAL PIER DETAIL
BUILDER INFORMATION
Complete Basement Systems of CO
11795 East 45th Ave
Denver, CO 80239
1-303-219-7646
General Notes:
1. Construction documents are valid for a single use at the project location and shall not be reused, copied, or
reproduced without written approval of the registered design professional in reasonable charge.
2. The contractor is responsible for the methods, means and sequence of all structural erection except when
specifically noted otherwise in the construction documents. The contractor shall provide temporary shoring and bracing,
providing adequate vertical and lateral support during erection. Shoring and bracing shall remain in place until all
permanent members are placed and all final connections are completed.
3. The contractor agrees that, in accordance with generally accepted construction practices, the contractor will be
required to assume sole and complete responsibility for job site conditions during the course of construction of the
project, including safety of all persons and property. This requirement shall be made to apply continuously and not be
limited to normal working hours. The contractor further agrees to defend, indemnify and hold owner and engineer
harmless from any and all liability, real or alleged, in connection with the performance of work on this project, exempting
liability arising from the sole negligence of engineer.
4. All existing sizes, dimensions and foundation damage shall be field verified by the contractor and owner prior to
construction. Discrepancies with the construction documents shall be reported to the structural engineer for additional
recommendations (if any).
5. Per the owner's request, the contractor shall stabilize the structure only. No attempt shall be made to lift or plumb
the foundation wall without approval for the owner and structural engineer.
Field Verification:
1. Contractor and Owner shall thoroughly inspect and survey existing structure to verify dimensions, elevations,
framing, etc. which affect the work shown on the drawings.
2. Report any variation or discrepancies to the structural engineer before work proceeding.
Foundation Design:
1. Soil conditions and types shall be verified by a Geotechnical Engineer during excavation.
2. Follow all recommendations of the Geotechnical Engineer for foundation elements.
3. All helical piles, push piers, helical anchor tiebacks, wall anchor tiebacks and connection hardware shall be
designed and installed by supplier, such that they provide the minimum allowable capacities as indicated on the
drawings. All capacities shown on the drawings are unfactored service loads and have not been reduced for live load
reductions.
4. All steel for helical piles, push piers, helical anchors tiebacks, wall anchor tiebacks and
connection hardware shall be hot dip galvanized.
5. Design of individual and continuous footings is based on a maximum allowable bearing pressure of 2000 lbs. per
square foot (dead load plus full live load), placed on the natural undisturbed soil, or compacted structural fill below frost
depth.
Design Criteria:
1. Building code: 2012 IBC, 2012 IRC with City of Wheat Ridge Amendments
2. Dead loads
2.1. Roof 20psf
2.2. Floor 10psf
2.3. Walls 10psf
3. Live loads
3.1. Residential40psf
3.2. Roof 20psf
4. Snow loads
4.1. Ground snow load 30 psf
5. Wind loads
5.1 Exposure Category C
5.2 105 mph 3 -Second Gust Wind Speed
Cast -in -Place Concrete
1. All concrete design is based on the "Building Code requirements for Reinforced Concrete" (ACI 318-05/318R-05)
All structural concrete shall have a minimum 28 -day compressive strength as follows:
1.1 Footings:3,000psi
1.2 Slab on Grade: 3,500psi
1.3 Foundation walls: 3,000psi
2. Concrete shall be placed on proportioned utilizing Type 1 cement except, concrete exposed directly to soil shall
use Type 2 cement. Concrete susceptible to freeze shall be formulated or maximum frost resistance in accordance with
the ACI
manual of Concrete Practice.
3. Cold weather and or hot weather placing procedures shall be provided, if conditions warrant, as recommended in
the ACI manual of Concrete practice.
Reinforcing Steel:
1. All detailing, fabrication, and placement of reinforcing steel shall be in accordance with the ACI Manual of Concrete
Practice.
2. Reinforcing bars shall conform to ASTM A615-79 and shall be grade 60.
3. Except as noted on the drawings, minimum concrete protection for reinforcing shall be in accordance with ACI
318-05/318R-05.
4. No. 5 or larger reinforcing bars shall not be re-bent.
5. Welding of rebar is not permitted unless procedure is approved by the Structural Engineer.
Structural Steel:
1. Structural Steel shall be detailed, fabricated and erected in accordance with 2010 AISC Specification for Structural
Steel Buildings, and "Code of Standard Practices" 2005.
2. Structural Steel shall be confirmed to the following grades:
2.1 W- & WT- Shapes: ASTM A36, A992
2.2 Plates & Angles: A36
2.3 HSS: ASTM A500 gr B
2.4 Steel Pipe: ASTM A53 gr B
3. All bolts shall conform to the ASTM A325 except anchor bolts which shall conform to ASTM A307. Bolt Size shall
be %", unless noted otherwise on the drawings.
All welding shall be by a certified welder in accordance with ACIS and AWS specifications and recommendation.
Structural Wood framing:
1. Except where noted otherwise, all 2" members shall be Hem -Fir No. 2 and better.
2. Except as noted otherwise, minimum nailing shall be provided as specified in Table No 2304.9.1 "Fastening
Schedule" of the IBC. All nails shall be common type, unless noted otherwise.
3. Unless noted otherwise, steel connectors such as those manufactured by Simpson Company, shall be used to join
rafters, trusses, joists, or beams to other members at flush -framed conditions. Use maximum number and size of nails
indicated in manufactures tables U.N.O. all nails holes shall be filled.
4. All multiple members shall be glued & nailed together.
5. All wood in contact with concrete or exposed to weather, shall be pressure treated Douglas Fir -Larch No. 2 or
equal.
Structural members shall not be cut for pipes, etc. Unless specifically noted or detailed.
Periodic surveys:
1. Periodic surveys of the supported structures should be conducted to assure project success. The Owner should
be responsible for annual surveys certifying project success. We would suggest that a
baseline survey be conducted immediately. The owner shall submit all findings and
reports to the Structural Engineer. K
2. If vertical movement of the piers is discovered, the piers should be o m m
re -pressured. A representative of the Geotechnical Engineer should be present to ,.y E. HpZ•., d'
observe the re -pressuring. A final report should be provided by the Geotechnical • '.`' 4'F'. F4
Engineer after observing the re -pressuring. a0cA:
0054409
ass/ONA1_ E�G�
EXP. 10/31/19
REVISIONS
0
0
N
U)
N
Z31V0
J
A
w
WAS
0 A03H0
2
Y
A8
r
Z M
O th
0
Qd�Z
QMWJ p
H3cd
Z0aZ
Q P C4
W O
Z 3
n
L6
LU
N
Z_ >LO LU
N V
ZJO4Lu
rkW00)Z
ZWp Z
O0J
Z33tic
W O
SCJ
JOB NO.:,
2019-58$3
1-1
OF
4
6 L/ L £/0 L 'dX3
R
G
Z-
133HS' �ln� •' •• a
OZ
dor
mvz
v
v N
0
Z Ah M
�p :EM
z(b ME
mah0rZ
M�oa�
0 NM0
3 N'
60VVS00
.0
pap!Ao.id
aney OM saouuas leuo!ssajoid ay} }o }no bu!sue sw!elo Ile pue Aue }su!e6e pue wa; J99u!6u3 pua}ap pue AJ!uwapu!
'sselwjey ploy Ilion }ua!10 ay} 'MuOu3 ay} }o lied ay} uo aoua6!l6au jo; }daoxe ' ley} saaj6e }ua110 ay} '6u!pl!nq
ay} ;o suo!}jod algeaouuas jo a}enbape asiAuay}o 6uiAoi}sap jo Aauow;o swns leuog!ppe 6u!puadxa }noy}!M algeguaA
aq lou Aew suo!}dwnsse asay} }o awos asneoaq pue suo!}!puoo Bu!}s!xe buipie6ai spew aq suo!}dwnsse u!e}jao ley}
seiinbei suo!}!puoo ain}onj}s ay} 6u!Ajesgo jo asodind ay} ao; ain}onu}s 6U1}SIXa ue }o M9IA9J a}!s ay} se yonw se ul 6
:Jaw!elosla
O0
-way} asn lou Aldw!s jo swa}sAs
u01je6un 6UTA0waa
vjap!suoo
pinoys jauMO ayl '6u!Ae9y Jo pue 6u!l}}as u! bui}lnsai Alq!ssod 'ajn}s!ow pa}uennun oonpoi}ul ueo sain}ons}s
0 m
o} }ueoelpe ain}s!ow aAISSaoxa pue swa}s�(s uo!}e6!.Ul 'uo!}epuno; ay} punoie 6u!}ea}Igui ain}s!ow }o �(}!l!q!ssod ay}
a N
:E
aonpaa o} papei6 Aliadoid pue pa}eu!w!la aq pinoys aa}eM u!e}ai pinoo yo!yM sain}ea; eoe}jns jay}o pue sia}ueld Z
-wa}sits uo!}epuno; 6u!}s!xe ay} 96ewep
zA to p
z
-Ieuo!ssajo.id
jo gjn}s!p jay}jn; lou o} ua� e} aq pinoys aje0 peouauadxa ue �tq panowaj Apn}ajeo aq pinoys saai}
v y
m a
pue sgnjys 'saysnq
'i -wa}sAs
r w
0-
s!a ay} aonpai o} japio ul uo!}epuno; ay} uo amssaid aAlssaoxa a}Mo pue I!os ui ain}s!ow ploy ueo uo!}e}a69n
to
* 0 r
s}uawanow uo!}epuno} o} peal AIlen}uana ueo sam}onu}s ;o ia}awuad ay} punae uo!}e}969A ley} ana!Iaq aM . L
M0=—
N
uo!}e}969A a}!S
co)co
C r -1
-a.in}onj}s ay} woi; Menne }aa; 06 }o wnw!u!w a abjeyos!p su!ejp }oar pue s}nodsunnop uo!}oun} � liedoid
�w 0
o} payoe}}e
z
aq pinoys u0lsua}x3 'papuawwooaa Albuw}s We swa}sAs 96eu!ejp ooe:pnsgns/aoejjns pue salenns 'sja!jjeq ain}s!ow
2131d NO GVOI
( )'d'H
'apej6-uo-sgels adols jado.id ;o asn ayl -Aenne u!ejp AlNo!nb ll!M suo!}e}!d!oeid ley} yons pau!e}u!ew aq }snw ain}oni}s
# 2}31d —��
ay} punoie
a6eu!ejp 9}!s ley} uo!u!do ino s! }I -pe/uasgo 96ewep uo!}epuno; o} jo}oe; 6u!}nqu}uoo a u94o si a6eu!eap jadoid }o ipe-j
BY
2i31d �`d01�3H
'bu!pl!nq ay} jo ej!I Injasn ay} ao; palloi}uoo aq }snw s}uawale uo!}epuno; punoie ain}s!ow ay} ley} ana!Iaq aM ' 4
=
G)
2131d NO GVOI
($Wcxxx)
a6eu!eaa a}!S
uo!}do i!edej s!y} ansind o} 9� !I
:HECK
BY
mx#
# 1SOd 'd'W
lou pinoM
v
m m
1SOd ONOW ��
aaunnO ay} ley} 6u!pue}s�apun ono s! }l }uawanow pue a6ewep uo!}epuno} asn}n;;o �{su ay} aonpa� �l}ea�6 pinoM 'AI}soo
r
m >
'b'M
ajow y6noy}le 'a!edaa wa}sols Iejaua6 y -pa}e6!}!w aq pinoo uo!}epuno} an}ua ay} 'os op o} sasooyo jaumo ay} }I Z
Z
# 2JOHONV — x#
-1]VM ��
-eiagmesle
DATE
O 0
�
HOHONV
2i31d NO a`d0� —��
an000 ll!M
s}uawanow uo!}epuno; ley} elq!ssod s! }! 'suo!}en}!s og!oeds ssaippe Il!M s!y} y6noy}ly 'pa}ea}uaouoo s! }uawanow aJayM
.
h)
sews ue I pa6ewep Alq!s!n }e Aluo paz!l!ge}s aq pinoo uo!}epuno; ay} os op o} sasooyo iaunno ay} ;l
p } suo! eoo 6
N
p
(#xxxx)
'd'd
-}soo pue '96ewep aan}n;;o A}!I!q!ssod ay} 'Nsu jo;
L
�p
# H31d X#
831d Hsnd ��
aouejalo} i!ay} uo puadep Il!nn pue jeuMO ay} Aq pajap!suoo Allnjejeo aq pinoys sj!edej uo!}epuno} ay} ;o ss9u9A!ssaa66e
'sNoejo '6u!Aeay
pue }ua}xe ayl -asdelloo IleM uo!}epuno; alq!ssod pue Aliedoid 6uluo!}oun; lou snnop!NVsjoop Al}y6!sun
M(N)
'Buil}}as jegpn; u! bu!}Insai (uaile} si uo!}oe ssalun)
JNIlSIX3 X3 (3)
os o} anu!}uoo �tla�I!l IIIM }! '6UTAow su!6eq ain}onu}s a aouo ley} eoua!jadxa ino uaaq sey }! 'ajowaay}jn j -Al}soo pue
}lnoyp ajow medal ajn}n} ajew A19N!I IIIM uo!}e6!}!w 6u ftlap 'i su piezey pue y}leay
-_
dN303l
a}e!pawwl ue asod lou saop Alleo!dA} 96ewep uo!}epuno; paAiasgo y6noy}Iy .6
:uogez!l!ge}S uo!}epuno3
--
0
31VG
SNOISIA3N
Q,
FOUNDATION PLAN
F
z
O Mo
N IL
JFV3
WOJ
H3od
z9z
3
C4 4 Q W O
z 3
0
O
�
N �
REVISIONS
z_ > N 0
Q C
CD
DATE
NOTES:
Z�CD
Oq*z
1.
SEE SHEETS S1-1 THROUGH S1-3
WO9
O —'
acJ
H
� • y �. ��
�•"\' tib.'
FOR GENERAL NOTES.
JOB NO.
�U cP • O
2019-5883
s
AO • �w�
SHEET
2. INSTALL HELICAL PIERS PER PLAN.
3.
THE EXISTING PROPERTY LINES
��..
EXP. 10/31/19
■ 4 ■
AND EXISTING HOUSE LOCATION
ARE SHOWN AS DRAWN ON THE
JEFFERSON COUNTY ASSESSOR'S
o
PARCEL MAP. FOUND ON
Z
C4
http://www.co.jefferson.co.us/assr/pdf/pmap39-291.pd
a
N
4.
FOR EXACT LOCATION OF THE
HOUSE ON THE PROPERTY, A LAND
O Siva
SURVEYOR SHOULD BE ENGAGED
J
FOR A MORE ACCURATE
p
ASSESSMENT.
Z
D
A8
0
A3Hu—
F
z
O Mo
N IL
JFV3
WOJ
H3od
z9z
3
C4 4 Q W O
z 3
0
O
�
N �
z_ > N 0
Q C
CD
zJO40{Y
a: Lu z
L03: -a -
Z�CD
Oq*z
OaJ
Z33ho
WO9
p,p0L/C
acJ
H
� • y �. ��
�•"\' tib.'
JOB NO.
�U cP • O
2019-5883
0054409
AO • �w�
SHEET
'� '• '•
o„ V. MSONAL ANG
1
��..
EXP. 10/31/19
■ 4 ■
i CITY OF WHEAT RIDGE
Building Inspection Division
(303) 234-5933 Inspection line
(303) 235-2855 Office • (303) 237-8929 Fax
INSPECTION NOTICE
Inspection Type: `�C v.� �' ^ �� r ���r C. h
Job Address:
Permit Number: rr
c.
LI -No one available for inspection: Time '-I'/ (-) AM/PM
Re -Inspection required: Yes No
When corrections have been made, call for re -inspection at 303-234-5933
4
Date: �� `' i Inspector:
S
DO NOT REMOVE THIS NOTICE
City of Wheat Ridge
fiy
,. Residential Sewer Repair PERMIT - 201900162
ix
PERMIT NO: 201900162 ISSUED: 01/25/2019
JOB ADDRESS: 12296 W 34th P1 EXPIRES: 01/25/2020
JOB DESCRIPTION: Residential sewer repair 80 feet from house to tap in street, install clean
outs in yard.
*** CONTACTS ***
OWNER (720)490-5865 LOWERS HEATHER
SUB (303)856-7476 Jacob Wakeham 140058 Dig Boss LLC
*** PARCEL INFO ***
ZONE CODE: UA / Unassigned USE: UA / Unassigned
SUBDIVISION CODE: 2403 / APPLEWOOD VILLAGES, PROSPECT V BLOCK/LOT#: 0 /
*** FEE SUMMARY *** ESTIMATED PROJECT VALUATION: 4,675.00
FEES
Total Valuation 0.00
Use Tax 98.18
Permit Fee 125.05
** TOTAL ** 223.23
*** COMMENTS ***
*** CONDITIONS ***
ALL sewer repair/replacements for which a permit is issued MUST be inspected by and receive
written approval from the City of Wheat Ridge BUILDING DIVISION, regardless of inspection
by any Sanitation District representative. Inspection and approval of work by any
Sanitation District representative DOES NOT grant authority to cover work without the
approval of the Building Division.
**For trenchless sewer replacements - The contractor will verify proper slope of new sewer
piping in conformance with the IRC and IPC of 1/4 inch per foot unless otherwise allowed
specifically by the applicable code. The plumbing contractor will provide verification of
proper slope and drainage in writing as a condition of approval of the permitted work.**
City of Wheat Ridge
Residential Sewer Repair PERMIT - 201900162
PERMIT NO: 201900162 ISSUED: 01/25/2019
JOB ADDRESS: 12296 W 34th P1 EXPIRES: 01/25/2020
JOB DESCRIPTION: Residential sewer repair 80 feet from house to tap in street, install clean
outs in yard.
I, by my signature, do hereby attest that the work to be performed shall comply with all accompanying approved plans and specifications,
applicable building codes, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized
by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with
this_permrt. I further attest that I am legally authorized to include all entities named within this document as parties to the work to be
performed arld thal all work t pertormed is disclosed in this document and/or its' accompanying approved plans and specifications.
Signature of OWNER or CO CTOR (Circle one) Date
I. This permit was issued based on the information provided in the permit application and accompanying plans and specifications and is
subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures.
2. This permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and
received prior to the date of expiration. An extension of no more than 180 days made be granted at the discretion of the Chief Building
Official and may be subject to a fee equal to one-half of the originalpermit fee.
3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard
requirements, fees androcedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of
the Chief Building Official and is not guaranteed.
4, No work of any manner shall be performed that shall results in a changeof the natural flow of water without prior and specific approval.
5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all required
inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services
6. Th ' suance or gra f g of a permit shall not be construed to be a permit for, or an approval of, an violation of any provision of any
9a li ble code or ordinance or regulation of this jurisdiction. Approval of work is subject to field inspection.
Signature of Chief Building Official Date
REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY.
City of
W heat Edge -
COMMUNITY DEVELOPMENT
Building & Inspection Services Division
7500 W. 2911 Ave., Wheat Ridge, CO 80033
Office: 303-235-2855 * Fax: 303-237-8929
Inspection Line: 303-234-5933
Email: permits(a)-ci.wheatridge.co.us
FOR OFFICE USE ONLY
Date: 1 / �S //
Plan/Permit #
�0 /1
Plan Review Fee:
Building Permit Application
*** Please complete all applicable highlighted areas on both sides of this form.
Incomplete applications may not be processed. ***
Property Address: W71n W ��Ll 42� /Li
Propertv Owner
Property Owner Email:
Tenant (Commercial Projects Only)
Property Owner Mailing Address: (if different than property address)
Address:
City, State, Zip:
Architect/Engineer E-mail: Phone:
Phone:
Contractor Name: 0 9 ,(jGZL1 /l
City of Wheat Ridge License #: f `/' / 70062 Phone: J
? JTL — 7y21�
Contractor E-mail Address: &1610104QA&14ta(�,� kur,wm
For Plan Review Questions & Comments (please print): �)
CONTACT NAME (please print): Te ra, Phone:
- 5r�
CONTACT EMAIL(p/ease print): L�
Sub Contractors (Must provide Wheat Ridge License No & Signed Subcontractor Authorization form):
Electrical: Plumbing: Mechanical:
W.R. City License # W.R. City License # W.R. City License #
Other City Licensed Sub: Other City Licensed Sub:
City License # City License #
Complete all fields. This is required information.
❑COMMERCIAL
1;4RESIDENTIAL
Provide description of work: For ALL projects, provide a detailed description of work to be
performed, including current use of areas, proposed uses, square footage, existing condition and
proposed new condition, appliance size and efficiency, type and amount of materials to be used, etc.
8d' sNerGh& �G�� Act-, kC4X' A �Qp ,h C=%re�
/n sial/ d(41-\ou�i �h �c rn�
Sq. FULF
Amps
BTUs
Squares
Gallons
For Solar: KW t1! of Panels
For Commercial Projects Only: Occupancy Type: Construction Type:
Occupancy Load: Square Footage: _
Project Value: (Contract value or the cost of all materials and labor included in the entire project)
$ '7.(S-
OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT
I hereby certify that the setback distances proposed by this permit application are accurate and do not violate applicable ordinances, rules or
regulations of the City of Wheat Ridge or covenants, easements or restrictions of record: that all measurements shown and allegations made are
accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance
with applicable City of Wheat Ridge codes and ordinances for work under any permit issued based on this application; that I am the legal owner
or have been authorized by the legal owner of the property to perform the described work and am also authorized by the legal owner of any
entity included on this application to list that entity on this application. 1, the applicant for this building permit application, warrant the
truthfulness of the information provided on the application.
CIRCLE ONE: (OWNER) (CG
Signature (first and la77,1
e):Printed Name: l
ZONING COMMMENTS:
Reviewer:
BUILDING DEPARTMENT COMMENTS:
Reviewer:
PUBLIC WORKS COMMENTS:
Reviewer:
or (A47HORIZED REPRESENTATIVE)
DEPARTMENT USE ONLY
of (OWNER) CONT CTOR)
DATE: g
OCCUPANCY CLASSIFICATION:
CONSTRUCTION TYPE:
Building Division Valuation:
City of
Wheat�idge
COMMUNITY DEVELOPMENT
City of Wheat Ridge Municipal Building 7500 W. 29" Ave
F: 303.237.8929
May 23, 2018
Owner/Occupant
12296 W. 34th Place
Wheat Ridge, CO 80033
Wheat Ridge, CO 80033-8001 P: 303.235.2855
RE: Previously permitted project plans available for retrieval — Permit 201700884 (Residential
Remodel)
Owner/Occupant,
This letter is being sent to you because a project for which a permit was issued by the City of
Wheat Ridge Building Division and plans and/or other documents were required was recently
completed and approved. In accordance with the Building Division's document retention policy,
the associated plans and/or other documents are scheduled for disposal.
We are writing to offer you an opportunity to retrieve those approved plans and/or documents
prior to their disposal by the Building Division. The plans and/or documents are available for
retrieval for a period of 20 working days (4 weeks) from the date of this letter — June 20th — and
must be retrieved in person at the Building Division offices. This letter must be presented at
the time of retrieval of the plans and/or documents. Plans and/or documents available for
retrieval CANNOT be mailed and plans and/or documents will NOT be available for retrieval
after the expiration of the retrieval period.
You may retrieve plans and/or documents between the hours of 7:30 a.m. and 3:30 p.m., Monday
through Friday, at the Building Division offices located at 7500 W. 29th Avenue in Wheat Ridge.
Cordially,
Kimberly Cook
Permit Technician
7500 W. 29th Avenue
Wheat Ridge, Colorado 80033
Office Phone: 303-235-2873
Fax: 303-237-8929
www.ci.wheatrid eg co.us
City of
Wheat 1 -ge
COMMUNITY DEVLLOPMEN-1-
www.6wheatridge.co.us
�617�S _(F-6 iK
INSPECTION RECORD Octuvancv/Tvm
INSPECTION ONLINE FORM: http://www.ci.wheatridge.co.us/inspection
INSPECTION REQUEST LINE: (303) 234-5933
Cancellations must be submitted via the online form before 8 a.m. the day of the inspection
Inspections will not be performed unless this card is -p sted on the project site.
**Request an inspection before 11:59 p.m. (midnight) to receive an inspection thh following business day.**
Inspector Must Sign ALL Spices pertinent to this project
Foundation Inspections Date
Insp ctor Comments
Initi
Pier
r
Concrete Encased Ground (CEG)
-
Foundation / P.E. Letter
Mid -Roof
Do Not Pour Concrete Prior To Approval Of The Ab ns tion
Underground/Slab Inspections Date InspectorComment
Initials
Electrical
Sewer Service
Plumbing
Do Not Cover Underground or Below/In-Slab Work Prior To Approval Of The Above (Ln�ections
Rough Inspections
Date
Inspector
Initials
Comments
Wall Sheathing
Mid -Roof
r r
Lath / Wall Tie
Rough Electric
Rough Plumbing/Gas Line
Rough Mechanical
Rough Framing
Rough Grading
Insulation
Drywall Screw/ Nail
Final Inspections Date
Inspector
Initials
Comments
Landscaping & Parking / Planning Dept.
Inspections from these entities should be requested
one week in advance. For landscaping and parking
inspections call 303-235-2846. For ROW and drainage
inspections call 303-235-2861. For fire inspections
contact the Fire Protection District for your project.
ROW & Drainage / Public Works Dept.
Floodplain Inspection (if applicable)
Fire Inspection / Fire Protection Dist.
Final Electrical
Final Plumbing
Final Mechanical
Roof
Final Window/Doors
Final Building
NOTE. All items must be completed and approved by Planning, Public Works, Fire and Building before a Certificate
of Occupancy is issued. Approval of the Final Building inspection does not constitute authorization of occupancy.
"For low voltage permits — Please be sure that rough inspections are completed from the Fire District and electrical low voltage
by the Building Division.
Occupancy Is Not Permitted Until A Certificate of Occupancy Is Issued
Protect This Card From The Weather
C
�WFLINSPE ITIOD�N�R CORD
INSPECTION O INE FORM: http://www.ci.wheatridge.co.us/inspection
INSPECTION REQUEST LINE: (303) 234-5933
Occupancy/? ype
Inspections will not be performed unless this card is posted on the project site.
**Request an inspection before 11:59 p.m. (midnight) to receive an inspection the following business day.**
Inspector Must Sign ALL Spaces pertinent to this project
Foundation Inspections Date Inspector Comments
Initials
Pier
Concrete Encased Ground (CEG)
Foundation / P.E. Letter
Do Not Pour Concrete Prior To Approval Of The Above Inspections
Underground/Slab Inspections Date
Inspector Comments
Initials
Electrical
Comments
Sewer Service
Plumbing
Do Not Cover Underground or Below/ - ab Work Prior To Approval Of The Above Inspections
Rough Inspections
Date
Inspector
Initials
Comments
Wall Sheathing
Mid -Roof
Lath / Wall Tie
Rough Electric
At-ff2 L
Rough Plumbing/Gas Line
Rough Mechanical
Rough Framing
Rough Grading
Insulation
Drywall Screw/ Nail
r �,
Final Inspections
Date
I spector
Initials
Comments
Landscaping & Parking / Planning Dept.
Inspections from these entities should be requested
one week in advance. For landscaping and parking
inspections call 303-235-2846. For ROW and drainage
inspections call 303-235-2861. For fire inspections
contact the Fire Protection District for your project.
ROW & Drainage / Public Works Dept.
Floodplain Inspection (if applicable)
Fire Inspection / Fire Protection Dist.
Final Electrical
Final Plumbing
Final Mechanical
l
RAIL -
Roof
Final Windnw/Doors
Final Building
t� .. . I
��oy►�,
NOTE: Al. -items must be completed and approved by Planning, Public Works, Fire and Building before a Certificate
of Occupancy is issued. Approval of the Final Building inspection does not constitute authorization of occupancy.
For iow voltage permits - Piease be sure that rough Inspections are completed from the Fire District and electrical low voltage
by the Building Division.
Occupancy Is Not Permitted Until A Certificate of Occupancy Is Issued
Protect This Card From The Weather
v City of Wheat Ridge
` Residential Remodel PERMIT - 201700884
?ERMIT NO: 201700884 ISSUED: 07/10/2017
TOB ADDRESS: 12296 W 34th PL EXPIRES: 07/10/2018
TOB DESCRIPTION: Interior Remodel - kitchen remodel, main floor bathroom remodel, basement
bath remodel, add 1/2 bath in basement, rework basement closet, new gas
fireplace, 3 new egress windows, reconfigure basement stairs
` CONTACTS ***
OWNER (720)490-5865 LOWERS HEATHER
3UB (303)500-3103 Ad4m & Julie Rossi
3UB (720)490-1533 David Capune
3UB (720)394-2363 Robert Fleming
3UB (303)598-8617 Michael J Lind
130036 Blue Sky Remodeling
090309 High Quality Plumbing Inc.
090151 Royal Comfort Heating & A/C
170368 Red Rock Electric
k** PARCEL INFO ***
7,ONE CODE: UA / Unassigned USE: UA / Unassigned
SUBDIVISION CODE: 2403 / APPLEWOOD VILLAGES, PROSPECT V BLOCK/LOT#: 0 /
*** FEE SUMMARY *** ESTIMATED PROJECT VALUATION: 81,345.00
FEES
Dotal Valuation 0.00
Plan Review Fee 641.65
Jse Tax 1,464.21
Permit Fee 987.15
** TOTAL ** 3,093.01
*** COMMENTS ***
*** CONDITIONS ***
All roughs to be done at Framing Inspection.
Approved per plans and red -line notes on plans. Must comply with 2012 IRC, 2014 NEC and all
applicable City of Wheat Ridge Municipal Codes. Work is subject to field inspections.
Occupancy/Type
J INSPECTION RECORD
INSPECTI N ONLINE FORM: http://www.ci.wheatridge.co.us/inspection
v^ P IJt,/ INSPECTION REQUEST LINE: (303) 234-5933
inspections will not be performed unless this card is posted on the project site.
**Request an inspection before 11:59 p.m. (midnight) to receive an inspection the following business day.**
Inspector Must Sign ALL Spaces pertinent to this project
Foundation Inspections Date Inspector Comments
Initials
Pier
Concrete Encased Ground (CEG)
Foundation / P.E. Letter
Do Not Pour Concrete Prior To Annroval Of The Ahnvp Insnpr_tinnc
Underground/Slab Inspections Date Inspector Comments
Initials
Electrical
Sewer Service
Plumbing
Do Not Cover Underaround or Below/In-Slab Work Prior To Annroval Of Thp Ahnvp Incnpr_tinnc
Rough Inspections
Date
Inspector
Initials
Comments
Wall Sheathing
Mid -Roof
Lath / Wall Tie
Rough Electric
Rough Plumbing/Gas Line
Rough Mechanical
Rough Framing
Rough Grading
Insulation
Drywall Screw/ Nail
Final Inspections
Date
Inspector
Initials
Comments
Landscaping & Parking / Planning Dept.
Inspections from these entities should be requested
one week in advance. For landscaping and parking
inspections call 303-235-2846. For ROW and drainage
inspections call 303-235-2861. For fire inspections
contact the Fire Protection District for your project.
ROW & Drainage / Public Works Dept.
Floodplain Inspection (if applicable)
Fire Inspection / Fire Protection Dist.
Final Electrical
Final Plumbing
Final Mechanical
I
(�
Roof
Final Window/Doors
Final Building
NOTE: All items must be completed and approved by Planning, Public Works, Fire and Building before a Certificate
of Occupancy is issued. Approval of the Final Building inspection does not constitute authorization of occupancy.
--ror iow voitage permits — mease De sure that rough inspections are compieted trom the Tire uistrict and electrical low voltage
by the Building Division.
Occupancy Is Not Permitted Until A Certificate of Occupancy Is Issued
Protect This Card From The Weather
City of Wheat Ridge
Residential Mechanic PERMIT - 2017036 75
PERMIT NO: 201703675 ISSUED: 07/11/2017
JOB ADDRESS: 12296 W 34th Pig EXPIRES: 07/11/2018
JOB DESCRIPTION: Replace existing boiler 130K BTU Bernham cast iron; Replace hot water
heater 60 gallon, side-arm heater
*** CONTACTS ***
OWNER (720)490-5865 LOWERS HEATHER
SUB (303)278-1332 Gary Ray Hall 020580 Circle H Plumbing & Heating
*** PARCEL INFO ***
ZONE CODE: UA / Unassigned USE: UA / Unassigned
SUBDIVISION CODE: 2403 / APPLEWOOD VILLAGES, PROSPECT V BLOCK/LOT#: 0 /
*** FEE SUMMARY *** ESTIMATED PROJECT VALUATION: 10,200.00
FEES
Boiler Replacement 40.00
Hot Water Heater 40.00
Total Valuation 0.00
Use Tax 214.20
** TOTAL ** 294.20
*** COMMENTS ***
*** CONDITIONS ***
Work shall comply with 2012 IRC & 2014 NEC. Per IRC Sec. R314, smoke detectors are required
to be installed in every sleeping room, in hallways outside of sleeping rooms, and on every
level of the structure.
I by my signature, do hereby attest that the work to be performed shall comply with all accompanying approved plans and specifications,
applicable building codes, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized
by the legal owner of the properly and am authorized to obtain this permit and perform the work described and approved in conjunction with
th is permit. I further attest that I am le all
authorized to include all entities named within this document as parties to the work to be
performed and that all work to be performed is disclosed in this document and/or its' accompanying approved plans and specifications.
Signature of OWNER or CONTRACTOR (Circle one) Date
1. This permit was issued based on the information provided in the permit application and accompanying Flans and specifications and is
subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, po Flans
and procedures.
2. This permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and
received prior to the date of expiration. An extension of no more than 180 days made be granted at the discretion of the Chief Building
Official and may be subject to a fee equal to one-half of the original permit fee.
3. If this permit expires, a new permit may be required to be obtamed. Issuance of a new permit shall be subject to the standard
requirements, fees androcedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of
the Chief Building Official and is not guaranteed.
4. No work of any manner shall be performed that shall results in a change of the natural flow of water without prior and specific approval.
5, The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all required
inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services
Division.
6. The issuanceoSord
ing of a permit shall not be construed to be a permit for, or an approval of, an violation of any provision of any
applicable co yeordmangula 'on f this jurisdiction. Approval of work is subject to field inspection.
Jam- &
Signature of Chief Building Official Date
REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY.
Inspection time requests will be accepted by email only. Please email requests to insptimerequest@ci.wheatridge.co.us
between 7:30am and 8:00am, the morning of the inspection. Please put the address of the inspection in the subject line.
A i CITY OF WHEAT RIDGE
Building Inspection Division
(303) 234-5933 Inspection line
(303) 235-2855 Office • (303) 237-8929 Fax
INSPECTION NOTICE
Inspection Type:��.
Job Address:541-1A L
Permit Number:
❑ No one available for inspection: Time (Y)pM
Re -Inspection required: Yes oNo
When corrections have been made, call f fw-mspe`ctiio}nn aatt 303-234-5933
Date: �� Inspector: �, ! 1''
DO NOT REMOVE THIS NOTICE
A i CITY OF WHEAT RIDGE
Building Inspection Division
(303) 234-5933 Inspection line
(303) 235-2855 Office • (303) 237-8929 Fax
INSPECTION NO^TICE
Inspection Type:
Job Address: 1(.P i ---
Permit Number: /L.D ('-I 00b`r7 ±
`�
❑ No one available for inspection: Time 1 QOM AM/ M
Re -Inspection required: Yes No
When corrections have been made, call W re -inspection at 30(3-234-5933
j
Date:—k k ?>h1 Inspector:
DO NOT REMOVE THIS NOTICE
City of Wheat Ridge
Residential Mechanic PERMIT - 201704865
PERMIT NO: 201704865 ISSUED: 07/26/2017
JOB ADDRESS: 12296 W 34th PL EXPIRES: 07/26/2018
JOB DESCRIPTION: Install DV NG fireplace, DV flue system 37K BTUS; breeze air evap cooler
7500 CFM; fireplace insert and flue liner kit 24K BTUs
*** CONTACTS ***
OWNER (720)490-5865 LOWERS HEATHER
SUB (303)816-4900 Chris Goodrich 120265 Goodrich Chimney Services
*** PARCEL INFO ***
ZONE CODE: UA / Unassigned USE: UA / Unassigned
SUBDIVISION CODE: 2403 / APPLEWOOD VILLAGES, PROSPECT V BLOCK/LOT#: 0 /
*** FEE SUMMARY *** ESTIMATED PROJECT VALUATION: 10,000.00
FEES
Total Valuation 0.00
Use Tax 210.00
Permit Fee 204.30
** TOTAL ** 414.30
*** COMMENTS ***
*** CONDITIONS ***
Work shall comply with 2012 IRC & 2014 NEC. Per IRC Sec. R314, smoke detectors are required
to be installed in every sleeping room, in hallways outside of sleeping rooms, and on every
level of the structure.
I, by my signature, do hereby attest that the work to be performed shall comply with all accompanying approved plans and specifications,.
applicable building codes, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been author�aed
by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with
this en -n I further attest that I am legally authorize oto include all entities named within this document as parties to the work to be
performed an�ttlat all work to be performed is disclod in this document and/or its' accompanying approved plans and specifications.
Signature o OWNER or CON RACTOR (C�tr�l ne) Date
1. This permit was issued based on the information provided in the permit application and accompanying plans and specifications and is
subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures.
2. This.permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and
received prior to the date of expiration. An extension of no more than 180 days made be granted at the discretion of the Chief Budding
Official and may be subject to a fee equal to one-half of the original permit fee.
3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard
requirements, fees and procedures for approval of any new permit. Re -issuance or extension of expired pen -nits is at the sole discretion of
the Chief Building Official and is not guaranteed.
4. No work of any manner shall be performed that shall results in a change of the natural flow of water without prior andspecific approval.
5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all required
inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services
Division.
6. The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, an violation of any provision of any
applicable code or any ordinance or regulation of this jurisdiction. Approval of work is subject to field inspection.
Signature of Chief Building ficial ate
REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY.
City of
Wheat iclge
COMMUNITY DEVELOPMENT
Building & Inspection Services Division
7500 W. 29th Ave., Wheat Ridge, CO 80033
Office: 303-235-2855 * Fax: 303-237-8929
Inspection Line: 303-234-5933
Email: permits@ci.wheatridge.co.us
FOR OFFICE USE ONLY
Date:
qg�Plan/Permit #! , ) I o
Plan Review Fee:
Building Permit Application
"` Please complete all highlighted areas on both sides of this form. Incomplete applications may not be processed. "'
Property Address: 12296 W 34th PI 80033
Property Owner (please print): Heather Lowers Phone: 720-490-5865
Property Owner Email:
Mailing Address: (if different than property address)
Address
City, State, Zip:
Architect/Engineer:
Architect/Engineer E-mail:
Contractor: Goodrich Chimney
Contractors City License #:
Contractor E-mail Address: gcsmainoffice@gmail.com
Sub Contractors:
Electrical:
W.R. City License #
Other City Licensed Sub:
City License #
Plumbing:
W.R. City License #
Phone:
Phone: 303-233-1307
Other City Licensed Sub:
City License #
Mechanical:
W.R. City License #
Complete all information on BOTH sides of this form
❑ COMMERCIAL ® RESIDENTIAL
Description of work: (Check all that apply)
❑ NEW COMMERCIAL STRUCTURE ❑ ELECTRICAL SERVICE UPGRADE
NEW RESIDENTIAL STRUCTURE ❑ COMMERCIAL ROOFING
COMMERCIAL ADDITION RESIDENTIAL ROOFING
RESDENTIAL ADDITION WINDOW REPLACEMENT
COMMERCIAL ACCESSORY STRUCTURE (Garage, shed, deck, etc.)
RESIDENTIAL ACCESSORY STRUCTURE (Garage, shed, deck, etc.)
MECHANICAL SYSTEM/APPLIANCE REPAIR or REPLACEMENT
PLUMBING SYSTEM/APPLIANCE REPAIR or REPLACMENT
ELECTRICAL SYSTEM/APPLIANCE REPAIR or REPLACEMENT
❑ OTHER (Describe)
(For ALL projects. please provide a detailed description of work to be performed. including current use of areas,
proposed uses, square footage, existing condition and proposed new condition, appliance size and efficiency, type and
amount of materials to be used. etc.)
Sq. Ft./LF
Amps
Install DV NG fireplace and DV flue system 37,000BTUs
Install Breeze Air Evap Cooer (roof mount) 7,500CFM
Install DV NG fireplace insert and flue liner kit 24,000BTUs
Btu's
Squares
Gallons
Other
Project Value: (Contract value or the cost of all materials and labor included in the entire project)
$ 10,000
OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT
1 hereby certify that the setback distances proposed by this permit application are accurate and do not violate applicable ordinances, rules or
regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown and allegations made are
accurate; that I have read and agree to abide by all conditions printed on this application and that 1 assume full responsibility for compliance
with applicable City of Wheat Ridge codes and ordinances for work under any permit issued based on this application; that I am the legal owner
or have been authorized by the legal owner of the property to perform the described work and am also authorized by the legal owner of any
entity included on this application to list that entity on this application.
CIRCLE O -VE (OWNER) (CONTRACTOR) or (AUTHORIZED REPRESENTATIVE) of (OWNER) (CONTRACTOR)
PRINT NVNIIE:
Samantha Goodrich
ZONING COMMMENTS
Reviewer
BUILDING DEPARTMENT COMMENTS
Reviewer
PUBLIC WORKS COMMEN-S
Reviewer
PROOF OF SUBMISSION FORMS
SIGNATFRE: 8 L�— DATE: 07/19/17
Fire Department ❑ Received ❑ Not Required
Water District ❑ Received ❑ Not Required
Sanitation Oictnr_t F1 RPrpivari f-1 Not Reouired
DEPARTMENT USE ONLY
OCCUPANCY CLASSIFICATION
, vPE OF CONSTRUCTION
SPRINKLEREC __...
OCCUPANT LOAD
Building Division Valuation: $
i CITY OF WHEAT RIDGE
Building Inspection Division
(303) 234-5933 Inspection line
(303) 235-2855 Office • (303) 237-8929 Fax
INSPECTION NOTICE
Inspection Type: /�C�-. V/�� 445�
Job Address: L�
Permit Number: Q(]
❑ No one available for inspection: Time 01 / 5 AM/PM
Re -Inspection required: Yes No
When corrections have been made, call for re -inspection at 303-234-5933
Date: *,-5,/7-inspector:
DO NOT REMOVE THIS NOTICE
41
�j
r (30
Inspection Type:
Job Address:
Permit Number:
❑ No one available for inspection: Time &2: 1A�1/PM
Re -Inspection required: YesN
When corrections have been made, ca re -inspection at 303-234-593
Date: ()• 5 %7 Inspector:
DO NOT REMOVE THIS NOTICE
�' ro
Nt i CITY OF WHEAT RIDGE
Building Inspection Division
(303) 234-5933 Inspection line
(303) 235-2855 Office • (303) 237-8929 Fax
INSPECTION NOTICE
Inspection Type: N GG V
Job Address: I Z Z 9& "-., 3 H
Permit Number: 2 U 1-700 272q
1 h oy'" 7/t --n 1 t ,jam —7
L�"Xis l �A kAl
❑ No one available for inspection: Time 11 `/S &I /PM
Re -Inspection required: Yes
When corrections have been made, call for re -inspection at 303-234-5933
Date: '7 / /1117 Inspector: A 10
DO NOT REMOVE THIS NOTICE
jt
4
F
i CITY OF WHEAT RIDGE F
- Building Inspection Division "
(303) 234-5933 Inspection line
(303) 235-2855 Office • (303) 237-8929 Fax
INSPECTION NOTICE
Inspection Type:, M27b
Job Address:
Permit Number:�7�St/�
❑ No one available for inspection: Time AM/PMS
Re -Inspection required: Yes No
*When corrections have been made, call for re -inspection at 303-234-5933
Date: 1/'/7 Inspector: g! ,
DO NOT REMOVE THIS NOTICE
i CITY OF WHEAT RIDGE f
Building Inspection Division
(303) 234-5933 Inspection line
(303) 235-2855 Office • (303) 237-8929 Fax
INSPECTION NOTICE
Inspection Type:
Job Address: % �196k/02VO 61
Permit Number: 2w_yZ60 e-
❑ No one available for inspection;. Time v AM/PSA
Re -Inspection required: Yes; No,'
When corrections have been made`,vaH for re -inspection at 303-234-5933
Date: /' Inspector:
DO NOT REMOVE THIS NOTICE
- i CITY OF WHEAT RIDGE
_��9�Building Inspection Division
(303) 234-5933 Inspection line
(303) 235-2855 Office - (303) 237-8929 Fax
INSPECTION NOTICE
Inspection Type:
Job Address:
Permit Number:
❑ No one available for inspection: Time /3 %LAMIPM
Re -Inspection required: Yes No
When corrections have been made, call for re -inspection at 303 -234 -
Date:— Inspector,
DO NOT REMOVE THIS NOTICE
,. City of Wheat Ridge
Residential Roofing PERMIT - 201705864
PERMIT NO: 201705864 ISSUED: 08/10/2017
JOB ADDRESS: 12296 W 34th PL EXPIRES: 08/10/2018
JOB DESCRIPTION: Residential Re -roof to install asphalt shingles - 28 sq
*** CONTACTS ***
OWNER (720)490-5865
SUB (303)756-7663
LOWERS HEATHER
Ty Correy
090134 Advanced
Exteriors, Inc.
*** PARCEL INFO ***
ZONE CODE:
UA / Unassigned
USE:
UA / Unassigned
SUBDIVISION CODE:
2403 / APPLEWOOD
VILLAGES, PROSPECT V BLOCK/LOT#:
0 /
*** FEE SUMMARY ***
ESTIMATED
PROJECT, GIA-hUAT-1-GN-:-----8-14000.00
FEES
_
Total Valuation
0.00
�•
r.
Use Tax
168.00
'`�
Permit Fee
172.60
Y
** TOTAL **
340.60
*** COMMENTS ***
*** CONDITIONS ***
Effective December 1, 2014, asphalt shingle installations require an approved midroof
inspection, conducted when 25-75 percent of the roof covering is installed, prior to final
approval. Installation of roof sheathing (new or overlay) is required on the entire roof
when spaced or board sheathing with ANY gap exceeding one half inch exists. Sheathing and
mid -roofs may be called in at the same time, one hundred percent of the sheathing must be
complete and 25-75 percent of the mid -roof may be complete. Asphalt shingles are required
to be fastened to the roof deck with a minimum of 6 nails per shingle. Ice and water shield
is required. Eave and rake metal is required. A ladder extending 3 feet above the roof eave
and secured in place is required to be provided for all roof inspections. Roof ventilation
is required to comply with applicable codes and/or manufacturer installation instructions,
whichever is more stringent. In order to pass a final inspection of elastomeric or similar
type roof coverings, a letter of inspection and approval from the manufacturer technical
representative stating that "the application of the roof at (project address) has been
applied in accordance with the installation instruction for (roof material brand name)
roof covering" is required to be on site at the time of final inspection.
Roof inspections for ROOFS OVER 6/12 PITCH: 3rd party inspection will be required, the 3rd
party inspection report will be collected at final roof inspection performed by City of
Wheat Ridge. If report is not available the final inspection will not be completed.
PERMIT NO:
JOB ADDRESS:
JOB DESCRIPTION
City of Wheat Ridge
Residential Roofing PERMIT - 201705864
201705864 ISSUED: 08/10/2017
12296 W 34th PL EXPIRES: 08/10/2018
Residential Re—roof to install asphalt shingles — 28 sq
I, by my signature, do hereby attest that the work to be performed shall comply with all accompanying approved plans and specifications,
applicable building codes, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized
by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with
this permit. I further attest that I am legally authorized to include all entities named within this document as parties to the work to be
performed and that all work to be performed is disclosed in this document and/or its' accompanying approved plans and specifications.
f
Signature of OWNER or CONTRACTOR (Circle one) Date
I. This permit was issued based on the information provided in the permit application and accompanying Flaps and specifications and is
subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures.
2. This.permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and
received prior to the date of expiration. An extension of no more than 180 days made be granted at the discretion of the Chief Building
Official and may be subject to a fee equal to one-half of the originalpermit fee.
3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard
requirements, fees androcedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of
the Chief Building Official and is not guaranteed.
4. No work of any manner shall be performed that shall results in a changeof the natural flow of water without prior and specific approval.
5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all required
inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services
Division.
6. The !issuance or granting of a permit shall not be construed to be a permit for, or an approval of, an violation of any provision of any
apphcabf code or any ordinance or regulation of this jurisdiction. Approval of work is subject to field inspection.
Signature of Chief Building Official Date
REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY.
Dane Lovett
0l70���`
2�
From: no-reply@ci.wheatri dge.co.us
Sent: Thursday, August 3, 2017 9:47 AM
To: CommDev Permits
Subject: Online Form Submittal: Residential Roofing Permit Application
Categories: Gina
Residential Roofing Permit Application
This application is exclusively for new permits for residential roofs and for licensed
contractors only. This type of permit is ONLY being processed online --do not come
to City Hall to submit an application in person. Permits are processed and issued in
the order they are received and due to the volume of requests, time to process
varies and is subject to change. YOU WILL BE CONTACTED WHEN YOUR
PERMIT IS READY FOR PICK-UP AND WILL BE GIVEN A SPECIFIC DATE
AND TIME WINDOW TO COMPLETE THE TRANSACTION. You will be notified if
your contractor's license or insurance has expired, and you may update those
documents at the time you are issued your permit.
For all other requests:
Homeowners wishing to obtain a roofing permit must apply for the permit in person
at City Hall. Revisions to existing permits (for example, to add redecking) must be
completed in person at City Hall. All other non -roofing permits must be completed in
person at City Hall. The Building Division will be open from 7:30-10:30 a.m.,
Monday through Friday to process these types of requests.
THIS APPLICATION DOES NOT CONSTITUTE A PERMIT. DO NOT BEGIN
REROOFING UNTIL PERMIT HAS BEEN ISSUED.
Is this application for a Yes
residential roof?
How many dwelling units Single Family Home
are on the property?
PROPERTY INFORMATION
Property Address
Property Owner Name
Property Owner Phone
Number
Property Owner Email
Address
12296 W 34th pl
heather lowers
720-490-5865
Field not completed.
Do you have a signed
Yes
contract to reroof this
property?
It will need to be
provided at the time of
permit pick-up.
Attached Copy of
Field not completed.
Contract
CONTRACTOR INFORMATION
Contractor Business
advanced exteriors
Name
Contractor's License
090134
Number (for the City of
Wheat Ridge)
Contractor Phone
303-725-4502
Number
Contractor Email Address
freddygreen@advancedexteriors.net
Retype Contractor Email
freddygreen@advanced exteriors. net
Address
DESCRIPTION OF WORK
Are you re -decking the
f'
No/
roof?
Description of Roofing
shingles
Material
Select Type of Material:
Asphalt
If "Other" is selected
Field not completed.
above, describe here:
How many squares of the
28
material selected above?
Does any portion of the
No
property include a flat
roof?
If yes, how many squares
Field not completed.
on the flat roof?
TOTAL SQUARES
28� l
(pitched + flat) of all
z
roofing material for this
project
Provide additional detail 4/12
here on the description of
work. (Is this for a house
or garage? What is the
roof pitch? Etc)
Project Value (contract 8000
value or cost of ALL
materials and labor)
SIGNATURE OF UNDERSTANDING AND AGREEMENT
I assume full Yes
responsibility for
compliance with
applicable City of Wheat
Ridge codes and
ordinances for work
under any permit
issued based on this
application.
I understand that this Yes
application is NOT a
permit. I understand I will
be contacted by the City
to pay for and pick up the
permit for this property.
I understand that work Yes
may not begin on this
property until a permit
has been issued and
posted on the property.
I certify that I have been Yes
authorized by the legal
owner of the property to
submit this application
and to perform the work
described above.
Name of Applicant Freddy g
Email not displaying correctly? View it in your browser.
3
Advanced Exteriors, Inc.
cuft
�77��17
00%
-p7rF
RopedIfAddoen
47-7
Primary
&
Cft state zip A 2),
SemndarvPhone
insurance Comparw CWm #
Ernall Ado"
C-'46 lk'6)Fn
Tea off � laver(s) of composition, &— lav") of
F1 Standard ridge High profile ridge
Inspect decking [] Install decking
Install starter course of shingles -entire perimeter
Install 15 # felt F-1 Install 30 # felt
E] Install ridge vent
Install turtle vents (3 -Install r. vents
Install pipe lack flashings 0 -Install furnace caps
Install 4�:� j. =j- -A--
Paint jocksVstacks to Match roofing color
Install Ice and water shletc! on -9 >9
Detach and reset
install drip edge - color '3
F Remove and cover
install reinforcement in valleys using _jz2:& ZZ g7 7; A,°4227_
Closed valleys n Open valleys
Install beauty course of ridge shingles on headwalls
Detach and reset satellite M, Remove satellite
Replace step flashing on sidewalls, chimney and skylights
Clean up & remove trashSweep with magnetic roller
4.
Install 6 nails per shingle throughout fled area
Clean out M ovlde building permit
!<SJT'T'r-M4
Roofing procluct44417- I iLr_ lZ'tl
Roofing color R�,i A
Register L," i Manufacturer Warranty
Advanced Exierlors, Inc-, Five Year Roofing Labor Warranty
Manufacturer Warranty j �Ct-
Advanced Exteriors, Inc. $2,000,000 Liability Insurance
E] Special Instructions(Additional Work
AWo)dmate Dallells) of Service: ` q43 "aymert"elms:
(AOMnced ExterWt I= is not reW=Ible for any property and casually lnstaranca cardWs delay or deniat of an ftmrance claim, In whole or ft) part).
By signing below I (We)
notice of1b"jWto-*
cornpany Projeof Maraorrft
2200 S. Valley Hwy.
Denver, CO 80222
to all contract conditions on front and back of this agreement, and hove been provided
writing and orally.
M070=
..`r
Z
Acceptance Date
303-756-ROOF(7663) Office
303-756-3756 Fax
i CITY OF WHEAT RIDGE
Building Inspection Division
(303) 234-5933 Inspection line
(303) 235-2855 Office • (303) 237-8929 Fax
y
INSPECTION NOTICE
Inspection Type:
a , l= IZ f- , ��I �Z L , Pry ����051�
Job Address:
Permit Number: 2 0 d(' t� rz-rc— --.L 124�no-L
.•r ,
❑ No one available for inspection. -Tim
Re -Inspection required: Yes (i
When correcti
Date:3-
AM/PM
i CITY OF WHEAT RIDGE
_:�9rBuilding Inspection Division
(303) 234-5933 Inspection line
(303) 235-2855 Office • (303) 237-8929 Fax
INSPECTION NOTICE
Inspection Typ
In tion e: 17L/ J
Job Address: % 1 1A/ 3 1S
Re -Inspection required: Yes(
When corrections have been made, call for re-inspeotionpf 303-234-5933
Date: r Inspector:
DO NOT REMOVE VWS NOTICE
City of Wheat Ridge
Residential Remodel PERMIT - 201700884
I Z. -o
PERMIT NO: 201700884 ISSUED: 07/10/2017
JOB ADDRESS: 12296 W 34th PL EXPIRES: 07/10/2018
JOB DESCRIPTION: Interior Remodel - kitchen remodel, main floor bathroom remodel, basement
bath remodel, add 1/2 bath in basement, rework basement closet, new gas
fireplace, 3 new egress windows, reconfigure basement stairs
*** CONTACTS ***
OWNER (720)490-5865 LOWERS HEATHER
SUB (303)500-3103 Add.m & Julie Rossi
SUB (720)490-1533 David Capune
SUB (720)394-2363 Robert Fleming
SUB (303)598-8617 Michael J Lind
130036 Blue Sky Remodeling
090309 High Quality Plumbing Inc.
090151 Royal Comfort Heating & A/C
170368 Red Rock Electric
*** PARCEL INFO ***
ZONE CODE: UA / Unassigned USE: UA / Unassigned
SUBDIVISION CODE: 2403 / APPLEWOOD VILLAGES, PROSPECT V BLOCK/LOT#: 0 /
*** FEE SUMMARY *** ESTIMATED PROJECT VALUATION: 81,345.00
FEES
Total Valuation 0.00
Plan Review Fee 641.65
Use Tax 1,464.21
Permit Fee 987.15
** TOTAL ** 3,093.01
*** COMMENTS ***
*** CONDITIONS ***
All roughs to be done at Framing Inspection.
Approved per plans and red -line notes on plans. Must comply with 2012 IRC, 2014 NEC and ali
applicable City of Wheat Ridge Municipal Codes. Work is subject to field inspections.
PERMIT NO:
JOB ADDRESS:
JOB DESCRIPTION:
City of Wheat Ridge
Residential Remodel PERMIT - 201700884
201700884 ISSUED: 07/10/2017
12296 W 34th PL EXPIRES: 07/10/2018
Interior Remodel - kitchen remodel, main floor bathroom remodel, basement
bath remodel, add 1/2 bath in basement, rework basement closet, new gas
fireplace, 3 new egress windows, reconfigure basement stairs
I, by my signature, do hereby attest that the work to be performed shall comply with all accompanying approved plans and specifications,
applicable building codes, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized
by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with
thjs ermit. I further attest that I am le ally authorized to include all entities named within this document as parties to the work to be
performed and that all work to be performed is disclosed in this document and/or its' accompanying approved plans and specifications.
Signat OWNER or CONTRACTOR (Circle one) Date
I , Tis permit was issued based on the information provided in the permit application and accompanying plans and specifications and is
subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, po Flans
and procedures.
2. This permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and
received prior to the date of expiration. An extension of no more than 180 days made -be granted at the discretion of the Chief Building
Official and may be subject to a fee equal to one-half of the original permit fee.
3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard
requirements, fees andprocedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of
the Chief Building Official and is not guaranteed.
4. No work of any manner shall be performed that shall results in a change, of the natural flow of water without prior andspecific approval.
5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all required
inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services
Division.
6. The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, any violation of any provision of any
applicable code or any ordinah- br regulation -"is jun d4ict',on. Approval of work is subject to field inspection.
cl tell
<a1
Signature of Chief Building Official Date
REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY.
Inspection time requests will be accepted by email only. Please email requests to insptimerequest@ci.wheatridge.co.us
between 7:30am and 8:00am, the morning of the inspection. Please put the address of the inspection in the subject line.
City of
meat jge
CMUNiTy DEVELOPMENT
Building & Inspection Services Division
7500 W. 29" Ave., Wheat Ridge, CO 80033
Office: 303-235-2855 * Fax: 303-237-8929
Inspection Line: 303-234-5933
Email: permitsCED-ci.wheatridge.co.us
FOR OFFICE USE ONLY
Date: 1*6 ! 1 ")
Plan/Permit # )'jqnyXY
Plan Review Fee:
Building Permit Application
*** Please complete all highlighted areas on both sides of this form. Incomplete applications may not be processed. —
Property Address: t
Property Owner (please print): �' 917` Zf5 Z 2Y/74,,
Property Owner Email:
Mailing Address: (if different than property address)
Address
City, State, Zip:
Architect/Engineer: ter; J�C.rC
Arch itectlEnginear E-mail:
Contractor:
Contractors City License #:
to
Contractor E-mail Address: -5
Sub Contractors:
Electrical: l`'�Xll
W.R. City License #
Other City Licensed Sub:
City License #
Plumbing:
W.R. City License #
4,
Phone: 3,,? - SSS 9118
Phone: 3o3- 3
��� ���m�� 4i� � /��yc'r , CJS'►
Mechanical:
✓ W.R. City License #
Other City Licensed Sub:
City License #
Complete all information on BOTH sides of this form
❑ COMMERCIAL A RESIDENTIAL
Description of work: (Check all that apply)
❑ NEW COMMERCIAL STRUCTURE ❑ ELECTRICAL SERVICE UPGRADE
❑ NEW RESIDENTIAL STRUCTURE ❑ COMMERCIAL ROOFING
❑ COMMERCIAL ADDITION ❑ RESIDENTIAL ROOFING
❑ RESDENTIAL ADDITION ❑ WINDOW REPLACEMENT
❑ COMMERCIAL ACCESSORY STRUCTURE (Garage, shed, deck, etc.)
❑ RESIDENTIAL ACCESSORY STRUCTURE (Garage, shed, deck, etc.)
❑ MECHANICAL SYSTEM/APPLIANCE REPAIR or REPLACEMENT
❑ PLUMBING SYSTEM/APPLIANCE REPAIR or REPLACMENT
❑ ELECTRICAL SYSTEM/APPLIANCE REPAIR or REPLACEMENT
OTHER (Describe) 4c /
(For ALL projects, please provide a detailed description of work to be performed, including current use of areas,
proposed uses, square footage, existing condition and proposed new condition, appliance size and efficiency, type and
amount of materials to be used, etc.)
Sq. Ft./LF
Amps
Btu's
Squares
Gallons
Other
Project Value: (Contract value or the cost of all materials and labor included in the entire project) I
- k" Jw�"_
OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT
I hereby certify that the setback distances proposed by this permit application are accurate and do not violate applicable ordinances, rules or
regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown and allegations made are
accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance
with applicable City of Wheat Ridge codes and ordinances for work under any permit issued based on this application; that I am the legal owner
or have been authorized by the legal owner of the property to perform the described work and am also authorized by the legal owner of any
entity included on this application to list that entity on this application.
CIRCLE ONE: (OWNED_ (CONTRACTOR) or (AUTHORIZED REPRESENTATIVE) of (OWNER) (CONTRACTOR)
PRINT NAME: kl yle S us e- SIGNATURE:
ZONING COMMMENTS:
Reviewer:
BUILDING DEPARTMENT COMMENTS:
Reviewer:
PUBLIC WORKS COMMENTS:
Reviewer:
PROOF OF SUBMISSION FORMS
Fire Department ❑ Received L_I Not Required
Water District ❑ Received ❑ Not Required
Sanitation District ❑ Received ® Not Required
DEPARTMENT USE ONLY
OCCUPANCY CLASSIFICATION:
TYPE OF CONSTRUCTION:
SPRINKLERED:
OCCUPANT LOAD:
Building Division Valuation: $
CAA
PLAN REVIEW COMMENTS
FOR CITY OF WHEAT RIDGE
Project Description: Remodel
Project Address: 12296 W 34"' Place
Permit App. Date: 5/25/17
Use: Residential Occupancy:
Plan Checker: Randy Slusser/CAA
Plan Check No.: 201700884
R3/U Const. Type: VB
Phone: (720)404-4538
Engineer email:
randysiusser@caaprofessionaIs.com
X
1 sc Review:
6/22/17
2nd Review:31d
Review:
Italic comments
By Appointment
The project plans were reviewed for compliance with the following codes and standards:
2012 IBC, 2012 IRC, 2012 IMC, 2012 IPC, 2014 NEC and Wheat Ridge Amendments
• TO EXPEDITE PROJECT APPROVAL: Please provide a written response indicating how and where each
comment was resolved on the plans.
• Resubmit all previously reviewed plans, updated plans and supporting documents with each subsequent
review.
• For clarification of any plan review comment, please call or email the plan checker listed above.
Note: Plan checks expire 180 days from date of submittal.
CI1ARL6,s ABBOTT AssoCi:Vrrs, INC.
17401 1 o,C At I oS -St a 1 210 -\I ISS I()\V ][ R Y C:A 91691
101A FRCS (866)X30-4980•PFiom (949)367-28�0•FAS'(949)367-28:2
\\\N\\ ( AAPR011RS10N VI S (0V1
GENERAL REQUIREMENTS
1. Please provide a full floor plan of main level and basement identifying all room locations and areas of construction.
Full existing floor plan of main floor and basement, hatched areas represent areas of construction.
2. Show all required electrical receptacles on partial plan that was previously submitted, Rev 2 dated 5/4/2017.
Electrical shown on plan
STRUCTURAL
3. Approved
If you have any questions or need assistance please email me at randyslusser@caaprofessionals.com
Thankyou
Randy Slusser
CAA
CII.uu.i;:s ABBOTT Assoclxria, INC.
17401 L o, AI Ms •S(nr 2?0 • VIISSIOA V 11 10. ('-A 92691
1-01L FRI F (866) �3i)-4980 • 11[lom 19491 367-73>U • I AS 1949136?-18�2
VAlA \A .(\.A PRO PL SSIUN VI,, (UM
Au,-
City
u�
W City of
�dge
��Wh6at
MUNITY DEVELOPMENT
City of Wheat Ridge Municipal Building 7500 W. 29" Ave. Wheat Ridge, CO 80033-8001 P: 303.235.2855 F: 303.237.8929
Review is limited to the contents of the plans submitted and any errors or omissions contained herein shall not be
construed as permission to allow any conditions to exist in violation of the codes of the City of Wheat Ridge
3 Burial depth requirements:
Electrical - direct burial conductors shall be a minimum of 24 -inches deep, non-metallic conduit 18 -inches deep or 24 -
inches under driveways. (IRC Table E3803.1)
Water Lines - shall be a minimum of 36 -inches deep. (IRC P2603.6)
Gas Service Piping - installed a minimum of 12 -inches below grade or 8 -inches below grade where serving individual
outside appliances. An 18 AWG yellow insulated tracer wire must be installed adjacent to underground nonmetallic gas
piping and terminate above grade at each end. (IRC G2415.1.2 and G2415.17.3)
4 Underground plumbing pipe shall have a solid and continuous load-bearing support. Piping cannot bear on rocks. Pipes
passing under a footing or through foundation wall shall be provided with a relieving arch or a sleeve. Trenches parallel to
footing shall not extend below the 45° plane of the edge of the footing. Water piping must be buried a minimum 36 -
inches deep. Water service pipe may be installed in the same trench as the building sewer provided the sewer pipe
material is listed for underground use within the building or the water service pipe is separated from the sewer by a
minimum distance of 5 -feet horizontally or elevated at least 12 -inches above and to one side of the sewer line.
5 Frost depth to the bottom of the foundation footings must be as noted on the engineered plans. If not noted, the frost
depth to the bottom of the footings must be a minimum of 30 -inches below finished grade. (IRC TableR301.2.1)
6 Caisson and helical pier foundations will not be inspected by Boulder County. A qualified, Colorado -licensed engineer
must perform the placement, drilling, and reinforcement of drilled piers. A signed, sealed and dated inspection report
must be provided to Building Inspection Services prior to the rough inspections R110.5.2.3)
7 A perimeter drain system that discharges to an approved drainage system is required around all foundations that
enclose usable spaces below grade. Foundations that retain earth and enclose interior spaces below grade must be damp
proofed. (IRC R405.1, R406.1, BC Amendment R401.2.14)
8 Slabs below grade must maintain a minimum of 6 -inches above the design water table. The interior finished crawl
space grade must be a minimum of 36 -inches above the design water table. (BC Amendment R401.2.1.3and R401.2.1.5)
9 Garage floor surfaces must be approved noncombustible materials. Floors must be sloped to facilitate the movement
of liquids to a drain or toward the main vehicle entry doorway. (IRC R309.1)
10 Foundation plates and sills must be bolted to the foundation wall as prescribed on the engineered plans. If not noted,
bolts shall have a minimum diameter of %-inch, embedded at least 7 -inches and spaced not more than 6-9apart.
minimum of 2 bolts are required per plate section, with one bolt located within 12 -inches of each endo each%%. (IR
R403.1.6)
Wheat Ridge
www.ci.wheatridge.co.us
Rough Framing and Wood Requirements
11 The complete rough inspection is to be made after the rough framing, rough electric, rough plumbing, and rough heat
and ventilation are complete. The building should be fully enclosed with the roof covering and siding in place.
12 Protection from decay shall be provided in the following locations by the use of naturally durable wood or wood that
is preservative treated in accordance with AWPA U1: (IRC R317)
13 Lumber, plywood, fiberboard, structural logs, and glued laminated timber must be identified by a grade mark or
certificate of inspection issued by an approved agency. (IRC R502.1, R602.1, and R802.1)
A. Wood joists closer than 18 -inches and wood girders closer than 12 -inches to grade located within foundation
periphery.B. Wood framing members that rest on concrete or masonry foundation walls and are less than 8 -inches from
the exposed ground.
C. Sills and sleepers on a concrete or masonry slab that is in direct contact with the ground.
D. Wood girders entering concrete or masonry walls with a clearance less than %2 -inch.
E. Wood siding, sheathing, and wall framing less than 6 -inches above the ground.
F. Wood members supporting moisture -permeable floors or roofs that are exposed to the weather.
G. Wood furring strips or wood members attached directly to the interior of below grade exterior masonry or concrete
walls.
H. Wood in contact with the ground, embedded in concrete in direct contact with the ground or embedded in concrete
exposed to the weather that supports permanent structures intended for human occupancy shall be approved pressure -
preservative -treated wood.
13 Accessible under -floor areas shall be provided with a minimum 18 -inches x 24 -inches opening through the floor or 16 -
inches x 24 -inches opening through the perimeter wall. When the access is through a below -grade wall an areaway of not
less than 16 -inches x 24 -inches must be provided. Where equipment is located beneath the floor, the access opening
must be within 20 -feet of the equipment and allow the removal of the largest piece of equipment. (IRC R408.4 and
M 1305.1.4)
14 Basements greater than 200 square feet and every sleeping room shall have at least one operable emergency and
rescue opening or a door to the exterior.
15 Emergency escape and rescue openings shall meet the following requirements: A minimum clear width of 20 -inches, a
minimum clear height of 24 -inches, with a total net clear opening of 5 square feet for grade level windows and 5.7 square
feet for all others. A sill height of not more than 44 inches measured from the finished floor to the bottom of the clear
opening. Window wells for emergency escape and rescue shall provide a minimum net area of 9 square feet with
minimum horizontal projection and width of 36 -inches. The area of the widow well shall allow the emergency escape and
rescue opening to fully open. (IRC R310)
16 Columns must be restrained to prevent lateral displacement at the bottom end to insure against u lift. (IRC`04p1. i
R407.3) a y')eatR��
; 9e
17 Fire blocking shall be installed to cut off all concealed draft openings in the following locations: (IR 30;�Q. In
0
concealed spaces of stud walls and partitions, including furred spaces, vertically at the ceiling and floor le a.nd`at 10 -
feet horizontal intervals.B. At interconnections between concealed vertical and horizontal spaces such as occur at soffits,
drop ceilings, and cove ceilings. C. In openings around vents, pipes, ducts, cable, wires, chimneys, fireplaces, and similar
openings that afford apassage for fire at ceiling and floor levels. D. In concealed spaces between stair stringers at the top
and bottom of the run, and between studs in line with the run of the stairs at unfinished walls.
18 At least one egress door shall be provided for each dwelling unit. The egress door shall be side -hinged, and
shall provide a minimum clear width of 32 -inches (813 -mm) when measured between the face of the door and
the stop, with the door open 90 degrees (1.57 rad). The minimum clear height of the door opening shall not be
less than 78 -inches (1981 -mm) in height measured from the top of the threshold to the bottom of the stop. Other
doors shall not be required to comply with these minimum dimensions. Egress doors shall be readily openable
from inside the dwelling without the use of a key or special knowledge or effort. (IRC R311, R311.2)
19 There shall be a floor or landing on each side of each exterior door, except where a stairway with 2 or fewer risers
located on the exterior side of the door, other than the required exit door, a landing is not required for the exterior
side of the door. The landing must be no lower than 73/ -inches below the top of the threshold of the door
provided the door does not swing over the landing. (IRC R311)
20 Stairways must be at least 36 -inches in width. Handrails shall not project more than 4%2 -inches. The maximum rise
may not exceed 7% -inches. The minimum tread depth may not be less than 10 -inches. Minimum headroom is 6 -feet, 8 -
inches. For stairways with solid risers a nosing of %-inch to 1Y4 -inches shall be provided. When open risers are used the
opening between the treads shall not allow the passage of a 4 -inch sphere. Landings must be provided at the top and
bottom of the stairway that is the width of the stairway measuring at least 36 -inches in the direction of travel. Handrails
shall be provided on at least one side of stairways with 4 or more risers and ramps with a slope exceeding 1:12. Handrails
shall be mounted 34 -inches to 38 -inches above the nosing of the treads. Handrails must be continuous for the entire
length of the stairs and provided with a minimum space of 1% -inch between the wall and the handrail. Ends shall be
returned or terminate in newel posts or safety terminals. See the requirements and more information. (IRC R311.7.8)
21 Handrail Grip Size Shall Be:A. Circular Handrails: 1% -inch to 2 -inches perimeter. B. Non -Circular: 4 -inches to 6% -inches
perimeter with a maximum cross section of 2% -inches. C. Perimeter Dimension Greater than 6% -inches: shall have a finger
recess on both sides.
22 Guards must be provided for porches, screened porches, balconies, fixed seating and raised floor surfaces more than
30 -inches above the floor or grade below. Guards must have a minimum height of 36 -inches. Open sides of stairs with a
total rise of more than 30 -inches above the floor or grade below shall have guards not less than 34 -inches high.
Intermediate rails shall not allow the passage of a 4 -inch sphere. (R312) Window fall protection must be provided for
window openings less than 24 inches above the finished floor and more than 72 inches above grade or surface
below. (R312.2)
23 Ceiling heights for habitable rooms, hallways, bathrooms, toilet rooms, laundry rooms, and basements shall be a
minimum of 7 -feet measured from the finished floor to the lowest projection of the ceiling. Non -habitable basements
may have a ceiling height of 6 -feet, 8 -inches with clearance below beams and ducts of 6 -feet, 4 -inches. Bathroom may
have a ceiling height of 6 -feet, 8 -inches at the fixture front clearance area and over the fixture. (IRC R305.1)
24 Attic access must be provided for attics that exceed 30 square feet and that have a vertical height of 3QJnehes or
greater. The access must be located in a hall or readily accessible location with a minimum 22 -inches 30-� h, ah ss
opening. The access must provide a minimum of 30 -inches headroom. (IRC R807) 4 Form: B/24 • R(
Ridge
25 Enclosed attic and rafter spaces must have cross ventilation for each space through screened o e ppgs. The total` net
free ventilating area shall not be less than 1 to 150 of the area of the space ventilated. The area may lie reduces o 1 to
300 if 50-80% is provided by ventilators located in the upper portion of the space or if a vapor barrier not exceeding 1
perm is installed on the warm side of the ceiling. At least a 1 -inch space is required between the roof sheathing and the
insulation at the location of the vent. (IRC R806)
26 Rafters must be framed to a minimum 1 -inch nominal ridge board that is not less than the depth of the cut end of the
rafter or to each other using a gusset plate. Hip, and valley rafters shall be a minimum of 2 -inches and not less in depth
than the cut end of the rafter. Hip and valley rafter shall be supported at the ridge by a brace to a bearing partition or be
designed. (IRC R802.3)
27 Rafters and ceiling joists having a depth -to -thickness ratio exceeding 5:1 shall be provided with lateral support at
points of bearing to prevent rotation. Rafters and ceiling joists having a depth -to -thickness ration exceeding 6:1 shall be
supported laterally by solid blocking, diagonal bridging or a continuous 1 -inch by 3 -inch wood strip nailed across the
rafters. (IRC R802.8) Roof trusses or rafters must be attached to supporting walls with approved hurricane clips. Trusses
must be braced to prevent rotation and to provide lateral stability in accordance with the construction documents and
the individual truss design drawings. (IRC R502.11.2, R802.11)
28 Trusses must be designed and fabricated in accordance with ANSI/TPI 1. A licensed professional shall prepare the
truss design. Trusses must be legibly marked within 2 -feet of the center to identify the manufacturer, the design load, and
the spacing. Truss engineering and layout must be provided at the site at the rough framing inspection. (IRC R502.11 and
R802.10)
29 Roofing material installed in the mountain areas is limited to Class -"A" roof coverings. Wood roofs in the plain areas
are limited to minimum Class "B" roof coverings. Shingle installation shall meet the manufacturer's high -wind installation
procedures in areas where wind load is greater than 105 mph (V3S). Chapter 9, R301.2.1, R325, and manufacturer's
listing
30 All habitable rooms shall be provided with aggregate glazing area for natural light of not less than 8% of the floor area
of such rooms. The glazed areas need not be installed in rooms where section M1507 is satisfied and artificial light is
provided at an average of 6 foot candles at a height of 30 inches.
31 Safety glazing shall be installed in the following hazardous locations and be permanently labeled as safety or
tempered glazing: glazing panels in doors; glazing enclosing spas, bathtubs or showers; glazing panels adjacent and within
24 -inches of the edge of a door; glazing panels greater than 9 square feet within 18 -inches of the floor; glazing used for
railings; glazing used for barriers for swimming pools and spas; and glazing enclosing stairways, landings, and ramps
within 36 -inches horizontally of a walking surface. See the Boulder County Land (IRC R308)
32 Roofs decks and enclosed roofed areas must be provided with roof drains installed at the low point of each roof.
Where roof drains are installed, overflow drains or scuppers are required. (IRC R903.4)
33 Exterior finish materials must conform to the conditions of your Site Plan Review to include: roof covering, siding,
color requirements, conforming light fixtures which comply with the approved lighting plan. Glazing and Window
Requirements
32 Skylights must be: (IRC R308.6 Table N1102.1)
A. laminated glass (with restrictions).
rRodg,.
B. fully tempered glass (with retaining screen).
Wheat
C. heat -strengthened glass (with retaining screen).
D. wired glass (with retaining screen in multiple glazing condition only).
E. approved rigid plastic.
F. Skylight U -factor required U-0.45.
Skylights installed on roofs flatter than 3 units vertical to 12 units horizontal must be mounted on a curb
4 -inches above the roof.
Heating and Ventilation Requirements
33 Crawl spaces shall be provided with conditioned air in compliance with Section N1102.2.9. Crawl space walls shall be
insulated in accordance with Table N1102.1 or Table N 1102.1.2. Crawl space wall insulation shall be permanently
fastened to the wall and extend downward from the floor to the finish grade level and then vertically and/or horizontally
for a least an additional 24 -inches. Exposed earth in unvented crawl space foundations shall be covered with a continuous
Class I vapor retarder with a minimum thickness of 10 -mil. All joints of the vapor retarder shall overlap by 6 -inches and be
sealed and taped. The edges of the vapor retarder shall extend at least 6 -inches up the stem wall and shall be attached to
the stem wall. N1102.2.9.2.2 Ventilated crawlspaces. Ventilated crawlspaces shall be provided with insulation in
accordance with Table N1102.1.
34 A. Habitable rooms must be provided with outdoor openings for ventilation equal to at least 4% of the floor area and
shall have heating facilities capable of maintaining 68° at 3 -feet above the floor and 2 -feet from exterior walls. B. The
windows need not be openable in a room where an opening is not required to be an egress window and a mechanical
ventilation system is capable of producing 0.35 air change per hour in that room, or a whole house mechanical ventilation
system provides 15 cubic feet of outdoor air per minute.
35 Bathroom exhaust fans shall exhaust directly to the exterior and must be provided in bathrooms where windows of at
least 3 square feet are not provided. The mechanical ventilation must be capable of providing an exhaust capacity of 50
cfm intermittent or 20 cfm continuous exhaust. (IRC R303.3, M1507.4)
36 Dryer vents must be rigid metallic, independent of all other systems, shall terminate outside the building, be equipped
with a back draft damper, and sized and terminated per the manufacturer. The maximum length of the exhaust duct shall
be 35 -feet (Unless approved under the manufacturer's listing) from the connection to the transition duct from the dryer
to the outlet terminal. Where fittings are used, the maximum length of the exhaust duct shall be reduced in accordance
with (IRC Table M1502.4.4.1) Flexible transition ducts are limited to 8 -feet, shall not be concealed within construction,
and shall be listed and listed per UL 2158A. (IRC M1502)
37 Appliances and equipment shall be installed in accordance with the conditions of their listing. Manufacturer's
installation instructions must be available at the time of the inspection. (IRC G2408.1, M1307.1, M1401.1,(M1902.2)
38 Appliances shall be accessible for inspection, service, repair and replacement without removing permanent
construction. 30 -inches of working depth and width shall be provided in front of the control side of an appliance. (IRC
M1305.1)
39 Gas and solid fuel appliances located in a garage and hazardous locations shall be elevated so the source of ignition is
at least 18 -inches above the floor. Rooms and spaces that are communicate directly with the garage and are -not part of
the living space shall be considered as part of the garage. Appliances located in garages must be instalLBuildding
-fe"
above the floor or protected from motor vehicle impact. (IRC G2408.2, G2408.3)
dge
40 Combustion air is required for all liquid fuel, solid fuel and gas appliances. (IRC M1701.1, G2407) ison
41 Gas burning appliances may not be located in or obtain combustion air from: a sleeping room, bathroom, toilet room,
or storage closet unless it is a direct vent appliance or installed in an enclosure that opens only into a bedroom or
bathroom in and such enclosure is provided with a solid weather-stripped door, a self-closing device and all combustion
air is taken from the outdoors. (IRC G2406.2)
42 Gas logs installed in solid fuel burning fireplaces shall be tested in accordance with ANSI Z21.60 and installed per the
manufacturers installation instructions. Gas logs installed in bedrooms must be direct vent or provided with an approved
source of outside combustion air. The approved gas log set must be installed in the Solid -fuel burning appliances at the
final inspection. (IRC G2406, G2432, and G2434)
43 B, BW, and L vents and factory -built chimneys must be provided with a clearance to combustibles per them a
manufacturer's listing. Where vents pass through insulated assemblies, they must be provided with an insulation shield. A
clearance of 9 -inches is required between single wall vent connectors and combustibles. Gas vents must penetrate
through the roof flashing, jack or thimble and terminate in a Chimneys listed cap or per the manufacturers listing.
Decorative shrouds installed at terminations shall be listed and installed per the manufacturer. (IRC G2425, G2426,
G2427)
Electrical Requirements
44 All electrodes present at each structure shall be bonded together to form one grounding electrode system to include:
Concrete Encased Electrodes (UFER), water piping, ground rings, grounding rods, and plate electrodes. Bonding shall
ensure electrical continuity. The electrode conductor must be connected in an approved manner and inspected prior to
concealing. (IRC E3607, E3608, E3609, E3610, E3611)
45 All hot, neutral, and grounding conductors in electrical boxes shall be tied together with a mechanical connection at
the time of rough inspection.
46 Recessed lighting fixtures must either be IC -rated or installed in a sealed box in which the insulation is at
least 3 -inches from the light fixture. All recessed lights must be tightly sealed or gasketed to prevent air leakage
through the fixture into the ceiling cavity. (IRC N 1102.4.5)
47 Tamper -resistant Receptacle outlets are required in every kitchen, family room, dining room, living room, parlor,
library, den, sunroom, bedroom, recreation room or similar dwelling areas spaced so that no point along the wall line
exceeds 6 -feet from an outlet. (IRC E3901, E3902, and 4002.1-4002.14)A. Counters 12 -inches in width or wider shall have
receptacles placed no more than 20 -inches above the counter top and spaced so no point exceeds 24 -inches from an
outlet. B. Island and peninsula counters with a length at least 24 -inches and a width of 12 -inches or greater must be
equipped with at least one outlet. C. At least one receptacle shall be installed in a bathroom within 36 -inches of each
basin. D. A least one receptacle outlet must be installed in each laundry, basement, attached garage and detached garage
with power. E. At least one receptacle outlet that is accessible while standing at grade level and located not more than6-
feet, 6 -inches (1981 -mm) above grade, shall be installed outdoors at the front and back of each dwelling unit having
direct access to grade. Balconies, decks, and porches that are accessible from inside of the dwelling unit a thatlhave a
usable area of 20 square feet. F. Attics or crawlspaces containing equipment must be provided with a east,
receptacle outlet within25-feet of the equipment. G. Hallways 10 -feet or more in length.
Wheat Ridge
48 Two 20 -amp rated branch circuits shall serve receptacles in the kitchen, pantry, breakfast area, a q%Mi piny,
ieast one 20 -amp branch circuit shall supply bathroom receptacles and at least one 20 -amp branch circ)%4 shall
laundry. (IRC E3703.2, E3703.3, E3901)
50 Ground fault protection shall be provided on all 125 -volt, single phase, 15 and 20 -amp receptacles in the following
locations: bathrooms, garages, unfinished grade level accessory buildings, at exterior locations , crawlspaces, unfinished
basements, kitchen counters, within 6ft. of laundry, utility and wet bar sinks, boathouses, hydro massage, spa and hot tub
locations. Receptacles must be in a readily accessible location. (IRCE3902, E3902.11)
51 Combination type arc -fault circuit interrupters must be installed on all 120 -volt 15 and 20 -amp branch circuit outlets
in Receptacle outlets are required in every family room, dining room, living room, parlor, library, den, sunroom, bedroom,
recreation room, hallway, closets, and similar dwelling areas. (IRC 3902.12)
52 At least one wall switch -controlled lighting outlet shall be installed in every habitable room, bathroom, hallway, (loft)
stairway, attached garage, detached garage with electric power, and at the exterior side of each outdoor egress door
having grade level access. Attics, under floor spaces, utility rooms and basements containing equipment or used for
storage must be provided with a switch
53 Smoke alarms shall comply with UL 217. Smoke alarms are to be powered by the building's wiring operated light. (IRC
E3903)with battery backup and shall be interconnected so the actuation of one alarm will activate all alarms in the
dwelling unit. Smoke alarms shall be installed in the following locations: (IRC R314) A. In each sleeping room; B. Outside
each sleeping area in the immediate vicinity of the bedrooms; and C. One on each additional story including basements.
54 Carbon Monoxide alarms are required in a single-family dwelling that has fuel -fired appliance(s), or a fireplace, or an
attached garage. The alarm must be installed within 15 -feet of the entrance to each sleeping room. Must be listed by a
nationally recognized, independent lab. Plugs into a dwelling's electrical outlet and has a battery backup. They may be
combined with a smoke -detecting device if the combined device complies with applicable law. (IRC R315)
55 Clothes closet lighting shall be limited to surface -mounted or recessed incandescent fixtures with completely enclosed
lamps, and surface -mounted or recessed fluorescent fixtures.Surface mounted fixtures shall be installed on the wall
above the door or on the ceiling with the following clearances between the fixture and the nearest point of a storage
space: (IRC E4003.12)A. Incandescent fixtures or LED shall have a minimum 12 -inch clearance. B. Fluorescent fixtures shall
have minimum 6 -inch clearance. Recessed fixtures shall be installed in the wall or ceiling with the following clearances: A.
Recessed incandescent fixtures shall have a minimum 6 -inch clearance to the nearest point of storage. B. Recessed
fluorescent fixtures shall have a minimum 6 -inch clearance to the nearest point of storage.
56 Working space must be provided around energized equipment for servicing and maintenance. The minimum
dimensions shall not be less than 36 -inches in depth and 30 -inches in width in front of the equipment. Working space
shall extend to at least 6 -feet, 6 -inches above the floor. (IRC E3405.2)
57 Electrical fixtures installed in wet or damp locations shall be installed so that water cannot enter or accumulate n
wiring compartments or other electrical parts. Fixtures installed in wet locations must be labeled "suitable for wet
locations". Fixtures installed in damp locations must be labeled "suitable for damp locations" or "suitable for wet
locations". Switches or circuit breakers located in wet locations or outdoors must be enclosed in a weatherproof
enclosure. Outdoor receptacles must have a weatherproof enclosure and an in -use cover. Cord -connected fixtures,
hanging fixtures, track lighting, pendants, and ceiling fans shall not be located within3-feet horizontally and 8 -feet
vertically from the top of a tub or shower rim. (IRC E4003.9, E4002.8, E4002.9,E4002.10, E4003.9, E4003.10,-15400 1;
City of
Wheat Ridge
Plumbing Requirements
58 DWV systems shall be tested on compellation of the rough piping installation by water or for Mgn :sy,
other than plastic by air with no evidence of leakage. Either test shall be applied to the drainage system in its
entirety or in sections after rough piping has been installed .l) Water test 10 feet above the highest fitting
connection or to the highest point of the completed system. The system shall prove leak free for 15 minutes.
2) Air test shall maintain 51bs of pressure for 15 minutes.
59 Piping must be inspected and tested prior to concealing. It shall be protected against physical damage and it must be
approved for use and bear the identification of the manufacturer. (IRC P2503, P2603, P2608.1)
60 Bathtubs, walls above bathtubs with shower heads, shower floors, and shower compartments shall be finished with a
non-absorbent surface which extends to a height not less than 6' above the floor. Showers must have a minimum 900
square inches of interior area and a minimum dimension in each direction of 30 -inches. Shower valves must be pressure
balance/thermostatic mixing valves. Shower receptors shall have a curb threshold not less than 1 -inch below the sides
and back of the receptor. The curb shall measure a minimum of 2 -inches to a maximum of 9 -inches above the top of the
drain. (IRC R307, P2708, P2709)
61 The centerline of toilets or bidets shall not be less than 15 -inches from adjacent walls or tub. Toilets, bidets, and
lavatories must have a minimum clear space of 21 -inches in front of the fixture. Lavatories require a 4 -inch clearance to
wall or to a toilet. (IRC P2705)
62 Showers and tub/shower combinations shall have control valves of the pressure balance, thermostatic mixing or
combination pressure balance/thermostatic mixing valve types with high limit stop per ASSE 1016 or CSA13125.1. Tubs
shall also have a control valve as listed for a shower or a water -temperature -limiting device that conforms to ASSE 1070.
The high limit stop for a device shall be set to a maximum of 120°. (IRC P2708.3,P2713.3)
63 Shower doors shall have safety glazing; hinged show door shall open outward. (R308.4.5 , P2708.1)
64 Backflow prevention must be provided to prevent contamination of potable water. This includes but is not limited to:
hose connections, irrigation systems, boilers, solar systems, fire sprinklers, and dishwashers. (IRCP2902.2, Table P2902.3,
P2717)
Insulation
65 R-20 Walls
R-49 Ceiling
R-19 Crawlspace
Window U -Factor .32
Floor R-30
66 Supply Ducts in attics shall be insulated to a minimum of R-8. All other ducts shall be insulated to minimum
R-6. ( N 1103.2.1)
67 Combustible insulation shall be separated a minimum of 3 -inches from fan motors and heat -producing devices.
Insulation shields must be provided where vents pass thorough insulated assemblies and must terminate at least 2 -inches
above attic insulation materials. Can lights must be airtight if located in the building envelope. (G2426.4)
Class 1 or II vapor retarders are required on the interior side of the insulation in framed walls, floors ar d roRf/ceilin of
>, of
the building's thermal envelope. The vapor barrier is not required in construction where moisture or fireezing will not 4
damage the materials, or where the framed cavity (or space) is ventilated to allow moisture to escape. A vap6r_rkarde is
not recommended on a concrete basement foundation wall or in a shower /bath compartment (IRC
Wallboard Requirements
68 The garage shall be separated from the residence and its attic by materials of not less than %-inch gypsum board
applied to the garage side. Garages beneath habitable rooms shall be separated from all habitable rooms above by not
less than 5 8 -inch Type X gypsum board. Where the separation is a floor -ceiling assembly, the structure supporting the
separation shall also be protected by not less than %:-inch gypsum board. (IRC R302.6) Openings between the garage and
residence shall be equipped with solid wood doors not less than 1 -inch in thickness, solid or honeycomb core steel doors
not less than 1 -inch thick, or 20 -minute fire -rated doors. Openings are prohibited between garages and rooms used for
sleeping. (11302.5.1 )Doors between attached garages and living space shall be weather stripped to the degree necessary
to make them airtight and shall be self-closing and self -latching.
69 Enclosed accessible space under stairs shall have walls, under stair surface and any soffits protected on the enclosed
side with %-inch gypsum board (IRC R302.7).
70 Cement, fiber -cement, glass mat gypsum backer and fiber reinforced gypsum in compliance with ASTM C
1288, C 1325, C 1178, or C 1178 and installed in accordance with manufacturer recommendations shall be used as
backers for wall tile in tub and shower areas and wall panels in shower areas. (IRC R702.4.2)
71 Nail spacing for gypsum board % gypum board Ceiling 16oc, 7", nails 12", Type S screws '/2 wall spacing
24"OC, 8" nailspacing. 12"OCscrews. 5/8 ceiling board 16"OC, 7"nails 12"spacing, screws 240C 8".
72 Water-resistant gypsum backing board used as the base or backer for adhesive application of ceramic the or other
required nonabsorbent finish material shall conform to ASTM C1396, C1178 or C1278. It is permitted on ceilings where
framing spacing does not exceed 12 -inches o.c. for %2 -inch thick or 16 -inches o.c. for 5 8 -inch thick gypsum board. Water-
resistant gypsum board shall not be installed over a vapor retarder in a shower or tub compartment and may not be used
where there will be direct exposure to water, or in areas of continuous high humidity. All cut and exposed edges shall be
sealed. (IRC R702.3.8)
73 Floor assemblies, not required elsewhere in this code to be fire resistance rated, shall be provided with a % inch
gypsum wall board membrane, 5/8 inch wood structural panel membrane, or equivalent on the underside of the floor
framing member.(IRC 501.3)
Final Inspection Requirements
74 Buildings shall have approved address numbers, building numbers or approved building identification placed in a
position that is plainly legible and visible from the street or road fronting the property. (IRC 319)
75 All dwellings shall have a controlled method of water dispersal from roofs that will collect and discharge all roof
drainage at least 5 -feet from the foundation. Gutters, downspouts, downspout extensions shall be deemed adequate to
meet these requirements. Surface drainage shall be diverted to a storm sewer conveyance or other approved point of
collection so as to not create a hazard. Lots shall be graded so as to drain surface water away from foundation walls. The
grade away from foundation walls shall fall a minimum of 6 -inches within the first 10 -feet. (IRC R401.3 and R801.3)
Swimming pools, fountains, hot tubs, spas, and hydro -massage "Jacuzzi" tubs and similar installations shall comply with
all provisions of the IRC for the approval of bonding equipment and lighting. All 15 and 20 amp, single-phase 125 -volt
receptacles located within 20 -feet of the inside walls of pools, outdoor spas and hot tubs shall be protected by a GFCI.
Motors and equipment must be accessible without damaging the building structure or building finish. (IRC E_4201;E4,Z03,
EE4204, E4205, E4206) r'�tyof
The reinforcing shell of the pool shell, metal forming shells, coping stones, deck, brackets of niche fixt res, in
and electrical equipment, located less than 5 -feet horizontally and less than 12 -feet above maximum w d�,9e
swimming pools and built in place hot tubs shall be bonded together. The parts specified above shall be c e
equipotential bonding grid. (IRC E4204.2)
o�
ry � 8905
"
0
N
13
cU)
>,
�-
CA
1 ry
O
y
V).jv
J
,
z
�0
s
LQ
C
m
m
^'�
` I
C
J
W
o�
ry � 8905
"
0
N
Q�
J
CA
1 ry
O
y
J
,
z
s
m
IL 00
C
J
o
�
m
_I L
o�
ry � 8905
III
0
III
-J U
96979
L4tZiv174 zt06M
E
5b0404
7
0
N
N
� o
N3
N N
c � .
O U 9 U)
E
LL 3
3
m Z cv m
N
Q j
J
CA
1 ry
O
y
J
m
-J U
96979
L4tZiv174 zt06M
E
5b0404
7
0
N
N
� o
N3
N N
c � .
O U 9 U)
E
LL 3
3
m Z cv m
a�
5210409
S?JOSOS
9992 i 9992
9992
09
� Ry ry
3
z --
890LZ SNOSOS
SNOSOA
- 9905
S210SOS
/
✓
�
�
0
N
LP ,
m
0
m
HOObQZ Ha04QZ
HCOKC
HQGbQZ
0
0
N
LU
� m
Z
M
M
o
�
L
o
I
LL
-_
LL-
-�-�
73
�--�
� I
•X
Lu
0
0
N
LU
� m
Z
i CITY OF WHEAT RIDGE
Building Inspection Division
r' (303) 234=5933 Inspectionline
(303) 235-2855 Office • (303) 237-8929 Fax
INSPECTION NOTICE
Inspection Type: c '
Job Address: jp~~ frLr/i`
Permit Number: 60 7'36
04("(y 6,0,11 U"tt
❑ No one available for inspection: Time la AM
Re-Inspection required: Yes 4
"When corrections have been made, call for re-inspection at 303-2345933
Date: I~ Q Inspector: rT R,
DO NOT REMOVE THIS NOTICE
CITY OF WHEAT RIDGE
y ♦ 41
fr Building Inspection Division
~ (303) 234-5933 Inspection line
(303) 235-2855 Office • (303) 237-8929 Fax
INSP(tECTI/O~N NOTICE
Inspection Type: I/m f
Job Address: l a lam. 30 (
Permit Number: 0t S-2)A
1-1 No one available for inspection: Time X60 AM
Re-Inspection required: Yes ~i
'When corrections have been made, call for 10 -in~~spe coon t 303-234-5933
Date: lInspector: ~~~.c ~I 1ao~T
DO NOT REMOVE THIS NOTICE
f
City of Wheat Ridge
Homeowner Roof PERMIT 093363
PERMIT NO: 093363 ISSUED:- 10/15/2009
JOB.`ADDRESS: 12296.:W 34TH PL `EXPIRES: 04/13/2010
DESCRIPTION.:.: Reroof.. 31.33 sqs
CONTACTS
owner 303/204-8426 Robert Neal'.
* * ` PARCEL INFO
ZONE CODE: UA USE: UA
SUBDIVISION:` 0696 `..BLOCK/LOT#: 0/
**"FEE SUMMARY ESTIMATED PROJECT VALUATION: 5,545.41.
FEES
Permit Fee 162.90
Total Valuation .00
Use .`.Tax 99 . 82
**:...TOTAL :..262.72
conditions:
i nail installation mid roof inspection required'. Board sheathing spaced more
_hall a 1/2 of an inch apart requires plywood overlay on entire roof. Ice and
Hater shield required from eave edge to 21 inside exterior walls.'
u**Contractor/Property owner shall provide ladder(s) secured in 'place for.
inpsections:'.
Subject to field inspection.
I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable
ordinances, rules or regulations of the City of-Wheat .Ridge . or.: covenants, easements or restrictions of record; that all
measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this
application and that I assume full responsibility for compliance with the Wheat Ridge Building: Code (I.B.C) and all other
applicable Wheat Ridge ordinances, for work under this permit. Plans subject to field inspection.
Signature of contractor/owner'.date
This permit was issued in accordance with the provisions set forth in your application and is subject to the laws of the
State of Colorado and to the Zoning Regulations and Building Codes of Wheat Ridge, Colorado or any other applicable
ordinances of the City.
This permit shall expire 180 days from the issue date. 'Requests for an extension must be received prior to expiration
date. An extension maybe granted at the discretion of the Building Official.
If this permit expires, .:a new permit may be :acquired for a fee of -r one-half the amount normally required, provided no
changes have been or will be made in the original plans and specifications'. and any suspension or. abandonment has not
exceeded one l,(1) year. If changes have been or if suspension or abandonment exceeds one (1) year, full fees 'shall
be paid for anew ;permit.
No work of any manner shall be done that will. change the natural flow of water causing a drainage. problem.
Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive
written approval on inspection card before proceeding with successive phases of the job'.`
The. issuance of a permit or the approval of drawings and. specifications shall`. not be construed to be a permit for, nor
an (approval of, any violation of the provisions of the building codes or any :ether ordinance, law, rule or regulation.`..
All plan review s ect to field inspections.
ignature of Ch ldmg.:official ..date
NSPECTIO REQUEST LINE: (303)234-5933 BUILDING OFFICE: (303)235-2855
.EQUESTS MUST: BE MADE BY 3PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY.
~oF"'"Etr~a City of Wheat Ridge Building Division Date:
m 7500 W. 291h Ave., Wheat Ridge, CO 80033
Office: 303-235-2855 * Fax: 303-237-8929 Plan M
°otoRroo Inspection Line: 303-234-5933
Permit A.
Building Permit Application
Prof, y Address. az% Lam. 31/
Property Owner (please print): R 17 e,,- ~ 1\1eo, Phone: 303-Za ll-P12(0
Mailing Address: (if different than property address)
Address: eo t30}(, G,Z3
City, State, Zip: t,,-j1, e,(,t (4r ~ , CO gp 3Y
V
Contractor: ~9w.2 v wv~2r
Contractor License Phone:
Stib Contractors:
Electrical City License Plumbing City License Mechanical City License*
Company: Company Company:
Exp. Date: Exp. Date: Exp. Date:
Approval: Approval: Approval:
Use of space (description): Construction Value: $
Description Of<work: (as calculated per the Building Valuation Data sheet)
Plan Review (due at time of submittal): $
Sq. Ft./L.Ftadded: Squares3t.33 BTU's Gallons Amps
OWNER
Ihereby /CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT
certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances,
rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and
allegations made are accurate; that 1 have read and agree to abide by all conditions printed on this application and that I assume full
responsibility for compliance with the Wheat Ridge Building Code (I.B.C) and all other applicable Wheat Ridge Ordinances, for work
under this permit. Plans subject to field inspection. -
CIRLCE ONE:: (OWNER) (CONTRACTOR) or PERSONAL REPRESENTATIVE of (OWNER) (CONTRATOR)
PRINT NAME: RoGz, r f Ne4-/ SIGNATURE: -1~, ,r? n~t~ Date: iO1is/O39
Inspections will not be made unless this card is posted on the building site
Call by 3:00 PM to receive inspection the following business day.
F
Electrical
V�J
Lath / Wall tie
Plumbing -
Mid -Roof = ��„
,
Electrical Service
INSPECTO MUST SIGN ALL SPACES -PEI�F G TO THIS JOB
FOUNDAT TIONS
DATE
INSPECTOR
INITIALS
COm ENTS:
Footings/Caissons
Gas Piping"
StemwallYcrete
Encased G
Fire Department
INSPECTIONS TO BE
Reinforcing thic
Framing
INSPECTIONS FOR PLANNING & ZONING, FIRE AND PUBLICE WORKS
SHOULD BE CALLED AT LEAST ONE WEEK PRIOR TO FINAL INSPECTIONS.
Insulation '.
Weatherprh Drain
- "NOTE: ALL ITEMS MUST BE COMPLETED AND APPROVED BY PLANNING AND ZONING, BUILDING AND PUBLIC WORKS BEFORE A
Drywall Screw
Sewer Ser
Water Service Lines-
'POUR NO CONCRETE UNTIL ABOVE HAS BEEN SIGNED
.`CONCRETE SLAB FLOOR
Electrical (Underground)
Plumbing (Underground)
Heating (Underground)
DO NOT POUR FLOOR UNTIL ABOVE HAS BEEN SIGNED
ROUGHS `.
OCCUPANCY NOT PERMITTED UNTIL
---- -------- — — - - -- — - - --
_.. OTECTTIfiSCAF
'Sheathing
Electrical
Lath / Wall tie
Plumbing -
Mid -Roof = ��„
Electrical Service
Rough Electric
Roof
Rough Plumbing
Gas Piping"
Building Final
Rough Mechanical
Fire Department
- ' ABOVE
INSPECTIONS TO BE
SIGNED PRIOR TO PROCEEDING
Framing
INSPECTIONS FOR PLANNING & ZONING, FIRE AND PUBLICE WORKS
SHOULD BE CALLED AT LEAST ONE WEEK PRIOR TO FINAL INSPECTIONS.
Insulation '.
- "NOTE: ALL ITEMS MUST BE COMPLETED AND APPROVED BY PLANNING AND ZONING, BUILDING AND PUBLIC WORKS BEFORE A
Drywall Screw
FINALS
Electrical
Plumbing -
Mechanical
Roof
y
Building Final
Fire Department
-R.O.W & Drainage
INSPECTIONS FOR PLANNING & ZONING, FIRE AND PUBLICE WORKS
SHOULD BE CALLED AT LEAST ONE WEEK PRIOR TO FINAL INSPECTIONS.
Parking &.Landscaping;
- "NOTE: ALL ITEMS MUST BE COMPLETED AND APPROVED BY PLANNING AND ZONING, BUILDING AND PUBLIC WORKS BEFORE A
OF A'CERTIFICATE OF OCCUPANCY NOR PERMISSION FOR OCCUPANCY.
RTIFICATE OF OCCUPANCY IS ISSUED