HomeMy WebLinkAbout4905 Van Gordon Streetn e FBI GENERAL NOTES 1. OWNER I CLIENT RESPONSIBILITIES. REFERENCE IS MADE THROUGHOUT THESE GENERAL NOTES TO RESPONSIBILITIES AND STANDARDS OF CARE TO BE FULFILLED BY THOSE PROVIDING SERVICES IN THE DEVELOPMENT AND CONSTRUCTION OF THIS PROJECT. OWNER / CLIENT SHALL BE RESPONSIBLE FOR ADHERENCE TO THOSE REQUIREMENTS BY THE OWNER, BUILDER, DEVELOPER, GENERAL CONTRACTOR SUBCONTRACTORS AND OTHER PROFESSIONAL CONSULTANTS NOT RETAINED BY THE DESIGNER. 2. BUILDER'S SET THE SCOPE OF THIS SET OF PLANS IS TO PROVIDE A "BUILDER'S SET- OF CONSTRUCTION DOCUMENTS AND GENERAL NOTES HEREINAFTER REFERRED TO AS "PLANS". AFTER FORMAL REVIEW AND APPROVAL, THIS SET OF PLANS IS SUFFICIENT TO OBTAIN A BUILDING PERMIT; HOWEVER, ALL MATERIALS AND METHODS OF CONSTRUCTION NECESSARY TO COMPLETE THE PROJECT ARE NOT NECESSARILY DESCRIBED. THE PLANS DELINEATE AND DESCRIBE ONLY LOCATIONS, DIMENSIONS, TYPES OF MATERIALS AND GENERAL METHODS OF ASSEMBLING OR FASTENING. ANY SPECIFICATION BOOK RECEIVED WITH THIS PLAN SET SPECIFIES THE PARTICULAR PRODUCTS OR MATERIALS RECOMMENDED FOR THIS HOME DESIGN. THE IMPLEMENTATION OF THESE PLANS REQUIRES AN OWNER/ CLIENT/ CONTRACTOR THOROUGHLY KNOWLEDGEABLE WITH THE APPLICABLE BUILDING CODES AND METHODS OF CONSTRUCTION SPECIFIC TO THIS PRODUCT TYPE AND TYPE OF CONSTRUCTION. 3. BUILDING MAINTENANCE: THE EXPOSED MATERIALS USED IN THE CONSTRUCTION OF THIS PROJECT WILL DETERIORATE AS THE COMPLETED PROJECT AGES UNLESS PROPERLY AND ROUTINELY MAINTAINED. OWNER/ CLIENT SHALL PROVIDE OR CAUSE THE DEVELOPMENT OF A PLAN TO KEEP THESE EXPOSED MATERIALS PROTECTED AND MAINTAINED. 4. CODES: ALL CONSTRUCTION SHALL COMPLY WITH THE MOST STRINGENT REQUIREMENTS OF ALL CURRENT APPLICABLE CITY, COUNTY, STATE AND FEDERAL LAWS, RULES, CODES, ORDINANCES AND REGULATIONS. IF THE GENERAL CONTRACTOR OR ANY SUBCONTRACTOR PERFORMS ANY WORK IN CONFLICT WITH THE ABOVE MENTIONED LAWS, RULES, CODES, ORDINANCES AND REGULATIONS, THEN THE CONTRACTOR IN VIOLATION SHALL BEAR ALL COSTS OF REPAIR ARISING OUT OF THE NON - CONFORMING WORK. 5. PERMITS: THE GENERAL BUILDING PERMITAND PLAN CHECK SHALL BE SECURED AND PAID FOR BY OWNER/CLIENT. ALL OTHERS PERMITS SHALL BE SECURED AND PAID FOR BY THE SUBCONTRACTOR DIRECTLY RESPONSIBLE. 6. INSURANCE: THE GENERAL CONTRACTORAND EVERY SUBCONTRACTOR PERFORMING WORK OR PROVIDING SERVICES AND/OR MATERIALS FOR THE WORKARE REQUIRED TO PURCHASE AND MAINTAIN IN FORCE "ALL RISK" BUILDERS INSURANCE PRIOR TO COMMENCEMENT OF THE WORK AND/ OR FURNISHING LABOR, SERVICES AND MATERIALS. EACH ALL RISK- POLICY SHALL BE IN AN AMOUNT SUFFICIENT TO COVER THE REPLACEMENT VALUE OF THE WORK BEING PERFORMED AND/ OR THE LABOR, SERVICESAND MATERIALS BEING SUPPLIED BYTHE GENERAL CONTRACTOR, SUBCONTRACTORS, DESIGNER, AND ALL PROFESSIONAL CONSULTANTS. 7. INSURANCE: OWNER/ CLIENT SHALL CAUSE THE GENERAL CONTRACTOR AND EVERY SUBCONTRACTOR PERFORMING WORK OR PROVIDING SERVICES AND / OR MATERIALS FOR THE WORK TO PURCHASE AND MAINTAIN GENERAL LIABILITY INSURANCE. 8. NAMED PRODUCTS: THE ARCHITECT MAKES NO GUARANTEE FOR PRODUCTS IDENTIFIED BY TRADE NAME OR MANUFACTURER. 9. SCOPE: THE GENERAL CONTRACTOR AND SUBCONTRACTORS SHALL FURNISH ALL LABOR, EQUIPMENT, AND MATERIAL INDICATED ON THE PLANS AND REASONABLY INFERRED OR REQUIRED BY THE APPLICABLE CODES. 1 SUBSTITUTION: SUBSTITUTIONS OF SPECIFIC MATERIALS OR PRODUCTS LISTED ON THIS SPECIFICATION SHEET SHALL NOT BE MADE WITHOUT WRITTEN AUTHORIZATION BY OWNER/ CLIENT THE GENERAL CONTRACTOR AND ANY SUBCONTRACTOR SHALL NOT MAKE THE STRUCTURAL SUBSTITUTIONS OR CHANGES WITHOUT PRIOR WRITTEN AUTHORIZATION FROM THE STRUCTURAL ENGINEER. 2 CHANGES: ANY ADDITION, DELETION, OR CHANGE IN THE SCOPE OF THE WORK DESCRIBED BY THE PLANS SHALL BE BY WRITTEN CHANGE ORDER ONLY. ANY APPROVAL FROM THE BUILDING OFFICIAL FOR A CHANGE IN THE WORK SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. 31NTENTION: THE GENERAL CONTRACTOR SHALL ENSURE THAT ALL LABOR, MATERIALS. EQUIPMENT AND TRANSPORTATION SHALL BE INCLUDED IN THE WORK FOR COMPLETE EXECUTION OF THE PROJECT. THE DESIGNER SHALL NOT BE RESPONSIBLE FOR THE MEANS AND METHODS OF CONSTRUCTION. 4 REVIEW OF DRAWINGS: THE GENERAL CONTRACTOR AND ALL SUBCONTRACTORS SHALL REVIEW THE FULL CONTENT OF THE PLANS FOR DISCREPANCIES AND OMISSIONS PRIOR TO COMMENCEMENT OF WORK. THE GENERAL CONTRACTOR AND ALL SUBCONTRACTORS SHALL BE RESPONSIBLE FOR ANY WORK NOT IN CONFORMANCE WITH THE PLANS OR IN CONFLICT WITH ANY CODE. 5 USE OF THE DRAWINGS: DIMENSIONS TAKE PRECEDENCE OVER SCALED MEASUREMENTS. DETAILSAND SECTIONS ON THE DRAWINGS ARE SHOWN AT SPECIFIC LOCATIONS AND ARE INTENDED TO SHOW GENERAL REOUIREMENTS THROUGHOUT. DETAILS NOTED'TYPICAL" IMPLY ALL LIKE CONDITIONS TREATED SIMILARLY, UNLESS NOTED OTHERWISE. THE ARCHITECTURAL DETAILS SHOWN ARE INTENDED TO FURTHER ILLUSTRATE THE VISUAL DESIGN CONCEPT AND THE MINIMUM RECOMMENDED WEATHER PROTECTION FOR THIS PROJECT. BUILDING CODE REQUIREMENTS, STRUCTURAL CONSIDERATIONS, TRADE ASSOCIATION MANUALS AND PUBLICATIONS AND PRODUCT MANUFACTURER'S WRITTEN INSTRUCTIONS SHALL ALSO BE CONSIDERED IN ORDER TO COMPLETE THE CONSTRUCTION OF THE DETAILS, AND IN SOME CASES MAY SUPERCEDE THE DETAILS. 6 APPROVED DRAWINGS: THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK BETWEEN THE DIFFERENT SUBCONTRACTORS AND REQUIRING ALL SUBCONTRACTORS TO USE THE MOST CURRENT BUILDING DEPARTMENT APPROVED SET OF PLANS. 7 CUTTING AND PATCHING. ALL SUBCONTRACTORS SHALL DO THEIR OWN CUTTING, FITTING, PATCHING, ETC. TO MAKE THE SEVERAL PARTS COME TOGETHER PROPERLY AND FIT IT TO RECEIVE THE WORK OF OTHERTRADES. 8 CLEAN UP: ALL TRADES SHALL, AT ALL TIMES, KEEP THE PREMISES FREE FROM ACCUMULATION OF WASTE MATERIALS OR RUBBISH CAUSED BY THEIR WORK. SUBCONTRACTORS SHALL REMOVE ALL RUBBISH, TOOLS, SCAFFOLDING AND SURPLUS MATERIALS AND LEAVE THE JOB IN A BROOM - CLEAN CONDITION. ALL FIXTURES, EQUIPMENT, GLAZING, FLOORS, ETC., SHALL BE LEFT CLEAN AND READY FOR OCCUPANCY UPON COMPLETION OF THE PROJECT. 9 STORAGE OF MATERIALS: THE GENERAL CONTRACTORAND SUBCONTRACTORS SHALL BE RESPONSIBLE FOR STORING THE MATERIALS ON THE SITE ACCORDING TO MATERIAL SUPPLIERS' OR MANUFACTURERS' INSTRUCTIONS. THE MATERIALS SHALL BE KEPT SECURE AND PROTECTED FROM MOISTURE, PESTS, AND VANDALS. ANY LOSS ARISING OUT OF MATERIALS STORED AT THE SITE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR OR SUBCONTRACTOR WHO STORED THE DAMAGED OR LOST MATERIALS. 10 ALL WORK DESCRIBED IN THE DRAWINGS SHALL BE VERIFIED FOR DIMENSION, GRADE, EXTENT AND COMPATIBILITY TO THE EXISTING SITE, ANY DISCREPANCIES AND UNEXPECTED CONDITIONS THAT AFFECT OR CHANGE THE WORK DESCRIBED IN THE CONTRACT DOCUMENTS SHALL BE BROUGHT TO THE DESIGNER'S ATTENTION IMMEDIATELY. DO NOT PROCEED WITH THE WORK IN THE AREA OF DISCREPANCIES UNTIL ALL SUCH DISCREPANCIES ARE RESOLVED. IF THE CONTRACTOR CHOOSES TO DO SO HE SHALL BE PRECEDING AT HIS OWN RISK. 11 OMISSIONS FROM THE DRAWINGS AND SPECIFICATIONS OR THE MIS -DESCRIPTION OF THE WORK WHICH IS MANIFESTLY NECESSARY TO CARRY OUT THE INTENT OF THE DRAWINGS AND SPECIFICATIONS, OR WHICH IS CUSTOMARILY PERFORMED, SHALL NOT RELIEVE THE CONTRACTOR FROM PERFORMING SUCH OMITTED OR MIS -DESCRIBED DETAILS OF THE WORK AS IF FULLY AND COMPLETELY SET FORTH AND DESCRIBED IN THE DRAWINGS AND SPECIFICATIONS. SITE CONDITIONS: ALL CONTRACTORS AND SUBCONTRACTORS SHALL VERIFY DIMENSIONS AND CONDITIONS AT THE SITE PRIOR TO COMMENCEMENT OF THEIR WORK. FAILURE TO DO SO SHALL NOT RELEASE THEM FROM THE RESPONSIBILITY OF ESTIMATING THE WORK. IF ANY VARIATION, DISCREPANCY OR OMISSION (BETWEEN THE INTENT OF THESE CONTRACT DOCUMENTS AND THE EXISTING CONDITIONS ARE FOUND, THE CONTRACTOR OR SUBCONTRACTOR SHALL NOTIFY THE ARCHITECT IN WRITING AND OBTAIN WRITTEN RESOLUTION FROM THE ARCHITECT PRIOR TO PROCEEDING WITH ANY RELATED WORK. 12 MOLDAND MILDEW REMEDIATION: CONTRACTOR SHALL FOLLOW SPECIFICATIONS FOR MILD AND MILDEW REMEDIATION AS SET FORTH ON SHEETS Al2 AND A13. CONTRACTOR SHALL NOTIFY OWNER IN WRITING THAT REMEDIATION HAVE BEEN COMPLETED AS SPECIFIED. 1. ALL DIMENSIONS TO BE FIELD VERIFIED. 2. VERIFY EXISTING CONDITIONS WHICH MAY DIFFER THAN SHOWN ON THESE PLANS. 3. PROVIDE FIRE SUPPRESSION SYSTEM IN H-3 AREAS ONLY 1 -11 ' f1�� .t 1 a I ' RuT�,) I I I it tr L9 STREET VIEW C1 D1 Booth Addition to �* Existing Lab Facility W Ave Weam Ave ALTA VISTA AREA N GRACE PLACE W 581M1 Ave WRod Ave a W5AM1 Ave WHth Ave Ralson Rd NDLELIGHTo _a + Stenger Soccer ComplexQ 2 r a Wynn Ave Gra,dI Ave Van Bibb O 8 E R O N JOpen �e RAINBOW = RIDGE LERI DGE ARVADA TATES PLAZA AREA t 13 Arvelo C f n Shopl d Ave WsennAve Echters Nursery a w5andAve si �y ITEMS 0' &Garden Center n ' 4805 Van Gtrdon 61, SORT h Ave ' • Wheat Ridg', CC 80033 -- _ a � MANSFIELD Mt. Olivet Catholic \ EI'I a Cemetery: CFCS_. PTARMIGAN y. © � KIPLING CONDOM D w04rM1 Ave-=--=� woatn Ave �RUITDALE o K'LING II HEIGHTS e sA Clear Ctee ' LOCATION MAP PROJECT 4805 Van Gordon Street INFORMATION: Wheat Ridge, CO 80033 EXISTING 1970's CONCRETE SINGLE STORY STRUCTURE. MULTI TENANT, NON-COMBUSTIBLE UNPROTECTED (EXCEPT IN H - CLASSIFICATION AREAS) PROVIDE NEW CRI DRI EXTRACTION BOOTH AND ASSOCIATED HVAC AND PROJECT VENTILATION PER CODE DESCRIPTION & SCOPE LIMITED TO SOUTH END OF BUILDING, EXISTING TENANT SCOPE OF WORK: UPGRADE. INSTALLATION OF UL -LISTED C1D2 BOOTH AND SUPPORTING AC/RTU SYSTEM. NO EXTERIOR CHANGES, NO PLUMBING CHANGES, EXISTING SECURITY SYSTEM TO REMAIN OCCUPANCY: THE BUILDING IS GROUP F1 & B-1 OCCUPANCY EXCEPT FOR DESIGNATED THE H3 ACCESSORY IN THE PROJECT BOOTH AREA WHICH IS PROTECTED WITH AN AUTOMATIC DRY CHEMICAL FIRE PROTECTION SYSTEM. SEE FLOOR PLAN. F1 OCCUPANCY: 6,330 S.F. H3 OCCUPANCY: 370 S.F. TOTAL: 63700 S.F. CODE USE GROUP: FACTORY INFORMATION: CLASSIFICATION: F1 w/ACCESSORY USES H3 (LP GAS) CONSTRUCTION: 1116 OCCUPANCY: 24 CODES: 2018 IBC, 2018 IMC, 2018 IPC, 2018 IFGC, 2018 IECC, 2017 NEC, ANSI A117.1 2019 & CITY OF WHEAT RIDGE AMENDMENTS eat "REVIEWED FOR CODE COMPLIANCE" These drawings were reviewed under the applicable laws in effect: at the time of submittal. Reasonable effort was exercised in checking for code compliance. The star ing of these documents shall not be construed W be a permit for, or an approval of any violation of state and/or local codes, ordinances or amendments thereto. Plan Reviewer Money Date 08/06/2021 PERMIT APPLICATION NUMBER: 202100259 SHEET INDEX: SHEET SHEET LABEL NUMBER TITLE Al 1 Cover Sheet A2 2 Code Review & Comments A3 3 Floor Plan - Full Building 1 4 HVAC Plan M2 5 HVAC NOTES 1 6 Mechanical Specs M4 7 RTU Roof Plan 1 8 COMcheck Compliance M6 9 HAL Booth Overview 1 10 Booth Plan & Elevations M8 11 Booth Air Flow Info. 1 12 Booth Safety Details 1 M10 13 Booth Safety Details 2 1 14 Compliance Certificates M12 15 Booth Components E1 16 Electrical Plan E2 17 Electrical Panels LS1 18 Fire Supression LS2 19 Fire Supression LS3 20 Fire Supression 10 Anther Architects, PLLC Architecture + Engineering 3727 Candia Drive Punta Gorda FL 33950 800-243-0528 734-709-7297 gburgh@gmail.com THE ERNEST OF THE CONTRACT DEVESENTS IS TO i AUL TONS INERMISMA FOR THE PROPER EXECUTION AND COMITTIEN, OF THE WERK TV THE CONTRACTOR THE COMPACT OVERUMENTS ME �w�� ME 1I Is TO THE EATENT STINMENEW Mi ONE STEVESTROT ME ROSSI INTENSE FROM THEM M III MEMEMARY el ME ENE INFORMATION SHMMIN OR THE SHISET ONES NOT UTHINIM CARGES TO CONTRACT TOM OR THIN UNUES E O 4_0 �r i }I O O CIO E O O TIRRE N C Q N CL Teee MID U E E ML t a -EIRE M ERRRRRE (D 6 caM C:) z /lURERRIP m LLQ U L _ _Y 113 O C7OIII U mW CC� (� i U }ILO ca N U X C) . > °' o LU L Cover Sheet F�� 7 City of W heat Ps- 4805 Van Gordon $[. 6) Planar 1,,* if the cause is prelmd with un 7mM,y Imn pueodemins 415.5 at INC. ask. In alavkitts with Nc ltthnkal supWrt,mmc^Iativcm HA on Tmbnolop, Brien B. indicated N,lmmanc LuwuuNlrYDMIMMFM TXpmlaatptanswaaroWewadbr compliance win Me mOowmB codes imndards:MIS Mike be frond on shin MIO. IBD,M181RC,20181MC,20181PD,2018 OC, 20181ECC, 2017 NEC, ANSI ICC ANTA MO add Applicanlemail: airy ACommm. Ibe Clrydr WM1 Ridge Amendments. grit Money 3) Pln¢ identify me=cut, If do M1vudulu melanin being atmM Intl identify 0...k ouiwufe ge pn mquim core pmgnming to inugnnt quiprtrntinm Ne NALOS,WIhrnNcwamblywould PermilCmrtlinalpr email: ]I Plmscidcntifyallml aswmbli within ... pu ow,"icn 508 of 6, 1111. TO FXPEOIM GRWECT APPROVAL Powe vim a www response indimtn how and wham ion 30 of the lBC. PmtaGiD CtlMlnn: mattlon BOMA, MIVM VXwIMNOIXYrerry eaM comment was mWva! m Me pkns. RBaIEm II pevlWYy mvreaed plans, updated plans and edimml F.I mmmo Amt A3 in, UL Lab esnnblim. Applicants Rapnnve Evlenen top in GB]pwmlmfmixN LP gm IJG°ry pmparc&]�n- peel' Edina rc&ncM arm lMu nanny camemx liens, up m IN pound, of miactl LP gas l hWµaue®]0%n. probact Aged a svanwmm St city-, Commrnt plena call sem 111 the plain owkd Niger Bumnou dl Plass Aetify iftAespxeisprvvideJ with an automatic frc deletion synem eude xatiun dlS JODAe IBC PotmOCpplimue fAle: }/09/21 etmltlppl'xmimp 2@tt@59 BReviewed antl Was at his nWrwy ai t iR Safety m, me wamaum m Apoicm as NA Plan Chaka: Kirk Money, ph (720) 34-0755, a kirkmomy®aeim Apphemo Repnn..: The BmlhewmmopmsmanmmmUJI-anH was Brtanppmaiw,nnm. Plan ReWew Conmeam: BuiMing.Aaeuibiliry. Energy. Mahvnicel and umbing. d,gCommeankel Building Commenm: Pypllcanf. IYa Avne: (3NIPa&Man can Molts. Alae, idcntifYOtevdlu'rot oauprry Bassi&n,m nxl tit apue parade sulmn Io trna Devils oftAls system may be sem on SAen M6. He1ofire low gpplk.,n, kown se: TAe rrw ClarenceAir RTU (AI-IBT-150-162)ia fm heated vironly: Nis is only usM to AplYinnn Rcepnse 1MmeinkmlvpmismF-I OmupmrywiN en eine H.2 bMhlmnd insiM in gertmmid provide make up air dating time Ne hams to in demiw w rmn the lu Ne City's Comment. Applicant email: niMirestarco®wl.epn fa a die®mI of� parry Wenifimtiana, PetmilCwainelrc Ciryh Comment'. 02013v00]SS SM Efflaw.amond is Full Modunneq AniMITEy%ERci.rcy,aM6:1Mu Tommi fm Tumdowo far m, Fol Tom iwa Undo ne slur N whne Nesumid, err mdaunide air far me mmmiw bmNiremming (ram. Plmee provide ell 5) Plnse clarify if the cause is pmvidM with an automatic frc ME profitable parade sect am 4156 art IBC. Applicmn Rmpnm Yee. An abamiil tlry mi Am, nklm rywmnirpmviaei in Jr HAL&Uo IlkMmry P REVIEWCOMMENTB 4805 Van Gordon $[. 6) Planar 1,,* if the cause is prelmd with un 7mM,y Imn pueodemins 415.5 at INC. ask. In alavkitts with Nc ltthnkal supWrt,mmc^Iativcm HA on Tmbnolop, Brien B. indicated Pormtt Applkdbnk A 24V erplwion pwfenmgemy tlum IN idM"CHALW hmanuf'amm. Deuileofmiealmmm TXpmlaatptanswaaroWewadbr compliance win Me mOowmB codes imndards:MIS Mike be frond on shin MIO. IBD,M181RC,20181MC,20181PD,2018 OC, 20181ECC, 2017 NEC, ANSI ICC ANTA MO add Applicanlemail: airy ACommm. Ibe Clrydr WM1 Ridge Amendments. grit Money haw M1rytusmadnw ngz. Noetlut 5hmtl of Ne HAL Evmekon dewing lvhx M6l speiaea Ne Mssld mquim core pmgnming to inugnnt quiprtrntinm Ne NALOS,WIhrnNcwamblywould PermilCmrtlinalpr email: ]I Plmscidcntifyallml aswmbli within ... pu ow,"icn 508 of 6, 1111. TO FXPEOIM GRWECT APPROVAL Powe vim a www response indimtn how and wham Applicmn Rm se:Per Tab SIB9. two rated uvumblicsurcprovgedelOng Ort,kmirmg xNl wiN Ne eaM comment was mWva! m Me pkns. RBaIEm II pevlWYy mvreaed plans, updated plans and edimml F.I mmmo Amt A3 in, UL Lab esnnblim. suppsmirq dcwmenm with edit suMty nl rev order moon of any plan mvww mmrrent, city-, Commrnt plena call sem 111 the plain owkd Niger anti I ml c,tend lwomh or mom, PereMe wwm 5106.7 a Ne IMCApplicants Aeeneibility Kim m THE FOLLOMNG RESPoNSEDS AREAUTHORED BY 3 TBURGH JUNE 10.2021 BReviewed antl Was at his nWrwy ai t iR Safety m, me wamaum m Apoicm as NA Plan Chaka: Kirk Money, ph (720) 34-0755, a kirkmomy®aeim Cirybe meet. Plan ReWew Conmeam: BuiMing.Aaeuibiliry. Energy. Mahvnicel and umbing. d,gCommeankel Building Commenm: Eoa Cweelon: D Pleeec attorney all arupmydaatifc ......Immigammmemmprcy TLinH W , wammue. aneis II Ieme JemOnn,me in the momirmni davmme Not the mahmical system, nm amalimt wait mod, woman can Molts. Alae, idcntifYOtevdlu'rot oauprry Bassi&n,m nxl tit apue parade sulmn Io trna bill Ifor'. He1ofire low gpplk.,n, kown se: TAe rrw ClarenceAir RTU (AI-IBT-150-162)ia fm heated vironly: Nis is only usM to AplYinnn Rcepnse 1MmeinkmlvpmismF-I OmupmrywiN en eine H.2 bMhlmnd insiM in gertmmid provide make up air dating time Ne hams to in demiw w rmn the lu Ne the train work au. An F -I OcwM is Newle Weuifienion in the ndaem spit Ieaw rthr m drat AJ ex To TAB mocatnim HVAC RTU'sortm,I cash and will end exmmo wino The owo at500CFMube fa a die®mI of� parry Wenifimtiana, W on. SP.m Mditut e Ho topics,; 161D Ohre Fag is Ciryh Comment'. SM Efflaw.amond is Full Modunneq AniMITEy%ERci.rcy,aM6:1Mu Tommi fm Tumdowo far m, Fol Tom iwa Undo ne slur N whne Nesumid, err mdaunide air far me mmmiw bmNiremming (ram. Plmee provide ell mel MMU Links glml BumuuW HmtEubenya."Pn Table C43.3215),thia wit meentkmhrtquimmrnl 2) Name dmtify all item, being swmdwirm this Mmc uA include the amount, beingnured atMaysawhu a180%<R iemy. Apldicmts Rmpn.e'. Ge d,tmd,,M am oily;, Ne Bmtn mo ... for l W p ... as If an LPpa (JesipmWw&ma. a bonne, Ne Booth is red for l Mrs) 1n No encrlor ueutod mutvgc umut rcw1I1M Gry'a Commmu less than 4th Pounds ofmixed ga.. Raw input mmctins forthe"maim go s.melading Oiromin aM Applicants ResWnse: There em w new peels dm Nis wwNm An existing elamnl plan has ample 0oxeram not swmd in this mount game, but adam ;manly 6 putds Afprac.vingm Send is brought t the 2) Please demonmw in mmmnscum davmelns that the electrical power and lighting system is compliant ndred baron mth... h ma Mmgaydc. Tni, mmm.l am,aeandar.d ran Na Waw pmntr am. a he wwrmdv, mn e4e,fthe lEoA NOM vide o(tha building. Who pme¢ving i,a,mpkm. Ne finivhad pada,]iv am,N mthev"IEcompiie Applieme, Respnse. Th,imYllalim of,,m,uWmYs mW tum ofw, LED brain, Ne MMM1ivcmw.m rypiully IN than 10 pond, of mumtiaL fioma lih sahrymNp'm. As the oRmm maymmin means in Ne mmn fm pearofid iw Nem iaa vibilily SEEM, light mold be sM1uloFwhcnthebwth is ouupi maw p^+cresigni! mtva(Y 4805 Van Gordon $[. ured in Nccvmedon prva'us. TMeis noumafnefwoAine e^cc+^ulaNe ofthebwN,WNcm( tic ask. In alavkitts with Nc ltthnkal supWrt,mmc^Iativcm HA on Tmbnolop, Brien B. indicated Pormtt Applkdbnk bevdinc vrntihlim ofNc bumM1 alit!/N cxccma Nc zquinmcm. M1e cane rax nwvrto(myavmmm impaling vnactrypmy mmtAertesrnaF Mike Phone: WemiBM Bur enaplov on prmfmory senwr-s ave lnbk fiom Lenon Elecacnn(MWeI Applicanlemail: VenllmonordsbmlM1'anotlanNllrlMR2ferrtqu rtmmnol50E 95 <. RefermULaerufWwnnimP-MS-N4%-AT-LV (y 52,016.4 m.)OmwNe mmvfldofvew,lwosmamswouldbcneded. That grit Money haw M1rytusmadnw ngz. Noetlut 5hmtl of Ne HAL Evmekon dewing lvhx M6l speiaea Ne Mssld mquim core pmgnming to inugnnt quiprtrntinm Ne NALOS,WIhrnNcwamblywould PermilCmrtlinalpr email: rntilelion mtcof500CFM fw IM1c 265 of MrhmePpmximotcly2cfiNR2lbhene WNe,,mfimlimpowua a,nowwromm eon of A, mi lion wwW be mnrnM1ert CI 'e Commmnb10.15Keenge. ThemW elmlwly mg rmntbi,ay,nin woultl Ue aruprneglaptlbmoRM igMalth,mcofowo My. NererlAekvx tkmianoguxnvatMt TMIRINN m 6) Pkve nNe mmwniondacumenu Nat ltvatda„v mM1eun MNu awo directly w me mxml www might far l ar Nwrwt loon awing ptentnl li R mfery wwwo anti I ml c,tend lwomh or mom, PereMe wwm 5106.7 a Ne IMCApplicants oapoa'. Thin pram yler< doe not have plenum ceilings. Edwt$a =milled dlmllyto /n�t,�W�,,mfimtmp�. lM for sena we [fully request Oatthe COS requiriment be wevM Sir His particular HemisideP n eethe Mth sec on vrrx' on sheet M2 for mort hails. nWrwy ai t iR Safety m, me wamaum ray', comm ,Comment.num d,gCommeankel Com ^ N No plumMng melow in dwok.rce tlmIN m me CO2, Mgm aM Pmpaa news, two em l wo Plane uclme two mmgc ar[res f^ h Pleue provido Poet piping diagrams for[M CD2 Buung st, tie. h an espme: ME pass art nmwPOlind by Pipe disiNtion symems. bu insteM. a 110 Pound supply ie ken menmlly inns Ne Mrh and[mnsf d"lvetommAn a Man high p mm Ase from Ne nun Challm: Bobby M,Km,,, ph: 03) 596]611, e: NMy kinzie(a)caim Penn m,o ;poo TIw,,m CG2m M,b:,dk . Revlew Cmmmev¢ Eleommi 4Cc mlmn EMHal Commean: N Pmvid<eleniknlpW sheets indiee0 i[s for all tyuiproem involved with me^pemlins of on MON. ne slur N whne Nesumid, err mdaunide air far me mmmiw bmNiremming (ram. Plmee provide ell gpplieew, Re,ponssaee vhml El fm EleauaW Cittvit depih calculetiom Crryh Cammm: ApplIww wwMwR'. Supply eirfw Ih tram in wAieh Ne bmN i laapd idmw hon the Auildillg exlelim Saudi MAU-I lomdafthM!BmOt makeup eirwNebmNis provided Aye UL 2) R^vitlelhespecifimlimv fe Ne elauialpa Ii ed fan drawing lmm the summding scam. Sse Oemrl2 "BmN Salim view" to graphic rep nmlian Applicants ResWnse: There em w new peels dm Nis wwNm An existing elamnl plan has ample Copy',Cement. opensgev a[H thetlrow ltlb Intl ins San ve3. AemN'a the clalnenl patrols nlAis le[iliry aprtv away rummal nM me avelable lmrt - e 3) Planes wimmamo H lin dmmnenn that aw,cama sun dischargecomplaint was raMoore a Comment code sal 5013 f h IMC Applie nn Rnpme:Laefonof lAe exhemldixhugekfoummahttl A311mlpW. The vro['i laMnl vin 3) lopoo fault a. onarruktim%,,Ifpanel, was nae ease- The reultancr akuMmnis"newb less than as spedM w Sxiao 5013.LL 10 lea fm oreMle apenroga Team man Ed fm Wm the proper begin with the uliliwmnsfalmmmdmntmmmm wall pawls voted. IAn and mattlluo 101M aMve h. Sm IXItiI2, ehtt1 M2 "Routh Seeliw View"fm hie nem ®e gaP «Wesco Applicants Response The fideunmtnkummn Man Ne ex,San Ihwein ME maonfi tlmmZviv PP P n g gee ofthdvchargemMitiw. promim m 5M1M E1. Cilyk comment: 4) Pleem demenw anthem wdm m Net Neeehuun ventilation fur Mmdwe msavb E Jo h ion 5038 of Ne IMC. 1 Pmnde ails if f the exmsls nts inclusion all, mills with ) system tglimm g mkAlgc Acle R :Nee Wa Sheet I of HAL Exmcdon reman (SHEET M6)s fin the base PP p 8 pa mommicde f -f - Y 9u Proem it tate of was CFM fm 0u 245 .fin N Vp,xo tcly 2cfM02 Make up pnowd by Applicants Rommm, TM highly 6mm� mmMoinl ma cxMl ommd vW ccnifieJ by Captive AurwffmuvlacihN hon M00(Pg pX)md apWrtmgv6mn.O g lopnati,ry HAL Exnmlmn Tubnology Plnxrm vMem M6Nmugh M101wdelaib uM coo Iegi.. Neuhaus fm'o Ne Mol6m' vaemallmpmeau penutemW'vemlM adl+eem roma. city :Comment. (psy a cammme AdNtimal em wnB may w Merced man Ne city taeiver mid mbmtmis and mwl 5) Pkue dem rote in the mmtrvnron dmmnmm mel in, Hawser, modambuuNle liErd exhaust worms ciao with me, waim 502.9.5 dc IMC N etyer{I(y, Srum Gr(pIn Archlrxe Bm8F. Apphams Rormew,.Series 502.9.54 Em. Nspenaing ma mixing) g to per the mm[aPolkable isma,munth,worom LP gas i, delivered b The mccumMummAmors, Ora by gasawpprer. Arm& nki,ma,.amN.11�111amhmdaeam when theewkmaam mm dw ,trod waning lank 1 I 2 1 3 City of Wheat piloe COMMUNm Dmi PMENT Project Description: Extraction Booth, Mix d Use with H Occupancy PLAN REVIEW COMMENTS The profed plans were reviewed for Cemplian ae vo the following woes and standards: 2018 IBC, 2018 KINDS 2018 IMC, 2018 IPC, 20181FGC, 20181ECC, 2017 NEC, ANSI ICC All 17.1200 and the City of Wheat Ridge Amendments. TOEXPEDITEPROJECTAPPROVAL: Please provide a written response indicating how and where each mmmentms resolved onthe plans. Resubmit all previously reviewed plans, updated plans and Supp Mng documen(swMeadlsubsequentre . For clarification Ofany, plan review wmmem, please call or email the plan checker listed. Plan Checker: Kirk Monty, ph: (20) 3404755, e: kihmoney@cu.in; Plan Review Commenm: Building, Accessibility, Energy, Mechanical end Plumbing. Buadmg Commeats: I) Plcm identify all computing classification including accessory mmpanq within the space(wsrehouse area& exMcdon booth). Also, identify the Audit occupancy classifmtion next to Was lemvt spa pay code s ftd 302.1 of Me MC. Applicants Response: The main tenant space is w F-1 Occupancy with an accessory 11-2 bWW located inside the main we&area An F-1 Occupancy is the sole classification in the adjacent spare. Please refer ha shat A3 for a diagram of occupancy classifications. City's Comment Acta clarification via emailresprme uceot , and moment closed. 2) Plmu identify all irons being shard within this span and inciu Else�mw lacing stored. Applicants Response: Gmsd stared indoam are only in the Booth and include 100 pounds of mixed LP gas (30%propane & ]0%n-Buf c, the Broth is rated far 1500). In We exlrrior wemd swmge arae them will ter less Wan 400 pounds of mixed gas. Now input mmmis for We exnactrn pros including uimoings and flower an not mored in this rowed Tisa, but communicably 6 pounds ofptweesmng mamrial is brought into the enclosed booth with mh prWaRing eyala This material comes on-0emand foo We grow facility arca on the North side of the building. When processing is compine, the finished product is Word in the vault, comprising typically less than 10 pounds of material. City's Corr[tr[rnd: Response wapdd, and comment Goad. 3) Plmse identify the amormb of all hamdom makerial being mord and idenrify thein lomdon of storage per nation 30] ofthe IBC. Project Atldlees: 4) Plmu d<monswtcm W<WastmcHiondWumants Hart dry exhausHvandilatiov for h d 1 'al' -s compliant wnM1 crude section 502.8 of the IMC Applicants R p :Nom That Shap 1 of the HAL Extraction showing (SHEET M61 P T - she base v�tiladon X of 500 CPM for rhe 245 I.E. booth, or appmxirwd IY 2 cfMfl2 Mak - add by p p Captive An roof fair as spccifd on shens M04 (Page #X) and supporting shops. Dunng normal opmaeion, the exhaust fens in the booth maintains a small negative air pressure relative to the djecanvooms City's Command: Response accepted, and cormndt closd. 5) Please demdswmin the conswcnon dorvmdu That We flammable bad combusdible liquid exhaust systema are mmpliwt with ado action 502.9.5 of the IMC. Applicants Response: Section 502.9.5.4 (Use, dispensing and mixing) appear by bethe most applicable provision in Wis satiwn. LP gas is ddivmd w the smwc amnor sdoragc more by the gas mpphcr. A single tank is mood to W<CISol booth enclosure where the-0onrems are mmovd and uansferrd He e working uM usd in dse exwdian process. There is no Transfer ofworking gases outside ofthe bWW, and therefore ane baseline ventilation of the broth at 2 cf/fl2 exceeds the requirement. 4805 Van Gordon $[. PoImB Application Dete: OPJ09/21 Pormtt Applkdbnk 202100259 Applicenb Mike Phone: (303)888-2968 Applicanlemail: mikef'rvertarco4Paol.com Pormit CDardinamr. grit Money Phone: (/20) 340-0]56 PermilCmrtlinalpr email: kilkmoneyWcaa.inc Applicants Response: The installation of an occupdcy sensor m mm olithe LED light an the booty is a concent fmmalifesafcrysmndpoint As the summer may remain motionless in the room for pends offime, them is possibility Haat We light could be shut off when We booth is occupid. This could Demand a significant saikry High, In speaking with We [ethnical support vibrational at HAL Extraction Technology, Bann B. indicated that he was not aware of any cushamer ansWBing an occupancy sensor in a HAL booth. Fuller mo arch identified that an explosion prmfmotion sensor is available boom Larson Electronics (Model EXP-MS-N4X- ATLV -„$2016.68 ea. Due to the wnow field of view, two senors would be needed Thesewould regove t tom de We mem anha We HAL of and Men would bl would robe D b g tegra equtP Y m. ted m WGr ecdti l electrical iw WolmoL We estimate thin We cnsd be about 10 cache be mmewhere in at $e ISK range. The halal G rpt o ff saving from Then system would be atom le epics per month assuming That the occupaol neglected to mm ice the light at the end o(mcM1 day. a safety cans, there is en guarantee Wet the minswer ,light fad st that the C 05 reguiien causing potential life safety laroccu Given the above issues, we Safety ully request arc paramount the 1405 requirement be wined for this particular occupancy si4eeion since We Life Sarpy co=marc sponse tit City's Covenant Response ucepded, cad comment closed. Mesh”" Comments: 1) Plmse idenfify where the CO2, Bumne and Propane storage banks are[scrod. Picture include the stormge mpinities for each. Please provide fuel piping diagrams for the CO2,Buba ok Pmpme. Applicants Response: LP gases arc not supplied by pipe disuabutian systems, but instead, a 100 pound supply tank is taken memtally into the booth and transferred valve m valve via a shoo high pressure hose form the booth extraction gquipme L There is no Cin an hat building. City's Comment Response accepted, and comment closed. 2) Please clarify where the supply air ad outside air lm We mtrinfion broth is coming boom. Mmm provide all calculations. Appliances Response: Supply air for We room in which the booth is loaedd is draw from Me building extenm via Ed 18" round duct from MAU-I located on the roof Booth make up air ha the prods is provided by a UL listed fan drawing from the sttmouding mom. See Derail 2" Booth Section View' for graphic repremnbation. City's Co rot: Res e accepted, Rod comment clod. ry Pons in eP 3) Please demonstrate in the mmwchon commands that the exhaust duct discharge mmsnation is antiphonal with ode section 5013 of We IMC Applicants Responu: Location of the exhaust discharge is found on chord A3 floor plan. The vent is Imawd not less Wan as specified in Section 501.3.1.1: 10 feel from operable rpenangs, more than 30 flat from the property line and more Man 10 feet above image. See Dismal 2, shut M2" Booth Section View" for graphic t msenunon of The discharge condition. Cory's Comment: Rdpovse wcVtd, and Rwanda closed. Applicants Response: Exmoor: up to 400 powds ofmixd LP gas (30% propane & 70%mBumne) stored in e rc fenced arca ander xerotica camerss. Interior: up to 100 pounds ofmixed LP gas (30%propane Its 70% m Butev<), City's Comment Response nccrgdd, and comment rdosd. 4) Please deny afinespsce ispmvided wiN an eummatic file detection system per lwde slxnion 615.3 oFlhe IBC. Applicants Response: The BWth conmins a pre<ngineeml and UL Certified powder fire suppression system. THIS SYSTEM HAS ALREADY BEEN REVIEWED AND APPROVED BY THE CITY OF ARVADA. Octants of this sysmm rosy bee seen on Sheer Mb, cad she full Arvada approval slices are inclldd hoe an; LSI and LS2. City's Commrne Group Haaupwcy snail Nor provided with aface detcction system per code section 415.3 of The IBC. Applicants Response: Cory's Comm<vr 5) Please clarify if the space is provided with maummeticfire spritWlm system per rode sedan dl5daffled, DEC. Applicants Response: Yes. An automatic dry cnemial f sprinkle system is provided in the HAL Exnapion bWIM1. Derails afthis system maybe seen on Sheet MI2. City's Comment: Response incepted, and cormnem closed. 6) Please clarify if the space is provided with memergency elmm per code section 615.5 of Due IBC. Applicants Response: A 24V explosion proof emergency alarm is provided by the HAL booth menufuturer. Dalada of alarm can be rnda on ,nen All 10 City 4 5 10 Anther Architect 's Commrnc Response accepted, mrd cormnda closed. )) Please identify all nod assmnblies caiman IN slate per code wmion 508 of Had BC. Applicants Response: Per Table SUN 0, Two cored assemblies are provided along the demising well with We adjacent F-1 Wcuparrry. see sheet A3 for UL Lab assemblies. City's Conmmnc Response inccptd, and commdt clod. e) Pa anvil, please danry she existing grow opnadid in she Wcility. Additionally, plmx dmiry if throe mwBRrtron documents identify the demo evd alteratiow to the misfivg systems. Applicams Response: The misting grow room in North bay of this mnmt suis will remain. It is marked on sn<ra A3. City's Commrnd: Accmvbiliy Comments: 1) Reviewed end wcomments at this firm Energy Comments; I) Please demonstrate in We mmwctian documents thM the mahanical systems ere complier with code section 1401 of the IECC. Appl Imvls Response: The new Captive Air RTU Loi SL- 1III is for heated air only; this is only Itsed w provide makeup air doting time the bootremain h in in operation (raking in tempered air from We larger roam into We broth and exhausting ah to the outride at 500 CFM). The Iwo existing HVAC RTU's are 5 -ton each and will n operation. Specs "Indirect Brnrtube Gas Fired Hinter with 16" Direct Drive Fen, I Furca Elmvonic Full Modulation. Consldt 80% ERcicv<y, and 6:1 Max Turndown for NQ (5:1 Max Tuodoam for LP). Stainless Seel Bunter and Heat Exchanger" Par Table 1403.3.2(5), dsia unit mean IM1e code requirement at ed% ersaianay. City's Commant Response uc<pded, and comment closed. 2) Pleasedemonstraeewthe mwwctiondocumrnmthat theelectriael powered lighting system is compliwt with code sxdid 1405 of Me IECC. Ventilation ofdhe booth is not Wall efiNfl2 per requirements of 502.954. Refer to UL -certified extractor bootM1 span and drawingr. Nora That Shat I of iM1c HAL Extraction drawing (sneer M6) specifics We base ventilation rate oC50o CFM for the 245 of bWlh or approximately 2 ufMli2. City's Commane Response accepdd, and comment dascrL 6) Please demonstm4 in the WnslNation documen, that M1eamdays exhaust duce are extended directly to the exterpor dshall I extend Throgh pl p d Saofton 51061 of W IMC Applicant, R P This X [ spNe d norh drawn l b.Exhaust votes um expend directly to moOutside Please sin the b dh section vieon w sheer SIT for more acmlm City's Colnmem: Response ace@Bed, and comment Boma. )) Please update gas isometric and demmso-am complievicewcode section 402.3 of We IECC. Calculations shall iinldetocol symem. Applicams Respovw: The rcgllmtd gas isompnc is shown d shat MI. City 's Command: wnmhine CammdL: I) No plumbing indoded in seopeof work. Plan Checker: Bobby McKmzia pit (303) 5967661, e: bobbymdimie@caa.inc Plan Review Commen[5: Electrical. EluMnl Commdtr: q Provide electrical plan shauidicating circuits for all equipment involved with Me oppation ofdsebWW. Applicants Response See sheet E I for Elemnaal Cireuitdereils City's Cotnmrnc Respowe ucepted, cold commdaclosed. 2) PrOvid<Wc spaificatidafor Me electrical panels Applicants Response: Pavel spas ere shown an sheer E2 E2 PANEL) City's Commdt Panel spccificetians ere required. 3) Pored fault current calculation enroll panels with new cu<mm The fault clrt'mrt aekuhfiw is mgmmd to begin -WW Utility t sformn evd mvwuHad haall panels involved Appl uR sponu: Thc Wul[curren[celculenon from We mtsding panel housing[here-configured circviu is provided on SkevaGL E2. City's Commane There are no huh current calculations provided on shat EI. 4) Provide all speciflaetiovs for We exhaust system requirements including all bterimldng mewls verb mechanical and fire safety equipment Applicants RsponseTh BoW cannabis apre engineered and UL Rmf<d powder fire suppressrov system. TMS SYSTEM HA LREADY BE R WED AND APPROVED BY THE CITY OF ARVADA. Derail a¢is y No She Ist6 y y' IArvada approval Slims We Included heremLSl end LS m PO 1 INFr�[iM Trerr F, Ci 'Commruc co Ic ry s pen Engine BtmepN. Additional comments may be g<namd orae the City eaeives revised submittals and responses. Updated respanas and Wmmanm 624/21 KM j: CODE REVIEW COMMENTS A2 s, PLLC Architecture +Engineering 3727 Candia Drive Punta Gorda FL 33950 500-243-0528 734-709-7297 9burgh@ gmail.com CWKTIT� Of TIE A AM 01 Is CONT'samm THE PC Code Review & Comments Code Review & Comments r -M M CSoJ sI Equardiany Tup I yet ME Sol ad ME WQ Sa O9 Me 0 WagO o000AREA m EXTERIOR SECURE --- STORAGE STORAGE AREA EVMnNG LOCKED w0► Preferred MATERIALS INC, 3 -Hour Fire Rating FN,M,g: all 16,84,9111701 MMMMYIM0m ASSEMBLY 1 1.Prt rrb gaenaeloxao c. m.u. 8'e 116 Rm 1Gy{eun N-19'tlgtll hM e6elvg Nmnubnpemllel,bal (urNenomegmmemm-1 bnee.IPua 4. ASTM o270 Mundane MmM,. Term M o, s Fab mall IS all mw, b ,%r 5. Mmm'M"g nlMayonp usual , Nlnl lel l rl mm. wEmmo Iwo and ms a(NN eepluM aWe. opWnan use wSea, apxlfiei. Pordersed Mahesh Pis,e ft an npanelwwwarpopvepp9[eeon WMe nM wW avemboyeeo".. wreaponoWl(Wnor Ma oamonshown orsual eeseMl STORAGE 73'<"X28'-0" �. 1 12'HDn X 8'4N r . Fire Rating: 3 Hour No. 8441070002 Concrete Masonry Unit snood se el ve.s ugly �w� sI Equardiany Tup I yet .PXw �a.mnu.al.r.azra.nrF�.eFkl.r,m..o--ana.....a a.mon. ua.mxa.> nolle omawewmlruobn.naw..11.rn.ewulee..rll in mi, SpxE 341n, ea Mx mm IX. Fire Rating:3 Hour No.84.910]OOD2 NOMlrecrooaetl altleio 9161 eemon ua wAclxua .,.men rb R..Imw. elo.N . n aeobrcw mal abq ane Rnlen swab us MADlxul 3- HOUR FIRE WALL DETAILS Wi CLASS 1 OPEN WORKSHOP 25'-9" X 24'-8"IF X 13'-0" V6.bW � IWU96 twwl �a01K61 H-3 ACCESSORY AREA —250SF LAB WORK AREA OFFICE 14'-77"X 28'-1 In EXISTING BREAM RM O UNIT HEATER it"X 75'-5" Ti) LOBBY 1YE r. 8oriaon[al Section { if st'``em ` - 4 "T' ASSEMBLY 2 P, T -�. 1 -4 -No t Fit I - 24 m as e00 nnm OC wl x t �T T , ��� ��'' Hnrizontnl Bcction aJ . Flow, ad, rd 411gi se •x•. Nn°ee "n".. mi, n z-vz In, ea (min 4in. aeap wPen synameleraj. Mm drepal leRwlzln.nnaue mmmin zX(mmAMSG when them Manzurere)MEN _ tlael. .P:„rem�areRuth NOR nwm. nu.tlM aa® wall visa IT 'J' - eP.cee rvnbn. z. Meal Muds — -or - ancee awo, min x-uz In deep Imm s In. seep We System a to aaem, beemke rmm mm zs MSD Imb m xsD rens Mms ED. aA 0a Or l Is u<a1j qap ae¢I. M to IenglM 3/6 to Vx In. ksi than IlroMo-ttlllry Mlgnl am l - _ ROOF LEVEL /� 114'-8� EXISTING ROOF STRUMIT1 CAULK AND SEAL AT TEE WEB PENETRATION R4 CONTINUOUS III IN m BOND DEAN MATCH GAD COURSING IN EJ(ISTING WALL AT GRID 2 ACT CEILING, 51.51FEND FROM ROOM 5TRUCTURE ® 32 -IN O.L. a x 8 x 16 REINPORCEDAV LMU - SCUD GROUP ALFINN I NNIFF RHIN May I L CELLS CONTAINING RfBARCreole KNISH: BLOCK FILLER AND Paur Born slofs - coLOR BY OWNER —Y4 REBAR ANCHOR 32 IN O G.. OVERTOP TIES MIN 20 -IN ANCHORTO PENETRATE PYISNNG SLAB MIN 4-I14; — SEF IN ANCHORING fP0%1' 15T FLOOR � ... 100' _ a' V n CMU WALL 76 -IN STUD AT NEW WALL EDGE TRIM GYP TO NT INTO OPENING IXISTING RIBBING CHANNELS AND GYP BD Fn I DINGLE PANE GU55 STRIP SET IN GL021NG COMOUND n INTERIOR PARTITION AT WINDOW SMO WALL DETAILS Mrsam U��OICk�MMI t Maine Adjulticrocknim, nus unit Conommuchl 910M amenture"I'Mom, 4A FIRE sitting offlowas 132 Me I Ed 375 Miu�d"ilk�1(illh") HIM CohnscritiousionstUnft moughommum, 10 ;ENT �W�KLMMIMI ME Is FIT RNSIMINI Thomas Of Own & I, HI SEEM C I SCOPE OF NEW WORK &INSTALLATION METER O H O O O O O O ROTE: FIRE SUPPRESSION SYSTEM INSTALLER SHALLSEALALHIRE LPENETFANONS INTOTHE / BWTH WITH Son LP25 WP SERIES FIRESTOFPIHGCIXAPWNDS (Ow APPROVED EOVIVALEHO FER LODEAND PER SE44NT MANUFACTURERS RECIXAMEHOATON3ANO2j PER THE R9L INSTALLATION M9HVALTO ACHIEVE AT LEAST 1 -HOUR MIING. NOTE: EXITING GROW ROOM TO REMAIN IN THIS BAY 3 00"1' '"/� 3 -HOUR WALL ASSEMBLY #1REI EXISTING SUPPLY AIR HANDLER i e nDIV RETURN RETURN Q f�15°.PPLv FLOWER RM SUPPLY AIR HANDLER E E AIR HANDLER 39'6"X56'-1" EXISTING EXISTING 0 o N u o 0 GAS METERS #2 INC WALL ASSEMBLY#1 D g =S [tea] EZA un � o I� a For 1 FLOOR PLAN -FULL BUILDING A3 SCALE: 1/8"=12.021 Anther Architects, PLLC Architecture +Engineering ' 3727 Candia Drive Punta Gorda FL 33950 800-243-0528 734-709-7297 9burghBgmail.com THE l�T OF THE CONNATS DICUMENC IS TO RESUME As OWWTTTTTT MNTS ME cocamp Am Ag IMT Is R�I Fr Toy SEOUL M ARS RINEING As IF R�WD TO ALL Me REARTARMSY I FROM THEM As who �E�y REWA� My, yen, "most CIARME TO 001I � CHANGES TO CONTRACT TOM OR THE mays iTUART GRI BURGH ARC004061 YLl/ n l° Wheal Rio' U 041 woo ENO TERMS No 00 % Helena cle) Malawi E t On ^` M L O U FIJI �' z (� c: O co LL o U Y o � - O C� 0FIRMS ) No cc (� i � U �r L(7 � U X a � g SHEET -NUMBER- P,ml.a: rMesaay,.wlyn zar Tup I yet ME SpxE 341n, ea Mx mm IX. Fire Rating:3 Hour No.84.910]OOD2 NOMlrecrooaetl altleio 9161 eemon ua wAclxua .,.men rb R..Imw. elo.N . n aeobrcw mal abq ane Rnlen swab us MADlxul 3- HOUR FIRE WALL DETAILS Wi CLASS 1 OPEN WORKSHOP 25'-9" X 24'-8"IF X 13'-0" V6.bW � IWU96 twwl �a01K61 H-3 ACCESSORY AREA —250SF LAB WORK AREA OFFICE 14'-77"X 28'-1 In EXISTING BREAM RM O UNIT HEATER it"X 75'-5" Ti) LOBBY 1YE r. 8oriaon[al Section { if st'``em ` - 4 "T' ASSEMBLY 2 P, T -�. 1 -4 -No t Fit I - 24 m as e00 nnm OC wl x t �T T , ��� ��'' Hnrizontnl Bcction aJ . Flow, ad, rd 411gi se •x•. Nn°ee "n".. mi, n z-vz In, ea (min 4in. aeap wPen synameleraj. Mm drepal leRwlzln.nnaue mmmin zX(mmAMSG when them Manzurere)MEN _ tlael. .P:„rem�areRuth NOR nwm. nu.tlM aa® wall visa IT 'J' - eP.cee rvnbn. z. Meal Muds — -or - ancee awo, min x-uz In deep Imm s In. seep We System a to aaem, beemke rmm mm zs MSD Imb m xsD rens Mms ED. aA 0a Or l Is u<a1j qap ae¢I. M to IenglM 3/6 to Vx In. ksi than IlroMo-ttlllry Mlgnl am l - _ ROOF LEVEL /� 114'-8� EXISTING ROOF STRUMIT1 CAULK AND SEAL AT TEE WEB PENETRATION R4 CONTINUOUS III IN m BOND DEAN MATCH GAD COURSING IN EJ(ISTING WALL AT GRID 2 ACT CEILING, 51.51FEND FROM ROOM 5TRUCTURE ® 32 -IN O.L. a x 8 x 16 REINPORCEDAV LMU - SCUD GROUP ALFINN I NNIFF RHIN May I L CELLS CONTAINING RfBARCreole KNISH: BLOCK FILLER AND Paur Born slofs - coLOR BY OWNER —Y4 REBAR ANCHOR 32 IN O G.. OVERTOP TIES MIN 20 -IN ANCHORTO PENETRATE PYISNNG SLAB MIN 4-I14; — SEF IN ANCHORING fP0%1' 15T FLOOR � ... 100' _ a' V n CMU WALL 76 -IN STUD AT NEW WALL EDGE TRIM GYP TO NT INTO OPENING IXISTING RIBBING CHANNELS AND GYP BD Fn I DINGLE PANE GU55 STRIP SET IN GL021NG COMOUND n INTERIOR PARTITION AT WINDOW SMO WALL DETAILS Mrsam U��OICk�MMI t Maine Adjulticrocknim, nus unit Conommuchl 910M amenture"I'Mom, 4A FIRE sitting offlowas 132 Me I Ed 375 Miu�d"ilk�1(illh") HIM CohnscritiousionstUnft moughommum, 10 ;ENT �W�KLMMIMI ME Is FIT RNSIMINI Thomas Of Own & I, HI SEEM C I SCOPE OF NEW WORK &INSTALLATION METER O H O O O O O O ROTE: FIRE SUPPRESSION SYSTEM INSTALLER SHALLSEALALHIRE LPENETFANONS INTOTHE / BWTH WITH Son LP25 WP SERIES FIRESTOFPIHGCIXAPWNDS (Ow APPROVED EOVIVALEHO FER LODEAND PER SE44NT MANUFACTURERS RECIXAMEHOATON3ANO2j PER THE R9L INSTALLATION M9HVALTO ACHIEVE AT LEAST 1 -HOUR MIING. NOTE: EXITING GROW ROOM TO REMAIN IN THIS BAY 3 00"1' '"/� 3 -HOUR WALL ASSEMBLY #1REI EXISTING SUPPLY AIR HANDLER i e nDIV RETURN RETURN Q f�15°.PPLv FLOWER RM SUPPLY AIR HANDLER E E AIR HANDLER 39'6"X56'-1" EXISTING EXISTING 0 o N u o 0 GAS METERS #2 INC WALL ASSEMBLY#1 D g =S [tea] EZA un � o I� a For 1 FLOOR PLAN -FULL BUILDING A3 SCALE: 1/8"=12.021 Anther Architects, PLLC Architecture +Engineering ' 3727 Candia Drive Punta Gorda FL 33950 800-243-0528 734-709-7297 9burghBgmail.com THE l�T OF THE CONNATS DICUMENC IS TO RESUME As OWWTTTTTT MNTS ME cocamp Am Ag IMT Is R�I Fr Toy SEOUL M ARS RINEING As IF R�WD TO ALL Me REARTARMSY I FROM THEM As who �E�y REWA� My, yen, "most CIARME TO 001I � CHANGES TO CONTRACT TOM OR THE mays iTUART GRI BURGH ARC004061 YLl/ n l° Wheal Rio' U 041 woo ENO TERMS No 00 % Helena cle) Malawi E t On ^` M L O U FIJI �' z (� c: O co LL o U Y o � - O C� 0FIRMS ) No cc (� i � U �r L(7 � U X a � g SHEET -NUMBER- P,ml.a: rMesaay,.wlyn zar 3- HOUR FIRE WALL DETAILS Wi CLASS 1 OPEN WORKSHOP 25'-9" X 24'-8"IF X 13'-0" V6.bW � IWU96 twwl �a01K61 H-3 ACCESSORY AREA —250SF LAB WORK AREA OFFICE 14'-77"X 28'-1 In EXISTING BREAM RM O UNIT HEATER it"X 75'-5" Ti) LOBBY 1YE r. 8oriaon[al Section { if st'``em ` - 4 "T' ASSEMBLY 2 P, T -�. 1 -4 -No t Fit I - 24 m as e00 nnm OC wl x t �T T , ��� ��'' Hnrizontnl Bcction aJ . Flow, ad, rd 411gi se •x•. Nn°ee "n".. mi, n z-vz In, ea (min 4in. aeap wPen synameleraj. Mm drepal leRwlzln.nnaue mmmin zX(mmAMSG when them Manzurere)MEN _ tlael. .P:„rem�areRuth NOR nwm. nu.tlM aa® wall visa IT 'J' - eP.cee rvnbn. z. Meal Muds — -or - ancee awo, min x-uz In deep Imm s In. seep We System a to aaem, beemke rmm mm zs MSD Imb m xsD rens Mms ED. aA 0a Or l Is u<a1j qap ae¢I. M to IenglM 3/6 to Vx In. ksi than IlroMo-ttlllry Mlgnl am l - _ ROOF LEVEL /� 114'-8� EXISTING ROOF STRUMIT1 CAULK AND SEAL AT TEE WEB PENETRATION R4 CONTINUOUS III IN m BOND DEAN MATCH GAD COURSING IN EJ(ISTING WALL AT GRID 2 ACT CEILING, 51.51FEND FROM ROOM 5TRUCTURE ® 32 -IN O.L. a x 8 x 16 REINPORCEDAV LMU - SCUD GROUP ALFINN I NNIFF RHIN May I L CELLS CONTAINING RfBARCreole KNISH: BLOCK FILLER AND Paur Born slofs - coLOR BY OWNER —Y4 REBAR ANCHOR 32 IN O G.. OVERTOP TIES MIN 20 -IN ANCHORTO PENETRATE PYISNNG SLAB MIN 4-I14; — SEF IN ANCHORING fP0%1' 15T FLOOR � ... 100' _ a' V n CMU WALL 76 -IN STUD AT NEW WALL EDGE TRIM GYP TO NT INTO OPENING IXISTING RIBBING CHANNELS AND GYP BD Fn I DINGLE PANE GU55 STRIP SET IN GL021NG COMOUND n INTERIOR PARTITION AT WINDOW SMO WALL DETAILS Mrsam U��OICk�MMI t Maine Adjulticrocknim, nus unit Conommuchl 910M amenture"I'Mom, 4A FIRE sitting offlowas 132 Me I Ed 375 Miu�d"ilk�1(illh") HIM CohnscritiousionstUnft moughommum, 10 ;ENT �W�KLMMIMI ME Is FIT RNSIMINI Thomas Of Own & I, HI SEEM C I SCOPE OF NEW WORK &INSTALLATION METER O H O O O O O O ROTE: FIRE SUPPRESSION SYSTEM INSTALLER SHALLSEALALHIRE LPENETFANONS INTOTHE / BWTH WITH Son LP25 WP SERIES FIRESTOFPIHGCIXAPWNDS (Ow APPROVED EOVIVALEHO FER LODEAND PER SE44NT MANUFACTURERS RECIXAMEHOATON3ANO2j PER THE R9L INSTALLATION M9HVALTO ACHIEVE AT LEAST 1 -HOUR MIING. NOTE: EXITING GROW ROOM TO REMAIN IN THIS BAY 3 00"1' '"/� 3 -HOUR WALL ASSEMBLY #1REI EXISTING SUPPLY AIR HANDLER i e nDIV RETURN RETURN Q f�15°.PPLv FLOWER RM SUPPLY AIR HANDLER E E AIR HANDLER 39'6"X56'-1" EXISTING EXISTING 0 o N u o 0 GAS METERS #2 INC WALL ASSEMBLY#1 D g =S [tea] EZA un � o I� a For 1 FLOOR PLAN -FULL BUILDING A3 SCALE: 1/8"=12.021 Anther Architects, PLLC Architecture +Engineering ' 3727 Candia Drive Punta Gorda FL 33950 800-243-0528 734-709-7297 9burghBgmail.com THE l�T OF THE CONNATS DICUMENC IS TO RESUME As OWWTTTTTT MNTS ME cocamp Am Ag IMT Is R�I Fr Toy SEOUL M ARS RINEING As IF R�WD TO ALL Me REARTARMSY I FROM THEM As who �E�y REWA� My, yen, "most CIARME TO 001I � CHANGES TO CONTRACT TOM OR THE mays iTUART GRI BURGH ARC004061 YLl/ n l° Wheal Rio' U 041 woo ENO TERMS No 00 % Helena cle) Malawi E t On ^` M L O U FIJI �' z (� c: O co LL o U Y o � - O C� 0FIRMS ) No cc (� i � U �r L(7 � U X a � g SHEET -NUMBER- P,ml.a: rMesaay,.wlyn zar l - _ ROOF LEVEL /� 114'-8� EXISTING ROOF STRUMIT1 CAULK AND SEAL AT TEE WEB PENETRATION R4 CONTINUOUS III IN m BOND DEAN MATCH GAD COURSING IN EJ(ISTING WALL AT GRID 2 ACT CEILING, 51.51FEND FROM ROOM 5TRUCTURE ® 32 -IN O.L. a x 8 x 16 REINPORCEDAV LMU - SCUD GROUP ALFINN I NNIFF RHIN May I L CELLS CONTAINING RfBARCreole KNISH: BLOCK FILLER AND Paur Born slofs - coLOR BY OWNER —Y4 REBAR ANCHOR 32 IN O G.. OVERTOP TIES MIN 20 -IN ANCHORTO PENETRATE PYISNNG SLAB MIN 4-I14; — SEF IN ANCHORING fP0%1' 15T FLOOR � ... 100' _ a' V n CMU WALL 76 -IN STUD AT NEW WALL EDGE TRIM GYP TO NT INTO OPENING IXISTING RIBBING CHANNELS AND GYP BD Fn I DINGLE PANE GU55 STRIP SET IN GL021NG COMOUND n INTERIOR PARTITION AT WINDOW SMO WALL DETAILS Mrsam U��OICk�MMI t Maine Adjulticrocknim, nus unit Conommuchl 910M amenture"I'Mom, 4A FIRE sitting offlowas 132 Me I Ed 375 Miu�d"ilk�1(illh") HIM CohnscritiousionstUnft moughommum, 10 ;ENT �W�KLMMIMI ME Is FIT RNSIMINI Thomas Of Own & I, HI SEEM C I SCOPE OF NEW WORK &INSTALLATION METER O H O O O O O O ROTE: FIRE SUPPRESSION SYSTEM INSTALLER SHALLSEALALHIRE LPENETFANONS INTOTHE / BWTH WITH Son LP25 WP SERIES FIRESTOFPIHGCIXAPWNDS (Ow APPROVED EOVIVALEHO FER LODEAND PER SE44NT MANUFACTURERS RECIXAMEHOATON3ANO2j PER THE R9L INSTALLATION M9HVALTO ACHIEVE AT LEAST 1 -HOUR MIING. NOTE: EXITING GROW ROOM TO REMAIN IN THIS BAY 3 00"1' '"/� 3 -HOUR WALL ASSEMBLY #1REI EXISTING SUPPLY AIR HANDLER i e nDIV RETURN RETURN Q f�15°.PPLv FLOWER RM SUPPLY AIR HANDLER E E AIR HANDLER 39'6"X56'-1" EXISTING EXISTING 0 o N u o 0 GAS METERS #2 INC WALL ASSEMBLY#1 D =S [tea] EZA 1 FLOOR PLAN -FULL BUILDING A3 SCALE: 1/8"=12.021 Anther Architects, PLLC Architecture +Engineering ' 3727 Candia Drive Punta Gorda FL 33950 800-243-0528 734-709-7297 9burghBgmail.com THE l�T OF THE CONNATS DICUMENC IS TO RESUME As OWWTTTTTT MNTS ME cocamp Am Ag IMT Is R�I Fr Toy SEOUL M ARS RINEING As IF R�WD TO ALL Me REARTARMSY I FROM THEM As who �E�y REWA� My, yen, "most CIARME TO 001I � CHANGES TO CONTRACT TOM OR THE mays iTUART GRI BURGH ARC004061 YLl/ n l° Wheal Rio' U 041 woo ENO TERMS No 00 % Helena cle) Malawi E t On ^` M L O U FIJI �' z (� c: O co LL o U Y o � - O C� 0FIRMS ) No cc (� i � U �r L(7 � U X a � g SHEET -NUMBER- P,ml.a: rMesaay,.wlyn zar a � g SHEET -NUMBER- P,ml.a: rMesaay,.wlyn zar A B C Ism MECHANICAL ABBREVIATIONS Ar METERS mum All ABOVE ERNEST) R NX FRE DAMPER "EATON MALAW INPUT m FM POWERED WN ApFNS PER INCH My BLOW RWRU FPM Fan PER MINUTE BE glow PRINTED FOUND NO gLm SAKE 650 AM HURT HEATER MIT LEMW MR TEMPERATURE CF'METERNSTM' FAX ANMA MANUN DAMPER ER EB DEC BUIL NATED WIN NEW ON I NOT TO SUIS WW OCnu OUTPUT DW METERS SMOKE DAMPER pSCONNEGT SHEET LM EST DURING AW MMPMR RE OR SUPPLY AIR NOTE FOM ELECTRIC DUCT HEATER D MMERMSE By ENllnUg FM NRIL MR VOLUME WS EXERDY mA EM Srilb WR III ROOM NOTE: WM ML MAY APPE GENERAL MECHANICAL NOTES I. CCMMCTq 9WL PRMIE ML WTLWS MO EMMW MD g9NN ML UBPI AS REWCOmrN AGLAREDRDMBBMEERM NSM MDe TO D Y RDA M SntFlGA MW, THIS DSK OF ICAT ANDALL NfWIHE CODE x. ALLMpR PWMM09WL EMFWu mNLMiUG ATE MIT LWl W[6. �ETH�D NgISSUE CONFUCTE 00 NOT � MmRMW 4 L MUM OF ANY ENmW NEPAL SHALL S UFA MTM THE MM MO SWILL SE WONMW AT A ME MD IN A METER SO AS TO V WE ME OWES A M" OF MICAME S. ALL STUFF SZE IN"� ON MARIS AND METERS ARE CLEAR INSIDE D�s COLI SEES WFD DWL BE WED 10M MAS MU Mw METERS �m USING R ALL SUPPLY DaRM ETURN SHEET f� TO FARES ME SAUDI AR TL01MF FRAME. ]. P TURNIW ANNE N ALL JDA RESURE Bo -DE N E PERF TLAS B. MMWLTNI SHALL M E MESS OMK FOR S:M1Ntt AND NUNIONICE M Al EIXFlOII LOUIERA MKKE COIN4S R REMAIN NFPi IMOD MARVIN E6MBCN USE AND 511T KMIT SIEE. MR ALL MIN. MECHANICAL LEGEND NOTE © THERMOSTAT 0 N D WE ® SMOKE DETECTOR RN EMg NEW OH HUMIRAAT eI EWHE,n NUMBER O TEMHRANRE DNXfl MIL MECWNICLL FIRST ROOM RM - FNM M1.1 MECHANICAL ROOF PLAN - I Q gRDW WCMORM ® WALL SMmx ACM ____ m H REMMID ® aST DIFFUSER m RE REMAINED mo M SHEETAIR ® MAZDA NEW ® SUPPLY CNILLE m TALLIES CFM E MUM CONNECTOR ® SUPPLY DRILLE O POINT OF OF DEMOLMOM EST ANNE RENRMUIRMSFER BRUTE US mm -�-- MouIN aM$ Mm Nm ® glMun wllu r wP0.r uR + r+ o UNEAR OFNsq w— RErvMFUENxwn xR x x r+ Wcr TRWSDPx NO MALL CUP /. .c CDM 49 TMEDK MYTH MUMMAL MLURE DMKR I MANUAL unuME DAMPER z _AD R2 PWPER 771 DPAMCx TME wrF JFSO nFE SMOKE SHEET MARKETS 16 K SWING TO DRIVE! 72 Is AREA ASSURED TO ESCAPE MEN SMOKE O tJ AM PERING TO RELOGET) MID [Y cc N NEW WFULATING PAR IMT 16 1 TURN ill"11 U MECHANICAL ABBREVIATIONS Ar METERS mum All ABOVE ERNEST) R NX FRE DAMPER "EATON MALAW INPUT m FM POWERED WN ApFNS PER INCH My BLOW RWRU FPM Fan PER MINUTE BE glow PRINTED FOUND NO gLm SAKE 650 AM HURT HEATER MIT LEMW MR TEMPERATURE CF'METERNSTM' FAX ANMA MANUN DAMPER ER EB DEC BUIL NATED WIN NEW ON I NOT TO SUIS WW OCnu OUTPUT DW METERS SMOKE DAMPER pSCONNEGT SHEET LM EST DURING AW MMPMR RE OR SUPPLY AIR NOTE FOM ELECTRIC DUCT HEATER D MMERMSE By ENllnUg FM NRIL MR VOLUME WS EXERDY mA EM Srilb WR III ROOM NOTE: WM ML MAY APPE GENERAL MECHANICAL NOTES I. CCMMCTq 9WL PRMIE ML WTLWS MO EMMW MD g9NN ML UBPI AS REWCOmrN AGLAREDRDMBBMEERM NSM MDe TO D Y RDA M SntFlGA MW, THIS DSK OF ICAT ANDALL NfWIHE CODE x. ALLMpR PWMM09WL EMFWu mNLMiUG ATE MIT LWl W[6. �ETH�D NgISSUE CONFUCTE 00 NOT � MmRMW 4 L MUM OF ANY ENmW NEPAL SHALL S UFA MTM THE MM MO SWILL SE WONMW AT A ME MD IN A METER SO AS TO V WE ME OWES A M" OF MICAME S. ALL STUFF SZE IN"� ON MARIS AND METERS ARE CLEAR INSIDE D�s COLI SEES WFD DWL BE WED 10M MAS MU Mw METERS �m USING R ALL SUPPLY DaRM ETURN SHEET f� TO FARES ME SAUDI AR TL01MF FRAME. ]. P TURNIW ANNE N ALL JDA RESURE Bo -DE N E PERF TLAS B. MMWLTNI SHALL M E MESS OMK FOR S:M1Ntt AND NUNIONICE M Al EIXFlOII LOUIERA MKKE COIN4S R REMAIN NFPi IMOD MARVIN E6MBCN USE AND 511T KMIT SIEE. MR ALL MIN. MRDEMCESCHEDULE MECHANICAL LEGEND QEgo NOTE ® TaWM"W MSN M.'UMMUMMRE m+M r MMMW AN MAKE w TNS S -0L om KE FAH DATA RE n UNLTSSOTE"lI NOMD MECHANICAL SHEET LIST MW MECNWICLL NOR. MD SMEOLLES <. PROVIDE WITH MANUAL VOLUME BAWM O MM MIL MECWNICLL FIRST ROOM RM - FNM M1.1 MECHANICAL ROOF PLAN - I MRDEMCESCHEDULE MARE UP AIR UNR SCHEDULE DESCRIPTION REM O M.'UMMUMMRE A TNS S -0L 1S'%B' SUPPLYgICTOIFFUSER FAH DATA RE n UNLTSSOTE"lI NOMD z6WAYTI PROVIDE nDP➢TOR BOTS AS REQUIRED PLATER <. PROVIDE WITH MANUAL VOLUME BAWM O MM 5 REFER TO FOR DACE AND DUCT SIZING. Q ACNMAPS R R' ACM O L"� iRHSTRE + m + E Ha1M 0 U + na EST ANNE mND + mm + CL r + r+ x E ca WE x x r+ a NO I /. .c CDM Nc U �� z o � m LL n MARKETS 16 OWNED 1 72 Is CANTS WED AnOF ALLREMARKSI O tJ U m MID [Y cc (� i WFULATING PAR IMT 16 1 TURN ill"11 U 1--a L(7 M RELY U X00 Lu Et ti0 ANN FAN MANOR12 HIRE ASK MTH METTARMEN ��S AW13 DONANDISCHARRUCE14 PREENSTAT15 MESSAGE CONTROMEMS Ani E�M BOOTH � AD THAT MAIL RNMEST MUM FAN&IN PROPPIC ROAD GUM MRDEMCESCHEDULE TIEMTPG DESCRIPTION REM O M.'UMMUMMRE A TNS S -0L 1S'%B' SUPPLYgICTOIFFUSER ALL RE n UNLTSSOTE"lI NOMD z6WAYTI PROVIDE nDP➢TOR BOTS AS REQUIRED S. COORDINATE FRAME SIZE WITH MCHIMCTURRL FLOWER. <. PROVIDE WITH MANUAL VOLUME BAWM O MM 5 REFER TO FOR DACE AND DUCT SIZING. — — 0— Imlm_ —0 — — STORAGE 13'-4" X 26'-9" OFFICE 14'-11" X 28'-11" OPEN WORKSHOP 25'-9" X 24'-8" we HVL EXTRACTION a]01H METER 4215 CLASS I O NV610N I (EXPLOSION PROOF) (BY GTHERS) H-3 ACCESSORY AREA Al , J]5 q }]5 O 14-R /.M W375 MA }]5 2 " 1 SURE ,RAGE X 13'-0" LAB WORK AREA BREAM RM O IITT ING NHEATER 11'-11" X 15'-5" € LOBBY JAN 0 12' 0A, X 8'-4•' X:IGAS ISOMETRIC DIAGRAM I\EJ W, nLTeM RTU GAS SUPPLY LINE DIAGRAM SCOPE OF NEW WORK & INSTALLATION METER O El O U _0 NOTE: FIRE SUPPRESSION SYSTEM INSTALLER SHALL SEAL ALL PENETRATIONS INTO THE BOOTH WITH 3M CP25 WP SERIES FIRESTOPPING COMPOUNDS (OR APPROVED IR -6 EQUIVALENT) PER CODE AND PER SEALANT °t MANUFACTURERS RECOMMENDATIONS AND PER THE HAL INSTALLATION MANUAL TO ACHIEVE AT LEAST A 1 -HOUR RATING. R RETURN N RETURN IN S11 PIELT QUPPLY AIR HANDLER E E AIR HANDLER 0 -.w o -- -- 0 ,m,,, -0 - NOTE: EXITING GROW ROOM TO REMAIN IN THIS BAY EXISTING SUPPLY AIR HANDLER FLOWER RM E 39'-6"X561-1" EXISTING CT UNIT HEATER HVAC DETAIL PLAN_ 'I SCALE: 1/412=12.021 GAS METERS ie Anther Architects, PLLC Architecture TE Engineering 3727 Candia Drive Punta Gorda FL 33950 800-243-0528 734-709-7297 gburgh@gmail.com 3TUARTGRI BURGH ARC 004061 IJE%47 1i THE ITTENT OF THE COMAREffir DOCUMENTS IS TO I An Wes EMMEMY FOR THE PIMPER EXECLITION AND OWKTIT� OR THE AMC TV THE CONTRACAM THE OWRACT ONEUMENTS ME �w�� AND IMF Is REENTRED NIP FINE SHALL MAN RINNING ASIF FEDERATED II SM APARTUMMELY EFORRED FROM THEM INS SEEN INEENCESEARY IMEMESPEOCRATENTH REWA� DER NUM MMNT KNOW AGREE REWA� SHELL APPLI "i PHRASE TO CONTACT Ill OR ENE IW�T� DIAGRAM ON THIN MMEr GUM NOT AUTHENNUE GEORGIA TO ONSTRAI AW OR TRY OHMS O + Q I --F O + m + E + 0 U + + U) + + CL r + r+ x E ca ,c x x r+ a NO I /. .c CDM Nc SCOPE OF NEW WORK & INSTALLATION METER O El O U _0 NOTE: FIRE SUPPRESSION SYSTEM INSTALLER SHALL SEAL ALL PENETRATIONS INTO THE BOOTH WITH 3M CP25 WP SERIES FIRESTOPPING COMPOUNDS (OR APPROVED IR -6 EQUIVALENT) PER CODE AND PER SEALANT °t MANUFACTURERS RECOMMENDATIONS AND PER THE HAL INSTALLATION MANUAL TO ACHIEVE AT LEAST A 1 -HOUR RATING. R RETURN N RETURN IN S11 PIELT QUPPLY AIR HANDLER E E AIR HANDLER 0 -.w o -- -- 0 ,m,,, -0 - NOTE: EXITING GROW ROOM TO REMAIN IN THIS BAY EXISTING SUPPLY AIR HANDLER FLOWER RM E 39'-6"X561-1" EXISTING CT UNIT HEATER HVAC DETAIL PLAN_ 'I SCALE: 1/412=12.021 GAS METERS ie Anther Architects, PLLC Architecture TE Engineering 3727 Candia Drive Punta Gorda FL 33950 800-243-0528 734-709-7297 gburgh@gmail.com 3TUARTGRI BURGH ARC 004061 IJE%47 1i THE ITTENT OF THE COMAREffir DOCUMENTS IS TO I An Wes EMMEMY FOR THE PIMPER EXECLITION AND OWKTIT� OR THE AMC TV THE CONTRACAM THE OWRACT ONEUMENTS ME �w�� AND IMF Is REENTRED NIP FINE SHALL MAN RINNING ASIF FEDERATED II SM APARTUMMELY EFORRED FROM THEM INS SEEN INEENCESEARY IMEMESPEOCRATENTH REWA� DER NUM MMNT KNOW AGREE REWA� SHELL APPLI "i PHRASE TO CONTACT Ill OR ENE IW�T� DIAGRAM ON THIN MMEr GUM NOT AUTHENNUE GEORGIA TO ONSTRAI AW OR TRY OHMS HVAC Plan Printed Tuestlay, July 27, M21 O Q I --F O m E 0 U TRRRR U) 0 CL r MID U E ca t a I M CDM U �� z o � m LL _0U _:Be O p CD O tJ U m MID [Y cc (� i U 1--a L(7 M RELY U X00 Lu Et ti0 HVAC Plan Printed Tuestlay, July 27, M21 0 LI HAL CONVICTION BOOTH MODEL /215 CLASS 1 O DMSION I (EXPLOSION PROOF) (BY OTHERS) A d75 375 TIn A H'0 A MA :\FIRST FLOOR PLAN — HVAC 4NN 1/4" = 1'-0" MECHANICAL PICKING ROOM 1 1 2 1 3 RET 1©I 4 18's 37s LM HAL EATRACRON BOOTH MODE /215 CLASS I DMSION 1 (IXPLOSDN PROOF) (BY OTHERS) J 7 )QUOOTH SECTION VIEW �O N NO SCALE MECHANICAL 4O CAUTION: IF THIS SHEET IS NOT 30 -AT IT IS A REDUCED PRINT GENERAL NOTES I, REFER TO GENERAL NOTES ON SHEET RED 2. REFER TO SPECIFICATIONS ON SHEET M0.1 KEY NOTES O1 18'0 WE UP MR DUCT DOWN FROM MMU -1 ON ROOF. O CORRECT 1810 ENHMLST DUCT TO E%rWCnOH BOOM 12.0 FIN CONNECTION. COORDINATE EXACT LOCATION IN FIELD. COHOST DUCT TO RUN UP THROUGH POO'. TERMINI WITH ROOF CUP. O 181 RETURN DUCT DOWN FROM MMU -1 TO ELBOW OUT INN PACKING ROOM UP HIGH. © EXISTING MECHMMICAL EQUIPMENT N REMMN, O EXTRACTION BOOTH BY OTHERS. REFER TO BOOTH CUR SHEETS AND PRODUCT DATA FOR MORE INFORMATION. KEY NOTES 4 15 6 HCO W OPINION BY, OI 18.0 WE UP AIR DUCT WNN FROM MA AI ON ROOF. (DI co p �/ � V / O m to O CONNECT CON E#NUST DUCT ORD N EDUCT LN BOORT 1Y0 FAN CONNECTION. EXACT L IN O Q Z P THR FIELDROOF EXHAUST DUCT ERTEN DIRECTLY UP THROUGH Q ROOF INO S. EXEND IN ORTH NOT EXPEND INTO OR 1HRgKN DUCTS L ER -16-0 TE OR PLENUMS. TERMINATE N1M POOP CM. u,12 m^ u IX OQ /0/n V Nom_N LL RERRMOR i0 SOON GUY BOOTHROOD BY OTHEDITA O O 3 SHEETSEXTRACAN F. SHEETS NIT Pfl000CT MTA FOR MORE INFORIPTION. CFM 2 OF —am Of BOORT TO BE AT A CONSISTENT NIPRESSESS PRESSURE. NE be OIXNMUST pSCIARGE TO BE A MINIMUM OF .Nr -0' AWAY FROM PROPERTY UNE, 10 FT FROM OPERABLE OPENINGS INTO BUILDING AND SFT ABOVE ROOF. © TIRRE CQ OS SUPPLY FAN PRWIDED MTM COMMOTION BOOTH. BOOTH N (D nt SUPPLIES NR TO BOOTH MOM ROOM, N FAN PRONEMED WITH EXTRACTION BOOTH OEXOI EhTWJSIS AIR MOM BOOTH TO OUTDOORS. Eli OREFER TO FIRE PROTECTION FOR HE SUPPRESSION m° U SYSTEM FOR BOOM AND EXHMIST DUCT. ca W1NDA NR UNIT SUPPIES OM TO ROM TO WE ONEW UP MR NR BEING EX STED THROUGH EXTRACTION ROOM. t 4 15 6 PI HCO W OPINION BY, 0 W co p �/ � V / O m to W O Q Z EREST— Q L u,12 m^ u cp OQ /0/n V Nom_N LL Lair O Q OF —am NE be CD 0 L) TIRRE CQ N (D nt PI HCO W OPINION BY, W W co p �/ � V / O m to W O Q Z J Q L OQ /0/n V Nom_N LL O Q i W Lf) CD 0 L) TIRRE CQ N (D nt PI me OPINION BY, W O_ FORT 110 41 MEET M1.0 10 Anther Architects, PLLC Architecture + Engineering 3727 Candia Drive Punta Gorda FL 33950 500-243-0528 734-709-7297 gburgh@gmail.com BURGH ARC 004061 THE WORST OF THE CONTRUCT DOCUMENTS IS TO I AU I WORMERS FOR THE MOM EXECUTION AND COMETTIM OF THE SETS IT THE COMPI THE 0041 DECTUMENTS ME �w�� ARE 1I Is REQUIRED IT ONE SHIMUL M AS THREATS ASIF REMITED MI TOO THE ESTENT MTH � SERI MISTRESSES ME PERESTREHY I FROM THEM M 81 TROPISMS IMMENSITY THE ROSE STMIMENT ARMOR MOSTLY M, ME TME WORMI SISTER, MR THE MT MEET 'IT AYHMESE COHORT TO CONFRACH MOM OR TIME USHER HVAC NOTES O_ 41 Q O O CID E 0 L) TIRRE N (D Q N a Eli m° U ca E t a >1111% RoRRE M M O LL O —0UY ) L_ O CD O U m� III cc (� i U 41 LTi N U X C) . °' W It �:L HVAC NOTES I� C C FBI 1.01 SCOPE OF WORK A THE GENERAL REQUIREMENTS OF THE ARCHITECTURAL SPECIFICATIONS ARE PART OF THESE SPECIFICATIONS. WHERE AN INCONSISTENCY EXISTS BETWEEN THE WORDING OR INTENT, THIS DIVISION SHALL TAKE PRECEDENCE B. THE STANDARD FORM OF GENERAL ONDITIONS ISSUED THE AMERICAN IN ITUTE OF ARCHITECTS DOCUMENT A201, DATES EDITION, SHALL FOR A PART OF THIS C TRACT. C. ALL CONTRACTORS FOR THIS WORK SHALL VERIFY EQUIPMENT LOCATIONS, WEIGHTS AND CLEARANCES IN THE FIELD PRIOR TO SUBMITTING BIDS TO VERIFY CONDITIONS. INTERFERENCES WITH OTHER TRADES, AND DIMENSIONS. NO ALLOWANCES WILL BE MADE AFTER ACCEPTANCE OF BIDS FOR FAILURE TO COMPLY. D. PROVIDE ALL LABOR AND MATERIALS, EQUIPMENT, FACILITIES, TRANSPORTATION AND SERVICES NECESSARY TO FURNISH, INSTALL AND COMPLETE THE HEATING, VENTILATING AND AIR CONDITIONING WORK AS INDICATED ON THE DRAWINGS AND SPECIFIED HEREIN. THE WORKMANSHIP SHALL BE COMPLETE IN EVERY RESPECT, BE TESTED AND APPROVED, AND BE SATISFACTORY TO THE ARCHITECT/ENGINEER AND IN ACCORDANCE WITH THE LOCAL, COUNTY AND STATE LAWS GOVERNING THIS INSTALLATION, INCLUDING THE FIRE MARSHAL. E. THE DRAWINGS INDICATE DIAGRAMMATICALLY THE EXTENT AND LOCATION OF THE WORK INCLUDED. WORK INDICATED. BUT HAVING MINOR DETAILS OBVIOUSLY OMITTED, SHALL BE PROVIDED. INCLUDING THESE DETAILS. WITHOUT EXTRA COST. F. IT IS THE DECLARED AND ACKNOWLEDGED INTENT OF THESE SPECIFICATIONS TO PROVIDE THE HEATING, VENTILATING AND AIR CONDITIONING SYSTEMS, INCLUSIVE OF ALL REQUIRED PARTS, ACCESSORIES AND CONTROLS COMPLETE AND READY FOR USE AS INDICATED ON THE ACCOMPANYING DRAWINGS. WORK INDICATED ON THE DRAWINGS, BUT NOT NECESSARILY INDICATED IN THESE SPECIFICATIONS SHALL BE PROVIDED AS REQUIRED. 1.02 RELATED WORK POWER WIRING (IE FEEDERS) TO MOTORS. INCLUDING FINAL CONNECTIONS TO EQUIPMENT, SHALL BE PROVIDED BY THE DIVISION 16 - ELECTRICAL CONTRACTOR. 1.03 VISITING THE SITE WE CONTRACTOR SHALL, PRIOR TO SUBMITTING HIS BID FOR DOING WORK AS DESCRIBED IN THIS SPECIFICATION AND ON THE ACCOMPANYING DRAWINGS, VISIT THE SITE AND COMPLETELY FAMILIARIZE HIMSELF WNH THE DIFFICULTIES AND FACILITIES THAT WILL BE INVOLVED FOR THE PROPER EXECUTION OF WE CONTRACT. NO EXTRA COMPENSATION SHALL BE ALLOWED FOR THE CONTRACTOR FAILING TO DO SO OR NOT TO FULLY APPRECIATE THE DIFFICULTIES AT HAND. 1.04 FEES AND INSPECTIONS ALL OF THE CONTRACTORS SHALL APPLY. PROCURE AND PAY FEES FOR ALL PERMITS AND INSPECTIONS OR OTHER OBLIGATIONS THAT WE CITY, COUNTY, STATE OR UTILITIES MAY REQUIRE IN ORDER FOR HIM TO DO HIS WORK ACCORDING TO THE PLANS AND SPECIFICATIONS, UNLESS OTHERWISE NOTED. 1.05 LAWS PND ORDINANCES THE CONTRACTOR SHALL GIVE ALL NOTICES AND COMPLY WITH AIL LAWS. ORDINANCES. RULES AND CHANGES SHALL BE ADJUSTED AS PROVIDED IN THE CONTRACT FOR SUCH CHANGES IN WORK. IF THE CONTRACTOR PERFORMS ANY WORK CONTRARY TO SUCH LAWS, ORDINANCES, RULES AND REGULATIONS, HE SHALL BEAR ALL COSTS FOR CORRECTING THE WORK. 1.06 TRADE JURISDICTION WHEN IT BECOMES NECESSARY FOR THE COMPLETE FULFILLMENT OF THIS WORK, FOR THE CONTRACTOR TO FURNISH LABOR OR MATERIALS OTHER THAN WHICH IS GENERALLY ACCEPTED BY HIS TRADE OR BRANCH OF WORK, THE CONTRACTOR SHALL SUBLET SAME TO A CONTRACTOR NORMALLY ENGAGED IN THE TRADE OR BRANCH OF WORK, INVOLVED TO THE END, SO THAT THERE IS NO DELAY TO OR STOPPAGE OF WORK DUE TO THE INFRINGEMENT OR ALLEGED INFRINGEMENT TO TRADE AGREEMENTS AS TO THE JURISDICTION. 1.07 SUBMITTALS THIS CONTRACTOR SHALL SUBMIT TO THE ENGINEER FOR APPROVAL, COMPLETE LISTS INCLUDING CATALOG CUTS, ETC., AND WHERE APPLICABLE DIMENSIONED SHOP DRAWINGS OF ALL MATERIALS, FIXTURES MD EQUIPMENT TO BE FURNISHED AND INSTALLED UNDER THIS CONTRACT. INCLUDE SHEEMEFAL DUCT LAYOUTS AND PIPING PLAN LAYOUTS. REFER TO THE MCHRECT'S GENERAL CONDITIONS FOR NUMBER OF COPIES TO BE SUBMITTED. DO NOT ORDER EQUIPMENT, FABRICATE DUCTWORK, OR INSTALL EQUIPMENT, DUCTWORK OR PIPING BEFORE RECEIVING SHOP DRAWINGS WHICH HAVE BEEN REVIEWED AND APPROVED BY THE ENGINEER. REQUIRED ITEMS TO BE SUBMITTED SHALL INCLUDE, BUT NOT BE LIMITED TO, THE FOLLOWING: DIFFUSERS, GRILLES AND REGISTERS ACCESS PANELS LOUVERS MOTORIZED DAMPERS FIRE DAMPERS EQUIPMENT ROOF CURBS INSULATION CONTROLS SPECIALTIES 1.08 RECORD DRAWING SUBMITTAL AT PROJECT CLOSEOUT, THE CONTRACTOR SHALL SUBMIT RECORD 'AS -BUILT" DRAWINGS OF INSTALLED DUCTWORK, PIPING AND EQUIPMENT AS IT WAS ACTUALLY INSTALLED SO AS TO WE A PERMANENT RECORD. REFER TO THE ARCHITECTS GENERAL CONDITIONS FOR NUMBER OF COPIES TO BE SUBMITIED. 1.09 WORKMANSHIP MD MATERIALS ALL MAI SHALL BE NEW AND OF FIRST QUALITY. ALL LABOR SHALL BE EXECUTED IN A NEAT WORKMANLIKE MINER AND SHALL BE PERFORMED BY MECHANICS SKILLED IN THEIR RESPECTIVE TRADES. THE ENGINEER SHALL DECIDE ALL MATTERS PERTAINING TO THE QUALITY OF WORKMANSHIP AND MATERIALS. ALL DUCTWORK BEING STORED ON SITE AWAITING INSTMIATION AND ALL INSTALLED DUCTWORK WITH OPEN ENDS SHALL BE COVERED TO REDUCE THE CLEMJING EFFORT ONCE THE SYSTEM IS PUT IMO OPERATION. 1.10 SPECIFICATIONS AND DRAWINGS SPECIFICATIONS AND DRAWINGS ME INTENDED TO BE COOPERATIVE. WHAT IS CALLED FOR BY EITHER SHALL BE M BINDING AS IF CALLED FOR BY BOTH. MY WORK OR MATERIALS NOT SPECIFICALLY MENDONED, THOUGH REQUIRED TO MAKE THE JOB COMPLETE, SHALL BE FURNISHED BY THE CONTRACTOR AT HIS EXPENSE. 1.11 OPERATING INSTRUCTIONS THIS CONTRACTOR SHALL PREPARE A TYPEWRITTEN LIST OF OPERATING INSTRUCTIONS FOR ALL THE EQUIPMENT INSTALLED UNDER THIS CONTRACT, AND SHALL INSTRUCT THE OWNER IN ITS OPERATION. INDIVIDUAL MANUALS PROVIDED BY THE EQUIPMENT MANUFACTURERS SHALL BE INCLUDED. 1.12 EQUIPMENT SCHEDULE THIS CONTRACTOR SHALL PREPARE AND FURNISH TO THE OWNER, TWO (2) BOUND BOOKLETS, EACH CONTAINING A COMPLETE LIST OF ALL EQUIPMENT AND VALVES INSTALLED UNDER THIS CONTRACT. EACH PIECE OF EQUIPMENT AND VALVE LISTED SHALL INCLUDE ITS TAG NUMBER, MANUFACTURERS MODEL NUMBER AND COMPONENTS THEREIN WHICH MAKE UP THE SPARE PMTS UST. 1.13 GUARANTEE THIS CONTRACTOR SHALL GUARANTEE HIS WORK TO BE FREE FROM DEFECTIVE WORKMANSHIP AND MATERIALS FOR A PERIOD OF ONE (1) YEAR FROM DATE OF FINAL CERTIFICATE. ANY REPAIRS OR REPLACEMENT DURING THE PERIOD SHALL BE MADE WITHOUT COST TO THE OWNER, UPON HIS OR HER REQUEST. 1.14 COORDINATION OF WORK CONTRACTOR CAUSED BY HIS NEGLECT TO COMPARE AND CONFER WITH OTHER TRADES SHALL BE MADE BY HIM AT HIS OWN EXPENSE. 1.15 CUTTING AND PATCHING EACH CONTRACTOR SHALL DO HIS OWN CUTTING AND PATCHING. IF STRUCTURALLY REQUIRED, HE SHALL PROVIDE AND INSTALL THE NECESSARY STEEL WHEN GOING THROUGH A LOAD BEARING WALL. THIS CONTRACTOR SHALL NOT ENDANGER ANY WORK BY CUTTING, DIGGING OR OTHERWISE AND SHALL NOT CUT OR ALTER THE WORK OF OTHER TRADES WITHOUT CONSENT OF THE ARCHITECT/ENGINEER. 1.16 DEMOLITION A. PIPING, VALVES, DUCTWORK, EQUIPMENT, ETC., WHICH IS REQUIRED TO BE REMOVED TO PERFORM WORK UNDER THIS SPECIFICATION WILL BE PERFORMED BY THIS CONTRACTOR AND TURNED OVER AND DELIVERED TO THE BUILDING MAINTENANCE DEPARTMENT OR DISPOSED OF AS DIRECTED. B. ANY HOLES OR OPENINGS LEFT IN WALLS, ROOFS, FLOORS, CEILINGS, ETC., AFTER REQUIRED DEMOUION WORK, SHALL BE FILLED IN AND PATCHED BY THIS CONTRACTOR IN A MANNER APPROVED BY THE ARCHRECT AND ENGINEER. FAILURE ON THIS CONTRACTOR'S PART TO COMPLY WITH ABOVE SHALL MAKE HIM RESPONSIBLE FOR ANY EXTRA EXPENSE INVOLVED. C. ANY EQUIPMENT OR ARCHITECTURAL ELEMENTS DAMAGED OR DESTROYED IN THE DEMOLITION WORK SHALL BE REPAIRED, REPLACED AND/OR BROUGHT BACK TO GOOD WORKING ORDER TO THE SATISFACTION OF THE ARCHITECT AND ENGINEER. 1.17 MECHANICAL IDENTIFICATION A. GENERAL: PROVIDE MECHANICAL IDENTIFICATION FOR ALL MECHANICAL EQUIPMENT, PIPING AND DUCT SYSTEMS. COMPLY WITH ANSI A13.1 FOR LETTERING SIZE. LENGTH OF COLOR FIELD. COLORS AND VIEWING ANGLES OF IDENTIFICATION DEVICES. B. EQUIPMENT: PROVIDE EQUIPMENT SYSTEM NUMBER, CAPACIIY, FLOW RATE, STATIC PRESSURE, PUMP HEAD, HORSEPOWER AND VOLTAGE. PROVIDE SUCH MODEL WENiMARK' MARKERS. C. PIPING: PROVIDE SYSTEM DESIGNATION NAME AND DIRECTION OF FLOW. PROVIDE SUCH MODEL 'SETMARK' PIPE MARKERS. D. DUCTS: PROVIDE SYSTEM DESIGNATION NAME ANO DIRECTION OF FLOW. PROVIDE SUCH MODEL NENTMARK' MARKERS. E. VALVES: PROVIDE BRASS VALVE TAGS AND BRASS 'S' HOOK FASTENERS WITH VALVE NUMBER AND TYPE OF SERVICE NOTED ON THE TAG. PROVIDE DUPLICATE VALVE CHARTS. THE CHART SHALL BE FOR ALL VALVES AND SHALL INDICATE VALVE IDENTIFICATION NUMBER, LOCATION AND PURPOSE. PROVIDE SUCH BRASS VALVE TAGS AND VALVE CHARTS. 1.18 TESTING AND BALANCING THIS CONTRACTOR SHALL NEGOTIATE A CONTRACT WITH AN INDEPENDENT, QUALIFIED AND CERTIFIED MEMEBER OF NEBB OR AABC TO COMPLETELY BALANCE THE AIR AND HIDRONIC SYSTEMS INCLUDED IN THIS SPECIFICATION AND ACCOMPANYING DRAWINGS, AS REQUIRED. THE CONTRACTOR SHALL SUBMIT A PROJECT CERTIFICATION GUARANTEE AND CERTIFIED BALANCE REPORT TO THE ARCHITECT/ENGINEER FOR REVIEW PND APPROVAL PRIOR TO FINAL ACCEPTANCE OF THE SYSTEMS BY THE OWNER. 1.19 NOISE AND VIBRATION CONTROL THIS CONTRACTOR SHALL PROVIDE ACCOUSRCAL AND VIBRATION TREATMENT FOR ALL EQUIPMENT WITH MOVING PARTS TO MEET CODE AND MAINTAIN THE FOLLOWING NOISE CRITERIA: LOBBIES, TOILETS AND CORRIDORS NO 40 SPACE ADJACENT TO FAN ROOMS NO 45 OFFICES, CONFERENCE ROOM, ETC. NO M VIBRATION ISOLATORS AND FLEXIBLE CONNECTIONS SHALL BE USED AT EACH PIECE OF EQUIPMENT WITH MOVING PARTS. 1.20 BUILDING STANDARDS IF BUILDING HAS STANDARDS FOR PIPING. DUCTWORK. DIFFUSERS, GRILLES, REGISTERS, TEMPERATURE CONTROLS, OTHER EQUIPMENT, ETC., PROVIDE SAME UNLESS OTHERWISE NOTED. 2.0 PRODUCTS, MATERIALS AND CONTROLS 2.01 HANGERS AND SUPPORTS A. PIPING HANGERS AND SUPPORTS SHALL COMPLY WITH MSS SP -58. PROVIDE ONLY ONE TYPE OF HANGER/SUPPORT, BY ONE MANUFACTURER, FOR EACH PIPING SERVICE. B. DUCT HANGERS AND SUPPORTS SHALL BE IN ACCORDANCE WITH SMACNA DUCT CONSTRUCTION STANDARDS. C. EQUIPMENT HANGERS AND SUPPORTS SHALL BE PROVIDED AND INSTALLED PER THE EQUIPMENT MANUFACTURER'S REQUIREMENTS. 2.02 ACCESS DOORS ACCESS DOORS SHALL BE INSTALLED FOR ALL NON -ACCESSIBLE EQUIPMENT, VALVES, OPERATIONS, CONTROLS, OR OTHER WORKING PARTS REQUIRING MNIENANCE OR ADJUSTMENT. THIS CONTRACTOR SHALL FURNISH ALL SUCH ACCESS DOORS AND ADVISE GENERAL CONTRACTOR OF THE LOCATION OF ALL ACCESS DOORS REQUIRED THROUGHOUT THE PROJECT. ACCESS DOOR MANUFACTURER'S DATA SHALL BE SUBMITTED FOR REVIEW MD APPROVAL BY WE ARCHITECT AND ENGINEER. COLOR OF ACCESS DOORS SHALL BE APPROVED BY THE ARCHITECT. 2.03 EQUIPMENT A. PROVIDE AND INSTALL ALL EQUIPMENT AS SHOWN IN THE EQUIPMENT SCHEDULES. B. ALL EQUIPMENT DATA SHALL BE SUBMITTED FOR REVIEW AND APPROVAL BY THE ARCHITECT AND ENGINEER. C. COLOR OF ALL DIFFUSERS, GRILLES AND REGISTERS SHALL BE APPROVED BY THE ARCHITECT. D. COORDINATE FINAL LOCATION OF ALL THERMOSTATS, DIFFUSERS, GRILLES MD REGISTERS WITH THE ARCHITECT'S REFLECTED CEILING PLAN. 2.04 DUCTWORK AND ACCESSORIES A. ALL DUCTWORK SHALL BE PRIME GALVANIZED SHEET STEEL, LOCK FORMING, FIRST QUALITY, FABRICATED IN ACCORDANCE WITH THE LATEST EDITION OF THE MHRAE GUIDE, EXCEPT AS NOTED OTHERWISE. B. ROUND SPIRAL DUCTWORK SHALL BE UNITED SHEET MEAL TYPE DUCT FITTINGS, OR APPROVED EQUAL, INSTALLED AND SUSPENDED AS PER MANUFACTURER'S RECOMMENDATIONS. C. ALL DUCTS ARE TO HAVE GALVANIZED STIFFENERS IN THE FORM OF SEAMS INVOLVING AT LEAST THREE FOLDS OF SHEET METAL (POCKET LOCKS, STANDING SEAMS, STANDING S -SLIPS, ETC.). D. VENTILATION CONSTRUCTION NOT COVERED BY THE ASHRAE GUIDE AND/OR GOVERNING AUTHORITIES SHALL BE IN ACCORDANCE WITH THE MAXIMUM STANDARDS AND TRADE PRACTICES AS SET FORTH BY THE SHEET METAL AND AIR CONDITIONING CONTRACTORS NATIONAL ASSOCIATION (SMACNA) INCLUDING THEIR MOST CURRENT DUCT MANUAL E. DUCT DIMENSIONS SHOWN ON THE DRAWINGS INDICATE INSIDE DIMENSIONS. INCREASE DUCT SIZE WHEN LINING IS UTILIZED. F. LOW PRESSURE DUCTWORK SHALL BE CONSIDERED AS ALL DUCTWORK NOT DEFINED AS MEDIUM PRESSURE DUCTWORK, UNLESS NOTED OTHERWISE. PROVIDE 2' SP DUCT CONSTRUCTION FOR SUPPLY MR DUCTS AND 1' SP CONSTRUCTION FOR RETURN AND EXHAUST MR DUCTS, UNLESS OTHERWISE NOTED. G. MEDIUM PRESSURE DUCTWORK SHALL BE CONSIDERED AS ALL DUCTWORK UPSTREAM OF VAV BOXES AND FAN -POWERED BOXES. PROVIDE T SP DUCT CONSTRUCTION UNLESS NOTED OTHERWISE. ROUND SINGLE WALL MEDIUM PRESSURE DUCTWORK IN SOUND-UNED SYSTEMS WILL NOT BE PERMITTED IN LENGTHS GREATER THAN FIVE FEET. H. ALL LOW AND MEDIUM PRESSURE DUCTWORK SHALL BE SEALED WITH AN APPROVED MASTIC. SYSTEM WILL BE 516 OF TOTAL AIR MANTIIY. SUBMIT TEST DATA SHEETS) TO ARCHITECT/ENGINEER FOR APPROVAL. J. A 5'-0' MAXIMUM LENGTH OF INSULATED FLEXIBLE DUCT WILL BE PROVIDED TO EACH SUPPLY OUTLET MND RETURN INLET AS REQUIRED. K. DIFFUSER TAKE -OFF WHERE DIFFUSER IS LOCATED BELOW THE MAIN TRUNK, AND WHERE INDICATED. DEVICE SHALL BE COMPLETE WITH WORM GEAR MECHANISM FOR OPERATION OR ADJUSTMENTS THIRD THE FACE OF THE DIFFUSER. IF TURNING DEVICE IS LOCATED REMOTELY FROM GRILLE, REGISTER OR DIFFUSER, PROVIDE EXTENSION ROD ON ADJUSTING DEVICE. TITTLE AND BAILEY, "VENTROL NDC' OR APPROVED EQUAL. L PROVIDE FACTORY -FABRICATED TURNING VANES IN ALL SQUARE ELBOWS. VANES SHALL BE BARBER -COLEMAN 'AIRTURNS' OR APPROVED EQUAL M. TAPERED SPIN -IN FITTING, WITH LOCK -IN QUADRANT AND VOLUME DAMPER SHALL BE PROVIDED FROM BRANCHES TO DIFFUSERS, FOR LOW PRESSURE DUCTWORK. N. ALL BRANCH DUCT TAKE -OFFS SHALL BE EQUIPPED WITH TAPERED FITTINGS. 0. ALL FULL RADIUS ELBOWS SHALL HAVE A CENTERUNE RADIUS OF 1.5 TIMES THE DUCT WIDTH. ELBOWS WITH A CENTERUNE RADIUS LESS THAN 1.5 TIMES THE DUCT WIDTH SHALL HAVE TURNING VINES. P. VOLUME DAMPERS SHALL BE PROVIDED FOR AIR BALANCE PURPOSES. PROVIDE MANUAL VOLUME DAMPERS ON ALL LOW PRESSURE SUPPLY, RETURN AND EXHAUST DUCT BRANCHES AND TO AIR DIFFUSERS, REGISTERS PND GRILLES, UNLESS NOTED OTHERWISE. DAMPERS SHALL BE OPPOSED BLADE TYPE UNLESS NOTED OTHERWISE. 1. FOR VOLUME DAMPERS ABOVE DRYWALL CEILINGS AND OTHER INACCESSIBLE LOCATIONS, PROVIDE LEVER, POSITION INDICATOR AND LOCK NUT, ENCLOSED IN A DEEP DIE-CAST BOX WITH ADJUSTABLE 2-5/8' DIAMETER COVER. YOUNG REGULATOR SERIES 315 OR VENTLOCK SERIES 677 AND/OR PROVIDE ACCESS PANEL, SIZED AS REQUIRED ( IT X 1T MINIMUM). 2. FOR VOLUME DAMPERS ABOVE ACCESSIBLE CEILINGS, PROVIDE LOCKING TYPE WITH LEVER HANDLE, POSITION INDICATOR AND LOCK NUT. YOUNG REGULATOR SERIES 400 OR VENTLOCK SERIES 600. Q. DYNAMIC RATED FIRE DAMPERS SHALL BE PROVIDED PER CODE REQUIREMENTS. PROVIDE TYPE B' FIRE DAMPERS FOR LOW PRESSURE DUCTWORK AND TYPE "C' FIRE DAMPERS FOR MEDIUM PRESSURE DUCTWORK. PROVIDE A DUCT ACCESS DOOR FOR EACH FIRE DAMPER. R. ROOFTOP UNIT LEVELING CURBS SHALL BE PROVIDED BY THE GENERAL CONTRACTOR. THE MECHANICAL CONTRACTOR IS TO INSTALL FACTORY PROVIDED CURBS ON TOP OF LEVELING CURB SO THAT THE ROOFTOP EQUIPMENT IS INSTALLED PLUM AND LEVEL, UNLESS OTHERWISE NOTED. S. PROVIDE RIGID LINED CONNECTIONS AT THE INLET AND OUTLET OF EACH VAV BOX AND INLET OF EACH FAN -POWERED BOX. FLEXIBLE CONNECTIONS ARE ONLY PERMITTED ON THE DISCHARGE OF FAN -POWERED BOXES. T. ALL UNINSULATED EXTERIOR DUCTWORK WHICH IS EXPOSED TO THE OUTDOOR ELEMENTS SHALL BE GALVANIZED OR BLACK IRON PND OF CONSTRUCTION TO COMPLY WITH SMACNA STANDARDS. PROVIDE WATER -PROOF SEAMS AND TWO COATS OF TPR -BASED PAINT OVER ALL DUCTWORK EXPOSED TO THE OUTDOOR ELEMENTS. PROVIDE 'PATE CO.' TYPE ROOF SUPPORTS WITH ALL NECESSARY ANGLE IRON SUPPORT LEGS AND CROSSES. WHEREVER THIS DUCTWORK PENETRATES THE BUILDING ENVELOPE, THE PENETRATION SHALL BE MADE WATER -PROOF. U. ALL KITCHEN HOOD EXHAUST DUCTWORK SHALL BE 14 GAUGE BUCK IRON OR 18 GAUGE 303 STAINLESS STEEL WITH CONTINUOUSLY WELDED SEAMS. ACCESS DOORS SHALL BE PROVIDED EVERY 20 FEE AND AT EVERY CHANGE IN DIRECTION. V. ALL DISHWASHER EXHAUST DUCTWORK SHALL BE ALUMINUM OF WATERTIGHT CONSTRUCTION. DUCTWORK SHALL BE PITCHED AT U(" PER FOOT TO ENSURE THAT ANY DEVELOPED CONDENSATION TRAVELS BACK TO THE DISHWASHER EQUIPMENT. 2.05 PIPING A. ALL PIPING FOR WORK CONTAINED IN THIS SPECIFICATION AND ACCOMPAM'ING DRAWINGS SHILL BE IN CONFORMANCE WITH ASTM STANDARDS. ALL CHANGES IN DIRECTION WILL BE MADE WITH FITTINGS. REAM ALL PIPING AND CLEAN OUT SAME BEFORE ASSEMBLY. PROVIDE VALVES OF SIMILAR MATERIAL AS THE PIPING MATERIAL THEY ARE INSTALLED IN. FERROUS BODY VALVES WITH STEEL PIPING. BRASS AND BRONZE VALVES WITH COPPER PIPING. PROVIDE DIELECTRIC FITTINGS. UNIONS. ETC. WHERE PIPING, VALVES. FITTINGS, EQUIPMENT, ETC. OF DISSIMILAR METALS ME JOINED. COVER OPEN PIPING DURING CONSTRUCTION. FLUSH OUT AND CLEAN PIPING IN A MANNER THAT IS APPROVED BY THE ENGINEER. FOR EACH BRANCH TAKE -OFF. PROVIDE A 3-ELB0W 'I SHAPE CONNECTION TO PROVIDE PIPING FLEXIBILITY FOR EXPANSION. PROVIDE GUIDES, ANCHORS, EXPANSION LOOPS, SUPPORTS, VENTS, DRAINS, MAKE-UP WATER, ETC., AS REQUIRED. B. COPPER PIPING SHALL HAVE SOCKET FITTINGS FOR SOLDER OR BRAZING CONNECTIONS. C. STEEL PIPING SHALL BE SCHEDULE 40, ASTM A120 OR A53, UNLESS OTHERWISE NOTED. THE FITTINGS IN PIPE 2' AND SMALLER SHALL BE CAST IRON OR MALLEABLE, UNLESS OTHERWISE NOTED. AIL PIPING 2-1/2' AND URGER SHALL BE BUTT WELDED. WELDING SHALL BE DONE ONLY BY WELDERS CERTIFIED FOR THIS TYPE OF WORK. ALL FITTINGS SHALL BE AS MANUFACTURED BY STOCKHOLM. BONNEY FORGE, WALWORTH, GRINNED OR TUBE TURNS. PANT ALL EXPOSED THREADS AFTER ASSEMBLY. FOR ALL PIPING EXPOSED TO THE OUTSIDE MR, PAINT PIPING WITH ONE COAT OF RUST INHIBITING PRIMER AND ONE COAT OF BUCK FINISH PANT. D. PIPING SYSTEMS AND MATERIALS 1. REFRIGERANT PIPING: TYPE K DRAWN COPPER. PROVIDE SHUTOFF VALVES, FILTER DRIERS, SOLENOID VALVES, THERMAL EXPANSION VALVES, SIGHT GLASSES, PRESSURE GAUGES, OIL TRAPS, ETC., AS REQUIRED. PROVIDE REFRIGERANT VENT PIPING TO THE OUTDOORS AS REQUIRED. 2. HVAC DRAIN PIPING: TYPE L DRAWN COPPER FOR INDOOR DRAINS FROM COPPER PIPING SYSTEM. SCHEDULE 40. ASTM A120 OR A53 STEEL FOR INDOOR DRAINS FROM STEEL PIPING SYSTEMS. SCHEDULE 40 PVC PLASTIC FOR OUTDOOR DRAINS. INSTALL A TRAP IN THE DRAIN PIPE. PROVIDE A CONCRETE SPLASH BLOCK FOR DRAIN TERMINATIONS FROM ROOFTOP HVAC UNITS. 3. GAS PIPING: PROVIDE SCHEDULE 40 STEEL PIPE OR CORRUGATED STAINLESS STEEL TUBING (CSST). PROVIDE VENTED ENCLOSURES FOR RISERS AND HORIZONTAL RUNS ( IN PLENUM CEILINGS, ETC.). FOR SCHEDULE 40 PIPE SIZES 2- AND SMALLER, PROVIDE ALL WELDED OR ALL SCREWED FITTINGS. FOR SCHEDULE 40 PIPE SIZES 2-1/T AND LARGER, PROVIDE ALL WELDED FITTINGS. ALL CSST SHALL MEET THE DESIGN AND INSTALLATION REQUIREMENTS SET FORTH IN ANSI/AGA LC 1-1993. GROUND ALL GAS PIPING. INSTALL DIRT LEGS IN ALL PIPING IMMEDIATELY BEFORE CONNECTION TO EACH PIECE OF EQUIPMENT. INSTALL VENT PIPING FROM VALVES, IF REQUIRED, TO THE OUTDOORS WITH WEATHER-PROOF AND INSECT -PROOF OUTDOOR TERMINATION DEVICES. 2.06 INSULATION A. FURNISH AND INSTALL INSULATION AS SPECIFIED. B. DUCT INSULATION 1. ALL SUPPLY, RETURN, AND EXHAUSr AIR DUCTWORK IN UNCONDITIONED SPACES: 1 -1/2 - FLEXIBLE GLASS FIBER WITH FACTORY APPUED ALUMINUM FOIL VAPOR BARRIER. 3/4 LBS. PER CUBIC FOOT DENSITY. FLAME SPREAD RATING OF NOT GREATER THAN 25 AND A SMOKE DEVELOPED RATING OF NOT GREATER THAN 50. 2. ALL OUTSIDE MR DUCTWORK AND DUCTWORK IN MECHANICAL ROOMS: 2' SEMI-RIGID GLASS FIBER WITH FACTORY APPLIED, WHITE, ALL SERVICE, VAPOR BARRIER JACKET. 3 LBS. PER CUBIC FOOT DENSITY. FLAME SPREAD RATING OF NOT GREATER THAN 25 AND A SMOKE DEVELOPED RATING OF NOT GREATER THAN 50. 3. ALL KITCHEN HOOD EXHAUST DUCTWORK: 2' THICK MINERAL WOOL WITH CANALS COVERING JACKET OVER INSULATION. COVERING OVER ACCESS PANEL SHALL BE REMOVABLE. C. INSULATED FLEXIBLE DUCT ALL SUPPLY AND RETURN/EXHAUST AIR CONNECTIONS TO EACH DIFFUSER: POLYETHYLENE GORE LAMINATED TO A GALVMIZED STEEL WIRE HELIX; 1' THICK, 1 LB. PER CUBIC FOOT DENSITY GLASS FIBER INSULATION; FIBERGLASS REINFORCED, METALLIZED, VAPOR BARRIER. D. PIPE INSULATION FINISH AS RECOMMENDED BY THE MANUFACTURER. K -VALUE OF 0.27 AT 75 DEGREES F. 2. CHILLED WATER SUPPLY AND RETURN, HEATING HOT WATER SUPPLY AND RETURN, LOW PRESSURE STEAM AND CONDENSATE, AND COOLING COIL INTERIOR CONDENSATE DRAIN PIPING: HEAW DUTY, MOLDED GLASS FIBER WITH FACTORY APPLIED ALL SERVICE VAPOR BARRIER JACKET AND SELF-SEALING JOINTS. V THICK FOR PIPE SIZES 2' AND SMALLER. 1-1/2' THICK FOR PIPE SIZES 2-1/2' AND LARGER. K -VALUE OF 0.24 AT 75 DEGREES F. 2.07 CONTROLS A THE NEW TEMPERATURE CONTROL SYSTEM SHALL BE AN EXTENSION OF THE EXISTING SYSTEM. EXTEND PNEUMATIC TUBING OR WIRING TO ALL NEW AND/OR RELOCATED EQUIPMENT AND DEVICES. MATCH EXISTING TEMPERATURE CONTROL THERMOSTATS AND OTHER EXPOSED CONTROLS AS MANUFACTURED AND/OR SUPPLIED BY THE ORIGINAL BUILDING STANDARD TEMPERATURE CONTROL CONTRACTOR, AS APPLICABLE. B. TYPICAL EXHAUST FAN CONTROL THE FANS SHALL BE CONTROLLED AS NOTED ON THE EQUIPMENT SCHEDULE. 3.0 EXECUTION 3.01 INSPECTION PRIOR TO BEGINNING ANY WORK, CAREFULLY COORDINATE WITH THE WORK OF OTHER TRADES AND AT TIMES CONFIRM THAT THE WORK OF OTHERS IS COMPLETE TO THE POINT WHERE THIS INSTALLATION CAN PROPERLY COMMENCE. 3.02 GENERAL INSTALLATION REQUIREMENTS VERIFY QUANTITIES, CAPACITIES. PERFORMANCE CHARACTERISTICS, OPERATING REQUIREMENTS AND CURRENT CHARACTERISTICS OF ALL EQUIPMENT PRIOR TO ITS INSTALLATION. VERIFY THAT SPACE ALLOTTED FOR EQUIPMENT IS SUFFICIENT FOR ENTRANCE AND INSTALLATION, MAINTENANCE AND SERVICE, AND REMOVAL AND REPLACEMENT. 3.03 COORDINATION OF INSTALLATION A INSTALL WORK IN SUCH A MANNER THAT IT WILL CONFORM TO THE STRUCTURE, AVOID OBSTRUCTIONS, MAINTAIN HEADROOM AND KEEP OPENINGS PND PASSAGEWAYS CLEAR. GENERALLY, KEEP HORIZONTAL UNES AS HIGH AS POSSIBLE. MAKE LOCAL PROVISIONS FOR THE SERVICING AND REMOVAL OF EQUIPMENT. B. ANY INTERFERENCE WITH WORK OF OTHER TRADES ARISING FROM FAILURE TO COORDINATE THE WORK AND LACK OF COOPERATION HEREUNDER. SHALL REQUIRE THE REMOVAL AND REINSTALLATION OF ALL INTERFERING WORK WITHOUT ADDITIONAL COST TO THE OWNER. 3.04 IDENTIFICATION OF EQUIPMENT EACH PIECE OF EQUIPMENT SHALL DISPLAY A PERMANENT MEAL OR PLASTIC NAMEPLATE WHICH SHALL BE LOCATED SO AS TO BE ALLY VISIBLE AFTER THE EQUIPMENT HAS BEEN INSTALLED. THE NAMEPLATE SHALL SHOW THE EQUIPMENT NUMBER AND OTHER PERTINENT INFORMATION. 3.05 CLEAN UP A UPON COMPLETION OF THE INSTALLATION OF DUCTWORK, CLEAN THE EMPIRE SYSTEM OF RUBBISH, PILASTER, DIRT, ETC., BEFORE INSTALLING THE DIFFUSERS, REGISTERS AND GRILLES. B. REMOVE TEMPORARY FILTERS FROM RETURN INLETS. C. OPERATE AND MANE ANY REQUIRED ADJUSTMENT TO EQUIPMENT, DUCTWORK, PIPING, ETC., AS MAY BE NECESSARY TO PUT THE SYSTEMS IN PROPER OPERATING CONDITION. D. REMOVE ALL LABELS, TAGS, ETC., FROM ANY SPECIALTIES, EQUIPMENT, ETC., AND REMOVE ALL GREASE OR OTHER PROTECTIVE COATING FROM ALL EQUIPMENT, PIPING, ETC., AND LEAVE WORK IN A MANNER THAT IS ACCEPTABLE TO THE MCHRECT/ENGINEER. 3.06 OPERATING AND MAINTENANCE INSTRUCTIONS AFTER HAVING COMPLETELY INSTALLED ALL SYSTEMS AND ALL NECESSARY TESTS ME COMPLETED, THIS CONTRACTOR SHALL WE ARRANGEMENTS TO OPERATE ALL THE SYSTEMS FDR A PERIOD OF NOT LESS THAN FIVE (5) DAYS AT NO EXPENSE TO THE OWNER. A WRITTEN NOTIFICATION OF THIS TRIAL OPERATING PERIOD SHALL BE PRESENTED TO THE ARCHITECT/ENGINEER, TEN (10) DAYS IN ADVANCE. FOR APPROVAL. DURING THIS TRIAL OPERATING PERIOD, THE CONTRACTOR MAY MAKE NECESSARY MINOR, BUT NON-INTERUPTVE ADJUSTMENTS, AND ALSO SHALL GIVE INSTRUCTIONS TO THE OWNER'S OPERATING PERSONNEL OR REPRESENTATIVES, ON THE OPERATION AND MAINTENANCE OF THE VARIOUS ITEMS OF EQUIPMENT AND SYSTEMS. 3.07 INSPECTION A. VISUALLY INSPECT ALL EQUIPMENT FOR COMPLETENESS AND FUNCTIONAL READINESS. B. LUBRICATE ALL FAN MD MOTOR BEARINGS. C. CHECK ALL FANS FOR ALIGNMENT MD CLEARANCE. D. INSPECT ALL DAMPERS FOR PROPER UNKAGE AND SETTING FOR OPERATION. E. CONFIRM THAT THE CONTROL SYSTEM HAS BEEN COMPLETED, CALIBRATED AND IS IN OPERATION. 3.08 ELECTRICAL A. INSPECT THE MOTOR CONTROL CENTERS, DISCONNECT SWTCHES, OVERLOAD PROTECTON AND WIRING FOR THE HVAC EQUIPMENT PRIOR TO STARTUP OF THE EQUIPMENT. B. COORDINATE THE STARTUP OF EQUIPMENT WITH THE ELECTRICAL CONTRACTOR. 3.09 CLOSING IN WORK WORK SHALL BE INSPECTED AND THEN APPROVED BY THE ARCHITECT/ENGINEER AND/OR AUTHORITIES HAVING JURISDICTION. ANY WORK COVERED PRIOR TO SUCH INSPECTION, TEST MD APPROVAL SHALL BE UNCOVERED, IF SO REQUESTED, AND AFTER APPROVAL, COVERED AGAIN WITHOUT COST TO THE OWNER. 3.10 TESTING, ADJUSTING AND BAIAINCING A THE HVAC CONTRACTOR SHALL HIRE AN INDEPENDENT, QUALIFIED AND CERTIFIED MEMBER OF NEBB OR AASC TO COMPLETELY BALANCE THE AIR AND HYDRONIC SYSTEMS, AS REQUIRED. THE TEST MD BALANCE CONTRACTOR SHALL SUBMIT A PROJECT CERTIFICATION GUARANTEE AND CERTIFIED BALANCE REPORT TO THE ENGINEER FOR APPROVAL BEFORE FINAL ACCEPTANCE. B. ADJUST ALL SUPPLY, RETURN AND EXHAUST DEVICES TO PLUS OR MINUS 5 PERCENT OF THE DESIGN AIRFLOW QUANTmES. C. ADJUST HYDRONIC FLOW QUANTITIES TO PLUS OR MINUS 10 PERCENT OF INDICATED DESIGN FLOWS. D. THE BALANCING CONTRACTOR SHALL REPORT ANY DEFICIENCIES TO THE ENGINEER AND MECHANICAL CONTRACTOR. THE BALANCING CONTRACTOR SHALL ALSO RECOMMEND POSSIBLE ACTIONS TO REMEDY THE DEFICIENCIES. E. IN GENERAL THE MECHANICAL CONTRACTOR SHALL CHANGE FAN SHIEVES, PUMP IMPELLERS, DRIVES, ETC., TO REMEDY THE DEFICIENCIES AT NO ADDITIONAL COST TO THE OWNER. rj MECHANICAL SPECIFICATIONS U 10 Anther Architects, PLLC Architecture + Engineering 3727 Candia Drive Punta Gorda FL 33950 800-243-0528 734-709-7297 gburgh@gmail.com THE WORST OF THE CONTRAST DOCUMENTS IS TO I AU I WORMERS FOR THE MOM EXECUTION AND COMETTIM OF THE SETS IT THE CENTIMETER THE Owwr DERMUMENTS ME �w�� ME 1I Is THE ROE STMIMENT ARMOR MOSTLY RETIREMENT SHALL AMI WITHOLT SHARER TO CONTRAST ME, 11 "1 WORMI SISTER, MR THE SHEET MEE 'IT AUTHORZE CHMSGEM TO CONFRACH MOM OR TIME USHER ;10 WheaYR6 U HIS w 0 c G�O9 DMS Mechanical Specs M3 _O 4_A RIO RRO Q i }F O /O Irr C C O U TIRRE N (D Q N CL TEEEE MID U ca E t OL >1111% RiRRE M _ M En O 00 z /lU m LLQ U C: _ _Y � O 0L C7 0) U m tY cc ZP (� i U }ALO N U X C).r. 00 0 w It �:L Mechanical Specs M3 I C CAUTION: IF THIS SHEET IS NOT 30R 4 IT IS A REDUCED PRINT GENERAL NOTES I. NEPER TO CENEHPL NOTES ON SHEET MOA 2. RETER TO SPECINGPONS ON SHEET M0.1 KEY NOTES O 16'0 DUCT UP FROM IXTRACOON BOOTH BROW. 16°0 ROOF W TO BE PRGYIDED MTTH BIRDSCREEN OND BACKORAFT DAIFER. MOTORIZED CAMPER TO BE INTEBLOCHED TO OPEN WHEN EF FAN RUNS. O ENHMIST DISCHARGE TO BE A MINIMUM OF 10'-0• AWAY FROM ANY ONSIDE NR INTONES. Oj NEW ROOF MOUNTED WE UP MR UNR TO BE PULED AT A MINIMUM OF 10'-0• AWAY FROM ANY E%HAIIST )SCHARGE WE UP NR UNIT TO BE CONIROLL£D BY ErRACTON BOOTH BROW. WHEN BOOTH 15 OPERTTIXNL WE UP NR UNIT TO SUPT S00 CM OF OJTSIDE HR. WHEN BOOTH GOES IMO EMERGENCY MOLE (PURGE MODE) WE UP NR UNIT TO SUNNI 1500 CFM OF OUTSIDE. © 16•X19• RETURN NR DUCT THROUGH ROOF. O1-1/1• GAS UNE TO SE RAN ON ROOF TO FEED WL -I. PROHDE ORE IED AND GAS REGUUTOR BEFORE CONNECTKKI TO MOU-1. Gi5 PRESSURE TO BE A MINIMUM OF 7 IN WA OCONTRACTOR TO FEED YERIFT WHICH IX5TNG MRRR TO TOP OFF MGM AS WI AS IF THAT MI Nis CAPACITY FOR NEW W-1 UNI. GOORDINCIE WON GAS UTUPT COMPANY FOR MEMO GAS LOAD. O] MITTR INE ACTUAL LOCATION OF WJJ-1 IN FEW WITH G.0 O6 18.0 MORE UP AIR DUCT N CONNECT TO MAU 21'X•16• DISCHARGE. 16.0 WE UP AR DUCT THROUGH ROOF 1/4" = 1'-0" MECHANICAL I I 2 I 3 I ROOF PLAN SHOWING MAKE-UP AIR IF y�•y 4 '. IWE ESH O O DRI 0 U 1 e OO Ecc,N ©❑ O 60M 000 O Cyt O_^E 1—I/C FIG 1/4" = 1'-0" MECHANICAL I I 2 I 3 I ROOF PLAN SHOWING MAKE-UP AIR IF io Anther Architects, PLLC Architecture + Engineering 3727 Candia Drive Punta Gorda FL 33950 500-243-0528 734-709-7297 gburgh@gmail.com BURGH ARC 004061 THE WORST OF THE CONTRAST DOCUMENTS IS TO I AU TROM WORMERS FOR THE MOM EXECUTION AND COMETTIM OF THE SETS TV THE CENTIMETER THE Owwr SEDIMENTS ME �w�� ME 1I Is MOMEITIOMORCHREST THE ROSE STMIMENT ARMOR MOSTLY RETIREMENT S,,1 NTH, ITTIOLT OHMME TO WITMOT SEES SIR HEAR WORMI SISTER, MR THE M, M, 'IT AUTHURSE GARGES TO CONFRACH MOM OR TIME USHER to NNhear Rio' U � w 0 G�T9 pMs y�•y 4 '. 0 U Ecc,N 0� 000 Cyt O_^E W M W M O Q M U)W Q Z O J 0 L O t) C O Q Q > W Lo CD CID /O co C C Q TIRRE N (D Q N CL r MID U 2 E t OL M M U �� z F m LL _J _ ca O 0 C7OIII U EL (� w U }0 L(7 U X LL p w �� Go O U a x U W am INMAN 6.: KB R EEI JBN. SHEET io Anther Architects, PLLC Architecture + Engineering 3727 Candia Drive Punta Gorda FL 33950 500-243-0528 734-709-7297 gburgh@gmail.com BURGH ARC 004061 THE WORST OF THE CONTRAST DOCUMENTS IS TO I AU TROM WORMERS FOR THE MOM EXECUTION AND COMETTIM OF THE SETS TV THE CENTIMETER THE Owwr SEDIMENTS ME �w�� ME 1I Is MOMEITIOMORCHREST THE ROSE STMIMENT ARMOR MOSTLY RETIREMENT S,,1 NTH, ITTIOLT OHMME TO WITMOT SEES SIR HEAR WORMI SISTER, MR THE M, M, 'IT AUTHURSE GARGES TO CONFRACH MOM OR TIME USHER to NNhear Rio' U � w 0 G�T9 pMs RTU Roof Plan SHEETNtlMBER- Printed Tuesday JWY27, M21 O_ Q i �O O /O co C C O U TIRRE N (D Q N CL r MID U ca E t OL M M U �� z o m LL BUY _ ca O 0 C7OIII U cc� 0 (� m i U }0 L(7 U X 00 0 w �� Go RTU Roof Plan SHEETNtlMBER- Printed Tuesday JWY27, M21 nVCOMcheck Software Version 4.1.5.1 Mechanical Compliance Certificate Project Information Energy Code: 20181ECC Pmbd mile, I.acamn: Wheat Ridge, Colorado almMezma: u Profen Type: Mew ConsWEllon A CmMctian him: Owner/Agw:t NsignuAmbacmr: Additional EKciency Packegels) thelookoffled Mechanical Systems List quantity ay,Mm TyM&Mscrlpdon 1 HVAC System 1 barge zoml. INatlng,t nM-Cx l Furnace. Gra, Capacity =146 kB1uT Pmpved ER:cNnq - N 00% Et. Required EMtlency NFO %EI 080%AFUE Fan SyN m: Unp Med Mechanical Compliance RUWmeM Compliance Statement. The promised mechanical design represented in this document is consistent with the building pians. specixcations, and other calculations submitted with this permit application. The proposed mechanical systems have been designed to meet the 20181ECC requirements in COMcheck Version 4.1.5.1 and to comply with any applicable mandatory requirements listed In the Inspection Checklist. Michael Best, PE 3/31/2021 Name. Tide Signature 0�y'y",E�"N Date Cr 7 ProjectTitle: Report date: 03131121 Oatafilename: 1:W5PROIEQSQ02141.FK.002-L dLabs Extractgn%07CALC5104 Page lof 9 ENERG"Momcheck michRxic ga[Ilon ✓COMcheck Inspection Checklist Energy Code: 2018 IECC Requirements: 100.0% were addressed directly in the COMcheck s Text in the "Commentslassumptions' column is provided by the user in if Mechanical Rough -In Inspection CamylimT COmmemF umowns i .10 Plan Rmierz wmlwr Mechanical "ugh -in Inspecllan 0102.1.6 Thermally MCHimElDees ExaepHen: Rpquir<m¢n[ticeanot apply. IME411a haveurtaR50f sensible heating panels M1ave heating Panels O Oboesbse Nes IPR2]r tions Provlde all InN [PR2]1 Oboes Not :nsulation>=R-3.5. i]No[Oburvable WACducts and plenums in determined and ONotA Applicable Temperature ctions. have sMpoin[ ONO[Applicable Requirement will be mac. 0103.6.1 HVAC fan systems at design OCamplles Requirement will be met. IME6513 condition do net excess allowable I]paes NO handbooks. fan system motor nameplate to or fan ON Observable see me Mechanical systems IM rw value:. Data filename: 1:105 PROIECFSR021R1.FK.002 -Lautl WIT; Extradmn107 CALCSV sy54m War.!ONO Applicable duringFundatinmayneetlm ser timing Foundation Inspection. CA03.6.3 Fans have efficiency grade (FEG)RI- OComplies Requirement will be met IME117P 57. The total eflicienry, of Ne tin at IOpaes NO 4 with integral heating Include the design Mint of operation <- 15% ONM Observable to (D IMIHI of maximum WWI efficiency of the Eh Applicable Requirement will be met 2.1. fan. g system when outdoor air OryOtA Ilcable C1103.12.1 Systems that heat outside the building OComPlies Exception: Rmuirement does not apply. IME7112 envelope are ranlaln heat systems Doses Not ca heating and cooling systems controlledan occupancy sensing ONgt Observable Requirement will he That. P12811 device ortimer switc ONot Applicable a 0403.2.3 HVAC equlpment efficiency vented. DCamighes Seelne MCMankalsysMmlhzbfvah .. IME5512 Doses Not FOR and cooling setpoint >= BOF. C4083,3. HVAC equipment has been Rated W ONO Observable 0108.2.2. Air outlets and zone terminal devices OCamplles RyuiremMt will be met. ONot Applicable z C403.23 Natural or mechanical venhigim is DCamplies Requimmm[ will be met. IME5911 provided in accordance with OPoes Not DNM Observable C408.2.3. Inmmahonal Mechanical Cade ONO Observable Requirement will be me[. DNOt Applicable Chapter 4. Mechanical ventilation has reduce supply ONO[ Applicable 0103.5, Refrigerated display cases, walk in W minimum Per IMC Chapter 400r r ONa[ObServaMe C403J.1 Demand control ventilation provitletl OCampher RNuirement will be Will IME59]1 far spaces >500 112 and >25 O(bes Not ONM Observable IFI2911 d demiW and peophisservedl� ONO observable. condenser;not located ins X servedsysteems with Elision ONO Applicable, o condeng Will, have fanpoweredONO economizer,aide modulating outside ONO Applicable CAOE.2.5. mntmh or dmign almow OComplies Requirement will WE mrd. 1 >3,000 can. C403.5.1 and reirigeration compressor Coal Enclosed packing garage venNation OComplies ExcapUm: Requirement does net apply. IME115P has automatic contaminant detection OPoes Not and capacity to stage or modulate fans to sax or less of design capacity. DNot observable vatil' ProjettTitle: Report date: 0313121 ONot ApplI 1:105 PROjECFAT021GOUSC002-Iain 0403.7.6 HVAC systems serving guestrowns In DCamplim Exception: Rmuirement does not apply. IME34113 Group R buildings with > 50 Doses Not 9ue4rooms: Each guestroom is ONot observable! provided with comrols that ONOAMINable utomatically manage temperature setpoint and ventllatim (Me semens C4a3.].6.] and C403J.6.2). ' 0103.7.4 Exhaust air energy recovery on IOCamplles I Excepdm: Requlrmren[ does not apply. IMES711 systems meeting Table C403.7AI11 !ODDes Not and C403.]4(2). ''ONOObservable ONot Applicable Cull Kitchen exhaust systems comply with OComphers Exception: Requirement does not apply. IME11613 replacement air and coghbon:N ODaes NO supply air limitations, and satisfy hood ONot Observable rating requimmems and maximum No[A Otil Applicable exhaust rare criteria. ProjettTitho galactose: 0313121 Data filename: 1:105 PROIEC7s12021VUSC,002-LOutl Ohs Extrachairl CALCs104 Page 50 9 ENERGyKomcheck mnch.cck Software Version 4.1.! ✓COMcheck Inspection Checklist Energy Code: 2018 IECC Requirements: 100.0% were addressed directly in the COMcheck s Text in the "Commentslassumptions' column is provided by the user in if requirement, the user certifes that a code requirement will be met and IT is being claimed. Where compliance is itemized in a separate table, a ref section • Plan Rmierz wmlwr Mechanical "ugh -in Inspecllan Gaseous? .ID OpNot ODI Re .m C103.i Plans, cations. Requlremenl ODTI Nes IPR2]r tions Provlde all InN [PR2]1 Oboes Not with which iance canceaEon withrminecompliancecanbe ONot Observable WACducts and plenums in determined and ONotA Applicable Temperature ctions. have sMpoin[ Equipment andtw yuipmept antl Requirement will be mac. docums document where exceptions IO the Nes ONO Not Mandard areclaimed. Wild calculations per acceptable construC403.1ctetl inaccordancewith engineering 4antlards and handbooks. Additional Comments/ umpHons: 1 IHigh Impact mer 11 12 1 Medium Impact(Tier 2) ProjettTitle: Data filename: 1:105 PROIECFSR021R1.FK.002 -Lautl WIT; Extradmn107 CALCSV ENER[myomcheck meth.cck Project Title: Report date: 0313121 DaWfilename: 1:105PR0]EMR 021121.FSC.002-Wudlabs Extraction\O7CALC " Page 7of 9 ENERGykemtheck n .cck I 3 I 4 1 High Impact mer 11 12 IMedium Impact mer 2) 3 Low Impact mer 3) Project Title: Report date: 0313121 Datifilename: 1:105PR0]EMR 021121.FSC.002-Wudlabs EAmctlon\O7CALC504 Page 8of 9 ENERGY amtheck mrom ck MECHANICAL COMPLIANCE CERTIFICATE 10 Anther Architects, PLLC Architecture + Engineering 3727 Candia Drive Punta Gorda FL 33950 800-243-0528 734-709-7297 gburgh:@gmail.com BURGH ARC 004061 THE ISTENT OF THE �� DOCEMENTIS IS TO ECUME ME THEM MESTEMMY FOR THE FROPER EXI ME CWTITIMS, Me TIE AMR 01 me COMMORM THE MIT WASSISMSEY I FROM THEM Ad III WERSEETY ME ME TME WORMI M,M, W THE mou Mas 'IT � wumic TO CORRECT MUM OR TIME UNUESS [alled fication/dehumidtlon mi hudiMca ONot Applicable O_ system. C403.4.1.1. Thermostatic controls haves 5'F R :a Mechanical "ugh -in Inspecllan Gaseous? CommaMs/AFaumptbns OpNot ODI Re .m OND[ Observable Qr 0103.11.1 WACducts and plenums in Ryuirem¢n[will be mel. OUdes; Temperature ctions. have sMpoin[ OCoes Requirement will be mac. ccortlancewaccordncewith1 1 and Nes ONO Not Not OpOM Not C403.11.2 construC403.1ctetl inaccordancewith Oryo[Oburvable IME601z may occur C903.2.9. Each zone "uipp d with setback OComplies duringFundatinmayneetlm ser timing Foundation Inspection. ONOA Applicable PP controls using au[amaxc time clock or ODoes Not O C403.4.1. Heating for vestibules and air curtains OCompl'ues Exception: Requirement dos not apply. ONO01aervable 4 with integral heating Include O[Mes Not ONot Applicable to (D IMIHI automatic controls that shut off the ONo[Oburvable Requirement will be met 2.1. (heat)and 85-F (c ): 7dey clack. 2- g system when outdoor air OryOtA Ilcable C403.2.4. hour occupant control. 10 -hour OND[Observable temperatures > 45F. Vestibule M backup ONO Applicable ca heating and cooling systems Commissioning plan developed by OComplies Requirement will he That. P12811 controlled by a thermostat m the ODOW Not a approved agency. vestibule with heating setpoint a- ONot Applicable FOR and cooling setpoint >= BOF. C4083,3. HVAC equipment has been Rated W O(domplies 0108.2.2. Air outlets and zone terminal devices OCamplles RyuiremMt will be met. ODOW Not z 1 have means for air balancing. DOoes NO LLo IME5315 ONO Applicable DNM Observable C408.2.3. HVAC canal systems have been OComplies Requirement will be me[. DNOt Applicable tested to ensure proper operation. Oboes Not 0103.5, Refrigerated display cases, walk in OCamighes Exception: Re uirementtices net apply. ONa[ObServaMe 0103.5.1, coolers or walk-in trrertrs served by DOaes NO cc 4-1 C408.2A C403.5.2 rennoter compre mantl remote ONM Observable IFI2911 completed and certifed by rminered IME12313 condenser;not located ins X design professional or approved ONO01 ervable o condeng Will, have fanpoweredONO Applicable ONO Applicable CAOE.2.5. condensers mac comply with Sections OComplies Requirement will WE mrd. 1 submitted m'[hin 90 days of system C403.5.1 and reirigeration compressor pinna acceptance. ONot Observade systems that comply with Ca03.53.. Additional CommentstA umpUons: 1 High Impact mer l) 2 1 Medium Impact(Tier 2) 3 Low Impact (Tier 3) ProjettTitle: Report date: 0313121 Data filename: 1:105 PROjECFAT021GOUSC002-Iain Ohs Extradmn107 CALCs104 Page 60f 9 ENER[myomcheck meth.cck Project Title: Report date: 0313121 DaWfilename: 1:105PR0]EMR 021121.FSC.002-Wudlabs Extraction\O7CALC " Page 7of 9 ENERGykemtheck n .cck I 3 I 4 1 High Impact mer 11 12 IMedium Impact mer 2) 3 Low Impact mer 3) Project Title: Report date: 0313121 Datifilename: 1:105PR0]EMR 021121.FSC.002-Wudlabs EAmctlon\O7CALC504 Page 8of 9 ENERGY amtheck mrom ck MECHANICAL COMPLIANCE CERTIFICATE 10 Anther Architects, PLLC Architecture + Engineering 3727 Candia Drive Punta Gorda FL 33950 800-243-0528 734-709-7297 gburgh:@gmail.com BURGH ARC 004061 THE ISTENT OF THE �� DOCEMENTIS IS TO ECUME ME THEM MESTEMMY FOR THE FROPER EXI ME CWTITIMS, Me TIE AMR 01 me COMMORM THE MIT WASSISMSEY I FROM THEM Ad III WERSEETY ME ME TME WORMI M,M, W THE mou Mas 'IT � wumic TO CORRECT MUM OR TIME UNUESS [alled fication/dehumidtlon mi hudiMca ONot Applicable O_ system. C403.4.1.1. Thermostatic controls haves 5'F OCo Requiremen[wlll be me. 2 OeadOand. OpNot ODI IFI3813 OND[ Observable Qr ONot Applicable 01033.9. Temperature ctions. have sMpoin[ OCoes Requirement will be mac. 1.3 overlap res[dRlonz. Not OpOM Not W120P OND[Observable ONm Applicable C903.2.9. Each zone "uipp d with setback OComplies Requirement will be mI 2 controls using au[amaxc time clock or ODoes Not O P139P programmable control system. ONO01aervable U TEREER ONot Applicable to (D C9033A. Automatic Controls: 5elback W 55-F OComplies Requirement will be met 2.1. (heat)and 85-F (c ): 7dey clack. 2- ODoes NO CL C403.2.4. hour occupant control. 10 -hour OND[Observable MID 2.2 P14013 backup ONO Applicable ca C406.24 Commissioning plan developed by OComplies Requirement will he That. P12811 registered design prohssimal or ODOW Not a approved agency. ONOObservable ONot Applicable C4083,3. HVAC equipment has been Rated W O(domplies Requirement will be met 1 ensure proper operation. ODOW Not z P13111 ONO01aservable LLo ONO Applicable co C408.2.3. HVAC canal systems have been OComplies Requirement will be me[. 2 tested to ensure proper operation. Oboes Not P11011 Wlibration and adjustment Of conj ONa[ObServaMe U m� ONot Applicable cc 4-1 C408.2A Preliminary commissioning report OComplies Requirement will be met. IFI2911 completed and certifed by rminered ODoes Not RM U X design professional or approved ONO01 ervable o ill agency. ONO Applicable CAOE.2.5. Furnished HVAC as-bi drawings OComplies Requirement will WE mrd. 1 submitted m'[hin 90 days of system ODoes Not pinna acceptance. ONot Observade ONat Applicable Project Title: Report date: 0313121 DaWfilename: 1:105PR0]EMR 021121.FSC.002-Wudlabs Extraction\O7CALC " Page 7of 9 ENERGykemtheck n .cck I 3 I 4 1 High Impact mer 11 12 IMedium Impact mer 2) 3 Low Impact mer 3) Project Title: Report date: 0313121 Datifilename: 1:105PR0]EMR 021121.FSC.002-Wudlabs EAmctlon\O7CALC504 Page 8of 9 ENERGY amtheck mrom ck MECHANICAL COMPLIANCE CERTIFICATE 10 Anther Architects, PLLC Architecture + Engineering 3727 Candia Drive Punta Gorda FL 33950 800-243-0528 734-709-7297 gburgh:@gmail.com BURGH ARC 004061 THE ISTENT OF THE �� DOCEMENTIS IS TO ECUME ME THEM MESTEMMY FOR THE FROPER EXI ME CWTITIMS, Me TIE AMR 01 me COMMORM THE MIT WASSISMSEY I FROM THEM Ad III WERSEETY ME ME TME WORMI M,M, W THE mou Mas 'IT � wumic TO CORRECT MUM OR TIME UNUESS COMcheck Compliance SHEEFNtlMBER- PWted: Taeddly, July 27, sera_ O_ •tea Qr Y }I O to C O U TEREER to (D CL TEEW MID U ca E 0L i a M ^`LM O U C:) z LLo O co -0UY L_ O N O CD 0) U m� III cc 4-1 (� i U }E ui c�a RM U X o ill 00�> Y > a COMcheck Compliance SHEEFNtlMBER- PWted: Taeddly, July 27, sera_ F E C Fy C C 0 0 FBI 8 7 6 5 4 GENERAL 22 ITEM NO. THE EXTRACTION BOOTH IS CONSTRUCTED WITH SHEET METAL PANELS THAT DO NOT I HAVE A FIRE RATING. THE SHEET METAL PANEL CONSTRUCTION MEETS NFPA 33.5.3.2 REQUIREMENTS. 2 THE EXTRACTION BOOTH SHALL BE INSTALLED A MINIMUM DISTANCE OF 3 FEET FROM ALL 3 OPERATIONS. THE EXTRACTION BOOTH CAN BE INSTALLED WITHIN 3 FEET OF AN OPERATION IF IT IS SEPERATED BY A PARTITION, WALL, OR FLOOR/CEILING ASSEMBLY WITH A MINIMUM FIRE RESISTANCE RATING OF I -HR AS DEFINED IN NFPA 33.5.5. MULTIPLE 4 CONNECTED BOOTHS SHALL NOT BE CONSIDERED OTHER OPERATIONS. 5 VENTILATION 6 THE EXTRACTION BOOTH'S VENTILATION SYSTEM IS DESIGNED TO OPERATE AT A BASE AIR FLOW RATE AND A PURGE AIR FLOW RATE UPON SENSING FLAMMABLE GAS CONCENTRATION EXCEEDING 10% OF THE LOWER EXPLOSIVE LIMIT (LEL). iTHE BASE AIR FLOW RATE MUST OPERATE AT A MINIMUM OF 500 CFM. iGE AIR FLOW RATE MUST OPERATE AT A MINIMUM OF 1500 CFyAIR FLOW RATE MUST OPERATE AT A MINIMUM OF 1500 CFM THE CLASSIC SERIES EXTRACTION BOOTH MODELS ARE EQUIPPED WITH TWO 12' TUBI AXIAL EXHAUST FANS. DUCTING IS REQUIRED FOR THE EXHAUST FAN AND MUST BE VENTED TO THE OUTDOORS. DUCTING MUST MEET NFPA 33 SECTIONS 7.3, 7.4, 7.5, 7. 7.7, AND 7.8 REQUIREMENTS. DUCTING FOR THE MAKE-UP AIR FAN MAY BE USED AS NEEDED. EACH FAN IS OPERATED BY AN INDEPENDENT PROGRAMMABLE VARIABLE FREQUEN DRIVE (VFD). EACH VFD SHOULD BE PROGRAMMED FOR NO LESS THAN 30 Hz AND I MORE THAN 60 Hz FOR ALL OPERATING CONDITIONS. THE EXTRACTION BOOTH IS SHIPPED WITH BOTH VFD'S SET TO 30 Hz FOR THE BASE AIR FLOW RATE AND 60 Hz FOI PURGE AIR FLOW RATE. CONTACT HAL EXTRACTION FOR TECHNICAL SUPPORT REGARDING VFD PROGRAMMING. THE HVAC SYSTEM SHOULD BE DESIGNED AND BALANCED TO CREATE A NET NEGA PRESSURE INSIDE OF THE BOOTH FOR ALL OPERATING CONDITIONS. THE PRESSURE IN OF THE BOOTH SHOULD NOT EXCEED -0.02 N.W.C. RELATIVE TO THE EXTERNAL ENVIRONMENT. HVAC SYSTEMS AND DUCTING SHOULD BE DESIGNED BY A MECHANICAL ENGINEER HAL EXTRACTION OFFERS MULTIPLE FAN CONFIGURATIONS. FOR FAN SIZING INFORMATION AND SPECIFICATIONS, CONTACT HAL EXTRACTION TECHNICAL SUPPI GAS DETECTION SYSTEM DURING BOOTH OPERATION, THE VENTILATION SYSTEM IS RUNNING AT A CONSTANT BASE EXHAUST FLOW RATE. UPON SENSING OF FLAMMABLE GAS CONCENTRATION EXCEEDING 10% OF THE LOWER EXPLOSIVE LIMIT (LEL), FAN SPEED IS INCREASED TO PURGE AIR FLOW RATE AT FULL FAN CAPACITY AND THE LIGHT ALARM IS ACTIVATED UPON SENSING OF FLAMMABLE GAS CONCENTRATION ABOVE 25% OF THE LOWER EXPLOSIVE LIMIT. THE SOUND ALARM IS ACTIVATED. CONTROL PANEL OUTPUTS CAN BE LINKED TO BUILDING HVAC CONTROL SYSTEMS T INCREASE THE BUILDING MAKEUP AIR SUPPLY UPON INCREASED EXHAUST FAN SPEEL CONTROL PANEL OUTPUTS CAN BE CONNECTED TO BUILDING FIRE CONTROL PANEI GIVE TROUBLE SIGNALS OR ALARMS AS DESIRED FOR THE 10% AND 25%LEL CONDITIONS. ELECTRICAL THE CONTROL PANEL MEETS UL SOBA STANDARDS. BOOTH POWER REQUIREMENTS: ONE SINGLE-PHASE 208V 20A CIRCUIT CONTROL PANEL FULL LOAD AMPERAGE IS 15 AMPS AT THE PURGE AIR FLOW RATE. CONTROL PANEL FULL LOAD AMPERAGE IS 8 AMPS AT THE BASE AIR FLOW RATE. CONDUIT NOT SHOWN. ALL CONDUIT AND CONNECTIONS LOCATED INSIDE THE BO MUST BE RATED FOR HAZARDOUS DUTY PER NFPA 500.8(E), 500.8(EI ), 501.10, AND 501.15. FIRE SUPPRESSION SYSTEMS FIRE SUPPRESSION SYSTEMS COMPATIBLE WITH HAL EXTRACTION BOOTHS: 9 L7 3 PART NUMBER Model 215U Panel Assembly Ventilation Assembly, 12D Fan, 0.5hp 1 - Butane Sensor Assembly, Version 2 Control Panel Assembly, Version 2 Sound Alarm Assembly, Version 2 Light Alarm, Amber, 24V Inside Lighting Assembly, Class I Division I Make -Up Air Spacer Assembly 1. AUTOMATIC STAND-ALONE DRY POWDER SYSTEMS INDUSTRIAL 2. AUTOMATIC SPRINKLER SYSTEMS FROM THE BUILDING STORAGE FIRE SUPPRESSION SYSTEMS SHOULD BE INSTALLED ON THE HAL EXTRACTION BOOTH BY A ADDITIONAL 300 LICENSED FIRE SYSTEMS CONTRACTOR. ENGINEERS AND INSTALLERS SHOULD REVIEW THE POUNDS FOLLOWING: 1B- FLAMMABLE LIQUID 1. ALL PENETRATIONS (SPRINKLER HEADS, PULLEYS, CONDUIT, ETC.) ARE TO BE 1,2 115/ SEALED FOR A 1 -HOUR FIRE RATING. 5902 MCINIYRE ST. 2. ANY CONDUIT PENETRATION INTO THE BOOTH MUST BE SEALED UTILIZING AN ISOPROPYL 120 do APPROPRIATE SEALING FITFING AND SEALING COMPOUND. 30d 3. FOLLOW THE APPLICABLE CODES FOR INSTALLING A FIRE SUPPRESSION SYSTEM ALL DIMENSIONS IN INCHES UNLESS OTHERWEE NOTE! y� THIRD ANGLE `W© IN PAINT SPRAY BOOTHS. 4. ALL ELECTRICAL COMPONENTS FOR THE FIRE SUPPRESSION SYSTEM MUST BE PROJECTION INSTALLED 3FT OR MORE FROM THE DOOR, UNLESS RATED FOR A CLASS VDIVISION 2 ENVIRONMENT. "SEEM2966 IDS 5. IN THE EVENT THE EXTRACTION BOOTH'S FIRE SUPPRESSION SYSTEM IS JGLADFELTER E TRIGGERED, THE BUILDING FIRE ALARM SYSTEM SHOULD BE ACTIVATED. 6. FOR BUILDING AUTOMATIC SPRINKLER SYSTEMS: SPRAY HEADS SHOULD BE TRRR` SEAT PLACED IN THE WORK AREA, EXHAUST PLENUM, AND EXHAUST DUCT. BOOTH I X 0r_ VENTILATION SYSTEMS SHOULD REMAIN OPERATIONAL. Exhacrion molh Model 215U 7. FOR DRY POWDER SYSTEMS: THE FIRE SUPPRESSION TRIGGER SHOULD TURN OFF THE BOOTH VENTILATION FANS, AS TO NOT EVACUATE THE FIRE SUPPRESSANT TEEI MEDIUM. SEE ELECTRICAL CIRCUIT DIAGRAM FOR CONNECTION POINT. MCI 2.3 ADDED TRANSMITTER TO SENSOR ASSEMBLY 06/29/2018 JGLADFELTER 22 UPDATED NOTES, ADDED SAFETY LABELS, MODIFIED THE LIGHT ALARM TO 04/25/2018 JGLADFELTER I BE AN ASSEMBLY, ADDED EMERGENCY LIGHT, ADDED FIRE EXTINGUISHER CL 2.1 ROTATED BUTANE SENSOR PARALLEL TO FLOOR 03/20/2018 JGLADFELTER 8 I 7 2 5 InHRL EXTRACTION 3 I 4 IC Dry Chemical, 2.5lbs 6 DESCRIPTION QTY. Extraction Booth, Panel Assembly, Model 215 1 Belt -Driven Tubeaxial Hazardous Location 12" Exhaust Fan, 2 1/2hp Butane Sensor Assembly, Version 2, UL Usted, Optima Plus IR Sensor I Control Box, 40" Panel Mount I F Sound Alarm Assembly, Version 2 1 Light Alarm, Class 1 Division 2 Location, Amber, 24V 1 Inside Light Assembly, Class I Division I Fixture, 2 Lights, 4' Fixture 5 Spacer, Make -Up Air Ventilation Fan 1 Fre Extinguisher, ABC Dry Chemical, 2.5lbs Fre Extinguishing 1 Emergency Light, Class I Division 1 Enclosure, Ceiling Mount 1 APPLICABLE BUILDING AND FIRE CODES MUST BE FOLLOWED FOR MAXIMIUM ALLOWABLE QUANTITIES (MAQ) OF SOLVENT USED WITHIN THE HAL EXTRACTION BOOTH SYSTEM. NOTE: NFPA 58 LIQUIFIED PETROLEUM GAS CODE TABLE 8.3.1(b) MAXIMUM ALLOWABLE STORAGE QUANTITIES OF LP -GAS IN INDUSTRIAL STORAGE OCCUPANCIES - EXCERPTS LP -GAS MAXIMUM ALLOWABLE QUANTITIES (INCLUDES N -BUTANE. ISO -BUTANE, PROPANE) OCCUPANCY SOLVENT INDUSTRIAL MAXIMUM ALLUWAbLt ULANTITYMA 300 POUNDS STORAGE 30 MAQ WITH 3DO FEET SEPARATION ADDITIONAL 300 ETHANOL, POUNDS NOTE: NFPA 30 TABLE 9.6.1 MAXIMUM ALLOWABLE QUANTITY OF FLAMMABLE AND COMBUSTIBLE LIQUIDS PER CONTROL AREA - EXCERPTS MAXIMUM ALLOWABLE QUANTITY - GALLONS CLASS/DESCRIPTION SOLVENT QUANTITY NOTES lA-FLAMMABLE LIQUID PENTANE 30 1,2 (150 de ETHANOL, IA - FLAMMABLE LIQUID PENTANE 1B- FLAMMABLE LIQUID ISOPROPYL 120 1,2 115/ ALCOHOL 5902 MCINIYRE ST. V I. Quantities are permitted to be increased 100 percent where stored in approved flammable liquids storage cabinets or in safety cans in accordance with the fire code. Where Note 2 also applies, the increase far both notes is permitted to be applied accumulatively. 2. Quantities are permitted to be Increased 100 percent in buildings equipped throughout with an automatic mnnkler system installed In accordance with NFPA 13. Standard for Installation of Sprinkler Systems. Where Note 1 also applies, the increase for both notes is permitted to be applied accumulatively. NOTE: 2016 CALIFORNIA FIRE CODE, TABLE 5003.1.1 (1) MAXIMUM ALLOWABLE QUANTITY OF HAZARDOUS MATERIALS PER CONTROL AREA- EXCERPTS AAAYIAAIIM At I nWARIEnIIAMT -rAl I nNC IPnIINDCI CLASS/DESCRIPTION SOLVENT STORAGE USE -CLOSED SYSTEMS USE -OPEN SYSTEMS 1 - FLAMMABLE GAS, GASEOUS LIQUIFIED BUTANE, PROPANE (150 d'AJ (150 de NOT APPLICABLE IA - FLAMMABLE LIQUID PENTANE 30 d'° 30d 10° HAL EXTRACTION TECHNOLOGY LTD. 115/ 5902 MCINIYRE ST. V 1B- FLAMMABLE LIQUID ISOPROPYL 120 do 120a 30d ALCOHOL ALL DIMENSIONS IN INCHES UNLESS OTHERWEE NOTE! y� THIRD ANGLE `W© d. Maximum allowable quantities shall be increased 1 W percent in buildings equipped throughout with an approved automatic spnnHer system in accordance with Section 903.3.1.1. Where Note a also applies, the increase for both notes shall be applied occumulotively. e. Maximum allowable quantifies shall be increased IED percent when stored in approved storage cabinets, day boxes, gas cabinets, exhausted enclosures, or listed safety cans. Listed safety cans shall be in accordance with Section 5003.9.10. Where Note d also applies, the increase for both notes shall be applied accumulatively. PERIOF HAL EXTRACTION TECHNOLOGY LTD. OMERWISESPECIFI® -Extraction Booth, Model 215, Make- 'ODUCTONINPAWORASAWHOLEWIiHOUT X-'.06 U Air Unit, Class Divisionl NRNTEN PERMISSION OF HAL EXTRACTION TECHNOLOGY LTD. R PROHIPATPn yX=.,01 ( plosion Proof), Paten} Pending .iox-:.Eos .Xxx00=2.0005 HAL EXTRACTION TECHNOLOGY LTD. 115/ 5902 MCINIYRE ST. V Q GOLDEN. CO aSNU ANGLES -112' PHONE p1a)SEWL,CM ALL DIMENSIONS IN INCHES UNLESS OTHERWEE NOTE! y� THIRD ANGLE `W© N 1;SD O PROJECTION ��12/20/2017 "SEEM2966 IDS X2.3 1 JGLADFELTER E of OOTH. 60115 TRRR` SEAT JGLADFELTER 12/20/2017 0r_ 2 FILENAME: 6077 r Exhacrion molh Model 215U BOOTH SAFETY FACTORS 6 6 E n C 0 A io Anther Architects, PLLC Architecture + Engineering 3727 Candia Drive Punta Gorda FL 33950 800-243-0528 734-709-7297 gburgh@gmail.com THE I OR THE COMINECT SOCHI IS TO I AIL I WORMERS TOM THE PRISON EXECUTON AND OWKTIT� OF IN OEM IT THE CONTRACTOM THE CONTACT MITI ME �w�� ME MET Is MORRIS IT ONE SHYL MAS SHORT ASIF MONTHS SHALL TO THE ONTO STOWEENT MIT � ETWORROT ENORMITY ITEM ME IME MOROI M,,M OR THE MEET ONE 'IT ATMEME CHNIGIES TO CONTRAST TOM OR TME UNLITS HAL Booth Overview _O -FIF Q TIRE tF O co E O U TRRR` US 0r_ N Cl. TEEI MCI U E I CL YHRRE M _ (D M O m En � z Q m ��U LL C: BUY � OI.CD 0L CA U m MCI tY cc (� i U 1--r L(7 N U X C)� O 0 w t�: 13 HAL Booth Overview �J I 8 7 F NOTE: FLOOR ANCHOR ASSEMBLY SHOWN A NC NC B C 2 C D NOTE: MAKE-UP AIR INLET. AIR FLOW MUST BE DIRECTED INTO THE BOOTH C 2 C B NOTE: MAKE-UP AIR INLET. AIR FLOW MUST BE DIRECTED INTO THE BOOTH L D SCALE I :20 7 A 2 D L D SCALE I :20 7 DTE: ALL ELECTRICAL FIXTURES, LINES, AND EQUIPMENT WITHIN CLASS I VISION 1 OR 2 SPACE MUST BE RATED HAZARDOUS LOCATIONS, CLUDING CUSTOMER -SUPPLIED EXTRACTION EQUIPMENT. ALL :NETRATIONS THROUGH THE WALLS FOR WIRING SHALL BE SEALED IN �CORDANCE WITH THE BOUNDARY SEAL REQUIREMENTS IN THE NEC. DEFINED BY NFPA 33.6.5.4 NOTE: EXHAUST OUTLET. AIR FLOW MUST BE DIRECTE OUT OF THE BOOTH B A O 2 � 1 DTE: ALL ELECTRICAL FIXTURES, LINES, AND EQUIPMENT WITHIN CLASS I VISION 1 OR 2 SPACE MUST BE RATED HAZARDOUS LOCATIONS, CLUDING CUSTOMER -SUPPLIED EXTRACTION EQUIPMENT. ALL :NETRATIONS THROUGH THE WALLS FOR WIRING SHALL BE SEALED IN �CORDANCE WITH THE BOUNDARY SEAL REQUIREMENTS IN THE NEC. DEFINED BY NFPA 33.6.5.4 NOTE: EXHAUST OUTLET. AIR FLOW MUST BE DIRECTE OUT OF THE BOOTH B A 1 O-111,011 IRH7mIB®PIQp i ❑ o ® 0 2.2 � 10 m I I AIR 0 w Lp ID � 30.0 A NOTE: MAKEUP AIR VENT SECTION B -B PANELS. SCALE 1:20 SOL PROPE�RTTYY°OFF CONTAINED EXTRACTINON THIS ECHNOLOGY THE TOLERANCES Exhacfion Booth, Model 215, Make- MYREPRODUCTIONINPARIORASAWHOLEWITHOUT x-� If Air Unit, Class Division1 THE WRITTEN PERMISSION OF HAL EXTRACTION U% H cHNOLOGYUNTI ST. PROHIBITED. X --.Dl plosion Proof) Patent Pending A .iYX-..Eos .XXXX,..ppp5 HAL EXTRACTION TECHNOLOGY LTD. 115/ OLDEN.YNIYREST. GOLD: (720) " ANGLES a1/T PHONF.II'NII�lxY16 ALL MMENSIONS IN INCHES UNUM OTHERWISE NOTE! THIRD ARGUE Ail© 1;.5D PROJECIONW EXTRACTION JGLADFELTER ��12/20/2017 29661bs RTH X2.3 2 of 5 ERRrr.I JGLADFELTER 812/20/2017 60115 4 3 2 FILENAME. -607 ExhaCtion 600lh MWO1215U BOOTH ELEVATIONS 7 4 6 Anther Architects, PLLC Architecture + Engineering 3727 Candia Drive Punta Gorda FL 33950 800-243-0528 734-709-7297 9burgh@gmail.com ARC 00406898 c�NSffO ARGNx� TENT OF THE MNTRAM DOCUMENTS 19 TO ECWDE MI NECESTEM, ME THE IROPIR EXECUTE' "I TI OF THE WERE IT THE! CONTMOTAI THE ACT DETERRENTS ME �w�� WE MET Is AEMMOY INTERRED FROM THEM M TEAM ATERMARY (TEXT THAI AMTO "THAT OFARME TO WNTWT RME QHMGEM TO CONTRAGI� TOM OR TME UNLESS WASEMIRTE l o W hear Rio' U w c 0 G�n9 EMs 0 Q �l co E O U r rn Q C CL TEEEE MID U E 1 OL > M M U �� z LL o m BUY L 0 (D 0) mo cc MIMI U N '0 (� i U 1--0 LO N U °) O X 0� lL L Booth Plan & Elevations M7 A FI E B D c c B A D 8 1 6 5 D� C SECTION D -D SCALE 1 :26 IF 1113 0000 l° fire ollee 9941 c BGydn9 DMso i UTILITY PENETRATION PANEL MAY BE INSTALLED ATJ ANY 49"PANEL LOCATION ON THE FRONT AND BACK OF THE BOOTH. DO NOT INSTALL THE UTILITY PENETRATION PANEL ON THE ENDS OF THE BOOTH SUCH THAT R INTERFERES WITH THE VENTILATION PLENUMS. UTILITY PENETRATION PLATE INCLUDES: • PRE -DRILLED HOLES FOR BULKHEAD FITTINGS AND CABLE STRAIN RELIEFS. • HOLE SEALS PROVIDED FOR ALL HOLES. ALL HOLE SEALS IN THE UTILITY PENETRATION PANEL SHALL BE SEALED IN ACCORDANCE WITH THE BOUNDARY SEAL REQUIREMENTS IN THE NEC. 7 0311 DETAIL E SCALE 1 :2 El NOTE: MOUNT THE TOP BRACKETS WITH 3/8-16 FLANGE BOLTS IN THE PRE -PUNCHED SLOT. DRILL A 13/32' CLEARANCE HOLE THROUGH BOOTH PANELS FOR TH 011/ II/ BOTTOMEACKEPS MOUNTING HARDW O NOTE: ITEMS 4 8.5 MAY BE MOVED TO ANY 40" PANELOUTSIDE OF THE CLASS I DIV 2 ZONE C 18 � 5 4 3 NOTE: ITEM 4 TO BE CENTERED BETWEEN 49"BOOTH PANEL WITH THE DISPLAYED MOUNTING BRACKETS IN DETAIL E. AIR 0 2 1 1 RG Goo o00 AIR DETAIL F SCALE 1 :5 AIR FLOW SCHEMATIC 5X n7 SECTION c -c SCALE 1 :26 AIR FLOW I NOTE: EXHAUST AIRS VENT PANELS. ie Anther Architects, PLLC Architecture + Engineering 3727 Candia Drive Punta Gorda FL 33950 800-243-0528 734-709-7297 F gburgh@gmail.com 3TUARTGRI BURGH ARC 004061 E THE I OF THE CNITROTT SOCHI IS TO I AU HIM NERMEMY FOR THE IFFESSM 0(1 AND OWKTIT� OF THE SETS N THE MOMENTUM THE OWWT DESTUMENTS ME �w�� AND 1I Is THE ROM SOMMENT ARMS MOSTLY REWA� SI ANSI "THEN O,W3E TO ONITMOT PITHINESS SIMON H TOM OR TEAM MINOR STATE ME µ. FO D I I I I I l° 4 3 NOTE: ITEM 4 TO BE CENTERED BETWEEN 49"BOOTH PANEL WITH THE DISPLAYED MOUNTING BRACKETS IN DETAIL E. AIR 0 2 1 1 RG Goo o00 AIR DETAIL F SCALE 1 :5 AIR FLOW SCHEMATIC 5X n7 SECTION c -c SCALE 1 :26 AIR FLOW I NOTE: EXHAUST AIRS VENT PANELS. ie Anther Architects, PLLC Architecture + Engineering 3727 Candia Drive Punta Gorda FL 33950 800-243-0528 734-709-7297 F gburgh@gmail.com 3TUARTGRI BURGH ARC 004061 E THE I OF THE CNITROTT SOCHI IS TO I AU HIM NERMEMY FOR THE IFFESSM 0(1 AND OWKTIT� OF THE SETS N THE MOMENTUM THE OWWT DESTUMENTS ME �w�� AND 1I Is THE ROM SOMMENT ARMS MOSTLY REWA� SI ANSI "THEN O,W3E TO ONITMOT PITHINESS SIMON H TOM OR TEAM MINOR STATE ME µ. FO D SOLE PROPER" OF tui EXTRACTION TEalHoiocr irli. OTHENTSEESPECIFiEo Ex}raction Boo}h, Mode1215, Make- Se ANY REPRODUCIION IN PAU OR AS A WHOLE WITHOUT x- iJ Air Unit, Class l Division1 THE WRITTEN PatM1610N OF HAL EXTRACTION US O HRL LEXTRA TEWTIO RE ISPROHIBITED.8x plosion Proof) Patent Pending A N . , .xxx-..ms O V �% U .xxxx=..mo5 HAL EXTRACTION NDIRE ST. LID. 115/ ni SRI2MCINIYREST. V GOLDEN.0080403 ANGLE a1R' PHONE: pMIm6-x716 r ' (a W i_ NL gMENSIONS IN INCHES UNLESS OTHERWISE NOTED MRD AlK'LE Ail© O 1:50 IIO� > }FO PROJECTION V JGLADFELTER 12/20 X233 NEXTRACTION o� O) IS,.e R12/20/2017 JGLADFELTER F 60115 X00 .o 3 2 FILE SAME: 6011 - EXI/OChon SI MoIdel 215U W � � D - BOOTH ELEVATIONS Booth Air Flow SHOWING BOOTH MAKE-UP AIR FITMENTS SHEET NUMBER Printed Tuesday, Ju•27, M21 Wheat Rio' l° c BGydn9 DMso c 0 4-0Q O m E 0 U TeRe N B Q d a C Teee MID U OL T a >1111% RHIRE M _ M N O m C:) z O Q m ��U LL U SOLE PROPER" OF tui EXTRACTION TEalHoiocr irli. OTHENTSEESPECIFiEo Ex}raction Boo}h, Mode1215, Make- Se ANY REPRODUCIION IN PAU OR AS A WHOLE WITHOUT x- iJ Air Unit, Class l Division1 THE WRITTEN PatM1610N OF HAL EXTRACTION US O HRL LEXTRA TEWTIO RE ISPROHIBITED.8x plosion Proof) Patent Pending A N . , .xxx-..ms O V �% U .xxxx=..mo5 HAL EXTRACTION NDIRE ST. LID. 115/ ni SRI2MCINIYREST. V GOLDEN.0080403 ANGLE a1R' PHONE: pMIm6-x716 r ' (a W i_ NL gMENSIONS IN INCHES UNLESS OTHERWISE NOTED MRD AlK'LE Ail© O 1:50 IIO� > }FO PROJECTION V JGLADFELTER 12/20 X233 NEXTRACTION o� O) IS,.e R12/20/2017 JGLADFELTER F 60115 X00 .o 3 2 FILE SAME: 6011 - EXI/OChon SI MoIdel 215U W � � D - BOOTH ELEVATIONS Booth Air Flow SHOWING BOOTH MAKE-UP AIR FITMENTS SHEET NUMBER Printed Tuesday, Ju•27, M21 I� B C C m I 50 EXTRACTION BOOTH MODEL: 215U INSIDE DIMENSIONS: 9'9"W, 22'1"L, 92'H OUTSIDE DIMENSION: 10'0"50, 237"L, 8'" F MAXIMUM HEIGHT W/FAN: 9'8" NOTE: CONTRACTOR TO VERIFY ALL DIMENSIONS IN FIELD AND REPORT ANY DISCREPANCIES PRIOR TO STARTING WORK. DESIGNED TO SATISFY CRITERIA STATED IN NFPA-60 AND OSHA 1910.106 NOTE: ALL PANELS MUST BE ANCHORED TO THE FLOOR USING 1 /4" FEMALE DROP ANCHORS IN EACH 7/16" SLOT. G 7 C I 011 ITEM NO. PART NO. DESCRIPTION DESCRIPTION 3 50211 Infored Gas Detector Assembly, UL Listed, Class I Division I Hazardous Location 8 7 1 6 2.3 4 F NOTE: OSHA REGULATIONS REQUIRE BELT GUARDS TO BE INSTALLED WHEN THE FAN ASSEMBLY IS LOCATED LESS THAN EIGHT FEET FROM FLOOR LEVEL. INSTALL THE SUPPLIED _ FAN BELT GUARD PER THE MANUFACTURER SPECIFICATIONS IF REQUIRED. HAZARDOUS LOCATION VARIABLE SPEED MOTOR 208-230 THREE PHASE MOTOR SIZES FOR 12" FANS: 1/2 hp 3/4 hp REFERENCE HAL EXTRACTION DRAWING PART NO. 50201, 50214 FOR FAN CURVES AND SPECIFICATIONS NOTE: SYSTEM OPERATION 'EADS SWITCH SETTINGS: -SYSTEM OFF -FAN - LIGHTS CONTROL PANEL CONSTRUCTEI TECHNOLOGY LTD. BY CES INDL MEETING ARTICLE 500-505 OF T4 UL 508A. G 1 I 2 I 3 I 4 V-BELT(X2)� 3 2 1 1 SRT NO. DESCRIPTION I QUANTITY 50201 Belt -Driven Tubeaxial Hazardous Location 12" Exhaust Fan 2 AMOUNTING INSTRUCTIONS: EXHAUST FAN: MOUNT TO TOP OF ITEM 1 WITH 5/16- 18 BOLTS, 5/16-18 NUTS, 5/16" WASHERS, & 5/16" LOCK WASHERS (X61. FAN MUST DIRECT AIR OUT OF THE BOOTH. MAKE-UP AIR FAN: MOUNT TO TOP OF ITEM 8 WITH 5/16-18 BOLTS, 5/16-18 NUTS, 5/16" WASHERS, & 5/16" LOCK WASHERS (X6(. FAN MUST DIRECT AIR INTO THE BOOTH. BELT -DRIVEN TUBEAXIAL UL APPROVED I2'HAZARDOUS LOCATION EXHAUST FAN ITEM NO. PART NO. DESCRIPTION 4 50212 Control Box, 40' Panel Mount F E ie Anther Architects, PLLC Architecture + Engineering 3727 Candia Drive Punta Gorda FL 33950 800-243-0528 734-709-7297 gburgh@gmail.com 3TUARTGRI BURGH ARC 004061 THE WORST OF THE CONTRAST DOCUMENTS IS TO I AU I WORMERS FOR THE PROPER EXECUTION AND COMETTIM OF THE SETS IT THE CENTIMETER THE Owwr DERTMENTS ME ME 1I Is MOMROOMORCHERST Im 11 "1 MORMI SISTER, OR THE SRI MEET 'IT JTHOMZE CHRNGIS TO CONTRAST TOM OR TIME USHER o Wheer RES U w 0 c G�n9 DMS ' THROUGH HOLES IN THE PANEL AND ARE SECURED WITH THE 3/8-16 NUTS AND 3/8" dN WASHERS PROVIDED 0 41 NOTE: SEE SECTION E FOR RIO C MOUNTING INFORMATION TO ITEM I Q CIRR EIII 0 0 m 0 O U r U7 —NOTE: SYSTEM DISCONNECT Q � B � a C 'o U E 1 a RIHRRo M M U En00 z n UII TO Y HE re RANCUNI IOLEB OTHERMESPECINEo mcm "` ac ion Booth, Model 215, Make- v >— THe W"R"iim`iPE.RNSEsION 0. F. HAL'oaencrioe .x=..0 Up Air Unit, Class I Division I HRL ALEXTRTECHNMONnIOGY HNOLO YL n _ (Explosion Patent Pending A 0 I xxxx=.ArosIII cc HALEXIRACIION TECHNOLOGY LID. X25/ }r GOLDEN. r`COPGIXi ANGLES ]Il3' m W PHONE I)ZIISOHJ]d Il IHIRD,WGIE \ U SRIALL OIMENSONS IN INCHES UNI OTHERWISE NOIE-0 THIRPROIICN 1'24 / �I EXTRACT 1 O N JGLADFELTER d"12/20/2017 29661bs ""`"2.3 4 of 5 N W JGLADFELTER 3 2 GAS SENSORS & EXHAUST 49/ 12/20/201760115 X C 'o HLENAME.W1 Hbadlon9xMMaOe1215U 11-I D_ Booth Safety Details 1 M9 6 8 1 7 1 NO. PART NO. DESCRIPTION 5 50213 Sound Alarm, Vibratone 24V F A SOUND ALARM, UL LISTED CONDUIT BOX, 2 GANG.TRADE SIZE CONDUIT KNOCKOUTS e 6 E B D C I L BEM NO. A D 8 50208 L BEM NO. PART NO. DESCRIPTION 8 50208 Spacer, Make -Up Air Ventila}ion Fan 61 5 1 4 ITEM NO. I PART NO. i DESCRIPTION 6 1 50217 1 LED Beacon, Amber, Hazardous Location Class I Division 2 ON 2, MOUNTING INSTRUCTIONS: INSTALL MAKE-UP AIR FAN AT DESIGNATED LOCATION. 8 I 7 p 5 T 4 O Tel; pkh= 3 12 11 ITEM NO. PART NO. I DESCRIPTION 7 50209 1 2048 Class I Division I Hazardous Location Inside -Access Light IF OUS 3HT, E NOTE: CLASS I / DIV I EMERGENC 3/4" NPT THREADS ID IC B THE INFORMATION CONTAINED IN THIS DRAWING IS THE TOLERANCES UNLESS tt¢ SOLE PROPERTY OF HAL EXTRACTION TECHNOLOGY LTD. OTHERWISESPECIPFD Ex}raction Booth, Model 215, Make- MYREPRODUCTIONINPARTORASAWHOLEWITHOUT U Air Unit, ClasslDivisionl THE WRITTEN PERMISSION OF HAL EXTRACTION x".U% HRL OHNOLOGYLIDIRIEST. PROHIBITED. =e of plosion Proof) Patent Pending A irX-..Ixn .ixxx=,.coos HPL EXTRACTION TECHNOLOGY LID. 115/ SRIDEIN.0YREST. GOLDER0)Sn ANGLES aIR' PHONE (I'NIISMJY16 ALL DIMENSIONS IN INCHES UNLESS OTHERWISE NOTED THIRDANGLE L$CI lIl PROJECTION `IMV EXTRACTION JGLADFELTER 12/20/2017 2966 lbs X2.3 5 of 5 rr.e JGLADFELTER 812/20/2017 60115 3 2 FsENI i-Exi0CEN0RT8 Olh ModeIY15U j BOOTH SAFETY EQUIPMENT 1 6 ie Anther Architects, PLLC Architecture + Engineering 3727 Candia Drive Punta Gorda FL 33950 800-243-0528 734-709-7297 gburgh@gmail.com THE WONT OF THE CONTRAM DOCUMENTS 19 TO ECWDE MI HOW NECESSARY ME THE PROPIR EXECUTON AND COMMITTEE, OR THE WMX IT THE 004TRACTOA THE OWRMT 0MUNENTS ME �w�� ME IMT Is REQUIRED � ONE SEWL YEAR BRUNT MIF MUMMY BYALL ME NEREMMLY INTERNE FROM THEM M TERM ATERMARY do Whea/R/6 U w c 0 G�n9 pMs _O MCI i --R O O 20 0 0 U r N C CL r MID J E OL 1 a ate+ M M (D O m RRRRRR U �� z C:0 O 1 �U m O -5 O 0) MCI cc V (5 '0 (� i U i --r LO N U X C) .r. O 0 A 4 o Booth Safety Details 2 M10 ITEM NO. PART NO. DESCRIPTION 2.2 10 50218 Emergency Light NOTE: CLASS I / DIV I EMERGENC 3/4" NPT THREADS ID IC B THE INFORMATION CONTAINED IN THIS DRAWING IS THE TOLERANCES UNLESS tt¢ SOLE PROPERTY OF HAL EXTRACTION TECHNOLOGY LTD. OTHERWISESPECIPFD Ex}raction Booth, Model 215, Make- MYREPRODUCTIONINPARTORASAWHOLEWITHOUT U Air Unit, ClasslDivisionl THE WRITTEN PERMISSION OF HAL EXTRACTION x".U% HRL OHNOLOGYLIDIRIEST. PROHIBITED. =e of plosion Proof) Patent Pending A irX-..Ixn .ixxx=,.coos HPL EXTRACTION TECHNOLOGY LID. 115/ SRIDEIN.0YREST. GOLDER0)Sn ANGLES aIR' PHONE (I'NIISMJY16 ALL DIMENSIONS IN INCHES UNLESS OTHERWISE NOTED THIRDANGLE L$CI lIl PROJECTION `IMV EXTRACTION JGLADFELTER 12/20/2017 2966 lbs X2.3 5 of 5 rr.e JGLADFELTER 812/20/2017 60115 3 2 FsENI i-Exi0CEN0RT8 Olh ModeIY15U j BOOTH SAFETY EQUIPMENT 1 6 ie Anther Architects, PLLC Architecture + Engineering 3727 Candia Drive Punta Gorda FL 33950 800-243-0528 734-709-7297 gburgh@gmail.com THE WONT OF THE CONTRAM DOCUMENTS 19 TO ECWDE MI HOW NECESSARY ME THE PROPIR EXECUTON AND COMMITTEE, OR THE WMX IT THE 004TRACTOA THE OWRMT 0MUNENTS ME �w�� ME IMT Is REQUIRED � ONE SEWL YEAR BRUNT MIF MUMMY BYALL ME NEREMMLY INTERNE FROM THEM M TERM ATERMARY do Whea/R/6 U w c 0 G�n9 pMs _O MCI i --R O O 20 0 0 U r N C CL r MID J E OL 1 a ate+ M M (D O m RRRRRR U �� z C:0 O 1 �U m O -5 O 0) MCI cc V (5 '0 (� i U i --r LO N U X C) .r. O 0 A 4 o Booth Safety Details 2 M10 C 7 1 D VERIFICATION OF EQUIPMENT AT INSTALL IS REQUIRED! Field verifications of equipment installations are required as required by IFC 2018 and NFPA 1, 2018 for all instances that PSI's engineering peer review is used to gain approval from an Authority Having Jurisdiction (AHJI). The design of this equipment has been found suitable for use provided that the equipment is fabricated and assembled using the components listed on the design documentation provided for the engineering peer review. The engineering peer reviews offers conditional approval of the equipment design only. At installation, the equipment must be successfully field verified by PSI to confirm the equipment was supplied and installed in accordance with this report in accordance with (IFC 3904.4) and (NFPA 1: CERTIFICATE OF COMPLIANCE Certificate Number E497776 Report Reference E497776-20180706 Issue Date 2020 -JULY -07 Issued to: HAL Extraction Technology 5902 McIntyre Street Golden CO 80403 This certificate confirms that PLANT OIL EXTRACTION BOOTHS FOR USE IN representative samples of HAZARDOUS LOCATIONS REFER ADDENDUM PAGE FOR MODELS Have been investigated by UL in accordance with the Standard(s) indicated on this Certificate. Standard(s) for Safety: UL1389, Standard for Plant Oil Extraction Equipment for Installation and Use in Ordinary (Unclassified) Locations and Hazardous (Classified) Locations UL/ULC 1389 Plant Oil Extraction Equipment for Installation and Use in Ordinary (Unclassified) Locations and Hazardous (Classified) Locations Additional Information: See the UL Online Certifications Directory at httos,//iQ.ulprospector.wm for additional information. This Cambodia of Compliance does not provide authorization to apply the UL Mark. Only the UL Follow -Up Services Procedure provides authorization to apply the UL Mark. Only those products bearing the UL Mark should be considered as being UL Certified and covered under UL's Follow -Up Services. Look for the UL Certification Mark on me product 8-� :`,MERM.End MTRA I MRS OL w .. ROM.�t--w—RETRI t.mns,May .��r__.U,�•.w..n__ Page 102 Pressure safety reluctant uc November 13, 2018 RE: Engineering Peer Review 201709024 Revision 4 Dear HAL Extraction Customer, The design of HAL Extraction models Classic Series (U), Critical Flow Series (C), Production Series (P), M Series (M), & Hood Series (H) have been evaluated by a Professional Engineer (AZ/CA/CO/FL/HVMA/MD/ME/M I/ NWPA/OH/OR/WA) and found suitable for use, providing: 1. At installation, the equipment is successfully field verified by PSI to confirm the equipment is Installed in accordance with Engineering Peer Review 201709024 Revision 4 (IFC 2018/NFPA/ 2018) The Classic Series (U), Critical Flow Series (C), Production Series (P), M Series (M), & Hood Series (H) have been renewed using the following codes and Standards: • Adzona Fire Code 2016 Edition (Based upon IFC 2012) • California Fire Code 1016 Edition (Based upon IFC 1015) • International Fire Code 2018 Edition • Oregon Fire Code 2014 (Based upon IFC 2012) • Washington Fire Code 1015 Edition IWAC51-54A, Based upon lFC 2015) • NFPA 1 Fire Code 2018 Edition • NFPA 58, Liquefied Petroleum Gas Code, 2017 • NFPA 30, Flammable and Combustible Liquids Code 2015 • NFPA 70 Notional Electric Code 2014 Please direct all technical questions to HAL Extraction. This is not a field verification letter and therefore does not include o serial number or installation address for the equipment. Chris J. Witherell, PE AZ/CA/CO/FL/HI/MA/ME/MI/NV/OH/OR/WA John Andrzejrzak, PE CO/MD/PA/WA THIS IS NOTA FIELD VERIFICATION LETTER 315a aamm Um, unit 155, Castle Roc, W 90103 1031 - IMoapslnspcmrs,mm. www.pslmpecds.mm CERTIFICATE OF COMPLIANCE Certificate Number E497776 Report Reference E497776-20180706 Issue Date 2020 -JULY -07 This is to certify that representative samples of the Product as specified on this certificate were tested according to the current UL requirements. Class I, Division 1, Group D within booth; Class I, Division 2, Group D outside booth around openings for distance of 3 ft in all directions. Classic Senes Model 85U, 120U, 150U, 180U, and 215U Plant oil extraction booths. Production Series Model 170P, 265P, and 355P Plant oil extraction booths. ofiessmill MCI UL LOS REARM I SCROLL I PWI CERTIFICATE OF COMPLIANCE Certificate Number 20180709-E497776 Report Reference E497776-20180706 Issue Date 2018JULY-09 Issued to: HAL Extraction Technology 5902 McIntyre Street Golden CO 80403 This is to certify that PLANT OIL EXTRACTION BOOTHS FOR USE IN representative samples of HAZARDOUS LOCATIONS Class I, Division 1, Group D within booth; Class I, Division 2, Group D outside booth around openings for distance of 3 R in all directions. Classic Series Model 85U, 120U, 150U, 180U, and 215U Plant oil extraction booths. Critical Flow Series Model 85C, 120C, 150C, 180C, and 215C Plant oil extraction booths. Production Series Model 170P, 265P, and 355P. Have been investigated by UL in accordance with the Standard(s) indicated on this Certificate. Standards) for Safety: NFPA 33, SPRAY APPLICATION USING FLAMMABLE OR COMBUSTIBLE MATERIALS UL 2011, FACTORY AUTOMATION EQUIPMENT UL 2755, OUTLINE FOR MODULAR DATA CENTERS Additional Information: See the UL Online Certifications Directory at winw.uLcom/database for additional information Only those products bearing the UL Certification Mark should be considered as being covered by UL's Certification and Follow -Up Service. Look for the UL Certification Mark on the protluct. REARM I Sea OL MMIRMS 41 TRI.MwI IS HER 1. 1 Page l oft 51112021 MONMEyES Arvada Fire Protection District _ Fire Marshal's mice y 7903 Allison Way -Arvada, CO 80005 Main 303-424-3012 - Fax 303-032-7995 wwwaty idafire.com occupam Name: Lend Labs. LLC Oomncbr: Shane Mendenhall, Owner Inlenor Sprinkler Systems, Inc (970)31 Address: 48034e4svan Gordon Inspenaonoate: vnno2l Street Wheat Ridw. CO W033 Job Numbac 210421p02JH Inspectlonrype: Plan ReHew-Ory Cremmal Sispesmon System Job Oascraow New Exdaclbn Boom Inspected By: John Hunney 303424-3012 Johnnussey9a Om.mm Plan Type Ofidnal Paas Fail NIA Plan Review Flood commmtte is] II [1 Tom Pimect -The 1pmwM9 mmmeas me we mlM pans and ,, as mmmeae sten be Sp c addres HN wwrp a aro AFRI commsms 1. A Mswpiw muwitq mndawl teat a iris symm end arao appm.a yWl de madwdHd IS] II [I 1002 Comments -Thempaas hsmoesn renieweem Me zole rmemsdanslam code tyre mrem red cwnlrenN mndemawaddpled -mese mmmenn, apgdved octans arMpwmM must as MI m rereive any in asap mWs. oewadon m me appmmn paw may mgpm m-wdrrMdp for awes andappmwmwdandoct rmrdaMapamnn e=on wr l Nomspar9dnswd omur rnamuY Fim paOictappmredpaw,annmeMa aMpemuYcard availabb on-vYe. -r scrwdwa nWcEw,sp nmp.anEST as.wbue Eyes candmlorPemd Patty at di(o/Mwx.mannesow mmTA_4gex wp AY aff m ft Sal de mase b scat an in5yec M Me date and Mme rep, Ve , Imseemome wul be Stll ed been an Mspeda-ama , and MET de:=deeded wimm 2a48dowsaMe ipe manex Jnap ns may reveal mrredia sue 7 To brrg as ,cork Inco mulyeVarrce went aprstarbe comm aMsarMerdx M 11 II t[m constants dAppmeai Status: Approved With Conditions Dams mbmified to After are reviewed Purmmplia ce per the Bre code as adopted and/or amended a mil any applicable State Of Colorado Requirements. The mbmMm1 plans are not reviewed to specific individual nlpanmm.nwsxp omwldhow, M,WJ1pww,PSnl ow ,rz an , Mearaw project specifications. This report u intended to provide the submitter with the sates of plan approval, and any mm mN that may require fuller informaaouverification or action for approval of plans. An plans may be subject to field inspection and/or testing for final approval prior to sign o0 on a Certificate Of thmpancy or Cerfificale of Inspection. The approval of plane constitutes a permit to commence workavhere required "a fire code, and Is subject to the conditions as may be noted in the comment section in the attached plan review report- Response to this review report as necessary along with the pi mil fee payment will be required prim to my field nsPection> nlroimrv.nmtx,re.m..na[umue_Aw,r�nagnrwnnlzv vx COMPLIANCE CERTIFICATES 10 Anther Architects, PLLC Architecture + Engineering 3727 Candia Drive Punta Gorda FL 33950 800-243-0528 734-709-7297 9burgh@gmail.com I NESMEMY FOR THE PROPER EXECUTION AND OWKTIT� OF THE OEM TV To CONTRI THE comMer DKESTUMENTS ME �w�� ME MAT Is REWA� THE "I SHERMENT ANSWER MOSTLY M, M Has WORMI TERM, OR THE vMT EMS 'IT to Wheal R/n U w c 0 offing DM5 Compliance Certificates M11 3 4 5 6 O Q }r O O C0 E O U TIRRE N (D Q CL Tans MID U E cc I OL Rieea M M C:) z Q m ��U LL I✓ BUY L _ � O O C7 N l) t U cc (� m i U �a LLQ N U X C 0 0 w ct�� Compliance Certificates M11 3 4 5 6 I� C C FBI Arvada Fire Protection District _ Fire Mamhal's OMI 7901 Allison Way- Arvada, 0000005 Mein 1 W NIz{2D1 z - Fax 101,432-7996 www.smadMm.e m m oMM Naw: Law vee. LLC Coma , Shane M, enhW, ommr lwz $Klnkbrsyebaw PC (Westphal man..: wosaasvm mann IMpm[tlm pct: wiia z, sow vmYMRklp sola Job xnmMr: z,azlMm.IH tmlwmwrlapm: PA, aYeamnl allhnmum ayebm oea[ Joe dPm: na«Fnh.Lmp a[an Iropwbd By: 'I`hwnMzaro 1 ,p Itlln Xaaae maMr .mm Plan Tye pyYw Pass Fall Pan Plan R9vgw Fine I mono b IN [I 11 FeelEFrgm TO�rcea nTroaroarrrome Wma rvhmmw avwnmxwanauos Comments a. p Mral inaptt W n In[Wdnp IvrlaNwlal ba of Mw ¢yslem ens pFPo apgpvsl NeM I w 14 11 11 ,aBz mrenl more:,plansneweeanRwwearomezpaemmmMmxrx. ememen]wmwa mmmmm nmaamaaaaapw iax wmmeM¢, eo meeplen ane PorTnmualM muibbrererve myGn Dwhi,liwpen,m� w nnl eepm smhe mmeyrmmn rNO mawlrmnww tleppmmvw,nmder Mrenyluxner�,peNaa ampe,mlwnlaveladeomMe. pttur ul Fire Di¢rrlcf apprpvatl c[mmen5 Tpeaaepkmmmlipm pleMA Whon 1p lM Mabtt Eyeabe mail mr Pennn Pd AM Mp/Mw ser theam mmNA-meata¢p pNehlws *fitbe ~baMMWan m*M Mlmly abM(orwhe ee. M1sp[24 WoI aMeeuke based an NgMwaaNaany aMwiNp aanadrW w.nrm Yd J8 Murso/Ins mlenMerpuM. MWs my Meer comcenna nensvry an MORE as "I IntoJieme WM1 mdiaedemeeamtl9enmrtla. Iq ❑ 11 ,W1 Cnwippm mlppwel Status: Approved With Conditions Flma..b Hed to.1FP0 an reviewed Ion mmplianm pn,he firecode IN AWRI and/or Amended ad any applicable Sure Of CoAmm, Requirements. IRS, eeobmined P6m are wt nvimiit, pec5, individual agcllrvcawwpmn E[ W wptw4rXwmYq I ME ce reaPna-eMm won. ton. PV>s ® MCI FUSIBLE LINK DETECTOR Pcr.re.aec CHAPTER 111 SYSTEM DESIGN Wna,al Daslgnim ft Pmp rType a system RoCHEM medmm earn NIMMm .s"nue It 11 the Oso daxon. to III tell 1. mw"lwWI1I Ad am Aetna gl�Ill" I'I If MM caurear Coal .11 h Me Am fallen. d Orldr, proper ADWPl.M 7" In as most Mo., Me PuamAmbel U�tAm COWAMPA.M. Its the b[w Will's do A Peru cal All Sir that godem A, My � ... 4 It �t�.r, 4 and Inpredict r B e contain arm mer,a�argn� MI the Intal aeawd are.. OI IW"Ino An the rylI'd elk ad nn MY ladiF IN ht d OF ba a mRCH-lm -n m n attend FacMN Coamlvn Tralmn„Clev and Monrre oWdI WIn edln Mh,N Fall SONY Carl to Mem FIAT mEM III Alda Pum CRY nd unc dp an naNM Sxry rV[m Birt Mpmam^n Saxon,, T, Centel b THAI mr,m m CH ales MI a p=rises time dere✓. CEowirN the Packets Agent 1, 1. Fusible Link lnalallagon withoutns. doCher , 161ser d.,mr.r p,wmw, gedeunw. TOMWMemtn ASSOM Meet Nabut sewn NASA In, me anyone m Hill Sound in the Sahara .. AM Corona IN It Few awroll Nor Ther link IS Sun. npmtMtl� TO Want used In Me ONma no IS The Total Telel FboClrq in, pm me Milan .1. a. Cylinders May,' a LIENIA) A FORD CHEM led, Pley Rule M by the MIMP PMOW mp Is to term me, Thl",111fact PP" 'I'll Ilb,rgi� ndpAI JACK, ad mil 70ABC mIIW�� I'S bel Mail For IMF The bell Is wJorge. PAM arm m:m[lp gasoline nc tibanP ites -Entepha hl.notd,monlSo AMIMIS Far tons•.bae Pinn' wGa Note editor The Malay At' 11 the .111 'old wereakno 11 mragrea PYYWiHEMCul Whill PASS SPIN �lh Fire E,pp,m,, MVFWA Work MeWhinfurni _ Nelson SCis hill to game, Clea o bvarea. Plrl leen 1pm e FIJIAN. Inatsell link NUFFI Mlt nqn i�w b,l^wlni To lane mwln be Now Erdwr mlldmry e„la ml nmw ma lPwdned boom �`rara notary plops Al ballon-wi'mua act of pnwmtNWe -b wa r.M •„ meta bmwa`rmz N'.11 IFA. PWMM& u^ar ArBClmnen.a Cnrpm 'em eb... e.AS 'em am nm Pei IRWIN won Poi ewwC mlN.n we Dan s1 MAN pie eno.areu orbU�,a n.ear s(owna. C. Temperature Range: MAE Ogden Or on Pont AM Deis maoawLb wNq lmm nu F. m Imam0 M m n Co. faun ent Men, Of al O d. Piping Requirements: M P101ry%wemw.umlmlw an xPmmwIf. are Mr� KW Awa to me actOln Nestle Jurisdiction. M the[ Me agent must W •nor rylrn ,p Piano lona l�Nn,, wawh.�,gWona ME ce neon N. ftIim lm imN. cr.P.,-6ymm w.wr won. ton. b°REYz zl FUSIBLE LINK DETECTOR Pcr.re.aec INSTALLATION M*6w FMnx wk we unmmmm wan used won CHAPTERI sl l WHIma& NMw30inter General lnrormation mR Arms ame ilienseaid erttaeM real I Ed 1. Wood used In conjurralkern Form Me MAIN Pclapmc olio ... 4 It �t�.r, 4 MCHWNMCH3 W�A�l Wall RAW. After hourand �,..m length 11 cable too n.lu.]m, Me FIJI, we welding head the mate, I An 11" Me W CYLINDER �".M 1 11 PUI,�, in Influall That flaw Stn I T, Centel b moa msemww.w�awan.sepxnh.e[ranoetm install" In IN Warn nes. thenamedsen, and 1, 1. Fusible Link lnalallagon withoutns. doCher , 161ser d.,mr.r p,wmw, gedeunw. ulda. NEW WIN M p IN It Few awroll Nor Ther link IS Sun. water 10 Me W WO Of the ,•rafts =mime...O o fl� e link 1, Pat pred Ill. under "I'll's aWilM 11 SAM wwwr IF �,Wlld A from keep A than Moo.n e �ia And NoM May,' a LIENIA) A FORD CHEM led, Pley Rule M by the MIMP PMOW mp Is to term me, SHIM The bell Is wJorge. pMemi m, unmi,O11r Iran d.e11n wI.FigureAM WE)San lines mmberewr.dm • we �nwed In Mass owing 1116 In dlOMO%F ANIMIll Note editor The Malay At' 11 the .111 'old wereakno Inall an A' We' 01 feeble link,, If this tl,Ml 1. rpZ1IlE dwIrI FIJIAN. Inatsell link NUFFI Mlt RM Par ink be the igra nRuiaheaMO neon N. ftIim lm imN. INTRODUCTION PROCHREM m� ea nosy em" na�@ of the Searle Al COMM 0 ulmluo^m.mons m mmn lona vand ne WMr-rlMd In the Manor Me Intended 0 be '�gnIJW,,nWW m Penn an Pool PRo- n Rise dealer BOP ocEMor FIOM. ere �� mo« '/ wmmmnthe aremm mem. Bea. eyw;Int° wmdl.fW gard,ansoYl. Wtulb. r newt blow delay This Same Noma 1.,metro naaw.n ma LL Iza wmn.n,. tman Ip SaeasbS TEMPERATURE LIMITATIONS r> mina IDW,m sow F. Mp Ad CHd vmkb FORT Month debt' m n MTP to CI UL LISTING Mft MINCTI hi been tested of Me EASY 0 'Net aha urea or um.r.nnn mhdrarnn.., iz. CITY OF OF NEW YORK APPROVAL The FRED CHEM Vanilla RAW Spray Truth F 11 SUPPF.11P SYIIIM 'A �� by the Chash OfNew fork Fit, Aftefteent OF Anshonere of m I Prior to nMilMiCA Plan' meetbe fied ,In wodol very, caa •d AM No kC�arOf SUP161191 N�F�nt IF lens Wall be pencorkend M top FIFO Itheryll am fellow and appennor with SOCt OPS are 904 1 1 and ODA 4 11 Nine Oak CAR OFF Code AVON 17 And 43 ral New Ark Carento War Ins III Far 0 CConti len Tode. Ammoral Ronal be IM WWI to ret Halt tell Serum Is in cargo Wrk,M led, a. mapwda maintenance PMnderee. eN lam whand �a hn eManual the Me mm, ural F'ro'xawY1. rate �m BPwra xdwal:ownap won. ton. neon saw zl raw Pcr.re.aec RICO M*6w grmnwn CHAPTERI General lnrormation mR INTRODUCTION PROCHREM m� ea nosy em" na�@ of the Searle Al COMM 0 ulmluo^m.mons m mmn lona vand ne WMr-rlMd In the Manor Me Intended 0 be '�gnIJW,,nWW m Penn an Pool PRo- n Rise dealer BOP ocEMor FIOM. ere �� mo« '/ wmmmnthe aremm mem. Bea. eyw;Int° wmdl.fW gard,ansoYl. Wtulb. r newt blow delay This Same Noma 1.,metro naaw.n ma LL Iza wmn.n,. tman Ip SaeasbS TEMPERATURE LIMITATIONS r> mina IDW,m sow F. Mp Ad CHd vmkb FORT Month debt' m n MTP to CI UL LISTING Mft MINCTI hi been tested of Me EASY 0 'Net aha urea or um.r.nnn mhdrarnn.., iz. CITY OF OF NEW YORK APPROVAL The FRED CHEM Vanilla RAW Spray Truth F 11 SUPPF.11P SYIIIM 'A �� by the Chash OfNew fork Fit, Aftefteent OF Anshonere of m I Prior to nMilMiCA Plan' meetbe fied ,In wodol very, caa •d AM No kC�arOf SUP161191 N�F�nt IF lens Wall be pencorkend M top FIFO Itheryll am fellow and appennor with SOCt OPS are 904 1 1 and ODA 4 11 Nine Oak CAR OFF Code AVON 17 And 43 ral New Ark Carento War Ins III Far 0 CConti len Tode. Ammoral Ronal be IM WWI to ret Halt tell Serum Is in cargo Wrk,M led, a. mapwda maintenance PMnderee. eN lam whand �a hn eManual the Me mm, ural F'ro'xawY1. rate �m BPwra xdwal:ownap won. ton. neon saw Puy 16 raw Pcr.re.aec M*6w grmnwn mxnz.z ml mR erttaeM Pclapmc olio a nems. rzmrml. enR]ml CYLINDER T, PERMIT COMPLETE IARD iNWECTea MONAT RP:DATE moa msemww.w�awan.sepxnh.e[ranoetm r M rrz rLI rpZ1IlE I AN I PC grat A. CMAr ICmnnw[I iselmmvme`�' V prplea aperifiwlimx. This rcppu is in,mded be provide,he submitter wiN IM1e sYNs of plan appmva6 and any cpmmmb IM1aI my rMvire (vMn inlprma,ion,verifiunon m .[tion far apPrnv+l o(Plarx.Ail pYns maybesvbjeabfield inspxtipnmNmmting lmSimi approvalpoor 1p sign off maCertifimce O(Oampanryoa CeNfiue N Wpeadort The approval W plw mmtiNMe apamirM eommmen wm4whererequiaedby the fire cyllmn w. xdwal:ownap won. ton. neon saw em""Brxmhdm raw Pcr.re.aec M*6w grmnwn mxnz.z ml mR erttaeM rzmrml. enR]ml ANSI sammar rm.E,m Arvada Fire Protection District _ Fee "ad miI NOW aww win win,wrtnrz_An wwN n,nam.lr, .t zAW sen Mader my [mm.mark Mer Mae To 911=21 wrawraw Vnmx ARVADA FIRE PERMITlnw�Spr�Sp� IN e- DRY CHEMICAL SUPPRESSION SYSTEM lmmww wmminn DNA MASS FAA PERMIT COMPLETE IARD iNWECTea MONAT RP:DATE moa msemww.w�awan.sepxnh.e[ranoetm sammar rm.E,m Arvada Fire Protection District _ Fee "ad miI NOW aww win win,wrtnrz_An wwN n,nam.lr, .t zAW sen Mader my [mm.mark Mer Mae To 911=21 wrawraw Vnmx ARVADA FIRE PERMITlnw�Spr�Sp� IN e- DRY CHEMICAL SUPPRESSION SYSTEM lmmww wmminn DNA MASS FAA PERMIT COMPLETE IARD iNWECTea MONAT RP:DATE moa msemww.w�awan.sepxnh.e[ranoetm eoM•And 'u aubjaY Io lMmndrXwav Mary be nWedm Wemmmmraeation in lheaXaehedplav reviewrcpoX.Response try lltie review repoX v areaeuary alon8 wills an Pnw fm payment wJl be rcquiaed Paiw b anY field wPea4wu Irpmremmv.rmmrruu.-mwepM.mwt�a of Eaton CnaNera-Seem we9n Real vw]oaep wa . mvb. ICmXwadl1. Ther Frol @Wly to Ml 70ABC Falk; Try, My IRA Ar My SW piping rept dre WlNcM Caere AIwOh feel To M NP, A To 10 al Fel 4)WWrx6ha XevleDmrery Xevbryw spry 8,rnm uwlrymiru nNvdw C menoT ap N. bz.z m. n XµCpz 1%axpvel nm7e leanew z en(as nl z ertlp]M Y wb. en P]W xpR: z. Yom length mmr w rvn .aManor to, .11 Al AM , and, combetal uM 0 Col 3, A Me "Be'.'. $.In ChAlk Valled Part No 417708. MCA by IMI" bi the Cyli�eF AM or llaN of sem w.r.m@ num spas e nwa s. Wel iIn' napmof ndzae rmm me.gmnto mons-xpnw.l ml. Y pnxkmaymwro 0e PC `F'aa'mm`,"xp[aa rs.wrz-cmrmnw Rmv PNEUMATIC ACTUATING 2 MaMI PAG200. ����Orav� CYLINDERS �0 nqr� do NEW are The locklel MC -10 is A pays ... IN use al a "KIM Can of " �,1,q_ Mdalnceml.. pn.wm wumm rec04R' 1. MDael Pac-t D. I F ASV mY` � ,w.rmum a,wmY 11 m.n ddlww m`waxwuw acmwMMmlw a+]wMn try X • all der werwrame Men My rear A Mo.' aft Pl1WIld no o IF N •Hmtq rvmn •Yon v6le®rp•G.'s P.aGEUmgenn men:!Ow nynaenoreetmmM m'Do' m..ame. ""mamm. P`w aic, Ia�mD�aEPar� y SaFqulrexe. I- �� 17 MARC aN.n x Xm Meta Prreum.a AmJnrm vylmae.. o am �.ewmXla ers IV Mlmar. M iller 1• t� emaHora;APPROVED ;`Fr .• 1{w y'' uvr nnxn n,max[[x wrcosp pxzy p,gT10AfinalinapedloninaudingNnCHnnallllMMaeye1q,18nUXfr.aML-3 gFPg eppoval allall be requllE.•23'lmXala•hrest. XXMM von or. H.Nar1YUfMA• eWN 10'DR I{'W N9a•MNwnartl 56memgdkolxuuL23L3{•XW,M19VvtINTfRIOR SPg1rg1ER 6K1FM5eto1)1)61X,AVRaN,463W EYM1g 1{wemmxarrdera[wmalolY9mRDUCEYaIa YYXH� seim Syxtem FO-]XHIIe[/alrlb Nfpp Standard fv 0.y CMmical ftlirrBUlsM1IrM Sys,en NWa I] II eafd Complanm Testing UL UxNng aHll men Merwlactue Spe[ifcationLanwryWebb rXSTPRfR dmmpemMthen None, IN Aral 16G A A will Is" it IT So WI MCI 4 ft PI Sol lot IT NI ANY It SO' 24 it IRWIN.' oweRformair Am ARM A Ad ITSale Pit it heq�nwrrural ARM WA in A Rr old ounce ordI on A Oil I IF IN BOOTH FIRE SUPPRESSION i-Amen4M IV �•g. Noale CavaragesThe Clark AM 19 "any Cel"sln Convon from WO Wine l xwwA .w Xu.ew mm�m [m x used x. .mouth, w m pmts alar pmwm. me mad. mwmum ,owxamn& CAN a MCI y�m.ranN.e<nnamm�m..d .,a. me.lmr,,. xw�una bN•ro'waea rmmn«m��nmenrvrznwlmew'am..r�mm rad o-dxam rnmunnw. n ra."mr.'y,'she• SCSI No froural no barely 0 has War M�U12, wvk Pm nm OwX.a Ar", ml. al a ml.wBm.n lax�eel m mX awr xY.6w son Tm au e Wgcel I+m`mn'all[elm wrwl Pam I[n rzn wl.mym set nacos e 6id.l[q n :rer�:o<n.�al ml Lm oleo sen law awn .a e ^ .Noon Wnavxr brtnaeel an an 6n[nnbwomer p n Nrrwl opadn n �ogldnw °F° e'n III mer ad. na a xnmml n,m WIF len Hn[n BNyn' lmBw tlew� p e waml x4QP_P BX BN an 6mrrutwelad„ once wrwrrWM IMF ,semi-water � blmrwmea lmlxtmelnm sawn u•wrmw won. waw A nom. .ts •A' Togo nmw`.r aware mrmrw hwuda s� 10 lPelnwwwr Pev NOZZLES nY®gl.apmo az .1 Oman ^ O m m m m IMmmd dma nMFpra ° Boaxso c�OOs MMODEL III - ECHANICAL CONTROL HEAD w' �. s.M ®r X.FLU a,ulrym IM command)W PIT r sock Mi; a OP, barn cos .muck ..mom I handle .Wareow crew IX POT Me C col it oTlie lbert m, 1.1 nalm! " wn��lWlld hewn I Carl Mdl head can Imum d nom l9 MlMgm mMUF NISSAN H"� NEWS,ownFewer .••swiss. CYLINDER BRACKETING XwaMcxa eoxeRaL XF{o wi .n 11 PrnMd l be y.`M Paul Merl 6=.NW � •,;_ w Ween iawv the mmol man mvumnp No „�, •-_ 24 ftx Bear lnl" m w PCFI]AMW -M eh nnrype Mu," AT w wMneaxmeeteet nmra THAL wluma Amid. n NSAOC, A10N.,Me • neryq mw nnrq d hi W b wti nge. Ibe Mmes m cul p. ��Y-PanmsY 0. Fusible Lint. nelgw 'Warner ellnX llrc,[wsiry he ons remprnure Wool 11 mac dict. evwmacmmi^n. sr FailureFailureism. DI1°• � pas ecl ioaPo IBM Flesect FDn•cl Tp�W ANN 1. ft ,D0.0 sw slam C L MODEL R P&M 'Flxlp�c, REMOTE S Fawa,ery_baawuw MECHANICAL PULL STATION `sewn-snT' •w Wu. aumwnxae u�:mw. r•lrr.wNm owl amm:p. °"Yw lndrxmmnm.: drxa"r"a"[drrw,dnw°I:`®aam MAY ba":mm�mnpamYvwnbw tlx MngrmnmWhn tlnnawv TMe bad In lRln. END mqux maw wM X sen Par y h exroM, Trans rem WEYI HLink YowunaMNm wnrvlvbl roiglprapmxfybeewXWPnrW Tmeame FYraeWIN. OY F(Me CI mM•d FIm s offic21 eFiiu°'�•eft) •F(WAR cr Rom tm'PryN•CI g.TMr mal Is O Dominantmap me Fral I AL . rrgnetM mmpmun nnrmu axemn en n[n xmYo-wwwwmw.m.mt most O a ec led .rcaOL tw wPww .isms. Op rn.r..n AAd My I 111.1 ,TI: haunt a.uwa nP �Mmaxml arremn. Mean a,xTamlRwam.. Fww.°°;.','zpm� !1 @ FAA Milan W FAA M� �MEWS IS TO IWWDE ALL Mae W��y Fret THE PMMR EM�ON AND OWKTIT� I THE wake of To OMTWT� THE W THE CRASH MN�M VON Rod ��U REWA� SHIP Al "most YARME TO WITWT MCI ON ENE IW�T� MI CAN THIS WEAT �S NOT Anther Architects, PLLC Architecture Th Engineering 3727 Candia Drive Punta Gorda FL 33950 500-243-0528 734-709-7297 9burgh gmail.com et �: L ycr"�j� BOOTH FIRE SUPPRESSION Booth Wall Components _SHEET -NUMBER- Pamaa: rmesaayrJuly l° Wheal Rio' U at' w c BGyd4 9 OMso 0 mFa Q tr MO W O U � N Q C N CL U ca >1111% wFAAa Car) CD 00 fee. E t a M lV Cca : O m O C7 000 ) All ccM WMALO U W n, zfir xpR: z. Yom length mmr w rvn .aManor to, .11 Al AM , and, combetal uM 0 Col 3, A Me "Be'.'. $.In ChAlk Valled Part No 417708. MCA by IMI" bi the Cyli�eF AM or llaN of sem w.r.m@ num spas e nwa s. Wel iIn' napmof ndzae rmm me.gmnto mons-xpnw.l ml. Y pnxkmaymwro 0e PC `F'aa'mm`,"xp[aa rs.wrz-cmrmnw Rmv PNEUMATIC ACTUATING 2 MaMI PAG200. ����Orav� CYLINDERS �0 nqr� do NEW are The locklel MC -10 is A pays ... IN use al a "KIM Can of " �,1,q_ Mdalnceml.. pn.wm wumm rec04R' 1. MDael Pac-t D. I F ASV mY` � ,w.rmum a,wmY 11 m.n ddlww m`waxwuw acmwMMmlw a+]wMn try X • all der werwrame Men My rear A Mo.' aft Pl1WIld no o IF N •Hmtq rvmn •Yon v6le®rp•G.'s P.aGEUmgenn men:!Ow nynaenoreetmmM m'Do' m..ame. ""mamm. P`w aic, Ia�mD�aEPar� y SaFqulrexe. I- �� 17 MARC aN.n x Xm Meta Prreum.a AmJnrm vylmae.. o am �.ewmXla ers IV Mlmar. M iller 1• t� emaHora;APPROVED ;`Fr .• 1{w y'' uvr nnxn n,max[[x wrcosp pxzy p,gT10AfinalinapedloninaudingNnCHnnallllMMaeye1q,18nUXfr.aML-3 gFPg eppoval allall be requllE.•23'lmXala•hrest. XXMM von or. H.Nar1YUfMA• eWN 10'DR I{'W N9a•MNwnartl 56memgdkolxuuL23L3{•XW,M19VvtINTfRIOR SPg1rg1ER 6K1FM5eto1)1)61X,AVRaN,463W EYM1g 1{wemmxarrdera[wmalolY9mRDUCEYaIa YYXH� seim Syxtem FO-]XHIIe[/alrlb Nfpp Standard fv 0.y CMmical ftlirrBUlsM1IrM Sys,en NWa I] II eafd Complanm Testing UL UxNng aHll men Merwlactue Spe[ifcationLanwryWebb rXSTPRfR dmmpemMthen None, IN Aral 16G A A will Is" it IT So WI MCI 4 ft PI Sol lot IT NI ANY It SO' 24 it IRWIN.' oweRformair Am ARM A Ad ITSale Pit it heq�nwrrural ARM WA in A Rr old ounce ordI on A Oil I IF IN BOOTH FIRE SUPPRESSION i-Amen4M IV �•g. Noale CavaragesThe Clark AM 19 "any Cel"sln Convon from WO Wine l xwwA .w Xu.ew mm�m [m x used x. .mouth, w m pmts alar pmwm. me mad. mwmum ,owxamn& CAN a MCI y�m.ranN.e<nnamm�m..d .,a. me.lmr,,. xw�una bN•ro'waea rmmn«m��nmenrvrznwlmew'am..r�mm rad o-dxam rnmunnw. n ra."mr.'y,'she• SCSI No froural no barely 0 has War M�U12, wvk Pm nm OwX.a Ar", ml. al a ml.wBm.n lax�eel m mX awr xY.6w son Tm au e Wgcel I+m`mn'all[elm wrwl Pam I[n rzn wl.mym set nacos e 6id.l[q n :rer�:o<n.�al ml Lm oleo sen law awn .a e ^ .Noon Wnavxr brtnaeel an an 6n[nnbwomer p n Nrrwl opadn n �ogldnw °F° e'n III mer ad. na a xnmml n,m WIF len Hn[n BNyn' lmBw tlew� p e waml x4QP_P BX BN an 6mrrutwelad„ once wrwrrWM IMF ,semi-water � blmrwmea lmlxtmelnm sawn u•wrmw won. waw A nom. .ts •A' Togo nmw`.r aware mrmrw hwuda s� 10 lPelnwwwr Pev NOZZLES nY®gl.apmo az .1 Oman ^ O m m m m IMmmd dma nMFpra ° Boaxso c�OOs MMODEL III - ECHANICAL CONTROL HEAD w' �. s.M ®r X.FLU a,ulrym IM command)W PIT r sock Mi; a OP, barn cos .muck ..mom I handle .Wareow crew IX POT Me C col it oTlie lbert m, 1.1 nalm! " wn��lWlld hewn I Carl Mdl head can Imum d nom l9 MlMgm mMUF NISSAN H"� NEWS,ownFewer .••swiss. CYLINDER BRACKETING XwaMcxa eoxeRaL XF{o wi .n 11 PrnMd l be y.`M Paul Merl 6=.NW � •,;_ w Ween iawv the mmol man mvumnp No „�, •-_ 24 ftx Bear lnl" m w PCFI]AMW -M eh nnrype Mu," AT w wMneaxmeeteet nmra THAL wluma Amid. n NSAOC, A10N.,Me • neryq mw nnrq d hi W b wti nge. Ibe Mmes m cul p. ��Y-PanmsY 0. Fusible Lint. nelgw 'Warner ellnX llrc,[wsiry he ons remprnure Wool 11 mac dict. evwmacmmi^n. sr FailureFailureism. DI1°• � pas ecl ioaPo IBM Flesect FDn•cl Tp�W ANN 1. ft ,D0.0 sw slam C L MODEL R P&M 'Flxlp�c, REMOTE S Fawa,ery_baawuw MECHANICAL PULL STATION `sewn-snT' •w Wu. aumwnxae u�:mw. r•lrr.wNm owl amm:p. °"Yw lndrxmmnm.: drxa"r"a"[drrw,dnw°I:`®aam MAY ba":mm�mnpamYvwnbw tlx MngrmnmWhn tlnnawv TMe bad In lRln. END mqux maw wM X sen Par y h exroM, Trans rem WEYI HLink YowunaMNm wnrvlvbl roiglprapmxfybeewXWPnrW Tmeame FYraeWIN. OY F(Me CI mM•d FIm s offic21 eFiiu°'�•eft) •F(WAR cr Rom tm'PryN•CI g.TMr mal Is O Dominantmap me Fral I AL . rrgnetM mmpmun nnrmu axemn en n[n xmYo-wwwwmw.m.mt most O a ec led .rcaOL tw wPww .isms. Op rn.r..n AAd My I 111.1 ,TI: haunt a.uwa nP �Mmaxml arremn. Mean a,xTamlRwam.. Fww.°°;.','zpm� !1 @ FAA Milan W FAA M� �MEWS IS TO IWWDE ALL Mae W��y Fret THE PMMR EM�ON AND OWKTIT� I THE wake of To OMTWT� THE W THE CRASH MN�M VON Rod ��U REWA� SHIP Al "most YARME TO WITWT MCI ON ENE IW�T� MI CAN THIS WEAT �S NOT Anther Architects, PLLC Architecture Th Engineering 3727 Candia Drive Punta Gorda FL 33950 500-243-0528 734-709-7297 9burgh gmail.com et �: L ycr"�j� BOOTH FIRE SUPPRESSION Booth Wall Components _SHEET -NUMBER- Pamaa: rmesaayrJuly l° Wheal Rio' U at' w c BGyd4 9 OMso 0 mFa Q tr MO W O U � N Q C N CL U ca >1111% wFAAa Car) CD 00 fee. E t a M lV Cca : O m O C7 000 ) All ccM WMALO U W n, zfir aN.n x Xm Meta Prreum.a AmJnrm vylmae.. o am �.ewmXla ers IV Mlmar. M iller 1• t� emaHora;APPROVED ;`Fr .• 1{w y'' uvr nnxn n,max[[x wrcosp pxzy p,gT10AfinalinapedloninaudingNnCHnnallllMMaeye1q,18nUXfr.aML-3 gFPg eppoval allall be requllE.•23'lmXala•hrest. XXMM von or. H.Nar1YUfMA• eWN 10'DR I{'W N9a•MNwnartl 56memgdkolxuuL23L3{•XW,M19VvtINTfRIOR SPg1rg1ER 6K1FM5eto1)1)61X,AVRaN,463W EYM1g 1{wemmxarrdera[wmalolY9mRDUCEYaIa YYXH� seim Syxtem FO-]XHIIe[/alrlb Nfpp Standard fv 0.y CMmical ftlirrBUlsM1IrM Sys,en NWa I] II eafd Complanm Testing UL UxNng aHll men Merwlactue Spe[ifcationLanwryWebb rXSTPRfR dmmpemMthen None, IN Aral 16G A A will Is" it IT So WI MCI 4 ft PI Sol lot IT NI ANY It SO' 24 it IRWIN.' oweRformair Am ARM A Ad ITSale Pit it heq�nwrrural ARM WA in A Rr old ounce ordI on A Oil I IF IN BOOTH FIRE SUPPRESSION i-Amen4M IV �•g. Noale CavaragesThe Clark AM 19 "any Cel"sln Convon from WO Wine l xwwA .w Xu.ew mm�m [m x used x. .mouth, w m pmts alar pmwm. me mad. mwmum ,owxamn& CAN a MCI y�m.ranN.e<nnamm�m..d .,a. me.lmr,,. xw�una bN•ro'waea rmmn«m��nmenrvrznwlmew'am..r�mm rad o-dxam rnmunnw. n ra."mr.'y,'she• SCSI No froural no barely 0 has War M�U12, wvk Pm nm OwX.a Ar", ml. al a ml.wBm.n lax�eel m mX awr xY.6w son Tm au e Wgcel I+m`mn'all[elm wrwl Pam I[n rzn wl.mym set nacos e 6id.l[q n :rer�:o<n.�al ml Lm oleo sen law awn .a e ^ .Noon Wnavxr brtnaeel an an 6n[nnbwomer p n Nrrwl opadn n �ogldnw °F° e'n III mer ad. na a xnmml n,m WIF len Hn[n BNyn' lmBw tlew� p e waml x4QP_P BX BN an 6mrrutwelad„ once wrwrrWM IMF ,semi-water � blmrwmea lmlxtmelnm sawn u•wrmw won. waw A nom. .ts •A' Togo nmw`.r aware mrmrw hwuda s� 10 lPelnwwwr Pev NOZZLES nY®gl.apmo az .1 Oman ^ O m m m m IMmmd dma nMFpra ° Boaxso c�OOs MMODEL III - ECHANICAL CONTROL HEAD w' �. s.M ®r X.FLU a,ulrym IM command)W PIT r sock Mi; a OP, barn cos .muck ..mom I handle .Wareow crew IX POT Me C col it oTlie lbert m, 1.1 nalm! " wn��lWlld hewn I Carl Mdl head can Imum d nom l9 MlMgm mMUF NISSAN H"� NEWS,ownFewer .••swiss. CYLINDER BRACKETING XwaMcxa eoxeRaL XF{o wi .n 11 PrnMd l be y.`M Paul Merl 6=.NW � •,;_ w Ween iawv the mmol man mvumnp No „�, •-_ 24 ftx Bear lnl" m w PCFI]AMW -M eh nnrype Mu," AT w wMneaxmeeteet nmra THAL wluma Amid. n NSAOC, A10N.,Me • neryq mw nnrq d hi W b wti nge. Ibe Mmes m cul p. ��Y-PanmsY 0. Fusible Lint. nelgw 'Warner ellnX llrc,[wsiry he ons remprnure Wool 11 mac dict. evwmacmmi^n. sr FailureFailureism. DI1°• � pas ecl ioaPo IBM Flesect FDn•cl Tp�W ANN 1. ft ,D0.0 sw slam C L MODEL R P&M 'Flxlp�c, REMOTE S Fawa,ery_baawuw MECHANICAL PULL STATION `sewn-snT' •w Wu. aumwnxae u�:mw. r•lrr.wNm owl amm:p. °"Yw lndrxmmnm.: drxa"r"a"[drrw,dnw°I:`®aam MAY ba":mm�mnpamYvwnbw tlx MngrmnmWhn tlnnawv TMe bad In lRln. END mqux maw wM X sen Par y h exroM, Trans rem WEYI HLink YowunaMNm wnrvlvbl roiglprapmxfybeewXWPnrW Tmeame FYraeWIN. OY F(Me CI mM•d FIm s offic21 eFiiu°'�•eft) •F(WAR cr Rom tm'PryN•CI g.TMr mal Is O Dominantmap me Fral I AL . rrgnetM mmpmun nnrmu axemn en n[n xmYo-wwwwmw.m.mt most O a ec led .rcaOL tw wPww .isms. Op rn.r..n AAd My I 111.1 ,TI: haunt a.uwa nP �Mmaxml arremn. Mean a,xTamlRwam.. Fww.°°;.','zpm� !1 @ FAA Milan W FAA M� �MEWS IS TO IWWDE ALL Mae W��y Fret THE PMMR EM�ON AND OWKTIT� I THE wake of To OMTWT� THE W THE CRASH MN�M VON Rod ��U REWA� SHIP Al "most YARME TO WITWT MCI ON ENE IW�T� MI CAN THIS WEAT �S NOT Anther Architects, PLLC Architecture Th Engineering 3727 Candia Drive Punta Gorda FL 33950 500-243-0528 734-709-7297 9burgh gmail.com et �: L ycr"�j� BOOTH FIRE SUPPRESSION Booth Wall Components _SHEET -NUMBER- Pamaa: rmesaayrJuly l° Wheal Rio' U at' w c BGyd4 9 OMso 0 mFa Q tr MO W O U � N Q C N CL U ca >1111% wFAAa Car) CD 00 fee. E t a M lV Cca : O m O C7 000 ) All ccM WMALO U W n, zfir BOOTH FIRE SUPPRESSION i-Amen4M IV �•g. Noale CavaragesThe Clark AM 19 "any Cel"sln Convon from WO Wine l xwwA .w Xu.ew mm�m [m x used x. .mouth, w m pmts alar pmwm. me mad. mwmum ,owxamn& CAN a MCI y�m.ranN.e<nnamm�m..d .,a. me.lmr,,. xw�una bN•ro'waea rmmn«m��nmenrvrznwlmew'am..r�mm rad o-dxam rnmunnw. n ra."mr.'y,'she• SCSI No froural no barely 0 has War M�U12, wvk Pm nm OwX.a Ar", ml. al a ml.wBm.n lax�eel m mX awr xY.6w son Tm au e Wgcel I+m`mn'all[elm wrwl Pam I[n rzn wl.mym set nacos e 6id.l[q n :rer�:o<n.�al ml Lm oleo sen law awn .a e ^ .Noon Wnavxr brtnaeel an an 6n[nnbwomer p n Nrrwl opadn n �ogldnw °F° e'n III mer ad. na a xnmml n,m WIF len Hn[n BNyn' lmBw tlew� p e waml x4QP_P BX BN an 6mrrutwelad„ once wrwrrWM IMF ,semi-water � blmrwmea lmlxtmelnm sawn u•wrmw won. waw A nom. .ts •A' Togo nmw`.r aware mrmrw hwuda s� 10 lPelnwwwr Pev NOZZLES nY®gl.apmo az .1 Oman ^ O m m m m IMmmd dma nMFpra ° Boaxso c�OOs MMODEL III - ECHANICAL CONTROL HEAD w' �. s.M ®r X.FLU a,ulrym IM command)W PIT r sock Mi; a OP, barn cos .muck ..mom I handle .Wareow crew IX POT Me C col it oTlie lbert m, 1.1 nalm! " wn��lWlld hewn I Carl Mdl head can Imum d nom l9 MlMgm mMUF NISSAN H"� NEWS,ownFewer .••swiss. CYLINDER BRACKETING XwaMcxa eoxeRaL XF{o wi .n 11 PrnMd l be y.`M Paul Merl 6=.NW � •,;_ w Ween iawv the mmol man mvumnp No „�, •-_ 24 ftx Bear lnl" m w PCFI]AMW -M eh nnrype Mu," AT w wMneaxmeeteet nmra THAL wluma Amid. n NSAOC, A10N.,Me • neryq mw nnrq d hi W b wti nge. Ibe Mmes m cul p. ��Y-PanmsY 0. Fusible Lint. nelgw 'Warner ellnX llrc,[wsiry he ons remprnure Wool 11 mac dict. evwmacmmi^n. sr FailureFailureism. DI1°• � pas ecl ioaPo IBM Flesect FDn•cl Tp�W ANN 1. ft ,D0.0 sw slam C L MODEL R P&M 'Flxlp�c, REMOTE S Fawa,ery_baawuw MECHANICAL PULL STATION `sewn-snT' •w Wu. aumwnxae u�:mw. r•lrr.wNm owl amm:p. °"Yw lndrxmmnm.: drxa"r"a"[drrw,dnw°I:`®aam MAY ba":mm�mnpamYvwnbw tlx MngrmnmWhn tlnnawv TMe bad In lRln. END mqux maw wM X sen Par y h exroM, Trans rem WEYI HLink YowunaMNm wnrvlvbl roiglprapmxfybeewXWPnrW Tmeame FYraeWIN. OY F(Me CI mM•d FIm s offic21 eFiiu°'�•eft) •F(WAR cr Rom tm'PryN•CI g.TMr mal Is O Dominantmap me Fral I AL . rrgnetM mmpmun nnrmu axemn en n[n xmYo-wwwwmw.m.mt most O a ec led .rcaOL tw wPww .isms. Op rn.r..n AAd My I 111.1 ,TI: haunt a.uwa nP �Mmaxml arremn. Mean a,xTamlRwam.. Fww.°°;.','zpm� !1 @ FAA Milan W FAA M� �MEWS IS TO IWWDE ALL Mae W��y Fret THE PMMR EM�ON AND OWKTIT� I THE wake of To OMTWT� THE W THE CRASH MN�M VON Rod ��U REWA� SHIP Al "most YARME TO WITWT MCI ON ENE IW�T� MI CAN THIS WEAT �S NOT Anther Architects, PLLC Architecture Th Engineering 3727 Candia Drive Punta Gorda FL 33950 500-243-0528 734-709-7297 9burgh gmail.com et �: L ycr"�j� BOOTH FIRE SUPPRESSION Booth Wall Components _SHEET -NUMBER- Pamaa: rmesaayrJuly l° Wheal Rio' U at' w c BGyd4 9 OMso 0 mFa Q tr MO W O U � N Q C N CL U ca >1111% wFAAa Car) CD 00 fee. E t a M lV Cca : O m O C7 000 ) All ccM WMALO U W n, zfir wvk Pm nm OwX.a Ar", ml. al a ml.wBm.n lax�eel m mX awr xY.6w son Tm au e Wgcel I+m`mn'all[elm wrwl Pam I[n rzn wl.mym set nacos e 6id.l[q n :rer�:o<n.�al ml Lm oleo sen law awn .a e ^ .Noon Wnavxr brtnaeel an an 6n[nnbwomer p n Nrrwl opadn n �ogldnw °F° e'n III mer ad. na a xnmml n,m WIF len Hn[n BNyn' lmBw tlew� p e waml x4QP_P BX BN an 6mrrutwelad„ once wrwrrWM IMF ,semi-water � blmrwmea lmlxtmelnm sawn u•wrmw won. waw A nom. .ts •A' Togo nmw`.r aware mrmrw hwuda s� 10 lPelnwwwr Pev NOZZLES nY®gl.apmo az .1 Oman ^ O m m m m IMmmd dma nMFpra ° Boaxso c�OOs MMODEL III - ECHANICAL CONTROL HEAD w' �. s.M ®r X.FLU a,ulrym IM command)W PIT r sock Mi; a OP, barn cos .muck ..mom I handle .Wareow crew IX POT Me C col it oTlie lbert m, 1.1 nalm! " wn��lWlld hewn I Carl Mdl head can Imum d nom l9 MlMgm mMUF NISSAN H"� NEWS,ownFewer .••swiss. CYLINDER BRACKETING XwaMcxa eoxeRaL XF{o wi .n 11 PrnMd l be y.`M Paul Merl 6=.NW � •,;_ w Ween iawv the mmol man mvumnp No „�, •-_ 24 ftx Bear lnl" m w PCFI]AMW -M eh nnrype Mu," AT w wMneaxmeeteet nmra THAL wluma Amid. n NSAOC, A10N.,Me • neryq mw nnrq d hi W b wti nge. Ibe Mmes m cul p. ��Y-PanmsY 0. Fusible Lint. nelgw 'Warner ellnX llrc,[wsiry he ons remprnure Wool 11 mac dict. evwmacmmi^n. sr FailureFailureism. DI1°• � pas ecl ioaPo IBM Flesect FDn•cl Tp�W ANN 1. ft ,D0.0 sw slam C L MODEL R P&M 'Flxlp�c, REMOTE S Fawa,ery_baawuw MECHANICAL PULL STATION `sewn-snT' •w Wu. aumwnxae u�:mw. r•lrr.wNm owl amm:p. °"Yw lndrxmmnm.: drxa"r"a"[drrw,dnw°I:`®aam MAY ba":mm�mnpamYvwnbw tlx MngrmnmWhn tlnnawv TMe bad In lRln. END mqux maw wM X sen Par y h exroM, Trans rem WEYI HLink YowunaMNm wnrvlvbl roiglprapmxfybeewXWPnrW Tmeame FYraeWIN. OY F(Me CI mM•d FIm s offic21 eFiiu°'�•eft) •F(WAR cr Rom tm'PryN•CI g.TMr mal Is O Dominantmap me Fral I AL . rrgnetM mmpmun nnrmu axemn en n[n xmYo-wwwwmw.m.mt most O a ec led .rcaOL tw wPww .isms. Op rn.r..n AAd My I 111.1 ,TI: haunt a.uwa nP �Mmaxml arremn. Mean a,xTamlRwam.. Fww.°°;.','zpm� !1 @ FAA Milan W FAA M� �MEWS IS TO IWWDE ALL Mae W��y Fret THE PMMR EM�ON AND OWKTIT� I THE wake of To OMTWT� THE W THE CRASH MN�M VON Rod ��U REWA� SHIP Al "most YARME TO WITWT MCI ON ENE IW�T� MI CAN THIS WEAT �S NOT Anther Architects, PLLC Architecture Th Engineering 3727 Candia Drive Punta Gorda FL 33950 500-243-0528 734-709-7297 9burgh gmail.com et �: L ycr"�j� BOOTH FIRE SUPPRESSION Booth Wall Components _SHEET -NUMBER- Pamaa: rmesaayrJuly l° Wheal Rio' U at' w c BGyd4 9 OMso 0 mFa Q tr MO W O U � N Q C N CL U ca >1111% wFAAa Car) CD 00 fee. E t a M lV Cca : O m O C7 000 ) All ccM WMALO U W n, zfir Pev NOZZLES nY®gl.apmo az .1 Oman ^ O m m m m IMmmd dma nMFpra ° Boaxso c�OOs MMODEL III - ECHANICAL CONTROL HEAD w' �. s.M ®r X.FLU a,ulrym IM command)W PIT r sock Mi; a OP, barn cos .muck ..mom I handle .Wareow crew IX POT Me C col it oTlie lbert m, 1.1 nalm! " wn��lWlld hewn I Carl Mdl head can Imum d nom l9 MlMgm mMUF NISSAN H"� NEWS,ownFewer .••swiss. CYLINDER BRACKETING XwaMcxa eoxeRaL XF{o wi .n 11 PrnMd l be y.`M Paul Merl 6=.NW � •,;_ w Ween iawv the mmol man mvumnp No „�, •-_ 24 ftx Bear lnl" m w PCFI]AMW -M eh nnrype Mu," AT w wMneaxmeeteet nmra THAL wluma Amid. n NSAOC, A10N.,Me • neryq mw nnrq d hi W b wti nge. Ibe Mmes m cul p. ��Y-PanmsY 0. Fusible Lint. nelgw 'Warner ellnX llrc,[wsiry he ons remprnure Wool 11 mac dict. evwmacmmi^n. sr FailureFailureism. DI1°• � pas ecl ioaPo IBM Flesect FDn•cl Tp�W ANN 1. ft ,D0.0 sw slam C L MODEL R P&M 'Flxlp�c, REMOTE S Fawa,ery_baawuw MECHANICAL PULL STATION `sewn-snT' •w Wu. aumwnxae u�:mw. r•lrr.wNm owl amm:p. °"Yw lndrxmmnm.: drxa"r"a"[drrw,dnw°I:`®aam MAY ba":mm�mnpamYvwnbw tlx MngrmnmWhn tlnnawv TMe bad In lRln. END mqux maw wM X sen Par y h exroM, Trans rem WEYI HLink YowunaMNm wnrvlvbl roiglprapmxfybeewXWPnrW Tmeame FYraeWIN. OY F(Me CI mM•d FIm s offic21 eFiiu°'�•eft) •F(WAR cr Rom tm'PryN•CI g.TMr mal Is O Dominantmap me Fral I AL . rrgnetM mmpmun nnrmu axemn en n[n xmYo-wwwwmw.m.mt most O a ec led .rcaOL tw wPww .isms. Op rn.r..n AAd My I 111.1 ,TI: haunt a.uwa nP �Mmaxml arremn. Mean a,xTamlRwam.. Fww.°°;.','zpm� !1 @ FAA Milan W FAA M� �MEWS IS TO IWWDE ALL Mae W��y Fret THE PMMR EM�ON AND OWKTIT� I THE wake of To OMTWT� THE W THE CRASH MN�M VON Rod ��U REWA� SHIP Al "most YARME TO WITWT MCI ON ENE IW�T� MI CAN THIS WEAT �S NOT Anther Architects, PLLC Architecture Th Engineering 3727 Candia Drive Punta Gorda FL 33950 500-243-0528 734-709-7297 9burgh gmail.com et �: L ycr"�j� BOOTH FIRE SUPPRESSION Booth Wall Components _SHEET -NUMBER- Pamaa: rmesaayrJuly l° Wheal Rio' U at' w c BGyd4 9 OMso 0 mFa Q tr MO W O U � N Q C N CL U ca >1111% wFAAa Car) CD 00 fee. E t a M lV Cca : O m O C7 000 ) All ccM WMALO U W n, zfir n, zfir I WA :CURE AREA 1 2 3 4 5 6 io NEW ELECTRICAL CONDUIT SHALL BE INSTALLED ON THE CEILING EXPOSED TO NEW WALL OUTLETS FROM THE EXISTING ELECTRICAL PANEL -A GRID CEILING Anther Architects, )LLC SHALL BE INSTALLED TO CONCIEL ALL CONDUIT A hitectu ring 3727 Candia Drive 3727 EXISTING SERVICE SIZE: 150 AMP 3 PHASE Punta Gorda FL 33950 800-243-0528 734-709-7297 =9E EXISTING 120V DUPLEX RECEPTICAL 9burgh@gmail.com �N NEW 120V DUPLEX RECEPTICAL �pF CO�p� =(H)N NEW 120V 4 FLEX RECEPTICAL P o E EXISTING DATA STUeuR RIIFFIN �* - -'__--- ----- ❑N N NEW DATA ARC 00406898 *. # NSeo " -- ITEM 26 THE REFRIGERATOR 120V SINGLE PHASE ARCH` ' ITEM 25 THE DISPLAY CASE IS 120V SINGLE PHASEMEMO OF GRIFFIN STRAIT MONITORED PLC [TENNESSEE I THIS ASSISTANT WAR OF TDIS CHRIST A ANNE? STARTING, ART ANTIM ARI RED ALL EDITS OFFERED CAPTIVE AIR RTU- r ' MODEL A1-IBT-150-16Z METER DO NOT SEEMS °"""""S OO I -- �?_ ,_; -Q_ O O=.rem THE CONTINSTOW SARI EASE SIDE) MEARTURENDEREAS AND WERE NEED OHNNORES, SAM THATHE TRANI MARINE DISARMAMENT AIDS MESODERM AM 01why, TO ME ONCROMFOR WITH THEM -------------- ❑ ❑ ❑ -------=MIN 3'= = -—_ __ - ' ---- EXISTING SUB PAMELA 1P wENTROMATINEW CONTENTS,, 1,I 11I AND CAMPARE DEMAND DEADEMENTO WITH WON STREET AM WON MENTIONED OF THE EASED AND OHIO AT SAM REFTERINT TO TOM AREDIFTEET My REFORM OR TEAMSTERS MADDAMED CONTRACTOR 12 MIAMI FOR EZ:EXISTING SUB PANEL: CIR-37 CIR-32 CIR-34 3DIMENSIONS ' CLE TING SUB PANEL L2: 120/240V 100A �[ SWITCH SHARE AN CORE WANT ANDCORREATEMAT �" 100 AMP 3P MIN 3' HAL EXTRACTION BOOTH MODEL g2 5 CLASS 1 0 200 AMP 30.W/ HIGH LEGAFTI THEN THE b WOODEN AM THE 6 °'°`°` "`°"^"" " DIVISION CLEARANCE 1 (EXPLOSION PROOF) ( OTHERS) - - �` ` THIS PANEL XS FED BY THE MAIN PANEL 3P 120/240V 400A,E TnEw AN THE MTRM, ESTIMATES IS TO MOUTH AUL ml MEADOWS' SIR THE PROPER EXEDUET11 "IOESEETTROW OF THE SOME OF THE CONTACTED THE MAIN CONTROL SERV CE OUTLET1s r ' Nk MAIN 40A 0PANEL C -PHASE HIGH LEG 208VMEASURES EDWARD AMENDMENTS ME �w�� AM THAT is SW ONE DOME MAE SENSE ASIR REMAINS WEST LAB PANEL FOR R__TU oaAND _ _ ' Q-' IFFERRED FROM TIE' AS HEING STRESSED' ', EXISTING NG SUB PANEL L1 NOT EXISTING SUB PANEL E: RTU �-----1�TU _" ' ', 200A3P120/240 � �'�_ �, -------- 120/240V 200A ❑ 375-39 CIR-1,3CZEDEDEEP! 375 EXISTING SUB PANEL AC STORAGE ECORKEN MINI COOLERS ' 200A 3P 120/240 OPEN WORKSHOP '9 18.4 3 5 � 97 ❑ ❑E_ cIR-38,40 140 A GIR-25. MA 375 _______ MA CIR-8310 CIR-19,21 FQ IR.90 22----______-- ---- o,Wheal,, R$'of LAYOUT QF _ --°' EQUIPMENT TO BE DETERMINED ' Cz 0 i r , O +I LAB WORK AREA Q O I m CO 0 0 0. ui c 0 CIR-14,16 CL AD ® r E U SECURE >. OFFICE STORAGE i a FLOWER RM m M —_ (D o f6 U C:)z m o O li BREAM RM o a)03 O C7 i) t Icc LOBBY JAN > LID X 00 0 O OJ o o O O W a • Electrical Plan j ELECTRICAL PLAN 1 SCALE: 1/4'r=1r-0r' E 1 E— m C 141m IIs + n As 0 ad 240V/208V BUCK + TRANSFORMER FOR RTU A MAKE-UP AIR + + + k + r + r + FAULT CURRENT CALCULATIONS: 400A MAIN PANEL TO TRANSFORMER L2 PANEL TO MAIN PANEL CONDUIT TYPE: NONMAGNETIC FAULT CURRENT CALCULATION. (FROM BREAKER TO PANEL) PHASE CONDUCTOR SIZE: 600 KCMIL MDP TO XFMR AVAILABLE FAULT CURRENT. 7,395.81 #CONDUCTORS/PHASE: 1 TRANSFORMER IMPEDANCE%: 4.1% SUB PANEL TO MDP FAULT CURRENT: 4,898.12 TRANSFORMER RATING 4KVAj: 125 CONDUCTOR LENGTH F j: 48 AVAIL FC Q EQUIPME 7,395.81 VOLTAGE: 3 PHASE 120/208V PHASE CONDUCTORS: 3 SINGLE CONDUCTORS PER PHASE RACEWAY: STEEL CONDUCTOR SIZE: 2 AWG # CONDUCTORS PER PHASE: 1 XFMR IMPEDANCE: 4.1% CONDUCTOR LENGTH: 61 FT XFMR RATING: 125KVA SERVICE PANEL: L2 200A 3PH MATERIALS SHALL BE LISTED BY UL (OR SIMILER AGENCY) AND CONFORM WITH NEMAANSI AND IEEE RACEWAYS ELECROMETALLIC TUBINGEMT THIN WALL PIPE GALVANIZED, THREADLESS. FLEXIBLE ALUMINUM COND UT: TANDARD WALL OUTLET BOXES 4" SQUARE WITH APPROPRIATE MUD RING. NEW WIRE WILL BE #12 THHN SOLID FEEDING 120V RECEPTACLES ALL OTHER COMPONANTS PER THE MANUFACTURERS SPECIFICATIONS LIGHTING WITHIN THE WAREHOUSE IS EXISTING BOOTH REQUIREMENTS' ONE SINGLE PHASE 208V 20A CIRCUIT ADD ONE 20 AMP CIRCUIT TO THE EXITING 200 AMP L2 SUB PANEL AN ADDITIONAL CIRCUIT WILL BE RUN TO THE MAKE UP AIR UNIT UTILIZING A STEP-DOWN TRANSFORMER FROM 240V 3P TO 208V. 3P. SEE SPEC $HEFT FOR FEDERAL TRANSFQRME INSIDE LIGHTING CLASS 1 DIVISION 1 EMERGENCY LIGHTING ALL PENITRATIONS INTO THE BOOTH MUST BE SEALED FORA 1 HOUR RATING CONTROL BOX UL FILE NO. E193676 POWER REQUIREMENTS 208-240VAC 1 P 20A MAIN SUPPLY 120/208V 1 PH 60 HZ 15A LARGEST LOAD 6.A MAIN DISCONNECT RATING -32A SCCR 1OKA OVERCURRENT PROTECTION 20A ELECTRIC MOTOR FOR HAZARDOUS LOCATIONS INTAKE AND EXHAUST FAN MOTORS HP.5 VOLTS 230/460 AMPS 1.6/.8 RPM 1735 PI TOTAL OF 2 UNITS THE CONTROL BOX HAS A VFD INSTALLED CONVERTING SINGLE PHASE TO THREE PHASE THE MOTORS ARE POWERED FROM THE CONTROL PANEL EXISTING LIGHTING FOR THE BOOTH IS 4' LED EXTERIOR GLOBE LIGHT IS LED BOTH IN EXPLOSION PROOF FIXTURES CORKEN RECOVERY PUMP -MEP XT70 HUBER-HEATING CIRCULATOR W/PRESSURE PUMP TAEEVN TECH MINI AIR COOLED CHILLER TOTAL OF 3 UNITS W +�+ +; + YY Y'+ 'v Technical Data Sheet Catalog No. KlXGF16-2 FEDERAL/PACIFIC wiin no aagremaoe PRIMARY HS�I H3 12 M OR xa "to u xI '£Cp10NH am r- 1 4b;I Leard 10 0 ;1 m 10 �a MIT ONline NO: 05A1460 Ed M down :nTHAIas nMI, Ad tu Meets 10 aR 431(2016) Efficiency 0p17[le IdeNanian m,grtwA For reference only Dry Type T2nsformer General Purl a Subject to change wigout noriR + + + C PHASE HIS,, LEG PLACARD LL NEL + + + NOTE FIYVAL ELECTAICAL� + INSPECTION SHALL INCLUDEA REVIEW OF BREAKERS IN THIS PANEL AND BREAKERS DEEMED BY + THE INSPECTOR TO BE NON- �+ -CONFORMING SHALL BE REPLACED + T + PRIOR iTO C.O. + # All Breakers in this panel shall be compliant with article 240.85 of the 2020 NEC 400 AMP MAIN PANEL (DELTA TRANSFORMER HIGH LEG C) CKT TRIP VOLTS AMPS CONDUIT GRD WIRE PH HE DESCRIPTION:KT TRIP VOLTS AMPS CONDUIT GRD cl,araam,eno CKT aanF AWG AWG Maine 1 AN ARTS And HE baeand .e 4xme m.mNa¢e.+M 'RIERRIF ESA 1 Makade,Naw,sx and IEEE MOSERM mTary 1=240V ,s ani M MONIMAlnM NEMA 31 1 20 208/240 15 11A � 12 1 ao Sentlpry, Issid/ I.R.A.S. PARE 12 3 2.5 Is .11 wend. Wal innefle SAMIeme �F m,dM copper Andelanandids. 12 1 Temp Rise 115.0FIAT emm. v ANSI as . RTU #2 he 9uentry MHz CAPTIVE AIR RTU TRANSFORMER m Taps None Alsop listings SPAR ESS No 20 Inwlatim 181 Line In lite l@LEON 161A 14 W theM, N/A Line In knatll@EWY am 12 WNI Mc a Wilt -in 230 16 1/2" 12 12 BREAKER 16 200 LOW lSaaontlaryl®L6V 1150P 3 SUB PANEL L1 We t(ftl 50 BREAKER 17 200 SouM(M) w LOW lsemntlarv) a 3A' 61 am r- 1 4b;I Leard 10 0 ;1 m 10 �a MIT ONline NO: 05A1460 Ed M down :nTHAIas nMI, Ad tu Meets 10 aR 431(2016) Efficiency 0p17[le IdeNanian m,grtwA For reference only Dry Type T2nsformer General Purl a Subject to change wigout noriR + + + C PHASE HIS,, LEG PLACARD LL NEL + + + NOTE FIYVAL ELECTAICAL� + INSPECTION SHALL INCLUDEA REVIEW OF BREAKERS IN THIS PANEL AND BREAKERS DEEMED BY + THE INSPECTOR TO BE NON- �+ -CONFORMING SHALL BE REPLACED + T + PRIOR iTO C.O. + # All Breakers in this panel shall be compliant with article 240.85 of the 2020 NEC 400 AMP MAIN PANEL (DELTA TRANSFORMER HIGH LEG C) CKT TRIP VOLTS AMPS CONDUIT GRD WIRE PH HE DESCRIPTION:KT TRIP VOLTS AMPS CONDUIT GRD WIRE PH HE DESCRIPTION CKT TRIP VOLTS AMPS CONDUIT AWG AWG PH HE DESCRIPTION AWG AWG 'RIERRIF 100 120/240100 1-1/4 #8 #3 IF SUB PANEL 50 120/240 50 3/4 10 8 3 RTU#1 1 20 208/240 15 11A 4 12 1 BOOTH MAIN CONTROL PANEL 2 5 PARE 12 3 2.5 CAPTIVE AIR RTU TRANSFORMER �F 3 7 PARE 12 1 BOOTH MAIN CONTROL PANEL 50 120/240 50 3/4 10 8 3 RTU #2 9 SPARE CAPTIVE AIR RTU TRANSFORMER m 5 20 SPARE 11 SPAR 12 20 13 SPARE N C 14 SPARE 20 230 16 1/2" 12 12 CKT TRIP VOLTS AMP CONDIT GRD WIRE PH DESCRIPTION 230 16 1/2" 12 12 BREAKER 16 200 120/240 200 2 4 3/0 3 SUB PANEL L1 9 20 BREAKER 17 200 120/240 200 2 4 3/0 3 SUB PANEL L2 20 i BREAKER 18 200 120/240 200 2 4 3/0 3 SUB PANELAC 11 L2 PANEL SPECIFICATIONS RATED FOR 200 AMPS, EATON, 3PHASE, 120/208V, MLO ON A DELTA SYSTEM. (FEED WITH A 125AMP BREAKER) PANEL L2 CKT TRIP VOLTS AMPS CONDUIT GRD WIRE PH HE DESCRIPTION CKT TRIP VOLTS AMPS CONDUIT GRD WIRE PH HE DESCRIPTION 'RIERRIF THHN THHN THHN THHN 1 20 208/240 15 11A 12 12 1 BOOTH MAIN CONTROL PANEL 2 20 208 15 1/1 12 12 3 2.5 CAPTIVE AIR RTU TRANSFORMER �F 3 20 208/240 15 1f'12 12 1 BOOTH MAIN CONTROL PANEL 20 0 CAPTIVE AIR RTU TRANSFORMER m 5 20 SPARE E 6 20 N C Q 7 20 230 16 1/2" 12 12 HUBER HEATER 120 230 16 1/2" 12 12 HUBER HEATER U 9 20 110 20 i a 11 20 SPARE _ N 12 20 SPARE As U RERE00 z 13 20 SPARE m LL —00m 14 20 SPARE --) O 15 20 SPARE t U mW 16 20 SPARE (� i U �g 17 20 SPARE U X C).r. 18 20 SPARE LU TY �: 12 19 20 230 15 1/2" 12 121 3 CORKEN RECOVERY PUMP 20 20 230 VERIFY 1/2" 10 10 1 TAEEVN MINI COOLER 21 22 20 23 20 SPARE 24 20 SPARE 2� 20 230 VERIFY 1/2" 10 10 1 TAEEVN MINI COOLER 26 20 EXISTING AIR COMPRESSOR N. WALL E. OF HALL DOORS 27 20 28 20 EXISTING AIR COMPRESSOR N. WALL E. OF HALL DOORS 29 BLANK 30 BLANK 31 40 230 32 3/4 10 8 1 WIPE FILM EVAPORATOR EXISTING 3i2 20 EXISTING 4 FLEX IN SOUTH LAB WEST WALL 33 40 WIPE FILM EVAPORATOR EXISTING 34 20 EXISTING 4 PLEX IN SOUTH LAB WEST WALL 35 BLANK 36 BLANK 37 20 EXISTING 4 FLEX N SOUTH LAB WEST WAL 4U 20 230 VERIFY 1/2" 10 10 1 TAEEVN MINI COOLER 39 20 120 16 1/2" 12 12 SERVICE OULTETIFO RTU 41 BLANK 42 BLANK ELECTRICAL PANELS & FAULT CURRENT 4 1 5 1 6 io Anther Architects, PLLC Architecture + Engineering 3727 Candia Drive Punta Gorda FL 33950 800-243-0528 734-709-7297 gburgh@gmail.com 3TUARTGRI BURGH ARC 004061 THE MIAMI OF THE CONTRACH ANSI IS TO I ALL ANSI EIRSAMMARY FORT THE FROPER EMED(i AND OWKTIT� OF THE wI on THE CONTRACTOR THE CONMEACT �MNTS ME �w�� ME EAST Is Me FASTARMANTAY AMERED TONS THEM AS Alone INEOREARRY REWA� &E, REAL, ITHAT CIARME TO CONTENT sm OR 'HE ISFARMI MMM Me THIS REAT EST 'IT METTIONTO CHANGETS TO CONTRAST SAM OR HAS UNUESS Electrical Panels E2 0 'RIERRIF Q �F 0 0 m E O U N C Q N CL TI AD U OL i a Saii-as M _ N M m As U RERE00 z o O m LL —00m Y --) O Oai C7 i) t U mW I cc (� i U �g ISO c� N U X C).r. O 0 LU TY �: 12 Electrical Panels E2 Flu I] C Fal Nt1RK1 kkdnEyn Arvada Fire Protection District Fire Marshal's Office' 7903 Allison Way - Arvada, CO 80005 Main 303-424-3012 - Fax 303-432-7995 www.arvadaffre.com Ocoul M Name: Loud Labs, LLC COMractor: Shane Mendenhall, Owner Interior Sprinkler Systems. Inc (970)302.377] Address: 4805-0845 Van Gordon Inspection Data: 511112021 Street Wheat Ridge, CO SM33 Job Number: 210420002/ Inepectlon7ype: Plan Revtaw-Dry Chemical Suppression System Job Description: New Extraction Booth Inspected By: John Hussey 303424-3012 lohn.huswy@arvadafim.mm Plan Type Original Pre Fall N/A Plan Review Floor 1 Cerlllrnu kj D [] 1001 Prelect -Ther WoWng comments ere specft ro life plans submitted, all Comments shall be SpecMC addressed In writing to Me AFPD: Comments 1. ASMI inspection Including Nnc mal lest dN system and AFPD approval shall be required. [al ❑ [] 1002 General -T "p)ensheybynmvlewedm Me20i8lnNmWnel Fim CWeandmbmnced Comments Mandates as adopted. -These Commenh, approved plans ant posted mug be Evil to receive any Fire Dishkllnspecfl0ns. Devletlonm the app pbnsmayrequlre msuDmnlg W mvkw and appmvalln orderhbrany Ndher Mspec s to be performed NO inspedans still occurw OFire District appmvedplans, Comments andpermd card available off -To schedule inspections please logon m the Mobile Eyes Cwtreclor P ft Portal at MlplNiww.m l"c s c PA Model All attempts will be made b schedule en inspection Cor Me date and time requested. Inspections ala be scheduled based on inapedor aveilabJiy end will be scheduled wiNin 24-08 hours ofMe intended mgwsf -Inspections meyreveal canecrrons necessary M bring all woririnb Compliermre with eppimebb codes and standards Ixl II I] 1003 cond;tions of Approval Status: Approved With Conditions Plans maintained to AFPD are reviewed for compliance per the fire code as adopted and/or amended and any applicable State Of Colorado Requirements. The submitted plans are not reviewed to specific individual aperSystem Design PPage s1n *... r REV 9 PC( 70ABC with 4 nosily CYLINDER fT1 /Tz NNA "..... l NOZZLE Le IS MaxM (Cwwnumm ULM 3197 CW32 September t, MON Inter Size Nouleu0uently Noule UyN Elbows LYI type Piping Sectlon $Ire MWmum Minimum PCIJOABC 4 NV WA or NN3W (.yllMerm T1 Tl mT2 1In. 1'i; M1. (S.S m) 2 MIS Up Noule 9/d lit. BN. (2A m) 2 Mulmum cylinder Size Noule Quantity M=e Type Piping 9aMbn Size Mulmum Mmm=mumPCI-]OABC 0 3-NVWAorNV-SWLyllnMrmTt 11n. bR vM 101 (12.2 m) NV -Pt (see Note 5) NV -UF NV-DP2 T1 mT2 tin. ten(fi.6 m) z T21D Nozne 3141n. Sol 2 61111 MzWsEya project specifications. This report is intended m provide the subminer with the status of plan appmval, and any mmments that may require further informationverification or action for approval of plans. All plans may be subject to field inspection and/or testing for final approval prior ro sign off on a Certificate Of Occupancy or Ceftifinte of Inspection. The approval of plana constitutes a permit to Commence workwhere required by the &e code, and is subject to the conditions n may be noted in the comment section in the attached plan review report Response to this review report as necessary along with the permit fee payment will be required prior to any field inspections. r Chapar 3 -System NWgn Page 3.1] REV 1 P0140ABC calm 4 nozzles (CoMnuad) their kW Na If wq NVDR2 must M bcete] on dalxn Tax to rook Only. NOTE: 1. ThOn Ilmhetkne apply to PCIVOABC using four NV WA or IN My noulea, 2. System typing must be balanced. Balanced piping is that In which the diMmnn between me ambient Men pips lerpm krona l to mssk and the longest =fuel type length from Tt m nozzle does cot exceed 10% Of the longest acWel type length from Tt m nozzle. T2 to nozzle on Me same brown mulct not exceed 10%0l Men Odoc ner number and type G lMngs for all last tee fo nozzle section must be Equal. 3. A Meln/Rnerver Swmg Check Vave, Pan No. 41]]88, may be located "e n the cylinder and T1. 4, All systema protecting vanlck paint Spray Moths require a baory pre-set time delay 5. Mon using an Nii hei me Iwo lergea discharger orff es in the mule baby coon be Imemoned Dena m IM lora t dimension o1 TO hazard befog pmbmed. s S. Mavimum height of nozzle from ben of tank to nozzle - 20 X 1a1 m). ULExeu7 cE 9eplemdw 1, May Maximum 4npM J2: Cylinder Sim Nozzle Ouently NOuls Type PlDlnp Season 8W Mekmum PCI-]OABC 4 2 -NV -WA or NPSW CyYneumTl 11n. 40R enm2 0l any (122 m) ro emanon or Nv.P1 or rvv.opz (Sae Note s) T1 m12 11n. 1B n. (5.d. m) linfeR(5.5m) T2mNoule y41ngR(2Jm) 32A` to Npm'6 Ya lit. Bn. 12.]m) 2 1 2 3 y cnnrerl -DanrW tyy Page 1-1 REV 2 n CHAPTERI General Information INTRODUCTION PYRO.CXEM WM1bM Paint spay Bn(tl automate dry eneMeel lire suppression system Is of ma pre-enpinearN We n eellnea by the NFPA 9(eNeM be Ory Chemical EMlrgul[M1ing Systeme, NFPA-9. The mfirgulehlnp units OeacnOetl In this manual are Intended to De Inarellee, Inaped etl, and maintained in azmraenn with NFPA-b. UmIMHcna ealeilee In 1111s manual have been eelebllsllea NwugM1 eklBneiw rebtlrp by Untlerwrnere Laboratories, Inc. lnamlletion and nonce of the ayBmm moat nnbrm to IM limilcibna III 'm (M1ia manual and De OeROrmetl M an PrathOrizea PYR0.LHEM dealer. no PYfl0.CHEM Vehitle Pont Booty Syalem Nlllzea a morgammonlum Phosphate based dry enemlttl egnt (Bpnlllcelly designed 10 aupPraaa nNOnecrou¢ sella, liquid, gu or electrical fired). The system pmvMeB mecM1enkel or electrical aummatle acluallon [M nn De manually adualM mmagn a remore memamul pull arenon. Upon actuation, the [yalam m=Wages a Pre -determined amount of Eqem to the hazard area The anurdmsn of wet and Power to the n.wa eree Is required upon ayarem acwenon. Exhaust Mole) in m0 vennlanon system must be ena on peer to ayarem discharge to allow IM Prenr cenlratbn of Vent to Wild up In to Mxem area. The PYRDCHEM PoM1lma Paint Booty System is anIBOM to eccwnmeeeU a merWemry hclory pre-nf time easy Thle time delay Is roOpirea based on m0 UL 1254 rompnenn leenne, Ip SCCaJ9 S TEMPERATURE LIMITATIONS _ The opennrg temperature range of the PYRD-0HEM Venkla Paint Boom System is 32 °F (0'C) minlmum to 120 °F 149 SCI mmlmum. UL LISTING The PYR0.CHEM WM1lde Paint Booth Industrial Fire Suppression System has been ledetl to the UL Standard ro! Prn-Fran weretl Dry fn pB +BOB ena uetab M u:merwmere L.Mremnea. Inc. •CITY OF NEW YORK APPROVAL The PYfl0.CXEM WM1lda Palo[ Spray Boots Fire Suppreulon System is approved py the Llty 01 Naw YOM Farre DBpenmem per Cennictle of Approyl No. 5644 under the mlbwirg wnallloM: 1. Prior to ;narelletion, plana moat be flied with and accepted by New York CIO Department of BuiltlinBa. MOHlonelly, a cop) M New Yol%Ciy Department of Buildings docketed pone aM1ell be baummea to the Fire Department Cor rwlew ma approval. 2. The system shall be;nablletl, nno0lcally Inepedea.leabtl and oNawlae meinbinetl In aroraer,ce with SeNone 901, 804,1.1 and BC/A 01 New Yolk Clry Flre Lase, NFPA 17 and ITll applicable New York City ConcbucHon Caae/Fire Cala. EIeMrIW wirinp Snell be In STREET. dance with the New York City Electrical LNO. 3. At leas) once a monis, an inepOdbn shall pa contlumaa by a Irairree and knowletlpeede Person to ueya that the system is In Broe working order. 4. The Im011atlon, maintenance pmceaurea, and Ilmileaona aulaa In this manual mun be wm- pnM an. r� uLEx sag] cFm: February 1.2010 cMder 3 -Strom Design Page the *... r REV 3 •g. Nozzle Coverages • 1 Nv-wA.M rWsw nomas ten be pats Ior pewm, n. w:me=now Poremn.Tna nozzle mylmpm gip=moanona mon be blbye. a Pont IOg dimensions 41n[h minimum a 4n IM mavlmYm. a NOiale oneel Is the mwlmum diMer:Ce Imre IM gp G to Mme m MB doaul e¢a of to pretezMn zone e BkMle nozzle appllmMn on a PCE 16paC p we IpIIle yWI4Xon m a PCI-RSWBC only. Nett: n Me mnwae Sud If pros(w Men 46 in, in tliemabr o 12 n pMmMn, no ON al mol nqV pmfedion un be unlizeo. uLFx 3197 cFYz32 Febuery 1, 2C10 February Pmlecllen Noula b[etlen �I IeneMoula SpadOnllen wltRin Noub Noule ProlxXan Nozzle L W Hl Mealmum Protection Zone OnrN OeoMatlen Wad Areal NV -WA Seo Table 3-0 Volume 1920 cu X 2 X mevimum D io 6 In. VeNcel I IITIRRE pne 160 p X on center rolnlinp down Diagonal 18.86 ft ceapn viae) coO Wad Aroal NKSW Sn Table SIA Volume 192D tisk 2Xmuimum DmBIn. Vankel N C Area taD p x on timer po^ming sown Diagonal 12.B X (sato eltle) ( fine in MID U Na rermea mrne0 � ca eiremon of I a mw) BacksreM1 NMP1 IX 14h 12X Vdume B)2 cuh shonnf el0e�nnrer Dm610. Wrticel PMnum n CLL C:) Area 66 p X O O m Side 14X Longest side -3 Inch BUY O O� (7 ON comer plan aide) tj Pont LED NKPi SIN 1B X 20 n Volume 128D _Wft SMbat sitltrnnler D m R W. Vehicle Plenums L(7 � � grad 84 p X W Side 18 X lurga¢i eme3 ircX off nnrer (can aide) PX NV -P1 24 ft 4 X 4 fl Volume 38{ cuh Snonnt vDa-nnrer 0 m S In. Wrticel 10pnDn 1) Area 98pX 8me Ian Longest eieo-cenrer Pit NIP2 4h 4h volume 904 Cun 6MneM aloe -center 21oS lit. Horizomal (Option 2) pros 96 p n alae z4 n Height center UMar FlOCr NVUF 10 R 14 R { X Polume 896 cu X Shortest side -center D m 01n. KNctl Plenum Area 224 aq R S;W t6R Longntaldennrer EMreuet N4DP2 9h 9n 24X Vdume 216wtt 8nonntaWe (croce Om01n. XDrImmM Cor Dud Area p p X aedion) - tinier MrlmMel tlucla Sin 9 k Longest rise Icroes IRpund DDM .aeticn) Cor 9 h 10 In, diameter) yL• reMnl MW duchy Eannet N.DCT 12XPerlmerer or Leym- [soler Db81n. HDrlmMel Cor Duda snmin. aiMnM.r eµP wkm-came, Mazonw m,de 26 h Mnpin Vertical tar wmeM apda Inter Size Nouleu0uently Noule UyN Elbows LYI type Piping Sectlon $Ire MWmum Minimum PCIJOABC 4 NV WA or NN3W (.yllMerm T1 Tl mT2 1In. 1'i; M1. (S.S m) 2 MIS Up Noule 9/d lit. BN. (2A m) 2 Mulmum cylinder Size Noule Quantity M=e Type Piping 9aMbn Size Mulmum Mmm=mumPCI-]OABC 0 3-NVWAorNV-SWLyllnMrmTt 11n. bR vM 101 (12.2 m) NV -Pt (see Note 5) NV -UF NV-DP2 T1 mT2 tin. ten(fi.6 m) z T21D Nozne 3141n. Sol 2 61111 MzWsEya project specifications. This report is intended m provide the subminer with the status of plan appmval, and any mmments that may require further informationverification or action for approval of plans. All plans may be subject to field inspection and/or testing for final approval prior ro sign off on a Certificate Of Occupancy or Ceftifinte of Inspection. The approval of plana constitutes a permit to Commence workwhere required by the &e code, and is subject to the conditions n may be noted in the comment section in the attached plan review report Response to this review report as necessary along with the permit fee payment will be required prior to any field inspections. r Chapar 3 -System NWgn Page 3.1] REV 1 P0140ABC calm 4 nozzles (CoMnuad) their kW Na If wq NVDR2 must M bcete] on dalxn Tax to rook Only. NOTE: 1. ThOn Ilmhetkne apply to PCIVOABC using four NV WA or IN My noulea, 2. System typing must be balanced. Balanced piping is that In which the diMmnn between me ambient Men pips lerpm krona l to mssk and the longest =fuel type length from Tt m nozzle does cot exceed 10% Of the longest acWel type length from Tt m nozzle. T2 to nozzle on Me same brown mulct not exceed 10%0l Men Odoc ner number and type G lMngs for all last tee fo nozzle section must be Equal. 3. A Meln/Rnerver Swmg Check Vave, Pan No. 41]]88, may be located "e n the cylinder and T1. 4, All systema protecting vanlck paint Spray Moths require a baory pre-set time delay 5. Mon using an Nii hei me Iwo lergea discharger orff es in the mule baby coon be Imemoned Dena m IM lora t dimension o1 TO hazard befog pmbmed. s S. Mavimum height of nozzle from ben of tank to nozzle - 20 X 1a1 m). ULExeu7 cE 9eplemdw 1, May Maximum 4npM J2: Cylinder Sim Nozzle Ouently NOuls Type PlDlnp Season 8W Mekmum PCI-]OABC 4 2 -NV -WA or NPSW CyYneumTl 11n. 40R enm2 0l any (122 m) ro emanon or Nv.P1 or rvv.opz (Sae Note s) T1 m12 11n. 1B n. (5.d. m) linfeR(5.5m) T2mNoule y41ngR(2Jm) 32A` to Npm'6 Ya lit. Bn. 12.]m) 2 1 2 3 y cnnrerl -DanrW tyy Page 1-1 REV 2 n CHAPTERI General Information INTRODUCTION PYRO.CXEM WM1bM Paint spay Bn(tl automate dry eneMeel lire suppression system Is of ma pre-enpinearN We n eellnea by the NFPA 9(eNeM be Ory Chemical EMlrgul[M1ing Systeme, NFPA-9. The mfirgulehlnp units OeacnOetl In this manual are Intended to De Inarellee, Inaped etl, and maintained in azmraenn with NFPA-b. UmIMHcna ealeilee In 1111s manual have been eelebllsllea NwugM1 eklBneiw rebtlrp by Untlerwrnere Laboratories, Inc. lnamlletion and nonce of the ayBmm moat nnbrm to IM limilcibna III 'm (M1ia manual and De OeROrmetl M an PrathOrizea PYR0.LHEM dealer. no PYfl0.CHEM Vehitle Pont Booty Syalem Nlllzea a morgammonlum Phosphate based dry enemlttl egnt (Bpnlllcelly designed 10 aupPraaa nNOnecrou¢ sella, liquid, gu or electrical fired). The system pmvMeB mecM1enkel or electrical aummatle acluallon [M nn De manually adualM mmagn a remore memamul pull arenon. Upon actuation, the [yalam m=Wages a Pre -determined amount of Eqem to the hazard area The anurdmsn of wet and Power to the n.wa eree Is required upon ayarem acwenon. Exhaust Mole) in m0 vennlanon system must be ena on peer to ayarem discharge to allow IM Prenr cenlratbn of Vent to Wild up In to Mxem area. The PYRDCHEM PoM1lma Paint Booty System is anIBOM to eccwnmeeeU a merWemry hclory pre-nf time easy Thle time delay Is roOpirea based on m0 UL 1254 rompnenn leenne, Ip SCCaJ9 S TEMPERATURE LIMITATIONS _ The opennrg temperature range of the PYRD-0HEM Venkla Paint Boom System is 32 °F (0'C) minlmum to 120 °F 149 SCI mmlmum. UL LISTING The PYR0.CHEM WM1lde Paint Booth Industrial Fire Suppression System has been ledetl to the UL Standard ro! Prn-Fran weretl Dry fn pB +BOB ena uetab M u:merwmere L.Mremnea. Inc. •CITY OF NEW YORK APPROVAL The PYfl0.CXEM WM1lda Palo[ Spray Boots Fire Suppreulon System is approved py the Llty 01 Naw YOM Farre DBpenmem per Cennictle of Approyl No. 5644 under the mlbwirg wnallloM: 1. Prior to ;narelletion, plana moat be flied with and accepted by New York CIO Department of BuiltlinBa. MOHlonelly, a cop) M New Yol%Ciy Department of Buildings docketed pone aM1ell be baummea to the Fire Department Cor rwlew ma approval. 2. The system shall be;nablletl, nno0lcally Inepedea.leabtl and oNawlae meinbinetl In aroraer,ce with SeNone 901, 804,1.1 and BC/A 01 New Yolk Clry Flre Lase, NFPA 17 and ITll applicable New York City ConcbucHon Caae/Fire Cala. EIeMrIW wirinp Snell be In STREET. dance with the New York City Electrical LNO. 3. At leas) once a monis, an inepOdbn shall pa contlumaa by a Irairree and knowletlpeede Person to ueya that the system is In Broe working order. 4. The Im011atlon, maintenance pmceaurea, and Ilmileaona aulaa In this manual mun be wm- pnM an. r� uLEx sag] cFm: February 1.2010 cMder 3 -Strom Design Page the *... r REV 3 •g. Nozzle Coverages • 1 Nv-wA.M rWsw nomas ten be pats Ior pewm, n. w:me=now Poremn.Tna nozzle mylmpm gip=moanona mon be blbye. a Pont IOg dimensions 41n[h minimum a 4n IM mavlmYm. a NOiale oneel Is the mwlmum diMer:Ce Imre IM gp G to Mme m MB doaul e¢a of to pretezMn zone e BkMle nozzle appllmMn on a PCE 16paC p we IpIIle yWI4Xon m a PCI-RSWBC only. Nett: n Me mnwae Sud If pros(w Men 46 in, in tliemabr o 12 n pMmMn, no ON al mol nqV pmfedion un be unlizeo. uLFx 3197 cFYz32 Febuery 1, 2C10 February Pmlecllen Noula b[etlen �I IeneMoula SpadOnllen wltRin Noub Noule ProlxXan Nozzle L W Hl Mealmum Protection Zone OnrN OeoMatlen Wad Areal NV -WA Seo Table 3-0 Volume 1920 cu X 2 X mevimum D io 6 In. VeNcel Mulmum cylinder Size Noule Quantity M=e Type Piping 9aMbn Size Mulmum Mmm=mumPCI-]OABC 0 3-NVWAorNV-SWLyllnMrmTt 11n. bR vM 101 (12.2 m) NV -Pt (see Note 5) NV -UF NV-DP2 T1 mT2 tin. ten(fi.6 m) z T21D Nozne 3141n. Sol 2 61111 MzWsEya project specifications. This report is intended m provide the subminer with the status of plan appmval, and any mmments that may require further informationverification or action for approval of plans. All plans may be subject to field inspection and/or testing for final approval prior ro sign off on a Certificate Of Occupancy or Ceftifinte of Inspection. The approval of plana constitutes a permit to Commence workwhere required by the &e code, and is subject to the conditions n may be noted in the comment section in the attached plan review report Response to this review report as necessary along with the permit fee payment will be required prior to any field inspections. r Chapar 3 -System NWgn Page 3.1] REV 1 P0140ABC calm 4 nozzles (CoMnuad) their kW Na If wq NVDR2 must M bcete] on dalxn Tax to rook Only. NOTE: 1. ThOn Ilmhetkne apply to PCIVOABC using four NV WA or IN My noulea, 2. System typing must be balanced. Balanced piping is that In which the diMmnn between me ambient Men pips lerpm krona l to mssk and the longest =fuel type length from Tt m nozzle does cot exceed 10% Of the longest acWel type length from Tt m nozzle. T2 to nozzle on Me same brown mulct not exceed 10%0l Men Odoc ner number and type G lMngs for all last tee fo nozzle section must be Equal. 3. A Meln/Rnerver Swmg Check Vave, Pan No. 41]]88, may be located "e n the cylinder and T1. 4, All systema protecting vanlck paint Spray Moths require a baory pre-set time delay 5. Mon using an Nii hei me Iwo lergea discharger orff es in the mule baby coon be Imemoned Dena m IM lora t dimension o1 TO hazard befog pmbmed. s S. Mavimum height of nozzle from ben of tank to nozzle - 20 X 1a1 m). ULExeu7 cE 9eplemdw 1, May Maximum 4npM J2: Cylinder Sim Nozzle Ouently NOuls Type PlDlnp Season 8W Mekmum PCI-]OABC 4 2 -NV -WA or NPSW CyYneumTl 11n. 40R enm2 0l any (122 m) ro emanon or Nv.P1 or rvv.opz (Sae Note s) T1 m12 11n. 1B n. (5.d. m) linfeR(5.5m) T2mNoule y41ngR(2Jm) 32A` to Npm'6 Ya lit. Bn. 12.]m) 2 1 2 3 y cnnrerl -DanrW tyy Page 1-1 REV 2 n CHAPTERI General Information INTRODUCTION PYRO.CXEM WM1bM Paint spay Bn(tl automate dry eneMeel lire suppression system Is of ma pre-enpinearN We n eellnea by the NFPA 9(eNeM be Ory Chemical EMlrgul[M1ing Systeme, NFPA-9. The mfirgulehlnp units OeacnOetl In this manual are Intended to De Inarellee, Inaped etl, and maintained in azmraenn with NFPA-b. UmIMHcna ealeilee In 1111s manual have been eelebllsllea NwugM1 eklBneiw rebtlrp by Untlerwrnere Laboratories, Inc. lnamlletion and nonce of the ayBmm moat nnbrm to IM limilcibna III 'm (M1ia manual and De OeROrmetl M an PrathOrizea PYR0.LHEM dealer. no PYfl0.CHEM Vehitle Pont Booty Syalem Nlllzea a morgammonlum Phosphate based dry enemlttl egnt (Bpnlllcelly designed 10 aupPraaa nNOnecrou¢ sella, liquid, gu or electrical fired). The system pmvMeB mecM1enkel or electrical aummatle acluallon [M nn De manually adualM mmagn a remore memamul pull arenon. Upon actuation, the [yalam m=Wages a Pre -determined amount of Eqem to the hazard area The anurdmsn of wet and Power to the n.wa eree Is required upon ayarem acwenon. Exhaust Mole) in m0 vennlanon system must be ena on peer to ayarem discharge to allow IM Prenr cenlratbn of Vent to Wild up In to Mxem area. The PYRDCHEM PoM1lma Paint Booty System is anIBOM to eccwnmeeeU a merWemry hclory pre-nf time easy Thle time delay Is roOpirea based on m0 UL 1254 rompnenn leenne, Ip SCCaJ9 S TEMPERATURE LIMITATIONS _ The opennrg temperature range of the PYRD-0HEM Venkla Paint Boom System is 32 °F (0'C) minlmum to 120 °F 149 SCI mmlmum. UL LISTING The PYR0.CHEM WM1lde Paint Booth Industrial Fire Suppression System has been ledetl to the UL Standard ro! Prn-Fran weretl Dry fn pB +BOB ena uetab M u:merwmere L.Mremnea. Inc. •CITY OF NEW YORK APPROVAL The PYfl0.CXEM WM1lda Palo[ Spray Boots Fire Suppreulon System is approved py the Llty 01 Naw YOM Farre DBpenmem per Cennictle of Approyl No. 5644 under the mlbwirg wnallloM: 1. Prior to ;narelletion, plana moat be flied with and accepted by New York CIO Department of BuiltlinBa. MOHlonelly, a cop) M New Yol%Ciy Department of Buildings docketed pone aM1ell be baummea to the Fire Department Cor rwlew ma approval. 2. The system shall be;nablletl, nno0lcally Inepedea.leabtl and oNawlae meinbinetl In aroraer,ce with SeNone 901, 804,1.1 and BC/A 01 New Yolk Clry Flre Lase, NFPA 17 and ITll applicable New York City ConcbucHon Caae/Fire Cala. EIeMrIW wirinp Snell be In STREET. dance with the New York City Electrical LNO. 3. At leas) once a monis, an inepOdbn shall pa contlumaa by a Irairree and knowletlpeede Person to ueya that the system is In Broe working order. 4. The Im011atlon, maintenance pmceaurea, and Ilmileaona aulaa In this manual mun be wm- pnM an. r� uLEx sag] cFm: February 1.2010 cMder 3 -Strom Design Page the *... r REV 3 •g. Nozzle Coverages • 1 Nv-wA.M rWsw nomas ten be pats Ior pewm, n. w:me=now Poremn.Tna nozzle mylmpm gip=moanona mon be blbye. a Pont IOg dimensions 41n[h minimum a 4n IM mavlmYm. a NOiale oneel Is the mwlmum diMer:Ce Imre IM gp G to Mme m MB doaul e¢a of to pretezMn zone e BkMle nozzle appllmMn on a PCE 16paC p we IpIIle yWI4Xon m a PCI-RSWBC only. Nett: n Me mnwae Sud If pros(w Men 46 in, in tliemabr o 12 n pMmMn, no ON al mol nqV pmfedion un be unlizeo. uLFx 3197 cFYz32 Febuery 1, 2C10 February Pmlecllen Noula b[etlen �I IeneMoula SpadOnllen wltRin Noub Noule ProlxXan Nozzle L W Hl Mealmum Protection Zone OnrN OeoMatlen Wad Areal NV -WA Seo Table 3-0 Volume 1920 cu X 2 X mevimum D io 6 In. VeNcel I IITIRRE pne 160 p X on center rolnlinp down Diagonal 18.86 ft ceapn viae) coO Wad Aroal NKSW Sn Table SIA Volume 192D tisk 2Xmuimum DmBIn. Vankel N C Area taD p x on timer po^ming sown Diagonal 12.B X (sato eltle) ( fine in 61111 MzWsEya project specifications. This report is intended m provide the subminer with the status of plan appmval, and any mmments that may require further informationverification or action for approval of plans. All plans may be subject to field inspection and/or testing for final approval prior ro sign off on a Certificate Of Occupancy or Ceftifinte of Inspection. The approval of plana constitutes a permit to Commence workwhere required by the &e code, and is subject to the conditions n may be noted in the comment section in the attached plan review report Response to this review report as necessary along with the permit fee payment will be required prior to any field inspections. r Chapar 3 -System NWgn Page 3.1] REV 1 P0140ABC calm 4 nozzles (CoMnuad) their kW Na If wq NVDR2 must M bcete] on dalxn Tax to rook Only. NOTE: 1. ThOn Ilmhetkne apply to PCIVOABC using four NV WA or IN My noulea, 2. System typing must be balanced. Balanced piping is that In which the diMmnn between me ambient Men pips lerpm krona l to mssk and the longest =fuel type length from Tt m nozzle does cot exceed 10% Of the longest acWel type length from Tt m nozzle. T2 to nozzle on Me same brown mulct not exceed 10%0l Men Odoc ner number and type G lMngs for all last tee fo nozzle section must be Equal. 3. A Meln/Rnerver Swmg Check Vave, Pan No. 41]]88, may be located "e n the cylinder and T1. 4, All systema protecting vanlck paint Spray Moths require a baory pre-set time delay 5. Mon using an Nii hei me Iwo lergea discharger orff es in the mule baby coon be Imemoned Dena m IM lora t dimension o1 TO hazard befog pmbmed. s S. Mavimum height of nozzle from ben of tank to nozzle - 20 X 1a1 m). ULExeu7 cE 9eplemdw 1, May Maximum 4npM J2: Cylinder Sim Nozzle Ouently NOuls Type PlDlnp Season 8W Mekmum PCI-]OABC 4 2 -NV -WA or NPSW CyYneumTl 11n. 40R enm2 0l any (122 m) ro emanon or Nv.P1 or rvv.opz (Sae Note s) T1 m12 11n. 1B n. (5.d. m) linfeR(5.5m) T2mNoule y41ngR(2Jm) 32A` to Npm'6 Ya lit. Bn. 12.]m) 2 1 2 3 y cnnrerl -DanrW tyy Page 1-1 REV 2 n CHAPTERI General Information INTRODUCTION PYRO.CXEM WM1bM Paint spay Bn(tl automate dry eneMeel lire suppression system Is of ma pre-enpinearN We n eellnea by the NFPA 9(eNeM be Ory Chemical EMlrgul[M1ing Systeme, NFPA-9. The mfirgulehlnp units OeacnOetl In this manual are Intended to De Inarellee, Inaped etl, and maintained in azmraenn with NFPA-b. UmIMHcna ealeilee In 1111s manual have been eelebllsllea NwugM1 eklBneiw rebtlrp by Untlerwrnere Laboratories, Inc. lnamlletion and nonce of the ayBmm moat nnbrm to IM limilcibna III 'm (M1ia manual and De OeROrmetl M an PrathOrizea PYR0.LHEM dealer. no PYfl0.CHEM Vehitle Pont Booty Syalem Nlllzea a morgammonlum Phosphate based dry enemlttl egnt (Bpnlllcelly designed 10 aupPraaa nNOnecrou¢ sella, liquid, gu or electrical fired). The system pmvMeB mecM1enkel or electrical aummatle acluallon [M nn De manually adualM mmagn a remore memamul pull arenon. Upon actuation, the [yalam m=Wages a Pre -determined amount of Eqem to the hazard area The anurdmsn of wet and Power to the n.wa eree Is required upon ayarem acwenon. Exhaust Mole) in m0 vennlanon system must be ena on peer to ayarem discharge to allow IM Prenr cenlratbn of Vent to Wild up In to Mxem area. The PYRDCHEM PoM1lma Paint Booty System is anIBOM to eccwnmeeeU a merWemry hclory pre-nf time easy Thle time delay Is roOpirea based on m0 UL 1254 rompnenn leenne, Ip SCCaJ9 S TEMPERATURE LIMITATIONS _ The opennrg temperature range of the PYRD-0HEM Venkla Paint Boom System is 32 °F (0'C) minlmum to 120 °F 149 SCI mmlmum. UL LISTING The PYR0.CHEM WM1lde Paint Booth Industrial Fire Suppression System has been ledetl to the UL Standard ro! Prn-Fran weretl Dry fn pB +BOB ena uetab M u:merwmere L.Mremnea. Inc. •CITY OF NEW YORK APPROVAL The PYfl0.CXEM WM1lda Palo[ Spray Boots Fire Suppreulon System is approved py the Llty 01 Naw YOM Farre DBpenmem per Cennictle of Approyl No. 5644 under the mlbwirg wnallloM: 1. Prior to ;narelletion, plana moat be flied with and accepted by New York CIO Department of BuiltlinBa. MOHlonelly, a cop) M New Yol%Ciy Department of Buildings docketed pone aM1ell be baummea to the Fire Department Cor rwlew ma approval. 2. The system shall be;nablletl, nno0lcally Inepedea.leabtl and oNawlae meinbinetl In aroraer,ce with SeNone 901, 804,1.1 and BC/A 01 New Yolk Clry Flre Lase, NFPA 17 and ITll applicable New York City ConcbucHon Caae/Fire Cala. EIeMrIW wirinp Snell be In STREET. dance with the New York City Electrical LNO. 3. At leas) once a monis, an inepOdbn shall pa contlumaa by a Irairree and knowletlpeede Person to ueya that the system is In Broe working order. 4. The Im011atlon, maintenance pmceaurea, and Ilmileaona aulaa In this manual mun be wm- pnM an. r� uLEx sag] cFm: February 1.2010 cMder 3 -Strom Design Page the *... r REV 3 •g. Nozzle Coverages • 1 Nv-wA.M rWsw nomas ten be pats Ior pewm, n. w:me=now Poremn.Tna nozzle mylmpm gip=moanona mon be blbye. a Pont IOg dimensions 41n[h minimum a 4n IM mavlmYm. a NOiale oneel Is the mwlmum diMer:Ce Imre IM gp G to Mme m MB doaul e¢a of to pretezMn zone e BkMle nozzle appllmMn on a PCE 16paC p we IpIIle yWI4Xon m a PCI-RSWBC only. Nett: n Me mnwae Sud If pros(w Men 46 in, in tliemabr o 12 n pMmMn, no ON al mol nqV pmfedion un be unlizeo. uLFx 3197 cFYz32 Febuery 1, 2C10 February Pmlecllen Noula b[etlen �I IeneMoula SpadOnllen wltRin Noub Noule ProlxXan Nozzle L W Hl Mealmum Protection Zone OnrN OeoMatlen Wad Areal NV -WA Seo Table 3-0 Volume 1920 cu X 2 X mevimum D io 6 In. VeNcel I IITIRRE pne 160 p X on center rolnlinp down Diagonal 18.86 ft ceapn viae) coO Wad Aroal NKSW Sn Table SIA Volume 192D tisk 2Xmuimum DmBIn. Vankel N C Area taD p x on timer po^ming sown Diagonal 12.B X (sato eltle) ( fine in MID U Na rermea mrne0 � ca eiremon of 1 2 3 y cnnrerl -DanrW tyy Page 1-1 REV 2 n CHAPTERI General Information INTRODUCTION PYRO.CXEM WM1bM Paint spay Bn(tl automate dry eneMeel lire suppression system Is of ma pre-enpinearN We n eellnea by the NFPA 9(eNeM be Ory Chemical EMlrgul[M1ing Systeme, NFPA-9. The mfirgulehlnp units OeacnOetl In this manual are Intended to De Inarellee, Inaped etl, and maintained in azmraenn with NFPA-b. UmIMHcna ealeilee In 1111s manual have been eelebllsllea NwugM1 eklBneiw rebtlrp by Untlerwrnere Laboratories, Inc. lnamlletion and nonce of the ayBmm moat nnbrm to IM limilcibna III 'm (M1ia manual and De OeROrmetl M an PrathOrizea PYR0.LHEM dealer. no PYfl0.CHEM Vehitle Pont Booty Syalem Nlllzea a morgammonlum Phosphate based dry enemlttl egnt (Bpnlllcelly designed 10 aupPraaa nNOnecrou¢ sella, liquid, gu or electrical fired). The system pmvMeB mecM1enkel or electrical aummatle acluallon [M nn De manually adualM mmagn a remore memamul pull arenon. Upon actuation, the [yalam m=Wages a Pre -determined amount of Eqem to the hazard area The anurdmsn of wet and Power to the n.wa eree Is required upon ayarem acwenon. Exhaust Mole) in m0 vennlanon system must be ena on peer to ayarem discharge to allow IM Prenr cenlratbn of Vent to Wild up In to Mxem area. The PYRDCHEM PoM1lma Paint Booty System is anIBOM to eccwnmeeeU a merWemry hclory pre-nf time easy Thle time delay Is roOpirea based on m0 UL 1254 rompnenn leenne, Ip SCCaJ9 S TEMPERATURE LIMITATIONS _ The opennrg temperature range of the PYRD-0HEM Venkla Paint Boom System is 32 °F (0'C) minlmum to 120 °F 149 SCI mmlmum. UL LISTING The PYR0.CHEM WM1lde Paint Booth Industrial Fire Suppression System has been ledetl to the UL Standard ro! Prn-Fran weretl Dry fn pB +BOB ena uetab M u:merwmere L.Mremnea. Inc. •CITY OF NEW YORK APPROVAL The PYfl0.CXEM WM1lda Palo[ Spray Boots Fire Suppreulon System is approved py the Llty 01 Naw YOM Farre DBpenmem per Cennictle of Approyl No. 5644 under the mlbwirg wnallloM: 1. Prior to ;narelletion, plana moat be flied with and accepted by New York CIO Department of BuiltlinBa. MOHlonelly, a cop) M New Yol%Ciy Department of Buildings docketed pone aM1ell be baummea to the Fire Department Cor rwlew ma approval. 2. The system shall be;nablletl, nno0lcally Inepedea.leabtl and oNawlae meinbinetl In aroraer,ce with SeNone 901, 804,1.1 and BC/A 01 New Yolk Clry Flre Lase, NFPA 17 and ITll applicable New York City ConcbucHon Caae/Fire Cala. EIeMrIW wirinp Snell be In STREET. dance with the New York City Electrical LNO. 3. At leas) once a monis, an inepOdbn shall pa contlumaa by a Irairree and knowletlpeede Person to ueya that the system is In Broe working order. 4. The Im011atlon, maintenance pmceaurea, and Ilmileaona aulaa In this manual mun be wm- pnM an. r� uLEx sag] cFm: February 1.2010 cMder 3 -Strom Design Page the *... r REV 3 •g. Nozzle Coverages • 1 Nv-wA.M rWsw nomas ten be pats Ior pewm, n. w:me=now Poremn.Tna nozzle mylmpm gip=moanona mon be blbye. a Pont IOg dimensions 41n[h minimum a 4n IM mavlmYm. a NOiale oneel Is the mwlmum diMer:Ce Imre IM gp G to Mme m MB doaul e¢a of to pretezMn zone e BkMle nozzle appllmMn on a PCE 16paC p we IpIIle yWI4Xon m a PCI-RSWBC only. Nett: n Me mnwae Sud If pros(w Men 46 in, in tliemabr o 12 n pMmMn, no ON al mol nqV pmfedion un be unlizeo. uLFx 3197 cFYz32 Febuery 1, 2C10 February Pmlecllen Noula b[etlen �I IeneMoula SpadOnllen wltRin Noub Noule ProlxXan Nozzle L W Hl Mealmum Protection Zone OnrN OeoMatlen Wad Areal NV -WA Seo Table 3-0 Volume 1920 cu X 2 X mevimum D io 6 In. VeNcel I IITIRRE pne 160 p X on center rolnlinp down Diagonal 18.86 ft ceapn viae) coO Wad Aroal NKSW Sn Table SIA Volume 192D tisk 2Xmuimum DmBIn. Vankel N C Area taD p x on timer po^ming sown Diagonal 12.B X (sato eltle) ( fine in MID U Na rermea mrne0 � ca eiremon of I a mw) BacksreM1 NMP1 IX 14h 12X Vdume B)2 cuh shonnf el0e�nnrer Dm610. Wrticel PMnum n CLL C:) Area 66 p X O O m Side 14X Longest side -3 Inch BUY O O� (7 ON comer plan aide) tj Pont LED NKPi SIN 1B X 20 n Volume 128D _Wft SMbat sitltrnnler D m R W. Vehicle Plenums L(7 � � grad 84 p X W Side 18 X lurga¢i eme3 ircX off nnrer (can aide) PX NV -P1 24 ft 4 X 4 fl Volume 38{ cuh Snonnt vDa-nnrer 0 m S In. Wrticel 10pnDn 1) Area 98pX 8me Ian Longest eieo-cenrer Pit NIP2 4h 4h volume 904 Cun 6MneM aloe -center 21oS lit. Horizomal (Option 2) pros 96 p n alae z4 n Height center UMar FlOCr NVUF 10 R 14 R { X Polume 896 cu X Shortest side -center D m 01n. KNctl Plenum Area 224 aq R S;W t6R Longntaldennrer EMreuet N4DP2 9h 9n 24X Vdume 216wtt 8nonntaWe (croce Om01n. XDrImmM Cor Dud Area p p X aedion) - tinier MrlmMel tlucla Sin 9 k Longest rise Icroes IRpund DDM .aeticn) Cor 9 h 10 In, diameter) yL• reMnl MW duchy Eannet N.DCT 12XPerlmerer or Leym- [soler Db81n. HDrlmMel Cor Duda snmin. aiMnM.r eµP wkm-came, Mazonw m,de 26 h Mnpin Vertical tar wmeM apda 041 cit=ler 3 -system Design 'k Page 39 Q REV 3 CHAPTER III SYSTEM DESIGN General Designing the PrIn oper Type of System PYROCHEM Intluelael Vehicle Paint Spray Bc[m PoO 6u mnlpn System h PP n been de[lanab and reams Cor use lua necessary for me ayarem assigner ro consider me e191 rablde paint spray Ooo1M1 epplimtl0na. The plryalgl characteristics antl layout 01 rile M1ezere vee to pultlallryarlletetl in this chapter deal wXM1 the Ilmnenorre and ensure proper protec0oa The M1ezeM area must meet the pvemeren M various eyalem nnlguraHona. II is to criteria cons a pertlaler system for that ayarem to he eflec. reapanal01111y 91 me CerlHletl installer to ensure IM1aI Me live. Each nozzle I$ iecletl and designed to protect a certain proper system tlaalgn is being Mlllmtl, est ilia( n,a eY¢mm ort Of the 10181 Ilexere area meals me umnenona and Parameters nares In cop Meprer. Before attempting to seaign any "stem, n Is nenaavy m In pram to comply wits me apprnel mavo-emema of UL NIeM a Factory CerlinCenOn Training Class and Mwme 1254 619Men1, when proleCllnp a Vehicle PeiM Spray CerlHletl m Inaiall PYRD-0HEM IMuatriel Vphida Paint Booth, no unGoeeBN Opanlnpe aro ellewW. Spray Boots Fire Supprenion $yMOMe. no ryBrem them eIn nnrem a discharge time abler Choosing the Proper Agent The vemu.Hon system copal be shut down berore ma It is nroneery Cor the system tlnigner to mntleer the Com discharge of the system, Wslide maletlu mune In ma M1uve area m ensure proper prdammn. The agent paab m me system must be approved Total Flooding Corms namrd clan of ma rombunlble mareML The rollow- 9 ine era the norm clues: e. Cylinders: 'A"CIO" -CNlnery solid eerNneeaoua mmbuetlbin. The MoealsPCI-15PHC. PCI-1]ABL,PC426MBL,PC1- lone Incluse want, ps0ep dpm. Ilberglne, and Dleetice 3SABQ, me PCI-]OABC oyllMen can Ce used cons lobi "B"Gley- Flammebb refusal and ge¢ec. These Incluse noMirp wnlde paint epeybmm epplinnona. pdnb, nlnnu,guollne, oils. and Mdremk nuke. b. Nozzles: "C'Glen- Electrical appliances, These Include comDu4 Seven nossl0a are evellWle bran In prolading vehicle ere, poesy genemmd, vA power trenarormen Pont spray booms: "D"Gan- LamDuat101e mebl¢sucn as eWlum, poleyF Nossle gppliunon megmaium, IlWaum,aM nrcp:ium.TM PYR6CHEM NV-,wA Work Aree/PrenumPn Ovemeetl PoanloM IntluelHel VeM1ltle paint Spray Bwln Flro SupPreulm NV,S,q Work AreWlenumNry (8lticwell PnnloM System Id. nM Intended to protect Clan D M1neMe. NW PI BecktlnlbPll (OvarMW PnllbM TM mlloxlnp 9ultlellMe should be used Cor determining the NVAF UMar Floor (Onrhsas Position) proper epenl: NV-DP2 PlUpud (EntlPoSIHon- Horizpnlaq N -OCT Oud Only ABC (me enlum pbespnalaBaaer) - Ions use cats •N-PLU Thee -Wry Nozzle lPilc, Plenums, Under all 'q; 'B�' antl "C' Class nezertic. Fbor Trencnn) ' Gen n uae] Min PCI-tSABC ens PCIVSN9c M,IMen only As Wz NFPA IT, pre-enBlneeretl Ory cnemlcel systema ere nol.pprona for deeo-nmed or burrowing from (.achy aTempereture Range: orslnerycomOuegDlea where Me agent cannm reach the The oPoraerg temperature nope tar vehicle pelnl0win point of wmWallon), or on cnemicalc that contain their cacti applications Is 32 °F. m 120 °510'G l0 40 -C.). orypen Supply pato as nllulne nitrate). Po not mix differ. ant lypeedymfs, or agents hour enrerem manufacturers. d. Piping Requirements: ceeminlread;om they Occur when incompatible cnaminle p;p;pg ei.greme mduee nmltniona an pipe lergm and fit - are Keep In colts IoM the pets cont Ba ¢npl- rings See IM1e blbwlrp peen for epecilic piping soelpn and able to ma Amnetlry Hrvinp JurlatllGtlon. Ilml[etrom Cor each aim ryl;Mer. IILE%343] CEz]32 September 1, 2036 III 1,'N10 Figure 2-19. Mosel RPS -M Mechanical cnyrerz-comPeMnm Pp Be * r REV, a 4. Fusible Linin. Atter determining m0 mekmum emblem temperature at The w[Ible lurk is designed m a thermal nmdar location, eelOd m. Ended thermal aarec- =scala at a epecmc rem- for acwminp to me temperature mndn'an cnen belbv: perelme, releasing tension hpm the stable link line, Causing Thermal system actuation. Sn Figure 2.12. Detector Maximum Ambient O Motl01 No. TBmpOnmro aT0.180 1r° F (r° CJ TD -125 1r° F (86• CJ TD -326 2B6•F1141°G) TD -0.S0 410° F 1210' C.) TD<00 690•F12B9'CJ SL MODEL RPS•M -REMOTE Flgpro alz.N4BWI. Fusible Link. MECHANICAL PULL STATION ^•,F A_ F L R.mma manual nmrol for ryerem r.re.a:g aayk.. I. vro- AXer determining IM mavlmum ambient v100e M me Model RPS -M ramble mechanical pull elation. g temperature at Me It is wnnecke m me ayarem releasing tlevlce M elelnleee lualNa Ilnk ICceMn, select the Conem luamle link e¢aral:p steel ce01e This cable Is enclosed In 1/2 in. EMT nneun US the temperature nMMon engirt allow: wlin comer pulleys M each UengO in tllndlpn. The remam Fuaida Link Mmlmum Ambient meeMnlul Dull ale4pn mall be Iecemtl at the Pont of hbeel No. Tempenlure egrna ham the nueN area.8n Flgun 2-13. FL -186 100° F (36' C.) FL -212 160' F (88° G) . 0 FL 280 226• F (107° C.) •IMr V FL3B0 2Po° F 1113. O) � FL -0.50 3B0•F(1B2°CJ FL -600 400' F (200• CJ _ S. Thermal Detectors. Rale rompensalM temperature thermal debcfora we nor- mally Cpan,m0cna0iC01 coM=I CIp6en sxiic608designed nMMlmaNdN.aK. m ryarele at a factory trent rempenture. They are evell� O aaeroxaS able In an treats femPorvurea wnlcn meet NFPA Manderde O est ere UL Llaretl and FM Approved, O a Itb Wag® ie Flgun t1b.TMnrl DereMor. uLEk 9p] cEnaz Pull station. FIRE DETECTION AND SUPPRESSION SYSTEM THEM W��y FOR THE FROPER ONSITION AND OWKTIT� Or THE MORE or To CONTRATon THE SIM surnmemy SPERRED FROM THEM HE saw wavervi MA ME ENE IW�T� SHROM OR THE Si ONES NOT � CHINGES TO CONTRAST ROM OR TEE XSESS , PL rhtcue +niernRoR 3727 Candia Drive Punta Gorda FL 33950 500-243-0528 734-709-7297 9burghHgmail.com t GFire Pmlecllen Noula b[etlen �I IeneMoula SpadOnllen wltRin Noub Noule ProlxXan Nozzle L W Hl Mealmum Protection Zone OnrN OeoMatlen Wad Areal NV -WA Seo Table 3-0 Volume 1920 cu X 2 X mevimum D io 6 In. VeNcel I IITIRRE pne 160 p X on center rolnlinp down Diagonal 18.86 ft ceapn viae) coO Wad Aroal NKSW Sn Table SIA Volume 192D tisk 2Xmuimum DmBIn. Vankel N C Area taD p x on timer po^ming sown Diagonal 12.B X (sato eltle) ( fine in MID U Na rermea mrne0 � ca eiremon of I a mw) BacksreM1 NMP1 IX 14h 12X Vdume B)2 cuh shonnf el0e�nnrer Dm610. Wrticel PMnum n CLL C:) Area 66 p X O O m Side 14X Longest side -3 Inch BUY O O� (7 ON comer plan aide) tj Pont LED NKPi SIN 1B X 20 n Volume 128D _Wft SMbat sitltrnnler D m R W. Vehicle Plenums L(7 � � grad 84 p X W Side 18 X lurga¢i eme3 ircX off nnrer (can aide) PX NV -P1 24 ft 4 X 4 fl Volume 38{ cuh Snonnt vDa-nnrer 0 m S In. Wrticel 10pnDn 1) Area 98pX 8me Ian Longest eieo-cenrer Pit NIP2 4h 4h volume 904 Cun 6MneM aloe -center 21oS lit. Horizomal (Option 2) pros 96 p n alae z4 n Height center UMar FlOCr NVUF 10 R 14 R { X Polume 896 cu X Shortest side -center D m 01n. KNctl Plenum Area 224 aq R S;W t6R Longntaldennrer EMreuet N4DP2 9h 9n 24X Vdume 216wtt 8nonntaWe (croce Om01n. XDrImmM Cor Dud Area p p X aedion) - tinier MrlmMel tlucla Sin 9 k Longest rise Icroes IRpund DDM .aeticn) Cor 9 h 10 In, diameter) yL• reMnl MW duchy Eannet N.DCT 12XPerlmerer or Leym- [soler Db81n. HDrlmMel Cor Duda snmin. aiMnM.r eµP wkm-came, Mazonw m,de 26 h Mnpin Vertical tar wmeM apda cit=ler 3 -system Design 'k Page 39 Q REV 3 CHAPTER III SYSTEM DESIGN General Designing the PrIn oper Type of System PYROCHEM Intluelael Vehicle Paint Spray Bc[m PoO 6u mnlpn System h PP n been de[lanab and reams Cor use lua necessary for me ayarem assigner ro consider me e191 rablde paint spray Ooo1M1 epplimtl0na. The plryalgl characteristics antl layout 01 rile M1ezere vee to pultlallryarlletetl in this chapter deal wXM1 the Ilmnenorre and ensure proper protec0oa The M1ezeM area must meet the pvemeren M various eyalem nnlguraHona. II is to criteria cons a pertlaler system for that ayarem to he eflec. reapanal01111y 91 me CerlHletl installer to ensure IM1aI Me live. Each nozzle I$ iecletl and designed to protect a certain proper system tlaalgn is being Mlllmtl, est ilia( n,a eY¢mm ort Of the 10181 Ilexere area meals me umnenona and Parameters nares In cop Meprer. Before attempting to seaign any "stem, n Is nenaavy m In pram to comply wits me apprnel mavo-emema of UL NIeM a Factory CerlinCenOn Training Class and Mwme 1254 619Men1, when proleCllnp a Vehicle PeiM Spray CerlHletl m Inaiall PYRD-0HEM IMuatriel Vphida Paint Booth, no unGoeeBN Opanlnpe aro ellewW. Spray Boots Fire Supprenion $yMOMe. no ryBrem them eIn nnrem a discharge time abler Choosing the Proper Agent The vemu.Hon system copal be shut down berore ma It is nroneery Cor the system tlnigner to mntleer the Com discharge of the system, Wslide maletlu mune In ma M1uve area m ensure proper prdammn. The agent paab m me system must be approved Total Flooding Corms namrd clan of ma rombunlble mareML The rollow- 9 ine era the norm clues: e. Cylinders: 'A"CIO" -CNlnery solid eerNneeaoua mmbuetlbin. The MoealsPCI-15PHC. PCI-1]ABL,PC426MBL,PC1- lone Incluse want, ps0ep dpm. Ilberglne, and Dleetice 3SABQ, me PCI-]OABC oyllMen can Ce used cons lobi "B"Gley- Flammebb refusal and ge¢ec. These Incluse noMirp wnlde paint epeybmm epplinnona. pdnb, nlnnu,guollne, oils. and Mdremk nuke. b. Nozzles: "C'Glen- Electrical appliances, These Include comDu4 Seven nossl0a are evellWle bran In prolading vehicle ere, poesy genemmd, vA power trenarormen Pont spray booms: "D"Gan- LamDuat101e mebl¢sucn as eWlum, poleyF Nossle gppliunon megmaium, IlWaum,aM nrcp:ium.TM PYR6CHEM NV-,wA Work Aree/PrenumPn Ovemeetl PoanloM IntluelHel VeM1ltle paint Spray Bwln Flro SupPreulm NV,S,q Work AreWlenumNry (8lticwell PnnloM System Id. nM Intended to protect Clan D M1neMe. NW PI BecktlnlbPll (OvarMW PnllbM TM mlloxlnp 9ultlellMe should be used Cor determining the NVAF UMar Floor (Onrhsas Position) proper epenl: NV-DP2 PlUpud (EntlPoSIHon- Horizpnlaq N -OCT Oud Only ABC (me enlum pbespnalaBaaer) - Ions use cats •N-PLU Thee -Wry Nozzle lPilc, Plenums, Under all 'q; 'B�' antl "C' Class nezertic. Fbor Trencnn) ' Gen n uae] Min PCI-tSABC ens PCIVSN9c M,IMen only As Wz NFPA IT, pre-enBlneeretl Ory cnemlcel systema ere nol.pprona for deeo-nmed or burrowing from (.achy aTempereture Range: orslnerycomOuegDlea where Me agent cannm reach the The oPoraerg temperature nope tar vehicle pelnl0win point of wmWallon), or on cnemicalc that contain their cacti applications Is 32 °F. m 120 °510'G l0 40 -C.). orypen Supply pato as nllulne nitrate). Po not mix differ. ant lypeedymfs, or agents hour enrerem manufacturers. d. Piping Requirements: ceeminlread;om they Occur when incompatible cnaminle p;p;pg ei.greme mduee nmltniona an pipe lergm and fit - are Keep In colts IoM the pets cont Ba ¢npl- rings See IM1e blbwlrp peen for epecilic piping soelpn and able to ma Amnetlry Hrvinp JurlatllGtlon. Ilml[etrom Cor each aim ryl;Mer. IILE%343] CEz]32 September 1, 2036 III 1,'N10 Figure 2-19. Mosel RPS -M Mechanical cnyrerz-comPeMnm Pp Be * r REV, a 4. Fusible Linin. Atter determining m0 mekmum emblem temperature at The w[Ible lurk is designed m a thermal nmdar location, eelOd m. Ended thermal aarec- =scala at a epecmc rem- for acwminp to me temperature mndn'an cnen belbv: perelme, releasing tension hpm the stable link line, Causing Thermal system actuation. Sn Figure 2.12. Detector Maximum Ambient O Motl01 No. TBmpOnmro aT0.180 1r° F (r° CJ TD -125 1r° F (86• CJ TD -326 2B6•F1141°G) TD -0.S0 410° F 1210' C.) TD<00 690•F12B9'CJ SL MODEL RPS•M -REMOTE Flgpro alz.N4BWI. Fusible Link. MECHANICAL PULL STATION ^•,F A_ F L R.mma manual nmrol for ryerem r.re.a:g aayk.. I. vro- AXer determining IM mavlmum ambient v100e M me Model RPS -M ramble mechanical pull elation. g temperature at Me It is wnnecke m me ayarem releasing tlevlce M elelnleee lualNa Ilnk ICceMn, select the Conem luamle link e¢aral:p steel ce01e This cable Is enclosed In 1/2 in. EMT nneun US the temperature nMMon engirt allow: wlin comer pulleys M each UengO in tllndlpn. The remam Fuaida Link Mmlmum Ambient meeMnlul Dull ale4pn mall be Iecemtl at the Pont of hbeel No. Tempenlure egrna ham the nueN area.8n Flgun 2-13. FL -186 100° F (36' C.) FL -212 160' F (88° G) . 0 FL 280 226• F (107° C.) •IMr V FL3B0 2Po° F 1113. O) � FL -0.50 3B0•F(1B2°CJ FL -600 400' F (200• CJ _ S. Thermal Detectors. Rale rompensalM temperature thermal debcfora we nor- mally Cpan,m0cna0iC01 coM=I CIp6en sxiic608designed nMMlmaNdN.aK. m ryarele at a factory trent rempenture. They are evell� O aaeroxaS able In an treats femPorvurea wnlcn meet NFPA Manderde O est ere UL Llaretl and FM Approved, O a Itb Wag® ie Flgun t1b.TMnrl DereMor. uLEk 9p] cEnaz Pull station. FIRE DETECTION AND SUPPRESSION SYSTEM THEM W��y FOR THE FROPER ONSITION AND OWKTIT� Or THE MORE or To CONTRATon THE SIM surnmemy SPERRED FROM THEM HE saw wavervi MA ME ENE IW�T� SHROM OR THE Si ONES NOT � CHINGES TO CONTRAST ROM OR TEE XSESS , PL rhtcue +niernRoR 3727 Candia Drive Punta Gorda FL 33950 500-243-0528 734-709-7297 9burghHgmail.com t GFire 0 �I Qr Y I IITIRRE coO U N C CL MID U � ca I a ^` L M O U n CLL C:) z' O O m ie Flgun t1b.TMnrl DereMor. uLEk 9p] cEnaz Pull station. FIRE DETECTION AND SUPPRESSION SYSTEM THEM W��y FOR THE FROPER ONSITION AND OWKTIT� Or THE MORE or To CONTRATon THE SIM surnmemy SPERRED FROM THEM HE saw wavervi MA ME ENE IW�T� SHROM OR THE Si ONES NOT � CHINGES TO CONTRAST ROM OR TEE XSESS , PL rhtcue +niernRoR 3727 Candia Drive Punta Gorda FL 33950 500-243-0528 734-709-7297 9burghHgmail.com t GFire SHEET NUMBER Printed: rpesary, Jalrn, zgr 0 �I Qr Y I IITIRRE coO U N C CL MID U � ca I a ^` L M O U n CLL C:) z' O O m BUY O O� (7 ) 000 tj III cc (� i U �a L(7 � � U W SHEET NUMBER Printed: rpesary, Jalrn, zgr Ch p 2 -Ca tap mm Ps(p 24 10 RENT Ina w Me m OM PASS PNEUMATIC ACTUATING 2. Model PA6200. CYLINDERS `� \ I&_ as Model PAC -200 is a pneumatic ak:ftj cyr ndeHMl ( OT \ 1. Model PAC -10. n adnate a maximum of twenty NO) agent cylind9re simultaneously The Modic PAC -too included a DoT RRID TEAM cylinder pressurized wIM dry nitrogen M 350 PSIG They Model Pil0 is a pneumenc Muating Minder Met M 70° F. a fords valve with pressure gauge, and a wall Can acWRW a maximum of ten (10) agent Cylinders Manua - mounting bracket. A Modal MCH$ kill or ECH3 control rou41y. The Model PAC 10 imiudes a DOT sell cyiim hoed must be purchased Separately and wnnMed b Me der pressurized with dry nitrogen to 350 PSIG ® TO. 5, a PAG20T W open Me valva. See Figure 2-9. Ernst valve with pressure gel and a wall mounting a yppEL ECX3, NMCHs qi MCHa bracket. A Madel MCH3. NMCH9 or ECXcontrol l htl CONTROL HEAD , must be purchased separatelyaMmnnc Mthe PAC -le I RJOLD 9EP TEL /'� to open the valve. Sao Figure 24. f, Figure 23. Modal Record Pneumago Actuating Cylinder. E IILDtfIT CO442 NM 1T, 4 C FBI Figure M. sweet PA M P mMk AC WN Cylinder. wal /, Chamber 2 -Ce nM Food 2-2 li4 NOZZLES Noubs have been developed bar Vehicle Point Spray Booth prOW01on Each mule has Hen deslgnM for use in cer- tain ansa of the booth. The blcdel N V WA nozzle is used Bar overhead application In the boom work area or planumkplL The Model NV -SW nozzle Is used Bar sldewell application In the Moth work area or plenuMplt An arrow stomped on the nozzle Whom Indicates me discharge dire llon. We MMeI NV -PI nozzle is used for overhead application In the backdraft plenum or mwndraft Pit area. The Modol NV -UF nozzle is used Mr owMead application in Me undeMmr plenum area. The Model kill tussle is used for horizontal (end position) appllution In Me pmducr area We Model Hill Nozzle Is also used for end Mat - Bad application for exhaust duct protection. The Model N PLU nozzle is used as a three-way nozzle air pmt ling pled, plenums, and under nom trenches. The Model Ni mute Is also an alternate nozzle used for exhaust stud pNW cilon The Model N -OCT nozzle can only be used on 15 to and 25 to Cylinders. Sao Figura 23. NV-WA NV3W I'll N -PLV No=W Neale NeuN Neale .11 Malawi, imi will 000 o O NV -UF Noule NV-DP2 Noulo N -BCT Nozzle pol Figure 2-3 Noulea �e CYLINDER BRACKETING Vertical well mounting be the PCMSABC, PC417ABC, and PCP2ga C. is provided by the Model bull mouMi bracket kit. Vertical well mounting for the PCI-MIABQe d PCMTOABC Is provlded by the Model MB -1 mounting breck. at kN We Figure 24. For vertical noor nwuMlrq of 1H p d.17ASC ata • MNNSABC, an B In. channel -type mounting bradmt Is awllable, the Model Niel • For wrnml Poor mounMq M the PCTMBC, a 10 in. uni • nel-ypc mounting Mmkm Is available. the Model Sol lKi34T7 CExM FWuery 1.2010 *< APPROVED SFF APPROVED fllfl ApDIl1 E OfIDILS A final inspection including functional test of the system and AFPD approval shall be required. — 23'L 9" 1 CLEAN AIR 61 14W V •For wmcalnmr mmnnnglaonec,.Iz in. Than. nal ype mounnng br sit Is availede. the Model Went. 0 0 Figure 24 Mounting brackets MB1Sand ME 1 MODEL MCH3 - MECHANICAL CONTROL HEAD /"1 The Model MCH3 mechanical control head Is a fully mechanical control head which con be connected to the PCI95n7@Sa35O0 callMor valve, This mntml head will support a froide fork defection system, a remote Wtheni- eel pull station (Model PPS -M), and a mmheniwl or added gas s Ment valve. A micro switch (Morel MS-SPDT. MS-DPDT M8-3PDT, or MS-4PDT1 can be OMsred Area Mthly am held InsWiled, It Is e0uipped with a local manual control h"W Mat allows this mechanical system actuation. Operation of the local manual control requires removing the pull pin MEM mooting Me handle clackyar We Modal MCX3 comrol Had can actuate a maximum of five (6) dissident. Sao Figure 2-5. MODEL MCH3 CONTROL HEAa 0 Figure 2-0. MeaMnimi Contrel Head.wi Nv-P3 3/4" 3/4" NV//W((A�� 1" N 3/4• NV -WA 1" 1 U DRAWINGG NOT TO P/m0 m vCI /ele Remote next to the Door volumel449 Lu FUSIBLE LINK DETECTOR INSTALLATION Fusible links are always used in conjunction with the MMel WH3/NMCH3 Me mlml Control Hold. After mounting the cylinder and control "ad, the fusible link line can be Installed. The first step M Intlallirg Me luelble link line Is M Install Me HMMr bncW(s), These blaukeb must be installed In the plenum area, the huaM area, and In each dun. sae Chador IN Be detector placement guidelines. Note: Only ML-aylo Fusible Under eon H used. Connect the fusible link bracken together using 1n In. win- bult and the wMuit monectars supplied in the detector kit (Abdel FLK -0J1 A). A PYRO-CHEM corner pulley must be used whenever a [lenge in comwt dlr nlon is necessary. no conduit as mnne M Me control head through e kmckout in Me upper MMside comer. In eaneral, fusible links cornered In Me dewmr brecb nerved In series using 1/16 In. diameter stainless • stele curie. The spring plate In Me control head maintains tendon on this series of MBINe brand. It Me tension is released kr any reeron (i.e.. a fusible link wpeatep, Me control head MII operate and Schism the system. Muimum limitations air the eased link detection one are as bllam Fusible links MEET be inablled with or without fusible link hangers (sea CbepMr II air daxrilabo 1, Ck4-SMlPlAtiOn Page 4-5 REV 2 Fusible Link Line LImIM11one When Msed With MMM MCH3 and NMCH3 Conical Heeds and Pen No. 415670 and 423250 Pulley Elbows Maximum a of Detectors: 20 Mezimum Iergch of cWle: 150 ft f0.5.> m) Muimum N of pulleys: 40 1. Fusible Link Installation Without Hangers. Begin boosted links at the mrmlrel bracket. The link 4 wn- nMed to the far lice of the terminal bracket using an "S' hook. The 'S' hook must H crimped closed after the link Is Installed. A tight loop M then made In the cable and secured by the Crimp provided. Who Imp M mnnened to the other side of the tern l link Mae nBure 4i1 and the cable no through the mmA M Me nen bracket. The cable proceed. IN from the tern link will be used M mnnmr the series Ilnke (we Figure 47). Series links must be centered In Their detector braaMs. Figure 4-6. Terminal Link Installation. _1 M•IassII II=in 1" 14W 3/4• DUCT Fuse Links 280 Globe �_E)P2 ML -3 1 Duct Straight up no Bends 909-H 04/20/21 Pyramid Pens 4805 van Gorden St. Wheatridge, Co. 80033 1920 Cu. Ft. per Nozzle Plenum 30"D% 14'W % 9'9"H Horn and Strobe middle of the Booth HAL EXTRACTION BOOTH INTERIOR SPRINKLER SYSTEMS 1717 61st Ave Greeley, Co 4101 6300 E. 88th Ave N 3 Henderson. Co. 80640 DUCT 2r Dia 12• H Strati Ftp Monarch Fire Suppression System PCI - 7011 ABC /4Nonk NFPA Standard For Dry Chemical Extinguishing System NFPA 17 UL 4864 Complance Testing UL Listing will meet Manufacture Specifications January 2004 INSTALLER Ramon Delo 3 Figure 4 7. Series Link Installation. 9'9"H ULEX U37 CEx732 March 17.MOR CLEAN AIR 14W 51112021 MMIIeEM, Arvada Fire Protection District mm ARVADA FIRE PERMIT • DRY CHEMICAL SUPPRESSION SYSTEM TO REQUEST INSPEC S. LOO CN TO WE WMPILttM PENMT FORTK AM REWESTTIE INSPECII(kl Few We PERIJR YW GW ACCESS ME mN1woTOR PEwe Roatu AT nrornwrnmlw.A..komva_nmamp Ina w Me m OM PASS FAIL Rio RRID Q NV-WA NV3W I'll N -PLV No=W Neale NeuN Neale .11 Malawi, imi will 000 o O NV -UF Noule NV-DP2 Noulo N -BCT Nozzle pol Figure 2-3 Noulea �e CYLINDER BRACKETING Vertical well mounting be the PCMSABC, PC417ABC, and PCP2ga C. is provided by the Model bull mouMi bracket kit. Vertical well mounting for the PCI-MIABQe d PCMTOABC Is provlded by the Model MB -1 mounting breck. at kN We Figure 24. For vertical noor nwuMlrq of 1H p d.17ASC ata • MNNSABC, an B In. channel -type mounting bradmt Is awllable, the Model Niel • For wrnml Poor mounMq M the PCTMBC, a 10 in. uni • nel-ypc mounting Mmkm Is available. the Model Sol lKi34T7 CExM FWuery 1.2010 *< APPROVED SFF APPROVED fllfl ApDIl1 E OfIDILS A final inspection including functional test of the system and AFPD approval shall be required. — 23'L 9" 1 CLEAN AIR 61 14W V •For wmcalnmr mmnnnglaonec,.Iz in. Than. nal ype mounnng br sit Is availede. the Model Went. 0 0 Figure 24 Mounting brackets MB1Sand ME 1 MODEL MCH3 - MECHANICAL CONTROL HEAD /"1 The Model MCH3 mechanical control head Is a fully mechanical control head which con be connected to the PCI95n7@Sa35O0 callMor valve, This mntml head will support a froide fork defection system, a remote Wtheni- eel pull station (Model PPS -M), and a mmheniwl or added gas s Ment valve. A micro switch (Morel MS-SPDT. MS-DPDT M8-3PDT, or MS-4PDT1 can be OMsred Area Mthly am held InsWiled, It Is e0uipped with a local manual control h"W Mat allows this mechanical system actuation. Operation of the local manual control requires removing the pull pin MEM mooting Me handle clackyar We Modal MCX3 comrol Had can actuate a maximum of five (6) dissident. Sao Figure 2-5. MODEL MCH3 CONTROL HEAa 0 Figure 2-0. MeaMnimi Contrel Head.wi Nv-P3 3/4" 3/4" NV//W((A�� 1" N 3/4• NV -WA 1" 1 U DRAWINGG NOT TO P/m0 m vCI /ele Remote next to the Door volumel449 Lu FUSIBLE LINK DETECTOR INSTALLATION Fusible links are always used in conjunction with the MMel WH3/NMCH3 Me mlml Control Hold. After mounting the cylinder and control "ad, the fusible link line can be Installed. The first step M Intlallirg Me luelble link line Is M Install Me HMMr bncW(s), These blaukeb must be installed In the plenum area, the huaM area, and In each dun. sae Chador IN Be detector placement guidelines. Note: Only ML-aylo Fusible Under eon H used. Connect the fusible link bracken together using 1n In. win- bult and the wMuit monectars supplied in the detector kit (Abdel FLK -0J1 A). A PYRO-CHEM corner pulley must be used whenever a [lenge in comwt dlr nlon is necessary. no conduit as mnne M Me control head through e kmckout in Me upper MMside comer. In eaneral, fusible links cornered In Me dewmr brecb nerved In series using 1/16 In. diameter stainless • stele curie. The spring plate In Me control head maintains tendon on this series of MBINe brand. It Me tension is released kr any reeron (i.e.. a fusible link wpeatep, Me control head MII operate and Schism the system. Muimum limitations air the eased link detection one are as bllam Fusible links MEET be inablled with or without fusible link hangers (sea CbepMr II air daxrilabo 1, Ck4-SMlPlAtiOn Page 4-5 REV 2 Fusible Link Line LImIM11one When Msed With MMM MCH3 and NMCH3 Conical Heeds and Pen No. 415670 and 423250 Pulley Elbows Maximum a of Detectors: 20 Mezimum Iergch of cWle: 150 ft f0.5.> m) Muimum N of pulleys: 40 1. Fusible Link Installation Without Hangers. Begin boosted links at the mrmlrel bracket. The link 4 wn- nMed to the far lice of the terminal bracket using an "S' hook. The 'S' hook must H crimped closed after the link Is Installed. A tight loop M then made In the cable and secured by the Crimp provided. Who Imp M mnnened to the other side of the tern l link Mae nBure 4i1 and the cable no through the mmA M Me nen bracket. The cable proceed. IN from the tern link will be used M mnnmr the series Ilnke (we Figure 47). Series links must be centered In Their detector braaMs. Figure 4-6. Terminal Link Installation. _1 M•IassII II=in 1" 14W 3/4• DUCT Fuse Links 280 Globe �_E)P2 ML -3 1 Duct Straight up no Bends 909-H 04/20/21 Pyramid Pens 4805 van Gorden St. Wheatridge, Co. 80033 1920 Cu. Ft. per Nozzle Plenum 30"D% 14'W % 9'9"H Horn and Strobe middle of the Booth HAL EXTRACTION BOOTH INTERIOR SPRINKLER SYSTEMS 1717 61st Ave Greeley, Co 4101 6300 E. 88th Ave N 3 Henderson. Co. 80640 DUCT 2r Dia 12• H Strati Ftp Monarch Fire Suppression System PCI - 7011 ABC /4Nonk NFPA Standard For Dry Chemical Extinguishing System NFPA 17 UL 4864 Complance Testing UL Listing will meet Manufacture Specifications January 2004 INSTALLER Ramon Delo 3 Figure 4 7. Series Link Installation. 9'9"H ULEX U37 CEx732 March 17.MOR CLEAN AIR 14W 51112021 MMIIeEM, Arvada Fire Protection District _ Fire Marehal'a GMce aY. 7903 Allison Way -Arvada, CO MOB Main 3034b3012 - Fax 3034327996 w ..arvadanm.wm Address. 4BMJ915 was coon Sewn Jab Number: 21042E00CJN [g.COBC04l Sona: b]SMRS I'll Nuordw,ala 21M911=12Jn decupanr xama: IMad LA,Sm"Mer LLC Permit loped On: 911rR Cpnlndar. Slane Meirde r Sdma Pormn Ezdm On: SI VN22 (OM)MMM"7 svawns. me Inspection* Rasumal Cary im SopPemlen SPlam conk con xw. JW owepum: Faurolw, mea ARVADA FIRE PERMIT • DRY CHEMICAL SUPPRESSION SYSTEM TO REQUEST INSPEC S. LOO CN TO WE WMPILttM PENMT FORTK AM REWESTTIE INSPECII(kl Few We PERIJR YW GW ACCESS ME mN1woTOR PEwe Roatu AT nrornwrnmlw.A..komva_nmamp Ina w Me m OM PASS FAIL Rio RRID Q co p U Till to 0r_ N CL Tows' MCI U Cu Cu T I a axiii M xxxxxxxiN M p CO C:) z Q m ��U LL _00 C: _ -Se Cu O 0L CD CA tJ PERMIT COMPLETE IAFPO INSPECTOR SIGNAIUREp DA E: m� NOTICE TO CONTRACTORS . fapalpnr}peasantteraµdslmmlgl MAN MatZO441 tours Ware me dglrty Irge9yl sae. Te local a TEN 9'Wr that da MIs ata Ill lnsy swil cexelMulelM To IMual,ne or apallaoke You will re amrfimuCan el with meactal daWw&e iRw¢L'm. . amm- woo mprwalvu[Rrelaamdmpowe gammeanmmbmalaMapnm. ohaNw�irm,mb cat b all arr Dome nM nonce r�awry ale,,ri Bret lwm am m all lmw. Work shall ha In stainless rayhwinker A pall oak mtin mmganaprual dp¢ mtmW minimum smeams rlpreTuireamnmal kpitiva. IrTom inxerl re a mmpmn�rwMianm zo lnm nmym Yr hall lnaz4 law NaMr9 period ],Theo sphi can bet e vein.gdahketlaard ffiMaMx. Askingp nsmay000rm am Model ode ,loca ig ManNo Fears ilia ata alNro®ry lnwmmppa,ey. RM me rerad In a mrebuu MEET. joadthis u,, Or eesmrmm or me ordMat ra}irerWxem[atl ma/R'1uire MlNanalMRS . M1ryc)M modleeyes.¢ ,M Epi mkPmmb_BaNCPomil.W?PID-W723PPIDS1M IT fil l /3/4" 231 1"�Y / 1 / /j���3/4. MV -WA r314Exw NV -WA / V l• 1, I r 1" 14W 3/4" DUCT fuLinks 280 Globe BeML-3 Duct Straight uo no 10'H Bends 9'9'H 04/20/21 Pyramid Pens 44105 Van Gorden St. Wheatridge, Co. 80033 1920 Cu. Ft. per Nozzle Plenum Remote Pull - 10"DX 14'50 K 9'9"H Morn and Strobe middle of the Booth FULL E1rTRAC710N BOOTH 231. ca uLa" WAN N n Mav4n sue INTERIOR SPRINKLER SYSTEMS DRAWING NOTTO 1717 61st Ave Greeley, Co PCI -70/ Remote i eat to the Door Hen r 88th Ave R3 Niel 40 Henderson, Co. 80640 Work Area Volumel449cuft DUCT 24"Die 12'H Strait up Monarch Fire Suppression System PCI - 7011 ABC /4NFkzde NFPA Standard For Dry Chemical Extinguishing System NFPA 17 UL 4864 Complance Testing UL Listing will meet Manufacture Specifications January 2004 INSTALLER Ramon Dena Anther Architects, PLLC Architect J.= t Engineering 3727 Candia Drive Punta Gorda FL 33950 800-243-0528 734-709-7297 gburghOgmail.com so l�T OF so CONTROT DMILMENTS 19 TO WHOM An OWKTIT� OF THE WON,( TV The CONUMMEA THE obvious Oxorchl ME �w�� ME 'Her Is R�� To ow cial ask shall Me R�WD El Me Novel EMITTED FROM THEM M ell lossessando REWA� we, AM, wall 0,vi TO WIMMOT �° Wheat Rk Uskyby c ding OMs0 Fire FIRE DETECTION AND SUPPRESSION SYSTEM Supression r LS2 4 5 6 _o 4xii Rio RRID Q co p U Till to 0r_ N CL Tows' MCI U Cu Cu T I a axiii M xxxxxxxiN M p CO C:) z Q m ��U LL _00 C: _ -Se Cu O 0L CD CA tJ U m� M0 Cu (� i U Lo } d to N U X 00 0 Lu a Fire FIRE DETECTION AND SUPPRESSION SYSTEM Supression r LS2 4 5 6 I� C FBI Fire Suppression System Installation Specs. FIRE SUPPRESSION SYSTEMS lxC FIRE SUPPRESSION SYSTEMS COMPATIBLE WITH HAL EXTRACTION BOOTHS: 1. AUTOMATIC STAND-ALONE DRY POWDER SYSTEMS 2. AUTOMATIC SPRINKLER SYSTEMS FROM THE BUILDING FIRE SUPPRESSION SYSTEMS SHOULD BE INSTALLED ON THE HAL EXTRACTION BOOTH BY A LICENSED FIRE SYSTEMS CONTRACTOR. ENGINEERS AND INSTALLERS SHOULD REVIEW THE FOLLOWING: 1. ALL PENETRATIONS (SPRINKLER HEADS, PULLEYS, CONDUIT, ETC.) ARE TO BE SEALED FOR A 1 -HOUR FIRE RATING. 2. ANY CONDUIT PENETRATION INTO THE BOOTH MUST BE SEALED UTILIZING AN APPROPRIATE SEALING FITTING AND SEALING COMPOUND. 3. FOLLOW THE APPLICABLE CODES FOR INSTALLING A FIRE SUPPRESSION SYSTEM IN PAINT SPRAY BOOTHS. 4. ALL ELECTRICAL COMPONENTS FOR THE FIRE SUPPRESSION SYSTEM MUST BE INSTALLED 3FT OR MORE FROM THE DOOR, UNLESS RATED FOR A CLASS I/DIVISION 2 ENVIRONMENT. 5. IN THE EVENT THE EXTRACTION BOOTH'S FIRE SUPPRESSION SYSTEM IS TRIGGERED, THE BUILDING FIRE ALARM SYSTEM SHOULD BE ACTIVATED. 6. FOR BUILDING AUTOMATIC SPRINKLER SYSTEMS: SPRAY HEADS SHOULD BE PLACED IN THE WORK AREA, EXHAUST PLENUM, AND EXHAUST DUCT. BOOTH VENTILATION SYSTEMS SHOULD REMAIN OPERATIONAL. 7. FOR DRY POWDER SYSTEMS: THE FIRE SUPPRESSION TRIGGER SHOULD TURN OFF THE BOOTH VENTILATION FANS, AS TO NOT EVACUATE THE FIRE SUPPRESSANT MEDIUM. SEE ELECTRICAL CIRCUIT DIAGRAM FOR CONNECTION POINT. A: SAFETY & HEALTH PRECAUTIONS AIRFLOW AIRFLOW EXHa. Bim DUCT TO STACKSTACKON ON BUILDING WOr u. DUCT E^CM PAN&FOR v/ G 'Ar Or• a9 0 F 3I Fire SuPP,e ssion System nf ration Example Detail Notes: Dstall A: Minimu sprinkler head per s oars feet. w P P 9 Detail lir Mechanical fire detection sensors (fusible links) must be placed so as not to interfere with interior lights. Dalai) G Minimum one sprinkler head in the exhaust duct. Detail D: One sprinkler head inside of the exhaust plenum. Two options shown. Detail E: If a serviceable sprinkler head is required inside the plenum wall, an access hole can be cut out of the center Aoa96'anel. A UL Listed access door to thes sprinkler head may be required for P P jurisdictional approval. 17 LS3 S ant and Packing Ma HW Model 215 Booth proposed here is pre-engineered and UL Approved. The Wind Fire Barrier Sealant CP 25WB+ engineered 3Ma"Flre tomer sealun lPnM+a a high Rrlulmme,my Huse, gung e, Isle -Lassa, IlM� xalall Me ansa te Mm a mcnsfic to be field installed and approved prior to fimnm Me Hot as a ffto aimme Sound transn'm'on. 3114 Rod Roper Sealant CP 250+ lelps a nl the Trend N rare, smote and rebus okass Ealua, during and site expmm to a Ire Men Yadoee In aver a with alisted in Tough ceWrMn or fim'"p ebint eambk 2, CNlnen and Asset Wmanuea) sxsdm. m rEd Me MCH per Edi Control Heed, or mmotely der Fire earnerR dam OMMIG+ bland swings ane Hndmbms peeing through fito Died inn,(cm]aullg or wall a asemMa and dLer firembe Indoor Wining MmlruM The unlpue lntumexeM of� of MIS maeral ahem 3M FBI Ean'nr Malam Up Sir IL wend and help malmh e _ OrMop Wenflw seal for up to 4 boom in onennd an 6 d ib fire. 3M Fire Ranlar Sealant CP 2511 w1md M secret adnaken to a full large 3.5-Auxlllary output. Tne Wmm shall prorlde lar the M sin hMn suWWta and pereVand. W mixing is rorylad. DHon Int dsnlam VA 4)Clil r MNis PCLZUENTEBC shall be used whir Base ws IRene ftmn- % e vemilnion HeMms in the event Nryabm nowwon. This AFpknbn Hail re ALI22T IT WCE Re P MNele PC"MBC shall be used Mtn suppmning agent Ml RATE NIIrE Yes MBSFDT or M5 POT minlaWm mfth ln=IIW In me Fire aabler up to 4 Hi smen seal L -_ S ificams Epledi SIC 54 Mtrq; L.Pagngi shall be used Min wppmeeing agent fill weightm UEDO LEE environmental rodulaters �eei/"'- ass Far auxiliary fu=ion¢ such on, aalbie Mames or alarm Se to (22.6 ad. Epode Models PCI ]BABC shall be used see.,e. with eupprwaing agent fill weight Ed 70 to (31.74), All aHa Yftpna+sls IEC:IRG IFC; IT II NFM S[ O]; - 3.6-suwmv ion. AModel M Senn 3olenola Monhry NEC fill 70) NWA Int M Nall W used he sugmiea the invegrM 0 all Meddwl ono 134 bar +19 TO L a.o ioi1R lmlll5.11m ]av'en eunr6Faunaavre..lal not causes 110 l n w lee mg 112 1 IV 1051115 ]l ore Mme Rdnm LP 25N9+, 20 n.[C S P IBM I a 11 [e jet m0 fill W /� US effislitarl 1 Mr. Rre MMV Mem a 25NH+. V I ptl I 9n s1 Ed 16 haven a bra=e body, Smell mm with mbb•r nn e v rP-'6 2a 01115rush]MoRre Mme nM LP2Ta1{+, 2 Wbn,pvl land liver 11 aconformancen NWA r] n u installed lirinn adYM5611 imillYiim yp+Rre MMe6YYIla2SM+, 51WbAh4laid 15am(Its 0 11 prodnm.cannot nand Wlhla.r wnan mttum.a moll enol be under Cn erg exam Wlim ul0,safety sem PHONE: 800-245-3573 www.311I.cumlElectrical 457 HnL EXTRACTION 3.16. The Control Panel can be mounted to the Booth wall panels with the provided mounting hardware or remotely mounted to a nearby wall with customer supplied unistrut. 3.19. The control panel door must be able to fully swing open for maintenance and repair. 3.20. The control panel door must have a minimum of a 36 inch clearance, which is required from the front panel surface to the nearest wall. (See Figure D) 331. An Uninterrupted Power Supply (UPS) is required to be Installed with the Booth to maintain compliance with Fire Code for Extraction Facilities. The standard UPS HAL Extraction provides with the Control Panel has noW of output and only backs up the PLC, gas detector, alar rid a single emergency light. It does not have enough power output to backup tha'fans. 332. NEPA I Chapter 38 states that the Extraction Booth's ventilations stem must WARNIN Puts and/or outputs uts from i have backup power. A6kVA onokVA UPS AIL UPS equipment may rempin rive avoir system can be purchased as an upgrade to , the main disconnect in off poetic,. meet this code requirement. A•4: FIRE SUPPRESSION Isixi 4.1. A UL Listed Fire Suppression Systems required to beinstalledon the HAL Extraction Booth to be covered under the Extraction Booths UL Certification. 4.2. Please consult with a fire suppression engineer to make sure you comply with regulations for your Authority Having Jurisdiction (Fl 4.3. The Fire Suppression System must be roared and installed b a licensed Fire Systems Installer to prrect y p y y obtain the correct permitting for the loal Authority Having Jurisdiction. 4,4. It is the responsibl lity of the purchaser and owner to evaluate their facility to determine which type of fire suppression system is best sated for their facility. db. It is the responsibility of the AHJ to vert the suitability of the fire au iso stem prior to e P ty Y Y PPre n Y installation and commaisn n 4.6. HAL Extraction wll terd'nate the installation of a standalone fire sit system for an suppression ra ys additional fee. Arlt' fire suppression system, whether coordinated by HAL Extraction oat, is not covered under the UL Certification for the Extraction Booth. but rather is covered under its own UL Listing. HAL Installation Instructions (Excerpts) 3 Fire Suppression System Comments 1.) The HAL Model 215 Booth proposed here is pre-engineered and UL Approved. The design requires a Pre- engineered UL Listed fire suppression system to be field installed and approved prior to operation. 2.) HAL Technology does not have a list of approved fire suppression installers, but HAL requires that a licensed fire suppression installer be used. 3.) Interior Sprinkler Systems is properly licensed has been selected to install the fire suppression system. Shane Mendenhal will be directing the installation process as well as the fire stopping of all booth penetrations per the specification set forth by HAL. See sheet M12 for the fire stopping specification and the cut sheet on this page for the 3M products to be used. A note on sheet M1 has been added to specify the fire sealant material. 4.) ISS (above) has provided details of the pre-engineered UL Listed dry chemical fire suppression system (see sheet M12). This system is manufactured by Monarch (a Johnson Controls company). The design details of this dry chemical system have already been approved by the Arvada Fire Marshals office (see sheet M12). 5.) In the case where a dry chemical suppression system is used, it is required that the active material remain inside the booth to extinguish the fire (see notes on sheet M6 - Fire Suppression). No mechanical ventilation or interconnect with mechanical systems is needed. 6.) Note that the new RTU make-up air unit supplies air to the general work area and this unit has no physical connection to the HAL booth and none is needed. 7.) The HAL booth as delivered includes two (2) alarms, the first being an audible alarm (Vibratone 24V buzzer, see sheet M10), and the second being an LED beacon light (see sheet M10). These alarms are not connected to any other alarm system as the UL -approved design contains the fire to the booth itself. The buzzer and the alarm are detectable from the exterior of the booth as well. 8.) Prior to occupancy, the complete system will be inspected for safe and proper operation. As such the pre- engineered UL -Listed booth together with the pre-engineered UL -Listed fire suppression system form an integrated system for ensuring life safety. MONARCH Dry Chemical Hazardous Material Storage Building Fire Suppression System General A gmwing number of heel, May, and Manor omine[cae daimea with the storage and wmainmem m hazardous male s has lee to me development M spemel application PWOM .ma gimme, bmial Than. ma Tormans b.grwM•n i men bfrtt tiemcme unNw norhe lack of proper spill mnueun mt eon nin here .¢upry andemml injury 0r groundalnmemehou on. Then relabb in can losedesignedrage ofapplicable oboe Ad", True mW olonal Far firimym amt a broad rang, um, variety, AN wees the Idea Farfire MAJOHronm Mean he Uniform im 11,rmng in Coe, mi Unit maim A*,Nin,. ilvmaingthe unimlm awiei Standard No.Fin Wen, National Fire promnion Ucalaon .'Mere No. 30-'Fl+mme bb and and Hmhhb tiyuids Cele,' and the The MOO Sapro dna xnnh An. Tneem Seem ee aweenglnwrea dun For Fire hazardWn ous eyaumoXenaconeThe"solid E der monnoemousmade Dal storage PVXOCXEMe Memlul suppress 9 0 ry- mm�dud s serf lido Awreml Ip agents am mpropn A hose suave ppm d. mnaeMmar epmt peps M type AfRmustWr sWo,a m,adm m to tag'al ammaa nm e. muums The MONARCH la me erome nemm.blM among - p•' ECT MONARCH system Infmse'Total ard No 17-' Do Cha n anwtn a¢ sores by NWAm.V mooed xo.n-•es cmmicals Extinguishing nerm dm LeWmmaeeane raidersMutualUW pmrnm pee ngnremM ayMm eppety 0 hpanmmema dalst meflexibilitybuilding lapoMna ...fiamm nn.m0ua m.mdel storage bunamg I.vOua with mnfitlma. System Operation HaMrMus material storage bull4lrq fire prMemIj Is a [Metal application or the MONMCH Industrial Fire Suppmmmn Smm it PFOVidW a highly r ble rn M ilii m e n Amodular mrc f uandA HI W prescribed onar 1 ea rd Ig .nen eared laxmem modular arw So%a o oinulnsuppliers bv dedicatedWunderwnu d chemical suppressing 9e a ppern+ppovsMlin consistent with the taetAaro9eauallMa. l ... lemuotfarm mapositionedamI ullrwmnMegdonMa„mbien Mpaen aOna ... an output Sirm monism ehtuweM. he eror input ".ond' n the control hoe. The amroi hese res nae a alai. the System p v g,gbY pn•Ir, mnmel lV M,vr ,nnphe utters epee MIM•r v.lva. A manual means of wi b,l g Is ansae motto provisE,paom MITI au Mwbnle hrcal a+bb b prorira emote manuarms. T ani. national equinr nMrlatl ompud he dor cSMmr M+inn. ml. omionlagungnen MIIgningW the basic Wamm dUSiore and m eculltemewnan designingadmrco comply Issuss wham, aamndn ossa, onset comply with eta wan. sent Bovdms Mnnlsl Shot eBulMln Prannlm ry N 9 . need wm,mebe nke l q 'hal tmer l n n9¢uinlessMel cable Moded MCS Control Head 4 MotlN Mi e, Agent Stoira VlI'n tln B sixth agent di piping BSAgent Discharge Noso ], All Isell 9 MadillflPS.M flemole Mechanical Full Station 4 Encb¢ure Suggested Architect's Specifications 1. GwxMI 99 P .1 1 -Th Jure day are empal remainsystem,Man Le le rime , ide THAI - racwrea by Jonson Camara Th "Mm ing rshall provide Fm on arms hazardous mM "I b"G ria pine I a al l number dmewl .In a xi lire lire ummr ane inti s obi 1 lx Then nem Ed utr taamef a sal �Mion li sneumUJ_ mactim Ile' m marine with Chem) Fre Preen nAswems' and No, o, ren No. 17, 'Do and ComWMInuMMn Systems' Xo.fir ly -Flemmebb and ComWNM•Liaub'COdards. comply 13- an lonlan6'or n.re Codes ed Fror rote. ti-meavpem ant Ttobe 120m(29 RCt 49 at FEEL e¢nom-xp •Fm txO •f 1-X •cwO<I. pager I CNlnaan pa Agent. mea n em mm use PO CHEM monamMMIphosphate h n•'besM or sMl,m bicarbonate dry Mmmal aVnt. a-CYnmersamanufactured, Tm,a, and marked in accordance with 0350orDOT 4B Site N all b, used to more the suppren,ng agent. cvlmae. Moa,Ia My Suprom Seem lel ideri JAM 1. Ilwmv. inmeat .He= ei� Johnson ��I ,,.,..r..mBHaummnwla.0 inane are..�bl OlodOse Mlh,ul .I Dom No% 2m Controls 4 Suggested Architect's Specifications a4 -Manuel amnion, The system Shall have mw"n,wl (Continued)nual anuetion capability revuiriw no elmr,ul pnwr. This 15 +cwmpliened lousy byte iaiig Ne handle on the 2, CNlnen and Asset Wmanuea) m rEd Me MCH per Edi Control Heed, or mmotely der PCI-1MM sell W Hand with supprewing agent fin mans of a Model RM M mmmo me anal pull "ion. ",am 012.5 To IRA kgl. CVllmbr Models PCLI]ABC shall 3.5-Auxlllary output. Tne Wmm shall prorlde lar the m used Sixth sulmre,ebg agent fin wMgm of n is NM off poser to wwWwrn within the mz,ra and to VA 4)Clil r MNis PCLZUENTEBC shall be used whir vemilnion HeMms in the event Nryabm nowwon. This supmsev seem en ww9m of 25 to P r3 Lou cylinder is accomplished by Levine of do mnmN on a Model MNele PC"MBC shall be used Mtn suppmning agent Ml MBSFDT or M5 POT minlaWm mfth ln=IIW In me might M As to fish 4). Cylinder Models PCL50M C control heed, Tie min,Mm switch may sea be used shall be used Min wppmeeing agent fill weightm Far auxiliary fu=ion¢ such on, aalbie Mames or alarm Se to (22.6 ad. Epode Models PCI ]BABC shall be used olal with eupprwaing agent fill weight Ed 70 to (31.74), All C7 3.6-suwmv ion. AModel M Senn 3olenola Monhry moosleer, d wAJ with dry nnm9en to Me pale AT He ME M Nall W used he sugmiea the invegrM 0 all Meddwl ono 134 bar +19 TO L O a irn ciHER i whnhw+su mn¢ or manual. 23- Gen Mer valve. A peuuresee let pori pe we We W /� 3.7-Prolanion. A wWnnpra enclosure arsig End and haven a bra=e body, Smell mm with mbb•r nn e v aconformancen NWA r] n u installed lirinn waNbe assembly, poure pane• prodnm.cannot nand Wlhla.r wnan mttum.a moll enol be under Cn erg exam Wlim ul0,safety sem location, lis" Golders, Mimemen+u m useofaa 4. r4.nJ.' morel The The rnmaentondena,reamuse at - Mo to aMa.PVRo<xtM 41hargenintodk system borawx morning nonebracket axim toaaemunin+mpdmem _ N area.vie•mopinmahnnb dagent WM ,uppaNngdidMof the filled rylintlenna the cones. 0% ton, anoeWtion•fn•ra and area Themodel.be ason of Bound,, l tliscnarpe. lionm imm�,d.lowith, MONARCH a anels ban nn amrtlen¢ with MONARCX Intlunriel 3 rim Suppression Technical Menus man x0. -controlr Nnlmeueee 3.1-CotnpHtmiAead. laden nvi ModelMCH Hand. The mnhplmeatl IRCIHneayn.mer Han. Th L^B` WD] 0.2 -No At NMlb, nn,mlMl with A2 -I n mmeif In- emonted dieeen the N e el foreign ,f m n m Pm a clogging omAven,mtfreig dna at tta roam train =o a derllmmouMil I Me 1 Most MB Px W Y >� dischargenoaln. head(for osingle mountingelm to rally rq 9up Y 6 %send Flttlne P e lea Adopt a none vada ale n apntM tl 1 ofApul 'IHlmrtra kg 5b P" All emllm$M1eaule 4e boat Mewife n,ca c e eons W I a .A b amim the)complieswXF MILMW1G Nell be used as en'mryral chrome planta or a noel v pe m moo with sup e ends c EIV m NWA 17 All pope ends M+Il mdeate by aelrniieo hopor•a¢mu¢'n.um .AsoFDngsteStanda debomupMyreemcwwIp Ending, and all Ml. [moa. add senn¢mallmremov6d poor � 33 061nhe MmgnWreurMehaoN s.]-FlNnge, Standard weight malleable. galranbea, mTheamblenfi re.Nell be Temperature tarrmal chrome placed o, sdimess Smell finm9e Nall be used. itheoree dveMo temperature o peratu calhe dan or the heard of me hosts eine ex[naa Me MlnpMenyaelxYot the Excedsthe Wm. IN any system plPo g i3-dance l and fihiin swillbe aiNosu enem,.nal n MIM.. tannpn m e oboe wnn.eme m me evn accordance m. con rnnmol Manual. rvC.umfim. rClnoa.musing ... or nim, stamen sowed. a normaaanWn pillordel Idea normally Chain ew'mA1Mm 5An6Joms No joint mWano used tMepensure the detector, signal tome deeam Tape pfiion; Teflon ups maV be metl fig mop ensure SA a wnirn" neynn Her in axemame asilug fit, stage. the Impemmeamrorha.a. .+a Her Imperial systems . 1 [Peamaacen. 55 Straps, en discharge I .hall be,[mel p Wn re 1.p v 33 evea fastened by mems odor Intoe mane the shallPAgmores Agent e1.hansom R tri n bon aPown ba nae shallbe nan P set,' ren con Iv.Nixon, enuh^n 5.6- steal se unon.A umm� an.nmmulde in the discharge of the or hand.TM enaa mines convenflonflydamn me cylinder valve to osteo Man train m PAC MIT mr, M vntPp,add a.=onnNon far inson and seri. Emitting mamine ,.hellee re ,stove g Iroge capable Me name nam m each agent [rune.,. owning each seem [vomer mlve.na rem.ang the Pr.awrlma engem. w IIIb shipping A B MWd No. in.Immo in._ (man) C D Wnphl Moumnng Immo in. In. ImImmo IS (W) Bmdn FQ-16ABC 6.CO 11621 31.0 IOM VIA IM TM 1041 SO IA) MB 15 FO 24.81 (WBI Bin (no)22m ISWI 59 123) me is tempC (total=I FCI BGBC no Blame AN thus Idiomland 4 128) MB -15 MI -3Y 'd94 Carl ow Pepsi N.81 Carl 10.00 35.e (NUNN thusVAR Ideal 139) Me MCIam4BC PCI I0,03 (Mi (]BBI (Mi 36.0 Ii0) 22.58 18901 m (39) MB -I (M) N I m OFABCCIBC mn.Must PCI ]OABC IhW I]061 s.31 (MBI 41.N 11W31 32.Y I8271 150 (681 MB -I Series Sam Tire courvened values in „IcIa. Fred MEA MONaCendountSm..an Is Mi. .1 ... I an inde...dC r Fe ww U.,u„ Mi. Assay plain (j ) Monarch Fire Dry Chemical Suppression System �Sy Johnson Controls 10 Anther Architects, PLLC Architecture + Engineering 3727 Candia Drive Punta Gorda FL 33950 800-243-0528 734-709-7297 gburgh@gmail.com BURGH ARC 004081 THE l�T OF ME M� �MEWS IS TO armen ALL REWA� THE ROLE MMNT Mason MOSTLY REWA� MALL ork, "MEET award TO COMMOST 0 6N hear Rio. ei w 0 c Offing gels _O VilessessM Q Y 1--F O C0 Mi'=r U LL Fire Supression LS3 E O U <n C Cis MIDE CO OL ext C7 N M M Vr O >> L" '^ Vi W /� L c0 m oUa) Y L CO _ N � Grp V 0% J M C LO L^B` WD] U C) O >� all> d Fire Supression LS3