HomeMy WebLinkAbout35 Hillside DriveCity of Wheat Ridge
Residential Detached Garage PERMIT - 201800025
PERMIT NO: 201800025 •ISSUED: 02/09/2018
JOB ADDRESS: 36 Hillside Dr EXPIRES: 06/15/2019
JOB DESCRIPTION: Detached garage on slab; add 100 amp subpanel - 1,000 sq ft
**Revision adding a non load bearing wall 2x4 and 2 storage closets at
backside of garage 27LF
Valuation $400.00**
*** CONTACTS ***
OWNER (720)840-4414
TOLVE JOSH
SUB (720)458-8411
Scott Berkman
080190 Current
Installations
*** PARCEL INFO ***
ZONE CODE:
UA / Unassigned
USE:
UA / Unassigned
SUBDIVISION CODE:
2404 / APPLEWOOD
KNOLLS, PARAMOUNT HE BLOCK/LOT#:
0 /
*** FEE SUMMARY ***
ESTIMATED
PROJECT VALUATION:
28,400.00
FEES
Total Valuation
0.00
Plan Review Fee
317.23
Use Tax
596.40
Permit Fee
488.05
** TOTAL **
1,401.68
*** COMMENTS ***
*** CONDITIONS ***
Approved per plans and red -line notes on plans. Must comply with 2012 IRC, 2014 NEC and all
applicable City of Wheat Ridge Municipal Codes. Work is subject to field inspections.
I, the property owner, by my signature, attest that I currently reside at the project
property, intend to reside at the property for a period of one year after completion of the
project, and am personally performing all work, without the assistance of hired or
professional workers. Consultations and inspections will only be performed with the
homeowner of record present.
As part of the foundation inspection and PRIOR to the placement of concrete and before
proceeding with any further construction, a completed, signed and sealed, Foundation
Setback and Elevation Certification shall be submitted to the City for review. The
certification form shall be fully completed by a Professional Land Surveyor licensed in the
state of Colorado, stating that the foundation was constructed in compliance with all
applicable minimum setback and elevation requirements of the City.
Owner/Contractor is responsible for locating property lines and constructing improvements
according to the approved plan and required development standards. The City is not
responsible for inaccurate information submitted within the plan set and any construction
errors resulting from inaccurate information.
For one- or two-family dwellings, the first twenty-five feet (25') of driveway area
from the existing edge of pavement into the site shall be surfaced with concrete, asphalt,
brick pavers or similar materials. A right-of-way permit may be required; contact Public
Works Department at 303-235-2861.
NOT APPROVED AS AN INDEPENDENT DWELLING UNIT.
Landscaping removed or damaged during construction must be replaced prior to final
inspection.
I, by my signature, do hereby attest that the work to be performed shall comply with all accompanying approved plans and specifications,
applicable building codes, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized
by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with
this permit. I further attest that I am legally authorized to include all entities named within this document as partes to the work toe
performed and that all work to be performed is disclosed in this document and/or its' accompanying approved plans and specifications.
Signature of OWNER or CONTRACTOR (Circle one) Date
1. This permit was issued based on the information provided in the permit application and accompanying plans and specifications and is
subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures.
2. This permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and
received prior to the date of expiration. An extension of no more than 180 days made be granted at the discretion of the Chief Building
Official and may be subject to a fee equal to one-half of the original permit fee.
3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard
requirements, fees and procedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of
the Chief Building Official and is not guaranteed.
4. No work of any manner shall be performed that shall results in a changeof the natural flow of water without prior and specific approval.
5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all required
inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services
Division.
6, The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, an violation of any provision of any
applicable code or a dinance or e ulation of this jurisdiction. Approval of work is subject to field inspection.
Signature of Chief Building Official Date
REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY.
City of
W at iclg�
COMMUNITY DEVELOPMENT
City of Wheat Ridge Municipal Building 7500 W. 29' Ave. Wheat Ridge, CO 80033-8001 P: 303.235.2855 F: 303.237.8929
Permit Extension Repuest Form
Permits expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in
writing and received prior to the date of expiration. An extension of no more than 180 days may be granted at the
discretion of the Chief Building Official and may be subject to a fee equal to one-half of the original permit fee.
Re -issuance or extension of expired permits is at the sole discretion of the Chief Building Official and is not
guaranteed. Please complete this form in its entirety and submit to the Building Division at
permits(j�ci.wheatridgexo.us or fax to 303-237-8929.
Party requesting permit extension: �`�� /O —
Permit Property Address: '7>E Lli ��Sr �� l T l/%[C-�'�fi R"adcte—
Phone # Email Address: 14
Reason for extension request: G/zn r
J D SIS(V-C @ fflav CcsYvN
Number of days requested: DL ACX' 6( � !C o.� Ao
Printed Name: :5�4! �� Signature- "I f' �-- Date:
For office use only
This request has been ?Approv ❑ Denied Extended until: % f'"✓
Approved by: Date: � 11510
www.ci.wheatridge.co.us
o CITY OF WHEAT RIDGE
Building Inspection Division
(303) 234-5933 Inspection line
(303) 235-2855 Office • (303) 237-8929 Fax
INSPECTION NOTICE
Inspection Type: 301 AF E
Job Address:
Permit Number:���
❑ No one available for inspection: Time //jam AM/PM
Re -Inspection required: YesNo
When correcti�>yhve been made, call for re -inspection at 303-234Date: ��/� Inspector:
DO NOT REMOVE THIS NOTICE
i CITY OF WHEAT RIDGE
Building Inspection Division
(303) 234-5933 Inspection line
(303) 235-2855 Office • (303) 237-8929 Fax
INSPECTION NOTICE
Inspection Type: y
Job Address:
Permit Number: Q-01 80
No one available for inspection: TimeAM/PM
Re -Inspection required: Yes oNo
When correc 71i
ve been made, call for re-inspection at 303303-2
Date:_, 7 1 Inspector:— -i i
DO NOT REMOVE THIS NOTICE
i CITY OF WHEAT RIDGE
Building'Inspection Division
(303) 234-5933 Inspection line
(303) 235-2855 Office • (303) 237-8929 Fax
INSPECTION NOTICE
Inspection Type: O--) v� G
Job Address: 35MUCf/Df
Permit Number: 7101 190 11 S (4
❑ No one available for inspection: Time (Yi l�;_,.'AM/, M
Re -Inspection required: YesNo
When corrections have been made, call for re -inspection at 303-234-5933
i
Date: 1 Inspector:,
DO NOT REMOVE THIS NOTICE
I* � 4 s CITY OF WHEAT RIDGE
Building Inspection Division
(303) 234-5933 Inspection line
(303) 235-2855 Office • (303) 237-8929 Fax
INSPECTION NOTICE
Inspection Type: y63 y�
Job Address: 35' -
Permit Number: �W to_, O 115-y
Y
❑ No one available for inspection: Time AM/PM
Re -inspection required: oe No
When corrections have been made, call for ryes -inspection at 303-234-5933
Date: p //0 inspector: MT#
DO NOT REMOVE THIS NOTICE
IMMA
I* � 4 i CITY OF WHEAT RIDGE
Building Inspection Division
(303) 234-5933 Inspection line
(303) 235-2855 Office • (303) 237-8929 Fax
INSPECTION NOTICE
10
30- r %1tV X11 Stmt✓
Inspection Type: 3a 1 - /yl o ►`s-) f, re a m00%
Job Address: 3 S 6 et e PJ
Permit Number: � 0 1 g a 1 S y
❑ No one available for inspection: Time IQLS_& A PM
Re -Inspection required: Yes No
When corrections have been made, call for re -inspection at 303-234-5933
Date: (o o / Inspector:
DO NOT REMOVE THIS NOTICE
o CITY OF WHEAT RIDGE
BUIlding Inspection"Nvision
(303) 234-5933 Inspection line
(303) 235-2855 Office • (303) 237-8929 Fax
INSPECTION NOTICE
Inspection Type: Wvv h 02 -es)
Job Address: 25 / 5/dr 191 -
Permit Number:
❑ No one available for inspection: Time q:56) AM/PM
Re -Inspection required: Yes �No
When corrections have been made, call for re -inspection at 303-234-
Date:- 'S i Inspector:
DO NOT REMOVE THIS NOTICE
City of Wheat Ridge
Residential Plumbing PERMIT - 201801625
PERMIT N0: 201801625 ISSUED: 06/04/2018
JOB ADDRESS: 35 Hillside DR EXPIRES: 06/04/2019
JOB DESCRIPTION: Underground rough plumbing, installing 3 piece bathroom in unfinished
basement. 200 square feet.
*** CONTACTS ***
OWNER (303)918-0115 NASH BARBARA L
SUB (303)280-5765 Larry Benavidez 100318 Colorado Heating L Cooling
*** PARCEL INFO ***
ZONE CODE: UA / Unassigned USE: UA / Unassigned
SUBDIVISION CODE: 2404 / APPLEWOOD KNOLLS, PARAMOUNT HE BLOCK/LOT#: 0 /
*** FEE SUMMARY *** ESTIMATED PROJECT VALUATION: 2,000.00
FEES
Total Valuation 0.00
Use Tax 42.00
Permit Fee 77.50
** TOTAL ** 119.50
*** COMMENTS ***
*** CONDITIONS ***
All work shall comply 2012 International Codes, 2014 NEC (if applicable), and ordinances
adopted by the City of Wheat Ridge. Work is subject to field inspections.
I, by my signature, do hereby attest that the work to be performed shall comply with all accompanyingg approved plans and specifications;
applicable building codes, and all applicable municipal codes, policies and procedures, and that I am tl�e legal owner or have been authorized
by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with
this permit. I further attest that I am legally authorized to include all entities named within this document as parties to the work to be
performed and that all work to be performed is disclosed in this document and/or its' accompanying approved plans and specifications.
Signature of OWNER or CONTRACTOR (Circle one) Date
I. This permit was issued based on the information provided in the permit application and accompanyingplans and specifications and is
subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures.
2. This permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and
received prior to the date of expiration. An extension of no more than 180. days made be granted at the discretion of the Chief Building
Official and may be subject to a fee equal to one-half of the original permit fee.
3. If this permit expires, a new permit may be required to be obtained. issuance of a new permit shall be subject to the standard
requirements, fees androcedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of
the Chief Building Official and is not guaranteed.
4, No work of any manner shall be performed that shall results in a changeof the natural flow of water without prior and specific approval.
5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all required
inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services
Division.
6_ The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, an violation of any provision of any
applicable code or any ordinance or regulation of this jurisdiction. Approval of work is subject to field inspection.
Signature of Chief Building Official Date
REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY.
City of
W heat Midge
OMMUNI iy Di:vt:Loi,mUN I
Building & Inspection Services Division
7500 W. 29' Ave., Wheat Ridge, CO 80033
Office: 303-235-2855 * Fax: 303-237-8929
Inspection Line: 303-234-5933
Email: permits&.6wheatridge.co.us
FOR OFFICE USE ONLY
Date:
P1anlPermit #
Al
Plan Review Fee:
Building Permit Application
Please complete all highlighted areas on both sides of this form. Incomplete applications
may not be processA. ***
Property Address:
Owner
Property Owner Email:
Tenant (Commercial Projects Only)
Phone:
Property Owner Mailing Address: (if different than property address)
Address:
City, State, Zip:
Arch itectlEngineer E-mail:
P__
Contractor:
City of Wheat Ridge License
a,.
Contractor E-mail Address:L)'
22
.. "?
For Plan Review Questions & Comments (please pri ):
CONTACT NAME (please print): 1 ��1'�1 ! 0
CONTACT EMAIL(p/ease print): l ' ' UA21-_
Sub Contractors (Must provide Wheat Ridge License No.):
Electrical: Plumbing:
W.R. City License # W.R. City License #
Phone:
Phone:�'�
� ' z Phone: tl2 a6 '5 7�.
Other City Licensed Sub: Other City Licensed Sub:
City License # City License #
Mechanical:
W.R. City License #
6�
❑ COMMERCIAL RESIDENTIAL
Description of work. For ALL projects, provid a detailed description of work to be performed,
including current use of areas, proposed uses, square footage, existing condition and proposed new
condition, appliance size and efficiency- tvDe and amount of materials to be used, etq.
J,'-3 &4J LVA-nVl-�Jv-� roj�
I
J,0 4 610
Commercial Projects Only: Occupancy Type: Construction Type: _
Sq. FULF BTUs Gallons
Amps Squares
Project Value: (Contract value or the cost of all materials and labor included in the entire project)
s 3666, ()0
OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT
I hereby certify that the setback distances proposed by this permit application are accurate and do not violate applicable ordinances, rules or
regulations of the City of Wheat Ridge or covenants, dements or restrictions of record; that all measurements shown and allegations made are
accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance
with applicable City of Wheat Ridge codes and ordinances for work under any permit issued based on this application; that 1 am the legal owner
or have been authorized by the legal owner of the property to perform the described work and am also authorized by the legal owner of any
entity included on this application to list that entity 2===
uilding permit application, warrant the
truthfulness of the information provided on the app
CIRCLE ONE: (OWNER) (CO T1 COR)o WNER� (CrOt]VTRACTOR)
Signature (first and last name):
Printed Name:
ZONING COMMMENfS:
Reviewer.
BUILDING DEPARTMENT COMMENTS:
Reviewer.
PUBLIC WORKS COMMENTS:
Reviewer.
DATE:
OCCUPANCY CLASSIFICATION:
CONSTRUCTION TYPE:
Building Division Valuation:
City of Wheat Ridge
Residential Remodel PERMIT - 201801154
PERMIT NO: 201801154 ISSUED: 05/01/2018
JOB ADDRESS: 35 Hillside DR EXPIRES: 05/01/2019
JOB DESCRIPTION: Add new bathroom to existing storage space below garage with lav, shower
and toilet - 42 sq ft; new water heater 28 gallon, 4500 watt
***
CONTACTS ***
OWNER (303)918-0115
NASH BARBARA L
GC
(720)898-0272
Ernest Martinez
022046 REPAIRS UNLIMITED, INC
SUB
(720)732-2178
Jose Lara Soto
090307 New Age Electric, Inc.
SUB
(303)280-5765
Larry Benavidez
100318 Colorado Heating & Cooling
*** PARCEL INFO ***
ZONE CODE: UA / Unassigned USE: UA / Unassigned
SUBDIVISION CODE: 2404 / APPLEWOOD KNOLLS, PARAMOUNT HE BLOCK/LOT#: 0 /
*** FEE SUMMARY *** ESTIMATED PROJECT VALUATION: 25,898.95
FEES
Total Valuation 0.00
Plan Review Fee 294.81
Use Tax 543.88
Permit Fee 453.55
** TOTAL ** 1,292.24
*** COMMENTS ***
*** CONDITIONS ***
All roughs to be done at Framing Inspection.
Approved per plans and red -line notes on plans. Must comply with 2012 IRC, 2014 NEC and all
applicable City of Wheat Ridge Municipal Codes. Work is subject to field inspections.
I, by my signature, do hereby attest that the work to be performed shall comply with all accompanying approved plans and specifications,
applicable building codes, and all applicable municipal codes, policies and procedures, and that I , the legal owner or have been authorized
by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with
this,permit. further attest that I am legally authorized to include all entities named within this document as parties to the work to be
performe d that�l ork#¢ be performed is disclosed in this document and/or its' accompanying approved plans and specifications.
osloe t
Signature of O ' R or CONTRACTOR .kCircle one) Date
1 This permit was issued ba Qn_the_ aerination provided in the permit application and accompanying plans and specifications and is
subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures.
2. This permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and
received prior to the date of expiration. An extension of no more than 180 days made be granted at the discretion of the Chief Building
Official and may be subject to a fee equal to one-half of the originalpennit fee.
3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard
requirements, fees androcedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of
the Chief Building Official and is not guaranteed.
4. No work of any manner shall be performed that shall results in a change, of the natural flow of water without prior and specific approval.
5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all required
inspects and shall not oceed or conceal work without written approval of such work from the Building and Inspection Services
Divisi
6. The : nce o grantin a permit shall not be construed to be a permit for, or an approval of, an violation of any provision of any
apple an r regulation of this jurisdiction. Approval of work is subject to field inspection.
Signature of Chief Building Official Date
REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY.
City of Wheat Ridge
Residential Remodel
PERMIT - 201801154
PERMIT N0:
201801154
ISSUED:
05/01/2018
JOB ADDRESS:
35 Hillside DR
EXPIRES:
05/01/2019
JOB DESCRIPTION:
Add new bathroom to existing
storage space below garage with lav, shower
and toilet - 42 sq ft;
new water heater 28 gallon,
4500 watt
I, by my signature, do hereby attest that the work to be performed shall comply with all accompanying approved plans and specifications,
applicable building codes, and all applicable municipal codes, policies and procedures, and that I , the legal owner or have been authorized
by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with
this,permit. further attest that I am legally authorized to include all entities named within this document as parties to the work to be
performe d that�l ork#¢ be performed is disclosed in this document and/or its' accompanying approved plans and specifications.
osloe t
Signature of O ' R or CONTRACTOR .kCircle one) Date
1 This permit was issued ba Qn_the_ aerination provided in the permit application and accompanying plans and specifications and is
subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures.
2. This permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and
received prior to the date of expiration. An extension of no more than 180 days made be granted at the discretion of the Chief Building
Official and may be subject to a fee equal to one-half of the originalpennit fee.
3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard
requirements, fees androcedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of
the Chief Building Official and is not guaranteed.
4. No work of any manner shall be performed that shall results in a change, of the natural flow of water without prior and specific approval.
5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all required
inspects and shall not oceed or conceal work without written approval of such work from the Building and Inspection Services
Divisi
6. The : nce o grantin a permit shall not be construed to be a permit for, or an approval of, an violation of any provision of any
apple an r regulation of this jurisdiction. Approval of work is subject to field inspection.
Signature of Chief Building Official Date
REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY.
City of
Wheat�dge
_AC110""'vAUN1T-, DFVELOPMENT
Building & Inspection Services Division CA�
7500 W. 29th Ave., Wheat Ridge, CO 80033
Office: 303-235-2855 * Fax: 303-237-8929
Inspection Line: 303-234-5933
Email: permits(d)-ci.wheatridge.co.us
FOR OFFICE USE ONLY
Date: ) / 5117
/
Plan/Permit # 2
Plan Review Fee:
Building Permit Application
*** Please complete all highlighted areas on both sides of this form. Incomplete applications
may not be processed. ***
Property Address: 35 Hillside Dr, Wheat Ridge, CO 80215
Property Owner (please print): Barbara Nash Phone: 303-918-0115
Property Owner Email: barb. nash(a)-comcast.net
Tenant (Commercial Projects Only) n/a
Property Owner Mailing Address: (if different than property address)
Address:
City, State, Zip:
Architect/Engineer: n/a
Architect/Engineer E-mail:
n/a
Contractor: Repairs Unlimited, Inc.
Phone:
City of Wheat Ridge License M 022046 Phone: 720-898-0272
Contractor E-mail Address: lizh(cb-repairs-unlimited.com
For Plan Review Questions & Comments (please print):
CONTACT NAME (please print): Lonnie Scull Phone: 720-380-4773
CONTACT EMAIL(please print): Ionniesa-repairs-unlimited.com
Sub Contractors (Must provide Wheat Ridge License No.):
Electrical: Nc--w A(s-(-,-, Plumbing: Mechanical:
W.R. City License # W.R. City License # W.R. City License #
Other City Licensed Sub: Other City Licensed Sub:
City License # City License #
❑ COMMERCIAL
RESIDENTIAL
Description of work: For ALL projects, provide a detailed description of work to be performed,
including current use of areas, proposed uses, square footage, existing condition and proposed new
condition, appliance size and efficiency, type and amount of materials to be used, etc.
5k ACe. 6t.cnW6W-14;1A In.A\lt
WA► -L• Co N 5`TfZ-u GZ.. 1�6 r.1 5A)f LL, LT -1A rzZ1--4iG- D 13or r m P -AT- A�Ajll
AUL WASTE BRAT -/o$ WKS,.- f IV �C:tC��7 e> PEI- l,u 4rcl6 wt-1�c,
P�AA v a- sT n; � � c 5 AND PC, V - C0) �`I ► u �{ -t� A �
-- NEW LVA Ao Stnn'€ 3vL-L45 DV3
Commercial Projects Only: Occupancy Type:
Sq. Ft./LF
Amps
BTUs
Squares
Construction Type:
Gallons
Project Value: (Contract value or the cost of all materials and labor included in the entire project)
$ Z s t 19q 's q 11�7
OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT
I hereby certify that the setback distances proposed by this permit application are accurate and do not violate applicable ordinances, rules or
regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown and allegations made are
accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance
with applicable City of Wheat Ridge codes and ordinances for work under any permit issued based on this application; that I am the legal owner
or have been authorized by the legal owner of the property to perform the described work and am also authorized by the legal owner of any
entity included on this application to list that entity on this application. 1, the applicant for this building permit application, warrant the
truthfulness of the information provided on the application.
CIRCLE ONE: (OWNER) (COIN RACTR (A BORIZED REPRESENTATIVE) of (OWNER) (CONTRACTOR)
Sienature tfirst and last name►: % DATE: 4/1IZO $
Printed Name: Lonnie Scull
DEPARTMENT USE ONLY
ZONING COMMMENTS OCCUPANCY CLASSIFICATION: 011?CONSTRUCTION TYPE:
Reviewer:
BUILDING DEPARTMENT COMM N'TS'':,^, AAss
Reviewer: �lJwv'
PUBLIC WORKS COMMENTS:
Reviewer:
Building Division Valuation:
9'
City of
Wh6atI�idge
COMMUNITY DEVELOPMENT
SUB -CONTRACTOR AUTHORIZATION FORM
wLa�A-az7F,j,
Project Address: 35 41: L -S-10(-- VQm_- Wl-2(5 Permit #:
General Contractor: ae- rA tip �_ r p,.�r�h
Contractor
Company N� ne: ��� n � �,� Phone #: � .� 32 8
State Licjn ill #: 7q 74 3 Master #: :A I o
Signat'of Authorized Agent
Plumbing Contractor
Lr E_.0, - I R
Date
Company Name: Q_c)) n qac U one � - 5-7 (v
State License #:(-)(p a g55 Master #: nC) (p -7 0
Wheat Ridge License #: 1 (7) O `3 j (j�-'
" ignature of Authorized Agent Date
Mechanical Contractor
Uompany Name:
Wheat Ridge License #:
Signature of Authorized Agent
Phone:
Date
*This application must be signed by each sub -contractor confirming the same.
hCity of SEE ATTCHED SHEETS FOR ADDITIONAL REQUIREMENTS
eat f d,�e FOR THIS PROJECT
COMMUNITY DEVELOPMENT
City of Wheat Ridge Municipal Building 7500 W. 291b Ave. Wheat Ridge, CO 80033-8001 P: 303.235.2855 F: 303.237.8929
Review is limited to the contents of the plans submitted and any errors or omissions contained herein shall not be
construed as permission to allow any conditions to exist in violation of the codes of the City of Wheat Ridge
Rough Framing and Wood Requirements
3 The complete rough inspection is to be made after the rough framing, rough electric, rough plumbing, and
rough heat and ventilation are complete. The building should be fully enclosed with the roof covering and
siding in place.
4 Protection from decay shall be provided in the following locations by the use of naturally durable wood or
wood that is preservative treated in accordance with AWPA U1: (IRC R317)
5 Basements greater than 200 square feet and every sleeping room shall have at least one operable
emergency and rescue opening or a door to the exterior.
6 Emergency escape and rescue openings shall meet the following requirements: A minimum clear width
of 20 -inches, a minimum clear height of 24 -inches, with a total net clear opening of 5 square feet for grade
level windows and 5.7 square feet for all others. A sill height of not more than 44 inches measured from
the finished floor to the bottom of the clear opening. Window wells for emergency escape and rescue shall
provide a minimum net area of 9 square feet with minimum horizontal projection and width of 36 -inches.
The area of the widow well shall allow the emergency escape and rescue opening to fully open. (IRC R310)
7 Fire blocking shall be installed to cut off all concealed draft openings in the following locations: (IRC
302.11)
A. In concealed spaces of stud walls and partitions, including furred spaces, vertically at the ceiling and floor
levels, and at 10 -feet horizontal intervals. B, At interconnections between concealed vertical and horizontal
spaces such as occur at soffits, drop ceilings, and cove ceilings. C. In openings around vents, pipes, ducts, cable,
wires, chimneys, fireplaces, and similar openings that afford a passage for fire at ceiling and floor levels. D. In
concealed spaces between stair stringers at the top and bottom of the run, and between studs in line with the
run of the stairs at unfinished walls.
8 Ceiling heights for habitable rooms, hallways, bathrooms, toilet rooms, laundry rooms, and basements
shall be a minimum of 7 -feet measured from the finished floor to the lowest projection of the ceiling. Non -
habitable basements may have a ceiling height of 6 -feet, 8 -inches with clearance below beams and ducts
of 6 -feet, 4- inches. Bathroom may have a ceiling height of 6 -feet, 8 -inches at the fixture front clearance
area and over the fixture. (IRC R305.1)
CRY of
9 All habitable rooms shall be provided with aggregate glazing area for natural light of not lespQaa�18% of
Q;
the floor area of such rooms. The glazed areas need not be installed in rooms where sectio rkjM1507�°
Il�/�
satisfied and artificial light is provided at an average of 6 foot candles at a height of 30 inches.n g -
10 Safety glazing shall be installed in the following hazardous locations and be permanently labeled as
safety or tempered glazing: glazing panels in doors; glazing enclosing spas, bathtubs or showers; glazing
panels adjacent
and within 24 -inches of the edge of a door; glazing panels greater than 9 square feet within 18 -inches of the
floor; glazing used for railings; glazing used for barriers for swimming pools and spas; and glazing enclosing
stairways, landings, and ramps within 36 -inches horizontally of a walking surface. See the Boulder County Land
(IRC R308)
Heating and Ventilation Requirements
I1 A, Habitable rooms must be provided with outdoor openings for ventilation equal to at least 4% of the
floor area and shall have heating facilities capable of maintaining 68' at 3 -feet above the floor and 2 -feet
from exterior walls. B. The windows need not be openable in a room where an opening is not required to
be an egress window and a mechanical ventilation system is capable of producing 0.35 air change per hour
in that room, or a whole house mechanical ventilation system provides 15 cubic feet of outdoor air per
minute.
12 Bathroom exhaust fans shall exhaust directly to the exterior and must be provided in bathrooms where
windows of at least 3 square feet are not provided. The mechanical ventilation must be capable of
providing an exhaust capacity of 50 cfm intermittent or 20 cfm continuous exhaust. (IRC R303.3, M1507.4)
13 Appliances and equipment shall be installed in accordance with the conditions of their listing.
Manufacturer's installation instructions must be available at the time of the inspection. (IRC G2408.1,
M1307.1, M1401.1,(M1902.2)
14 Appliances shall be accessible for inspection, service, repair and replacement without removing
permanent construction. 30 -inches of working depth and width shall be provided in front of the control
side of an appliance. (IRC M1305.1)
15 Combustion air is required for all liquid fuel, solid fuel and gas appliances. (IRC M1701.1, G2407)
16 Gas burning appliances may not be located in or obtain combustion air from: a sleeping room,
bathroom, toilet room, or storage closet unless it is a direct vent appliance or installed in an enclosure that
opens only into a bedroom or bathroom in and such enclosure is provided with a solid weather-stripped
door, a self-closing device and all combustion air is taken from the outdoors. (IRC G2406.2)
Electrical Requirements
17 All hot, neutral, and grounding conductors in electrical boxes shall be tied together with a mechanical
City or
connection at the time of rough inspection.
Wheot 9e
18 Recessed lighting fixtures must either be IC -rated or installed in a sealed box in which the insulatig,}&ns
P least 3 -inches from the light fixture. All recessed lights must be tightly sealed or gasketed to prevent air9p'��sio,)
leakage through the fixture into the ceiling cavity. (IRC N1102.4.5)
19 Tamper -resistant Receptacle outlets are required in every kitchen, family room, dining room, living
room, parlor, library, den, sunroom, bedroom, recreation room or similar dwelling areas spaced so that no
point along the wall line exceeds 6 -feet from an outlet. (IRC E3901, E3902, and 4002.1-4002.14)A. Counters
12 -inches in width or wider shall have receptacles placed no more than 20 -inches above the counter top
and spaced so no point exceeds 24 -inches from an outlet. B. Island and peninsula counters with a length at
least 24 -inches and a width of 12 -inches or greater must be equipped with at least one outlet. C. At least
one receptacle shall be installed in a bathroom within 36 -inches of each basin. D. A least one receptacle
outlet must be installed in each laundry, basement, attached garage and detached garage with power. E.
At least one receptacle outlet that is accessible while standing at grade level and located not more than6-
feet, 6 -inches (1981 -mm) above grade, shall be installed outdoors at the front and back of each dwelling
unit having direct access to grade. Balconies, decks, and porches that are accessible from inside of the
dwelling unit and that have a usable area of 20 square feet. F. Attics or crawlspaces containing equipment
must be provided with at least one receptacle outlet within25-feet of the equipment. G. Hallways 10 -feet
or more in length.
20 Two 20 -amp rated branch circuits shall serve receptacles in the kitchen, pantry, breakfast area, and
dining area. At least one 20 -amp branch circuit shall supply bathroom receptacles and at least one 20 -amp
branch circuit shall supply laundry. (IRC E3703.2, E3703.3, E3901)
21 Ground fault protection shall be provided on all 125 -volt, single phase, 15 and 20 -amp receptacles in the
following locations: bathrooms, garages, unfinished grade level accessory buildings, at exterior locations,
crawlspaces, unfinished basements, kitchen counters, within 6ft. of laundry, utility and wet bar sinks,
boathouses, hydro massage, spa and hot tub locations. Receptacles must be in a readily accessible location.
(IRCE3902, E3902.11)
22 Combination type Arc -Fault circuit interrupters must be installed on all 120 -volt 15 and 20 -amp branch
circuit outlets in Receptacle outlets are required in every family room, dining room, living room, parlor,
library, den, sunroom, bedroom, recreation room, hallway, closets, and similar dwelling areas. (IRC
3902.12)
23 Smoke alarms shall comply with UL 217. Smoke alarms are to be powered by the building's wiring
operated light. (IRC E3903)with battery backup and shall be interconnected so the actuation of one alarm
will activate all alarms in the dwelling unit. Smoke alarms shall be installed in the following locations: (IRC
R314) A. In each sleeping room; B. Outside each sleeping area in the immediate vicinity of the bedrooms;
and C. One on each additional story including basements.
24 Carbon Monoxide alarms are required in a single-family dwelling that has fuel -fired appliance(s), or a
fireplace, or an attached garage. The alarm must be installed within 15 -feet of the entrance to each
sleeping room. Must be listed by a nationally recognized, independent lab. Plugs into a dwelling's electrical
outlet and has a battery backup. They may be combined with a smoke -detecting device if the combined
device complies with applicable law. (IRC R315)
City of
Wheat Ridge
25 Working space must be provided around energized equipment for servicing and maintenance. The
minimum dimensions shall not be less than 36 -inches in depth and 30 -inches in width in front of th�6iing Division
equipment. Working space shall extend to at least 6 -feet, 6 -inches above the floor. (IRC E3405.2)
26 Electrical fixtures installed in wet or damp locations shall be installed so that water cannot enter or
accumulate n wiring compartments or other electrical parts. Fixtures installed in wet locations must be
labeled "suitable for wet locations". Fixtures installed in damp locations must be labeled "suitable for
damp locations" or "suitable for wet locations". Switches or circuit breakers located in wet locations or
outdoors must be enclosed in a weatherproof enclosure. Outdoor receptacles must have a weatherproof
enclosure and an in -use cover. Cord -connected fixtures, hanging fixtures, track lighting, pendants, and
ceiling fans shall not be located within3-feet horizontally and 8 -feet vertically from the top of a tub or
shower rim. (IRC E4003.9, E4002.8, E4002.9,(E4002.10, E4003.9, E4003.10,E4003.11)
Plumbing Requirements
27 DWV systems shall be tested on compellation of the rough piping installation by water or for piping
system other than plastic by air with no evidence of leakage. Either test shall be applied to the drainage
system in its entirety or in sections after rough piping has been installed .1) Water test 10 feet above the
highest fitting connection or to the highest point of the completed system. The system shall prove leak free
for 15 minutes. 2) Air test shall maintain 51bs of pressure for 15 minutes.
28 All piping must be inspected and tested prior to concealing. It shall be protected against physical
damage and it must be approved for use and bear the identification of the manufacturer. (IRC P2503,
P2603, P2608.1)
29 Bathtubs, walls above bathtubs with shower heads, shower floors, and shower compartments shall be
finished with a non-absorbent surface which extends to a height not less than 6' above the floor. Showers
must have a minimum 900 square inches of interior area and a minimum dimension in each direction of
30 -inches.
Shower valves must be pressure balance/thermostatic mixing valves. Shower receptors shall have a curb
threshold not less than 1 -inch below the sides and back of the receptor. The curb shall measure a minimum of
2 -inches to a maximum of 9 -inches above the top of the drain. (IRC R307, P2708, P2709)
30 The centerline of toilets or bidets shall not be less than 15 -inches from adjacent walls or tub. Toilets,
bidets, and lavatories must have a minimum clear space of 21 -inches in front of the fixture. Lavatories
require a 4 -inch clearance to wall or to a toilet. (IRC P2705)
31 Showers and tub/shower combinations shall have control valves of the pressure balance, thermostatic
mixing or combination pressure balance/thermostatic mixing valve types with high limit stop per ASSE 1016
or CSA13125.1. Tubs shall also have a control valve as listed for a shower or a water -temperature -limiting
device that conforms to ASSE 1070. The high limit stop for a device shall be set to a maximum of 120`. (IRC
P2708.3,P2713.3)
32 Shower doors shall have safety glazing; hinged show door shall open outward. (R308.4.5, P2708.1)
City of
Wheat Ridge
Building Division
Insulation
65 R-20 Walls
R-49 Ceiling
R-19 Crawlspace Window
U -Factor .32 Floor R-30
66 Supply Ducts in attics shall be insulated to a minimum of R-8. All other ducts shall be insulated to minimum
R-6. ( N 1103.2. 1)
67 Combustible insulation shall be separated a minimum of 3 -inches from fan motors and heat -producing
devices. Insulation shields must be provided where vents pass thorough insulated assemblies and must
terminate at least 2 -inches above attic insulation materials. Can lights must be airtight if located in the building
envelope. (G2426.4)
68 Class I or II vapor retarders are required on the interior side of the insulation in framed walls, floors and
roof/ceilings of the building's thermal envelope. The vapor barrier is not required in construction where
moisture or freezing will not damage the materials, or where the framed cavity (or space) is ventilated to allow
moisture to escape. A vapor retarder is not recommended on a concrete basement foundation wall or in a
shower/bath compartment (IRC 702.7, R702.7.1).
Wallboard Requirements
69 Enclosed accessible space under stairs shall have walls, under stair surface and any soffits protected on the
enclosed side with %-inch gypsum board (IRC R302.7).
70 Nail spacing for gypsum board 1/ gypum board Ceiling 16oc, 7", nails 12", Type S screws 'h wall spacing
24"OC, 8" nail spacing. 12"OCscrews. 5/8 ceiling board 16"OC, 7"nailsl2"spacing, screws 24OC 8".
72 Water-resistant gypsum backing board used as the base or backer for adhesive application of ceramic tile or
other required nonabsorbent finish material shall conform to ASTM C1396, C1178 or C1278. It is permitted on
ceilings where framing spacing does not exceed 12 -inches o.c. for %-inch thick or 16 -inches o.c. for 5 8 -inch
thick gypsum board. Water-resistant gypsum board shall not be installed over a vapor retarder in a shower or
tub compartment and may not be used where there will be direct exposure to water, or in areas of continuous
high humidity. All cut and exposed edges shall be sealed. (IRC R702.3.8)
73 Floor assemblies, not required elsewhere in this code to be fire resistance rated, shall be provided with a
inch gypsum wall board membrane, 5/8 inch wood structural panel membrane, or equivalent on the underside
of the floor framing member.(IRC 501.3)
7500 W. 29n Ave
Wheat Ridge, Co 80033-8001
City of
Wheat Ridge
Building Division
r
IG` qP
S-QkA6L CobIVA
41 WGey 4
�i heatWg
MUNnY DM DPMENT
APPROVED
Reviewed for Code compliance
L - - q /2-). (�
4x"..
ammer Date
VaNdiity of uermit The issuance of a permit a opProvol of PWm specife tfoms
orad compulations sholl not be a permit for, of on opprovol0f, any viWaWri to
ony of the provisions of the bwlding code or of ony City ordinomm. permits
presum4g to give authority to violate of cancel the provisions of the lWOO
f vj�EN Dolga
FZ]
�3, toll
rG C:5 -I A d
l`b"x3�C"
r
�C
11
A LV
2a(5AL-d q S v,)k -F , Wry I
f
.YO/
I
4Y,34
21(
rf
QQ
,Ac -
pec Kbbm
2 /5
5
Iv,
crew
TV -1b" icc) 60Z,15
L�-)Nll,� Tll,�G-
q
W-tNCLW
4t
F,
q.
0
co
9
FOR OFFICE USE ONLY
City of pate:
,1(??7Wh6at e
991
COMMUNITY UNI EVELOP Et' IT PtanJP rmit
Building Inspection Services Division � �
7600 W. gIAve., Whet Ridge, CO 80033 Plan Review
Office: 303-235-2855 * Fax: 303-237-8929
Inspection Line: 303-234-5933
BuIldingPermit Application
Please oomplate all hightighted wvas onboth, si of this form. Incompleile spolostions may not be pr
ProOwner (please print):Phone: .... N .
..,°..
Mailing dress: (if different than property address
Address:
(mit �fte,`i
r
rch tectlEngin`E-mail: Phone.-
Contractor: n g,—
Contractors City icen a *. _ Phorw,
Contractor E-mail Address:
Sub Contractors:
Electrical; Plumbing: Mechanical:
W.R. City License # W.R City License # W.R. City License
AP .RVA . - X C,00
Other City Licensed Saab: Other City Licensed Sub.
City License # (3L� i City License ##
. E le.
_. " ..
Complete all information on BOTH skies of this form
$ NEW COMMCIA STRUCTURE $ <; w w»-*■»
NEW R\ \ / STRUCTURE $COMMERCIAL^/e■FI
■
COMMERCIAL \■ITION $ RESIDENTIAL ROOFI
$ t SDENT /`AD 2,■\ WINDOW REPL�
$COMMERCIAL ACCESSORY ^
r (Garage,shed,deck, 7—�
■
RESIDENTIAL /%ACCESSORY STRUCTURE (Garage, shed, deck,
$
MECHANICAL«/ SYSTEM/APPLIANCE \§� REPAIR orREPLACEMENT
@ t \ %B /\\\/ SYSTEM/APPLIANCE REPAIR IR or RELACMENT
$ 2< - »SYSTEM/APPLIANCE
/{, REPLACEMENT
/<<:\\ / \
.F LF ^ / °l. mea Gallons.
A . . .... . a.\ y:Squares. .»..... .«\ Other
I
m
BE
I
-W
C
C-1
LU
cy-
a
4E'31
-31
on
I
50
4k
In
41-- P# I -') f Vt
Address:
City, State, Zip:
• •
jotidn ofj� (Fully describe work to be performe - Attach additional sheet if necessary)
* .:rdt rl �:� I* I all
r
*
S quares B A *..
Reviewer:
PUBLIC WORKS COMMENT&
Reviewer
FIRE DEPARTMENT:.' 0 approved wl comments El disapprove(
OC CUPANCY:
no review required Bldg Valuation:
City License # City License # City License
4,
Zb
I T
❑ No one available for inspection: /T
Re-Inspection required: Yes /No
When corrections have been madj �,& I
Date: Inspector:
DO NOT REMOVE " 7
• CITY OF WHEAT RIDGE
Building Inspection Division
(303) 234 -5933 Inspection line
(303) 235 -2855 Office' (303) 237 -8929 Fax
INSPECTION NOTICE
Inspection Type MAE
Job Address 35 s`fe /sic OR .
Permit Number
" 1 City of Wheat Ridge
]�� Residential Mechanic PERMIT - 102399
PERMIT NO: 102399 ISSUED: 10/15/2010
JOB ADDRESS: 35 HILLSIDE DR EXPIRES: 10/15/2011
DESCRIPTION: Replace 6500 CFM swamp cooler
* ** CONTACTS * **
owner - 303/232 -7877 Barbara Nash
sub 303/456 -7995 Paul Fortenberry 07 -0062 American Heat Cool
** PARCEL INFO
**
ZONE CODE:
UA
USE:
UA
SUBDIVISION:
0675
BLOCK /LOT #:
0/
** FEE SUMMARY ** ESTIMATED PROJECT VALUATION: 4,200.00
FEES
Permit Fee 40.00
.
Total Valuation 00 ,
Use Tax 75.60 C ' U �
** TOTAL ** 115.60
Conditions:
Must comply w/ 2006 IRC & 2005 NEC.
Subject to field inspections.
I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable
ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all
measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this
application and that I assume full responsibility for compliance with the Wheat Ridge Building Code (I.B.C) and all other
applicable Wheat Ridge Ordinances, for work under this permit. Plans subject to field inspection.
Signature of contractor /owner date
1. This permit was issued in accordance with the provisions set forth in your application and is subject to the laws of the
State of Colorado and to the Zoning Regulations and Building Codes of Wheat Ridge, Colorado or any other applicable
ordinances of the City.
2. This permit shall expire 180 days from the issue date. Requests for an extension must be received prior to expiration
date. An extension may be granted at the discretion of the Building Official.
3. If this permit expires, a new permit may be acquired for a fee of one -half the amount normally required, provided no
changes have been or will be made in the original plans and specifications and any suspension or abandonment has not
exceeded one (1) year. If changes have been or if suspension or abandonment exceeds one (1) year, full fees shall
be paid for a new permit.
4. No work of any manner shall be done that will change the natural flow of water causing drainage problem.
5. Contractor shall notify the Building Inspector twenty -four (24) hours in advance for all inspections and shall receive
written approval on inspection card before proceeding with successive phases of the job.
G. The issuance of a permit or the approval of drawings and specifications shall not be construed to be a permit for, nor
an approval of, any olation of the provisions of the building codes or any other ordinance, law, rule or regulation.
All plan review s ject to f d in ections.
Signature ldin cia date
INSPE ON REQUEST LINE: (303)234 -5933 BUILDING OFFICE: (303)235 -2855
REOUE S MUST BE MADE BY 3PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY.
jd
Date:
�
CO MMUNITY D LOPMENT Permit #: lLI M
" X�7A
!Pud 7600 . 29 Ave., Wheat Ridge, CO 80033
Office: 303 -235 -2855 * Fax: 303 - 237 -8929
Inspection Line: 303 - 234 -5933
Facsimile Building Permit Application
PAWMAMMM 35 Fitt 2 Stn p �>2
Property Owner (please print): 13 I3 8 KI A811 Phone:
Mailing Address: (if different than property address)
Address:
City, State, Zip:
Qym � YN I (jg n) R z- A CO(`1 L
Contractor License #: Phone:
Company ryame. License #: Expiration Date: Trade /Profession: Approval:
Use of space. (desc'ription): ( ,,e i _ ��
c� ��.
Plan Review (due at Gme of submittaO: $
Sq. Ft. /L. Ft added: L Squares BTU's Gallons Amps
OWNERICONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT
I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances,
rules or regulations of the City of Wheat.Ridge or covenants, easements or restrictions of record; that all measurements shown, and
allegations made are accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full
responsibility for compliance with the Wheat Ridge Building Code (I.B.C) and all other applicable Wheat Ridge Ordinances, for work
under this permit. Plans subject to- field - inspection.
CIRLCEONE:t(OWNE (CONTRACTOR or PERSONAL REPR ENTATIVE ; (OW N TRATOR)
PRINT NAME: SIGNATURE: �� Y �Z " rr " �� Date: /6 Ya
Bldg valuation; $
Credit Card Payment: Use credit card listed on file: Date'
Print name: Signature:
♦ i CITY OF WHEAT RIDGE
Bung Inspection Division
(303) 234-5933 Inspection line
(303) 235-2855 Office • (303) 237-8929 Fax
INSPECTION NOTICE
Inspection Type: lcl'41 L _oo
Job Address: ,i75 !~./1S i~S z~6
Permit Number: : 1CC)o3c)
r'-r 9xV4 7V r~F, ssr - ~P t 4 ~ of 1 r~afsz
El No one available for inspection: Time 2' ® AM$ M,~
Re-Inspection required: es No
When corrections have been made, call for re-inspection at 303-234-5933
Date: / k, Inspector:
DO NOT REMOVE THIS NOTICE
r
♦ i CITY OF WHEAT RIDGE
r Building Inspection Division
1 (303) 234-5933 Inspection line
(303) 235-2855 Office • (303) 237-8929 Fax
INSPECTION NOTICE
Inspection Type: pmf
Job Address: 35 ~f' 1 S T' Dr,
I Permit Number: f~€ n
❑ No one available for inspection: Time Ir AMM
Re-Inspection required: Yes 00
*When corrections have been made, call for re-fn action t 3Q3-234-5933
Date: inspector:
PC,
DO NOT REMOVE THIS NOTICE
♦ i CITY OF WHEAT RIDGE
Bung Inspection Division
r' (303) 234-5933 Inspection line
(303) 235-2855 Office • (303) 237-8929 Fax
INSPECTION NOTICE
Inspection Type: 11N,d'iar
Job Address: ?S I-1,116 4e Ar,
Permit Number: F XG~f(1
❑ No one available for inspection: Time 11 I M PM
Re-Inspection required: Yes No
'When corrections have been made, call for rej. nspection at 303-234-5933
Date: Inspector: A 61
DO NOT REMOVE THIS NOTICE
of W"~"'R City of Wheat Ridge Building Division
~Om 7500 W. 29th Ave., Wheat Ridge, CO 80033
Office: 303-235-2855 " Fax: 303-235-2857
oo<oRn°° Inspection Line: 303-234-5933 ,
Building Permit Application
a 3~ I A tSlol~ ~r.
Date: 115,~112, .
Plan
-ermit 9d,tojD
Property Owner (p/ease print): Y h(~ f N~,~;~ Phone: 3 _Ci 19-0 1 Is
Mailing Address: (if different than property address)
Address: I A &(d Q A_ 14 • ~~^^City, State, Zip: kol n I l l ~~S J g o7 S
Rock a~,
Contractor License Phone: 7J - ~2 ~-7 cJ
Electrical City License Plumbing City License Mechanical City License
Company: Company Company:
Exp. Date: Exp. Date: Exp. Date:
Approval: nApproval: Approval:
Use of space (description): _l G (i\1 n 1 t eS( I Sit no Construction value: $ ~ q I n 3~
- (as calculated per the Building Valuation Data sheet)
Plan Review (due at time of submittal): $
Lo1 ooe t0 eii- mace
Sq. Ft./L.Ft added: Squares 0 BTU's Gallons Amps
OWNERICONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT
I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances,
rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurementg:-shown, and
allegations made are accurate; that I have read and agree to abide by all conditions printed on this application and that [,assume full
responsibility for compliance with the Wheat Ridge Building Code (I.B.C) and all other applicable Wheat Ridge Ordinances, for work
under this pennit. Plans subject to e d inspection.
CIRLCE ONE' (O R) ONTRACTOR) r PERSONAL REPRESENTATIVE of(OWNEIR~) (CONTRATOR)
PRINT NAME: .1JM. ,VI(,ZtR CO SIGNATURE: /I-.KUJIALt`x.ir tOlA-QC~ Dater
f -SO
i
I
Ci y ot Wheat Ridge
,
R side~tial Mechanic PERMIT - 07
,
i
I
I
1OE: Dj<
175K ~TU Boiler
i
89
PERMIT NO:
JOB ADDRESS:
DESCRIPTION:
070089
35 HILL
install
ISSUED: 02/05 2007
EXPIRES: 08/04 2007
50 gal. water heat r
01-8464 B & F Hating & A/C
install
***
CONTACTS ***
303/431-891
303/232-787
303/420-1516
I
J.I Patrick Quinlan
B.INash/S. Schafer
I
gc
owner
sub
01-7875 Coffman Electric, Inc
*- PARCEL INFO --
ZONE CODE: UA
SUBDIVISION: UA
USE: UA
BLOCK/LOT#: 0/
-- FEE SUMMARY --
ESTIMATED PROJECT VALUATION:
FEES
217.50
.00
217.50
Permit Fee
Total Valuation
** TOTAL **
Comments:
Electrical
Subject to
must mee 2005 6EC
field in pecti~
I hereby certify that the etback ~8tance8 proposed by this permit application are accurate,
ordinances, ruleeor regul tions Ofl the City of Wheat Ridge or covenant~, easements or restrict
measurements shown, and al egations made are accurate; that I have read and agree to abide by a
application and that 1 ass me full ~esponsibility for compliance with the Wheat Ridge Building
applicable Wheat Ridge Ord nances, ifar work under this permit. plans subject to field inspectio
<-/'5)<7")
date
1.
er I
This permit was issued n accor~ance with the provisions set forth in your application and i
State of Colorado and t the zo~ing Regulations and Building Codes of Wheat Ridge, Colorado
ordinances of the City. i
This permit shall expir 180 da~s from the issue date. Requests for an extension must be rec
date. An extension may be gran~ed at the discretion of the Building official.
If this permit expires, anew p~rmit may be acquired for a fee of one-half the amount normal
changes have been or wi I be ma4e in the original plans and specifications and any suspensi
exceeded one (1) year. If chanses have been or if suspension or abandonment exceeds one (1)
be paid for a new permi . I
No work of any manner s 11 be done that will change the natural flow of water causing a dr
Contractor shall notify the Bui~ding Inspector twenty-four (24) hours in advance for all in
written approval on ins ection qard before proceeding with successive phases of the job.
The issuance of a permi or theiapproval of drawings and specifications shall not be constr
an approval of, any vio ation o~ the provisions of the building codes or any other ordinanc
All plan review is subj ct to f~eld inspections.
I
I
2.
3.
,.
5.
6.
Signature of Chief Building Officali
INSPECTION REQUEST INS. (303)234-5933
REQUESTS MUST BE E BY 3PM ANY BUSINESS
date
8,811.00
d do not violate applicable
ons of record; that all
I conditions printed on this
ode (I.B.C) and all other
subject to the laws of the
r any other applicable
ived prior to expiration
y required, provided no
or abandonment has not
year, full fees shall
nage problem.
ections and shall receive
d to be a permit for, nor
law, rule or regulation.
BUILDING OFFICE: (303)235- 855
DAY FOR INSPECTION THE FOL WING BUSINESS DAY.
Feb 05 07 11:46a
Patt~ Schmidt
303-421- 28B
COMMUNITY DEVELOPMENT DEPARTMENT
BUILDING INSPECTION LINE - 303-l34-6933
CITY OF WHEAT RIDGE
7500 WEST 29TH AVENUE
WHEAT RIDGE, CO 80033 - (303-l35-2855)
APPLlCA TlON
Property Owner: &rbNaSh ../ Sac SchaFer"
Property Address: ::55 II;;/sicle Dri 1/(
Contmclor License No_: l'il 1./ (p '-I
Company: B.j..~ [-Ieo.tin TC~'1.LD#04110
p.2
Buildi 9 Permit Number: ,--; J -:;-J... .
Date ~5((J '1
P e3fl'? Z32 ~j?,/I(
: 303 '-1-3/ 89/,-/
OWNERiCONTRACTOR SIGNAlURE OF UNDeRSTANDING AND AGREEMENT
Bulldino DeDf. Va atlon Figure: $
I hereby certify that the setbock distances proposed by this permit application a"re
accurate. and do not violate applicable ordinances. rules or regulations of the City of
\fIJheat Ridge or eovena nts, easements or restridions of record: thai all measurements
sho'Ml. and allegations made are accurate: that I have read and agroe to abickl by all
conditions printed on this application and that I assume full responsibility for
compliance with the Wleat Ridge Building Code(I.B.C) and all other applicable Wleat
Ridge Ordinances. for work under ~permjt. Plans ubject to fieid inspection.
(""fiER '~';mACTS'GN .i;;:uc.'~ , ./.-,;d DAT~"7
(cmN (CONTIlACTOR :PRINTED ];ifr; C)t::l JI,[CAl?lidfDATE '51&1
alue:$ ~/I d/
Pe t Fee: $ :;?/'1,2/
Plan Reyie ,. Fee:$
Use of Space (description): . ,
Description of work: 7nS-/tz II rl S OOtJ 81Z1 's :fib/ /f'i('
...LaSkl/ SOlq//P,7 lurK l/ea:fo'Z.
Sq. Ft. added
BUlLDING DEPARTMENT USE ONLY
ONING COMMENTS:
Approval:
Zoning:
BUILDING COMMENTS:
Approval:
PUBliC WORKS COMMENTS:
Approved:
IRE DEPARTMENT COMMENTS:
Approval:
Occu nc
Stories:
Residentia Un~s:
Walls:
Roof.
Electrical License No: /1f7.5-
companYr.:r%""'ll Ot'clrfc
Expiration Date:
A roval:
Total:$ .2"'750
51
Sq.Ft.:
Plumbing License No:
Company:
Mecha cal License No:
Compa y:
Expiration Date:
A roval:
Date:
(1) This permitwas issued in accordance with the provisions set forth In your application and issubje ta the Iewsofthe Sl8teaf
Colorada and to the Zoning Regulations and Building Codesofwtleat Ridge. Colorado or anyoth r applicable arclinlncesaf
the City.
(2) This permit shall expire if (A) the work authorized is not commenced w;thin sixty (90) days from tie date or (B) the building
authorized is suspended or abandoned for a period of 1 SO days.
(3) If this permit expires, a new pennit may be acquired for a fee of one-hatfthe amount nonnaly feq ired, provided no changes
have been Of will be made in the original plans and specifICations and any ,uspension aT abando nt has not exc:eeded one
(1) }'Gaf. If changes have been orffsuspension or abandonmont exceeds ono (1) year, fullfeos s II be paid fora newpe~.
(4) No work of any manner shall be done thai win change the natural flow of water causing a ckaina e prolMm.
(5) Contractor shaa notify the BuIlding Inspector twenty~four (24) hours In advance for all inspectio and shen receiw written
approval on inspection card before proceeding 'Nith successive phasos of the job.
(6) The issuance of a permit or lhe approval of drawings and specifteations shall not be construe to be 8 pennie. for. nor an
approval of, any violalion of the provisions of the bulldlrtg codes or any other ardinanee, law, Ie or regulation. All plan
review is subject to field inspections.
Chief Building Official