HomeMy WebLinkAbout4980 Kipling Street4980 Kipling St 202001889 FRONT RANGE TEST & BALANCE 11111*11 will 01U1 -fill Will 011d=1111N4161:AI FOR CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING STREET WHEAT RIDGE, COLORADO MAY 2021 MECHANICAL CONTRACTOR: CRYTON IJiI x91: /e1011190 a 4 01 m1011440KC31// =I 01[:11eFI-16191 Fill *? ARCHITECT: CHORD DESIGN STUDIO, PC. PREPARED BY: FRONT RANGE TEST AND BALANCE, INC. Front Range Test & Balance, Inc. certifies that all balancing is done in accordance with NEBB, AABC and ASHRAE standards. P.O. Box 630112 • Highlands Ranch • Colorado • 80163-0112 FRONT RANGE TEST &. BALANCE May 7, 2021 Building Department Wheat Ridge, Colorado RE: CLEAR CREEK ANIMAL HOSPITAL To Whom It May Concern: All test and balance work on Clear Creek Animal Hospital in Wheat Ridge, Colorado has been completed in accordance with NEBB, AABC, and ASHRAE standards. Please let me know if you need anything else with regard to the Air Balance Report for Clear Creek Animal Hospital. Sincerely, Chris Cooper President Front Range Test & Balance, Inc. FRONT RANGE TEST AND BALANCE FAN TEST REPORT PROJECT: CLEAR CREEK ANIMAL HOSPITAL FAN DATA FAN NO. E RTU -4 FAN NO. EF -1 FAN NO. EF -2 Location ROOF CEILING CEILING Service OFFICE/BREAK RESTROOM MOP SINK Manufacturer CARRIER GREENHECK GRENNHECK Model Number 48VL-C4813030 SP -A290 -C SP-B150-QD Serial Number 1917C43491 17784727 116583209-0029 Motor Make/Frame NG/NG MCMILLAN/NG GRENNHECK/NG Motor H.P./RPM 1/NG 1/29/1050 NG/1050 Volts/Phase/Hertz 208/230/1/60 115/1/60 115/1/60 F.L. Am ps/S.F. 7.6/TP .83/TP 1.8/TP Motor Sheave Make DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE Motor Sheave Diam./Bore DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE Fan Sheave Make DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE Fan Sheave Diam./Bore DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE No. Belts/Make/Size DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE Sheave CL Distance DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE Filters 1-16"X25"X2"/1-16"X20" X2" TEST DATA DESIGN ACTUAL DESIGN ACTUAL DESIGN ACTUAL CFM 1000 1056 75 243 50 161 Fan RPM NG DD NG DD NG DD Outside Air 180 0 Voltage 208 207 115 121 115 122 Amperage 7.6 5 .83 .65 1.8 1.1 REMARKS: TEST DATE: 5/7/2021 READINGS BY: CC&VL FRONT RANGE TEST AND BALANCE PROJECT: CLEAR CREEK ANIMAL HOSPITAL SYSTEM: E RTU -4 AIR OUTLET TEST REPORT TEST APPARATUS: FLOW HOOD AREA OUTLET DESIGN PRE IMINARY11 FINAL I FINAL REMARKS SERVED I NO. TYPE SIZE I AK I CFM L VEL/CFM CFM % 1 CD 24"X24" 1.0 125 208 131 105% 2 CD 24"X24" 1.0 125 222 128 102% 3 CD 24"X24" 1.0 50 145 53 106% 4 CD 24"X24" 1.0 100 132 109 109% 5 CD 24"X24" 1.0 125 135 129 103% 6 1 CD I 24"X24" 1.01 350 1 207 1 376 1 107% 7 CD 24"X24" 1.0 100 107 103 103% 8 CD 24"X24" 1.0 25 72 27 108% TOTAL 1000 1228 1056 106% REMARKS: O CORRECTED FORALTITUDE TEST DATE: 5/7/2021 READINGS BY: CC&VL UPT,/ (E)RTu-3 5/12/2021 Report Arvada Fire Protection District Fire Marshal's Office 7903 Allison Way - Arvada, CO 80005 Main 303-424-3012 - Fax 303-432-7995 www.arvadafire.com Occupant Name: Clear Creek Animal Clinic Contractor: Pete Alarid ❑ ❑ 1@ Foothills Commercial ❑ ❑ ® Builders Inc ❑ ❑ ® 303-859-7870 c Address: 4980 Kipling Street Inspection Date: 5/11/2021 H Wheat Ridge, CO 80033 ❑ 155 Fire alarm final Job Number: 200923002 -KK InspectionType: Tenant Finish/Remodel Job Description: Renovationlexpansion of Inspected By: Kevin Kirby H existing animal hospital. No ❑ 303-228-3610 0' change of use. ❑ kevin.kirby@arvadafire.com Pass Fail N/A Custom Codes At the time of this inspection, no discrepancies or violations have been found. By no means does this exonerate you from responsibility to adhere to all pertinent codes and restrictions. Status: Approved With Conditions Inspector:4;9�11 sq.aanvaaa:, n roar.w. aaam.aa Kevin Kirby 5/11/2021 https:Uwww.mobile-eyes.com/PA Report TabletReports.asp?Mode=Bldg&Type=Full&FullText=F&PIOID=6822 1/1 Tenant Finish ❑ ❑ 1@ 151 Radio signal strength testing completed (>5000sgft only) ❑ ❑ ® 152 Knox box installed ❑ ❑ ® 153 Keys for Knox box ❑ ❑ ® 154 Fire sprinkler final H ❑ ❑ 155 Fire alarm final ❑ ❑ ® 156 Special hazard / extinguishing system final ® ❑ ❑ 157 Fire extinguishers installed H ❑ ❑ 158 Means of egress illumination 0' ❑ ❑ 159 Means of egress identification ❑ ❑ H 160 Interior signage - to include stairwells, occupant load etc. (if required) ❑ ❑ ® 161 Exterior signage - (Address, FACP, Sprinkler Riser, Electric room, etc) ® ❑ ❑ 162 Door hardware is compliant ® ❑ ❑ 163 Construction material storage removed from premises ® ❑ ❑ 164 Other At the time of this inspection, no discrepancies or violations have been found. By no means does this exonerate you from responsibility to adhere to all pertinent codes and restrictions. Status: Approved With Conditions Inspector:4;9�11 sq.aanvaaa:, n roar.w. aaam.aa Kevin Kirby 5/11/2021 https:Uwww.mobile-eyes.com/PA Report TabletReports.asp?Mode=Bldg&Type=Full&FullText=F&PIOID=6822 1/1 � ► 44" City of Wheat Ridge '/� Comm. Tenant Finish PERMIT - 202001889 PERMIT NO: 202001889 ISSUED: 02/24/2021 JOB ADDRESS: 4980 Kipling St Ste A-6 EXPIRES: 02/23/2022 JOB DESCRIPTION: Interior remodel and expansion of existing animal hospital. Interior of existing space and adjacent tenant space. New door, deck and stair in alley. Sq ft: 3,675 *** CONTACTS *** OWNER (303)292-5608 CAROL PECK LIVING TRUST GC (303)792-5901 WILLIAM J. HOLLINGSWORTH 150307 FOOTHILLS COMMERCIAL BUILDERS SUB (303) 432-1041 PAUL M. KNAPP 020962 FRESCO ELECTRIC INC SUB (303) 789-2740 DANIEL E. PARSONS 020070 CRYTON INC SUB (303)419-5225 LOUIS BUCCINO 018490 BUCCINO PLUMBING *** PARCEL INFO *** ZONE CODE: UA / Unassigned USE: UA / Unassigned SUBDIVISION CODE: 330 / General Retail BLOCK/LOT#: / *** FEE SUMMARY *** ESTIMATED PROJECT VALUATION: 220,000.00 FEES Total Valuation 0.00 Plan Review Fee 11238.93 Use Tax 41620.00 Permit Fee 11906.05 ** TOTAL ** 71764.98 *** COMMENTS *** *** CONDITIONS *** All roughs to be done at Framing Inspection. A printed copy of the permit and city stamped on-site plans must be available on-site for the first inspection. Approved per plans and red -line notes on plans. Must comply with 2018 IBC, 2020 NEC and all applicable City of Wheat Ridge Municipal Codes. Work is subject to field inspections. **Prior to final inspection approval - As-builts are required before approval of the Building Final Inspection and Certificate of Occupancy can be issued. 1* � 4 41' PERMIT NO: JOB ADDRESS: JOB DESCRIPTION: City of Wheat Ridge Comm. Tenant Finish PERMIT - 202001889 202001889 ISSUED: 02/24/2021 4980 Kipling St Ste A-6 EXPIRES: 02/23/2022 Interior remodel and expansion of existing animal hospital. Interior of existing space and adjacent tenant space. New door, deck and stair in alley. Sq ft: 3,675 I, by my signature, do hereby attest that the work to be performed shall comply with all accompanying approved plans and specifications, applicable building codes, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with this�permrt. I further attest that I am leg ally authorized to include all entities named within this document as parties to the work to be performed and that all work to be performed is disclosed in this document and/or its' accompanying approved plans and specifications. Signature of OWNER or CONTRACTOR (Circle one) Date 1, This permit was issued based on the information provided in the permit application and accompanying plans and specifications and is subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures. 2. This permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and received prior to the date of expiration. An extension of no more than 180, days made be granted at the discretion of the Chief Building Official and may be subject to a fee equal to one-half of the original permit fee. 3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard requirements, fees and��procedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of the Chief Building Official and is not guaranteed. 4. No work of any manner shall be performed that shall results in a change of the natural flow of water without prior and specific approval. 5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all requ�ired inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services Division. 6. The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, anviolation of any provision of any �pplicabje code or any ordinance or regulation of this jurisdiction. Approval of work is subject to field inspection. 02/24/2021 Signature of Chief Building Official Date REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. From: no-reolv(alci.wheatridae.m. us To: CommDev Farm is Subject: Online Form Submittal: Commercial Interior Remodel/Tenant Finish Date: Monday, September 21, 2020 2:26:54 PM Commercial Interior Remodel/Tenant Finish Application for Commercial Remodel/Tenant Finish This application is for Commercial Remodels and Tenant Finishes. Do not being work until the permit has been issued to the General Contractor. Required to Submit Proof of Submission to Fire Department Proof of Submission to Arvada Fire - proof of submittal.Ddf Fire Department Begin Application PROPERTY INFORMATION Property Address 4980 Kipling Street, Ste A6 Property Owner Name Carol Peck Living Trust C/O Rio Real Estate Property Owner Phone 303-292-5608 Number (enter WITH dashes, eg 303-123- 4567) Property Owner Email nsimkowitz@rio-realestate.com Address Attach City of Wheat Electronic Payment Form City of Wheat Ridae odf coov to JK 9 - Ridge Electronic 17-20 Ddf Payment Form - "DO NOT ATTACH A PICTURE OF A CREDIT CARD" APPLICANT INFORMATION Contact Name of Robert Forslund Person Submitting Application What is your role in the Architect project? Contact Phone Number (enter WITH dashes, eg 303-123-4567) Contact Email Address for Plan Review Questions 303-694-2445 rforslund@chord-ds.com Retype Contact Email rforslund@chord-ds.com Address DESCRIPTION OF WORK Is this for a new No tenant? Business Name of Clear Creek Animal Hospital Tenant Detailed Scope of Work - Provide a detailed description of work including mechanical, electrical, plumbing work occurring, adding/removing walls, etc Iii .i . STiTtamr, Square Footage Area of Work Being Performed Asbestos Report - if applicable Construction Plans scanned on 11'x17" or larger Interior remodel and expansion of existing animal hospital. No change of use. Interior of existing space and adjacent tenant space. New door, deck and stair in alley. 3675 Field not completed. 2020-09-15 - 20019 - Clear Creek Animal Hosoital - Permit Sett Ddf Project Value (contract 220000 value or cost of ALL materials and labor) $220,000 Valuation is OK SIGNATURE OF UNDERSTANDING AND AGREEMENT I assume full Yes responsibility for compliance with applicable City of Wheat Ridge codes and ordinances for work under any permit issued based on this application. I understand that work Yes may not begin on this property until a permit has been issued and posted on the property. I certify that I have Yes been authorized by the legal owner of the property to submit this application and to perform the work described above. I attest that everything Yes stated in this application is true and correct and that falsifying information in this application is an act of fraud and may be punishable by fine, imprisonment, or both. Person Applying for John Krol Permit Email not displaying correctly? View it in your browser. �6 A! "� Wh6a-ttPs'* dge �MMUNITY DEVELOPMENT SUBCONTRACTOR AUTHORIZATION FORM I Electrical Subcontractor This form must be completed & signed by the ELECTRICAL SUBCONTRACTOR performing electrical work on site. Subcontractor's insurance and license must be up to date prior to permit issuance. Project Address: '1 , General Contractor: ��-�AL �� W1 Q —8( N _LC LO AS ill ■ 111uliffell wool:. i ■11,11i► i Company Name: )� ��[Contact Phone #: � - �8� �bl Wheat Ridge Contractor License #: M0(required field) State License Master License #:_ D) L , Ci? Z 5 $ '�- 1 4U-mFWAAce Printed Name of AuthdiWd Agent �aj— Signature of Author' gent Date City of h16 at ge SUBCONTRACTOR AUTHORIZATION FORM Mechanical Subcontractor This form must be completed & signed by the MECHANICAL SUBCONTRACTOR performing mechanical work on site. Subcontractor's insurance and license must be up to date prior to permit issuance. Project Address:General Contractor: Contractor:�"� FORM WILL NOT BE ACCEPTED WITH MISSING INFORMATI 3,N Company Name:,Q-Ij� -- Contact Phone #: -,"� - e Z-1 4 Wheat Ridge Contractor License #: 0Z0Qq0 (required field) Printed Name of Authorized Agent 'gnatu a of Authorized Agent 22,5-2-1 Date City of Wh6atf�id ge wMUNITY DEVELOPMENT SUBCONTRACTOR AUTHORIZATION FORM Plumbing Subcontractor This form must be completed & signed by the PLUMBING SUBCONTRACTOR performing plumbing work on site. Subcontractor's insurance and license must be up to date prior to permit issuance. Project Address: (�';A iZ L �` General Contractor: FORM WILL NOT BE ACCEPTED WITH MISSING INFORMATION Company Name: Contact Phone #: Wheat Ridge Contractor License #: CEJ 4U (required field) State License #: oy—) Master License #: / LID % 6 r Printed Name of Authorized Agent Signature of Authorized Agent Date 9/21/2020 Permit Application I ®MObileEyes Contractor Permit Portal Need Help? L lM1l LIX6 A SAF!! WORLD User Options Welcome back Michael Slater (Chord Design Studio) Eog Off Update Account Tyler Privacy Policy Applications City/Dept.: Arvada Fire Protection District lication 0 Just My Jobs (0 All Jobs for my company Address: 4980 Street: Kipling Street Status: *All OUnsubmitted OSubmitted OReturned Address Clear Creek Animal Clinic STE 6-7 4980 Kipling Street Wheat Ridge, CO 80033 Occupant Job Type: v Search Clear Filters Job Type Status Tenant Finish/Remodel Submitted 9/21/2020 4:17:44 PM Active Jobs 0 Just My Jobs All Jobs for my company Address: Occupant: Street: Job #: Schedule Status: Search *All OScheduled OUnscheduled Clear Filters Address Job Type /# Status Schedulinq Invoices 4 No matches Completed/Canceled Jobs 0 Just My Jobs 0 All Jobs for my company Address: Occupant: Street: Job #: Status: https://Www.mobile-eyes.com/PA_index.asp 1/2 9/21/2020 Permit Application ®MobileEyes Contractor Permit Portal Need Help? ENABLING A SAF!! WORLD Address Job Type /# Status Invoices No matches https://www.mobile-eyes.com/PA_index.asp 2/2 DS Environmental CONSULTING "The trusted choice for your environmental & industrial hygiene needs." ASBESTOS INSPECTION REPORT 4980 Kipling St, Unit A6 & Unit 8, Wheat Ridge, Colorado PRESENTED TO: Mr. Kenneth Lindsey Lindsey & Associates, LLC (303)514-0575 ken@lindseyandassoc.com Front Range 7555 W 10th Ave Suite A, Lakewood, CO 80214 INSPECTED BY: Mr. Zack Westfall DS Environmental Cell: (303) 304-1329 Mountains PO Box 6864 Avon, CO 81620 Web dsconsultinginc.com Direct (303) 286-9094 PROJECT DETAILS: DS Job Number: 21758 Date of Inspection: October 28, 2020 City of Wheat Ridge Building Division Western Slope PO Box 3793 Aspen, CO 81612 Fax (303) 986-0121 Table of Contents 1.0 Introduction 2.0 Limitations of Inspection 3.0 Conclusions & Summary of Findings 4.0 Material Information 5.0 Inspector & Firm Certifications 6.0 Inspection, Sampling & Analytical Procedures 7.0 Recommendations 8.0 Asbestos Abatement & Demolition Requirements 9.0 Major & Minor Asbestos Spill Response Actions 10.0 Project Design & Project Manager Requirements 11.0 Disclaimer & Limitations 12.0 Copyright Notice APPENDIX A CERTIFICATIONS APPENDIX B LABORATORY REPORT PJ City of Wheat Ridge Building Division 1.0 Introduction Mr. Zack Westfall with DS Environmental Consulting (DS) conducted an asbestos inspection and collected bulk - samples of suspect asbestos -containing building materials within the commercial units detailed on the cover page of this report. The purpose of the inspection was to determine if any of the materials that may be impacted by the renovation activities contain asbestos. 2.0 Limitations of Inspection This inspection was limited in its scope and only included specific areas and materials as defined by the client. The inspection did not constitute a full -building inspection and does not fulfill the asbestos inspection requirements for structures that are to be demolished. The table below, (Table 1.0), lists the suspect asbestos -containing materials included in the scope of the inspection. It identifies the specific areas that were included in the inspection as well descriptions of the suspect asbestos -containing materials in those areas that were sampled; or materials that were assumed to contain asbestos. The suspect asbestos -containing materials listed below may be found in other areas of the building that were outside of the scope of work for this inspection and sampling. Additionally, there may be other materials in other parts of the building that contain asbestos, which were not included in the scope of this inspection and sampling. Table 1.0 Scope of Work Materials in RED are materials that contain greater than 1% asbestos or are assumed to contain >1% asbestos. Materials in GREEN contain 1% or less asbestos Materials in BLACK do not contain asbestos. Suspect Asbestos -Containing Materials Sampled Material Locations Homogeneous Area 1(SM 1) Orange -Peel Drywall Texture Dividing Wall Between Units Interior Walls in Unit 8 Homogeneous Area 2 (JC1) Joint Compound Associated Dividing Wall Between Units with SM1 Interior Walls in Unit 8 Homogeneous Area 3 (CDW1) Joint Compound on Interior Walls Within Unit A6 Untextured Drywall Homogeneous Area 4 (LIP1) 2x4 White Lay -in Ceiling Panel Unit A6 Ceiling Grid Homogeneous Area 5 (LIP2) 2x4 White Lay -in Ceiling Panel Unit 8 Ceiling Grid w/ Large Fissures Homogeneous Area 6 (LIP3) 2x4 White Lay -in Ceiling Panel . Unit 8 Ceiling Grid w/ Small Pinholes and Fissures City of Wheat Ridge 3 Building Division Homogeneous Area 7 (CBA1) Brown Cove Base Adhesive Unit A6 Interior Walls Homogeneous Area 8 (CBA2) Beige/Gray Cove Base Adhesive Unit 8 Walls Homogeneous Area 9 (CA1) Yellow Carpet Adhesive Unit 8 Floor Homogeneous Area 10 (WTA1) Ceramic Wall Tile Adhesive North Wall in Front Room of Unit 8 Homogeneous Area 11 (SUC1) Gray Sink Undercoating Sink in Middle Room of Unit 8 Homogeneous Area 12 (FT1) Faux Wood Vinyl Flooring Floor on West Side of Unit A6 rd City of Wheat Ridge Building Division 3.0 Conclusions & Summary of Findings Materials in RED are materials that contain greater than 1% asbestos or are assumed to contain >1% asbestos. Materials in GREEN contain 1% or less asbestos Materials in BLACK do not contain asbestos. Sample Information ACRONYMS ACM ASSESSMENT CATEGORIES 1—damaged/significantly damaged thermal system insulation ACM SUMMARY OF CHRY— Chrysotile ACT—Actinolite 2—damaged friable surfacing material ACM FINDINGS TR— Trace; >1%Asbestos 3— significantly da maged fria ble surfacing material ACM ND — None -detected 4— damaged or significantly damaged friable miscellaneous material ACM ACM —Asbestos Containing 5 —ACM with the potential for damage Material (>J% asbestos) 6—ACM with the potential for significant damage Classification: Surfacing Material 7—any remaining friable ACM or friable suspected ACM Materials in RED are materials that contain greater than 1% asbestos or are assumed to contain >1% asbestos. Materials in GREEN contain 1% or less asbestos Materials in BLACK do not contain asbestos. Sample Information Material Information Asbestos Content Sample ID: SM1-1 Sample Location: Unit 8 — Middle Room — Description:Orange Peel Drywall Texture W North Wall cc Classification: Surfacing Material V) Sample ID: SM1-2 Condition: Good 0 Sample Location: Unit 8 — Middle Room — Quantity: —800 ft2 ND w East Wall Friability: Friable C7 0 Assessment Category: No Category (Non -ACM) Sample ID: SM1-3 Reason for Assessment: = Sample Location: Unit 8 East Room — North Wall N Description: Joint Compound Associated w/ SM1 W Sample ID: JC1-1 a Sample Location: Unit 8 — Front Room — Classification: Miscellaneous Material V) Northeast Corner Condition: Good uantit : —800 ft2 ND w Sample ID: JC1-2 Friability: Friable 0 Sample Location: Unit 8 — Middle Room — Assessment Category: No Category (Non -ACM) Southeast Corner Reason for Assessment: x City of Wheat Ridge Building Division 11 City of Wheat Ridge Building Division Sample ID: CDW1-1 rn Sample Location: Unit A6— North Middle Description: Joint Compound on Untextured w Exam Room—Southeast Corner Drywall cc a Classification: Miscellaneous Material � Sample ID: CDW1-2 Condition: Good 0 Sample Location: Unit A6—South Middle Quantity: 150 ft 2 ND w Exam Room — Northwest Corner Friability: Friable 2 Sample ID: CDW1-3 Assessment Category: No Category (Non-ACM) = Sample Location: Unit A6— Water Heater Reason for Assessment: Room — Northeast Corner v Description: 2x4 White Lay-in Ceiling Panel W Sample ID: LIP1-1 a Sample Location: Unit A6—Northwest Classification: Miscellaneous Material V) Exam Room Ceiling Condition: Good uantit : ^1000 ft2 ND w Sample ID: LIP1-2 Friability: Friable 0 Sample Location: Unit A6—Northwest Assessment Category: No Category (Non-ACM) Exam Room Ceiling Reason for Assessment: x Ln Description: 2x4 White Lay-in Ceiling Panel with W Sample ID: LIP2-1 Large Fissures aSample Location: Unit 8 — Middle Room Classification: Miscellaneous Material V) Ceiling Condition: Good z Quantity: —400 ft2 ND w Sample ID: LIP2-2 p Sample Location: Unit 8—Middle Room Friability: Friable 2 Ceiling Assessment Category: No Category (Non-ACM) x Reason for Assessment: 11 City of Wheat Ridge Building Division 7 City of Wheat Ridge Building Division Description: 2x4 White Lay-in Ceiling Panel with w Sample ID: LIP3-1 Small Pinholes and Fissures a Sample Location: Unit 8 — Middle Room Classification: Miscellaneous Material V) Ceiling Condition: Good z Quantity: —400 ft2 ND W Sample ID: LIP3-2 p Sample Location: Unit 8—Middle Room Friability: Friable 2 Ceiling Assessment Category: No Category (Non-ACM) = Reason for Assessment: Description: Brown Cove Base Adhesive W Sample ID: CBA1-1 a Sample Location: Unit A6—Reception Classification: Miscellaneous Material V) M Desk Condition: Good uantit : —30 ft2 ND w Sample ID: CBA1-2 Friability: Non-Friable 0 Sample Location: Unit A6—Recetion P Assessment Category: No Category (Non-ACM) 0 Desk Reason for Assessment: x Go Description: Beige/Gray Cove Base Adhesive W Sample ID: CBA2-1 aSample Location: Unit 8 — Front Room — Classification: Miscellaneous Material M North Wall Condition: Good W Quantity: —900 ft2 ND w Sample ID: CBA2-2 Friability: Non-Friable 0 Sample Location: Unit 8 — Middle Room — Assessment Category: No Category (Non-ACM) North Cabinetry Reason for Assessment: x 7 City of Wheat Ridge Building Division m Description: Yellow Carpet Adhesive w Sample ID: CA1-1 a Sample Location: Unit 8 — Front Room Classification: Miscellaneous Material V) Floor Condition: Good uantit : —600 ft2 ND w Sample ID: CA1-2 Friability: Non-Friable O � Sample Location: Unit 8 — Front Room Assessment Category: No Category (Non-ACM) O Floor Reason for Assessment: x 0 ~ Description: Ceramic Wall Tile Adhesive Sample ID: WTA1-1 W xSample Location: Unit 8 —Front Room — Classification: Miscellaneous Material V) North Wall Condition: Good OQuantity: —80 ft2 ND Z Sample ID: WTA1-2 Friability: Non-Friable W Sample Location: Unit 8 —Front Room — Assessment Category: No Category (Non-ACM) 2 O North Wall Reason for Assessment: x Description: Gray Sink Undercoating N Classification: Miscellaneous Material Sample ID: SUC1-1 Condition: Good W a Sample Location: Unit 8 — Middle Room — uantit 2 ft2 V) North Sink Friability: Non-Friable 0 15/ CHRY W Assessment Category: (6) Sample ID: SUC1-2 W O Sample Location: Unit 8 — Middle Room — Reason for Assessment: O 2 North Sink Potential for Contact: Moderate O x Potential for Vibration: Moderate Potential for Air Erosion: Low City of Wheat Ridge Building Division N ~ Description: Faux Wood Vinyl Flooring W Sample ID: FT1-1 cc Sample Location: Unit A6— Reception Area Classification: Miscellaneous Material V) Floor Condition: Good OQuantity: —500 ft2 ND Z Sample ID: FT1-2 Friability: Non -Friable W Sample Location: Unit A6—Reception Area Assessment Category: No Category (Non -ACM) 2 O Floor Reason for Assessment: x 4.0 Material Information A Homogeneous Area (HA) means an area of surfacing material, thermal system insulation material, or miscellaneous material that is uniform in color and texture. The asbestos content of the bulk -samples collected within a homogeneous area can be applied to the entire homogenous area, if they conform to the above characteristics and the regulated minimum sample quantities of each type of material have been collected and analyzed. An Asbestos Containing Material (ACM) is a material that contains more than 1% asbestos. Any material can be assumed to be an ACM, but not the contrary. 4.1 Material Friability A material can either be friable or non friable. A friable material is one that, when dry, can be pulverized, or reduced to powder by hand pressure, a non -friable material cannot. A non -friable material may become friable if its condition had deteriorated or has been impacted by forces that have rendered it friable. 4.2 Material Classifications Sampled materials are divided into one of the following three categories: • Surfacing Material: sprayed or troweled onto structural building members • Thermal System Insulation (TSI): any type of pipe, boiler, tank, or duct insulation • Miscellaneous Material: all other materials not classified in the above two categories 4.3 Material Conditions Sampled materials are placed into one of the following three categories of conditions: • Good: none to very little visible damage or deterioration • Damaged: the surface is crumbling, blistered, water -stained, gouged, marred or otherwise abraded over less than one-tenth of the surface if the damage is evenly distributed, or one-quarter if the damage is localized • Significantly Damaged: the surface is crumbling, blistered, water -stained, gouged, marred or otherwise abraded over greater than one-tenth of the surface if the damage is evenly distributed, or one-quarter if the damage is localized 9 4.4 Sample Quantities DS collected at least the minimum number of samples from each homogeneous area necessary to meet all regulatory requirements for the quantity of material to be disturbed in the scope of work as defined by the client. The quantities listed in this report are approximate and on-site verification of the exact quantity of each material is required for permitting, estimating and billing purposes. The following outlines the minimum sample quantities required per homogeneous area: • Surfacing Materials: up to 1,000 ft' of material requires a minimum of three (3) samples; between 1,000 ft' and 5,000 ft' of material requires a minimum of five (5) samples; over 5,000 ft' of material requires a minimum of seven (7) samples; one (1) sample of each patch • Thermal System Insulation (TSI): each homogeneous area requires a minimum of three (3) samples; at least one (1) sample must be collected from each patch; and collect enough samples sufficient to adequately assess the material and determine the asbestos content for TSI fittings such as pipe elbows or T's, which a minimum of two (2) samples of each • Miscellaneous Materials: collect enough samples sufficient to determine the asbestos content with a minimum of two (2) samples of each 4.5 Materials Reporting `TRACE" Results Any sample reporting a "TRACE" amount of asbestos shall be considered to contain greater than 1% asbestos unless it is further analyzed utilizing the point -count method and verified to be less than or equal to 1% asbestos content, and therefore not an ACM. TRACE does not mean it contains less than or equal to 1%. 4.6 Materials Containing 1% Asbestos or Less Materials containing less than or equal to 1% asbestos are not regulated by the Colorado Department of Public Health and Environment (CDPHE) Regulation 8, Part B — Asbestos. However, all demolition/abatement activities should be performed following the applicable Occupational Safety and Health Administration (OSHA) regulations. This includes, but is not limited to, the appropriate asbestos training for the type of material being removed/disturbed as well as having a properly trained supervisor onsite, using wet removal methods, wearing adequate personal protective equipment (HEPA-filtered particulate respirators), medical surveillance of workers, personal -exposure air monitoring, area air monitoring in occupied buildings, etc. There may also be landfill disposal requirements for these materials, depending on the facility. DS recommends that all demolition/renovation projects involving the disturbance of any amount of asbestos be subjected to post - work visual inspections and a final clearance air testing by a CDPHE-certified Asbestos Air Monitoring Specialist (AMS) after the work has been completed, but before any containments are dismantled, the contractor demobilizes, and the area is reoccupied. 4.7 Overspray Any surfacing material indicated in this report also includes any associated overspray of that material, e.g., under carpet, above suspended ceilings, on studs and structural members, etc. 5.0 Inspector & Firm Certifications The inspection detailed within this report was conducted by Mr. Zack Westfall with DS. DS is a CDPHE certified Asbestos Consulting Firm, Registration No. 14912. Mr. Westfall is a CDPHE certified Building Inspector; having certification number 22529 (see Appendix A for certificates). City of 10 Wheat Ridge Building Division 6.0 Inspection, Sampling & Analytical Procedures 6.1 Inspection Procedures The asbestos inspection detailed in this report was conducted by an Environmental Protection Agency (EPA) and CDPHE certified asbestos Building Inspector. The inspection procedures included identifying and sampling suspect ACM within the pre -defined areas that were within the scope of work, submitting samples to an accredited laboratory for analysis, classifying the materials and assessing their condition, and compiling a final report detailing the inspection and the analytical results of the bulk -samples. 6.2 Sampling Procedures Statistically random bulk -samples representative of the suspect ACM of each homogeneous area were collected according to the guidelines published in the Environmental Protection Agency's October 1985 publication, "Asbestos in Building: Simplified Sampling Scheme for Friable Surfacing Materials", commonly known as the "Pink Book." DS has collected the appropriate number of bulk -samples to meet all regulatory requirements for the classification and quantity of each homogeneous area. All reasonable efforts were made to identify homogeneous areas and to sample or assume suspect materials. Destructive investigation was conducted whenever feasible, and every effort was made to locate and quantify suspect ACM within the scope of work. Any material not identified and sampled in this report shall be assumed to be an ACM or shall be sampled by an EPA -trained and CDPHE-certified inspector and submitted for analysis. 6.3 Analytical Procedures All asbestos bulk -samples were analyzed by a third party, National Voluntary Laboratory Accreditation Program (NVLAP) accredited laboratory via Polarized Light Microscopy (PLM) for asbestos content per CDPHE Regulation 8 (see Appendix 8 for laboratory report). 7.0 Recommendations The asbestos inspection detailed in this report did identify ACM(s); therefore, professional abatement activities are required to remove or disturb the above -referenced asbestos -containing materials. 8.0 Asbestos Abatement & Demolition Requirements If ACM is to be removed or disturbed in a single-family residence, and the total quantity exceeds any of the regulatory trigger levels of 50 linear ft. on pipes, 32 ftZ on other surfaces, or the volume equivalent of a 55 -gallon drum, a CDPHE-certified General Abatement Contractor (GAC) is required to perform the work. The regulatory trigger levels within a commercial building are 260 linear ft. on pipes, 160 ftZ on other surfaces, or the volume equivalent of a 55 -gallon drum. In addition, formal notification to CDPHE prior to the abatement of ACM as well as air monitoring, visual inspections, and final air clearances by a CDPHE-certified Asbestos AMS is required. DS can provide the client or building owner with a proposal for project design, abatement oversight and air monitoring upon request. CDPHE regulations allow for the demolition of a building that contains non -friable asbestos -containing materials, such as caulking, mastic or resilient floor tiles. However, demolition must be completed without causing the non -friable ACM to be rendered friable. Burning a building with any ACM is prohibited. Operations such as sanding, cutting, crushing, grinding, pneumatic jacking, etc. of ACM are not permitted. Recycdnga4f 11 Wheat Ridge Building Division building materials such as concrete, metal, or wood that are bonded or contaminated with ACM, e.g. glue, caulking, or mastic is also prohibited. If any of the non -friable asbestos containing materials are to be recycled and rendered friable after demolition (i.e. crushing mastic -coated concrete), these materials must be abated of all ACM prior to shipping offsite for recycling. OSHA regulations regarding occupational exposure during demolition activities is still mandatory. OSHA 29 CFR 1926.1101 requires that workers performing construction -related activities be protected from asbestos fibers in excess of the permissible exposure limit of 0.1 f/cc of air. Contractors are must comply with applicable provisions of OSHA 29 CFR 1926.1101 during demolition and renovation activities. These OSHA provisions include, but are not limited to, PPE and respirators, personnel training, personal -exposure air monitoring, employee medical surveillance, wet removal methods, signage for regulated areas, etc. 9.0 Major & Minor Asbestos Spill Response Actions If ACM is significantly damaged and the total quantity exceeds the regulatory trigger levels, the area is deemed a "Major Asbestos Spill." The area is consequently subject to the requirements in Reg. 8, Section III.T.1. —Major Asbestos Spills, as outlined below. Additional asbestos air or dust sampling should also be conducted within the remaining areas not directly impacted by the Major Asbestos Spill to determine if asbestos -containing dust/debris has spread to adjacent areas. If asbestos fibers are found within any other areas or on building contents, they should be included in the scope of professional abatement and decontamination. The following response actions must be followed per Colorado Reg. 8 when a Major Asbestos Spill occurs: • Restrict access to the area and post warning signs to prevent entry to the area by persons other than those necessary to respond to the incident. • Shut off or temporarily modify the air handling system to prevent the distribution of asbestos fibers to other areas. • Immediately contact the Division by telephone, submit a notification in compliance with subsection III.E. (Notifications) and, if in an area of public access, apply for a permit in accordance with subsection III.G. (Permits). • Be exempted from the requirements to have a certified Supervisor on-site at all times, until such time as the immediate danger has passed. Any cleanup or asbestos abatement that must occur after the immediate danger has passed shall be supervised by a person certified by the Division. • Using certified Supervisors and certified Workers in accordance with section II. (Certification Requirements) of this Regulation, seal all openings between the contaminated and uncontaminated areas and establish negative air pressure within the contaminated area in accordance with paragraph III.J. (Air Cleaning and None -detected Pressure Requirements). This is to be accomplished using polyethylene sheeting to cover areas such as doorways, windows, elevator openings, corridor entrances, grills, drains, grates, diffusers and skylights. • HEPA vacuum or steam clean all carpets, drapes, upholstery, and other non -clothing fabrics in the contaminated area, or discard these materials. • Launder or discard contaminated clothing in accordance with subsection III.R. (Waste Handling). • HEPA vacuum or wet clean all surfaces in the contaminated area. • Discard all materials in accordance with subsection III.R. (Waste Handling). • Following completion of subparagraph III.T.1.a. through III.T.1.i. above, comply with air monitoring requirements as described in subsection III.P. (Clearing Abatement Projects); air samples shall be collected aggressively as described in 40 C.F.R. Part 763, AppendixAto Subpart E (EPA 1995), except that the air stream of the leaf blower shall not be directed at any friable ACM that remains in the arel9ty of 12 Wheat Ridge Building Division • Comply with any other measures deemed necessary by the Division to protect public health. In the event of an asbestos spill involving less than or equal to the trigger levels, the building owner or contractor should take the following non -mandatory steps: • Restrict entry to the area and post warning signs to prevent entry to the area by persons other than those necessary to respond to the incident. • Shut off or temporarily modify the air handling system to prevent the distribution of fibers to other areas in the building. • Seal all openings between the contaminated and uncontaminated areas. This is to be accomplished by using polyethylene sheeting to cover all areas such as windows, doorways, elevator openings, corridor entrances, drains, grills, grates, diffusers and skylights. • HEPA vacuum or steam clean all carpets, draperies, upholstery and other non -clothing fabrics in the contaminated area or discard all contaminated materials in accordance with subsection III.R. (Waste Handling). • Launder or discard contaminated clothing in accordance with subsection III.R. (Waste Handling). • HEPA vacuum or wet clean all non -fabric surfaces in the contaminated area. • Following completion of subparagraphs III.T.2.a. through III.T.2.f. of Regulation 8, conduct air monitoring as described in paragraph III.P.3 of Regulation 8. (Final Clearance Air Monitoring and Sample Analyses); air samples shall be collected aggressively as described in 40 C.F.R. Part 763, Appendix A to Subpart E (EPA 1995), except that the air stream of the leaf blower shall not be directed at any friable ACM that remains in the work area. 10.0 Project Design & Project Manager Requirements DS can provide an Asbestos Abatement Project Design as well as fulfill the Colorado Asbestos Abatement Project Manager requirements for any asbestos abatement project, as applicable below. Project Design An abatement Project Design is an accurate and detailed scope of work, which includes project specifications and procedures, containment design/equipment placement, and descriptions of engineering controls and work practices for an asbestos abatement project or response action that is required by CDPHE Regulation Number 8, Part B - Asbestos (Reg. 8) on large asbestos abatement projects. Prior to the start of any asbestos abatement project in a non -school building, where the amount of asbestos -containing material (ACM) to be removed or disturbed exceeds 1,000 linear feet on pipes, or 3,000 square feet on surfaces, or in a school building in which the amount of friable ACM to be abated exceeds 3 linear feet on pipes, or 3 square feet on surfaces, a written Project Design must be developed by a State of Colorado certified Project Designer in accordance with subsection IV.G.7 of Regulation 8. A signed copy shall be posted on-site prior to commencing any abatement activities, shall be available on-site at all times, and shall remain onsite until final air clearances have been completed by a State of Colorado -certified Air Monitoring Specialist (AMS). Project Manager A Project Manager shall be used on all asbestos abatement projects in which the amount of friable asbestos - containing material to be abated exceeds 1,000 linear feet on pipes, or 3,000 square feet on other surfaces per CDPHE Regulation Number 8, Part B — Section III.6.6. An asbestos Project Manager on an abatement project shall be responsible for assessing that the project is conducted in accordance with Regulation 8, asses�,{Yghat the Project Design is followed, assessing that the abatement project is cleared in accordance with Regulation 8, 13 Wheat Ridge Building Division assessing that the asbestos waste generated on the project is properly manifested and disposed of in accordance with Regulation 8, and communicating these assessments to the building owner or GAC. Project Managers must have proof of Colorado certification as an asbestos Project Designer and Air Monitoring Specialist in accordance with Section II of CDPHE Regulation 8 as well as a minimum of one (1) year of experience supervising, overseeing or monitoring asbestos abatement projects. A 4 -year college degree in industrial hygiene, a degree in environmental health with a major concentration in industrial hygiene, or the possession of a certified industrial hygienist (CIH) certificate given by the American Board of Industrial Hygiene (ABIH) may be substituted for the Colorado asbestos Air Monitoring Specialist certification. The GAC shall notify the building owner during the bid process as to whether a Project Manager is required. Project Managers shall be independent of the asbestos abatement contractor and work strictly on behalf of the building owner to the extent feasible unless the abatement is being performed in-house. Project Managers must sign the original copy of the abatement permit for the permit to be valid, and before any abatement can take place. 11.0 Disclaimer & Limitations The activities outlined in this report were conducted in a manner consistent with a level of care and expertise exercised by members of the environmental consulting and industrial hygiene profession. All activities were performed in accordance with all applicable federal, state, and local regulations as well as generally accepted standards and professional practice. No warranty is either expressed or implied. DS assumes no responsibility or liability for error in public information utilized, statements from sources other than DS, or developments resulting from situations outside the scope of work for this project. The details provided within this report outline the inspection activities on the date(s) indicated and should not be relied upon to represent conditions at a later date. The laboratory results contained in this report apply specifically to the materials in which bulk -samples were collected. The results do not include or apply to any other materials within the structure that were not sampled but may contain asbestos; including materials that may be hidden or inaccessible. Additional inspection and bulk -sampling activities by a certified inspector would be required to determine whether any other materials contain asbestos. This report has been prepared on behalf of and exclusively for use by the DS's client, with specific application to their project as discussed in the scope of work. The information contained in this report is intended as supplementary material for abatement design and is not to be used as the sole means to develop the scope of abatement activities, bidding or billing purposes. Contractors or consultants reviewing this report must draw their own conclusions regarding further investigation or remediation deemed necessary. DS can provide a full scope of work for abatement upon request. DS does not warrant the work of regulatory agencies, laboratories or other third parties supplying information which may have been used in the preparation of this report. 12.0 Copyright Notice © DS Environmental 2020. All Rights Reserved. This document contains material protected under Federal Copyright Laws. No part of this document or any of its contents may be reproduced, copied, modified or adapted, without the prior written consent of the author and DS Environmental. City of 14 Wheat Ridge Building Division APPENDIX A: CERTIFICATIONS 15 City of Wheat Ridge Building Division City of 16 Wheat Ridge Building Division ' v 7 ✓ � 1 b i � L � xe� � *� "`., >"' 'his r Calorado Deepparm, r �fP.bhc}tealth dEttrin mmnt e < ., ASBESTOS £ ; CERTIFICATION* e This certifies that a Zack WestfaB I " s 0� y p Uj U ¢ o r Certification No.: 22529 Z ♦ <s 9� 0 d c A has met the re,,amments of 25 7 507. C R 5. and Air Quality Control V o Commission Regulation No 8, Par[ 13and is hereby candied by the state of Colorado in the following discipline: Building Inspector* � '' aw s' Issued October 07, 2020 i MWM I� _ Q `—a u p {y Exprrea. Nmc2021 mber Od, �. � so eyu n .rre (Mabrvzbk .reweN vn am w�wn makoa l sees S 5t fs I•� �§h ,y k�, =: ,.,,"2. e '1 i 4t Q �'trl fit rh TF- "a n l Inspector Certification: 22529 Firm Certification: 14912 City of 16 Wheat Ridge Building Division 17 AEROb olociyLAbORATORy ASSOCIATES, INCORPORATED Client Name Street Address City, State ZIP Attn: Client Project Name: Expertise Since 1997 DS Environmental Consulting 7555 W. 10th Ave, Suite A Lakewood, CO 80214 Zack Westfall 4980 Kipling St., Units A6 & 8, Wheat Ridge, CO Certificate of Analysis TESTING NVLAP Lab Code 200860-0 780 Simms Street Suite 104 Golden, CO, 80401 303.232.3746 www.aerobiology.net Date Collected: 10/29/2020 Date Received: 10/29/2020 Date Analyzed: 11/5/2020 Date Reported: 11/5/2020 Project ID: 20046439 Test Requested: 3002, Asbestos in Bulk Samples Method: EPA 600/R-93/116: Method for Asbestos in Bulk Building Materials, EPA -- 40 CFR Appendix E to Subpart E of Part 763, Interim Method for Asbestos in Bulk Insulation Samples Sample Identification Physical Description of Sample/Layer Homo- geneous (Y� Layer percentage Asbestos Detected Asbestos Percentage Non -Asbestos Fiber Percentage Non -Fibrous Material Percentage Matrix Material Composition Client Lab Sample Number SMI -1 20046439-1A White Texture with Tan Paint N 50 ND 100 C 20046439 -IB White Texture with White Paint N 15 ND 100 C 20046439 -IC Pink/Tan Drywall N 35 ND 20 CELL 80 G SMI -2 20046439-2 Off -White Texture with White Paint N 100 ND 100 C SMI -3 20046439-3A Off -White Texture N 55 ND 100 C 20046439-3B White Texture with White Paint N 20 ND 100 C 20046439-3C Off -White Texture N 25 ND 100 C JC1-1 200464394A White Texture with White Paint N 10 ND 100 C 20046439-4B White Texture with White Paint N 5 ND 100 C 200464394C White Tape N 2 ND 99 CELL 1 Afld rea Ba ios Laboratory Analyt 1 �f � } � .A+ Shanmon 1�"hitmofe Asbaitos Lab Super AC = Actinolite l = Amogitt AN = A mthophyllite AH = n;ma1 k a.if CELL = Ce]hdose PG # Fibron Gl:sx B = Bin#fr C = Ca:citf D = Dimon" CHRY w Onry-sotile 1%1W w Mineral Wool G a C*Vylm CR ■ Cro.tidolit* OT ■ Othar- M • hfici TFC! m Tremo4te SYN 0 syathvic OR M Qrjsnk Tr m Tract TL m Tac OP i Qp4que:1 ND i Ions Iettct4d W = WoLmtonit# P = Pt,; Litt Q = Q�Lrtz T=Tat V m Ver-mivnLite City of Wheat Ridge Page 1 of 8 Building Division AEROb olociyLAbORATORy ASSOCIATES, INCORPORATED Client Name Street Address City, State ZIP Attn: Client Project Name: Expertise Since 1997 DS Environmental Consulting 7555 W. 10th Ave, Suite A Lakewood, CO 80214 Zack Westfall 4980 Kipling St., Units A6 & 8, Wheat Ridge, CO Certificate of Analysis TESTING NVLAP Lab Code 200860-0 780 Simms Street Suite 104 Golden, CO, 80401 303.232.3746 www.aerobiology.net Date Collected: 10/29/2020 Date Received: 10/29/2020 Date Analyzed: 11/5/2020 Date Reported: 11/5/2020 Project ID: 20046439 Test Requested: 3002, Asbestos in Bulk Samples Method: EPA 600/R-93/116: Method for Asbestos in Bulk Building Materials, EPA -- 40 CFR Appendix E to Subpart E of Part 763, Interim Method for Asbestos in Bulk Insulation Samples Sample Identification Physical Description of Sample/Layer Homo- geneous (Y� Layer percentage Asbestos Detected Asbestos Percentage Non -Asbestos Fiber Percentage Non -Fibrous Material Percentage Matrix Material Composition Client Lab Sample Number JC1-1 200464394D White Joint Compound N 8 ND 100 C 200464394E Pink/Tan Drywall N 75 ND 10 CELL 90 G JCI -2 20046439-5A Off -White Texture N 1 ND 100 C 20046439-5B White Texture with White Paint N 10 ND 100 C 20046439-5C White Texture with White Paint N 10 ND 100 C 20046439-5D White Texture with Beige Paint N 2 ND 100 C 20046439-5E White Tape N 2 ND 99 CELL 1 20046439-5F White Joint Compound N 5 ND 100 C 20046439-5G Light Gray/Tan Drywall N 70 ND 12 CELL,FG 88 G CDW1-1 20046439-6A White Compound with Pink Paint N 17 ND 100 C Afl6rea Be=rrios LabHwatory Analyt 1 �f e :Shannon 1�"hitmore Asbaitos Lab Super AC = Actinolite Ahl = Amogitt AN = A mthophyllite AH = aimal Hair CELL = Ce]hdose PG # Fibron Glasx B = $in#ff C = Ca:cite D = Diaton" CHRY w Onry-satile 1%1W • Mineral Wool G a C*Vvum CR ■ Cro.tidol t* OT ■ Othar- M • hfici TFC! m Tremo4te SYN 0 syathvic OR M Qrjpnk Tr m Trac* TL m Tac OP i Qpm -3 ND i Ions Iettct4d W = WoLmtonit# P = Ptrlitt Q = Q�Lrtz T = Tai V m Ver-mivnLite City of Wheat Ridge Building Division Page 2 of 8 AEROb olociyLAbORATORy ASSOCIATES, INCORPORATED Client Name Street Address City, State ZIP Attn: Client Project Name: Expertise Since 1997 DS Environmental Consulting 7555 W. 10th Ave, Suite A Lakewood, CO 80214 Zack Westfall 4980 Kipling St., Units A6 & 8, Wheat Ridge, CO Certificate of Analysis TESTING NVLAP Lab Code 200860-0 780 Simms Street Suite 104 Golden, CO, 80401 303.232.3746 www.aerobiology.net Date Collected: 10/29/2020 Date Received: 10/29/2020 Date Analyzed: 11/5/2020 Date Reported: 11/5/2020 Project ID: 20046439 Test Requested: 3002, Asbestos in Bulk Samples Method: EPA 600/R-93/116: Method for Asbestos in Bulk Building Materials, EPA -- 40 CFR Appendix E to Subpart E of Part 763, Interim Method for Asbestos in Bulk Insulation Samples Sample Identification Physical Description of Sample/Layer Homo- geneous (Y� Layer percentage Asbestos Detected Asbestos Percentage Non -Asbestos Fiber Percentage Non -Fibrous Material Percentage Matrix Material Composition Client Lab Sample Number CDW1-1 20046439-6B White Tape N 3 ND 99 CELL 1 20046439-6C White Joint Compound N 10 ND 100 C 20046439-6D Light Gray/Tan Drywall N 70 ND 12 CELL,FG 88 G CDW 1-2 20046439-7A White Compound with Pink Paint N 20 ND 100 C 20046439-7B White Tape N 3 ND 99 CELL 1 20046439-7C White Joint Compound N 12 ND 100 C 20046439-7D Light Gray/Tan Drywall N 65 ND 12 CELL,FG 88 G CDW1-3 20046439-8A White Compound with Pink Paint N 15 ND 100 C 20046439-8B White Tape N 2 ND 99 CELL 1 20046439-8C White Joint Compound N 8 ND 100 C Afldrea Ba ios Laboratory Analyt 1 �f � } � .A+ :Shannon 1�"hitmore Asbaitos Lab Super AC = Actinolite Ahl = Amogitt AN = A mthophyllite AH =minimal Hair CELL = Ce]hdose PG # Fibron Glasx B = Bin#fr C = Ca:cite D = Diaton" CHRY w Onry-iotile 1%1W • Mineral Wool G a C*Vvum CR ■ Cro.tidolit* OT ■ Othar- M • hfici TFC! m Tremo4te SYN 0 syathvic OR M Qrjpnk Tr m Tract TL m Tac OP i Qpm# ND i Ions Iettct4d W = WoLmtonit# P = Pt,; Litt Q = Q�Lrtz T = Tai V m Ver-mivnLite City of Wheat Ridge Building Division Page 3 of 8 AEROb olociyLAbORATORy ASSOCIATES, INCORPORATED Client Name Street Address City, State ZIP Attn: Client Project Name: Expertise Since 1997 DS Environmental Consulting 7555 W. 10th Ave, Suite A Lakewood, CO 80214 Zack Westfall 4980 Kipling St., Units A6 & 8, Wheat Ridge, CO Certificate of Analysis TESTING NVLAP Lab Code 200860-0 780 Simms Street Suite 104 Golden, CO, 80401 303.232.3746 www.aerobiology.net Date Collected: 10/29/2020 Date Received: 10/29/2020 Date Analyzed: 11/5/2020 Date Reported: 11/5/2020 Project ID: 20046439 Test Requested: 3002, Asbestos in Bulk Samples Method: EPA 600/R-93/116: Method for Asbestos in Bulk Building Materials, EPA -- 40 CFR Appendix E to Subpart E of Part 763, Interim Method for Asbestos in Bulk Insulation Samples Sample Identification Homo- Layer Non -Asbestos Non -Fibrous Matrix Physical Description of Sample/Layer geneous Asbestos Detected Asbestos Percentage Fiber Material Material (Y� percentage Percentage Percentage Composition Client Lab Sample Number CDW1-3 20046439-8D Light Gray/Tan Drywall N 75 ND 90 G CEL0 LIP 1-1 20046439-9 White/Gray Perlitic Ceiling Tile N 100 ND 15 P CELL5 LIP 1-2 20046439-10 White/Gray Perlitic Ceiling Tile N 100 ND 15 P CELL5 LIP2-1 20046439-11 White/Tan Perlitic Ceiling Tile N 100 ND 20 P CELL0 LIP2-2 20046439-12 White/Tan Perlitic Ceiling Tile N 100 ND 20 P CELL0 LIP3-1 20046439-13 White/Gray Perlitic Ceiling Tile N 100 ND 10 P CELL0 LIP3-2 20046439-14 White/Gray Perlitic Ceiling Tile N 100 ND 10 P CELL0 20046439-15A Brown Cove Base N 94 ND 100 B,C CBA1-1 20046439-15B White Mastic N 3 ND 100 B 20046439-15C Off -White Paint with Off -White Compound N 3 ND 100 C Afldzrea Ba ios Laboratory Analyt Page 4 of 8 1 �f � } � .A+ :Shannon 1�"hitmore Asbaitos Lab Super AC = A ctinoliite Ahl = Amogitt AN = A mthophyllite AH = aimal Hair CELL = Ce]hdose PG # Fibron Glasx B = $in#fr C = Ca:cite D = Diaton" CHRY w Onry-iotile 1%1W • Mineral Wool G a C*Vvum CR ■ Cro.tidol t* OT ■ Othar- M • hfici TFC! m Tremo4te SYN 0 syathvic OR Qrjpnk Tr m Trac* TL m Tac OP i Qpm# ND i Mons Iettct4d W = WoLmtonit# P = Ptrlitt Q = Q�Lrtz T = Tai V m Ver-mivnLite AEROb olociyLAbORATORy ASSOCIATES, INCORPORATED Client Name Street Address City, State ZIP Attn: Client Project Name: Expertise Since 1997 DS Environmental Consulting 7555 W. 10th Ave, Suite A Lakewood, CO 80214 Zack Westfall 4980 Kipling St., Units A6 & 8, Wheat Ridge, CO Certificate of Analysis TESTING NVLAP Lab Code 200860-0 780 Simms Street Suite 104 Golden, CO, 80401 303.232.3746 www.aerobiology.net Date Collected: 10/29/2020 Date Received: 10/29/2020 Date Analyzed: 11/5/2020 Date Reported: 11/5/2020 Project ID: 20046439 Test Requested: 3002, Asbestos in Bulk Samples Method: EPA 600/R-93/116: Method for Asbestos in Bulk Building Materials, EPA -- 40 CFR Appendix E to Subpart E of Part 763, Interim Method for Asbestos in Bulk Insulation Samples Sample Identification Physical Description of Sample/Layer Homo- geneous (Y� Layer percentage Asbestos Detected Asbestos Percentage Non -Asbestos Fiber Percentage Non -Fibrous Material Percentage Matrix Material Composition Client Lab Sample Number CBA1-2 20046439-16A Brown Cove Base N 96 ND 100 B,C 20046439-16B White Mastic N 2 ND Tr CELL,AH 100 B 20046439-16C Off -White Paint with Off -White Compound N 2 ND 100 C CBA2-1 20046439-17A Off -White Cove Base N 82 ND 100 B,C 20046439-17B Off -White Mastic N 10 ND 100 B 20046439-17C White Paint with White Texture N 7 ND 100 C 20046439-17D Brown Paper N 1 ND 75 CELL 25 CBA2-2 20046439-18A Light Gray Cove Base N 94 ND 100 B,C 20046439-18B Light Tan Mastic N 5 ND 100 B,C 20046439-18C Light Tan Wood N 1 ND 70 CELL 30 Afld rea Ba ios Laboratory Analyt 1 �f � } � .A+ :Shannon 1�"hitmore Asbaitos Lab Super AC = Actinolite l = Amogitt AN = A mthophyllite AH =Animal k a.ir CELL = Ce]hdose PG # Fibron Glasx B = Bin#fr C = Ca:cite D = UiatoaLs CHRY w Onry- otile 1%1W w Mineral Wool G a C*Vylm CR ■ Cro.tidolit* OT ■ Othar- M • hfici TFC! m Tremo4te SYN 0 syathvic OR M Qrjsnk Tr m Tract TL m Tac OP i Qp4que:1 ND i Ions Iettct4d W = WoLmtonit# P = Pt,; Litt Q = Q�Lrtz T=Tat V m Ver-mivnLite City of Wheat Ridge Page 5 of 8 Building Division AEROb olociyLAbORATORy ASSOCIATES, INCORPORATED Client Name Street Address City, State ZIP Attn: Client Project Name: Test Requested: Method: Expertise Since 1997 DS Environmental Consulting 7555 W. 10th Ave, Suite A Lakewood, CO 80214 Zack Westfall 4980 Kipling St., Units A6 & 8, Wheat Ridge, CO Certificate of Analysis TESTING NVLAP Lab Code 200860-0 780 Simms Street Suite 104 Golden, CO, 80401 303.232.3746 www.aerobiology.net Date Collected: 10/29/2020 Date Received: 10/29/2020 Date Analyzed: 11/5/2020 Date Reported: 11/5/2020 Project ID: 20046439 3002, Asbestos in Bulk Samples EPA 600/R-93/116: Method for Asbestos in Bulk Building Materials, EPA -- 40 CFR Appendix E to Subpart E of Part 763, Interim Method for Asbestos in Bulk Insulation Samples Sample Identification Physical Description of Sample/Layer Homo- geneous (Y� Layer percentage Asbestos Detected Asbestos Percentage Non -Asbestos Fiber Percentage Non -Fibrous Material Percentage Matrix Material Composition Client Lab Sample Number CAI -1 20046439-19A Tan Mastic N 35 ND Tr SYN 100 B 20046439-19B Gray Granular Plaster N 33 ND 100 Q 20046439-19C White Plaster N 32 ND 100 CAI -2 20046439-20A Tan Mastic N 55 ND Tr SYN 100 B 20046439-20B White Plaster N 45 ND 100 20046439-20C Gray Granular Plaster N Tr ND 100 Q WTA1-1 20046439-21A Green Granular Plaster N 94 ND 100 Q 20046439-21B White Plaster N 6 ND 100 WTA1-2 20046439-22A Green Granular Plaster N 95 ND 100 Q 20046439-22B White Plaster N 5 ND 100 Afldrea Bam-Gs Laboratory Analyt Jk-i�A- :Sharman 1�"hitmore Aabaitos Lab Super AC _ Actinolite # _mogitt AN A mthophyllite CHRY w Chrvsotile Cly ■ Cro.tidolit* TFC! m Tr Lite Tr m Trac* ND i Ikon m Doomt4d AH = aimal Hair B = $iftif" CELL = ce hdose C = Ca:cite FG Fibro'I� Glasx D = Ulitoau S# y 177 7�T w Mineral Wool G a OT ■ Othar- M • hfici SYN 0 syatwic OR M Qrtsnk TL m Tac OP i Qpm -3 W = W-0 LMtQn1t# F = ptrtitt Q = Q�Lrtz T=Tm V m Ler-mivnLite City of Wheat Ridge Page 6 of 8 Building Division AEROb olociy LAbORATORy ASSOCIATES, INCORPORATED Expertise Since 1997 Client Name DS Environmental Consulting Street Address 7555 W. 10th Ave, Suite A City, State ZIP Lakewood, CO 80214 Attn: Zack Westfall Client Project Name: Test Requested: Method: 4980 Kipling St., Units A6 & 8, Wheat Ridge, CO 3002, Asbestos in Bulk Samples Certificate of Analysis TESTING NVLAP Lab Code 200860-0 780 Simms Street Suite 104 Golden, CO, 80401 303.232.3746 www.aerobiology.net Date Collected: 10/29/2020 Date Received: 10/29/2020 Date Analyzed: 11/5/2020 Date Reported: 11/5/2020 Project ID: 20046439 EPA 600/R-93/116: Method for Asbestos in Bulk Building Materials, EPA -- 40 CFR Appendix E to Subpart E of Part 763, Interim Method for Asbestos in Bulk Insulation Samples Sample Identification Physical Description of Sample/Layer Homo- geneous (YN) Layer percentage Asbestos Detected Asbestos Percentage Non -Asbestos Fiber Percentage Non -Fibrous Material Percentage Matrix Material Composition Client Lab Sample Number SUC1-1 20046439-23A Gray Sink Undercoating N 100 ND 15 CELL 85 BIC 20046439-23B Light Tan Sink Undercoating N Tr ND 5 CELL,FG 95 BIC 20046439-23C Black Tar Sink Undercoating N Tr CHRY 15 85 T,C SUC1-2 20046439-24 POSITIVE STOP FTI -1 20046439-25A Tan Vinyl Flooring N 85 ND 100 B 20046439-25B Colorless Mastic N 5 ND 100 B 20046439-25C Gray Leveling Compound N 10 ND 5 CELL 95 C FTI -2 20046439-26A Tan Vinyl Flooring N 90 ND 100 B 20046439-26B Colorless Mastic N 3 ND 100 B 20046439-26C Gray Leveling Compound N 7 ND 5 CELL 95 C 20046439-26D Tan Mastic N Tr ND 100 B An&ea Berrios Labofatofy Analyst Page 7 of 8 Shannorn 'Whit:mofa Asbsstos Lab Sup_-,Riaar AC = Actinolite ANI = Arnosi.te AN = A nthaphyllite AH = Animal Flair 70-541MVITTFM FIG w FAwous Glass B= C = calcite D • Diatom.& CHRY • chyviotile lam* ■ Mineral Wool G m Oypmnl CR M Cro•tidolit* OT M Other M M Nrwl TILNi i Trem*lit* SYN a Synthetic IDR a Oesxnie Tr + Trxor TL f Tak IDP in OYsaJ-M ND w None DiNctapd W = WgLutonito P = laelrlite Q = Q=tX T=Tm V • V'errrucnlite City of Wheat Ridge Building Division AERObIOlOGy LAbORATORy 780 Sunnis Street ASSOCIATES INCORPORATED Suite Golden, � Golden, CO. 804401 Expertise Since 1 9 997 3bolog.3746 p Certificate of Analysis www aerobiology net Client Name DS Environmental Consulting�r �� n® Date Collected: 10/29/2020 Street Address 7555 W. 10th Ave, Suite A v LJ� I Date Received: 10/29/2020 City, State ZIP Lakewood, CO 80214 TESTING V Date Analyzed: 11/5/2020 Attn: Zack Westfall NVLAP Lab Code 200860-0 Date Reported: 11/5/2020 Client Project Name: 4980 Kipling St., Units A6 & 8, Wheat Ridge, CO Project ID: 20046439 Test Requested: 3002, Asbestos in Bulk Samples Method: EPA 600/R-93/116: Method for Asbestos in Bulk Building Materials, EPA -- 40 CFR Appendix E to Subpart E of Part 763, Interim Method for Asbestos in Bulk Insulation Samples General Notes • ND indicates no asbestos was detected; the method detection limit is 1 %. • Trace or "< 1" indicates asbestos was identified in the sample, but the concentration is less than 1% and cannot be quantified without point counting. • Samples identified as inhomogeneous (more than one layer) are separated into individual layers, and each layer is analyzed and reported separately. 11 All regulated asbestos minerals (i.e. chrysotile, amosite, crocidolite, anthophyllite, tremolite, and actinolite) were sought in every layer of each sample, but only those asbestos minerals detected are listed. Amosite is the common name for the asbestiform variety of the mineral grunerite. Crocidolite is the common name used for the asbestiform variety of the mineral riebeckite. • Tile, vinyl, foam, plastic, and fine powder samples may contain asbestos fibers of such small diameter (< 0.25 microns in diameter) that these fibers cannot be detected by PLM. For such samples, more sensitive analytical methods (e.g. TEM, SEM, and XRD) are recommended if greater certainty about asbestos content is required. Semi -quantitative bulk TEM floor tile analysis is accepted under NESHAP regulations. • These results are submitted pursuant to Aerobiology Laboratory Associates, Inc.'s current terms and conditions of sale, including the company's standard warranty and limitation of liability provisions. No responsibility or liability is assumed for the manner in which the results are used or interpreted. • Unless notified in writing to return the samples covered by this report, Aerobiology Laboratory Associates, Inc. will store the samples for a minimum period of thirty (30) days before discarding. A shipping and handling charge will be assessed for the return of any samples. • Aerobiology does not guarantee the results of tape lifts, microvacs, wipe, and/or debris samples. Accurate analysis cannot be performed due to particle size, media used, and/or amount of material given. Analysis of these materials should be preformed by a TEM. A result of ND does not indicate that the sample area does not contain ashestos. It means the analyst could not identify ashestos in the specific sample for the reasons listed above. Notes Required by NVLAP • This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. • This test report relates only to the items tested or calibrated. • This report is not valid unless it bears the name of a NVLAP-approved signatory. • Any reproduction of this document must include the entire document in order for the report to be valid. City of Wheat Ridge Page 8 of 8 Building Division DRAWING SYMBOLS GRID DESIGNATION O 0 STRUCTURAL GRID ELEVATION X'-X" LEVEL OR DATUM ELEVATION DRAWING NUMBER X WALL SECTION XXXX REFERENCE SHEET NUMBER DRAWING NUMBER X SHEET NUMBER XXXX EXTERIOR ELEVATION REFERENCE DRAWING NUMBER X X X INTERIOR ELEVATION REFERENCE SHEET NUMBER X DRAWING NUMBER X �L--� SHEET NUMBER REFERENCE AREA XXXX WALL LOCATION TAIL X WALL TYPE NUMBER DOOR TYPE NUMBER 101 DETAIL SECTION REFERENCE PLAN, SECTION OR ELEVATION DETAIL OR ENLARGEMENT WALLTYPE REFERENCE DOOR IDENTIFICATION EQUIPMENT NUMBER P C01)EQUIPMENT IDENTIFICATION WINDOW TYPE 1t WINDOW IDENTIFICATION NUMBER ROOM NAME ROOM NUMBER 101 ROOM IDENTIFICATION REVISION NUMBER �1� REVISION NOTE REFERENCE KEYNOTE NUMBER 2— DRAWING NUMBER 1 / A101 SHEETNUMBER KEYNOTE IDENTIFICATION MATCHLINE GRID LINE MATERIAL SYMBOLS 1. SITEWORK TART III— UU-U U O DO C GRAVEL 3. MASONRY OM/ BRICK om CMU STONE 5. WOOD WOOD BLOCKING CONTINUOUS WOOD FRAMING 0000000 FINISH WOOD PLYWOOD 8. FINISHES GYPSUM BOARD CARPET TILE 2. CONCRETE m. CONCRETE SAND/GROUT METAL ALOO 000000 STEEL FIRE SAFING FOAMED -IN-PLACE INSULATION ABBREVIATIONS GENERALNOTES 1 ALL WORK SHALL COMPLYWITH APPLICABLE FEDERAL STATE LOCAL AND ADOPTED CODES ORDINANCES REGULATIONS LAWS STATUTES GUIDELINES AND REQUIREMENTS OF BUILDING AND FIRE AUTHORITIES HAVING JURISDICTION. 2 THE GENERAL CONTRACTOR (HEREAFTER "THE CONTRACTOR") AND SUBCONTRACTORS SHALL CAREFULLY STUDY ALL CONTRACT DOCUMENTS AND ACQUIRE THOROUGH UNDERSTANDING OF THE DESIGN INTENT OF THE PROJECT AND THE DETAILS REQUIRED TO ACHIEVE THE DESIGN INTENT. 3 THE CONTRACTOR SHALL FORWARD REQUESTS FOR CLARIFICATION OR ADDITIONAL INFORMATION WITH REGARD TO ACHIEVING THE DESIGN INTENT OF THE PROJECTTO THE ARCHITECT IN WRITING FOR REVIEW AND WRITTEN RESPONSE. 4 THE CONTRACTOR SHALL CHECKAND VERIFYTHE CONTRACT DOCUMENTS WITH FIELD CONDITIONS, CONFIRMING THAT ALL WORK IS BUILDABLE AS SHOWN, PRIOR TO PROCEEDING WITH THE WORK AND VERIFYALL SPACE DIMENSIONS AS SHOWN WITH EXISTING JOB CONDITIONS BEFORE STARTING CONSTRUCTION. IF DISCREPANCIES EXIST THE CONTRACTOR SHALL IMMEDIATELY NOTIFYTHE ARCHITECT IN WRITING PRIOR TO COMMENCEMENT OF WORK. 5 PRICING OF THESE CONTRACT DOCUMENTS SHALL INCLUDE ALL LABOR, MATERIALS, EQUIPMENT AND SERVICES REQUIRED TO CONSTRUCT THE PROJECT IN ACCORDANCE WITH THE DESIGN INTENT DESCRIBED THEREIN. 6 THE CONTRACTOR SHALL VERIFY AND COORDINATE ALL OPENINGS AND SLEEVES THROUGH FLOORS, CEILINGS, ROOFS, WALLS, STRUCTURAL MEMBERS AND ARCHITECTURAL ELEMENTS WITH CIVIL, LANDSCAPE, ARCHITECTURAL, STRUCTURAL, MECHANICAL, PLUMBING, FIRE PROTECTION, ELECTRICAL AND OTHER DISCIPLINES DRAWINGS, SPECIFICATIONS AND EXISTING CONDITIONS. 7 THE CONTRACTOR SHALL PROTECT ALL IN-PLACE CONSTRUCTION, LANDSCAPING, PAVING, UTILITIES, ETC. FROM DAMAGE DURING CONSTRUCTION. ALL DAMAGED AREAS AND ITEMS SHALL BE RESTORED TO ORIGINAL CONDITION BYTHE CONTRACTOR OR SUBCONTRACTOR DAMAGING THE SAME. 8 THE CONTRACTOR SHALL SUBMIT PROPOSED SUBSTITUTIONS OF SPECIFIED MATERIALS/ PRODUCTS TO THE ARCHITECT FOR REVIEW, IN ACCORDANCE WITH PROCEDURES DESCRIBED IN THE SPECIFICATIONS. 9 THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS, CUT -SHEETS, AND SAMPLES WHEN REQUIRED BYTHE SPECIFICATIONS, FOR REVIEW BYTHE ARCHITECT, PRIOR TO COMMENCING WITH RELATED WORK. 10 ALL WORK SHALL BE ERECTED PLUMB, LEVEL AND TRUE -TO -LINE IN ACCORDANCE WITH BEST PRACTICES OF THE TRADE, MANUFACTURER'S INSTRUCTIONS FOR THE PARTICULAR PRODUCT, AND IN ACCORDANCE WITH THE SPECIFICATIONS. 11 THE CONTRACTOR SHALL NOTIFYALL APPLICABLE LOCAL GOVERNMENTAL AGENCIES WHEN THERE IS A NEED FOR AN INSPECTION REQUIRED BYTHE APPLICABLE CODE, OR BYTHE AUTHORITY HAVING JURISDICTION. 12 THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE SAFETYAND CARE OF ALL PERSONNEL AND OF ADJACENT PROPERTIES DURING CONSTRUCTION, FOR COMPLIANCE WITH FEDERAL AND STATE OSHA REGULATIONS, AND FOR THE PROTECTION OF ALL WORK UNTIL IT IS DELIVERED TOTHE OWNER. 13 DO NOT SCALE DRAWINGS. 14 INTERIOR PARTITIONS ARE DIMENSIONED TO FACE OF GYPSUM BOARD, UNLESS INDICATED OTHERWISE. 15 THE INSIDE FACE OF DOOR JAMBS SHALL BE 4" FROM ADJACENT WALL OR FINISHED COLUMN, UNLESS INDICATED OTHERWISE. 16 WHERE NEW WORK HAS DISTURBED PREVIOUSLY INSTALLED OR EXISTING WORK OR FINISHES SUCH AREAS SHALL BE REWORKED AND/OR REFINISHED AS REQUIRED TO MATCH THE ORIGINAL CONDITION OF THE AREA PRIOR TO THE DISTURBANCE. 17 EACH MISCELLANEOUS ITEM OF CUTTING, PATCHING OR FITTING IS NOT NECESSARILY INDIVIDUALLY DESCRIBED IN THE DOCUMENTS. THE ABSENCE OF SPECIFIC DESCRIPTIONS OF CUTTING, PATCHING, OR FITTING REQUIRED TO PROPERLY ACCOMMODATE THE SCOPE OF WORK SHALL NOT RELIEVE THE CONTRACTOR OR SUBCONTRACTOR FROM THE RESPONSIBILITY TO PERFORM SUCH WORK AS REQUIRED TO ACHIEVE THE DESIGN INTENT OF THE PROJECT. 18 NOTES APPEAR ON DIFFERENT SHEETS FOR DIFFERENT SYSTEMS AND CONSTRUCTION MATERIAL. ALL SHEETS ARE TO BE REVIEWED AND NOTES ON ANY ONE SHEET ARE TO BE APPLIED TO ALL RELATED DRAWINGS AND DETAILS. 19 DETAILS NOT SHOWN ARE SIMILAR IN CHARACTER AND QUALITY TO THOSE DETAILED. WHERE SPECIFIED DIMENSIONS, DETAILS, OR DESIGN INTENT CANNOT BE DETERMINED, THE CONTRACTOR SHALL NOTIFYTHE ARCHITECT IMMEDIATELY FOR CLARIFICATION, PRIOR TO PROCEEDING WITH WORK. 20 ALL DISSIMILAR METALS SHALL BE EFFECTIVELY ISOLATED FROM EACH OTHER TO AVOID GALVANIC ACTION. 21 A FINISH OR FIRE RATING ON A WALL SHALL MEAN THE ENTIRE LENGTH AND HEIGHT OF WALL TO BE FINISHED OR FIRE RATED AS INDICATED. 22 THE HEAD AND BASE CONDITIONS OF ALL FIRE RATED WALLS SHALL BE TERMINATED WITH UL -APPROVED DESIGNS AND MATERIALS. 23 SCOPES OF WORK ON THE DRAWINGS NOTED AS"NIC"ARE" NOT INCLUDED IN CONTRACT. 24 ALL FLOOR ELEVATIONS ARE TO TOP OF STRUCTURAL CONCRETE OR TOPPING SLAB UNLESS INDICATED OTHERWISE. 25 PROVIDE BLOCKING OR OTHER SUPPORT AS REQUIRED FOR ALL WALL, FLOOR, CEILING AND ROOF MOUNTED ITEMS. BLOCKING SHALL BE FIRE RESISTIVE TREATED AS REQUIRED AND PERMITTED BY CODE. 26 SHOULD ANY CONFLICT OCCUR BETWEEN THE ARCHITECTURAL DRAWINGS AND THE ARCHITECTS CONSULTANTS'DRAWINGS, THE CONTRACTOR SHALL NOTIFY THE ARCHITECT IMMEDIATELY FOR CLARIFICATION. 27 COORDINATE PLACEMENT OF ALL CEILING ELEMENTS WITH MECHANICAL, ELECTRICAL, FIRE PROTECTION, EQUIPMENT AND OTHER INSTALLERS. WHERE DISCREPANCIES EXIST BETWEEN DRAWINGS AND FIELD CONDITIONS, CONSULT THE ARCHITECT PRIOR TO PROCEEDING WITH INSTALLATION. 28 REFER TO PLUMBING DRAWINGS FOR LOCATIONS OF ALL FLOOR DRAINS, TRENCH DRAINS, SUMPS AND SUBSOIL DRAINAGE, UNLESS INDICATED OTHERWISE. IF LOCATIONS CONFLICT WITH ARCHITECTURAL DRAWINGS, THE CONTRACTOR SHALL NOTIFYTHE ARCHITECT IMMEDIATELY FOR CLARIFICATION. 29 ALL PENETRATIONS OF DUCTWORK, CONDUIT, PIPING AND OTHER WORK THROUGH FIRE RATED ASSEMBLIES SHALL BE SEALED WITH UL -APPROVED DESIGNS AND MATERIALS TO MAINTAIN THE RATING OF THE ASSEMBLY. 30 ALL EQUIPMENT INSTALLED IN RETURN AIR PLENUMS SHALL BE APPROVED BYTHE AUTHORITY HAVING JURISDICTION AGENCY FOR COMPLIANCE WITH CODE. 31 THE CONTRACTOR SHALL COORDINATE ALL EQUIPMENT BASE AND HOUSEKEEPING PADS WITH MECHANICAL PLUMBING AND ELECTRICAL CONTRACTORS. EQUIPMENT BASE AND HOUSEKEEPING PADS TO BE MINIMUM 4" HIGH AND TO BE INSTALLED BENEATH THE PROJECTED AREA OF THE EQUIPMENT AND IN ACCORDANCE WITH THE EQUIPMENT MANUFACTURER'S INSTRUCTIONS AND RECOMMENDATIONS. 32 ALL ROOF -TOP EQUIPMENT SHALL BE LOCATED SUCH THAT FALL PROTECTION SYSTEMS ARE NOT REQUIRED FOR EQUIPMENT MAINTENANCE. U.N.O. 33 GRAPHICS ARE NOT NECESSARILYAN INDICATOR OF DESIGN INTENT. IF DESCREPANCIES EXISTED BETWEEN NOTES/SPECIFICATIONS AND GRAPHICS CONSULT ARCHITECT PRIOR TO PRIOR TO PROCEEDING. LOCATION MAP as en.mr.evQ CEILING TYPE yIDwI.D u, w..,n m. G012 CEILING HEIGHT REFERENCE G201 EL=X'-X" G301 ACCESSIBILITY REQUIREMENTS 14 c - HEIGHTABOVE INTERIOR SCHEDULES AND DETAILS A852 FINISH FLOOR CLR CLEAR DRAWING NUMBER w Qca.ma..r De.., HR X X BUILDING SECTION XXXX XXXX REFERENCE SHEET UN MBER < CENTERLINE DRAWING NUMBER X WALL SECTION XXXX REFERENCE SHEET NUMBER DRAWING NUMBER X SHEET NUMBER XXXX EXTERIOR ELEVATION REFERENCE DRAWING NUMBER X X X INTERIOR ELEVATION REFERENCE SHEET NUMBER X DRAWING NUMBER X �L--� SHEET NUMBER REFERENCE AREA XXXX WALL LOCATION TAIL X WALL TYPE NUMBER DOOR TYPE NUMBER 101 DETAIL SECTION REFERENCE PLAN, SECTION OR ELEVATION DETAIL OR ENLARGEMENT WALLTYPE REFERENCE DOOR IDENTIFICATION EQUIPMENT NUMBER P C01)EQUIPMENT IDENTIFICATION WINDOW TYPE 1t WINDOW IDENTIFICATION NUMBER ROOM NAME ROOM NUMBER 101 ROOM IDENTIFICATION REVISION NUMBER �1� REVISION NOTE REFERENCE KEYNOTE NUMBER 2— DRAWING NUMBER 1 / A101 SHEETNUMBER KEYNOTE IDENTIFICATION MATCHLINE GRID LINE MATERIAL SYMBOLS 1. SITEWORK TART III— UU-U U O DO C GRAVEL 3. MASONRY OM/ BRICK om CMU STONE 5. WOOD WOOD BLOCKING CONTINUOUS WOOD FRAMING 0000000 FINISH WOOD PLYWOOD 8. FINISHES GYPSUM BOARD CARPET TILE 2. CONCRETE m. CONCRETE SAND/GROUT METAL ALOO 000000 STEEL FIRE SAFING FOAMED -IN-PLACE INSULATION ABBREVIATIONS GENERALNOTES 1 ALL WORK SHALL COMPLYWITH APPLICABLE FEDERAL STATE LOCAL AND ADOPTED CODES ORDINANCES REGULATIONS LAWS STATUTES GUIDELINES AND REQUIREMENTS OF BUILDING AND FIRE AUTHORITIES HAVING JURISDICTION. 2 THE GENERAL CONTRACTOR (HEREAFTER "THE CONTRACTOR") AND SUBCONTRACTORS SHALL CAREFULLY STUDY ALL CONTRACT DOCUMENTS AND ACQUIRE THOROUGH UNDERSTANDING OF THE DESIGN INTENT OF THE PROJECT AND THE DETAILS REQUIRED TO ACHIEVE THE DESIGN INTENT. 3 THE CONTRACTOR SHALL FORWARD REQUESTS FOR CLARIFICATION OR ADDITIONAL INFORMATION WITH REGARD TO ACHIEVING THE DESIGN INTENT OF THE PROJECTTO THE ARCHITECT IN WRITING FOR REVIEW AND WRITTEN RESPONSE. 4 THE CONTRACTOR SHALL CHECKAND VERIFYTHE CONTRACT DOCUMENTS WITH FIELD CONDITIONS, CONFIRMING THAT ALL WORK IS BUILDABLE AS SHOWN, PRIOR TO PROCEEDING WITH THE WORK AND VERIFYALL SPACE DIMENSIONS AS SHOWN WITH EXISTING JOB CONDITIONS BEFORE STARTING CONSTRUCTION. IF DISCREPANCIES EXIST THE CONTRACTOR SHALL IMMEDIATELY NOTIFYTHE ARCHITECT IN WRITING PRIOR TO COMMENCEMENT OF WORK. 5 PRICING OF THESE CONTRACT DOCUMENTS SHALL INCLUDE ALL LABOR, MATERIALS, EQUIPMENT AND SERVICES REQUIRED TO CONSTRUCT THE PROJECT IN ACCORDANCE WITH THE DESIGN INTENT DESCRIBED THEREIN. 6 THE CONTRACTOR SHALL VERIFY AND COORDINATE ALL OPENINGS AND SLEEVES THROUGH FLOORS, CEILINGS, ROOFS, WALLS, STRUCTURAL MEMBERS AND ARCHITECTURAL ELEMENTS WITH CIVIL, LANDSCAPE, ARCHITECTURAL, STRUCTURAL, MECHANICAL, PLUMBING, FIRE PROTECTION, ELECTRICAL AND OTHER DISCIPLINES DRAWINGS, SPECIFICATIONS AND EXISTING CONDITIONS. 7 THE CONTRACTOR SHALL PROTECT ALL IN-PLACE CONSTRUCTION, LANDSCAPING, PAVING, UTILITIES, ETC. FROM DAMAGE DURING CONSTRUCTION. ALL DAMAGED AREAS AND ITEMS SHALL BE RESTORED TO ORIGINAL CONDITION BYTHE CONTRACTOR OR SUBCONTRACTOR DAMAGING THE SAME. 8 THE CONTRACTOR SHALL SUBMIT PROPOSED SUBSTITUTIONS OF SPECIFIED MATERIALS/ PRODUCTS TO THE ARCHITECT FOR REVIEW, IN ACCORDANCE WITH PROCEDURES DESCRIBED IN THE SPECIFICATIONS. 9 THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS, CUT -SHEETS, AND SAMPLES WHEN REQUIRED BYTHE SPECIFICATIONS, FOR REVIEW BYTHE ARCHITECT, PRIOR TO COMMENCING WITH RELATED WORK. 10 ALL WORK SHALL BE ERECTED PLUMB, LEVEL AND TRUE -TO -LINE IN ACCORDANCE WITH BEST PRACTICES OF THE TRADE, MANUFACTURER'S INSTRUCTIONS FOR THE PARTICULAR PRODUCT, AND IN ACCORDANCE WITH THE SPECIFICATIONS. 11 THE CONTRACTOR SHALL NOTIFYALL APPLICABLE LOCAL GOVERNMENTAL AGENCIES WHEN THERE IS A NEED FOR AN INSPECTION REQUIRED BYTHE APPLICABLE CODE, OR BYTHE AUTHORITY HAVING JURISDICTION. 12 THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE SAFETYAND CARE OF ALL PERSONNEL AND OF ADJACENT PROPERTIES DURING CONSTRUCTION, FOR COMPLIANCE WITH FEDERAL AND STATE OSHA REGULATIONS, AND FOR THE PROTECTION OF ALL WORK UNTIL IT IS DELIVERED TOTHE OWNER. 13 DO NOT SCALE DRAWINGS. 14 INTERIOR PARTITIONS ARE DIMENSIONED TO FACE OF GYPSUM BOARD, UNLESS INDICATED OTHERWISE. 15 THE INSIDE FACE OF DOOR JAMBS SHALL BE 4" FROM ADJACENT WALL OR FINISHED COLUMN, UNLESS INDICATED OTHERWISE. 16 WHERE NEW WORK HAS DISTURBED PREVIOUSLY INSTALLED OR EXISTING WORK OR FINISHES SUCH AREAS SHALL BE REWORKED AND/OR REFINISHED AS REQUIRED TO MATCH THE ORIGINAL CONDITION OF THE AREA PRIOR TO THE DISTURBANCE. 17 EACH MISCELLANEOUS ITEM OF CUTTING, PATCHING OR FITTING IS NOT NECESSARILY INDIVIDUALLY DESCRIBED IN THE DOCUMENTS. THE ABSENCE OF SPECIFIC DESCRIPTIONS OF CUTTING, PATCHING, OR FITTING REQUIRED TO PROPERLY ACCOMMODATE THE SCOPE OF WORK SHALL NOT RELIEVE THE CONTRACTOR OR SUBCONTRACTOR FROM THE RESPONSIBILITY TO PERFORM SUCH WORK AS REQUIRED TO ACHIEVE THE DESIGN INTENT OF THE PROJECT. 18 NOTES APPEAR ON DIFFERENT SHEETS FOR DIFFERENT SYSTEMS AND CONSTRUCTION MATERIAL. ALL SHEETS ARE TO BE REVIEWED AND NOTES ON ANY ONE SHEET ARE TO BE APPLIED TO ALL RELATED DRAWINGS AND DETAILS. 19 DETAILS NOT SHOWN ARE SIMILAR IN CHARACTER AND QUALITY TO THOSE DETAILED. WHERE SPECIFIED DIMENSIONS, DETAILS, OR DESIGN INTENT CANNOT BE DETERMINED, THE CONTRACTOR SHALL NOTIFYTHE ARCHITECT IMMEDIATELY FOR CLARIFICATION, PRIOR TO PROCEEDING WITH WORK. 20 ALL DISSIMILAR METALS SHALL BE EFFECTIVELY ISOLATED FROM EACH OTHER TO AVOID GALVANIC ACTION. 21 A FINISH OR FIRE RATING ON A WALL SHALL MEAN THE ENTIRE LENGTH AND HEIGHT OF WALL TO BE FINISHED OR FIRE RATED AS INDICATED. 22 THE HEAD AND BASE CONDITIONS OF ALL FIRE RATED WALLS SHALL BE TERMINATED WITH UL -APPROVED DESIGNS AND MATERIALS. 23 SCOPES OF WORK ON THE DRAWINGS NOTED AS"NIC"ARE" NOT INCLUDED IN CONTRACT. 24 ALL FLOOR ELEVATIONS ARE TO TOP OF STRUCTURAL CONCRETE OR TOPPING SLAB UNLESS INDICATED OTHERWISE. 25 PROVIDE BLOCKING OR OTHER SUPPORT AS REQUIRED FOR ALL WALL, FLOOR, CEILING AND ROOF MOUNTED ITEMS. BLOCKING SHALL BE FIRE RESISTIVE TREATED AS REQUIRED AND PERMITTED BY CODE. 26 SHOULD ANY CONFLICT OCCUR BETWEEN THE ARCHITECTURAL DRAWINGS AND THE ARCHITECTS CONSULTANTS'DRAWINGS, THE CONTRACTOR SHALL NOTIFY THE ARCHITECT IMMEDIATELY FOR CLARIFICATION. 27 COORDINATE PLACEMENT OF ALL CEILING ELEMENTS WITH MECHANICAL, ELECTRICAL, FIRE PROTECTION, EQUIPMENT AND OTHER INSTALLERS. WHERE DISCREPANCIES EXIST BETWEEN DRAWINGS AND FIELD CONDITIONS, CONSULT THE ARCHITECT PRIOR TO PROCEEDING WITH INSTALLATION. 28 REFER TO PLUMBING DRAWINGS FOR LOCATIONS OF ALL FLOOR DRAINS, TRENCH DRAINS, SUMPS AND SUBSOIL DRAINAGE, UNLESS INDICATED OTHERWISE. IF LOCATIONS CONFLICT WITH ARCHITECTURAL DRAWINGS, THE CONTRACTOR SHALL NOTIFYTHE ARCHITECT IMMEDIATELY FOR CLARIFICATION. 29 ALL PENETRATIONS OF DUCTWORK, CONDUIT, PIPING AND OTHER WORK THROUGH FIRE RATED ASSEMBLIES SHALL BE SEALED WITH UL -APPROVED DESIGNS AND MATERIALS TO MAINTAIN THE RATING OF THE ASSEMBLY. 30 ALL EQUIPMENT INSTALLED IN RETURN AIR PLENUMS SHALL BE APPROVED BYTHE AUTHORITY HAVING JURISDICTION AGENCY FOR COMPLIANCE WITH CODE. 31 THE CONTRACTOR SHALL COORDINATE ALL EQUIPMENT BASE AND HOUSEKEEPING PADS WITH MECHANICAL PLUMBING AND ELECTRICAL CONTRACTORS. EQUIPMENT BASE AND HOUSEKEEPING PADS TO BE MINIMUM 4" HIGH AND TO BE INSTALLED BENEATH THE PROJECTED AREA OF THE EQUIPMENT AND IN ACCORDANCE WITH THE EQUIPMENT MANUFACTURER'S INSTRUCTIONS AND RECOMMENDATIONS. 32 ALL ROOF -TOP EQUIPMENT SHALL BE LOCATED SUCH THAT FALL PROTECTION SYSTEMS ARE NOT REQUIRED FOR EQUIPMENT MAINTENANCE. U.N.O. 33 GRAPHICS ARE NOT NECESSARILYAN INDICATOR OF DESIGN INTENT. IF DESCREPANCIES EXISTED BETWEEN NOTES/SPECIFICATIONS AND GRAPHICS CONSULT ARCHITECT PRIOR TO PRIOR TO PROCEEDING. LOCATION MAP as en.mr.evQ aem..een�n...naV yIDwI.D u, w..,n m. G012 SPECIFICATIONS G201 OCCUPANT LOADS, EGRESS & TRAVEL DISTANCE G301 ACCESSIBILITY REQUIREMENTS A801 c - A851 INTERIOR SCHEDULES AND DETAILS A852 INTERIOR DETAILS CLR CLEAR FF w Qca.ma..r De.., HR HOUR MWP METAL WALL PANEL RD wsm�>.e T.O.P. TOP OF PARAPET < CENTERLINE CMU CONCRETE MASONRYUNIT FH FINISH HEIGHT HRA HOT RUBBERIZED ASPHALT NA NOTAPPLICABLE RE: REFER TO T.O.R. TOP OF RAIL > PLATE COL COLUMN FHC FIRE HOSE CABINET HT HEIGHT NIC NOT IN CONTRACT REQ'D REQUIRED T.O.R.D. TOP OF ROOF DECK @ AT CONC CONCRETE FIN FINISH(ED) HTR HEATER NO/# NUMBER ROW RIGHT OF WAY T.O.S. TOP OF STRUCTURE AC AIR CONDITIONING CONST CONSTRUCTION FLR FLOOR IAW IN ACCORDANCE WITH NOM NOMINAL RS ROUGH SAWN T.O.W. TOP OF WALL ACT ACOUSTICAL CEILING TI LE CONT CONTINUOUS FND FOUNDATION aaalswpv INSIDE CLEAR NTS NOTTO SCALE SAT SUSPENDED ACOUSTICAL TEL TELEPHONE ADJ ADJUSTABLE CPT CARPET FR �aoe ID INTERIOR DESIGN O.C. ON CENTER TILE =0 TEMPERED GLASS AFF ABOVE FINISH FLOOR O.nec.a sw« CERAMIC TILE FRP FIBER REINFORCED PLASTIC D.a.."a:wm MD INSULATION OA OVERALL SC SOLID CORE THK THICKNESS AFR ABOVE FINISH ROOF DD DESIGN DEVELOPMENT FRT FIRE RETARDANT TREATED V 0 OD OUTSIDE DIAMETER SCHED SCHEDULE TOPO TOPOGRAPHY AL ALUMINUM DIA DIAMETER FTG FOOTING ISS ISSUE ek.Drom OVERFLOW DRAIN Da..r SECTION c, TYPICAL ALT ALTERNATE DJ Darl.:o .a... ..,r.... vrag. e..... - •"••°"••'"• FIELD VERIFY _ wavnnw wean n.. wavnnr< wean n.. waannr< SF SQUARE FOOT OR FEET U.N.O. y AN ANODIZED DS DOWNSPOUT FVC FIRE VALVE CABINET 9 JOIST OPG OPENING SHT SHEET VAR 0 ARCH ARCHITECT(URAL) QBDwaQ DETAIL FXT � �y vdnenaan JOINT OPP OPPOSITE HAND W.cn pioDz,LU �. VCT Nvvinm..rieD M� ASPH DonOers -.1 DWG DRAWING De Wel M V GAUGE L ANGLE ORD OVERFLOW ROOF DRAIN F SHEET METAL ]O Exmllve LeMee VERTICAL B.O. BOTTOM OF EA EACH F GALVANIZED LAM LAMINATE PART BIRD PARTICLE BOARD SPEC SPECIFICATION y VESTIBULE PoMueE D°w.eD, BOARD EJ EXPANSION JOINT GC GENERAL CONTRACTOR LAV • aDO � SQ SQUIRE VIF VERIFY IN FIELD BLDG BUILDING EL ELEVATION GEN Qvaac.m.r.�a. LP LOW POINT PERF PERFORATION SS STAINLESS STEEL VWC VINYL WALLCOVERING BLK BLOCK ELEC ELECTRICAL m GLASS FIBER REINFORCED LT LIGHT PL PROPERTY LINE STD STANDARD W.O. WHERE OCCURS BM BEAM ELEV ELEVATOR CONCRETE MACH MACHINED PLAM PLASTIC LAMINATE STL STEEL W/ WITH BOT BOTTOM EPS EXPANDED POLYSTYRENE GL GLASS MATL MATERIAL PLUMB PLUMBING STRUC STRUCTURAL W/O WITHOUT BRG BEARING EQ EQUAL GND GROUND MAX MAXIMUM PLWD PLYWOOD SYM SYMETRICAL WC WATER CLOSET SHEET INDEX SHEET NUMBER SHEET NAME 01 GENERAL GO COVER G011 GENERAL INFORMATION G012 SPECIFICATIONS G201 OCCUPANT LOADS, EGRESS & TRAVEL DISTANCE G301 ACCESSIBILITY REQUIREMENTS 02 DEMOLITION A101 FLOOR PLAN A151 REFLECTED CEILING PLAN A401 ENLARGED PLANS AND INTERIOR ELEVATIONS A402 RECEPTION DESK PLAN AND ELEVATIONS A501 DOOR, WINDOW, PARTITION TYPES AND DETAILS A801 FINISH PLAN A851 INTERIOR SCHEDULES AND DETAILS A852 INTERIOR DETAILS 04 MECHANICAL M001 GENERAL INFORMATION M002 MECHANICAL SCHEDULES MD101 FIRST FLOOR DEMO MECHANICAL PLAN M101 FIRST FLOOR MECHANICAL PLAN M102 ROOF MECHANICAL PLAN M501 MECHANICAL DETAILS 05 PLUMBING P001 PLUMBING SPECS SCHEDULES & LEGEND PD101 FIRST FLOOR DEMO PLUMBING PLAN P100 UNDERGROUND PLUMBING PLAN P101 FIRST FLOOR PLUMBING PLAN P501 PLUMBING ISOMETRICS P601 PLUMBING DETAILS 06 ELECTRICAL E001 ELECTRICAL SPECS LEGEND ONE -LINE ED101 FIRST FLOOR DEMO POWER PLAN ED201 FIRST FLOOR DEMO LIGHTING PLAN E101 FIRST FLOOR POWER PLAN E102 ROOF POWER PLAN E201 FIRST FLOOR LIGHTING PLAN E301 ELECTRICAL PANEL SCHEDULES E401 ELECTRICAL COM CHECK (E) EXISTING CLG CEILING FEC FIRE EXTINGUISHER CABINET HPL HIGH PRESSURE LAMINATE MTL METAL RCP REFLECTED CEILING PLAN T.O.F.F. TOP OF FINISH FLOOR (N) NEW CLR CLEAR FF FINISH FLOOR HR HOUR MWP METAL WALL PANEL RD ROOF DRAIN T.O.P. TOP OF PARAPET < CENTERLINE CMU CONCRETE MASONRYUNIT FH FINISH HEIGHT HRA HOT RUBBERIZED ASPHALT NA NOTAPPLICABLE RE: REFER TO T.O.R. TOP OF RAIL > PLATE COL COLUMN FHC FIRE HOSE CABINET HT HEIGHT NIC NOT IN CONTRACT REQ'D REQUIRED T.O.R.D. TOP OF ROOF DECK @ AT CONC CONCRETE FIN FINISH(ED) HTR HEATER NO/# NUMBER ROW RIGHT OF WAY T.O.S. TOP OF STRUCTURE AC AIR CONDITIONING CONST CONSTRUCTION FLR FLOOR IAW IN ACCORDANCE WITH NOM NOMINAL RS ROUGH SAWN T.O.W. TOP OF WALL ACT ACOUSTICAL CEILING TI LE CONT CONTINUOUS FND FOUNDATION IC INSIDE CLEAR NTS NOTTO SCALE SAT SUSPENDED ACOUSTICAL TEL TELEPHONE ADJ ADJUSTABLE CPT CARPET FR FIRE RESISTANT ID INTERIOR DESIGN O.C. ON CENTER TILE TG TEMPERED GLASS AFF ABOVE FINISH FLOOR CT CERAMIC TILE FRP FIBER REINFORCED PLASTIC INSUL INSULATION OA OVERALL SC SOLID CORE THK THICKNESS AFR ABOVE FINISH ROOF DD DESIGN DEVELOPMENT FRT FIRE RETARDANT TREATED INT INTERIOR OD OUTSIDE DIAMETER SCHED SCHEDULE TOPO TOPOGRAPHY AL ALUMINUM DIA DIAMETER FTG FOOTING ISS ISSUE OD OVERFLOW DRAIN SECT SECTION TYP TYPICAL ALT ALTERNATE DJ DEFLECTION JOINT FV FIELD VERIFY JAN JANITOR OH OVERHEAD SF SQUARE FOOT OR FEET U.N.O. UNLESS NOTED OTHERWISE AN ANODIZED DS DOWNSPOUT FVC FIRE VALVE CABINET JST JOIST OPG OPENING SHT SHEET VAR VARIES ARCH ARCHITECT(URAL) DTL DETAIL FXT FIXTURE JT JOINT OPP OPPOSITE HAND SIM SIMILAR VCT VINYL COMPOSITION TILE ASPH ASPHAULT DWG DRAWING GA GAUGE L ANGLE ORD OVERFLOW ROOF DRAIN SM SHEET METAL VERT VERTICAL B.O. BOTTOM OF EA EACH GALV GALVANIZED LAM LAMINATE PART BIRD PARTICLE BOARD SPEC SPECIFICATION VEST VESTIBULE BD BOARD EJ EXPANSION JOINT GC GENERAL CONTRACTOR LAV LAVATORY PC PRECAST CONCRETE SQ SQUIRE VIF VERIFY IN FIELD BLDG BUILDING EL ELEVATION GEN GENERAL LP LOW POINT PERF PERFORATION SS STAINLESS STEEL VWC VINYL WALLCOVERING BLK BLOCK ELEC ELECTRICAL GFRC GLASS FIBER REINFORCED LT LIGHT PL PROPERTY LINE STD STANDARD W.O. WHERE OCCURS BM BEAM ELEV ELEVATOR CONCRETE MACH MACHINED PLAM PLASTIC LAMINATE STL STEEL W/ WITH BOT BOTTOM EPS EXPANDED POLYSTYRENE GL GLASS MATL MATERIAL PLUMB PLUMBING STRUC STRUCTURAL W/O WITHOUT BRG BEARING EQ EQUAL GND GROUND MAX MAXIMUM PLWD PLYWOOD SYM SYMETRICAL WC WATER CLOSET C.O. CENTER OF EQUIP EQUIPMENT GR GRADE MCM METAL COMPOSITE MATERIAL PN PROJECT NORTH T TRANSFORMER WD WOOD C.O.F. CENTER OF FLUE ETR EXISTING TO REMAIN GWB GYPSUM WALL BOARD MDF MEDIUM DENSITY PR PAIR T.O. TOP OF WH WATER HEATER C.O.W. CENTER OF WALL EWC ELECTRIC WATER COOLER GYP GYPSUM FIBERBOARD PT PRESSURE TREATED T.O.B. TOP OF BEAM WP WATERPROOFING CG CORNER GUARD EXH EXHAUST HC HANDICAPPED ACCESSIBLE MECH MECHANICAL PT PAINT T.O.C. TOP OF CONCRETE WWF WELDED WIRE FABRIC CIP CAST -IN-PLACE F.B.O. FURNISHED BYOWNER HDWR HARDWARE MFR MANUFACTURER PTN PARTITION T.O.D. TOP OF DECK CJ CONTROL JOINT F.O. FACE OF HM HOLLOW METAL MIN MINIMUM R.O. ROUGH OPENING T.O.F. TOP OF FOOTING CL CENTERLINE F.O.W FACE OF WALL HORIZ HORIZONTAL MISC MISCELANEOUS RAD RADIUS T.O.F.D. TOP OF FLOOR DECK FD FLOOR DRAIN HP HIGH POINT MR MOISTURE RESISTANT RB RUBBER BASE chord% of Coto ROBERT O h J OHN OgRSL UND * �I 17 \ri T 46 zs'�: ��i �FD AitC�'r� OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO P.0 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 COPYRIGHT: 2020 THIS DOCUMENTANDTHE DESIGNS INCORPORATED HEREIN CAN ONLYBE USED FOR THISPROJECT. NO OTHER USE OFTHIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUTTHE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Project Number: 20019 GENERAL INFORMATION G011 City of Wheat Ridge Building Division GENERAL CONDITIONS The General Contractor and all Subcontractors shall read the following General Conditions, and project notes as responsibilities affecting all trades are described herein. The General Contractor is responsible for the overall quality and scheduling ofthe work and the coordination ofthe various trades. 1.0 The reference to'Owner'throu hout these documents shall referto the Landlord's and/or Tenant's representatives. 9 P Reference to the 'Contractor' shall mean the General Contractor in charge of and supervising the work ofthe project. The 9 P 9 P 1 reference to 'CDS' or'Architecf throughout these documents shall refer to Chord Design Studio P.C. 9 9 1.1 The Contractor shall coordinate all aspects ofthe project with the Owner and Building Manager. Areas of P P 1 9 9 coordination include, but are not limited to: - Insurance Requirements - Hours and Methods of Access - Project Safety - Building Security and Emergency Procedures - Materials Staging Areas - Hazardous Materials - Access to Trash Facilities - Use and Protection of Elevators and Common Areas - Parking for Supervision and Trades - Deliveries - Other Applicable Contract Provisions and Requirements 1.2 Before performing any work or ordering any materials, the Contractor shall be responsible for verifying all project conditions and his subcontractors, forverifying that actual field conditions are not in conflict with the dimensional relationships and design intent as shown on the drawings. The Contractor shall immediately advise the Architect of any discrepancies and/or conflicts between the existing conditions and the Construction Documents priorto proceeding with the work in question or related work. 1.3 As a minimum standard, all materials and workmanship shall be equal or superior to prevailing industry practices, and all work performed and materials installed shall be in strict accordance with all applicable codes, regulations and ordinances ofthe governing jurisdiction. Contractor shall obtain all permits required for construction and occupancy ofthe project. 1.4 Install all manufactured items, materials and equipment in strict accordance with the manufacturers recommended specifications, unless otherwise specifically noted or approved bythe Architect or interior designer in advance ofthe installation. Where applicable and available from Owner or building management, referto Building Standard Information for details, assemblies, and typical finish specifications. Notify Architect of any conflicts between building standards and the Contract Documents priorto starting work. 1.5 The Contractor shall be responsible for familiarizing himselfwith the Owner's requirements for occupancy, and shall, priorto the start of work, submit a Project Schedule indicating milestone dates, and delivery dates for long lead time items. The schedule shall be updated as necessary throughout the duration ofthe project. All proposed changes are to be approved bythe Owner and Architect. 1.6 All Contractor or Supplier requests for substitutions of specified items shall be submitted to the Architect in writing and be accompanied by proposed alternative product information. A substitution will be considered only if it does not sacrifice quality, appearance and function. Under no circumstances will the Architect be required to prove that a product proposed for substitution is or is not of equal qualityto the product specified. 1.7 Installation of all selected materials and assemblies shall be complete and functioning in all respects prior to final acceptance. Any miscellaneous items or materials not specifically noted, but required for proper installation shall be furnished bythe Contractor. The Contractor shall furnish to the Owner all warranties and guarantees required atthe conclusion ofthe work. The Contractor is responsible for the inspection, acceptance, storage, installation and continuous protection of all new materials delivered to the project. 1.8 When required bythe drawings or specifications, the Contractor shall submit (three complete hard copies or electronic data) shop drawings, schedules and cut sheets for items specified for review bythe Architect priorto order or fabrication. When submitting, the Contractor shall notify the Architect, in writing, of any proposed deviations from the Contract Documents, along with the reason for the proposed deviation. Any fabrication carded out priorto the review ofthe shop drawings bythe Architect shall be at the Contractor's risk. CDS will reviewshop drawings and submittals within ten business days in most cases. Review of these items by the Architect and the Architect's consultants, shall be for general conformance to the design intent ofthe project and with the information within the contract documents. Review of a separate item shall not indicate a reviewof an assembly in which the item functions. Shop drawings that are incomplete or contain excessive errors will be returned unchecked with any resulting delay being the responsibility ofthe Contractor. The Contractor shall submit and resubmit the required number ofcopies of corrected shop drawings. Review of shop drawings, submittals and/or samples by the Architect orthe Architect's consultants shall not relieve the Contractor of responsibility for erom and omissions in the items submitted. 1.9 The Contractor shall guarantee that the materials and workmanship shall be ofthe quality specified or referenced standards, and that any defect due to improper workmanship or defective material discovered and made known within one year from the date of substantial completion ofthe installation, shall be repaired or replaced with reasonable promptness without additional expense to the Owner. The Owner shall give notice of such observed defects with reasonable promptness. 1.10 Bid all materials as if being purchased new. Provide Owner credit for materials proposed to be reused or available from Owner's existing stock. 1.11 Contractor shall perform high quality professional work. Join materials to uniform accurate fits so they meet with neat, straight lines, free of smears or overlaps. Install exposed materials appropriately level, plumb and at accurate right angles, orflush with adjoining materials. Work of each trade shall meet all national standards published by the trade, except in the case where contract documents are more stringent. 1.12 The General Contractor shall at all times cooperate with others who may be performing work at the job site which is not in the general contractors contract. 1.13 The General Contractor shall be responsible for the protection of existing and newly installed materials, millwork, built-ins and finishes. 1.14 The General Contractor shall provide blocking in partitions as required for all items attached to walls. All blocking shim materials shall be fire resistant in accordance with all applicable codes and requirements. 1.15 Provide necessary outlet boxes, conduit and plastic rings as needed (with pulls) for all telephone/cable/data outlets indicated unless noted otherwise. 1.16 When electrical work is specified in conjunction with millwork items, all raceways, pre -wiring, and fixtures shall be provided and installed by Electrical Contractor. Cut-outs for outlets, switches, etc., as required are by Millwork Contractor and shall be coordinated with Electrical Contractor. 1.17 Details are typical fora similar condition throughout, unless otherwise noted. Typical implies typical for all similar conditions, unless otherwise noted. Align implies align other similar components ofconstruction, i.e., face ofwalls, millwork, etc. 1.18 The Contractor is responsible for continuous and final cleaning and debris removal. The Contractor shall protect and maintain areas outside the project area including paths oftravel throughout the building. The Contractor shall construct dust proof partitions to protect common areas, building occupants, building systems, and building finishes. Clean and/or polish surfaces as necessary and appropriate to the material orfinish being cleaned. Items to be cleaned include but are not limited to: - SAC Tile and Grid - Switches, Outlets, Devices, Diffusers, Grilles, Louvers, etc. - Light Fixtures (including lamps, lenses, diffusers and trim) - Plumbing Fixtures &Trim - Appliances and Accessories - Sprinkler, Detection, and Life Safety System Components and Trims - Painted or Stained Surfaces - Wall Coverings - Floor Coverings & Floor Base - Glass and Glazing Systems (all sides) - Laminates, Solid Surface Materials - Stone and Ceramic Surfaces (including groutjoints) - Millwork, Casework & Cabinetry (including cabinet interiors) Remove all labels, dirt, dust, debris, grease, adhesives, paint drips/overspray, and stains, etc. from all surfaces. 73 0- 00 Lo N N O N 00 M 1.19 Contractor shall at all times, take necessary measures to minimize interruption to Owner or Tenant operations. Schedule an work involving excessive noise fumes construction traffic or debris for off -hours P Y 9 coordinate with Owner and buildingmanagement. Avoid an disruption of utilities or services to occupied 9 Y P P areas. Coordinate demolition and construction schedules with Owner and building management. 1.20 The presence of a representative of CDS on the job site does not imply concurrence or approval ofthe work. The Contractor shall call specific items to the attention ofthe CDS representative if he wishes to obtain P P CDS approval. The Contractor shall document all field approvals with a separate field report or in week) PP PP P P Y project minutes. 1.21 If the Contractor Owner or Tenant substitute a material revise a construction detail method of attachment or in any wayalter the work so that it does not conform with these documents without CDS written approval, such action will relieve the Architect of any responsibility of liability as to the functionality, aesthetic effect, subsequent failure, property damage or personal liability. 1.22 Contractor shall provide to the Architect a set marked -up Contract Documents indicating the final "as - built" conditions of the project. All architectural, mechanical, electrical, plumbing, and fire protection changes and/or additions shall be legibly shown. 1.23 Verify existing fire extinguishers are updated, and provide new as required by drawings. All new fire extinguishers are to be installed in recessed or semi -recessed cabinets. Submit cut sheets. DEMOLITION NOTES 1.0 Salvageable items to be removed are the property ofthe Owner and shall be protected and stored at a location determined bythe Owner or Property Manager. Typical salvageable materials include doors, frames, hardware, glazing, HVAC components, plumbing fixtures, electrical/lightingAife safety components, ceiling tile and other ceiling components. Salvageable implies that the component is refurbishable, so as to be reasonably indistinguishable from new items. Existing materials approved to be reused shall be refurbished so as to be comparable, matching, and reasonably indistinguishable to similarto new materials. Recycle removed carpeting. 1.1 Remove and store, or protect in place, all building standard window coverings and re -install after completion of construction. Protect all millwork, doors, frames, glazing, fixtures, devices, & accessones, etc., during demolition & construction. 1.2 All switches, outlets, etc. to be removed or relocated shall be completely removed, with abandoned conduit and wiring stripped back to the source. Patch and finish as indicated on drawings. 1.3 The General Contractor and Sub -contractors are required to refer to the Engineers plans for additional demolition, relocation and final design requirements, and field verify all reasonably accessible conditions to assess the work required for conformance to the final construction documents and design intents. While not necessarily indicated bythe drawings, existing conditions may require additional mechanical, electrical, plumbing, sprinkler, and architectural demolition in areas ofthe project work. The Contractor is responsible for this additional demolition. 1.4 For demolition in areas with or adjacent to wall covering to remain, consult with wall covering contractor regarding preservation of materials to remain and extent of materials to be removed. For floor covering demolition, completely remove all materials, tack strips, leveling materials, grout and/or adhesives, patch surfaces as necessary, and prepare for newfloor covering installation per manufacturer's specifications. CONSTRUCTION AND MILLWORK NOTES 1.0 Do not scale drawings. Dimensions govern; enlarged plans and details govern over smaller scale. New drywall partitions are dimensioned from face ofwall to face of wall unless otherwise noted. Existing partitions are dimensioned from finish to finish. Windowwalls are dimensioned from centerline of mullion or joint to centerline ofmullion orjoint. Glazing sizes are shown as nominal, actual sizes shall be field vented after glazing system or finished opening is constructed. Electrical and communications outlets or devices are dimensioned from centerline of single outlet or device or group ofoutlets or devices. Where two or more devices are indicated, each device in a group is to be located immediately adjacent to the next device. 1.1 Furnishings, fixtures and equipment may be shown for reference purposes, and are not a part ofthe construction contract unless otherwise noted. 1.2 Replace any firestopping altered in the course of performing the work ofthe project. For new installation offirestopping, provide product data and certificates certifying compliance with UL and ASTM E 84 and ASTM E 814 requirements. Installation offrestopping to comply with manufacturer's specifications and with testing agency's specifications forthe required fire -resistance rating. 1.3 Replace any building thermal or acoustical insulation altered in the course ofperforming the work of the project. For new installation of insulation, provide product data and certificates certifying compliance with UL and ASTM E 84 and ASTM C 665 requirements. Materials and installation of insulation materials to comply with manufacturer's specifications and with testing agency's requirements for performance (r -value, STC rating, etc.) and flame spread (maximum 25) and smoke -developed (max 50) surface burning characteristics. 1.4 Do not proceed with gypsum drywall installation over inadequately spaced or poorly aligned framing. It is the General Contractor's responsibility to coordinate the work of sub -contractors in order to ensure that one sub -contractor does not perform work or install materials over inappropriately finished, damaged, or otherwise poorly prepared work. Notifythe architect or designer immediately regarding any concerns or conflicts regarding the compatibility of anyfinish specified and the preparation or condition ofthe related substrate. Unless otherwise specified, all gypsum drywall shall receive a Level 4 (GA -214-96) or higher finish. All joints and interior angles have tape embedded in joint compound and two separate coats ofjoint compound applied over all flatjoints and one separate coat ofjoint compound applied over interior angles. Fastener heads and accessories are covered with three separate coats ofjoint compound. All joint compound to be smooth and free of tool marks and ridges. Finished surfaces shall be coated with a drywall primer prior to the application of final finishes. Wallboard edges and inside and outside corners shall be crisp and straight or plumb. Reveals, when present, shall be uniform (parallel) and aligned vertically or horizontally unless otherwise specified. Flat surfaces will be free of gouges, trowel marks, and pitting. No corner or edge material, joints orjoint tape or tape edges, mud, or screws or screw locations shall be visible or 'telegraph' through applied finish materials. Joints shall be taped and joint compound applied to within 3/4" above floor, and finished smooth for installation of final finishes and floor base. All partitions extending to the bottom of suspended acoustical ceiling systems shall receive compressible neoprene tape (1/4"x 1- 1/4") between ceiling and runner track. Provide non-combustible blocking equal to the depth of the acoustic tile reveal when working with tegular edge tiles. 1.5 Within the project area, including the outside faces of perimeter and exterior limits, the Contractor shall seal all penetrations in structure to structure partitions or other existing rated assemblies (floors, chases, etc.), whether caused by the work of the Contractor or existing. All penetrations shall be sealed in a manner that maintains requirements for rated separations between areas. 1.6 The Contractor shall provide slip joints at all wall connections to building envelope or structure, and bracing for all walls below structure. Slip joint construction shall maintain fire rated separation, where applicable. 1.7 Contractor shall provide sufficient framing of all openings for duct work return air grill openings above and below ceiling; these are to be coordinated with the air conditioning engineer's and mechanical contractors shop drawings. All openings shall be properly sealed for soundproofing and vibration control. 1.8 Walls shown aligned with base building structure, shall be flush and smooth with the base building structure, unless otherwise indicated. All existing corner beads shall be removed, taped and spackled properly. 1.9 The Contractor shall provide and install all plumbing rough -ins, fixture accessories and equipment required to complete the installation as shown and noted. 1.10 The Contractor shall coordinate the drywall rough openings and dimensions with the requirements of any millwork. 1.11 Where STC rated assemblies are specified, provide materials and assemblies identical to UL or ASTM tested assemblies of the specified rating. Submit testing agency rating for assemblies utilized. 1.12 Unless otherwise dimensioned doors shall be set 4" from clear opening of frame to immediate adjacent partition. 1.13 All hardware required but not specified in these drawings is to be selected by the Contractor and submitted to the Architect for review before orders are placed. 1.14 Furnish and install all architectural woodwork counters tops, casework paneling, panel -work, and closet/stora a shelving) shown on drawin sands specified herein. Provide and coordinate complete installation of 9 9) 9 P P items, where the work of other trades is necessary for intended function. Architectural woodwork includes all interior woodwork exposed to view in finished building and includes wood, wood veneers, plywood, laminates, liners, and vinyl surfaces or edgings. 1.15 The "QualityStandards' of the Architectural Woodwork Institute shall a and b reference are hereby PPY v v made a part of this specification. Any reference to Premium, Custom or Economy in this specification shall be as defined in the latest edition of the AWI "QualityStandards". An item not given a specific quality rade shall be v 9 P 9 Y9 provided as "Custom" rade as defined in the latest edition of the AWI "Quality Standards'. Submit shop drawin s P 9 Y P 9 on all items of architectural woodwork. Submit manufacturer's descriptive literature of specialty items not P Y manufactured b the architectural woodworker, as requested b the Architect. Submit samples of each wood Y 9 Y P species which is to receive transparent finish at job site, as requested by the Architect. Submit finish samples of each painted or laminated finish to be applied at factory. All new millwork to use FSC Certified & formaldehyde free wood products including blocking, plywood, particle board, MDF, &laminate. The woodwork manufacturer is responsible for details and dimensions not controlled byjob conditions and shall show on his shop drawings all required field measurements beyond his control. The General Contractor and the woodwork manufacturer shall cooperate to establish and maintain these field dimensions. The woodwork manufacturer and the Contractor shall be jointly responsible to make certain that woodwork is not delivered until the building and storage areas are sufficiently clean, dry and prepared so that the woodwork will not be damaged. Contractor shall provide blocking in partitions as required for all millwork items attached to walls. Unless otherwise noted, work shall conform to flush overlay design standards. All exposed components to match specified finish. Semi -exposed surfaces per AWI grade standards. Unless otherwise noted, interiors of all cabinets shall be covered with liner grade. Finished end panels shall apply when millwork is not abutting a partition. Filler strips shall be installed as required and shall be installed as required and shall match adjoining millwork. For all casework, paneling, frames, and running trim, adjust all joints and miters for tight, aligned fit. Fill openings at joints and at nail sets. Touch-up stain at cuts ijoints, end pieces, etc.) and where color does not match. All plumbingAighting fixtures shall be supplied and installed by plumbing/electrical contractor, who shall supply all necessary information for cut-outs to be performed by cabinet contractor. The General Contractor is responsible for the complete installation and coordination between trades. Unless otherwise noted, tops to be AWI Quality Grade 'Custom' high pressure laminate. Where not specified by the Contract Documents, finish and color selections shall be made by the Owner. All cabinet hardware shall be furnished and installed by casework manufacturer. Submit samples of all exposed hardware. Unless otherwise noted, hardware to be as follows: A: Drawer slides: "Accuride" full extensions; self closing. B: Shelf standards and brackets: K.V. heavy duty. C: Hinges: Blum or equal. D: Catches: Optional with supplier. E: Pulls: Varies, see millwork drawings for locations & types F: Clothes poles: Optional with manufacturer. 1.5 All floodingis to be installed over properly prepared surfaces. Perform moisture test to confirm P P YP P moisture content per manufacturers recommendation. Installed stone or ceramic file shall be clean proper and free from grout, adhesives, paint drips/overspray, etc. Sub -floors shall be clean, leveled and otherwise prepared to receive finish flooring without noticeable unevenness. Grout shall be sealed. No tripping hazards from raised edges or comers will be acceptable. Where resilient flooring is specified, no telegraphing of unfinished, irregular, substrate will be accepted. All materials will be fully adhered to sub - floor, free of gaps, bubbles and bulges. Seams shall be per manufacturer's method and tolerances. 9P, 9 1.6 Where countertop a partition artition and adjoins backs lash a sealant caulk shall be applied which P PP matches the color of laminate specified. 1.7 Where rubber or vinyl wall base materials are specified, Contractor shall use continuous rolled stock (not 4' sections) to minimize joints. The Contractor shall utilize preformed inside and outside corners where offered by the manufacturer. Base material shall be level and uniformly adhered along walls and corners, with joints tightly butted and aligning. All walls shall be finished as specified or as otherwise necessaryto receive the specified base materials . Wood tile or other rigid materials are to be installed P 9 over smooth, even walls. Caulk gaps and fill (or grout) joints as required and appropriate to material. No obvious bows, gaps, or misalignments vAll be accepted. Do not install over poorly prepared substrate (floors or walls). 'Telegraphing' of substrate irregularities or adhesives will not be accepted. 1.8 Patch, repair and finish (paint or stain) all existing doors and frames to remain for reasonably comparable finish to new doors and frames. Remove paint or stains from hardware to be reused and polish for reasonably comparable finish of new hardware. Unless otherwise noted, all doors shall receive the same finish both sides. Unless otherwise noted, stain wood items (doors, moulding, base, etc.) shall match existing to remain in project area or building standard finish. 1.9 Provide 8" x 8" (min) samples of all finishes and colors specified to Architect for approval prior to commencement of work. Painting Contractor to paint a single 24" x 60" sample of each paint specified (coordinate walls to receive paint samples with Architect) for Owner approval prior to final purchase of paint materials. Submit manufacturer's flame spread ratings with samples of finish materials. Flame spread ratings for wall coverings shall be 25 or less, smoke -developed rating to be 450 or less per ASTM E 84. 1.10 New and repaired acoustical ceiling systems (grid components and tile) are to match building standard. Center ceiling mounted devices in tiles, typical. Ceiling system materials and installation to comply with ASTM E 1264, ASTM E 84, ASTM C 635 & 636, ASTM A 641 and IBC standards. All grid components are to be clean and in place, with ceiling tiles and devices setting flush into grid, clean and free of chips and scrapes. Grid components (mains and tees) shall be hung for level installation throughout. Level all existing components to remain. Replace missing, damaged and incomplete or patched segments for like new installation. Use matching system components. No obvious repairs will be accepted. Where new and reused items are used, separate new from reused by area/room. Utilize reused components (where applicable) in less visible areas/rooms (storage or utility rooms, for example) when possible. All devices penetrating ceiling tiles shall be snug fitting, clean, and complete with all trim. No gaps between tile cuts and trim pieces shall be visible. All devices shall be centered on tiles (unless otherwise specified by the drawings) except where above -ceiling conflicts make centering impossible. It is the General Contractors responsibility to coordinate the work of sub -contractors in order to preserve the ability to center or otherwise locate devices as specified by the architect of engineers. Bring any conflicts to the immediate attention of the architect or engineer. 1.11 Provide cement board on walls behind all tile and FRP. 1.16 Door/Frame/Sidelite System to match building standard unless otherwise noted. Submit product data, finish MECHANICAL, PLUMBING, ELECTRICAL, DATA/COMMUNICATIONS & LIFE SAFETY (M/P/E/C/LS) samples, and door schedule. SYSTEMS NOTES Doors and Frames shall be rated in accordance with A.S.T.M. procedure for use in fire rated wall assemblies. Comply with ANSI/SDI 100 and NFPA 80 for fire rated door assemblies. All new or modified components shall be labeled by U L or acceptable rating agency. Frames shall encompass the specified finished wall thickness and attach to the wall with all fasteners concealed. Frames shall accommodate 1-3/4" thick doors and surface mounted closers. Jambs shall be over -length to permit custom fitting to the floor. Jamb design shall permit jamb removal and replacement without disturbing the stud fasteners and without damage to the wall finish. Fixed throat jambs shall be adaptable to receive standard flush glazing snap -in sections where sidelites are used. All frame and sidelite units shall be furnished with steel attachment clips for extrusion intersections so as to facilitate fast, precise installation. Assembled glass frames shall provide 5/16" minimum glass coverage at head, sill and jambs, or 5/8" total coverage. All glazing extrusions shall accommodate 1/4" thick glass as specified. Finished doors shall be trimmed and beveled to ft frame opening with standard clearances as follows: 1/8" at hinge edge, 1/8" at lock edge, 1/8" at top, 1/4" at bottom, stiles beveled 1/8" in 2". In order to ensure proper fit to uneven floors, doors shall be ordered with sufficient over -length at bottom to permit custom fitting to floor by the door installer. Doors shall be completely prefnished and machined for all hardware as specified. Match veneer species, stain, and grain patterns of existing doors in project area. Door edge finishes shall match face finishes. 1.17 All 'hard' ceilings will be installed and finished such that seams and edge/comer bead materials do not telegraph. All devices, grille frames, fixture trim pieces, etc. are flush and caulked. Devices will align as shown or specified on architect's or engineer's drawings. It is the General Contractors responsibility to coordinate the work of sub -contractors in order to preserve the ability to align or otherwise locate devices as specified by the architect of engineers. Bring any conflicts to the immediate attention of the architect or engineer. Ceiling and drywall soffit finishes shall receive a Level (GA -214-96) or higher finish. Meet all finish standards for wall finishes. 1.18 Any new concrete slabs shall conform to all applicable ASTM Standards for curing methods/time, reinforcing, etc. FINISH NOTES 1.0 Do not install or applyfnishes over poorly constructed or prepared substrates. Immediately notifythe Contractor of conditions affecting the quality or appearance of a specified finish. Advise the Architect if there are unforeseen conditions or other concerns or circumstances preventing any specified material from fulfilling the intent ofthe design for safe and properfunction and a pleasing appearance, compatible with other existing and new materials. Repair and touch up any items when damaged during demolition or construction when item intended to remain. 1.1 All drywall finishes shall be Level 4 or higher unless otherwise noted. High color accent walls and lighted walls (wall washers, spot lights, etc.) and wdteable walls shall be finished to Level 5 standards. Provide overlay or skim coat if required to meet appearance standards of specified finish. Extend preparation and finish in project area to nearest surface break. Finish drywall to within on halfinch offloor. 1.2 All surfaces shall be properly cleaned and prepared priorto installation of all paint and base. Paint shall be roller -applied to non-metallic surfaces using short -nap (1/2" or less), lint -free roller covers or as recommended bythe paint manufacturer. Utilize a three coat system (primer plus two finish coats) on all newly painted surfaces unless otherwise noted. Provide stain killers and additional coatings where required for even, non -transparent coverage over substrate and/or existing colors. 1.3 Unless otherwise noted, all paints shall be premium commercial grade, lowv.o.c. acrylic latex, low -sheen eggshell finish (otherthan flat) not susceptible to burnishing under normal office and commercial wear. All metal components (access panels, door frames, metal doors, grilles, diffusers, etc.) to be painted shall be semi -gloss latex enamel. All new items shall be shop finished. Unless otherwise noted, contractor shall patch, prepare and repaint all existing partitions shown to remain. Remove all existing device covers, fixtures, furnishings, signage, etc., priorto installing newfnishes. Clean and replace/reinstall all items removed priorto painting. 1.4 All HVAC ceiling diffusers and registers shall be prefinished to match building standard devices, unless otherwise noted. Caulk around all doorframes, glazing systems, running trim (base and crown mold), millwork (built- ins, cabinets & countertops), grilles, registers, louvers, access panels, and other ceiling and/orwall mounted devices. Caulk color to match device finish. 1.0 The Mechanical, Plumbing, Electrical, Data/Communications and Fire Protection contractors shall field verify all existing conditions and shall familiarize themselves with all work and dimensions. The Contractor shall notifythe Architect of any conditions or discrepancies adversely affecting the design and installation priorto proceeding with the work. This shall include conflicts with mechanical ducts, piping and structure. Immediately notify Architect if existing M/P/E /C/LS systems are in conflict with the intents ofthe architectural or engineering design. 1.1 Locations of M/P/E/C/LS and life safety components, fixtures, devices, etc., shall be as shown on architectural plans. Referto Engineering drawings and specifications for system or component integration and performance requirements. If discrepancies between the engineering and architectural drawings occur, notify Architect priorto bidding or installation for clarification. The Contractor shall be responsible for costs of reinstallation ofwiring and components when no clarification of discrepancies is requested. The contractor shall be responsible for engineered and code conforming installation of systems provided as 'Design -Build' 1.2 No component, fixture or device substitutions shall be permitted without written confirmation from the Architect. Devices include switches, power/data outlets, thermostats, wall stops, Life Safety components, access panels, grilles, diffusers, light fixtures, speakers, etc. If a new component, fixture, or device is not specified, use building standard components, or exactly match components existing within the project area. Seek clarifications where specifications conflict with existing conditions. Verifythat all M/P/E/C/LS components to be reused in the project area are functioning and adjusted properly. Clean all new and reused components. Remove all labels unless required to remain by code or manufacturer. All new devices shall be consistent with respect to finish or color and mounting heights. All trim shall be secure, flush to wall and attached with matching hardware. 1.3 Provide fire dampers in all ducts penetrating fire rated or demising partitions. 1.4 The Contractor and Subcontractors shall provide for uninterrupted building utilities and life safety systems operation, unless coordinated with the Owner. 1.5 All dimensions to the centerline of an outlet or pair of outlets, unless otherwise noted. All outlets shown back-to-back shall be offset 6" minimum. Provide necessary studwork supports needed for installation. All cover plates to be building standard, unless otherwise noted. Where more than one switch occurs in the same location, they shall be installed in a gang -like box under one cover plate, unless otherwise noted. All existing outlets not utilized by a tenant for electrical, telephone or CRT shall be capped with a blank cover plate - see finish. All thermostats shall be at building standard height unless otherwise noted, and located as shown on mechanical drawings. When thermostats and light switches occur together, install thermostat at V-6" above the same witch on centerline, with switch and thermostat aligned vertically on the same partition. 1.6 Mechanical, Plumbing, Electrical, Data/Communications and Life Safety subcontractors shall provide as -built drawings offnal circuiting, switching, lighting and HVAC/plumbing diagram. 1.7 Electrical Contractor shall clearly and accurately label all new panel boxes, circuits, and outlet covers associated with the project area. 1.8 Verify telephone /IT -data requirements and telephone equipment board location with the Owner before proceeding with the work. City of Wheat Ridge Building Division PERMIT SET IS FOR BUILDING DEPARTMENT REVIEW. FINAL PRICING SHOULD INCLUDE ALL DRAWINGS ISSUED AS ADDENDA FOR PERMIT APPROVAL. Op C0 O W0ROBERT OyJOHNT OLUNRD �/ T7.i $A 0,0 F D ARS+ OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO P.C. 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 AWWill0Eel mIlill THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN CAN ONLY BE USED FOR THISPROJECT. NO OTHER USE OFTHIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUTTHE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. 1 CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Project Number: 20019 SPECIFICATIONS G012 RECEPTION ♦ 100 OWNER TO PROVIDE WATER SERVICE AS PER IPC 410.4 IN SUBSTITUTION OF SECOND WA—TER�' 3'-6" •' 12 Q W co N O N O N LO N Iy:I�\�N�iI ANIMAL HOSPITAL FUNCTION: BUSINESS AREA SUBTOTAL: 3675 SF LOAD FACTOR: 100 SF / OCC OCCUPANT LOAD: 36.75 EXAM 3 ♦ 103 �do ' • 1W EEN EX`-� g�, 62 -0 do • A� p\S1 NA BE • 10 EXAM 4 OFFICE 104 T 117 0 0 LAB 107 A X RAY 108 TREATMENT 109 • GROOM 110 A o RESTROOM 111 ISOLATION 112 i DENTAL DOGS 114 113 1 o ` J cfl RESTROOM o I 106 HALL 118 T T T T T ♦ DELIVERY 301-011 26-0 If TOTAL TRAVEL DISTANCE: 85'-6" (MAX: 200'-0") 2 COMMON PATH OF TRAVEL: 41'-6'♦ O� F RE EXTINGUISHER _ I ° L7 EXAM 5OFFICE BREAK ° o 105 119 122 ♦ UTILI I 121 LL `I 5'-6" 1 LEVEL 01 SCALE: 1/4" = V-0" EGRESS LEGEND SYMBOL DESCRIPTION SPRINKLERED • 200' •'rEil B 200' DENTAL DOGS 114 113 1 o ` J cfl RESTROOM o I 106 HALL 118 T T T T T ♦ DELIVERY 301-011 26-0 If TOTAL TRAVEL DISTANCE: 85'-6" (MAX: 200'-0") 2 COMMON PATH OF TRAVEL: 41'-6'♦ O� F RE EXTINGUISHER _ I ° L7 EXAM 5OFFICE BREAK ° o 105 119 122 ♦ UTILI I 121 LL `I 5'-6" 1 LEVEL 01 SCALE: 1/4" = V-0" EGRESS LEGEND SYMBOL DESCRIPTION SPRINKLERED COMMON PATH OF TRAVEL: 200' 75' MAX (TYPICAL OCCUPANCY) B 200' 300' 25' MAX (H OCCUPANCY) 300' 100' MAX (FULLY SPRINKLERED B, F & S OCCUPANCY) 1-1, 1-2, 1-3, 1-4 COMMON PATH OF TRAVEL: 200' 2 SEPARATE PATHS OF EGRESS TO SEPARATE EXITS OVERALL DIAGONAL DIMENSION DISTANCE BETWEEN EXITS (< 1/3 OVERALL DIAGONAL DIMENSION) TRAVEL DISTANCE OCCUPANCY MAXIMUM EXIT ACCESS TRAVEL DISTANCE NON-SPRINKLERED SPRINKLERED A, E, F-1, M, R, S-1 200' 250' B 200' 300' F-2, S-2, U 300' 400' 1-1, 1-2, 1-3, 1-4 NP 200' OCCUPANCY 2 EXITS REQ'D WHEN OCCUPANT LOAD > THAN A, B, E, F,M,U 49 H-1, H-2, H-3 3 H-4, H-5, 1-1, 1-2, 1-3, 1-4, R 10 S 29 NOTES: SEE CODE SUMMARY FOR ADDITIONAL EGRESS INFORMATION OCCUPANT LOAD & EXITING LEGEND DOCCUPANT LOAD CODE ANALYSIS 2018 INTERNATIONAL BUILDING CODE (IBC) 2018 INTERNATIONAL MECHANICAL CODE (IMC) 2018 INTERNATIONAL PLUMBING CODE (IPC) 2018 INTERNATIONAL FIRE CODE, AS REFEREED BY IBC (IFC) 2018 INTERNATIONAL FUEL GAS CODE (IFGC) 2020 NATIONAL ELECTRIC CODE 2018 INTERNATIONAL ENERGY CONSERVATION CODE (IECC) IECC PRESCRIPTIVE PATH, REFER TO MECHANICAL AND ELECTRICAL CODE AND DESIGN CRITERIA ICC/ANSI A117.1 - 2009 AND ALL CURRENT WHEAT RIDGE AMENDMENTS CONSTRUCTION TYPE: V -B OCCUPANCY CLASSIFICATION - B BUILDING HEIGHT: 1 STORIES TOTAL BUILDING AREA: 21,745 SF - EXISTING PROJECT AREA: 3,675 GSF TOTAL OCCUPANT LOAD: 37 (SEE EGRESS PLAN) FIXTURE COUNTS 37/2 = 19 PERSONS PER GENDER WATER CLOSETS REQUIRED: 1 PER 25 FOR THE FIRST 50 AND 1 PER 50 FOR THE REMAINDER EXCEEDING 50 PER IBC 2902.1 = 19/25 = 0.76 (1 PER GENDER.) PROVIDED: 1 LAVATORIES: REQUIRED: 1 PER 40 FOR THE FIRST 80 AND 1 PER 80 FOR THE REMAINDER EXCEEDING 80 PER IBC 2902.1 = 19/40 = 0.475 (1 PER GENDER.) PROVIDED: 1 SERVICE SINK REQUIRED: 1 PER IBC 2902.1 PROVIDED: 1 DRINKING FOUNTAINS REQUIRED: 1 PER 100 PER IBC 2902.1 PROVIDED: 1 FIRE ALARM: YES - EXISTING SPRINKLER SYSTEM: NO IECC REQUIREMENTS CLIMATE ZONE 5B SWINGING OPAQUE DOORS: U-0.37 REVISION City of Wheat Ridge Building Division chcird"11, /OIIF- C040\ C07ROBERT yd JOHN O n 1 W11 4.0 /. OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.C. 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 COPYRIGHT: 2020 THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN CAN ONLY BE USED FOR THIS PROJECT. NO OTHER USE OF THIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUT THE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. # DESCRIPTION DATE 1 PERMIT SET 15 SEPT 2020 2 ADDENDUM #1 13 NOV 2020 3 ASI 1 13 DEC 2020 CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Project Number: 20019 OCCUPANT LOADS, EGRESS & TRAVEL DISTANCE G201 0 N N 0 N 0 N C2 M WALKING PARALLEL TO A WALL UNOBSTRUCTED FORWARD REACH LIMIT NOTE: THE SEPARATION BETWEEN OUTLETS &THE DISTANCE FROM THE LIGHT SWITCH TO JAMB TO BE CONSISTENT THROUGHOUT THE SPACE. v m ZR" ANY AMni INT WALKING PARALLEL TO A WALL 0 N Q ADA POWER INSTALLED PUSH BUTTON EXTINGUISHER N H N 111 INCHES TO BE BE_RNEEN 48 INCHES 34"-48" AFF 142 INCHES X 36 INCHESI J LL Z FOUNTAIN SIGN BUT NOT ON DOOR SIGN IN U OR LAVATORY) LL Z O O 30" MIN. CLR. N VI � v 12" MAX z zo MAXIMUM FORWARD REACH OVER AN OBSTRUCTION SINGLE SWITCH PLATE, TYP. THERMOSTAT GANG PLATE ELECTRICAL WALL OUTLET SMOOTH SURFACE FULL WIDTH OF DOOR ON PUSH SIDE SOAP DISPENSER o w z F= <� v U Q x M w U w. FIRE ADA POWER INSTALLED PUSH BUTTON EXTINGUISHER DOOR HANDLE CABINET MOUNTING HEIGHT 111 INCHES TO BE BE_RNEEN 48 INCHES 34"-48" AFF SMOOTH SURFACE FULL WIDTH OF DOOR ON PUSH SIDE SOAP DISPENSER o w z F= <� v U Q x M w U w. FIRE SOAP DISPENSER EXTINGUISHER (48" MAX AT 20" DEEP CABINET OR LESS 111 INCHES OBSTRUCTION) MAXIMUM REACH DEPTH AND HEIGHT OPERABLE PARTS ON TOWEL DISPENSERS AND HAND DRYERS MAXIMUM REACH DEPTH 1 .5 INCH 12 INCHES 15 INCHES 16 INCHES 19 INCHES 111 INCHES MAXIMUM REACH HEIGHT 48 INCHES 148 INCHES 142 INCHES 1401NCHES 36 INCHESI 34 INCHES w PAPER TOWEL MIRROR MOUNTED WALL NAPKIN DISPENSER & OVER A LAVATORY MOUNTED a RECEPTACLE (35" AFF IF NOT DRINKING LL w a OVER A COUNTER FOUNTAIN SIGN BUT NOT ON DOOR SIGN IN U OR LAVATORY) 0 x ❑ a Z O O 30" MIN. CLR. VI 777TH (#288114) 12" MAX z t7 CLEAR RASTER STYLE BRAILLE z ..... SIZE SHALL COMPLYw/ LOCAL CODE OTHER FIXTURES NOT / w - 36" MIN 6" MAX U TACTILE CHARACTERS SHALL m IN SIZE BE PERMITTED ON THE PUSH O ALLOWED IN THIS AREA a 54 MIN m 6"x2" MIN. IN SIZE GRAB SIGNAGE LL BARSO d w U O Nw z O 42" MIN :2z v z o J ❑ z y m - F v p a°i w o M m 0 a m SANITARY PAPER TOWEL MIRROR MOUNTED WALL NAPKIN DISPENSER & OVER A LAVATORY MOUNTED RECEPTACLE RECEPTACLE (35" AFF IF NOT DRINKING PYLON BEFORE w a OVER A COUNTER FOUNTAIN SIGN BUT NOT ON DOOR SIGN IN U OR LAVATORY) 0 x ❑ a NOTE: ALL VERTICAL GRAB BAR DIMENSIONS ARE TO THE TOP OF THE GRIPPING SURFACE I! l:r A THIS OVERHANG CAN BE GREATER THAN 12" BECAUSE NO ONE CAN APPROACH THE OBJECT FROM THIS DIRECTION CANE RANGE 12" MAX V WALKING PERPENDICULAR TO A WALL OBJECTS MOUNTED ON POSTS OR PYLONS -PLAN VIEW m Z UNOBSTRUCTED SIDE REACH LIMITS 30" X- 24" MAXIMUM SIDE REACH OVER AN OBSTRUCTION 12" v CANE FLOORSPACE Q 60"MIN CLEAR CANE HITS POST 39"-41" AND 450 OPEN POSITION -TYP. OR POST OR T(RANC w EQ EQ m BUILDINGS AND FACILITIES PYLON BEFORE w a a z FLOORSPACE SIGN BUT NOT ON DOOR SIGN IN U OBJECT 0 x ❑ a Z O O 30" MIN. CLR. Q J LL 777TH (#288114) 12" MAX z CORRESPONDING GRADE 2 CLEAR RASTER STYLE BRAILLE FLOORSPACE ..... SIZE SHALL COMPLYw/ LOCAL CODE OTHER FIXTURES NOT / w - 36" MIN 6" MAX PICTOGRAM SIGN TO BE 6"x6" MIN. TACTILE CHARACTERS SHALL m IN SIZE BE PERMITTED ON THE PUSH O ALLOWED IN THIS AREA a 54 MIN m 6"x2" MIN. IN SIZE GRAB SIGNAGE / BARSO U V / EQ EQ/ Nw z O 42" MIN :2z v m p W M m V M M m 0 v o o — 2" MIN 24" MIN 16"- 18"I DISPENSERS TO BE LOCATED 24" CONTROL FOR 6" MAX fI 36" MIN I MIN - 36" MAX FROM REAR WALL IF FLUSH VALVE ABOVE GRAB BAR AND 24"-42"IF SHALL BE 5'- 0" MIN BELOW GRAB BAR. RECESSED UNITS MOUNTED ON THE NOT TO PROJECT MORE THAN 1/4". OPEN SIDE OF THE TOILET CE WATER CLOSETS THAT ARE NOT IN TOILET DRINKING FOUNTAIN COMPARTMENTS WATER CLOSET ELEVATIONS I! l:r A THIS OVERHANG CAN BE GREATER THAN 12" BECAUSE NO ONE CAN APPROACH THE OBJECT FROM THIS DIRECTION CANE RANGE 12" MAX V WALKING PERPENDICULAR TO A WALL OBJECTS MOUNTED ON POSTS OR PYLONS -PLAN VIEW m Z UNOBSTRUCTED SIDE REACH LIMITS 30" X- 24" MAXIMUM SIDE REACH OVER AN OBSTRUCTION 12" WALKING PERPENDICULAR TO A POST v CANE FLOORSPACE Q o CANE HITS POST NATIONAL STANDARD FOR AND 450 OPEN POSITION -TYP. OR POST OR T(RANC w EQ EQ m BUILDINGS AND FACILITIES PYLON BEFORE w a a z PERSON HITS SIGN BUT NOT ON DOOR SIGN IN U OBJECT 0 x ❑ a Z WALKING PERPENDICULAR TO A POST F]Y 1 • MEN WOME THE SIGN TO BE NEXTTO DOOR ON LATCH SIDE, MOUNTED 48" MIN. TO B.O. LOWEST TACTILE CHARACTER (BRAILLE) AND 60" MAX. A.F.F. TO TOP OF HIGHEST TACTILE CHARACTER 30" MIN CLR v SPACE, CENTERED ON TACTILE FLOORSPACE Q o `� NATIONAL STANDARD FOR AND 450 OPEN POSITION -TYP. ACCESSIBLE AND USABLE w EQ EQ m BUILDINGS AND FACILITIES w G w a w a SIGN BUT NOT ON DOOR SIGN IN U of 0 x ❑ a Z O O :2 - m � Q J LL LL (#288114) z - m CORRESPONDING GRADE 2 CLEAR RASTER STYLE BRAILLE w ..... SIZE SHALL COMPLYw/ LOCAL CODE —U AND ADA REQUIREMENTS ANSI A117.1703.3.11 z LL EXCEPTION - SIGNS WITH F]Y 1 • MEN WOME THE SIGN TO BE NEXTTO DOOR ON LATCH SIDE, MOUNTED 48" MIN. TO B.O. LOWEST TACTILE CHARACTER (BRAILLE) AND 60" MAX. A.F.F. TO TOP OF HIGHEST TACTILE CHARACTER 30" MIN CLR NOTE. SIGNAGE MUST SPACE, CENTERED ON TACTILE FLOORSPACE CHARACTERS OF SIGN, BEYOND ARC A117.1 AMERICAN of�� NATIONAL STANDARD FOR AND 450 OPEN POSITION -TYP. ACCESSIBLE AND USABLE w EQ EQ m BUILDINGS AND FACILITIES w G w a w a SIGN BUT NOT ON DOOR SIGN IN U of 0 x ❑ a Z O O :2 - m � BE "BAN K GOTHIC" IN WHITE COLOR (#288114) g„ g„ CORRESPONDING GRADE 2 CLEAR RASTER STYLE BRAILLE w ..... SIZE SHALL COMPLYw/ LOCAL CODE —U AND ADA REQUIREMENTS ANSI A117.1703.3.11 z LL EXCEPTION - SIGNS WITH PICTOGRAM SIGN TO BE 6"x6" MIN. TACTILE CHARACTERS SHALL m IN SIZE BE PERMITTED ON THE PUSH O SIDE OF DOORS WITH LETTER AND BRAILLE SIGN TO BE LAVATORYPLAN (ALSO APPLIES TO DIAPER CHANGING STATION) F O_ N � 24" MAX M o: U ADDITIONAL PROTECTION NOT REQUIRED BE_RNEEN WING WALLS SHELVES D:IS�b9gU919x? SHOULD HAVE PIPE WRAP 8' MIN AT 27" A.F.F. L n M 11" MIN Z_ om LAVATORY ELEVATION (ALSO APPLIES TO DIAPER CHANGING STATION) 34" MAX IS TO TOP LIP OF SINK WHETHER COUNTER MOUNTED OR WALL HUNG) CORRIDOR OR OTHER CIRCULATION SPACE ANY DIM PROTRUDING OBJECTS HANGING ON WALL WITH LEADING EDGES ABOVE 27" PROTECTION AROUND WALL MOUNTED OBJECTS - PLAN PROVIDE WNW' MIN. CLEAR FLOOR NOTE. SIGNAGE MUST SPACE, CENTERED ON TACTILE COMPLYWITH ICC/ANSI CHARACTERS OF SIGN, BEYOND ARC A117.1 AMERICAN OF DOOR SWING BE_RNEEN CLOSED NATIONAL STANDARD FOR AND 450 OPEN POSITION -TYP. ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES INTERNATIONAL TOILET FACILITY AND WITH AMERICANS SYMBOLS ARE REQUIRED ON WALL WITH YACT SIGN BUT NOT ON DOOR SIGN IN REQUIREMENTS REQUIRDISABILIEMENTS THE SAME CONTRASTING COLOR 3/4" TALL & 1/32" RAISED TACTILE LETTERING. FONT SHALL BE "BAN K GOTHIC" IN WHITE COLOR (#288114) g„ g„ CORRESPONDING GRADE 2 CLEAR RASTER STYLE BRAILLE NOTE: SIGNAGE COLOR AND LETTER ..... SIZE SHALL COMPLYw/ LOCAL CODE AND ADA REQUIREMENTS ANSI A117.1703.3.11 z EXCEPTION - SIGNS WITH PICTOGRAM SIGN TO BE 6"x6" MIN. TACTILE CHARACTERS SHALL m IN SIZE BE PERMITTED ON THE PUSH SIDE OF DOORS WITH LETTER AND BRAILLE SIGN TO BE CLOSERS AND WITHOUT 6"x2" MIN. IN SIZE HOLD -OPEN DEVICES. SIGNAGE City of Wheat Ridge Building Division chord,111111 tiOf COLO /.� ROBERT O JOHN \� 5. ARG 0 `� ED AF��+� OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.0 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 AWWAEll Eel. I/DL➢A: THIS DOCUMENTAND THE DESIGNS INCORPORATED HEREIN CAN ONLYBE USED FOR THISPROJECT. NO OTHER USE OFTHIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUTTHE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Project Number: 20019 ACCESSIBILITY REQUIREMENTS G301 SHEET NOTES 1. DO NOT SCALE DRAWINGS. THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS BEFORE CONSTRUCTION. IF THERE ARE ANY DISCREPANCIES, THE CONTRACTOR SHALL NOTIFY THE ARCHITECT BEFORE PROCEEDING WITH THE CONSTRUCTION. 2. ALL DIMENSIONS ON THE DRAWINGS ARE TO THE FACE OF SHEATHING. 3. REFER TO THE STRUCTURAL DRAWINGS FOR SLIP JOINTS ON ALL INTERIOR NON -LOAD BEARING WALLS, UNLESS NOTED OTHERWISE. 4. THE CONTRACTOR SHALL COORDINATE AND IMPLEMENT ALL SAFETY MEASURES REQUESTED AND/OR REQUIRED BY THE LOCAL FIRE MARSHAL, HEALTH DEPARTMENT, BUILDING OFFICIALS, AND ALL OTHER AUTHORITIES HAVING JURISDICTION. 5. THE CONTRACTOR SHALL MAINTAIN SECURITY OF THE CONSTRUCTION SITE THROUGHOUT THE ENTIRE CONSTRUCTION PROCESS. 6. THE CONTRACTOR SHALL SLOPE ALL FLOORS WITHIN A TWO FOOT RADIUS OF A DRAIN AT A MINIMUM SLOPE OF ONE EIGHTH OF AN INCH PER FOOT TO DRAIN, UNLESS NOTED OTHERWISE. 7. THE CONTRACTOR SHALL COORDINATE ALL ITEMS PROVIDED OR INSTALLED BY THE OWNER OR THE OWNER'S SUBCONTRACTORS DURING CONSTRUCTION. THESE ITEMS INCLUDE, BUT ARE NOT LIMITED TO, THE INSTALLATION OF AUDIO AND VISUAL EQUIPMENT, EQUIPMENT AND WIRING RELATED TO THE TELEPHONE, COMPUTER, AND INTERNET SYSTEMS, AND THE INSTALLATION OF THE FOOD SERVICE EQUIPMENT. 8. THE CONTRACTOR SHALL PROVIDE BLOCKING AT ALL WALL HUNG ACCESSORIES, HARDWARE, AND WALL - HUNG CABINETS AS REQUIRED. 9. THE CONTRACTOR SHALL PROVIDE A TRANSITION STRIP AT ALL DISSIMILAR FLOOR MATERIALS. 10. THE CONTRACTOR SHALL REVIEW THE CIVIL, STRUCTURAL, MECHANICAL, ELECTRICAL, AND ALL OTHER RELATED DRAWINGS AND DOCUMENTS FOR ANY ADDITIONAL BUILDING REQUIREMENTS. 11. TYPE I AND II CONSTRUCTION: WOOD BLOCKING IN EXTERIOR WALLS AND ROOF ASSEMBLIES SHALL BE FIRE RESISTANT TREATED (FRT) WOOD. 12. MILLWORKER TO FIELD VERIFY EXISTING COUNTERS TO BE DEMOLISHED AND REPLACED. COORDINATE WITH ARCHITECT ON NEW COUNTER DIMENSIONS EXISTING BUILDINGS 1. THE CONTRACTOR SHALL PATCH AND REPAIR ALL EXISTING FIRE -RATED BUILDING ELEMENTS, ADD FIRE - SMOKE DAMPERS WHERE NEW DUCTS CROSS, AND ADD FIRE STOPS AT ALL PENETRATIONS TO MAINTAIN ALL DESIGNATED FIRE -RATINGS. 2. THE CONTRACTOR SHALL PATCH, REPAIR, AND PAINT ALL EXISTING WALLS TO MATCH ADJACENT SURFACES AS REQUIRED. 3. THE CONTRACTOR SHALL PROVIDE CONTROL JOINTS WHERE NEW GYPSUM BOARD IS PLACED IN ALIGNMENT WITH EXISTING WALLS. ALIGNMENT IS TYPICAL AT ALL LOCATIONS UNLESS NOTED OTHERWISE. 4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING, LEVELING AND/OR GRINDING SMOOTH ALL EXISTING FLOORS FOR THE INSTALLATION OF NEW FLOORING MATERIALS. 5. THE CONTRACTOR SHALL PATCH AND REPAINT ALL EXISTING WALLS AT CONDITIONS WHERE EXISTING FIXTURES ARE TO BE REMOVED. SEE MECHANICAL, PLUMBING, ELECTRICAL, AND ARCHITECTURAL DEMOLITION DRAWINGS FOR LOCATIONS. 6. THE CONTRACTOR SHALL VERIFY ROUGH -IN DIMENSIONS WITH THE MANUFACTURER FOR ALL NEW, EXISTING, AND REUSED EQUIPMENT. 7. THE CONTRACTOR SHALL PATCH, REPAIR, AND PAINT ALL EXISTING CEILINGS TO MATCH ADJACENT SURFACES AS REQUIRED. 8. THE CONTRACTOR SHALL COORDINATE ALL FLOOR CORE DRILLING WITH EXISTING STRUCTURE 9. EXISTING DOORS THAT ARE TO REMAIN ARE UNNUMBERED W N O N O N LO N RECEPTION EXAM 1 100 101 COUNTER 4TCH NT OF )LISHED 1 A402 EXAM 4 104 SINK, UPPER AND LOWER F_ - - -1 CABINETS RELOCATED FROM ISOLATION 112. NEW COUNTER TO MATCH EXTENT OF DEMOLISHED. T I I nnA401 6 ° 1�5E I I � I REST OOM "All• I 106 I I 4'-- 6 -0� 4'-6" • B C 1 OB v A401 6'-0" 6'-1 9 A852 B ALIGN WALL WITH 105A 1056 119 CENTER OF MULLION EXAM 5 105 l A REINSTALL SINK IN NEW COUNTER TO MATCH EXTENT OF DEMOLISHED O I GROOM fl 110 0 EXAM 2 LAB X RAY 102 107 108 102 RESTROOM 109A 111 3 A401 A EXAM 3 TREATMENT 9 103 109 ISOLATION 4'- 9 1/4" 4'- 9 1/4" 112 3 A401 (V (V ELECTRICAL REINSTALL EXISTING A401 PANEL SINK IN NEW COUNTER TO MATCH EXTENT OF 77 DEMOLISHED 7 104'- 4 1/2" ALIGN oUo 104'-0" ib 01 01 00 3' - 8" C M 3 INFILL C OPENING OFFICE SX 117 115 6 A852 0� DENTAL DOGS O114 113 B WINDOW JAMB ALIGN A401 ALIGN ALIGN AT TRANSITION FROM EXISTING 5 WALL TO NEW C C RELOCATED 3 3-8" 1 C CABINETRY C 1'-0" TTTTT 117 104'- 41/2" 104' - 0" 0 o C HALL M BREAK4'-2" DELIVERY 118 LO 122 A401 120 � C ALIGN C 8 RELOCATED /DRYER 2'-0" O C B ° 2'-0" ° ° 2'- 11 " 4'- 6 1/4" 3 OFFICELO M 119 A401 4 3' - 0" - ow� UTILITY FURR OUT WALL TO 121 BUMP OUT ALIGN H ADJACENT w (E) TENANT DEMISING WALL TO REMAIN. SEAL ALL PENETRATIONS AND HEAD WITH FIRE SEALANT OWNER PROVIDED ANIMAL CAGES 0 COORDINATE WITH OWNER IN FIELD HEIGHT OF TUB SILL/WALL FRAMING OWNER PROVIDED ANIMAL CAGE OWNER PROVIDED ANIMAL CAGES REVISION City of Wheat Ridge Building Division 1 LEVEL 01 SCALE: 1/4" = 1'-0" chcird, OF CpL®' ROBERT 'qQ C/o) JOHN Co � a4stn� \�SFD ARG�''� OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.C. 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 COPYRIGHT: 2020 THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN CAN ONLY BE USED FOR THIS PROJECT. NO OTHER USE OF THIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUT THE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. # DESCRIPTION DATE 1 PERMIT SET 15 SEPT 2020 2 ADDENDUM #1 13 NOV 2020 3 ASI 1 13 DEC 2020 CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Project Number: 20019 FLOOR PLAN A1 01 SHEET NOTES 1. THE DRAWINGS ARE DIAGRAMMATIC AND MAY NOT SHOW ALL DEMOLITION THAT IS REQUIRED. THE CONTRACTOR MUST VISIT THE BUILDING TO DOCUMENT ALL CONDITIONS AND DETERMINE THE EXTENT OF DEMOLITION THAT WILL BE REQUIRED TO CONSTRUCT THE PROJECT AS IT IS DOCUMENTED. 2. THE CONTRACTOR SHALL DOCUMENT AND COORDINATE THE SALVAGE OF ALL EXISTING MATERIALS, EQUIPMENT, FIXTURES, AND OTHER BUILDING ITEMS WITH THE OWNER. THE OWNER RETAINS SALVAGE RIGHTS TO ALL ITEMS REMOVED FROM THE BUILDING AS PART OF THE PROJECT. ITEMS WHICH THE OWNER DOES NOT WISH TO KEEP SHALL BECOME THE PROPERTY OF THE CONTRACTOR. 3. THE CONTRACTOR SHALL PROTECT ALL BUILDING ITEMS AND CONDITIONS TO REMAIN. IT IS THE CONTRACTORS RESPONSIBILITY TO REPAIR AND REPLACE ANY EXISTING ITEMS OR CONDITIONS THAT ARE DAMAGED DURING CONSTRUCTION ACTIVITIES. 4. THE ARCHITECT ASSUMES NO RESPONSIBILITY FOR THE DETECTION OR REMOVAL OF ANY HAZARDOUS MATERIAL INCLUDING BUT NOT LIMITED TO ASBESTOS. PARTIES RESPONSIBLE FOR DEMOLITION SHALL NOTIFY THE OWNER IMMEDIATELY OF ANY SUSPECTED HAZARDOUS MATERIALS. 5. REPLACE RELOCATED UTILITIES, FIXTURES AND ACCESSORIES IN DEMOLISHED AREAS. 6. THE CONTRACTOR SHALL REMOVE ALL EXISTING ELECTRICAL DEVICES WHEN THEY ARE AFFECTED BY EXISTING CEILINGS TO BE REMOVED. WIRING SHALL BE CAPPED AND MAINTAINED FOR THE REINSTALLATION OF SUCH DEVICES IN THE NEW CEILING CONSTRUCTION. co N O N O N LO N 0 0 v_1111 1L -iJ COQ ROBERT O C") JOHN O II � II ISI I/ /I 71 F II/ /II 146 A. .l3 ARGN�� v_1111 1L -iJ T — II SII II II DEMO CEILING TILE AND GRID n DEMO ALL CEILING TILE, GRID TO REMAIN, LINO COQ ROBERT O C") JOHN O II � II ISI I/ /I 0 L \� 146 A. .l3 ARGN�� T — II SII II II DEMO CEILING TILE AND GRID n DEMO ALL CEILING TILE, GRID TO REMAIN, LINO n COQ ROBERT O C") JOHN O II � II ISI I/ /I 0 � 146 A. .l3 ARGN�� n REVISION City of Wheat Ridge Building Division 1 LEVEL 01 -DEMO chcirdl. OF COQ ROBERT O C") JOHN O 0 � 146 A. .l3 ARGN�� REVISION City of Wheat Ridge Building Division 1 LEVEL 01 -DEMO chcirdl. OF COQ ROBERT O C") JOHN O � 146 A. .l3 ARGN�� II II h���I t _ 1 J REMOVE AND � i RELOCATE SURGICAL \ LIGHT, RE: A151 L I h li I L— — — — — — — — — - - — —— — — — — — — — — — — — — — — — — — — I � I �7I I, REVISION City of Wheat Ridge Building Division 1 LEVEL 01 -DEMO chcirdl. OF COQ ROBERT O C") JOHN O � 146 A. .l3 ARGN�� II II h���I t _ 1 SII II � i I I \ I h li I II II II I II ! II II REVISION City of Wheat Ridge Building Division 1 LEVEL 01 -DEMO chcirdl. OF COQ ROBERT O C") JOHN O � 146 A. .l3 ARGN�� OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.C. 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 COPYRIGHT: 2020 THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN CAN ONLY BE USED FOR THIS PROJECT. NO OTHER USE OF THIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUT THE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. # DESCRIPTION DATE 1 PERMIT SET 15 SEPT 2020 3 ASI 1 13 DEC 2020 CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Project Number: 20019 DEMOLITION REFLECTED CEILING PLAN AD1 51 SHEET NOTES 1. DO NOT SCALE DRAWINGS. THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS BEFORE CONSTRUCTION. IF THERE ARE ANY DISCREPANCIES, THE CONTRACTOR SHALL NOTIFY THE ARCHITECT BEFORE PROCEEDING WITH THE CONSTRUCTION. 2. ALL DIMENSIONS ON THE DRAWINGS ARE TO THE FACE OF SHEATHING. 3. REFER TO THE STRUCTURAL DRAWINGS FOR SLIP JOINTS ON ALL INTERIOR NON -LOAD BEARING WALLS, UNLESS NOTED OTHERWISE. 4. THE CONTRACTOR SHALL COORDINATE AND IMPLEMENT ALL SAFETY MEASURES REQUESTED AND/OR REQUIRED BY THE LOCAL FIRE MARSHAL, HEALTH DEPARTMENT, BUILDING OFFICIALS, AND ALL OTHER AUTHORITIES HAVING JURISDICTION. 5. THE CONTRACTOR SHALL MAINTAIN SECURITY OF THE CONSTRUCTION SITE THROUGHOUT THE ENTIRE CONSTRUCTION PROCESS. 6.THE CONTRACTOR SHALL SLOPEALL FLOORS WITHIN ANVO FOOT RADIUS OFA DRAIN ATA MINIMUM SLOPE OF ONE EIGHTH OFAN INCH PER FOOTTO DRAIN, UNLESS NOTED OTHERWISE. T THE CONTRACTOR SHALL COORDINATE ALL ITEMS PROVIDED OR INSTALLED BYTHE OWNER OR THE OWNER'S SUBCONTRACTORS DURING CONSTRUCTION. THESE ITEMS INCLUDE, BUTARE NOT LIMITED TO, THE INSTALLATION OF AUDIOAND VISUAL EQUIPMENT, EQUIPMENTAND WIRING RELATED TOTHETELEPHONE, COMPUTER, AND INTERNET SYSTEMS, AND THE INSTALLATION OF THE FOOD SERVICE EQUIPMENT. 8. THE CONTRACTOR SHALL PROVIDE BLOCKING AT ALL WALL HUNG ACCESSORIES, HARDWARE, AND WALL - HUNG CABINETS AS REQUIRED. 9.THE CONTRACTOR SHALL PROVIDE A TRANSITION STRIP ATALL DISSIMILAR FLOOR MATERIALS. 10. THE CONTRACTOR SHALL REVIEW THE CIVIL, STRUCTURAL, MECHANICAL, ELECTRICAL, AND ALL OTHER RELATED DRAWINGS AND DOCUMENTS FOR ANYADDITIONAL BUILDING REQUIREMENTS. 11. TYPE I AND II CONSTRUCTION: WOOD BLOCKING IN EXTERIOR WALLS AND ROOF ASSEMBLIES SHALL BE FIRE RESISTANT TREATED (FRT) WOOD. 12. MILLWORKER TO FIELD VERIFY EXISTING COUNTERS TO BE DEMOLISHED AND REPLACED. COORDINATE WITH ARCHITECT ON NEW COUNTER DIMENSIONS EXISTING BUILDINGS 1. THE CONTRACTOR SHALL PATCH AND REPAIR ALL EXISTING FIRE -RATED BUILDING ELEMENTS, ADD FIRE - SMOKE DAMPERS WHERE NEW DUCTS CROSS, AND ADD FIRE STOPS ATALL PENETRATIONS TO MAINTAIN ALL DESIGNATED FIRE -RATINGS. 2. THE CONTRACTOR SHALL PATCH, REPAIR, AND PAINT ALL EXISTING WALLS TO MATCH ADJACENT SURFACES AS REQUIRED. 3. THE CONTRACTOR SHALL PROVIDE CONTROL JOINTS WHERE NEW GYPSUM BOARD IS PLACED IN ALIGNMENT WITH EXISTING WALLS. ALIGNMENT IS TYPICAL ATALL LOCATIONS UNLESS NOTED OTHERWISE. 4.THE CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING, LEVELINGAND/OR GRINDING SMOOTH ALL EXISTING FLOORS FOR THE INSTALLATION OF NEW FLOORING MATERIALS. 5.THE CONTRACTOR SHALL PATCH AND REPAINTALL EXISTING WALLS AT CONDITIONS WHERE EXISTING FIXTURES ARE TO BE REMOVED. SEE MECHANICAL, PLUMBING, ELECTRICAL, AND ARCHITECTURAL DEMOLITION DRAWINGS FOR LOCATIONS. 6. THE CONTRACTOR SHALL VERIFY ROUGH -IN DIMENSIONS WITH THE MANUFACTURER FOR ALL NEW, EXISTING, AND REUSED EQUIPMENT. T THE CONTRACTOR SHALL PATCH, REPAIR, AND PAINT ALL EXISTING CEILINGS TO MATCH ADJACENT SURFACES AS REQUIRED. 8. THE CONTRACTOR SHALL COORDINATE ALL FLOOR CORE DRILLING WITH EXISTING STRUCTURE. 9. EXISTING DOORS THATARETO REMAIN ARE UNNUMBERED tl N Lo N 0 N O N C2 M REINSTALL SINK IN NEW COUNTER M 2 RECD EXAM / II I I II \ EX 2 100 101 102 T-11" _2'-4" 3'-61/2" 1'-8" z 104A EXAM 4 a 104 T — SINK, UPPER AND LOWER CABINETS RELOCATED FROM ISOLATION 112. NEW COUNTER. A401 6 I <B> I IREST OO7�' I 106 L I � 4'-0" I J 8'-6" / 2'_0" It (J06 \---------__ OB a l01 O � ALIGN OFFICE 117 LAB ,07 ,02 X RAY 108 A401 TREATMENT 9 109 4'-91/4" 4'-91/4 3 A401�� v Z ry i) REINSTALL EXISTING SINK IN NEW COUNTER ALIGN 4' 0" INFILL OPENING SX 115 6 A8! O O WINDOW JAMB ALIGN ATTRANSITION D FROM EXISTING WALL TO NEW C O 117 o HALL 118 ALIGN WALL WITH 105A 119 O CENTER OF MULLION E EXAM 5 OFFICE IIII 105 B <C'> B 119 a FURR OUT WALL TO — M ALIGN WITH ADJACENT BUMP OUT r� A401 ALIGN 5 RELOCATED - CABINETRY 4'-0" 0 GROOM 00'-6" ^ 110 X104'-0" r 0' RESTROOM 11 OISOLATION C 112 N 2 A401 7 104'-4 04' - ELECTRICAL PANEL O DENTAL DOGS 114 113 ALIGN ho ill T—T—T—T—T— IT104'-4 1/2" 104'- 0" i '-0.. BREAK C 4,-2" O DELIVERY I 120 122 A401 120 I J ALIGN C 8 RELOCATED WASHER/DRYER C ^_ 4'-61/4" �� 7 D 1121TY I J )RAGE (E) TENANT DEMISING WALL TO REMAIN. SEAL ALL „� PENETRATIONS AND HEAD WITH FIRE SEALANT OWNER PROVIDED ANIMAL CAGES COORDINATE MOUNTING H EIGHT WITH OWNER IN FIELD OWNER PROVIDED ANIMAL CAGE OWNER PROVIDED ANIMAL CAGES 1 City of Wheat Ridge Building Division 1 LEVEL 013 SCALE: 1/4" = 1'-0" chord,111111111 Of C010 ROBERT JOHN * OOj�RSLLIND �� 1 1148 OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.0 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 �Z• WA0Eel mI/DL➢A: THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN CAN ONLY BE USED FOR THISPROJECT. NO OTHER USE OFTHIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUTTHE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Project Number: 20019 FLOOR PLAN A101 ALIGN ' ALIGN T 1103A ; EXAM 3 1 C I 103 B I T-- z � I 1 a I GROMMET I L — i 1038 ALIGN\• ALIGN 1008 �•�•�•�• •�• •� C — — J 1048 R, r� z 104A EXAM 4 a 104 T — SINK, UPPER AND LOWER CABINETS RELOCATED FROM ISOLATION 112. NEW COUNTER. A401 6 I <B> I IREST OO7�' I 106 L I � 4'-0" I J 8'-6" / 2'_0" It (J06 \---------__ OB a l01 O � ALIGN OFFICE 117 LAB ,07 ,02 X RAY 108 A401 TREATMENT 9 109 4'-91/4" 4'-91/4 3 A401�� v Z ry i) REINSTALL EXISTING SINK IN NEW COUNTER ALIGN 4' 0" INFILL OPENING SX 115 6 A8! O O WINDOW JAMB ALIGN ATTRANSITION D FROM EXISTING WALL TO NEW C O 117 o HALL 118 ALIGN WALL WITH 105A 119 O CENTER OF MULLION E EXAM 5 OFFICE IIII 105 B <C'> B 119 a FURR OUT WALL TO — M ALIGN WITH ADJACENT BUMP OUT r� A401 ALIGN 5 RELOCATED - CABINETRY 4'-0" 0 GROOM 00'-6" ^ 110 X104'-0" r 0' RESTROOM 11 OISOLATION C 112 N 2 A401 7 104'-4 04' - ELECTRICAL PANEL O DENTAL DOGS 114 113 ALIGN ho ill T—T—T—T—T— IT104'-4 1/2" 104'- 0" i '-0.. BREAK C 4,-2" O DELIVERY I 120 122 A401 120 I J ALIGN C 8 RELOCATED WASHER/DRYER C ^_ 4'-61/4" �� 7 D 1121TY I J )RAGE (E) TENANT DEMISING WALL TO REMAIN. SEAL ALL „� PENETRATIONS AND HEAD WITH FIRE SEALANT OWNER PROVIDED ANIMAL CAGES COORDINATE MOUNTING H EIGHT WITH OWNER IN FIELD OWNER PROVIDED ANIMAL CAGE OWNER PROVIDED ANIMAL CAGES 1 City of Wheat Ridge Building Division 1 LEVEL 013 SCALE: 1/4" = 1'-0" chord,111111111 Of C010 ROBERT JOHN * OOj�RSLLIND �� 1 1148 OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.0 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 �Z• WA0Eel mI/DL➢A: THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN CAN ONLY BE USED FOR THISPROJECT. NO OTHER USE OFTHIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUTTHE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Project Number: 20019 FLOOR PLAN A101 ., LO N O N O N LO N SHEET NOTES 1. REFER TO MECHANICAL AND ELECTRICAL DRAWINGS FOR FIXTURES AND EQUIPMENT NOT SHOWN HERE. 2. REFER TO MECHANICAL AND ELECTRICAL DRAWINGS FOR MOUNTING OF ITEMS WHERE NO CEILING IS REQUIRED OR INDICATED. 3. LIGHTS, DIFFUSERS, EXIT SIGNS, SMOKE DETECTORS, FIRE ALARM SPEAKER/STROBES, AND ALL OTHER DEVICES SHALL BE ALIGNED WITH EACH OTHER AND CENTERED IN THE CEILING TILES IN WHICH THEY OCCUR UNLESS NOTED OTHERWISE. 4. PATCH/REPAIR CEILING GRID AS REQUIRED. Al 71 Al RECE TION - ------ ---- -- -- -- -- 100 Al GYP BD CEILING - -- - -- -- -- - - - - - -- SCOPE TO BE PRICED AS AN ADD ALTERNATE Al _ 1'-6" A3 109'- 11 1/4" ALIGN "rC - _- -__ _- -=:-•,-'�"'tet 131 Ld 131 w l PT -2 RCP LEGEND DESCRIPTION A2 131 EXAM 1 101 Al S1 SUPPLY RETURN EXHAUST FAN Al RECESSED RECESSED RECESSED PENDANT 109'- 11 1/4" ALIGN "rC - _- -__ _- -=:-•,-'�"'tet 131 Ld 131 w l PT -2 RCP LEGEND DESCRIPTION A2 131 P1 P2 S1 SUPPLY RETURN EXHAUST FAN Al RECESSED RECESSED RECESSED PENDANT SURGICAL WALL DIFFUSER DIFFUSER FIXTURE FIXTURE CAN LIGHT LIGHT SCONCE Al EXAM 4 104 Al 1'-6" S_1 0 , _ = w 106Lu B1 _ :.. .. DESCRIPTION DATE 1 EXAM 2 102 Al 2 ADDENDUM #1 13 NOV 2020 3 ASI 1 13 DEC 2020 Al EXAM 4 104 Al 1'-6" S_1 0 , _ = w 106Lu B1 _ :.. .. Al Al A3 Al Al 1 Al OFFICE 117 OFFICE 119 HALL 118 A3 Al LAB 107 Al TREATMENT 109 Al A3 A2 Al A2 SX 115 P2 A3 A2 bi=tel! n GROOM 110 Al Al Al Al RESTROOM 111 DENTAL 114 A3 A3 piA3 DOGS 113 0 A3 A3 Al Al DELIVERY 120 Al ® Al BREAK UTILITY 121 REVISION City of Wheat Ridge Building Division 1 LEVEL 01 chcirdl. 0� C040 ROBERT 90 JOHN O A. J \�SFD ARGN\/! OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.C. 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 COPYRIGHT: 2020 THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN CAN ONLY BE USED FOR THIS PROJECT. NO OTHER USE OF THIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUT THE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. # DESCRIPTION DATE 1 PERMIT SET 15 SEPT 2020 2 ADDENDUM #1 13 NOV 2020 3 ASI 1 13 DEC 2020 1.Al > U 505 }EXAM Al Al A3 Al Al 1 Al OFFICE 117 OFFICE 119 HALL 118 A3 Al LAB 107 Al TREATMENT 109 Al A3 A2 Al A2 SX 115 P2 A3 A2 bi=tel! n GROOM 110 Al Al Al Al RESTROOM 111 DENTAL 114 A3 A3 piA3 DOGS 113 0 A3 A3 Al Al DELIVERY 120 Al ® Al BREAK UTILITY 121 REVISION City of Wheat Ridge Building Division 1 LEVEL 01 chcirdl. 0� C040 ROBERT 90 JOHN O A. J \�SFD ARGN\/! OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.C. 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 COPYRIGHT: 2020 THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN CAN ONLY BE USED FOR THIS PROJECT. NO OTHER USE OF THIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUT THE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. # DESCRIPTION DATE 1 PERMIT SET 15 SEPT 2020 2 ADDENDUM #1 13 NOV 2020 3 ASI 1 13 DEC 2020 CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Project Number: 20019 REFLECTED CEILING PLAN A1 51 ., N O N O N N 8 UTILITY ELEVATION SCALE: 1/2" = V-0" RELOCATED WASHER/DRYER 4 BREAK ROOM ELEVATION SCALE: 1/2" = V-0" \NEL OPEN BEYOND 7 MILLWORK ELEVATION SCALE: 1/2" = V-0" TOE KICK NOT INTEGRAL TO DOOR, WHEELCHAIR SIDE APPROACH A 3 TREATMENT MILLWORK ELEVATION SCALE: 1/2" = V-0" ACCESSORY SCHEDULE NUMBER ACCESSORY TYPE MANUFACTURER/ MODEL COMMENTS 1 PAPER TOWEL DISPENSER BOBRICK / B-3944 1 2 GRAB BARS - 42", 36", 18" BOBRICK / B6806 SERIES PROVIDE BLOCKING IN WALL 3 TOILET PAPER DISPENSER BOBRICK / B2888 13 DEC 2020 4 SOAP DISPENSER BOBRICK / B4112 5 FRAMED MIRROR BOBRICK / B-290 2436 6 UNDER LAVATORY GUARD TRUEBRO LAV GUARD 2 7 UTILITY SHELF BOBRICK/ B-239 PL -1 COUNTER CHAMFER CABINET TRIM, PROVIDE END PANEL TO MATCH 6 EXAM MILLWORK ELEVATION SCALE: 1/2" = V-0" V REINSTALL (E) SINK AND FAUCET J 9 ISLAND MILLWORK ELEVATION SCALE: 1/2" = V-0" TOE KICK NOT INTEGRAL TO DOOR, WHEELCHAIR SIDE APPROACH WITH CENTER OF SINK 2 RESTROOM ELEVATION SCALE: 1/2" = V-0" RELOCATED CABINETRY, NOTE: ALL MILLWORK IN COORDINATE LAYOUT ELEVATION IS EXISTING WITH OWNER IN FIELD TO BE RELOCATED FILLER PANEL TO MATCH CABINETS 5 S ELEVATION SCALE: 1/2" = V-0" V NEW PL -1 COUNTER AND BACKSPLASH 1 RESTROOM ENLARGED PLAN SCALE: 1/2" = V-0" K r, v 1�1vN City of Wheat Ridge Building Division chcird, C040 11-z ROBERT y� co JOHN O ASFD OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.C. 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 COPYRIGHT: 2020 THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN CAN ONLY BE USED FOR THIS PROJECT. NO OTHER USE OF THIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUT THE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. # DESCRIPTION DATE 1 PERMIT SET 15 SEPT 2020 2 ADDENDUM #1 13 NOV 2020 3 ASI 1 13 DEC 2020 000 0 o o FILLER PANEL TO MATCH CABINETS 5 S ELEVATION SCALE: 1/2" = V-0" V NEW PL -1 COUNTER AND BACKSPLASH 1 RESTROOM ENLARGED PLAN SCALE: 1/2" = V-0" K r, v 1�1vN City of Wheat Ridge Building Division chcird, C040 11-z ROBERT y� co JOHN O ASFD OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.C. 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 COPYRIGHT: 2020 THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN CAN ONLY BE USED FOR THIS PROJECT. NO OTHER USE OF THIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUT THE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. # DESCRIPTION DATE 1 PERMIT SET 15 SEPT 2020 2 ADDENDUM #1 13 NOV 2020 3 ASI 1 13 DEC 2020 CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Project Number: 20019 ENLARGED PLANS AND INTERIOR ELEVATIONS A401 FACE OF KNEE WALL 4RECEPTION DESK INTERIOR ELEVATION SCALE: 1/2" = V-0" LEASH HOOK (4) 3 RECEPTION DESK FRONT ELEVATION1 SCALE: 1/2" = V-0" 2 RECEPTION DESK BACK ELEVATION SCALE: 1/2" = 1'-0" SS -1 LEASH HOOK RELOCATED DOUBLE PL -2 ACTING HINGES ON 1 3/4" THICK DOOR PANEL. PL -2 ON ALL WB -1 SIDES. 3'-51/2" VIF 5 RECEPTION DESK SIDE ELEVATION SCALE: 1/2" = 1'-0" A402 RELOCATED DOUBLE ACTING H INGES 5 B" F C� rn ih BLOCKING IN WALL FOR HINGES — —J GROMMET 1'- P' HSS COUNTER o SUPPORT A402 3 M 4 A402 2 GROMMET BLOCKING IN WALL FOR M HINGES I � I L/ M 50PP RELOCATED DOUBLE A402 ACTING HINGES City of 1 RECEPTION DESK ENLARGED PLAN Wheat Ridge SCALE: 1/2" = 1'-0" Building Division chord,1111111 �F�� h� ROBERT 0 JOHN 1148 SED ARG OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.0 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 �Z0WA0Eel :I/DL➢A: THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN CAN ON LY BE USED FOR THISPROJECT. NO OTHER USE OFTHIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUTTHE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Project Number: 20019 RECEPTION DESK PLAN AND ELEVATIONS A402 W N O N O N LO N DOOR SCHEDULE DOOR NUMBER TYPE DOOR FRAME HARDWARE SET NOTES WIDTH HEIGHT MATERIAL FINISH MATERIAL FINISH 102 A 3' - 0" 6' - 8" WD - HM - 03 MATCH EXISITING EXTERIOR DOOR LEAF AND FRAME FINISHES AND HARDWARE 104B A 3' - 0" 6' - 8" WD - HM - 03 MATCH EXISTING DOOR LEAF AND FRAME FINISHES 105A A 3' - 0" 6' - 8" WD - HM - 03 MATCH EXISTING DOOR LEAF AND FRAME FINISHES 105B A 3' - 0" 6' - 8" WD - HM - 03 RELOCATED, DECORTIVE FILM DOOR AND HARDWARE 106 A 3' - 0" 6' - 8" WD - HM - 01 MATCH EXISTING DOOR LEAF AND FRAME FINISHES 117 A 3' - 0" 6' - 8" WD - HM - 02 MATCH EXISTING DOOR LEAF AND FRAME FINISHES 118 B 3' - 0" 6' - 8" WD - HM - 03 MATCH EXISTING DOOR LEAF AND FRAME FINISHES 119 A 3' - 0" 6' - 8" WD - HM - 02 MATCH EXISTING DOOR LEAF AND FRAME FINISHES DOOR TYPES 7'-0" DATE RE: SCHEDULE EQ 3 RE: SCHEDULE RE: SCHEDULE RE: SCHEDULE v EQ MATCH (E) 'IFIL 'IFIL INTERIOR WINDOW SILICONE 2" 2" CAULK AT 0 GLASS \ J \ J \ J J 0 w i LdU U) U) U) ,' bi 6i , 6i ' SLIDE --s- 6i A B C D E HOLLOW METAL FRAME RELOCATED HOLLOW HOLLOW METAL NOT USED WOOD FRAME WITH WITH HOLLOW METAL METAL FRAME WITH FRAME WITH HOLLOW SOLID CORE WOOD OR SOLID CORE WOOD HOLLOW METAL OR METAL DOOR POCKET DOOR DOOR SOLID CORE WOOD DOOR WITH WINDOW HARDWARE SETS DOOR NOTES SET 01: RESTROOM 1. ALL DOORS TO PROVIDE 32" MIN CLEAR OPENING WHEN OPENED TO 90 DEGREE POSITION U.N.O. (1) FACULTY RESTROOM LOCK (WITH INDICATOR CYLINDER), (SCHLAGE AL85PD-JUP) 2. SEE SCHEDULE FOR FINISH INFORMATION. (3) BALL BEARING BUTT HINGES (MCKINEY, MPB79, 4 1/2" x 4 1/2", 26D) 3. SWINGING EXTERIOR DOORS: HM = 16 GA. (1) WALL STOP (ROCKWO0D, 403, 626) 4. EXTERIOR DOOR LOCK TO HAVE 1" BOLT PROTECTION (IF APPLICABLE) ONE MOTION, LEVER (1) CLOSER (LCN, 4040 XP) HANDLE, DEADBOLT FUNCTION REQUIRED (1) KICK DOWN HOLD OPEN 5. SOLID STEEL CYLINDER GUARD/APPROVED ESCUTCHEON REQUIRED. (2) 8" X 32" STAINLESS STEEL KICK PLATE 6. NON -REMOVABLE EXTERIOR HINGE PINS (NRP) REQUIRED ON OUTSWINGING DOORS. (3) SILENCERS (TRIMCO, 1229A) 7. ALL DOORS SHALL BE PROVIDED WITH WALL OR FLOOR STOPS. 8. ALL DOORS THAT DO NOT HAVE SMOKE SEALS SHALL BE PROVIDED WITH SILENCERS. SET 02: OFFICE 9. COORDINATE DOORS WITH UNDERCUTS WITH THE MECHANICAL DRAWINGS. (1) OFFICE LOCK LEVERSET (SCHLAGE, ND50PD, ATHENS LEVER HANDLE, 626) (3) BALL BEARING BUTT HINGESH( AGER, BB1279, 41/2" x 4 1/2", 626) HARDWARE NOTES (1) FLOOR STOP (IVES, FS13, US26D) (1) SURFACE CLOSER (LCN 4040XP) (3) SILENCERS (TRIMCO, 1229A) 1. THE FORCE FOR PUSHING OR PULLING OPEN INTERIOR SWINGING EGRESS DOORS, OTHER SET 03: PASSAGE SET THAN FIRE DOORS, SHALL NOT EXCEED 5 POUNDS (22 N). (1) PASSAGE LEVERSET (SCHLAGE ND10S, ATHENS LEVEL HANDLE, 626) 2. DOOR HANDLES, PULL, LATCHES, LOCKS AND OTHER OPERATING DEVICES ON DOORS (1) SURFACE CLOSER WITH OVERHEAD STOP (GLYNN-JOHNSON 100 SERIES) REQUIRED TO BE ACCESSIBLE SHALL NOT REQUIRE TIGHT GRASPING, TIGHT PINCHING OR (3) BALL BEARING BUTT HINGES (HAGER BB1279, 4 1/2 X 4 1/2,626) TWISTING OF THE WRIST TO OPERATE. (1) WALL STOP (ROCKWOOD, 403, 626) 3. THRESHOLDS AT DOORWAYS SHALL NOT EXCEED 1/2 INCH IN HEIGHT ABOVE THE FINISHED (3) SILENCERS (IVES, SR64) FLOOR. RAISED THRESHOLDS AND FLOOR LEVEL CHANGES GREATER THAN 1/4 INCH AT DOORWAYS SHALL BE BEVELED WITH A SLOPE NOT GREATER THAN ONE UNIT VERTICAL IN TWO UNITS HORIZONTAL (50 -PERCENT SLOPE). GC TO VERIFY HARDWARE FUNCTION AND KEYING REQUIREMENTS WITH OWNER PRIOR TO ORDERING 4'-6" Of EQ EQ CLEAR SILICONE CAULK AT JAMB AND BUT JOINT MATCH (E) INTERIOR WINDOW MULLION TYPE AND GLASS 0 E WINDOW TYPE E SCALE: 1/2" = 1'-0" M SHEET NOTES 1. REFER TO THE ARCHITECTURAL FLOOR PLANS FOR PARTITION TYPE TAGS 2. SEAL ALL PENETRATIONS & OPENINGS (INCLUDING THE PERIMETER) IN ALL SOUND RATED WALLS. 3. THE PARTITION TYPES INDICATE THE BASIC WALL CONSTRUCTION ONLY. REFER TO ALL THE CONSTRUCTION DOCUMENTS FOR OTHER REQUIREMENTS INCLUDING: MECHANICAL, ELECTRICAL, PLUMBING, BLOCKING & BACKING, WALL BASE, WALL FINISH, AND RECESSED & SURFACE MOUNTED EQUIPMENT. 4. INSTALL CEMENTITIOUS BACKER UNITS BEHIND ALL TILE IN LIEU OF GYPSUM SHEATHING (TYPICAL). SEE THE ROOM FINISH SCHEDULE AND INTERIOR ELEVATIONS FOR LOCATIONS OF TILE. A Of 7'-0" DATE 1 EQ 15 SEPT 2020 2 EQ MATCH (E) CLEAR --J INTERIOR WINDOW SILICONE INTERIOR WINDOW SILICONE MULLION TYPE CAULKAT AND GLASS JAMB AND BUT JOINT CWINDOW TYPE C, NOT USED B WINDOW TYPE 6 SCALE: 1/2" = 1'-0" SCALE: 1/2" = 1'-0" 20 GA. 2 1/2" METAL STUD KICKERS BRACED BACK TO STRUCTURE EVERY 4'-0" UNINTERRUPTED WALL LENGTH _ BATT INSULATION ABOVE CEILING EXISTING CEILING BATT INSULATION WHERE APPLICABLE 1/4" COMPRESSIBLE NEOPRENE SEALER 5/8" GYPSUM WALL BOARD (PROVIDE MOISTURE RESISTANT GWB OR CEMENT BOARD WHERE APPLICABLE) 5/8" 20 GA METAL STUDS 116" O.C. FALL BASE AS CHEDULED CPARTITION WALL - NON -RATED (STC: N/A) SCALE: NOT TO SCALE EALANT LIP TRACK- 1 1/2" DEFLECTION LLOWANCE 8" GYPSUM WALL BOARD 'ROVIDE MOISTURE ESISTANT GWB OR CEMENT BOARD WHERE APPLICABLE) CEILING BATT INSULATION WHERE APPLICABLE 61 6" FRAMING 5/8" 20 GA METAL TUDS @ 16" O.C. FALL BASE AS CHEDULED B PARTITION WALL - NON -RATED (STC: N/A) SCALE: NOT TO SCALE O�ALANT 8" GYPSUM WALL BOARD 'ROVIDE MOISTURE ESISTANT GWB OR CEMENT JARD WHERE APPLICABLE) 4TT INSULATION WHERE 'PLICABLE EILING 5/8" 20 GA METAL TUDS @ 16" O.C. NCE OF WALL TO BE FURRED VHERE APPLICABLE) 'ALL BASE AS DHEDULED A FURRED WALL - NON -RATED (STC: N/A) SCALE: NOT TO SCALE 0 M 10'-5" 3-6" 3-5" 3-6" A WINDOW TYPE A SCALE: 1/2" = 1'-0" REVISION City of Wheat Ridge Building Division chcird% /OF COL®\ ROBERT 9� co JOHN O 1 OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.C. 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 COPYRIGHT: 2020 THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN CAN ONLY BE USED FOR THIS PROJECT. NO OTHER USE OF THIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUT THE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. # DESCRIPTION DATE 1 PERMIT SET 15 SEPT 2020 2 M MATCH (E) CLEAR --J INTERIOR WINDOW SILICONE MULLION TYPE AND CAULK AT 0 GLASS JAMB AND BUT JOINT M A WINDOW TYPE A SCALE: 1/2" = 1'-0" REVISION City of Wheat Ridge Building Division chcird% /OF COL®\ ROBERT 9� co JOHN O 1 OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.C. 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 COPYRIGHT: 2020 THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN CAN ONLY BE USED FOR THIS PROJECT. NO OTHER USE OF THIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUT THE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. # DESCRIPTION DATE 1 PERMIT SET 15 SEPT 2020 2 ADDENDUM #1 13 NOV 2020 3 ASI 1 13 DEC 2020 CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Project Number: 20019 DOOR, WINDOW,PARTITION TYPES AND DETAILS A501 SHEET NOTES 1. THE CONTRACTOR SHALL REFER TO FINISH PLANS AND SCHEDULE FOR LOCATION & LAYOUT OF MATERIALS. 2. ALL NEW WALLS ARE TO BE PAINTED -COLOR AND SHEEN TBD OR AS INDICATED ON THE ROOM FINISH SCHEDULE OR DRAWINGS. 3. NEW BULKHEADS, SOFFITS, & GYPSUM BOARD CEILINGS ARE TO BE PAINTED - COLOR AND SHEEN TBD OR AS INDICATED ON THE ROOM FINISH SCHEDULE OR DRAWINGS. 4. EXISTING WALLS ARE TO BE PAINTED - COLOR AND SHEEN TBD OR AS INDICATED ON THE ROOM FINISH SCHEDULE AND DRAWINGS. 5. INFILL AREAS (WALLS AND CEILINGS) SHALL BE TEXTURED AND PAINTED TO MATCH ADJACENT SURFACES. 6. REFER TO THE DRAWINGS FOR CONTROL JOINT LOCATIONS. 7. TRANSITION STRIPS AND THRESHOLDS SHALL BE LOCATED ATTHE CENTERLINE OF DOORS IN THE CLOSED POSITION, UNLESS NOTED OTHERWISE. 8. FLOORING TRANSITIONS SHALL ALIGN WITH FINISH BASE (EXCEPT AT DOORS), UNLESS NOTED OTHERWISE. THE CONTRACTOR SHALL PROVIDE A SUBMITTAL OF EACH TRANSITION TYPE FOR APPROVAL BYTHE ARCHITECT PRIOR TO ORDERING. REFER TO TRANSITION DETAILS. 9. TILE FLOORING UNDERLAYMENT SHALL BE INSTALLED BYTHE CONTRACTOR AS REQUIRED. 10. MOISTURE BARRIERS SHALL BE INSTALLED BYTHE CONTRACTOR AS REQUIRED UNDER ALL MOISTURE -SENSITIVE FLOORING IF MOISTURE READINGS ARE HIGHER THAN THE LEVELS RECOMMENDED BYTHE MANUFACTURER THE ATTIME OF INSTALLATION. 11. WHEN HARD FLOORING IS INSTALLED OVER CONSTRUCTION JOINTS THE CONTRACTOR SHALL PROVIDE A SOFT JOINT WHERE THE FLOORING IS SEAMED. 12. DOOR FRAMES SHALL BE PAINTED UNLESS NOTED OTHERWISE -COLOR AND SHEEN TBD OR AS NOTED IN DRAWINGS 13. NEW INTERIOR DOORS SHALL MATCH EXISTING COLOR AND TYPE, UNLESS NOTED OTHERWISE. 14. METAL TRIM KITS & DOOR LOUVERS AT INTERIOR DOORS SHALL BE PAINTED TO MATCH DOOR FRAME (PAINT GRILLES PRIOR TO INSTALLATION). 15. PAINTABLE CAULKING/SEALANTS SHALL BE USED AS REQUIRED ATALL INTERIOR WALLS TO BE PAINTED. 16. CEILING COMPONENTS IN OPEN AREAS SHALL BE PAINTED UNLESS NOTED OTHERWISE - COLOR AND SHEET TBD OR AS NOTED IN DRAWINGS 17. CONDUITS & BRACKETS SHALL BE PAINTED TO MATCH ADJACENT SURFACE MATERIAL UNLESS NOTED OTHERWISE 18. NEW COUNTER TOPS TO OVERHANG BASE CABINETS BY 1", TYP. a Lo N 0 N O N C2 M RECEPTION 100 /LVT-1) N FL EXAM 1 101 EXAM 2 102 EXAM 3 103 FL a TS TS EXAM 4 104 �\ 1V-- -p T PT -2 o � - 1V -1 \—/ WT -1 RESTROOM 106 N FL �TS OFFICE 117 �\ FL (LVi-1) FL TS TS — _L LAB 107 PROVIDE FULL HEIGHT WALL TILE IN DOG WASH AREAAND ON ALL FACES OF PARTIAL HEIGHT WALL. X RAY 08 ®' GROOM TREATMENT ISOLA9 09 112 T o o A SX D NTAL DOGS 115 114 113 EP -1 I I EP -1 — T—T—T —T —T — HALL BREAK DELIVERY 118 4 TS 122 TS 120 TS TS EP -1 4Vi-1) EP -1 EXAM 5 TS OFFICE 105 119 q' _ __L] I 1VT-1) (LVED FRP-1 o_ UTILITY 121 STORE GE O ��\ O w PT -2 PT -2 � PT -2 EP -1 City of Wheat Ridge Building Division J) 1 LEVEL 01 FINISH PLAN SCALE: 1/4" = V-0" chord,111111 F coco� a AT ROBERT O (0 JOHN * ORSLUND_ !'jC ?24 OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.C. 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 �Z� WA0Eel mIWL➢A: THIS DOCUMENTANDTHE DESIGNS INCORPORATED HEREIN CAN ONLYBE USED FOR THISPROJECT. NO OTHER USE OFTHIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUTTHE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. 1 CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Project Number: 20019 FINISH PLAN A801 W N O N O N LO N FLOORING EP -1 EPDXY FLOORING NUMBER MATERIAL EPDXY BASE MANUFACTURER ARMSTRONG NOTES STYLE -COLOR NATURAL CREATIONS - GRIST MILL BUTTERED TP065 SOUTH NOTE MATCH EXISTING EPDXY FLOORING, PROVIDE INTEGRAL BASE LVT-1 VINYL TILE NUMBER MATERIAL VINYL TILE BASE MANUFACTURER ARMSTRONG NOTES STYLE -COLOR NATURAL CREATIONS - GRIST MILL BUTTERED TP065 SOUTH SIZE 9" X 48" - NOTE TARKETT SSR -63-B TRANSITION STRIP AT EP -1 WALL FINISH 0 FRP-1 FIBERGLASS REINFORCED PLASTIC NUMBER MATERIAL FIBERGLASS REINFORCED PLASTIC BASE MANUFACTURER MARLITE NOTES STYLE -COLOR SMOOTH SURFACE - S 100 G WHITE SOUTH NOTE PROVIDE SANI-SEAL TRIM TO MATCH CEILING ACT -1 ACOUSTICAL CEILING TILE NUMBER MATERIAL ACOUSTICAL CEILING TILE BASE MANUFACTURER ARMSTRONG NOTES STYLE -COLOR KITCHEN ZONE SOUTH NOTE ACT -1 TO BE USED THROUGHOUT SPACE, UNO. PAINT PT -1 PAINT - INTERIOR MATERIAL MANUFACTURER STYLE -COLOR SHEEN NOTE PRO INDUSTRIAL ACRYLIC SHERWIN WILLIAMS MATCH EXISTING PAINT IN COLOR AND SHEEN. PAINT ALL NEW WALLS AND MODIFIED EXISTING WALLS. UNO. PT -2 PAINT - INTERIOR NUMBER MATERIAL PRO INDUSTRIAL ACRYLIC BASE MANUFACTURER SHERWIN WILLIAMS NOTES STYLE -COLOR SW 7609 GEORGIAN REVIVAL BLUE SOUTH SHEEN SEMI -GLOSS - NOTE PAINT TEST PATCH TO CONFIRM FINAL COLOR SELECTION WITH OWNER. DECKING 2x JOISTS PER PLAN, - ATTACH W/ FACE MOUNTED HANGERS, TYP SIMPSON BCS POST CAP SIMPSON ABA POST BASE WOOD BEAM PER PLAN PT4x4 POST PER PLAN BASE WBA WALL BASE NUMBER MATERIAL RESILIANT VINYL BASE MANUFACTURER JOHNSONITE NOTES STYLE -COLOR 63 BURNT UMBER SOUTH SIZE 4" -.080 GAUGE - NOTE APPLY TO ALL WALLS WITHOUT INTEGRAL EPDXY BASE OR TILE MILLWORK PLA PLASTIC LAMINATE MATERIAL MANUFACTURER STYLE -COLOR NOTE PLASTIC LAMINATE NEVAMAR VISABLE VAVA - VA2001 T ALL EXAM ROOM MILLWORK COUNTERS, LAB COUNTERS, SX, UTILITY AND BREAKROOM COUNTER PL -2 PLASTIC LAMINATE NUMBER MATERIAL PLASTIC LAMINATE BASE MANUFACTURER HANEX NOTES STYLE -COLOR BL -208 - ULMUS SOUTH NOTE MATCH EXISTING CABINET LAMINATE SS -1 SOLID SURFACE NUMBER MATERIAL SOLID SURFACE BASE MANUFACTURER HANEX NOTES STYLE -COLOR BL -208 - ULMUS SOUTH NOTE - CONCRETE PIER - TAPER TOP FOR DRAINAGE AWAY FROM POST FIN GRADE (4)—#5 VERT #3 TIES @ 12" O.C. MAX 4 DECK POST FOUNDATION SCALE: 6" = 1'-0" ROOM FINISH SCHEDULE NUMBER NAME FLOOR BASE WALL FINISH CEILING NOTES NORTH EAST SOUTH WEST 100 RECEPTION LVT-1 WB -1 PT -1 PT-1/PT-2 PT -1 PT -1 ACT -1, PT -2 3 101 EXAM 1 - - - - - PT -2 ACT -1 GC TO PROVIDE ADD ALT FOR NEW LVT-1 102 EXAM 2 - - - PT -2 - - ACT -1 GC TO PROVIDE ADD ALT FOR NEW LVT-1 103 EXAM 3 - - - PT -2 - - ACT -1 GC TO PROVIDE ADD ALT FOR NEW LVT-1 104 EXAM 4 - WB -1 - - PT -2 - ACT -1 105 EXAM 5 LVT-1 WB -1 PT -1 PT -1 2 PT -2 PT -1 ACT -1 2 106 RESTROOM LVT-1 FRP-1 FRP-1/PT-1 FRP-1/PT-1 PT -1 FRP-1/PT-1 PT -1 FRP-1 UP TO 8'-0" AFF 107 LAB - - - - - - ACT -1 108 X RAY - - - - - - ACT -1 109 TREATMENT - - - - - - ACT -1 110 GROOM - EP-1-1/WT- 1 PT-1/WT-1 PT-1/WT-1 PT-1/WT-1 PT-1/WT-1 ACT -1 WT -1 FULL HEIGHT IN SHOWER AREA, PATCH EPDXY FLOOR AND BASE AS REQUIRED 111 RESTROOM - - - - - - ACT -1 112 ISOLATION - - - - - - ACT -1 113 DOGS EP -1 EP -1 PT -1 PT -1 PT -1 PT -1 ACT -1 114 DENTAL EP -1 EP -1 PT -1 PT -1 PT -1 PT -1 ACT -1 115 SX EP -1 EP -1 PT -1 PT -1 PT -1 PT -1 ACT -1 116 STORAGE SC -1 EP -1 PT -1 PT -1 PT -1 PT -1 ACT -1 117 OFFICE LVT-1 WB -1 PT -1 PT -1 PT -1 PT -2 ACT -1 118 HALL SC -1 EP -1 PT -1 PT -1 PT -1 PT -1 ACT -1 119 OFFICE LVT-1 WB -1 PT -1 PT -1 PT -1 PT -1 ACT -1 120 DELIVERY SC -1 EP -1 PT -1 PT -1 PT -1 PT -1 ACT -1 121 UTILITY SC -1 EP -1 PT-1/FRP-1 PT -1 PT -1 PT-1/FRP-1 ACT -1 122 BREAK SC -1 WB -1 PT -1 PT -1 PT -2 PT -1 ACT -1 2NOT USED 1NOT USED SCALE: 3/4" = 1'-0" SCALE: 3/4" = 1'-0" chcird, j OF COL® co ROBERT 90 JOHN O +01140 /. �St�D ARGN�� OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.C. 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 COPYRIGHT: 2020 THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN CAN ONLY BE USED FOR THIS PROJECT. NO OTHER USE OF THIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUT THE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. # DESCRIPTION DATE 1 PERMIT SET 15 SEPT 2020 2 ADDENDUM #1 13 NOV 2020 3 ASI 1 13 DEC 2020 CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Project Number: 20019 INTERIOR SCHEDULES AND DETAILS A851 L N O O co W EXISTING CMU WALL, FIELD VERIFY ANGLES PER SCHEDULENEW CMU FACE SHELLS WITH SOLID GROUT BEHIND 2-12 �--yi' CONT. PLATE NOTES: 1. GROUT ALL CELLS SOLID TO 8" ABOVE BOTTOM OF LINTEL. 2, COORDINATE W/ ARCHITECTURAL DWGS FOR SIZE AND LOCATION OF ALL NEW OPENINGS IN EXISTING CMU WALLS 3. DURING LINTEL INSTALLATION, CONTRACTOR SHALL TAKE ALL MEASURES NECESSARY TO PROTECT THE EXISTING STRUCTURE INCLUDING, BUT NOT LIMITED TO BRACING AND SHORING. 1 OCMU LINTEL SCALE: N.T.S. P1 SS -1 2'-0" GROMMET, COORDINATE LOCATION WITH OWNER i L — — — l 2X2X1/4 HSS, W ELD TO 1/2" X 3 1/2" X 12" BASE PLATES WITH (4) 1/2" DIA HILTI KB3 ANCHOR BOLTS (MIN Y EMBEDMENT) STAGGERED WITHIN 31/2" PLATE WIDTH, AT EACH VERTICAL TUBE POST — — 3" 1' - 0" LEASH HOOK, STEEL LINTEL SCHEDULE SPAN SIZE 2 PCS - 6' -0" MAX (2) L6x4x;i (LLV) TYPICAL STEEL ANGLE LINTEL BEARING FACE TOWARDS 2'- 9" WALL (4) SS -1 PT -1 P1 M I N I L 2X2X1 /4 H SS, W ELD TO 1 /2" X 3 1 /2" X 12" BASE PLATES WITH (4) 1/2" WB -1 DIA HILTI KB3 ANCHOR BOLTS (MIN Y EMBEDMENT) STAGGERED WITHIN 3 1/2" PLATE WIDTH, AT — EACH VERTICAL TUBE POST — 8 RECEPTION DESK TRANSACTION TOP SCALE: 1 1/2" = V-0" NOTE: PROVIDE SOLID BLOCKING IN WALL TO SUPPORT COUNTER AS NEEDED. PLA BACKSPLASH PLA COUNTERTOP 4SECTION AT DISHWASHER SCALE: 1 1/2" = V-0" 7 RECEPTION DESK FRONT SECTION SCALE: 1 1/2" = V-0" EXIST CMU WALL STEEL ANGLE LINTEL INSTALL LINTEL ON FRESH MORTAR BED FOR FULL BEARING GROUT CELLS SOLID BELOW BEARING IF HOLLOW NOTES: PROVIDE INSULATION WRAP ON ALL EXPOSED WATER AND DRAIN PIPES PER ADA REQUIREMENTS. PROVIDE SOLID BLOCKING IN WALL TO SUPPORT COUNTER AS NEEDED. g/q PL -1 BACKSPLASH SCHEDULED SINK & FAUCET. RE: PLUMBING DRAWINGS PL -1 COUNTERTOP Ita PL -2 ON 3/4" PARTICLE - BOARD FIXED PANEL `O Q IV CABINET PULL, MATCH EXISTING I WHITE MELAMINE ON INTERIOR SURFACES 0 LINE OF UNDER COUNTER KNEE CLEARANCE I � PL -2 ON 3/4" PARTICLE BOARD BASE CABINET DOOR __— PROVIDE 2 X 2 X CONT. ALUMINUM ANGLE ATTOE KICK y v 3„ STRAIGHT BASE ON INTEGRALTOE KICK, UNO TRANSACTION TOP BEYOND PT -1 3 SECTION AT SINK SCALE: 1 1/2" = V-0" PL -1 COUNTERTOP ON NVO LAYERS OF 1/2" PLYWOOD v HAFELA 208 SERIES L -BRACKET, SUPER DUTY, WHITE. SPACED EVERY 1'-4" O.C. ANCHOR INTO BLOCKING OR STUD. BLOCKING WHERE REQUIRED FOR BRACKET 6 SECTION AT COUNTER SCALE: 1 1/2" = V-0" 2'-1" v 2 SECTION AT BASE SCALE: 1 1/2" = V-0" PL -1 BACKSPLASH PL -1 COUNTERTOP Q a CABINET PULL, �lil_\CN:�D:16911Re 0 1"THICKWHITE MELAMINE ADJUSTABLE SHELFW/ PVC EDGE ,raiana�/dar_u/ulalalaua:IC•]:a PL -2 ON 3/4" PARTICLE BOARD BASE CABINET DRAWER BASE AS SCHEDULED - v GORDONO MULLION MATE 4 (SERIES 30) FINISH TO MATCH EXISTING MULLION FACTORYAPPLIED GASKET WITH ADHESIVE BOTH SID 9 MULLION MATE DETAIL SCALE: 1 1/2" = V-0" 1'- 3" 107' - MULLION MATE END CAP EXTRUSION REFER TO PLAN FOR PARTITION TYPE PL -2 ON 3/4" PARTICLE BOARD BASE CABINET DOOR WHITE MELAMINE INTERIOR z O 1" a IV CABINET PULL, MATCH EXISTING m o ro f N m WHITE MELAMINE INTERIOR PL -2 ON 3/4" PARTICLE BOARD BASE CABINET DRAWER F 1"THICK WHITE MELAMINE j ADJUSTABLE SHELFW/ PVC EDGE w w CABINET PULL, MATCH EXISTING 5SECTION AT UPPER CABINET SCALE: 1 1/2" = V-0" NOTE: PROVIDE SOLID BLOCKING IN WALLTOSUPPORT COUNTERAS NEEDED. 3/4" PLA BACKSPLASH PLA COUNTERTOP NJ BINET 1 SECTION AT DRAWERS SCALE: 1 1/2" = 1'-0" City of Wheat Ridge Building Division chord'1111111 tiOF Coto /.� ROBERT JOHN * ORSLUND pop �Cr OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.0 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 COPYRIGHT: 2020 THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN CAN ONLYBE USED FOR THISPROJECT. NO OTHER USE OFTHIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUTTHE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Project Number: 20019 INTERIOR DETAILS A852 1" a IV CABINET PULL, MATCH EXISTING m o ro f N m WHITE MELAMINE INTERIOR PL -2 ON 3/4" PARTICLE BOARD BASE CABINET DRAWER n BASE AS SCHEDULED BINET 1 SECTION AT DRAWERS SCALE: 1 1/2" = 1'-0" City of Wheat Ridge Building Division chord'1111111 tiOF Coto /.� ROBERT JOHN * ORSLUND pop �Cr OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.0 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 COPYRIGHT: 2020 THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN CAN ONLYBE USED FOR THISPROJECT. NO OTHER USE OFTHIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUTTHE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Project Number: 20019 INTERIOR DETAILS A852 MECHANICAL SPECIFICATIONS THIS SHEET SPECIFICATION SHALL GOVERN IN LIEU OF SEPARATE BOUND SPECIFICATIONS. UPON ISSUANCE SHOULD CONFLICTS ARISE BETWEEN THE SHEET AND THE BOUND SPECIFICATION THEN THE MORE STRINGENT OF THE TWO SHALL PREVAIL. BASIC REQUIREMENTS A.MECHANICAL DESIGN SHALL CONFORM TO 2018 INTERNATIONAL MECHANICAL CODE. PROJECT SHALL BE COORDINATED WITH THE EXISTING BUILDING SERVICES AND SHALL INCLUDE ALL ITEMS NECESSARY FOR COMPLETE AND FULLY OPERATIONAL TENANT MECHANICAL SYSTEMS. MAKE CONNECTIONS TO AND EXTEND SYSTEMS INSTALLED BY OTHERS AND/OR FURNISHED BY OTHERS. PROVIDE ACCESSORIES AND INCIDENTAL ITEMS AS REQUIRED FOR A COMPLETE AND FULLY OPERATIONAL SYSTEM WHETHER OR NOT SPECIFICALLY SPECIFIED AND/OR SHOWN ON THE PLANS. B.DO NOT SCALE FROM THESE DRAWINGS. REFER TO ARCHITECTURAL OR CIVIL DRAWINGS BY OTHERS FOR DIMENSIONS AND FOR ESTIMATING DISTANCES. THESE DRAWINGS ARE TO BE READ IN CONJUNCTION WITH ALL RELEVANT DRAWINGS AND SPECIFICATIONS RELATING TO THE JOB WETHER OR NOT INDICATED ON THESE DRAWINGS. C.ANY SCALE, DIMENSION OR QUANTITIES SHOWN ON THE DRAWINGS ARE FOR ENGINEERING CALCULATION PURPOSES ONLY. THE MECHANICAL CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR ESTIMATING AND DETERMINING ALL DISTANCES AND QUANTITIES RELATED TO THE PROJECT. REFER TO ARCHITECTURAL OR CIVIL DRAWINGS BY OTHERS AND VERIFY EXISTING CONDITIONS ON SITE FOR ALL ESTIMATING PURPOSES. D.000RDINATE WITH OTHER TRADES FOR A COORDINATED INSTALLATION WITHIN THE AVAILABLE SPACE. WHERE CROWDED CONDITIONS EXIST, PREPARE COORDINATION DRAWINGS SHOWING ALL TRADE CONFLICTS AND SUBMIT TO ARCHITECT FOR APPROVAL AND DIRECTION PRIOR TO ROUGH—IN AND/OR INSTALLATION. RELOCATION OF OUTLETS AND/OR DEVICES MADE PRIOR TO ROUGH—IN SHALL BE DONE AT NO ADDITIONAL COST. E. ALL WORK SHALL BE PERFORMED BY PROPERLY LICENSED MECHANICS OR UNDER THEIR DIRECT SUPERVISION. ALL MATERIALS AND EQUIPMENT SHALL MEET THE REQUIREMENTS OF THE APPLICABLE STANDARDS OF UL AND SHALL BEAR THE UL LABEL AS EVIDENCE THAT THE MATERIAL AND/OR EQUIPMENT MEETS THIS REQUIREMENT. F.INSTALL ALL EQUIPMENT PER MANUFACTURER'S RECOMMENDATIONS AND DETAILS UNLESS OTHERWISE NOTED IN THESE PLANS. IF DISCREPANCIES EXIST CONTACT THE ENGINEER PRIOR TO ORDERING EQUIPMENT AND ROUGH—IN. G.ALL EQUIPMENT START UP AND TESTING SHALL BE PERFORMED BY THE EQUIPMENT MANUFACTURER TRAINED SERVICE TECHNICIAN. H.SUBMIT MANUFACTURER'S LITERATURE (SHOP DRAWINGS) FOR MATERIALS AND EQUIPMENT. SUBMITTAL SHALL INCLUDE EQUIPMENT PERFORMANCE DATA AT ELEVATION AND/OR LOCAL CONDITIONS. EQUIPMENT CUTSHEETS OR CATALOG COPIES ARE NOT ACCEPTABLE. SUBMITTAL SHALL BEAR THE APPROVAL OF THE GENERAL CONTRACTOR FOR COMPLIANCE WITH COORDINATION AND THESE SPECIFICATIONS PRIOR TO SUBMITTAL TO ARCHITECT AND/OR HIS AGENCIES. ANY EQUIPMENT SUBSTITUTED FOR WHAT IS SCHEDULED SHALL BE EQUAL TO THAT SCHEDULED IN CONTROLS, ACCESSORIES, AND PERFORMANCE REGARDLESS OF MANUFACTURER. I. FIELD LABEL ALL MECHANICAL EQUIPMENT AND PIPING AS INDICATED ON THE PLANS PER MECHANICAL AND LOCAL CODE REQUIREMENTS. INDICATE DIRECTION OF FLOW ON PIPING. J. PROVIDE 2" DEEP AUXILIARY DRAIN PAN WITH SEPARATE DRAIN LINE UNDER HEATING AND COOLING COILS (AIR HANDLING UNITS, FAN COIL UNITS, INLINE PUMPS, ETC.) AND PROVIDE A WATER—LEVEL MONITORING DEVICE ON ALL DOWNFLOW EQUIPMENT WITHOUT A SECONDARY COIL WHERE CONDENSATION OR LEAKAGE CAN OCCUR. ALTERNATELY, IF ALLOWED IN LOCAL JURISDICTION, PROVIDE AN OVERFLOW CONDENSATE KILL SWITCH. K.PROVIDE EXPANSION LOOPS, SWING JOINTS, OR MECHANICAL EXPANSION COMPENSATING DEVICES AS REQUIRED TO ACCOUNT FOR THERMAL EXPANSION OF ALL PIPING SYSTEMS. EXPANSION SYSTEM SIZING SHALL BE IN ACCORDANCE WITH MATERIALS DATA SHEETS AND MANUFACTURER RECOMMENDATIONS. L. PROVIDE MANUFACTURERS RECOMMENDED MODIFICATIONS (SUCH AS HEAT TRACE AND ROUTING CHANGES) TO CONDENSING GAS FIRED EQUIPMENT LOCATED IN POTENTIAL FREEZING SPACES (SUCH AS ATTICS) 2. BASIC MATERIALS A.PROVIDE MECHANICAL SYSTEM CONTROLS, CONTROLLERS, CONTROL TRANSFORMER, DISCONNECTS, STARTERS, CONTROL WIRING, ASSOCIATED CONTROL POWER WIRING, AND ALL WORK NECESSARY FOR A COMPLETE AND OPERATIONAL MECHANICAL SYSTEM. B.PROVIDE SUPPLEMENTAL STEEL AND SUPPORTS AS REQUIRED FOR INSTALLATION OF MECHANICAL MATERIALS, EQUIPMENT, AND APPARATUS. C.PROVIDE VIBRATION ISOLATION ON ALL MECHANICAL EQUIPMENT. INSTALL FLEXIBLE DUCT CONNECTORS ON ALL AIR HANDLING UNIT SUPPLY OUTLET AND RETURN INLET. D.ALL WORK IN FINISHED AREAS SHALL BE CONCEALED UNLESS SPECIFICALLY NOTED AS EXPOSED ON THE PLANS. PRIOR TO THE INSTALLATION OF ANY EXPOSED WORK THIS CONTRACTOR SHALL VERIFY AND OBTAIN ARCHITECTURAL. APPROVAL OF LOCATION AND EXTENT. E UTILIZE AN INDEPENDENT BALANCER WITH NEBB AND/OR AABC CERTIFICATION. MECHANICAL SYSTEM SHALL BE BALANCED TO 10% DISCREPANCY OF THE CFM INDICATED ON THE PLANS. IF THERE IS A AIR BALANCE DISCREPANCY GREATER THAN 10%, BALANCE CONTRACTOR SHALL CONTACT ENGINEER. PROVIDE MANUAL VOLUME DAMPERS ON DIRECT DRIVE UNITS AS REQUIRED TO MEET SPECIFIED NR QUANTITIES. F. CONFIRM ACTUAL VOLTAGES, PHASE AND CHARACTERISTICS OF EXISTING EQUIPMENT AND APPARATUS FURNISHED BY TENANT OTHER TRADES, AND/OR DIVISIONS. CONFIRM PRIOR TO ROUGH—IN. IF DISCREPANCIES ARE NOTED TO THE INSTRUCTIONS OF THESE PLANS AND SPECIFICATIONS, SUBMIT THE NOTED DISCREPANCIES TO THE ARCHITECT FOR DIRECTION PRIOR TO PROCEEDING. G.PROVIDE DUCT SMOKE DETECTORS FOR AUTOMATIC EQUIPMENT SHUTOFF IN AIR—MOVING SYSTEMS THAT RETURN IN EXCESS OF 2000 CFM TO ENCLOSED SPACES WITHIN BUILDINGS PER MECHANICAL HAVING JURISDICTION. MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE AIR HANDLING UNIT AUTOMATIC SHUT—DOWN WIRING AND DUCT/SMOKE DETECTOR WIRING WHEN REQUIRED. DETECTORS SHALL BE COMPATIBLE WITH BUILDING FIRE ALARM SYSTEM. H.SMOKE, FIRE, RADIATION, AND COMBINATION FIRE/SMOKE DAMPERS SHALL BE FURNISHED AND INSTALLED BY THE MECHANICAL CONTRACTOR. UNITS SHALL BE 120V AND ALL 120V WIRING SHALL BE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR. SMOKE, FIRE AND COMBINATION FIRE/SMOKE DAMPERS FURNISHED SHALL BE COMPATIBLE WITH BUILDING FIRE ALARM SYSTEM. MC SHALL COORDINATE WITH EC AT TIME OF BID TO ENSURE ALL LINE VOLTAGE AND FIRE ALARM CONNECTIONS ARE INCLUDED IN THE BID SCOPE. I. CEILING RADIATION DAMPERS, FIRE DAMPERS, AND SMOKE DAMPERS SHALL BE UL LISTED FOR DYNAMIC USE IN CONFORMANCE WITH UL 555C, UL 555, AND UL 5555 RESPECTIVELY AND LISTED FOR USE WITH THE INSTALLED RATED WALL, FLOOR/CEILING, OR ROOF/CEILING ASSEMBLY. THE CONTRACTOR SHALL MAKE APPROPRIATE PROVISIONS IF AN DYNAMICALLY RATED DAMPER IS NOT AVAILABLE FOR USE IN THE INSTALLED UL LISTED ASSEMBLY. PROVISIONS TO INCLUDE BUT NOT LIMITED TO, A MEANS FOR THE HVAC UNIT BLOWER(S) SHUT DOWN IN THE CASE OF A FIRE AND/OR SMOKE EVENT. NON—DYNAMICALLY RATED DAMPERS ARE ALSO REQUIRED TO BE UL LISTED FOR USE WITH THE INSTALLED RATED ASSEMBLY. J. FIRE/SMOKE DAMPERS SHALL BE FURNISHED WITH REMOTE COMMAND STATION EQUIPPED WITH TEST SWITCH, THERMAL TEST RESET SWITCH, OPEN/CLOSE PILOT LIGHT INDICATORS. FIRE/SMOKE DAMPERS FURNISHED BY MECHANICAL CONTRACTOR AND WIRED BY ELECTRICAL CONTRACTOR. K.THE CONTRACTOR SHALL LOCATE AND FURNISH FOR INSTALLATION BY OTHERS, ALL ACCESS PANELS AS REQUIRED FOR ACCESS TO VALVES, DAMPERS, MOTORS, ETC. AND THE PROPER SERVICING OF EQUIPMENT AND LINES INSTALLED UNDER THIS CONTRACT. AT TIME OF BID THE MC AND GC SHALL COORDINATE TO ENSURE THAT ALL ACCESS PANELS (INCLUDED FIRE AND/OR SMOKE RATED MODELS) ARE INCLUDED. LIN JURISDICTIONS WHERE SEISMIC OR WIND LOADING SECUREMENT DETAILS AND/OR DRAWING ARE REQUIRED THE MECHANICAL CONTRACTOR SHALL COORDINATE WITH THE EQUIPMENT OR CURB SUPPLIER(S) TO OBTAIN THE DRAWINGS AND INSTALL THE SYSTEM AS REQUIRED BY THE MANUFACTURER. THIS MAY APPLY TO ROOF MOUNTED EQUIPMENT AS WELL AND EQUIPMENT SUSPENDED FROM THE STRUCTURE WITHIN THE BUILDING. MECHANICAL CONTRACTOR TO SELECT ATTACHMENT AND MOUNTING SYSTEM(S) BASED ON ATTACHING TO THE DESIGNED SUBSTRATE AND STRUCTURE WITHOUT REQUIRING ADDITIONAL REINFORCEMENT BY OTHER 3. PIPING AFIRE STOP ALL PIPING MATERIALS PASSING THROUGH FIRE RATED STRUCTURES OR FIRE RATED ASSEMBLIES IN ACCORDANCE WITH THE REQUIREMENTS OF AUTHORITIES HAVING JURISDICTION. USE CURRENTLY LISTED U.L. CLASSIFIED PRODUCTS, TESTED BY ASTM E814. USE FOR ALL APPLICABLE PIPE PENETRATIONS THROUGH FIRE RATED FLOORS, WALLS, OR FLOOR CEILING ASSEMBLIES IN ACCORDANCE WITH LOCAL CODE REQUIREMENTS. 4. DUCTWORK A.DUCTWORK SHALL BE GALVANIZED SHEET METAL INSTALLED IN ACCORDANCE WITH SMACNA STANDARDS. INSTALL TURNING VANES IN ALL ELBOWS. ALL SPIN—IN FITTINGS AND RUNOUTS TO ANY REGISTERS, RETURN, OR EXHAUST TERMINAL SHALL BE PROVIDED WITH MANUAL VOLUME DAMPERS. B ALL DUCTWORK SHALL BE SEALED IN ACCORDANCE WITH SMACNA STANDARDS. THE DUCT PRESSURE CLASS SHALL BE AS NOTED ON PLANS OR CORRESPONDING TO THE MAXIMUM EQUIPMENT ESP ON EACH SYSTEM. THE DUCTWORK SHALL BE SEALED TIGHT. LEAKAGE MAY NOT EXCEED 10% OF DESIGN AIRFLOW AT DESIGN PRESSURE. FOR SMOKE CONTROL SYSTEMS THE DUCT MUST BE TESTED AT 1.5 TIMES ITS DESIGN PRESSURE AND LEAKAGE MAY NOT EXCEED 5% OF DEIGN AIRFLOW. C.ALL EXPOSED ROUND DUCTWORK SHALL BE SPIRAL DUCT. NO JOINTS OR CONNECTIONS SHALL HAVE ANY VISIBLE SEALANT FROM THE EXTERIOR SO THE DUCTWORK HAS A CLEAN AND WORKMAN LIKE APPEARANCE. D.DUCT SIZES GIVEN ARE NET INSIDE FREE AREA. E.EQUIPMENT FLEXIBLE DUCTWORK CONNECTION NOT TO EXCEED 10 INCHES IN LENGTH WITH A MAX. 25 FLAME/50 SMOKE INDEX. F. FLEXIBLE DUCTWORK TO AIR DEVICES SHALL HAVE A MAXIMUM STRETCHED LENGTH OF 6 FEET. SUITABLE FOR RETURN AIR PLENUM. G.PRESSURIZED EXHAUST DUCTWORK LOCATED RETURN AIR PLENUM SHALL BE SEALED WITH SMACNA SEAL CLASS "A" DUCT SEALANT. H.ALL FLUE GAS DUCTWORK TO BE METALBESTOS TYPE B VENTING OR EQUAL UNLESS OTHERWISE NOTED ON PLANS. I. ALL EXHAUST TERMINALS MUST BE 3'-0" AWAY FROM IN ELEVATION FROM OPERABLE PORTION OF WINDOW AND DOORS. MC TO OFFSET AS REQUIRED. J. ALL DIRECT VENT VENT TERMINALS MUST BE 4'-0" AWAY IN ELEVATION HORIZONTALLY OR BELOW AND ATLEAST 1'-0" ABOVE ANY OPERABLE PORTION OF A WINDOW OR DOOR. MC TO OFFSET AS REQUIRED. K.IF MC INSTALLATION RESULTS IN LONGER DRYER DUCT VENT LENGTHS THAN NOTED THEN THE OWNER/ ARCH MUST BE INFORMED TO ENSURE PROPER DRYERS ARE INSTALLED. L.INSTALL PERMANENT NAMEPLATE AT ALL DRYER CONNECTIONS WITH J" TEXT STATING THE REQUIRED DUCT LENGTH AND ELBOWS FOR EACH. M.WHERE ROOFTOP HVAC EQUIPMENT OR DUCTWORK PENETRATES A RATED CEILING/ROOF STRUCTURE THEN THE MC SHALL COORDINATE WITH THE GC TO PROVIDE MEMBRANE EXTENSIONS UP TO THE ROOF DECK AT TIME OF BID. IF IMPRACTICAL OR COST PROHIBITIVE THEN FIRE DAMPERS MAY BE USED, AND COORDINATED AT TIME OF BID, AT THE MEMBRANE PENETRATION IN WHICH CASE THE MC AND GC SHALL COORDINATE PROPER ACCESS FOR DAMPER MAINTENANCE. 5. INSULATION A.ALL ROUND CONCEALED RIGID SUPPLY DUCTWORK SHALL BE EXTERNALLY WRAPPED WITH NOMINAL 1-1/2" THICK (MINIMUM R-5.0) FIBER GLASS INSULATION WITH FIRE RETARDANT VAPOR BARRIER. B.OUTDOOR AIR INTAKE DUCTS SHALL BE EXTERNALLY WRAPPED WITH NOMINAL 1-1/2" THICK (MINIMUM R-5.0) FIBER GLASS INSULATION WITH FIRE RETARDANT VAPOR BARRIER. C.WHEN LOCATED IN UNCONDITIONED SPACES ALL RECTANGULAR DUCTWORK SHALL BE LINED WITH 1" THICK 2 POUND DENSITY (MINIMUM R-6.0) FIBER GLASS ACOUSTIC DUCT LINER. ALL DUCTWORK EXPOSED TO OUTDOOR AMBIENT TYPE CONDITIONS (UNCONDITIONED ATTICS, OUTSIDE AIR DUCTS, ETC) SHALL BE EXTERNALLY WRAPPED OR INTERNALLY LINED IN 2 — 2.5" NOMINAL INSULATION (MINIMUM R-12.0). ALL OUTDOOR DUCTWORK SHALL HAVE 2 — 2.5" DUCTLINER (MINIMUM R-12.0) AND THE DUCT BE SEALED WEATHERPROOF PER SMACNA GUIDELINES. RECTANGULAR DUCT WORK IN RETURN AIR PLENUM SHALL BE LINED WITH 1/2" THICK 2 POUND DENSITY (MINIMUM R2.1) MAT—LACED ACOUSTIC DUCT LINER. D.CONDENSATE DRAIN PIPING SHALL BE 1/2—INCH THICK INSULATION WITH AN ALL—SERVICE JACKET. EANSULATE REFRIGERANT SUCTION LINES WITH 1/2" FOAM PLASTIC CLOSED CELL INSULATION. 11. AIR INLETS AND OUTLETS A.FURNISH AND INSTALL AIR INLETS AND OUTLETS AS SCHEDULED ON THE PLANS. B.OUTLETS SHALL HAVE A WHITE BAKED ENAMEL FINISH TO MATCH CEILING OR WALL. 12. EXHAUST FANS A.FURNISH AND INSTALL CENTRIFUGAL EXHAUST FANS AS SCHEDULED ON THE PLANS. B.FURNISH AND INSTALL UNITS COMPLETE WITH ALL OPERATIONAL AND SAFETY CONTROL NECESSARY FOR PROPER OPERATION. 13. CONTROL SYSTEM A.FURNISH AND INSTALL A COMPLETE SYSTEM OF ELECTRIC/ELECTRONIC CONTROL FOR THE SYSTEMS INSTALLED TO PROVIDE THE FOLLOWING SEQUENCES OF OPERATION. B.EXHAUST FANS B.1. EXHAUST FANS TO BE CONTROLLED AS INDICATED ON THE SCHEDULES. 2101: MECHANICAL LEGEND �CHWS� CHILLED WATER SUPPLY �DVR� CHILLED WATER RETURN CDS CONDENSER WATER SUPPLY �CDR� CONDENSER WATER RETURN �HIIS� HOT WATER SUPPLY �HNR� HOT WATER RETURN ® SUPPLY UP IV CEILING SUPPLY DIFFUSER E` SUPPLY DOWN CEILING RETURN AIR REGISTER ® RETURN UP ® ROUND CEILING DIFFUSER EiRETURN DOWN CEILING LINEAR SUPPLY/RETURN i EEXHAUST UP .0. SIDEWALL SUPPLY/RETURN REGISTER EXHAUST ON MANUAL VOLUME DAMPER ® FLEXIBLE DUCT ®F FIRE OR RADIATION DAMPER A ECKAIR DEVICE TAG - S SMOKE DAMPER TAG EQUIPMENT TAG ®FS FIRE SMOKE DAMPER ® DEMO DESIGN CRITERIA N JURISDICTION: ROOF TOP UNIT ,&(POC) POINT OF MECHANICAL CODE: 2018 IMC vv CONNECTION ENERGY CODE: 2018 IECC (POD) POINT OF ApB�Y� IQIJ FURNACE DISCONNECTION 95 / 59 F WB DESIGN OTHERMOSTAT I( )I CONDENSING UNIIT O HUMIDISTAT }� INDOOR HEATING SET POINT: 72 F PARALLEL FAN POWERED VAV BOX C1'd ELBOW UP CUBIC FEET PER MINUTE ELEVATION: C_ ELBOW DOWN MECHANICAL SHEET LIST SHEET # SHEET TITLE VAV BOX ►C}+ TEE UP MECHANICAL SPEC SCHEDULE & LEGEND CV TEE DOWN MECHANICAL SCHEDULES CABINET UNIT HEATER CODES & DESIGN CRITERIA N JURISDICTION: WHEAT RIDGE, CO AIR ADMITTANCE VALVE MECHANICAL CODE: 2018 IMC AFF ENERGY CODE: 2018 IECC AIR HANDLING UNIT WINTER DESIGN DB: —10 F? SUMMER DESIGN TEMP DB / WB 95 / 59 F WB DESIGN FOR EVAP COOLING 64 F DB DESIGN FOR AIR COOLED EQUIP 105 F INDOOR HEATING SET POINT: 72 F INDOOR COOLING SET POINT: 75 F CUBIC FEET PER MINUTE ELEVATION: 5280 FT MECHANICAL SHEET LIST SHEET # SHEET TITLE CLINICAL SINK M001 MECHANICAL SPEC SCHEDULE & LEGEND CV M002 MECHANICAL SCHEDULES CABINET UNIT HEATER MD101 FIRST FLOOR DEMO MECHANICAL PLAN OF MD102 ROOF DEMO MECHANICAL PLAN DOMESTIC HOT WATER M101 FIRST FLOOR MECHANICAL PLAN EVC M102 ROOF MECHANICAL PLAN ELECTRICAL CONTRACTOR M501 MECHANICAL DETAILS ABBREVIATIONS (D) I DEMO E EXISTING N NEW AAV AIR ADMITTANCE VALVE AD AREA DRAIN AFF ABOVE FINISH FLOOR AHU AIR HANDLING UNIT B BOILER BB BASEBOARD BF BOOSTER FAN BFP BACKFLOW PREVENTER BT BATH TUB BV BALL VALVE CD CONDENSATE DRAIN CFM CUBIC FEET PER MINUTE CH CHILLER CS CLINICAL SINK CU CONDENSING UNIT CV CHECK VALVE CUH CABINET UNIT HEATER DCW DOMESTIC COLD WATER OF DRINKING FOUNTAIN DHW DOMESTIC HOT WATER DSN DOWN SPOUT NOZZLE EVC EVAPORATIVE COOLER EC ELECTRICAL CONTRACTOR ECO END OF LINE CLEANOUT EDH ELECTRIC DUCT HEATER EF EXHAUST FAN ERU ENERGY RECOVERY UNIT ER EXISTING REMOVED ERR EXISTING REMOVED & RELOCAT EW EMERGENCY EYEWASH EWC ELECTRIC WATER COOLER EWH ELECTRIC WATER HEATER F FURNACE FCO FLOOR/GRADE CLEANOUT FCU FAN COIL UNIT FD FLOOR DRAIN FS FLOOR SINK G GAS GC GENERAL CONTRACTOR GM GAS METER GPH GALLONS PER HOUR GPM GALLONS PER MINUTE GR GAS REGULATOR GUH GAS UNIT HEATER GW GREASE WASTE GWH GAS WATER HEATER HB HOSE BIB HP HEAT PUMP HX HEAT EXCHANGER IM ICE MAKER BOX LAV LAVATORY LS LAUNDRY SINK MAU MAKE—UP AIR UNIT MC MECHANICAL CONTRACTOR MF MEASURE FLOW NIC NOT IN CONTRACT NC NORMALLY CLOSED NO NORMALLY OPEN NTS NOT TO SCALE OA OUTSIDE AIR ORD OVER FLOW ROOF DRAIN P PUMP PC PLUMBING CONTRACTOR PFT PARALLEL FAN TERMINAL PRV PRESSURE REDUCING VALVE PSI POUNDS PER SQUARE INCH PSIG PRESSURE GAUGE RA RETURN AIR RAR RETURN AIR REGISTER RD ROOF DRAIN RE RELOCATE EXISTING RH RADIANT HEATER RTU ROOF TOP UNIT SA SUPPLY AIR SAR SUPPLY AIR REGISTER SF SUPPLY FAN SFT SERIES FAN TERMINAL SH SHOWER SK SINK SOI SAND/OIL INTERCEPTOR SS SERVICE SINK T&P TEMPERATURE & PRESSURE TO TRENCH DRAIN TYP TYPICAL UR URINAL VAV VARIABLE AIR VOLUME VVT VARI TRAC WB WASHER BOX WC WATER CLOSET/WATER COLUMN WCO WALL CLEANOUT COLUMN WH WALL HYDRANT City of Wheat Ridge Building Division &CIATES INC FqGIYEN lll%1MNIGL s EIFCINCdL e1�EF]IB 735 S. Xenon Ct. #201 Lakewood, Colorado 80228 Ph: 303.716.1270 Fax: 303.716.1272 www.g ivenandassociates.com Project # 20084 chord,10 0&152020 OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.C. 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 COPYRIGHT: 2020 THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN CAN ONLY BE USED FOR THIS PROJECT. NO OTHER USE OF THIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUTTHE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. # DESCRIPTION DATE PERMIT SET 09/15/2020 CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Project Number: 20019 MECHANICAL SPECS & LEGEND M001 VENTILATION SCHEDULE PLAN MARK MFR MODEL NO. CFM MIN OA CFM GAS NAT/ PROP HEATING CAPACI ET COOLING CAPACITY ZONE PER2018 IMC REMARKS INPUT TOTAL MBH SL MBH SENS MBH VOLT PH FLA LG MTR MCA MOCP AREA (SF) RIP I Ra 1 1000SF #1 OCCUPAN# Vbz Ez Voz Ev Vot R-41 OA 208 1 4.4 29 45 (1) (E)RTU-3 (E)RTU-4 2YCC304BA1120AA 1720 EXG NAT EXG EXG EXG R-41 OA 105 EXAM 126 5 0.06 45 5 1 13 0.8 16 0.9 17 116 STORAGE 31 0 0.06 208 O 0 2 0.8 2 0.9 3 118 HALL 303 0 0.06 5 2 18 0.8 23 0.9 25 119 OFFICE 88 5 0.06 5 1 10 0.8 13 0.9 14 120 DELIVERY 124 0 0.06 5 1 7 0.8 9 0.9 10 121 UTILITY 52 0 0.06 5 1 3 0.8 4 0.9 4 122 BREAK 178 5 0.06 40 8 51 0.8 63 0.9 70 TOTAL REQUIRED 145 TOTAL SUPPUED 180 Vbz = Rp • Pz+Ra •Az RIP = OUTDOOR AIRFLOW RATE PER PERSON (CFM/ PERSON) Ra = OUTDOOR AIRFLOE RATE REQUIRED PER UNIT AREA (CFM/ SQFr) Az = ZONE FLOOR AREA (sqft) P. = ZONE POPULATION; OCCUPANTS Vbz (CFM) = BREATHING ZONE OUTDOOR AIR FLOW Voz = Vbz/ Ez Ez = ZONE AIR DISTRIBUTION EFFECTIVENESS Voz (CFM) = ZONE OUTDOOR AIR FLOW Vat = Vbz/ Ev Ev = SYSTEM VENTILATION EFFICIENCY Vot (CFM) = REQUIRED OUTDOOR AIR INTAKE FLOW EXISTING RTU SCHEDULE - FOR REFERENCE ONLY PLAN MARK MFR MODEL NO. CFM MIN OA CFM GAS NAT/ PROP HEATING CAPACI ET COOLING CAPACITY REFRIG (R41OA / R22 I ELECTRICAL DATA REMARKS INPUT TOTAL MBH SL MBH SENS MBH VOLT PH FLA LG MTR MCA MOCP (E)RTU-2 TRANE 2YCC304BA1120AA' RESTROOM 106 EXG NAT EXG EXG EXG R-41 OA 208 1 4.4 29 45 (1) (E)RTU-3 TRANE 2YCC304BA1120AA 1720 EXG NAT EXG EXG EXG R-41 OA 208 1 4.4 29 45 2 (E)RTU-4 CARRIER 48VL-048130 1000 180 NAT EXG EXG EXG R -410A 208 1 7.6 33.2 50 3 (1) EAIJIIINU KUUFIUY UMI IU KtMAIN. NU WUKK. (2) CONTRACTOR TO REBALANCE RTU TOTAL CFM AS SHOWN ON SCHEDULE. (3)CONTRACTOR TO REBALANCE OUTSIDE AIR CFM. EXHAUST FAN SCHEDULE PLAN MARK MFR MODEL N0. LOCATION STYLE CFM ESP IN SONES WEIGHT LBS SPD ELECTRICAL DATA REMARKS VOLT PH HP WATTS EF -1 GREENHECK SP—A110 RESTROOM 106 CEILING 75 .25 0.9 17 950 120 1 — 14 (1)(2)(3) EF -2 GREENHECK SP—A90 UTILITY 121 CEILING 50 0.25 0.7 12 900 120 1 12 1 2 3 4 (1) PROVIDE 6" RU UUCI UP 10 WEAIHER PROOF HOOF CAP AND BACKDRAFI DAMPER. (2) FAN TO OPERATE WITH LIGHT SWITCH. COORDINATE WITH EC FOR EXACT LOCATION IN BATHROOM. (3) REQ ACCESSORIES: CEILING MOUNTING BRACKETS, BACKDRAFT DAMPER. (4) FAN TO RUN ON TIMECLOCK. AIR DEVICE SCHEDULE PLAN MARK STYLE MATERIAL FIN FACE PATT. DAMPER NC MAX NO. SLOTS SIZE INLET DIA. REMARKS A TMS STL WHIT LF NONE35 — 24X24 NOTED (1) B TMS STL WHIT LF NONE 35 — 12X12 NOTED (1) C 350RL STL WHIT LF OP.BLD 35 — 24X24 NOTED (1 )(2) (1) REFERS TO TITUS (2) PROVIDE SQUARE TO ROUND TRANSITION. City of Wheat Ridge Building Division FqGIYEN &CIATES INC YEau m • EIFCINaAL oNEE9s 735 S. Xenon Ct. #201 Lakewood, Colorado 80228 Ph: 303.716.1270 Fax: 303.716.1272 www.g ivenandassociates.conn Project # 20084 chord,11111111 03152020 OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.C. 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 COPYRIGHT: 2020 THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN CAN ONLY BE USED FOR THIS PROJECT. NO OTHER USE OF THIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUTTHE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. # DESCRIPTION DATE PERMIT SET 09/15/2020 CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Project Number: 20019 MECHANICAL SCHEDULES M002 w \ ■ FIRST FLOOR DEMO MECHANICAL PLAN M D 101 4' 2' 0 4' 8' 0 GENERAL NOTES: 1. VERIFY ALL EXISTING MECHANICAL EQUIPMENT AND SIZES PRIOR TO START OF WORK. REPORT ANY DISCREPANCIES TO ENGINEER. 2. ALL EXISTING EQUIPMENT (NO WORK) SHOWN ON PLAN ARE FOR COORDINATION PURPOSES ONLY AND ARE NOT TO BE PART OF SCOPE OF WORK. DRAWING NOTES: O EXISTING RTU ON ROOF TO REMAIN. CONTRACTOR TO VERIFY ALL COMPONENTS OF RTU TO BE WORKING IN PROPER CONDITION PRIOR TO START OF WORK. CONTRACTOR TO REPLACE FILTERS, CLEAN COILS AND REPLACE/ REPAIR ANY THERMOSTAT WIRING THAT IS DAMAGED OR EXPOSED. ORELOCATE GRILLE/DIFFUSER, REFER TO M101 FOR MORE INFORMATION. O REMOVE THERMOSTAT AND RELOCATE TO AREA SHOWN ON M101. O REMOVE AND DISCONNECT DRYER VENT. REFER TO M101 FOR NEW LOCATION OF DRYER. AND RELOCATION City of Wheat Ridge Building Division &CIATES INC FqGIYEN �auinrx s rarEeliocK otns 735 S. Xenon Ct. #201 Lakewood, Colorado 80228 Ph: 303.716.1270 Fax: 303.716.1272 www.g ivenandassociates.conn Project # 20084 chord,11111111 03152020 OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.C. 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 COPYRIGHT: 2020 THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN CAN ONLY BE USED FOR THIS PROJECT. NO OTHER USE OF THIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUTTHE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. # DESCRIPTION DATE PERMIT SET 09/15/2020 CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Project Number: 20019 FIRST FLOOR DEMO MECHANICAL PLAN MD101 i►tlir: FIRST FLOOR MECHANICAL P LAN M 101 4' 2' 0 4' 8' 1/4"= 1'-0" WATER - HEATER GENERAL NOTES: 1. VERIFY ALL EXISTING MECHANICAL EQUIPMENT AND SIZES PRIOR TO START OF WORK. REPORT ANY DISCREPANCIES TO ENGINEER. 2. ALL NEW HVAC UNITS TO BE COORDINATED WITH EXISTING CONDITION OF THE BUILDING PRIOR TO START OF WORK. 3. ALL EXISTING EQUIPMENT (NO WORK) SHOWN ON PLAN ARE FOR COORDINATION PURPOSES ONLY AND ARE NOT TO BE PART OF SCOPE OF WORK. DRAWING NOTES: O PROVIDE NEW CONNECTION TO EXISTING SUPPLY AND RETURN AIIR DUCTS. O PROVIDE 3/4" DOOR UNDERCUT. O EXTEND AND RECONNECT DUCT TO RELOCATED DIFFUSER/GRILLE. O RECONNECT DRYER VENT TO DRYER BOX ANDS ROUTE OVER TO WALL. O TERMINATE DRYER VENT AT WALL WITH WALL CAP 9'-0" MINIMUM ABOVE WALKWAY. u REVISION City of Wheat Ridge Building Division FiGIVEN & ASSOCIATES INC MECHANICAL & ELECTRICAL ENGNEM 735 S. Xenon Ct. #201 Lakewood, Colorado 80228 Ph: 303.716.1270 Fax: 303.716.1272 www.givenandassociates.com Project # 20084 chcird% OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.C. 1425 MARKET STREET SUITE 220 DENVER, CO 80202 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 COPYRIGHT: 2020 THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN CAN ONLY BE USED FOR THIS PROJECT. NO OTHER USE OF THIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUT THE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. # DESCRIPTION DATE PERMIT SET 09/15/2020 2 ADDENDUM #1 11/13/2020 3 ASI #1 12/17/2020 CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Project Number: FIRST FLOOR 20019 MECHANICAL PLAN M101 w \ ■ ROOF MECHANICAL PLAN M 10 2 4' 2' 0 4' 8' GENERAL NOTES: 1. VERIFY ALL EXISTING MECHANICAL EQUIPMENT AND SIZES PRIOR TO START OF WORK. REPORT ANY DISCREPANCIES TO ENGINEER. 2. ALL NEW HVAC UNITS TO BE COORDINATED WITH EXISTING CONDITION OF THE BUILDING PRIOR TO START OF WORK. 3. ALL EXISTING EQUIPMENT (NO WORK) SHOWN ON PLAN ARE FOR COORDINATION PURPOSES ONLY AND ARE NOT TO BE PART OF SCOPE OF WORK. DRAWING NOTES: O EXISTING RTU ON ROOF TO REMAIN. CONTRACTOR TO VERIFY ALL COMPONENTS OF RTU TO BE WORKING IN PROPER CONDITION PRIOR TO START OF WORK. CONTRACTOR TO REPLACE FILTERS, CLEAN COILS AND REPLACE/ REPAIR ANY THERMOSTAT WIRING THAT IS DAMAGED OR EXPOSED. O REBALANCE RTU TOTAL AIRFLOW TO 1720 CFM. SEE SCHEDULE FOR MORE INFORMATION. O REBALANCE RTU TOTAL AIRFLOW TO 1000 CFM. SEE SCHEDULE FOR MORE INFORMATION. City of Wheat Ridge Building Division &CIATES INC FqGIYEN lll%1MNIGL s EIFCINCdL e1�EF]IB 735 S. Xenon Ct. #201 Lakewood, Colorado 80228 Ph: 303.716.1270 Fax: 303.716.1272 www.g ivenandassociates.com Project # 20084 chord,11111111 09-152020 OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.C. 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 COPYRIGHT: 2020 THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN CAN ONLY BE USED FOR THIS PROJECT. NO OTHER USE OF THIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUTTHE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. # DESCRIPTION DATE PERMIT SET 09/15/2020 CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Project Number: 20019 ROOF MECHANICAL PLAN M102 ERIOR WALL WALL CAP WITH BIRDSCREEN WALL CAP D ETAI L M501 N.T.S. SUPPLY AIR TRUNK DUCT DUCT INSULATION RIGID ROUND DUCT BUTTERFLY TYPE DAMPER PRE -INSULATED FLEX DUCT AT FINAL 6'-0" MAX CLAMP `CEILING � DIFFUSER INSTALL DETAIL M501 N.T.S. MAIN .5D FLEXIBLE DUCT TO TROFFER OR DIFFUSER SHEET METAL AS REQUIRED CIRCULAR BRANCH DUCT DETAIL M501 N.T.S. City of Wheat Ridge Building Division GIVEN &ASSOCIATES INC lll%1MNIGL a EIFCINCdL e1�EF]IB 735 S. Xenon Ct. #201 Lakewood, Colorado 80228 Ph: 303.716.1270 Fax: 303.716.1272 www.g ivenandassociates.com Project # 20084 chord,11111111 03152020 OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.0 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 COPYRIGHT: 2020 THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN CAN ONLY BE USED FOR THIS PROJECT. NO OTHER USE OF THIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUTTHE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. # DESCRIPTION DATE PERMIT SET 09/15/2020 CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Project Number: 20019 MECHANICAL DETAILS M501 u x4linsmusim THIS SHEET SPECIFICATION SHALL GOVERN IN LIEU OF SEPARATE BOUND SPECIFICATIONS. UPON ISSUANCE SHOULD CONFLICTS ARISE BETWEEN THE SHEET AND THE BOUND SPECIFICATION THEN THE MORE STRINGENT OF THE TWO SHALL PREVAIL. 1. BASIC REQUIREMENTS A.PLUMBING DESIGN SHALL CONFORM TO 2018 INTERNATIONAL PLUMBING CODE. PROJECT SHALL BE COORDINATED WITH THE EXISTING BUILDING SERVICES AND SHALL INCLUDE ALL ITEMS NECESSARY FOR COMPLETE AND FULLY OPERATIONAL TENANT PLUMBING SYSTEMS. MAKE CONNECTIONS TO AND EXTEND SYSTEMS INSTALLED BY OTHERS AND/OR FURNISHED BY OTHERS. PROVIDE ACCESSORIES AND INCIDENTAL ITEMS AS REQUIRED FOR A COMPLETE AND FULLY OPERATIONAL SYSTEM WHETHER OR NOT SPECIFICALLY SPECIFIED AND/OR SHOWN ON THE PLANS. B.DO NOT SCALE FROM THESE DRAWINGS. REFER TO ARCHITECTURAL OR CIVIL DRAWINGS BY OTHERS FOR DIMENSIONS AND FOR ESTIMATING DISTANCES. THESE DRAWINGS ARE TO BE READ IN CONJUNCTION WITH ALL RELEVANT DRAWINGS AND SPECIFICATIONS RELATING TO THE JOB WETHER OR NOT INDICATED ON THESE DRAWINGS. C.ANY SCALE, DIMENSION OR QUANTITIES SHOWN ON THE DRAWINGS ARE FOR ENGINEERING CALCULATION PURPOSES ONLY. THE PLUMBING CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR ESTIMATING AND DETERMINING ALL DISTANCES AND QUANTITIES RELATED TO THE PROJECT. REFER TO ARCHITECTURAL OR CIVIL DRAWINGS BY OTHERS AND VERIFY EXISTING CONDITIONS ON SITE FOR ALL ESTIMATING PURPOSES. D.000RDINATE WITH OTHER TRADES FOR A COORDINATED INSTALLATION WITHIN THE AVAILABLE SPACE. WHERE CROWDED CONDITIONS EXIST, PREPARE COORDINATION DRAWINGS SHOWING ALL TRADE CONFLICTS AND SUBMIT TO ARCHITECT FOR APPROVAL AND DIRECTION PRIOR TO ROUGH -IN AND/OR INSTALLATION. RELOCATION OF OUTLETS AND/OR DEVICES MADE PRIOR TO ROUGH -IN SHALL BE DONE AT NO ADDITIONAL COST. E. ALL WORK SHALL BE PERFORMED BY PROPERLY LICENSED PLUMBERS OR UNDER THEIR DIRECT SUPERVISION. ALL MATERIALS AND EQUIPMENT SHALL MEET THE REQUIREMENTS OF THE APPLICABLE STANDARDS OF UL AND SHALL BEAR THE UL LABEL AS EVIDENCE THAT THE MATERIAL AND/OR EQUIPMENT MEETS THIS REQUIREMENT. F. INSTALL ALL EQUIPMENT PER MANUFACTURER'S RECOMMENDATIONS AND DETAILS UNLESS OTHERWISE NOTED IN THESE PLANS. IF ANY DISCREPANCIES EXIST CONTACT THE ENGINEER PRIOR TO ORDERING EQUIPMENT AND ROUGH -IN G.ALL EQUIPMENT START UP AND TESTING SHALL BE PERFORMED BY THE EQUIPMENT MANUFACTURER TRAINED SERVICE TECHNICIAN. H.SUBMIT MANUFACTURER'S LITERATURE (SHOP DRAWINGS) FOR MATERIALS AND EQUIPMENT. SUBMITTAL SHALL INCLUDE EQUIPMENT PERFORMANCE DATA AT ELEVATION, ALTITUDE, AND/OR LOCAL CONDITIONS. EQUIPMENT CUTSHEETS OR CATALOG COPIES ARE NOT ACCEPTABLE. SUBMITTAL SHALL BEAR THE APPROVAL OF THE GENERAL CONTRACTOR FOR COMPLIANCE WITH COORDINATION AND THESE SPECIFICATIONS PRIOR TO SUBMITTAL TO ARCHITECT Q HIS AGENCIES. ANY AND/OR EQUIPMENT SUBSTITUTED FOR WHAT IS SCHEDULED / SHALL BE EQUAL TO THAT SCHEDULED IN CONTROLS, ACCESSORIES, AND PERFORMANCE REGARDLESS OF MANUFACTURER. I. FIELD LABEL ALL PLUMBING EQUIPMENT AND PIPING AS INDICATED ON THE PLANS PER PLUMBING AND LOCAL CODE REQUIREMENTS. INDICATE DIRECTION OF FLOW ON PIPING. J. TAG ALL VALVES WITH CONSECUTIVE NUMBERING ON PERMANENT HARD PLASTIC OR METAL TAB AND PROVIDE SCHEDULE LISTING ITEMS, AREA SERVED, SIZE AND VALVE TYPE. SUBMIT FINAL VALVE SCHEDULE FOR REVIEW. K.PROVIDE EXPANSION LOOPS, SWING JOINTS, OR MECHANICAL EXPANSION COMPENSATING DEVICES AS REQUIRED TO ACCOUNT FOR THERMAL EXPANSION OF ALL PIPING SYSTEMS. EXPANSION SYSTEM SIZING SHALL BE IN ACCORDANCE WITH MATERIALS DATA SHEETS AND MANUFACTURER RECOMMENDATIONS. L.INSTALL ALL EQUIPMENT PER MANUFACTURERS INSTRUCTIONS AND RECOMMENDATIONS. IF PLAN DIFFERS FROM THESE INSTRUCTIONS THEN NOTIFY ENGINEER PRIOR TO ROUGH -IN. MANUFACTURERS INSTRUCTIONS SHALL PREVAIL. SPECIAL ATTENTION MUST BE PAID TO GAS FIRED EQUIPMENT FLUE/CA LENGTHS, SIZES, AND MATERIAL. M.SITE CONTRACTOR TO BRING ALL UNDERGROUND PLUMBING TO A MINIMUM OF 5' OF BUILDING UNLESS NOTED OTHERWISE AND COORDINATE CONNECTION TO ALL PLUMBING LEAVING OR ENTERING THE BUILDING. PLUMBING CONTRACTOR TO COORDINATE THE CONNECTIONS TO THE SITE SYSTEMS. AT TIME OF BID THE CONTRACTORS SHALL ENSURE THE SITE TO BUILDING UTILITY CONNECTIONS ARE INCLUDED. CONTRACTOR SHALL CONTACT DESIGN TEAM DURING THE BID PROCESS IF THERE IS A DISCREPANCY BETWEEN THE CIVIL DOCUMENTS AND THE PLUMBING DOCUMENTS. 2.13ASIC MATERIALS A.PLUMBING CONTRACTOR TO PROVIDE PLUMBING SYSTEM CONTROLS, CONTROLLERS, CONTROL TRANSFORMER, DISCONNECTS, STARTERS, CONTROL WIRING, ASSOCIATED CONTROL POWER WIRING, AND ALL WORK NECESSARY FOR A COMPLETE AND OPERATIONAL PLUMBING SYSTEM. ALL ELECTRICAL ITEMS SHALL BE COORDINATED WITH ELECTRICAL DRAWINGS AND ELECTRICAL SUB -CONTRACTOR FOR INSTALLATION. &PROVIDE SUPPLEMENTAL STEEL AND SUPPORTS AS REQUIRED FOR INSTALLATION OF PLUMBING MATERIALS, EQUIPMENT, AND APPARATUS. C.ALL WORK IN FINISHED AREAS SHALL BE CONCEALED UNLESS SPECIFICALLY NOTED AS EXPOSED ON THE PLANS. PRIOR TO THE INSTALLATION OF ANY EXPOSED WORK THIS CONTRACTOR SHALL VERIFY AND OBTAIN ARCHITECTURAL. APPROVAL OF LOCATION AND EXTENT. D.PROVIDE PRESSURE REDUCING VALVE ASSEMBLY AT BUILDING WATER SERVICE ENTRY WHERE PRESSURE EXCEEDS 65 PSI. PRESSURE REDUCING VALVE TO BE SET TO 65 PSI. E.PROVIDE SANITARY SEWER SYSTEM CLEANOUTS AS REQUIRED BY LOCAL CODES. F. PROVIDE BRANCH SHUT-OFF VALVES ON ALL WATER LINES EXTENDING FROM MAINS. G.THE CONTRACTOR SHALL LOCATE AND FURNISH FOR INSTALLATION BY OTHERS, ALL ACCESS PANELS AS REQUIRED FOR ACCESS TO VALVES, MOTORS, ETC. AND THE PROPER SERVICING OF EQUIPMENT AND LINES INSTALLED UNDER THIS CONTRACT. 3. PIPING A.SANITARY, VENT, GREASE, SAND OIL, AND STORM PIPING ABOVE GRADE SHALL BE CAST IRON NO -HUB PIPE AND FITTINGS, MANUFACTURED TO CISPI 310 BEARING THE COLLECTIVE TRADEMARK OF THE CAST IRON SOIL PIPE INSTITUTE AND BE LISTED BY NSF INTERNATIONAL. COUPLINGS FOR JOINING CAST IRON NO -HUB PIPE SHALL MEET THE REQUIREMENTS OF CISPI 310 AND LISTED BY NSF INTERNATIONAL TO THE CISPI 310 STANDARD. IF HEAVY DUTY COUPLINGS ARE REQUIRED: HUSKY 2000, CLAMP ALL 80, OR MISSION 80 COUPLINGS WITH CONSIDERATION TO USE: HUSKY 4000 OR CLAMP ALL 125. INSTALLATION IN COMPLIANCE TO CISPI HANDBOOK. B.SANITARY, VENT, GREASE, SAND OIL, AND STORM PIPING BELOW GRADE SHALL BE CAST IRON HUB AND SPIGOT PIPE AND FITTINGS, MANUFACTURED TO ASTM A74 AND BEARING THE COLLECTIVE TRADEMARK OF THE CAST IRON SOIL PIPE INSTITUTE AND LISTED BY NSF INTERNATIONAL. CAST IRON HUB AND SPIGOT PIPE SHALL BE JOINED WITH COMPRESSION GASKETS MANUFACTURED IN COMPLIANCE WITH ASTM C564 AND C1563. OR CAST IRON NO -HUB PIPE AND FITTINGS MANUFACTURED TO CISPI 301 AND LISTED BY NSF INTERNATIONAL AND, BEARING THE COLLECTIVE TRADEMARK OF THE CAST IRON SOIL PIPE INSTITUTE. COUPLINGS FOR JOINING CAST IRON NO -HUB PIPE SHALL MEET THE REQUIREMENTS OF CISPI 310 AND LISTED BY NSF INTERNATIONAL. IF HEAVY DUTY COUPLINGS ARE REQUIRED: HUSKY 2000, CLAMP ALL 80, OR MISSION 80 COUPLINGS WITH CONSIDERATION TO USE: HUSKY 4000 OR CLAMP ALL 125. INSTALLATION IN COMPLIANCE TO CISPI HANDBOOK. C.SANITARY, VENT, GREASE, SAND OIL, AND STORM PIPING ABOVE AND BELOW GRADE SHALL BE SOLID CORE (NO CELL CORE) PVC SCHEDULE 40 PIPE (140F MAX) AND SHALL BE IRON PIPE SIZE (IPS) CONFORMING TO ASTM D 1784, ASTM D 1785 AND ASTM D 2665. INJECTION MOLDED PVC DWV FITTINGS SHALL CONFORM TO ASTM D 2665. FABRICATED PVC DWV FITTINGS SHALL CONFORM TO ASTM F 1866. PIPE AND FITTINGS SHALL BE MANUFACTURED AS A SYSTEM AND BE THE PRODUCT OF ONE MANUFACTURER. ALL PIPE AND FITTINGS SHALL BE MANUFACTURED IN THE UNITED STATES. ALL SYSTEMS SHALL UTILIZE A SEPARATE WASTE AND VENT SYSTEM. PIPE AND FITTINGS SHALL CONFORM TO NSF INTERNATIONAL STANDARD 14. INSTALLATION SHALL COMPLY WITH THE LATEST INSTALLATION INSTRUCTIONS PUBLISHED BY MANUFACTURER AND SHALL CONFORM TO ALL APPLICABLE PLUMBING, BUILDING, AND FIRE CODE REQUIREMENTS. BURIED PIPE SHALL BE INSTALLED IN ACCORDANCE WITH ASTM D 2321 AND ASTM F 1668. SOLVENT CEMENT JOINTS SHALL BE MADE IN A TWO STEP PROCESS WITH COLORED PRIMER CONFORMING TO ASTM F 656 AND SOLVENT CEMENT CONFORMING TO ASTM D 2564. THE SYSTEM SHALL BE PROTECTED FROM CHEMICAL AGENTS, FIRE STOPPING MATERIALS, THREAD SEALANT, PLASTICIZED VINYL PRODUCTS, OR OTHER AGGRESSIVE CHEMICAL AGENTS NOT COMPATIBLE WITH PVC COMPOUNDS. SYSTEMS SHALL BE HYDROSTATICALLY TESTED AFTER INSTALLATION. D.DOMESTIC WATER PIPING WATER ENTRY MECH ROOMS MAINS DISTRIBUTION ABOVE BELOW GRADE: ABOVE GRADE COPPER SHALL BE ( ) ABOVE/ BELOW B 88 TYPE L COPPER WITH WROUGHT OR FORGED FITTINGS AND LEAD FREE SOLDERED OR MECHANICALLY PRESSED -CONNECTED JOINT PRO PRESS OR EQUAL. BELOW GRADE WATER PIPING SHALL BE TYPE K COPPER WITH SILVER SOLDERED JOINTS E. DOMESTIC WATER PIPING (MAINS, DISTRIBUTION) ABOVE/BELOW GRADE: TYPE A UPONOR AQUAPEX PIPING WITH PROPEX FITTINGS FOR ALL BRANCH CONNECTIONS AND TERMINATIONS (OR REHAU EQUIVALENT). TYPE B VIEGA PEX OR EQUAL WITH ZERO LEAD BRONZE, RADEL-R PEX PRESS, OR EQUAL FITTINGS FOR ALL BRANCH CONNECTIONS AND TERMINATION. MANIFOLD SYSTEM SHALL BE REVIEWED AND APPROVED PRIOR TO INSTALLATION. DCW TO BE BLUE PIPE, DHW TO BE RED PIPE, AND DHWR TO BE WHITE PIPE. F. CONDENSATE DRAIN PIPING SHALL BE TYPE M COPPER WITH SOLDERED JOINTS, OR CPVC IF ALLOWED BY LOCAL AUTHORITY HAVING JURISDICTION. G.ANY PIPING SYSTEM LOCATED IN A RETURN AIR PLENUM SHALL BE NONCOMBUSTIBLE OR SHALL HAVE A FLAME SPREAD INDEX OF NO MORE THAN 25 AND A SMOKE -DEVELOPED INDEX OF NOT MORE THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84. H.FIRE STOP ALL PIPING MATERIALS PASSING THROUGH FIRE RATED STRUCTURES OR FIRE RATED ASSEMBLIES IN ACCORDANCE WITH THE REQUIREMENTS OF AUTHORITIES HAVING JURISDICTION. USE CURRENTLY LISTED U.L. CLASSIFIED PRODUCTS, TESTED BY ASTM E814. USE FOR ALL APPLICABLE PIPE PENETRATIONS THROUGH FIRE RATED FLOORS, WALLS, OR FLOOR CEILING ASSEMBLIES IN ACCORDANCE WITH LOCAL CODE REQUIREMENTS. C INSULATION A.PIPING INSULATION TO BE INSTALLED AS PER BELOW. WHEN CONFLICTING INSULATION REQUIREMENTS ARE LISTED, THE MORE STRINGENT SHALL BE USED. B.INSULATION SHALL BE INSTALLED PER 2015 IECC C404.4. TABLE C403.2.10 HOT & RETURN WATER PIPING (105'-140') 1-1/4" AND SMALLER SHALL HAVE 1" FIBER GLASS INSULATION WITH AN ALL -SERVICE JACKET, 1-1/2" AND LARGER SHALL HAVE 1-1/2" FIBER GLASS INSULATION WITH AN ALL -SERVICE JACKET -0.21-0.28).141'-200' 1 1 4" AND SMALLER SHALL HAVE 1 1 2" (K VALUE OF / / FIBER GLASS INSULATION WITH AN ALL -SERVICE JACKET, 1-1/2" AND LARGER SHALL HAVE 2" FIBER GLASS INSULATION WITH AN ALL -SERVICE JACKET (K -VALUES OF 0.25-0.29). VALUES PER 2015 IECC TABLE C403.2.10. EXCEPTION: PIPING SURROUNDED BY BUILDING INSULATION WITH A THERMAL RESISTANCE OF NOT LESS THAN R-3. C.SANITARY, DOMESTIC COLD, AND HOT WATER PIPING IN AN EXTERIOR WALL, CEILING, OR FLOOR THAT IS ADJACENT TO AN UNCONDITIONED SPACE SHALL BE INSTALLED TO THE WARM SIDE OF THE BUILDING INSULATION D.IN COLD ENVIRONMENTS (99% WINTER DESIGN DB <34F): D.A. HORIZONTAL SANITARY AND STORM PIPING EXPOSED TO OUTDOOR TYPE AMBIENT CONDITIONS INCLUDING COVERED PARKING AND CRAWL SPACES SHALL BE HEAT -TRACED AND INSULATED WITH 1 -INCH FIBERGLASS INSULATION. D.B. VERTICAL SANITARY AND STORM PIPING EXPOSED TO OUTDOOR TYPE AMBIENT CONDITIONS INCLUDING EXTERIOR WALLS COVERED PARKING AND CRAWL SPACES SHALL BE INSULATED WITH 1 -INCH FIBERGLASS INSULATION. D.C. DOMESTIC COLD & HOT WATER PIPING EXPOSED TO OUTDOOR TYPE AMBIENT CONDITIONS INCLUDING ATTICS COVERED PARKING AND CRAWL SPACES SHALL BE HEAT -TRACED AND INSULATED WITH MINIMUM 2 -INCH FIBERGLASS INSULATION. D.D.PROVIDE MINIMUM 1 -INCH THICK INSULATION ON DOMESTIC WATER LINES IN AN EXTERIOR WALL, CEILING, OR FLOOR THAT IS ADJACENT TO AN UNCONDITIONED SPACE. 5.PLUMBING FIXTURES A.FURNISH AND INSTALL PLUMBING FIXTURES AS SCHEDULED ON THE PLANS. B.PROVIDE CHROME PLATED ANGLE STOPS AND ESCUTCHEON PLATES ON ALL EXPOSED FIXTURE RUNOUTS C.PROVIDE INSULATION AND ROUGH IN AS REQUIRED FOR COMPLIANCE WITH ADA REQUIREMENTS. D.PROVIDE ALL ACCESSORIES AND SPECIALTY ITEMS AS REQUIRED FOR A COMPLETE FIXTURE INSTALLATION. 9.ELECTRIC WATER HEATERS H.FURNISH AND INSTALL A GLASS LINED ELECTRIC WATER HEATER AS SCHEDULED ON THE PLANS. I. FURNISH HEATER WHICH ARE UL LABELED AND MEET THE REQUIREMENTS OF LOCAL MUNICIPALITIES. J.WATER HEATER LOCATED IN CEILING SHALL BE PROVIDED WITH 2 1/2" DRAIN PAN. TERMINATE DRAIN TO NEAREST FLOOR DRAIN, FLOOR SINK OR LAV TRAP. 10. PUMP A.FURNISH AND INSTALL INLINE OR BASE MOUNTED PUMP AS SCHEDULED ON THE PLANS. B.FURNISH AND INSTALL PUMP COMPLETE WITH ALL OPERATIONAL AND SAFETY CONTROLS. 11. CIRCULATING PUMP A.FURNISH AND INSTALL A DOMESTIC ALL BRONZE HOT WATER RETURN CIRCULATOR AS SCHEDULED ON THE PLANS. PROVIDE RETURN LINE AQUASTAT AND WIRE COMPLETE TO CYCLE CIRCULATOR TO PROVIDE 120 OR 140 DEGREES RETURN WATER TEMPERATURE (ADJUSTABLE). PLUMBING FIXTURE SCHEDULE TAG ADA DESCRIPTION CONNECTIONS FIXTURE MODEL NO. BO -BATTERY OPERATED PA -PER ARCHrrECT/OWNER DCW I DHW I WASTE VENT MANUFACTURER MODEL NAME MODEL FLOW RATE DIMENSIONS MOUNTING MIS. DIMENSIONS FINISH MISG. REMARKS WC -1 YES WATER CLOSET -TANK 3/4' 3' 2' AMERICAN STANDARD CADET 3 2383.012 1.28 GPF 12" R.I. 16 1 -1/2 -RIM FLOOR 2-1/8- TRAP WHITE VITREOUS CHINA ELONGATED CONDENSING UNIT CV CHECK VALVE OPEN FRONT LESS COVER CABINET UNIT HEATER DCW AMERICAN STANDARD HEAVY DUTY 5901.110 DHW ELONGATED DSN DOWN SPOUT NOZZLE PLASTIC STAINLESS HINGES EC IAV -1 YES OVAL 1-1/2" 2" KOHLER SOHO K-2084 ENERGY RECOVERY UNIT 20" X 18" WALL MOUNT ERR WHITE VITREOUS CHINA FRONT OVERFLOW 4" CENTERSEr EMERGENCY EYEWASH EWC YES LAV -FAUCET 1/2- 1/2- F MOEN T6142BL T61428L 1.2 GPM 5-5/8" SPOUT B-16" CENTER SINGLE HOLE MATTE BLACK FLOOR SINK G KS -1 GC KITCHEN SINK 2" 2" BLANCO STELLAR 441529 GALLONS PER MINUTE 25'X22"XB" UNDERMOUNT GUH 18 GUAGE STAINLESS GW GREASE WASTE GWH GAS WATER HEATER FAUCET 1/2 1/2 HP MOEN 7565BL 7565BL 1.5 GPM 7" PULLOUT SPOUT LAV LAVATORY MATTE BLACK LAUNDRY SINK MAU MAKE-UP AIR UNIT MC DISPOSER MF MEASURE FLOW IN-SINK-ERRATOR BADGER 5SE NORMALLY CLOSED NO FLANGE NTS NOT TO SCALE 1/2 HP 12V SINGLE PH OUTSIDE AIR SS -1 NO MOP BASIN 3" 2" STERN WILLIAMS CORLOW HL -1800 PRV 24'X24')(12" FLOOR POUNDS PER SQUARE INCH TERRAZZO STAINLESS CAPS RA RETURN AIR RAR MOP BASIN -FAUCET 1 2" 1/2- ROOF DRAIN STERN WILLIAMS RELOCATE EXISTING T -10 -VB RADIANT HEATER RTU WALL 24" ABOVE RIM CHROME W T-35 OPTION SUPPLY AIR REGISTER DF -1 YES SINGLE -LEVEL 1 2" 2 2 1 ELKAY EZH2O BOTTLE FILLING LZSDWS SO 19" WIDE WALL 27' CUR STAINLESS STEEL BARRIER FREE, 115V, BOTTLE FILLER TO TRENCH DRAIN TYP WALL HANGER UR URINAL VAV VARIABLE AIR VOLUME WT VARI TRAC WB FLOOR WC DURA COATED CARRIER ONLY WALL CLEANOUT COLUMN WB -1 NO WASHER BOX 3 4 3 4 2 2 SIOUX CHIEF OX BOX 696-2313XF-1 2 11-1 2 X 7-1 4 WALL ABS W WATER ARRESTOR AND VALVE H DW -1 DOG WASH FAUCET 1 2 1 2 FOREVER STAINLESS STEEL QUAOIY FIXTURE WALL FS -1 FLOOR SINK 2-4" 2" ZURN ZN-1900-KC-4 12" X 12" X 6" 1 FLOOR WHITE TRAP GUARD FD -1 I I FLOOR DRAIN 1 1 3" 1 832 -25D -NR -B 1 1 5-1/2 ROUND FLOOR NICKEL BRONZE FINISH STAINLESS STRAINER I ALILRNAIE MFG: AMERICAN SIANUARU, CRANE, DELIA, LLKAY, HAWS, HALSLY IAYLOR, J.R.SMIIH, KOHLER, IASCU, MOEN, SIOUX CHIEF, SIING NAY, SYMMORS, 1010, WADE. LURN. AF -ALTERNATE FIXTURS NOT ALLOWED LS-UNT SCREEN ON PUBLIC WASHERS TP-ASSE 1018 OR 1044 TRAP PRIMER BS -BASKET STRAINER NA -NO ALTERNATES UNLESS PROVIDED BY OWNER. WB -WALL BRACKET MODEL NO. BO -BATTERY OPERATED PA -PER ARCHrrECT/OWNER WD -WATER DAM RISE F DS -DOME STRAINER PS -POP UP STRAINER 6W-6" WALL REO. PHASE DW -DISH WASHER CONNECTION RC -REMOTE CHILLER, REQUIRES 12" CLEAR 8W-8" WALL REQUIRED I SSE -65A EC -120 VOLT, SINGLE PHASE CONNECTION SM-SENSOR/METERING FAUCET 15W-7" VOID BETWEEN (2)4" WALLS GS -GRID STRAINER TG-ASSE 1072 TRAP GUARD 17W-9" VOID BETWEEN (2)4" WALLS ELECTRIC WATER HEATER SCHEDULE DEMO E PLAN MARK PLAN MARK MANUFACTURER MODEL NO. TANK GALLONS RESIDENTIAL ENERGY FACTOR GPH RECOVERY RISE F ELECTRICAL REMARKS VOLT PHASE WATTS EWH-1 I STATE I SSE -65A 1 65 1 1.98 1 33.00 1100.001 208 1 1 1 9 kW 1 GENERAL NOTES: 1. ALL PUBLIC SINKS TO HAVE OPEN GRID STRAINERS. 2. ALL NON-PUBLIC SINKS TO HAVE POP-UP STRAINERS. 3. ALL FIXTURES TO BE PROVIDED W/ FLEXIBLE WATER UNES, ANGLE STOPS (INCLUDING DISHWASHER CONNECTIONS), TRAP WRAP, ESCUTCHEON PLATES AS REQUIRED PER FIXTURE INSTALL AND CODE. 4. ALL INSTALLATIONS SHALL COMPLY WITH MANUFACTURER'S INSTRUCTIONS, AND STATE AND LOCAL CODES. 5. PROVIDE BACKFLOW PROTECTION ON FIXTURES AS REQUIRED PER LOCAL CODE. 6. TRIP LEVERS SHALL BE TO WIDE/OPEN SIDE OF TOILET. 7. GOOSE NECK FAUCETS TO BE PROVIDE WITH SPOUT SWIVEL RESTRICTION SETTING OR SHALL BE SET STATIONARY WITHOUT SWIVEL PUMP SCHEDULE DEMO E PLAN MARK MANUFACTURER MODEL N0.(FT) GPM HEAD RPM I ELECTRICAL REMARKS VOLT I PHASE I HP I WATTS CP -1 I GRUNDFOS JUP 15-10 F/FR1 2 1 4 117501 115 1 1 1 1/25 1 25 1 (1) HKUVUL 2 1/2- DEEP DRAIN FAN. KUUIL 3/4 DRAIN 10 SERVICE SINK. (i) INILKGRAL AQUA SIAI SLI IU 11UF ON/ 12U OFF. PUMP SHALL BE ELM IYHL PUMP. (2) COMPLY ICC/ANSI A117.1 FOR ACCESSIBILITY. PLUMBING LEGEND BICARB �CT� CONCENTRATE CNO CONDENSATE I---DCW-- DOMESTIC COLD WATER �DCWR� DOMESTIC COLD WATER RECIRC r ----121F -- DOMESTIC HOT WATER r----120'R----� DOMESTIC HOT WATER RECIRC �GN� GREASE WASTE �MCA� MEDICAL COMPRESSED AIR �G� GAS 02 OXYGEN �RO� REVERSE OSMOSIS �RD� ROOF DRAIN �ORD� OVERFLOW ROOF DRAIN �SO� SAND OIL �SS�-SANITARY SEWER r------V-----� VENT �SCA� SCAVENGER AIR �VAC� VACUUM SUCTION --------- -------y A%%- TYPICAL PIPE ABOVE ON ROOF ---------B%%--------y TYPICAL PIPE BELOW/UNDERGROUND --------- %%---------y SSSS TYPICAL PIPE EXISTING 1� r VALVES FIXTURES ® BALL VALVE II WALL CLEAN OUT GATE VALVE QF FLOOR CLEANOUT GLOBE VALVE AREA DRAIN N CHECK VALVE ® OFLOOR DRAIN APRESSURE REDUCING VALVE (PRV ® OFLOOR SINK FULL COVER IM MEASURE FLOW ® OFLOOR SINK 3/4 COVER TEE UP ® OFLOOR SINK 1/2 COVER =-1 TEE DOWN non GAS METER OFELBOW UP 7-} HOSE BIB C- ELBOW DOWN p OBATH TUB/MOP SINK MISG. 0-o SINK C B POINT OF CONNECTION (POC) FC:82-COMPARTMENT SINK ®DEMO OC-bDRINKING FOUNTAIN/URINAL WASHER BOX q9 ICE BOX Q O WATER CLOSET STACK p O WATER CLOSET GENERAL NOTES: 1. ALL ITEMS CONNECTING TO POTABLE WATER SHALL MEET THE LEAD FREE STANDARD OF .25% OR LESS LEAD. 2. MINIMUM WASTE INVERTS ARE BASED UPON THE STARTED INVERT (BELOW SLAB) WITH PIPES SLOPED PER CODE TO EXIT INVERTS. COORDINATE WITH STRUCTURAL ENGINEER AND CIVIL ENGINEER FOR STRUCTURAL FOOTINGS/BEAMS AND CONNECTION INVERTS. NOTIFY ARCHITECT/ENGINEER IF THERE ARE ANY CONFLICTS PRIOR TO ROUGH -IN. 3. START TRENCHING FOR NEW SANITARY LINE AT FURTHEST FIXTURE (HIGHEST POINT IN SYSTEM) FROM CIVIL CONNECTION POINT TO BUILDING. 4. PLUMBING PLANS REFERENCE FINISHED FLOOR TO FINISHED FLOOR ABOVE. SANITARY SHOWN IS FOR FIXTURES ABOVE UNLESS NOTED OTHERWISE. 5. FIELD VERIFY ALL ROUTING OF PLUMBING LINES WITH OTHER TRADES. FIELD ADJUST ROUTING ACCORDINGLY TO MAKE SYSTEM WORK WITH OTHER TRADES. 6. PROVIDE ASSE1070 MIXING VALVE AT ALL PUBLIC FIXTURES AS REQUIRED PER LOCAL CODE. 7. PROVIDE WATER HAMMER ARRESTORS AT ALL FIXTURES AND EQUIPMENT ON DOMESTIC WATER SYSTEM WITH QUICK CLOSING VALVES. B. PC TO PROVIDE VACUUM BREAKERS AT LOCATIONS WHERE HOSES AND NOZZLES ARE USED, I.E. JANITOR SINKS, BEAUTY SINKS, KITCHEN SPRAYERS, DISHWASHERS, AND BATHS. INSTALL CHECK VALVES ON BOTH COLD AND HOT WATER LINES TO FIXTURE. 9. ALL DRAINAGE LINES 2-1/2" AND UNDER TO BE SLOPED AT 1/4" PER FOOT, 3"-6" TO BE SLOPED AT 1/8" PER FOOT, AND 8" AND OVER TO BE SLOPED AT 1/16" PER FOOT UNLESS NOTED OTHERWISE. 10. ALL SANITARY PIPING BELOW GRADE TO BE MINIMUM 3" UNLESS NOTED OTHERWISE. VERTICAL PIPES LESS THAN 3" SHALL TRANSITION BELOW GRADE AFTER ELBOW. 11. FIELD ROUTE ALL CONDENSATE LINES, T&P VALVES, AND DRAIN VALVES FROM MECHANICAL AND PLUMBING EQUIPMENT TO SANITARY SEWER RECEPTOR OR STORM/GRADE PER LOCAL CODE AND JURISDICTION. 12. REFER TO ARCHITECTURAL DRAWINGS FOR FINAL HEIGHTS AND/OR LOCATIONS OF SHOWER FIXTURES. 13. WATER CLOSETS ON BEAMS OR COLUMNS TO BE OFFSET 18" OFF FINISHED WALL (OFFSET FLANGES NOT ALLOWED). 14. PEX PIPING IS AN APPROVED PIPING MATERIAL FOR DISTRIBUTION TO ALL FIXTURES OFF WATER MAINS. 15. DO NOT SECURE ANY PIPING TO EXPANSION JOINT WALLS. (D) DEMO E EXISTING N NEW AAV AIR ADMITTANCE VALVE AD AREA DRAIN AFF ABOVE FINISH FLOOR AHU AIR HANDLING UNIT B BOILER BE BASEBOARD BF BOOSTER FAN BFP BACKFLOW PREVENTER BT BATH TUB BV BALL VALVE CD CONDENSATE DRAIN CFM CUBIC FEET PER MINUTE CH CHILLER CS CLINICAL SINK CU CONDENSING UNIT CV CHECK VALVE CUH CABINET UNIT HEATER DCW DOMESTIC COLD WATER OF DRINKING FOUNTAIN DHW DOMESTIC HOT WATER DSN DOWN SPOUT NOZZLE EVC EVAPORATIVE COOLER EC ELECTRICAL CONTRACTOR ECO END OF LINE CLEANOUT EDH ELECTRIC DUCT HEATER EF EXHAUST FAN ERU ENERGY RECOVERY UNIT ER EXISTING REMOVED ERR EXISTING REMOVED & RELOCAT EW EMERGENCY EYEWASH EWC ELECTRIC WATER COOLER EWH ELECTRIC WATER HEATER F FURNACE FCO FLOOR/GRADE CLEANOUT FCU FAN COIL UNIT FD FLOOR DRAIN FS FLOOR SINK G GAS GC GENERAL CONTRACTOR GM GAS METER GPH GALLONS PER HOUR GPM GALLONS PER MINUTE GR GAS REGULATOR GUH GAS UNIT HEATER GW GREASE WASTE GWH GAS WATER HEATER HE HOSE BIB HP HEAT PUMP HX HEAT EXCHANGER IM ICE MAKER BOX LAV LAVATORY LS LAUNDRY SINK MAU MAKE-UP AIR UNIT MC MECHANICAL CONTRACTOR MF MEASURE FLOW NIC NOT IN CONTRACT NC NORMALLY CLOSED NO NORMALLY OPEN NTS NOT TO SCALE OA OUTSIDE AIR ORD OVER FLOW ROOF DRAIN P PUMP PC PLUMBING CONTRACTOR PFT PARALLEL FAN TERMINAL PRV PRESSURE REDUCING VALVE PSI POUNDS PER SQUARE INCH PSIG PRESSURE GAUGE RA RETURN AIR RAR RETURN AIR REGISTER RD ROOF DRAIN RE RELOCATE EXISTING RH RADIANT HEATER RTU ROOF TOP UNIT SA SUPPLY AIR SAR SUPPLY AIR REGISTER SF SUPPLY FAN SFT SERIES FAN TERMINAL SH SHOWER SK SINK SO SAND/OIL SS SERVICE SINK T&P TEMPERATURE & PRESSURE TO TRENCH DRAIN TYP TYPICAL UR URINAL VAV VARIABLE AIR VOLUME WT VARI TRAC WB WASHER BOX WC WATER CLOSET/WATER COLUMN WCO WALL CLEANOUT COLUMN City of Wheat Ridge Building Division FqGIYEN &CIATES INC TEa m • EIFCINCAL oNEE9s 735 S. Xenon Ct. #201 Lakewood, Colorado 80228 Ph: 303.716.1270 Fax: 303.716.1272 www.g ivenandassociates.conn Project # 20084 chord,10 09512020 OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.C. 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEVVOOD, CO 80228 t: 303.716.1270 COPYRIGHT: 2020 THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN CAN ONLY BE USED FOR THIS PROJECT. NO OTHER USE OF THIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED VVITHOUTTHE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. # DESCRIPTION DATE PERMIT SET 09/15/2020 CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Project Number: 20019 PLUMBING SPECS SCHEDULES & LEGEND P001 v w \ ■ FIRST FLOOR DEMO PLUMBING PLAN P D 101 4' 2' 0 4' 8' GENERAL NOTES: 1. EXISTING CONDITIONS SHOWN ON PLANS ARE BASED ON BEST INFORMATION AVAILABLE, INCLUDING LIMITED SITE SURVEY CONDUCTED ON 08-2020. PC SHALL FIELD VERIFY ALL EXISTING CONDITIONS ON WHICH NEW WORK IS DEPENDENT, INCLUDING PIPE LOCATION, MATERIAL, SIZE, AND ELEVATION/INVERT PRIOR TO STARTING WORK. DRAWING NOTES: Oj DEMO FIXTURE AND ASSOCIATED PIPING BACK TO MAIN AND CAP. DEMO ELECTRIC WATER HEATER AND ASSOCIATED PIPING BACK TO MAIN AND CAP. O2 DEMO EXISTING 4" SANITARY LINE OUT TO CIVIL. O EXISTING 4" SANITARY LINE FROM SPACE. CONTRACTOR TO FIELD OVERIFY. 4 City of Wheat Ridge Building Division &CIATES INC FqGIYEN lll%1MNIGL s EIFCINCdL e1�EF]IB 735 S. Xenon Ct. #201 Lakewood, Colorado 80228 Ph: 303.716.1270 Fax: 303.716.1272 www.g ivenandassociates.conn Project # 20084 chord,11111111 09512020 OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.C. 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 COPYRIGHT: 2020 THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN CAN ONLY BE USED FOR THIS PROJECT. NO OTHER USE OF THIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUTTHE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. # DESCRIPTION DATE PERMIT SET 09/15/2020 CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Project Number: 20019 FIRST FLOOR DEMO PLUMBING PLAN PD1 01 0 w \ ■ UNDERGROUND PLUMBING PLAN GENERAL NOTES: 1. EXISTING CONDITIONS SHOWN ON PLANS ARE BASED ON BEST INFORMATION AVAILABLE, INCLUDING LIMITED SITE SURVEY CONDUCTED ON 08-2020. PC SHALL FIELD VERIFY ALL EXISTING CONDITIONS ON WHICH NEW WORK IS DEPENDENT, INCLUDING PIPE LOCATION, MATERIAL, SIZE, AND ELEVATION/INVERT PRIOR TO STARTING WORK. 2. DEMO ANY PLUMBING FIXTURES NOT BEING REUSED AND ALL ASSOCIATED PIPING BACK TO MAIN AND CAP. DEMO ANY PIPING NOT BEING REUSED FOR NEW DESIGN. DRAWING NOTES: O1 BEFORE NEW CONSTRUCTION, CONTRACTOR TO DEMO ALL SANITARY PIPING FROM FIXTURES BEING REMOVED. DEMO SANITARY LINE TO MAIN AND CAP IF APPLICABLE. CONTRACTOR TO MAKE ADJUSTMENTS AS NEEDED. O CONNECT NEW SANITARY LINE OF EQUAL OR LESS SIZE INTO EXISTING SANITARY LINE. CONTRACTOR TO FIELD VERIFY SIZE AND INVERT BEFORE CONNECITON. O EXISTING 4" SANITARY LINE OUT TO CIVIL. O EXISTING 4" SANITARY LINE FROM SPACE. CONTRACTOR TO FIELD VERIFY. City of Wheat Ridge Building Division &CIATES INC FqGIYEN lll%1MNIGL s EIFCINCdL e1.EF]IB 735 S. Xenon Ct. #201 Lakewood, Colorado 80228 Ph: 303.716.1270 Fax: 303.716.1272 www.g ivenandassociates.com Project # 20084 chord,11111111 09512020 OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.C. 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 COPYRIGHT: 2020 THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN CAN ONLY BE USED FOR THIS PROJECT. NO OTHER USE OF THIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUTTHE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. # DESCRIPTION DATE PERMIT SET 09/15/2020 CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Project Number: 20019 UNDERGROUND PLUMBING PLAN Pi 00 w \ ■ FIRST FLOOR PLUMBING PLAN P 101 4' 2' 0 4' 8' GENERAL NOTES: 1. EXISTING CONDITIONS SHOWN ON PLANS ARE BASED ON BEST INFORMATION AVAILABLE, INCLUDING LIMITED SITE SURVEY CONDUCTED ON 08-2020. PC SHALL FIELD VERIFY ALL EXISTING CONDITIONS ON WHICH NEW WORK IS DEPENDENT, INCLUDING PIPE LOCATION, MATERIAL, SIZE, AND ELEVATION/INVERT PRIOR TO STARTING WORK. 2. DEMO ANY PLUMBING FIXTURES NOT BEING REUSED AND ALL ASSOCIATED PIPING BACK TO MAIN AND CAP. DEMO ANY PIPING NOT BEING REUSED FOR NEW DESIGN. DRAWING NOTES: O1 CONNECT NEW DOMESTIC COLD WATER LINE TO EXISTING DOMESTIC COLD WATER LINE OF EQUAL OR LARGER SIZE. O2 CONNECT NEW DOMESTIC 1207 HOT WATER LINE TO EXISTING OF EQUAL OR LARGER SIZE. O CONNECT NEW VENT LINE TO EXISTING OF EQUAL OR LARGER SIZE. O4 1/2" DCW, DHW, AND 2" VENT DOWN TO SERVE FIXTURE. O 3/4" DCW AND 2" VENT DOWN TO SERVE FIXTURE. O6 1/2" DCW DOWN TO SERVE FIXTURE. O 1/2" DCW AND 3/4" DHW DOWN IN WALL TO KS -1 LOCATION. OFFSET 1/2' DCW AND 1/2" DHW TO KS -1, 1/2" DHW TO DISHWASHER CONNECTION. EXTEND DRAIN LINE TO SANITARY. O EXISTING 3" VENT THROUGH ROOF. CONTRACTOR TO FIELD VERIFY. O REPLACE PREVIOUS 1" DOMESTIC COLD WATER LINE WITH NEW 1-1/4" DOMESTIC COLD WATER. CONNECT INTO EXISTING 1-1/2" DOMESTIC COLD WATER LINE. CONTRACTOR TO FIELD VERIFY LOCATION BEFORE WORK. TOTAL NEW CWSFU LOAD FROM EXISTING AND NEW FIXTURES ADDED= 27.75. 10 CONNECT EXISTING DOMESTIC WATER LINE OF EQUAL OR LESS SIZE INTO NEW SHOWN ON PLAN. 11 ROUTE NEW 1" DHW DOWN IN WALL AND CONNECT EXISTING 3/4" DHW SERVING EXAM SINKS INTO NEW 1" DHW LINE, AFTER CONNECTIONS, CONNECT NEW 3/4" DHW INTO EXISTING 3/4" DHW LINE AS SHOWN ON PLANS. 12 1/2" DCW AND 1/2" DHW DOWN IN WALL TO SERVE LAVATORY. BRANCH 1/2" DCW TO CONNECT INTO NEW DRINKING FOUNTAIN. PROVIDE 2" VENT TO SERVE BOTH FIXTURES. REFERENCE DETAIL 1/P601 FOR HOT WATER ROUTING FOR LAVATORY. 13 EXISTING PIPING. CONTRACTOR TO VERIFY SIZE, MATERIAL, AND LOCATION BEFORE CONSTRUCTION. DEMO ANY PIPING NOT APPLICABLE FOR NEW CONSTRUCTION. 14 CONNECT EXISTING 3/4" DHW INTO NEW 3/4" HWR. PROVIDE BALANCING VALVE AT POINT OF CONNECTION. 15 SALVAGE EXISTING ELECTRIC WATER HEATER SERVING FORMER ADJACENT TENANT SPACE. OWNER TO RELOCATE WATER HEATER TO THE NEW ADJACENT TENANT SPACE. 16 NEW 65 GAL ELECTRIC WATER HEATER. ROUTE T&P RELIEF TO SERVICE SINK. REFERENCE SCHEDULES AND DETAILS FOR MORE INFORMATION. 17 EXISTING 1-1/2" BRANCHED DCW SERVING TENANT SPACE. CONTRACTOR TO FIELD VERIFY LOCATION AND SIZE. 18 RELOCATED EXISTING SINK. REFER TO ARCHITECTURAL PLAN FOR MORE INFORMATION. city of Wheat Ridge Building Division &CIATES INC FqGIYEN lll%1MNIGL s EIFCINCdL e1�EF]IB 735 S. Xenon Ct. #201 Lakewood, Colorado 80228 Ph: 303.716.1270 Fax: 303.716.1272 www.g ivenandassociates.conn Project # 20084 chord,11111111 09512020 OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.C. 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 COPYRIGHT: 2020 THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN CAN ONLY BE USED FOR THIS PROJECT. NO OTHER USE OF THIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUTTHE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. # DESCRIPTION DATE PERMIT SET 09/15/2020 CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Project Number: 20019 FIRST FLOOR PLUMBING PLAN P101 LAV -1 PROVIDE CLEANOUTS PER 2018 IPC 708 /\ s / \ 12" V \ 2"VI \\ "V SK2 I 3" SS \ / / / 2" V / / / / / \ \ / \ 2 V/ / \2.. V � KS -1 \ I WB -1 12.. V I I SS—1 3" SS SANITARY ISOMETRIC r ­R City of Wheat Ridge Building Division &CIATES INC FqGIYEN lll%1MNIGL sEIFCINCdL e1�EF]IB 735 S. Xenon Ct. #201 Lakewood, Colorado 80228 Ph: 303.716.1270 Fax: 303.716.1272 www.g ivenandassociates.conn Project # 20084 chord,11111111 09512020 OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.C. 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 COPYRIGHT: 2020 THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN CAN ONLY BE USED FOR THIS PROJECT. NO OTHER USE OF THIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUTTHE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. # DESCRIPTION DATE PERMIT SET 09/15/2020 CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Project Number: 20019 PLUMBING ISOMETRICS P501 STRAINER WITH HOSE END VALVE & CAP (TYPICAL) P601 TO TIME CLOCK POWER PRESSURE GAUGE (TYPICAL) I�I 1 INLINE PUMP WITH INTEGRAL T UNION STAT (TYPICAL) NOTE: INDEPENDENTLY SUPPORT PUMP & PIPING. GRISWOLD VENTURI FLOW METER FLEXIBLE OR EQUAL FOR TESTING ONLY. CONNECTION (100" GAUGE) (TYPICAL) 110' LOOP: 140 LOOP: VALVE (TYPICAL) INLINE AQUASTAT PUMP DIAGRAM CONTINUOUS HOT WATER LOOP FULL SIZE. SEE FLOOR PLAN FOR ROUTING AND SIZE. N.T.S. CONTINUOUS HOT WATER LOOP FULL SIZE. SEE — f1120" ROUTING PLAN FOR ROUTING AND SIZE. 1 1 EXTEND TO 1 1 SINK FAUCET b i 1 b 1 CONNECT 1/2" DHW WITHIN 24" OF STOP. IECC C404.5.1 ANGLE STOP TYPICAL. ASSE 1070 MIXING VALVE. BALL VALVE (TYPICAL) PUBLIC RESTROOM FIXTUF FIXTURE REQUIREMENTS WITH CONNECTION LENGTH NOT EXCEEDING IECC C404.5.1. RE: ARCHITECTURAL DWG'S FOR EXACT LOCATION OF EQUIPMENT THAT REQUIRES HOT WATER. PROVIDE 1/2" PIPE TO HOT N CONNECTION AT PUBLIC FIX 1" DHW (120'F) TO SPACE 3/4" DHWR FROM SPACE EXPANSION 1 TANK AMT ROL 1 MODEL ST -12 VALVDIJ11ARE CHGEO ROUTED TO RVICE SINK ELECTRIC WATER HEATER DRAIN VALVE 3/4"DCW FROM BACKFLOW DRAIN PAN Provide support per manufacturer specificatiuons 1" DRAIN TO FLOOR SINK ELECTRIC WATER HEATER DIAGRAM P601 N.T.S. WALL BINET COUNTER TOP DRAIN SUPPORT STRAP STRAINER FLUSH WITH FLOOR ADJUSTABLE DRAIN HEAD TRAP GUARD ASSE 1072 APPROVED. PIPE TYPICAL HOT WATER TOFLOOR DRAIN W/ PUBLIC FIXTURE DETAIL OTRAP GUARD DETAIL P 6 01 N.T.S. P 6 01 N.T.S. city of Wheat Ridge Building Division &CIATES INC FqGIYEN IEaulnrx ! EIFCINCdL e1�EF]IB 735 S. Xenon Ct. #201 Lakewood, Colorado 80228 Ph: 303.716.1270 Fax: 303.716.1272 www.g ivenandassociates.conn Project # 20084 chord,11111111 09512020 OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.C. 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 COPYRIGHT: 2020 THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN CAN ONLY BE USED FOR THIS PROJECT. NO OTHER USE OF THIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUTTHE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. # DESCRIPTION DATE PERMIT SET 09/15/2020 CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Project Number: 20019 PLUMBING DETAILS P601 GENERAL PROJECT NOTES 1. COORDINATE INTERIOR LIGHTING LAYOUT, FIXTURE LOCATIONS AND MOUNTING HEIGHTS WITH ARCHITECT DRAWINGS BY OTHERS. PROVIDE ALL FINAL CONNECTIONS AND CONTROLS AS REQUIRED FOR A COMPLETE AND OPERATIONAL SYSTEM. 2. COORDINATE MECHANICAL EQUIPMENT INSTALLATION REQUIREMENTS WITH THE MECHANICAL CONTRACTOR AND PROVIDE ALL FINAL CONNECTIONS AS REQUIRED FOR A COMPLETE AND OPERATIONAL SYSTEM. 3. COORDINATE PLUMBING EQUIPMENT INSTALLATION REQUIREMENTS WITH THE PLUMBING CONTRACTOR AND PROVIDE ALL FINAL CONNECTIONS AS REQUIRED FOR A COMPLETE AND OPERATIONAL SYSTEM. ABBREVIATIONS X x" ELECTRICAL SPECIFICATIONS 1. BASIC REQUIREMENTS B. INFORMATION ON EXISTING ELECTRICAL EQUIPMENT, PANELS WIRING, AND A. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH CURRENT LOCAL AFG DEVICES INDICATED AS BEING REUSED IN THIS PROJECT IS AS ACCURATE AG CODES, ORDINANCES, AND REGULATIONS, NATIONAL ELECTRIC CODE, AHU AS COULD BE OBTAINED FROM A CURSORY SURVEY. THE ACCURACY OF AIC LOCAL HEALTH DEPARTMENT REGULATIONS, AND APPUCABLE NFPA CODES. AL THIS INFORMATION IS NOT GUARANTEED AND IS FOR THE INFORMATIONAL C PAY FOR ALL FEES AND PERMITS AS ARE NECESSARY FOR THE CLG GUIDANCE OF THE PREDICATIONS AND LOCAL CODES. THIS CONTRACTOR CU COMPLETE INSTALLATION OF THE ELECTRICAL SYSTEMS INCLUDING UTIUTY CKT SHALL MAKE NECESSARY CORRECTIONS TO EXISTING SYSTEMS AS ARE CT CHARGES. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH DYR REQUIRED FOR A COMPLETE AND OPERATIONAL ELECTRICAL SYSTEM. DW LOCAL UTILITY REQUIREMENTS. (E) SHOULD INSUFFICIENT CAPACITY, CAPABILITY, OR INCOMPATIBLE E.C. ELECTRICAL CONTRACTOR EF ELECTRICAL TERMINATIONS BE PRESENT THIS CONTRACTOR SHALL SUBMIT B. PROJECT SHALL INCLUDE ALL ITEMS NECESSARY FOR COMPLETE AND EWC THE NOTED DISCREPANCIES TO THE ARCHITECT FOR DIRECTION PRIOR TO EXP FULLY OPERATIONAL TENANT AND BUILDING ELECTRICAL SYSTEMS. MAKE G ROUGH—IN OR PROCEEDING WITH THE WORK. GO CONNECTIONS TO AND EXTEND SYSTEMS INSTALLED BY OTHERS AND/OR GFI GROUND FAULT CIRCUIT INTERUPTER HD FURNISHED BY OTHERS. PROVIDE ACCESSORIES AND INCIDENTAL ITEMS C. ELECTRICAL SERVICE TO THE BUILDING MAY BE INTERRUPTED ONLY AT A IG REQUIRED FOR COMPLETE AND FULLY OPERATIONAL SYSTEMS MCR TIME COORDINATED WITH AND APPROVED BY THE BUILDING MANAGER. IN MDP W WHETHER OR NOT SPECIFICALLY SPECIFIED AND/OR SHOWN ON THE MH GENERAL THIS WILL BE ALLOWED DURING OFF HOURS AND ON WEEKENDS MTD PLANS. MVOLT FOR LIMITED PERIODS OF TIME. C. DO NOT SCALE FROM THESE DRAWINGS. REFER TO ARCHITECTURAL OR OVN OVEN N CIVIL DRAWINGS BY OTHERS FOR DIMENSIONS AND FOR ESTIMATING 4. BASIC MATERIALS NL DISTANCES. THESE DRAWINGS ARE TO BE READ IN CONJUNCTION WITH A. RACEWAYS AND FITTINGS: RACEWAYS EMBEDDED IN CONCRETE OR PH ALL RELEVANT DRAWINGS AND SPECIFICATIONS RELATING TO THE JOB (R) MASONRY WALLS SHALL BE IN IMC; IN HOLLOW NON MASONRY WALLS REF WETHER OR NOT INDICATED ON THESE DRAWINGS. RNG AND ABOVE CEILINGS SHALL BE EMT OR MC CABLE; RACEWAY EXPOSED D. ANY SCALE, DIMENSION OR QUANTITIES SHOWN ON THE DRAWINGS ARE TS TO SEVERE PHYSICAL DAMAGE SHALL BE RIGID GALVANIZED STEEL; AND TTB FOR ENGINEERING CALCULATION PURPOSES ONLY. THE ELECTRICAL UG RACEWAYS BETWEEN VIBRATING EQUIPMENT SHALL BE FLEXIBLE METALUC V CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR ESTIMATING AND VA CONDUIT. MC CABLE IS NOT ALLOWED FOR BRANCH CIRCUIT HOMERUN VFD DETERMINING ALL DISTANCES AND QUANTITIES RELATED THE PROJECT. W CONDUITS FROM LAST DEVICE OR JUNCTION BOX TO PANELBOARD. I WG S AND VERIFY REFER TO ARCHITECTURAL OR CIVIL DRAWINGS BY OTHERS WP CONDUITS IN CONTACT WITH BARE EARTH SHALL BE SCHEDULE 40 PVC. WSH EXISTING CONDITIONS ON SITE FOR ALL ESTIMATING PURPOSES. B. CONDUCTORS: ALL CONDUCTORS SHALL BE COPPER RATED FOR 600 E. COORDINATE WITH OTHER TRADES FOR A COORDINATED INSTALLATION VOLTS AND HAVE MINIMUM 90 DEGREES C INSULATION. MINIMUM SIZE SINGLE PUSH BUTTON WITHIN THE AVAILABLE SPACE. WHERE CROWDED CONDITIONS EXIST, B SHALL BE #12 AWG. ALL BUILDING WIRING SHALL BE THHN/THWN. PREPARE COORDINATION DRAWINGS SHOWING ALL TRADE CONFLICTS AND EXTERIOR WIRING SHALL BE XHHW. ALL WIRES ON THE SA E LEG OR SUBMIT TO ARCHITECT FOR APPROVAL AND DIRECTION PRIOR TO PHASE SHALL HAVE THE SAME COLOR CODE. ALUMINUM IS PERMITTED ROUGH—IN AND/OR INSTALLATION. RELOCATION OF OUTLETS AND/OR FOR FEEDERS RATED AT 100 AMPERES OR MORE (#1/0 AWG DEVICES MADE PRIOR TO ROUGH—IN SHALL BE DONE AT NO ADDITIONAL MINIMUM). COST. C. INCREASE CONDUCTOR SIZE TO MAINTAIN A MAXIMUM VOLTAGE DROP OF F. ALL WORK SHALL BE PERFORMED BY PROPERLY LICENSED ELECTRICIANS 3% ON FEEDERS, 3% ON BRANCH CIRCUITS AND 5% COMBINED ON BOTH OR UNDER THEIR DIRECT SUPERVISION. ALL MATERIALS AND EQUIPMENT FEEDERS AND BRANCH CIRCUITS TO THE FARTHEST OUTLET. SHALL MEET THE REQUIREMENTS OF THE APPLICABLE STANDARDS OF UL D. PROVIDE SEPARATE (DEDICATED) NEUTRAL CONDUCTOR FOR EACH AND SHALL BEAR THE UL LABEL AS EVIDENCE THAT THE MATERIAL DEDICATED EQUIPMENT CIRCUIT; SHARED NEUTRAL CONDUCTORS ARE NOT AND/OR EQUIPMENT MEETS THIS REQUIREMENT. PERMITTED FOR DEDICATED CIRCUITS. WHERE PERMITTED, SHARED G. SUBMIT MANUFACTURERS LITERATURE (SHOP DRAWINGS) FOR RACEWAYS NEUTRAL CONDUCTORS SHALL BE COPPER #10 AWG MINIMUM. PROVIDE AND FITTINGS, BOXES, WIRE, CABLES, WIRING DEVICES, NAME PLATES, BREAKER TIES IN PANEL FOR ALL MULTIWIRE BRANCH CIRCUITS WITH LEGEND PLATES, LABELS, PANELBOARDS, FUSES, CIRCUIT BREAKERS, SHARED NEUTRALS. SWITCH GEAR, AND SAFETY SWITCHES. SUBMITTAL SHALL BEAR THE E. PROVIDE METALUC OUTLET, PULL AND JUNCTION BOXES AS REQUIRED. APPROVAL OF THE GENERAL CONTRACTOR FOR COMPLIANCE WITH ALL POWER, CONTROL, OR INSTRUMENTATION, WIRING GREATER THAN 24 COORDINATION AND THESE SPECIFICATIONS PRIOR TO SUBMITTAL TO VOLTS SHALL BE IN CONDUIT. TYPE NM, NMC, OR NMS CABLES ARE ARCHITECT AND/OR HIS AGENCIES. PERMITTED WHERE ALLOWED BY LOCAL AUTHORITY HAVING JURISDICTION H. ALL SWITCH BOARDS, DISTRIBUTION BOARDS, PANEBOARDS, DISCONNECT AND APPROVED BY OWNER. CONTRACTOR SHALL BE RESPONSIBLE FOR SWITCHES, TRANSFORMERS AND SIMILAR ELECTRICAL EQUIPMENT SHALL BE ALL CONSTRUCTION CHANGES DUE TO THESE CABLES USE IN UEU OF PROVIDED WITH ENGRAVED PLASTIC—LAMINATE LABELS INDICATING THE EQUIPMENT CONDUIT. LOW VOLTAGE WIRING MAY BE PLENUM RATED IN ACCESSIBLE NAME SPECIFIED ON THE PUNS OR THE LOAD SERVED BY THE EQUIPMENT. LOCATIONS CONCEALED FROM FINISHED AREAS AS APPROVED BY LOCAL ALL PANELBOARDS SHALL BE PROVIDED WITH REMOVEABLE, TYPED PANEL AUTHORITIES. SCHEUDLES WITH CLEAR PLASTIC COVERS AFFIXED TO THE FACE OR INSIDE OF THE PANEL DOOR. PANEL SCHEDULES SHALL CLEARLY INDICATE THE SPECIFIC F. PROVIDE RECEPTACLES, GFI RECEPTACLES, SPECIAL PURPOSE LOAD SERVED BY EACH INDIVIDUAL CIRCUIT BREAKER OR DISCONNECT SWITCH RECEPTACLES AND SWITCHES OF ONE MANUFACTURER. PROVIDE AND SHALL REFLECT THE FINAL, AS—BUILT CONDITIONS AT COMPLETION OF COMMERCIAL GRADE DIMMERS FOR CIRCUITS INDICATED. STAB—IN WORK. THE IDENTIFICATION SHALL INCLUDE SUFFICIENT DETAIL TO ALLOW EACH CONNECTION WILL NOT BE APPROVED. SEE ARCHITECTURAL DRAWINGS CIRCUIT TO BE DISTINGUISHED FROM ALL OTHERS. SPARE POSITIONS SHALL BE FOR SPECIAL MOUNTING LOCATIONS, ORIENTATION, AND COLORS. LIBELED ACCORDINGLY. CONFIRM RECEPTACLE, SPECIAL RECEPTACLE AND SWITCH MOUNTING I. CONTRACTOR SHALL THOROUGHLY REVIEW THE PLANS AND SPECIFICATIONS HEIGHT AND ORIENTATION WITH ARCHITECT PRIOR TO ROUGH—IN. WHERE OF ALL DIVISIONS AND TRADES, ESPECIALLY THE ARCHITECTURAL NEW OUTLETS AND DEVICES ARE INSTALLED, MAINTAIN ADA MOUNTING DRAWINGS. ELECTRICAL REQUIREMENTS OF OTHER TRADES AND DIVISIONS HEIGHTS AND REQUIREMENTS UNLESS SPECIFICALLY DIRECTED OTHERWISE. INCLUDING PRODUCTS SPECIFIED, MOUNTING INSTRUCTIONS, AND MATERIAL G. PANELBOARDS AND SAFETY SWITCHES SHALL BE OF ONE MANUFACTURER SELECTIONS SHALL BE FURNISHED AND INSTALLED BY THIS CONTRACTOR. AND SHALL BE COMPLETE WITH PROTECTIVE DEVICES, ENCLOSURES, IF A CONFLICT EXISTS, CONTRACTOR SHALL OBTAIN A CLARIFICATION AND BUSSES, GROUNDS, ISOLATED GROUND BUS, AND NEUTRAL BARS AS DIRECTIONS FROM THE ARCHITECT PRIOR TO ROUGH IN OR PROCEEDING REQUIRED. WITH THE WORK. H. PROVIDE ARC FLASH HAZARD WARNING LABELS ON ALL ELECTRICAL J. FURNISHED EQUIPMENT. EQUIPMENT PER NEC 110.16. a. MAKE FINAL CONNECTIONS TO FURNISHED EQUIPMENT AS REQUIRED. b. RECEIVE AND COMPLETELY INSTALL FURNISHED EQUIPMENT, 5. GROUNDING MATERIALS, AND APPARATUS FURNISHED BY OTHERS FOR INSTALLATION OF A COMPLETE ELECTRICAL SYSTEM. A. PROVIDE COPPER GROUNDING CONDUCTORS AND COPPER CLAD STEEL c. REVIEW CONSTRUCTION DOCUMENTS AND INSTALLATION INSTRUCTIONS MADE ELECTRODES IN ACCORDANCE WITH THE NEC. BARE COPPER OR FOR MATERIALS AND EQUIPMENT FURNISHED FOR INSTALLATION BY GREEN INSULATED WIRE IS ACCEPTABLE. THIS CONTRACTOR. INSTALL ALL EQUIPMENT AND APPARATUS IN B. ALL EQUIPMENT SHALL BE CONTINUOUSLY GROUNDED. AN EQUIPMENT ACCORDANCE WITH MANUFACTURERS REQUIREMENTS AND SUGGESTED GROUNDING CONDUCTOR IS TO BE INSTALLED IN ALL FEEDER AND PRACTICES, PROVIDE SUPPLEMENTAL AND INCIDENTAL MATERIALS BRANCH CIRCUITS. INCLUDING CORDS, PLUGS, AND RECEPTACLES AS MAY BE REQUIRED FOR A COMPLETE AND FULLY OPERATIONAL SYSTEM. d. CONFIRM ALL CONNECTION REQUIREMENTS AND ROUGH—IN 6. LIGHTING CONDITIONS PRIOR TO INSTALLATION. CERTAIN DATA IS GIVEN BUT A. PROVIDE ALL ACCESSORIES REQUIRED FOR A COMPLETE AND OPERABLE NOT GUARANTEED. PROVIDE ROUGH—IN AND FINAL TERMINATION SYSTEM. FOR RECESSED FIXTURES, PROVIDE PLASTER FRAMES AND INCLUDING APPROPRIATE PLUGS AND DISCONNECTS AS MAY BE FLANGES SUITABLE FOR CEIUNG. CLEAN AND SERVICE FIXTURES. REQUIRED. PREPARE A DETAILED ROUGH—IN DRAWING FOR PROVIDE ACCESSORIES AND INCIDENTAL ITEMS AS REQUIRED FOR APPROVAL PRIOR TO ROUGH—IN. FIXTURES FURNISHED BY OTHERS FOR INSTALLATION. H. CONFIRM ACTUAL VOLTAGES, PHASE AND CHARACTERISTICS OF EXISTING B. FINAL LOCATION OF ALL FIXTURES SHALL BE AS INDICATED ON EQUIPMENT AND APPARATUS AND EQUIPMENT AND APPARATUS FURNISHED ARCHITECTURAL REFLECTED CEILING PLANS AND/OR ELEVATIONS AND BY TENANT, OTHER TRADES, AND OR DIVISIONS. CONFIRM PRIOR TO DETAILS. ROUGH—IN. IF DISCREPANCIES A E NOTED TO THE INSTRUCTIONS OF C. INSTALL ACCESSORIES AND MODIFY FIXTURES AS REQUIRED FOR THESE PLANS AND SPECIFICATIONS, SUBMIT THE NOTED DISCREPANCIES COMPLIANCE WITH REQUIREMENTS OF LOCAL DEPARTMENT OF HEALTH. TO THE ARCHITECT FOR DIRECTION PRIOR TO ROUGH—N OR PROCEEDING OBTAIN ARCHITECTURAL APPROVAL FOR ANY SUBSTITUTION OR WITH THE WORK. MODIFICATION TO FIXTURES GIVEN. I. ALL WORK IN FINISHED AREAS SHALL BE CONCEALED UNLESS D. PROVIDE TENTING OR OTHER SUITABLE MEANS TO KEEP NON—IC RATED SPECIFICALLY NOTED AS EXPOSED ON THE PLANS. PRIOR INSTALLATION ANY EXPOSED WORK THIS CONTRACTOR SHALL VERIFY A FIXTURES A MINIMUM OF 3" OR MANUFACTURER REQUIRED DISTANCE ( ) R AND OBTAIN ARCHITECTURAL APPROVAL OF LOCATION AND EXTENT. FROM INSULATION. J. UNLESS OTHERWISE SPECIFIED ALL OUTLETS ARE 18" AFF. IF OUTLET IS E. ALL EXIT SIGNS AND EMERGENCY LIGHTING UNITS SHALL BE WIRED AHEAD SPECIFIED UNDER OR ABOVE COUNTER, CONFIRM HEIGHT WITH ARCHITECT. OF ANY CONTROL DEVICES, FED FROM AN UNSWITCHED CIRCUIT. K. COORDINATE WITH MECHANICAL AND PLUMBING ENGINEERED DRAWINGS AND PROVIDE ELECTRICAL CONNECTIONS FOR ALL EQUIPMENT AS 7. TELEPHONE/DATA PROVISIONS SCHEDULED, INCLUDING BUT NOT LIMITED TO ALL HVAC EQUIPMENT, A. INSTALL OUTLET BOX WITH CONDUIT TO ABOVE THE CEILING. INSTALL PUMPS, WATER HEATERS, FIRE SMOKE DAMPERS, ETC. CABINET AND/OR FIXTURE OUTLETS IN COORDINATION WITH L. PROVIDE FIRE STOPPING FOR PENETRATIONS OF ALL CONDUIT, SLEEVES, ARCHITECTURAL AND MILLWORK DETAILS WITH CONDUITS OR RACEWAYS TO WIRING AND CABLES THROUGH FIRE RATED WALLS, FLOORS AND SHAFTS ABOVE NEW FINISHED CEILING. IN ACCORDANCE WITH UL LISTED FIRE RATED ASSEMBUES TO MAINTAIN THE RATING OF THE WALL, FLOOR OR SHAFT BEING PENETRATED. B. PROVIDE PULL BOXES WITH PULL WIRE ROPE IN ALL OUTLETS. (ROPE) C. PROVIDE COVER PLATES FOR ALL OUTLETS. COLOR SELECTED BY ARCHITECT. CONFIRM ALL MOUNTING HEIGHTS AND ORIENTATIONS WITH 2. ELECTRICAL SERVICE ARCHITECT PRIOR TO ROUGH—IN. A. EXISTING 208Y/120 VOLT, 3 PHASE, 4 WIRE ELECTRICAL SERVICE TO REMAIN. S. FIRE ALARM SYSTEM A. FIRE ALARM SYSTEM DESIGN SHALL BE A DEFERRED SUBMITTAL BY 3. DEMOLITION AND CONTINUITY OF SERVICE OTHERS, SHALL BE DESIGNED, SIGNED AND SEALED BY A FIRE ALARM A. ALL UNUSED ELECTRICAL RACEWAYS, DEVICES, DEVICE APPUCATIONS, WIRE PROFESSIONAL AND SHALL BE APPROVED BY THE LOCAL FIRE DISTRICT. AND CABLE LOCATED IN THE AREA TO BE RENOVATED SHALL BE B. E.C. SHALL COORDINATE WITH THE FIRE ALARM SUB—CONTRACTOR TO REMOVED BACK TO THEIR EXISTING SOURCE PANELBOARD. CONTRACTOR PROVIDE AND INSTALL A COMPLETE FIRE ALARM SYSTEM INCLUDING ALL SHALL MAINTAIN THE CONTINUITY OF ALL EXISTING BUILDING SYSTEMS IN HORN/STROBE DEVICES, SMOKE DETECTORS, DUCT SMOKE DETECTORS, THE REMAINING TENANT SPACE INCLUDING PANEL DISTRIBUTION AND HEAT DEFECTORS, PULL STATIONS, ETC. AS REQUIRED BY CODE. UGHTING SYSTEMS LOCATED IN THE TENANT OR RUNNING THROUGH THE TENANT SPACE. RELOCATE OUTLETS, CONDUITS, WIRING, BOXES, ETC. AS C. EXTEND AND CONNECT THE NEW FIRE ALARM APPARATUS TO THE NECESSARY ENSURE THAT INDIVIDUAL BRANCH CIRCUITS ARE NOT EXISTING BUILDING FIRE ALARM SYSTEM, WHERE AVAILABLE AND SUITABLE W EEN TENANT SPACES. SHARED BETWEEN FOR REUSE AS DETERMINED BY THE FIRE ALARM VENDOR. INSTALLATION SHALL BE BY A TRAINED AND LICENSED CONTRACTOR OF THE EXISTING EQUIPMENT MANUFACTURER. —END— GENERAL PROJECT NOTES 1. COORDINATE INTERIOR LIGHTING LAYOUT, FIXTURE LOCATIONS AND MOUNTING HEIGHTS WITH ARCHITECT DRAWINGS BY OTHERS. PROVIDE ALL FINAL CONNECTIONS AND CONTROLS AS REQUIRED FOR A COMPLETE AND OPERATIONAL SYSTEM. 2. COORDINATE MECHANICAL EQUIPMENT INSTALLATION REQUIREMENTS WITH THE MECHANICAL CONTRACTOR AND PROVIDE ALL FINAL CONNECTIONS AS REQUIRED FOR A COMPLETE AND OPERATIONAL SYSTEM. 3. COORDINATE PLUMBING EQUIPMENT INSTALLATION REQUIREMENTS WITH THE PLUMBING CONTRACTOR AND PROVIDE ALL FINAL CONNECTIONS AS REQUIRED FOR A COMPLETE AND OPERATIONAL SYSTEM. ABBREVIATIONS X x" MOUNTING HEIGHT A / AMP AMPERE AC ABOVE COUNTER AFF ABOVE FINISHED FLOOR AFG ABOVE FINISHED GRADE AG ABOVE COUNTER GFI DEVICE AHU AIR HANDLING UNIT AIC FAULT CURRENT CAPACITY AL ALUMINUM C CONDUIT CLG CEILING CU COPPER CKT CIRCUIT CT CURRENT TRANSFORMER DYR DRYER DW DISHWASHER (E) EXISTING E.C. ELECTRICAL CONTRACTOR EF EXHAUST FAN EM EMERGENGY EWC ELECTRIC WATER COOLER EXP EXPLOSION PROOF G GROUND GO GARBAGE DISPOSER GFI GROUND FAULT CIRCUIT INTERUPTER HD EXHAUST HOOD HP HORSEPOWER IG ISOLATED GROUND MCR MICROWAVE MDP MAIN DISTRIBUTION PANELBOARD MH MANHOLE MTD MOUNTED MVOLT MULTI -VOLTAGE OCPD OVERCURRENT PROTECTION DEVICE OVN OVEN N NEUTRAL NIC NOT IN CONTRACT NL NITE LIGHTING (24/7) PART PARTIAL PH PHASE (R) RELOCATE REF REFRIGERATOR RNG RANGE RTU ROOF TOP UNIT TS THERMAL SWITCH TTB TELEPHONE TERMINAL BOARD UG UNDERGROUND V VOLT VA VOLT-AMPERE VFD VARIABLE FREQUENCY DRIVE W WALL WG WEATHERPROOF GFI WP WEATHERPROOF WSH WASHER CODES AND DESIGN CRITERIA JURISDICTION: WHEATRIDGE, CO ELECTRICAL CODE: 2020 NEC ENERGY CODE: 2018 IECC " DISTANCES ARE ESTIMATED. «« VOLTAGE DROP IS CALCULATED FROM THE SERVICE ENTRANCE TO THE REFERENCED POINT. T SIMPLEX RECEPTACLE qp DUPLEX RECEPTACLE (WALL MTD) ® DUPLEX RECEPTACLE (FLOOR MTD) ® DUPLEX RECEPTACLE (CEILING MTD) qp DUPLEX (SWITCHED) 4-PLEX RECEPTACLE (WALL MTD) ® 4-PLEX RECEPTACLE (FLOOR MTD) ® 4-PLEX RECEPTACLE (CEILING MTD) Z SPECIAL PURPOSE RECEPTACLE ® SPECIAL PURPOSE RECEPTACLE (FLOOR MTD) JUNCTION BOX (WALL MTD) O JUNCTION BOX (FLOOR MTD) JUNCTION BOX (CEILING MTD) V DATA OUTLET DATA OUTLET ® (FLOOR MTD) - TELEPHONE OUTLET (WALL MTD) V TELEPHONE/DATA OUTLET ® TELEPHONE/DATA/DUPLEX OUTLET (FLOOR MTD) $ SWITCH $� 3 -WAY SWITCH $4 4 -WAY SWITCH $B DIMMER SWITCH $T THERMAL OVERLOAD SWITCH a CONTROLLING OUTLET OR $ FIXTURE ON SWITCH LEG $x KEYED SWITCH $ov MANUAL OVERRIDE SWITCH PC PHOTOCELL OCCUPANCY SENSOR (WALL MTD) ® WITH (1) INTEGERAL SWITCH OCCUPANCY SENSOR (WALL MTD) ® WITH (2) INTEGERAL SWITCHES ® OCCUPANCY SENSOR (CEILING MTD) OCCUPANCY SENSOR (CEILING MTD) ® WITH CORRIDOR SENSING PATTERN ® DIGITAL LIGHTING CONTROL SOFT SWITCH 'x' REFERS TO CONTROL SCHEDULE ID# EXISTING PRIMARY EXISTING UTILITY TRANSFORMER 208/12OV, 30 300KVA IN] (E) PANEL 'At 2' 208/120V 30, 4W 200A MLO ELECTRICAL SYMBOL LEGEND DOWNUGHT SHORT CIRCUIT CALCULATIONS Isc 11 DIST %VD FO 52,000 A — — F1 35,228 A 100 1.29% F2 29,097 A 10 0.15% F3 6,494 A 11 200 2.92% 74 5,095 A 11 30 0.46% " DISTANCES ARE ESTIMATED. «« VOLTAGE DROP IS CALCULATED FROM THE SERVICE ENTRANCE TO THE REFERENCED POINT. T SIMPLEX RECEPTACLE qp DUPLEX RECEPTACLE (WALL MTD) ® DUPLEX RECEPTACLE (FLOOR MTD) ® DUPLEX RECEPTACLE (CEILING MTD) qp DUPLEX (SWITCHED) 4-PLEX RECEPTACLE (WALL MTD) ® 4-PLEX RECEPTACLE (FLOOR MTD) ® 4-PLEX RECEPTACLE (CEILING MTD) Z SPECIAL PURPOSE RECEPTACLE ® SPECIAL PURPOSE RECEPTACLE (FLOOR MTD) JUNCTION BOX (WALL MTD) O JUNCTION BOX (FLOOR MTD) JUNCTION BOX (CEILING MTD) V DATA OUTLET DATA OUTLET ® (FLOOR MTD) - TELEPHONE OUTLET (WALL MTD) V TELEPHONE/DATA OUTLET ® TELEPHONE/DATA/DUPLEX OUTLET (FLOOR MTD) $ SWITCH $� 3 -WAY SWITCH $4 4 -WAY SWITCH $B DIMMER SWITCH $T THERMAL OVERLOAD SWITCH a CONTROLLING OUTLET OR $ FIXTURE ON SWITCH LEG $x KEYED SWITCH $ov MANUAL OVERRIDE SWITCH PC PHOTOCELL OCCUPANCY SENSOR (WALL MTD) ® WITH (1) INTEGERAL SWITCH OCCUPANCY SENSOR (WALL MTD) ® WITH (2) INTEGERAL SWITCHES ® OCCUPANCY SENSOR (CEILING MTD) OCCUPANCY SENSOR (CEILING MTD) ® WITH CORRIDOR SENSING PATTERN ® DIGITAL LIGHTING CONTROL SOFT SWITCH 'x' REFERS TO CONTROL SCHEDULE ID# EXISTING PRIMARY EXISTING UTILITY TRANSFORMER 208/12OV, 30 300KVA IN] (E) PANEL 'At 2' 208/120V 30, 4W 200A MLO ELECTRICAL SYMBOL LEGEND DOWNUGHT ® MOTOR (CEILING MTD) _ FRACTIONAL HP MOTOR WITH TOGGLE 0000 (� STARTER & THERMAL OVERLOAD RELAY WALL WASHER ###AF NODE (CEILING MTD) �q XYJ6J MOT&MOTOR STARTER/ AWG CU + ###/###V N DISCO NECT SWITCH COMBO EXTERIOR SCONCE DISCONNECT SWITCH (NON-FUSED) (BRACKET MTD) SCONCE AL1 LY DISCONNECT SWITCH (WALL MTD) ®I DISCONNECT STARTER SCONCE (WALL MTD, HALF ROUND) MOTORIZED DAMPER SURFACE GLOBE ® THERMOSTAT PENDANT (SMALL) C' PANEL 'C' INDICATES PANEL NAME PENDANT (LARGE) © TELEVISION OUTLET 2X4 FLUORESCENT TC TIME CLOCK WITH BATTERY FIXTURE (CEILING MTD) C® FIRE ALARM CONTROL PANEL 2X2 FLUORESCENT ® FIRE ALARM ANNUNCIATOR (REMOTE) FIXTURE (CEILING MTD) IN FIRE ALARM HORN 1X4 FLUORESCENT W FIRE ALARM STROBE FIXTURE (CEILING MTD) 040 FIRE ALARM STROBE/HORN 1X4 FLUORESCENT STRIP FIXTURE FIRE ALARM PULL STATION TRACK MOUNTED FIXTURE FIRE/SMOKE DAMPER DH MAGNETIC DOOR HOLDER POLE MOUNTED FIXTURE (SINGLE ARM) SD GUESTROOM SMOKE DETECTOR CO GUESTROOM COMBINATION EMERGENCY EGRESS FIXTURE SO SMOKE/CO DETECTOR EXIT SIGN (SHADING INDICATES OG SECURITY CAMERA ILLUMINATED FACE(S)) ❑� SINGLE PUSH BUTTON CEILING FAN B 3 PUSH BUTTON IN -GRADE UPLIGHT BOLLARD SPOT LIGHT POST -TOP STEP LIGHT LIGHTING FIXTURE NOTATION (EXAMPLE A1E INDICATES FIXTURE TYPE DIAGONAL HATCH & 'E' SUFFIX INDICATE H1 -12a FIXTURE PROVIDED W/ EMERGENCY BATTERY BACKUP INDICATES CIRCUIT NUMBER; LOWERCASE LETTER INDICATES SWITCH LEG DESIGNATION /'--N Al -1 HOMERUN CIRCUIT, PANEL AND CIRCUIT NUMBER INIDCATED CONCEALED CONDUIT — — — UNDERGROUND/UNDERSLAB CONDUIT — — — EXPOSED CONDUIT 6 CONDUIT RUN TURNED DOWN CONDUIT RUN TURNED UP CONDUIT CONTINUATION MARK 3 CONDUIT STUB -OUT INDICATES COMMON CIRCUIT WITH SEPARATE SWITCHING NEW/EXISTING/DEMO NOTATION NEW WORK EXISTING WORK DEMOLITION WORK (E) PANEL (E) PANEL PANEL C' 'B' C2' 208/120V 208/120V O 208/120V 30, 4W 30, 4W ®� 30, 4W 200A MLO 200A MLO j 100A MLO 9003 LL 90/3 F4 200 F3 AREA OF WORK (E) 20OA3P (E) 20OA3P SWITCH W/ SWITCH W/ 200A FUSES 200A FUSES C 200 200 (E) 40OA3P SWITCH W/ 400A FUSES F21 400 C F1 (E) 1200A BUSSED GUTTER 208/12OV, 3PH, 4W (E) GROUNDING ELECTRODE NEMA 3R (E) 20OA3P SWITCH W/ 200A FUSES PAD MOUNTED UTILITI TRANSFORMER ###/###V, #01 #W ### kVA PRIMARY O STANDBY/EMERGENCY G GENERATOR ###/###V, #01 #W ###kW, ###kVA AUTOMATIC TRANSFER SWITCH A ###P # aUTILITY METER 0-3 UTILITY METER & CT's UTILITY METER M (INTEGRAL) UTILITY METER &CT's IV� J (INTEGRAL) DUAL METER STACK #P/3 UNIT# UNIT## /3 D OM SINGLE METER STACK ###/3 UNIT CIRCUIT BREAKER ##13 (DIAGRAMMATIC) FEEDER CIRCUIT BREAKER 1200 (DIAGRAMMATIC) _ FUSED SWITCH 0000 (DIAGRAMMATIC) ###A3P FAULT CALCULATION ###AF NODE PANEL 90 XX' AWG CU + ###/###V XXA PANELBOARD XXk AIC AIC DIAGRAMMATIC (DIAGRAMMATIC) FEEDER MAIN OCPD 1200 GROUND FAULT _ PROTECTION 0000 FEEDER TAG X FO FAULT CALCULATION 200 NODE FEEDER SCHEDULE 1200 4 [(4 350 KCMIL CU) 3"C.1 400 2 [(4 #3/0 AWG CU + 1 #3 AWG CU G.) 2"C.] 200 (4 #3/0 AWG CU + 1 #6 AWG CU G.) 2"C. 90 (4 #2 AWG CU + 1 #8 AWG CU G.) 1-1/4"C. DRAWING NOTES: OPROVIDE NEW BREAKER OF SIZE AND TYPE SHOWN IN EXISTING PANEL. MATCH PANEL AIC RATING. OPROVIDE REVENUE GRADE kW -HR DEMAND METER (100A, 208/12OV, 30, 4W) TO MONITOR ELECTRICAL USEAGE ON SUB -PANEL 'C2'. MOUNT METER NEXT TO PANEL 'C2' IN TENANT SPACE. OPROVIDE NEW PANEL AND FEEDER AS INDICATED. REFER TO POWER PLAN FOR PANEL LOCATION 1 GENERAL NOTES: 1. CONTRACTOR TO VERIFY ALL EXISTING FEEDER AND FUSE SIZES IN THE FIELD AND NOTIFY ENGINEER AND ARCHITECT IMMEDIATELY OF AN DISCREPANCIES FROM SIZED INDICATED ON PLANS. ELECTRICAL ONE -LINE DIAGRAM E001 N.T.S. ;i0tz))OZO & CIATES INC FqGIYEN YEauKlrx ! E1FCmCAL oNEE9s 735 S. Xenon Ct. #201 Lakewood, Colorado 80228 Ph: 303.716.1270 Fax: 303.716.1272 www.g ivenandassociates.conn Project # 20084 chord,11111111 OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.C. 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEVVOOD, CO 80228 t: 303.716.1270 COPYRIGHT: 2020 THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN CAN ONLY BE USED FOR THIS PROJECT. NO OTHER USE OF THIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED VVITHOUTTHE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. # DESCRIPTION DATE PERMIT SET 09/15/2020 CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Project Number: 20019 ELECTRICAL SPECS LEGEND ONE -LINE E001 w \ ■ FIRST FLOOR DEMO POWER PLAN E D 101 4' 2' 0 4' 8' N GENERAL NOTES: 1. DEVICES SHOWN WITH DIAGONAL HATCH ARE MARKED FOR DEMOLITION. 2. CURSORY SURVEY OF TENANT—OCCUPIED SPACE CONDUCTED BY ENGINEER PRIOR TO DESIGN. FIELD VERIFY ALL EXISTING CONDITIONS AND COMPLICATIONS THAT ARISE DURING DEMOLITION PHASE. 3. MAINTAIN ELECTRICAL CONTINUITY FOR ALL DEVICES NOT AFFECTED BY DEMO SCOPE. 4. ALL WORN OR DAMAGED DEVICES AND FACEPLATES SHALL BE REPLACED WITH WITH NEW TO MATCH EXISTING. 5. COORDINATE WITH OWNER/LANDLORD TO ENSURE NEIGHBORING TENANTS' OPERATIONS ARE NOT INTERRUPTED. 6. CONDUIT AND CONDUCTORS BEING REMOVED SHALL BE DEMO'D BACK TO NEAREST JUNCTION BOX OR BACK TO THE PANEL. 7. COORDINATE WITH ALL OTHER NECESSARY DISCIPLINES PRIOR TO BEGINNING WORK. DRAWING NOTES: COEXISTING OVERHEAD EXAM LIGHT. &CIATES INC FqGIYEN �auhlrx s ufcmcK ops 735 S. Xenon Ct. #201 Lakewood, Colorado 80228 Ph: 303.716.1270 Fax: 303.716.1272 www.g ivenandassociates.conn Project # 20084 chord,11111111 09-15-2020 OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.C. 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 COPYRIGHT: 2020 THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN CAN ONLY BE USED FOR THIS PROJECT. NO OTHER USE OF THIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUTTHE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. # DESCRIPTION DATE PERMIT SET 09/15/2020 CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Project Number: 20019 FIRST FLOOR DEMO POWER PLAN ED101 w \ ■ FIRST FLOOR DEMO LIGHTING PLAN ED201 4' 2' 0 4' 8' N GENERAL NOTES: 1. DEVICES SHOWN WITH DIAGONAL HATCH ARE MARKED FOR DEMO. 2.CURSORY SURVEY OF TENANT—OCCUPIED SPACE CONDUCTED BY ENGINEER PR TO DESIGN. FIELD VERIFY ALL EXISTING CONDITIONS AND COMPLICATIONS THAT ARISE DURING THE DEMOLITION PHASE. 3.MAINTAIN ELECTRICAL CONTINUITY FOR ALL DEVICES NOT AFFECTED BY DEMO SCOPE. 4.ALL WORN OR DAMAGED DEVICES AND/OR FACEPLATES SHALL BE REPLACED TO MATCH EXISTING. 5.000RDIINATE WITH OWNER/LANDLORD TO ENSURE NEIGHBORING TENANTS' OPERATIONS ARE NOT INTERRUPTED. 6.CONDUIT AND CONDUCTORS BEING REMOVED SHALL BE DEMO'D BACK TO NEAREST JUNCTION BOX OR BACK TO THE PANEL 7.000RDINATE WILL ALL OTHER NECESSARY DISCIPLINES PRIOR TO BEGINNING WORK. 8.ALL EXISTING EXTERIOR LIGHTING AND CONTROLS SHALL REMAIN UNLESS NOTED OTHERWISE. DRAWING NOTES: 1OEXISTING LIGHT SWITCH TO BE REMOVED AND REPLACED WITH NEW DEVICE. MAINTAIN EXISTING WIRING FOR CONNECTION TO NEW DEVICE. &CIATES INC FqGIYEN �auhlrx s ufcmcK ops 735 S. Xenon Ct. #201 Lakewood, Colorado 80228 Ph: 303.716.1270 Fax: 303.716.1272 www.g ivenandassociates.conn Project # 20084 chord,11111111 09-15-2020 OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.C. 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 COPYRIGHT: 2020 THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN CAN ONLY BE USED FOR THIS PROJECT. NO OTHER USE OF THIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUTTHE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. # DESCRIPTION DATE PERMIT SET 09/15/2020 CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Project Number: 20019 FIRST FLOOR DEMO LIGHTING PLAN ED201 ■mI EXAM 5 105 Go (E) F E)AC �G_ A (E) X RAY (E)C E A(� �( 108 (E) (E) (E) C-10 EXAM 2 GFI GFI EXAM 1 102 (E)C-31,33 101 (E)C-8 LAB 1ODA 2P (E) 07 ri r005 —_100 \� (E) C-12 \ I C-18 (E) �(E)C-16 TREATMENT (E) (E) 09 EXAM 3 (E) 103 (E) (E) ❑ AC (E) (E) AC (E) D . (E) -2 C-23 \ /� (E) C-2 EXAM OFFICE 104 GFI 117 6 (E) C-20 O6 03 (E) EWC (E) AG(E) GF� ® .. GFI "I t, (E) O 0 EF -1 RESTROOM 106 (E) 16 (E) IWIIk; 1 SX 115 V �_F — T ACII AC AG (E) GROOM 10 RESTROOM 11 ISOLATION 112 DENTAL 114 O O (E) AC DOGS AC 13 HALL BREAK C2—1,\,DELIVERY 23/ 118 125 uu =rr7 W D � C2-17 C2-15 � GFI GFI C2-11,13 GFI DW 1 M OFFICE BKR C2-25 I 119 C2-21 1 GFI AG EF -2 C2-7,9 C2-23 3OA2POCC2-27 (E) (E) GFI EF EWH-1 CP -1 BKR CF2-19 "C2" FIRST FLOOR POWER PLAN E101 4' 2' 0 4' 8' \wC ■ E )"B� O LTJ UTILITY 124 GENERAL NOTES: 1. WIRE SIZE SHALL BE MINIMUM /12 AWG, THWN SOLID COPPER UNLESS NOTED OTHERWISE. PROVIDE GROUND WIRE WHERE REQUIRED BY CODE. INCREASE WIRE SIZE TO COMPENSATE FOR VOLTAGE DROP WHERE TOTAL LENGTH OF ANY BRANCH EXCEEDS 100 FEET. ALL WIRING SHALL BE IN APPROVED RACEWAY. 2. ALL OUTLETS, FIXTURES AND EQUIPMENr SHALL BE CIRCURED AS NOTED. PANEL NAME AND CIRCUIT NUMBER(S) INDICATE BRANCH CIRCUF(S) TO BE USED. 3. VERIFY MOUNTING AND LOCATION OF ALL OUTLETS WITH ARCHITECT AND COORDINATE WITH ALL NECESSARY DISCIPLINES AS REQUIRED PRIOR TO ROUGH—IN. 4. COORDINATE LOCATIONS AND REQUIREMENTS OF ALL CAN, TELEPHONE OUTLETS WITH OWNER/ARCHrrECT. 5. REFER TO MECHANICAL AND PLUMBING DRAWINGS FOR THE LOCATIONS OF HVAC EQUIPMENT AND PLUMBING FIXTURES. 6. COORDINATE INSTALLATION REQUIREMENTS WITH MECHANICAL AND PLUMBING. PROVIDE ALL FINAL CONNECTIONS AS REQUIRED FOR A COMPLErE AND OPERATIONAL SYSTEM. 7. REFER TO EQUIPMENT CONNECTION SCHEDULE FOR FEEDER, DISCONNECT. AND CIRCUIT BREAKER SIZES FOR MECHANICAL AND PLUMBING EQUIPMENT. REFER TO MECHANICAL AND PLUMBING PIANS FOR THE EQUIPMENT LOCATIONS. 8. AT LEST ONE RECEPTACLE SHALL BE WITHIN 25 FT OF EACH PIECE OF SERVICEABLE EQUIPMENT FOR MAINTENANCE PURPOSES. FIELD VERIFY EXACT EQUIPMENT LOCATIONS AND PROVIDE ADDITIONAL RECEPTACLES AS REQUIRED. 9. ALL EXTERIOR MOUNTED RECEPTACLES, JUNCTION BOXES AND CONDUIT SHALL BE WEATHERPROOF. EXTERIOR MOUNTED RECEPTACLES SHALL BE GFCI—PROTECTED AND SHALL BE PROVIDED WITH WHILE—IN—USE COVERS. 10.140 EQUIPMENT, DEVICES, FURNITURE, OR THE LIKE SHALL BE INSrALLED OR PLACED IN FRONT OF ELECTRICAL PANELS OR EQUIPMENT THAT WOULD VIOLATE CODE REQUIREMENTS FOR WORKING CI FARANCFS_ DRAWING NOTES: 01 PROVIDE AND INSTALL NEW PANELBOARD, "C2", 1ODA, 208/12OV, 3PH, 4W. COORDINATE EXACT LOCATION WITH OWNER/ARCHITECT. PROVIDE REVENUE—GRADE kW—HR DEMAND METER TO MONITOR ELECTRICAL USAGE FOR PANEL "C2". 02 PANEL "B" IS LOCATED IN NEIGHBORING SUITE. PROVIDE 9OA/3P BREAKER FOR SUBFEED TO PANEL "C2". COORDINATE ALL WORK TO AVOID INTERRUPTION OF NEIGHBORING TENANT'S OPERATIONS AND ELECTRICAL SERVICE. 03 PROVIDE GFCI—PROTECTED RECEPTACLE FOR EWC CONNECTION. 04 EXHAUST FAN TO BE CONTROLLED WITH LIGHT SWITCH SERVING AREA. CONNECT EXHAUST FAN TO LIGHTING CIRCUIT SERVING AREA AND NOTIFY THE OWNER/BUILDING ENGINEER IF THE CIRCUIT EXCEEDS 16A OR 1920VA ON A 20A BREAKER. OS EXISTING X—RAY EQUIPMENT TO REMAIN. MAINTAIN CIRCUIT CONTINUITY AS INDICATED. O6 CIRCUIT MADE AVAILABLE EITHER BY DEMOING PREVIOUS RECEPTACLES OR EQUIPMENT, OR BY RELOCATING PREVIOUS LOAD TO NEW PANEL, "C2". REFER TO C2 PANEL SCHEDULE FOR LIST OF RELOCATED LOADS. &CIATES INC FqGIYEN YEMRATRICAL ! EIFCINCAL r]NEE9s 735 S. Xenon Ct. #201 Lakewood, Colorado 80228 Ph: 303.716.1270 Fax: 303.716.1272 www.g ivenandassociates.conn Project # 20084 chord,, OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.0 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 COPYRIGHT: 2020 THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN CAN ONLY BE USED FOR THIS PROJECT. NO OTHER USE OF THIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUTTHE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. # DESCRIPTION DATE PERMIT SET 09/15/2020 CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Project Number: 20019 FIRST FLOOR POWER PLAN E101 FIRST FLOOR POWER PLAN E101 4' 2' 0 4' 8' 1/4"= 1'-0" E)"B7 L5!= --j 0 GENERAL NOTES: 1. WIRE SIZE SHALL BE MINIMUM #12 AWG, THWN SOLID COPPER UNLESS NOTED OTHERWISE. PROVIDE GROUND WIRE WHERE REQUIRED BY CODE. INCREASE WIRE SIZE TO COMPENSATE FOR VOLTAGE DROP WHERE TOTAL LENGTH OF ANY BRANCH EXCEEDS 100 FEET. ALL WIRING SHALL BE IN APPROVED RACEWAY. 2. ALL OUTLETS, FIXTURES AND EQUIPMENT SHALL BE CIRCUITED AS NOTED. PANEL NAME AND CIRCUIT NUMBER(S) INDICATE BRANCH CIRCUIT(S) TO BE USED. 3. VERIFY MOUNTING AND LOCATION OF ALL OUTLETS WITH ARCHITECT AND COORDINATE WITH ALL NECESSARY DISCIPLINES AS REQUIRED PRIOR TO ROUGH—IN. 4. COORDINATE LOCATIONS AND REQUIREMENTS OF ALL CATV, TELEPHONE OUTLETS WITH OWNER/ARCHITECT. 5. REFER TO MECHANICAL AND PLUMBING DRAWINGS FOR THE LOCATIONS OF HVAC EQUIPMENT AND PLUMBING FIXTURES. 6. COORDINATE INSTALLATION REQUIREMENTS WITH MECHANICAL AND PLUMBING. PROVIDE ALL FINAL CONNECTIONS AS REQUIRED FOR A COMPLETE AND OPERATIONAL SYSTEM. 7. REFER TO EQUIPMENT CONNECTION SCHEDULE FOR FEEDER, DISCONNECT, AND CIRCUIT BREAKER SIZES FOR MECHANICAL AND PLUMBING EQUIPMENT. REFER TO MECHANICAL AND PLUMBING PLANS FOR THE EQUIPMENT LOCATIONS. 8. AT LEAST ONE RECEPTACLE SHALL BE WITHIN 25 FT OF EACH PIECE OF SERVICEABLE EQUIPMENT FOR MAINTENANCE PURPOSES. FIELD VERIFY EXACT EQUIPMENT LOCATIONS AND PROVIDE ADDITIONAL RECEPTACLES AS REQUIRED. 9. ALL EXTERIOR MOUNTED RECEPTACLES, JUNCTION BOXES AND CONDUIT SHALL BE WEATHERPROOF. EXTERIOR MOUNTED RECEPTACLES SHALL BE GFCI—PROTECTED AND SHALL BE PROVIDED WITH WHILE—IN—USE COVERS. 10. NO EQUIPMENT, DEVICES, FURNITURE, OR THE LIKE SHALL BE INSTALLED OR PLACED IN FRONT OF ELECTRICAL PANELS OR EQUIPMENT THAT WOULD VIOLATE CODE REQUIREMENTS FOR WORKING CLEARANCES. DRAWING NOTES: O1 PROVIDE AND INSTALL NEW PANELBOARD, "C2", 100A, 208/120V, 3PH, 4W. COORDINATE EXACT LOCATION WITH OWNER/ARCHITECT. PROVIDE REVENUE -GRADE kW -HR DEMAND METER TO MONITOR ELECTRICAL USAGE FOR PANEL "C2". O PANEL "B" IS LOCATED IN NEIGHBORING SUITE. PROVIDE 90A/3P BREAKER FOR SUBFEED TO PANEL "C2". COORDINATE ALL WORK TO AVOID INTERRUPTION OF NEIGHBORING TENANT'S OPERATIONS AND ELECTRICAL SERVICE. O PROVIDE GFCI-PROTECTED RECEPTACLE FOR EWC CONNECTION. (�4 EXHAUST FAN TO BE CONTROLLED WITH LIGHT SWITCH SERVING AREA. CONNECT EXHAUST FAN TO LIGHTING CIRCUIT SERVING AREA AND NOTIFY THE OWNER/BUILDING ENGINEER IF THE CIRCUIT EXCEEDS 16A OR 1920VA ON A 20A BREAKER. t�5 EXISTING X-RAY EQUIPMENT TO REMAIN. MAINTAIN CIRCUIT CONTINUITY AS INDICATED. O CIRCUIT MADE AVAILABLE EITHER BY DEMOING PREVIOUS RECEPTACLES OR EQUIPMENT, OR BY RELOCATING PREVIOUS LOAD TO NEW PANEL, "C2". REFER TO C2 PANEL SCHEDULE FOR LIST OF RELOCATED LOADS. FiGIVEN & ASSOCIATES INC MECHANICAL & ELECTRICAL ENGNEM 735 S. Xenon Ct. #201 Lakewood, Colorado 80228 Ph: 303.716.1270 Fax: 303.716.1272 www.givenandassociates.com Project # 20084 chcird,, 12-17-2020 OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.C. 1425 MARKET STREET SUITE 220 DENVER, CO 80202 RW111911:16zWzm�i MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 COPYRIGHT: 2020 THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN CAN ONLY BE USED FOR THIS PROJECT. NO OTHER USE OF THIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUT THE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. # DESCRIPTION DATE PERMIT SET 09/15/2020 2 ADDENDUM #1 11/13/2020 3 ASI #1 12/17/2020 CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Project Number: 20019 FIRST FLOOR POWER PLAN E101 w \ ■ ROOF POWER PLAN El 0 2 4' 2' 0 4' 8' GENERAL NOTES: 1. ALL EXISTING ROOFTOP EQUIPMENT S EXISTING TO REMAIN UNLESS NOTED OTHERWISE. MAINTAIN CIRCUIT CONTINUITY TO ALL ROOFTOP EQUIPMENT AND ANY OTHER EXISTING LOADS. DRAWING NOTES: COCIRCUIT EXISTING ROOFTOP UNIT TO NEW PANEL, "C2". PROVIDE CONDUIT AND WIRING BACK TO THE PANEL AS INDICATED ON MECHANICAL EQUIPMENT SCHEDULE. REVISION FqUIYEN CIATES INC . 735 S. Xenon Ct. #201 Lakewood, Colorado 80228 Ph: 303.716.1270 Fax: 303.716.1272 www.g ivenandassociates.conn Project # 20084 chord,11111111 11 III 11 I1 09-15-2020 OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.C. 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 COPYRIGHT: 2020 THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN CAN ONLY BE USED FOR THIS PROJECT. NO OTHER USE OF THIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUTTHE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. # DESCRIPTION DATE PERMIT SET 09/15/2020 CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Project Number: 20019 ROOF POWER PLAN El 02 FIRST FLOOR LIGHTING PLAN E 2 01 4' 2' 0 4' 8' w \ ■ GENERAL NOTES: 1. WIRE SIZE SHALL BE MINIMUM B12 AWG, THWN SOLID COPPER UNLESS NOTED OTHERWISE. PROVIDE GROUND WIRE WHERE REQUIRED BY CODE. INCREASE WIRE SIZE TO COMPENSATE FOR VOLTAGE DROP WHERE TOTAL LENGTH OF ANY BRANCH EXCEEDS 100 FEET. ALL WIRING SHALL BE IN APPROVED RACEWAY. 2. ALL OUTLETS, FIXTURES AND EQUIPMENT SHALL BE CIRCUITED AS NOTED. PANEL NAME AND CIRCUIT NUMBER(S) INDICATE BRANCH CIRCUIT(S) TO BE USED. 3. VERIFY MOUNTING AND LOCATION OF ALL OUTLETS WITH ARCHITECT AND COORDINATE WITH ALL NECESSARY DISCIPLINES AS REQUIRED PRIOR TO 4. VERIFY LIGHT FIXTURE SCHEDULES, LOCATIONS, QUANTITIES AND LIGHTING CONTROL REQUIREMENTS. PROVIDE LIGHTING AND CONTROLS AS REQUIRED FOR THE SCOPE OF THIS PROJECT. 5. ALL EXIT SIGNS AND EGRESS LIGHTS SHALL BE CONNECTED TO LIGHTING CIRCUIT IN THE AREA AND WIRED TO AN UN—SWITCHED HOT LEG. 6. NO EQUIPMENT, DEVICES, FURNITURE, OR THE LIKE SHALL BE INSTALLED OR PLACED IN FRONT OF ELECTRICAL PANELS OR EQUIPMENT THAT WOULD VIOLATE CODE REQUIREMENTS FOR WORKING CLEARANCES. DRAWING NOTES: OCIRCUIT THE NEW LIGHTING FIXTURES AND LIGHTING CONTROLS SHOWN TO THE EXISTING LIGHTING CIRCUIT IN THE AREA. VERIFY EXACT SWITCH LOCATIONS AND OCCUPANCY SENSOR LOCATIONS WITH OWNER/ARCHITECT. NOTIFY OWNER OR BUILDING ENGINEER IF LOAD EXCEEDS 16A OR 1920 VA ON A 20A BREAKER. O2 REUSE EXISTING SWITCH. (3)EXISTING OVER HEAD OPERATING LIGHT TO BE REUSED. COORDINATE EXACT RELOCATION IN FIELD WITH OWNER/ARCHITECT. SEE NEXT UPDATED C*y« &CIATES INC FqGIYEN �auhlc,� s ufemcK oomis 735 S. Xenon Ct. #201 Lakewood, Colorado 80228 Ph: 303.716.1270 Fax: 303.716.1272 www.g ivenandassociates.conn Project # 20084 chord,11111111 09-15-2020 OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.C. 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 COPYRIGHT: 2020 THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN CAN ONLY BE USED FOR THIS PROJECT. NO OTHER USE OF THIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUTTHE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. # DESCRIPTION DATE PERMIT SET 09/15/2020 CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Project Number: 20019 FIRST FLOOR LIGHTING PLAN E201 ;1' 2 102 --- LAB 07 J (b) Wr RECEPTION 100 EXAM 1EXAM 101 L X RAY 108 O1 L A (a) EM1 Oj (b) EM1 (b) ® O GROOM 110 O q (E) VANITY LIGHT XiRESTROOM NL O (a) EM1 (b) TREATMENT 109 (b) P1 B10 ® (a) 0(o) I- B1 0(o) P1 B1 ® (a) O(a) Ir EM1( O A (b) EXAM ❑ 103 I (b) (b) EM%� z (a) ISO'A21 2 (b) 3'M (a) ® ® (b) X21 (b) E 1 (d) (b)4 `I EM1 3 2 A (c) A (d) DOGS (a) O O O O 3 EM1 EM1 1 EM1 DENTAL 114 A EM( F- ® ® (c) a O (E)C-28 1 O EXAM 4 104 OF CE A (c) A (d) (d) 0 117 A (a) ❑ EM1 S1 B1 B1 ESTRO O 106 X1 11 a If7AI DELIVER —T—T— —T—1 123 (c) A (d) 3 4A (d) EM1 (a) ® (o) c () (c)® HALL 118 X2� (d) EMXO IE v12 EM1 J (c) (c) BREAK 125 EXAM 5 7 105 Or==1=24 ITY Ul OFFICE FF A EM1Ll 119 STORAGE 116 FIRST FLOOR LIGHTING PLAN E 2 01 4' 2' 0 4' 8' w \ ■ GENERAL NOTES: 1. WIRE SIZE SHALL BE MINIMUM B12 AWG, THWN SOLID COPPER UNLESS NOTED OTHERWISE. PROVIDE GROUND WIRE WHERE REQUIRED BY CODE. INCREASE WIRE SIZE TO COMPENSATE FOR VOLTAGE DROP WHERE TOTAL LENGTH OF ANY BRANCH EXCEEDS 100 FEET. ALL WIRING SHALL BE IN APPROVED RACEWAY. 2. ALL OUTLETS, FIXTURES AND EQUIPMENT SHALL BE CIRCUITED AS NOTED. PANEL NAME AND CIRCUIT NUMBER(S) INDICATE BRANCH CIRCUIT(S) TO BE USED. 3. VERIFY MOUNTING AND LOCATION OF ALL OUTLETS WITH ARCHITECT AND COORDINATE WITH ALL NECESSARY DISCIPLINES AS REQUIRED PRIOR TO 4. VERIFY LIGHT FIXTURE SCHEDULES, LOCATIONS, QUANTITIES AND LIGHTING CONTROL REQUIREMENTS. PROVIDE LIGHTING AND CONTROLS AS REQUIRED FOR THE SCOPE OF THIS PROJECT. 5. ALL EXIT SIGNS AND EGRESS LIGHTS SHALL BE CONNECTED TO LIGHTING CIRCUIT IN THE AREA AND WIRED TO AN UN—SWITCHED HOT LEG. 6. NO EQUIPMENT, DEVICES, FURNITURE, OR THE LIKE SHALL BE INSTALLED OR PLACED IN FRONT OF ELECTRICAL PANELS OR EQUIPMENT THAT WOULD VIOLATE CODE REQUIREMENTS FOR WORKING CLEARANCES. DRAWING NOTES: OCIRCUIT THE NEW LIGHTING FIXTURES AND LIGHTING CONTROLS SHOWN TO THE EXISTING LIGHTING CIRCUIT IN THE AREA. VERIFY EXACT SWITCH LOCATIONS AND OCCUPANCY SENSOR LOCATIONS WITH OWNER/ARCHITECT. NOTIFY OWNER OR BUILDING ENGINEER IF LOAD EXCEEDS 16A OR 1920 VA ON A 20A BREAKER. O2 REUSE EXISTING SWITCH. (3)EXISTING OVER HEAD OPERATING LIGHT TO BE REUSED. COORDINATE EXACT RELOCATION IN FIELD WITH OWNER/ARCHITECT. SEE NEXT UPDATED C*y« &CIATES INC FqGIYEN �auhlc,� s ufemcK oomis 735 S. Xenon Ct. #201 Lakewood, Colorado 80228 Ph: 303.716.1270 Fax: 303.716.1272 www.g ivenandassociates.conn Project # 20084 chord,11111111 09-15-2020 OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.C. 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 COPYRIGHT: 2020 THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN CAN ONLY BE USED FOR THIS PROJECT. NO OTHER USE OF THIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUTTHE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. # DESCRIPTION DATE PERMIT SET 09/15/2020 CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Project Number: 20019 FIRST FLOOR LIGHTING PLAN E201 i►tlir: FIRST FLOOR LIGHTING PLAN E 2 01 4' 2' 0 4' 8' 1/4"=l' -O" GENERAL NOTES: 1. WIRE SIZE SHALL BE MINIMUM #12 AWG, THWN SOLID COPPER UNLESS NOTED OTHERWISE. PROVIDE GROUND WIRE WHERE REQUIRED BY CODE. INCREASE WIRE SIZE TO COMPENSATE FOR VOLTAGE DROP WHERE TOTAL LENGTH OF ANY BRANCH EXCEEDS 100 FEET. ALL WIRING SHALL BE IN APPROVED RACEWAY. 2. ALL OUTLETS, FIXTURES AND EQUIPMENT SHALL BE CIRCUITED AS NOTED. PANEL NAME AND CIRCUIT NUMBER(S) INDICATE BRANCH CIRCUIT(S) TO BE USED. 3. VERIFY MOUNTING AND LOCATION OF ALL OUTLETS WITH ARCHITECT AND COORDINATE WITH ALL NECESSARY DISCIPLINES AS REQUIRED PRIOR TO ROUGH -IN. 4. VERIFY LIGHT FIXTURE SCHEDULES, LOCATIONS, QUANTITIES AND LIGHTING CONTROL REQUIREMENTS. PROVIDE LIGHTING AND CONTROLS AS REQUIRED FOR THE SCOPE OF THIS PROJECT. 5. ALL EXIT SIGNS AND EGRESS LIGHTS SHALL BE CONNECTED TO LIGHTING CIRCUIT IN THE AREA AND WIRED TO AN UN -SWITCHED HOT LEG. 6. NO EQUIPMENT, DEVICES, FURNITURE, OR THE LIKE SHALL BE INSTALLED OR PLACED IN FRONT OF ELECTRICAL PANELS OR EQUIPMENT THAT WOULD VIOLATE CODE REQUIREMENTS FOR WORKING CLEARANCES. DRAWING NOTES: O1 CIRCUIT THE NEW LIGHTING FIXTURES AND LIGHTING CONTROLS SHOWN TO THE EXISTING LIGHTING CIRCUIT IN THE AREA. VERIFY EXACT SWITCH LOCATIONS AND OCCUPANCY SENSOR LOCATIONS WITH OWNER/ARCHITECT. NOTIFY OWNER OR BUILDING ENGINEER IF LOAD EXCEEDS 16A OR 1920 VA ON A 20A BREAKER. O2 REUSE EXISTING SWITCH. N ISTING OVER HEAD OPERATING LIGHT TO BE REUSED. COORDINATE EXACT LOCATION IN FIELD WITH OWNER/ARCHITECT. REVISION FiGIVEN & ASSOCIATES INC MECHANICAL & ELECTRICAL ENGNEM 735 S. Xenon Ct. #201 Lakewood, Colorado 80228 Ph: 303.716.1270 Fax: 303.716.1272 www.givenandassociates.com Project # 20084 chcird,, 12-17-2020 OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.C. 1425 MARKET STREET SUITE 220 DENVER, CO 80202 RW111911:16zWzm�i MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 COPYRIGHT: 2020 THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN CAN ONLY BE USED FOR THIS PROJECT. NO OTHER USE OF THIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUT THE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. # DESCRIPTION DATE PERMIT SET 09/15/2020 2 ADDENDUM #1 11/13/2020 3 ASI #1 12/17/2020 CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Project Number: 20019 FIRST FLOOR LIGHTING PLAN E201 PANEL BTYPE: CUTLER -HAMMER VOLTAGE 208/120 MTG: RECESSED PHASE 3 1 AIC: 1OKAIC WIRES 4 LARGEST MOTOR: 0 VA RATING 225 A MAIN BREAKER MLO CD1 CKT DESCRIPTION BKR CKT A B C CKT BKR CKT DESCRIPTION CD 1 LTG - CLASS ROOM 20A1P 1 550 ---- ---- 3 20A1P GARBAGE DISPOSAL 3 900 ---- ---- 2 1 LTG - CLASS ROOM 20A1P 3 ---- 650 ---- 2 20A1P DISHWASHER 4 1200 ---- 4 1 LTG - BANQUET HALL 20A1P 5 ---- ---- 350 2000 6 20A1P REFRIERATOR - KITCHEN 3 ---- ---- 900 6 3 WAHSER 20A1P 7 1000 ---- ---- ---- 8 20A1P RCPT - KITCHEN GFCI 2 360 ---- ---- 8 2 SPARE 20A1P 9 ---- ---- E CORN X-RAY 20A1P RCPT - KITCHEN GFCI 2 ---- 360 ---- 10 2 SPARE 20A1P 11 ---- ---- E ROOF GFCI 20A1P RCPT - KITCHEN GFCI 2 ---- ---- 360 12 2 RCPTS - CLASS ROOM 20A1P 13 540 ---- ---- E SPACE 20A1P RCPT - KITCHEN GFCI 2 360 ---- ---- 14 2 RCPTS - CLASS ROOM 20A1P 15 ---- 720 ---- (E) RTU -3 (RELOCATED FROM #7, #9) 20A1P RANGE HOOD 3 ---- 200 ---- 16 2 RCPT - RTU GFCI 20A1P 17 ---- ---- 180 19 1 2900 ---- 20A1P LTG - BATH HALL 1 ---- ---- 250 18 ---- 20 SPARE 3OA2P 19 21 ---- 20A1P RCPT - BATHROOM GFCI 2 180 ---- ---- 20 ---- 22 2 RCPTS - SURGERY 20A1P RCPT - HEAT TAPE 2 ---- 500 ---- 22 2 SPARE 50A2P 23 ---- ---- 3380 1 20A1P EXISTING LOAD 5 ---- ---- 500 24 SPACE 25 3380 ---- ---- ---- 30A2P COOKTOP 4 2500 ---- ---- 26 (E) LTG - OPERATING RM SPARE 30A2P 27 ---- ---- 1 4 ---- 2500 ---- 28 E RCPT - TELECOM 2 ---- ---- 50A2P RANGE 4 ---- ---- 4000 30 7 EWH 3OA2P 31 4000 ---- ---- 1560 ---- 4 1500 ---- ---- 32 7 33 ---- 3380 ---- ---- 1560 3OA2P RTU 5 3 ---- 1500 ---- 34 500 (N) PANEL C2 9OA3P 35 ---- ---- 9315 ---- ---- 3 ---- ---- 3380 36 20A1P 37 9660 ---- ---- ---- 20A1P SPACE 5 ---- ---- 38 5 39 ---- 1 9160 ---- 20A1P 39 ---- 500 SPACE 20A1P ---- ---- 40 ---- 500 SPACE 5 41 ---- ---- z0A1P 41 ---- ---- SPACE 20A1P ---- ---- 42 TOTAL VOLT -AMPS 24930 20170 22615 720 42 PANEL CONNECTED LOAD 67,715 VA 188 AMPS FEED -THROUGH LOAD 0 VA 0 AMPS TOTAL CONNECTED LOAD 67,715 VA 188 AMPS TOTAL DEMAND LOAD OF I DEMAND TOTAL DEMAND LIGHTING 1 1800 1.25 2250 LIGHTING 1 RECEPTACLES 2 6980 10k+.5 6980 PHASE IMBALANCE MOTORS 3 17715 1+0.25 17715 10.45% 0.64%1 0.19% I A B IC Ot : 2 KITCHEN 4 12900 1.00 12900 MISCELLANEOUS 5 500 1.00 500 ELECTRIC HEAT 6 4680 1.00 4680 ELECTRIC HEAT 6 ELEC. WATER HTG 7 16380 1.25 20475 ELEC. WATER HTG 7 HOTEL 8 0 NEC 0 0 SQ FT - PER NEC 220.14(J) & 220.42 ELEVATOR 9 0 1.00 0 ELEVATOR 9 TOTALS 1 50955 65500 TOTALS 182 AMPS PANEL CTYPE: SIEMENS VOLTAGE 208 120 MTG: RECESSED PHASE 3 1 AIC: 10KAIC WIRES 4 LARGEST MOTOR: 0 VA RATING 225 A MAIN BREAKER MLO CD CKT DESCRIPTION BKR CKT A B C CKT BKR CKT DESCRIPTION CD 1 E OUTSIDE SIGN 20A1P 1 200 ---- ---- 20A1P EWC 3 500 ---- ---- 2 3 (E) RTU -2 50A2P 3 ---- 2900 ---- 20A1P RCPTS - RR DOGS 2 ---- 1260 ---- 4 3 5 ---- ---- 2900 20A1P E EUH-1 6 ---- ---- 2000 6 20A1P SPARE 50A2P A + 1 20A1P RCPTS - AG - LAB 2 360 ---- ---- 8 LITHONIA MVOLT MAIN BREAKER 20A1P RCPTS - AG - EXAM 1 2 2 ---- 1080 ---- 10 5 E CORN X-RAY 15A1 P 11 ---- ---- 1000 20A1P RCPTS - EXAM 1 2 2 ---- ---- 720 12 2 E ROOF GFCI 20A1P 13 180 ---- ---- 20A1P SPARE RCPTS - UTILITY ---- ---- 14 720 E SPACE 20A1P 15 ---- ---- 20A1P RCPTS - EXAM 3 2 ---- 900 ---- 16 3 (E) RTU -3 (RELOCATED FROM #7, #9) 50A2P 17 ---- ---- 2900 20A1P RCPTS - RECEPTION DESK 2 ---- ---- 720 18 3 19 1 2900 ---- ---- 20A1P RCPTS - OFFICE 117 2 1080 ---- ---- 20 ---- ---- 6 SPARE 20A1P 21 ---- ---- 20A1P RCPTS - EXAM 4 2 ---- 1440 ---- 22 2 RCPTS - SURGERY 20A1P 23 ---- ---- 1260 20A1P LITHONIA 2 ---- ---- 1080 24 RCPTS - AC - DENTAL 1 LTG - GENERAL 20A3P 25 720 ---- ---- ---- SPACE WET LOCATION, 0 DEG F ---- ---- 26 1 27 ---- 900 ---- 20A1P (E) LTG - OPERATING RM 1 ---- 500 ---- 28 1 29 ---- ----900 3 20A1P E RCPT - TELECOM 2 ---- ---- 360 30 5 (E) X-RAY 10OA2P 31 10400 ---- ---- 20A2P DOG DRYER 6 1560 ---- ---- 32 5 33 ---- 10400 ---- 6 ---- 1560 ---- 34 5 EXISTING LOAD 20A1P 35 ---- ---- 500 20A1P EXISTING LOAD 5 ---- ---- 500 36 5 EXISTING LOAD 20A1P 37 500 ---- ---- 20A1P EXISTING LOAD 5 500 ---- ---- 38 5 EXISTING LOAD 20A1P 39 ---- 500 ---- 20A1P EXISTING LOAD 5 ---- 500 ---- 40 5 EXISTING LOAD z0A1P 41 ---- ---- 500 20A1P RCPTS - CEILING - STOREFRONT 2 ---- ---- 720 42 TOTAL VOLT -AMPS 18900 21940 I 16060 PANEL CONNECTED LOAD 56,900 VA 158 AMPS FEED -THROUGH LOAD 0 VA 0 AMPS TOTAL CONNECTED LOAD 56,900 VA 158 AMPS TOTAL DEMAND LOAD OF DEMAND 1200 LIGHTING 1 3220 1.25 4025 RECEPTACLES 2 11160 10k+.5 10580 PHASE IMBALANCE % MOTORS 3 12100 1+0.25 12100 0.35%1 15.68%1 15.33%1 A B C KITCHEN 4 0 1.00 0 MISCELLANEOUS 5 25300 1.00 25300 ELECTRIC HEAT 6 5120 1.00 5120 ELEC. WATER HTG 7 0 1.25 0 HOTEL 8 0 NEC 0 0 SQ FT - PER NEC 220.14(J) & 220.42 ELEVATOR 9 01.00 0 ---- TOTALS 56900 57125 159 AMPS LUMINAIRE SCHEDULE PANEL C2 DESCRIPTION MANUFACTURER AND TYPE: SIEMENS LAMP REMARKS MARK VOLTAGE 208/120 LAMPS TYPE MTG: RECESSED RECESSED 2'X4' LITHONIA MVOLT PHASE 3 DISC. SIZE O.C. PROTECTION CB SIZE FUSE SIZE 1 AIC: 1OKAIC 2BLT4 30L * EZ1 LP835 WIRES 4 2'X4' LARGEST MOTOR: 0 1 VA 0.21 0.26 20A1P RATING 100 A + 1 #12AWG GND A3 RECESSED 2'X2' LITHONIA MVOLT MAIN BREAKER MLO 0.014 - 0.12 0.15 213LT2 33L * EZ1 LP835 2 #12AWG CD CKT DESCRIPTION BKR CKT KT GOTHAM B C CKT BKR 1 CKT DESCRIPTION CD 2 RCPTS - UTILITY 20A1P 1 720 ---- ---- PENDANT TBD BY OWNER MVOLT SPACE 20W LED I I ---- 2 3 RTU-4 (RELOCATED FROM B-23,25) 50A2P 3 ---- 3255 ---- 2 4AWG SPACE 10AWG ---- ---- 4 3 5 ---- ---- 3255 E RTU -:'EXISTING EM1 SPACE FROG EYES ---- ---- 6 7 EWH-1 50A2P 7 4500 ---- ---- ELM2L + 1 10AWG SPACE 3 4 ---- ---- 8 7 9 ---- 4500 ---- LITHONIA 120 277 SPACE 8.57W LED ---- ---- 10 6 DRYER (RELOCATED FROM C-21,23) 30A2P---- 11 ---- ---- 2340 WET LOCATION, 0 DEG F EMX WALL MOUNT SPACE LITHONIA ---- 12 6 13 2340 ---- ---- WITH BATTERY BACK-UP 6510 SPACE ---- ---- 14 3 WASHER RELOCATED FROM C-24 20A1P 15 ---- 1200 ---- LITHONIA 120T27_7 - SPACE WITH BATTERY BACK-UP ---- ---- 16 3 GARBAGE DISPOSER 20A1P 17 ---- ---- 1200 X2 PER PLAN EXIT SIGN SPACE 120/2// ---- ---- 18 3 REFRIGERATOR - BREAKROOM 20A1P GFI 19 900 ---- ---- 1 I W FIXTURE SPACE ---- ---- 20 2 RCPT - AG - BREAKROOM 20A1P 21 ---- 180 ---- SPACE ---- ---- 22 2 RCPTS - OFFICE 119 20A1P 23 ---- ---- 1440 SPACE ---- ---- 24 4 DISHWASHER - BREAKROOM 20A1P GFI 25 1200 ---- ---- SPACE ---- ---- 26 3 CP -1 20A1P 27 ---- 25 ---- SPACE ---- ---- 28 2 RCPTS - EXAM 5 20A1P 29 ---- ---- 1080 1 1 SPACE ---- ---- 1 30 SPARE 20A1P 31 ---- ---- SPACE ---- ---- 32 SPARE 20A1P 33 ---- ---- SPACE ---- ---- 34 SPARE 20A1P 35 ---- ---- SPACE ---- ---- 36 SPACE 37 ---- ---- SPACE ---- ---- 38 SPACE 39 ---- ---- SPACE ---- ---- 40 SPACE 41 ---- ---- SPACE ---- ---- 42 TOTAL VOLT -AMPS 1 9660 1 9160 1 9315 PANEL CONNECTED LOAD 28,135 VA 78 AMPS FEED -THROUGH LOAD 0 VA 0 AMPS TOTAL CONNECTED LOAD 28,135 VA 78 AMPS TOTAL DEMAND LOAD I OF DEMAND LIGHTING 1 0 1.25 0 RECEPTACLES 2 3420 10k+.5 3420 PHASE IMBALANCE % MOTORS 3 9835 1+0.25 9835 3.00% 2.33% 0.68% A B C (Qty: 1 KITCHEN 4 1200 1.00 1200 MISCELLANEOUS 5 0 1.00 0 ELECTRIC HEAT 6 4680 1.00 4680 ELEC. WATER HTG 7 9000 1.25 11250 HOTEL 8 0 NEC 0 0 SQ FT - PER NEC 220.14(J) & 220.42 ELEVATOR 9 0 1.00 0 TOTALS 28135 30385 84 AMPS LUMINAIRE SCHEDULE PLAN MOUNTING DESCRIPTION MANUFACTURER AND VOLTAGE NO. OF LAMP REMARKS MARK CATALOG NUMBER LAMPS TYPE DESCRIPTION Al RECESSED 2'X4' LITHONIA MVOLT 1 24W LED DISC. SIZE O.C. PROTECTION CB SIZE FUSE SIZE FEEDER 2BLT4 30L * EZ1 LP835 A2 RECESSED 2'X4' LITHONIA MVOLT 1 48W LED 0.21 0.26 20A1P HIGH OUTPUT 2BLT4 60L * EZ1 LP835 12AWG + 1 #12AWG GND A3 RECESSED 2'X2' LITHONIA MVOLT 1 27W LED 0.014 - 0.12 0.15 213LT2 33L * EZ1 LP835 2 #12AWG + 1 B1 RECESSED DOWNLIGHT GOTHAM MVOLT 1 9.6W LED 120 1 0.012 6" APERTURE EV06 35/10 * * * MVOLT EZ10 0.1 0.125 20A1P 2 P1 PENDANT PENDANT TBD BY OWNER MVOLT 1 20W LED ELECTRIC WATER HEATER S1 SCONCE SCONCE TBD BY OWNER MVOLT 1 20W LED 2 4AWG (RESTROOM) 10AWG GND 1 C E RTU -:'EXISTING EM1 WALL MOUNT FROG EYES LITHONIA 120/2-7-7 2 1.5W LED WITH BATTERY BACK-UP 30A 50A2P 45 2 ELM2L + 1 10AWG GND 3 4 EM2 WALL MOUNT EXTERIOR LITHONIA 120 277 1 8.57W LED WITH BATTERY BACK-UP 27.9 29 EMERGENCY AFF OELR * WT 2 10AWG + 1 WET LOCATION, 0 DEG F EMX WALL MOUNT COMBO EM + EX LITHONIA 120 277 2 4.3W LED WITH BATTERY BACK-UP 6510 LHQM LED G SO 60A 50A2P 50 2 10AWG X1 PER PLAN EXIT SIGN LITHONIA 120T27_7 - LED WITH BATTERY BACK-UP SINGLE FACE LOM 3 G MVOLT I I W FIXTURE X2 PER PLAN EXIT SIGN LITHONIA 120/2// - LED WITH BATTERY BACK-UP DOUBLE FACE LOM 3 G MVOLT 1 I W FIXTURE &CIATES INC FqGIYEN �auhlrx s ufcmcK ops 735 S. Xenon Ct. #201 Lakewood, Colorado 80228 Ph: 303.716.1270 Fax: 303.716.1272 www.g ivenandassociates.conn Project # 20084 chord% 09-15-2020 OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.C. 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 COPYRIGHT: 2020 THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN CAN ONLY BE USED FOR THIS PROJECT. NO OTHER USE OF THIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUTTHE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. # DESCRIPTION DATE PERMIT SET 09/15/2020 CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Project Number: 20019 ELECTRICAL PANEL SCHEDULES E301 EQUIPMENT CONNECTION SCHEDULE TAG DESCRIPTION VOLT PHASE KW HP FLA MCA DISC. SIZE O.C. PROTECTION CB SIZE FUSE SIZE FEEDER CP -1 CIRCULATION PUMP 120 1 0.025 - 0.21 0.26 20A1P 2 # 12AWG + 1 #12AWG GND 3 4C EF -1 EXHAUST FAN 120 1 0.014 - 0.12 0.15 20A1P 2 #12AWG + 1 #12AWG GND 3 4C EF -2 EXHAUST FAN 120 1 0.012 - 0.1 0.125 20A1P 2 12AWG + 1 12AWC GND 3 4C EWH-1 ELECTRIC WATER HEATER 208 1 9 - 43 54 60A 60A 2P 2 4AWG + 1 10AWG GND 1 C E RTU -:'EXISTING ROOFTOP UNIT 208 1 5800 27.9 29 30A 50A2P 45 2 10AWG + 1 10AWG GND 3 4 C E RTU- EXISTING ROOFTOP UNIT 208 1 5800 27.9 29 30A 50A2P 45 2 10AWG + 1 1OAWG GND 3 4 C E RTU- EXISTING ROOFTOP UNIT 208 1 6510 31.3 33.2 60A 50A2P 50 2 10AWG + 1 10AWG GND 3 4 C &CIATES INC FqGIYEN �auhlrx s ufcmcK ops 735 S. Xenon Ct. #201 Lakewood, Colorado 80228 Ph: 303.716.1270 Fax: 303.716.1272 www.g ivenandassociates.conn Project # 20084 chord% 09-15-2020 OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.C. 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 COPYRIGHT: 2020 THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN CAN ONLY BE USED FOR THIS PROJECT. NO OTHER USE OF THIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUTTHE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. # DESCRIPTION DATE PERMIT SET 09/15/2020 CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Project Number: 20019 ELECTRICAL PANEL SCHEDULES E301 fCOMcheck Software Version 4.1.1.0 Interior Lighting Compliance Certificate Project Information Energy Code: Prefect Title PrejectType Construction Site 4960 KIPLING ST STE A-6 WHEAT RIDGE, CO 80033 2018 IECC CLEAR CREEK ANIMAL HOSPITAL Alteration Owner/Agent Allowed Interior Lighting Power A Area Category Designer/Contractor. GIVEN AND ASSOCIATES 735 A XENON CT STE 201 LAKEWOOD, CO 88228 7206386586 B C D Flool-Area Allowed Allowed Watts (ft2) Watts / ft2 (B X C) 1- VETERINARY OFFICE (Office) 3561 079 2813 Tobi Allowed Watts= 2813 Proposed Interior Lighting Power A B C D E Fixture In Description/Lamp/Wattage Per Lamp/Ballast Lamps/ #of Fixture (CXD) Fixture Fixtures Watt. VETERINARY OFFICE ( Office 3561 so ft ) LED 1: At NEW 2X4 LED TROFFER Omer: 1 23 24 552 LED 2: A2 NEW 2x4 LED TROFFER Omer: 1 11 48 528 LED 3: A3: NEW 2X2 LED TROFFER. Omer: 1 16 27 432 LED 4: B1'. NEW LED DOWULIGHT Omer 1 6 10 60 LED 5'. P1'. NEW PENDANT: Other: 1 2 20 40 Total Proposed Watts Interior Lighting Compliance Statement Compliance Statement The proposed Interior lighting alteration project represented In this document is consistentwim the building pians, specifications , and other calculations submitted with this permit application . The proposed interior lighting systems have been designed to meetthe 2018 IECC requirements In COMcheck Version 4.1.1 0 and to comply with any applicable mandatory requirements listed In the Inspection Checklist. 1632 Project Title CLEAR CREEKANIMAL HOSPITAL Report date 09/15/29 Data filename: G:vejobs\Clear CreekAnlmal Hospital-29984\Engrtile\Elec calce\2929-0908-CLEAR CREEK Page 1of6 ANIMAL HOSPITAL- COM CHECK cck Section Plan Review Complies? hill Comments/ASSumptions C1032 # Rough In Electrical Inspection Complies? Comments/Assumptions calculations provide all information & Reg IF C303.3, with which compliance can be ONotObservable C40523 Daylight zones provided with (TComplies (TDoesNot C40523 individual controls that control the (TDoesNot ONDAppiicabie 1, lights Independent of general area (Trot Observable ONotObservable C40523 lighting. See code section C40523 (TNatApplicable (TNotAPPuable 2 Daylight responsive controls for provided should Include Interior (TComplie [EL23]2 applicable spaces, C405231 Daylight lighting power calculations, wattage of (TDoesNot responsive control function and bums and ballasts, transformers and (TNot Observable section C405 23 2 Sidelit zone. antral devices. (TNot Observable C40524 Separate lighting control devices for (TCompues (TNot APPuabe [EL26H specific uses installed per approved (TDoesNot (TNot Applicable lighting pians. (Trot Observable (TComplies [eCl (TNot Applicable ODoesNot C40524 Additional Interior lighting power (TCompues [EL27H allowed for special functions Perthe (TDoesNot (TNot Appliable approved lighting pians and is (Trot Observable automatically controlled and (TNot Applicable separated from general lighting. syslemsare Intended to be Installed, C4053 Exit signs do not exceed 5 watts per (TCompues [EL61 Ince. ODoesNot (TComplies 1 (Trot Observable (TDoesNot XI163 (TNot Applicable ODoesNot C4056 Low voltage dry -type distribution (TComplies (Trot Observable [EL26]2 electric transformers meetthe (TDoesNot ONUAPPuabe minimum efficiency requirements of (Trot Observable (TComplies Table C4050. (TNat Applicable (TDoesNot C4057 Electric motors meetthe minimum (TComplies (TNotObservable [EL27]2 efficiency requirements of Tables (TDoesNot ONUAPPuabe C4057(1) through C405 7y) (TNotObservable Efficiency verified through codification (TNot Applicable under an approved codification controlled by the sensor. program orthe equipment efficiency Occupant sensor control function in OComplies ratings shall be provided by motor open plan office areas Occupant ODoesNot manufacturer (where certification sensor controls In open office spaces (TNot Observable programs do not exist). — 300 sq ft. have controls 1 J C40582, Escalators and moving walls comply (TComplies (TNot Applicable C40582. with ASME A17 1/CSA B44 and have (TDoesNot 1 automatic controls configured to (Trot Observable [EL28G reduce speed to the minimum (TNot Applicable permitted speed In accordance with off general lighting In all control zones ASME A17.1/CSA B44 or applicable within 20 minutes after all occupants local code when not conveying have leffthe space, 3) are configured passenger so that general fighting power in each C4059 Total voltage drop acass[he (TComplies [EL29]2 combination offeedea and branch (TDoesNot circuits =5% (Trot Observable (TNot Applicable Additional Comments/Assumptions. 1 HighImpact (Tier 1) MediumImpact (Tier ) 1 8 LowImpact (Tier s Project Title CLEAR CREEKANIMAL HOSPITAL Data filename: G:vejobs\Clear CreekAnimal Hospital-29984\Engrtile\Elec calce\2929-0908-CLEAR CREEK ANIMAL HOSPITAL- COM CHECK cck �( COMcheck Software Version 4.1.1.0 Inspection Checklist Energy Code: 2018 IECC Requirements: 0.0% were addressed directly in the COMcheck software Text in the "Comm ants/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, orthatan exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided. Section # & Reg IF Plan Review Complies? hill Comments/ASSumptions C1032 Plans, specifications , and/or OCompiies Commen[aWssumptions CR4j1 calculations provide all information ODoesNot C303.3, with which compliance can be ONotObservable C408 5. determined forthe Interior lighting (TDoesNot 2 and electrical systems and equipment ONDAppiicabie CHF3 and document where exceptions to ONotObservable the standard are claimed Information (TNotAPPuable C4054.1 provided should Include Interior (TComplie See the Interior sorting none whedule for velues IFH8]1 lighting power calculations, wattage of (TDoesNot C405 21. bums and ballasts, transformers and (TNot Observable 1 antral devices. (TNot Observable Additional Comments/Assumptions. 1 jugh impact (Tier 1) MediumImpact (Tier ) 1 8 dow impact (Tier s ProjectTitle CLEAR CREEKANIMAL HOSPITAL Report date 09/98/29 Data filename G.Vyobs\Clear Creek Animal Hospital -29984\Engrtile\Eleccalce\2920.09 08 CLEAR CREEK Page 2of6 ANIMAL HOSPITAL- COM CHECK cck Section # Final Inspection Complies? Commen[aWssumptions & Reg 1D C303.3, Furnished 0&M Instructions for (TComplies C408 5. systems and equipment to the (TDoesNot 2 building owner or designated (TNotObservable CHF3 representative. ONotObservable reasonably uniform Illumination (TNotAPPuable C4054.1 Interni installed lamp and t#ur (TComplie See the Interior sorting none whedule for velues IFH8]1 lig toting p ower is consslent with what (TDoesNot C405 21. is shown on the approved lighting (TNot Observable 1 demonstrating proposed watts (TNot Observable [EL18H pans, so than or equal to al lowed (TNot APPuabe watts (TNot Applicable C408.1.1 Building opeationsand maintenance (TComplies [eCl documentswill be Pmvldedb the ODoesNot owner Documentswm cover nufacturers information(TNotobseaame, specifications, programming (TNot Appliable procedures and means of illustrating to owner how building, equlpmentand syslemsare Intended to be Installed, obtained, and operated. C408 5. Furnished asbull[ drawings for (TComplies 1 electric power systems within 90 days (TDoesNot XI163 of system acceptance. ODoesNot [EL19H lighting In aisleways and open areas is (Trot Observable controlled with occupant sensoathat ONUAPPuabe C408 Lighting systems have been tested to (TComplies X133]1 ensure proper calibration, adjustment (TDoesNot programming, and operation. (TNotObservable control lighting In each disewmy ONUAPPuabe Additional Comments/Assumptions: 1 High Impact(Tier 11) Medium Impact (Tier OL 18 ow Impact (TierBL Section # RoughInElectrical Inspection Complies? Comments/Assumptions & Reg1D C40522. Spaces required to have light OComplies 2 reduction controls have a manual ODoesNot [EL22j1 control that allows the ocmpantto reduce the connetledlight no load In ONotObservable reasonably uniform Illumination (TNot Applicable pattern v 50 percent C4052.1, Occupancy sensors Installed In OComplles C405 21. cassreomslecut re/training moms, ODoesNot 1 conference/meeting/multipurpose (TNot Observable [EL18H ms copy/prutroom s, unges/breakrooms, enclosed offices, (TNot Applicable open plan office areas, restiuoms, storage moms, locker rooms, warehouse storage areas, and other spaces e 300 sgff that are enclosed byfloor-toceiling height Partitions. Reference section language C405. 2.1.2 for control function in warehouses and section C405 2.1 3 for open plan office spaces. C40521. Occupancy sensors control function in Ocomplies 2 warehouses: In warehouses, the ODoesNot [EL19H lighting In aisleways and open areas is ONot Observable controlled with occupant sensoathat automatically reduce lighting power (TNot Applicable by 50% or more when the areas are unoccupied The occupant sensors control lighting In each disewmy independently and do not control lighting beyond the aisleway being controlled by the sensor. C40521. Occupant sensor control function in OComplies 3 open plan office areas Occupant ODoesNot [EL20j1 sensor controls In open office spaces (TNot Observable — 300 sq ft. have controls 1 J configured so that general lighting an (TNot Applicable be controlled separably In control floor areas c 600 sq ft. withiwith n the space, 2) automatically tum off general lighting In all control zones within 20 minutes after all occupants have leffthe space, 3) are configured so that general fighting power in each control zone is reduced by — 80% of the full zone general lighting power within 20 minutes of all occupants that control zone, and 4) are coving nfigured such that any daylight responsive control will activate space general lighting or control zone general lighting onlywhen occupancy forthe same area Is detected. C40522, Each area not served by occupancy OComplies C405 2 2 sensors(per C4052. 1) have time ODoesNot 1, switch controls and functions detailed ONotObservable c40522. sections c4o52v and c4o5 zz 2. 2 (TNat APPname [EL21 1 jugh impact (Tier 11) 1 D ediumimpact (Tier 2) 8 ow impact (Tier B3) Project Title CLEAR CREEKANIMAL HOSPITAL Report date 09/98/29 Data filename: G:vejobs\Clear Creek Animal Hospital-29984\Engrtile\Elec calce\2920.90.98-CLEAR CREEK Page 3of6 ANIMAL HOSPITAL- COM CHECK cck Re ohdate09/08/20 Project CLEAR CREEK AN I MAL H CAPITAL Recondite 09/08/20 ProectTite: CLEAR CREEK ANIMAL HOSPITAL Report h date 09/08/20 P P P Page 4of8 Data filename ANIMAbsHOSPICreek Animal Hospital -20084\Engrtile\Elecalcs12020-00.08-CLEAR CREEK Page 5of8 Data filename ANIMALs\Clear Creek Animal Hpro ital-20084\Engail e\Elecalcs12020.09-OB-CLEAR CREEK Page BofB ANI MAL HOSPITAL- COMCHECK cuk ANI MAL HOSPITAL- COMCHECK cuk FiGlYEN 8 CIATES INC A an �auhlcr� s oaemcK r� 735 S. Xenon Ct. #201 Lakewood, Colorado 80228 Ph: 303.716.1270 Fax: 303.716.1272 www.g ivenandassociates.com Project # 20084 chord". 09-15-2020 OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.C. 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 COPYRIGHT: 2020 THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN CAN ONLY BE USED FOR THIS PROJECT. NO OTHER USE OF THIS DOCUMENT OR THE DESIGNS, IN WHOLE OR PART, ARE PERMITTED WITHOUTTHE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO, P.C. # DESCRIPTION DATE PERMIT SET 09/15/2020 CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Project Number: 20019 ELECTRICAL COM CHECK E401 OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 t: 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.0 1425 MARKET STREET SUITE 220 DENVER, CO 80202 t: 303.694.2445 MEP ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, #201 LAKEWOOD, CO 80228 t: 303.716.1270 CLEAR CREEK ANIMAL HOSPITAL 41 chord design studio WHEAT RIDGE, CO Project Number:20019 PERMIT SET 15 SEPT 2020 ON SITE PLANS MUST BE ON SITE FOR INSPECTION ALL Projects are Subject to Field Inspections fv CIIY of ' W hcatR�dge [OMMUNI IY UEV EIOPMENT APPROVED Reviewed fm Code Camollanse Randy Slusser 11/16/2020 Plans Examiner Dale vexax. eEe<nnm me;sNm.. o/aaemEa•appewre7Whxu«;Mnnm em.afstmnosx. Of 01 of a 1 �Y x ftr m wYv/fM YOWxbru t+.lie bxNN9 cMe vx v/41'�Y bOIN,[H hmYs w•xuMre a oM euElKKilY EeNNnRmmME� er.aw.aun 9xNwamnE .dn e. annvarwn.. W n. aY+bx �M a.axe REVISION JAPPROVED 1/7/2021 RS. o CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: P(,/ Job Address:-! �1' 9 0 Permit Number: Vr` E �l '7r- R C- J J No one available for inspection: Time Z AM/PM Re -Inspection required: Yes '' No When corrections are complete, scheddle re -inspection online, Date: Inspector: DO NOT REMOVE THIS NOTICE 4980 Kipling St A6 FOOTHILLS 202001889 4 COMMERCIAL BUILDERS 7241 South Fulton Street - Centennial, Colorado 80112- (303) 792-5901 Fax: (303) 792-5902 REQUEST FOR INFORMATION Project Number: 21008 RFI Number: BUCCI001-001 Issued to: Information: Michael Slater Project: Clear Creek Animal Hospital 1425 Market Street Suite 220 Date Issued: 2021-02-23 02:28 PM Denver, CO 80202 Required by: 2021-03-02 14:25:37.0 Subject: re-route underground plumbing Request: See attached sketch for requested alternate UG -plumbing route to avoid saw -cutting in client's existing occupied space. Response The proposed solution is acceptable as long as the existing 4 inch sanitary piping that the fixtures are connecting into is at least 17 inches below finished floor or deeper. Judging by the as built drawing it most likely is. GC to field verify. Route affected fixtures at a 1/8 inch per foot slope into the 4 inch sanitary piping as long as it can meet the invert elevation of 17" below finished floor. Given and Associates - Answered by: Josh Lukes ❑ NO EXCEPTION TAKEN M EXCEPTIONS AS NOTED ❑REJECTED ❑REVISE AND RESUBMIT O SUBMIT SPECIFIED ITEM CHECKING IS ONLY FOR GENERAL CONFORMANCE WITH THE DESIGN CONCEPT OF THE PROJECTAND GENERAL COMPLIANCE WITH THE INFORMATION GIVEN IN THE CONTRACT DOCUMENTS. ANYACTION SH OWN IS SU BJECT TO THE REQUIREMENTS OF THE PLANS AND SPECIFICATIONS. CONTRACTOR IS RESPONSIBLE FOR DIMENSIONS WHICH SHALL BE CONFIRMED AND CORRELATED AT THE JOB SITE, FABRICATION PROCESSES AND TECHNIQUES OF CONSTRUCTION, COORDINATION OF HIS WORK WITH THAT OF ALL OTHER TRADES AND THE SATISFACTORY PERFORMANCE OF HIS WORK. CHORD DESIGN STUDIO, P.C. DENVER,COLORADO DATE: 23 Feb 2021 BY: M. Slater Date: 03.02.2021 Signed: iE)SG (X—S—A (PICK tl (F\cv slu ,/ fA AC UNDERGROUND PLU P 1 00 a' z• D a' B' N 0 a-ar s�r WB -1 SIL -1.. 55-1 GENERAL NOTES: 1. EXISTING CONDRpNS SHOWN ON PUNS PRE &SED ON BEST INFORMATION AVNIAPIF, INCLUDING UMREO SHE SURVEY CONDUCTED ON OB -2020. PC SHALL MEW VERIFY ALL EXISTING CONDITIONS ON WHICH NEW WORK IS DEPENDENT, INCLUDING PIPE LOCATION, MATERIAL. SIZE, AND EUNATION/INVERT PRIOR TO STARTING WORK. 2. DEMO ANY PLUMBING `=RES NOT BUNG REUSED AND PLL ASSOCIATED PIPING BACK TO MAIN AND CAP. DEMO PNY PIPING NOT BEING REUSED FOR NEW DESIGN. DRAWING NOTES: O BEFORE NEW CONSTRUCTION, CONIRAGIOR TO DEMO ALL SANITARY PIPING FROM FIXTURES BEING REMOVED. DEMO SANITARY UNE TO MAN AND CAP IF APPLICABLE. CONTRACTOR TO MAKE AD USIMEWS AS NEEDED. O CONNECT NEW SANITARY LINE OF EQUAL OR LESS SIZE INTO EXISTING SANITARY UNE CONTRACTOR TO REM VERIFY SIZE AND INVERT BEFORE CONNECTION. 0 EXISHNG 4' SANITARY LINE OUT TO CML © EXISDNG 4' SANITARY LINE FROM SPACE CONTRACTOR TO MEW VERIFY. rG I AVGE�N 7355. Xenon CI. #201 LokaWOOU. Cobrado 80228 Ph: 303.716.1270 fox: 303.716.1272 "S W.givanan0associotes.cOm PlDjeel q'eYCB4 OWNER CLEAR CREEK ANIMAL HOSPITAL 4980 Y,IPIING ST WHEAT RIDGE, CO 80033 D 303.424.1314 ARCHITECT CHORD DESIGN STUDIO, P.0 1425 MARKET STREET SURE 220 DENVER, C0 80202 F. 3D3.694.2445 MEG ENGINEER GIVEN AND ASSOCIATES 735 S XENON COURT, 11201 IAKEWOOD, GO W228 t 303.716.1270 THIS DOCUMENT AND THE DESIGNS INCORPORATED HEREIN GAN ONLY BE USED FOR THIS PROJECT NOOTHERUSEOFTHIS DOCUMENT ORTHE DESIGNS. IN WHME OR PART ARE PERMITTED WITHOUT THE WRITTEN AUTHORIZATION OF CHORD DESIGN STUDIO. P C. A DESCRIPTION DATE PERMRSET "'/ G*OHI 0 ADDENDUM nt 1111.8 CLEAR CREEK ANIMAL HOSPITAL 4980 KIPLING ST. WHEAT RIDGE, CO 80033 Pmpa Numb. 20019 UNDERGROUND PLUMBING PLAN P100 e i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type:r rt Job Address: = c: S _0 Permit Number: c)() (-\� 0 r ❑ No one available for inspection: Time t.. AM/PM Re -Inspection required: Yes No When corrections have been made, schedule for re -inspection online at: http://www. ci. wheatridge. co. uslinspection Date:, ' Inspector: L^ 1 DO NOT REMOVE THIS NOTICE d O Cl �" M N •� N s L o A o� s o0o d w O c O O N00 Z cl ea end ° 00U A O w '° �° r-. W O ,d "n o do o 4J H a cc 00 o o w.c o �Q�F w �+� n.3� QU °waroi O �^ O d O Ci H ' ' F o d +�+ .� oto c�C .-by '.74-4 L� Fri W O V O 4J U4 ° d zOa' do`Do�U�" ro w V d"C3 N�O y s .+ at 0 r -I w 4 O un GG m $4 C7 'C U 0 C7 O 4" a 0 cd 3 0 00 CU i C a 0 ° Q � W z a� zc) OAz4 " o cu O as WQA�O u C �aA 'a z N ~ eCa w 0� u� zzoaxz m N O.Z OUaa�U u0 �v w O y A 0 U a �b a w � U 4J $4 0 row U w q 4 U b U m 0 O U a PERMIT NO. 201900175 City of Wh6atf<ji!jgc BUSINESS LICENSE INSPECTION INSPECTION DAY/TIME Thurs. May 24 @ BF1 INSPECTION DAY/TIME �Gi- �S-k g% 7 INSPECTION DAY/TIM BUSINESS NAME: Little Scissors & Anita's Gifts ADDRESS: 4980 Kipling Street #A1-2 CONTACT NAME: 2280 SQ FT 8 OCCUPANCY TYPE R� OCCUPANCYLOAD JCONSTRUCTION TYPE ❑ SPRINKLERED 1_1q�] NON-SPRINKLERED Inspector Signature Date 0 gqq� *** CONTACTS *** OWNER 720-662-8525 PINNACOL REAL ESTATE MGMT SUB (303)422-7440 GARRET GIFFORD 019918 FASTSIGNS OF ARVADA *** PARCEL INFO *** ZONE CODE: UA / Unassigned USE: UA / Unassigned SUBDIVISION CODE: 330 / General Retail BLOCK/LOT#: 0 / *** FEE SUMMARY *** Total Valuation Plan Review Fee Use Tax Permit Fee ** TOTAL ** *** COMMENTS *** ESTIMATED PROJECT VALUATION FEES 0.00 26.07 17.26 40.10 83.43 822.05 *** CONDITIONS *** Approved per plans and red -line notes on plans. Must comply with 2012 IBC, 2017 NEC and all applicable City of Wheat Ridge Municipal Codes. Work is subject to field inspections. **Prior to final inspection approval - As-builts are required before approval of the Building Final Inspection and Certificate of Occupancy can be issued. City of Wheat Ridge P� Commercial Sign PERMIT - 201902009 PERMIT NO: 201902009 ISSUED: 09/20/2019 JOB ADDRESS: 4980 Kipling St Ste Al EXPIRES: 09/19/2020 JOB DESCRIPTION: Adding injection molded dimensional letters to storefront installed with stud mounts; including existing 8 ft x 2 ft cabinet sign not previously permitted *** CONTACTS *** OWNER 720-662-8525 PINNACOL REAL ESTATE MGMT SUB (303)422-7440 GARRET GIFFORD 019918 FASTSIGNS OF ARVADA *** PARCEL INFO *** ZONE CODE: UA / Unassigned USE: UA / Unassigned SUBDIVISION CODE: 330 / General Retail BLOCK/LOT#: 0 / *** FEE SUMMARY *** Total Valuation Plan Review Fee Use Tax Permit Fee ** TOTAL ** *** COMMENTS *** ESTIMATED PROJECT VALUATION FEES 0.00 26.07 17.26 40.10 83.43 822.05 *** CONDITIONS *** Approved per plans and red -line notes on plans. Must comply with 2012 IBC, 2017 NEC and all applicable City of Wheat Ridge Municipal Codes. Work is subject to field inspections. **Prior to final inspection approval - As-builts are required before approval of the Building Final Inspection and Certificate of Occupancy can be issued. City of Wheat Ridge Commercial Sign PERMIT - 201902009 Y PERMIT NO: 201902009 ISSUED: 09/20/2019 JOB ADDRESS: 4980 Kipling St Ste Al EXPIRES: 09/19/2020 JOB DESCRIPTION: Adding injection molded dimensional letters to storefront installed with stud mounts; including existing 8 ft x 2 ft cabinet sign not previously permitted I, b my sJildin , do he a attest that the work to be performed shall comply with all accompanying approved plans and specifications; app cablg code , a d all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized by t legof th pro erty and am authorized to obtain this permit and perform the work described and approved in conjunction with this er atte t th I am legally authorized to include all entities named within this document as parties to the work to be per ort all w rk t be perto a is disclosed in this documentd/or r';' accompanying approved plans and specifications. Signature of O o CONTRACTOR (Circle one) D to I. This per ' was issued based on the information provided in the permit application and accompanying plans and specifications and is subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures. 2. This permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and received prior to the date of expiration. An extension of no more than 180 days made be granted at the discretion of the Chief Building Official and may be subject to a fee equal to one-half of the originalpermit fee. 3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard requirements, fees androcedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of the Chief Building Official and is not guaranteed. 4. No work of any manner shall be performed that shall results in a change of the natural flow of water without prior and specific approval. 5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all required inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services Division. 6. The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, any violation of any provision of any applicable code or any ordinance o regulation of this jurisdiction. Approval of work is subject to field inspection. Signature of Chief Building Official Date REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. City of `)`I heat idge COMMUNI n' DE.Vt:L01'ME.N i Building & Inspection Services Division 7500 W. 291h Ave., Wheat Ridge, CO 80033 Office: 303-235-2855 * Fax: 303-237-8929 Inspection Line: 303-234-5933 Email: permits(a)ci.wheatridge.co.us FOR OFFICE USE ONLY Date:/71q �� ILI Plan/Permit # � 0 a Plan Review Fee: Building Permit Application *** Please complete all highlighted areas on both sides of this form. Incomplete applications may not be processed. *** Property Address: Owner iia Property Owner Email: C )� Tenant (Commercial Projects Only) ��Lk r� �,L� /� :X,l(�+'1 Property Owner Mailing Address: (if different than property address) Address: State. Zi r_TR.if[l _i I. I I I IT] Arch itect/Eng 1 neer E-mail: Contractor Name: City of Wheat Ridge License Contractor E-mail Address: Phone: Phone: �d_� "q1a - 1 LIC) �J For Plan Review Questions & Comments lease print): CONTACT NAME (please print): Q�C�� Phone: Jg�V CONTACT EMAIL(p/ease print): Sub Contractors (Must provide Wheat Ridge License No.): Electrical: Plumbing: Mechanical: W.R. City License # W.R. City License # W.R. City License # Other City Licensed Sub: City License # Other City Licensed Sub: City License # �❑ COMMERCIAL ❑ RESIDENTIAL Description of work: For ALL projects, provide a detailed description of work to be performed, including current use of areas, proposed uses, square footage, existing condition and proposed new condition, appliance size and efficiency, type and amount of materials to be used, etc. Mel t t -to LAC 'f L911 jJ bL �� C �� Sq. Ft.- { Q L BTUs q f B VUs Amps Squares Gallons Commercial Projects Only: Occupancy Type: Construction Type: Occupancy Load: Project Value: (Contract value or the cost of all materials and labor included in the entire project) $ OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance with applicable City of Wheat Ridge codes and ordinances for work under any permit issued based on this application; that I am the legal owner or have been authorized by the legal owner of the property to perform the described work and am also authorized by the legal owner of any entity included on this application to list that entity on this application. 1, the applicant for this building permit application, warrant the truthfulness of the informationp� vided on tlr,application. CIRCLE ONE: (O Signature (first and last Printed Name: ZONING COMMMENTS: Reviewer: BUILDING DEPARIXENT OMMENTS: 12 L/ � Reviewer: 4li'"(� PUBLIC WORKS COMMENTS: Reviewer: ------------ (AU ZED REPRESENTATIV) of (OWNER) ONTRACTOR)J ✓� �` DATE: DEPARTMENT USE ONLY OCCUPANCY CLASSIFICATION: CONSTRUCTION TYPE: Building Division Valuation: Wall Sign Calculation Sheet You must complete this sheet and include it in the submittal package for any new wall signs. You will also need to create a site plan and a detail sheet of the signage. E n Project Address: 0A Contractor:, You are allowed 1 square foot of signage for every 1 linear foot of wall to which you are attaching a sign. All wall signs must be adjacent to a street or major interior drive. Step 1: Measure the length of the wall(s) where you are attaching the sign: Wall 1 - feet Wall 2 - feet Wall 3 - feet Step 2: The length of the wall is the allowable square footage for the wall sign. Wall 1 allowable signage- square feet Wall 2 allowable signage- square feet Wall 3 allowable signage- square feet Site Plan 5,1%^ I . t U 'T13 ,4 5;�� Z 16.2 s Reviewed for m r I ian c r by the City of Wheat Ridge Plannirg Div;, on APPROVED BY: �i� DATE: 41 me^lq COMMENTS: A )W HIRING LA ° O� n D N �<UG, O Z w ID 00 �0 O n 7 n : �<=I FN l O 0 ^N G7 go p �'n �doa,�N n- .i. 0-i M' < q Q V CD P o.3'D ° �g33 n^mo;o��M�c— o ° n v ro o w o" 0 o o n *, * v+ v n m'9 _'D " 0, .w. '" ® *, °° i a rn n o T< , a�w+a DFS o C =n��vmaw.c —_" T - o m o F � 'n <w�= tSp �.D nO .NNrpwd pia co fm w a oc3.a Nw a (D Ej _ n� '<O n ° 7 D'rV i3 D A a o N w N � •°K -O M-0 nv w <n • • O -V W . O FS`< . 3,:p � i5'0 cl.f - r m ^ O} .A �/ Mm ''pco1D, :E Dn O 4 LA 0. ID <von.noG =mm' oc ^c 000cMn m rn m �. D O .��. d� N= ° D nce m ab - ° N �� 7Nin On7•— r) .o Z G1 �o N c n _n m En a c .. n n 3 m -` w < a = D n'O O ON _�' n° I� ;K0 5., � w 0 Z) NA'S ��p-o �B,� � � n -=wW �o�v° �� -n< o -Sc eD � °c ul 0, rD Oma' = ,00. � � o t a n a �va K °M z Z0 vs ONpn m n n Qa�n< o p9a -rDi O z Z 3• � w o Z °'mm N 4 D. O D' 2 O o`0 � 4 7c O � 4 i Z '0 D Q c p 4 I c o .T _ n n CL ID M m (�LD rL Z q Q O dtD nm a nryl o Z y w ep 4) tz rl wwov rD A �IC< Z Ea3a C-) o -� T1 �� D _awn <?D w = o n 7 nJ 'k S C N 1 .� nm ° �_ �• ~ e'M1Y LA ° O� �.m ID bD S. N O 00 O C O 0 0 � j ° C Q V CD P O Li rD Q CL O rp .- �°ai NJ 3 f F rD O S C rD � to S L co q in M 0 ti FAST,S/GNS® More than fast. More than signs:" CONSULTING GRAPHIC PROJECT SURVEYING& SIGNS& INTERACTIVE DESIGN PLANNING PERMITTING GRAPHICS &DIGITAL ® 2012 FASTSIGNS International, Inc. 7320 W. 52nd Ave. Arvada, CO 80002 1 t: 303.422.7440 1 f: 303.422.2076 1 e: 2320fastsigns.com ( fastsigns.com/232 INVOICE/EST. #77359 18.889"hx82.74"w (letter height: 18") Injection molded letters with paper pattern with combo stud/pad mounting with install Qty. 1 *Shown on building sign band of 24"hx421 "w 1 0 'z ) . Reviewed dor 2on�ng Co'moliance by the , City of Wheat Ridge Planning Division y APPROVED BY: DATE: 01(Zo/ i" COMMENTS: C0**0'pi;,eS 4-4/ Sjipi t o<A PROOF #2 All original artwork contained within shall remain intellectual property of FASTSIGNSO of Arvada and is not to be duplicated or distributed without the written consent of FASTSIGNSO of Arvada. We reserve the right to photograph and/or distribute or publish for our company's promotional and marketing needs any work we create for you, including mock-ups and comprehensive presentations, as samples for our portfolio, newletter, brochures, slide presentations and similar media. "y OL" At FASTSIGNSO, we take pride in precision, but the final examination for accuracy is your responsibility. In the event that we have miscommunicated regarding your original design, we will be happy to provide a second proof. Please note any and all changes at one time for faster proofing and be specific as possible. We will send the revised version the following work day. Our normal production cycle will begin from the date approval is received. We cannot accept changes or approvals verbally. BEFORE GIVING APPROVAL, PLEASE EXAMINE CAREFULLY for the accuracy of information presented, as well as: • Spelling • Punctuation • Numbers • Graphics • Colors • General layout. COLOR DISCLAIMER: Please note that images viewed on monitors do not represent the appearance and exact color of the final product, due to the variance of RGB and CMYK and other factors in the large format printing process. If you have specific colors (pantone or otherwise) that you are trying to match, please request a test print, or swing by the store and choose your colors from our color print simulations - THANKS! SPECIFICATIONS: DESCRIPTION: QTY: SIDES: INSTALLATION: NOTES: APPROVED, AS IS APPROVED, WITH CHANGE Yost" of oermit� nw hsu a of a prima a aowovaaf F andrwacatiam S^a11 ot be a �° fa,, a, mrooftePn% 6111Z,codr ❑ REVISE, SEND NEW PROOF p raffir t" to 9W W to noble Mcome tht wawa m% 0, iii..- iw,46 w rales or 4,tk—ar wmet of ft 00"60 be -OW Signature Date PLEASE NOTE: 2 proofs provided. Any further proofs APPROVED will be billed at $10 minimum each. If further revisions are required after approval has been NoWewed for Code Com ceived, additional charges will be incurred. APPROVED, AS IS APPROVED, WITH CHANGE Yost" of oermit� nw hsu a of a prima a aowovaaf F andrwacatiam S^a11 ot be a �° fa,, a, mrooftePn% 6111Z,codr ❑ REVISE, SEND NEW PROOF p raffir t" to 9W W to noble Mcome tht wawa m% 0, iii..- iw,46 w rales or 4,tk—ar wmet of ft 00"60 be -OW Signature Date N T A=Main Si( =Existing "-�4 n V) 5otr LOT UIL ng St Unit 1, Wheat Ridge, I LITTLE SCISSORS SALON 80033 ire°t�la9g`s�oo Q�J i CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type: 6L -17 Job Address: t4 G1 52 C) !c c S Permit Number: 0 1 CI C) G= f J ❑ No one available for inspection: Time t AM/PM Re -Inspection required: Yes No When corrections have been made, call for re -inspection at 303-234-5933 r Date:-., " ��;�> ' i Inspector: DO NOT REMOVE THIS NOTICE M- i CITY OF WHEAT RIDGE -1�9rBuilding Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type:= i-- =- Job Address: Permit Number: ❑ No one available for inspection: Time AM/W/ Re -Inspection required: _Yes o When corrections have been made, call for re -inspection at 303 -234- Date: - 03 -234 -Date: `� ` Inspector: , DO NOT REMOVE THIS NOTICE i CITY OFWHEATRIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type: 9 \ U %y\S �v t tin a Job Address: \ ;r\ r <A. Permit Number: aC1 \C� C U 171C Lf Ll No one available for inspection: Time AM%I M,� Re -Inspection required: Yes�_ When corrections have been made, c`�lrfor re -inspection at 303-234-5933 Date: `5• 2,U - 1'` Inspector:: DO NOT REMOVE THIS NOTICE A i CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type: Job Address: l NX, <' Permit Number: ❑ No one available for inspection: Tin46;:-�'M Re -Inspection required: Yes When corrections have been made, cal re -inspection at 303-234-5933 Date:; ``Inspector. DO NOT REM E THIS NOTICE i CITY OF WHEAT RIDGE 1�9�Building Inspection Division (303) 234-5933 Inspection line 1(303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type: Job Address: I+�? Permit Number: �a� ❑ No one available for inspection: Tirrle- AM/PM Re -Inspection required:,, --Yes ) No When corrections have been made, call,,' f r re -inion at 303-234-5933 i Date:_- ' Inspector. 1 DO NOT REMOVE THIS NOTICE i CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax C INSPECTION NOTICE Inspection Type:(' - Job Address:D r_ ,� 51- Permit Number: c7 6 Cr- Llok- No one available for inspection: Time i AM/PM Re -Inspection required: Yes No When corrections have been made, call for re -inspection at 303-234-5933 .h Date: J 2 1 Inspector: <o) DO NOT REMOVE THIS NOTICE 1�� rn 1 <"-) --3 q'('o FRONT RANGI TEST • BALANCE TEST AND BALANCE REPORT FOR LITTLE SCISSORS & ANITA'S GIFTS 4980 KIPLING STREET, UNIT 1 WHEAT RIDGE, COLORADO MAY 2019 PREPARED BY: FRONT RANGE TEST AND BALANCE, INC. Front Range Test & Balance, Inc. certifies that all balancing is done in accordance with NEBB, AABC and ASHRAE standards. P.O. Box 630112 - Highlands Ranch - Colorado - 80163-0112 FRONT O r , TEST & BALANCE May 21, 2019 Wheat Ridge Building Department Wheat Ridge, Colorado RE: LITTLE SCISSORS & ANITA'S GIFTS To Whom It May Concern: All test and balance work on the Little Scissors & Anita's Gifts in Wheat Ridge, Colorado has been completed in accordance with NEBB, AABC, and ASHRAE standards. Please let me know if you need anything else with regard to the Air Balance Report for Little Scissors & Anita's Gifts. Sincerely, Chris Cooper President Front Range Test & Balance, Inc. FRONT RANGE TEST AND BALANCE PROJECT: LITTLE SCISSORS & ANITA'S GIFTS FAN TEST REPORT FAN DATA FAN NO. RTU -1 FAN NO. RTU -2 FAN NO. EF -1 Location ROOF ROOF CEILING Service NORTH SOUTH NAIL SALON Manufacturer AMERICAN STANDARD AMERICAN STANDARD NU -TONE Model Number 2YCC3048A1 2YCC3048A1 EZ80N-B Serial Number 7215X889H 7201KV79H 91A26C1 Motor Make/Frame NG NG BROAN / NG Motor H.P./RPM 3/4/1080 3/4/1080 7/735 Volts/Phase/Hertz 208/1/60 208/1 /60 120/l/60 F.L. Amps/S.F. 4.4 / T. P. 4.4 / T. P. .18 / T.P. Motor Sheave Make DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE Motor Sheave Diam./Bore DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE Fan Sheave Make DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE Fan Sheave Diam./Bore DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE No. Belts/Make/Size DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE Sheave CL Distance DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE Filters 2 - 20X2OX2 2 - 20X2OX2 TEST DATA DESIGN ACTUAL DESIGN ACTUAL DESIGN ACTUAL CFM 1680 1646 1680 1624 80 81 Fan RPM NG DD NG DD NG DD Outside Air 336 341 336 339 Voltage 208 212 208 212 120 120 Ampera e 4.4 2.7 4.4 2.7 .18 .1 REMARKS: EXISTING EF IN RESTROOM = -71 CFM TEST DATE: 5/21/2019 READINGS BY: CC & JR FRONT RANGE TEST AND BALANCE PROJECT: LITTLE SCISSORS & ANITA'S GIFTS SYSTEM: RTU -1 AIR OUTLET TEST REPORT TEST APPARATUS: FLOW HOOD AREA OUTLET DESIGN PRELIMINARY FINAL FINAL REMARKS SERVED NO. TYPE SIZE AK CFM VEL/CFM CFM % 1 CD 24X24 1.0 420 280 427 102% 2 CD 24X24 1.0 420 284 418 100% 3 CD 24X24 1.0 420 217 401 95% 4 CD 24X24 1.0 420 234 400 95% TOTAL 1680 1646 98% RTU -2 1 CD 24X24 1.0 560 567 537 96% 2 CD 24X24 1.0 560 551 530 95% 3 CD 24X24 1.0 560 213 557 99% TOTAL 1680 1624 97% REMARKS.- (D CORRECTED FOR ALTITUDE TEST DATE: 5/21/2019 READINGS BY: CC & JR T �i r CD cl) u -4 O \ m m O m 96'-0" ` VMASSAGEIFACIAL Ng N m l O v �i 30 .c vii 6 �u 3� T �i r CD m D 3 i a PRODUCTSIGIFTS 6'-2" cl) u -4 O \ m m O m 96'-0" ` D N N m l O v �i m D 3 i a PRODUCTSIGIFTS 6'-2" m m n D m v �i 30 m 3a i CITY OF WHTAT MIDGE Building Inspedtion'Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type:' _ Job Address:/ Permit Number:�i ❑ No one available for inspection: Time �� r5 'LA. M Re -Inspection requireq,' Yes No When corrections have beden�m `de, call for re -inspection, at 303-234-5933 Date:--- � Inspector: A— DO NOT REMOVE THIS NOTICE i . CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (3a 237-8929 Fax INSPECTION NOTICE Inspection Type: Job Address: L4 Cq�— Permit Number: IMVA�WFMM ❑ No one available Re -Inspection required: Yes No e (( ZC :) AM/PM When corrections have been made, c for re -inspection at 303-234-5933 Date -Z �_ Z Inspector'. DO NOT REMOVE THIS NOTICE i CITY OF WHEAT RIDGE Building Insp4ction Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE 1. Inspection Type:? Job Address: `% :;a� i---t''L.,1 7 .- �_• Permit Number: 0--l. j']1 ❑ No one available for inspection: Time%'`�I-+'AfMIPM Re -Inspection required: Yesj OL) When corrections have been made, call for re -inspection at 303-234-5933 Date: t:) 1 < 1 i Inspector:`. DO NOT REMOVE THIS NOTICE i CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type: `-� Job Address: Permit Number: 2. f 7Q, ❑ No one available for inspection: Tim AM/PM Re -Inspection required: Yes No When corrections have been made, call r re -inspection at 303-234-5933 DateO -- Inspect 1 DO NOT REMTHIS NOTICE i CITY OF WHEAT,RIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type: Job Address: t=1 Permit Number: 1' fi JQ ❑ No one available for inspection: Time 1U.' 1-5 AM/#M Re -Inspection required: YesLNo When corrections have been made, call for re -inspection at 303 -234 - Date: 3, /� i Inspector: DO NOT REMOVE THIS NOTICE i 41TY O.F. WHET RIDGE Build6t Inspele'tion Div%ion (303) 234-5933 Inspection line (303) 235-2855. Office • (303) 237-8929 Fax I�NS PEC/ ON Inspection Type: . Job Address: - -- -- - - :�._ ❑ No one available for inspection: Time AM/PM Re -Inspection required: Yes No When corrections have been made, call for re -inspection at 303 -234 - Date: r A° Inspector: /_,; —- DO NOT REMOVE THIS NOTICE i CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Typb: 311q F, Job Address: qqqo - 5t - Permit t -Permit Number: 2-019G0 3217 ❑ No one available for inspection: ' e V / "/ AM/PM Re -Inspection required: YesNo When corrections have been made, call for re -inspection at 303-234-5933 Date: Inspector:_ iii► 1iY DO NOT REMOVE THIS ,NOTICE City of Wheat Ridge Comm. Tenant Finish PERMIT -201900396 I PERMIT NO: 201900396 ISSUED: 04/08/2019 JOB ADDRESS: 4980 Kipling St Ste Al EXPIRES: 04/07/2020 JOB DESCRIPTION: Tenant finish to include new 200 amp electric service; new lighting, plumbing, outlets, fixtures for new breakroom, salon area and massage room - 2,280 sq ft total Tenant: Little Scissors & Anita's Gifts *** CONTACTS *** OWNER 720-662-8525 PINNACOL REAL ESTATE MGMT GC (303)286-1965 Kerry Schell 018995 KASCO COMMERCIAL SUB (303)330-0550 JOE GONZALES 110022 HONEST PLUMBING LLC SUB (303)400-4321 Edward Jueschke 021943 SJO Electric LLC *** PARCEL INFO *** ZONE CODE: C-1 / Commercial USE: UA / Unassigned SUBDIVISION CODE: 330 / General Retail BLOCK/LOT#: 0 / *** FEE SUMMARY *** Total Valuation Plan Review Fee Use Tax Permit Fee ** TOTAL ** *** COMMENTS *** ESTIMATED PROJECT VALUATION FEES 0.00 735.83 2,093.12 1,132.05 3,961.00 99,672.48 *** CONDITIONS *** All roughs to be done at Framing Inspection. Approved per plans and red -line notes on plans. Must comply with 2012 IBC, 2017 NEC and all applicable City of Wheat Ridge Municipal Codes. Work is subject to field inspections. **Prior to final inspection approval - As-builts are required before approval of the Building Final Inspection and Certificate of Occupancy can be issued. City of Wheat Ridge "- Comm. Tenant Finish PERMIT - 201900396 PERMIT NO: 201900396 ISSUED: 04/08/2019 JOB ADDRESS: 4980 Kipling St Ste Al EXPIRES: 04/07/2020 JOB DESCRIPTION: Tenant finish to include new 200 amp electric service; new lighting, plumbing, outlets, fixtures for new breakroom, salon area and massage room - 2,280 sq ft total Tenant: Little Scissors & Anita's Gifts I, by my signature, do hereby attest that the work to be performed shall comply with all accompanyingg approved plans and specifications, applicable building codes, and all applicable municipal codes, policies and procedures, and that I am t1�e legal owner or have been authorized by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with thisermit. I further attest that I am legally authorized to include all entities named within this document as parties to the work to be performed anworktobe rfo-rmed is disclosed in this document and/or its' accompanying approved plans and specifications. /r`d�lu�t� ja 1 e /� Signatut'e of ,OWNER or CONTIrACTOR (Circle one) /lute 1, This permit was issued based on the information provided in the permit application and accompanying plans and specifications and is subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures. 2. This permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and received prior to the date of expiration. An extension of no more than 180 days made be granted at the discretion of the Chief Building Official and may be subject to a fee equal to one-half of the originalpermit fee. 3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard requirements, fees androcedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of the Chief Building Off-cial and is not guaranteed. 4. No work of any manner shall be performed that shall results in a change, of the natural flow of water without prior and specific approval. 5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all required inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services Division. 6. The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, any violation of any provision of any applicable code or any ordinance or regulation of this jurisdiction. Approval of work is subject to field inspection. Signature of Chief ' ffx$dPV,20ff-� Date REQUESTS MUST BE MADE Bk 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. FOR OFFICE USE ONLY Date: j City of Wheat�idge J Cl COMMUNITY DEVELOPMENT Plan/Permit#�l�'� 0�+1"( �n Building & Inspection Services Division , 7500 W. 29th Ave., Wheat Ridge, CO 80033 Plan Review Fee: ( n Office: 303-235-2855 * Fax: 303-237-8929 Inspection Line: 303-234-5933 Email: Permits(d)ci.wheatridge.co.us Building Permit Application *** Please complete all highlighted areas on both sides of this form. Incomplete applications may not be processed. *** Property Address: Prooerty Owner Phone:' Property Owner Email: J [ i Tenant (Commercial Projects Only) Property Owner Mailing Address: (if different than property address) Address: City, State, Zip: eo!�' Architect/Engineer E-mail: Phone: Contractor Name: &&/r, ;?;- /G , City of Wheat Ridge License #: Phone: _A . ��� `��.� Contractor E-mail Address:%SSC-U For Plan Review Questions & Comments (please print): CONTACT NAME (please print): 5eAe/( Phone:_ CONTACT EMAIL(p/ease print): Sub Contractors (Must provide Wheat Ridge License No.): Electrical: Plumbing: Mechanical: W.R. City License # W.R. City License # W.R. City License # Other City Licensed Sub: Other City Licensed Sub: City License # City License # �RbOMMERCIAL ❑ RESIDENTIAL Description of work: For ALL projects, provide a detailed description of work to be performed, including current use of areas, proposed uses, square footage, existing condition and proposed new condition, appliance size and efficiency, type Ad amount of materials to be used, etc. ,I/IICFi S/'�✓ I / � �G'tG���C� ��1�'�rS � � y'c�t✓/•� ter^r' ����/ / !�'�G<� i/��l/ T��S `,f�Fs��ry� Sq. FULF V BTUs Amps Squares _ Gallons Commercial Projects Only: Occupancy Type: Z3 Construction Type: - V% Occupancy Load: `J Project Value: (Contract value or the cost of all materials and labor included in the entire project) OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance with applicable City of Wheat Ridge codes and ordinances for work under any permit issued based on this application; that I am the legal owner or have been authorized by the legal owner of the property to perform the described work and am also authorized by the legal owner of any entity included on this application to list that entity on this application. I, the applicant for this building permit application, warrant the truthfulness of the information provided on the application. CIRCLE ONE: (OWNER) (tNTR�ACTO~R) or (AUTHORIZED REPRESENTATIVE) of (OWNER) (CONTRACTOR) Signature (first and last name): "fit tee✓- y DATE: Printed Name: 2 '2n,/ DEPARTMENT USE ONLY ZONING COMMMENTS: OCCUPANCY CLASSIFICATION: CONSTRUCTION TYPE: Reviewer: ,J BUILDING DEPARTMENT COMMENTS:, 0.J __ = j (7 Cy x cl Reviewer: — e W toC _ 5 PUBLIC WORKS COMMENTS: Reviewer: Building Division Valuation: - L/� Kimberly Cook From: KERRY A SCHELL <kasco33@msn.com> Sent: Friday, March 8, 2019 1:19 PM To: CommDev Permits Subject: Fw: Permit Application returned for review - Arvada Fire Protection District Sent from Outlook From: No Reply@mobile-eyes.com <NoReply@mobile-eyes.com> Sent: Thursday, March 7, 2019 2:02:15 PM To: kasco33@msn.com Subject: Permit Application returned for review - Arvada Fire Protection District Your permit request for Little Scissors And Anita's Gift's at STE 1-2, 4980 Kipling Street Wheat Ridge, CO 80033 has been returned. The AFPD has made the following comments: 3/7/2019 4:02:15 PM - Submitted plans must all be properly oriented, meaning face up, not sideways or upside down, so that the document can be viewed without rotating it. Individual plan pages must be combined into one pdf document. You can correct the application from the online portal and re -submit the application to the Arvada Fire Protection District Community Risk Reduction Division. G MobileEyes ENABLING A SAFER WORLD User Options Welcome back Kerry Schell (KASCO Commercial, Inc.) Log Off Update Account Help Videos Single Portal Account Overview allow to Find Your Active Jobs How to Request an Inspection How to Request Multiple Inspections HOW to Cancel an Inspection Contractor Permit Portal Help Desk: 866-442-9002 (8a -8p EST) Email: help@mobile-eyes.com Applications City/Dept.: Arvada Fire Protection District • btart New application Just My Jobs " All Jobs for my company Address: Occupant: Street: Status: " All Unsubmitted — Submitted Address Little Scissors And Anita's Gift's STE 1-2 4980 Kipling Street Wheat Ridge, CO 80033 Job Type: Search Returned Clear Filters Job Type Status Tenant Finish/Remodel Submitted 3/7/2019 8:18:29 PM Active Jobs Just My Jobs All Jobs for my company Address: Occupant: Street: Schedule Status: • All Scheduled , Unscheduled Address No matches Job #: Search 11 Clear Filters Job Type / # Status Scheduling Completed/Canceled Jobs Just My Jobs All Jobs for my company Address: Occupant: Street: Job #: Status:Search 8 All Completed Canceled Clear Filters Permit Application returned for review - Arvada Fire Protection District NoReply@mobile-eyes.com Thu 3/7/2019 2:02 PM To: kasco33@msn.com <kasco33@msn.com> Your permit request for Little Scissors And Anita's Gift's at STE 1-2, 4980 Kipling Street Wheat Ridge, CO 80033 has been returned. The AFPD has made the following comments: 3/7/2019 4:02:15 PM - Submitted plans must all be properly oriented, meaning face up, not sideways or upside down, so that the document can be viewed without rotating it. Individual plan pages must be combined into one pdf document. You can correct the application from the online portal and re -submit the application to the Arvada Fire Protection District Community Risk Reduction Division. AAA Asbestos Analysis LLC. P.O. Box 116 Arvada, CO 80001 303-907-7866 Lesrees00(a gmail.com February 21, 2019 Kasco Commercial/Kerry 4980 Kipling St. #1 & #2 Wheat Ridge CO., Attention: Kerry, Report of Findings /Limited Asbestos Survey to include the Following Suspect Area's In Unit #1 & #2 to be Disturbed & Remodeled, Only, No other Area's were tested. Homogenous Area #1 Drywall/Texture/Joint Compound in Dressing Closets in Unit #1 & #2 (S0014003) Homogenous Area#2 Ceiling Panels 2'x 4' (MO01-M002). Homogenous Area#3 Carpet Adhesive/Carnet (M003 -M004). Homogenous Area#4 Cove Base Adhesive (MO05-MO06). ONLY THESE MATERIALS ARE COVERED IN THE SURVEY. Asbestos Survey for Suspect Affected Materials in Garage which affects above Area's to Be Remodeled (Named Above), Samples were collected at #1 & #2 4980 Kipling St, Wheat Ridge CO. AAA Asbestos Analysis LLC. provides the following "LIMITED ASBESTOS SCOPE/SURVEY" of the above-mentioned address, which included collection of "suspect" bulk samples and walk-through inspection to determine any Asbestos Containing Materials (ACM) that needs to be addressed as a result of a customer concern of Suspect Affected Building Materials in the Area's mentioned above, only. This Asbestos Survey is "limited" to the suspect Asbestos Containing Materials (ACM) mentioned above, only. These Suspect Materials to be removed, demolished or disturbed , only. No other suspect materials were observed that could be disturbed during #1 & #2 Remodeling Activities. If other "suspect materials" are hidden, buried or uncovered during the Removal & Demolition Activities, Stop work Immediately & do not proceed with removing any other suspect material, until it is tested. The walk-thru, "Limited Scope" bulk sampling and "change of custody" of the bulk sampling to EMSL Inc. were conducted on February 20, 2019. Work was performed by a certified and accredited Asbestos Building Inspector / Les Rees with an EPA and State of P.O. Box 116 Arvada, CO 80001 / lesrees00@gmail.com / AsbestosTestDenver.com t alp ACF -24074. This inspection was limited to the Suspect Areas mentioned above, only. SCOPE OF WORK Nine (9) Bulk Samples" were collected from "Suspect Materials" from the above mentioned Areas mentioned to be, disturbed, demolished or remodeled, only. These "bulk Samples" were taken from these areas @ 4980 Kipling St #1 & #2 Wheat Ridge CO. Nine (9) representative bulk samples of "suspect" ACM were submitted to the lab for PLM testing. These Bulk samples were collected randomly, pursuant to EPA and OSHA asbestos inspection regulations from homogeneous areas of suspect ACM. Nine (9) Bulk Samples were collected and given Alpha Numeric Identification Numbers according to EPA regulations 4980-#1&2-022019- 5001-5003 & M00 ] -M006. Only, SOOI-S003 & M001 -M006, will be used in this reportfrom this pointforward. There are 3 Categories of ACM (Asbestos Containing Material) Surfacing, Miscellaneous and TSI/Thermal Systems Insulation. ACM is either "friable" or "non - friable." Some non -friable ACM's can be rendered friable by movement. ACMs can be in three (3) conditions: "good", "damaged", or "significantly damaged". The Three (3) Drywall/Texture/Joint Compond Samples (5001-5005). These Samples were taken from Dressing Closet Area's from the inside of the Unit. They are in the Surfacing Category. They are Friable & in Good Condition. This Entire Area contains approximately total 368 square feet of Homogenous Drywall/Joint Compound/Texturing Surfacing. The Two (2) Ceiling Panel Samples (M001 -M002). These Samples were taken from the Ceiling Panel Area. They are in the Miscellaneous Category. They are Friable & in Good Condition. This Area has approximately 2400 total square feet of Homogenous Ceiling Panels. The Two (2) Carpet/Adhesive Samples (M003 -M004). These Samples were taken from the Carpeting on the Floor. They are in the Miscellaneous Category. They are Non -Friable & in Good Condition. This Area has approximately 2400 total square feet of Homogenous Carpet/Adhesive. The Two (2) Cove Base Adhesive Samples (MO05-M006). These Samples Were taken from the Cove Base on the Walls. They are in the Miscellaneous Category. They are Non -Friable & in Good Condition. This Area has approximately 66 total square feet of Homogenous Cove Base Adhesive. P.O. Box 116 Arvada, CO 80001 / lesrees00@gmail.com / AsbestosTestDenver.com LAB PROCEDURES Diagram. Bulk Samples were delivered to EMSL Lab, for a 24 -Hour Turnaround. Bulk samples are stored for six (6) months unless otherwise stipulated. EMSL Inc., a third - party independent lab, is accredited through NIST (National Institute of Standards and Technology) and participates in the National Voluntary Lab Accreditation Program (NVLAP) as required by the EPA. Bulk Samples were analyzed by Polarized Light Microscopy (PLM) in general compliance with guidelines established by the US EPA (40 CFR Part 763, Subpart F, Appendix A). Asbestos concentrations were visually estimated and/or point -counted and reported in percent for each layer of the sample. This includes the description and location of all ACM tested and laboratory analysis results of all acquired bulk samples. RESULTS EPA, OSHA and the State of Colorado considers any material containing more than 1% asbestos to be ACM. "None detected" means no asbestos was found. Trace means less than (<I%) is present. Samples S001-5003. Drywall/Joint Compound/Texturing from Homogenous Area #1 Dressing Closets Walls is None Detected, No Asbestos is present in the Drywall/Joint Compound/Texturing in the Dressing Closet Area, only. Samples M001 -M002, Ceiling Panel Materials from Ceiling Panel Area/Homogenous Area #2 are None Detected, No Asbestos is present in the Ceiling Panel Material. Samples M003 -M004, Carpet / Adhesive from Homogenous Area #3 are None Detected, No Asbestos is present in these Flooring Materials. Samples M005 -M006, Cove Base Adhesive from Homogenous Area #4 are None Detected, No Asbestos is present in the Cove Base Adhesive. RECOMMENDATIONS AND SUMMARY All areas of ACM should be removed per Colorado Regulation 8 protocol. A homogeneous area is ACM if at least one sample from that area shows that asbestos is present in an amount greater than 1%. A sample is "None detect" if it has no amounts of asbestos present. A Sample is Trace if amount of ACM < I%. ALL 9 SAMPLES ARE "NONE DETECTED", NO ASBESTOS IS PRESENT. P.O. Box 116 Arvada, CO 80001 / lesrees00@gmail.com / AsbestosTestDenver.com All 9 Samples of Suspect affected Area's are "None Detected", No Asbestos is Present in these Area's (S001-5003 & M001 -M006), only. All affected areas of ACM are to be removed per Colorado Regulation 8. Homeowner and Contractors are to be notified All Area's of ACM to be removed per Colorado Regulation 8 protocol by a GAC (General Abatement Contractor). All affected areas of Trace (<I %) are to be removed per OSHA removal protocol. A General Abatement Contractor is recommended': No Trace Samples were Analyzed. A Homogeneous area is ACM if at least one sample from that area shows that asbestos is present in an amount greater than 1%. The EPA and CDPHE require all friable and non -friable ACMs be removed prior to renovation activities that may disturb the ACM, and all friable ACM must be removed prior to demolition. All ACMs are to be removed per Colorado Regulation 8 protocol. OSHA regulates all building materials that contain smaller amounts of asbestos (even trace concentrations/< 1%) by PLM & Point Counting. Suspect Materials under the 55 gallon drum, 32 square foot and 50 lineal foot "trigger levels" are not regulated by EPA or CDPHE. However, trace samples are regulated by OSHA. Suspect materials are sometimes hidden behind other building materials. These inaccessible areas are to be "tested" if additional "suspect" materials are found. There may be other ACM or suspect materials "Buried" or "Hidden Beneath" other Building Materials. If additional "suspect materials" are discovered, work needs to Cease Immediately & these additional "Suspect Materials" must be tested. Other areas on the property do not apply to this survey. Therefore, it is important to note that not all ACM at this residence may have been observed or sampled. Or, there may be other ACM in the structure not identified or "suspect" because this part of the structure was not yet affected or yet uncovered. This report pertains to only the areas mentioned specifically herein. All activities conducted in this report were performed in accordance with all applicable federal, state and local regulations as well as general accepted standards and professional practice within the environmental consulting profession. No warranty is expressed or implied. AAA Asbestos Analysis Inc. assumes no responsibility or liability for error in public information utilized, statements from other entities or developments outside the specific scope of this project. The details of this report outline the inspection activities on the date(s) indicated and should not be relied upon to represent conditions at a later date, the limited number of samples collected and the laboratory results of those samples. The laboratory P.O. Box 116 Arvada, CO 80001 / lesrees00@gmail.com / AsbestosTestDenver.com were collected. The results do not apply to any other areas within the structure that were not sampled, but may contain airborne asbestos fibers, including areas that may be inaccessible. Additional inspection and sampling would be required to test other areas of the building. This report has been prepared exclusively for use by the client, with specific application to their project as discussed in the scope of work. The information contained in this report is intended as supplementary material for Abatement Design and not to be used as personal exposure determinations, or determining the scope of work for abatement activities, bidding or billing purposes. Regulators, contractors or consultants reviewing this report must draw their own conclusions regarding the further investigation or remediation deemed necessary. AAA Asbestos Analysis Inc. can provide a scope of work for abatement upon request. AAA Asbestos Analysis Inc. does not warrant the work of regulatory agencies, laboratories or other third parties supplying information which may be used in preparation of this report. Sincerely, s Les Rees, CDPHE ID # 14762 AAA Asbestos Analysis Inc. Attachments will follow P.O. Box 116 Arvada, CO 80001 / lesrees00@gmail.com / AsbestosTestDenver.com AAA Asbestos Analysis LLC. P.O. Box 116 Arvada, CO 80001 303-907-7866 Lesrees00@gmail.com February 21, 2019 Kasco Commercial/Kerry 4980 Kipling St. #1 & #2 Wheat Ridge CO., Attention: Kerry, Report of Findings /Limited Asbestos Survey to include the Following Suspect Area's In Unit #1 & #2 to be Disturbed & Remodeled, Only, No other Area's were tested. Homogenous Area #1 Drywall/Texture/Joint Compound in Dressing Closets in Unit #1 & #2 (S001-5003) Homogenous Area#2 Ceiling Panels 2'x 4'(M001 -M002). Homogenous Area#3 Carpet Adhesive/Carpet (M003 -M004). Homogenous Area#4 Cove Base Adhesive (MO05-M006). ONLY THESE MATERIALS ARE COVERED IN THE SURVEY. Asbestos Survey for Suspect Affected Materials in Garage which affects above Area's to Be Remodeled (Named Above), Samples were collected at #1 & #2 4980 Kipling St. Wheat Ridge CO. AAA Asbestos Analysis LLC. provides the following "LIMITED ASBESTOS SCOPE/SURVEY" of the above-mentioned address, which included collection of "suspect" bulk samples and walk-through inspection to determine any Asbestos Containing Materials (ACM) that needs to be addressed as a result of a customer concern of Suspect Affected Building Materials in the Area's mentioned above, only. This Asbestos Survey is "limited" to the suspect Asbestos Containing Materials (ACM) mentioned above, only. These Suspect Materials to be removed, demolished or disturbed, only. No other suspect materials were observed that could be disturbed during #1 & #2 Remodeling Activities. If other "suspect materials" are hidden, buried or uncovered during the Removal & Demolition Activities, Stop work Immediately & do not proceed with removing any other suspect material, until it is tested. The walk-thru, "Limited Scope" bulk sampling and "change of custody" of the bulk sampling to EMSL Inc. were conducted on February 20, 2019. Work was performed by a certified and accredited Asbestos Building Inspector / Les Rees with an EPA and State of P.O. Box 116 Arvada, CO 80001 / lesrees00@gmail.com / AsbestosTestDenver.com ACF -24074. This inspection was limited to the Suspect Areas mentioned above, only. SCOPE OF WORK II,ar it ration No. Nine (9) Bulk Samples" were collected from "Suspect Materials" from the above mentioned Areas mentioned to be, disturbed, demolished or remodeled, only. These "bulk Samples" were taken from these areas @ 4980 Kipling St #1 & #2 Wheat Ridge CO. Nine (9) representative bulk samples of "suspect" ACM were submitted to the lab for PLM testing. These Bulk samples were collected randomly, pursuant to EPA and OSHA asbestos inspection regulations from homogeneous areas of suspect ACM. Nine (9) Bulk Samples were collected and given Alpha Numeric Identification Numbers according to EPA regulations 4980-#1&2-022019- S001 -S003 & M001 -M006. Only, S001-SO03 & M001 -M006, will be used in this report from this point forward. There are 3 Categories of ACM (Asbestos Containing Material) Surfacing, Miscellaneous and TSI/Thermal Systems Insulation. ACM is either "friable" or "non - friable." Some non -friable ACM's can be rendered friable by movement. ACMs can be in three (3) conditions: "good", "damaged", or "significantly damaged". The Three (3) Drywall/Texture/Joint Compond Samples (5001-S005). These Samples were taken from Dressing Closet Area's from the inside of the Unit. They are in the Surfacing Category. They are Friable & in Good Condition. This Entire Area contains approximately total 368 square feet of Homogenous Drywall/Joint Compound/Texturing Surfacing. The Two (2) Ceiling Panel Samples (M001 -M002). These Samples were taken from the Ceiling Panel Area. They are in the Miscellaneous Category. They are Friable & in Good Condition. This Area has approximately 2400 total square feet of Homogenous Ceiling Panels. The Two (2) Carpet/Adhesive Samples (M003 -M004). These Samples were taken from the Carpeting on the Floor. They are in the Miscellaneous Category. They are Non -Friable & in Good Condition. This Area has approximately 2400 total square feet of Homogenous Carpet/Adhesive. The Two (2) Cove Base Adhesive Samples (MO05-M006). These Samples Were taken from the Cove Base on the Walls. They are in the Miscellaneous Category. They are Non -Friable & in Good Condition. This Area has approximately 66 total square feet of Homogenous Cove Base Adhesive. P.O. Box 116 Arvada, CO 80001 / lesrees00@gmail.com / AsbestosTestDenver.com LAB PROCEDURES Bulk Samples were delivered to EMSL Lab, for a 24 -Hour Turnaround. Bulk samples are stored for six (6) months unless otherwise stipulated. EMSL Inc., a third - party independent lab, is accredited through NIST (National Institute of Standards and Technology) and participates in the National Voluntary Lab Accreditation Program (NVLAP) as required by the EPA. Bulk Samples were analyzed by Polarized Light Microscopy (PLM) in general compliance with guidelines established by the US EPA (40 CFR Part 763, Subpart F, Appendix A). Asbestos concentrations were visually estimated and/or point -counted and reported in percent for each layer of the sample. This includes the description and location of all ACM tested and laboratory analysis results of all acquired bulk samples. RESULTS EPA, OSHA and the State of Colorado considers any material containing more than 1% asbestos to be ACM. "None detected" means no asbestos was found. Trace means less than (<I%) is present. Samples S001 -S003. Drywall/Joint Compound/Texturina from Homogenous Area #1 Dressing Closets Walls is None Detected, No Asbestos is present in the Drywall/Joint Compound/Texturing in the Dressing Closet Area, only. Samples M001 -M002, Ceiling Panel Materials from Ceiling Panel Area/Homogenous Area #2 are None Detected, No Asbestos is present in the Ceiling Panel Material. Samples M003 -M004, Carpet / Adhesive from Homogenous Area #3 are None Detected, No Asbestos is present in these Flooring Materials. Samples M005 -M006, Cove Base Adhesive from Homogenous Area #4 are None Detected, No Asbestos is present in the Cove Base Adhesive. RECOMMENDATIONS AND SUMMARY All areas of ACM should be removed per Colorado Regulation 8 protocol. A homogeneous area is ACM if at least one sample from that area shows that asbestos is present in an amount greater than 1%. A sample is "None detect" if it has no amounts of asbestos present. A Sample is Trace if amount of ACM < I%. ALL 9 SAMPLES ARE "NONE DETECTED", NO ASBESTOS IS PRESENT. P.O. Box 116 Arvada, CO 80001 / lesrees00@gmail.com / AsbestosTestDenver.com i na na All 9 Samples of Suspect affected Area's are "None Detected", No Asbestos is Present in these Area's (S001-5003 & M001 -M006), only. All affected areas of ACM are to be removed per Colorado Regulation 8. Homeowner and Contractors are to be notified All Area's of ACM to be removed per Colorado Regulation 8 protocol by a GAC (General Abatement Contractor). All affected areas of Trace (<I %) are to be removed per OSHA removal protocol A General Abatement Contractor is recommended': No Trace Samples were Analyzed. A Homogeneous area is ACM if at least one sample from that area shows that asbestos is present in an amount greater than 1%. The EPA and CDPHE require all friable and non -friable ACMs be removed prior to renovation activities that may disturb the ACM, and all friable ACM must be removed prior to demolition. All ACMs are to be removed per Colorado Regulation 8 protocol. OSHA regulates all building materials that contain smaller amounts of asbestos (even trace concentrations/< 1%) by PLM & Point Counting. Suspect Materials under the 55 gallon drum, 32 square foot and 50 lineal foot "trigger levels" are not regulated by EPA or CDPHE. However, trace samples are regulated by OSHA. Suspect materials are sometimes hidden behind other building materials. These inaccessible areas are to be "tested" if additional "suspect" materials are found. There may be other ACM or suspect materials "Buried" or "Hidden Beneath" other Buildinr Materials. If additional "suspect materials" are discovered, work needs to Cease Immediately & these additional "Suspect Materials" must be tested. Other areas on the property do not apply to this survey. Therefore, it is important to note that not all ACM at this residence may have been observed or sampled. Or, there may be other ACM in the structure not identified or "suspect" because this part of the structure was not yet affected or yet uncovered. This report pertains to only the areas mentioned specifically herein. All activities conducted in this report were performed in accordance with all applicable federal, state and local regulations as well as general accepted standards and professional practice within the environmental consulting profession. No warranty is expressed or implied. AAA Asbestos Analysis Inc. assumes no responsibility or liability for error in public information utilized, statements from other entities or developments outside the specific scope of this project. The details of this report outline the inspection activities on the date(s) indicated and should not be relied upon to represent conditions at a later date, the limited number of samples collected and the laboratory results of those samples. The laboratory P.O. Box 116 Arvada, CO 80001 / lesrees00@gmail.com / AsbestosTestDenver.com were collected. The results do not apply to any other areas within the structure that were not sampled, but may contain airborne asbestos fibers, including areas that may be inaccessible. Additional inspection and sampling would be required to test other areas of the building. This report has been prepared exclusively for use by the client, with specific application to their project as discussed in the scope of work. The information contained in this report is intended as supplementary material for Abatement Design and not to be used as personal exposure determinations, or determining the scope of work for abatement activities, bidding or billing purposes. Regulators, contractors or consultants reviewing this report must draw their own conclusions regarding the further investigation or remediation deemed necessary. AAA Asbestos Analysis Inc. can provide a scope of work for abatement upon request. AAA Asbestos Analysis Inc. does not warrant the work of regulatory agencies, laboratories or other third parties supplying information which may be used in preparation of this report. Sincerely, Les Rees, CDPHE ID # 14762 AAA Asbestos Analysis Inc. Attachments will follow P.O. Box 116 Arvada, CO 80001 / lesrees00@gmail.com / AsbestosTestDenver.com EMSL Analytical, Inc. 1010 Yuma Street Denver, CO 80204 Tel/Fax: (303) 740-5700 / (303) 741-1400 - http://www.EMSL.com / denverlab@emsl.com Attention: Les Rees AAA Asbestos Analysis Inc PO Box 116 Arvada, CO 80001 Project: 4980 KIPLING ST/#1 & #2 EMSL Order: 221901553 Customer ID: AASB42 Customer PO: Project ID: Phone: (303) 907-7866 Fax: 2% Non-fibrous (Other) None Detected Received Date: 02/20/2019 11:15 AM Analysis Date: 02/21/2019 Collected Date: 02/20/2019 Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized DRYWALL/J Light Microscopy 2% Non-fibrous (Other) None Detected Non -Asbestos Asbestos Sample Description Appearance % Fibrous % Non -Fibrous % Type 498041 & DRYWALL/J White 20% Ca Carbonate None Detected #2-022019-S001-Textur COMP/TEXT/? Non -Fibrous 80% Non-fibrous (Other) e Heterogeneous 221901553-0001 Inseparable paint / coating layer included in analysis HA 1 HA:1 498041 & DRYWALL/J White 98% Cellulose 2% Non-fibrous (Other) None Detected #2 -022019 -S001 -Tape COMP/TEXT/? Fibrous Heterogeneous Compound 221901553-0002 Homogeneous 221901553-0001A HA 1 HA'.1 White 98% Cellulose 498041 & DRYWALL/J White 20% Ca Carbonate None Detected #2 -022019 -S001 -Joint COMP/TEXT/? Non -Fibrous 80% Non-fibrous (Other) Compound Homogeneous HA: 1 221901553-00018 HA.1 498041 & DRYWALL/J White 15% Cellulose 65% Gypsum None Detected #2-022019-5001-Drywal COMP/TEXT/? Fibrous <1 % Glass 20% Non-fibrous (Other) I Homogeneous 221901553-000IC HA:1 498041 & DRYWALL/J White 20% Ca Carbonate None Detected #2-022019-5002-Textur COMP/TEXT/? Non -Fibrous 80% Non-fibrous (Other) e Heterogeneous Compound 221901553-0002 Homogeneous Inseparable paint / coating layer included in analysis HA 1 498041 & DRYWALL/J White 98% Cellulose 2% Non-fibrous (Other) None Detected #2 -022019 -5002 -Tape COMP/TEXT/? Fibrous 65% Gypsum None Detected #2-022019-S002-Drywal Homogeneous Fibrous <1% Glass 221901553-0002A Homogeneous HA: 1 221901553-0002C 498041 & DRYWALL/J White 20% Ca Carbonate None Detected 42 -022019 -S002 -Joint COMP/TEXT/? Non -Fibrous 80% Non-fibrous (Other) Compound Homogeneous 221901553-0002B HA. 1 498041 & DRYWALL/J White 15% Cellulose 65% Gypsum None Detected #2-022019-S002-Drywal COMP/TEXT/? Fibrous <1% Glass 20% Non-fibrous (Other) Homogeneous 221901553-0002C HA 1 Initial report from: 02/21/2019 15:43:07 A:'B �L/rf_0} 110,8 0001 - 1.18 Printed- 2/21/2019 1:43 PM Page 1 of 3 EMSL Analytical, Inc. EMSLOrder: 221901553 Customer ID: AASB42 1010 Yuma Street Denver, CO 80204 Customer PO: Tel/Fax: (303) 740-5700 / (303) 741-1400 Project ID: M http://www.EMSL.com / denverlab@emsl.com Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy Non-Asbestos Asbestos Sample Description Appearance % Fibrous % Non-Fibrous % Type 498041 & DRYWALUJ Brown/White 15% Cellulose 65% Gypsum None Detected #2-022019-S003 COMP/TEXT/? Fibrous 20% Non-fibrous (Other) Homogeneous 221901553-0003 HA:1 498041 & CEILING PANEL 2'x4' Gray 40% Cellulose 40% Non-fibrous (Other) None Detected #2-022019-M001 Fibrous 20% Min. Wool Homogeneous 221901553-0004 HA: 2 498041 & CEILING PANEL 2'x4' Gray/White 45% Cellulose 10% Non-fibrous (Other) None Detected #2-022019-M002 Fibrous 45% Min. Wool Homogeneous 221901553-0005 HA: 2 498041 & CARPET ADHESIVE Gray 85% Synthetic 15% Non-fibrous (Other) None Detected #2-022019-M003-Carpe Fibrous t Homogeneous 221901553-0006 HA: 3 498041 & CARPETADHESIVE Tan 100% Non-fibrous (Other) None Detected #2-022019-M003-Mastic Non-Fibrous Homogeneous 221901553-0006A HA: 3 498041 & CARPET ADHESIVE Gray 80% Synthetic 20% Non-fibrous (Other) None Detected #2-022019-M004-Carpe Fibrous t Homogeneous 221901553-0007 HA: 3 498041 & CARPET ADHESIVE Tan 100% Non-fibrous (Other) None Detected #2-022019-M004-Mastic Non-Fibrous Homogeneous 221901553-0007A HA:3 498041 & COVE BASE Gray 100% Non-fibrous (Other) None Detected #2-022019-M005-Cove ADHESIVE Non-Fibrous Base Homogeneous 221901553-0008 HA:4 498041 & COVE BASE Tan 100% Non-fibrous (Other) None Detected #2-022019-M005-Mastic ADHESIVE Non-Fibrous Homogeneous 221901553-0008A HA: 4 498041 & COVE BASE White 20% Ca Carbonate None Detected #2-022019-M005-Textur ADHESIVE Non-Fibrous 80% Non-fibrous (Other) e Heterogeneous 221901553-00088 Inseparable paint/ coating layerincluded in analysis HA:4 498041 & COVE BASE Black 100% Non-fibrous (Other) None Detected #2-022019-MG06-Cove ADHESIVE Non-Fibrous Base Homogeneous 221901553-0009 Initial report from: 02/21/2019 15:43:07 ASB____PLt€!t__0008__0001 - 1.78 Printed: 2/21/2019 1:43 PM Page 2 of 3 EMSL Analytical, Inc. EMSL Order: 221901553 Customer ID: AASB42 1010 Yuma Street Denver, CO 80204 Customer PO: Tel/Fax: (303) 740-5700 / (303) 741-1400 http://www.EMSL.com / denverlab@emsl.com Project ID: Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy Non -Asbestos Asbestos Sample Description Appearance % Fibrous % Non -Fibrous % Type HA'4 498041 & COVE BASE Tan #2 -022019 -M006 -Mastic ADHESIVE Non -Fibrous Homogeneous 221901553-0009A HA: 4 498041 & COVE BASE White #2-022019-M006-Textur ADHESIVE Non -Fibrous e Homogeneous 221901553-00098 Inseparable paint /coating /ayerincluded in analysis HA: 4 Analyst(s) Amanda Hammer (14) Molly Elkins (7) 100% Non-fibrous (Other) None Detected 10% Ca Carbonate None Detected 90% Non-fibrous (Other) Melanie Rech, Laboratory Director or Other Approved Signatory EMSL maintains liability limited to cost of analysis. The above analyses were performed in general compliance with Appendix E to Subpart E of 40 CFR (previously EPA 600/M4-82-020 "Interim Method"), but augmented with procedures outlined in the 1993 ("final') version of the method. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations . Interpretation and use of test results are the responsibility of the client. All samples received in acceptable condition unless otherwise noted. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. EMSL recommends gravimetric reduction for all non -friable organically bound materials prior to analysis. Estimation of uncertainty is available on request. Samples analyzed by EMSL Analytical, Inc. Denver, CO NVLAP Lab Code 200828-0 Initial report from: 02/21/2019 15:43:07 A.Bo__FLM.._0008__0001 - 1.78 Printed: 2/21/2019 1:43 PM Page 3 of 3 Troy Dicker From: Troy Dicker Sent: Thursday, March 21, 2019 11:32 AM To: 'kasco33@msn.com' Cc: Randy Slusser Subject: 4890 Kipling St., Plan/permit # 201900396 Kerry, Thank you for submitting the changes to the proposed project. All corrections look ok so far, ( The electrical plan reviewer will still need to look at the changes on the electrical sheets, but they appear to be ok ) except for the nail station. I should have been more clear in what I need to see. For that, I apologize. As per 2012 IMC, section 403.1, supply air and return or exhaust air are required. Per section 403.3 ( Table under specialty shops; nail salons ) it states ( Footnote B ) mechanical exhaust is required, and the recirculation of air from such spaces is prohibited. ( Footnote H ) For nail salons, each nail station shall be provided with a source capture system capable of exhausting not less than 50 cfm per station. The plans are showing supply air, but no form of exhaust or capture. Please amend the plans to reflect this requirement. You will only need to submit page M1 for corrections, the rest of the plan sets have the required information and corrections listed that I previously asked for. Feel free to contact me with any questions. Thank you! Troy Dicker, Building Inspector, Plans Examiner Building Division 7500 W. 29th Avenue Wheat Ridge, Colorado 80033 Office Phone: 303-235-2882 Fax: 303-237-8929 www.ci.wheatridge.co.us V1Thea� F`t 4 ��� � ,TtCity -f-)f L (,o9�.. �V V he t 1C ,CommumT-' DEVELOPMENT lvur / 5"- /7 KASCO Commercial, Inc. 5970 Broadway, Denver, CO 80216 20 19 o Phone: 303-909-0629 E-mail: kasco33Amsn.com 3 Plan Review Comments Response 1. Details added to plans. 2. CFM indicated per diffuser. 3. Drain added to plans. 4. Codes indicated. 5. Details added to plans. Dryer vents 105 cfm, makeup air will not be required. 6. Tenant will provide bottled water, drinking fountain will not be required. 7. Washer/ Dryer location verified on plans. 8. Partition details added to plans. 9. Fault current calculations are currently on plans, sheet E0.2. If additional information is required, we will provide it. Project Description: Project Address: 4980 Kipling Permit App. Date: 03/08/19 Applicant: KASCO Commercial Applicant email: kasco33@msn.com Plan Checker: Troy Dicker Plan Checker email: t itv of W hk�- at c PLAN REVIEW COMMENTS Tenant Improvement Plan Check No.: 201900396 Phone: 303-909-0629 Phone: 303-235-2882 tdicker @ci.wheatridge.co.us The project plans were reviewed for compliance with the following codes and standards: 2012 IBC, 2012 IRC, 2012 IMC, 2012 ECC, 2017 NEC, 2012 IPC, 2009 ANSI/ICC, City of Wheat Ridge Amendments • TO EXPEDITE PROJECT APPROVAL: Please provide a written response indicating how and where each comment was resolved on the plans. • Resubmit all previously reviewed plans, updated plans and supporting documents with each subsequent review. • For clarification of any plan review comment, please email the plan checker listed above. 1. Provide details for existing ADA bathroom, including turning radius dimensions. Details to include grab bars, (vertical and horizontal) heights of grab bars, height of sink, and height of toilet. Also show distance of toilet from wall, and any accessories located in the bathroom. 2. Code requires ventilation to be provided for each nail station of not less than 50 cfm per station. Code does not recognize difference between toxic/non-toxic applications. ( IMC 403.3 ) 3. Washer drain not on plumbing isometric drawings. Must meet requirements of IPC 406.2; 802.4 4. Specify on plan sheet applicable codes of: 2012 IBC, IMC, IPC, IECC, Wheat Ridge amendments, and 2017 NEC. 5. Dryer vent requires more details. Show length of duct, and size. ( 4" min. size ) If dryer vents more than 200 cfm, make up air will be required. 6. Verify water fountain. Not shown on plumbing plans. Show dimensions to verify ADA compliance. 7. Washer/Dryer shown in different locations on different pages. Verify location and have them match on all plan sheets. City F '11C 8. Plans should show partition walls drawn with more details to include steel stud gauge, height, and any other framing details to verify requirements. 9. Provide fault current calculations on electrical system. Please redraw and resubmit plans with above requested corrections. i CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type: t = - Job Address: cl 19 o W .'r, i Permit Number: _2 0 I g 0 d a-31731 )'D 7 7 trn Jiro ❑ No one available for inspection: Time 10 _(AM)PM Re -Inspection required: Yes No When corrections have been made, call for re -inspection at 303-234-5933 Date: 'a / a / Inspector: ) DO NOT REMOVE THIS NOTICE 1C i :XI ��A41w 91. CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax T10 ( ) I- SPECTION NOTICE Inspection Type: JobAddress: Permit Number: a O /goo a -so ❑ No one available for inspection: Time i4.WPM Re -Inspection required: Yes When corrections have been made, calif re -inspection at 303-2 S Dat '" l� Inspec DO NOT REM E THIS NOTICE f L N L s o Q N m z° Q den � O ° O O a C V O "Ol U �j u ee C ¢ C7 (r cS ri U �1 v :j o u Q -1 fl C o N o d Awa H U + (v 4.) l n l y _ °cc y Q a o +) Hw +.) p m O CdM ° t F > o a OCC H aro o H o _ Cc m U H O o�� N� rA tcU g� q U 44 U ry �I o cG � •o A � w ,i ° N u on o y G4.) � U i C Q d N A U W O o o o U b G cc u u u bD .Q V] V1 GG �D tw N ^o R s•CU 'O d, ❑ Z141 O u u W rZp O � �I o� zF a 04 od A jr 6. `� � UPC��Z H0 O to w 00 M d o E WAtn4+� a�M3 o u A > L 0aA�° ° CO 44 N U 44 A U O ti = r7 CQ W I�i o ~ 4J ro tzt d 4 Z wvE, z o n a Wa1i4 U m CCC°333 a ��= 30aQ0 ba OU F a. OU $ z Q` Q PERMIT NO. 201900238 City of Wh6atR�i�djge BUSINESS LICENSE INSPECTION INSPECTION DAY/TIM INSPECTION DAY/TIME INSPECTION DAY/TIME BUSINESS NAME: Dream Dinners Arvada ADDRESS: 4980 Kipling A3 CONTACT NAME: Jamie �'- SQ FT FF OCCUPANCY TYPE 13 OCCUPANCY LOAD CONSTRUCTION TYPE ❑ SPRINKLERED Q NOWSPRINKLERED Inspector Signature Date Tues, Feb 12 @ 10 am City of Wheat Ridge �=' Commercial Sign PERMIT - 201800250 PERMIT NO: 201800250 ISSUED: 01/25/2018 JOB ADDRESS: 4890 Kipling ST EXPIRES: 01/25/2019 JOB DESCRIPTION: Remove existing illuminated cabinet sign; fabricate and install new front lit logo can and all cap pan channel letters; overall sign dimensions 24 in x 263.78 in; 524 sq ft total *** CONDITIONS *** The issuance of a building permit should not be construed to be approval of a business license. Business licenses are independent of the building permit and can not be approved until completion and approval of the associated building permit. All lighting shall be in conformance with Section 26-503 of the Zoning and Development Code with fixtures fully shielded so that the source of the illumination is not visible from adjacent properties and streets. Sign: Clear Creek Animal Hospital *** CONTACTS *** OWNER (303)423-1177 KIPLING LAND LLC SUB (720)772-7446 Chad Smith 160156 Smith Sign Company LLC SUB (303)570-3489 Damon Summers 170113 Enterprise Electric Company *** PARCEL INFO *** ZONE CODE: UA / Unassigned USE: UA / Unassigned SUBDIVISION CODE: 520 / Office; 0 BLOCK/LOT#: 0 / *** FEE SUMMARY *** ESTIMATED PROJECT VALUATION: 2,268.50 FEES Total Valuation 0.00 Plan Review Fee 60.68 Use Tax 47.64 Permit Fee 93.35 ** TOTAL ** 201.67 *** COMMENTS *** *** CONDITIONS *** The issuance of a building permit should not be construed to be approval of a business license. Business licenses are independent of the building permit and can not be approved until completion and approval of the associated building permit. All lighting shall be in conformance with Section 26-503 of the Zoning and Development Code with fixtures fully shielded so that the source of the illumination is not visible from adjacent properties and streets. 1, by my signature, do hereby attest that the work to be performed shall comply with all accompanying approved plans and specifications, applicable building codes, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with this pennrt. I further attest that I am legally authorized to include alI entities named within this document as partes to the work to be performed and that all work to be performed is disclosed in this document and/or its' accompanying approved plans and specifications. Signature of OWNER or CONTRACTOR (Circle one) Date I . This permit was issued based on the information provided in the permit application and accompanying plans and specifications and is subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures. 2. This permit shall expire 365 days after the date of issuance regardless of activity. Re nests for extension must be made in writing and received prior to the date of expiration. An extension of no more than 180. days made be granted at the discretion of the Chief Building Official and may be subject to a fee equal to one-half of the originalpermit fee. 3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard requirements, fees and procedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of the Chief Building Official and is not guaranteed. 4, No work of any manner shall be performed that shall results in a change of the natural flow of water without prior and specific approval. 5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of aIl required inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services Division. 6. The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, any violation of any provision of any applicable code or any ordinance or regulation of this jurisdiction. Approval of work is subject to field inspection. Signature of Chief BbiTding Official V y_; Date REQUESTS MUST BE MADE BY 11:59PM AN'Y BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. City of Wheat Ridge ~^� Commercial Sign PERMIT - 201800250 PERMIT NO: 201800250 ISSUED: 01/25/2018 JOB ADDRESS: 4890 Kipling ST EXPIRES: 01/25/2019 JOB DESCRIPTION: Remove existing illuminated cabinet sign; fabricate and install new front lit logo can and all cap pan channel letters; overall sign dimensions 24 in x 263.78 in; 524 sq ft total Sign: Clear Creek Animal Hospital 1, by my signature, do hereby attest that the work to be performed shall comply with all accompanying approved plans and specifications, applicable building codes, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with this pennrt. I further attest that I am legally authorized to include alI entities named within this document as partes to the work to be performed and that all work to be performed is disclosed in this document and/or its' accompanying approved plans and specifications. Signature of OWNER or CONTRACTOR (Circle one) Date I . This permit was issued based on the information provided in the permit application and accompanying plans and specifications and is subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures. 2. This permit shall expire 365 days after the date of issuance regardless of activity. Re nests for extension must be made in writing and received prior to the date of expiration. An extension of no more than 180. days made be granted at the discretion of the Chief Building Official and may be subject to a fee equal to one-half of the originalpermit fee. 3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard requirements, fees and procedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of the Chief Building Official and is not guaranteed. 4, No work of any manner shall be performed that shall results in a change of the natural flow of water without prior and specific approval. 5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of aIl required inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services Division. 6. The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, any violation of any provision of any applicable code or any ordinance or regulation of this jurisdiction. Approval of work is subject to field inspection. Signature of Chief BbiTding Official V y_; Date REQUESTS MUST BE MADE BY 11:59PM AN'Y BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. �� City, of ' o h6 1dg Building & Inspection Services Division 7500 W. 29" Ave., Wheat Ridge, CO 80033 Office: 303-235-2855 , Fax: 303-237-8929 Inspection Line: 303-234-5933 Email: Permits(a)ci.wheatridge.co.us I FOR OFFICE USE ONLY I Plan/Permit # ,/`: QK Plan Review Fee: Building Permit Application Please complete aft highlighted areas on both sides of this form. Incomplete applications may not be processed. PropertyAddress: 4890 KIPLING ST. UNITA-6 Property Owner (please print): KIPLING LAND LLC Phone: 303-423-1177 Property owner Email: N/A Mailing Address: (if different than property address) Address: SAME AS PROPERTY Citv, State, Zi ArchitecttEngineer E-mail: Contractor: SMITH SIGN COMPANY LLC Phone: Contractors City License #: 160156 Phone: 720-592-1169 Contractor E-mail Address: CHADaDENVFRSIGNANDLIGHTING.COM For Plan Review Questions & Comments (please print): CONTACT NAME (please print): JESSICA REDMOND Phone: 720-592-1169 CONTACT EMA1L(please print): JESSICA&DENVERSIGNANDLIGHTING COM Sub Contractors: NONE Electrical: W.R. City License # Other City Licensed Sub: City License # City License # Plumbing: W.R. City License # Other City Licensed Sub: Mechanical: W.R. City License # Complete all information on BOTH sides of this form X COMMERCIAL ❑ RESIDENTIAL Deaccription of work. (Check all that apply) ❑ NEW COMMERCIAL STRUCTURE ❑ ELECTRICAL SERVICE UPGRADE ❑ NEW RESIDENTIAL STRUCTURE ❑ COMMERCIAL ROOFING ❑ COMMERCIAL ADDITION ❑ RESIDENTIAL ROOFING ❑ RESIDENTIAL ADDITION ❑ WINDOW REPLACEMENT ❑ COMMERCIAL ACCESSORY STRUCTURE (Garage, shed, deck, etc.) ❑ RESIDENTIAL ACCESSORY STRUCTURE (Garage, shed, deck, etc.) ❑ MECHANICAL SYSTEM/APPLIANCE REPAIR or REPLACEMENT ❑ PLUMBING SYSTEM/APPLIANCE REPAIR or REPLACMENT ❑ ELECTRICAL SYSTEM/APPLIANCE REPAIR or REPLACEMENT X OTHER (Describe) NEW WALL SIGN (ILLUMINATED) (For ALL projects, please provide a detailed description of work to be performed, Including current use of areas, proposed uses, square footage, existing condition and proposed new condition, appliance size and efficiency, type and amount of materials to be used, etc.: ) SSC TO REMOVE EXISTING INTERNALLY ILLUMINATED CABINET SIGN. FABRICATE AND INSTALL NEW FRONT LIT LOGO CAN AND ALL CAP PAN CHANNEL LETTERS TO READ CLEAR CREEK ANIMAL HOSPITAL. OVERALL SIGN DIMENSIONS ARE 24" X 263.78 Sq. Ft./LF Amps Btu's Squares Gallons Other Project Value: (Contract value or the cost of all materials and labor included in the entire project) $ 2268.50 OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance with applicable City of Wheat Ridge codes and ordinances for work under any permit issued based on this application; that I am the legal owner or have been authorized by the legal owner of the property to perform the described work and am also authorized by the legal owner of any entity included on this application to list that entity on this application. I, the applicant for this building permit application, warrant the truthfulness of the information provided on the application. CIRCLE ONE: (OWNER CONTRACTOR or (AUTHORIZED REPRESENTATIVE) of (OWNER) (CONTRACTOR) atur (ttrst and log name): DATE: 1/25/18 DIEPA►RTIItI NT USE ONLY ZONING COMIMMFNTS: � OCCUPANCY CLASSIFICATION: Reviewer:.y f �i N 0`^i l% i f 1. J BUttDING DEPARTMENT COMMENTS; Reviewer. Building Division Valuation Project Address Wall Sign Calculation Sheet You must complete this sheet and include it in the submittal package for any new wall signs. You will also need to create a site plan and a detail sheet of the signage. 365 -WARDS RD;-i4N4-T-+60 Contractor: SMITH SIGN COMPANY You are allowed 1 square foot of signage for every 1 linear foot of wall to which you are attaching a sign. All wall signs must be adjacent to a street or major interior drive. Step 1: Measure the, length of the wall(s) where you are attaching the sign: Wall 1 - 65 feet Wall 2 - feet Wall 3 - feet Step 2: The length of the wall is the allowable square footage for the wall sign. Wall 1 allowable signage - Wall 2 allowable signage - Wall 3 allowable signage - Site Plan SEPARATE PAGE 65 , square feet square feet square feet Reviewed for Zoning Compliance by the City of Wheat Ridge Planning Division Or APPROVED By: I -W^ DATE: L1L-S I I g COMMENTS: s Z pk. J 0 IL 0 IL V Z V 0 IxO W I- x W J U) 0 2 cn co Q~o W CO Z<�O W00 W Z ct J UWP Of Y Q WCD W W Reviewed for Zoning Compliance by tl City of Wheat Ridge Planning Division APPROVED By: 7i1, m DATE: (. I 7-3 I ir COMMENTS: S r -e-- a ie,- W D M Z W p Qco =o O U LnW� 1 WWEE° H N �► O w o 3 n /ok ► A City of Wheat Ridge ..4 r Commercial Plumbing PERMIT - 201801241 PERMIT NO: 201801241 ISSUED: 05/01/2018 JOB ADDRESS: 4980 Kipling ST STE A-5 EXPIRES: 05/01/2019 JOB DESCRIPTION: Remove and replace 6 gallon electric 120 volt water heater in ceiling above restroom *** CONTACTS *** OWNER (888)568-1880 GALLONT COMPANIES SUB (303)343-0032 Jeff Metz 021428 DONE SERVICE GROUP, INC *** PARCEL INFO *** ZONE CODE: UA / Unassigned SUBDIVISION CODE: 330 / General Retail USE: UA / Unassigned BLOCK/LOT#: / *** FEE SUMMARY *** ESTIMATED PROJECT VALUATION: 1,095.00 FEES Total Valuation 0.00 Use Tax 23.00 Permit Fee 46.90 ** TOTAL ** 69.90 *** COMMENTS *** *** CONDITIONS *** All work shall comply 2012 International Codes, 2014 NEC (if applicable), and ordinances adopted by the City of Wheat Ridge. Work is subject to field inspections. I, by my signature, do hereby attest that the work to be performed shall comply with all accompany ingg approved plans and specifications, applicable building codes, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with this_,p enrrttt.-I-further attest that I am legally authorized to include all entities named within this document as parties to the work to be p�rtormed and that;all work to be perFprmed is disclosed in this document and/or its' accompanying approved plans and specifications. Signature of "©WNER or CONTRACTOR (Circte one) Date I. This permit was.issued based on the information provided in the permit application and accompanying plans and specifications and is subject to the co►ppliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures. 2. This permit shall' expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and received prior to the date of expiration. An extension of no more than 180 days made be granted at the discretion of the Chief Building Official and maybe subject to a fee equal to one-half of the originalpermit fee. 3. If this permit expires, a new permit may be required to be obtained. issuance of a new permit shall be subject to the standard requirements, fees androcedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of the Chief Building Official and is not guaranteed. 4. No work of any manner shall be performed that shall results in a changeof the natural flow of water without prior and specific approval. 5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all required inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services Division. 6. The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, an violation of any provision of any applicable code or any ordinfife or regulation of this jurisdiction. Approval of work is subject to f any inspection. AMY Bui` -1 . Signature o re l, mg Official Date REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. b� City of `7V heat ROgle COMMLJNiTy DEVELOPMENT Building & Inspection Services Division 7500 W. 291' Ave., Wheat Ridge, CO 80033 Office: 303-235-2855 * Fax: 303-237-8929 Inspection Line: 303-234-5933 Email: permits@ci.wheatridge.co.us FOR OFFICE USE ONLY Date: ) Plan/Permit # 00 Plan Review Fee: Building Permit Application *** Please complete all highlighted areas on both sides of this form. Incomplete applications may not be processed. *** Property Address: Property Owner (Please print): t All I` II/ Ii 1 1,'11110111Phone: Property Owner Email: Tenant (Commercial Projects Only) Property Owner Mailing � Address: (if different than property Address: *NCSjA'(�ilf1 %vj a I �)r #9 Architect/Engineer: Architect/Engineer E-mail: Contractor: City of Wheat Ridge License #: Contractor E-mail Address: ®� O K For Plan Review Questions & Comments (please print): Phone: Phone: V ��- , �s�/V/` CONTACT NAME (please print): Phone: CONTACT EMAIL(p/ease print): Sub Contractors (Must provide Wheat Ridge License No.): Electrical: Plumbing: Mechanical: W.R. City License # W.R. City License # W.R. City License # Other City Licensed Sub: Other City Licensed Sub: City License # City License # [COMMERCIAL F-1 RESIDENTIAL Description of work: For ALL projects, provide a detailed description of work to be performed, including current use of areas, proposed uses, square footage, existing condition and proposed new condition, appliance size and efficiency, type and amount of materials to be used, etc. ki1)V� od rep 69 al�cil� L&Oflb 190V- owkleql�t-1 Y\1 W/( 0�a+((- 10 above rt�7sYrvc to Commercial Projects Only: Occupancy Type: �Construction Type: Sq. FULF BTUs � ��(� t��� ��/G Gallons 1 4 Amps Squares Project Value: (Contract value or the cost of all materials and labor included in the entire project) OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance with applicable City of Wheat Ridge codes and ordinances for work under any permit issued based on this application; that I am the legal owner or have been authorized by the legal owner of the property to perform the described work and am also authorized by the legal owner of any entity included on this application to list that entity on this application. 1, the applicant for this building permit application, warrant the truthfulness of the information provided on the application. CIRCLE ONE: (OWNER) (CC Signature (first and last name): Printed Name: ZONING COMMMENTS: Reviewer: BUILDING DEPARTMENT COMMENTS: Reviewer: PUBLIC WORKS COMMENTS: Reviewer: (OWNER) ONTRA CTOR) kTE: C OCCUPANCY CLASSIFICATION: CONSTRUCTION TYPE: Building Division Valuation: c -i o o ro i N m u q Nm u o \ ro w z � u m O as w m x QJ 0 1J (d a ro 0 Q o a .V O r N o .yi m 3 rl U A y m w A 0 _ 0 0 m a 44 � w y O y ro u W 0 U rt U rl b 0 li r \ O O W qH O y1 E•1 P' Ip W v A 41 OC)c0 \ I m b mm 14 U y H •.i V �W M o ro y 0 H (d �I O 'v Q W 4jA w a H ��' 00 m 0 :D y w W z pa b) O O d x '0H A U O �- N U u 4,.Q ° 0 11 $ 4.) fA 1nn1��� WLW 0 U W W 3 0 m o O(d U °' N y .� ky O Q �Ep'i Ay v pryW .0 r U L— uu Z. Ln . 4Ju E bi b F M U o ro q b 0 d) 0 V W o "� ro A U 44 H 4.) u rn v ° �4 r-1 O to v o� ld L. - ug •r a -1 Av" 4) N H E, A •a U v bl Irl m u o F o q W U 44 to O >, -1 u) C u)U A ii rl o C u �"� my O 0 O u u m w 7 H 0 O w m o„ x N u] �d LL N$4 0 H N Q o o °a U O m 00 g o a u a)O0 N a > roq H vW�� z4.l k to .. N W u U w rd •ui m a S a w14 A rl wa w m F 0 °w J ro Gv •, m > V uua F. W b H � p �4 4 41 b a a wNA U E N U t!1 Fi a City of Wheat Ridge Commercial Sign PERMIT - 201705177 PERMIT NO: 201705177 ISSUED: 08/01/2017 JOB ADDRESS: 4980 Kipling ST STE Al EXPIRES: 08/01/2018 JOB DESCRIPTION: SIGN DARE2BFIT LED INTERNAL LIGHTING. 45 SQ FT BUILDING LINEAR FRONTAGE 100FT. SEE PLANS *** CONTACTS *** OWNER 720-662-8525 PINNACOL REAL ESTATE MGMT SUB (303)789-7566 Chul Man Pak/Heejin Lim 170076 Create Sign *** PARCEL INFO *** ZONE CODE: UA / Unassigned USE: UA / Unassigned SUBDIVISION CODE: 330 / General Retail BLOCK/LOT#: 0 / *** FEE SUMMARY *** ESTIMATED PROJECT VALUATION: 2,000.00 FEES Total Valuation 0.00 Plan Review Fee 50.38 PAID Use Tax 42.00 Permit Fee 77.50 ** TOTAL ** 169.88 "- *** COMMENTS *** *** CONDITIONS *** ZWM: All lighting shall be in conformance with Section 26-503 of the Zoning and Development Code with fixtures fully shielded so that the source of the illumination is not visible from adjacent properties and streets. The issuance of a building permit should not be construed to be approval of a business license. Business licenses are independent of the building permit and can not be approved until completion and approval of the associated building permit. City of Wheat Ridge Commercial Sign PERMIT - 201705177 PERMIT NO: 201705177 ISSUED: 08/01/2017 JOB ADDRESS: 4980 Kipling ST STE Al EXPIRES: 08/01/2018 JOB DESCRIPTION: SIGN DARE2BFIT LED INTERNAL LIGHTING. 45 SQ FT BUILDING LINEAR. FB0v1�G2 100FT. SEE PLANS I by my signature do hereby attest that the work to be performed shall comply with all accompanying approved plans and specifications applicable building codes, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with this permit. I further attest that I am legally authorized to include all entities named within this document as parties to the work to be performed and that all work to be perfor I_ is disclosed in this document and/or its' accompanying approved plans and specifications. Signature of NziEB or CONTRACTOR (Circle one) Date 1. This permit was issued based on the information provided in the permit application and accompanying plans and specifications and is subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures. 2. This.permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and received prior to the date of expiration. An extension of no more than 180.days made be granted at the discretion of the Chief Building Official and maybe subject to a fee equal to one-half of the original permit fee. 3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard requirements, fees androcedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of the Chief Building Official and is not guaranteed. 4. No work of any manner shall be performed that shall results in a change. of the natural flow of water without prior and specific approval. 5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all required inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services Division. 6. The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, an violation of any provision of any applicable code or any ordinance or regulation of this jurisdiction. Approval of work is subject to field inspection. Signature of Chief Building Official — Date REQUESTS MUST BE MADE BY 11:59PM ANY BUSIN SS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. City of Wh6atP,,d 'j�ge FOR OFFICE USE ONLY I Date: 9// // � Plan/Permit #;/? / 7 J -1-77 Building & Inspection Services Division 7500 W. 29th Ave., Wheat Ridge, CO 80033 Plan Revie Fee: Office: 303-235-2855 * Fax: 303-237-8929 Inspection Line: 303-234-5933 Email: permitseci.wheatridae.co.us Building Permit Application Please complete all highlighted areas on both sides of this form. Incomplete applications may not be processed. *** Property Address: 4g8-0 k1Dh & Owner (, nnA Property Owner Email: Ak [In @ 2inna c/ q rew Mailing Address: (if different than property address) Address: Zoo Lip" Sf Co F ZZ3 City, State, Zip: Arch itect/Engineer: N /* Architect/Engineer E-mail: Contractor: Phone: Phone: 770- &2- FS -2,r Contractors City License # 1/1D Q 24J Phone: 303 — 115 - },6-66 Contractor E-mail Address: Cte0+,eCPStriA04-Il`M arl-1 Stan S CO jMall . CM4A Sub Contractors: /J {#- Electrical: W.R. City License # Other City Licensed Sub: City License # Plumbing: W.R. City License # Other City Licensed Sub: City License # Mechanical: W.R. City License # Complete all information on BOTH sides of this form COMMERCIAL ❑ RESIDENTIAL Description of work: (Check all that apply) ❑ NEW COMMERCIAL STRUCTURE ❑ ELECTRICAL SERVICE UPGRADE ❑ NEW RESIDENTIAL STRUCTURE ❑ COMMERCIAL ROOFING ❑ COMMERCIAL ADDITION ❑ RESIDENTIAL ROOFING ❑ RESDENTIAL ADDITION ❑ WINDOW REPLACEMENT ❑ COMMERCIAL ACCESSORY STRUCTURE (Garage, shed, deck, etc.) ❑ RESIDENTIAL ACCESSORY STRUCTURE (Garage, shed, deck, etc.) ❑ MECHANICAL SYSTEM/APPLIANCE REPAIR or REPLACEMENT ❑ PLUMBING SYSTEM/APPLIANCE REPAIR or REPLACMENT ❑ ELECTRICAL SYSTEM/APPLIANCE REPAIR or REPLACEMENT ❑ OTHER (Describe) (For ALL projects, please provide a detailed description of work to be performed, including current use of areas, proposed uses, square footage, existing condition and proposed new condition, appliance size and efficiency, type and amount of materials to be used, etc.) Sq. Ft./LF 75 Btu's Amps Squares Gallons Other Project Value: (Contract value or the cost of all materials and labor included in the entire project) $ ZOW Obi NERICONTRACTOR SIGNATURE Or UNDERSTANDING AND AGREEMENT 1 hereby certify that the setback distances proposed by this permit application are accurate and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record. that all measurements shown and allegations made are accurate: that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance with applicable City of Wheat Ridge codes and ordinances for work under any permit issued based on this application: that I am the legal owner or have been authorized by the legal owner of the property to perform the described work and am also authorized by the legal owner of any entity included on this application to list that entity on this application. 1, the applicant for this building permit application, warrant the truth (biness of the information provided on the application. CIRCLE ONE(OWNER) (CONTRACTOR) or (AUTHORIZED REPRESENTATIVE) of (OWNER) (CONTRACTOR) Electronic Signature (first and last name ; C\ DATE: DEPARTMENT USE ONLY ZONING COMMMENTS: OCCUPANCY CLASSIFICATION: Reviewer:t f i(W Q l . �d� BUILDING DEPARTMENT COMMENTS: Reviewer. Building Division Valuation: Wall Sign Calculation Sheet You must complete this sheet and include it in the submittal package for any new wall signs. You will also need to create a site plan and a detail sheet of the signage. e Project Address: Gam/ q%h Contractor: You are allowed 1 square foot of signage for every 1 linear foot of wall to which you are attaching a sign. All wall signs must be adjacent to a street or major interior drive.`F Step 1: Measure the length of the wall(s) where you are attaching the sign: Wall 1 - feet Wall 2 - feet Wall 3 - feet Step 2: The length of the wall is the allowable square footage for the wall sign. Wall 1 allowable signage- square feet Wall 2 allowable signage- square feet Wall 3 allowable signage- square feet Site Plan 1%'C\ x 1,71S 475 ?143ro as� o Ln x .S n N A as cr N °�c�°c o: Z � � a = r)CD /v O. O -11� CD a m CD CD m < f 0 l N 2ODa m Gi o OJ � £ z 0 Q s n � CDc o T i r� Q� Fc Z rn w ~ ~ o x c m 0\1 I I W -P U1 ID W o � � CL o Y n � D D � G a CD D O d�4 ' CSD SCD D �m Z� a xc F - � mf � F 9mam�a�a�� * -r, 0 N 00 :10 w C:)m N CL �• T CSD CO - I l J 0 n x y Z z PH � W M °O o N or n � Z N v D n v W N -i Z m u, rt -yi m Z o °i o O A a 2. < Z1 m to OEn to mo w 't7 Z rn in z C y D o+ C m m M N s [i o � � CL o Y n � D D � G a CD D O d�4 ' CSD SCD D �m Z� a xc F - � mf � F 9mam�a�a�� * -r, 0 N 00 :10 w C:)m N CL �• T CSD CO - I l J 0 n x y Z z PH � W M °O o N or n � Z N W C c m m M = Q -yi m rq o o A a �0En < Q+ m M mo w 't7 Z rn in �wh"�R MUMM APPROVED it- 'am for Code Com N Mans E xaminer Dote Vaadity of Mn,g: TAe issuorrce of o permd d approval oiP s and computation shotl trot be a Permit Iw. or on oPWov peomits an M me proves ont of the hutM np code or of mW dy presumhp to Give ourtwity to violate of mncei the pn v4*" of the BttddirrG codes a other ordhtonces of the oty sholl tot he valid. ON INSPF-C'r�ON must ' BE ON S1T m m m ? 5 V N A 1 11 n A U n f T A Zi C - Q CD C) D w a 49 a a Sq D y y r- ° S Z -I- o g --� _I o O rn a rn z o m ENED Z Cl m ul m Zl cy U, Z a .c 9_- _.= s ' CO o� i m Z m9�Na lD O A D C v y a .n a rD ' Z Z] 'J N m n Qps�mo5 Q1 U7 m ip S a o mig o [n r1 n 1.� 'I f INSPECTIONURECORD Ply 5t' INSPECTION REQUEST LINE: (303) 234-5933 Occupancy/Type Inspections will not be performed unless this card is posted on the project site. Call the inspection request line before 11:59 p.m. to receive an inspection the following business day.** Inspector Must Sign ALL Spaces pertinent to this project Foundation Inspections Date Inspector Comments Initials Pier Inspections from these entities should be requested one week in advance. For landscaping and parking inspections call 303-235-2846. For ROW and drainage inspections call 303-235-2861. For fire inspections contact the Fire Protection District for your project. Concrete Encased Ground (CEG) Foundation / P.E. Letter Floodplain Inspection (if applicable) Do Not Pour Concrete Prior To Approval Of The Above Inspections Underground/Slab Inspections Date Inspector Initials Comments Electrical Comments Sewer Service Plumbing Inspections from these entities should be requested one week in advance. For landscaping and parking inspections call 303-235-2846. For ROW and drainage inspections call 303-235-2861. For fire inspections contact the Fire Protection District for your project. Do Not Cover Underground or Below/In-Slab Work Prior To Approval Of The Above Inspections Rough Inspections Date Inspector Initials Comments Wall Sheathing Inspections from these entities should be requested one week in advance. For landscaping and parking inspections call 303-235-2846. For ROW and drainage inspections call 303-235-2861. For fire inspections contact the Fire Protection District for your project. Mid -Roof Floodplain Inspection (if applicable) Lath / Wall Tie Fire Inspection / Fire Protection Dist. Rough Electric Final Electrical Rough Plumbing/Gas Line Final Plumbing Rough Mechanical Final Mechanical Rough Framing Roof Rough Grading Final Window/Doors Insulation Final Building �I Drywall Screw/ Nail NOTE: All items must be completed and approved by Planning, Public Works, Fire and Building before a Certificate of Occupancy is issued. Approval of the Final Building inspection does not constitute authorization of occupancy. Final Inspections Date Inspector Initials Comments Landscaping & Parking / Planning Dept. Inspections from these entities should be requested one week in advance. For landscaping and parking inspections call 303-235-2846. For ROW and drainage inspections call 303-235-2861. For fire inspections contact the Fire Protection District for your project. ROW & Drainage / Public Works Dept. Floodplain Inspection (if applicable) Fire Inspection / Fire Protection Dist. Final Electrical Final Plumbing Final Mechanical Roof Final Window/Doors Final Building �I NOTE: All items must be completed and approved by Planning, Public Works, Fire and Building before a Certificate of Occupancy is issued. Approval of the Final Building inspection does not constitute authorization of occupancy. *For low voltage permits — Please be sure that rough inspections are completed from the Fire District and electrical low voltage by the Building Division. **For Inspection Time Window — Please email insptimerequest@ci.wheatridge.co.us by 8:00 A.M. the morning of the inspection with the property address in the subject line of the email. Time window is based on the inspector's route. Occupancy Is Not Permitted Until A Certificate of Occupancy Is Issued Protect This Card From The Weather City of Wheat Ridge Commercial Demolitio PERMIT - 201700442 PERMIT NO: 201700442 ISSUED: 04/03/2017 JOB ADDRESS: 4980 Kipling ST STE Al EXPIRES: 04/03/2018 JOB DESCRIPTION: Removing dividing walls - 30 LF *** CONTACTS *** OWNER 303-662-0923 CATHY ROSCIO GC (303)216-9947 Harold Johnson 090441 Blue Mountain Design, Inc. *** PARCEL INFO *** ZONE CODE: UA / Unassigned SUBDIVISION CODE: 333 / USE: UA / Unassigned BLOCK/LOT#: 0 / *** FEE SUMMARY *** ESTIMATED PROJECT VALUATION: 2,000.00 FEES Total Valuation 0.00 Demolition Fee 50.00 ** TOTAL ** 50.00 *** COMMENTS *** *** CONDITIONS *** Must comply with 2012 IBC, 2014 NEC and all applicable City of Wheat Ridge Municipal Codes. Work is subject to field inspections. I, by my signature, do hereby attest that the work to be performed shall comply with all accompanying approved plans and specifications, applicable building codes, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with this permit. I further attest that I am legally authorized to include all entities named within this document as parties to the work to be performed and that all work to b�performed is disclosed in this document and/or its' accompanying approved plans and specifications. —7) Z Signature of OWNER %CONTRACTOR (Circle one) Date 1. This permit was issued based on the information provided in the permit application and accompanying plans and specifications and is subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, po plans and procedures. 2. This permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and received prior to the date of expiration. An extension of no more than 180 days made be granted at the discretion of the Chief Building Official and may be subject to a fee equal to one-half of the originalpermit fee. 3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard requirements, fees androcedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of the Chief Building Official and is not guaranteed. 4, No work of any manner shall be performed that shall results in a change of the natural flow of water without prior and specific approval. 5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all required inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services Division. 6. The issuance or ranting of a permit shall not be construed to be a permit for or an approval of, an violation of any provision of any applicable code o ny ordinance oegul ign f this jurisdiction. Approval of work is subject to field inspection. k Signature of Chief Building Official Date REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. Inspection time requests will be accepted by email only. Please email requests to insptimerequestgei.wheatridge.co.us between 7:30am and 8:00am, the morning of the inspection. Please put the address of the inspection in the subject line. City of ]Wh6at Riclge COMMUNITY DEVELOPMENT Building & Inspection Services Division 7500 W. 29th Ave., Wheat Ridge, CO 80033 Office: 303-235-2855 * Fax: 303-237-8929 Inspection Line: 303-234-5933 Email: permits(a_cimheatridge.co.us FOR OFFICE USE ONLY Date: 4/3/P� Plan/Permit # lnfW Plan Review Fee: Building Permit Application *** Please complete all highlighted areas on both sides of this form. Incomplete applications may not be processed. *** Property Address: T Property Owner (please print): f % (� Phone: 0_2 i Property Owner Email: Mailing Address: (if different than property address) Address City, State, Zip: Architect/Engineer: Architect/Engineer E-mail: Phone: Contractor:3/,&2L– Z2 % L c= L / e: / ZJ P—, Contractors City License #: Phone: :50 Contractor E-mail Address: �,jj7�AJ 7-)e=T'4 Sub Contractors: Electrical: W.R. City License # Other City Licensed Sub: City License # Plumbing: W.R. City License # Other City Licensed Sub: City License # Mechanical: W.R. City License # Complete all information on BOTH sides of this form "ErCOMMERCIAL ❑ RESIDENTIAL Description of work: (Check all that apply) ❑ NEW COMMERCIAL STRUCTURE ❑ ELECTRICAL SERVICE UPGRADE ❑ NEW RESIDENTIAL STRUCTURE ❑ COMMERCIAL ROOFING ❑ COMMERCIAL ADDITION ❑ RESIDENTIAL ROOFING ❑ RESDENTIAL ADDITION ❑ WINDOW REPLACEMENT ❑ COMMERCIAL ACCESSORY STRUCTURE (Garage, shed, deck, etc.) ❑ RESIDENTIAL ACCESSORY STRUCTURE (Garage, shed, deck, etc.) ❑ MECHANICAL SYSTEM/APPLIANCE REPAIR or REPLACEMENT ❑ PLUMBING SYSTEM/APPLIANCE REPAIR or REPLACMENT ❑ ELECTRICAL SYSTEM/APPLIANCE REPAIR or REPLACEMENT OTHER (Describe) t�C,7y✓i��n�JG- (For ALL projects, please provide a detailed description of work to be performed, including current use of areas, proposed uses, square footage, existing condition and proposed new condition, appliance size and efficiency, type and amount of materials to be used, etc.) Sq. Ft./LF / ,�, O Btu's Amps Squares Gallons Other Project Value: (Contract value or the cost of all materials and labor included in the entire project) $ U� G OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance with applicable City of Wheat Ridge codes and ordinances for work under any permit issued based on this application; that I am the legal owner or have been authorized by the legal owner of the property to perform the described work and am also authorized by the legal owner of any entity included on this application to list that entity on this application. I, the applicant for this building permit application, warrant the truthfulness of the information provided on the application. CIRCLE ONE: (OWNER) (CONTRACTOR) or (AUTHORIZED REPR ENTATIVE) of (OWNER) (CONTRACTOR) Electronic Signature (first and last name): DATE: DEPARTMENT USE ONLY ZONING COMMMENTS: Reviewer: BUILDING DEPARTMENT COMMENTS: Reviewer. OCCUPANCY CLASSIFICATION: Building Division Valuation: $ BTG & ASSOCIATES,LLC BUILT ON TRUST LIMITED -ASSESSMENT OF SUSPECT ASBESTOS -CONTAINING MATERIALS RETAIL LEASE SPACE RENOVATION INSPECTION 4980 KIPLING STREET - UNIT #2 WHEAT RIDGE, COLORADO April 2, 2017 Prepared For: Mr. Harold A. Johnson Blue Mountain Design, Inc. c/o Mr. Troy Johnson & Susan Schimpeler 13010 W. 301h Drive Golden, Colorado 80401 Prepared By: Billy Godby, General Manager BTG & Associates, LLC 834-F South Perry Street — Suite 551 Castle Rock Colorado 80104 BTG Project No.: B172201.02 BTG & ASSOCIATES,LLC BUILT ON TRUST INTRODUCTION Blue Mountain Design, Inc., retained BTG & Associates, LLC (BTG) to conduct an assessment of suspect asbestos -containing materials (ACM) at the Retail Lease Space located at 4980 Kipling Street (Unit #2) in Wheat Ridge, Colorado. Mr. Billy Godby of BTG is an AHERA-accredited building inspector and is also licensed as a building inspector by the Colorado Department of Public Health and Environment (CDPHE) (License No. 14714 expires April 27, 2017) conducted the assessment on March 30, 2017. Copies of the inspector's certificates of accreditation and licensure are included in Appendix C. At the time of this limited inspection, BTG collected suspect asbestos -containing building materials (ACBM) from areas of renovation to take place. If other areas of the lease space will be renovated in the future, BTG recommends that these areas be inspected for ACBM prior to renovation and/or demolition. The following appendices supplement the results of this assessment: • Appendix A: Data Tables • Appendix B: Laboratory Reports • Appendix C: BTG & Laboratory Credentials ASSESSMENT DESCRIPTION BTG understands that the objective of this assessment was to identify ACM and/or presumed ACM (PACM) that must be removed prior to planned renovation/demolition of the Site. The samples collected by BTG during this assessment were submitted to Reservoirs Environmental, Inc. in Denver, Colorado for analysis using polarized light microscopy (PLM) in accordance with United States Environmental Protection Agency's (USEPA) method EPA/600R-93/116 (July 1993) for determining asbestos in bulk building materials. This laboratory is accredited for asbestos analysis using PLM by the National Institute of Standards and Technology National Voluntary Laboratory Accreditation Program (NVLAP). Certificates of laboratory accreditation and licensure are included in Appendix C. The EPA National Emissions Standard for Hazardous Air Pollutants (NESHAP) (40 CFR 61, Subparts A and M) has a requirement related to assessment of suspect ACM in buildings. Per CDPHE, Section I II.A.1.c., if the asbestos content of a sample of friable asbestos is estimated to be 1 % asbestos or less, but greater than 0%, by a method other than point counting (such as visual estimation), the determination shall be repeated using the point counting technique with polarized light microscopy (PLM). If a result obtained by point count is different from a result obtained by visual estimation, the point count result must be used. When no asbestos is detected by PLM, point counting is not required. Prior to beginning this assessment, 834-F South Perry Street 9 Suite #551 9 Castle Rock, CO 9 80104 • (720) 341-9495 BTG & ASSOCIATES,LLC BUM ON TRUST BTG confirmed with the client that BTG would point count samples reported as trace (<1%) asbestos, and consider results of 1 to 10% as positive for asbestos. RESULTS AND RECOMMENDATIONS The results of the assessment and recommendations are summarized in the table below. A table providing detailed results of the assessment is provided in Appendix A. A copy of the laboratory report is provided in Appendix B. Based on the laboratory analysis report, NO samples collected contain asbestos. Friable ACM No samples collected during the inspection contained friable asbestos at concentrations greater than 1 % asbestos under PLM analysis. Non -Friable ACM No samples collected during the inspection contained non -friable asbestos at concentrations greater than 1% asbestos under PLM analysis. Materials with <1% Asbestos No samples collected during the inspection contained concentrations of less than or equal to 1 % asbestos under PLM analysis. During renovation/demolition operations, materials may be uncovered which are different from those accessible for sampling during this assessment. Personnel in charge of demolition should be alerted to note materials uncovered during these operations which differ substantially from those included in this assessment. If suspect ACM are found, additional sampling by a CDPHE-licensed building inspector and analysis by a NVLAP-accredited laboratory should be performed to determine if the materials contain asbestos. ASSUMPTIONS AND LIMITATIONS The results, findings, conclusions, and recommendations expressed in the report are based only on conditions that were noted at the time of BTG's assessment. BTG's selection of sample locations and frequency of sampling was based on our observations and the assumption that like materials in the same area are homogeneous in content. The report is designed to aid the building owner, architect, construction manager, general contractors, and potential asbestos abatement contractors in locating ACM. Under no 834-F South Perry Street 9 Suite #551 • Castle Rock, CO • 80104 9 (720) 341-9495 BTG & ASSOCIATES,LLC BUILT ON TRUST circumstances is the report to be utilized as a bidding document or as a project specification document since it does not have all the components required to serve as an Asbestos Project Design document or an Abatement Work plan. Our professional services have been performed, our findings obtained, and our conclusions and recommendations prepared in accordance with customary principles and practices in the fields of environmental science and engineering. This statement is in lieu of other statements either expressed or implied. This report does not warrant against future operations or conditions, nor does it warrant against operations or conditions present of a type or at a location not investigated. This report is certified to Blue Mountain Design, Inc. The scope of services performed in execution of this evaluation may not be appropriate to satisfy the needs of other users, and use or re -use of this document or the findings, conclusions, or recommendations is at the risk of said user. ASSESSMENT METHODOLOGY BTG's inspector completed a walkthrough assessment of the building and recorded the areas of the building inspected, as well as areas where materials suspected of containing asbestos were located. BTG's inspector also evaluated the condition, accessibility, and friability of suspect ACM according to the following ratings: • Condition, as good (G), fair (F), or poor (P) • Friability, as friable (F), Category I non -friable (CAT 1), or Category II non -friable (CAT 11), according to the USEPA National Emissions Standard for Hazardous Air Pollutants (NESHAP) definitions in Section 4.0. When materials suspected of containing asbestos were identified, BTG's inspector collected representative bulk samples from each homogeneous area using the protocol presented in the following table: SUSPECT ACM SAMPLING PROTOCOL Homogeneous Area (HA) Category HA Size Minimum Number of Samples 1,000 SF or Less 3 Surfacing Materials 1,001-5,000 SF 5 >5,000 SF 7 or more Thermal System Insulation No Stipulation 3 of each type of TSI. (TSI) I (Must also sample all repair patches) 834-F South Perry Street • Suite #551 • Castle Rock, CO • 80104 • (720) 341-9495 BTG & ASSOCIATES,LLC BUILT ON TRUST SUSPECT ACM SAMPLING PROTOCOL Homogeneous Area (HA) Category HA Size Minimum Number of Samples Miscellaneous Materials No Stipulation One to 3 samples of each miscellaneous material. Note: A Homogeneous Area is defined to include surfacing material, thermal systems insulation, and miscellaneous material areas which are uniform in color, texture, construction and application date, and general appearance. Destructive access and sampling techniques were not used during this assessment. However, it is possible that additional materials are present that were not visible or accessible during BTG's assessment. If suspect materials are encountered during future renovation or demolition activities, they should be assumed to contain asbestos until evaluated by a qualified asbestos inspector. "Suspect" material includes, but is not limited to, any material serving as a sprayed on or troweled on acoustic or fireproofing surface; floor and ceiling tiles; drywall, joint compound, and related materials; transite panels, siding and shingles; thermal insulation and any material associated with mechanical systems; and binding agents such as tar sealant, mastic, adhesive, roofing tar, caulking, etc. REGULATIONS AND GUIDELINES EPA National Emissions Standard for Hazardous Air Pollutants (NESHAP) The U.S. Environmental Protection Agency (EPA) National Emissions Standards for Hazardous Air Pollutants (NESHAP) regulations for asbestos (40 CFR 61, Subparts A and M) apply to certain demolition and renovation projects in facilities containing ACM and/or presumed ACM (PACM). The NESHAP rule usually requires that all friable ACM and some categories of non -friable ACM be removed before a building is demolished, and may require localized removal before or as part of a renovation. For renovation projects where friable ACM will be disturbed, the NESHAP rule may require appropriate work practices or procedures for the control of emissions. The following EPA NESHAP definitions of ACM are very important in interpreting which NESHAP requirements may apply to your building: • Friable asbestos -containing material. any material containing more than 1 percent asbestos, determined using PLM analysis, that when dry, can be crumbled, pulverized, or reduced to powder by hand pressure. • Category l non -friable asbestos -containing material., asbestos -containing packings, gaskets, resilient floor covering, and asphalt roofing products containing more than 1 percent asbestos as determined using PLM. • Category l/ non -friable asbestos -containing material., any material excluding Category I non -friable ACM, containing more than 1 percent asbestos as determined using PLM that, when dry, cannot be crumbled, pulverized, or reduced to powder by hand pressure. • Regulated asbestos -containing material (RACM). (1) friable ACM, (2) Category 1 non -friable ACM that has become friable (3) Category I non -friable ACM that will be or has been subjected to 834-F South Perry Street 9 Suite #551 9 Castle Rock, CO • 80104 • (720) 341-9495 BTG & ASSOCIATES,LLC BUILT ON TRUST sanding, grinding, cutting, or abrading, or (4) Category II non -friable ACM that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder by the forces expected to act on the materials in the course of demolition or renovation operations regulated by NESHAP. According to NESHAPs, RACM need not be removed before demolition if: It is Category I non -friable ACM that is not in poor condition and is not friable. It is on a facility component that is enclosed in concrete or other similarly hard material and is adequately wet whenever exposed during demolition • It was discovered after demolition began, and as a result, cannot be safely removed. If not removed, the material must be kept wet until disposal. • It is Category II non -friable ACM and the probability is low that the material will become crumbled, pulverized, or reduced to powder during demolition. NESHAP also requires that the EPA or the state (if the state has been delegated authority under NESHAP) be notified before a building containing RACM is demolished, or before certain renovations impacting RACM begin. OSHA Asbestos Standards The U.S. Occupational Safety and Health Administration (OSHA) regulates employee exposure to asbestos in general industry (29 CFR 1910.1001) and construction (29 CFR 1926.1101). The OSHA asbestos standards provide a permissible exposure limit (PEL) of 0.1 fibers (equal to or longer than 5 micrometers) per cubic centimeter of air (fibers/cc) determined as an 8 -hour, time -weighted average (TWA) and an excursion limit of 1 fiber/cc as a 30 -minute TWA. The asbestos construction standard applies to exposure of employees to asbestos during abatement and renovation/demolition activities. The construction asbestos standard also applies to employees who may contact or disturb ACM during their work activities (e.g. maintenance and custodial workers). It is important to note that the OSHA regulations apply to materials that contain any detectable concentration of asbestos, whereas the NESHAP regulations only apply when the concentration is greater than 1%. The following are selected OSHA definitions regarding asbestos work: • Class I asbestos work: means activities involving the removal of TSI and surfacing ACM and PACM. • Class 11 asbestos work: means activities involving the removal of ACM which is not thermal system insulation or surfacing material. This includes, but is not limited to, the removal of asbestos -containing wallboard, floor tile and sheeting, roofing and siding shingles, and construction mastics. • Class 111 asbestos work: means repair and maintenance operations, where "ACM", including TSI and surfacing ACM and PACM, is likely to be disturbed. • Class IV asbestos work: means maintenance and custodial activities during which employees contact but do not disturb ACM or PACM and activities to clean up dust, waste and debris resulting from Class I, II, and III activities. 834-F South Perry Street • Suite #551 • Castle Rock, CO 9 80104 • (720) 341-9495 BTG & ASSOCIATES,LLC BUILT ON TRUST • Intact. means that the ACM has not crumbled, been pulverized, or otherwise deteriorated so that asbestos is no longer likely to be bound with its matrix. OSHA requires that specific work practices and procedures be followed to control asbestos exposure of employees involved in abatement or renovation activities as well as the building occupants. In addition, the OSHA standard provides requirements for exposure monitoring, employee training, medical surveillance, respiratory protection, signage, and other protective measures. LOCAL AND STATE REGULATIONS The Colorado Department of Public Health and Environment (CDPHE) has promulgated regulations pertaining to asbestos activities in Colorado Regulation 8, Part B. Regulation 813 is based on the EPA NESHAP requirements, with additional state -specific provisions for asbestos inspections, abatement, and other activities. Regulation 813 also identifies training and certification requirements for professionals performing asbestos work in the State of Colorado. A summary of the requirements related to renovation and demolition of structures containing ACM is provided below: 1. Regulation 813 requires that any public or private building must have an asbestos survey performed to confirm the presence of ACM prior to renovation or demolition activities. 2. If friable ACM will be removed or disturbed as part of the renovation/demolition activities, the ACM must be removed under abatement conditions before demolition begins. CDPHE Regulation 813 requires that a State of Colorado Licensed General Abatement Contractor (GAC) perform the removal in accordance with Section III.H (Abatement Sequence). 3. CDPHE must be notified for all renovations and demolitions of all residential and commercial structures and all asbestos abatement projects that exceed the trigger levels (50 linear feet, 32 square feet, or the volume equivalent to a 55 -gallon drum, "residential'I and (260 linear feet, 160 square feet, or the volume equivalent to a 55 -gallon drum, "commercial'J. The notification requirements apply to both friable and non -friable asbestos materials. Notifications must be postmarked or delivered at least 10 working days before initiating abatement activities, and must be made using CDPHE forms. 4. During demolition, all non -friable asbestos -containing materials are exempt from abatement activities provided that they remain in a non -friable state and are kept wet at all times during demolition activities. 5. During renovation, non -friable materials may remain in place if they are not disturbed during the renovation activities. If these materials will be disturbed, they must be removed prior renovation. 6. Waste materials containing friable ACM must be properly disposed of at a landfill licensed to receive friable ACM materials. This requirement applies even if the quantities are below the CDPHE trigger levels requiring an abatement permit. Non -friable ACM waste must be disposed of at an approved landfill that accepts non -friable materials. If waste contains a mixture of friable and non -friable materials, it must be disposed of at a landfill licensed to receive friable ACM materials. 7. A CDPHE licensed Air Monitoring Specialist (AMS) shall follow Regulation 813 Section III.P (Clearing Abatement Projects) prior to signing any demo permits at the site. 8. The building owner should be aware that removing ACM does not discharge ownership of the ACM. During transport or after burial in an approved landfill, any contamination throughout the lifetime of the material remains the responsibility of the building owner. 834-F South Perry Street 9 Suite #551 • Castle Rock, CO • 80104 9 (720) 341-9495 & ASSOCIATES,LLC r" BUILT ON TRUST QUALITY ASSURANCE BTG appreciates this opportunity to provide asbestos consulting services to Blue Mountain Design, Inc. We have enjoyed working with you on this project and look forward to meeting your needs in the future. Should any questions arise concerning this report, please contact us at (720) 341-9495. This report was prepared by: Billy Godby General Manager BTG & Associates, LLC 834-F South Perry Street 9 Suite #551 9 Castle Rock, CO 9 80104 • (720) 341-9495 B TG & ASSOCIATES,LLC BUILT ON TRUST Appendix A: Data Tables 834-F South Perry Street • Suite #551 • Castle Rock, CO • 80104 • (720) 341-9495 � CL _ d 0 �ci cj 22220 $>kL-/ §oao o � �J$�S LLI m�I3�a « CD ca �aE R2$�2J E§\k% ems# ■ �k k mJ \ � � 0 \ 0 k 2 / i M 2 U- § 2 2 § 3 E 2 � \ Ek Ue � w o 2 2 2 2 g - E o 0 » E � § / _ e o 0 0 \ f O k0 //< ■Q kk& O § = c g $ E _ \ u 0 m§ 2E\ 2 J i \ CO CO U f \ 11 m P $ 0 11 //\ it $ d m R \ k /_ j. @ � .\. \/-0 \ \ \ \ 7 k c = _ _ < m ® E . g \ . g c 7 $ £ i s / \ y 2 ° # 0 \ \ 0 E 11 / E O 2 5 3 K o ) # ) / ) / ) M / : a / © ) (D -i �4 aewe3R,1�011 / 3 a- O 5 \ 2 2 a 2 2 9 g m = % y \ 2 $ § $ > $ > 5 5 m > 2 E % 7 % m / / k ¥ ® a !y 7 2 3 0 0 0 < 2 .2 % (f > @ D C14 o n 0 « 0 ) �' / $ \ e ± ` < < < 4 = c ° e o e -M 0 0 0 o f a ( \ \ \ \ o o ) \ „ I Z Z @ 2 - �� �� �• �� �� 7 ~ { 2 / / \ g .ƒ BTG & ASSOCIATES,LLC BUILT ON TRUST Appendix B: Laboratory Data 834-F South Perry Street • Suite #551 • Castle Rock, CO • 80104 • (720) 341-9495 Reservoirs Environmental, Inc. Effective January 1, 2015 Reservoirs Environmental QA Manual T:\QAQC\Lab\Reservoirs Environmental QA Manual.doc REI LAB Reservoirs Environmental, Inc. March 30, 2017 BTG & Associates, LLC 834-F South Perry St. #551 Castle Rock CO 80104 Dear Customer, Subcontract Number: Laboratory Report: Project # / P.O. # Project Description: NA RES 375643-1 B172201.02 Lease Space #2 - 4980 Kipling St Wheat Ridge CO Reservoirs Environmental, Inc. is an analytical laboratory accredited for the analysis of Industrial Hygiene and Environmental matrices by the National Voluntary Laboratory Accreditation Program (NVLAP), Lab Code 101896-0 for Transmission Electron Microscopy (TEM) and Polarized Light Microscopy (PLM) analysis and the American Industrial Hygiene Association (AIHA), Lab ID 101533 - Accreditation Certificate #480 for Phase Contrast Microscopy (PCM) analysis. This laboratory is currently proficient in both Proficiency Testing and PAT programs respectively. Reservoirs Environmental, Inc. has analyzed the following samples for asbestos content as per your request. The analysis has been completed in general accordance with the appropriate methodology as stated in the attached analysis table. The results have been submitted to your office. RES 375643-1 is the job number assigned to this study. This report is considered highly confidential and the sole property of the customer. Reservoirs Environmental, Inc. will not discuss any part of this study with personnel other than those of the client. The results described in this report only apply to the samples analyzed. This report must not be used to claim endorsement of products or analytical results by NVLAP or any agency of the U.S. Government. This report shall not be reproduced except in full, without written approval from Reservoirs Environmental, Inc. Samples will be disposed of after sixty days unless longer storage is requested. If you have any questions about this report, please feel free to call 303-964-1986. Sincerely, t U, L/ L'{, cx-U Jeanne Spencer President P: 303-964-1986 5801 Logan Street, Suite 100 Denver, CO 80216 1-866-RESI-ENV F: 303-477-4275 www.reilab.com Page 1 of 1 U Z � Q F- 2 w 2 2 O > Z w � � 55 > � W U) W w F. e m � Q � § � \ o / n 4 w § 0 Q � � / � § 0 7 ƒ t Go � _ (D k�{ moo§ / (n C _ to ~ 1 m a I m -1 ■ w (.4 0 \ \ \ j� ) \ E 2 ¥ z 0 z \ \ - 0 m 0- a £ £ £ e / U) f± 3 5 m x 0 0 2 0 5 \ / m 2 \ / e / 2 2 @ % 2 \ z22 \ 2 \ E / § @ § ]� 2 & / 2 / zyo=� e \\\ E / 44 2 2 2 2 2 2 2 2E 0 ---.LU .... ■ R k � & \ a- r--7 E co £ \ \ / E \ \k f �\ E $\ 2 \ » 7 \ 0_ = s a 70 0 / .0 \ E / _/ / k z z 3 a Z@ 5 4 4 4 A 4 I u<»IOf <100<<< CN Cl) It k \ \ / \ § \ \ \ \ g / / w i \C:) / 3 / \ \ \ E 2 .0000co_ 0 $ $ & ? J 7 S \\ a u 2 E s a° Z E? z W f 1 ® J ` I I m C■ mai ■ q® ~ L) x lh D o x O g ■ 3 1 I–�-4w I -I LD WOUPW * •— 1� Men -- _ I I I i mN 1 (,I) awnloA aldweS MMD 'SPI '-h 3"- dw1•wdS*PH ;.. r 61 `a U00—Amp Jo -14 momm 0■7 Oi W C y UOPOMAXAMA -h '0111+f+o0 _• m -W 8 A JO eue Nod =aMY AawAe Ki9uaN1 (3 � � � Z i> � � i � A -h �■�0�%5W3 _ t�! N is 0uoqemfflmQ o a -h-o■oavd■I.o wom s '•ten 'LH LSlO @-3 'SPS UW'9 NNd WPW -WMDD Md coSr_ er Nd '—S WPw '—_4 �M 'aiaL '8 rasa SWABN "a• ,mi - "M IrI 4 i J _ _ — vmo 'emol Vow - am I I J i i (WQ m Wow) -h 'Osl 'i00t 'II Irl '1 *w - mu ow"We Voft &-I *woo Dead 1Md■1 U04S 1114 e mE e5 ¢ a I CL ix 1 s e i ix �Z t•va v pp d f a U q di N ICL • O _. t 3 E O D$ E !crI A a 3 II c r; 'c m n r 1 � .00 f'�o � a�w AQ ■gyp �' �•m++ � E � t 7 t1Y CC 40 m Y cc w t!i MJ I (y =S 0 S o O 2 , O t�pj'ro _ cc 4 4 t==`= N N 8 m OD OD N > �% } 111 t C A U a cC O air Qm 3 40 LLLLT ti- p 5 G O O m1� T y J€ } p CO 0 tl Z C C w ii0 C Q CD Q m 1177 co U of F- } p � — J t` u o cr y C E E V� O V � 0) � CS u m e «w a �0. �YQQ mm =�� gA j !- N of O lef to � Z T 9C �� U 2 � LL O Z w a g h U BTG & ASSOUATES,LLC BUILT ON TRUST Appendix C: BTG & Laboratory Credentials 834-F South Perry Street • Suite #551 • Castle Rock, CO • 80104 • (720) 341-9495 Colorado Dcpartpnent of Public Health and Environment ASBESTOS CERTIFICATIf3N This certifies that Billy Godhy Certification No.: 14714 has met the requirements of 25-7-507, C.R.S. and Air Quality Control Commission Regulation No. 8, Part B, and is hereby certified by the state of Colorado in the following discipline: Issued: Expires: Building Inspector* April 27, 2016 April 27, 2017 * This certificate is valid only with the possession of a current Division -approved training course certification in the discipline specified above. _ uu_ _` �_� A thorized APCD Reprme n aiwe SEAL „1 Q U H 0 z. 000 z v� U � .O 4-4 Q Q4-4rn} N � 7 o rP.+ W' W 0 U M a N � IC -1 y N Qu C � Qr p 7 7 { + Aw p C d o65 (� 6 ' 5 c „1 Q U H 0 z. 000 z v� U � .O 4-4 Q Q4-4rn} N � 7 o rP.+ W' W 0 U M a LO ti cu N L6 ■ ■ o o ^ U N (6P � �t U Uca O �. C W op m .0 0 Cr a w ; U ® � m ° 'a (D W 42co V QQ co o o o CO �. z O` CL Cl)� � p �CO er CN "'�' o � op ,o c a o u°_ *..� -1-- O N O O 2 �.cU Lo o m co to Qi00 +�(01 eu73 a N .� p U � ca 03 a? I-- co =`Q O Uco� o m `o" a ca o �� N cc (Op /1 \ .� 0 N -tg .. W C13 'coi� O ■ V2 U kai O o U mr IN m VERT KITCHEN 4980 Kipling St. Unit 1.13 A14, Wheatridge, CO 80033 NGMMZMMEM� ,tPro jct: Veft KitehanApex Engin r, tic �,. Architect. Ethos Architecture, 2701 La ence fit., Denver, Co Engin r. LD P. (720) 699-3222 J L dnfo@apex-eng ner .com o Sot lottormt1oll h tlwww,apax-snqht"rs.00m Building Code: 1012 Internatiotial Building Code Stdidbig Dqwftatit. Wheat Ridge, CO �71 Apex Engineers, Inc. I of 3 Title Block Line 1 Project Title: You can change this area Engineer. Project ID. using the "Settings" menu item Protect Descr: and then using the 'Printing Title dock" selection. CODE CES Calculations per AISC 360-10, IBC 2012, ASCE 7-10 Load Combination Set: ASCE 7-05 Material Pro erties, Analysis Method: Allowable Strength Design Fy : Steel Yield: 36.0 s Beam Bracing: Seam is Fully Braced against lateral -torsional buckling B; Modulus . 29,000.0 ks Bending Axis: Major Axis Bending V w° w w Applied Loads Service loads entered. Load Factors will be applied for calculations. Beam self weight calculated and added to loading Uniform Load :. D = 0,020, S - 0,030 ksf, Tributary Width =1H ft, (Roof Load) Uniform Load: D = 0,0540 ksf, Tributary Width = 6.0 ft, (CMU) DESIGN SUMMARYM " Maximum Bending Stress Ratio _ 0,217: 1 Maximum shear Stress Ratio 0,114 : 1 Section used for this span C12 2O.7 Sections used for this span C12 20»7 Ma: Apphed 9,958 k -ft Va : Applied 4.979 k Mn f Omega: Allowable 45.988 k -ft Vn/Omega : Allowable 43.769 k Load Combination +D+S+H Load Combination +D+S+H Location of maximum on span 4.000ft Location of maximum on Sparc 0.000 It Span # where maximum occurs Span # I Span # where maximum occurs Span If 1 Maximum Deflection Max Downward Transient Deflection 0,013 in Ratio = 7. Max Upward Transient Deflection 0.000 in Ratio = () <300,0 Max Downward Total Deflection 0.017 in Ratio : 55105 >=360. Max Upward Total Deflection 0.000 in Ratio : <360,0 Maximum Forces tresses for Lod Combinations Load Combination Max Stress Ratios Summary of Moment Values Summary of Shear Values Segment Length Span M V Mmax + Mmax - Me Max nx MnxlOmega Cb Rm Va Max Vnx Vnx/omega D Only Dsgn. L = 8.00 it 1 0,123 0,064 5.64 5.64 76.80 45.99 1.00 1,00 2.82 73.09 43.77 Dsgn, L = 8.00 ft 1 0,123 4.064 5.64 5.64 76.80 45.99 8,00 1.00 2.82 73.09 43.77 gyp +D+Lr+H Dsgn. L = 8.00 it 1 0,123 H64 5.64 5.64 76,80 45.99 1,00 8.00 2.82 73.09 4377 +D+S+H Dsgn. L = 8.00 If 1 0.227 0.214 9.96 9,96 76.80 45.99 9.00 1,00 4.98 73.09 43.77 +D+0.75OLr+0.750L+H Dsgn. L = 8.00 If 1 0.323 0.064 5.64 5.54 78.80 4x.99 1.00 1.00 2.82 73.09 43.77 +0+0.750L+0.750S+H Dsgn. L = 8.00 6t 1 0.193 0.101 8.88 8.88 76.80 45.99 1.00 1.00 4,44 73.09 43.77 +C+w+H Dsgn. L = 8.00 it i (1.123 0,064 5.64 5.64 76,80 45.99 1.00 1.00 2.82 73009 43.77 +0+0,70E4H Dsgn. L = 8.00 ft 1 0.123 0.064 5.64 5.64 76.80 45.99 1.00 1.00 2.82 73.09 43.77 41)+0 750Lr47 0L. 0 750WAI Dsgn. L = 8.00 It 1 0,123 0,064 5.64 5.64 76.80 45.99 1.00 1.010 2.82 73.419 43.77 +D+0.750L+0.750S40. 750W+H Dsgn. L = 8.00 ft 1 0.193 0,101 8.88 8,88 76,80 45.99 1.00 1.00 4.44 73.09 43,77 +D+0.75OLr-+0,750L+0.5250E+H Dsgn. L = 8.00 ft 1 0.123 0,064 5.64 5.64 76.80 45.99 1.00 1,00 2.82 7109 43,77 +0+0.750L+0.754S+0.5250 -44 Dsgn, L = 8.00 ft 1 0.193 0.101 Apex Engineers, 8.88 l 988 76.80 45.99 1.00 1.00 4.441 3 4337 Title BincX Line 1 Project Titjed You can change this area Engineer: Project ID: using the "Settings' menu item Project Descr: and then using the "Printing & Title Block' selection. Description : 8'Opening - Lintel Load Combination Max Stress Ratios Summary of Moment Values Summary of Shear Values Segment Length Span # R V iirnax + Wax M,atax' M -I Mnxt'Om'ega Cb Ren Va Max Vnx VnxtOmega Dsgn, L = 8.00 ft 1 0.074 0,039 138 3,38 76.80 45,99 1.00 1.00 1,69 7109 43,77 +0+60D+030E-H4 Dsgn, L = 8.00 If 1 0.074 0,039 3,38 138 76,80 45,99 1,00 1,00 1,69 7109 43,77 Overall Maximum Deflections Load Combination Span Wx. '-'Deff Location in Span Load Combination Max, Dell Location in Span C (�Xly' 1 6,6174 4.023 U000 0,000 Vertical Reactions Support notation: Far left is #1 Values in KIPS Load Combination Support I Support 2 Oreran MAXimurn 4.979 4.079 Overall MINimum 1,691 1.691 D Only 2.819 2.819 +D+L+H 2.819 2,819 +0-+Lf+H 2,819 2A19 +D+ +H 4,979 4,979 +D+0.750Lr+0,750L+H 2,819 2.819 +D-+0,750L,+0.750S+H 4,439 4,439 +D+W-++i 2.839 2,819 +D,+0,70E+H 2,835 2,819 +D+0.750Lr+0.750L*0,750W+H 2.819 2,819 -+D+0.750L-+0.75OS-,0,750W+H 4,439 4.439 +0,+0,750Lr+0.750L+0.5250E,+H 2,819 2,819 +D+0.750L+0,750S,+0,5250E+H 4,439 4.439 +0.6013 +H 9.691 1.691 +0,60D+0, 70E+H 1.691 1,691 D Only 2,839 2,819 Lr Only L Only S Only 2.160 2,160 W Only E Only H Only D Only 2.819 2,819 +D+L+H 2.819 2,819 4)44,.r+H 2,819 2,819 +D+S+H 4.979 4.979 +D+0,750Lr-+0350L-+H 2,819 2,819 +D+01501 -4750S44-1 4,439 4.439 +0-+W+H 2.519 2,819 +D+030E+H 2,819 2,819 +{)-+0.75OLr-+0,750L+0,750W+H 2.599 2.819 Apex Engineers, Inc. 3 of 3 T*11`#S*T & ti*A* 1, AN C* E TEST AND BALANCE REPORT FOR VKGG, INC. 4980 KIPLING STREET UNITA13ANDA14 WHEAT RIDGE, COLORADO APRIL 2016 MECHANICAL CONTRACTOR- E3 SERVICE GROUP MECHANICAL ENGINEER: THOMPSON ENGINEERING ARCHITECT- DESIGN LABORATORY PREPARED BY: FRONT RANGE TEST AND BALANCE Front Range Test & Balance oerfifies that all balancing is done in accordance ah NESS, AABC and ASHRAE standards. RO. Box 630112 # Highfamis Rarick Colorado 80163-0112 * (3D3) 888-4107 # frontrangeth0comastnet April 5,2016 Wheat ridge Building Department NAVI'vat, ridge, Colorado : VKGG, INC To Whom Itk one All test and balance work on VKGG, Inc. in Wheat Ridge, Colorado has n completed in accordance with N . B, AABC, and ASHRAE standards. Please let me know if you reed anything, else with regard to the Air Balance Reportfor KCC„ Inc. Sincerely, Chris :"doper Field Manager Front Range "est & Balance FRONT RANGE TEST AND BALANCE FAN TEST REPORT FiYr PROJECT, VKGG, INC. TEST `E; 4/5/2016 READINGS B' , FRONT RANGE TEST AND BALANCE AIR OUTLET TEST REPORT PROJECT; LAG, INC, SYSTEM, RTU -1 TEST APPARATUS: US: L W HOOD AREA OUTLET DESIGN PRELIMINARY FINAL REMARKS SERVED TYPE Z AK CFM VEL VELICFMVEL/CFM VEL t I CD 24X24 1.0 ---200 46 2 CD 24X24 tO 260 6 3 CD 24024 tO 200 38 4 CD 24X24 1,0 3004 CSD 24X24 tO 100 90 6 CD 24X24 1.0 100 135 a CD 24X24 1.0 100 6 ' TOTAL 1200 ARKS; (D CORRECTED FOR ALTITUDE OUTSIDE AIR DESIGN = 66 OUTSIDE AIR ACTUAL = 6 TEST DATE4/5/2016 READINGS BY,.CC FRONT RANGE TEST AND BALANCE AIR OUTLET TEST REPORT FST. 1G, I. SYSTEM:_TESTAPPARATU& FLOW HOOD AREA OUTLET DESIGN PRELIMINARY FINAL REMARKS SERVED NO, TYPE WE AK CFM VEL VEUCFM VELIUM VEL CFM T CD 2024 1.0 325 2 CD 24X24 tO 250 280, 3 3 CD 2024 IZ 275 4 CD 4 1.0 275 5 CD 2024 1.0 275 105 5 CD 2024 1.0 200 101 TOTAL 150 REMARKS- CORRECTED FOR ALTITUDE DELETED FED FROM TLS_ OUTSIDE AIR DESIGN= 240 OUTSIDE AIR ACTUAL = 243 TEST DATE4/5/2016 READINGS BY: CC FRONT RANGE TESTAND BALANCE AIR OUTLET TEST REPORT PROJECT: VKGG, INC. SYSTEM- TU -3 TEST APPARATUS: FLOW HOOD AREA OUTLET T DESIG PRELIMINARY FINAL REMARKS SERVED NO. TYPE SIZE AK CFM L VEUC.FM vEUCFM VEL I CD 24X24 tO 350 - 2 2 CD 2424 1.0 150 519 3 3 CCS 2024 1.0 350 465 4 CD 04 1,0 350 301 TOTAL 120 REMARKS,- CORRECTED FOR ALTITUDE 2 DELETED 3 NEW LOCATION OUTSIDE II DESIGN OUTSIDE AIR ACTUAL TEST" CRATE: 4/5/2016 DINGS : FRONT RANGE TEST AND BALANCE AIR OUTLET TEST REPORT PROJECT: VKGG, INC. SYSTEM "U-4 TEST APPARATUS -O HOOD AREA T DESIGN MI INAL E LMARKS SERVED "i YP SIZE AK CFM V FSA UCF if CFM LI) I CD 24X24 1.0 100 279 103 2 CD 24X24 tO 150 265 148 3 CD 24X24 tO 150 263 151 4 CD 24X24 tO 100 240 96 -CD 24X24 tO 350 225 285 6 CD 24X24 1,0 350 62 280 TOTAL 200 1063 REMARKS: CORRECTED FOR ALTITUDE OUTSIDE AIR DESIGN OUTSIDE AIR ACTUAL = 201 TEST DREADING$ BY: CC AO"''REIX ~ \��}� � \� �/ m VERT KITCHEN ling St. Unit A13 Project. Vert Kitchen Apex Engineers, Inc. Architect: Ethos Architecture, LLC 2701 Uwremos St*, benvar, Co A Engineer: tG P: (720) 68V-3222 AP E., � Chocked. JML into@apex-en iners.com Aron t in on Sh t napex-engineers.com Code: a Ridge, Apex Engineers, Inc, 1 of • 2mm Load Combination Max Stress Ratios Summary of Moment Values Summary of Shear Values Segment Length Span Lh V knaix'+ Mmax - Ma -Max M' nx 'M''n'x/Omega' Cb Rm Va Max Vnx Vnx/Omega Dsgn. L = 8,00 it 1 0,074 0,039 3,38 3,38 7640 45,99 1 ZO 1.00 1.69 7109 4177 -,0,60D+070E+H Ds n.. L = 8,00 ft 1 0.074 0,039 138 3.38 76.80 45.99 1,00 1,00 1.69 73,09 43,77 Overall Maximum Deflections Load Combination Span Max, "-'Dell Location in Span Load Combination Max, Dell Location in Span D Only I . 11 01 1 7 1 4 0.0174_. 4.0231 Ho 1 0 1 0 HOD Vertical Reactions Support notation: Far left is #1 Values in KIPS Load Combination Support's Support2. Chrinall MA imam 4,019 4.070 Overall MiNimum 1.691 1.691 D Cry 2.819 2,819 +O+L+H 2,819 2.899 +D+Lr4H 2.819 2.899 -D+S+H 4.079 4,979 +0-+0,750Lr-+0150L+H 2,819 2,819 40+0.750L+0,750S+H 4,439 4.439 +D+W+H 2.819 2,819 +0-+0,70E+H 2,819 2,819 +0-+0,750Lr-+0,750L+0.7504N-04 2.819 2.819 +0-4750L+0,750S+0350W+H 4,439 4,439 +D40.75OLr+0.750L+0.525OE4H 7819 2.819 40+0,750L+0,7505+0,525OE4H 4.439 4.439 +0.801} +H 1,691 1,691 +0,60D4,(3,70E+H 1,691 1,691 D Only 2.819 2.819 Lr Only L Only S Only ZM 2.160 W Only E Only H Only D Only 2,819 2.819 +D+L+H 2,819 2..819 +D44_r+H 2.819 7819 +D+S++i 4.979 4,979 +0+0.75OLr40,750L+H 2,819 2.899 +D+0,750L+0,750$+H 4.439 4.439 +D+W+H 2,819 2.819 +D+0,70E+H 2,819 2,819 +D+0,750Lr-+0,750L+0.750W+H 2,819 2,819 Apex Engineers, Inc. 3 of 3 CHANNEL LINTEL;.. RE: PLAN 7-.0. 0 ­ __ CONT., PL5. W/ 3/4`x5" E BOLT AT 2d STAGG E RE LINTEL DETAIL STAGGER (4) 3/4""x5" EXP. BOLTS EA. E N D mi 111 , l��v i q�� � 11 : ;1:i�li 11:41"oirciLlit'LlImel BUILDING CODE: STEEL MEMBERS 2012 INTERNATIONAL BUILDING CODE AS ADOBPTD AND/OR AMENDED BY LOCAL BUILDING CODES ASTM A992 ROOF LOADING INFORMATION: ASTM A36 ROOF DEAD LOAD ASTM A36 20 psf ROOF LIVE LOAD HIGH STRENGTH BOLTS 20 psf SNOW LOADING INFORMATION: ASTM F1554 (36 ksi) GROUND SNOW LOAD, Pg 30 psf ROOF SNOW LOAD, Pr 30 psf 1. THESE DRAWINGS ARE INTENDED TO BE USED WITH ARCHITECTURAL AND MECHANICAL DRAWINGS. CONTRACTOR IS RESPONSIBLE FOR COORDINATING SUCH REQUIREMENTS INTO THEIR SHOP DRAWINGS AND WORK. 2. NO OPENING SHALL BE MADE IN ANY STRUCTURAL MEMBER WITHOUT THE WRITTEN APPROVAL OF THE ENGINEER. 3. NO CHANGE IN SIZE OR DIMENSION OF STRUCTURAL MEMBERS SHALL BE MADE WITHOUT THE WRITTEN APPROVAL OF THE ENGINEER. 4. OPENINGS IN SLAB OF l'-4" AND LESS ONASIDE ARE GENERALLY NOT SHOWN ON THE STRUCTURAL DRAWINGS. REFER TO ARCHITECTURAL AND MECHANICAL DRAWINGS FOR SUCH OPENINGS. 5. THE CONTRACTOR IS RESPONSIBLE FOR LIMITING THE AMOUNT OF CONSTRUCTION LOAD IMPOSED UPON STRUCTURAL FRAMING. CONSTRUCTION LOADS SHALL NOT EXCEED THE DESIGN CAPACITY OF THE FRAMING AT THE TIME THE LOADS ARE IMPOSED. 6. THE STRUCTURE IS DESIGNED TO FUNCTION AS A UNIT UPON COMPLETION. THE CONTRACTOR IS RESPONSIBLE FOR FURNISHING ALL TEMPORARY BRACING AND/OR SUPPORT THAT MAY BE REQUIRED AS THE RESULT OF THE CONTRACTOR'S CONSTRUCTION METHODS AND/OR SEQUENCES. 7. UNLESS OTHERWISE NOTED, FIREPROOFING METHODS AND MATERIALS FOR STRUCTURAL MEMBERS ARE NOT SHOWN ON STRUCTURAL DRAWINGS. REFER TO ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR FIRE RATING REQUIREMENTS, FIRE PROOFING METHODS AND MATERIALS. 8. DO NOT SCALE THESE DRAWINGS, USE DIMENSIONS. 9. THE CONTRACTOR SHALL INFORM THE ARCHITECT/ENGINEER OF ANY DEVIATION FROM THE CONTRACT DOCUMENTS. THE CONTRACTOR SHALL NOT BE RELIEVED OF THE RESPONSIBILITY FOR SUCH DEVIATION BY THE ARCHITECT/ENGINEER'S APPROVAL OF SHOP DRAWINGS, PRODUCT DATA, ETC., UNLESS HE HAS SPECIFICALLY INFORMED THE ARCHITECT/ENGINEER OF SUCH DEVIATION AT THE TIME OF SUBMISSION, AND THE ARCHITECT/ ENGINEER HAS GIVEN WRITTEN APPROVAL TO THE SPECIFIC DEVIATION. 10. ALL THINGS WHICH, IN THE OPINION OF THE CONTRACTOR, APPEAR TO BE DEFICIENCIES, OMISSIONS, CONTRADICTIONS, BE BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER. PLANS AND/OR SPECIFICATIONS WILL BE CORRECTED, OR WRITTEN INTERPRETATION OF THE ALLEGED DEFICIENCY, OMISSION, CONTRADICTION OR AMBIGUITY WILL BE MADE BY THE ARCHITECT/ENGINEER BEFORE THE AFFECTED WORK PROCEEDS. 11. CONTRACTOR TO NOTIFY APEX ENGINEERS, INC AT LEAST 48 HOURS IN ADVANCE OF ANY CONCRETE POUR. 12. SPECIAL INSPECTIONS ARE REQUIRED IN ACCORDANCE WITH THE INTERNATIONAL BUILDING CODE AND THE SPECIFICATIONS OF THIS PROJECT PER SPECIAL INSPECTION TABLE THIS SHEET. SPECIAL INSPECTIONFREQUENCY CODE CONT TASK .PER. REFERENCE STRUCTURAL STEEL 1704.3 FIELD WELDING OF STRUCTURAL STEEL X FIELD BOLTING OF STRUCTURAL STEEL X STEEL FRAMING INSPECTION X REINFORCED MASONRY 1704.5 PLACING OF REINFORCING STEEL X PLACING OF CMU AND GROUT X STEEL NOTES 1. ALL STRUCTURAL STEEL TO BE FABRICATED AND ERECTED IN ACCORDANCE WITH AISC "CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES," 2. BOLTED CONNECTIONS: ALL BOLTED CONNECTIONS SHALL BE SNUG -TIGHT IN ACCORDANCE WITH THE "SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS" PUBLISHED BY THE RESEARCH COUNCIL ON STRUCTURAL CONNECTIONS. 3. WELDED CONNECTIONS: ALL WELDING SHALL BE IN ACCORDANCE WITH THE "STRUCTURAL WELDING SOCIETY CODE" (AWS D1.1-96) PUBLISHED BY THE AMERICAN WELDING SOCIETY. ELECTRODES FOR WELDING SHALL COMPLY WITH THE REQUIREMENTS OF TABLE 3.1 OF (AWS D1.1-96). ALL WELDING TO BE DONE BY QUALIFIED WELDERS CONFORMING TO THE AMERICAN WELDhNG SOCIETY STANDARDS. 4. SPLICING OF STEEL MEMBERS, UNLESS SHOWN ON THE DRAWINGS, IS PROHIBITED WITHOUT THE WRITTEN APPROVAL OF I THE ENGINEER. 5. CHANGES IN SIZE OR POSITION OF THE STRUCTURAL ELEMENTS, AND HOLES, SLOTS, CUTS, ETC. THROUGH ANY MEMBER, ARE NOT PERMITTED UNLESS THEY ARE DETAILED ON THE APPROVED SHOP DRAWINGS. 6. NO FINAL BOLTING OR WELDING SHALL BE MADE UNTIL AS MUCH OF THE STRUCTURE AS WILL BE STIFFENED THEREBY HAS BEEN PROPERLY ALIGNED. 7. FABRICATE ALL BEAMS WITH THE MILL CAMBER UP U.N.O. 8. ALL COLUMN BASE PLATES SHALL BE SOLIDLY GROUTED WITH NON - SHRINK GROUT UNDER THE ENTIRE BASE PLATE AREA. GROUT SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 5000 PSI @ 28 DAYS. 9. ALL VISIBLE WELDED CONNECTIONS ON ARCHITECTURAL ELEMENTS TO BE GROUND SMOOTH. DO NOT REDUCE THROAT SIZE OF WELD. 10. THE FABRICATOR SHALL BE RESPONSIBLE FOR THE DESIGN AND PERFORMANCE OF ALL CONNECTIONS NOT FULLY DESIGNED OR DETAILED ON THE CONTRACT DOCUMENTS. FABRICATOR IS TO FURNISH ARCHITECT/ ENGINEER WITH SHOP DRAWINGS FOR APPROVAL.. 11. STEEL MEMBERS ON THE EXTERIOR OF THE BUILDING OR EXPOSED TO SOIL MUST BE, AT A MINIMUM, PROPERLY PRIMED WITH RUST INHIBITING PRIMER AND PAINTED. STEEL MEMBERS COMPLETELY ENCLOSED IN BUILDING ENVELOPE DO NOT REQUIRE PRIMER OR PAINT, U.N.O.. REFER TO ARCHITECTURAL DOCUMENTS FOR ADDITIONAL, REQUIREMENTS OF EXPOSED STEEL. STEEL MATERIAL SCHEDULE STEEL MEMBERS MATERIAL WIDE FLANGE SHAPES (W) ASTM A992 CHANNELS (C), ANGLES (L) ASTM A36 PLATES ASTM A36 HOLLOW STRUCTURAL SHAPES (HSS) ASTM A500, GRADE B HIGH STRENGTH BOLTS ASTM A325 ANCHOR BOLTS ASTM F1554 (36 ksi) EPDXY BOLTS ASTM A36 ADHESIVE IN CONCRETE HILTI HIT -Hy 150 (OR HIT-HY 250) ADHESIVE IN MASONRY HILTI HIT-HY 20 EXPANSION BOLTS HILTI KWIK BOLT III ARCHITECTURAL C DESIGN LABORATORY 1585 GLENCO STREET DENVER, COLORADO 80220 kwahab@ethos-architecture.com (303)941-5368 r � ♦ f � }' .r i. r r °•••RE �� E r ---x ,,cif N w. A X43292 ' •� V / 4 DATE 03/17/2016 PHASE PERMIT SET REVISIONS um 11 ELEVATION VIEW S 1. 0 1 3/411 = 1 1-011 FOR OFFICE USEONLYT)(,-, City of ,:9'Wh6at 10 c:jTY DEVELOPT tr" plawpermit Building & Inspection Servlces Division >t .. 7500 W. 2e Ave., Wheat Ridge, CO 80033 Plan Review Office: 303-235-2855 * Fax: 303-237-8920 ,- Inspection Line; 303-234-5933 Building rApplication , Pteaae complete all highlighted e s on both sides of this form. Inmoplete applications may not be processed. .. w. Property Address # ° i A ck-L.- PhoneS)_ - ?Zcj Property Owner * c .. , AlinAddress: (if different than property address) Address; City, State, Zip: ArchitectlEngineerE-mail: ' A cc Phone. - 0414 hone.-0414'x.Y, evn Contractorw Li L�- oint o License .\ .-. + � � � 1: C x Contractor E-mail Address: Sub Cont Electrical: GIZEATlumbin: 6PLA M696 t, !mechanical: MR. City License # W` R. City License Wk City License Other City Licensed Sub: Other City Licensed Sub. City License # City License Complete plete all information oe BOTH sides of this form f t + (Check all that apply) NEW COMMERCIAL STRUCTURE ELECTRICAL SERVICE UPGRADE NEW RESIDENTIAL STRUCTURE COMMERCIAL ROOFING COMMERCIAL ADDITION RESIDENTIAL ROOFING RESDENTIAL ADDITION WINDOW REPLACEMENT COMMERCIAL ACCESSORY STRUCTURE (Garage, shed, deck, etc.) RESIDENTIAL ACCESSORY STRUCTURE (Garage, shed, deck, etc.) MECHANICAL SYSTEM APPLIANCE REPAIR or REPLACEMENT PLUMBING SYSTEM/APPLIANCE REPAIR or REPLACMENT ELECTRICAL SYSTEM/,APPLIANCE REPAIR or REPLACEMENT OTTER {Describe} s� yq{� �y My �+. g� &'l t o iti ri-si T to- Ms- * j Vii. �� `v' � � d .� ksj v,) C,- O -V\ c� ce- '11", L) fo 1�,Pw C,Plvl C 'ru k-" Sq. Ft./LF Btu's Gallons Amps Squares Other J+ect Value. (Contract value or the crest of iii materiels and labor Included In the 9DILM project) x � w w:. . ! ♦ ♦:::..M��� City of ]RrWh6atR�e CITY OF WHEAT RIDGE BUILDING AND INSPECTION SERVICES DIVISION 7500 W 29th Ave Wheat Ridge, CO 80033-8001 p, 301235,2855.f 301237.8929 A copy of this form must be completed by each agency indicated on the Permit Submittal Checklist for the project type and be attached to the Building Permit Application at the time of submission. Applications presented for submission without a completed Proof of Submission form from a required agency will not be accepted or processed." , Date: MEMMU= ) ; I ttingdocuments: A i Project Type/Description: IMEM23MM -TfT -717 -ency Wbelow, hereby acknowledge receipt of documents necessary indicated above. Aggripy r9pi9sen-ted; (Please check one) o Wheat Ridge Fire Protection ,)It Arvada Fire Protection • Wheat Ridge Water District • Consolidated Mutual Water District • Valley Water District • Denver Water • Wheat Ridge Sanitation District • Clear Creek Sanitation District • Fruitdale Sanitation District • Westridge Sanitation District • Other Agency Notes: , RX4 Zc�v"e I'Z —1 LA— 1 Signature: Date: (Agency Representative) City of ommuNiTYDEwLoPmENT SUB -CONTRACTOR t' R d d I, TION FORM Pr 33 eject Address: o - Pe General Contra€ term FEIectricalContractor Company Name: 8ael State License Master # Signature of Authorized Agent Date LI'iur b' g Co acto Com em °emsP A,�pteaphone3� State license #:Master #: Wheat Ridge License Signature of Authorized A.geni Date ech .cal Contractor C anap e: ,� 'hone: meat .ie Lieense #b Signature of Authorized Agent Date *Thisapplication a be + t' t by each sub -contractor ci ma+ the same. VKGG INC. Expansion notes: 4980 Kipling Street Unit A-12 (expanding into unit A-13 and A-1 4) Wheat Ridge, CO 80033 Noah Stephens, Owner 303-882-2008 noah@vertkitchen.com VKGG is a WHOLESALE FOOD OPERATION, VKGG currently operates a WHOLESALE comrnerciai federaHy inspected VVE�ars,e inspected and under the jurisdiction of the FDA and USDA. VKGG operatr,,s .ir'def tihe svicl guidelines of these federal agencies. VKGG does not sell directly to the PLA)!.'p�:. 1"he out of the location will correspond with all federal guidelines for, commercial kit,,: (, -ns', The ktdhen is designed for this purpose and meets and exceer-J's,Jefferson County standard's, VKGG will update our current file with the JEFFCO health dept,, LUt does not require approval for the facility. VKGG lies outside of their jurisdiction, VKGG has been operating for 2 years at the CUrrent facility in Wheat Ridgra (T tai' Kipling unit A-12) and is now expanding to meet the cornparies growing needs. VKGG w'Pll (i.,xpand in the two adjacent units at the same address (units A-13 and A-14), The new exp ansion will have no cooking or hot food production in the expanded area. VKGG will only Use tr),.r ne-w space for cold prep, cold storage dry storage, office, shipping/receiving and employee locker roon-is and facilities. There is no need for a grease trap, as no rooking will occur. The space will strictly be used for assembly of f,esl-i cold ford prodUcts and The existing unit will remain as is. VKGG will have approximately 8 to 10 employees. ineirwishi-A SquM -- VKGG ft 11111120 15, Page 1 (424 T"Is LEASE is made and entered into this M by ano between StOVOO In consideration Of the rentai and the Mutual covenants and agreements hereislafter contamed, La ndICU'd and Tenant hereby enter into the f0flOwing Lease, (the `Lease'): ARTICLE I - 0041SE I'l EMMSCS• Landlord teases to Tenant, and Tenant les from Landiorn and agrees to take possession of sulte(s) numbered the r orsido, Or the he 'Shopping COMWL tOcifted in MAUJU0014 Cal 80033. For the pu seatat square fooprge of the Leased Premises shalt be deemed to ware ionate share ar the coir on area, The Shopping Center, 0 be, SAAMU4 improvements and location of the Leaser! Prernises are as outfined and legally described on Exhibit A attached hereto, ti then with a mien-oXclUsive right, subject to the provisions hereof, to ease all appurtenances thereto, including, but not limited to, apy plazas, common areas, walkways or other areas of the Shopping Center clesignated by Landlord for the exclusive or non-exclusive use of the tenants of the Shosteng Center. Such letting is upon and subject, to the terms, coed ons and covenants herein set, forth, and Teriant covenants as a material part of the consideration for this Lease to Xep and perforin each and all of said teMs, conditions and covenants by it to be kept and performed and that r,,his Lease is made upon the condition of such performance, Lanolord reserves, the right to rerneasure Tenant's Premises wituin nine ry (90) days or CoMimencenrient OaM The square footAge of the Rentable Area deterrNned ot that time sroH be adjuste,,,l If ft is dilfferent from the square footage noted herein, The Base Rent, Operating Costs dnd Tax Pays aft M1 61SO br» adjusted m accordavice with the appropriate rate per square foot to ref e,t the correct annuaiprionthly payment. ARTICLE 11 -TERM 2,1 lgn< The term or this LeAse and Tenant's obb9sition to pay rent hereunder shall cornmence upon November 1,_2M �the "COMMOMOMOOt ftt*"), The terra shall end at 11,59 ti,rn, on April 30,_= (the -Tiarl"IrMtJon D*W') unless sooner terminated 1% herein provided (trie "Lea" Term'), 2,2 Other thaii as set forth in fAbJW", the "Tenant Work Letter, Lar dkird shaH have nO obligation for the completion of the Premises, Tenant acknowledges that no promises, representations, statement-,, La be on inn t ased or warranties have tiftn made by or on behalf of ridboo tu Tenant respecting t c dit o the Lea. premises the rnanner of operating the Shotping Center, or the making of repairs to the Lease Premises, except as may be specifically provided herein, The taking of possession of, the Leased preroises dytenarat sball constitute an acknowledgernent by Tenant that the Leased Premises were taken "AS IS", in good and satisfactory condition and free of any latent defects, Tenant shall upon termination of the Lease, by lapse of time or otherwise remove all of Teriant'S PrOpettY therefrOrn (it required by Landlord) and shall surrender the Leased Premises to Landlord in as R ood condition as when Tenant took pos".ssaran, orriorn olein, normal wear excepted. Landlord does not warranty the accuracy Of ally existing bufldrng plans user] by the Tenant which have riot been prepared by the current Landlord even though as a coineity Landlord may provide the Tenant a copy of the existing building plans. 23 QgW» if for any reason Landlord delivers the Leased Premises afttr the Comirencerilent Date, rental for the interim period between the ears mencenient Date. and actual date of Possession snali be prorated based upon the actual number of days in such period, The Lease. shiefl not be, void or voidab4e in the event of a late delivery of the Leased Premises by the Landlord, nor shalt Landlord be fiaWe for any loss or darnatIe therefrom, Tenant's irumllipy or failure to take posWi0on of the Waxed Premises on the Commencen*ot Date or such later date that Lwiftrd delivers the Leased Premises shall not delay tne cornmencement of the term of this Le&se or Tenant's obligation to pay rPrint. hereunder. No eariier- or later delivery or taking possession of the Leased Premises ithall Oange the tertntriation, date of this Lease, p"e I in**, MOU wdepwxwce squav - VKGG lix, iwrm, Ps" 2 d 24 in writing from me to Orm, without VlOr de0jand and without offset or deductioll im lawful money of the United States, "#AjjLB&A4 OM fOIlOwV The first NO monthly installment of Base Pent and NNN shall be payaWe upon completion of, the Free Rent Period, but gra no event later than Aphi 1, 2016, If the terror shali commence upon a day other than the first calendar day to the month, rotin Tanant shall pay upon the corrifflancernment Date a Pro Rata porttimi of the rnonthly Base, Rent as above provoed so that all futore rental Oyfflents eittl tare due on the firs -t day of every month, The term *Lo"e year, shalt mean each twelve (1 2) month period scab wtuern to the, Commencement Date, mumm M= Annual base Monthly base PSF rent total rent I 5 — 4/30/16 $ - $ - $ 5/1/16 — 4/30/17 $8,25 $ 4$,460,50 $ 4,03838 5/1/17 —4/$0/1,8 $ &SO $ 49,929.00 $ 4,16015 5/1/18 —4/30/19 $8,75 $ 51,397,50 $ 4,28113 5/1/19 —4/30/20 $9,01 $ $2,924.74 4,410.40 5/1,/'20 — 4/30/21 $9.29 $ 54,569.46 4,547.46 $ 257,28110 The first NO monthly installment of Base Pent and NNN shall be payaWe upon completion of, the Free Rent Period, but gra no event later than Aphi 1, 2016, If the terror shali commence upon a day other than the first calendar day to the month, rotin Tanant shall pay upon the corrifflancernment Date a Pro Rata porttimi of the rnonthly Base, Rent as above provoed so that all futore rental Oyfflents eittl tare due on the firs -t day of every month, The term *Lo"e year, shalt mean each twelve (1 2) month period scab wtuern to the, Commencement Date, mumm M= tridep"WA sq"s - VKGG Inc, 10FU2015, Pap 3 d 74 3,3AdotKUW a t and Percentage Rent _&= Except for the firsti 6 months, of the lease, ri I ,, dditton to base Ren ual (if applicable), fruit shall pay to Landlord in rhunthly tristaHmerits, as adtfitionai rent, an amount do to Tenant's Paira Share of Landlord's Operating Expensw,las defined In Article 4.2 herein, 'Tenant's Prorate Share' as useti in this Lease shall be equal td 8 traction by which the tape rentable area of Tenant's Premises ars to the total rentable area of 1100r SPaCe in than Shopping Center as of the dater hereof. if there is a change, In the total Shoppinq Center rentable area as of, an addition to the Shopping Center, partial destruction, modification Or similar cause, which event causes a reduction or incivase on a permanent tuisis, Landlord shall cause adjustments in the crirnputatrons as shelf be necessary to provide for any suCh changes. Landlord's system for me0sUreffrarat Of rentable area shall be applied sirriiiarly to all tenants in the Shopping (,"enter, 333 gUajWjLgLAddjWn&RrXj, Prior to Jantairy I of each catendar year roilicioung the calendar year Ira which this Lesii; cornmences the ('Base Year') Landlord shall ftimish to Tenant a written statement showing in reasonable detail the estirnated Landlord's Operating Expense for the next forthoarning calendar year, At the first monthly rent payment date in such, calendar year following Tenant's romitit Of such gatement and at Bch of the other monthly rent payment dates during such year, Tenant shail pay to Landlord as additional rent, 11ir of an ,art ount equal to Tenant's Pro Rata shave of the cAnnated annual operating Expenses, in the event of the inability of Landiora kir any reason to furouill sale statement prior to Ninuary 1, Tenant shall pay, at the monthly rent payrnent date next faltowing 'Tenant's receipt of said statement, any additionaf rent which shall have accrued priOr to such payrnevit date. On or before March 31 (or as coon thereafter as possible) in each calendar year after commencing anth the calendar year the Base Year, Landlord shall furnish to Tenant as written staterrient showing in reasonable detail toe xectual Operating Expenses incurred during the preceding calendar year or portion thereof, At the nutrithly rent payment next following Tenant's recgipt of such statement, Tenant shall pay to Landlord as additional rent in the event, of an excess (or Tenant shall receive as credit to be untitled against the next succeeding monthly operating expense payrrient in the event of a deficiency) an amount equal to the difference between (i) the additional rent payable by Tenant based upon the actual Operating Expenses for the preceding calendar year., and (6) the additional rent paid by Tenant based upon tntirnated Operating Expenses for such year, Estimates Of Operating Expenses shail be made exclusively by Landlord, based upon Landlord's experience with actuad costs and reasonalde pooffttons: 3,4 In the event Tenant's Pro Rata Share of conshon ares ext>enses (CAM) increases by niore, than Ten percent (10%) in any Lease Year, Terrant may audit Landlord's CAM in order to verity the accuracy of CAM charges provided that (i) Tenant spacificallY ftllignStei the fis year(s) that 'Tenant intends to audit, %vhich shall be a year within three (3) years, of the date of the audit but Must be within the Term of, this LeaSe, and (it) such audit will be conducted only during regular business hours at the office where. Landlord maintains CAM expense rea,)rds and only after Tenant gives Landlord t6niftaom (14) days notice. Tenant shall deliver to Landlord a copy of the results of such audit within fifteen (IS) days of its reciept by Tenant. No such audit shall he conducted if any other termist has conducted an audit for the time fm6od Tenant intends to audit and Landlord furnishes to Tenant as cupof the results of such audit, No audit shail be conducted at any to that Tenant is in default of any of the trans of the Lease, No subtenant shall have array right to conduct in audit and no assignee qhaV conduct, an audit for any period during which such assignee was not In possession of file Premises. All ccAts; for the audit including costs for copies shail be borne by the Tenant, 3,S L4W-ft=,, Any rent (whether Base Rent, Percentage Rent or Additionai Rent) or other amount one, from Tenant to Landlord under this Lease not paid within five (5) days of the day due shall be assessed an additional one time tarty charge fear any such late payment in the amount of fifteen percent (15%) of the a# twat of such late payrn(Vot, om inisitipailios Squam -• VKGGk Inc, * ar 41 (fai, L a. : The ." `" is the Kart Of the pfaing Cent designat i y Landlord from Carrie to tithe for the common use ; all anly ash er such property be Owned leased by Landlord, rrctardrrrg among talar facilities, parkingarea, sidewalks, landscaping, curbs, loading area, private st .is and alleys, fighting facilities, hallways, malls, rest and other brews and improvements provided by Landlord for the common use of all tenants, all of which shall be subject to Landlord's le rna and control and shaii be operated and maintained in such Manner as Landlord, in its sole discretion, shall deternlrler landlord reserves the unrestricted right to change the building perftneters, driveways, parking ar aas, store sizes and identity and type of other stores or tenancies and add building() andaror structures, provided only that the size of the Premises and minimum parkins focilites as required by governmental authorities having jurisdiction, shall not, be substantially or" Matel'411Y impar Tenant and its employees, ctuitioners and invitees shah have the rion-exclusa e riblet and license to usic the Common Area as ctanstitut i truth tuna to time, sur„h us to , iri common with Landlord, rather teraarats rat the hoppi��r and any �h perstsa s pe aai ed by Landlord to use the same and subject to such reasonable el rules and regulatroris gtrueming iise as Landlord May f� thea to time redo in including automobiles the designation y speduc areas within the Shopping Center or in a reasonable proximity th s to lh filch ado 14 s o reed by Tenant, its employees, sobtenants and iowtt?es shaii be parked. Tenant agrees to friraiish to Landlord a complete list of the names of the Tenant's employees at the Privnises, who have automobiles and it the license numbers thereof and or all other tar vshitls$ operated by tenant, Landlord shall have the right to use artiOns of the ornmon Areas tier the purpose of displays, promotions, programs, game or other uses v"alss th may be ref bate s to all or part of the general public. Landlord shall have the right to close portions of the Common Areas from tl ffin to tir. for repairs and to prevent a raaar'sttg of public right therein and for any other legitimate purpose, Landlord shalt rave the riot to d . timistk parking areas or outside storage areas for specific tenants and to designate paat'*mg areas for Tonarit' rrspicay s at Ls,1dda O*s sola rt scred n, 42 "dam': 0Waating Cxpense,a andjor° phis shaali mean the total costs anti expenses incurred in poratlnt , managing and r . intaining tale shotapi Center, including ithout lsrrAtaatiOn, such rraarratarrahl brad repair as shall be required in Landlord's judgneat is preserve the Shopping Center in the same, c ditkin and staartis as it was at the tl of orripleb0o of the original c ostrrattion and installation; the chats an tiaraexteriord expenses planting, maintaining and replacing tascapinga cater a s e � p � ventilating;sage and rep car�sarat of painting, required licenses and permits, crests of exterior It kiting, exterior signs; maintenance, repair and clean ng of Cameron Area floors; tebaovai of %n w, trash, rubbish, garbage and other refuse, parking lot maintenance and line str'iplogx all costs and experts of fire protection and sprinkler rarawitenance, ecarrity rOsts, tr4flc entral an policing” orrititsiti n costs of replacement acid /fir P 11 for dile leasing of ,ally nachinerya equipment, including lighting, l cod in connKtion with operation, rnaanaagernent or maintenance; repair and/or replacernent of the rdof and of on-site grater lines, sanitary arm storm sewer ho"; 1 tet and expense of leasing all or any port of the Common Area, the cola of management perSOnlUff and supervision (including compensation tion and benefit Cost'; of such personool), opeclal assessolorits, any and all goyerareental it posibons and surcharges; administrative, charges equal to fibre percent (5%) of the total cost,$ Of Operating, managing and maintaining the Shopping Center, and ansa costs incurred by the Landlord in making capital improvertlepts, reasonable ressives for anticipated capital improvements, or other modifications to the ShOttising Center or any part thererf; and any instaHatkril of equipmarit or ntaternio., or makes other improvements required to comply with applicable taws, orders or regulations, of goverrrmeaatasi authorities enacted after the date hereof, haat roosts of Stich improvements, lultin'le at, materials or modifications shall to. arriortsaad over the Useful life Of stiff Improvement or modification amount, in accordance with such r onable life and amortization schedules and shall be determined by Landlord in accordance with generally accepted arcoutiting grin pl : and costs incurred in engaging experts or mer consultants to assist Landlord in making any of the pornptatations required under this Lease. In addition to the above, Operating Expenses shall be deemed to lticione all premiums paid for all Insurance by Landlord which insurance Landlord agrees to carry in accordance with the terms of Article TX, Section g,t hereof, Current Operating Expense is estimates a per wuaam,. t t per year, Operating Expense slaatd€ not include leasing coslnaisslons, cost of r"epalrs or other asGark to the extent that such is irisairaid and rrascsran pr s are lar rved therefore and costs of repairs or rebudding necessitated by c onde rrinati ', it - VXGG IM, any talon of the aaratY as or applied, Tenant shall, upon dechantl, de "t cash with ndlo f If be in an amount sr ffieki�it to sto the aaryty� l of sat to its genas amount, and Tenant's failure to do Shalt a material breach Of dalS Wasp, LAlord shall not be required to keep the SeiolritY Oeposit separate from Its fine l f hds and Tenant Shall till t interest earned the Security Sat. TT Tenant shall flaky and faithfuPy perform every provision of this Lease to be performed by Tenant, the Security Deposit or any lance thereof shalt be returned to "Tenant (or, at Landlord's 00 01", to the last transferee of Tenant's irate st hereunder) within sixty (f days after the expiration of tad Lease Term and the Tenant's delivery of the Leased Premises to Landlord with as written stateroarit listing tile exact reasons for retention, of any portion of the Security Deposit; provided, however, that Landlord Creasy retain the g . arrty Deposit until such time as any arnovnt dace fircri X Te riant s been determined and paid in Rall, waiuding any portion thereof that may have been utilized by Landlord to cure any default, or applied to any damage suffered try Landlord. Tenant shall not assign or encumber its contingent rights frs Security de sit separate f °i oars Lease, Arad neither Landlord nor its success s or assigns shirr da h bound try any such assignment or eracaarrataran . In thra event of any sate or transfer of the hopping renter by Landlord, by foreclosure, deed in lieu the f or otperaise, Tenant shall took only to the new las it rd for return to the Security Deposit if Such SocuritY Deposit is actually transferred las said Pandford, ARTICLF-VI-TAXES f,, t W 0: s eased ire this Lease, the tern, "' l to Tax",means any aricf all general and special faxes or impositions of every kind and nature wriaatsoever ie�red, assessed i POSed rap a or with resPect to the Stroplang Center, any Leasehold improveffients, fixtures, installations, additions and equipment whether owned by Landlord or Tenant or nattier be(Au,,.e of or in crinnecton with the Landlord's ownership, leasing and otinnition of the t optirn Center, including wai hoot limitation, ream estate taxes, parsorial propefty tears, general or special assessrnents and duties or levies charged or levied upon or assessed against toe Shopping Center and personal pro, y, transit taxes, all cuts and expenses (including regal fees and court costs) for the protest or reduction of property taxes or assessments in connection with the Shopping Center, or any tax or exercise on rent or any anther tax. (however er d ° =ri ) on account of rental receipt for use,, and occupancy Of 0 or any of tate hopping Center, whether any such taxes are imposed by the United States, state ref Colorado, the County of or any local governmental municipality, authorty or agerKy or any political subdivision of any there -of. Real estate Taxes shall not tridude arty net Inc iia, capital stock, sue ten, transfer, frank , gift, estate and inheritanLe taxes; provided, however, if at wily time during the terse, hereof, the tax or excise on rents or income or ottaer tax, however described, is levied or assessed by trie State of Colorado or any political subdivuiron thereof, on ascationt of the rent hereunder or the interest of Landlord under this Lease, such tax shall be deemed Real Estate Tax, n it shall the r sponsibi ity of d�aariatra a ccs IraY or a;�rt# � t� trn flail ai3i Peal Estate Taxes imp upon the shopping center which b orae due car payableduring tfie Lease To Ta Tenant' covenants and agrees to pay promptly when due all personal Co y taxes on pessonal property of "Tenant on the Leased Premises and earl federal, state and nKvi err tai taxes, "W as taxes, use taxes, Social Security taxes, unemployment taxes and taxes withheld from wages and saaiaaries paid to Terianirs emptoyeas, the nonpayment of which might give rise to a Iran on the Leased Premises or Tenant's interest therein, and to furnish if reque ed by Landlord evidence of payments, frK �t�) s..�gf �.,. wt.� p t sod: Landlord shall havaa the seta right to contest any tains asses, ed against the Shopping Center. Landlord shali pay to or credit T`emant with any abaternent, reduction or recovery of any taxes attributable to the, Lease Term to the extent such abatement, reduction or revery reduces Tenaynt,S Pro Rata share of taxes tar any calendar year with the Lease Term, th Tenant's Pro Rata Share of all costs and expenses incurred by Landlord including attorrrsy'S few in connection with such aabaaterrrent reduction or rte. uer'y. ra. TT d : Tenant agr es tie paiy its Pro Ra`ate haare, as defined it) Article3.3. of al Estate Taxes as dafinQ herein above. "Tenant shall psy an estimated as tint as solely determined is Landlord by written notice to tenant of its Pro Rate Share of such taxes to landlord together with all other rhOnthtif payments made by Tenant under the terms of this Lease on the first pay of each and every calendar month during the Lease Terve,. on or before March :TT for as soon thereafter as possible) ars each calendar year ciarnmericing witti the calendar year after the Base Year, Landlord shall furnish to Tenant a written statement showing in reasonable shaa€i fine actual Real Estate "Taxes otcurred during the preceding calendar year of portion thereof with respect tri the Shopping Center and 'Teraarit.s Pro Rata Share thereof, ,At the monthly rent payment next following Tenant's . eipt of Such to a= Tenant, ant shall pay to Landlord as adettronal rarest era the event df ars excess ( T ant strap recalve a credit to be applied against the next Succeeding Monthly Real Estate Tax payment las the event of a deficiency) ars arhounit, equaat td the difference bet (t) the Real Estate "Tax payable by Tenant based upon the actual Real Estate Tax for ase, preceding calendar year, arid (aa) the Real Estate Tax paid by Tenant based up on estimated l Estate Tax for such year, Estimates of Peal Estate, Tax shalt be rte exclusively by Landlord, based capon LarldlordS experiente with actual costs and reasonable i , anerpeenoe Sili_ VKGG tna. 7,t : During the Lease Term tine Premises shall be used solely for the purpose of conducting business of trice pia tion, notion and the operation of a cacommissary commis ry t tchen sten n public retail service,, arid fes° her pu without tare prior written consent of landlord. The Tenant may not sell sondwsches to the public in Valu n sufpciernt to Interfere with the Subway tenant's exclusive use. "r. M : T ant convents to o ate the Lea, .s Pre . 's w tinuously durtrag the entseca farm of this Lease with due diligence and efficiency so as to produce a rhalutnurn volume of gross sales, sub -t to causes bayorad T°dnarnt's coutroi, for pulses of this Lease, continuously" shall mean been; open for business on all days and during the favours that are customary considering the nature of Tenant's business and the location of the Shopping Center with no t rrnitaabon. t.:3 , " n € lin f atnt sfaall neat use tine Prerrasws nor perm€t anything to be dssrne in or about the Premises whicti will in any ,gay conffict with any lass, status, ordinance, or r ovemmental rule or, regulation or which may hemina er be enacted or prordulgated. Tenant shall, at its sole cost and expense, promptly comply with all tars, statutes, ordinances and governmental rules, regulations flow in force or whicti may hereafter be in force anti with the requirements of any Board of Fire Underwriters or other sirrils r body now or hereafter constituted reta ing to or affecting the condition, use or occupancy of tine Premises excluding structural characTes not relaters to or affected by TO nnatni`s nrn r Farms tr acts. lWjThe Preanal s shall not used fiat tine`« carrying rail of any aesrtion, fire-, bankruptcy or other dnstress sales without the prior written consent of the landlord nor shall Tenant keep, use, sell or offer for sale in or upon the Premises any article which may be prohibited by arra insurance policy in force train time to brine coversng the Shopping Center. in the event Tenant's us or conduCt Of business in or on the Premises results in any ,ncrea$ s in premiums for the msursi nce carried frarrn tone to orne by Landlord, Tenant shall pay any Such increase in prerniurns as AddAional Herat with tan (1 0) slays after bills for such ad rtsonar prerniums, shall rendered try the tansdloro. Tenant agrees to prornphy ctxMPly carni iii reasonable requirements of the insurance, ,authority or of any imurer ,now or hereafter in effect relaatrrig to the Pr'esrTnises: I'S ft Tenant agr . li it shalt not commit, suffer or permit any wastes, darnnage, disfiguration or rn)ury to final premises or the ST Ppang Center or the fixturefaa and equtprrnent located theresr or ttiereon or flet°mart or suffer any overloading of the flocirs thereof rasa Use or permit tri be, used any dangerous, nauseous or offensive trade or b# Sme,ss and shall not cause or permit any AuuianM .fs $N p ` i ' y° ,all personal property ari the Least; I*rrrnnses alta#I be placed therein at the task of Tenant only, Landlord ,hall not be liable for any loss or damage to any pro ,,rty of Tenant or its agents, employees a anvil s caused by theft, steam, olas`tric'sty, selvage, gas or odors or from mater, airs or snow which may teak into, issue or flow into the Leased Premises from any part of the Shopping carat r or from any other place or quarter or for any damage done to Tenant's property rn moving same to or fronn the Shopping Center or the leased Premises, except that landlord will be, liable for damages arta losses rtmolting from negliflence, of the Landlord or Its employees or ire- ns Or entities hired by Landlord to Perform work at the ShOPPing ter, Tenant shall gave Lanifloid prompt written notice of any damage to or defects to the Lead Premises, rr ► t mityT Tenant covenants and agr to pay all charges for water, sewer, gas, electt'icrty, isght, hent, power, telephone or other utility semces used or consumed it) or supplied to the teased Premises, 'Etre de , ination of any such otifities small at the optionof Landlord be either (I) by a separate are,ter installed by Tenant at its expense, or (si) ajilociated by landlord to Tenant on an equitable trasis. Should landlord elect to ssafd Premises, Tenant small upon Rent under the terms hereof, y, or for Tenant's Arta its used premises Such prod percentage of the total spua assessed Tenant by virtue of utilized in 'Tenant's operation, first year of occupancy, or per of ~ rd total utilities is equdal Landlord if necessary, tarndic payment which shall be, vayah all or any portion of, the utility yorvices to be used or consumed on the Leased santatipn of such statement for such ubhty serice pay to lands as ittiO nal e amount of said stat rrient if it represents utifitY serviceto the Teased Pramises le share of said stater cat if It includes utility service to an area greater tfnan the donate share will be based upon the. square footage clauPied by Tenant as a footage of the area teetered, adjusted higher for any extra usage r'easi nably !nant's disproportionate use of utilities as a result of Tenants use or equipment aid proration of utnlstnes shall be revuswed by Landlord and Tenant at the egad of the lically then after, at which time Landlord $ball tdeterrrnrne if telae present percentage in relation to the use Of total services py all file tenants and will be adjusted by may elect to estimate the average monthly east and eS blish a monthly escrow by T°eriant along with Its monthly rent and adjusted at the end of each year. do i _VK t- 13M,M,015, Pap I of 24 If any such aatilities s above defined stead be shaar aan or �€ tenants occupied units, t eir € cent t20% of the total 006t Of such utilities shall be. assessagainst the varant unit and the remaining eighty percent (go. ) stall to assessed and allocated as outfined ave, iidldrtf shit sraott dltadllity to eriiiat sn the event that any fatality tar a€� frrarrs gray source of supply or for any meson not within Landlord's reasonable control. All utilities required by Tenant and not provided by 1 ndirartf, s het fabove, shall be contraactisd for day Teriant in Tenant's own name with true afrproDriaate anality suppliers. Tenant shall pay for all such utilities. Landlord covenants and agrOeS to pay frit° MI utilities used or cransurried in the Common Areas str t ° to L androrths right to receive from Tenant Tenant's Pro Rate SharP Of Oiverastsng Expense as provided for in Article III, 8.2 �fadlpC ��` eta ��pd, .f3rr tU; Subject to Articles . , t ,1, and 2 LandlaPif covenants and agrees ta, retrain, repWr, replaceand keep the ornmon Areas las hereinafter defir ed) aand this ptartunl$ Of the Shopping Center c at inlrig rentable ams that sonsist of foundations, exterior wai aather wails (excluding tciref ,onts and glass), structure, sunfiners anti root structure, the structural portions of bearing units and structural colui-faps and bearris in gam, safe and sanitary condition, order and repair and in atcordan e with all applicable laws, ordinances, orders, stairs and regut tions tat governmental authorities having larr°'ssitiction, t#.Ml rr�tr3 T tram covefRints anti agrees to maintain, repaw, repWi e and keep the Leased Premises (P cept only such parts thereof expressly the obligation 0 Landlord under Article 8,2) including all leasehold rrraprov°ements therein, whether installed by Landlord or Tenaarit including aarthout hruiteabOn tree entire storefront, all ceslsrit#sp interior aa34s> door iylfnngs arid gls; i€ Teraint signs, the portion of the heabrig, ventilating and cooling equiPrnent in and for the exclusive use of the Leased Premises, all of Tenants fiirtasshings, fixtures and personal property it, the tweas d rrernises ;n good, safe and sanitary condition, order and repair and in accordance With all applicable laws, ordinances, orders, rides andrelations o yernraaetaral autho nes having jurlsd8 €cera, to pay all costs and Pspen., , in cimir ctio therewith (including luding without limitation, costs and expenses kir janitorial and cleaning services,, painting, replascernent of damaged or broken glass and other breakable materials in the Leased erases and ptaceinent Of fights and light fixtures in or sung the Leased Premises), and td Contact for the surae in Tenant's OWn tremae° All maintenance and repairs by Tenant shall be done ta qtly in a and workmanlike laashion and without clttyainishirag the original l raualrey of free used premises or the Shopping tenter, 8. 3,1 HVAC fats ionance and Repair' Landlord will provide maintenance of HVAC units and twill thrOugh e.taarp , Tenant is onrasttala for i sr of to Ptgsrip rrt sn flee Parfitt ter alar, their Assigns, ntra d CAM worken. darriatte a unit, , n f . tl i Landlord may from time to time aaiter or change 811Y Of file i queue rats Or permit such to be altered or changed on the Shoplatrig Center" (titpiti ing the Common Areas) by the ConStructl0n,. removal, reloc tr or alterationof such improvements, in the sale of c 0duc�ting any such alterations, Landlnrd shall have the right to a alterations, stetas ural of otherallse, to the Leased Premises, including services and rin'litles for the Leased Premises, but in so dolsag Stahl to the extent pmible minimize any interference with tenant's test* Pati cupancy elf r ss try the Leased Pr „ a s. EtLQt Tenant, shall not, without prior written consent Of Landlord, make any b1terati s, improvements or additions that exceed a test of $IS000,00 to the Leased Premises including, ding, dart hot limited to, partitions, wells ddv rffags, r �erings and special t hong installations. In the e ent fPosrst desires to a� any alterations, ;Mrr Vefnents or additions, Tenant shall first sudnrtt to Landisro, two copies of fin8l COnstfuctkin documents and soedfiCations ,a awe and obtain LandlorWs written approval prior to curnmencing any such work. Notice sof any charge Barters newest submittal to tie L�aradl and within racy four (24) h s. Landlord may s e, m VKGG lac *1101 Page 8 Of 24 rc.iSrair Tenant Tray TSitsiarat rant, Landia l s I to r =ne lana �t vialterations, improvements of Landlord shall decide at to its best interest, to do so. Tenant agrees that it shall Compensate Landlord for said pian review and said construction sUpervision within teff (i i) days of hitting. All alterations, irnp oveor nts or additions,hetfat r in or upon the Leased Pre, mni&S shall become Landlord's Property rod shall remain upon the Leased predysys at the torrilinetion of this Lease by lapse of time otherwise without compensation to Tenant (e ceptto only Tenant's moveable furniture, trade fixtures, office and professional t, floor d,, however, that Landlord , , Tenant);provide iiprer shall have the right to require (errant to remove Stich niter puns, improve nts or additions at T ant*s cost upon the termnlotion of anis Lease, and the repair of any daoaa� alis to the Lean premises or the aai4ct§r%c� as result of any such removal shall be pard for by Tenant, The work necessary ry to make airy repairs required pursuant to MIS, SeCtkin 8,5, or to make airy alterations, irnprovernents or addltsrefs to the Leased Premises to which Landlord may mnsent pursuant hereto, shall to dine day ens ayees or contractors employed by Laredlord, or with U ndf£ir£fd's consent in writing givers prior to the letting of retract, by contractors , played by Tenant, but in each case only laser written contract al)laroved in writing by Landlord, and subject to all conditions 1,andlord may �rm o e including but not limited to the receipt by Landlord from Tenant of as copy of the perapral contractor's contract and a copy of the complete job dcsdpet by division; a list of all subcontractors, vendors, suppliers, a copy of the oontracttor's certiflcaste of insurance for General Liability; a copy of the contractor's certificate of insurance for Worrers Compensation or the CCIA Independent. Contractors, Aatacation Form approved by , a statexrient signed by contractor that the contractor is vaalsing its ot€€ to lien the &a Yi and s n l�emriity state nt contractor rsarvina liability against owner/Landlord for cortstraacVCin Performed kyr Tenant Ih the rrsa satisfactory to Landlord, shah pmaitly Pay to Landlord or to i"arirtt's r.oritriictoi„ as tdier rasa may be, wriell rite, that cost of all such work and of all decorating required by reason thetect, and upon completion, deliver to Landlord, if payment is made direCtlY to Tenant's contractors, evil ce of Payment and waivers Of all liens for tabor, spices or materials, c sty, da liens for tabor, services or materials re?aatiri to such work and defend and hoed Landlord harmless from ail costs, damages, liens and expenses related meretc, Upon completion of work, Landlord rust receive a signed affidavit by Tenant's stearal Con ractrirs in the €curie so isdiL ory to landlord and signed waivers by Tenant's general contractor aril all its subcontractors in the form satisfect0ty to Landlord, Sri the event Landlord incurs ally expenses in the r crow l of trash or vara to, tiff* Cleaning Of 9 vstrars, iariGtll� £a to L ark loading £l Asa as dare€�t result of "Tenant*s contractors work theta Tenant agrees to it shaft romper', Larirllord wittim seven (7) days of taitim , The provisions and requirements of Article 8.5 hereof, includmg treat not limited to Tenant's obligation to secure a bond(s) inderriniflong Landlord,, shalt apply to aall Chitriges, 8,6 Tenant coverhints that the Tenant will riot suffer or pr rata"st dxriisg Cria term hereof any ctsanrc`s or other trams for work, labor, services or roatoriasls ordered by the Tenant or for the cost of whichTenant diaY be in any way obligated to attach to the tareiriases or to the Shofrpinfi Center. At least, five () days prier to the corurne,ricturent cif any work permitted to be done by persons requested by the Tenant on the Premises, the Tenant st,ail notify the Landlord of the, proposed work so that the Landlord may avail its if of the provisions of any statares or ordinances such as Sion 38-22-105 (7) of the Calorado qvvised Statues (197 3), Miring any such work on toe Preir)ises, the Landlord or its felly os rstatives shall nava the right to go upon and ms'pect tete Premises at ail carnes and shall fame the right to frost and keep posted thereon notices such as true provided for by ffilicpon 38- 22-1015(2), CR,S, (1773) or to take further action which the Landlord may deern to be per for the cti'an of the Landlord's interest In tire, Premises, 8, 6,1 ed L aK If at any tirrr' as hers r encumbrance is died or recorded against the rnis Promises or the Center as a result of Tenant's failure to satisfy Sarni, Tenant shall promptly discharge said lien or encumbrance, and if said lien or encumbrance has not been removed within thirty (Tei) days from the date it rs filers or recorded against the Demiult in cash eQual t.0 premises, eraarat agrees it will de ith Landlord an hOri moa aaciatily �to+aoti�r d#orb one hundred My Percent sT (1 ) of the amount of the lien filed or post a and dull leave the same on deposit with Landlord until said idea is discharged, tt Tenant shall at any time fail neglect or raOu u to sattsty any scarfs lien or encumbrance, or shall fail, negl t or refuse to dire Landlord as herelitabove prThilded, then Landlcii,d shall have the option (butshall not be r . uir to yahely such lien or encumbrance and any arnounts paid themfore by Landiord shall be deemed additioreil rent and shall be paid by Tenant to Landlord at the next ease ypolt payment date after any such payment and shalt tear interest at the lesser of (a) the maximum rate permitted by lawn or (b) eighteen n percent (i.fl'tria) per annum from the respective, £Erie date until paid, .CLEIX-INSURANC . i r Landlord asg ,s to rry or cause tae, oe carried during the teraii fist t Public liability ins sralrace On the Shopping Center providing average of not less trian one million dollars ($1,000,000-00) for personal injury of dealt) risft Out of any one occu rence. Landlord also adrees to ca during ttse term hereof insurance for fire, ascended coverage, vandalism and malicious mischief, Insuring ft Shopping Center (excluding foundations, excavations and other re, -insurable items) for the flail insuradie valvae thereof, Landlord may, but shall mit to liable to, take out and carry any other forin or forms of irwurance as it or the mortgagees of Landlord reasonably to be advis tale, Notwithstanding any contribution for T v, tit to the cost Of squKe'. 9iirtr"��latfa, pop 5 d214 oce insurance Premiums s s PrOvideo in Article- III, T riaarat 6:rars ti ledrust it has rru right to receive any odin s from anysuchinsurance policies cawed by t rrdicrrd srrd that such insurance will be ftir the l benefit nt of Landlord eth no coverage for Tenant nor any risk v1surad 89dinat, b n �0, . Tenant agrees to carry and maintain in (i) public 1i 4ity inssur nc Includingbodily acrd dam ,pest § iruturY aratr�sa l 9 dal y witti respect t llamas, .ands or tions by any imury person, firm or Corporation i any rising rri fr , relatedconnectedor with the Conduct and operation of Such p Tenant's business ruse the ar is sa paiddes shalt be written on corprehensiv basis with limitsof ra t t r i such higher limits as Landlord or the rratsrtp es of Landlord fray require from bre to less than time, till tine grad rterrrt ea r p l sail rsr ty including ing but not limited ¢ to � st r ,�a rosin �t uOrs, .psypprinpklb�eer s ,�3i.ya�ga ra aararrrqy ail t) g Y rrt s� dh f a yi+ervi S} try y alteration i.m{arr.Yp 0.�d8,5�Aae�ear�'sF pgir"iLar�ra+a# i�CL�:Sm �m8. 'FdF iw�W�� rdRJ anythingRBS the r�&�r �$ &4 t4R�:Stiv4?v9id rrrpv%��Fr�S�E 0.. C�� an arattatiirit rtss l tca tine full r pi rent rest f such property without deduction for depreciation sho irir landlord as ars sdditaeirraa2 irrsra d sats arrt r t �y , tiri) standard fora worker's compensation and glass insurance, in employees liability MSurdn 9rr arr#saiirrts t %3 i3r d by saay aappir iii government earreatierrt s urel y lar a<age;t(v comprehensiveautomobile a amount net l than the full replay �asat a is rat any such glass bra n : � � hatigity insurance prali v €rl unman all owned, raearihuwned and hired vehicles used in the conduct, of Teri rat's bossiness and orperasttad capon or parked insane the Shopping Center area with firniLS Of liability of not, less di la $250,000,00 'corrnce for bodily ir)cr-y and , ,dooccurrence for property each f� rid 500,�band aOther armOrforms of insurances tie rrort eS Of dinns� and i ss interruption etsrr r Landlord may reasonably nasb€y requir from Curler to time in form, m arnourits and for insurance risks against which as printe,nt tenant would erect fts lt. All policies shall be taken aunt with insurers acceptable Cas taaaadirrrd in p frsrM satisfactory iinoa orriefor timeto Landlord, Tenant agrees that certificates 6rof t d t+ insurance d to L t rd tag onas pr bierd or the rs after placing ortgages of reat the cart a r copy f insurance miry, s required insurance, but irr no vent tater than t (td) Til yds s afterTenant written tata�ta possessionekes delivered � by the Premises, All Wines shall require that ria ieaast tda y .- y" prior insurers, prior tai t rrriinaatiOn, cariceloincin or material change In such iusurt nCe, Tenant agrees that ire tha event of damage lar aestructl0n to the tessehuld improvements sie the Premises r ve:*rad by insursri e required to be taken out lay Tenant pursaikint trs this section, Teri rat shall use the proceedS Or such insurance for the purpose of repairing, or r 5tonn sasrh leasehold irsaprca eovets. ars the event Of dilitnage Or destruction Of the ShOPping Center entitling either Landlord or the Tenant to terrivri to this tease purses rat is Article XII herein, then it the Promises Clave also been d rrr a ed, rernivint onii surrender to Landlord, in accordance with provisions of this Lease, the feaS.*hoId improverrients and the r rnises 93 5, pt his; The patties hereto agree tont any orad all tire, extend uca drop and/or property damage Insurance which is required to be tarried by either strut be endorsed wid, a subesgation clause, substantuiVy as ajxyes; "This insurance shall most be frivallboted should the insured waive, inritin prior to a toloi, any and all hereto f ht of recovery aairsst gray party for Mass occurring tae tile pM,*,rty d r`bed tar rrt'", a n4 each part, waives ail claims for recovery from the attar party, its re °s, sets or paplssydt*s fir udy toss damage (whether or not such loss or damage is caused by ne it en e of the otther, pasty), and noterithotanding any provisions contained in this Lease to the contrary to any of its real of personal property insured under valid and coilectible insurance, policies to the e tvnt of the collectible recovery under with Insurance, ARTICLE t - t NITY 1p. t T iaarat �aii r rC rrs ray«, sacalst to rrrr ss ssad defiled Landlord n # andiord's agents ft,orn sun against any and ail costs, p rases, liabilities, losses, da ar es, Suits, ac�so,s�rs. fir ratst� orit say D�3 or claims of any biles including attorney's fee's aass rted lay Or lana behalf of any t. au hcarir arising out of or in any way Connected with either (i) failure by Tenant Gra urn) any eatagreements, taarrris or conditions of this Lease required to be r€`ssrin by Tenant li failure by Tenant to cssrri Ey rata any applicable laws,, orders or requt ti nS of governmental authorities, or (iii) any a .,sd et, death or personal ins urY Of damage to or kiss or theft of praperty which shall occur oil of absent the Leased PrerinSeS which is not caused by landlord. 1€0,2 Tenant, its successors, as lis arrest s uasresrrtcars shall in r nify, defend, reimburse and hold harmless Landlord freers and against any and all °` Environmental es* arising rorn the pre< a or use of "Hazardous Maaterials' caused, permitted or suffered by Tenant's use or occupssacy of the teased promises or aarlsi in any manner who arer neat � rias ori l�t tarn trf, any " ri irsarerr e etal Requir z rats" pertatrain to the Leased predefts and the activities thereon, or the breach of any warrants or covenant or the ifulcouracy of any repmentation, f Tenant CiDntllkked in this Lease. inileperdwr* SqW* ­ VKGG ft, ull1=15, Pep 10 of 24 10,2,1 upiazardous t4storials" means any sutistarim-, ^, 'The presence nit which requires invests tions or Retrediabon under any federal, state or iocat statute, regulation, ordinance, order, action, po6cy or comrnon law; or b. WhiLh is or becomes defined as "hazardous waste', 'tuizardous substance", pollutant or contaminant under any federal, state Of local statute, regulation, rule or ordinance of, aruendments, thereto including, without jinatatern, the Comprehensive Environmental Response, Compensation and Liability Act ('CERCLA') (42 U,S�C, 4§ 9601 t and/or, the Resource Conservation and Recovery Act (42 ti. S,C. 6SO1 OtSerti.);ear c. Which is toxic, exfsiovve, corrosive, flammable, aifectous, radioactive, carcinogenic, mutagenic or otherwise hazardous and is or becornes requiated by any governmental authority or instrumentally of the United States, the State of Colorado or t1re county of the Siceng Center, or, ."The presence of which in, on or atx)ut file Leased Promises causes or threatens to cause a nutsence upon the Leased Preuldies or to adjacent properves or poses or threatens to pose 3 ha and to health or safety of perwrts on or about the Leased Premises; or e. The presice of which on adjacent properties coula constitute a trespass by'Tenarit; or f. Without limitation which contains gasoline, diesel fuel or other petroteurn hydrocArtions, 10,12 "Envltoteirionsai staquireirlmlift" means all applicable present and future statues, regulations, rules, ordinances, codes, license$, permits, orders, approvals and similar items of 311 qOverrimental authorities or Instrurrientalities of the United States, Colorado, the county of the Shopping Center and all applicablejudicial, achninutretive and regulatory decrees, Judgments or ordem relating to the Protection of human health or the erivironment. 10.23 "gosirriaomantal Dam"es" means all claims, judgments, darnages, losses, penalties, fines, liabilities, encumbrances, hens,'costs and expenses of whatever kind or, nature, contingent or otherwise, matured or un"tured, atile or unforeseeable, including without limitation, reasonable attorney's and consultants' fees, any of which are incurred at any time as a result oftenant's use oriccupancy of the Leased Premises or violation of any Environmental Requirement m, on or about the Leased Premises or any portion thereof, 10. 2.4 'The obligations of Tenant, its successors, assigns and guarantors in this paragraph shaO survive the expiration of terrinnation of this Lease, 10, 2.5 If Tenant shall become aware of or receive notice ot othercornoitriucation concerning assay actual, allegmi, suspected or threatened violation of Environmental ReQuiremeras or habitity for Erive roftrriental Damages in ctinnecoon with the Leased Premises or past or present activities of any person thereon, then , within ten (10) days of becoming aware of or the receipt of notice or other cotnmunication, Teriant shall deliver to Landlord a written description of sifffle, together with copies of any supporting documents. 1 LeAtatpin Tenant at or sublet the fireemises or any p prerrilesa without the prior vi Notwithstanding the atarement commissary space PrOvided tha this Lease, Tenant shall as. 1 common control with Tenant or without the consent of the Lan' more subletting of the Prernisi assignment or subletting witho Notwithstanding any aSsign" shall at all times remain (till) compliauce with all other items Neither this Lease nor arry inti wtmorit the written consent, of in the event Landlord ccins lncreai*,�AQ base Rens, and ill not assign or in any nuinner oransfer thilS, Lease or any estate or interest,, herein t thureof, or grant a kense, coricession or other right to 0 cupy any Portion of the tten consent of Landlord, swd consent shall not unreasonably be Withheld. uod, 'Tenant shaft have, the right to subiOt a portion Of 00 frulieltse defecated tO the Sub -Tenant has adequate insurance for its use of the Premise consistent With ave„ the, tight to assign this Lease to an entry controlled by. controlling or under o an entity which acquires all or substordially all of Vie assets of Tonants' business card, Consent by Landlord to ont,, or rnore assignments of this Lease or to one or shall not operate as a waiver, of, Landlord's rights under, this SeCtiOn. Any such Landlord's consent shall be deented wild and confer no rights upon a third party. or subletting, "Tenant and any guarantor of Tenant's obligavons under this Lease responsible and liable for the payment of the rental herein spelblited and for od conditions of this Lease. -at thereat shall be. assignable as to the interest of the Tenant by operation of law to an arw9ornent or subletting, Tenant agrees; that LanRen0 shall receive (1) all 1qO ill increases In Percentage tS resUfting from Wicrobse Raid by assignee trr - VKGG lam, 1Lyliles. page 11024 Ctr subtenant sig of the gent set ftarth helrerri, ndlo shall not, be entitled to receive any rent received by frorre any t tai of sts cCairllds� d rr above, ' _ tl 11 fly 1( this Lease be assigned or if the PremisesOf any part thereof be outlier or es cupied by anybody rather than Tenant, Lars tar'd ruin after default tai t` arit, call, the rent from the assign si�bt aait Car ccrfrarscY acid ally the net amount collected to the rent in re ed, but no fi suchoccupant m t subletting, Cbl art y tai li td shall be deemed 4 e�tt r9 of to assignee, Tenant hensCid, or constitute a release of Tenant from further performance by Tenant of the covenants on the part of Tenant herein contained, .. All discurraurits utilized by Tenant to evidence aany subletting or assignment for whicu Landlord's consent, has been requested strati be sLitaeCt to prior atifivad by Landlord or its attorrsey. Tenant aha M on demand the sung of (wive Hundred dollar ($500,00 ) t flier with �& of Landlord's rpascrnable and expenses, including reasonable attorney's fees incurred in determining whether or not to consent to any requested subletting or assignneent and for the review and approval of such doccurnentatiom a 'VAI: Lf` during the tern of this L , the Leased Prr shall be so 12.1 �_ rla�naa� by Elia Car a€ay tserr caeise, e��t as +' result of Tenant's ner21`srorit or ia'stetttlor3ai act Car Issicara, so as to radar the Lead Pic nY sp s untarsai�tabta for Tenant's daily a raatroi1ai use the rent shall be abated durih(l the tosae Lea ,t# f'rorrirses are ianteraantable err an arnaurrt equal to bw proportion thereof which the number of Vote t trefe o � eo dl area Cif the Leased Pr rnises renderedunteriantabte bears to the total Net table Area of the L se rarrrl s, acrd sr+ the C:varet cif such damage, Landlord shlall el whether° to repair' ttra i ea,, Area � or to cancel this Lias and shaEl notify Tenant in writing Cat its ei ion within sixty (60) days after o 6ysuch damage. Err the event Landlord el to repair the Leased premises, the work car repair shall in hail i carried e e without to assay delay but only to the extent tat insurance proceeds available. In the event 1_andlr _ elects not to repair the Leased Premises, the Lease shall dare d canceted as of �� date LandlordLandlord gives notice to Tenant as ro above. 1f d ndkird el s not to r°efaarr theLeased Premises, hall be obligated to pay Tenant one tiff nth (1/15} of One Land aaky Pryp Thousand ions ($125,000,00) nines the number of years left on the Lease, to include the tivit Five-year Options (i.e. ,f iand3ord elected to cancel the Leas two yeaar kntO the f srst option time period, Tenant oCrld be entitled to receive one Hundred Twenty Five Thousand Dollars ($125,000,00) divided by fifteen (,S) times eight (a)). Such damage shall not extend the Lease Tlfr . Tenant SW riot ba entitled to any damages by reason of any inconvenience or IOSS sustained by Tenant as a result of the Leased Premises or any portion thereof being unteriantable while the Leased Premises are being repa%rrrsd or in the event Landlord elects to cancel the Lease as provided above, Each of the following events shall ctansbtute a default ora breach of this Lease by aj� It Isloget Nils to poy Lar4ford any ease Pent or percei Rent when due hereuryter� .t "I'll 1_uLtftnejbsd anv Additional Rent within the Period speolifted in Article III; o. 1f Tenant vacates or abaridorr; the Leased Ps -raises; d, if Tenant files a petition in bankruptCy or insolvency or for reorganizatiOn dander any trankruptcy acts voluntarily takes advancirge of any such act by answer or otherwise, makes and assignment for the benefit o creditor's or o insolvent or unable t€a meet it obligations as they become dare, a, It involuntary proceedings under and bankruptcy or insolverlCy act shall be instituted against Tenant or if a receiver of trustee shall be appointed for all or substaPtially a" of the property of Tenant and such tarn ings shall not be dismissed Car trap receivership o trusteestitp vacated ithi,n thirty (30) days after notice thereof from Landlord to Tentrnt, p If Tenant falls to perform or Iy With any other terra or condition of this tease and such nonperformance shall continue for a period of thirty i fl days after notice therr„eef from Landlord to Tenant, 13 �` in the event of any default or breach hereunder, in addition to any other 691"t or rernedy available to Landlord, either at law or xi equity, Landlord may (mit need not) exercise any one or more Of the following rights; have the right, but not the obligilib0n, to Store such property in a public warehouse or at a place Sitiected by Landlord at, the risk and expense of Tenant. lt. Landlord may terminate this Lease. by giving written notice of termination to Tenant, Without such notice, Landlord's re-entering and/or relating of the Leased premises will not, ter nate the Lease. On termination, Landlord my recover from Tenant all damages proximately resulting from the breach, including the c Of recovering the LeAsed Premises and the vidueor the balance of the Lease over the reasonable rental value Of the Leased Premises for the remainder of the Lease Term, nunch sum 5haH be immediately due Landlord frorn Tenant. c, Landlord may on behalf of Tenant, reset the Leased Premises or any part thereof for any term without being deemed to have terminated this Lease at such rent and on yu& , terms as it may choose, Landlord may make alterations and repairs to the Leased Premises, In addition to Tenant's continumll ha ti to Landlord for Tenant's citilgiations under this Lease, 'Tenant shall be liable for sit expenses of the reletting (including brokerage and kiqw fees), for any alterations and repairs rade, and for the difference between rent received by Landlord underan't Sa p nod urn 0 r this ea new least Agreement and the rent installments rnat are due for the me e a , L se, d, Landlord may make any paymnt or perform any act cr behaif of Tenant n acSery to cu such Dignuit by Tenant and make all necessary payments in connection therewith, including without limitation the payment of reasonable attorney's fees, costs and charges of or in connection with any legal PrOctedin9s which may have been commended, Tenant shall Pay to Landtord, as Additional Rent upon dernand, any arnoont so pwd by Landlord together with it thereon at the lesser of I 8% per arinum or the Nhest rate then allowed by law frorri the date mid payment was due until paid by Tenant, 'Tire payment of such interest, shoti not excuse or cure any Default by Tenant under this Lease. e, All costs and expenses alcurred by Landlord in connection with collecting any arriounts and damages owning by Tenant pursu8ttt to the provisions of this Lease or to enforce any provision of this Lease including Without limitation reasonable attorney's fees and Landlord's internal personnel COSM, whether or not any action is commenced by Landlord shall be paid by Tenant to Landlord upoin demand, It Landlord without fault is at any time made a party to any fitigatiM instituted by or against Tenant, Tenant shall reirriburse to Landlord and shall indemnify and hold Landlord harmless against all costs and expenses, im:ludrng but neat limited to att0rheya fees and Landlord's int mal personnel LOS% incurred by Lantilord in connection therewith, 133 VAakag=, Landlord and Tenant understand that notivithstanding certain provisions to the contrary contained herein, a trustee or debtor in possession tinder the Bankruptcy Code of the United the United States the "640kria puy Code-) may have, certain rights to assume or assign this Lease, Landlord and Tenant further understand that in any event Landlord Is entitled under the Bankruptcy Code to adequate assurances of future performance of the tertris, covenants and conditions tel this Lease, For purposes of any such asauraptton or assignment, the patties hereto agree that the term "Adetivate Assurance* shall include at least the following, a, In order to assure Landlord that the proposed assignee wolf have the rpsourtbs with which to pay all rent due hereunder, any proposed assignee must, have derwristrated to Landlord's satisfaction a net worth (as defined in accordance with getierally accepted accourthrit; principles tonsistently applied) at least as great as the not worth cif Tenant on the date this Leave became, effective increased by ten percent (10%) for each year from the effective date of the Lease through the, date of the proposed assignment, The financial condition and resources of Tenant were, a material indukement to Landlord in entering into this Lease, b. Any proposed assionee must have been engaged in the Permitted Use at least five (5) years prior to any such proposed assignment, c In entering into this Lease, Landlord considered extensively the Permitted Use and determined that the permitted Use would add substantially to Landlord's tenant balance and that if it were not for Tenant's agreement to timit its operations to the Permitted Use, Landlord would not have entered into this Lease, Landlord's overfill operation will be substantially impaired if the trustee in bankruptcy or any assignee of this Lease makes any use of the Leased Premises other than the Pertwitted Use. d. Any proposed assignee of this Lease must assurrie and agree to oa persnualty bound by the terms, provisions and covenants of this Lease, 13,4 QSj"jjXAJ1Qd1Q1d- In the eVeat Of OAY default by Landlord ("Lla"dW4 VWauW1), Tenant's exclusive remedy shall be to commence an action for damages, Prior to instituting any such action, Tenant shall advise Landlord by written notice specifying such Landlord Default with particularity and Landlord shall thereupon have thirty (30) days in which to cure any such Landlord Default, provided, however that if the nature of the Landlord Default is such that raore than thirty (30) days are required foir, its cure, Landlord shall not be In default if Landlord comn-wrices performance within said thirty. (30) days and thereafter difigently prosecutes the sarne to completion. Unless and until Landlord laft to go cure any Landlord Default after such written notice,riant shall not, have any Y /.71-1 q VKGG IM Page 13 d24 16A Landlord rese .rves e, Leased Premises superior in lien and the light to place, liens and encumbriiinCes Oil the effect to this Lease, This Lease and all rights of Tenant hereunder shall be subject and subordinate to any fiens and encumbrances now or hereafter imposed by Landlord Upon the Leased premises or the Shopping Ce"Iter Or OnY part thereof and Tenant agreeS to execute, acknowledge and deliver to LandlOrd, Upon demand, any and all Instrurivulls required by Landlord, Landlord's lender(s) to subordinate this Lease and all rights herein to airy Such lien or encurnbrzrrrce, in the event of at foreclosure of any mortgage on the Shopping Center or a deed In lieu thereof, Tenant shall attorn to and become the Tenant of the purchaser at the forettosarra sale or the grantee of such deed in lieu thereof, and shall recognize such party as the Landlord under this Lease. Aft T1CU'XVU-*$TOPPFL CeRTIFICATIES 17, t Tenant agrees that at any tirrie and from time rn trroa. during the term of this Lease, and within three (3) days after demand therefore by Landlord, to execute and deliver to Landlord or any mortgagee (existing or propoiazl), trustee, beneficiary or purchaser of the Shopping Center, a certificate in recordable form certifying that this Lease is in full force and offect, that the Lease is urionylibed or if modified, describing such modification, that there, are no defenses Of Offsets thersto or describing any such defenses or offsets as are claimed, the dates to which all rentals have been paid and any other matters reasonably requested by Landlord, 181A if the whole or any part of the LeaSed Prernises shall be taken for any pubkc or quasi-pudijC tie under the emse power of erninent dornain, then the term of this Lease shall cease as totMat portion Of tree L Leased Pris so taken, fron'l the date of, title vesting, and the rent shall be paid to that date with proportionate refund by Landlord to Tenant of suCh wt as many have been paid by Tenant in advance, If the portion of the Leased premises taken rs such that it prevents the practical use of the Leased Preouses for Tenant's purriosft, their Tenant shall have the right either (j) to terioinate. this Lease by giving written notice of such terrnnatorri to Landlord not later than thirty (30) days after taking, or (0) to olifitinue in possession Of the remainder of the Leased Premises, except that the rent "Vb?e nature, value and areas of the Leased Premises tak I _feduced jA proportion to th J 1_7 WK*Pgndw" s4aft -- VKW 'no, I(Ill Page 14 of 24 In the event of any taking or C of damages shaft tle the exci diminutitio in vaide to the Will value of any uAeXPirtd to hereafter tel in Tenant, In Landlord shall pay Tenant an Oollars ($125,000,00) times t cancel the Lease two YeOrs 41 TweritY Five "Th end D014liS M 2,0,1 Any notices, demands or other cc)mmunications to be given hereunder shall be given in writing and sent by (i) perwrial deOvery, (ij) overnight courier service., (jjj) rejecopy, or (iv) registered or certified mail, return receipt requested to the following address: ,If to landlord: Steve Hod9tion, Trustee 23030 Lake. Forest Dr 202 Laguna Hill CA 92653 Phone; 415-596-7,415 It to Tenant'. Andrew Douglas, President and Noah StePhens, SecretarY VKGG, Inc, 4980 Kipling St, Unit A- 12 Wheat Ridtle, CO 80033 or at such address as either WY may from tirrie to time designate in writing, Each such notice shall br* deer ned to have been given at tne brae rt shall be delivered, sent via telecopy or overnight courier service. or if mailed, at the tune itch ll be deposited in the United Statil frinil in the manner prescribed herein. Nothing Contained herein shall be construed personal service of any notice. in the rnarnutr prescribed by law for personal service Of a surcrtions or other legal process, Poo 14 w t S - VKGG dam; tWodlh;,Papl5slet r GES Landlord s right y tics to chugs the size, area or dire ra ion of the nopprn rater, change trio size or tion of points of access or parking grad crit s rite to otta t s s LandlCentel or any adjacent Of m y wrii desirable sri Connection i�rsih the nr develoPment Of the Shoppinq sarin ap t effect of altering Tenant'stPro or neighboring properties, Tenant Rckooa led . µ that Ceter , in Tenant's reasonable Rapt tiar w if ntlord changes the size, area or dimensions of the Shopfliri tr nnf rs rEtcriaay terminate theLease discretion, negatively no s the Tenant's based sis t use of the Premise,s One Handled time without penalty and Landlord sficid�3 ��ees the number of years equating t fifteenth � rads Option terms f if Tenant Paws Thousand Dollars f t ,,Tenant would ontled to receive erre elected to cane t the Lease, � y rs sato � first loo time period, Hundred Twenty Fiero Thousand Willits ($125,000,00) divided by fifteen (1 5) times el tit ftf, ARTICLE XXIII-SIGNS, FIXTURES' ` R10 OVA ,i �; Tenant to li rant woke or cause to p ct xray, u r ns, ddib s or lra r a rr e�l tial ho osn Center or hast it lir Coosa to � installed any e torior si res, r covering, exterior isr radii la mooing fe for , shad or awnings, wiaido coverings, radio or television antennae, loud speakers, socsrld lifters or sirellat devices or make any changes to tue storefront or exterior of the, SbotithrIg Cancer withoutand tthritcofortri in Landlord's or writtenapproval- All signs installed i etri right o okeiby Tenant $hal�then sign criteria res is with sign criteria established for the Shopping Center. andltrdras at such ti t as its necessary dire to a change in events such as Changes in the city sign ordinance or a redevelopment of tris Shopping Cenosr. ose Tenant a r sok fr oil r' signs it, rod condition and repair and o . w to is such signs isle during left n0UM fromtime tirne required by Landlord, Any installation of new signage requires the Tenant to obtain a pe"nit from the appropriate r..opriate city authority and the sesta llatioai must be done in accordance with city sign ordinances ARTICLE XXXV-1LANOLOAWS RESERVED R16"'tS 24,1 Without notice to Tenant and Mtr, Our, tnat illty to 'Ternint for danlage or injury to OrOPertY, Person or business and without giving in rise to a claims for evsotion or constructive e ictiort of `feaaant, disturbance of T r'iant's uss or possessioti or sattiff or abatement of rent, Landlord shall leave the right to: a, Change the rierne or stree, address of the l hcipiong Center. b, install and rivintaih signs on the exterior of the ShOpPing tenter, c. At reasonable tirrita, to decorate and to make at its own expense,repairs, alter amort , additions and any a ro nems, strcrtural or otherwise in or to then Leased Premises, the err adjacent encs r > tared stmt or airy acid during such O trans to fake into .arid thr'ou h the leased R a�ais s car build MM ifars - Vit as Inc, Alt a ,Pap 17 0174 other provisions contained between the parties hereto ,10 tl« Partnerrs, employees and a ants of Landlord ,Emla have absolutely no Penional liability with to Gray Provision of thisL se or away obligation or liability arising in Connection herewith. risstlettTenant 00 solely to theequity gra the Leased + to hCififdrigi t rat r r tl� t# tiol €€ remediesc Tenant asst to the event � t of a breach by the Landlord of any of it obligations.such exculpation ra oof liability shall be, absolute without, any excePtiOn whatsoever, 26.11 UqUQC._UCC9M. Tenant,, its princitans, employees and agents agree not to opPOse if' any rraanner applications for issuance of liquor licenses to any establishment located within the hopparal Center. 26-12 # �u ` Tenant agrees that Tenant,Tenant's ernPkiyees and agents or any other paw parosited by Tenant to occuthror enter the e s shall abide by the rules and regulations c.ont'sned in Exhibit Landlord rha3l have the right to arraerad, modify or change ilea rules and regulations provided that said arraeridments are applicable to and uniformly faired each temint of the hong "enter, `eaaartt actress to cora° Y with a#i such rules and regulations upon notice from Landlord thereof, A breach of any sucrM rule or regulation shall be deenled a default under this Lease and Landlord shaft haus all of the remedies set forth herein. ,13 M., . : The fact that some r visitil", of this Lease are lrt bold and lamer type Brat has no unpor4 and shall riot be construed as giving those provisions added weight, .1 r tenant shall be allowed to install window signs within and upon the exterior glass of the denused building as allowable under applicable govemmental rauctrority without Landlord's natter consent so long as such supe shall amain drvictly to the promatiou of Terlauf,s bull ss use within the premises arid shall not be "sive in nature. However, Landlord does retain the right to reparare tenant to remove such s€a rsta e show landlord deer" necessary in its style discretion, in the event of a conflict with Article 23.2 hareem foregoing, this paragraph shall supersede, Z6.15 Other than triose rterras specified hemi€wafter, Landlord shalt deliver the premises in was is" condition, f Landlord shall warrant that as of the tirne delivery of the Premises 80 plumbing, eledrical, mechanical and HVAC systems sh ail be iri good worming order, free of defects, The roof shalt be free of teaks at delivery of the pr muses to Tenant.nd #t sh reralnt ire tree �, the cost of which shall be included gra Additional beret and/or mating tenses and may to ll arta ed or expensed as set fortri gra Paragraph 4. herein f firer caangp "the prendses shall be gra compliance with appficable, rounicicall, county, and state envir rarrr rrtal egad fora ordaraances, des and requlattons� ti� 16 Tenant shall be allowed to combirie and recoro4ure the subject space,; to meet its business i . nts and other improvements per a orae,ulgto be attached as an Exhibit to thisLease sli cent to execution by the parties and subject to flraai atrprraval o ' Landlord, such a al not to be unreasonably withheld, Tenant rraay m such alt�nons at its own expense asset only use qualified or licensed contractors, o new demising partitions shalt extend beyond t niches below the existira oillrnp, shell contain no electrical, pian bin , or HVAC systems, and shall be Constructed and finished in a professional, workmanlike liner, In no event shell Tenant cause !teres for such Worts to be placed against Landlord's real property, nor any acts of the Pales lie o shalt d to create any relatfonshata than the r eationshita of Landlord and Tenant, 26,19€ � i t if it° is d wm a any time by Landlcard in its reasonablediscretion that eraant' usethe . s u n i ft}tans (such as but not limited airs or fve nin to emanate from traaratas Leases lasrr€rses ihata !siege offensive, distrarlain, or silsraafahve to neighboringTenant's within flee center, ierrarar. hit bave five t day's frfaava the time of Tenant's receipt of trarilord notice of such condition iia desist, r #ve rr socia radlk€ceras . Tenant's failure to desist, reserve or acre such condition(,) shall constitute a fault by anarat for avta§dh Landltard daay exercise, its rights under 'Article X111 •-Default' provisions of this Ledge. Squips M. VKGG lac iorrrzow Par 18 of 24 26,210 option to Extend Leaser If the Tenant has COMPlied with and Performed all the covenants, conditions and provisions of this Lease by the Tenant to be, observed and performed without any uncured defaults having curred dttrrrrt the 3ftitrdl Trvr ear tease of this Lease (thy "Initial 'T "`)F thea the T ant shall have theright t extend the term the f initial Lease f the xtrrraatltara of the thitiaal 'Terms for ar peri of five () additional years, upon the sairry terms and conditions s f in the Initial Term, except, s expressly difi� andr # herein, r�vsda*d that t the Tenant gives the Landlord written notice of such election to extend the term not less than ninety ( days prior to the expiration of the initial Term. tiow ^ver, under no circumstances shall the Tenant be required to exercise said option earlier than raaraety ( days Teaser tca the expiration of, the initial Term. to the isvent Of the exercise c)f said opt,#sacro, the Tenant nt shill pay rest to the Lsodlord, during the aw dita rs t five () tar tears (the "`Fwst Five -Year option "Term"), in the total amount tat Two r t tat tad r fiat d ffty vier and 94/100lot$ ,457.941. Stich rentshall be paid in advance, without dernand rad or rortrce in monthly installments on the tst daay of each month during the taint Five -Year option Terra, as ftilki s. 1f the Tenant has COMPlied with and performed all the coveriants, conditions, grad provisions f this Lease by the Tonant to be Observed and performed, wittiout any uncured d rlits having curved during the flse Five- year iv - y r option Term, theca the,rinisint shall have the d ht to extend the tamer Of rials tease for a second five ( year term (the "second Five-YeAr option Teras'), upon the same terms and conditions as are in the first five -Year option Term, except as expressly modified and provided herein, provided that the. Tran, gives the Landlord irrevocable written notice, of such election to extend the form sitar less them ninety ( ? days tarrtsr to than expiration of the First Five-year Option Term However, under no circumstances shall the Tenant be r irk eta exd id option earlier than ninety (0) days prior to the expiration of the First Five-year option "tens, to the event of the exercise of the W�ond Five-year Option Tenn, the Tenant Shall P8Y react to the t„ rrdf ard, during the additional five f 5i year Barr, (thaw oSec grad Five -Year Option " rrn') in the total amunt Of "undred Forlpf fiverad 141aie Hunillredeta nd t �� �, Such rent shall so loyitarle jra advance withont dernadd Of n0fice, in monthly hrostitllmeats on the VO day Of each month during the Second Five-year option Term as follows� Z .Zt Until this Lease's execart�ad tars behalf of ll p rti haver td, it shall be onstad ss gra r � Tenant to anter issue this Lease. e erect of this as is also metol rand t as the cd d to execution of certain -Terrul adtrdra of Lease* with the current tenant Of this ssat#f ct spaact, era event this Leasetd to is not fully executedby both the Landlord and T` nt assert delivered to the other care or f " .j, this Lease shall become scala, and void and of no further force and shall release all parties from all harthdr ligations, All deposits, if any, shall tw. returned forthwith to the Tenant, 26,22 r l td ",m r� t and Tenant age to azar ftdk0VirnQ t4sararldal is natives to execute this lease, Tenant and Landlord that the following financial considerations are revoked and smrr*W tely due and payable in the event of default or not Completing the fall term of the lease., Landlord will forgive unpaid 2014 CAM charges of aapproxir" , tawiy 30(I(Loo h, 1wandtatrd will forgive T martortion of n 12 HVAC. upgrade , C, Landlord will contribute 1i ,£T t"00 for Tenant lrrtprove rats to a4�'tai. d. Cancellation of Lease for recast - t 2 upon execution of this leas, and return of security deposit fat"tatry 60 days of the execution of this Lease, if Tenant descovers any physical conditions of the Premise e. which, in Tenant's unfettered discretion, make leasing the predose cost prohibitive, their Tenant. shalt A ­. M, —VKGGdrys 1WI1201, Pap of 24 Ns # > s " ,., r� BY te$. go n y� is c .. d , A TE JTSu President Ing s - VKGG ft jodirXiS, Pap 20 of 14 SITE PLAN (N,ot to scale, For identifiraboin purtxsesordy. fatts d Kipling 500£ Bus tit Lot 1 2"Pilin Replat 1(st I lot W02 SU ` Owli i Range Quartet SEC SW 3°'115, pMe 2,1 of 24 �ndaiveosym Squale - VKGG Inc I W1,20 Is, Pace 22 at 74 Tenant shad not obstruct, or interfere with the rights of other tenants of the Shopping center or of persons having business in the Shopping Center or in any way irrlure or annoy such tenants or persons, Tenant shafl not couirnit any PCs or vieninit anything in or about the Shopping Center which shall or nilght sutoert Landlord to any liability or responsibility for upury to any person or property by reason of any business or operation twNing carried on in or about the Shopping Center for any other reason, subject to the Terms of this Lease Tenant shall not use the Prernises for lodging, sleeping or for any chnarral or illegal purposes or for any clot se; that will damage the Shopping Center or the reisutation thereof for any purposes other their those specified in the Lease in the Landtord's reasonable judqrnent, (LarivasiOng, soliciting and pecidling in the Suopping Center are prohibited, and Tenant shall cooperate to lNI"Nent such ate vibes Tenant shall not bring or keel) within the prernises any bicycle or other motor vehicle. Tenant shall not place or use fitendritible, CombustiMe, explosive or hazardous fluid, chemical, devices, Suestances or materwIs in or about the Premises without the prior written consent of Landlord ever and above its initial use and leased Purpose Of the Prem'Ws, Tenant shoO comply with the statues, ordinances, rules, orders, regulations and requirements imposed ray governmental or quasi -governmental authorities in connection outh fire and public safety and fire prevention and shall not commit any act or permit any object, to be, brought or kept in tire Shopping Center which shafi result in a change of rating of any portion of the Shopping Center by the insurance Services offloe or siffidar person or entity subject to the Terms of this Lease- Tenant shall not COMMIt 8nY act Or Permit any object to be brought or kept in the Premises which shall increase the rate, of fire losurance, on the Premises or on property located therew, subject to the Temo; of this Lease. Tenant shall not conduct in or about the Shoptimg Canter any auction, public or private, without the prior written approval of Landlord, Tenant shall out install or ul- in the Shopping Center any air condMorimij unit, engine, holler* generator, machinery, theIturg unit, stove, ventilator, radiator or any other similar apparatus without the express pnor written consent of Landlord, and then only as Landlord may reasonaNy direct, All office equipritent and any other device of any electrical or rriechadical nature shall be placed Dy Tenant in the Premises In settings reasonably approved by Landlord, so as to absorb or prevent vibration, noise or annoyance, Tenant shall not cause improper not aes, vibrations or odors within the Shopping Center. Tenant shall move all freight, supplies, furniture, fixitcres, and other personal property into, within and Out of only such outraficas as may be reasonably designated try Landlord, and such, movement, of sucti items shall he under the reasotwee ie supervision of Landlord, Landlord agrees freight, supplies and other equipment may be moven in through the front entry to Premise. Landlord reserves the hgtft W perrsdically inspect all such freight, supplies, furniture, fixtures 6nd other personal property to be brought into the, Premises and to exclude from the Shopping Center all such Aects which violate and of these rules and regulations of the provisions of the Lease, Tenant shall not move or install such objects in or about the Premises in such a fashion as to unreasonable obstruct the activities of the other tenants and all sucti rnowng shall be at the sole expense, risk and responsibility of the Tenant, Tenant, Tenant's ploys s, guests, vereturs or invittes shall not deposit any trash, refuse, agareftes or other suestare ws of any kind within or out of the Shoppmg Center except in refuse containers, Tenant shall exercise its best efforts to keep the sideeiNks, entrapses, pesstiqcm, courts, lobby antais, parking areas, vestibules, public corridors and haft in and about the Shopping Center (hereinafter 'Common Areas') clean and free from rubWsh. Tenant shall use the Commor, Areas curly as a rivans of ingre,,ss and egress and other designated purposes, and Tenant shall permit no loitering by any of Tenant's employees upon Common Areas or elsewhere within the Shopping Center, The Comirlon Areas and roof of the Shopping Center are not for, the use of the general public, and Landlord Shall in all cases retain the right to control or prevent accft*s thereto by all persons WheSe "asta in the reasonable judgment of the Landlord shalt be prejudicial to the Safety, character, reputation or ire terelits of the Shopping Center wit the exprians prior rotten consent of the Landlord, Maixicisliss aeive.. Rigel Inc, I at tyid5, Pap f 24 Landlord re _ o- yes the right, to exclude or expel from theheapptro f} Centel, ac"y perSOn with, rra the reasonable judgment of landlord, is intoxicated or under the influence of liquor or drugs or who shall In any manner act in violation of the rrules and regulations of the Shopping Center, Sufnect to the e ws rat this Lease, Landlord call have tate right to reasonably designate the a s or areas, in any, in which Tenant and "tenant's servants, emlepyeas, contractors, jobbers, agents, licenses, invitees, guests and visitors may paw vehicles, and Tenant Arid its servants, employees, contractors, tobber"sa agents, licenses, invtt , s, guests and visitors Basalt observe and carhply with all driving and parking signs and ruarkers within and about the Shopping Center, All parkmci rarxaps and any pedestrian walkways, plazas or other public areas ftarming 8 part of the Premises or the land upon whlch the Shopping Center is situated shall be, lander the wade and abs6ute control of, Landlord who shall have the right to reasonably riptulate and control those areas, Tenant shall our mark, print, drill into, cut, string wires within or an any way deface, any part of the Shopping Center wittadwrt the express prior written approval of Landlord. upon renvival of any wall decorations or installations or otter coverings by Tenant, any damage to died watts Or, fltsars shalt be repaired by Tenant at Tenant's sole crest and expense. Without limitation uprin any of the provisions of the Lease, "Eeriest stwall rifer all contractors` representatives, tives, instaaltaation technicians and other rnifcharrics, artisans and laborers rendering any service in connection with the repair or permanent improvements vements of the Premises to Landlord for Landlord's approval before performance of arwy Stich seicer ThiS Paragraph shall apply to all work perftar red of any such service, f"his Paragraph shall apply tri all work performed in the Frear` ses including without firrift0tiOn, installattofr Of telephones, microwave uquiptTrent, saltine dishes or antennae, electrical devices and a chMeInts and installments of any nature affecting OOOrS, watts ceilings, the roof, f', woradasorka trim, windows, ceilings, e trafin7erit: ur any lather portion of the Shopping ertter. Plans and specifications for such work, prepared at Tenant's solo expense, shall be suprnitted to Landlord and shat( be subject to Landlord's express prior written approval Bra each rnstbece before the cornmericerrient of work. All installations, alterations and additions strait be. constructed by Tenant in a good and workmanlike manner and only good grades of orateoWs shall be used In connection therewith, The means by which corraMun€crat ren and shnllar warn are to be introduced to the Premises and the location Of telephones, satellites and other ofte eeltastament affixed to the Premises shall be subject to the express prior written approval of Landlord.. No signs, rrwrairatts, showaaa" sa advertising devices tar. tattler, projections or obstructions shall be, attached to the. catitside walls of the Shopping Center or attached or placed uptin any Common Areas without the exit res pricer written consent nt of Landlord, No Winds, drapes of other window coverings shalt to installed in tree Prem s . ° wwitonot pn written cone rat ref Laai dkird. ktra sign, pictur , aad rtise rat, window display or other public display or notice spall be Inscribed, exhibsted, pakited or axed by 1 enant open Or within any part of the Premises iia short a fashion an to be seen from the outside of the Premises without the express prior, written consent of the Landlord. In the event of the violation of any of the foregoing by Tenant, Landlord may within fifteen (1,S) daysof written notice to Tenant during which period Tenant may repair same, remove the articles constituting the violation without any liability unless a toss other than said removal arises from Larldlord's willful Or netildfaht acts ° omissions, and tenant shall reirriburse Landlord for the reasonable expeorms incurred in such removal uporl demand and upon Submission Of afapiicsta#e bills as aadatationai rent cinder the Leasee. Interior signs can doom shall he subject to the express prior written approval of La Milord. Tenant shall not use tete narrip of the Landlord in its business narne, tr•adetraiarks signs, aCdvertsement+, descriptive material, letter he , insignia or any other similar item without Landlord's express prior Written aPprovai, Employees of Landlord shall not receive or carry rne* " ries for or to t"eraant or any anther person nor contact with or render fte, or paid services to Tenant or Tenant servants, employees, contractors, jobbers, agents, inviefes, t3 nes, guests orvWtors. Tenant shall chango no tOrks withratit tate express prior written approval of Landlord, Tenant shall, Upon terrwaanaticvi of its tenancy, provide, Landlord with the coordinations to all cornionation larks on sol s, f burets and vaults and deliver to Landl ,d all keys to the PrP Landlord and all inter#rar dtaoa"si s,abinets and other key -controlled mechanisms therein, whether or not such keys were, furnished by Larcflord, Tenant shall pay to itandlord the reasonable cost of repiactrap the same or changing the loth opened by such lost key if landlord Streif reirisinably deem it necessary to rnake such as charge, Landlord shall not be responsible for arid Tenant herepy indei n&ies and holds Landlord harmless from any liability in connection with the loss, theft, misappropriation or, other disappearance of himitur'e, furnishings, fixtures, machinery, equipment, eye jewelry or other items oaf Pau n sal Arra . ny f tlatr P em or other parts of tete ShOPPing Center regardless of whether tate Premises are locked at the Barrie of such loss unless the Suss arises from Landlord's Willful negligent acts or onisleoras. '/2"'—) j€ S - VKGG I mmrAA PamUdA Or Current Owner/Occupant CATHY ROSCIO 383 INVERNESS PKWY. SUITE 285 ENGLEWOOD, CO 80112 Regarding Permit: 201400193; Install 20 sf fascia sign using existing electrical. 4980 Kipling ST STE Al, Wheat Ridge, CO 80033-6733 Our Records indicate that the above noted permit was issued on 02/20/14. Our last inspection related to that permit was on NONE, Because of the inactivity on this permit, it will become void as of 12/31/2015. Please contact this office within one week from the date of this letter to update us on the status of this permit, or call for a final inspection on the property. You may call 303-234-5933 or request inspections online at www.ci.wheatridge.co.us. Information needed are permit number, property address, type of inspection and date to be inspected. If you do not contact this office, and wish to resume work at a later date, you will be required to submit a new permit application, drawings with appropriate code edition information and pay applicable fees. Incomplete or inactive permits may be reported to agencies such as Jefferson County Assessor, title companies, etc., and could affect future transactions related to this property. Thank you for your cooperation concerning this matter. If we can answer any questions, please don't hesitate to contact us at 303-235-2855, option 7. Melissa Mackey Senior Permit Technician pity cad tit�� , COMMUNITY DEVELOPMENT tr,N tri its# Building Inspection Services Division �i 7504 W, 2e Ave., Wheat Ridge, CO 80033 Plan Review r*e. Office: 303-235-2355 * Fax: 303--237-5929 Inspection Line; 303-234-5933 Building r iAppliCation Mailing rens. (if different than property address) Address; ,. City, tate,' i Architect/Engineer E-maili, e. - Contractor: C_-, Contractors License M. Phone. 3 Contractor - td et Sub Contractors: Electrical: Plumbing: Mechanical. W.R. City License W.R. City License # Vita. City License # Other City Licensed Sub: Other City Lien Sub: City License ## City License Complete all information cin BOTH sides of this for 1111 111111111�� 111 * w • .st UPGRADENEW COMMERCIAL STRUCTURE ELECTRICAL SERVICE RESIDENTIALNEW STRUCTURE COMMERCIAL ROOFING COMMERCIALCOMMERCIAL ADDITION RESIDENTIAL ROOFING RESDENTIAL ADDITION WINDOW REPLACEMENT ACCESSORY STRUCTURE deck, • :sx , shed, deck, etc.) MECHANICAL SYSTEM/APPLIANCEREPAIR REPLACEMENT •LUMBING SYSTEM/APPLIAREPAIRREPLACMENT ELECTRICAL SYSTEM/APPLIANCE REPAIR or REPLACEMENT •: •. Sq. FUL F Btu's Gallons Amps Squares Other Cr"/'OL0F')1ADO ASBESTOS 1,1 E C T1 0 IN! S Limited Asbestos Inspection Report 4980 Kipling St Unit At 4, A13 Wheat Ridge, CO 80033 10/24/15 Prepared For., Noah Stephens Noah Stevens 4980 Kipling St Unit At 4 Wheat Ridge, 00 80033 303-882-2008 ELqa-h@vertkftchen,corp Prepared by: Colorado Asbestos Inspections 303 S Broadway, Unit 200-209 Denver, CO 80209 iu��Olmffl 303-246-4587 Table of Contents 1.1 Project Summary 1.2 Photo Log of ACM materials (if identified) Summary of Asbestos Samples Recommendations Section 3 MEN= Section 4 4.1 Asbestos Containing Materials (ACM 4.2 Suspect Asbestos Containing Materials 4.3 General Comments Conclusion WE= MIGMEM Section 1 1.1 Project Job Ila. 151021-1 Site Address: 4980 Kipling St Unit At 4, Ala Inspection Date. 10/21/15 Wheat Ridge, CO 80083 Inspector: Jim Durgee Approximate year. 33m CO Cert ##. 10040 Site Contact. yeah Stevens Laboratory: Reservoirs Environmental Client; !Noah Stephens NV 101838-0 Contact: !Noah Stephens Turnaround "Time. Rush Reason for Inspection: Investigative "Total Samples. 9 Affected Area; Unit A14 and adjacent wall of unit At 3 Inspection "Type:. Limited ACM AH RA/Reg 8 Project /dotes; 2 x 4 ceiling tiles, drywall, cove base and carpet glue Homogenous Areas to Work Scope Table Desc # Class/Il') Description (I3esc #) Functional apace/Locations QTY in Scope 1 CT 2 x 4 white ceiling the Ceiling tiles throughout units 1000 2 SMW White black, grey smooth texture, Interior walls throughout units 1800 drywall 3 CDW Composite drywall Joint compound areas- interior walls 300 4 CB r" cove base Cove base areas- both units 400 C(3 Yellow carpet glue Below carpet- both units 1500 1.2 Photo Log of ACM (if identifie Sample ID Desc # Sample Locations Condition Friable Result Yes/No CT 1-1 1 Unit A14 Large NE room Ceiling, NW corner G Yes None detected SMW 1-1 2 Unit A13 SW room S wall, W end G Yes None detected SMW 1-2 2 Unit Al SE room S wall, e end G Yes None detected SMW 1-3 2 Unit A14 Front entry N wall, middle G Yes None detected SMW 1-4 2 Unit A14 Large NE room N wall by exit door G Yes None detected SMW 1-5 2 Unit A14 Large NE room S wall, middle G Yes None detected CDVV 1-1 3 Unit A14 Large NE room SE corner of black G No None detected painted area CB 1-1 4 Unit At 4 Large NE room NW corner G No None detected CG 1-1 5 Unit A14 Large NE room SE corner by door G No None detected SD= Significantly Damaged, D= Damaged, G=Good, ND= None Dectected Section 2 listed in this report, please contact Colorado Asbestos Inspections for additional sampling. Colorado Asbestos Inspections was contracted by the client to perform a limited asbestos inspection at the previously referenced address. This asbestos inspection was conducted by a Colorado State Certified Asbestos Building Inspector. The client is planning repair, remodel or demo activities of the inspected areas in the home/facility at the above acTivives over Me established trigger levels (32 sq feet or 50 linear feet or the equivalent to a 55 gallon drum, for residential progerties and 160 s2uare It, 260 linear feet for commercial properties). The purpose of this inspection was to identify and sample all suspect ACBM that may be disturbed during the course of the repair/renovation work. • This asbestos inspection was conducted according to the United States Environmental Protection Agency (EPA) procedures published in 40 Code of Federal Regulations (CFR) Part 763, Subpart E - Asbestos.containing Materials in Schools and Colorado Regulation 8. These inspection protocols specify requirements for the inspector (Section 763.85), laboratory (Section 763.87), and number of samples collected during an inspection (Section 763.86). This inspection involved identification and sampling of suspect ACBM in the areas to be repaired or renovated. Suspect ACBM includes nearly all building materials except glass, metal, wood and ceramic. Bulk samples • suspect ACBM were collected in general conformance with AHERA protocols as outlined in Colorado Regulation 8. Random samples of suspect building materials were collected throughout each homogeneous area qKWIPTUM I - 11 W I � - lf;#Ie n*ffJ*e('S U Asbestos Containing Materials (ACM) contain asbestos in concentrations greater than I percent, (> I % asbestos) as confirmed by an accredited laboratory. ACM is categorized as Non -friable or Friable asbestos. Non -friable asbestos is any material that cannot be crumbled, pulverized or reduced to a powder by hand pressure when dry. Friable asbestos can be crumbled, pulverized, or reduced to a powder by hand pressure when dry. SamUla(l) were submitted under chain of custod, light microscopy with dispersion staining techniques per EPA methodology (40 CFR 763, Subpart F). Microscopic visual estimation was used in obtaining the percentage of asbestos in bulk samples. The laboratory is accredited under the National Voluntary Laboratory Accreditation Program NVLAR See appendix A for sample and laboratory summary and appendix C for laboratory report and chain of custody documents. mmma= Suspect ACBM are building materials historically known to contain asbestos and therefore suspected to contain asbestos. The EPA and the Occupational Safety and Health Administration (OSHA) maintain comprehensive lists of suspect ACBM frequently encountered during inspections. This asbestos ins,?,ection was conducted in x� by members of the profession currently practicing under similar conditions in the same locale. The results, findings, conclusions and recommendations expressed in this report are based on conditions observed during our limited inspection of the areas in question. The information contained in this report is relevant to the date on which this survey was performed, and should not be relied upon to represent conditions at a later date. This report has been prepared on behalf of and exclusively for use by the client for specific application to the project as discussed. Contractors or consultants reviewing this report must draw their own conclusions regarding further investigation or remediation deemed necessary Colorado Asbestos Inspections does not warrant the work of regulatory .• laboratories or other third patties supplying information that may have been used in the preparation of this report. No warranty, express or implied is made. Colorado Asbestos Inspections has performed a limited asbestos inspection of the home previously referencem- ;PIAS 40, abatement contractor only if asbestos containing materials were identified, as determined by laboratory testing a in Sections 1 & 2 of this report. Any work associated with any asbestos containing materials must be performed in accordance with all State and Federal Regulations. Reasonable effort was made by Colorado Asbestos Inspections to locate and sample accessible suspect buildi materials. However, for any structure, the existence of unique or concealed asbestos containing materials is strong possibility. Colorado Asbestos Inspections only collected PLM bulk samples in the home repair/renovati areas at the direction of the client. This limited asbestos inspection report ia-ytot considered a comprehensil asbestos inspection report. James Durgee Colorado State Certified Building Inspector #16040 Colorado Asbestos Inspections, LLC. 303 S Broadway, Suite 200-209 Denver CO. 80209 Tel (303) 246 4587 i11to_Ca)co Asb,estejLcom i aa€uYa3iG t:k�roxr9ssaccYr G� �3vtic i da�a9akzAnd finiron"ma ASBESTOS O James D, Durgee £.rrliAvY km AUG,: ts'ldl.ii4 6.ann�=isa r..,i,n.nrQW a, Ch'.4,wix Airahra4' )CwG4O C tz�,Mion "'o 9„ Pat i9, and 6 haw, a".si50 3 r,; taw, sot" e,,Cok jdo m tta 8€ i,cx:. ss�t. i s 6pinw+ Building Inspector* fw�t& Wcomber 07, M4 vi,pim: 9aua Ytrtsar t!^, 20B Yik, nrr3R'ms 1 ,s, wNh fe,s?,x va dbsM'eda �vEmo-'.yy ...ruxn� Appendix 8: Laboratory Report and Chain of Custody Form Re,,e,voirs EnwonmeWat, Nuc. Effectwe January 11, 21325 Resew ms Environmgfti OA klanuaA, T:A0AWLablReservogs Ermronmenw OA Manua; doc REI LAF3RLM_qerVJ3ir -Vpppp"- q E vironmental, Inc. Wl 1" Laboratory Report: Project Project Description: Jim Durgee CoIGf4,,0o4sbestos Inspections 303 S. Broadway Suite 200-209 Denver CO 80209 MEMOZE= NA RES 334721-1 151021-1 4980 Kipling St. Unit A14, A13 Reservoirs—Environmental, Inc, is an analytical laboratory accredited for the analysis of Industrial Hygiene and Environmental matrices by the National Voluntary Laboratory Accreditation Program (NVLAP), Lab Code 101896-0 for Transmission Electron Microscopy (TEM) and Polarized Light Microscopy (PLM) analysis and the American Industrial Hygiene AssociationLab ID 101533 - Accreditation Cercate #480 for Phase Contrast Microscopy (PCM) analysis. This laboratory is currently proficient in both Proficiency Testing and PAT programs respectively, t — S — FMMMM , - T7777771-5—dTla I'll, trig sampies Tor asoestos content as per your request. the analysis has been completed in general accordance with the appropriate methodology as stated in the attached analysis table, The results have been submitted to your office. RES 334721-1 is the job number assigned to this study, This report is considered highly confidential and the sole property of the customer. Reservoirs Environmental, Inc. will not discuss any part of this study with personnel other than those of the client, The results described in this report only apply to the samples analyzed. M"1101101�1.WWMAN M4 i Sincerely, P: 303,1964 1986 F: 3014774275 5801 Logan StrCO, Sude 100 Denver, CO 802!6 r-- — -------- C) C) to C> U C> Ul) 0 Ul) C) till 0 0 c 0 0 0 co 0 00 0 co C) OD z 2 E c u 0 0 C 0. LU E < 0 0 C> to U 0 ') C> U'� U 0 U') C� ') Cz t = C t (0 — — — — — c LL E 0 < 0 ZU �J-j E -i2? 0 a a = (a 0 rm ........... co co 00 m CN all rs 0') U) m U') 0) Give CL > z 0 CL 0 0 0 < CL 0 0 M w W w < < cc < co < co < co < co uj C14 to t- co m 0 t, 0 z ujM C*4 M 0 M (JtY1000 0 Cecaw uj 00 o w w U.i w w CL c6 z 0 CL C: E 0. z a E zoma asCL .0 E c,, E C? rl 0 0- 0. ro rti 0 U) 4) c C 0 0 C C E E E w = = = 'W zm = F- X 0 0 U Q) Z 10 U) I 0 u spa I I > E z � w I cv 0 I m 0 0 C OOOOLO 0 0 — 000 000 000 0 0 E Z 0 iT 0 ujo E > 0 rte- 0 0 0 0 E0 z 2 C .0 ca miz < 0 E 0 fil E =—M—zzzzzzzzz ui w 44 00 0 co ko N 1 - to a. a> a CL — '0 0 E C 0) 0 E 0 0 0 E cm 0 c & 0 -0 N Oz LO 0 0 0 < Z: 0 CO — Z w o CL Ix U 0' uj 0' a ui ui ui 0 0- 0 o L E vo) 75 c 0 = 0) .0 z 0 < E z E cm E 'm 0 cL a. 00 0 m 0) — CL M c co c c CE 2 0 0 0 z ui A = = m cc u Q u a zi 12 C) m V) z > E z � w I cv 0 I m p�wim G+J 3 f lot A i a mF yyFFa ' :v Y n. a G+J 3 f lot i y mF yyFFa ' :v Y n. a �4tf P"iia �a.� t Yi3 4t x+ a,ba»5, ? x wmt tla�+ a,-�9� 6d,;y x{, Y" i ��iifeta #vis Vol 4 1 w � 9 w� is e W' e of m P Fe mu r s, „ tl Sa+ ,,... �CA+ 5a-tli 5, t%43'zA zit f s a3 a, IS. - aro i e s G+J Certificate of Completion Building Division 7500 W 29TH AVE WHEAT RIDGE CO 80033-8001 Stipulations: Tenant improvement - Remodel of an existing two stall non -ADA compliant restroom, to a new ADA compliant restroom - Unisex and addition of a collectiN n room with toilet. Includes addition of 6 ft high separation walls in lobby area. This certificate verifies that the building constructed and/or the use proposed of the building and/or premises, under the above permit number and on property described below, does comply with the Wheat Ridge Building Code and development standards of the zone district in which it is located and may be occupied. All other licensing requirements for the City must be met. Site Address: 4980 Kipling ST UNIT #A -r Parcel No: 39-153-14-010 Owner: ANN HURLEY HODGDON TRUST PO BOX 440 NOVATO CA 94948 Contractor: Kenneth Powell 4251 S NATCHES CT UNIT #A ENGLEWOOD CO 80110 For the Following Purpose: Commercial Remodel Cod -Editions NO change shall be made in the USE of 2012 ICC/2014 NEC this building without prior notice — 2006 ICC/2011 NEC and a new Certificate Of Completion — 2006 ICC/2905 NEC from the City of Wheat Ridge. Other ;:: 1110111111 1 IFICATE MUST BE POSTED BY FRONT DOOR OF COMMERCIAL OCCUPANCIES City of' Wheat j - rcige, COMMUNi'ry DIEVELOPMEW , # Date: P1811#10MIt # -17 4-0 LAk'- NMWZ= Building Permit Application M Address: City, State, Zip:- AO Contractor- , Phone: Contractor E-mail Address: Sub Contractors: Eieern col;),,J� Plumbing. Mechanical: # ity Uce'nse # W"Ofti Lic ense WR City License # #,ther City Licensed Sub, City License # Complete all information on BOTH sides of this form a +►s COMMERCIALNEW STRUCTURE ELECTRICAL SERVICE UPGRA, NEW RESIDENTIAL STRUCTURE COMMERCIALROOFING COMMERCIAL ADDITIONs ROOFING ACCESSORYRESDENTIAL ADDITION WINDOW REPLACEMENT COMMERCIAL .. , RESIDENTIAL .,: deck, MECHANICAL d } J5Ylk} REPAIR M gWk REPLACEMENT PLUMBING F4F SYSTEMIAPPLIANCE REPAIR i.. REPLACMENT ELECTRICAL A 6 5t M A REPAIR x Y (gyp. REPLACEMENT YII } matmials, to be used, i`r. rte', a "✓r }tc�. t e- t7�x 7e> 14 Sq. FULFg e> - Btu's Gallons & A I City of jq�Wh64,itRoge- CITE' OF WHEAT RIDGE BUILDING AND INSPECTION SERVICES DIVISION 7500 W 29th Ave Wheat Ridge, CO 80033-8001 p. 303,235.2855.f 303.237.8929 A copy of this form must be completed by each agency indicated on the Permit Submittal Checklist for the project type and be attached to the Building Permit Application at the time of submission. Applications presented for submission without a completed Proof of Submission form from a required agency will not be accepted or processed ti Date: Project Address: Name of Firm/Individual subrn ,,,I ting documents: 1, indicated below and do, . I I , duly authorized representative of the agency Wbelow, hereby acknowledge receipt of documents necessary indicated above. • Wheat Ridge Fire Protection • Arvada Fire Protection • Wheat Ridge Water District • Consolidated Mutual Water District • Valley Water District o Denver Water Agency Notes: • Wheat Ridge Sanitation Distri • Clear Creek Sanitation Distri • Fruitdale Sanitation District • Westridge Sanitation District • Other I +---It=-Z. (N Sia tPfW j �Yvet" mm '. yy fa O gq tat R1 ge Building Departmek Uj OZ I= t a i�-3 rz rye .sirs am UD "Q FFICIAL 0 LU valk*Qf Issuance of a W alkleeftwtatimi staff not boa pem# ft, f, cn Pitisions of the buffing code or of any Uy ordkmmi� Pwmbpmum to give authority to violate !0:4ma r c', air other ordinances of the t be vad CL r' iWW` - } Kid Build b �Ytt t . Signed,q plan Checker � w rId NEW FLOOR PLAN ... ....... .ww•°� ''V TIMI ' � � iMM� a I I t I ' W/Z' nM property address) Steve Hodgd a F Novato, CA 94948 CO 80033 Complete all information on BOTH sides of this form DocuSign Envelope ID: s k apply) (Check all that 6*w Sq. FULF _1 ,021 MMEMM ROOFING ROOFING MmEam I / Application Approvals Page I of I Main Nags lla,nt-ance Filters S0115 [I T Department JA — c6on Acfl . • Has )epartme nt Description Date Stav L Date Note * 122 COMM DEVEL-BUILDING Pending 180 IFRE Wheat Ridae Fire I tPendinal 109/081141 1 1 f htt 10/29/2014 John Schumacher From: Kenneth Johnstone Sent: Tuesday, August 19, 2014 9:11 AM To: Brad Umbarger, John Schumacher, Kenneth Johnstone; Kim Waggoner, Kirk Cadotte; Lauren Mikulak Melissa Mackey, Meredith Reckert, Michael Abruzzi; Wade Saner Subject: Marijuana Moratorium 23 rut Re processing UfMT applications for medical marijuana establishments, MIP tiiat we have been working with at 49thl5oth and Kipling. k working with Council on potential amendments to the code to consider providing additional restrictions on the locational or procedural requirements for receiving approval for a new establishment. MEME !�� Ken Johnstone, AICP 7500 W. 29th Avenue Wheat Ridge, Colorado 80033 Office Phone: 303-235-2844 Fax: 303-234-2824 M I II I OWN network to which your computer is connected. Thank you. City of Wh6atai IULA i6 City of wheat Ridge Municipal Building 7500 W. 29" Ave. Wheat Ridge, CO 80033-8001 P: 303235.2855 F: 301237.8929 September 10, 2014 Wayne D Anderson 7825 West Ontario Place Littleton, CO 80128 303-550-5678 wandersonaia@comcast.net IM Dear Mr. Anderson, The construction doctanents submitted ivere revietved for compliance to the 2012 edition ql'the International Residentia Code, the 201 I edition of the National E lectrica / Code, and Ci�y of lFheat Ridge pa lac ies. These discrepancies have been,tbund. 1) The 2-hour wall elements must be an assembly tested in accordance with ATM E 119. Please reference a listed (UL, Gypsum association, etc.) assembly on the plans Refer to sheet A2.2; (703, 2012 IBC). 2) The south cast exterior egress door opening requires be protected with a fire-rated assembly. This is based on fire area separation distance of 2 " -0" tirom lot line. Refer to sheets Al. 1, A2.1 & door schedule A7.1; (definition, table 705.8 & 705.8.2, 2012 IBC). 3) Provide energy compliance calculations to ensure that the mechanical system adhere to the energy code. Refer to sheets A2.1, E4, Sr M2; (chapters 4 &5, 2006 JECC). 4) Please provide roof plan detailing the location of the new mechanical equipment, added plumbing vents for this project and electrical service outlets required within 25' of mechanical equipment; (107.2, 2102 IBC). 5) How will the fume hoods, shown on plumbing plan, exhaust duct discharge to the exterior of the building Refer to sheet P-2; (501.3.1.1, 2012 IMC). 6) How will the potable water system be protected, from chemicals or other substances, at kitchen sinks? Refer to sheet P-2; (608.5, 2012 IPQ. 7) What method will be used to neutralize the chemicals from damaging the plumbing system at floor/trench drains? Refer to sheet P-2 & P-3; (803.2, 2012 IPQ. 8) The water heater architectural detail symbol references plan sheet PI 1.01 which is not included in the construction documents. Please revise. Refer to sheet P-2; (106.3.1, 2012 IPQ. www,ci.wheatridge.co.us 9) A panel board is neither shown on the electrical one-line nor on the power plan where lighting branch circuits terminate. Refer to sheets E2 & E3; (220.10, 2011 NEC). • MR DE SKI! UJIMEMMIJ, Please provide minimum 24"X36" reprised plans, three sets, with revisions highlighted, 4980 Kiphn,� Streelt. A I �Vlwat lZid,�"Ie, ("0 8003" September 5, 2►14 City of Wheat Ridge Building & Inspection Services Division 7500 W. ' Avenue Wheat Ridge, CO 80033 Dear Plans Examiner, I have compiled the following documents for your review: 1. Building Permit Application. An amendment to the application with all farther information required will be provided as soon as, possible. Further documentation that will be submitted includes water line construction plans, sprinkler plans, the general contractor's information, and all subcontractors" information. The contract value of all or to be performed is provided on the Building Permit Application. If this amount changes, document will be provided as soon as possible. 2. our copies ( three printed and one electronic) copies of Construction Plans with descriptions of or to be performed, If more detailed documentation is obtained from general and subcontractors, it will be provided as soon as possible. 3. A copy of the lease verifying the company's residency, Please do not hesitate to contact me with any questions regarding these documents or any aspect of the application process. My contact information is below. Th k you, O illiam Thomsen���� Ebbu, LL('.' 301-5184981 ebbu,6 ebbuxoin El d o » ractor Compan .. ' ¥ ± / Phone v. Name \� \�� .. ? e . Signature \{Authorized Agent \ . . \ \.. §.. \ ~/ . \§ \l Date . Signature of Authorized Agent f\«2f Date ? «* *2<y »+ # >? iT I 2II1 i» ?t«i « :y »+ «1 «<d* <<+ +? »# \l:iTf1» « Cit ' 0 r WJ= 0f tP4-99e CITY OF WHEAT RIDGE 13UILDING AND INSPECTION SERVICES DIVISION 7500 W 29th Ave Wheat Ridge, CO 80033-8001 p, 303.2351855,f 301237.8929 A M= �'roject Address: 4 0 47"1 M a duty authorized representative • the agency W •elow, hereby acknowledge receipt of documents necessary +r ect indicated above. • Wheat Ridge Sanitation Distri • Clear Creek Sanitation Distric • Fruit•ale Sanitation District • Westri•ge Sanitation District • Other I Agency Notes: Signature: Date: (Agency Representative) Fire Detection and Fire Alarm Systems: The fire alarm system shall annunciate at the panel and shall initiate occupant notification within the occupancy upon activation of the automatic fire detection, sprinkler water flow devices, or manual fire ala rm box. A minimum of two (2) sets of plans and supporting documentation, including but not limited to manufacturers model and listing information for equipment devices and materials to be installed will need to be submitted to the Division of Fire Prevention of review and comment prior to changes and installation. No work is to commence prior to be the approval of plans and permits being obtained. IFC 06907.1/ IFC 06907.1.2. A rough wiring and device location inspection will need to be conducted by the Arvada Life Safety Division. No work is to be concealed - until all rough inspections and any necessary corrections have been completed and re-inspected. IFC 06 106.2. Fire Extinguishers: Fire extinguishers shall be a minimum of a 4-A rated, 51b ABC dry chemical type unit, fully charged with current inspection tags. Please contact the Division of Fire Prevention for information on the number of units and mounting locations. lFC 06 906.3. Amended. Provide a nunimum of 1, each 4-A rated 10-lb dry chemical extinguisher durin construction. A separate permit will need to be obtained from the Life Safety Division for the installation of fire alarm systems, fire sprinkler systems and fire alarm, detection systems. Miscellaneous: Key boxes and locking FDC caps shall be provided on all buildings containing a sprinkler, standpipe or fire alarm system required by this code and shall contain all keys necessary to gain access and shall be maintained at all times. IFC 06 912.3.1. Amended. Date: 9/12/14 Reviewed By: _ Sparky Shriver, Address: 4980 Kipling Street. Unit/Suite Number: — A-5 Construction Type: – 111-B — Occupancy Classification: H-3 Square Feet: _5,159_ Sprinkler System: Yes: _X_ No: — Fire Alarm System: Yes: _X_ No: om Available Fire Flow: _ 4,149, MUKU114.1-11111 VISTA trect trontugc. Vimcf-Vininvult i 11 it ff signagc on tue Fear 06505.1. Exits and Locking Devices: Each door in a means of egress from a Group H occupancy shall not be provided with a lock or latch unless it is panic hardware or fire exit hardware. IF 06 1008.1.9. When panic hardware is installed, no additional locks or latches may be installed. lFC 06 1008.1,9. Means of egress doors shall be readily distinguishable from adjacent construction and finishes, such that the exit doors are easily recognizable as doors during and after construction. Mirrors or similar reflecting materials shall not be used on means of egress doors. Means of egress doors shall not be concealed by curtains, drapes, decorations or similar materials. Exit Illumination: The means of egress, including the exit discharge shall be illuminated at all times that the building or space served by the means of egress is occupied. In the event of a power failure, battery pack emergency egress lighting units shall be installed. IFC 06 1006.3. Emergency egress lighting shall be subject to field inspection. Additional units may be required if emergency egress illumination appears inadequate. IFC 06 1006.3. Provide additional emergency lighting in the extraction area Exits and exit access doors shall be marked by approved exit signs that are readily visible from any direction of egress travel. Exit signs shall be subject to field inspection. Additional exit signs may be required if the exit access or doors are not clearly identified. IFC 06 1411.1. Exit signs shall be illuminated at all times. To ensure that continued illumination for a duration of ninety (90) minutes in case of primary power loss, the sign illumination shall be connected to an ernergency power system powered from storage batteries, unit equipment or an onsite generator. IFC 06 101.1.1. The owner or occupant shall verify that sufficient electrical receptacles are provided as extension cords are not permitted, nor shall flexible cords pass through walls, ceilings or doorways. IFC 06 605.5. Fire Protection Systems: An automatic sprinkler system shall be installed in Group H occupancies, IFC 06 903.2.4.1. Buildings equipped with a sprinkler system installed in accordance with section 903 or 904 shall have a fire hydrant within 150 feet of the fire department connection. IFC 06 507.5.3. Amended. A minimum of two (2) sets of plans will need to be submitted for review and comment by the Life Safety Division. All work is to be performed by a State of Colorado licensed sprinkler contractor. No work is to commence without approval of plans and permits being obtained. lFC 06 901.4. When automatic sprinkler systems are required within a building that serves more than one tenant space, the main control valves shall be located within an approved room that is accessible directly from the building exterior. The door to said room shall be not less than three (3) feet in width by six (6) feet eight (8) inches in height. The door to said room shall be identified "Fire Control Room". IF 06 903.1.2. Amended. Fire department hose connections for a sprinkler system shall be located within one hundred fifty (150) feet of afire hydrant. Hose connections shall be located aminimurn height of three (3) feet and a maximum of four (4) feet above the finished grade. IFC 06 903.3.7.1. Group H Occupancy corridors shall be fire-resistance with a minimum rating of one (1) hour. IFC 06 Table 1017.1. Identification of rooms containing service items such as "Electrical", "Fire Control Room" etc. as determined by the Fire Marshal shall be labeled with approved signage in one inch letters and permanently affixed to the door. IFC 06 1 The fire code official is authorized to require warning signs for the purpose of identifying the hazards of storing or using flammable liquids. Signage for identification and warning such as for the iiiherent hazard of flammable liquids or smoking shall be provided in accordance with the fire code. IFC 06 34015. Compressed gas systems shall meet the requirements of Chapter 30 of the 06 IFC, The maximum allowable storage of flammable and or combustible liquids shall meet the requirements of Chapter 34 of the 06 IFC. Approved storage cabinets shall be provided. These comments shall remain with the approved plans and posted pennit card at the construction site. Contact Deputy Fire Marshal Sparky Shriver at 303-403-0477 Monday through Friday. MEM= Any code requirements arising from construction will be addressed. Twenty four (24) hours notice is required for all inspections and tests. �r .. � � &g #4ttrt tf ERgieta t g Sae t P t Mailing Address: (if different than property address Address; C: it , State, Z ry ArchitectAngineer E-mail.* e Property Ow ner (please print): Property Owner Email IN Mooj�� (if different than address) A r a : ' 1 1 1 e } 4 x Buil ding Division Valuation. eg S C i Y 2 9 0 y y b UPI O n x e S O tto 4 i y y b UPI HH x e O tto 4 i b UPI HH x O tto 4 i b 0 \� _ ) \ t ƒ / {r ;mvm��E \ �) $ @) u �2 \ \\ { ) ( «7 \# § \ \ /¢ /k \f( ww EE §\$)jf ƒwk& &MZ.a. « ) \ t ƒ / {r ;mvm��E ELECTRICAL GENERAL NOTES - APPLICABLE TO ALL ELECTR SHEETS •,7 " h r. "'7 Y 'i hit 7/ 1 al. «'M! 1' •.., ,p 71 1 F "F ' '1' II 1 1'.• : M 7 +v 'i 7 'r i 'h]- ,• 1 '1 '1 './ •• / 'h0. t• F :Y 10. t 7• •7/ J' :110. 17 V `:.1 I '/ :1 r1' 7' -, • .'!]I f 'h' r1. 1 M0. 1 '13 4 71 17 7 t I17 I w ' F '1'1' 1 1 1 1 1- '.7'1 ali. i.. t]I V •' 7 1'• ] ♦ • 1` 3 •_CF• 1 r 1 �• r 1 71 . r ' .7 1 ri. , a 7' 1 •'Y U '1 , '. .«F0.\ •• YT IF hl a ] h 4 • «a. • a• a a1 4 h 1 7 3 • 1 COD ill. ALL E h "r Ir LUGS SHALL BE RAT F OR A MINIMUM OF DE GREES CELS i / 1'7• k l 7 1' •' 7 h '171 a a .•. 1." >, ': Y• « ':7t 717':. ,. Y••. 'i7 + 71 1 ah 71 Y71. �. 3 1 7 # ivil :7 4 ha'. h v v•7 .v1 7 :. r h �' a 1 1 '. ]' 1 YI ' 1 7 M. ' 1 '.7 " 1 31 r • '1 :• i '1� h1P ' �1 'll r'4 ti N i � 1 • h a, i Y i' h I h, .v ' 7/ t' i 1 r F .' h' 1'177 - W' C •' i N 1'11:I r "•' '7 t' 4 J- 1 •nv 71 I - 1"A 'Y4 •7 •.. 71 T n "4 1 !1 KIIIIIK 41 7' v 'i V !171 h11'4 'eP y'I ra T r1 •' 7 '1.. r•' N 'I :C 1 ♦• 1 a 10. 1 7 A / >• 10. 1 ]' Y/ ]'w 1''1 '.]I '1 ►111 1' 1 1 ]I • h4 1 1�" r h '1 i' « '1' 1' t 'i'. i h •1 •1.• Mt I7 F • r ] 1 r Yr/ 1 rr4 ':. •a :a' t 1 'h0. u Y N 1 t •« 71 h '�71 1 h ''117 '] Y h 1 :'1 10. 4 i � F I M0. fi7' 1:' :! 1 � •.• 1 Y • :t h1 7 w : hi . ".3 1' h•' 1' r1.171 "1 V 1'' 1'J �'� 131: ''1]i •• ] 1 N• 1 1 ' 1 ►1 1 1' 41 t' x1'60. 171 t • .! 7 1 r 1 t•a7 r u r•,i] ,1 1177 ] 4 1 i' t 1' 1' ] '1 Y6 1 • v 7 .` '. 1' r 1 •.,.• 1. 771 7• 1 I n - • ". 4 '7 11'0. 1 ] h77/ � i i' x 1 1 'F F."h '' 11'0. J a h77/ 1' 1 7• 1. -0 1' 1'/ 1 1: : 7ai7•w w 7i 1 ► ':71' ]. 1 ] •;, 1 r r' '1 771 ]' 'F FI'r ' vI i Y 1 71 .731 71 7 '1 Fh 1�' h1 / 1 4140. 1' r1 • : •1 r :':17 7 r r 7 1, 1 -1 Yn7. 4 .1 u•rl 4 h• 7 6 1 . '1 r ;171 :.. •� « • 1I" ]':7 1 FFt ti h •i17 h1 r M" 6 1 r4' - t 1 4. ''.1] i7 'h • ILL- _ it - alb '; 4 0. 1' •7 1, i - h! 1' 'i U f�• '1' • , «Ii ✓1 '.'. 1, 7 7 4 T • I h•i 7 ?a 1 1• «71''� 1 h4; 1 / 1 r r r1. ' ►T; '�: -• 1 i.• v7 4Y « ''7 •' 1 V' 1 hi '7'r 7. 7 « 't '1 / «11 Y 1' 7 '.7 1 7 7 '.7 1 I I ]1• �• . h •' • • 1 IY "1 ] "/ 71 7 :'1.'J 114' 1':'d 1 1 • 71 «.' « ' ca-w .y. ,t a r• it :a 1 'a....« 1 ril '': a •. 1 ':7 4• h ,:.4..11 ... r ',,. ., ,. «I J !. 57' Y 1 'bil «' h 1]'w '1 r I'171 1 •" 1 ', 1' ! •� '' ]. t'• ,• «]. .7 ' 1 .171 17° «4 111' 111' FI !, • :4 F •:" M •!1 «• • • I'i ' it 0.v4 « 1' '.0.v• 6' •1' a ] ', ;' « -F '''1 al N1911' 10.vn '� 11 « ' r • - 17:n Wheat Ridge Building-Dept. Date: - Plan checker ,p Y IC J� c , a " Wh11 jt RWllge B- ,, D, , .;-ent RECORD DOCUMENTS: ELECIRICAL CONTRACTOR SHALL h RECORDS OF ALL DEIIIIIATIONS IN WORK AS INWALLED FROM WORK SPECIFIED ON THE DRANIMS OR IN THE SPECWA71M AND IDDM ORIGIN OF CHANGE 2. 1 A COMPLETE SET OF RECORD DOCUMENT PRINTS IN CUSFIDDY DURIN ENTIRE BRIO OF ODINSIRUCTION AT THE CONSTRUCTION STIE ON COMPLETION OF THE PROIJECI T1111) COMPLETE SETS OF MAWD-UP PRINTS WNW THESE DEVIRIONS SHALL BE DELIVERED TO GENERAL C ONTRACTOR AND AR CHTEECT / EIMM . TH COWRACT WILL HOT CONSIDERED COMPLETED UNTIL l RECORD 1'' h HAVE BEEN RECEIVED 1 REVIENED BY THE ENG 3 7 '1 r4 4' F 1 /• A 1 h !4 0. 4• 71 i 2 Y v.F Kil a L. 1 1111:0 7 1 ]i '1'� 1 / • 1. w 6 1 r "'i ❑ "11• 1 ••/ 1 1 6 .171 •/ 1 1. ` rw 4b41 « 7, ':7 4 '. '�7 r a 7•a1 1 4: Y v t '. 1/, '1T '0. 1 «I. ] •1 7 'rl 'x.77' 4' '.•. 1. 1Ir :171 4 i' 1, 41 « �,0. Y0.} ] " ':71 7 1' W- 1 1 !7' ':1 • 1', , , _' , '171 N "4 "7' /•,• 1 /, 1 , •,• •1 3 K kil Z I I •, •rg BUI 0 r 4E - - T ATE Val" of permit: Of specifludgM and computations sh*'Adbleap aporova °oyviolalente my of the prowww ottlub, ,,yr 'namoa, P"Mk piesurning udtari, ,!. ',a„ 'drsofOn Buildinticoch 0111 in 'N 111d WARRANTY 1. PROVE COMPLETE WARRANTY INFORMATION FOR EACH ITEM. WHICH SHALL INCLUDE NAM OF PRODUCT OR EQUIPMENT: DATE OF BEGINNING OF WARRANTY OR BOND; DURATION OF WARRANTY OR BOND; AND NAMES, ADDRESSES„ AND TELEPHONE NUMBERS OF MANIFACTURING /SERVICING PERSONNEL AS WELL AS PROCEDURES FOR FLING A CLAIM AND OBTAINING WARRANTY SERVICES. 2. THE CONTRACTOR SHALL WARRANT ALL MATERIALS. WgOOAA OW AND THE SUCCESSFUL OPERATION OF ALL EQUIVENT AND APPARATUS INSTALLED FOR A PERK OF ONE (1) YEAR FROM THE DATE OF FINAL ACCEPTANCE OF THE ENTIRE WORK AS IDENIIIFIED IN THE G04RAL COlINTIONS. ELECTRICAL SYMBOLS •, 4' t v :� ! }Ii. 7 1 r4 1' C v 1 •. 7•r., :']`I ', i'1 7 3 r4 ,.• '17' !1 f al+ i I - 1 •.: �.] h•. :1: 1 n �.1 1'� h '.0. '.h 7.l ':.77' v • v.1' 1.1 V POWER SYMBOLS , 4 '.7 P 1] 31 1 v' r''. 31 r '7 LIGHTING SYMBOLS ] 7 1'. "M0. M : P 1 'r0. •1 1 F0. / 7 •r ALARM and MISCELLANEOUS SYMBOLS 1 "F0. ! rr 0.\`1 . 1'0. '1 ] 3 '1 : '1 t' ONE LINE DIAGRAM SYMBOLS • l] 1 -} '. '�1 7 't ai' h al, ►1' �/. i � ':. F hhi' •, / • • F 1V "'« JUNCTION BOX; CEILING MOUNTED t 1', �h1:• i 11 •' J' 1 h•' w J tIF ': :, Fl�;l h,, ,• L1.7 4.: J 3'+ 'rt UY FIRE HORN WITH STROBE LIGHT PANEL BOARD x w « 10 JUNCTION BOX; WALL MOUNTED it / • i•1 . '., ]1 t t I0. 7 44 T. 71 '1 ® 7r' '7 4'U'7'17/ ':' F Y71 � • ': . 7i 'CI • � • /. � , Mir '.. II7t 4 i • L'� A ''i h '. ".0. , i I � /. 'J "♦ 71' '. ]. G 7 a •' ti t 1 a. 14 r • ':1 '. 1 0. t h ] 1'1 'i7 0. 1 1' 1 ]" a 17 f 7] '1 Y. •� 1 � N X NON -FUSED 1'; '71 1 ] 7 / 4 7• 1 7.' n ' h "71 11 1 ? t GENERATOR © JUNCTION BOX; WITH COVER PLATE r•1'.'il: 1 i'. '1\ 7/ 7'i7 h ] 7 '1 4', 1 1 'iT 1" 1 1. ' {'T 1�' + 7' O n 7 1'. f. :.0.Y ,•. r, .,. 4 . 1 /.• ti • 1' .Y 71 II 3 4 V 1 '. ''. 1' 3. !/' . 4 � ' i l "' 1' 7t 1' ' h DISCONNECT 1 •, 0. 71 :1 1 /' 4' 7' Y '7 i 7• '1''11 " i 1 :. 71 ^ ~ w 1 h 1 ! 4 Fk !1 1 1 • "' } '17' r I ,. i • • 7'1 11 r 1 ';/ 1'/ Ti 1:' • 1# i O i h 1' aln 'h'. 7 ] IT 1 'Y iil ': U ] N' 1' •/ ` ~" SWITCH El '']:� � ]i 1 C 1 71 11 / 7 ' ]I •' 4? ': PULLBOX Y• h' f !. 1' 7 ,• ► f. !. , •, � �, "+ v ' F ''. 7 a r :v• n y' r a•; rr. f.• , a r3 F rr r h . :7'':.41 METER (n Y' SIMPLEX RECEPTACLE , , tw`I• ',. \v V:. F 211 7 - 1. W' 1' t 7 ® 1'..t i'.31 ]/ ,, "'ii 4' "1M0. \v]i ]' 1/' 1 F CEILING MOUNTED FIRE ALARM SPEAKER CEILING MOUNTED FIRE ALARM SPEAKER/STROBE C ' t �� WEATHER HEAD :73 1 '. 71 ' 1 1' ! :ry 1.' v' «'� 4. , n"7 '! 1 v t DUPLEX RECEPTACLE +7,`. ^1 � �: •' 1'1 4 ai' ] ,"0. '1 ':'131 /. F ., p0. • 4. ] - 1 h w '1371 7 - i h4 V,• JQ 1 :. r', a1 / • ' 11 ". Y' Shi '.71 F :171 hIn 1 •1 r' ".171 7 � I♦ :'a 1 7 3 '1 •� h1' ,.• 10.v C:: /.• • V 31 1 • t.. ! 1. CURRENT i. a i' '. 'M / r' 1 '�. ,/... ti !7 ''r7 '7 7 "i 7 4 a M '.'7 w V ! '11. 1 A' n • t 1' I v 1 ," LA FLUORESCENT ON EMERGENCY CIRCUIT ♦ O CEILING MOUNTED FIRE ALARM STROBE M. /• n - 17. } • r wY "^ 4• h 1 , /'• 3 TRANSFORMER T 1a° w:�3 1 7 a 4r /• •i 3.v• 1 �Y :' h' a � DOUBLE DUPLEX RECEPTACLE ,• F f !. - V'l h. 7 4 't ''..h1 /'] 7 I. ♦ 1: '7 ',.vl' :. 7", 71 1. t'• / 1 � r w ;• r ':] 4 I r ',. EXTERIOR +'- n � 1 a Ir • 4 'r •a '.7 4• � u � f CURRENT 4 , J ] 1 ,. ]i / V'i 1 DUPLEX RECEPTACLE ON DEDICATED CIRCUIT /'` • M 7 "i 1' 7 !C:! w , 1 V . 1. / i 1'I '7 O 4 w Q DOWNLIGHT FIXTURE= ' C REMOTE LAMP P F PAD MOUNTED «t r<'�1 1 •ar ':13.:7 / / a• 1']. , ,.,,. TRANSFORMER 7 h4.. h• v 1': / 4' / 30. • 31 ', 1 SPECIAL RECEPTACLE -AS NOTED ON PLANS COMBINATION POWERiCOMMUNICATIONS FLOOR BOX k' it ' 7 t . 71 v 6 '' + W I « PENDANT FIXTURE WALL MOUNTED FIXTURE `T r0. /. ', :.."7 4. 1 '1 0. 1 r ':'iL 7 P'1 1✓ '.... FIRE ALARM STROBE LIGHT DUCT DETECTOR i- '13:1 ']/ ! '7 / J r t ": 10.Y r ,• 7 B x a FF ti h M0.\ + •. •l a' 1 11 h !7 - ] •Y"''� W f' Y 1 7 r '.73' ': 91 7 �- PM -� ,•1 Q+ WALLWASH FIXTURE wv1 f. / 1 '7'. 1'1 !31 a T '�..4 r1.. v '17 MOTION SENSOR q.1 . .• ] h7' •'' ` t' •0.vr 7/ 7' V '1 ' a1't071� 1 '1 ]/ '': 4v' 1' 1 ,•, O Y h•: '7 1 . 1 J. N' 1: v7' F 1 alt '�, , 'T 7 1 rk t' «•1'11i 1 ',• 'A "13. 0. Ni' -) ',1 411.•]' 1' ': ]. 1' '.7 1 ]/. x 7 '1 •, • 1' 1 '71 J i' '. ,. r• «• ••1 0. ,A rf ] 1: n ] / 1.... ,. 1 10. O 7! '4 V '• ] 1 41'1' Tl 1 I. h11. t O EMERGENCY FIXTURE •, 1 17' 7 1 t ✓.7 '.7 ' T1 1'1 f'1 rN 11 F FIREISMOKE DAMPER _ •, '.' ". hl I hM « 1''. 1 ]I X 1 r !1a 7 1 1 ]' ',T'. ].v7 t f'r + F7 !7' 0. a M0. \Y i.� 1 . ,. '1 1 /' 41 7 :a + / 13 13 TRACK LIGHTING 7 1' 1'/ v i : F ': 1 7 1'� 7]' 1 h na. THERMOSTAT ".':1 :'37 1 : I '71 • • I. t �, ' r7' 1' •w '7 SPARE r7 SPACE 1 SPACE WITHIN SWITCHBOARD •,7 " h r. "'7 Y 'i hit 7/ 1 al. «'M! 1' •.., ,p 71 1 F "F ' '1' II 1 1'.• : M 7 +v 'i 7 'r i 'h]- ,• 1 '1 '1 './ •• / 'h0. t• F :Y 10. t 7• •7/ J' :110. 17 V `:.1 I '/ :1 r1' 7' -, • .'!]I f 'h' r1. 1 M0. 1 '13 4 71 17 7 t I17 I w ' F '1'1' 1 1 1 1 1- '.7'1 ali. i.. t]I V •' 7 1'• ] ♦ • 1` 3 •_CF• 1 r 1 �• r 1 71 . r ' .7 1 ri. , a 7' 1 •'Y U '1 , '. .«F0.\ •• YT IF hl a ] h 4 • «a. • a• a a1 4 h 1 7 3 • 1 COD ill. ALL E h "r Ir LUGS SHALL BE RAT F OR A MINIMUM OF DE GREES CELS i / 1'7• k l 7 1' •' 7 h '171 a a .•. 1." >, ': Y• « ':7t 717':. ,. Y••. 'i7 + 71 1 ah 71 Y71. �. 3 1 7 # ivil :7 4 ha'. h v v•7 .v1 7 :. r h �' a 1 1 '. ]' 1 YI ' 1 7 M. ' 1 '.7 " 1 31 r • '1 :• i '1� h1P ' �1 'll r'4 ti N i � 1 • h a, i Y i' h I h, .v ' 7/ t' i 1 r F .' h' 1'177 - W' C •' i N 1'11:I r "•' '7 t' 4 J- 1 •nv 71 I - 1"A 'Y4 •7 •.. 71 T n "4 1 !1 KIIIIIK 41 7' v 'i V !171 h11'4 'eP y'I ra T r1 •' 7 '1.. r•' N 'I :C 1 ♦• 1 a 10. 1 7 A / >• 10. 1 ]' Y/ ]'w 1''1 '.]I '1 ►111 1' 1 1 ]I • h4 1 1�" r h '1 i' « '1' 1' t 'i'. i h •1 •1.• Mt I7 F • r ] 1 r Yr/ 1 rr4 ':. •a :a' t 1 'h0. u Y N 1 t •« 71 h '�71 1 h ''117 '] Y h 1 :'1 10. 4 i � F I M0. fi7' 1:' :! 1 � •.• 1 Y • :t h1 7 w : hi . ".3 1' h•' 1' r1.171 "1 V 1'' 1'J �'� 131: ''1]i •• ] 1 N• 1 1 ' 1 ►1 1 1' 41 t' x1'60. 171 t • .! 7 1 r 1 t•a7 r u r•,i] ,1 1177 ] 4 1 i' t 1' 1' ] '1 Y6 1 • v 7 .` '. 1' r 1 •.,.• 1. 771 7• 1 I n - • ". 4 '7 11'0. 1 ] h77/ � i i' x 1 1 'F F."h '' 11'0. J a h77/ 1' 1 7• 1. -0 1' 1'/ 1 1: : 7ai7•w w 7i 1 ► ':71' ]. 1 ] •;, 1 r r' '1 771 ]' 'F FI'r ' vI i Y 1 71 .731 71 7 '1 Fh 1�' h1 / 1 4140. 1' r1 • : •1 r :':17 7 r r 7 1, 1 -1 Yn7. 4 .1 u•rl 4 h• 7 6 1 . '1 r ;171 :.. •� « • 1I" ]':7 1 FFt ti h •i17 h1 r M" 6 1 r4' - t 1 4. ''.1] i7 'h • ILL- _ it - alb '; 4 0. 1' •7 1, i - h! 1' 'i U f�• '1' • , «Ii ✓1 '.'. 1, 7 7 4 T • I h•i 7 ?a 1 1• «71''� 1 h4; 1 / 1 r r r1. ' ►T; '�: -• 1 i.• v7 4Y « ''7 •' 1 V' 1 hi '7'r 7. 7 « 't '1 / «11 Y 1' 7 '.7 1 7 7 '.7 1 I I ]1• �• . h •' • • 1 IY "1 ] "/ 71 7 :'1.'J 114' 1':'d 1 1 • 71 «.' « ' ca-w .y. ,t a r• it :a 1 'a....« 1 ril '': a •. 1 ':7 4• h ,:.4..11 ... r ',,. ., ,. «I J !. 57' Y 1 'bil «' h 1]'w '1 r I'171 1 •" 1 ', 1' ! •� '' ]. t'• ,• «]. .7 ' 1 .171 17° «4 111' 111' FI !, • :4 F •:" M •!1 «• • • I'i ' it 0.v4 « 1' '.0.v• 6' •1' a ] ', ;' « -F '''1 al N1911' 10.vn '� 11 « ' r • - 17:n Wheat Ridge Building-Dept. Date: - Plan checker ,p Y IC J� c , a " Wh11 jt RWllge B- ,, D, , .;-ent RECORD DOCUMENTS: ELECIRICAL CONTRACTOR SHALL h RECORDS OF ALL DEIIIIIATIONS IN WORK AS INWALLED FROM WORK SPECIFIED ON THE DRANIMS OR IN THE SPECWA71M AND IDDM ORIGIN OF CHANGE 2. 1 A COMPLETE SET OF RECORD DOCUMENT PRINTS IN CUSFIDDY DURIN ENTIRE BRIO OF ODINSIRUCTION AT THE CONSTRUCTION STIE ON COMPLETION OF THE PROIJECI T1111) COMPLETE SETS OF MAWD-UP PRINTS WNW THESE DEVIRIONS SHALL BE DELIVERED TO GENERAL C ONTRACTOR AND AR CHTEECT / EIMM . TH COWRACT WILL HOT CONSIDERED COMPLETED UNTIL l RECORD 1'' h HAVE BEEN RECEIVED 1 REVIENED BY THE ENG 3 7 '1 r4 4' F 1 /• A 1 h !4 0. 4• 71 i 2 Y v.F Kil a L. 1 1111:0 7 1 ]i '1'� 1 / • 1. w 6 1 r "'i ❑ "11• 1 ••/ 1 1 6 .171 •/ 1 1. ` rw 4b41 « 7, ':7 4 '. '�7 r a 7•a1 1 4: Y v t '. 1/, '1T '0. 1 «I. ] •1 7 'rl 'x.77' 4' '.•. 1. 1Ir :171 4 i' 1, 41 « �,0. Y0.} ] " ':71 7 1' W- 1 1 !7' ':1 • 1', , , _' , '171 N "4 "7' /•,• 1 /, 1 , •,• •1 3 K kil Z I I •, •rg BUI 0 r 4E - - T ATE Val" of permit: Of specifludgM and computations sh*'Adbleap aporova °oyviolalente my of the prowww ottlub, ,,yr 'namoa, P"Mk piesurning udtari, ,!. ',a„ 'drsofOn Buildinticoch 0111 in 'N 111d WARRANTY 1. PROVE COMPLETE WARRANTY INFORMATION FOR EACH ITEM. WHICH SHALL INCLUDE NAM OF PRODUCT OR EQUIPMENT: DATE OF BEGINNING OF WARRANTY OR BOND; DURATION OF WARRANTY OR BOND; AND NAMES, ADDRESSES„ AND TELEPHONE NUMBERS OF MANIFACTURING /SERVICING PERSONNEL AS WELL AS PROCEDURES FOR FLING A CLAIM AND OBTAINING WARRANTY SERVICES. 2. THE CONTRACTOR SHALL WARRANT ALL MATERIALS. WgOOAA OW AND THE SUCCESSFUL OPERATION OF ALL EQUIVENT AND APPARATUS INSTALLED FOR A PERK OF ONE (1) YEAR FROM THE DATE OF FINAL ACCEPTANCE OF THE ENTIRE WORK AS IDENIIIFIED IN THE G04RAL COlINTIONS. ELECTRICAL SYMBOLS LEGEND POWER SYMBOLS LIGHTING SYMBOLS FIRE ALARM and MISCELLANEOUS SYMBOLS ONE LINE DIAGRAM SYMBOLS Q JUNCTION BOX; CEILING MOUNTED Fl�;l RECESSED FLUORESCENT FIXTURE UY FIRE HORN WITH STROBE LIGHT PANEL BOARD x 10 JUNCTION BOX; WALL MOUNTED ® SURFACE FLUORESCENT FIXTURE � MANUAL PULL STATION X G X NON -FUSED GENERATOR © JUNCTION BOX; WITH COVER PLATE • • PENDANT FLUORESCENT FIXTURE O SMOKE DETECTOR DISCONNECT I FLUORESCENT O HEAT DETECTOR SWITCH El pal PULLBOX STRIP FIXTURE METER (n Y' SIMPLEX RECEPTACLE ® FLUORESCENT WALL BRACKET UNDER CABINET FLUORESCENT F CEILING MOUNTED FIRE ALARM SPEAKER CEILING MOUNTED FIRE ALARM SPEAKER/STROBE C INTERIOR FF TRANSFORMER �� WEATHER HEAD DUPLEX RECEPTACLE FIXTURE JQ •�- CURRENT LA FLUORESCENT ON EMERGENCY CIRCUIT ♦ O CEILING MOUNTED FIRE ALARM STROBE TRANSFORMER T DOUBLE DUPLEX RECEPTACLE ♦ EXTERIOR CURRENT Q DUPLEX RECEPTACLE ON DEDICATED CIRCUIT Q DOWNLIGHT FIXTURE= ' C REMOTE LAMP P F PAD MOUNTED W TRANSFORMER SPECIAL RECEPTACLE -AS NOTED ON PLANS COMBINATION POWERiCOMMUNICATIONS FLOOR BOX O IO PENDANT FIXTURE WALL MOUNTED FIXTURE F FIRE ALARM STROBE LIGHT DUCT DETECTOR B x TRANSFORMER PULL BOX - GROUNDING CONNECTION �- PM -� PLUGMOLD Q+ WALLWASH FIXTURE � MOTION SENSOR FUSED 0 0 TRANSFER O MOTOR x DISCONNECT I SWITCH O DUPLEX FLOOR RECEPTACLE O EMERGENCY FIXTURE O FIREISMOKE DAMPER X SWITCH X 13 13 TRACK LIGHTING pT THERMOSTAT SPARE X FUSED SPACE 1 SPACE WITHIN SWITCHBOARD ® COMBINATION DATA/TELEPHONE FLOOR OUTLET DISCONNECT ® TELEPHONE FLOOR OUTLET ® EXIT SIGNS; WALL, (;FILING MOUNTED. O PAGER OR MUSIC SPEAKER 1x SPARE SWITCH WITHIN SWITCHBOARD x WITHIN SWITCHBOARD �� • • CIRCUIT BREAKER ® CRT OR DATA FLOOR OUTLET EMERGENCY BATTERY PACK FIXTURE PANELBOARD 0.0 POLE MOUNTED OUTDOOR FIXTURE TELECOMMUNICATION SYMBOLS CIRCUITING SYMBOLS m SWITCHBOARD 5 SWITCH, SINGLE POLE V TELEPHONE OUTLET, SINGLE GANG BOX, 314" � HOMERUN, SOLID 720/208 V, OPEN 2771480 V G 5 2 TWO POLE SWITCH CONDUIT STUB TO ACCESSIBLE CEILING. Zl DISCONNECT SWITCH, NON -FUSED 53 DATA OUTLET, SINGLE GANG BOX, 314" CONDUIT CIRCUIT; RUN CONCEALED IN WALL OR CEILING LO DISCONNECT SWITCH, FUSED THREE WAY SWITCH STUB TO ACCESSIBLE CEILING. 54 DATA/TELEPHONE OUTLET, DOUBLE GANG BOX, - - - - CIRCUIT; RUN CONCEALED IN FLOOR OR GRADE TRANSFORMER FOUR WAY SWITCH v F 314" CONDUIT STUB TO ACCESSIBLE CEILING. -0 -• CONDUIT RISER; TURNED UP, TURNED DOWN O MOTOR 5, KEYED SWITCH TELEVISION CABLE OUTLET Te TIME CLOCK 51) DIMMER SWITCH 0 METER SP SWITCH WITH PILOT LIGHT NOTATION SYMBOLS and TEXT WH WATER HEATER (D PHOTOCELL AFF ABOVE FINISHED FLOOR IG ISOLATED GROUND EM EMERGENCY 5 TO THERMAL OVERLOAD SWITCH AC ABOVE COUNTER NL NIGHT LIGHT HD HEAVY DUTY GIN GROUND FAULT CIRCUIT INTERRUPTER RL RELOCATED DEVICE OR EQUIPMENT TR TAMPER RESISTANT GND GROUND WP WEATHER PROOF 50 e ¢ Eo V Ol c PF Q � C y 6 • s® O n .. N � L N ZZ y cn a v a F N Bl61 E �o � ° v C2 C G W 0 Ei m 173 c ® c to Na V U 'S ai N r EBBU Service Entrance 4980 KIPLING PKWY, UNIT 14 WHEAT RIDGE, CO U00 I I � • Corey FI ... ,t1 b,,neenng. Th6 Aocumev mut the Id i,, end deeigru imnrpernlai4erain, as an bunumum oJpr Jevsinna] sert cmmm he naed, In whole nr in ynrr.,fiv'hin rant orherpr le'' +, u'hhme th Written ow/mmunen Korey Flttinral Errginecring. SUBMITTAL DATE 07.07.2014 FOR PERMIT & CONST. 07.10.2014 Revised Conductor size & length PROJECT TEAM CONTACT: TE DESIGN BY: TE CHECKED BY: SLS PROJECT NUMBER 14158 ENGINEERS STAMP SHEET DESCRIPTION GENERAL NOTES & ELECTRICAL LEGEND SHEET NUMBER El Work shall comply with 2006 IBC, 1PC, IMC, IFGC, IFC, 2011 NEC and any applicable City of Wheat Ridge Municipal Codes. A diiiiiii --- 10 =a M ... M _ f ' O ..... M M LEI M M EXISTING 300 kVA 1201208V, 30,4W O MDFR COMER #2 I \ Fal PAD / MOUNT BY XCEL ENERGY "OP" Sh NEW 604A DISCONNECT ~� V O NEWCR,METER — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — _ _ _ _ _ _ _ _ _ _ _ _ _ _ — — — — — — — — — — — — — — _ _ _ _ _ _ _ _ _ _ ",. _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ — — � N POWER PLAN Q SCALE: NONE GENERAL NOTES: A. NEW AND RELOCATED ITEMS SHOWN AS BOLD EXISTING ITEMS SHOWN AS LIGHT O PANEL "DP" (NEW) #4 PER NEC' 50.66 (B) : I y #2/0 /0 CU PER NEC 7250.66 USE WHAT IS AVAILABLE ON EXISTING BUILDING UFER BLDG GND STEEL r- 2[(4.350 KCMIL CU; 1412 G) 3" C. 600 13 2[(4.350 KCMIL CU; 142 G) 3" C. NEW (, M UTILITY T METER N C ' POINT #2 3 JAl2 H 200/3 200/3 n V #A3 N P ANEL 1 25/2 900/3 \400/3 200/3 IDA 1ZSS/2 200A M FR IEIER cow #1 -- - - -- -- --- - --- -- EXISTING BUSSED GUTTER - J EXISTING 300 kVA 1201208V, 30,4W PAD MOUNT BY XCEL ENERGY O DETAIL NOTES - POWER 1. TYPE OF THE PANEL "DP" WILL BE DETERMINED UNDER SEPARATE CONTRACT. MINIMUM REQUIREMENTS OF 22K AIC RATED, 42 POSITION, LOCKABLE DOOR, COORDINATE EXACT LOCATION OF CONDUITS ENTER BUILDING WITH TENANT PRIOR TO ROUGH IN. 2. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH XCEL PRIOR TO TRENCHING THE AREA NEAR THE TRANSFORMER. E.C. SHALL BRING THE CONDUITS INTO THE TRANSFORMER IN THE GENERAL LOCATION SHOWN. CONDUITS SHALL BE BROUGHT INTO THE TRANSFORMER FROM THE FRONT PER THE XCEL LINEMAN SERVICING THIS AREA. INFORMATION BASED ON THE TRANSFORMER INVESTIGATION COMPLETED ON JULY 2ND, 2014 WITH COREY ELECTRICAL ENGINEERING AND XCEL ENERGY LINEMAN. 3. NEW UNDERGROUND CONDUIT, COORDINATE EXACT ROUTING WITH LOCATION OF EXISTING UNDERGROUND CONDUITS. CALL FOR LOCATES BY UNCC PRIOR TO EXCAVATING. TRENCH T = . TRENCHLESS CKL Q ACCEPTABLE OPTION, LOCATES STILL REQUIRED. 4. NEW 2-HOUR RATED DEMISING WALL FROM FLOOR TO DECK TO COMPLETELY SEPARATE THIS TENANT FROM THE ADJOINING SUITE. 5. CONDUIT AND CONDUCTORS TO EXISTING PANELS IN THIS AREA FROM METERING CENTER #1 SHALL BE REMOVED IN THEIR ENTIRETY. REMOVE METERS AND RETURN TO XCEL AND PROVIDE BLANKS. 6. PROVIDE PHENOLIC PLAQUE LABELS AT BOTH SERVICE ENTRANCES INDICATING THE EXISTENCE OF 2 SERVICES FED FROM THE UTILITY TRANSFORMER AND THE LOCATION OF EACH SERVICE. 7. PRICE ALTERNATE: ELECTRICAL CONTRACTOR PROVIDE PRICING FOR EACH TYPE OF CONDUIT AND CONDUCTOR TO FEED THE NEW SERVICE. ELECTRICAL CONTRACTOR SHALL VERIFY ACTUAL DISTANCE OF WIRE PRIOR TO BIDDING. � � a ( � P < #1 #6 CU PER i 4[(4 -500 KCMIL CU) 3" C.] T 1/ NEC 250.66 (A) 1 �- 2[(4500 KCMIL CU) 3" C.] GND I - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - --- =KCMILCU) --- - - - - - J i ROD 7 -¢ I - J t .,_------ -_¢ ----- ------------------- ------------ 3 0 ���•�l i�V�e►•rriln f1�IC 1 IA#C r%1Af'%15ALA SCALE: NONE GENERAL NOTES: A. NEW AND RELOCATED ITE=MS SHOWN AS BOLD EXISTING ITEMS SHOWN AS LIGHT Q 1 EBBU - 4980 Kipling Pkwy Project #14158 Based on BOW Load Price Alternate: Copper O VOLTAGE DROP CALCULATION Voltage .............. t 208 Load Amperage ........ : 480 Circuit Length (Ft) .. : 256 Conductor Size ....... : 400 Kcmil Conductors Per Phase " ; 2 Conductor Material ... : Copper Circuit Type .. : AC Three Phase 4 Wire Voltage Drop between any two phase conductors (0,866 x 2 x Ohms per 1000 ft x Length x Amps) VD ---------------------------------------------- 1000 x Qty Wires per Phase 0.866 x 2 x 0.0321 x 256 x 480 VD= - ------- ----- ---- -- --- -- - - -- -- x 0.5 1000 x 2 Volts Dropped : 3.42 Volts At Load : 204 "58 Percent Drop .: 1.64 EBBU - 4980 Kipling Pkwy Project #14158 Based on 8041 Load Price Alternate; Aluminumr Q V OLTAGE DROP CALCULATION Voltage .............. : 208 Load Amperage ........ : 480 Circuit Length (Ft) .. : 256 Conductor Size ....... 600 Kcmil Conductors Per Phase . : 2 Conductor Material ... : Aluminum Circuit Type .. : AC Three Phase 4 Wire Voltage Drop between any two phase conductors (0,866 x 2 x Ohms per 1000 £t x Length x Amps) VD= -------------------------------------------"-- 1000 x Qty Wires per Phase 0,866 x 2 x 0.0353 x 256 x 480 VD= ------------------------------ x 0,5 1000 x 2 Volts Dropped : 3.76 Volts At Load : 204.24 Percent Drop .: 1,81 30 FAULT CALCULATION - CU POINT #1, AT THE UTILITY TRANSFORMER; Ise = 52,OOtl A POINT #2, AT THE 600A MAIN DISCONNECT;. f = 1.73 x Length x Ise (source) I L -L Volts x Wire Factor f = 1.73 x 256 x 52000 A/ 208 x 48592 f a 2.26 M= 1 / t +f=1/ 1+ 2.28 = 0.31 Ise - M x Ise (source) = 0.31 x 52000 A = 15,861 A 30 FAULT CALCULATION - AL POINT #1, AT THE UTILITY TRANSFORMER; Isc a 52,000 A POINT #2, AT THE 600A MAIN DISCONNECT; f - 1.73 x Length x Ise (source) I L-L Volts x Wire Factor f- 1.73 x 256 x 52000 A/ 208 x 46902 f = 2.36 Ma 1 I 1 +f =1/ 1+ 2.36 = 0.30 Ise - M x Ise (source) = 0.30 x 52000 A = 15,473 A APPROVED Subject to Field Inspections Wheat Ridge Building Dept. Date: 8 l g Signed Plan checker �E �m Qd ® o`s Wm 0 cn LLA a a � a d N 0 r m a o � a yy L C G W V � m C � � U v d L N N r EBBU Service Entrance 4980 KIPLING PKWY, UNIT 14 WHEAT RIDGE, CO CmrP! r''F" Thi d nr aM eh vdeu aMde gr , p w /herei - mr r Jp f' 'o I r be ed ' ,vhMe , fmrh jnr Uis aru YmhcrYrzO�gx ham rho xvix<n our! r' nnJCo YE9xMm! Fngirueni SUBMITTAL DATE 07.072014 FOR PERMIT & CONST. 07.10.2014 Revised Conductor size & length PROJECT TEAM CONTACT: TE DESIGN BY: TE CHECKED BY: SLS PROJECT NUMBER 14158 I ENGINEERS STAMP SHEET DESCR ELECTRICAL PLANS & ONE -LINE DIAGRAM SHEET NUMBER EZO City of ta ° W h6, at g COMMUNrii, DEVELOPMLNT # Building Permit Application W T-tv wli!, P*0004*00** (please prin Property Owner Email: mz���� Address: gy, �State, �Zi. Dl MFUMM n.1-MMUZ I'll I Plumbing: W.R, City Licen A City License # Sq. FULF Btu's Gallons Amps Squares Other any new wall signs. You will also need to create a site plan and a detail sheet • the signage. Project Address: x� 'k v --, Contractor: You are allowed I square foot of signage for every I linear foot of wall to which you are attaching a sign. Stop 1: Measure the length of the wall(s) where you are attaching the sign: Wall I - 2 feet Wall 2 - feet Wall 3 - feet LVIIINH LVIT'R.1 square feet square feet square feet Nvork shall coj -y with 2006 IBC rj pj and any applicable City of Wheat Ridge, Municipal Codm 0 .......... .......... - .......... ..... .......... .............. .. ..... .. SIGN AREA. CAPTURE RECTANGLE 20 S. A E VIA SCALE: 1/2" = V-0" m i Customer Approval , PP BY ... F - P 0 V - E "'- D Subjectito Field j , Date: Signed" ---Ran EXISTING CONDITIONS - EXISTING CHANNEL LETTERS ARE 12' HIGH ANDING 0' -0 ". LETTERS MOUNTED ON RACEWAY. --. - ---_ - 13'-4" C Property Address� Property Owner OleasE� pfint): Mailing Address (if slifferi- than prc�perty address) AcJdress: 01v, State, Zirt Q3 Phone , 3c (ANNER"'CONAR WTOR S1CN,A'fVR1'0F1 NDVRS'1ANDJN(; k\ don o" 0� It' i, E 144 V,14 X zd abi d vt md � t Not tit al 1 1 ic, il 4m u id h it I a nn tatty ,rc °ap>tce stand ,tt' +s4 comilk;m"'v \,k it kA of kk I�c% t R sthuv i:,odc- amtl tv J in" m cc ft w ml, kmo'cr xv m-M,To: t vO b� Ink ovkmj 3, s ,%or d 4% tag w , V""'pvv mduzl d im 'W xirfw , tw , 1" lhm p0c,mon, Wit Nhki Uty% TR j(j(hq�) if 71101WED Rt P/11"VE % T I III I') Zak IfM H f)N r1i It ME • • You must complete this sheet and include it in the submittal package for any new wall signs. You will also need to create a site plan and a detail sheet • the signage. Project Address: 30' L, f contractor: ANdAdAWd You are allowed I square foot of signage for every I linear foot of wall to which you are attaching a sign. OEM IM I � I �, I I 1� I I to 1: Measure the length of the wall(s) where you are attaching the sign: Wall I - feet Wall 2 - feet Well 3 - feet Wall I allowable signage- i'll ♦ IN a W N i UIRTZOT M-2 10 square feet square feet square feet :t .g le. @39.7 ,- 105,1 77661, 1 =! ll le3 If9 211 14 Goog Maps h ;/ le. / @3 .?$ .105.1 18,1 -t i! 1 3 1f1 211Z2014 Goog Maps ROM Jason Poland ° n pol nd gmaH. cm> Your sign quotel Icheele Sweet <msweet l84 mail.co > Wed, Feb 12, 2094 at 12:49 F To: Jason Poland < son d nt esl ncomp ny.com> From: Cathy Roscio D. te: February 10, 2014 M AM EST • Subject: Your • • "' pprc d, both signs! 383 I nvemess parkway, Suite 285 Englewood, CO 80112 Phone 303,662,0923 www.transwestem.net • !Ii#• Sent: Monday, February 10, 2014 9:13 AM To: i Subject: r* Your # quote! Nice lady! I met vvith her for 40 minutes last Tbursday. Let me know if a "temporary banner" is OK prior to the permanent sign getting installed. Edgy, I like it! 4980 Kipling St, Wheat-ffi e. C 0 80033 Fabricate one new set of 12" LED illuminated pan channel letters mounted a raceway with 5" deep black returns and 3/16" white acrylic faces with translucent vinyl overlays. Quote includes installation but not primary electrical hookup, please see below. $3,722M Fabricate one 3'x 12'double-faoed white 13 oz. banner, hemmed and grommeted, with the graphics digitally printed on both sides of the banner, Quote includes installation. $ 447,00 Note Taxes, permit and permit acquisition fees are not included in this quo and will be an additional charge. i Note: *Artwork. When reproducing clients logos or graphic identification, camera-ready artwork is to be supplied by customer' Additional charges will accrue for cleanup and preparation of artwork that is not 'camera ready' at a rate of $65,00 per hour. 4 4 1 prhm ry el�ectrktal Conner ions rnust be cornplet , 1 a ficen t d ele� ftioian and v na t"biscontract and are the soie 'All applicable taxes, permit fees and permit acquisition fees are an additional cost, *AH electrical outdoor displays are U,L. listed and comply with all local county and cfty regulatory codes, WARRANTY: The above display is guaranteed against defective, materials and workmanship for 12 months from the date of installation. Customer's initials IMMEMMEMM . . . . . . . . . . . . 4980 Kipling St, Wheat-ffi e. C 0 80033 Fabricate one new set of 12" LED illuminated pan channel letters mounted a raceway with 5" deep black returns and 3/16" white acrylic faces with translucent vinyl overlays. Quote includes installation but not primary electrical hookup, please see below. $3,722M Fabricate one 3'x 12'double-faoed white 13 oz. banner, hemmed and grommeted, with the graphics digitally printed on both sides of the banner, Quote includes installation. $ 447,00 Note Taxes, permit and permit acquisition fees are not included in this quo and will be an additional charge. i Note: *Artwork. When reproducing clients logos or graphic identification, camera-ready artwork is to be supplied by customer' Additional charges will accrue for cleanup and preparation of artwork that is not 'camera ready' at a rate of $65,00 per hour. 4 4 1 prhm ry el�ectrktal Conner ions rnust be cornplet , 1 a ficen t d ele� ftioian and v na t"biscontract and are the soie 'All applicable taxes, permit fees and permit acquisition fees are an additional cost, *AH electrical outdoor displays are U,L. listed and comply with all local county and cfty regulatory codes, WARRANTY: The above display is guaranteed against defective, materials and workmanship for 12 months from the date of installation. Customer's initials IMMEMMEMM CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line 303) 235-2855 Office - (303) 237-8929 Rix Inspection Type 1"e'0L4e"41 Job Address Permit Number 0 r , Oli - AJ A- eel's I No one available for inspection Time - AM/PM Re-inspection required: Yes No * When corrections have been made, caff for re -In apection at 303-234-5933 Date: L a—l' — ( 1—/ 3 Inspector: _U1 CITY OF WHEAT RIDGE Building Inspection Division (3 03) 234-5933 Inspection line 235-2855 Office - (303) 237-8929 I F] No one available for inspection: Time - AM/PM Re-Inspection required: Yes No Men 7717777 catt r re- on UFMaMns TINTO ..... .... . Date inspector: �4 City of What COMMUNITY DEWLOPMENT Electrical Contractor Plumbing Contractor __ ~ Company Name: Phone °~ �t�� �~ �^ -__-__'__- ' _~_s~_~.. Date Mechanical Contractor wv6 4. Signature of Authorized Agent Date » ^ . r � a •sue .•a Cont r actors City License M. P hone: Cont ractor E -mail Address. Sub Contractors: E lectrical: plumbing: ' Mechanical: W.p. City License # WR City Ucense# WR City License ;# Other City Licensed Sub: Other City Licensed Sub: City License # City License Complete all information on BOTH sides of this form � W� 0 � W, �� S q. Ff. LF Stu's Gallons Amps Squares Other • =17 I M# Plan chef �,er A 8 C D Area Category Floor Area Allowed Allowed Watts (M) Watts / M (B x C) Office 80 1 80 MSMUMMZX�� A B C D E Fixture ID . Description I Lamp / Wattage Par Lamp / Ballast Lamps/ # of Fixture (C X D) Fixture Fixtures Watt. Linear Fluorescent I � k 24' T8 17W: Electronic: 2 2 32 64 I Interior Lighting PASSES: Design 20% better than code. Lighting Wattage: 1, Total proposed watts must be less than or equal to total allowed watts, Allowed Watts Proposed Watts Complies 80 64 YES Exception& LJ Areas designated as security or emergency areas that must be continuously illuminated. LJ Lighting in stairways or corridors that are elements of the means of egress, Project Title: VERT KITCHEN Report date: 11/06613 Data filename: S:\Drawingsk2013\4980 Kipling A-12 Wheaffidge 13170\Beffay\Calculations\Eiectrical\lnt Lighting 13170.cck Page 1 of 2 Compliance Statement. The proposed fighting design represented in this document is consistent with the building plans, specifications posed Ii htin s�.fstem has been -designed to meet the 2009 IECC requirements in COMcheck Version 3,9.2 and to comply with the mandatory requirements in the Requirements Checklist, Brian Bryce - Belfay Engineering ...... Name - Title Signature • a e Project Title: VERT KITCHEN Report date; 11106/13 Data filename: SADrawings\2013\4980 Kipfing A-12 Wheatridge 131700Beffay\Calculations\Electrical\lnt Lighting 13170,cck Page 2 of 2 City Date: of Wh6atR c ,,_jA COMMUNiTy Du-VELOPMENT Plan1peftnit # Complete all information on BOTH sides of this form 124 or have bevn authorized by the legal owner of the property to perfonn the described work and am also authorized by the legal owner of any entity included on this application to list that entity on this application. Bui dNtlb"' Certificate Of Completion Building Division 7500 W 29TH AVE WHEAT RIDGE CO 80033-8001 Permit#:201300614 Issued: 05/30/2013 Stipulations: Reconstruct (1) One Hour Rated Wall to Demise a Suite into (2) Two Suites. This certificate verifies that the building constructed and/ the use proposed of the building and/or premises, under t above permit number and on property described below, does compl with the Wheat Ridge Building Code and development standards the zone district in which it is located and may be occupie All other licensing requirements for the City must be met. I # 0 9 IMMUM Owner: TR INVERNESS CORP. 383 INVERNESS PARKWAY SUITE 285 ENGLEWOOD, CO 80211 Contractor: John Glassner 12254 W ARLINGTON AVE LITLLETON CC 30127 C of _i��Wh­ -�itt� k jjgc COMMUNrry DEVELOPMENT _08-1 Plan Perm it , ? �Q 4980 Kipling Street, Suite A13 & A14, Wheat Ridge, CO 80033 mmmommEwm Electrical: N /A Plumbing N /A Mechanical: N/A City License # City License City License W b F 91 qg0 Kfplidn INSPECTION ft fel Occunanc�Tvne l (e' "V �� S�iT INSPECTION REQUEST LINE: (303) 234 -5933 Inspections will not be performed unless this card is posted on the project site. Call the inspection request line before 3:00 p.m. to receive an inspection the following business day. Inspector Must Sign ALL Spaces pertinent to this project Foundation Inspections Date Inspector Comments omments Monolithic Slab Reinforcement Drywall Screw / Nail Caissons FInalInspections Date Inspector `Initials Concrete Encased Ground (CEG) Final Electrical / Footing /Stemwall P.E. Letter Final Plumbing Do Not Pour Concrete Prior To Approval Of The Above Inspections Underground /Slab Inspections Date Inspector Initials Comments Electrical (Underground) Final Building / Frame Sewer Service (Underground) Water Service (Underground) Landscaping & Parking / Planning Dept.. Plumbing (Below / In -slab) Inspections from these entities should be requested one week in advance. For landscaping and parking inspections call 303 - 235 -2846. For ROW and drainage inspections call 303 - 235 -2861. For fire inspections contact the Fire Protection District for your project. ROW & Drainage / Public Works Dept. Heating (Below/ In -slab) Fire Inspection / Fire Protection Dist. Do Not Cover Underground or Below /In -Slab Work Prior To Approval Of The Above Inspections Rough Inspections Date Inspector Initials Comments Wall Sheathing Roof Sheathing Lath / Wall Tie Rough Electric Rough Plumbing Rough Mechanical Gas Piping . I 4.1 V161 N J 90T04aN. 8119 Y l Tel a r9 n.l iLlrRl u f i.�:T.l�'L1- lTR:1:1 rT,TTS Rough Framing nsylati6n Drywall Screw / Nail FInalInspections Date Inspector `Initials Comments Final Electrical / Final Plumbing Final Mechanical Roof Final Building / Frame Landscaping & Parking / Planning Dept.. Inspections from these entities should be requested one week in advance. For landscaping and parking inspections call 303 - 235 -2846. For ROW and drainage inspections call 303 - 235 -2861. For fire inspections contact the Fire Protection District for your project. ROW & Drainage / Public Works Dept. Fire Inspection / Fire Protection Dist. * *Note: All items must be completed and approved by Planning, Public Works, Fire and Building before a Certificate of Occupancy is issued. Approval of the Final Building inspection does not constitute authorization of occupancy. Occupancy Is Not Permitted Until A Certificate Of Occupancy Is Issued Protect This Card From The Weather ♦ i CITY OF )(VHEAT RIDGE r Building Inspection Division 1 (303) 234 -5933 Inspection line (303) 235 -2855 Oiii e • (303) 235 -2857 Fax INSPECTION NOTICE Inspection Type: Job Address: Permit Number: = i.` w-c.>�; a c G F f I ❑ No one available for inspection: Time AM /PM t° Re- Inspection required: Yes �Wo * When corrections have been made, call for re- Inspection at 303 - 234 -5933 Date: s .1 Inspector: ':7 DO NOT REMOVE THIS NOTICE City of Wheat Ridge _ter ► J Commercial Electric PERMIT - 111304 PERMIT NO: 111304 ISSUED: 10/25/2011 JOB ADDRESS: 4980 Kipling St., Unit #13 EXPIRES: 10/24/2012 DESCRIPTION: Meter reset * ** CONTACTS * ** owner 303/745 -5800 sub 303/288 -3152 Colliera B -K Victor /Norma Frank 01 -8734 COLORADO LIGHTING, INC. ** PARCEL INFO ** ZONE CODE: UA USE: UA SUBDIVISION: 0041 BLOCK /LOT #: 0/ ** FEE SUMMARY ** ESTIMATED PROJEC VALUATION: 150.00 FEE Permit Fee 26.50' Total Valuation .00 CDlkbbb5l Use Tax 2.70 - ' ** TOTAL ** 29.2 Conditions: Must comply w/ 2006 IBC & 2005 NEC. Subject to field inspection. I, by my signature, do hereby attest that the work to be performed shall comply with all accompanying approved plans and specifications, applicable building codes, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with this permit. I further attest that I am legally authorized to include all entities named within this document as parties to the work to be performed and that all work to be performed is disclosed in this document and /or its accompanying approved plans and specifications. Signature Ing " OWNER or ONTRACTOR (Circle one) Date 1. This permit was issued based on the information provided in the permit application and accompanying plans and specifications and is subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures. 2. This permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and received prior to the date of expiration. An extension of no more than 180 days made be granted at the discretion of the Chief Building Official and may be subject to a fee equal to one- half of the original permit fee. 3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard requirements, fees and procedures for approval of any new permit. Re- issuance or extension of expired permits is at the sole discretion of the Chief Building Official and is not guaranteed. 4. No work of any manner shall be performed that shall results in a change of the natural flow of water without prior and specific approval. 5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all required inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services Division. 6. The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, any violation of any provision of any applicable code or any ordinance or regulation of this jurisdiction. Approval of work is subject to field inspection. Signature f Building Offical Date INSP IO REQUEST LINE: (303)234 -5933 BUILDING OFFICE: (303)235 -2855 REQ STS MUST BE MADE BY 3PMANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. W heat x ,,O le Date: �ommum , DEVELOPMENT Plan # Building & Inspection Services Division Permit # 7500 W. 29" Ave., Wheat Ridge, CO 80033 Office: 303 - 235 -2855 * Fax: 303 - 237 -8929 Inspection Line: 303 - 234 -5933 I Building Permit Application Property Address, ! 8o f Ixi ) .2 } t : Property Owner (please print): Co (((hkA Phone: 3)- ' 5 0 Mailing Address: (if different than property address) Address: '7�y3 City, State, Zip: w,VVln Contractor: C o) o f TN Contractors City License M Phone: 2 p " ZV5 2 I 's L = qr s� Plumbing: Mechanical: City License # City License # City License # �b�s7ryrt»tion`�of�vSoik ConSr ct Value: $ 9r�,O Review Fee (due at of submittal): Squares BTU's Gallons Amps Sul Ft. $ OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate and do not violate, applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown and allegations made are accurate;. that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance with applicable City of Wheat Ridge codes and ordinances for work under any permit issued based on this application; that I am the legal owner or have been authorized by the legal owner of the property to perform the described work and am also authorized by the legal owner of any entity included on this application to list that entity on this application. CIRCLE ONE: (OWNER) (CONTRACTOR) i r (AUTHORIZED REPRESENTATIVE) /[� "l SEN(jTATIV/�En) of (OWNER (CONTRACTOR) PRINT NAME: b..V�A i / Y o I t /U hh. l/(X/ SIGNATURE: DATE:. P--251 Bldg Valuation: $ City of Wheat Ridge r0 000r_ Commercial Remodel PERMIT - 110777 PERMIT NO: 110777 ISSUED: 07/06/2011 JOB ADDRESS: 4980 KIPLING ST EXPIRES: 07/05/2012 DESCRIPTION: Create opening and install OH door in commercial space * ** CONTACTS * ** gc 303/778 -8555 Alan P, Waring 06 -0220 A &B Builders, Inc. owner Colliers Internation ** PARCEL INFO ** ZONE CODE: UA USE: UA SUBDIVISION: 0041 BLOCK /LOT #: 0/ Conditions: KC: Approved per plans and red -line notes on plans. Must comply with 2006 IBC, 2005 NEC and all applicable City of Wheat Ridge Municipal Codes. Subject to field inspections. I, by my signature, do hereby attest that the work to be performed shall comply with all accompanying approved plans and specifications, applicable building codes, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with this permit. I further attest that I am legally authorized to include all entities named within this document as parties to the work to be performed and that all work to be performed is disclosed in thi document apd /or ij �ompanying approved plans and specifications. SlgnaEure of OWNER orV CONTRACTOR (Circle one) ­ Date 1. This permit was issued based on the information provided in the permit application and accompanying plans and specifications and is subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures. 2. This permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and received prior to the date of expiration. An extension of no more than 180 days made be granted at the discretion of the Chief Building Official and may be subject to a fee equal to one- half of the original permit fee. 3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard requirements, fees and procedures for approval of any new permit. Re- issuance or extension of expired permits is at the sole discretion of the Chief Building Official and is not guaranteed. 4. No work of any manner shall be performed that shall results in a change of the natural flow of water without prior and specific approval. of all required inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services Division. 6. The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, any violation of any provision of any applicable code or any ordinance or regulation of this jurisdiction. Approval of work is subject to fieldAnAction.., Sign at a ofl Fhief Building Offical .. Date INS CTION REQUEST LINE: (303)234 -5933 BUILDING OFFICE: (303)235 -2855 REQUESTS MUST BE MADE BY 3PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. City of P Wl leat �lC e � N Date: -711 11 COMMUNITY DEVELOPMENT j Vp, Plan # Building & Inspection Services Division r Permit 7500 W. 29 Ave., Wheat Ridge, CO 80033 �., 1 10 177 Office: 303 - 235 -2855 * Fax: 303 - 237 -8929 ' Inspection Line: 303 - 234 -5933 Building Permit Application y � IU e( rJC S . roperty_Add_ress J y� Property Owner (please print) j ) �� 6 r1 Phone: Mailing Address: (if different than property address) Address: City, State, Zip: r71 �.,���pp ) , Contractor L F gu VP aG R �tN c P ti °k-, 3 2 ° G 1 6 Contractors City License #: 06? Phone:��js Sub Contractors�:� ( Electrical I J J Plumbing: &( / Mechanical: N City License # City License # City License # c/e D pra- - M SI o Con r ct Value: Review Fee (due at time of submittal): quares BTU's Gallons _ Amps Sq Ft. $ ° �� 1 OWNEWCONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT 1 hereby certify that the setback distances proposed by this permit application are accurate and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance with applicable City of Wheat Ridge codes and ordinances for work under any permit issued based on this application; that I am the legal owner or have been authorized by the legal owner of the property to perform the described work and am also authorized by the legal owner of any entity included on this application to list that entity on this application. CIRCLEON6: (OWNER)' CONTRACTOR) r (AUTHORIZED REPRESENTATIVE) of (0{ %P). (CONTRACTOR) PRINT NAME: AO DN V &% /: i SIGNATURE: DATE: t t I . Bldg Valuation: + �� a mxawuawn�vamaw. mtn.azruu",v�uro,nmat :e Dt VrJ�r �1 x t � 1 y sA f x� VArbu�.�t� * x c ed\ Vxq x tixxi rl ft x �1 }x � Ct�Ysav �A 1nAA i A � U r L.1�lPtN t a t r 0 Qtb \` ry�yy � C �0. y �k�l VtV0 t � �xC�k� t.G ,Waw t� d V p P� O �� \ t =» h 1 ur��q �i: ..Aa x �� V a P., •. mo A-G.t Si7� �ert%ys✓L E isUi� O' Kea ✓� °s rY?J .!1� ®�E� ✓E'v �3y n3G�i✓f_f ;�Y 13v lv>:vG f ✓ <SsQ v y LuF: - Sr "-rTrk 0 S 86d/ 2 h* w6 qufad cols or lJ u 55CfM AA MIOK9 ca um, 6X6 CO LWN 51MLAR - Nobe% Cavkuchm shad be as per 2006 i>fawtwrW codes. oQPe 5ted shad be gads M6, Welds and coWm chm as per A15C manual, Caw& wdfi amrow when wad Is e>p OVA fa• w MkStbn of inns / best 6w ri 2006 IBC, IMC, IPC, IPMC, IECC, IFC, IFGC; 2005 NEC; NFPA 99 and ICC /ANSI A117.1 - 2003 1/ 2 all dread 6 laq a 24 ac. thu web 5 per cdumn dated a not necessary for M 00 cdum, spoxil Into black wad kml v u flii / r— A B 8x&/ 2" 5ted A* w svAmvow 6 -87 -11 O ,� pl Iced I,I,� 'YV 'i -if i 1 heAw* roof JMA is needed uder,pist, WId+ �WHECT, M O�COR a�O Wheat Ridge Building Department Approved DATE UIL !ali ity of permit: The issuance of a permit or approval of plans, specifications_. and computations shall not be a permit for or an approval of, any violation to any of the provisions of the building code or of any City ordinances. Penoitit presuming to give authority to violate or cancel the provisions of the building codes or other ordinances of the City shall not be valid. APPROVED Subject to Field Inspections Wheat Ridge Building Dept. i Sign .... ..........plan Checker A pr00vEE D: rt. --- CERTIFICATE OF COMPLETION City of Wheat Ridge 7500 W 29th Ave Wheat Ridge CO 80033 Permit# 110008 Stipulations: Issued: 03/02/11 Tenant Finish; New Walls, Door, and 4 Outlets. This certificate verifies that the building constructed and/ or the use proposed of the building and /or premises, under the above permit number and on property described below, does comply with the Wheat Ridge Building Code and development standards of the zone district in which it is located and may be occupied. All other licensing requirements for the City must be met. Site Address: 4980 KIPLING ST Suite #4 Parcel Number: 39- 153 -14 -010 Owner: Edward Jones 4980 Kipling St Suite 4 Wheat Ridge CO 80033 Contractor: Craig Wilpolt Creative Construction 8449 Flora St Unit B Arvada, CO 80005 For the Following Purpose: Comm. Tenant Finish Code Editions NO change shall be made in the USE of ��06 ICC /2008 NEC this building without prior notice 2006 ICC /2005 NEC and a new Certificate of Completion 2003 ICC /2005 NEC from the City of Wheat Ridge. ,9�prinklAr System ng Inspector Zoning Administrator CERTIFICATE MUST BE POSTED BY FRONT DOOR OF COMMERCIAL OCCUPANCIES 03/03/11 08:15:17 City of Wheat Ridge Page 1 bp701 -ls PERMIT INFORMATION - 110008 mmackey PERMIT INFORMATION: Permit #: 110008 Permit Type: Comm. Tenant Finish Permit Dt: 01/04/2011 Expires: 01/04/2012 Address: 4980 KIPLING ST Suite #4 Parcel Cd: 39- 153 -14 -010 OWNER: Edward Jones Address: 4980 Kipling St Suite 4 City /St /Zip: Wheat Ridge CO 80033 LAND PARCEL INFORMATION: Zone Cdr Unassigned DU: 1 Funct Use: Unassigned Last Zone Dt: Subdivision: KIPLING 5000 BUS PK Annex Dt: Cant Type: Miscellaneous Lot: Block No: 0 Legal: JOE DESCRIPTION: Install new walls, hang drywall,new door, 4 outlets FEES QTY DUE PAID: Permit Fee 2,300.00 93.35 93.35 Plait Review Fee .00 60.68 60.68 Total Valuation 2,300.00 .00 .00 Use Tax 2,300.00 41.40 41.40 ---- - - - - -- 195.43 --- - - - - -- 195.43 SetBacks- Front: 0.0 Left: 0.0 Right: 0.0 Back: 0.0 CONTACTS: owner Edward Jones 4980 Kipling St Suite 4 Wheat Ridge CO 80033 3145152000 go CL1 Creative Construction Craig Wilpolt 8449 Flora St Unit B Arvada, CO 80005 3034311729 sub CIA Bradley Electric, Inc. Mark Bradley 4631 Pierce St. Wheat Ridge, CO 80033 3034244374 PARCEL INFORMATION: 10 Structure Type 101 20 Year Built 1984 30 Property Type COMMR PERMIT CONDITIONS: JZ: Approved per plans and red -line notes on plans. Must comply with 2006 IBC, 2005 NEC, and all applicable City of Wheat Ridge Municipal Codes. Subject to field inspections. APPROVALS: REQUIRED INSPECTIONS STATUS: Type Description Required By Completed On - - - -- -------------- - - - - -- ----- - - - - -- ------ - - - - -- Fire Final Fire Dept Insp PERMIT NOTES: 01/04/11 Given to KC for review. 01/04/11 CREATED FROM APPL# 11 -0002 INSPECTION INFORMATION: # TYPE CONTR# CALLED MCI WHO RED DT INS DT STATUS 1 FRI:Framing Rough Insp. 08 -0269 02/01/11 no KC 02/01/11 02/01/11 INCOMPLETE 2 ERI:Electrical Rough Ins 01 -8594 02/01/11 no KC 02/01/11 02/01/11 INCOMPLETE 3 FRI:Framing Rough Insp. 08 -0269 02/02/11 no KC 02/03/11 02/03/11 INCOMPLETE 4 ERI:Electrical Rough Ins 01 -8594 02/02/11 no KC 02/03/11 02/03/11 COMPLETE 03/03/11 08:15:17 City of Wheat Ridge Page 2 bp701 -1s PERMIT INFORMATION - 110008 mmackey 5 FRA:Framing Inspection 08 -0269 02/04/11 no KC 02/07/11 02/07/11 COMPLETE 6 OWS:Orywall screw /nail 08 -0269 02/09/11 no KC 02/09/11 02/09/11 COMPLETE 7 EFI:Electrical Final Ins 01 -8594 03/01/11 no BCSI 03/02/11 03/02/11 COMPLETE 8 BFI:Building Final Insp 08 -0269 03/01/11 no BCSI 03/02/11 03/02/11 COMPLETE INSPECTION RECORD 777 Occup an cy/Type "VI NSPECTION LINE (303) 234 -5933 Inspections will not be made unless this card is posted on the building site Call by 3:00 PM to receive inspection the following business day. IN PECTOR MUST SIGN ALL SPACES PERTAINING TO THIS JOB FOUNDATION INSPECTIONS DATE INSPECTOR INITIALS COMMENTS: Footings /Caissons Drywall Screw Stemwall / (CEG) Concrete Encased Ground j Reinforcing or Monolithic Weatherproof / French Drain Sewer Service Lines , Fire Department Water Service Lines R.O.W & Drainage CONCRETE SLAB FLOOR Electrical Plumbing (Underground) Heating (Underground) ROUGHS Sheathing ,�,c Insulation Lath /Wall tie Drywall Screw Mid -Roof j Electrical Service Rough Electric Rough Plumbing , Fire Department Gas Piping R.O.W & Drainage Rough Mechanical INSPECTIONS FOR PLANNING & ZONING, FIRE AND PUBLICE WORKS SHOULD BE CALLED AT LEAST ONE WEEK PRIOR TO FINAL INSPECTIONS. Parking & Landscaping Framing -7. 11 ,�,c Insulation Plumbing Drywall Screw Mechanical FINALS Electrical Plumbing Mechanical Roof Building Final �� N Fire Department R.O.W & Drainage INSPECTIONS FOR PLANNING & ZONING, FIRE AND PUBLICE WORKS SHOULD BE CALLED AT LEAST ONE WEEK PRIOR TO FINAL INSPECTIONS. Parking & Landscaping "NOTE: ALL ITEMS MUST BE COMPLETED AND APPROVED BY PLANNING AND ZONING, BUILDING AND PUBLIC WORKS BEFORE A CERTIFICATE OF OCCUPANCY /S ISSUED. FINAL INSPECTION BY THE BUILDING DIVISION DOES NOT CONSTITUTEAUTHORIZATION OF A CERTIFICATE OF OCCUPANCY NOR PERMISSION FOR OCCUPANCY. OCCUPANCY NOT PERMITTED UNTIL CERTIFICATE OF OCCUPANCY IS ISSUED PROTECT THIS CARD FROM THE WEATHER ♦ i, A i CITY OF WHEAT RIDGE Building Inspection Division r (303) 234 -5933 Inspection line (303) 235 -2855 Office • (303) 237 -8929 Fax INSPECTION NOTICE N . A Inspection Type: L; i Job Address: q q gC) �i � v S F. Permit Number: 10C 40 4 ❑ No one available for inspection: Time _L1 L 4km;PM Re- Inspection required: Yes No When corrections have been made, call for re - lns�, ct/ n at ;303 r, Date: "� " �l Inspector: DO NOT REMOVE THIS NOTICE ♦ i CITY OF WHEAT RIDGE Building Inspection Division (303) 234 -5933 Inspection line (303) 235 -2855 Office • (303) 237 -8929 Fax INSPECTION NOTICE Inspection Type: < t Pc % c 4 L Job Address: Permit Number: ' / 1 0 OCj ,-Z ❑• No one available for inspection: Time AM /PM Re- Inspection required: Yes No When corrections have been made, call for re- inspection at 303 234 -5933 Date: K"e_A/// jEyZ DO NOT REMOVE THIS NOTICE A: CITY OF WHEAT RID Building Inspection Di% (303) 235 -2855 Office Inspection Type Mfwg r Job Address VFgiP A ,W � r x�, ry V Permit Number f /4t700 ' ❑ No one available for inspection: Time d, 4f `AMPM DICE t' CITY OF WHEAT RIDGE Budding Inspection Division (303) 234 -5933 Inspection line (303) 235 -2855 Office;' (303) 237 -8929 Fax INSPECTION NOTICE Inspection Type 6efm 1 ,9AZ_ Job Address Y9 fir' Permit Number /I &F f 1 P � 7 - sr' ✓€ s.,s ll < S�eLIAe_0 A7-1 !A1X a 7 4­9P 7 ❑ No one available for inspection: Time x Mt r Re- Inspection required: No When corrections have been made, call for re-inspection at 303 - 234 -5933 Date: 1fz! 1 Inspector: - DO NOT REMOVE THIS NOTICE Inspection Type :k�L Job Address Z?9'0 Permit Number 1Pr n ❑ No one available for inspection: Time ,//,'.TV ( ' PM Re- Inspection required: Q­e No *When corrections have been made, call for re- inspection at 303- 2345933 Date: Inspecto DO NOT REMOVE THIS NOTICE " ' City of Wheat Ridge Commercial Electric PERMIT - 110088 PERMIT NO: 110088 ISSUED: 01/28/2011 JOB ADDRESS: 4980 Kipling St Unit 4 EXPIRES: 01/28/2012 DESCRIPTION: Add 4 oultets and 1 switch * ** CONTACTS * ** owner Edward Jones sub 303/424 -4374 Mark Bradley 01 -8594 Bradley Electric, Inc. ** PARCEL INFO ** ZONE CODE: UA SUBDIVISION: UA USE: UA BLOCK /LOT## : 0/ ** FEE SUMMARY ** ESTIMATED PROJECT VALUATION: 400.00 FEES ? Permit Fee 26.50 L Total Valuation .00 Use Tax 7.20 0 ** TOTAL ** 33.70 Conditions: Must comply w/ 2006 IBC & 2005 NEC. Subject to field inspections. I, by my signature, do hereby attest that the work to be performed shall comply with all accompanying approved plans and specifications, applicable building codes, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with this permit. I further attest that I am legally authorized to include all entities named within this document as parties to the work to be performed and that all work to be performed is disclosed in this document and /or its' accompanying approved plans and specifications. Signature of OWNER or CONTRACTOR (Circle one) Date 1. This permit was issued based on the information provided in the permit application and accompanying plans and specifications and is subject to the compliance with those documents, and all applicable statutes, ordinances, .regulations, policies and procedures. 2. This permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and received prior to the date of expiration. An extension of no more than 180 days made be granted at the discretion of the Chief Building Official and may be subject to a fee equal to one- half of the original permit fee. 3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard requirements, fees and procedures for approval of any new permit. Re- issuance or extension of expired permits is at the sole discretion of the Chief Building Official and is not guaranteed. 4. No work of any manner shall be performed that shall results in a change of the natural flow of water without prior and specific approval. S. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all required inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services Division. 6. The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, any violation of any provision of any applicable code or any ordinance or regulation of this jurisdiction. Approval of work is subject to fieldsnsdec Signature Offical INSPECTION REQUEST LINE: (303)234 -5933 BUILDING OFFICE: (303)235 -2855 REQUESTS MUST BE MADE BY 3PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. COMMUNITY DEVELOPMENT ° Building & Inspection Services Division 7500 W. 29 Ave., Wheat Ridge, CO 80033 Office: 303 - 235 -2855 * Fax: 303 - 237 -8929 Inspection Line: 303- 234 -5933 Ct f COMMUNITY DEVELOPMENT ° Building & Inspection Services Division 7500 W. 29 Ave., Wheat Ridge, CO 80033 Office: 303 - 235 -2855 * Fax: 303 - 237 -8929 Inspection Line: 303- 234 -5933 Building Permit Application Property Pidciesss ` ��� t�� z 1 i{ P. Property Owner (please print) �q PJn ti j Phone: Mailing Address: (if different than property address) Address: City, State, Zip: p Contractor: d7 r��� i ��r G �i c_ �n, Contractors City License #: 2 Phone:3 0-7 y2 `/ y27 'l Subcontract= -ate LL Plumbing: Mechanical City License # City License # City License # Des�ri // ntits"n�fiwork»b 1. A Ofr%f Contract Value;.y �- Swir lG� $ x(34 Review Fee (due at time of submittal): Squares BTU's Gallons Amps Sq Ft. $ OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application me accurate and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown and allegations made are accurate;. that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance with applicable City of Wheat Ridge codes and ordinances for work under any permit issued based on this application; that am the legal owner or have been authorized by the legal owner of the property to perform the described work - and am also authorized by the legal owner of any entity included on this application to list that entity on this application. CIRCLEONE: (OWNER) t (CONTRACT�O / R) or (AUTHORIZED REPRESENTATIVE) of (OWNER) (CONTRACTOR) PRINT NAME: ` c�'r X r4(N /�L y SIGNATURE:. � CVV DATE: Z g" / /1 Wi > Fltt�; Bldg Valuation: $ _ City of Wheat Ridge ►/ Comm. Tenant Finish PERMIT - 110008 PERMIT NO: 110008 ISSUED: 01/04/2011 JOB ADDRESS: 4980 KIPLING ST Suite #4 EXPIRES: 01/04/2012 DESCRIPTION: Install new walls, hang drywall,new door, 4 outlets * ** CONTACTS * ** owner 314/515 -2000 Edward Jones - go 303/431 -1729 Craig Wilpolt 08 -0269 Creative Construction sub 303/424 -4374 Mark Bradley 01 -8594 Bradley Electric, Inc. ** PARCEL INFO ** ZONE CODE: UA USE: UA SUBDIVISION: 0041 ': BLOCK /LOT #: 0/ ** FEE SUMMARY ** Permit Fee Plan Review Fee Total Valuation Use Tax ** TOTAL ** ESTIMATED PROJECT VALUATION: FEES 93.35 60.6 41.40 195.43 2,300.00 �YJUI��r'J Conditions: JZ: Approved per plans and red -line notes on plans. Must comply with 2006 IBC, 2005 NEC, and all applicable City of Wheat Ridge Municipal Codes. Subject to ._ inspections. I, by my signature, do hereby attest that the work to be performed shall comply with all accompanying approved plans and specifications, applicable building codes, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with this permit. I further attest that I am legally authorized to include all entities named within this document as parties to the work to be performed and that all work to be performed is disclosed in this do ment and /or its' acc mp ying app owed plans and specifications. Signature of OWNER or CONTRACTOR (Circle one) Date 1. This permit was issued based on the information provided in the permit application and accompanying plans and specifications and is subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures. 2. This permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and received prior to the date of expiration. An extension of no more than 150 days made be granted at the discretion of the Chief Building Official and may be subject to a fee equal to one- half of the original permit fee. 3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard requirements, fees and procedures for approval of any new permit. Re- issuance or extension of expired permits is at the sole discretion of the Chief Building Official and is not guaranteed. 4. No work of any manner shall be performed that shall results in a change of the natural flow of water without prior and specific approval. 5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all required inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services Division. 6. The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, any violation of any provision of any applicable code or any ordinance or regulation of this jurisdiction. Approval of work is subject to field inspectio Signature of ilding Offical Date INSPECT N REQUEST LINE: (303)234 -5933 BUILDING OFFICE: (303)235 -2855 REQUESTS MUST BE MADE BY 3PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. v City of hi6 t (Agle Date: �� I�' l�201 j. MUNITY DEVELOPMENT Plan # Building &Inspection Services Division Permit # 7500 W. 29 t Ave., Wheat Ridge, CO 80033 Office: 303 -235 -2855 * Fax: 303 - 237 -8929 Inspection Line: 303 - 234 -5933 Building Permit Application PropertyAddress; YY60 ;&G Property Owner (please print) Phone: : ZY g ©/� j /('�% > �� , Mailing Address: (if different than property address) Address: City, State, Zip: Contractor: t��l�<a�>•t'�L��. c'Y='- >�i"'1L�i)L'? � ��T(�I��'7 Contractors City License #: ©''�j —Q'� 9 Phone:�7 Sub�ontract�r§ Electrical: Plumbing: Mechanical: � a City License # City License# City License # Uescrlbtlon?of Itiwork & d -to J "n 115 r N trf ad Contract Value: l{ cxit�ets $ �3oo.on 0 Review Fee (due at time of submittal): Squares BTU's Gallons Amps Sq Ft. OWNER /CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown and allegations made are accurate;. that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance with applicable City of Wheat Ridge codes and ordinances for work under any permit issued based on this application; that I am the legal owner or have been authorized by the legal owner of the property to perform the described work and am also authorized by the legal owner of any entity included on this application to list that entity on this application. CIRCLEONE: (OWNER) CONTRACT ar (AUTHORMEDREPRESENTATIVE) of (OWNER) (CONTRACTOR) PRINT NAME: C , 6tl 44/ � (Q /]� SIGNATURE: C' zwek 6 DATE: I' 1" 1 .✓ SfY �' a- it ! n r if '" / S fir. FIRE pEPARTNIENT ❑ applot(ed w/ comments ❑disapproved 'O,yto review rewired Bldg Valuation $ �3 6� r CITY OF WH When corrections n ♦ ♦ CITY OF WHEAT RIDGE Building Inspection Division (303) 234 -5933 Inspection line (303) 235 -2855 Office • (303) 235 -2857 Fax INSPECTION NOTICE Inspection Type: Job Address: Permit Number: ar9ipS� ❑ No one available for inspection: Time : sa AM /T) Re- Inspection required: Yes (s o When corrections have been made, call for re- inspection at 303- 234 -5933 Date: ® /3 /ru Inspector: i DO NOT REMOVE THIS NOTICE • CITY OF WHEAT RIDGE Building Inspection bivision (303) 234 -5933 Inspection line (303) 235 -2855 Office ` (303) 237 -8929 Fax INSPECTION NOTICE Inspection Type Job Address 1/9 1 Permit Number s� t X55 " r /,7 s r L P "S r 7`isa✓�r f„�/f /aee° 311 �,C- 9�n�R7iP�rG/ M ?d��l�y' ,f�¢ ser,J 5'i rvw`c�aa✓ i7,.¢- s�s?,�C�3J1ssx �:{� 1; o No one available for inspection: Time i lv AM /PM Re- Inspection required: Cl e: ; 1 No g; When corrections have been made, call for � re-inspection at 303- 234 -5933 Vs, Date 9'//0 Inspector: c s DO NOT REMOVE THIS NOTICE ►r CITY OF WHEAT RIDGE Building Inspection Division f (303) 234 -5933 Inspection line (303) 235 -2855 Office ' (303) 237 -8929 Fax INSPECTION NOTICE Inspection Typ Job Address Y91Fq etPe� S'r Permit Number / V I 9 /jS6e' iP ,mot X �f� 4' City of Wheat Ridge r 40001'r, Commercial Sign PERMIT - 102054 PERMIT NO: 102054 ISSUED: 08/27/2010 JOB ADDRESS: 4980 Kipling St Ste 5 EXPIRES: 08/27/2011 DESCRIPTION: Raceway sign to face of building * ** CONTACTS * ** ten 720/385 -3776 Lori Thompson sub 303/683 -1340 Rick Fagan 10 -0262 Jet Fast Services (JFS) ** PARCEL INFO ** ZONE CODE: UA SUBDIVISION: 0041 USE: UA BLOCK /LOT #: 0/ ** FEE SUMMARY ** ESTIMATED PROJECT VALUATION: 1,050.00 FEES Permit Fee 46.90 Plan Review Fee 30.49 Total Valuation .00 ,--_ Use Tax 18 90 ** TOTAL ** 96.29 Conditions: SS: Approved. Wall sign may be maximum of 20 sq ft. Zoned C -1. Subject to field inspection. MV: Approved. Subject to field inspection. Must comply with 2005 NEC, 2006 IBC, and all applicable City of Wheat Ridge Municipal Codes. I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application that I assume full responsibility for compliance with the Wheat Ridge Building Code (I.B.C) and all other applicab at Ridge Ordinances, for work under this permit. Plans subject to field inspection. -rte ... Owl /F Signature of contract l er date 1. This permit was issued in accordance with the provisions set forth in your application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Codes of Wheat Ridge, Colorado or any other applicable ordinances of the City. 2. This permit shall expire 180 days from the issue date. Requests for an extension must be received prior to expiration date. An extension may be granted at the discretion of the Building Official. 3. If this permit expires, a new permit may be acquired for a fee of one -half the amount normally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes have been or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. 4. No work of any manner shall be done that will change the natural flow of water causing a drainage problem. 5. Contractor shall notify the Building Inspector twenty -four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceeding with successive phases of the job. 6. The issuance of a permit or the approval of drawings and specifications shall not be construed to be a permit for, nor an approval of, an violation of the provisions of the building codes or any other ordinance, law, rule or regulation. All plan r vi i object to field inspections. Signature of hie uilding Official -date INSPECT N REQUEST LINE: (303)234 -5933 BUILDING OFFICE: (303)235 -2855 REQUESTS MUST BE MADE BY 3PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. 5S k `> City of `f" Wh6at1 ,,Ale COMMUNITY DEVELOPMENT Building & Inspection Services Division 7500 W. 2e Ave., Wheat Ridge, CO 80033 Office: 303 -235 - 2855 " Fax: 303 -237 -8929 Inspection Line: 303 - 234 -5933 Building Permit Application Date: - 6( 1 I I v Plan # Permit # � D E�.�.!.OFkt'I.Y%Q1;4 a,_..: 990o Vs ,- Property Owner (please prino j, p a %/ 'J 1 o,i„ nseau Phone: 7 ZM" 3g5 - 3T ( Mailing Address: (Y different than property address) A dd re ss: SARA -P A5 A6-,/ City, State, Zip: M � U -0- Electrical: City License # Plumbing: City License # 17eis - rA II 2ACe.a�g.y�Ia I i1ce�F t3 .lc ror as rt55 Mechanical: City License # Contract Value: $ Review Fee (due at time of submittal): quares BTU's Gallons _ Amps Sq Ft I OWNERICONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance with applicable City of Wheat Ridge codes and ordinances for work under any permit issued based on this application; that I am the legal owner or have been authorized by the legal owner of the property to perform the described work and am also authorized by the legal owner of any entity included on this application to list that entity on this application, CIRCLEONE: (OWNER) (CONTRACTOR) ar (AUTHORIZED REPRESENTATIVE) of (OWNER) (CONTRACTOR) PRINT NA117E: K •'i.k r �.xw SIGNATURE: !K % DATE: $ jct t Bldg Valuation: FHSTSIGNS: Online Proofing System FASTSIMS• hup:fl -fasts igms.corWbasic. asWCG UID= ee074e S t-c I66- 4f41 -975c. :anLdb 239 2388AFbiam ESaPI Pnep wdrar[lelaanav:lort Taompm PIeaC a,elxartb bwc aPP roedbet4 eiPYar: elaONin4 N Pmo"Tw an0 sudndpw Ieamatk teals alyau srSat t3 i y ybr (3W)761-7217 eBndflYM1an.9aCiansotml73a o �. Adrem 5]24SBoadKw FAdk- w4Cciw6b9011; ©� lr g t } {O t I 1-51 I 0Y i �� wttESr,p� a C oto Wheat Ridge Bui ing Department ved OTi � BUILD 010 OFFICIAL ATE Validity of permit. The Issuance of a permit or approval of plans, speciliehllm and computation shall not be a permit for, or an approval of, any viold" to any of the provisions of the building code or of any City o rd in anc4 Palmitspresumingtogivesuthodlyto violate or cancel the previsions dot ` z Building codes or othavordinances of the City shall not be vdi I off 8/1712010 8:39 At Eaf M..ti'MK dNd.8Vp1A IEPfhbM M11M {{��ryII awr+MN - •.+r.+ln• rrrr r.l..H r..e ria4:8/la' Oapa LYA 8aJ1M1lkglrp r.11 ao: Mll. •.e..r wlw se.:::..:, dl S4.GdbGerrw:8d vrlsa: How: r�lto�l 9MM"; IN"TVIM! Nat". ©� lr g t } {O t I 1-51 I 0Y i �� wttESr,p� a C oto Wheat Ridge Bui ing Department ved OTi � BUILD 010 OFFICIAL ATE Validity of permit. The Issuance of a permit or approval of plans, speciliehllm and computation shall not be a permit for, or an approval of, any viold" to any of the provisions of the building code or of any City o rd in anc4 Palmitspresumingtogivesuthodlyto violate or cancel the previsions dot ` z Building codes or othavordinances of the City shall not be vdi I off 8/1712010 8:39 At FASTSIGNS: Online proofing System FAST - hup: ll wp.£ asrsigu, cojWbasic .aspx ?CGUID--ee074eSI -cI66 4W- 975c... :N1LQ: 238 ZwobFbknL tdlTlnmpmn Proa"Tod am audnd�n1R 1e910aY a6U5 aaywrt ear5at M:Ym (983)7$1 -7212 Mam11rnvw.9abiannmm7238 amvrhm. aNW18r: iddmm S1t45aMadWe Fj,rky Cdvn4D 801x3 I orl �0 q' WNe�It. ttEolge 8u i , q Depaftirlerlt YaNdgyoPpanwlt. The' i6i0aneootaprtMtorapdr�lirNafpbn �a slbixmObblaals shop ow be 6 k for, orsa 3ppmw of, OW VIOMM'b MY of die Oroylsi mofthebugdingcodaoraP4ftpCMyordinaiea, I�tlafbOmlaMng o9ma*&*,Ioriolkawe flaprorhlolas -�tlM k ,_:�dldMg'PAdesoi dtlaCilyrwther 8/1772010 8:39 AM e r orr r,:r.:se aq ae:o.. a.oaa.mr xnwr dn.r+.ur....�.m rnrr•wna�a n,orr: arr aup ux aeao-u: MMo t� cw: r MNu a n::.r ss m. Yo/R: Wmame: AW TTM: 1Mttl: I orl �0 q' WNe�It. ttEolge 8u i , q Depaftirlerlt YaNdgyoPpanwlt. The' i6i0aneootaprtMtorapdr�lirNafpbn �a slbixmObblaals shop ow be 6 k for, orsa 3ppmw of, OW VIOMM'b MY of die Oroylsi mofthebugdingcodaoraP4ftpCMyordinaiea, I�tlafbOmlaMng o9ma*&*,Ioriolkawe flaprorhlolas -�tlM k ,_:�dldMg'PAdesoi dtlaCilyrwther 8/1772010 8:39 AM CL U) W c r- tom APPROVED Subject to Field Inspections Wheat '- Ridge Building Dept. Date: 4 Signed: S ` Plan checker 4 ) dd R 7 =6G � N T L� V UTa � o^ 0 0 0 M �E O_ wNM N �. v rn �I CO Cm ) Y � R r a��ca�c 4) Q v I A, O APPROV / BY 2 � ` Ul��nwn�1 L1 A/ DATE: 0 S comMENT: a ' �x S F MY a e 7 Page 1 of 1 Subj: Sign info for Permit Date: 8/13/2010 1:59:32 P.M. Mountain Daylight Time From: 238(aAastsigns. com To: ietfastservices(a)aol.com Hello Rick, Here's the info. for the Newport Audiology Sign in Wheat Ridge (address: 4980 Kipling Suite A -5 Wheatridge, CO 80033 (just North of 1 -70 on the West side of Kipling; between Edward Jones and the Animal Hospital)) I'll need you to pull the sign and electrical permit. Please let me know if you need anything else as they need this up by Sunday. just kidding :) Thanks again! Hopefully I'll be bringing some more work to you soon ... will be in touch. Curt Rogers FastSigns 5124 South Broadway Englewood, CO 80113 Phone 303 - 761 -7212 Fax 303 -761 -4605 www.fastsi-qns.com/238 Check out this informative video: www.fastsigns.com /innovation Tuesday, August 17, 2010 AOL: Jetfastservices Page 1 of 1 Subj: Newport sitemap Date: 8/17/2010 10:15:34 A.M. Mountain Daylight Time From: 238(5fastsig ns. com To: letfastservices(@aol.com Rick, Here's the aerial map and the sq. footage of their space in the building is 1200 sq feet appx. The length of the storefront is 20 feet. Thanks and let me know if you need anything else! Curt Rogers FastSigns 5124 South Broadway Englewood, CO 80113 Phone 303 - 761 -7212 Fax 303 - 761 -4605 www.fastsi-qns.com/238 Check out this informative video: www.fastsigns.com /innovation Tuesday, August 17, 2010 AOL: Jetfastservices Wall Sian Calculation Sheet You must complete this sheet and include it in the submittal package for any new wall signs. You will also need to create a site plan and a detail sheet of the signage. Project Address: Contractor. L, r!S) J'ei r;4 sT sue al ce-S You are allowed i square r ®6t of signage for every i linear foot of waii to which you are attaching a sign. All wall siqns must be adjacent to a street or major interior drive. yes Steq 1: vteasure the length of the wall(s) where you are atttachinq the sign: Wall i - 2® feet xNall 2 - vet 'Alai! 3 - feet Stec 2: 1 he lenoth of the wall is the al -Wahle square rootage for the s=o -- I Cw i� s Jam• ft�L �p.�y�rk.� I i i I k � t ` i f E 7 � t Rr Im 0 RL (D 9 I T ;D CL V -n 10 a: 0 m 0 CD 0 04V \w C`7) Plan checker Page 1 of 1 Subj: Sign info for Permit Date: 8/13/2010 1:59:32 P.M. Mountain Daylight Time From: 238Qfastsians. com To: ietfastservicesaaol.com Hello Rick, Here's the info. for the Newport Audiology Sign in Wheat Ridge (address: 4980 Kipling Suite A -5 Wheatridge, CO 80033 Oust North of 1 -70 on the West side of Kipling; between Edward Jones and the Animal Hospital)) I'll need you to pull the sign and electrical permit. Please let me know if you need anything else as they need this up by Sunday. just kidding :) Thanks again! Hopefully I'll be bringing some more work to you soon ... will be in touch. Curt Rogers FastSigns 5124 South Broadway Englewood, CO 80113 Phone 303 - 761 -7212 Fax 303 - 761 -4605 www.fastsians.Com/238 Check out this informative video: www.fastsicgns.com /innovation Tuesday. August 17- 2010 AOL: 7etfa.stservices Page 1 of 1 Subj: Newport sitemap Date: 8/17/2010 10:15:34 A.M. Mountain Daylight Time From: 238na fastsigns.com To: jetfastservices(@aol.com Rick, Here's the aerial map and the sq. footage of their space in the building is 1200 sq feet appx. The length of the storefront is 20 feet. Thanks and let me know if you need anything else! Curt Rogers FastSigns 5124 South Broadway Englewood, CO 80113 Phone 303 - 761 -7212 Fax 303 - 761 -4605 vvErvww.fastsiq ns.com /238 Check out this informative video: www.fastsicins.com /innovation Wall Sian Calculation Sheet You must complete this sheet and include it in the submittal package for any new wall signs. You will also need to create a site plan and a detail sheet of the signage. Project Address: AT90 (C.; 33 _ Contractor: � > �5� ) p s i SQr ✓ ! "�S You are allowed P squa font of signage for every "i Unear foot of wall to whi Gil - you are attaching a sign. All wall signs must be adjacent to a street or major interior drive.S to $ : Mfeasure the lei � th of the walls) where you care attcs€.: aina the s . -n: :`tall �® - feet lk'alt ` f'—'et '.. °a :. 3eei €€e i_ .€�ti o wra-kl [ s; the — €fowaW—me Suuare £y* - m�e the __�-- s:$� =s�.. all 3 au Me S l a nai' e - � © G uaiv fuaT v.�..tE .even 53 UM +?E = +33 +ev «.npt ♦ i CITY OF WHEAT RIDGE Building Inspection Division I r (303) 234 -5933 Inspection line r (303) 235 -2855 Office • (303) 237 -8929 Fax INSPECTION NOTICE `Inspection Type: 81.r Job Address: V722 A Z i nerd <' t/" Permit Number: Tc 2 r T✓ I}n.�A 7a A r�Si Fss �lc�n ss_ J3�s�rf >4G'vFr� AlleL 3o3- V3S- 9 ❑ No one available for inspection: Time r`A PM Re Inspection required No 'When corrections have been made, calli for re inspection at 303 - 234 - 5933 Date: 4Zzr 10 Inspecto DO NOT REMOVE THIS NOTICE f; NSPECTIOD INSPECTION LINE: Inspections will not be made unless this Call by 3:00 PM to receive inspectio s r i RECORD Occupancy /Type 03) 234 -5933 and is posted on the building site the following business day.` INSREICTOR `MUST SIGN ALL SPACES PERTAINING TO THIS JOB FOUNDATION INSPECTIONS DATE : INSPECTOR INITIALS COMMENTS:. Footings /Caissons Stemwall / (CEG).Concrete Encased Ground Reinforcing or Monolithic Weatherproof / French Drain Sewer Service Lines Water' Service. Lines ROUGHS Sheathing Lath /.Wall tie Mid Roof Electrical Service Rough.. Electric Rough Plumbing Gas Piping Rough .Mechanical ' '- ABOVE INSPECTIONS TO BE SIGNED PRIOR TO PROCEEDING Framing Insulation Dr/wallScrew FINALS` Electrical J Plumbing Mechanical Roof Building ,Final Fire Department R.O. W & Drainage INSPECTIONS FOR PLANNING & ZONING, FIRE AND PUBLIC WORKS SHOULD BE CALLED AT LEAST ONE WEEK PRIOR TO FINAL INSPECTIONS. Parking & Landscaping ** NOTE. ALL ITEMS MUST BE COMPLETED. AND APPROVED BY PLANNING AND ZONING, . BUILDING AND PUBLIC WORKS BEFORE A CERTIFICATE OF OCCUPANCY IS ISSUED. FINAL INSPECTION BY THE BUILDING DIVISION DOES NOT CONSTITUTE AUTHORIZATION OFA CERTIFICATE OF OCCUPANCY 'NOR PERMISSION FOR OCCUPANCY. OCCUPANCY NOT PERMITTED UNTIL CERTIFICATE OF OCCUPANCY IS ISSUED PROTECT THIS CARD FROM THE -WEATHER- ♦ A e CITY OF WHEAT RIDGE Building Inspection Division (303) 234 -5933 Inspection line (303) 235 -2855 Office • (303) 237 -8929 Fax INSPECTION NOTICE Inspection Type: 5 o N I Job Address: y99 i, m1 Permit Number: l�f ✓> /< °.r !Y' .=�✓ �,L �2 ��GLS L" it �i I j I ❑ No one available for inspection: Time i (AM M Re- Inspection required: Yes No *When corrections have been made, call for re- inspection at 303234 - 5933 Date: Inspector: ®O NOT REMOVE THIS NOTICE COMMUNITY DEVELOPMENT DEPARTMENT Building Permit Number: G" 19c l of wnegr BUILDING INSPECTION LINE - 303-234-5933 Date: CITY OF WHEAT RIDGE ]~7 I 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80033 - (303-235-2855) APPLICATION Property Owner Property Address: 419g-6 Kll~l 1C1 51 ij,-JiT 4-3 Phone: Contractor License No.: 018(.22- Company: S2T_. CIEZJ p Ir Phone: 31g77 3a~ OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT _ 1 hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application and that 1 assume full responsibility for compliance with the Wheat Ridge Building Code (U.B.C) and all other applicable Wheat Ridge Ordinances, rwo undert sp (OWNER)(CONTRACTOR): SIGN 2 DATE `/-30` (OWNER)(CONTRACTOR):PRINTED DATE Value:$ Permit Fee:$ Plan Review Fee:$ e Tax j Total:$ Description: R6 . S Z cSe_,Zv/CG~ Gc/1 ` rkAC~ 4A.) Cv$T/ vfo /C c~ q r, /U'cu o?C0 4- &Z 5~2vac ' Sq.Ft. added Expiration Date: Expiration Date: Expiration Date: Approval: Approval: Approval: (1) This permit was issued in accordance with the provisions set forth in your application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Codes of Wheat Ridge, Colorado or any other applicable ordinances of the City. (2) This permit shall expire if (A) the work authorized is not commenced within sixty (60) days from issue date or (B) the building. authorized is suspended or abandoned for a period of 120 days. (3) If this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1)year. If changes have been or if suspension or abandonment exceeds one(1)year, full fees shall be paid for anew permit (4) No work of any manner shall be done that will change the natural flow of water causing a drainage problem. (5) Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceeding with successive phases of the job. (6) The issuance of a permit or the approval of drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation of the provisions of the building codes or any other ordinance, law, rule or regulation.. Chief Building Official Electrical License No: Plumbing License No: Mechanical License No: Company: Company: Company: .G,EPTIFI:CATE'OF OCCUPANCY C -ty of Wheat, Ridge 7500 W 2.9th'~~ve wheatRidae;CO 50033 n- c'7 Edavtions NQ change shill be made rn;t e USE,of. 2003ICC%2005, NEC,, this, building,-asthovt prior notzce pp, 200`3 SCE/. 002 NEC and 'a new C rt'i scat of Qc q ti1,14, 1957 UBCfd002 £rom the, City 4 W1Ya}t Ri~lge, Sr ,Y!{r~kles' Sy ~m ~ r C 3.' i d~t~g ~iaspeCtbr '%Zofyd i'nis atd lit IE C E, M 97 ;POSSE g FRG~N3 DOQiE QF D , ~~CONINIE,23C3AT; OC~~~~1IV~,IES~~ ~ ` 01/30/09 08:27:13 City of Wheat Ridge Page 1 bp701-1s PERMIT INFORMATION - 081288 mmackey PERMIT INFORMATION: Permit#: 081288 Address: 4980 KIPLING ST Permit Type: Comm. Tenant Finish Parcel Cd: 39-153-14-010 Permit Dt: 11/04/2008 OWNER: Expires: 05/03/2009 Address: 2000 S Colorado Blvd #800 City/St/Zip: Denver CO 80222 LAND PARCEL INFORMATION: Zone Cd: Unassigned DU: 1 SetBa cks-Front: 0.0 Recut Use: Unassigned Last Zone Dt: Left: 0.0 Subdivision: KIPLING 5000 BUS PK Annex Dt: Right: 0.0 Cent Type: Miscellaneous Lot: Block No: 0 Back: 0.0 Legal: JOB DESCRIPTION: Interior remodel of Veterin ary Clinic FEES QTY DUE PAID: Permit Fee 117,168.80 1,422 .99 1,422.99 Plan Review Fee .00 662 .32 662.32 Plan Review Addtiona 262.62 924 .94 924.94 Total Valuation 117,168.80 .00 .00 Use Tax 117,168.80 2,109 .04 2,109.04 - 5,119 .29 5,119.29 CONTACTS: owner Bunton Commercial Property 2000 S Colorado Blvd #800 Denver CO 80222 3037583131 go CIA. EJCM, LLC. T.Clark/P.Gillespie 111 Kalamath Street Denver, CO 802231436 3035735678 sub CLA BENEFIEL ELECTRIC, INC. Harry D.Benefiel 7685 ESTES ST. ARVADA, CO 80005 3034220430 sub CIS Wray Sheet Metal, Inc. 5495 Marion Street Denver, CO 80216 3032921116 sub CL8 Merkel's Plumbing, Inc. Allen Merkel 6377 So. Wolff Ct Littleton, CO 80123 3037970128 PARCEL INFORMATION: 10 Structure Type 101 20 Year Built 1984 30 Property Type COMMR PERMIT CONDITIONS: KC: Approved per plans and notes and fire department requirements. JH: Fence cannot exceed 6' in height Must comply w/ 2003 IBC & 2005 NEC. APPROVALS: REQUIRED INSPECTIONS STATUS: PERMIT NOTES: 11/04/08 JH: OK - fence on east elevation cannot exceed 6' in height. 11/04/08 CREATED FROM APPL# 08-0393 10/20/08 Given to JS for review INSPECTION INFORMATION: # TYPE CONTR# CALLED CNCL WHO RIO DT INS DT STATUS 1 PRI:Plumbing Rough Insp. 01-9549 12/02/08 no KC 12/03/08 12/03/08 COMPLETE 2 FRI:Framing Rough Insp. 01-7826 12/05/08 no KC 12/08/08 12/08/08 INCOMPLETE 3 ERI:Electrical Rough Ins 02-1591 12/05/08 no KC 12/08/08 12/08/08 COMPLETE 01/30/09 08:27:13 City of Wheat Ridge Page 2 bp701-15 PERMIT INFORMATION - 081288 mmackey 4 EDG: Electrical Ondergrd. 02-1591 12/05/08 no KC 12/08/08 12/08/08 COMPLETE 5 PRI: Plumbing Rough Insp. 01-9549 12/10/08 no KC 12/11/08 12/11/08 PARTIAL 6 fri: Framing Rough Insp. 01-7826 12/10/08 no kc 12/11/08 12/11/08 COMPLETE 7 dws: Drywall screw/nail 01-7826 12/12/08 no kc 12/15/08 12/15/08 COMPLETE 8 eri: Electrical Rough Ins 02-1591 12/18/08 no my 12/18/08 12/18/08 COMPLETE 9 MRI: Mechanical Rough Ins 01-8977 12/19/08 no KC 12/22/08 12/22/08 INCOMPLETE 10 PRI: Plumbing Rough Insp. 01-9549 12/19/06 no KC 12/22/08 12/22/08 INCOMPLETE 11 PRI: Plumbing Rough Insp. 01-9549 12/23/08 no KC 12/24/08 12/24/08 INCOMPLETE 12 MRI: Mechanical Rough Ins 01-8977 12/23/08 no KC 12/24/08 12/24/08 COMPLETE 13 PRI: Plumbing Rough Insp. 01-9549 12/29/08 no KC 12/30/08 12/30/08 INCOMPLETE 14 PRI: Plumbing Rough Insp. 01-9549 01/07/09 no CCI 01/08/09 01/08/09 INCOMPLETE 15 PRI: Plumbing Rough Insp. 01-9549 01/08/09 no CCI 01/09/09 01/09/09 COMPLETE 16 EFI: Electrical Final Ins 02-1591 01/13/09 no MV 01/14/09 01/14/09 INCOMPLETE 17 ELC: Elect. Inspection 02-1591 01/15/09 no MV 01/15/09 01/15/09 COMPLETE 18 EMR : Elec Service - EMR 02-1591 01/15/09 no MV 01/15/09 01/15/09 COMPLETE 19 EFI: Electrical Final Ins 02-1591 01/20/09 no MV 01/21/09 01/21/09 COMPLETE 20 PFI: Plumbing Final Ins, 01-9549 01/22/09 no KC 01/23/09 01/23/09 INCOMPLETE 21 MFI: Mechanical Final 01-8977 01/22/09 no KC 01/23/09 01/23/09 COMPLETE 22 BFI: BUilding Final Insp 01-7826 01/22/09 no KC 01/23/09 01/23/09 INCOMPLETE 23 FRA: Framing Inspection 01-7826 01/26/09 no KC 01/27/09 01/27/09 INCOMPLETE 24 PFI: Plumbing Final Insp 01-9549 01/26/09 no KC 01/27/09 01/27/09 COMPLETE 25 LFI: Landscaping Final 01-7826 01/26/09 no aH 01/29/09 26 BFI: Building Final Insp 01-7826 01/29/09 no KC 01/29/09 01/29/09 COMPLETE ~V M M O ~O 00 0 U.) -0 U.) a M °O O _ Ch O M N V N ce) 00 O ~ CO b a s 3 .Q d C 0 a w O a N V t a m c m E 0 c .y O d CL a c a 0 d a C L W d L d L v O 3 O N U C w Q U U O N T H O N Z d a N d a,o 0 32 .Q'5 0 E- 0 m 8 m F.U. O W w = U p 2 1 U o Z a q z z t - w a J W p a Q a n. ch J O J z a (D D F 0 o a z a 2 O J U W O c z C Cl) LL 2 o 8 Z : E m Ft G' 3 U. 0 D ~ C O s 3 w _ v o L LM c o L E t L U v w g s' N ~ Z Q x 0 i R . C l6 w 0 d ~ ~ m t Fy 4 0 W ,Q _V LL V Z D W L6 a 0 Z V a D V X X W N U) N Z IL V v ui W W U. v H CLEAR CREEK ANIMAL HOSPITAL Anna Lindsey, DVM 4980 Kipling St. Ste A-6 Wheat Ridge, CO 80033 (303) 514-0525 To Whom It May Concern, A Due to financial constraints, we will not be purchasing a freezer or building a deck at the rear of 4980 Kipling Street, Wheat Ridge, CO 80033. If you have any questions, feel free to contact me at (303) 514-0525. Thank you, Anna Lindsey i ~ CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office ' (303) 235-2857 Fax INSPECTION NOTICE Inspection Type:~,~et~° f94Lefla ess'G-,t 91Psyp. Job Address/Permit Number: X7,1'0 + i oLs~G 3~r, t5;91.2 ®s`t--• e < - <s'IS~'-"'-'a "2~" r./ s=» 77 ~i. 7~s~-a • ~l n 901 ser"Yf7 Tom'' 1dPY3 721; -f .4~L°f sib, f i:S 1 it 9:7" D No one available for inspection: Time AM/PM Re-Inspection required: es No When corrections have been made, call for re-inspection at 303-2345933 Date: Inspect DO NOT REMOVE THIS NOTICE Y S ' 41 CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line 3 (303) 235-2855 Office ` (303) 235-2857 Fax 24'A" 1. INSPECTION NOTICE Inspection Type: 2~/~CTTZ/f,/_G ~ SS~/mod i ZA~16 27- Job Address/Permit Number: 1.*1 ❑ No one available for inspectio Re-Inspection required: Yes / When corrections have been mape, AM/PM at 303-234-5933 V Date: i 01a Inspector „ ♦~~I ~ CITY OF WHEAT RIDGE Building Inspection Division (303) 2x34-5933 Inspection line (303) 235-2855 Office ' (303) 235-2857 Fax INSPECTION NOTICE Inspection Type: ~TJ1/G97/Z<S Job Address/Permit Number: /'l~6~'~~,~ ~ ..FfS'c -G~ y SLZ✓f //JifT-i3~ y ❑ No one available for inspecti n: in, , e AM/PM Re-Inspection required: Yes No When corrections have been matle, H r re-inspection at 303-234-5933 L c Date: Inspector: I~ V DO NOT REMOVE jHNOTICE F 41 CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office - (303) 235-2857 Fax INSPECTION NOTICE Inspection Job Address/Permit Number: ❑ No one available for inspection:Jime AM/PM Re-Inspection required: Yes "When corrections have been made., Date: Inspector: DO NOT REMOV at 303-234-5933 ....`Ili CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office - (303) 235-2857 Fax INSPECTION NOTICE Inspection Type: ;F. e,< k ~ Job Address/Permit Number: 9 0 ~ r ❑ No one available for inspection: Time AM/PM Re-Inspection required: Yes vxQ_~ When corrections have been made, call for re-inspection at 303-234-5933 Date: / C99 Inspector: DO NOT REMOVE THIS NOTICE 46 , , 0 --r-~, -7, 4~a;e S`- 1 I ' ~ CITY OF WHEAT RIDGE / Building Inspection Division (303) 234-5933 Inspection line { (303) 235-2855 Office ` (303) 235-2857 F~axl INSPECTION NOTICE i Inspection Type: J~ t Job Address/Permit Number: >a. a. r `i 7 I @ S /fin P~ YP~ .°ci F?~ 6 1 `l 7 3'. -e a, ❑ No one available for inspection: Time AM/PM 1 Re-Inspection required: Q~:)No' 'When corrections have been made, call for re-inspection at 303-234-5933 1 ~ Date: Inspector: 'Al DO NOT REMOVE THIS NOTICE - ♦~~I CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office - (303) 235-2857 Fax INSPECTION NOTICE Inspection Type: ~RkivgW ~L d Job Address/Permit Number: sd 114 ,,vX c 7 ` sh`pf~gg I/Jt/ s.rr iri,J/ ! / 4 ~{a~2.7' ~•s~/~L ri nG O .i.n/ T T d/vl~lJ-rJf ~-..Qr E'S ~I~tl~f <'Tif~nJ !1.9A!¢ ~s~`I(>2 Wit? r ❑ No one available for inspection: Time °Vn AM/PM Re-Inspection required: es No When corrections have been made, call for re-inspection at 303-234-5933 Date: xa/S? Inspector: DO NOT REMOVE THIS NOTICE `114' CITY OF WHEAT RIDGE / Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office ` (303) 235-2857 Fax INSPECTION NOTICE Inspection Type: Job Address/Permit Number: lW&~ lJAJ1,PG 57-. cif'/29? ~~V JA~ Z-4 04 - Oje E ❑ No one available for inspection: Time d AM/PM Re-Inspection required: -No t When corrections have been made, call for re/-inspection at 303-234-5933 Date: 9 9 Inspector: rr L~ DO NOT REMOVE THIS NOTICE CITY OF WHEAT RIDGE `9r(303) Building Inspection Division r (303) 234-5933 inspection line 235-2855 Office ' (303) 235-2857 Far INSPECTION NOTICE Inspection Type: ssar wl c~~i2 &02 Job Address/Permit Number: - - - - - - - - - - - - - - M ❑ No one available for inspection: Time AM/PM Re-Inspection required: es:` No When corrections have been made, call for re-inspection at 303-234-5933 Date: a 14q Inspector: DO NOT REMOVE THIS NOTICE ;,V-7'-- A CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line ~JJ (303) 235-2855 Office ' (303) 235-2857 Fax INSPECTION NOTICE Inspection Type: ~Ccc T/L/~1fL - D~IZ~^~ Job Address/Permit Number: /Di rJ~ ❑ No one available for inspection: Virile AM/PM Re-Inspection required: Yes `When corrections have been made, Dater ~ ,K Inspector: DO NOT REMOb at 303-234-5933 NOTICE ~►~i ~ CITY OF WHEAT RIDGE ~ Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office - (303) 235-2857 Fax f 3 INSPECTION NOTICE f Inspection Type: Job Address/Permit Number: R/,1, t =i 1 F}} t 3 ! i 3. ❑ No one available for inspection: Time f a AM/PM Re-Inspection required: Yes No When corrections have been made, call for re-inspection at 303-234-5933 Date: _4z/z /e i 8 Inspector: i DO NOT REMOVE THIS NOTICE a CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office ' (303) 235-2857 Fax INSPECTION NOTICE Inspection Type: 4 "o-c nsQl ~ Job Address/Permit Number: V790 /lrP4a/G ST• r~S, Iz88 4~z_> A/ 7-, &(!kl /24/r _ f r24E Gt f~.~ 4S ❑ No one available for inspection: Time 9.'so AM/PM Re-Inspection required: Yes No When corrections have been made, call for/re-inspection at 303-234-5933 Date: Gx Inspector: DO NOT REMOVE THIS NOTICE r~rfs,9y/1 ~;Z,puniGS fLfc°. -r~~C City of Wheat Ridge ./9 Comm. Tenant Finish PERMIT - 081288 PERMIT NO: 081288 ISSUED: 11/04/2008 JOB ADDRESS: 4980 KIPLING ST EXPIRES: 05/03/2009 DESCRIPTION: Interior remodel of VeterinaryClinic CONTACTS owner 303/758-3131 Dunton Commercial Property gc 303/573-5678 T.Clark/P.Gillespie 01-7826 EJCM, LLC. sub 303/422-0430 Harry D.Benefiel 02-1591 BENEFIEL ELECTRIC, INC. sub 303/292-1116 01-8977 Wray Sheet Metal, Inc. sub 303/797-0128 Allen Merkel 01-9549 Merkel's Plumbing, Inc. PARCEL INFO ZONE CODE: UA USE: UA SUBDIVISION: 0041 BLOCK/LOT#: 0/ FEE SUMMARY ESTIMATED PROJECT VALUATION: 117,168.80. FEES Permit Fee 1,422.99 Plan Review Fee 662.32 Plan Review Addtiona 924.94 Total Valuation .00 Use Tax 2,109.04 TOTAL 5,119.29 6~( Conditions: KC: Approved per plans and notes and fire department requirements. JH: Fence cannot exceed 6' in height Must comply w/ 2003 IBC & 2005 NEC. I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance with the Wheat Ridge Building Code (I.B.C) and all other applicably Wlieat Ridge ordinances, for work under this permit. Plans subject to field inspection. Signature of contractor/owner date 1. This permit was issued in accordance with the provisions set forth in your application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Codes of Wheat Ridge, Colorado or any other applicable ordinances of the City. 2. This permit shall expire 180 days from the issue date. Requests for an extension must be received prior to expiration date. An extension may be granted at the discretion of the Building Official. 3. If this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes have been or if suspension or abandonment exceeds one (1) year, full tees shall be paid for a new permit. 4. No work of any manner shall be done that will change the natural flow of water causing a drainage problem. 5. Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceeding with successive phases of the job. 6. The issuance of a permit or the approval of drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation of the provisions of the building. codes or any other ordinance, law, rule or regulation. All plan review is subject to field inspections. Signature of Chief Bu' £ficial date INSPECTION RE EST LINE: (303)234-5933 BUILDING OFFICE: (303)235-2855 REQUESTS MUST BE MADE BY 3PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. pFm"~>R City of Wheat Ridge Building Division paw, .~Q •Qg' 7500 W. 29th Ave., Wheat Ridge, CO 80033 U m Office: 303-235-2855 * Fax: 303-235-2857 Plan c o Inspection Line: 303-234-5933 QD/ pCORPp PermitD Building Permit Application Property Address: LJ9$0 K14 1Xr4G Sr-. Property Owner (please print): DtAlMN l c4a ssti~ i Naeo+-j . Phone: 303 S$ • 313 ) Mailing Address: (if different than property address) Address: ~-OOfl S. CO(oGt.Alo DuL~A ~~OOfl City, State, Zip: DekP-R- , • ~D131- Contractor: I;TC ut,c-c~- /+ft1ORBu~ALR9flTRN r 30.54 } Q~~ Contractor License Q I (kiy{ Phone: 303 , S } 3 , S[Q Subcontractors: I t/D Electrical City License per- (~9 Company: JQPiP-Rd. Exp. Date: Approval: F, rk /f~(kYk11 t~ 15b Plumbing City License #:61.4 Company((~Q LIS ~~UINIW~, Exp. Date: Approval: Mechanical City License ~ ~.7 Company O " Exp. Date: Approval: g " Use of space (description): UT&uk -y Q ~ X-C Construction Value: $ -4-0 (I3o Description of work: Tn D ~~Q~ (as calculated per the Building Valuation Dam sheetl Y + W 44 Aprry E F~ Plan Review (due at time of submittal): $ Sq. Ft./L.Ft added: Squares BTU's Gallons Amps OWNERICONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance with the Wheat Ridge Building Code (I.B.C) and all other applicable Wheat Ridge Ordinances, for work under this permit. Plans subject tofieldins on CIRLCE ONE:: (OWNER)/( ONTRACTOR) r PERSONAL REPRESENTATIVE of (OWNER) (CONTRATOR) PRINT NAME: It-E~J- SIGNATURE. Date: ON DEPARTMENT USE ONLY ZONING COMMENTS: '1 j L ZoningC" 1-JA Op I- 11/1 (08- Fcor& h cantutf e-kfee G I1k ~0 Reviewer. PUBDC WORKS COMMENTS: Reviewer. nn L/f/fJt~,✓T~SjslH~odds'.EG$C~l BUILDING DEPARTMENT CO ENTS OCC Reviewer. s6/~3al~oA~ /IE,uiJnyE ?o,~idG ~I9dSt's'^TS FIRE DEPARTME approved wl comments ❑ disapproved ❑ no review required Bldg Valuation $ 0 July 14,2008 Building Division Community Development 7500 W. 29th Avenue Wheat Ridge CO 80033 Re: Sign Permit Edward Jones Investments 4980 Kipling, Suite 4 Dear Sirs: Can you please mail the approved sign permit, referenced above, back to us in the self- addressed stamped envelop. We paid for the permit already. Thank you. Sincerely, ~~4rrp Brad Camp President 4720 S. Santa Fe Circle, #4 - Englewood CO 80110 -303-795-6551 - 303-703-6075 fax ~~4.( ~ City of Wheat Ridge Commercial Sign PERMIT - 080735 PERMIT NO: JOB ADDRESS: DESCRIPTION: 080735 4980 KIPLING ST 12.03 sq ft individual ISSUED: EXPIRES: letter sign old sign is 06/30/2008 12/27/2008 11 sq ft *** CONTACTS *** owner gc 303/795-6551 Independance Square Brad Camp 02-1182 ROYAL SIGNS INC. ** PARCEL INFO ZONE CODE: SUBDIVISION: ** UA 0041 USE: BLOCK/LOT#: UA 0/ Permit Fee Plan Review Fee Total Valuation Use Tax ** TOTAL ** ESTIMATED FEES 162.90 105.89 .00 91.80 360.59 PROJECT VALUATION: 5,100.00 ** FEE SUMMARY ** Il~~ Conditions: Must comply wI 2003 IBC & 2005 NEC. I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance with the Wheat Ridge Building Code (I.B.C) and all other applicable Wheat Ridge Ordinances, for work under this permit. Plans subject to field inspection. Signature of contractor/owner date 1, This permit was issued in accordance with the provisions set forth ~n your application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Codes of Wheat Ridge, Colorado or any other applicable ordinances of the City. 2. This permit shall expire 180 days from the issue date, Requests for an extension must be received prior to expiration date. An extension may be granted at the discretion of the Building Official. 3. If this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (l) year. If changes have been or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. 4, No work of any manner shall be done that will change the natural flow of water causing a drainage problem. 5. Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall rece~ve written approval on inspection card before proceeding with successive phases of the job. 6, The issuance of a permit or the approval of drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation the provisions of the building codes or any other ordinance, law, rule or regulation. All plan review is sub. c ield inspections. signature of Chief Build' date INSPECTION REQUE REQUESTS MUST BE (303) 234-5933 BUILDING OFFICE: (303) 235-2855 3PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. . O~'l<H~~", ~ OI..ORp..OO City of Wheat Ridge Building Division 7500 W. 29th Ave., Wheat Ridge, CO 80033 Office: 303-235-2855 * Fax: 303-235-2857 Inspection Line: 303-234-5933 Date: ~- 30 -oz; Plan#: Permit#: D801ijj Building Permit Application Property Address: -=t ~ ~O f( \ pI; f'--.S <;1"" $-+ e 4 W ~~, U, Property Owner (please print): I",J f'~v.fi. p f\,' -f ~ 'b; I _I A 'l Phone: Mailing Address: (if different than property address) ~Pf L' 101 ~ Address: City, State, Zip: ~ ;) Contractor: _t:.- 0 J {'AJ. ~'8"'-."> Contractor License #: ~C- Phone: 30 ~ jq c; ~S51_ g .s:: Sub Contractors: Electrical City license #: Company: Plumbing City license #: Company Mechanical City license #: Company: Exp. Date: Approval: Exp. Date: Approval: Exp. Date: Approval: Construction Value: $ Vj l t;. bU (as calculated per the Building Valuation Data sheet) Plan Review (due at time of submittal): $ Use of space (description) -I '::J. -0 ':-, ~ .,t.'t., Description of work: l \ old Q.\!\t t'S ~ t'+. Sq. Ft./L.Ft added: Squares BTU's Gallons Amps OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate: that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance with the Wheat Ridge Building Code (l.B.G) and all other applicable Wheat Ridge Ordinances, for work under this permit. Plans subject to field inspection. CIRLCE ONE:: (OWNER) (CONTRACTOR) or PERSONAL REPRESENTATIVE of (OWNER) (CONTRATOR) PRINT NAME: SIGNATURE: Date: DEPARTMENT USE ONLY ZONING COMMENTS: {e/OB Zonmg:( -f -, Reviewer: J H - 0 [(. PUBLIC WORKS COMMENTS: Reviewer: BUilDING DEPARTMENT COMMENTS: Reviewer: FIRE DEPARTMENT:: 0 approved wi comments 0 disapproved 0 no review required I Bldg Valuation: $ OCCUPANCY City of Wheat Ridge Community Development Department Building Permit Number: Date: MINOR BUILDING PERMIT APPLICATION Propc'fly Owner: .E'DvJ,M<::O ;::f oNeS I,J ve-S T(}1etVTS Prop<-'flyAddr=,: 4'1Bo i'C1f'L-lIv6 , Contractor License No.: 00>. I , 8 ;;L Company: fZO'l'AL Sol &'('Js lINe Phone 7).0 -818 -8,1;;1.) Phone 30"3 - 7<f5" - b 5 51 OWNERICONTRACTOR SlGHA1\JRE OF _STANIIING AND AGR-..T Buildina Deot Valuation Rgure: $ 5/ DO~ I hereby certify that the .- distances proposed by this perrot appIicabon are accurate, and do not violate ~.......- ontnances, n_... regulations 01 the CIy of \Mleat Ridge or covenants. __"lleIlIIsor t~~1IS of record; thatal~ shown, and alegations made are aa:onte; that I have read and agree to"- by al condIions printed on this applicalion and thai I assume full...""",,,,, for compliance wiIh the _ Ridge Build019 Code Q.B.C) and aD oIher8pllk:able_ Ridge Ordinances, for wort< under this permi!. Plans subject 10 tleld inspec:lion. IC>M'lER)(CONTRACTOR)S1GNED ~r- {{:rrrp IlAlE" 1?o/o8 (OWNER)(comRACTOR):PRlNTED 6f2AD j....., '-AiJI\ P DATE~ Use of Space (description): i2eJ?\QC,,..,'j (7V"S~"'~ s1ore-f0:,A1"' ~,jrJ WI ~ Description of work: l \ Q' ,\:o /" <' L< ~ - 0 <. ) N \ArV -"" 'J . -C ~ ,fttoJI~ Value:S Pennit Fee:S Plan Review Fee:S Use TalcS Total:S Sq. FL added BUILDING DEPARTMENT USE ONLY SIC: Sq.Ft.: ~ONING COMMEJ>lTS: Approval: Zoning: Ioull[)(NG COMMENTS: Approval: PUBlIC 'M1RKS CO....ENTS: Approval: IRE DEPARTMENT COMtENTS: Approval: IoccuD3ncv: Walls: Roof: Slories: Residential Uni1s: Eleclrical Ucense No: Company: Plumbing Ucense No: Company: Mechanical Ucense No: Company: Expiration Date: Approval: Expiration Date: Approval: Expiration Date: Approvat (4) (5) 151 This pennI was issued in acconIance wlh the provisions sellorth in your application and is subjed to the laws ofthe State of Colorado and to the Zoning RegUaIionsand BLiId019 Codes of Wheal Ridge, Colorado or any other applicable ...dinances of the Ciy. This pemilshaU expire W (A) the _.- is not~,.,,,,,0.c4_ siXty (60) daystium issue - ... (B) the -019 authoriZed is suspended ... abandoned for a period 01180 days. If this pemiI expires, a new pemiI may be acquired for a fee of one-/\a.the amount nonnaUy required, provided no changes have been...wiI be made in the orginaI plans and ..,.,..;r....lionsand any suspension... __ has not exceeded one (1) year. If changes have been... W susper19oo'" aba-..ment exceem one (1) year, full lees _I be paid for a new pernI<. No work of any manner shaI be done thai wIIc1Bnge the _ flow afwater causing a dra__ problem. ConIraclor shaD notify the Building InspedDr 1wenIy-four (24) houIs in advance for al inspections and _I receive _en approval on inspeclion card before proceeding with ,... . ..e phases 01 the job. The issuance of a pennil ...the _01 of drawings and .,....kafions shaD not be co-..ed to be a permrt for, nor an __I 01, any violalion of the provisions of the building codes ... any ofher ordinance, law. rule ... regUation. AI plan review is subject fo field inspections. (1) (2) (3) f')c\ S TINb S (brJ - fi<\STrNb S\bN ;: t2-RfYl ov-f'D I -rHIS s E:,/'J IS Be rJ6 ( \ 5'1, f+, o rSf'OSEO I zO' I FA~! 96.c 5'" c.s. ~.~,*.-i_ .'!"'....___.: ~:!.i1 I - I -- ,<;1'< II I'" ~,- j'''~'i\_ - EDWARD JONES IN\~>I'\IFN'I' ~ ~13391.ART1 I.EPLACE" Ill6! ""I:ICGCour;t."~mloln ,- " ... ,QN.1 PANEl. 4f:BO J"!plilll,/St:,,,'flt I 'SIF INTFRN,"LLY ILLUMINATW ::;'uitr.4 'Jh~l;f.It4~,::;C -FhCE IS #7328 WHITE LEX/\t-I wI FA.CE BKG[) llf:..ItW.CI....tll;P_"" 4/Si,)b S]LK-SCPFFN~C' Of'AQUF f'MS 553~' DARK GR.F~N ,....~,t..'1 ~,' -COP\( IS viHiTE \I"~ K'I\<l:""1 ..l>IA -RULE liNES ,A,ND REVEAL ro BE SIU',-SCREHJED tM!C'NOID"', TO MAleH f'lv15 371 ~ ..jNf'l-ALL AS f;HCl/'iN I ... - ......",-~ -~'." .....~... ~~~}&~ .MfI"....o;OT\~ MD~r~ II ~m FRONT ELEVATION :".:..:~_~_I'!'~.?;~E_.____..._~_ -.. ntl.;.lJfl;o.'.lYII.lGt!:lHl P1lOf'~RH 0" "",~'I~llS"::! tJl'f.R.JA';YJ~III:C. ,Cf"f!;...RRO','vf:HM>f<&S,IT flll---,ioanii9iii';eiiiiftijiiWiliiii"'CllIiiiiiOiiiijiPriiVal-",rniiOFi'sTsiGNS1*ORAWING 5 NOT TO SCAlE BUT IS PROPORTIONATE TO AClUAl BULDlNG* ";:';;:~~~:',;::,~~rn I I I t Signature below illdic:ates .pproval of BOTH design & plac:ement of sign/II DIRE'CTL.... OR lllt!lflE<:7tY, fJCIl I' X I FIELD VERIFY All MEASUREMENTS BEFORE BEGINNING ANY WORK. D^1E I "'___ =___________ INSTAllER TO VERIFY MOUNTING SURFACE PRIOR TO INSTA~lAnON. 1 ~t7 ..u =< u '" ~ 0 '" rf'. ~~ ~ ~ ..u < C> ~J a \J .. f 'D (}I ~ ~_\b~ 'v 2 ~ ...l 0 ;:i \;L ~ 1 '- gC: c> - cl.. \) ~ ~ ~ ~~ 1: t"V' a (L ~ --1~X ~V) Cl.~3,~ <vT 0 r- /\;l Z - on \f\ '" <, ~ "" 3 " c> c> 0 -< /\) z o<S .ill 3' >- z -< ~ "" a c> .!e u;lfte 2 0 =~ 0 (3 .... CD U T"' u\ I ..i G) ~ mS a, LL .........- CY(\llfd J::;;t \.. ~ 8 aa i ~ ,...... e en .. o...m · N-- ~ .. ._ CD 0 ;.c...c ~:5.n f:~ ~z ~ L c = , ~ ~ ~ - ~ ~ L1-2R 15" ILL. CHNL. L TRS. ON A RA' !\Y~ QrY.15Er ~ \~,(~ f~,CE TO BE <732B WHllE II'ilIIIIIiii/i IRIMeAf' fOMATCH f~155535 GREEN .,...,.".....=- 4/910' RET1J;;:~~5 TO M..;TCH Ol~ GREEI.... (PM5 5535 G~=~t~} ")'\/1' ~ NE.OH TO BE /H3500 I,\'HITE o;'Hl" ~~~.j}6s ~.A,CEWAYGOlOR?nIl6UILOING FASCA - .AU ELEcr~IC.,.I.,L COMPONENtS F,RE UL LISTED. 6tJma TRI-,I-;srOR~E.'<::S A7:S Ij~ .i21S1 G~OUND FAULT ::OMPlIM:T. <;:'.ACEWf,Y EO") PFED W,lH EXT~'R~j/\L 5Eli:VlCE 5WifCH. i"12~' liG:N.N.cfJYTERED IN SIG!{Q.A.N .y;;,,. p..",.,.., U\'cloCr.loOtl - - :;: ;;: - - ~ ,,;H - II i ......&.8 ~ = ~ 1l111~JV,\',lItliISIH; , FIlCI~I"'1("jMl6'G ~ 1'~I."lIn,l:_'Nc. ~ TII~ ItAlIOJI~H.G~f'~ UW.IH01H&~tl";!Owr.fIJ. ~ CCPlf:l{,""~IJf'OSlDOf'. ~ DI'l!CllYCR l~r~RECllY.N(JR ~ U!IO)FORA'IY 1l.I1I~OEE g "'"....OUtp,o:RIJISSlO.;. ~ , ::: - ~ ~ o 'F = ~ ;:. " ~ ~ " " " ~ n ~ ~ G ~ ::' - ~ G . . ',' '5IGNS, Sql~~~\~ >>n1LW'''CLINlllf:l =M EDWARD JONES .~~;=;1...." r~tJ~:t" Url r",~"'''J W/P. ~ '"REQUIRES U.L. & MANUfACTURE'S lABELS' 115.5" , r---- --- ---. 'JWJL Jln j \'). J ~,{D.l\\fj,1:1511;I!1~(Q)[jjJ@~ 2~ ~__--5--- !-.--- I .. ~ ~ " " . -- ,. '-'1.: "1 ~:...l '. ~iIi<., --- r,~;. T I , "', ~I ~appr.Va'-f;ini101ASfSra1Tsl'D~AWlNG IS NOI 10 SCALE BUT IS pnOPO~IIONAIE TO ACIUAl BUilDING' H doslen & Placl"~lg"I" I FIELD VERIFY ALL MEASUREMENTS e.EFORE BEGINNING Ai'IYWORK. _____o.!:::!:d.P, -J_ .!_J INSTAllER TO VERIFY MOUNTING SURFACE PRIOR TO INSTALLATION, L-t{ r-J J O~ Afp(7) u-q ( FRO~T EOLEVMlON f+ 0) ~ N~ S~bN gQ~ S'\6,J ~~ 01<:0 (-e-~~~ 20./ \Iif" ~ >(v-. e~.arJi<<itVJj -- "",.. EDWARD JDNEB AEVIlIDNNOIII: Chaneedfrom rl!lplaUll'l1l!lntf1lll"to t.1-2R _#lift I llEY.1lRII .....- llet"''''1 ItW:IlRII .....- - - I; -.. 6. 6u~" .........6.5u1!i5tl THIS llRAVf1NG IS THE PRClf'S'UYCfFABTSlGNS IHTERtUI'TJONAL,INC. THE BORROWER AGREES, rr SHALL NOT BE REi>ROOUcetl. COPIED OR DISPOSED OF, D1RECTLYORINOIREOTLV,NOR USED FORAN'( PURPOSE WlTHOUTPERMI8SIDN. "REQUIRES U.L. & MANUFACTURE'S LABELS" 115.5" \QI 1-2R 15" ILL. CHNL. LTRS. ON A RACEWAY -QTY.15ET _ - FACE TO BE #7328 WHITE ~ - TRIM CAP TO MATCH PMS 5535 GREEN - RETURNS TO MATCH DK GREEN (PMS 5535 GREEN) - NEON TO BE #6500 WHITE - RACEWAY COlOR PTM BUiLDING FASCIA - ALL ELECTRICAL COMPONENTS ARE UL LiSTED. 60ma TRANSFORMERS ARE UL #2161 GROUND FAULT COMPLIANT. RACEWAY EQUIPPED WITH EXTERNAL SERVICE SWITCH. -/~ n LEVATION 11---...._-PltiH'iiiii'i"iiiiiindii!Win. 'iii&iiiiidiOriiPiirmiioTmlo"FwiiiNil "DRAWING is NOT TO SCALE BUT IS PROPORTIONATE TO ACTUAL BUILDING" I I SlgIlllluI8 below Indlcat8t approval of BOTH d881gn & p1acsmsnl of sign/BI I . '; I FIELD VERIFY ALL MEASUREMENfS BEFORE BEGINNING ANY WORK. l! X ' ~!!'________J INSfALLER ro VERIFY MOUNTING SURFACE PRIOR fO INSfALLAIION. , IS) ~ ~ ru , , ~ ~ ~ ~~ C" SINGLE ;:;TIZ(iKE l'IE(iI~ WALL 050" ALU~~HUM FiLLEf~ f';\NE /. ;_TS r ~,----~.~:j--- -/ / n SIG\I GWUI\DING LU(; / ' or/TED IN'" I Dr:: -I~C (',"IJ"E' ! ~,_ l.-.\ ' ,_J '- t: _,,_u,,), ,,- J i' L I "C'HoD c'le'I\1 C 'O("'ION I .~.. L.I....-' I ,--' ,/ JLc...>' ~ ( (COINSISTS OF': nZ/\NC'rFOF':Iv1Ef< ! . w/301v1!\ NOf,M/,L P()'vVER ./ i FI\CTOV ,".ND l:NCI.OSURE) 1/ TRANSFORMER TO BE 1 ENCLOSED FROM EXPOSURE ! TO OUTDOOR ELEMENTS' TEl:::XAJ,1 ,ACE W -r:R f)T ET" .~ , II , ILL---- II .1 .,-.. . ('- .,,------ rt- " 1" TI< 11v1 C/', F' C,500 WHITE NEGI'I (APf?ROX. 1/2'") NE()I~ SlWPOR'S SECTION DETAIL "'Ii , " 'L, ."-'---~-- . (E 'e. J .::710 VOLll\GE f\!\CK WEEP HOLE::, wi SH/\DOW ScrZEEN C' J SIGN TYPE LI-2R ElECTRICi\l SPECIF'ICI\TI(}\b IT 1i.!.Ulvlll~A,TED INDIVIDUAl, LETTERSET "UL 2161 LISTED AND 1996 & 1999 NEC COMPLIANT, SECO~IDARY GROUr,D FAULT PROTECTED ALL SIGNS CARRY lIL LISTING LABELS ~ '-!J iil Ii; ~~ F1l - ml----~.. h , v ; _1~~---; TOT/'lL --- '70' 0" , ,).::j - I i .~~~~ 2 '5" s 6500 WHITE I\IEON f-~ d Tl 0-1 nre rl 25'-0' 'Li' -0" . ~_ _.~___~~~ I, , '!,,'.'bF':>'/I, 'i: 12,OOOv 7500 I !\'.Wf, 2.'3. r'--'-", 'r V 1_'_ -. .--.-------..---.-----.--...--.- -- L.5 "",-",., ---- L-.- __'._ __ 1 20 VOLT 15 /\MP CIRCUIT F/\CTO~~Y ~ROI,/IOt:D IvlllirOI'-H (:;I~OUNr) TE'~Iv1IN/\1 --HiC+l VOLTAC:: SECON[),A.RY Tlel(l!I I--I)\L. m Om ~),~:J' REIvIOTE TR!\NSFORMERS WITH ENCI.OSUKE CiUIT/\t3LE h')f( I,JDOOr(USE o f,jL'r it .J'-TkJIiiSFoRMEif p_ ' -...~ NUMBER ONE ....l~ , . ~rd-I-;l a I--;T HIGH 'fOLIAGE :'j[CONL:/\RY TERMINN. SIG~J GKC!UNDIW; GKOUNDII.jG LUG lSiD!: ENC_05ur<E) Ir~r 0 I I L1-2R DETAIL SHEET ELECTRICN SPECiFICATiONS lh,OOO 5" IU.U,'vill--li\IED II--IOI'/IDUA CTO Ci\t3LE !i--J ETERSET C,ll--lDUII. (IYF') 30 lvil\ NOTICE TO ALL SIGN INSTALLERS AND LICENSED ELECTRICIANS: ( SIGNS MUST USE MID-POINT GROUNDI ,. [~:' ~""." E " CERTIFICATE OF COMPLETION City of Wheat Ridge 7500 W 29th Ave Wheat Ridge CO 80033 permit# 070620 Issued: 02/12/08 Stipulations: This certificate verifies that the building constructed and/ or the use proposed of the building andlor premises, under the above permit number and on property described below, does comply with the Wheat Ridge Building Code and development standards of the zone district in which it is located and may be occupied. All other licensing requirements for the City must be met. Site Address: 4980 KIPLING ST Parcel Number: 39-153-14-010 Owner: STEVE HODGES Contractor: GEORGE HARTMAN EGC SERVICES, INC 1156 SO. LIPAN STREET DENVER, CO 80223 For the Following Purpose: Commercial Miscellan Cody Edi tions ~2003 ICC/2005 NEC -- 2003 ICC/2002 NEC 1997 UBC/2002 NEC Sprinkler S stem NO change shall be made in the USE of this building without prior notice and a new Certificate of Completion from the City of Whea~e. Zoning FICATE MUST BE POSTED BY FRONT DOOR OF COMMERCIAL OCCUPANCIES ~^_"__ ~~,,_"_ ,"'~""- " _,,~,.,.,.....,""~', '~'../"~"'...' .,..~ ....."_,.....^_...,-...',/'.I"_..........""v'"....-./'\./',,/./"v""-"/ ,"v',_^~'~/'"_"'.,--'/"A""" /.~"_A .'-,,/v- ,"V' ./-/"/'--' ~~'./_v~,~~,,,,~'-__'''''''"VA./y'-/-./'v''/-_'V'''v-'/''''/;' ~: Date: ;, 1-jty/o8 '. < '> ~ " , < .; A Certificate of Occupancy J Completion has been requested for: L\,ClEo 'Wu"-~ ~ ADDRESS: < : PURPOSE QF STRUCTURE: , < 5 " ~ Building Department Approval: '> '. '> Remarks: " '> ~ Zoning Approval: " <. Remarks: , '> , '> :' Public WorkS Approyal: , { , , Remarks: < ~ Fire Marshall Approval: ~ (If Applicable) '> < < , , " Remarks:. ~ Sanitation District Approval: ~ (If Applicable) , '. Remarks: < Water District Approval: ~ (If Applicable) " Remarks: , { .' 5 , ~; ( '> <" >- ) ': ) ( , ? , I <. ( .; " " ) :' ; .' f i ( 5 , < 5 ( , , ( i { < i ( f ~ / , '> , > ., '> > , < '" ( 5 ~ .:......-...,"''-.....^- ....."""'.....'""'-'^--""^-~~~^..--..."" ~_^"^"'~,^--"'-^-....,.-....".'- ,~--...^-./"",..........-^-_"'............,r-v-.........--,., -....--..."'-./'V.....,,""v'"......... .,,"', --...r--..^--____''"v''~-^-,,,,..~"'-'....-...r~'""-^-'^-,.'. COMMUNITY DEVELOPMENT DEPARTMENT Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office. (303) 235-2857 Fax INSPECTION NOTICE Inspection Type: ~;,,/,-II /5, {'0. , Job AddresslPermit Number: V'i"?c I~AI,.</ t fr"J"1.l A3<.-,!p/"'! f A ?r>i'r:n/ .fr;.' . o No one available for inspection: Time 1/,' 3c AM/PM Re-Inspedion required: -'~--1 Yes ctJ.2J .When corrections have been made, call for re-inspection at 303-234-5933 Date'. ".J j"//~I ,- .".' / <' ~' ,",' .,. Inspector: .2;/," DO NOT REMOVE THIS NOTICE INSPECTION RECORD 7500 W. 29th Avenue Wheat Ridge, Colorado 80033 (303) 235-3855 r:rlnspectio.n Line (303) 234-5933 Inspections will not be made unless this card is posted on the building site 24 Hours notice required for inspections Job Address 4 Building Permit No. Owner .c. Contractor Contractor Address s'r Date Issued \7 2P'1 Type Occupancy CC)(Y\f('c J..U!.. C INSPECTOR MUST SIGN ALL SPACES PERTAINING To THIS JOB FOUNDATION INSPECTIONS DATE APPROVAL DISAPPROVAL INSPECTOR COMMENTS: INmALS Footings/Caissons Stemwall Reinforcing or Monolithic Weatherproof I French Drain Waler/Sewer Service Lines POUR No CONCRETE UNTIL ABOVE HAS BEEN SIGNED CONCRETE SLAB FLOOR Electrical (Underground) Plumbing (Underground) Heating (Underground) Eleclrical Service Rough EIeclric Rough Plumbing /IW Test Gas Piping Rough Mechanical ,I"P'0 7 v y"~ ~i'rE..:n.l"'t il"'I:~j' '" , ,,- /c . :( $. c.? v- I< Ap''',nl,~-4] rft~'.1J>f. Framing~i f-tl[',1-'t)t" W '6t I L..-/" r.. ,-'-;:' Roofing Insulation Drywall Screw ;#4lp/1.t>vF /'/JJ~' 7 e>": fLo .- ~rI a"""l.v Il..\..... .A4'.v ~t..i> A1/hVfAt2./J .+t)/h77i....l~ FINALS Eleclrical Plumbing Mechanical Frame I Interior Finish 1#lh7 ,,/ K(. R.O.W & Drainage Fire Department Parking & Landscaping **NOTE: ADDITIONAL INSPECTIONS / COMMENTS ON BACK Do NOT POUR FLOOR UNTil ABOVE HAS BEEN SIGNED OCCUPANCY NOT PERMITTED UNTIL CERTIFICATE OF OCCUPANCY IS ISSUED PROTECT THIS CARD FROM THE WEATHER 1~7() ~p/'~ St. . -cuIdtrtj o..ddl-ftol'1~1 ardtl~ {,.J",U 10 -facA.d ~ cJu,..l'Ltje If -J--. . " # /",.t? ~r ~ } 7 ~ t1f[.. }, J~ 'I;.. , l ; , , l . < ~ f ~ , i \ ; ~ i < i i i ! ~ , ; ~ i i ! , . ! I i > ~ ! , , 2 ! I City of Wheat Ri~ge Commercial Signi PERMIT - 071254 PERMIT NO: JOB ADDRESS: DESCRIPTION: 071254 4980 KIPLING ST ROSSI'S CATERING - 2X8 CABINETSIGN ISSUED: 11/15/2007 EXPIRES: 05/13/2008 (UP TEMPORARILY) . *** CONTACTS *** 303/399-3334 Keith Hurley 01-9226 Ad Light & Sign Co. ANN HURLEY HODGDON TRUST GC OWNER ** PARCEL INFO ZONE CODE: SUBDIVISION: ** C-1 0041 USE: BLOCK/LOT#: UA 01 Permit Fee Plan Review Fee Total Valuation Use Tax ** TOTAL ** ESTIMATED FEES 54.37 23.54 .00 19.80 97.71 PROJECT VALUATION: 1,100.00 ** FEE SUMMARY ** llCoJt~] Comments: MR: 11/14/07 C-1 ELECTRICAL MUST MEET 2005 NEC SUBJECT TO FIELD INSPECTION I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance with the Wheat Ridge Building Code (l.B.C) and all other appli bIe Wheat Ri~ e ces, for work under this permit. Plans subject to field inspection. ! (~, S' 1. This permit was issued in accordance with the provisions set forth in your application and is subject to the laws of the State of Colorado and to the zoning Regulations and Building Codes of Wheat Ridge, Colorado or any other applicable ordinances of the City. 2. This permit shall expire 180 days from the issue date. Requests for an extension must be received prior to expiration date. An extension may be granted at the discretion of the Building Official. 3. If this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes have been or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. 4. No work of any manner shall be done that will change the natural flow of water causing a drainage problem. 5. Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceeding with successive phases of the job. 6. The issuance of a permit or the approval of drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation of provisions of the building codes or any other ordinance, law, rule or regulation. All plan review is subject.to inspections. signature of Chief Building date INSPECTION REQUEST ~ NE. (303)234-5933 BUILDING OFFICE: (303)235-2855 REQUESTS MUST BE MADE BY 3PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. ~ City of Wheat Ridge Community Development Department MINOR BUILDING PERMIT APPliCATION Building Permit Number: Date: D~' 0'1 I 2.')L( Property Owner:Ann ~wky ~5c1o,,~<, Property Address: 4l:\BO IG: pl. ~ Contractor License No.: 19l.u.. J Company: .td ll~n r -\ S'Q>'\ Phone: Phone: 353. 30/1, 53"1/ OWNER/CONTRACTOR SIGNATURE OF UNOERSTANDING AND AGREEMENT BulldincsDeot. Valuation Figure: $ I hereby certify that the setback distances proposed by this permit application are accurate, and do notviolate applicable ordinanCes, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made-are-accurate; that! have.readand agree to -abide by all conditions printed on this application and that I assume full responsibility for compliance with the Wheat Ridge Building Code (I.B.G) and all other applicable Wheat ___Bl~ge Ordinances, for work under this ~ermit. Plans subjecllo field Inspection. (OWNER)(CONTRACTOR); sle iJHl2 'ft:l1 li:!;b . DATE II ((X(C7 (OWNER)(CONTRACTOR):PRINTEO Arm rr1'a...U)Vt It-e DATE~ UseofSpace(description): 1/0;<:"1'0; (~~) . . Descriptionofwork:\tlsWI I ;/'''5'(: 'i1t.t--\o..-~'PossI$'- Value:$ 1100.32- Permit Fee:$ Plan Review Fee:$ tJse-HBf7$----- Total: $ w, H D,,-I:; /a< "'f -wn pu,'" , tj Sq. Ft. added ONING COMMENTS: Approval: . Zoning: BUILDING DEPARTMENT USE ONLY \. st t J.>!.' ~ i' ~ SIC: Sq.Ft.: Occupancy: Walls: Roof: ~~(J ~ -'1Vt'O !)Yr-- 6 <..() BUILDING COMMENTS: Approval: USLlC WORKS COMMENTS: Approval: IRE DEPARTMENT COMMENTS: Approval: StDries: tJ' Residential Units: Eiectrical License No: Company: Plumbing License No: Company: Mechanical License No: Company: Expiration Date: ____--"'QllLOVal'--_____~.____ Expiration Date: Approval: Expiration Date: uApproval: (1) This permit was issued in accordance with the provisions set forth in your application and is subject to the laws of the State of Colorado and to the Zoning Regulations and BUilding Codes of Wheat Ridge, Colorado or any other applicable ordinances of the City. (2) This permit shall expire if (A) the work authorized is not commenced within sixty (60) days from issue date or (B) the building authorized is suspended or abandoned for a period of 180 days. . (3) If this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes have been or if suspensian or abandonment exceeds one (1) year, full fees shall be paid far a new permit. (4) No work of any manner shall be done that will change the natural flow of water causing a drainage problem. (5) Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceeding with successive phases of the job. (6) The issuance of a permit or the approval of drawings and specifications shall not be construed to be a permit for, nor an approval!)f, any violation ofthe provisions of the building cades or any other ordinance,Jaw, rule or regulation. All plan review 'is subject to field inspections. Chief Building Official . City of Wheat Ridge Building Permit Submittal List The following items are required for the minor building permit submittal for the property located at -.!::I9 W ru-r:X1rit{ . . If any of the required items are not included in the submittal, the sul)m' al will be considered incomplete and returned immediately without review. . Minor permit is defined as: fence installation, sign age, decks or covered patios, concrete work in excess of 500 square feet, sheds, garages and over the counter permits. You do not need to submit a site plan with over the counter permits. This sllf:Jd"lIu:sL ue suu'lIiLleu wilh lhe building permit appliGatimT;-Please initlal-oes1Oe each required item, signifying that it has been included. Review Required by: 0 Building o Planning o Public Works SUBMITTAL DOCUMENTS: PLANS: DOne (1) site plan Contents of plans detailed in the minor permits handout DOne (1) Elevations/details page DOCUMENTATION: DOne (1) completed building permit application 0' One (1) property deed DOne (1) building permit submittal list ..----..------.--.-.---------...-------- Call the inspection line before 3 p.m. for a next working-day inspection City of Wheat Ridge Community Development Department 7500 W. 29th Avenue Wheat Ridge, CO 80033 . Building Division - 303.235.2855 Planning Division - 303.235.2846 Inspe"ction Une - 303.234.5933 www.ci.wheatridrJe.co.us Wall SiQn Calculation Sheet You must complete this sheet and include it in the submittal package for any new wall signs. You will also need to create a site plan and a detail sheet of the signage. Project Address: 4ro k.;pl\~ ';jt Contractor: M L.A8hH<2,;8(\ You are allowed 1 square foot of signage for every 1 linear foot of wall to which you are attaching a sign. All wall signs must be adjacent to a street or major interior drive. Step 1: Measure the length of the wall(s) where you are attaching the sign: Wall 1 - AL feet Wall 2 - feet Wall 3 - feet Step 2: The length of the wall is the allowable square footage for the wall sign. Wall 1 allowable signage- Wall 2 allowable signage- Wall 3 allowable signage- 4\ square feet square feet square feet Site Plan b'p\\f\.! 3~ ....(4- I ~\' I - -' i 8 1 d' 1 RuS5\ '5 8;11, dew 11,,,,, M TV L.o...m~ . lJolj O:\.f'\cOlof~ ~ City of Wheat Ridge Commercial Sign PERMIT - 071255 PERMIT NO: JOB ADDRESS: DESCRIPTION: 071255 4980 KIPLING ST PET GROOMING - 2X8 CABINET ISSUED: 11/15/2007 EXPIRES: 05/13/2008 SIGN - UP TEMPORARILY *** CONTACTS * ** 303/399-3334 Keith Hurley 01-9226 Ad Light & Sign Co. ANN HURLEY HODGDON TRUST GC OWNER ** PARCEL INFO ZONE CODE: SUBDIVISION: ** C-1 0041 USE: BLOCK/LOT#: UA 0/ Permit Fee Plan Review Fee Total Valuation Use Tax ** TOTAL ** ESTIMATED FEES 54.37 23.54 .00 19.80 97.71 PROJECT VALUATION: 1,100.00 ** FEE SUMMARY ** lFi'~~J) Comments: MR: 11/14/07 C-1 ELECTRICAL MUST MEET 2005 NEC SUBJECT TO FIELD INSPECTIONS I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this applic tion and that I assume full responsibility for compliance with the Wheat Ridge Building Code (I.B.C) and all other appli a le Wheat Ridg es, for work under ;'/is !brj/:;'7ans subject to field inspection. S' ure '/ date 1. This permit was issued in accordance with the provisions set forth in your application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Codes of Wheat Ridge, Colorado or any other applicable ordinances of the City. 2. This permit shall expire 180 days from the issue date. Requests for an extension must be received prior to expiration date. An extension may be granted at the discretion of the Building Official. 3. If this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes have been or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. 4. No work of any manner shall be done that will change the natural flow of water causing a drainage problem. 5. Contractor shall notify the Building Inspector twenty" four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceeding with successive phases of the job. 6. The issuance of a permit or the approval of drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation of the ,pr~~sions of the building codes or any other ordinance, law, rule or regulation. All plan review is subject to fie d' ~ctions. signature of Chief Building OffiC~;' INSPECTION REQUEST LINE: (303)234-5933 BUILDING OFFICE: (303)235-2855 REQUESTS MUST BE MADE BY 3PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. date ~: @1 ~~3 . - 01\ 2S') "~~ VlHE_> .., ~ 0 - " " m cbl.ORp...'\>O City of Wheat Ridge Community Development Department MINOR BUILDING PERM.J.T APPUCATION Building Permit Number: Date: Property Owner: An" # "'1-<'1 Kccj~'n 1hl' \- Property Address: 4900 - ~q'1O t, f I;",') Contractor License No.: IC) .?:JlP . Company: Ad L.13h t + S 'Vll Phone: Phone: ?fE '3'JC) - 3 "634 OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit appiication are accurate, and do not-violate applicable ordinanCes, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made-are acclfrate; that I have.reada.nd agree-to-abideby all conditions printed on this application and that I assume full responsibility for compiiance with the Wheat Ridge Building Code (LB.C) and ali otherappiicabie Wheal _ __1319g6 Ordinances, for work under this permit. Plans subject to field Jnsnection. (OWNER)(COtiTRACTOR): SIGNEO lIllJll/lo!t..- t(ft,[ DATE 111""/07 L./ Arm I I (OWNER)(COtiTRACTOR):PRINTEO rdfl kilh I~ DATE fj/(J'.pi , Buildinq.Dept. Valuation Figure: $. Value:$Ilf1)'gg.. Permit Fee:$ Plan Review Fee:$ Use-'fmc-+$---- Tota1:$ Use of Space (description): Ie.+-C'IfWml"~ . Description of work: !Mt...1I f ~'lQ)' ~Id.wd 'Pef0fWm,''Y' _ wlll~I'f b<. ""p t..mp",""I'j Sq. Fl added I... BUILDING DEPARTMENT USE ONLY ONING COMMENTS: I ./'J.- Approval: <0 -r., ,,"'. Zoning: ~..J'. " I ~ SIC: ::;q,Ft.: /_(--=2'~ " IRE DEPARTMENT COMMENTS: Approval: 2 -'?<t() ~ .-tOtro ;:YYr-- 6 ,() I 3, I BUILDING COMMENTS: Approval: PUBUC WORKS COMMENTS: Approval: Occupancy: Walls: Root Stories: Residential Units: Electrical License No: company: Plumbing License No: Company: Mechanical License No: Company: Expiration Date: AQQroval: Expiration Date: AQQLoval: Expiration Date: Approval: (1) This pennitwas issued in accordance with the provisions set forth in your application and is subject to-the laws of the State of Colorado and to the Zoning Regulations and Building Codes of Wheat Ridge, Colorado or any other applicable ordinances of the City. . This pannit shall expire if (A) the work authorized is not commenced within sixty (60) days from issue date or (8) the building authorized is suspended or abandoned for a period of 180 days. If this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been orwill be made in the original plans and specifications and any suspension or abandonment has.not exceeded one (1) year. If changes have been or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. No work of any manner shall be done that will change the natural flow of water causing a drainage problem. Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceeding with successive phases of the job. The issuance of a permit or the approval of drawings and specifications shall not be construed to be a permit for, nor an .approvalpf, any violation of the provisions of the building codes or any other ordinance,Jaw, rule or regulation. All plan review is subject to field inspections. (2) (3) (4) (5) (6) Chief Building Official . City of Wheat Ridge Building Permit Submittal List The following item!! ar~ required for the minor building permit submittal for the property located at !1tw) K..pllV1~ . . If any of the required items are not included in the submittal, the subm' al will be considered incomplete and returned immediately without review. . Minor permit is defined as: fence installation, signage, decks or covered patios, concrete work in excess of 500 square feet, sheds, garages and over the counter permits. You do not needlo submit a site plan with over the counter permits. Thi~ ~hl;j~llllu~LI.Jl;j ~ul.Jlllilll;jd wiLh Lhe building permit applicatim1;--f"tea.g-einitialbeslae each required item, signifying that it has been included. Review Required by: D Building D Planning D Public Works SUBMITTAL DOCUMENTS: PLANS: DOne (1) site plan Contents of plans detailed in the minor permits handout DOne (1) Elevations/details page DOCUMENTATION: D D D One (1) completed building permit application One (1) property deed One (1) building permit submittal list Call the inspection line before 3 p.m. for a next working-day inspection City of Wheat Ridge Community Development Department 7500 W. 29th Ayenue Whe~t Ridge, CO 80033 . Building Division - 303.235.2855 Planning Division - 303.235.2846 Inspection line - 303.234.5933 www.ci.wheatridoe.co.us Wall SiQn Calculation Sheet You must complete this sheet and include it in the submittal package for any new wall signs. You will also need to create a site plan and a detail sheet of the signage. - Project Address: -1CJ?() lli pi, 'Y1~ Contractor: You are allowed 1 square foot of signage for every 1 linear foot of wall to which you are, attaching a sign. All wall signs must be adjacent to a street or major interior drive. Step 1: Measure...tl:le-length-of-th.e.-wall's)--where...y.ou-araattachin9-tbasign:_____ Wa1l1- dO feet Wall 2- feet Wall 3- feet Step 2: The length of the wall is the allowable square footage for the wall sign. Wall 1 allowable signage- :;)(:) Wall 2 allowable signage- Wall 3 allowable signage- square feet square feet square feet Site Plan k.\P\;I'\~ <:,\- :,;.. "t:" 'PJ' ;( '17\ 1"_ '\ , \ J . City of Wheat Ridge Commercial Sign PERMIT - 071256 PERMIT NO: JOB ADDRESS: DESCRIPTION: 071256 4980 KIPLING ST SOCCER STOP - 2X8 ISSUED: 11/15/2007 EXPIRES: 05/13/2008 CABINET SIGNSIGN - UP TEMPORARILY *** CONTACTS *** 303/399-3334 Keith Hurley 01-9226 Ad Light & Sign Co. ANN HURLEY HODGDON TRUST GC OWNER ** PARCEL INFO ZONE CODE: SUBDIVISION: ** C-1 0041 USE: BLOCK/LOT#: UA 0/ Permit Fee Plan Review Fee Total Valuation Use Tax ** TOTAL ** ESTIMATED FEES 54.37 23.54 .00 19.80 97.71 PROJECT VALUATION: 1,100.00 ** FEE SUMMARY ** '--;C', I.:1.- < JJ4~4~n?~) Comments: MR: 11/14/07 C-1 ELECTRICAL MUST MEET 2005 NEC SUBJECT TO FIELD INSPECTIONS I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance with the Wheat Ridge Building Code (I.B.C) and all other applicab Wheat R dge 0 d nan es, for work under thls permlt Plans subJect to fleld lnspectlon ~e~ I~/I~.~q 1. This permit was issued in accordance with the provisions set forth in your application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Codes of Wheat Ridge, Colorado or any other applicable ordinances of the City. 2. This permit shall expire 180 days from the issue date. Requests for an extension must be received prior to expiration date. An extension may be granted at the discretion of the Building Official. 3. If this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (I) year. If changes have been or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. 4. No work of any manner shall be done that will change the natural flow of water causing a drainage problem. 5. Contractor shall notify the Building Inspector twenty four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceeding with successive phases of the job. 6. The issuance of a permit or the approval of drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation of the provisions of the building codes or any other ordinance, law, rule or regulation. All plan review rs subject to fr~~'"trons Slgnature of Ch~ef BUlld~ng Off~c~afl date INSPECTION REQUEST LINE: (303)234-5933 BUILDING OFFICE: (303)235-2855 REQUESTS MUST BE MADE BY 3PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. City of Wheat Ridge Community Development Department MINOR BUILDING PERMIT APPUCATION Property Owner: ~ Ilwltlf I'<<fj~Yllr""'r Property Address: 4~80 1(\ pl;~ Contractor License No.: IC\ OZ:Lv . Company: M L~'liht + S\~(1 ptJn.J Building Permit Number. Date: CJ II L 'J 'Co Phone: Phone: .~- 394. 33'Y! OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Buildinq.Dept. Valuation Figure: $ I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinanCes, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegatfons madeateuaccui"ate; that [have read. and agree-to-abideby all conditions printed on this application and that I assume full responsibility for compliance with the Wheat Ridge Building Code (I.B.G) and all other applicable Wheat ____Bjdge Of!lJnance~-'orwork under this permit. Plans SULI 10 field Inspection. (OWNER)(CONTRACTOR): SIGNED /Ju1o.Jt/A - tI~ . DATE l/tI~o; (OWNER)(CONTRAcTOR):PRINTE~ .A<<1OJY1iA vJh.1 +:~ DATE I' 0 Use of Space (description): Stx:w stop (f(G.TAc ( L- \ Description of work: \II'lW/ I 1.'<13' i'aJ,i'l.d Iv v-l<l<d l.Jtx~r !Jf<p '_ "'<i( ~11 hf. "P f-<fYlp'r~r, '1 Value:$ "OD'~ Permit Fee:$ Plan Review Fee:$ U~:$c----- Tota1:$ Sq. Ft. added valle WORKS COMMENTS: Approval: \ ty BUILDING DEPARTMENT USE ONLY ONINGCOMMENTS: I' '/ ,J . . Approvai:.. \. ...... . Zoning: ". \ . . . 81 ,. BUILDING COMMENTS: Approval: IRE DEPARTMENT COMMENTS: Approval: Occupancy: Wails: Roof: Stories: Residential Units: Electrical License No: Company: Plumbing License No: Company: Mechanical License No: Company: Expiration Date: Almroval: Expiration Date: ApJlElval: Expiration Date: _ Approval: (1) This permit was issued in accordance with the provisions set forth in your application and is subject to'the laws of the State of Colorado and to the Zoning Regulations and Building Codes of Wheat Ridge, Colorado or any other applicable ordinances of the City. (2) This permit shall expire if (A) the work authorized is not commenced within sixty (60) days from issue date or (B) the building authorized is suspended or abandoned for a period of 180 days. (3) If this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes have been or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. (4) No work of any manner shall be done that will change the natural flow of water causing a drainage problem. (5) Contractor shall notify the Building Inspector twenty-four {24} hours in advance for all inspections and shall receive written approval on inspection card before proceeding with successive phases of the job. (6) The issuance of a permit or the approval of draWings and specifications shall not be construed to be a permit for, nor an .approvalpf, any violation of the provisions of the bUilding codes or any other ordinance,Jaw, mle or regulation. All plan review is subject to field inspections. Chief Building Official , City of Wheat Ridge Building Permit Submittal List The following items are required for the minor building permit submittal for the property located at 4'180 ~~('1. . If any of the required items are not included in the submittal, the submi al III be considered Incomplete and returned Immediately without review. . Minor permit is defined as: fence installation, signage, decks or covered patios, concrete work in excess of 500 square feet, sheds, garages and over the counter permits. You do notneedto submit a site plan with over the counter permits. This sllt:itll"lIlusl ue suulllilleu wilh the building permit applicCltimr.-Please Initiattleside each required item, signifying that it has been included. Review Required by: D Building D Planning D Public Works SUBMITTAL DOCUMENTS: PLANS: DOne (1) site plan Contents of plans detailed in the minor permits handout DOne (1) Elevations/details page DOCUMENTATION: DOne (1) completed building permit application DOne (1) property deed DOne (1) building permit submittal list Call the inspection line before 3 p.m. for a next working-day inspection City of Wheat Ridge Community Development Department 7500 W. 29th Avenue Wheat Ridge, CO 80033 . Building Division - 303.235.2855 Planning Division - 303.235.2846 inspe'ction line - 303.234.5933 www.ci.wheatridoe.co.us Wall SiQn Calculation Sheet You must complete this sheet and include it in the submittal package for any new wall signs. You will also need to create a site plan and a detail sheet of the sign age. PrOjectAddress:jq'?:O r'.lpli't{j ~ contractor:\.--Ad (.Rc~AJ- -f: g;cpL You are allowed 1 square foot of signage for every 1 linear foot of wall to which you are attaching a sign. All wall signs must be adjacent to a street or major interior drive. Step 1: Measure the length of the wall(s) where you are attaching the sign: Wall 1 - .z:(:) feet Wall 2- feet Wall 3- feet Step 2: The length of the wall is the allowable square footage for the wall sign. Wall 1 allowable signage- ~ Wall 2 allowable signage- . Wall 3 allowable signage- square feet square feet square feet Site Plan 8i- ~I S':: Ox;; ~ \. 1 1 g'. 1 d' SOLt~{ Sto -p. 1 51n cle2p +to Lomp il. ~l~~~ City of Wheat Ridge Commercial Sign PERMIT - 071253 PERMIT NO: JOB ADDRESS: DESCRIPTION: 071253 4980 KIPLING ST WALL SIGN "GATE MINISTRIES" ISSUED: EXPIRES: 11/15/2007 05/13/2008 *** CONTACTS *** 3031399-3334 Keith Hurley 01-9226 Ad Light & Sign Co. ANN HURLEY HODGDON TRUST GC OWNER ** PARCEL INFO ZONE CODE: SUBDIVISION: ** C-1 0041 USE: BLOCK/LOT#: UA 0/ Permit Fee Plan Review Fee Total Valuation Use Tax ** TOTAL ** ESTIMATED FEES 54.37 23.54 .00 19.80 97.71 PROJECT VALUATION: 1,100.00 ** FEE SUMMARY ** W~!TI~ Comments: MR: 11/14/07 C-1 SUBJECT TO FIELD INSPECTION ELECTRICAL MUST MEET 2005 NEC I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance with the Wheat Ridge Building Code (I.B.C) and all other applica e Wheat Ridge nces, for work under thi! le~jt~ns subject to f,eld ,nspect,on. ( ~ate 1. This permit was issued in accordance with the provisions set forth in your application and is subject to the laws of the State of Colorado and to the zoning Regulations and Building Codes of Wheat Ridge, Colorado or any other applicable ordinances of the City. 2. This permit shall expire 180 days from the issue date. Requests for an extension must be received prior to expiration date. An extension may be granted at the discretion of the Building official. 3. If this permit expires, a new permit may be acquired far a fee of one-half the amount normally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes have been or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. 4. No work of any manner shall be done that will change the natural flow of water causing a drainage problem. 5. Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceeding with successive phases of the job. 6. The issuance of a permit or the approval of drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation of the pr~visions of the building codes or any other ordinance, law, rule or regulation. All plan review is subject to f'el in ctions. , Signature of Chief Building affic date INSPECTION REQUEST LI (303)234-5933 BUILDING OFFICE: (303)235-2855 REQUESTS MUST BE MADE BY 3PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. City of Wheat Ridge Community Development Department MINOR BUILDING PERMIT APPUCATlON Property Owner: Mn l{wle'i ~b'-TNS+- Property Address: 4"1'CO \(\ p\i^.j Contractor License No.: I C)>>b Company: AdL\'3ht +'3i'JY"I -1~~3) --- Phone: Phone:?a3,319-'5'334 OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Buildinq Dept. Valuation Figure: $ I hereby certify that the setback distances proposed by this permit application are accurate, and do not.violate applicable ordinanCes, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations madeate--a'-ccifrate; than have read and agree-lo-abide -by all conditions printed on this application and that I assume full responsibility for compliance with the Wheat Ridge Buliding Code (LB.C) and ali other applicable Wheat _____B!~ge Ordinances, for work under this ermlt. Plans sub"ect to field Ins action. (OWNER)(CONTRACTOR): SIGNE (OWNER)(CONTRACTOR):PRINTED ~h\'~ DA~~ DATE II (,1 Value:$I/00-& Permit Fee:$ Plan ReView Fee:$ l}s~$ Total:$ Use of Space (description):_~J.(I~i-sIJ~<; ( r\J ..ck \ Description of work: 1 Sq. Fl added IRE DEPARTMENT COMMENTS: Approvai: BUILDING DEPARTMENT USE ONLY ONING COMMENTS: 1\ I). Approval: '. ~ I \) Zoning: A ( -j' ., " SIC: BUILDING COMMENTS: Approval: PUBLIC WORKS COMMENTS: Approval: Occupancy: Walls: Root Stories: Residential Units: Electrical License No: Company: Plumbing License No: Company: Mechanical License No: Company: Expiration Date: Approval: Expiration Date: APj:l[oval: Expiration Date: Approval: (1) This permit was issued in accordance with the provisions set forth in your application and is subject to' the laws of the State of Colorado and to the Zoning Regulations and Building Codes of Wheat Ridge, Colorado or any other applicable ordinances of the City. . (2) This permit shall expire if (A) the work authorized is not commenced within sixty (60) days from issue date or (8) the building authorized is suspended or abandoned for a period of 180 days. . (3) If this permit expires, a new permit may be acquired for a fee of one-half the amount nonnally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded cine (1) year. If changes have been or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. (4) No work of any manner shall be done that will change the natural flow of water causing a drainage problem. (5) Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceeding with successive phases of the job. (6) The issuance of a permit or the approval of drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation of the provisions of the building codes Of any other ordinance,Jaw, r\jle or regulation. All plan review "is subject to field inspections. Chief Building Official . City of Wheat Ridge Building Permit Submittal List The following ite s are required for the minor building permit submittal for the property located at . ., . , If any of the required items are not included in the submittal, the sub . al will be considered incomplete and retumed immediately without review. . Minor permit is defined as: fence installation, signage, decks or covered patios, concrete work in excess of 500 square feet, sheds, garages and over the counter permits. You do nofneedto submit a site plan with over the counter permits. ~heel"llIu~t ue ~uulllillet.l with the building permit applicatiurr.-Please-irritialbesloe each required item, Signifying that it has been included. Review Required by: D Building D Planning D Public Works SUBMITTAL DOCUMENTS: PLANS: DOne (1) site plan Contents of plans detailed in the minor permits handout DOne (1) Elevations/detailspage DOCUMENTATION: D D D One (1) completed building permit application One (1) property deed One (1) building permit submittal list Call the inspection line before 3 p.m. for a next working-day inspection City of Wheat Ridge Community Development Department 7500 W. 29th Avenue Wheat Ridge, CO 80033 . Building Division - 303.235.2855 Planning Division - 303.235.2846 Inspection fine - 303.234.5933 www.ci.wheatridqe.co.us Wall Sian Calculation Sheet You must complete this sheet and include it in the submittal package for any new wall signs. You will also need to create a site plan and a detail sheet of the signage. Project Address: ~q~6 1G p\\~ S Contractor: ~M U1ft t- -t '61':}11 You are allowed 1 square foot of signage for every 1 linear foot of wall to which you are attaching a sign. All wall signs must be adjacent to a street or major interior drive. Step 1: Measure the length of the wall(s) where you are attaching the sign: Wall 1 - Jor) feet Wall 2- feet Wall 3- feet Step 2: The length of the wall is the allowable square footage for the wall sign. Wall 1 allowable signage- --100 . square feet Wall 2 allowable signage- square feet Wall 3 allowable signage- square feet Site Plan IS; f- (v 20~ ~ -e ~ .............. I/:'()' 1 81 T d\ GoJe Mi(\\s+(\es 1 ~ if\ dfep \-l0 Lo-mp ~l. '-1=0 l LJ Cb.I ~ Thc-e. City of Wheat Ridge Commercial Sign PERMIT - 071252 PERMIT NO, JOB ADDRESS, DESCRIPTION, 071252 4980 KIPLING .8T remove exising SUBWAY ISSUED, EXPIRES: sign/replace with 11/15/2007 05/13/2008 channel Itrs *** CONTACTS *** 3031399-3334 Keith Hurley 01-9226 Ad Light & Sign Co. ANN HURLEY HODGDON TRUST gc OWNER ** PARCEL INFO ZONE CODE, SUBDIVISION, ** C-l 0041 USE, BLOCK/LOT#, UA 0/ Permit Fee Plan Review Fee Total Valuation Use Tax ** TOTAL ** ESTIMATED FEES 181.10 23.55 .00 126.00 330.65 PROJECT VALUATION, 7,000.00 ** FEE SUMMARY ** 1Jo~m1] G.:> <!..>--' Comments: MR, 11/14/07 C-l ELECTRICAL MUST MEET 2005 NEC SUBJECT TO FIELD INSPECTIONS I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance with the Wheat Ridge Building Code (I.B.C) and all other applic e Wheat Ridg es, for work under this permit. Plans subject to field inspection. (I//i/~ 1. This permit was issued in accordance with the provisions set forth In your application and is subject to the laws of the State of Colorado and to the zoning Regulations and Building Codes of Wheat Ridge, Colorado or any other applicable ordinances of the City. 2. This permit shall expire 180 days from the issue date. Requests for an extension must be received prior to expiration date. An extension may be granted at the discretion of the Building Official. 3. If this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes have been or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. 4. No work of any manner shall be done that will change the natural flow of water causing a drainage problem. 5. Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceeding with successive phases of the job. 6. The issuance of a permit or the approval of drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation of the rovisions of the building codes or any other ordinance, law, rule or regulation. All plan review is subject t d Signature of Chief BUilding Of date INSPECTION REQUEST LINE: (303)234-5933 BUILDING OFFICE, (303)235-2855 REQUESTS MUST BE MADE BY 3PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. City of Wheat Ridge Community Development Department MiNOR BUILDiNG PERMIT APPUCAnON Property Owner:-Ann lIurl€-j f1;<XI~Tr\A.~+ Property Address: Lf"lW IG ph' Contractor License No.: 1C)~J.l" "j, . . Company: M u~ht- ~ 3,<;)(\ OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Building Pe~it Numbe(o'J I ;). t) ~ Date: Phone: Phone: ~3qq.'335'-1 Buildinq Dept. Valuation Figure: $ I hereby certify that the setback distances proposed by this permit application are accurate, and do not.violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations rriadearefa:tciJrate; that I have. read- and agree to -abide-by all conditions printed on this application and that I assume full responsibility for compliance with the Wheat Ridge BUilding Code (I.B.G) and all other applicable Wheat ____,_ RiQge Or...c!lnances, for work under this pennit. Plans subject to field Inspection. (OWNER)(CON1RACTOR); SIG'(='~...)~/~ ! (t.<.b DATE~ (OWNER)(CON1RACTOR):PRINTEO ~1l..d0l WIt.k DATE 1lty;'~7 , Value:$ '1@.s2- Permit Fee:$ Plan Review Fee:$ -Us~$------ Total:$ UseofSpace(descriptiOn):~ (CccA\ Description of work: ~j)ltJshroi"'u.b~' .0 plo.U' wi VUW CYoMovJ 1'- H4S - 2 ~ ;21. 2 ~ . Ie 33.3f i.i-tt.1 ,C;, I ~ Sq. Ft. added BUILDING COMMENTS: Approval: ~ BUlLDINGDEPARTMENTUSEONLY V I .)., \. , '-.: '( ONING COMMEl'fTS: /' Approval: t; J Zoning: 't' ." PUBLIC WORKS COMMENTS: Approval: IRE DEPARTMENT COMMENTS: Approval: Occupancy: Walls: Roof: Stories: Electrical License No: Company: Plumbing License No: Company: Expiration Date: AQQroval: Expiration Date: Apj:>[Qval: ___~_ Residential Units: Mechanical License No: Company: Expiration Date: _Approval: {1) This permit was issued in accordance with the provisions set forth in your application and is subject to-the laws of the State of Colorado and to the Zoning Regulations and Building Codes of Wheat Ridge, Colorado or any other applicable ordinances of the City. . (2) This pennit shall expire if (A) the work authorized is not commenced within sixty (60) days from issue date or (B) the building authorized is suspended or abandoned for a period of 180 days. (3) If this penn it expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been orwill be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes have been or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit (4) No work of any manner shall be done that will Change the natural flow of water causing a drainage problem. (5) Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceeding with successive phases of the job. (6) The issuance of a permit or the approval of drawings and specifications shall not be construed to be a permit for, nor an approvalpf, any violation of the provisions of the building codes or any other ordinance,Jaw, rl:lle or regulation. All plan review "is subject to field Inspections. Chief Building Official . City of Wheat Ridge Building Permit Submittal List The following items are required for the minor building permit submittal for the property located at -flM fLt" I~ . . If any of the required items are not included in the submittal, the sub ttal will be considered incomplete and returned immediately without review. . Minor permit is defined as: fence installation, signage, decks or covered patios, concrete work in excess of 500 square feet, sheds, garages and over the counter permits. You do not neecl to submit a site plan with over the counter permits. Tms-shei:>llllu:;l uti :;uulTlilled wilh lhe building fJermit apfJlication-'-PlmrseilTltialoeslCle each required item, signifying that it has been included. Review Required by: 0 Building o Planning o Public Works SUBMITTAL DOCUMENTS: PLANS: DOne (1) site plan Contents of plans detailed in the minor permits handout DOne (1) Elevations/detailspage DOCUMENTATION: DOne (1) completed building permit application DOne (1) property deed DOne (1) building permit submittal list .._.__._"~~._---~----._-_.--- ---- -- ----- - ---- -- - Call the inspection line before 3 p.m. for a next working-day inspection City of Wheat Ridge Community Development Department 7500 W. 29th Avenue Wheat Ridge, CO 80033 . Building Division - 303.235.2855 Planning Division _ 303.235.2846 Inspe"ction iine - 303.234.5933 www.ci.wheatridae.co.us Wall Sian Calculation Sheet You must complete this sheet and include it in the submittal package for any new wall signs. You will also need to create a site plan and a detail sheet of the signage. . Project Address: 1180 14\>""'5 '!,~ Contractor: kUJ8hh g;~(1 You are allowed 1 square foot of signage for every 1 linear foot of wall to which you are attaching a sign. All wall signs must be adjacent to a street or major interior drive. Step 1: Measure the length of the wall(s) where you are attaching the sign: Wall 1 - ~ feet Wall 2 - ~ 4(0 ,C;_ feet Wall 3 - feet Step 2: The length of the wall is the allowable square footage for the wall sign. Wall 1 allowable signage- Wall 2 allowable signage- Wall 3 allowable signage- square feet square feet square feet Site Plan 2','4 'l.2+ I:f., S ~-t ,. ~., ~ !\ ~ ) ~ ,l{)UGllf'Mt~~lOClOSR~MAlCHco.CY...NCUI:tl'GPMl,\\HEREKfEOWEONNlJGiJAAAMEE~fESOO:IOVAA\1NGCCM'AJlllllV()\Ulf.lCt~LSANDl'Atl1SlI'iD "\ I d CLIENT SUBWAY -/0 :A~ON . i SALESPERSON Igh!" sign Ph: 303-399.3334 Fax: 303-399.3395 , r. I .. 1HS DESlGN IS IHEPROPEIlfYOfKJ UGHT + S1GNNf)ISSUBMTTEOFORVOlMUSElN CONll.WCllONWllHAPRO.lCTBElNG "'-NHDFORYOUBYADUGHlIlCNflOl BE REPROOOCED EMf! IN WHClU: OR IN PAA1 WllHOUT KlR WRIIlEN CONSENt 0/31107 KEITH HURlEY .ll.lIl.l1.MNMHlOO'tAiSlUJ 1'20VOOIH.E5S0Il!IR'IIl!lSPKfIaJ 12JVAC ~~IImPON8lIl)NID fW!. H(X)(lf a'!rnlRSSIGIIC1OCUIIISliKORr: lICCAIeDfIO",N8.I!AAl.1#) Gi1~DTElMWl(iA'f'Alf:l ARTWOR< """, CLIENT APPROVAl I PRobucTlON Al'PR6\iAl 10 MFR. DCONCEPl\IAl. _REVISION: 11(21Q7 INITIALS: DATE: jl~I_TIALS: DATE: DF"NALAA1WORI( - DAlOOOCOON DO NOT MANUFACTURE WITHOUT APPROVAlS G CJSHOPOAAwtlG TH[BOXlSAllOVf:MUSrBENllALEDAND~TIDPRalTOMANLFACTURlNG P . OF FABRICATED ALUM. CHANNEL LETIERS WiTH 118" ACRYLIC FACES - RETURNS Of LETTERS PAINTED BLACK WITH BLACK TRJMCAP - "SUB~ 1/8" ACRYLIC WHITE - 'WAY" 1/8" ACRYLIC WITH 3M TRANSLUCENT 'YELLOW VINYL APPLIED TO FACE OF LEITERS INNER IllUMINATED VVlTH 15mm WHITE NEON LETTERS MOUNTED FLUSH TO WALL WITH REMOTE TRANSFORMER - NO RACEWAY Ul APPROVED ."IT,,~{:::TH:;S l"RVo.~ ~.Tq:on;G.',$0 ''':::V,Tj~''$J''''O~ :::-"CT'Wo\.T:;.,C:O:' "-,,ct.wJ:::300f " '~NV T~O:; T)~':"0 S:'l<>.:::::'T-'-a<:: ~~iJ~fi-m~::::::J ;'.::::-Y:iG !,c~cce.[;,,- .,Tr,,~ :"r,~'.O~ ><:'.rro)w~.r, @ _:::TT3JJ''/CTO, 'lO","A~ -"TT:::~ trJ~~W/::''''JJT::; ;-sw:.~"cr",,,.l"C~ T,~JETR~ 12()\'~Z"A;!Y o_,'cr:n ~".[Kf/H/ .!il 30' I ~~. ~I ..--/" " /--------) /" , /~ FLUSH MOUNTED: NEON i' " -.I' ~ \1 r'J yl ~!j' j i/~ !~) / 1,1/ , ! / i i ! I~ / i'/OT1USCALE Xd- Ct'"\ \<.ipl'<\j r' "^""",- 2'-0" 13'-3lh" 1/ 10'-71/4" ,,'\ y;~!; VJj-- /;;:) F / I / I I ! ' ~. ~- ~ ; i I I o Elec. 0 Plumb. 0 Mech. 0 Structural 0 Other o 1 st 0 2nd 0 3rd Job Address: 1'.# t'J7tJc;,.JO i/9,?c lIIY.',,,,l .; t. _ $'ir'.t.'.L.J: /1,;'~' // ,..!I /.> N C,'~I //)/.r ~ 1/9"?".~) J{~..J~i,.^././ ~1. "' ~"~-nl/. nJ'K'{ ,,"uO u-,,~,_.,<"~,,:.)( -oj.; .t!? ~'E.M..,r~~-:' f'C:c~~./" ". h"~' ".#E /() oRe-inspection fee of $ must be paid prior to re-inspection. o Blocked Access o No one available for inspection: Time AM/PM 'When corrections have been made, call for re-inspection at 303-234-5933 Date: /"'//'7/;J~ , Inspector: L"", DO NOT REMOVE THIS NOTICE "---_.._.._-~ .- ----_..._-,-_._.._.~"---," ~._.__.- .~-'-_. -- ,. _._--_..._--~_._..~,.,_.~- _.."'-~-- .-'--"--'." ... I ~ " ... City of Wheat iRidge Community Dev~lopment Department COMMERCIAL & MULTI-FAMiLY JJUIL>>lNG PERMl1' APPUCATION STEVE t~~6ES . '-i 'f &,0 IX. I f)LIIU G 5 r. Phone: 303 8'HP7700' 07 0102. FGC, Sf(.\h Building Permit Number: Date: Property Owner: Property Address: Contractor License No.: Company: c'fOIJ.GE.. /JItt'qI#W Phone: 303-1?'I-;3D1.1- OWNER/CONTRACTOR SIGNATURE OF UNDERSTA~DING AND AGREEMENT Buildinq Dept. Valuation Figure: $ I hereby certify that the setback distances proposed by this permit application are accurEite, and do not violate applicable ordinances, rUles or regulations of the City of Wheat Ridge orcovenanls, easements or restrictions pf record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this applicati.on and that I ,assume full responsibility for compliance with theWheat Ridge Building Code (I.B.C) and ali other applicable Wheat Ridge Ordinances, for work under this permit. Plans $ubJect to field lnsp~ction, Value: $ Permit Fee:$ Plan Review Fee:$ Use Trod; Total:$ (OWNER)(CONTRACTOR): SIGNED DATE {OWNER)(CONTRACTOR):PRINTEO DATE Use of Space (description): Description of work: PE~ ~/r # 0706~O . R.EUlf'O.v OF EXISl1/u6 PLJr-;V. \ llUll,. G DEPARTMENT USE ONLY ONING COMMENTS: .~. 'X r" . Approvat C). IY Zoning: /Q \ . BUILDING COMMENTS: /,\' ,x;.. r&.~ V Approval: #' .., :r-: f- PUBLIC WORKS COMMENTS: f\V--~ .. . Approval: Y ~ . . Sq. Ft. added SIC: Sq.Ft.: ~1S,r: Rill I.. ". "I '--' IRE DEPARTMENT COMMENTS: Approval: Occupancy: Walls: Rool: Residential Units: Stories: Electrical License No: 02 /3 S 2. Company: Tlfltf/\l1 eUcre_Ie PluJilbing License No: Company: Mechanical License No: Company: Expiration Date: Approval: Expiration Date: Approval: Expiration Date: Approval: . (1) This permit was issued in accordance with the provisions set forth in your application and is subject to the laws ofthe State of Colorado and to the Zonfng.Regu.lations-afltd. Building Codes of Wheat Ridge, Colorado or any other applicable ordinances of the City. . . This permit shall expire if (A) the work authorized is not commenced within sixty (60) days from issue date or (8) the building authorized Is s'Jspended or abandoned for a period of 180 days. If this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been orwill be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes have been or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. No work of any manner shall be done that Will change the natural flow of water causing a drainage problem. Contractor shall notify the Building lnspect~r twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceeding with successive phases of the job. The issuance of a permit or the approval c)f drawings and specifications shall not be construed to be a permit far, nor an approval of, any violation of the provisions of the building cod~s or any other ordinance, law, rule or regulation..AII plan review is subject to field Inspections.. (2) (3) (4) (5) (6) Chief Building Official t ;, j:' ';"! /:. ",i .;:, ;>: ., f.: 'x ii, " )< r;' ~5 ,.: ~';; . ", E~: ;;.'" t,' C,," E fV I> 'X" ;; Building Permit Number: 18383 Date: 2/23/2005 COMMUNITY DEVELOPMENT DEPARTMENT BUILDING INSPECTION LINE - (303-234-5933) CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80033 - (303-235-2855) Property Owner: GOERGE MESBABA Property Address: 4980 KIPLING STREET Contractor License No.: 18796 Company: Ziska Construction, Inc. Phone: 303-758-3137 Phone: 431 8665 OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I~erebycertlfy that the setback distances proposed by this permit application are accurate. and dp,nptvlolate applicable ordinances. rules or:regulations of the City of Wheat Ridge or c?venants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application, and that I assume full responsibility for compliance with the Wheat Ridge Building Coda (U.B.C.) and all other applica~I~",_\JV~~at Ridge ordina~~Sf'f~r~rk under this permit. .'.... (OWNER)(CONTRACTOR) SIG~:;~~ :~ DA~0J..t1S // c:; / Use: 'oescriplion : TEN€K(~'~INISH , ELEC~RICAL PLANS WILL COME IN LATER ALONG WITH FIRE ALARM SYSTEM BUILDING DEPARTMENT USE ONLY Valuation: Permit Fee: Plan Review Fee: Use Tax: $50,000.00 $836.95 $544.02 $900.00 Total: $2,280.97 SIC: Sq. Fl.: NEED ALL SUB CONTRACTOR TO PULL LICENSE Approval : Occupancy : Walls: Roof: Stories: Electrical License No : 18011 ~ompany:Larson Electric Expiration Date: 2/28/2005 Approval: Plumbing License No : 18805 Company: Tony V Plumbing & Heating Expiration Date: 9/10/2004 Approval : Residential Units: Mechanical License No : 19005 Company : PRATT SHEET METAL Expiration Date: 8/1/2004 Approval: (1) This permit was issued in accordance with the provisions set forth in yopur application and Is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Code of Wheat Ridge, Colorado or any other applicable ordinances of the City. (2) This permit shan expire If (A) the wor\< authorized is not commenced within sixty (60) days from issue date or (B) the building authorized is suspended or abandoned for a period of 180 days. (3) If this permit expires. a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made In the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new pennit. (4) No wor\< of any manner shalt be done that will change the natural flow of water causing a drainage problem. (~) Contractor shall notify the Building Inspector twenty.four (24) hours in advance for all inspections and shall receive written approval on Inspection card before proceedilng with successive phases of the job. (6) The issuance of a permit or the approval of drawl~gs and specifications shall not be construed to be a permit for, nor an approval of, anyviolatlon of the provisions of the buil~~~.25Xldes or any o~rJ)rd1~,~ce, law, rule or regUlation. ._/___,~::,,:_;p~'_c""/r-::"'" :;;;7 /- ' Chief Building.-fnspector Please sign Terms and Conditions on reverse side of page. ! :1 City of Wheat Ridge Commercial Sign PERMIT - 070714 PERMIT NO: JOB ADDRESS: DESCRIPTION: 070714 4980 KIPLING ST RETAIL SIGN - 20 UNITS, ISSUED: EXPIRES: ATTACHED 07/13/2007 01/09/2008 PER *** CONTACTS *** 303/399-3334 Keith Hurley 01-9226 Ad Light & Sign Co. INDEPENDENCE SQUARE GC OWNER ** PARCEL INFO ZONE CODE: SUBDIVISION: ** C-1 0041 USE: BLOCK/LOT#: UA 0/ Permit Fee Plan Review Fee Total Valuation Use Tax ** TOTAL ** ESTIMATED PROJECT VALUATION: FEES 521.83 339.19 ~e:~ 468:~~ JjL~~'I2~ 1,329.02 26,000.00 ** FEE SUMMARY ** Comments: MR: approved w/ 30' setback for sign. JS: approved per engineering. I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance with the Wheat Ridge Building Code (I.B.C) and all other appli;'fble Whea~Ridifr~ancea, for work under thia per~it. plana aubject to field inapection. LiJ')!'~'v'; 11 / [ ~ ~ Ilk} I/(:rn signatu e 0 contrac r/owner J f date This permit was issued in accordance with the provisions set forth 1n your application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Codes of Wheat Ridge. Colorado or any other applicable ordinances of the City. 2. This permit shall expire 180 days from the issue date. Requests for an extension must be received prior to expiration date. An extension may be granted at the discretion of the Building Official. 3. If this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes have been or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. 4. No work of any manner shall be done that will change the natural flow of water causing a drainage problem. 5. Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall rece1ve written approval on inspection card before proceeding with successive phases of the job. 6. The issuance of a permit or the approval of drawings and specifications shall not be construed to be a permit for, nor an approval of iolation of the provisions of the building codes or any other ordinance, law, rule or regulation. All plan subject to field inspections. Signature of date INSPECTION REQUEST LINE, (303) 234-5933 BUILDING OFFICE: (303) 235-2855 REQUESTS MUST BE MADE BY 3PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. -- City of Wheat R.idge Community Development Department MINOR BUILDING PERMIT APPLiCATION hcperty Owner: 11\Ck\Xlfl~ 8co~-Z.. hoperty Address:4'12:lO'4'\"lO \L,'pirtj st CDutra::or License No.: 0 I '1l.l.1., COillpany: M L.9ht- +-Slsn /~ '~Y_,,(M'A '10 '1,~) c.;' 1"'1) \~ 6/) ~61- Ol~ Building Permit Number: Dcte:~~ 0101.ll( Phone: Phone: 303, 3'1'1- 553'-/ -- OWNER'CO~TRACTOR SIGNATURE_OF UNDERSTANDING _ AND AGREEr.\ENT I Buildinq Dept. Valuation Figure: $ I 'lereby certify tr,at the setback distances proposed by this pennit application are accurate, andJo not-violate app[jcable ordinances, rules or regulations of the City of Wheat Rid':;le or covenants, easements or restrictions of record; that all measurements shewn, and allegations made -are -.recur-ate; that I have :-ead'and agree- to abide by all conditkns printed on this application and that I a:3s~me full responsibility for ::onpliance with the Wheat Ridge Building Code (l.B.C) and all other applicable Wheat 3.idg_e q.r~~inanc6s, for work under this permit. Plans sl~ect to field ins ection. :CWNE""ICON"BACTORI,SIGNEO I/Alaltd- Utc6 DATE ~ 1<1/01 (ClIINER'{CON-cRACTOR),PRINTE:irYlQJY'.((l Wh':l~) DATE 1-14/01 . \ Use of Space (descriPtion):~ ",,:+-c,-.J Ce,scription of work: Value:$-..;2,l.c:t:O Permit Fee:$ Plan Review Fee:S .~Use-+ax~$-- Total:$ Sq. Fl added d.J / ,JV BUILDIN~PARTMENTUSE ONLY ONI~G :;~~~r U \ ~{" o'.flj , Zoning: 0,;., 1) ;?\ ~ I';-, "UIC:ING CWMENTS. , if % y ,)J A:JprovE.1 V ~ "-..... ~J ' PL13l ::: WORKS COMMENTS: \J. f'j... Approval: SIC: Sq..t.: OCCJ;)ancy: Walls: Roof: Stories: Residential Units: I ~IR~ DE?A;TMENT COMMENTS: I Approval: El""ct~ical License No: Com~any: Plum ding License No: Comp"ny: Mechanical License No: Company: -.. ------._--- ----------,---- ---~--------------~----- Expiration Date: ~\~illrt;Yf!J. Expir3tion Date: ApJ)LQ~___~ Expiration Date: Approval: .{J ::5:, This peIT:1it was issued in accordance with the provisions set forth in your application end is subject to :he laws of the State)f ColoradCi and to the Zoning Regulations and 3uilding Codes of Wheat Ridge, Coi::JradJ or any ether a;):Jii:abie oc,::iinan:::es:;f the City. Tlis perT:lit shall expire if (A) the work authorized is not commenced within sixty (60) cays from issue dale or (0) ~le building authcrized is suspended or abandoned for a period of 180 days. ]f this permit expires, a new permit l7lay be ac:quired f::>r a fee of one-half the amount nJrmally required, provided :-:0 changes have been orwill be made in the original plan:3 and specifications and any suspension:x abandonment has not exceeded Qne (1) year. If changes have been crif suspension or abandonment exceeds one (1) year, full fees shall be paic fOI a 'iew :Je:rit \Ie work of ary manner shall be done that will change the natural flow of water c312sir'9 a drainage pr:::blerr.. Contractor shall notify the Building inspectot" b.venty-four (24) hours in advance for a:1 inspections a:-"d shall ;e:-eive w:-iite:~ a:Jproval on inspection card before proceedhg with successive phases of the job. T:<e issuance of a permit or the approval of d~awings and specifications shall not be construec to w$ a perTl" br, no" a:: a:Jproval of, any violation of the provisions of -:he bUilding codes or any other ordinance, Jaw, rule or regu:atior.. All plan ra'. iew is: subject to field inspections. <. ','/ (2) (6,1 Chief Euilding Official Freestandina Sian Calculation Sheet You must complete this sheet and include it in the submittal package for any new freestanding signs. You will also need to create a site plan and a detail sheet of the signage. C'Ol.OR/>S,o Project Address: L\~'?()-L\.~() \(;oli<js'+. Contractor: M- L.1~,1tt- + 3(~ () You are allowed 1 freestanding sign for every street right-at-way adjacent to your property. The allowable sign size is related to building size. Step 1: Determine the square footage-of the-ouitdirrg: -- -------BuilEl1H~sii!':e-tifl--squ3re feet): 4{ m~1 (:J:Ris.-will-fle-inserted--iA-tt:le-formula below) Step 2: Complete the appropriate allowable signage formula: If the buildin';J is 0 - 1,500 square feet in size, you are allowed a 35 square foot sign. If the building is 1,501 - 5,000 square feet in size, complete the following: 1-1,501 = 1 l + 50 = + 35 = I ] Building size Allowed sign size If the building is 5,001 - 50,000 square feet in size, complete the following: 1-5,001 = 13'125S- 1+500= 1 I L\L\-, 2310 Building size I'O.SI 1+ 100 = I 11 ~J. s-11 Allowed sign siz; "'\'2t' (~1&3- ~. '* " If the building is 50,000 + square feet in size, complete the following: 1- 50,001 =1 l+ 1,000 = I I + : 90 = I Building size Allowed sign size -..--- -- ---------------. - ------_._------~---_.._- The "allowed sign size" may be placed on each side of the freestanding sign. o Check her~ if the sign is existing and you are replacing a cabinet or face with the same size cab net or ,ace. "[J. n., ( . rl" 1 (~sc; \V\.WI / 'f Ml [..e oti- 1- <] f-V'-l'l'\\t\:Qd SO i 1Illrt'- Continued on back SlLC 2.4>-1. CA 01 The sign must meet a setback from the street right-of-way. If ,he sign is less than 7 feet in height, the sign must be setback 5 feet. If the sign is between 7 feet and 15 feet the sign must be setback 10 feet. For most freestanding signs, the maximum height is 15 feet. For properties within Y. mile of the interstate, freestanding signs may be 50 feet tall. These signs must be setback at least 30 feet from the s:reet right-of-way. Step a: Determine the height of the new sign: The new proposed freestanding sign will be d--~ feet tall. l.ndu.tL\~ ~ Step 4: Determine the setback from the street right-of-way: 3:{::J \ The nl~W proposed sign will be setback ?-D feet from the street right-of-wa:L All freestanding signs must adhere to the sight distance triangle requirements as listed in Section 26-603 of the Code of Laws. You must include a site plan which details the location of the freestanding sign, building and drive areas. Show all new and existing signage (include the square footage and height of all existing signs). Please include a detail of the proposed sign, including the overall square footage and heigrt as we!! as any electrical and structural details which may be pertinent. .~ ~~'~"""'~''"'"~'''==re::;l..'';';~=~"'''''''W.,"~-":;,,_,:':']''-'i;;:C:U~;: ,-.,",o.~~,._",,,,~",,.~..,.. ._'" ,'-~~--'"--',-, '-.-C:T~"'" ""~"="';%-:t=:l,"'"",===----",='='S~~='-";':=0:=,=Z'=>::;::""IEL::;'-:l",tZ_'",'C,'C='E~",--"==,~=,.-.,L':;:;;-:';;',,,; , . . ~~~!1f.JIiIII!I~lti~11!!lr.111~!1~1~~~~11111~ti11jjjiiiiiiiii~EFJiiiiJrr"""" ! . 7'","C4~d~~~~~li~~~:ii~"'''W7"n i ~ 110 ESSEX FINANCIAL 4980 - 4990 KiplliDg St 1 GROUP Wheat Ridge., CO ." Qln r..o.O"TAl l.l.,- r''''....--..F'' Fi:rst Mortgage Request JulV 2006 i 1 .~ -~ '~ ~ ~ i ~ I ~ 1 l 1 J J ~ j 1 ~ j .1 J 1 'I ,j , ~ I i . i 1-- """-==-=~""""-~~'''''''''',,,,,",,'__''''''.''''''-=~---'''.''',",''''''","=",,=~c,, ~ ~_",...1 ,4 ~ I~~\~ I , ~l ,;>- ...1 'I j 'J ! '~ -~ 1 j '.J._ ~ j 1 ~ i 'j SE at SubJ" ec1l:.! ., . 'j i , I Dete~:::~ond, ] 1....-;] 0 d o--c\~w v I ~ ~,)'V. ~ ;1 I ~,~~~ I I \j0" . "r,JJ'/\-VV' I ~ ,. "~"o:) M;;;~- ~ ';;;;;;;;;."'''",'''~_'_'"ID""wm+. ~' .. ~==~===";:l',=)=ll====!:a<"-"~=,",''''=r.n=,,,_ - ~"'" . .' . .' 'v=c.m--==~_ '~:F;='.'> Monument Signage at East End of Site ~~.H'...~.. ~\%r'\<l,~ ,lo \ ~ " I..j;, , I ! , ii ;; I" i; " ~i :4 \[<:111 WILL (MWM 10 llO\!ll ~ll(H mOil, IM(L@IW PH\, ~['f \I'{ClFIEO W{ CiN~OT (IJ!Itl~lEE H' ~IJ! TO V\~"N( (nH~I!IBlIII1 n! \1 "' .HIIPI , 1lllllllHIMI1FII 111\Plll\ "11111IW\l111 IIHIF\\ (JMIWIW WE lAC PRlHIR1 P{IWEITh lNIi IIHlI ~OOIIJ" Il'l ol\lm ~r~ tI~nllli\1 RfOllIRf IllII HOT HllllIW,liW (IOUH~ lERMII Al VAl A~JWO"'~ r'IcAS~ r CLllNT APPROVAL - dlighl CLIENT INDEPENDENC~ PRODUCTION APPROVAL 10 MfR. THIIDEIIGNIITHE PROfERTYOf AD liGHT + CC()OIC~ld"'l ,IGN AND 1\ IIIBMITIIO lOR IOIIR U\E IN lOCATION XXXXXX W ~L'v;,!Ori~.U)! INITIALS: DATE: INITIALS: DATE sign CONJUNCTION WITH . PROIEL! BEING DATE 03112/07 [--- tiNA, '''~iw()~r, PLANHfD fOR YOU 8Y AD LIGHT. IT (,I.HN(J/ , -" ~(jI.;,Jr:![l', L~(J_t'l n T f\i\8JJ!.lf!'~,Cl!.lELW I T I lQUL6J:l'EL! Y.!\L~ Sf UPROOUCW EI IN WHOLE OR IN SALESPERSON Keith Hurley TI'f Bntf\ ^~()V' .'TIAI FJ AII~J r;A1F; r~I()f! In I~ArdlfA( 111ft P(j OF " ml WITHllUT " .>IT " " ,)~AtI;';(, ----- . - i), " f' '!i" " 1 " " u ()if ((It -~ u o -.--'::-. LUKE'S STEAKHOUSE ~ 0 STATE FARM INSURANCE SOCCER STOP -..--.- .. - 0 EDWARD JONES CHIRiiPjfAj;folfSMASSAGE 1-:-' 0 __.OOG GRI!!lM~... ROSSI'S CATERING DREAM DINERS LA PIAZZA ,-- _m-~-v1NyLiPMSOOI6Rs --~ _ BERRILJGE URRA CO! lA II BERRIDGE COLONIAL RED :~__J BERRIDGE SIERRA TAN L_._j 230-20 WHITE _ 230-63 RUST BROWN f PHS 48 o 230-149 LT.BEtGE I PMS 468 C c " ~ \\ \\ 1,\.\ '-"":'. " j-,';',', ',,- ,,' .""" '7\ . 1,""" 7\ '.7\ 1, ^ ~ '1J r ~ Z G) W 4 AI m m 4 \ \ \\ 1, 1, HORZ. SCALE: i 1":::: 10 l '"", ~~ <D 1 j~ , ""' .' ..l ,J ,. City of Wheat Ridge Community Development Department Building Inspection Division -'-~~ 'NHE4t 1'" '- 0 - C> u co C'OL OR I'SP Plan Review Notes 1 st Review 8/6/07 Ad Light and Sign Attn: Amanda White 4150 Elati Street Denver, CO 80216 Ms. White, A review of your submittal documents for City of Wheat Ridge Permit #070714 for a sign at 4980- 4990 Kipling Street, Wheat Ridge, CO 80033 , demonstrates the need for engineered drawings that reflect compliance of the proposed footing/foundation, structural, and electrical systems of the sign with the following codes: 2003 International Building Code 2005 National Electrical Code In order to proceed with the processing of your permit application, it will be necessary for you submit the requested documents to the Building Department. Should you have any questions concerning the required documents, please feel free to contact me at 303-235-2853. Cordially, ~J- ~"umacher, Jr., CBO Chief Building Official City of Wheat Ridge Building Department 7500 W. 29th Avenue Wheat Ridge, CO 80033 Office (303) 235-2853 Fax (303) 235-2857 I Oct.22 2007 9:52AM AD LIGHT AND SIGN lightosig I Fax I I To. k.ri51tJ From: Aman~Wh~e F;oo 303-235-2857 Pages: 4 ! Phone: D<lte: 10 f1 Re: 4980 Kipling St-Independence Square CC: I Sign Permit- Engineering I o Urgent 0 For Review 0 Please Comment 0 p...1 Reply No. 2133 P 1 fillS . Comments o Ple....e Recycle ~ = = ~ ... trWt'M!l !IO:00 i'Il4l(flll HiIRIlCWflM1~MI:i~'MI1I; ~,I d ~ /0 lig01 I .~ sign Ph.:30J..J'iP..JJJ ox;31XJ~99~9 TIC: Pfl(jM 5 TnE ~klli'mIOF" If&1T ~ ll&r.l.llfJ5UBHrnrOFOltfOft'ft'll-ll 11- [O~IJllnIOIl WfN ~ ~RO(W Wf' ILNI"!~ fOllro IT ill LliNI.. CAIMil'T 8l "!tumiD urm II....HOIE (IJ II , ,fW wlIHorr rHI ~ li'LnlrW Ollmr. CUEi'IT LOCAIJON --_.~.-~ DATE .-----------. SAl.ESPERSON "rlltllMO ~r~ 11.111 '.". \W l'IUS31llnllillE .lI'Il1ll~. ,- r-~~-" _ CONCEPJUM . .i i REVl~O'l: 1- .------ i -:'FNl\LJlll'lWCfl't 1._____'_'-"__ ,l"'--i~=:G . " IC._~~_ -- NITlALS DATE DATE - - DO NOT MANUfACJURE WITHOUT APPROVALS TH~ IlOJCESl<bOlfE h/Il(srlH ....."I.Oo.ClD AND D.\UD PRIOR IOMANUh"C1U~lNG PG. OF :2' """ ~ ~ ~ 1 = = = = = """ 0- = = ~ = """ i '" ~ a J I ~, .1 =-. II m m ~ o =~ J o :..i..'".;.'.lllr.::Q~.'(:".".~.:'~l.':.'.j ~i'f. 6.:~"GC..'...'..~"\~~ c', !!!UI;~lJillUCiI1 . .flMZA .,;.;.4~ '-,'".'~ '-~.-, '''-., .~" '-'.-,':.'~ ;---_.,'.';~._;-,.'..... ., :.~., ~__-i'_; "''-~:-,<:;~'--;'i"-'-'' ,0,' '_. ' !: STATE FARM INSURANCE -J>- ._, ...;:+ !" SOCCER STOP \ ,~'.:; - n -- fi;: EflWARD)0NES , 0 .i{ cr,'f: ~IROPRACTOR & MASS~GE ~ ,;'b[ DOGGROOMING 2V1 ROSSI'S CATERING i,~;J DREAM DINER~ J::;; LA PIAZZA '~"-'" " :--~- T T i..\o C.R V\~c--T..... ~<!.. ~t~ owr~JUfl.l\llf~OOf' 1ft WllW.nu(l(>>D IEllnWIK-'i mn PRODUCTION APfROVAl TO MFI{ NITIALS: I "=~';;; ~ i . 1......__ \ o I -0 " ~ Oct. 22. 2007 9:52AM. AD LIGHT AND SIGN CHISHOLM CONSUlTING SERVICES.. LTD. StrllCwnll Engineers 1074 S. Alkire St. LAKEWOOD, CO 80228 (303)914-8202 No. 2133v""'P. 3~ J08~~IJ/,M:d~, LJtr..Jp.~Lt- )yuu(: ~400 ~'rl;~ ~ .....'00>. \ ""J_ CAlCIAAtaJ BY -,Wlltu G, ICt sh """lE I a III (6 "7 ......"""v1"~:tt'()o.,6S. o^'" L,' ~ - . . . . , , I. . ! S' : F' J I.; :." , ' : ,Ir~ o,v.~lt,b... , ....,.'.,. ...., ...... ;.. .'..,..... ,...-......'.-1.,". Soi.l~ ~~'7 p(.~}Q'C(;IJi...dd:d ',5a"I~I,~d 14f~14(!{tli>1~"u! lS,o.'f? bJ r'~L(~~I;~1 at 1$0 tli tor ,~Jt . H 0 ,Jt;yt~, :......!.., ..;.,.. . , ..,.'. : " ..,.. '., ..: _. : Wi,^~ ~ladroO",t~,i;{fC~()r, C,!,....fJJ/":(I,~f~t . . I ;WO"3 r~G:,' "'rL' : :: t'l; :r.~"'~' :,...,,~.-.,; ; .!....(.n;,r. :\":,: ,~'" \ .~- ~..._._'." :u+-...:-_,,~..,+,.~., l : 51'p tl!,Il.10,O ,.~ 1O-0.,P.I!,I~"',~y je ~r'1~tlY~IQ\~T: .~d.f: (Qh, QI T~I ~fQ~:' Iril~,...!f:oLfall~l~,&o~, ,: .::' .,:..; " : :. ',,', ~:;..:,", <. . wii,fit>;vrc m~I-S'i z~,b.{i, "W,~Jtte1.irjlf \:$}-u{~Z~JL., ,.~. _,..H; , . '. ,...," AP,PRO'VED , ), VY.t'.JlouJ,.. (lo~"ilI)~i~I,~i~f).:J','O 'i,~Q-{ F,,~.'T SUbj~ctIOF\eldlns~ecti~n~ . .. (roft)(s- f+ X.t4,[I~f) ~1'2~S '~~i 1jt ~V +; i Wheat Ridg~ Building dep!.: , 1 Itlof OVt1tVf~\~J MI.,e~t.; t~,oJ~}c1i5 m;':((~~~!I)(/zsft); ~Q'{]i':-I~"... ' .'. D:te.c......; , Signed.i...... .. .. .~...,+.....Plan Chec r .-.: I.. : "1" .. . i., :.'. '. .,:. . L.. .':' 1. t 1I(~.k{~J.J,4[o... J~.L'~~ ~O" ~ 1 ~',t?Ld.tel' : . W[ly~t, ,~O~ 1\," 51'r~rWliJ~i.r 100.0 \~~,~ ,,( .1 ~ nso I~{. . !..' . .... ; . " :' .;' .:. ., .;. ~ .. i .. t91~( 7YOS \1. . . I . ciD'-I~ 7'-'1, .~ ,5 .' ).i'~(h.:j+:'lrO!('~', :! . ~I' (l.S ft) "0,0 fi K'(Oo~~t>lz ~ . 1,- c (Z,S ft)(3,O{P( lot?f;lI : ~~: (Ls(f)(3,O~t)hs.qIIDlv ...!... I,'. ~l~O\\,.., I ' 61);)[1,; : g II' 16.5 .,. '" 'Ill. ~. ., -' ~ ~ . <> -, 'N' : IOTHIQ II \T, . -, 5 ,I 0 'd' ~~i. I. ,";. ,,~ ~ ell t ~)(: tlJ.r, .,.t.I:lp,^,(~~.. . . >-:..: ,n......-:. .....1 :5? -==.. ~ . (PSQ!IXc,011)d (P50:1\)GbHh~J6~~I~)(z.0#.L"" "" o l7Vl)j l\X ('l~ {tl.,!Lm'I~I\'_~_{<<JY:t1:IO'.:L": . ~ ~ ~, Ily tocti"yW ~r. 10'-0" JUF' : i. ' <>>ely~f<lilt 11.:. . ;)il~ w~;,kt "pO~H": ... . t.t.I.La.lID G.. ' ,.....; I ,. , .,i.. f, .f, . . : HrOf\( ~~. loo/I .... , . . SQ',) teli\t,'~jO'\~l. .'. ' ! ". P,' (zsft)t",br.HH tdOOp~/u !i3?~.u, ~,. (1st"f)(},}3(t)J iOOOp>.{J < ilI~i1lI\ o '(.' ft" 't) ( . I)' L' , , r-i' ,,5. -1\3,~'T'.5OVf)1Il ~.. lP~'1 II. .... : ." ..', ' .~_...",., ..:" .. : ,i .".. . ;F" :.- . \, _' . i :. . ..I... ;. ...:,.. .n,. . .., ~ :.. ..: 'I"" S~; I ~Q.\(ft;~? MO"l/.L 'l rn~ /llll..zt ftJ.4_ [Z.13gMI;lr7.{fJ t[ (1,~'1: 1~)~z:Li{i}+ (~!IOIIX~~{tJ:, .,. 09 11~ "'1'l11..! ",..,...... .,---"~- * Oct.22. 2007 9:53AM AD lIGHT AND SIGN CHISHOLM CONSULTING SERVICES. lTD. SlnIctural En&ineer$ . 1074 S. Alkire St. LAKEWOOD,CO 80228 (303)914-8202 ~'.... r....jJ . No. 2133I1"P. 4~(<". .JOB~;~~I IJ!J,,.J/~u1'lm.' ~q~~ K.;f"'f 5t "."""". 7. I. e,--L tl.'l.OAATelBV W&lter G.j(e~ke Dm to!n/o7 , . 10 ~ II! 1007115 """",li 5' ~7110.H~' ,. ~~'6J I~I. . F, S. ,: 1;1/ <'t~O ,: , :..' .:...; ; j - ~, '.. 7 f'1 [OO~;~J10"WJ If '..0 , Jttf " : WLi,hl;. J~ H 11. . \iyk'-Ut~1~tc. r~ [I. tot.1 ' gno II. .. , . . . . . .1 D:. i.if";' . "'. ! 'iou: ).L7t$ II1 ,.~.Uc,5 .~... ,.,.: . 9," (tSHkl,t\J1)(lroo;~OV~"IQ7~gH. ,. -.P.' (z,5Wl):b1{lXli()Of~f)," :0n,m : ~; < (t, ftJl 1.1<7 HX S50f)DIZ r . .t.5!o"ll. . ( 'j 0 ,I, M.':I' . . )01, N:'I\l\ll.t'f'~iO: " '.: (J07i!.~ IIhwW ~G07ggl~XI:8,.,,~t) . t (mol')(!8~(t) 'Jat 30 (')((:Z5 tf) " , n,-s.l HI.'. " , ., . U. · l.S0 >.(,5,,01(: \))E ~OOTJN~l~b"~~ II~O" :.. . ; I 1 . <.' Cf.. f II " ,./,,_ J ,Wt ,Ll ... . .,.. . ~fi~ '10 ~ ~ ~H), 4~5 ~~~ '!'II~, ,. '- ./' ' , : Iry TS'8q~,y~, S; Ig,~ i. +,-111(1" c$H31'; " ~~~4h";.... . h. 21,6 h,'. :....... o~, : U5{ TS .tXilx y~. .l;r~.j~:tl~~r~' ~, Kd~fo,(ti~ G" '.~ s L ~'!: (..I 'Ill! ., ., , .. ...0 .. , i , .....,,~J,I' '"' , '" I Pli p~ fl5~pf . 'f' if'OO'flF i..... ! .. .... ... ",,' '".W , I. . ... I '" . .. ' i ji j:' i ,. ,. i, - ~ .... . ,.., ~ 0= ~ "'H, . ''''l 1:.- , {. !'. P{ ....lr ,.' . ...,:,. ,... ~ ; ..~ :;.- "':r:: III .....~,. ~ ... L.lP,r~ -'1 -. ~04~7'.& :.<<{)"f;tm~ fr ;,.-.. itO~lt'l p" Wfflll: n.. V<5s~LNQO ~, ; I . 'tl' i; ,': I'. .... ..... . HIIO. W, 01"'," . ~1 "0 i .. . ~; ',I. . .. ,:,lJJS :0,. : ; . ~ ; : ',:" : Subject.to Field I Mpeolion$ .;" , . ~ , . .. . . -- ,. t. ,- ..... , Wheal Ridge Building D~pl: . . , . , 0p .. ...... . ", 1/' '" , .. " ...;Dale...~../ .0.7 ~ :, : , - j , , " ; Signed..... ...'. .. , .:...~........F;lan'Checker o0f~~ """" . Q ~ . ;ii...~..,1se14: !"~'. l"'i.\ .. :J 01,,' r ." \~: IOrtH:l "', ~~ '. ~.",... ., "." , . ., "fijONJll' "'~.,.."'. . ""lIm"\\\V " I City of Wheat Ridge Commercial Miscellan PERMIT - 070620 PERMIT NO: JOB ADDRESS: DESCRIPTION: 070620 4980 KIPLING ST FACADE RENOVATION ISSUED: EXPIRES: 06/22/2007 12/19/2007 *** CONTACTS *** 303/765-2490 303/898-4700 303/698-2110 GEORGE HARTMAN STEVE HODGES Torn Ryckman 07-0102 EGC SERVICES, INC GC OWNER sub 02-1382 Team Electric Inc. ** PARCEL INFO ZONE CODE: SUBDIVISION: ** C-1 0041 USE: BLOCK/LOT#: UA 0/ Permit Fee Plan Review Fee Total Valuation Use Tax ** TOTAL ** ESTIMATED FEES 2,383.95 1,549.57 .00 4,500.00 8,433.52 PROJECT VALUATION: 250,000.00 ** FEE SUMMARY ** ~E] Comments: BM: plans approved, SS: OK per comments MR: Permit approved signage. subject to all field inspections from Arvada Fire District. with note regarding roof appurtenances not being used for I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulati ns of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and all tions made are accurate; that I have read and agree to abide by all conditions printed on this applicati and that as full responsibility for compliance with the Wheat Ridge Building Code (I.B.C) and all other ap 'ca e Wheat for work under this permit. Plans subject to field inspection. 'r 1. is permit was issued in accordance with the provisions set forth in your application and is subject to the laws of the tate of Colorado and to the Zoning Regulations and Building Codes of Wheat Ridge, Colorado or any other applicable ordinances of the City. 2. This permit shall expire 180 days from the issue date. Requests for an extension must be received prior to expiration date. An extension may be granted at the discretion of the Building Official. 3. If this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes have been or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. 4. No work of any manner shall be done that will change the natural flow of water causing a drainage prOblem. 5. Contractor shall notify the Building Inspector twenty. four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceeding with successive phases of the job. 6. The issuance of a permit or the approval of drawings and specifications shall not be construed to be a permit for, nor an approval any violatio of the provisions of the building codes or any other ordinance, law, rule or regulation. All plan r is subj t field inspections. Signature 0 date INSPECTION REQUEST LINE: (303)234-5933 BUILDING OFFICE: (303)235-2855 REQUESTS MUST BE MADE BY 3PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. Property Owner: Property Address: Contractor License No.: Company: '""""'''H;~' ~ ~I" . . .' {J~ ()- ~r(lO(P ')'0 City of Wheat Ridge Building perrhii Number: Community Development Department Date: COMMERCIAL.& MULTI-FAMiLY BUILDJNG PERMIT APPUCATION ~t'rcllt: 44e)d~t i '1q eo. Itf.:,.il'h3 (f)~OIOZ CGC ,S, nl'(ct. '> f /t7c. .".,...., C"';;' Phone: 303-8<;8-41CO Phone: J03 ~q~,.-30Z 2.: OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Buildinet Dept. ValuatIon Figure: $ I hereby certify that the s.tback distanc.s proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this applicati.on and that I assume full responsibility for complianc. with the Wheat Ridge BUilding COd.... (LB. .C) a'!!ail other applicable Wheat Ridge Ordinances, for work der t permit. PJi'hS ~ect to field InspEl;ction, IOWNER)ICONTRACTOR): SIGNE . '" "', <,"~ ~"""'ATE# (OWNER)(CONTRACTOR);PRINT DATE Va1ue:$l~1eC Permit Fee:$ Plan Review Fee:$ Use Tax:$ Tota1:$ Use of Space (description): Desorlptlonofwork: ~ ~~ Sq. Fl added ONING COMMENTS: Approvai: Zoning: SIC: Sq.Ft.: BUILDING COMMENTS: Approval: :.It ~/', PUBLIC WORKS C Approv I: /?cZ.o /'",.5""r"'~ IRE DEPARTMENT COMMENTS: Approval: Occupancy: Walls: Roof: Stories: Residential Units: Electrical License No: Company: --r~ gkcC-' Expiration Date: Approval: Plumbing License No: Company: Mechanical License No: Company: Expiration Date: Approval: Expiration Date: Approval: (2) (3) This permit was issued in accordance with the provisions set forth in your application and is subject to the laws of the State of Colorado and to the Zoning-Regulations-and Building Codes of Wheat Ridge, Colorado or any other applicable ordinances of ~Q~ . This permit shall expire if (A) the work authorized is not commenced wllhin sixty (60) days from issue date or (B) the building authorized is suspended or abandoned for a period of 180 days. If this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the original plans and specifications and any suspensiol) or abandonment has not exceeded one (1) year. If changes have been Of if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. No work of any manner shall be done that will change. the natural flow of water causing a drainage problem. Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceeding with successive phases of the job. The issuance of a permit or the approval of draWings and specifications shall not be construed to be a permit for, nor an approval of, any violation of the provisions of the building cod~s or any other ordinance, law, rule or regulation. All plan review is subject to field InspecUons. (1) (4) . (5) (6) Chief Building Official i I OS/29/2007 12:17 3034327995 ARVADA FIRE DISTRICT PAGE 02 Division of Fire Prevention p.,8VAD"q 1l.~I<- w Ji ~~. p';; " C ""~ 0%1 (\'~~' A iG 0- 'S' = Arvada Fire Protection District Project Name: Independence Square Shopping Center Locati.on: 4980 Kipling Street Date: 5/29/07 ReTI~edby: SparkyShriv~ 6) 7) 8) 9) I) Fire protection is proTIded to this site by Station #1 located at 7900 W 57th Avenue and Station #2 located at 12195 W 5200 Avenue. 2) The building address numbers shall be pennanently affixed to the building in a minimum of 4 inch numbers on a contrasting background. Recommend labeling rear doors to the businesses. IFC 03 505.1. 3) All weather Fire Department access roadways are required to be a minimum of24 feet of unobstructed width. (new outdoor patio) IFC 03 503.2.1. Amended. 4) Fire apparatus access roads shall have an unobstructed vertical clearance of not less than 13 feet 6 inches. IFC 03 503.2.1. 5) Fire hydrants shall be installed in such a mann.er that the 41/2 inch discharge nozzle is a minimum of 18 inches above finished grade. A minimum of three (3) reet clear space shall be maintained around the circumference offire protection equipment. IFC 03 312.1. Gas and electrical meters shall be identified with the address and or unit number. IFC 03 603.9.1. Amended. "NO PARKING FIRE LANE" signs may be required to be installed. Signs shall meet the City of Wheat Ridge standard~. IFe 03 503.3. Any outside doors blocked from the inside shall be labeled "DOOR BLOCKED" Trash enclosures including doors shall be of non -combustible construction. 6503 Simms Street . Arvada, Colorado 80004-2607 . (303) 424-3012 . Fax (303) 432-7995 08/22/2007 15:53 3034327995 ARVADA FIRE DISTRICT PAGE 02 Division of Fire Prevention p.SWAD.4 1l1~'.\.l.J :n ~CIIOt\:) ^,,~I?"'~O ~\~(>~~ ~\S' <G ~ Arvada Fire Protection District -.--"'-.-.-.-- ProjectNaxne: Independence Square Shopping Center Location: 4980 Kipling Street Date: 5/29/07 Reviewed by: Sparky Shriver 1) 2) 3) Fire protection is provided to this site by Stalion #1 located at 7900 W 51" Avenue and Station #210cated at 12195 W 52nd Avenue" The building address numbers shall be permanently affixed to the building in a minimum of 4 inch numbers on a contrasting backgroWld. Recommend labeling rear doors to the businesses. !FC 03 505.1. All weather Fire Department access roadways are required to be a minimum of 24 feet of unobstructed width. (new outdoor patio) IFC 03 503.2.1. Amended. 4) Fire appa1'lltus access roads shall have an unobstructed vertical clearance of not less than 13 feet 6 inches. IFC 03 503.2.1. 5) Fire hydrants shall be installed in such a manner that the 41/2 inch discharge nozzle is a minimum of 18 inches aoove finished grade. A minimum of three (3) feet clear space shall be maintained around the circumference offire protection equipment. IFC 03 312.1. 6) Gas and electrical meters shall be identified with th.e address and or unit !lumber. IFC 03 603.9.1. Amended. 7) "NO PARKING FIRE LANE" signs may be required to be installed. Signs shall meet the City of Wheat Ridge standards. !FC 03503.3. 8) Any outside doors blocked from the inside shall be labeled "DOOR BLOCKED" 9) Trash enclosures including doors shall be of non-combustible construction. 6503 Simms Street . Arvada, Colorado 80004-2607 . (303) 424-3012 . Fax (303) 432-7995 ~, ..,~. ';""~..,;;,:: ':,~ "'", " - . k;,_"__,,,- ',,^ ',~:" . ., . '/' 8tHlding Permit 0fI1Y OF wtlBAT RIDGE .' 7S00WestmrkAv- 1.'; ,co:, .._,_,- ~.. 00110033 . 3(13.~S.23n' Pemi\t Nulllber ;";,t,,: ,'," ,;, . ..; -, " ~esidential Plumbing. , '-''<1,- '\~-<; X,. c' >'-,," ~i ,i'<- -' , .,", ,J.' _' ,_ ,'- ,~ ',1 ' '~I\OI'JllTV 4980 Kipling St oWlWJ: . Westwood Church ': ,~. :jj-. ",';'".' ,-: ~Iion Gas P,iPe ':':, 't'~r. Unit: . (3j)3) 219.16l6 , ,.j( "<'j " " _,'1' ,I, :;i,'- ;'( , " ;0' ,',,,. lH20~ics.1Ihc~ . ,', ", "_ii, ,,' UCl!IlSl! # 122457 ,;-' . . ~ 0(".1 RItIa, PH8eftlfTMIt! " " . ...... 8:/1 eR$/FUlNACESAMlHw~~~GV:~ , '. - ~ 4EATI!lI8A MlNIMtJ AFIie. ~'M/Cv., t'A~A MOF.60E/',lERGY'___p';' '__1( THERMO~ :AT Fi"'~~ OF .93 ENERGY rwnlll':' It-Z1 WAUs . R-38 Cl;I~I'-! cePT HYORONIC~. .~ · a.fl CRAlM.I-. ..' '. c., , 'co"~ , "', ,,,,~, ;,-, " . j{;'~:.',~t;~_~ ", . }- -,~-,;', - ';" , ,'-, ' 1 . ';' ,~~f~ . ~......,.' WaDs: Roof: Stories: SqFeilt: 0::1,' ":~'''~'V.,..''''byddJ''''applla:tioD'''''''~_ do DOt vIoIaalJlll"'Ie~"~~ITI "~e~~1 ~"'~olm.ml;1IlI11B-t. ..iboW.t..............eanaceiili.te;:..J..ftI ........ .r\ ~_Afj~ .....1..... tdrupoulbllllyforcomplilitcewtllr. die Wbut IUdp Bv.iIdi8cc.a:.(L..e.)........~ ';t~ ~ror....~..penak. , '" ,;,"_i,,', L'r ,'I :-'}SiQlt;rUJA~~-':-'>~~~;'~~~: \,~O~;~l0:;, ,-:' " ,', ' . ,', ~~:' __'- "--;' ,:>~~t' ] _'''__'-~_~''''j~~''di.~letrorala)'OtU'applIadoa''''lIlA1bjcet''dle''Wlor''Sh&ul~~.~1O''~ ,,:,'..<, ;<_'~'''' _ _', _Of""-JUdp.CoJo...doOl'hl)'othlirappldlll..nllll..-eofdle(:lty. '." <: _',-' h~' _ _ 1",; ~:"~,, ",~"j "-""i ;--~,~it'~,"'~~."'WorkOlllbellte.""""'~"'(lG'MltlJ-.--dwldl~J"~.~"'Ir~'1nik -J'..':,: ';'-j~:."'~~"""""II~orilb........tu.pcdId.t1lO4.,ufterdledllWof-n.1i ,~l"" '"'>,, _ , ,1', ": '<"', " "'--," _' :', ': r" '<_ ',' _,," , ' ~, ' __ ' . ',', j~"d, !' ':.', ,-,',' ,j ,','-'-, ,\...:" ~ , ',3' ',,' _'~:..,~~~~~",:'~eacq.....ti~UfeiOf~IIl.......t~","""""riW""""'~~.1'i~h~1!"'lii 'j " "':~""'''' "'j~ ~J1:'.""",,,,,,,,,, ...~t",.............(1)~.If..,..~......-~..'1IIt"',t" 1 ~ '_: "',- ,;~<:!-- -....'...(l)~~...~tHipawfOr.lle'lf....,... , , ." ,- ! ,~ " '4 "~_~.d:'II!I1~''''''''e\~,'''tdcUDpthU'''''''DDWof.....ea",-,dnlaappnblca. , ' ':",'" ;,"" ,_ _' <" i,<F'-' ,;,-" 5 ::",;__,~~~_:~........~...(U)llountaa4vuc:elor"luper:tIlNUlud"'aD.reoeIu.......~IiiII-~~~\ .:...-,-..........."...1... .: . . , ,\t;_~;cii ..~ ora ....dO...haI.otbeCOlUlnldlGbe.........tror.....lUl~_.,.__,,.....~,,. , ilfe ,,' ~',_ ~"otPr .."',....r repIHIlm. !' "-, ' ,.";",,1";' , -~"-- ~ " uaiJ:: 7 " , . - , , , " ' ~' " ' ' , . W~Y. No....b..t~, 2005 :-~ ,: '. PUol COMMUNITY DEVELOPMENT DEPARTMEf'lT' BUILDING INSPECTION LINE. 303.234.5933 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80033'. (303.235,2855) APPUCATION Building Permit Number: Date: . Property Owner: tv ~ )T '" OD l) (HoJ 0( <. 1-1 Property Address: 'If 80 g,,ot'Aj '-, :) 1 Contractor License No.: ;) ';). '( -5 7 Company: H"2. 0 J\'1 Cl.I-C"'Ar I L s:. ,,.., { Phone: 1 0 '} J 1 ~ . 1<..1(" Phone: 7;) ., fJ 'I. ,., If :f OWNER/CONTRACTOR SIGNATURE OF UNOERSTANDING AND AGREEMENT Bu/JdinCl Dept, Valuation Figure: $ I hereby certify that the setback distances proposed by this permit "application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance with the Wheat Ridge Building Code (loB.C) and all other applicable Wheat Ridge Ordinances, for work under thIs p.ermlt. Plans subject to field inspection. , (OWNER)(CONTRACTOR),SIGNED J?.,..( <- DATE 11- )0 . Value:$ lS-bO~ Permit Fee:$ Plan Review Fee:$ Use Ta.x:$ S Total: $ (OWNER)(CONTAACTOR):PRlNTED DATE Use of Space (description): C,,q) Description of work: PI pe Sq. Ft. added ~ONING'COMMENTS: Approval: Zoning: BUUDING DEPARTMENT USE ONLY SIC: Sq.Ft.: BUILDING COMMENiS: Approval: PUBUC WORKS COMMENTS: Approyal: IRE DEPARTMENT COMMENTS: Approval: Occupancy: Walls: Roof: Stories: Residential Units: Electrical License No: Company: Plumbing License No: :l? '-f :s 7 Company: H J 0 f'I1.. (/l/g",(<.5 Mechanical License No: Company: Expiration Date: Approvai: Expiration Date: Approvai: Expiration Date: Approval: . (4) (5) (6) This permit was Issued In.accordance with the provisions set forth In your appllcation and Is subject to the laws of the State of Colorado and to the Zoning Regulations and BuUdlng Codes of Wheat Ridge, Colorado or any other applicable ordinances of ~~ .' This permit shall expire If (A) the work authorized Is not commenced within sixty (90) days from Issue date or (B) the building authorized Is suspended or abandoned for a period of 180 days. . If this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been orwill be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1)-year. If changes have been orif suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit No work. of any manner shall be done that will change the natural flow of water causing a draInage problem. Contractor shall notify the Building Inspector wenty-four (24) hours In advance for all Inspections and shall receive written approval on Inspection card before proceeding with successive phases of the job. The Issuance of a permit or the approval of drawings and specIfications shall not be construed to be a permit for, nor an approval of, any violation of the provrs!ons of the building codes or anyotherordtnance,law, rule or regulation. All phm review Is subject to field InspectIons. (1) (2) (3) r.hiAf Rlliirlinn Official City of Wheat Ridge Community Development Department Memorandum TO: FROM: Accounting Department Kristy Shutto, Building Division @ SUBJECT: Refund for Permit DATE: May 27,2005 Reason: Payment of Use Tax on property with Colorado Exemption. 4980 Kipling St. Please refund: 100% permittee: 100% plan review 100% use tax: $ $ $900.00 (acct 01-510-00-516) (acct 01-550-05-551) (acct 01-500-02-505) Total: $900.00 TO: Ziska Construction 4090 Field Dr. Wheat Ridge, CO 80033 Thank You! ~~ M. Shutt() Bldg. Dept. Secretary BuildingPermit CITY OF WHEATRIDGE 7500 West 29TIi Avenue Wheatridge, CO 80033 303-235-2855 Commercial Tenant Finish Permit Number 18383 2/2312005 Inspection Line 3D3,234-5933 PROPERTY 4980 KIPLING ST OWNER: GOERGE MESBABA Unit: 303- 758-31 Description TENANT FINISH, ELECTRICAL PLANS WILL COME IN LATER ALONG WITH FIRE ALARM SYSTEM 1 IDue 1$836.95 1$900.00 1$900.00 1$2.636.95 I I IUcense # 118011 119005 118805 118796 IFEES !Fees IPermit Fee IPlan Review Fee luse Tax :Total Fees I ICONTRACTORS IName ILarson Electric IPRATT SHEET METAL ,Tony V Plumbing & Heating IZiska Construction, Inc. Vults: Occup.uey: Walls: Stories: Roof: I Hnby certify IIut dM.-back dIIt:a.- p.-.pnecI by c.... ~ applicadcNI an ac&:1Il1Ite,..d do JtOt noa.ce .pplkallle."u. WlIeatlUdte w COYCllalltJ, _eats... RIb1cdou .freeorcl; dull" __mb dtowa, utI.....dou IUd, an aecwau ..CMKtIdou.....1cd _ dtb .~.. ud thll__faD,..,.....llky ror_~ witlI the WMat IUdp B.lkIiIICC Wlaut IUd. onUauca."" wed ..... dUt ~ (OWNER){CONTRACTOR) TIW penalt .... '-ed hi aec:orduee wIdro tM pnl...... .. JordI .. y.... applka" aad b .IIbJKI to dte b_ of dM : R.epbdou..d a.JJdloI& Code .fWlteat 1Udp, eot.nNto or..y.tIter applkllble ord.._ of tJH: City. This pmMt'" eJ:Ph if("\) dae....-k ..dMriIted b..c ~ wtdUalhty (60) up frv. bI., elate or (B) die b ab.lllI~fw.peri04of12ed.,.... Udall penaituplrel...... pawM..y be IlCl!ItdreciI fwa Cet.,..........tlu~ _t.-.lty reqalre4, pnlvided.. It orf:&iaaI...... aH IpCdIkadetu ud..y........... "'~I w... ueecded Oft (1) year. If daa.pI an_ ureedI_ (I) yar. fd '- sUI be,....,.,.. _ .--Jt. 4 No wort..r..y -.c:r JIaaII bold.- dtat wtII o.CIr t111r ..tanl"'w .rw.ter auUaca ~ pntb~ ! C_1rader IIWI Mtlfy 1M BddiItc Iup<<tOf' t.-ty-,"" (104)....n III Hu_....... tQpeed_ ad ..all'ftdft WI ~CwttII__~p~.ftkjob. 6 TM a.a.ct of. per'*k or aM approl'al .r dnwtap PCl tpedAcadou .... ... M WIIIb'1le4 .. be' a pendl for, ..r a ~ .fllM b.adiaC toda.....y.a.r onMu-. taw, Rk or repladoa.. CllkfB1IlJd1ac lMped... Friday, May 27, 200S I IPaid 1$836.95 1$544.02 1$900.00 1$2.280.97 I I IPhone 17722054 14218259 , .........-........1:; I 1 I I ~ I 1 CITY OF ~T RIDGE 02/25/05 11:04 AM cdb \ AI10IJNT 900.00 ziska construction RECEIPT NO:C0189+6 \ Hl':>D BUILDIJ<<J USE T~X but l BUILDIJ<<J USE TAX F MSD BUILDING PER11IT5 bp BUILDING PERMITS,FM5D ZONING FtAH REVIEW F zprf ZOHIJ<<J FtAH REVIEW F 836.95 5#.02 PAYMENT RECEI~D Cl( 9611 TOTAL AMOUIH 2,280.97 2,280.97 Mar" 11 05 02: 58p . OR ,to (W1) DEPARTMENT OF REVENUE 7375 mERMAN S'mEET DENVER. COlORADO 8:J2I61 n.US UCENSE IS NOT TRANSFERABlE Brid(';eCenters 7208749501 p.1 State of Colorado CERTIFICATE OF EXEMPTION FOR SALES AND USE TAX ONLY CORNERSTONE CHRISTIAN FELLOWSHIP 12930 W 32ND AYE GOLDEN CO 80~01-5~01 .,', - . , ,~ ',. ."' ,<. ':-~ ~. ~ '. " "',..~: ../ " _.~ to ~.'I~.~ ~; ~'::'~<~'; .j:_,., ISSUE DATE :'," ;,..d :. ',"' :~t , ::;..... (-:.':,_L.. \ -..>. ~~ . :.~-. -, '~<~:'~~(,:~~~:\,>,<~':'~.f ' ACCCMNOT_ I L\4BtJTY N=ORMATlON 98-06571 11 042 5999 9 010186 DEe 22 1988 ~~~- 12930 W 32ND AYE GOLDEN CO Ex<<UIIw Dnccor . ~"'A__ ,\ ~'/' ,u0'7 C~-:'t:/ ~A'/f7'('''t'V'''' ~--/tCk .#,,-J .I ~'1;>[F," gOC?>? /J~f/:J~lCJ /}~~O I -I ~. IY v 1fV~j.;" Certificate of Completion And/Or Compliance City of Wheat Ridge 7500 W 2<7h Avenue lVheat Ridge) Colorado 80033 THIS CERTIFICATE VERIFIES THAT THE PROPERTY DESCRIBED BELOW, DOES COMPLY WITH THE WHEAT RIDGE BUILDING CODE, ZONING AND OTHER RELATED LAND USE AND DEVELOPMENT LAWS OF THE CITY OF WHEAT RIDGE FOR THE FOLLOWING PURPOSE. PERMIT #18383 Tenant Finish Date: 4,// v?nnli Owner: aeor.ge Mefhaha Owner Address: 40Jln T<ipli'l1g "t # A "-0, 1VhPl7t Ridgt', rn Rnm~ Property Address: Same Contractor: Ziska Construction Contractor Address: 4090 Field Dr., Wheat Ri4ge, CO 80033 Chief Building Official: Zoning Administrator: -,- .. FINALS EJeclricaI Plumbing Mechanical Frame /Interior Finish R.OW & Drainage Fie Department Parting & Landscaping -NOTE: ADDITIONAL INSPECTIONS / COMMENTS ON BACK OCCUPANCY NOT PERMITTED UNTIL CERTIFICATE OF OCCUPANCY IS ISSUED PROTECT THIS CARD FROM THE WEATHER Framing ~-I<-> (":'/<- ,j\.~ Roofing Insulation Drywall Screw OJ\.. I I ()li~v Do NOT POUR FLOOR UNTIL ABOVE HAS B "1/-t's ~I <Y J\ . c/ll dle EJeclricaI Selvice Rough EIecIric Rough Plumbing PJr Test Gas Piping Rough Mechanical CONCRETE SLAB FLOOR EJeclricaI (Underground) Plumbing (Underground) :;ul-r- Cl~ ,1M '\ Heating (Underground) - POUR No CONCRETE UNTIL ABOVE HAS BEEN SIGNED INSPECTOR MUST SIGN ALL SPACES PERTAINING To THIS JOB FOUNDATION INSPECTIONS DATE APPROVAL DISAPPROVAl INSPECTOR COMMENTS: INmALS Footings/Caissons Stemwall Reinforcing or Monolithic Weatherproof / French Drain Water/Sewer Service Lines </iY,Io r/;/J.,; /2, '(,'tJlJB tuK Job Address J- Building Permit No. Owner _ Contractor Contractor Address Inspections will not be made unless this card is posted on the building site 24 HO'!t!Jlftice required for inspections sJ Date Issued ~ Occupancy Type 1500 W. 29th Avenue Wheat Ridge, Colorado 80033 (303) 235- 2855 <7' ll1&.ect./ofl Line QQ3J 23~~93.3 . "'TION ~"':CORD .f f"(if ,:\\.. . Place in Visible Location for Inspector ADDITIONAL COMMENTS & INSPECTIONS: 3 - 1&""-<::' s;- ~ _ \s;--os ,3- \~-_cr 3' I <;-_0 S- :s- I.s;-C ,- 3.-<.I-(J~ :, ,-21 - C. '> 'L r '.N ,"2> ,-U. I L yl1 ~\\l,",~ \-\,~'f-'~J ~n~--- K ~ ~ "" ,--T 'oN ,,-:0-.\,") R.~ 0 l<:... )lA.~ , ~ \ \1J<. -...;; ~\ ~""~ 0 \<- I~' C~<-..,.. .y':"I"",""~ OJ': J &:...'6 \::>"'-D \':\S;- Cll( [~ ~e; \;"''1 (vov-.\- 3/<-1 C>,k. \ \0 boct ~v ~ L~ll ~p(uep~ ~0efL S'46 Ie, If q, {-of- ~L<t0 L \ ., - C 1.~ ~1~ ' ...-~ .. 'm~\..,.J J,~\ '?.~ r<Mc.1M. \, '"'^" '" ~ Qll D-\,,,,,0\,"~ '<"".....-. R.[, (L'M ~z. V ~-2...\-~ t;;~ "",. 'm,""",,,,!,',,,,,~" " "~F"""'" 1.''''r~''~",",''''i~l!li'i~~~~!!~,,",{\H~''1II..i!!! ~Ul'ln_.~ umlJilll'i~' ill.\...~~.lI'Ji~lftW COMMUNITY DEVELOPMENT DEPARTMENT 8UILDING INSPECTION LINE. (303-234-5933) CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80033. (303-235-2855) Building Permit Number: 18549 Date: 4/5/2005 Property Owner: GATES MINISTRIES Property Address: 4980 KIPLING ST Contractor License No.: 18011 Company: Larson Electric PhOne: Phone: 772 2054 OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Valuation: Permit Fee: Use Tax: I herebyceitify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants,8l!iSemel1ts or restrictions of record; that all measun~ments shown. and allegations made: are accqrate; that I have read and agree to abide by all conditions printed on this a~pllcation, andthat 1 assume.full responsIbility for compliance with the Wheat Ridge Building Code (1.!3.C.) arid all other applicable W t Ridge ordinances, for work under th~J;~ J" (OWNER)(CONTRACTOR) SIGNED - AT~ Use: $0.00 Tolal: Description: FIRE ALARM INSTALLATION (FEES INCLUDED UNDER TENANT FINISH PERMIT) BUILDING DEPARTMENT USE ONLY SIC: Sq. FI.: ARVADA FIRE DEPARTMENT HAS A coPY OF THE pLANS Approval: Occupancy: Walls: Roof: Stories : Residential Units: Electrical License No : 18011 Company. :Larson Electric Expiration Date: 2/28/2007 Approval: OK/KS Plumbing License No : Company: Mechanical License No : Company: Expiration Date: Approval : Expiration Date : Approval: (4) (5) (6) This permit was Issued In accordance with the provisions set forth in yopur application and Is subject to the laws of the State of CoI0f'8do and to the Zoning Regulations and Bunding Code of Wheat Ridge, Colorado or any other applicable ordinances of the City. This pennit shall expire if (A) the work authorized Is not commenced within sixty (60) days from issue date or (8) the building authorized is suspended or abandoned for a pariod of 180 days. If this permit expires, a new pennit may be acquired for a fee of one-half the amount normally required. provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment exceeds one (1) year, full fees shall be paid fora new pennit. No WOrk of any manner shall be done that will change the natural flow of water causing a drainage problem. Contractor shall notify the Buildi nty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before pmceediing wi 5i ses of the . The Issue . ~~,ap drawings and specifications shall not be construed to be a pennit for, nor an approval of, any violation of the provisjcm(i 9=:: .. r ordinance, law, rule or regulation. (1) (2) (3) , ". Chief Building Inspector Please sign Terms and Conditions on reverse side of page. ~' WHf~,.,. ~ / ~ " - 0 U ~ COl.ORp..~O COMMUNITY DEVELOPMENT DEPARTMENT BUILDING INSPECTION LINE - 303-234-5933 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80033 ' (303-235-2855) APPLICATION G<~~s~ 49~ J<:: -rkr;;+ -#-A~ /gO/( ,n ' ?-o-\SO"'- L.~ Property Owner: Property Address: Contractor License No.: Company: Building Permit Number: Date: 1/5/05"" Phone: OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Phone: Building Dept. Valuation Figure: $ 1 hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application and that 1 assume full responsibility for compliance with the Wheat Ridge Building Code (I.B.C) and all other applicable Wheat Ridge Ordinances, for work under this permit. Plans subject to field inspection. (OWNER)(CONTRACTOR)SIGNEO~ DATrIf/lz) (OWNER){CONTRACTOR):PRINTED l..... -'2-- DATE~II~ Description: ;:ii'ie IHA-4tA... W5.77'fL...ljf-777J/t Sq. Ft. added Value:$ Permit Fee:$ Plan Review Fee:$ Use Tax:$ Total:$ 060. BUILDING DEPARTMENT USE ONLY Sq.Ft.: ONING COMMENTS: Approval: Zoning: SIC: U1LDING COMMENTS: Approval: rJl!.JJ J"ri)A F. p, /) H/lS e CJ P'J OF tpt./MJS VBLle WORKS COMMENTS: Approval: IRE DEPARTMENT COMMENTS: Approval: Occupancy: Roof: Stories: Walls: Electrical License No: I8'D \ \ Company: LOJC ":, ~ ~ ~ Ie Plumbing License No: Company: Expiration Date: Approval: Expiration Date: Approval: Residential Units: Mechanical License No: Company: Expiration Date: Approval: (1) This permit was issued in accordance with the provisions set forth in your application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Codes of Wheat Ridge, Colorado or any other applicable ordinances of the City. (2) This permit shall expire if (A) the work authorized is not commenced within sixty (gO) days from issue date or (B) the building authorized is suspended or abandoned for a period of 180 days. (3) If this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes have been or jf suspension or abandonment exceeds one (1 ) year, full fees shall be paid for a new permit. (4) No work of any manner shall be done that will change the natural flow of water causing a drainage problem. (5) Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceeding with successive phases of the job. (6) The issuance of a permit or the approval of drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation of the provisions of the building codes or any other ordinance, law, rule or regulation. AU plan review Is subject to field inspections. Chief Building Official Division of Fire Prevention Arvodo Fire Protection District Bronco Fire Alarm Systems 3704 Osage Street Denver, CO 80211 RE: Gate Ministries, 4980 Kipling Street, Wheat Ridge, CO. The following are our plan review comments for the installation of the fire alarm system; 1) Fire alarm evacuation signals shall be subject to field inspection. Additional units may be required. 2) The installing contractor shall provide calculations for the sound level in the proposed area or building. Upon completion of the acceptance test, the contractor shall provide audibility test results to the Fire Marshal that show compliance with the decibel levels as required by the fire code. 3) The permitted shall provide written certification to the Fire Marshal that the system has been installed in accordance with the approved plans and specifications. 4) Fire alarm systems required by this code shall be supervised by an approved central, proprietary, or remote station service or local alarm which will give an audible signal at a constantly attended station. 5) A satisfactory test of the entire system shall be made in the presence of the Fire Marshal. All system functions shall be tested. 6) An approved key box shall be provided on all buildings containing a fire alarm system required by this code and shall contain all keys necessary to again access. 7) All low voltage wiring to be inspected by the Wheat Ridge Electrical Inspection Department with documentation provided prior to acceptance testing. 8) The kitchen residential fire extinguishing system shall be supervised by the fire alarm system on a separate zone. 9) Manual pull stations are required to be installed at designated exit doors only. Verify required exit door systems prior to installation of pull stations. 6503 Simms Street . Arvada, Colorado 80004-2607 . (303) 424-3012 . Fax (303) 432-7995 10) Any code requirements arising from construction. 11) Twenty-four hours notice required for all tests and inspections. Kent "Sparky" Shriver Fire Marshal Arvada Fire Protection District Application Date: 0')- {}\\..\ Permit# . ARV ADA FIRE DISTRICT 6503 Simms St. . Arvada CO 80004 303-424-3012 . 303-432-7995 (fax) Contractor Information Site Information Address: '"\"\ to \.l..~~,,,,, ~'" Business: (-,0..\:10.. ("(\'.. ,..\',,6 Contact: Name: Agent: Address: Phone: Phone: I attest the above information to be accurate. I have received and reviewed the Inspection Compliance and the Fee Schedule. This permit is the property of the Arvada Fire District and is issued subject to conditions contained herein. Upon any failure of any condition including failure of clearance of any permit payment, this permit is subject to immediate revocation and the permit must be returned upon demand to a representative of the Arvada Fire District. Signature of Applicant: NonCE: If construction is started prior to the Issuance 01 a perm~, THREE (3) times the normalleel will be essessed. INSPECTION BY FIRE DISTRICT REQUIRED? Post this permit in a conspicuous place. Request required inspections a minimum 0 NO ys in advance at 303-424-3012. TYPE OF PERMIT FORMULA (sea fee achedule sheel) FEES Tank Inspection No. of Tanks = Review Alarm SYStem Plans SYStem Value= Review S rlnkler SYStem Plans SYStem Value= Review Misc. System Plans SYStem Value= Review Buik:Jina Plans Valuation= Soecial Handline or Use Plans Valuabon= I TOTAL FEES DUE Date Paid AmI. Paid Method In~lals o Total Building o New D Meration DPartial Other Field Inspections and Dates: Hydrostatic Tests and Dates: Comments: FIRE DISTRICT APPROVAL IS REQUIRED PRIOR TO THE ISSUANCE OF THIS PERMIT. <.. Date 11 TYPE OF PERMIT FORMULA (sea fee achedule sheel) FEES Tank Insoection No. of Tanks = Review Alarm System Plans ./ SYStem Value= Revtew Sprinkler System Plans System Value= Date Paid Review Misc. System Plans System Value= AmI. Paid Revtew Building Plans Valuation= Method Special Handling or Use Plans Valuation= In~ials I TOTAL FEES DUE A R V A D A F I R E D I S T R I C T p E R M I T 03/24/2035 10:25 3e34318594 zrSVA :ONSTRUCTICJ'~ PAGE J3 Application Date: .2. I.... 1/ IJ,s , , r,"',- D\ 0 Permit # AAVADA FIAr:: DISTRICT 6503 Simms St. . ArvBda CO 80004 303,424-3012 . 303-432-7llll6 (fax) Contractor Intonnatlon Site Information Address: \.'.\ ?i) K. <':e c..,),.., Business; L-'<A..l.t-~ ~'\\,t""" \'t:,1;,. Contact Name: Agent: Address: 7\~\.-,~ \I'.\..."" ~/"l 0..C\ (Q _L-i..... ..L ~~ 1"\ '\" ~,. 2\~~r.A,. ~..\A \)<,...c. Phone: Phone: '", ">,\- ~\ ,a,,\ I allast the aboVe infor'1'la!ion to be accurate, I have receIVed and reviewed the Inspection Compliance and the Fee Sc~edule. This petTl'Iit is the property oIlhe Arvada Fire District and is issued subject to conditions contained herein. Upon any failure 0/ llflY oond~ion including failure 01 cl....rance 01 any ~m'\it payment, Ihi. ~m'\it i. .ubj..,t to Immediate revocaMn aOO the pe1fTlil must be retumed upon demand to a representative 01 the Arvada Fire District. $gnature a Appraca.nt. NonCE: .1 conslrUC11on illW'lad prtor EO th. ;nuanee 01 a perml1. THReE (3) tlm.. the ftOrmtlll f"1 will ba ......Hd. INSPECTION BY FIFlE DISTRICT REQUIRED? YES NO POll thie permit In a ~UOUl otaCI. .~Ulil" r~uired map.ction8 8 rninirJl um of in .ctvence at: 3CX)..42.f-301 2. TYPE OF PERMIT FOIlMULA (_ --'-1 Nn. Y""". Val_ 0- FEES Da. Paid ..., -. MIL Paid /~~ - MtfUlULl .:.i~'? ~.. lmialo " v Va TOTALF~SO~ ~ EJ = BuUding ~8f8ljon t::1 Partial Other Field InsptlCllOns and Dales: Hydrostalie Teats and Dates: Comments: ARE DISTFIICT APPROVAL IS REQUIRED PRIOR TO THE ISSUANCE OF THIS PERMIT, H ~rowd 8lllubmttted ! ~ _1::1t1 ~prC1VCd (See comT~:~ , ("4"\.., \ ,. \ Date .. I~ \ I,\~ .' ( m- TYPE OF PERIIIT FORMULA (_ lei 10_1. .~Mt) fEeS T_' .ol ana _ V " Review Sprinkler _ PIano Syslom VaI_ 0.... Paid ROIIiow MIoc. S.._ Plans System VII.... Aml PaId RC\ilow 8ulldlna Pbno ,,"'- -... SpedaI Hondlinv or u.. Piano Valuolio... lnitialo 1'I!!!5 DUe A R V A D A F I 1 E D I jS T I I C T p B I M I T -,...-..,.....-'...".. ,.,.;"....,..-"......--. .. STOP WORK ORDER YOU ARE HEREBY ORDERED TO STOP WORK LOCATED AT I L\ c~ 8: a \<~ \ \-. \ \ y\ (~\ '-.J BY ORDER OF THE CITY OF' Wl-lEAT RIDGE BUILDING DEPARTMENT F'OR THE FOLLOWING REASON(S) nJ C) ) 't' ....Q \- 0"- \ ~ ~. ~ ._".~ 0\ \j \ {\ y\J , \.2..J-. ,-~...jl,< \ \.).J c~ \ "-\ ~. \'V"' 1"\ , i \<5 y y,,"\\- This not.ice may be removed ONLY by THE CITY OF' WHEAT RIDGE BUILDING DEPARTMENT I Date 2..... - \ \ -.('\ c~ \ I i / Building ins,pector ~-... \ "', "-'1. \' " , I ':x '_ -- \ - --"'--~----------_.~--..~..._._--,.--_.,._.~'---_.~..."._-.-. ---.--- ~---..... ..-.., --~. ._.__.._--._--_._._._---,.--^"-----_._-~..~-<------,.__. ."._-_.--,~-_..__.,_. -.,,- rMI~~~'+!IJ.'ll'IW1W:'lli""'""'~~J' ,~"""",,,,,,,~~~,:!Il'Il,-~' l!1I!ll!l'l~_ 1,1.11 !MIUm ,(,1-"~I~llllll:lIl,,I"lIIIIIlJlll.~m!IIL~~ f ~ COMMUNITY DEVELOPMENT DEPARTMENT Building Permit Number: 18268 '" BUILDING INSPECTION LINE - (303-234-5933) CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80033 - (303-235-2855) Date: 1/19/2005 I I Property Owner: GEORGE AND RUZEUN MESBABA property Address: 4980 KIPLING Contractor License No.: 18796 Company: Ziska Construction, Inc. Phone: 303-758-3137 .oWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Phone: 431 8665 I hereby certify thet the setback distances proposed by this permit eppllcation are accurate. and do n'ot violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenal"lts. easements or restrictions of record; that all measurements shown. and allegations made are liCCUn!lite: that I have read and agree to abide by all conditions printed on this appUcation, and -that 1 assume full responsibility for compliance with the Wheat Ridge Building Code (U.S.C.land all other applicable Wheat Ridge ordinances; for work under this permit. (OWNER)(CONTRACTOR)~7..d ~V-./ DATE /-/9'-a...s- / Use: DE~SIDE OF CHURCH Total: $0.00 $50.00 $0.00 $0.00 $50.00 Valuation: Permit Fee: Plan Review Fee: Use Tax: O$scrlptlon : BUILDING DEPARTMENT USE ONLY SIC: Sq.Ft. : lW~ Approval : Occupancy: Walls: Roof: Stories: Residential Units : Electrical License No : Company: Plumbing License No : Company: Mechanical License No : Company: Expiration Date: Approval: Expiration Date: Approval: Expiration Date : Approval: (1) This permit was Issued in accordance with the provisions set forth in yopur application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Code of Wheat Ridge, Colorado or any other applicable ordinances of the City. (2) This permit shall expire if (A) the work authorized Is not commenced within sixty (60) days from issue date or (B) the building authorized is suspended or abandoned for a period of 120 days. (3) If this pennit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the origlnal plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment exceeds one (1) year, full fees shall be paid fora new permit. (4) No Work of any manner shall be done that will change the natural flow of water causing a drainage problem. (5) Conti'ectOr &hell notify the Building Inspector twenty-four (24) hours In advance for all inspections and shall receive written approval on inspection card before proce8diingwlth successive phases of the job. (6) The i$sUance of a p&nTIit or the approval of drawl specifications shall not be construed to be a permit for, nor an approval of, anyviolatlon of the provtsions 0 nyoth law, rule or regulation. spector Please sign Terms and Conditions on reverse side of page. COMMUNITY DEVELOPMENT DEPARTMENT BUILDING INSPECTION LINE - 303-234,5933 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80033 - (303.235-2855) APPLICATION Property Owner: G(}o'JI.... 9t ~)(t!q" /?f'e..J'h.,6f:,'f. Property Address: r9Ji10 /C" ,/,"''::;' , /f - ..) - - ? Contractor License No.: /;>79" V Company:.? /7 .-/ ....-< ?f'/-I.., t' ~NJrMz)e-""/~H ~~ OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants. easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance with the Wheat Ridge Building Code (U.B.C) and all other applicable Wheat Ridge Ordinances, for work under this permit. , __ICOtITRACTORlSIG=Z'/ .J~ oAT'/'/'l-C/ (OWN~R)(CONTRACTOR):PRINTE . . DATE Building Permit Number: Date: Phone:.;70J-7-.SJ'- ..]/..7,7 Phone:...7&..l-f':7/ ~C:J- Value:$ Permit Fee:$ Plan Review Fee:$ Use Tax:!!; Total:$ I- Description: -7~. ~ "",. -" ' ..J-/v,t:'G/O-'<>' rc t!'~"cL. C!..h?l>Z J, t/j~- 0"'" C:;MO fh-, ;/;.v Sq. Ft. added BIDLDlNG DEPARTMENT USE ONLY SIC: Sq.Ft.: ZONING COMMENTS: Approval: Zoning: BUILDING COMMENTS: Approval: PUBLIC WORKS COMMENTS: Approval: !occupancy: Walls: Roof: Stories: Residential Units: Electrical License No: Company: Plumbing License No: Company: Mechanical License No: Company: Expiration Date: Approval: Expiration Date: Approval: Expiration Date: Approval: (1) This permit was issued in accordance with the provisions set forth in your application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Codes of Wheat Ridge, Colorado or any other applicable ordinances of the City. (2) This permit shall expire if (A) the work authorized is not commenced within sixty (60) days from issue date or (B) the building authorized is suspended or abandoned for a period of 120 days. (3) If this permit expires. a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes have been or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. (4) No work of any manner shall be done that will change the natural flow of water causing a drainage problem. (5) Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceeding with successive phases of the job. (6) The issuance of a permit or the approval of drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation of the provisions of the building codes or any other ordinance, law. rule or regulation. ~, 41 - ~ ~ CITY OF WHEAT RIDGE Building Inspection Division / (303) 234-5933 Inspection line (303) 235-2855 Office - (303) 235-2857 Fax INSPECTION NOTICE Inspection Type:21d/J - / % S! C Job Address/Permit Number: t - r i .rte ❑ No one available for inspectio Re-Inspection required: Yes IN When corrections have been made; i Date: ~l1 Inspector I-jme AM/PM for re-inspection. at 303-234-5933 COMMUNITY DEVELOPMENT DEPARTMENT BUILDING INSPECTION LINE - (303-234-5933) CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80033 - (303-235-2855) Property Owner: Property Address Contractor License No. DREAM DINNERS 4980 KIPLING ST #A-3 20472 Phone : Company : Lighted Business Signs Phone : 662-8361 OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this. application, and that I assume full responsibility for compliance with the Wheat Ridge Building Code (U.B.C.) and all other applicable Wheat Ridge ordinances, for work under this permit. (OWNER)(CONTRACTOR) Building Permit Number: 17854 Date : 10/8/2004 Valuation: $1,000.00 Permit Fee : $50.40 Plan Review Fee : $0.00 Use Tax : $12.00 Total: $62.40 Use: Description : WALL SIGN BUILDING DEPARTMENT USE ONLY SIC Approval : TRC Zoning : C-1 OK. BullO Comr ents w Approval #_„bttcWWorks:rCommentsy Approval: Occupancy: Walls MUST MEET 2002 NEC Roof Electrical License No : Company: Expiration Date Approval : Plumbing License No: Company : Expiration Date Approval: Sq. Ft. : Stories : Residential Units : Mechanical License No Company : Expiration Date Approval: (1) This permit was issued in accordance with the provisions set forth in yopur application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Code of Wheat Ridge, Colorado or any other applicable ordinances of the City. (2) This permit shall expire if (A) the work authorized is not commenced within sixty (60) days from issue date or (B) the building authorized is suspended or abandoned for a period of 120 days. (3) If this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. (4) No work of any manner shall be done that will change the natural flow of water causing a drainage problem. - (5) Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceeding with successive phases of the job. (6) The issuance of a r the ~p~Mrawimgs and specifications shall not be construed to be a permit for, nor an approval of, any violation of the provisions e g c /orrraany other or aneb, law, rule or regulation. Chief Building Inspector Please sign Terms and Conditions on reverse side of page. Certificate ofCompletitm And/Or Compliance City of Wheat Ridge 7500 W 2CJfh Avenue Wheat Ridge) Colorado 80033 THIS CERTIFICATE VERIFIES THAT THE PROPERTY DESCRIBED BELOW, DOES COMPLY WITH THE WHEAT RIDGE BUILDING CODE, ZONING AND OTHER RELATED LAND USE AND DEVELOPMENT LAWS OF THE CITY OF WHEAT RIDGE FOR THE FOLLOWING PURPOSE. PERMIT #17782 Tenant Finish Date: 1 0/7. ~/?n(}4 Owner: Dream Dinners Owner Address: 4QRn T<'ipling <;t #A-~~ "M,"l1t RidS", rn Rnm~ Property Address: Same Contractor: Custom Outdoor Creatwns Contractor Address: 1{}419 Christa Cir.. T,ittleton. CO 8012S ~ ~ Chief Building Official: Zoning Administrator: OCCUPANCY NOT PERMITTED UNTIL CERTIFICATE OF OCCUPANCY IS ISSUED PROTECT THIS CARD FROM THE WEATHER Final Electrical Plumbing Heating & Ventilation Frame R.O.w. & Drainage Fire Department Parking & Landscaping 10 - 2. i:- -0'- I iO - <-'>.--O'-! I I I () - ~ \;:-,-0'1 11(:) - '<.;.-~'\ i~.- ~C"-" , 10 - 12. ....Oq .. LJ.L\ Drywall Nailing 4 Roofing Refrigeration Electrical Underground Em~ Framing Insulation ~ ~ - I\. - 0 'i ~ Do NOT POUR FLOOR UNTIL ABOVE HAS BEEN SIGNED 10- 8~o \0 - ~~Lf' Rough Electrical Rough Plumbing Air Test Gas Piping Rough Heating & Ventilation Concrete Slab Floor: Electrical (Ground Work) Plumbing (Ground Work) (0 I. - O,-! lillA\ Heating (Ground Work) POUR No CONCRETE UNTIL ABOVE HAS BEEN SIGNED _.~.._-._--- - ~ INSPECTOR MUST SIGN ALL SPACES PERTAINING TO THIS JOB INSPECTION I DATE I INSPECTOR Foundations Footings Caissons Reinforcing or Monolithic Weatherproofing WEST EAST SOUTH SETBACKS FROM PROPERTY LINES NORTH JOBADDRESS-A9~ ~I'~St ~A--3 ~-~ BUILDING PERMIT NO. -J l'll{:Z;- _ DATE ISSUED 3} z..11~ I TYPE I OCCUPANCYl OWNER --.DJ.. 0 n........ ~ -t1 Nt 0 ~ A ) ~ CONTRACTOR_etA lt~ 6 ~Cll)Y"""" CJl 0 ~-1l"i:vs:. WHEAT RIDGE, COLORADO 7500 WEST 29th AVENUE (303) 234-5933 INSPECTION RECORD THIS CARD IS POSTED ON THE BUILDING SITE 24 HOURS NOTICE REQUIRED FOR INSPECTIONS mll ~ wnll~ ~lIl~l ~ Ill~~ COMMUNITY DEVELOPMENT DEPARTMENT BUILDING INSPECTION LINE. (303-234-5933) CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80033 - (303-235-2855) Building Permit Number: 17763 Date: 9/27/2004 Property Owner: DUNTON COMMERCIAL Property Address: 4980 KIPLING ST #A-3 Contractor License No.: 18377 Company: Ledges Electric Service Phone: 758-3131 Phone: 472-1197 OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Total: $4,000.00 $126.50 $0.00 $48.00 $174.50 I hereby certify that the setback distances proposed by ttlis permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application. and that I assume full responsibility for compliance with the Wheat Ridge Building Code (U.B.C.) and all other applicable eat Ridge ordinances, f.or work under this permit. (OWNER)(CONTRACTOR) SIGNE ~ DATE9-J2I"o'{ Construction Value: Permit Fee: Plan Review Fee: Use Tax: Use: Description: SERVICE CHANGE/UPGRADE COMMERCIAL. CHANGE EXISTING SERVo FROM 100A TO 100A 3CiRCUIT METER AND DISCONNECTS ARE EXISTING. SWAP FEEDS, HOUSE PANEL TO TENANT PANEL. CHANGE TENANT PANEL BUILDING DEPARTMENT USE ONLY "':':ni momm- _ ng. "'!.'!'Jl Approval: Zoning: .i:lin_inent1lll Approval: pdfc Wo~omri1~w Approval: SIC: Sq. Fl.: 9~~~t- l'WlO Occupancy: Walls: Roof: Stories: Residential Units: Electrical License No : 18377 Company: Ledges Electric Service Expiration Date: 2/28/2005 Approval: OKlKS Plumbing License No : Company: Mechanical License No : Company: Expiration Date: Approval: Expiration Date: Approval: (1) This permit was issued in accordance with the provisions set forth in yopur application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Code of Wheat Ridge, Colorado or any other applicable ordinances of the City. (2) This permit shall expire if (A) the work authorized is not commenced within sixty (60) days from issue date or (B) the building authorized is suspended or abandoned for a period of 120 days. (3) If this pennit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the original plans and specifications ~nd any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. (4) No work of any manner shall be done that will change the natural flow of water causing a drainage problem. (5) Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceediing with successive phases of the job. (6) The issuance of a permit or the a roval of drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation of the provisions of e-dildin pdt1Sor any 0 rdinance, law, rule or regulation. pec or Please sign Terms and Conditions on reverse side of page. COMMUNITY DEVELOPMENT DEPARTMENT BUILDING INSPECTION LINE - 303,234-5933 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80033 - (303-235-2855) APPLICATION Building Permit Number: Date: Property Owner: Ou-V\. +<9"" Cb W\.~ e...-<<-' "'- \ Property Address: 4 9 coo K;P I '~Y .51-. #' A. 3 Phone303'- 75-1I-:J i 3 ( CODeraclor License No.: '-t c) "7 1>" Company: 1--e..!..fJe-~ E/",-",f",c. :S".,......,'c.<- .I~c. Phone:303-'7~-1I9 7 OWNEIVCON'TRACTOR SIGNATURE Of UHOERST ANDING AND AGREEMENT Construction Value:$ 'i, 0=. ,? Permit Fee:$ Plan Review Fee:$ Use Tax'~ Total:$ I hereby cer1i1y thaI !he setback distances pr_sed by II"s penn. applicatJon are acc:ura1e. and dO not violate applicable ordinances. ru\es or regulations ot the City of Wheal R;dgeor covenants. eaoemenls or _of recclRl: that aIlmeasuremenls shown. and aDegnons made are accurate; that I have read and agree 10 abKie by aU concIition$ printed on thra app4icatton and that I anume full responsibility for compliance wtth 1he Wheat Ridge Building Code (U.8.C) and all other applicable Wheal Ridge Ordinances. for work undef this permit. ,00000000C()I<TAACTOR) $OGNED-c::JA~ 1lI. ~~ATE9- ;;I7-0'{ , {OWNERXCONTRACTOR):PR'NTEO S+e.",,,,"Vl. J..t. I<l/,'! so,",,- Descriptlon:~crv,cc. <--ho..-~Jr:I"-fJ"r~r: "-6-._....."'~c.("'-I-c...~e r::,(/'$I,"'1 S<-y,)','c-r:: 1'1"",....... /=0'" /qt5 fo /ooA 34', fVlc.ofer a.....d- O,t>c_~"ec.fs a..,-e- e"-'<'$fiY1.f- 5CAJa-p .fr:~d.". hC?~6'" f?oPf.," '" ( f<" +e",,,,-" r- p",-""e ( Sq. Fl. ._ /1 Ct.,.e......0"1.-7..e. 'Tc-n~'.+ '"'C:-C-Yl. e...- ( BUlLDI~G DEP ARTME~T USE O~L Y SIC: Sq.Ft. ~()NJNG COMMENTS: Approval: Zoning: BUILDING COMMENTS: Approval: 0. -. ~ WORKS co....ENTS: Approval : Occupancy: Walls: Roof: Stories : Residential Units: EJectricaI License No: /~ :3 7 7 Plumbing License No: Company: t..ed.:fe 5 ,c/<-C..f,..,'c.. Company. Expiration Date: Expiration Date: Approval: Approval: Mechanical License No: Company. Expiration Date: Approval: (1) Thill ponnil_ _ in _ _!he 1"6-0;..... lei ""'" in)'O\O"~ _ is aubjocl "'!he - 01 !he S1ale 01 Color*"> _ "'!he Zoning ReguI8tions _ ~C_ of _ Ridge, Cokndo or ony_ ~ ordinances 01 !he CiIy_ (2) This ponnil_.... ~ (A) !he -" _ Is not commenood MtNn sixty (60) days from issue dale or (8) !he oold;ng __ is __ '" _.Ied lor. period 0/ 120dloyo. (3) ,,_ ponnil aplNo.'... ponnil mey be~lor. 1M "'_!he _ romoIIy noquAcI, pro._ no__ __ "'.. be_ in ...oAgInoI....._ -X ..... __ ony _..... or ",*_.._4_ nol_ one (1)_. ,,__--"'~--- or__.....d_one(11_.IuI__ bepoid lor.... permit. (4) No_ 01 ony_ _ be done.. wiI chonge'" _ _ 0/ - COUIing. --~. (5) c......cIor _ noliIy!he Bo-.g ~ ~ (24) hours in _lor" inapecIions - - -...- ~ on ....,.,<600. conl_ p........lG _ -..i.1 phaa "'!he job. (6) The __ 01 . permit '" !he epproveI 01 <hwingI _ specilIc:HoI.. _ nol be construed '" be . permit lor. nor an approval of, any violation 01 the provi$ions of 1he bu~ng codeS or any other ordinance. law. rule or regulation. COMMUNITY DEVELOPMENT DEPARTMENT of '""EST s BUILDING INSPECTION LINE - 303-2345933 g CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80033 -4303-235-2855) APPLICATION Building Permit Number: Date: S0033 10kIj f ~dq~- Property Owner. pfe-A ko 01,qN of S Property Address: 1 `j A-3 Contractor License No.: C T orrpany:., cJ~~WS Phone: Phone: SO-3 - Z9 S = OWNERICONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurafe, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants. easements or restrictions of record: that as measurements shown, and allegations made are accurate: that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance with the Wheat Ridge Building Code (U.B.C) and all other applicable Wheat Ridge Ordinances, for work under this permit. ,MUUCOVrlwrou-rnm-cw~cn /6~r ~ nATf/// Description: ~~lQi /~u~T7 Sq. Ft. added /t Z~ iiLL Zoning: C_ . BUILDING DEPARTMENT USE ONLY COMMENTS: Approval i,cMMENTS: Approval: ro t t,S-l 57e",--j -gmba 11j:9Tc WORKS COMMENTS: Approval: Walls: Roof: Stories: Residential Units: Electrical License No: Plumbing License No: Mechanical License No: Company. Company. Company. Expiration Date: Expiration Date: Expiration Date: Approval: Approval: Approval: lt.) This permit was issued in accordance with On provisions set forth in your application and is subject to the laws of the Slate of Colorado and to the Zoning Regulations and Bullring Codes of Wheat Ridge. Colorado or any other applicable ordinances of the city. (2) This permit slug. expire if (A) the work authorized is not commenced within sixty (60) days from issue date or (B) the bunldvg autlrortted is suspended or abandoned for aleriod of 120 days. (3) if this; perrlf exples, a new permitmay be acquired fora tee of one-half tee amount normally isquili provided no doges havebeenorwBbe made in the original p>m and specifications and any anpension or abandonment has not exceeded one (1) yew. If changes have been or K suspension or abandonment exceeds one (1) yew, kill Ion shelf be paid for a new permit (s) No work of any manner shag be dorms that will change the natural lbw of water causing a drainage problem. (5) Contractor shall poly the Buildag Inspector twenty-bmx (24) hays in adve ce for as inspections and shall receive written approval on inspection cad before proceeding with successive phases of the job. (6) The issuance of a permit or the approval of drawings and specifications shag not be construed to be a permit for, nor an approval of, any violation of the provisions of the building codes or any other ordinance. law, rule or regulation. instruction Value:$ /060 = Permit Fee:$ Plan Review Fee:$ I ice Tax-$ Total:$ 09-24-04:03:SOPM:Berry Neon Sign Systems SEP-21-04 10:00 AM BEAU JO-S ACCOUNTING 3082380023 6NWM A UWMLMCRWWNMW0AG=ILM i I 1 fill I'm 1.3! L--._ ._._--------.--_.r. goo 4 2/ 2 P.01 Page 17 of 21 Landlord's initials: 711104 Teaan4a lnkws: .2 ems", ~ `ry= Q vii ~ uY m o E 0 N _ a m o S m ~ g~ S. N O r T° F T d 0 W N N Ii T 7 O 0 w E c r W LL 3 3 O a` v 3 _ E ~ r~ `Y o a z _ o _ a. e F W 8'. G F v F a ~ii G G S 8 0 G 0 3 3 d °e m, Q c ~ G 13 3 V 3 E', b 3 `m E'. O rz xw w mz O w -COMMUNITY DEVELOPMENT DEPARTMENT BUILDING INSPECTION LINE - (303-234-5933) CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80033 - (303-235-2855) Building Permit Number: 17782 Date: 9/27/2004 Property Owner: DREAM DINNERS Property Address: 4980 KIPLING ST A-3 Contractor License No. : 22106 Company: Custom Outdoor Creations Phone: 425-948-5277 Phone: 358-7977 OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Total: $10,000.00 $235.70 $153.21 $120.00 $508.91 I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree j y con' ions ri on this application, and that I assume full responsi .. y f m nc h t at Ridge Building Code (U.B.C.) and all other applicable at es, r this permit. (OWNER)(CONTRACTOR) SIGNE DATE 7-71-01' , I Construction Value: Permit Fee: Plan Review Fee: Use Tax: Use: Description: TENANT FINISH BUILDING DEPARTMENT USE ONLY ~"'::"..~'*'''.'''':1'f: Z:lml.ng qll..m.ments: Approval: Zoning: _in~erit. Approval: CR SIC: Sq. Ft.: OK. 9127/04. ~~omma~ Approval: Occupancy: Walls: Roof: Stories: Residential Units: Electrical License No : 18377 Company: Ledges Electric Service Expiration Date: 2/28/2005 Approval: ok/ks Plumbing License No : 221 09 Company: Bud's Mechanical Expiration Date: 9/29/2005 Approval: OK/KS Mechanical License No : Company: Expiration Date: Approval: (1) (2) (3) This permit was issued in accordance with the provisions set forth in yopur application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Code of Wheat Ridge, Colorado or any other applicable ordinances of the City. This permit shall expire if (A) the work authorized is not commenced within sixty (60) days from issue date or {Bl the building authorized is suspended or abandoned for a period of 120 days. If this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. No work of any manner shall be done that will change the natural flow of water causing a drainage problem. Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceediing with successive phases of the job. The issuance of a pe~ or the a pm"13tof "ngs and specifications shall not be construed to be a permit for, nor an approval of, any violation of the provisions of llJa-t:r'"'" g c or any other or e, law, rule or regulation. ./ (4) (5) (6) Chief Building Inspector Please sign Terms and Conditions on reverse side of page. '" ....,., . .., ~ " - co u ~ ("OLOf<",Q9 COMMUNITY DEVELOPMENT DEPARTMENT BUILDING INSPECTION LINE - 303-234-5933 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80033. (303-235-2855) APPLICATION :J:l:-)Ii'l';) Building Permit Number: Date: Property Owner: J>reA..M \) i I\V\ <<"".s; Property Address: 4'1 &:::> Gp l \ -::rr. A-3 Contractor License No.: 7.2/010 1") CompanyC ( '...o-.1-v (,J::x.J~ /:. ~ - J... . .... 1 ~Olll--", Phon<: ~35B-/Cj,-+ ~ Phone <f20-3'fS-Sdll OWNERlCONlRACTOR SIGNATURE Of UNOERST ANDING AND AGREEMENT I hereby certify tI"1at the setback distancei proposed by this permit appltcation are a<:curate. and do not violate applicable ordinances. 0JI0s or rogulabons of the Cdy of Wheat Ridge or covenants. easements or restnctions 01 reoonl: that all measuremonls shown, and aIIega90ns made are aCOJrate; Chat I have read and agree to abide by all concfttions printed on this application and that I assume full responsibility for compliance \Mill the Wheat Ridge Building Code (V.B.C) and aU other applicable Wheal RM:5ge Ordinances. for work under this permit. jOWNER)(CClH'I'RACTORj. SaGNEO DATE (OWNERXCONTRACTOR):PRINTED "\3c ~ \)C'>=> t.:\\\..)~ . '\-2-'5>- 3c.f8-'5?--" Descnptlon: T~ 'R,,^'~~ Sq. ft. .dded BmLDl~G DEP ARTME~T USE ON QNlNG CClMUENTS: Approval: Zoning: Construction Value:$1J Otl~. Pennit Fee:$ I Plan Review Fee:$ Use Tax:~ Total:$ lit ([:~i!.' i1"\7EIUf\ I ~ \ -------- - - _. - --- SIC: Sq.Ft. BUILDING COMMENTS: Approval: ar - ?-z 7~o-i tJ,~ WORKS COOlMENTS: Approval: upancy: Walls: Roof: Stories: Elec;tric;aI License No: 1~37\ Company: '..ft:Upv Expiration Date: Approval: Plumbing License No: Company: "Ex,.{Ls. (Y\c t'J, Expiration Date: Approval: Residential Units: Mechanical License No: Company: I\) I'fl EJ<piration Date: Approval: (1) Thio ponnil_ _ in accordanoo with !he 1lRI'......... for1Il in JOUr ~ ~ and is aullject to !he _ 01 !he SlaIo 01 Colorado and to !he Zoning RoguIa1ions and Builcing ~ 0I~ Ridge. Colorado Of any _ ~ __ 01 !he City. (2) Thio ponnilshal expire W (A) !he WOfk _ is not commenood _ si>dy (60) days from iauo date Of (8) Iho building __ is ____ Of __led..... poIiod 01120 d8yL (3) ,,-I*JIlIl....... MWI*JIlIl moy 1>0-"'"<1..... too 0I_!he _1QInOIy....-. prollided no__ __orwllbo_inlhe original pIonoand ~~andany__or_""".._A_nol_ono (1)_. "__--orll..__. Of_""".._A..-ono(I)_.IuI__bepa;clloranowpormit. (A) No _ 01 any _ _ be dono .... wiD chongo!he _ _ 01_ causing. __ probIom. (5) c.....ctor _ rdIy Ihe Builcing ~...-... ~ (2A) ""'" in __ .... .. inapocIions and ..... .-vo - __ on ~~\ card __ po~dillg with '" .... phMM 01 !he job. (6) Tho __ 01. ponnil Of Ihe __ 01 ~ and ..-.. _ not be conslJUod 10 be . ponnillor. nor an ---~'77---'~----'- SEP-23-04 THU 2:25 PM ARVADA FIRE PROTECTION D FAX NO. 3034327995 P. 2 '!~ - - . ~ . ..-- .. . Division of Fire Prevention i'~VAOA 11i6JW ~~~;:,,& ~~~'<J. ~<;> - Arvodo Fire Protection District Plan Review Comments Date: W21104 ReViewed By: Sparky Shriver Name of I'rujcct: Dream Dinners Address: 4980 Kipling Slreet Unit A-3 Occupancy Class: B Square Footage: 1,500 Sprinkler System: No Fire Alann System: No I) Exit sigll~ shown on the plans shall be subject to field inspection. Additional units may be required. UI'C 97 1212.3 2) Emergency lighting shall be subject to field inspection. Additional units may be required. UFC 971211.1. 3) Provide sufficient electrical receptacles as exlension cords and multiple adapters are not pennitted, nor shall flexible cords pass through walls, ceil ings or doorways. UFC 97 8506.3. 4) Carpeting if installed shall be a minimum ofa Class n Critical Radiant Flux and documentation shall be provided prior to installation. liFe 97 Appendix I V -A. S) An approved fire-suppression system shall be provided fOT the protection of ventilating hoods, ducts, cooking surfaces, deep fat fryers, griddles, upright broilers, char broilers, range tops and grills. Protection within the hood above tho fillers and exhaust ducts serving the hood. UFC 97 1006.2.3.1. 6) Fire extinguishers shall be a minimum of a 4-A rated, 10-lb ABC dry chemical unit. ConLacl the Fire Marshal's Office for the number of units and mounting locations. UFC 971002.1. Amended. 7) Any code requirements arising from constrUctioll will be addressed. 8) These conunenls shall remain with the approved plans at the construction site. 9) Contaot the Fire Marshal's Office at 303-425-0905 X 212 for questions or additional information. 10) T wanty-four hours notice is required for all inspections. UFe 97 103.2.2. 6503 Simms Street . Arvada. Colorado 80004-2607 . (303)424-3012 . Fax [303) 432.7995 _..._.._...._..".~ -~.,._.~ COMMUNITY DEVELOPMENT DEPARTMENT BUILDING INSPECTION LINE - (303-234-5933) CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80033 - (303-235-2855) Building Permit Number: 16249 Date: 9/22/2003 Property Owner: DUNTON REALTY Property Address: 4980-90 KIPLING ST Contractor License No. : 17911 Company: Alpine Roofing Co., Inc. Phone: 758-3131 Phone: 295-7769 OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application, and that I assume full responsibility for complianc ith the Wheat Ridge Building Code (U.B.C.) and all other applicable eat Ridge 0 a ,fa ork under this permit. (OWNER)(CONTRACTOR) SIGNED DATE 1- z Z - 0-; Total: $15,215.00 $344.90 $0.00 $182.58 $527.48 Construction Value: Permit Fee: Plan Review Fee: Use Tax: Use: Description: 83 SQUARES- TEAR OFF SHAKE SHINGLES, INSTAll 30# FELT AND 3D-YEAR DIMENSIONAL SHINGLES, INCLUDING MISC. SHEET METAL BUilDING DEPARTMENT USE ONLY i!IJlilng~llJiiients: Approval: Zoning: !llIIII!qing ~fs: Approval: lfubl~S:CQmniill.l~ Approval: Occupancy: Walls: SIC: Sq. Fi.: Roof: Stories: Residential Units: Electrical License No : Company: Plumbing License No : Company: Mechanical License No : Company: Expiration Date: Approval: Expiration Date: Approval: Expiration Date: Approval: (4) (5) (6) This permit was issued in accordance with the provisions set forth in yopur application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Code of Wheat Ridge, Colorado or any other applicable ordinances of the City. This permit shall expire if (A) the work authorized is not commenced within sixty (60) days from issue dale or (8) the building authorized is suspended or abandoned for a period of 120 days. If this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. No work of any manner shall be done that will change the natural flow of water causing a drainage problem. Contractor shall notify the Building Inspector twenty-four (24) hours (n advance for all inspections and shall receive written approval on inspection card before proceediing with successive phases of the job. The I ~~lt or the approval of drawmgs and speCifications shall not be construed to be a permit for, nor an approval of, any Violation of the on 0/ II ~ g codes or any other ordmance, law, rule or regulatIOn , (1) (2) (3) spector Please sign Terms and Conditions on reverse side of page. Build;ng Pennit Application City of Wheat Ridge Building Permit Application !Department of Planning and Development--.---.----.----- -.--- I!Building Inspection Line: 303.234.5933 City of Wheat Ridge 17500 West 29th Avenue Wheat Ridge, CO 80215 303.235.2855 Iproperty Owner: Dunton Realty -. - Property Address: 4980 - 4990 Kipli~Street Contractor License No: 17911 Company: Alpine Roofing Co., Inc. I Building Permit Number: Date: Phone: (303) 758-3131 Phone: (303) 295-7769 OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, ruies or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that ali measurements shown, and aliegations made are accurate; that I have read and agree to abide by ali conditions printed on this applications and that I assume fuli responsibility for compliance with the Wheat Ridge Building Code (U.B.C) and ali other applicable Wheat Ridge Ordinances, for work under this permit. ~ (OWNER)(CONTRACTOR) SIGNED:----J ~ DATE: 9/16703 Robert. lC y, esident IDescription: 83 squares-tear off existing shake shingles, install 3011 felt and 30 year dimension~l Slllll~.'-"b, "'~o~ 0"__" Construction Value: $15,215 00 Permit Fee: 344,90 Plan Review Fee: Use Tax: 182.58 Total: 527.48 Building Department Use Only Zoning Comments: SIC: Approval: Zoning: Sq.Ft.: Building Comments: Approval: Public Works Comments: Approval: I , I , IEiectrical License No: Icompany: I Expiration Date: iApprovai: /Plumbing License No: Icompany: , IExpiration Date: !APproval: Mechanical License No: Company: I Expiration Date: ,Approval: ! (1) This permit was issued in accordance with the provisions set forth in your application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Code of Wheat Ridge, Colorado or any other applicable ordinances of the City. (2) This permit shail expire if (A) the work authorized is not commenced within sixty (60) days from issue date or (B) the building authorized is suspended or abandoned lor a period of 120 days. file:/IIEllwwwrooVcitydev/building_permicapplication.htm (1 of 2) [7/2/200210:22:41 AM] Building Permit Application (3) If this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes have been made or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. (4) No work of any manner shall be done that will change the natural flow of water causing a drainage problem. (5) Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceeding with successive phases of the job. (6) The issuance of a permit or the approval of drawings and specifications shall not be construed to be a permit fee, nor an approval of, any violation of the provisions of the building codes or any other ordinance, law, rule or regulation. Chief Building Inspector file:/IIEl/wwwrooVcitydev/building_permiCapplication.htm (2 of 2) [7/212002 10:22:41 AM] COMMUNITY DEVELOPMENT DEPARTMENT BUILDING INSPECTION LINE - (303-234-5933) CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80033 - (303-235-2855) Building Permit Number: 15986 Date: 8/5/2003 Property Owner: ROSSI CATERING Property Address: 4980 KIPLING ST #11 Contractor License No. : 19797 Company: Rocky Mtn. Fire & Safety Inc. Phone: Phone: 321-0345 OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application, and that I assume full responsibility for compliance with the Wheat Ridge Building Code (U.B.C.) and all other applicable Whe Ridge ordin,!!!"es. for work under th~' (OWNER)(CONTRACTOR) SIGNED -:AU e DATE:J:: J.J Total: $270.00 $30.50 $0.00 $3.24 $33.74 Construction Value: Permit Fee: Plan Review Fee: Use Tax: Use: Description: RELOCATE DROPS ON HOOD FIRE SUPPRESSION SYSTEM. FOR NEW APPLIANCES I """" " . :~<{I:l{ 2-- - BUILDING DEPARTMENT USE ONLY '_jy---_""'/r= SIC Sq. Ft. Z;Qnlrigi~ommen*!Ii,_ Approval Zoning B "ldlllg:.B6:r * . ..IIL_ ". "...' JI!1l!l" Approval Publi",.~mm~n*s: Approval Occupancy Walls Roof Stories Residential Units Electrical License No : Company: Plumbing License No : Company: Mechanical License No : Company: Expiration Date: Approval: Expiration Date: Approval: Expiration Date: Approval: (1) This permit was issued in accordance with the provisions set forth in yopur application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Code of Wheat Ridge, Colorado or any other applicable ordinances of the City. (2) This permit sldl expire if (A) the work authorized is not commenced within sixty (60) days from issue date or (B) the building authorized is suspended or abandoned for a period of 120 days. (3) If this permit 1_\iJires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the original plans .i,ld specifications and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. (4) No work of any manner shall be done that will change the natural flow of water causing a drainage problem. (5) Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before procee' with succes ive phases of the job. (6) T . or the approval of drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation of the pro, E- othe' oed,nance. law. rule 0' '"9ulabon Chief BUilding nspector Please sign Terms and Conditions on reverse side of page. DEPARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number: BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE Date: 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 ,(055 I C'q IttC","!j ifc;8o k'.t1/'"j ~ / ( Phone: Property Owner: Property Address: Contractor License No. : Company: let. OWNER/CONTRACTOR SIGNATURE OF 1: NDERSTANDING AND AGREEMEN Phone :303 - .3,;2/ - 03r'S Construction Value: 27 o' "" Permit Fee: Use Tax: I hereby certify that the setback distances proposed by this pennn applica.tion are accurate. and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown. and allegations made are accurate; that I have read and a9ree to abide by all conditions printed on this application, and that I assume full responslbir for compliance with the Wheat Ridge Building Code (U.B.C.) and all other applicable Wh at . ge 0 In nee or ark under this permit. (OWNER)(CONTRACTOR)SIGN~ DATE8 '1-(J~ Total: $0.00. Use: Description: /P!Ocq k dt'015 SW,('e.s:&'/~., -5'/..5tm. o f1 ;Iood /- rite /':';;R "1"<<.) .~jJI,ant:c$ BUILDING DEPARTMENT USE ONLY f!RllJmlQO'.mmll.nU!J Approval : Zoning: ~~,!p~!:!mme.n.~ Approval: cmn~.9~!l-'lJl!!!!n!Sl Approval: Occupancy: Walls: SIC: Sq. Fl: Roof: Stories: Residential Units: Electrical License No : Company: Plumbing License No : Company: Mechanical License No : Company: Expiration Date: Approval: Expiration Date: Approval: Expiration Date: Approval : 14) 5) (6) This permit was Issued In aCCOC'danee with the provfsions set forth in yopur application and Is subied to the laws of the State 01 Colorado and to the Zoning Regulations and Buildin9. Code of\fllheat Rid~e, Colorado or any other applk:able ordinances of the City. This permit shan expire if (A) the wock authoriZed Is not c::onvnenced within sixty (60) days from lssue dale or (8) the building authorized is suspended or abandoned for a period of '20 days. . If this permit expires. a new permit may be acquired for a fee of one-half the amount normally required. provided no changes have been or w;1( be made in the original plans and specifications and any suspension or abandonment has not exceedec:l one (1) year. If changes are made or tf suspenaion or abandonment exceeds one (1) year, full fees shall be paid for a new permit No woOl; of any maMer shall be done that will change the natural flaw of water causing a drainage problem. ContradOf' shaD notify the Building InspedOf twenty-fot,Ir (24) houB In advance fOl' .11 inspections and shall receive Minen approval on Inspection card before _U"ll with successive phases of the Job. lhe issuance of a pennit or the approval of draw(ngs and SpecifICations shan not be construed to be a permit for. nor an approval of. Iny vtoCation of the provisions of the building codes or any other ordinance, law. rule or regulation. . (1) (2) (3) Chief Building Inspector For Mayor THIS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION ~=rg:aUJ"'O c:..$a:CtlCC- :;_ n; 0<0..2': ~ ~ g. :2' =- ~ <n . 0 (ii-:::i:: Q) 5 ~ c)".{g 0 (i (I) ~ ::J CD ::u "2::)og.9~ n a. - 0' ~ '0 ____ _ "T1::1<.C.... 5,:t) _. In ::r 0 ::J!e.CDD.lQ)(i ~Vl"'O::J5.c.. ::I Nro c...."m Q. J::o, < D) -. en ::;t::r{t)g~(IJ en 0::1 Cl)-c _ c: =-0 5" 0- cnUlgm",3 Q) "0 ::1: i!.a~~m- 8< -- I>> W CD (5":e :::3g8<n::l;::o; ~(tlJ,..(i)~:::r Sl::l "-J Q) z:e ~g6io~ s::g~8~~ ge._013~Q) g. 5" rn ~ ar 5- ,<{g~CD6"Q) ........ CD a. - ~o r-v. c:r5i oeo...... (1)0 c:ON""Cn:::r (Q ::I - - 0 CD :::r<n_m:::lo.. -iOo",n~ ::::r....UJco:D3 [~~g~~ ll> C c: -< _. ~!iT" . fII tU n.$!Z o ll> 1D 2l~~ '^'!.9l. Q:!Q)~ 3 :!!~ ~~ ~ 9~ co '" ~Q. ---. 0" <::=> <0 ll> _. 0. <n Q) s: - '"' ,,-- 00 (Xl ~: 0", ocr 0" f"o '" - 0>." 0_. "<il " <il ili " '"' o " fiiSl ~ 1..LX4"WXZ'H HOOD: I.EMOTE PULL STATION OYEN IIlEVISED: 7/31120031 PYIlO CHI!M 3." GALLON ~ CHI!MICAI. IYSYI!M - 13 flOW POINTIIIIIX '1.1. JJr' lUCK 10H.DULI 41 1.0lS1 CATEIlING COVl!IlAlII! NOZZLI! flOW POINTS NOZZLE PLACI!MI!NT 4... KlPLlNlI 111 11Z"' .IIIT C..DUIT-oO.... 'ULLIY IADH _UTIlIDGI!, CO. 0....... a. DIUOTIOII DUCT NLDZ 2 DUCT INTI!....CI! PLI!NUM Z. NLA 2 I!VEI.Y I IT UMOTa PULL STATIOII LOCATIO .11 Till INSTALLAnON DAorB JlANGI! NLUl21 NU 1 3 3Z"'-4r11r-3r 'ATH .. IXIT lIllIDDLI! NU2 2 1r-4r ".VALVI TO SHUT DO" lIAS SU.'LY JlANlIl! Z. NLUl2 4 3Z"'.4r UPOII ACTIVATION INSTAL LEI. ( S ): II10a. IWlTOII SU"LIID TO DDIITROL ALL ~ CS:~ ILlIITRlOAL 'UNGTIOIIS TOTAL now POINTS . IXtlAun PAil Mun STAY 011 DR COMI ON I' 0" . IlAKI U. AIR MUST IHUT DO'" . ALL ILlOTRlDAL A'.LIAIIC.S AIID IlOCKY MOUNTAIN F111E & THIS SYSTEM WILL BE INSTALLED IN ACCOIIDANCE WITH NFPA 17'" OUTLns UIID.. TMI MDOD MUST SHUT safETY, INe. UL 300 STANDAIIDS, AND ALL MANUFACTUIIE SPECIFICATIONS DD" 3745 E. HTII AVE ~ INTI.CO..ln PlIlI ALAD 'AIIIL IP DENYE" CO. 1021. DISTill. =--z21-0345 511120.1 -. _ ~_.l._ _.1.:__ -.._&...- :..........._11,,- """ JlANGI! 3rX :M"' Fire p y: responsible for the system meeting UL/FM and manufacturers requirements and rlilcommtndlttlMI, DEPARTMENT OF PLANNING AND DEVELOPMENT BUILDING INSPECTION LINE - 303-234-5933 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 - (303-235-2855) Building Permit Number: Date: 13338 1/14/02 Property Owner: Property Address: 4980 KIPLING ST UNIT 4 Contractor License No.: 21182 Company: ROYAL SIGNS OF COLORADO Phone: 972-238-0771 Phone: 303-795-6551 OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Construction Value: Permit Fee Plan Review Fee Use Tax: $1,01300 ~41 sn SO 00 $15.20 I hereby certify that the setback distances proposed by this permit application are accurate and do not violate applicable ordinances, rules or regulations of the City of Wheal Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate: that I have read and agree to abide by all conditions printed on this application, and that I assume full responsibility for compliance with the Wheat Ridge Building Code (U.B.C.) and all other applicable Wheat Ri e or . an s, for work under this permit (OWNER)(CONTRACTOR) SIGNED Total. $56.99 DATE Use: Description: INTERIOR LIGHTED CABINET SIGN TO BE ATTACHED TO BUILDING FAS BUILDING DEPARTMENT USE ONLY IIIIIIIIIIIIilI Approval: MLC Zoning: C-1 SIC. Sq. Ft COMPLIES WI SIGN CODE ....... Approval: BG MUST BE U.L. LISTED & MEET N.E.C. REQ. Approval: Occupancy: Walls: Rool: Stones. Residential Units Electrical License No : Company: Plumbing License No : Company: Mechanical license No . Company' Expiration Date: Approval: Expiration Date: Approval: Expiration Date: Approval: (4) (5) (6) This permit was issued in accordance with the provisions set forth in yopur application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Code of Wheat Ridge, Colorado or any other applicable ordinances of the City This permit shall expire if (A) the work authorized is not commenced within sixty (60) days from issue date or (B) the building authorized is suspended or abandoned for a period of 120 days. If this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year If changes are made or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit No work of any manner shall be done that will change the natural flow of water causing a drainage problem Contractor shall notify the Building Inspector twenty.four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceediing with successive phases of the job. T!)eo f~Smance of a ermit or the approval of drawings and spec ifications shall not be construed to be a permit for, nor an approval of, any violation of the provi"ion ilding codes or any other ordinance, law, rule or regulation. , )~. ~ Chief Buil~ Inspector (1) (2) (3) ~O, 'IIH"r 1', ~ 0 - " U ~ C'O( OR~\P DEPARTMENT OF PLANNING AND DEVELOPMENT BUILDING INSPECTION LINE - 303-234-5933 .CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 - (303-235-2855) A.PPLlCATlON Building Permit Number: Date: Property Owner: Property Address: Contractor License No.: Company: 4-"1 B 0 ~ 1 P 1--1 rJ~ OS,. i U /J I -r +- ;}. II 8;). 4'<-OYAl- ;51 (,,/Js 0 F CoL612.ADo OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Phone: 172 -.23 e -OT7 J Phone: Jo3.-7'if)-~55/ /0/3 Construction Value:$ Permit Fee:$ Plan Review Fee:$ Use Tax:$ Total:$ I hereby certify that the setback distances proposed by this pennit application are accurate, and do not violate applicable ordinances, rules or reguLations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance with the Wheat Ridge Building Code (U.B.C) and all other applicable Wheat Ridge Ordinances, for work under :::;~NTI<AcrOR)S[GNED .~~C1:TE 1/$/0 Description: :4;#-10< 1-j'I-W CC{b,,~.t- ~t-l .-/-0 ~ awcW .~ bl..ddlNJ ' scto.. ZONING COMMENTS: Approval: Zoning: BUILDING DEPARTMENT USE ONLY ~\\\~~S uJ/~l'1'(\ C'roc M..~ Q.-\ BUILDING COMMENTS: Approval: IS C;. J I (/ L /i 5/ J 4- ..",_j rl1 u 51 1Oe. '. e.{ iVE.C ,.e q . PUBLIC WORKS COMMENTS; Approval: Occupancy: Wails: Roof: Stories: Electrical License No: Company: Plumbing License No: Company: Expiration Date: Approval: Expiration Date: Approval: Expiration Date: Approval: \~,~~ ~ :\'~ SIC: \~ '\\ "\",.. "", '\~'- , .~;~'''. Residential Units: Mechanical License No: Company: (1) This permit was issued in accordance with the provisions set forth in your application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Codes of Wheat Ridge, Colorado or any other applicable ordinances of the City. (2) This permit shall expire if (A) the work authorized is not commenced witb.in sixty (60) days from issue date or (B) the building authorized is suspended or abandoned for a period of 120 days. (3) If this permit expires, a new permit may be acquired for a fee of one~half the amount norinally required, provided no changes have been or will be made in the originalpla.ns and specifications and any suspension or abandonment has not exceeded one (1) year. If changes have been or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. (4) No work of any manner shall be done that will change the natural flow of water causing a drainage problem. (5) Contractor shall notify the Building Inspectortwenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceeding with successive phases of the job. (6) The issuance of a permit or the approval of drav.rings and specmcations shall not be construed to be a permit for, nor an approval of, any violation of the provisions of the building codes or any other ordinance, law, rule or regulation. ~L . . ChiefBu~pector j;l n :!: ,!, ~ ~ 0.' 1::J 1"' ~ ~ ~ = - " = ~ ~ 1I ~ ~ a' .~'i U =~ 08 li q " :;" '"' o ... '" " -Q.3 SCreerpmled v111'11 graphic .V.l P,emlum whlte vinyl copy r:zo- C ( C\ \.5lc I\l [II - 1~"'Jkpmortlll"... I ""..-, I 16" - 9'.6" t- f:. 8'.8" 9'-2" ~ . ll; " 0' ~ ~ .. . . , . ~---\ , CD N lNSTALL EDWARD JONES WALL SIGN IWI.31 . Internally illurrrimted wall cabinet -OveTaJI siZ(" of wall slgn 16- x 8'.] If -Cabinet is pamted to match PMS 5535 r,rcen -Face 18 .7328 white le>ian wjth Edwald Jon.:s specific green vmy! (Kapco .9535 EVeJgrrnl) -Copy is reversed ou1 to show-thru whj1e acrylic. Border and rule 111lf's are.a translucc=nl Edward Jones SpfClfK green vinyl to match PMS 37J -Install as noted onto 8v81lable &ign band Qrea -Jnstaller to provide mounting hardware D jll 1o"':.;.:E;- v'('Jyl 3~ b b- " ~ w . , " " I. ~'I~ ~ II _ 0 ~ r ~ ~ "' u ;:; ~! . Ie 8/-1 (I L-J~~ C~(^'~+- ~()r iD { DII\'G l(;AC~1jAl 8LJ ','~lr: 'r;('IPQ[} ~Ul *DRAWil\'G 151','011'": '5C1- ~~ ~ g ,::: l~ ~ - ~ , , i ~I ~ ..:.. .- ,,- =~ !~ II i ~ ~ ::. ~ ~ ~ ~ " > w , , o 'J a ~ 7 o .. ,. o , L. ~ o r > . o . ~ ~ ... 1; => ~ ~ " c t. '" ~I . o o . ~ ~ i ~i ". .., .., . . INDEPENDENCE SQUARE 1f~ ~WlM 1R<~~1fM~!NJtr @~ IN] ~~ [FT~ ~Mmw @~@IMI~IR? ~\J- U ,'IV,! f m u L ~_~e;vfMJT Sf 6N .- _~L&4: '\fJ 1 t( ~~ ~~a)\lf- I u, I I EdwardJones I 3'7 inl ~ SIGN ELEVA1lON MUt 1HE NANl INSTAll RIA V~Yl FOR DI5 W11- llNI\NI MONUMEM VISlb6e openng 15" lC:W . Bcx:kgrDU1d10 be exGIhgvk1de -CClP'/10 be EJ DI< (;I""" IKapcO #'103; Evergreenl .E"Iloct 10:::'01100 on 51gn to be de1etTl"l1l1El 'DRAWlI'GS 1'I{)1 '0 5C'~lE 9UIISD[JOPO~1Ia.;\H 10 ACiJ\l i9J1Lm>J< DEPARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number: 8382 BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE Date: 1/12/99 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 Property Owner: Property Address: 4980 KIPLING ST #15B Contractor License No.: 17232 Company: Colorado & Santa Fe Construction Co. OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Phone: 466-2500 Phone: 466-2500 1 hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that 1 have read and agree to abide by all conditions printed on this application, and that I assume full responsibility for compliance with the Wheat Ridge Building Code (U.B.C.) and all other applicable Wheat Ri ordinances, for work under this permit. (OWNER)(CONTRACTOR) SIGNE DATE //;:3..h'7 Total: $9,250.00 $167.25 $108.72 $138.75 $414.72 Construction Value: Permit Fee: Plan Review Fee: Use Tax: Use: Description: Tenant remodel, build interior offices BUILDING DEPARTMENT USE ONLY SIC: Sq. Ft.: Approval: Zoning: ...... Approval: OM Okay, need subcontractors license #'s if not Colo. Santa Fe Const. Approval: Occupancy: Walls: Roof: Stories: Residential Units: Eiectrical License No : Company: Plumbing License No : Company: Mechanical License No : Company: Expiration Date: Approval: Expiration Date: Approval: Expiration Date: Approval: (4) (5) (6) This permit was issued in accordance with the proVisions set forth in yopur application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Code of Wheat Ridge, Colorado or any other applicable ordinances of the City. This permit shall expire if (A) the work authorized is not commenced within sixty (60) days from issue date or (B) the building authorized is suspended or abandoned for a period of 120 days. If this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. No work of any manner shall be done that will change the natural flow of water causing a drainage problem. Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceediing with successive phases of the job. The issuance of a permit or the approval of drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation of the provisions of ':/!.ing or any other ordinance, law. rule or regulation. Chief Building nspector THIS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION (1) (2) (3) DEPARTMENT OF PLANNING AND DEVi:LOPMENT Building Permit Number: , BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE Date: 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 Property Owner: Co \ Oof ...~o ~ >0.""<>"';:" Property Address: 4<18'0 \'-<'f' \ ",^~ Contractor License No, : I 7 2. ~ -z...- Company: Co\O<f'C>-~'" € Se...~...,,-y <" (o~ S"'<J"C<;"","- (0 Phone: 'f'b- Z-!:O 0 \o-v.cl Co #rs b Phone: '!bb - 2>6 i?J OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this pennit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants. easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and aQree to abide by all conditions printed on this application, and that I assume full responsl~ility (or compliance wit th Wheat Ridge Building Code (V. B.C.) and all other applicable Whe Ri ordmances r rk under this permit. (OWNER)(CONTRACTOR) SIGNED DATE 1;1/ /9J Construction Value' '12..- SO. oc> / Permit Fee: Pl4n <..heck P~e--"1> Use Tax: Total: $0,00 Use: Description: 0) ("\f' G ( , - 17u ,'I C l .....k<<J,'c." oo-~, ,(.....5 (}f2.t f3 OL&'(OYlC- ~lWFommll~J$j Approval : Zoning: ~RiI!J~~mmeJl.~ Approval : ~~!!Sf<SU;>J:l.I1JJ)J!ln~ Approval: Occupancy: Walls: ^'\IL-EleCtrical License No : ~ Company: Roof: Stories: f. "\ ~~?\ ,1,1'- '-., ,_ \ ,,\ '\ L- f ': ~ f' . ~ , :-',') ... ......- i__,' ~.~ <. iJ .... J4,'j ~;..t..: , 1 BUILDING DEPARTMENT USE ONLY lumbing License No : Company: Mechanical License No : Company: Expiration Date: Approval : Expiration Date: Approval: Expiration Date : Approval : (4) (5) This permit was Issued in ac:cordance with the provisions set (orth in yopur application and Is subied to the Laws o( the State of Colorado and to the Zoning Regulations and Build~ Code of Yv'heat FUdge, Colorado 0( any other, applicable OI'dil'lances of the City. This pennit Shall expire If (A) the work authonzed is not commenced within sixty (60) days from Issue date oc (9) the building authorized is suspended or abandoned for a period of 120 days. . It this permit expires, a new permit may be acquired for a fee of one-half the amount nonnaily required. provided no changes have been or will be made in the original plans and spec:ific3tions and any suspension or abandonment has not exceedeO one (1) year. If changes are made or if suspension or abandonment exceeds one (1) year, full fees shall be paid (or a new permit. No work of any manner shall be done Ulat will change the natural ftow of water causing a drainage problem. Contractor shall notify the Building Inspector twenty.four (24) hours In advance for all inspections and shall receive written approval on inspection card before. proceediing with suc:cesslve !)haleS ot the Job. The issuance of a pennit or the approval of drawings and specifications shall not be construed to be a permit for. nor an approval of. any vtofation of the provisions 01 the build" codes or any other ordinance, law. rule or regulation. (1) (2) (3) " '(6) ~ nspector For Mayor THIS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MA VOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION ,," ,,'" ."," ,,"" IfII"" \ I , J N REFL.EC TED CE IL.l NG PL.AN sc,ALE 14ft = f'-Oll R rei ., . :2 . PL.ANTeR RELOGATE FIXTURES AS NEc,ESSA~Y* NE~ UPPER 4 LOYE~ GABINETS ~/ SINK 4 cSARBAeE DISPOSAL N (f) SI1"f: P'L.AN N OFFICE C> I I ~ I I I U : STORAGE .. A I I I t I f I I I I I I I I 21,Ql5 SF T A I ATI N c,OMPUTER BUI INSTAL-L 6 NEVi RECEPTAC,LES. (SUi TES e> 4 q) UNIT -IS6 1,655 5P 4~S'F f ,225 5r ',65' SF CONSTRUe TION rrPE IteT ALL 51eN THIS DOOR TO REMAI UNLOCKED DURIN6 BUSINESS HOtRS. ICE II N FL.OOR PL.AN UNIT 158 ALE 1/4U:: '_0 PANEL SCHEDULE.. lOOA I -G-Ib c,IRc,Ufr LOAD GENTER MAIN 2P - 60 HYA,C, :2P 30 T LE5 THROOM ARE LITES LITES RaEe T ACLt:S SF E - NE~ REC,EF'T ACLE5 SPAC,E - KITCHEN CCVNTERIDISPOSAL BREAK ~OOM LEVER HANDLES ON ALL DOOR.5 ELEC PANEL ,~;, y6tRV1 r::; V, ~;/'>o )jJ/I(/5 . 10.,( ~19 Jef''or g, If tjp p.t tJ-- 6 OFFI COPY ROOM INSTALL 5TOREROO FUNC TION L.EVER HA 4- o 4 ~ONG. STEPS HE I cSHT HALL PROPOSED USE: fDL~ APPROVED Subject to Field Inspections Wheat Ridge Building Dept. /-/2- yeT' Date.......____.. Signed ~ Plan Ch k (, " _.._...' ec ., . ~/ GRID HEleHT I Ne ~ALL HEleHT NEY't ~ALL-S 4 EXISTI HALLS ARE BE EXTENDED CEILING (SRI . ELECTRICAL LEGEND: PARTITION L.E END CEILING LEGEND. . .2 .. e- O: -= ~ O:ca . TeL.EPHONe 0IJT1.Er eXISTI P'ART'''ON TO AlH @] eXI5TlNe PARTITIONS AND liJ I! " 1 zr <"" .r t# I I J:JI " ...... PARTITION TO . . 24. Ot;.. K' '/6ft ~ IX' TO 01 U* J -AI.. TO_ ", \D . o o AIR ~ (. Tee HeleHT A.,..,.) TURN BUILDING DEPARTMENT (303) 235-2855 CITY OF WHEAT RIDGE * * Correction Notice Job Located at ;j 9?O J4 J/' / j) i I have this day inspected this structure and these premises and have found the following violations of City and/or State laws gov- erning same: I.) j/j,p "vlb> <5z; p -'.1-c:..JI / I;' -4 I. Gi.<:,' t- ""/Y>< r:N~ Pf=}e..,s You are hereby notified to correct the foregoing violations. When corrections have been made, call for inspection. DO NOT REMOVE Inspector lor Bu ding Dept. Date FORM WR6-22 'DEPARTMENT OF PLANNING AND DEVELOPMENT BUILDING INSPECTION LINE - 303-234-5933 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 - (303-235-2855) Building Permit Number: Date: 13233 12/11/01 Property Owner: Edward Jones Property Address: 4980 Kipling St Contractor License No. : 20858 Company: KPS Electric Inc. Phone: 800-824-6525 Phone: 720-524-0280 Construction Value. Permit Fee: Plan Review Fee' Use Tax' OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all easurements shown, and allegations made are accurate; that I have read and agree to abid y all conditions printed on this application, and that I assume full responsibility or c pliance with the Wheat Ridge Building Code (U.B.C.) and all other applicabl at 9 0 inances, for work under this permit. (OWNER)(CONTRACTOR) SIGNED DATEJ)../JJ)JJJ Total: $3,500.00 $97.25 $000 $52 50 $149.75 Use: Description: Adding outl ts & moving light fixtures in ceiling BUILDING DEPARTMENT USE ONLY IIIIIIIIIIIIIIB Approval: Zoning: SIC: Sq. Ft. : ---- Approval: ....-.... Approval: Occupancy: Walls: Roof: Stories: Residential Units: Electrical License No : Company: Plumbing License No : Company: Mechanical License No : Company: Expiration Date: Approval: Expiration Date: Approval: Expiration Date: Approval: (1) This permit was issued in accordance with the provisions set forth in yopur application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Code of \^/heat Ridge, Colorado or any other applicable ordinances of the City. (2) This permit shall expire if (A) the work authorized is not commenced within sixty (60) days from issue date or (B) the building authorized is suspended or abandoned for a period of 120 days. (3) l1this permit expires, a new permit may be acquired fOf a fee of one-half the amount normally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year, If changes are made or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. (4) No work of any manner shall be done that will change the natural flow of water causing a drainage problem. (5) Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceediing with successive phases of the job. (6) The issuance of a permit or the approval of drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation of the provisions of the building codes or any other ordinance, law, rule or regulation. Chief Building Inspector ,.~' WHEAr l' /.....: -0 - " " ~ COLOR ",QO DEPARTMENT OF PLANNING AND DEVELOPMENT BUILDING INSPECTION LINE - 303-234-5933 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 - (303-235-2855) A.PPLlCATION Building Permit Number: Date: Property Owner: f dWftJ J 0 >'<5 Properly Address: "f 'I po }C, 'f' if"? sr if VlI f 'I Contractor License No.: '17/3 Company: kP.( F-{pc i-Y'L J:r1C Phone: I on. ~ )- I bO S Phone: 7)0- "if '1- '()) fl OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by, this permit application are . accurate, and do not violate applicable ordinances, rules or regulations oithe City of Wheat Ridge or covenants, easements or restrictions of record; that aU measurements shown, and allegations made are accurate; that I have read and agree to' abide by all conditions printed on this application and that I assume full responsibility for compliance with the Wheat Ridge Building Code (U.B.C) and all other applicable Wheat Ridge Ordinances, for work u~~er this pn!h (OWNER)(CONTRACTOR): SIGNED . i Ii, 0 J f///1 DAlE / ,j J ~ J (j I r I -- ./.dI.4f!J Description: akhY10 ;6utLdS Ovr\/ f1/1 d/ill? Construction Value: Permit Fee: Plan Review Fee: Use Tax: Total: 3s1JO Q 1, Z.S /,?!rf /, 'rfy V<.f I y1 eel), J/lCj BUILDING DEPARTMENT USE ONLY SIC: Sq.Ft.: ZONING COMMENTS: Approval: Zoning: BUILDING COMMENTS: Approval: PUBLIC WORKS COMMENTS: Approval: Occupancy: Walls: Roof: Stories: Residential Units: Electrical License No: Company: Plumbing License No: Company: Mechanical License No: Company: Expiration Date: . Approval: Expiration Date: Approval: Expiration Date: Approval: (1) This permit was issued in accordance with the provisions set forth in your application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Codes of Wheat Ridge, Colorado or any other applicable ordinances of the City. (2) This permit shall expire if (A) the work authorized is not co=enced within sixty (60) days from issue date or (B) the building authorized is suspended or abandoned for a period of 120 days. (3) Ifiliis permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes have been or ifsuspension or abandonment exceeds one (1) year, full fees shall be paid for a new pennit. (4) No work of any )!lamer shall be done that will change the natural flow of water causing a drainage problem. (5) Contractor shall notify the Building Inspectortwenty.four(24) hours in advance for all inspections and shall receive written approval on inspection card before proceeding with successive phases of the job. (6) The issuance of a penn.it or the approval of drawings and specifications shall not be construed to be a pennit for. nor an approval of. any violation of the provisions of the building codes or any other ordinance, law, rule or regulation. Chief Building Inspector DEPARTMENT OF PLANNING AND DEVELOPMENT BUILDING INSPECTION LINE - 303-234-5933 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 - (303-235-2855) Building Permit Number: Date: 12991 10/23/01 Property Owner: Property Address: 4980 KIPLING ST UNIT 5 Contractor License No.: 19362 Company: Action Signs Phone: 420-6412 Phone: 431 1182 Construction Value: Permit Fee: Plan Review Fee: Use Tax: OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all con itions printed on this application, and that I assume full responsibility for compliance w. h the Wheat Ridge Building Code (U.B.C.) and all other applicable haa idge'lftinances or work under this permit. (OWNER)(CONTRACTOR) SIGNED A", DATd() -z.L(-tJ f Total: $715.00 $32.65 $0.00 $10.73 $43.37 Use: Description: MOVE CHANNEL LETTERS FROM LAKEWOOD LOCATION TO NEW STORE LOCATION. 11 LETERS - COPY; SPORTS CARDS - 18" LETTERS, OVERALL LENGTH 10'6" - 19 SO FT. (ELECTRICAL TO SIGNAGE IS NOT INCLUDE) BUILDING DEPARTMENT USE ONLY - Approval: MLC Zoning: C-1 SIC: Sq. Ft. ___1111' 11lf~!I~!lf:m_.j,. 10/18/01 COMPLIES WI SIGN CODE Approval: SG Approval: Occupancy: Walls: Roof: Stories: Residential Units: Electrical License No : Company: Plumbing License No : Company: Mechanical License No : Company: Expiration Date: Approval: Expiration Date: Approval: Expiration Date: Approval: (1) This permit was issued in accordance with the provisions set forth in yopur application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Code of Wheat Ridge, Colorado or any other applicable ordinances of the City (2) This permit shall expire if (A) the work authorized is not commenced within sixty (60) days from issue date or (8) the building authorized is suspended or abandoned for a period of 120 days. (3) If this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. (4) No work of any manner shall be done that will change the natural flow of water causing a drainage problem. (5) Contractor shall notify the BUilding Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceediing with successive phases of the job. (6) The issuance of a permit or the approval of drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation of the pr ISI ns 0 the Iding codes or any other ordinance, law, rule or regulation. Inspector DEPARTMENT OF PLANNING AND DEVELOPMENT BUILDING INSPECTION LINE - 303-234-5933 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 - (303-235-2855) APPLICATION Building Permit Number: Date: Sf']J1 5 J OWNERlCONTRAcrOR SIGNATURE OF UNDERSTANDING AND AGREEMENT "\"h<^scn J{'1 G-cJ 1<, tJ I';J r.J '" f 1'i:3 b:z... It r +-, h>. ;;- Phone:)-3 4.2.0 -6,//L Phone: >'7 13/-1/'it 2. Property Owner: Property Address: Contractor License No.: Company: S h<""" f ,'" Construction Value: 71 . Permit Fee: Plan Review Fee: Use Tax: Total: I hereby certify that the setback distances proposed by this permit application are-. accurate, and do not violate applicable ordinances, roles or regmations of the City of Wheat Ridge or covenants, easements or restrictioDS of record; that all measurements shown, and allegatioDS made ar;e accurate; that I have read. and .agree to abide by all conditions printed on this application and - that I assume full responsibility. for compliance with the Wheat Ridge Building Code (U.B.C) and all other applicable Wheat Ridge Ordinances, for work under this permit (OWNER)(CONTRAcroR), srGNED 'C - I q DATE:LOO / + D .. fY/p,<;;: CJ..",-",'",.( I~J/"", +..---., La.k~w'r) /UXA.fr"" 0 escnption: /' ITt c/ "'''t5 J1 A "'Ie qr 1-/98'6 1(, /,'" J OJ,,;- - II leif~r5 - utv : <; AJr<. ),C/r';lP - /~.;t.. ./~I,.,,_ t;'l'JSJJf,",~/,.f<trl<J /or- ,),I.uJ,,; ,"/,^eJ"''/t? Cude.. (,1 ~&, "- ,j /Ad- 1V'<f,,)('~l . . BUILDING DEPARTMENT USE ONLY Illil'l\~ W/Stgn (loiQ . ".. L<l 5iiJ/'Q. kx.."f; <'>( if" /4/6'r5 o,"con,11 - e le<{.,.,~1 +<' Occupancy: Walls: Roof: Stories: SIC: ZONING COM~ENTS: lV\ \ Approval: \ \\J.. t- . Zoning: ~'I BUILDING COMMENTS: _ / Approval: IPIt '$1(7/ /3;t:- PUBL.IC WORKS COMMENTS: Approval: Electrical License No: Company: Plumbing License No: Company: Mechanical License No: Company: Expiration Date: Approval: Expiration Date: Approval: Expiration Date: Approval: (1) (1) (3) This pennlt was issued in accordance with me provisions set forth in your applicati'o.o. and is subject to the laws of tho State of Colon do and to tb.o Zoning RegulatiollS and Building Codes ofWh.eat Ridge, Colorado or any' oilier applicable ordinances of the; City. This permit sb.all expire if (A) the work authorized is not commenced within sixty (60) days from issu.e date or (1:1) tho building authorized is suspended or 'abandoned for a period of 120 days. Iflb.is permit expires, anew permit may be acquired for a fee ofone-llalftho amountnoxma.lly required, provided no changes have been or will be made in the original pla,ns and specifications a.n.d any suspensianorabandoomenthu notelCceededoue (1) year, If cb.anies ha....e been or ifsuspension or abandonment exceeds one (1) year, full fees shall be paid for anew permit No work of any manner shall be done that will change the natural flow ofW1lter causing a drainage problem. ConttactorshallnotifytheBuilding InsPectortwenty.foUI (24) hours in advmce for all inspections and shall receive written approval on inspection card before proceeding with. successive phases ofth.e job. . The issuance of a permit or the approval of drawings and specifications shall not be construed to be a pennitfor, nor an approval of, my violation. of the provisions of the building codes or any other ordinance, law, rule or regulation. . (4) (5) (5) 4~~~ ChiefBuil . g Inspector .~_._._._IO '6 " . , _ _._.__w______.._'_.___~ t< I ,-, n--" //'~~- 1- .-., ,~- (,QJ UII IUji (r~L~ I~I '. ) '--.j [I'j ~ I OJ in u- IJl j ull ~J) 8'\ A f1 () t)1..:.-0 I c..i,AIIJ,""''- J-f':TT~S ,,,,,,,-,,,,;(. TC vI' ~ .'(t..ANliw,'tt.) Ci) ) FRoi'l1 ;:JREV;e'u:' t-OC.rrttl:,v 1 ;J -':-- ~ , -'.. [ -- I'r) 5 v~,t- (; 30' -r~.~t-<>i ~ I I (f.) Ll'"-I-,,~,,,J ;//f'r- +t.) tie 'v\ ST~ ~ 5/,,,1' -rf, f'''' ..IL_ {'ICc.c.t~ (5jyn,'/I""'-' i-tP lY pr.5 erl ;.~t:e f..---'~' 1"- Ctc,,j.,.r. -DEPARTMENT OF PLANNING AND DEVELOPMENT BUILDING INSPECTION LINE - 303-234-5933 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 - (303-235-2855) Building Permit Number: 12100 Date: 5/7/2001 . Property Owner: Property Address: 4980 KIPLING ST #11 Contractor License No.: 19797 Company: Rocky Mtn. Fire & Safety Inc. OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Phone: Phone : 321-0345 I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and 89ree to abide by all conditions printed on this application, and that I assume full responsibility for compliance with the W5Rldge Building Code (U.B.C.) and all other applicable Wheat Ridge ordinances, for work unde his permit. (OWNER)(CONTRACTOR) SIGNED G~\ ~,v1-Jk...<Y O~/v '~/'D Total: $1,989.00 $69.25 $0.00 $29.84 $99.09 Construction Value: Permit Fee: Plan Review Fee: Use Tax: Use: If ill;~ Description: FIRE SUPPRESSION HOOD SYSTEM BUILDING DEPARTMENT USE ONLY SIC: Sq. Ft.: Approval : Zoning: Approval: Occupancy: Walls: Roof: Stories: Residential Units: Electrical License No : Company: Plumbing License No : Company: Mechanical License No : Company: Expiration Date: Approval: Expiration Date: Approval: Expiration Date: Approval : (4) (5) (5) This permit was issued in accordance with the provisions set forth in yopur application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Code of lNheat Ridge, Colorado or any other applicable ordinances of the City. This permit shall expire if (A) the work authorized is not commenced within sixty (60) days from issue date or (B) the building authorized is suspended or abandoned for a period of 120 days. If this permit expires, a new permit may be acquired for a fee of one*half the amount normally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. No work of any manner shall be done that will change the natural flow of water causing a drainage problem. Contractor sh notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceediin successive hases of the Job. The is 0 a . e approval of drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation of the provisions of the b d other ordinance, law, rule or regulation. Chief BUil~ing Ins~ (1) (2) (3) DEPARTMENT OF PLANNING AND DEVELOPMENT BUILDING INSPECTION LINE - 303-234-5933 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 - (303-235-2855) A -eEJ.Jc.A-o.o ^' ~~' .~olgO ~~ #- II Building Permit Number: \~,\(jD 05/D7/U / Date: Property Owner: Property Address: Contractor License No. . lA.J -~ Co. Phone: Company: ~ (Y\~ P~.~~one:"3o.::, 3;;.103I/S.... OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Construction Value: (<1 fQo7:> I I hereby certify that the setback distances proposed by this pennit application are accurate. and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate: that I have read and agree to abide by all conditions printed on this application. and that I assume full responsibility for compliance with the Wheat Ridge Building Code (U.B.C.) and all other applicable Wheat Ridge ordinances. for work, under this pel11)it. (OWNER)(CONTRACTOR) SIGNED f.': \L ~ Q........, ~--L .\i......., )DA TE ".,/0 '7/0 I ~- ,--- \ / 7 Use: Permit Fee: Use Tax: Total: Description: c:: I ~ i VLR. Jt<Lf~C4--t,Lc '6\/\ f-tCHJ-d . ~L_r-=- BUILDING DEPARTMENT USE ONLY SIC: Sq. Ft.: Approval: Zoning: Approval: Approval: Occupancy: Walls: Roof: Stories: Residential Units: Electrical License No : Company: Plumbing License No : Company: Mechanical License No : Company: Expiration Date: Approval: Expiration Date: Approval: Expiration Date: Approval: (1) (2) (3) This permit was issued in accordance with the provisions set forth in yopur application and is subject to the laws of the State of Colorado and to the Zoning Re,gulations and Building Code of Wheat Ridge, Colorado or any other applicable ordinances of the City. ThIs permit shaH expire If (A) the work authonzed IS not commenced Within SIxty (60) days from Issue date or (B) the building authorized is suspended or abandoned for a period of 120 days. If this permit expires. a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or wiil be made in the ongmal plans and specIfications and any suspension or abandonment has not exceeded one (1) year, If changes are made or if suspension or abandonment exceeds one (1) year, full fees shall be paId for a new permtt. No work of any manner shall be done that will change the natural flow of water causing a drainage problem. Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceediing with successive phases of the job. The issuance of a permit or the approval of drawings and specifications shall not be construed to be a permit for. nor an approval of. any violation of the provisions of the building codes or any other ordinan~, law, rule or regulation. (4) (5) (6) Chief Building Inspector THIS SYSTeM WILL BE INSTALLED IN JlCCOI\U.NCE WITH NfPA 17A, UL 3M STANDAIIDS, AND ALL MANUfACTUIlE SPECifiCATIONS TOTAL flOW POINTS to UICRIIIWlTCtlIU"LIID TO CDIITIUII. ALL IUCTRlCAL .UIICTIOIII . IXIlAUIT PAR lIIIun STAY 011 OR CoUI.II IF OFF . IIIIAKI U' AIIlIIUST SHUT DO" . ALL IUOTIUOAL ""LIANal. ...110 OUTLlTS UIID.R Till HOOD IIIUST SHUT DOn I INTI.DDlIlIloT FIRE ALARII 'AIIIL IF IXIITIIIG IlOCKY MOUNTAIN fie .. lIAI'~. INC. 3141 E. Ifl1I AVE DENVEI, co. _tl 303-UU34a ..tlZOOt PYIlO CHEM 3." 8JlI.LON WI!T COYE"'E NOZZLE DUCT PLENUM UNGE GUOOLE NLIZ Z. NLA Z. NLIUIZ NLIZ Z Z 4 Z IUCT INTE_acE EYEIV . " 3Z" - 4r t"'-4t". ..... VALVI TO SHUT DOWN ....IIU..L Y UPOII ACTIVATIDN INIlTALLEI 8): CHEMICAL SY8TEM - t3 flOW POINT8 MIlX flOW POINTS NOZZLE PLJ\CEMENT ".DTI PULL STATIDII LOCATID .N Till 'ATH O. IX" 1/1'" lilT ca.OuIT-CO.... 'ULLIV IAOH CHA..' D' D...OTIOII INIlTALLAnON DIITE: IOS81 CAnUNG _IlIPLING II tt WllEATlU8GI!, Co. I=YEI Pin: 3/'1"' .LAOK SONIDULE .. Fire protection system installers are responsible for the DY.3te<:n meeting Ul. and m:;;;Y'.l~:clct"),.!rers :ccoln:;TH;ndations of tIle ir..stJ..n.a1J.on NLIUIZ NLIUIZ NLlZ eMOTI! PULL 8TIIT10N Diwict HOOD: t..L X4"WX rH Approved as drawn subject to Field Inspection Contact TIle Arvada fire Marshal's QHicB at 425-0850,24 hours piiar to Final inspection. DEPARTMENT OF PLANNING AND DEVELOPMENT BUILDING INSPECTION LINE - 303-234-5933 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 - (303-235-2855) Building Permit Number: 12004 Date: 4/13/2001 Property Owner: Property Address: 49.80 KIPLING ST Contractor License No. : 20854 Company: Del-Co Stainless, Inc. OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Phone: 829-7694 Phone: 297-0308 Description: FABRICATED & I#LL S/S EXHAUSrtJOOD SYSTEM Total: $6,500.00 $139.25 $0.00 $97.50 $236.75 (' 0/ 0 Q4"1 1 hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application, and that I assume full responsibili for pliance with the Wheat Ridge Building Code (U.B.C.) and all other applicable Whea id inances for~~rk ,u;1er this permi " DATE y,: 7 Construction Value: Permit Fee: Plan Review Fee: Use Tax: (OWNER)(CONTRACTOR) SIGNED Use: .M CUF BUILDING DEPARTMENT USE ONLY SIC: Sq. Fl.: Approval: Zoning: OK Approval: OM Approval: Occupancy: Walls: Roof: Stories : Residential Units: Electrical License No : Company: Plumbing License No : Company: Mechanical License No : Company: Expiration Date: Approval: Expiration Date: Approval: Expiration Date: Approval: (4) (5) (6) This permit was issued in accordance with the provisions set forth in yopur application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Code of Wheat Ridge, Colorado or any other applicable ordinances of the City. This permit shall expire if (A) the work authorized is not commenced within sixty (60) days from issue date or (8) the building authorized is suspended or abandoned for a period of 120 days. If this permit expires, a new permit may be acquired for a fee of one-half the amount nonnally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandon",ent has not exceeded one (1) year. If changes are made or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit... . . . No work of any manner shall be done that will change the natural flow of water causing a drainage problem. Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceediing with successive phases of the job. The i ~it or the approval of drawings and specifications shalt not be construed to be a permit for, nor an approval of, any violation of the provisions u' i/ / I'; any other ordinance. law, rule or regulation. . (1) (2) (3) DEPARTMENT OF PLANNING AND DEVELOPMENT BUILDING INSPECTION LINE - 303-234-5933 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 - (303-235-2855) AffUcALlON gl/~ fIT~gbJ ~~11 / t{/&~,~ " ;2 tJ g 3'<( 1/ '( / .ff:ze; /?d...if ~ Company. Ik./ a ~ j~' OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Building Permit Number: Date: Property Owner. Property Address. Contractor License No. . Phone. :1t:73- .?z'1-7f<11 Phone ...Jti.? z:297 -tJ??J,I(' Construction Value. I hereby certify that the setback distances proposed by this permit application are accurate. and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or 'covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application, and that I assume full responsibili for compliance with the Wheat Ridge Building Code (U.B.C.) and all other applicable Whe Ridge ordinances. for ork under thIS;;1;:; / (OWNER)(CONTRACTOR) SIGNED' DATE Permit Fee. Use Tax. Total. tJvJm;;-g;:- Description . hti!~,& ~ ~:y:5 ~:/ .~ VI Use. ~!tmg Approval. Zoning. aJJl[lIltl~l'l&Q'tml1~m$~ Approval. SIC. BUILDING DEPARTMENT USE ONLY GJ1L 7 J//!~ e.nQlml'<<~~ornIDJtQ...~ Approval. Occupancy. Walls. Roof. Stories. Electrical License No . Company. Plumbing License No . Company. Mechanical License No . Company. Expiration Date: Approval. Expiration O'ate . Approval. Expiration Date. Approval. (1) (2) (3) (4) (5) (6) This permit was issued in accordance with the provisions set forth in yopur application and IS subject to the laws of the Stale of Colorado and to the Zoning Regulations and BUIlding Code of VVheat Rldge. Colorado or any other applicable ordinances of the City. This permit shall expire If (Al the work authonzed IS not commenced wlthm Sixty (60) days from Issue dale or (8) the building authorized is suspended or abandoned for a periOd of 120 days. If thiS permit expIres. a newpermll may be acquired for a fee of one-half the amount normally required. prOVided no changes have been or will be made in the anginal plans and speCIfications and any suspenSion or abandonment has not exceeded one (1) year. Jf changes are made or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. No work of any manner shall be done that will change the natural flow of water causing a drainage problem. Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceed ling WIth succeSSive phases of the Job. The Issuance permit or the approval of drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation of the provisions of the bUlldi es r ny other ordinan:e, law, rule or regulation. Chi .... DIatJIot imms Street. Arvada, CO 80004 . 303/424~30 12 . 303/432~ 7995 fax Wheat Ridge Building Department 7500 W 29th Avenue Wheat Ridge, Colorado 80030 4/8/0 I RE: Rossi Catering, 4980 Kipling Street. The following are our plan review comments; 1) The building address numbers shall be posted on a permanent basis and shall be affixed to the building in a minimum of 4 inch numbers on a contrasting background. UFC 97 901.4.4. 2) An approved fire-suppression system shall be provided for the protection of ventilating hoods, ducts, cooking surfaces, deep fat fryers, griddles, upright boilers, char broilers, range tops and grills. Protection shall also e provided for the enclosed plenum space within the hood above the filters and exhaust ducts serving the hood. UFC 97 1006.2.3.1. 3) The make-up air shal1 shut down and exhaust shall continue to operate upon fire protection system activation. 4) Submit (3) three sets of automatic fire extinguishing system plans for approval prior to work commencing. Fire extinguishing systems shall be installed by a licensed, factory authorized fire protection company. UFC 971001.3. 5) A separate permit for the installation of the fire extinguishing system will need to be obtained from the Wheat Ridge Building Dept. 6) In addition to the fixed fire protection system, a portable (K) unit fire extinguisher shall be installed. UFC 97 1006/2/7. 7) Provide emergency lighting by night light circuits or battery pack units. UFC 97 1211.1. 8) Emergency lighting sis subject to field inspection, additional units may be required. UFC 97a 1211.1. 9) Exit signs shall be subject to field inspection. Additional units may be required. UFC 97 1212.2. 10) The main exit doors in Group B Occupancies provided with a double cylinder key lock shall be provided with a sign stating "THIS DOOR IS TO REMAIN UNLOCKED DURING BUSINESS HOURS". UFC 971207.3. 11) All other exit doors in Group B Occupancies shall be openable from the inside without use of key or special knowledge. 12) If carpeting is installed it shall be a minimum of Class II critical Radiant Flux. Documentation shall be provided prior to installation. UFC 97 Appendix IV-A. 13) Fire extinguishers shall be a 4-A rated 10-lb ABC dry chemical type. The required number of units and mounting information shall be provided prior to final inspection. UFC 97 1002.1. 14) Any code requirements arising from construction will be addressed. IS) Twenty-four hours notice required for all tests and inspections. ..... Kent "Sparky" Shriver Fire Marshal Arvada Fire Protection District 1~"Ji !~~ ~" i 1 I I I, , ! ! I 11P"7g" ! I ! I 1 ; ! ! II II , , I I Jf1 /t.t> ~ ,y ~() V . 1; 0(' ~) \1' . f&~11 rP~ .f) I ~ I i I I , , I I I i i I I: , i , ! i I i , ~r.'jif.~:r;tr .1.a~li~Q~UJe~J~.k." ~~-- _ Jf. (Lt- A,' ,_ <:J ~_A!l.JJ:2_ _ d.7~___ 71'?h: If/x 4' xt.' I~ I J~ ~tx(#a' {;/;fM\,J'jILL 14 Il~ .""; At? ____._,_. _. ~ ~Y.'::':~~______~____ ~.~LlU~ V"P/}~- . '&Pff' ~ ~:2__ .eJ?-- , ~ It ! . iP4,j f'MId' 'f , .f ~}{ ~ Ad ~ ~'fA!t - I[ (\r~' j\ o<f '1 V ~c/h~ ~ ~9~~~ -I ... K 11H '" 1"?z.4 t mitJp. Ilt5v' I I .(21' IJ/-,Ll' W~= 1 ()(~', ~ ? ::tie -fur~1Z.Lttl4€f7 ,AI Hil~ 4- .pj{!:~ {~- .K;'(LLlf#:JJ JOOr? -Sr_~/I.J$i," ;~~ a.~ ~~l<J'<f~~ I k'fJI:.Jur V'J/f ,f01A....F.fuL-- 4,~~.. 11'/ 't . I ~t!ifl-~! ~ - ;; - -!~ ,-~ . rr,; - tJ. ki ,: Z3~:/J' U 'f -r..,--.-__... ......-'0> ~----- ~,y;?' . ~ffl~.:...4qQf&( - -. -~0-'"~f"'.=_.__. .. ._.WJ~Af~ ~ La Ih, r"? .. Jilft,.l~AL .-- J2.t"'~ ....- . 10 I 1{)'-! MU/:l.-/ u ~ \1'/ ~< ~.~~ I , . l ~~ i ~ \ \ ! \ i \ i I \ I \ I t , ~. i I ~ i , BUILDING DEPARTMENT \ \ 1 , , j I \ 1 I I (303) 235-2855 CITY OF WHEAT RIDGE * * Correction Notice , , J b L t d t L../ ~ 00 I /. /. /' r ' o oca e a 7 ~, c.), Uj j , / . I I have this day inspected this structure and these premises and 1 have found the following violations of City and/or State laws gov-' 1. erning same: 1 j , , I I 1 T ,/Jj./~:I ;u F /" ,,1., II 'I I" I ~ / I -) 2' ,II' (: ~ Inrd: /, /~.., fr/N/'"lft.4.J- J<i,-/I""/~- ~~-~> Ilk/Cop \ , t I I , , . I 1 I 1 You are hereby notified to correct the foregoing violations. When corrections have been made. call for inspection. i I i t I , [ \ \ Date ";//11" ,1 / I ;/.../ /~ ~for Dept. DO NOT REMOVE THIS TAG FORM WR6-22 ___...."...._.....,'_..."........,.....~......,.~ ~""'__~.......""~_~~~'j...:"...,.:..c-.---".......--'~c'-.........-'--~~._"-~~"""'-"'------....:.-........:-~-~~~.~- .... DIatrIot 3 Simms Street. Arvada. CO 80004 . 303/424-3012 . 303/432-7995 fax Wheat Ridge Building Department 7500 W 29th Avenue Wheat Ridge, Colorado 80030 4/8/01 RE: Rossi Catering, 4980 Kipling Street. The following are our plan review comments; 1) The building address numbers shall be posted on a permanent basis and shall be affixed to the building in a minimum of 4 inch numbers on a contrasting background. UFC 97 901.4.4. 2) An approved fire-suppression system shall be provided for the protection of ventilating hoods, ducts, cooking surtaces, deep fat fryers, griddles, upright boilers, char broilers, range tops and grills. Protection shall also e provided for the enclosed plenum space within the hood above the filters and exhaust ducts serving the hood. UFC 971006.2.3.1. 3) The make-up air shall shut down and exhaust shall continue to operate upon fire protection system activation. 4) Submit (3) three sets of automatic fire extinguishing system plans for approval prior to work commencing. Fire extinguishing systems shall be installed by a licensed, factory authorized fire protection company. UFC 971001.3. 5) A separate pennit for the installation of the fire extinguishing system will need to be obtained from the Wheat Ridge Building Dept. 6) In addition to the fixed fire protection system, a portable (K) unit fire extinguisher shall be installed. UFC 97 1006/2/7. 7) Provide emergency lighting by night light circuits or battery pack units. UFC 97 1211.1. 8) Emergency lighting sis subject to field inspection, additional units may be required. UFC 97a 1211.1. 9) Exit signs shall be subject to field inspection. Additional units may be required. UFC 97 1212.2. 10) The main exit doors in Group B Occupancies provided with a double cylinder key lock shall be provided with a sign stating "TillS DOOR IS TO REMAIN UNLOCKED DURING BUSINESS HOURS". UFC 97 1207.3. I 1) All other exit doors in Group B Occupancies shall be openable from the inside without use of key or special knowledge. 12) If carpeting is installed it shall be a minimum of Class II critical Radiant Flux. Documentation shall be provided prior to installation. UFC 97 Appendix IV-A. 13) Fire extinguishers shall be a 4-A rated 10-lb ABC dry chemical type. The required number of units and mounting information shall be provided prior to final inspection. UFC 97 1002.1. 14) Any code requirements arising from construction will be addressed. 15) Twenty-four hours notice required for all tests and inspections. - Kent "Sparky" ShriversFire Marshal Arvada Fire Protection District DEPARTMENT OF PLANNING AND DEVELOPMENT BUILDING INSPECTION LINE - 303-234-5933 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 - (303-235-2855) Building Permit Number: 11829 Date: 2/27/2001 Property Owner: Property Address: 4980 Kipling St Units 10 & 11 Contractor License No. : 20927 Company: ROGER ROSSI CONSTRUCTION OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate: that I have read and agree to abide by all conditions printed on this application, and that I assume full respons "lity for compliance with the Wheat Ridge Building Code (U.B.C.) and all other applicable W e Ridge ordi ances, for work under this permit. (OWNER)(CONTRACTOR) SIGNE DATE?h:~1 Description : Interior alteration. BUILDING DEPARTMENT USE ONLY Change of use allowed. Approval: mlc Zoning: C-1 Approval: OM Approval: Occupancy: Walls: Roof: Stories : Electrical License No : 19894 Company: Kruse Electric Inc. Expiration Date: 7/3/2001 Approval: Plumbing License No : 20938 Company :DOUBLE "D" PLUMBING, INC. Expiration Date: 2/27/2002 Approval: BG Phone: 303-233-9581 Phone: 3032339581 Construction Value: Permit Fee: Plan Review Fee: Use Tax: $55,000.00 $678.75 $0.00 $825.00 $1,503.75 Total: Use: SIC: Sq. Ft.: Residential Units: Mechanical License No : 19827 Company: Walrath Heating and Air Cond Co. Inc. Expiration Date: 1/23/2002 Approval : This permit was issued in accordance with the provisions set forth in yapur application and is SUbject to the laws of the State of Colorado and to the Zoning Regulations and Buildlnf! Code of Wheat Rldge, Colorado or any other applicable ordinances of the City. This pennit shall expire if (A) the work authonzed is not commenced within sixty (60) days from issue date or (B) the building authorized is suspended or abandoned for a period of 120 days. If this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment ~as not exceeded one (1) year. If changes are made or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. No work of any manner shall be done that will change the natural flow of water causing a drainage problem. Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all Inspections and shall receive written approval on inspection card before proceedllng with successive phases ot the I i.,ob. The issuance of rmlt or the approval 0 drawings and speciflcations shall not be construed to be a permit for, nor an approval of, any violation of the provisions of the building or a y 0 ordinance, law, rule or regulation. (1) (2) (3) (4) (5) (6) '" DEPARTMENT OF PLANNING AND DEVELOPMENT BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 Building Permit Number: Date: 2/27/2001 11829 Property Owner: Property Address: 4980 Kipling St Units 10 & 11 Contractor License No. : 20927 Company: ROGER ROSSI CONSTRUCTION R SIGNATURE OF UNDERSTANDING AND AGREEMENT Phone: 303-233-9581 Phone: 3032339581 Construction Value: Permit Fee: Plan Review Fee: Use Tax: (OWNER)(CONTRACTOR) SIGNED DATE Total: $55,000.00 $678.75 $0.00 $825.00 $1,503.75 I hereb I the setback distances proposed by this pennit application are accurate, and do not vi e applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application, and that I assume full responsibility for compliance with the Wheat Ridge Building Code (U.B.C.) and all other applicable Wheat Ridge ordinances, for work under this permit. Use: Description: Interior alteration. BUILDING DEPARTMENT USE ONLY SIC: Sq. Ft.: Change of use allowed. Approval: Occupancy: Walls: Roof: Stories: Residential Units: Electrical License No: 19894 Company: Kruse Electric Inc. Expiration Date: 7/3/2001 Approval: Piumbing License No : Company: Mechanical License No : 19827 Company: Walrath Heating and Air Cond Co. Inc. Expiration Date: 1/23/2002 Approval: Expiration Date: Approval: (4) (5) (6) This permit was issued in accordance with the provisions set forth in yopur application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Code of Wheat Ridge, Colorado or any other applicable ordinances of the City. This permit shall expire if (A) the work authorized is not commenced within SIxty (60) days from issue date or (8) the building authorized is suspended or abandoned for a period of 120 days. If this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. No work of any manner shall be done that WIll change the natural flow of water causing a drainage problem. Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceediing with successive phases of the job. The issuanc permit or e approval of drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation of the provisions of the u' des r ther ordinance, law, rule or regulation. (1) (2) (3) Chief Building Ins For Mayor THIS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION DEPARTMENT OF PLANNING AND DEVELOPMENT BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 Building Permit Number: \ \txiq Date: APPLICATION FORM Property Owner: /<:>>5 SI . 's C.kl~/l;.J~ Property Address tfttf;>o 41''-;.-/tT t!,P/TT:> /ut/l Contractor License No. : ().O 9 )f1 /J . f) . ;; Company: ib4~-n kJ'1>.G; r:tN<J51/l<<.a:r70 OWNERlCONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Phone :C3P~) .r:33 .-9'5:8/ I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application, and that I assume full responsibilit or compliance with the Wheat Ridge Building Code (U.B.C.) and all other applicable Whea . ge ardi ces, for ~ark under th7r7& / (il. .I._,l/(CONTRACTOR) SIGNED DATE i-? Phon(7C;l) R,g/-';:656 .5 -' C5lSD I Permit Fee: Plan Review Fee: Use Tax: Total: Use: Description: -:url -4J./v- <?<.J!i 0---- Approval: r"'---4liiIli__ Approval: Occupancy: Walls: BUILDING DEPART rJ \'< .& SIC: Sq. Fl.' -"~~IJI.!ii!l. ,A,,,,,, ,,,,:,~:,,'1. ';)",,4'..""" """'-"'"iv,. \ (\ Approval :1\ \A.L.. Zoning: C - \ Residential Units: umbing License No . o CMech8nlcal LiCense N0 Company: No.1rrn \\. Expiration Date: Approval: Expiration Date: Approval: Expiration Date: Approval: (1) (2) (3) This permit was issued in accordance with the provisions set forth in yo~r application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Code of Wheat Rid~e, Colorado or any other applicable ordinances of , the City. This permit shall expire if (A) the work authonzed IS not commenced within sixty (60) days from Issue date or (B) the building authorized is suspended or abandoned for a period of 120 days. If this permit expires, a .new permit may be acquired for a fee of one-half the amount normally required. provided no changes have been or will be made in the original plans and specIfications and any suspenSIon or abandonment has not exceeded one (1) year. If changes are made or If suspensIon or abandonment exceeds one (1) year, full fees shall be paid for a new permit. No work of any manner shall be done that will change the natural now of water causing a drainage problem. Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all mspections and shall receive written approval on inspection card before proceediing with successive phases of thel'Ob. The issuance of a pe it or the approval 0 drawings and specifications shall not be construed to be a permit for. nor an approval of, any violation of the provisions of the building s an ther ordinance, law, rule or regulation. (4) (5) (6) Chief BUI ding In THIS PER VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION I I, I' ~ !I ~ l' 39'-4H , 8'-710 8 . DINNING ROOM SCALE= 3/16" = 1 '-0" ENTRY ll'-gu ll'-gu f/"./ "" ,,,; ,/,,,././,, //././././" A BUILD-UP WALL 2' FROM EXISTING 17'-6H OFFICE ll'-gu 59'-9H 10'-6 H '-3H WOMENS BATHROOM I '-3D i i MENS i! BATHROOM I! 6'-UU II ! ! 1 ! PROPOSED KITCHEN 30'-91H 4 28'-010 2 3'17' j ! I II I I I Ii I! i! I, I I ! I I i I , , I ! ! I I I i I I I I I EXI~ I 120551' 5 (:A-r~!/j,J&- ,,/,q(J b K't j.!oJ4- U/-h r /0 ic tf " . > f 10 CU/fG7irlt(~E, ~J! ~ CIl ~ "" 0 CIl ':l-... .s::. , <II ....: ~ U C 0. 0 CIl C ~ 0 ~ .!!! CIl Cl 0. C ~ <II :Q E '5 OJ 'tl CD 0 Qi CIl u: Cl 0 -0 - Ii: tl - CIl OJ :s- CIl .s::. :> 3: III ! n-- !I II " " II II n '. " Ii !j il ~ I, i! ,. i! I! II II " " _JJ /" '\ \; "- ~ n d '. " n '. U " II Ii q II cl II I' I, '. " " il H II U ,. il i! I! " il II I! n " 'I J i:~- \ \. lL_______ DINNING ROOM [~ ENTRY-.c ",V vr'~\ ~/\ t' d i.v U~T 1='~.J1ir- "' ..-1- 001s .pp,nJr&'''-' J c,:r:!"-V" 3~ "He!'v, -STORAGE ,- "StfiU .{r{b --- --";Q'FZB;;-;;::;Jt- FfLP vl~ls> WOMENS BATHROOM ...-.1------,---,...-......."........---1 ' Uc.r,'uxw.Jift,! !*twf?,D e.JM't'- ' MENS BATHROOM I "~ iJ (;/ h 0 OiL ;/.)f; r4It)/!?b u) 411"0 5'lS' pe7Jti-! ~b") r:- t!:., OVEN STOVE GRILL , I SINKS EXHAUST HOOD 9' 7'-2~" D F- I D /JOt) S/(rf) /-1.0,..... D F(l.l u)/l-ils lJ~tUl!/! Ldtf$rfiretr Cc;') t/~f;- PROPOSED KITCHEN ~ ~ I " 1 In ! ~ I I I I L -~ EXIT I Ii. I , '" W N W W '" u.. 4'-4" OFFICE e1 !~ l.Jcfv' V~ SCALE= 3/16" - 1 '-0" NEW DISHWASHER 23AMP@ 120 V FREEZER 10.3AMP @ 208V CONVECTION OVEN 3.6AMPS @ 208V EXHAUST HOOD FAN 12.5AMPS @ 120V NEW EXIT FIXTURE /W/BATTERY BACK-UP EMERGENCY LIGHTS EXISTING RECEPTACLES AND LIGHTING EXISTING RELOCATE TO PANEL "B" 120V REFRIG EXISTING EXHAUST FANS EXISTING PANEL "B" TO PANEL "B" SINKS D EXISTING LIGHTING TO PANEL "A" 6,8 - 10.3A lj1 ,. ~MAIN ELECTRICAL SERVICE ~ i! il; " ~ 1t------ TO PANEL "A" 120V I ! 23A _ CKT 10 Ii II II . , I! >l3Z33lU . . . , i i .~ EXIT l .I i i 1 ~ EXISTING PANEL "A" SCALE= 1/8" - 1'-0" '-..... D PARTMENT OF PLANNING AND DEVELOPMENT BUILDING INSPECTION LINE - 303-234-5933 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 - (303-235-2855) Building Permit Number: Date: 10908 7/26/2000 . Property Owner: Property Address: 4980 KIPLING ST, UNITS 5 & 6 Contractor License No.: 17232 Company: Colorado & Santa Fe Construction Co. ONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Phone: 466-2500 Phone: 466-2500 Desc ption: CONSTRUCT IVIDING NON-BEARING WALL BETWEEN UNITS 5 & 6 FOR CAMPBELL MUSIC LOCATED @4980 KIPLING ST DATE Total: $4,000.00 $97.25 $0.00 $60.00 $157.25 Construction Value: Permit Fee: Plan Review Fee: Use Tax: I hereby rtify that the setback distances proposed by this permit application are accurate, and do no violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants easements or restrictions of record; that all measurements shown, and allegations made are ccurate; that I have read an a9ree to abide by aU conditions printed on this applicatio ,and that I assume full resp Ibility for compliance with the Wheat Ridge Build. 9 Code (U. C.) and all other applicable e t Ridg ordinances, for work under this ermit ?-1 ()O (OWNER) CONTRACTOR) SIGNED Use: BUILDING DEPARTMENT USE ONLY SIC: Sq. Ft.: 7/25/00 Approval: Oc upancy: Walls: Roof: Stories: Residential Units: I License No : 17232 y :Colorado & Santa Fe Construction Co. Expirat on Date: 4/25/2001 Appro I: Plumbing License No : Company: Mechanical License No : Company: Electri Comp Expiration Date: Approval: Expiration Date: Approval: l~l (6) his permit was issued in accordance with the provisions set forth in yopur application and is subject to the laws of the State of Colorado and to the Zoning egulations and Building Code of Wheat Rid~e, Colorado or any other applicable ordinances of the City. is permit shall expire jf (A) the work authorized is not commenced within sixty (60) days from issue date or (B) the building authorized is suspended or bandoned for a period of 120 days. I this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the riginal plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment xceeds one (1) year, full fees shall be paid for a new permit. o work of any manner shall be done that will change the natural flow of water causing a drainage problem. ontractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before roceecliing with successive phases of thel.Ob. e issuance of a permit or the approval 0 drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation of the provisions f the bu. . 9 cocIes or any other ordinance, law, rule or regulation. (1) (2) (3) DEPARTMENT OF PLANNING AND DEVELOPMENT BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 APPL\(f\TIO N Building Permit Numter: ~(o1{)g Date: 1/~407) Property Owner: COL.ORAoO ~. SftNTI+'* ~',' (( '(.~J~lrf~ lII9f .....C CoN.,~(.jIC>N Co. PropertyAddress: 'I1BO !<-IPLIN6;;l.T,) lI'1;ts ~+b Phone: ~o~'ft..~ -~5'D'D Contractor License No.: / 1- ~;3;;;L Company: (PU>f.tto~ ~ SA-N7\'I.ft:.lefVlTlUL11~ C" Phone@.b3) 1~(" -;/ S-ob OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Construction Value: t;ODD "S- I hereby certify t~at the setback 'distances proposed by t~is permit aPl?lication are IC?Curate, and do not vlola~e applicable ordinances. rules or regulations of the CIty of Wheat RIdge o.r covenants. eaSejITlents or restncticns of record; that all measurements Shown, and allegatIons made are accurate; that I have read and agree to abide by all conditions printed on this application. and that I assume full respo ibility for compliance with the Wheat Ridge Building Code (U.S.C.) and all other applicable Ridge 'rdinance.. for wor!< under :;rrmr' (OWNER)(CONTRACTOR) SIGNED . . - DATE;;d IfO Permit Fee: Use Tax: Total: Use: Description: ~NS~c:r DIVIOING NCJN-13EfK.IN6 WI'I-u. BE.~ uNIT6 'fO~ C.l'\'rV\pB€t-L MUSIC LOc.A--f\C{) e i"l'OD )GII'LII\Jc, 5... , fi'e:-La. BUILDING DEPARTMENT USE ONLY ~onJ.Ilg~..!i'm~~!:I~ Approval: Zoning: ~,'~ln94tmm.nlr.il I Approval: ..,/:1<;-/(10 SIC: ~UD.'.~~~~'~"I~n~ Approval: Occupancy : \'.... RECEI EO JUL 2 A. ?nn~ Walls: Roof: Stories: Residential Units : Electrical License No: ~_I i/ 5':3 Company' 7 ('h~O' S.~1€- ~t>js,Co. 15/l."'.e... w~13ROr'" i Expiration Dale: 8-10.6 0 I Approval: Plumbing License No : Company: Mechanical License No : Company: Expiration Date : Approval : Expiration Date: Approval: (1) ThIS penn;tWUIIIued "'.& 4lo.._With"prDIIiIionIMtfarl'l in'fOtM' J.c . - .... talUD!ilCtlOlhelevs or.. State ot CoIoraoo..,., 1D":.arq Regu__a.-.gea.aI_Iticlge.~......___o/...CIty. (2) ThIS permjt sh811 ..,. If (A) tne work authonDd IS not _..._.-4 Witl'lln SDCty (80) days '"'"' issue clllte Of (B) tI'Ie building autnonz:ed IS suspenaea or abandOned for a oenoa of 120 days. (3) It tnis pentut 1IXf)lteS, a new ,""",,""'" De KQUftd for a ,.. 01 one-hatl' Ihe a'f'IOUnt nom'IIlty rwquired, pn:tvicllld no c:ftanges n.ve tIftn or wilt De fI'IIlde in WI onglnal~and IP1~ _and..,- ~ ~'''~4....._.lnasnatexceedadone(1)ynr. 1t~"'1Ndeoritl'IIPI ~_.or4b-~..._il _~~(11.... __.._.....__ (4) No work 0\' any manner..,... be done... will c::t\atIge the ftIIUI'al now of __ causing a draiNge ~ (51 ~CIOli"'.lInotify...B-.__(2.)IIaurs.._......______..._calU_ p~ WIth - . .. DftUes OI"';ob. (E1) ThellSUMce at I petmIt or.. ~ot drWlMngIlI'Id _~..-Sftd not be c:anstrued 10 bill pemit for. nor In approval of. any VICUtIon afU'le pnMIIOftI of...~_......llIlIor_......_.._. Ch~~fn~r DEPARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number: 8820 BUILDING INSPECTION LINE - 303-234-5933 CITY OF WHEAT RIDGE Date: 4/26/99 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 - (303-235-2855) Property Owner: Properly Address: 4980 KIPLING ST Contractor License No. : 17232 Company: Colorado & Santa Fe Construction Co. OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Phone: 466-2500 Phone: 466-2500 Construction Value: Permit Fee: Plan Review Fee: Use Tax: Total: $225.00 $23.50 $0.00 $3.38 $26.88 r hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application, and that I assume full responsibility for compliance with the Wheat Ridge Building Code (U.B.C.) and all other applicable Wheat Ridge ordinances, for work under this permit. (OWNER)(CONTRACTOR) SIGNED DATE Use: Descri ption : Wire new sign to existing sign circuit BUILDING DEPARTMENT USE ONLY SIC: Sq. Ft. : -- Approval: .,.~ ,,,drml,_ Approval: Occupancy: Walls: Roof: Stories: Residential Units: Electrical License No : Company: Plumbing License No : Company: Mechanical License No : Company: Expiration Date: Approval: Expiration Date: Approval: Expiration Date: Approval: (1) (2) (3) This permit was issued in accordance with the provisions set forth in yopur application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Code of Wheat Ridge, Colorado or any other applicable ordinances of the City. This permit shall expire if (A) the work authorized is not commenced within sixty (60) days from issue date or (8) the building authorized is suspended or abandoned for a period of 120 days. If this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes are made or jf suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. No work of any manner shall be done that will change the natural flow of water causing a drainage problem. Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceediing with successive phases of the job. The issuance of a permit or the approval of drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation of the provisions of th:;(7g codes or any other ordinance, law, rule or regulation. ,-"':. mJ..~ Chief Building Inspector (4) (5) (6) -..... .........-.-- -- - - BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 Date: 1-)fo ,qq Property Owner: Property Address: Contractor License No. : Company: Colorado f-- ~+o._ LvdPpMd e,nc.e L/qgo ~pl,"j Y.t.. V o.re.. L-L-L Phone: , I1Mo' J~MY Fe...- (O\s+rlJt:t'.cr, [bPhone: OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Construction Value: Permit Fee: ~~(rd:;tlJ dJ-~~ t'() I hereby certify that the setback distan proposed by this permit application are accurate, and do not violate applicable ordinance. les or regulations of the City of Wheat Ridge or covenants, easements or restrictions 0 re ref; that all measurements shown, and allegations made are accurate: that I have read a 39 e to abide by all conditions printed on this application, and that 1 assume full res nSI lity f r compliance with the Wheat Ridge Building Code (U.B.C.) and all other applicable e t Ri e ordinan s, r wo under this permit. , DATE il ,)(,. 19 Use Tax: Total: $0.00 (OWNER)(CONTRACTOR) SIGNED Use: Description: iJJ~ ~.~ -k BUILDING DEPARTMENT USE ONLY . ~ SIC: Sq. Fl: f!)tI!rr~Ommll1LtsJ Approval: Zoning: ~mrmncOl1lIDemSll Approval: e.nJ51r~O~K~9mnJ!!n~ Approval: Occupancy: Walls: Roof: Stories: Residential Units: Electrical License No: iiP)'s- Company: s.. MfL-- Plumbing License No : Company: Mechanical License No : Company: Expiration Date: Approval: Expiration Date: Approval : Expiration Date: Approval: (') (2) (3) This pennit was Issued In accordance with the provisions set forth In yopur application and Is subied to the taws of the State of Cotorado and to the Zoning Regulations and Buildi"9. Code of W'heat R1dge, Colorado or any other applicable ordinances of the City. This permit shall expire If (A) the WOfk authorized Is not commenced within sixty (60) days from Issue date or (8) the building authoriZed is suspended or abandoned for a period of 120 da)'s. . If this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension Of abandonment exceeds one (1) year, full fees shall be paid for a new permit. No wor1< of any manner shall be done that will change the natural1\ow of water causin~ a drainage problem, Contrac:tor shall notify the Building Inspedor twenty.four (24) hours In advance for aU Inspections and shall receive written approval on lnspedion card before' proceed1ing with successive phases of the Job. The issuance of a pennit oc the approval of drawings and specifications $hall not be construed to be a pennit for. nor an approval of. any violation of the provisions of the building codes or any other ordInance. law, rule or regulation. (4) (5) '(6) Chief Building Inspector For Mayor THIS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION I D'PARTMENT OF PLANNING AND DEVELOPMENT BUILDING INSPECTION DIVISION - 235-2855 . CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 Building Permit Number: Date: 8571 3/5/99 ~ Property Owner: Property Address: 4980 KIPLING ST SUITE 15-B Contractor License No. : 20265 Company: Sign World of Colorado ONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Phone: 940-3400 Phone: 773-9369 Total: $1,221.00 $47.90 $0.00 $18.32 $66.21 I hereby c rtify that the setback distances proposed by this permit application are accurate, and do no violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants easements or restrictions of record; that all measurements shown, and allegations made are ccurate; that I have read and 89ree to abide by all conditions printed on this applicatio ,and that I assume full responsibility for compliance with the Wheat Ridge Building Code (U. .C.) and all other applicable Wheat Ridge ordinances, for work under this permit. Construction Value: Permit Fee: Plan Review Fee: Use Tax: (OWNER) CONTRACTOR) SIGNED DATE Use: Desc iption : 18" X 96" lighted sign cabinet BUILDING DEPARTMENT USE ONLY SIC: Sq. Ft.: Approval: MLC Zoning: C-1 complies w/sign code okay, to meet NEC article 600 Approval: Oc u pancy : Electri~al License No : comp1ny : Walls: Roof: Stories: Residential Units: Plumbing License No : Company: Mechanical License No : Company: Expiration Date: Approval: Expiration Date: Approval: (4) (5) (6) his permit was issued in accordance with the provisions set forth in yopur application and is subject to the laws of the State of Colorado and to the Zoning egulations and Building Code of lJIIheat Ridge, Colorado or any other applicable ordinances of the City. is permit shall expire if (A) the work authorized is not commenced within sixty (60) days from issue date or (B) the building authorized is suspended or bandoned for a period of 120 days. f this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the riginal plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment xceeds one (1) year, full fees shall be paid for a new permit. o work of any manner shall be done that will change the natural flow of water causing a drainage problem, ontractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before roceediing with successive phases of the job. e issuance of a permit or the approval of drawings and speCifications shall not be construed to be a permit for, nor an approval of. any violation of the provisions f building codes or any other ordinance, law, rule or regulation. (1) (2) (3) DEPARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number: BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE Date: 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 A PPL\ C.f\T I D N ~s71 Property Owner: .J:/.JN:.[!f1J{)(-ilC(- stlYIi-fE LL. ( Property Address: L[11i'D kif!-I,J& SlA/7r 15~8 Contractor License No.: <::O;20;;XLJ-r Company: 5 !utJG;o~o oy ("LOf<Jr{Jr) OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Phone Do)} qlf()-3 I(OcJ Phone: C3 03) 7;73- "(3G7 Construction Value: I d,;2 \ . Cf'-! I I hereby certify that the setback distances proposed by this permit application are accurate. and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and a~ree to abide by all conditions printed on this application, and that I assume full responsibility for compliance with the Wheat Ridge Building Code (U.B.C.}and all other applicable ~~ces, for work under this penni!. (OWNE~~T~SIGNED ), . DATE 3/1 /1 r ~' --:Del''''''''' S\,CL(H\D0 ' Permit Fee: Use Tax: Total: Use: Description: t S 'I X '1 (;, I' Li 6'Ih6/J )ltrtJ VwtNf1 Q- ~.RIIIf~~ Approval: -J-O /'Yl)... t1- BUILDING DEPARTMENT USE ONLY Cbffi~~ \D/s/?f C~ Cf)Jc.-- f)m ,; .'1- q :> NCe... 1JP,h'cb ,()9. .'.!', .I~ ! iP \ ..'-- .. "- SIC ':;:,.\c/ Sq~ ,'.0 ,. A. "\ ,I F4." VI/ OECt.NS~ .~~. " O. '\ 'I'!"/~ .., " \1\1-\1' 6 -, -.. 1 .' ,.l. " Approval: Occupancy: Walls: Roof: Stories: Electrical License No : Company: Plumbing License No : Company: Mechanical License No : Company: Expiration Date: Approval: Expiration Date: Approval : Expiration Date: Approval: (4) (S) (6) This permit was issued in accordance with the provisions set forth in yopur application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Code of Wheat Ridge, Colorado or any other applicable ordinances of the City. This permit shall expire if (A) the work authorized is not commenced within sixty (60) days from issue date or (8) the building authorized is suspended or aba~doned. for a period of 120 days. . . . .. It thiS permit expires, a new permit may be acquIred for a fee of one-half the amount normally required. proVIded no changes have been or will be made In the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. No work of any manner shall be done that will change the natural flow of water causing a drainage problem. Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceediing with successive phases of the job. The issuance rmit or the approval of drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation of the provisions of the buildi s or her ordinance, law, rule or regulation. (1) (2) (3) 158 ! i iTt "'T'i i-'-j-.[ .-,. ; "j I r'J r:j 'J t-r] i i, ~ t'- ~ , i~ ')'J . !'i C"!.' '\1 ;Tl '..;J, i'I'1 ~tll' i--t.' ': ~~i:. : ; ,"...' ... J' , : "''''. .. I' :nU "I! . II -r.; , , < .. 9 T ,r' ~t> WASHINGTON INVENTORY h .~ ~ . __ __n____ . --.. T i:U ....n /8 ,~ - F;;0 , C//l t)~ ~/o .. 't> L s 5 IIUIAlsu.{c.eAl T we. e.,ye(<- 03/01/99 MON 14:33 FAX 1aI002 LEGAL DESCRIPTION LOTS 1 J\N[)' 2, .REPLATOF LOT 1, KlPUNG 5000 Su$INESS PARK AEPLAT OF LOT 1 SECOND FlUNG AS REC9RDED IN BOOK 81 AT PAGE 31 UNDER RECEPTION NO. 84106971 IN THE JEFFERSON COUNTY RECORDS, STATE OF COLORADO CONTAINING 147,906 SQUARE FEET OF 3.395 ACRES.' .' , ~. TRACT A As SHOWN ON THE REPLAT OF LOT 1, KlPUNG 6000 BUSINESS PARK REPLAT OF LOT 1, SECOND FlUNG AND ADDITIONALLY.DESCRlBED IN CrtY OF WHEATRIDGE COUNCIL BILL NO. 126, ORDINANCE NO. 569, SERIES OF 1984 AS OESCRIBED UNDER 'RECEPTION NO. 84039242 AND RECEPTION NO. 87020514 OF THE JEFFERSON COUNTY RECORDS, STATE OF COLOAAOO, CONTAINING 2665.SQUARE FEET OR 0.081 ACHES; RESULTING IN 150,570 SQUARE FEET OR 3.457 ACRES. _ HLE COMMITMENT NOTES HIS SURVEY DOES NOT CONSTITUTE A TiTlE SEARCH BY JR ENGINEERING, LTD. TO IETERMINE OWNERSHIP OF THIS TRACT OR TO VERIFY THE DESCRIPTION SHOWN; THE :OMPATlBILITY OF THIS DESCRIPTION WITH THAT OF ADJACENT TRACTS; NOR ASEMENTS OF RECORD. FORALL INFORMATION REGARDING EASEMENTS, RIGHT-OF-WAY IR TITlE OF RECORD, JR ENGINEERING,- LTD. REUED UPON TITlE CUMMITMENT NO. .BP0391431, PREPARED BY LAND TITLE GUARANTEE COMPANY, DATED OCTOBER 13, 1993 .T 8:00 A.M. . HE FOLLOWING COMMENTS ARE IN REGARDS TO LAND TITLE GUARANTEE CQMPANY JMMlTMENT NO. ABP0391431. DATED OCTOBER 13, 1993 AT 8:00 A.M. THE NUMBERS IN JR COMMENTS CORRESPOND TO THE NUMBERING SYSTEM USED IN SAID TITLE )MMITMENT. . :;HEDULE A :M: COMMENT: . - AS SHOWN HEREON TO THE .BEST OF OUR KNOWLEDGE AND BELIEF. ~,4 JR ENGINEERING, LTD. DID NOT EXAMINE OR AO[)RESS THESE ITEMS. AS SHOWN HEREON TO THE BEST OF OUR KNOWLEDGE AND BEUEF. :HEDULE B-1 oM: COMMENT: 03/01/99 14:47 TX/RX NO.3250 P.002 . V"'/ v.....,...... ~n(~_. ..~.~_~_ - ~iI:._ , i ~.. t~\' :.". :.." 03/01/99 MON 14:34 FAX ~003 SURVEYOR'S CERTIFICATE . r. MATHEW E. SELDERS, A PROFESSIONAL lAND SURVEYOR REGISTERED IN THE STATE OF COLORADO, UCENSE NO. 27276, DO HEREBY CERTIFY TO DEVLET.GETSoN, TO VICTORIA INN ACQUISmONS CORPORATION, A COI.OAAQo CORPORATION; AND TO lAND ffiLE GUARANTEE COMPANy, AS FOLLOWS: THAT THE AlTAlACSM lAND TITLE SURVEY ON WHICH THIS CERTIFICATE APPEARs (THE'''SURVev, IS BASED UPON A FIELD SURVEY CONDUCTED BY ME OR UNDER MY SUPERVISION ON NOVEMBER " 1993; THAT SUCH FILED SURVEY AND THIS SURVEY WERE MADe IN ACCORDANCE WITH THE REQUIREMENTS . OF ARTICLE 51 OF l1TlE38 OF THE Col.OAADO REvISED STATUTES AND IN ACCORDANCE WITH THE "MINIMUiI!' STANDARD DErAIL REQUIREMENTS FOR AlTAlACSMlAND lJTUi SURVEYS: JOINnY ADOPTED BY AlTA AND ACSMIN 1992, M&ET8 THE ACCURAC'( REQUIREMENTS OF AN URBAN SURVEY, AS DEFINED THEREIN, AND (t4ClUDES lTI;MS " 3, 4, 8, 7 (a), 8. 10 AND 11 OF TABLe A THEREOF; THAT THE leGAl. DEsc.RlP11bN SET FORTH ON THE SURVEY IS A cOMPlETE AND COAlU5CT l.EGAl.DESCRlPTI9N OF THE . SURVEYED PROPERTY; THAT rHE' SURVEY"~REOTLY 100NTlI!lES (1) AL(;.,'COURsES, .. MIiA8URED Df8TAN0E8 AND ..CIJFM! DAJ:'A. (2) TH&' AIlOOAD!!'I'm.ir UNO Of' THE : . SURVEYED PROPERTY AND ALL LOT UNES; IF ANY. (3) THE L~1'lON;D1MENSIONS AND 1YPE OF AU BUILDINGS ANOOTHERSTRUe1\JRES ON THE SURVEYED.PROPERlY, (4) THE LOCATION OF AU FENCES, HEDGES, WAI..I.S.FOUNDAl1ON8 AND OTHER VlSlaLf; AND. APPARENT IMPROVEMENTS ON OR WITHIN lWO FEET OF THE BOUNDARIES OF THE . SURVEYED PROPERTY. (6) THE LOCATION OF ALL DITCHES, WATER 'c6I.JRSES,ELECTRIC AND TElePHONE UNES AND OTHER ununES SERVING THE SURVEYED PROPERTY, BASED ON RECORDEDUTlUlY EASEMENTS (AS. REFLECTED IN THE' TIllE COMMITMENT" DESCRIBED BELOW) AND VISiBLe SURFACe EVIDENCE ON THESURViYED PROPERlY. (6) THE LOCATION AND DIMENSIONS 01" ALL EASEMENTS ANO RlGHl'8.oOF-WAY OF RECORD. (AS REFLE<!TED IN THE TITLE COMMITMENT DESCRIBED BELOW) 'OR VISIBLE ON THE SURVEYED PROPERlY (INCWDING THE BOOK AND PAGE OR RECEPTION NUMBERS OF ANY RECORDED INSTRUMENTS CREATING SUCH EASEMENTS OR RIGHTS-OF-WAY AND ALL EASEMENTS AND RIGHTS-oF-WAV CRFATED BY AN INRTRUMENTOF RECORD HAVE BEEN LOCATED IN ACCORDANCe WITH THE LEGAL DeSCflIPTION\'SET FORTH IN SUCH RECORDED INSTRUMENT), m THE LqcATION AND WIDTtt OF. ALl PUBLIC STREETS. AND ALLEYS ABUTTING THE SURVEYED PROPERlY AND (8) THE SCAIJi AND THE INO/CATION _ OF NORTH; THAT, EXCEPT AS8HOWN ON 'THE SURVEY; NOWl/SLe AND APPARENT IMPROVEMENT ON THE SUAVE't'ED PROPERTY ENCROACHes-ON ANY ADJACENT PROPERlY OR ON ANY EASEMENT OR RIGHT-OF-WAY ANC':JliAT NO VISIBLE AND ApPARENT IMPROVEMENT ON ADJACENT PROPERlY ENCROACHES ON THE SURVEYED PROPERlY; THAT INGRESS TO AND EGRESS FROM THE -SURVEYED PROPERlY ARE PROVIDED BY K1PUNG STREET AND WEST 50TH AVENUE (WHICH STREET HAs BEEN DEDICATED TO, AND ACCEPTED FOR MAINTENANCE BY, A GOvERNMENTAL AUTHORITY}; THAT, EXCEPT AS SHOWN ON:THE SURVEY. THE SURVEYED PROPERTY DOES NOT SERVE ANY ADjOINING PROPERlY FOR EGRESS, INGRESS. DRAINAGE OR arHE'R PURPOSE; THAT THE SURVEYED PROPERlY IS LOCATED IN ZONE 8, THE AREA DETERMINED TO BE OUTSIDE THE 100-YEAR FLOOD PLAlN, ACCORDING TO THE FEMA FLOOD INSURANCE RATE MAP COMMUNllY PANEL NUMBER 08507llOOO5C DATED FEBRUARY 4, 11188; AND THAT THE AREA QFTHE SURVEYED PROPERlY IS 160,570 SQUARE FEET (3.<457 ACRES), MORE OR LESS. FOR PUR - . E' FYING EASEMENTS, RESERVATIONS AND PRIVATE RESTRICTIONS OF EVI~ED AND REUED ON LAND l1TlE GUARANTEE COMPANY'S TIT . P0391431. . 03/01/99 14:47 TX/RX NO.3250 P.003 . Certificate of Completion AND / OR Compliance CITY OF WHEAT RIDGE 7500 W. 29TH A VENUE WHEA T RIDGE, COLORADO 80034 THIS CERTIFICATE VERlFlES THAT THE PROPERTY DESCRIBED BELOW, DOES COMPLY WITH THE WHEAT RIDGE BUILDING CODE, ZONING AND OTHER RELATED LAND USE AND DEVELOPMENT LA WS OF THE CITY OF WHEAT RIDGE FOR THE FOLLOWING PURPOSE: Permit Number 98-8382 Tenant Finish / Offices OWNER Colorado Santa Fe ADDRESS 4980 Kipl inq St.. #15B CONTRACTOR Colorado Santa Fe PROPERTY ADDRESS 4980 Kipl ing Street Unit 15B DA TE2-j2. 71 CHIEF BUILDING OFFICIAL i!tr'~ / ' ZONINGADMINISTRATO~ ; Date: c2 - /d. - 91 A Certificate of Occupancy or Completion has been requested for: ADDRESS: 49 j()' K LpJ il71 J}. =tJ: /:515 Purpose of Structure: J~ fl/J /l:f ~..A..~J; Building Department Approval: CPdc W! Z-/c-11 Remarks: Zoning Approval: /xll. '"" (/ 1fA-..-/ 'i'!lq! qq Remarks: Public Works Approval: . Remarks: Fire Marshall Approval: (If Applicable) Remarks: 4 4 APPROVED Subject to Field Inspections Wheat Ridge Building Dept. Date.!.!/}/.t1..~ :~~~~!'l~-=__...Plan Checker INSPECTIONS WILL NOT BE MADE UNLESS THIS CARD IS POSTED ON THE BUILDING SITE 24 HOURS NOTICE REQUIRED FOR INSPECTIONS WHEAT RIDGE, COLORADO 7500 WEST 29th AVENUE (303) 234-5933 INSPECTION RECORD :~:,~=!~~'ns 5\'~~~o~l~q~ I "" I ="''"''1 OWNERf' ~\o. ""V\ n+~ ~e. CONTRACTOR ~ rn t!... Q~ Of dO l!..-Y" SETBACI<S FROM PROPERTY LINES: NORTH SOUTH EAST WEST INSPECTOR MUST SIGN ALL SPACES PERTAINING TO THIS .IOR INSPECTION DATE INSPECTOR Footings Caissons Reinfprcing or Monolithic Weatherproofing POUR No CONCRETE UNTIL ABOVE HAS BEEN SIGNED r.oncrete !':I"b Flnnr' Electrical (Ground Work) Plumbing (Ground Work) Heating (Ground Work) ED Rough Electrical Rough Plumbing Air Test Gas Piping Rough Heating & Ventilation Framing Insulation (above must be signed prior to framing inspection) 0)( I 1/ (q Jq., J!;.c- Drywall nailing Rooling Refrigeration Electrical underground Electrical Plumbin Heatin & Ventilation Frame R.OW. & Drainage Fire Oepartment Parking & Landscaping OCCUPANCY NOT PERMITTED UNTIL CERTIFICATE OF OCCUPANCY IS ISSUED PROTECT THIS CARD FROM THE WEATHER D PARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number: 8382 BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE Date: 1/12/99 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 Property Owner: Property Address: 4980 KIPLING ST #15B Contractor License No.: 17232 Company: Colorado & Santa Fe Construction Co. Phone: 466-2500 Phone: 466-2500 OWNER CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT DATE Construction Value: Permit Fee: Plan Review Fee: Use Tax: Total: $9,250.00 $167.25 $108.72 $138.75 $414.72 I hereby rtify that the setback distances proposed by this permit application are accurate, and do n t violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenant , easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and a~ree to abide by all conditions printed on this applicatio ,and that I assume full responsibility for compliance with the Wheat Ridge Building Code (U. .C.) and all other applicable Wheat Ridge ordinances, for work under this permit. (OWNER (CONTRACTOR) SIGNED Use: Desc iption : Tenant remodel, build interior offices BUILDING DEPARTMENT USE ONLY SIC: Sq. Ft.: Approval: Zoning: Okay, need subcontractors license #'s if not Colo. Santa Fe Canst. Approval: Oc upancy : Stories: Walls: Roo!: Residential Units: Electri al License No : Comp ny: Plumbing License No : Company: Mechanical License No : Company: Expiration Date: Approval: Expiration Date: Approval: Expira on Date: Appro al : (1) (2) (3) his permit was issued in accordance with the provisions set forth in yopur application and is subject to the laws of the State of Colorado and to the Zoning egulations and Buildin~ Code of Wheat Ridge, Colorado or any other applicable ordinances of the City. his permit shall expire If (A) the work authorized is not commenced within sixty (60) days from issue date or (B) the building authorized is suspended or bandoned for a period of 120 days. this permit expires, a new permit may be acquired for a fee of one-half the amount normally required. provided no changes have been or will be made in the riginal plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment xceeds one (1) year, full fees shall be paid for a new permit. o work of any manner shalt be done that will change the natural flow of water causing a drainage problem. ontractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before roceediing with successive phases of thel.Ob. he issu~nce perm;,.o r.the approval 0 drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation of the provisions f the buildi q~~ other ordinance, law, rule or regulation. ,. (' //(1 ...../ 'I'~ hie! Building Inspector THIS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION (4) (5) (6) DEPARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number: 8410 BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE Date: 1/18/99 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 Property Owner: Property Address: 4980 KIPLING ST #15B Contractor License No.. 17178 Company: Good Plumbing Service Co., Inc. OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Phone: 466-2500 Phone: 455 4307 (OWNER)(CONTRACTOR) SIGNED DATE Total: $600.00 $26.55 $0.00 $9.00 $35.55 Construction Value: Permit Fee: Plan Review Fee: Use Tax: I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application, and that I assume full responsibility for compliance with the Wheat Ridge Building Code (U.B.C.) and all other applicable Wheat Ridge ordinances, for work under this permit. Use: Description: Replacing break room sink and disposal with new BUILDING DEPARTMENT USE ONLY SIC: Sq. Fl. Approval: Zoning: ---- Approval: Approval: Occupancy: Walls: Roof: Stories: Residential Units: Electrical License No : Company: Plumbing License No : Company: Mechanical License No : Company: Expiration Date: Approval: Expiration Date: Approval: Expiration Date: Approval: (1) (2) (3) This permit was issued in accordance with the provisions set forth in yopur application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Code of \Nheat Ridge, Colorado or any other applicable ordinances of the City. This permit shall expire if (A) the work authorized is not commenced within sixty (60) days from issue date or (6) the building authorized is suspended or abandoned for a period of 120 days. If this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. No work of any manner shall be done that will change the natural flow of water causing a drainage problem. Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceediing with successive phases of the job. ihe issuance of a permit or the approval of drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation of the provisions of the building codes or any other ordinance, law, rule or regulation. (4) (5) (6) ~~-r C BUildi~9)PS~~LU' THIS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION DEPARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number: BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE Date: 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 Property Owner :(~ 0 L D l" /-/ /) u y-huTH /-::::- <:C_ Property Address: tj f Y ,) M ,r{j.-LC- ;:1< /'58 r ContractorLlcenseNo.: ~7'l70::.->tna:71ey (7f7g-{7'!Y Company: (:J--ooL:> I'LI.I /71 r.;/ /U(~ Phone: '1'00 --~ ,,-ZJJ)) Phone: "/SS-Y3CJ7. OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Construction Value: 4f (, c;XJ _ .->-0 Permit Fee: Use Tax: I hereby certify thltlhe setblck dlstlnces proposed by this pennH Ippllcatlon Ire Iccurlte, Ind do nol vlollte Ippllcable ordinances, rules or regulltions of the City of Wheat Ridge or covenants, easements or restrictions of record; that 811 measurements shown, and allegations made Ire Iccurate: thlt I hIve read Ind IQree to Ibide by III conditions printed on this Ippllcatlon, and that I I..ume full responSIbility I pllance' the Wh I Ridge Building Code (U.B.C.) Ind III other Ippllcable Wheat A g rdlna s work er this pennl!. (OWNER)(CONTRACTOR) SIGNEO Total: $0.00. Use: Description: .-? ."'C' .1 /l /J-;::~:.u /::i-Lcl-+!- ;COO'on .i- )) I !: .1"0 S Fl f.-- ....: //Uic BUILDING DEPARTMENT USE ONLY '~l'llIl._i\!!!)lill\UA1tl SIC: Sq.Fl: Approval: Zoning: .:I!,I' 'J\c 'u!lll.Jl~ Approval: . I . (:: \ . i};; \.!.1!l.!illjJ;lll~ Approval : Occupancy : Walls: Roof: Stories: Residential Units: Electrical License No : Company: Plumbing License No: /7/ 7:/ Mechanical License No ; Company: GOOD PL{,ll11e/,uc, Company: Expiration Date: Approval : Expiration Date: Approval : 1--/- / (, . .-/9 Expiration Date: Approval: (1) Thl. permt ....luued In ao:ordlnce wtth the provI.lon. .et foI1h In YOIM Ipplleation Ind I. .ubIed to the laws 01 the Stole 01 CoIorIdo and to the Zoning Regulations and BuRdin; Code of 'Nheat Rickie, CoIorIdo Of .ny other .pp1ic:abte ordinances of the City. (2) Thls porm/t shel expire W (A) !he work I_OIl Is not CO<Mlenad wtthin sOrIy (60) dlY' from Issuo dale or (e) the building _OIl Is .usponded or lbondoned lor I period or 120 day.. (3) If !his penN! """"es, I new porm/t may be ocqulred lor I I.. or one-tuiW!he I.....nl nomuol1y requlred. plOOtded no chonge. hi.. been or wItI be mode In !he original plans and lpedfaUons and .ny luspenslon or ,bandonmenl hIlS not exceeded one (1) yelt. If changes Ire made or If suspension Of 1~IdoI:.ment exceeds one (1) ye.r, fun fees shan be p111d for. new permit. l'5) No WOft of any maMer shaft be done that will change the natural tIow of waler causing a drainage problem. t Conlnldor shin notify the Building 'nspector twenty-four (24) hours In advance kw.n InspecUons Ind ,hal receive written approval on Inspection Clnf before proeeedifna wtth successtve phases of the Job. (8) lhe issuance of. pennit Of' the approval or drawings and speciflcations shan not be construed to be . pennIt for. nor In approval of. any.....tIon of the ptOYfslons of the but1dJng codes or Iny other ordinance. law, ruJe or regulation. Chief Building Inspector For Mayor . THIS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION BUILDING DEPARTMENT (303) 235-2855 CITY OF WHEAT RIDGE * * Correction Notice Job Located at 1/ f (j ~k;~),.,...,'1 / I I have this day inspected this structure and these premises and have found the following violations of City and/or State laws gov- erning same: v;"'h rr/r I,) I'l/qed --) ~ rel/"}7/~, L' '" /'V-J ~} f;"i/rr J)!f'P t,adr;.;w-f' r<:>rV M a/I ,--t}OO/i> ~) f~l&/r~~;n7h:L::~ ~/V";J';;v:rn ;;,~~ _ '/Joo,-~ Ie> r->PJY1IJJ'7 Ci.1/t'"'it".Lrr--l dv"'i/'l.,. nU~:V1~('; hl.J.--~ I -ex-kvsf ~/? I~ h'aJl,nu..... kuc /;-/J vn do-o..-- 10 e/cc.h"":", You are hereby notified to correct the foregoing violations. When corrections have been made, call for inspection. Date 1/-/2-C;V ~~ - or lor Building Dept. DO NOT REMOVE THIS TAG FORM WR6-22 N' D PARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number: 8079 ~ - BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE Date: 11/2/98 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 Property Owner: Property Address: 4980 KIPLING ST #8 & #9 Contractor License No.: 17232 Company: Colorado & Santa Fe Construction Co. OWNER CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby rtify that the setback distances proposed by this permit application are accurate, and do no violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenant , easements or restrictions of record; that all measurements shown, and allegations made are ccurate; that I have read and agree to abide by all conditions printed on this applicatio ,and that I assume full responsibility for compliance with the Wheat Ridge Building Code (U, .C.) and all other applicable Wheat Ridge ordinances, for work under this permit. (OWNER CONTRACTOR) SIGNED DATE Desc iption : Demo walls and install door, open up area for exit Phone: 466-2500 Phone: 466-2500 Construction Value: Permit Fee: Plan Review Fee: Use Tax: $1,000.00 $35.75 $0.00 $15.00 $50.75 Total: Use: ;t-; v 1:;- J(/i-clfT~~ BUILDING DEPARTMENT USE ONLY his permit was Issued in accordance with the provisions set forth in yopur application and is subject to the laws of the State of Colorado and to the Zoning egulations and Building Code of Wheat Ridge, Colorado or any other applicable ordinances of the City. is permit shall expire if (A) the work authorized is not commenced within sixty (60) days from issue date or (8) the building authorized is suspended or bandoned for a period of 120 day's. f this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the riginal plans and specifications and any suspension or aban.donment has not exceeded one (1) year. If changes are made or if suspension or abandonment ceeds one (1) year, full fees shall be paid for a new pennit o work of any manner shall be done that will change the natural flow of water causing a drainage problem. ontractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before edilng with successive phases of thel.ob. he issuance of a permit or the approval 0 drawings and specifications shall not be construed to be a pennit for, nor an approval of, any violation of the provisions fthe bUilding codes or any other ordinance, law, rule or regulation. ci~ Hl7cJ AN 11-13-77 {}rn - {{.I:: o.k. 'ferfsl$p Approval: Oc upancy : Walls: Roof: Stories: Electri al License No: '3?> 35 L Plumbing License No : Comp ny: C o!orA.lo ~ S UVllftX:ompany: Expira ion Date: ~- Zi>- 9'f Appro al : Expiration Date: Approval: (1) (2) (3) (4) (5) (6) SIC: Sq. Ft.: cIP QroJf Residential Units: Mechanical License No : Company: Expiration Date: Approval : hief uilding Ins THIS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION ~ "'.,-r l . J) PARTMENT OF PLANNING AND DEVELOPMENT -~BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 Building Permit Number: Date: 8079 11/2/98 Property Owner: Property Address: 4980 KIPLING ST #8 & #9 Contractor License No. : 17232 Company: Colorado & Santa Fe Construction Co. Phone: 466-2500 Phone: 466-2500 OWNE CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby rtify that the setback distances proposed by this permit application are accurate, and do n violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenant ,easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this applicatio ,and that I assume full responsibility, fa complianceffiith)he Wheat Ridge Building Code (U. .C.) and all other applicable Wh;..at1;li e ordtnan9'o/. :~;work under this pe'l"it. (OWNER (CONTRACTOR) SIGNED .' / / )//~<'_DATE / / l"5:I9Il r/ I / Desc iption : Demo walls and install door, open up area for exit Construction Value: Permit Fee: Plan Review Fee: Use Tax: $1,000.00 $35.75 $0.00 $15.00 $50.75 / Total: Use: BUILDING DEPARTMENT USE ONLY SIC: Sq. Fl. Roof: Residential Units: Stories: Electri I License No : Comp ny: Plumbing License No : Company: Mechanical License No : Company: Expira on Date: Appro al : Expiration Date: Approval: Expiration Date: Approval : (1) (2) (3) is pennit was issued in accordance with the provisions set forth in yopur application and is subject to the laws of the State of Colorado and to the Zoning egulations and Building Code of Wheat Ridge, Colorado or any other applicable ordinances of the City. is permit shall expire if (A) the work authorized is not commenced within sixty (60) days from issue date or (B) the building authorized is suspended or bandoned for a period of 120 days. this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the riginal plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment xceeds one (1) year, full fees shall be paid for a new pennit. o work of any manner shall be done that will change the natural flow of water causing a drainage problem. ontractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before roceediing with successive phases of the/.ob. e issuance of a pennit or the approval 0 drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation of the provisions f the building codes any other ordinance, law, rule or regulation. (4) (5) (5) hief Building lector THIS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION DEPARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number: - BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE Date: IDI7. ~)q~ 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 PropertyOwner:Co(Md~ ~ ~~c._.(o..,.-... L-c~^d CD Property Address: "7 't gO \ L, . f' \ , . u... '::> fI= 6- <~ '1 Contractor License No. : I 7 -z -) z- 4~b <?~O,:, Phone: . . Company: C ,,(", v eo) '" "', 1 ~~....,-!~. C'-r VIA() C~'(.'\_. s.-Iv't.>(:-t.~,;.~hone: '-f(..6# '2:; r.:).c) ^ ---c OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Construction Value: lObe> Permit Fee: 55. 75 Use Tax: j 5, DD Total: 0,15$0.00 I hereby certify that the setback. distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants. easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and a9.ree to abide by all conditions printed on this application, and that I assume full responslbili r compliance with th~ Wheat Ridge Building Code (U.B.C.) and all other applicable Wh' i <~rdinances:.,~~r..,wo~ under this pe~it. ~ (DWNER)(CDNTRACTDR) SIGNED /V~ ,/ '-cATE Il 'I. Z. 'Y ;If -- Dn(, S\'\E' 0,- Description: r.\ _ .', "'-I!:> W C> \ \ <;, \' '^ ).-e c..\ \, c~C'>O r Use: C/ BUILDING DEPARTMENT USE ONLY l!;~OJmtomtiJ&~ Approval: Zoning: ID!]R1lJ1mommentl>.t Approval : c.[m(l:1Jo'V,llo(SJl,5_Q.ll)l!!ertts1 Approval : Occupancy: Walls: Roof: Stories: ,t;j;.YsCi. Ft: ~ ~~\ Rl,.-..'--' ""\...~._I '. 'f.;, ..'-~. " .-"I;'l _. '~.- '.,-., ';' ( n"",- ", - ,,',,; 1~ Electrical License No : Company: Plumbing License No : Company: Mechanical License No : Company: Expiration Date: Approval : Expiration Date: Approval: Expiration Date: Approval: (1) This permtt was Issued In accordance with the provisions set forth In yopur application and Is subjed.to the laws of the State of Colorado and to the Zoning Regulations and BuHdirl9. Cod~ of v.Jheat Rid~e, COlorado or any other applicable oroinances of the City. (2) This pelT1lit shall expire If (A) the wofk authortzed Is not commenced within sixty (60) days from Issue date or (B) the building authorized is suspended Of abandoned for a period of 120 days. . (3) If this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made In the original plans and specifications and any luspension Of abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new pennil (4) No work of any manner shall be done that will change the natural flow of water causing a drainage problem. (5) Contlactor shall notify the Building Inspector twenty-four (24).hours in advance for all inspections and shall receive written approval on Inspection card before ~~ proceedilng with successive phases ot 1heIICob. '(6) The issuance of a permit or the approval 0 drawings and specifications shall not be construed 10 be a permit for, not an approval or, any violation of the provisions of the bui~ es or any other ordinance, law, rule or regulation. For Mayor THIS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-593324 HOURS PRIOR TO INSPECTION 10/30/98 FRI 14:53 FAX ~001 -' -~ October 30. 1998 Mr. Bob Gasper Building Inspection City of Wheatridge Re: N Scale Supply Independence Shopping Center 4980 Kipling Street, Suites 8 & 9 Wheatridge, CO Dear Mr. Gasper: The above tenant finish involves two separate areas. The north side of the unit, Unit 8, has approximately 600 SF of retail area (mail order sales), or a maximum of 20 occupants. The south side, Unit 9, has approximately 1,200 SF of retail area, or 40 occupants. Each side has its own exit out the front of the store, meeting the exit requirement for less than 50 occupants. The fact that there is a doorway joining the two rooms should not affect the independent exiting calculation for the two rooms. No required exit will pass through the storage room. Please respond as quickly as possible so that we may avoid any unnecessary delays. I will be glad to discuss this issue with you if you have any further concerns. Sincerely, ItLy(~ H. Lee Hardies, AlA Architect 2400 Industrial lane. Unit 1520 Broomfield. Colorado80020 (303)466-2500 D PARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number: 4397 E')JILOfNG INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE Date: 12/26/96 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 Property Owner: tN' %cJ Property Address: "i!IIQ KIPLING ST #1 0 & 11 Contractor License No.: 18122 Company: Mark's Electric Phone : Phone: 425 0753 OWNE CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby rtify that the setback distances proposed by this permit application are accurate, and do n violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covensn ,easements Of restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all condItions printed on this applicatio ,and that I assume full responsibility for compliance with the Wheat Ridge Building Code (U. .C.) and all other applicable Wheat Ridge ordinances, for work under this permit. Construction Value: Permit Fee: Plan Review Fee: Use Tax: $800.00 $45.00 $0.00 $9.60 (OWNER (CONTRACTOR) SIGNED DATE Total: $54.60 Desc plion : TENNANT WIRE BUILDING DEPARTMENT USE ONLY SIC: Sq. Ft.: ~::] Rool: Stories: Residential Units: Plumbing License No : Company: Mechanical License No : Company: Expiral on Dale : Appro I: . Expiration Date: Approval: II Expiration Date: Approval: II (4) (5) (6) Is permit was issued in accordance with the provisions set forth in yopur application and is subject to the laws of the State of Colorado and to the Zoning egulations and Building Code of Wheat Rid~e, Colorado or any other applicable ordinances of the City. his permit shall expire if (A) the worn authonzed is not commenced within sixty (BO) days from issue date or (8) the building authorized is suspended Of bandoned for a period of 120 day'8. this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the riginal plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment xceeds one (1) year, full fees shall be paid for a new permit. o work of any manner shall be done that will change the natural flow of water causing a drainage problem. ontraetor II notify the Building Insreetor twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before roceedii th successive phases 0 the job. he iss~ of a mit or the approval of drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation of the provisions f the QUi in or any other ordinance, law, rule or regulation. ~. (1) (2) (3) I Building Inspector THIS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION DEPARTMENT OF PLANNING AND DEVELOPMENT BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215. Building Permit Number: Date: Property Owner: Property Address: Contractor License No. : . '" 1f9ao 1<"fC'P5 71/011 1'8 1/-2- Company: YhI9'f.JL's EL<;;!(.+ Phone: Phone: (p...~ 07~3 Construction Value.f'l" 800, ~ Permit Fee: Plan Review Fee: Use Tax: OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application, and that I assume full responsibility for compliance with the Wheat Ridge Building Code (U.B.C.) and all other applicable Wheat Ridge ordinances, for work under this permit. (OWNER)(CONTRACTOR) SIGNED m (~ 'Y\.1~'\....--' DATE 11';;' ~ 9{., Description: Total: ()J % -fJ.-A",.'i O-.t-e.-c.- BUILDING DEPARTMENT USE ONLY Zcmlng~Qmm8nt1'3 Approval: Zoning: BffiRi)!![ll!OOpmm:en.tlr.I Approval: RommwvlH'lam;;PI1!IJ:!!!J!Q1il Approval: Occupancy: Walls: SIC: Sq. Ft.: Roof: Stories: Residential Units: Electrical License No : Company: Y\1 A~<"S f (.eG+: Plumbing License No : Company: Mechanical License No : Company: '" .lOi.l.: I "..J Expiration Date: Approval : . Expiration Date: Approval: Expiration Date: Approval: III '" ~-"I!f" . l- . . ii - . I [j. . " !~l (6) This permit was issued in accordance with the provisions set forth in yopur application and is subject to the laws of the State of Colorado and to the Zoning RegUlations and Buildin9. Code of lNheat Ridge, Colorado or any other applicable ordinances of the City. This permit shall expire If (A) the work authonzed is not commenced within sixty (60) days from issue date or (8) the building authorized is suspended or abandoned for a period of 120 days. If this permit expires. a new permit may be acquired for a fee of one-half the amount normally required. provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. No work of any manner shall be done that will change the natural flow of water causing a drainage problem. Contractor II notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceedii ith successive phases of the/'ob. The iss n of a p rmit or the ap roval 0 drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation of the provisions ofthebUil ng_cod .0ra'}Jothe rdin ,I w,ruleorregulation. \'-C Chi Building Inspector For Mayor HIS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION (1) (2) (3) li' DEPARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number: 4389 ,. # BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE Date: 12/23/96 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 Property Owner: Property Address: 4980 KIPLING ST #10 & 11 Contractor License No. : 17772 Company: Culligan Construction Co., Inc. Phone: 431-4040 Phone: 420 5544 OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Construction Value: Permit Fee: Plan Review Fee: Use Tax: $3,580.00 $88.00 $0.00 $42.96 I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read an to abide by all conditions printed on this application, and that I assume full r onslbility com ance with t Wheat R ge uilding Code (U.B.C.) and all other applic le_Wh at R or I cas, for or JI)Ae. it. <Jl. I . Ar DATEZ/",? 7< ! / RING PARTITION WALLS PER DRAWING Description: Total: $130.96 (OWNER)(CONTRACTOR) SIGNED AA- ctl\.l\b Sq. Ft. : BUILDING DEPARTMENT USE ONLY SIC: Approval : Zoning: FIRE PROTECTION BY FIRE DEPARTMENT Approval: J E 12/20/96 Approval : Occupancy: Walls: Roof: Stories: Residential Units: Plumbing License No : Company: Mechanical License No : Company: Electrical License No : Company: Expiration Date : Approval: . Expiration Date: Approval : .~ Expiration Date: Approval: .IE' ,__ (4) (5) (6) This permit was issued in accordance with the provisions set forth in yopur application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Code of Wheat Ridge, Colorado or any other applicable ordinances of the City. This permit shall expire if (A) the work authorized is not commenced within sixty (60) days from Issue date or (6) the building authorized is suspended or abandoned for a period of 120 days. 11 this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. No work of any manner shall be done that will change the natural flow of water causing a drainage problem. Contractor shall notify the Building lnsfector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceecliing with successive phases 0 the job. The Issuance of a permit or the approval of drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation of the provisions of the bu in codes or any other rdinance, law, rule or regulation. . ~) { (1) (2) (3) Building Inspector IS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION ~)(I( <if"!>" A-FF ....'0' fbwu- . Sfn ps ~ ~. .5' e R \II CI2 CoutJ-le., .3Gx"IZ" ArW Jt:f' A Iht fl.mv 11-J.fILL OLD DooR - ~l Rcc.Jt. s , , . <;/-0 t+ff IcJ t> CxISt: De",,'ISI Nt:, LJALL IO'-(!) " AFF t,,/!:t DzMI~INfo WALL /'IEkJ ,pAUlS. 3~ ~""'L ~t~s wlfft )Z" ./J ''/ wA/..t.... ~~ -'tff 1'2. '0 o~~v fbl.l ve RI'iY LOC.. IO~' /1.:0 AFF -/ 1\1\\ T MDR - TE.k COM Pu fE R~ L..j'l~O 1",PlIt-:lL:. sf. StAlt 10"11 WI-la.A1~1 DbE., CD, /2 - 11.,,- q~ / 9:..M.e. ~"::: I' ~~ " / I DEPARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number: I / '} ctV BUILDING INSPECTION DIVISION - 235-2855 'f' CITY OF WHEAT RIDGE Date: 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 Properly Owner: jVl 6f - ie k l.'-~ ^^'etA I-e.,...~ s . Properly Address: 'ferae ~Ll N (p "",t .5j/1.lt 16~ II Contractor License No.: /777 2.~ Company: C.LALL.1 GIl-N C;ONSr- CO ll\l( 1507 Gr!>' Dl1teoJ ,Me .., <;:;OOd't.- OWNE ICONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I herebY~rtify that the setback distances proposed by this permit application are accurate, and do n t violate applicable ordinances, rules or regulations of the CIty of Wheat Ridge or covenan S, easements or restrictions of record; that all measurements shown, and allegations made af accurate; that I have read and agree to abide by all conditions printed on this applicati n, and that I assume full resp t r co pllance with the Wheat RIdge BUIlding Code (U B.C.) and all other applicabl W eat dge nanees, for work under thiS permit. (OWNE+(CONTRACTOR) SIGNED /,,? ~~ DATE I? //1 It? , Desc~iption : r!: - I)) !lM7l lx.a.u; Phone: c;5/ - '-/6'16 Phone: if 2-D .. 5 -Sl/L! Construction Value: . S' '., I', ~ Permit Fee: Plan Review Fee: Use Tax: is permit was issued in accordance with the provisions set forth in yopur application and is subject to the laws of the State of Colorado and to the Zoning egulations and Buildin~ Code of Wheat RidSle, Colorado or any other applicable ordinances of the City. is permit shaH expire If (A) the work authonzed is not commenced within sixty (60) days from issue date or (B) the building authorized is suspended or bandoned for a period of 120 days. I this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the riginal plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment xceeds one (1) year, full fees shall be paid for a new permit. o work of any manner shall be done that will change the natural flow of water causing a drainage problem. ontractor II notify the Building Inspector twenty.four (24) hours in advance for all inspections and shall receive written approval on inspection card before roceedi' ZJf.th su essive phases of the!Ob. he is an of a rmit or the pprov 10 drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation of the provisions f th uil s or ~t r 0 . a aw, rule or regulation. I 'tA BUILDING DEPARTMENT USE ONLY , zojl\1r&om.~ ~: Approval: i Zoning: BliI I e IS. Approval: ,.,. rl No. Proi6-e/11/>- f3'i Fir/.- Dc-p Approval: Oc upancy : Walls: Roof: Stories: Electri al License No : Comp ny: i Plumbing License No : Company: Expiration Date: Approval: . II -. ..~I_I.. I- . -. - 'W.L' I (') (2) (3) (4) (5) (6) Total: wtLM riUk/J/14 SIC: Sq. Ft.: Residential Units: MeChanical License No : Company: Expiration Date: Approval: . 1IEI8lrI'.R1!IID1'lRI For Mayor HIS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION I [, I , ~. I ~1 BUILDING DEPARTMENT , r l r ~ f l (303) 235-2855 CITY OF WHEAT RIDGE * * Correction Notice t t f Job Located at &!crto f/. I f'L'A'c:., f #'tz HcPdh"oS , \'// / I (,U) '''''17 "'-..II "I-~ . , , p(J'~ r~" ,f/ 1'-101 p,....n' II", e j::' C NOt' /lPI) You are hereby notified to correct the foregoing violations. When corrections have been made, call for inspection. Date 7)- '::10 J -;~ . ,/.. .l" " DO NOT REMOVE THIS TAG Inspector lor Building Dspt. FORM WR8-22 ,..c_ _.~_.__..",..__ u_ -~-_._- ~"_._. ---- -'"--_.~~,",~~~...........~.. . _.._._~-_..~,._- <.- .-.. DEPARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number: 3328 BUILDING INSPECTION DIVISION. 235-2855 CITY OF WHEAT RIDGE Date: 6/24/96 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 Property Owner: Property Address: 4980 KIPLING ST #8 Contractor License No.: 18929 Company: Grand Electric Phone: 398-9001 Phone: 6989001 OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Construction Value: Permit Fee: Plan Review Fee: Use Tax: (OWNER)(CONTRACTOR) SIGNED DATE Total: $1,500.00 $45.00 $0.00 $18.00 $63.00 I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and 8!;lree to abide by all conditions printed on this application, and that I assume full responsibility for compliance with the Wheat Ridge Building Code (U.B.C.) and all other applicable Wheat Ridge ordinances, for work under this permit. Description: ADD ONE 2X4 LIGHT, RELOCATE 1 SWITCH ADD 12 DUPLEX RECEPTACLES AND DATA WIREING BUILDING DEPARTMENT USE ONLY SIC: Sq. Ft. : Approval: Occupancy: Walls: Roof: Stories: Residential Units: Electrical License No : Company: Plumbing License No : Company: Mechanical License No : Company: Expiration Date: Approval: II Expiration Date: Approval: Expiration Date: Approval: . II This permit was issued in accordance with the provisions set forth in yopur application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Buildin~ Code of Wheat Ridge, Colorado or any other applicable ordinances of the City. This permit shall expire If (A) the war\< authorized is not commenced within sixty (60) days from issue date or (8) the building authorized is suspended or abandoned for a period of 120 days. If this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no Changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. No work of any manner shall be done that will change the natural flow of water causing a drainage problem. Contractor s tify the Building Inspector twenty.four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceediin ith uccessive phases of the job. The issu ce 0 pennlt or the approval of drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation of the provisions ofthe b i1ding es 0 ny <=-z:e. law, ,ule orregulation. i1ding Inspector T IS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION (1) (2) (3) ~tl (6) his permit was issued in accordance with the provisions set forth in yopur application and is subject to the laws of the State of Colorado and to the Zoning egulations and Building Code of Wheat Ridge, Colorado or any other applicable ordinances of the City. is permit shall expire if (A) the work authorized is not commenced within sixty (60) days from issue date or (8) the building authorized is suspended or bandoned for a period of 120 days, this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been orwill be made :n the riginal plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment xceeds one (1) year, full fees shall be paid for a new permit. o work of any manner shall be done that will change the natural flow of water causing a drainage problem. ontractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before roceediing with successive phases of the job. e issuance of a permit or the approval of drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation of the provisions fthe buildin codes or any other on;llnance, law, rule or regulation. / 7/1/(, , c.,,,- 0 (~-~.C'v 1, G/L,- lef Building Inspector THIS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION ~ D PARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number: BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE Date: 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 Property Owner: Property Address: 4980 KI PLI NG ST #8 Contractor License No.: 18929 Company: Grand Electric Phone: 398-9001 Phone: 6989001 OWNE ICONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Construction Value: Permit Fee: Plan Review Fee: Use Tax: I hereby rtify that the setback distances proposed by this permit application are accurate, and do n t violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenant ,easements or restrictions of record; that all measurements shown, and allegations made ar accurate; that I have read and agree to abide by all conditions printed on this applicati n, and that I assume full responsibility for compliance with the Wheat Ridge Building Code (U. .C.) and all other applicable Wheat Ridge ordinances, for work under this permit. (OWNE (CONTRACTOR) SIGNED DATE Total: ~.J';r- Desc iption : ADD ONE 2X4 LIGHT, RELOCATE 1 SWITCH ADD 12 DUPLEX RECEPTACLES BUILDING DEPARTMENT USE ONLY SIC: Sq. Ft.: \ Approval: Oc upancy: Roof: Stories: Residential Units: Walls: ~ Electri al License No : Comp ny: Plumbing License No : Company: Mechanical License No : Company: Expira on Date: Appro al : Expiration Date: Approval : . Expiration Date: Approval: . . (1) (2) (3) (4) (5) (6) $1,500.00 $45.00 $0.00 $18,00 $63.00 City of Wheat ridge Permit Department As tenant of 4980 Kipling, suite 8, I am aware that currently one electrical panel is selVicing suite 8 and 9. According to our lease this only temporary as of August I, 1996 I will be taking possession of suite 9 as is. G. rand .slec~ll be installing the telephone cable at no cost. The final termination of all telephone and dara lines . fbe done as we move in due to our current need and use of /equipment. , Sincerely, [; PARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number: 3328 BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE Date: 6/24/96 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 Property Owner: Property Address: 4980 KIPLING ST #8 Contractor License No.: 18929 Company: Grand Electric Phone: 398-9001 Phone: 6989001 OWNER CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT (OWNER (CONTRACTOR) SIGNED DATE 2'/T"~' Total: $1,500.00 $45.00 $0.00 $18.00 $63.00 Construction Value: Permit Fee: Plan Review Fee: Use Tax: I hereby rtify that the setback distances proposed by this permit application are accurate, and do n t violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenant, easements or restrictions of record: that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this applicatio ,and that I assume full responsibility for campI' nee with the Wheat Ridge Building Code (U. ,C.) and all other applicable Wheat Ridge . ances, for work under this permit. Desc ption : ADD ONE 2X4 LIGHT, RELOCATE 1 SWITCH ADD 12 DUPLEX RECEPTACLES BUILDING DEPARTMENT USE ONLY SIC: Sq. Ft.: Approval: Zoning: Approval: Oc upancy : Walls: Roof: Stories: Residential Units: Electri Comp I License No : y: Plumbing License No : Company: Mechanical License No : Company: Expirat on Date: Approv I: . Expiration Date: Approval: .~ Expiration Date: Approval: . his permit was issued in accordance with the provisions set forth in yopur application and is subject to the laws of the State of Colorado and to the Zoning egulations and Building Code of Wheat Ridge, Colorado or any other applicable ordinances of the City. his permit shall expire if (A) the work authorized is not commenced within sixty (60) days from issue date or (B) the building authorized is suspended or bandoned for a period of 120 days. I this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the riginal plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment xceeds one (1) year, full fees shall be paid for a new permit. o work of any manner shall be done that will change the natural flow of water causing a drainage problem. ontractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before roceediing with successive phases of the job. he issuance of a permit or the approval of drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation of the provisions 'the ildin codes oeny other/!dinan~,. law. rule or regulation. / ..6 O~~),A / C uilding Inspector THIS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-593324 HOURS PRIOR TO INSPECTION (1) (2) (3) (4) (5) (6) DEPARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number: BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE Date: 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 Property Owner: Property Address: Contractor License No. : Company: 'I r~O f(,,;?/'''I /r.f' ;l Id> .2 {OMj Efecfr.'C Phone: Phone: r; r p- fti't7/ OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Construction Value: /5(/ (/ . rJ (l Permit Fee: Plan Review Fee: Use Tax: I hereby certify that the setback distances proposed by this pennit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application, and that I assume full responsibility for campI' nee with the Wheat Ridge Building Code (U.8.C.) and all other applicable Wheat Ri e . ances, for work under this permit. (OWNER)(CONTRACTOR) SIGNED DATE 6-,) 't'-1't Total: Description: ,q,pp /-.:zX't' L.;'':r ,; If'C&c"'~( /Si-' /?RP /.2 R""'/<")< Rcu.......;.~t,. BUILDING DEPARTMENT USE ONLY ~of!i.ilIl~9m!fj.!"nU'~ Approval: Zoning: !:!!!i1qiQlj~9)ij1!!ie.ri~ Approval: ~ijbliGl~q1'KS1(:i:lmmej1ts:] Approval: Occupancy: Walls: SIC: Sq. Ft.: Roof: Stories: Residential Units: Electrical License No : ;;I. t,.P ) Company: c;,."'A" t:-/(C "": '( 711 ( W 1-1'';U'./~ ,P/' Expiration Date: Approval: ~ Iil~lliif~~i@OC~ Plumbing License No : Company: Mechanical License No : Company: Expiration Date: Approval: ~ fii~laifS':~ilillilrell_ Expiration Date: Approval: 11 m".lailS'~eqijjr'ell~ (4) (5) (6) This permit was issued in accordance with the provisions set forth in yopur application and is subject to the laws of the Stale of Colorado and to the Zoning Regulations and Building Code of lNheat Ridge, Colorado or any other applicable ordinances of the City. This permit shall expire if (A) the work authorized is nol commenced within sixty (60) days from issue date or (8) the building authorized is suspended or abandoned for a period of 120 days. If this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. No work of any manner shall be done that will change the natural flow of water causing a drainage problem. Contractor shall notify the Building Inspector twenty-four (24) hOurs in advance for all inspections and shall receive written approval on inspection card before proceedilng WIth successive phases of the Job. The issuance of a permit or the approval of drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation of the provisions of the building codes or any other ordmance, law, rule or regulation. (1) (2) (3) Chief Building Inspector For Mayor THIS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION '. D PARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number: 3307 BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE Date: 6/20/96 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 Property Owner: INDEPENDENCE SQUARE L TD LIABILITY COMPANY Property Address: 4980 KIPLING ST Contractor License No. : 18926 Company: D FRANKLIN ENT. Phone: 466-3008 Phone: 412-4316 OWNE ICONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT (OWNE )(CONTRACTOR) SIGNED DATE Total: $3,000.00 $54.00 $0.00 $36.00 $90.00 Construction Value: Permit Fee: Plan Review Fee: Use Tax: I hereby ertify that the setback distances proposed by this permit application are accurate, and do n t violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenan ,easements or restrictions of record; that all measurements shown, and allegations made af accurate; that I have read and agree to abide by all conditions printed on this applicati n, and that I assume full responsibility for compliance with the Wheat Ridge Building Code (U. .C.) and all other applicable Wheat Ridge ordinances, for work under this permit. Desc iption : INTERIOR WALL FRAMING IN UNIT #8 BUILDING DEPARTMENT USE ONLY SIC: Sq. Ft. _rI Approval: "I Approval: Oc upancy : Walls: Root: Stories: ResidfL~~J1 Electri al License No : Comp ny: Plumbing License No : Company: Mechanical License No : Company: Expirat on Date: Appro I: . Expiration Date: Approval: .~I- Expiration Date: Approval: . (4) (5) (6) his permit was issued in accordance with the provisions set forth in yopur application and is subject to the laws of the State of Colorado and to the Zoning egulations and Building Code of Wheat Ridge, Colorado or any other applicable ordinances of the City. his permit shall expire if (A) the work authorized is not commenced within sixty (60) days from issue date or (B) the building authorized is suspended or bandoned fOf a period of 120 days. I this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the riginal plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment xceeds one (1) year, full fees shall be paid for a new permit. o wo ny manner shall be done that will change the natural flow of water causing a drainage problem. ontr or hall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspectlon card before ro edii with successive phases of the/'ob. h issu of permit or the approval 0 drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation of the provisions f e b I de~inance, law. rule or regulation. (1) (2) (3) iet Building Inspector THIS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION DePARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number: BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE Date: 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 Property Owner: TrtJ.ePfnJe,r.c.e-1uare- Uc. Property Address: If1gt;' Kill, 1/ '? /.In. I f :;iff Contractor License No. : Company: Firt few ;tf"r7;41E Phone: ,Lf{b-"10tJf? Phone : ~-~-Pf(} ( OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Construction Value: Permit Fee: Plan Review Fee: Use Tax: f;&~6', 6'('~~ .3 COO .0<;) I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application, and that I assume full responsibility for compliance with the Wheat Ridge Building Code (U.B.C.) and all other applicable Wheat Ridge ordinan for w rk u,..nder this permit. ~DATE'/-/'146 L,fent;rr Ctl/1 tr-al#r;l'f /'....~nft ~I ~~ ,1&.:.- BUILDING DEPARTMENT USE ONLY (OWNER)(CONTRACTOR) SIGNED Description: !eJ'/?(11 t hi1 (S '1 Total: V~~-V(~~ ~6!li~:g:OlT!i'riijfjts;l Approval: Zoning: !:!.f!ill:llmr:j::ol'filTje1its~ Approval: P(jblii:~VVQtIr~gl:!!f1meritsl1 Approval: Occupancy: Walls: SIC: Sq. Ft.: Roof: Stories: Residential Units: Electrical License No : Company: Plumbing License No : Company: Mechanical License No : Company: Expiration Date: Approval: !2l !!plails:1ReiJilj[{Q_ Expiration Date: Approval: IIll\e1ill!,i;Rl[qliitl[d_ Expiration Date: Approval: ~ ~Plifri\l:~e:qli!reCl~ (4) (5) (6) This permit was issued in accordance with the provisions set forth in yopur application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Buildin5! Code of VVheat Ridge, Colorado or any other applicable ordinances of the City. This permit shall expire If (Al the work authorized is not commenced within sixty (60) days from issue date or (8) the building authorized is suspended or abandoned for a period of 120 days. If this permit expires, a new perrmt may be acquired for a fee of one-half the amount normally required. provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. No work. of any manner shall be done that will change the natural flow of water causing a drainage problem. Contractor shall notify the Building Inspector lwenty.four (24) hours in advance for an inspections and shall receive written approval on inspection card before proceediing wit uccessive phases of the job. The Issuance ~~r~or Ihe approval of drawings and speclficallons shall nol be conslrued 10 be a permll for, nor an approval of. any vlolallon of Ihe provisions of Ihe build; e~ ny 2zce. law. rule or regulallon. (1) (2) (3) Chief For Mayor THIS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION 4980 Kipling, unit Whea!ricj9~,..G() #8 80033 , ... , ;;; 1 b .. t- '" .. ~t-- ;;;: i- ... ... .., J- ... l-.. N , origmallayout 30'1 60' 20'1 All new electrical wiring to be provided by licensed contractor. Permit to be provided by electrical contractor. existing ceiling at 10' high, acoustical 2X4 grid with drop Has sufficient light fixtures. heating and air condition vents(all to stay as is). 30'1 ~ 60' 20'1 ~ g10i l<l electrical panel 0 g10~ , ~ ~ N r ~ b ... t- N ... ~t- ~ ... t-- ~ ... M J-- ~ ~ N , 30'1 door bell = future phone/fax line tv = active single phone line - - om - OFl Ofl OFl - =i - ~ - - DO - - 30'1 50'4 - gfi = computer dedicated outlets - - r N ... - - - 50'4 10' 10'3 10' ~ ~ ;... 20'3 10'3 ,~ -~l~ Ol '" N M ~ , , ~ ~ en ~ .' .. 'Gu~; f:nold . ........... ''l:i'466~3Cl08'' ........ ....UJJ6i19i96 (\) 1Cl:25 AM D2/2 Independence Square LLC 4980 Kipling Street Wheatridge, Colorado June 19,1996 To Whom It May Concern, First Select Mortgage has the permission of the Landlord to pull a permit in order to build some internal walls. Signed, Guy M. Arnold Agent for Landlord G' ~y Arnold "ll" 466-3008 11116/19/96 'D10:25AM Cl1/2 ~ FAX IN BRIEF TO: Bruce Gordon. First Select Mortgage Corp. FAX 458-6554 FROM: Guy Arnold PAGES (INCLUDING COVER) 2 Wednesday, June 19, 1996 "., '".. DEPARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number: 3292 'BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE Date: 6/19/96 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 Property Owner: INDEPENDENCE SQUARE L TD LIABILITY COMPANY Property Address: 4980 KI PLI NG ST Contractor License No.: 18823 Company: Apollo Sign Phone: Phone: 986 6667 OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Construction Value: Permit Fee: Plan Review Fee: Use Tax: I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application, and that I assume full responsibility for compliance with the Wheat Ridge Building Code (U.B.C.) and all other applicable Wheat R~rdinances, for work under this permit. (OWNER)(CONTRACTOR) SIGNED (;...-/ f:::r'~DATE Total: $600.00 $15.00 $0.00 $7.20 $22.20 Description: WALL SIGN BUILDING DEPARTMENT USE ONLY SIC: Sq. Fl. : 20 SQ. FT. MEETS SIGN REQUIREMENTS (ALLOWED 120 SQ. FT.) Approval: Approval: Occupancy: Walls: Roof: Stories: Residential Units: Electrical License No : Company: Plumbing License No : Company: Mechanical License No : Company: Expiration Date: Approval: ..-- Expiration Date: Approval: Expiration Date: Approval: . II This permit was issued in accordance with the provisions set forth in yopur application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Buildin~ Code of Wheat Ridge, Colorado or any other apphcable ordinances of the City. This permit shall expire If (A) the work authorized is not commenced within sixty (60) days from issue date or (B) the building authorized is suspended or abandoned for a period of 120 days. If this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. No work of any manner shall be done that will change the natural flow of water causing a drainage problem. Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceediing with successive phases of the job. The issuance of a permit or the approval of drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation of the provisions o he ~ ilding cod;}t~l;e.law, rule or regulation. Chief Building Inspector THIS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION (1) (2) (3) l~l (6) ! DePARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number: BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE Date: ? - /1{- y( 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 I Property Owner: ~ M~ . Property Address: .y'l 'it> ;:;r"~~. e 7f --..:r Contractor License No.: / , 3' ~ 3 , Company: ~y ,,/. -<I ~ OWNER CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby ~ertify that the setback distances proposed by this pennit application are accurate, and do n t violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenant, easements or restrictions of record; that all measurements shown, and allegations made arefaccurate; that t have read and agree to abide by all conditions printed on this applicatio ,and that I assume full responsibility for compliance with the Wheat Ridge Building Code (U. .C.) and all other applicable Wheat Ridge ordinances, for work under this permit. (OWNER!(CONT~CTOR)SIGNED ;;; ~~ DATE /- -/,y-9( Desc1iPtion: ./ ~ 'tV ~ ~ s-- t + 7 Phone: Phone: 7'.? t - ~ t ( ~ Construction Value: Permit Fee: Plan Review Fee: Use Tax: {,60 Total: BUILDING DEPARTMENT USE ONLY Sq. Ft. : Po cp ! ~V;P(l]jfill~l!l) 1,/1'0/<('0 Approval: ~ ~S Zoning: il -I Bum rng~Comments';1 ""'" ,.. .. . ...', . Approval: Pllbl i;1~({jf!p-dIfIm.fijts:l Approval: Oc upancy : SIC: ,-,rv' Y'E'<j.~ (o...Rk;,AJe,{ Roof: Stories: Mechanical License No : Company: Walls: Electric~l License No : Compahy : Plumbing License No : Company: I Expirat on Date: Approv I: ~ ~J' aifS'f'{i!!llllre~ Expiration Date: Approval: I!I Il;'latiir;~equ!rlrlf_ 170 rj) Residential Units: Expiration Date: Approval: III ~f>rali~'J!egl!lre'J1_ his permit was issued in accordance with the provisions set forth in yopur application and is subject to the laws of the State of Colorado and 10 the Zoning egulations and Building Code of Wheat Ridge. Colorado or any other applicable ordinances of the City. is permit shall expire if (Al the work authorized is not commenced within sixty (60) days from issue date or (6) the building authorized is suspended or bandoned for a period of 120 days. I this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the riginal plans and specifications and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment xceeds one (1) year, full fees shall be paid for a new permit. o work of any manner shall be done that will change the natural flow of water causing a drainage problem. ontractor shall notify the Building Inspector twenty.four (24) hours in advance for all inspections and shall receive written approval on inspection card before roceediing with successive phases of the job. e issuance of a permit or the approval of drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation of the provisions f the building codes or any other ordinance, law, rule or regulation. (1) (2) (3) (4) (5) (6) , , ~hief Building Inspector For Mayor ! THIS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR I CALL: 234-5933 24 HOURS PRIOR TO INSPECTION .If\ .~ . 1 IT' - o -I a G'::. r ~ -\ 111 ~ 1_..___---- r. --. 1--- Iv> o. x ""- g .'l: I~ ~ I::l ~ , ~ ~ I Il" 1-1' r- ~ rtl tJ l> ..0 D ((l~ (')\ .- I 0 \f\ !\' ll) ~ '- --J~ {!\ I o