HomeMy WebLinkAbout3032 Ingalls Court� zolyoe5j 3 August 20, 2018 Cameron Cuyler 3032 Ingalls Ct. Wheat Ridge, CO 80214 RE: Engineer's Foundation Opinion and Certification To Whom It May Concern, The scope of our work was to inspect the installation of the foundation stabilization helical pier systems designed by our firm. LEVEL Engineering LLC has inspected the above referenced single family residence. This letter reflects our observations. The foundation has a standard concrete cast in place partially reinforced 8 in thick foundation of various heights placed spread footings. The foundation structure has experienced a settlement on the southeast corner of the main house and portions of the detached garage structure. This is a partial repair of the main house and garage structure. LEI has designed a system to secure the foundation from significant further movement. Implementation was done by Complete Basement Systems. This is to certify that LEVEL Engineering LLC, to the best of our knowledge, has concluded that this foundation helical pier system was installed as directed and designed. The foundation underpinning system will benefit the foundation in the future and improve its structurally competency. If you have any questions or concerns ur findings, please feel free to contact us. 0 UC� Sincerely, 0:� S Cott Z E. (#28253) Our inspection and findings are limited to wor od t dstatements contained herein by LEVEL Engineering, LLC (LEI) and we have not made any determinations on other issues hit y ffe life and safety concerns. Our findings ore based on conditions of the time of inspection. Structural elements hidden from view c not a evaluated and therefore LEI does not predictor warrant future performance of existing ctrurturra I FVFI Fnginrrring I I r tntnl lin ili ' s are mutually agreed by all parties to be limited to the fees charged. All objections to the terms and findings within this document must be made in writing within five days of this report. i CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type: RF I Job Address: O; 2 / �J (-TA LLQ' Permit Number: 2QJ 1Z Z3) 3 CQ( (M2 ❑ No one available for inspection: Time A PM Re -Inspection required: Yes No When corrections` have been made, call for re ' pect'on at 309-234-5 ( 933 Date: 11� Inspector: —" jj,44�_ DO NOT REMOVE THIS NOTICE i CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax Inspection Type: Job Address: Permit Number: INSPECTION NOTICE CA\ -",5Q, k ❑ No one available for inspection: Time °`I i� AM/PM Re -Inspection required: YC No When corrections have been made, call for re -inspection at CD3=�34`=5933 Dater• '3 4 - /c/ Inspector: l 1, DO NOT REMOVE THIS NOTICE i CITY OF WHEAT RIDGE Building Inspectior bivisi mn (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type: t09- C a s Sans i), e C- -5 Job Address: '3o3-0 C-� Permit Number: -P o J S o a 3 1 3 �1SSonrotied Vn b t -o I oco,+e roved( rJl�ns- T{► Q Y are re q v i`1 O-� WorL'- S�CkeC Uce i ❑ No one available for inspection: Time g= 3 gy/pM Re -Inspection required: Ye No When corrections have been made, call for re -inspection at 303 -234 - Date: 9 a - / 8 Inspector: `T b DO NOT REMOVE THIS NOTICE a City of Wheat Ridge y , Residential Foundation Repair PERMIT - 201802313 PERMIT NO: 201802313 ISSUED: 09/13/2018 JOB ADDRESS: 3032 Ingalls Ct EXPIRES: 09/13/2019 JOB DESCRIPTION: Foundation stabilization with reinforcement steel *** CONTACTS *** OWNER (970)218-0303 CAMERON CUYLER SUB (303)805-8751 Rodney Martin 060125 Complete Basement Systems *** PARCEL INFO *** ZONE CODE: UA / Unassigned USE: UA / Unassigned SUBDIVISION CODE: 2405 / BARTHS, COULEHAN GRANGE, WHEAT BLOCK/LOT#: 0 / *** FEE SUMMARY *** ESTIMATED PROJECT VALUATION: 19,000.00 FEES Total Valuation 0.00 Plan Review Fee 225.52 Use Tax 399.00 Permit Fee 346.95 ** TOTAL ** 971.47 *** COMMENTS *** *** CONDITIONS *** Approved per plans and red -line notes on plans. Must comply with 2012 IRC, 2017 NEC and all applicable City of Wheat Ridge Municipal Codes. Work is subject to field inspections. I, by my signature, do hereby attest that the work to be performed shall comply with all accompanying approved plans and specifications; applicable building codes, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with this permit. 1 further attest that Ism le ally authorized to include all entities named within this document as parties to the work to be performs, and that all work t�eibe�pe Ottned is disclosed in this document and'X) its' accompanying approved plans and specifications. Signaturel,�f OWNER or--Cb3�I�CTOR (Circle one) Date 1. This permit was issued based on the information provided in the permit application and accompanying plans and specifications and is subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures. 2. This permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and received prior to the date of expiration. An extension of no more than 180 days made be granted at the discretion of the Chief Building Official and may be subject to a fee equal to one-half of the original permit fee. 3. If this permit expires, a new permit may be required to be obtained. Issuance of a new pen -nit shall be subject to the standard requirements, fees androcedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of the Chief Building Official and is not guaranteed. 4. No work of any manner shall be performed that shall results in a changeof the natural flow of water without prior and specific approval. 5. The pen -nit holder shall notify the Building and Inspection Services Division in accordance with established policy of all required inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services Division. 6. The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, anviolation of any provision of any applicable code or ordinance or gulation of this jurisdiction. Approval of work is subject to field inspection. Signature of Chief Building Official Date REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. City of Wheat l �dgie_ COMMUNiTy DEVELOPMEN r Building & Inspection Services Division 7500 W. 2911 Ave., Wheat Ridge, CO 80033 Office: 303-235-2855 * Fax: 303-237-8929 Inspection Line: 303-234-5933 Email: perm its(o)ci.wheatridge.co.us FOR OFFICE USE ONLY Date: Plan/Permit # �'1 Plan Review Fee: 1 c , Building Permit Application *** Please complete all highlighted areas on both sides of this form. Incomplete applications may not be processed. *** Property Address: 3032 Ingalls Ct Property Owner (please print): Cuyler Cameron Phone: 970-218-0303 Property Owner Email: cuylerc(a_gmail.com Mailing Address: (if different than property address) Address: City, State, Zip: Architect/Engineer: Level Engineering Architect/Engineer E-mail: Scott Zurn Phone: 720-408-0119 Contractor: Rod Martin's Complete Basement Systems Contractors City License #: 60125 Phone: 303-805-8751 Contractor E-mail Address: kayla.montez(a�completebasementsystems.net For Plan Review Questions & Comments (please print): CONTACT NAME (please print): Kayla Montez Phone: 303-805-8751___ CONTACT EMAIL(p/ease print): kayla.montez(a)_completebasementsystems.net Sub Contractors: Electrical: W.R. City License # Other City Licensed Sub: City License # City License # Plumbing: W.R. City License # Other City Licensed Sub: Mechanical: W.R. City License # Complete all information on BOTH sides of this form ❑ COMMERCIAL 2 RESIDENTIAL Description of work: (Check all that apply) ❑ NEW COMMERCIAL STRUCTURE ❑ ELECTRICAL SERVICE UPGRADE ❑ NEW RESIDENTIAL STRUCTURE ❑ COMMERCIAL ROOFING ❑ COMMERCIAL ADDITION ❑ RESIDENTIAL ROOFING ❑ RESIDENTIAL ADDITION ❑ WINDOW REPLACEMENT ❑ COMMERCIAL ACCESSORY STRUCTURE (Garage, shed, deck, etc.) ❑ RESIDENTIAL ACCESSORY STRUCTURE (Garage, shed, deck, etc.) ❑ MECHANICAL SYSTEM/APPLIANCE REPAIR or REPLACEMENT ❑ PLUMBING SYSTEM/APPLIANCE REPAIR or REPLACMENT ❑ ELECTRICAL SYSTEM/APPLIANCE REPAIR or REPLACEMENT 4VOTHER (Describe) Foundation Stabilization (For ALL projects, please provide a detailed description of work to be performed, including current use of areas, proposed uses, square footage, existing condition and proposed new condition, appliance size and efficiency, type and amount of materials to be used, etc.) Sq. Ft./LF Amps Btu's Squares Gallons Other Project Value: (Contract value or the cost of all materials and labor included in the entire project) $ 19,000 OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance with applicable City of Wheat Ridge codes and ordinances for work under any pen -nit issued based on this application; that 1 am the legal owner or have been authorized by the legal owner of the property to perform the described work and am also authorized by the legal owner of any entity included on this application to list that entity on this application. 1, the applicant for this building permit application, warrant the truthfulness of the information provided on the application. CIRCLE ONE: (OWNER) (CONTRACTOR) or (AUTHORIZED REPRESENTATIVE) of (OWNER) (CONTRACTOR) Signature (first and last name): ylaoCO/.1V h1 a DATE: 08/20/2018 DEPARTMENT USE ONLY ZONING COMMENTS: OCCUPANCY CLASSIFICATION: Reviewer: BUILDING D PART ENT CO MENTS: Reviewers Building Division Valuation: $ 8 ° a AAA G o r r �• Z �� 7 �,� �,"� � o •C3 � °o' a. °w G7 cD CD ^ Irl LA ch C ch � 1� ' a n �` g o a rp ` FID n fD• • CSD � Ci � € C E 4 �� 0.nCD 0 CD � � ? � �4� s 'D caD oz AL G •'•. Z '� ✓•�� c o f��F;� `�`, • a �` (" S= CD •� y C>.6 CD P.- -- rl xc COO 00 rr PV CD -- OVERALL LENGTH[EXTENSION]- OVERALL LENGTH [LEAD[ SHAFT LENGTH [EXTENSION] 4.30 3 x OIAMETER OF 3 x DIAMETER OF 3 DI R OF 3 x DIAMETER OF _ HELIX PLATE Ki HELIX PLATE art ELI PLATE �03 �1 XXX ILAT�E $4 rn A t 7. y ' 3 X X D x1 D D d :_ m M ❑ a W ZO D r j D t] A g u m 2 y N p ❑ N m ❑ G f•1 iv D A ML" D �o Y.00 1.50 o G C h m W .O{ C MAX 3 no w O 00 Z!o G N11rd y C3 M 4 8 r D n O X m � r .o y 7C ❑ z -1 m z = z c W = o z ❑ m L jy N x A < � o £ N N Wco A F, NXD v v $ r � m x m LA N o � r x o E � N N z I N J N ci -�xsssxxm-4 O M m m m nr X V r mu N :_ W ~y f W J X1 x a W ZO N j D t] A D = r1 ❑ G f•1 iv D xnl �o in V UI A U 000000�i �o y W .O{ ❑ m W A r o 0 0 0 0 T r N� N11rd m N 7C ❑ z m x z N z �> � rxcvvp�poyoa �,,, a> -- a < yx. [m, 7pQeD 9,p f3• rm ((��--ii Yin 5. Z7pn Z�a•'�^,1Cr� Tl2 �5 n� p rl- m r >p>y St�Ao rprprye� yy .y n 'yry G> G1= Y. "I 'd'•nl'n a hl n n X�prY yK ya pr� irumi ..t to 7:s xp'w r1 m Cf ^�o 3 Pe�s�yrm m� 98<o ntiL'v -1� 7 y OGptr FF o tl v�'� n0 rf Fy ig d.y�s-pi i�• p>�in OOn a'L ptiir yU1+nr RF PpSi it ;J n o p�Hl��mA°, n PFFD wp o 5 twin �mtvn O,,.a yywt/.�'m t -my r�r •>>0 �7m x z m Yno XF s j 'J'j. Yl anm° iein'xe y.�m t+f Qy t�y� A ^� H �O 9i�n t�-1"rtI rtI CQ%P m "'tel 26 � m�•y 9rC7 rv„ O �° r- Q o n 0 r C►Iy 01 V4,,ieat 9-ldge b .-r •; O� 0• 00 C x CD O � C n O Y CD CD O• II -'l W { -- .,rg= it - � o w W. (a INr � Ul .l%P LNa — G P g �I aV 1 �./�1n tte� t n i t, 1�� 1 II� �fy City w 'peat Ri V rl5i] u . ov C N cD v b w 00 C CCD CD y Iii= cC�� wX71 ConfNumard t� 1 * A\ �1 M- r 0190131 3 1/11// Y PLAN OF REPAIR FOR Mr. Cameron Cuyler 3032 Ingalls Ct. Wheat Ridge, CO 80214 Reference #: 20180721 Job # 3083 July 21, 2018 Scott A. Zurn, PE" 01M STRUCTURAL GENERAL CONDITIONS Contractor shall maintain comprehensive general liability, workman's compensation, automobile liability and/or other insurance as appropriate for the work performed which will provide protection form any and all construction or completed operations claims. Certificates of Insurance shall be provided to LEVEL ENGINEERING LLC and/or the Client upon request. The limits will not be less than the minimum mandatory amounts required by the State of Colorado. All construction shall be performed in accordance with all applicable codes and standards, and good construction practices. Contractor shall obtain and pay for any and all permit fees, taxes and licenses required by governing agencies to complete the work. Contractor shall be responsible for all labor, materials, equipment, tools, operations and any other item necessary for proper completion of the work. Contractor should visit site prior to bid submittal to fully understand the scope of the project and the conditions at the site. By submitting a bid for the work proposed in this PLAN of REPAIR, the contractor is implying that they have fully reviewed all associated documents and that they have full understanding of the work to be completed. The Contractor shall conduct a full review of this PLAN of REPAIR prior to beginning work. If during this review or at any time during the construction process the contractor notes any errors or omissions in the plan, work shall be stopped and LEVEL ENGINEERING LLC shall be contacted immediately. Recommendations and specifications contained herein are based on general assumptions of the conditions, some of which cannot be observed during typical nondestructive visual observations. If unexpected conditions are encountered during the course of work, the Contractor shall contact LEVEL ENGINEERING LLC prior to proceeding. The Client shall provide water and electric hook-ups for temporary use. (Contractor must pre -arrange with Owner.) All utility lines and easements shall be located, marked and protected from damage throughout the performance of the work. Contractor shall call for utility locations unless other arrangements are made. Any damage to utility lines caused by the Contractor shall be repaired at the Contractor's expense. Contractor shall field verify all dimensions and existing conditions prior to commencement of work. Contractor shall notify LEVEL ENGINEERING LLC upon determination of any significant variation of the information provided on the attached documentation for his/her interpretation and decision, and such decision shall be final. Information provided regarding the existing conditions are believed to be accurate, however, Contractor shall be responsible for, and shall only use, his/her own measurements to verify existing conditions. 2 1 407 N LINCOLN AVE. SUITE 104, LOVELAND CO 80537 1 MAIN: 720.408.0119 I ADIVIN@LEVELI f 011 Ck co.COM �R�d9e NNXIea THE REPAIR DESIGN Prepared by LEVEL Engineering, LLC makes no provisions for construction conditions that may arise during the performance of the work. Contractor shall be responsible for maintaining the stability and integrity of existing structures (bracing, shoring, benching, etc.). Contractor shall be responsible for the acts or omissions of his/her agents and subcontractors in the performance of their work. The Contractor shall be responsible for the means, methods, techniques, and sequences of construction. Existing material or property outside the scope of work that is damaged during construction shall be repaired to match their pre -construction condition at Contractor's expense. Unless noted otherwise, no substitutions or deviations from the repair plan and specifications are permitted without the express approval of LEVEL ENGINEERING LLC. Unauthorized modifications to the repair plan and specifications may deem the work unacceptable. All unacceptable work shall be promptly correct at the Contractor's expense under the direction of the LEVEL ENGINEERING LLC. Contractor shall maintain safe jobsite. The Contractor is to stack all necessary equipment and materials in a low traffic rea or in an area that will insure the safety of all individuals potentially present at this site during construction. OSHA standards shall be used as a guideline. Contractor shall keep the jobsite thoroughly clean at the end of each day. All surplus materials shall be safely stacked in a low traffic area or hauled away from the site. Contractor agrees to perform the work in a diligent manner and in full conformance with the repair plan. If a condition arises during the repair process which requires a change in the scope of work, LEVEL ENGINEERING LLC may submit addendums or modifications to the design which may add, delete or modify the scope of repair. Performance of any extra work, or payment for same, shall only be considered upon prior written authorization from Client. This document is for bid purposes only, The Contractor shall be responsible for utilizing a qualified Colorado Licensed Professional Engineer to inspect the repair work and to verify that the repair specifications described within this document are in compliance with local building codes and applicable Manufacturer standards. The proposal shall include a description of the Contractor's Warranty Terms and Conditions was well as Warranty Limitations. The proposal shall also include a description of the system as applicable. 3 1 407 N LINCOLN AVE. SUITE 104, LOVELAND CO 80537 1 MAIN: 720.408.0119 1 ADMIN@LEVELINSPECTI F City 01 COM CONCRETE All concrete shall conform to the most recent editions of the Building Code and ACI 318 adopted by the governing agencies in which the project is to be completed. All concrete shall have a 28 day compressive strength of 3000 psi. All concrete shall have a maximum aggregate size of 3/4" and no pea -gravel shall be used without written approval of this office. Minimum concrete coverage for steel reinforcement shall be as follows: Concrete cast against and permanently exposed to earth .......................... 3" Concrete cast in forms and exposed to earth or weather No. 6 bar and larger..................................................2„ No. 5 bar and smaller .... :........................................... 1-1 /2" Concrete not exposed to weather or in contact with ground .......................1-1 /2" Non -shrink grout shall conform to ASTM C-1 107 Care shall be taken to properly consolidate concrete thoroughly without causing segregation of the materials. STEEL REINFORCEMENT All reinforcement steel shall be deformed bars conforming to ASTM A-615, grade 60. Welding of steel reinforcement shall conform to AWS D-1.4. Provide chairs concrete blocks, spacer bars, ties, etc. As required to securely hold bars in place. When reinforcement must be spliced the bars should overlap at least 24', UNO. Overlapping bars shall be securely tied together with wire ties. Provide a minimum concrete cover of 3" where concrete is cast on the surface of the ground and 1-12" at all other locations, UNO. STRUCTURAL STEEL AND BOLTS All steel fabrication and installation shall conform to the latest addition of the AISC Manual of Steel Construction. All welding shall be completed by a certified welder using an AWS prequalified welding method in accordance with the requirements specified by the AWS in the structural welding code. E70xx electrodes shall be used for welds. I.--"' ow 61 4 1 407 N LINCOLN AVE. SUITE 104, LOVELAND CO 80537 1 MAIN: 720.408.0119 1 ADMIN@LEVELINSPECTIONSCOfOM Vvf ez 9iWe '3116103 All structural steel shall conform to ASTM A-36, UNO. All wide flange beams shall conform to ASTM A-572, grade 50. All pipe columns shall conform to ASTMA-53, grade B or A-501 All tube steel shall conform to STM A-500, Grade B. Bolts and all -thread shall comply with ASTM A-325 Epoxy for epoxy bolts shall be Hilt! Hit HY-150 or approved equal. Expansion bolts shall be Hilti Kwik Bolt III Expansion Anchors or approved equal. HELICAL PIERS/SOIL ANCHORS The Helical Pier and concrete contractor shall be fully experienced in all aspects of helical pier installation. SPECIFICATION FOR HELICAL PILE FOUNDATIONS COMPRESSION APPLICATIONS 1 SCOPE 1.1 The work consists of designing, furnishing and installing helical piles and load transfer devices used to support compressive loads according to the project Plans and these specifications. 1.2 The parties and contract terms referred to in this specification are asfollows: 1.2.1 The Owner is the person or entity that owns the facility or will own the facility once it is completed. The Owner may have contractual agreements with, and be represented by, other parties such as engineers, architects or contractors that perform services under the direction of the Owner. Where Owner is used in this specification, it refers to the owner or the Owner's contracted representatives separate from the Installing Contractor. 1.2.2 The Pile Designer is the individual or firm generally hired by the Installing Contractor to design the helical piles. 1.2.3 The Installing Contractor installs and tests (if necessary) the helical piles, and possibly performs other tasks associated with the project. 1.2.4 The Plans refer to the contract documents; including but not limited to the drawings and specifications for the project. 1.3 The work may include helical pile load testing. 5 1 407 N LINCOLN AVE. SUITE 104, LOVELAND CO 80537 1 MAIN: 720.408.0119 1 ADMIN@LEVELINSPECTIO city ).COM WViieat Ridge DN 1.4 The Owner will be responsible for obtaining any right-of-way or easement access permits necessary for the helical pile installation. 1.5 Unless otherwise noted, the Installing Contractor shall provide all labor, tools, equipment and materials necessary to accomplish thework. 1.6 The Owner will provide suitable access to the construction site forthe Installing Contractor's personnel and equipment. 1.7 Unless specifically noted otherwise in the contract documents, the Owner will remove and replace any structures, utilities, pavements, landscaping orother surficial improvements in the work area as necessary to facilitate the work. 1.8 The Owner will be responsible for overall construction oversight to preclude the development of unsafe conditions. 1.9 The Owner will be responsible for a horizontal field survey of the helical pile locations prior to helical pile installation and an elevation survey to determine pile shaft cutoff height subsequent to helical pile installation. 1.10 The work does not include any post -construction monitoring of pile performance unless specifically noted otherwise in the contract documents. 2 REFERENCES 2.1 American Institute of Steel Construction (AISC) 2.1.1 AISC 360: Specification for Structural Steel Buildings 2.2 American Society for Testing and Materials (ASTM) 2.2.1 ASTM A36: Carbon Structural Steel 2.2.2 ASTM A123: Zinc (Hot -Dip Galvanized) Coatings on Iron and Steel Products 2.2.3 ASTM A 153: Zinc Coating (Hot -Dip) on Iron and Steel Hardware 2.2.4 ASTM A307: Carbon Steel Bolts, Studs, and Threaded Rod 60000 PSI Tensile Strength 2.2.5 ASTM A325: Structural Bolts, Steel, Heat Treated, 120/105 ksi Minimum TensileStrength 2.2.6 ASTM A500: Cold -Formed Welded and Seamless Carbon Steel Structural Tubing in Rounds and Shapes 2.2.7 ASTM A513: Electric -Resistance Welded Carbon and Alloy Steel Mechanical Tubing 2.2.8 ASTM A572: High -Strength Low -Alloy Columbian -Vanadium Structural Steel 2.2.9 ASTM B633: Electrodeposited Coatings of Zinc on Iron and Steel 2.2.10 ASTM D1143: Deep Foundations Under Static Axial Compressive Load 2.3 International Code Council Evaluation Services (ICC -ES) 2.3.1 Acceptance Criteria 358 (AC358): Acceptance Criteria for Helical Pile Systems and Devices 2.4 Society of Automotive Engineers (SAE) 2.4.1 SAE J429: Mechanical and Material Requirements for Externally Threade anerP,y 6 1 407 N LINCOLN AVE. SUITE 104, LOVELAND CO 80537 1 MAIN: 720.408.0119 1 ADMIN@LEVELINSPECTI N.COf� 3 DEFINITIONS 3.1 The following terms apply to helical piles used to support compressive loads: 3.1.1 Allowable Stress Design: A structural and geotechnical design methodology that states that the summation of the actual estimated loads (nominal loads) must be less than or equal to the allowable design load (required strength). Allowable loads areobtained by dividing a nominal resistance (strength) by an appropriate factor of safety. 3.1.2 Bearing Stratum: The soil layer (or layers) that provide the helical pile end - bearing capacity through load transfer from the helical plates. 3.1.3 Crowd: Axial compressive force applied to the helical pile shaft as needed during installation to ensure the pile advances at a rate approximately equal to the helix pitch for each revolution. 3.1.4 Design Loads: A generic and ambiguous term used to describe any load used in design. It is not specific to factored or unfactored loads or any particular design methodology. It is a term; therefore, that should be avoided when specifying load requirements. FSI recommends using the term service load, nominal load or factored load, as described herein, where applicable. 3.1.5 Design Strength: A term used in structural design which is defined as the product of the nominal strength and the applicable resistance factor. An equivalent term typically used in geotechnical design is, also sometimes referred to as factored resistance (Load and Resistance Factor Design). 3.1.6 Extension Section: Helical pile shaft sections connected to the lead section or other extension sections to advance the helix plates to the required bearing depth. Plain extensions (without helix plates) or helical extensions (with one or more helix plates) may be used depending upon soil conditions or project requirements. 3.1.7 Factor of Safety: The ratio of the ultimate pile capacity or nominal resistance (strength) to the nominal or service load used in the design of any helical pile component or interface (Allowable Stress Design). 3.1.8 Factored Load: The product of a nominal load and an applicable load factor (Load and Resistance Factor Design). 3.1.9 Factored Resistance: The product of a nominal resistance and an applicable resistance factor (Load and Resistance and Factor Design). 3.1.10 Geotechnical Capacity: The maximum load or the load at a specified limit state, that can be resisted through the piles interaction with the bearing soils (see also Ultimate Pile Capacity). 3.1.11 Helical Pile: Consists of a central steel shaft with one or more helix -shaped bearing plates and a load transfer device (bracket) that allows attachment to structures. Helical piles are installed into the ground by application of torque and axial compressive force ("crowd"). 3.1.12 Helix (Helical) Plate: Generally round steel plate formed into a helical spiral and welded to the central steel shaft. When rotated in the ground, the ix C![, shape provides thrust along the pile's longitudinal axis thus aiding in ile 7 1 407 N LINCOLN AVE. SUITE 104, LOVELAND CO 80537 1 MAIN: 720.408.0119 1 ADMIN@LEVELINSPE 10N SC , installation. The plate transfers axial load to the soil through bearing. 3.1.13 Helix Pitch: The distance measured along the axis of the shaft between the leading and trailing edges of the helix plate. 3.1.14 Lead Section: The first helical pile shaft component installed into the soil. It consists of one or more helical plates welded to a central steel shaft. 3.1.15 Limit State: A condition beyond which a helical pile component or interface becomes unfit for service and is judged to no longer be useful for its intended function (serviceability limit state) or to be unsafe (ultimate limit state (strength)). 3.1.16 Load and Resistance Factor Design: A structural and geotechnical design methodology that states that the Factored Resistance (Design Strength) must be greater than or equal to the summation of the applied factored loads. 3.1.17 Load Factor: A factor that accounts for the probability of deviation of the actual load from the predicted nominal load due to variability of material properties, workmanship, type of failure and uncertainty in the prediction of the load (Load and Resistance Factor Design). 3.1.18 Load Test: A process to test the ultimate pile capacity and relation of applied load to pile head settlement by application of a known load on the helical pile head and monitoring movement over a specific time period. 3.1.19 Loads: Forces that result from the weight of all building materials, occupants and their possessions, environmental effects, differential movement, and restrained dimensional changes. Permanent loads are those loads in which variations over time are rare or of small magnitude. All other loads are variable loads (see also Nominal Loads). 3.1.20 Mechanical Strength: The maximum load or the load at a specified limit state that can be resisted by the structural elements of a helical pile. 3.1.21 Net Deflection: The total settlement at the pile head minus the theoretical elastic deformation of the pile shaft during a load test. 3.1.22 Nominal Loads: The magnitude of the loads specified, which include dead, live, soil, wind, snow, rain, flood and earthquakes (also referred to as service loads or working loads). 3.1.23 Nominal Resistance: The pile capacity at a specified ultimate limitstate (Load and Resistance Factor Design). See Ultimate Pile Capacity. 3.1.24 Nominal Strength: A term used in structural design which is defined as the structure or member capacity at a specified strength limit state. See Ultimate PileCapacity. 3.1.25 Resistance Factor: A factor that accounts for the probability of deviation of the actual resistance (strength) from the predicted nominal resistance (strength) due to variability of material properties, workmanship, type of failure and uncertainties in the analysis (Load and Resistance Factor Design). 3.1.26 Service Loads: See "Nominal Loads" above. 3.1.27 Ultimate Pile Capacity: The helical pile capacity based on the least capacity determined from applicable ultimate limit states for mechanical and geotechnical capacity. 01 8 1 407 N LINCOLN AVE. SUITE 104, LOVELAND CO 80537 1 MAIN: 720.408.0119 1 ADMIN@LEVELINSPECTIONSCO.yuN1^'r1��i Rtlokog ®i'v 1="'� 1.1 SCOPE OF WORK The work shall consist of the Helical Pile Contractor furnishing all labor, tools, equipment, materials and supervision to install Helical Piles according to the specifications contained herein and shown on the construction drawings. The Helical Pile Contractor shall install a helical pile which will provide a minimum load capacity as indicated on the construction documents/plans. 1.2 DEFINITIONS Some of the terms used in this specification may be unfamiliar to the reader, or may be used with a specific meaning not commonly known outside the helical pile industry. In determining the meaning of any term used herein, a definition contained in the following list shall take precedence. A. Bearing Stratum -The undisturbed soil layer at any pile excavation location which provides a significant portion of the axial resistance of an installed helical pile bearing on one or more of the pile helices. Contractor - The person/firm responsible for performing the helical pile work. C. Crowd - Axial compressive force applied to the head (top) of the helical pile shaft during installation as required to ensure the pile progresses into the ground with each revolution a distance approximately equal to the helix pitch. D. Extension -A pile section without helical plates. Extension (s) are installed after the lead section. Each extension is connected with integral couplings which provide a rigid load transferring connection. Their purpose is to extend the lead section with helical plates to a load bearing stratum. E. Helix Driver- A high torque hydraulic motor used to advance (screw) a helical pile into the soil to a load bearing stratum. Depending on the capacity of the helix driver, it may be either hand held or machine operated. F. Helical Pile - A steel pile consisting of one or more helical plates which is torqued into the soil until the lead section is embedded into a load bearing stratum. They're purpose is to transfer structural loads (tension and/or compression) to a load bearing stratum. G. Helix Plate - A round plate formed into a ramped spiral. When rotated into the soil, the helical shape provides thrust along its longitudinal axis thus aiding in pile installation. After installation, the plate transfers axial load into the soil through bearing. H. Installation Torque -The resistance generated by a helical pile when installed into the soil. The installation resistance is a function of the strength properties of the soil the helical piles are being installed in as well as the shaft geometry of 9 1 407 N LINCOLN AVE. SUITE 104, LOVELAND CO 80537 1 MAIN: 720.408.0119 1 ADMIN a@LEVELINSPECTIO ,P,A.e the pile shaft and helical plates. I. Lead Section - The first helical pile section installed into the soil consisting of one or more helix plates welded to the pile shaft. J. Torque Rating -The maximum torque energy that can be applied to a helical pile during installation into the soil. 1.3 REFERENCES A. American Society of Testing and Materials (ASTM) a. ASTM -A29 Steel Bars, Carbon and Alloy, Hot Wrought and Cold Finished b. ASTM -A36 Structural Carbon Steel c. ASTM -A53 Welded and Seamless Steel Pipe d. ASTM -A500, Grade C, Cold Formed Welded and Seamless Carbon Steel Structural Tubing in Rounds and Shapes e. ASTM -A307 Carbon Steel bolts and Studs f. ASTM -563 Carbon and Alloy Steel Nuts B. American Welding Society (AWS) a. AWS Dl.I Structural Welding Code - Steel C. Society of Automotive Engineers (SAE) a. SAE J429 Mechanical and Material Requirements for Externally Threaded Fasteners D. International Code Council - Evaluation Services (ICC -ES) a. Acceptance Criteria for Corrosion Protection of Steel Foundation Systems Using Polymer (EAA) Coatings (AC228) b. Acceptance Criteria for Helical Pile Systems and Devices (AC358) c. Evaluation Service Report (ESR) E. International Organization for Standardization (ISO) a. ISO 9001:2008 -Quality Management System 1.4 SUBMITTALS A. Five (5) sets of site specific shop drawings sealed by a registered professional engineer. Shop drawings to include: a. Helical pile/anchor identification number and location b. Helical pile/anchor design load c. Type and size of helical pile/anchor shaft d. Helical configuration (number and diameter of helical plates) e. Minimum effective torque required city C4 10 1 407 N LINCOLN AVE. SUITE 104, LOVELAND CO 80537 1 MAIN: 720.408.0119 1 ADMIN@LEVELINSPECTIONSio.ii"eat Ridge Ing f. Connection details B. Copies of certified calibration reports for all hydraulic gages. The calibrations shall have been performed within one (1) year of the proposed starting date of the pile installation. C. Provide steel manufacturer's mill test reports, covering physical and chemical tests, for all steel piles. D. Provide strength and properties sections of pile sections and calculations bya Professional Engineer demonstrating the pile will meet or exceed the strength requirements of the design loads as shown on the construction documents. a. If applicable, the calculation(s) shall include the load eccentricity on the pile. The eccentricity shall be measured from the vertical face of the footing to the center of the pile shaft. b. If the helical pile is deemed laterally unbraced per section 1808.2.5 of the International Building Code (IBC), the allowable load capacity calculation(s) of the pile shall take into consideration the unbraced length of the pile per section 1808.2.9.2 of the International Building Code (IBC). E. Installation Records: Within 7 days after pile installation, submit 2 copies of the installation record for each pile installed. a. The installation record shall clearly indicate the pile identification number or mark, pile diameter, helix configuration, installation depth, installation torque, ultimate and allowable capacity of pile. b. Where helical piles are being installed on existing structures providefinal lifting force/design load applied to pile, the amount of elevation recovery of each pile. 1.5 QUALITY ASSURANCE A. The Contractor performing the Work of this Section shall have been regularly engaged in pile work for a period of not less than 5 years and shall be properly equipped to execute the Work. If directed, furnish a list of projects of a similar type and magnitude executed by the Contractor. In lieu of the Contractor achieving 5 years of Helical Pile experience, a certificate of competency can be provided by manufacturer. The certificate should state that the Contractor has been trained and is authorized to install the underpinning pile system or the manufacturer shall provide a letter expressing the ability and intent to provide on-site supervision of the pile installation. C. Design of the helical piles/anchors shall be performed by a professional engineer licensed in the state of the project in accordance with existing 111 407 N LINCOLN AVE. SUITE 104, LOVELAND CO 80537 I MAIN: 720.408.0119 1 ADMIN@LEVELINSPECTI Wheat Ridge Ing Div building code requirements. D. The helical pile shall be recognized by the International Code Council (ICC) and the manufacturer shall hold a current ICC -ES issued ESR report showing compliance with AC358 and the current International Building Code (IBC). E. The manufacturer shall have been issued an International Organization for Standardization - (ISO) 9001:2008 - Quality Management System Certificate and be compliant. 1.6 DELIVERY, STORAGE, AND HANDLING A. Transport, store, and handle piles in a manner to prevent damage to the piles. Piles shall be stored above the ground surface by pallets, blocking or other means. PART 2 PRODUCTS 2.1 MATERIAL A. Manufacturer: Supportworks: Foundation Supportworks®, Inc., 12330 Cary Circle, Omaha, NE 68128; Phone: (800) 281-8545; Fax: (402) 393-4002. Note: Equivalent systems may be substituted. System equivalence will be determined by comparing a manufacturer's current ICC -ES issued ESR report to ESR -1854. B. The helical piles/anchors shall have a central shaft that is cold formed welded and seamless carbon steel structural round tubing with a minimum yield strength of 65 ksi and meeting the dimensional and workmanship requirements of ASTM A500 as well as the following properties: 2 7/8" diameter piling/anchor: Torsional strength rating = 8,000 ft -lbs Ultimate resistance capacity = 72,000 lbs a. Shall conform to ASTM A-36 and have minimum yield strength (FY) of 50 ksi. b. Shall have a minimum thickness of 3/8". 01 12 1 407 N LINCOLN AVE. SUITE 104, LOVELAND CO 80$37 1 MAIN: 720.408.0119 1 ADMIN@LEVELINSPECTIONSCO. W C. All other flat plate steel shall conform to ASTM A-36 unless noted otherwise on the plans. D. All coupling connection thru bolts shall be 3/4" diameter and conform to SAE J429 Grade 8 or equivalent. (minimum yield strength (F,,) = 130 ksi and minimum tensile strength (Fu) = 150 ksi) E. All piling sections and brackets shall be coated with a polymer alloy thermoplastic powder coating, Plascoat PPA 571 ES or equal, in compliance with ICC -ES acceptance criteria AC228 for corrosion resistance. 2.2 PERFORMANCE REQUIREMENTS A. All helical piles shall be designed to support the design load(s) as shown on the plans. B. Except where noted on the plans, all helical pile components shall be selected to provide a minimum factor of safety against ultimate mechanical failure of two (2). C. The helical pile design shall take into account pile spacing, soil stratification and strain compatibility issues as are present for the project. See drawings for reference for the project geotechnical report. A copy of the project geotechnical report shall be provided to and reviewed by the Pile Contractor prior to bid submittal. D. Where helical piles are subjected to lateral or base shear loads as indicated on the plans, the bending moment and stress from said loads shall be determined using a lateral load analysis program such as LPILE or equal commercially available software. The required soil parameters (c, 0, y and ks) for use with LPILE or equal shall be provided in the geotechnical report(s). The allowable lateral deflection of the helical pile shall be limited to one (1 ") inch unless noted otherwise on the plans. E. The helical pile bracket shall distribute the design load (s), as indicated on the plans, to the concrete foundation such that the concrete bearing stress does not exceed those in the ACI Building Code and the stress in the steel plate/welds do not exceed AISI allowable stresses for steel members. F. Helical piles shall be designed by a licensed professional engineer in accordance with the current International Building Code (IBC) adopted by the local jurisdiction. city 01 R0(ff' 13 1 407 N LINCOLN AVE. SUITE 104, LOVELAND CO 80537 1 MAIN: 720.408.0119 1 ADMIN a@LEVELINSPECTI PART 3 EXECUTION 3.1 PREPARATION A. Before entering the construction site to begin work, the Helical Pile Contractor shall provide proof of insurance coverage as stated in the general specification and/or the contract. B. The Helical Pile Contractor shall request markings of underground utilities by an underground utility location service. All efforts shall be made to protect any underground utilities encountered during the excavation and pile installation. Any separations or damage caused to the underground utilities shall be repaired/ performed by a licensed professional. C. Mark all pile installation locations as shown on the plans or approved shop drawings. The Engineer of Record shall be notified if the piles are relocated more than 12" from the locations shown on the plans or approved shop drawings. Relocation of the piles will not be allowed unless approved by the Engineer of Record. D. A torque indicator shall be used during helical pile/anchor installation. The torque indicator can be an integral part of the installation system or externally mounted in-line. E. A third party inspector shall be retained to oversee all aspects of installation of the helical piles/anchors. The items to be inspected include, but not limited to the following: a. Verify the type of helical pile/anchor being installed is as specified on the shop drawings. b. Verify final embedment depth of helical pile/anchor. c. Verify final installation torque readings as specified on the shop drawings. 3.2 INSTALLATION A. The helical pile/anchor installation technique shall be such that it is consistent with the geotechnical, logistical, environmental and load carrying conditions of the project. B. The lead section shall be positioned at the location as shown on the construction drawings. Battered helical piles/anchors can be positioned perpendicular to the ground to assist in initial advancement into the soil before the required battered angle shall be established. C. The helical pile/anchor sections shall be engaged and advanced into the soil in a smooth, continuous manner at a rate of rotation of 5 to 25 RPM'S. Extension sections shall be provided to obtain the required minimum overall length and installation torque as shown on the construction drawings. Connect sections together using coupling bot(s) and nut torqued to snuKC71ty tight perAISC. 14 1 407 N LINCOLN AVE. SUITE 104, LOVE;.AND CO 80537 1 MAIN: 720.408.0119 1 ADMIN@a LEVELINSPECTI ,nmeat W90 D. Sufficient down pressure shall be applied to uniformly advance the helical pile/anchor sections approximately 3 -inches per revolution. The rate of down pressure (crowd) shall be adjusted for different soil conditions and depths. E. The minimum installation torque and minimum overall length criteria as shown on the construction drawings shall be satisfied prior to terminating the helical pile/anchor installation. F. If the torsional strength rating of the pile shaft and/or installation equipment has been reached prior to achieving the minimum overall length required, the Contractor shall have the following options: a. Terminate the installation depth obtained subject to the review and acceptance of the Engineer of Record, or: b. Remove the existing helical pile/anchor and install a new one with fewer and/or smaller diameter helix plates. The new helix plate configuration shall be subject to review and acceptance of the Engineer of Record. If re -installing in the same location, the top -most helix of the new helical pile/anchor shall be terminated at least three feet (3'-0) beyond the terminating depth of the original helical pile/anchor. G. If the minimum installation torque as shown on the working drawings is not achieved at the minimum overall length and there is no maximum length constraint, the Contractor shall have the following options: a. Install the helical pile/anchor deeper using additional extension sections, or: b. Remove the existing helical pile/anchor and install a new one with additional and/or larger diameter helix plates. The new helix plate configuration shall be subject to review and acceptance of the Engineer of Record. If re -installing in the same location, the top- most helix of the new helical pile/anchor shall be terminated at leastthree feet (3'-0) beyond the terminating depth of the original helical pile/anchor. c. De -rate the load capacity of the helix pile/anchor and install additional helical piles/anchors. The de -rated capacity and additional helical piles/anchors location shall be subject to the review and acceptance of the Engineer of Record. H. If the helical pile/anchor is refused or deflected by a subsurface obstruction, the installation shall be terminated and the pile/anchor removed. The obstruction shall be removed, if feasible, and the helical pile/anchor re- installed. If the obstruction can't be removed, the helical pile/anchor shall b installed at an adjacent location, subject to the review and acceptance/cm 0. 15 1 407 N LINCOLN AVE. SUITE 104, LOVELAND CO 80537 1 MAIN: 720.408.0119 1 ADIVIN�%a LEVELINSPECTIONSC[CO eat Ridge DIV the Engineer of Record. I. The Contractor shall conduct his construction operations in a manner to insure the safety of persons and property in the vicinity of the work. The Contractor's personnel shall comply with safety procedures in accordance with OSHA standards and any established project safety plan. J. The portion of the construction site occupied by the Helical Pile Contractor, his equipment and his material stockpiles shall be kept reasonably clean and orderly. 3.3 FIELD QUALITY CONTROL A. The Helical Pile Contractor shall furnish and install all helical piles per the plans and approved pile design documentation. In the event of conflict between the plans and approved pile design documentation, the contractor shall not begin construction on any affected items until such conflict has been resolved. B. Centerline of helical piles/anchors shall not be more than three inches (3") from indicated plan location unless approved by the Engineer of Record. C. Helical pile/anchor plumbness shall be within 2 degrees of the design alignment. 3.4 CLEAN UP A. Within seven (7) days of completion of the work. The Helical Pile Contractor shall remove any and all material, equipment, tools, building materials, concrete forms, debris or other items belonging to the Contractor or used under the Contractor's direction. END OF SPECIFICATION 4 QUALIFICATIONS OF INSTALLING CONTRACTOR AND DESIGNER 4.1 The Installing Contractor and/or Pile Designer shall submit to the Owner, a proposal including the documentation required in this Section. Work shall not begin until all the submittals have been received and approved by the Owner. All costs associated with incomplete or unacceptable submittals shall be the responsibility of the Installing Contractor. 4.2 Evidence of Installing Contractor's competence in theinstallation of helical piles shall be provided to the Owner's satisfaction and may include any or all of the following: o', OOk 16 1 407 N LINCOLN AVE. SUITE 104, LOVE LAND CO 80537 1 MAIN: 720.408.0119 1 ADM IN@LEVELINSPECTIONS co,gNkteat R",69c, 4.2.1 Pile manufacturer's certificate of competency for the installation of helical piles, 4.2.2 A list of at least three projects completed within the previous three years wherein the Installing Contractor installed helical piles similar to those shown in the project Plans. Such list to include names and phone numbers of those project representatives who can verify the Installing Contractor's participation in those projects, and/or 4.2.3 A letter from the pile manufacturer or manufacturer's representative expressing ability and intent to provide on-site supervision of the pile installation. 4.3 A listing of all safety violations lodged against the Installing Contractor within the previous three years and the current status or final resolutions thereof. Descriptions of safety improvements instituted within the previous three years may also be submitted, at the Installing Contractor's discretion. 4.4 Evidence of Pile Designer's competence shall be provided to the Owner's satisfaction and may include any or all of the following: 4.4.1 Registration as a Professional Engineer or recognition by the local jurisdictional authority, 4.4.2 A list of at least three projects completed within the previous three years wherein the Pile Designer designed helical piles similar to those shown in the project Plans. The list shall include names and phone numbers of those project representatives who can verify the Pile Designer's participation in those projects,and/or 4.4.3 Recommendation from the pile manufacturer or manufacturer's representative. 5 PRE -CONSTRUCTION SUBMITTALS 5.1 Within 2 weeks of receiving the contract award, the Installing Contractor and/or Pile Designer shall submit the following helical pile design documentation: 5.1.1 Certification from the Pile Designer that the proposed piles meet the requirements of this specification. 5.1.2 Qualifications of the Installing Contractor and Pile Designer per Section8. 5.1.3 Product designations for helical lead and extension sections and all ancillary products to be supplied at each helical pile location. 5.1.4 Individual pile nominal loads, factors of safety, LRFD load and resistance factors and required ultimate torque correlated capacities, where applicable. 5.1.5 Individual pile loading requirements (if any). 5.1.6 Manufacturer's published allowable system capacities for the proposed pile assemblies, including load transfer devices. 5.1.7 Calculated mechanical and theoretical geotechnical capacities of the proposed piles. 5.1.8 Minimum pile termination torque requirements. 5.1.9 Maximum estimated installation torque and allowable installation torque ratin of the proposed piles. lZf oy 17 I 407 N LINCOLN AVE. SUITE 104, LOVELAND CO 80537 I MAIN: 720.408.0119 1 ADMIN@LEVELINSPECTION ��COM dJ` 5.1.10 Minimum and/or maximum embedment lengths or other site specific embedment depth requirements as may be appropriate for the site soil profiles. 5.1.11 Inclination angle and location tolerance requirements. 5.1.12 Load test procedures and failure criteria, if applicable. 5.1.13 Copies of certified calibration reports for torque measuring equipment and load test measuring equipment to be used on the project. The calibrations shall have been performedwithin one year of the proposed helical pile installation starting date or as recommended by the equipment manufacturer. 5.1.14 Provide proof of insurance coverage as stated in the general specifications and/or contract. 6 PLACEMENT REQUIREMENTS 6 Helical piles shall be installed within 3 -inches of the indicated plan location. 6.1 Helical pile shaft alignment shall be within 2 -degrees of the inclination angle shown on the Plans. 6.2 Top elevation of the helical piles shall be within 2 -inches of the design vertical elevation. 7 PILE/PIER INSTALLATION 7.1 Installing Contractor shall furnish and install all helical piles per the project Plans and approved pile design documentation. In the event of conflict between the project Plans and the approved pile design documentation, the Installing Contractor shall not begin construction on any affected items until such conflict has been resolved. 7.2 The Installing Contractor shall conduct their construction operations in a manner to insure the safety of persons and property in the vicinity of the work. The Installing Contractor's personnel shall comply with safety procedures in accordance with OSHA standards and any established project safety plan. 7.3 The Owner shall request marking of underground utilities by an underground utility location service as required by law, and the Installing Contractor shall avoid contact with all marked underground facilities. 7.4 The portion of the construction site occupied by the Installing Contractor, including equipment and material stockpiles shall be kept reasonably clean and orderly. 7.5 Installation of helical piles may be observed by representatives of the Owner for quality assurance purposes. The Installing Contactor shall give the Owner at least 24 hours' notice prior to the pile installation operations. 7.6 The helical pile installation technique shall be such that it is consistent with the geotechnical, logistical, environmental, and load carrying conditionsof the project. The lead section shall be positioned at the appropriate site survey stake location as determined from the plan drawings. 18 1 407 N LINCOLN AVE. SUITE 504, LOVELAND CO 80537 1 MAIN: 720.408.0119 1 ADMIN@LEVELINSPECTIO 7.7 The helical pile sections shall be advanced into the soil in a continuous manner at a rate of rotation less than 25 revolutions per minute (rpm). Sufficient crowd shall be applied to advance the helical pile sections at a rate approximately equal to the pitch of the helix plate per revolution. The rate of rotation and magnitude of down pressure shall be adjusted for different soil conditions and depths. Extension sections shall be provided to obtain the required minimum overall length and minimum torsional resistance as shown on the project Plans. 8 TERMINATION CRITERIA 8.1 The minimum final torsional resistance and/or any required pile length and embedment depth criteria, as specified in the Pre -Construction Submittals, must be satisfied prior to terminating the pile installation. In the event an helical pile fails to meet these production quality control termination criteria, the following remedies may be suitable if authorized by the Owner: 8.1.1 If the installation fails to meet the minimum torsional resistance criterion at the minimum embedment length: 8.1.1.1 Continue the installation to greater depths until the torsional resistance criterion is met, provided that, if a maximum length constraint is applicable, continued installation does not exceed said maximum length constraint, or 8.1.1.2 Demonstrate acceptable pile performance through pile load testing, or 8.1.1.3 Replace the pile with one having a different helix plate configuration. The replacement pile must not exceed any applicable maximum embedment length criteria and either: (A) be embedded to a length that places the last helix plate at least equal to its own diameter beyond the depth of the first helix plate of the replaced pile and meet the minimum torsional resistance criterion; or (B) pass pile load testing criteria. 8.1.2 If the torsional resistance during installation reaches the helical pile'sallowable torque rating prior to satisfaction of the minimum embedment length criterion: 8.1.2.1 Terminate the installation at the depth obtained, or 8.1.2.2 Replace the pile with one having a shaft with a higher torsional strength rating. The replacement pile must be installed to satisfy the minimum embedment length criterion. It must also be embedded to a length that places the last helix plate at least equal to its own diameter beyond the depth of the first helix plate of the replaced pile without exceeding any applicable maximum embedment length requirements and it must meet the minimum final torsional resistance criterion, or 8.1.2.3 Replace the pile with one having a different helix plate configuration. The replacement pile must be installed to satisfy the minimum embedment length criterion. It must also be embedded to a length that places the last helix plate at ast, 6� ).COM "�� '.. 'W 19 1 407 N LINCOLN AVE. SUITE 104, LOVELAND CO 80537 I MAIN: 720.408.0119 1 ADMIN@LEVELINSPECTIO equal to its own diameter beyond the depth of the first helix plate of the replaced pile without exceeding any applicable maximum embedment length requirements, and it must meet the minimum final torsional resistance criterion. 8.1.3 If the installation reaches a specified maximum embedment length without achieving the minimum torsional resistance criterion: 8.1.3.1 If allowed, remove and reinstall the pile at a position at least three times the diameter of the largest helix plate away from the initial location. Original embedment length and torsional resistance criteria must be met. The pile repositioning may require the installation of additional helical piles with nominal loads adjusted for these spacing changes, or 8.1.3.2 Demonstrate acceptable pile performance through pile load testing, or 8.1.3.3 De -rate the load capacity of the helical pile based on default or site specific torque correlation factors and install additional piles as necessary. 8.1.3.4 Replace the pile with one having a different helix plate configuration. The replacement pile must be installed to satisfy the minimum and/or maximum embedment length criterion and it must meet the minimum final torsional resistance criterion. 8.1.4 If a helical pile fails to meet the acceptance criteria in a pile load test: 8.1.4.1 Install the pile to a greater depth and installation torque and re- test; provided that, if a maximum embedment length constraintis applicable, continued installation will not exceed said maximum length constraint, or 8.1.4.2 Replace the pile with one having more and/or larger helix plates. The replacement pile must be embedded to a length that places the last helix plate at equal to its own diameter beyond the depth of the first helix plate of the replaced pile without exceeding any applicable maximum embedment length requirements. The replacement pile must be re -tested, or, 8.1.4.3 De -rate the load capacity of the helical pile based on the results of the load test and install additional piles. Additional piles must be installed at positions that are at least three times the diameter of the largest helix plate away from any other pile locations. 8.1.5 If a helical pile fails a production quality control criterion as described in this Section or for any reason other than described in this Section, any proposed remedy must be approved by the Owner prior to initiating its implementation at the projectsite. City of 20 1 407 N LINCOLN AVE. SUITE 104, LOVELAND CO 80537 1 MAIN: 720.408.0119 1 ADMIN@LEVELINSPECTIONVOMmat Ridge Uildincg Diviso 9 INSTALLATION RECORD SUBMITTALS 9.1 The Installing Contractor shall provide the Owner copies of the individual helical pile installation records within 24 hours after each installation is completed. Formal copies shall be submitted within 30 days following the completion of the helical pile installation. These installation records shall include, but are not limited to, the following information: 9.1.1 Date and time of installation 9.1.2 Location of helical pile and pile identification number 9.1.3 Installed helical pile model and configuration 9.1.4 Termination depth, pile head depth, and length of installed pile 9.1.5 Actual inclination of the pile 9.1.6 Final torsional resistance 9.1.7 Calculated geotechnical capacity based on final torsional resistance 9.1.8 Comments pertaining to interruptions, obstructions, or other relevant information 10 FIELD COMPRESSION LOAD TESTING 10.1 If field compression load testing is required, the Installing Contractor shall furnish all labor, equipment and, pre -production helical piles necessary to accomplish the testing as shown in the approved pile design documentation. Installing Contractor shall apply the specified loads for the specified durations and record the specified data, for the specified number of piles. No deviations from the test plan(s) will be allowed without explicit approval in writing from the Owner. Pile testing shall be in general accordance with the ASTM Dl 143 quick test method and the following criteria: 10.1.1 Failure criteria shall be in accordance with AC358 and is when plunging occurs or when the net deflection exceeds 10% of the average helix plate diameter, whichever occurs first. 10.1.2 An alignment load equal to 5% of the anticipated failure load or maximum anticipated test load may be applied prior to the start of the test to take out slack in the load test frame. 10.1.3 Loading increments shall be performed at 5% of the anticipated failure load or maximum anticipated test load with a minimum hold time of 4 minutes at each increment. 10.1.4 Upon completion of the maximum test load hold increment, the pile shall be unloaded in 5 to 10 even increments with minimum hold times of 4 minutes at each increment. 10.2 Installing Contractor shall provide the Owner copies of raw field test data within 24 hours after the completion of each load test. Formal test reports shall be submitted within 30 days following test completion. Formal test reports shall include the following information: 10.2.1 Name of project and Installing Contractor's representative (s) present during load testing. c;ty 211 407 N LINCOLN AVE. SUITE 104, LOVELAND CO 80537 1 MAIN: 720.408.0119 1 ADMINa1LEVELINSPEC�IONNSSCO.C4VRjo,s*e 10.2.2 Name of manufacturer's representatives) present during load testing, if any. 10.2.3 Name of third party test agency and personnel present during load testing, if any. 10.2.4 Date, time, duration and type of the load test. 10.2.5 Unique test identifier and map showing the test pile location. 10.2.6 Pile model and installation information including shaft type, helix configuration, lead and extension section quantities and lengths, final pile tip depth, installation date, total test pile length and final termination torque. 10.2.7 Calibration records for applicable pile installation and test equipment. 10.2.8 Tabulated test results including cumulative pile head movement, loading increments and hold times. 10.2.9 Plots showing load versus deflection for each loading/unloading interval. LIMITATIONS This repair design does not represent a complete analysis of the entire structure; it addresses conditions covered under the structural warranty provided by the contractor. The interpretations of the distress to be repaired are based on the visual observations of the structure. No detailed study was made of the structural elements of any part of the building. Therefore, no opinion is presented or shall be implied concerning the structural integrity of those elements not subject to visual inspection. Investigation and analysis of other portions of the structure are beyond the scope of this design at this time. LEVEL Engineering, LLC will not be responsible for 1) knowledge of subsurface conditions away from the existing borings, if any, without extensive geotechnical information supplied by a competent geotechnical engineer, 2) knowledge of distresses, or differential displacements that have occurred in an area which had not been exposed for visual observation during our site visit and 3) any other elements such as joists or beams and other structural members that are not readily visible. LEVEL Engineering, LLC assumes that all information provided by the Client, Contractor, or other Consultants is correct, accurate, and may be acted upon accordingly, and shall have no liability for the validity of information provided. LEVEL Engineering, LLC shall have no liability for acts or omissions of the Contractor or any other agents performing the work on this project or for the failure of the Contractor to carry out the work in accordance with the plans and specifications if not inspect as intended. LEVEL Engineering, LLC shall not be responsible for the construction means, methods, techniques, sequence, procedures, or safety precautions related to this project and its execution that is under the control or direction of the Contractor. This PLAN of REPAIR is to be used with the accompanying drawings. Do not rely on one or the other, all materials contained in THE PLAN of REPAIR including but not limited to the cover letter, notes, plans, details, shall be used together to perform the proposed remedial construction. _ C'%%,l 0. 22 1 407 N LINCOLN AVE. SUITE 104, LOVELAND CO 80537 1 MAIN: 720.408.0119 1 ADMIN a@LEVELINSPECTIONS(V60te3 WORK DESCRIPTION For the purposes of this report, the front of the home is considered to face North. The structure of the single story single family home is a conventionally framed residence. The home has a cast in place concrete foundation with crawl space stem walls placed on spread footings. Portions of the exterior of the foundation structure is settling. This is the fourth partial of underpinning that has occurred on this structure. These issues are causing faulting and fracturing of the slabs, exterior and interior finishes, and unevenness of the roof and floor structures. Helical underpinning is part of this work. This area of repair is referenced in the attached drawings. (see plan). Once the piles are installed. All restoration of finishes exterior and interior flatwork shall be restored in kind and in accordance with the owner's approval. The contractor is responsible for coordinating these type of repair scopes with the contractor. The contractor is required to coordinate these expectations with the owner and include the necessary work items in their bid proposals. REPAIR RECOMMENDATIONS 1. The concrete slab and walls are to be braced as required during the repair process by the Contractor. 2. Remove decks, pavers, slabs etc. to excavate the soil required to install the new helical foundation devices, in accordance with drawings prepared by Level Engineering LLC. 3. Excavate the soil required to install the helical piers and anchors in accordance with drawings prepared by Level Engineering LLC. 4. Install 8 helical piles/piers to a depth of 25 ft. and 3500lbs/sf torque on the main structure and 4 piers on the garage structure. Coordinate location with engineer per support works specifications and recommendations and drawings including specifications prepared by Level Engineering LLC. 5. Restore all finishes exterior and interior in accordance with agreements with owner. City Lz4 23 1 407 N LINCOLN AVE. SUITE 104, LOVELAND CO 80537 1 MAIN: 720.408.0119 1 ADMIN@LEVELINSPtTION�rCATO i(je Uilding PROPOSED COMPLIANCE OBSERVATIONS All observations shall be conducted by a qualified Colorado Licensed Professional Engineer. More than one observation may be conducted during a site visit. The contractor is to determine the number of site visits required to do the observations and include this information in the bid documents. LEVEL Engineering, LLC is willing to complete the observation under contract. 1. Pre -Construction Meeting 2. Attachment of brackets to foundation walls. 3. load tests 4. Epoxy Injection of foundation wall cracks (directed by owner) 5. Review pier logs 6. Final city c 24 1 407 N LINCOLN AVE. SUITE 104, LOVELAND CO 80537 1 MAIN: 720.408.0119 1 ADMIN@LEVELINSPECTIONSC0.Cfteat Ridge Dil,isO 4' CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type: I,, o F Job Address: -4 -;n i f C Permit Number: U i -1 1 9 7 Li 0 'e o U `P 0 ❑ No one available for inspection: Time % e,- 2— yAM/PM Re -Inspection required: Yes No When corrections have been made, call for re -inspection at 303-234-5933 Date: �- Inspector: I DO NOT REMOVE THIS NOT/CE City of Wheat Ridge Residential Roofing PERMIT - 201701397 PERMIT NO: 201701397 ISSUED: 06/02/2017 JOB ADDRESS: 3032 Ingalls CT EXPIRES: 06/02/2018 JOB DESCRIPTION: Reroof 34 squares OC Dimensional asphalt shingles; 4/12 pitch; 1 layer *** CONTACTS *** OWNER (970)218-0303 CAMERON CUYLER SUB (720)810-1991 Tim Bonneville 170180 Hassle Free Contracting LLC *** PARCEL INFO *** ZONE CODE: UA / Unassigned USE: UA / Unassigned SUBDIVISION CODE: 2405 / BARTHS, COULEHAN GRANGE, WHEAT BLOCK/LOT#: 0 / *** FEE SUMMARY *** ESTIMATED PROJECT VALUATION: 8,738.00 FEES Total Valuation 0.00 Use Tax 183.50: Permit Fee 188.45 ** TOTAL ** 371.95 *** COMMENTS *** *** CONDITIONS *** Effective December 1, 2014, asphalt shingle installations require an approved midroof inspection, conducted when 25-75 percent of the roof covering is installed, prior to final approval. Installation of roof sheathing (new or overlay) requires an approved inspection prior to installation of ANY roof coverings and is require on the entire roof when spaced or board sheathing with ANY gap exceeding k/2 -inch exists. Asphalt shingles are required to be fastened to the roof deck with a minimum of 6 nails per shingle. Ice and water shield is required. Eave and rake metal is required. A ladder extending 3 feet above the roof eave and secured in place is required to be provided for all roof inspections. Roof ventilation is required to comply with applicable codes and/or manufacturera€Ims installation instructions, whichever is more stringent. In order to pass a final inspection of elastomeric or similar type roof coverings, a letter of inspection and approval from the manufacturer&#39;s technical representative stating that "the application of the roof at (project address) has been applied in accordance with the installation instruction for (roof material brand name) roof covering" is required to be on site at the time of final inspection. •aull laafgns aql uI uollaadsul aql jo ssa ipps aql lnd aseald •umpadsm aql jo tuluaow aql `mi000:8 Pus wu0£:L uaamjaq sn•oa•atpialeagm•la�klsanba.aatuildsui of slsanbaa lisuta assald -Sluo llsuta Sq paldaaas aq Il►m slsanbaa awil uoilaadsul •xva ssaw[sna JLQIMo=d atll NOIZO3asiQI uo3 )Lea ssamisne xat*a wa6s:TT x8 aavN as LsnN smsanbau 3173(1 leiogjo 2ulPltng 3aigD 3o a.tnieui?iS uogoadsui plait of loafgns si JlOM3o Ienotddy uoiloipsunf si i uoilp.Il ac to aOueCn fi fiu� to apoo algpai�dde /upio uoisinoid Cup j6 UO (113161A up `Jo Ienotddu up .to `.god liuuod a aq of ponilsuoo aq lou III,gs liw.tad I, 3o fuiluet3 .to aauunsst aql '9 uoistnt(1 saolntDS uotloodsul pup �uipling aqi woij �Itom qons jo lenoiddr ualli.tm inoglim �Itom Ieaauoo .to paaaotd lou hugs pus suoilaadsui poiinbat II lio Xoilod p34s11Quiso glim 03u73p.1033s ui uoistnt(1 S331AIOS uoiloadsul pup 5uipling aqj Xji1ou hugs .tapioq liuuad aqi 'S •II,noadde oi31oads pup .toi.td inoglim .talum jo moll Ivinlpu agldo agupgo i ui sllnsw llegs legs pau i6jiod oq 11734s .tauuew AULIJO �I.tom ON °b •paaluejenO lou st Pup 1E1�33o 5uIpltng jaigD aql 3o uoila.tosip 310S agl173 si sliuuad pazidxa3o uoisuaixa.to aouenssi-ail •liuuad mau,Cue3o Ienoidde .to3 satnp000l pue sa53 `slu3 at nbat piupueis aqi of loafgns aq llugs liuuad mou e io oauunssl •poutelgo oq of paunow oq ilww liuuad mau s `saaidxa liuuod sigl31 ' £ 3a3 liwaa leuif'i.to aql jo jleq-auo of 1pnba Oa3 e of loafgns aq Xpu► pup let31330 2utplmgdaig� agi3o uoilaaosip aql 1I, palupt� agbapew s/Cpp 081 upgi aaow ou jo uoisuoixo uv •uoiletidxa3o alpp aql ol.totid paniaoai pup uilum ui appw aq Ism uoisualxa .god sisan 32I •/CltnIJMJO ssolpteRoi aoumsst�lo alep aql jade s,(I,p S9£ omdixo llpgs liuuod stq L 'Z sO.tnpaoozd pup smijod `suotipinOw `sooueutp• d `salnlpls Ofgeaildde llu pus `sluawnoop asogl glim ooueildwoa aql of 13orgns st pus suoilpogiaads pus suejd fuiXuudwonv put,uoi�w)ilddr liuuo Orli ut papinoad uo►leuuodui aqi uo paseq panssi spm liuuad si41 'I alea (auo 3l3lID) 2IO.LDVldLNoD JO NHNMO 3o;DlnluufiS �c •suotleagioods pue sueld panotddr 2uiXusdw000e ,sli .to/pue luawnoop stgl ui posolosip si pouuo i3d zq of Niom lip lugs pue p�tfcto .tad aq of atom aqi of satupd ss luawnoop sigi utglim paweu satitiva Iju Opnloui of pazi toginp �Ilp al wI, I 1pgi isallp zaqund I •ituuad sigl giim uoilounfuoa ut panotddp pup pogi.tosap 31iom aqi uuodtOd pus litwad sigl uiulgo of pazitoglnu we pup il.tadoad aql jo .taumo luBal aql Xq pozi.toglne uaaq aneq .to numo 1p5al atll urs I ipgl pup `swnpaootd pup somtjod `sapoo II,dmiunw alquoildde III, pup `sapoo 13uipig algI,oilddI, suotIBogioads pup suuld pano.tddI, ut�iupdw000e III, grim ,Cldwoo pegs pouuojj3d aq of )laom aqi 1pgl lsaile ,tg3ioq op a.tnlpu is w q I aGAPT T 'uo;Td ZT/Ii 'saTbuTus qTpudsp TPuoTsuautTQ Dp sa=bs V£ joozag 8TOZ/ZO/90 :SRdId= JD sTTpbuI Z£0£ LTOZ/ZO/90 :QEIIsSI L6£TOLTOZ L6£i0Ll0Z - .LIM:4d 21uU00-d Iuiluapisald atp!H lvauAc1 jo Sji3 NOIldIUDSHQ 90f sSa'dCCr EOf ON ,LIKEEd ., City of %Wheat Rd�� COMMUN lTY .DEvuoPMEN"i Building & Inspection Services Division 7500 W. 29" Ave., Wheat Ridge, CO 80033 Office: 303-235-2855 * Fax: 303-237-8929 Inspection Line: 303-234-5933 Email: permits(a)ci.wheatridge.co.us FOR OFFICE USE ONLY Date: Plan/Permit # 90/ 1661 Plan Review Fee: Building Permit Application **"*,,Please complete all highlighted areas on'both sides of this form. Incomplete applications may not be processed. *** Property Address: 303-?, 'Zhqa //S Cf: , -�"64e,iy Sbal< Property" owner (please print): u `��� ���� Phone: '� 7d - A 18'03 a3 Property'owner Email Mailing Address;(if different than property address) Address City, State, Zip: Architect/Engineer Architect/Engineer E-mail: GESS le- Fee - Phone: Contractors°City License M. 170 60 Phone: Contractor E-mail Address: �� m � /Cj a -SS 1 e- -Free Cc -7t( A-r—f nj -'�r_z Sub Contractors Electrical: W.R. City License # Other City Licensed Sub: City License # Plumbing: W.R. City License # Other City Licensed Sub: City License # Mechanical: W.R. City License # Complete all information on BOTH sides of this form ❑ COMMERCIAL X RESIDENTIAL Description, of work: (Check all that apply) ❑ NEW COMMERCIAL STRUCTURE ❑ ELECTRICAL SERVICE UPGRADE ❑ NEW RESIDENTIAL STRUCTURE ❑ COMMERCIAL ROOFING ❑ COMMERCIAL ADDITION RESIDENTIAL ROOFING ❑ RESIDENTIAL ADDITION WINDOW REPLACEMENT ❑ COMMERCIAL ACCESSORY STRUCTURE (Garage, shed, deck, etc.) ❑ RESIDENTIAL ACCESSORY STRUCTURE (Garage, shed, deck, etc.) ❑ MECHANICAL SYSTEM/APPLIANCE REPAIR or REPLACEMENT ❑ PLUMBING SYSTEM/APPLIANCE REPAIR or REPLACMENT ❑ ELECTRICAL SYSTEM/APPLIANCE REPAIR or REPLACEMENT ❑ OTHER (Describe) (For ALL projects; please provide a detailed description of work to be performed, including current use of areas, proposed uses, square footage, existing condition and proposed new`coridition, appliance size and efficiency, type and amount of materials to-kie used, etc.)�DD 3 , p S C. f � e-115 i vh a. -L a yha_/'� Sq. Ft./LF Amps Btu's Squares Gallons Other Project Value (Contract value or the cost of all materials and labor included in the entire project) OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT 1 hereby certify that the setback distances proposed by this permit application are accurate and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance with applicable City of Wheat Ridge codes and ordinances for work under any permit issued based on this application; that 1 am the legal owner or have been authorized by the legal owner of the property to perform the described work and am also authorized by the legal owner of any entity included on this application to list that entity on this application. 1, the applicant for this building permit application, warrant the truthfulness of the information provided on the application. CIRCLE`ONE: (OWNER) (=ONTRACTO or (AUTHORIZED REPRESENTATIVE) of (OWNER) (CONTRACTOR) Electronic Signature Mrst"and last came); Building Division Valuation: $ 4' CITY OF WHEAT RIDGE ]�;IrBuilding Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type: AlIZI-) /�60 r Job Address: a 3 2- c S G Permit Number: /°7 El No one available for inspection: Time - 00 AM PM Re -Inspection required: Yes SO) *When corrections have been made, call for -inspection at 303-234-5933 Date: �i Inspector: ®O NOT REMOVE THIS NO fICE City of Wheat Ridge Residential Miscella PERMIT - 201700279 PERMIT NO: 201700279 ISSUED: 02/24/2017 JOB ADDRESS: 3032 Ingalls CT EXPIRES: 02/24/2018 JOB DESCRIPTION: Foundation stabilization *** CONTACTS *** OWNER (303)274-4761 CAMERON CUYLER GC (303)805-8751 Rodney Martin 060125 Complete Basement Systems *** PARCEL INFO *** ZONE CODE: UA / Unassigned USE: UA / Unassigned SUBDIVISION CODE: 2405 / BARTHS, COULEHAN GRANGE, WHEAT BLOCK/LOT#: 0 / *** FEE SUMMARY *** ESTIMATED PROJECT VALUATION: 13,500.00 FEES Total Valuation 0.00 Plan Review Fee 174.01 Use Tax 243.00 rl Permit Fee* 267.70 j jC ILt TOTAL 684.71 s- *** COMMENTS *** *** CONDITIONS *** MM: Approved per plans and red -line notes on plans. Must comply with 2012 IRC, and all applicable City of Wheat Ridge Municipal Codes. **PLEASE NOTE FOR FINAL INSPECTION: please email engineer letter approval to mmackey@ci.wheatridge.co.us for close out of the permit. No on-site inspection will be required. I, by my signature, do hereby attest that the work to be performed shall comply with all accompanying approved plans and specifications, applicable building codes, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with this permit. I further attest that 1 am legally authorized to include all entities named within this document as parties to the work to be performed and that all work to be performed is disclosed in this document and/or its' accompanying approved plans and specifications. 0112ul( l-4 Signature of OWNER or C&NTRACTOR (Circle one) Date 1. This permit was issued based on the information provided in the pennit application and accompanying plans and specifications and is subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures. 2. This permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and received prior to the date of expiration. An extension of no more than 180 days made be granted at the discretion of the Chief Building Official and may be subject to a fee equal to one-half of the original permit fee. If this permit expires, a new permit may be required to be obtained. Issuance of a new pen -nit shall be subject to the standard requirements, fees and procedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of the Chief Building Official and is not guaranteed. 4. No work of any manner shall be performed that shall results in a change of the natural flow of water without prior andspecific approval. 5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all required inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services Division. 6. The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, an violation of any provision of any ap cco�d�e� or any ordinance or regulation of this jurisdiction. Approval of work is subject to field inspection. Signature of Chief Building Official Date REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. Inspection time requests will be accepted by email only. Please email requests to insptimerequestgci.wheatridge.co.us between 7:30am and 8:00am, the morning of the inspection. Please put the address of the inspection in the subject line. I FOR OFFICE USE ONLY I 4 � Date: p V,t�ity of Wheat d '�Ot✓smUt'v I Iy DEVELOPMENT Plan/Permit # Building & Inspection Services Division tel! I 7500 W. 29" Ave., Wheat Ridge, CO 80033 Plan Review Fee: � Office: 303-235-2855 * Fax: 303-237-8929 r Inspection Line: 303-234-5933 Building Permit ApplicationU *** Please complete all highlighted areas on both sides of this form. Incomplete applications may not be processed. I Property Address: 3036-2— 1 V1 G 0, -A 1 S GC"" . Property Owner (please print): C)IJ 9 i- jr C.� eXa n Phone: 'I Property Owner Email: Mailing Address: (if different than property address) Address: City, State, Zip: Arch itect/Enaineer: Arch itectlEngineer E-mail: Phone: Contractor: C,o6n=471-e l PQug-f_t'Vl LIX2 Contractors City License #: L0 Phone: O a ' 0Fj �1�J Contractor E-mail Address: ajncl , CO (,D 2,1'1" 1-5 L4 s'he"S; . K-0— Sub — J' Sub Contractors: Electrical: W.R. City License # Other City Licensed Sub: City License # Plumbing: W.R. City License # Other City Licensed Sub: City License # Mechanical: W.R. City License # Complete all information on BOTH sides of this form Description of work. (Check all that apply) ❑ NEW COMMERCIAL STRUCTURE ❑ ELECTRICAL SERVICE UPGRADE ❑ NEW RESIDENTIAL STRUCTURE ❑ COMMERCIAL ROOFING ❑ COMMERCIAL ADDITION ❑ RESIDENTIAL ROOFING ❑ RESIDENTIAL ADDITION ❑ WINDOW REPLACEMENT ❑ COMMERCIAL ACCESSORY STRUCTURE (Garage, shed, deck, etc.) ❑ RESIDENTIAL ACCESSORY STRUCTURE (Garage, shed, deck, etc.) ❑ MECHANICAL SYSTEM/APPLIANCE REPAIR or REPLACEMENT ❑ PLUMBING SYSTEM/APPLIANCE REPAIR or REPLACMENT iL LECTRICAL SYST /�IANCE REPAIR or REPLACEMENT THER (Describe) (Forprojects, please provide a detailed description of work to be performed, including current use of areas, proposed uses, square footage, existing condition and proposed new condition, appliance size and efficiency, type and amount of materials to be used, etc.) Sq. FtJLF Amps Btu's Squares Gallons Other Project Value: (Contract value or the cost of all materials and labor included in the entire project) $ I?D.rc--)00 OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance with applicable City of Wheat Ridge codes and ordinances for work under any permit issued based on this application; that I am the legal owner or have been authorized by the legal owner of the property to perform the described work and am also authorized by the legal owner of any entity included on this application to list that entity on this application. CIRCLE ONE: (OWNS �QNTCTOR)(AUTHORIZED RP,PTr?ENTATIVE) (f�(OER)5CONTRACTOR) PRINT NAME Q V d O -l/1 SW Vep $IG I URE: DATE: U 011-7 �-rT DEPART E T USE ONLY ZONING COMMMENTS: OCCUPANCY CLASSIFICATION: Reviewer: BUILDING DEPARTMENT COMMENTS: Reviewer: 04241 rov RIM 1(tIft +0 PUBLIC WORKS COMMENTS: i�l����t CD + v.3 Reviewer: c" ON PROOF of SUBMISSION FORMS �O Fire Department ❑ Received ❑ Not Water District ❑ Received [I Not Required Sanitation District E]Received E]Not Required Building Division Valuation: $ PLAN OF REPAIR FOR Mr. C. Cameron 3032 Ingalls Ct Wheatridge, CO 80204 Reference #: 201612 10 December 10, 2016 Scott A. Zurn, PE Loveland Colorado 970-449-2785 www.levelinspectionsco.com �164I 91 City of �" `7V heat iidge COMMUNITY DEVELOPMENT Wheat Ridge Building Division Validity of permit: the issuance of a permit or approval of plans, specifications and computations shall not be a permit for. or on oppK*d of,' yioipt"g any of the provisions of the building code or of any City ordinances. Permits presuming to give authority to violate or concea the provisions of the Building codes or other ordinances of the City shall not be valid. Page 2 of 23 CD n Q.41 0.m• Oo° !`? %".e l 1 CD CD 'v C O'a 'nCD •, G' '\ J r r _ ••.....•• G� ,.C3 + + t*�rn ,�0� N O b 'C3 'rn i W FA O oo– o � - � li CD — CD CD ��� CD rLob" ESM Col*wWd 00 CD �gp• N j f CD Low CD N 9 q m - a Dao -.r t ggQ 2 r-ac�-xG7 �+rnot-�mr rni.,On tmisD cmma'-x Cr O-o,Orm-z rz- cn cpm m�rm_-• v� �� '� rnc•�mm _ o�c�c�X�-3�arn� a'mnn stn O-cz �r= mor,__'l- Z �sr'nz ��� may, yr-� �o�C CTr aF cn C�m.v �Caq7O Z[i� Z m -t Om p O `�' Z-tst m r- Z2rn rAm•-rn=�a�r i RC7� 2�=5 A D -Tp 2 C~� tri NCD7� v m S y OAS' C rmn yt/> rnncnv-icn�ax.-a�++ Z M:V-r' mrni D-trrm�y t-. �_'i0y0 �mS O mrn Z mrnO r D OSrnc D vrz'- nT000z nZ rn�� Z Z m s Z t -r m -n 'o D �m z �� (`��yOO C D Qm 2 w'•ax D 2='- m eD- C.7 C C'T gym, n' Zz rm" r O m 'm5= C7 ~--� rymjr �.ppt?�z Z 0 Cj SC �' _� rnC'] m Gi�rn m Z m m O S ao r m m m •n Z m v is Z c7m n m Q rnrn0 t'�nn�-1 Zi -m-.Z -moi =-_9 z zz Z a' Dic�%9 v� vw DOO CA n tn''O�Op~FA Offer W pva0 RZt K2C2� ��rf~nZ tr1 cm i Z Olcr a OrnrnT �� rz�r m n Qx D yrnZ �_ Z� T h2 rn Z �p rarnOS 0:1 mO� QAC Q 2�v? Z Oqq ttv-- O OG7� Arn D m v D Sg m rp_mm r 03+ 02 < to Neafm2�".00 OzmT m 2z Cop � �pq� O m �rnz mc7 cam`, � C'�� tr,mx O{T� 0 tnoy a �C= rn{zy [n C mzZzO r En v0 C� v v r' p fJ m o C -t T eri r �+ n T m T T rn Z -OI T$ C h Q O m O x < p D D to m -� oar y, -t C'� �' to m -�'-' ...i z ® W r Z rn S al' rn 'n.'Z P mrn Z p mho la 0 3 m p' Co� amen - azo -� <+'> z r R9 co, C am= o z' -� - �=tc Ooyz Fg rmn�m y �Qm z `xD p mC, T [p m Z N p N fA')Qi m v o S+ • m s m i Cl mea° rnymao oz a m p A -t D p N y ft1 = --' M O x -.c m M"2 s mm< m<xAn A p" to A W N :-- d d= C,,G 0 - cD � rr r"n . B is p o :1. yG A? lD y W O (.A CAi A r r 0 CL N V + + — O r O iC to to 0 Mt 0. ITJ dd : l 1 n lA Qc"D C O O c n LM O O CD C C � 0 N 7 n n � I O CD O �• O � ';S. ;S F � 3 � t a fid � J s .} 'Y b C CN N m K Page 2 of 23 ENGINEERING AND INSPECTION PLAN OF REPAIR FOR Mr. C. Cameron 3032 Ingalls Ct Wheatridge, CO 80204 Reference #: 201612 10 December 10, 2016 Scott A. Zurn, PE Loveland Colorado 970-449-2785 www.levelinspectionsco.com Level Engineering LLC Page 3 of 23 STRUCTURAL GENERAL CONDITIONS Contractor shall maintain comprehensive general liability, workman's compensation, automobile liability and/or other insurance as appropriate for the work performed which will provide protection form any and all construction or completed operations claims. Certificates of Insurance shall be provided to LEVEL ENGINEERING LLC and/or the Client upon request. The limits will not be less than the minimum mandatory amounts required by the State of Colorado. All construction shall be performed in accordance with all applicable codes and standards, and good construction practices. Contractor shall obtain and pay for any and all permit fees, taxes and licenses required by governing agencies to complete the work. Contractor shall be responsible for all labor, materials, equipment, tools, operations and any other item necessary for proper completion of the work. Contractor should visit site prior to bid submittal to fully understand the scope of the project and the conditions at the site. By submitting a bid for the work proposed in this PLAN OF REPAIR, the contractor is implying that they have fully reviewed all associated documents and that they have full understanding of the work to be completed. The Contractor shall conduct a full review of this PLAN OF REPAIR prior to beginning work. If during this review or at any time during the construction process the contractor notes any errors or omissions in the plan, work shall be stopped and LEVEL ENGINEERING LLC shall be contacted immediately. Recommendations and specifications contained herein are based on general assumptions of the conditions, some of which cannot be observed during typical nondestructive visual observations. If unexpected conditions are encountered during the course of work, the Contractor shall contact LEVEL ENGINEERING LLC prior to proceeding. The Client shall provide water and electric hook-ups for temporary use. (Contractor must pre -arrange with Owner.) All utility lines and easements shall be located, marked and protected from damage throughout the performance of the work. Contractor shall call for utility locations unless other arrangements are made. Any damage to utility lines caused by the Contractor shall be repaired at the Contractor's expense. Contractor shall field verify all dimensions and existing conditions prior to commencement of work. Contractor shall notify LEVEL ENGINEERING LLC upon determination of any significant variation of the information provided on the attached documentation for his/her interpretation and decision, and such decision shall be final. Information provided regarding the existing conditions are believed to be accurate, however, Contractor shall be responsible for, and shall only use, his/her own measurements to verify existing conditions. THE REPAIR DESIGN Prepared by LEVEL Engineering, LLC makes no provisions for construction conditions that may arise during the performance of the work. Contractor shall be Level Engineering LL,' m Page 4 of 23 responsible for maintaining the stability and integrity of existing structures (bracing, shoring, benching, etc.). Contractor shall be responsible for the acts or omissions of his/her agents and subcontractors in the performance of their work. The Contractor shall be responsible for the means, methods, techniques, and sequences of construction. Existing material or property outside the scope of work that is damaged during construction shall be repaired to match their pre -construction condition at Contractor's expense. Unless noted otherwise, no substitutions or deviations from the repair plan and specifications are permitted without the express approval of LEVEL ENGINEERING LLC. Unauthorized modifications to the repair plan and specifications may deem the work unacceptable. All unacceptable work shall be promptly correct at the Contractor's expense under the direction of the LEVEL ENGINEERING LLC. Contractor shall maintain safe jobsite. The Contractor is to stack all necessary equipment and materials in a low traffic rea or in an area that will insure the safety of all individuals potentially present at this site during construction. OSHA standards shall be used as a guideline. Contractor shall keep the jobsite thoroughly clean at the end of each day. All surplus materials shall be safely stacked in a low traffic area or hauled away from the site. Contractor agrees to perform the work in a diligent manner and in full conformance with the repair plan. If a condition arises during the repair process which requires a change in the scope of work, LEVEL ENGINEERING LLC may submit addendums or modifications to the design which may add, delete or modify the scope of repair. Performance of any extra work, or payment for same, shall only be considered upon prior written authorization from Client. This document is for bid purposes only, The Contractor shall be responsible for utilizing a qualified Colorado Licensed Professional Engineer to inspect the repair work and to verify that the repair specifications described within this document are in compliance with local building codes and applicable Manufacturer standards. The proposal shall include a description of the Contractor's Warranty Terms and Conditions was well as Warranty Limitations. The proposal shall also include a description of the system as applicable. Level Engineering LLC 9 Page 5 of 23 CONCRETE All concrete shall conform to the most recent editions of the Building Code and ACI 318 adopted by the governing agencies in which the project is to be completed. All concrete shall have a 28 day compressive strength of 3000 psi. All concrete shall have a maximum aggregate size of 3/4" and no pea -gravel shall be used without written approval of this office. Minimum concrete coverage for steel reinforcement shall be as follows: Concrete cast against and permanently exposed to earth .......................... 3" Concrete cast in forms and exposed to earth or weather No. 6 bar and larger..................................................2„ No. 5 bar and smaller ................................................ 1-1 /2" Concrete not exposed to weather or in contact with ground ....................... 1-1 /2" Non -shrink grout shall conform to ASTM C-1 107 Care shall be taken to properly consolidate concrete thoroughly without causing segregation of the materials. STEEL REINFORCEMENT All reinforcement steel shall be deformed bars conforming to ASTM A-615, grade 60. Welding of steel reinforcement shall conform to AWS D-1.4. Provide chairs concrete blocks, spacer bars, ties, etc. As required to securely hold bars in place. When reinforcement must be spliced the bars should overlap at least 24', UNO. Overlapping bars shall be securely tied together with wire ties. Provide a minimum concrete cover of 3" where concrete is cast on the surface of the ground and 1-12" at all other locations, UNO. STRUCTURAL STEEL AND BOLTS All steel fabrication and installation shall conform to the latest addition of the AISC Manual of Steel Construction. All welding shall be completed by a certified welder using an AWS prequalified welding method in accordance with the requirements specified by the AWS in the structural welding code. E70xx electrodes shall be used for welds. All structural steel shall conform to ASTM A-36, UNO. All wide flange beams shall conform to ASTM A-572, grade 50. Level Engineering LLC H Page 6 of 23 All pipe columns shall conform to ASTMA-53, grade B or A-501 All tube steel shall conform to STM A-500, Grade B. Bolts and all -thread shall comply with ASTM A-325 Epoxy for epoxy bolts shall be Hilti Hit HY-150 or approved equal. Expansion bolts shall be Hilti Kwik Bolt III Expansion Anchors or approved equal. HELICAL PIERS The Helical Pier and concrete contractor shall be fully experienced in all aspects of helical pier, concrete and floor beam installation, design and construction. EPDXY INJECTIONS Concrete crack repair includes the sealing and healing of surface and internal cracks 1/16 inch or wider. Use epoxy paste sealer to install injection port devices and to caulk and seal cracks. Epoxy paste sealer shall be Sika Sikadur 33 or Sika Sikadur 31 hi -mod or approved equal. Space metal or plastic injection port tubes, or other approved injection port devices, approximately twelve (12) inches on center. As required, decrease port spacing to insure maximum penetration of the injected epoxy adhesive. Increase port spacing only with the engineer's approval. Epoxy injection adhesive shall be a 2 -Component, solvent free, moisture -insensitive epoxy adhesive. Sika Sikadur 52 or Sika Sikadur 35 hi -mod LV or approved equal. Once injection has been started on a crack, it shall be continued uninterrupted until the crack has been completely injected. Sufficient materials shall be immediately available at the jobsite before starting injection. Start injection at the lowest elevation point along a vertical crack and at an end of a horizontal crack. Continue injection until epoxy appears at the next consecutive port. Cap or seal the injection port and begin injection at the next consecutive port which has not been capped or sealed. Continue in this manner until the crack is completely injected. Upon completion of the crack injection process, all excess epoxy sealer and injection port devices shall be ground smooth and flush with the adjacent concrete surfaces. Level Engineering LLC • Page 7 of 23 SPECIFICATION FOR HELICAL PILE FOUNDATIONS COMPRESSION APPLICATIONS SCOPE 1.1 The work consists of designing, furnishing and installing helical piles and load transfer devices used to support compressive loads according to the project Plans and these specifications. 1.2 The parties and contract terms referred to in this specification are as follows: 1.2.1 The Owner is the person or entity that owns the facility or will own the facility once it is completed. The Owner may have contractual agreements with, and be represented by, other parties such as engineers, architects or contractors that perform services under the direction of the Owner. Where Owner is used in this specification, it refers to the owner or the Owner's contracted representatives separate from the Installing Contractor. 1.2.2 The Pile Designer is the individual or firm generally hired by the Installing Contractor to design the helical piles. 1.2.3 The Installing Contractor installs and tests (if necessary) the helical piles, and possibly performs other tasks associated with the project. 1.2.4 The Plans refer to the contract documents; including but not limited to the drawings and specifications for the project. 1.3 The work may include helical pile load testing. 1.4 The Owner will be responsible for obtaining any right-of-way or easement access permits necessary for the helical pile installation. 1.5 Unless otherwise noted, the Installing Contractor shall provide all labor, tools, equipment and materials necessary to accomplish the work. 1.6 The Owner will provide suitable access to the construction site for the Installing Contractor's personnel and equipment. 1.7 Unless specifically noted otherwise in the contract documents, the Owner will remove and replace any structures, utilities, pavements, landscaping or Level Engineering LLC Page 8 of 23 other surficial improvements in the work area as necessary to facilitate the work. 1.8 The Owner will be responsible for overall construction oversight to preclude the development of unsafe conditions. 1.9 The Owner will be responsible for a horizontal field survey of the helical pile locations prior to helical pile installation and an elevation survey to determine pile shaft cutoff height subsequent to helical pile installation. 1.10The work does not include any post -construction monitoring of pile performance unless specifically noted otherwise in the contract documents. 2 REFERENCES 2.1 American Institute of Steel Construction (AISC) 2.1.1 AISC 360: Specification for Structural Steel Buildings 2.2 American Society for Testing and Materials (ASTM) 2.2.1 ASTM A36: Carbon Structural Steel 2.2.2 ASTM A123: Zinc (Hot -Dip Galvanized) Coatings on Iron and Steel Products 2.2.3 ASTM A153: Zinc Coating (Hot -Dip) on Iron and Steel Hardware 2.2.4 ASTM A307: Carbon Steel Bolts, Studs, and Threaded Rod 60000 PSI Tensile Strength 2.2.5 ASTM A325: Structural Bolts, Steel, Heat Treated, 120/105 ksi Minimum Tensile Strength 2.2.6 ASTM A500: Cold -Formed Welded and Seamless Carbon Steel Structural Tubing in Rounds and Shapes 2.2.7 ASTM A513: Electric -Resistance Welded Carbon and Alloy Steel Mechanical Tubing 2.2.8 ASTM A572: High -Strength Low -Alloy Columbian -Vanadium Structural Steel 2.2.9 ASTM 8633: Electrodeposited Coatings of Zinc on Iron and Steel 2.2.10 ASTM Dl 143: Deep Foundations Under Static Axial Compressive Load 2.3 International Code Council Evaluation Services (ICC -ES) 2.3.1 Acceptance Criteria 358 (AC358): Acceptance Criteria for Helical Pile Systems and Devices 2.4 Society of Automotive Engineers (SAE) 2.4.1 SAE J429: Mechanical and Material Requirements for Externally Threaded Fasteners 3 DEFINITIONS 3.1 The following terms apply to helical piles used to support compressive loads: 3.1.1 Allowable Stress Design: A structural and geotechnical design methodology that states that the summation of the actual estimated loads (nominal loads) must be less than or equal to the allowable design load (required Level Engineering LLC [v Page 9 of 23 strength). Allowable loads are obtained by dividing a nominal resistance (strength) by an appropriate factor of safety. 3.1.2 Bearing Stratum: The soil layer (or layers) that provide the helical pile end - bearing capacity through load transfer from the helical plates. 3.1.3 Crowd: Axial compressive force applied to the helical pile shaft as needed during installation to ensure the pile advances at a rate approximately equal to the helix pitch for each revolution. 3.1.4 Design Loads: A generic and ambiguous term used to describe any load used in design. It is not specific to factored or unfactored loads or any particular design methodology. It is a term; therefore, that should be avoided when specifying load requirements. FSI recommends using the term service load, nominal load or factored load, as described herein, where applicable. 3.1.5 Design Strength: A term used in structural design which is defined as the product of the nominal strength and the applicable resistance factor. An equivalent term typically used in geotechnical design is, also sometimes referred to as factored resistance (Load and Resistance Factor Design). 3.1.6 Extension Section: Helical pile shaft sections connected to the lead section or other extension sections to advance the helix plates to the required bearing depth. Plain extensions (without helix plates) or helical extensions (with one or more helix plates) may be used depending upon soil conditions or project requirements. 3.1.7 Factor of Safety: The ratio of the ultimate pile capacity or nominal resistance (strength) to the nominal or service load used in the design of any helical pile component or interface (Allowable Stress Design). 3.1.8 Factored Load: The product of a nominal load and an applicable load factor (Load and Resistance Factor Design). 3.1.9 Factored Resistance: The product of a nominal resistance and an applicable resistance factor (Load and Resistance and Factor Design). 3.1.10 Geotechnical Capacity: The maximum load or the load at a specified limit state, that can be resisted through the piles interaction with the bearing soils (see also Ultimate Pile Capacity). 3.1.11 Helical Pile: Consists of a central steel shaft with one or more helix -shaped bearing plates and a load transfer device (bracket) that allows attachment to structures. Helical piles are installed into the ground by application of torque and axial compressive force ("crowd"). 3.1.12 Helix (Helical) Plate: Generally round steel plate formed into a helical spiral and welded to the central steel shaft. When rotated in the ground, the helix Level Engineering LLC Page 10 of 23 shape provides thrust along the pile's longitudinal axis thus aiding in pile installation. The plate transfers axial load to the soil through bearing. 3.1.13 Helix Pitch: The distance measured along the axis of the shaft between the leading and trailing edges of the helix plate. 3.1.14 Lead Section: The first helical pile shaft component installed into the soil. It consists of one or more helical plates welded to a central steel shaft. 3.1.15 Limit State: A condition beyond which a helical pile component or interface becomes unfit for service and is judged to no longer be useful for its intended function (serviceability limit state) or to be unsafe (ultimate limit state (strength)). 3.1.16 Load and Resistance Factor Design: A structural and geotechnical design methodology that states that the Factored Resistance (Design Strength) must be greater than or equal to the summation of the applied factored loads. 3.1.17 Load Factor: A factor that accounts for the probability of deviation of the actual load from the predicted nominal load due to variability of material properties, workmanship, type of failure and uncertainty in the prediction of the load (Load and Resistance Factor Design). 3.1.18 Load Test: A process to test the ultimate pile capacity and relation of applied load to pile head settlement by application of a known load on the helical pile head and monitoring movement over a specific time period. 3.1 .19 Loads: Forces that result from the weight of all building materials, occupants and their possessions, environmental effects, differential movement, and restrained dimensional changes. Permanent loads are those loads in which variations over time are rare or of small magnitude. All other loads are variable loads (see also Nominal Loads). 3.1.20 Mechanical Strength: The maximum load or the load at a specified limit state that can be resisted by the structural elements of a helical pile. 3.1.21 Net Deflection: The total settlement at the pile head minus the theoretical elastic deformation of the pile shaft during a load test. 3.1.22 Nominal Loads: The magnitude of the loads specified, which include dead, live, soil, wind, snow, rain, flood and earthquakes (also referred to as service loads or working loads). 3.1.23 Nominal Resistance: The pile capacity at a specified ultimate limit state (Load and Resistance Factor Design). See Ultimate Pile Capacity. 3.1.24 Nominal Strength: A term used in structural design which is defined as the structure or member capacity at a specified strength limit state. See Ultimate Pile Capacity. 3.1.25 Resistance Factor: A factor that accounts for the probability of deviation of the actual resistance (strength) from the predicted nominal resistance (strength) due to variability of material properties, workmanship, type of Leve! Engineering LLC Pagel 1 of 23 failure and uncertainties in the analysis (Load and Resistance Factor Design). 3.1.26 Service Loads: See "Nominal Loads" above. 3.1.27 Ultimate Pile Capacity: The helical pile capacity based on the least capacity determined from applicable ultimate limit states for mechanical and geotechnical capacity. 4 APPROVED HELICAL PILE MANUFACTURERS 4.1 Foundation Supportworks@, Inc., 12330 Cary Circle, Omaha, NE 68128; Phone: (800) 281-8545; Fax: (402) 393-4002. Ram Jack as an approved equal. 4.2 Due to the special requirements for design and manufacturing of helical piles, the piles shall be obtained from Foundation Supportworkso, Inc., or other qualified manufacturer with an approved equivalent product. A request to substitute any other manufactured helical product must be submitted to the Owner for review not less than seven (7) calendar days prior to the bid date. The request must include: 4.2.1 Documentation of at least five years of production experience manufacturing helical piles, 4.2.2 Documentation that the manufacturer's helical piles have been used successfully in at least five engineered construction projects within the last three years, 4.2.3 Product acceptance by the local building code official(s) having jurisdiction over the project, and/or 4.2.4 Current ICC -ES product evaluation report or complete description of product testing and manufacturing quality assurance programs used to assess and maintain product quality and determine product mechanical strength and geotechnical capacity. 5 ACCEPTABLE PRODUCTS 5.1 Hollow Round Shaft Helical Pile Models HP237, HP287, HP288, HP350, HP450, HP662 and HP700 manufactured in accordance with the requirements of Sections 5 and 6 of this specification. 5.1.1 Hollow round shaft helical piles shall be used to resist compression loads. Round shaft helical piles are generally more resistant to bending or buckling over solid Level Engineering LLC Page 12 of 23 square shaft counterparts due to superior cross-sectional properties and coupling details. 5.1.2 Pile shaft sections shall be in full, direct contact within couplings so as to remove coupling bolts and coupling welds from the "in-service" axial load path. 5.1.3 Pile shafts and couplings shall have a fit -up tolerance of 1/16 -inch or less. 5.1.4 Helix plates shall meet the following geometry and spacing criteria to minimize soil disturbance: 5.1.4.1 True helix -shaped plates that are normal to the shaft such that the leading and trailing edges are within'/4-inch of parallel. 5.1.4.2 Helix pitch is 3 -inches ±'/4 -inch. 5.1.4.3 All helix plates have the same pitch. 5.1.4.4 Helix plates have generally circular edge geometry. 5.1.4.5 Helix spacing along the shaft shall be between 2.4 and 3.6 times the helix diameter. 5.1.4.6 Helix plates are arranged along the shaft such that they all theoretically track the same path as the proceeding plate. 6 MATERIALS 6.1 Model HP237 Helical Pile System 6.1.1 Central Steel Shaft: The central steel shaft of the lead and extension sections are 2.375 -inch outer diameter by 0.154 -inch nominal wall thickness, hollow structural section in conformance with ASTM A500 Grade B or C with a minimum yield strength of 60 ksi and a minimum tensile strength of 70 ksi. The shaft finish is either plain steel or hot -dip galvanized in accordance with ASTM A123. 6.1.2 Shaft Coupling Material: The shaft coupling material is factory welded to the extension shaft and consists of 2.750 -inch outer diameter by 0.156 -inch nominal wall thickness, hollow structural section in conformance with ASTM A513 Type 5, Grade 1026 with a minimum yield strength of 70 ksi and a minimum tensile strength of 80 ksi. The shaft coupling finish is either plain steel or hot -dip galvanized in accordance with ASTM A123. 6.1 .3 Helix Plate Material: The helix plates are factory welded to the lead or extension shaft sections and consist of either 0.313 or 0.375 -inch thick ASTM A572 Grade 50 steel with a minimum yield strength of 50 ksi and a minimum tensile strength of 65 ksi. Helix plate outer diameters are 6, 8, 10, 12 or 14 -inches. The helix plate finish is either plain steel or hot -dip galvanized in accordance with ASTM Al 23. 6.1.4 Shaft Coupling Hardware: The lead and extension shaft sections are coupled with two (2) bolts and nuts per coupled shaft section. The coupling hardware consists of 0.625 -inch standard hex bolts conforming to ASTM A325 and heavy hex jam nuts. The bolts and nuts are hot -dip galvanized in accordance with ASTM A153. 6.1.5 Brackets: New construction bracket HP238NCB and retrofit brackets HP238132 and HP238BML are designed for use with the HP237 shaft. Bracket finishes are either plain steel or hot -dip galvanized in accordance with ASTM A123. Bracket hardware finishes for the new construction brackets are hot -dip galvanized in Level Engineering LLC Page 13 of 23 accordance with ASTM A153. Bracket hardware finishes for the retrofit brackets are zinc coated in accordance with ASTM B633. 6.2 Model HP287 and Model HP288 Helical Pile Systems 6.2.1 Central Steel Shaft: The central steel shaft of the lead and extension sections are 2.875 -inch outer diameter by 0.203 -inch nominal wall thickness (HP287) or 0.276 -inch nominal wall thickness (HP288), hollow structural section in conformance with ASTM A500 Grade B or C with a minimum yield strength of 60 ksi and a minimum tensile strength of 70 ksi. The shaft finish is either plain steel or hot -dip galvanized in accordance with ASTM A123. 6.2.2 Shaft Coupling Material: The shaft coupling material is factory welded to the extension shaft and consists of 3.500 -inch outer diameter by 0.281 -inch nominal wall thickness, hollow structural section in conformance with ASTM A513 Type 5, Grade 1026 with a minimum yield strength of 70 ksi and a minimum tensile strength of 80 ksi. The shaft coupling finish is either plain steel or hot -dip galvanized in accordance with ASTM A123. 6.2.3 Helix Plate Material: The helix plates are factory welded to the lead or extension shaft sections. Helix plates with outer diameters of 6, 8, 10, 12 or 14 -inches are either 0.375 or 0.500 -inches thick and 16 -inch diameter helix plates are 0.500 - inches thick. The helix plates are manufactured with ASTM A572 Grade 50 steel with a minimum yield strength of 50 ksi and a minimum tensile strength of 65 ksi. The helix plate finish is either plain steel or hot -dip galvanized in accordance with ASTM A 123. 6.2.4 Shaft Coupling Hardware: The lead and extension shaft sections are coupled with two (2) bolts and nuts per coupled shaft section. The coupling hardware consists of 0.750 -inch standard hex bolts conforming to SAE J429 Grade 8 and standard jam nuts. The bolts and nuts are zinc coated in accordance with ASTM 8633. 6.2.5 Brackets: New construction brackets HP288NCB or HP288NCB8 shall be used for tension and compression applications and HP288NCBE or HP288NCBE8 shall be used for compression only applications with the HP287 or HP288 shafts. Retrofit brackets FS288B, FS288BL, HP288B2, and HP288BML are designed for use with the HP287 or HP288 shafts. Bracket finishes are either plain steel or hot -dip galvanized in accordance with ASTM Al 23. Bracket hardware finishes are zinc coated in accordance with ASTM B633. 6.3 Hollow Round Shaft Helical Pile Models HP350, manufactured in accordance with the requirements of Sections 5 and 6 of this specification. 6.3.1 Hollow round shaft helical piles shall be used to resist compression loads. Round shaft helical piles are generally more resistant to bending or buckling Level Engineering LLC Page 14 of 23 over solid square shaft counterparts due to superior cross-sectional properties and coupling details. 6.3.2 Pile shaft sections shall be in full, direct contact within couplings so as to remove coupling bolts and coupling welds from the "in-service" axial load path. 6.3.3 Pile shafts and couplings shall have a fit -up tolerance of 1/1 6 -inch or less. 6.3.4 Helix plates shall meet the following geometry and spacing criteria to minimize soil disturbance: 6.3.4.1 True helix -shaped plates that are normal to the shaft such that the leading and trailing edges are within'/4-inch of parallel. 6.3.4.2 Helix pitch is 3 -inches ±'/4 -inch. 6.3.4.3 All helix plates have the same pitch. 6.3.4.4 Helix plates have generally circular edge geometry. 6.3.4.5 Helix spacing along the shaft shall be between 2.4 and 3.6 times the helix diameter. 6.3.4.6 Helix plates are arranged along the shaft such that they all theoretically track the same path as the proceeding plate. 7 DESIGN AND PERFORMANCE REQUIREMENTS 7.1 Helical piles shall be designed to support the specified compressive load (s) as shown on the project Plans. The overall length, helix configuration and minimum torsional resistance of a helical pile shall be such that the required capacity is developed by the helix plate(s) in an appropriate bearing stratum. 7.2 All structural steel pile components shall be designed within the limits provided by the American Institute of Steel Construction (AISC) Specification for Structural Steel Buildings (AISC-360). Either Allowable Stress Design (ASD) or Load and Resistance Factor Design (LRFD) are acceptable methods of analysis. Product testing in accordance with ICC -ES Acceptance Criteria 358 may also be considered as an acceptable means of establishing system capacities. 7.3 Except where noted otherwise on the project Plans, all piles shall be installed to provide an ultimate torque -correlated capacity based on an ASD or LRFD analysis. For ASD, a minimum factor of safety of 2 applied to the service or nominal loading shall be required. When an LRFD analysis is required, the Owner shall provide applicable pile design information including but not limited to; factored loads, resistance factors and/or the required ultimate pile capacity. Factors of safety (ASD) or resistance factors (LRFD) may require modification to meet specific deflection criteria stated on the Plans or drawings. 7.4 The required ultimate torque -correlated capacity shall be verified at each pile location by monitoring and recording the final installation torque and applying default torque correlations per ICC -ES AC358. Site specific torque Level Engineering LI_L Page 15 of 23 correlation factors may be determined by field compression load testing as specified in Section 14. 7.5 Except where noted otherwise on the project Plans, each pile shall be designed to meet a corrosion service life of 50 years in accordance with ICC -ES AC358. 7.6 The pile design shall take into account group efficiency from pile spacing, pile buckling potential, soil stratification, and strain compatibility issues. 8 QUALIFICATIONS OF INSTALLING CONTRACTOR AND DESIGNER 8.1 The Installing Contractor and/or Pile Designer shall submit to the Owner, a proposal including the documentation required in this Section. Work shall not begin until all the submittals have been received and approved by the Owner. All costs associated with incomplete or unacceptable submittals shall be the responsibility of the Installing Contractor. 8.2 Evidence of Installing Contractor's competence in the installation of helical piles shall be provided to the Owner's satisfaction and may include any or all of the following: 8.2.1 Pile manufacturer's certificate of competency for the installation of helical piles, 8.2.2 A list of at least three projects completed within the previous three years wherein the Installing Contractor installed helical piles similar to those shown in the project Plans. Such list to include names and phone numbers of those project representatives who can verify the Installing Contractor's participation in those projects, and/or 8.2.3 A letter from the pile manufacturer or manufacturer's representative expressing ability and intent to provide on-site supervision of the pile installation. 8.3 A listing of all safety violations lodged against the Installing Contractor within the previous three years and the current status or final resolutions thereof. Descriptions of safety improvements instituted within the previous three years may also be submitted, at the Installing Contractor's discretion. 8.4 Evidence of Pile Designer's competence shall be provided to the Owner's satisfaction and may include any or all of the following: 8.4.1 Registration as a Professional Engineer or recognition by the local jurisdictional authority, 8.4.2 A list of at least three projects completed within the previous three years wherein the Pile Designer designed helical piles similar to those shown in the project Plans. The list shall include names and phone numbers of those Level Engineering LLC Page 16 of 23 project representatives who can verify the Pile Designer's participation in those projects, and/or 8.4.3 Recommendation from the pile manufacturer or manufacturer's representative. 9 PRE -CONSTRUCTION SUBMITTALS 9.1 Within 2 weeks of receiving the contract award, the Installing Contractor and/or Pile Designer shall submit the following helical pile design documentation: 9.1.1 Certification from the Pile Designer that the proposed piles meet the requirements of this specification. 9.1.2 Qualifications of the Installing Contractor and Pile Designer per Section 8. 9.1.3 Product designations for helical lead and extension sections and all ancillary products to be supplied at each helical pile location. 9.1.4 Individual pile nominal loads, factors of safety, LRFD load and resistance factors and required ultimate torque correlated capacities, where applicable. 9.1.5 Individual pile loading requirements (if any). 9.1.6 Manufacturer's published allowable system capacities for the proposed pile assemblies, including load transfer devices. 9.1.7 Calculated mechanical and theoretical geotechnical capacities of the proposed piles. 9.1.8 Minimum pile termination torque requirements. 9.1.9 Maximum estimated installation torque and allowable installation torque rating of the proposed piles. 9.1.10 Minimum and/or maximum embedment lengths or other site specific embedment depth requirements as may be appropriate for the site soil profiles. 9.1.1 1 Inclination angle and location tolerance requirements. 9.1.12 Load test procedures and failure criteria, if applicable. 9.1.13 Copies of certified calibration reports for torque measuring equipment and load test measuring equipment to be used on the project. The calibrations shall have been performed within one year of the proposed helical pile installation starting date or as recommended by the equipment manufacturer. 9.1.14 Provide proof of insurance coverage as stated in the general specifications and/or contract. Level Engineering LLC Page 17 of 23 10 PLACEMENT REQUIREMENTS 10.1 Helical piles shall be installed within 3 -inches of the indicated plan location. 10.2 Helical pile shaft alignment shall be within 2 -degrees of the inclination angle shown on the Plans. 10.3 Top elevation of the helical piles shall be within 2 -inches of the design vertical elevation. 11 PILE INSTALLATION 11.1 Installing Contractor shall furnish and install all helical piles per the project Plans and approved pile design documentation. In the event of conflict between the project Plans and the approved pile design documentation, the Installing Contractor shall not begin construction on any affected items until such conflict has been resolved. 11.2 The Installing Contractor shall conduct their construction operations in a manner to insure the safety of persons and property in the vicinity of the work. The Installing Contractor's personnel shall comply with safety procedures in accordance with OSHA standards and any established project safety plan. 11.3 The Owner shall request marking of underground utilities by an underground utility location service as required by law, and the Installing Contractor shall avoid contact with all marked underground facilities. 11.4 The portion of the construction site occupied by the Installing Contractor, including equipment and material stockpiles shall be kept reasonably clean and orderly. 11.5 Installation of helical piles may be observed by representatives of the Owner for quality assurance purposes. The Installing Contactor shall give the Owner at least 24 hours' notice prior to the pile installation operations. 11.6 The helical pile installation technique shall be such that it is consistent with the geotechnical, logistical, environmental, and load carrying conditions of the project. The lead section shall be positioned at the appropriate site survey stake location as determined from the plan drawings. 11.7 The helical pile sections shall be advanced into the soil in a continuous manner at a rate of rotation less than 25 revolutions per minute (rpm). Sufficient crowd shall be applied to advance the helical pile sections at a rate approximately equal to the pitch of the helix plate per revolution. The rate of rotation and magnitude of down pressure shall be adjusted for different soil conditions and depths. Extension sections shall be provided to obtain the required minimum overall length and minimum torsional resistance as shown on the project Plans. 12 TERMINATION CRITERIA 12.1 The minimum final torsional resistance and/or any required pile length and embedment depth criteria, as specified in the Pre -Construction Submittals, must be satisfied prior to terminating the pile installation. In the event any Level Engineering LLC Page 18 of 23 helical pile fails to meet these production quality control termination criteria, the following remedies may be suitable if authorized by the Owner: 12.1.1 If the installation fails to meet the minimum torsional resistance criterion at the minimum embedment length: 12.1.1.1 Continue the installation to greater depths until the torsional resistance criterion is met, provided that, if a maximum length constraint is applicable, continued installation does not exceed said maximum length constraint, or 12.1.1.2 Demonstrate acceptable pile performance through pile load testing, or 12.1.1.3 Replace the pile with one having a different helix plate configuration. The replacement pile must not exceed any applicable maximum embedment length criteria and either: (A) be embedded to a length that places the last helix plate at least equal to its own diameter beyond the depth of the first helix plate of the replaced pile and meet the minimum torsional resistance criterion; or (B) pass pile load testing criteria. 12.1.2 If the torsional resistance during installation reaches the helical pile's allowable torque rating prior to satisfaction of the minimum embedment length criterion: 12.1.2.1 Terminate the installation at the depth obtained, or 12.1.2.2 Replace the pile with one having a shaft with a higher torsional strength rating. The replacement pile must be installed to satisfy the minimum embedment length criterion. It must also be embedded to a length that places the last helix plate at least equal to its own diameter beyond the depth of the first helix plate of the replaced pile without exceeding any applicable maximum embedment length requirements and it must meet the minimum final torsional resistance criterion, or 12.1.2.3 Replace the pile with one having a different helix plate configuration. The replacement pile must be installed to satisfy the minimum embedment length criterion. It must also be embedded to a length that places the last helix plate at least equal to its own diameter beyond the depth of the first helix plate of the replaced pile without exceeding any applicable maximum embedment length requirements, and it must meet the minimum final torsional resistance criterion. 12.1.3 If the installation reaches a specified maximum embedment length without achieving the minimum torsional resistance criterion: 12.1.3.1 If allowed, remove and reinstall the pile at a position at least three times the diameter of the largest helix plate away from the initial location. Original embedment length and torsional resistance criteria must be met. The pile repositioning may require the Level Engineering LLC Page 19 of 23 installation of additional helical piles with nominal loads adjusted for these spacing changes, or 12.1.3.2 Demonstrate acceptable pile performance through pile load testing, or 12.1.3.3 De -rate the load capacity of the helical pile based on default or site specific torque correlation factors and install additional piles as necessary. 12.1.3.4 Replace the pile with one having a different helix plate configuration. The replacement pile must be installed to satisfy the minimum and/or maximum embedment length criterion and it must meet the minimum final torsional resistance criterion. 12.1.4 If a helical pile fails to meet the acceptance criteria in a pile load test: 12.1.4.1 Install the pile to a greater depth and installation torque and re- test; provided that, if a maximum embedment length constraint is applicable, continued installation will not exceed said maximum length constraint, or 12.1.4.2 Replace the pile with one having more and/or larger helix plates. The replacement pile must be embedded to a length that places the last helix plate at equal to its own diameter beyond the depth of the first helix plate of the replaced pile without exceeding any applicable maximum embedment length requirements. The replacement pile must be re -tested, or, 12.1.4.3 De -rate the load capacity of the helical pile based on the results of the load test and install additional piles. Additional piles must be installed at positions that are at least three times the diameter of the largest helix plate away from any other pile locations. 12.1.5 If a helical pile fails a production quality control criterion as described in this Section or for any reason other than described in this Section, any proposed remedy must be approved by the Owner prior to initiating its implementation at the project site. 13 INSTALLATION RECORD SUBMITTALS 13.1 The Installing Contractor shall provide the Owner copies of the individual helical pile installation records within 24 hours after each installation is completed. Formal copies shall be submitted within 30 days following the Level Engineering LLC Page 20 of 23 completion of the helical pile installation. These installation records shall include, but are not limited to, the following information: 13.1.1 Date and time of installation 13.1.2 Location of helical pile and pile identification number 13.1.3 Installed helical pile model and configuration 13.1.4 Termination depth, pile head depth, and length of installed pile 13.1.5 Actual inclination of the pile 13.1 .b Final torsional resistance 13.1.7 Calculated geotechnical capacity based on final torsional resistance 13.1.8 Comments pertaining to interruptions, obstructions, or other relevant information 14 FIELD COMPRESSION LOAD TESTING 14.1 If field compression load testing is required, the Installing Contractor shall furnish all labor, equipment and pre -production helical piles necessary to accomplish the testing as shown in the approved pile design documentation. Installing Contractor shall apply the specified loads for the specified durations and record the specified data, for the specified number of piles. No deviations from the test plan(s) will be allowed without explicit approval in writing from the Owner. Pile testing shall be in general accordance with the ASTM Dl 143 quick test method and the following criteria: 14.1.1 Failure criteria shall be in accordance with AC358 and is when plunging occurs or when the net deflection exceeds 10% of the average helix plate diameter, whichever occurs first. 14.1.2 An alignment load equal to 5% of the anticipated failure load or maximum anticipated test load may be applied prior to the start of the test to take out slack in the load test frame. 14.1.3 Loading increments shall be performed at 5% of the anticipated failure load or maximum anticipated test load with a minimum hold time of 4 minutes at each increment. 14.1 .4 Upon completion of the maximum test load hold increment, the pile shall be unloaded in 5 to 10 even increments with minimum hold times of 4 minutes at each increment. 14.2 Installing Contractor shall provide the Owner copies of raw field test data within 24 hours after the completion of each load test. Formal test reports Level Engineering LLC Page 21 of 23 shall be submitted within 30 days following test completion. Formal test reports shall include the following information: 14.2.1 Name of project and Installing Contractor's representatives) present during load testing. 14.2.2 Name of manufacturer's representatives) present during load testing, if any. 14.2.3 Name of third party test agency and personnel present during load testing, if any. 14.2.4 Date, time, duration and type of the load test. 14.2.5 Unique test identifier and map showing the test pile location. 14.2.6 Pile model and installation information including shaft type, helix configuration, lead and extension section quantities and lengths, final pile tip depth, installation date, total test pile length and final termination torque. 14.2.7 Calibration records for applicable pile installation and test equipment. 14.2.8 Tabulated test results including cumulative pile head movement, loading increments and hold times. 14.2.9 Plots showing load versus deflection for each loading/unloading interval. 15 CLEANUP 15.1 Within one week of completion of the work, the Installing Contractor shall remove any and all material, equipment, tools, debris or other items belonging to the Installing Contractor or used under the Installing Contractor's direction. LIMITATIONS This repair design does not represent a complete analysis of the entire structure; it addresses conditions covered under the structural warranty provided by the contractor. The interpretations of the distress to be repaired are based on the visual observations of the structure. No detailed study was made of the structural elements of any part of the building. Therefore, no opinion is presented or shall be implied concerning the structural integrity of those elements not subject to visual inspection. Investigation and analysis of other portions of the structure are beyond the scope of this design at this time. LEVEL Engineering, LLC will not be responsible for 1) knowledge of subsurface conditions away from the existing borings, if any, without extensive geotechnical information supplied by a competent geotechnical engineer, 2) knowledge of distresses, or differential displacements that have occurred in an area which had not been exposed for visual observation during our site visit and 3) any other elements such as joists or beams and other structural members that are not readily visible. Level Engineering LLC �7 Page 22 of 23 LEVEL Engineering, LLC assumes that all information provided by the Client, Contractor, or other Consultants is correct, accurate, and may be acted upon accordingly, and shall have no liability for the validity of information provided. LEVEL Engineering, LLC shall have no liability for acts or omissions of the Contractor or any other agents performing the work on this project or for the failure of the Contractor to carry out the work in accordance with the plans and specifications if not inspect as intended. LEVEL Engineering, LLC shall not be responsible for the construction means, methods, techniques, sequence, procedures, or safety precautions related to this project and its execution that is under the control or direction of the Contractor. This PLAN of REPAIR is to be used with the accompanying drawings. Do not rely on one or the other, all materials contained in THE PLAN of REPAIR including but not limited to the cover letter, notes, plans, details, shall be used together to perform the proposed remedial construction. WORK DESCRIPTION For the purposes of this report, the front of the home is considered to face North. The structure of the single story single family home is a conventionally framed residence. The home has a crawl space with a majority of the space accessible through the exterior. The foundation system consists of reinforced concrete walls on spread footings. The structure is settling unevenly causing faulting and fracturing of the foundations, exterior brick veneer and unevenness of floors the structure. Helical underpinning is part of this work. This is the third stabilization effort on the home. This area of repair is in the back portion of the home. Nine helical piers are needed to lift and stabilize the back of the structure foundations (see plan). Once installed the foundations shall be raised as much as practical to a level position. Once the piles are installed. All restoration of finishes exterior decks and flatwork shall be restored in kind and in accordance with the owner's approval. The contractor is responsible for coordinating these type of repair scopes with the contractor. The contractor is required to coordinate these expectations with the owner and include the necessary work items in their bid proposals. REPAIR RECOMMENDATIONS 1. The concrete foundation walls are to be braced as required during the repair process by the Contractor. 2. Remove decks, pavers, slabs etc. to excavate the soil required to install the new repair helical foundation work, in accordance with drawings prepared by Level Engineering LLC. 3. Excavate the soil required to install the helical piers in accordance with drawings prepared by Level Engineering LLC. 4. Install nine helical piles to a depth of 25 ft. and 3500lbs/sf torque. Coordinate location with engineer per support works specifications and recommendations and drawings including specifications prepared by Level Engineering LLC Level Engineering LLC Page 23 of 23 5. Adjust foundation to level as much as practical. 6. Epoxy inject cracks per owner's direction. 7. Restore all finishes exterior and interior in accordance with agreements with owner. PROPOSED COMPLIANCE OBSERVATIONS All observations shall be conducted by a qualified Colorado Licensed Professional Engineer. More than one observation may be conducted during a site visit. The contractor is to determine the number of site visits required to do the observations and include this information in the bid documents. LEVEL Engineering, LLC is willing to complete the observation under contract. 1. Pre -Construction Meeting 2. Attachment of brackets to foundation walls. 3. load tests 4. Epoxy Injection of foundation wall cracks (directed by owner) 5. Review pier logs 6. Final Level Engineering LLC �6 Mr. Tyler Cameron 3032 Ingalls Court, Wheat Ridge, Colorado 80204 RE: Engineer's observation and certification for referenced single family residence, To Whom It May Concern, NKNMAig;201f art The scope of our work was to inspect the installation of foundation stabilization through helical piers designed by our firm. LEVEL Engineering LLC has inspected the above reference single family residence, This report reflects our observations, 9-b-s-ervations The foundation has a standard concrete cast in place partially reinforced 8 in thick foundation approximately 3 ft, in height, The residence has a crawl space. The foundation has experienced a settlement around the masonry and stone fireplace. The home has had helical piers placed in this area before however the quantity of piers was not implemented per the earlier engineering directives. As a result of this variance in directive, the foundations both yielded, settled and brokethe foundations, LEI has designed a foundation re6air and new helical ji F;11111;11��I��J�N' k6ft 1i This is to certify that LEVEL Ensi foundation repair system was installed as directed and designed. The foundation is structurally competent as of the date of this letter, I I f you have any questions or concerns regarding our findings, please feel free to contact us, Sincerely, 319 Mountain Climb Road Loveland CO 80537 970-449-2785 Daate:FOR OFFICE USE ONLY city Of ��'Wh6atp'd e P1 Wper it # C0MM,uN1TY'DEVE1,0PhiiNF Pien,Permit # Building & Inspection Services Division 7500 W. 29ttAve., Wheat Ridge, CO 80033 Plan Review Office: 303-235-2855 * Fax: 303-237-8929 Inspection Line.- 303-234-5933 q III III III 11111IIIIIIIIIIIIIIIII I! Ir Address: 0600111" Electrical: A�,2, Citv Licetse Plumbing., IL Complete all information on BOTH sides of this form NEW COMMERCIAL STRUCTURE Q ELECTRICAL SERVICE UPGRADE NEW RESIDENTIAL STRUCTURE 0 COMMERCIAL ROOFING COMMERCIAL ADDITION 0 RESID RESDENTIAL ADDITION 0 WINDOW REPLACEMENT COMMERCIAL ACCESSORY STRUCTURE w rage, shed, deck, etc.) RESIDENTIAL ACCESSORY STRUCTURE (Garage, shed, deck, etc.) MECHANICAL R M M1 REPAIR RR. REPLACEMENT PLUMBING SYSTEM/APPLIANCE REPAIR F • gr or • • LACMENT ELECTRICAL SYSTEM/APPLIANCE REPAIR or REPLACEMENT Sq. FULF Fife's Gallons Amps Squares Other Carbon ri-lonoxide detector(s) shall c(,m-nply with Section R,315 of the 2102 IR,(` & 'lot more than 10' ffi,),,y) the entrance of any sleeping room, Sinoke alan-ris all be required in each sleeping morn and outside each sleeping area per 2012 IRC, Section 313, MiVULW 4CEERING AND INSPECTION FoR Mr. Tyler Cameron 41n0 SjrrF'P'T 201 V T rcA �1'j `t, �-J` "A Scott A. Zurn, PE C H I [T B ,j i C1 AL .. .. ... ... . Loveland Colorado 9/� 449-2785 ' i6irC4 cnl S' o:.4 cr APPROVED Contractor shall be responsible for the acts or omissions of his/her agents and subcontractors in the performance of their work. The Contractor shall be responsible for the means, methods, techniques, and sequences of construction. k4*V.r,j-rr-.*t,v• * #pp. •u(s*.+� 5*rvRmupw----#*ru-rk • *--wTKx7ut*j*4 repaired to match their pre -construction condition at Contractor's expense. tie re�#,Tlr *janllal W7777ans are �Pett-nITTe-AM without the express approval of LEVEL ENGINEERING LLC. Unauthofted modifications to the repair plan and specifications may deem the work unacceptable. All unacceptable work shall be promptly correct at the Contractor's expense under the direction of the LEVEL ENGINEERING LLC. Contractor shall maintain safe jobsite. The Contractor is to stack all necessary equipment and materials in a low traffic rea or in an area that will insure the safety of all individuals potentially present at this site during construction. OSHA standards shall be used as a guideline. Contractor shall keep the jobsite thoroughly clean at the end of each day. All surplus materials shall be safely stacked in a low traffic area or hauled away from the site. wv� prior written authorization from Client. Licensed Professional Engineer to inspect f he repair work and to verify f hat f he repair specifications described within this document are in compliance with local building codes and applicable Manufacturer standards. 3 1 P a g e All concrete shall conform to the most recent editions of the Building Code and ACI 318 adopted by the governing agencies in which the project is to be completed. IN 1 11 INI !1 1 All concrete shall have a maximum aggregate size of 3l"' and no pea -gravel shall be used without written approval of this office. Minimum concrete coverage for steel reinforcement shall be as follows: Concrete cast against and permanently exposed to earth............ ............... 3" Concrete cast in forms and exposed to earth or weather No. 6 bar and larger... .............................. ............ 2" No. 5 bar and smaller ................................................1-1 /2" Concrete not exposed to weather or in contact with ground ...... — ........ .... 1-1/2" Care shall be taken to properly consolidate concrete thoroughly without causing segregation of the materials. STEEL REINFORCEMENT All reinforcement steel shall be deformed bars conformina to ASTM A-61 I � ii I t I i I i I � IN i I iii 111111 1 When reinforcement must be spliced the bars should ovedap at least 24UNO. Overlapping bars shall be securely tied together with wire ties. Provide a minimum concrete cover of 3" where concrete is cast on the surface of the ground and 1-12" at all other locations, UNO. All steel fabrication and installation shall conform to the latest addition of the AIS C Manual of Steel Construction. III qIIIIII 11111111 MAUO�P I '4MA 11 C ri f- lary- la Lqzm�i 't_ r Space metal or plastic injection port tubes, or other approved injection port devices, approximately twelve (12) inches on center. As required, decrease port spacing to insure maximum penetration of the injected epoxy adhesive. increase port spacing only with the engineer's approval. Epoxy injection adhesive shall be a 2 -Component, solvent free, moisture -insensitive epoxy adhesive. Sika Sikadur 52 or Sika Sikodur 35 hi -mod LV or approved equal. TiTt T1WF61_#�VJrTrtTT-drT"FW1# l­7#,7�:; 'CURTU 5T 11 1 completely injected. Sufficient materials shall be immediately available at the jobsite before starting injection. Start injection at the lowest elevation point along a vertical crack and at an end of a horitzontal crack. Continue injection until epoxy appears at the next consecutive port. III 11IRTI 111 11111111 1 IM IS 0 5 1 P a g e OA,is rw#jwir *esifn **ts "J retres&-i-it # c*mj#ltfd *m*lysis--*f t;Ne- tntirt strwctfire; it **,'*,r'tssds c*m*iti#,M covered under the structural warranty provided by the contractor. The interpretations of the distress to be repaired are based on the visual observations of the structure. No detailed study was made of the structural elements of any part of the building. Therefore, no opinion is presented or shall be implied concerning the structural integrity of those elements not subject to visual inspection. Investigation and analysis of other portions of the structure are beyond the scope of this design at this time, LEVEL Engineering, LLC will not be responsible for 1) knowledge of subsurface conditions away from f he existing borings, if any, without extensive geotechnical information supplied by a competent aeo ec N LEVEL Engineering, LLC assumes that all information provided by the Client, Contractor, or other Consultants is correct, accurate, and may be acted upon accordingly, and shall have no liability for f he validity of information provided. 'well'ourl"S 1rre'TT'vPfK'Wr1 1#1 Ifit- 1"911fulIQ Q1 ITIQ worK in accor#ancd with the plans and specifications if not inspect as intended. LEVEL Engineering, LLC shall not be responsible for the construction means, methods, techniques, sequence, procedures, or safety precautions related to this project and its execution that is under the control or direction of the Contractor. This PLAN OF REPAIR is to be used with the accompanying drawings. Do not rely on one or the other, all materials contained in THE PLAN OF REPAIR including but not limited to the cover letter, notes, plans, details, shall be used together to perform the proposed remedial construction. For the purposes of this report, the front of the home is considered to face north. The structure of the one story single family home is a conventional framed residence. The home has a crawl space. The foundation system consists of reinforced concrete grade beams on footings and has additions beyond the original construction. The home is exhibiting major settlement in one of the additions, Corrective measures through helical piers was executed in 2002 as a remediation to the settlement. The engineering recommendations on the placement of piers were only partially executed. As a result the home has continued to settle under the stone fireplace. This continued settlement has snapped the grade beam on the eastern portion of the addition. The 2002 pier under this wall performed wee however the grade beam failed under the stresses. The work areas are replacement of the eastern grade beam, utilizing the existing pier and adding three new helical piers on the north side under the stone fireplace. the broken wall shall new grade beam the contractor shall install new piers and correct the settlement through the lifting brackets. 1. The concrete foundation walls and home structure are to be braced as required during the repair process by the Contractor, 2. Excavate the soil required to install the helical pile at the foundation walls in accordance with drawings pages I and 2 dated Jan 12 th, 2016 by Level Engineering I. 3. Dowell new grade beam reinforcement construction into the exiting walls in accordance with the plans. 4. All excavations may be backfilled with the soil removed from the excavations. Compact the soil in 6" lifts. All observations shall be conducted by a qualified Colorado Licensed Professional Engineer. More than one observation may be conducted during a site visit. The contractor is to determine the number of site visits required to do the observations and include this information in the bid documents. LEVEL Engineering, LLC is willing to complete the observation under contract. 1. Pre -Construction Meeting 2. Installation of helical pile 3. Attachment of brackets and channels to foundation walls. 4. load tests 5. Foundation and steel beam re -leveling 6, Epoxy Injection of foundation wall cracks 7. Final 7 1 P a g e 0 6 0 A 0 0 a, MEMM01 J, 1:1 :11 *:M to] 17k, IFFAM :4 Z M M il, Y 0 0 ± 0 S!qOPE ].I The work consists of designing, furnishing and installing helical piles and load transfer devices used to support compressive and tension loads according to the project Plans and these specifications. III giii�111 !!II I!! I III !1 111 111111 :iiiil I Imp! 1.2.1 The Owner is the person or entity that owns the facility or will own the facility once it is completed. The Owner may have contractual agreements with, and be represented by, other parties such as engineers, architects or contractors that perform services under the direction of the Owner. Where Owner is used in this specification, it refers to the Owner or t Owner's contracted representatives separate from the Installing Contractor. 1.2.2 The Pile Designer is the individual or firm generally hired by the Installing Contractor to desig the helical piles. 1 IT 1.2.3 The Installing Contractor installs and tests (if necessary) the helical piles, and possibly performs other tasks associated with the project. 1.2.4 The Plans refer to the contract documents; including but not limited to the drawings a specifications for the project. I 1.4 The work includes installing piles in a quantity shown on the plans to a minimum of 20 ft. in depth and/or 3500 ft -pounds of torque. If this cannot be achieved contact the engineer for direction, 1.5 The Owner will be responsible for obtaining any right-of-way or easement access permits necessary for the helical pile installation. 1.6 Unless otherwise noted, the Installing Contractor shall provide all labor, tools, equipment and materials necessary to accomplish the pile installation work. 1.7 The Owner will provide suitable access to the construction site for the Installing Contractor's personnel and equipment. 1.8 Unless specifically noted otherwise in the contract documents, the Owner will remove and replace any structures, utilities, pavements, landscaping or other surficial improvements in the work area as necessary to facilitate the work. 1.9 The Owner will be responsible for overall construction oversight to preclude the development of unsafe conditions. rizon i 10W Ile 1*Q*T I nor TO helical pile installation and an elevation survey to determine pile shaft cutoff height subsequent to helical pile installation. specifically noted otherwise in the contract documents. 1.12 The work does not include any repairs to exterior landscaping or interior finishes repair or restoration due to installation. The work includes pile installation and concrete items only. 2 REFERENCES 11111ri 11111111111111 1111, # 2.2.1 ASTM A36: Carbon Structural Steel 2.2.2 ASTM A123: Zinc (Hot -Dip Galvanized) Coatings on Iron and Steel Products 2.2.3 ASTM, A 153: Zinc Coating (Hot -Dip) on Iron and Steel Hardware 2.2.4 ASTM A307: Carbon Steel Bolts, Studs, and Threaded Rod 60 000 PSI Tensile Strength 2.2.5 ASTM A325: Structural Bolts, Steel, Heat Treated, 120/105 ksi Minimum Tensile Strength 2.2.6 ASTM A500: Cold -Formed Welded and Seamless Carbon Steel Structural Tubing in Rounds and Shapes 2.2.7 ASTM A513: Electric -Resistance Welded Carbon and Alloy Steel Mechanical Tubing 2.2.8 ASTM A572: High -Strength Low -Alloy Columbian -Vanadium Structural Steel 2.2.9 ASTM 8633: Electrodeposited Coatings of Zinc on Iron and Steel 2.2.10 ASTM DI 143: Deep Foundations Under Static Axial Compressive Load 1111 � 11I i JIM I I I'II I 1!II I III mall iiri�IIJIIIIII I, Iiiiii 111111111fillliii i I I III III I III IIIIIIIIIIIp", '1111,1111 1111 1111111111111, l� 1111111 Jill 1� 3.1.1 Allowable Stress Design: A structural and geotechnical design methodology that states that the summation of the actual estimated foods (nominal loads) must be less than or equal to the allowable design load (required strength). Allowable loads are obtained by dividing a nominal resistance (strength) by an appropriate factor of safety. Bearing Stratum: The soil foyer (or layers) that provide the helical pile end -bearing capacity through load transfer from the helical plates. Crowd: Axial compressive force applied to the helical pile shaft as needed during installation to ensure the pile advances at a rate approAmately equal to the helix pitch for each revolution. 3.1.4 Design Loads: A generic and ambiguous term used to describe any food used in design. It is not specific to factored or unfactored loads or any particular design methodology. It is a term; therefore, that should be avoided when specifying food requirements. FSI recommends using the term service load, nominal load or factored load, as described herein, where applicable. Design Strength: A term used in structural design which is defined as the product of the nominal strength and the applicable resistance factor. An equivalent term typically used in geotechnical design is, also sometimes referred to as factored resistance (Load and Resistance Factor Design). 3.1.6 Extension Section: Helical pile shaft sections connected to the lead section or other extension sections to advance the helix plates to the required bearing depth. Plain extensions (without helix plates) or helical extensions (with one or more helix plates) may be used depending upon soil conditions or project requirements. 9 P a g e 3. 1.7 Factor of Safety: The ratio of the ultimate pile capacity or nominal resistance (strength) to the nominal or service load used in the design of any helical pile component or interface (Allowable Stress Design). 3.1.8 Factored Load: The product of a nominal load and an applicable food factor (Load and Resistance Factor Design), 3.1.9 Factored Resistance: The product of a nominal resistance and an applicable resistance factor (Load and Resistance and Factor Design). 3.1.10 Geotechnical Capacity: The maximum food or the load at a specified limit state, that can be resisted through the piles interaction with the bearing soils (see also Ultimate Pile Capacity). 3.1.11 Helical Pile: Consists of a central steel shaft with one or more helix -shaped bearing plates and a load transfer device (bracket) that allows attachment to structures. Helical piles are installed into the ground by application of torque and axial compressive force ("crowd"). 3.1.12 Helix (Helical) Plate: Generally round steel plate formed into a helical spiral and welded to the central steel shaft. When rotated in the ground, the helix shape provides thrust along the pile's longitudinal axis thus aiding in pile installation. The plate transfers axial load to the soil through bearing. 31.13 Helix Pitch: The distance measured along the axis of the shaft between the leading and trailing edges of the helix plate. 3.1.14 Lead Section: The first helical pile shaft component installed into the soil. It consists of one or more helical plates welded to a central steel shaft. 11.15 Limit State: A condition beyond which a helical pile component or interface becomes unfit for service and is judged to no longer be useful for its intended function (serviceability limit state) or to be unsafe (ultimate limit state (strength)). 3.1.16 Load and Resistance Factor Design: A structural and geotechnical design methodology that states that the Factored Resistance (Design Strength) must be greater than or equal to the summation of the applied factored loads. 3.1.17 Load Factor: A factor that accounts for the probability of deviation of the actual food from the predicted nominal load due to variability of material properties, workmanship, type of failure and uncertainty in the prediction of the load (Load and Resistance Factor Design). 3.1.18 Load Test: A process to test the ultimate pile capacity and relation of applied load to pile head settlement by application of a known load on the helical pile head and monitoring movement over a specific time period. 3.1.19 Loads: Forces that result from the weight of all building materials, occupants and their possessions, environmental effects, differential movement, and restrained dimensional changes. Permanent loads are those loads in which variations over time are rare or of small magnitude. All other loads are variable loads (see also Nominal Loads). 11.20 Mechanical Strength: The maximum load or the load at a specified limit state that can be resisted by the structural elements of a helical pile, 3.1 .21 Net Deflection: The total settlement at the pile head minus the theoretical elastic deformation of the pile shaft during a load test. 3.1.22 Nominal Loads: The magnitude of the loads specified, which include dead, live, soil, wind, snow, rain, flood and earthquakes (also referred to as service loads or working loads). 3.1 .23 Nominal Resistance: The pile capacity at a specified ultimate limit state (Load and Resistance Factor Design). See Ultimate Pile Capacity. 3.1.24 Nominal Strength: A term used in structural design which is defined as the structure or member capacity at a specified strength limit state. See Ultimate Pile Capacity. 10 1 Pi g e Resistance Factor: A factor that accounts for the probability of deviation of the actual resistance (strength) from the predicted nominal resistance (strength) due to variability of material properties, workmanship, type of failure and uncertainties in the analysis (Load and Resistance Factor Design). 3.1.27 Ultimate Pile Capacity: The helical pile capacity based on the least capacity determined fro applicable ultimate limit states for mechanical and geotechnical capacity, i 4.1 Foundation Supportwarks 's, Inc., 12330 Cary Circle, Omaha, NE 68128; Phone: (800) 281-8545; Fax: (4 2) 393-4002. 4.2 Due to the special requirements for design and manufacturing of helical piles, the piles shall be obtained from Foundation SupportworksP, Inc., or other qualified manufacturer with an approved equivalent product. A request to substitute any other manufactured helical product must be submitted to the Owner for review not less than seven (7) calendar days prior to the bid date. The request must include: Documentation of at least five years of production experience manufacturing helical piles, Documentation that the manufacturer's helical piles have been used successfully in at least five engineered construction projects within the last three years, 4.2.3 Product acceptance by the local building code official(s) having jurisdiction over the project, and/or 4.2.4 Current ICC -ES product evaluation report or complete description of product testing and manufacturing quality assurance programs used to assess and maintain product quality and determine product mechanical strength and geotechnical capacity. ACCEPTABLE PRODUCTS 5,1 Hollow Round Shaft Helical Pile Models HP237, HP287, HP288, HP350, HP450, HP662 and HP700 manufactured in accordance with the requirements of Sections 5 and 6 of this specification. 5.1.1 Hollow round shaft helical piles shall be used to resist compression loads. Round shaft helical piles are generally more resistant to bending or buckling over solid square shaft counterparts due to superior cross-sectional properties and coupling details. 5.1.2 Pile shaft sections shall be in full, direct contact within couplings so as to remove coupling bolts and coupling welds from the "in-service" axial load path. 5.1.3 Pile shafts and couplings shall have a fit -up tolerance of I/ 16 -inch or less. 5.1.4 Helix plates shall meet the following geometry and spacing criteria to minimize soil disturbance: 5JAJ True helix -shaped plates that are normal to the shaft such that the leading and trailing edges are within 1/4 -inch of parallel. 5.1.4.3 All helix plates have the some pitch. 5.1.4.4 Helix plates have generally circular edge geometry. 5.1.4.5 Helix spacing along the shaft shall be between 2.4 and 3.6 times the helix diameter, 5.1.4.6 Helix plates are arranged along the shaft such that they all theoretically track the same path as the proceeding plate. 6 MATERIALS 111 P age 6AA galvanized in accordance with ASTM A 153. Bracket hardware finishes for the retrofit brackets are zinc coated in accordance with ASTM B633. 12 1 P a g e III Ir 1111111i, III, Fill 11; 621 Central Steel Shaft: The central steel shaft of the lead and extension sections are 2.875 -inch outer diameter by 0.203 -inch nominal wall thickness (HP287) or 0,276 -inch nominal wall thickness (HP288), hollow structural section in conformance with ASTM A500 Grade B or C with a minimum yield strength of 60 ksi and a minimum tensile strength of 70 ksi. The shaft finish is either plain steel or hot -dip galvanized in accordance with ASTM A 123. 6.2.2 Shaft Coupling Material: The shaft coupling material is factory welded to the extension shaft and consists of 3.500 -inch outer diameter by 0.281 -inch nominal wall thickness, hollow structural section in conformance with ASTM A513 Type 5, Grade 1026 With a minimum yield strength of 70 ksi and a minimum tensile strength of 80 ksi, The shaft coupling finish is either plain steel or hot -dip galvanized in accordance with ASTM A 121 6.2.3 Helix Plate Material: The helix plates are factory welded to the lead or extension shaft section Helix plates wiith outer diameters of 6, 8, 10, 12 or 144nches are either 0,375 or 0.500 -inches thick and 16 -inch diameter helix plates are 0.500 -inches thick. The helix plates are manufactured �,Mth ASTM A572 Grade 50 steel witth a minimum yield strength of 50 ksi and a minimum tensile strength of 65 ksi. The helix plate finish is either plain steel or hot -dip galvanized in accordance \With ASTM A] 23. 6.2.4 Shaft Coupling Hardware: The lead and extension shaft sections are coupled with two (2) bol and nuts per coupled shaft section. The coupling hardware consists of 0.750 -inch standard )I hex bolts conforming to SAE J429 Grade 8 and standard jam nuts. The bolts and nuts are zin coated in accordance with ASTM B633. C2.5 Brackets: New construction brackets HP288NCB or HP288NCB8 shall be used for tension and compression applications and HP288NCBE or HP288NCBE8 shall be used for compression only applications with the HP287 or HP288 shafts. Retrofit brackets FS288B, FS288BL, HP288B2, and HP288BML are designed for use with the HP287 or HP288 shafts. Bracket finishes are either plain steel or hot -dip galvanized in accordance with ASTM A 123. Bracket hardware finishes are zinc coated in accordance with ASTM B633. 7.1 Helical piles shall be designed to support the specified compressive load(s) as shown on the project Plans. The overall length, helix configuration and minimum torsional resistance of a helical pile shall be such that the required capacity is developed by the helix plate(s) in an appropriate bearing stratum. 7.2 All structural steel pile components shall be designed within the limits provided by the American Institute of Steel Construction (AISC) Specification for Structural Steel Buildings (AISC- 360). Either Allowable Stress Design (ASD) or Load and Resistance Factor Design (LRFD) are acceptable methods of analysis. Product testing in accordance with ICC -ES Acceptance Criteria 358 may also be considered as an acceptable means of establishing system capacities. 7.3 Except where noted otherwise on the project Plans, all piles shall be installed to provide an ultimate torque -correlated capacity based on an ASD or LRFD analysis. For ASD, a minimum factor of safety of 2 applied to the service or nominal loading shall be required. When an LRF* analysis is required, the Owner shall provide applicable pile design information including but not limited to; factored loads, resistance factors and/or the required ultimate pile capacity. Factors of safety (ASD) or resistance factors (LRFD) may require modification to meet specific deflection criteria stated on the Plans or draWings. 7.4 The required ultimate torque -correlated capacity shall be verified at each pile location by monitoring and recording the final installation torque and applying default torque correlations per ICC -ES AC358. Site specific torque correlation factors may be determined by field compression load testing as specified in Section 14. 13 1 Page 7.5 Except where noted otherwise on the project Plans, each pile shall be designed to meet a corrosion service life of 50 years in accordance with ICC -ES AC358. 7.6 The pile design shall take into account group efficiency from pile spacing, pile buckling potential, soil stratification, and strain compatibility issues. 8 QUALIFI!gATIONS OF INSTALLIN!q!PONTRACTOR AND QESIGNER I 8.1 The Installing Contractor and/or Pile Designer shall submit to the Owner, a proposal including the documentation required in this Section. Work shall not begin unfit all the submittals have been received and approved by the Owner. All costs associated with incomplete or unacceptable submittals shall be the responsibility of the Installing Contractor. 8.2 Evidence of Installing Contractor's competence in the installation of helical piles shall be proviM ed to the Owner's satisfaction and may include any or all of the following: 8.2.2 A list of at least three projects completed vvithin the previous three years wherein the Installing Contractor installed helical piles similar to those shown in the project Plans, Such list to include names and phone numbers of those project representatives who can verify the Installing Contractor's participation in those projects, and/or 823 A letter from the pile manufacturer or manufacturer's representative expressing ability and intent to provide on-site supervision of the pile installation. 14 1 P a g e 8.3 A listing of all safety violations lodged against the Installing Contractor within the previous three years and the current status or final resolutions thereof. Descriptions of safety improvements instituted Within the previous three years may also be submitted, at the Installing Contractor's discretion. 8.4 Evidence of Pile Designer's competence shall be provided to the Owner's satisfaction and may include any or all of the following: Registration as a Professional Engineer or recognition by the local jurisdictional authority, 8.4.2 A list of at least three projects completed within the previous three years wherein the Pile Designer designed helical piles similar to those shown in the project Plans. The list shall include names and phone numbers of those project representatives who can verify the Pile Designer's participation in those projects, and/or 8.43 Recommendation from the pile manufacturer or manufacturer's representative. PRE-CONSTRU!qTION SUOMLTTALS 9.1 Within 2 weeks of receiving the contract award, the Installing Contractor and/or Pile Designer shall submit the following helical pile design documentation: 9.1.1 Qualifications of the Installing Contractor and Pile Designer per Section 8. 9.1.2 Product designations for helical lead and extension sections and all ancillary products to be supplied at each helical pile location, 9. 1.3 Individual pile nominal loads, factors of safety, LRFD load and resistance factors and required ultimate torque correlated capacities, where applicable. 9. 1.4 Individual pile loading requirements (if any). 9,1.5 Manufacturer's published allowable system capacities for the proposed pile assemblies, including load transfer devices. 9.1.6 Calculated mechanical and theoretical geotechnical capacities of the proposed piles. 9.1.7 Minimum pile termination torque requirements, 9.1.8 Maximum estimated installation torque and allowable installation torque rating of the proposed piles. 9.1.9 Minimum and/or maximum embedment lengths or other site specific embedment depth requirements as may be appropriate for the site soil profiles. 9.1.10 Inclination angle and location tolerance requirements. 9.1.11 Load test procedures and failure criteria, if applicable. 9.1.12 Copies of certified calibration reports for torque measuring equipment and load test measuring equipment to be used on the project. The calibrations shall have been performed within one year of the proposed helical pile installation starting date or as recommended by the equipment manufacturer. 11111111!1 111011 1111II1;11II1JI!!!IJII11I 1111111 111 1 MM 2 Uil 141;11113�V* 10. 1 Helical piles shall be installed within 3 -inches of the indicated plan location. 10.2 Helical pile shaft alignment shall be within 2 -degrees of the inclination angle shown on the Plans, Installing Contractor shall furnish and install all helical piles per the project Plans and approved pile design documentation. In the event of conflict between the project Plans and the approved pile design documentation, the Installing Contractor shall not begin construction on any affected items until such conflict has been resolved. 11 .2 The Installing Contractor shall conduct their construction operations in a manner to insure the safety of persons and property in the vicinity of the work. The Installing Contractor's personnel shall comply with safety procedures in accordance \With OSHA standards and any established project safety plan. 11.3 The Owner shall request marking of underground utilities by an underground utility location service as required by law, and the Installing Contractor shall avoid contact with all marked underground facilities. and material stockpiles shall be kept reasonably clean and orderly. 11 .5 Installation of helical piles may be observed by representatives of the Owner for quality assurance purposes. The Installing Contactor shall give the Owner at least 24 hours' notice prior to the plile installation operations. 11.6 The helical pile installation technique shall be such that it is consistent with the geotechnical, logistical, environmental, and load carrying conditions of the project. The lead section shall be positioned at the appropriate site survey stake location as determined from the plan drawings. 1]. 7 The helical pile sections shall be advanced into the soil in a continuous manner at a rate of rotation less than 25 revolutions per minute (rpm). Sufficient crowd shall be applied to advance the helical pile sections at a rate approximately equal to the pitch of the helix plate per revolution. The rate of rotation and magnitude of down pressure shall be adjusted for different soil conditions and depths. Extension sections shall be provided to obtain the required minimum overall length and minimum torsional resistance as shown on the project Plans. TY -f -I e m n mum na torsional resiss-fance and/or any required pile length and embedment depth criteria, as specified in the Pre-Constructiton Susls, must be satisfied prior to terminating the pile installation. In the event any helical pile fails to meet these production quality control termination criteria, the following remedies may be suitable if authorized by the Owner: 12. 1.1 If the installation fails to meet the minimum torsional resistance criterion at the minimum embedment length: 12.1.1.1 Continue the installation to greater depths until the torsional resistance criterion is met, provided that, if a maximum length constraint is applicable, continued installation does not exceed said maximum length constraint, or 12.1.1.3 Replace the pile with one having a different helix plate configuration. The replacement pile must not exceed any applicable maximum embedment length criteria and either: (A) be embedded to a length that places the lost helix plate at 16 1 P a g e least equal to its own diameter beyond the depth of the first helix plate of the replaced pile and meet the minimum torsional resistance criterion: or (B) pass pile load testing criteria. 12.1.2 If the torsional resistance during installation reaches the helical pile's allowable torque rating prior to satisfaction of the minimum embedment length criterion: 12.1-2.2 Replace the pile with one having a shaft with a higher torsional strength rating. The replacement pile must be installed to satisfy the minimum embedment length criterion. It must also be embedded to a length that places the last helix plate at least equal to its own diameter beyond the depth of the first helix plate of the replaced pile without exceeding any applicable maximum embedment length requirements and it must meet the minimum final torsional resistance criterion, or 12.1.2.3 Replace the pile with one having a different helix plate configuration. The replacement pile must be installed to satisfy the minimum embedment length criteriM n. It must also be embedded to a length that places the last helix plate at least equal to its own diameter beyond the depth of the first helix plate of the replaced pile without exceeding any applicable maximum embedment length requirements, and it must meet the minimum final torsional resistance criterion. 12-1.3 If the installation reaches a specified maximum embedment length without achieving the minimum torsional resistance criterion: 12.1.11 If allowed, remove and reinstall the pile at a position at least three times the diameter of the largest helix plate away from the initial location. Original embedment length and torsional resistance criteria must be met. The pile repositioning may require the installation of additional helical piles with nominal foods adjusted for these spacing changes, or 12.1.3.2 Demonstrate acceptable pile performance through pile load testing, or 1113.3 De -rate the load capacity of the helical pile based on default or site specific torque correlation factors and install additional piles as necessary. 12.1.3.4 Replace the pile with one having a different helix plate configuration. The replacement pile must be installed to satisfy the minimum and/or maximum embedment length criterion and it must meet the minimum final torsional resistance criterion. 12.1.4.1 Install the pile to a greater depth and installation torque and re -test; provided that, if a maximum embedment length constraint is applicable, continued installation will not exceed said maximum length constraint, or 12.1.4.2 Replace the pile with one having more and/or larger helix plates. The replacement pile must be embedded to a length that places the last helix plate at equal to its own diameter beyond the depth of the first helix plate of the replaced pile without exceeding any applicable maximum embedment length requirements. The replacement pile must be re -tested, or, 12.1.4.3 De -rate the load capacity of the helical pile based on the results of the load test and install additional piles. Additional piles must be installed at positions that are at least three times the diameter of the largest helix plate away from any other pile locations, 12.1.5 If a helical pile fails a production quality control criterion as described in this Section or for any reason other than described in this Section, any proposed remedy must be approved by the Owner prior to initiating its implementation at the project site. Mmlaw, •'M J&HIE-11M records within 24 hours after each installation is completed. Formal copies shall be submitted within #1•• owing the completion of the helical pile installation. These installation records shall include, but are not limited to, the following information: 13.1.1 Date and time of installation 13.1.2 Location of helical pile and pile identification number 13.1.3 Installed helical pile model and configuration 13.1.4 Termination depth, pile head depth, and length of installed pile 13.1.5 Actual inclination of the pile 13.1.6 Final torsional resistance 13.1.7 Calculated geotechnical capacity used on final torsional resistance 13.1.8 Comments pertaining to interruptions, obstructions, or other relevant information I Elm If 44MV161"T h1a **1 M• 14.1 If field compression load testing is required, the Installing Contractor shall famish all labor, equipment and pre -production helical piles necessary to accomplish the testing as shown in the approved pile design documentation. Installing Contractor shall apply the specified loads for the specified durations and record the specified data, for the specified number of piles. No deviations from the test plants) will be allowed without explicit approval in writing from the Owner. Pile testing shall be in general accordance with the ASTM D1143 quick test method and the following cdte(ia: 14.1.1 Failure criteria shall be in accordance with AC358 and is when plunging occurs or when the net deflection exceeds I 0'Yo of the average helix plate diameter, whichever occurs first. 14.1.2 An alignment load equal to 5% of the anticipated failure load or maximum anticipated test load may be applied prior to the start of the test to take out slack in the load test frame. 14.1.3 Loading increments shall be performed at 5% of the anticipated failure load or maximum anticipated test load with a minimum hold time of 4 minutes at each increment. 14.1.4 Upon completion of the maximum test load hold increment, the pile shall be unloaded in 5 to 10 even increments with minimum hold times of 4 minutes at each increment. 14.2 Installing Contractor shall provide the Owner copies of raw field test data within 24 hours after the completion of each food test. Formal test reports shall be submitted within 30 days following test completion. Formal test reports shall include the following information: 14.21 Name of project and Installing Contractor's representative (s) present during load testing. 14.2.2 Name of manufacturer's representative{s} present during load testing, if any. 14.2.3 Name of third party test agency and personnel present during load testing, if any. 14.2.4 Date, time, duration and type of the load test. 14.2.5 Unique test identifier and map showing the test pile location. 14,2.6 Pile model and installation information including shaft type, helix configuration, lead and extension section quantities and lengths, final pile tip depth, installation date, total test pile length and final termination torque. 14.2.7 Calibration records for applicable pile installation and test equipment. 14.2.8 Tabulated test results including cumulative pile head movement, loading increments and hold times. EMM41 15.1 Within one • of completion of the work, the Installing Contractor shall remove any and all material, equipment, tools, debris or other items belonging to the Installing Contractor or used under the • Contractor's direction. 19 1 P age Em� ~ ` | | ---- { ----- m 9 I I a ,W] Cp 4 M W. P. vto 6d A R tt vv NIRz r. I INSPECTION RECORD o ccupancy /TVpe �I►vsPECTION LINE: (303) 234 -5933 Inspections will not be made unless this card is posted on the building site Call by 3:00 PM to receive inspection the following business day. I I N SPECTOR MUST SIGN ALL SPACES: PERTAINING To THIS .JOB r` FOUNDATION INSPECTIONS DATE '. - INSPECTOR INITIALS COMMENTS: Footings /Caissons Stemwall.I (CEG).Concrete Encased Ground Reinforcing or Monolithic Weatherproof/ French Drain Sewer Service Lines. Water Service Lines' Heating (Underground) ^' POU NO CONCRETE UNTIL ABOVE HAS BEEN SIGNED CONCRETE SLAB FLOOR 'Electrical (Underground) K Plumbing (Underground) Heating (Underground) DO NOT Poui FLOOR UNTIL ABOVE HAS BEEN SIGNED :ROUGHS Sheathing,'. Lath / Wall tie 'Mid -Roof :Electrical Service Rough Electric Rough Plumbing Gas Piping'. Rough Mechanical ABOVE INSPECTIONS TO BE SIGNED PRIOR TO PROCEEDING Framing - Insulation Drywall Screw FINALS Electrical Plumbing Mechanical Roof Building Final Fire Department R.O.W & Drainage INSPECTIONS FOR PLANNING & ZONING, FIRE AND PUBLICE WORKS Parking & Landscaping ':SHOULD BE CALLED AT LEAST ONE WEEK PRIOR TO FINAL INSPECTIONS. "NOTE: ALL ITEMS MUST BE COMPLETED AND APPROVED BY PLANNING AND ZONING, BUILDING AND PUBLIC WORKS BEFORE A CERTIFICATE OF OCCUPANCY IS ISSUED. FINAL INSPECTION BY THE BUILDING DIVISION DOES NOT CONSTITUTE AUTHORIZATION OF A'.CERTIFICATE OF OCCUPANCY NOR PERMISSION FOR OCCUPANCY. UCCUNANCY NOT PERMITTED UNTIL CERTIFICATE OF OCCUPANCY IS ISSUED PROTECT THIS CARD FROM THE WEATHER I' ♦ i CITY OF WHEAT RIDGE Building Inspection Division (303) 234 -5933 Inspection line (303) 235 -2855 Office - (303) 237 -8929 Fax INSPECTION NOTICE. Job Address: -7 u,c:ea (A, 0, Permit Number: 061 '3 A S7 CJ NO one avallaDie Tor inspection: I ime ftl' cF_r, (AMtNM Re- Inspection required: Yes f i When corrections have been made, call or re- inspection at 303 - 2345933 ) i 1 Date: Ic? 4 7 6 inspector: L'a 'ZS -' � DO NOT REMOVE THIS NOTICE ♦ i CITY OF WHEAT RIDGE Building Inspection Division (303) 234 -5933 Inspection line (303) 235 -2855 Office • (303) 237 -8929 Fax - INSPECTIO - .0 Inspection Type: Job Address: Permit Number: ❑ No one available for inspection: Time b�, A Re- Inspection required: Yes * When corrections have been made, call for re- inspection at 303- 234 -5933 Date: i Inspector: I V t DO NOT REMOVE THIS TICE ♦ i CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type: LL7_ de,,. Job Address: 2n. /R/ -A/_Z, Permit Number: D q~X~ ) ❑ No one available for inspection: Time 414-) IAM/ M Re-Inspection required: Yes CNo *When corrections have been made, call for re-inspection at 303-2345933 Date: f //f I Inspector: DO NOT REMOVE THIS NOTICE ♦ i CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type: ~~iiYl2 %✓f ,7 Job Address: S'T~r7~~ f Permit Number: ❑ No one available for inspection: Time S` AM M Re-Inspection required: ee No When corrections have been made, callfofoJr re-inspection at 303-234-5933 Date: Inspector:'_~0 DO NOT REMOVE THIS NOTICE City of Wheat Ridge _r- Residential Solar PERMIT - 094527 a z PERMIT NO: 094527 ISSUED: 12/21/2009 JOB.. ADDRESS:. 3032.. INGALLS:. CT EXPIRES.: ..0.6/19/2010: DESCRIPTION: Solar- roof mounted. flush. x CONTACTS _ OWNER :-720/732-9008 Ray/Nikki Ragoness gc 303/233-3109 Joseph -L, -Espinoza 07-0010 ESP ELECTRIC * * PARCEL: INFO ZONE. CODE: UA - USE: UA SUBDIVISION: 0503 BLOCK/LOT#: 0./ N 0 FEE SUMMARY ESTIMATED PROJECT VALUATIO : 15,000.0 R id i l S l FEES 500 00 r s ~ es ent a o ar . ~ - Total valuation - .00 3°I41 ae NO A TOTAL * .500.00. . ^ g Conditions: RP: Must comply w/ 2003 IRC & 2005 NEC. Install per manufacturer specifications. Subject to field inspection. All metal rails shall be bonded. permit application are accurate, and do not violate applicable I hereby certify that the setback distances proposed by this ordinances, rules or regulations of the City of,Wheat Ridge or covenants,. easements or restrictions of record, that all measurements shown, and allegations: made are accurate; that I have read and agree to. abide by all conditions printed on this S application and that I: assume full responsibility for compliance with the Wheat Ridge Building Code. (I.B.C) and all other applicable Wheat Rrd rdinances, for work under this permit. Plans subject to field inspection. Si at e o£ retractor/owner date , 1. This permit was issued in accordance with the provisions set forth. in your application and is subject to the laws of the. State of Colorado and to the Zoning Regulations and Building Codes of wheat Ridge, Colorado or any other applicable ordinances of the City.. 2 This permit shall expire. 180.days ,from .the.issue .date. . Requests for.. an extension must be received prior to expiration date. An extension may be granted. at the discretion of the Building Official. 3. If this permit expires, a new permit may be acquired for a fee of one-half the amount normally. required, provided no changes have. been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes have been or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a. new permit. 4.. No work of any manner shall be done that will. change the natural flow of water causing a drainage problem. 5. Contractor shall notify. the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval oninspection card before proceeding with successive phases of the job. 6. The issuance of a permit or the approval of drawings. and specifications shall not be construed to be a permit for, nor an approval of,. any. violation of the. provisions of the building codes or any .other . ordinance,... law, rule.. or. regulation. " All plan revi subject to field inspections. . Signatur o ~Ilef Building Official date INSP TI ON REQUEST LIKE: (303)234-5933 BUILDING OFFICE: (303)235-2855 a REQUESTS MUST BE MADE BY 3PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. M a 7~ 3 l yoF "'"Eq? p City of Wheat Ridge Building Division m 7500 W. 29th Ave., Wheat Ridge, CO 80033 Office: 303-235-2855 " Fax: 303-237-8929 cO<oaro° Inspection Line: 303-234-5933 Building Permit Application Date: /DD)D q Plan ( ~7L~ Permit Q /Y Sv 7 Property Address; ~ } 3 Z ( jft P OL C t . `~f ~ ~5 O U Property Owner (please print): -Q) A~ ctJ A) - left. 2A~ I,nast Phone ~?ZO Z32 Mailing Address: (if different than property address) Address: ~F~' 0SCF J(c~ S City, State, Zip: 1 c~ 00 ~o z I 1 ~I o Contractor: :11 yt j6L Contractor License Phone: 72a - / 3' (P 3Z Sub Contractors: Electrical City License Plumbing City License Mechanical City License Company:'LrS P ~ ted", ~ Company Company: Exp. Date: ~bE ~LS~"2oz.° Exp. Date: Exp. Date: Approval: Approval Approval: Use of space (description): So ( Construction value: $ 1S-, doo. w Description of work: (as calculated per the Building Valuation Data sheet) Plan Review (due at time ofsubmittall: $ Sq. Ft./L.Ftadded: Squares BTU's Gallons Amps OWNEWCONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance with the Wheat Ridge Building Code (I.B.C) and all other applicable Wheat Ridge Ordinances, for work under this permit. Plans subject to field inspection. CIRLCE ONE.: (OWNER) (CONTRACTOR) or PERSONAL REPRESENTATIVE of (OWNER) -(CONTRATOR) PRINT NAME: ~(~CA~1 VAhC ~(°A rfb SIGNATURE: Date: 0 o.. p- Table of Contents i. Installer's Responsibilities ................2 Put I. Procedure to Determine the Design Wind Load 3 Part H. Procedure to Select Rail Span and Rail Type 10 Part III. Installing SolarMount [3.1.] SolarMount rail components 14 [3.2.] Installing Solar-Mount with top mounting clamps ..............15 [3.3.] Installing SolarMount with bottom mounting clips 21 [3.4.]Installing SolarMount with grounding clips and lugs 25 OF U N I RAC 6/1,1y copy Bright Thinking in Solar Unimc welcomes input concerning the aooaea yand user-friendliness of this publication. Please write to publications@unirac.eom. WO-UNIRAC Unirac Code-Compliant Installation Manual SolarMount i. Installer's Responsibilities Please review this manual thoroughly before installing your SolarMount system. This manual provides (1) supporting documentation for building permit applications relating to Unirac's SolarMount Universal PV Module Mounting system, and (2) planning and assembly instructions for SolarMount SolarMount products, when installed in accordance with this bulletin, will be structurally adequate and will meet the structural requirements of the IBC 2006, IBC 2003, ASCE 7- 02, ASCE 7-05 and California Building Code 2007 (collectively referred to as "the Code"). Unirac also provides a limited warrantyon SolarMour.t products (page 26). L SolarMount is much more than a product. It's a system of engineered components that can be assembled into a wide variety of PV mounting structures. With SolarMount you'll be able to solve virtually any PV module mounting challenge. It's also a system of technical support: complete installation and code compliance documentation, an on-line SolarMount Estimator, person-to-person customer service, and design assistance to help you solve the toughest challenges. Which is why SolarMount is PV's most widely used mounting system. The installer is solely responsible for: • Complying with all applicable local or national building codes, including any that may supersede this manual; • Ensuring that Unirac and other products are appropriate for the particular installation and the installation environment; • Ensuring that the roof, its rafters, connections, and other structural support members can support the array under all code level loading conditions (this total building assembly is referred to as the building structure); • Using only Unirac parts and installer-supplied parts as specified by Unirac (substitution of parts may void the warranty and invalidate the letters of certification in all Unirac publications); • Ensuring that lag screws have adequate pullout strength and shear capacities as installed; • Verifying the strength of any alternate mounting used in lieu of the lag screws; • Maintaining the waterproof integrity of the roof, including selection of appropriate flashing; • Ensuring safe installation of all electrical aspects of the PV array; and • Ensuring correct and appropriate design parameters are used in determining the design loading used for design of the specific installation. Parameters, such as snow loading, wind speed, exposure and topographic factor should be confirmed with the local building official or a licensed professional engineer. 2 SolarMount Unirac Code-Compliant Installation Manual ;;•UNIRAC Part I. Procedure to Determine the Design Wind Load [1.1.1 Using the Simplified Method - ASCE 7-05 The procedure to determine Design Wind Load is specified by the American Society of Civil Engineers and referenced in the International Building Code 2006. For purposes of this document, the values, equations and procedures used in this document reference ASCE 7-05, Minimum Design Loads for Buildings and Other Structures. Please refer to ASCE 7-05 if you have any questions about the definitions or procedures presented in this manual. Unirac uses Method 1, the Simplified Method, for calculating the Design Wind Load for pressures on components and cladding in this document. The method described in this document is valid for flush, no tilt, SolarMount Series applications on either roofs or walls. Flush is defined as panels parallel to the surface (or with no more than 3" difference between ends of assembly) with no more than 10" space between the roof surface, and the bottom of the pV panels. This method is not approved for open structure calculations. Applications of these procedures is subject to the following ASCE 7-05 limitations: 1. The building height must be less than 60 feet, h < 60. See note for determining h in the next section. For installations on structures greater than 60 feet, contact your local Unirac Distributor. 2. The building must be enclosed, not an open or partially enclosed structure, for example a carport. 3. The building is regular shaped with no unusual geometrical irregularity in spatial form, for example a geodesic dome. 4. The building is not in an extreme geographic location such as a narrow canyon or steep cliff. 5. The building has a flat or gable roof with a pitch less than 45 degrees or a hip roof with a pitch less than 27 degrees. 6. If your installation does not conform to these requirements please contact your local Unirac distributor, a local professional engineer or Unirac If your installation is outside the United States or does not meet all of these limitations, consult a local professional engineer or your local building authority. Consult ASCE 7-05 for more clarification on the use of Method I. Lower design wind loads may be obtained by applying Method II from ASCE 7-05. Consult with a licensed engineer if you want to use Method II procedures. The equation for determining the Design Wind Load for components and cladding is: pnet (psf) = AKsrlpnet3o pnet (Psf) = Design Wind Load A = adjustment factorfor height and exposure category Kn = Topographic Factor at mean roof height, h (ft) I = Importance Factor pnet3o (psf) = net design wind pressure for Exposure B, at height =30,1=1 You will also need to know the following information: Basic Wind Speed = V (mph), the largest 3 second gust of wind in the last 50years. h (ft) = total roof height forflat roof buildings or mean roof height for pitched roof buildings Effective Wind Area (sf) = minimum total continuous area of modules being installed Roof Zone = the area of the roof you are installing the pv system according to Figure 2, page 5. Roof Zone Setback Length = a (ft) Roof Pitch (degrees) Exposure Category [1.2.] Procedure to Calculate Total Design Wind The procedure for determining the Design Wind Load can be Step 2: Determining Effective Wind Area broken into steps that include looking up several values in different tables . Determine the smallest area of continuous modules you will be installing. This is the smallest area tributary (contributing load) to a support or to a simple-span of rail. That area is the Step 1: Determine Basic Wind Speed, V (mph) Effective Wind Area, the total area of the fewest number of Determine the Basic Wind Speed, V(mph)by consulting your modules on a run of rails. local building department or locating your installation on the maps in Figure 1, page 4. - 3 ::'UNIRAC UnfracCode-CompliantlnstallatonManual SolarMount 85 mpfi. , re 38 m/s) Step 3: Determine Roof/Wall Zone The Design Wind Load will vary based on where the installation is located on a roof. Arrays maybe located in more than one roof zone. Using Table 1, determine the Roof Zone Setback Lengt14 a (ft), according to the width and height of the building on which you are installing the pv system. Table I. Determine RooffWall Zone, length (a) according to building width and height a = 10 percent of the least horizontal dimension or 0.4h, whichever is smaller, but not less than either 4°k of the least horizontal dimension or 3 ft of the building. Roof Least Horizontal Dimension (ft) Height (ft) 10 IS 20 25 30 40 50 60 70 80 90 100 125 150 17S 200 300 400 S00 J=...... 3=. . 3 .J. 4 0__¢ :a: A 7 12tlr 20; _s IS 3 3 3 3 3 4 5 6 6 6 6 6 6 6 7 8 12 16 20 5,.,6 3 8. ,8 .-Ib„(f= 25 3 3 3 3 3 4 5 6 7 8 9 10 10 10 10 10 12 16 20 -30..„i .,.,f:.~~IZ"" 35 3 3 3 3 3 4 5 6 7 8 9 10 12.5 14 14 14 14 16 20 4 lbws-.15:10 45 3 3 3 3 3 4 5 6 7 8 9 10 12.5 15 17.5 18 18 18 20 4.2 .,.5 12.5- „15. ..f5.5 20 20.....3.q". 20=; 60 3 3 3 3 3 4 5 6 7 8 9 ID 12.5 15 17.5 20 24 24 24 Source: ASCEISEI 7-05, Minimum Design Loads for Buildings and Other Structures, Chapter 6, Figure 6-3, p.41 r.k 4 C, SolarMount UniracCode-Compliant Installation Manual p UNIRAC Step 3: Determine Roof Zone (continued) UsingROOfZone Setback Length, a, determine the roof zone locations according to your roof type, gable, hip or monoslope. Determine in which roof zone your pv system is located, Zone 1, 2, or 3 according to Figure 2. G ❑ Interior Zones Roofs -Zone I/Walls -Zone 4 End Zones Corner Zones Roofs - Zone 2/Walls - Zone 5 Roofs - Zone 3 Source: ASCE/SEI 7-05, Minimum Design Loads for Buildings and Other Structures, Chapter 6, p. 41. Step 4: Determine Net Design Wind Pressure, pnerso (psf) Using the Effective Wind Area (Step 2), Roof Zone Location (Step 3), and Basic Wind Speed (Step 1), look up the appropriate Net Design Wind Pressure in Table 2, page 6. Use the Effective Wind Area value in the table which is smaller than the value calculated in Step 2. If the installation is located on a roof overhang, use Table 3, page Z Both downforce and uplift pressures must be considered in overall design. Refer to Section II, Step 1 for applying downforce and uplift pressures. Positive values are acting toward the surface. Negative values are acting away from the surface. 5 Figure 2. Enclosed buildings, wall and roofs r U N I RAC Unirac Code-Compliant Installation Manual SolarMount Table 2. pnet3o (psi) Roof and Wall ftkWmdspeed,v(mph) 90 _ 100 1'1.0 .3, 120 ":130' : . f40 " °136- 170 e~aHe e ,.A , WndAmo Zan e (:0 PpIFo@n .,Upjh Dowforce Uplih pavmt,r up1fiNpownfortt Whpavm(arce UpIUC, Dov Tce Uplfe 'p?oymk[ae_' UpFft-Do fo rce UpW I 10 59 146' 7.3 -18.0 89 3.1,8'! 10.5 -25.9 14.3 -353 f6S_ 21.1 -52.0 1 20 6.9 -17.5 83 -212 , 9.9 -25.2 I I4..: -29,4= 13.4 -344 5 1 4 -~-39~^ 19.8 -50.7 0 1 50 737"'. 6.3 -16.9 76 -2QS.y 9.0 -24.4 106 =2$6 ' 12.3 , , , -332 141''-; 18.1 -48.9 I 100 47 133„ 5.8 -16.5 70'x'-#9.9'=1 8.3 -23.7 9.8 27 11.4 -32.3 13,0,-37;@ 16.7 A7.6 'a 2 10 $9 24.4 7.3 -30.2 89 36.5 a 10.5 -43.5 14---54;0 14.3 -592 163 67 921.1 -87.2 c 2 20 ::5 6 218:. 6.9 -27.0 5,3 -32.6?1 9.9 -38.8 I 1 6 ,4516 ' 13.4 52.9 45 4 =6@.7 [9.8 -78.0 2 50 . S 1 I S 4.. 6.3 -22.7 , - 47:5:: 9.0 -32.7 10 6, ,-3$;4 :i ' 12.3 -44.5 I4.J, =31;1.: 18.1 -65.7 c 2 100 5.8 -19.5 ':-Z@ 2368.3 -28.1 9.8 :330'= 11.4 -382 i39:-=F3.9'= 16.7 -56.4 3 10 "i59 36$x: 7.3 -45.4 89 10.5 -65.4 124.:"-7628 " 14.3 -890 465 T.-1Q2,2i 21.1 -131.3 3 20 'Sb 305,' 6.9 -37.6 9.9 -54.2 116„~63.'b i 13.4 -738 I$AI ,44119.8 -108.7 3 50 =223:', 6.3 -27.3 Tb =33.1'2- 9.0 -39.3 : J -46;2 _ 12.3 -535 147:°¢1„18.1 -78.9 3 100 .4:7 5.8 -19.5 70 '-23.6-- 8.3 -28.1 -=i -310 11.4 -382 130 16.7 -56.4 I 10 .:84 133-:-_ 104 -16.5 42 194,-, 14.9 -23.7 !75 27$. 20.3 -323 233 "y37P 30.0 -47.6 1 20 ; 37 13-0:9 4 16.0 l 14 -i9 4 w 13.6 -23.0 I 6O :T 27-0• 5 18. -31 4 X 13 36.0 27.3 -46.3 a v I 50 82 -15.4 AO 486'i 11.9 -22.2 -i39 ,36.0 16.1 -302 1$5 =34&''. 23.8 -44.5 1 100 59 12:1 7.3 -14.9 89 -1;3.1° 10.5 -21.5 QSi2'. 14.3 - -293 165 21.1 -43.2 2 10 ':$;4 6232,' 104 -28.7 1125, -34.71; 149 A1.3 175`'-4$:4-'- 20.3 -562 23,3 ~=64:5' 30.0 -82.8 e 2 20 77 9.4 26.4 =17 4 :314 13.6 -38.0 I b D -944'i 18.5 ~-593,'., 27.3 -51.7 ;71,3 -76.2 2 50 IS91 82 23.3 =980 -MZ:° 11.9 -33.6 139 -394:. 16.1 , -457 185";'?52-,.F 23.8 -67.4 ° 2 100 ; 5,9 -17A - 7.3 -21.0 10.5 -30.3 124 =35:6'' 14.3 -41.2 16,5. , =4T 3.`: 21.1 -60.8 o 3 10 AA 3431 104 -424 _125 51A 14.9 -61.0 175 `-71.6,; 20.3 -831 2234>-95:.4": 30.0 -122.5 3 20 7 321.- 94 39.6 114 -979-' 13.6 -57.1 160. -74- 18.5 -777 213, :.9 ;k _ 27,3 -114.5 3 50 ;67 29:.f 82 360 '810Q M#3;S_-. 11.9 -51.8 139 W" 16.1 . . -705 fB5 'Sk 0'7 23.8 -104.0 3 too Sg 26:9'` 73 332 $9 -40- 10.5 -47.9 124"-56- 14.3 -651 21.1 -96.0 I 10 ~Tv 133 .L4.b': 16.5 18.0 ::199 21 23.7 -25.9 278 :an4' 32.3 -35.3 -90.5'. 47.6 -52.0 1 20 160 171 %194 2tj,"7"~= 23.0 -24.6 27Q .48:9 31.4 -335 36@ .'-3&4'46.3 - -49.3 I so 125 "12:8 is 154 15.9 :356 `:n19.2 ' 22.2 -22.8 260 26:8 `i 30.2 - AF -31.1 -346-.,-3 $7 44.5 -45.8 1 100 921 149 14.9 =[$1,x5;1!^=.21.5 -21.5 453.] 29.3 , -293 33b.",-«3.6;:43.2 -43.2 a 2 10 14:3 -17.0 16.5 -21.0 =19 9 -25.5 , ' 23.7 -30.3 27 8 •35 32.3 -41.2 378 3ff 3;` 47.6 -60.8 2 20 110 16.3 ~ 16.0 -20.1 'k94 24 3 23.0 -290 27 Q -34.b" 31.4 -39.4 4C A .-4S 346 3 -58 1 « 2 50 15.4 -18.9 , °I8 5 32 9., 22.2 -27.2 36 0 U 30.2 . -37 1 34 6 `-2 S 44.5 . -54 6 2 100 .12:1 14,6 14.9 -18.0 21 ] & I 218' 5 , -25 9 toL'~'541 3014 29 3 _ . -35 3 409-: 43 2 33 b . 52 0 . . . _ . . . , - - . - . 0 3 10 13':3 165 -21.0 E99 35.5', 23.7 TTTT -30.3 278 35,fx 32.3 -41.2 -370 ~}73:"'. 47.6 -60 8 m 3 20 13:8 #63,,160 201 -194 3.4323.0 " -29.0 3T0 340 2 31.4 -394 360 ''='453..46.3 . -58.1 3 50 ° I2<5 15 3 g 15.4 -18.9 .,I$ b 229 22.2 . -27.2 26-4 32.0 30.2 -425 i 44.5 -37.1 34fi -54.6 3 100 ,12;:.7 l4 149 180 E81 21 $ = 21.5 -25.9 252 3Qx4 29.3 , -353 836 :;-.;}P.S 43.2 -52.0 4 10 i*6 15.8 - I 8.o 19 5 21.8 23 6 25.9 -28.1 30 4 33.0 ` 35.3 -38.2 4PS :439--_ 52.0 -56.4 4 20 172 187 X08 Z2.6.: 24.7 -26.9 290,31.6',, 33.7 -36.7 557 42149.6 -54.1 4 50 110 14.3' 16.1 17.6 -395 21.3 23.2 -25.4 X72 39.8` 31.6 -34.6 46.6 -51.0 4 100 1T4 •13.6 . 1-5.3 -16.8 .1$ 5 -2Q4: 22.0 -24.2 25 9 2$:4 30.0 -33.0 344 ' -37844.2 -48.6 m 4 500 10.9 12:1 34 -149 16 2 ! %T~ 19.3 -21.5 22 7 25:2 26.3 -29.3 38.8 -43.2 3 5 t0 1'#n6 19.5'- 180 24.1 -218 29>I 25.9 -34.7 8P.} qP _ 35.3 -47.2 52.0 59.6 5 20 1,3,J 753`;. 172 225 `@fl 27.2:24.7 32.4 2Y4 '=3$.6 : 33.7 -44.0 49.6 -64.9 5 50 L3;q 165.!. 161 203 795 246,':123.2 -29.3 272 34,;,3 31.6 -39.8 363..-45,7:;:46.6 -58.7 5 100 '12_-4 13.1 153 187 22.0 -26.9 "25 r} 3:I:fi- 30.0 -36.7 -44.2 -54.1 5 500 i,'d 9 12.1 ! 13 4 14 9 ' ["6 2 ..98;1 ' 19.3 -21.5 22 7 25.2-- 26.3 -29.3 3P 2 :333`"-, 38.8 -43.2 3oorwe: A>LUt to /-W, Minimum Design Loads for Buildings and Other Structures, Chapter 6, Figure 6-3, p. 42-43. 6 SolarMount Unirac Code-Compliant Installation Manual po UNIRAC Table 3. pner30 (pso Roof Overhang Step 5: Determine the Topographic Factor, Kzt For the purposes of this code compliance document, the Topographic Factor, Ks,, is taken as equal to one (1), meaning, the installation is surrounded by level ground (less than 10% slope). If the installation is not surrounded by level ground, please consult ASCE 7-05, Section 6.5.7 and the local building authority to determine the Topographic Factor. Step 6: Determine Exposure Category (B, C, D) Determine the Exposure Category by using the following definitions for Exposure Categories. The ASCE/SEl7-05* defines wind exposure categories as follows: Exeosums E is urban and suburban areas, wooded areas, or other terrain with numerous closely spaced obstructions having the size of single family dwellings. exrosuve c has open terrain with scattered obstruc- tions having heights generally less than 30 feet. This category includes flat open country, grasslands, and all water surfaces in hurricane prone regions. Exi OSURE D has flat, unobstructed areas and water surfaces outside hurricane prone regions. This catego- ry includes smooth mud flats, salt flats, and unbroken ice. Also see ASCE 7-05 pages 287-291 for further explanation and explanatory photographs, and confirm your selection with the local building authority. 7 Source: ASCEISEl 7-05, Minimum Design Loads for Buildings and Other Structures, Chapter b, p. 44. } ::°UNIRAC UniracCode-Compliant lnstaltarionManual SolarMount Step 7: Determine adjustmentfactorfor height and Table 4. Adjustment Factor (A) for Roof Height& exposure category,A Exposure Category Using the Exposure Category (Step 6) and the roof height h sr>o < (ft), look up the adjustmentfactor for height and exposure in me<~,ool Table 4. h,h,(p) g C D Step 8: Determine the Importance Factor, I Determine if the installation is in a hurricane prone region. Look up the Importance Factor, I, Table 6, page 9, using the occupancy category description and the hurricane prone region status. Step 9: Calculate the Design Wind Load, pact (ps.) IS 1.00 1.21 1.47 20 1.00 1.29 1.55 25 1.00 1.35 1.61 30 1.00 1.40 1.66 35 1.05 1.45 1.70 40 1.09 1.49 1.74 45 1.12 1.53 1.78 50 1.16 1.56 1.81 55 1.19 1.59 1.84 60 1.22 1.62 1.87 Multiply the Net Design Wind Pressure, pner3o (psf) (Step 4) by the adjustment factor for height and exposure, A (Step 7),the Topographic Factor, Kzt (Step 5), and the Importance Factor, I (Step 8) using the following equation: pnet (PSD = AKztl pner3o x pnet (psj) = Design Wind Load (10 psf minimum) A = adjustrnentfactorfor height and exposure category (Step 7) Kzt = Topographic Factor at mean roof height,h (ft) (Step 5) I = Importance Factor (Step 8) pner3o (psf) = net design wind pressure forExposure B, at height = 30, I = 1 (Step 4) Use Table 5 below to calculate Design Wind Load. The Design Wind Load will be used in Part II to select the appropriate SolarMount Series rail, rail span and foot spacing. Source: ASCEISF7 7-05, Minimum Design Loods for Buildings and Other Structures, Chapter 6, Figure 6-3, p. 44. Table 5.Worksheet for Components and Cladding Wind Load Calculation: IBC 2006,ASCE 7-05 Yanoble 0<snpvon Symbol Value Una Sap Re(ana Building, Least Horizontal Dimension it RoafPteh, ....m Exposure Category. 6 Effective Wind Area 2 Roof Zone Roof Zone Location ~'jaF,s,1e-3... - c 3 Figure 2 Importance Factor Z x 8 Table 5 r.d,. lv~ 8 SolarMount Unirac Code-Compliant Installation Manual p0 UNIRAC Table 6. Occupancy Category Importance Factor Nom4urtlc Pmne Regions and Humcwe Pmne Regions a, a Prone amgory attgorypesrcnption uWingType Esanpla wuh n Speed,V= 85.100 100 m ph and Alaska M g.spe iiW Basic Wh i 5ped,V>IOOmph I Buildings and other Agricultural facilities 0.87 0.77 structures that Certain Temporary facilities represent a low Minor Storage facilities hazard to human life in the event of failure, including, but limited to: All buildings and other II structures except those I I listed in Occupancy Categories 1, III, and IV Buildings and other Buildings where more than 300 people congregate structures that Schools with a capacity more than 250 1.15 1.15 III represent a substantial Day Cares with a capacity more than ISO hazard to human life in Buildings for colleges with a capacity more than 500 the event of a failure, Health Care facilities with a capacity more than 50 or more including, but not limited resident patients to: Jails and Detention Facilities Power Generating Stations Water and Sewage Treatment Facilities Telecommunication Centers Buildings that manufacture or house hazardous materials Buildings and other Hospitals and other health care facilities having surgery or 1.15 1.15 structures designated emergency treatment IV as essential facilities, Fire, rescue, ambulance and police stations including, but not limited Designated earthquake, hurricane, or other emergency to: shelters Designated emergency preparedness communication, and operation centers Power generating stations and other public utility facilities required in an emergency Ancillary structures required for operation of Occupancy Category IV structures Aviation control "towers, air traffic control centers, and emergency aircraft hangars Water storage facilities and pump structures required to maintain water pressure for fire suppression Buildings and other structures having critical national defense functions Source: IBC 2006, Table 1604.5, Occupancy Category of Buildings and other structures, p. 281; ASCEISEI 7-05, Minimum Design Loads for Buildings and Other Structures,Table 6-1, p.77 9 :!UN 0 RAC Unirac Code-Compliant Installation Manual SolarMount Part H. Procedure to Select Rail Span and Rail Type [2.1.] Using Standard Beam Calculations, Structural Engineering Methodology The procedure to determine the Unirac SolarMount series rail type and rail span uses standard beam calculations and structural engineering methodology. The beam calculations are based on a simply supported beam conservatively, ignoring the reductions allowed for supports of continuous beams over multiple supports. Please refer to Part I for more information on beam calculations, equations and assumptions. In using this document, obtaining correct results is dependent upon the following: 1. Obtain the Snow Load for your area from your local building official. Step 1: Determine the Total Design Load The Total Design Load, P (psf) is determined using ASCE 7-05 2.4.1 (ASD Method equations 3,5,6 and 7) by adding the Snow Loads, S (psf), Design Wind Load, poet (psf) from Part I, Step 9 and the Dead Load (psf). Both Uplift and Downforce Wind Loads calculated in Step 9 of Part 1 must be investigated. Use Table 7 to calculate the Total Design Load for the load cases. Use the maximum absolute value of the three downforce cases and the uplift case for sizing the rail. Use the uplift case only for sizing lag bolts pull out capacities (Part II, Step 6). 2. Obtain the Design Wind Load, pnet. See Part I (Procedure to Determine the Design Wind Load) for more information on calculating the Design Wind Load. 3. Please Note: The terms rail span and footing spacing are interchangeable in this document. See Figure 3 for illustrations. 4. To use Table 8 and Table 9 the Dead Load for your specific installation must be less than 5 psf, including modules and Unirac racking systems. If the Dead Load is greater than 5 psf, see your Unirac distributor, a local structural engineer or contact Unirac. The following procedure will guide you in selecting a Unirac rail for a flush mount installation. It will also help determine the design loading imposed by the Unirac PV Mounting Assembly that the building structure must be capable of supporting. Figure 3. Rail span and footing spacing are interchangeable. Rai/y Pan 0, otspa'. 10 P (ps,f) = LOD + LOSt (downforce case 1) P (psf) = LOD + 1.0pnet (downforce case 2) P (psf) = LOD + 0.75Sr + 0.75paet (downforce case 3) P (psf) = 0.61) + 1.Opnet (uplift) D = Dead Load (psf) S = Snow Load (psf) prier = Design Wind Load (psf) (Positive for downforce, negative for uplift) The maximum Dead Load, D (psf], is 5 psf based on market research and internal data. I Snow Load Reduction - The snow load can be reduced according to Chapter 7ofASCE 7-05. The reduction is a function of the roof slope, Exposure Factor, Importance Factor and Thermal Factor. Please refer to Chapter? of AS(E 7-05 for more information. '0oa6\ecS'pN peR o `as\s c Note: Modules must be centered symmetrically on the rails 2*), as shown in Figure 3. If this is not the case, tail Unirac for assistance. - SolarMount Unirac Code-Compliant Installation Manual ;;•UNIRAC Table 7. ASCE 7ASD Load Combinations Desorytion Yori bl _[y 1 -t ''-ay- units Dead Load D 1 Q ~ ` x. 1 Q X ~ ° I sf p Snow Load 5 a f:r FOx+- p7g t" sf Design Wind Load Poor -_~J~~S-° ~-2v. f s Total Design Load P a . = E p te , ; p Note: Table to be filled out or attached for evaluation Step 2: Determine the Distributed Load on the rail, w (pit) Determine the Distributed Load, w (PIA by multiplying the module length, B (ft), by the Total Design Load, P (psf) and dividing by two. Use the maximum absolute value of the three downforce cases and the Uplift Case. We assume each module is supported by two rails. w = PB/2 w = Distributed Load (pounds per linear foot, plf) B = Module Length Perpendicular to Rails (ft) P = Total Design Pressure (pounds per square foot psf) Table 8. L-Foot SolarMount Series Rail Span SM - S.IarMount HD- SolarMount Heavy Duty Step 3: Determine Rail Span/L-Foot Spacing Using the distributed load, w, from Part H, Step 2, look up the allowable spans, L, for each Unime rail type, SolarMount (SM) and SolarMount Heavy Duty (HD). There are two tables, L-Foot SolarMount Series Rail Span Table and Double L-Foot SolarMount Series Rail Span Table. The L-Foot SolarMount Series Rail Span Table uses a single L-foot connection to the roof, wall or stand-off. The point load connection from the rail to the L-Foot can be increased by using a double L-foot in the installation. Please refer to the Part III for more installation information. 2 2.5 3 3.5 4 4.5 5 S.5 6 6.5 7 7.5 8 8.5 9 9.5 10 10.5 11.5 12 12.5 13 13.5 14 14.5 IS 15.5 16 17 11 sWIUNIRAC UniracCode-ComplianttnstallationManual SolarMount Table 9. Double L-Foot Solar-Mount Series Rail Span SM - SolarMount HD- SolarMuunt Heavy Duty. Span w=OWbvrtd L.adf 1 0 20 25 30 40 50 60 80 100 120 140 160 180 200 220 240 260 280 300 2 2.5 Ei 3 3.5 t" Sfsr' .314:' ,~3♦`J' Pte: °_E- z"Ii.`~.LSi~- `."b` - 4 45 55 E9-°ceS're"h.FSM 6.5 75 sct'~m SM A~"SHs~-- .3 8.5 9 9.5 nSl*3V_`°_=y?SL'~"* =tl ,gym 10 10.5 it ''~_T''=SPIT: 11.5 12 12.5 13 13.5 14 14.5 IS 15.5 16 17 Step 4: Select Rail Type Selecting a span and rail type affects the price of your installation. Longer spans produce fewer wall or roof penetrations. However, longer spans create higher point load forces on the building structure. A point load force is the amount of force transferred to the building structure at each connection. It is the installer's respon ibility to verify that the building structure is strong enou hg to support the point load forces. Step 5: Determine the Downforce Point Load, R (lbs), at each connection based on rail span When designing the Unnac Flush Mount Installation, you must consider the downforce Point Load, R (lbs) on the roof structure. The Downforce, Point Load, R (lbs), is determined by multiplying the Total Design Load, P (psf) (Step 1) by the Rail Span, L (ft) (Step 3) and the Module Length Perpendicular to the Rails, B (ft) divided by two. R (ibs) = PLB12 12 R = Point Load (7bs) P = Total Design Load (psD L = Rail Span (ft) B = Module Length Perpendicular to Rails (ft) It is the installer's responsibility to verify that the building structure is strong enough to support the maximum point loads calculated according to Step 5. SolarMount Unirac Code-Compliantlnstallation Manual U N I RAC Table 10. Downforce Point Load Calculation Total Design Load (downforce) (max of case I, 2 or 3) P Module length perpendicular to rails B x Rail Span L x Downforce Point Load R psf ft ft 12 Ibs Step I Step 4 Step 6: Detertnine the Uplift Point Load, R (Ibs), at each connection based on rail span You must also consider the Uplift Point Load, R (lbs), to determine the required lag bolt attachment to the roof (building) structure. - Table 11. Uplift Point Load Calculation Total Design Load (uplift) P psf Step I Module length perpendicular to rails B x ft Rail Span L x it Step 4 12 Uplift Point Load R Ibs Table 12. Lag pull-out (withdrawal) capacities (Ibs) in typical roof lumber (ASD) Use Table 12 to select a lag bolt size and embedment depth to Lag screw spedficotions satisfy your Uplift Point Load s Force, R (lbs), requirements. Specific /c° shaft- gravity per inch thread depth It is the installer's responsibility Douglas Fir, Larch 0.50 266 to verify that the substructure and attachment method is strong Douglas Fir, South 0.46 235 enough to support the maximum Engelmann Spruce, Lodgepole Pine point loads calculated according to (MSR 1650 f & higher) 0.46 235 Step 5 and Step 6. Hem, Fir, Redwood (close grain) 0.43 212 Hem, Fir (North) 0.46 235 Thread Southern Pine 0.55 307 depth Spruce, Pine, Fir 0.42 - 205 Spruce, Pine, Fir (E of 2 million psi and higher - grades of MSR and MEL) 0.50 266 Sources:American Wood Council, NDS 2005,7able 11.2A, 11.32A. Notes: (1) Thread must be embedded in the side grain of a rafter or other structural member integral with the building structure. (2) Lag bolts must be located in the middle third of the swauml member. (3) These values are not valid for wet service. (4) This table does not include shear capacities. If necessary, contact a local engineer to specify lag bolt size with regard to shear forces. (5) Install log bobs with head and washer flush to surface (no gap). Do not over-torque (6) Withdrawal design values for log screw connections shall be multiplied by applicable adjustment factors if necessary. See Table 10.3.1 in the American Wood Council NDS for Wood Construction. *Use flat washers with lag screws. 13 U N RAC Unirac Code-Compliant Installation Manual SolarMotmt Part III. Installing SolarMount The Unirac Code-Compliant Installation Instructions support applications for building permits for photovoltaic arrays using Unirac PV module mounting systems. This manual, SolarMount Planning and Assembly, governs installations using the SolarMount and SolarMount HD (Heavy Duty) systems. ® Rail - Supports PV modules. Use two per row of modules. 6105-T5 aluminum extrusion, anodized. ® Rail splice - Joins and aligns rail sections into single length of rail. It can form either a rigid or thermal expansion joint, 8 inches long, predrilled. 6105-T5 aluminum extrusion, anodized. ® Self-drilling screw- (No. 10 x 3/a") - Use 4 per rigid.. splice or 2 per expansion joint. Galvanized steel. 0 L-foot - Use to secure rails. either through roofing material to building structure or standoffs. Refer to loading tables for spacing. Note: Please contact Unirac for use and specification of double L-foot. ® L-foot bolt (3/8" x 3/a") - Use one per L-foot to secure rail to L-foot. 18-8A2 stainless steel. O Flange nut (3/8 - Use one per L-foot to secure rail to L-foot. 18-8A2 stainless steel. ® Flattop standoff (optional) (3/8 - Use standoffs to increase the height of the array above the surface of the roof or to allow for the use of flashings. Use one per L-foot. One piece: Service Condition 4 (very severe) zinc-plated-welded steel. Includes 3/8"x 1/4" bolt with Figure 4. SolarMountstandard rail components. lock washer for attaching L-foot. Flashings: Use one per standoff. Unirac offers appropriate flashings for both standoff types. Note:'There is also a flange type standoff that does not require an L-foot. O Aluminum two-peice standoff (optional) (4" and 7") - Use one per L-foot. Two-piece: 6105-T5 aluminum extrusion. Includes 3B" x /4" serrated flange bolt with EPDM washer for attaching L-foot, and two /16" lag bolts. O Lag screw for L-foot (5/16") - Attaches standoff to rafter. 0 Top Mounting Clamps ® Top Mounting Grounding Clips and Lugs Installer supplied materials: • Lag screw for L-foot-Attaches L-foot or standoff to rafter. Determine the length and diameter based on pull- out values. If lag screw head is exposed to elements, use stainless steel. Under flashings, zinc plated hardware is adequate. Waterproof roofing sealant- Use a sealant appropriate to your roofing material. Consult with the company currently providing warranty of roofing. 14 [3.1.] SolarMount® rail components SolarMount Unirac Code-Compliant Installation Manual U N I RAC [3.2.] Installing SolarMount with top mounting clamps This section covers SolarMount rack assembly where the installer has elected to use top mounting clamps to secure modules to the rails. It details the procedure for flush mounting SolarMount systems to a pitched roof. Figure 5. Exploded view of a flushmount installation mounted with L feet. Table 14. Clamp kit part quantities End Mid module '/."x %s" flange Modules clamps clamps clamp bolts safety bolts nuts 2 4 2 6 2 8 3 4 4 a 2 10 4 4 6 10 2 12 5 4 8 12 2 14 6 4 10 14 2 16 7 4 12 16 2 18 8- 4 14 18 2 20 Table 15.Wrenches and torque Wrench Recommended size torque (ft-Ibs) hardware 5 - 10 g ''/s" hardware A Ail top down clamps must be installed with anti- j(\ seize to preventgalling and provide uniformity I -L-1 i in clamp load. UniRac Inc recommends Silver Grade LocTite Anti-Seize Item numbers: 38181, 80209,76732,76759,76764, 80206, and 76775, or equivalent. 114"- 20 hardware used in conjunction with top down clamps must be installed to 5 - 10 ft-Ibs of torque. When using UGC-1, UGC-2, WEEB 9.5 and WEEB 6.7,114" - 20 hardware must be installed to 10 ft-lbs or torque. Additionally, when used with a top down clamp, the moduleframe cross section must be boxed shaped as opposed to a single, I-shaped member. Please refer to installation supplement 910: Galling and Its Prevention for more information on galling and anti-seize and installation manual 225. Top Mounting Unit" Grounding Clips and WEEBLugs for more information on Grounding Clips." Torques are not designated for use with wood connectors 15 :e'UNIRAC UniracCode-CompliantInstallationManual SolarMount [3.2.1] Planning your SolarMount® installations The installation can be laid out with rails parallel to the rafters or perpendicular to the rafters. Note that SolarMount rails make excellent straight edges for doing layouts. Center the installation area over the structural members as much as possible. Leave enough room to safely move around the array during installation. Some building codes require minimum clearances around such installations, and the user should be directed to also check `The Code'. The width of the installation area equals the length of one module. The length of the installation area is equal to: • the total width of the modules, • plus 1 inch for each space between modules (for mid- clamp), • plus 3 inches (11/2 inches for each pair of end clamps). Peak v w Low-profile High-profile mode mode Gutter Figure 6. Rails may be placed parallel or perpendicular to rafters. 16 SolarMount Unirac Code-Compliant Installation Manual p•.FUNIIA[ ~<--Overhang 25%L max 25% of module Foot spacing/---i width a~ f i i ' 5W. of module 1 / width (TYP) N M l Rafters ote: odu es mustbe Lower roof edge centered symmetrically on the (Building Structure) rails 2•). If this is not the case, call Unirac for assistance. Figure S. Layoutwith rails perpendicular to rafters. Installing L-feet Drill pilot holes through the roof into the center of the rafter at each L-foot lag screw hole location. Squirt sealant into the hole, and on the shafts of the lag screws. Seal the underside of the L- feet with a suitable sealant. Consult with the company providing the roofing warranty. Securely fasten the L-feet to the roof with the lag screws. Ensure that the L-feet face as shown in Figure 8 and 9. For greater ventila- tion, the preferred method is to place the single-slotted square side of the L-foot against the roof with the double-slotted side perpen- dicular to the roof. If the installer chooses to mount the L-foot with the long leg against the roof, the bolt slot closest to the bend must be used. 25% of module width 50% of module width I 1 I 5`t ti 1 "'f } Fdotspach / ( I Span, L Lower roof edge Overhang 25%L max Rafters (Building Structure) 2-1 Note: Modal. onatbe centered symmetrically on the rails (+/-2*). If this is not the case, call Unirac for assistance. P1gWV Y. LayoatWuh rails parallel to rafters. Page 17 ::°UNIRAC Unirac Code-Compliant Installation Manual SolarMount [3.2.3] Laying out standoffs Standoffs (Figure 10) are used to increase the height of the array above the surface of the roof. Pair each standoff with a flashing to seal the lag bolt penetrations to the roof. Use Figure 11 or 12 to locate and mark the location of the standoff lag screw holes within the installation area. Remove the the or shake underneath each standoff location, exposing the roofing underlayment. Ensure that the standoff base lies flat on the underlayment, but remove no more mate- rial than required for the flashings to be installed properly. The standoffs must be firmly attached to the building structure. Overhang 257 L max Foot spacing/ 25% module width Rail Span L each end PI \ PIT, 137 6 1 .....E td e k . 1 F 0% module width (TYP) 71 Lower of edge y~`--- Rafters (Building Structure) Note: Modules must be centeredsymmetrically on the rails (+1-2*). If this is nctthe case, call Unirac forassismoc. Figurell. Layout with railsperpendicular to rafters.perpendicular to rafters. Overhang 25% of S0%6 typical d l i mo u e w dth (TYP) 7116 Ali F7 e - t ( 1 Cl _ t E_T 1 r far#Pa 3 t Fo spacing/ -*^---7116" „ " ' \ 1' L Span E Lower roof edge 11 Overhang 25%L,max 1 i ~ e Rafters (Building Structure) Note: Modules rn stbe centeredsymmen'iw11yan th, rails (+/-29. If Otis is not the case, call Unirac for assistance. Figure 12. Layout with rails parallel to rafters. If multiple high-profile rows are to be installed adjacent to each other, it may not be possible for each row to be centered above the rafters. Adjust as needed, following the guidelines of Fig. 12 as closely as possible. Installing standoffs Drill 3/16 inch pilot holes through the underlayment into the center of the rafters at each standoff location. Securely fasten each standoff to the rafters with the two 5/16" lag screws. Enure that the standoffs face as shown in Figure 11 or 12. Unirac steel standoffs (15/8 "O.D.) are designed for collared flashings available from Unirac. Aluminum two-piece standoffs (11/8"O.D.) take all-metal flashings, also available from Unirac. Install and seal fleshings and standoffs using standard building practices or as the company providing roofing warranty directs. 18 SolarMount Unirac Code-Compliant Installation Manual :P U N I RAC [3.2.4] Installing SolarMount rails Keep rail slots free of roofing grit or other debris. Foreign matter will cause bolts to bind as they slide in the slots. Installing Splices. If your installation uses SolarMount splice bars, attach the rails together (Fig. 13) before mounting the rails to the footings. Use splice bars only with flush installations or those that use low-profile tilt legs. Although structural, the joint is not as strong as the rail itself. A rail should always be supported by more than one footing on both sides of the splice. (Reference installation manual 908, Splices/Expansion Joints.) If using more than one splice per rail, contact Unirac concerning thermal expansion issues. Mounting Rails on Footings. Rails may be attached to either of two mounting holes in the L-feet (Fig. 14). Mount in the lower hole for a low profile, more aesthetically pleasing installation. Mount in the upper hole for a higher profile, which will maximize airflow under the modules. This will cool them more and may enhance performance in hotter climates. Slide the''%-inch mounting bolts into the footing bolt slots. Loosely attach the rails to the footings with the flange nuts. Ensure that the rails are oriented to the footings as shown in Figure 8, 9, 11, or 12, whichever is appropriate. Aligning the Rail Ends. Align one pair of rail ends to the edge of the installation area (Fig. 15 or Fig. 16). The opposite pair of rail ends will overhang the side of the installation area. Do not trim them off until the installation is complete. If the rails are perpendicular to the rafters (Fig. 15), either end of the rails can be aligned, but the first module must be installed at the aligned end. If the rails are parallel to the rafters (Fig. 16), the aligned end of the rails must face the lower edge of the roof. Securely tighten all hardware after alignment is complete (20. it lbs). Mount modules to the rails as soon as possible. Large temperature changes may bow the rails within a Jew hours if module placement is delayed. Edge of installation area --n Figure 15. Rails perpendicular to the rafters. Clamping bolt slot Mounting slots Footing bolt slot Figure 14. Foot-to-rail splice attachment u 3 I Nil dl e ~ P I a t~ P Edge of installation area Figure 16. Rails parallel to the rafters. rte. 19 U N I RAC Unirac Code-Compliant lnstailation Manual SolarMount [3.2.5] Installing the modules Pre-wiring Modules. If modules are the Plug and Play type, no pre-wiring is required, and you can proceed directly to "Installing the First Module" below. If modules have standard J-boxes, each module should be pre-wired with one end of the intermodule cable for ease of installation. For safety reasons, module pre-wiring should not be performed on the roof. Leave covers off J-boxes. They will be installed when the modules are installed on the rails. Installing the First Module. In high-profile installations, the safety bolt and flange nut must be fastened to the module bolt slot at the aligned (lower) end of each rail. It will prevent the lower end clamps and clamping bolts from sliding out of the rail slot during installation. If there is a return cable to the inverter, connect it to the first module. Close the J-box cover. Secure the first module with T-bolts and end clamps at the aligned end of each rail. Allow half an inch between the rail ends and the end clamps (Fig.18). Finger tighten flange nuts, center and align the module as needed, and securely tighten the flange nuts (5-10 ft lbs). to '✓'1 I It i-boxes Figure 17 Installing the Other Modules. Lay the second module face down (glass to glass) on the first module. Connect intermodule cable to the second module and close the J-box cover. Turn the second module face up (Fig. 17). With T-bolts, mid-clamps and flange nuts, secure the adjacent sides of the first and second modules. Align the second module and securely tighten the flange nuts (Fig. 19). For a neat installation, fasten wire management devices to, rails with self-drilling screws. Repeat the procedure until all modules are installed. Attach the outside edge of the last module to the rail with end clamps. Trim off any excess rail, being careful not to cut into the roof. Allow half an inch between the end clamp and the end of the rail (Fig. 18). Check that all flange nuts on T-bolts are torqued to 5-10 it Ibs Figure 18 Figure 19 High-lipped module (cross section) Spacer" Low-lipped module Figure 20. Mid clamps and end clamps for lipped-frame modules are identical. A spacer for the end clamps is necessary only if the lips are located high on the module frame. 20 ~e SolarMount Unirac Code-Compliant Installation Manual U N IRAC [3.3] Installing SolarMount with bottom mounting clips This section covers SolarMount rack assembly where the installer has elected to use bottom mounting clamps to secure modules to the rails. It details the procedure for flush mounting SolarMount systems to a pitched roof. I soloo.:wr7 rats Fo,olsig oclr Sol MOVIAng -,.6p Table 16. Wrenches and torque Wrench Recommended size torque (ft-lbs) '/s" hardware $ ''/a' hardware 20 Note:Torque specfcations do not apply to lag halt connections. Stainless steel hardware can seize up, aprocess called galling. To significantly reduce its ' likelihood, (1) apply lubricant to bolts, preferably an anti-seize lubricant, available at autoparts stores, (2) shade hardware prior to instailatiory and (3) avoid spinning on nuts at high speed. See Installation Supplement 910, Galling and Its Prevention, at www.unirac.com. 21 n UNIRAC UniracCode-Compliant Installation Manual SolarMount [3.3.1] Planning the installation area Decide on an arrangement for clips, rails, and L-feet (Fig. 22) Use ArrangementA if the full width of the rails contacts the module. Otherwise use Arrangement B. Caution: If you choose Arrangement B, either (1) use the upper mounting holes of the L -feet or (2) be certain that the L -feet and clip positions don't conflict. If rails must be parallel to the rafters, it is unlikely that they can be spaced to match rafters. In that case, add structural supports - either sleepers over the roof or mounting blocks beneath it These additional members must meet code; if in doubt, consult a professional engineer. Never secure the footings to the roof decking alone. Such an arrangement will not meet code and leaves the installation and the roof itself vulnerable to severe damage from wind. Leave enough room to safely move around the array during installation. The width of a rail-module assembly equals the length of one module. Note that L-feet may extend beyond the width of the assembly by as much as 2 inches on each side. The length of the assembly equals the total width of the modules. Distance between - lag bolt. centers. 2" Distance between --.-i idule mounting holes t PV module i addle bolt clip bolt L-fact Distance between log €14' -Distance between module mounting hot a' LB] Figure 22. Clip Arrangements A and B 22 d" U N I RAC Unirac Code-Compliant Installation Manual SolarMount [3.3.3] Attaching modules to the rails Lay the modules for a given panel face down on a surface that will not damage the module glass. Align the edges of the modules and snug them together (Fig. 21, page22). Trim the rails to the total width of the modules to be mounted. Place a rail adjacent to the outer mounting holes. Orient the footing bolt slot outward. Place a clip slot adjacent to the mounting holes, following the arrangement you selected earlier. Assemble the clips, mounting bolts, and flange nuts. Torque the flange nuts to 5 foot-pounds. Wire the modules as needed. For safety reasons, module wiring should not be performed on a roof. For a neat installation, fasten cable clamps to rails with self-tapping screws. [3.3.4] Installing the module-rail assembly Bring the module-rail assembly to the installation site. Keep rail slots free of debris that might cause bolts to bind in the slots. Consider the weight of a fully assembled panel. Unirac recom- mends safety lines whenever lifting one to a roof. Align the panel with the previously installed L-feet. Slide 3/8 inch L-foot mounting bolts onto the rail and align them with the L-feet mounting holes. Attach the panel to the L-feet and finger tighten the flange nuts. Rails may be attached to either of two mounting holes in the footings (Fig. 25). • Mount in the lower hole for a low, more aethetically pleasing installation. • Or mount in the upper hole to maximize a cooling airflow under the modules. This may enhance perfor- mance in hotter climates. Adjust the position of the panel as needed to fit the installa- tion area. Slide the remaining L-feet bolts onto the other rail, attach L-Feet, and finger tighten with flange nuts. Align L-feet with mounting holes previously drilled into the roof. Install lag bolts into remaining L-feet as described in "Laying out and installing L-feet" above. Torque all footing flange nuts to 20 foot-pounds. Verify that all lag bolts are securely fastened. 24 Figure 25. Leg-to-rail attachment SolarMount Unirac Code-Compliant Installation Manual U N I RAC [3.3.2] Laying out the installing L-feet L-feet are used for installation through existing low profile roofing material, such as asphalt shingles or sheet metal. They are also used for most ground mount installations. To ensure that the L-feet will be easily accessible during flush installation: • Use the PV module mounting holes nearest the ends of the modules. • Situate the rails so that footing bolt slots face outward. The single slotted square side of the L-foot must always lie against the roof with the double-slotted side perpendicular to the roof. Foot spacing (along the same rail) and rail overhang depend on design wind loads. Install half the L-feet: • If rails are perpendicular to rafters Il fi I ! Install Second Sal rMouht Rails n H i If n ) u Install First " _J L if , H ii Ledger } roof edge}f Rafter Rafters (Fig. 23), install the feet closest to Figure 23. Layout with mils perpendicular to rafters. the lower edge of the roof. • If rails are parallel to rafters (Fig 24), install the feet for one of the rails, but not both. For the L-feet being installed now, drill pilot holes through the roofing into the center of the rafter at each lag screw hole location. Squirt sealant into the hole and onto the shafts of the lag screws. Seal the underside of the L-feet with a sealant. Securely fasten the L-feet to the building structure with the lag screws. Ensure that the L-feet face as shown in Figure 23 or Figure 24. - Hold the rest of the L-feet and fasteners aside until the panels are ready for the installation. 23 SolarMount Unirac Code-Compliant Installation Manual p: U N I RAC [3.4] Installing SolarMount with grounding clips and lugs Clips and lu, are sold separately. Figure 28. Place grounding clips, lugs, and copper wire (6 -10 AWG). Place a loop in the wire around splices to prevent tension. Be sure wiring between rails is not taut. KEY ❑ PV module O SolarMount rail (any type) Rail splice x Grounding lug Grounding clip - Copper wire 3 I EE II ' Sinale aroundina Alt wire for entire array _ ern for in-li 25 O UNIRAC Unirac Code-Compliant Installation Manual SolarMount 10 year limited Product Warranty, 5 year limited Finish Warranty Unirac, Inc., warrants to the original purchaser ("Purchaser") of product(s) that it manufactures ("Produce) at the original installation site that the Product shall be free from defects in material and workmanship for a period of ten (10) years, except for the anodized finish, which finish shall be free from visible peeling, or cracking or chalking under normal atmospheric conditions for a period of five (5) years.from the earlier of 1) the date the installation of the Product is completed, or 2) 30 days after the purchase of the Product by the original Purchaser ("Finish Warranty"). The Finish Warranty does not apply to any foreign residue deposited on the finish. All installations in corrosive atmospheric conditions are excluded. The Finish Warranty isVOID if the practices specified byAAMA 609 & 610-02-"Clearing and Maintenance for Architecturally Finished Aluminum' (www.aamanet.org) are not followed by Purchaser.This Warranty does not cover damage to the Product that occurs during its shipment, storage, or installation. This Warranty shall be VOID if installation of the Product is not performed in accordance with Unirac's written installation instructions, or if the Product has been modified, repaired, or reworked in a manner not previously authorized by Unirac IN WRITING, or if the Product is installed in an environment for which it was not designed. Unirac shall not be liable for consequential, contingent or incidental damages arising out of the use of the Product by Purchaser under any circumstances. If within the specified Warranty periods the Product shall be reasonably proven to be defective, then Unirac shall repair or replace the defective Product or any part thereof, in Unirac's sole discretion. Such repair or replacement shall completely satisfy and discharge all of Unirac's liability with respect to this limited Warranty. Under no circumstances shall Unirac be liable for special, indirect or consequential damages arising out of or related to use by Purchaser of the Product Manufacturers of related items, such as PV modules and fiashings, may provide written warranties of their own. Unirac's limited Warranty covers only its Product and not any related items. n' I 1411 Broadway Boulevard NE ® Albuquerque NM 87102-1545 USA ' V 26 DENVER ALTERNATIVE ENERGY PV SYSTEM LINE DIAGRAM (XCEL) Prepared by Ric Nepomuceno, DenverAlternative Energy, LLC Rebate Application #:11721 Name: Ray and Nikki Ragonese Address: 30321ngauCt. 1„0(; -ply Co City/State/Zip: Berra CO. 80214 Phone: 720-732-9008 Email nikbovilcomcastnet Xcet#: 53-2394335-9 Premise#: 300898500 System Size: 8060w # of Modules: 14 # of Strings 2 Panet Information A.erisolar AS-6.30 240. 2A .3V 2A 0w Length AV 4- V39.4- 0" 4 Wo. Calculations PV Side Ampacity per string Isc REM NEC conductor short circuit adj, x1.56 PV Source Current Max 13.29A Max PV system voltage vs. Max rated DC inverter input voltage: PV .,to. VOC 259.7 Temp correction factor for-23 x 1.23 to -31 deg. F Max PV system voltage 319V Max rated DC inverter input 450 V voltage 500 V-318V 131V PV Conductor Ampacity Req. AmpacityTotal 13,29A #tOAWGTHWN-2 40A 140 deg. F Decate Factor x0.71 Wire Capacity Available 28.4A Equipment Grounding Conductor PV parallel string combine,/ 15A DC disco/AC disco OCPD Min. AWG for Equip. Ground #14AWG M 15A OCPD Grounding Conductor Size #10AWG used in system Max Wolfe, 3000/ Min.ottage 211 14.22A Cantata Factor x1.25 Inverter Output Conductor 17..A Ampacity Minimum 2 Strings #Panels/string 7 Vmp 212AV VOC 259.7 Imp 7.92A Ins 8.52A Distances= 8 ft. Distances = 9 ft. DC Current Max 13A 1 4410 USE-2 PV Wire 2 AA 1-#10 AWG Bare CU Ground Combiner Be. Source Combiner Ratings Max OCPD Rating =15 A OCPDAmp Rating = 15 A OCPD Vail Rating = 600 V DC Current Max 13A 4-#10AWOTHWN-2 28.4A DC Disconnect 1-#10 Bare CU Ground 600. JA 314"EMT or Equivalent Inverterintegrated Inverter PV Powered 3000 PV MIN WATTS 0 PV MAX WATTS 3000 PV USABLE VOLTAGE MIN 180 PV USABLE VOLTAGE MAX 450 PV VOLTAGE MAX 500 PVMAXCURRENT 26 MAX AC POWER WATTS 3120 MAXAC CURRENT at 240V 13 M IN AC VOLTAGE RANGE 211 MAXEFFICIENCY% 93.5 INTEGRATED DC DISCONNECT YES MAX AC OVERCURRENT PROTECTION 30A YEARS WARRANTY 10 WIDTH (IN) 16.6 HEIGHT (IN) 30.4 DEPTH IIN) 8.25 WEIGHTILBSI 80 UL1741APPROVED YES Distances= 2ft. Distances = 2 ft. Ground AC Disconnect Easily Accesible, lockable, In clear view of meter. Labeled- "Photovoltaic System Disconnect" DISCOAMPRATING 32A DISCOVOLTRATING 600V i~ 2Conductors #10 AWG THWN INeutral #to AWGTHWN Ground #IOAWG THWN Conduit 3/4"EMT or Equivalent Service Panel 600V 200A Max Breaker: 200 A ` Backfed Breaker: 25 A Bus Amp Rating: 200 A Service Voltage: 600 V UTILITY METER .J ♦ i CITY OF WHEAT RIDGE r Building Inspection Division 1 (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPEC~NOTICE Inspection Type: Job Address: Permit Number: 6~1~G~7 U ❑ No one available for inspection: Time 6Z'1 t A Re-Inspection required: Yes No When corrections have been made, call for re-inspection at 303-2345933 Date: cl # L Inspector: NI-1 DO NOT REMOVE THIS N~TICE 41 City of Wheat Ridge ► Residential Roofing PERMIT - 093887 r40oor- PERMIT NO: 093887.' ISSUED:'. 11/05/2009 JOB ADDRESS: 3032 INGALLS CT EXPIRES: 05/04/2010 DESCRIPTION: Reroof 30 sqs **s CONTACTS owner 303/232-6002 NikiRagenese sub 970/669-6999 Anthony Ostblom 09-0451 A.J,. Shirk Roofing.. LLC PARCEL INFO ZONE CODE: UA USE: UA" SUBDIVISION:..... 0503. -BLOCK/LOT#.: 0/ FEE SUMMARY ESTIMATED PROJECT VALUATION: 9,225.00 FEES Permit Fee 235.70ty Total Valuation .00 L Use Tax, 166.05 TOTAL 401.75 . Conditions: 6 nail .installation mid-roof inspection required.. Board sheathing spaced more than al/2: of an inch apart... requires plywood overlay on entire roof. Ice and water shield required from eave edge to 2' inside exterior walls. ***Contractor/Propertyowner shall provide -ladder,,(s)secured in place for inpsections..; ' - Subject to field inspection. I hereby certify .that . the. setback distances. proposed by. this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat: Ridge or covenants, easements or restrictions of record; that all measuremen s own; and allegations. made are accurate; that I have read and agree to abide by all conditions printed on this applicat' d'that I assume full responsibility for compliance' with the Wheat Ridge Building Code (I.B.C) and. all other appli eat Ridge Ordinances, for work under this permit. Plans subject to field inspection. ture of contractor/owner date 1. This permit was issued in accordance with the provisions set forth in your application and is subject to the. laws of the. State of Colorado and to the Zoning Regulations and Building Codes of Wheat Ridge, Colorado or any other applicable ordinances. of the City. 2.. This permit shall expire 180 days from the issue date. Requests for an extension must be received prior to expiration date. An extension may be granted at the discretion of the Building Official. 3. If this permit expires, a new permit may be acquired for a. fee. of one-half the amount normally. required, provided no J. changes have been or will be made in the original plans. and specifications and any suspension or abandonment has not exceeded one (1) year. If changes have been or if suspension or..abandonment exceeds one.(1). year, full fees shall be paid for a new permit. - 4. No work of any manner shall be done that will change the natural flow of. water causing a drainage problem. 5. Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection bard before proceeding with successive phases of the job. - 6. The issuance of a permit or the approval of drawings and specifications shall not be construed to be a permit for, nor' an approval of, any violation of the provisions of the building codes or any other ordinance,. law, rule or regulation. All plan review is subject to field inspections. - SignaturWSMUST Building Official date INSPEC N EQUESTLINE: (303)234-5933 BUILDING OFFICE: (303)235-2855 BE MADE BY 3PM ANY BUSINESS DAY FOR INSPECTION THE. FOLLOWING BUSINESS DAY. Nov 05 09 05:52p P.1 City of Wheat Ridge Building Division Date: 7500 W. 29th Ave_, Wheat Ridge, CO 80033 Office: 303-235-2855' Fax. 303-235-2857 Plan#: o Inspection Line: 303-2345933 Aermn 0 lO T s wD J- ~toBno Building Permit Application Property Address: 3 D..3 C / Property Owner (please pano: A/ , k,' lPn C 7°✓1 ti° S e Phone:. 3a 3 - a3a - ~Oa Mailing Address: (ifdi(feient than prapeftyaddress) Address: City, State, Zip: Contractor. ~/l rr /c Roo-Fiii L.C Contractor License Phone: Q70 - ~o loq- 1? 9 9 Sub Contractors: Electrical City License Plumbing City License Mechanical City License Company: Company Company: Exp. Date. Exp, Date: Approval: Exp. Date: Approval: Approval: Use of space (description): Construction Value: ; 9 a a 5 Description of work: Revnoij-e ehLSf'Iny ShrnflP.s (asCalwlatedpe d8-EWRdwgyabwawnDafasheet) oh'e io"1pn y hsA-u (-l 3 (D sq9 (4are 111~ Plan Review (dueat time oisubmMalJ: $ OW~hs Cornth5 ,3p yprcr Y~fvnenSlmv14~ ~(r S Sq. FLIL. t added: Squares BTU's Gallants Amps 4 OMERICONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I nereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules regulations s m City Wheat Ridge or and covenants, agree to sawmills ar nditd phi of record: that all measurements ume full allegations made auls are am rate; that I have read full agrce tc abide by all Conditions nrhs printed on this application and that I assume full responsibility for compliance with the wheat Ridge Building Code (LB.C) and all other applicable Wheat Ridge ordinances, for work under this pernit. Plans subject to field Inspection. CIRLCEONE: ( FR) ( ) or PERSONAL REPRESQ of(O1IYNFR) (CONTRATOR) PRINT NAME SIGNATURE: Date: l/-S L 51 ZONING COMMENTS: Zoning: Reviewer. PUBLIC WORKS COMMENTS: Reviewer. BUILDING DEPARTMENT COMMENTS: OCCUPANCY: Reviewer. - FIRE DEPARTMENT:: 0 approved W/ Comments 0 disapproved 0 no review requted Bidg valuation:; DEPARTMENT USE ONLY ~---- I o Elec. S Plumb. 0 Mech. 0 Structural 0 Other o 1 st 0 2nd 0 3rd Job Address: :7032 :?/r#b.A-il $ c!"" , h.....d /L_t:. - oj/' , I f , I I ! I I i , I f t ! ! oRe-inspection fee of $ o Blocked Access o No one available for inspection: Time must be paid prior to re-inspection. AM/PM 'When corrections have been made, call for re-inspection at 303-234-5933 / Date: /?'/~<,~7 Inspector>Z:::'~ DO NOT REMOVE THIS NOTICE i i I I , i i. . ,-.-. ~"_~_____.c...c_.~_.~"__,..~__~_ _~__.<~_',c___._..~~, _,~_.__. ...."'-___ ..C.__.. ___ -- ,'. .._- ----,--- - ---'.... ~_.~.. .-- --- ~:"";'T1'", '\<~'~"0'""""",,,,,,<,,,_~,,..,,,,,..,,\' ",I", JI,JII!~t~"~I;;;,,,,,,,, ""'''',,''r'' u""", "" ,""o/""~",ll!ll,"","~,,,I!I!'!l,jl!!!III'lil!!JI!l City of Wheat Ridge r Residential Plumbing PERMIT - 071134 PE:RMIT NO: JOB ADDRESS: DESCRIPTION: 071134 3032 INGALLS Repipe Waste CT pipe in C.S: ISSUED: EXPIRES: Inclpulling/replacing 10/19/2007 04/16/2008 main flange, *** CONTACTS *** owner 720/732-9008 gc 720/628-9882 Niki Ragonese CESAR VITELA 07-0169 CESAR'S PLUMBING, LLC .. PARCEL INFO ZONE CODE: SUBDIVISION: .. UA 0503 USE: BLOCK/LOT#: r-3 0/ Permit Fee Total Valuation Use Tax ** TOTAL ** ~17 ~::1,"d~ ESTIMATED FEES 70.25 .00 27.00 97.25 PROJECT VALUATION: 1,500.00 ** FEE SUMMARY ** Comments: ~ I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all me.surements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application and that I assume _full responsibility for compliance with the Wheat Ridge Building Code (I.B.C) and all other applicable Wheat Ridge Ordinances, for work under this permit. plans subject to field inspection. Sl~ature ofcontractor!owner date l~ This permit was issued in accordance with the provisions set forth in your application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Codes of Wheat Ridge, Colorado or ariy other applicable ordinances of the City. 2. This permit shall expire 180 days from the issue date. Requests for an extension must be received prior to expiration date. An extension may be granted at the discretion of the Building Official. 3. If this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes have been or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. 4. No work of any manner shall be done that will change the natural flow of water causing a drainage problem. S Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections' and shall receive written approval on inspection card before proceeding with successive phases of the job. 6. The issuance of a p rmit or the approval of drawings and specifications shall not be construed to be a permit for, nor violation of the provisions of the building codes or any other ordinance, law, rule or regulation. is subject to field inspections. date Signature INSPECTION REQUEST LINE. (303)234-5933 BUILDING OFFICE: (303)235-2855 REQUESTS MUST BE MADE BY 3PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. ~ COMMUNITY DEVELOPMENT DEPT. Inspection Services Division (303) 235-2855 Correction Notice Job Address: .3032 IN&;!}//~<; /'!OuR7, F/A//J/ ~/ /C7"rR/r /. :> \. ~ L ..k"/1 @'J ,v AR /.:J....-;w'..Q (;f/ me> rJr ,.c/l/"/"/~<;O.k>ft" ;? >- :L,~'/'1"r-z. /?LL .b""~...vc.--....1-' I~' -<<~~(~~ ~. ~ ....,,..., ;::-7 (..,../ " )7 J.r-J ,,_jI) '_ . 3. "> ~;;rtJt/?-- /~J__,,'--A- _.t:!l -,," ~;;2\.,~ !h,//yL'7C:X? /YOr../ /V..6:ZI~AL C'~ I S~ PA'/V./,Q. .d 4-.... T/C/lhbV C.RO///1,n LL//; c9 2. ,~ ;7 r'/J7Z/ M/J-'J/I/,L) ~ LOh//) /} AI/CR. When corrections have been made, call fo 303-234-5933. Date: DO NOT REMOVE T --r Building Permit CITY OF WHEAT RIDGE 7500 West 29TIIAvenue Wheatridge, CO 80033 303-235-2855 Permit Number 19081 8/812005 Inspection Line 303-234-5833 .~jiy.~'~&'f#:.~~':--:~2{ Residential Electric PROPERTY 3032 Unit: OWNER: Ingalls St Nicole Regonese Description 200 amp service upgrade. IFEES IFees IUse Tax IPermit Fee ITotal Fees 1 ICONTRACTORS IName ISraQdon Electrical Contractors 1 IDue 1$18.00 1$50.40 1$68.40 1 1 1 License # 122350 1 IPaid 1$18.00 1$50.40 1$68.40 1 1 IPhone 1303948-5251 .'Vnits: Roof: Stories: SqFeet: o Occ;upancy: Walls: entsshown, and allegations made are accurate; that I have read and agreeto 3))ide by for compliance with the Wheat Ridge Building Code (V.B.C.) and allother applicable WNERC OR) SIGNED DATE , This permit was Issued in accordance with the provisions set forth In your application and Is subject to the laws Gfthe State of Color ado and to tbeZoning RegulationundBUlldingCodeofWhea~Ridge,COJoradooranyotherapPlieable ordinances oftheCity. , " ',',_, " _.,'__, ' This pennit sha~ expire if(A) the work authorized is not commenced within sixty (60) days fromlssue date or (8) th~building authorized lssuspended or abandoned for a period of120 days. Hthis pennit expires, a new permit may be acquired for afee of one-half the amountilOnnauy required, p~vliled no changes ~,ave:been or,.."m,bemade intb~ original plans and specifications and any suspension or abandonment has not exceeded one (1) year. H cbanges are made or if suspension or abandonment exceeds one (I) year, full fees shallbe paid for a new permit. Noworkof~nymannershallbCdonethatwillchli.ngethenaturalnowofwatercausingadralnageproblem~ _ _____ _ _ _ _,< . Contractor Shall notify the Building Inspector twenty-four (24) bours in advance for all inspedlons and Shall receive written approval on'inSPection card before proceeding with successive phases oftbejob. The issuance ofa permit or the approval of drawings and specifications shan not be construed to be a pennit for,nor'an appn)'val of, any violation oft~~ provisions of the building codes or any other ordinance, law, rule or regulati on. 3 4 5 6 Chief Building Iuspeetor SIGNED DATE Page 1 of 1 Monday, August 08, 2005 ~~' ~HE~r 1', ~ 0 - " u - ~ COLORp..'iP COMMUNITY DEVELOPMENT DEPARTMENT BUILDING INSPECTION LINE - 303-234-5933 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80033 - (303-235-2855) APPLICATION Building Permit Number: Date:g-g -O~ Property Owner:,.J \Co L. ~ eE&roN e..5~ Property Address: 3o~Z I ,.)074 <..~ c -r. g 02-1...../ Contractor License No.: (j, <; 7 D CompanY:!3tfAC-,,::>o,J ~l.a. CDN1~(f'.)?..s l..l-C- Phone: Phone:3) '1'-( (S - ~ Z5) I OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING ANO AGREEMENT I Buildino DeDt. Valuation Figure: $ I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown. and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application and that 1 assume full responsibility for compliance with the Wheat Ridge Building Code and all other applicable Wheat Ridge Ordinances. for work under this i lans b' ct to field inspection, (OWNER)(CONTRACTOR)" SI DAT0" .,8 -Os. Value:$ 1000,..... Permit Fee:$ Plan Review Fee:$ Use Tax:$ Total:$ DA Use of Space (description): Description of workSe:e..l1c. EO l.:)f'C7 ~A\-r:::.c ZoO AI'1f'" Sq. Ft. added BUILDING DEPARTMENT USE ONLY SIC: Sq.FI.: !zONING COMMENTS: Approval: Zoning: IaUILDING COMMENTS: Approval: PUBLIC WORKS COMMENTS: Approval: IRE DEPARTMENT COMMENTS: Approval: Jccupancy: Walls: Roof: Stories: Residential Units: Electrical License No: Company: Plumbing License No: Company: Mechanical License No: Compsny: Expiration Date: Approval: Expiration Date: Approval: Expiration Date: Approval: (1) This permit was issued in accordance with the provisions set forth in your application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Codes of Wheat Ridge. Colorado or any other applicable ordinances of theCily. (2) This permit shall expire if (A) the work authorized is not commenced within sixty (90) days from issue date or (8) the building authorized is suspended or abandoned for a period of 180 days. (3) If this pennit expires. a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes have been or if suspension or abandonment exceeds one (1) year. full fees shall be paid for a new permit (4) No wof1( of any manner shall be done that will change the natural now of water causing a drainage problem. (5) Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceeding with successive phases of the job. (6) The issuance of a pennit or the approval of drawings and spedfications shall not be construed to be a permit for. nor an approval of, any violation of the provisions of the building codes or any other ordinance, law, rule or regulation. All plan review Is subject to field Inspections. Chief Building Official - --1-- ,Byilding Permit CITY OF WHEAT RIDGE 7500 West 29TII Avenue Wheatridge, CO 80033 303-235-2855 Permit Number 19070 8/4/2005 Inspection Line 303-234-5933 Residential Mechanical PROPERTY 3032 ingalls OWNER: Nicole raymond ragonese Unit: (303) 232-6002 Description New swamp cooler IFEES IFees IUse Tax IPermit Fee ITotal Fees 1 ICONTRACTORS IName IHome Owner 1 IDue 1$9.00 1$30.55 1$39.55 I 1 ILicense # 10 I IPaid 1$9.00 1$30.55 1$39.55 1 1 IPhone 1 Units: Qccupancy: r-3 Walls: City of Wheat Ridae .PRESCRIPTIVE ENERGY CODe BOILERS I FURNACES A MINIMUM OF 90% AFUE GAS WATER HEATERS A MINIMUM OF .60 ENERGY FACTOR ELECTRIC WATER HEATERS A MINIMUM OF .93 ENERGY FACTOR smACK THERMOSTAT REQUIRED (EXCEPT HYDRONIC HEAT) R-21 WALLS ~ R-38 CEILINGS. R-19 CRAWLSPACES Roof: Stories: Sq Feet: o. I hereby certify that the setback distances proposed by this permit application are accurate, and do not viohite applicable ordinances, rules or regulatiolL'l ofthe City of Wheat Ridge or covenants, easements or restrictlolL'l ofrecon!; that all measurements shown, and allegations made are accuratc;tbat I bave read and agree to abide, by .. roodi"", p';ot'~4it'" .pplk"''', ~d th" I u,"ro, '0. ,mpo",'bili" ,,, "rop""" with th, Wh," Rid" Bo",m, Cod, (U.B. 'C.') and all other applicable Wheat Ridge l~aA rOI".&Dder,thisPCrmlt. , g'Lt03 N CTOR) SIGNED DATE \ r This pennlt was Issued in accordance with thepmvisions set forth in your application and is 5ubjeclto the laws DC the State of Colorado andtotheZonlng Regulations lmd Building Code or~hcat Ridge, Colorado or any other applicable ordinances ofthe City. This pennlt shall expire if(A)the work authorized is not commenced withinsixt)' (60) days from issue date or (B) the building authorized is suspended or abandoned for.a period of1IO days. Hthispennit eipires, II riewpermit may be acq~ CoraCce oron~halfthe llDlount nonnany required, provided noclwnges have beenorWill be made mthe original plans andspeeilkatlons and any suspension or abandonment has note:rceeded one (1) year. Ifchangesare made or lfsuspension or. abandonment exceeds one (1) year, full fees shall be paid for a new permit. 4 NO.work ofanYffi,anner shaU be done that wlUchangethe natural 80w of water causing a drainage problem. S Contractor shaU notify the Building Inspector twenty-four (24) hours in advance for aU inspectiOl1.'lund shall receive written approval on inlipectioncard before proceeding with successive phases ,of the job. (; The issuance ofapennit or the approval of drawings and specifications shall notbeoonstmed to be II pennlt for, nor anapproval of, any violation of the provisions ofthe bui. es or any ot ce, law, rule or regulation. ChlefB Thursday, August 04, 2005 SIGNED DATE Page I of 1 Building Permit CITY OF WHEAT RIDGE 7500 West 29TH Avenue Wheatridge, CO 80033 303-235-2855 ,:g~y#'~~.~g,~'<<'l Permit Number 19070 8/4/2005 Inspection Line 3D3-234-5933 Residential Mechanical PROPERTY 3032 ingalls OWNER: Nicole raymond ragonese Description New swamp cooler Authorized By Building Approval Authorized On Thursday, August 04, 2005 Zoning 5/5/2005 Approved By croot Unit: (303) 232-6002 Page lof 1 COMMUNITY DEVELOPMENT DEPARTMENT BUILDING INSPECTION UNE -303-234-5933 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80033 - (303-235-2855) APPLICATION Property Owner- \ wLe: _4-- L'i\lJN\ C ;'-.j.) 12,\-(':,C):...JIS U Property Address:~yy I NG--f\LV~ C.:-;: Contractor License No.: Company: Building Permit Number: Date: Phone: ~f)'" - 2<,2--(( ':;6 L Phone: i2b ;l ':, '2 - 4\)Jr OWNERlCONTlIACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I Buildino Deal. Valuation Figure: $ 1 hereby certify that the setback distanoes proposed by this permit applicaijon are aCCUl"3le. and do not violate applieable or<linances, rules or regulations of the City 01 Wheal Ridge or covenan\lI. _ or __s of record; thalaI measuremenls shown. ar>d allegations made ate accurale: that I have read and agree ID abide by aI cor>ditionS printed on this application and that I auume fuU responsibility to< complian<:e with the Wheat Ridge Buitding Code (I.B.C) and all other applicable Wheat 1~:;=~:=l~~.Liie:~~:~}o) ((OW~COHTRACTOR);PRIHTEO . COLt fj, <i' DATE~ --- Use of Space (description): Description of work: )~Q. (' --s."'-'1:1lf ey(, G.:,- Value:$ Pennit Fee:$ Plan Review Fee:$ Use Tax'$ Total:$ Sq. Ft. ad_ BUILDING DEPARTMENT USE ONLY SIC: Sq.Ft.: QNING C<:JMMENTS: Approval: Zoning: 3uIU)lNG COMMENTS: Approval; >usuc WOI'J<S CQNMENTS: Approval; IRE DEP.....-nEHT COUMENTS: Approval: Occupancy: Walls: Roof: Stories: Residential Units: Electric:aI License No: Company: Expiration Date: Approval: Plumbing License No: Company: Expiration Date: Approval: Mechanical License No: Company: Expiration Date: Approval: (4) (5) Ie) This permiI_ issued in ac:oordance with the provisions ""'loI1h in your application and is subjoct lo the laws 01 the Slate 01 Colorado and lo the Zonng Regu\Blions and s.-.g Codeo of W_ Ridge. CoIorwIo or any _ appIlcabIe ordinanoes of the CIfy. This permiI_ e><pA W (A) the -'< __ is not oommenoad within sixty (90) daY' from issue dale 0< (B) the building __ is ..-- 0< _.do...d lor a period of 1110 days. ~ this permiI """""". a MW permiI may be -""'" lor a lee of one-haIf the amount nonnaIIy requil1ld. provided no changes __o<wiI be_in the original pIano__ili- oOli ..._any-,""," o<__notexceededone (1)_. I__--orl-'""'" or_4...-..oI_ona (1)_. "'__be paid 10< a newpermil. I0Io-'< of any_"" be dona _wiI c:Iwlge the..... - aI_c:auoIng a ~~. c...1Il_"" noIIy the a.-.a ~_ .....<I)-fw' (24) holn in ___lor.. .lOpllCfiol.. and _ receive_ __on...,--..,c:anI-.... .iIlIllI-"- '..~ofthejob. The iuuanoa aI a permiI 0< the __ of dIa..olllO _ opedlIcatioI.. .... I1CIl be ~ to be a permillor, nor an a~ aI. any_ of the provisionsalthe bI-.g codeoor any_"'''''''''''.law. rule 0<"-. AII.........- Is subject: to fteId 1nI~' ctl EmS. (1) (2) (3) ChiAf Buildino 0fficiaJ ?7""''>P '" \ / -\ -<\" ry/J' a.~ 4501 Wadsworth Blvd., #102 Wheat Ridge, CO 80033 (303) 423-8982 Fax: (303) 423-0067 FIELD OBSERVATION REPORT July 19,2002 City of Wheat Ridge Building Department 7500 W. 29th Ave. Wheat Ridge, CO 80215 Engineer's Job No.: 3148 Permit No.: 13875 Project Address: 3032 Ingalls Court Wheat Ridge, CO 80215 General Contractor: Ray & Nikki Ragonese 3032 Ingalls Court Wheat Ridge, CO 80401 Type of observation: Date of observation: STEEL PIER INSTALLATION NEW COLUMN 05/06/02 05/21/02 FOOTING PAD 05/21/02 I certif'y that the above items were observed by a qualified person under my supervision on the date indicated and that the items liste~iUlW,j"tpd were in conformance with the requirements of the engineered plans " \\\, R --.rtlll prepared for thiS project. ,,\\\ "'\l~ S/:'qzz .;'$ o_~.. .~ ~ ~ ~'f:i:" ..'\. . <~ ~ .:::: " .~~ :: -', 0 ~ -' -""",.'- -. .- - : 3170 :",,= s. ""'0 .. ~. I-IJ ;: Rb LMalffPE"'~' ",,::: o ert. OU,.. ~ '*' .... ~.~'._.;>. ~ <' "l'J' ...."... \\J' ~ Zz S "':.... '--" Zz ION ,. \ ., \\' 1'/1/ r-.\..-__ \\\' _"119"'2002 DEPARTMENT OF PLANNING AND DEVELOPMENT BUILDING INSPECTION LINE - 303-234-5933 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 - (303-235-2855) Building Permit Number: Date: 13875 5/17/02 Property Owner: NICOLE RAGONESE Property Address: 3032 INGALLS CT Contractor License No. : Company: Phone: 303-232-6002 Phone: OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Construction Value: Permit Fee: Plan Review Fee: Use Tax: I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application, and that I assume full responsibility for compliance with the Wheat Ridge Building Code (U.B.C.) and all other applicable Whe t R ge or' nces, for work under this permit. (OWNER)(CONTRACTOR) SIGNED' DATE5--2..D-O Total: $4,200.00 $111.25 $0.00 $84.00 $195.25 Use. Description: ROCKY MTN STEEL PIERS (L1C#21293) REINFORCING STRUCTURAL DAMAGE TO EXISTING ADDITION WI STEEL PIERS- HAND DIGGING HOLES & MANUALLY INSERTING PIERS. SIC: BUILDING DEPARTMENT USE ONLY Approval: Zoning: ----- Approval: BG 5/16/02. CONTRACTOR MUST BE LICENSED. Approval: Occupancy: Walls: Roof: Stories: Residential Units: Electrical License No : Company: Plumbing License No : Company: Mechanical License No : Company: Expiration Date: Approval: Expiration Date: Approval: Expiration Date: Approval: (4) (5) (6) This permit was issued in accordance with the provisions set forth in yopur application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Gode of Wheat Ridge, Colorado or any other applicable ordinances of the City. This permit shall expire if (A) the work authorized is not commenced within sixty (60) days from issue date or (8) the building authorized is suspended or abandoned for a period of 120 days If this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. No work of any manner shall be done that will change the natural flow of water causing a drainage problem. Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceediing with successive phases of the job. The issua ~ the approval of drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation of the pro.. of / i I;. des or any other ordinance, law, rule or regulation. (1) (2) (3) ~~' WH[Ar 1'/ ~ 0 - C> u ~ C'OLORF>-QO DEPARTMENT OF PLANNING AND DEVELOPMENT BUILDING INSPECTION LINE - 303-234-5933 CITY OF WHEAT RIDGE 7500 WEST 29TH A VENUE WHEAT RIDGE, CO 80215 - (303-235-2855) APPUCA.TION 'Building Permit Number" Date: Property Owner: NICo L"L- eA-60N""iS-"Y'___ Property Address: 3'732- / NG--AU-<;;. C::r; (~~) Phone:30~-2/32.-GOO2- Contractor License No.: ';?Iz.~~r/L<~ ) , .&13> Company: ~CJC<.I KTN .::sl't-."i..(.... PI Ge..& c\- I-"'Al-OlItFF Phone I Z-<J - 73>2 :400't OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Construction Value:$-4 7-00 Permit Fee:$ } Plan Review Fee:$ Use lax:$ Total:$ /Gt? Z5- I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance with the Wheat Ridge Building Code (U.B.C) and all other applicable Wheat Ridge Ordinances, for work under this permit. -l (OWNER)(CON1RACTOR) SIGNED ~;J L ~^C"" . DATE Sf I 51 07 Description: ~\M01"'CA' '<5 ~ch.v-~ ~~ +0 ~"'-I'4 ~ ~:h' or--' \NI~ p<u-s-I"u---.-I c&~t3'C: Nb+IY'~ ;~O po '0--'5.. BUILDING DEPARTMENT USE ONLY SIC: Sq.Fr.: ZONING COMMENTS: Approval: Zoning: BUILDING COMMENTS: Approval: tJ. ~. '/I~/(j).. (..,.. frH-.1tP i. .I pe/ V'- C~~ ' t#fI?i f_11 r,,"ff':f. PUBLIC WORKS COMMENTS: Approval: Occupancy: Walls: Roof: Stories: Residential Units: Electrical License No: Company: Plumbing License No: Company: Mechanical License No: Company: Expiration Date: Approval: Expiration Date: Approval: Expiration Date: Approval: (I) This permit was issued in accordance with the provisions set forth in your application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Codes of Wheat Ridge, Colorado or any other applicable ordinances of the City. (2) 111is permit shall expire if (A) the work authorizcd is not commenced within sixty (60) days from issue date or (B) the building authorized is suspended or abandoned for a period of 120 days. (3) Iftlus permit expires, a new permit may be acquired for a fee of one-half the amount nonnally required, provided no changes have been or will be mnde in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year [fchanges h~ve been or if~u~pel1~i()n or <lb<lllc1nllllle'nt exceeds one (1) year, full fees shall be paid for a new permit. (4) No work of any manner shall be done that will change the natural flow of water causing a drainage problem. (5) Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written ~pproval on inspection card before proceeding with successive phases of the job. (6) The issuance of a permit or the approval of drawings and specifications shall nol be construed 10 be a permit for, nor an approval of, any violation of the provisions of the building codes or any other ordinance, law, rule or reguJation. ChGiwin~~ e5/15/2ee2 15:27 15e9552e229 NIrYI RAGONESE PAGE e1 3p~~~ 10'. t.ti 'S'-T1' ~1\O ~ ~ +fu., ~ JrOVV",' ~ ~ (S\ 30 3> L I ~~ cJ_ ~~ f1ifS. ~ .?:o3 - Z~2 - Co 0-0 2... ~ ~cb~ * ;~: -4il-ll$S LtZc~ ~ ~ Ru-s) t-Pb H.~~ ~. u..v+-{A/"J .&r~~ 4'l..-~ - <{4~Z- - 05/15/2002 15:27 15095620229 .8 n 9 I n e 8 r I n 9 4501 Wadsworth Blvd., #102 Wheat Ridge, CO 80033-3303 (303) 423-8982 \ \" \ ," \ ~ IIIP I ! , 11111111 of~~.?.~~~~si~~'~~~ ;&"'il"\.'~('" "<. "c.;"~ q;;.. ~ ~! ('" ~ ;.l - . - \ ~ g % '-... ..... f >, ~'"S ........... ~G-~' "/"f~.." iONAl ~~. ).~~"O"ll'" APPROXIMATE PIER L-OC-ATION NIKKI RAGOf~ESE PAGE 02 Job No. 314b Sheet No.2-of~ Client RAY AND NIKKI RAGONE5E Job Address 5032 INBAL.L-5 GOURT Description PIER LAYOUT Scale AS St-\OI'lN Date 415102 - ---v~ - rr II ;2'-0' X 2'-0' X q" n!ICK I <:;ONGRETE PAD i'Un! I (4)-WI3 REBAR eACH HAY I REBAR EACH HAY I (b)-;2 X 4 DIAeONAL.j I eRACES ATTAC.HED TO THE: eoTTOM OF BEAM AND EAOl I I FL-OOR .JOIST i'Un! (b)-Ibd NAIL-S I _ -=- -=- J~ TfV\-- - - -V\--I- II ~ I I EXISTING BEAM~ ..---1 II I I 3-1/2"4> SCHEDULE 40 I ADJJ5TAt3LE STEa. PIPE COLUMN l-Iln! 3/4 X 4-1/2 ,. I X 0'-0" STEEL PLATE I ~ER BEAM I L~~~r><' L~ X f!> X 1/2 X I'-t>" STEEL BRACKET H1ill (;2)-3/4"4> BOLT5 INTO EACH FOUNDATION lo'\ALL APPROXIMATE PIER Loc.A TlON "-AF'PROXIMATE PIER LOCATION CD PARTIAL FOUNDATION PLAN 3 sc.AU;:, NOT TO 5C-ALE 05/15/2002 15:27 15095520229 NIKKI RAGONESE PAGE 03 Job NO._:l14f> _Sheet No.~of 4 Client MY ANO NIKKI RAeoNESE Job AddresS 30~2 IN6ALl-5 COURT Description oe;iAILS scale_AS ~ Date 4/5/02 COL.~ PER f'\..AH s .. G) \ 15M ~ PERPLAA on FOOTIN6 PAD PER P..AN ~~J:~~O~YLEINTERIOR PADS FOUNDATION l'lAU- 61/2' l/f>'6) HOLES FOR 3/4'6) BOLTS \\,,\\'1111"" ....,\,'~t)O AS""'"" $',;y ...... GIS;;" , n i:~~~L~' M......~\ ~-- )...~ ~,~.. :~~ "0 <<'.r" /ti} g '''-i",~io'' ....... ...~~ ,./ A- '",,," ~At t.~ ,,,,,,, rlTlf)'tll~ . ~ 5~ B X 1/:2 Tct=- AN6LE x 1'-6" B HAL~TH FCJUNo 8Ol.. TED 5C RACKET 5 AT/ON A1.C, NoT To 5GALr:ET AIL I I I I I i i , 2 s . DEPARTMENT OF PLANNING AND DEVELOPMENT BUILDING INSPECTION LINE. 303.234.5933 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 - (303-235-2855) Building Permit Number: 11307 Date: 10/10/2000 Property Owner: Property Address: 3032 INGALLS CT Contractor License No. : Company: OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Phone: 232-6002 Phone: I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application, and that I assume full responsibility for lIance with the Wheat Ridge Building Code (U.B.C.) and all other applicable at"d 0 mances, for work. under this permit. (OWNER)(CONTRACTOR) SIGNED DATE I ol/Pi! ()Q Total: $900.00 $35.70 $0.00 $22.50 $58.20 Construction Value: Permit Fee: Plan Review Fee: Use Tax: Use: Description : BRICK MASON REMOVING BRICKS FROM WALL TO INSTALL A SLIDING GLASS DOOR IN DINING ROOM BUILDING DEPARTMENT USE ONLY SIC: Sq. Ft.: OK 10/10/00 Approval : Occupancy: Walls: Roof: Stories: Residential Units : Electrical License No : Company: Plumbing License No : Company: Mechanical License No : Company: Expiration Date : Approval: Expiration Date: Approval: Expiration Date : Approval: (4) (5) (6) This permit was issued in accordance with the provisions set forth in yopur application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Code of vvtleat Rid~e, Colorado or any other applicable ordinances of the City. This permit shall expire If (A) the work authorized Is not commenced within sixty (60) days from Issue date or (B) the building authorized is suspended or abandoned for a period of 1:2:0 days. If this permit expires, a new permit may be acquired for a fee of one~half the amount normally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. No work of any manner shall be done that will change the natural flow of water causing a drainage problem, Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on Inspection card before proceediing with successive phases of the/'ob. The issuance of a permit or the approval 0 drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation of the provisions of the b . 9 codes or any other ordinance, law, rule or regulation. (1) (2) (3) C DEPARTMENT OF PLANNING AND DEVELOPMENT Building Permit NumDe~ . BUILDING INSPECTION LINE - 303-234-5933 CITY OF WHEAT RIDGE Date I I 7500 WEST 29TH AVENUE (.) WHEAT RIDGE, CO 80215 - (303-235-2855) ~\ON Property Owner. NI W &:>" e..c at- iZ-A-j e4kso N<'~S U Property Address $032- I N E,--t+\..-LS ( I. Phone .~ 3 - 2- S2-'LLco 2.- Contractor License No. . Company: OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Phone .IZv" 7SZ -C1co 8' Construction Value. "100 _ I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide b)' all conditions printed on this application, and that t assume full responsibility for campi e with the Wheat Ridge Building Code V.B.C.) and all otherappJicable WheRidge ord" ces, for work under this permit. DATE I DhlOJ Description :Srtd:- 'HOVJ7YJ re.fYY}Y1 ~ b,lt..ka- ~ WdJQ +0 ({l~ ~,:Jh (5 ~ vbor If'diA.J'IO y-oonl Permit Fee. Use Tax. Total: Use: ~ BUILDING DEPARTMENT USE ONLY ~mg'."'c:Jmments1 Approval: Zoning: Biilrd~o.rtIml!!lts:l ~ tiJrT).... tal/I:> /0-0 Approval: - ~ ~lJ1)I~o!1t!r~C;e!T!!l1.!t!!!!l;l Approval: Occupancy: Walls: Roof: SIC: ~qj /~. :Zfi(.. l "., ,., J ~~/"l ':1' I ' Q I:..X' . <::). i.....'/' ,- " .IYL' i vQ <..~/'r U'7 ,Ole V '.1 . ':-Z:'l'? Stories : r;----". . ,/ Electrical License No .. Company: Plumbing License No : Company: Mechanical License No : Company: Expiration Date: Approval: Expiration Date : Approval: Expiration Date: Approval: ". (1) (2) (3) This permit was i,ssued in accordance witI'I tna provisions let forth in yopur application and is subject to the laws of the State of Colorado and to the ZOning Re,gulations and Building Code of Wheat Ridge. Colorado or any other applicable ordmances ottne City. ,,_' This permit shall expire if (A) the worX authonzed is not commenced within Sixty (60) days from issue date or (B) the building authonzed IS suspended or abandoned for a period of 120 days. _ _ . If thiS permit expires, a _new pennlt may be acquired fOf a fee of one-half the amount normally required. Pl"OVlded no changes have been or will be made in U'le ongmal plans and SpeCIfications and any suspenSIon or abandonment has not exceeded one (1) year. If Changes are made or If suspension or abandonment exceeds one (1) year, full fees snail be paid for a new permit. No work of any rnar.lner shaUbe done that will Change the natural flow of water causing a drainage problem. Contractor shall notify U'le BUIlding' Inspector twenty-four (24) hours in advance for aU inspections and Shall receive written approval on inspection card before proceediing WlU'l succesSIve phases of the job. The Issuance of a permit or the approval of drawings and specifications shall not be construed to be a permit for. nor an approval of any violation of the provisions of the buildmg eodes other inanee, law, rule or regulation. . (4) (5) (6) ~ie.... 4, tcoo Pec.JEt::;r~ /..iNfra- ~I&lN Fee N~ ~DIN~ b~ ~~ ONN~; f2.A-'I e~eNt-~ 1 I<iI~KI Bove~ 4DD~; ~07Z. INbA~ ~~ i2iDSe) CJ)/iI!t:;\ to ~4 U0t:..: c;;'y: 3/2 x ~/( AN&1LE roe. 4w CDI\J.J2I!-(E euz.(L tNtJ.'fY2- J.,)rt1L- 7'1z- X ~'!z.- x y~ M8/k:.. me ~la:.. V~fEe No~S. ~ I"tlN/MrA/'IJ 4'1 ~~AeJ~ EA?H &J.D Mo l2..Thl2. ANC;;:j~.s IN Pl..ACE. /J)Axt{ll1lAilVl, t,.lNiU.-7PA-N 1'-0" I f IN0~ WA1-L- 17 &~ ef... 6 "~fVI(;() G:,f2O.Li --lA-ME> "Scu D. 'TYPlc.4t- Lf 4!1 1!\J11i/8L crv1 (;( '5>ec..ll oi'-.J . ~~~,n----E70.CL VENC8Z... Bl D ~ "r/" ~ 871- '^ 3/<. 1'-;+ Mc?L-€ ," ,j 1/ 1/ ({ ) :;7 X 3/[. ;< /4- !i:N6IAE'/5"/..e7=, I';;> V~T7.Ac-, 1\11111'", ,\ \', \\ ~i:.;',"" " ....\\\) .....iJ1J'/', .... t"V ..', ,'" ~~' ............ <.~~ ...... .';.,"'~ ...\\-\OIT/~'~.. r~,_""... .$~ ..e\;), <f<}-... ./ -=: ,,::,, c~:. - ........ C' "- - ..h .- .....,..."......."2 '.)'-j- :).4 :<'( .,).j.:JL G;:': ~ \"Z 1f....-<l0 "'.: _ ~ '~~y'.~- "-:..~~~ e. . .c"; :",:: ....... j'.,.('~ ............\ ">,,,"?, ...... , ~ J {I . .....",.. " ..;/)\1 'I. '\." ,," I'II'/,J.\ \\\\ 111/lJlill\ -.--i--___" l)f\(E__~3/ lh/~3 FEE MornGII,CL Co. I<AREN 00.00 Jon II -.!~~O PRASI<I LAN 0 SURVEYING AD'",,,,,_ :1032 INGALLS CT. [jOHflO"'I:II~, NAME __~~AURO ----- ~j<'jfjO WAR!) flOAD . 5tH n: I GO AHVADA, '-':OLOH\lJO eQ002 (30J) 1120-4700 ------_..--~._- ---. 1 r,l/'/H_IVEM E NT L\JCATlOU C f~nTl FJCATE ALtn: SIIAfWN LEGAL DESCHIPTION (PER CU[NII r:~T 5, DLOCI( 3 STEBBINS SUB., COUNTY OF JEFF~RSCN, STATE OF COLOI/ADO I L ~ ,SCAU>/"0 ZD' '- \ \ \ I~i I '6 I '~ ---,..- ~'''- ,.~' ('... '"to \ /' '\ ./ \ - '\ ., //, ' /--(.... oj. )t" / ih _-'(/ fl. '/' \_> ,/'< "" // \.... /.( 'I c ' / O() ........... '~'I ;t.". t /-'~I _ ---\ I -~ ~/ ,// ')<:'\ /, /t '. -. ::... -- -'. - _/LI I;' \ ~~' " ..........,./ --"- - -~ -- -~ / - ,/( \\ /'-//' , I I ,/ r,. \\ /' /'\ / J ,/ ", \'c~// ,\ ! : '_. ) '1 I ,v;:' ",,' ~-:J, , '\':;~)0> 0, I' ~~ ~- D~\vt:.. ~, \ ' ,/'? ofl;-~,., ~' 0\ oJ:- ~V0G. (\ \j:P,(}V '" 22,1'-': " <(v. ~.' ':'>f' 10 =e ~ ~I ~ ....- ,,~\ ...............- "I II-q' \ ,. ci /)'\ '~}l ,,' (',.. ./ -r i I I I\J '" I 'n '~--}2~)(' \;; "----~L---.J:L n I' ~_~t' J if.. 'I S' j C<t.(,y"'(,f~Y;-;if."\+!'-----__-'J ,,~L~_ "'~~--- '3 u. 00: -~- - ~ _ ~"- - ~'~l::;'/ o C.v-(.. "..., ~-I oyp .~~JV \/0" 1f)'P ~o/ ,\~p '\ "-,y-' ~ ",~",,/ '}() 'oV , -~/ ~~ ,(' , <' I ,/, ", . -, ,..' ... III>,:'-"D \ r.- . , I 'Z I' '.. ---'p---- , I. , " .' Il " ~, ., -, ", Orl tile basis of my knowledge, information a/ld belief, I heroby certify 1I)o3t t11is IlnprClvement location cerUficate W<;ls prepared for 1(6Pf:N P[JAr>I<I /...' ,that it Is not a La:~d Survey Plat or Improvement Survey 'F''ft t, all 'frlat it is ~ot to bo relied u on for the estab ishment of fence, building, or\other futuro "nprovement lines, I further cerlify th,,' lIe irnprovemenL Dn the above d,)scribed parcel on this date, e~cept ulllity connecliDns, are entirely within Iho boun"ar es of the pm cel, except as shown, thai Ihem are no encroachme"'~s upon the described premises by Improveme"ls on. "y ~djoi"ing premis s, except as indicated, and Ihat there is no apparent evidence or siun of any cLlsernenl crossing or burdeni"j nn~Clrt of said p<.J 'cer, Oxcept as notecl. I ~\\"II: 11/ II' I "NOnCE: Acco<<fiog 10 C%m,/o law you '" ont co O,"OCO no,' '0'1' '0'(;00 '''\.~')\ tll"}i[W J!b1rH:t in tllis SlJfv(>V wiChin /1110(> }(,ilr~ af/er rou (j'sl '/,se",,,,, .suc/, oIelec/. /00" evool, may noy ,"Uo" I,d,pol ""oo"'y, '<(el io "!In'f'\< "~ /', ,6,\Y,Ic\"cool mom ""''' /00 yoa" "'''', tI.e ,/.-.Ie 01 fll(>c,?!(lfiCil!iOI}S!)()Wllhnrcoll." ",\.~..:, '\.';' rli "'a (-p'_:: / ~ . / .:J ."~\,\ "~';':t<~'-::;. " is my ill,',O >rpr.e, lalion lI,lalll>O "bave describe/! '-',:_ ' "'''} " )". ,;) " p,apOlly /05 /'o'C:: _'_.. . localed \\it"'n a 1Ot, ....... /', ~~ ", ':::.', / year flood I>aza,u lx>uIKJary based on h)(lor31 "-(~: ' -2.Z(~€>", _ /2 ' 1/1. 'i:c, Ern/!'gcncy Mamgomentllgency Flood "'SU~l9C8 -- -:T~--;.._ 6P _________ _ r'ilIOM~"I'XJ --j3,,;:'__~,,"-=, 4-c.... Hobert E. p(".t~ I-;;~. '15a..1 or.t'll' ,ert M. HaYden, L.S. 27260 '" "cu-----....... . d c. . ., l..-IJ-' /J OU\JI.-JU-O "" ,.. .' ~'.', - -- --_. ~ -'-' '-] ...._""" ' ''-:-i-. iJj"1 "\\\ ,.\' //,'// ,II .1\ \ \' S" II.ili.,: ITl,\\ ,. D/iPARTMENT OF PLANNING AND DEVELOPMENT BUILDING INSPECTION LINE - 303-234-5933 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 - (303-235-2855) Building Permit Number: 11119 Date: 9/5/2000 Property Owner: Property Address: 3032 INGALLS CT Contractor License No. : Company: OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Phone: 832~002 Phone : I hereby certify that the setback distances proposed by this permit application are accurate. and do not violate applicable ordinances, rules or regulations of the City of Wheat Rklge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and a9ree to abide by all conditions printed on this application, and that I assume full respon Ibilit for lance with the Wheat Ridge Building Code (U.B.C.) and all other applicable eat 'dg 0 nanees. for work under this perm~tj (OWNER)(CONTRACTOR) SIGNED DATE 'I/Q.tfiI:? Total: $5,000.00 $111.25 $0.00 $125.00 $236.25 Construction Value: Permit Fee: Plan Review Fee: Use Tax: Use: Description: ADD 6' PRIVACY FENCE TO REAR AND SHADE PERGOLA BUILDING DEPARTMENT USE ONLY SIC: Sq. Ft. : Approval: Occupancy: Walls: Roof: Stories; Residential Units: Electrical License No : Company: Plumbing License No : Company: Mechanical License No : Company: Expiration Date: Approval: Expiration Date: Approval : Expiration Date : Approval: (1) This permit was issued in accordance with the provisions set forth In yopur application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Code of Wheat Rid~e, Colorado or any other al?plicable ordinances of the City. (2) This pennlt shall expire If (A) the work authonzed is not commenced within sixty (60) days from issue date or (B) the building authorized Is suspended or abandoned for a period of 120 days. (3) If this pennit expires, a new pennlt may be acquired for a fee of one-half the amount normally required, provided no changes have been Of will be made in the orIginal plans and specificatIons and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment exceeds one (1) year, full fees shall be paid fOr a new pennit (45l No work of any manner shall be done that will change the natural flow of water causing a drainage problem. ( Contractor shall notify the Building Inspector twenty-four (24) hours in advance for alllnspeclions and shall receive written approval on inspection card before proceeclilng with successive phases ot the job. (6) The issuance of a pennlt or the approval of drawings and specifications shall not be construed to be a pennit for, nor an approval of, any violation of the provisions of the building es or yother ordinance, law, rule or regulation. DEPARTMENT OF PLANNING AND DEVELOPMENT BUILDING INSPECTION LINE - 303-234-5933 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 - (303-235-2855) ~\ON WVTL ~ I NGA-L-.L~." C- T~ Building Permit Number: Date: Property Owner: N k:..o L.<L Property Address: =>;p 32- Contractor License No. : Phone: :?o3 -032 -(;iooz. Company: OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Phone: Construction Value: 5.QaD PermitFee: II/.;)..~ Use Tax: 1 hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application, and that t assume futl responsibility for compliance with the Wheat Ridge Building Code (V. B.C.) and all other applicable eat Ridge ances, forwor1< under :l.:J:...i~ ~~CONTRACTOR) SIGNED DAT~ Description: {y ~oo-I- frlltX. ~c:....e.--' ~~ Br'5d1 BUILDING DEPARTMENT USE ONLY Total: Use: ~fii1l9\.~grq~emJ] Approval: :JF:.- Zoning :Q.z. Btll!!I~~!!~1! Approval: VI/ ~/(}CT R.~.I5~..Qmm~u!~.;! Approval: Occupancy: Walls: SIC: e .Ft.: ~ RECEIVED SEP 0 52000 Roof: Stories: Electrical License No : Company: Plumbing License No : Company: Mechanical License No : Company: Expiration Date: Approval: Expiration Date: Approval: Expiration Date: Approval: (1) (2) (3) This permit was issued in accordance with the provisions set forth in yopur application and is subject to the laws of the State of Colorado and to the. Zoning Regulations and Building Code of Wheat Ridge, Colorado or any other applicable ordinances of the City. _- This permit shall expire if (A) the work authorized is not commenced within sixty (60) days from issue date or (8) the building authonzed is suspended or abandoned for a period of 120 days. If thIS permit expires, a new permit may be acquired for a fee of oOE~"half the amount normally required, provided no changes have been or will be made in the anginal plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. No work of any manner shall be done that will cnange the natural "ow of water causing a drainage problem. Contra~~r Sh~lI notify the Building Insr~r twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceedimg WIth successive phases 0 the Job. . . . The issuance 01 a pennit or the approval 01 drawings and specifications shaH not be construed to be a permit for, nor an approval of. any violation of the prOVISIons of the buildin cod or a other ordinance, law, rule or regulation. (4) (5) (6) Chief Building Insp or -,-_.; -.-- D/\rE 12/14/93 FEE 00.00 J08ff~~-20540 PRASI<I MORTGAGE CO. I(AREN LAN 0 SUR V E Y I N G AODRE'3S 3032 INGALLS CT. 54()O WARD nOAD . SUITE I GO ARVAOA. ''::OLORl\UO 80002 J30:3) 420-4788 GORIWNf.::RS NAME __t~AURO IMPROVEMENT LOCATION CERTIFICATE Attn: SHARON LEGAL DESCRIPTION IPER CLIENT) ~OT 5, BLOCI( 3J STEBBINS SUB" coumv OF JEFFtRSON, STATE OF COLORADO I L ~ SCALf:.-/i/= ZO' r~ I \ \ , -' 'j, ,~\ .< 0 0 .'" " . , ...., ." /,' "- ~'/. )",. /', flY /i 'I, < "'", ." ";;- // \o~~<.A' 1, ~~ _ \~? / /~ ,t' I /-"'\A" ~~_' 2. _ 2.__1-..1 .... -'\. \ -- - - -- -- - - - ~~ ~ \ ~ ' . (; \ ..-- ..--/ /"\ I /,t< \\ ./"",/ r\ / ,,' \~/~// ,\ / //"F~ .:.: \ ~:7:J( <. ""' .,J> 0, \0' , \ ,,/.Q 01;:-1... , 0\ +- ,.:>vf<./ \ A (j). (<,(/(/' V'1/-7 1--'" II / I I I n~PY r f"'~ V' lEV .J1,0/ \P 'Y' ."lY '~ .. '" .A / , ,( " i. . /) l>'/ r- "'~'.~AD I 'ZI' '- - L'--f,--- o .. I) Cl "" .,. 1- <'-11 - , , D)2\-IE. .\ "1.'2.'1' --: " '" ~ o o l .~ ~<S>. (,0 '1 11... 0'1.1 ,'7 \ . V \/ . \,V Sr;: I c..K I) I/O /' 0 f_^"'^, e. " /'" l;J-~ ..-- ,,/- I I\l I\l 'I) /";,..,... . '/ . I I ( I ~ n.,' I:J~' ~--. -, ~I L____ -__, I , L~ '-"-"< '0 c::s(. ~ C~,.., /S'-I lJi -t'~,,\of', ,"" , On tile basis of my knowledge, Information and beller\ herOIJy'certif{t;,at this Im~";:(lvom0nt location certificate \:v.;lS prepared for 1(6RFN PR6~I(I /.... ,that it Is not a La'1d Survey Plat or Improvement Survey'Plllt, atlU'rrl'al: it is ~ot to be relied u on for the estab ishrnent of fence, building, or\other futuro i'nprovement lines. I further certify t1l" I t)e irnprovemenL on the above d,iscribed parcol on this date, e~cept utility connections, are entirely within tlm boundar es of tho pm cel, oxcept as sllown; that [hero are no encroacl)men'fS upon the described premises by improvements on , ny ~djojning premis S, except as indicatecl, and that there is no apparent ,evidence or sign of any easement crossing or burdeni/l.J an~art of said pa .eel, except as noted. i ~l\II11:II!II' J "NOTICE: According to Colm'ado law you '" mt co mence an',' ieq, I aclion I"W~I'J\ '?\"liVty dl>foct In 'his Su<vey w,lhln ""ee ,\'a'5 ofter you rust cliscovrw .~uch defect. In no event, may any .lction bi}sed upon ,lily c feef in Uil~'6i ~tJd c6t/lpiat;ced more lIlan ton yoa,-s frlxn the dale of tile cmtificnlion S/lOWIl hereon." ~.:, '\'.' -r A, . '... t_,"') '-;'~ I ' '{' \ 1\1 I' Jr.,'..- .~ .:::::; .'\.', . I", (",,(-< ~ II is my in(erprelalion thai the above described ,. .) .~l) _{ )..~ (? . proporty /<5."'.=____ n localed ",Ulin a 10(. , ) , ,~: / year ncxxl haulId boundary based on Feder31 ~_.. ~I ',>--0 12.11.<;~ Ernerqenc.y Management Agency Ffood fnsuljl9CE . ROICMilpS Oled_j.51.52:,__~,,-::, 4_<.... Rober-t E. Pory~;~, 15321 or,.~" )"rt M. Hayden, L.S. 27268 "5u~~ . up' 'J "' _ ' ,-> OVV/~rJ'() ";. I""........ ~'~> ..'~'- '/,z ,;4' III . '\ \\ ..'.,' I~'i( 'I - .,\ \ .S.,' 11';li';l11\',,\\ DEPARTMENT OF PLANNI~G AND DEVELOPMENT Building Permit Number: BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE Date: I d.-'S . Cf9 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 Property Owner: Property Address: Contractor License No. : Company: S"u'3 f'lrJ (Y\A L.tE 0 :3 0 .,)~ l.- 0Cj.QlLST IS~'~ we.STS;cle c--r, Phone: :30'3 -..). 7'-1-"1710 I //eo.0jJ~ <JA/c. Phone: 3 0 3- '-I1oC; . 'IS (Y7 OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT d.-90() ~.~ 8'3 JS Construction Value: I hereby certify that the setback distances proposed by this permit application are accurate, Permit Fee: and do not violate applicable ordinances. rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record: that all measurements shown, and allegations Plan Review Fee: made are accurate; that I have read and agree to abide by all conditions printed on this application, and that I assume full responsibility for compliance with the Wheat Ridge Building Use Tax: \.1 :2, 50 Code (U.B.C.) and all other applicable Wheat Ridge ordinances, for work under this permit. J (OWNER)(CONTRACTOR,)SIGNED~Y)AL1r~ krg~ DATEJ,:).-'/~g '" v.1-;:,C\~t~ Tolal: .lllr~~;5:' D 't' "'euhc,,- eXI5'I'NQ r'-dtJo.cC";,W. rAh!Je~'JJ GO,uee 0- '-1~,C0 v escnp Ion: '1'< r I BUILDING DEPARTMENT USE ONLY Zl>II~~mm!!.n~ Approval: Zoning: BmlCl!n!l1..Qomm:en~ Approv~l: SIC: Sq. Fl.: . RDP~~CJ.~PI)1[IJ~"~ Approval: Occupancy: Walls: Roof: Stories: Residential Units: Electrical License No : Company: Plumbing License No : Company: Mechanical License No: 19'1? 1<-1 Company: Expiration Date: Approval: III G' -l~lill.:;c,!, Expiration Date: Approval : . Expiration Date: Approval: '" tY' 'Wj.{j,J . '" tlJ.hl ;'Qlill0D . (4) (5) (6) This permit was issued in accordance with the provisions set forth in yopur applic:ation and Is subject to the laws of the Slale of Colorado and to the Zoning Regulations and Building Code of Wheat Ridge, Coiorado Of any other applicable ontinanees of the City. This permit shall expire If (A) the work authonl.ed is not commenced within sixty (80) days from issue date or (8) the building authorized is suspended or abandoned for a period of 120 days. . If this permit expires, a new permIt may be acquired for a fee of one--half the amount normally required, provided no changes have been or will be made In the original plans and specific:ations and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. No work of any manner shall be done that will change the natural flow of water causin~ a drainage problem. Contractor shall notify the Building Inspector twenty.four (24) hours in advance for all Inspections and shall receive written approval on Inspection card before proceediing with successive phases 0' the/'ob. . . . The issuance of a permit or the approval 0 drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation of the proVISIonS of the building codes or any other ordinance, law, rule or regulation. (I) (2) (3) Chief Building Inspector For Mayor THIS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MA VOR CALL: 234-593324 HOURS PRIOR TO INSPECTION . DEPARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number: . BUILDING INSPECTION LINE - 303-234-5933 CITY OF WHEAT RIDGE Date: 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 - (303-235-2855) 9898 12/9/99 Property Owner: Property Address: 3032 INGALLS CT Contractor License No. : 19814 Company: Westside Heating and Air Conditioning Inc OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Phone: 274-4761 Phone: 469-4507 Construction Value: Permit Fee: Plan Review Fee: Use Tax: I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application, and that I assume full responsibility for compliance with the Wheat Ridge Building Code (U.B.C.) and all other applicable Wheat Ridge ordinances, for work under this permit. (OWNER)(CONTRACTOR) SIGNED DATE Total: Use: Description: Replace existing furnaces with new furnaces, 60,000 btu and 45,000 btu BUILDING DEPARTMENT USE ONLY .i 1,J!, IJIIWII.~. Approval: Zoning: SIC: Sq.Ft. : .--. Approvai : Approval: Occupancy: Walls: Roof: Stories: Residential Units: Electrical License No : Company: Mechanical License No : Company: Plumbing License No : Company: Expiration Date: Approval: Expiration Date: Approval: Expiration Date: Approval: $2,900.00 $83.25 $0.00 $43.50 $126.75 This permit was issued in accordance with the provisions set forth in yopur application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Gode of Wheat Ridge, Colorado or any other applicable ordinances of the City. This permit shall expire if (A) the work authorized is not commenced within sixty (60) days from issue date or (8) the building authorized is suspended or abandoned for a period of 120 days. If this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been o~ will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. No work of any manner shall be done that will change the natural flow of water causing a drainage problem. Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceediing with successive phases of the job. The issuance of a permit or the approval of drawings and speCifications shall not be construed to be a permit for, nor an approval of, any violation of the provisions of the buildin des or any other ordinance, law, rule or regulation. (1) (2) (3) (4) (5) (6) Chie ~~",~cc,.Jl!!C~1~'''''~''''':?'?1"""'''"''''''_P~'''CC.''"",~,,",,,""""'1~1'~C""'",C,?"I"""",...,~,,,,,,,,~,~,,,,,~,,,,,~""',"1"1.""'" ~,. btE~AR""NT OF PLANNING AND DEVELOPMENT Building Permit Number: 5535 StJILDINGINSPECTIO~ DIVISION. 235.2855 qtTY OF WKEATRIDGE Date: 7/28/97 1eiOClWE$T 29TH AVENUE ~TRlDGe,CO 80215 Property Owner: Property Address: 3032 INGALLS CT ContractOr LiCense No. : Company: phone: Phone: . OWNERlCONTRAcrOR SIGNATURE OF UNDERSTANDING AND AGREeMENT I hereby ..r\ifY lhattlle Qtbaek!listanees proposed by this pennK applk;atlon are accurate. and do nolvloltte 8PPIicabl8 orllllulnees, rulaS or regulallons of the City of Wheat Ridge or covenants. .asemsills orl8Sl/ldiOlls of rocon:l; that all,""",urements .hown, and allegations made a.. _urate; the. lllle.......ar\<lavree to. . abide by all cond~lon. printed on this appllcatlon, and thet t.........fuU ","pilnslbllllY for compllanelt with the Wheat Ridge Ill.rildlng =:~~;:=:::~~I::~~~i\~ Description: 4' FENCE Total: $1;000.00 $35.75 $0.00 $20.00 $55.75 Construction Value . Permit Fee : Plan Review Fee : Use Tax: BUILDING DEPARTMENT OSE ONLY SIC: Sq. Ft. : 4' FENCE MUST REMAIN OUTSIDE OF SIGHT DISTANCE TRIANGLE (25' X 25') otl CORNER OF PROPERTY Approval: Occupancy: WaDs: Roof: Stories: Residential Units: Plumbing License No : Company: Mechanical License No : Company: Electrical License No : Company : Expiration Date: Approval: . Expiration Date: Approval: . Expiration Date : Approval: . (1) this _It was...... ii,........nce _11\0 pIOYia\Ol1S set lcI1h in yopur application and Is s_ to thO _ olll\O S1ll1OqI CoIcxadO'" to 1ho Zoning ~_s...IIlllIdInQ~ 01_ _. COlorado or any _aoollcablo onIinanQes 01 thO CIty. (2) 'fhIl~. iIIllIlI'oXplnl' (Aj1ho ~ _ ia not CO/l1IIlllIlC8C wllhm Bixty (60) c!ayllrom IBaue dale or (8) IhO bulkflllll_1s suapanded or ~for.JlllitodoU=~' .. (3) Wthis~..OllPi*. . ...... may be aoquiIaOfOr a feeol_1hO amount l1Offl1lliIy requinld, _ no changes '- been orwiR be_In IhO orlgInjI ~........ .__. lindany.- or abandonment has not_ona (1) yNr. lfchangeo'" _or ,_or aba/1dorU1lenI _sona(ljye8r.lUII__l>ejloll<ffora_- (<lj 110 Wl>ll<ol~mOnr\af""Rbo_lI\aI wiUehange lhe nei1lnllllowofwa1sr<:aUBing a -.go~. (5)~'t#~~:='~'t,1wanly.lour(24) hours lnadvancelorallli1specllona snd_ __ opPnMIOll ~oard__ (8) olssU8nCe llflloermlt ",tl1a,~ ofnwings and ..,..:IfIcalIoI1S shall not be COIlSf/UOd to be. pannIt lor. nor an ajlpl'OVOI <>I, any _0I1hO pnMBiorIS 0I1ho~-..orany ___ee,~, rule orragulation. ~ ~/<<~k (sr~ ef Building Inspector . ... THIS \>eRMIT VAI.IDQNLY WHet( SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION DEPARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number: .. BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE Date: 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215- Property Owner: Property Address: Contractor License No. : Company: \Zdo2r\C\ b~" ~'-'--"D 7:J:-.,-~7..... ~,~)..\\"':> c.. '\ - c~'t--l>----r Phone: Phone: OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Construction Value: \\\;)00 Permit Fee: Plan Review Fee: Use Tax: I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances. rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate: that I have read and agree to abide by all conditions printed on this application, and that I assume full responsibility for compliance with the Wheat Ridge Building Code (U.B.C.) and all other applicable Wheat Ridge ordinances, for work under this permit. (OWNER)(CONTRACTOR) SIGNE!J ~, , """",,,,'->--. i t.. ~ ~TE'f ) 2 '-\ \ q G Description: i...j ~\::,.\ \Aioc:.c\ \;?" ~ '\ "3;;" "-'- ,'- ~ BUILDING DEPARTMENT USE ONLY Total: Z6fii!llJ'~_oml!lents"l 7(1. ~ /1-,. Approval: 7r'- '-/ I J'IACA Zoning: "In Ii - Bml(llng~!:tol:l1mentS:] --\1'l.M:~ Approval: p-'nlil~kSl.l,;;omm~!)~ Approval: SIC: Sq. Ft. : l'vf.,tPrr I~<<M-- (~c/ns') ~ ~~k '2 ~ cltd' (~ ~~~. Occupancy: Walls: Roof: Stories: Residential Units: Electrical License No : Company: Plumbing License No : Company: Mechanical License No : Company: Expiration Date: Approval: fill !!i!!l!~~"'!@_ Expiration Date: Approval: \I ~llflfI'..B.!ql!~c!BI1 Expiration Date: Approval: . ~Blrn!f.@__ (4) (5) 16) This permit was Issued in accordance with the provisions set forth in yopur application and Is subject to the laws of the State of Cobrado and to the Zoning Regulations and Building Code ot YVheat Rid~e, Colorado or any other applicable on:finances of the City. This permit shall expire If (A) the work authonzed is not commenced within sixty (60) days from issue date or (B) the building authorized is suspended or abandoned to( a period ot 120 days. . If this permit expires, a new permIt may be acquired for a tee of one.half the amount normally required, provided no changes have been or will be made in the original plans and Specifications and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment exceeds one (1) year. full fees shall be paid tor a new permit No work of any manner shall be done that will change the nalural flow of water causing a drainage problem. Contractor shall notify the Building Inspector twenly.four (24) hours in advance for aU inspections and shall receive written approval on inspection card before proce . g WIth successive phases of the/.ob. The i u ce of a permit or the approval 0 drawings and specifications shall not be construed to be a pennit for, nor an approval of, any violation of the provisions of t b din es or any other inance, law, rule or regulation. (I) (2) (3) C For Mayor THIS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION "ifIt DArE 12/14/93 FEE 80'.00 Jos# 93-20548 MORTGAGE CO. KAREN PRASKI AODRESS- 3032 INGALLS CT. BORRO""'RS NAME MAURO -------,.. I . LAND SURVEYING 5460 WARD ROAD. SUrrE 160 ARVADA, COL..RA,OO 80002 .(303) 420~4788 1M PROVEM ENT .LOCATION C ERTI FICATE Attn: SHARON ~ LEGAL DESCRIPTION lPEfl CLIENT) ~OT 5, BLOCK 3~ STEBBINS SUB., ~ COUNTY OF JEFFtRSON, STATE OF COLORADO L _Sc.ALf."/": ZO' P:J I .' "', ... \ /~~ G'~' "~"-'7...' /' '" / / , /'<''' S , '/ ()~,~' . -- ~', I % I . .~ I //-<,/0)(\ . /:::\--2-_, '---_:i/ / c.' \\ '~/.../ T, ", / /'-" \\ /...'" / ' \ \ / / I.iI \ / ... , I . , ,<: <,' I If // ,~.~ .,,:, /' C':'N'- " \ &0' rfY 0, I \<fJ /' ,_D~,,,E.. \ I~ 0"vJ ft:1." '<f .J--W<(/ . \~~Q'<F / ~-./ 1.'2..,' o o o '" S~la.. Q .q-_~e. III '\ 'p '-'2.,,' .... .,. ;-11 ~ \ \ , / 1/ / " I I I 1 IV -: 0 -: '" 0 () ~ 1]\ .. I\l III lit, o ,j MI.. ~,~ ~-{: , ," ." "', ".-.- --,- On tl1e basis of my knowledge, informatIon and beji~f, I hereby certifYt~at this Imp~vement location certfflca~~"Wl;iS prepared for' / i ,that ~ Is not a L8l1,d SUrvey Plat or Improvement Surve~m~aRB1R~lt Is ~ot to be relied u on for the ests ,Ishment of fence. building, Or\,other future improvement lines. I further certify that t e improvement on the above described parcel on this date, e,?<cept utility connections. are entirely within the boundar es of the parcel, except as shown;' that there are no encroachments upon the described premises by improvements on .. flY djoining pramls 5, except as indicated, and that there is no apparent ~vldence or sign ,of any easement crossing or burdenil1 J an part of said pa eel, except as t")oted. i 1\\'\\\I\\;/II/jj," I "NOTICE: According to Colorado law you m 1St co mence any leg I action bi;\~ rHJ1lY 'Il!?t in this survey within three >/ears after you first discover such defect. In no event, may any .lctfon b d upon .1ny feet In C~ lH b ~t)y,ed more than ten years :>m the date of the certincation shown hereon." ,.::' ....' 1 lv' .. .... ~1>. ~ ~," ,~."(5, . 1f..1)~...~ ., .(JoV .." ~ __ '.l..,...,) ().::;. - ",) 1"''' to:. '" 'Z".= / "',:: :>-~ t2.lq.'i~ Robert E. por; ~'\l. 1 21 or . 'rt M. Hayden, L.S. 27268 ~;\J>>... ....,~!:/' '" ,~/ . .. ..'J ,-....:. . ( (J. , -. ~ ' '//111/11" A l I ~ l\ t\ ~, s::/~., '("It/liI'\I\\\\\\' It is my interpretation that the above described property he; ,...o~ located Vvithin a 100 year flood hazard boundary based on Federal Emergency Management /vger<;y Flood Insu'PJlC'l Rale M"%ated 1'3.1i~ ,;:lC-:,.;;,. <- g.5U7S Oc>.llCeJd) DEPARTMENT OF PLANNING AND DEVELOPMENT BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 Building Permit Number: 95-1191 Date: 6/13/95 Property Owner: MAURO ROBERT H Property Address: 3032 INGALLS CT Contractor License No.: 18271 Company: CENTENNIAL ROOFING Phone: 447-2020 Phone: 238-5557 OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Construction Value: Permit Fee: Use Tax: $2,720.00 $54.00 $40.80 I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application, and that I assume full responsi . ity for camp h the Wheat Ridge Building Code (U.B.C.) and all other applicable t ~idge or . ances, fur work under this permit. (OWNER)(CO~CTOR) SIGNE[f . ~-ec; DATE~ ~ Description: REROOF Total: $94.80 BUILDING DEPARTMENT USE ONLY Approval: Zoning: Approval: Occupancy: Walls: Roof: Stories: Residential Units: Electrical License No : Company: Plumbing License No : Company: Mechanical License No : Company: Expiration Date: Approval: Expiration Date: Approval: Expiration Date: Approval: . . . (1) (2) (3) This permit was issued in accordance with the provisions set forth in yopur application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Code of Wheat Ridge, Colorado or any other applicable ordinances of the City. This permit shall expire if (A) the work authorized is not commenced within sixty (60) days from issue date or (8) the bUilding authorized is suspended or abandoned for a period of 120 days. If this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. No work of any manner shall be done that will change the natural flow of water causing a drainage problem. Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceediing with successive phases of the/'ob, The issuance of a permit or the approval 0 drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation of the provisions of the bui ing codes or any other ord' ance, aw, rule or regulation. 1 "5 ,--Or Chi uilding Inspector THIS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION (4) (5) (6) If~~~] ULI "" ""L>' I U~- f-'LANNING ANO uL:cVI::LUf-'l::MEN1 BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 Application NUflluel . Date: .6;?~J- Property Owner :/50 6 ,4t!op,z 0 Property Address: "30? Z /,.<->.;;"p c. L J C r Contractor License No.: ~ Z ? /' / Company: t?'fr,.vl",;,,",~; ,'1 L ~e/././"':' <j ./ Phone: "<:/"/7 -20 Z 0 Phone :2 f Y-SSS7 Construction Value: ?; 7 20 Permit Fee: "'if" c/ ~ OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDtNG AND AGREEMENT I hereby cert!fy that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances. rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations mad~ are accurate: that' have read and 89.ree to abide by all conditions_printed on this . application, and that I assume full responsibility for compliance with the Wheat Ridge Building Code (U,B.C,) and all other applicable WIle Ridge ordinance, r work under this permit. ~<" /J~ p "'DATEf1~,4f "'-.4-.4 ~~i.. 6-C,,.-.,'.?4J 32 ./ Use Tax: '/), ^ ~:;I c~ c.. V . c; ~;. Total: (OWNER)(CONTRACTOR) SIGNED - Description A'f"J /~ , / >;'J '" BUILDING DEPARTMENT USE ONLY tm:!J.i)l'l~,Q.m.l:1,1!ln~; Approval: Zoning: Rilll(linr".Co........-nts.:. liiiaL~li:e~\r..~~ Approval' r,f!P.J!"lK'{!1!,I5~;2,<i,!l1l!Xtn.t~!;l Approval: Occupancy: Walls: Roof:.".,...- Stories: Residential Units : Electrical License No : Company. Plumbing License No : Company: Mechanical License No : Company: Expiration Date: Approval ~ ~f'lal)s;Re.g011elt-.. Expiration Date: Approval : Expiration Date Approval . iW ml;insSeqlilre,<!.B II .:lIlL' ;'i.:)'(~lIf.: ~r (') (5) (6) This permit was ISSUed in accordance with the provisions set forth in yopur application and is subject to the lawS oIlhe State 01 ~ and to the Zoning R~ulalloos and Buddln9 Code at Vv'heat Ridge. Colorado or any other applicable ordinances at the City. ThIs pe/mlt shall expire If (A) the work authOriZed IS not commenced within sixty (60) days from issue dale or (8) the building authorized is suspended or abandoned 10f a period of 120 days. II this permll expires. a new permit may be acquired lor a lee of one-half the amount normafty' required. provided no changeS have been or will be made in the onglOal plans and specifications and any suspension or abandonment has not exceeded one (1) year. .. changeS are made or if suspension or abanCSor'\rnerll exceeds one (1) year. full fees shall be paid for a new permIt No work of any manner shall be done that wiU change the naturalllow of water causing a drainage problem. . Conll ;Jr.;101 shall notlly the Building Inspector twenty-fOUl (241 hours in advance ror an inspections and shaI receive written approval on InspeCtiOn card before pfOcc<.>uung Wllh succeSSive phases of the iob.. . . - . The ISSUdllce 01 a permit ()( the approval of drawings and speCIfIcations shall not be construed 10 be a pennit for. nof an approvat of. any violation 01 the provrSlOl'lS oll1l{~ lllJrl'j"Hj codes or any other ordinance. law. rule or regulatiOn (I) (2) (3) ChI( . l1"II(j[('g Inspector For Mayor THIS PFf<MIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION Occupancy/Type aosl_ 113q,NSPE C 1 O N R CORD INSPECTION REQUEST LINE: (303) 234-5933 Inspections will not be performed unless this card is posted on the project site. Call the inspection request line before 11:59 p.m. to receive an inspection the following business day.** Inspector Must Sign ALL Spaces pertinent to this project Foundation Inspections Date Inspector Comments Initials Pier Concrete Encased Ground (CEG) Foundation / P.E. Letter Do Not Pour Concrete Prior To Approval Of The Above Inspections Underground/Slab Inspections Date Inspector Initials Comments Electrical Comments Sewer Service Plumbing Inspections from these entities should be requested one week in advance. For landscaping and parking inspections call 303-235-2846. For ROW and drainage inspections call 303-235-2861. For fire inspections contact the Fire Protection District for your project. Do Not Cover Underground or Below/In-Slab Work Prior To Approval Of The Above Inspections Rough Inspections Date Inspector Initials Comments Wall Sheathing Inspections from these entities should be requested one week in advance. For landscaping and parking inspections call 303-235-2846. For ROW and drainage inspections call 303-235-2861. For fire inspections contact the Fire Protection District for your project. Mid -Roof 0 7 Floodplain Inspection (if applicable) Lath / Wall Tie Fire Inspection / Fire Protection Dist. Rough Electric' Final Electrical Rough Plumbing/Gas Line Final Plumbing Rough Mechanical Final Mechanical Rough Framing Roof ( �, Rough Grading Final Window/Doors Insulation Final Building Drywall Screw /Nail NOTE: All items must be completed and approved by Planning, Public Works, Fire and Building before a Certificate of Occupancy is issued. Approval of the Final Building inspection does not constitute authorization of occupancy. Final Inspections Date Inspector Initials Comments Landscaping & Parking / Planning Dept. Inspections from these entities should be requested one week in advance. For landscaping and parking inspections call 303-235-2846. For ROW and drainage inspections call 303-235-2861. For fire inspections contact the Fire Protection District for your project. ROW & Drainage / Public Works Dept. Floodplain Inspection (if applicable) Fire Inspection / Fire Protection Dist. Final Electrical Final Plumbing Final Mechanical Roof ( �, Final Window/Doors Final Building NOTE: All items must be completed and approved by Planning, Public Works, Fire and Building before a Certificate of Occupancy is issued. Approval of the Final Building inspection does not constitute authorization of occupancy. *For low voltage permits — Please be sure that rough inspections are completed from the Fire District and electrical low voltage by the Building Division. **For Inspection Time Window — Please email insptimerequest@ci.wheatridge.Co.US by 8:00 A.M. the morning of the inspection with the property address in the subject line of the email. Time window is based on the inspector's route. Occupancy Is Not Permitted Until A Certificate of Occupancy Is Issued Protect This Card From The Weather z City of Wheat Ridge Residential Roofing PERMIT - 201701397 PERMIT NO: 201701397 ISSUED: 06/02/2017 JOB ADDRESS: 3032 Ingalls CT EXPIRES: 06/02/2018 JOB DESCRIPTION: Reroof 34 squares OC Dimensional asphalt shingles; 4/12 pitch; 1 layer *** CONTACTS *** OWNER (970)218-0303 CAMERON CUYLER SUB (720)810-1991 Tim Bonneville 170180 Hassle Free Contracting LLC *** PARCEL INFO *** ZONE CODE: UA / Unassigned USE: UA / Unassigned SUBDIVISION CODE: 2405 / BARTHS, COULEHAN GRANGE, WHEAT BLOCK/LOT#: 0 / *** FEE SUMMARY *** ESTIMATED PROJECT VALUATION: 8,738.00 FEES Total Valuation 0.00 Use Tax 183.50 Permit Fee 188.45 ** TOTAL ** 371.95 *** COMMENTS *** *** CONDITIONS *** Effective December 1, 2014, asphalt shingle installations require an approved midroof inspection, conducted when 25-75 percent of the roof covering is installed, prior to final approval. Installation of roof sheathing (new or overlay) requires an approved inspection prior to installation of ANY roof coverings and is require on the entire roof when spaced or board sheathing with ANY gap exceeding A1/2-inch exists. Asphalt shingles are required to be fastened to the roof deck with a minimum of 6 nails per shingle. Ice and water shield is required. Eave and rake metal is required. A ladder extending 3 feet above the roof eave and secured in place is required to be provided for all roof inspections. Roof ventilation is required to comply with applicable codes and/or manufacturer!4FIRs installation instructions, whichever is more stringent. In order to pass a final inspection of elastomeric or similar type roof coverings, a letter of inspection and approval from the manufacturer&#39;s technical representative stating that "the application of the roof at (project address) has been applied in accordance with the installation instruction for (roof material brand name) roof covering" is required to be on site at the time of final inspection.