Loading...
HomeMy WebLinkAbout3810 Pierce StreetCONTROLLED AIR, LLC. TESTING AND BALANCING OF DENVER,COLORADO MECHANICAL SYSTEMS 303-883-4688 DRS. JACOB & MAURA FLETCH ER WELL BEING CHIROPRACTIC FAMILY HEALTH 3810 PIERCE STREET WHEAT RIDGE COLORADO CONTROLLED AIR, LLC. TESTING AND BALANCING OF MECHANICAL SYSTEMS GENERAL INFORMATION PROJECT: WELL BEING CHIROPRACTIC LOCATION: WHEAT RIDGE COLORADO ARCHITECT SA ARCHITECTURE MECHANICAL ENGINEER PROFICIENT ENGINEERING GENERAL CONTRACTOR DT CONSTRUCT BALANCING CREW Raymond Lamp / Curtis McNair DATE 2-3-2021 DIFFUSERS AND REGISTERS AND GRILLES SIDEWALL DIFFUSER INSTRUMENTS USED VELOMETER SHORTRIDGE FLOW HOOD ANEMOMETER DAVIS SPEED INDICATOR BIDDLE AMMETER FLUKE VOLTMETER FLUKE INCLINED DRAFT GAGE MAKE MAGNEHELIC GAGE DWYER 0"-1" PRESSURE GAGE PRESSURE GAGE -DIFFERENTIAL PYROMETER THERMOMETERS DIFFUSERS AND REGISTERS AND GRILLES SIDEWALL DIFFUSER MAKE TYPE CEILING DIFUSER MAKE TYPE RETURN REGISTER MAKE TYPE SUPPLY REGISTER MAKE TYPE RETURN GRILLES MAKE TYPE DENVER,COLORADO 303-883-4688 119 PROJECT ALTITUDE 5280' VELOMETER CORRECTION 1.10 APPLIED TO AREA (K -FACTOR) X VELOCITY STATIC PRESSURE CONNECTION 1.21 RECORDED PRESSURE READINGS ARE MEASURED X CORRECTED CONTROLLED AIR, LLC DENVER,COLORADO AIR SYSTEMS RECAP SHEET JOB: WELL BEING CHIROPRATIC FAMILY HEALTH FUNCTION UNIT NO. ZONE OR MAIN REO'D CFM ACT'L CFM % OF REQ'D REMARKS SUPPLY F-1 MAIN 1990 1915 96 SUPPLY F-2 MAIN 1900 1835 96 SUPPLY F-3 MAIN 1940 1925 99 EXHAUST EF -1 MAIN 80 85 106 EXHAUST EF -A MAIN 60 65 108 EXHAUST EF -AA MAIN 60 65 108 EXHAUST EF -AB MAIN 60 65 108 Denver, Colorado CONTROLLED AIR, LLC. PAGE DATE EQUIPMENT DATA PROJECT WELL BEING CHIROPRACTIC A) UNIT NO. F-1 PLAN LOC. MAKE TRANE MODEL# SMD1201-15PS SER. NO. 20334H9S3G RATING SPEED, RPM DIRECT DRIVE B) MOTOR NO ACCESS H.P. 3/4 RATED PF/EFF TYPE PH. 1 RATED SPEED MEAS. VOLTS (L/L) SF N/G RATED VOLTS 120 MEAS. AMPS 5.8 FR. N/G RATED AMPS 13.9 MEAS. VOLTS (L/G) 119 MEAS. KW C) STARTER PART OF PACKAGE SIZE THERMALS (EXIST) AMP. RATING THERMALS (REQ'D) AMP. RATING OTHER D) DRIVEN DIRECT DRIVE SHEAVE X BORE DIRECT DRIVE DRIVER SHEAVE X BORE BELTS SIZE X NO. BELTS MOT. ADJ. IN/OUT CL DIST. DRIVE CHANGE BELT CHANGE DIRECT DRIVE FINAL RPM DIRECT DRIVE FINAL AMPS 5.8 FINAL KW PF (1st) FIN E) FILTER IN -0.28" OUT DROP HEAT COIL IN OUT DROP COOL COIL IN OUT DROP FAN IN OUT 0.10" RISE 0.38" PUMP IN OUT RISE REMARKS 1.0 SQFT X 270 VEL = 270 CFM OSA FINAL CONTROLLED AIR, LLC. AIR BALANCE DATA DENVER, COLORADO PROJECT WELL BEING CHIROPRACTIC LOCATION WHEAT RIDGE COLORADO FAN SYSTEM F-1 M�M—ww mowwo JiIi= Denver, Colorado CONTROLLED AIR, LLC. PAGE DATE EQUIPMENT DATA PROJECT WELL BEING CHIROPRACTIC A) UNIT NO. F-2 PLAN LOC. MAKE TRANE MODEL# S9V2C1000PN SER. NO. 20241 KD43G RATING SPEED, RPM DIRECT DRIVE B) MOTOR NO ACCESS H.P. 3/4 RATED PF/EFF TYPE PH. 1 RATED SPEED MEAS. VOLTS (L/L) SF N/G RATED VOLTS 120 MEAS. AMPS 5.4 FR. N/G RATED AMPS 13.9 MEAS. VOLTS (L/G) 119 MEAS. KW C) STARTER PART OF PACKAGE SIZE THERMALS (EXIST) AMP. RATING THERMALS (REQ'D) AMP. RATING OTHER D) DRIVEN DIRECT DRIVE SHEAVE X BORE DIRECT DRIVE DRIVER SHEAVE X BORE BELTS SIZE X NO. BELTS MOT. ADJ. IN/OUT CL DIST. DRIVE CHANGE BELT CHANGE DIRECT DRIVE FINAL RPM DIRECT DRIVE FINAL AMPS 5.4 FINAL KW PF (1st) FIN E) FILTER IN -0.30" OUT DROP HEAT COIL IN OUT DROP COOL COIL IN OUT DROP FAN IN OUT 0.10" RISE 0.40" PUMP IN OUT RISE REMARKS 1.0 SQFT X 340 VEL = 340 CFM OSA FINAL CONTROLLED AIR, LLC. AIR BALANCE DATA DENVER,COLORADO PROJECT WELL BEING CHIROPRACTIC LOCATION WHEAT RIDGE COLORADO FAN SYSTEM F-2 CONTROLLED AIR, LLC. Denver, Colorado PAGE DATE PLAN LOC. MODEL# S9V2D120U5PS SPEED, RPM DIRECT DRIVE RATED PF/EFF 1 RATED SPEED N/G RATED VOLTS 120 N/G RATED AMPS 13.9 MEAS. KW SIZE (EXIST) AMP. RATING (REQ'D) AMP. RATING SHEAVE X BORE DIRECT DRIVE SHEAVE X BORE SIZE X NO. BELTS CL DIST. BELT CHANGE DIRECT DRIVE FINAL AMPS 5.7 FIN DROP DROP DROP 0.10" RISE 0.34" RISE EQUIPMENT DATA PROJECT WELL BEING CHIROPRACTIC A) UNIT NO. F-3 MAKE TRANE SER. NO. 20334KYY3G RATING B) MOTOR NO ACCESS H.P. TYPE PH. MEAS. VOLTS (L/L) SF MEAS. AMPS 5.,7 FR. MEAS. VOLTS (L/G) 119 C) STARTER PART OF PACKAGE THERMALS THERMALS OTHER D) DRIVEN DIRECT DRIVE DRIVER BELTS MOT. ADJ. IN/OUT DRIVE CHANGE FINAL RPM DIRECT DRIVE FINAL KW PF (1st) E) FILTER IN -0.24" OUT HEAT COIL IN OUT COOL COIL IN OUT FAN IN OUT PUMP IN OUT REMARKS PAGE DATE PLAN LOC. MODEL# S9V2D120U5PS SPEED, RPM DIRECT DRIVE RATED PF/EFF 1 RATED SPEED N/G RATED VOLTS 120 N/G RATED AMPS 13.9 MEAS. KW SIZE (EXIST) AMP. RATING (REQ'D) AMP. RATING SHEAVE X BORE DIRECT DRIVE SHEAVE X BORE SIZE X NO. BELTS CL DIST. BELT CHANGE DIRECT DRIVE FINAL AMPS 5.7 FIN DROP DROP DROP 0.10" RISE 0.34" RISE CONTROLLED AIR, LLC. AIR BALANCE DATA DENVER,COLORADO PROJECT WELL BEING CHIROPRACTIC LOCATION WHEAT RIDGE COLORADO FAN SYSTEM F-3 '•s •'From m ®®®®® �' ® �' ® �' RETURN NO SUPPLY soil Denver, Colorado CONTROLLED AIR, LLC. PAGE DATE EQUIPMENT DATA PROJECT WELL BEING CHIROPRACTIC A) UNIT NO. EF -1 PLAN LOC. MAKE BROAN MODEL# L100 SER. NO. 91 F03H RATING SPEED, RPM DIRECT DRIVE B) MOTOR NUTONE H.P. N/G RATED PF/EFF TYPE PH. 1 RATED SPEED MEAS. VOLTS (L/L) SF N/G RATED VOLTS 120 MEAS. AMPS 0.9 FR. N/G RATED AMPS 1.1 MEAS. VOLTS (L/G) 118 MEAS. KW C) STARTER SIZE THERMALS (EXIST) AMP. RATING THERMALS (REQ'D) AMP. RATING OTHER D) DRIVEN DIRECT DRIVE SHEAVE X BORE DIRECT DRIVE DRIVER SHEAVE X BORE BELTS SIZE X NO. BELTS MOT. ADJ. IN/OUT CL DIST. DRIVE CHANGE BELT CHANGE DIRECT DRIVE FINAL RPM DIRECT DRIVE FINAL AMPS 0.9 FINAL KW PF (1st) FIN E) FILTER IN OUT DROP HEAT COIL IN OUT DROP COOL COIL IN OUT DROP FAN IN OUT RISE PUMP IN OUT RISE REMARKS 1.0 SQFT X 80 VEL = 80 CFM : 1.0 SQFT X 85 VEL = 85 CFM FINAL Denver, Colorado CONTROLLED AIR, LLC. PAGE DATE EQUIPMENT DATA PROJECT WELL BEING CHIROPRACTIC A) UNIT NO. EF -A PLAN LOC. MAKE BROAN MODEL# AE80BA SER. NO. 91 F041-12 RATING SPEED, RPM DIRECT DRIVE B) MOTOR NUTONE H.P. 1/26 RATED PF/EFF TYPE PH. 1 RATED SPEED MEAS. VOLTS (L/L) SF N/G RATED VOLTS 120 MEAS. AMPS 0.3 FR. N/G RATED AMPS 0.3 MEAS. VOLTS (L/G) 118 MEAS. KW C) STARTER SIZE THERMALS (EXIST) AMP. RATING THERMALS (REQ'D) AMP. RATING OTHER D) DRIVEN DIRECT DRIVE SHEAVE X BORE DIRECT DRIVE DRIVER SHEAVE X BORE BELTS SIZE X NO. BELTS MOT. ADJ. IN/OUT CL DIST. DRIVE CHANGE BELT CHANGE DIRECT DRIVE FINAL RPM DIRECT DRIVE FINAL AMPS 0.3 FINAL KW PF (1st) FIN E) FILTER IN OUT DROP HEAT COIL IN OUT DROP COOL COIL IN OUT DROP FAN IN OUT RISE PUMP IN OUT RISE REMARKS 1.0 SQFT X 60 VEL = 60 CFM: 1.0 SQFT X 65 VEL = 65 CFM FINAL Denver, Colorado CONTROLLED AIR, LLC. PAG DATE EQUIPMENT DATA PROJECT WELL BEING CHIROPRACTIC A) UNIT NO. EF -AA PLAN LOC. MAKE BROAN MODEL# AE80BA SER. NO. 91 F041-12 RATING SPEED, RPM DIRECT DRIVE B) MOTOR NUTONE H.P. 1/26 RATED PF/EFF TYPE PH. 1 RATED SPEED MEAS. VOLTS (L/L) SF N/G RATED VOLTS 120 MEAS. AMPS 0.3 FR. N/G RATED AMPS 0.3 MEAS. VOLTS (L/G) 118 MEAS. KW C) STARTER SIZE THERMALS (EXIST) AMP. RATING THERMALS (REQ'D) AMP. RATING OTHER D) DRIVEN DIRECT DRIVE SHEAVE X BORE DIRECT DRIVE DRIVER SHEAVE X BORE BELTS SIZE X NO. BELTS MOT. ADJ. IN/OUT CL DIST. DRIVE CHANGE BELT CHANGE DIRECT DRIVE FINAL RPM DIRECT DRIVE FINAL AMPS 0.3 FINAL KW PF (1st) FIN E) FILTER IN OUT DROP HEAT COIL IN OUT DROP COOL COIL IN OUT DROP FAN IN OUT RISE PUMP IN OUT RISE REMARKS 1.0 SQFT X 60 VEL = 60 CFM : 1.0 SQFT X 65 VEL = 65 CFM FINAL Denver, Colorado CONTROLLED AIR, LLC. PAGE DATE EQUIPMENT DATA PROJECT WELL BEING CHIROPRACTIC A) UNIT NO. EF -AB PLAN LOC. MAKE BROAN MODEL# AE80BA SER. NO. 91 F04H2 RATING SPEED, RPM DIRECT DRIVE B) MOTOR NUTONE H.P. 1/26 RATED PF/EFF TYPE PH. 1 RATED SPEED MEAS. VOLTS (L/L) SF N/G RATED VOLTS 120 MEAS. AMPS 0.3 FR. N/G RATED AMPS 0.3 MEAS. VOLTS (L/G) 118 MEAS. KW C) STARTER SIZE THERMALS (EXIST) AMP. RATING THERMALS (REQ'D) AMP. RATING OTHER D) DRIVEN DIRECT DRIVE SHEAVE X BORE DIRECT DRIVE DRIVER SHEAVE X BORE BELTS SIZE X NO. BELTS MOT. ADJ. IN/OUT CL DIST. DRIVE CHANGE BELT CHANGE DIRECT DRIVE FINAL RPM DIRECT DRIVE FINAL AMPS 0.3 FINAL KW PF (1st) FIN E) FILTER IN OUT DROP HEAT COIL IN OUT DROP COOL COIL IN OUT DROP FAN IN OUT RISE PUMP IN OUT RISE REMARKS 1.0 SQFT X 60 VEL = 60 CFM : 1.0 SQFT X 65 VEL = 65 CFM FINAL DCD W A VOUAAC DA%M ePOf0 Tmm JCrACOMAND =APMCM OM-SM. aso". CTG. C 10T WRffiC. RtfM MACTWTJRKAIID T UlettuwDALUsuxro TO Re r¢w ox+Drtroe s+®)} u+o asSoaATm�OLIMOOR S 4KT Or MAU&M BALM CCM T SCRCCR. CoNN=W Rtrm tooppA . %RCCN. M AW 10 1AR: oPOd!lDD. nxN WC. DDR DRAM W FBQIHACA ROW, ro^uet�ere��wc. i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: ", 6e,j �; � le -C . Job Address: 3 t� { Permit Number: a 0 �0 d V/5- LJ /j ❑ No one available for inspection: Time AM/PM Re -Inspection required: Yes No When corrections have been made, schedule for re -inspection online,at: httpY www.ci. wheatridge.co. usfinspection Date: Inspector: DO NOT REMOVE THIS NOTICE i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: eksay- Job Address: ICS Eala r Permit Number: ( f----` r LlNo one available for inspection: Time AM/PM Re -Inspection required. -Yes`,-` No *When corrections are complete, s he le re -inspection on ina- Date` � Insipectoy: ' n� w►�r miff n&^,iU— ru Inspection Type: Job Address: Permit Number: CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION. NOTICE ❑ No one available for inspection: Timq(7 `` � ,_I.''�AM/PM Re -Inspection required: Ye( N When corrections are complete, scheduAe re -inspection online. Date-.///;77—/24Inspector: AA AI/1T I-ICA.W/7fIA � ► 44" City of Wheat Ridge '/� Comm. Tenant Finish PERMIT - 201802415 PERMIT NO: 201802415 ISSUED: 10/04/2018 JOB ADDRESS: 3810 Pierce St EXPIRES: 03/02/2021 JOB DESCRIPTION: Demo of all non -load bearing interior partitions, fixtures and finishes; remodel interior to create three spaces; 3,375 sq f t ; l , 761 sq ft and 1,134 sq ft; 6,490 sq ft total *** CONTACTS *** OWNER (303) 238-6500 GC (720) 373-9605 SUB (720) 441-5065 SUB (720) 394-0288 SUB (303) 627-2714 SUB (303)444-1191 Tenant: Well Beings Chiropractic **REVISION: Hanging hat channel and sheet rock in lieu of floating the existing CMU block wall. No added valuation. FLETCHER MAURA & JACOB DAN THOEMKE/ERNIE GILBERT ERIC S OLRIKSEN JOSE A ORTIZ BENJAMIN STUCKEY ROBERT BONIFAS *** PARCEL INFO *** ZONE CODE: UA / Unassigned SUBDIVISION CODE: 420 / Storage Warehouse; 0 *** FEE SUMMARY *** Total Valuation Plan Review Fee Use Tax Permit Fee Extend Expired Permi Plan Review Addll ** TOTAL ** *** COMMENTS *** 190196 DT CONSTRUCT INC. 180168 SOVCO HYDRONICS 190332 COMMUNITY MECHANICAL SVCS LLC 019484 STANMARK ELECTRIC 170005 SAFE SYSTEMS INC USE: UA / Unassigned BLOCK/LOT#: 0 / ESTIMATED PROJECT VALUATION: FEES 0.00 11574.33 6,300.00 2,422.05 11211.03 120.00 11,627.41 300, 000.00 *** CONDITIONS *** All roughs to be done at Framing Inspection. Approved per plans and red -line notes on plans. Must comply with 2012 IBC, 2017 NEC and all applicable City of Wheat Ridge Municipal Codes. Work is subject to field inspections. **Prior to final inspection approval - As-builts are required before approval of the Building Final Inspection and Certificate of Occupancy can be issued. � ► 44" City of Wheat Ridge '/� Comm. Tenant Finish PERMIT - 201802415 PERMIT NO: 201802415 ISSUED: 10/04/2018 JOB ADDRESS: 3810 Pierce St EXPIRES: 03/02/2021 JOB DESCRIPTION: Demo of all non -load bearing interior partitions, fixtures and finishes; remodel interior to create three spaces; 3,375 sq f t ; l , 761 sq ft and 1,134 sq ft; 6,490 sq ft total Tenant: Well Beings Chiropractic **REVISION: Hanging hat channel and sheet rock in lieu of floating the existing CMU block wall. No added valuation. I, by my signature, do hereby attest that the work to be performed shall comply with all accompanying approved plans and specifications, applicable building codes, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with this�permrt. I further attest that I am leg ally authorized to include alI entities named within this document as parties to the work to be performed and that all work to be performed is disclosed in this document and/or its' accompanying approved plans and specifications. Signature of OWNER or CONTRACTOR (Circle one) Date 1, This permit was issued based on the information provided in the permit application and accompanying plans and specifications and is subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures. 2. This permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and received prior to the date of expiration. An extension of no more than 180, days made be granted at the discretion of the Chief Building Official and may be subject to a fee equal to one-half of the original permit fee. 3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard requirements, fees and��procedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of the Chief Building Official and is not guaranteed. 4. No work of any manner shall be performed that shall results in a change of the natural flow of water without prior and specific approval. 5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all requ�ired inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services Division. 6. The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, anviolation of any provision of any �pplicabje code or any ordinance or regulation of this jurisdiction. Approval of work is subject to field inspection. 10/04/2018 Signature of Chief Building Official Date REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. )%P � 4 41 City Of MWheat�dgc COMUNITY DEVELOPMENT SUBCONTRACTOR AUTHORIZATION FORM Electrical Subcontractor This form must be completed & signed by the ELECTRICAL SUBCONTRACTOR performing electrical work on site. Subcontractor's insurance and license must be up to date prior to permit issuance. Project Address: 3810 Pierce Street General Contractor: Safe Systems, Inc FORM WILL NOT BE ACCEPTED WITH MISSING INFORMATION Company Name: Safe Systems, Inc Contact Phone #: 720-354-5061 Wheat Ridge Contractor License #: 170005 State License #: 19-S-08820 Master License #: Elyse Frazier Printed Name of Authorized Agent Signature of Aut orized Agent (required field) 1/21/2021 Date i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: C.4 Vk,-) " Job Address: r= '! -s c= Permit Number: (Z--> _ I ❑ No one available for inspe Re -Inspection required: When corrections are complete, Date: (A Ins online. M i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address:,y(Q� r= df' Permit Number: (ZD`ZZ I FD w ❑ No one available for inspection: Time Re -Inspection required: Yes' No - When corrections are complete, schedy_e re -inspection online. Date: Inspector: � ► 44" City of Wheat Ridge '/� Comm. Tenant Finish PERMIT - 201802415 PERMIT NO: 201802415 ISSUED: 10/04/2018 JOB ADDRESS: 3810 Pierce St EXPIRES: 03/02/2021 JOB DESCRIPTION: Demo of all non -load bearing interior partitions, fixtures and finishes; remodel interior to create three spaces; 3,375 sq f t ; l , 761 sq ft and 1,134 sq ft; 6,490 sq ft total *** CONTACTS *** OWNER (303) 238-6500 GC (720) 373-9605 SUB (720) 441-5065 SUB (720) 394-0288 SUB (303) 627-2714 Tenant: Well Beings Chiropractic **REVISION: Hanging hat channel and sheet rock in lieu of floating the existing CMU block wall. No added valuation. FLETCHER MAURA & JACOB DAN THOEMKE/ERNIE GILBERT ERIC S OLRIKSEN JOSE A ORTIZ BENJAMIN STUCKEY *** PARCEL INFO *** ZONE CODE: UA / Unassigned SUBDIVISION CODE: 420 / Storage Warehouse; 0 *** FEE SUMMARY *** Total Valuation Plan Review Fee Use Tax Permit Fee Extend Expired Permi Plan Review Addll ** TOTAL ** *** COMMENTS *** 190196 DT CONSTRUCT INC. 180168 SOVCO HYDRONICS 190332 COMMUNITY MECHANICAL SVCS LLC 019484 STANMARK ELECTRIC USE: UA / Unassigned BLOCK/LOT#: 0 / ESTIMATED PROJECT VALUATION: FEES 0.00 11574.33 6,300.00 2,422.05 11211.03 120.00 11,627.41 300, 000.00 *** CONDITIONS *** All roughs to be done at Framing Inspection. Approved per plans and red -line notes on plans. Must comply with 2012 IBC, 2017 NEC and all applicable City of Wheat Ridge Municipal Codes. Work is subject to field inspections. **Prior to final inspection approval - As-builts are required before approval of the Building Final Inspection and Certificate of Occupancy can be issued. � ► 44" City of Wheat Ridge '/� Comm. Tenant Finish PERMIT - 201802415 PERMIT NO: 201802415 ISSUED: 10/04/2018 JOB ADDRESS: 3810 Pierce St EXPIRES: 03/02/2021 JOB DESCRIPTION: Demo of all non -load bearing interior partitions, fixtures and finishes; remodel interior to create three spaces; 3,375 sq f t ; l , 761 sq ft and 1,134 sq ft; 6,490 sq ft total Tenant: Well Beings Chiropractic **REVISION: Hanging hat channel and sheet rock in lieu of floating the existing CMU block wall. No added valuation. I, by my signature, do hereby attest that the work to be performed shall comply with all accompanying approved plans and specifications, applicable building codes, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with this�permrt. I further attest that I am leg ally authorized to include alI entities named within this document as parties to the work to be performed and that all work to be performed is disclosed in this document and/or its' accompanying approved plans and specifications. Signature of OWNER or CONTRACTOR (Circle one) Date 1, This permit was issued based on the information provided in the permit application and accompanying plans and specifications and is subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures. 2. This permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and received prior to the date of expiration. An extension of no more than 180, days made be granted at the discretion of the Chief Building Official and may be subject to a fee equal to one-half of the original permit fee. 3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard requirements, fees and��procedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of the Chief Building Official and is not guaranteed. 4. No work of any manner shall be performed that shall results in a change of the natural flow of water without prior and specific approval. 5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all requ�ired inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services Division. 6. The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, anviolation of any provision of any applicable code or any ordinance or regulation of this jurisdiction. Approval of work is subject to field inspection. Signature of Chief Building Official Date REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. DR. Dan moi ran Kimberly Cook on Danielle Relief e,Coa rs Graham tender Care Pairs Subnert: Re reed Dann °;ad,°�M, ,r�doeboducion Al..nte.Di 24.24,n,.nei Neaten,invacram,con as 24x24 we Sony the guys have been slammed Please remove these three Thank you, Dan All all Al all w Rea. .luau ,.o "i r... .®Real al rrm ".. loal ynatural rents w as oT Construct Inc. Dann Ramos CEO 720 373960s ..e, amonrnnn hom On San 7, 2021, at 2.03 PM, Kimberly Cook <kcook@ci wheal co us wrote CITY OF WHEAT RIDGE Building Ins Division 9 ection p I (303) 235-2855 Office IN PECTIO NOTICE Inspection Type: f Job Address:° Permit Number: -,7 ( 4 f ® ❑ No one available for inspectii l-' e AM/PM Re -Inspection required: Y N When corrections are complete, Date: Insp i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: ---f Job Address: Permit Number: ❑ No one available for inspection: Time AM/PM Re -Inspection required: Yes No When corrections have been made, httpYlvvww.ci. wheatridge.co. usfinspi Date: ; 1 �_Inspe� nn A/nT RFMA for re -inspection online at: City of Wheat idle COMMUNITY DEVELOPMENT SUBCONTRACTOR AUTHORIZATION FORM Electrical Subcontractor This form must be completed & signed by the ELECTRICAL SUBCONTRACTOR performing electrical work on site. Subcontractor's insurance and license must be up to date prior to permit issuance. Project Address: 3� 10 i 1 e f (& / t wt General Contractor: PT Co n &t�1)Lr FORM WILL NOT BE ACCEPTED WITH MISSING INFORMATION Company Name: /�lGtnni( V-- ? e 6yk& Contact Phone #: 2)0;) - W i- ZM Wheat Ridge Contractoyr, License #:_ � � � G' � (required field) State License #: Master License #:—DY U o g tv%- �ell�ae'�l Printed Name of Authorized Agent 12I�i�Zcyy Signature of Authorized Agent Date i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: a (qc�, r,= -y r�� -7yzj C "t Job Address: �Zsr� Permit Number: ,,z" ❑ No one available for inspection: Re -Inspection required,: es o *When.corrections have been made, scheme h ttp ✓/www. ci. wheatridge. co. uslinspegton t Time _, M for re -inspection online at: � ► 44" City of Wheat Ridge '/� Commercial Low Voltage PERMIT - 202002013 PERMIT NO: 202002013 ISSUED: 10/07/2020 JOB ADDRESS: 3810 Pierce St EXPIRES: 10/07/2021 JOB DESCRIPTION: Installation of a non required addressable Notifier NFW-10OX manual fire alarm system. Sq ft: 6,490 *** CONTACTS *** OWNER (303)854-8871 WELL BEING FAMILY CHIROPRACTIC SUB (303)444-1191 ROBERT BONIFAS 170005 ALARM DETECTION SYSTEM, INC *** PARCEL INFO *** ZONE CODE: UA / Unassigned USE: UA / Unassigned SUBDIVISION CODE: 440 / R&D/Flex BLOCK/LOT#: 0 / *** FEE SUMMARY *** ESTIMATED PROJECT VALUATION: 91500.00 FEES Total Valuation 0.00 Use Tax 199.50 Permit Fee 204.30 ** TOTAL ** 403.80 *** COMMENTS *** *** CONDITIONS *** All work shall comply 2018 International Codes, 2020 NEC (if applicable), and ordinances adopted by the City of Wheat Ridge. Work is subject to field inspections. I, by my signature, do hereby attest that the work to, be performed shall comply with all accompanying approved plans and specifications, applicae building codes, and all applicable municpal codes, policies and procedures, and that I am the legal owner or have been authorized by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with this�permrt. I further attest that I am leg ally authorized to include alI entities named within this document as parties to the work to be performed and that all work to be performed is disclosed in this document and/or its' accompanying approved plans and specifications. Signature of OWNER or CONTRACTOR (Circle one) Date 1, This permit was issued based on the information provided in the permit application and accompanying plans and specifications and is subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures. 2. This permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and received prior to the date of expiration. An extension of no more than 180, days made be granted at the discretion of the Chief Building Official and may be subject to a fee equal to one-half of the original permit fee. 3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard requirements, fees and��procedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of the Chief Building Official and is not guaranteed. 4. No work of any manner shall be performed that shall results in a change of the natural flow of water without prior and specific approval. 5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all requ�ired inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services Division. 6. The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, anviolation of any provision of any applicable code or any ordinance or regulation of this jurisdiction. Approval of work is subject to field inspection. Signature of Chief Building Official Date REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. From: CommDev Permits TO: Dina Kemp Subject: Fw: Online Forth Submittal: General Permit Application Date: Sunday, December 13, 2020 4:14:55 PM General Permit Application This application is exclusively for Scopes of Work that do not already have a specific form. YOU MUST ATTACH AN ELECTRONIC PAYMENT FORM IN ORDER FOR THE PERMIT TO BE PROCESSED. THIS APPLICATION DOES NOT CONSTITUTE A PERMIT. DO NOT BEGIN WORK UNTIL PERMIT HAS BEEN ISSUED. PROPERTY INFORMATION Is the property Commercial Residential or Commercial? Property Address 3810 Pierce St, Wheat Ridge, CO 80033 Property Owner Name Well Being Family Chiropractic Property Owner Phone 303-854-8871 Number (enter WITH dashes, eg 303-123- 4567) Property Owner Email Address Attach City of Wheat Ridge Electronic Payment Form - "DO NOT ATTACH A PICTURE OF A CREDIT CARD" CONTACT INFORMATION Submitting General Contractor or Architect installpermits@safe-systems.com Electronic Payment Form.odf Safe Systems Contractor's License 170005 Number (This is a 5 or 6 digit number for the City of Wheat Ridge) Contract Phone 720-975-0076 Number (enter WITH dashes, eg 303-123- 4567) Contact Email Address installpermits@safe-systems.com Retype Contact Email installpermits@safe-systems.com Address 01:we]ziIa1[0]0N]ayONlS21 Detailed Scope of Installation of a non required addressable Notifier NFW-10OX Work - Provide a manual fire alarm system detailed description of work including mechanical, electrical, plumbing work occurring, adding/removing walls, etc. Square footage of 6490 scope of work Location of work Inside building (backyard, on roof, etc) Project Value (contract 9500 value or cost of ALL materials and labor) Upload Engineer letter, Field not completed. other documents on 8 1/2" x 11 " Upload Asbestos Field not completed. Report if triggler level is met per CDPHE regulation. Upload Vell Beijos Stjlbw.�o.e...odi 17" or larger SIGNATURE OF UNDERSTANDING AND AGREEMENT I assume full Yes responsibility for compliance with applicable City of Wheat Ridge codes and ordinances for work under any permit issued based on this application. I understand that work Yes may not begin on this property until a permit has been issued and posted on the property. I certify that I have Yes been authorized by the legal owner of the property to submit this application and to perform the work described above. I attest that everything Yes stated in this application is true and correct and that falsifying information in this application is an act of fraud and may be punishable by fine, imprisonment, or both. Person Applying for Mariel Molke Permit Email not displaying correctly? View it in your browser. August 28, 2019 Mr. Jeremy Bennett Haystack Construction 3615 S Huron St #201, Englewood, CO 80110 Phone: 720-452-5657 Printz Engineering Services, LLC RE: Structural Inspection & Recommendations — 3810 Pierce St. Wheat Ridge, CO Dear Mr. Bennett, On August 23, 2019, 1 conducted a structural inspection and at the property referenced above. This work was performed in order to provide a general assessment of the current status of the property and serve to gather information to aid in designing lintels to span the penetrations in the N -S running CMU wall as well as the design of the header beam to be installed where the E -W oriented CMU wall has been removed to make way for a walkway. The investigation was strictly visual and only included the taking of pictures and measuring of the openings. No material or geotechnical testing was performed and is beyond the scope of this investigation. The property is one level commercial building, grout -filled CMU block wall with concrete stem foundation & concrete slab consisting of a single main level set at equal grade to what is presented on the exterior of the building. OBSERVATIONS: During the visit and inspection on August 23, 2019 there were a total of 9 wall penetrations observed on the N -S running CMU block wall to make way for MEP passage. The maximum span of these penetrations was observed to be 28" in length with the wall consisting combination of (1) course of 4 x 8 x 16 grout filled CMU block backed up to a standard 3-1/2 x 2-1/4 x 7-5/8 brick and mortar wall. Spans 1- 5, and 7-9 (numbered in ascending order from 1-9 from N -S) are cut out of the N -S load-bearing wall and will require lintel support across the top span of the penetration. Penetration 6 is a former penetration that shall be abandoned as no MEP will be passing through it in the new finish of the building. Instructions on how to finish this penetration are included in the recommendations section. Directly to the west of the N -S running CMU block wall with the 9 penetrations mentioned in the previous paragraph, there is an E -W running load-bearing wall where 54" of load-bearing wall has been removed and temporarily vertically shored, but will need a permanent vertical load support. RECOMMENDATIONS: Printz Engineering Services, LLC 1710 Cuprite Court Castle Rock, CO 80108 e-mail: jpendleton@printzengineeringservices.com Page 1 of 6 �-- Zolg OZy/S Printz Engineering Services, LLC Penetrations 1-5 and 7-9 should have a minimum of an A-36 steel L 2x2x1/8 lintel (with the vertical leg oriented down) concrete anchored into the CMU / brick wall spanning the full length of each penetration span with 4" of steel angle length overlap on both the north and the south side of the penetrations. This should occur on both the east and west sides of the wall. There should be a total of (3) 3/8" X 2" minimum depth concrete anchors used in order to positively fasten the angle iron lintel to the face of the cmu / brick wall. Two of the three concrete anchors should be installed 2" outside of the profile of the penetration (half -way through the overlap of the lintel outside of the north -south profile of each penetration) and the third concrete anchors should be installed mid -span of the lintel (exactly in the middle of the full lintel span length). Penetration 6 can be framed in and blocked using a minimum of (5) 2x6 pieces of heat-treated lumber as vertical shims evenly spaced N -S with the top and bottom of the penetration being plumbed and framed using lateral 2 x 6 lumber and the vertical shims toed in. The 54" East-West span of the load-bearing CMU wall that has been removed should have the roof dead, live, and snow loads supported via (2) 3-1/2" Nominal Sch. 40 Adjustable posts supporting an up to 60" long W413 A-36 steel header beam in a simple span fashion with the adjustable end of the posts facing. The top flange of the steel beam is to be put in direct bearing with the roof framing above to for support. The adjustable posts shall be fixed on both the top and bottom junctions. The top junction between the post and the steel beam should either be attached via a flange plate with (4) 3/8" self -tapping metal screws to connect the flange plate to the beam flange, the flange plate of the adjustable post welded to the base flange of the beam around the full perimeter of the adjustable post plate, or have the adjustable plate for the post be built with the end termination plate having bendable flanges that can reach up and around the base flange of the steel beam and be wrapped and pinched tightly around the bottom flange of the steel beam. The bottom junction of the adjustable steel post should be either tied in via a flange plate with (4) 3/8" diameter Hilti Redheads or have the post cast -in to a concrete slab section pour with a minimum embedment of the post of 4" in depth. Alternatively, the East-West span of the load-bearing CMU wall that has been removed may have the roof dead, live, and snow loads supported via (2) 4x6 wood columns supporting up to a 60" long 2.5x18 Western Glu -tam. There should be fixity at the top and bottom junctions of the wood columns if utilized. The top junction to the glu-lam should be attached by (4) 3/8" x 4" long wood lag screws that penetrate through the flange of the glu-lam into the top of the wood post. At the bottom junction of the wood post, the post should be attached by an industry standard steel post base anchors with a minimum of (4) 3/8" diameter Hilti Redheads tapped into the slab concrete. This concludes the report. Observations made in this report pertain to the condition of the structure on the date of the inspection. No warranty is expressed or implied by this report. If I can be of further assistance or should you have any questions about this report, please do not hesitate to contact me. Printz Engineering Services, LLC 1710 Cuprite Court Castle Rock, CO 80108 e-mail: jpendleton@printzengineeringservices.com Page 2 of 6 3 g /D c e S1- Printz Engineering Services, LLC 7o1goz GlS Kind Regards, Jeff Pendleton, P.E. Staff Engineer Printz Engineering Services, LLC Attachments: Pictures from On-site Inspection Lintel Beam Span Calculations Header Beam Calculations Wood Column Calculation 08-29-19 ON-SITE INSPECTION PHOTOS Photo 1: Penetrations 1 & 2 Photo 2: Penetrations 2 & 3 Photo 3: Penetration 5 Photo 4: Penetrations 6 & 7 Printz Engineering Services, LLC 1710 Cuprite Court Castle Rock, CO 80108 e-mail: jpendleton@printzengineeringservices.com Page 3 of 6 Printz Engineering Services, LLC Photo 5: Penetration 9 Photo 6: E -W 60" CMU Load -Bearing Wall Shoring - Header & Columns to be Placed Here Printz Engineering Services, LLC 1710 Cuprite Court Castle Rock, CO 80108 e-mail: jpendleton@printzengineeringservices.com Page 4of6 t t t i d 1 2xzX/ . r (.b i , l 1 t l t j 4 { I ( 77 -it w Aq I r ® c , I i i i t i. i ,}.�.. t wv � .... , } - ice._';'--"-�. �__.__ �..T..._... -.- ¢. ...•..._ $ - ... 3 L"k ioGt(+_fit , 'I CA t Ct t` t , ro cfi r r f � N - - r -L s ,T a-r't s LAS + pw,v gtJ`kr + G� C7Pa e7� FL U IL' �i e Ftp i 1 k i Ivis c _ : L._ ; Page 5 of 6 _ -�- , 1 1[ 1 5 d S ,1 f , i { 1 ; f LONA+ I i 7 1 I f i ' _.. P "'�-�_ ' l t i v i (2) yX 5�toN CO ,A IA __ ax „ ; • s i i �_ I ! a �i - _ . ,. ___ , . _ �� � oast, 1 A 1—_ 4 77. ._.__ 4 ` E C '„�,,f ___r.---'�-- .. iL- i ._ --d -_ r''E G1�is^�"�% � ��%�-l.�/�ws _ ,.:. � i •. ` -.._ ' j ' .._: fi i (\ III 11 i 1 , , I i 1 a— t , , , i f Page 6 of 6 i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: C) 1/ir Job Address: _31 1�'r42 Permit Number: Z-0,/ Q 0 7,_� !!Z/ P, ILI No one available for inspection: Time '' 7 AM Re -Inspection required: Yes �o When corrections have been made, 6e ule for re -inspection online at: http://www. ci. wheatridge. co. ueInspection 7 Dat1e: /�`-��� Inspector: f DO NOT REMOVE THIS NOTICE i CITY OF WHEAT RIDGE' Building Inspection Division /! _ 0 (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address: Permit Number: = t:?r i i .ice/f A �� �-f'i r':✓r'j ,�c!.% r ❑ No one available for inspection: Time AMLPM Re -Inspection required: Yes No When corrections have been made, schedule for re -inspection online at: http://www. ci. wheatridge. co, uslinspection Date: ; ;*` _ ` - Inspector: DO NOT REMOVE THIS NOTICE 1z s e� i CITY OF WHEAT RIDGE r Building Inspection Division J (303) 235-2855 Office INSPECTION NOTICE Inspection Type: L4/ Job Address: 3 /l f;&' - �� Sf Permit Number: ZV/!3 p Z,' ��/5" ❑ No one available for inspection: Time AM/¢ Re -Inspection required: Yes No When corrections.have been made, schedule for re -inspection online at: http://www.ci. wheatridge.co.usrnspection Date: In -30'c02t7 Inspector: .5J--0 DO NOT REMOVE THIS NOTICE CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: %Job Address: Permit Number: ❑ No one available for inspection: Time AWPM Re -Inspection required: Yes No When corrections have been made, schedule for re -inspection online at. http://www. ci. wheatridge. co. usrinspection Date: /®- Z cl' 2*5,;-�"V Inspector: S/110 DO NOT REMOVE THIS NOTICE ' : 3 a i CITY OF WHEAT RIDGE �•r� ; M Z) Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address: Permit Number: ?—V / /- Y ❑ No one available for inspection: Time �' � ,N' PM A Re -Inspection required: Yes . --o When corrections have been made, schedule for re -inspection online at. httpYlwww.ci. wheatridge.co. usfinspection Date:. nspector: DO NOT REMOVE THIS NOTICE i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address: Permit Number: r j ❑ No one available for inspection: AM/PM Re -Inspection requireds No When corrections have been made, scherdgle for re -inspection online at: hUp✓/www.ci. wh ea tridge. co. usrnspect�o Y112 .243 01 9M 0_ of i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type:.:2� f,�- / E Job Address: Permit Number: ❑ No one available for inspection: Time NI M Re -Inspection required: Yesl�„o When corrections have been madq;'sch� .Wv for re -inspection online at: http✓/www.ci.wheatridge.co.u�nspec ioi CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: FI Job Address: -- R/0 ?,,.e / S Permit Number: C7 ❑ No one available for inspection: Time ASF°" Re -Inspection required: Yes Ao _/ When corrections have been made, schedule for re -inspection online at: http://www.ci. wheatridge.co. uslinspection Date: /O-2,/-2UZ0lnspector: S DO NOT REMOVE THIS NOTICE i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type:f Job Address: -.>4 10 4P I Cr < C_ Permit Number: ?C: ) 40r�{ I rte/ ❑ No one available for inspection:,Time AM/PM Re -Inspection required: Yes 00 When corrections have been made, schedule for re -inspection online at: http✓/www. ci. wheatridge. co. ussfinspection DatAo' �� � � Inspector: br- DO NOT REMOVE THIS NOTICE ♦ A i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type:. MY2 : rn /t` Job Address: i c ; 5j - Permit Number: ca(D 1 ;U��) ❑ No one available for inspection: Time `lam AM/PM Re -Inspection required: Yes Jo When corrections have been made, schedule for re -inspection online at: http✓/www. ci. whea tridge. co. usrnspection Datedb.a ao->o Inspector:_ DO NOT REMOVE THIS NOTICE CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type- o c) 0� C Job Address: -3;7 (0 -Pie Permit Number: lg,, /i r elo (v,,) c y - J No one available for inspection: Time i AM/PM r\ Re -Inspection required: Yes No When corrections have been made, schedule for re -inspection, online at: http;llwww.cL wheatridge.co. uslinspection Date --)r dda Inspector: DO NOT REMOVE THIS NOTICE City of ,Ad Wh6atpjdge COMMUNITY DEVELOPMENT SUBCONTRACTOR AUTHORIZATION FORM Plumbing Subcontractor This form must be completed & signed by the PLUMBING SUBCONTRACTOR performing plumbing work on site. Subcontractor's insurance and license must be up to date prior to permit issuance. ProjectAddress: 3 910 General Contractor: Company Names (:O IDQO NJA , Contact Phone #: 5775-1 Wheat Ridge Contractor License #: / D 0 M4?' (required field) State License #:j' C . oao 3 711l Master License #: me . OwOA O �<rc. 5. C tRZ<5" .A Printed Nam f th d A ent ignature of Authorized Agent � ► 44" City of Wheat Ridge '/� Comm. Tenant Finish PERMIT - 201802415 PERMIT NO: 201802415 ISSUED: 10/04/2018 JOB ADDRESS: 3810 Pierce St EXPIRES: 03/02/2021 JOB DESCRIPTION: Demo of all non -load bearing interior partitions, fixtures and finishes; remodel interior to create three spaces; 3,375 sq f t ; l , 761 sq ft and 1,134 sq ft; 6,490 sq ft total *** CONTACTS *** OWNER (303) 238-6500 SUB (303) 720-5345 SUB (303) 233-7007 SUB (303) 233-7007 GC (720) 373-9605 Tenant: Well Beings Chiropractic **REVISION: Hanging hat channel and sheet rock in lieu of floating the existing CMU block wall. No added valuation. FLETCHER MAURA & JACOB Adam Stockton Torrey Cosgrove Torrey Cosgrove DAN THOEMKE/ERNIE GILBERT *** PARCEL INFO *** ZONE CODE: UA / Unassigned SUBDIVISION CODE: 420 / Storage Warehouse; 0 *** FEE SUMMARY *** Total Valuation Plan Review Fee Use Tax Permit Fee Extend Expired Permi Plan Review Addll ** TOTAL ** *** COMMENTS *** 170035 Exceed Electrical Contracting 017885 Lakewood Plumbing LLC 017885 Lakewood Plumbing LLC 190196 DT CONSTRUCT INC. USE: UA / Unassigned BLOCK/LOT#: 0 / ESTIMATED PROJECT VALUATION: FEES 0.00 11574.33 6,300.00 2,422.05 11211.03 120.00 11,627.41 300, 000.00 *** CONDITIONS *** All roughs to be done at Framing Inspection. Approved per plans and red -line notes on plans. Must comply with 2012 IBC, 2017 NEC and all applicable City of Wheat Ridge Municipal Codes. Work is subject to field inspections. **Prior to final inspection approval - As-builts are required before approval of the Building Final Inspection and Certificate of Occupancy can be issued. � ► 44" City of Wheat Ridge '/� Comm. Tenant Finish PERMIT - 201802415 PERMIT NO: 201802415 ISSUED: 10/04/2018 JOB ADDRESS: 3810 Pierce St EXPIRES: 03/02/2021 JOB DESCRIPTION: Demo of all non -load bearing interior partitions, fixtures and finishes; remodel interior to create three spaces; 3,375 sq f t ; l , 761 sq ft and 1,134 sq ft; 6,490 sq ft total Tenant: Well Beings Chiropractic **REVISION: Hanging hat channel and sheet rock in lieu of floating the existing CMU block wall. No added valuation. I, by my signature, do hereby attest that the work to be performed shall comply with all accompanying approved plans and specifications, applicable building codes, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with this�permrt. I further attest that I am leg ally authorized to include alI entities named within this document as parties to the work to be performed and that all work to be performed is disclosed in this document and/or its' accompanying approved plans and specifications. Signature of OWNER or CONTRACTOR (Circle one) Date 1, This permit was issued based on the information provided in the permit application and accompanying plans and specifications and is subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures. 2. This permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and received prior to the date of expiration. An extension of no more than 180, days made be granted at the discretion of the Chief Building Official and may be subject to a fee equal to one-half of the original permit fee. 3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard requirements, fees and��procedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of the Chief Building Official and is not guaranteed. 4. No work of any manner shall be performed that shall results in a change of the natural flow of water without prior and specific approval. 5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all requ�ired inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services Division. 6. The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, anviolation of any provision of any applicable code or any ordinance or regulation of this jurisdiction. Approval of work is subject to field inspection. Signature of Chief Building Official Date REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. From: no-reolv(alci.wheatridae.m. us To: CommDev Farm is Subject: Online Form Submittal: Commercial Interior Remodel/Tenant Finish Date: Thursday, June 25, 2020 10:21:50 AM Commercial Interior Remodel/Tenant Finish Application for Commercial Remodel/Tenant Finish This application is for Commercial Remodels and Tenant Finishes. Do not being work until the permit has been issued to the General Contractor. Required to Submit Proof of Submission to Fire Department Proof of Submission to West Metro Fire ADDroval.Ddf Fire Department Begin Application PROPERTY INFORMATION Property Address 3810 Pierce St Wheat Ridge CO 80033 Property Owner Name Jacob and Maura Fletcher Property Owner Phone 303-238-6500 Number (enter WITH dashes, eg 303-123- 4567) Property Owner Email mmheaveykidchiro@gmail.com Address Attach City of Wheat Electronic Payment Form - Revised 5-1-20 Ridge Electronic Fillable 202005011620013849 202006081141368198 Ddf Payment Form - "DO NOT ATTACH A PICTURE OF A CREDIT CARD" APPLICANT INFORMATION Contact Name of Graham Fetyko Person Submitting Application What is your role in the General Contractor project? Wheat Ridge Contractor's License Number (This is a 5 or 6 digit number for the City of Wheat Ridge) Contact Phone Number (enter WITH dashes, eg 303-123-4567) Contact Email Address for Plan Review Questions 190196 720-373-9605 dan@dtconstruct.com Retype Contact Email dan@dtconstruct.com Address DESCRIPTION OF WORK Is this for a new Yes tenant? Business Name of Well Beings Chiropractic Family Health Tenant Detailed Scope of Work - Provide a detailed description of work including mechanical, electrical, plumbing work occurring, adding/removing walls, etc Iii .M . STMO 7: Project was started by other contractor. Plumbing and electrical are partially roughed in, roughed in, framing is 90% complete, some drywall is up. Revised plans have new furnaces and condensers, added office in north east corner. New framed ceiling in corridor 3, 105 Entire building Square Footage Area 6490 of Work Being Performed Asbestos Report - If Field not completed. applicable Construction Plans stamo.odf scanned on 11 "x17" or larger Project Value (contract 420,000 value or cost of ALL materials and labor) SIGNATURE OF UNDERSTANDING AND AGREEMENT I assume full Yes responsibility for compliance with applicable City of Wheat Ridge codes and ordinances for work under any permit issued based on this application. I understand that work Yes may not begin on this property until a permit has been issued and posted on the property. I certify that I have Yes been authorized by the legal owner of the property to submit this application and to perform the work described above. I attest that everything Yes stated in this application is true and correct and that falsifying information in this application is an act of fraud and may be punishable by fine, imprisonment, or both. Person Applying for Dan Thoemke Permit Email not displaying correctly? View it in your browser. 0 Occupant Name Address Permit Number: Plan Type Pass Fail N/A Plan Review General West Metro Fire Protection District 433 S. Allison Pkwy, Lakewood, CO 80226 (303) 989-4307 Well Being Chiropractic Family Health (TI) 3810 Pierce Street Wheat Ridge, CO 80033 N/A Original Contractor: InspectionType: Inspection Date: Inspected By: DT Construct Inc. Plan Review - Tenant Improvement 6/25/2020 Mark Dean 303-989-4307 [x] [ ] [ ] G.30 REVIEW Yourplans have been approved. Follow this Link and the steps below to reconcile FEES: your in voice. 1. Select "Life Safety" under the Bill Type options #20062514501 2. Enter invoice number 3. Select the associated permit type from the "Permit/Fee Type" drop down menu 4. Select "Construction Permit" in the "WMFR Acct#" drop down menu 5. Enter the Job Address 6. Enter payment amount of $697.85 7. Select Pay by Card to complete the transaction Once completed, you are no longer required to send us a copy of your payment receipt. It is your responsibility to retain a copy for your records. Your payment will be processed within (1) business day after it was made and has posted to our Heartland account. Once payment has been confirmed, a link to the reviewed plans will be emailed to the contact listed on the permit. Please be sure to check your junk mail folder if you're anticipating a link email from our office. Your plans have been approved. Refer to the area above for further relevant information. West Metro Fire Rescue Life Safety Plan Review Desk Status: Approved City of `1Vheat dgc COMMUNITY DEVELOPMENT Building & Inspection Services Division 7500 W. 291' Ave., Wheat Ridge, CO 80033 Office: 303-235-2855 * Fax: 303-237-8929 Inspection Line: 303-234-5933 Email: perm its(a)-ci.wheatridge.co.us FOR OFFICE USE ONLY Date:�� Add to Permit # Zai S bV L/ /5 Building Permit Revision/Amendment Application *** Please complete all highlighted areas on both sides of this form. Incomplete applications may not be processed. I Property Address: l 4� Owner Phone: 36:3 Property Owner Email:\r) , kOn ', s t,�,� 0 rJt SC " 6-1 Mailing Address: (if different than property address) Address: 3�,, lo t,i-C 574. City, State, Zip:CO CCS S30v.$ 3 SubmittingCompany: C3 C -./-v L C -t-5 Contact Person: --Sir Phone: Contractor: C S Co -S ", v cx j Contractors City License #: j 7flb Phone: %aa y3 4— gjjo Contractor E-mail Address: 3 \0 " --kt .S1. ' Co CCS Please Note: Additional valuation must include all general and subcontracted work to be performed related to the revisions and/or amendments declared in the description of work and which were not included in the original permit valuation. If revisions or amendments increase the original valuation, additional fees will be due at the time of approval. Depending on the scope of work, additional plan review fees may be due upon approval ($60.00 an hour — 2 hour minimum). Description of revised/amended work: �1n i � <<„ l� Ww.�I S C7 L.J S4 (}`J' Cl C.i - C7 Sq. Ft./LF , Btu's Amps Squares Gallons Other Additional Project Value: (Must include all general and subcontracted work to be performed related to revisions/amendments described above) 5 OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record. that all measurements shown and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance with applicable City of Wheat Ridge codes and ordinances for work under any permit issued based on this application; that I am the legal owner or have been authorized by the legal owner of the property to perform the described work and am also authorized by the legal owner of any entity included on this application to list that entity on this application. CIRCLE ONE: (OWNER) (CONTRACTOR) or (AUTHORIZED REPRESENTATIVE) of (OWNER) (CONTRACTOR) C� PRINT NAIVE: J -� SIGNATIIRi DATE: 1 DEPARTMENT USE ONLY ZONING COMMMENTS: Reviewer BUILDING DEPARTMENT COMMENTS: Reviewer: [,;R461z� PUBLIC WORKS COMMENTS: Reviewer: PROOF OF SUBMISSION FORMS Fire Department ❑ Received ❑ Not Required Water District ❑ Received ❑ Not Required Sanitation District ❑ Received ❑ Not Required OCCUPANCY CLASSIFICATION: Building Division Valuation: $ We October 8, 2019 protect what matters DR JACOB AND MAURA FLETCHER most" 3810 PIERCE STREET WHEAT RIDGE, CO 80033 Re: 3810 PIERCE 3810 PIERCE STREET WHEAT RIDGE, CO 80033 Guarantee #: G2019-00008771 Dear Sir or Madam: Thank you for choosing a GAF EVERGUARD DIAMOND PLEDGE 20 Year Guarantee for your roofing system. We believe that you've made the best and safest choice to protect your property for years to come. We've enclosed the following items in this package: ❑ Your Guarantee - please keep this in your files. You'll need it in the unlikely event that there is ❑ a problem with your roof, or if you should sell the property. ❑ Scheduled Maintenance Checklists Booklet - provides you with suggested inspection checklists that you and your contractor can use for the life of your Guarantee - and beyond. Stop Sign - attach this sign to the main point of entry to your roof system. It helps remind other trades that may need to access the roof about the importance of being careful with your investment. Your contractor can provide you with more if needed. Sincerely, Guarantee Services Guarantee Services I 1 Campus Drive, Parsippany, NJ 07054 1 Toll Free 877.423.7663 1 MTGuarantee@GAF.cor A Stmldard 1NousTRIEs COMPANY ti oo O 0 O O O O. cm N 2 z W W WZ Ca o Cl cc U LLF W a C.0 w Q13 Q L ui J O CZ CC 16.2 Wa 2 MJ O z z 41 WC2Z a 2 D. LL LU Z 3 0 W U W a O m M zZ m LL O LU a Z w z N W cc CD N LL O O m LL O Cl) O 8 O U W 0 wW x w W F- !A W ccU W CL 0 00 i3 z J D m LL O y w 0 Z O Q U LL w a w LL O O m O L cc w z W O O m W O N m w w J a a Z O a 2 O U LL O W 0 �E pC ro C1Q i—. ° « N ai C co Zb �° O Z N �'c Y° N C U T'm6 U N Z o c C T �'_T. oL O a)= m ¢ =O' -w y. y E mC _o _c a33 roo ro vi «- om O o)»=m� Z=` c-- o L a) a) 3. N CN •• �U•C U'c C CO a) tea) -°mu1 r YCO� T Lro LO Fro 3 �`v1�w YU _ 41O =(6 .m. 3tY U% .r.Om �ro—i0 N O 0 Cl c 3 a E a) c _� ro m 2 c ° > �' ro n O - a O= o � E a) Y U) LL (D o �o n aim a ° a �v� 0 3m U o 3 X m n� o,ro = U 3 m `° m U o `-�-o _D of c c 2 ro af¢H ac co c n c c o »- U o = o CD c� �L a)— c� a) O a) CLO m N YEa) a)C c)m m a) Cm Mn LL-- av) Lm C� ofn X Oro. Z V)-0 yV v) U x, vi� c roro°' of oL nc E L - «�c0 ¢c o- ai mwcL w u) �� oLLE co u) °)m m t0 m °)Uro o. o x. 0 0 m C3 o vie L m o roa z `o rn3 pA< i 3 mo .9; a) a)0 'L.. ) ca Off: O= �N T ��Ufr-m0 0)V `jo O� 0-0C'No0 ¢ NNCc6 w0)C7"6 C.Na o CO.- C c"" c E d C i C._ O E N V) = ro0.`. J— c a) OLQ n"' N H' U) O n ro M . _ LL m Q. C 'R) a) :0 E O LL LL m E C m tS'C O LLL tC LCL F- ro N a1 a)5a } 3mm0 980 2T Np c > E=v'¢o) =n m °� ca) ¢¢Y o T- �°Lin TN ro cm J O oz Y N ro ia j c c L m o a)O.n N ro m o 0 E X00 m= > m ca o o N m L,ca c Z _ ro._ a E L m a L o ca o o L (M r- L c o0o p roam ca -- �� �a° Q a) m0--�a mL cm E� o�°r- LnLLo m Lo)(5o 00 a) 0c' U.E mm m o` c ro ECD >1 ° ma C3 a)—0 OL o =a COCc m® caa °) 0 o¢a .a r 0 a) o w c m % (D Cl 3 Y a n< LL m c a) a) i� a o= ca is U c m = N o 'c m o ° C7 c a) o� cn ro O c a) � O COZ¢ c ro (i to o cn V) V « N p m c) 6 O n m cpmLL O -E C 'co) 2 >, cc m aQ O o W OZ o m mz CL Lr-- QOu --a m o �- vTi C (D CO o m 0 °'q m e Eji a`) r- Z6 E E `a o 0 cL � a) 0< TC a 0 c� c �o cLi «¢ wro0 � �¢ EP m m Oma a) m¢ ca Oox mo=O(D y ¢� Xci� °mo as 0) U ro n-_ =3 ca E of > m o a) ro c m c Y O =° o)9 � w E om o ro o Ca E O 6) w ca y N ro w -00 CM 00E >°, 0-0 Q):3aci > `°�'cEc' c _cYo°) 'ro v=im�oEL U oY�T L/j�Lo �U) o nm ac mLL o d m c m n 0 `� y'ca O a) °.3 0 ¢ a = ca co c- c mo mL w0 0 o car c3a ~ m E nao a ¢ ca oro o ma axi E o E c a) m o `o m� O c o o ca c m= a) F- a m m mn - m0 CU -'.,c LLC3 00 gc c H a)n�--= o lY LL3 ca) Omo.3� a zLrLc croco e a 3 m c° m ¢ °t 0- a) ro .S ro O v axi t° = c LL a¢ c ';a > v m aoi c m m-ia a) ro ¢� o._ . L- o W=._ a) > C7 --F _rn0 �`m Y a) o Z o = ism =O._ cnw w -i m ° nro E nZ c ¢a da'3� d� T ro na O C UC= a T cn roU C'O ¢ a =OILL _ L N �Na)O) Q C N7oU a= m3LO U roroW Uro O i°lT .Cmro m o m TO LmYm NC_o Om NCO w NTN ¢W roa ()Or G a oUo a) is - mU ?� Om C "�O Wim•_ C V m ` Ntn ,L (ion C (j LC m >� EN—O e y o rno Cro m ro m �O c m cn inOC N o 0 aai °'� ro ro Y c o n o: o) c=a 3 a ¢ ro o 0 3¢O o f .ro Cl) E n nL E Y m = ro Z m L 'L-. O1tL � o o c ro ;Z = c m 0 c c m cn 0 a) w o m vi ¢ c �. o Y m g 0 U�= °= a o A r - o)o cn c vi o¢ o .� E ro m rno ca E N YLL m m o rn TB F o `o con ca a m mm Y._ o- mE -0 = c a) ro C0 w a m 3 c oro m 0 3 0 .�O o a) E U m =a o rn ° a) o m o m aa'i LL off m c E y e` LL wW c° c T o o a) L03L (n Y ro —m V) 9mm OE N m 0ca �n u) CCUOm nmU V)¢T O C!i a=Na) ®W¢ro= `N n LL in U m ro>n a) "a w a) 0 cL ac xTx m(7c = Omw LL o� ¢roc°�aoN ® EL a) me o Y.�m m� L Qm ca F ro m Um=W to LarojZo LL0 ^0c WZ¢3a >croE O�Oo o F- LT �f° � of a� n Oa) LO m r oo cN v aim 0o c) T V¢Q0C2 0CL roV)OmN U N°C (D CO cN _ O= O'CCrY'- Om Y--N� OQ LpOc°1'o ocaU m = �= n' =m E 0) O ro [C roa) = 00 L a'c v, OEY rn a) N`oim Lca p n mmo 0cri> T L0)n tai v3 a) �LLro� 0�ro- a)cd x 2occ m cmn oo c oo)orncrn m mT? w- oinc'- V yU o- (D a) L m 0E o� Y o m a)CA ca >.c o naro ro c =•-c o0. m o co'� C7U c >E m cpm O).- ro ro J 7 �, C � c n a) C cc) O U a) a) 'O C a ._ car C m = ro m u) L ._ C— O O) O C a) C F' m o= Y =— O a) ro E ° m `o O F- a 0 T o m a 3 LTw .- >_ a- cLn m m coE o F- u c m L Z W w a m ro a a) o m Oro LmtL w T0)� c Via) om mN °ro ° Lm = w c = u a) 3- Ow °'E y�L a v CU ~ ca ro c LY = w e -a) mLN oro L ro?cym�. Y onenn° wzcY c co LU -a p u�U� vo m 0 E mro ° mca oo)asE a=n a� io = 0>o,3=N LcF p ocm= =m n ron C? z m m= m LO °> cam _o °) v (n o c=i L vi ai `o 8",- 0 0 m T-0 a) > 0 - CC C W rn c '� O V ~O LL rn c m> C- =3 t o o ro c L v3 c c• -m o 0 o• -m' c_ c c m z ¢=ro c CC co > mg'rnLiw ro rocs Ec i _ c Yoa._ n =m mo �, roaLromc J =cro O} m rna)m'- a) -m D:Oc�c > 0mc¢ mo c mro rom m �Y E i= o=c croiN� )LLo°0 c. n0 Jo o-3ov) Nz0�0_mO3 oom N O) O a) O a ro E a O- m r -0 07� T C N T C 7 T L C'3 'La ca _ m._ L= L o� E `o ._ o v, x �¢ m o-- m LU 403 c° c ca c 0 rno CL o m= c + N y o m ro c o(D � n v, = 0 o U 3 L m ro o LL ow cLID vi 16 ° i O) L - ca O) f6 m O U ro m L .-- N rn a) ca 3 C v) v! O) - O C— 7 N LA: m ._ a z = LL c -� o L ro m 'O cEcot a a mo room cc 0 000 a°m ¢o mro m �0-=(3 c •cm= =mL W --Q) Ca m co a) enc E a) E m >' a o- m Y m ¢ c c c ¢ m ¢ a) ro a a) -a a9 0=oU m mm= Y c co mmo cn E� o - E3 00wooa U� men ca aoY o v) as E m w > o a n •c cc m w o e a) ro ro c c _ T� = ZU¢am m U nLa > J= as - 0cmcy c is = m E a)=ai afn Tom rn=U ro ¢ oro F - a) m 3 a)c Z-0 a) a) m m o . m ro E Tea E- m m c > m a'm LL0 c - LL 0 c w- cn (D as o) pwZ NQp 00) a) ma 7 > m � V m N a) u1 c D> m ro LL O y a) m O OO m L` E L C E Q m m 0)Q (a � O m V1 J m a) « Z N ro c= m LL > o._ ro= o a m = m CO = m'c4 c oar ¢LJ n L o %CY QE'c ro a ¢ roF- m ac 0 E o c ro m 3a n c =�° cam oy C7 c0 c m N a) c 0._ oo mF QZ= E O� w d W n =o c 'a-00LLm mo Tm g'c a 03 mcnm N mjO � m3Y wm c Uva¢ ca) y :-. a) C fa men„ ro C C ._ — ro a) C "' F- O) caa m o O a)=z ¢> �� m0 _ ro. E w o ° c a= Tm oc LL0-1-- a L m._1= 0 0 m.= a° COY C U aca t' YNO)0 L om'-=ro ro-- �L 0'-. YC } Z- a n aroc m 3wO tea) 0s=; ro=ro C7m0 c._ ocrn ao = L3 a`)¢ Z ca mo WJWt w mecca - c �-a m Z C 3 a) m N y m— amg Y-_ ro ro 0 0` N O 0)- Lu (D ='3._M MM v,0 a" men m n= = C a c is c O fn U L a cL n O 'o QcQuScJ a W ELL Nro mm a=Co �crn ¢a> 00m� auSY COLm viL o_'( c0 L1 0 ,6 O c- om0 0 v=ia' m 3' -mm x Ln¢o- c moo roc Lo mmo o` o cmc T— (n ca -3E0 LajLUU fro Uo a)L is m ca W o -'c E En a) F rn i� `o T m' c w o c c o o °° o c- ai cnZ-0o w o °) 02-1--, �a- J m a) o J = C3 ro L ro O U ro.= i0 1 0° roU To o xa y� E `o; -'--c a) cn O- D T m m Wa0 mZ m m Q«. m- c m m W E2 00� m L`moc ca C0' Qyo°C 000 0a)��ca� °°m cdo0 0,10 oc=om¢Uc w� o)or0 aLxyL�EO c`naroovoi� oC'lcc�ma ami �Lo c Ln} E o o E cC'3Q c c aac c m n=.-oLL u,m zm == co > t�t O E c) Ea o tA�eY a)� U= Cl)^ ca. E 5LL E i Z 'm Co Ca'F 0 w c o my wL E 0 ¢ m e y N v). m �w¢ nJ = 3 o E ro W om ca oa) Wa Z ami aroi To 0' TE cm, C E m� m o �C¢i o O 0 E a«ci'R) c �a c �`o c°`a cg o 3 m¢ LO a) Qw F_ c° n m c Ow¢ >F L E 3 � m ro qQ m N E) c a) d o OJ -LLQ._ m- m = w a), o c >Y a)- ca O)0) o m o a 0 E" m J o e rn m c ro a Zwo)t=o m a.�cawooLLroo 2� 0)0 oL LL -0 omm L>'cm me _�S ani > ro Y`m 2(5 mo'w U.W¢mW 0CZ m Lc O = a)C =U W �O¢=C a) v_) a) C a) N is mC a) a)° o O ¢ mN 0-v) Q �� Q) T> �._oo E N W 0 >'Z C'3 0- m n L U E_=' E (At `o o._ m o Y c (jL x m > mm a E ro Z �� cc c o F -Y W m a) Tc >. o a)Ly ° nvi Z.. o m a)^ a).,- o a) c ao c o'w Q =a o c Z¢Oy0 ca ° roL c cLn o ma w S�Nc C Nm"" tn0— Qrood^o c �Oc0j,« rn ro :.m am cTa3m '9._ pcCnc mann 3avS�...- 2Eo.._a m=oc o c� �cacaom cLWa)W moa a7 m ch ZL� ra) C Calf- m= mC¢ `01 Qro Gf�a _—U� mC OC mmOVIC V) u1'—C�Uc ci0 W'.'a)O)TT O¢J'=Cn NL=mC LLNCO- (� LL C7 =Q aro' � o W O mM nca o Vic ° c E Y `� ro =<0 C116 cam �m j 0 a°i � caLL y.E a m m o m o E m o ca Qv, m m ro� �U to m -6 QC7�LiZ c`a ° m 0 O� U O ro cal rn0 i O) Z E a) c fl m o ro a m= ro o° ro c J_ 0) a L: O = a) roc E E- o m o m e mc C- v rng Z m=_ ._ O N> o o m = W LL 002,00 0 za Q L ro o T= ` O °= T X CfL a (n d O c L 0 .S D ev� E o E o y c Y E CL 0A L <_¢^ c= Z> m o O1 cn F o n o Al'LL c ra m m} F- rnt > �a ¢ o U w ro o x0 c ro m LL _ m ro= O'- 3 ":-� U Z moo F -LL f -}(j OM O JF-¢ O m F- E o-0.? z = EL F- O t- C7 Y Ci F 00 - 3 LL c m m e d Q m CU ci W �:F r. �i ri v o 0 o c L m e O c m c- < N A i CITY OF WHEAT RIDGE _1�9rBuilding Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type: Ly Q y'- F—f n CL( Fl� 0 o Job Address: (a) 0 P e rce_ s� Permit Number: a2/go / 0 30 I P no -P _ Azo r --o cerl- Ca it - L, ✓i G, f` r" e, ❑ No one available for inspection: Time `� = { AM/ Re-Inspection required: Yes No When corrections have been made, call for re -inspection at 303-234-5933 + 1 Date: 9 Inspector: '"EIS DO NOT REMOVE THIS NOTICE A i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: r� C_ Job Address: r Qt_ Permit Number: U 10 _r') kA ! S o/Cn V ❑ No one available for inspection: Time ' AM/PM Re -Inspection required: Yes No When corrections have been made, schedule for re -inspection online at: http://www. cL wheatridge. co. uslinspection Date: 1 (�•'),) • �� Inspector: DO NOT REMOVE THIS NOTICE i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: 3 °'r� ke-&"`) Li r le(l. Job Address: 7 I ® i'i er (G S Permit Number: -d0I F° d V ! S ❑ No one available for inspection: Time AM/PM Re -Inspection required: Yes When corrections have been made, schedule for re -inspection online at: h ttp✓/www. ci. wheatridge. co. uslinspection Date: (0 -K -P Inspector: DO NOT REMOVE THIS NOTICE i CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type: 0 r =t w n � , Job Address: 7S2 ! � V r c C Permit Number: cl c-) 1-2 U L -i t S` Ai ❑ No one available for inspection: Time AM/PM Re -Inspection required: Yes No ¢„ When corrections have tteenade, call for re inspection at 303-234-5933 Date: c Inspector: DO NOT REMOVE THIS NOTICE i UTY.DF WHEAT RIDGE Building, Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type:Yfi Job Address: g--- Permit Number: s ❑ No one available for inspection: Time,/4&2_(A PM Re -Inspection requirede: Yes )No When corrections have been made, ifor re -inspection at 303-234-5933 k Date ��° Inspecb I DO NOT REMOVE THIS NOTICE 1 It � I i CITY OF WHEAT RIDGE _:�9�Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type: Job Address: Permit Number: c)Q 1 _� 0'_ 111 cl- Vol ❑ No one available for inspection: Time AM/PM Re -Inspection required: ;;Fes No When corrections have been made, call for re -inspection at 303-234-5933 Dater - � � (_ Inspector: DO NOT REMOVE THIS NOTICE i CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type: Job Address:_2 10 Permit Number: -4- t� 4)WN--ci ? C niv ❑ No one available for inspection: Time AM/PM Re -Inspection required: Ns, When corrections have been made, call for re -inspection at 303-234-5933 Date:---), i CU • i t Inspector: DO NOT REMOVE THIS NOTICE i CITY OF WHEAT RIDGE Building Inspection -®!vision (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type: Fti f=- Job Address: `+.1 L .Yrs C' 'L- ,-7 Permit Number: 0c i �*o one available for inspection: Time = AM/PM l Re -Inspection required: Yes No When corrections have been made, call for re -inspection at 303-234-5933 Inspector: DO NOT REMOVE THIS NOTICE i CITV OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type: In 1d ' o 0-,r Job Address: 3 g )O r erce + Permit Number: "d' a 1 q 0 /0 30 ❑ No one available for inspection: Time 1i = D) OPM Re -Inspection required: Yes When corrections have been made, call for re -inspection at 303 -234 - Date: S:LO'djel Inspector: _T_Jb\ DO NOT REMOVE THIS NOTICE r City of Wheat Ridge Commercial Roofing PERMIT - 201901030 PERMIT NO: 201901030 ISSUED: 05/21/2019 JOB ADDRESS: 3810 Pierce St EXPIRES: 05/20/2020 JOB DESCRIPTION: Commercial re -roof disposing of old roof and replacing with TPO flat roof system, including EPS foam taper system. 60 mil GAF Everguard TPO finishing. Coated edge metals per manufacturer&#39;s specs. *** CONTACTS *** OWNER (303)990-7713 FLETCHER MAURA & JACOB SUB (303)600-8696 LAWRENCE KERR 110274 FORMULA ROOFING *** PARCEL INFO *** ZONE CODE: UA / Unassigned USE: UA / Unassigned SUBDIVISION CODE: 420 / Storage Warehouse; 0 BLOCK/LOT#: 0 / *** FEE SUMMARY *** ESTIMATED PROJECT VALUATION: 74,500.00 FEES Total Valuation 0.00 Use Tax 1,564.50 Permit Fee 930.80 ** TOTAL ** 2,495.30 *** COMMENTS *** *** CONDITIONS *** In order to pass a final inspection on commercial elastomeric or similar type roofing, a letter of inspection and approval from the manufacturer technical representative stating that "the application of the roof at (project address) has been applied in accordance with the installation instruction for (roof material brand name) roof covering" is required to be on site at the time of final inspection. Effective December 1, 2014, asphalt shingle installations require an approved midroof inspection, conducted when 25-75 percent of the roof covering is installed, prior to final approval. Installation of roof sheathing (new or overlay) is required on the entire roof when spaced or board sheathing with ANY gap exceeding one half inch exists. Sheathing and Mid -roof inspections may be called in at the same time, 100 percent of the sheathing must be complete and 25-75 percent of the midroof may be complete. Asphalt shingles are required to be fastened to the roof deck with a minimum of 6 nails per shingle. A ladder extending 3 feet above the roof eave and secured in place is required to be provided for all roof inspections. Roof ventilation is required to comply with applicable codes and/or manufacturer installation instructions, whichever is more stringent. 1► � w e City of Wheat Ridge Commercial Roofing PERMIT - 201901030 PERMIT NO: 201901030 ISSUED: 05/21/2019 JOB ADDRESS: 3810 Pierce St EXPIRES: 05/20/2020 JOB DESCRIPTION: Commercial re -roof disposing of old roof and replacing with TPO flat roof system, including EPS foam taper system. 60 mil GAF Everguard TPO finishing. Coated edge metals per manufacturer&#39;s specs. I, by my signature, do hereby attest that the work to be performed shall comply with all accompanying approved plans and specifications= applicable building codes, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with this permit. I further attest that I am legally authorized to include alI entities named within this document as parties to the work to be performed and t� all work toperrmesdisclosed in this document and/or its' accompanying approved plans and specifications. 2,/// Signature of OtNEI(Jor CONTRACTOR (Circle one) Date 1. This permit was issued based on the information provided in the permit application and accompanying plans and specifications and is subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures. 2. This permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and received prior to the date of expiration. An extension of no more than 180 days made be granted at the discretion of the Chief Building Official and may be subject to a fee equal to one-half of the original permit fee. 3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard requirements, fees androcedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of the Chief Budding Official and is not guaranteed. 4, No work of any manner shall be performed that shall results in a change of the natural flow of water without prior and specific approval. 5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all required inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services V,NIV,I. 6_ T ' uance or gr ng of a permit shall not be construed to be a permit for, or an approval of, an violation of any provision of any abl code or ordinance or regulation of this jurisdiction. Approval of work is subject to field inspection. Signature of Chief Building Official Date REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. City of W heat. I icigc ( O NA N,W N I I Y D I VI W l' 1v1 E N I (— Building & Inspection Services 7500 W. 2911 Ave., Wheat Ridge, CO 80033 Office: 303-235-2855 * Fax: 303-237-8929 Inspection Line: 303-234-5933 Email: permits(o-)ci.wheatridge.co.us I FOR OFFICE USE ONLY I Date: -5/3-f /�� Plan/Permit # rw Plan Review Fee. Building Permit Application *** Complete all applicable highlighted areas on both sides of this form. Incomplete applications may not be processed. *** Property Address: 0-1 S Property Owner (please print): \ \ O_cGb Phone: q `i0 Property Owner Email: Tenant Name (Commercial Projects Only) Property Owner Mailing Address: (if different than property address) Address: Citv. State. Zi Arch itect/Engineer: Architect/Engineer E-mail: Phone: Contractor Name: City of Wheat Ridge License #: ! ri �� �' Phone: 3C ' CcC) o 4 Contractor E-mail Address: C; For Plan Review Questions & Comments (please print): CONTACT NAME (please print): Phone: 0 'Z, cl L(� r� CONTACT EMAIL(p/ease print): fir,'rn vow. I L (' <cy ✓-­" Sub Contractors (Must provide Wheat Ridge License No & Signed Subcontractor Authorization form): Electrical: Plumbing: Mechanical: W.R. City License # W.R. City License # W.R. City License # Other City Licensed Sub: Other City Licensed Sub: City License # City License # Complete all highlighted fields. [.COMMERCIAL ❑ RESIDENTIAL Provide description of work: For ALL projects, provide a detailed description of work to be performed, including current use of areas, proposed uses, square footage, existing condition and proposed new condition, appliance size and efficiency, type and amount of materials to be used, etc. Sq. Ft./LF U %'r BTUs A) EPS mow. TuPe-�- tt par Lf'7 sky -N, 00 Coo,4-ec( edy � Gallons Iy Amps A] �� Squares '4 6 For Solar: Vfl KW f _# of Panels _Requires Structural For Commercial Projects Only: Occupancy Type: Construction Type: Occupancy Load: Square Footage: _ Project Value: (Contract value or the cost of all materials and labor included in the entire project) OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance with applicable City of Wheat Ridge codes and ordinances for work under any permit issued based on this application; that I am the legal owner or have been authorized by the legal owner of the property to perform the described work and am also authorized by the legal owner of any entity included on this application to list that entity on this application. I, the applicant for this building permit application, warrant the truthfulness of the information provided on the application. CIRCLE ONE: (OWNER) (CONTRACTOR) or (AUTHORIZED REPRESENTATIVE) of (OWNER) (CONTRACTOR) Signature (first and last name): DATE: Printed Name: ZONING COMMMENTS: Reviewer: BUILDING DEPARTMENT COMMENTS: Reviewer: PUBLIC WORKS COMMENTS: Reviewer: DEPARTMENT USE ONLY OCCUPANCY CLASSIFICATION: CONSTRUCTION TYPE: Building Division Valuation: i CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type: t7 �l - Q u h, F� �`� 4 o t► J. -17-� -,L Job Address: Permit Number:S-- 4 (61 ❑ No one available for inspection: Time q = �1 `3 &PM Re -Inspection required: Yes �» When corrections have been made, call for re -inspection at 303-234-5933 Date: '3 11 Li -inspector: `77I5 DO NOT REMOVE THIS NOTICE i CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type: cr_ Job Address: f' Permit Number: r-? a R ❑ No one available for inspection: Time -'Y M Re -Inspection required: Yes When corrections have been made,, for re -inspection at 303-234-5933 Date'—inspect DO NOT REM E THIS NOTICE i CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type: Job Address: �_�r�% I t_l'a PermitNumber: I e St Q re S<_:� o re c c/ e- i- � r ❑ No one available for inspection: Time 9 = V '7 MM Re -Inspection required:e� No When corrections have been made, call for re -inspection at 303-234-5933 Date: /,q Inspector:_ - F -b DO NOT REMOVE THIS NOTICE s_ CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type: �' ^' �' ` V"'(C / i' Job Address: 3 1 P- c c 5 �� Permit Number: ;N ❑ No one available for inspection: Time AM/PM Re -Inspection required: i&es' No When corrections have been made, call for re -inspection at 303-234-5933 Date: �-` ► ` Inspector: DO NOT REMOVE THIS NOTICE - - City of Wheat Ridge Comm. Tenant Finish PERMIT -201802415 PERMIT NO: 201802415 ISSUED: 10/04/2018 JOB ADDRESS: 3810 Pierce St EXPIRES: 10/04/2019 JOB DESCRIPTION: Demo of all non -load bearing interior partitions, fixtures and finishes; remodel interior to create three spaces; 3,375 sq ft;1,761 sq ft and 1,134 sq ft; 6,490 sq ft total Tenant: Well Beings Chiropractic *** CONTACTS *** FEES Total Valuation OWNER (303)238-6500 FLETCHER MAURA & JACOB 1,574.33 Use Tax GC (303)359-8337 Lance Nading 170675 C3 Construction Services SUB (303)720-5345 Adam Stockton 170035 Exceed Electrical Contracting SUB (303)233-7007 Torrey Cosgrove 017885 Lakewood Plumbing LLC SUB (303)233-7007 Torrey Cosgrove 017885 Lakewood Plumbing LLC *** PARCEL INFO *** ZONE CODE: UA / Unassigned USE: UA / Unassigned SUBDIVISION CODE: 420 / Storage Warehouse; 0 BLOCK/LOT#: 0 / *** FEE SUMMARY *** ESTIMATED FEES Total Valuation 0.00 Plan Review Fee 1,574.33 Use Tax 6,300.00 Permit Fee 2,422.05 ** TOTAL ** 10,296.38 *** COMMENTS *** PROJECT VALUATION: 300,000.00 *** CONDITIONS *** All roughs to be done at Framing Inspection. Approved per plans and red -line notes on plans. Must comply with 2012 IBC, 2017 NEC and all applicable City of Wheat Ridge Municipal Codes. Work is subject to field inspections. **Prior to final inspection approval - As-builts are required before approval of the Building Final Inspection and Certificate of Occupancy can be issued. City of Wheat Ridge Comm. Tenant Finish PERMIT - 201802415 PERMIT NO: 201802415 ISSUED: 10/04/2018 JOB ADDRESS: 3810 Pierce St EXPIRES: 10/04/2019 JOB DESCRIPTION: Demo of all non -load bearing interior partitions, fixtures and finishes; remodel interior to create three spaces; 3,375 sq ft;1,761 sq ft and 1,134 sq ft; 6,490 sq ft total Tenant: Well Beings Chiropractic I, by my signature, do hereby attest that the work to be performed shall comply with all accompanying approved plans and specifications, applicable building codes, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with this perfopermit. I further attest that I am leggally authorized to include alI entities named within this document as parties to the work to be r work tg b p rto ed is disclosed in this document and/or its' accompanying approved plans and specifications. O /t Signature of VWT;VR or CONTRACTOR (Circle one) Date 1. This permit as issued based on the information provided in thepermit application and accompanying Flans and specifications and is subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures. 2. This permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and received prior to the date of expiration. An extension of no more than 180 days made be granted at the discretion of the Chief Building Official and may be subject to a fee equal to one-half of the originalpermit fee. 3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard requirements, fees androcedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of Official Chief Building Ocial and is not guaranteed. 4. No work of any manner shall be performed that shall results in a changeof the natural flow of water without prior and specific approval. 5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all required inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services Division. 6. The issuance or granting of a permit shall riot be construed to be a permit for, or an approval of, an violation of any provision of any applicable code or any or ce or regul i n of this jurisdiction. Approval of work is subject to field inspection. /" /X"t*_ .__ - Signature of Chief Building Official a Date REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. City of' �Wh6at ldg C(OIMMMUNiTy DEVELOPMENT Building & Inspection Services Division 7500 W. 29th Ave., Wheat Ridge, CO 80033 Office: 303-235-2855 * Fax: 303-237-8929 Inspection Line: 303-234-5933 Email: permits(o)-ci.wheatridge.co.us FOR OFFICE USE ONLY Date: 2 / J Plan/Permit #�l�j CCC Plan Review Fee: 7 JlJ �-12 Building Permit Application *** Please complete all highlighted areas on both sides of this form. Incomplete applications may not be processed. *** Property Address: 3810 Pierce Street Property Owner (please print): MU ,r o.d S -b �� ����nea- Phone: 3 o 3 2384S"00 Property Owner Email: A C 1 o,_cr)�C'-) W elk Vi c \.r.1 .ySCV,.r o ra.0--l+, r- , c_o...,.. Tenant (Commercial Projects Only) W Property Owner Mailing Address: (if different than property address) Address: City, State, Zip: Arch itectlEIng 1neer: Micheal Sickbert, Sickbert & Associates Arch itectlEng1neer E-mail: Mike@SABoulder.com Phone: 303-443-1585 Contractor Name: C 3 City of Wheat Ridge License #: i 7 0 � TS Phone: 3:,30 L13 Lt - ,�i a69 Contractor E-mail Address: . Coy"-. For Plan Review Questions & Comments (please print): CONTACT NAME (please print): Mike Sickbert Phone: 303-443-1585 CONTACT EMAIL(p/ease print): Mike@SABoulder.com Sub Contractors (Must provide Wheat Ridge License No.): Electrical: Plumbing: Mechanical: W.R. City License # 1 app 3 5 W.R. City License #0 J-3 9 SS W.R. City License # O l -f 8 'cd S Other City Licensed Sub: Other City Licensed Sub: City License # City License # XI COMMERCIAL ❑ RESIDENTIAL Description of work: For ALL projects, provide a detailed description of work to be performed, including current use of areas, proposed uses, square footage, existing condition and proposed new condition, appliance size and efficiency, type and amount of materials to be used, etc. Interior remodel of existing 6,490 SF. building to house three separate medical service tenants. Work includes demolition of nearly all non -load bearing interior partitions, fixtures and finishes. Building is currently vacant, previous occupant was Summit Center Medical Health Services (Occupancy Group B), so no change in occupancy. Sq. FULF 6,490 BTUs Amps Squares Gallons Commercial Projects Only: Occupancy Type: B Construction Type: III -B Occupancy Load: 64 Project Value: (Contract value or the cost of all materials and labor included in the entire project) OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEME: �f I hereby certify that the setback distances proposed by this permit application are accurate regulations of the City of Wheat Ridge or covenants, easements or restrictions of record, tl accurate; that I have read and agree to abide by all conditions printed on this application ar with applicable City of Wheat Ridge codes and ordinances for work under any permit issu( or have been authorized by the legal owner of the property to perform the described work entity included on this application to list that entity on this application. I, the applicant for truthfulness of the information provided on the application. CIRCLE ONE: (OWNER) (CO CTOR) or (AUTHORIZED REPRESENTAT.% Signature (first and last —naame). I Printed Name. �1 DEPARTMENT USE ZONING COMMMENTS: Reviewer: BUILDING DEPARTMENT COMMENTS: i Reviewer. 1 CAfuNIM�GF�,PGi,�s OAC) PUBLIC WORKS COMMENTS: 31 Sf le :. 110 i M"k wv TENA I - 3 37) 5 &) Q 312 Z 114-71SM I. P T&AqP1T 1134 CZ) zt. l & LNIJY, q'1 Reviewer: -1 K-1� �� Building Division Valuation: �A� PROFICIENT E N G I N E E R I N G September 18, 2018 City Of Wheat Ridge Community Development ATTN: Mr. Randy Slusser & Mr. Mike Theisen RE: Plan Check No: 201802415 Dear Sirs; In reference to the above plan check, we provide the following responses to accompany our updated drawings. All changes are clouded as Revision #1 on the drawings. Mechanical Provide energy documentation for mechanical system and equipment. (COMCheck mechanical compliance certificate) Engineer's Respo e. ee new drawing M-0.5 for full mechanical compliance certificate information. Plumbing - / �� �` 2. No Comments, Engineer's Response: Acknowledged. Electrical 3. Provide available Fault current calculations at all equipment in the electrical distribution,system Engineer's Response: A Fault Current Schedule has been added to drawing E-0.2/0 �& 4. Provide code references and length of conductors for Tapped service entrance conductors Engineer's Response: See new Keynote 1 on drawing E-0.2. V' d 5. Provide detailed information and specs for the wireway referenced on Sheet E-0.2 Engineer's Response: See new Keynote 2 on drawing E-0.2. /0 A m 7/#. Please contact me if you have any further questions regarding this matter. �pero Ll ar Re g •' h. ARM Brian Armenta I PE, LEED AP Proficient Engineering, Inc. I Electrical 6991 Peachtree Industrial Boulevard, Building 700, Peachtree Corners, GA 30092 - P: 404.330.9798 proficientengineering.com Occupant Name: Address: Permit Number: Plan Type Pass Fail N/A West Metro Fire Protection District 433 S. Allison Pkwy, Lakewood, CO 80226 (303) 989-4307 Well Being Chiropractic Family Health 3810 Pierce Street Wheat Ridge, CO 80033 N/A Original Plan Review General [x] [ ] [ ] G.30 REVIEW FEES: Contractor: InspectionType: Inspection Date: Inspected By: Haystack Construction Plan Review - Tenant Improvement 8/27/2018 Wayne Keith 303-989-4307 Your plans have been approved. Follow this Link and the steps below to reconcile your invoice. 1. Select "Life Safety" under the Bill Type options 2. Enter invoice number #18082714501 3. Select the associated permit type from the "Permit/ Fee Type" drop down menu 4. Select "Construction Permit" in the "WMFR Acct#" drop down menu 5. Enter the Job Address 6. Enter payment amount of $487.85 7. Select Pay by Card to complete the transaction Once completed, send a copy of the invoice Here Once confirmation of payment is received by our office, a no-reply@mobile-eyes.com email will be sent with a link to the approved plans and permit card, with instructions for printing. Your plans have been approved. Refer to the area above for further relevant information. West Metro Fire Rescue Life Safety Plan Review Desk Status: Approved 5httir—e SICKBERT & ASSOCIATES 5375 Pennsylvania Ave. Boulder, Colorado 80303 303.443.1585 September 19, 2018 Mr. Randy Slusser — Wheat Ridge Building Department Re: Tenant Finish, 3810 Pierce St. Plan Check #: 201802415 Dear Randy: In response to your plan review comments dated 9/10/2018, we offer the following; Archi ectural 'NlSite plan, van accessible parking space details and location have been added to sheet SP -1. There are 1 existing sparking spaces on this site which per ANSI l 17.1 requires a total of 1 van accessible space. ® Suite numbers for the individual tenants are indicated on sheet LS -1. Suite #1, #2 & #3. X We will advise the Owner regarding the requirement for obtaining a business license from the City prior r to final inspection. Mechanical & Electrical See attached stamped review comments from the project's mechanical engineer. All plan changes are identified as revision 1 Best Regards, Micheal J. Sickbert Sickbert & Associates Attachments: (2) Copies - Sheets SP -1, LS -1, M-0.5 & E-0.2, Revision 1 dated 9/18/2018 Stamped Engineering Review Comments i k Crity0l m r Wheat is 70 - PLAN REVIEW COMMENTS Project Description: Tenant Finish Project Address: 3810 Pierce St. Plan Check No.: 201802415 Permit App. Date: 8/31/18 Applicant: Jeremy Bennett Phone: 720-434-8269 Plan Checker: Randy Slusser, Mike Theisen (Electrical) Phone: 303-235-2803 Plan Checker email: rslusser(a)ci.wheatridge.co.us, mtheisen(@ci.wheatridge.co.us The project plans were reviewed for compliance with the following codes and standards: 2012 IBC, 2012 IRC, 2012 IMC, 2012 ECC, 2017 NEC, 2012 IPC, 2009 ANSI/ICC, City of Wheat Ridge Amendments • TO EXPEDITE PROJECT APPROVAL: Please provide a written response indicating how and where each comment was resolved on the plans. • Resubmit all previously reviewed plans, updated plans and supporting documents with each subsequent review. • For clarification of any plan review comment, please call or email the plan checker listed above. 9/10/18 Architectural 1. Specify and show on plan number of accessible parking spaces. Provide minimum of 1 van accessible space. 2. Specify suite numbers for each tenant. 3. Informational Only: Each tenant will require a business license from the City of Wheat Ridge prior to final inspection. Mechanical 4. Provide energy documentation for mechanical system and equipment.(COMCheck mechanical compliance certificate) Plumbing 5. No Comments Electrical 6. Provide available Fault current calculations at all equipment in the electrical distribution system 7. Provide code references and length of conductors for Tapped service entrance conductors 8. Provide detailed information and specs for the wireway referenced on Sheet E-0.2 4FARMER ENWRO►NMENTAL wvvw.farmereg.com GROUP July 19, 2018 Jeremy Bennett Haystack Construction 3615 S Huron St #201 Englewood, CO 80110 RE: Asbestos -Containing Building Materials Survey 3810 Pierce St, Wheat Ridge, Colorado Farmer Project No. 3996.03 Dear Mr. Bennett. �I&J�.415 Farmer Environmental Group, LLC (Farmer) performed the limited asbestos -containing building material survey of the commercial building (Site) located at 3810 Pierce St, Wheat Ridge, Colorado for asbestos -containing building materials (ACBM) on July 16 and 17, 2018. Colorado Department of Public Health and Environment (CDPHE)-licensed Asbestos Inspectors Kurt Pierce (License #14063) and Mark Brady (License #23494) conducted this survey under an agreement between Farmer and Haystack Construction. The purpose of the survey was twofold: 1) determine locations and conditions of asbestos -containing products at the Site; and 2) assist in obtaining the necessary building permits with the State of Colorado in accordance with Colorado Regulation #8. The following non -friable asbestos products were identified at the site: 11 CKY O V4bes% FOP 8120 Sheridan Blvd , Ste A306 • Westminster. CO 800113. Ottice 303 468 8763 Asbestos Material Description Quantity Location Content Small Restroom off Dining Room and • Brown Adhesive on Pink Tile 224 SF 2% Chrysotile Office Rest Room walls. • 9"x 9" Gray Floor Tile 63 SF 3% Chrysotile Storage / Vault Floor Storage / Vault Floor • 9"x9" Brown Floor Tile 63 SF 10% Chrysotile (under Gray Tile) 11 CKY O V4bes% FOP 8120 Sheridan Blvd , Ste A306 • Westminster. CO 800113. Ottice 303 468 8763 3810 Pierce St, Wheat Ridge, Colorado Asbestos Report July 19, 2018 Page 2 • . s The. following cont ins trace asbestos, upon point count analysis, this material is not regulated by EPA or CDP'YiE. Material Description Quantity Asbestos Content Location Small Restroom off Dining Room and • Green Mosaic Floor Tile 96 SF o <1% Chrysotile Adhesive Office Rest Room Floors. All accessible areas within the Site were viewed and suspect materials touched by the inspector to determine the location, condition, and friability of observed asbestos material. All bulk samples were submitted for PLM analysis. When suspect material was initially sighted, bulk samples were usually collected. By definition, a homogeneous area means an area of surfacing material, thermal system insulation material, or miscellaneous material that is uniform in color and texture and is installed within the same period. Farmer has had extensive experience with older buildings that have been abated during demolition or renovation projects. Occasionally, additional asbestos was discovered during demolition of concealing ceiling, wall, or flooring materials. Sample analysis reported as "None Detected" should be interpreted as meaning no asbestos was observed in the suspect material above the reliable limit of detection, (I% by visual estimation) for the PLM method. The following materials did not contain asbestos: • Smooth Plaster • Smooth Texture over Drywall • Black Covebase with White Adhesive • Knockdown Texture • 12"x12" Green and White Floor Tile with Yellow Adhesive • CMU Sealant • Teal Carpet with Yellow Adhesive • Tan Tile with White Grout and White Adhesive • FRP Adhesive • Pink Tile with white Grout • White FRP Adhesive • Green 12"x12" Ceramic Tile and Brown Grout • HVAC Duct Sealant • Black Mastic on 9"x 9" Gray Floor Tile • Black Mastic on 9"x 9" Brown Floor Tile (under Gray 9 x 9 tile) • Green Mosaic Floor Tile Grout �. Drywall beneath Plaster a. FARM ER GROUP 3810 Pierce St, Wheat Ridge, Colorado Asbestos Report July 19, 2018 Page 3 Any product containing more than I% fibrous asbestos, when analyzed by PLM, is considered a potential hazard by the Environmental Protection Agency (EPA). PLM is the EPA -recognized method for determining fibrous bulk asbestos content. Additionally, the EPA indicates that further analysis by point counting be performed to confirm asbestos content for friable materials found to contain less than ten percent asbestos by visual area estimation. Point counting analysis may be omitted if the material is assumed to contain more than one percent asbestos and is then handled accordingly. All samples collected by Farmer were analyzed by EMSL Analytical, Inc.'s NVLAP-accredited laboratory in Denver, Colorado. Sample locations are presented in Appendix I. The PLM Report in Appendix II indicate the results of PLM analysis for bulk samples collected in the scheduled demolition areas. The PLM Report shows the room or area in which the sample was collected and provides a description of the sampled material. Based on observations made at the Site, and results of the analysis of bulk samples collected during the survey, Farmer recommends the following: Collect additional bulk samples from previously concealed materials that may be revealed during demolition activity, or from materials outside the original survey scope of work. "Suspect" material includes any material serving as a sprayed -on or troweled -on acoustic or fireproofing surface; floor and ceiling tiles; transite panels, siding or shingles; thermal insulation or any material associated with mechanical systems; or any binding agent such as tar sealant, mastic adhesive, roofing tar, caulking, et cetera. Colorado Regulation #8 requires bulk samples in public buildings be collected by a licensed Asbestos Inspector. 2. Friable ACBM that is in good condition and is not disturbed does not require additional action. However, if the friable material becomes disturbed, or is in poor condition, then stabilization measures need to be taken. No friable materials observed during this investigation require stabilization at this time. 3. If ACBM are to be removed or disturbed as part of renovation/demolition activities the ACBM should be removed under abatement conditions before renovation begins. 4. According to Colorado Regulation #8, CDPHE must be notified for all demolitions of all facilities and all asbestos abatement projects that exceed the trigger levels, whatever is the lesser quantity. The notification requirements apply to both friable and non -friable asbestos materials. Notifications must be postmarked or delivered at least 10 working days before initiating abatement activities, and must be made using CDPHE forms. Forms can be obtained by contacting the CDPHE Asbestos Notification and Information Section at 303- 692-3100 or online through the CDPHE website at www.cdphe.state.co.us. 5. If any material cannot be positively identified as non -asbestos -containing by the analytical results of samples collected during this inspection, it should be treated as asbestos until a sample of the newly identified suspect material can be collected and analyzed by PLM. city of 6. The building owner should be aware that removing ACBM does not discharge ownersp. During transport or after burial in an EPA -approved landfill, any contamination through uNVheat Ridge the lifetime of the material remains the responsibility of the building owner. ng FARMER ENVIRONMENTAL GROUP 3810 Pierce St, Wheat Ridge, Colorado Asbestos Report July 19, 2018 Page 4 Farmer has endeavored to inspect the existing conditions within the affected areas using CDPHE inspection protocols. Regardless of the thoroughness of a survey, it is possible that some areas containing asbestos were overlooked or inaccessible. This report presents general descriptions of various construction materials and the general locations where these materials were encountered. If questions arise during the planning for renovation, demolition or other construction, Farmer should be notified to permit us to review the situation and present recommendations. This report has been prepared on behalf of and exclusively for the use of Haystack Construction. The conclusions expressed by Farmer regarding the conditions of the site are based solely on the observations made on July 16 and 17, 2018, the data collected during this survey, and the laboratory results of the samples collected and analyzed. The beneficiaries are hereby advised that conditions observed are subject to change. This report and the findings contained herein shall not, in whole or in part, be disseminated or conveyed to any other party or be used or relied upon by any other party, in whole or in part, without Haystack Construction' or Farmer's prior written consent. Farmer appreciates this opportunity to provide asbestos consulting services to Haystack Construction. We have enjoyed working with you on this project and look forward to meeting your needs in the future. Should any questions arise concerning this report, please contact us at (303) 468-8763. Sincerely, Mark Brady CDPHE Building Inspector #23494 Farmer Environmental Group, LLC FARMER GROUP APPENDIX I TABLES AND FIGURES 3810 Pierce St, Wheat Ridge, Colorado Asbestos Report July 19, 2018 Page 5 city of Wheat Ridge ENYIRONN L% GROUP Data Summary Table 3810 Pierce St, Wheat Ridge, Colorado Homogeneous Application Material Description Sample ID Friable Type TSM Condition Future Condition Comments HA -1 Plaster Smotth A 18175 Yes S Good Renovation Snack bar, E wall -4' from S HA -1 Plaster Smotth A 18176 Yes S Good Renovation Work Area E wall T from N / hallway, 4'up HA -1 Plaster Smotth A 18177 Yes S Good Renovation Refi orator Room, W wall, 4' from N wall, 5'up HA -1 Plaster Smotth A 18178 Yes S Good Renovation Boiler Room, S wall, 4' from E wall, 5'up HA -1 Plaster Smotth A 18179 Yes S Good Renovation Closet, W wall, 2' from N wall, 4'up HA -1 Plaster Smotth A 18180 Yes S Good Renovation Office Restroom, S wall, 4' from W wail, 5' u HA -1 Plaster Smotth A 18181 Yes I S Good I Renovation Hallway N of Office E wall 8' from N wall, 5'up HA -2 Texture with Drywall smooth A 18182 Yes S Good Renovation Work Area W wall 10' from N wall 4'up HA -2 Texture with Drywall smooth A 18183 Yes S Good Renovation Rec Room W wall, 6' from S wall 4' u HA -2 Texture with Drywall smooth A 18184 Yes S Good Renovation Pantry, N wall, T from E wall, 4'up HA -2 Texture with Drywall smooth A 18185 Yes S Good Renovation Dining Room, N wall, 8' from E, Sup HA -2 Texture with Drywall smooth A 18186 Yes S Good Renovation Reception, S wall, 8' from E wall, 5'up HA -3 Black covebase w/ white adhesive A 18187 No M Good Renovation Work area S wall 4' from W wall HA -3 Black covebase w/ white adhesive A 18188 No M Good Renovation E Hall 4' from W wall HA -3 Black covebase w/ white adhesive A 18189 No M Good Renovation Restroom Hall, E wall 2' from N wall HA -4 Texture w Drywall knockdown A 18190 Yes S I Good Renovation Work Area E wall HA -4 I Texture w Drywall knockdown A18191 Yes S Good Renovation Janitor Hall way, S wall HA -4 Texture w Drywall knockdown A18192 Yes S Good Renovation Menns Restroom, W wall, behind door HA -4 Texture w Drywall knockdown A18193 Yes S Good Renovation Computer Lab Closet, N wall HA -4 Texture w Drywall knockdown A18194 Yes S Good Renovation Snack Bar W wall HA -4 Texture w Drywall knockdown A18195 Yes S Good Renovation Dining Room outside RR hall Q IGtchen S wall HA -4 Texture w Drywall knockdown A18196 Yes S Good Renovation Rec Room, S wall at Closet HA -5 12x12 Floor tile, Green & White w/ Yellow adhesive A 18197 N M Good I Renovation Dining Room, E wall of snack bar, 1' from W wall, 15' from S wall HA -5 12x12 Floor tile, Green & White w/ Yellow I adhesive A 18198 N I M Good Renovation Restroom Hall, 7' from E wall, S wall HA -5 12x12 Floor tile, Green & White w/ Yellow adhesive A 18199 N M Good Renovation E Exit wall, 1' from S wall, T from W wall HA -5 12x12 Floor tile, Green & White w/ Yellow adhesive A 18200 N M Good Renovation E Exit hall, 6' from W, 1' from S wall HA -6 CMU Sealant A 18201 Yes S Good Renovation Work Area, Stub wall, at reception entrance @ S wall HA -6 CMU Sealant A 18202 Yes S Good Renovation Rec Room closet, N wall HA -6 CMU Sealant A 18203 Yes S I Good Renovation Pantry, S wall HA -6 CMU Sealant A 18204 Yes S Good Renovation Dining Room computer lab door, S wall HA -6 CMU Sealant A 18205 Yes S Good Renovation Dining Room Sw Comer near storage room HA -6 CMU Sealant A 18206 Yes S Good Renovation Dining Room @ comer of 2 offices HA -6 CMU Sealant A 18207 Yes S Good Renovation Dining Room, S of Reception near hallway HA -7 Teal Carpet w/ Yellow adhsive 1 A 18208 No S GoodRenovation Work Area, 4' from W, 6' from N HA -7 Teal Carpet w/ Yellow adhsive A 18209 No S Good Renovation Computer Lab, 2' from S wall, T from E wall HA -7 Teal Carpet w/ Yellow adhsive I A 18210 No S Good Renovation ISW office, 1' from N wall, 2' from W wall HA -7 Teal Carpet w/ Yellow adhsive I A 18211 No S Good I Renovation I Rec Room 6' from W wall 8' from N wall Fanner Environmental Group, Inc. March 26, 2018 Data Summary Table 3810 Pierce St, Wheat Ridge, Colorado Homogeneous Application Material Descriptio Sample ID Friable Type T S,M Condition Future Condition Comments HA -8 Tan tile with White grout and white adhesive A 18212 No M Good Renovation Women's Room, N wall 2 1/2' from W wall, 5'up HA -8 Tan tile with White grout and white adhesive A 18213 No M Good Renovation Men's Room, E wall, T from N wall 5'up HA -9 FRP Adhesive A 18214 No M Good Renovation Kitchen, N wall, —3' from W wall HA -9 FRP Adhesive A 18215 No M Good Renovation Kitchen, S wall, — 4' from E wall HA -10 Pink tile w/ white grout and brown adhesive A 18217 No M Good Renovation Restroom, W wall, T from S wall, 4'up HA -10 Pink tile w/ white grout and brown adhesive A 18218 No M Good Renovation Restroom, W wall, T from S wall, 4'up HA -11 White FRP adhesive A 18219 No M Good Renovation Dishwasher, W wall HA -11 White FRP adhesive A 18220 No M Good Renovation Kitchen, S wall @ doorway HA -12 Green 12x12 Floor Tile A 18221 No M Good Renovation Women's Room, 2' from E wall at door HA -12 Green 12x12 Floor Tile A 18222 No M Good Renovation Men's Room, 2' from W wall at door HA -13 HVAC Duct Sealant A 18223 Yes M Good Renovation Dishwasher Ductwork HA -13 HVAC Duct Sealant A 18224 Yes M Good Renovation Kitchen ofice, ductwork HA -14 9x9 gray floor tile over 9x9 brown floor tile with black mastic A 18225 No M Good Renovation Storage / vault, 2' from W wall, 2' from S wall HA -14 9x9 gray floor tile over 9x9 brown floor tile I with black mastic A18226 No M Good Renovation Storage / vault, 4' from N wall, 2' from E wall HA -15 Green mosaic floor the grout A 18227 No M Good Renovation RR, W wall HA -15 Green mosaic floor the grout A 18228 No M Good Renovation Office RR, at door HA -16 Green mosaic floor tile adhesive A 18229 No M Good Renovation RR, W wall HA -16 Green mosaic floor tile adhesive A 18230 No M Good Renovation Office RR, at door HA -17 Drywall behind plaster A 18231 Yes M I Good Renovation Work Area, E wall T from N / hallway, 4'up T=TSI, S=Surfacin , M=Miscellaneous Farmer Environmental Group, Inc. March 26, 2018 City of VVheat Ridge Bulk Sample Location 3810 Pierce St Wheatridge, CO _ A 18207 A 18181 A 18210 A 18210 Non-ACBM A 18210 ACBM A 18208 A 18183 A 18190\ I A 18211 / Music EX -1 EX -2 Conference Work Area/ Admin Unit II Room ----_A 18201 A 18182 A 1821 Server I A 18187 A 18197 A 1821 A 18194 / / A 18227, A 181� A 91 A 18175 A 18231231 � RIR Stor 8229 -177 Reception Snack Bar A 18191 � A 18214 A 18186 Dining Room A 18 20 A 18185 A 18198 A 18212A 181 9 Kitchen A 18206 A 18192 A 181 9 A 18215 Office A 1822 A 18205 A 18239---A 18204Ld k L filer / Office Computer Lab storage N 0 m' m m A 18196 -A 18199 A 18188 A 18200 A 18177 A 18219 �A 18223 A 18184 Storage m� RIR —A 18224 El A 18178 A 18203 A 18180 A 18226 A 18225 A 18209 A 18193 A 18222 1 A 18221 A 18213 A 18195 Farmer Environmental Group 3996.03 APPENDIX II BULK SAMPLE ANALYSIS 3810 Pierce St, Wheat Ridge, Colorado Asbestos Report July 19, 2018 Page 6 City of wheat Ridge 14FARMER ENVIRONMENTAL CROUP �0EMSL Analytical, Inc. 1010 Yuma Street Denver, CO 80204 Tel/Fax: (303) 740-5700 / (303) 741-1400 _ hftp://www.EMSL.com / denverlab@emstcom EMSL Order: 221805286 Customer ID: FARM50D Customer PO: Project ID: Attention: Jennifer Day Phone: (303) 468-8763 Farmer Environmental Group, LLC Fax: 8120 Sheridan Blvd Received Date: 07/17/2018 12:00 PM Suite A306 Analysis Date: 07/17/2018 - 07/19/2018 Westminster, CO 80002 Collected Date: 07/17/2018 Project: 3810 Pierce St./ 3996.03 Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-931116 Method using Polarized Light Microscopy A18179 -Skim Coat Plaster (Smooth) White/Beige 30% Gypsum None Detected Non -Fibrous 70% Non-fibrous (Other) 2218052860005 Heterogeneous Non -Asbestos Asbestos Sample Description Appearance % Fibrous % Non -Fibrous % Type A18175 -Skim Coat Plaster (Smooth) White 5% Ca Carbonate None Detected 221805286-0005A Non -Fibrous 95% Non-fibrous (Other) 221805286-0001 Gray Homogeneous None Detected At 8175 -Plaster Plaster (Smooth) White 5% Ca Carbonate None Detected Non -Fibrous 95% Non-fibrous (Other) 5% Ca Carbonate 2218052860001A Homogeneous 20% Gypsum A18176 -Skim Coat Plaster (Smooth) Tan/White 5% Ca Carbonate None Detected Non -Fibrous 95% Non-fibrous (Other) Beige 2218052860002 None Detected Heterogeneous Non -Fibrous 15% Gypsum Inseparable paint / coating layer included in analysis 221805286-0006A Homogeneous 80% Non-fibrous (Other) A18176 -Plaster Plaster (Smooth) White 5% Ca Carbonate None Detected Non -Fibrous Non -Fibrous 95% Non-fibrous (Other) 2218052860007 221805286-0002A 75% Non-fibrous (Other) Homogeneous Inseparable paint /coating layerincluded in analysis A18177 -Skim Coat Plaster (Smooth) White/Beige 10% Ca Carbonate None Detected None Detected Non -Fibrous 20% Gypsum 2218052860003 Homogeneous Heterogeneous 70% Non-fibrous (Other) Inseparable paint/ coating layer included in analysis A18177 -Plaster Plaster (Smooth) Beige <1% Hair 5% Ca Carbonate None Detected Fibrous 20% Gypsum 221805286-0003A Homogeneous 75% Non-fibrous (Other) A18178 -Plaster Plaster (Smooth) Tan/Beige <1% Hair 5% Ca Carbonate None Detected Fibrous 20% Gypsum 2218052860004 Heterogeneous 75% Non-fibrous (Other) Inseparable paint / coating layer included in analysis A18179 -Skim Coat Plaster (Smooth) White/Beige 30% Gypsum None Detected Non -Fibrous 70% Non-fibrous (Other) 2218052860005 Heterogeneous Inseparable paint/ coating layer included in analysis At 8179 -Plaster Plaster (Smooth) White 30% Gypsum None Detected Non -Fibrous 70% Non-fibrous (Other) 221805286-0005A Homogeneous A18179 -Concrete Plaster (Smooth) Gray 10% Ca Carbonate None Detected Non -Fibrous 90% Non-fibrous (Other) 2218052860005e Homogeneous A18180 -Skim Coat Plaster (Smooth) White/Beige 5% Ca Carbonate None Detected Non -Fibrous 20% Gypsum 2218052860006 Heterogeneous 75% Non-fibrous (Other) Inseparable paint/coating layer included in analysis A18180 -Plaster Plaster (Smooth) Beige 5% Ca Carbonate None Detected Non -Fibrous 15% Gypsum 221805286-0006A Homogeneous 80% Non-fibrous (Other) A18181 -Skim Coat Plaster (Smooth) White/Beige 5% Ca Carbonate None Detected Non -Fibrous 20% Gypsum 2218052860007 Heterogeneous 75% Non-fibrous (Other) Inseparable paint /coating layerincluded in analysis A18181 -Plaster Plaster (Smooth) Beige 5% Ca Carbonate None Detected Non -Fibrous 15% Gypsum 2218052860007A Homogeneous 80% Non-fibrous (Other) Initial report from: 07/19/2018 13:33:02 ASS -PLM -0008-0001 - 1.78 Printed: 7/19/2018 11:33 AM Page 1 of 8 EMSL Analytical, Inc. EMSL Order: 221805286 Customer ID: FARM50D 1010 Yuma Street Denver, CO 80204 Customer PO: Tel/Fax: (303) 740-5700 / (303) 741-1400 http://www.EMSL.com / denverlab@emsl.com Project ID: Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-931116 Method using Polarized Light Microscopy A18183 -Drywall Texture w/ Drywall Brown/White 15% Cellulose Non -Asbestos Asbestos Sample Description Appearance % Fibrous % Non -Fibrous % Type A18182 -Drywall Texture w/ Drywall Brown/Tan/White 15% Cellulose 70% Gypsum None Detected (Smooth) Fibrous 15% Non-fibrous (Other) None Detected 221805286-0008 Heterogeneous 80% Non-fibrous (Other) None Detected Inseparable paint/coating layer included in analysis Heterogeneous Non -Fibrous 80% Non-fibrous (Other) A18183 -Texture Texture w/ Drywall White/Beige 20% Ca Carbonate None Detected (Smooth) Non -Fibrous 80% Non-fibrous (Other) None Detected 221805286-0009 Heterogeneous 15% Non-fibrous (Other) Inseparable paint / coating layer included in analysis Homogeneous A18183 -Drywall Texture w/ Drywall Brown/White 15% Cellulose 70% Gypsum None Detected (Smooth) Fibrous 15% Non-fibrous (Other) Fibrous 221805286-0009A Homogeneous 2218052860011A A18184 -Texture Texture w/ Drywall Tan/White 20% Ca Carbonate None Detected (Smooth) Non -Fibrous 80% Non-fibrous (Other) None Detected 221805286-0010 Heterogeneous Non -Fibrous 80% Non-fibrous (Other) Inseparable paint/ coating layer included in analysis 221805286-0012 Homogeneous A18184 -Drywall Texture w/ Drywall Brown/White 15% Cellulose 70% Gypsum None Detected (Smooth) Fibrous 15% Non-fibrous (Other) 221805286-OOIOA Homogeneous A18185 -Texture Texture w/ Drywall White 20% Ca Carbonate None Detected (Smooth) Non -Fibrous 80% Non-fibrous (Other) Brown/White 15% Cellulose 221805286-0011 Homogeneous (Smooth) Inseparable paint/coating layer included in analysis 20% Non-fibrous (Other) 221805286-00128 A18185 -Drywall Texture w/ Drywall Brown/White 15% Cellulose 65% Gypsum None Detected (Smooth) Fibrous 20% Non-fibrous (Other) 2218052860011A Homogeneous A18186 -Texture Texture w/ Drywall White 20% Ca Carbonate None Detected (Smooth) Non -Fibrous 80% Non-fibrous (Other) 221805286-0012 Homogeneous A18186 -Mesh Texture w/ Drywall Pink 95% Glass 5% Non-fibrous (Other) None Detected (Smooth) Fibrous 221805286-0012A Homogeneous A18186 -Drywall Texture w/ Drywall Brown/White 15% Cellulose 65% Gypsum None Detected (Smooth) Fibrous 20% Non-fibrous (Other) 221805286-00128 Homogeneous A18187 -Cove Base Black Cove Base w/ Black 30% Ca Carbonate None Detected White Adhesive Non -Fibrous 70% Non-fibrous (Other) 2218052860013 Homogeneous A18187 -Mastic Black Cove Base w/ Beige 30% Ca Carbonate None Detected White Adhesive Non -Fibrous 70% Non-fibrous (Other) 221805286-0013A Homogeneous A18188 -Cove Base Black Cove Base w/ Black 15% Ca Carbonate None Detected White Adhesive Non -Fibrous 85% Non-fibrous (Other) 2218052860014 Homogeneous A18188 -Mastic Black Cove Base w/ Beige 30% Ca Carbonate None Detected White Adhesive Non -Fibrous 70% Non-fibrous (Other) 221805286-0014A Homogeneous A18189 -Cove Base Black Cove Base w/ Black 100% Non-fibrous (Other) None Detected White Adhesive Non -Fibrous 2218052860015 Homogeneous A18189 -Mastic Black Cove Base w/ Tan 100% Non-fibrous (Other) None White Adhesive Non -Fibrous 221805286-0015A Homogeneous 01 A18190 -Texture Texture w/ Drywall White/Beige (Knockdown Stomp) Non -Fibrous 221805286-0016 Heterogeneous Inseparable paint/coating layer included in analysis 20% Ca Carbonate None Detected 80% Non-fibrous (Other)Whet Ridge Initial report from: 07/19/201813:33:02 ASG, YLAI 008 0001 - 1.7E Printed: 7/19/2018 11:33 AM Page 2 of 8 EMSL Analytical, Inc. EMSLOrder: 221805286 Customer ID: FARM50D 1010 Yuma Street Denver, CO 80204 Customer PO: Tel/Fax: (303) 740-5700 / (303) 741-1400 http://www.EMSL.com / denverlab@emsl.com Project ID: Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-931116 Method using Polarized Light Microscopy A18192 -Drywall Texture w/ Drywall Brown/White 15% Cellulose Non -Asbestos Asbestos Sample Description Appearance % Fibrous % Non -Fibrous % Type A18190 -Drywall Texture w/ Drywall Brown/White 15% Cellulose 70% Gypsum None Detected A18193 -Texture (Knockdown Stomp) Fibrous 15% Non-fibrous (Other) None Detected 22180528&0016A (Knockdown Stomp) Homogeneous 80% Non-fibrous (Other) A18191 -Texture Texture w/ Drywall Tan/White 20% Ca Carbonate None Detected Inseparable paint / coating layer included in analysis (Knockdown Stomp) Non -Fibrous 80% Non-fibrous (Other) A18193 -Tape 221805286-0017 Tan 95% Cellulose Heterogeneous None Detected Inseparable paint / coating layer included in analysis Fibrous 20% Non-fibrous (Other) A18191 -Drywall Texture w/ Drywall Brown/White 15% Cellulose 70% Gypsum None Detected A18193 -Joint (Knockdown Stomp) Fibrous 15% Non-fibrous (Other) None Detected 22180528&0017A (Knockdown Stomp) Homogeneous 80% Non-fibrous (Other) A18192 -Texture Texture w/ Drywall TanM/hite 20% Ca Carbonate None Detected 221805286-00198 (Knockdown Stomp) Non -Fibrous 80% Non-fibrous (Other) 221805286-0018 Texture w/ Drywall Heterogeneous 70% Gypsum None Detected Inseparable paint/ coating layer included in analysis (Knockdown Stomp) Fibrous 15% Non-fibrous (Other) A18192 -Drywall Texture w/ Drywall Brown/White 15% Cellulose 70% Gypsum None Detected (Knockdown Stomp) Fibrous 15% Non-fibrous (Other) 221805286-0018A Homogeneous A18193 -Texture Texture w/ Drywall Tan/White 20% Ca Carbonate None Detected (Knockdown Stomp) Non -Fibrous 80% Non-fibrous (Other) 221805286-0019 Heterogeneous Inseparable paint / coating layer included in analysis A18193 -Tape Texture w/ Drywall Tan 95% Cellulose 5% Non-fibrous (Other) None Detected (Knockdown Stomp) Fibrous 20% Non-fibrous (Other) 221805286-0019A Homogeneous A18193 -Joint Texture w/ Drywall White 20% Ca Carbonate None Detected Compound (Knockdown Stomp) Non -Fibrous 80% Non-fibrous (Other) 221805286-0022 Homogeneous 221805286-00198 A18193 -Drywall Texture w/ Drywall Brown/White 15% Cellulose 70% Gypsum None Detected (Knockdown Stomp) Fibrous 15% Non-fibrous (Other) 221805286-0019C Homogeneous A18194 -Texture 1 Texture w/ Drywall White 20% Ca Carbonate None Detected (Knockdown Stomp) Non -Fibrous 80% Non-fibrous (Other) 221805286-0020 Homogeneous Inseparable paint/coating layer included in analysis A18194 -Texture 2 Texture w/ Drywall White 20% Ca Carbonate None Detected (Knockdown Stomp) Non -Fibrous 80% Non-fibrous (Other) 221805286-0020A Homogeneous Inseparable paint/ coating layer included in analysis A18194 -Drywall Texture w/ Drywall Brown/White 15% Cellulose 65% Gypsum None Detected (Knockdown Stomp) Fibrous 20% Non-fibrous (Other) 221805286-0020e Homogeneous A18195 -Texture Texture w/ Drywall White 20% Ca Carbonate None Detected (Knockdown Stomp) Non -Fibrous 80% Non-fibrous (Other) 221805286-0021 Homogeneous Inseparable paint/ coating layer included in analysis A18195 -Drywall Texture w/ Drywall Brown/White 15% Cellulose 65% Gypsum None Detected (Knockdown Stomp) Fibrous 20% Non-fibrous (Other) 221805286-0021A Homogeneous A18196 -Texture Texture w/ Drywall White 20% Ca Carbonate None Detected (Knockdown Stomp) Non -Fibrous 80% Non-fibrous (Other) 221805286-0022 Homogeneous Inseparable paint / coating layer included in analysis A18196 -Drywall Texture w/ Drywall Brown/White 15% Cellulose 65% Gypsum None Detected (Knockdown Stomp) Fibrous 20% Non-fibrous (Other) 221905286-0022A Homogeneous Initial report from: 07/19/2018 13:33:02 ASB_PLM_0008_0001 - 1.78 Printed: 7/19/2018 11:33 AM Page 3 of 8 EMSL Analytical, Inc. EMSL Order: 221805286 Customer ID: FARM50D 1010 Yuma Street Denver, CO 80204 Tel/Fax: (303) 740-5700 / (303) 741-1400 Customer PO: hftp://www.EMSL.com / denverlab@emsl.com Project ID: Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-931116 Method using Polarized Light Microscopy A18201 -Sealant CMU Sealant White Non -Asbestos Asbestos Sample Description Appearance %, Fibrous %, Non -Fibrous %, Type A18197 -Floor Tile Floor Tile, 12x12, Green 35%u Ca Carbonate None Detected Inseparable paint/ coating layer included in analysis Green + White w/ Non -Fibrous 65%u Non-fibrous (Other) A18201 -CMU 221805286-0023 Yellow Glue Homogeneous None Detected A18197 -Mastic Floor Tile, 12x12, Yellow 100% Non-fibrous (Other) None Detected Green + White w/ Non -Fibrous A18201 -Mortar 221805286-0023A Yellow Glue Homogeneous None Detected Al 8198 -Floor Tile Floor Tile, 12x12, White 35% Ca Carbonate None Detected Green + White w/ Non -Fibrous 65% Non-fibrous (Other) A18202 -Sealant 221805286-0024 Yellow Glue Homogeneous None Detected A18198 -Mastic Floor Tile, 12x12, Yellow 100% Non-fibrous (Other) None Detected Green + White w/ Non -Fibrous A18202 -Brick 221805286-0024A Yellow Glue Homogeneous None Detected A18199 -Floor Tile Floor Tile, 12x12, Green 100% Non-fibrous (Other) None Detected Green + White w/ Non -Fibrous A18203 -Sealant 221805286-0025 Yellow Glue Homogeneous None Detected A18199 -Mastic Floor Tile, 12x12, Tan 100% Non-fibrous (Other) None Detected Green + White w/ Non -Fibrous Inseparable paint /coating layer included in analysis 221805286-0025A Yellow Glue Homogeneous All 8200 -Floor Tile 1 Floor Tile, 12x12, Green 35% Ca Carbonate None Detected Green + White w/ Non -Fibrous 65% Non-fibrous (Other) 221805286-0026 Yellow Glue Homogeneous A18200 -Mastic 1 Floor Tile, 12x12, Black/Yellow 100% Non-fibrous (Other) None Detected Green + White w/ Non -Fibrous 221805286-0026A Yellow Glue Heterogeneous Inseparable black and yellow mastics A18200 -Floor Tile 2 Floor Tile, 12x12, White 35% Ca Carbonate None Detected Green + White w/ Non -Fibrous 65% Non-fibrous (Other) 221805286-00269 Yellow Glue Homogeneous A18200 -Mastic 2 Floor Tile, 12x12, Black/Yellow 100% Non-fibrous (Other) None Detected Green + White w/ Non -Fibrous 221805286-0026c Yellow Glue Heterogeneous Inseparable black and yellow mastics A18201 -Sealant CMU Sealant White 100% Non-fibrous (Other) None Detected Non -Fibrous 221805286-0027 Homogeneous Inseparable paint/ coating layer included in analysis A18201 -CMU CMU Sealant Gray/Various 10% Ca Carbonate None Detected Non -Fibrous 90% Non-fibrous (Other) 221805286-0027A Homogeneous A18201 -Mortar CMU Sealant Gray 20% Ca Carbonate None Detected Non -Fibrous 80% Non-fibrous (Other) 221805286-00279 Homogeneous A18202 -Sealant CMU Sealant White 100% Non-fibrous (Other) None Detected Non -Fibrous 221805286-0028 Homogeneous A18202 -Brick CMU Sealant Red 100% Non-fibrous (Other) None Detected Non -Fibrous 221805286-0028A Homogeneous A18203 -Sealant CMU Sealant White 100% Non-fibrous (Other) None Detected Non -Fibrous 221805286-0029 Heterogeneous Inseparable paint /coating layer included in analysis , A18203 -CMU CMU Sealant Gray/Various Non -Fibrous 221805286-0029A 10% Ca Carbonate ' NoOlDelected 90% Non-fibrous (Other) A18203 -Mortar CMU Sealant Gray 20% Ca Carbonate etected Non -Fibrous 80% Non-fibrous (Other) p"I'Son 221805286-00299 Homogeneous Uj�ding Initial report from: 07/19/2018 13:33:02 ASf3- PLM, 0U08 0;;01 - 1.78 Printed: 7/19/2018 11:33 AM Page 4 of 8 EMSL Analytical, Inc. EMSLOrder: 221805286 Customer ID: FARM50D 1010 Yuma Street Denver, CO 80204 Customer PO: Tel/Fax: (303) 740-5700 / (303) 741-1400 40- http://www.EMSL.com / denverlab@emsl.com Project ID: Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy Initial report from: 07/19/201813:33:02 ASB—PLM-0008-0001 - 1.78 Printed: 7/19/2018 11:33 AM Page 5 of 8 Non -Asbestos Asbestos Sample Description Appearance % Fibrous %, Non -Fibrous % Type A18204 -Sealant CMU Sealant White/Green 100% Non-fibrous (Other) None Detected Non -Fibrous 221805286-0030 Heterogeneous A18204 -CMU CMU Sealant Gray/Various 10%u Ca Carbonate None Detected Non -Fibrous 90% Non-fibrous (Other) 221805286-0030A Homogeneous A18204 -Mortar CMU Sealant Gray 15% Ca Carbonate None Detected Non -Fibrous 85% Non-fibrous (Other) 221805286-0030e Homogeneous A18205 -Sealant CMU Sealant White 100% Non-fibrous (Other) None Detected Non -Fibrous 221805286-0031 Homogeneous A18205 -Brick CMU Sealant Red 100% Non-fibrous (Other) None Detected Non -Fibrous 221805286-0031A Homogeneous A18205 -Mortar CMU Sealant Gray 100% Non-fibrous (Other) None Detected Non -Fibrous 221805286-00318 Homogeneous A18206 -Sealant CMU Sealant White 100% Non-fibrous (Other) None Detected Non -Fibrous 221805286-0032 Homogeneous A18206 -CMU CMU Sealant Gray 100% Non-fibrous (Other) None Detected Non -Fibrous 221805286-0032A Homogeneous A18207 -Sealant CMU Sealant White 100% Non-fibrous (Other) None Detected Non -Fibrous 221805286-0033 Homogeneous A18207 -Brick CMU Sealant Red 100% Non-fibrous (Other) None Detected Non -Fibrous 221805286-0033A Homogeneous A18208 -Carpet Carpet + Yellow Blue/Green 80%u Synthetic 15% Ca Carbonate None Detected Adhesive Fibrous 5% Non-fibrous (Other) 221805286-0034 Homogeneous A18208 -Adhesive Carpet + Yellow Yellow 100% Non-fibrous (Other) None Detected Adhesive Non -Fibrous 221805286-0034A Homogeneous A18209 -Carpet Carpet + Yellow Blue/Green 80%u Synthetic 15% Ca Carbonate None Detected Adhesive Fibrous 5% Non-fibrous (Other) 221805286-0035 Homogeneous A18209 -Adhesive Carpet + Yellow Yellow 100% Non-fibrous (Other) None Detected Adhesive Non -Fibrous 2218052860035A Homogeneous A18210 -Carpet Carpet + Yellow Green 90% Synthetic 10% Non-fibrous (Other) None Detected Adhesive Fibrous 221805286-0036 Homogeneous A18210 -Adhesive Carpet + Yellow Tan 100% Non-fibrous (Other) None Detected Adhesive Non -Fibrous 221805286-0036A Homogeneous A18211 -Carpet Carpet + Yellow Blue/Green 80% Synthetic 15%n Ca Carbonate None Detected Adhesive Fibrous 5% Non-fibrous (Other) 221805286-0037 Homogeneous A18211 -Adhesive Carpet + Yellow Black/Yellow 100% Non-fibrous (Other) None Detected Adhesive Non -Fibrous 221805286-0037A Heterogeneous Inseparable black and yellow adhesives Initial report from: 07/19/201813:33:02 ASB—PLM-0008-0001 - 1.78 Printed: 7/19/2018 11:33 AM Page 5 of 8 EMSL Analytical, Inc. EMSL Order: 221805286 Customer ID: FARM50D 1010 Yuma Street Denver, CO 80204 Tel/Fax: (303) 740-5700 / (303) 741-1400 Customer PO: http://www.EMSL.com / denverlab@emsl.com Project ID: Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-931116 Method using Polarized Light Microscopy Non -Asbestos Sample Description Appearance % Fibrous % Non -Fibrous Asbestos % Type A18212 -Ceramic Tile Tan Tile + Grout White 100% Non-fibrous (Other) None Detected Non -Fibrous 221805286-0038 Homogeneous A18212 -Grout Tan Tile + Grout White 15% Ca Carbonate None Detected Non -Fibrous 85% Non-fibrous (Other) 221805286-0038A Homogeneous A18212 -Mastic Tan Tile + Grout Tan/Beige 35% Ca Carbonate None Detected Non -Fibrous 65% Non-fibrous (Other) 221805286-00386 Homogeneous A18212 -Mud Tan Tile + Grout White 20% Ca Carbonate None Detected Non -Fibrous 80% Non-fibrous (Other) 221805286-00380 Homogeneous A18212 -Drywall Tan Tile + Grout Brown/White 15% Cellulose 70% Gypsum None Detected Fibrous 15% Non-fibrous (Other) 221805286-0038D Homogeneous A18213 -Ceramic Tile Tan Tile + Grout White/Beige 100% Non-fibrous (Other) None Detected Non -Fibrous 221805286-0039 Homogeneous A18213 -Mastic Tan Tile + Grout Beige 100% Non-fibrous (Other) None Detected Non -Fibrous 221805286-0039A Homogeneous A18213 -Mud Tan Tile + Grout White 100% Non-fibrous (Other) None Detected Non -Fibrous 221805286-00398 Homogeneous A18213 -Caulk Tan Tile + Grout White 100% Non-fibrous (Other) None Detected Non -Fibrous 221805286-0039C Homogeneous A18214 -Paneling FRP Adhesive White 35% Glass 20% Ca Carbonate None Detected Fibrous 45% Non-fibrous (Other) 221805286-0040 Homogeneous A18214 -Adhesive FRP Adhesive Yellow 25% Ca Carbonate None Detected Non -Fibrous 75% Non-fibrous (Other) 221805286-0040A Homogeneous A18215 -Paneling FRP Adhesive White 15% Glass 85% Non-fibrous (Other) None Detected Fibrous 221805286-0041 Homogeneous A18215 -Adhesive FRP Adhesive Tan 100% Non-fibrous (Other) None Detected Non -Fibrous 221805286-0041A Homogeneous A18217 -Ceramic Tile Pink Tile + Grout White/Pink 100% Non-fibrous (Other) None Detected Non -Fibrous 221805286-0042 Homogeneous A18217 -Grout Pink Tile + Grout White 20% Ca Carbonate None Detected Non -Fibrous 80% Non-fibrous (Other) 221805286-0042A Homogeneous A18217 -Mastic Pink Tile + Grout Tan 98% Non-fibrous (Other) 2% Chrysotile Non -Fibrous 221805286-00428 Homogeneous A18218 -Ceramic Tile Pink Tile + Grout White/Pink 100% Non-fibrous (Other) None Detected Non -Fibrous 221805286-0043 Homogeneous A18218 -Mastic Pink Tile + Grout Tan Non -Fibrous 221805286-0043A A18218 -Grout Pink Tile + Grout White Non -Fibrous 221805286-00438 Initial report from: 07/19/2018 13:33:02 98% Non-fibrous (Other) .26/6 Chrysotile 100% Non-fibrous (Other) 1 None DeteAed RSB., PLM_ 0008 0001 - 1Js Printed: 7/19/2018 11:33 AM Page 6 of 8 EMSL Analytical, Inc. EMSL Order: 221805286 Customer ID: FARM50D 1010 Yuma Street Denver, CO 80204 Customer PO: Tel/Fax: (303) 740-5700 / (303) 741-1400 http://www.EMSL.com / denverlab@emsl.com Project ID: Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-931116 Method using Polarized Light Microscopy Initial report from: 07/19/2018 13:33:02 ASB—PLM-0008-0001 - 1.78 Printed: 7/19/2018 11:33 AM Page 7 of 8 Non -Asbestos Asbestos Sample Description Appearance % Fibrous % Non -Fibrous % Type A18219 -Paneling White FRP Adhesive White 30% Glass 25% Ca Carbonate None Detected Fibrous 45% Non-fibrous (Other) 221805286-0044 Homogeneous A18219 -Adhesive White FRP Adhesive Beige 30% Ca Carbonate None Detected Non -Fibrous 70% Non-fibrous (Other) 221805286-0044A Homogeneous A18220 -Adhesive White FRP Adhesive White 100% Non-fibrous (Other) None Detected Non -Fibrous 221805286-0045 Homogeneous Inseparable paint /coating layer included in analysis A18221 -Ceramic Tile Green Tile + Grout Brown/Green 100% Non-fibrous (Other) None Detected Non -Fibrous 221805286-0046 Homogeneous A18221 -Grout Green Tile + Grout Gray 15% Ca Carbonate None Detected Non -Fibrous 85% Non-fibrous (Other) 221805286-0046A Homogeneous A18221-Thinset Green Tile + Grout Gray 15% Ca Carbonate None Detected Non -Fibrous 85% Non-fibrous (Other) 221805286-00468 Homogeneous A18222 -Ceramic Tile Green Tile + Grout Tan/Green 100% Non-fibrous (Other) None Detected Non -Fibrous 221805286-0047 Homogeneous A18222 -Grout Green Tile + Grout Gray 100% Non-fibrous (Other) None Detected Non -Fibrous 221805286-0047A Homogeneous A18222-Thinset Green Tile + Grout Gray 100% Non-fibrous (Other) None Detected Non -Fibrous 221805286-00478 Homogeneous A18223 HVAC Duct Sealant Gray 3% Synthetic 30% Ca Carbonate None Detected Fibrous 67% Non-fibrous (Other) 221805286-0048 Homogeneous A18224 HVAC Duct Sealant Gray 100% Non-fibrous (Other) None Detected Non -Fibrous 221805286-0049 Homogeneous A18225 -Floor Tile 1 9x9 Tile (Gray) Over Gray 35% Ca Carbonate 3% Chrysotile 9x9 Tile (Brown) w/ Non -Fibrous 62% Non-fibrous (Other) 221805286-0050 Black Mastic Homogeneous A18225 -Mastic 1 9x9 Tile (Gray) Over Black 100% Non-fibrous (Other) None Detected 9x9 Tile (Brown) w/ Non -Fibrous 221805286-0050A Black Mastic Homogeneous A18225 -Floor Tile 2 9x9 Tile (Gray) Over Brown 35% Ca Carbonate 10% Chrysotile 9x9 Tile (Brown) w/ Non -Fibrous 55% Non-fibrous (Other) 221805286-00508 Black Mastic Homogeneous A18225 -Mastic 2 9x9 Tile (Gray) Over Black 100% Non-fibrous (Other) None Detected 9x9 Tile (Brown) w/ Non -Fibrous 221805286-0050C Black Mastic Homogeneous A18226 -Flooring 1 9x9 Tile (Gray) Over Gray 97% Non-fibrous (Other) 3% Chrysotile 9x9 Tile (Brown) w/ Non -Fibrous 2218052860051 Black Mastic Homogeneous A18226 -Mastic 1 9x9 Tile (Gray) Over Black 100% Non-fibrous (Other) None Detected 9x9 Tile (Brown) w/ Non -Fibrous 221805286-0051A Black Mastic Homogeneous A18226 -floor Tile 2 9x9 Tile (Gray) Over Brown 92% Non-fibrous (Other) 8% Chrysotile 9x9 Tile (Brown) w/ Non -Fibrous 22180528600518 Black Mastic Homogeneous Initial report from: 07/19/2018 13:33:02 ASB—PLM-0008-0001 - 1.78 Printed: 7/19/2018 11:33 AM Page 7 of 8 EMSL Analytical, Inc. EMSL Order: 221805286 Customer ID: FARM50D 1010 Yuma Street Denver, CO 80204 Customer PO: Tel/Fax: (303) 740-5700 / (303) 741-1400 http://www.EMSL.com / denverlab@emsl.com Project ID: Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-931116 Method using Polarized Light Microscopy Analyst(s) a a Cassandra Schorzman (4) Amanda Lang, Asbestos Laboratory Manager Gentry Catlett (10) or Other Approved Signatory Molly Elkins (37) Stuart Printz (79) EMSL maintains liability limited to cost of analysis. The above analyses were performed in general compliance with Appendix E to Subpart E of 40 CFR (previously EPA 600/M4-82MZ6 1h, Method"), but augmented with procedures outlined in the 1993 ('final') version of the method. This report relates only to the samples reported above, and may not be reproduG d, except in full, vi'Ithout written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations . Interpretation and use of test results are the resporsibilitygof It e d lent. Allot samples received in acceptable condition unless otherwise noted. This report must not be used by the client to claim product certification, approval, or endorsement by NV+<AP, NIST or any agency of the federal government. EMSL recommends gravimetric reduction for all non -friable organically bound materials prior to analysis. Estimation of uncertainty is available In request. _ a.. Samples analyzed by EMSL Analytical, Inc. Denver, CO NVLAP Lab Code 200828-0 (; Initial report from: 07/19/2018 13:33:02 AS1 _ PLM 000E 0001 - 1.78 Printed: 7/19/2018 11:33 AM Page 8 of 8 Non -Asbestos Asbestos Sample Description Appearance % Fibrous % Non -Fibrous % Type Al 8226 -Mastic 2 9x9 Tile (Gray) Over Black 100% Non-fibrous (Other) None Detected 9x9 Tile (Brown) w/ Non -Fibrous 221805286-0051C Black Mastic Homogeneous A18227 Green Mosaic Floor White 40% Ca Carbonate None Detected Tile Grout Non -Fibrous 60% Non-fibrous (Other) 221805286-0052 Homogeneous A18228 Green Mosaic Floor White 100% Non-fibrous (Other) None Detected Tile Grout Non -Fibrous 221805286-0053 Homogeneous A18229 -Backing Green Mosaic Floor Pink 98% Cellulose 2% Non-fibrous (Other) None Detected Tile Adhesive Fibrous 221805286-0054 Homogeneous A18229-Thinset Green Mosaic Floor White 30% Ca Carbonate <1% Chrysotile Tile Adhesive Non -Fibrous 70% Non-fibrous (Other) 221805286-0054A Homogeneous A18229 -Adhesive Green Mosaic Floor Black 100% Non-fibrous (Other) None Detected Tile Adhesive Non -Fibrous 221805286-0054B Homogeneous Al 8230 -Ceramic Tile Green Mosaic Floor Green 100% Non-fibrous (Other) None Detected Tile Adhesive Non -Fibrous 221805286-0055 Homogeneous A18230 -Adhesive Green Mosaic Floor Tan 100% Non-fibrous (Other) None Detected Tile Adhesive Non -Fibrous 221805286-0055A Homogeneous A18230-Thinset Green Mosaic Floor White 100% Non-fibrous (Other) <1% Chrysotile Tile Adhesive Non -Fibrous 221805286-00558 Homogeneous A18231 Drywall Behind Brown/White 20% Cellulose 70% Gypsum None Detected Plaster Fibrous 10% Non-fibrous (Other) 221805286-0056 Homogeneous Analyst(s) a a Cassandra Schorzman (4) Amanda Lang, Asbestos Laboratory Manager Gentry Catlett (10) or Other Approved Signatory Molly Elkins (37) Stuart Printz (79) EMSL maintains liability limited to cost of analysis. The above analyses were performed in general compliance with Appendix E to Subpart E of 40 CFR (previously EPA 600/M4-82MZ6 1h, Method"), but augmented with procedures outlined in the 1993 ('final') version of the method. This report relates only to the samples reported above, and may not be reproduG d, except in full, vi'Ithout written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations . Interpretation and use of test results are the resporsibilitygof It e d lent. Allot samples received in acceptable condition unless otherwise noted. This report must not be used by the client to claim product certification, approval, or endorsement by NV+<AP, NIST or any agency of the federal government. EMSL recommends gravimetric reduction for all non -friable organically bound materials prior to analysis. Estimation of uncertainty is available In request. _ a.. Samples analyzed by EMSL Analytical, Inc. Denver, CO NVLAP Lab Code 200828-0 (; Initial report from: 07/19/2018 13:33:02 AS1 _ PLM 000E 0001 - 1.78 Printed: 7/19/2018 11:33 AM Page 8 of 8 OrderID: 221805286 2lg EMSL ANALYTICAL, IHC. uaowonwr..auourn.iwxwa Asbestos Chain of Custody EMSL Order Number (Lab Use Only): 221%0SZIb EMSL ANALYTICAL, INC. 1010 YUMA STREET, DENVER, CO, 80204 PHONE: (303) 740-5700 FAx: (856) 858-4960 Company: Farmer Environmental Group, LLC EMSL-Bill to: ® Same ❑ Different If Bill to is Different note instructions in Comments" Third Party Billing requires written authorization from third payy Street: 8120 Sheridan Boulevard City: Arvada StatelProvince: CO Zi /Postal Code: 80003 Count : US -Report To (Name): Jennifer Da Fax #: IEmail Telephone #: 303.468-8763 Address: Jennifer.day@farmereg.com, kurt.pierc rmere .com Project Name/Number. to -A. Ltclq(P-0:s Please Provide Results: E] Fax ❑ Email Purc ase Order: U.S. State Samples Taken: Turnaround Time TATO tions" - Please Check ❑ 3 Hour ❑ 6 Hour PI 24 Hour I ❑ 48 Hour I ❑ 72 Hour I ❑ 96 Hour I ❑ 1 Week 1-a 2 Week 'For TEM Air 3 hr through 6 hr, please call ahead to schedule. `There is a premium charge for 3 Hour TEM AHERA or EPA Level //TAT. You will he asked to sign an authorization form for this service. AnalWysis com feted in accordance with EMSL's Terms and Conditions located in the Analytical Price Guide. PCM - Air ❑ NIOSH 7400 ❑ w/ OSHA 8hr. TWA TEM - Air ❑ 44.5hr TAT (AHERA only) ❑ AHERA 40 CFR, Part 763 ❑ NIOSH 7402 ❑ EPA Level 11 ❑ ISO 10312 TEM- Dust ❑ Microvac - ASTM D 5755 ❑ Wipe - ASTM D6480 ❑ Carpet Sonication (EPA 600/J-93/167) PLM - Bulk freporting limit) LM EPA 600/R-931116 (<1%) ❑ PLM EPA NOB (<i%) Point Count [:1400 (<0.25%) ❑ 1000 (<0.1%) Point Count w/Gravimetric ❑ 400 (<0.25%) ❑ 1000 (<0.1%) ❑ NYS 198.1 (friable in NY) ElNYS 198.6 NOS (non -friable -NY) ❑ NIOSH 9002 <1% Soil/Rock/Vermiculite ❑ PLM CARS 435 - A (0.25% sensitivity) ❑ PLM CARS 435 - B (0.1% sensitivity) ❑ TEM CARS 435 - B (0.1% sensitivity) ❑ TEM CARS 435 - C (0.01% sensitivity) ❑ EPA Protocol (Semi -Quantitative) ElEPA Protocol (Quantitative) TEM - Bulk ❑ TEM EPA NOB ❑ NYS NOB 198.4 (non -friable -NY) ❑ Chatfield SOP ❑ TEM Mass Analysis -EPA 600 sec. 2.5 TEM - Water: EPA 100.2 Fibers >10pm ❑ Waste ❑ Drinking All Fiber Sizes ❑ Waste ❑ Drinking Other: 1 ❑ ❑ Check For Positive Stop - Clearly Identify HorriggeTrapA Gr up Samplers Name: Kurt A. Pierce Samplers Signatu Sample # Sample Description Volum HA # Bulk Date/Time Sampled rs t7 Q1As� com, �-1 rj- �Irg { -7 (e 1 q4 17 t'l� ( 5...,O -JA I $ 8 A'di-, Cs 4l 79 Ply C 41 g1 SO PAA.., C'5.40 1_�l v?1 1.0CS,,t66�h Client Sample # s - C)3 Total # of Samples: Relinquished(C[ie Date: �i C� Time: Received (Lab):' Date: Time: 12� 0� !>� Comments/Special Instructions: 1t11, Cart'vo11e0 Docimient —Asbestos CAC —R2 —1622010 Page 1 of A pages Paqe 1 Of OrderID: 221805286 EMSLANALYTIGAI, INC. Asbestos Chain of Custody 1010 PUMA STREET, EMSL Order Number Lab Use Only): DENVER, CO, 802042 ---PHONE_ (303)740-5700- enns�suvA�rricnL INC. FAX: (856) 858-4960 uuow.,nm..uoourn....w,.ac Additional Pages of the Chain of Custody are only necessary if needed for additional sample information Sample # Sample Description Volume/Area (Air) HA # Bulk Date/Time Sampled 1! O w Q vis �'X �i�►ro�7'i 1 /t�,� f i� �Q►$� W/ 1±4� A) 1$ 110 7' J� Lkno A4% 19 j41414 3 `fCs-IW'k y uMP C kwJJ64.11, X41 Alst?q '- 'U ( A'v ) A-1 gi 957 T -f. t A w d wx lk &,,rL e4 tp Flot-r4%Ic Vi „- V'Arw lt-1 "Comments/Special instructions: City of Page —%_ of -y— pages Uuilding Colftl.d D.—fg-AscoW-COC R2-1172!2010 Paqe 2 Of OrderID: 221805286 Asbestos Chain of Custody Volume/Area (Air) HA # Bulk EMSL Order Number (tab use Only): EMSL ANALYTICAL, INC. EMSLANALYTICAL, INC. 1010 YUMA STREET, DENVER, CO, 802042 --PHONE: (303) 740-5700- FAx:(856)858-4960 Additional Pages of the Chain of Custody are only necessary if needed for additional sample information Sample # Sample Description Volume/Area (Air) HA # Bulk Date/TIme Sampled 11 ID ( a 1- LISA LA, 4 (q -;)L 0 3 C_X4 VA A I%Z b% 4 ;L I L 4 f4 14 + (� L � .4 ro-- ,� yT;k tit FAP s 'Comments/Special Instructions: Corta9 AOna 19-A.^.bW"COC-W-1(12nolD Page of pages Paqe 3 Of OrderID: 221805286 EMSL ANALYTICAL, INC. Asbestos Chain of Custody 1010 YUMA STREET, EMSL Order Number (Lab Use Only): DENVER, CO, 802042 EMSL ANALY7ICAL' INC. J PHONE: (303) 740-5700--- FAX: (856) 858-4960 Additional Pages of the Chain of Custody are only necessary if needed for additional sample information Sample # Sample Description Volume/Area (Air) HA # Bulk DatefTime Sampled r&P j45'rq- Tq7 201q -414%2(5 Atis d .�... 4 �r of I% FIR P ,¢ ( t fort - (� q U4L s� t41T CL5 x9 `� 1�t q xq ww-Rx9k Cb L»"f-I- 1 i �2� G ikaswt v43r4l r@ ` ;13 0 Cir ✓� vw s4 � � !�1do r �4t j kq._& i ,.Q_ 'Comments/Specia uctions: G 3'ily of COftVWOo 619—Asbestos COC—M—/117!2010 Pageo�"`f —' pages y cr-�y Paqe 4 Of gui1din9 pivison 3810 Pierce St, Wheat Ridge, Colorado Asbestos Report July 19, 2018 Page 7 APPENDIX III LICENSES & ACCREDITATION 14FMMER ENVIRONMENTAL GROUP N J R UJ CU ' O O O n � O N cv x i 1 O � O M cl cz rA E c� W � Z r ojr O O C N z oc %� V L [L T^ 7cz. r--� ..-� �•+ (:3cq cq Z3 G) C G' ' � O � y +•� ca cd Q . U OM ��' W .... .... .. 'OPP, wilo" WSK r OR -N r W IOKI yr ar � er ar tiSt sc sr .F' � ar as ar ,r sr Kr sr air a. r a! r r ars lS�� F�\ `'1i►!G'1 ' �J`1`i�G„ ,'1�('; ��51'r!r%i�;,' ��`uZ�(G��!, � �`�1�LG � ' �1`►fG !; ���`1`�fG . � \ �, � ; `_ C cu n U F_ o C06O m O U w � v Q Z z z — U Z v C =° Y W Z J C�LU _ o a o -,T N ~ v cn W 42 W -� L oVx — .= G. _ M CUo - oo 70 cu o O U W > O o�ti w V • v- v N cb c N c a, g U N w 5 LOi Q W a (f� cr C .0 N 00 o< o N> o (D (D�- N a CL Q w�; � O U Z o �- ti Q Q a W O o 16 �. --Z o C]m� o , :r _ m m EL U W CW W IOKI yr ar � er ar tiSt sc sr .F' � ar as ar ,r sr Kr sr air a. r a! r r ars lS�� F�\ `'1i►!G'1 ' �J`1`i�G„ ,'1�('; ��51'r!r%i�;,' ��`uZ�(G��!, � �`�1�LG � ' �1`►fG !; ���`1`�fG . � \ �, � ; `_ ®.ew :i , 1 • i MI; . TT J, P , mco c N U C a'0 E OD CoQ Ln U o CD CD v � V LO 0 Q ,In 0 LU V Fier LL W u tn u O cn � v i� Q �o t L C: O C: U "O u O 4- I- In Q. -0 Q =3 (Z to u CL o -C-+ O C O (,D +, O N CL c O O v V N o C: S Q) N c O u c Uo O t)A O U L v C: V) _ a L v— N L O U w V) z 0 z Q 0 N W CY1 W L) r) 00 O N W n L�i) w r) O d-' N Q W C D U • 13 • 0 13 c 0 0 C o a` O CD U �c N N C2, X Lta c O L V 06 an c_ 'C _ L U >- C U �y V m- i° w yj c 'CZo0 F— C "cv i w cv c.6 Ln oLO u z m� ,In 0 LU V Fier LL W u tn u O cn � v i� Q �o t L C: O C: U "O u O 4- I- In Q. -0 Q =3 (Z to u CL o -C-+ O C O (,D +, O N CL c O O v V N o C: S Q) N c O u c Uo O t)A O U L v C: V) _ a L v— N L O U w V) z 0 z Q 0 N W CY1 W L) r) 00 O N W n L�i) w r) O d-' N Q W C D U • 13 • 0 13 c 0 0 C o a` O CD U �c F AMMENR "VE NNENTAL www.farrnereg.corn GROUP July 19, 2018 Mr. Jeremy Bennett Haystack Construction 3615 South Huron Street, Suite #201 Englewood, Colorado 80110 SUBJECT: Lead -Based -Paint Survey 3810 Pierce Street, Wheat Ridge, Colorado Farmer Project No. 3996.03 Dear Mr. Bennett, Enclosed is Farmer Environmental Group, LLC (Farmer)'s Lead -Based -Paint Survey Report for the property located at 3810 Pierce Street in Wheat Ridge, Colorado. If you have any questions or comments concerning this information, please feel free to call me at (303) 468-8763. Sincerely, Kurt A. Pierce CO Lead Inspector #21170 Farmer Environmental Group, LLC City of Wi+eat Ridge 8120 Sheridan Blvd., Ste. A306 • Westminster. CO 80003. Offices 303 468 8763 IMMR tLORMONKwwwfarmereg.corn LEAD -BASED -PAINT SURVEY Commercial Building 3810 Pierce Street Wheat Ridge, Colorado Prepared for: Haystack Construction 3615 South Huron Street, Suite #201 Englewood, Colorado 80110 Prepared by: Farmer Environmental Group, LLC 8120 Sheridan Boulevard, Suite A306 Westminster, Colorado 80003 303-468-8763 July 19, 2018 Farmer Project No. 3996.03 8120 Sheridan Blvd , Ste A306 • Westminster CO 80003. Office 303 468 8763 TABLE OF CONTENTS Page 1.0 EXECUTIVE SUMMARY........................................................................................ 1 2.0 OBJECTIVE............................................................................................................ 1 3.0 SAMPLING METHODOLOGY............................................................................... 1 4.0 XRF RESULTS....................................................................................................... 1 5.0 CONCLUSIONS AND RECOMMENDATIONS....................................................... 2 6.0 LIMITATIONS.......................................................................................................... 3 APPENDICES: APPENDIX A— XRF DATA SHEETS APPENDIX B — LICENCES oll of ,teat Ride E mAlONME% GROUP 3810 Pierce Street Wheat Ridge, Colorado July 19, 2018 Page 1 1.0 EXECUTIVE SUMMARY Haystack Construction authorized Farmer Environmental Group, LLC (Farmer) to conduct a Lead -Based -Paint (LBP) Survey of the commercial property located at 3810 Pierce Street in Wheat Ridge, Colorado. Mr. Kurt A. Pierce of Farmer Environmental Group, LLC (Farmer) conducted the onsite inspection on July 16, 2018. Based on the XRF, the following surfaces contained lead-based paint in the areas surveyed at a level above the HUD standard of 1.0 milligram per square centimeter of surface area or 0.5% by weight. Based on the XRF, no surfaces contained lead-based paint in the areas inspected at a level above the HUD standard of 1.0 milligram per square centimeter of surface area or 0.5% by weight. The following non -painted surfaces were lead containing: • 6"x6" Pink Ceramic Wall Tiles located in the small restrooms 2.0 OBJECTIVE Farmer was contracted to perform a LBP Survey of the commercial property located at 3810 Pierce Street in Wheat Ridge, Colorado. The purpose of the LBP Survey was to confirm the presence or absence of LBP for ongoing maintenance of the building and future renovation projects. 3.0 SAMPLING METHODOLOGY Lead-based paint was analyzed by a Niton hand held x-ray fluorescence (XRF) spectrum analyzer (Serial No. 25197) that produces results for lead content in paint. Calibration checks were conducted at the beginning and end of the inspection and/or every four hours during use. The inspection was conducted in accordance with Housing and Urban Development (HUD) accepted scientific practices, industry standards and regulatory protocols. The HUD standard of 1.0 milligram per square centimeter of surface area was used to determine positive or negative results for lead based paint. 4.0 XRF RESULTS Based on the XRF, no surfaces contained lead-based paint in the areas inspected at a level above the HUD standard of 1.0 milligram per square centimeter of surface area or 0.5% by weight. FARMER CRQUP 3810 Pierce Street Wheat Ridge, Colorado July 19, 2018 Page 2 The following non -painted surfaces were lead containing: • 6"x6" Pink Ceramic Wall Tiles located in the small restrooms The following surfaces did not contain lead-based paint. • Beige painted plaster ceilings and walls located throughout building • Beige painted drywall (Gypsum Board) walls located throughout building • Beige painted concrete and concrete masonry block and brick walls located throughout building • Brown painted plaster, drywall (Gypsum Board), concrete and concrete masonry block and brick walls located throughout building • Brown and beige painted metal heat registers located throughout building • Brown painted wood door casings located throughout building In some instances a "null" result may be shown. In this case the sample is retaken from the same location because the instrument did not obtain a reading on the first attempt. A "null" result may occur because the instrument was moved during the sample, or the shutter did not open for any reason. 5.0 CONCLUSIONS AND RECOMMENDATIONS According to OSHA 29 CFR 1926.62 Lead Standard, employers are required to comply with the standard during scraping, sanding, burning, sandblasting, demolition, or any intentional disturbance of surfaces with detectable levels of lead paint. During demolition activities, composite samples should be collected from building materials painted with lead-based paint that are scheduled for disposal. Composite samples should be submitted for Toxicity Characteristic Leachate Procedure (TCLP) analysis to characterize the waste for disposal. The U.S. Environmental Protection Agency's (EPA) Lead Renovation, Repair and Painting Rule (RRP) govern the work of professional remodelers in homes and public buildings where there is lead-based paint. In buildings built before 1978 that are inhabited or frequented by pregnant women or children under seven and are used as residential, multifamily structures or public buildings, these rules apply. They require lead -safe work practices and training for all workers who may come into contact with lead. If lead content is unknown, the worker must sample every component to be impacted during work or a lead inspection must be performed by a certified lea inspector to determine which components contain lead. Any worker who will disturb is 11 of surface must be lead trained and practice lead -safe work. Ridge FARMER GROOP 3810 Pierce Street Wheat Ridge, Colorado July 19, 2018 Page 3 6.0 LIMITATIONS The professional Lead -Based -Paint Inspection service has been performed, our findings obtained and recommendations prepared in accordance with generally accepted principles and practices outlined by local, state, and federal agencies. This warranty is in lieu of all other warranties either expressed or implied. Farmer is not responsible for the conclusions, opinions, or recommendations made by others based on our inspection, the field reconnaissance, and/or information derived from this report. It should be noted that any investigation cannot absolutely rule out the existence or presence of LBP at a given facility, especially facilities built prior to 1978. This evaluation has been based upon limited available prior subject site history, observable conditions and activities at the site, information provided, and XRF field analysis of samples collected during the site investigation. If you have any questions concerning this report, please do not hesitate to contact our office. Farmer appreciates the opportunity to provide you with professional LBP services and hope we can provide assistance in the future. Respectfully, `I 1 Kurt A. Pierce CO Lead Inspector #21170 Farmer Environmental Group, LLC FARMER ENVIRONMENTAL GROUP APPENDIX A XRF DATA SHEETS City of Wheat Ridge uilding Diviso 14FARMER EM/IRONMENTAL GROUP 333= WS =. mma= CAP Squares _ BTU's _ Gallons _ Amps _ Sq Ft, son= - --------- Contract Value. 0 Review Fee (due at time of submittal): $ OWN ER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application am accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, casements or restrictions of record; that all measurements shown and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application and that I assume Rill responsibility for compliance with applicable City of Wheat Ridge codes and ordinances for work under any permit issued based on this application; that I am the legal owner or have been authorized by the legal owner of the property to perfonn the described work and am also authorized by the legal owner of any entity included on this application to list that entity on this application. CIRCIEONE (OWNER) (CONTRACTOR) gr (AUTHORNIZED.En of (ORWER) (CONTPUCTOR) Bldg Valuation: - ----- r CITY OF WHEAT RIDGE Building Inspection Division (303) 234 -5933 Inspection line (303) 235 -2855 Office ' (303) 237 -8929 Fax INSPECTION NOTICE Inspection Type Job Address Permit Number ffixo 6 -a e; ` 'P � Inspector: .ff �° DO NOT REMOVE THIS NOTICE " 1 City of Wheat Ridge - r Commercial Roofing PERMIT - 110945 PERMIT NO: 110945 ISSUED: 08/10/2011 JOB ADDRESS: 3810 PIERCE ST EXPIRES: 08/09/2012 DESCRIPTION: Remove and replace 2.5 sqs of modified with asphalt shingles * ** CONTACTS * ** gc 303/287 -3043 Robert McReynolds 01 -7787 D & D ROOFING ** PARCEL INFO ** ZONE CODE: UA USE: UA SUBDIVISION: 0408 BLOCK /LOT #: 0/ ** FEE SUMMARY ** Permit Fee Total Valuation Use Tax ** TOTAL ** ESTIMATED PROJECT VALUATION: FEES 50.30 .00 21.33 71.63 1,185.00 �70 �' Conditions: 6 nails per shingle is required. Ice dam membrane is required from eave edge to 2' inside exterior walls. Board sheathing with any gap greater than 1/2" requires panel sheathing overlay on entire roof. Sheathing inspection is required prior to covering. Contractor shall provide ladder for inspections. Scheduled inspections that cannot be performed due to inclement weather must be cancelled prior to 8:30 a.m. on the day of inspection or a re- inspection fee will be assessed. I, by my signature, do hereby attest that the work to be performed shall comply with all accompanying approved plans and specifications, applicable building codes, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with this permit. I further attest that I am legally authorized to include all entities named within this document as ties to the work to be performed and that all work to be performed is disclosed in this document an /or its' acc omy par anying plans and specifications. Signature of OWNER- ar--'COw,�*"� (Circle one) tJate/ 1. This permit was issued based on the information provided in the permit application and accompanying plans and specifications and is subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures. 2. This permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and received prior to the date of expiration. An extension of no more than 180 days made be granted at the discretion of the Chief Building Official and may be subject to a fee equal to one- half of the original permit fee. 3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard requirements, fees and procedures for approval of any new permit. Re- issuance or extension of expired permits is at the sole discretion of the Chief Building Official and is not guaranteed. 4. No work of any manner shall be performed that shall results in a change of the natural flow of water without prior and specific approval. S. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all required inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services Division. 6. The issuance or granting of permit shall not be construed to be a permit for, or an approval of, any violation of any provision of an a Ii a code or any ordinance or regulation of this jurisdiction. Approval of work is subject to field inspectio . Signature of Chief EALding Offical Date INSPECTION REQUEST LINE: (303)234 -5933 BUILDING OFFICE: (303)235 -2855 REQUESTS MUST BE MADE BY 3PM ANY BUSINESS .DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. pY City of Wheat Ridge Building Division 7500 W. 29 Ave., Wheat Ridge, CO 80033 Office: 303 - 235 -2855 * Fax: 303 - 235 -2857 ° ptpr Pp° Inspection Line: 303 -234 -5933 Building Permit Application Date: Plan #: Permit #: Property Address: >V(0 1 �.efC- S, � rr � ((, ((�� Property Owner (please print): f�/Sp" Cen mac/ �v � t 7L�' KPhone: 77 n 0 0 I — tS(p $ Mailing Address: (if different than property address) Address: ill e City, State, Zip: (vwr1� 9--k et Contractor: l t� , d— 3� 2 fll Contractor License #: v Phone: 3 1 — 30 3 Sub Contractors: Electrical City License #: Plumbing City License #: Mechanical City License #: Company: Company Company: Exp. Date: Exp. Date: Exp. Date: Approval: Approval: Approval: Use of space (description): &,c i4— P-AT,' Construction Value: $ 11 — 6O Description of Work: t (as calculated per the Building Valuation Data she 1 - e-. , - t � e` mo t i e Plan Review (due at time of submittal); $ (0 (�rir -cJ- 'so t4 Gcl� DC Sur r2wN- Sq. Ft7L.Ft added: Squares Z. -5 BTU's Gallons Amps OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance with the Wheat Ridge Building Code (I.B.C) and all other applicable Wheat Ridge Ordinances, for work under this permit. Plans subject to field inspection. CIRLCE ONE:: (OWNER) CONTRACTOR r PERSONAL REPRESENTATIVE of (OWNER) ( CONTRATOR) PRINT NAME: + a.� ✓S SIGNATU Date COMMENTS: Zoning: Reviewer: PUBLIC WORKS COMMENTS: Reviewer: BUILDING DEPARTMENT COMMENTS: Reviewer: DEPARTMENT USE ONLY OCCUPANCY: FIRE DEPARTMENT:: 11 approved w/ comments ❑ disapproved 0 no review required w~ 0 w~ w~ 0 ~ o to m W C1 W O 7 N ~ < N 6 N (D 7 3 N a (D ~ ~ 0 (D 3 a y ~ m 0 ~ S C- 0 a Q a ~ N N n 0 O (D Z ~ ~ ~ m w cn O w ~ m ~ • r Z o ~ (n N O ~ v ~ . m 0• N (D ' v ~ H a = w 0 0 0) ~ .N z > ,v W ~ .W d NLLon Z d ~ O ~N = 0 W ~ M . > d N W (j) M lm =M V } 0- L L ? d 0 ~ N V 2 = O V ~ ~ w , u `p a c ~ J ~ ~ G cc . v m E c ~ o a~ ~ a > \ N c C O - M M d \ ~ N Q i ~ 1O a J V v ' M > ~ . ~ s d a c COMMUNITY DEVELOPMENT DEPARTMENT Building Permit Number : 78003 BUILDING INSPECTION LINE -(303-234-5933) Date : 11/5/2004 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80033 - (303-235-2855) Property Owner: JEFFERSON CENTER FOR MENTAL HEALTH Property Address : 3810 PIERCE ST Phone : 432-5164 Contractor License No. : 22042 Company : D'AGOSTINO MECHANICAL Phone :(970) 535-4724 CONTRACTOR OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of W heat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printeQ on this application, and that I assume full responsibility for compliance with the Wheat Ridge Building Code (U.B.C.) and all other applicable Whe Ridge o/r'dinances for work under this permit. (OWNER)(CONTRACTOR) SIGNED ~ DATE ly Description : DEMO AND REMOVE EXISTING BOILER AND REPLACE W ITH 3 GFA FURNACES AND ONE 75 GALLON GAS WATER HEATER BUILDING DEPARTMENT USE ONLY : Z8f1IFtg COmrtlBntt;......... SIC: Sq. Ft. Approval : Zoning : BulidlndkComments: Valuation $23,000.00 Permit Fee : $472.30 Plan Review Fee : $0.00 Use Tax : $0.00 Total: $472.30 Use : Approval : PupticVVork~ GQmRientss Approval : Occupancy: Walis Roof : Stories Residential Units : Electrical License No : Company: Expiration Date : Approval : Plumbing License No :22042 Company :D'AGOSTINO M ECHAN ICAL CONTRACTOR Expiration Date : 7/23/2005 Approval: pF(/KS Mechanical License No : 22042 Company : D'AGOSTINO M ECHAN ICAL CONTRACTOR Expiration Date : 7/23/2005 Approval : OK/KS (1) This permit was issued in accortlance with the provisions set forth in yoDUr appliwtion and is subject to the laws o( the Stete of Colorado and to the Zoning Regulations and Building Code of Wheat Ridge. Cobrado or any other applicable ordinances of the Ciry. (2) This permit shall expire i! (A) the work authorized is not commenced within sixty (60) days from issue date or (B) ihe building authorized is suspended or abantloned for a period of 120 days. (3) If lhis permit expires, a naw pertnit may be acquired for a fee of one-half the amount normally required, providetl no changes have been or will be made in ihe original ptans and specifcations and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. (4) No work of any manner shall be done that will change lhe naNrdl Flow of water causing a drainage problem. (5) Contrector shall notify the Building InspeIXOr twenty-four (24) houre in advanca for all inspections and shall receive written approval on inspection carU before pro sucr~essiVe pTas9sof,ihe job. (B) ~fi ' nce ermiS or the a ro Af drewings and specifications shall not be consWed to be a permit for, nor an approval of, any violation ot the yiM~ tod-~ any other ordinance, law, rule or regulation. ~f" Chief Building Inspector Please sign Terms and Conditions on reverse side of page. COMMUNITY DEVELOPMENT DEPARTMENT Building Permi[ Number: oF w"EAT.p BUILDING INSPECTION LINE - 303-234•5933 Date: ~ g CITY OF WHEAT RIDGE " 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80033 • (303-235-2855) ~OLORAO~ APPLICATII/t ♦ Property Owner: VF'arZoi (.`y~ j'w Property Address: 36\C V,4cE, Contracror License No.: ;9,(9 y Phone: 303-422.- 516-4 Company:bs A9uA-1-o Phone:303-V"1"1I i0'&L OWNER/CONTRACTOR SIGNATURE OF UNOERSTANUING AND AGREEMENT I hereby certiy that the setback distances proposetl by this permit application are accurate, antl do not violate applicable ordinances, rules or re9ulations ot the Ciry of Wheat Ridge or covenants, easements or restriclions of recortl; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance with the Wheat Ridge Building Cotle (U.B.C) and all other applicable Wheat Ridge Ordinances, for work under this permit. (OWNERNCOMRAGTOR):SIGNEO<~1-4P• V~_Q*-~6DATE It TI (0WNER)(CONTR4CTOR):PRIMED ~ 1,9 -tiri p- DATE "ISI04 mstruction Value:$ t3oW. eo Permit Fee:$ Plan Review Fee:$ jJS Tax:R &tie~.~o} Total:$ Description: Uftn,u ~,a rq..ove, e,i:a~ln bo~le,e- on~ f.~rnayJ c~n1e~ one -15 9c\\ew gat, ualar 4eo,~or-. Sq. Ft. atldetl Y6 BUILDING DEPARTMENT USE ONLY COMMENTS: Approval: Zoning: G COMMENTS: Approval: WORKS COMMENTS: Approval: ancv: Walls: Roof: ,410-1 3 (nFA SIC: Sq.Ft.: Stories: Residential Units: Electrical License No: Plumbing License No: Mechanical License No: Company: Company: Company: Expiration Date: Expiration Date: Expiration Date: Approval: Approval: Approval: (1) This permitwas issued in accordancewith the provisions setforth in yourapplication and is subject to the laws of the State of Colorado and tothe Zoning Regulations and Builtling Codes of Wheat Ridge, Colorado or any other applicable ordinances of the Ciry. (2) This permit shall expire if (A) tha work authorized is nol commenced within sixry (60) days from issue date or (B) the building authorized is suspended or abandoned for a period of 120 days. (3) If this permit expires, a new permit may be acquired for a fee ot one-half the amount nortnally required, provitled no changes have been orwill be made in the original plans and specifications and any suspension or abandonment has not exceeded one (1) year. It chan9es have been or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. (4) No work of any manner shall be done that will change the natural ilow ofwater causing a tlrainage problem. (5) Contractor shall notify the Building Inspector lwentyiour (24) hours in advance for all inspecdons and shall receive wntten approval on inspection card before proceeding with successive phases of the job. (6) The issuance of a permit or the approval of drawings antl specifcations shall not be construed to be a permit tor, nor an approval of, any violation of the provisions of the building codes or any other ordinance, law, rule or regulation. Building Offcial COMMUNITY DEVELOPMENT DEPARTMENT BUILDING INSPECTION LINE - 303-234-5933 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 - (303-235-2855) Building Permit Number Date 15390 4/25/2003 Property Owner: JEFF. CO. Property Address : 3810 PIERCE ST Contractor License No. : 19325 Company : Jim McNerny CM Phone: 432-5806 Phone : 744 2422 OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurete, and do not violate applicable ordinances, rules or regulations of the City of W heat Ridge or covenants, easements or restrictions of record; that all measuremenis shown, and alle9ations made are accurate; that I have read and agree to abide by all conditions printed on this application, and that I assume full responsibility for compliance with the Wheat Ridge Building Cocle (U.B.C.) and all other applicable Wheat Ridge ordinances, for work under this permit. (OWNER)(CONTRACTOR) SIGNED DATE Use : Description : REPLACE 7 WINDOWS BUILDING DEPARTMENT USE ONLY Zoning Comnients: SIC : Sq. Ft. : Approval : Zoning : Buildili,g Comments:; Approval: BG Pub11G Works' Commentsi' Approval : Occupancy : W alls : Roof : Stories : Residential Units : Electrical License No : Company: Expiration Date : Approval: Plumbing License No : Company: Expiration Date : Approval: Construction Value : $12,000.00 Permit Fee : $272.10 Plan Review Fee : $0.00 Use Tax : $144.00 Total : $416.10 Mechanical License No : Company: Expiration Date : Approval: (1) This permit was issuetl in acwrdance with the provisions set forth in yopur application and is subject to the laws o/ the Slate of Coloredo antl to the Zoning Regulations and Building Cotle of W heat Ridga, Colorado or any other applicable ordinances of the City. (2) This permil shall expire if (A) the work aulhorized is not commenced within sixty (60) days from issue date or (B) the builtling authorized is suspended or abandonetl for a period of 120 days. (3) If this permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in the original plans antl specifcations antl any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment ezceeds one (1) year, full fees shail be paid for a new permit. (4) No work of any manner shall be done that will change the natural Flow of water causing a tlrainage problem. (5) Contractor shall notify the Building Inspector nvanty-four (24) hours in advance for all inspections and shall receive writlen appmval on inspection card before proceediing with successive phases of the job. (6) The issuance of a permit or the approval of drawings and specifcations shall not be construed to be a permit for, nor an approvai of, any violation of the provisions of the building,codes or any other ordinance, law, rule or regulation. Chief Building Insp ctor COMMUNITY DEVELOPMENT DEPARTMENT Building Permit Number: ~ oF W~EqT .p BiJII.DING INSPECTION LINE - 303-234-5933 Date: ~ m CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE ~a a WFIEAT RIDGE, CO 80215 -(303-235-2851~vpq p~~ 5,j) CORAO ~~,~~4.PdidNfV Property Owner: Z EV F E 9 -5 a/y CLW 1,4-~ Y ME=- Nt A L. 4 E R"'T ii Property Address: 3 b Ic> 5 T. Phone:3o3 2F32-5906 Conuactor License No.: Company: --I I tA McNp(cN~ C',~•1. Phone:3o3 744-242-,- O WNER/CONTRACTOR SIGNATURE OF UNDERSTAnDING AND AGREEhD+,NT S hereby certify that the setback distanccs proposed by this pemtit applicatlon aze accurak, and do not violate applicable ordinances, mles orregulafions of the City of Wheat Ridge or covenants, eesements orrestrictions ofrocord; fliat allmeasurements shown, and allegations made are accurate; that I have read and agree to abide by al] conditions grinted on this apptication and that I assume full responsibiliTy for compliance with the Wheat Ridge Building Code (U.B.C) and al] other applicable Wheat Ridge Ordinances, for work unda Nis yorm;c Construction Value:$ ( 2 ,ooo Permit Fee:$ Plan Review Fee:$ Use Taac:$ Total:$ DESCRIPTION: A~ Wi+J Do'ea s-C7J c.t~'t~T S t.Pa. c6~> ~ orR.Tta St.Qe. BUILDING DEPARTMENT USE ONLY SIC: Sq.Ft.: ZONING COMMENTS: ' Approval: Zoning: BUILDING COMMENTS: Approval: PUBLIC WORKS COMMENTS: Approval: Occupancy: Walls: Roof: Stories: Residential Units: Electrical License No: Plumbing License No: Mechanical License No: Company: Company: Company: Expiration Date: Expuarion Date: Expiration Date: Approval: Approval: Approval: (1) 7Lis pemut was usued in accordance with the provisioas set forth iu your epplicatio¢ and is subject m the laws of the Smte of Colondo and to tLe Zoning Regulations andBuilding Codes of Wheat Ridgq Coloado or eny otter applicabie ordinancee of the CYty. (2) This pecmit shell upire if (A) the woxk authoxized'u not comme¢ced withiu sizry (60) days from issue dak or (H) ihe bmlding authonzed is svspended or ebandoned for a period of 120 days. ' (3) If tids pe*mit expses, a new pami[may be acquircd for a fee of one-half the amomt nmmally requittd, provided ao eLanges have bern or will be made m the origiualplans andspecificaROnt andaaysuspmsioa or abendonmeutLav uotexceeded one (1) yeu. Ifchangu havebeen orifsuspension or abandomnent eficeeda one (1) year, fiill fees sLall be paid for a uew pmmit (4) No xrork of eny mamer shall be done that will change the natunl flow of water causing a dnmage problem. (5) CoahactorshallnoEfytheBuilding7vspectortwmty-faur(24)hoursi¢advmceforallinspec¢onsmdshallzeceivewrittmepprovalo¢inspecrioncudbefon proceediug with succwsive phaies of ffiejob. (6) The issuance of e peimit or the approval of dnwings md speciEcadons shall not be coastued W be a pumit for, nor an approval of any riolaGOn of tLe provisions of the buil/d/iag coda or a¢y other ord'mmce, law, rvle w regulatiou. Chief Building ctor 3eta ~i~RcCs~ EXHSgXT A Description of Work The windows to be installed under this contract shall be as described below. Manufacture: Cradaco Windows Material: Wood, Western pine Finish: Exteriar, extruded aluminum clad Cheatnut Hronze Interiar, pre-painted white Glass: Duat-pane with LoS coating Screen: Fiberglass Mesh Screen, Brilliant White West side windows: _ ~ I u! K F r . W ~ F- , ~ E4 e 4 E~ E cl E2 Ep North side windows. =J/ 1~~O f 81 - 41( I ~ " s~ Il 8o-c~aN~ d' ~ -~aoR ~ ~ ~ ~lo-~~ ~o~TEnL„~k ~~IDIUT~S ~(~WNfNC7 WiND04~1 OT'~EK W) NpGd./5 FEzE f iX,EI'J ~ .a a ~ ~ k~`t^ z Y y. es~ COMMUNITY DEVELOPMENT DEPARTMENT Building Permit Number : 15061 BUILDING INSPECTION LINE - 303-234-5933 CITY OF WHEAT RIDGE Date : 1/27/03 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 - (303-235-2855) Property Owner: JEFFERSON CENTER FOR MENTAL HEALTH Property Address : 3810 PIERCE ST Contractor License No. : 21520 Company : ROSS TREE COMPANY OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restnctions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application, and that I assume full responsibility for compliance with the Wheat Ridge Building Code (U.B.C.) and all other applicable WheatARidge ordinances, for work under this permit. (OWNER)(CONTRACTOR) SIGNED ~ 76!~DATE I-JA7' U3 Description : TRASH DUMPSTER ENCLOSURE CHAIN LINK W/SLATS INCLUDING GATES BUILDING DEPARTMENT USE ONLY w"MSIC : Sq. Ft. : Approval : DM OKAY Zoning : R-C OKAY Approval: DM Approval : Occupancy : Walls : Roof Stories : Residential Units : Phone : Phone : 871-9121 Construction Value : $0.00 Permit Fee : Plan Review Fee : $0.00 Use Tax : $0.00 Total: $0.00 Use: Electrical License No : Company: Plumbing License No : Company: Mechanical License No : Company : Expiration Date : Approval : Expiration Date : Approval: Expiration Date : Approval : (1) This permil was issued in accordance with lhe pmvisions set forth in yopur application and is subject to the laws of the State of Colorado and to the Zoning Regulations and Building Code of Wheat Ridge. Colorado or any other applicable ordinances of the City. (2) This permit shall expire if (A) the work authorized is not commencetl within sixty (60) days from issue tlate or (B) the building authorized is suspended or abandoned for a penod of 720 days. (3) If this permit expires, a new permit may be acquired for a fee of one-haif ihe amount normally required, provided no changes have been or will be made in the original plans and specifcations and any suspension or abandonment has not exceeded one (1) yeac If changes are made or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. (4) No work of any manner shall be dane that will change ihe natural flow of water causing a drainage problem. (5) ConUactor shall notify the Building Inspedor hventy-four (24) hours in advance for all inspections and shall receive written approval on inspedion card 6efore proceediing wilh successive phases of the job. (6) The issuance of a pe ' or Ihe a prov f drawings and specifications shall not be construed lo be a pertnit for, nor an appmval of, any violation of ihe provisions of the bUl ~ g d her ordinance, law, rule or regulation. < Chief Building Inspector - 't-DJS ~ CI o I f ~ , ~ ~ 'P.L - ( ' ~ - I i i , ~ ~ s ~ ~l'O ~ ~ / ~ ~ q I Re R. ~ ~ ~1 ~ r I- - IDO' -LS S I 10 CONIM[JNITY DEVELOPMENT DEPARTMENT Building Permit Number: ISQ (bl OF WHEql { BIJII.DING INSPECTION LINE - 303-234-5933 Date: ~ m CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 - (303-235-2855) COLORP00 ,y p~~,y j 4~PP~1 {t~iTd ON ^ Property Owner:jeP-C.rsuh(~Qn~t✓~t~tH~., Property Address: 3,~ ! UPl E pc~& S T Phone : (C- on4actor License No.: Company: j2055 T/ZG:c- C/ orr"2An t- Phone: 303-Sr7 l-c7i a l OWNER/CONTRACTOR SIGIYATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distanccs proposed by this pemut application are accurate, md do not violate applicable ordinances, mles or regulaHons of the City of Wheat Ridge or covenanfs, easements orrestrictions ofrecord; fthat all measuroments shown, md allega6ons made aze accura[e; that I have read and agree to abide by all condiNons printed on this application md tha[ I aasume full responsibility for compliance with the Wheat Ridge Building Code (U.B.C) md all other applicable Wheat Ridge Ordinances, for work under this pmnit. (OWNER)(CONTRAC'IOA):SIGNED DATE'-~7 DESCRIPTION: Construction Value:$ ~ PermitFee:$ Plan Review Fee:$ Use Tax:$ ~ TOt31:$ BUII,DING DEPARTMENT USE ONLY SIC: Sq.Ft.: ZONINO COMMENTS:. Approval: Zoning: BUILDING COMMENTS: Approval: PUBLIC WORKS COMMENTS: . Approval: Occupancy: Walls: Roof: Stories: Residential Units: Electdcal License No: Plumbing License No: Mechanical License No: Company: Company: Company: Expirarion Date: Expi;ation Date: Expirarion Date: Approval: Approval: Approval: (1) This pemtit was'ssued in accordautt with the provisions set forth in youz applicaROn md is subj¢t to the laws of the Sta[e of Colondo md ro Ne Zoving Regulations a¢d Building Codes of Wheat Ridge, Cololado or any oNer appGcable ordinances of the City. (2) This pumit shall eap¢e if (A) the urork aufhorized is not commmced withiu sizty (60) days from isme date or (B) the building authorized is suspended or abendoned for a period of 120 days. (3) If thix pemut expins, a new pexmit may be acquired for a fee of one-Lalf the amount noimelly rtqu'ved provided no chmmges have been or will be made in theoriginalplansandspecificationsandanysuspensionorabandonmeuthasnolezceededone(I)yeu.Ifchangeshavebeenorifsuspensionorabandonment ezceeds one (1) yeaz, full fres shall be paid for a uew permit - (4) No work of any manntt sLall be done that will cha¢ge the uatunl flow of water causing a d*aivage problem (5) ConhacmrshalluotifytheBuildinglaspecmrnveury-fow(24)hoursinadvanceforallinspec¢onsandsfiallroceivewrittenapprovalouiospectioncardbefore pmceeding with euccessive pLases ofthejob. (6) She issuance of a pexmit or the appioval of diawings md speci5catioas shall uot be cous4ued ro be a persnit foz, nor an approval of, avy violatlon of the provisioas of the buildivg codes or any other ordinance, law, iule or reguUtiov. ChiefBuild pector ~ . . ~ . . . . . . . . ~P TM' . DEPARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number : 10253 BUILDING INSPECTION LINE - 303-234-5933 c- ~ CITY OF WHEAT RIDGE Date : 3/16/00 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 - (303-235-2855) Property Owner : Property Address : 3810 PIERCE ST Phone : 432-5824 Contractor License No. : Company : Phone : OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certiy that the setback distances proposed by this pertnk application are accurete, and do not violate appliceble oWinancea, rules or reguletions of the City of Wheat Ridge or wvenants, easements or restrictions of record; that all measurements shown, and allegetions made are accurate; that I have read and a8ree to abide by all conditions printed on this application, and that I assume full responsibility for comphance with the Wheat Ridge Building Code (U.B.C.) and all other applicable Wheat Ftidge ordinances, for work under this permit. (OWNER)(CONTRACTOR) SIGNED DATE Construction Value : Permit Fee : Plan Review Fee : Use Tax: Total $23.50 $0.00 $0.00 $23.50 Use: Description : Install accoustical grid system in various areas of the buildiny. Only partial installation of ceiling tiles to allow smoke detector functions above. Install pass thru window in snack bar wall BUILDING DEPARTMENT USE ONLY ~ SIC : Sq. Ft. : Approval: Zoning : Approval : Approval : Occupancy : Walls : Roof : Stories : Residential Units : Electrical License No : Company : Plumbing License No : Company : Mechanical License No : Company: Expiration Date : Expiration Date : Expiration Date : Approval: Approval: Approval: (t) 71i1s permit was issued in acmrtlance with the provlsions set foM in yopur application and is subiect lo ihe laws of Me Siate of Colwedo antl M the Zoning Reguletlons antl Building CoCe of Wheat Ritl~e, Cobretlo or any other applicable oNinarwea of the Cily. (2) This peimit ahell racplre A(A) the vrork eWhonzad is not commenced within eixly (80) days from issue date or (B) ihe building authorized is suapended or abandoned fbr a periotl of 120 days. (3) If this pertnk expires, a new permd may 6e acquired fbr a fee of one-half the amouM normalty required, provitleC no changes have been or wlll be made in the original plans and spec~cetlons and any suspansion or abandonmeM has nM exeeeded one (1) year. It changes are mede or if suspensbn or ebandonment exceetls one (1) year, full lees shall be paitl for a rrewpa rmR. (4) No woilc of any manner ahell be done that wlll change tlie nalurel flow of waler causing a tl2inage proWem. (5) Contractor shall notiry ihe Builtling Inspector lwenty-four (24) Faura In advance fbr ell inspectlons and shall receive written approval on inspection cerd before proceetlii with suxesaive phases of the oD. (6) The ia Fn M e pe ' a the approval of tlrawings and speelAcations shall nM be consWed to be a permit for, nor an approval W, any violation oF the provisions il iry olher ordinance, law, rule or repulation. ~ Chief Building ! spector DEPARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number : BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE Date : 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 q PpLI CAT Io N ge PropertyOwner: ,,~i0 Pierce St. Property Address: 3810 Pierce St. 303-432-5824 Contractor License No. WheatRidge, Co 80033 Phone: : Company: pwner Installed Phone: OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate, antl tlo not violate applicable ordinances, rules or regulations of the City of Wheat RiCge or covenants, easements or restrictions of recortl: that all measurements shown, and allegations made are accurate: that I have read and agree to abide by all conditions printetl on this application, and that I assume full responsihility for tompiiance with the Wheat Ridge Building Code (U.B.C.) and all other applicable W eat Ridge inances, for work untler this rmi (OWNER)(CONTRACTOR) SIGNED pATE 3 ~F OB Construction value : Donati on Permit Fe= : Use Tax:Donation Total : Donati on VJC Description: I INstall accoustical grid system in various areas of the building. Only partial instalation of ceiling tiles to allow smoke detector fanctions above. ow in snack bar wall. omm ~ Approvai: Zoning : u om ~ Approval - F Approval: Occupancy : Walls BUILDING DEPARTMENT USE ONLY SIC : Sq. Ft. : Roof : Stories : Residential Units : Electrical License No : Company : Expiration Date : Approval : Plumbing License No : Mechanicai License No : Company: Company: Expiretion Date : Expiration Date : Approval : Approval : (1) This permit was issuad in accortlance wIN the pmWSions set forth in yopur appliraticn antl is au0ject M the laws o! the State a! ColoraEO anG to the .'.oning Regulations antl Builtling Cotle of Vuheat RiOge. CobraEO or arry oNer apPlirable ordinances ol the Ciry. (Z) 71tls Pertnit ahall expirc d(A) the wark auMOnzeE is not commencetl wdhin siuty (80) tlays from iuue tlate or (B) the Ouiltling aut~onze0 is suspentletl or abantloned tor a DenW of 120 tlays. (7) If this permit eapires, a new pertnR may pe acpuireE for a fee ot one-half the amount nortnalty requireC, pmviEeC no Uanges nave Oeen or will Ce maEe in the ex9ceeads one jna specifiptlons and any suepenaion or a0antlonrtront has not excaeEetl one (t) yeac If changes are maCe or if suspension or abanEOnment O yaar. NII fees shall De pai0 fir a new pertnR (5) No work of any manner shall be Eone Mat will Uange the natural Ilow of water rausing a tlninage pmClem. O ContraROr shall notity the Builtling Inapector hrcn(y.lour (24) houn in aEvance br all inspMions antl ahall receive wntlen appmval on inspection rard pNOre proceetlling with successive pnaus of Mep' b. (8) 7ha iuuance of a permit or Me apProval of Eravnngs antl sperifippons shall not be canstrueC to Ee a pertnit kr, nor an appmval ot, any violation of the provislons _ af the builCing coCea or any oMd oNinance, law, mle or regula6on. Chief Building Inspect DEPARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number : 14288 BUILDING INSPECTION LINE - 303-234-5933 Date 8/6/02 CITY OF WHEAT RIDGE : 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 - (303-235-2855) Property Owner: JEFFERSON CENTER FOR MENTAL HEALTH Property Address : 3810 PIERCE ST Contractor License No. : 17787 Company : D& D Roofing Inc. Phone: 432-5164 Phone : 287-3043 OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of recoM; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application, and that I assume full responsibility for compliance with the Wheat Ridge Building Code (U.B.C.) and all other appliqablg Wheat Ridge ordinances,/, fo-rwIork, under.this permit. (OWNER)(CONTRACTOR) SIGNED 0 ,P~,v DATE`Zj Lc Construction Value : $23,152.00 Permit Fee : $377.25 Plan Review Fee : $0.00 Use Tax : $277.82 Total: $655.07 Use: Description : TEAR-OFF EXISTING ROOFING TO WOOD DECK. FASTEN 1/4" DENS-DECK. FULLY- ADHERE CARLISLE.060 MIL EPDM ROOF SYSTEM C 1 i~tf~ l BUILDING DEPARTMENT USE ONLY SIC : Sq. Ft. : Approval: Zoning : Approval: Approval : Occupancy : Walls Electrical License No : Company : Expiration Date : Approval: Roof Plumbing License No : Company: Expiration Date : Approval : Mechanical License No : Company: Expiration Date : Approval: (1) This permilwas issued in accordance wifh the provisions set forth in yopur application antl is subject to the laws oi the State of Colorado antl ro the Zoning Regulations and Building Code of Wheat Ridge, Colo2tlo or any other applicable ortlinances of the Ciry. (2) This permit shall expire if (A) the work authorized is not commencetl within sixry (60) tlays from issue tlate or (B) the building authorized is suspentled or abandonetl for a periotl of 120 days. (3) If this permit expires, a new permit may be acquired for a fee ot one-half the amoun[ normally required, provided no changes have been or will be made in the original plans and specifications and any suspension or abantlonment has not exceeded one (i) year. If changes are made or if suspension or abandonment exceeds one (1) year, tull fees shall be paid for a new pertnit. (4) No work of any manner shall be done that will chan9e the natural flow of water causing a drainage problem. (5) ConVaclor shall notity the Builtling Inspector twenry-PoUr (24) hours in atlvance for all inspections and shall receive wntten approval on inspection wrtl bePore proceediin successivephasesoFthejob. (6) The i e a ete approval of drewings antl specifcations shall not be wnsirued to be a permit for, nor an approval of, any violation of ihe provisio of jfie b~~' C es or any other ordinance, law, rule or regulalion. Chief Building In ector Stories : Residential Units : DEPARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number : BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE Date : 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 PropertyOwnerCa.vr41t-Y -2ztt- 14"c"~ Property Address : 38 do Re vet 94- Contractor License No. : (-7'7 2 7 Company: p,4 D U-no- OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certiry that the setback distances proposed by this permit appliwtion are accurate, and do not violate applieable ordinances, rules or regulations of the City ot Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that 1 have read and agree to abide by all conditions printed on this application, and that I assume onsibility for compliance with the Wheat Ridge Building Code (U.B.C.) and all olher li W eat R'dge or ' nces a work under this permit. (OWNER)(CONTRACTOR) IGNE ' DATE 5 Da '"Leezr- o~ 4@~(s4-t' v~ rex~Fd~ u,~er,l oLe~~ Description :~~~,~,n, ~lx,Y~~s~e UUC rnY'i E'GD~I l'~~ BUILDING DEPARTMENT USE ONLY Zoififig'Cb,~ m"m8`ii3s; SIC: Sq.Ft.: Approval : Zoning : B "uilding'C~ _o~ ent9q Approval : PGbli 1N-o"fKs~~~ Approval : Occupancy : Walls : Roof : Stories : Residential Units : Phane : 43:z - Si to4 Phone: &)3- aS'-1- ?;D'+3 Construction Value : 15-2 Permit Fee : Plan Review Fee : Use Tax : Total : ~a54c~ ,~~+~o(Q~s-ciecl~ . F-u[cy . ~JS~e.yn Electrical License No : Company: Plumbing License No : Company : Mechanical License No : Company: Expiration Date : Approval : El ~P..tafi~R~. Expiration Date : Approval ~ ~PI~R§2~IC~t1~ Expiretion Date : Approval: .K~4_tab~ 0 4Pr11W (1) This permit was issued in accortlance with the provisions set forth in yopur applifation antl is subject to the laws of Ne State of Colo2EO and to the Zoning Regulations and Builtling Code ol Wheat RiEge, Colorado or any other ap0liwble orCinances of the Ciry. (2) This permit shall expire d(A) the work authonzed is not wmmenced within sixry (60) days from issue tlate or (B) the building auNOnied is suSpenCetl or aEanCOnetl for a penod o1120 days. (3) If this permit expires, a new permd may be acquired for a lee of one-half the amount normalty repuirM, provided no changes have been or will be made in the onginal plans and speci(c~ations and any suspension or aCandonment has not ezceetletl one (1) yeac II c0anges are maAe or if suspension or abanaonment ezceeds one (t) year, (ull lees shall 6e paid for a new, permit. (j Cobator shall shall btlino~at will change the natu2l flow of water wusing a dreinage OroClem. (S y the Buiq Ispector iwenry-four (24) hours in a0vance for all inspections antl shall receive writlen approval on inspection card be(ore proceetliing with successive phases o( the 7ob (6) The issuance ol a permit or the approval of Crawings and spxi(wtions shall not be construed to Ce a permit Ior, nor an approval ol, any violation of the provisions of the builtling codes or any other ordinance, law, rule or regulation. Chief Building Inspector For Mayor THIS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION DEPARTMENT OF PLANNING AND DEVELOPMENT BUILDING INSPECTION LINE - 303-234-5933 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 - (303-235-2855) Building Permit Number Date 9282 8/4/99 Property Owner : Property Address : 3810 PIERCE ST Contractor License No. : 20411 Company : Ronald K. Hufford Builder Phone : 216-9346 Phone: 851-6286 OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit appliwtion are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application, and that I assume full responsibility for compliance with the Wheat Ridge Building Code (U.B.C.) and all other applicable W.4at Ridge ordinances,for work qlfder this permit. (OWNER)(CONTR4CTOR) Construction Value : $5,500.00 Permit Fee : $125.25 Plan Review Fee : $0.00 Use Tax : $82.50 Total: $207.75 Use: Description : Complete structure of a patio cover, attached to existing building BUILDING DEPARTMENT USE ONLY ~ SIC : Sq. Ft. : Approval : MLC Zoning : R-C WR-.-°~~ ~ Okay Approval: BG . Approval : Occupancy : Walls : Roof : Stories : Residential Units : Electrical License No : Company: Expiration Date : Approval: Plumbing License No : Company : Expiration Date : Approval: Mechanical License No : Company : Expiration Date : Approval: (1) This permit was issued in accordance with the provisions ut forth in yopur applicalion antl is subject to the laws of the State of Coloratlo antl ro the Zoning Regulations and Building Code of Wheat Ridge, Colorado or any other applicable oNinances of the Ciry. (2) This permit shall expire if (A) the work auNOrizetl is not commenced within siMy (60) tlays from issue tlate or (B) the Duiltling authorized is suspentle0 or abandoned for a period of 120 days. (3) If this permit expires, a new permit may be acquired !or a fee of one-half the amount normally required, provided no chan9es have been or will be made in ihe original plans antl specifcations antl any suspension or abandonment has not exceetletl one (1) year. If changes are made or if suspension or abandonmen[ exceeds one (1) year, full fees shall be paid Por a new permit. (4) No work of any manner shall be done thal will change the naturel Flow of water wusing a drainage problem. (5) Contractor shall notiry the Builtling Inspedor hventy-four (24) hours in advance for all inspections and shall receive wntlen approval on inspection wrd betore proceediing with suaessive phases of the job. (6) The issuance of a it or Ne approval of drewings and specifcalions shall not be construed to be a permit for, nor an approval of, any violation of ihe provisions oi the building es r any oUer oNinance, law, rule or regulation. IA Chief Building I ector ,Ofp DEPARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number : BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE Date : 8/-~`I 9 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 qPPLICATIo N PropeRy Owner : SU M't11 r C EN;`rle Property Address : 3:?f0 10115'Rcs _~-T Phone :~O-3"z!6-Q35~6 Contractor License No. : /Yp V a01// Company: 1e(91V,4U9 !`'4vFFO~'J C;U/Lbb~ Phone:?D_? -23z-g-oe/7 OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are aceurate; that I have read and a4ree to abide by all conditions printed on this application, and that I assume full responsibility for complianee with the Wheat Ridge 8uilding Code (U.B.C.) and all other applicable at Ridge ordinances, for work der this pertnit. (OWNER)(CONTR4CTOR) SIGNED DATEJ/~/= Description : ~~~1_~1-1F ,d -~tAcfl ,S4 Construction Value : SS~ 00 Permit Fee : Use Tax : Total : Use: oP /z / VAtcv GCjvFise lv ,zfixts7"iu4 ao~GainiG, BUILDING DEPARTMENT USE ONLY APProval: Mo_ Zoning : Approval : . ,l. d//~y Approval: Occupancy : Walls Electrical License No : Company : Expiration Date : Approval : Roof Plumbing License No : Company : Expiration Date : Approval: SIC : Sq. IN A RECEIVED AU6 0 3 1999 Mechanical License No : Company: Expiration Date : Approval: (i) TTis permit was issuetl in accorOance wiN the pmvisions set Mrth in yopur appliw6on antl is subject to the laws of the SWte of Colorado antl to the Zoning Regulations and BuilCing Code of Wheat Ritlge, ColoraCO or arry other applicable aNinances oltlie Ciry. (2) This permit shall expire if (A) the work authonzetl is not wmmenceE within sixty (80) days from issue Aate or (B) the building authonzetl is suspended or abantlanetl tor a penoA of 720 tlays. (3) I( this pertnit expires, a new permit may be acquiretl /of a fee of one-halt ihe amount normelry requireE, provitletl no changes have been or vnll be matle in the onginal plans anA specifirations anO arry suspension or abantlonment has not exceetletl one (1) year. If changes are made or if suspension or abanCOnment exceeds one (1) year, NII (ees shall be paid far a new pertnit (4) No work ot any manner shall be tlone Mat will Uange the naN21 Ilow of water wusinq a tlrainage problem. (5) Contractor shall notiry the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approval on inspectlon caM before proceetliing with successive phases ot the ob. (6) The issuance ot a permk or Me approval o~Erawings and specifiwtlons shall not be consWetl to be a peimit tor, nor an approval a!, any violation of the provisions af the builAi co s or any other or0inance, law, nile or regulatlon. Chief Buildin nspector Stories : "6-16-1999 8:31AM FROM SPARLIN AND ASSOC. 3832350874 MAY- 3-99 MON 217 PM Patio Addition 3810 Piuce St. Wheat Ridgc, CU SPECIFICATIONS (;onartte lab - Moaoslab designed to code by contraetur with a smooth finislt. Es[imace uncolored, and coloted (terra wtta of similar) at an altema[e. Client w'tll apply sealam or oeher surfnce treatment. Rpgf ao havc a 3J8 inch soiling xnachsd ro:aftscs. . 'dinR - Cedu, tongue and groove ot si,milaz. Escimate fedwood as aa alternate. &tjWg of redwood. Gutter and doWndrain coloced brown. All wogdivqrk to 6e teft ualfniah0d. Finish to be applied by clieM. Cuntractor ao rcdesign any components ttiat do na mcei code as drawe. We would like to have ywr estilnnte by May 14. Ifyou ete no loager inucested in this project, pleaso !ei us know. Send cuimates to Bob Hrockwehl ai: Summit Centcc 3810 Pierce St. v/hcas ltidgs, CO $0033 Ortucw: 303-432-5898 Address quascions to Bob BrockweAl ar P. 2 P. 2 303-216-9346 or303-432-5800 ~ 7 \L ~ ~ I i ~i i j ~ ; ~ v v < ~ ~ Q ~ J J ~ ~ Vt~ ~ v ~ i~ tQ \A ~n. IV, ~ 1 ~.J Q 13 c~ ZQ ~ ~ q q f°- \h v . ~ xa ~L ~ ~ ~ uj ~ ~ ~ ~ 16 O ~ o s ~ . w > o-0 m ~ @ ;a$ a U u Q ~ N t cn 3 J ~ v f..~ i Y V V .6-16-1999 8:31AM 64AY- 3-99 MON 2:18 PM ~ ~j 'se ~ y ~ ~ ~ FROM SPARLIN AND ASSOC. 3032350874 ~ K -Q .v cJ i„ .T~ 2 ~ 4 ' Q ~ . y ~ 4\~ `y: ~ C4, ~ \ y M ~ *i. fli. ~l tc -4 l" ~ ~ O ~ 3 ~a ~ _.~/I~ ~ ~ , .'4..._. y ~ mJ . ~{a~ J I ~ZG"~_A_ZRI, r i 3 ~-J`~ ~oj ~`•j , 11 ~..~~AL._ z- rl"' `~1.~- J ~ ~ 1-11 IE . ,T_. ~ ~ w . 3 ~ . ~ Z YI sr ~K C 4ri O ~ w Q~ 1 O . , ; . ~ ~ ~ I P. 3 iJ v 7 w ~ o ~ P. 3 M (IL 0 ~ V ~ ~ H ~ ~ ~ v' ~ ~ • J~ 1 ~ S 4) 7j! j 1 ~ ~ S ~ c6 h 6-16-1999 8:31AM FROM SPARLIN AND ASSOC. 3032350874 MAY- 3-99 MON 2:18 PM /~~1L1~lG P"= 6") 3"~- 'YS et f eac% Gor,n..e- t . Gthcl pvr. rtt oT ~4ch s~~..t%on zXd P. 4 !-~A T/a AoN 28 !0 Pm~!3.C.,;= SY: 3o AnR,I t.- ~qqq ; y" S~-Pel Gtn.tlxor hracket P. d 3 af 3 .6-16-1999 8:32AM FROM SPARLIN AND ASSOC. 3032350874 MAY- 3-99 MON 2:19 PM A'Arro , h t i ~~6NiNG l~ i . ;i ~ ~i ~ ~ z a~ ~ ~h ~ I n.. I u ~ w 0 ~z ay r;.rMC,. QureEr OVF~~~.4D ~/ENTS y` P. 5 P. 5 ~ 6-16-1999 8:32AM FROM SPARLIN AND ASSOC. 3032350874 WHEAT RIDGE,i ZONED R- rLOT 6 ~O~IERHE40~ COWER IINE 93 20, e vqRKiNG SPnCES /q NE COR, LO7 5 PP C,0 O N m o ~ ~ O ' n . . .~.QJ. ' q ~ . . r \ y S yP ~ i' 9 ~.2 32' 20,914. SO.F7. z y ` C N I ' m I -rr \ ~ \ ASPHALT CURB ' A. HELM 8 WiLMA L. HELt ~ vI )3A A$V/ ROO78EER # i785 W. 387H AVE. - NHEAT RIDGE, COLO. ; ?ONEOz R-C i' ~ H;X I I Ay 0~0 ~C) _ ~ ZJ H I w ~ I ~ ~ ; n o ~ J ~ W ~ . `}W o I. 0 m ~ I_ ~o 1 ym~ o, n 25'" P. 6 n0~ eQy co~ J Of N XU~ 4 0 L! R C .7 E 0 Cm 0 4 CO ti o t; H S >n 2 W, : z~ 4 u o w H E ~ A r uo 0 C zU ? 0 L o ` ~ L' {,h 0 . C C UO ~ 4•' *40 a h EH C ~ .7 I7 O x W u z4 L'1 aV E 0 x a ~ U a C C n z , e E o ~Q L• ~ mA G o n H 4 h u~ SH£S'S NVM9 ER C ~ Z 6-16-1999 8:32AP4 FROM SPARLIN AND ASSOC. 3032350874 P. 7 j ~ , ' ' . . . y ' , . _ . ~ ~ WHEAT' ftIDGECOl.O'. . ~ , . - o: ".ZONED .R:3 ~ LOT I I W coa . 1 ~ lAX.S • . 'iIB.00~ ' ~ " . . ~•vP ~ 1 , 5.426 ` 211.20 ~ .r I 5426 ~ y- - 30, 5 P4RKING SA4,^ES~ 27.6 ~ ! / • 1 ~ SERViCE t Q ' , ~.5..~ ~ za' 7 ea.~' ) W 1 i, 5 -~o ~I y ► I, a{r. i~ r w 7 .4• ~ . L~ • ~ C Z~ • n z- N $I ~ U FINISH fLOOR ELEV.Sa25.85 " E~ ~ F c .jp3'. I ~ BUIl01NG 14.75 HIGH . V p ~ I 1'.=~" - I Y ^ U i r O I ~ 13 . i . 1 I '14 34,9' o r ; L e " SD.00' y 09 w u \ .c e~r o T' • : -o . IG.O, ~ 29.2~ 09' 209.00' T 0.7 LOT 5 z I < 00 , KENNETH E. I.EWIS AND DOROTHY L.LEWIS OBA TEX4C0 STqTION ~ 6795 W, 38TH. AVE, wHEn7 RIDGE, Ca_O. . ZONED! C-I , Module NoM Owmr / coahacoor is reapomibk for taC91ng peppeRy Bm'°~ corabueft imPro+'ernent4 accotding m t1a appmved plea and required ievelopment standarda. 77u City b not ratponaibte for inaecumte information abmitted within fhe plan set and any construction amn iesulting from Lucctuate informatioa Sz'I`E PL..AN - SL7~ - b- ib- iyya 8:33AM FROM SPARLIN AND ASSOC. 3032350874 P. 8 - FEB- 5-99 PRI 1`24 PM P. 1 rA F~ r~' CONSIDERATlONS Z~35- 0$7y FOR PATtO F.nvirommntal Factors Noise from SSth St. Shade Shelter from rain or snow kieat off pavement Securiry for tables, chairs, ash trays Wind gossible Desifen OAtiqp~ I3ick floor Unibrellas Treesin planters Built-in or immoveable ashtrRys Partially or eomyletely roofed Incorpoxate dumpstec enelosura Coni r- ittee Ron Russell Mike Most Fxank liegen£uss Don Dodson Chris Hill Desi ncrs I30f3rockwehl llick 5parlin, Ph. 237-3926, Fax 235-0874 2•5-99 a:\yatio DEPARTMENT OF PLANNING AND DEVELOPMENT BUILDING INSPECTION LINE - 303-234-5933 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WWEAT RIDGE, CO 80215 - (303-235-2855) Building Permit Number Date 9302 8/11/99 Property Owner : Property Address : 3810 Pierce St Contractor License No. : 18274 Company : HALLMARK ELECTRIC Phone: Phone: 458-1509 OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certiTy that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application, and that I assume full responsibility for compliance with the Wheat Ridge Building Code (U.B.C.) and all other applicable Wheat Ridge ordinances, for work under this permit. (OWNER)(CONTRACTOR) SIGNED..DATFIJ~ Description : Wiring patio Construction Value : $400.00 Permit Fee : $23.50 Plan Review Fee : $0.00 Use Tax : $6.00 Total: $29.50 Use: BUILDING DEPARTMENT USE ONLY RIO~~" SIC : Sq. Ft. : Approval : Zoning : ' ~'M ifflo, Approval: Approval: Occupancy : Walls : Roof : Stories : Residential Units : Electrical License No : Company: Plumbing License No : Company : Mechanical License No : Company: Expiration Date : Expiration Date : Expiration Date : Approval: Approval: Approval: (i) This permit was issued in accordance with the provisions set forth in yopur applicaUon and is subjecl to ihe laws of the State of Colorado and to the Zoning Regulations antl Building Code of Wheat Ritlge, Colorado or any other applicable ordinances of the City. (2) This permit shall expire if (A) the woric authorized is not wmmencetl within sixty (60) days trom issue tlate or (B) the builtling authorized is suspentletl or abandoned for a period of 120 days. (3) If this permit expires, a new permit may be acquiretl for a fee of one-half the amount normally required, provided no changes have Deen or will be made in the original plans and speafcations and any suspension or abandonment has not exceetled one (7) year. If changes are matle or if suspension or abandonment exceetls one (1) year, full fees shall be paid !or a new permit. (4) No work of any manner shall be tlone Ihat will change the naturel flow of wa[er causing a tlraina9e problem. (5) Contrector shall notify the Building Inspector lwenty-four (24) hours in advance for all inspec6ons antl shall receive written approval on inspection card before pmceediing with successive phases ot the ob. (e) The issuance of a permit or ihe approval o~tlrawings and speciFlCations shall not be construed to be a permit for, nor an approval of, any violation of the provisions of the ~Wfl6ing codes or any other ordinance, law, mle or regulation. ,F , . .i . ~ . . _ Chief Building Inspector DEPARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number : BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE Date : 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 APPLICATIo N PropertyOwner: Ce,,-{6e/ PropertyAddress: 3 $10 PoFYC; Sk- Contractor License No. : X1 y Phone : Company : HG IJw+A✓ ~C- E~~G~r'I L Phone : 303_11;-J-I 5--0 j OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certi(y that the setbaek distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations ot the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are aceurate; that I have read and agree to abide by all conditions printed on this application, and that I assume full responsibility for compliance with the Wheat Ridge Building Code (U.B.C.) and all other applicable WtMat Ridge ordinan.Qes, for work under this permit. (OWNER)(CONTRACTOR) SIGNED/r~, DATE 0V_" Description Approval Zoning : MEMUMEMM Approval : SIC : Sq. Ft. : I Approvai: Occupancy : Walis : Roof : Stories : Residential Units Electrical License No : Plumbing License No : Mechanical License No : C o m p a n y : /A l/Mxri( Company : Company : of the builOing codes or any oNer ortlinance, law, rule or regulaUOa Construction Value : y6d, pp Expiration Date : Expiretion Date : Expiretion Date : Approval : Approval : Approval : (1) This permit was issued in accortlance with the pmvisions set krth in yopur aDPiifaGOn and is subject to Me laws of the State of Caloredo and to the Zoning Regulations antl Builtling Cade of VJheat Ritlge, Colo2EO or any other applicable oitlinances of the Ciry. (2) This pertnit shall expire i( (A) the work authanzed is not commenced wiNin sixty (80) tlays (rom issue tlate or (B) the Duiltling authonzed is suspenEeA ar abantloned !or a penod ot 120 Cays. (3) If ihis pertnit expires, a new pertnit may Oe acquired (or a(ee of one-half the amount normally required, provided no Uanges have been or will be matle in the onginal plans antl specifiwtions and any suspension or abantlonment has na ezceeCetl one (1) yeac If changes are maae ar if suspenslon or a0antlonment exceetls ona (t) year. NII fees shall ba paitl Por a new permit (4) No vrork ot any manner shall be Cone that will thange Ma naNral flow of water pusing a d2inage problem. (5) ConUactar ehall notily the Building Inspector twenry-four (24) hours in aEvance for all inspections antl shall receive written approval on inSpecUOn earC Oebre prxeetliing with successive phases of Ne job. (6) The issuance ot a pertnN or the approval ol d2vnngs anE specifiwUons shall not be mnsWed to be a pertnit for, nor an approval of, any violatlon of the provisions Permit Fee : Use Tax: Total : Use: BUILDING DEPARTMENT USE ONLY Chief Building Inspector Certificate of Completion AND/OR Compliance CITY OF WHEAT RIDGr 7500 W. 29TH AVENUE WHL-A"C R1DGF.. COLORADO 80034 T'HIS CERTIf1CA7'E VERIPIES FHA"T THE PROPCR'I'Y DGSCRIBED BELOW, DOES COMPLY WI rH THE WHGAT RIDGE BUILDING CODE, ZONING AND O'I'HER RELA7'ED LAND USG AND DEVELOPMENT LAWS OF THE C[TY OF WHEAT RIDGG POR 'CHE FOLLOWING PURPOSE: Update of Housing for Jefferson County Housing OWNER Jefferson County CONTRACTOR various PROPERTY ADDRESS 3810 Pierce Street DATE 7/3/97 CHIEF BUILDING OFFICIAL , / ~ 7,ONING ADMIN[STRATO _ ADDRESS Center for Mental Health DATE: 6 -0 C) -G--;7 t~~r A CERTIFICATE OF OANCY HAS BEEN REQUESTED FOR: PURPOSE OF STRUCTURE: Building Dept. Approval: Remarks: Zoning Approval: G 1~t 0 l ~l2✓ C'~-~~^"i -7I2 Remarks: INSPECTIONS WILL NOT BE MADE UNLESS THIS CARD IS POSTED ON THE BUILDING SITE 24 HOURS NOTICE REQUIRED FOR INSPECTIONS WHEAT RIDGE, COLORADO 7500 WEST 29th AVENUE (303) 234-5933 INSPECTION RECORD JOBADDRESS 3810 Pierce Street BUILDING PERMIT N0. 96 -4411 DATE ISSU€D 12 / 31 / 96 OWNER Jefferson Co. CONTRACTOR SETBACKS FROM PROPERTY LINES: NORTH SOUTH EAST WEST Caissons or Monolithic POUR NO CONCRETE UNTIL ABOVE HAS BEEN SIGNED Rough Electrical Rough Plumbing ;z „2 7 7 Air Test Gas Piping Rough Heating & Ventilation j ~ (above myst bftsigned prior to lraming inspection) Framing Insulation Drywall nailing / 5. U . z w~~-G Roofing Refrigeration Electrical underground Final 2 Electrical 4 d ~ Plumbin ~ Heatin & Ventilation U'ff ~ Frame R.O.W. & Drainage Fire Department Parking & Landscaping 1~~-j 0 9 1er c?l M/ , OCCIfPANCY NOT PERMITf'tD UNTIL CERTIFICATE OF OCCUPANCY IS ISSUED TYPE OCCUPANCY PROTECT THIS CARD FROM THE WEATHER 9o N/9r Poua FLooR )UNTIL AB* HAS BEEN SIGNED m s A v z ~ m < m ~ ~ a~\ LI m ~ S 3 m s ~ ~ ~ 0 e o w (D w~ d < 3 lD ~ A ~ ~a ~ 3 0 a0 ~ o ; d~ o ~ $ o ~ ~o 7 IQ < 0 m 0 0 N 3ff~ c" 3 ~m r o e W 3 a? N ~ ^ C a m~ ~ ♦r ~ r O 0 O ~ m a ",o ~ " ~ < i7 w m m y A ~ c n k D ~ d ~ Z Go C' ~ r o ~ ' a 0 ° n ` Z M p ~p ( 3 o+ f A N tl! cc m < a , m :r C- °a = =~I ~mn+ ~ yo~ ci W e °r ° 0. ~ A C 0 :r ~ ~ 0 ~ m ~ e O o-~ w Q v-- J ~ (D o p » ~ < V " S7 o Y, _ ~ M a dN v : m 3 0 O = O ro cn m y C -`~~p ~ O m y ~ o» >co ~ Z ~ cn rN ° m c, ~ O ~ I N y o o C ~:r ~ ~ N(D ( ~ Z ~ e ~ o 0 < a ; , , : , , . . . . .a. . . . w : .-DEPARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number: 4872 . e~ ~ B[IILQING IBfSPECTtON DIVISION - 235-2855 GITY OF WNEAT RIDGE Date : 4/11/97 7500 WEST 29TH AYENUE WHEAT RIDGE, GO $0215 Property Owner : Property Address Contractor License No. Company 3810 PIERCE ST 17743 Gordon's Heating & Cooling Phone : 744-2422 Phone : 232 2345 OWNER/CONTRACTOR SIGNATURE OF LNDERSTANDING AND AGREEMENT Constructioh Value : $1,976.00 I hereby certiy that Mesetbadc diatartces proposed by this permk appliwtion are accurate, Pe('ITIt Fe2 : $63.00 and do not violateapplicable oMihancas; rulea or regulations of the City of Wheat Ridge or t ll t h d 11 ti t a e s t t id M f . Pl R i F 00 $0 a a measuremen s s own, an a e0a ons covenan s, e sem nt or res tk roos o reco ; . an ev ew ee . made are accurate; that I havetaatl and agree to abide by alI contlRionspriMed on this application, and that 1 asSUme fu11 responsibiRty for conlPliance wkh the WheafRidge Building U36 T2X : . $23:64 es, work under this permR. Code (U.B.C.) and all4ther applicetila VYhe t RWge ordmanc . ~ in~enavavnnr.rrennrnm mrum /'_Y[~1 A1 iiI(n~ )~NYN..erc '1 I ' / 7otal : . $86•64. Description : GENERAL REPAIR AND UPDATE BUILDING DEPARTMENT USE ONLY SIC : Sq. Ft. : Roof : Stories : Residential Units : Electrical License No : Company : Plumbing License No : Company : Mechanicaliicense No : Company: Expiration Date : Expiration Date : Expiration Date : ApprovaL Approval : Approval : (1) This permit was isauaC m accordance with Me provisions set forth in yopur appikation and is aubbct to the laws of the Stateot Cdondo arW ~ the Zoning RegWationa and Bu1WingCode of VJheat Ridpe, Coloratlo w a~ry otlrer, applicabb ortlmancea o! the City. (2) This pemiil shaflexryire If (A) Me wwk autho'rsed is not commenced w~thin sbdy (80) Aays from isaue dale w(B) the buNding authorizetl Is suspentled or abandoned for aperloC oi120 days. (3) If this pamqt expiros, a naw permN may be aNuired for a fee of onahalf the emounl nomrely required, Pmkied. m chwgb%havebean a wAlGe made in the . orqmal Wan4 md spedflCdLOnc and any suspenaon w aberMonment has not oxceetled one (1) year. If changes are matle or il suspenskn or a6anlonment 4) No work of any I mamier the elwll be done tlpieectwitl change tha netural flow of water eausinp e tlreinage probkm. pnoceetl~ng withnosuc~cessWe~p ha~ses of Me ~ IoU~nH'bur (24) houra in advarwe for a0mspections antl shell receive writtan approvel on inspecdon cerd hefore (s) . The Iswa~ of a petmit or tlfe epproval of EfBWings and speCiflCetions Bhall not 68 tonsWed to be e pefmR for, fror an appiovel of, any videtion of dte provisions of the Dui1Ci~jxx1es* any oNwadinance, law, rule w regulatiai. THIS PERMlT VALtL1 ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPEC70R AND MAYOR CAIL: 234-5933 24 HOURS PRIOR TO INSPECTION DEPARTMENT OF PLANNING AND DEVELOPMENT BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 Building Permit Number : Date : Property Owner ~v" wj;z- Property Address Contractor License No. Phone : L1 4( ZG( 2 Company : Phone : ,Z -32 -Z 3 L-CS OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit appliwtion are accurate, and tlo not violate applicable ordinances, rules or regulations of the Ciry of Wheat Ridge or covenants, easements or resirictions of record; that all measurements shown, and ailegations made are accurete; that I have read and agree to abide by all conditions printed on this application, and that I assume full responsibiliry for compliance with the Wheat Ridge Building Code (U.B.C.) and all other applicable Wheat Ridge ordinances, for work under this permit. (OWNER)(CONTRACTOR) SIGNED i ' ~-4"'OATEI' d / Description BUILDING DEPARTMENT USE ONLY ZoningxCtimmeFi~4 SIC : Sq. Ft. : Approval : Zoning : 9ui@ing'Comments:7 Approval : Pu blRqWb'Fff.G"dlri1i-mentsy Approval: Occupancy : Walls : Roof : Stories : Residential Units : Electrical License No : Company: Expiration Date : Approval: J a;rians;rceq. Plumbing License No : Company : Expiration Date : Approval: n la'Fi~!!Rei~ Construction Value : C q76c Permit Fee : ~ CJ Plan Review Fee : Use Tax: Total : Mechanical License No : Company: Expiration Date : Approval : ~ ~iaKWReqairea~ (1) This permit was issuetl in accortlance with the Orovisions set forth in yopur application anA is subject to the laws of the State of Cobratlo ana to the Zoning Regulations and BuilGing CoAe of Wheat Ritlge. Colorado or any other ap0liwEle orCinances of tne Ciry. (2) This permit shall expire il (A) the work authonzed is not commenced within sizty (60) days trom issue date or (8) the builtling authorizeC is suspenCed or aDandoneC (or a penotl of 120 days. (3) If Nis permit expires, a new permit may Ee acquired for a fee of one-halftne amount normally requircd, provitlcW no changes have Eeen or will be maae in the original plans and specifiwtions and any suspension or aEandonment has not ezcee7eC one (1) year. It changes are made or il suspension or aEandonment exceetls one (1) year, tull fees shall be paid for a new permit. (4) No work of any manner shall be done tnat will change the natural flow ot water causing a tlrainage Oro0lem. (5) Contractor shall notiy the 8uilaing Inspector twenry-four (24) Oouro in atlvance (or all inspec[ions and shall receive wntlen appmval on inspection rarE before proceetliing with sutCessive phases of the )ob, (6) The issuance of a permit or the approval of tlrawings anC specifications shalt not be constmed ro De a permit for, nor an approval o( any violation ol the provisions of the builtlin9 cotles or any other ordinance, law, rule or regulation. Building Inspector For Mayor THIS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION Property Address ; 3810 PIERCE ST Contractorticense No: : 18570 Company ; GiII Electric OWNER/CONTWiCTOR SIGNATURE OF UNDERSTANDING AND AC,REEMENT 1 here4y certiry that the setback disterroas proposedby lhis permN applicatton ere aaurete, and do not violate applicable otdiaancas, rub5 ot regulatbns of the: Ctty of Wheat Ritlge or covenanU, easementaocrestridbqsM Yeccrd;tAat all measurements shown, and allegetions made are accurate: Mat. l havaread 8nd anYee ta a6tde bv all conditlons oriMed on Mis (OWMER)(CONTRACTOR) SI Description : IWRE E AUST FAN Phone : 237-1483 Phone : 237 1483 Permit Fee : $45.00 Plart Review Fee : $0.00 Use?Tax; $6.00 Total: $51.00 BUILDING DEPARTMENT USE ONLY Occupancy : Walls : Roof : Stories Plumbing LicenSe No : Company : Electrical License No : Company : Ezpiration Date Approval : (1) This pertmt was issuetl MaEC . Regulaponaand.BuiMM C9tl (Z) This pamon9d Mr a ~ Peexpim AOd of(1) aband 2( (3) Mihispemfite)Vfires,eneW;p (5) (61 Expiration Date : Approvai : r S!C : Sq. Ft. : Residential Units Mechanfcai License Na : Company : Expiretion Date : Approvaf : a Rt forth in yopur applkation antl Is subiect ro the lawa ot Me Stete.of CdwaGO arM totlre Zoniig or any other appGCaWe orcHnances M the Ciry. . mmencetl within sucty (BO) days trom issue date ar (B) the 6uilalng autlrorized:ls auspenFkE a ee of one-Iwlf the amount rwmtally required; providedno changes havC been a wiil be made GI the antlonment has not axceadedone (1) year. If changes are madawMsuspension a abanEanmeM a natural Mow of water eausf~ a dralnape problem. (24) hours in atlvarwe tor all nspecliona antl shell receive written approval on inspection. cerU beTOre I specificafions shall na Oa conaWetl to be a pertnR fir, nor an approval W, amj viabtlon M Ua provisi0ns Building inspector S PERMIT VALID QNLY WHEN SiGNED BY THE CHfEF BUILDING INSPEGtOR AND MAYOR CALL: 234-5833 24 HOURS PRIOR TO INSPECTION DEPARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number : BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE Date : 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 Property Owner : Property Address Phone : Contractor License No. : Company r" CLc ~ i?s G- Phone OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certi(y that the setback distance5 proposed by this pertnit application are accurete, and do not violate applicable ordinances, rules or regulations of the Ciry of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this appliwtion, and that 1 assume full respqnsibility for compliance with the Wheat Ridge Building Code (U.B.C.) and all other applicable Wheat Ridge ordinances, for work under this pertnit. (OWNER)(CONTRACTOR)SIGNF(~-~/o"_ DATE Construction Value : j o ` Permit Fee : Plan Review Fee : Use Tax: Tota I : Description : 6,Lj i ae 7- BUILDING DEPARTMENT USE ONLY Zoitlfi-~0 SIC : Sq. Ft. : _ Approval : Zoning : Buifd_. (.'25ffi~ Approval: l]bl Approval: Occupancy : Walls : Roof : Stories : Residential Units : Electrical License No : Plumbing License No : Mechanical License No : Company: Company: Company: Expiretion Date : Expiration Date : Expiration Date : Approval: Approval: Approval: 9 WaGMa~ n 0 WmR~am r (1) 1Tis pertnit was Issued in accordance with the pmvisions sel IoM in yapur ap0licatlon antl is suDject to the laws ol the State ol Colo2do an0 to the 2oning Regulations antl 8uilding Cade of Wheal Rid9e. Colo2do or any other aOP~~~ble oNinances af the Ciry. (2) iTie pertnit shall expire if (A) the work authonzetl is not commenced within sicry (80) days from issue tlate or (B) the builtling authonied is suspendetl or abandoned for a penod ot 120 days. (7) If this pertnit ezpires, a new pertnrt may Oe acquired lor a fee ol ono-hall the amount nortnally required, Drovided no changes have Oeen or will be made in the odginal plans entl specifrations and any suspension or aOanAOnment has not ezceeded one (1) year. If changes are matle or if suspension or aDandonment exceeds one (1) year, full tees shall De paid br a new permit. (4) No vrork of any manner shall be done thal will change the natu2l Oow of water rausing a Arainage problem. (5) Contractor shall notify the Building Inspector twenry-lour (24) houB in aEvance for all inspections and shall receive wntten appmval on inspection wrd Oelore proceeEiing with auccessive phases ol t~e Iob. (6) The Issuance ol a permit or the epproval o( drowings and speufirations shall not be construed to be a pertnit for, nor an apProval o( any violation of the Drovisions of the huilding codes or any other ortlinance, law, rule or regulatiort Chief Building Inspector For Mayor THIS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION x m;~~R~t~mro's"~~~ , ~k9~"•:, M ,~-~~s~~'a~.,. . „ . ~ DEPARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number : 4809 BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE Date : 4/2/97 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 Property Owner : ' Property Address Contractor License No. Company 3810 PIERCE ST 18071 Sentry Fire & Safety Phone : 425-0300 Phone : 294 0708 OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certiy that the satback distances proposed by this parm(t application are accurata, and do not violate applicable ordinances, rules or regulations of the Cky of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that 1 have read and a8ree to ' e by all conditions printed on this application, and that I assume full responsibili mpliance with the Wheat RidgeBuilding Code (U.B.C.) and all other appliwbfe N(h idgp ordma s, for work under this permit. (OWNER)(CONTRACTOR) c .db Description : INSTALL`FIRE SUPPRESSION SYSTEM Construction Value : $1,200.00 Permit Fee : $41.25 Plan Review Fee : $0.00 Use Tax : $14.40 Total: $55.65 Electrical License No : Company : Plumbing License No : Company : Mechanical License No : Company : Expiration Date : Expiration Date : Expiration Date : Approval : Approval : Approval : ~ (1) This permit was issued in accordance wkh the provisions set forlh in yopur application and is subiect lo the laws of Ne State of Colorado and W fhe Zoning Regulations and Buildin~ Cotle of Wheat Ridge, Colo2do or any oNer applicable ordinances Mthe City. (2) This permtt shall expire d(A) the work authonzed is not commencetl within sixry (80) days from Issue tlate or (8) ihe bulltling authorizetl is suspended or abandoned for e period of 120 days. (3) It this permit expires, a new permit may De acquired for a fee of orie-hatt the artwurrt nortnalty required, provided no cliangec have been w will be made in the original plane and speciffca6ons and any suspension w abandonmenl has not ezceeded are (1) year. If chanpes are maCe or if suapension or abantlonment exceeds one (1) year, full feas shall be paitl lor a rrew permk. (4) No work ot any marxier shall be done Nat wlll change the naturel flow of water causing a dreinage problem. (5) Contracror ahall noUfy the Building Inspector twenty-four (24) hours in atlvance Por all inspedions and shall receive writlen approval on inspeclion cartlbefore proceadiing with successive phases of ihe job. (8) The issuance of a partnlt or the approval of drawings antl specifiwtlons shall not ba conshueC M be a pertnit for, na an approval ot, any violation of the provisions o` the iltli codes any ot oNi nce, law, rule or regulation. Inspector `rtHIS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEP BUILDING IMSPECTOR AND AAAYOR CALL: 234-5833 24 HOURS PRIOR TO INSPECTION DEPARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number : BUiLDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE Date : 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 Property Owner : ~FT(-2SG`a/ ~ ~F^~>L~2 /'C'i? ~'7c=✓r~t Cl,~~GP~/ Property Address : 3 9 / 0 P/r~"-ez Phone: Contractor License No. : / eC7/ I yzf-'-, 0 v Company: Sir_~nzr FirE ~ .S'-+'Y OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certity that the setback distances proposed by this pertnit application are accurate, and do not violate applicable ordinances, mles or regulalions of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abby all conditions printed on this application, and that I assume full responsibdd cortapliance with the Wheat Ritlge Building Code (U.B.C.) and all other appliwble Wh idge q~pinyyes, for work under this permit. (OWNER)(CONTRACTOR)SIG DATE 7'Z 9-7- Phone ZyI _0 Construction Value : /Zopor- _~td Permit Fee : Plan Review Fee : _ b Use Tax : Total : Description : ~,~ST,yL~~~ O~ ~2~ SJ~~~ SYfrt,•n iBUILDING DEPARTMENT USE ONLY Zohiny' Approval : Zoning : Approval : ?Qbl~ Approval : Occupancy : Walls : Roof : Stories SIC : Sq. Ft. : Residential Units : Electrical License No : Plumbing License No : Mechanical License No : Company: Company: Company: Expiration Date : Expiration Date : Expiration Date : Approval: Approval: Approval: n 0 iPlai mtffdm 0 ~fa~~ (1) TTis pertnit was issueA in accortlance wiU the pmvisions sel forth in yo0ur apPlicaGOn and is su6ject to the laws of the State of Coloratlo and lo the Zoning Regulations anE Builtliny CoCa o1 Wheat Ridge, Colorado or any olher appliwble ordinances ot the Ciry. (2) Th1s pertnit shall expire d(A) the vrork autnonzeC is not commenced within siriy (60) days /rom issue date or (e) the builaing autnoAZed is suspenEeC or a0andonetl lor a penod of 120 days. (J) It Uis permit ezpires, a new permit may Ee acquiretl for a lee of one-half the amount nortnally required, proviaetl no changes have been or will 6e made in the ori9inal plans anG speciflca0ons antl any suspension or abantlonmeiit has nol eaceeded one (7) year. If changes are matle or if suspension or abandonment eaceeds ona (1) year, full Ices shall 6e paid for a new Oermit. (4) No work of any manner shall Oe tlone that will change the naWral flax of water causing a tlreinage Oroblem. (5) Contractor shall notify the Building Inspector twenN-four (24) houn in atlvance lor all inspections and shall receive wntten appmval on inspection wrtl before proceediing wilh successive phases of the jo0. (fi) The issuanca of a permit or the approval ol drewings and specifications shall not Ee construed to be a permit for, nor an approval ol, any violalion ol the provisions ol the Duilding cades or eny otner ordinance, law, rule or regulation. Chief Building Inspector For Mayor THIS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION DEPARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number : 4760 BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE Date : 3/24/97 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 Property Owner : Property Address : 3810 PIERCE ST Contractor License No. : 17977 Company : K C A Companies Inc. OWNEWCONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certiry that the setback distances proposad by this pertnR application are accurete, and do not violate applicable ordinances, rules or regulations of the City of 1Nheat Ridge or wvenants, easements or restriclions of recoM; that all measurements shown, and allegations made are accurate; that I have read end ayr to abide by all conditia rinted on this application, and that I assume full respons i for co p jance wit e eat Ridge Building Code (U.B.C.) and all other applicable idge di nces ork nder this pertnit. (OWNER)(CONTRACTOR) SIGNED ~E Description : KITCHEN HOOD AND MAKEUP AIR SYSTEM Phone : 744-2422 Phone : 288 0119 Construction Value : $7,800.00 Permit Fee :12-s--5?) $158-89- Pian Review Fee : $0.00 Use Tax : Zq " $93-GB- Total: $231.60 Electrical License No : Plumbing license No : Mechanical License No : Company : Company : Company : Expiration Date : Expiration Date : Expiration Date : Approval: Approval: Approval: (1) . This pertnit was issuetl in accordance with the provisions set forth in yopur epplication and is subiact to the laws of the Siate ot Cdarado and ro the Zoning RegulaUOns antl eviltlin~ Code of Wheat Ritlge, Colorado or any oMer aDPlicaDle ortlinancas of the Ciry. (2) This permit shall expire if (A) the work authonzed is nat commencetl within sinty (60) days from issue date or (B) the builtling authonzetl is suspendetl or abandoned fOr a periotl of 720 days. (3) If this permit expires, a new permit may be acquiretl for a fee of ona-half the amount normally required, provitled no changes have been or will be matle in the ori9inal plans and specifications and any suspension or abendonment has not exceeded one (1) year. If changes are maCe or tt suspension or abandonmeM exceeds one (1) year, PoII fees shall be paiC for a new pertnit (41 No work ot any manner shall be done Nat will change the natural Oow o( water causinp a d2inage pmblem. (5) Contractw shall notiry the Building InsoecWr twenry-four (24) houn in atlvance for all inspeelions and shall receive written approval on inspection cerd before proceediirg with successive phases o# the iob. (6) The issuaQce of a permit or ihe approval of drawings end specifiwlions shall not be construetl lo be a pemiit for, nor an appmval of, any violation of the provisions of the buyqing codes or any other ortlinance, law, rule or regulation. tHding Inspector PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION DEPARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number : BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE Date : 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 Property Owner : ,7'q4PrS~'w ~")P vrt~iv Property Address : 38 rO CQ Phone: 7 4fq-- Contractor License No. : frJ `f fi, Company: KkC /3 coNpl41~deo_5 'TpC- Phone:~gg-Q~j 9 OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Construction Value I hereby certify that the setback distances proposed by this permit application are accurete, pefmit FBB : and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations Plan Review Fee : made are accurete; that I have read and agree to abide by all conditions printed on this application, and that I assume full respons'~~ity for co pliance 't the Wheat Ridge Building USe T2X : Code (U.B.C.) and all other applicable W e t Ridg o inan e, for ork under this permit. (OWNER)(CONTRACTOR) SIGNED G ~ ATE ~ I"' TOf81 : Description: ~Ft'-rGA.e}J He5od 4 Mak-u19 AAr sYst~M BUILDING DEPARTMENT USE ONLY ~womroOAIM SIC : Sq. Ft. : Approval : Zoning : BularnmGbT~fif~r~t~ Approval : P~iZ~Wb~'KB~SYHiYY~ifiF3'd Approval : Occupancy : Walis : Roof : Stories : Residential Units : Electrical License No : Plumbing License No : Mechanical License No : J~ y'? ~J Com an Com an ComPan ~ P Y~ P Y~ Y: kcf} ComP,py,,es J~c_ Expiration Date : Expiration Date : Expiration Date : Approval: Approval: Approval: 8 it31mmRm$Hmm 2 ~I~lRc9U~ ■ zm~~ (7) This permit was issued in accoMance with the provisions set forth In yopur aDGlicatlon and is subjecl to the laws of the Stale of Cobrado and to the Zoning Regulalians and Building Code o( VJheal Ridge, Coloredo or any olher applicable ordinances of the Ciry. (2) This permit shall expire d(A) the work authonzed is not commencetl within sixry (BO) days from issue tlate or (e) the building authonzeE is suspentled or abandoned for a period of 120 days. (3) It this pemit expires, a new pemit may he acquired for a fee of one-half Ne amount normally require4 proviUetl no changes have been or will be made in ihe original plans anA specifications antl any suspension or abantlonment has not ezceeAeC one (t) year. If changes are matle or i/ suspension or aDandonment exceetls one (1) year, full fees shall be paid for a new pertnit. (4) No work of ny manner shall be done lhat will change the naturel ilow of water causing a drainage Droblem. (5) Contrac hall notify ihe Building Inspector twenry-four (24) hours in advance for all inspections anG shall receive wntten approval on inspection card before proce ii wiM tcessive pha5es of therI'o6. (6) The i su ce opermit or the approvaL6~ drewings and specifcations shall not be construetl ro be a pemit for, nor an approval o( any violatlon of the provisions of t, b Idiqg' es or aJiy ott}Er ordignce, law, mle or regulation. Inspector For Mayor PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION a" p .r. s. II'Xll.' bUCT COLLAR SHIP LOOSE 3" AIR /tT '~F..FI (L ~ S~DL~ 4 - fIANC64 NSF/UL VAPOR PROOF LIGHT% ALUMINUM BAFFLE FILTERS I-T REMOVABLE GREASE CUP SECTIUN: 1-1 /2" = 1'-0" TYPE I , EXHAUST HOOD 18 GA. STAINLESS STEEL HOOD, FULLY WELDED PER N.F.P.A. CODE 96 ri~• 78" A.F.F. a ~ k : r Q 'O ~ - ~ n ~ ' (hC ~ n ~ - i ~ W k ~ b k ~ t ~ • ~7 . L~ ~ ,.C l ` ` - T rN tt j ~ ~ ~ .r L~ ~ln IQ _ ~ m m I~ ~ o ~ !n ~ ~ ~ ~ , , . , . DEPARTMENT OF PLANNINii AND DEVELOPMENT Building PermitNumber : 4645 BUiLDtNG tNiSPECT1ON D1ViS10N - 235-2855 C17Y OF WHEAT RIDGE Date : 2/24/97 7500 WE37 297'H AVENUE WHEAIT RiDGE. CO 80215 , Properly c7wner : Property Address : 3810 PIERCE ST Phone : 237-1483 Contractorticense No: : 18570 Compaoy Gifl Electric Phone : 2371483 OWNER/CONTf2ACt013 SICsMATURE OF UWDERSTANDING AND AGREEMENT Constructiort Value : $3,000.00 1 nereby certiry uNt flve setadi dMtances Proposed by tnis pemin licaaon aro axurate, Permit Fee : $57.00 and ao na vaiete apWkebb uroMpneec, rubs a regulanoos m n,e~'cay or vwreat wa9e or mvenants, eaaemenp or reafflcdoons of rocoM; that aR measurernents shown, and allegetions Plan Review Fee : ~$0.00 rAgde arb acmrats; thet 1~have rwel. eMt to aWtle by#11 conditlans priMed on thb ePP~~u~an. and that Bssume~ tuN nNpOn~i~my.~for compI~le~nca~ wIM tha Wl~eat Rbge 8uilding . . US8 Ta7C . ..$36.00 : . eods (U.B.G.) arM a~ dMlbr epplk~e.RYlge adinancea, r~rk un this pemrit. . (OWNERxCONTRACTOR) SlG b.; . DATE~~ TOfel: . . . ...$93.00 Descripton : RELf)CA OUFLETS-WALL DEMO BUILDING DEPARTMENT USE ONLY SIC : Sq. Ft: : Approrrai : Zoning; Approval ; ApproJal ; Occupancy : Walls : Roof : Stories : Residential Units ; ftectricat Lk:ense No : Plumbing License No ; Mechanicai License No : Company: Company: Company; Expiration Date : Expiration Date : Expiration Date : APProval : ApProval : Approval : ~ ~IM ■ ■ ~r (i) mia panmEwa Iausd in aanudancawa absaoviwom eae roim m yopur apqic.na, and 1s au 6ied m u,e lewe ama sMs.a adormo ana tr~ niszoneq. Reyulrtloew ardfktls W srtRIdps Colw~do or anY Whxapp~caqs atlinenees oflhe Ciry. . Tri4 Pe~n ahai ozpGS H~ {he ~wtWhlc auCqfized.b rwt mmmx~ced with7n abAy (EO) days fiom Imue date w(B) the 6uNdNpauMaefmd b suapended a eWntlaned forBpxfotl W i30 (3) q IMS patmil sKoriM arieM maY be aWUketl Wr a fae of one-liaM the anqunt noimalty requlretl,provNetl no cha~ea have Eeen w~ bs made M theoh0~~l P~ie dld eAW erH' tppn ot aCantlonment hes not exwedotl one (1) y~r. lf ~ are metle orfl sueP4~elonad abamla~meM ~Wl!{1} !WlfeNNMNbapdd~kti~pertN! . . . . (4) No waltdAny cAsd W done tlbt wXl t~enpa ihe neWrel lbw ot waterosusInp a Orelnepe pmbbm. (8) ConUeao~ Map la~' CN dupN1tl~MB .hipanor W~b~'-iwr (24) houB in stlvance for aB (napecUOns and shad iaroive wACen a~roval on InspBdbn card 6efore ~ (8) ~ibau nmx6da~partnk a Ifia .i//rovofft al Vdmxinge and apaGficallona shali not be consUUed l0 6e a permR tor, nor mapproval ot. arry vblalbn M1M provhbns W Me d~9nCk~A -des ehY ntlrer adinerxe, law, ~ule or reBulatlai. !7 ~ Chiet Bu~g ln TFfi3 PER#MT V/4LID ONLY WHEN SIGNEQ BY THE CHIEF BUILDING INSPECTOR AND' MAYOR CALL: 234-6833 24 HOURS PRIOR TO INSPECTION DEPARTMENT OF PLANNING AND DEVELOPMENT BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 Building Permit Number : Date : Property Owner: c~ ,-___L Property Address : 3'V/ 'D Contractor License No. : ~0 Company: l7i~ f 1t,9 sL (JI y, !z- c ~E' ~ Til! G Phone: c; 3 7 - / :~D Phone: OWNER/CONTR,4CTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurete; that I have read and agree to abide by all wnditions printed on this application, and that I assume full responsibiliry for compliance with the Wheat Ridge Building Code (U.B.C.) and all other applicable Whea Ridge ordinances, for work under this permit. (OWNER)(CONTRACTOR) SIGN~h - DATE-;' Description : ~ o c ct 7 7 ] - / / /✓`E~t~-t ~ BUILDING DEPARTMENT USE ONLY Zo'tii..iSgG3iiZY~fflitsi SIC : Sq. Ft. : Approval : Zoning : Approval : PIIbl _ Approval: Occupancy : Walls : Roof : Stories : Residential Units : Electrical License No : a e ~ Plumbing License No : Mechanicai License No : Company : Company : Company : Expiretion Date :_X -*~-9' 47 C7 Expiration Date : Expiretion Date : Approval: Approval: Approval: ~ ~'~~~YR~'~$_0_IEM a (1'-_I9ffIMMQUM~ 0 VIHS$M90iF~1~ (1) This permit was issue0 in accordance with the provisions set forth in yopur application antl is subI'ect to ihe laws of the State of Colorado and to Ne Zoning Regulations antl Builtlina Cotle o1lMheat RiEae, Cobrado or any other applicable ortlinances of ihe Ciry. (2) This permit shall expire if (A) the work authonzed is not commenced within siMy (60) tlays from issue date or (B) the Ouilding authonzed is suspended or abantlonetl tor a penotl of 120 tlays. (3) If this permit expires, a new pertnit may be acquirM ior a lee of onehalf the amount normally required, provided no changes have been or will be made in the onginal plans and specifications and any suspension or a0andonment has not exceeded one (1) yeac If changes are made or if suspension or abantlonment exceetls one (1) year, full fees shall be paiG lor a new permit. (4) No work of any manner shall be done that will chan9e the nalurol flow of water causing a drainage problem. (5) Conlractor shall nodry the Builtling InspeIXOr twenty-four (24) hours in advance for all inspections antl shall receive wnrien approval on inspection caM Oelore proceetliing with successive phases of the'ob. (6) The issuance o( a pertnit or the approval o~drewings and specifications shall not Ee conslrued to be a pertnit for, nor an approval ol, any violation of the provisions of the OuilEing codes or any other ordinance, law, rule or regulation. Construction Value : Permit Fee : Plan Review Fee : Use Tax : Total : Chief Building Inspector For Mayor THIS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION t{ bEPARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number : 4662 BUILDING INSPECTCON DIVISION - 235-2855 CITY OF WNEAT RIDGE Date : 2/26/97 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 Property Owner : Property Address : Contractor License No. : Company 3810 PIERCE ST 18007 Walrath Heating 8 A/C Phone : 425-0300 Phone : 232 4343 AWNEWCONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I heroby certity fhat. tfro setbeck distences proposed by this pertnk applicetion are accurate, and do nM violata appGcable ordinances, ruks or regutehons of the CRy of Wheat Ridge or covenants, easements or restridions of rocoM; that all measurements shown, and allegations made are aawrate; that I have read erW agreo to abide by all condkfons prtnted on this application, and that I assume tull responsibil pliance with the Wheat Ridge BuiWing VV1~atxmarwas, for work under ffiis pertnil. Code (U.B.C.) and all other applicable ~ (OWNER)(CONTRACTOR) SIGNE[i~~.r/ //.CJA DATEL / Description : VENTILATION DUCTWORK MODIFICATIONS Construction Value Permit Fee Plan Review Fee Use Tax Total $675.00 $27.50 $0.00 $0.00 $27.50 BUILDING DEPARTMENT USE ONLY SIC : Sq. Ft. : Approval : Zoning : Approval : Approval : Occupancy : Walls : Roof : Stories : Residential Units : Electrical License No : Plumbing License No : Mechanical License No : Company : Company : Company : Expiretion Date : Expiration Date : Expiration Date : Approval : Approval : Approval : 0 n-~ 0was (1) Re~pula~tlons aM BuildmIanCatlc o~t WfieRitlg e~tlo o~r eh lothe epplu~ IGk a~rtlir snacea of Iheecl to the laws M ihe State W Cobredo antl lo the Zoning (z) rnu permit shall e~ire it (nJ me wonc euthorized b not eommenced w~thm sixty (8~ tlays hom iscue dale or (B) the buildiMJ aNhorizetl la swperWetl or abandoned for a perlod of 130 tla (3) ~orbina~ da a a emeo~mnew na .ne ~ env baw~oane or abandon nmeM has rwl exuncoetled one (1~year, Ifchanpe ere made w n us~pena~on o~e madS n ir~~i (4) No work ot a,iy mmnM shall be done tliat will chenpe the mNial fiow of water causing a aninege prooiem. (5) Coninctor ahallrwdy Me BulWkig Inapecfor N+enry-MUr (24) houn in aavance ror aN inspsetions antl shall receive written apqovai on inepectlon card belare roceetllMp wlifi suaassive Dtiasea oi tl» 1ob. ~ions shall na oe consaued m ee a ~rnn ror, n« an a~rwei a, eny violaaon a me praiabns ~8) a me e~nal o°r a~ °e o am~~~ or° d alr~ep, law, ~ iub or .e~~u ei eor. Building Inspector S PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION DEPARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number : BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE Date : 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 Property Owner: C--712. ~ M0N %F+-L `4~7# Property Address : 3OIC /J, Phone : Contractor License No. : Company: W6i.R1g-7,q b4A. 6qVD•Phone: ~3~~3Y3 OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Construction Value : I hereby certiry that the setback distances proposed by this permit application are accurate, Pefmlt F00 and do not violate applicable ordinances, rules or regulations of the Ciry of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations Plan Review Fee : made are accurete; fhat I have read and agree to abide by all wnditions pnnted on this application, and that I assume full respons 'li for complian i e Wheat Ridge Building Use Tax :~n Code (U.B.C.) and all other applicable W id e ordina or er this permit. l.' (OWNER)(CONTRACTOR) SIGNED D TE ~ ~Total : 7,7,50 Description : ~~L~~~U~ ~p~~-1G'/} 71-O04IS BUILDING DEPARTMENT USE ONLY Zohi"n` ~oihi►i"e_nfs~ SIC : Sq. Ft. : . . Approval : Zoning Bulfdin~C3inments'~ Approval: P u bl ic~Vl yo~C:o~mefifs~ Approval: Occupancy : Walls : Roof : Stories : Residential Units : Electrical License No : Plumbing License No : Mechanical License No :/RP91-6i J Company : Company : Company : ~4~ ~ ~ /Vc~ &Nt~. Expiration Date : Expiretion Date : Expiretion Date :1_1/. qcQ' Approval: Approval: Approval: ~ EPlaq:Vqjred~ (1) This pertnit was issuetl in accordance wilh the provisions set forth in yopur appliration and is suDject to the laws of tAe Slale of Colo2CO and ro the 2oning Regulations anC Buildinq CoEe of Wheat Ridge, Colorado or any other applicaEle ordinances ot the Ciry. (2) This pertnit shall e:pire il (A) the work authonzeA is not commenced within sixry (60) tlays hom issue tlate or (B) the building authonzeO is suspentletl or abandoneA for a penod o1120 Eays. (3) If this pertnit expires, a new permM1 may Ee acpuired for a lee ot one-hali the amount normally required, provided no changes have been or will be made in the original plans anC specifications and any suspension or abandonment has not exceetletl one (1) year. If cnanges are made or i( suspension or aDanEOnment exceeds one (1) year, fulllees shall be paid br a new permit. . (4) No woB of any manner snall Ee done Nat will Uange the naNral flow of water causing a Arainage Oroblem. (5) Contredor shail natify the Buibing Inspector twenry-four (24) hours in atlvance (or all inspections antl shall receive written approval on inspection cartl bePore pmceetliing with successive phases ol the job. (6) The issuance of a permit or the approvat of drawings and specifiwtions Shall not De wnstruetl to be a pertnit for, nor an approval ol, any violation of the provisions of tne CuilEing wtles or any other ortlinance, law, rule or re9ulation. Chief Building Inspector For Mayor THIS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION 10q,RTME01"f QF PtANNIMG ANL1 QEVELOPMENT Building Permit Number : 4576 BVli.tWG tMlSf'F.4"ON DtVfStON - 235-2855 Ct'TY C?F WHEAT RIDGE Date : 2l12/97 75M'WESfi 38't'W AVENUE W^]EAT:R#t)GEs`CO 80215 Properq+ OremeF . Property Address : 3810 PIERCE ST Phone : 851-2526 ContraetoF Liaense No. : 18740 Camparry : LEE MAR ENTERPRISES, INC. phane : 232-0083 OWNERrCONTRqC'TOR S,FGNA'TURE,OF UNDERSTAMDING AND AGREEMENT Cor5~doqVpiue:, g75350.00 i narony oortry thac the eefliamc distaroes proposad bx mu permn ap~ ncauon'sro axunro, Pemit Fee $138.00 do aot vlclate I~bl~ r~iat~Ces, ruks or reguMtiorre of the eIry W WAesf RWge or cwvenahb, 4r fe~fdf~ bf rebwd: MataN meseuremeMS sMown, ana aibaaftm Pian Reviaw Fee : $0.00 madb an.aCalr9te; tli~t I hsvs reed aAtl W abide all mntlkWns Dhntod on thia - applicatWa, a~id tlu~ 1 iWt fw eom'noewith the Mlhoat Ridpo BWlding . Us8 Tax :.$68.20 Code (k1.6.~;} antl 8fl kYb10-: eat ordihWitxs, for work utder Mb permk:. . : . (OWNERHCOhITRA816NEC1 . DATF~Z ...TOt81 : - $226.20 . Description : REPLACE AMD ADD PLUM G RESTROOM FIXTURES AND REPLRCE GA5 LINE; ADO KFTCHEN SFW BttiLDiNG DEPARTMENT USE ONLY SIC : Sq. ft: : ; Ap~Proual`: Zoning : ApProval APPro`121: Ocq►pancy : Walis : Roof : Stories : Residential Unft: Electriaal License No : Plumbing License No : Mechanical Licehse No : Company;: Company : Company : : Expiration Date : Expiration Date : Expiradon Date APProval'. Approval : Approvai : ' (1) thM PemMtwYsMWeapt~tf»idMCe wdh the Prowbns aet rorih in WMa ePPMetlOn entl is aubiectSo the lews oi the 8tmb ot C*tCO and m Uw Zoning (2) yM ~4qds W l~Mptp~CoNxado ar e~ry other artlinenc olfiw CNy. tt~pea~hM tl9e WWIC aulhoffutl Is iwl cammencetl wNhl°~n ~a~ 90)dayn 1earom.ieeus tleb or (6) the Cutl~prp A4Va~IxW b wOpendetl or . ibMEOnW fG'tptll4Ni~pr . . (3) tt " Palttdt aakM, rrAw rW DO acquhad fa' a tee of on"alf 4ie emowt mrmelN rs7Wretl,no eftppet lws blw M MN be made in IM awwPhmad antCSm M abwMmmenthssn6l emoode tlane(t)Year. lfdianps6atemedlorNeWpwalOnordbe~donmeM. . sXo6eMOM(1) fd fb" duuYOlpddnew PertnN. . . . : (4) Nowakoa(rYMWOttlotMOwtwltlclieM.thairetuiellbwo}wabrC6ueMaadralnapapfobkm... . . ~ laauas~ r ta1m~' w-w-^^~r1, dventy-tour (24) houra M advancs tor au ~nepecuona end aheN rscetve wMlen e~pProved an NaPecUUn nb oefore(8) df$ MId ~ U~1. ~11~~sf 811tl OB bh811 IIO1118 CqMUYld aD b8 8 P~n }0r, 1qf B(18~fOY9~ Of, 9M1Y VIdBdM Of MIB PIDVhb119 the dtlie mdesa tvborreGulaUOn. . . . . . . C Building:lrlspector 18 PEFtAMT 1fAE.[D CtNLY WHEN SIGNED BY THE CHIEF BUItDING IMSPECTORR /tND NtAYCJR CALL: 234-5933 24 HOURS PRIOR TO INSPEG710N ' __U _l ,ir ~ 11 r`) II I pl \ CtI J_D_-1- I I 1 1 ~ II I t-I Ir-F~- i i I~ I i 01 II II \i _ I ~ I I I 1 / i t r If \ III , Ail 1 0 I _r r l l I I I I \ 2 -1 3- I' II II II REMOVE EXISTING I II 1 I DROP CEILING GRID ~I\I I I I O I IN THIS AREA ~I I\ ~J II i7 I I- - - -r' - - - - - - - - - - - - - - - - - - - 0 if if- \ ILI, \ ~ I ~ A II H I ~z~ II H Ili Ezw *II.~ mza\ II i it \w.`~+`t szll I T°\ W U H 11 II Wr~ E, N 0 11 II aqH I I - If D E MO L T T= ON P LAN SCALE: 1/8'= 1'-0" i ~ 4 WOR K NOT E S - REMOVE FLOOR TO \I~ CEILING NON-BEARING PARTITIONS. 1 i II lL~~ m 02 REMOVE 7' HIGH 0PARTIAL PARTITIONS. GENERAL NOTE: DASHED LINES INDICATE PARTITIONS TO BE REMOVED. MON NpN HZN OCN j tlp I ~ Caa OC 0 pC >m uv a U z a 0 d V Z 00 ~ Um sE p0 ~ mm H pry r) lux E a G a o H z F W t 0 C F C C L1 S F z a u w u E. Q u m C C u C. p u 0 CA F4 m~ L'0 ZUo H ,M au0 UO Xy Om CC 0 z~ ou m3 m SHEET NVMBEFx A - 1 I I i i~ _ _ IJ _I O II i' I I II li r-1 ur-~: F--In i II a.) 11 II 2 s I~ Jr it ii II 7 S S- WORK NOTES - O RELOCATE MOP SINK. REMOVE ABANDONED PIPING TO NEAREST BRANCH AND CAP. REMOVE ALL EXISTING O URNIALS, TOILETS AND ASSOCIATED VALVES. REMOVE ABANDONED PIPING TO NEAREST BRANCH AND CAP. REMOVE LJ ~I REMOVE LAVATORIES !'L AND ASSOCIATED PING T PI O THE FLOOR AND CEILING AND CAP - FLUSH WITH SAME. D © -EXISTING UNDERGROUN WASTE LINE: 2'- 6" DEEP it (APPROX. LOCATION) SUBCONTRACTOR TO PROVIDE ONE LINE DRAWING FOR CITY PERMIT D E MO L= T= ON P L UMB S N G P LAN SCALE: 1/8" = 11-0" 3 NEW LOCATION OF MOP O SINK O PROVIDE ROUGH-IN FOR ' NEW KITCHEN SINK 5 CUT FLOOR TO EXTEND U SANITARY PIPING TO NEW FIXTURE LOCATIONS. PATCH TO MATCH EXISTING. PROVIDE NEW FIXTURES AND INSTALL. LAVATORY TYPE: COUNTERTOP, OVAL SELF-RIMMING BRAND: CRANE MODEL 1-287 TRIM: DELTA 501WF HGM HDF, ADA APPROVED LEVER HANDLES. FLOOR DRAIN BRAND: ZURN MODEL ZN-415-B CLOSET BOWL CRANE 3-372 CLOSET TANK CRANE 3-543 CLOSET SEAT CHURCH 295C CLOSET BOWL CRANE 3-154E CLOSET TANK CRANE 3-544E CLOSET SEAT CHURCH 295C WALL HUNG URINAL CRANE 7-109TS ZURN FLUSH VALVE Z6003XL-WSI = N F= L L P L UMB = N G P LAN SCALE: 1/8^ = 11-0" MON t~pN H (ter OZN 001 r0I OC XUtl 0 Cn C~ 0 >n z- a 0 U h z~ 0 z po uo 7E NO Gf~ H 00 h uE E a N C a 0 Q r 2 H L 0 ~ 4 O h] C G a N z a u c:' u Q Oz E O G N ~ K LI L h. f] h F u N0 4Q nC 0 Wa U0 GU a 0 H •n C, :+o UO ~p0 PH 0 z4 O tl H- m3 n 5 HEFT N UMBER M_ 1 ~ WORK NOTES r4 O a a m a ~w- Z Wa aw 3 L E4 EQ L STO STO :7 - - 9'-0 tom' 9 O BOILER 0/0 O STO 0 0 - f MEN J KITCHEN 5 F1 O W C7 a O E A W r4 W x z J, l W a O H A W H W x z 'o STO WOMEN 1 DINING / PROJECTS u X11 CLERICAL TELE EQUIP m CLERICAL LOUNGE E E3 STORAGE STO MOVE EXISTING CABINETS TO NEW KITCHEN; REMOVE EXISTING FOUNTAIN. ITICI / \ i / 1O OFFICE V m OFFICE a E OFFICE 5Z E C4 - C•= r OFFICE U RECEPTION / WAITING l ENTRY 0 ~2 CLERICAL F LOO R P LAN SCALE: 1/8' = 1'-0" CONFERENCE DOOR SCHEDULE MARK SIZE FRAME REMARKS 1 3068 SC HOLLOW METAL 2 1 3070 STORE FRONT W/CLOSER S PANIC MOWN 3 3068 SC HOLLOW METAL W/CLOSER; 20 MIN X E%IST ING TO R£N.AIN - MATERIAL KEY ® NEW WALL WORK NOT E S = D 8'- 0" HIGH PARTIAL PARTITIONS O FLOOR TO CEILING 6" PARTITION O I HOUR CORRIDOR FILL IN DOORWAY O EXISTING 5" STEEL COLUMN © EXISTING 5" STEEL COLUMN LOCATE NEW WALL 6" WEST OF EXISTING COLUMN e rT~ W 2 A5 MON UQN OCN Her 001 cac or Xu~l 0 A Cm uo ~m z~ a U r a 'o z 0 u 4 0 JC H 0 10 H ON h ux F a G C a 0 z ti E w 00 u C C u ~z a G ' u u 0z £o l7 N C C LI w U h F u 140 4Q NO wa 00 au W, 0 H m au0 00 "pa FH 0 za 0w H" 03 M SHEET NUMBER A - 2 DEPARTMENT OF PLANNING AND DEVELOPMENT Buiiding Permit Number : BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE Date : 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 PropertyOwner:JC.°eAIN 2 Q lflP,,,t,qL ~dl.f t-I Property Address : 3~ 1 a 'e oeL'e- j r, phone :~`i' j 1•~2 S.z ll~ Contractor License No. :il y0 CompanY : J,ti f /0/A.i2 a P 21 S Y S `ir'.t'G . Phone : 2 3 2- o n43 OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify thal the setback distances proposed by this permit application are accurate, and do not violate appliwble ordinances, rules or regulations of the City ot Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application, and that I assume full r onsibility for compliance with the Wheat Ridge Building Code (U.B.C.) and all other applica le eat Ridge erdi nces, for ork under this permit. (OWNER)(CONTRACTOR) SIGNED ~ • DATE,2-11" 17 Construction Value : '735 0"0 Permit Fee : Plan Review Fee : Use Tax : Total : r~ • ~Q~Ma. Description BUILDING DEPARTMENT USE ONLY SIC : Sq. Ft. : Approval: Zoning : Approval: Approval : Occupancy : Walls : Roof : Stories : Residential Units : Electrical License No : Plumbing License No Mechanicai License No : Company : Company : A£E'/})at J7v'~QR~'~~Srs Company : Expiration Date : Expiration Date : Expiretion Date : Approvai: Approval: Approval: IN iP~3[i~'#ftNl'IM~ 0 KINIEM88U[[~Sfl= a 3f~ " (1) This permit was issuetl in accar0ance with the provisions sel forth in yopur applic~ation antl is sub~eq to the laws o/ the Slate ot Colorado anE to the Zoning Regula6ons and Buildinq Code of Wheat Ridge, Colorado or any other appliwble oMinances of ~e City. (2) This pertnit shall expire d(A) the work aulhonzetl is not commencetl wiNin sizry (60) days from issue date or (B) the building authonzed Is suspended or abandoned for a period of 120 days. (3) If this pertnit expires, a new permM1 may be acquired for a fee of one-half the amount normally required, proviEeA no changes have been or will be made in the original plans and specifcations antl any suspension or abandonment has not exceeEed one (1) year. If changes are ma0e or if suspension or abantlonmenl exceeds one (1) year, full fees shall be paid for a new pertnit. (4) No work of any manner shall be tlone that will change the natural flow of water causing a tlrainage problem. (5) Contredor shall notiry the Buildin9 Inspector Cxenry-four (24) hours in aEvance tor all ins0ectlons an0 shall receive wntten approval on inspection card be(ore proceediing with successive phases of the 1~ob. (6) The issuance of a permit or the approval o( tlrawings and specifications shall not be wnsWetl lo be a pertnit (or, nor an approval o[ any violation of the proNsions of the builtling cotles or any other ortlinance, law, rule or regulation. Chief Building Inspector For Mayor THIS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION i 1 i i x l J ~J 7; {r i s } C ~ i i 1 d f f ' i +Y t ~ i x f G~°. 7 fi F~ , ~ , b U.,, ~ ~ ~ ~m_ ~ _._.~~,_~.,~~,„,~,.u~a.,~._.....w_d . ~ r~  r 1 r ~ k 3m f AIAMW $TO rA6 ~ I ,5 w~yu.~¢v~,~,,•~1+:+s~R~`~r°r~.'?'rp'.an, . i~a~a~t~tsswt~ ys,iP;~v~ ~x ,~ti,~wy~it,~ 4~ i:. it~~s~~~?~sg'~-0v7'a5'Y,~~~'~9k5=?t~sw'hs~ , a *1~'C~'ftcyY~;g , Rk.+~'!~~Ns DEPARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number : 4692 fi BUILDING iNSPECTION DIVISION - 235-2855 ' CITY OF WHEAT RIDGE Date : 3/5/97 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 Property Owner : Property Address : 3810 PIERCE ST Contractor License No. : 18071 Company : Sentry Fire & Safety OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT 1 hareby certify that the setback distances proposed by this permk application are accurete, and do not violate applicable ordinancas, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measuraments shown, and allegaGons made aro accurete; that I have read and eQree to abide by all condRions printed on this application, and that I assume full resp na~bility for compliance wRh the Wheat Ridge BuiWing Code (U.B.C.) and all other applicable e~ RM i oi ces, for work under Nis pertnR. (OWNER)(CONTRACTOR) SIGNED DATE J~ 5- 7 Description : FIRE ALAR Phone : Phone : 294 0708 Construction Value : $4,000.00 Permft Fee : $89.00 Plan Review Fee : $0.00 Use Tax : $48.00 Total: $117.00 BUILDING DEPARTMENT USE ONLY SIC : Sq. Ft. : Approval : Zoning : Approval : Approval : Occupancy : Walls : Roof : Stories : Residential Units : Electrical License No : Plumbing License No : Mechanical License No : Company : Company : Company : Expiration Date : Expiration Date : Expiration Date : Approval : Approval : Approval : 0 ' 0 (t) This pertnR was issued in accortlance with the provislons set forth In yopur application and is sub1'ec[ to the laws M the State M Cdorado arM to the Zoninp RepulaWna antl Bulltling Cotle ot Wheat Ridae, ColoraCO or any other applicable ortlinanm of the Ciry. (2) Tltla permN shall expire 7(A) the work authonzed ia not commenced wkhin sizry (80) days from issue date or (B) Ne building authonze0 ia suspentled or auarwonea Tor s cerwa a 130 days. ns may be acquired for a fee of onehalf tlie artrount nomiely require4 povitled no Clianges heve bean a will be maGe in the (3) If Nla pertnil axpires, e new partM onginal plens and spedficetlo and any auspens~on or abendonment has rrol euraeded one (t) year. It ~anpes are meda or rf suspenalon or abendonment ~eee0s one (1) yesr, NII teea ahall be pe10 for a new pertniL , (4) No work of arry manner shall be tlone thal will change the natu2l Bow of water causinp a Eralnape problem. (5) ConUaclor shell rwtly the Builtlirre Inspeclor lwenry-four (24) houn in advance for all inapectlona entl shall receive wrillen approval on inspecllon caN before proceetliinpwiThsuccesaivepheseso~theW' b N N or the appmval otCrewings and spedficaGons shall not be consdued W be a pertnil for, nor an approval of, arry violatlon W the provisfons (8) ~he isguance of a perm M eAuilding coQea or any o4ber oMmance, law, n~le or regulatlon. Building Inspector THIS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION DEPARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number : BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGg Date : 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 PropertyOwner: ^5c"rN CC''Jf rr o~• Y+~e/1~'qf P4/7~h. Property Address : 3k/O P ~c e S 7- Phone : Contractor License No. : 19071 Company: lj''?'Jt-ry ~%re Y-Se~7c~ Phone: OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application, and that I assume full responsibility for compliance with the Wheat Ridge Building Code (U.B.C.) and all other applicable Wheat Ridge ordinances, for work under this permit. (OWNER)(CONTRACTOR) Description : ri° f(' gr r ~ ( BUILDING DEPARTMENT USE ONLY SIC : Sq. FL : Approval: Zoning : Build n Approval : PUb'I . Approval : Occupancy : Walls : Roof : Stories : Residential Units : Construction Value . y CnoQ.Q6 Permit Fee : Plan Review Fee : Use Tax : Total : Electrical License No : Company: Plumbing License No : Company : M'echanical License No : Company: Expiration Date Approval: In (1) This permit was Issued in ao Regulations and Building Co (2) This permit shall expire R(A) abandoned for a penotl of 12 (3) If lhis permit expires, a new 1 original plans antl specifratii exceeds one (1) year, lull fee (4) No work of any manner 5hall (5) Contracror shall notiry the BL proceediing with successive (6) Theissuanceo/apermitort of lhe building codes or any i Expiration Date : Approval: 0 ~ Expiration Date : Approval: 0 ce with the provisions sel forth in yoDUr applicatioa and Is sub'ect to the laws of the SWte ol ColoroCO antl to the Zoning Nheat Ridge, Coloretlo or any other applicable oMinances of t~e Ciry. ork authonzed is not commence0 within sixry (80) days from issue date or (B) the building authorized is suspended or may be acquired for a lee of onrhalt the amount normally required, provided no changes have been or will be made in the d any suspenslon or aban0onment has not exceedetl one (1) year. II changes are made or il suspension or abandonment I be paid for a new permit. ne ihat will change the nalural flow of water causing a drainaqe pro0lem. Inspector twenty-tour (24) hours in a0vance (or all inspections antl shall receive written approval on inspection card before s of Ihe ob. ~roval o~tlrawings and speciflcations shall not be wnstmed to be a permit for, nor an approval ol, any violation of the provisions rtlinance, law, rule or regulation. Chief Building Inspector For Mayor THIS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION z -s r- Z vr7 -.0 V STORAGE BOILER ` I ~ O / I it E 0 w a O U) I~ F R R w 0 O F P ~0-7 KITCHEN rl_ STO ~d WALLS 8' HIGH NO DROP CEILING oar 12 FOOT CELING 12 FOOT CELING I / IN OPEN AREA I~ O OFFICE CLERICAL \J/ °a OFFICE O RECEPTION O O rl c v -L lP' FIRE ALARM SYSTEM MS 9200 ~ ADDRESSABLE FIRE PANEL W/ BATTERY STANDY UDACT-F/ABS-8F DIGITAL DIALER W/PHONE CORDS & BACK BOX s SD-300 O SMOKE DETECTOR O 601/M301 RATE-OF-RISE HEAT DETECTOR W/ M301 MODULE O AT200/M301 F FIXED-TEMP. DET. 200 DEG W/M301 Cp BG-10LX ADRESSABLE PULL STATION GXS-4-15 STROBE SHG-24-15/75 STROBE/HORN GRAPHIC WALL MAP nOH r.<d O rl n ODi car or L XUr D C 0 < No r >n Z 14et Ridge Fire Protection District Plans Review 7 ti i ` Q Date:-5 o Reviewed by David M. Roberts ~de, Uniform Fire Code Certification #53275 u x Colorado State Fire Suppression System U Inspector Certification #92-173 z a u Comments:Q Qrav.Qe owl 0 z . G U Q O I gR~T bjln ~iW atii+anc~ w o. 0 U a ~ i-es'C-, ~~1tan.~a Na~l-~3a3. 3a OFFICE p s~ e 'L va viSEcS. azaresseRas~~ti7~e_ t'~ H h GO d UE h LO M !1 0 U0 CU H ~~so UO f• H ~r 0 'z4 0N, H- 03 n boY S HE ET N UMBER O OFFICE STO - O~ U 12 FOOT CELING IN OPEN AREA DINNING r, i OFFICE i; WALLS 8' HIGH NO DROP CEILING / 12 FOOT CE LING "I LlEPARtMENT pF PiANNING ANQ DEVELOPMENT Building Permit Number : 4411 r^ BUILOWC {MESPEC'tI0N t1lVfSIOM - 235-2$56 C!TY QPt1VF1EA17 R1DGE Date : 92131/96 7~q9 fi~S"C 297H AVEN11E YVHEq,T RIDGE.-CO 84215 d d+ . Properiy Ownei : Propetty AddrBas : 3810 PIERCE ST Phone : 744-2422 Contraetor'License No. : 19325 Company : Jim McNemy CM Phone : 744 2422 (3WNMR1G0Ii7$CAG7QR"t#AT19R6 CF 11MDERSTANDING AND AGREEMENT #30,000i00 theroEYc9Rif}'tl~C~.~ftllplCiC4"PVPOSW:dY,~sFMe~'appllCntlf~utixe~9ecuraM~ R@N1►M~@C`~ p~ 5397.00 snd do not vwf~ Ikaqte ontlMeiaoes, nftlk a regulaNom of ihe City of uVfieat Ridpe or ccvMarNs, a matr10010rw ot roopttt; tlaat ap ryenuromeMa shoxm, qnd albgatbns USe TSDC : $0.00 rrwte prf atqYa~s~ tllrt t have nW Rrrcl b ebkle by aN conCHicM hnted on thb . ' ~y ~ gy{b~ . Yp~iOA. ~ t ~pN CM M 1 IIq11C8 'Y ~7:06 Code(U.9.E.~~ ~Ft~tM vro~undsrth~spem#. '~o~iiF:~ ; . . !3 3/ (4~ER)(COM(YltALf'OR) Description : TE F! H , ' " ~ilfLDlNG DEPARTNi~N'f' US~'OPtLY ` SIC : Sq. Ft. : _ APPr'~~ , Zorting ; ApDrovat : lpprovgl : pccupgncy : Walis : Roof : Stories : Residential Units : Elec= iicense No : Plumbing License No : Mechanical'LicBnse No : ~Company : Company : Gompany r ExpttBtion Date : Expiration Date : Expiretion Date : Approygl; Apptoval : MProval : 'Twiw.-P+wftwaslwndin 4wortiarice wnhmeIi eutammyopur ap@ilmSnon aFwbw*Ct~ lawsatla Smuatcxwwdoenatotl~azuMw r ntlstNNNwet oraol!oMer aQinanasdihs (2) . ~ ,~,~nap'''"°"`wi~ Cv~w~ woix "a~~CW' u na aon.r~,wa w,mN`~p's~ (60)aar. hom beue a.te a(B) n,e aMna wuotxeu b.uy~rw.a or n~ql~ra aFy (7) fl~l~wle, ~may6mdWUketltoralesWone~liaMMearnouMnamWYn~irod,q~ nod~rpNlavsMaia~wWbsmeAelnlMMrtlny aa0an~ntharatexceaaeaane(1)1roar. 7tcnanpmaismWSauweperuY~oraEUao~M 97tcaeW C4ib ('1) tYW1~ b4 R~~ 1'~6wOdk9Fa~Y' 64dwy~~o-ptl~NtNF~diM~Wr~tflOVtdWe2m eA~aNnapeMOdem. . (6) t611pi~FlhtK ~~p~~Dqpy~,q'-~+r (24) hwn in aEwnoe M M~ enA eM91lCafw xftn eppoval on WMpictlon cnd bBfote (8) ~IWM~qiias~i pMfrYtnr~Yw: ~~a'/iWdl d~Y~wi~W Hntl eDedflcetione ahap mt he conetrued b be a Pwrnh fw, nw en ePPmvW a, vN'v1019tlm of tl» piwlabns Of pfda oe anY cBwr~ law, ~ub a reptNetlon. . . . . . ` tet Buifditag:inspector THI$ PERMIT VALI) 43Ati,Y WHEM SIGNED BY THE CHfEF BUILDlNG lNSPECTt1R AND MAYQR CALL! 234-683324 HOURS PRIOR TO INSPECTiON DEPARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number : BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE Date : 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 Property Owner :.~F_ F P-E Rs o~ CE~lTE2 ~02 q ~-~~--T~ Property Address : 3 t's( o PLC3 CLE 5-r ~ Phone : Contractor License No. : Company : J x n,t i4c, ~k 6Iwa 1 C./lA , LL9 N S? Z-c-Z~ Phone : 74L(-Zy L Z OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the Ciry of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegalions made are acturate; that I have read and agree to abide by all conditions printed on this application, and that I assume full res ~ ility for compliance with the Wheat Rid9e Building Code (U.B.C J and all other applicab e Whea f~idge or "nances,,~gr work under this permit. (OWNER)(CONTRACTOR) Description Construction Value : ; O omo, - i Permit Fee : Plan Review Fee : Use Tax : Total : BUILDING DEPARTMENT USE ONLY Approval: Zoning : Approval : RIIt3111:?V1(~, rn-imt§'~ Approval: SIC : Sq. Ft. : Occupancy : Walls : Roof : Stories : Residential Units : Electrical License No : Company : Expiration Date : Approval: it ommf~,i~Ql Plumbing License No : Company : Expiration Date : Approval : 0 iEl_MRSQOIt8i1~ Mechanical License No : Company : Expiration Date : Approval : 0 r ~q (1) This permit was issued in accordance with the provisions set forth in yopur appliwtion and is sub1'ect to the laws of the Stale ol Colo2do antl to Ihe Zoning Regulations and BuilAing CoOe of Wheat RiCge, Coloredo or any olher applicable ordinances of the Ciry. (2) This permit shall expire d(A) the work authonzed is not commenceG wiUhin si:ty (80) days irom issue Oate or (B) the builtling authorized Is suspentletl or abandoneA for a period of 720 days. (3) If this permit expires, a new pertnd may be acquire0 for a iee of one-half ihe amount normally require0, providetl no changes have been or will be made in Ue original plans and specilwdons and any suspension or abandonment has nol exceeded one (7) year. II changes are made or if suspension ar aUandonment exceeds one (1) year, full fees shall be paid br a new permit. (4) No work of any manner shall be done lhat will change the natural tlow ofwater causing a tlrainage problem. (5) ConVador shall notify the Building Inspector iwenty-four (24) hours in advance for all inspedions and shall receive wntten approval on inspedion card before proceediing with ccessive phases o( the IoD. (6) The issuance opertnilpr the approval o(tlyawings an0 specificatlons shall nol be wnstrue0 to be a permit for, nor an approval of, any violation of the provisions of the Duilding es o,9ny other ordinanceJiaw, rule or regulation. Chief Bylldrng Inspector For Mayor PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION R EMOD E L AND RE T RO F T T F O R JEFFERSON C E N T E R F O R ME :N T A L H E A L T H 3 8 1 0 NORTH P T E RC E STREET WHEAT R T D GE , C O L ORAD O SHEET 1 ND E X GENERAL NOTES n l- O COVER SHEET 1) THE GENERAL CONTRACTOR SHALL OBTAIN ALL PERMITS, LICENSES, INSPECTIONS AND PAY C- 1 S I T E P LAN / S U RVEY ALL FEES REQUIRED, A- 1 EX T S T I N G C OND T T TONS /DEMO PT-AN 2) THE MECHANICAL, PLUMBING AND ELECTRICAL SUB-CONTRACTORS SHALL OBTAIN ALL A- 2 FL Oo R PLAN PERMITS, LICENSES, INSPECTIONS AND PAY ALL FEES REQUIRED. A-3 D E T A T IS P LAN 3) THE GENERAL CONTRACTOR SHALL BE M- 1 P L UMB T NG P LAN RESPONSIBILE FOR THE PROTECTION OF ALL ADJACENT AND ADJOING CONSTRUCTION AND M-2 ME CHAN S CAL / HVAC P L AN SHALL TAKE CARE TO MINIMISE DAMAGE AND REPAIR AND/OR REPLACE ALL SUCH DAMAGE TO E-1 ELECTRTCAL LTGHTTNG PLAN IT'S FORMER CONDITION. E-2 E L E C T R T CAL POWER P LAN 4) THE GENERAL CONTRACTOR SHALL CLEAN-UP TOOLS, WASTE AND DEBRIS CAUSED BY THE WORK DAILY AND AS THE JOB PROGRESSES. MATERIALS SHALL BE STORED IN A NEAT AND ORGANIZED MANNER. MI ON ko pN ri Kr 0CN OOi rar or %ur 0 Cm w0 >r) zv w a u N z a 0 NC 0 of u~ NA H 00 h UE ti a z 0 0 . H z H w 4 w 0 y 0 O u C C w S E z a w w u Q o z x o w N C G wI~ u w w h F wo Cq F4 ww 0 wa u0 Cu w o H •n awo uo "qm CC 0 zH oG r~ 03 n SHEET NUMBER A - 0 Tw NORTH w OF EAT s COMY OF JAN STATE OF COLORADO -J n O _ S2 ~ w W f-. 8 ~ s u z4- z O PN 2tr.20' 763' aSSIO I MAY MM &()t K & STONE CaIERUAL 24r H h L s F- J 8b' C ty~gc x c:. a C S n.r I COLUMOINR SURVEYING, INC. 7573 S. AMOS Wa Littleton, CO SaI23 872-8006 IMPROVEMENT LOCATION CERTIFICATE I hereby codify that this improvement location cerilficate was prepared for CORNERSTONE. FINANCIAL CORPORATION that it is not a land survey plat or improvement survey plat, and that it 14 not to be relied upon for the estabii&hment,Of fence. Mill future Improvement lines, t further codify that the improvement; on the above described parcel, except utility connections, are entirelywithin the boundaries as 'shown, that there are no encroachments upon hie described premises by Improvements on any adjoining premises, except aa' there is no apparent .evidence or Sion of any easement crassing or burdening any part of said parcel, except as noted, S='I'E PLAN - SURVEY or othar rcol, except d, and that NON 'VON .tr;a OZN GOI Tar Or y,ur 0 CN Q0 >N z~ N N U z G c i] ~+u UU W A H o0 ry u~ F a N G a 0 4 F z F N H E G 0 C F 0 u u d F N U a u S o N N C N l: A G u h F N NO CC F~ N; 0 Na uo ~T 0 H •N N Ia0 00 "Qq FH 0 z~ ON H qJ N SHEET NUMBER C - 1 I I''`/ II II _T II 41l II it ` I, I - -r r I I I I\REMOVE EXISTING J,_ - II DROP CEILING GRID EJ I~ I l IN THIS AREA \ ! r- I ,iii !I II - II, ~ µ II ! \ \ Y 41 Q I. - H I z~ A I I , i I I I i F~ EC I II ~W~~ 5211 > x II soy' WZZ aQH I II II D E MO L I T T ON P LAN SCALE: 1/8" - P -O" i 1 =rr I 1 ~L 11011 ly WO R K NOT E S - REMOVE FLOOR TO L~ CEILING NON-BEARING PARTITIONS. REMOVE 7' HIGH PARTIAL PARTITIONS. GENERAL NOTE: DASHED LINES INDICATE PARTITIONS TO BE REMOVED. nON OQN rf~l 0&N 001 rac or Xur, 0 zm No >N Z_ A U z uo Z 0 UU 7E tD NI H 01 h uE h a 0 h, h Fz h L r 0 0 14 h t1 (ti G d h z a u u u £ 0 G N C C W p G h h u as hk N~ 0 r! a 00 u a 0 H (71 uG0 00 "A co OC z~ ON rf w 0J N SHEET NUMBER A - 1 STO ~ STO W c7 a BOILER 0 E Ca W O----------TI E. W a z O Ca - KITCHEN W a w 0 o / W Kc r~ ~ E U? OO 4 CE w O O z _i JJ OO r- W O a 0 H vZ Q w E W x z CLERICAL E (4 O 1 OOH -r O 0 STO 0/0 O STO a MEN WOMEN 1 V d Lv FI DINING / PROJECTS CLERICAL LOUNGE U E O0 O STORAGE STO OFFICE OFFICE L 9 m CLERICAL FLOOR P LAN SCALE; 1/8° = V-0` T v~ . o =O ~ r "I , m O OFFICE 1 V OFFICE OE O I '~ZOE~ zC RECEPTION WAITING ENTRY i2 (OL 1l CONFERENCE DOOR SCHEDULE MARK SIZE FRAME REMARKS 1 3068 SC HOLLOW METAL _ 2 3070 STORE FRONT W/CLOSER & PANIC HDWR 3 13068 SC HOLLOW METAL I W/CLOSER; 20 KIN X EXISTING TO REMAIN MATERIAL KEY ® NEW WALL 4JORK NOTES O 8'- 0" HIGH PARTIAL PARTITIONS A3 O FLOOR TO CEILING 6" PARTITION A~ 9 1 HOUR CORRIDOR Z ® FILL IN DOORWAY A3 O EXISTING 5" STEEL COLUMN © EXISTING 5" STEEL COLUMN LOCATE NEW WALL 6" WEST OF EXISTING COLUMN MON UON OCN F aoi a CaC Oe G Xur a F u C a o Cn 0 "A Ua H r >m z Ula v 4! H £ G.1 q u0 a 0 o H goo a - .l f] 0 ' z. a u zN , u o u o z o W a ~ o HE vc Z u m b3 ~ yUU ~ C N ~ ;fir u 0 H pA SHEET NUMBER A - 2 5/8' GYP. BOARD 3 5/8' METAL STUDS 0 16' O.C. PER BEAD I PARTIAL WALLS A~ 4 7/a' 5/8' 3 5/e' S/8' NOTE: FLOOR TO CEILING HEIGHT = 1z-O° 5/8- GYP. BOARD 3 5/8' METAL STUDS 0 1 O.C. EXISTING STRUCTURE ABOVE FASTEN SECURELY SECTION THRU TYPICAL PARTITION A~ 5/e cm. BD. 5/8' GYP. BD. b i ONE-HOUR CORRIDOR 2 4' 41hT1 CONCRETE SLAB N9TH FLOOR FINISH PER PWdS }-5/8- MET. STUD 0 24' O.C. SVSFENDED CEILING GYP. BD. E RATED DOORS AND ELIES 0 CORRIDOR TYP. NOT / TING CORRIDOR WALL EXIS EXISTING CONCRETE FLOOR 4' VLlYl VINYL BASE TYPICAL WALL BASE F, 3 B ETA = L S P LAN MON NQN Hkc OCN G01 CaC oe kur 0 40 ~N z~ G C x u c 0 u ll~ UO 7E UO 1C r~ .C om H a u 0 C r 4 z F W H 8 0 C C 0 4 d n C ~z a u u u a oz £ 0 G N C G U u n F 4 GO CA Frc N.. 0 Ga 00 Cu it 0 H Cl a0 00 FH C" 0 z~ 0N m3 N SHEET NUMBER A - 3 4 7/8' 5/8' } 5/s 5/8' n it JJ r u, it I I VVV i, ~ ''d%'\ ~ it O\ I~ WORK NOTES O RELOCATE MOP SINK. REMOVE ABANDONED PIPING TO NEAREST BRANCH AND CAP. REMOVE ALL EXISTING O URNIALS, TOILETS AND ASSOCIATED VALVES. REMOVE ABANDONED PIPING TO NEAREST BRANCH AND CAP. REMOVE REMOVE LAVATORIES AND ASSOCIATED PIPING TO THE FLOOR AND CEILING AND CAP FLUSH 141TH SAME. © EXISTING UNDERGROUND WASTE LINE: 2'- 6" DEEP (APPROX. LOCATION) SUBCONTRACTOR TO PROVIDE ONE LINE DRAWING FOR CITY PERMIT D E MO L T T T ON P L UMB T N G P LAN SCALE: 1/8'= 1'-0" ~s -S S- 5 3 NEW LOCATION OF MOP O SINK n PROVIDE ROUGH-IN FOR NEW KITCHEN SINK 5 CUT FLOOR TO EXTEND U SANITARY PIPING TO NEW FIXTURE LOCATIONS. PATC TO MATCH EXISTING. PROVIDE NEW FIXTURES AND INSTALL. LAVATORY TYPE: COUNTERTOP, OVAL SELF-RIMMING BRAND: CRANE MODEL 1-287 TRIM: DELTA 501WF HGM HDF, ADA APPROVED LEVER HANDLES. FLOOR DRAIN BRAND: ZURN MODEL ZN-415-B CLOSET BOWL CRANE 3-372 CLOSET TANK CRANE 3-543 CLOSET SEAT CHURCH 295C CLOSET BOWL CRANE 3-154E CLOSET TANK CRANE 3-544-E CLOSET SEAT CHURCH 295C WALL HUNG URINAL - CRANE 7-109TS! - ZURN FLUSH VALVE Z6003XL-WSI - T N F T L L P L UMB T N G P L AN SCALE: 1/8'z 1'-0" / H mON QQIN HNC' OZN lot v01 xur 0 0 Cm N0 ~m z~ u A x u a0 LI ;j l ~a 7 E nC H. 0 z h u£ H a a C a 0 ~ C+ N z H ~ p 0 C 4 O u C C L1 w F a u u oz S 0 h: m ~ C u L'. A u h N k' I10 CC jt r~N~ 0 as u0 CU ';J 0 H ,m auo UO 'Cm ~C O zu OG m3 m S HEFT NUMBER M - 1 ~ WORK NOTES c WORK NOT E S - O EXISTING RESTROOM EXHAUST FAN O NEW EXHAUST FAN GRILL, CONNECT TO EXISTING SYSTEM O EXISTING RESTROOM EXHAUST FAN C EXISTING EXHAUST FAN SYSTEM, 3 GRILLS MECHANICAL / HVA C P LAN SCALE: 1/8" = 1'-0" O EXISTING FINNED TUBE RADIATION TO REMAIN O EXISTING HEAT TERMOSTAT SOUTH ZONE O EXISTING HEAT TERMOSTAT NORTH ZONE C- \ EXISTING HEAT TERMOSTAT KT FAN COIL ' EXISTING ROOF TOP EVAPORATIVE COOLER SUPPLY EXISTING ROOF TOP EXHAUST FAN IN' MON C r iv .i " (yL)~r oxN 4 ooi a vaa E oa a xu~ 0 f7 G a Cn 0 9 Uo N >n ti u a rl 0 C u 0 ~ u u n z a u o ! o z L7 i ll! x 0 I _ Lz up' h: N 9 U~ 9 U; C 1L L7~C.FG L - H h ux w ao ao Ed N: 0 ~a u0 Gu 0 H •n P. C4 0 00 EH C~ 0 •z oa H" l03 M SHEET NUMBER M - 2 I~ ! i 9 ~~IL ~ ( Imo) 11 W 2 EF f [~o d i O,M 5b I/ 11 -Ji 0 103 E L E C T R= C A L L= GH T= N G P LAN SCALE: 1/8" = 1' 0" WORK NOT E S - O RELOCATE SWITCH FOR MAIN LIGHTING O NEW LOCATION FOR MAIN LIGHTING SWITCH O RELOCATE SWAMP COOLER SWITCH NEW LOCATION FOR SWAMP COOLER SWITCH O REMOVE OFFICE LIGHT SWITCH © DISCONNECT LIGHTING IN DROP CEILING IN THIS ROOM O RELOCATE RESTROOM LIGHT SWITCH ® NEW LOCATION OF RESTROOM LIGHT SWITCH; SWITCH TWO EXISTING LIGHTS SEPARATELY O RELOCATE KITCHEN LIGHT SWITCHES Q NEW LOCATION KITCHEN LIGHT SWITCHES DICONNECT LIGHTING IN DROP CEILING IN THE AREA 12 REMOVE LIGHT SWITCH FOR THIS ROOM GENERA L NOTES DISCONNECT ALL POWER TO RECEPTACLE OUTLETS IN WALLS TO BE DEMO'D ALL FIXTURES SHOWN ARE EXISTING REPLACE FAULTY BALLAST WITH ELECTRONIC TYPE SUBCONTRACTOR TO PROVIDE ONE LINE DRAWING FOR CITY PERMIT MON ID DN r1; a OC.N q0i car Or XU 0 Cn N0 ~m z~ u a U z o ~ll Z 0 VO 9E s;A uc AA H OW h uE h a h G Ci 0 NC 0 ua u0 CU 0 H .,n Q0 UO ao FH CC 0 z~ Oa R'A n3 n C a 0 z h u ;s 0 C C 0 ~i C G n S 'n Z .7 G Q I 0 C C u c u u h SHEET NUMBER E - 1 U F7 1 lil o WORK NOT E S - (E) EXISTING (N) NEW GND TYPE DUPLEX (N) NEW RECEPTACLE WITH GROUND cw FAULT INTERRUPTER D (T) TELEPHONE D (C) COMPUTER O 125 V 30 AMP LS-30 E L E C T R= C A L P OWE R P LAN SCALE: 1/8" = 1'-0" MON ~pN 0 z N X01 car OC Xur 0 C7 Cm u0 ~m uV a H a C1 z a 04 t~ F z H r. 0 C C 0 H u G C G ~ H z a u Q u C oz & 0 C1 co C C G u a h h u N0 as hQ Nr 0 r•a u0 - a U 0 H •m qG0 00 „Q PH CC 0 zH 4 0G H" m3 M SHEET NUMBER E - 2 COMMUNITY DEVELOPMENT DEPARTMENT Building Permit Number : 78025 BUILDING INSPECTION LINE -(303-234-5933) Date : 11/9/2004 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80033 - (303-235-2855) Property Owner: JEFFERSON CENTER FOR MENTAL HEALTH PropertyAddress : 3810 PIERCE STREET Contractor License No. : 21284 Phone: 303-432-5800 Company : Thunder Ridge Electric Co. Phone : 432-1222 OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurete, and do not viola[e applirable ordinances, rules or regulations of the City of W heat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurete; thal I have read and agree to abide by all conditions printed on this application, and that I assume full responsibility for compliance with the Wheat Ridge Building Code (U.B.C.) and all other applicable W heat Ridge~rdinances, for ork 4nder lhis permit. (OWNER)(CONTRACTOR) SIGNED - ek-~" DATE 11 'PI'-~y Valuation : $3,000.00 Permit Fee : $108.30 Plan Review Fee : $0.00 Use Tax : $36.00 Total: $144.30 Use: Description : SERVICE CHANGE AND WIRE 3 A/C UNITS AND 3 FURNACES BUILDING DEPARTMENT USE ONLY Zoning0ommentl* SIC : Sq Ft. : Approval Zoning BuPtdin~?Cammeiits;:r ~ Approval ^ Publlc Works Garrlm0nlts`,` l Approva : Occupancy : Walls : Roof : Stories : Residential Units : Electrical License No : Company: Expiration Date : Approval: Plumbing License No : Company: Expiration Date : Approval : Mechanical License No : Company: Expiration Date : Approval: (7) This permit was issued in accordance with the provisions set forth in yopur apDlication and is subject to the laws of the State of Colorado and to the Zoning Regulafions and Builtling Code ot Wheat Ridge. Colorado or any other applicable ordinances of the Ciry. (2) This permit shall ezpire if (A) the work authorized is not commenced within sixty (60) days fmm issue da[e or (B) the 6uilding authonzetl is suspentletl or abandoned for a period of 120 tlays. (3) If this permit axpires, a new pertnit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be matle in the original plans and specifcations and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. (4) No work of any manner shall be done thaf will change lhe natural Flow of waler causing a drainage problem. (5) Coniractor shall notify the Building Inspector twenty-four (24) hours in atlvance for all inspections and shall receive writlen approval on inspedion card before proceediing with successive phases of the job. (6) The issuance of a pe , itc~fFk approval of drawings an i iwtions shall not be consWed to be a pertnit for, nor an appmval o[ any violation of the provisions of 1 i jlnfyo~es or any oth law, rule or regulation. Please sign Terms and Conditions on reverse side of page. f WHE4 - COMMUNI7Y DEVELOPMENT DEPARTMENT Building Permil Number o q BUILDING INSPECTION LINE - 303-234•5933 Date: ` m CITY OF WHEAT RIDGE " 7500 WEST 29TH AVENUE WMEAT RIDGE, CO 80033 - (303•235-2855) APPLICATION Property Owner: i c ~ c~ ~[V~ Cr,1 !L- Fct'A1<ci. Nrn PropertyAddress: 3~iw p4c-i2'e t;), Phone: Contractor License No.: Company. ,T,11j,6iG'rf' ~?,d9C jr--/lGT7 L Phone: OWNER/CONTR4CTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances Droposed by ihis permit appliption are acwrate, and Go not violale applicable ordinances, rules or repulations of the City ot W heat Ridge or covenanis, easements a restrictions of record; that atl measurements shown, and allegafions made are accurate; that I have read and agree to abide by all wntlitions pnntetl on this application and Ihal I assume full responsibility for wmpliance with the Wheat Ridge Builtling Code (U.B.C) and all other applicabie Wheat Ridge Ordinances, for work un/Qer this permit. ~ (OWNERNCONTRACTOR):SIGNEDC.!"'A'' '7" -~'4~DATE (OWNER)(CONiRAGTOR):PRINTED DATE Value:$ Permit Fee:$ Plan Review Fee:$ Use Tax- Total:$ Description: 5cfL'iC ~ C Ir 4vgr - Lc i'Pe 3 Ax U.a; ~ j < 3 t ucJY1C~S Sq. Ft. addad Expiration Date:'17,/Dl/flS Expiration Date: Expiration Date: Approval: Approval: Approval: (1) This permit was issuatl in accordance wiM the provisions set forth in your application and is suDject W the lav+s o( the Siate of Cdorado and to the Zoning Repulations and Building CoOes ot Wheal RiOge, CobraOO or any other applipble wdinances of the Cily. (2) This permit shall ezpire if (A) the work authorized is not commenced wiMin sixty (60) days hom issue date or (B) the builtling autliorized is suspanded or abandoned for a period of 120 days. (3) 1f Mis pennit mepires, a new pertnit may be acquired for a fee of one-half the amount nortnalty required, provided no changes have been or will be made in the oripinal plans and spedfica0ons and any suspension or abandonment has not exceedetl one (1) year. If changes have been a if suspension w abandonment exceeAS aie (1) year, tull fees shall be paiC for a new permiL (4) No work of any manner shall be done tliat will change Me natural flow of vrater pusing a drainage problem. (5) Contractor shall nody the BuiWinp Inspector twenty-four (24) twurs in advance for alt inspections arW shall receive wntten approval on inspacfion prd befom procee0iny wiM suaessive phases oi the job. (6) The iuuance of a permit or the approval of drawinps and spedficatlons shall no[ be consWeE lo be a permit for, nor an approval ot, any viola6on of the provisions of the building codes a any oNer ordinance, law, rule or regutaGOn. Chie,j uiding fficial Electrical License No:57~• Plumbing License No: Mechanical License No: CompanY:7kx,ytdrr' pCk~c h k~)nt Company: Company: