COMcheck Software Version 4.0.8.2
Mechanical Compliance Certificate
Project Information
Energy Code:
Project Title:
Location:
Climate Zone:
Project Type:
Construction Site:
3600 Youngfield St.
Wheat Ridge, CO
2015 IECC
HOMEGOODS
Wheat Ridge, Colorado
5b
New Construction
Owner/Agent:
T.J. Maxx
770 Cochituate Road
Framingham, MA
Designer/Contractor:
Robert D Anderson P.E.
Dallas, TX
Additional Efficiency Package(s)
Reduced interior lighting power. Requirements are implicitly enforced within interior lighting allowance calculations.
Mechanical Systems List
Quantity System Type & Description
1 HVAC System 1 (Single Zone):
Heating: 1 each - Central Furnace, Gas, Capacity = 180 kBtu/h
Proposed Efficiency = 80.00% Et, Required Efficiency = 80.00% Et
Cooling: 1 each - Single Package DX Unit, Capacity = 102 kBtu/h, Air -Cooled Condenser, Unknown Economizer
Proposed Efficiency = 12.20 EER, Required Efficiency: 11.00 EER + 12.6 IEER
Fan System: None
1 HVAC System 6 (Single Zone):
Heating: 1 each - Central Furnace, Gas, Capacity = 150 kBtu/h
Proposed Efficiency = 80.00% Et, Required Efficiency = 80.00% Et
Cooling: 1 each - Single Package DX Unit, Capacity = 60 kBtu/h, Air -Cooled Condenser, Unknown Economizer
Proposed Efficiency = 16.00 SEER, Required Efficiency: 14.00 SEER
Fan System: None
4 HVAC System 2,3,4,5 (Single Zone):
Heating: 1 each - Central Furnace, Gas, Capacity = 240 kBtu/h
Proposed Efficiency = 80.00% Et, Required Efficiency = 80.00% Et
Cooling: 1 each - Single Package DX Unit, Capacity = 150 kBtu/h, Air -Cooled Condenser, Unknown Economizer
Proposed Efficiency = 12.00 EER, Required Efficiency: 10.80 EER + 12.2 IEER
Fan System: None
1 HVAC System 7 (Single Zone):
Heating: 1 each - Central Furnace, Gas, Capacity = 180 kBtu/h
Proposed Efficiency = 80.00% Et, Required Efficiency = 80.00% Et
Cooling: 1 each - Single Package DX Unit, Capacity = 90 kBtu/h, Air -Cooled Condenser, Unknown Economizer
Proposed Efficiency = 12.00 EER, Required Efficiency: 11.00 EER + 12.6 IEER
Fan System: None
1 Water Heater 1:
Electric Storage Water Heater, Capacity: 20 gallons
No minimum efficiency requirement applies
O�ty os
Eit r
Project Title: HOMEGOODS Report?
Data filename: C:\Program Files (x86)\AutoCAD 2002\DWG\ROGUE\_HG WHEAT RIDGE, CO\HG Wheat Ridge ,C, Pa
2015 IECC.cck
_..ement
rhe proposed mechanical design represented in this document is consistent with the building plans,
other calculations submitted with this permit application. The proposed mechanical systems have been
j to meet the 2015 IECC requirements in COMcheck Version 4.0.8.2 and to comply with any applicable mandatory
aments listed in the Inspection Checklist.
Mark Swanson -Project Manager Ma r�z E Swa vusov�, 05/16/18
ame - Title Signature Date
Project Title: HOMEGOODS Rer
Data filename: C:\Program Files (x86)\AutoCAD 2002\DWG\ROGUE\_HG WHEAT RIDGE, CO\HG Wheat Ridge ,C,
2015 IECC.cck
High Impact (Tier 1) 1 2 I Medium Impact (Tier 2) 1 3 1 Low Impact (Tier 3)
Project Title: HOMEGOODS Report date:
Data filename: C:\Program Files (x86)\AutoCAD 2002\DWG\ROGUE\_HG WHEAT RIDGE, CO\HG Wheat Ridge , v,. Oan
2015 1ECC.cck k -is
Section
#
Footing / Foundation Inspection
Complies?
Comments/Assumptions
& Req.ID
I
C403.2.4.
Snow/ice melting system sensors for
❑Complies
5,
future connection to controls. Freeze
❑Does Not
C403.2.4.
protection systems have automatic
❑Not Observable
6
controls installed.
Not Applicable
❑ PP
[FO9]3
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 1 Medium Impact (Tier 2) 3 1 Low Impact (Tier 3) t
Project Title: HOMEGOODS ReporN
Data filename: C:\Program Files (x86)\AutoCAD 2002\DWG\ROGUE\_HG WHEAT RIDGE, CO\HG Wheat Ridge ,C, Pa
2015 IECC.cck
Section
#
Plumbing Rough -In Inspection
Complies?
Comments/Assumptions
& Req.117
C404.5,
Heated water supply piping conforms
❑Complies
C404.5.1,
to pipe length and volume
❑Does Not
C404.5.2
requirements. Refer to section details.
FJ Observable
[PL6]3
❑Not Applicable
C404.5,
Heated water supply piping conforms
❑Complies
C404.5.1,
to pipe length and volume
❑Does Not
C404.5.2
requirements. Refer to section details.
FI Observable
[PL6]3
❑Not Applicable
C404.5,
Heated water supply piping conforms
❑Complies
C404.5.1,
to pipe length and volume
❑Does Not
C404.5.2
requirements. Refer to section details.
❑ Not Observable
[PL6]3
❑Not Applicable
C404.5,
Heated water supply piping conforms
❑Complies
C404.5.1,
to pipe length and volume
❑Does Not
C404.5.2
requirements. Refer to section details.
❑Not Observable
[PL6]3
❑Not Applicable
C404.5,
Heated water supply piping conforms
❑Complies
C404.5.1,
to pipe length and volume
❑Does Not
C404.5.2
requirements. Refer to section details.
FI Observable
[PL6]3
❑Not Applicable
C404.6.3
Pumps that circulate water between a
❑Complies
[PL7]3
heater and storage tank have controls
❑Does Not
that limit operation from startup to
❑Not Observable
<= 5 minutes after end of heating
❑Not Applicable
cycle.
C404.6.3
Pumps that circulate water between a
❑Complies
[PL7]3
heater and storage tank have controls
❑Does Not
that limit operation from startup to
❑Not Observable
<= 5 minutes after end of heating
❑Not Applicable
cycle.
C404.6.3
Pumps that circulate water between a
❑Complies
[PL7]3
heater and storage tank have controls
❑Does Not
that limit operation from startup to
❑Not Observable
<= 5 minutes after end of heating
❑Not Applicable
cycle.
C404.6.3
Pumps that circulate water between a
❑Complies
[PL7]3
heater and storage tank have controls
❑Does Not
that limit operation from startup to
❑Not Observable
<= 5 minutes after end of heating
❑Not Applicable
cycle.
C404.6.3
Pumps that circulate water between a
❑Complies
[PL7]3
heater and storage tank have controls
❑Does Not
that limit operation from startup to
❑Not Observable
<= 5 minutes after end of heating
❑Not Applicable _
cycle.
c; y �1
�1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3) ,, ti'r� �,t`-A
Project Title: HOMEGOODS Report date: 05/16/18
Data filename: C:\Program Files (x86)\AutoCAD 2002\DWG\ROGUE\_HG WHEAT RIDGE, CO\HG Wheat Ridge ,C, Page 8 of 19
2015 1ECC.cck
Section
#
Plumbing Rough -In Inspection
Complies?
Comments/Assumptions
& Req.ID
__
C404.7
Water distribution system that pumps
❑Complies
[PL8]3
water from a heated -water supply
❑Does Not
pipe back to the heated -water source
❑Not Observable
through a cold -water supply pipe is a
❑Not Applicable
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold -water piping to
104°F.
C404.7
Water distribution system that pumps
❑Complies
[PL8]3
water from a heated -water supply
❑Does Not
pipe back to the heated -water source
❑Not Observable
through a cold -water supply pipe is a
❑Not Applicable
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold -water piping to
104°F.
C404.7
Water distribution system that pumps
❑Complies
[PL8]3
water from a heated -water supply
❑Does Not
pipe back to the heated -water source
❑Not Observable
through a cold -water supply pipe is a
❑Not Applicable
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold -water piping to
104°F.
C404.7
Water distribution system that pumps
❑Complies
[PL8]3
water from a heated -water supply
❑Does Not
pipe back to the heated -water source
❑Not Observable
through a cold -water supply pipe is a
❑Not Applicable
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold -water piping to
104°F.
C404.7
Water distribution system that pumps
❑Complies
[PL8]3
water from a heated -water supply
❑Does Not
pipe back to the heated -water source
❑Not Observable
through a cold -water supply pipe is a
❑Not Applicable
demand recirculation water system.
—--Pumps
within this system have
- —
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold -water piping to
104°F.
Additional Comments/Assumptions:
C:M o{
h Impact (Tier 1):J - Medium Impact (Tier 2) 3 1 Low Impact (Tier 3) 1t CZe
Project Title: HOMEGOODS Report date: 05/16/18,1
Data filename: C:\Program Files (x86)\AutoCAD 2002\DWG\ROGUE\_HG WHEAT RIDGE, CO\HG Wheat Ridge ,C, Page 9 of 19
2015 1ECC.cck -
High Impact (Tier 1) 2 1 Medium Impact (Tier 2) 3 Low Impact (Tier.
Project Title: HOMEGOODS f1eport date: 05/1618
Data filename: C:\Program Files (x86)\AutoCAD 2002\DWG\ROGUE\_HG WHEAT RIDGE, CO\HG Wheat Ridge ,G1 Page10 of 19
2015 IECC.cck
City of
High Impact (Tier 1) _T2 Medium Impact (Tier 2) 3 Low Impact (Tier 3) hO,t Ridge
Project Title: HOMEGOODS Report date`: 05/16/8
Data filename: C:\Program Files (x86)\AutoCAD 2002\DWG\ROGUE\_HG WHEAT RIDGE, CO\HG Wheat Ridge ,C, Pah�r f 19
2015 IECC.cck
v
_Section
#
Mechanical Rough -In Inspection
Complies?
Comments/Assumptions
& ReciAD
C402.2.6
Thermally ineffective panel surfaces of
❑Complies
[ME41]3
sensible heating panels have
❑Does Not
insulation >= R-3.5.
❑Not Observable
❑Not Applicable
C403.2.12
HVAC fan systems at design
❑Complies
See the Mechanical Systems list for values.
.1
conditions do not exceed allowable
❑Does Not
[ME65]3
fan system motor nameplate hp or fan
❑Not Observable
system bhp.
❑Not Applicable
C403.2.12
HVAC fan systems at design
❑Complies
See the Mechanical Systems list for values.
.1
conditions do not exceed allowable
❑Does Not
[ME65]3
fan system motor nameplate hp or fan
❑Not Observable
system bhp.
❑Not Applicable
_
C403.2.12
HVAC fan systems at design
❑Complies
See the Mechanical Systems list for values.
.1
conditions do not exceed allowable
❑Does Not
[ME65]3
fan system motor nameplate hp or fan
❑Not Observable
system bhp.
❑Not Applicable
C403.2.12
HVAC fan systems at design
❑Complies
See the Mechanical Systems list for values.
.1
conditions do not exceed allowable
❑Does Not
[ME65]3
fan system motor nameplate hp or fan
❑Not Observable
system bhp.
❑Not Applicable
C403.2.12
Fans have efficiency grade (FEG) >_
❑Complies
.3
67. The total efficiency of the fan at
❑Does Not
[ME117]2
the design point of operation <= 15%
❑Not Observable
of maximum total efficiency of the
❑Not Applicable
fan.
C403.2.12
Fans have efficiency grade (FEG) >_
❑Complies
.3
67. The total efficiency of the fan at
❑Does Not
[ME117]2
the design point of operation <= 15%
❑Not Observable
of maximum total efficiency of the
❑Not Applicable
fan.
C403.2.12
Fans have efficiency grade (FEG) >_
❑Complies
.3
67. The total efficiency of the fan at
❑Does Not
[ME117]2
the design point of operation <= 15%
❑Not Observable
of maximum total efficiency of the
❑Not Applicable
fan.
C403.2.12
Fans have efficiency grade (FEG) >_
[]Complies
.3
67. The total efficiency of the fan at
❑Does Not
[ME117]2
the design point of operation <= 15%
❑Not Observable
of maximum total efficiency of the
❑Not Applicable
fan.
C403.2.13 Unenclosed spaces that are heated
❑Complies
[ME71]2
use only radiant heat.
❑Does Not
❑Not Observable
❑Not Applicable
C403.2.3
HVAC equipment efficiency verified.
❑Complies
See the Mechanical Systems list for values.
[ME55]2
❑Does Not
❑Not Observable
❑Not Applicable
_
C403.2.6.
Demand control ventilation provided
❑Complies
1
for spaces >500 ft2 and >25
❑Does Not
[ME59]1
people/1000 ft2 occupant density and
❑Not Observable
served by systems with air side
❑Not Applicable
economizer, auto modulating outside
air damper control, or design airflow
>3,000 cfm.
City of
High Impact (Tier 1) _T2 Medium Impact (Tier 2) 3 Low Impact (Tier 3) hO,t Ridge
Project Title: HOMEGOODS Report date`: 05/16/8
Data filename: C:\Program Files (x86)\AutoCAD 2002\DWG\ROGUE\_HG WHEAT RIDGE, CO\HG Wheat Ridge ,C, Pah�r f 19
2015 IECC.cck
Section
#Mechanical
Rough -In Inspection
Complies?
Comments/Assumptions
& Req. ID
__
C403.2.6.
Enclosed parking garage ventilation
❑Complies
2
has automatic contaminant detection
❑Does Not
[ME115]3
and capacity to stage or modulate
❑Not Observable
fans to 50% or less of design capacity.
❑Not Applicable
C403.2.7
Exhaust air energy recovery on
❑Complies
[ME57]1
systems meeting Table C403.2.7(1)
❑Does Not
and C403.2.7(2).
❑Not Observable
❑Not Applicable
_
C403.2.8
Kitchen exhaust systems comply with
❑Complies
[ME116]3
replacement air and conditioned
❑Does Not
supply air limitations, and satisfy hood
❑Not Observable
rating requirements and maximum
❑Not Applicable
exhaust rate criteria.
C403.2.9
HVAC ducts and plenums insulated.
❑Complies
[ME60]2
Where ducts or plenums are installed
❑Does Not
in or under a slab, verification may
❑Not Observable
need to occur during Foundation
❑Not Applicable
Inspection.
—
C403.2.9
Ducts and plenums sealed based on
❑Complies
[ME10]2
static pressure and location.
❑Does Not
❑Not Observable
❑Not Applicable
C403.2.9.
Ductwork operating >3 in. water
❑Complies
1.3
column requires air leakage testing.
❑Does Not
[ME11]3
❑Not Observable
❑Not Applicable
C403.2.9.
Ductwork operating >3 in. water
❑Complies
1.3
column requires air leakage testing.
❑Does Not
[ME11]3
❑Not Observable
❑Not Applicable
C403.2.9.
Ductwork operating >3 in. water
❑Complies
1.3
column requires air leakage testing.
❑Does Not
[ME11]3
❑Not Observable
❑Not Applicable
C403.2.9.
Ductwork operating >3 in. water
❑Complies
1.3
column requires air leakage testing.
❑Does Not
[ME11]3
❑Not Observable
❑Not Applicable
C403.4.4.
Multiple zone VAV systems with DDC
❑Complies
See the Mechanical Systems list for values.
6
of individual zone boxes have static
❑Does Not
[ME110]3
pressure setpoint reset controls.
❑Not Observable
❑Not Applicable
C403.4.4.
Multiple zone VAV systems with DDC
❑Complies
See the Mechanical Systems list for values.
6
of individual zone boxes have static
❑Does Not
LME11013__
pressure setpoint reset controls.
❑Not Observable
❑Not Applicable
C403.4.4.
Multiple zone VAV systems with DDC
❑Complies
See the Mechanical Systems list for values.
6
of individual zone boxes have static
❑Does Not
[ME110]3
pressure setpoint reset controls.
❑Not Observable
❑Not Applicable
_
C403.4.4.
Multiple zone VAV systems with DDC
❑Complies
See the Mechanical Systems list for values.
6
of individual zone boxes have static
❑Does Not
[ME110]3
pressure setpoint reset controls.
❑Not Observable
❑Not Applicable
11 High Impact (Tier 1) 2 1 Medium Impact (Tier 2) 3 1 Low Impact (Tier 3A I
Project Title: HOMEGOODS Report date: 05/16/18
Data filename: C:\Program Files (x86)\AutoCAD 2002\DWG\ROGUE\_HG WHEAT RIDGE, CO\HG Wheat Ridge ,O Page 12 of 19
2015 IECC.cck
Section
#
& Req.ID
Mechanical Rough -In Inspection
Complies? Comments/Assumptions
_
C408.2.2.
Air outlets and zone terminal devices
❑Complies
1
have means for air balancing.
❑Does Not
[ME53]3
❑Not Observable
❑Not Applicable _
C403.5,
Refrigerated display cases, walk-in
[]Complies
C403.5.1,
coolers or walk-in freezers served by
❑Does Not
C403.5.2
remote compressors and remote
❑Not Observable
[ME123]3
condensers not located in a
❑Not Applicable
condensing unit, have fan -powered
condensers that comply with Sections
C403.5.1 and refrigeration compressor
systems that comply with C403.5.2..
Additional Comments/Assumptions:
High Impact (Tier 1)
Medium Impact (Tier 2) 1 3 1 Low Impact (Tier 3)
Ig
-
Project Title: HOMEGOODS Reportte: 05/ 18
Data filename: C:\Program Files (x86)\AutoCAD 2002\DWG\ROGUE\_HG WHEAT RIDGE, CO\HG Wheat Ridge,C, P 3 of 19
2015 IECC.cck
section
#
Rough -In Electrical InspectionComplies?
Comments/Assumptions
& Req.ID
-
C405.2.1
___—L
Lighting controls installed to uniformly
❑Complies
[EL15]1
reduce the lighting load by at least
❑Does Not
50%.
❑Not Observable
❑Not Applicable
C405.2.1
Occupancy sensors installed in
❑Complies
[EL18]1
required spaces.
❑Does Not
❑Not Observable
❑Not Applicable
C405.2.1,
Independent lighting controls installed
❑Complies
C405.2.2.
per approved lighting plans and all
❑Does Not
3
manual controls readily accessible and
❑Not Observable
[EL23]2
visible to occupants.
❑Not Applicable
C405.2.2.
Automatic controls to shut off all
❑Complies
1
building lighting installed in all
❑Does Not
[EL22]2
buildings.
❑Not Observable
❑Not Applicable
C405.2.3
Daylight zones provided with
❑Complies
[EL16]2
individual controls that control the
❑Does Not
lights independent of general area
❑Not Observable
lighting.
❑Not Applicable
C405.2.3,
Primary sidelighted areas are
❑Complies
C405.2.3.
equipped with required lighting
❑Does Not
1,
controls.
❑Not Observable
C405.2.3.
❑ Not Applicable
2
[EL20]1
C405.2.3,
Enclosed spaces with daylight area
❑Complies
C405.2.3.
under skylights and rooftop monitors
❑Does Not
1,
are equipped with required lighting
❑Not Observable
C405.2.3.
controls.
❑ Not Applicable
3
[EL21]1
C405.2.4
Separate lighting control devices for
❑Complies
[EL4]1
specific uses installed per approved
❑Does Not
lighting plans.
❑Not Observable
❑Not Applicable
C405.2.4
Additional interior lighting power
❑Complies
[EL8]1
allowed for special functions per the
❑Does Not
approved lighting plans and is
❑Not Observable
automatically controlled and
[]Not Applicable
separated from general lighting.
_
C405.2.5
Automatic lighting controls for exterior❑Complies
[EL25]nu°
lighting installed. Controls will be
❑Does Not
daylight controlled, set based on
❑Not Observable
business operation time -of -day, or
❑Not Applicable
reduce connected lighting > 36%
C405.3
Exit signs do not exceed 5 watts per
❑Complies
[EL6I1
face.
❑Does Not
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
11 High Impact (Tier 1) 2TMedium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title: HOMEGOODS Report dat6:--Q5/16/18
Data filename: C:\Program Files (x86)\AutoCAD 2002\DWG\ROGUE\_HG WHEAT RIDGE, CO\HG Wheat Ridge ,C, Page 14 of 19
2015 IECC.cck
Section
-T
#
Final Inspection
Complies?
Comments/Assumptions
& Re_q.ID_
C303.3,
Furnished O&M instructions for
❑Complies
C408.2.5.
systems and equipment to the
❑Does Not
2
building owner or designated
❑ Not Observable
[FI17]3
representative.
❑Not Applicable
C303.3,
Furnished O&M manuals for HVAC
❑Complies
C408.2.5.
systems within 90 days of system
❑Does Not
3
[F18]3
acceptance.
❑ Not Observable
❑Not Applicable
C403.2.2
HVAC systems and equipment
❑Complies
[F127]3
capacity does not exceed calculated
❑Does Not
loads.
❑Not Observable
❑Not Applicable _
C403.2.4.
Heating and cooling to each zone is
❑Complies
1
controlled by a thermostat control.
❑Does Not
[F147]3
Minimum one humidity control device
❑Not Observable
per installed
humidification/dehumidification
❑Not Applicable
system.
C403.2.4.
Heating and cooling to each zone is
❑Complies
1
controlled by a thermostat control.
❑Does Not
[FI47]3
Minimum one humidity control device
❑Not Observable
per installed
humidification/dehumidification
❑Not Applicable
system.
C403.2.4.
_
Heating and cooling to each zone is
❑Complies
1
controlled by a thermostat control.
❑Does Not
[F147]3
Minimum one humidity control device
❑Not Observable
per installed
humidification/dehumidification
❑Not Applicable
system.
C403.2.4.
Heating and cooling to each zone is
--
❑Complies
1
controlled by a thermostat control.
❑Does Not
[FI47]3
Minimum one humidity control device
❑Not Observable
per installed
humidification/dehumidification
❑Not Applicable
system.
C403.2.4.
Thermostatic controls have a 5 °F
- ---- ----
❑Complies
1.2
deadband.
❑Does Not
[F138]3
❑Not Observable
❑Not Applicable
C403.2.4.
Temperature controls have setpoint
❑Complies
13
overlap restrictions.
❑Does Not
[F120]3
❑Not Observable
❑Not Applicable
C403.2.4.
Each zone equipped with setback
❑Complies
2
controls using automatic time clock or
❑Does Not
[F139]3--
programmable control system.
❑Not Observable
❑Not Applicable
C403.2.4.
Automatic Controls: Setback to 55°F
❑Complies v
2.1,
(heat) and 85°F (cool); 7 -day clock, 2-
❑Does Not
C403.2.4.
hour occupant override, 10 -hour
❑Not Observable
2.2
[F140]3
backup
❑Not Applicable
High Impact (Tier 1) 1 2 1 Medium Impact (Tier 2)
Low Impact (Tier 3)
Project Title: HOMEGOODS Reporkogt?s` 05/1 8
Data filename: C:\Program Files (x86)\AutoCAD 2002\DWG\ROGUE\_HG WHEAT RIDGE, CO\HG Wheat Ridge ,C, Pag of 19
2015 IECC.cck
Project Title: HOMEGOODS Report date: 05/16118
Data filename: C:\Program Files (x86)\AutoCAD 2002\DWG\ROGUE\_HG WHEAT RIDGE, CO\HG Wheat Ridge ,Ci Page 19 of 19
2015 IECC.cck
COMcheck Software Version 4.0.8.2
Inspection Checklist
Energy Code: 2015 IECC
Requirements: 0.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
#
Plan Review
Complies?
Comments/Assumptions
& Re .ID
— —— —
C103.2
Plans, specifications, and/or
❑Complies
[PR2]1
calculations provide all information
❑Does Not
with which compliance can be
❑Not Observable
determined for the mechanical
❑Not Applicable
systems and equipment and
document where exceptions to the
standard are claimed. Load
calculations per acceptable
engineering standards and
handbooks.
_
C103.2
Plans, specifications, and/or
❑Complies
[PR3)1
calculations provide all information
❑Does Not
with which compliance can be
❑Not Observable
determined for the service water
❑Not Applicable
heating systems and equipment and
document where exceptions to the
standard are claimed. Hot water
system sized per manufacturer's
sizing guide.
C103.2
Plans, specifications, and/or
[]Complies
[PR4)1
calculations provide all information
❑Does Not
with which compliance can be
❑Not Observable
determined for the interior lighting
❑Not Applicable
and electrical systems and equipment
and document where exceptions to
the standard are claimed. Information
provided should include interior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
control devices.—
C103.2
Plans, specifications, and/or
❑Complies
[PR8)1
calculations provide all information
❑Does Not
with which compliance can be
❑Not Observable
determined for the exterior lighting
❑Not Applicable
pp
and electrical systems and equipment
and document where exceptions to
the standard are claimed. Information
provided should include exterior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
control devices.
C406
Plans, specifications, and/or
❑Complies
[PR9]1
calculations provide all information
❑Does Not
with which compliance can be
❑Not Observable
determined for the additional energy
❑Not Applicable
efficiency package options.
Additional Comments/Assumptions:
c �
_
N a
High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3) t' '" o
0
Project Title: HOMEGOODS Report d teb05/S
Data filename: C:\Program Files (x86)\AutoCAD 2002\DWG\ROGUE\_HG WHEAT RIDGE, CO\HG Wheat Ridge ,C, Page 5 0T
2015 IECC.cck
The Ciry of
7500 WEST 29TH AVENUE G
WHEAT RIDGE, CO 80215-6713 (303) 2345900
Wheat
City Admin. Fax # 2345924 Police Dept Fax a 235-2949 `;Ridge
October 8, 1997
Mr. Rudy Blea
State of Colorado
Departrnent of Transpor[ation
Region 6 - Permit Section
5640 East Atlantic Place
Denver, Colorado 80224
Re: Chesrown's Friendly Ford, 3600 Wadsworth Blvd. - Parking Lot Drainage & Access
Concerns
Deaz Mr. Blea,
This letter is to inform CDOT of the potentia( drainage and access related problems that may
impact the Wadsworth Blvd. frontage as a result of the unauthorized asphalt paving of a new
parking lot azea at the above reference address.
First, a temporary parking lot, measuring approxiinately 200 L.F. (WadswoRh frontage) by 350
L.F., was designed for the area direcUy south of the existing service facility. A drainage report
and plan for the pazking area was prepared by Martin Design, Inc. and approved by the City of
Wheat Ridge on Mazch 25, 1997. Briefly, the majority of the proposed grading for this design
consisted of slopes directed to the west, away from Wadsworth Blvd. A small azea, located at the
northeast corner of the site, was to remain essentially unchanged, maintaining the tustoric
pattern of drainage towazds Wadsworth Blvd. Finally, uid most importantly the surface of the
entire temporary parking area was to consist of a Class 6 road base, placed 6-inches in depth.
On September 29, 1997 this entire azea was paved with an asphalt surface, at the direction of
Chesrown Ford representatives. A drainage report and plan for this surface type was never
submitted to the City for review and approval. In addition, the City was not notified prior to the
commencement of this wark, and Chesrown Ford representatives did not attempt to obtain prior
authorization from the Public Works, Planning or Building Departments. Please be aware that
subsequent inspections of the parking lot suggest that a substantial azea of this pazking/sales lot
azea now appears to be sloped towazds the noRheast corner and Wadsworth Blvd.. This grading,
combined with the rainfall intensities associated with a major storm, the increased
imperviousness of the asphalt surface placed, and no detention facilities to control this flow,
create a situation that could have a significant and adverse impact on Wadsworth Blvd.
rj Recvcieo RnNta
Mr. Rudy Blea
CDOT
Page 2
Secondly, the City would like to make you aware of a potential access problem on Wadsworth
Blvd. as a result of the new parking/sales lot. As you may be awaze, there is an existing curb cut
on Wadsworth that has historically served as access only to Chesrown's service center. It now
appeazs that this curb cut is also being used to provide access to the new pazking/sales lot to the
south of the existing service center.
The City is pursuing all relevant avenues of enforcement within its authority as a result of these
and other violations that have occurred as a result of the recent consmxction activities on the site.
It would be appreciated if CDOT could investigate within its authority, the two issues presented
and provide the City with a copy of the violation(s) determined, along with any actions that will
be pursued to correct these violations.
'I'hank a ip advance for you cooperation in this matter. If you have any questions, please do
not sitate tb contact me at 235-2868.
~
i
Si er y,
~,-M.P.A.
Greg KnddsDevelopment Review Engineer
cc: Robert Middaugh, City Manager
Bob Goebel, Public Works Director
Alan White, Planning & Development Director
Dave Kotecki, Sr. Project Engineer
John Eckert, Chief Building Inspector
Meredith Reckert, Sr: Planner
Susan Eliis, Code Enforcement Officer 11
COMMUNITY
7500 wES7 29tn AvENUE DEPARTB ILD N~ NSPECTION D V SI NPMENT pERM1T N0.
237-8944 ExT. 255 P.O. BOX 638 CITY OF WHEAT RIDGE, COLO.
THIS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDIN6 INSPELTOR AND RECEIPTED BEL7W.
t(~,~~~ APPLICATION FOR MISCELLANEOUS( prIERM `
JOB ADDRESS 4U00 "^'~"7"o~'~H OWNER ` ~
CONTRACTOR LSI~ i C~~1~~ I ADDRESS ~"ICIJ ~ ~~~'!b)~f}L Sj• _
ADDRESS.} ~~"IQ ,._.~(-Zi_..RIv1l1 St= - PHONE _ ' ZIP CODE
CITY L~ "~~'O^) y-, ZIP CODE %ONTRAGT PRICE $
PHONE LICENSE NO. /y99O ff
TYPE Ground❑ Wall❑ Proisotinp❑ Otha SaDFaee
1
.
2. MATERIAL Tofol Squon Fset
SIGNS
Permit No
s EIKI
ILLUMINATION Y
❑ N
❑ 7
3
.
.
ea
o
yp
.
4, SET BACK FROM PROPERTY LINE N_ 5_ E_ W Zom_ ADproved, 2one Inapsetor
(Spetify whieh is fronf ) ❑ ❑ ❑ ❑ DiwpDrwed
1. TYPE SolidO More TMn BO% Opan❑ Lost Thon BO% Open
MATERIAL HeipM
FENCES
3. SET BACK FROM PROPERTY LINE N_ S_ E_ W Zone_ ApprwW,Zone Inspxtor
(Spacify whieh is front) ❑ ❑ ❑ ❑ Diaapprovsd
- cvNo~' . ;h 3tat~ W -n} } n ST.
i
.
~ omj~ TO 300 K)~' ~
2
OTHER
'
3
Yl &IDET111 1-0 SiiL
2
a ~.Le ina-ct.c0/ ~~/.Ytc~u.a.c 1517/,ccti.ac(n.c (W- 9.'00 AM
DRAW SKETCH OR SHOW BELOW, THE FENCE,SIGN,OR OTHER STRUCTURE, GIVih'u DISTANCES FROM PROPERTY LINES.
(SETBACKS OR PROJECTpNSINCLUOED)
~
SPECIFY NORTH
STREET NAME
SHOW DISTANCES FROM THE M41N BUILDING TOADJOINING NOUSES, STREETS, AND PROPERTV LINES; ON IRREGULAR lATS, SNOW LEAST
DISTANCE TO PROPERTY LINES, NOT MAXIMUM OR AVERAGE D15T4NCE.
APPLICATION FOR PLUMBWG; ELECTRICAL; MECHANICAL PERMIT
THIS APPLICATION WILL BECOME A PERMIT TO PERFORM THE INDICATED WORN ONLY UPON WILIDATION BY TME BUILDINC INSPECTION DIVISION.
PERMIT WILL EXPIRE 60 DAYS FROM DATE OF ISSUANCE !F WORK IS NOT STARTED WITHW THAT TIIAE.
ELECTRICAL PERMIT
STATE LICENSE N0.
PLUM8ING PERMIT
STATE UCENSE N0.
MECHANICAL PERMIT
ALUMINUAI WIRE UNDER SIZE 8 Il.LE6AL
Np.
TEMPORARY METER
FLOOR
WATER CLASET
WASH BOWL
BSM
IST
2ND
3RD
4TH
N0.
Fl1EL:CNrJSOro Gof 0II R'opone E Solor
FORCED AIR - BTU
HOT WATER - BTU
NEW SERVICE AMPS
BATH TU8
STEAM - BTU
CHANGE SERVICE-AMPS
SHOWER
Alq CONDITIONING-BTU
LIGHTING
SINK
OTHER
HEATING
GARBA6E DISP
REFRIGERATION SYS?EM
POWER SUB-CIRCUITS
UTILITY(RANGE,DISPOSER,ETC.)
FIXTURES
WdTER HEATER
AUTO. WASHER
DISH WASMER
Rafri eront Gap
Pa+nds CMr s
AUTOMATIC SPRINKLER SYSTEM
WIRING MOTORS B CONTROLS
FIDOR DRAIN
ELEVATOR
SIGNS
URINAL
?RANSFORMERS 6 RECTFIERS
SEWERS
ADDITION TO OLD WORK
OTHER
MOTORS OVER I HP
TOTAL FI7(TURES
REMARKS
Iica-
t fhia o
th
l
d
PERMIT FEE
pp
a
qe
e
I hereby acknow
tion ia correct and understond that I
USE TAX
eannof afort fhis Drojecf until ihia aOVli-
th
~C~
$
wtion is approved. I shall oomplY wi
TOTAL FEE
r2
the laws oi the State of Colorado ond to
the Zoninp Requlations ond 8uildinq
APPROVED
.
~
Gode of the City oi Wneat Ridpe. Any
iololi of the obove terma wili cauae
DISAPPROVED
CHIEF BUILDINGA
SPECTOR,City of Wheot Ridqe
v
imm ia ravowtion ot his permil.
d
Dote Issued
VALID UNLE55 RECEIMED
CALL 237-8944 EXT. 255
24 HOURS IN ADVANCE
FORINSPECTIONS
C'