HomeMy WebLinkAbout4050 Miller Streetr� vt q75 10/21/2020 Complete Basement Systems 11795 East 45th Ave. Denver, CO 80239 RE: Job Number 2020-8391 Site Observation Visit (Camp - 148774) 4050 Miller St. Wheat Ridge, CO 80033 OL ENGINEERING. INC 9100 W Jewell Ave Lakewood, CO 80232 720-440-9450 www.dlengineer.com DL Engineering Inc. reviewed the progress of construction for the subject project on October 20, 2020. The following is a summary of the observations made: New Observations: • Reviewed the helical piers. There were 4 piers installed on the center beam lines of the structural subfloor north wall spaced at approximately 11' o.c. o The pier spacing was observed and appears to be in conformance with the construction documents. o The piers were installed to refusal or to a depth no less than that specified in the construction documents. o The helical piers appear to be installed in conformance with the structural mitigation plan. o The mono posts were not installed due to spacing limitations in the crawlspace. This was approved by the engineer on record. • Site grading around the perimeter of the house did not appear to be modified. • Vegetation around the perimeter of the house did not appear to be modified. Volatile Soils: The moisture around the foundation elements must be controlled for the useful life of the building. Time has shown that Colorado soils can be unstable, and structures can experience damaging movements due to expanding and shrinking soils, primarily when moisture changes occur. Maintaining consistent soil moisture contents around all foundation elements is crucial to minimizing foundation movements. Even with properly engineered/constructed foundation systems these volatile soils can still exert excessive pressures causing damage in the residence. If the Owner would like further insight about the on-site soil conditions and preventative measures, a Geotechnical Engineer should be consulted. Geotechnical Consideration: It is possible that the piers may consolidate the soil under the piers. Because of this, periodic surveys of the supported structures should be conducted to assure project success. The Owner should be responsible for annual surveys certifying project success. It is recommended that a baseline survey be conducted immediately. The Owner should report all findings and reports to the Structural Engineer. If vertical movement of the foundation walls is discovered, the piers should be re -pressurized. A Geotechnical Engineer should be present for the re -pressurizing of the piers. yo.Sro A4 ,1( bad �;,4 Pei-"4;.�- aoeo r l iS ENCINEERING, INC Disclaimer: In as much as the site review of an existing structure for the purpose of observing the structure conditions requires that certain assumptions be made regarding existing conditions and because some of these assumptions may not be verifiable without expending additional sums of money or destroying otherwise adequate or serviceable portions of the building, the Client agrees that, except for negligence on the part of the Engineer, the Client will hold harmless, indemnify and defend Engineer from and against any and all claims arising out of the professional services we have provided. If you should have any further questions, please feel free to contact me at (720) 440-9450 or gpalmieri@dlengineer.com. Sincerely, Giovanni Palmieri, EI Under the direct supervision of, Jim Slama, PE JAMES N ON: CN=.TAMES NJ SLAMA_StAMA E=JSLAMA@ DLENGI NEER.COM SLA Reason 1 the author of this tlocumenf Location: Data: 2020- '12 0048580 SCA) 2 � ► � i City of Wheat Ridge Residential Foundation Repair PERMIT - 202001975 PERMIT NO: 202001975 ISSUED: 10/02/2020 JOB ADDRESS: 4050 Miller St EXPIRES: 10/02/2021 JOB DESCRIPTION: Interior, Install (4) helical piers with pier caps and (4) new mono posts at the center beam lines. *** CONTACTS *** OWNER (303)870-2170 CAMP EDWARD JOYCE SUB (303)805-8751 RODNEY MARTIN 060125 COMPLETE BASEMENT SYSTEMS *** PARCEL INFO *** ZONE CODE: UA / Unassigned USE: UA / Unassigned SUBDIVISION CODE: UA / Unassigned BLOCK/LOT#: 0 / *** FEE SUMMARY *** ESTIMATED PROJECT VALUATION: 61400.00 FEES Total Valuation 0.00 Plan Review Fee 101.89 Use Tax 134.40 Permit Fee 156.75 ** TOTAL ** 393.04 *** COMMENTS *** *** CONDITIONS *** A printed copy of the permit and city stamped on-site plans must be available on-site for the first inspection. Approved per plans and red -line notes on plans. Must comply with 2018 IRC, 2020 NEC and all applicable City of Wheat Ridge Municipal Codes. Work is subject to field inspections. Inspection by Wheat Ridge Building Inspector required prior to backfill. Observation letter from Engineer to be provided to Wheat Ridge Building Inspector at Final Inspection. 1* � � i City of Wheat Ridge Residential Foundation Repair PERMIT - 202001975 PERMIT NO: 202001975 ISSUED: 10/02/2020 JOB ADDRESS: 4050 Miller St EXPIRES: 10/02/2021 JOB DESCRIPTION: Interior, Install (4) helical piers with pier caps and (4) new mono posts at the center beam lines. I, by my signature, do hereby attest that the work to be performed shall comply with all accompanying approved plans and specifications, applicable building codes, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with this�permrt. I further attest that I am leg ally authorized to include all entities named within this document as parties to the work to be performed and that all work to be performed is disclosed in this document and/or its' accompanying approved plans and specifications. Signature of OWNER or CONTRACTOR (Circle one) Date 1, This permit was issued based on the information provided in the permit application and accompanying plans and specifications and is subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures. 2. This.permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and received prior to the date of expiration. An extension of no more than 180, days made be granted at the discretion of the Chief Building Official and may be subject to a fee equal to one-half of the original permit fee. 3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard requirements, fees and��procedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of the Chief Building Official and is not guaranteed. 4. No work of any manner shall be performed that shall results in a change of the natural flow of water without prior and specific approval. 5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all requ�ired inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services Division. 6. The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, anviolation of any provision of any applicable code or any ordinance or regulation of this jurisdiction. Approval of work is subject to field inspection. Signature of Chief Building Official Date REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: F / G F IN Job Address: `/ O S a /" %v -e r` .S Permit Number: "2.C72!0 o/ '`� 7__�; ❑ No one available for inspection: Time lz2/ 10 ,IMYPM Re -Inspection required: Yes, *When corrections have been made, schedule for re -inspection online at: http✓/www. ci, wheatridge, co. uslinspection Date: A0 -71-70e'O Inspector: SLS DO NOT REMOVE THIS NOTICE no change to valuation From: no-reolv(alci.wheatridae.m. us To: CommDev Perm is Subject: Online Form Submittal: Foundation Repair Date: Thursday, October 1, 2020 8:55:40 AM Foundation Repair This application is exclusively for FOUNDATION REPAIRS. YOU MUST ATTACH A VALID ELECTRONIC PAYMENT ORM IN ORDER FOR THE PERMIT TO BE PROCESSED. Your Permit will be emailed to the email address provided below once it is processed. THIS APPLICATION DOES NOT CONSTITUTE A PERMIT. DO NOT BEGIN WORK UNTIL PERMIT HAS BEEN ISSUED. Is this application for a Yes Foundation Repair? PROPERTY INFORMATION Property Address 4050 Miller Street Property Owner Name Camp, Edward Joyce Property Owner Phone Number (enter WITH dashes, eg 303-123- 4567) Property Owner Email Address Attach City of Wheat Ridge Electronic Payment Form - "DO NOT ATTACH A PICTURE OF A CREDIT CARD" (303) 870-2170 ecamp80l9@aol.com Wheat Ridae Payment Form.Ddf CONTRACTOR INFORMATION Contractor Business Name Wheat Ridge Contractor's License Number (This is a 5 or 6 digit number for the Complete Basement Systems - Greg Knapp 60125 City of Wheat Ridge) Contractor Phone Number (enter WITH dashes, eg 303-123- 4567) Contractor Email Address 720-507-2711 cbs.permits@completebasementsystems.net Retype Contractor cbs.permits@completebasementsystems.net Email Address DESCRIPTION OF WORK Location of Work Interior, Install (4) helical piers with pier caps and (4) new mono posts at the center beam lines How is repair being helical piers done? Piers, strips, etc. # of Piers or Strips 4 Upload engineer letter Observation Letter 4050 MillerSt.ndf or pages on 8 1/2" x 11" only Repair Plan Set on Plans 4050 Miller St ndf 11'x17" only - if applicable Project Value (contract 6400 ok 10/02/2020 bf value or cost of ALL materials and labor) SIGNATURE OF UNDERSTANDING AND AGREEMENT I assume full Yes responsibility for compliance with applicable City of Wheat Ridge codes and ordinances for work under any permit issued based on this application. I understand that work Yes may not begin on this property until a permit has been issued and posted on the property. I certify that I have Yes been authorized by the legal owner of the property to submit this application and to perform the work described above. Person Applying for COMPLETE BASEMENT SYSTEMS INC Permit I attest that everything Yes stated in this application is true and correct and that falsifying information in this application is an act of fraud and may be punishable by fine, imprisonment, or both. Email not displaying correctly? View it in your browser. INDEX: S1-1 GENERAL NOTES S1-2 GENERAL NOTES S1-3 GENERAL NOTES S14 GENERAL NOTES / LEGEND S2-1 FOUNDATION PLAN S3-1 TYP. HELICAL PIER AND MONO POST DETAIL BUILDER INFORMATION: Complete Basement Systems 11795 East 45th Ave. Denver, CO 80239 720-487-9568 Scope of Work - 1 . ork:1. Install (4) new helical piers with pier caps and (4) new mono posts at the center beam lines of the structural subfloor to support the main steel beams. General Notes: 1. Construction documents are valid for a single use at the project location and shall not be reused, copied, or reproduced without written approval of the registered design professional in reasonable charge. 2. The contractor is responsible for the methods, means and sequence of all structural erection except when specifically noted otherwise in the construction documents. The contractor shall provide temporary shoring and bracing, providing adequate vertical and lateral support during erection. Shoring and bracing shall remain in place until all permanent members are placed and all final connections are completed. 3. The contractor agrees that, in accordance with generally accepted construction practices, the contractor will be required to assume sole and complete responsibility for job site conditions during the course of construction of the project, including safety of all persons and property. This requirement shall be made to apply continuously and not be limited to normal working hours. The contractor further agrees to defend, indemnify and hold owner and engineer harmless from any and all liability, real or alleged, in connection with the performance of work on this project, exempting liability arising from the sole negligence of engineer. 4. All existing sizes, dimensions and foundation damage shall be field verified by the contractor and owner prior to construction. Discrepancies with the construction documents shall be reported to the structural engineer for additional recommendations (if any). 5. Per the owner's request, the contractor shall stabilize the structure only. No attempt shall be made to lift or plumb the foundation wall without approval for the owner and structural engineer. Field Verification: 1. Contractor and Owner shall thoroughly inspect and survey existing structure to verify dimensions, elevations, framing, etc. which affect the work shown on the drawings. 2. Report any variation or discrepancies to the structural engineer before work proceeding. Design Criteria: DATE: JOB #: DL ENGINEERING INC. 2. 9/30/2020 2020-8391 9100 W. JEWELL AVENUE FOUNDATION STABILIZATION AT 2.2. Floor 12psf 2.3. LAKEWOOD, CO 80232 4050 MILLER ST. REVISION DATE: PAGE OF 720-440-9450 WHEAT RIDGE, CO 80033 S1-1 6 BY: CHECKED BY: WWW.DLENGINEER.COM OWNER: CAMP (148774) 4.1. Ground/Snow snow load 30psf GP JS INDEX: S1-1 GENERAL NOTES S1-2 GENERAL NOTES S1-3 GENERAL NOTES S14 GENERAL NOTES / LEGEND S2-1 FOUNDATION PLAN S3-1 TYP. HELICAL PIER AND MONO POST DETAIL BUILDER INFORMATION: Complete Basement Systems 11795 East 45th Ave. Denver, CO 80239 720-487-9568 Scope of Work - 1 . ork:1. Install (4) new helical piers with pier caps and (4) new mono posts at the center beam lines of the structural subfloor to support the main steel beams. General Notes: 1. Construction documents are valid for a single use at the project location and shall not be reused, copied, or reproduced without written approval of the registered design professional in reasonable charge. 2. The contractor is responsible for the methods, means and sequence of all structural erection except when specifically noted otherwise in the construction documents. The contractor shall provide temporary shoring and bracing, providing adequate vertical and lateral support during erection. Shoring and bracing shall remain in place until all permanent members are placed and all final connections are completed. 3. The contractor agrees that, in accordance with generally accepted construction practices, the contractor will be required to assume sole and complete responsibility for job site conditions during the course of construction of the project, including safety of all persons and property. This requirement shall be made to apply continuously and not be limited to normal working hours. The contractor further agrees to defend, indemnify and hold owner and engineer harmless from any and all liability, real or alleged, in connection with the performance of work on this project, exempting liability arising from the sole negligence of engineer. 4. All existing sizes, dimensions and foundation damage shall be field verified by the contractor and owner prior to construction. Discrepancies with the construction documents shall be reported to the structural engineer for additional recommendations (if any). 5. Per the owner's request, the contractor shall stabilize the structure only. No attempt shall be made to lift or plumb the foundation wall without approval for the owner and structural engineer. Field Verification: 1. Contractor and Owner shall thoroughly inspect and survey existing structure to verify dimensions, elevations, framing, etc. which affect the work shown on the drawings. 2. Report any variation or discrepancies to the structural engineer before work proceeding. Design Criteria: 1. Building code: 2018 IBC, 2018 IRC with City of Wheat Ridge Amendments 2. Dead loads 2.1. Roof 20psf 2.2. Floor 12psf 2.3. Walls 10psf 3. Live loads 3.1. Residential40psf 3.2. Roof 20psf 4. Snow loads 4.1. Ground/Snow snow load 30psf N00 LIC 5. Wind loads 5.1 ►d Exposure Category C v : : O 5.2 135 mph Ultimate Wind Speed Wheat Ridge �� 0048580 6. Seismic Loads Building 6.1 Seismic Design Category: B I�'�<v� 6.2 Site Class: "D" per USGS ONAL 7. Soil Bearing Capacity = 1,500 psf (assumed) Foundation Design: 1. Soil conditions and types shall be verified by a Engineer during excavation. 2. All helical piles, push piers, helical anchor tiebacks, wall anchor tiebacks and connection hardware shall be designed and installed by supplier, such that they provide the minimum allowable capacities as indicated on the drawings. All capacities shown on the drawings are unfactored service loads and have not been reduced for live load reductions. 3. Design of individual and continuous footings is based on an assumed maximum allowable bearing pressure of 1500 lbs. per square foot (dead load plus full live load), placed on the natural undisturbed soil, or compacted structural fill below frost depth. STEEL HELICAL PIERS: 1. Grip Tlte: Model GTRDS2875-0203 (round shaft) Helical Pier with FP3BA Retrofit Bracket 2. Install with Pro -Dig X9 torque head to a maximum of 4,800 ft -lbs torque. 3.. Pier depth is dependent on depth of bearing soil adequate to provide the specified torque resistance, therefore, depth is not specified. Pier to be advanced until torque is attained. 4. Installation torque serves as empirical verifications of pier capacity, yielding an onsite load test for each pier. Therefore, soils testing is not necessary for generating a theoretical capacity. 5. Piers shall be 8" minimum helical piers, installed at locations shown on the plans. 6. It is assumed the each new pier will achieve penetration into bedrock or competent soil, and can be installed to the specified capacity. Should bedrock or competent soil not be reached within reasonable depth this office should be notified for further instructions. 7. Contractor is to maintain accurate pier depth and pressure / torque charts for each pier, showing depth and pressure / torque at each shaft section. Charts shall be filled out in real time during installation, and maintained onsite for engineer review during inspection. Charts shall be provided to engineer in final form upon completion. Special Inspections 1. Special inspections shall be provided per the requirements in the UES Evaluation Report #391, Section 3.3 as well as the requirements of the 2018 IBC Section 1705.9. Cast -in -Place Concrete oWheatRidge 1. All concrete design is based on the "Building Code requirements for Reinforced Concrete" (ACI 318-05/3181 All structural concrete shall have a minimum 28 -day compressive strength as follows: 1.1 Footings: 3,000psi 1.2 Slab on Grade: 3,500psi 1.3 Foundation walls: 3,000psi 2. Concrete shall be placed on proportioned utilizing Type 1 cement except, concrete exposed directly to soil shall use Type 2 cement. Concrete susceptible to freeze shall be formulated or maximum frost resistance in accordance with the ACI manual of Concrete Practice. 3. Cold weather and or hot weather placing procedures shall be provided, if conditions warrant, as recommended in the ACI manual of Concrete practice. Reinforcing Steel: 1. All detailing, fabrication, and placement of reinforcing steel shall be in accordance with the ACI Manual of Concrete Practice. 2. Reinforcing bars shall conform to ASTM A615-79 and shall be grade 60. 3. Except as noted on the drawings, minimum concrete protection for reinforcing shall be in accordance with ACI 318-05/318R-05. 4. No. 5 or larger reinforcing bars shall not be re-bent. 5. Welding of rebar is not permitted unless procedure is approved by the Structural Engineer. O N. SZ*. 7, 0048580 DATE: JOB #: DL ENGINEERING INC. 9/30/2020 2020-8391 9100 W. JEWELL AVENUE FOUNDATION STABILIZATION AT LAKEWOOD, CO 80232 4050 MILLER ST. REVISION DATE: PAGE OF 720-440-9450 WHEAT RIDGE, CO 80033 S1-2 6 BY: CHECKED BY: WWW.DLENGINEER.COM OWNER: CAMP (148774) GP JS Foundation Design: 1. Soil conditions and types shall be verified by a Engineer during excavation. 2. All helical piles, push piers, helical anchor tiebacks, wall anchor tiebacks and connection hardware shall be designed and installed by supplier, such that they provide the minimum allowable capacities as indicated on the drawings. All capacities shown on the drawings are unfactored service loads and have not been reduced for live load reductions. 3. Design of individual and continuous footings is based on an assumed maximum allowable bearing pressure of 1500 lbs. per square foot (dead load plus full live load), placed on the natural undisturbed soil, or compacted structural fill below frost depth. STEEL HELICAL PIERS: 1. Grip Tlte: Model GTRDS2875-0203 (round shaft) Helical Pier with FP3BA Retrofit Bracket 2. Install with Pro -Dig X9 torque head to a maximum of 4,800 ft -lbs torque. 3.. Pier depth is dependent on depth of bearing soil adequate to provide the specified torque resistance, therefore, depth is not specified. Pier to be advanced until torque is attained. 4. Installation torque serves as empirical verifications of pier capacity, yielding an onsite load test for each pier. Therefore, soils testing is not necessary for generating a theoretical capacity. 5. Piers shall be 8" minimum helical piers, installed at locations shown on the plans. 6. It is assumed the each new pier will achieve penetration into bedrock or competent soil, and can be installed to the specified capacity. Should bedrock or competent soil not be reached within reasonable depth this office should be notified for further instructions. 7. Contractor is to maintain accurate pier depth and pressure / torque charts for each pier, showing depth and pressure / torque at each shaft section. Charts shall be filled out in real time during installation, and maintained onsite for engineer review during inspection. Charts shall be provided to engineer in final form upon completion. Special Inspections 1. Special inspections shall be provided per the requirements in the UES Evaluation Report #391, Section 3.3 as well as the requirements of the 2018 IBC Section 1705.9. Cast -in -Place Concrete oWheatRidge 1. All concrete design is based on the "Building Code requirements for Reinforced Concrete" (ACI 318-05/3181 All structural concrete shall have a minimum 28 -day compressive strength as follows: 1.1 Footings: 3,000psi 1.2 Slab on Grade: 3,500psi 1.3 Foundation walls: 3,000psi 2. Concrete shall be placed on proportioned utilizing Type 1 cement except, concrete exposed directly to soil shall use Type 2 cement. Concrete susceptible to freeze shall be formulated or maximum frost resistance in accordance with the ACI manual of Concrete Practice. 3. Cold weather and or hot weather placing procedures shall be provided, if conditions warrant, as recommended in the ACI manual of Concrete practice. Reinforcing Steel: 1. All detailing, fabrication, and placement of reinforcing steel shall be in accordance with the ACI Manual of Concrete Practice. 2. Reinforcing bars shall conform to ASTM A615-79 and shall be grade 60. 3. Except as noted on the drawings, minimum concrete protection for reinforcing shall be in accordance with ACI 318-05/318R-05. 4. No. 5 or larger reinforcing bars shall not be re-bent. 5. Welding of rebar is not permitted unless procedure is approved by the Structural Engineer. O N. SZ*. 7, 0048580 Structural Steel: 1. Structural Steel shall be detailed, fabricated and erected in accordance with 2010 AISC Specification for Structural Steel Buildings, and "Code of Standard Practices" 2005. 2. Structural Steel shall be confirmed to the following grades: 2.1 W- & WT- Shapes: ASTM A36, A992 2.2 Plates & Angles: A36 2.3 HSS: ASTM A500 gr B 2.4 Steel Pipe: ASTM A53 gr B 3. All bolts shall conform to the ASTM A325 except anchor bolts which shall conform to ASTM A307. Bolt Size shall be 3/", unless noted otherwise on the drawings. 4. All welding shall be by a certified welder in accordance with ACIS and AWS specifications and recommendation. Structural Wood framing: 1. Except where noted otherwise, all 2" members shall be Hem -Fir No. 2 and better. 2. Except as noted otherwise, minimum nailing shall be provided as specified in Table No 2304.9.1 "Fastening Schedule" of the IBC. All nails shall be common type, unless noted otherwise. 3. Unless noted otherwise, steel connectors such as those manufactured by Simpson Company, shall be used to join rafters, trusses, joists, or beams to other members at flush -framed conditions. Use maximum number and size of nails indicated in manufactures tables U.N.O. all nails holes shall be filled. 4. All multiple members shall be glued & nailed together. 5. All wood in contact with concrete or exposed to weather, shall be pressure treated Douglas Fir -Larch No. 2 or equal. 6. Structural members shall not be cut for pipes, etc. Unless specifically noted or detailed. Periodic surveys: 1. Periodic surveys of the supported structures should be conducted to assure project success. The Owner should be responsible for annual surveys certifying project success. We would suggest that a baseline survey be conducted immediately. The owner shall submit all findings and reports to the Structural Engineer. 2. If vertical movement of the piers is discovered, the piers should be re -pressured. A representative of the Geotechnical Engineer should be present to observe the re -pressuring. A final report should be provided by the Geotechnical Engineer after observing the re -pressuring. Foundation Stabilization: 1. Although observed foundation damage typically does not pose an immediate health and hazard risk, delaying mitigation will likely make future repairs more difficult and costly. Furthermore, it has been our experience that once a structure begins moving, it will likely continue to so (unless action is taken) resulting in further settling, heaving, unsightly cracks, doors/widows not functioning properly and possible foundation wall collapse. The extent and aggressiveness of the foundation repairs should be carefully considered by the Owner and will depend on their tolerance for risk, the possibility of future damage, and cost. 2. If the owner chooses to do so the foundation could be stabilized only at visibly damaged locations and areas where movement is concentrated. Although this will address specific situations, it is possible that foundation movements will occur elsewhere. 3. If the Owner chooses to do so, the entire foundation could be mitigated. A general system repair, although more costly, would greatly reduce the risk of future o�p,GO•L/CF, foundation damage and movement. It is our understanding that the Owner would not ��S N. like to pursue this repair option. v :"T �•, p 0048580 City of W heatge �o,�o i I 4v or ss/4NAL �� DATE: JOB #: DL ENGINEERING INC. 9/30/2020 2020-8391 9100 W. JEWELL AVENUE FOUNDATION STABILIZATION AT LAKEWOOD, CO 80232 4050 MILLER ST. REVISION DATE: PAGE of 720-440-9450 WHEAT RIDGE, CO 80033 S1-3 6 BY: CHECKED BY: WWW.DLENGINEER.COM OWNER: CAMP (148774) GP JS Structural Steel: 1. Structural Steel shall be detailed, fabricated and erected in accordance with 2010 AISC Specification for Structural Steel Buildings, and "Code of Standard Practices" 2005. 2. Structural Steel shall be confirmed to the following grades: 2.1 W- & WT- Shapes: ASTM A36, A992 2.2 Plates & Angles: A36 2.3 HSS: ASTM A500 gr B 2.4 Steel Pipe: ASTM A53 gr B 3. All bolts shall conform to the ASTM A325 except anchor bolts which shall conform to ASTM A307. Bolt Size shall be 3/", unless noted otherwise on the drawings. 4. All welding shall be by a certified welder in accordance with ACIS and AWS specifications and recommendation. Structural Wood framing: 1. Except where noted otherwise, all 2" members shall be Hem -Fir No. 2 and better. 2. Except as noted otherwise, minimum nailing shall be provided as specified in Table No 2304.9.1 "Fastening Schedule" of the IBC. All nails shall be common type, unless noted otherwise. 3. Unless noted otherwise, steel connectors such as those manufactured by Simpson Company, shall be used to join rafters, trusses, joists, or beams to other members at flush -framed conditions. Use maximum number and size of nails indicated in manufactures tables U.N.O. all nails holes shall be filled. 4. All multiple members shall be glued & nailed together. 5. All wood in contact with concrete or exposed to weather, shall be pressure treated Douglas Fir -Larch No. 2 or equal. 6. Structural members shall not be cut for pipes, etc. Unless specifically noted or detailed. Periodic surveys: 1. Periodic surveys of the supported structures should be conducted to assure project success. The Owner should be responsible for annual surveys certifying project success. We would suggest that a baseline survey be conducted immediately. The owner shall submit all findings and reports to the Structural Engineer. 2. If vertical movement of the piers is discovered, the piers should be re -pressured. A representative of the Geotechnical Engineer should be present to observe the re -pressuring. A final report should be provided by the Geotechnical Engineer after observing the re -pressuring. Foundation Stabilization: 1. Although observed foundation damage typically does not pose an immediate health and hazard risk, delaying mitigation will likely make future repairs more difficult and costly. Furthermore, it has been our experience that once a structure begins moving, it will likely continue to so (unless action is taken) resulting in further settling, heaving, unsightly cracks, doors/widows not functioning properly and possible foundation wall collapse. The extent and aggressiveness of the foundation repairs should be carefully considered by the Owner and will depend on their tolerance for risk, the possibility of future damage, and cost. 2. If the owner chooses to do so the foundation could be stabilized only at visibly damaged locations and areas where movement is concentrated. Although this will address specific situations, it is possible that foundation movements will occur elsewhere. 3. If the Owner chooses to do so, the entire foundation could be mitigated. A general system repair, although more costly, would greatly reduce the risk of future o�p,GO•L/CF, foundation damage and movement. It is our understanding that the Owner would not ��S N. like to pursue this repair option. v :"T �•, p 0048580 City of W heatge �o,�o i I 4v or ss/4NAL �� Site Drainage 1. We believe that the moisture around foundation elements must be controlled for the useful life of the building. Lack of proper drainage is often a contributing factor to foundation damage observed. It is our opinion that site drainage around the structure must be maintained such that precipitations will quickly drain away. The use of proper slope slabs -on -grade, moisture barriers, swales and surface/subsurface drainage systems are strongly recommended. Extension should be attached to properly function downspouts and roof drains discharge a minimum of 10 feet away from the structure. Site vegetation 1. We believe that vegetation around the perimeter of structures can eventually lead to foundation movements. Vegetation can hold moisture in soil and create excessive pressure on the foundation system. In order to reduce the risk, bushes, shrubs and trees should be carefully removed by an experienced professional. Care should be taken to not further disturb or damage the existing foundation system. 2. Planters and other surface features which could retain water should be eliminated and properly graded to reduce the possibility of moisture infiltrating around the foundation. Irrigation systems and excessive moisture adjacent to structures can introduce unwanted moisture, possibly resulting in settling and or heaving. The Owner should consider removing irrigation systems or simply not use them. Disclaimer: 1. In as much as the site review of an existing structure for the purpose of observing the structure conditions requires that certain assumptions be made regarding existing conditions and because some of these assumptions may not be verifiable without expending additional sums of money or destroying otherwise adequate or serviceable portions of the building, the Client agrees that , except for negligence on the part of the Engineer, the Client will hold harmless, indemnify and defend Engineer from and against any and all claims arising out of the professional services we have provided. LEGEND: (E) EXISTING (N) NEW PUSH PIER P. P. #X f- PIER # (xxxx#) LOAD ON PIER HELICAL PIER PIER # H. P. #x (xxxx#) _� LOAD ON PIER WALL ANCHOR W.A. #x ANCHOR # WALL BRACE W.B. #x BRACE # CARBON FIBER DATE: JOB #: DL ENGINEERING INC. Wheat Ridge 9/30/2020 2020-8391 9100 W. JEWELL AVENUE FOUNDATION STABILIZATION AT _� LOAD ON PIER LAKEWOOD, CO 80232 4050 MILLER ST. REVISION DATE: PAGE OF 720-440-9450 WHEAT RIDGE, CO 80033 S1-4 6 BY: CHECKED BY: WWW.DLENGINEER.COM OWNER: CAMP (148774) GP JS Site Drainage 1. We believe that the moisture around foundation elements must be controlled for the useful life of the building. Lack of proper drainage is often a contributing factor to foundation damage observed. It is our opinion that site drainage around the structure must be maintained such that precipitations will quickly drain away. The use of proper slope slabs -on -grade, moisture barriers, swales and surface/subsurface drainage systems are strongly recommended. Extension should be attached to properly function downspouts and roof drains discharge a minimum of 10 feet away from the structure. Site vegetation 1. We believe that vegetation around the perimeter of structures can eventually lead to foundation movements. Vegetation can hold moisture in soil and create excessive pressure on the foundation system. In order to reduce the risk, bushes, shrubs and trees should be carefully removed by an experienced professional. Care should be taken to not further disturb or damage the existing foundation system. 2. Planters and other surface features which could retain water should be eliminated and properly graded to reduce the possibility of moisture infiltrating around the foundation. Irrigation systems and excessive moisture adjacent to structures can introduce unwanted moisture, possibly resulting in settling and or heaving. The Owner should consider removing irrigation systems or simply not use them. Disclaimer: 1. In as much as the site review of an existing structure for the purpose of observing the structure conditions requires that certain assumptions be made regarding existing conditions and because some of these assumptions may not be verifiable without expending additional sums of money or destroying otherwise adequate or serviceable portions of the building, the Client agrees that , except for negligence on the part of the Engineer, the Client will hold harmless, indemnify and defend Engineer from and against any and all claims arising out of the professional services we have provided. LEGEND: (E) EXISTING (N) NEW PUSH PIER P. P. #X f- PIER # (xxxx#) LOAD ON PIER HELICAL PIER PIER # H. P. #x (xxxx#) _� LOAD ON PIER WALL ANCHOR W.A. #x ANCHOR # WALL BRACE W.B. #x BRACE # CARBON FIBER C.F. #x �- CARBON FIBER #°� city MONO POST Wheat Ridge M. P. #x i- POST # Building Divison (xxxx#) _� LOAD ON PIER Oma. •��' • N ..S�y NOO LIC �s� :> v• 0048580 �o�0 3 1I � 1 ••��v�v S/ONAI. E� IfI CA/) ti 0 otOUNDATION PLAN (E) HOUSE/ BASEMENT NOTES: 1. SEE SHEETS S1-1 THROUGH S1-4 FOR GENERAL NOTES. 2. INSTALL HELICAL PIERS AND MONO POSTS PER PLAN. of a' FRONT OF HOUSE N N 0 0 0048580 DATE: JOB #: DL ENGINEERING INC. 9/30/2020 2020-8391 9100 W. JEWELL AVENUE FOUNDATION STABILIZATION AT LAKEWOOD, CO 80232 4050 MILLER ST. REVISION DATE: PAGE OF 720-440-9450 WHEAT RIDGE, CO 80033 S2-1 6 BY: CHECKED BY: WWW.DLENGINEER.COM OWNER: CAMP (148774) GP JS IfI CA/) ti 0 otOUNDATION PLAN (E) HOUSE/ BASEMENT NOTES: 1. SEE SHEETS S1-1 THROUGH S1-4 FOR GENERAL NOTES. 2. INSTALL HELICAL PIERS AND MONO POSTS PER PLAN. of a' FRONT OF HOUSE N N 0 0 0048580 ALL WORK SHALL COMPLY WITH 2018 IRC, 2018 IECC, 2020 NEC, COLORADO PLUMBING CODE ATTACH THE TOP PLATE TO THE BEAM PER MANUFACTURER INSTRUCTIONS OR MIN. (4) 2" SCREWS SJ350TP (TOP PLATE) %2"x5.00"x6.00" ASTM A36 PLATE W/ 1.75" DIA. x 0.25" WALL x 1.38" LONG ASTM A53 GRADE B CONFINING RING `I f, city of COW heat Rage MMUNnY DEVELOPMENT APPROVED Reviewed for Code Compliance BRANDON F 10/02/2020 Plans Examiner Date Valldity 0 penah: The issaancs of o paprtlt or gpprovd of plans specp=wns and compumtronv shaft not be a pemR for, or on approval of, any vaorobon to any of the provlslons of the baking code or of o,W City ordinances. permits presumng to gfw outhorlty to vsolole or cancel the pro istmis of tele fudding coda or other ordrnoneerof due Crly shuH not be raid. AN IN SPEC TION BY THE CITY OF WHEAT RIDGE ISNPECTORS IS REQUIRED PRIOR TO BACKFILLING. ENGINEER OBSERVATION LETTER IS REQUIRED FOR FINAL INSPECTION. (E) JOIST (E) BEAM FIELD VERIFY B.O. (E) BEAM (N) INTELLIJACK MONO POST BY INDEPENDENCE MATERIALS GROUP 3.50" OD x 0.165" THICK TUBE YIELD STR = 50 KSI (MIN) TENSILE STR = 55 KSI (MIN) FIELD CUT TO LENGTH SJ350BP (BOTTOM PLATE) %2'x3.50" SQUARE ASTM A36 PLATE W/ 3.13" DIA. x 0.187" WALL x 0.75" LONG ASTMA53 GRADE B CONFINING RING FIELD VERIFY T.O. (E) SOIL H.P. PIER CAP LU H.P. CAP > ATTACHMENT w O BY GRIP TITE U � Q w (N) HELICAL PIER, v GRIP TITE: MODEL GTRDS2875-0203 W/ = w FP3BA RETROFIT BRACKET 11J 0 INSTALL W/ PRO -DIG X9 TORQUE HEAD TO 4,800 FT -LBS TORQUE MAX. 2,010 FT -LBS TORQUE MIN. TYP. HELICAL PIER AND MONO POST 1/211 = 11-011 City of °. 2' Wheat Ridge Building Nwh on 0 o�NO LIC 4 per' •F's •N •SZ* �s� :> v• 0048580 o,�o•% I � 1 •`��v ss/ONAL ��G DATE: JOB #: DL ENGINEERING INC. 9/30/2020 2020-8391 9100 W. JEWELL AVENUE FOUNDATION STABILIZATION AT LAKEWOOD, CO 80232 4050 MILLER ST. REVISION DATE: PAGE OF 720-440-9450 WHEAT RIDGE, CO 80033 S3-1 6 BY: CHECKED BY: WWW.DLENGINEER.COM OWNER: CAMP (148774) GP JS ALL WORK SHALL COMPLY WITH 2018 IRC, 2018 IECC, 2020 NEC, COLORADO PLUMBING CODE ATTACH THE TOP PLATE TO THE BEAM PER MANUFACTURER INSTRUCTIONS OR MIN. (4) 2" SCREWS SJ350TP (TOP PLATE) %2"x5.00"x6.00" ASTM A36 PLATE W/ 1.75" DIA. x 0.25" WALL x 1.38" LONG ASTM A53 GRADE B CONFINING RING `I f, city of COW heat Rage MMUNnY DEVELOPMENT APPROVED Reviewed for Code Compliance BRANDON F 10/02/2020 Plans Examiner Date Valldity 0 penah: The issaancs of o paprtlt or gpprovd of plans specp=wns and compumtronv shaft not be a pemR for, or on approval of, any vaorobon to any of the provlslons of the baking code or of o,W City ordinances. permits presumng to gfw outhorlty to vsolole or cancel the pro istmis of tele fudding coda or other ordrnoneerof due Crly shuH not be raid. AN IN SPEC TION BY THE CITY OF WHEAT RIDGE ISNPECTORS IS REQUIRED PRIOR TO BACKFILLING. ENGINEER OBSERVATION LETTER IS REQUIRED FOR FINAL INSPECTION. (E) JOIST (E) BEAM FIELD VERIFY B.O. (E) BEAM (N) INTELLIJACK MONO POST BY INDEPENDENCE MATERIALS GROUP 3.50" OD x 0.165" THICK TUBE YIELD STR = 50 KSI (MIN) TENSILE STR = 55 KSI (MIN) FIELD CUT TO LENGTH SJ350BP (BOTTOM PLATE) %2'x3.50" SQUARE ASTM A36 PLATE W/ 3.13" DIA. x 0.187" WALL x 0.75" LONG ASTMA53 GRADE B CONFINING RING FIELD VERIFY T.O. (E) SOIL H.P. PIER CAP LU H.P. CAP > ATTACHMENT w O BY GRIP TITE U � Q w (N) HELICAL PIER, v GRIP TITE: MODEL GTRDS2875-0203 W/ = w FP3BA RETROFIT BRACKET 11J 0 INSTALL W/ PRO -DIG X9 TORQUE HEAD TO 4,800 FT -LBS TORQUE MAX. 2,010 FT -LBS TORQUE MIN. TYP. HELICAL PIER AND MONO POST 1/211 = 11-011 City of °. 2' Wheat Ridge Building Nwh on 0 o�NO LIC 4 per' •F's •N •SZ* �s� :> v• 0048580 o,�o•% I � 1 •`��v ss/ONAL ��G :-7 9100 W Jewell Ave — Lakewood, CO 80232 OL ENGINEERING. INC. 720-440-9450 www.dlengineer.com 9/30/2020 RE: Job# 2020-8391 4050 Miller St. Wheat Ridge, CO 80033 As requested, a site visit and observation were performed at the property located at the address above on 9/22/2020 at approximately 3:00 p.m. by Jim Slama, PE. The purpose for the site visit and observation was to review the structure for movement of the foundation. The subject property is a single-family home with a basement and a crawlspace located in an established neighborhood. The building is assumed to have been built in 1998 (based on an online search of the Jefferson County Assessors records). The foundation is constructed of concrete and is assumed to be on caissons. The house appears to be constructed of wood with lap siding and partial brick veneer. The observation was visual and limited to the exterior and the interior house. No observation was performed on the roof structure. For purposes of this report we assume that the house faces south. Observations • Bowing of the floor joists in the crawlspace • Beam posts are not centered on the concrete caissons and are bearing with metal shims. The concrete is eroded and spalling • Floor joist is bearing on the beam with metal shims and not an additional 2x plate • Cracking in the foundation wall in the basement Commentary At the time of the observation, there were multiple areas of concern. The below recommendations will help prioritize items by severity. The majority of the basement foundation walls were either covered with drywall or vapor barrier which limited view to the concrete to observe any cracks in these areas. • The interior caissons are degraded. The concrete is eroded and spalling. The cause of this is not known. However, it is conservative to assume the erosion and spalling will continue. Replacement with helical piers adjacent to the existing concrete caissons is warranted. Recommendations The cracks observed in the walls were likely caused by vertical and lateral movement of the foundation. These movements are most likely caused by contraction and expansion of the soil due to changing moisture content. The following is a prioritized list of recommended repairs that should be made to stabilize the foundation: • Install (4) new helical piers with pier caps and (4) new mono posts at the center beam lines of the structural subfloor to support the main steel beams. 1 :-7 9100 W Jewell Ave — Lakewood, CO 80232 OL ENGINEERING. INC. 720-440-9450 www.dlengineer.com • Monitor the home for further signs of vertical movement. These signs may include new or worsening cracks in the interior finishes, new or worsening cracks in the foundation, floors that become more out of level, and/or doors and windows that become difficult to operate. If further signs of vertical movement are observed, the homeowner should contact DL Engineering for further assessment. • Patch and monitor cracks in concrete, brick veneer and drywall. This will give a baseline for any new movement. If new movement is observed, contact DL Engineering Inc. for further assessment. • With any vertical foundation movement, the only way to ensure complete stability is to fully underpin the entire foundation. This observation only addresses the areas that appear to be actively moving. Best Practices for Foundation Maintenance The following best practices are actions to maintain the service life of the foundation that can be applied to all structures. Proper site drainage and placement of vegetation alone may not prevent movement of a structure; however, they are prudent steps to avoid the contraction and expansion of the soil due to changing moisture content. We share the following information, which is not property specific, with all our clients. Site Drainage • The moisture around foundation elements must be controlled for the useful life of the building. Lack of proper drainage is often a contributing factor to foundation damage observed. The site drainage around the structure must be maintained such that precipitations will quickly drain away. The use of proper slope slabs -on -grade, moisture barriers, swales, and surface/subsurface drainage systems are strongly recommended. Extensions should be attached to properly functioning downspouts and roof drains such that they discharge a minimum of 10 feet away from the structure. Site Vegetation • The vegetation around the perimeter of the structure can eventually lead to foundation movements. Vegetation can hold moisture in soil and create excessive pressure on the foundation system. In order to reduce the risk, bushes, shrubs, and trees should be carefully removed by an experienced professional. Care should be taken to not further disturb or damage the existing foundation system. • Planters and other surface features which could retain water should be eliminated and properly graded to reduce the possibility of moisture infiltrating around the foundation. 7 :-7 9100 W Jewell Ave — Lakewood, CO 80232 OL ENGINEERING. INC. 720-440-9450 www.dlengineer.com Figure 1: Bowing of the floor joists in the crowlspoce Figure 2: View of the crowlspoce :-7 9100 W Jewell Ave — Lakewood, CO 80232 OL ENGINEERING. INC. 720-440-9450 www.dlengineer.com Figure 3: View of the crawlspace Figure 4: View of the crawlspace U1 :-7 9100 W Jewell Ave — Lakewood, CO 80232 OL ENGINEERING. INC. 720-440-9450 www.dlengineer.com Figure 5: View of the crowlspace Figure 6., Beam posts are not centered on the concrete caissons and are bearing with metal shims. The concrete is eroded and spoiling :-7 9100 W Jewell Ave — Lakewood, CO 80232 OL ENGINEERING. INC. 720-440-9450 www.dlengineer.com Figure 7: Floorjoist is bearing on the beam with metal shims and not on additional 2x plate Figure 8: Bowing of the floor joists in the crowlspace OL ENGINEERING. INC. 9100 W Jewell Ave Lakewood, CO 80232 720-440-9450 www.dlengineer.com Figure 9: Bowing of the floorjoists in the crowlspace Figure 10., Beam posts are not centered on the concrete caissons and are bearing with metal shims. The concrete is eroded and spoiling :-7 9100 W Jewell Ave — Lakewood, CO 80232 OL ENGINEERING. INC. 720-440-9450 www.dlengineer.com Figure 11: The concrete caisson is eroded and spoiling Figure 12: View of the crowlspace :-7 9100 W Jewell Ave — Lakewood, CO 80232 OL ENGINEERING. INC. 720-440-9450 www.dlengineer.com Figure 13: The concrete caisson is eroded and spoiling Figure 14: View of the crowlspace CR7d Wheat Ridge euldirg til :-7 9100 W Jewell Ave — Lakewood, CO 80232 OL ENGINEERING. INC. 720-440-9450 www.dlengineer.com Figure 15: View of the crowlspace Figure 16: View of the basement. Remove and replace the post 10 7 :-7 9100 W Jewell Ave — Lakewood, CO 80232 OL ENGINEERING. INC. 720-440-9450 www.dlengineer.com Figure 17: View of the basement Figure 18: View of the basement 11 :-7 9100 W Jewell Ave — Lakewood, CO 80232 OL ENGINEERING, INC. 720-440-9450 www.dlengineer.com Figure 19: View of the basement Figure 20: Cracking in the foundation wall in the basement 12 :-7 9100 W Jewell Ave — Lakewood, CO 80232 OL ENGINEERING, INC. 720-440-9450 www.dlengineer.com Figure 21: Cracking in the foundation wall in the basement Figure 22: Existing beam pocket 13 :-7 9100 W Jewell Ave — Lakewood, CO 80232 OL ENGINEERING. INC. 720-440-9450 www.dlengineer.com In as much as the site review of an existing structure for the purpose of observing the structure conditions requires that certain assumptions be made regarding existing conditions and because some of these assumptions may not be verifiable without expending additional sums of money or destroying otherwise adequate or serviceable portions of the building, the Client agrees that, except for negligence on the part of the Engineer, the Client will hold harmless, indemnify and defend Engineer from and against any and all claims arising out of the professional services we have provided. If you should have any further questions, please feel free to contact me at (720) 440-9450 or islama Pdlengineer.com Sincerely, Jim Slama, PE a N- C -) .S U > 7- 0048580 14 PERMIT NO: JOB ADDRESS: JOB DESCRIPTION City of Wheat Ridge E -Res. Window Replacement PERMIT - 202001437 202001437 4050 Miller St Replacing 4 windows U -value is .30 ISSUED: 07/30/2020 EXPIRES: 07/30/2021 *** CONTACTS *** OWNER (303)870-2170 CAMP EDWARD W SUB (303)945-1519 MATTHEW SEILER 180220 SEILER CONSTRUCTION *** PARCEL INFO *** ZONE CODE: UA / Unassigned USE: UA / Unassigned SUBDIVISION CODE: 2426 / PATIO HOMES/CAMBRIDGE BLOCK/LOT#: 0 / *** FEE SUMMARY *** ESTIMATED PROJECT VALUATION: 10,886.00 FEES Window Replacement 50.00 Total Valuation 0.00 Use Tax 228.61 ** TOTAL ** 278.61 *** COMMENTS *** *** CONDITIONS *** Both the front and back of this permit are required to be posted on the job site at all times. If the complete permit is not present, inspections WILL NOT be performed. Work shall comply with 2018 IRC & 2020 NEC. Smoke alarms shall comply with 2018 IRC Section 134. Interior alterations, repairs, fuel -fired appliance replacements, or additions, any of which require a building permit, occurs or where one or more rooms lawfully used for sleeping purposes shall have an operational carbon monoxide alarm installed within fifteen feet of the entrance to each room lawfully used for sleeping purposes. PERMIT NO: JOB ADDRESS: JOB DESCRIPTION City of Wheat Ridge E -Res. Window Replacement PERMIT - 202001437 202001437 4050 Miller St Replacing 4 windows U -value is .30 ISSUED: 07/30/2020 EXPIRES: 07/30/2021 I, by my signature, do hereby attest that the work to be performed shall comply with all accompanying approved plans and specifications, applicable building codes, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with this ermit. I further attest that I am legally authorized to include all entities named within this document as parties to the work to be performed and that all work to be performed is disclosed in this document and/or its' accompanying approved plans and specifications. Signature of OWNER or CONTRACTOR (Circle one) Date 1. This permit was issued based on the information provided in the permit application and accompanying plans and specifications and is subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures. 2. This permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and received prior to the date of expiration. An extension of no more than 180 days made be granted at the discretion of the Chief Building Official and maybe subject to a fee equal to one-half of the originalpermit fee. 3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard requirements, fees androcedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of the Chief Building Official and is not guaranteed. 4. No work of any manner shall be performed that shall results in a change of the natural flow of water without prior and specific approval. 5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all required inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services Division. 6. TV711fuance or gra ,f g of a permit shall not be construed to be a permit for, or an approval of, any violation of any provision of any a a de or ordinance or regulation of this jurisdiction. Approval of work is subject to field inspection. Signature of Chief Building Official Date REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. Dina Kemp <*Ij-6 A Q�)L/ a From: no-reply@ci.wheatridge.co.us Sent: Wednesday, July 29, 2020 3:19 PM To: CommDev Permits Subject: Online Form Submittal: Residential Window/Door Replacement Permit Application Categories: Dina Residential Window/Door Replacement Permit Application This application is exclusively for RESIDENTIAL REPLACEMENT WINDOWS and DOORS - LIKE FOR LIKE ONLY. YOU MUST ATTACH A VALID CREDIT CARD AUTHORIZATION FORM AND WINDOW/DOOR CUTSHEET (SPEC SHEET) IN ORDER FOR THE PERMIT TO BE PROCESSED. Your Permit will be emailed to the email address provided below once it is processed. THIS APPLICATION DOES NOT CONSTITUTE A PERMIT. DO NOT BEGIN WORK UNTIL PERMIT HAS BEEN ISSUED. Is this application for Yes replacement window(s) and/or door(s) like for like? PROPERTY INFORMATION Property Address Property Owner Name Property Owner Phone Number (enter WITH dashes, eg 303-123-4567) Property Owner Email Address Attach City of Wheat Ridge Electronic Payment Form - **DO NOT ATTACH A PICTURE OF A CREDIT CARD** 4050 Miller St Edward Camp 303-870-2170 Field not completed. camp cc auth.pdf CONTRACTOR INFORMATION 1 Contractor Business Seiler Construction Name Contractor's License 180220 Number (This is a 5 or 6 digit number for the City of Wheat Ridge) Contractor Phone 303-945-1519 Number (enter WITH dashes, eg 303-123-4567) Contractor Email Address mbeaudoin@renewalcolorado.com Retype Contractor Email mbeaudoin@renewalcolorado.com Address DESCRIPTION OF WORK Number of window 4 windows and/or doors being replaced Location of 1 front, 3 bay windows)/door(s) being replaced (for example, master bedroom, kitchen, bathroom, etc): What is the u -value of the .30 or better window(s)/door(s)? City of Wheat Ridge requires the u -value to be .32 or better on windows.. Attach copy of camp specs.pdf window/door cut sheets showing sizes and u -value Project Value (contract 10886 value or cost of ALL materials and labor) SIGNATURE OF UNDERSTANDING AND AGREEMENT I assume full Yes responsibility for compliance with applicable City of Wheat Ridge codes and ordinances for work z under any permit issued based on this application. I understand that work Yes may not begin on this property until a permit has been issued and posted on the property. I certify that I have been Yes authorized by the legal owner of the property to submit this application and to perform the work described above. I attest that everything Yes stated in this application is true and correct and that falsifying information in this application is an act of fraud and may be punishable by fine, imprisonment, or both. Person Applying for Mackenzie Beaudoin Permit Email not displaying correctly? View it in your browser. 5/23/2019 Complete Basement Systems 11795 East 45' Ave. Denver, CO 80239 RE: Job Number 2018-5664 4050 Miller St. Wheat Ridge, CO 80033 OL ENGINEERING. INC- .-, _ .- -__ - 11 - 2750 S. WAOSWORIB 8E4 SUITED 207 DWR. L0 88227 720 443 9450 N DL Engineering Inc. reviewed the progress of construction for the subject project on May 17, 2019. The following is a summary of the observations made: New Observations: • Reviewed the helical piers. There were 3 piers installed at the south west corner of the house (front patio) spaced at approximately 7' to 8' o.c. o The pier spacing was observed and appears to be in conformance with the construction documents. o The piers were installed to refusal or to a depth no less than that specified in the construction documents. o The helical piers appear to be installed in conformance with the structural mitigation plan. o Monoposts were installed on top of the eastern 2 helical piers. The base of the monoposts were welded to the helical piers and top plate was screwed to the porch header. This was an addition to the project that was not shown on the original engineering drawings. The engineer approves of the monoposts as observed in the field. • Site grading around the perimeter of the house did not appear to be modified. • Vegetation around the perimeter of the house did not appear to be modified. Volatile Soils: The moisture around the foundation elements must be controlled for the useful life of the building. Time has shown that Colorado soils can be unstable and structures can experience damaging movements due to expanding and shrinking soils, primarily when moisture changes occur. Maintaining consistent soil moisture contents around all foundation elements is crucial to minimizing foundation movements. Even with properly engineered/constructed foundation systems these volatile soils can still exert excessive pressures causing damage in the residence. If the Owner would like further insight about the on-site soil conditions and preventative measures, a Geotechnical Engineer should be consulted. Geotechnical Consideration: It is possible that the piers may consolidate the soil under the piers. Because of this, periodic surveys of the supported structures should be conducted to assure project success. The Owner should be responsible for annual surveys certifying project success. It is recommended that a baseline survey be conducted immediately. The Owner should report all findings and reports to the Structural Engineer. If vertical movement of the foundation walls is discovered, the piers should be re -pressurized. A Geotechnical Engineer should be present for the re -pressurizing of the piers. 1 Disclaimer: In as much as the site review of an existing structure for the purpose of observing the structure conditions requires that certain assumptions be made regarding existing conditions and because some of these assumptions may not be verifiable without expending additional sums of money or destroying otherwise adequate or serviceable portions of the building, the Client agrees that, except for negligence on the part of the Engineer, the Client will hold harmless, indemnify and defend Engineer from and against any and all claims arising out of the professional services we have provided. If you should have any further questions, please feel free to contact me at (720) 440-9450 or islama@DLEngineer.com. Sincerely, Jim Slama, PE Under the direct supervision of, Daniel LeMier, PE Digitally signed by Daniel D l LeMier DN: CN --Daniel LeMier, 0--DLanie Engineering Inc., E-dlemier@dlengmeer ■ Reason: I am appro is LeM�ero°to°t Date 2019-0 QW N W �4t 35393 2 44M0PM"ii• OL ENGINEERING. INC. 2150S WAM911IN 9I.tl0 SU17E 8 20 OEAYER. CO 80227 720-Ad0-9150 Disclaimer: In as much as the site review of an existing structure for the purpose of observing the structure conditions requires that certain assumptions be made regarding existing conditions and because some of these assumptions may not be verifiable without expending additional sums of money or destroying otherwise adequate or serviceable portions of the building, the Client agrees that, except for negligence on the part of the Engineer, the Client will hold harmless, indemnify and defend Engineer from and against any and all claims arising out of the professional services we have provided. If you should have any further questions, please feel free to contact me at (720) 440-9450 or islama@DLEngineer.com. Sincerely, Jim Slama, PE Under the direct supervision of, Daniel LeMier, PE Digitally signed by Daniel D l LeMier DN: CN --Daniel LeMier, 0--DLanie Engineering Inc., E-dlemier@dlengmeer ■ Reason: I am appro is LeM�ero°to°t Date 2019-0 QW N W �4t 35393 2 4 n M 0. a Z Z 1 rkN 4 rkN O s � r � m Ir m 3 R L)s V W i� us r .. a Z m m m Q ��Ah1 - 1 co us V ��Ah1 - 1 co ,t r� CW� q zZ �m .m o 00 ' n mom rh ZIl A "ate . i CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type: Job Address: - Permit Number: e. ,\C, U \-C, ❑ No one available for inspection: Time i' AM/PM i Re -Inspection required: Yes/ No When corrections have been made, call for re -inspection at 303-234-5933 Date: c-> ql ` Inspector: DO NOT REMOVE THIS NOTICE i CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE r" Inspection Type: �"� r` c i Job Address: m Permit Number: Do a i o o I k, 1� ❑ No one available for inspection: Time AM/PM Re -Inspection required:; NO When corrections have been made, call for re -inspection at 303-234-5933 Date: _ Inspector:, DO NOT REMOVE THIS NOTICE i CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type: Job Address: LA U 'S'O m Permit Number: c) U` 9 0 &: ❑ No one available for inspection: Time ,AM/PM Re -Inspection required: (es)No When corrections have been made, call for re -inspection at 303-234-5933 Date: C, k Inspector: DO NOT REMOVE THIS NOTICE i CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type: Job Address: LAC) ` "O r7 -,- Permit Number: C� U\ 9 () L)a U U ❑ No one available for inspection: Time �,4M/PM Re -Inspection required: es No When corrections have been made, call for re -inspection at 303-234-5933 Date:_"s d G , i � Inspector: - -J- DO - DO NOT REMOVE THIS NOTICE *** COMMENTS *** *** CONDITIONS *** Approved per plans and red -line notes on plans. Must comply with 2012 IRC, 2017 NEC and all applicable City of Wheat Ridge Municipal Codes. Work is subject to field inspections. I, by m signature, do hereby attest that the work to be performed shall comply with all accompanyingg approved plans and specifications= applicable building codes, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with this ermit. I further attest that I am legally authorized to include al i entities named within this document as partes to the work to be performed and that all work to be performed is disclosed in this document and/or its' accompanying approved plans and specifications. Signature of OWNER or CONTRACTOR (Circle one) Date 1. This permit was issued based on the information provided in the permit application and accompanying plans and specifications and is subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures. 2. This permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and received prior to the date of expiration. An extension of no more than 180 days made be granted at the discretion of the Chief Building Official and may be subject to a fee equal to one-half of the originalpermit fee. 3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard requirements, fees androcedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of the Chief Building Official and is not guaranteed. 4. No work of an manner shall be performed that shall results in a change of the natural flow of water without prior and specific approval. 5. The permit ho der shall notify the Building and Inspection Services Dlvlsion in accordance with established policy of all required inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services Division. 6. The is ce or grantin ' f a permit shall not be constryed to be a permit for, or an approval of, any violation of any provision of any apph b cods or any r inance or regulation of thi�j�Jgdiction. Approval of work is subject to field inspection. '5I2 -I 1 9 Signature of Chief Building Official Date REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. City of Wheat Ridge Residential Foundation Repair PERMIT - 201900866 PERMIT NO: 201900866 ISSUED: 05/02/2019 JOB ADDRESS: 4050 Miller St EXPIRES: 05/01/2020 JOB DESCRIPTION: Residential foundation repair on 3 helical piers. *** CONTACTS *** OWNER (303)423-1905 CAMP EDWARD W SUB (303)805-8751 Rodney Martin 060125 Complete Basement Systems *** PARCEL INFO *** ZONE CODE: UA / Unassigned USE: UA J Unassigned SUBDIVISION CODE: 2426 / PATIO HOMES/CAMBRIDGE BLOCK/LOT#: 0 / *** FEE SUMMARY *** ESTIMATED PROJECT VALUATION: 4,650.00 FEES Total Valuation 0.00 Plan Review Fee 81.28 Use Tax 97.65 Permit Fee 125.05 ** TOTAL ** 303.98 *** COMMENTS *** *** CONDITIONS *** Approved per plans and red -line notes on plans. Must comply with 2012 IRC, 2017 NEC and all applicable City of Wheat Ridge Municipal Codes. Work is subject to field inspections. I, by m signature, do hereby attest that the work to be performed shall comply with all accompanyingg approved plans and specifications= applicable building codes, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with this ermit. I further attest that I am legally authorized to include al i entities named within this document as partes to the work to be performed and that all work to be performed is disclosed in this document and/or its' accompanying approved plans and specifications. Signature of OWNER or CONTRACTOR (Circle one) Date 1. This permit was issued based on the information provided in the permit application and accompanying plans and specifications and is subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures. 2. This permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and received prior to the date of expiration. An extension of no more than 180 days made be granted at the discretion of the Chief Building Official and may be subject to a fee equal to one-half of the originalpermit fee. 3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard requirements, fees androcedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of the Chief Building Official and is not guaranteed. 4. No work of an manner shall be performed that shall results in a change of the natural flow of water without prior and specific approval. 5. The permit ho der shall notify the Building and Inspection Services Dlvlsion in accordance with established policy of all required inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services Division. 6. The is ce or grantin ' f a permit shall not be constryed to be a permit for, or an approval of, any violation of any provision of any apph b cods or any r inance or regulation of thi�j�Jgdiction. Approval of work is subject to field inspection. '5I2 -I 1 9 Signature of Chief Building Official Date REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. City of W heat midge C ommuNITy DEVELOPMENT Building & Inspection Services Division 7500 W. 29th Ave., Wheat Ridge, CO 80033 Office: 303-235-2855 * Fax: 303-237-8929 Inspection Line: 303-234-5933 Email: permits d.wheatridge.co.us FOR OFFICE USE ONLY Date: Plan/Permit # Plan Review Fee:Zg- �4Y7 Building Permit Application *** Please complete all highlighted areas on both sides of this form. Incomplete applications may not be processed. *** Property Address: 4050 MILLER ST Property Owner (please print): EDWARD AND JOYCE CAMP Phone: 303-423-1905 Property Owner Email: ECAMP8019(a)AOL.COM Mailing Address: (if different than property address) Address: City, State, Zip: Architect/Engineer: DL ENGINEERING Architect/Engineer E-mail: khoiness(ci_)dlengineer.com Phone: 720-440-9450 Contractor: Rod Martin's Complete Basement Svstems Contractors City License #: 60125 Phone: 303-805-8751 Contractor E-mail Address: Sara. hasse(a_)completebasementsystems.net For Plan Review Questions & Comments (please print): CONTACT NAME (please print): Sara Hasse Phone: 303-805-8751 CONTACT EMAIL(please print): Sara. hasse(a_completebasementsystems.net Sub Contractors: Electrical: W.R. City License # Plumbing: W.R. City License # Other City Licensed Sub: Other City Licensed Sub: City License # City License # Mechanical: W.R. City License # Complete all information on BOTH sides of this form ❑ COMMERCIAL 2 RESIDENTIAL Description of work: (Check all that apply) ❑ NEW COMMERCIAL STRUCTURE ❑ ELECTRICAL SERVICE UPGRADE ❑ NEW RESIDENTIAL STRUCTURE ❑ COMMERCIAL ROOFING ❑ COMMERCIAL ADDITION ❑ RESIDENTIAL ROOFING ❑ RESDENTIAL ADDITION ❑ WINDOW REPLACEMENT ❑ COMMERCIAL ACCESSORY STRUCTURE (Garage, shed, deck, etc.) ❑ RESIDENTIAL ACCESSORY STRUCTURE (Garage, shed, deck, etc.) ❑ MECHANICAL SYSTEM/APPLIANCE REPAIR or REPLACEMENT ❑ PLUMBING SYSTEM/APPLIANCE REPAIR or REPLACMENT ❑ ELECTRICAL SYSTEM/APPLIANCE REPAIR or REPLACEMENT OTHER (Describe) Foundation Stabilization (For ALL projects, please provide a detailed description of work to be performed, including current use of areas, proposed uses, square footage, existing condition and proposed new condition, appliance size and efficiency, type and amount of materials to be used, etc.) Sq. FULF Amps 3 HELICAL PIERS Btu's Gallons Squares Other Project Value: (Contract value or the cost of all materials and labor included in the entire project) $ 4,650 OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance with applicable City of Wheat Ridge codes and ordinances for work under any pen -nit issued based on this application; that I am the legal owner or have been authorized by the legal owner of the property to perform the described work and am also authorized by the legal owner of any entity included on this application to list that entity on this application. I, the applicant for this building permit application, warrant the truthfulness of the information provided on the application. CIRCLE ONE: (OWNER) (CONTRACTOR) or (AUTHORIZED REPRESENTATIVE) of (OWNER) (CONTRACTOR) Signature (first and last name): litly ye' DATE: 05/02/2019 DEPARTMENT USE ONLY el? ZONING COMMENTS: DEPARTMENT CLASSIFICATION: Reviewer: BUILDING DEPARTM T COMMENTS: Revie er: s jzec � PC Building Division Valuation: $ ti (55b 1/16/2019 RE: Job# 2018-5664 4050 Miller St Wheat Ridge, CO 80033 4 9100 W Jewell Ave Lakewood, CO 80232 OL ENGINEERING, INC. 720-440-9450 www.dlengineer.com RECDI ED As requested, a site visit and observation were performed at the property located at the address above on 12/6/2018 at approximately 12:00 p.m. by Daniel Lemier, PE and Kelly Hoiness, PE. The purpose for the site visit and observation was to review the structure for movement of the foundation. The subject property is a single-family home with a finished basement located in an established neighborhood. The building is assumed to be built in 1998 (based on an online search of the Jefferson County Assessors records). The foundation is constructed of concrete and is assumed to be on caissons. The building appears to be constructed of wood with lap siding and partial brick veneer. The observation was visual and limited to the exterior of the house. No observation was performed on the roof structure. For purposes of this report we assume that the house faces west. Observations • Cracking of the brick veneer bordering the house at the front porch • Separation between the brick veneer on porch columns and the porch handrail siding • Settling of porch columns • Separation of lower brick veneer portion of porch columns from the upper, siding clad, portion of the porch columns • Settling of concrete porch slab Recommendations The cracks observed in the porch were likely caused by vertical movement of the foundation. These movements are most likely caused by contraction and expansion of the soil due to changing moisture content. The solution is to drain water away from the house and prevent it from infiltrating the soil next to the foundation. The following is a prioritized list of recommended repairs that should be made to stabilize the foundation: 1. Install (3) new helical piers with pier caps, one at each porch column location, to mitigate vertical movement. • Verify that each column location provides a continuous support between the column foundation and the roof supporting member above. We were unable to confirm if an interior column existed at the time of the visit since the columns have a brick and siding veneer. Presently the brick portion of the column is separating from the siding -clad portion as a result of the settlement, and therefore if an interior support does not exist then there is no continuous support from the foundation to roof. Because these column ..pyof 1 gat R,d9e Buila�n9 O'�Jso,.; (�1 Orb are supporting roof loads, a continuous support should be installed if there is not an existing one. • Install Polyl-evel material under portions of slab and flat work that have settled. • Patch and monitor cracks in concrete, brick veneer and drywall. This will give a baseline for any new movement. If new movement is observed, contact DL Engineering Inc. for further assessment. General Information: Site Drainage • The moisture around foundation elements must be controlled for the useful life of the building. Lack of proper drainage is often a contributing factor to foundation damage observed. The site drainage around the structure must be maintained such that precipitations will quickly drain away. The use of proper slope slabs -on -grade, moisture barriers, swales, and surface/subsurface drainage systems are strongly recommended. Extensions should be attached to properly functioning downspouts and roof drains such that they discharge a minimum of 10 feet away from the structure. General Information: Site Vegetation • The vegetation around the perimeter of the structure can eventually lead to foundation movements. Vegetation can hold moisture in soil and create excessive pressure on the foundation system. In order to reduce the risk, bushes, shrubs, and trees should be carefully removed by an experienced professional. Care should be taken to not further disturb or damage the existing foundation system. • Planters and other surface features which could retain water should be eliminated and properly graded to reduce the possibility of moisture infiltrating around the foundation. 9100 W Jewell Ave Lakewood, CO 80232 OL ENGINEERING, INC. 720-440-9450 www.dlengineer.com are supporting roof loads, a continuous support should be installed if there is not an existing one. • Install Polyl-evel material under portions of slab and flat work that have settled. • Patch and monitor cracks in concrete, brick veneer and drywall. This will give a baseline for any new movement. If new movement is observed, contact DL Engineering Inc. for further assessment. General Information: Site Drainage • The moisture around foundation elements must be controlled for the useful life of the building. Lack of proper drainage is often a contributing factor to foundation damage observed. The site drainage around the structure must be maintained such that precipitations will quickly drain away. The use of proper slope slabs -on -grade, moisture barriers, swales, and surface/subsurface drainage systems are strongly recommended. Extensions should be attached to properly functioning downspouts and roof drains such that they discharge a minimum of 10 feet away from the structure. General Information: Site Vegetation • The vegetation around the perimeter of the structure can eventually lead to foundation movements. Vegetation can hold moisture in soil and create excessive pressure on the foundation system. In order to reduce the risk, bushes, shrubs, and trees should be carefully removed by an experienced professional. Care should be taken to not further disturb or damage the existing foundation system. • Planters and other surface features which could retain water should be eliminated and properly graded to reduce the possibility of moisture infiltrating around the foundation. -71 9100 W Jewell Ave Lakewood, CO 80232 OL ENGINEERING, INC. 720-440-9450 www.dlengineer.com Figure 1: Cracking of the brick veneer bordering the house at the front porch Figure 2: Separation between the brick veneer on porch columns and the porch handrail siding City of what Ridge Nam no 9100 W Jewell Ave Lakewood, CO 80232 DL ENGINEERING, INC. 720-440-9450 www.dlengineer.com Figure 3: Settling of concrete porch slab and columns Figure 4: Settling of concrete porch slab crtY Of What Ridge 1 no CIL ENGINEERING, INC. II3^90 Figure 5: Separation of siding and brick veneer, front porch VWX whom Figure 6: Settling of concrete porch slab and cracking of brick veneer 9100 W Jewell Ave Lakewood, CO 80232 720-440-9450 www.dlengineer.com !:ity of , LVhs?at Ridge Figure 7: Settling of porch columns Figure 8: Settling of concrete porch slab We 99=90 city or Wheat Rage Ave Vq��9100Wwell Lakewood,Lakewokewo oddso C080232 OL ENGINEERING, INC. 720-440-9450 www.dlengineer.com Figure 7: Settling of porch columns Figure 8: Settling of concrete porch slab We 99=90 city or Wheat Rage Figure 9: Cracking of the brick veneer bordering the house at the front porch Figure 10: Cracking of the brick veneer bordering the house at the front porch 7 �tty o� , gat &idee 9100 W Jewell Ave Lakewood, CO 80232 OL ENGINEERING, INC. 720-440-9450 www.dlengineer.com Figure 9: Cracking of the brick veneer bordering the house at the front porch Figure 10: Cracking of the brick veneer bordering the house at the front porch 7 �tty o� , gat &idee 04-1 4-0" 9100 W Jewell Ave Lakewood, CO 80232 OL ENGINEERING, INC. 720-440-9450 www.dlengineer.com t ¢r f jA +f 1 a r> Figure 11: Separation between the brick veneer on porch columns and the porch handrail siding Figure 12: Separation between the brick veneer on porch columns and the porch handrail siding City Ot 8 'Wheat Ridg, ,u"ding Oivison. Figure 13: Front of house In as much as the site review of an existing structure for the purpose of observing the structure conditions requires that certain assumptions be made regarding existing conditions and because some of these assumptions may not be verifiable without expending additional sums of money or destroying otherwise adequate or serviceable portions of the building, the Client agrees that, except for negligence on the part of the Engineer, the Client will hold harmless, indemnify and defend Engineer from and against any and all claims arising out of the professional services we have provided. If you should have any further questions, please feel free to contact me at (720) 440-9450 or khoiness@dlengineer.com 1,c-cvr_ Sincerely, Kelly Hoiness, PE Uz FICO 0054409 N ONA1. EXP. 10/31/19 City of Whe,A Ridge tiding 9100 W Jewell Ave Lakewood, CO 80232 OL ENGINEERING, INC. 720-440-9450 www.dlengineer.com Figure 13: Front of house In as much as the site review of an existing structure for the purpose of observing the structure conditions requires that certain assumptions be made regarding existing conditions and because some of these assumptions may not be verifiable without expending additional sums of money or destroying otherwise adequate or serviceable portions of the building, the Client agrees that, except for negligence on the part of the Engineer, the Client will hold harmless, indemnify and defend Engineer from and against any and all claims arising out of the professional services we have provided. If you should have any further questions, please feel free to contact me at (720) 440-9450 or khoiness@dlengineer.com 1,c-cvr_ Sincerely, Kelly Hoiness, PE Uz FICO 0054409 N ONA1. EXP. 10/31/19 City of Whe,A Ridge tiding HP BRACKET (E) PORCH COLUMNS (E) PORCH SLAB ° <4 REVISIONS DATE Q —� FV ED Q -- 3 —' 4 10►4i w City of -� Wh��ar T.dge (E) FOUNDATION COMMUNI1Y INN i IOPMtN I WALL APPROVED as deview@ f ompliance FOUNDATION TYPE TO BE a FIELD VERIFIED ° L Plan Examiner Date FIELD VERIFY yYp f, at �s f: me Issuance of a peemx or wprovd of plans specrfrcawnt T.O. (E) FOOTING andoomputonom shall rat be a pernetp, w on approvd of, any viol000n to any of the provisans of the building code or of any Oty aanonres. A WFWb MWAMeg to qhs outhawy to violate or cancel the prowsta►t of the BLO&V coda or uktset afOnanon of the Chy sholr rat be va" (N) HELICAL PIER, SLEEVE AND BEARING CAP BY FOUNDATION SUPPORT WORKS MIN 25' DEEP WITH 10" 0 BLADES NUMBER OF SETS PER z MANUFACTURER'S SPECIFICATIONS N z �FYP. HELICAL PIER DETAIL in Inspection by Wheat Ridge Building z Inspector required prior to backfill. in Observation letter from Engineer required to be provided to Wheat Ridge Building Inspector at Final Inspection. o° 1 O�,'PpO LIC�� HO�,y . S Y cn 0054409 SOT X41 �SS�ONA� EAG\ EXP. 10/31/19 LLJ O 31Va z IY W p w —j Z W Aa O NO3HD a Z 0 M 0 NI% �W O J HCo juin -J O ti W Z1YZ Oo3 Q W Z 3 Z) O L6 N 2 Z ao V oo� ZJO.4W �LUUChz D O LL,LU 0 o J W o W n C J D J JOB NO. 2018-5664 SHEET S3-1 OF 4 J ' FROG *FRON' ARE 21 FOUNDATION PLAN 1/20" = 1'-0" NOTES: 1. SEE SHEETS S1-1 THROUGH S1-3 FOR GENERAL NOTES. 2. INSTALL HELICAL PIERS PER PLAN. 3. THE EXISTING PROPERTY LINES AND EXISTING HOUSE LOCATION ARE SHOWN AS DRAWN ON THE JEFFERSON COUNTY ASSESSOR'S PARCEL MAP. FOUND ON http://jeffco.us/assr/pdf/pmap59-094.pdf 4. FOR EXACT LOCATION OF THE HOUSE ON THE PROPERTY, A LAND SURVEYOR SHOULD BE ENGAGED FOR A MORE ACCURATE ASSESSMENT. BACK PORCH LC o!EHoiti ')41,jr 0.. 0054409 •0054409 0 cr /ONAU 0 EXP. 10/31/19 REVISIONS DATE 0 ti U w H 0 0 3J V0 z z J W W J z Lu A8 C7 >103HO T. z O M C cc J W 0.3 mJW2 O .. rA2CW Z 01%Z ONFT: a�Wo zz 3 0 O L6 N 2 Z > N U Q M J 0 ZO'TW � LLI U Z W W 0 0 0 Z Z'O0J Z33tio W O Z COJ JOB NO. 2018-5664 SHEET S2-1 OF 4 Foundation Stabilization: 1. Although observed foundation damage typically does not pose an immediate health and hazard risk, delaying mitigation will likely make future repairs more difficult and costly. Furthermore, it has been our experience that once a structure begins moving, it will likely continue to so (unless action is taken) resulting in further settling, heaving, unsightly cracks, doors/widows not functioning properly and possible foundation wall collapse. The extent and aggressiveness of the foundation repairs should be carefully considered by the Owner and will depend on their tolerance for risk, the possibility of future damage, and cost. 1. If the owner chooses to do so the foundation could be stabilized only at visibly damaged locations and areas where movement is concentrated. Although this will address specific situations, it is possible that foundation movements will occur elsewhere. 2. If the Owner chooses to do so, the entire foundation could be mitigated. A general system repair, although more costly, would greatly reduce the risk of future foundation damage and movement. It is our understanding that the Owner would not like to pursue this repair option. Site Drainage 1. We believe that the moisture around foundation elements must be controlled for the useful life of the building. Lack of proper drainage is often a contributing factor to foundation damage observed. It is our opinion that site drainage around the structure must be maintained such that precipitations will quickly drain away. The use of proper slope slabs -on -grade, moisture barriers, swales and surface/subsurface drainage systems are strongly recommended. Extension should be attached to properly function downspouts and roof drains discharge a minimum of 10 feet away from the structure. Site vegetation 1. We believe that vegetation around the perimeter of structures can eventually lead to foundation movements. Vegetation can hold moisture in soil and create excessive pressure on the foundation system. In order to reduce the risk, bushes, shrubs and trees should be carefully removed by an experienced professional. Care should be taken to not further disturb or damage the existing foundation system. 2. Planters and other surface features which could retain water should be eliminated and properly graded to reduce the possibility of moisture infiltrating around the foundation. Irrigation systems and excessive moisture adjacent to structures can introduce unwanted moisture, possibly resulting in settling and or heaving. The Owner should consider removing irrigation systems or simply not use them. Disclaimer: 1. In as much as the site review of an existing structure for the purpose of observing the structure conditions requires that certain assumptions be made regarding existing conditions and because some of these assumptions may not be verifiable without expending additional sums of money or destroying otherwise adequate or serviceable portions of the building, the Client agrees that , except for negligence on the part of the Engineer, the Client will hold harmless, indemnify and defend Engineer from and against any and all claims arising out of the professional services we have provided. LEGEND: (E) EXISTING (N) NEW ..--� PUSH PIER P.P. #X PIER # (xxxx#) LOAD ON PIER WALL ANCHOR W.A. #x ANCHOR # MONO POST M.P. #x POST # (xxxx#) LOAD ON PIER HELICAL PIER H P #x PIER # (xxxx#) LOAD ON PIER o" REVISIONS DATE as n U) LLI 0 31b4 Z Z J W � w W J Z w na (� NO3HD 7"'d Z M 0 M 0 Ny00W O - W 0 J m .5 LS a H W Z0CcZ 003 Q�WO ZZ 3 n O W Its U!N 2 Z>N 0 •ityof Q CO O � --at Rid ZJOvW oC W V Cf Z �9e W300� hu;ia,n 9 Divisor W 5 O v Z Z ' 0 W Z33�o W O Y DOL/ CF �oJ RFLP �tE.HO� O. � JOB NO. 0054409 2018-5664 130• 4((/ SHEET SSS/ONA� SI -2 E� of EXP. 10/31/19 4 INDEX: S1-1 GENERAL NOTES S1-2 GENERAL NOTES S2-1 FOUNDATION PLAN S3-1 TYP. HELICAL PIER DETAIL BUILDER INFORMATION Complete Basement Systems of CO 11795 East 45th Ave Denver, CO 80239 1-303-219-7646 General Notes: 1. Construction documents are valid for a single use at the project location and shall not be reused, copied, or reproduced without written approval of the registered design professional in reasonable charge. 2. The contractor is responsible for the methods, means and sequence of all structural erection except when specifically noted otherwise in the construction documents. The contractor shall provide temporary shoring and bracing, providing adequate vertical and lateral support during erection. Shoring and bracing shall remain in place until all permanent members are placed and all final connections are completed. 3. The contractor agrees that, in accordance with generally accepted construction practices, the contractor will be required to assume sole and complete responsibility for job site conditions during the course of construction of the project, including safety of all persons and property. This requirement shall be made to apply continuously and not be limited to normal working hours. The contractor further agrees to defend, indemnify and hold owner and engineer harmless from any and all liability, real or alleged, in connection with the performance of work on this project, exempting liability arising from the sole negligence of engineer. 4. All existing sizes, dimensions and foundation damage shall be field verified by the contractor and owner prior to construction. Discrepancies with the construction documents shall be reported to the structural engineer for additional recommendations (if any). 5. Per the owner's request, the contractor shall stabilize the structure only. No attempt shall be made to lift or plumb the foundation wall without approval for the owner and structural engineer. Field Verification: 1. Contractor and Owner shall thoroughly inspect and survey existing structure to verify dimensions, elevations, framing, etc. which affect the work shown on the drawings. 2. Report any variation or discrepancies to the structural engineer before work proceeding. Foundation Design: 1. Soil conditions and types shall be verified by a Geotechnical Engineer during excavation. 2. Follow all recommendations of the Geotechnical Engineer for foundation elements. 3. All helical piles, push piers, helical anchor tiebacks, wall anchor tiebacks and connection hardware shall be designed and installed by supplier, such that they provide the minimum allowable capacities as indicated on the drawings. All capacities shown on the drawings are unfactored service loads and have not been reduced for live load reductions. 4. All steel for helical piles, push piers, helical anchors tiebacks, wall anchor tiebacks and connection hardware shall be hot dip galvanized. 5. Design of individual and continuous footings is based on a maximum allowable bearing pressure of 2000 lbs. per square foot (dead load plus full live load), placed on the natural undisturbed soil, or compacted structural fill below frost depth. Design Criteria: 1. Building code: 2012 IBC, 2012 IRC with City of Wheat Ridge Amendments 2. Dead loads 2.1. Roof 20psf 2.2. Floor 10psf 2.3. Walls 10psf 3. Live loads 3.1. Residential40psf 3.2. Roof 20psf 4. Snow loads 4.1. Ground snow load 30 psf 5. Wind loads 5.1 Exposure Category C 5.2 105 mph 3 -Second Gust Wind Speed Cast -in -Place Concrete 1. All concrete design is based on the "Building Code requirements for Reinforced Concrete" (ACI 318-05/318R-05) All structural concrete shall have a minimum 28 -day compressive strength as follows: 1.1 Footings:3,000psi 1.2 Slab on Grade: 3,500psi 1.3 Foundation walls: 3,000psi 2. Concrete shall be placed on proportioned utilizing Type 1 cement except, concrete exposed directly to soil shall use Type 2 cement. Concrete susceptible to freeze shall be formulated or maximum frost resistance in accordance with the ACI manual of Concrete Practice. 3. Cold weather and or hot weather placing procedures shall be provided, if conditions warrant, as recommended it the ACI manual of Concrete practice. Reinforcing Steel: 1. All detailing, fabrication, and placement of reinforcing steel shall be in accordance with the ACI Manual of Concrete Practice. 2. Reinforcing bars shall conform to ASTM A615-79 and shall be grade 60. 3. Except as noted on the drawings, minimum concrete protection for reinforcing shall be in accordance with ACI 318-05/318R-05. 4. No. 5 or larger reinforcing bars shall not be re-bent. 5. Welding of rebar is not permitted unless procedure is approved by the Structural Engineer. Structural Steel: 1. Structural Steel shall be detailed, fabricated and erected in accordance with 2010 AISC Specification for Structural Steel Buildings, and "Code of Standard Practices" 2005. 2. Structural Steel shall be confirmed to the following grades: 2.1 W- & WT- Shapes: ASTM A36, A992 2.2 Plates & Angles: A36 2.3 HSS: ASTM A500 gr B 2.4 Steel Pipe: ASTM A53 gr B 3. All bolts shall conform to the ASTM A325 except anchor bolts which shall conform to ASTM A307. Bolt Size shall be %", unless noted otherwise on the drawings. All welding shall be by a certified welder in accordance with ACIS and AWS specifications and recommendation. Structural Wood framing: 1. Except where noted otherwise, all 2" members shall be Hem -Fir No. 2 and better. 2. Except as noted otherwise, minimum nailing shall be provided as specified in Table No 2304.9.1 "Fastening Schedule" of the IBC. All nails shall be common type, unless noted otherwise. 3. Unless noted otherwise, steel connectors such as those manufactured by Simpson Company, shall be used to join rafters, trusses, joists, or beams to other members at flush -framed conditions. Use maximum number and size of nails indicated in manufactures tables U.N.O. all nails holes shall be filled. 4. All multiple members shall be glued & nailed together. 5. All wood in contact with concrete or exposed to weather, shall be pressure treated Douglas Fir -Larch No. 2 or equal. Structural members shall not be cut for pipes, etc. Unless specifically noted or detailed. Periodic surveys: 1. Periodic surveys of the supported structures should be conducted to assure project success. The Owner should be responsible for annual surveys certifying project success. We would suggest that a baseline survey be conducted immediately. The owner shall submit all findings and reports to the Structural Engineer. 2. If vertical movement of the piers is discovered, the piers should be K A. re- ressured Are resentative of the Geotechnical En ineer should be resent to SS REVISIONS DATE M r rn L Z 31V0 J W w Z w �e 0 NO3HO Y Aa r Z O M 0 N yco W OJ J W t� J mJW� HBO N W Z o 19 Z 0 Ln 3: QSTWO Z 3 n O L6 N 2 Zao V CO CD LU Z J O .1 W 2LU00Z p 0 ZOO .4Z 0 LUJ Z 3 UJ P LU o M J V p g F, �. -� c •, observe the re -pressuring. A final report should be provided by the Geotechnical 0: ;�� �Fv,•.�p JOB No. Engineer after observing the re -pressuring. : r �n: 0054409 2018-5664 011 �0 \���� ONAL ��1 EXP. 10/31/19 SHEET S1-1 OF 4 l�l3 ii_r` R)S) INSPECTION RECORD ` INSPECTION REQUEST LINE: (303) 234-5933 Occupancy NRe - — Inspections will not be performed unless this card is posted on the project site. Call the inspection request line before 11:59 p.m. to receive an inspection the following business day.** Inspector Must Sign ALL Spaces pertinent to this project Foundation Inspections Date Inspector Initials Comments Pier Concrete Encased Ground (CEG) Foundation / P.E. Letter Lath / Wall Tie Do Not Pour Concrete Prior To Approval cit I ne Above Inspections Underground/Slab Inspections Date Inspector Comments Initials Electrical Sewer Service Plumbing Lath / Wall Tie r% AIS I-e%wnr I Inr1nrnrniinr1 nr Rpinw/ln_Slah Wnrk Prinr Tn Annroval Ot I he Above Insoections Rough Inspections Date Inspector Initials Comments Wall Sheathing Mid -Roof 401, Lath / Wall Tie Rough Electric Rough Plumbing/Gas Line Rough Mechanical Rough Framing Rough Grading Insulation Drywall Screw / Nail Final Inspections Date Inspector Initials Comments Landscaping & Parking / Planning Dept. Inspections from these entities should be requested one week in advance. For landscaping and parking inspections call 303-235-2846. For ROW and drainage inspections call 303-235-2861. For fire inspections contact the Fire Protection District for your project. ROW & Drainage / Public Works Dept. Floodplain Inspection (if applicable) Fire Inspection / Fire Protection Dist. Final Electrical Final Plumbing Final Mechanical Roof 1 Y 7 ZI Final Window/Doors Final Building NOTE: All items must be completed and approved by Planning, Public Works, Fire and Building before a Certificate of Occupancy is issued. Approval of the Final Building inspection does not constitute authorization of occupancy. *For low voltage permits — Please be sure tnat rougn inspections are compietea irurn mu rlrtl uISUIGI dllu CICI .dual ww VURCIVc by the Building Division. **For Inspection Time Window — Please email insptimerequest@Ci.Wheatridge.CO.US by 8:00 A.M. the morning of the inspection with the property address in the subject line of the email. Time window is based on the inspector's route. Occupancy Is Not Permitted Until A Certificate of Occupancy Is Issued Protect This Card From The Weather Y CITY OF WHEAT RIDGE Building Inspection Division / (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type: 0— Job —Job Address: 060 Permit Number: c d i 76 130F ❑ No one available for inspection: Time AM Re -Inspection required: Yes M *When corrections have been made, call for re -inspection at 303-234-5933 Date: Inspector: 0 DO NOT REMOVE THIS NOTICE City of Wheat Ridge r Residential Roofing PERMIT - 201701308 PERMIT NO: 201701308 ISSUED: 06/01/2017 JOB ADDRESS: 4050 Miller ST EXPIRES: 06/01/2018 JOB DESCRIPTION: Reroof 33 squares; remove and replace with 1 layer architectural shingles *** CONTACTS *** OWNER (303)981-6306 CAMP EDWARD W SUB (303)356-2560 Lane Moore 140197 Mile High Construction *** PARCEL INFO *** ZONE CODE: UA / Unassigned USE: UA / Unassigned SUBDIVISION CODE: 2426 / PATIO HOMES/CAMBRIDGE BLOCK/LOT#: 0 / *** FEE SUMMARY *** ESTIMATED PROJECT VALUATION: 11,000.00 FEES Total Valuation 0.00 Use Tax 231.00 Permit Fee 220.15 ** TOTAL ** 451.15 *** COMMENTS *** *** CONDITIONS *** Effective December 1, 2014, asphalt shingle installations require an approved midroof inspection, conducted when 25-75 percent of the roof covering is installed, prior to final approval. Installation of roof sheathing (new or overlay) requires an approved inspection prior to installation of ANY roof coverings and is require on the entire roof when spaced or board sheathing with ANY gap exceeding k/2 -inch exists. Asphalt shingles are required to be fastened to the roof deck with a minimum of 6 nails per shingle. Ice and water shield is required. Eave and rake metal is required. A ladder extending 3 feet above the roof eave and secured in place is required to be provided for all roof inspections. Roof ventilation is required to comply with applicable codes and/or manufacturera€ms installation instructions, whichever is more stringent. In order to pass a final inspection of elastomeric or similar type roof coverings, a letter of inspection and approval from the manufacturer&#39;s technical representative stating that "the application of the roof at (project address) has been applied in accordance with the installation instruction for (roof material brand name) roof covering" is required to be on site at the time of final inspection. City of Wheat Ridge Residential Roofing PERMIT - 201701308 PERMIT NO: 201701308 ISSUED: 06/01/2017 JOB ADDRESS: 4050 Miller ST EXPIRES: 06/01/2018 JOB DESCRIPTION: Reroof 33 squares; remove and replace with 1 layer architectural. shingles I, by my signature, do hereby attest that the work to be performed shall comply with all accompanying approved plans and specifications, applicable building codes, and all applicable municipal codes, policies and procedures, and,that I am the legal owner or have been authorized by the legal owner of the property and am authorized to obtain this permit and perform th "work described and approved in conjunction with this,permit. I further attest that I am legally authorized to include all entities named withvthis document as parties to the work to be ��o performed and that alrk to be performed is disclosed in this document and/ r its' apdompanying approved plans and specifications. Signature of OWNER or CONTRACTOR (Circle one) Da e I . This permit was issued based on the information provided in the permit application and accompanying plens and specifications and is subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures. 2. This, permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and received prior to the date of expiration. An extension of no more than 180 days made -be granted at the discretion of the Chief Building Official and may be subject to a fee equal to one-half of the original permit fee. 3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard requirements, fees and procedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of the Chief Budding Official and is not guaranteed. 4. No work of any manner shall be performed that shall results in a change of the natural flow of water without prior and specific approval. 5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all required inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services Division. 6. The issuance or granting. of a permit shall not be construed to be a permit for, or an approval of, an violation of any provision of any applicable code or any finance or ion thi ' jurisdiction. Approval of work is subject to field inspection. Signature of Chief Building Official Date REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. Inspection time requests will be accepted by email only. Please email requests to insptimerequestgci.wheatridge.co.us between 7:30am and 8:00am, the morning of the inspection. Please put the address of the inspection in the subject line. City of �' 6at 1 c ✓� CORAtn uNfT'y DEVELOPMENT Building A Inspection Services Division 7500 W. 29"' Ave., Wheat Ridge, CO 80033 Office: 303-235-2855 ° Fax: 303-237-8929 Inspection Line: 303-234-5933 Email: permits(d)ci.wheatridge.co.us LFOJ1 OFFICE USE ONLY Planmennit # J30 Plan Review Fee: Building Permit Application Please complete all highlighted areas an� both sides of this form Incom ®P �plete applications m y not be processed. Pro Address: --�zz'�� Property Owner Email: Mailing Address: (if different than property address) Address: City, State, Zip: Archltect/Enginser E-mail: Contractor: / v11 Phone: j Cr� Jl� U - V v�tc, Contractors City License IN: � � � 2 Phone: Contractor E-mail Address: Sub Contractors: Electrical: W.R. City License # Other City Licensed Sub: City License # Plumbing: W.R. City License # Other City Licensed Sub: City License # Mechanical: W.R. City License # Complete all information on BOTH sidles of this form ❑ COMMERCIAL *RESIDENTIAL Description of work: (Check all that apply) ❑ NEW COMMERCIAL STRUCTURE ❑ ELECTRICAL SERVICE UPGRADE gNEW RESIDENTIAL STRUCTURE ❑ COMMERCIAL ROOFING COMMERCIAL ADDITION RESIDENTIAL ROOFING ❑ RESDENTIAL ADDITION ❑ WINDOW REPLACEMENT ❑ COMMERCIAL ACCESSORY STRUCTURE (Garage, shed, deck, etc.) ❑ RESIDENTIAL ACCESSORY STRUCTURE (Garage, shed, deck, etc.) ❑ MECHANICAL SYSTEM/APPLIANCE REPAIR or REPLACEMENT ❑ PLUMBING SYSTEM/APPLIANCE REPAIR or REPLACMENT ❑ ELECTRICAL SYSTEM/APPLIANCE REPAIR or REPLACEMENT ❑ OTHER (Describe) (For ALL projects, please provide a detailed description of work to be performed, including current use of areas, proposed uses, square footage, existing condition and proposed new condition, applian size and efficiency, type and amount of materials to be used, etc.) J 3 -S ITe 1,,1�6 V �° �� tA_)/ Sq. Ft./LF Amps Btu's Gallons Squares .33 Other Project Value: (Contract value or the cost of all materials and labor included in the entire project) OWNEWCONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance with applicable City of Wheat Ridge codes and ordinances for work under any permit issued based on this application; that I am the legal owner or have been authorized by the legal owner of the property to perform the described work and am also authorized by the legal owner of any entity included on this application to 'ty on this application. CIRCLE ONE: (OWNER) (ONTRACT R) or (AUTHORIZED REPRESENTATIVE) of (OWNER) (CONT COR) IIPR NC NAME: L �;t rf' Q / " t �'�/�— SIGNATURE DEPARTMENT USE ONLY ZONING COMMMENTS: Reviewer: BUILDING DEPARTMENT COMMENTS: Reviewer: PUBLIC WORKS COMMENTS: Reviewer PROOF OF SUB[th'ISMON FORMS Fire Department L ! Received ❑ Not Required Water District ❑ Received ❑ Not Required Sanitation District ❑ Received ® Not Required OCCUPANCY CLASSIFICATION: TYPE OF CONSTRUCTION: SPRINKLERED: OCCUPANT LOAD: Building Division Valuation: $ d D, CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type: -\ C) Job Address: Z�ti Cp Permit Number: i :7 ::>A 3 •� � ❑ No one available for inspection: Time 3 , q AM/PM Re -Inspection required: Yes (N—o *When corrections have been made, call for re -inspection at 303-234-5933 Date: Inspector e DO NOT REMOVE THIS NOTICE .�>J r INSPECTION RECORD OccuDancvrrvDe 'INSPECTION LINE (303) 234 -5933 ` Inspections will not be made unless this card is posted on the building site Call by 3:00 PM to receive inspection the following business day. x INSPECTOR MUST SIGN ALL SPACES PERTAINING TO THIS JOB s r , a s FOUNDATION INSPECTIONS DATE INSPECTOR " INITIALS COMMENTS: Footings /Caissons Plumbing Stemwall / (CEG) Concrete 'Encased Ground Mechanical :Reinforcing or Monolithic Roof 7�3 Arg— Weatherproof / French Drain Building Final Sewer Service Lines Fire Department Water Service Lines >: R.O.W & Drainage, POUR NO CONCRETE UNTIL ABOVE HAS BEEN SIGNED 'CONCRETE SLAB FLOOR `Electrical (Underground) Plumbing (U n d e rg ro u n d) Heating (Underground) Do NOT POUR FLOOR UNTIL ABOVE HAS BEEN SIGNED ROUGHS Sheathing Lath / Wall tie Mid Roof Electrical Service Rough Electric Rough Plumbing Gas Piping Rough Mech"anlcal ABOVE INSPECTIONS TO BE SIGNED PRIOR TO PROCEEDING F Framing Insulation FINALS Electrical Plumbing Mechanical Roof 7�3 Arg— MFOR Building Final Fire Department R.O.W & Drainage, G, FIRE AND PUBLICE WORKS EEK PRIOR TO FINAL INSPECTIONS. ' Parking & Landsca ping "'NOTE: ALL ITEMS MUST BE COMPLETED AND APPROVED BY PLANNING AND ZONING, :BUILDING AND PUBLIC WORKS BEFORE A CERTIFICATE OF OCCUPANCY 1S ISSUED. FINAL INSPECTION BY THE BUILDING DIVISION DOES NOT CONSTITUTE AUTHORIZATION - - OF A CERTIFICATE OF OCCUPANCY NOR PERMISSION FOR OCCUPANCY kNCY IS ISSUED ♦ i CITY OF WHEAT RIDGE Building Inspection Division (303) 234 -5933 Inspection line (303) 235 -2855 Office • (303) 235 -2857 Fax INSPECTION NOTICE 1- Inspection Type: Job Address: 5r Permit Number: cv ;yV54e ❑ No one available for inspection: Time y AMf W Re- Inspection required: Yes * When corrections have been made, call for re- inspection at 303 - 234 -5933 Date: �1 1 , Yl l e, Inspector: DO NOT REMOVE THIS NOTICE City of Wheat Ridge Residential Roofing PERMIT - 094560 x. PERMIT NO: - 094560 ISSUED: 12/23/2009 'i SOB ADDRESS: 4050 MILLER ST-. -:EXPIRES: 06/21/2010 9. DESCRIPTION: Replace 5 sqs of hip/ridge :shingles and few in the field 11 CONTACTS 46.43 a nation .00 15.93 k W 62.36 City of Wheat Ridge Building Division 7500 W. 29 h Ave., Wheat Ridge, CO 80033 ° m Office: 303-235-2855 ` Fax: 303-237-8929 . inspection Line: 303-234-5933 Building Permit Application Date. Plan Permit M, Ptopeily;Adtf~ss: tdSD r~l1lt2 5~'.( Win aT~2ro~QG Property Owner (please print): A,SSoc t 4I on ~,M rKTy r^ 1~ Phone: 3 03 - 233 y 6` t Mailing Address: (if different than property address) Address: (2265 W• f3uyauc~ Ave :#z 1t0 City, State, Zip: La lecw ood , CC) / e0226 Grittt~ai<tor: (~e5rtcrn ~yn~A AC.. Contractor License 819 667 _ Phone: 3 63 ,271- c" v ( Stib ctioltraiit6'rs: Electrical City License Company: Plumbing City License Company Exp. Date: Exp. Date: Approval: Approval: Use of space (description): IY pescripfiun 4f=:Hi 3rki 1 ~C fllerG-• le'Ale S~`IAQIC3 W1 1 NC(.t~ ix-00ce- A Ircw $ArA, Irr 4c- r 01.Q Wt Mechanical City License Company: Exp. Date: Approval: Construction Value: $ 82s' (as catoulated Perth a Bulld(ng Valuat/on Data sheet) Plan Review (due at time of submitt tl: S ~ `S~~NATttdrt Sq. Ft./L.Ftadded: Squares S BTU's Gallons Amps OWNEWCONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record: that all measurements shown, and allegations. made are.accurate: that 1 have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance with the Wheat Ridge Building. Code (I.B.C) and all other applicable Wheat Ridge Ordinances, for work under this permit Plans subject to field Inspection. CIRLCE ONE:: (OWNER) CONTRACTOR or PERSONAL REPRESENTATIVE of OWNER) (CONTRATOR) J Z3 PRN7NAME: ~ts li(WzV4 _ SIGNATURE: r Date: f2j~ ♦ i CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 235-2857 Fax INSPECTION NOTICE Inspection Type: Job Address: w / j_4" L Permit Number: ~~aQ e D No one available for inspection: Time AM/PM Re-Inspection required: Yes When corrections have been made,~cgll for re-inspection at 303-234-5933 Date: Q Inspector: [jol, '64, PllfXT of Who-at 1D;,A rn 06/05/2009 12/02/2009 City of Wheat Ridge Building Division s, 7500 W. 29th Ave., Wheat Ridge, CO 80033 Office: 303-235-2855 * Fax: 303-235-2857 Inspection Line: 303-234-5933 E~~ft t Property Owner (plea Mailing Address. (If different than property address) Address: City, State, Zip: , R Date.U& Plan (CI ~(rl~`~ Permit Contractor License V ~;k1 a (a g Phone: IJWTC Electrical City License* Company: Plumbing City License Mechanical City License Company Company: Exp. Date: Exp. Date: Exp. Date: Approval: Approval: Approval: Use of s ace (description): Construction Value_ S GC2 x (as calculated per &a Sultdrng Valuation Data sheet) s NC, R Y CikC p Y~Q.Y~Jt" Plan Review (due at time of submittal): S, Sq. Ft./L.Ft added: Squares BTU's OO Gallons Amps OWNERICONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application. are accurate,. and do not violate applicable ordinances,. rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record;. that all measurements shown, and allegations made are accurate-, that I have read: and agree to abide by all conditions printed. on this application and that t assume full responsibility for compliance with the Wheat Ridge Building Code (I.B.C) and'. all other applicable Wheat Ridge Ordinances,. for work. under this permit. Plans subject to-fi~eeI°d4nspection. CIRLCE ONE:: (OWNER) 'lCO1lFF,RACTOR) oo PERSONAL REPRESENTATIVE of(O)NNER) (CONTRATOR) PRINT NAME: C` SIGNATURE: (-JcL 4S) Date: - Bldg Valuation: S. Building Permit Application CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office ' (303) 235-2857 Fax INSPECTION NOTICE'S Inspection Type: _ IF Job Address/Permit Number: d M i l (Pr cl~f. ❑ No one available for inspection: Time AM/PM Re-Inspection required: es o When corrections have been made, call for re-inspection at 303-234-5933 Date: 7 Inspector: / s DO NOT REMOVE THIS NOTICE " : City of Wheat Ridge Residential Electric PERMIT - 081293 PERMIT NO: 081293 ISSUED: 11/05/2008 JOB ADDRESS: 4050 MILLER ST EXPIRES: 05/04/2009 DESCRIPTION: Move switches and recepticles add 1 for island CONTACTS owner 303/396-9440 Camp sub 303/683-8470 DAVID J. BARAJAS 07-0115 PARADISE ELECTRIC, LLC PARCEL INFO ZONE CODE: UA USE: UA SUBDIVISION: 0209 BLOCK/LOT#: 0/ , FEE SUMMARY ESTIMATED PROJECT VALUATION: 1,000.00 FEES Permit Fee 50.40 Total Valuation .00 DM Use Tax - 18.00 TOTAL 68.40 Conditions: Must comply w/ 2003 IRC & 2005 NEC. I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and s made are accurate; that I have read and agree to abide by all conditions printed on this application and th u~ fu11 rlity for compliance with the wheat Ridge Building Code (I.B.C) and all other applicable Whe rdg ina s, work under this permit. ijlans subject to field inspection. 1. This permit was issued in accordance with the provisions set forth in your application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Codes of Wheat Ridge, Colorado or any other applicable ordinances of the City. 2. This permit shall expire 180 days from the issue date. Requests for an extension must be received prior to expiration date. An extension may be granted at the discretion of the Building Official. 3. If this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes have been or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. '.4. No work of any manner shall be done that will change the natural flow of water causing adrainage problem. 5. Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceeding with successive phases of the job. 6. The issuance of a permit or the approval of drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation f the provisions of the building codes or any other ordinance, law, rule or regulation. All plan review is a Ia t field inspections. Signature of Chief Buil ng gYficial date INSPECTION REQU AT LINE: (303)234-5933 BUILDING OFFICE: (303)235-2855 REQUESTS MUST BE MADE BY 3PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY... City of Wheat Ridge Building Division 7500 W. 29th Ave., Wheat Ridge, CO 80033 Office: 303-235-2855 * Fax: 303-235-2857 c- o Inspection Line: 303-234-5933 OtORP~ Building Permit Application Date: I l . OF~? -OK Plan Permit o ~2qJ Property Address: 10 5-0 IM( Property Owner (please print): Gy,-~ Phone: Mailing Address: (if different than property address) Address: City, State, Zip: Contractor: Contractor License Phone: Sub Contractors: Electrical City License Plumbing City License Mechanical City License Company: ~V e Ase, t~ Company Company: Exp. Date: Exp. Date: Exp. Date: Approval: Approval: Approval: Use of space (description): ) iA-c~ Ayj 4MOC4 Construction Value: $ &K v-` Description ofwork: (as calculated per the Building Valuation Data sheet) MID V-p Plan Review due at time of submittal): $ 0 Sq. Ft./L.Ft added: Squares BTU's Gallons Amps OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance with the Wheat Ridge Building Code (I.B.C) and all other applicable Wheat Ridge Ordinances, for work under this permit. Plans sublect to f' ection. CIRLCE ONE:: (OWNER { CON or PERSONAL REPRESENTA tZf KN(CONTRATTOR) a PRINT NAME: %7a !I~p ice! SIGNATURE: Date: G~ SJ o a DEPARTMENT USE ONLY ZONING COMMENTS: Zoning: Reviewer: PUBLIC WORKS COMMENTS: Reviewer: BUILDING. DEPARTMENT COMMENTS: Reviewer FIRE .DEPARTMENT ❑ approved w/ comments ❑ disapproved ❑ no review required Bldg Valuation: OCCUPANCY: DEPARTMENT OF PLANNING AND DEVELOPMENT BUILDING INSPECTION LINE - 303-234-5933 - CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 - (303-235-2855) Building Permit Number Date 8865 5/7/99 Property Owner : Property Address: 4050 MILLER ST Contractor License No. : 19302 Phone : 431-1007 Company : M& R Plumbing, Inc. Phone : 425 6030 OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are acwrete; that I have read and agree to abide by all conditions printed on this application, and that I assume full responsibility for compliance with the Wheat Ridge Building Code (U.B.C.) and all other applicable Wheat Ridge ordinances, for work under this permit. (OWNER)(CONTRACTOR) SIGNED DATE Construction Value : $800.00 Permit Fee : $32.65 Plan Review Fee : $0.00 Use Tax : $12.00 Total: $44.65 Use: Description : Plumbing to new toilet and lav in basement rough and fixture setting BUILDING DEPARTMENT USE ONLY SIC : Sq. Ft. : Approval Zoning : Approval : Approval : Occupancy : Walls : Roof : Stories : Residential Units : Electrical License No : Company : Expiration Date : Approval: Plumbing License No : Company: Expiration Date : Approval: Mechanical License No : Company: Expiration Date : Approval: (1) This permit was issued in accordance with the provisions set forth in yopur application antl is sub1ect to the laws of Ihe State oF Colorado antl lo the Zoning Regula[ions and Building Cotle of Wheat Ridge, Colorado or any other applicable ordinances of the Ciry (2) This permit shall expire if (A) the work authonzed is not commencetl within sizty (60) days from issue date or (B) the building authorized is suspentled or a0andoned tor a period of 120 days. (3) If this permit expires, a new permit may be acquired for a fee o( one-half the amount nortnally requiretl, provided no changes have been ot will be matle in the original plans antl specifcations and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment exceeds one (1) year, full (ees shall be paid for a new permit. (4) No work of any manner shall be done that will change the naNral flow of water causing a dreinage problem. (5) Contraclor shall notify ihe Building Inspector hventy-tour (24) hours in atlvance for all inspections and shall receive written approval on inspection card before proceetliing with successive phases of the ob. (6) The issuance of a permit or the approval o~drawings and specifcations shall not be cnnstrued to be a permit for, nor an approval o( any violation of the provisions of the builtlodes or any other ordin-_ a~nce, law, rule or regulation. Chief uilding Ir DEPARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number : BUILDING INSPECTION DIVISION - 235-2855 " CITY OF WHEAT RIDGE Date : 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 qPPLICATIo N Property Owner: ,jo%~1 114'^1441~4%.rr Property Address : ~J3~ •~'I•'~~~ ~ Phone : L13)-1047 Contractor License No. : l 9302 Company://'JI$iC jnc Phone: y2S-60~0 OWNER/CONTR,4CTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of rewrd; that all measurements shown, and allegations made are aecurete; that 1 have read and ayree to abide by all conditions printed on this application, and that I assume full responsibility for compliance with the Wheat Ridge Building Code (U. B.C J yad all.pther applicable,Ml"eayRidge ordirSance3{'tor work untler this pertnit. Construction Value : Permit Fee : Use Tax : Total : Use Description: I t / / ~ 4 a^/~M1 "j~ 7 J ~l L4✓ fJ , /Y ~ 1- F li V,1n 64f[~in BUILDING DEPARTMENT USE ONLY o_ ng~CSriSfii671'~ SIC : Sq. Ft. : Approval : Zoning : B-Tii7i Approval : _P,abliZ? W_OtII~Sffiiii@~~t~:1 Approval : Occupancy : Walls : Roof : Stories : Residential Units : Electrical License No : Plumbing License No jJp Z Mechanicai License No : Company : Company : NJ$'Q p/u.+. 4%~9 , _F.. c Company : Expiretion Date : Expiration Date : Expiretion Date : Approval : Approvai : Approval : (i) This pertnit was issued in accordance with Na provisions sel (orth in yopur applicatlon and is subI'ect to the laws at the SUte of Coloratlo anA to the Zoning Regulations an0 Builtling CoOe of Wheat RiCge, ColoraAO or any oNer applicable ordinances of the Ciry. (2) This pertnit shall expire if (A) the work authonzed is not commenced within sixty (60) Eays from issue date or (B) the building authorizeC is suspended or abandoned for a period of 120 tlays. (3) I( Nis pemtit expires, a new permit may be acpuiretl (or a fee of one-half ihe artwunt normally requlred, Drovided no changes have Eeen or will De made in the onginal plans antl specifications antl any suspension or abanCOnmenl has not exceetleC one (i) year. If changes are made or il suspension or abandonment eaceetls one (1) year, NII fees shall Ee paitl kr a new permit. (4) No work of any manner shall be tlone that will change the natural Ilow of water causing a dainage problem. (5) Contractor shall notiy the BuilCing InspeMOr Iwenly-faur (24) houro in atlvante for all inspections and shall receive wntlen approval on inspection tard be(ora proceediing with successive phases of the job. (6) The issuance ot a permit or the aDGroval ol drawings anG specifcations shall not be wnstnietl to be a permit for, nor an approval of, any violatian of the provisions ol the builtling codes or any other ordinance, law, rule or regulation. . Chief Building Inspector ;.-s L• •f~ pf 5 t/r~ fa Jco u ~~ck~~ ya~afe ~4 d ~-~e- iw ~ eK, s~~ f yc~~f" t f, ( ~j~r,' eiJ 'e . (OPTION D or E) ESCROW AGREEMENT LANDSCAPING & PUBLIC IMPROVEMENT TO: City of Wheat Ridge P.O. Box 638 Wheat Ridge, Colorado 80034 The sum of DOLLARS S 00 - 07/ ) to be held in escrow with (City 'df eat Ridge, Option D) (Bank, Option E) until landscaping and public improvements are completed at 4~, (Description) wheat Ridge, Colorado by /Developer/Owner) The City of Wheat Ridge shall have the absolute right to withdraw the Escrow funds for the purpose of completing the landscaping and public improvements for ~0-~70 should (Contractor/Developer/owner) fail to complete or provide said landscaping and public improvements prior \ to the date of The only requirement to withdraw the Escrow funds in behalf of the City of Wheat Ridge shall be a letter from the Planning & Development Department of the City, executed by the Director of said Department and witnessed by the Mayor of the City o£ Wheat Ridge. Said letter shall state that the landscaping, as above set forth, have not been completed or provided by ,fi . 1, ~ . (Contractor/Developer/Owner) and that the date o£ t, has expired. (over) (OPTION D or E) ESCROW AGREEMENT LANDSCAPING & PUBLIC IMPROVEMENTS -2- ACCEPTED: (Director of Planning & Development - City of Wheat Ridge) (Bank - Option E) Address Phone Number (Contractor/Developer/Owner) Address Date Phone Number Temporary Certificate of Occupancy for structures covered by this agreement may be issued by the Mayor of the City of Wheat Ridge for a time period not to exceed six (6) months upon acceptance of this agreement by the City. ~ z H b ~ Cr1 C~ H d CrJ ~ ~ C r t1 ~ n~ 0 CF) i ~ 0) ~ VD J .~...f;:. N N 0 ct ~ a N. C i O ; O Irl ~ W . ra ! I (p (D C'r 1 i i . U7 .~y. ln O ) C) p ~ 0 C) it. ) J 0 A 0': C) C3: o O ~ 3:; Ln O Ul O 31t: p 0 0 D T The Ciry of 7500 WEST 29TH AVENUE GvVheat WHEAT RIDGE, GO 80215-6713 (303) 234-5900 Ciry Admin. Fax # 234-5924 Police Dept Fax N 235-2949 1; R idge DATE: NOVEMBER 14, 1997 TO: ACCOUNTING DEPARTMENT SUBJECT: ESCROW REFUND Reimbursement is requested for escrow funds being held for 3$3-} Miller Street 4065 Lee Circle 4076 Lee Circle 4000 Miller Street 4082 Lee Circle 4050 Miller Street 4092 Lee Circle 4010 Miller Way 4096 Lee Circle 4021 Miller Way 4091 Miller Way 4090 Miller Way The landscaping has been completed to the City's satisfaction. The escrow received and held by the City is $2,500 for each address. The total refund would equal $30,000. If you have any questions, please call Agnes at X2855. The refund should be sent to Cambridge Development, 835 Delawaze, Denver, CO 80204. % AA/;4-~ Alan White, Director of Planning & Development 16i31/1997 16:22 363-592-9337 TRITOri DEV LLC PHGE 61 4Nnepe la-aeow oena Q'Q'd /MiYf Rqp \4 Q'CD (~I 1 C-C.G-c (L ~A 'e Cn.ct Gau z ae+ziee ~a. a ~cKw , , sw~~ C,w , ,IW,..~ e 3oz u. cw. LM YUr 10 le~ ' fl ~.C6,A. 7 3916 LN CYaI~ tC Wt9LeaCiroW u1)M - t5 ]YOY Ln titla 16 SBW W Ci~ =1 lxe drels , L. L~ ,o 3USL..CIM. zo ytaLaocwa z, aeoswc:w l4 a aei L ~ Ll 3B9iulibr3l I 2=97 uw.a e,~,w.w~s 6 N ]M MRU3L 1 Mller& i811.MiiW3t 91 Jr ~ 32 2%1 M 33 9vasrawst +tsscras TMM ro1uMY poMa mMbn~~bewrreWE dcaaaw a .1. ~ lw evtle a U.. .ds• - 6..~. w7 m:.a rx.wo..uW. Q-l Ckto iw,w7 3O.L,c.u. w aenl.m ynp~W • DBlllae rNv Uo CYCM n • w a ~we~a.wer tw cuao wem • ~ 80 7BBB aCrt1a 1 3B0BLm rtla• S Lw .a4 , &t69) W}90I 9n69T cbwG • wMUe.fW.u ue ~ lMCW1 SI ]939 MCKM ~ tlDwtl tl(ItOqrNY1W 60 8 WK~ m a L"crw e1 4056 uo tvw U 4092 Lw C„no W Lw Yw Et ~R12l.es 4076lss LYCiaie L..C~.- LM J eY .OMlwGhk r~c aroy w c,w 7/1EM En9~lf 27N t eowa dwd ~.w daW A~ww+uPs q~aora„~yya a ~wow 8uor tl~~wwaww K r7k :Jk ~ 71 ~ W Cide IOpS LM LImft • las CLtle '4045 9I76A1 1 tlnW ykyyq. "iy lw e 75 Lw C+tN T6 ~O151a wap W10lp7 ' l9YVLMCicY R ~ t6 4OOOMIW M MYIM C Bt 28+6 YNS ~ 95 8/1blY~ rwi~ IQ91 nano ro qM~O Ck~00 ro 4rw Q*M ' m MFY~ Yuw ~rsaM MYw iL1Yi m eY~ ~ww ivWw ol 1~4 " tl„~... ~ , 102 Ma,9. ~ ,W , ro ,a usou+w u, awe a.wo.~n.w ~ anua7 ~wa -~w.a.raw q', TO DA74 N;lM /ov31- q 7 ~ a ~acJ ~N c~ U~a~re ~ n C~c~~oQ ~ c~ne~ 1 ~ ~ ~ J ) ) ~ i^ l~Gkn LG~ S^Ra - ~ &Oo ' l aOI-IX A " ! t V -+*PI - A► 1CV,11N] ~ 0) a) ~ 0 ot-6 N B " v C L - ~-U c o3m 3 C S Eo ~ now U m ~ ~ oa~ z m n ~ a oa; ° ' m U W ~ °0 m U =mq O ~ o ~ o ''v m m v C o ~ 0 29 ° O L O ° V 2 m~ U 3 m m 0 ` mm a ° W 3a LL ~~me, t E~ U cj m v ~ a H E c m d r Y mN V 0-4 W m a ~ O > E D 00 m a V a 0 0 P T r. m C N caE W > " = v U mam~ U j W ~ - m aa tm¢¢ LL m m ~ w E m m 0 tOLL F- n 3 3 3 o j W N W ~ 0 O ¢ Y v v i ~ N i N f O ~ 0 -It J a. ~ N 2 O Q O Q p ¢ ~ O Q U w ~ ¢ F ~ W Q Z Z O f7 O U a ~ 3 0 C ~ v ~ ~ ~ 0 0 v U 0 a ~ 3 m a n' m .E t 3 0 ~y O T v n U ~ m rn m « 5 « N c O a G m E `m m n a ~ U 00 W m `p y 0 P m a `a u ~ U ~ O 0 Z Z U 0 J LL W S H Q. LL 0 a o 0 ~ c E ~ a ~ a T m ~ m m c ~ U N tL d 0 LL 3 LZib-96 uaaenH iiwuae DATE : 6-,/0 ' 77 ~ A CERTIFICATE OF OCCUPANCY HAS BEEN REQUESTED FOR: (f v s-6 C"~ a,~- PURPOSE OF STRUCTURE: z Y Building Dept. Approval: Remarks: ( a l~ ~ ~ G Zoning Approval: Remarks: ~ 2 ~ P INSPECTIONS WILL NOT BE MADE UNLESS THIS CARD IS POSTED ON THE BUILDING SITE 24 HOURS NOTICE REQUIRED FOR INSPECTIONS WHEAT RIDGE, COLORADO 7500 WEST 29th AVENUE (303) 234-5933 INSPECTION RECORDg4, JOBADDRESS 4050 Miller Street BUILQING PERMIT N0. 96-4127 OWNER Cambridge Ventures DATEISSUED 10/30/96 coNTrancroa Triton Developme SETBACKS FROM PROPERTYLINES: NORTH SOUTH EAST TYPE OCCUPANCY WEST INSPECTOR MUST SIGN ALL SPACES PERTAINING TO THIS JOB INSPECTION DATE INSPECTOR Foundations Footings Caissons Reinforcing or Monolithic Weatherproofing POUR NO CONCRETE UNTIL ABOVE HAS BEEN SIGNED Concrete Slab Floor: Electrical (Ground Work) Plumbing (Ground Work) Ln,k, Heating (Ground Work) DO NOT POUR FLOOR UNTIL ABOVE HA>q~BEEN SIGNED Rough Electrical Rough Plumbing 4-7 Air Test Gas Piping j Rough Heating & Ventilation e (above must be signed prior to framing inspection) Framing Y y ~ G Insulation Drywatl nailing , Le. )VI ~ ~ - Roofing Refrigeration Electrical underground Final Electrical Plumbin `7 ~ G Heatin 8 Ventilation Frame R.O.W. & Drainage Fire Department Parking & Landscaping c.- OCCUPANdY NOT PER'MITTED UNTIL CERTIFICATE OF OCCUPANCY IS ISSUED PROTECT THIS CARD FROM THE WEATHER DEPARTMENT OF PLANNING AND DEVELOPMENT BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 Building Permit Number Date 5213 6/3/97 Property Owner : Property Address : Contractor License No. : 4050 MILLER ST 19436 SA BELL'S ENTERPRISES Phone: Company Phone : 205-9777 OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances propos and do not violate applicable ordinances, rules or covenants, easements or restrictions of cor , tY made are accurate; that I have read a agree o applir,ation, and that I assume full res onsibil' ~(c Code (U.B.CJ and all other applicabl W F}~d (OWNER)(CONTR4CTOR) Description : LAWN SPRINKLER BUILDING DEPARTMENT USE ONLY ..4M~. SIC: Sq.Ft.: Approval: Zoning : Approval: w•~~ ~ Approval : Occupancy : Walls : Roof : Stories : Residential Units : application are accurate, City of Wheat Ridge or ots shown, and allegations itions printed on this i the Wheat Ridge Building r,work under this pervnit. A Construction Value : $1,500.00 Permit Fee : $49.50 Plan Review Fee : $0.00 Use Tax : $18.00 3 Total: $67.50 Electrical License No : Plumbing License No : Mechanical License No : Company : Company : Company : Expiration Date : Expiration Date : Expiration Date : Approval : Approval : Approvai : -6 u al - - i ~ (1) This pertnit was issuetl in accordance with the provisions set forth in yopur application and is subject to the laws o( the State of Coloredo and to the Zoning Regulations and Builtling Cotle of Wheat Ridge, Colorado or any other applicable ordinances of the Ciry. (2) This permit shall expire it (A) the work authorized is not commenced wtlhin sixry (60) days from issue date or (B) the building authorized is suspentletl or abandoned for a period of 120 tlays. (3) If ihis permit expires, a new permR may be acquired for a fee of one-halt the amount normally required, provitletl no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or aDandonment exceeds one (1) year, full fees shall be paid for a new permit (4) No work of any manner shall be done that will change the naWral Flow otwater causin9 a drainage problem. (5) Contraclor sh notiry the Building Inspector hventy-four (24) hours in advance for all mspections and shali receive written approval on inspeclion cartl before proceediin i successive phases ofthejob. (6) The issu ce f a per~1 t or the appmval of drewings and specifcations shall not be construed to be a permit for, nor an approval of, any violation otthe provisions of the b tli codesgf any other ordpance, law, rule or re9ulation. ing Inspector IS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION DEPARTMENT OF PLANNING AND DEVELOPMENT BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 Building Permit Number : Date : zI,iJe c17 Property Owner : /,Pi Dt~ %~Ld~NL~I/f Property Address : ~/1620 R/LLIT .~r Contrector License No. : Cf~ Company : L=.✓/t~2~'/s t C_ OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit apptication are acwrate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or reslrictions of record; that all measuremenis shown, and allegations made are accurete; that 1 have read and aqrs4 to abide hy all conditions prinfed on this application, and that I assume full respo ibili lor compliance Ifr the Wheat Ridge Building Code (U.B.C.) and all olher appli[abl he idg ordmanc work under this permit. (OWNER)(CONTRACTOR) SIGNED I~ DATE G'DY•YYDescription S Vc{`tt_'7-1 BUILDING DEPARTMENT USE ONLY Zohffi 'CO~i1Tif~ii~ SIC : Sq. Ft. : : Approval : Zoning : B y i fd Ii►~;Cb'~ii"'n~ts~ Approval : p011:111 f~3k11,~FKis?Gbl~lt~~fi, . Approval : Occupancy : Walis : Roof : Stories : Residenlial Units : Electrical License No : Plumbing License No Mechanical License No : Company: Company: Company: Expiration Date : Expiration Date : Expiration Date : Approval : Approval : Approval : gj 14PI3[I11'1Rdi~Ul ~ In a;iaortRWl"~ IN maxme:gairaa~q (1) This pertnit was issued In aaordance wiM the provisions set lorth in yoDUr application and is suh'ect b the laws of the State o1 Colorado and to the Zoning Regulations a~M BuilAing Code of 4Vheat Rid4e. Cobrado or any olher applicable ordinances ol the Ciry. (2) TTis permil shall ezpire d(A) the work authonzed is nol tommenced wilhin sixry (60) days fmm issue date or (B) the building aulhodzed is suspentled or a0antloneA for a penod of 120 days. (J) II Ihis permit expires, a new pertnM1 may be acquired br a lee of one-half the amount normalty require4 Orovided no changes have been or will be made in the original plam and speciOwUOna and any suspension or abandonmenl has not exceedetl one (f) year. II changes are made or i1 suspenslon or abandonmont exceeds one (t) year, full lees shall be paid br a new permit. (4) No work of any manner shall be done Nal will change the natural Ilow of water causing a drainag? Droblem. (5) Contractor shall notify the 8uilding Inspeclor Iwentylour (Za) hourt in advance br ail inspectionc and shall raceive written apOmval nn inspeclion card bnbrp proceediing wtlh eucceasive phases of the ob. (G) The issuance ol a Oermit or ihe approval o~drawings and specificalions shall not be consimeA b hr i prrmil lor, nor an appioval ol, ony violation of the pmvisions of fhe OuilAinq co0es or any olher oNinance, law, rulp or regulation. Chie( Building Inspector For Mayor THIS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR /1ND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPF_CTION Phane: Phone : 2_e~~ -y777 Construction Value : / 5 Permit Fee ' Plan Review Fee : USP, T2X : Total : BUILDING DEPARTMENT 237 • 6944 Ext. 255 CITY OF WHEAT RIDGE t * Correction Notice ' Job Located at ;2Ir:1.f~1.:....................................... I have this day inspected this structure and these premises and have found the following violations of City and/or State laws governing same: ' ; , I L. ~n1. c. <7u~~... .a. J..,'.. ~?.a. ~.....7,`..,::~~ ........;-..!~..Y..u'!1.rf~....~~:: G ~ . . l•.............. - i.........,...1-'.:e -~......>....~..~-.t~.1........ ~ ~ ' You are hereby notified to correct the foregoing violations. When corrections have been made, call for inspection. ' Date....................................... . I In pect~~Bruid~ing Dept. DO NOT REMOVE THIS TAG FORM WR6-E2 BUILDING DEPARTMENT 237094W-E-Xe: 2ss CITY OF WHEAT RIDGE ' . . Correction Notice Job Located at ~.CI., SU.... ~:F!.L z!....6.~°....... ..C✓..Z I have this day inspected ihis structure and these premises and i have found the following violations of City and/or State laws ' goveming same: w ~_7fJtuPcl~ ~~C.y.../o-vY✓'.E 0 / y~.. / ri .......~j...........CJ......J^ .✓.f.z:-r.~...~/./ ! .......J.~ . ~ ' o "t' . l1;/.r..t.Y.a4~.t~/.•...:n o;C'.+......P:l...:L'.::?f'.vC .......~.:.f..9 Y . , ' `~i-~-Fen I~ a~ ,lxi. o S ...l..... .~h....:... ..r~..:.....,~ .:..............:~...~f.................................. ° F.i..X b„ ~P.5 1 f? .e t~;~u{~ r~/oa1- . S~~Jdr h~lr~er -rz r6f ,7V i ~ w.....1........................... Yti..... . l. ~ : . - T... -~•°r S~~J~%j`~a ji 2'~• . 1•~~i ,.r,c✓f,-. 1~7~q~2 S~rC -41-rvSS You are hereby notified to correct the foregoing violations. LJf I~ When corrections have been made, call for inspection. I ~ , Date... . ' ~ /';I. ~ . - Inspector forBuilding Dept. DO NOT REMOVE THIS TAG FORM WF6-32 BUILDING DEPARTMENT (303) 235-2855 CITY OF WHEAT RIDGE * * Correction Notice Job Located at ! U 5U 1'!11/E'r I have this day inspected this structure and these premises and have found the following violations of City and/or State laws gov- erning same: rc- s 4c A 6-c- You are hereby notified to correct the foregoing violations. ~ When corrections have been made, call for inspection. i !J Date 3 - 2 cj _ i ~ Inspectw for BulWing Dapt. ` DO NOT REMOVE THIS TAG ~ i FORM WRB-22 iK S BUILDING DEPARTMENT (303) 235-2855 CITY OF WHEAT RIDGE * * Correction Notice Job Located at LIo=u I have this day inspected this structure and these premises and have found the following violations of City and/or State laws gov- erning same: r You are hereby notified to correct the foregoing violations. When corrections have been made, call for inspection. Date ~fORM WR&22 ~ / Inspector for Building Dept DO NOT REMOVE THIS TAG HLPIVORTFI-PA\NI.AK GI:0171CIINICAI„ Jnc. 10214 Suwh Yrugrcss I.n. P~kcr, CO 80134 Pax303 84I-7556 PLanc303 841-7119 December 5, 1996 Cambridge Partners, LLC Attn: Barry Odean 10241 W. 38th Ave, Construction Trailer Wheat Ridge, Colorado 80033 Job Na 296 131-1 Subject: Observation ofExcavation for House at Lot 86, Cambridge Park, Wheat Ridge, Colorado. Dear Mr. Odean: This letter will confirm our visual observations made at an earlier date. \0'e observed the excavation for the subject lot on November 22, 1996. The proposed house will have a basement. At the time of our visit the eacavation had been dug to 2 to 7 feet in two levels. The soils exposed on the bottom of first level consisted of weathered claystone bedrock and second level consisted of claystone bedrock. The bedrock is similar to that encountered in our borings. A sample of the bedrock was taken and tested for swell potential. The results are attached. In our opinion the house should be founded on a Type 5 foundation consisting of piers. A structural floor system should be used. Slab on grade floors will have a high risk of movement. The other recommendations in our report 296 13 dated August 8, also shouid be observed. lf you have any questions, please call. Sincerely, HEPWORTH-PAWLAK GEOTECHNICAL, Inc. Nick Cheng ~I+~f & (1 ~ F I T ' 46'iXa .i Richard C. Hepworth, P.E. <vl l 7 Y f~~F ~ cc. Bill Lyons ont /eic C 86 on °nt = 16.4 percent lht = 108.2 pcf laystone @ S.G. wetting 100 HEPWORTH-PAWLAK Cambridge Park 296131-1 GEOTECHNICAL, INC. SWELL-COMPRESSION TEST RESULTS Fig. 1 design inc. b-ilon Denelopment, /,.l..('. 835 Ueleware Slree[ l)enrer, CO 80204 A(bc A4r. Billl,yon.r 136o Soerh Clurksai St Denrer, CO 80210 (303) 744-7839 tax (joj) 744 -9603 nt-ce,,,ner za, 1996 Yr(jec! Nrmrher: 962-4640 Subjecl: Pier Drilling & FounJation {Vrd! bmpectirui.s 4050 tYli!!er .Slree[ L.ot 86 Cnnibrirlge Pnrk Whentridge, Co%rnrlo Uenr Mr. Lyons: A1 yoin• i•eqtresl, on Ueceinber 3iz(crnd 30111. 1996, u pier elrilling cuid /ouixlurion wull inspec[ions ivere perfi~rnied otr !he single fanrily re.siclence lncalecl au -IOSO A-IiNer .Slreel, Wheatridge, Colorndo. 7he perlriren! rnfaomalioti regurcli»g lhr msJwclion r.s us./bIlows: YlF;RDRII,l.INGlNSPF,('7%ON-UF.('LIfRt:W 3 1996 Soi1 Yrojile 1 he .soil pi•ofrle encoturtered diu•ing di-i/ling consi.rlec! oj (I ' ln 9'_0 " uf c/aV anc/ 9' io 18'-0 qf clnystone 6edrock in t{te irpper lerel, nne! 0' ru .i '-D " uf'c/uv nncl 5' In 18'-0' of clnyslone bedrock in the lower level No wnJer ira.t forrncl in the holes nl Jhe fime qj drilfiirg. Sorls report reqnii•emenls were me( nl crll pier (occuiuir.s in.yectec(. Rein{orcemeit( Concrete A!l of'the pieis were reii !forced with !hi•ee uo. S hcu•s, gl uch 60, f'ui iheii eutire leiig!lz. 7 'he coticrete used consisled of a 3, 000 psi, 3/4 " slnne nggregnle utix. Al! of !he piei.r were proper•ly conslrircled necoi•ding lo air recommeudnlioit.s nnc/ Ihe i•ecununendnlion.s ur [he .soils report. FOUNDA710NWAL1 STFH'l INSPI-'("l'/(JNS l)l;('lrl-IHI•:R10 1996 77ie f01!)7CIpIlO!! walls were reinforcec/ horizonln!!v irilh nru no. 5 burs, grnde 60, n/ ihe top and bottont. All of !he brn•s were pruper(y lappecl cmd lied. 7he foundnlion ira!/ fbi•nrs were properly centered over !he (ki!!ed pier joiuidntion sp.stem, nncl Jhe reinforciilg steel,fi•ont the prers ex/rnded !o liie lol) rour (?f i•eiuforcing iit (hr frnmidulioii ira!(. Puq)w voic/ mnterin! ivn.s properly in.rta!(ec/ be(iveen !hr piri luctdiuns iii!!re huuuin u/ Ihe forms. Reii forcing stee! was properlyplncec! u1 ihe Juruululion ircrl( .sirp clomrus and tivindinropenings. Adclftional verlical bnrs were plucee! iir n!l ivnlLs !n!!er !{tnn R'_0.. Please coittael nry ciee if I mny he qf frrllier asvisvunce. btspected By: Apprured i3Y: Brrrce D. Kiiiney -~L- liespectoi• h;ncln.rtire: Imvoice MCMics A-/cu7in, P. E. Prurcipn! Su ucluru! Fuginreei• /ni•liir l )e.rigii, lnc. IMPROVLMENT LOCAtIifl 6 / i nh ~ Fj / IJ. 1,071 86 BLOG< I COVERE , PORCI i ~ Covt_raro , " ~ - - POR( :I l \ ~ ~ i •D.` . ~ r~. , 0 ~ \ l\ F. 3 . . j)~ A:- . ~ . co ; ! . ~ , ~ 'Ft~. I 5' l~~f~f_T i~ p L= 157 1 I A11L1,1;'R S'l'I~'1%L"1, FLOOD PLAIN S7ATEMENT TIIIS PROPFRTY LIES OUISIDE OF THE 100-YEAR FLOOD f'LAIIJ AS DEFINED B'i fEMA FLOOU INSURANCE RAIE MAP 140. 085079 0005 C DATED: PEI3. 4, 1988 ZONE: B IMPROVEMENT LOCATION CERTIFICATE I HEREBY CERfIFY THIS IMPROVEMENT LOCAIION CERIIFICATE WA5 PR[PnRCD FOR __1RI70I4_QEV[I QPpAFli(__ OF THE PF'OPERTY DESCRIBED A5: LEzA11E,SCRIPTION CAMBRIDGE PARK (AMENDED) LOT 86, BLOCK 1 AKA 4050 MILLER STREET AND 11-IAT IT IS NOT A LAND SURVEY PLAT OR IM ROVEMENi SURVEY PLAT, AIID ❑IAT II IS PIOT 10 f3C RELIFD UP411 IuK f1iF ESTABUSHMENT OF FENCE, BUILDING, OR OTNER FUTURE IMPROVEMENT LIN[S, 1 FURTHER CFRFIFY THAi THE IMPROVEIdEIIi; CJI inE ABOVE DESCRIBED PARCEL ON THIS DATE 6 -9-$2 _ ExCEPT UiILITY CONWECi10115. ARE ENIIRELY vllifllN i11E BOUNDARIES OF THE PARCEI_, EXCEPT AS SIIOWN, ThIAT THERE ARE IJO ENCROACHMEIIfS uPn11 TIIE DESCRIBED PPELUSF_S H~ IMPROVEA1EM5 OIJ ANY ADJOINING PREMISES, ExCEPi AS INDICATED, AFID TIIAI tllERf IS Ilu nF'PnRUI! EvIDEIIrIF qE ~,p.IJ f ail, EAS[MLNI CROSSWI: bR 13URDENING AMI PARi OF SAID PARCEL, E%CGPI AS IIGIFU, f A;f 4111113 SIIUWII 116RCGI1 W6P1I%I I II !i-~~ IIiE RFCORDED PI.AT DESCRIBED ABOVE, NO OIIItR RESEnRCII OF IIII L Wn5 I4HFOlt1,11 U III i,nUIllC"7lOli WI III II11 F.1- 16 V:II NOiIrE nCCORUING i0 COLORA00 LAW, YW NUSi WMAIENCE ANY AC710N BASED UPON ANY DEfECI IN illl$ $IIRVEY YA61111 IMREE YEARS fR01A W11Ef1 YIXI FIRSt DISCOVCR SVpI DEFECT. IN NO EVENT IAAY ANY ACiION BE COMAIENCED MORE iHAN lEN YEARS (ROM ➢IE DATE OF OIE CERPFlCAl10N II[REOH OEARIIJGS, If SIIIOWN, PRE UASED UPON THE RECORDED PUi AND E%ISIING MONIIMENIION. 110.: 97 -c 2993 So. PEORIA STREET ~U1"VPy1.11~", j11C'. A~~o~a~~~ 80014 ~ Phone (303) 750-4591) DEPARTMENT OF PLANNING AND DEVELOPMENT B'UILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 Building Permit Number : 4127 Date : 10/30/96 Property Owner : Property Address : 4050 MILLER ST Contractor License No. : 18844 Company : Triton Development, L.L.C. Phone : 456-0986 Phone : 592 9600 OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, ea:>ements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and ayree to abide by all conditions printed on this application, and that I assume full resp for compliance with the Wheat Ridge Building Code (U.B.C.) and all other applicable onsRidge ordinapwes„for work under this permit. Z (OWNER)(CONTRACTOR) SIGN DATEf/ Description : SINGLE FAMILY R IDENCE Construction Value : $87,400.00 Permit Fee : $$17.50 Plan Review Fee : $0.00 Use Tax : $1,048.80 Total: $1,866.30 BUILDING DEPARTMENT USE ONLY SIC : Sq. Ft. : 2025 Approval : SM 10123196 Zoning : pRD Approval : Approval : Occupancy : SFR Walls MEETS ALL R-1 AND PRD DEVELOPMENT REGULATIONS Roof : Stories Residential Units : 7 Electrical Li,cense No : 17997 Plumbing License No :18982 Mechanical License No : 17977 Company : No Shorts Electric Company :T M Plumbing, Inc. Company : K C A Companies Inc. Expiration Date : 2/28/97 Expiration Date : 7/25/97 Expiration Date : 517/97 Approval: Approval: Approvai: . 'U gKo Womm" m ' (1) This pi;rmit was issued in accordance with the provisions set forth in yopur application and is subject to the laws of the State of Colorado and to ihe Zoning Regulations and Building Cotle of Wheat Ridge, Coloratlo or any other applicable ortlinances of the City. (2) This pertnit shall expire if (A) the work authorized is not commencetl within sinfy (60) tlays from issue date or (B) the Ouiltling au[horized is suspenAetl or abandunetl for a penod of 120 tlays. (3) If this permit expires, a new pertnit may be acquired for a fee of one-half the amount normalty required, provitletl no changes have been or will be made in the original plans and speafications and any suspension or abandonment has not exceeded one (1) year. It changes are made or rt suspension or abandonment exceeiis one (1) year, full lees shall be paid for a new permit. (4) No work of any manner shall be tlone that will change the naturai flow of wa[er causing a drainage pro6lem. (5) Contm:clor shall notify the Builtling Inspector hventy-FOUr (24) hours in atlvance for all inspections antl shall receive written approval on inspec[ion card beFOre proce[:tliing with successive phaus otthe job. (6) The is,auance of a permit or the apProval of tlrawings and specifcations shall not be constmeU tO be a permit for, nor an approval of, any violation of the provisions of e b'Iding codes or any oMer ordinance, law, rule or regulation. 71 ^ l L hief Building Inspector For ayor ThIIS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION DEI'AF2TMENT OF PLANNING AND DEVELOPMENT Building Permit Number : BUILDING INSI'ECtION DIVISION - 235-2855 CITY OF WHEAT RIDGE Date : 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 PropertyOwner: CAMBRIDGE VENTURES L.L.C. ProperiyAddress: 4050 MRiller SC, Phone! 592 9600 Contracbr Llcense No. : Wh 1889~dge CO 80033 Lot# 86 Company: TRITON DEVELOPMENT L.L.C. Phone: 592 9600 835 Delaware St. Qenver se 89294 OWNER/CONTRAC70R SIGNATURE OF UNDERS7ANOING AND AGREEMENT , I hereby ce~flly Ihnl the selbeck dislancee ptoposed by Ihie permif s and do not violale ap Iieable ordinancee, rules or regulatlons of the covenants, 9asemenPe or reslricllone ol recoid: lhat ail meaeureme made are aecurele; Ihal I have read and agree lo abide by ell eondl applieallon, end lhat 1 essume full reaponsib lor comPllanee wllh Code (U.B.C.) and all olhar applicable Idga ordicesi (OWNER)(CONTRACTOR) Description : SINGLE FnMILY ESIDENCE SIC G BUILDING DEPARTMENT USE ONLY zo-fi11i~~C~hiFffiRt3~ ie z3 '~b Approval : ~✓m '"F✓~ Zonin9 : pRr7 Approval: Approval: Occupancy : Walis : Roof : Slories ~ ~ 'S. 7otai : ( 8 , 6. Sq. Ft. : ~z5 + Resldentfal Units : ElectricalLicenseNo:77997. PlumbingUcenseNot8982-,,. MechanicatLicenseNo: 17977 Company:NO SHORTS ELECTRIOompany:TM PLOMHING Company: KCA COMPANIES Expiralion 0 : 2g/97 npproval: ~ Pi a~at (1) Requallonaend (2) 1Ma permll $hMl ebendonedla e (7) II thh permll exp I ei In a or Expiralfon Date : /3 Explralton D 5 /9 Approval : ~ApprovAl : )I~ 1m ~,rian~,Raqui~s~,~ ~ ~~IansRaqatr~n3~'&il Ith the Orovlelons sel lorth In yopur applleallon and is eublect lo the lawe ol ll+e Slels ol Colorado and lo the ioning 1 Rid e. Coloredo or eny olher aDDll"ble ordlnencee of Ihe Ciry. ulhorPzed Is nal eommeneed wllhln alzty (BO) days Irem beue dale or (A) the butldMq eWhodzed le sueDmded or be ecquired lor a fee ol one-half the amount normally requhed. Drovided no chenp!s hevh been or wiM Ae mede In Ue y suepeneion or abandonmenl ha nol ezeeeded one (1) year. 11 chenqef ue made a H me0enelon or ebendonment oal7 for e new permlt, iat will change Ihe nalural now of weler ceaeing e inaye problem. edor Iwenty-IOw (29) haure In advanoe ior aIl In ~ine Bnd shall iecelve wdll ~ ova Inion ta~d beforo he ob. il o~drawinge And epeNfkalions shan nol be ne d lo be a permll lor, nor ep al vio Ilon of the provieiene ance, law, rule or re ulalion. / ConstrucUon Value . JI { ere accorate, Permlt Fee : ~Ql S~ ieal Ridge or and allegallons Plan Revlew Fee : d on !hb 1 Ridge Building USB T81C : ~ 4 c~5 r ihis permit. ~ D Chief ViIding Inspeclor For Mayor - - TlIIS PERMIT VAIID ONLY WHEN SIGNED BY THE CNIEF BUILDING WSPECTOR AND AYOR CALL: 234-5933 24 FIOURS PRIOR TO INSPECTION . DEPAR7'MENT OF PLANNING 4 DEVELUPMC:t::REQUEST FOR PUBLZC SVORKS REVZEN Dste; Case/Building Permit No. Loaation: _Sit Lol -e 86 aYeas~`T~e ~ ew the attached materials submitted in application for approval of , and indicate your decis:on on those items checi; below, and please add any other comments which you ma; r.a.-e under number 18. 1• Soundary C1osuYe: ~OK _ Not OK; refer t, ~,c~pulations 2• L- AYea: Acres Square 3. Drainage: a. Drainage plan (and report) needed b. D=ailtage plan not needed P. Drainage provisions have been reviewed and are found to be: X OK _ Not OK; refer to stipulations 4• ~NPDES Permit Required ~ N 5. Legal Deserip tion: ~'OK Not oK; eefer to stipulations If not okay, please explain: 6. % P13bZiC Improvements:-(~~ ~j0-'A AJGQUG 'a'I~y/~'~a"~` `^'~ro~e~P~n-~ -7p~Cr~tDlr•~ a. Street paving needed N b. Curc & Gutter needed(E) N c. SideWalk needed Y N d. Street Lights neede~ N e. Stol~n Sewer needed N f. Escrcw required N If Escrow required, for wha impr vem? Tn uhat qmount? 7. ~ Development'Agreement required ~ N If Yes, for car,~i~~fzc/ 8. All necessary documents have been initiated Public works and are attached hereto: "Z 9 c . ~~Is a traPfic impact analysis and report reqc::ed? ~ N 10. ~s a State Highway Access Permit needed? z NO 11. _ New roadway or alley R.O.W. dedication i§ r,~ c9~mm ended: If yaa, what ie recommended: 12. 11 eXi ting dedicated roadways and alleys meet the standards of the City: ~tp If no, which do not and what is requested: 13. _ 11 eXisting and proposed dedications have been reviewed and found to be: ~,c OK _Not OK; refer to numbers 11 & 12. 14. ~~Approval Th Public Works Department has reviewed this request and hsrsby giv s it approval, subject to the above and/or attached stip at na. .e~ /0/29~ 9.6 Sianat e Date '~'15. _ The PubliC Works Department has reviewed this request and does not approve ior the reasons stated: Signature Date 16. ~ Stipulations attached: Yea N~ 17. DEADLINE DATE FOR PUBLIC WORKS DEPARTMENT kEPLY: A: \PLAN&DEV. r..., (F.....-,S) z ~ ~ iA o~5 o~ r. c N S< Z~lo n o'N $~w I I• x w I raaa *"iMMn~ zzzz cooo 1314111 NCr ~ ► Ito, Ior i ~ o~ ur 3/r ..s~w ":.cu SWM lK Y I/I YCIMY.' l, PdMl fi C~Nl n~v o' [ lesvrm) wu• wr vh veuna r ~-J in I REST 38th AVENUE 1$' HEREBY DEDICARD 41 Y~SML~ f0 ME Gtt Of MHEAT ItID~ .5. ].~N 5 0917'43" W 539.38' , ,a.,.1. . • ~ ♦ ~ ~ ( / ♦ \ ~ ~ ~ U X - °:p~ r U 1 ~ti ,sy ~ wb8 ~ ° - - - - 5 ~ / I I~ ~ ~ U~ I xasc / , s eu-zs'oo• w tjv _ xy ~ ~ € g ~ ~S ' i ~a~ ~e \ -4 ~ ~ rl s ~ ~9A a N ~w • X~ ~ OI zw.or ~ W I r 5 O ~ x • ~ ~ ~ is e924•00' w xw.or ~ ~'^a ~ `"7 • ~c / ' ~1 ,y • • , ~ ~u ~ ---i--~-- -----~PS X ~M I ' S $zi gg I I'' I . i o a ~ m \ I I I ~S - N r ~ xa0 $z \ \J ~o - e--r I Sa ~ ~~8 ~ I 7~ i I ~ gN ~ R i dn ~ &u \ i/ ~ i ~ ~ 0 ` Va`ipr I I I 1 ~ ! 9'24'00" E 219 O1, 4 ~ Y N N t AV - 1 N 89'24'00' E r ee1.79. 1e ENUE 40' R01/-' M.'IIM[YL LI M 4 I/~ Y I/~ mo , I ~ ~ ~ ~ fz ul ~ 1 04 a~r~M t R~ a E ~ ~ n ~ Aafi ~ ~'d x 110 f~yNM V/~ lr J^ 4~VJ N ~ ~N~Li 'I'PI'Tt)N DEVELOF'_EMFIVT C,'AMBRIDGF PARI< PLOT PLAN ~ ~ c. a¢. CIO h 1=157.I1' MILLER S1 5i861VISI0N~ CAMBRIDGE PARK 1 ADDRESS 4050 MILLER 5T L. ~ IDRAWN BY_~dc~~ ~JO8 NQ.: ~UiNIMUM 5ETBACkS: FR014T: 20' REA?' iC' ~ASI I A ~.~PE A, T S \ \ i' / ~r f3~ ng PLATTE! REVI3101J5: ~ REV N5~"I . ° . 10--04-96 _ 519E 0' CORNER: DRIb'EWAY GF.Hi1•' p~oRIA -ilk. '•~.1~ ' !n u_r°veyi~~~,~', Il~ e: 80014 ~ Pi,ane !'OSl 750-45~;. ~ ~,e.~~r~ a 2 _i @ .~f~k~ °~e. r ~~j f C .~Y - 31 r t i A 1 Y r ~ .  p YM v M ~ • ~ t ~`V.. F 6 4 >uw ~ . ,.a,~n:~ _ p~ 4t m~~ ~y.~d" iri~r, ~~YeA4 UM:. r~. ~.y.. _ m ) ~r ~ ` ~ ~e A. j k ~ ~ ~ ~ ~ M yx,. '~q .j~ ` Win' ~ ~ r e r e ~ R~ ~:~~4 1~ 4 ; m A t ~ e A r ~y 6p ~ o ✓ 4 ~FV~" "a~xF wyy. ~ r mrm. ~ ~ ~ !9 g~~` a~^ ~ y~ j *a ~xmMMe a. ~ br ~ .w..,•.BYffipn}n,re,~py. v,rm-sy~r,ra,..„' _ ~ ~ fi ~ N M 6l IP ~l~~wR t~ k ~2 a ~ g~F - k S m ~ , ~x b ;w~ s? ; a J ~m~"~e ~ , ~ ' ~ s i ~ 1 ~-w.4zweuaNwwuc,.ssa.~.vo~.g}m.~apw.wn.. w+,.m~ :E ~ ~ ~ . ~ t ~ '~y s c ~ ~ a~~ r r r P ~ Y ~ r p .~w ~ ~k i k ~ ~ ~ ~ ' ~ f jj wee ° a ryW ...M n 1 ~ .~va~q~rw~+v..wwr+,~~mrin~.nwmsmn ~ ~ i. ~ J~ 1^y N ; ~ 1 Y s ' ~ -l , ~ . _ ~ _ iw.~.. ~ ~f i ` ~ ~ << ~ t < ~ t'F ~ . - :AWE _ ~ ~ ct~- i ~ rk' j 4,.~..~ ,.~51 Z i, } ~ ~ ' pan ' j rc ,J ~ ~ - era ti~-..~ _ ~ ~ i~ a ii a° _°~b f , E ! _ - ~vm mpadq[an~. _ .t.. ~ ar .cone ~ ~ n as ¢a ~ - u vv^5n'aww+.wn'xissa ~ i~ F. ~ s; ~}x~ r: IIIx ' C .~+"t" ..'.F z ~ , m. ~ a.: d nve.,.~. a rm ~..rmun..;:li .a. s. w..m . r I !y d ~ ~ Y '1 a Ur't'; :d a x . n~ , ....>u, M..._ awe......... , , „w.w..n...., , y re . _ 4f f t "m <<~-. 1 i n y..... emu- ...r~ ~ zaoa~.M ~ ~ ~•a N ~ ~ ~ jj ,,fir ' x~,~; _.~w,~ . u. w r~.~.ra„,.~„ ~ ~ W _ r.. w_ ~_.r, b _ _ ~ qq ~:1 ~ p F 1 ~ a ":n i t oa, x~~,.;~+,~,~.,R,~,w„.~a~s ~.n~,.xi~.,.~.,,P~,ro~wen~w,~.x.~~,.~+uwt-.e+~m~.~n ~+s.,.aun~,mm, „no. `a<....,~,~.~ "ii.~d'~ 4 T. Y :t ~ ~ p i a - s yz h ~ ~ i s,-_«.w , 1a a j f q uo.. G ..rt, 3 , ~y -..«.~~~,~.~~na~ar:~s.~w«un~ aa+o+nuwn.+z n ~ .inn m ,.enra„.,. nn, m Po.. ~ n ma .g..... ,...,w ,~...w.~...._.,. N ! ~ Q .n ` 1 ' ~ s 4,r. (f u ~A A ' 2 (FS 1 L E t E ~ rr, a' y~ ~ , ~ y { ..x: ,...;,.W e.,..«. i - ,»,n,~~w.~.e+~..~,.,»~.u..rv:.«~wW.,,~,~,a;uw+x.+xim,.,rr~»: ~..,.,emd..amw~w,~ arrw,n+m~m~..mx .w .ey_....cem..._~; j i. f ~ ~x ! a i 1 S Y _ , _ . n ~ _ ^°.v i j { i 6 ~4 9 @ ~w<k~~ ~ ~ ~ s P~ .  d ; - q , s ~ LUALKOUT a 7 P i i D f= ~ hti E; rX ; 9 } { xt ~ ~ ~ . ~ s ~ ~ B~ ~ ~ ~ ~.r i ~ ~ ` I ~r Fdi F~} a .w u, m mub,~ ~ .e.~.m ~,..~m.d ~ u.~~.,w.~W..~_ ~a o__~~~___ ~ ~3, I ~r` 3 z. p F ..aws,-.,',~.wi.n. ~,b...nwrn~w..e avRr+'4ym~,.<taw.-..~„o¢,- m, - - ~ ~ - e. - ~ ~ u - ~ ~ - ~ ~r - v` :7 P - • - R a a ~ i ~ ~ ,_~r ~h~ ~ ~ , ' ~ , r ii e a t1 y _r.~. Q i~ a ,y. ~x r 1 4 F. ~ ~f m jet ~Y i .~~.e,.~~_.~~~._.__~_~_..~~,,.~. 6 1 'fie:,, ~ ~ r ` } S Y_; J ~~'i  ~~y ~ r~ n s ~ , , . . , ~ ~ ~ a ~ i a~ [ ~ ~ a z ~ F 'spa Q¢~'~ . p ~ ~ a.TM , ~ ~ , t , =r~.~ a 1,. ~ ~ ,1.. . a ' ~ ~ r w 3, t a, E a t ~ ~ ~ i.!i.~ d'am' . ~ . e,rzz~ ,at€ p _ r ~ r . ~ ~ , E i { p ~ ,f~ a~ t ~ l~ ~ . ~R, - : M. 4 A:•~.~...~Mew31Wn!u➢SWB,Mdtffi H.MNSS.s;,. .•,~lF^~h.}ti~:g'n w-,^.v .i pr •?tiiL:0hp3rbWm;.mx:& F a y. 6 Y ~ 3 ~~4 t~'v o - ~ ~ ~ L - f E a, - x E r s i , a, t w~ti Y ^jt'„ 7 3d y F . ~ i w. j. ~ ~ f ?a^ ~ ' J „ 4 ~ ~ ~ ~ ~ ~ n~ N-• w fi . n. ...:::ssw. w•~lnr'-..: _amu2v.:.4~.sFC~Anxa.Mrv. v . ,.,.......>+~rtw :....raNMM• µ a. b ym~xsw.arm~me gyp. . ~ i i.. 5 t; a ) -~r.~n...-,. .fin rc~i~_ .iNTYlala ~ } $6g 1 MMM ~ 4 1 g ~ k ~ ~ rw" r ~4 ~ ~ ~ ~ ! ~ ~ ~ ~ ~ r E _ ,,,.,4 3 { 4 hi' i$ Via. ~ i k~ .....rnnaaar w ;+aamx k ww w, ZZ Wow. y v '.f x i . _ .e.~ i 3 i t