HomeMy WebLinkAbout4335 Quay StreetCPSCO DATE: May 21, 2021 RE: 4335 Quay St, Wheat Ridge, CO 80033, USA To Whom It May Concern, As per your request, we have conducted a structural assessment of the building at the above address. PV solar panels are proposed to be installed on roof areas as shown in the submitted plans. The panels are clamped to rails which are attached to the roof with a lagged mounting system. The PV system (PV modules, racking, mounting hardware, etc.) shall be installed according to the manufacturer's approved installation specifications. The Engineer of Record and Exactus Energy assume no responsibility for misuse or improper installation. It was found that the roof structures satisfactorily meet the applicable standards included in the IBC 2018JRC RC 2018 and I EBC 2018 as well as the design criteria shown below: Design Criteria: Wind speed = 105 mph Ground snow load = 30 psf Roof snow load = 23.1 psf Roof dead load = 9 psf Solar system dead load = 3 psf Overall, the roof area is structurally adequate to support the PV alteration as per 2018 IEBC Sections 502.4 and 502.5. This letter was completed in accordance to recognized structural analysis standards, professional engineering experience, and judgement. Prior to installation, the on-site contractor must notify Exactus Energy if there are any discrepancies, or damages to the structural members, that was not addressed in the plan set. If you have any further questions, please do not hesitate to contact me. Acknowledged by: 05/24/21 V Q Digitally signed b David C. Hernandez ' 58 David C. HernandezDate: 20021.05.24 07:44:37 -04:00 Exp. 10/31/ 1 0�ILL, ` ELECTRICAL POWER & SAFETY CO. ELECTRICAL POWER &SAFETY CO. EP COOperating in: USA. Canada. Mexico P: 651.433.4550 Office Locations: MN - FL - NY - OH - TX - CA E: service@epsco.co A qualified person must be present at the time of a PV electrical inspection 1) Licensed master or journeyman electrician, RESIDENTIAL SOLAR PHOTOVOLTAIC SYSTEM 2) Residential wireman 3) NABCEP-certified solar installer capable of testing the rapid shut down system. TITAN 5 0 _ _. .. P O W E R 1 -855 -SAY -SOLAR 525 W BASELINE ROAD MESA, AZ 85210 EC.0101592 Digitally signed by David C. Hernandez David C. HernandeZ Date: 2021.05.24 07:45:48 -04:00 05,24,21 rr 52158 � Exp. 10/31 /21 � �t,; ��. P 0, tl_EETRICAL ROWER & SAFETY Gu. { Eldorado_ r , - Springii, Y NORTW •' WESTMINSTER� r A� r Ilrr , _ Broomfield ` II' ��nd�On Rocky Flats hladionai•NBRTII cENTRIAL ti '* 1 3'I WildiIfe WESTbAr T�` ® North9le1'1rr�Ir Fr ~ Refi,ge WESTER`, Federal hornton hitflghts / a' M Leydea - ,T) Rocky _ Derbylraunti� White I Y Woestmin$kar � Ranch Park i 4 I Twin L�IIt#� `-- .. -ADAMS CITY �rArsenal+� � RALSTON VALLEY - " -' National. Commerce Arvada City North Table _ 4335 Quay S1, Wheat _ N�RTtn Mountain Park � �• i ce:- Ridge. CO 80033, US � --- West T railhead __'_ - '�► ----- Wheat Ridge tA.•� � _ Golden Denver Zoo ► � _APPLEW100D ar Creek�fl� T West Pleas Int Deriver yon Park View" f -�_,�4y[f�r - Denver Botanic t s � .� yPE ! 3enesee Park -. ��--� V�lilliarTl F Lakewood Gardens Hayden Crean �3 Genese Mountain Park ' 5) u.a ) so! _ sovJr; (B Idledale Kittredge morrisdrl = Z85 - SOUTHEAST- - Q 2a� �, n Englewood *I \\ 11 c:= :vergreen NIA RST9N Mar aCherry CrL!t GOVERNORS. Creemvc>od State Parl, Indian kills- RANCH _.o. IIEL . - 11 4335 QUAY ST WHEAT RIDGE. CO 80033 a L' .►� d_ 1��- � 2.960 kW DC -STC / 3.000 kW -AC 22/MAY/21 SYSTEM SPECIFICATIONS SYSTEM SIZE: 2.960 kW MODULE: SILFAB SIL -370 NX NUMBER OF PANELS: 8 INVERTER: SE3000H-US (240V) OPTIMIZER: P370 RACKING SYSTEM: EVEREST RAIL 44X City of ZWheat idle MUNI"IY UEVElCyI'MENT APPROVED Reviewed for Code Comp[ianee mancs txaminer nate Y�ift of permit: Me issuanw of a permit or qWOf *ns spec*Orwnr and computabans shaft not be a permitlor, or an approval of,, oly viaraoon 10 any of the prov/06m al the budding code or of a1W 4`##y ardiwncess. PermiVs pmsunwng to ow a uthodty to viwam or coneI the pwimm of the- alit coda ar'er "no .of the City shall root be v9ftd AHJ: WHEAT RIDGE, CO UTILITY: XCEL ENERGY - CO GOVERNING CODE: IBC 2018 IRC 2018 IFC 2018 NEC 2020 EXACTUS ENERGY NEW AGE ENGINEERING +1 833 392 2887 208-888 DUPONT STREET TORONTO, ON SHEET INDEX C1 - COVER PAGE N1 - GENERAL NOTES S1 - SITE PLAN S2 - PANEL LAYOUT S3 - STRUCTURAL DETAIL E1 - LINE DIAGRAM E2 - ELECTRICAL CALCULATIONS E3 - WARNING LABELS Al - PANEL SPECIFICATIONS A2 - RACKING SPECIFICATIONS A3 - MOUNTING SPECIFICATIONS A4 - INVERTER SPECIFICATIONS A5 - OPTIMIZER SPECIFICATIONS A6 - SAFETY PLAN C1 - COVER PAGE GENERAL HOTES: TH E INSTALLATION OF FV SYSTEM SHALL BE IN ACCOR DANCE 'A ITH THE MOST R EC EN T NATIC N AL ELECTR _,C AND EU ILDIN 0 GOD ES AND STAND ARDS. AS AMENDED BY Js, -.l R ISD ICTION a4- - N - FV SYSTELAS SHALL BE PERMITTED TO SU FFLY A BU Il" Z) ING OR OTHER STRU CTUR E IN ADD ]O TO AN Y OTHER ELECTRICAL SUPPLY SYSTEIMi(S) [NEC 090-4(A)] : F EENT AND ALL ASSOCIATED- WIRING AND R INTECONNECTION SHALL BE THE INSTALLATIO::%J OF CHARM PERFORIVED OILY' BY QUALIFIED PERSONS [N EC 1590-A(C) ""IS -TING PLUME ING VENTS. IK ILIG PITS. S YEXHAUST OUTLETS VENTILATIONS INTAKE AR OPENINGS SHALL NOT 13E C OVERED 13Y THE SOLAR PHOTOVOLTAIC SYSTEM- • INVERTERS, MOTOR GENERATORS, PHOTOVOLTAIC MODULE PHOTOVOLTAIC PANELS, AC PHGTO VOLTAIC MODULES, SOUR CE -CIRCUIT COMBINERS, AND CHARGE CCIN TRO RS INTENDED FOR U!SE INFVSYS7Eh,IS!S,HAU.IBELtS7ED OR FIELD LABELED FOR THE FV APP LICATIGH NEC 090-4 (E)] 0 A_� _ OJ7DOOR EOUI IPMEN7 SH ALL BE NEMA 3R R A7ED (OR BETTER), IME LUD-IING ALL. ROOF MOU HIED TRANSITION BOXES AND SWITCHES. • k_14_ EQU IF-MEN7 SHALL BE PR OPERLY GR OUNDED AND BON DED IN AC; CORD AN CE WITH N EG AR TICLE 250. SYSTF-M G,=' DING SHALL BE IN AC CORD NC E WITH NEC 690.41 • EQUIPMEN 7 GROUN DING CON DUG TORS SLV%.LLER TH AN 6A SHALL COMPLY WITH NEC 260.120�G) • ALL FV:SXSTEM D C CIRC UI IT AND IN VER TER OUTPUT GOND UCTOR S AND E12UIPWNT SHALL BE PR OT EC TED AGAIN ST OVER URR ENT UN LESS STATED OTHERWISE IN NEC 690.9(A) OVERC URR ENT DEVICES USED IN PV SYSTEM DC C R CU 17S SHALL 13E LISTED FOR USE IN PV SYSTEMS [NEC 690.9fl] PV SYSTEM CIRCU ITS IN STALLED ON OR IN BUILD INGS SHALL MIN CLU DE A RAPID SH UTDOWIN FUNCTION IN ACC ORDANGEWITH NEC 690-12 D 13C 0 N HE C TIN 0 MEANS SHALL EE LO C ATED IN A %45113 LE, READ ILY AC CE 5 S -11B LE LOCATION [NEG 090.13(A)] ALL'S ING METHOD 8 SHALL BE IN ACC ORD AFI C E WITH NEC 090-31 CONN EC TORS 'EH ALL COMPLY WlITHj NEC 090-33 ALL GROU LADED C ONDU GTOR SHALL- COMPLY AITH NEC 200-15 PV SYSTEM G ON NECTEID ON TH E LOAD S ID E OF TH E SERVICE DISC ONNECTIN G MEAN S OF TH E OTH ERI SOU:)%C S) AT ANY DISTRIBUTION EQU IPMENT ON TH E PREM IISES SH ALL WET THE FaLLaWIN (3 [NEC 05.12] 1� EAC "-I SOURCE CONNECTION SHALL BE lAkDE AT ADEDIGATEID CIRCUIT BREAKER OR FUSIR i — 0 IS (Y-1 EIEC TING MEANS. [NEC 7D5. 12(A)] 2' THE P01,7Em. SOU RCE OUTPUT CIRCU IT CURRENT MULTIPLJED- BY 125 PERCENT SHALL 13E U SED IN A%eTmACI TY CALCULATIONS [NEC 705-12(p] 3) EQU IPLIEN7 0 ONTAINING OVER CURR EN T DEVIC ES IN CI CUITS SU PPLY4114G POWER TO A BUS BAR OR COI's DU GTOR, SHALL BE MARKED TO N DILATE THE PRESENCE OF: ALL SOU IAC ES [NEC 705 0 12�C]] 4) CIRCU IT ER EAKER, IF BACK FED, SHALL EE SUITABLE FOR SUC H OFERA71ON . [NEiC 7e G-5, 12(D -1] T I TA Iq S 0 L A R P 0 W E R TITAN SOLAR PHONE: 1 -855 -SAY -SOLAR WWW.TITANSOLARPOWER.COM PROJECT: 4335 QUAY ST MUNICIPALITY: WHEAT RIDGE, CO ZIP CODE: 80033 CLIENT: RORY PIERCE 2.960 kW DC-STC/3.000 kW -AC "HEN A BACFBF ED BIR EAKER IS THE METHOD OF UTILITY IN TER CONN EC TIO NI:j THE BREAKER SHALL, BE INSTALLED AT THE OPPO S]TE END OF THE BLIJ S BAR OF THE MlAIH EIREAHER- TO R ED UCE FIRE HAZARDS, DC FV SYSTEMS WILL BE, ECIJ IPPED WITH A OR CXJ ND FAULT PROTECTION SYST13M IN AC CORD AN CE WITH, N EC 090.4 l(B) "9H ER E GR OUND -FAULT PROTECT ION IS USED . TH E OUTPD T OF AN INTERACTIVE SYSTEM SH ALL, BE C ON NECTED TO THE SU PPLY S ID E OF THE GR OUND FAULT PROTECTION [NEC 705.32] ALL PLAQUES AN 17.) SIGNAGE REQU IREO BY TH E LATEST ED IT ION OF N AT ION AL ELECTR ICAL COD E. LABEL SHALL 13E ISE TALL IC OR PLASTIC , ENGRAVED CR MACH INE FR INTED IN A CONT RAST IN G C CLOR TO TH E PLAQUE. PLAQUE SH ALL BE UV RES ISTAN T F: EXPOSED TO SUN LJGHT.. ALL THE NEC REQUIREID WARINiN G S IGN S, MAR IQlN GS, AND LABELS SHALL BE POSTED ON EQU IPLENT AND DIS GO NN EG TS PIR 10 R TO ANY, I NSP EC T 10 N S TO EE PE, FORhV- D EY THE BU ILD IN G D E PARTIVE NT. C ON NECTORS SHALL BE OF LATCHIN G OR LOCF31NG TYPE. CONN EG TORS THAT ARE READ ILY ACCESS4ELE AND OPE RA71NG A7 OVER 30 VOLTS SH ALL R EMU IRE TOOL TO OPEN AP40 MARKED'DO NOT D ISCON NECT UN DER LOAD" OR "NOT FOR CUR RENT 114TERR UPTINGO. WHER, E MATING CONN EC TORS AR E NOT OF THE ID ENTdGAL TYPE AND BRAN D. THEY SHALL BE LISTED AN D ID ENI _nFIED FOR INTERMATABILITY, AS DESCRIBED IN THE MANUFAIC TCF ER'S INSTR UGTI0NS_ [IN EC 090_3 C) & (E.)(2)-] FLEABILE, FIFI E-STIS AFI DED CAE LES SH ALL, BE TERMINATED ONLY WITH TERMIN ALS, LUGS, DEVIC ES, OR C ON NEC TOR 8 "1 N AC CORD AN CE W I TH N EC 116_'14 WORK CLEAR ARMC ES ARC)U HD ELEC TR IC AL EQUIPNEN T WILL BE MAIN TAI NED PER N EC 116.26 �A)(1). 110-20(AX2) AND 110.20(AX3)- ALL EXTERIOR C ON DU ITS, FITTINGS AND BOXES SHALL BE RAIN -TIGHT AND A.FPR OVED FOR U SE IN WET LOCATIONS PER NEC 314.15. ROOFTOP MOUNTED PHOTOVOLTAIC PANELS AND MODULES S" ALL TESTED,,, LISTED & IDENTIFIED IN ACCORDANCE WITH UL1703 EACH MOD ULE TO BE GROUN DED USING TH E SU PFUED C ONNECTION F01N T PER KAANU FACTUR ER IS REQUIREMENTS.. ALL: SOLAR MODULES, EQUIPMENT, AND METALLIC COWONEN7S ARE TO 13E BONIDE0. IF THE EXJSTING GROUNDING ELEC7R ODE SYSTEM CAN NOT BE AER IF IED OR 15 ONLY METALLIC 'Ir FATER PIPING, IT IS TH E C 0N7RACTOR,'S R ESPONS MEAL ITY TO IN STALL A SUPPLEMENTAL GROUND ING ELE C TIR 0 D E_ DC C ONDU GTIOR S SHALL. BE RUN IN EIVT AND SH ALL BE LABELED, 'Ic NLI 710N D C C I:RC ji IT" OR Eou I'- EVERY5 FT. C CX%l F ID"el ANE Sig E VOLTAGE AT R ECTR C. J71LITSERVICE PRIOR TO C ON NEC71').113 INVERTER- VERIFY SERV IC=`m.l`OLTAGE IS A97H P4 N VER 7ER VOLTAGE OPER.A710NAL RA. JOE .j - 71- LI­rY TOm­`_ *- I �`l CTI- IED 13E FORE ACTIVATION OF PV SYSTEM. XF�1%E LE C NSIGN JOINTS AND ANGHOR COWIDUIT RUNS AS T"R I C A - CONTRAC7,:Dzl TO PROVIDE CO�NDJ171TE- REQo,..llRE_D FIER NEC_ AUTHOR: EE DATE: 22/MAY/21 REV- - N - GENERAL NOTES cay of 10-4 n IDO t 05/24/21 vm 52 IM Exp. 10/31/21 At P 0, ELECTRICAL POWER 6 SAFETY CO. NOTES: - SCALE AS SHOWN - ALL DIMENSIONS IN FEET UNLESS OTHERWISE STATED T I TA Iq tS - ,_ i5 QUAY ST DWELLING JUNCTIO CD JTION PANEL UTILITY MET AC DISCOr INVERTER PROPERTY LINE 1401-611 SAFETY PLAN: - INSTALLERS SHALL DRAW IN DESIGNATED SAFETY AREA AROUND HOME - INSTALLERS SHALL UPDATE NAME, ADDRESS, AND PHONE NUMBER OF NEAREST URGENT CARE FACILITY RELATIVE TO THE SITE BEFORE STARTING WORK PROJECT: 4335 QUAY ST TITAN SOLAR MUNICIPALITY: WHEAT RIDGE CO AUTHOR: EE PHONE: 1 -855 -SAY -SOLAR ZIP CODE: 80033 DATE: 22/MAY/21 WWW.TITANSOLARPOWER.COM CLIENT: RORY PIERCE2.960 kW DC-STC/3.000 kW -AC REV: - NEAREST URGENT CARE FACILITY NAME: ADDRESS: PHONE NUMBER: S1 - SITE PLAN SCALE: 111 05/24/2152 1w" � N V Exp. 10/31/21 �NAt.�� P 0 ELECTRICAL POWER 6 SAFETY CL LEGEND �M METER 36" FIRE ACCESS PATH 18" FIRE VENTILATION PVC VENT METAL VENT VENT BOX STRUCTURAL DELIMITER � SERVICE MAST O SATELLITE f ANTENNA SNOW GUARD � DOWNSPOUT ELECTRICAL MOUNT RAIL TOP CHORD CONIFEROUS TREES TREETOP: 30' CONIFEROUS TREE TREETOP: 56' DECIDUOUS TREE TREETOP: 49' DECIDUOUS TREES TREETOP: 57' ROOF PITCH: 14°, 22.50 SLOPED SHINGLE ROOF AZIMUTHS: 900, 1800 RACKING TYPE: EVEREST RAIL 44X MOUNT TYPE: QUICKBOLT MICROFLASHING CONIFEROUS TREES TREETOP: 56' ROOF 1 PITCH 22.5° AZM 180 ROOF 2 PITCH 14° AZM 180 ROOF 3 PITCH 22.5° AZM90 MOUNTING PATTERN SAMPLE I MAXIMUM MOUNT SPACING: 48" TOP CHORD SPACING: 24" MOUNT PATTERN: STAGGERED ALL HARDWARE, INCLUDING MOUNTING AND RACKING, TO BE INSTALLED PER MANUFACTURER SPECIFICATIONS. ROOF 1 AREA: 104.16 FT ARRAY AREA: 39.47 FT ARRAY PERCENT COVERAGE: 37.9% ROOF 2 AREA: 101.21 FT ARRAY AREA: 59.21 FT ARRAY PERCENT COVERAGE: 58.5% ROOF 3 AREA: 553.85 FT ARRAY AREA: 59.21 FT ARRAY PERCENT COVERAGE: 10.7% j SCALE: 1 PANEL TYPE: SILFAB SIL -370 NX PANEL SIZE: 72.13" X 39.4" NUMBER OF PANELS: 8 SYSTEM SIZE: 2.960 kW TITAN SOLAR PROJECT: 4335 QUAY ST MUNICIPALITY: WHEAT RIDGE, CO T I T A Iq PHONE: 1 -855 -SAY -SOLAR ZIP CODE: 80033 S 0 L Q R P 0 W E R WWW. TITAN SOLARPOWER.COM CLIENT: RORY PIERCE 2.960 kW DC-STC/3.000 kW -AC NOTES: - SOLAR PANEL LAYOUT SUBJECT TO CHANGE ACCORDING TO EXISTING CONDITIONS - SCALE AS SHOWN - ALL DIMENSIONS IN FEET UNLESS OTHERWISE STATED AUTHOR: EE DATE: 22/MAY/21 REV: - S 2 -PANEL LAYO U T 05/24/21 �'DO t 52158 Exp. 10/31/ 1 t��V P a ELECTRICAL POWER 6 SAFETY CO. MODULE SCALE: NTS PANEL TYPE: SILFAB SIL -370 NX PANEL SIZE: 72.13" x 39.4" RACKING TYPE: EVEREST RAIL 44X MOUNT TYPE: QUICKBOLT MICROFLASHING EVEREST 44X RAIL 01 IIr.KROI T WOODEN STRUCTURAL MEMBER NOTES: - SCALE AS SHOWN - DIMENSIONS IN FEET UNLESS OTHERWISE STATED FLASHING LAG SCREWS SHALL BE S.S. 5/16" DIA W/ 2.5" MIN EMBED IN RAFTERS/TRUSS TOP CHORDS 05/24/21!4CPF� $FO" 1 D 0I)o vm .0 52158 TITAN SOLAR PROJECT: 4335 QUAY ST MUNICIPALITY: WHEAT RIDGE, CO ���',� +�►� AUTHOR: EE S3 -STRUCTURAL DETAIL PHONE: 1 -855 -SAY -SOLAR ZIP CODE: 80033DATE: 22/MAY/21 Exp. 10/31/21 �L11iAL� T I T A Iq WWW.TITANSOLARPOWER.COM CLIENT: RORY PIERCE pSCO S 0 L Q R P 0 W E R 2.960 kW DC-STC/3.000 kW -AC REV: - ELECTRICAL POWER 6 SAFETY CO. NOTE: PV PRODUCTION METER NOT REQUIRED DUE TO THE SYSTEM SIZE BEING LESS THAN 10KW. STRING OF SILFAB SIL -370 EACH CONNECTED TO P37( Ln INVERTER SUMMARY Approval Notes: 1) P/V array system to have grounding system installed per Part III of Article 250 per 2017 NEC Article 690.47(A). 2) If LIFER ground in not available provide or verify supplemental ground rods per 2017 NEC Article 250.53(A)(3). 3) Natural Gas & Cold Water bonding per 2017 NEC Article 250.104(6) EQUIPPED WITH DC DISCONNECT DISCONNECT SWITCH LABELLED "PV AC DISCONNECT" WITHIN 10' OF BILLING METER Inverter Inverter Inverter Number Of Inverter Module Module Optimizer Optimizer String # of Circuit Stringy DC:AC DC Power AC Power ID Manufacturer Mode Inputs Input manufacturer Model Manufacturer Model Length Optimizers Current Power Ratio 1 SILFAB SIL -370 NX .o 1 a rEde P370 15A 2,60'�V .E INil1 S�OIarE�de E000H-US (240V) 2 2,011 31000W 0.99 2 SILFAB SIL -370 NX SolarEdge P370 O O 15A OW ONAL UTILITY METER FALLED BY XCEL ENERGY - CO "PHOTOVOLTAIC DNNECTED" EXTERNAL MAIN SERVICE PANEL 240/120 V 10, 3W, 200A EXISTING GEC f CRY d n 05/24/21 � N 52158 TITAN SOLAR PROJECT: 4335 QUAY ST MUNICIPALITY: WHEAT RIDGE, CO AUTHOR: EE E1 -LINE DIAGRAM Exp. 10/31/21 NAL +T I T A Iq PHONE: 1 -855 -SAY -SOLAR ZIP CODE: 80033 DATE: 22/MAY/21 WWW. CLIENT: RORY PIERCE PSCO S 0 L Q R P 0 W E R 2.960 kW DC-STC/3.000 kW -AC REV: - ELECTRICAL POWER 6 SAFETY CO. DC CONDUCTOR SCHEDULE MODULES TO JUNCTION BOX *TEMPERATURE FACTOR IS BASED ON 2% DRY BULB HIGH TEMPERATURE OF 31.4°C WITH A O°C TEMPERATURE ADDER THEREFORE RACEWAYS MUST BEAT LEAST 0.75 INCHES ABOVE ROOF AS PER NEC 310.15(B)(3)(C) Number of Conductor Conductor Conductor Base Ampacity *Temperature Fill Derated Circuit Min. OCPD EGC EGC EGC Temp. Conductor Ampacity Max Derated # of Neutral Ground Ground Conduit Conduit ID From Conduit Strings Material Type Size @ 90'DC Factor Factor Ampacity Current (If Required) Material Type Size No Limit CU PV Wire 10 AWG 40A 0.96 1.00 38.40A 15.00A 20A CU BARE 6 AWG N/A - Free Air JUNCTION BOX TO INVERTER *TEMPERATURE FACTOR IS BASED ON 2% DRY BULB HIGH TEMPERATURE OF 31.40C WITH A OOC TEMPERATURE ADDER THEREFORE RACEWAYS MUST BE AT LEASTO.75 INCHES ABOVE ROOF AS PER NEC 310.15(B)(3)(C) **TABLE ASSUMES ONE EGC PER CONDUIT. MINIMUM ONE EGC IS REQUIRED PER INVERTER PER CONDUIT. Number of Conductor Conductor Conductor Base Ampacity *Temperature Fill Derated Circuit Min. OCPD EGC EGC EGC Temp. Conductor Ampacity Max Derated # of Neutral Ground Ground Conduit Conduit ID From Min. EMT Size Strings Material Type Size @ 9000 Factor Factor Ampacity Current (If Required) Material Type Size 1 CU THWN-2 10 AWG 40A 0.96 1.00 38.40A 15.00A 20A CU THWN-2 10 AWG 0.50 in. 2 CU THWN-2 10 AWG 40A 0.96 0.80 30.72A 15.00A 20A CU THWN-2 10 AWG 0.50 in. AC CONDUCTOR SCHEDULE T1 I T A Iq S 0 L A R P 0 W E R TITAN SOLAR PHONE: 1 -855 -SAY -SOLAR WWW.TITANSOLARPOWER.COM PROJECT: 4335 QUAY ST MUNICIPALITY: WHEAT RIDGE, CO ZIP CODE: 80033 CLIENT: RORY PIERCE 2.960 kW DC-STC/3.000 kW -AC AUTHOR: EE DATE: 22/MAY/21 REV: - E2 - ELECTRICAL CALCULATIONS C" of 05/24/21 Exp. 10/31/21 0 plt.�� CASCO ELECTRICAL POWER 6 SAFETY CO. AC Circuit 125% OCPD Conductor Fill Ambient Temp. Conductor Ampacity Max Derated # of Neutral Ground Ground Conduit Conduit ID From To Phase Material # of CCCs Ground Voltage Current Multiplier (If Present) Type Factor Temp. Factor Size @ 75°C Ampacity Ampacity Neutrals Size Type Size Type Size 1 SE I NV1 AC Disconnect 1 10 240 (V) 12.5 (A) 15.6 (A) 20 (A) CU THWN-2 2 1.00 31.4 (°C) 0.96 8 AWG 50 (A) 55 (A) 52.8 (A) 1 8 AWG EGC THWN-2 10 AWG EMT 0.75 (in.) 2 AC Disconnect 1 POI 1 10 240 (V) 12.5 (A) 15.6 (A) 20 (A) CU THWN-2 2 1.00 31.4 (°C) 0.96 8 AWG 50 (A) 55 (A) 52.8 (A) 1 8 AWG EGC THWN-2 I 10 AWG EMT 0.75 (in.) T1 I T A Iq S 0 L A R P 0 W E R TITAN SOLAR PHONE: 1 -855 -SAY -SOLAR WWW.TITANSOLARPOWER.COM PROJECT: 4335 QUAY ST MUNICIPALITY: WHEAT RIDGE, CO ZIP CODE: 80033 CLIENT: RORY PIERCE 2.960 kW DC-STC/3.000 kW -AC AUTHOR: EE DATE: 22/MAY/21 REV: - E2 - ELECTRICAL CALCULATIONS C" of 05/24/21 Exp. 10/31/21 0 plt.�� CASCO ELECTRICAL POWER 6 SAFETY CO. WARNING ELECTRIC SHOCK HAZARD TERMINALS ON BOTH THE LINE AND LOAD SIDE MAY BY ENERGIZED IN THE OPEN POSITION [NEC 690.13(B)] PLACE THIS LABEL ON ALL DISCONNECTING MEANS WHERE ENERGIZED IN AN OPEN POSITION WARNING PHOTOVOLTAIC POWER SOURCE [NEC 690.31(D)(2)] PLACE ON ALL JUNCTION BOXES. EXPOSED RACEWAYS EVERY 10' WARNING POWER SOURCE OUTPUT CONNECTION DO NOT RELOCATE THIS OVERCURRENT DEVICE [NEC 705.12(8)(3)(2)] PLACE THIS LABEL AT P.O.C. TO SERVICE DISTRIBUTION EQUIPMENT (I.E. MAIN PANEL OR SUB -PANEL) IF APPLICABLE WARNING THIS EQUIPMENT FED BY MULTIPLE SOURCES. TOTAL RATING OF ALL OVERCURRENT DEVICES EXCLUDING MAIN SUPPLY OVERCURRENT DEVICE SHALL NOT EXCEED AMPACITY OF BUSBAR. [NEC 690.56(C)(2)] PLACE NO MORE THAN 3.3FT FROM SWITCH SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUT DOWN PV SYSTEM AND REDUCE SO �P� �s �� SHOCK HAZARD IN THE ARRAY. [NEC 690.56(C)] PLACE AT MAIN SERVICE PANEL PLACE THIS LABEL WITHIN MAIN SERVICE DISCONNECT (OR ON OUTSIDE DISCONNECT OF OPERABLE WITH COVER CLOSED) CAUTION: SOLAR ELECTRIC SYSTEM CAUTION CONTAINS MULTIPLE POWER SOURCES [NEC 705.12(8)(3)(3)] PLACE THIS LABEL AT [NEC 705.12(C)] PLACE LABEL ON ALL EQUIPMENT CONTAINING P.O.C. TO SERVICE DISTRIBUTION EQUIPMENT OVERCURRENT DEVICES IN CIRCUITS SUPPLYING POWER (I.E. MAIN PANEL OR SUB -PANEL) IF APPLICABLE TO A BUSBAR OR CONDUCTORS SUPPLIED FROM MULTIPLE SOURCES NOTES: 1) ALL LABELING USED OUTDOORS MUST BE ENGRAVED METAL, UV STABILIZED ENGRAVED PLASTIC OR OF A MATERIAL SUFFICIENTLY DURABLE TO WITHSTAND THE ENVIRONMENT INVOLVED. VALUES HAND WRITTEN OR IN WRITTEN IN MARKER ARE NOT ACCEPTABLE PER NEC 2020. 2) LABELS USED INDOORS MAY BE MADE OF DURABLE VINYL OR PAPER 3) DO NOT COVER ANY EXISTING MANUFACTURER APPLIED LABELS WITH INSTALLATION SPECIFIC LABELS 4) LABEL COLORS CHOSEN PER NFPA 70 2020 DIRECTION THAT ANSI Z535-2011 BE USED 5) ALL FORMATTING SHALL COMPLY WITH NEC 2020 6) ADDITIONALLY, IT IS HIGHLY RECOMMENDED THAT THE INSTALLER ATTACH A LABEL WITH THE COMPANY NAME AND CONTACT INFORMATION AT THE INVERTER 7) ALL WARNING SIGNS OR LABELS SHALL COMPLY WITH NEC 110.21(8) TITAN SOLAR PROJECT: 4335 QUAY ST MUNICIPALITY: WHEAT RIDGE, CO T I TA 11 PHONE: 1 -855 -SAY -SOLAR ZIP CODE: 80033 SOLAR P O k,�� ER WWWTITANSOLARPOWER.COM CLIENT: RORY PIERCE 2.960 kW DC-STC/3.000 kW -AC [NEC 690.13(B)] ALL AC DISCONNECT SHALL BE LABELED lqv DC PHOTOVOLTAIC DISCONNECT [NEC 690.13(6)] ALL DC DISCONNECT SHALL BE LABELED [NEC 690.54] PLACE LABEL AT "POINT OF INTERCONNECT 1" [NEC 690.53] PLACE AT INVERTER 1 FORMAT 1. MINIMUM 3/8 INCHES LETTER HEIGHT 2. ALL LETTERS SHALL BE CAPITALIZED 3. ARIAL OR SIMILAR FONT (NON -BOLD) PHOTOVOLTAIC SYSTEM CONNECTED UTILITY METER SHALL BE LABELED PHOTOVOLTAIC AC DISCONNECT AC DISCONNECT SHALL BE LABELED REFLECTIVE, WEATHER RESISTANT MATERIAL SUITABLE FOR THE ENVIRONMENT (USE UL -969 AS STANDARD FOR WEATHER RATING). DURABLE ADHESIVE MATERIALS AUTHOR: EE DATE: 22/MAY/21 REV: - E3 - WARNING LABELS 05/24/21 17�p �tks Ns; _wE_t9"qlN ib A r:�� fel vm -qo 52158 Exp. 10/31/21 {%NAt. P 0 ELECTRICAL POWER 6 SAFETY CO. rpp- M 1111L S 0 L A R larjAK161�'Emp JUST ER 1 6A r 5 )k- -IN- 01 B NILE A. AA F%CDXT IL TIME NDUSTRY LEADING WARRANTY I* Titan Solar Panel is manufactured by Silfab Solar ind, includes an industry leading 25 -year product rormanshlp and 30 -year performance warranty. AAXIMUM ENERGY OUTPUT .everaging over 35+ years of worldwide %perience in the solar industry, Silfab is dedicated to uperior manufacturing processes and innovations uc has Bifacial and Back Contact technologi'es, to ,nsure our partners, such as Titan Solar have the 3test I n so la r I nnovation. SIO RTH AMERICAN QUALITY 'A fab is the leading automated solar module nanufacturer in North Merica, Utilizing rem lum qwl it:y materials and strict quality control nanagement to deliver the highest efficiency, wernlum quality PV modules. Has"M BAA / A RRA C OM P LI A N T These panels are designed and manufactured to meet Buy Ame- rican Act Compliance The US State Department, US Military and FAA have all utilized Silfab panels in their solar installations. 1H LIGHT AND DURABLE Engineered to accommodate high wind load conditions for test loads validated up to 400OPa uplift The light -weight frame is exclusively designed for wide -ranping racking compatibility and durability EQUALITY MATTERS Total automation ensures strict quality controls during the entire manufacturing process at ISO certified faciliti-Eks T I T A 11 5 0 L A R P 0 W E R Iii DOM ESTI C S U PPORT I S ERV I CES Our 50 Ot N-cirth American team is rea dy to hell p Ti to n Sol a r win the hearts and minds of custorniers, providiN customer service a nd produc t d elivery that is di rest, effic le nt a nd I octal 1H AESTHETICALLY PLEASING I -profile residential or A] I blas: k sl eek design idea I for high I I commercial applications ;NWHE PID RESISTANT PID Resistant due to advanced cell technology and r-nat-i--ii- I a I S,A_ lec t ion . I n ac cords nce to I EC 62804-1 - OAA TITAN SOLAR PHONE: 1 -855 -SAY -SOLAR WWW.TITANSOLARPOWER.COM Electrical Specifications SIL -37O NX mono PERC�111111110����� Test Cancitiorz STC N OCT M *did* 140M W, LYS Mmirnurn power yolta;p CVprnmc) ]pan circuit vc1t3g!(V6r.) Short drcuit current On) W1 370 V 37.2 A 10.0 V A 44.8 10.6 MDJLJQ e5ciency % 201, Mwimurn systern voltap (VDQ V Swim fuse Ttm_ A PkiwarToleriiiincs WP Moa uran wa cm t" ww STC 100 0 W.Wa - " t 5 - Twine ro tau m 2S "C - N= KmO WNn' ■ AV. LS - MM Lr,@..m , u r4WU my 3% Sun i rm 6tcr c d kx&6 con r4fw4m ca m *Ju 6s frcm Fram Nsfw I ndk4ke. E 6ctr cd c 6 rectf risti rrmy y ry by IM ord pow w by tl- 3 .Tomporaturo Ratings Ta"Ywvturn CamAdant kc 1000 7WTpuature Coaffident We 20 Torperamm Qwffi(ient PMW Glass q_31X SIL -570 NX tnom PERC (I- 064 %PC -0.26 %PC -0.36%FC NOCT (± 20C), 2 0 Para t ir, jq to m p Gra tu r e 33.7 Mecivnical Proporti4s and Cccnpor4nts 7.9 Module weight 402 Dirn"icvs (H x Lx D) 63 Muirnum, surfitca load fivindAnawr 4.2 1000 o 1 in at 51.6 mIII 20 66 - S mono- PERC - '5 busbw, 62.25 x 6"5 in q_31X SIL -570 NX tnom PERC (I- 064 %PC -0.26 %PC -0.36%FC NOCT (± 20C), 46 OC 0 Para t ir, jq to m p Gra tu r e -40f+:95� Mecivnical Proporti4s and Cccnpor4nts SIL -370 NX mono PERC Module weight 44±O A lbs Dirn"icvs (H x Lx D) 72.13 in x 39.4 in x 1.5 in Muirnum, surfitca load fivindAnawr 83.5A1 . 9 1 blfe2 Hail impact rwisunce o 1 in at 51.6 mIII Cel6 66 - S mono- PERC - '5 busbw, 62.25 x 6"5 in Glass 0.126 in hilb triiinarniumnou, twripwwd, DSM anti -rqAect" coating Cab I as a in d co rn coc to rs (rvfw im i ron Lnion ma mail) 47.2 in, o 0.22 i n, M C4,fircrn Six u LA i Back3heat H th durab i I ity, smperior by4T and UVr=ktancorntJfi-laywdie1actAc filen, ftxwind-fiwPVbwckJ�[ Frame Anodized Aluminum (Sack) Bypam dojm 3 c1c<6-30SQ045T(4W nmcDC 61cckingwaltage, 3OAmm fcr•r�rd r*<tiFowJ current) Junction Box UL 3730 Cartif6d . I K 6279C GartificA, I P67 rated SIL -370 NX mono PERC Modulle Prod Lxt workmanshowarTanty 25 years" br*2ar promeor p6rforTzncra guarantQQ30 ymrs 207.1% and 1a +6 91.6% grid IT' year 2:85.1% and 25 r 2: 92.6% and 3 120' V ew " r be�� L-370 NX mono PERC - U LC ORD 01703, U LT703, CEC listedens I U L 612154 -1 -If- 2, U L 617310-1f-2, product IEC 61215 -V -1-11-2'"c_ 1 E -C 6T730 -V- ', C&A C22 -2"T7304-2- I EC 62716 A wrrm im Corm io n; I T701:20'11 So k M is;t Carra6 an 9!q99 U L Am P ati nig Two—z— Fwwry I509001:2015 A I I i raTa s au: a pri C A ftm i -a Calffania M ol ul a s Nr Rai Lar. 26 OM od u iv. P, -r P -J I in: 26 Pa I 4c s F! r Truck: 34 0 A I kc s Rear Truck: 32 Molulas Por Tnick: 884 MModu6s Pet Truck: 832 *A Wa 6 rq. Paz d d -ba Saixy and Axion Ma vA fio r m o umvq &pic 6:j d c4m in d Lefcxe hard iri & irmEj I it a nd 0P;fZ6q mxlulvr. "12 y;Ar -x c iird;kk m 2 5yaj rs su b.' a to reek rmim an d and a . o ns o Lrd in ad u redo r "Wi rn n ce n www_qiR2b%d;r. ccfn "Kv-6fica-rion and CE -C lisarq in pragw. PAN files jrwmad from 3rd pay F-;ffcrmerr: a cera a rro, im a i la ble 15cr dmA cad in: siftoA;rx ornfdnwloads. TITAN 6 0 t L 0 IP iN 0 0 4 PROJECT: 4335 QUAY ST MUNICIPALITY: WHEAT RIDGE, CO ZIP CODE: 80033 CLIENT: RORY PIERCE 2.960 kW DC-STC/3.000 kW -AC ritan Schr Povw 525W Baslino Rd Mcm,A7 85210 TQI 65 5 SAY- SO LA R rainsa"a"ar.ccim inl5cs,'a)tkwddapohw S I fab Sd;r Inc. 240 CourtneyWDerry East Mi sismup ON L5T 2Y3 Car -oda 'M 1-1905-255-25011 Ru tl 905-696-02& ink'@siF;bs62r.com I www a I Fi bc dw. c cm Silfab Sd2r Inc. WO Cornwa I Ao-e BSI irieurn %VA 98225 USA Td 1-1960-569-4733 AUTHOR: EE DATE: 22/MAY/21 REV - C Al - PANEL SPECIFICATIONS myof 05/24/21 A VM 52158 Exp. 10/31/21 CPSCO, ELECTRICAL POWER 5 SAFETY CO. [,rosslRail LILI-X IvIec.1hanical P Material Ultimate Tensile strength Yield 'Strength Weight Finish ectio)n Propertio'c's 6,000 Series Aluminum 37.7 ksi (260 MPa), 34.8 ksi (240 MPa) — ��I��� ����I cls ta 0.47 I bslft (0.99 kg/m) 1�e Mill or Dark Anodized Roof Type Material sx 0.1490 ire -' (0.3785 cm) Flexibility Sy 0.1450 in (0.36683 CM3) PV Modules A V -Section) 0.4050 in -2(1.0287 cm2 Module Orientation Roof Attachment Structural Validity .39 14216.401 1.54 166 Warranty Dimensions in [mm] Inches Notes; 0 Structural values and span charts determined in accordance with Aluminum Design Manual and ASCE. 7-16 ► UL2703 Listed System for Fire and Banding wv.errerest- styIarsystems.cepm TITAN SOLAR PROJECT: 4335 QUAY ST MUNICIPALITY: WHEAT RIDGE, CO )TITA I PHONE: 1 -855 -SAY -SOLAR ZIP CODE: 80033 S 0 L Q R P 0 W E R WWW.TITANSOLARPOWER.COM CLIENT: RORY PIERCE 2.960 kW DC-STC/3.000 kW -AC [44] 1.732 -1.0150 wo 2 5 CrossRail System ►ears xt a Composition shingle, tile, standings seam High corrosion resistance stainless steel and high grade aluminum Modular construction, suitable for any system size, height adjustable For all common module types Portrait and landscape Screwy connection into rafter I BC compliant, stamped engineering letters available for all solar states 25 years wwtiv eve rest- sol e rsyst em s.com AUTHOR: EE DATE: 22/MAY/21 REV: - A2 - RACKING SPECIFICATIONS CRY of 05/24/21 � �N 52158 Exp. 10/31/21 ANplt. P 0 mo)*PEC SHEET JA a Part #1 74 5.25'' 304 Aj 5/16-18 X 5.25 AMI 304 Stainless Steel Removable Hanger Bolts Part # Box Quantity 0.39 7 17664 5.25"' Bolts (10) 50 17666 Tr' Microflashinq(D (10); 5,25" Bolts (10) 3" icroflashing(25); 5.25 11 Bolts (25); L -Foot (25); 5/16" 17667SS 0_7 " Serrated Hex Flange Nuts (25) - 4.15 ppp"p— F" ou I cocrews Inrl cofp F, $17669 File# E493748 Part # 17669 J 5/16 X 3 304 Stainless Steel Microollusl-unUfc. Part # 17669 5/1 611) x 3" 304 Stainless Steell Compression Washer Black Part# 17659 5/16" x 411 304 Stainless Steel Compression Washer Black 5830 Las Positas Road, Livermore CA 94551 1 3948 Airway Drive, Rock Hill SC 29732 Phone, (844) 671-6045 1 Fox-, (800) 689-7975 1 www.quickbolt.com QuickBOLT is a division of Quickscrews I nternotionall Corp. TITAN SOLAR )TITA I PHONE: 1 -855 -SAY -SOLAR 5 0 L A R P 0 W E R WWW.TITANSOLARPOWER.COM L 3 PROJECT: 4335 QUAY ST MUNICIPALITY: WHEAT RIDGE, CO ZIP CODE: 80033 CLIENT: RORY PIERCE 2.960 kW DC-STC/3.000 kW -AC Compression Washer Black Natural oolar/Blaek Cust r 15894ss "15 7945 S 40 C: LU 41-nrri I hick 1 4C 4 C Technical requiraDmt : The dimensions of the hooks are in accordance with the drluvings. Surface smooth, without burr. & 2 rnm 304SS mdpw.. HVIC 05 MM Hoic difflame t 0.5 r-T-lr-rl 017. 11. Auditor: Yom W kK t 2 m r -n 0.1 r-1-1 M Awe tekMee ± 1* rnm 5830 Las Po:sitas Road, Livermore CA 94551 1 3948 Airway Drive, Rock Hill SC 29732 Phone: (844j 671-6045 1 Fax: (8,00) 689-7975 1 www.quickbolt.com QuickBOLT is a division of Quickscrews International Corp. AUTHOR: EE A3 - MOUNTING SPECIFICATIONS DATE: 22/MAY/21 REV - 05/24/21 N 52158 Exp. 10/31/21 At CPSCO, ELECTRICAL POWER 5 SAFETY CO. /Sin le Phase Inverter wit HD -Wave Technology for North America SE300OH-US / SE380OH-US / SE500OH-US / SE600OH-US/ SE760OH-US / SE1000OH-US / SE1 140OHl-us OUTPUT -1 F AC P'� r C7 t t A I TP% roc 's' r�,:�� 3V VA 3300 0 2cay Maianllm Calmixg WpA U-5 Curm t 0240V 5400 0, 2C6V '103CO 0 2D6V Mai , n c r 3 02 42 0240V' 1140) @ 260V �� M830r`6Itm Cfirtf1mxm Wput _ Curren 02M X30 0 SOW - 5M 0 2c�r 103 CO @ 2�V 4&5 A CMI tfs W!i 01 240- j A AC W�U Un. -Mm- . I N 093 - M _ INPUT fix F*qwmyMIN"imso A I TP% 5" -W- TITAN SOLAR KE Maianllm Calmixg WpA U-5 Curm t 0240V % 21 _ 25 32 42 475 A M830r`6Itm Cfirtf1mxm Wput _ Curren 02M 16 - 24 - 4&5 A CMI tfs W!i A itc(4 �J� witty Il*+�. +_��u 7 • •z.�r-rtion' c cw�.�_Wsble f !Ills INPUT Maammm IDC Pawer @241W 4€5oO 59CO 7750 93CG 11m, 15500 176,50 W Mammum (]C mer G2MV - W -D - 'Sb - - 155M W Trar r -k% Unger *s mato 11.m kw vauge 480 Nomim oc hPA "age 400 M"mLrn hW C:urrem W4WA &5 IL5 134 165 20 27 305 AdC Mai6m nn Input Cur +t 02MW - 9 - 133 27 Ade Max- VW Ston Ctain Currern 45 AdC kmove- ki—b ity PMWic�n Goird-FaLit hol*m tkI 60ft SenstWy CEC 1ighd Efty 99 0 240V NottUrft Fbwer Crnsumptort W ADDMN A L FEATURIES ftveftije Gr&k DaL% S1 012.20 opticx Ra - NEC 2DU ard 2017169a12 Ajjtr-"k Rapid Stautdbwn upon AC GrA D&arned STANDARD COMPLIANCE Go [onnxctix+ Saxuro� INSTALLATION VEOWATIONS AC WpUCa utWefMri � 4' minirnurn / 14--6 AVdG DC KpLt Carddt Size 18 of Strings M40 rnhkTutn / WurkVs f 14-6 AMS AWS P Dhwesiors wlh SARy h 17.7 x UA x 6.8 4%_ x 370 1174 0-fKWAP Vkight Sk*y S040 22/10 25.1 11.4 2W M9 25 cads Naaaral Ccctinn opmtrg kmpe( ure R&W -40, to +140 / -25 to +6000 (-4VF I -4CrC opbooft 4 kir ell W" pct �t ,DA NOW Cif 1t DSO rro f ta U224 v1put cL f we W ft ya-" gaw a ftwus goads Nrnertw PIN. Sf LaaaH soffrpcmw -d.-raung ►fin raim = C,�► �r�Ft r�� tam davdnq- romp& a 410 war P'N 4j9X)0"ML14 Oschrf&r Uch-o aq ". n r. AJ - ift I lL OPTUM 1W SOLAPN uv Irrdwrwr-a or w aftwid Aden iris cO Sd*vtdp !ktrc i6 I re AA carr �.d�n � �t � narA x� ' lam•. a� trid�n res d� 1'1'�tr drrl Ea�,■7. �l�R �� Oilhi�t4 f�� f� � 1 rr� � rFr�t r A%VG 3/4' fin I4-3 !&I gs / 14--6 A%VG 213 x 1&6 x 73 1540 x370x 135 inwon� 388117.6 lb / kg 50 dBA �f4C off , T A I TP% I TITAN SOLAR PROJECT: 4335 QUAY ST MUNICIPALITY: WHEAT RIDGE, CO (j j PHONE: 1 -855 -SAY -SOLAR ZIP CODE: 80033 S 0 L Q R P 0 W E R WWW.TITANSOLARPOWER.COM CLIENT: RORY PIERCE 2.960 kW DC-STC/3.000 kW -AC Single Ph, ase I nverter with HD -Wave Technology for North America SE300,OH-US / SE380OH-US / SE500OH-US / SE600OH-US / SE7600H-US / SE1 OOOOH-US / SE1 140OH-US 0 " taw*4 • Igo a Optimized ivAth HD -Wave technology I Specifically de,icgned to wc62 vAth Extr-emely :;mall power opfin117er-s I Record-breaking efficiency Built-in nodule -level nionitol-ir I Fixed voltage inverter for longer Wings l Outdoor and indoor in,tailation I Integrated arc fault protection and rapid shutdown for I OpWnal. revenue grade data, ALIBI C12.20 NEC 2014 and 2017, per artide 690.11 and 690.12 Class 0.5 (0.5% accuracy) 1 U L 17 4 1 SA certified, for CPUC Rule 21 grid compliance solaredge.com S�I8rag: or AUTHOR: EE A4 -INVERTER SPECIFICATIONS DATE: 22/MAY/21 REV: - 05/24/21 � �N 52158 Exp. 10/31/21 t��V P 0 / Power Optimizer For North America P320 / P340 / P370 / P400 / P405 / P505 INMT, RAW t DC PowntA K10 W 370 d", 4M ri:-n knft itbftgc atbar stWrrgXV3) 6 so KOPT Opmarig I arge w .:f 9-60 8-90 12 S - 105 3',5.83 )kk Max mi_ -n Shur Cxam3 1 14 #rte Mm r'ium DC bpLf Cum m 1161 ITS +Adc Mw morn Vkwncy .S % Vir. grid Eftwincy qGS A o OUTPUT DU FUNG OPE RATION (POWER 0PTIMEZER CONNECTED TO OPERATING SOLARED+GE IN'V'ERTER) KAMM%xn Ckfi;X* Cwt A& Imre QLCPU %%taw 60 � re -OUTPUT DUFUNG STAN06'Y (POWER OPTIMEZER DMON NECrED FROM LAREDGE INVERTER OR SOLAREDGE IERTE ) E r C :tm mm STANDARD compLI SMC=:::ftr1S Class BLl� _-:, KLIOW-6-3 S;* � R.r-jd= Is � & LLi f Y - _V - -1— UqSTALLAT. ION �Sy.P+�L��TION M= r -a- -n A WOO CCrn,167.bV rror6rsrrri S12e P wid T?m Ph= Ri1iff m -s Dew its rr L i F ,r 11 t 1W 1281 5 Y 5.97 X 1.1 S x 5.97 x I 5 x 5 47 x 1.-965 T S:97 x? 1.2 "� d i n VMKft IrdAng cNes) 630/14 75011.7 845/19 3 +fir /' Ib In pt Cv i wtw Crus 1,A M / CXx bmkgod AC4 OtAr.,r;1►4'trn ! m th OL951 ID i.? r 3 4 -n / ft In Put Wm L * (116/052 Praftcux P.Vrlkj� Rjnr* 0-10 LmW M per of #* No&& WtAA of up to • 5% poww xlwa * AftW matu than WV Fir o�dw wo Np=t;;� p4b"M carr of :olArtap Mritn6sm SVrg lv-tr Itwr 6 Max t'urTr x'•71 tk3 L UX (CM wth Lis) FardelSart* d WkMft Lefton Fir dffjftd " rrron raW of It It k mo iwd to rm W5 %M with P3: "340,P3IMP4M in ort cx AA a" %h4v r -c" 1� n 30 oodmuft A*n got t NEC rapid OkAdcmn rapssr,�-xtf. safer ,alma ,rel to aAiv,t V e M taq w* "for SE 14 c..S . 3 : tl rS k rc akn e! to md up t1 40M Pff irts; wtwi 3 iuim+ Ora awnixud tL. rar t -%'i iw l3 i r" prr uM bt 5143 29 Q i ww% *I* � p cmw ,rtes t5maeft dw W:V_ ► s of ft 2 AWW s F -a S E 30 e.E3!J r Libel :1S f. DO KLIS kis aboaW to crag ► p ij, IS LIVAI 4o sa wq *#w, 3 itw rte a,* cavoo wJ to Ow ktu mm fl, 2dmp pu rM Err fir 1 Ej .wA were ter r -%m ira fyi Farr Sfiwe" t +.& s rfV;;L rt u' b i-WLIPA Power Optimizer For North America P320/P340/P370/P400/P405/P505 � 25� PV power optimization at the module -level I Specifically designed to work with SolarEdge inw•e rte rs l Up to 25% more energy I Superior efficiency (99.S%) I Mitigates all bype of module mismatch I�sse� from manufacturing tolerance to partial shading I Flexible system deign for maximum space utilizabon I Fast installation with a single bolt I Next generation maintenance with mdule- level monitoring I Meets NEC requiren-ents for arc fault protection (AFC]) and Photovoltaic Rapid Shutdov/n SVstem ( PVR) I Module -level voltage shutdown for installer and firefighter safe% t� d CC ��i�8 or solam 8 � 05/24/21 ��,rm rs �....,�d �Qc�, tr,f Ldatr�t�'rCt� � :otart _ c1a r�� fae 1 8**t '' rr meff tit a� tlor era Cox .VW j1:0�G W &U*d !a dwW nafres. 58 TITAN SOLAR PROJECT: 4335 QUAY ST MUNICIPALITY: WHEAT RIDGE CO AUTHOR: EE A5 -OPTIMIZER SPECIFICATIONS T I T A Iq Exp. 10/31/21 -O NA PHONE: 1 -855 -SAY -SOLAR ZIP CODE: 80033 DATE: 22/MAY/21 P 0, CLIENT: RORY PIERCE � A� IR � � .TITANSOLARPOWER.COM 2.960 kW DC-STC/3.000 kW -AC REV: - ELECTRICAL POWER 6 SAFETY CO. LOCATION OF NEAREST URGENT CARE FACILITY NAME: ADDRESS: PHONE NUMBER: NOTES: • INSTALLER SHALL DRAW IN DESIGNATED SAFETY AREA AROUND HOME *INSTALLERS SHALL UPDATE NAME, ADDRESS, AND PHONE NUMBER OF NEAREST URGENT CARE FACILITY RELATIVE TO THE JOB SITE BEFORE STARTING WORK. PERSONS COVERED BY THIS JOB SAFETY PLAN INJURED AT WORK TODAY? INITIAL YES OR NO PRINT NAME INITIAL YES NO UNDERGROUND DIG REQUIRED? YES PERMIT # T T A Iq S 0 L Q R P 0 W E R TITAN SOLAR PHONE: 1 -855 -SAY -SOLAR WWW.TITANSOLARPOWER.COM PROJECT: 4335 QUAY ST MUNICIPALITY: WHEAT RIDGE, CO ZIP CODE: 80033 CLIENT: RORY PIERCE 2.960 kW DC-STC/3.000 kW -AC AUTHOR: EE DATE: 22/MAY/21 REV: - A6 - SAFETY PLAN City of � 4.. -zz. 05/24/21!4CPF� $FO" D 0 � N 52158 Exp. 10/31/2 A�plt. EPSCO' ELECTRICAL POWER 6 SAFETY CO. From: no-reolv(alci.wheatridae.m. us To: CommDev Perm is Subject: Online Form Submittal: Solar PV Installation Date: Wednesday, June 9, 20218:10:04 AM Solar PV Installation This application is exclusively for Solar PV Installations YOU MUST ATTACH A VALID ELECTRONIC PAYMENT ORM IN ORDER FOR THE PERMIT TO BE PROCESSED. Your Permit will be emailed to the email address provided below once it is processed. THIS APPLICATION DOES NOT CONSTITUTE A PERMIT. DO NOT BEGIN WORK UNTIL PERMIT HAS BEEN ISSUED. Is this application for Yes Solar PV Installation? PROPERTY INFORMATION Property Address 4335 Quay St. Wheat Ridge CO, 80033 Property Owner Name Rory Pierce Property Owner Phone 720-290-2070 Number (enter WITH dashes, eg 303-123- 4567) Property Owner Email Address Attach City of Wheat Ridge Electronic Payment Form - "DO NOT ATTACH A PICTURE OF A CREDIT CARD" Roryanddee@comcast.net 09. Ddf CONTRACTOR INFORMATION Contractor Business Titan Solar Power CO Name Wheat Ridge Contractor's License Number (This is a 5 or 6 digit number for the 202247 City of Wheat Ridge) Contractor Phone Number (enter WITH dashes, eg 303-123- 4567) Contractor Email Address 4802372375 copermitting@titansolarpower.com Retype Contractor copermitting@titansolarpower.com Email Address DESCRIPTION OF WORK Scope of Work Installation of a 2.960 kW DC roof mounted solar system. KW 2.960 # of Panels 8 Location of Panels house roof Structural required No Upload engineer letter 4335 Quay St Wheat Ridge CO 80033 SL.odf or pages on 8 1/2" x 11" only Solar Installation Plan 4335 Quay St Wheat Ridge CO 80033 Plans.odf Set on 11'x17" only. Project Value (contract 14867.00 value or cost of ALL materials and labor) SIGNATURE OF UNDERSTANDING AND AGREEMENT I assume full Yes responsibility for compliance with applicable City of Wheat Ridge codes and ordinances for work under any permit issued based on this application. I understand that work Yes may not begin on this property until a permit has been issued and posted on the property. I certify that I have Yes been authorized by the legal owner of the property to submit this application and to perform the work described above. Person Applying for Erica Ford Permit I attest that everything Yes stated in this application is true and correct and that falsifying information in this application is an act of fraud and may be punishable by fine, imprisonment, or both. Email not displaying correctly? View it in your browser. 1* � � i City of Wheat Ridge �� Residential Solar PERMIT - 202101229 PERMIT NO: 202101229 ISSUED: 06/14/2021 JOB ADDRESS: 4335 Quay St EXPIRES: 06/14/2022 JOB DESCRIPTION: Installation of a 2.960 kW DC roof mounted solar system on roof top - 8 panels *** CONTACTS *** OWNER (720) 290-2070 PIERCE RORY A SUB (480)226-6769 DAVID WILLIAMSON 202247 TITAN SOLAR POWER CO *** PARCEL INFO *** ZONE CODE: UA / Unassigned USE: UA / Unassigned SUBDIVISION CODE: 2405 / BARTHS, COULEHAN GRANGE, WHEAT BLOCK/LOT#: 0 / *** FEE SUMMARY *** ESTIMATED PROJECT VALUATION: 14,867.00 FEES Total Valuation 0.00 Residential Solar 500.00 ** TOTAL ** 500.00 *** COMMENTS *** *** CONDITIONS *** A printed copy of the permit and city stamped on-site plans must be available on-site for the first inspection. Approved per plans and red -line notes on plans. Must comply with 2018 IRC, 2020 NEC and all applicable City of Wheat Ridge Municipal Codes. Work is subject to field inspections. I, by my signature, do hereby attest that the work to, be performed shall comply with all accompanying approved plans and specifications, applicae building codes, and all applicable municpal codes, policies and procedures, and that I am the legal owner or have been authorized by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with this�permrt. I further attest that I am leg ally authorized to include alI entities named within this document as parties to the work to be performed and that all work to be performed is disclosed in this document and/or its' accompanying approved plans and specifications. Signature of OWNER or CONTRACTOR (Circle one) Date 1, This permit was issued based on the information provided in the permit application and accompanying plans and specifications and is subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures. 2. This permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and received prior to the date of expiration. An extension of no more than 180, days made be granted at the discretion of the Chief Building Official and may be subject to a fee equal to one-half of the original permit fee. 3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard requirements, fees and��procedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of the Chief Building Official and is not guaranteed. 4. No work of any manner shall be performed that shall results in a change of the natural flow of water without prior and specific approval. 5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all requ�ired inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services Division. 6. The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, anviolation of any provision of any �pplicabje code or any ordinance or regulation of this jurisdiction. Approval of work is subject to field inspection. 06/14/2021 Signature of Chief Building Official Date REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. � ► � i City of Wheat Ridge Residential Remodel PERMIT - 202002641 PERMIT NO: 202002641 ISSUED: 03/11/2021 JOB ADDRESS: 4335 Quay St EXPIRES: 03/11/2022 JOB DESCRIPTION: Residential remodel of kitchen, laundry room and bathroom; rewire electrical throughout house, install tankless water heater Sq ft: 209 *** CONTACTS *** OWNER (720) 290-2070 PIERCE RORY A GC (720)275-2604 ROBERT CUNNINGHAM 180050 RSC REMODELING SUB (303)904-2000 JONATHON FAWKES 210055 RENEW HOME INNOVATIONS SUB (720)799-8012 PHILLIP EASTWOOD 160081 TIPPING HAT PLMBG, HTG & ELEC SUB (720)799-8012 PHILLIP EASTWOOD 160081 TIPPING HAT PLMBG, HTG & ELEC *** PARCEL INFO *** ZONE CODE: UA / Unassigned USE: UA / Unassigned SUBDIVISION CODE: 2405 / BARTHS, COULEHAN GRANGE, WHEAT BLOCK/LOT#: 0 / *** FEE SUMMARY *** ESTIMATED PROJECT VALUATION: 40,510.00 FEES Total Valuation 0.00 Plan Review Fee 277.03 Use Tax 850.71 Permit Fee 626.05 ** TOTAL ** 11753.79 *** COMMENTS *** *** CONDITIONS *** All roughs to be done at Framing Inspection. A printed copy of the permit and city stamped on-site plans must be available on-site for the first inspection. Approved per plans and red -line notes on plans. Must comply with 2018 IRC, 2020 NEC and all applicable City of Wheat Ridge Municipal Codes. Work is subject to field inspections. 1* � 4 41' PERMIT NO: JOB ADDRESS: JOB DESCRIPTION: City of Wheat Ridge Residential Remodel PERMIT - 202002641 202002641 4335 Quay St ISSUED: 03/11/2021 EXPIRES: 03/11/2022 Residential remodel of kitchen, laundry room and bathroom; rewire electrical throughout house, install tankless water heater Sq ft: 209 I, by my signature, do hereby attest that the work to be performed shall comply with all accompanying approved plans and specifications, applicable building codes, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with this�permrt. I further attest that I am leg ally authorized to include all entities named within this document as parties to the work to be performed and that all work to be performed is disclosed in this document and/or its' accompanying approved plans and specifications. Signature of OWNER or CONTRACTOR (Circle one) Date 1, This permit was issued based on the information provided in the permit application and accompanying plans and specifications and is subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures. 2. This permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and received prior to the date of expiration. An extension of no more than 180, days made be granted at the discretion of the Chief Building Official and may be subject to a fee equal to one-half of the original permit fee. 3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard requirements, fees and��procedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of the Chief Building Official and is not guaranteed. 4. No work of any manner shall be performed that shall results in a change of the natural flow of water without prior and specific approval. 5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all requ�ired inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services Division. 6. The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, anviolation of any provision of any �pplicabje code or any ordinance or regulation of this jurisdiction. Approval of work is subject to field inspection. 03/11/2021 Signature of Chief Building Official Date REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. valuation change From: no-reolv(alci.wheatridae.m. us To: CommDev Perm is Subject: Online Form Submittal: Residential Interior Remodel Date: Monday, December 21, 2020 2:30:36 PM Residential Interior Remodel This application is exclusively for Residential Interior Remodels and other scopes of work which do not have a specific form already available. YOU MUST ATTACH A VALID CREDIT CARD AUTHORIZATION FORM IN ORDER FOR THE PERMIT TO BE PROCESSED. Your Permit will be emailed to the email address provided below once it is processed. THIS APPLICATION DOES NOT CONSTITUTE A PERMIT. DO NOT BEGIN WORK UNTIL PERMIT HAS BEEN ISSUED. PROPERTY INFORMATION Property Address 4335 Quay St. Wheat Ridge, CO 80033 Property Owner Name Rory Pierce Property Owner Phone 720-290-2070 Number (enter WITH dashes, eg 303-123- 4567) Property Owner Email roryanddee@comcast.net Address Attach City of Wheat Electronic Payment Form - Bob Cunninaham.odf Ridge Electronic Payment Form - "DO NOT ATTACH A PICTURE OF A CREDIT CARD" APPLICANT INFORMATION Applicant Name Robert S. Cunningham What is your role in the General Contractor project? Wheat Ridge 180050 Contractor's License Number (This is a 5 or 6 digit number for the City of Wheat Ridge) Contact Phone Number (enter WITH dashes, eg 303-123-4567) Contact Email Address for Plan Review Comments Retype Contractor Email Address DESCRIPTION OF WORK Detailed Scope of Work - In the space below (not as an attachment), Provide a detailed description of work including mechanical, electrical, plumbing work occurring, adding/removing walls, etc I, the applicant, understand my application will be rejected if I do not include a Detailed Scope of Work. 720-275-2604 rscunningham28@gmail.com rscunningham28@gmail.com Will be removing existing cabinets and replacing them with new cabinets and counter tops. There will be new flooring in the Kitchen. In the Laundry room there will be a toilet added and a building of a pocket door. There will be a replumb of the washer and dryer and utility skink. In addition there will be a demand water header added to that. New flooring in the laundry room. In the Bathroom I will install new vanity, new flooring, new shower pan, shower valve, shower wall and shower head. I have entered a detailed scope of work. Location of Work Kitchen, Laundry Room, Bathroom Square Footage Area of Work Being Performed Asbestos Report 209 Field not completed. Upload letter size pierce20201221 013919 PDF documents here Construction Plans scanned on 11'x17" or larger kitchen remodel $15,410.00 bathroom remodel $6,500.00 Project Value (contract $15,750.00 washer lines $750.00 value or cost of ALL water heater $850.00 materials and labor) total = $23,510.00 bf 12/21/2020 SIGNATURE OF UNDERSTANDING AND AGREEMENT I assume full Yes responsibility for compliance with applicable City of Wheat Ridge codes and ordinances for work under any permit issued based on this application. I understand that work Yes may not begin on this property until a permit has been issued and posted on the property. I certify that I have Yes been authorized by the legal owner of the property to submit this application and to perform the work described above. Person Applying for Permit I attest that everything stated in this application is true and correct and that falsifying information in this application is an act of fraud and may be punishable by fine, imprisonment, or both. Robert S. Cunningham Yes Email not displaying correctly? View it in your browser. From: no-reolv(alci.wheatridae.m. us To: CommDev Pets Subject: Online Form Submittal: Revision to Permit Application Date: Wednesday, March 10, 20213:41:42 PM Revision to Permit Application Permit Number 202002641 assigned to project 303-904-2000 PROPERTY INFORMATION Permit Number 202002641 Property Address 4335 Quay St Wheat Ridge, CO 80033 Property Owner Name Rory Pierce Property Owner Phone 720-290-2070 Number (enter WITH dashes, eg 303-123- 4567) Property Owner Email 720-290-2070 Address Contact Name Robert S. Cunningham Contact Phone Number (enter WITH dashes, eg 303-123-4567) 303-904-2000 Contact Email Address rscremodeling202O@gmail.com Retype Contact Email Address rscremodeling202O@gmail.com DESCRIPTION OF WORK Detailed Revised Scope of work not on the original permit application which is: Scope of Work - rewiring the entire home. In addition to that we are installing a Provide a detailed tankless water heater. description of the change in scope of work including mechanical, electrical, plumbing work occurring, adding/removing walls, etc Engineer Letter (if applicable) Additional Documents on Letter Size Are plans or documents locked for editing? Construction Plans scanned on 11'x17" or larger Additional Project Value Only add what the revised scope of work is valued at. Attach City of Wheat Ridge Electronic Payment Form - "DO NOT ATTACH A PICTURE OF A CREDIT CARD" Sub contractor Authorization -Mechanical (002).odf Sub contractor Authorization -Electrical (0041.odf No Field not completed. 17, 000.00 Electronic Payment Form - 3.10..21.odf SIGNATURE OF UNDERSTANDING AND AGREEMENT I assume full Yes responsibility for compliance with applicable City of Wheat Ridge codes and ordinances for work under any permit issued based on this application. I understand that work Yes may not begin on this property until a permit has been issued and posted on the property. I certify that I have Yes been authorized by the legal owner of the property to submit this application and to perform the work described above. I attest that everything Yes stated in this application is true and correct and that falsifying information in this application is an act of fraud and may be punishable by fine, imprisonment, or both. Person Submitting Robert S. Cunningham Revision Email not displaying correctly? View it in your browser. City of Wheat P,jdge COMMUNITY DEVELOPMENT SUBCONTRACTOR AUTHORIZATION FORM P I u mb i ng Subcontractor This form must be completed & signed by the. P (Vr4A% r1g SUBCONTRACTOR performing electrical work on site. Subcontractor's insurance and license must be up to date prior to permit issuance. Project Address:y S3 j ()U" ST w 1 "-T Rl "' Ok E , CO SCO33 General Contractor: RSC. 26YN1 b ]a ELI N G FORM WILL. VOT BE kCCEPTED WITH MISSING INF RNIATION Company Name: RGry E W r+O M6 Contact Phone #: 3 C) 3 , q 0 q . 2-000 INNOV AZ IONS Wheat Ridge Contractor License #: 2- 1oQS!i—(required field) State License #: P C. O o o 4 2.18 Master License #: Kp, OD IS 040(e %,aPt4 �L,u EPVdKES Printed Name of Authorized Agent Z�Z Signature of AdIkorized Agent Date 4'� City of '� Wheatjdge COMMUNITY DEVELOPMENT SUBCONTRACTOR AUTHORIZATION FORM Mechanical Subcontractor This form must be completed & signed by the MECHANICAL SUBCONTRACTOR performing mechanical work on site. Subcontractor's insurance and license must be up to date prior to permit issuance. Project Address: 4335 General Contractor: Street Wheat Ridge CO 80033 Company Name: TippingHat Contact Phone#: 720-799-8010 Wheat Ridge Contractor License #: 160081 Erin Eastwood Printed Name of Authorized Agent EwaL tuoad Signature of Authorized Agent field) 3/90/29 Date 4'� City of '� Wheatjdge COMMUNITY DEVELOPMENT SUBCONTRACTOR AUTHORIZATION FORM Electrical Subcontractor This form must be completed & signed by the ELECTRICAL SUBCONTRACTOR performing electrical work on site. Subcontractor's insurance and license must be up to date prior to permit issuance. Project Address: 4335 Quay Street Wheat Ridge CO 80033 General Contractor: Company Name: Tipping Hat Contact Phone #: 720-799-8010 Wheat Ridge Contractor License #: 160081 (required field) State License #: EC -0100594 Master License#: ME0030228 Erin Eastwood Printed Name of Authorized Agent Fria £neh'mad 3110129 Signature of Authorized Agent Date 111"age Elevation Environmental Services Elevation Environmental Services 13340 Harrison St xln.,tioo enwro®enml Thornton CO 80241 (833)536-8476 4335 Quay St Wheat Ridge, CO 80033 Prepmed For: Rodney Payne Asbestos Masters PrepmedBy: Elevation Environmental Services 13340 Harrison St Thornton, CO 80241 CDPHE CERTIFICATE #'s: 24795, 25621 Date(s) of Clearance(s)—February 2, 2021 2 1 P a g e Elevation Environmental Services Table of Contents 1.0 Introduction.................................................................................................... 3 2.0 Visual Inspection............................................................................................. 3 3.0 Final Clearance Air Monitoring............................................................................ 3 4.0 Sample Results................................................................................................ 3 5.0 Conclusion and Recommendations......................................................................... 3 6.0 Lab Results /Permits/ Certifications.......................................................................... 4-9 3 1 P a g e Introduction Elevation Environmental Services On February 2, 2021 Elevation Environmental conducted Asbestos Major Spill Air Clearances according to CDPHE Regulation No. 8 Part Section IIIP (page 46) at 4335 Quay St, WheatRidge, CO. Clearance was performed on cleaning of ACM Major Spill. 2. Visual Inspection A visual inspection was conducted by wearing black nitrile gloves and touching all work and adjacent surfaces to look for any dust or debris left behind. Critical barriers were inspected to make sure they were in place and no dust or debris had passed through. 3. Final Clearance Air Monitoring Aggressive sampling was performed using fans and leaf blowers prior to setting up the samples in the breathing zone. Five pumps were set in the work area and allowed to equilibrate. The pumps were calibrated and PCM cassettes were attached on stands to each. The pumps were allowed to sample until the requirements of NIOSH Method 7400 were met. The pumps were then recalibrated and the average of the two calibrations was used to calculate the volume of air passed through each cassette. [Liters/min] * [Run Time (min)] = Liters Sampled 4. Sample Results Samples were submitted to Reservoirs Environmental which is a NIST approved lab for PCM and TEM analysis. Sample Name Volume Sampled L MAAL (F/cc) Fiber Cone (F/CC) PASS/FAIL 4335-CLO1 1214 0.01 BRL Pass 4335-CL02 1217 0.01 BRL Pass 4335-CL03 1208 0.01 .005 Pass 4335-CL04 1220 0.01 BRL Pass 4335-CL05 1211 0.01 BRL Pass 5. Conclusions and Recommendations The work areas/containments met the standards set forth by CDPHE Regulation 8. The interior of the structure was cleaned and HEPA vacuumed and the exterior had an area that was cleaned, and 2 inches of soil was removed. Therefore; the area is cleared for the purposes intended. OlPage Elevation Environmental Services 6. Lab Remlts/ Permit/ Certdications �0.�V� •vs—`='� RESFAVOIg9 EHVIRp1YEMLL.ML OA 14111 msmk mm^mwim�e mM�'®env Mm wwom�Mam, ma ma Map mm Fmm w 5mm _ Pq mcam 1214 Off I ?At um am MIL 4mmaz 1217 IM 05 701 0% am am mental 0 a urtmwv.veeaw amewryrv.eMnMnwauy cmcv as ram nIwc am ...mane 511"age Elevation Environmental Services TReservoirs Envimnmen[al, Inc- In nc. m .,.v..i�Jap 1 } fF !'' 1111 p i 9lPage Elevation Environmental Services wV z � e s � E a ° z � U � w 0 op H a BEDROOM r—BROOM CLOSET CLOSET CLOSET MASTER BEDROOM HALT_ ♦k4e City of 9corm e COMMUNfIY DEVELOPMENT APPROVED Reviewed for Code Compliance BRANDON F 02/05/2021 Plans Examiner Date LIVING ROOM -2 ADDED ENTRY GLASS DOOR C TOP C' FORMAL KITCHEN DINING LIVING ROOM -1 BAY WINDOW ALL WORK SHALL COMPLY WITH 2018 IRC, 2018 IECC, 2020 NEC, COLORADO PLUMBING CODE AND THE CITY OF WHEAT RIDGE AMENDMENTS ON SITE PLANS MUST BE ON SITE FOR INSPECTION G TOP ALL prolaeta am DINING BubNet to Flak I cSlons ENTRY faNkyo1xfmO The IuW ofPP~WWpr*WofPAMssper*otkm Ord computabonf shag not be a perm Of Off apprA'tit of Orr/ kkoeahpn 0 FISTING LIVING AREA Ol of the prOWSIORa of the barking cook or of u,(aV City ordirnnces. rMnngs APPROES 1,470 5O. ET. preslurung to 0" outhorfty to wolaN w camel the FaWYals Ly t" oilausag coda ar oMer arBnences of the Cgyshog apt be wga FRONT PORCH smoke alarms shall comply with section 314 of 2019 IRC Smoke alarms shall be installed In the following locations: In each sleeping room. GARAGE Outside each Separate sleeping area in the immediate vicinity ofthe bedrooms. On each additional story of Me dwelling, including basements and habitable attics and not including crawl spaces and uninhabitable attics. In dwellings or dwelling units with split levels and without an intervening door between Me adjacent levels, a smoke alarm installed on the upper level shall suffice for Me adjacent lower level provided that the lower level is les. than one full story below the upper level. When more than one smoke al.. is required to be installed within an individual dwelling unit, Me alarm devices shall be interconnected in such a manner that the actuation of one alarm will activate all of Me alarms in the individual unit carbon Monoxide alarms shall be installed within 15 feet of each GARAGE DOOR sleeping room ENTRY PANTRY REFRIG ® P] O UTILITY UTILITY STORAGE SHED ENTRY faNkyo1xfmO The IuW ofPP~WWpr*WofPAMssper*otkm Ord computabonf shag not be a perm Of Off apprA'tit of Orr/ kkoeahpn 0 FISTING LIVING AREA Ol of the prOWSIORa of the barking cook or of u,(aV City ordirnnces. rMnngs APPROES 1,470 5O. ET. preslurung to 0" outhorfty to wolaN w camel the FaWYals Ly t" oilausag coda ar oMer arBnences of the Cgyshog apt be wga FRONT PORCH smoke alarms shall comply with section 314 of 2019 IRC Smoke alarms shall be installed In the following locations: In each sleeping room. GARAGE Outside each Separate sleeping area in the immediate vicinity ofthe bedrooms. On each additional story of Me dwelling, including basements and habitable attics and not including crawl spaces and uninhabitable attics. In dwellings or dwelling units with split levels and without an intervening door between Me adjacent levels, a smoke alarm installed on the upper level shall suffice for Me adjacent lower level provided that the lower level is les. than one full story below the upper level. When more than one smoke al.. is required to be installed within an individual dwelling unit, Me alarm devices shall be interconnected in such a manner that the actuation of one alarm will activate all of Me alarms in the individual unit carbon Monoxide alarms shall be installed within 15 feet of each GARAGE DOOR sleeping room EEE EcETHF— B.00M Ali BEDROOM O JL CLOSET HALL CLOSET CLOSET =I MISTER BEDROOM LIVING ROOM -2 ADDED ENTRY ELE� - -ETINGAFEE5 G ASS DOOR C.TOP OO D EEE thea DINING ELI FORMAL tr SINK KITCHEN STOVE/OVEN 5 LE E15T Ev - REFRIG. M ® � EEEE a v_ LJI NEW UTIL W SINK r� NEW WATER / LYING ROOM -1 NEW ON DEMAND HOT WATER HEATER ENTRY BAY WINDOW NEW WING AREA APPROX. 1,490 5Q. FT. FROM PORCH GARAGE GARAGE DOOR provide gas line isometric to inspector prior to the inspection for rerview. STORAGE SHED F city of Wheat Ridge i CRY of A Wheat Ridge '<3ullWdirnVg Di 4 1 SC i CRY of A Wheat Ridge '<3ullWdirnVg Di 4 1 r 0 0 2 F CRY at -q Wheat Ridge 0 „oIo nnn Wheat Ridge C1" ` V% tJ LL LOU 10 y 3 A 0 e Wheat Ridge t�t 1 Z i T 3 A 0 e Wheat Ridge t�t 1 Z ON SITE PLANS MUST BE ON SITE FOR INSPECTION //fl 4 (aldhicl � ALL Prolsc(�r_� to FWjLnspqqEions ��L• ALL WORK SHALL COMPLY p WITH 2018 IRC, 2018 IECC, L 2020 NEC, COLORADO 1lJJ J CFS' V 1 PLUMBING CODE AND THE CITY OF WHEAT RIDGE AMENDMENTS t 0 v F dry at Wheat Ridge }j M Q J D�.1 inn u, KK. s I it 1 Wheat Rldge 11010 to CRY of Wheat Ridge 1* ► � i City of Wheat Ridge '/� Residential Asbestos Abatement PERMIT - 202100296 PERMIT NO: 202100296 ISSUED: 02/16/2021 JOB ADDRESS: 4335 Quay St EXPIRES: 02/16/2022 JOB DESCRIPTION: Residential abatement in driveway and throughout home, 400 square feet. State permit no.:21JE0524A *** CONTACTS *** OWNER (720) 290-2070 PIERCE RORY A SUB (720)227-7129 RODNEY PAYNE 210030 MASTER ABATERS , LLC *** PARCEL INFO *** ZONE CODE: UA / Unassigned USE: UA / Unassigned SUBDIVISION CODE: 2405 / BARTHS, COULEHAN GRANGE, WHEAT BLOCK/LOT#: 0 / *** FEE SUMMARY *** ESTIMATED PROJECT VALUATION: 81000.00 FEES Asbestos Abatement 50.00 Total Valuation 0.00 ** TOTAL ** 50.00 *** COMMENTS *** *** CONDITIONS *** Work shall comply with 2018 IRC & 2020 NEC. Smoke alarms shall comply with 2018 IRC Section 134. Interior alterations, repairs, fuel -fired appliance replacements, or additions, any of which require a building permit, occurs or where one or more rooms lawfully used for sleeping purposes shall have an operational carbon monoxide alarm installed within fifteen feet of the entrance to each room lawfully used for sleeping purposes. I, by my signature, do hereby attest that the work to be performed shall comply with all accompanying approved plans and specifications, applicable building codes, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized by the legal owner of the property and am authorized to obtain thispermit and perform the work described and approved in conjunction with this�permrt. I further attest that I am legally authorized to include alI entities named within this document as parties to the work to be performed and that all work to be performed is disclosed in this document and/or its' accompanying approved plans and specifications. Signature of OWNER or CONTRACTOR (Circle one) Date 1, This permit was issued based on the information provided in the permit application and accompanying plans and specifications and is subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures. 2. This permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and received prior to the date of expiration. An extension of no more than 180, days made be granted at the discretion of the Chief Building Official and may be subject to a fee equal to one-half of the original permit fee. 3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard requirements, fees and��procedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of the Chief Building Official and is not guaranteed. 4. No work of any manner shall be performed that shall results in a change of the natural flow of water without prior and specific approval. 5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all requ�ired inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services Division. 6. The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, anviolation of any provision of any �pplicabje code or any ordinance or regulation of this jurisdiction. Approval of work is subject to field inspection. 02/16/2021 Signature of Chief Building Official Date REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. From: no-reolv(alci.wheatridae.m. us To: CommDev Perm is Subject: Online Form Submittal: Asbestos Abatement Date: Monday, February 15, 2021 11:56:52 AM Asbestos Abatement This application is exclusively for RESIDENTIAL ASBESTOS ABATEMENT YOU MUST ATTACH A VALID CREDIT CARD AUTHORIZATION FORM IN ORDER FOR THE PERMIT TO BE PROCESSED. Your Permit will be emailed to the email address provided below once it is processed. THIS APPLICATION DOES NOT CONSTITUTE A PERMIT. DO NOT BEGIN WORK UNTIL PERMIT HAS BEEN ISSUED. Is this application for residential asbestos abatement? Provide copy of CDPHE State Permit or Stamped Approved CDPHE State Permit Application Yes PROPERTY INFORMATION Property Address 4335 Quay Street, Wheat Ridge Property Owner Name Rory Pierce Property Owner Phone Number (enter WITH dashes, eg 303-123- 4567) 720-290-2070 Property Owner Email roryanddee@comcast.net Address Attach City of Wheat Ridge Electronic Payment Form - "DO NOT ATTACH A PICTURE OF A CREDIT CARD" Electronic -Payment -Form wheat ridae.odf CONTRACTOR INFORMATION Contractor Business Master Abaters Name Wheat Ridge 210030 Contractor's License Number (This is a 5 or 6 digit number for the City of Wheat Ridge) Contractor Phone 720-227-7129 Number (enter WITH dashes, eg 303-123- 4567) Contractor Email asbestosmasters@gmail.com Address Retype Contractor asbestosmasters@gmail.com Email Address DESCRIPTION OF WORK State Permit No. or 01/28/2021 TS Application Approval Date with Initials of CDPHE Employee approving application. Location of Abatement Driveway and Entire home was cleaned - Major Spill Square Footage Area 400 Square Feet of Abatement Has the abatement Yes been completed If abatement has been 4335 Quay St So 11 Air Clearance (1) ndf completed, upload the clearance report. Project Value (contract $8000 value or cost of ALL materials and labor) SIGNATURE OF UNDERSTANDING AND AGREEMENT I assume full Yes responsibility for compliance with applicable City of Wheat Ridge codes and ordinances for work under any permit issued based on this application. I understand that work Yes may not begin on this property until a permit has been issued and posted on the property. I certify that I have Yes been authorized by the legal owner of the property to submit this application and to perform the work described above. Person Applying for Rodney Payne Permit I attest that everything Yes stated in this application is true and correct and that falsifying information in this application is an act of fraud and may be punishable by fine, imprisonment, or both. Email not displaying correctly? View it in your browser. Colorado Department of Public Health and Environment Air Pollution Control Division — Indoor Environment Program — Asbestos/IAQ Unit 4300 Cherry Creek Drive South, APCD-IE-131 Denver, Colorado 80246-1530 Phone: 303-692-3100—Fax: 303-782-0278 E-mail: asbestos@state.co.us ASBESTOS ABATEMENT PE This permit is granted subject to Colorado Air Quality Control Commission Regulation No. 8, Part , adopted December 21, 2007, and effective January 30, 2008, the Colorado Air Pollution Prevention and Control Act (25-7-101 o 25-7-501 et seq., C.R.S.) and the following provisions. It is only for the purpose of allowing asbestos abatement. ADDITIONAL PERMIT PROVISIONS: By performing work under this permit the abatement contractor agrees that the Division may revoke or suspend this permit should the Division fmd that the contractor: • has violated or has aided and abetted in the violation of 25-7-101 or 25-7-501 et seq., C.R.S. or R gulation No. 8, Part B, or an order of the Division or Commission, • has failed to meet any permit and notification requirement or failed to correct any violations cited by the Division during any inspection within a reasonable period of time, as may be determined by the Division, • has used misrepresentation or fraud in obtaining this permit, or, • has committed any act or omission which does not meet generally accepted standards of the practice of asbestos abatement. As a contractor, you may be subject to other licenses and permits, depending on the requirements of the county and municipality in which the work is being performed. The Colorado Department of Public Health and Environme , Air Pollution Control Division strongly suggests that you check with county and municipal authoritiesin order to determine any other local building/permitting requirements that must be met. THE ORIGINAL PERMIT MUST BE POSTED ON SITE A ALL TIMES. Immediately notify the Asbestos/IAQ Unit of project modifications by fax (number above) or e-mail (address above) and the appropriate county health department by fax. Project modifications include changes in the scope of work or the scheduled work dates, etc. This asbestos abatement permit is valid beginning 1/28/2021 through 11:59 PM on 2/26/2021. The actual scheduled work dates are from 1/28/2021 through 1/31/2021. Approval issued on: 2/9/2021 Fee paid: $400.00 Record number: 166346 Check number: 160129862 —N`odceDumber: 2IM524X- _ _ _ _ _._ Variance: None Comments: None For the location specified below: Rory Place Bedrms,Bathrms,Garages, LivingRoom, Kit 4335 Quay St Wheatridge Jefferson County This permit has been issued to: Master Abaters, LLC 12445 E 39th Ave., Unit 402 Denver, CO 80239 Project Supervisor: Rodney Payne Cerification No.: 13337 Project AMS: Jonathon Milazzo Cerification No.: 24795 Project Manager: Issued by: TS 1 m (O-Dvocm-_ a � m N 3 k U O U R ([ O 3 7 O v 10 _ �cn c m 3= t o�'I�D CD�� (, U73CCDD C 7 O N 7 (D C v o w n� v 5 o c Qo 7 9 (D n O� i m m m M s 6 (D 3 O '6 C (D Oo Si (D I S. S S (D C O N ID a : S O .00-. ^D O (D o GN v CD i (D p = O 3 3 3 3 g n0(D C) � o (u O 6 O CD (D CD .p-. S o�cDwm N O O 3'6 v (D o o 3 v N Co O ID N 3 CD ° m o 71 _o p� — D N N (n • Q =t O Q. m 6 m 3 Q y CD CD (D o-3 3 in y (n rn 0 3 v v o v <Cn CD co 3 = (6D < N CS q CD (D CD N N (OD O � 3 3 Q. 3• o < o m v(o �3CD _-a M c� 3 v� o C, N (D 3 = O N (D O � fll 'n =r CD p (D N Cr m::,(D Q x sD (D. (n 0 o (D (D w v _.3 O < CS Q. C2 n (D N C 6 02 O CN D (D o Zo C) m m 6 (Dn (n y„- r o - (� �vO '::r (n (D m o c C1 (n C Q 7 < 3 (D 0- -p n O O O N c) Ci M CS O (D p m 7 v :, 7 (O 7'I D o p ^CD IV O 47 O * 0” o ro O Cn m o �CD OO m CD CD O O (D (D 3a sv CD CJ 3 o N 3 � 0 3 O ^' 3 o n D iv o p Z o O O (p Cn N p (z CD cn (2 K CO 3 CD CD -M < 4tCD n p U> m 2 N N N _co OD Qo v3 CD U) (f] CD m `° D oZ N °' n 3 Z v 0 0 p W p(D -r. N C D o = nzim 0 0 O v moA (D Q. (_ HT1 m S11 (D O m N CO N > O 0 ,f (D C= w m � CD 3 O (D 7 °' 3 CD sD D (D D CS CD n G 0 CD W CD c O -n O D N O O Vi CO) O x C C C in 0 oCD m CL rt CD p ^« m n rml. Cn cn .p»• -t i bl � C)n) o O -t, - 0 O (o O k O N N rt -CJ M {= d1 I. CD O Om N M (D D Q i I ° (n 7 p C7 -i i W O 0,3 0 0 — CD Z jal�. Q (D *k W Q CJ O W -O C D N N 7 Cb O ON Q m D D (w0 i D r m n sn cn rp C) cn (n W c D 3 O 3 CD C07 CL 3 IIIcQ CD CD (a CO)(D D CL m o o o (o CDCD Q w m \ `< D m ! m (n o s cn 3 (D O CD ® coZ N O O CD o N -n 7 Z El p -0 (� v p 1 "0 �. O 77 (on 3 a O 3 D cn N 3 o s o CD w a m O Q NO 11 Sv 3 C:) A 7 0 rr p c W cn (O m r+ CD O TI O o -n (D ® co � � CD -I+ m m v om n ❑ n Q CD cn v m (D N. CD O ET �. rh 7 40 (n C ❑< CD rF N Cp m CD O CD .. X®3 s O O— 3 W 7 < 0 Cn Cf) 0- (O CD 00 ® m > o CT CD O O O ° kHN0 y®m j w �' '-`�3 rn m�mN 7'I -n m STlq n Cn r N 47 O * 0” J- i N CD O Cn C) O O Ci CD OO N CD CD O O (D (D 3a sv CD Q 9k o n Z m 0 n o v CL 1 C) v o Q CD a) 3 o CD N (z CD cn CD 3 m m C> (D (D n p U> m o N m CD ? Qo < 3 3 CD `° D n 3 W p(D -r. C D -m = 0 0 0 moA cri Q. o- HT1 o O co CO N > O cn C= SU o �o Q 3 N � sD U) `° 0 0 CD W CD _ (D O Q _ Vi CD O C C 6 0 m CL rt CD ^« v Q Nm -t i bl � C)n) CD CD O O (o Om (Q CJ N CD 2 M {= d1 N M (D D Q - < I ° -i i W O 0,3 0 0 Z i Q (D W Q CJ O C i N v Uj N 0 �� m W CD m m O O O O O O O T 0 0 0 0 0 0 �A a C1 Ca v Vi O CD (D CD CD (D (D N J N N N N N_ N N T .� ( �1 O CO)) O � O 01 CD ;o o y D Cl) ❑❑❑❑❑❑❑ cQ lJ DT v n W fA (SEA ffl Ffl Ffl Fa �• cn a w (A 0 C:) 0 0 0 0 0 � 6 CD Z w(owZZO IA �• D m �. � c �,Q Z O Cr T T —, Z DOI -0 m(D n z o D _ 33g C)6. o� Cf) (D O T Z (n U) o O0 0 Z m OO (n _ Cl) � CD CD v 57 Z 8 Q O 00 mZ 0o 0 0 � a CL !Q Q m� (DCD CD O O O CD 0 -��.0 O O :� D Q. (2 rn(0wna CD Ui O O (D CD COD v 0 -u T -+ N N N— C7 V J W mca800 3 r m J J N N • (T • � ❑❑❑®❑0❑ y v 00 r0r�F0f0r) C� 0 (b (b P. 110 C) 0C)CDO O 000000 -�-I VJ D o Q < T w m w Z Z o 0000�T� �r O O o Z3- ^ (D CD O N N COD N v O W cy-`� m v lC) > o m O CD- n -n m m Q -i 0 �000 �Z 6 m -TICD Q)) Z 'i1 (� 3 _ CD 0 m,ivpAD nm� vxo�cC7�o .� nOmQr.r. °n(W (-DFn�00 @JwwO,jO7o�Q3 P1 N � o J) 'a O 0 co Wim° to O (T 6 w p (D O U) = 0 m C N S 3 O � STlq 47 O * 0” CD CD v Uj N 0 �� m W CD m m O O O O O O O T 0 0 0 0 0 0 �A a C1 Ca v Vi O CD (D CD CD (D (D N J N N N N N_ N N T .� ( �1 O CO)) O � O 01 CD ;o o y D Cl) ❑❑❑❑❑❑❑ cQ lJ DT v n W fA (SEA ffl Ffl Ffl Fa �• cn a w (A 0 C:) 0 0 0 0 0 � 6 CD Z w(owZZO IA �• D m �. � c �,Q Z O Cr T T —, Z DOI -0 m(D n z o D _ 33g C)6. o� Cf) (D O T Z (n U) o O0 0 Z m OO (n _ Cl) � CD CD v 57 Z 8 Q O 00 mZ 0o 0 0 � a CL !Q Q m� (DCD CD O O O CD 0 -��.0 O O :� D Q. (2 rn(0wna CD Ui O O (D CD COD v 0 -u T -+ N N N— C7 V J W mca800 3 r m J J N N • (T • � ❑❑❑®❑0❑ y v 00 r0r�F0f0r) C� 0 (b (b P. 110 C) 0C)CDO O 000000 -�-I VJ D o Q < T w m w Z Z o 0000�T� �r O O o Z3- ^ (D CD O N N COD N v O W cy-`� m v lC) > o m O CD- n -n m m Q -i 0 �000 �Z 6 m -TICD Q)) Z 'i1 (� 3 _ CD 0 m,ivpAD nm� vxo�cC7�o .� nOmQr.r. °n(W (-DFn�00 @JwwO,jO7o�Q3 P1 N � o J) 'a O 0 co Wim° to O (T 6 w p (D O U) = 0 m C N S 3 PERMIT NO: JOB ADDRESS: JOB DESCRIPTION: City of Wheat Ridge Residential Roofing PERMIT - 201705351 201705351 ?SSUED: 08;03/2017 4335 Quay ST EXPIRES: 08/03/2018 Residential Re -roof to install asphalt shingles with OSB ROOF DECKING - 20 SQ. *** CONTACTS *** OWNER (720)290-2070 PIERCE RORY A SUB (303)222-0600 Jim Faydenko 150044 Roof N Exteriors, LLC *** PARCEL INFO *** ZONE CODE: UA / Unassigned USE: UA / Unassigned SUBDIVISION CODE: 2405 / BARTHS, COULEHAN GRANGE, WHEAT BLOCK/LOT#: 0 / *** FEE SUMMARY *** ESTIMATED PROJECT VALUATION: 12,306.00 FEES Total Valuation 0.00 Use Tax 258.43 Permit Fee 251.85 ** TOTAL ** 510.28 *** COMMENTS *** *** CONDITIONS *** Effective December 1, 2014, asphalt shingle installations require an approved midroof inspection, conducted when 25-75 percent of the roof covering is installed, prior to final approval. Installation of roof sheathing (new or overlay) is required on the entire roof when spaced or board sheathing with ANY gap exceeding one half inch exists. Sheathing and mid -roofs may be called in at the same time, one hundred percent of the sheathinu_ must be complete and 25-75 percent of the mid -roof may be complete. Asphalt shingles are required to be fastened to the roof deck with a minimum of 6 nails per shingle. Ice and water shield is required. Eave and rake metal is required. A ladder extending 3 feet above the roof eave and secured in place is required to be provided for all roof inspections. Roof ventilation is required to comply with applicable codes and/or manufacturer installation instructions, whichever is more stringent. In order to pass a final inspection of elastomeric or similar type roof coverings, a letter of inspection and approval from the manufacturer techn4 a1 representative stating that "the application of the roof at (project addressl has been applied in accordance with the installation instruction for (roof mnterial brand ame; roof covering" is required to be on site at the time of final '_nspectior, Roof inspections for ROOFS OVER 6/12 PITCH: 3rd party inspection will be required, the 3rd party inspection report will be collected at final roof inspection performed by City o= Wheat Ridge. If report is not available the final inspection will not be completed. INSPECTION RECORD IFASPE:.TION ONLINE FORM: http://www.c'.wheatridge.co.us/in:;pection ii JSPECTION REQUEST LINE: (303)'r"34-5933 Cancellations must be submitted via the online form b -fore 8 a.m. the day of the i,Ispgctior. Occupancy'T12e Inspections will no: be perfort-ned unless this card is posted on the project site. j **Rept est an insp-,c?ion before 13.59 p.m. ;midniight) to receive an inspection the fol!ov,ing business day.*, - Inspector 11Aus. Sign ALL Spaces pertinent to this project �-- --- ------ I !rlspector --� Foun.'ation inspc;ctions DaiQ Comments ' Pier —� -- -- - -�--- ----- — — -- ----- — 1 Concrete Encased Ground (CEG) LFoundation T.F. uett•:r-- Do Not Pcur• Concrete Prion ro k,oval Of The Above Insi:tectioiys Underground/Slab InsFectic.ns 1 Date Irlsper=trar Comments 10tials P;ectrical— aewe- Se vice Plumbinq _Do NiA Cover Uil dergroline's;_S,Inw.M_-Slab_Work Pri -.)r, To A4proval OfTheAbove Ir. ipections r Inspac6r-7-- --- Rougn Inspections Date j 'omments - --� Vail Sheathing Mid -Roof Z''Ll�—---- ---- -- r �tti i INIn'! Tie -- -- — . Rough Elelr..ric Rough IP mbi, d/Gas Line I Rough Mec is !ical Rotgh raining II Kaugh Grading Cryw311 Screw i Nail Final Inspections Dat Inspector T Comments initials _ _ _ _ and.,capir5 & Parking /'Manning [ ept. —� Inspections from these entities F'huuld be •equested -- -- - -- --- - — - one ov 'k in advance. For landscaping and Rin � ROW & Drainagi : Public'y ,r! s Deft. - g F'oodpl= in Insfactior, (if applicaurF) 1 e tic ns ca!' 301-2: i-'•346. Fir ROW and drainage — - -- — -- -- — -- I it; )ec nor cal, 'Y13-235-2851 For ';re '-;,spectior s i i -ire i, spertior, i Fire Pr,tection Dist. I I co0.act the Protection ')istrict for yot,r projec'.. Fina: FIE Arical I I Final i'h,mt -ig ina, ME aha sic ar IRoot ---- -- ---- - -- —--------- Fi+ 31 Windu v/;. Dors I, - Building — — - ­_ — -- -- ---- --- I NOTE: A,' itf. rs rr; ..5 completed and approved by Planning, Public Works, Fire and Bui' ging before a Certificate of r` ; yr ?n, y i.-: iss,.,p .. ,nroval of the Final Building inspection does not constitute authorizv.icn of orcx�,,ai►cy. — *For .a1 ` von agE p �r m .. F as tip sure that rough inspections are completed from the Fire District a:io electrical low voltage by the Bui, lir.. c r..panI .y s Nr, r�P '*ted Until A Certificate of Occupancy Is Issued Nrot► ct This Card From The Wea+h 9011ON SIH13AOM13H ION OO af :aoloadsul :ale(] ££65-b£l-£0£ je uoijoadsut-aa ao} Ileo `apew uaaq aney suoi;oaaaoo uayM. saA :paainbaa uoiloodsul-aa Nd/INV quail :uoiloodsui aol apepena quo ON r 01/- /n :aagwnN Mwaad :ssaappd qof :adA1 uoiloadsul -71V iv 33I10N N01103dSNI xeJ 6z68 LEz (EOE) • 00140ssgz-3Ez (EOE) aull uolloadsul EE6S-bEZ (£OE) J uoisinid uoiloodsul 6uippe 3Jam 1V3HM =10 A113 A y I AN City of Wheat Ridge Residential Roofing PERMIT - 201705351 PERMIT NO: 201705351 ISSUED: 08/03/2017 JOB ADDRESS: 4335 Quay ST EXPIRES: 08/03/2018 JOB DESCRIPTION: Residential Re -roof to install asphalt shingles with OSB ROOF DECKING - 20 SQ. *** CONTACTS *** OWNER (720)290-2070 PIERCE RORY A SUB (303)222-0600 Jim Faydenko 150044 Roof N Exteriors, LLC *** PARCEL INFO *** ZONE CODE: UA / Unassigned USE: UA / Unassigned SUBDIVISION CODE: 2405 / BARTHS, COULEHAN GRANGE, WHEAT BLOCK/LOT#: 0 / *** FEE SUMMARY *** ESTIMATED PROJECT VALUATION: 12,306.00 FEES Total Valuation 0.00 Use Tax 258.43 Permit Fee 251.85 ** TOTAL ** 510.28 *** COMMENTS *** *** CONDITIONS *** Effective December 1, 2014, asphalt shingle installations require an approved midroof inspection, conducted when 25-75 percent of the roof covering is installed, prior to final approval. Installation of roof sheathing (new or overlay) is required on the entire roof when spaced or board sheathing with ANY gap exceeding one half inch exists. Sheathing and mid -roofs may be called in at the same time, one hundred percent of the sheathing must be complete and 25-75 percent of the mid -roof may be complete. Asphalt shingles are required to be fastened to the roof deck with a minimum of 6 nails per shingle. Ice and water shield is required. Eave and rake metal is required. A ladder extending 3 feet above the roof eave and secured in place is required to be provided for all roof inspections. Roof ventilation is required to comply with applicable codes and/or manufacturer installation instructions, whichever is more stringent. In order to pass a final inspection of elastomeric or similar type roof coverings, a letter of inspection and approval from the manufacturer technical representative stating that "the application of the roof at (project address) has been applied in accordance with the installation instruction for (roof material brand name) roof covering" is required to be on site at the time of final inspection. Roof inspections for ROOFS OVER 6/12 PITCH: 3rd party inspection will be required, the 3rd party inspection report will be collected at final roof inspection performed by City of Wheat Ridge. If report is not available the final inspection will not be completed. City of Wheat Ridge Residential Roofing PERMIT - 201705351 PERMIT NO: 201705351 ISSUED: 08/03/2017 JOB ADDRESS: 4335 Quay ST EXPIRES: 08/03/2018 JOB DESCRIPTION: Residential Re—roof to install asphalt shingles with OSB ROOF DECKING — 20 SQ. I, by my signature, do hereby attest that the work to be performed shall comply with all accompanying approved plans and specifications, applicable building codes, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with this per I further atte that I am legally authorized to include ali entities named within this document as parties to the work to be performed and that to be performed�isclosed in this document and/or its' accompanying approved plans and specifications. d'l A,--.,< `-D Signature off OWNER or CONTRACTOR (Circle one) Date I.This permit was issued based on the information provided in the permit application and accompanying plans and specifications and is sub.ect to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures. 2. This.permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and received prior to the date of expiration. An extension of no more than 180 days made be granted at the discretion of the Chief Building Official and maybe subject to a fee equal to one-half of the originalpermit fee. 3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard requirements, fees and procedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of the Chief Building Official and is not guaranteed. 4. No work of any manner shall be performed that shall results in a change. of the natural flow of water without prior and specific approval. 5. The permit ho der shall notify the Building and Inspection Services Division in accordance with established policy of all required inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services Division. 6. The issuance or granting of a permit shall not be construed to be a permit for or an approval of, any violation of any provision of any applicable code or any ordmanee-or egulation of thi . Approval of work is subject to field inspection. Signature of Chief Building Official Date REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. Dan Schultz From: no-reply@ci.wheat ridge.co.us Sent: Wednesday, July 26, 2017 10:20 PM To: CommDev Permits Subject: Online Form Submittal: Residential Roofing Permit Application Categories: Danny Residential Roofing Permit Application This application is exclusively for new permits for residential roofs and for licensed contractors only. This type of permit is ONLY being processed online --do not come to City Hall to submit an application in person. Permits are processed and issued in the order they are received and due to the volume of requests, time to process varies and is subject to change. YOU WILL BE CONTACTED WHEN YOUR PERMIT IS READY FOR PICK-UP AND WILL BE GIVEN A SPECIFIC DATE AND TIME WINDOW TO COMPLETE THE TRANSACTION. You will be notified if your contractor's license or insurance has expired, and you may update those documents at the time you are issued your permit. For all other requests: Homeowners wishing to obtain a roofing permit must apply for the permit in person at City Hall. Revisions to existing permits (for example, to add redecking) must be completed in person at City Hall. All other non -roofing permits must be completed in person at City Hall. The Building Division will be open from 7:30-10:30 a.m., Monday through Friday to process these types of requests. THIS APPLICATION DOES NOT CONSTITUTE A PERMIT. DO NOT BEGIN REROOFING UNTIL PERMIT HAS BEEN ISSUED. Is this application for a Yes residential roof? How many dwelling units Single Family Home are on the property? PROPERTY INFORMATION Property Address Property Owner Name Property Owner Phone Number Property Owner Email Address 4335 Quay Street Rory Pierce 720.290.2070 rory@minersalley.com Do you have a signed Yes contract to reroof this property? It will need to be provided at the time of permit pick-up. Attach Copy of Contact rory pierce ATR RNE.pdf CONTRACTOR INFORMATION Contractor Business Roof N Exteriors Name Contractor's License 150044 Number (for the City of Wheat Ridge) Contractor Phone 303.222.0600 Number Contractor Email Address dean@roofnexteriors.com Retype Contractor Email dean@roofnexteriors.com Address DESCRIPTION OF WORK Are you re-decking the Yes roof? Description of Roofing OSB, 40 Yr asphalt Material Select Type of Material: Asphalt If "Other" is selected N/A above, describe here: How many squares of the 20 material selected above? Does any portion of the No property include a flat roof? If yes, how many squares Field not completed. on the flat roof? TOTAL SQUARES 20 (pitched + flat) of all 2 roofing material for this project Provide additional detail House, shed, dog house here on the description of work. (Is this for a house or garage? What is the roof pitch? Etc) Project Value (contract C $12306 value or cost of ALL materials and labor) SIGNATURE OF UNDERSTANDING AND AGREEMENT I assume full Yes responsibility for compliance with applicable City of Wheat Ridge codes and ordinances for work under any permit issued based on this application. I understand that this Yes application is NOT a permit. I understand I will be contacted by the City to pay for and pick up the permit for this property. I understand that work Yes may not begin on this property until a permit has been issued and posted on the property. I certify that I have been Yes authorized by the legal owner of the property to submit this application and to perform the work described above. Name of Applicant Dean Millar Email not displaying correctly? View it in your browser. 3 fuer a latanaca aeuaalttams Ph: 303 222-0600 Fax: 888 370-6018 Roof N Exteriors, LLC Email: officearootnexteriors.com 12(181 W Alanioda Pkwy, 0229 Web Site: roofnexteriors.com Lakewood. CO 0022Li AUTHORIZATION TO REPAIR Homeowner (Insured): L,Ir ; • I r Home Phone: Address: `tx�j ar Work Phone: 1 0 1 ti d� City/State: Mh T- f o�c,, LU Zip: ) 0Sl Ceti Phone: �(� ,�, Email: Job Site Address (if different from above): �l/1'e'+n ROOFING SPECIFICATION Shingle Year. 25 ❑ 30 ❑ 40 rl;x- 50 ❑ Life ❑ Hail Resistant ❑ Color. Brand: i �LL� �,A-,rt 7 Pitch(s): /12 /12 /12 Story(s): i Layers:' '' Tear Off: Yes No ❑ Ice & Water, Overhang Depth ` Felt: �3 Vents: ❑ R&R 0 D&R ❑ Drip Edge: Eve [,tj Rake `Y LF in Est. Color: Decking: $70 / Sheet R&R if needed Furnish Permit: 14 Skylight(s): ❑ Magnetic yard for nails:,{ Remove Trash from roof, gutters and yard: V1 Protect landscaping where applicable: Q t�? GUTTERS SPECIFICATION Gutters: Color. CO -� rt e� Size: 5' 12f 6' ❑ Downs: 2'x3' 2' 3-W ❑ Replace All: Yes 0-1.(No ❑, LF in Est. _� Gutter screens: Yes ❑ NoA DELIVERY INSTRUCTIONS & NOTES Material delivery. Shingles roof top Yes' ❑ Other items driveway placed: Middle on RT ❑ or LT M side (Drive clear) Approximate dates of service: Property owner preferred completion date: /6 / 11 Driveway Damage: Yes ❑ No By law, RNE shall hold, in trust, any payment from the Insured until roofing materials have been delivered to the property or until RNE has performed a majority of the roofing work on the property. (SENATE BILL 12-038) PROCEEDS BREAKDOWN Total Insurance Claim $ 15y SL G 4 ' TOTAL AMOUNT $ t t; `k5O , ��, he total amount of the agreement can change with additional mouses from aap'scab!e overhead and profit. deductible, perm ts. s;;p;;ements, taxes and upgrades. t'we understand that the coo, pony is a geneera' contractor and is entitled these p "ment (rorn the r-surance company. Cus"cimer Initials Please make checks payable to: Roof N Exteriors, LLC. Payment Schedule 1) Fest insurance Draft or equal sum due upon signing as a Deposit to start unit. 2) Frat balance due upon comp'etion to Include applicable overhead and pro t, deducab'c. permits, supp!cments and uplades. PAYMENT DATE CHECK 0 AMOUNT Fust Check $ Live hereby authonze Roof N Exteriors, C. to communicate Wth our insurance and mortgage companies gKour behalf. Mortgage Co. Accountir Phone Number Insurance Co. 1 e r, _ Policy *t QA 7% (9 9'.110 Claim it S UUia t fol 3h: Phone Number X_u Coen' pyla x.� .- CGent Sk3nalure Own Field Representit,ve, A(,iJ J Scanned by CamScanner i CITY OF WHEAT RIDGE _��9rBuilding Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type: fl�F Job Address: 13 f- U, 4 G ( Permit Number: ?(,/7t) F 3 Li No one available for inspection: Time V I ') /PM Re -Inspection required: Yes No When corrections have been made, call for re -inspection at 303-234-5933 Date: ! �l Inspector: DO NOT REMOVE THIS NOTICE i CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type: Job Address: �3 r✓.A?✓� 1 Permit Number: r: v ❑ No one available for inspection: Time J{U AM/& 1 f Inspection required: No / When corrections have been made, call for re -inspection at 303-234-5933 Date: -'��/ � ��/ � � Inspector: 1<11t DO NOT REMOVE THIS NOTICE COMMUNITY DEVELOPMENT DEPARTMENT Building Permit Number : 15324 BUILDING INSPECTION LINE - 303-234-5933 CITY OF WHEAT RIDGE Date : 4/11/03 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 - (303-235-2855) Property Owner: Property Address Contractor License No. MARY ANN MARTENS 4335 QUAY ST 17944 Company : Arvada Lakewood Fence Co. Phone : 995-3010 Phone: 424 1089 OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback dislances proposed by thjs permit application are accurate, and do not violate applicable ordinances, rules or regulation of the City of Wheat Ridge or covenants, easements or restrictions of recortl; that all easurements shown, and allegations made are accurate; that I have read and agree to abid~ by all conditions printed on this application, and that I assume full responsibil' r cpliance with the Wheat Ridge Building Code (U.B.C.) and all olher applicable WF}~f2i~gg rdinances, forwork under this per,mit. ~ (OW N ER)(CONTRACTOR) G Construction Value : $3,800.00 Permit Fee : $126.50 Plan Review Fee : $0.00 Use Tax : $45.60 Total $172 10 Use Description : INSTALL 242' 6F 5' SEMI-PRIVACY FENCE W/ TWO GATES. REMOVE OLD FENCE. BUILDING DEPARTMENT USE ONLY Zoning Comments: Approval : MP Zoning : R-2 Building Comments Approval: BG Public Works Commenxs: Approval : Occupancy: Walls SIC : Sq. Ft. : 4110103. OK PIease Note: pwner/ oonttactor is responsible for locating property OK. 4/10/03 lines and constructing improvements accr.rding to the approved plan and required developmcnt star,dards. The City is not responsible fur ir.acc:art.; infnnna:ion submitted within tkie ptan sct and onv errors resulting from Roof : Stories : Residential Units : Electrical License No : Company: Expiration Date : Approval : Plumbing License No : Company: Expiration Date : Approval : Mechanical License No : Company : Expiration Date : Approval: (1) This permit was issued in acwrdance with lhe pmvisions set foAh in yopur application and is subject ro the laws of the State ot Cobrado and to the Zoning Regulations and Building Code of Wheat Ridge, Colorado or any other applicable ordinances of the City. (2) This permit shall ecpire if (A) the work authorized is not commenced within sixty (60) days from issue date or (B) the building authorized is suspended or abandoned for a period of 120 days. (3) If this permit expires, a new permit may be acquired for a fee of one-half the amount normalty required, providad no changes have been or will be made in the original plans and specifcations and any suspension or abandonment has not exceeded one (1) yeac If changes are made or if suspension or abandonment exceeds one (1) year, futl fees shall be paid for a new permit. (4) No work of any manner shall be done lhat will change the natural Flow of waler causing a drainage problem. (5) Contractor shall notiy the Builtling Inspector twenry-four (24) hours in advance for all inspections and shall receive written appmval on inspection card before proceediing with successive phases of the job. (6) The issua e 9f a pe mit Ihe approval of drawings and specifications shall not be consirued to be a permit for, nor an approval of, any violalion of the provi~ of iJne trdes or any other ordinance, law, rule or re9ulation. s~, Chief Building Ins ector CONIlVI[JNITY DEVELOPMENT DEPARTMENT Building Pexxnit Number: oF w"EA' P BUII,DING INSPECTION LINE - 303-234-5933 Date: CTTY OF WHEAT RIDGE " 7500 WEST 29TI3 AVENUE WHEAT RIDGE, CO 80215 - (303-23j5-2~85'Y~ ~?/Vyry ~OC OR P00 P~-liL l~.Pdd-ll~~l ~ Property Owner: Fh( 4 u)'7 t'A , ' v Property Address: y 3':> S Ck-« y 5k, Phone:36>-`i'/ S - 3°i° Contractor License No.: Phona: 3 0 3' `-l 2 ~-1-t ek Company: Y~ v OK'NER/CONTRACTOR SIGNATI7RE OF UNDERSTAPiDING AND AGAEEIYIENT I hereby certify that the setback distances proposed by this perrttit applieaGon aze accurate, md do notviolate applicable ordinances, mles orregu]ations of [he CiTy of Wheat Ridge or covenants, euements orrestrictions ofrecord; that all measurements shown, md allcgations made aze acwra[e; [hat I have read md agree to abi e by all conditions printed on this applica5on md [hat I assume full responsibility for compliance with the Wbeat Ridge Building Code (U.B.C) md all other applicable Wh t Ridge Ordinances, for work under this permit. ~ . (pWNER)(CONTR4CTOR):SIGNSD . ✓ DATE Construction Value:$ 3'~ 0c) Permit Fee:$ Plan Review Fee:$ Use Tas:$ TOtdl:$ DESCRIPTION: ~,ti ,{.t l1 2~I 2o+ S S 9 r, U w c~~ BUII,DING DEPARTMENT USE ONLY SIC: ZONINGCOMMENTS: n NI~p1O~ Approval: 01~- zoning: BUILDING COMMENTS: Approval: O.~C PUBLIC WORKS COMMENTS: APproval: Occupancy: Walls: Elec4ical License No: Company: t//,/D ~O -3 Roof: Plumbing License No: Company: Mechanical License No: Company: Expiration Date: Expiration Date: Expiration Date: Approval: Approval: Approval: (1) Tpis pumit wu usued iu accordence with ehe provisiom set fonh in yow applicadon and'a subjxt to Ne laws of the SEate af Colondo end to the Zonmg Regula¢oaa md Building Codu of Wheat Aidge, Coloado or any athu applicable ord'mances of the Ciry. (2) 1'Lis pamit ahall upire if (A) the work auNoriud is not commrnced vritLin sixty (60) days from issue date or (B) the bulding authorized is suspended or abandoned for a period of 120 days. (3) IfiLispeimitexp'vu,anewpe=mitmaybeacquiredforafreofone-helftheamountnolmallyrzqui*ed,yrovidednochangeshavebernorwillbemadein the origivalplaos endspecificatioas md auy suspcnsionor abandonmenthaznotexceeded one (1) yeaz. Ifetanges have been orifsutpmsion or abandwment exceeds one (1) yeaz, full fres shall be paid for a aew peauit (4) No work af any mauna sE%11 be don<that will change the nature] flow of wate[ causing a drainage problem. (5) ConaactorsLallnotifytLeBUildinBlnsPeetortwenty-fms(24)homsinadvancefwallinspectionsandshellraeivewrittenapprovaloninspectioncardbefore proceeding wiffi successive pLases of thejob. (6) The issuance of a pamit or the approvat of drawings md speci5cations sLall not be conswed b be a pemilt for, nox av approval of, any violation of the provisions a7he,, d ing codes or any other ardinanw, la`v. rvle or ttgulation. 1 i Chief Buil ' spector . v_ c ~ , k Ll 7P79' Stories: Residential Units: IMPROVEMENT LOCATION CERTIFICATE 4335 QUAY STREET, (tEGAlpEStRIP11pJFU4NIeMED6YLliENTJ LOT12, MAUREEN 5UBDIVI510N, COUNTY OF JEFFER50N, STATE OF COLORADO. ' I ' S•O U TI L. ES N' T y C P lAT) I ( I I`, I N I I r ~I ~I w ~ ~ I - UI NI _iti° _ ~ r ~ Q~ O -<4Nt_ I ~ 1 Ibb 12Z ; N 01. ~ p I-6TOP--Y 13q-1 G✓-- ~ e 2ES~OErK.~ i I V' J n ~o O I Co. I I 5'- I ~ S N. G~2 I < . ~ ~W iZ15. 4' I . ` ~ I I I ~wti+~ I LP ~DRivE I I b I -7cJ' ' -'1335 QU.o: ( STP- E ET 13 NOTE . L1SE~ ~UTERS@CTiON pF CD-uVy ~T2EET ANr~ A-14r-l ,>vcw1uE Fo2 LotiTILOL. CERTIFYCATTON: I hereby cerHfy that this impmvement location certiCcate was prepared for CTX MORTGAGE, THAT IT IS NOT A LAND SURVEY PLAT OR IMI'ROVEIvTENT SURVEY PLAT, and that it is not to be relied upon for the eatablis}unent of fence, building, or other future improvement lines. I further certify that the improvements on the above described Parcel on this date, JUNE 17,1996, except uNlity connecNons, are entirely witltin the boundaries of the parcel, except ae shown, that there are no encroachments upon the described premises by improvements on any ad'oining premises, except as indicated, and that there is no APPARENT evidence or sign of any easement crossing orbur~ening any part of said parcel, except as noted. FLOOD HAZARD CER77F[CATION: Dased only uPon my interpretation of the cutrent HUD Federal Administration Flood Hazard Maps, but without benefit of actual elevaHons used in standard survey methods and declarations b local juriadictions, the property described hereon DOEi NOT appear to be located in a flood hazard boundary. Y Map Dated 02-04-88 Panel No. 085079 0005C Zone C CENSUS TRACT NO. 106.03 ~~~NPP~Q iq LENZINI AND ASSOCIATFS DATE: JUNE 11, 1996 Q~,•~ERr*••TE,9~ Professional Land Surveyors BORROWER: FEE: MARTENS $85.00 ' ~ F';F ~ =vl 7905 Zenobia Stteet Westminste C l d 80030 , ~ r, o ora o JOB NO.: 0696044 = s a o- 03) 430-0209 FAX (303) 430-0825 #CR065 CH16LED IN CONC. WKF/LURB MEM I~ • • ~ ' oFWNDPIWRNAND UP ^ V~O PAUL A. LENZINI PLS 11636 ,,NA(niiwnw ~o } COMMUNITY DEVELOPMENT DEPARTMENT Building Permit Number BUILDING INSPECTION LINE - (303-234-5933) Date CITY OF WHEAT 7500 WEST 29TH WHEAT RIDGE, CO 80033 RIDGE AVENUE - (303-235-2855) Property Owner: RORY PIERCE Property Address : 4335 QUAY ST 15513 5/13/2003 Phone: 424-7416 Contractor License No. : 18464 Company : B& F Heating & PJC Phone : 431 8914 OWNERICONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby oertify that the setback distances proposed by lhis permil applicalion are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenanis, easements or restrictions of record; lhat all measurements shown, and allegations made are accurale; that I have read and agree to abide by all conditions printed on this applicatioin, and that I assume full responsibility for compliance with the Wheat Ridge Buildin9 Code (U.F3.C.) and all other applicable Wheat Ridge ordinances, for work under this permit. (O W NER)(CONTRACTOR) Construction Value : $3,099.00 Permit Fee : $126.50 Plan Review Fee : $0.00 Use Tax : $37-19 Total: $163.69 Use : Description : INSTALL 80,000 BTU'S FURNACE. INSTALL 2 TON A/G CUSTOMER TO PRO ID ELECTRICAL ~ ~r~ 1o-) BUILDING DEPARTMENT USE ONLY SIC : Sq. Ft. : Zoni,ng Comments: Approval: Zoning : Builg Commenks:`` Approval : Pubiic Works Comments: APProval: Oc:cupancy : Walls : Roof : Stories : Residential Units : Electrical License No : Plumbing License No : Mechanical License No : 18464 Company : Company : Company : B& F Heating & A/C Expiration Date : 6/25/2003 Expiration Date : Expiration Date : Approval : OKIKS Approval : Approval : (1) This permit was issued in accordance wilh the provisions se[ forth in yopur application and is subject to lhe faws of the Stale of Colorado and to the Zoning Ragulations antl Building Code of W heat Ridge, Colorado or any other applicable ortlinances of the City. (2) This permit shall expire if (A) the work authorized is not commenced within sixty (60) days from issue date or (B) the building authorized is suspentled or abandoned for a period of 120 days. (3) If lhis permit expires, a new permit may be acquired for a fee of one-half the amount normally required, provided no changes have been or will be made in t e original plans and specifcations and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment exceeds one (1) year, full fees shall be paid for a new permit. (4) No work of any manner shall be done that will change the natural flow of water causing a drainage problem. (5) Contrector shall notify the Building Inspedor hventy-four (24) hours in advance for ail inspections and shall receive written appmvai on inspection card before pmceediing with~ essrve pha s of the job. (6) The issuancey/2 p8rn~~Proval of drawings and specificalions shall not De construed to be a permit for, nor an approval of, any violalion of the f .4~ldin e o r ordinance, law, rule or re9ulalion. provisions o llle Chief Building Inspector Mu. I ouuwiiy reirni[ ivumDef : BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE Date :~}~ZG~Q 3 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 pppLICATio N Property Owner :ory e rC e Property Address : q335 Qua y 5f Phone : jQ3 L{Zq 744 Contractor License No. : fg4 (c Company: Phone:,jQ3't'3~ OWNER/CONTRACTOR SIGNATURE OF ~ AND AGREEMENT I hereby certify that the setback distances proposed by this permit applieation are accurete, and do not violate applicable ordinances, rules or regulations of the City of Wheal Ridge or covenants. easements or restnctions of rewrd; that all measurements shown, anA allegations made are accurate: that I have reatl and aQree to abide bY all conditions printed on this applicahon, and lhat I assume Iuil responsibility for wmphanca with the Wheat Ridge Building Code (U.B.CJ and all other applipble Whe3J.3idge ordinance~{, forwork under this certnd.. (OWNER)(CONTRACTOR) Description : 11,5MrnE Approval : Zoning : Approval : Approval : Occupancy : Walls Electrical License No : Company ; Expiration Date : Approval: construction value : 3~9 ~ - DATE~L~~ Use: ~ DOD ~1L1~ QC e BUILDING DEPARTMENT USE ONLY SIC Roof Plumbing License No : Company : Expiration Date : Approval: Mechanical License No : Company: Expiration Date : Approval: enee vAth sub (1) RThis egulalions andiBu Id ng C~f WTeat Ridqe CobraCO or, any othera001 ble ordi ances of tl e Oiry~ I~ a~e State M Coloneo anC ro Ne Zoninq (2) This pertnil s0all expire if (A) Me work auMOnzeE is rqt commenceE wiNin IIixty (80) Cays hom iesue Oate a(B) the builtliny authotlzed is suspentle0 or aEandoneC lor a penod of 120 days. (7) II this pertnit expircs, a new permit may pe acQuired fpr a ke o/ onchal/ the amount rwrmelly requireC, qpviEeA no Uianqes have peen or will Ce mape in the onginal Olans antl specifiotbna anE any avapension or aCantlonment has rwl ezceeUeE one (1) yeac II Uanpes aro ma0e or if suspension or abanOonment exceetls one (1) ynr, lull fxs slull be paiq fpr s new, permit (a) No work of any manner shall be done Mat will Uqnpe pro naturai 11ox, of water nusing s drainage problem. (5) Contraqor shall notly the BuilOing Inapectw twenydour (24) houn in advance for all inapectione and sHall receive wtitten appioval on inspectlon ~ard Eefore proceedimg wlth successive phasea of N~p' 0 (6) Tne issuanx ol a permit or the approval o(Enwinps an0 speURraCOna ahall not be wnsUued W Ee a permit for. nor an a0proval W. any violation ot the Proviaions of the ouilainy COOes or any oUlef OrOinante,l8w, NIe or fepulaCan. Permit Fee : Use Tax : ~ Total : /-7 i Sq. Ft. : Stories : Residential Units : ~ Chief Building Inspector COMMUNITY DEVELOPMENT DEPARTMENT Building Permit Number : 15463 BUILDING INSPECTION LINE -(303-254-5933) Date : 5/6/2003 CITY OF WHEAT RIDGE 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80033 - (303-235-2855) Property Owner: RORY PIERCE Property Address : 4335 QUAY ST Contractor License No. : 21600 Phone : 424-7416 Company : A Electric Co. Phone : 762-9720 OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by Ihis permit application are accurale, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application, and that I assume full responsibility for compliance with the Wheat Ridge Building Code (II.B.C.) and all other applicable Wheat Rid9e ordinapces, for work under this permit. (OWNER)(CONTRACTOR)SIGNED4&92'"v' ~_z ' DATEy5-6_-~~Z Description : INSTALL 30A A/C CIRCUIT & 15A FURNACE CIRCUIT Construction Value : $400.00 Permit Fee : $30.55 Plan Review Fee : $0.00 Use Tax : $4.80 Total: $35.35 Use: lzm BUILDING DEPARTMENT USE ONLY Zoning CommentS; SIC : Sq. Ft. : Approval : Zoning : Build'ing Camments: Approval : Putilic Works Comments: Approval : Occupancy : Walls : Roof : Stories : Residential Units : Electrical License No : 21600 Plumbing License No : Mechanical License No : Company :A Electric Co. Company : Company : Expir3tion Date : 2/28/2005 Approval : OKIKS Expiration Date : Expiration Date : Approval : Approval : (1) This permil was issued in accordance with lhe provisions set fotlh in yopur applicalion and is subject ro the laws of the State of Colorado and to the Zoning Regulations and Building Code of Wheat Ridge, Colorado or any other applicable ordinances of ihe Ciry. (2) This permit shall expire if (A) the work authorized is not commenced within sixty (60) days from issue dale or (B) the building authorized is suspended or abandoned for a period of 120 days. (3) If this permit expires, a new permit may be acquired for a fee of one-half the amount normalty required, provitled no changes have been or will be matle in ihe original plans and specifcations and any suspension or abandonment has not ezceedetl one (1) yeac If changes are made or it suspension or abantlonment exceeds one (1) year, Full fees shall be paid for a new permit. (4) No work of any manner shall be done that will change the naturel Flow of water causing a drainage problem. (5) Contractor shall notify the Builtling Inspecbr twenty-four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceediing with successive phases of the job. (6) The issuance ot a permit or the approval of drawings and specifcations shall not be construed to be a permit for, nor an approval of, any violation of the provisions he building codes or any other ordinance, law, rule or regulaSion. P Ch rlild n I ctr CONIMiJNITY DEVELOPMENT DEPARTMENT Building Pemvt Number: ;Q0L BUILDING INSPECTION LINE - 303-234-5933 Date: CITY OF WHEAT RIDGE U 7500 WEST 29TH AVENUE : WHEAT RIDGE, CO 80215 - (303-235-2855) APPpp~14.py,y ~3Tj dON PropertyOwner: ~fp/L, Pit/CC PropertyAddress: 03S ~vo~J S7' Phone: 30 3 Contractor License No.: a 16L70 ComPanY: /9 "-r1zG-11-1 G GD Phone: 303 -7iV -f767D OWNER/CONTRACTOR SIGTIATURE OF UNDERSTM`DING AIVD AGREEMENT 1 hereby certify that [he setback distances proposed by this peimit application are accurate and do not violate applicable ordinances, rules or regulations of the CiTy of Wheat Ridge o covenanis, easements orrestrictions ofrecord; that all measuremenis shoum, and allegation: made aze accurate; that I have read and agree W abide by all conditions prin[ed on thi: applicaNon and that I assume full responsibility for compliance wi[h the VJhcat Ridgt Buitding Code (U.B.C) and all other applicable Wheat Ridge Ordinances, for work unde [his pemiit. (OWNER)(CONIRACTOR):SIGNED~ AC/LL✓(r'~~YL'~I? DATE6~6 G Construction Value:$ Permit Fee:$ Plan Review Fee:$ Use Tax:$ TOt31:$ DESCRIPTION: 3, y ~9~G G~ Li~ 7 BUII.DING DEPARTMENT USE ONLY SIC: Sq.Ft.: ZONING COMMENTS Approval: Zoning: BUILDING COMMENTS: Approval: PUBLIC WORKS COMMENTS: . Approval: Occupancy: Walls: Roof: Stories: Residential Units: Electrical License No: Plumbing License No: Mechanical License No: Company: Company: Company: Expiration Date: Expiration Date: Expiration Date: Approval: Approval: Approval: (I) Phis pvmit was issued in accordanc< with the pmvisions set to+th in your applicatiou avd is subject m th< laws of the Stah of Cololado and m the Zoning Regulatioaa and Buildi¢g Codu af Wheat Ridge, Colo}ado or any other applica6le ordinancu otthe City. (2) This penmit shell ezpire if (A) the work authonzed is not commenced within aixry (60) days from issue date or (B) tLe bwlding authonzed is suspended or abandoned for a period of 120 days. (3) Ifthis prnnit ncpires, a newpeavit may be acqu'ved fw a fee of ono-helf the amomt no'mally requ'ved, p+ovided vo chavg<s Eave bem or vrill be made in theoriginalplavsandspeci5cationsandenysuspensionoraSandonmentLasnotexceededone(1)yeaz. IfcLangeshavebemorifsuspeusionorahandonment neceeds oue (I) year, fWl fees sLall be peid tor a new permit (4) No work of auy manner ahall be done tLat will change the nafural flow of wata causing e diaiuage pmblem. (5) Contactorshall notifyfLeBuildinglnspecWrtweuty-four(24)hoursinadvanceforallinspecROVSandsLallrcceivewrittenappmvaloninspectioacardbefine proceeding with successive pLases of thejob. - (6) The issuance of a peimit or the approval of dnwings and speci5cations s6a11 not be construed to be a permie for, nor au approval o( avy violaEOn of the provisions of the building codes or any other ordinance, Iaw, rvle or ngulatioa . Chief Building Inspector