HomeMy WebLinkAbout3615 Teller StreetWCONSULTING,A Scott E. Wyssling, PE, PP, CME February 12, 2021 Dallas Bradshaw, Senior Account Manager Encor Solar, LLC 3401 N. Thanksgiving Way #450 Lehi, LIT 84043 Wyssling Consulting 76 North Meadowbrook Drive Alpine, UT 84004 office (201) 874-3483 swyssling@wysslingconsulting.com Re: Engineering Services Mallory Residence 3615 Teller Street, Wheatridge, CO 5.000 kW System Dear Mr. Bradshaw: Pursuant to your request, we have reviewed the following information regarding solar panel installation on the roof of the above referenced home: 1. Site Visit/Verification Form prepared by a Enc6r Solar representative identifying specific site information including size and spacing of rafters for the existing roof structure. 2. Design drawings of the proposed system including a site plan, roof plan and connection details for the solar panels. This information was prepared by Encor Solar and will be utilized for approval and construction of the proposed system. 3. Photographs of the interior and exterior of the roof system identifying existing structural members and their conditions. Based on the above information we have evaluated the structural capacity of the existing roof system to support the additional loads imposed by the solar panels and have the following comments related to our review and evaluation: Description of Structure: The existing structure is a typical wood framing detached garage construction with the roof system consisting of 2 x 6 dimensional lumber at 24" on center. The attic space is unfinished and photos indicate that there was free access to visually inspect the size and condition of the roof rafters. All wood material utilized for the roof system is assumed to be Southern Pine #2 or better with standard construction components. The existing roofing material consists of composite asphalt shingles. Photos of the dwelling also indicate that there is a permanent foundation. A. Loading Criteria Used • 110 MPH wind loading based on ASCE 7-16 Exposure Category "B" ata slope of 20 degrees • 7 PSF = Dead Load roofing/framing Live Load = 20 PSF • 3 PSF = Dead Load solar panels/mountina hardware Ground Snow Load = 40 PSF Total Dead Load =10 PSF The above values are within acceptable limits of recognized industry standards for similar structures in accordance with the 2018 International Building Code. Analysis performed of the existing roof structure utilizing the above loading criteria indicates that the existing rafters will support the additional panel loading without damage, if installed correctly. Page 2 of 2 B. Solar Panel Anchorage 1. The solar panels shall be mounted in accordance with the most recent "Unirac Installation Manuaf', which can be found on the UniRac website (http://unirac.com�). If during solar panel installation, the roof framing members appear unstable or deflect non -uniformly, our office should be notified before proceeding with the installation. 2. Maximum allowable pullout per lag screw is 235 lbs/inch of penetration as identified in the National Design Standards (NDS) of timber construction specifications for Doug -Fir (North Lumber) assumed. Based on our evaluation, the pullout value, utilizing a penetration depth of 2 %", is less than what is allowable per connection and therefore is adequate. Based on the variable factors for the existing roof framing and installation tolerances, using a thread depth of 2 '/" with a minimum size of 5/16" lag screw per attachment point for panel anchor mounts should be adequate with a sufficient factor of safety. 3. Considering the roof slopes, the size, spacing, condition of roof, the panel supports shall be placed no greater than 72" o/c. 4. Panel supports connections shall be staggered to distribute load to adjacent rafters. Based on the above evaluation, it is the opinion of this office that with appropriate panel anchors being utilized the roof system will adequately support the additional loading imposed by the solar panels. This evaluation is in conformance with the 2018 International Building Code, current industry and standards, and based on information supplied to us at the time of this report. Should you have any questions regarding the above or if you require further information do not hesitate to contact me. V truly yours, Scott E. lWyssli , PE Colorado License N 7 W CONSULTING 0 0 J > LON 0) 0 Or4N CO 0 KD Z N LU co Approval Notes: 1) P/V array system to have grounding system installed per Part III of Article 250 per 2017 NEC Article 690.47(A). 2) If LIFER ground in not available provide or verify supplemental ground rods per 2017 NEC Article 250.53(A)(3). 3) Natural Gas & Cold Water bonding per 2017 NEC Article 250.104(6) N W J 0 Q a M w M`�' LnLna~c rr 0 N Ln J � v, Co Z o > o�000� Y cV "t)'o c! M c/ +�+ VCV G7 a fC Q'I N z °J v� ,ri ^ o to N O w o �N w 08p z� LL a) a�OH ot"a a, z U N J 3 L w O Ln X M J H C. a V 2 n U l0 r_1 r_1 v v DATE: February 12, 2021 PAGE: SHEET NAME: PV01 COVER PAGE DRAWN BY: SoloCAD Vo 644 City of IZWh6at�e MUNfTY UEVELUI'MENT APPROVED Reviewed for Code Compliance 1. INSTALLATION OF SOLAR PHOTOVOLTAIC SYSTEM SHALL BE IN ACCORDANCE WITH NEC ARTICLE 690, AND ALL OTHER APPLICABLE NEC CODES WHERE NOTED OR EXISTING. 2. PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110. 3. ALL WIRES, INCLUDING THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM PHYSICAL DAMAGE IN ACCORDANCE WITH NEC ARTICLE 250 4. THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE; THIS SYSTEM IS UTILITY INTERACTIVE PER UL 1741 AND DOES NOT INCLUDE STORAGE BATTERIES OR OTHER ALTERNATIVE STORAGE SOURCES. 5. ALL DC WIRES SHALL BE SIZED ACCORDING TO [NEC 690.81 6. DC CONDUCTORS SHALL BE WITHIN PROTECTED RACEWAYS IN ACCORDANCE WITH [NEC 690.31] 7. ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL JURISDICTIONAL BUILDING CODE. PV01 COVER PAGE PV02 PROPERTY PLAN PV03 ROOF PLAN PV04 ROOF ATTACHMENTS + BOM PV05 MOUNTING DETAIL PV06 ELECTRICAL DIAGRAM PV07 LABELS PV08 PLACARD PV09 SITE PHOTOS DESCRIPTION OF DESIGN: INSTALLATION OF GRID -TIED, UTILITY INTERACTIVE PHOTOVOLTAIC SYSTEM EQUIPMENT: MAX CONTINUOUS AC SYSTEM SIZE: 5 kW AC DC SYSTEM SIZE: 5.12 kW DC (16) Hanwha Q. Cells Q.Peak DUO BLK-G5 320 PV MODULES (1) SolarEdge SE5000H-US (240V) INVERTER RACKING: Unirac - 48" O.C. 0 LICE 0� i 45 .., ...... S�ONAL E� APPLICABLE GOVERNING CODES: I SITE SPECIFICATIONS: 2017 NATIONAL ELECTRIC CODE [NEC] uuuur/►ivur: n -z5 2018 INTERNATIONAL BUILDING CODE [IBC] ZONING: RESIDENTIAL 2018 INTERNATIONAL RESIDENTIAL CODE [IRC] 2018 INTERNATIONAL FIRE CODE [IFC] 0 Lo U � J > N 0 L '4' N 0 8 Z N U o o Z qm 0) cv W cy 2151-111 Ln J EQUIPMENT LEGEND: 0 UTILITY METER Q a 0 Y M Fm s PI MAIN SERVICE PANEL w �n Ln Ln � ) w o L? w VISIBLE, LOCKABLE, LABELED E c) N Ln J z w N W - AC DISCONNECT Ou Lu u Ln O > Pv METER SOCKET o 0 0 ry Y cV (FOR UTILITY PV METER) "� c! M c/ a :3 INV] INVERTER M Q � Ln z cn � t NIS NO O to — O O w �, O Fc COMBINER BOX < 0 +.+ = N w 7 N Z N M� N UU � >- p °J z LU C m o29 0 LL(Ua,OH0= aJ Lc LOAD CENTER Z H U J 3 L w LU o ¢ J = �° U ® FIRE ACCESS PATHWAY (3' TYP) v)UM20 �— �r-1 v v PROPERTY LINE DATE: February 12, 2021 PAGE: SHEET NAME: PV02 PROPERTY PLAN BATT BATTERY(IES) DRAWN BY: SCALE: SoloCAD 1" = 26.22' lool 115'-11" O O O O � O O 1 I p I I O O I K m INV rAC LC I I JB I I MP1 PITCH: 20° AZIMUTH: 180° N 5Q r� 7ENCOR 0 Zo o L' O � r O J c O z -J.> cm �n O O � Y M � V O r� N O o � 2 � N -n zU o 0 O O z 4 z (� W MJJ z O n O 0 K m N w J C �. RY 0 0 EQUIPMENT LEGEND: V 0 : 3: C) UTILITY METER LU m`n Ln`na~c mo LLi o Y � MSP MAIN SERVICE PANEL �N J N m z O 2 u O > VISIBLE, LOCKABLE, LABELED 6 �-- o o p E AC DISCONNECT i Y N INV AC U N Ln a Pv METER SOCKET IC z N '-'� (FOR UTILITY PV METER) Q o O N o o INV] INVERTER 0�0.oO L/C ySs • 2 �izcnm - N T G''0 r� � Oz N o Z w v a COMBINER BOX 45 z s P. ULt �, , w'°u7x�� c 12 J MP1 u u �c LOAD CENTER ° JB �um2o -- x PITCH: 20 '��SS�oNAt AZIMUTH: 180° FIRE ACCESS PATHWAY 3' TYP DATE: February 12, 2021 ( ) PAGE: SHEET NAME: 3' TY P PV03 ROOF PLAN BATT BATTERY(IES) DRAWN BY: SoloCAD N I NV AC ENCOR LC z o L0 o � r O J LL J > Zcm O � Y M � U O r � N 000 z� N Z CUA -c O z�0S2 �of (� W 0, 1 1 Z�b v, LU J J B 11110 o i iC Y M w �Q,o V 'CO M� �0c~c = 45 CD Z o� �o� uwa0�o ���: Ss�� 'O GJ i! � � � N NAL U NLn m Q �--I _ Z W r-4 O rl- Vf O w o Q Z N M . Ln U cncnN U 0 EQUIPMENT INFORMATION: ROOF INFO: PHOTOVOLTAIC ARRAY STRUCTURAL CRITERIA: °J OJ r - ROOF ATTACHMENT COUNT: 32 o z Lu �a��o�oCU RAIL MANUFACTURER Unirac ROOF TYPE asphalt_ shingle z c ~ u N J 3 Ln X N a-+ � fD ` wJ RAIL PART NUMBER SM ROOF FRAMING traditional -framing PV MODULE COUNT: 16 ~ 1O Q -j= o U ^ x ATTACHMENTS Unirac - FLASHKIT PRO ARRAY AREA: RAFTER/TOP CHORD SIZE 2x4 MODULE COUNT * 18.06ft2 = 288.96 ROOF AREA: 1179 ft2 -`-1 r-1 ATTACHMENT QTY 32 MIDCLAMP QTY 28 RAFTER/TOP CHORD SPACING 24 PERCENT OF ROOF COVERED: ATTACHMENT SPACING 48 ARRAY WEIGHT: 25% MODULE COUNT * 50lbs = 800 DATE: February 12, 2021 PAGE: SHEET NAME: PV04 ROOF ATTACHMENTS+BOM ENDCLAMP QTY g SPLICE QTY 4 DISTRIBUTED LOAD: POINT LOAD: (Ib ARRAY LBS ATTACHMENTS = 25 (ARRAY) WEIGHT/AREA = 2.77 lbs/ft2 DRAWN BY: SoloCAD PV MODULE END CLAMP MID CLAMP 1 2 RAIL ENC6R PV MODULE PV MODULE o MAX. 48" MAX. Ozo RAIL RAIL a FRONT VIEW r Z J ; 1 END CLAMP DETAILS 2 MID CLAMP DETAILS xa In al � 04 O YMo rn co V O r N RAIL ` "' W �' PV MODULE H C) z = rn z Vow L� O zv FLASHING & LAG-BOLT a� ._ (� W cn � � 4� RAIL 10" MIN 11-411 MAX L-FOOT/ATTACHMENT BRACKET 710" MIN — 411 2'-8" MIN - 1 '-411 3'-10" MAX 1 MAX N W _j 7 (E) COMP SHINGLE ROOF (1 LAYER) 0 O (E) RAFTER/TOP CHORD U > FLASHING 2'-8" MIN - a _ o10" MAX N 2 .' MIN. Q'P►��....�OF�L m w DEPTH 5/16" STAINLESS STEEL LAG-BOLT v0: YS�; �' • In In In � O :''� m � L9 I= WITH 2-1/2" MIN. EMBEDMENT oC) N J z AND FLAT WASHER 0o N ,� m _ 4 5 o -- o LU 0 0 0 (E) ROOF FRAMING • ' �� ap N �; DETAIL, MOUNTING AND FLASHING �Ss�ONAL��C� M a 'I L 3 SIDE VIEW z ANN^ o Vf O w r o Q 0U Ln O �i z cn md N u EQUIPMENT INFORMATION: ROOF INFO: PHOTOVOLTAIC ARRAY STRUCTURAL CRITERIA: � O aj z 0 -0 v RAIL MANUFACTURER Unirac ROOF TYPE asphalt shingle ROOF ATTACHMENT COUNT: 32 IL a� � O � o z ~ u N J 3 ` w X m J RAIL PART NUMBER SM ROOF FRAMING traditional—framing PV MODULE COUNT: 16 LnN a-+ � ~ fD 1O ¢ UJ u J = o u 2x4 ARRAY AREA: MODULE COUNT* 18.06ft2 = 288.96 x ATTACHMENTS Unirac - FLASHKIT PRO RAFTER/TOP CHORD SIZE LID ROOF AREA: 1179 ft2 —`-1 r-1 ATTACHMENT QTY 32 RAFTER/TOP CHORD SPACING 24 PERCENT OF ROOF COVERED: 25% DATE: February 12, 2021 MIDCLAMP QTY 28 ATTACHMENT SPACING 48 ARRAY WEIGHT: MODULE COUNT * 50lbs = 800 PAGE: SHEET NAME: ENDCLAMP QTY $ / DISTRIBUTED LOAD: ARRAY LBS ATTACHMENTS = 25 PV05 MOUNTING DETAIL SPLICE QTY 4 POINT LOAD: (Ibs/ft2) (ARRAY) WEIGHT/AREA = 2.77 Ibs/ft2 DRAWN BY: SoloCAD WIRE SCHEDULE (1) 10 AWG THWN-2 COPPER - (1-1) (1) 10 AWG THWN-2 COPPER - (1-1) 1 (2) PV-WIRE -10 AWG, USE-2, COPPER (OR CODE APPROVED EQUIVALENT) 2 (1) 10 AWG THWN-2, or THHN, or 10/2 NM-B COPPER- (POSITIVE) (1) 10 AWG THWN-2, or THHN, or 10/2 NM-B COPPER- (NEGATIVE) 3 (1) 10 AWG THWN-2 COPPER - (1-2) (1) 10 AWG THWN-2 COPPER - (NEUTRAL) 4 (1) 10 AWG THWN-2 COPPER - (1-2) (1) 10 AWG THWN-2 COPPER - (NEUTRAL) (1) 10 AWG THWN-2, or THHN, or 10/2 NM-B COPPER- (GROUND) (1) 10 AWG THWN-2 COPPER - (GROUND) (1) 10 AWG THWN-2 COPPER- (GROUND) 6 AWG BARE, COPPER (GROUND) (1) 3/4" LIQUID TIGHT OR EMT OR FMC (1) CONDUIT: 3/4" LIQUID TIGHT OR EMT (1) CONDUIT: 3/4" LIQUID TIGHT OR EMT (OR CODE APPROVED EQUIVALENT) (OR CODE APPROVED EQUIVALENT) (OR CODE APPROVED EQUIVALENT) ENCOR(1) STRINGS: SERVICE EQUIPMENT & PV OCPD STRING 1 16 PV MODULES MAIN BREAKER RATING RATINGS 200A MAIN SERVICE BUS RATING 200A OLO PV OCPD RATING 30A 41 AC VOLTAGE 240V >t� Cft AC DISCONNECT RATING 30A IY >SUB BUS 125 0 J C Z J > SUB MAIN 41h 100 LA j of O � Y Mr, loon U r N • LOAD SIDE CONNECTION NEC 705.12(B) q00 �OZD Z C.1 o(E) O Z ,U � � MAIN LU_ (� � UL 1741 COMPLIANT PV AC DISCONNECT (E) SUB PANEL SERVICE PANEL (E) UTILITY METER INTEGRATED RAPID VISIBLE, LOCKABLE, SHUTDOWN DC DISCONNECT LABELED, OPEN (E) MAIN 240V, 2-POLE (E) SUB BREAKER MAIN INVERTER (E) LOADS (E) LOADS DC N _= STRING [1] Ar__ __ (N) PV OCPD LU O \/1 I I AC � N N c 2 J-BOX c ITI V > Q a 1 (E) GROUNDIN 2 (E) 1ELECTROD 120/240 VAC Y MAppr w vI Notes. 4 - TO UTILITY GRID Ln Ln Ln � 1) PN array system to have grounding system installed per Part III of M r-iC) N o J > Article 250 per 2020 NEC Article 690.47(A). Co — 2) If UFER ground in not available provide or verify supplemental o Lu U o o ground rods per 2020 NEC Article 250.53(A)(3). 6 � o 0 0 tw_ v}, INTERCONNECTION NOTES: 1. INTERCONNECTION SIZING, LIMITATIONS AND COMPLIANCE GROUNDING & GENERAL NOTES: 3) Cold & Hot Water & Natural Gas bonding per 2020 NEC Article 250.104(A)(B) ,N cn U Q �n ? DETERMINED IN ACCORDANCE WITH [NEC 705.12], AND [NEC 690.64]. 1. PV INVERTER IS UNGROUNDED, TRANSFORMER-LESS TYPE. 2. DC GEC AND AC EGC TO REMAIN UNSPLICED, OR SPLICED TO EXISTING z t vi r- 0 3. GROUND FAULT PROTECTION IN ACCORDANCE WITH [NEC 215.91, ELECTRODE =) 2� p LLi � p [NEC 230.95] AND [NEC 690.5] a +j Ncri v w 4. ALL EQUIPMENT TO BE RATED FOR BACKFEEDING. 3. ANY EXISTING WIRING INVOLVED WITH PV SYSTEM CONNECTION THAT IS _o fO N j) CYN �. FOUND TO BE INADEQUATE PER CODE SHALL BE CORRECTED PRIOR TO FINAL EQUIPMENT SCHEDULE: O z LU C M -a c Ov DISCONNECT NOTES INSPECTION. TYPE: QTY: DESCRIPTION: RATING: Z c � V)i 5 3 w _ >` w � N w 1. DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN 4. JUNCTION BOX QUANTITIES, AND PLACEMENT SUBJECT TO CHANGE IN THE MODULES: (16) Hanwha Q. Cells Q.Peak DUO BLK-G5 320 320 W LU M = p Q THE SWITCH IS OPENED THE CONDUCTORS REMAINING LIVE ARE FIELD - JUNCTION BOXES DEPICTED ON ELECTRICAL DIAGRAM REPRESENT WIRE X CONNECTED TO THE TERMINALS MARKED "LINE SIDE' (TYPICALLY TYPE TRANSITIONS. INVERTERS: (1) SolarEdge SE5000H-US (240V) 5000 W THE UPPER TERMINALS) 2. AC DISCONNECT MUST BE ACCESSIBLE TO QUALIFIED UTILITY 5. AC DISCONNECT NOTED IN EQUIPMENT SCHEDULE OPTIONAL IF OTHER AC DISCONNECT(S): (1) PV AC DISCONNECT, 240V, 2-POLE AC DISCONNECTING MEANS IS LOCATED WITHIN 10' OF SERVICE DISCONNECT. DC OPTIMIZERS: (16) SolarEdge P320 30A 15 Adc DATE' February 12, 2021 PERSONNEL, BE LOCKABLE, AND BE A VISIBLE-BREAK SWITCH PAGE: SHEET NAME: PV06 ELECTRICAL DIAGRAM DRAWN BY: SoloCAD N LU J O 2 '¢ a Y M w M `n � `r) 1= L7 LU O N OLn J 00 N m Z OO � a O CD Y r4 .2 N , M Ln 4"-"-V CV Ln !F 5 M¢ rl N C7 = z °J v) Ln ^ o N O w koo ViLrl c; ztAm"LU o C7 N 0 �,zLU r M o LLa� a� O H 0 -0 a, z ��VV)J3Li' 'U L LJJ W Ln X ( a-+ M M J H C. V � 2 U � � DATE, February 12, 2021 PAGE: SHEET NAME: PV07 LABELS DRAWN BY: SoloCAD LABEL 5 PLACED ATO THE BACK -FED BREAKER WA E N I N. FROM T EDJACENT INVERTER IF IE IN CONSISTS OF LOAD SIDE CONNECTION TO BUSBAR. INVERTER OUTPUT CONNECTION [NEC 705.12(D)(2)(3)(b)] DO NOT RELOCATE THIS OVERCU'RRENT DEVICE LABEL VALUES: x WARN I G f�'1�'M,� ELECTRIC SHOCK HAZARD TERMINALS ON THE LINE AND LOAD SIDES MAY BE ENLRGIZLJ_"s .WR IN THE OPEN POSITION LABEL 1 FOR PV DISCONNECTING MEANS WHERE ALL TERMINALS OF THE DISCONNECTING MEANS MAY BE ENERGIZED IN THE OPEN POSITION. [NEC 690.13(B), NEC 705.221 LABEL 2 DC IMP: L DIRECT CURRENT AT EACH DC DISCONNECTING MEANS, INCLUDING THE DC VOC. PHOTOVOLTAIC POWER • s DC DISCONNECT AT THE INVERTER. [NEC 690.53, NEC 690.13(B)] SEE DATASHEET MAXIMUM VOLTAGE 480 VDD; 5120 AC OPERATING CURRENT: CIRCUIT CURRENT 15 AMPS AC VOLTAGE: UMAX cm C IDENTIFIED RAPID SHUTDOWN SWITCHES J J > PHOTOVOLTAIC [NEC 690.56(C)(1)(A)] INTERCONNECTION BILLING METER PER XCEL ENERGY. LABEL 3 Y M PHOTOVOLTAIC AT POINT OF INTERCONNECTION, MARKED AT AC C � ti ; AC DISCONNECTf DISCONNECTING MEANS. 0 =00) 0 CV SIDE BREAKER) [NEC 690.54, NEC 690.13 (B)] �Z00 ? N RATED AC OUTPUT CURRENT 21 A '0 0 N NDMINAL OPERATING AG VOLTAGE 240 V Z � 0) cv LU M J J LABEL 4 A R N I N G AT OFFOR EQUIPMENT CONTOAI ING OVERCUOR ENT DEVICES IN CIRCUTS DUAL POWER SUPPLY SUPPLYING POWER TO A BUSBAR OR CONDUCTOR SUPPLIED FORM MULTIPLE SOURCES, EACH SERVICE EQUIPMENT AND ALL ELECTRIC POWER PRODUCTION SOURCES: UTILITY GRID AND SOURCE LOCATIONS. PV SOLAR ELECTRIC SYSTE1\ 1 [NEC 705.12(B)(3)] N LU J O 2 '¢ a Y M w M `n � `r) 1= L7 LU O N OLn J 00 N m Z OO � a O CD Y r4 .2 N , M Ln 4"-"-V CV Ln !F 5 M¢ rl N C7 = z °J v) Ln ^ o N O w koo ViLrl c; ztAm"LU o C7 N 0 �,zLU r M o LLa� a� O H 0 -0 a, z ��VV)J3Li' 'U L LJJ W Ln X ( a-+ M M J H C. V � 2 U � � DATE, February 12, 2021 PAGE: SHEET NAME: PV07 LABELS DRAWN BY: SoloCAD LABEL 5 PLACED ATO THE BACK -FED BREAKER WA E N I N. FROM T EDJACENT INVERTER IF IE IN CONSISTS OF LOAD SIDE CONNECTION TO BUSBAR. INVERTER OUTPUT CONNECTION [NEC 705.12(D)(2)(3)(b)] DO NOT RELOCATE THIS OVERCU'RRENT DEVICE LABEL VALUES: DESCRIPTION VALUE: DC IMP: 9.6 DC VMP: 33.32 DC VOC. 40.56 DC ISC: SEE DATASHEET DC SYSTEM SIZE (W): 5120 AC OPERATING CURRENT: SEE DATASHEET AC VOLTAGE: 240 LABELING NOTES: 1. LABELS CALLED OUT ACCORDING TO ALL COMMON CONFIGURATIONS. ELECTRICIAN TO DETERMINE EXACT REQUIREMENTS IN THE FIELD PER CURRENT NEC AND LOCAL CODES AND MAKE APPROPRIATE ADJUSTMENTS. 2. LABELING REQUIREMENTS BASED ON THE 2014 NATIONAL ELECTRIC CODE, OSHA STANDARD 19010.145, ANSI Z535. 3. MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION. 4. LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED [NEC 110.21] 5. LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8", WHITE ON RED BACKGROUND; REFLECTIVE, AND PERMANENTLY AFFIXED [IFC 605.11.1.11 LABEL 6 AT DIRECT-CURRENT EXPOSED RACEWAYS, CABLE TRAYS, COVERS AND ENCLOSURES OF JUNCTION BOXES, AND OTHER WIRING METHODS; SPACED AT MAXIMUM 10FT SECTION OR WHERE SEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS, OR FLOORS. [NEC 690.31(G)(3&4)] SOLAR PV SYSTEM EQUIPPED LABEL 7 WITH RAPID SHUTDOWN FOR PV ARRAY SYSTEMS THAT SHUT DOWN THE AND CONDUCTORS LEAVING THE TURN RAPID SHUTDOWN ARRAY: SWITCH TO THE SIGN TO BE LOCATED ON OR NO MORE OFF` POSITION T4 srnnRaEerRic THAN 3 FT AWAY FROM SERVICE SHUT DOWN PV SYSTEM �'�rre�s DISCONNECTING MEANS TO WHICH THE AND REDUCE PV SYSTEMS ARE CONNECTED AND SHOCK HAZARD SHALL INDICATE THE LOCATION OF ALL INTHE ARRAY SOLAR PV SYSTEM EQUIPPED , WITH RAPID SHUTDOWN iL W,A R N I N G FIR .;., r, ALL ELECTRIC DOWER SOURCE TOTHE'OFF POSITIONy DISCONNECTING MEANS GROUPED AND TO SHUT DOWN CONDUCTORSsur eir O CDNDUGTORSWUIN THE ARRAY REMAINENERGIZED MAIN SUPPLY OVERCURRENT IN, SUNLIGHT M -OPACITY OF BUSBAR. IDENTIFIED RAPID SHUTDOWN SWITCHES IF NOT AT THE SAME LOCATION. PHOTOVOLTAIC [NEC 690.56(C)(1)(A)] SOLAR PV SYSTEM EQUIPPED , WITH RAPID SHUTDOWN iL W,A R N I N G FIR .;., r, ALL ELECTRIC DOWER SOURCE TOTHE'OFF POSITIONy DISCONNECTING MEANS GROUPED AND TO SHUT DOWN CONDUCTORSsur eir O CDNDUGTORSWUIN THE ARRAY REMAINENERGIZED MAIN SUPPLY OVERCURRENT IN, SUNLIGHT DEVICE, SHALL NOT EXCEED LABEL 8 FOR PV SYSTEMS THAT ONLY SHUT DOWN CONDUCTORS LEAVING THE ARRAY: SIGN TO BE LOCATED ON OR NO MORE THAN 3 FT AWAY FROM SERVICE DISCONNECTING MEANS TO WHICH THE PV SYSTEMS ARE CONNECTED AND SHALL INDICATE THE LOCATION OF ALL IDENTIFIED RAPID SHUTDOWN SWITCHES IF NOT AT THE SAME LOCATION. [NEC 690.56(C)(1)(B)] LABEL 9 SIGN LOCATED AT RAPID SHUT DOWN DISCONNECT SWITCH [NEC 690.56(C)(3)]. I A' --LABEL 13 SIGN LOCATED AT MAIN SERVICE iL W,A R N I N G DISCONNECTING MEANS IF ALL ALL ELECTRIC DOWER SOURCE ELECTRICAL POWER SOURCE DISCONNECTING MEANS GROUPED AND DISCONNECTING MEANS ARE GROUPED LABELED WITHIN 10 FT AND LINE OF SITE WITHIN 10' AND LINE OF SITE OF MAIN OF THIS LOCATION SERVICE DISCONNECT [NEC 690.56(B) & MAIN SUPPLY OVERCURRENT NEC 705.101. MAIN SERVICE PANEL PV AC DISCONNECT NO DC WIRES PRESENT RAPID SHUTDOWN TEST NOT REQUIRED 11 00103 LABEL 10 iL W,A R N I N G (ONLY IF 3 A BUSBAR) R MORE SUPPLY SOURCES TO PV COMBINER SUBPANEL - IF USED TO COMBINE PV OUTPUT CIRCUITS SIGN LOCATED AT LOAD CENTER IF IT THIS EUIPIEdWT FED BY MULTIPLE 3 OR MORE POWER SOURCES. [NEC [NEC 705.12(D)(2)(3)(C)] SOURCES. TOTAL RATING OF ALL O C'VERCURRENT DEVICES, EXCLUDING O7 OR O8 OO MAIN SUPPLY OVERCURRENT 12 O DEVICE, SHALL NOT EXCEED M -OPACITY OF BUSBAR. (ONLY IF PV LABEL 11 PHOTOVOLTAIC PLACARD TO BE PLACED AT THE MAIN INTERCONNECTION BILLING METER PER XCEL ENERGY. SYSTEM CONNECTED PV AC DISCONNECT NO DC WIRES PRESENT RAPID SHUTDOWN TEST NOT REQUIRED 11 00103 O O O4 13 EXISTING SUB PANEL (IF WHERE POINT OF INTERCONNECTION IS MADE) LABELING DIAGRAM: AC DISCONNECT PV COMBINER SUBPANEL - IF USED TO COMBINE PV OUTPUT CIRCUITS O O O O O O7 OR O8 OO O4 12 O O 0 (ONLY IF PV (ONLY IF PV 14 O INTERCONNECTION INTERCONNECTION CONSISTS OF LOAD CONSISTS OF LOAD SIDE BREAKER) SIDE BREAKER) LABEL 12 PLACARD TO BE PLACED AT AC DISCONNECT PER XCEL ENERGY. LABEL 14 SIGN LOCATED AT AC COMBINER BOX FOR ALL MICRO -INVERTER / AC MODULE INSTAL INVERTER (S) HDC JUNCTION BOX OR COMBINER BOX OOE�oq O O INTEGRATED DC DISCONNECT *ELECTRICAL DIAGRAM SHOWN ABOVE IS FOR LABELING PURPOSES ONLY. NOT AN ACTUAL REPRESENATION OF EQUIPMENT AND CONNECTIONS TO BE INSTALLED. LABEL LOCATIONS PRESENTED MAY VERY DEPENDING ON TYPE OF INTERCONNECTION METHOD AND LOCATION PRESENTED ON PV5 OF 3 LINE DIAGRAM. PV5 LINE DIAGRAM TO REFLECT ACTUAL REPRESENTATION OF PROPOSED SCOPE OF WORK. 0 Lo J .� J > L.0 N C0 0) O r '4m N 0 8 z N V o o z 0) c� W c1r) N W J OC G 'Q a Y M W M � Lr) Ln � 0 cr N OLn LUJ � v, co z o > o�000� Y cV "t),o c! m c/ +�+ VCV G7 a � a 'I Ln z °J ,r; r o N 0Lto �o +� = N � (A tnn m v U w OU p z b 1 LL a) a�OH o=-0 v z_ �HV�nJ 3 L - O Ln X N a-+ fD J H a V 2 n U t/f U M ^N X v v DATE February 12, 2021 PAGE: SHEET NAME: PV08 PLACARD DRAWN BY: SoloCAD CAUTION POWER TO THIS BUILDING IS ALSO SUPPLIED FROM ROOF MOUNTED SOLAR ARRAYS WITH SAFETY DISCONNECTS AS SHOWN: N MAIN DISTRIBUTION UTILITY DISCONNECT 0 0 O o -n O z O --1 0 AC DISCONNECT z O INVERTER & RAPID z m SHUTDOWN DC DISCONNECT SWITCH PV ARRAY 3615 Teller St, Wheatridge CO 80033 DIRECTORY PERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION OF THE SERVICE DISCONNECTING MEANS AND THE PHOTOVOLTAIC SYSTEM. (ALL PLAQUES AND SIGNAGE WILL BE INSTALLED AS OUTLINED WITHIN: NEC 690.56(B)&(C), [NEC 705.10]) SITE PHOTOS: EJO ENCOR 0 B c o IB\b H 508Ts u Z i.v emn f 0 LoO O u ry O U U- J C Z J cLo U) N O � M cc)( C O = VM U (n � W � _l l i 1l _— kWh x'_200 240V 3SV TYPE C15R 30TA I.00 CAT# 0130536") Xcel Energy CA 0.5 60HZ s2oz 75 459 202 I (000; 10 Z u�i -I.lr�n METER loon ZZ or UJ m, SA 1.7 _ ;� f 1 ❑tea ®�m�® i� Uj �°r• J`i Q, Q a C) c M WLn Ln Lni W_ C) LU N O J Z00 �r OV LU Q O o > — v — b En fV re Ito - 4L•+ U 1-4 Ln � M Q rl Ln ' Z �c/1 NC1=. 'n^ q T- l t N _� O � to 0 � ��Owl, c) �+ = N w Q o rn � O �cnZinM N U CC H tan pi dTuo: , 11 OH o�"a a, Z H V J 3 111 w •L - _ W O LnX N +� m —i L Q J = U- r1 ` DATE, February 12, 2021 PAGE: SHEET NAME: PV09 SITE PHOTOS DRAWN BY: SoloCAD The new D.PEAB DUO BLg-G5 solar module from Q CELLS impresses with its outstanding visual appearance and particularly high performance �vn on a small surface thanks to the innovative O.ANTUM DUO Technology. in D.ANTUM's world -record -holding cell concept has now been combined 2Cr with slate -of -the -art circuitry half cells and a six -bulbar design, thus cImp / TYPE Iair achieving outstanding performance under real conditions — both with In low -intensity solar radiation as well as an hot, clear summer days. I-AwlnD wva n ANTUM TECHNOLOGY LOW LEVEUIEO 105T 01 EIECTRIPTI HSher yield pface area lower BUS casts higher Hover m' tl an efficiency rate of up to 19.3 Is. ^ma. ' IXXOVA➢VF ALL WEATHER TECHNOLOGY 2lhusAs Op[mal yeltls whatever the weather with excellent ow-I'Art ,.. Mosse. con. and temperature hanador. °'4/ •— ENDURING RIGH PERFORMANCE rem Demo em mf, y l tt� L g- y Itl ur ty with Ant LID TUM1n01no' CICELLS A [ PIDIAOhn,lbar, Hot Saot Pmtectantl Toy ceffile Quality Tom UU-. EXIREME WEATHER RATING High tech Nlumnum alloy frame wrifatl for high snow rver,n 8018 (5400 Pa) and wind loads (4000 had regarc i TO l EC. BLE O ARELMerfarm Inclu=va 12yearproduct wsranty and 25jear ® �'` linear perfprmanw guarantaea- ncepaT `/\`�J'A, STATE Or THE ART MODULE TECHNOLOGY In Pereves, gAN,UM DUO combines cutting edge cell separation andtl-nnova[ve Along who OANTUM Teentology am . u)m THE IDEAL SOLUTION FOR: 1w INA. vast ar nor for mor mto.mauon. n....ml,.oema ® ammwnpN Engineered In Germany Q CE LLS r^'^ras lAXSNmOrrIeOu .E ad say lsMlA.1 �vn in gga 2Cr ini NUUA cImp / TYPE Iair a+y.. tw 1111w In a,mmoto S I-AwlnD wva m , .e....... m' IW ^ma. 11ff 01Maine FUNIT th aau rexu'uoa c anal lI ma—exec all as,1.1, 2lhusAs Om.va a x ,.. Mosse. con. °'4/ •— rem Demo em mf, y gre rer lym w mure x n 109 15.4.43 x3.t o�E C E $P" eam[a e[Nm,D.r .n �~�- , wmm etaI m 6120 111anquall-GANTUMwIeTf I, Is ammwnpN ❑ 6 tui fe 21-1 uAssirs Sor use ww r.z (]tOomM. Fl za331alImpss "NeI ]05 ]10 315 I30 MINIMUM FE:FORM"GE AT STwwnxo man POND, s'Agv tm[vnx[[15 MINIMUM [ AT xuxlnn[ Or[unxxw years ad 22v 1 2278 PAT 6 Is, 1 21N 1 IT P 111 7. 7 12 7A7 111 to Is 11 37 an I My Is IT 11 11 an 7 IN 711 117 7 It 711 x.Mewne, Use on To IN IT 1 van IT awe If awry lAXSNmOrrIeOu .E ad say lsMlA.1 ..+ >um.m Iss, Unix ery, gga 2Cr ini NUUA cImp / TYPE Iair a+y.. tw 1111w In 5� I-AwlnD wva m , m' an nmm eutl ^ma. Om.va a x ,.. Mosse. con. rem Demo em mf, y Ups o.]s xmmv W uk]emn w mure x n 109 15.4.43 x3.t >um.m a,aaa wenn Us In, hemnwe Iu ..+ >um.m Iss, Unix ery, IN al 2Cr ini NUUA cImp / TYPE Iair a+y.. tw 1111w In 75 11111111, 15 11517 'xI I-AwlnD wva m , an nmm eutl c ras Pc, o�E C E $P" eam[a e[Nm,D.r .n �• , wmm etaI m ammwnpN Let amI.,ad Optimized installation with HD -Wave technology Specifically designed to work with Extremely small power optimizers Record-breaking efficiency Built-in module -level monitoring Fixed voltage inverter for longer strings Outdoor and indoor installation Integrated arc fault protection and rapid shutdown for Optional: Revenue grade data, ANSI C12.20 NEC 2014 and 2017, per article 690.11 and 690.12 Class 0.5 (0.5% accuracy) UL1741 SA certified, for CPUC Rule 21 grid compliance solaredge.com so I a r.. C of Single Phase Inverter with HD -Wave Technology for North Ameri( SE3000H-US / SE3800H-US / SE5000H-US / SE6000H-US/ SE7600H-US / SE10000H-US / SE11400H-US OUTPUT Rated AC Power Output 3000 3800 @ 240V 5000 6000 @ 240V 7600 10000 11400 @ 240V VA 3300 @ 208V 5000 @ 208V 10000 @ 208V 3800 @ 240V 6000@ 240V Maximum AC Power Output 3000 5000 7600 10000 3300 @ 208V 5000 @ 208V Single Phase Inverter z with HD -Wave Technology m ✓ Vac AC Frequency (Nominal) 59.3 - 60 - 60.511) for North America ;a_ SE3000H-US / SE3800H-US / SE5000H-US / SE6000H-US / 25 SE7600H—US / SE10000H—US / SE11400H—US r� 12-25 m YEAR solar =--- WAR7RIANTY 24 CA 0 solarZ-,T!z GFDI Threshold 1 A Utility Monitoring, Islanding Protection, Country Configurable Thresholds Yes Optimized installation with HD -Wave technology Specifically designed to work with Extremely small power optimizers Record-breaking efficiency Built-in module -level monitoring Fixed voltage inverter for longer strings Outdoor and indoor installation Integrated arc fault protection and rapid shutdown for Optional: Revenue grade data, ANSI C12.20 NEC 2014 and 2017, per article 690.11 and 690.12 Class 0.5 (0.5% accuracy) UL1741 SA certified, for CPUC Rule 21 grid compliance solaredge.com so I a r.. C of Single Phase Inverter with HD -Wave Technology for North Ameri( SE3000H-US / SE3800H-US / SE5000H-US / SE6000H-US/ SE7600H-US / SE10000H-US / SE11400H-US OUTPUT Rated AC Power Output 3000 3800 @ 240V 5000 6000 @ 240V 7600 10000 11400 @ 240V VA 3300 @ 208V 5000 @ 208V 10000 @ 208V 3800 @ 240V 6000@ 240V Maximum AC Power Output 3000 5000 7600 10000 3300 @ 208V 5000 @ 208V 11400 @ 240V VA 10000 @ 208V AC Output Voltage Min. -Nom. -Max. ✓ ✓ ✓ ✓ ✓ ✓ (211 - 240 - 264) ✓ Vac AC Output Voltage Min. -Nom. -Max. ✓ ✓ _ - (183 - 208 - 229) ✓ Vac AC Frequency (Nominal) 59.3 - 60 - 60.511) Hz Maximum Continuous Output 12.5 16 Current @240V 21 25 32 42 47.5 A Maximum Continuous Output - 16 Current @208V 24 48.5 A GFDI Threshold 1 A Utility Monitoring, Islanding Protection, Country Configurable Thresholds Yes INPUT Maximum DC Power @240V 4650 5900 1 7750 1 9300 11800 15500 17650 W Maximum DC Power @208V - 5100 - 7750 15500 W Transformer -less, Ungrounded Yes Maximum Input Voltage 480 Vdc Nominal DC Input Voltage 380 400 Vdc Maximum Input Current @240V111 8.5 10.5 13.5 16.5 20 27 30.5 Adc Maximum Input Current @208V(" - 9 - 13.5 - - 27 Adc Max. Input Short Circuit Current 45 Adc Reverse -Polarity Protection Yes Ground -Fault Isolation Detection 600kQ Sensitivity Maximum Inverter Efficiency 99 99.2 % CEC Weighted Efficiency gg 99 @ 240V % 98.5 @ 208V Nighttime Power Consumption < 2.5 W ADDITIONAL FEATURES Supported Communication Interfaces RS485, Ethernet, ZigBee (optional), Cellular (optional) Revenue Grade Data, ANSI C12.20 Optional"' Rapid Shutdown - NEC 2014 and Automatic Rapid Shutdown upon AC Grid Disconnect 2017 690.12 STANDARD COMPLIANCE Safety UL1741, UL1741 SA, UL1699B, CSA C22.2, Canadian AFCI according to T.I.L. M-07 Grid Connection Standards IEEE1547, Rule 21, Rule 14 (HI) Emissions FCC Part 15 Class B INSTALLATION SPECIFICATIONS AC Output Conduit Size / AWG Range 1" Maximum / 14-6 AWG 1" Maximum /14-4 AWG DC Input Conduit Size / # of Strings / 1" Maximum / 1-2 strings / 14-6 AWG 1" Maximum / 1-3 strings / 14-6 AWG AWG Range Dimensions with Safety Switch 17.7 x 14.6 x 6.8 / 450 x 370 x 174 21.3 x 14.6 x 73 (HxWxD) / 540 x 370 x 185 in/ mm Weight with Safety Switch 22110 25.1/11.4 26.2/11.9 38.8/17.6 Ib / kg Noise < 25 <50 dBA Cooling Natural Convection Operating Temperature Range -13 to +140 / -25 to +601'1 (-40°F / -40°C option)151 °F / °C Protection Rating NEMA 4X (Inverter with Safety Switch) "I For power de -rating information refer to: httpsV/www.solaredge.com/sites/default/files/se-temperature-derating-note-na.pdf 151-40 version P/N: SExxxxH-USOOONNU4 ® SolarEdge Technologies, Inc. All rights reserved. SOLAREDGE, the SolarEdge logo, OPTIMIZED BY SOLAREDGE are trademarks or registered trademarks of SolarEdge Technologies, Inc. All Ro HS other trademarks mentioned herein are trademarks of their respective owners. Date: 03/2019N01/ENG NAM. Subject to change without notice. Power Optimizer ma O For North America P320 / P340 / P370 / P400 / P405 / P505 T 25 YEAR • WARRANTY PV power optimization at the module -level Specifically designed to work with SolarEdge Fast installation with a single bolt inverters Up to 25% more energy Superior efficiency (99.5%) Mitigates all types of module mismatch losses, from manufacturing tolerance to partial shading Flexible system design for maximum space utilization solaredge.com Next generation maintenance with module - level monitoring Meets NEC requirements for arc fault protection (AFCI) and Photovoltaic Rapid Shutdown System (PVRSS) Module -level voltage shutdown for installer and firefighter safety solar =-W Power Optimizer For North America P320 / P340 / P370 / P400 / P405 / P505 INPUT Rated Input DC PowerO 320 340 370 400 405 505 W Absolute Maximum Input Voltage (Voc at lowest temperature) 48 60 80 12581 87(2) Vdc MPPT Operating Range 8-48 8-60 8-80 12.5 -105 12.5-87 Vdc Maximum Short Circuit Current (Isc) 11 10.1 14 Adc Maximum DC Input Current 13.75 12.5 17.5 Adc Maximum Efficiency 99.5 % Weighted Efficiency 98.8 98.6 % Overvoltage Category II OUTPUT DURING OPERATION (POWER OPTIMIZER CONNECTED TO OPERATING SOLAREDGE INVERTER) Maximum Output Current 15 Adc Maximum Output Voltage 60 85 Vdc OUTPUT DURING STANDBY (POWER OPTIMIZER DISCONNECTED FROM SOLAREDGE INVERTER OR INVERTER OFF) SOLAREDGE Safety Output Voltage per Power Optimizer 1 ± 0.1 Vdc STANDARD COMPLIANCE EMC FCC Part15 Class B, IEC61000-6-2, IEC61000-6-3 Safety IEC62109-1 (class II safety), UL1741 Material UL94 V-0, UV Resistant RoHS Yes INSTALLATION SPECIFICATIONS Maximum Allowed System Voltage 1000 Vdc Compatible inverters All SolarEdge Single Phase and Three Phase inverters Dimensions(WxLxH) 129x153 x27.5/5.1x6x1.1 129 x153 x33.5/ 5.1x6x1.3 129 x159x49.5/ 5.1x6.3x1.9 129x162 x59/ 5.1x6.4x2.3 mm/in Weight (including cables) 630/1.4 750/1.7 845/1.9 1064/2.3 gr / Ib Input Connector Single or dual MC40I Input Wire Length 0.16/0.52 m / ft Output Wire Type / Connector Double Insulated / MC4 Output Wire Length 0.9/2.95 1.2/3.9 m / ft Operating Temperature Range -40 - +85 / -40 - +185 -C / -F Protection Rating IP68 / NEMA6P Relative Humiditv 0-100 % nl Rated power of the module at STC will not exceed the optimizer "Rated Input DC Power". Modules with up to +5% power tolerance are allowed ¢ NEC 2017 requires max input voltage be not more than 80V Of For other connector types please contact SolarEdge PV System Design Using Single Phase Single phase Three Phase 208V Three Phase 480V a SolarEdge Inverterf41f51 HD -Wave g •-0 Minimum String Length • " (PowerOptimizers) StringMaximum Length .. �. 00 .000 with Maximum Power per String SE7600-U .I Different Lengths or . i , .i wl For detailed string sizing information refer to: http://www.sularedge.com/sites/default/files/string_sizing_na.pdf (S) It is not allowed to mix P405/P505 with P320/P340/P370/P400 in one string * A string with more than 30 optimizers does not meet NEC rapid shutdown requirements; safety voltage will be above the 30V requirement m For SE14.4KU5/5E43.2KUS: It is allowed to install up to 6,500W per string when 3 strings are connected to the inverter (3 strings per unit for the maximum power difference between the strings is up to 1,000W Il) For SE30KUS/SE33.3KUS/SE66.6KUS/SE100KUS It is allowed to install up to 15,000W per string when 3 strings are connected to the inverter and when the maximum power difference between the strings is up to 2,000W ® SolarEdge Technologies Ltd. All rights reserved. SOLAREDGE, the SolarEdge logo, OPTIMIZED BY SOLAREDGE are trademarks or registered trademarks of SolarEdge Technologies, Inc. E Ro H S All other trademarks mentioned herein are trademarks of their respective owners. Date: 07/2019N01/ENG NAM. Subject to change without notice. CONCEALED UNIVERSAL CLAMPS 0UNIRAC OPTION FRONAL YEAR T TRIM f�LL SYSTEM WARRANTY 9p, I MIN THE PROFESSIONALS' CHOICE FOR RESIDENTIAL RACKING'' BEST INSTALLATION EXPERIENCE • CURB APPEAL • COMPLETE SOLUTION • UNIRAC SUPPORT SOLARMOUNT BETTER DESIGNS TRUST THE INDUSTRY'S BEST DESIGN TOOL Start the design process for every project in our U -Builder on-line design tool. It's a great way to save time and money. BETTER SYSTEMS ONE SYSTEM - MANY APPLICATIONS Quickly set modules flush to the roof on steep pitched roofs. Orient a large variety of modules in Portrait or Landscape. Tilt the system up on flat or low slow roofs. Components available in mill, clear, and darkfinishesto optimize yourdesign financials and aesthetics. TETTER RESULTS MAXIMIZE PROFITABILITY ON EVERY JOB Trust Unirac to help you minimize both system and labor costs from the time the job is quoted to thetime yourteams get off the roof. Faster installs. Less Waste. More Profits. BETTER SUPPORT WORK WITH THE INDUSTRIES MOST EXPERIENCED TEAM Professional support for professional installers and designers. You have access to our technical support and training groups. Whatever your support needs, we've got you covered. Visit Unirac.com/solarmount for more information. c BONDING&GROUNDING LU MECHANICAL LOADING SYSTEM FIRE CLASSIFICATION .No UNIRAC CONCEALED UNIVERSAL ENDCLAMPS UNIVERSAL SELF STANDING MIDCLAMPS 6 0 0 END CAPS INCLUDED WITH EVERY ENDCLAMP U -BUILDER ONLINE DESIGN TOOL SAVES TIME & MONEY Visit design.unirac.com UNIRAC CUSTOMER SERVICE MEANS THE HIGHEST LEVEL OF PRODUCT SUPPORT UNMATCHED CERTIFIED ENGINEERING BANKABLE DESIGN PERMIT E EXPERIENCE QUALITY EXCELLENCE WARRANTY TOOLS DOCUMENTATION TECHNICAL SUPPORT CERTIFIED QUALITY PROVIDER BANKABLE WARRANTY Unirac's technical support team is dedicated to answering Unirac is the only PV mounting vendor with ISO certifications Dort leave your project to chance, Unirac has the financial questions & addressing issues in real time. An online for 90012008, 140012004 and OHSAS 180012001, strength to back our products and reduce your risk. Have library of documents including engineering reports, which means we deliver the highest standards for fit, peace of m' stamped letters and technical data sheets greatly form, and function. These certifications demonstrate our exceptional simplifies your permitting and project planning process. excellence and commitment to first class business practices. limited produ ENHANCE YOUR REPUTATION WITH QUALITY RACKING SOLUTIONS BACKED BY ENGINEERING EXCELLENCE lit« PUB20IGMAY16 - PRINTED UPDATE mmUNIRAC FLASHKIT PRO MEN ME FEATURING ® SHED & SEAL TECHNOLOGY FLASHKIT PRO is the complete attachment solution for composition shingle roofs. Featuring Unirac's patented SHED & SEAL technology, a weather proof system which provides the ultimate protection against roof leaks. Kitted in 10 packs for maximum convenience, flashings and hardware are available in Mill or Dark finishes. With FLASHKIT pro, you have everything you need for a quick, professional installation. TRUSTED WATER SEAL FLASHINGS FEATURING ® SHED & SEAL TECHNOLOGY nun YOUR COMPLETE SOLUTION CONVENIENT 10 PACKS Flashings, lags, continuous slot L -Feet and hardware Packaged for speed and ease of handling FLASHKIT PRO soon U N I RAC INSTALLATION GUIDE FEATURING ® SHED s SEAL TECHNOLOGY FLASHKIT PRO IS THE COMPLETE FLASHING AND ATTACHMENT SOLUTION FOR COMPOSITION ROOFS. 1►1+1ru1m, �f a19;11111XIIIIN _ 81r111101111 PRE -INSTALL • Locate roof rafters and snap chalk lines to mark the installation point for each roof attachment. • Drill a 1/32" pilot hole at each roof attachment. Fill each pilot hole with sealant. STEP 1 INSTALL FLASHKIT PRO FLASHING • Add a U-shaped bead of roof sealant to the underside of the flashing with the open side of the U pointing down the roof slope. Slide the aluminum flashing underneath the row of shingles directly up slope from the pilot hole as shown. Align the indicator marks on the lower end of the flashing with the chalk lines on the roof to center the raised hole in the flashing over the pilot hole in the roof. When installed correctly, the flashing will extend under the two courses of shingles above the pilot hole. STEP 2 INSTALL L -FOOT • Fasten L -foot and Flashing into place by passing the included lag bolt and pre-installed stainless steel -backed EPDM washer through the L -foot EPDM grommet, and the raised hole in the flashing, into the pilot hole in the roof rafter. ATTACH L-FOOTTO RAIL • Drive the lag bolt down until the L -foot is held firmly in place. It is normal for the EPDM on the underside of the stainless steel backed EPDM washer to compress and expand beyond the outside edge of the steel washer when the proper torque is applied. TIP: • Use caution to avoid over-torqueingthe lag bolt if usingan impact driver. • Repeat Steps 1 and 2 at each roof attachment point. STEP 3 ATTACH L-FOOTTO RAIL • Insert the included 3/8"-16 T -bolts into the lower slot on the Rail (sold separately), spacing the bolts to match the spacing between the roof attachments. • Position the Rail against the L -Foot and insert the threaded end of the T -Bolt through the continuous slot in the L -Foot. Apply anti -seize to bolt threads to prevent galling of the T -bolt and included 3/8" serrated flange nut. Place the 3/8" flange nut on the T -bolt and finger tighten. Repeat STEP 3 until all L -Feet are secured to the Rail with a T -bolt. Adjust the level and height of the Rail and torque each bolt to 30ft-lbs. From: no-reolv(alci.wheatridae.m. us To: CommDev Perm is Subject: Online Form Submittal: Solar PV Installation Date: Monday, February 22, 20214:50:38 PM Solar PV Installation This application is exclusively for Solar PV Installations YOU MUST ATTACH A VALID ELECTRONIC PAYMENT ORM IN ORDER FOR THE PERMIT TO BE PROCESSED. Your Permit will be emailed to the email address provided below once it is processed. THIS APPLICATION DOES NOT CONSTITUTE A PERMIT. DO NOT BEGIN WORK UNTIL PERMIT HAS BEEN ISSUED. Is this application for Yes Solar PV Installation? PROPERTY INFORMATION Property Address 3615 Teller St Property Owner Name Caroline Mallory Property Owner Phone Number (enter WITH dashes, eg 303-123- 4567) Property Owner Email Address Attach City of Wheat Ridge Electronic Payment Form - "DO NOT ATTACH A PICTURE OF A CREDIT CARD" (303) 949-1900 Choc489@hotmail.com Electronic Payment Wheatridae.odf CONTRACTOR INFORMATION Contractor Business Encor Solar LLC Name Wheat Ridge 0101434 Contractor's License Number (This is a 5 or 6 digit number for the City of Wheat Ridge) Contractor Phone 5124899919 Number (enter WITH dashes, eg 303-123- 4567) Contractor Email permits@encorsolar.com Address Retype Contractor permits@encorsolar.com Email Address DESCRIPTION OF WORK Scope of Work Installation of PV Solar Panels (Rooftop) KW 5.12 # of Panels 16 Location of Panels Garage Roof Structural required No Upload engineer letter Mallory ENG.odf or pages on 8 1/2" x 11" only Solar Installation Plan Mallory CAD.Ddf Set on 11'x17" only. Project Value (contract $21,986.08 value or cost of ALL materials and labor) SIGNATURE OF UNDERSTANDING AND AGREEMENT I assume full Yes responsibility for compliance with applicable City of Wheat Ridge codes and ordinances for work under any permit issued based on this application. I understand that work Yes may not begin on this property until a permit has been issued and posted on the property. I certify that I have Yes been authorized by the legal owner of the property to submit this application and to perform the work described above. Person Applying for Rodrigo Quezada Permit I attest that everything Yes stated in this application is true and correct and that falsifying information in this application is an act of fraud and may be punishable by fine, imprisonment, or both. Email not displaying correctly? View it in your browser. 1* ► � i City of Wheat Ridge '/� Residential Solar PERMIT - 202100341 PERMIT NO: 202100341 ISSUED: 06/14/2021 JOB ADDRESS: 3615 Teller St EXPIRES: 06/14/2022 JOB DESCRIPTION: Install 5.12 kw solar PV system, 16 panels on garage roof, no structural required *** CONTACTS *** OWNER (3 0 3) 949-1900 MALLORY CAROLINE SUB (888)240-1131 NATE HADACHEK 210130 IMPACT ENERGY *** PARCEL INFO *** ZONE CODE: UA / Unassigned USE: UA / Unassigned SUBDIVISION CODE: 2405 / BARTHS, COULEHAN GRANGE, WHEAT BLOCK/LOT#: 0 / *** FEE SUMMARY *** ESTIMATED PROJECT VALUATION: 21,986.08 FEES Total Valuation 0.00 Residential Solar 500.00 ** TOTAL ** 500.00 *** COMMENTS *** *** CONDITIONS *** A printed copy of the permit and city stamped on-site plans must be available on-site for the first inspection. Approved per plans and red -line notes on plans. Must comply with 2018 IRC, 2020 NEC and all applicable City of Wheat Ridge Municipal Codes. Work is subject to field inspections. I, by my signature, do hereby attest that the work to, be performed shall comply with all accompanying approved plans and specifications, applicae building codes, and all applicable municpal codes, policies and procedures, and that I am the legal owner or have been authorized by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with this�permrt. I further attest that I am leg ally authorized to include alI entities named within this document as parties to the work to be performed and that all work to be performed is disclosed in this document and/or its' accompanying approved plans and specifications. Signature of OWNER or CONTRACTOR (Circle one) Date 1, This permit was issued based on the information provided in the permit application and accompanying plans and specifications and is subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures. 2. This permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and received prior to the date of expiration. An extension of no more than 180, days made be granted at the discretion of the Chief Building Official and may be subject to a fee equal to one-half of the original permit fee. 3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard requirements, fees and��procedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of the Chief Building Official and is not guaranteed. 4. No work of any manner shall be performed that shall results in a change of the natural flow of water without prior and specific approval. 5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all requ�ired inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services Division. 6. The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, anviolation of any provision of any �pplicabje code or any ordinance or regulation of this jurisdiction. Approval of work is subject to field inspection. 06/14/2021 Signature of Chief Building Official Date REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. �a A i CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type: --Sol, m, d Job Address: -3b 15– —J, 11, , 5-L Permit Number: a 0 r —7 6 9 3 45 t, n P r --n a ge s S ❑ No one available for inspection: Time l = / S AM/ M� Re -Inspection required: es No When corrections have been made, call for re -inspection at 303 -234 - Date: ! I /-7 Inspector: =ra- DO NOT REMOVE THIS NOTICE A City of Wheat Ridge .,r r ® Residential Roofing PERMIT - 201709286 PERMIT NO: 201709286 ISSUED: 11/28/2017 JOB ADDRESS: 3615 Teller ST EXPIRES: 11/28/2018 JOB DESCRIPTION: Residential re -roof of house and detached garage with asphalt architectural/dimensional shingles.Pitch is°x/12 and 37 total number of squares. U *** CONTACTS *** OWNER (303)949-1900 CAROLINE MALLORY SUB (303)758-7663 Jason Gillis 090242 d-7 Roofing, LLC *** PARCEL INFO *** ZONE CODE: UA / Unassigned USE: UA / Unassigned SUBDIVISION CODE: 2405 / BARTHS, COULEHAN GRANGE, WHEAT BLOCK/LOT#: 0 / *** FEE SUMMARY *** ESTIMATED PROJECT VALUATION: 23,630.00 FEES Total Valuation 0.00 Use Tax 496.23 VAI N Permit Fee 426.20 ** TOTAL ** 922.43 *** COMMENTS *** *** CONDITIONS *** Midroof & Final Roof inspections for ROOFS 6/12 PITCH & OVER: 3rd party inspection will be required for both the midroof and final inspections. The 3rd party inspection report AND THE ORIGINAL PERMIT CARD needs to be dropped off to the Permit Desk at the City of Wheat Ridge. The report MUST BE SIGNED by the Homeowner. REGARDING ROOF VENTILATION: Roof ventilation shall comply with IBC Sec. 1203.2 or IRC Sec. R806. The installation of ridge venting requires the installation or existence of soffit venting. For calculation purposes, one hat or turtle vent equal to one-half of one square foot of opening. Effective December 1, 2014, asphalt shingle installations require an approved midroof inspection, conducted when 25-75 percent of the roof covering is installed, prior to final approval. Installation of roof sheathing (new or overlay) is required on the entire roof when spaced or board sheathing with ANY gap exceeding one half inch exists. Sheathing and mid -roofs may be called in at the same time, one hundred percent of the sheathing must be complete and 25-75 percent of the mid -roof may be complete. Asphalt shingles are required to be fastened to the roof deck with a minimum of 6 nails per shingle. Ice and water shield is required. Eave and rake metal is required. A ladder extending 3 feet above the roof eave and secured in place is required to be provided for all roof inspections. Roof ventilation is required to comply with applicable codes and/or manufacturer installation instructions, whichever is more stringent. In order to pass a final inspection of elastomeric or similar type roof coverings, a letter of inspection and approval from the manufacturer technical representative stating that "the application of the roof at (project address) has been applied in accordance with the installation instruction for (roof material brand name) roof covering" is required to be on site at the time of final inspection. City of Wheat Ridge Residential Roofing PERMIT - 201709286 PERMIT NO: 201709286 ISSUED: 11/28/2017 JOB ADDRESS: 3615 Teller ST EXPIRES: 11/28/2018 JOB DESCRIPTION: Residential re -roof of house and detached garage with asphalt architectural/dimensional shingles.Pitch is 6/12 and 37 total number of squares. I, by my signature; do hereby attest thdt`the work to be performed shall comply with all accompanying approved plans and specifications, applicable uiiding codes, and all applicable municipal codes, policies and procedures, and that I, the legal owner or have been authorized by the legal pwner of the propert, am authorized to obtain this permit and perform the work described and approved in conjunction with this ermit.:i further attest that I` legally authorized to include all entities named within this document as parties to the work to be perform and that alt w r t performed is disclosed in this document and/or its' accompanying approved plans and specifications. Signatuk of OWNER q I NTRACTOR (Circle one) Date I . This permit was issued ba$ed on the information provided in the permit application and accompanying plans and specifications and is subject to the compliance4ith those documents, and all applicable statutes, ordinances, regulations, policies and procedures. 2. This permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and receivedior to the date of expiration. An extension of no more than 180 days made be granted at the discretion of the Chief Building Official and' may be subject to a fee equal to one-half of the original ermit fee. 3. if this permit expires;,a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard requirements, fees androcedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of the Chief Building Official and is not guaranteed. 4, No work of an manner shall be performed that shall results in a change of the natural flow of water without prior and specific approval. 5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all required inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services Division. 6. The issuance_orgranting of a permit shall not be construed to be a permit for, or an approval of, an violation of any provision of any applicable 4odefir any ordma> ice ox regulation of this jurisdiction. Approval of work is subject to f any inspection. Signature of Chief Building Official Date REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. Ctistt niur Name, Jab LocatiOtl: Contact Numbers $.IR:tLt'P tC ' Carrier d-7"Rn7lat109 L,LC pr 1.0cGktjojl. Prices incl 1)Rtk'R; WA x dF that reylisrmelrrvo-y ac Caciiow AP initial 41 Trac faff 67W vi%h arca (} &Plaar glltztialF,,A% overlay 70 6" o"& 1P .4 411. QPM f i Xatstal) *100ard ridgy C ISWtx I 'Ito P1411ta)cit�liQ,. of Ro-R'9esh ( ) uw.a:m y} lifettt�'Ek ee3i crsa�h.1 min F1 CC` Ri'1sRt11t iae Haid wilt Inglaitpre-PeiW4d. SLtbw'J"otal1$ that tete scope of not covered by the SCOPE OF ENSOt ANCA insurance Wi-l"Pe responsible to s* �� �t.7 Dffi�aallalg x,Z.t X't3T.140MEtYrPi NER CLAIM }.XALSFR:tN D d-7 t poling i,l.t:, ab. 1x1 your }Ampterty. f.�hCUtRatC' Deaver .. 54�i1 X.i7octybo J1. Dvrivea,isE:} ', Bft'�i4 Ux?rca: 30.?-'15K•764;i 4'ss' 36i!•75tx-7G<rs SpravaHd•: ("%:a�lrm>0 'trT.a�q-7va� t:otersd<1 "i}3rFuprk .:ar I,? C`9wr:Ztnr: kr"s F<are4:elRiogx.. �a1>K.c-ai3etBsAle MtR. Jrnt�(i'diiva,.CtTRow2f.4")q-'rv'1»3Sti3 vsn,;,i}'tgcrit:,:?t� SAt4 (,sL-e i;.ta+• . 3c�a w caro s. ,�teix R.nsta c_nr, a.t i' a.ttza aa�TR-5vo.?nils? r- _.._..�._.:...,._.._ . Claim C4FPf:CZ i`IX:10e: - rolling . a f the Jab poscs to providf: all inaterlal.s, tabor and ei}ui Qa: all applteabte salmi tars, 9:Icata^EtkJ v rear�l.,(1� t)" tievul of � azs��rt dPr rCD�FRRLse la��,�',�� shirts of Serrvere ae c�tra<a.n t� �Y Esc F(N(� �a:e r w,a 5 C. �i�� T3:t -1:1119:, ref esY: ...__.:..,._.,.,._........... rs o! eTsirtti�s� rsx;liisg i Lrxstm.11,V I11 v#�_Dnc;t4'mrro yaaa>;e Stgort saal'6ar }'fix, p,.ytatss, A:tat�Ia drsav inRB 'SO,EttX 11a¢ D D Gutic'rand Li wnapgw 4:vkTr..... gdl. jl—........, _ � ilalAtealt fl.lelt f��,9� avdr DJxr lu?}g!�u 9Citi P�l Shingle Sty ;i$d {YpRRey� °�i41.A�1E''E:41.laM tt rkC�}1T F{tax$tC5 .�6�7 t..Iactlii OW iEt1185 RTk,+taribeaRsxtsa�go` � T fdll,�sl At.raxlAh xira®Yi¢r; dear vept 11,cirxtW l )cllinat>:y (D.2utmrworkmaOA4; WatrAnty d: M*;**tis S%%,m P of the properay 1d an; i:iuit,tcad4'sraormnty uadsbltivatml toes apply [� as}l; PiRemw vaut. lZee�hmgi W nivut all applia:mW Code requir;r aeaTt3a FittielFi at (X "ves i. uasltoys { } ari6 .roes a!" t�eyaxireci xr)Sitatea4{l,pabieettxial julrlteeaSoltalXtptR+:abla:exoderegxxa.s�oxaKltta.C;Gtta�=,_�����a�-.__ �c � � ..�� ra.a� Ii4stir��ee.etait�a 'f1t114Sliril priEsr tAa.$t�ouctzXs. c, LAlm A& � �Ta-azA�s d.-7 f�v�Xrlrlg LLC to repressycaatr interests end +��®�t9�tea d9'isldc�$1�a3 t#a19�rt� to ensure +cork will be repaired or teglarecl with NO ADDITl£]ial6ll.OAST beY your .e3e0actible. Any items customer's-irisurartcie Carftef *b x the cWttamur a aq rests wiEl be bfbf¢ti sep9rtetely. thf5 ttgr6errtmala is, f4xrtaxm RILL 0LACEMENT C05T P9tClWDS, sf)ClUding SUp fnents: The final' price. $igre4 d Llpo tl between the Y and d.•7 hoofing LLC shall become the final contract 9`iT1ouFjt ,Arhit,c1 you, tha Costorner, will be we pa�finent to 7 Roofing LL.0 upon installation Of mate;`121s. - a r not moka p4js>°aa�r44r. lt�sasn rls�t�roxc �sds c.y'SnyY¢z�r9y aAaMl axsuaa@rpt fsArt Ow @c7� o:aAnrtt (Say, w4ive of rebpixil shay rxyrtion *faw uastiialnce (k-Atctih.le in peri (4 iii va�h41lo •� t«ta�itMl�+r hisisalx, l 4AY WITHDRAW 'd til5 C'.();'iTRAC'T' W117HI D 72 IIC3trRS r�%'C1 kL RFSC�;s�'tAtC NQcRCS THAT .t' In tru$t MY P161VATICrit received f ruan yrata Unlit tk+i.tvvey (if nw4tt~Ws ttstlsst"jtabsitx or pimrNfilliaaca Of tbl! kWoOk X'IXDS k'f4( F'E)`3i L7 -P C.I�S• SPECIPICA,'C'XC NS .a4 XD '1"F;01S AND CONDITIONS AAF D MhU `iATB,�F'A.CTORLY AND AQCF'X''rFD DY SIC3NAT URMX 0 1,4)W T.,'3'HE (t?.S TCi)y FA. AVT'!•XS RIZF" dw7 �.GSO T?wt) I. R.s' "1'e) "Rtd}f,:Ft,i31�t'eFY [aA XIM ta7 iSrfLl_!9 MADER)R A (Iv C F� R OSx) ABOVE , t i� T"<t3ti #1 Milk BACK l %:S i�tY il'i3ii ialL tS a4 ll)t WKS PR:'iAi'l'R?f)QN Ti s 5tXa�CAi 't'RtI. .tAaC3Xt[� ME I t-as5Pa8Yser €sti isRat; ,.» � CUSTOMER Si ,NATURE,.._ .------- _ DATE Ll Z. SALES REP SIGNATURE: FBF: � 1/ ' Z D AC'C"EP'rPD HA RiNT:.........., _ . ....... .._.,,_ .._...._�a�TE_.. .._.......__...,._._.__._. Ai •p,L,vr .:. 640 1 1V- 6 qzn. Kimberly Cook From: no-reply@ci.wheatridge.co.us Sent: Monday, November 27, 2017 2:48 PM To: CommDev Permits Subject: Online Form Submittal: Residential Roofing Permit Application Residential Roofing Permit Application This application is exclusively for new permits for residential roofs and for licensed contractors only. This type of permit is ONLY being processed online --do not come to City Hall to submit an application in person. Permits are processed and issued in the order they are received and due to the volume of requests, time to process varies and is subject to change. YOU WILL BE CONTACTED WHEN YOUR PERMIT IS READY FOR PICK-UP AND WILL BE GIVEN A SPECIFIC DATE AND TIME WINDOW TO COMPLETE THE TRANSACTION. You will be notified if your contractor's license or insurance has expired, and you may update those documents at the time you are issued your permit. i" For all other requests: Homeowners wishing to obtain a roofing permit must apply for the permit in person at City Hall. Revisions to existing permits (for example, to add redecking) must be completed in person at City Hall. All other non -roofing permits must be completed in person at City Hall. The Building Division will be open from 7:30-10:30 a.m., Monday through Friday to process these types of requests. THIS APPLICATION DOES NOT CONSTITUTE A PERMIT. DO NOT BEGIN REROOFING UNTIL PERMIT HAS BEEN ISSUED. Is this application for a Yes residential roof? How many dwelling units Single Family Home are on the property? �1 PROPERTY INFORMATION Property Address 3615 Teller St � Property Owner Name Caroline Mallory Property Owner Phone 303-949-1900 Number (enter WITH dashes, eg 303-123-4567) Property Owner Email Field not completed. Address 17 Do you have a signed Yes contract to reroof this property? Applications cannot be submitted without an executed contract attached below. Attach Copy of Executed 3615 Teller St Signed Proposal.pdf Contract CONTRACTOR INFORMATION Contractor Business d-7 Roofing LLC Name Contractor's License 090242 Number (This is a 5 or 6 digit number for the City of Wheat Ridge) Contractor Phone 303-758-7663 Number (enter WITH dashes, eg 303-123-4567) Contractor Address 5470 Lincoln St (Primary address of your business) Contractor Email Address vance@d-7roofing.com Retype Contractor Email vance@d-7roofing.com Address DESCRIPTION OF WORK TOTAL SQUARES of 37 the entire scope of work: Project Value (contract 23,630 value or cost of ALL materials and labor) Are you re -decking the No roof? Is the permit for a flat Pitched roof (2:12 pitch or greater) roof, pitched roof, or both? (check all that apply) 18 What is the specific pitch of the PITCHED roof? How many squares are part of the PITCHED roof? Describe the roofing materials for the PITCHED roof. Type of material for the PITCHED roof: 6/12 37 Archetectual/dimensional asphalt shingles Asphalt Provide any additional Roofing house and Detached Garage. detail here on the description of work. (Is this for a house or garage? Etc) SIGNATURE OF UNDERSTANDING AND AGREEMENT I assume full Yes responsibility for compliance with applicable City of Wheat Ridge codes and ordinances for work under any permit issued based on this application. I understand that this Yes application is NOT a permit. I understand I will be contacted by the City to pay for and pick up the permit for this property. I understand that work Yes may not begin on this property until a permit has been issued and posted on the property. I certify that I have been Yes authorized by the legal owner of the property to submit this application ..... .... . 19 and to perform the work described above. I attest that everything Yes stated in this application is true and correct and that falsifying information in this application is an act of fraud and may be punishable by fine, imprisonment, or both. Name of Applicant Vance Manzanres Email not displaying correctly? View it in your browser. 20 +11'1 1-1,nflil�� 'NS 646WRECORD Cq 6e- LA v�o�f 1-( INSPECTION BEQUEST LINE: (303) 234-5933 Occupancy/Type Inspections will not be performed unless this card is posted on the project site. Call the inspection request line before 11:59 p.m. to receive an inspection the following business day.** Inspector Must Sign ALL Spaces pertinent to this project Foundation Inspections Date Inspector Comments Initials Pier Inspections from these entities should be requested one week in advance. For landscaping and parking inspections call 303-235-2846. For ROW and drainage inspections call 303-235-2861. For fire inspections contact the Fire Protection District for your project. Concrete Encased Ground (CEG) Foundation / P.E. Letter _ Do Not Pour Concrete Prior To Approval Of The Above Inspections Underground/Slab Inspections Date Inspector Comments Initials Electrical Sewer Service Plumbing Do Piot Cover Underground or Below/In-Slab Work Prior To Approval Of The Above Inspections Rough Inspections Date Inspector Initials Comments Wall Sheathing Inspections from these entities should be requested one week in advance. For landscaping and parking inspections call 303-235-2846. For ROW and drainage inspections call 303-235-2861. For fire inspections contact the Fire Protection District for your project. Mid -Roof Fire Inspection / Fire Protection Dist. Lath /Wall Tie Final Electrical 2-2-i -1-1 Rough Electric * Final Plumbing _ Rough Plumbing/Gas Line _ 22 i -- / Rough Mechanical Roof Rough Framing Final Window/Doors Insulation Final Building Drywall Screw/ Nail NOTE: All items must be completed and approved by Planning, Public Works, Fire and Building before a Certificate of Occupancy is issued. Approval of the Final Building inspection does not constitute authorization of occupancy. Final inspections Date Inspector Initials Comments Landscaping & Parking / Planning Dept. Inspections from these entities should be requested one week in advance. For landscaping and parking inspections call 303-235-2846. For ROW and drainage inspections call 303-235-2861. For fire inspections contact the Fire Protection District for your project. ROW & Drainage / Public Works Dept. Fire Inspection / Fire Protection Dist. Final Electrical 2-2-i -1-1 13 -a Final Plumbing Final Mechanical 22 i -- / L� Roof Final Window/Doors Final Building NOTE: All items must be completed and approved by Planning, Public Works, Fire and Building before a Certificate of Occupancy is issued. Approval of the Final Building inspection does not constitute authorization of occupancy. *For low voltage permits — Please be sure that rough inspections are completed from the Fire District and electrical low voltage by the Building Division. **For Inspection Time Window Requests — Please email insptimereguest(a)ci.wheatridge.co.us by 8:00 A.M. the day of the inspection with the property address in the subject line of the email. Occupancy Is Not Permitted Until A Certificate of Occupancy Is Issued Protect This Card From The Weather i CITY OF WHEAT RIDGE Building Inspection Division / (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type: e r-1, A T I Job Address: 36 fs i G[ 2 sr Permit Number: 2 o/-740009 6 fe -?IGce 'r-)A?,010("9 ❑ No one available for inspection: Time 10 AM/PM Re -Inspection required: YesNo *When corrections have been made, call for re -inspection at 303-234-5933 Date: 2'2pIns ector:4Ajy__ DO NOT REMOVE THIS NOTICE 41 CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type: i Job Address: 7 Permit Number: t 7 006f f fir. rc $e' C-1 1E' C, e o vtei �j, tJ e, J;' 4 r VV e C '%'I = f epi / c _1 ❑ No one available for inspection: Time A /PM Re -Inspection required: Yes No When corrections have been made, call for re -inspection at 303-234-5933 Date: Inspector: ". r DO NOT REMOVE THIS NOTICE City of Wheat Ridge Residential Mechanic PERMIT - 201700098 PERMIT NO: 201700098 ISSUED: 01/24/2017 JOB ADDRESS: 3615 Teller ST EXPIRES: 01/24/2018 JOB DESCRIPTION: Install Gas line and gas insert into existing wood burning fireplace *** CONTACTS *** OWNER (303)918-2716 MALLORY CAROLINE SUB (303)935-1617 Ronald Florez 022421 Florez Heating & Gas Works *** PARCEL INFO *** ZONE CODE: UA / Unassigned USE: UA / Unassigned SUBDIVISION CODE: 2405 / BARTHS, COULEHAN GRANGE, WHEAT BLOCK/LOT#: 0 / *** FEE SUMMARY *** ESTIMATED PROJECT VALUATION: 2,600.00 FEES Total Valuation 0.00 Use Tax 46.80 Permit Fee 93.35 ** TOTAL ** 140.15 q *** COMMENTS *** *** CONDITIONS *** Installation must comply with manufacturer specifications and meet EPA Phase II or Colorado Phase III certification requirements. All work is subject to field inspections. All work shall comply with applicable codes and ordinances and is subject to field inspections. I, by myy si nature, do her attest that the work to be performed shall comply with all accompanying approved plans and specifications, applicable des, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized by th al owner of he pp.e�ry and am authorized to obtain this permit and perfor the work described and approved in conjunction with thi er t. I furth att at I am le ally authorized to include all entities named thin this document as parties to the work to be r or a rmed is disclosed in this document and/ori accompanying approved plans and specifications. mature of OWNER or COCTOR (Circle one) Date ' 1. This permit was issued based on the information provided in the permit application and accompanying plans and specifications and is Subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures. 2. This permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and received prior to the date of expiration. An extension of no more than 180 days made be granted at the discretion of the Chief Building Official and may be subject to a fee equal to one-half of the originalpermit fee. 3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard requirements, fees and procedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of the Chief Building Official and is not guaranteed. 4' No work of any manner shall be performed that shall results in a change of the natural flow of water without prior and specific approval. 5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all required inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services Division. 6. The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, any violation of any provision of any applicable code or ani, dinatice or gulati o this jurisdiction. Approval of work is subject to field inspection. Np Signature of Chief Building Official Date REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. Inspection time requests will be accepted by email only. Please email requests to insptimerequest@ci.wheatridge.co.us between 7:30am and 8:00am, the morning of the inspection. Please put the address of the inspection in the subject line. City of W heat Ijdge COMMUNITY DEVELOPMENT Building & Inspection Services Division 7500 W. 29`h Ave., Wheat Ridge, CO 80033 Office: 303-235-2855 * Fax: 303-237-8929 Inspection Line: 303-234-5933 Email: permits .ci.wheatridge.co.us 1 FOR OFFICE USE ONLY Date: Plan/Permit # �'u 0o0q Plan Review Fee: Building Permit Application *** Please complete all highlighted areas on both sides of this form. Incomplete applications may not be processed. **" Property Address: J 7 r Property Owner (please print): �/4� %� Zl/' �� Phone: Property Owner Email: Mailing Address: (if different than property address) Address: City, State, Zip: Architect/Engineer: Architect/Engineer E-mail: Phone: Contractor: Contractors City License #: Contractor E-mail Address: Sub Contractors: Electrical: W.R. City License # Other City Licensed Sub: City License # Plumbing: W.R. City License # Phone: Other City Licensed Sub: City License # Mechanical: W.R. City License # Complete all information on BOTH sides of this form ❑ COMMERCIAL ❑ RESIDENTIAL Description of work: (Check all that apply) ❑ NEW COMMERCIAL STRUCTURE ❑ ELECTRICAL SERVICE UPGRADE ❑ NEW RESIDENTIAL STRUCTURE ❑ COMMERCIAL ROOFING ❑ COMMERCIAL ADDITION ❑ RESIDENTIAL ROOFING ❑ RESDENTIAL ADDITION ❑ WINDOW REPLACEMENT ❑ COMMERCIAL ACCESSORY STRUCTURE (Garage, shed, deck, etc.) ❑ RESIDENTIAL ACCESSORY STRUCTURE (Garage, shed, deck, etc.) MECHANICAL SYSTEM/APPLIANCE REPAIR or REPLACEMENT ❑ PLUMBING SYSTEM/APPLIANCE REPAIR or REPLACMENT ❑ ELECTRICAL SYSTEM/APPLIANCE REPAIR or REPLACEMENT ❑ OTHER (Describe) (For ALL projects, please provide a detailed description of work to be performed, including current use of areas, proposed uses, square footage, existing condition and proposed new condition, appliance size and efficiency, type and amount of materials to be use d, etc.) K- Sq. Ft./LF Amps Btu's Squares Gallons Other Value: (Contract value or the cost -of all materials and labor included in the entire project) OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this permit application are accurate and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance with applicable City of Wheat Ridge codes and ordinances for work under any permit issued based on this application; that I am the legal owner or have been authorized by the legal owner of the property to perform the described work and am also authorized by the legal owner of any entity included on this application to list that entity on this application. I, the applicant for this building permit application, warrant the truthfulness of the information provided on the application. CIRCLEONE: (OWNER) (CONTRACTOR) or (AUTHORIZED REPRESENTATIVE) of (OWNER) (CONTRACTOR) Electronic Sienature (first and last name): ZONING COMMMENTS: Reviewer: BUILDING DEPARTMENT COMMENTS: Reviewer: DEPARTMENT USE ONLY DATE: OCCUPANCY CLASSIFICATION. Building Division Valuation: $ Design Features • Clean Face Look—No Louvers • SIT Valve 820 (Standing Pilot) • SIT Valve 885 (IPI System with Remote) • Glass Size: 171/2" x 193/4", 3451/2 in, • High Definition Log Set • 150 CFM Room Fan (with variable control) • Limited Lifetime Warranty • Quick Access Valve Controls iL�;JIJ� � trr7�rd - 1'�IFa �=�rr1 ::1�t �tlrt J Available Options • Remote or Thermostat Control • Coal, or Log Set Burner • Liners Options: - Brick Liner with Logs -Porcelain Liner with Glass or Logs - Ledgestone Liner • Surround Options: -Minimal Surround - 4 -Sided Minimal Surround - Modern Stainless Steel Surround -Trimmoble Surround Fireplace Details Model BTU Maximum Input BTU Minimum Output Heating Area Steady State Efficiency Min. Insert Dims. Q1 20,000 BTU 7,900 BTU 1,100 ft, 76% 20'/4"w 14'/4"d 271/2"h I City of Wheat Ridge Residential Addition PERMIT - 201600109 ?ERMIT NO: 201600109 ISSUED: 02/19/2016 JOB ADDRESS: 3615 Teller ST EXPIRES: 02/18/2017 JOB DESCRIPTION: 800 sf addition to existing home and upgrade existing finish 1,484 sf. Installation of 960 sf detached garage. **Install 30,000 btu Archgard fireplace and venting. t** CONTACTS * * * OWNER (303)423-0341 3C (970)213-1185 3C (303)598-3963 3UB (303)286-7644 3UB (303)917-7881 3UB (303)935-1617 MALKET PARTNERSHIP Dan Cantu Larry Whiting Boe Kampbell Michael Miller Ronald Florez 110048 Sierra Vista Electric, LLC 160017 All Seasons Construction LLC 020801 Eastside Heating 160032 Mountain Plumbing & Mechanical 022421 Florez Heating & Gas Works t** PARCEL INFO *** ,ONE CODE: UA / Unassigned USE: / SUBDIVISION CODE: 2405 / BARTHS, COULEHAN GRANGE, WHEAT BLOCK/LOT#: 0 / `** FEE SUMMARY *** ESTIMATED FEES Cotal Valuation 0.00 ?lan Review Fee 1,071.23 Jse Tax 3,304.80 ?ermit Fee 1,673.85 t* TOTAL ** 6,049.88 ** COMMENTS *** PROJECT VALUATION: 183,600.00 t** CONDITIONS *** JJ: Approved per plans and red -line notes on plans. Must comply with 2012 IRC, 2014 NEC and all applicable City of Wheat Ridge Municipal Codes. Work is subject to field inspections. LR: As part of the foundation inspection and PRIOR to the first framing inspection, a completed, signed and sealed, Foundation Setback and Elevation Certification shall be submitted to the City for review. The certification form shall be fully completed by a Professional Land Surveyor licensed in the state of Colorado, stating that the foundation was constructed in compliance with all applicable minimum setback and elevation requirements of the City. For one- or two-family dwellings, the first twenty-five feet (25&#39;) of driveway area from the existing edge of pavement into the site shall be surfaced with concrete, asphalt, brick pavers or similar materials. A right-of-way permit may be required; contact Public Works Department at 303-235-2861. No new driveway shall be permitted to the proposed garage, access shall remain from the existing horseshoe driveway. A new driveway shall be allowed if the existing is removed. City of Wheat Ridge Residential Addition PERMIT - 201600109 ?ERMIT NO: 201600109 ISSUED: 02/19/2016 JOB ADDRESS: 3615 Teller ST EXPIRES: 02/18/2017 JOB DESCRIPTION: 800 sf addition to existing home and upgrade existing finish 1,484 sf. Installation of 960 sf detached garage. "Install 30,000 btu Archgard fireplace and venting. by my signature, do hereby attest that the work to be performed shall comply with all accompanying approved plans and specifications, ipplltcabble building codes, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized )y the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with hispermit. I further attest that I am legally authorized to include all entities named within this document as parties to the work to be )ertbaat all work to be pTat is disclosed in this document and/or its' accompanying approved plans and specifications. JCAG� ;ignature of OWNER or CONTRAC R (Circle e) Date . , This permit was issued based on the inform rove ed in the permit application and accompanying plans and specifications and is subject to the compliance with those documents, and a 1 applicable statutes, ordinances, regulations, policies and procedures. This permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and received prior to the date of expiration. An extension of no more than 180 days made be granted at the discretion of the Chief Building Official and may be subject to a fee equal to one-half of the originalpent fee. 1, If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard requirements, fees and procedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of the Chief Building Of t-ccial and is not guaranteed. 1, No work of any manner shall be perfonned that shall results in a change. of the natural flow of water without prior and specific approval. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all required inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services Division. The issuance or granting of a pe it shall not be construed to be a permit for, or an approval of, an violation of any provision of any applicahle ggde or any ordinpncAor re&latiop of this jurisdiction. Approval of work is subject to field inspection. ;ignature of Chief Building Official — Date LEQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. 06-08-'16 14:49 FROM -fireplace outlet sup City Of WheatRl1 COMMUNITY DEVELOPMENT Building & Inspection Services Division 7500 W. 291' Ave,, Wheat Ridge, CO 80033 Office: 303-235-2855 . Fax, 303-237-8929 Inspection Line, 303-234-5933 Email: Perm its(ci)ci.whftajridge.co.us 303-935-5001 T-158 F0001/0003 F-566 FOR OFFICE USE ONLY Date; Plan/Pennit # -v Fee: Plan Re - 4 Building Permit Application Aiw P ow J. .... ....... wii 3615 TELLER ST CHARLOTTE KETTERING 303-949-1900 P (please pri*. w NA (if different than property address) Address: City, State, Zip: FLOREZ HEATING & GAS WORKS - Fg 022421 P>t.......... . � 303-935-1617 0. M-1,104 CAMHANK@AOL.COM to dr' S: suoziowadom Electrical: Plumbing: Mechanical: W.R. City License # W. R. City License# W.R. City License Other City Licensed Sub: Other City Licensed Sub: City License # City License # Complete all information on BOTH sides of this form 06-08-'16 14:49 FROM -fireplace outlet sup 303-935-5001 T-158 P0002/0003 F-566 p&''ad (Check all that apply) ❑ NEW COMMERCIAL STRUCTURE ❑ ELECTRICAL SERVICE UPGRADE it rrr)KAMFR(:IAL ROOFING INSTALL MANIFACTURER "ARCHGARD" MODEL AND VENTING, NO GAS LINE INSTALLED BY US Sq. FtJLF Btu's 30,000 Amps Squares "BRIGANTIA PERFECTION 35" FIREPLACE Gallons 1411-im B7 (Contract value or the cost of all materials and labor included in the entire project) 54500 OWN-ER/CONTRACTOR SIGNATURE OF UNDERSTANWING AND AGIEi£E111�NTOr I hereby certify that the setback distances proposed by this permit application are accurate and do not violate applicable ordinances, rules made e regulations of the Cin of Wheat Ridge or covenants, casements or restrictions of record; that all measurements shown and allegations are accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility far compliance with applicable City a£ 1t heat Ridge codes and ordinances for wrork under any permit issued based on this application; that I am the legal owner or have been authorized by the legal owner of the property to perform the described work and am also authorized by the legal owner of any entity included on this application to list that entity on this application. 1, the applicant for this building permit application, warrant the truthfulness of the information provided on the application. C*t"i4� (pci'NER) (COM'RACTOR) a (A(,7ifOR1ZED REPRESENTATIVE) of (OWNER) (CONTRA , P; 06/09/1 ✓� I understand that checking this box, that I acknowledge that this constitutes a legal signature. ... ...... ,. ,.v,...,,, tit :��r�r,+�,» YV;i5/ tNAi•71":�Riia''4'k7J';h'hl'h� Building Division Valuation; S 06-08-'16 14;49 FROM -fireplace outlet sup 303-935-5001 T-158 P0003/0003 F-566 i CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type: RC_; f ,4E F ;I P1 F i/ i m Job Address: 3 t l S" Tr 114 01 S t Permit Number: G / C ® / C; 9 X00 ❑ No one available for inspection: Time �AM PM Re -Inspection required: Yes No ' When corrections have been made, call for re -inspection at 303-234-5933 .4 ' Date: Inspector: DO NOT REMOVE THIS NOTICE ca - "y O�QQIW .N ;5A V? 1 ity of WTiewRiidgc Neturnicipal, BuildHin,7-500 V1 W An, WWI Ridge, CO 800334001 P: 3032351846 P 3032352857 F01-M)ATIONN SETBACK AND MEVATTO'N CERTIFICATION This lbmna including Q Exhbit on die reverse side, must be fully completed by a Profiessional. Land Suneyor licensed in the State of'Colorade, TV WMEwbon must be submitted for review and apptoval prior to the MRST FRA -MING INSPEC MONand before proceeding with ary further BAIT: 0214710 lei ker. . INY ,, no A q� Mq of to swwyw,,�, :'�, ": -,, data . W, nweshed b V nw iw dw.0y UM kr iny Mqwn4sh" 11C ownwown. x. ."r, V d X, ANY —whemen, and J ,..iii:` wnheknp nmi y WTANCaa, norr the progrqGn,Ns havz Wan dawknud to W, )0 1 A A; 5" atm w 1155 Thu X& w Q U wi A 1 T X&� # ,0U uo 'be' � -NAA;D83,', 01 dheye tbe C%"k Ono ont Top of Wutidauoi� pr iow to p1lacennent of concrett, I# ofprn�.x,,sera foundation subsequent to pla=mnent of concrz,,tc, The seback and zli;r, iu',,00, inez urement locadons are idimtffiied on the xUached exhibit ""ignw'd, losteta �%J%111111111 1% ,CSS? Rq FOR OFFT E USE CALY A d % W: 25933 0% 1 D arte 1k, z- LANV I It", R. U/1 2 Date. Plan1permito t")�v, I ", C -I Plan Review Fee: PrOPerty Owner Emall- C) Q,. 4 Address* L� r) N*AIN.A.. Sub Contractors: Electrical: Sle-r(-,A vl�� W.R. City License# 0vi;tje_ MIRf IK A V - I Plumbing: MWO-m.) Pf ttvl)� t Mch.,,i..l: 1-1--�ct4., iy- )r W.R. City LicenseA4WI riftu WR City License # 1:MR, - 190 Other City Licensed Sub: City License # Complete all information on BOTH sides of this form 113, 1, of w(ok ,, (Goh(-cA all ih;,"A a'pply) NI.7,,W ELI 0" I'R I CAt r--- R V I G E' IJ ['�'A D E NEW RESIDENTIAL( STRUC"I'URFE', cOMMERCIAL ROOFINC, COMMER IAL ADDITION RESIDENTIAL ROOFING RESDENTIAL ADDITION WINDOW REPI-ACEMENT COMMERCIAL (Garage, shed, deck, etc.) RESIDENTIAL ACCESSORY STRIX TUR[:�, (&)rage, shed, deck, etc-) MECHANICAL SYSTEM/APPLIANCE REPAIR or RE[ILACEMENT EJ PLUMBING SYSTEM/APPLIANCE REPAIR or REP LACMENT ELECTRICAL SYSTEM/APPLIANCE REPAIR or REPLACEMENT OTHER (Describe) �Vl C, , -�L ox - (For ALL projects, please provide a detailed description of work to be perf6fined, including eUrfent use of areas, proposed uses, square footage, existing condition and proposed new condition, appliance size and efficiency, type and amount of materials to be used, etc.)V- JeNtI.el (,4Neo SqFULF Stu's Gallons Amps Squares Other NEW COMMERCIAL P w w ELECTRICAL SERVICE UPGRADE NEW RESIDENTIAL STRUCTURE COMMERCIAL ROOFING COMMERCIAL RESIDENTIAL RESDENTIAL ADDITION WINDOW REPLACEMENT 'COMMERCIAL ACCESSORY STRUCTURE (Garage, shed, deck, etc,) RESIDENTIAL ACCESSORY STRUCTURE (Garage, shed, deck, etc.) MECHANICAL ,a SYSTEM/APPLIANCE wPrt i w *,w REPLACEMENT M 1'i. PLUMBINGSYSTEM/APPLIANCEREPAIR aR. REPLACMENT ELECTRICAL * aww: y CE REPAIR REPLACEMENT a Sq» FtJLF Btu's ty"o Gallons Amps r" Squares Other Projed Value: (Contract value or the cast of pLmaterials and labor Included in the 9DItM prefect) OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed # applicable ordinances, regulations of the City of Wheat Ridge or orrestrictionsof •; that all measurements shown and allegations made Buildingaccurate; that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance with applicable City of Wheat Ridge codes and ordinances for work under any permit issued based on this application; that I am the legal owner or have been authorized by the legal owner of the property to perform the described work and am also authorized by the legal owner of any entity included on this application to list that entity on this application, Lei Vill WC-1-ty, of .�M► AUTHORIZATIONC ct 110A OMMUNITY DEVELOPMENT Project Contractor: y Address: General 10 M y } Company Name:Phone 7 State * Master k Signature „ Authorized A w r Company Name: `s ig ,s= .' % �" �� � $ � � � : Phone #: f State License #: Master #: Wheat Ridge License Signature of Agent Mechanical Company Name: Phone - Wheat Ridge License #: 0A D 90 t Signature *♦ Authorized y. y ♦ i:. Date ii 1711tJo f E x ^ i y t M y §+,'��1'fi»..: $, „w+ nq } _ : { f� !~ 4 �' ^ �) Y � d °i i t y f f —✓. { ,� � � �..� v" � 3 J tR v .0 k " A.� R 8 �4 ?,»,. � F f WARAX110TY DEED THIS DEED, m da this 14thduy or Amt '19 5 betwovo of s8na County of J7 if f erson Saste orc6omft yram *0d t-xIMT Partnership whose taxi address it 365 Tell t -Wheat Ridge, Colorado $0033 �Uote� lyiftif, sod Was in the County or Jefferson, Suite or coloraft county ofJefferson, state of Colorado 3615 Teller Street, Wheat Ridge, Colorado 80033 408803 led the mv And her self her heirtisw por"MA) rtsm"Colvisivm does if 4htjff*ft(*K* for its how and stsslivits, that N't the tives of Ow 90001148 *ad thdittery ot "we pmvvis� �`o Wine the ifmoffit4 It �dhas pod riot, ruff power *rA susbuidisr to itraos, toir0n, stli and cowitst the IMM in Menu" A44 JbM Its win WARRANT AND .. • the Premises to mito qokt vto istuto"Nt Possession WJUS 14. IMISM STATE O9 COLORADOy{ j ai> rover of Jeffersonj[ Atte forelvi"f anstrutx am was ackoowdedted b1forc me this 14 a dag or AL1: '1996 ur DORIS tai. n3amn p My tmasittsion niur a � 2.0'0 t> Witness racy fiend and offiviat s L Nta< 032. Rua.. 4-94. V, Rnnrxe' lin, tear "w.6a 1 pra Saatng, t99S St., BdtSnx w.. dBitSt'•92�S�S «— Leg# Description Provided b tomer LOT , k4 I HFTIRE NT Cdr QTY SUBDVISM, COLNTY OF EFFERSON, STATE OF COLORADO. OR .. LOT 3 M E # # t Aso m I� x U1 --4 X M m CC = Covered Concrete r-` ° - Corcrate x x = Fence .. ;.: #.#,. a «... # # R • ♦ # R # 6, R M I ,Alew Ridge Water District Home Page Nisirmss Houm Flaymsqt Mothod5 I Water Rostoctiont I'Xe6scopo Plant WO Soff Amoriftent I ! uniine Oymis FAQ O015 Rate Schadtiv, You may acwts our b3aZmrtaCy r here IM, fig M�- Ofte phone- 303424-29" Fax 303423-9462 P - p. pi th- k t Zll Id =11 Ck -b"arc ZZZI,66 B&—WReUt ?gL-ts tL Wt MoAmtS oftAW nitpupdLom & j M9MQVj±W httn-//www.wrwdiqt,ric,t,.com/ 1/18/2016 eA �r � -724D ter m g d" � 4 �i Wheat Ridge Water Proof of Submission - christappco@gmail.com - Gmail Page I of I VVRW Proof of Submissrorri.pdf Open with Chris Compost firbox (3) Starred Sent Mail Drafts More i Uq i, k' t k /H -,i e V I Chris A cc'py tj thtwwrn"mt hk., torn'Act*'d is t6z.-'rl ,.,J,czte ¢o,E Nwt SuabrnftttO ch�zckw' rc'r rft I b is p!oject type and 4c aitschtd to tIrw t,,64ng Pernit ApMicw',;',n at ha' ti , tai su m P,�'m, A;r;,4sfw,iwe presented "of sobrnsson waho, vr.,w'npk-ec� "'mor of hem fro,,,, t, agenoy w4! nvt be iwceoed v, proc"see, p,r ojec" I'd4few ...... .... Naff"O or skgbrmt",ng do-'wrnrants. tor4ect 1 No racer Start a I I Signature of Firm RepresaroaVvc or In:Vvidusi, T W E ,am a &h suthorized rvp4rtserdahva of the e re"'O."'Pt of docurrivnis necessary tr6cm below age'do, by my ; fix rewew, and apprarva; of the project insitcated above, A2WYxJAWAVAfiA& Inua, Oaak om) V 0 Wheat Pi M. Fitt, Proterrtion cs Wheat Ridge Sarvitatkin District o, Arvada Fire Protection ck--rx ("'tsk' sanitation District 'q woobt iindge Water District Frmadole Saratatiori District o Corrsisfideted Muturit Woter Disfrict o Wesindge Swrviation Dm. a Vahey Water Diticrict Other Denver Winter Agency Rinses: q& 77�N C- -t-7 -z si2natut Dew https://mail.google.com/ma,il/u/O/?tab=wm 1/26/2016 From: Patrick Roberts <PRoberts@martinmartin.com> Sent: Friday, January 22, 201612:1 PM To: Tapp, Chris Cc: choc489@hotmaii.com; Bill Willis; Peter Everest, Sue Matthews, - info @wheatridgesanitation.com,- David Sebern Subject: RE: Emailing: Teller 111615.pdf ® 3615 Teller St. Attachments: WRSD - Proof of Submission - 3615 Teller Street.pdf SM Please find attached proof of submission for the City of Wheat Ridge indicating the discussion regarding coordination with Wheat Ridge Water on the size of the water meter in relation to the additions planned for the new single horne, d h k oi f Ner s i cong ion "=Q66ewer service occurs. observation U� Patrick Roberts, PE, CCM Project Eng�t�_�Prf�d�_C. �jtion�_Managgjr_P E-Ul LL- . Martin/Martin, Inc. 12499 W. Colfax Ave., Lakewood, CO 80215 P) 303-431-6100 Ext. 353 www.martinmartin.com ----- Original Message ---- From: Tapp, Chris mailto:Chris.Ta PPROBUILP.COM J Sent: Wednesday, January 20, 2016 454 PM To: Patrick Roberts <PRobertsftmartinmartincom> Cc: choc489Photmailcom Subject: FW: Emailing: Teller 111615.pdf - 3615 Teller St. Hi Patrick, Attached are the building plans for the addition/remodel at 3615 Teller St. in Wheat Ridge. The final plumbing fixtures/fittings have yet to be selected. Let me know if these selections are needed. There will be a detached garage to be built in the near future. There will be no plumbing in the detached garage. Let me know if you have other questions or need additional information. Thanks, ----Original Message ----- From: Tapp, Chris Sent: Monday, January 18, 2016 12:42 PM To: ba.rrvCr,_Dwrwdistrict.com Subject: FW: Emailing: Teller 111615.pdf - 3615 Teller St. 2� Attached building plans for your review of the 3615 Teller St. project. Thanks, -----Original Message ----- From: Tapp, Chris Sent: Tuesday, November 17, 2015 12:32 PM To: tgg��l@eas�tsid.heat.com Subject: FW: Emailing: Teller 111615.pdf Chris Tapp ProBuild Holdings Sales Mobile 720-508-0804 www.r)robuild.com __-.._Original Message ---- From: Murphy, Joe Sent: Tuesday, November 17, 2015 12:24 PM Ta: Tapp, Chris Subject: Emailing: Teller 111615.pdf 3�� JUEWEUU���t # 2 attachments. Check your e-mail security settings to determine how attachments are handled. CONFIDENTIALITY NOTICE: This email may contain confidential and privileged material for the sole use of the intended recipient(s), Any review or use by others is strictly prohibited. Any distribution or disclosure by or to others is strictly prohibited. If you have received this communication in error, please notify the sender immediately by e-mail and delete the message and any file attachments from your computer. +W37_dn_ht_R_4 the use of the individual or entity to which they are addressed. If you are not the intended recipient or the person responsible for delivering the e-mail to the intended recipient, you are hereby notified that any dissemination, disclosure or copying of this e-mail disclosure or copying of this e-mail or any of its attachments is strictly prohibited. If you have received this e-mail in error, please immediately notify the sending individual or entity by e-mail and permanently delete the original e-mail and attachment(s) from your computer system. Thank you. 0 a CITY OF WMEAT RIDGEAND INSPEMON SERVICES DIVISION agency7SOO W 291h Ave WhW Ridge, CO 900334001 p303.235.2855.f 303.237-9929 the project type and be attached to the Building Permit Application at the time of submission. Applications presented for submission Without a completed Proof of Submission form from a required , .. accepted or processed. Date: Project Address- 3(oI5 • of FirmAndivi4ualw ♦ r i6 4 Project Type/Description. eal Signature of Firm Representative or Individual.* TT— am a duty authorized representativeof indicated below and do, by my signature below, hereby acknowledge recelpt of documents necessary for review and approval of the project Indicated above. e Protectiono Wheat Ridge Fire w Arvada Fire Protection Ridgeo Wheat Water District s Consolidated Mutual Water District o Valley Water District o Denver Water * Clear Creek Sanitation U • Frultdate Sanitation District • Westridge Sanitation • Other Agency «, s (Agencysignature.* Date: -72P Representative) Address. .honing: Lot Size: .scatWidth: Property in the flood plain? Ifyes, add surveying condition I Type OfProject (applicable survey conditions in parenthesis : Accessory ISP, ILC or site plan non Addition ILC and site plan if Win ': o if scil� t s floodplain W*floodplain II. acrd site pl yes ) if /azo ' cf" sctl�ck (712;) ifin floo 1 , i Lot average: �'� in floodplain (F sq, Existing , Improvements: House: �r+ Os Improvements: sq. fl. O 'additi n: S sq. fl. Shed: q, ft ft, ech Bare: sq t. Detached Garage: sq, sq. f.,Other: sq. ft. Total Existing s . fl s. . CoverageLot q Propos +pisting d . ft Lot coverage ° Required Setbacks: Fly S S 5 ( Provided Setbacks: FR $ `' � S � ? ' � RPolo- For additions or neve consJQQn, rs the structure within 2 feet Of minimum ....... _.mw. _.rv._ _ ._,._..._ es, dsuurve,)9!2_dition_FND, Maximum Height: axirnurn Size: ' sq. ff. Proposed Height: . $� Proposed Size. sq, ff. Parkland: if the permit is for new construction, have Parkland dedication fees been paid? If o, add condition PFEE, notify owner, notal bu ldin —division. Streetscape: Does the permit result in any of the following conditions? Construction of neve roads 0 .Flatting of new lots New development 0 Additions that increase floor area. by % or more see fo (proposed floor area — xis . floor ula W__ g ) /existing floor area o ./ inc. If any boat is checked SF/DUPLEX-1s there existing j Curb 0Cltttt er If curb, gutter or sidewalk is missing, streetscapeconstructiontor� fees -ice lierrlwill beacentoreq property? ..urs . MULTIFAMILY—Does the frontage meet current city standards? If not, streetscape construction or fees -in -lieu will be required. Fees -in -lieu ofd dication or construction are due at the time the permit fs issued. Minimum Minimum Minimum Minimum Maximum Maximum Minimum Lot Front Side Rear Briding Lot Height Building ) Yard Yard Yard Coverage* Area Setback Setback Setback fib} d) fd3 Lead Description Provided Customer LOT , WNNGSIDE RETIRE NT CCS !l SUBDIVISION, COLNTY OF XFFERSON, STATE OF COLORADO. LOT I M /4 x to #3615 Tj STORY Ci) 0-) �A (C) LOT I 00 \VM HWMJMSE M1 M COLUMBINE SURVEYING, INC. 7573 South Arms Way Littleton, CO 80128 303-972-8000 fox 303-972-8001 Cirigind Scale I" = 30' IMPROWEMENT LOCATION CERTIFICATE I hereby certify that this improvement location certificate was prepared for 0 15 30 MALKET PARTNERSHP LLQEM that it is not a lownd surve at i ovement sur�ve of- and that it is not to be relied Lpon for 'the establishrr*int of fence, bulidi or C vere oncre 112� y other future improvement lines. This certificate is valid only f use b --I MALKET PARTNERSHP Concrete and describes the parcels appearance on 2015-03-14. 1 further certif that the improvements on the above described parcel on this dote, '� 7, except utility Fence connections, ore entirely within the boundaries of the parcel, except as shown, that there are no encroachments upon the described premises by improvements on any adjoining promises, except as indicated, and that there is no qpparent evidence or sign of any easement crossing or burdening any port of scid parcel, except as noted. Notice: Accordto Colorado low you must owimence Note' All platted and apparent easements qny fegd octionlosed upon any defect in this ore shown. Record easements, if any, are improvement location certificate within three years located by information provided by the after you first discovered such defect, In no event, may any oction customer, unless otherwise noted, based upon any defect in this improvement location certificate be commenced more than ten years from the date of the GG certificate shown hereon. Professional Land Surveyor Date SIERRA VISTA ELECTRICLLC 22322 Schultz Lane BERTHOUD, CO $0513 ?701532-4404 FAX: (9701532 -?945 Emoil-sieffavistaelec' Re: 3615 Teller Street, Wheat Ridge, Co General lighting load — 2,260 sq. ft. @ 3 VA/ sq.ft.= 2 Small Appliance- Laundry- Dishwasher - Disposal - Total 3,000 VA @ 100% 13,200 VA — 3,000 VA = 10,200 CM3= east corner exterior. f 141rode corrdutitor Sincereley, Dan Cantu � n 970-213-1185 at you SUbjeCt to Field Wheat, Ridge Buil6t,ig Dept ff 1, I jjj k?�un ddd Wr ti on, QY . .... ..... ff 1, I ti Project Summary fi Entire House Authority Air Designs, LLC. Job: 361STellerSt. Date: Dot 31, 2015 SyJoe Colbum Plan: Malket Partnership For: BoeKampbell, Eastside Heating & Air Conditioning, Inc. 10381 E, 106th Ave., Briphton, CO 80601 Phone: (303) 731-2136 ax: (303) 286-76>46 Notes'. Web: www,EastsideHeat.com Email: BoeKamp@EastsideHeat,c] Outside db 0 OF Inside db 70 OF Design TD 70 OF Heating Summary 0,13 Structure 51441 Btuh Ducts 0 Btuh Central vent (169 cfm) 10737 Btuh Humidification 10853 Btuh Piping 0 Btuh Equipment load 73031 Btuh Make Rheern Trade Classic 92 Series Model R92PA1151524MSA AHRI ref 6468406 Outside db Heat!Cooli ng'43 Area (111) 42 OF Volume (W) 19337 19337 Air changes/hour 0,13 O07 Equiv. AVF (cfm) 42 23 Make Rheern Trade Classic 92 Series Model R92PA1151524MSA AHRI ref 6468406 Outside db 91 OF Inside db 75 OF Design TD 16 OF Daily range H Btuh Relative humidity so % Moisture difference -34 gr/lb Structure 19634 Btuh Ducts 0 Btuh Central vent (169 cfm) 2423 Btuh Blower 0 Btuh Use manufacturer's data n Bt Rate/swing multiplier 0.96 to Equipment sensible load 21131 Btuh mma�# Structure 570 Bt Ducts 0 st Central vent (169 cfm) -3227 Bt Equipment latent load if Bt Equipment total load 21131 Bt Req. total capacity at O85 SHR 2.1 to Calculations approved by ACCA to meet all requirements of Manual J 8th Ed, 13 SEER Make Rheern Btuh 4380 Trade Classic 13 Series 29200 Btuh Cond RA1330AJI cfrn O070 Coil RCFV-AU3824AC 0.90 in H20 AHRI ref 7508098 92AFUE Efficiency 11,5 EER, 112000 Btuh Sensible cooling 82368 Btuh Latent cooling 65 OF Total cooling 1400 ofm Actual air flow 0.027 cfm/Btuh Air flow factor 0.90 in H2O Static pressure Load sensible heat ratio Calculations approved by ACCA to meet all requirements of Manual J 8th Ed, 13 SEER 24820 Btuh 4380 Btuh 29200 Btuh 1400 cfrn O070 cfm/Btuh 0.90 in H20 1.00 If Project Summary Zone I Authority Air Designs, LLC. ill Job: 3616T911erSt. Date: °o. 31, 2015 By: Joe colburn Plan- Malket Partnership For: Boe Kampbell, Eastside Heating & Air Conditioning, Inc, 10381 E. 1 06th Ave, Briphlon, CO 80601 Phone: (303) 731-2136 ax: (303) 286-7646 NotesWeb., www-EastsideHeat-corn Email: BoeKamp@EastsideHeat.com g-gg �tN& . . . . . . . . . . . . . . �g, g t 141p It t""""77, Outside db 0 OF Inside db 70 OF Design TO 70 OF Heating Summary Heath Structure 33475 Btuh Ducts 0 Btuh Central vent (105 cfm) 0 Btuh Humidification 922 Btuh Piping 0 Btuh Equipment load 34396 Btuh TMIM= Method 91 Simplified Construction qualityI 75 Ti ht Fireplaces 16 (Tight) Tigt) Daily range Heath Coolin Area (W 2719 27111 Volume ?ftp) ?1 12704 12704 Air changes/hour 0A3 0.07 Equiv. AVF (cfm) 27 14 Heating Equipment Summary Make n1a Conal n1a Trade We Call n/a Model n1a AHRI ref n1a AHRI ref n1a Efficiency n/a Efficiency Sensible cooling n/a Heating input Latent cooling 0 Heating output Total cooling 0 Btuh Temperature rise Actual air flow 0 *F Actual air flow Air flow factor 0 cfm Air flow factor Static pressure 0 cfm/Btuh Static pressure Load sensible heat ratio 0 in H2O Space thermostat We Outside db 91 *F Inside db 75 *F Design TO 16 *F Daily range H Btuh Relative humidity 50 % Moisture difference -34 gr/lb Structure 15706 Btuh Ducts 0 Btuh Central vent (105 cfm) 0 Btuh Blower 0 Btuh Use manufacturer's data n Btuh Xatelswing multiplier 0,96 ton Equipment sensible load 15047 Btuh Structure -275 Btuh Ducts 0 Btuh Central vent (105 cfm) 0 Btuh Equipment latent load 0 Btuh Equipment total load 15047 Btuh Req, total capacity at 0.85 SHR 1.5 ton Cooling Equipment Summary Make rVa Trade We Conal n1a Call n/a AHRI ref n1a Efficiency n/a Sensible cooling 0 Btuh Latent cooling 0 Btuh Total cooling 0 Btuh Actual air flow 0 cfm Air flow factor 0 cfm/Btuh Static pressure 0 in H2O Load sensible heat ratio 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. wrightSOft' Right-SuiteV Universal 2016 1&0,23 RSU18198 2015-Dec-31M34�36 ,,.ng\3615TWfer$t\Eastside-36l5TefferStrup Calc-Wlt Front Door faces: SE Page 2 Project Summary Zone 2 Authority Air Designs, LLC. W N N M ",1"N"'N"d 1 k 1'5' Job: 3616'rellerSt. D. Doc 31,2015 By: Joe Colbum Plan: Malket Partnemhlp For: Boe Kampbell, Eastside Heating on & Air Conditioning, Inc. 10381 E. 106th AveBri ht, CO 80601 Phone: (303 731-2136 Pax: (303) 286-7646 Notes: Web: www.aastsideHeat.com Email- BoeKamp@EastsideHeat.c N� Outside db 0 OF Inside db 70 OF Design TO 70 OF Heating Summary Heafin Coolin Structure 17966 Btuh Ducts 0 Btuh Central vent (65 cfm) 0 Btuh Humidification 518 Btuh Piping 0 Btuh Equipment load 18484 Btuh TOMM Method 91 Simplified Construction quality1 75 Ti ht Fireplaces 16 (Tight) Daily range Heafin Coolin Area (W) 167� 167� Volume (ft -3) 6633 6633 Air changes/hour 0.14 0,07 Equiv. AVF (cfm) 15 8 Heating Equipment Summary Make n/a Trade n1a Model n/a ARI ref n/a n/a Efficiency 0 nta Heating input 0 Btuh Heating output 0 0 Btuh Temperature rise 0 0 'F Actual air flow 0 0 cfm Air flow factor 0 0 cfm/Btuh Static pressure 0 0 in H20 Space thermostat n/a -g­t"-V aN 11 g "s r M 2 Outside db 91 OF Inside db 75 OF Design TO 16 OF Daily range H Btuh Relative humidity 50 % Moisture difference -34 gr/lb Structure 6585 Btuh Ducts 0 Btuh Central vent (65 cfm) 0 Btuh Blower 0 Btuh Use manufacturer's data n Btuh Ratetswing multiplier 0.96 ton Equipment sensible load 6308 Btuh Structure 845 Btuh Ducts 0 Btuh Central vent (65 cfm) 0 Btuh Equipment latent load 845 Btuh Equipment total load 7154 Btuh Req, total capacity at 0.85 SHR 0.6 ton Cooling Equipment Summary Make n/a Trade ria Cond ria Coil nta AHRI ref ria Efficiency n/a Sensible cooling 0 Btuh Latent cooling 0 Btuh Total cooling 0 Btuh Actual air flow 0 cfm Air flow factor 0 cfm/Btuh Static pressure 0 in H20 Load sensible heat ratio 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2015 -Dec -3118:34: wrightsoft, Riflht-SufteO Universal 2015 15,0.23 RSU18198 Pao ",ng%3615 Taller StTastside - 3615 Teller St,rup Cate - MJ8 Front Door faces: SE AED Assessment Entire House Authority Air Designs, LLC. 6608 W. 95th Place, Westminster, CO 80021-6422 Phone; (720) 3,5"105 Email: JoeQAuthonll Web: wwwAuthofityAk.com Job: 361STelterSt. Date- Doc 31, 2015 By. Joe Colbum Plan: Malket Partnevi M3MnME3= H -A Dw flillifill 1!lj!111�Ill!lllll!llJJlll Jill williplijil!iJillipil MOMMOMMM MIZIM11 2015 -Dec -31 18:34:36 wrigh Right-S.ReV Universal 2015 15A 23 R SU 18198 Page I .-nqX361S Teller St\Eastside - 3615 Teller St,rup Calc - MJ8 Front Door faces: SE . .. . . .. . . ... .. . . . . gg3 M , "0 01" ' M3MnME3= H -A Dw flillifill 1!lj!111�Ill!lllll!llJJlll Jill williplijil!iJillipil MOMMOMMM MIZIM11 2015 -Dec -31 18:34:36 wrigh Right-S.ReV Universal 2015 15A 23 R SU 18198 Page I .-nqX361S Teller St\Eastside - 3615 Teller St,rup Calc - MJ8 Front Door faces: SE AED Assessment Zone I Authority Air Designs, LLC. 6608 W. 95th Place, Mstminster, CO 80021-6422 Phone: (720) 354-8105 Email: Jo9(MAuthodtyAircom Web: wwwAuthorityAitcorn Job. 361STellerSt. D. Dec 31,2016 By: Joe Colburn Plan: Malket Partnership I 1""ti"............ ... . 7-777 Ono r gg"*"-g'y "'V 700 "I'll I'll d , , 12 M i'm 't, 1M t wrightSORight-SuReV Universal 2016 15A23 RSU18198 2015 -Dec -31 W34 AM ... ng\361$Telier$tNEastside-36l5TegerSt.rup CaTc=MJ8 Front Door faces: SE P-91 -'tj -MW I 1""ti"............ ... . 7-777 Ono r gg"*"-g'y "'V 700 "I'll I'll d , , 12 M i'm 't, 1M t wrightSORight-SuReV Universal 2016 15A23 RSU18198 2015 -Dec -31 W34 AM ... ng\361$Telier$tNEastside-36l5TegerSt.rup CaTc=MJ8 Front Door faces: SE P-91 ♦ A ^ED Assessment Zone 2 Authority Air Designs, LLC. 6608 W. 96th Place, V*strninster, CO 80021-6422 Phone: (720) 354-8105 Email: JoeGAuthontyAircom, Web: www.AuthodtyAjrxom, Job: 361STellerSt. Date. Der. 31, 2016 By: Joe colbum Plan: Malket Partnership RI00\'111 " n O2 kg jA .:c i ?P MMESIMM= NARM 2016 -Dec -31 WX36 + wrightSOft"' Right-SuiteO Universal 2015 15.013 RSUIS198 Page 3 -.9MIS Taller St\Eastside - 3615 Teller St,rup Cato - MJ8 Front Door facw SE Building Analysis rxEntire House a , Authority Air Designs, 6608 K 95th Place, Westminster, CO 80021-6422 Phone: (720) 354.8105 Email: .ioe AuthorityAr.com Web: wwwAuthontyAjrcom, Job; MIS Teller St. Date:Oft 31, 2016 Joe colbum Plan. Malket Partnership ';a��1}11��„i �. >L�t„{ t<i t}t I 7177 ttlii ;�. t� Yx `'6th tt Ytx; 141 til j� ,„'gtit ttt $ I,ttt tti(%'tr t;.11�111 1'11 11 7,i 1. <? +`tS4{t t1iY 4:kivlity ,Un�t�� t,,wy4uFl 4lty .iti~,al ltx 11z34,Il..0 t?�1=lt,t�ifit,'ax���;,:tk. 't11yR,. vPt�ttt.<t.,: *R ..t r,. r$i,.< < `�{t t:tKtzt 11 .+t. �`Xteit�$. 1.1,. ., .Y:1�S ,t,'ui 4i Yt�..t tt ,.t t�l Yt ii tt�2*t, s.tt. u�,t �.. 1t 3��th`{L611>t1S t t t k 1 1 t Till, 1 t t t t 4# Glazing M,. 11043 15 1 t Dla # : Doors • • ty�� YI t] a Ceilings Floors41 9803 13.4 Infiltration1.0 • # M • #0 .. 0Humidification 10853 14.91 t Ventilation 10737 14.7 i Adjustments Total ! :1 i .tt itt Y': 6, Y ntt t m.. ..l .t<,l� <i!t •,..... n ..,i t ,Y L:, 'd., J t. .,,.1 .i t l .l. 1. i ti -.t 1. 7 t.. i 2. T � „ (.. 4. tt I t Y.1 t. a .. � 1., ,1� '1 h.. 1 .�.. .t. � �. t, ,...ppit` ,.�r t , ,p� t .t. L 1. `� .l -. � {.. t}..1•£,.117..:1 g.. 111 ,-.1 ut:,4 ,�: ., ,2' 1 t ;t 1 t .U:, tt;.,..,.. < :a, < t t .1:-. a S t. .. <. ,.,.... ,. J!xs. ,1 ,a f s , ., t e t A . ,.. :.., tt... 1 4 .< .. 1t .x1 i tr .... �»t 1 t l ..1 :. t,. ., �� � .l. 1 l . L .,. t�..... 7 .. 1. d.. t;. `t',tra .. t zX ,.. d=. t �tl ,1.t t 11 tt1 ,: (, ,l ,.,"1 �... t t �tblt 4 moi, � t Walls 0.1N i13.4 27,71 12859 &3 yealazing Ceilings 11 1.0',.2253 •y: Infiltration T ill Ducts y # T 1 Ventilation 2423 110 Internal gains 1150 5.2 Blower {]0 Adjustments 0 Total : 220 58 00 y rt "! 2015 -Dec -31 18:34:36 # F Page Building Analysis Zone 1 Authority Air Designs, LLC. 6608 W. 95th e, Westminster, CO 80021.6422 Phone: (720) 354-8105 EmaiE JoeQAuthodtyAircorn Web: wwwAuthofftyAkeorn Job: 3616TellerSt. Date: Doc 31, 2016 By. Joe Colbum Plan: Malkot Partnomh1p 47MEWN—MO Data entries checked. 2015 -Dee -3118:34::: WrightSoft' Right-S.ReO Universal 2015 MOM RSU18198 Pag ... ngX3615 Teller St\Eastside - 3615 Teller St.rup Calc-MJS Front Door faces: SE ................ Walls 59 13752,� 40.0 Glazing 218 8143 217) Doors 0 0 01 Ceilings 1A 2150 6.31 Floors 5.3 7730 22.5 Infiltration 1.0 1700 49 Ducts 0 0 Piping 0 0 Humidification 922 2.7 Ventilation 0 Adjustments Total �-"g -Jaom n" gmm t.tiake �""!p g ta ANTIMIN Walls fY 1725 110 i Glazing X0 12 7&5 Doors 0 0 Ceilings 10 1447 9.2 Floors 0 0 0 Infiltration OA 207 1,3 Ducts 0 0 Ventilation 0 0 Internal gains 0 0 Blower 0 0 Adjustments 0 Total 1570611 100.0 47MEWN—MO Data entries checked. 2015 -Dee -3118:34::: WrightSoft' Right-S.ReO Universal 2015 MOM RSU18198 Pag ... ngX3615 Teller St\Eastside - 3615 Teller St.rup Calc-MJS Front Door faces: SE !„Component Constructions Job: Date: Dec3l,2015 Entire House By: ! Authority Air . gns,Partnership #8W21-6422 Phone: (720) 35"105 Email: Joe@AuthodtyAjrcom, Web: www.AuthorftyAjrcorn DrapedConstruction 312 0163 0 9.85 3076 0 0 se 303 0.163 0 R 1 t t't 1�1 11,`1 tl 1 tdh .t t x171 t 11tt ti. 1 o tt tttt tp,.„ i� 11 . t,..' tt ` �; t ttk i t tl 1 t 1x11 10 t t 1 Location: fid:Cooling Heating 0 a.. D'Stapletonl i i y , US Indoor*' r temperature 3068 Elevation: :: r #P' ' # II Design 6 Latitude:1 •' 1 50 Outdoor: Heating Cooling Moisture difference (gr1lb) 61.4 -34O Dry bulb i 91 Infiltration: 1066 Daily range Method Simplified 10.2 Wet bulb ('F) - 60 Construction quality 0 speedWind - • i 7.5 Fireplaces h 0.056 v4 • .•«t .,�i... b% 1 'x' o- tx: meJ i o- , -� 1 4 descriptions 'u?. t li St,„:i+ t t,va^t':" 4„t tr t- { �Jt MU v t. �. tl, lR i'� - h t 1i:t to -u t A, k,.t Or Area U-Valus Insul R Htg HTM Loss a b Ld, t ,ti ';k;}... Clg HTM Gain 0 0 se Insulation,Vinyl iNKON #:" S#. ne 312 0163 0 9.85 3076 0 0 se 303 0.163 0 11.4 3465 0 0 sw 312 0.163 0 9.83 3068 0 0 nw 138 0.163 0 8,94 1236 0 0 a99 1066 0.163 0 10.2 10845 0 0 ne 202 0.056 13,0 3.89 783 0 0 se 66 0.056 13.0 3.69 255 0 0 sw 187 0.056 13.0 189 728 0 0 w 20 0.056 13.0 3.69 79 0 0 nw 129 0.056 13.0 3.89 501 0 0 a91 604 0.056 13.0 3,69 2346 0 0 ne 222 0.093 11.0 6.50 1439 1.73 382 se 240 0.093 11,0 6.50 1558 1,73 414 sw 118 0.093 11,0 6.50 763 1.73 203 nw 104 0.093 11.0 6.50 676 1.73 179 a99 683 0.093 11.0 6.50 4436 1.73 1179 ne 454 0.061 20.0 4.26 1933 1.13 514 se 241 0.061 20.0 4.26 1026 1.13 273 sw 496 0,061 20.0 4,26 2110 1.13 561 w 27 0.061 20.0 4.26 114 113 30 raw 352 0.061 20.0 426 1498 1.13 398 all 1569 0.061 20,0 4.26 6682 1,13 1775 2015 -Dee -31 18:X36 AMK -ng\3615 Teller WEastalde - 3615 Teller Strup Cair - MJ8 Front Door facw SE Windows U-34 SHGC-31: U-34 SHGC-31 - Windows; NFRC rated (SGC -0,31); 7 ft head ht U-34 SHGC-31 GD: U-34 SHGC-31 - Glass Door; NFRC rated (SHG C=0.3l)-17 it head ht U-34 SHGC-31 SLG: U-34 SI GC -31 - SLG Door; NFRC rated (SHGC=0.31); 7 ft head ht Doors Exterior Door: Exterior Wood Door Ceilings STD - Attic CLG - R-49: Attic Ceiling, Asphalt Shingles, R-49 Ceiling Insulation, 1/2" Gypsum Board Floors STD - Basement Floor: 4" Concrete Below Grade Basement Floor STD - Crawl - Visqueen: Crawl Space,Dirt FloorVisqueen Cover STD - Stab on Grade: 4" Concrete Slab on Grade ne 13 0.340 0 218 300 24.6 310 ne 72 0.340 0 23,8 1714 24,6 1774 ne 35 0.340 0 218 821 24.6 850 se 24 0.340 0 218 571 29.8 714 se 60 0340 0 23.8 1428 2:3.8 1786 sw 13 0.340 0 218 303 29,8 379 sw 48 0,340 0 23,8 1142 29.8 1429 sw 46 0,340 0 23,8 1095 29,8 1369 w 14 0,340 0 2.3.8 333 34.6 485 nw 9 0.340 0 23,8 208 24.6 216 nw 24 0.340 0 23,8 571 24.6 591 nw 27 0.340 0 218 643 24.6 665 all 384 0.340 0 218 9129 27.6 10569 se 20 0.340 0 23.8 478 29.8 598 mv 20 0.340 0 23.8 478 24.6 495 all 40 0.340 0 23.8 957 27.2 1094 sw 40 0,340 0 23.8 957 29.8 1196 $a 20 0.244 5:0 14.4 281 432 95 2316 0.021 49.4 1,45 3349 4.97 2253 1278 4.031 0 215 2746 0 0 802 0,044 0 3.05 2445 0 0 49 1.358 0 95,1 4613 0 0 ---------- — -------------------------------- ------------------------- ---------------- ....... .. + wrighftOft' Riqht�SuiteO Universal 2015 15A23 RSU18198 201 S -Dec -31 18:34:36 page 2 AOM ... nq\3615 Teffer SAEastaide - 3616 Taller St,rup Calc - MA Front Door faces: SE Component Constructions Job. 361STetlerSt. !III Date: Doc 31,2016 JIM- Zone I By: Joe Colburn Plan: Malket Authority Designs,r Windows I Or Area -value Insul R Htg HTM Loss CIS HTM Gain ne re eWhAt^..-'F Rl-'Muh .h 6tuh Blathlfe Ruh ne 197 0.163 t �Y^i �t tttt ttt�t ��,% 1, t t s..,.a }ah ~:�ttai,,,, l�t,t..,at�k, t a..>lt+�,.:m,tt1,..: 1 ilv, it Ct y#y ■■yy .gY, rt� t1� i :, 1� t vl }t ,,r.;. � a,. Ya,. tt.it,.m,.,.t, ,.... .r„tt,t�..., t ., ,.1. t,t,.,a,t..,..if�.sa., it at, t1 uatt,, tlltt t t.,, at., t'� t 1 } {, 't~•ti .,.,t�. 1786 se 19 0.163 0 11.4 217 0 0 sw 312 0.163 0 9.83 3063 0 0 nw 19 0.163 0 11.4 217 0 0 all 547 0.163 0 10,5 5755 0 0 ne 122 Windows I Or Area -value Insul R Htg HTM Loss CIS HTM Gain ne re eWhAt^..-'F Rl-'Muh .h 6tuh Blathlfe Ruh ne 197 0.163 0 11.4 2253 0 1786 se 19 0.163 0 11.4 217 0 0 sw 312 0.163 0 9.83 3063 0 0 nw 19 0.163 0 11.4 217 0 0 all 547 0.163 0 10,5 5755 0 0 ne 122 0.056 13.0 189 472 0 0 se 66 0.056 13.0 3,89 255 0 0 sw 107 0.056 13.0 3.89 417 0 0 20 0.056 13.0 3.89 79 0 0 nw 73 0.056 13.0 3.89 284 0 0 all 388 0.056 13.0 3.89 1506 0 0 ne 118 0«093 11,0 6.50 763 1.73 203 sw 118 0,093 11.0 6.50 763 1:73 203 all 235 0.093 11.0 6.50 1526 1.73 406 ne 305 0.061 20.0 4,26 1297 1.13 345 se 241 0.061 20.0 4.26 1026 1.13 273 sw 346 0.061 20.0 4.26 1472 1.13 391 W 27 0.061 20.0 4.26 114 1.13 30 nw 248 0,061 20.0 4.26 1056 1.13 280 all 1166 0,061 20.0 4.26 4964 1.13 1319 ne 48 0340 0 23.8 1142 24.6 1183 ne 24 0.340 0 23.8 571 24.6 591 se 60 0.340 0 218 1428 29.8 1786 sw 13 0.340 0 23.8 303 29.8 379 sw 48 0.340 0 23.8 1142 29.8 1429 sw 36 0,340 0 23.8 857 23.8 1071 W 14 0.340 0 218 333 34.6 485 nw 19 0,340 0 23.8 452 24.6 468 all 262 0.340 0 23.8 6230 28,2 7393 2015 -Dec -31 18:34:36 wright$Oft'•ht-SuReS Universal 2016 M0,23 Door U-34 SHGC-31 GD: U-34 SHGC-31 - Glass Door; NFRC rated (SHGC=0,31); 7 It head ht U-34 SWIG -31 SLG" U-34 SHGC-31 - SLG Door; NFRC rated (SHGC=0,31); 7 It head ht Doors (none) Ceilings STD - Attic CLG - R-49: Attic Ceiling, Asphalt Shingles, R-49 Ceiling Insulation, 1/2" Gypsum Board Floors STD - Basement Floor: 4" Concrete Below Grade Basement Floor STD - Crawl - squeen: Crawl Space,Dirt FloorVisqueen Cover STD - Stab on Grade: 4" Concrete Slab on Grade $a 20 0.340 0 218 478 29,8 598 nw 20 0,340 0 23.8 478 24,6 495 all 40 0,340 0 218 957 27,2 1094 sw 40 0,340 0 23.8 957 29.8 1196 1487 0,021 49.0 1.45 2150 0.97 1447 710 0.031 0 2.15 1525 0 0 522 0,044 0 105 1592 0 0 49 1.358 0 95.1 4613 0 0 2015 -Det -31 18:34:36 +wright$aw Right-SuiteOUnivemal2ol5l5.0.23RSU18198 Page 4 )M ... ng\3615 Teller ShEastside - 3615 Teller SCrup Calc=MJS Front Door facm SE Component Constructions Job; 3616'TallerSt. Data: Doe 31, 2016 Zone 2 By. JoeColburn Ian Mnlkg*+ PA irtnership 6608 K 951h Place, l/Vastminster, CO 80021-6422 Phonw (720) 35"105 Email: JoeQAtithorityAkcorn Web: vrww.AuthorftyAjrxorn For: Boe Kampbell, Eastside Heating &Air Conditioning, Inc. 10381 E. 106th Ave., Brighton, CO 80601 Phone: (303) 731-2136 Fax: (303) 286-7646 Web: www.EastsideHest.com Email: BoeKamp@EastsideHeat.com fer iii itapteTor-l-m' e,, Elevation: 5285 Illi Latitude� 40"IM N Outdoor: Heating Dry bulb (*F) 0 Daily range Wet bulb (T) - Wind speed (mph) 15.0 Cooling 91 27 ( H 60 7.5 in000r temperature (-F) Design TD (OF) Relative humidity Moisture difference (gr/lb) Infiltration: Method Construction quality Fireplaces to 70 50 61.4 0 Construction descriptions Or Area U-valusi Insul R Ht9 HTM Loss C19 FITM Gain 24 0,340 it, EWh/ftl-*F ft--'Flfth StUhM atuh Sturm Stun Walls 0 23.8 250 24.6 259 se 24 0.340 STD - Basement Wall - None: 8" Below Grade Concrete Wall ne 115 0.163 0 713 823 0 0 218 se 284 0.163 0 11.4 3248 0 0 208 nw 119 0.163 0 8.54 1019 0 0 24.6 all 519 0.163 0 9,81 5090 0 0 STD - Crawl Space Wall - R-13 - Draped: 8" Below Grade Concrete ne 80 0.056 13.0 189 311 0 0 Wall,R-13 Draped Insulation,Vinyi sir 80 0.056 13.0 3,89 311 0 0 mv 56 0.056 13,0 189 218 0 0 all 216 0.056 13.0 3,89 839 0 0 STD - Frame - RAM Wood Ext, 112" Wood Stith, 2"x4'Fara Wall, ne 104 0,093 11,0 6,50 676 1,73 179 R-11 Cavity Insulation, 1/2" Gypsum Board se 240 0.093 11.0 6.50 1558 1.73 414 rev 104 0M3 11.0 6.50 676 1.73 179 all 448 0.093 Mo 6.60 2909 1,73 773 STD - Frame - R -20 W: Wood Ext, 1/2" Wood Shth, 2"x 6" Fr m Wall, ne 150 0.061 MO 426 637 113 169 R-20 Cavity Insulation, 1/2" Gypsum Board ate 150 0,061 20.0 4.26 639 113 170 nw 104 0Z61 20.0 426 443 1A3 118 all 404 0.061 20,0 426 1718 1A3 457 EM Windows U-34 SHGC-31: U-34 SHGC-31 - Windows; NFRC rated (SHGC=U1); 7 ft head ht ne 13 0.340 0 218 300 24.6 310 ne 24 0,340 0 23.8 571 24,6 591 ne 11 0.340 0 23.8 250 24.6 259 se 24 0.340 0 218 571 29.8 714 sw 10 0.340 0 218 238 29.8 298 nw 9 0.340 0 218 208 24,6 216 nw 24 0.340 0 23,8 571 24.6 591 mv 8 0.340 0 23.8 190 24.6 197 all 122 0.340 0 23.8 2900 261 3176 se 20 0,200 5.0 14.0 281 4.72 95 ---------- 2015-Dec-31 18:34�36 wrightsoW Right-SufteS Universal 2015 15A23 RSUIS198 page 5 �M -ng\3615 Teller StTastside - 3615 Tager Sr.rup Colo - MJ8 Front Door faces: SE Ceilings STD -Attic CLG - R-49: Attic Ceiling, Asphalt Shingles, R-49 Ceiling 829 0,021 49.0 1,45 1199 0,97 Insulation, 1/2" Gypsum Board Floors STD - Basement Floor: 4" Concrete Below Grade Basement Floor 568 0,031 0 2.15 1220 0 STD - Crawl - Vis queen: Crawl Space,Dirt Floor Visqueen Cover 280 0,044 0 105 853 0 M 2015 -Dec -31 18:34:36 wrightS� Right-Suftee Universal 2015 MOM RSU18198 Page 6 ... ng�3615Te#erStNEastside-361STeNer$t,rup Catc-M.18 Front Door facm SE s Right -JO WorksheetJob i Entire House :. Dec3l,2016 Joe Colbum m�> Authority Air Designs, LLC. L: Malket Partnomhlp 6606 W. 95th Place, Westmkister, CO 60021-6422 Phcsw (720) 354-8105 mad: Joe@Authordy0jr.com Web: www,AtdhoMyAit.com Oh"Oft" Right-SrifteV Universal 2015 15,013 RSUI$198 Page I ."ng\3616T�allerSt\Eastside-3615TeRorSt.rup CWc-MJB Front Door faces: SE RighWO Worksheet Entire House 6608 W 95th Place, V%stminster, CO 80021-6422 Phone: 1720) 354-8105 EmaiV Joe@AuIhorftyAjLcom WW www,AtithantyAW.com .doe Colburn Pr,*n: Malket Partnership tA2015-Dec-31 1&3k36 + Wlr'9h SC*ft* Right-SufteO Universal 2015 MOM RSU18198 Page 2 —ng\3615 Teller SAlEastside - 3615 Teller SCrup Cato - MJ8 Front Door faces: SE Right -JO Worksheet Zone I Alr r M* -- - Asima'" -n * 6608 W. 96th Place, V*stminster, CO 80021-6422 Phone. (720) 36"105 Email: Joe@AuthorftyMcom Web: www.AuthofityAlt.com BJoe Colbum pfa*n: Malket Partnership 4 -ff+- wrightsoft- Right-SufteV Universal 2016 15,0.23 RSU18198 201 S -Deo -31 18:34 lzl—& .,ng\3615 Teller StkEastside � 3615 Teller St.rup Calc=MJB Front Door faces� SE P1.9i Right -JO Worksheet Zone I i I liaJ.LL 6608 W 95th Place, V*sWrister, CO $0021-6422 Phow (720) 35,4-8105 Email: JoeQAuthodtyAjrcorn Web: www.AuthorityAk.com Job: 3616 Teller St. Date: Doe 31, 2015 Joe Colbum P : Malket Partnership SEF.1 UWAMOZIOW 4 2015 -Der -31 18:34:36 A4- 'OV Qht'50ft- Right-S.ReV Universal 2016 15,0.23 RSU18198 Page 4 ,,,ng\3615 Teller StkEastside - 361STeffer St-rup CaIc-MJ8 Front Door faces: SE Right -JO Worksheet Zone I 6608 W, 95th Place, VWstminster, CO 80021-6422 Phone: (720) 354-8105 ErrueL Joe*AuthorityAk.corn Web: www,AuthorkyAk.com Joe ColburnL, Malket Partnership Calculations 2ppL by ACCA to meet all requirements of Manual J 8th Ed 2015-Dec-31 1814:36 -q+ wrightsofto Right-SulteV Universal 2015 15.0,23 RSU18198 Page 5 -ng\3615 Teller SAEastside - 3615 Teffer St.rup Cale - MJ8 Front Door faces: SE Right -JO Worksheet Zone I 6608 W. 95th Place, Westminster, CO 80021-6422 Phone: (720) 35"105 Email: Joe@AuthorityAir.com Web: www,AuthofftyAir.com Br* Joe Colburn P in: Malket Partnership 2015 -Dee -31 18:34�36 -44+ vvrlqhtaoft� Right-SuiteS Universal 2015 15.0.23 RSU18198 Page 6 04�1& ...ng%3615 Teller SAEastside - 3615 Teller StImis Calc - MJ8 Front Door faces: SE Right -JO • • I 6608 W 95th Place, V*stminster, CO $0021-6422 Phone: (720) 354-8105 Email: JoeQAuthodtyAjrcom Wab� wwwAuthorityAjrcorn Job: 3616 Tefter St. •. Doc 31, 2016 Joe Colbum L. Malket Partneiship vwriqht$Oft�� Right -Suite* Universal 2015 15,0,23 RSU18198 2015 -Dec -31 %34:36 ... ngN36l5TegerSt\Eastside-361$TegerSt.rup Cak-MJ8 Front Door facw SE Page 7 Right -JO Worksheet Zone I r bIL&AjirLnQaffjajMjs. LLC - 6608 K 96th Place, Westminster, CO 80021-6422 Phone: (720) 354-8105 Email: Joe@AuthodtyAJrcom Web; www,AuthorityAir.com Joe Colbum L. Malket Partnotship Right-SufteS Universal 2015 M0,23 RSU18198 2015 -Dec -31 M34:36 —ng\3615 Teller SAEastside - 3615 Teller Strup Cadc - MJ8 Front Door faces: SE Page 8 Right -M) Worksheet Job: 3616 Teller St. 4 Zone 2 Date: Dec 31, 2016 B p&n Joe Colbum ft> Authority Air Designs, LLC. a - Malket Partnership 6608 W 95th Place, V*strninster, CO 80021-6422 Phone: (720) 354-8105 Email: Joe QAuthordyAjrcom Web: wwwAuthorityAktorn 2015 -Dec -31 W34:36 Right-SuftfO Universal 2015 ISA23 RSUIS198 Page 9 —ngX3615 Teller ShEastside - 3616TelferStxup CaIc-MJ8 Front Door faces: SE Right -JO Worksheet Zone 2 ? 6608 W 95th Place, Mstminster, CO 80021-6422 Phow (720) 354-8105 Emait Joe@Authofity.Aircom Web: wwwAuthorilyAkcom Br ' Joe Colbum Eden: an: Malket Partnership Right-SulteSUntversal20l5l5,O.23RSUIR198 2015 -Dec -3118:34:36 ,,ngk3616 Teller St\Eastside - 3615 TeVer SCrup Calc - MJ8 Front Door faces: SE Page 10 Right -AD Worksheet Zone 2 Authoritv Air D 6608 W 95th Place, VOrstminster, CO 80021-6422 Phow (720) 354-8105 EmO JoeWutho6tyAjrcom WW voww.AuthorityAjLcom Is 1 86.Joe Colbum : Malket Partnembip Oil 2015 -Dec -31 18:34�36 444-wrightsoft' Righl-SulteO Universal 2015 MOM RSUIS198 Page 11 —ng,3615 Teller StkEastside - 3615 Teller St.rup Calc - MJ8 Front Door faces: SE Right -AD • Zone 2 Wr . r as•, s 6608 W. 95th Place, Vyestrihnsier, CO 80021-6422 Phone: (720) 354-8105 Email: Joe@Auth*iffyAJrcom Web: wwwAuthorgyAkeorn Job: 3615 Teller St Date: Det 31, 2016 1361 Joe Colbum III : Malket Partnembip +j4- RiOWSWWO Universal 2015 15A23 RSU18198 2016 -Dec -31 18:34:36 ... ng\3616 Teller St\Eastside - 3615 Tager St,rup CWc-MJ8 Front Doer faces� SE Page 12 Right -JO Worksheet Zone 2 r 6608 K 96th Place, Okstminster, CO 80021-6422 Phone: (720) 35"105 Email: JoeQAuthordyAltcorn Web: www,AuthoMyAir.com M1160 Joe Colbum : Malket Fradnership rim. AMMOTAW, 2015 -Dec -31 18:34:36 A*' Right-S.A.0 Universal 201615,0.23 RSU18190 Page 13 ... nok3615 Teller St\Eastside - 3615 Taller St,rup Cate - MJ8 Front Door facw SE M. Right -JO Worksheet Zone 2 uft , or i IT A MrDeai o-rtN--LLC-. 6608 W, 95th Place, Westminster, CO 80021-6422 Phone; (720) 35"105 Email: Joe@AuthordyAjr.com Web: www.AuthorttyAif.com Calculations approved by ACCA to meet all rNuirements of Manual J 8th Ed 2015 -Dec -31 MC36 A4- wriqhtSC'ft' Right-SuItOO Universal 201516,0.23IRSU18198 Page 14 ,,,ngk3615 Teller St\Esstsido - 3615 Teller St.rup Cale -M,18 Front Door faces� SE Right -JO Worksheet Zone 2 rt lki 6608 W, 95th Place, V*stminster, CO 80021-6422 Phone: (720) 354-8105 EmWI: Joe @AuthorityAjrcom Web: www,AuttwrityAjr.com B' m Joe Colbu PL: Malket Partnership Calculations MgLpyed �j ACCA to meet all requirements of Manual J 8th Ed. 2015 -Dec -31 18:34:36 Right -S.06 universal 2oI5 15,0,23 RSUIS198 Page 15 .,,ng\3615 Teller SINEastside - 3615 Teller St.rup Calc - MJ8 Front Door faces: SE Load Short Form Job: 36167rellerSt. Date: Doc 31, 2016 Entire House By: Joe Colbum Plan. Malket Partnomh1p Authoft Air Designs, LLC. I M= HEATING EQUIPMENT COOLING EQUIPMENT Make Rheern Make Rheem Trade Classic 92 Series Trade Classic 13 Series Model R92PA1151524MSA Cord RA1330AJI AHRI ref 6468406 coil RCFV-AU3824AC AHRI ref 7508098 Efficiency 92AFUE Efficiency 11.5 EER, 13 SEER Heating input 112000 Btuh Sensible cooling 24820 Btuh Heating output 82368 Btuh Latent cooling 4380 Btuh Temperature rise 65 OF Total cooling 29200 Btuh Actual air flow 1400 cfm Actual air flow 1400 cfm Air flow factor 0.027 cfm/Btuh Air flow factor 0=070 cfm/Btuh Static pressure 0.90 in H2O Static pressure 0.90 in H2O Space thermostat Load sensible heat ratio 1,00 ROOM NAME Area Htg load Clg load Htg AVF Cig AVF (Btuh) (Btuh) (cfm) (cfm) Zone 1 p 2719 33475 15706 911 1100 Zone 2 p 1677 179ffi 6585 489 461 Entire House d 4396 51441 19634 1400 1400 Other equip loads 21590 2423 Equip. @ 0,96 RSM 21131 Latent cooling 1 0 - TOTALS --------- - 4396----31 -- —�1�40O 1 21131 � � 1400730 Calculations approved by ACCA to meet all requirements of Manual J ft Ed, �a Load ShortForm Job: « Doc 31, 2016 ;t<Zone I By- Joe Colbum Authority 6608 W. 95th P4sco, Westminster, CO $0021-6422 Dhow (720) 35"105 mail: JoeQAuth0rAyAir.com Web: www.AothorityAircom HEATING EQUIPMENT COOLING EQUIPMENT Make nta lake nfa Trade nVa Trade nta Model nta Cond nta AHRI ref nla Coil n/a AHRI ref nla Efficiency nVa Efficiency nla Heating input Sensible coofing 0 Btuh Pleating output 0 Shah Latent cooling 0 Btuh "Temperature rise 0 OF Total cooling 0 Btuh Actual air flow 0 cfm Actual air flow 0 cfm Air flaw factor 0 cfnVBtuh Air flow factor 0 cf lBtuh Static pressure 0 in H2O Static pressure 0 in H2O Space thermostat nta load sensible heat ratio 0 ROOM NAME Area Htg load Cig load Htg AVF Clg AVF (ftp) (Btuh) (Btuh) (cfm) (fm) On Crawl 1 118 844 0 23 0 On Crawl 3 404 2254 0 61 0 Cin Kitchenette 182 1378 0 37 0 Dn Cards 156 1582 0 43 0 inn lec 402 4624 643 126 4 Kitchen 302 2723 2049 74 144 living 530 4903 4207 133 295 Sunroom 225 7384 3617 201 253 Powder 32 1733 375 47 26 Office 128 1035 859 28 60 Creat 270 5015 3957 136 277 Calculations approved . meet all requirements of Manual J 8th Ed zone 1 • equip loads Equip. @ 0.96 Latent cooling p 2719 33475 15706 922 0 RSM 15047 0 2719 34396 15047 11" 11' 1 11 1 i I I pillpi'llyrt�111• i I + wrightSOft' Right -Suit eS Universal 2455 15,0.23 RSU18198 -mg\3615 Taller StNEastside - 3615 Teller St.rup Calc - MJ8 Front Door faces: SE 911 1100 911 1100 zm e Load • Form Job: * + Date: Det3l,2016 Zone 2 By: m� x.. Colbum AuthorityDesigns, 6608 W, 96th MCC V*$WnSter� CO 80021-6422 Phone: (720) 354-8106 Ernad: Joe@Authed1yAjcccm Web: www.AuthorftyAjrcorn o- Kampbell,r • &Air Conditioning, 10381 E. 106th Ave., Brighton, CO 80601 • i i 286-7646 Web- e-BoeKamp@EastsideHeat.com HEATING EQUIPMENT COOLING EQUIPMENT Make nta Make nfa Trade nia Trade nia Model nla Cond nta AbRI ref nda Coil nta AbRI ref nfa Efficiency nta Efficiency ria Heating input sensible cooling 0 Btuh Heating output 0 Btuh Latent cooling 0 Btuh Temperature rise 0 OF Total cooling 0 Btuh Actual air flow 0 cfm Actual air flow cfm Air flow factor 0 cfm/Btuh Air flaw factor 0 cfm/Btuh Static pressure 0 in b20 static pressure 0 in 120 Space thermostat nia Load sensible heat ratio 0 ROOM NAME Area btg load Clg load btg AVF Clg AVF (ft2) (Btuh) (Btuh) (cfm) (cfm) Dn Crawl 2 280 1693 0 46 0 Dn Mech 127 1011 132 28 9 Dn Bath 64 626 132 17 9 Dn Bedroom 227 2834 476 77 33 Dn ball 150 2347 0 64 0 Entry 86 1770 872 48 61 M Bedroom 224 2742 1881 75 132 M Bath 84 586 443 16 31 M WC 22 230 178 6 12 M ball 42 733 353 20 2 M WIC 131 1677 621 46 44 Bedroom 1 123 797 737 22 52 Bedroom 2 116 921 760 25 53 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed, t s tone 2 Other • s loads • s @ M .96 Latent cooling 1677 17966 6585 489 461 518 RSM 6308 845 1677 18484 7154 489 461 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed 2015-Dec-31 18:34:40 wright$Oft"'Right-S.ite01515.0.23RSU18198 Page 5 "A It mb , N iv 'R M ROOM NAME Alva Heating Cig load I-Itg AVF ClgAVF Cooling ft2 ZONENAME Volume AC H AVF FITM Volume ACI AVF HTM 23 W Dn Crawl 3 cfm Btu W Cf M Btuh/ft2 Zone 1 12704 0.13 27 1.0 12704 0,07 14 0.1 Zone 2 6633 0,14 is 1.0 6633 O.07 8 O'l Entire House 19337 0.13 42 1.01 19337 0.07 23 011 "A It mb , N iv 'R M ROOM NAME Alva Htg, load Cig load I-Itg AVF ClgAVF ft2 Btuh Btu h cfm CfM Dn Crawl 1 118 844 0 23 0 Dn Crawl 3 404 2254 0 61 0 Dn Kitchenette 152 1378 0 37 0 Dn Cards 156 1582 0 43 0 Dn dee 402 4624 643 126 45 Kitchen 302 2723 2049 74 144 Living 530 4903 4207 133 295 Sunroom 225 7384 3617 201 253 Powder 32 1733 375 47 26 Office 128 1035 859 28 60 Great 270 5015 3957 136 277 Zone 1 2719 33475 15706 911 1100 Dn Crawl 2 280 1693 0 46 0 Dn Mech 127 1011 132 28 9 Do Bath 64 626 132 17 9 Dn Bedroom 227 2834 476 77 33 Dn Hall 150 2347 0 64 0 Entry 86 1770 872 48 61 • Bedroom 224 2742 1.882 75 132 • Bath 84 586 443 16 31 M WC 22 230 178 6 12 M Hall 42 733 353 20 25 • WIC 131 1677 621 46 44 Bedroom 1 123 797 737 22 52 Bedroom 2 116 921 760 25 53 Zone 2 1677 17966 6585 489 461 Entire House 4.396 514-41- 19634 1400 1400 + wrightSW Right-SufteV Universal 2015 MOM RSU18198 2015 -Dec -3118:34:40 Page I I'm ..,ng\3616 Teller SnEastside - 3615 Teller St,rup Cak.=MJ8 Front Door faces: SE Duct System Summary Job: orSt. 0.38 Date: D36167retloc 31, 2016 Entire House By: Joe Colbum Authority Air Designs, LLC. Plan: Malket Partnership 6608 W. 95th Place, Westminster, CO 80021-6422 Phone: (720) 354-8105 Emait Joe*AuthorityAirxom Web: wwwAuthorityAkeorn External static pressure Pressurelosses Available static pressure Lowest friction rate Actual air flow Total effective length (TEL) Heating 0.90 in H20 0.38 in H20 0.52 in H20 4.1141illi--irl,4;lq--#�- in H2O 0.072 in/100ft 1400 cfrn Cooling 0.90 in H2O 0.38 in H2O 0.52 in H20 0.260 / 0,260 in H2O 0.072 in/100ft 1400 cfm 723 ft ------ ----- 2015-Dec-31 M34:40 + Wrl Right-SulteQ Universal 2015 15,0,23 RSU18198 Page I A00k ... ng\3615 Teller St\Eastside - 3615 Teller St,rup Cato - MJS Front Door faces: SE s �k I t Yit � t ��� l it..rt t ����� t Design HxW Actual Ftq.E w # s OX0 27.2 235. w. Bedroom 2 c 760 25 53 Dn IT # # !:. ,. BedroomDn # U99 6.0 ! # 41.2 220.0 Do Cards h 1582 43 ! 0.095 5.0 Ox ! 391 On Crawl 3 h 2254 0 0.0921, 5.01" Ox 0 53'5 230.0 stIOA Do Hall h 2347 64 f f f• e Do Kitchenette h 13780.09 Y it 5. #i 37.9 225.0 stII l ! 4Z9 220.0 stIO Entry C # 4 : •:y i T • Ox a Ik Great c 1319 4 92 #OV# 0, { Ox 723 255.0 ! #. 92 0.05 Ox R r 64A i stI#A M # •F# Rt • ♦ •kI # st1OA Kitchen C * 0. # 6.0 Ox 0 40.0 205* Living-B 1402 98 0. 10111 &0 Ox 0 X3 2210 Stlo • WC C 178 6' 12 O09ri, 4O OX0 451 235O t6 Office C 85911 i 60 0,089 5.0 Ox 0 55.4 23&0 Powder h 1733 26 0.092 &0 !# 1 Y#Y 127 : i5.0 18081 yy 1 •{iy yid� yiY�.. y x 0 y .22 yi :t. t.c�iC t ti ti�11 i t t .-.:; It t l tti �.l dl,:. t�lt � t �. tiit'i tlt till.., t V �, Li `t. : t.. § i` l is-. 1 :`��. t Ll �t�. r- n tt�til 4`fi t \.: it , tt t.,lt{ sl ..qJ .. Y *;. �, ... tt 1...... '•t Y .t t t r � � "t � t lii t \ tR. t tl t'. tt k�. }t"- q lj tt >.} . �, 7{{• 11 • e i . Duct • Material Sti} Peak AVF 485 77# # 677 12.5 Peak 911 1100 2 #Stl 15.2 10 x 20 ShtMetl Stl StI3 Peak AVF i� 464 t ir .1..,R: 1 F$t ';'•:: tb Cti^. ,. t1 t s. ttlt tl 13 1 t t t k i t �.. 1. ., t ..li '?. ,� z,`stlt k t ik: St It .,1k R t.;:: 1s{11: 1.: 11�� it„ 111 t HxWDuct :^Type.. (in) Material s Peak AVF •s-ning (in) 587 O 106 t 10 x 20 i Peak AVF y 0 106 12.6 10 194.2 O 134 538 8.0 ox 0 rt7 r ♦it 10 x 22 ShtMetl R{ 1 ♦ 454, YX R 0 rt7 10 x 25 ShtMetl �245.4 i• 8. Ox 0 rt5 »• 2046 rb3 144 ::0: rb4 14x 4 75 ., W rb5 14x 6 121 227.3 48 8.0 ox 0 rt5 it,1 t1t;•i1r t *11 it '.{�{ Xl; yt K": i 1 L t t" 111 Fi ht„.r' t41i..Z,:'.. Y 1t, i :'.t s. zru: §":, . 10v.t4.it1 .,etIl. t1 }t t .tt'x- tt1.t ...�t,.�.t��*�'�1t\.. 1 , t••.� ltti 1'11 ,:=t,: M ", c 1,4t. i� 1\1itY,1t 1�i ti 1t�t1 •: t...,,'::1 . tEt 1 1 t1 ttl t t it �t.b..y.,iM1t 4 1t1li��t§�i1.t t� � l,1tti,...�.t...,�;:tt.. ,.4;,1..t . 11 1 . Trunk HxWDuct :^Type.. (in) Material Peak AVF 587 O 106 9,0 10 x 20 ShtMetl Peak AVF 587 0 106 12.6 10 Peak AVF 974 U72 14.6 10 x 22 ShtMetl Peak AVF 974 0,072 14.6 10 x 25 ShtMetl 2015 -Dec -31 M34A0 41+ WrIghYM a..Universal 2015 M0,23:: s, .. Page 3 Job #: 3616 Teller St. Performed by Joe Colbum for: Boe Kampbell 10381 E. 106th Ave. Brighton, CO 80601 Ir ilil,[Zllll I'll 11111 gq!r4«<� 6608 W95th Place Westminster, CO 80021-6422 Phone(720) 354-8105 Scale: 1 :119 Page I t., ».e Universal 2015 15.0.23 RSU18198 2015 -Dec -31 1846:59 .-ShEastsWe - 3615 Teller St. ri I m Job M 3616 Teller St. Boe Kampbelf 10381 E. 106th Ave. Brighton, CO 80601 Authority Air Designs, LLC. 6608 W. 95th Place Westminster, CO 80021-6422 Phone: (720) 354-8105 Scale: I : 119 Page 2 Right -Suite@ Universal 2015 15.023 RSU18198 .59 2015-ec-31 W45:59 �J D * m FRTMM Main Floor a it1C t .,.€.. t€ i I I k ! po IT kixv.m.9. h kg pbL aF €E p!!p iFSXPMm J r I i W CP�ct F 4, Job t. 3616 Tetter St Authority Air Designs, LLC. S � 1 VT Performed by Joe Colburn for. Page 2 Boo Kwnpbd 6906 W. 95th PlvA Right-SuftoO Wvmai 2915 10381 E. 1061h Ave. Westminster, CO 80021.6422 15.9.23 RSU18198 Brighton, CO 80601 Phone: (720) 364.8106 2015-Doe-31 18.45:29 Phone., (303) 734-2936 Fax, (303) 285-7646 ".� .AuftrityAmcom Joe@AuthorityAxrcom ...SLLEaaatsido - 3616 Tore, St.rup ua�xu.EestssdeHeet.com EooKsrn Eeai m • IWO *01, IMWO M, provided giving rise to the claim. The limitation of liability set forth herein is for any and all matters for which Authority Air Designs may otherwise have liability arising out of or in connection with this Agreement, whether the claim arises in contract, tort, statute, or otherwise. 1849UHTIM, WO -mmer -mvj YWJ An F for the particular service provided that gives rise to the claim, subject to the limitation contained in the above Limitation clause. Client agrees that it will not allege that this remedy fails its essential purpose. t..... ...... 0 to a project or Service (the "Reimbursable Costs"), Travel costs are defined as air travel, lodging, meals and incidentals, ground transportation, tools, and all costs associated with travel. All extraordinary travel expenses must receive Client's approval. Authority Air Designs shall provide to Client substantiation of Reimbursable Costs incurred, invoice, Client will so notify AuthorityAir Designs within seven (7) calendar days of receipt of invoice by Client, and if no such notification is given, the invoice will be deemed valid. The portion of Authority Air Designs invoice which is not in dispute shall be paid in accordance with the procedures set forth herein. AGREEMENT By the Client's use of any report, opinion, deliverable, work product, document or otherwise, the Client agrees to the terms and conditions set forth in this document, If Client disagrees with the content of this document, the Client must respond to Authority Air Designs, in writing, within 5 days of receiving the Reports and Designs and discontinue the use of the reports or services provided, �, , . * , , � , . .� , , , . 1�1­_,,, - , `­ , - � � j,:, ,. � � � ", ,� , . . 4::: i�:: ,11�,� � � .,%, -:-: � . " , � I , --:Q�­, " :�, 1 , ::� � - ,. , I . , i �_,, I , � � � � � : - I � ��, . "I - - ., �,q� ::,­ - -�,".-3. � - � � . , , I , � " I , , * ' * , . - -7 - ,. , �, � � I - . :,::� ��-:_ � ,*�-,,� � ,:T', , �, � I �- -,,� � ,­ � , - ,,­�--,, , � � , , , : , I - � , _- � L-t ­,,i ", , � � _ � - , ,,-,!�, j , � : , , . i 1,-��,,,_: I.,", 11-- , '**, . � " � � �, * � . I � �� , I - , : -, , , , - - ,�:, . �V. - - � ,,�:�� , ,�� ,. - ,_ _:_,,N , . , - -1 , - - , � � . , , � I , � � ,, , ; ,,, �:I�:, , , � . , I , � � 'I. I ,�,,­� ,�, ,. I , I ,:� - �, � ---i -,�­: a �i � � � I - " � ,,,. , ,i�:: � [::::�,_,:� � "':�-__ � - i. �/. � , - � - __,:� , :::,�::4:::, , � , - � .::, � - I :::,l , - a � , , J� ... ��? - - lll,� ,�: I , - � 1, A - � I , - . �i,, I-- � , , , � , - - I , 11 * �1, , � � , � , :u'.- - - i � , I , I 1� �- ,,� , , ,, � , , , ,�� , '' I , � , , , , � " _ - : , , � W ,, :!,��:� ­,,,"", , , , ,:: - I- I , ,. ::,�:]�::Ii,:] - , ., � � , , I� � I � . , �� , � � i I ,, , , -, , , , � , , , �� � � - � ,*, � " :�, : , "' '' - ---;�­ � , :: : " , "'..",_ , �, I , I � ., I , . " -, � " i.:, , ,,�i, � :v I, . �, , " , "' , , , -, � �,,,, t ,", I , ",",�,�,.--.-��*::::���,::������ I- - , - � - - , - � . � ,­ � � -, , :,�: IV , , - , I , �, , � ,. >_ � I , .1 " , ::�i,::� , I lll:::�] - , , , , ,�� - �,, .��,,, - , I * , , . " : - I I � - � 11 , " "I", ,T, , , , , I � -, I � , :: � � 1 - : ��:�::� � � , �,��,,-,,_ -, . ��, ,:�--� I :: , � , ,,, � ,-, , , � - , .: i . � .� � , , , � , � . � , ; , , - � ,, ,�,, �v : -: , �, , ,,,,�� , , ,� � � ,��. - - , I � � � , :,�� , ­ � , , ­ , .� , , , ,. . I . , " , , , � : , � I " . "-ul" : -:,,� ., -:::: r � , - rl, � � . ­ � � : - I � � I , , : � I � . � , � - � .� , , � I ,>I , I , ,- " . ":-, :i� , ,-,: , I -:] ,,` :0 --:::_ -,�, �� ,,­­ ,­�,­,,�,,, - , -1 , � ,. , I - , , � � - , ,�� , , , �:, - , . ,� , - , �i�� � , � :- , , , - I . , � . I �, ­ �„.:� , �!� , ,:, , ,� � :�!: , , , , , .. I I - � , ,,� �: I , , , ... � � , 1 , , - ” � � , , � , ­­ I ,•, , , , I " I I ,: - , , , , , , � . � , - , , " , 1� ,!� � I I -,:: ,I - ,:: I . 1- - .- I , , .1 I - I -:::.1 , - J,,:�:!:� ..'', I I,. I , � - �� , � 1, , - � _-., � : , ��:�4 , � ­ � ­,", �-<� lK I , " , � , .� � �:,,, , , , - - -- : , I , , , �_ . �, � ,��,, � ­,� : � � , ,�,, , , " � , I I : . , ,-', - , ;_l, � . I I � ,� � � � " ,:, , i,�* ,.�,, . ,: ; I I 1� I , � � I -:�: ` ,:. ::, I ,� : ":: ., , - " � :::: � :��*:::�:, � , , - , i � I � J�,:� I : , I . � : � , , ­ � � � � I � - , I I , , �,- , , , , � - " , " , ­:� 1, _,il:: �:: I ,1:�,:::�: I � , � J", , ::� -1 - - 11 - - - - � - � , . � I ­'. :,--:I:��:�, I , � , - I 1.11: I I .. " -. ,- -- I I � I - . - ,:, � � - : : � I , , , - - - - � � " � , I< . i-::: �. ,:: � . : I :::� � � � - �. :,, � :: , � - ,�: � I , , , -, , I � I , � I <. ". ,- � ,,�, � ,i� :::" * " 1, i,::�� � , , :::� :�� I ::,,: . �, , : � I I � I I , � , I , , " , " , ,,, ,,, Or . - - , , � I � :, �_� - " : : � ­,", ­­ -� . ,., , , i - � _ � �.: I ,:: - ,:::,�,: I , . � ,,," 11 �, , ` " A " , � . - , , - �! , � � -, - , � , .1 , �� : ., , " "' . � -1-1'-," ­ - - ., - , , � ,.�* . , - , - , � .,<, . , : � I" . , , * : ,,*�,, - : "',"', - � ,, I , I "" , � � ,,, ­."', � ,,.-,.,-,, z, � -:�i< - �,,,, I , - -:�,�,�:: , :- -. -- , -: � , : � , , ,., � , , , � I ,­ . , V � � , , , � I - 11, ,;�� � 'i", � � - - ,� , " �� . ,��.� �< , ,�; , - f I -,,­:� . � -11�, � i _1 � � , ,". � , I , '. , •I )lj , I I � : , ::-": , I � : ��­ , , 1, ;:,** :tl% :� , , , I , �,� _�­ �,i , - :-� 0 � -- � - I � ::?.� - , I --,. :', * :;J:,, � -- I . . , I I I � '. � � I I � - - . � , , - - - , � I I � : I I : � I � 11 , � , , . ".4- .., .- , , � 1 , -, -, ,11: " . , , , ­,-, �, -, , � , , , ,. ., � � ` - ." ­ ,� . � ,� - I - -, , �-_, - � - - "' , ;,- , * - . , I , - - - , �::� . , � , � I I � . � . I .1. I , : : "!: , , ,;,: I � ,11-1.1-1 i "."i,l " , , I. , , . , I . t .. � � , I � � � � , , , � .1 - , - - � ,�-. , , , � - - , -,, � , _�,I,� , I !-,:: 4 - '""i :, .- ,. � � , ��,� A-11 , � - - � I I - I - , , , ,�:, I- I I , , , ,_ �? � . , -, � ,­, ,*,�,� , � ?:� . ''I ,;� : � - , I I , � , I ,,La,� , 1, � ,,� , , I I I . I , , . ,�,­ " " � � � - . � - � ., I , . . . . , � , � - , ,�� , , ,- : ,-� i � �i � , � � ,,�, i � �r�,. � , —, � '' � 1� � � , � . � - � ,l ,!:', ; , — , � , ­ I , "" � .., I � , 1, , � , , �> . � � � . . . . , __ --, �, � ,v- � �� , , , kh:::', 'I,���i,-,:, � ::: �, � � ",, - , � ,11" , -:: - �:: � ,, � . , ,. � " [:�,� , � ,�:i, I : ", , '- � , ,��"�:�I'�::�:��.":: � I I , � I , � " . I , � ., I , � ", , , 1414 ,-,�i� � , . _*::'. .,,-��:, , — i ,: - , I � _� -I,- ", -,!,:: � ,- ,-< � ,, � ";, , " " � ,,� � ,:: � " , " ''., , �:��,,�� � �:::,�T:�::,,,,:::I� " �v:: , ,��:, � , � , � 4, � , , , , �� , � �,!,�::i I � � � . , I : ,_1 �,�:-.., ., I 1, ,,�-, 1— 1, � , � � � ,,J,. � _��-� ,:!, i• � I � . i .� - 11 ", . , 1, i i .I.: � ,,:-�:::: � ". ::" , , � , ��,,, � - � . � I �, . ,:.*, ,,, . I , ., � ,,,*:,­, : � � . , ,�, � � � � � i — , ­ , ,,, , -', -::,,,,- ,_ I ,,!�, � ", , � � , � � _ , , � ,­ � ,::-�,: ­:-,,,�,,�,: Il ,`�, � � ,; ,, " .�,, � " �,., ,� , , , � , , , _ ", �,*::�l�, " * "T"11-1. _11, �­ II � — � �:::::, , l . , I I - I I , I � .I,,. , �� � �-� ., 1�1 �,, � -­ � , � � , . ,.!:,,:. . �K,� , � � , ,,:! � --,�: .. ",�, I � � , �. :,., � � , I , , I � . , - , , ,,,, , : �tl� � . � , ­ ,-,- � ::-*:: -, :,,,**� � , � V*, � : "' � . :::�, * , i ��, �:t: � ., ,% .11 � . . ` : — , � , . � , . I, �., - — � � — � , ,,: , ., ­ , , - ,, . "'; ".­ . � . ,:,, � � � I _. , * , , * , , -, , - , , , , , , , , * , , , , , , , , * - , , , ­_ , , , , - " , * , , * , , , , , , , , , , , , , , * , , , , , , , , , � ,_- -- I - - I I - I , , - 1-1 � I � I I- � - I — - — -, __ I- I I- � __ 1 � - "' , I - - I �_ I ­ I.- \`__�__ , , , , , , , � I � '. I I � - - I � � � ; -"-,-- "' ",-- , I I - � � I - - - I ­ � - � ­ - ­ - _­ ­, - - ", " -, �- ,. :�-�, � �.:�­,,� � ,,, � ,�, � - , � � � , : " , , � � ,.- : � , , : , � � � . ,- : ,;,: : � � �;, : - -,A - :A � � .-,,7-. ,:,,,,� , � , , ,,;t­-� - -, I � � .,*� :* i--::.* i - � " - -- < , A � , � , I , � ,", : i, - � I _ � . � , : �. , - , ­ I I , I , i -J, I , , � , , :,�:::��] , � ,��> , ,,,�I,,� I � � , , � : � - ,� � ,,,.„,,�,,,,: � . , � � ,. , � �� � � � , � � � , ".*_1 i,w-* I . � ,_i_ , .., - . � � i i � . ”" _�__. ,,,,,� � ., � * � . � ; ":", � ,, � � ` . , :: , : . � ,� , � ' D. . ". . ,. * �� , . � : . ., ., , ' � 1, � — — I :� �NO.- . .t�, I , - - t: `­: *�, �: . . I , � * . . . .. � I � : , i , �, ,,:�,, � �,;������ * *,,� -.i.- fflmmwwlr__��� 1p, w m m 0 92 3(olS TEJ�EK 5�- f NilMiTek" MITek , Inc. 7777 Greenback sane Suite 109 Citrus Heights, CA, 95610 Telephone 915/676-1900 Re: 3615 Teller v2 Fax 916/676-3909 The truss drawing(s) referenced below have been prepared by lv iTek USA, Inc, under my direct supervision based on the parameters provided by ProBuild South (Littleton, CO). Pages or sheets covered by this seal:. 846103248 th u 1.46103268 My license renewal date for the state of Colorado is October 1, 2017. Lumber design values are in accordance with ANS1t I M 1 section 6.3 These truss designs rely on lumber values established by lathers. IMPORTANT NOTE: Truss Engineer's responsibility is solely for design of individual trusses based upon design parameters shown on referenced truss drawings. Parameters have not been verified as appropriate for any use. Any location identification specified is for file reference only and has not been used in preparing design. Suitability of truss designs for any particular building is the responsibility of the building designer, not the Truss Engineer, per ANSI/TPI-1, Chapter 2. 1 *.#0006 PE -46766 December 11,201 5 j- ernandez, Marcos The seal on these drawings indicate acceptance of professional engineering responsibility solely for the truss components shown. The suitability and use of this component for any particular building is the responsibility of the building designer,, per ANSI/TPI 1. s -r' in 3-ae 2-0,0 Scale - 1 A2A 4x4 9 10 33 32 3130 29 28 27 26 26 24 23 22 21 20 3A LOADING (ptiff SPACING- 2-0-0 CSI.. DEFL, in (toe) Well Lid TCLL 30.0 Plate Grip DOL 1,15 TC 0,51 Vert(LL) -0,11 17-16 n/r 120 TCDL 10.0 Lumber DOL IAS SC 0A3 Vert(TL) -0.1917-18 nir 120 BELL 0,01 Rep Stress Incr YES We 0.75 Horz(Tt) -0.03 20 n/a We BCDL 10,0 Code IRC2012fTP12007 (matrix) LUMBER- BRACING - PLATE$ GRIP MT20 197/144 TOPCHORD 2x4 SPF No.2 TOP CHORD Structural wood sheathing directly applied or 5-10-16 oc puffins. BUT CHORD 2x4 SPF No.2 BOOT CHORD Rigid boiling directly applied or 5-8-1 oc bracing, WEBS 2x4 SPF No.2 OTHERS MiTek recommends that Stabilizers and required cross bracing 2x4 SPF No.2 be installed during truss erection, in accordance with Stabilizer Installation guide. REACTIONS. All bearings 18.4-8, (to) - Max Herz 2=-60(LC 14) Max Uplift All uplift 100 Ib car Bess atjoint(s) 27,28,29,31, 32,33,25, 24,23,22 except 2=-178(LC 33), 26-182(LC 13), 20-419(LC 13), 21--707(LC 22) MaxGrav All reactions 250 to or less at joints) 27,28,29,31, 32, 33, 25, 24, 23, 22 except 2=265(LC 32), 26-629(LC 1), 20-1043(LC 22), 21-322(LC 13) FORCES. (to) - Max. Comp./Max. Ten. -All forces 250 (to) or less except when shown. TOP CHORD 2-34-9291866, 3-34-9221902, 34=486W8, 4-5-8630891, 5-6--8381890, 6 -35= -812J$74,7-35--807/889,7-8-780/894,8-9-728/878,9-10-722/881, 10 -11= -757/900,11 -36=-775/895,12-36--779/874,12-13=-805/897,13-14--831/892, 14-15-7631786,15-16=-8831902,16-37--8911914,17-37-902/846 BOT CHORD 2-33-829MO, 32-33=-8291948,31-32-8291948,30-31--8291948,29-30--8291948, 28-29--829/948, 27-28=-629/948, 26-27--829/948, 25-26-8291M,24-25=-829 8, 23-24--829/948,22-23=-829/948,21-22-8291948,20-21=-829/948,19-20-8291948, 19-38-829/948, 17-38--829/948 WEBS 9-26=-602/492,16-20-406/400,14-21-250/225 NOTES - 1) Unbalanced root live loads have been considered for this design, 2) Wind: ASCE 7-10; Vult=126mph (3 -second gust) V(IRC2012)=100mph: TCDL-6,Opsf; BCDL-6,Opst; h-26ft; B-45ft; L-24ft; eve -211; Cat, 11; Exp C; enclosed; MVVFRS (directional) and C -C Comer(3) -2-0-0 to 1-0-0, Exterior(2) 1-0-0 to 10-11-0, Comer(3)10-19-0 to 13-11-0 zone; cantilever left and right exposed: end vertical laft and right exposed�C-C for members and forces & Mt RS for reactions shown; Lumber DOL=1 .60 plate grip DOL -I A0 3) Truss designed for wind loads in the plane of the truss only. For studs exposed to wind (normal to the face), see Standard Industry Gable End Details as applicable, or consult qualified building designer as per ANSIITPI 1. 4) TOLL,:: ASCE 7-10: Pr -30.0 pill (roof live Lumber DOL -1, 15 Plate DOL -1. 15); Pf-30Z psf (flat roof snow: Lumber DOL=I, 15 Plate DOL -1.15); Category It; Brig C; Partially Exp,; Ct-1.1 5) Unbalanced snow loads have been considered for this design, 6) This truss has been designed for greater of min roof live load of 22.0 par or 1,00 times flat roof load of 30:0 par on overhangs non -concurrent with other live loads, 7) All plates are 2x4 MT20 unless otherwise indicated, 8) Plates checked for a plus or minus 5 degree rotation about its center, 9) Gable studs spaced at 1-4-0 oc, 10) This truss has been designed for a 20.0 Pat bottom chord live load non current with any other live loads. A WARMANS - VWWx d.10. pentaterots, sed READAVOITS ON THIS AND INCLUDW WrVK REFERANCE PAGE W7471 fee 14032015 BEFORE USE Mvafid for, tom The design, is based or upon corron-eters shown. and is for an individocil bottling coorponent, not I stem b relsf; designer must verffy the oppirloo ty of design pato fess end property Oar rate this design into the overall :foreMyerIneMbuil inconnec bukifixtcles%in, firacing fridicoted is to prevent buckfiret of indAdud truss web and/or chord tnernbess ony, A. °. teffpwcry and pefnionentbroc.hg is ahatys requked for stobffly and to prevent collapse Wth pos0bre persond intury and property darooste, For generd guidance regarding the toledcofk)m storage, delivery, erection and kyackv of trmser and truss systetm, see ANS111frn QuattyCaterio, tegaq and ECS1 guildea Component Sattlyfisfismallon avoloble from True Plate hstrfute, 218 N, Lee Street, Suite 3 AtexancirktVA223i4. I December 11,2015 ....... ... I.W I =,P- 11) * This truss has been designed for a live load of 20,Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-" wide will fit between the bottom chord and any - other members, 12) One RT3A USP connectors recommended to connect truss to bearing walls due to UPLIFT at A(s) 2, 26, 20, 27, 28, 29, 31, 32, 33, 25, 24, 23, and 22. This connection is for uplift only and does not consider lateral forces, 13) Two RT3A USP connectors recommended to connect truss to bearing walls due to UPLIFT at (t(s) 21. This connection is for uplift only and does not consider lateral forces. 14) Non Standard bearing condition, Review required, 15) "Semi-rigid pitchbreaks including heeW'Member end fixity model was used in the analysis and design of this truss, AWARMNG- V-YYd--IW1P--0..W WAD NOTES ON TMANDINCLUMOMYEKREPER4NCEPAGEW7471mv. 14""15BEFOWUSE, In 1, o `*C ond is for on indIviduol bvlddng conVoneni, not vo " v` O'�� re_ "e d incoWrole Ibb P11 PrOWY detion hro the over(A 8, -g iriddcateds I only, Add*mol len4x"V and pffmanent brocaV cYs i gg; �ge, Fax Qenwoi rividonce regording the d -1ertaie .r C41o", OSS-Iff and ICS1 Bo#dhV Compmont T 14� 7777 Greenbw* Lane suite 109 Oftroti0ghts, CA 956}0 - -•.-� ;r Rua .. 7V^A't^U 15-99.10 21.10.0 23-10.0 20.0 5^90"8 5-EY`1Q .... .... 5.0-10 ...5^10.6 ... 2^0-'4.:. Beale - 1:42.4 Rim 13 3X4 w— 3x4 3x4 3X4 U10 3XIG LOADING lost) SPACING. 2-0-0 CSI.DEFL. In (too) i!defd i1d TCLL 310,0 Plate Grip DOL 1.15 TC 0.97 Vert(LL) -0,17 8-10 >999 360 TCDL 90.0 Lumber DOL 1.15 SC 0.85 Vert(TL) -0,35 6-10 >756 240 SCLL 0.0 ' Rep Stress Incr YES WB 0.99 Horz(TL) 0.t37 6 We We SCDL 10,0 Code 1RC201 PI2007 (Matrix -M) nd(LL) 0.19 8-10 >999 240 LUMBER- RACIN - I Or CHORD 2x4 SPF 165OF 1.55 TOPCHORD Structural wood sheathing directly applied, SOT CHORD 2x4 SPF 165OF 1.5E `Except., BOTCHORD Rigid ceiling directly applied or 10-0^0 oe bracing, 2-9:2x4 SPF 1,0 2 Was reccrrnmends that Stabilizers and requited cross bracing 55 2x4 SPF No.2 MOGE be installed during truss erection, In accordance with Stabllizer Installation guide, Right, 2x6 SPF 9 Po,BE REACTION& (lb/size) 2=117710.5-6, 6-132710^7-12 # # # # # « # l ».t :Mt :t.:f. .tet:^^ t Y Y ♦•. .. t. :t'• M M:..`M t t.:^.» � «� tt ..• t # t # ..: tw Y„:r t' I # t..: t „. i ... ♦». t... Y 't :♦ »: M»i: t' I #w... i. - ♦ ♦. M t . . '”. M • # w... # t.. t♦ t.M w t M! t ♦ M^ # ... • ♦ ..♦ ". t f.^t t M Yt.., a...t ♦ w t ♦ :t.. t." WAMOGr. i+IM9Tydi#ogtM P#r#rvn#f# #»d READ NOTES ON "M AND M(CLUDED OTEX REFERANCE PAGEMP7473 res+. fdA7t120IS BEFORE USE. TMVoldfor use only vAth ANTeW carnedws. This design to based on upon Trac tern shown, cared h for an OW9,Aduoi buPdd co nt, meat sysie . Before use. the txn7d designer must ve fp the oppl ab ty of design par tern acrd property hcwpeuote this design into the overaf building design. d ing indicated b to prevent buckling of individual truss web Writer chord asernbers onty. Additionol femsxwary and Ssenryse e nt bracingy is ONKVs ea N and to prevent colopse Win possible penisnor irigury and property darrxage. Feu generd gluldonce regarding the fsrbrk,oflon. storage, defivery, erection and bracing of trusm and truss systems, sale ANSI/Mt Quality Cessfe, 0$9.89 and $CSI a i; Crisrspiet SaWykildostallon avokible from Truss mate institute. 218 N. Lee Street Suite 31Z Alexandria, VA 22394- December11,2015 MM • *^ „�. 7,640 a Sap 2x12415 Mfrek industries, its. Thu tae 10 15:03:46 2415 Page 1 IOOSsAPQtgttf97gZt �,05zYFFE mnLSM9? rOZSpa9IHd3is6_T4ari7. AI, 10.11-0 ^2'40 5.90.6 ..,,. ,.. ; 15.11.10 «14 _. 210 _.... 23-10.0 2.40 6-10-6 5-0.10 5.0-10 5.10-6 . . 2-0.0 Scale = 1:42.4 4x4 4 3x6 3x4 3x4 30 3x8 LOADING (psfj SPACING- 2-0-0 30.0 Plate Grip DOL 1.15 TCDL 90.0 Lumber DOL 1.15 BCLL 0.0 ° Rep Stress Incr YES BCDL 10.0 Code IRC2012tTP12007 8-10 LUMBER - 360 TOP CHORD 2x4 SPF No: Ven(TL) BOT CHORD 2x4 SPF No.2 8-10 WEBS 2x4 SPF No.2 240 CSI. DBFL. in (too) I/clots Ltd TC 0.63 Vert(LL) -11.15 8-10 }999 360 BC 0.64 Ven(TL) -0.33 8-10 -799 240 0.17 Horz(TL) 0.08 6 We nits (Matrix -R1) d(LI.) 000 8-10 >999 240 BRCING- fight. 73 Ib FT - 0% RigidTOPCHORD Structural wood sheathing directly applied a 3-1-11 oc purlips, SOTCHORD ceilingd MiTek recommends that Stabilizersrequired cross bracing be during truss erection, in accordance with Stabilizer FORCES.Installation ouide Max Herz 2-60(LC 14) yComp./Max.t or i TOPCHORD 2-3--2396/462, t t 5-6-23961462 BOTCHORD +9-10-192/1517, B-9-192/1517, 6-8-367/2212 NOTES - 1) y. * * ! #u rt.. t► ... # - i t • to ,. 13-11 -0 zone� cantilever left and right exposed ; end vertical left and right exposed"C-C for members and forces & MWFRS for reactions shown; ..r DOL -1,60 plate5# 'a t Category3) TCLL� ASCE 7-10; Pr --30.0 pat (roof live load: Lumber DOL -1, 15 Plate DOL -1 15); Pf--30,0 psf (flat roof snow� Lumber DOL=1 15 Plate 4) Unbalanced snow loads have been considered for this design, 5) This truss has been designed for greater of min roof live load of 12,0 Pat or 1.00 times flat roof load of X0 par on overhangs norrooricurrent with other live loads, 6) Plates checked for a plus of minus 5 degree rotation about its center. 7) This truss has been designed for a 10,0 psf bottom chord live load nonconcurrent with any other live loacs 8) * This truss has been designed for a live load of 20,Opsf on the bottom chord in all areas where a rectangle 3-6-0 tali by 2-0-0 vAde will fit between the bottorn 9) One RT4 USP connectors recommended to connect truss to hearing walls due to UPLIFT at #(a) 2 and 6, This connection is for uplift only and i elateral t. 'Semi-rigid plichbreaks includingMember i fixity modelused in the analysis and design WA NANO • Veft d.19. paratrW. and ftAD NOTES ON THIS AND INCLUDED AtTEK REFEFtANCE PAQaEWT ff,? mv. 4t+V0"015 BEFORE USE. 02me rase witty lR6FeA eonnectors. This c#assagniztsasedcwsilyy vpern przraetenshavwt, ds Fru sirs&tdsduadbuild' ea ernt, ¢uat efae use. tfie btsbkS'a'ag designer must v�.rity the appPRicobtGh' of des&gn'a Por tens and pr ire rata this n into Nae i}VBt oh9a'co-cdn atcd*cczfed is to prevent bvckfha of indtvtduo3 truss web on ddcr chord neer nbg . g onty'. Rddit". t . tsrud rserrvteaneni broetng d Fpr stability and Po prevent ca ewebs poseble persona! injury rand pro FY drama e For moi guidance r rditel tare , drr, itVery.. ereeP,an arad ktrac:wrg of tanses ari d truss sWettd. see ANSt/it99 C 00, DSS -91 and SCSI Co ponent an av irCYrax Truss PktYe Institute. 218 K Cee Street Smite 312, Alexandra, VA 22314, December 11,2015 4x4 4 3x4 3x4 3X4 LOADING (psi SPACING- -0.0 C t, DEFL. in (tae) Udell Ud PLATE$ GRIP TCLL 30,0 Plate Grip DOL 1"15 TC 0,61 Vert(LL) -0,15 7.9 >999 360 MT20 1971144 TCDL 10.0 Lumber DOL 1.15 BC 0.64 Vert(TL) -0.33 7-9 >796 240 HELL 0.0 { Rep Stress Incr YES WS 0.17 Horz(TL) 0.08 6 nta me BCDL 10.0 Cade IRC201 PI2007 (Matrix -M) Wnd(LL) 0,10 7-9 >999 240Weight: 70 to FT = 0% LUMBER- BRACING - TOP CHORD 2x4 SPF No,2 TOP CHORD Structural wood sheathing directly applied or 3-2- 10 ac purlins. BOT CHORD 2x4 SPF No,2 BOTCHORD Rigid ceiling directly applied or 9-3.8 ae bracing. BS 2x4 SPF No.2 Work recommends that Stabilizers and required cress bracing be installed during truss erection, in accordance with Stabilizer Installation_ guide. C it Max Herz 2-64(LC 15) Max { FORCES(14) -Max, Comp,,/Max, Ten. -All forces 250 (lb) or less except when shown, TOPCHORD 2 -3 -24"474,3 -16=-21031398,16-17--2092/406,4-17-20351417,4-18=-20,501425, 5-18-2118/414, 5-19--23611477, 6-19-2422/467 .• {'r2-9=40012220, 8-9-22611526, 7-8-22611526, 6-7-39412240 WEBS 4-7-761712, 5-7-531/188, 4-9-701675, NOTES - 1) 13 -11-0 zone; cantilever left and right exposed; end vertical left and right exposed;C-C for members and forces & MVWRS for reactions shown; Lumber DOL=l 60 plate grip DOL -1,60 DOL-1,15)� Category 11; Exp C; Partially Exp,; Ct-1.1 4) Unbalanced snow toads have been considered for this design. 5) This truss has 4.. designed { greater of min roof>a of # psf or 1,00- roof load of X0 s. f on overhangs non-concurrentother live toads, 6) Plates chocked for a plus or minus 5 degree rotation about Its center, 7) This truss has been designed for a 10,0 pal bottom chord live load nonconcument with any other live toads, 8) * This truss has been designed for a live Brad of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 ivide will fit between the bottom chord 4 any other members, 9) One RT4 USP connectors recommended to connect truss to bearing walls due to UPUFT at fte) 6 nd 2, This connection is for uplift 4 and o ♦ consider aforces,.. 10) "Semi-rigid pitchbreaks4 4 fixity model was used in the analysis and designof WARMNO . Y. y gxr .d READ tIOMSOtiTWAtiOWCLODEONTEKRMPANCEPAGEWI4IJtw. raoxmit BEFORE USE, Destgn void for use only Wth h47e t connectors This, design is based ae�y upon poo tens strown, b for on 6ndivVJvd b inn corrtponent, rout a true system . Befcae use, Vie b kt& g des gne mus# v the app acobtGty of design parameters and Karo h' krc ate this design retia the overati ffi deegn, Broci ng indacoted is to prevent t uck1h g of ineyAdvol fnsss vyeb sand/or chcvd nvoribers, only. Additiorrol himpotary and peunarrent hrocki Is otyrars reqvited for stobttty end to prevent ca se with possibie perse m -A herry and property unmade, Kix genord guidonce regarding Etre f atiots storage degverY. ereef on and brachg of trusses acrd truss cyst—, se: ,#/1111 C a, D5B 4 end 4CSt 0. g Conese sent Safety lydasnnascan a e from Truss Prate#nst74ute. 218 N e Street, Surto: 312. Agar , VA "'"*314, IN a W-0 4-11-5 5-19, 8 2-0-0 Scaie - 143,2 2X6 Us 13 3X4 20D 12 11 10 9 8 3X4 Us LOADING (psf) SPACING- 2-0-0 TCLL 30,0 Plate Grip DOL IAS TCDL 10,0 Lumber DOL 1,15 SCLL 0.0 Rep Stress Incr YES BCDL 10.0 Code IRC2012MM2007 LUMBER. BC US TOP CHORD W SPF No,2 -0.0516-31 BOT CHORD W SPF No,2 240 WEBS 2x4 SPF No.2 Horz(TL) OTHERS 20 SPF No,2 n/a CS1, DEFL. In (loc) Vdefi Lid TC 0,63 Vert(LL) -0,0215-31 >999 360 BC US Vert(TL) -0.0516-31 >999 240 WB 0,17 Horz(TL) 0,01 8 n/a n/a (Matrix -M) Vvind(LL) 0.0175-31 >9W 240 BRACING - WeighL 88 to FT=O% TOPCHORD Structural wood sheathing directly applied or 6-0-0 oc punins. BOTCHORD Rigid ceiling directly applied or 10-0-0 ocbracing, Except� 6-0-0 oc bracing: MiTek recommends that Stabilizers and required cross bracing be installed during truss erection, in accordance with Stabilizer Installation We,, Irecember 11,2015 A WARWM a V.0 design j..f. >4t d READ stores ON MS AW flWUMW hMK RMAAMCE PAGE MP74.73 rw, 1"34015 BEFORE USE De I ro'on I '1h M o� len. iasis do, bu y EFot-d b;7 ing Fs 1- d .d bracing of #ra.«sses nand tease syatarv.. ANS4/IPii . D59-8$ need @&Si 8 rag Caamp srt $.Qan auaiabisn '0n' Yrans f*kafe Xasti#ufa. 23#3 N. t. Street 5ui9e 3i2, Adexern . YA 23l4„ Jab Truss Truss Type Qty fey 846103292 3BS5;T"Et.LE'R_V7 +.of ;$eassrar +.9 i PfOB. ... JO, , eferer _ {opt l) . 7,64a s 29 2016 Wes $ Wend , 0 , Inc. Thu...Dec 10 M03:1F 2015 Nfie 2 10'98sAP09gtdf17gatDGu_05xY6F ®VxosLIplOgsbU oQukJSRKeJKBwH JkPSCgcyAlud t 3) One RT"4 USP connectors recommended to connect truss to bearing walls due to UPLIFT at jbs) 6, This connection is for uplift only and does not consider lateral forces. 14) "Semi-rigid pitchbreaks including heels" Member end fixity model was used in the analysis and design of this truss. WARNfri6 - Y dealgn p tis and READ NOTES ON DO AND WCUMV WYEK REFERANCE PAGE W7413 rev, f"W015 BEFORE USE. Design vakd for use, onEy with AN`feP cearanectars. this des #n is ba s psr teas shown. 0 for an indhndud buSd"sng c en9, not a mess stafern, Betore ose, the building designer must verity the a=' iy of deOgn de'poron x0en and propedy ieac ate this dfndgn into the overzafl I btidestpsw, 8aacing indtca4ed is #a prteverai trucklaz7g of ine3tvidvat andlar chorcd nae Add6t` fe aay card p. hent Lrechg '. €s s re�arred Oar sfcab2rty arxi fo prevent caasapza wh4h possi per ir' 4xape+tY dctnxage. For erg gsxkiesnce se dkag the tatxicat an, sf x defYvr r , e erfk n a l k c ca g of f uses s*s S f uns sYste s, see A Sf(TP19 a C a, 650 fi4 and @ Std ng Cexrrpanrnf 7777 Gr back Lane So t assn avakabte N rn T uss Pk #e &astltute. 2F8 h ,tee Sf set. Su to 332, axa Va 3t4. $sake 109 ovv go15-10-8 21A(SID 23-10H0 2-0-0 4-10-8 4-11-8 5-11-8 2.0-0 Srale, -1:43,2 M!!l= 0 LOADING (psf) SPACING- 2-0- T TCLL 30,0 Plate Grip DOL 1,15 TCDL 10,0 Lumber DOL 1,15 SCLL 0.0 Rep Stress met YES BCDL 10,0 Code IRC2012(TP12007 LUMBER - >999 TOP CHORD 2x4 SPF No.2 BC 0,66 BOT CHORD 2x4 SPF No.2 -0,35 WEBS 2x4 SPF No.2 >539 CSL DEFL, In (too) Ideff Ud PLATES GRIP TC OV Verbl-L) -0,13 8-9 >999 360 MT20 197/144 BC 0,66 Vert(:TL) -0,35 8-9 >539 240 AS 0,37 Horz(TL) 0.11 8 ore his (Matrix -M) \Mnd(LL) 0,06 9 >999 240 Weight: 72 to FT = 0% D Structural wood sheathing directly applied or 3-8-1 oc puffins, BOTCHORD Rigid ceiling directly applied or 5-7-6 oc bracing, WEBS I Row at midg! 4-8 MiTek recommends that Stabilizers and required cross bracing be installed during truss erection, in accordance with Stabilizer lstatlatla7n quids, REACTIONS. (Itilsize) 2-82610-5-8,6-124/0-3-8,8=155310-5-8 Max Herz 2=60(LO 15) Max Uplift 2-196(LC 16),6--153(LC 32),8-202(LC 16) Max Grav 2=850(LC 21), 6- LC 33), 8=1553(LC 1) FORCES. (to) - Max, Comp,/Max. Ten, - All forces 250 (lb) or less except when shown. TOP CHORD 2-3=-223M96,3-16--1411/167,4-16-13181178,4-17=-7611161, 5-17-8619098, 5.18=-137191602, 6-t8=-1 S&I 157 BOT CHORD 2-9--288t2317,8-9=01396,6-8-10671244 WEBS 3-9---8591286, 4-9-4311187, 4-8-17661264, 5-8-562/190 NOTES 1) Unbalanced roof live loads have been considered for this design, 2) Wind: ASCE 7-10: Vult--126mph (3 -second gust) V(IRC2012)-1oomph; TCDL-6.0psf; BCDL=6,Opsf; h-25ft; B-45ft; L=24ft; eave-4ft; Cat, 11; Exit C; enclosed; MWFRS (directional) and C -C Exterior(2) -2-0-0 to 1-2-5. lnhsrkir(l) 1-2-5 to 10- 11 -0, Exterior(2) 10-11-O to 13-11-0 zone; cantilever left and right exposed; end vertical left and right exposed;C-C for members and tomes & MWFRS for reactions shown; Lumber DOL -1,60 plate grip DOL -1,60 3) TOLL: ASCE 7-10; Pr --30,0 pat (roof live lead: Lumber DOL -1.15 Plate DOL=1,15): Pf=X0 par that roof snow: Lumber DOL=1.15 Plate DOL -1,15); Category it; Exp C; Partially Exp,; Ct-1,I P190 Lit 4) Unbalanced snow loads have been considered for this design. 5) This truss has been designed for greater of min roof live toad of 12.0 pst or 1.00 times flat roof load of 30,0 Pat on overhangs P, HP 0%. non -concurrent with other live Wits, 0 6) Plates checked for a plus or minus 5 degree rotation about its center. 0 7) This truss has been designed for a 10,0 pat bottom chord live load nonconcurrent with any other five foads. 8) - This truss has been designed for a live toad of 20,Opsf on the patient chord In all areas where a rectangle 3-6-0 fail by 2-" wide will 6766 m *6 fit between the bottom chord and any other members, tv 0 9) Beating at joint(s) 2 considers parallel to grain value using ANSVTPI I angle to grain formula, Building designer should verify capacity of beating surface, 10) One RT4 USP connectors recommended to connect truss to beating walls due to UPLIFT at JI(s) 2, 6, and 8. This connection is lot. uplift only and does not consider lateral tomes. 'Semi-rigid Ceeaeow 11) pilghbreaks including heels' Member end fixity model was used in the analysis and design of this truss, A WARIWARt - V.* d-11011 P..1. and READ NOTE$ Oef THIS AND WOLUDED AWMK REFS CE PAGE "P7470 to, taAP9120158EFOREUSE �e ,;jn4old for use only Win Wetysconnecton INS design, is based on upon porometers shown, end is for an indNidoa buldino, component, not shen a. pro vsc the buR ding designer mal verify the aprdicoMly of design par tars end prossorly hcorporoto in* design into ton morsto buiWingdeson. Srannng indicated is to prevent bvckRng of insfividura truss web ondlor chord trerreNiNs only, Additkmoiteniporaryand onentbrochg Is aWays re oiked for stobitify end to prevent colopse With possitste penonot " and property dorrisme. For general gtAdonce rding the lobrication, storoge. deOvety, erection and bruchor of tmases end Inns s"ter-, - ANSI/MI QUOWCil 04*,DSS-SgaftdSCSI Baso dhVComponent 7777 Greenback Lane Solely information avolobie from Inas Piate institute, Vit N. Lee Street, Suite 3M Aiexonddo, VA 22314, side 1409 06 4 Us 3x4 3x4 3sc4 3x4 LOADING (psf) SPACING• 2-0-0 38.45 Plate Grip DOL 1.15 TCDL 90.45 Lumber DOL 9.95 BOLL 0'0 ` Rep Stress incr YES BC£DL 145.0 Code IRC2012JTPI2907 LUMBER - SC 0,49 TOP CHORD 2x4 SPF No,2 -0,1910-13 BOT CHORD 2x4 SPF W1 240 WEBS 20 SPF No.2 CSL DEFL in (ft) Well Lid TC 0,52 -0,0710-13 >999 360 SC 0,49 VerflTL) -0,1910-13 >999 240 we 0.75 #: 0,0310-13 +. ight: 73 to FT -O% *#!Structural+asheathing directly appliedor oc purists. BOTCHORD Rigid calling directly applied or 61 # A bracing, MiTek recommends that Stabilizers and required cross bracing be installed during accordance with Stabilizer Max Herz yt Max r t Max Grass 2=961(LC 21), 8=1220(LC 1) 0 FORCES, s. . A.. Ten.forces or less except TOPCHORD 2-3=-166,V320,3-17=-1069/201,4-17-9731212,4-18-0/345, 5­18-0ra(), 5-19-381350, 6-19-571346 ; 2-10-20911433 WEBS 3-10-6241215,4-10--33/613,4-8-10891187,5-8-5531191 NOTES- 1) Unbalanced + loads M been A...F A design, 13-11 -0 zone; cantilever left and right exposed; end vertical left and right exposed;C-C for members and forces & MVVFRS for reactions shown; Lumber DOL -1.60 piate grip OOL-1.60 3) TCLL� ASCE 7-10� Pr=30.0 par (roof thre load� Lumber DOL=1,15 Plate DOL -1,15); Pf=30,0 Pet (flat roof snow: Lumber DOL -1.15 Plate i r 4) Unbalanced snow loads have been considered for this design, 5) This truss has e designed forgreater of ♦• 12,0 # times flat roof♦.d of 30,0 psf on overhangs non -concurrent oat 6) Plates checked for degree rotationabout its center, 7) This truss has been designed for ► t psf bottorn chord live lead nonconcurrent with any other live lraY.: 8) * This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom h w ♦ and any other 9) One RT4 USP connectors recommended to connect truss to bearing walls due to UPLIFT at Its) 2, 8, and 6, This connection is for uplift only and does not consider lateral forces, 10) "Semi-rigid fiftchbreaks, including heels" Member end fixity model was used in the analysis and design of this truss, WARMNO- ViwilydWitafteramatani and READNOTES ON TM AND WCI.WV"D TEKWF"A"CEPAQEW7413rev, 14934015 BEFORE USE. design vo#d for use only with MffeM connectors, This design is b ando upon u tees shovm, and is far onndividuol bWdk ro pareent. not truss system. Before use, the t«uaiiding des' e nwst ver4fy the cnah° of design paroareters erred property incorporate this n Into the overdo bvkfhg design, Brocird indicated is to prevent buckfi rg of " ai truss web and/or chord rysernbers onty. Addtionof temporory and pennoneni brocing is oiwoys secured for Mondry or d to prevent colissism Wth possibie persond e4ury triad prop" dornage. For generoi guidance regarding the fofxicot on, storage dersvery, ensc#`son and brocing of irvsaes avid tress systeruns, zee AR34/urtt QvalftyCdfiyda« OSS -89 and SCSI OuNdIng Component Safety Information ovatable fusm Truss Notre hstitute. 218 Pte Lee Street, Sartre 333, r,iaxandraa" VA 32314, Deoember11,2015 7777 Greirstrifsk Lane 109 2-0-0 7 __. 70-0 2-0-0 Sciffe - 1:29 6 0 U4 LOADING tp SPACING- 2- est. DEFL. in (loc) Vdefl Ltd PLATES, GRIP TCLL 30.0 Plate Grip DOL t.t TC 0"31 Vert(LL) -0.03 9 nlr 120 MT20 1971144 TCOL 10.0 Lumber DOL 1 A 5 EC 0.11 Vert(TE-) -0.03 9 nir 120 BCLL 0.0 Rep Stress Incr YES VVB 0"04 Horz n) 0"00 6 nla ria SCDL 10,0 Cade IRC2012iTPI2007 (matrix)Weight: 47 to FT - 0% LUM ERBRACING. TOP CHORD 2x4 SPF No,2 TOP CHORD Structural wood sheathing directly applied or 0 oc purlins, OT CHORD 2x4 SPF No.2 SOT CHORD Rigid ceiling directly appy or 6-0-0 oc bracing, OTHERS 2x4 SPP lslo.2 MiTek reeornmelds that Stabilizers and required cross bracing be installed during truss erection, In accordance with Stabif6zer installation guide. # # # # # i w a Y # tt V 4 # J! # # #---------- AWARAMO. Vivify dift0on parairsoferi MdREAV NOTES ON 108S AMD INCLUDED AUTEK MFE44MCEPAGE h0r,7419 Me, 1 8fS BEFORE USE Oeogn valid for use only Win MffeW connectors, This, design hbasedupon par tees O and is for on hdividuat bulding corresonent: rant a farts systema. 0e:.fore use, the burfld dei a f verify lase ty of designparon hers curd propeoy hCorporate fire design into itis overall bus'idding deax gen,. eracirrg indicated is to prevent bvcJ*V of hxtviduol Muss ymb and/or chord arembers only, Additional tefferwory and pennoraen€ boscins; is otwoys reefed lot sfakrors and to prevent coltapse with poselde, personse marry and property damage, For general guidance regardfriq this rotwicotion, storage. delivery, erection and tracing of trusses and easy, systems. seas ANSI/Mil C ria, 1±55~84 o+tA SCSI 8:.. ng GanPon safa#tytadwmsa#4rt crvadablePeoanTruss Note kest6#rte,"ZteN Lee Street. Sar7te i2.AIe 'A 424T4, Pi fUVb rcaagtirarg,?tutar_vbZY(3t-E*t100ktQDDVta lkbcTvOBaA K BbZV uhozVgyAluY 1440 16-0-0 1.29,6 44 LOADING (psf) SPACING- 2-0.0 TCLL 30.0 Ptete Grip DOL 1.15 TCDL 10.0 Lumber DOL 1.15 BOLL 0,0 * Rep Stress ttacr YES BCDL 10,0 Code tRC2012frPt2007 LUMBER - TOP CHORD 20 SPF No.2 BC 0,39 BOT CHORD 2x4 SPF No.2 } BS 2X4 SPF No,2 CSL } a Well x TC } } BC 0,39 } VVB 06 . } + 0,03 6-12 >999 240 3x4 PLATES GRIP MT20 197/144 Weight: 40 to FT - 0% TOPCHORD Structural wood sheathing directly applied or 4-8-7 oc purlins, BOTCHORD Rigid calling directly applied or 1 D-0-0 on bracing, MiTek recommends that Stabilizers and requited cross bracin be installed during truss erection, in accordance with Stabilizer rf} } Max a Max Upitft2-194(LC 16), 4-194(LC 16) mp,/Max, Tan. -All forces 250 (to) or less except when shown, f f M. } } 4-16-10771197 BOTCHORD 2-6-1031943, MBS "-01272 NOTES - 1) Unbalanced r#.. live leadshave i ....a. x. CategoryCat, ll'Exp C� enclosed; MWFR$ (directional) and C -C Extertor(2) -2-0-0 to 0-9-12, Interion(l) 0-9A2 to 7-0-0, Exterior(2) 7-0-0 to 10-0-0 zone; cantilever Wit and right exposed; end vertical left and right exposed�C-C for members and forces & MWFRS for reactions show Lumber DOL -1.60 plate grip DOL=1,60 3) TCLL-1 ASCE 7-10; Pr --30.0 Pat (roof live load: Lumber DOL=1.15 Plate DOL -1.15); Pf-30.0 list (flat roof snow: Lumber DOL -1,15 Plate # C; Partially Exp� Ct-1,1 considered4) Unbalanced snow loads have been for this design, non-concurrent5) This truss has been designed for greater of min roof live two of 12,0 pef or 1 00 times flat roof load of 30.0 Pat on overhangs other 6) Plates checked for a plus or minus 5 degree rotation about its center, 7) This truss has been designed for a 10,0 list bottom chord live load nonconcument with any other live loads 8) * This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members, 9) One RT4 USP connectors recommended to connect truss to bearing walls due to UPLIFT at ft(s) 2 and 4, This connection is for uplift only and does not consider lateral forms. 10) 'Semi-rigid pftchbreaks including heels" Member end fixity model was used in the analysis and design of this truss, WARNRNO - V -MY chap#» p}r}rnefar} Sed READ NOTES ON 110 AND XCLUDED Ong<REFE44NCE PAGE W7413 Farr. 1Qdt9312015 DEFDRE #ISE, Design vcafid for use only with Wei connectors. The design isbased= upon porortreters shown, and is for aro erddKiducot butt cent, notopedy a hvss system. Before use, the d : nxvst verity she iY of design parameters and or Incorporate this design into the oveesh bWdhg deson. Bracing indicated is to prevent buckling of ' c#axN truss web and/or chrwci merebeers only. Additional temporary old permnent bracing is ohvosi required for stobirty and to prevent co faith goss"is penond ' sand property domoge, For generat guidance r' rd the fabrication, storage, delivery, erection and brocing off saran truss system, see ANSI/"CPh C e< bS5-S4 and 8C3�i St"ng Caaap. reart Saf f of a ffon ovadable from Truss Pkate, institute, 218 N Lee Street. Suite 312. Atexand rs, VA 2s, _ y lD:05aAPQlgtW17gZt TOu Q5zY6F-J5A8b4u3 k x9Y"78ZPh KwKOR86 GGA€uX ?-�- ... 14.0.0 2-0-0 7-0-0 7-0-6 _ 11 axrm 2x4 7- Plate Offsets (X,Y)-- (2:0-1-2, dge , [4:0-1-2,E49e] LOADING (psf) SPACING- 2-0.0 CSI, DEFL. In (loc) lldefl Ltd TCLL 30„0 Plate Grip DOL 1.15 TC 0.68 Vert(LL) -0.07 5-8 >999 360 TCDL 10,0 Lumber DOL 1.15 BC 0,42 Vert(TL) -0.15 5-9 >999 240 BOLL 0,0 ' Rep Stress fncr YES WB 0.06 Horz(TL) 0,02 4 We We SCDL 10,0 Code 8RC20121TP12007 (Matrix -M) d LL 0,04 -8 >999 246 • REACTIONS. (lb/size) 4=696/0-5-8,2-86410-” Max =69610-5.8,2.86410- Max Harz -50(LC 12) Max Uplift4--100(LC 16), 2--196(LC 16) FORCES, (lb) -Max, Comp,/Max, Ten, -All farces 250 (lb) or less except when shown, TOP CHORD 2-12-1096/225,3-12-10141237, 3-13-1014/249,13-14=-1014/237,4-14-1095/233 BOT CHORD 2-5--156/962,4-5-1661962 BS 3-5-01274 Structural wood sheathing directly applied or 4-1-14 oc, puffins, Rigid Y: directly applied or 10-0-0bracing, requiredMiTek recommends that Stabilizers and o bracing installedbe during truss erection,da Instal . #- NOTES - 1) Unbalanced roof live loads have been considered for this design Catll� Exp C; enclosed; MWFRS (directional) and C -C Exterior(2) -2-0-0 to 0-9-12, lifterior(l) 0-9-12 to 7-0-0, Exterior(2) 7-0-0 to 10-0-0 zone; cantilever left ight exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions Lumber DOL=1,60 plate a grip w# #i :. * Pr --30,0 #at (roof live #».# Lumber 1. Plate DOL -1,t ► ».. roof snow: LumberDOL=1Plate N #f # #. 4) Unbalanced snow loads have been considered for this desigm 5) This truss has been designed for greater of min roof live Wit of 12,0 psf or 1,00 times flat roof load of 30,0 psf on overhangs non -concurrent with other live bads. 6) Plates checked for a plus or r a •: rotation about 7) This truss has been designed ^# • : 10,0 psf bottom# live load nonooncurrentany other leads. 8) * This truss has been designed for a live toad of 20,Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom other 9) One RT4 USP connectors recommended to connect truss to bearing walls due to UPLIFT at ft(s) 4 and 2. This connection is for uplift only # does not•• rr 10) 'Semi-rigid pitchoreaks including heels' Member end fififty model was used in the analysis a design WARNBNG - VoWd-1119-plinurithin, andREAD NOTES ON 100 AND INCILUMONTEXREPEPANCE PAGE 1.1473 t : 1""015 BEFORE USE Oewatr3 tcx lase orafy wrath Nt'f carsao #cars. Ttats 8ameters stwwn and is for tan lndividuat bold' component, not asystem. Before use The drug igner" in verity thea c a¢kty oi' de' p ameters and pr inc.ate hats design into Sloe averse buil design. &lacing trrdicate d is tea Bare t buckfiyng of indi truss eb and/or chord me s orally, Additional temporary and pernrosent brocngMe!6s ys required for stoblity and to prevent c ewith posuble onal �^yvey and rxopedy damage, for general uida+ace re fabrication, storage, defivery, erection and bracing of trusserand suss systerns, see ANS#/Tril g girding the 7771 Greenback Large So twit m rson av bfe from truss Plate Institute, 218 N. Lee Street" Me 312, Alewancdo, VA 223 .CatYes4a, �t56�ffiV and 8C5t ng C So" 109 2.•0-0 5.118 2-7-8 3.9.8. 4.10-10 ,.,.i Scale = 1.35.4 0 o»� 5x8 2.00 12.. 3x10::«.. LOADING (psf) SPACING- -€3-0 TCLL 30,0 Plate Grip DOL 1,15 TCDL 10.0 Lumber DOL 1.15 BCLL 0,01 Rep stress Incr YES BCDL 10.0 Cade IRC2012ITP12007 LUMBER - >999 TOP CHORD 2x4 SPF Na.2 SC 0,76 BOT CHORD 20 SPF NO,2 -0.39 BS 2x4 SPF INo.2 >532 OTHERS 2x4 SPF Pio. VVB 0.39 CSL DEFL. In (lac) Wed Ud PLATES GRIP TC 0,61 Vert(LL) 418 8-9 >999 360 MT20 1971144 SC 0,76 Vert(TL) -0.39 8-9 >532 240 VVB 0.39 Horz(TL) 0.13 6 the ria (Matrix -M) Wnd(L.L) 0.11 8 >999 240 sght: 65 to FT 0% BRACING. TOPCHORD Structural wood sheathing directly appliedor a BOTCHORD Rigid« directly .# . « REACTIONS, (dbl ize) 2-1032/0-5-8, Ld Max Harz —49(LC 14) Max Uplift 2--217(LC 16), 6--216(LC 16) FORCES. (lb) -Max. Comp./Max, Ten, - Ali forces 250 (lb) or less except when shown, TOP CHORD 2-26=-1673/302,26-27--15931310,3-27=-15431311, 34-16391370,4-28=-27821482, 5-28=-2616/471, 6-29=-30261567, 6-29-30961555 Wok recommends t .. 5tabillzers and required crass bracing be installed during truss erection, in accordance with Stabilizer Installation guide, wARNf e; • vedd, daawo. m rametear aaad READ mores aAF rate; AND WC'S..t,fVED I ITEK REFERANCE PAGE A 7471 nnr 140MIS SEFORE (ASIS D" n v0Ad for use o N w ih hR 3 4... toes. This desPgn s d upon parameters shove . end is for on Individual buld3ng c nt, no amass sysfe .Beforetion ' mast verily thea csb ty of design p0ratr tern and Property incaPorate this design Into ttre overaft butldfng design. firac'sag indlooted is to prevent boct.Ping of WrdMducy truss web and/or chord nrembers on€y. Additional ternporay and pernwanent lxocbag is ceyoys realuued fcar crobEty and to prevent collapse with rocs personal intsary and pro dardoge. For general guWance r d!ng the faixe,aflon, siafage, dr iduyry, erection and bracing of truss and truss systems, see ANSI/17`11 Quality Crikeirs, 0$4-S9 and SGS/ S. Safety Ifflonnallan avokilde from Trus Moe institute, 218N. tee Street. Suite 312„ Alexandria, VA 22314., December 11,2015 uu� 7777 (4ftntfack Lane suffe 109 ""�'.t1•Ei-:7•Q .. 12 -3 -Hi t..... ... i?' -2-0 .... 19-2- 2"0-0... 2-7-8 344 4-10-10 .. 2-0.0 Scale 9:35..4 4X6 4 pax$ 2,00 12 3%10 11-4.0 . , ... ....17-2 0 ... 5.91- 5. 8 5 iia ti LOADING (psf) SPACING- 2-0-0 CSL DEFL. in (toe) Well Ud PLATES GRIP TCLL 30.0 Plate Grip DOL 1.15 TC 0.51 Vert(LL) .0.18 8-9 >999 369 MT20 197/144 TCDL 117,0 Lumber DOL 1.15 BC 0.76 Vert(TL) -9.39 8-9 >532 240 BCLL 0.9 ° Rep Stress Inor YES VVB Ot 39 Horz(TL) 0,13 6 nta n/a BCRL 10.0 Code IRC2912/TPI2007 (Matrix - M) Vitnd(LL) 011 8 >999 249 fight: 67 to FT - 0% LUMBER. BRACING. TOP CHORD 2x4 SPF No.2 TOP CHORD structural wood sheathing directly applied or 3-0-3 oc purlins. BOT CHORD 2x4 SPF No.2 BOT CHORD Rigid calling directly applied or 8-6-5 oc bracing. BS 2x4 SPF' No.2 MfTek mmends that Stabilizers and required cross bracing be installed during truss erection, in accordance with Stabilizer Istaffafion guide, REACTIONS. (lb/size) 2-103210.5,15,6=100505-8 Max Herz 2-49(LC 15) Max Uplift 2--217(LC 16), 6=-216(1_016) FORCES. (lb) - Max. Comp./Max, Ten, -All forces 259 (Ib) or Bess except when shown TOPCHORD 2-16-16731302,16-17-1593/310,3-17-15431311, 3-4--1639/370, 4-18--27821482, 5.18--2815/471, 5-19-30261567, 6-19--30961555 BOT CHORD -9 =-19311 519, 8.9-17611376, 6-8--48212925 BS 3-9-3921153, 4-9-99/410,41-8-21011607, 5-8=-371/156 NOTES. 1) Unbalanced roof live loads have been considered for this design. 2) Wind; ASCE 7-10; Vult-126 ph (3 -second gust) V(IRC2012)-100mph; TCDL-6 9psf; BCDL-6.0psf; h-25ft; 8-45fi, L-24ft; eave=oft; Cat. It; Exp C; enclosed; MVVFRS (directional) and C -C Exterior(2) -2-0-0 to 0-9.12, Interior(1) 0-9-12 to 8.1-0, Ext r(2) 8-7-0 to 11-7-9 zone; cantilever left and right ex d ; end vertical left and right exposed;0-C for members and forces 6 MWFRS for reactions shown; LumberCC7L=1.60 plate grip DOL -1.60 3) TCLL. ASCE 7-10; Pr --30,0 psi (roof lave load: Lumber t7OL=1.15 Plate DOL -1,15); Pf=30,0 psf (flat roof snow: Lumber DOL=1.15 Plate DOL -1,15); Category ll; Exp C; Partially Exp„ Ct=1.1 4) Unbalanced snow loads have been considered for this design. 5) This truss has been designed for greater of min roof live load of 12.0 psi or 1.00 times flat roof Toad of 30,9 psi on overhangs non -concurrent with other live loads, NDOu 6) Plates checked for a plus or minus 5 degree rotation about its center. 7) This truss has been designed for a 10,0 psf bottom chord live load non current with any other live loads, 8) ` This truss has been designed for live food 20.Opsf the bottom y a of on chord In all areas where a rectangle 3 tall by 2-0-0 wide will fit between the bottom chord and any other members. 9) Bearing at joints) 6 considers parallel to grain value using ANSV TPI 1 angle to grain formula, Building designer should verify capacity of bearing surface.66s 19) One RT4 USP connectors recommended to connect truss to bearing walls due to UPLIFT at jt(s) 2 and 6. This connection is for uplift � only and does not consider lateral forces, 11) "Semi-rigid pitchbreaks including heels" Member end fixity model was used in the analysis and design of this truss. " 00 December a",cru #-tS-sP SOWS III Plate Offsets (x,` )-- [2:0-2-7,Edgaj, j4:0-2-7,Ed9 I 6 g; LOADING III SPACING- 2-0-0 CSI. DEF1., in (loc) !/deft Lid PLATES GRIP TCLL 30.0 Plate Grip CSDL 1.15 TC 0.46 Vert(LL) «0.08 6-16 >999 350 T20 1574144 TCDL 90.0 Lumber DOL 1.15 BC 0.50 Vert(TL) -0.17 6-15 >833 240 BCLL 0.0 ° Rep Stress mar YES WB 0,95 Horz(T€.) 0.07 4 nta nfa BCDL 10,0 Code 1RC2012ITP1 007 (Matrix -M) VVrnd(LL) 0.07 6-16 >999 240 WIIII 351b FT = 0% LUMBER- BRACING - TOP CHORD 2x4 SPF No,2 TOPCHORD Structural woad sheathing directly applied or 4-2-4 oc puffins, BCT CHORD 2x4 SPF No.2 BOT CHORD Rigid ceiling directly applied or 8.1-14 oc bracing. BS 2x4 SPF No.2 1I recommends that Stabilizers and required cross bracing OTHERS 2x4 SPF No.2 be installed during truss erection, in accordance with Stabilizer Installation guide, s # r r f. " " of # #♦... ».Y #. ,. " ' ,Y �# y # # #. # 't * '° # '. M w a- # ° "# a # - w # Yrs# I a 1i # •.:t t: 1 ► t s WAR N • Vify dWS. Pmot. and READ NOTES ON TNS AND MCLUDED AUTEK REEERANCE PAGE AW7473 rev, 149M15 SEFOas USE. Ckes gn vsra�d Ca- arse wihh hiiScak connacPcus. This def ' SZ based tinXy GpCrn ,fere shrswn. and 4 for an ina h4dud bu klI component, not a truss syxtem. SeBcxe usca. it>e bu3tdiraG des r must veri€'r tine abi9tp aP de ' s Srexgrrrete rs andptopedy hscorpvote thea design into the overatd b ': " g de ° $racdAtg. safed is tar prawent buckiirrg of i+'rdilvrtiva§ tewsx : flrseffes chcad e only. Addifioncri fenVAxary end peTwnent bracing tS {Yi 8et�illred {i.# A{flub{}+ Pcro rA+'C;.v'ent G p$rS 4: tt#t 75i7i1w$§ dnit±y GN➢d pf ty°ge, for generoi oukionce reowding the f ".4caSusn, etcxcstpe, de§§very, eree:tiora rrrrof tardcirmg at trusses esnd tnsss syste s, see A SfltBdi Criteria, DS3-81i and SCSI SuAtfing Component Sa arw ave to bran irc.rss t'LSte �es3[dute. 2iE N. lee Sweet. Suite 3t2. Atexandr&s, VA 2`134. HIM Ay4 3 LOADING (psf) SPACING. 2- CS€. TOLL 30.0 Plate Grip DOL 9.15 TC 0,46 TCDL 10,0 Lumber DOL 1.95 SC 0.50 SCLL 0.0 Rep Stress Iter YES WB 0.15 BCDL 10.0 Code iRC2012frPI2007 (Matrix - M) LUMBER - r TOP CHORD 2x4 SPF No.2 SCT CHOR 3 2X4 SPF No.2 R WEBS 2x4 SPF No.2 REACTIONS. (tbistze) 2-743/0-5-8,4-74310-5-8 Max Herz 2=37(LC 15) 0,04 MaxUpli t=-177(LC 16), 4=-177(LC 16) .+ FORCES, (lb) - Max, Comp,/Max, Ten, - All forces 250 (to) or less except when shown, :{ ,15-16-1568/268,Y .• 1.. 4-6-19011501 WEBS i 3X4 PLATES GRIP MT20 1971144 tght. 34 to FT = 0% ceilingStructural wood sheathing directly applied or 4-2-4 Ire punins, Rigid directly applied or 10-0-0 do bracing, Weir recommends w cross bracing binstalledduring truss erection, NOTES- 1) Unbalanced • o.:' .. .. considered for this design, 2) Wind: ASCE 7-10, Vuft=126mph (3 -second gust) V(IRC2012)-100rnph� TOOL-6,0psf; BCDL=S,Opsfh=25ft; B-45ft; L-24ft� eave=4ft; w r y s (directional) : R Exterior(2)-2-0- 0 to interior(l)1-2-5 t #: 0 to 8-10-0 zone; cantilever left and right exposed; end vertical left and right exposed�C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1,60 plate gdp DOL -1.60 i ♦ ♦ ti ryA.' MR Y. M r t # Unbalanced snow loadsbeen Consideredfor this design, non-concurrent5) This truss has been designed for greater of min roof live load of 12.0 Pat or I 00 times flat roof load of 30,0 par on overhangs othero. checked6) Plates for a plus or minus 5degree rotation about 7) This truss has been designed for a 10,0 psf bottom chord live load nonconcurrent with any other live loads, 8) * This truss has been designed for a live load of 20,Opsf on the bottom chord in all areas where a wrangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. Bearing o .. considers parallel tort ,::: a ANSVTPI I+.le to grain formula,o ♦ designer shouldverify capacity 0 0 II OneY'w connectors- ♦ - o -w to connect truss to bearing due to UPLIFT at #(a) 2 and 4, This connectionfor uplift only and does not consider lateral forces, 11) "Sent-jigid pitchbreaks including heels" Member end fixity model was used in the analysis and design of this truss, °'rnr i Aa P NOTES ON THIS AND INCLUDED WTEK REFERANCE PAGE W7473rov, IGVVMS BEFORE USE, gh g#n volyd fa use only wish Weisconnectors, This desQn, is based onthyr upon parcmauten shcavat, read is for an indivkiuot bu c menta rust a m ss sYS om. Before use, the ba ding des must verify the oppocob kry of dery Aa smeters and property inn ate this deVn deinto the ovkrsaft bukfirgdesign. firocingt caped is 10 prevent buckirng of WeSvWua9 "s web or sfror chord n s on y. Asidat # cry and peerxarsent bsacsag is is req . for Vobiify and to prevent co4opse Wth possibte personot imrry and Procerty dorstoge,. For gfers cd sttridance regassfing the W lubrication, c storogge, delivery, erection azul brocing of trusses end truss syste", see ANSIjiPII € u . Ca. otar S4 and 0 7771 WOW ng component a sa Sa mo avol Cram1r..ns PUe knstRufe, 23$ N, tee Street. Surte 3i2, Aiexon VA'.�3t.4. _ «. 6-12 >999 360 r R } 0,04 .+ 240 FORCES, (lb) - Max, Comp,/Max, Ten, - All forces 250 (to) or less except when shown, :{ ,15-16-1568/268,Y .• 1.. 4-6-19011501 WEBS i 3X4 PLATES GRIP MT20 1971144 tght. 34 to FT = 0% ceilingStructural wood sheathing directly applied or 4-2-4 Ire punins, Rigid directly applied or 10-0-0 do bracing, Weir recommends w cross bracing binstalledduring truss erection, NOTES- 1) Unbalanced • o.:' .. .. considered for this design, 2) Wind: ASCE 7-10, Vuft=126mph (3 -second gust) V(IRC2012)-100rnph� TOOL-6,0psf; BCDL=S,Opsfh=25ft; B-45ft; L-24ft� eave=4ft; w r y s (directional) : R Exterior(2)-2-0- 0 to interior(l)1-2-5 t #: 0 to 8-10-0 zone; cantilever left and right exposed; end vertical left and right exposed�C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1,60 plate gdp DOL -1.60 i ♦ ♦ ti ryA.' MR Y. M r t # Unbalanced snow loadsbeen Consideredfor this design, non-concurrent5) This truss has been designed for greater of min roof live load of 12.0 Pat or I 00 times flat roof load of 30,0 par on overhangs othero. checked6) Plates for a plus or minus 5degree rotation about 7) This truss has been designed for a 10,0 psf bottom chord live load nonconcurrent with any other live loads, 8) * This truss has been designed for a live load of 20,Opsf on the bottom chord in all areas where a wrangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and any other members. Bearing o .. considers parallel tort ,::: a ANSVTPI I+.le to grain formula,o ♦ designer shouldverify capacity 0 0 II OneY'w connectors- ♦ - o -w to connect truss to bearing due to UPLIFT at #(a) 2 and 4, This connectionfor uplift only and does not consider lateral forces, 11) "Sent-jigid pitchbreaks including heels" Member end fixity model was used in the analysis and design of this truss, °'rnr i Aa P NOTES ON THIS AND INCLUDED WTEK REFERANCE PAGE W7473rov, IGVVMS BEFORE USE, gh g#n volyd fa use only wish Weisconnectors, This desQn, is based onthyr upon parcmauten shcavat, read is for an indivkiuot bu c menta rust a m ss sYS om. Before use, the ba ding des must verify the oppocob kry of dery Aa smeters and property inn ate this deVn deinto the ovkrsaft bukfirgdesign. firocingt caped is 10 prevent buckirng of WeSvWua9 "s web or sfror chord n s on y. Asidat # cry and peerxarsent bsacsag is is req . for Vobiify and to prevent co4opse Wth possibte personot imrry and Procerty dorstoge,. For gfers cd sttridance regassfing the W lubrication, c storogge, delivery, erection azul brocing of trusses end truss syste", see ANSIjiPII € u . Ca. otar S4 and 0 7771 WOW ng component a sa Sa mo avol Cram1r..ns PUe knstRufe, 23$ N, tee Street. Surte 3i2, Aiexon VA'.�3t.4. _ Scale 4x4 B 9 so ,•„ 31 30 29 28 2.s 26 25 24 23 22 21 20 19 1$ 3x4 .. 3A 24-04 LOADING (psf) SPACING;- 2- CSI. DEFL. in (loci Udell Lid PLATES GRIP TOLL 30.0 Plate Grip DOL 1,15 TC 0,31 Vert(LL) -0,03 17 €#fi 126 MT20 197#144 TCDL 10.17 Lumber DOL 1.15 Sc 0.10 VerhTL) -0.04 17 nfr 120 BCLL 0.0 ` Rep Stress Incr YES WS 0,04 Horz(TL) 0.00 16 We rite BCDL 16,0 Code IR20121"iPI2007 (Matrix) Watgft 96 to FT 0 LUMBER. BRACING. TOP CHORD 2x4 SPF No.2 TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins, SOT CHORD 2x4 SPF No.2 RUT Ch ORD Rigid ceiling directly applied or 6.0-0 oc bracing. OTHERS 2x4 SPF No,2 Mitek recommends that Stabilizers and required cress bracing be installed during truss erection, in accordance with Stabilizer Installation guide. REACTIONS, All beatings 4- (tb) - Max Harz --65(L 14) Max Upttft All uplift 100 lb or less at iotnt(s) 25, 27, 28, 29, 30, 31, 23, 22, 21, 20, 19, 18 except 2--149(LC 16), Ifs=_'149(LC 16) Max rav All reactions 250th or less at joints) 24, 25, 27, 28, 2, 30, 3, 22, 21, 20,19 except-377(LC 21), 31=324(LC 32), 18.324(LC 33), 16=377(LC 22) FORCES. (to) -Max, ComplMax, Ten. -All forces 250 (to) or less except when stn SS 3-31 =-25 21152, 15-18-2531152 NOTES - 1) Unbalanced roof live loods have been considered for this design. 2) 44#ind: ASCE 7-10; Vult-I 26mph (3 -second gust) V(tRC 012)-100mph; TCDL=6.Opsf; SCDL=6.Opsf; h=25ft; S-45ft; L=2411, eave=2ft; Cat. It; Exp C; enclosed: MVVFRS (directional) and C -C Comer(3) -2-0-0 to 1-0.0, Exterior(2) 1-0-0 to 12-0-0, Corner(3) 12-0-0 to 15.0-0 zone; cantilever left and right exposed; end vertical left and right exposed C -C for members and forces & MWFRS for reactions shown; Lumber DOL=1,60 plate grip DOL -1.60 3) Truss designed for wind toads in the plane of the truss only. For studs exposed to wind (normal to the face), see Standard Industry Gable End Details as applicable, or consult qualified building designer as per ANSWrPt 1, 4) TOLL: ASCE 7-10; Pr -30.0 psf (roof live load. Lumber DOL -1.15 Plate DOL -1.15); Pf=30.0 psf (fiat roof snow: Lumber D0L=9.15 Plate DOL=1.15); Category 11; Exp C; Partially Exp,; Ct=1.9 5) Unbalanced snow loads have been considered for this design. {� , 6) This truss has been designed for greater of min roof live load of 12,0 psf or 1.00 times flat roof toad of 30.0 psf on overhangs« non -concurrent with other live toads 7) All plates are 2x4 MT20 unless otherwise indicated. rev c + 8) Plates checked for a plus or minus 5 degree rotation about its center. C3 9) table requires continuous bottom chord bearing. � 10) table steads spaced at 1-4-0 as. 66 Mo 11) This truss has been designed for a 1(L0 psf bottom chord live load nonconcurrent with any other live toads. � 12) " This truss has been designed for a live load of 20,Opsf on the bottom chord in all areas where a rectangle 3- tall by 2.0-0 wide will fit between the bottom chord and any other members, Glx 13) One RT3A USP connectors recommended to connect truss to bearing walls due to UPLIFT at jt(s) 2, 25, 27, 28, 29, 30, 1, 23, 22, 21, 20, 19, 18, and 16, This connection is for uplift only and does not consider lateral forces,i "Semi-rigid 14) pkchbreaks including heels" Member end fixity mode$ was used in the analysis and design of this truss. ONA W - li `.. MAID NOTES ON OAS .41141 JWL 0DW dM MK REFS NCE PA GE 0•7473 mv. MOMIS Saxons NSE, u.. Deskol void for tw, onh, with Wen& connectors. This desig+ sipso bweed c nj up*n portame4 sf o wi, and b for an hdN ud btAdk)g Ca t not a twis systean. Berate use. the ' rr kvg de w.+st veepty opplicobi iy of devWg tens and. prop W " krc ofe this deggn de"tato it* owsao4 . Brae Matracated ks to prevent buckping csf indduidtta# Noss weir andlor chcxd er2e Addirsond ferripoory rand piomonent baocing" is r tcaz s1 `hr rand fxa prs++ent ca4agws wifit pia ie risrserrscs4' arxi demo . For gen d guk9atace r dhri the t cefkan aicw . . dstiwr„ty. erec:titwrr ane$ txcecksg of hvasses cane truss systems, zee AHSi{[P#t Qu Cdhato OSS -67 wend SCSI. Cc mpo 7777 Greenback Une awn heats Tnrsc Pka� 4+sfiiute. 218 N. les Sfraret. Sul#e 9a2, Rlexar? , etA 2z3i4. Susie i09. .. vt 4 IN o-q-sw ._.. _.. 7d -i}-+3 17-7.2 24-0-0 2iS»# 0 2-00 6.4,14 $-7-2 5-7.2 ...6.4-14 2.0-0 .. Scale = 146.0 0 3x4 3x4 - 3x4 3X6 3x6 LOADING (psD SPACING. -O.0 TCLL 30.0 Plate grip DOL 1.95 TCDL 10.0 Lumber L 1.15 BCLI 0.0 * Rep Stress inor YES BCDL 10.0 Code IRC24121TPI2007 8-10 LUMBER - 360 TOP CHORD 2x4 SPF No2 Vert(TL) BOT CHORD 2x4 SPF No.2 -10 VVESS 2x4 SPF No.2 240 CS#. DEFL. in (Boc) Udell Ud TC 0,83 Vert(LL) -0.19 8-10 >999 360 C 0.72 Vert(TL) -0,42 -10 >692 240 VM 0.99 Hora(TL) 0,10 6 n% n1a (Matrix - M) Wn (LL) 0.12 8-10 >999 240 RACING - fight: 79 to FT = 00% TO10f CHORD Structural wood sheathing directly applied or 2-2-0 oc pudins, SOTCHORD Rigid ceiling directly applied or 9-2-9 oc bracing, Mrrek reconimends that Stabilizers and required cross bracing be Installed during truss erection, in accordance with Stabilizer FORCES,Max Horz 2=66(LC 15) Max Uprrft2-266(LC 16), 6�266(LC 16) # t t TOPCHORD 2-3-26671506, 3-17--2330/432,01 06 BOTCHORD 2-10-38012464, WEBS 4-8-78f785, 5-8-59W203,# NOTES- 1) 2) Wind: ASCE 7-10; Vuft-126mph (3 -second gust) V(IRC2012)-100rriph� TCDL=6,Opsf,, BCDL-6.Opsf: tr-25ft� B-45ft: L-24ft; eave-4ft; Cat, ll� Exp C; enclosed; MVWRS (directional) and C -C Exterior(2) -2-0-0 to 0-9-12, hiterioril) 0-9-12 to 12-0-0, Exterfor(2) 12-0-0 to 15-0-0 zone; cantilever left and right exposed � end vertical M and right exposed;C-C for members # forces & MWFRS for shown; Lumber DOL -1 A0 pride 96P DOL -1,60 R e## w 4) Unbalanced snow loads have been considered for this design. 5) This truss has been designed for greater of min roof live load of 12.0 psf or 1,00 times flat roof load of 30,0 psf on overhangs non -concurrent with other live loads, 6) Plates checked for a plus or minus 5 degree rotation about its center, 7) This truss has been designed for a 10,0 psf bottom chord live load nonconcurrent with any other live load& 8) - This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-" wide will fit between the bottom •. # and any other 9) One RT4 USP connectors recommended to connect truss to bearing walls due to UPLIFT at ft(s) 2 and 6, This connection is for uplift only and does not consider lateral forces, 10) 'Semi-rigid pftchbreaks including heels' Member end fixity model was used In the analysis and design of this truss, December +i w I 5-0-10 5^0^50 a 4 2x4 •, 2x4 i i 2x4 ;,-� LOADING (psh SPACING- 2-0-0 CSI. TOLL 30.0 Plate Grip DOL 1.15 TC 0,26 TCDL 10,0 Lumber DOL 1.15 BC 0.14 BCLL 0.0 " Rep Stress Incr YES M 0.04 BCDL 10,0 Code IRC2012ffP12007 (Matrix) LUMBER - rade TOP CHORD 2x4 SPF No.2 SOT CHORD 2x4 SPF No,2 OTHERS 2x4 SPF No.2 DEFL. In lioc) Udell Ud PLATES GIP VerdLL) nta The 099 MT20 1971144 Vert(TL) rile nta 999 ttorz(TL) 0.00 3 Ola rade Weight: 23 lb FT = 0% BRACING- # sheathing directly BOTCHORD Rigid ceilingdirectly applied osa oc bracing, MiTek recommendsand required ciess bracing be Installed during truss erection, in accordance Installation outdo, • # Max Harz 1-19(LC 15) FORCE& (lb) - Max. Comp,/Max, Ten, - Ail forces 250 d1a) or less except when shown, WEBS 2-4-3411179 NOTES - 1) # # a M: i Ok • ai. Cat, It; Exp C; enclosed" MWFRS (directional) and C -C Exterior(2) 0-11-5 to 3-11-5, interior(l) 3-11-6 to 5-0-10, Eidedor(2) 5-0-10 to 9-0-10 zow cantilever left and right exposed; end vertical left and right exposed�C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1,60 plate grip DOL -1,60 DOL=I 16); Category 11; Exp C; Partially Exp.; Ct=l,l 4) Unbalanced snow loads have been considered for this design, 5) Plateff checked for a plus or minus 5 degree rotation about its center, 6) Gable requires continuous bottom chord hearing. 7) Tits truss has been designed for a 10D psf bottom chord live load nonconcurrent with any other five loads, 9) * This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-" tall by 2-0-0 wide will fit between the bottom chord other ii) One RT3A USP connectors recommended to connect truss to hearing wells due to UPLIFT at #(a) 1, 3, and 4This connection Is for uplift only and does not consider lateral forces. 10) a pdchbreaks Including heels"Member end fixitymodelwas used in the analysis and design of WARAANViipal.andREAD NOTES. ON TM AND INCLOVEDANTEKREFER01WEPAGCW1473mv, 14,022ins BEFORE USE: ge weld It'sr ane only wfth Weiser connectors This design 4 based or u. pcararraeters ata � Tem an kxtividual bu c int, not es tears syslent. setore use, the bat+"k ' designer meSSf verify itre czppFc:atri ty of design paron'seters md propimy,heorporate thEs design into the ovtroft bulofinSc design, brocing todica ed h to prevent bucMing of individuot truss web ond/or chord mernben Oros, Addiiiarroi ternporoty cued penruorreni bracing is otways required t« sfoloiity and to prevent colsopse with possible persona inlu+y and property dorsidge. for qorwfid guidonce regarding the tcsbricoWn, storage, delivery, erection and broeng o1 frusses and truss sirstetym see /Tilt . DSC491 1 ng Component solelyt tion ovolobirs from Truss Note irestf ute, 2 18 N. Cee Street, Suite 3d A ex a re VA r2314. Y� wa°�l v j+ ut#r 14 ii II i, I N 3--0.10 $10.10 4.00 12 2 LOADING (pst) SPACING- 2- CSI. TCLL 30,0 Plate Grip DOL 1.15 TC 0.09 TCDL 10,0 Lumber DOL 1,15 BC 0.18 BCLL 0.0 " Pep Stress Incr YES WS 0,00 8CI?L 10.0 Code IF4C2012iiPt2007 (Matrix) LURBR- Rigid ceiling directly applied or 10-0.0 on bracing. TOP CHORD 2x4 SPF No.2 be installed during truss erection, in accordance with Stabilizer BOT CHORD 2x4 SPF No.2 Installation aside. N EM I DEFL. in (loc) Weir Ltd PLATES GRIP Vert(LL) the did 999 MT20 1971144 Vert(TL) fila - We Horz(TL) 0.00 3 rata We tight: 12 Ib FT = 0 BRACING - SOP CHORD Structural wood sheathing directly applied or 6-0.0 no puffins, BOT CHORD Rigid ceiling directly applied or 10-0.0 on bracing. MiTek recommends that Stabilizers and required cross bracing be installed during truss erection, in accordance with Stabilizer Installation aside. Max Horz I-10(LC 15) • " •ms(to) or less except when shown. CHORDTOP 1• 0 NOTES - 1) 2) Vying: ASCE 7-10; Vu#-126mph (3 -second gust) V(IRC2012)-100mph� TCDL=6.Opsf,, w i µ Catll� Exp C; enclosed; MWFRS (directional) and C -C Extedor(2) zone: cantilever left and right exposed; end vertical left and right exposed;C-C for members and forces & MVWRS for reactions shown; Lumber DOL=1,60 plate grip DOL=1,60 Category between4) Unbalanced snow loads have been considered for this design, 5) Plates checked for a plus or minus 5 degree rotation about its center. 6) Gable requires continuous bottom chord bearing, 7) This truss has been designed for a 10,0 per bottom chord live load nonconcuffent with any other live loads, 8) * This truss has been designed for a live load of 20,Opsf on the bottom chord in all areas where a rectangle 3-6-0 tail by 2-0-0 wide will fit the bottom t and any other members, 9) One RT3A USP connectors recommended to conned truss to bearing walls due to UPLIFT at that I and 3, This connection is for upift only ♦ does considerlateral i.. 0. ti. Aincluding�heels"Member i fixitymodel was 't in the analysisand design of this truss, WA . Nt3+ trafry W On atvra . 6 N TES ON TM AND INCLUDW OTLR REFEMWE PAGE W7477 rev. fee"0115 WORE USE. Design void rd, use only Wth mlek i connectors, This design is based�upan tern shown, end is for on kid° ual b ca nent,. not a truss syxtern. frefore use. the building designer niust ver4 the appk of design posarnetesx and property hcorpoeste the design On, the o woq building design, f racerg indicated 4 to prevent buckling of hdAduol inns web sonfl x chord mernuess only. Addi ionat ternwary and pessnonwit bracing ys required for stobtity and to present cokopse w&th possidie pessonaf infury and property donsage. For geneosi gtAdome regarding the fabrk:oticn storage, delivery, erection and bracing of Ureses and 4russ wsferns, see Sli5P94 G a, eSR R9 said 3 R nR Goanp t Internsaffon avarlabie (torn Twee Pi ate Institute, 218 R Lee Street, Suite 3tZ Alexandho,. VA 22,314. December11,2015 t a MM 4x4 3 Same -1.25,2 3x4 .,� 6 7 6 3x4 2x4 2x4 2x4 LOADING (psi) SPACING- 2.0-0 CSI. DFL, in (too) Udell d PLAYS GRIP TOLL 30.0 Plate Grip DOL 9,15 TC 0.21 Vert(LL) Wit WE 999 MT20 1971144 TCOL 10,0 Lumber DIOL 9.15 BC 0,09 Verl(TL) We nfa 999 BCLL 0.0 ` Rep Stress Iver YES VVB 0.04 Horz(TL) 0,00 5 pro WE SCDL 10.0 Code IRC20121TP12007 (Matrix) fight: 38 lb FT - 0°rL LUMBER- BRACING - TOP CHORD 2x4 SPF No.2 TOP CHORD Structural wood sheathing directly applied or 5-0.0 oc purlins. BOT CHORD 2x4 SPF No.2 BOOT CHORD Rigid ceiling directly applied or 94.0.0 oc bracing. OTHERS 2x4 SPF No.2 RAiTsk rate inmends that Stabilizers ar t3 required cross bracing be Installed during truss erection, in accordance with Stabilizer Installation guide. —W-7 Andeanngs f5-4-V— Harz Max Uplift All upidt ar lb or MaxGrav All reactions r to. # r FORCES. # a # or NOTES - 1) 2) Wind: ASCE 7-10; Vuft=126mph (3 -second gust) cat11; # # t# R *shown� Lumber DOL -1,60 . plate10-8-2 zone; cantilever left and right exposed; end vertical left and fight exposed;C-C for members and forces & MWFRS for reactions " Categoryrip DOL -1 60 Pet checked4) Unbalanced snow loads have been considered for this design, 5) Plates for a plus or minus 5 degree i s about bottom6) Gable requires continuous bottom chord hearing, 7) This truss has been designed for a 10.0 psf 8) * This truss has been designed for a live load of 20.0psd on the bottom chord in all areas where a rectangle 3-6-0 toll by 2-0-0 wide will fit between the bottom chord and any other members, ..RT3A USPconnectors recommended to connect truss toik k walls due to t and « This connection is for uplift only ♦ i' 10) "Serni-sigid pitchbreaks including heets" Member end fixity model was used in the analysis and design of this truss, WARNING - Weill, deeJgn parameters ami READ NATES ON TM AND WCI WW ANTEK REFER.ANCE PAGE16 P7473 pair. 1Gkq"01S BEFORE USE, Cs 'on vaSc9 for use only v>•ftFt Weise cesrraasators This: designs is rased antY a parannetes shown., and 4 for ata find' uoi building can ernt, not sa LAM system, Before use, the Widing designer must verkfy the icabSuty, of design Porcerreters end property Incorporate this design. into the oversff building design, Brocang indicated is to prevent buckliag of WKINWOL truss web ami/tar chord inenibers only, Additional temporary and perroarrent brocing 6 chorys required for Vob5rty and to prevent coNotire vAth pussVe pessonai " and property dernage, rxx minerat grAdance regoldlog the folark.ation, storage, deliveryerection and bracing of trusses and tti ns system, see ANSWT111 C , OSN-84 and Nu ng Comp t Solverfalomaltint avauable from Truss Plate institute, 218 t7. Lee Street, Suite 3Q. Atex. `a, VA 22314, December l 5.8-2 rig"2 IN 4 2x4 == 2x4 2x4 Z� 0'0-1 11.4.4 .... _. .. @•0-Y 1138 ... _.. ... ... LOADING fpsf) SPACING- 2-0-0 CSL DEFL, in (toc) Well t.ad PLATES GRIP TCLL 3(r0 Plate Grip DOL 1,15 TC 0.36 Vert(LL) We WE 990 MT20 1971144 TOOL 10.0 Lumber DOL 1,15 SC 0.19 Verff%) nta n1a 999 SCLL. 0.0 " Rep Stress incr YES WB 0.05 Hsrz(TL) 0.00 3 nae We SCDL. 10,0 Code iRC2012I TP12007 (Matrix) ight_ 26 to FT - 0% LUMBER- BRACING - TOP CHORD 2x4 SPF No,2 TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins. SOT CHORD 2x4 SPF No.2 SOT CHORD Rigid setting directly appy or 10-0-0 oc bracing. OTHERS 2x4 SPF No.2 MiTels m nds that Stabilizers and required cron bracing be installed during truss erection, in accordance with Stabilizer Installation guide, i= Max Harz 1-22(LC 15) FORCES, (lb) -Max. Comp./Max, Ten. - Ali forces 250 (lb) or less except when shown, WEBS 2-4-393/187 • enclosed;1) Unbalanced roof live toads have been considered for this design, . . w } . } zone; cantilever left and right exposed; end vertical " and right exposed;C-C for members and forces & MWFRS for reactions showim Lumber }i } } «# ' ! Pr -X0 •♦ •.. ... Plate •1.. }. a ♦•: .... p... • ...;:,.. i -bY. } 4) Unbalanced snow toads have been considered for this design. 5) Plates checked for a plus or minus 5 degree rotation about its center. 6) Gable requires continuous bottom chord beating, 7) This truss has been designed for a 10,0 psf bottom chord live load nonconcurrent with any other live toads. ♦ ..s}.. designed for .. live loadof #eb:' on the bottom 1: in all areas where a rectangle}t tall by 2-0-0 wide will fit between 4 any other members. 9) One RT3A USP connectors recommended to connect truss to bearing walls due to UPLIFT at jhs) 1, 3, and 4, This connection is for uplift only and does not consider tateral forces, 10) 'Semi-rigid pitchbreaks including heels" Member end fixity model was used in the analysis and design of this truss, WAR Q - Vivityrferignparanishtisond READ MOTES ON TINS AND INCLWWARTEXREFERANCE PAGE Mr,7472W, 1AW,2015 BEFORE USE 11esign -kdd tear use Only Witty t €ie connectorx Toms de ' is d +17Vn Par tars shown, rand k for on indiAdvol buSding co rat, not .,;%truss system. Before case, the ing rtes ner rmast ueity the aP0=1LY of design parameters and property inc ate this design into the overolt bukfing design, Stcacing indicated 4 to Prevent buckimg at inckoduol truss web and/or chord "nibers, aa*, Additional ternporory and permanent bracing Is alw ayi racivired for sioblity and to prevent cokpse Y iffy possible peri and property dornarise, For general guidance regarding the fabrication, stowage, delivery, erection and bracing of fraasses and tntss altene, see AMSI/fIrn Clu n. OSS . »S9 and SCSI leading Component SaI ovagaarce 0cam truss Plate Institute 218 N, tee Street, Suite 312, Atextara ' „ VA I4. December suite 109 V BE 4cD 12 4 2 5: 2x4 LOADING (psl) SPACING- 2 CSL DEFL. to ([oc) Vdeft LAI PLATES GRIP TCLL 30.0 Plate Grip DOL 1.15 TO 0.15 Vert(LL) me - nta 999 MT20 197/144 TOOL 10:0 Lumber DOL 1.15 BC 0.33 Vert(TL) nta w n/a 999 BOLL 0,0- Rep Stress lncr YES WE 0.00 Horc(TL) 0.043 3 nia n/a BCDL 10.0 Code IRC201 iTP 2007 (Matrix)Weight: 15 to FT = 09 LUMBER- BRACING - TOP CHORD 2X4 SPF No.2 TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc puffins. BOT CHORD 2x4 SPF No.2 BOT CHORD Rigid ceiling directly applied or 10- oc bracing. MiTek recommends that Stabilizers and required cross bracing be installed during truss erection, in accordance with Stabilizer installation guide, REACTIONS. (!b/size) 1-274f7-2-12,3-27417-2-12 Max Harz 1--23(LC 14) Max Uplift I--40(LC 16), 3= 40(4C 16) FORCES. (lb) -Max, Cotmp.tMax. Ten. -AIL farces 250 (lb) or less except when shown. TOP CHORD 1-4--369/243,2-4--3171247,2-5--3171247,3-5---369/243 BOT CHORD 1-3--198/323 UnbalancedNOTES- foods. { Catt : enclosed; . RS (directional) and i..zone; left n right exposed; .i. .! end vertical left and right Categoryexposed�C-C for members and forces & MWFRS for reactions shown; Lumber DOL -1,60 plate grip DOL -1,60 3) TCLL: ASCE 7-10; Pr -X0 psf (roof five load: Lumber DOL -1,15 Plate DOL -1. 15); Pf=30.0 psf (flat roof snow: Lumber DOL -1,15 Plate ♦ #"«.,tin.« Unbalancedsnow oods have been considered for this design. g checked5) Plates for a plus or minus 5 degreeiabout its center, bottom6) Gable requires continuous bottom chord bearing, 7) This truss has been designed for a 10,0 psf bottom chord live load nonconcurrent with any other live toads, 8) * This truss has been designed for a live load of 20,Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the t { and any other members, 9) One RT3A USP connectors recommended to connect truss to bearing walls due to UPLIFT at flis) I and 3, This connection is for uplift only and does not consider lateral forces, 10) "Semi-rigid pitchbreaks including heels' Member end fixity model was used in the analysis and design of this truss. NNOWN WARNNO - V "0. pormotem and AM NOTES ON VWS ANO INCLUDED ANTEXAVFEAWCE PAGE MI -7473 rev. i 15 SEFORE USE. DeOgn vo5d for use Inky wash Mlei* connector, This dextgn b ed 00rkv1 trron po tern wn, unci is tar can individuot b component, not a truss system. Before use, the build designer must ve»fy the cabiSty of defign porometers and proper.ty incorpcx'oie this design into the overoas "ding design,. Bracing imutcated 4 to prevent buckOng of indvidud Iran web and/or chord mernbert orriyy. Audit'.. ternporary and permanent bracing Is dways regueed for stabskty and to prevent co#opsf with possibie, persond " `. and property domoge.. For geneon guidance regarding the fobrico6m storage, deflvery, ereck rn and bracing of tn,uses and truss systems. see ANSI/TF11 CdWo, M-$rs and BCSt Su Component Sofelyinformation, avoflobe, from Yrcrs More 9nstitute, 2 ui Ft. Lee Street Suite 312. Atexandria. VA 2131k December ! MII o z X M fF " ° 0 r� e er ' t t cr MN ca n o '�gin° rs ° c c0> on > a "q z 0 `; ° ' c:Ir ID c t CD ID��� 'c 203 �� �. acne � � '� = 2 s- n � cr to a a Q cia`caI'D ` n 0 m< eD q s a ti c, ca can t " n � 0CUD , " _ ?- Hca. c a s MM 6 C? TOP FitPD 'm z co ren ,.«, cile .�.. e?,MR pi C) 4' -� z M e 91 3 n f} _ o 0 cb two ` Ci " u t 0z a, y al. u " Cz r, ° WMIN k ix > W3-6 07 (' w LM c< -s ` 0- cts TCP CHORD "n 3« C7 ++t' G1 R7 tfs C o Zne c roccs 0 a ^CS t7 6i ) Ch CR 80 Ir` h l S a C t o 8, c m 0° i°m Ep 5: ro ' -s (U 3 0 0, 5' 0 a °R a n tecta ° 3`0 3 3 3 c0• µ 0 + #@ Ci ,3 0 it1 °" p � Q? sn t tD 'y 0 *" cR �a � o 0- CP" 5 i2 a ° o : io rod �r c3 < m � oro 0 ca n � cr C7 < m oto co, cr r � ' o a «. da C fA CTU n p. C7 `„, a$ t1 0 +8 - 0.0 a � p 4tT c coos o ° a ua' < �" ?. i ear xo ro` 0 m eco a"� ss� U ��° � a 0 � °�'� �o �� o ca co cO a a o n ii �m 50-5 o 0 z „ c ra 'cc' a� 4. 2- c n o 0nao w. n i m 00 i -c; a a �g°° °cM a YQ o —am ° m cr o o 0 0 o to a c c a ca m M� ° ° ° M°0 m R - o ��, ,� f ,i {�'., .. �, >� �. �' � ___ __ � � �i� � �� --- ._...,� __ . ��,ti - ...� ,.���.. ���. � � .. _.. v_ __ ._ :, � . .�. ...,, .. . .s�. ,.. ,,,� ,� a __ __ _ _ _ — � �a � � �� u �,j . � �. � A ��� � �� �� y �-- . ".� � t .3�� �. x, x `�� - e �. - � — _ . � _ ,� ..� ,.: �" _ w ;' .,� � 3 -J _The first 2510f a drivfrom the existin, edge of pavement into t.e site shall be_ surfaced with concrete, asphalt, brick paver or similar material. Contact Dept of Public -As part of the foundation insPection Works for ROW Permit X03-235-286 L FIRST FRAMfNCjINSPECTION, �i completed, Iun. sealed.® Fdt n andElevation � Certification sha Abe subs review, The certification. roe shbe Professional Land l completed by a .r ficensed in the state of Coloradostab w, was constnicled in J 4,: applicable' bl( Jance with afl, Tunimum setback and -� .. �a USE _1"TY)s i T A `iat ' r F. Malling Address: (it diftrant then property address) d « s Use of + A « D . i n ldf work: .rm is Valum, A + NM s ,, +rte . . , . . . . . . . . . . . Building Permit Permit Number 19617 CTI'I' OF WHEAT RIDGE 12/27/2005 7500 west 29Tx avw,u wheatridge, Co 80033 ' Inspection Llne 303-235-2855 303-234-5933 Residential Mechanical PROPERTY 3615 Teller St Unit: owtvER: Cazoline Mullory (303) 423-0341 Descriptlon Insta1190K Btu furnace, Cof&nan Electric to do furnace hook-up, GFI & light / switch CKv of Wheat Ridg~ PRESCRIpTIVE ENERGY CODE BOILERS / FURNACES A MINIMUM OF 90°h AFUE GAS 1NATER HEATERS A MINIMUM OF.60 ENERGY FACTOR ELECTRIC WATER HEATERS A MINIMUM OF.93 ENERGY FACTpR lETBACK THERMO$TAT REQUIRED (EXCEPT HYDRONIC HEAn 11141 WALI.B n R.Ti CEIUNGS • R-18 CRAWLSPACES Units: Occupancy: Walls: Roof: Stories: Sq FceC I hereby evtlfy fh~llYe eeWuk dY'aose propo,eA Ey IIW permit aDPileadmaR wmnle,+nA do ooc vbhte ~yptlnble oNio~neu. mb orregubabu Mthe City of WAe~t Ald`s or wveunls, euemmb or rnW¢Ilovs of ~emM; that ~11 iaweremmb Wowo, ~nd atleg~tbn~ maAe ~rc ~avnle; W~t I have rtW ud ~pve m WWe by ~B tondWoo~piatod m f1W ~Pp14etion, and tWt I urvme fiJl nepovlbWty for comPdo~n with Nc Went RIECe BaWin{ CoEe (1_&C.) ~ntl &Y e~er appYsabk . W6~[AI~ or~Yl~ce4 for noric mder th4 penait ~ 1 7We pnnk wu luued Ie amrd~em w~N ~~e proWbe~ s[ for1E In your apptlutlov ~nA 6 ~ob~ec[ ro the I~we o(the SfHe of Cobe~ ud ro the 7plu~ Re~ubtlouud BoOdle~ Cotle o( Whnt AWiq ColonEO er ~ny oNm ~pptlaabk oMle~nns of Ne Cky. 3 Every pe'mit I~mad ~L~Ybetnme Inr~l~d uokn Ne wor4 on Ihe Yte auNorized by futh permlt la commevtal wi[Wn 160 d~y~ ~Pke ib Ywan. m NOe Mo~Y ~uthortrd on We tlte by ~ech pe~mit le ~uapeeEW or Wmdovetl fv ~ perbC of 180 dqa oRer We tlme of work b romueneed l If Ihb peemll aapbq a aew pernit mey be uqvlred for a fa of avo-hW tbe nmaant oormtQv reqnirtd, providM m cWeen hrve Gm or xil Ee mWe In We erl~le~lp6o~ ~nd ~pal0eatbu ~ed ~ny suepm~lon or ~b~edamomt hu sot aeeeded one (1) Yar. if~hmt+~rt wtle or U~mpeWOV ar ab~vdmsmt eseutl~ au (1) yar, fu0 fw tla0 be paid tor a ee~r pe'mll. 4 NowaYOf~nyv~ouer~WllbedovetL~twWaWnCet6emtnNMwofw~lersaueie'~drdoaeeprobkm 5 Cmtrubr,Y" notlfyNeHUYdln{IoryMnrtwwtY-four(34)houninaAVavafor0 iupMlovs mdshO rtetlvewNdenapprovalom lupMlm ardbetore promedb 4a, 4 6 •ppppnvYOfdrmlo epeclfiotlem~W11no16emnxrvedrobeapermltfor,oorw. pprvvd o4~yMOblbnofWe ~ ordlvoocq bw, rub w reeuWbo. Chk(1hWtlb[lo4aror SIQVmDAT6 Tuesday, December 27, 2005 Page 1 of 1 Bec 23 OS 12:42p w,.,~~v~~-cs~-~g55 P.2 7 0I WESTV~TFj qVRIDGrz Date : ENUE WHEAT RIQGE, CO 80215 /~I Properry pwner : Property qddress : Contrectur License No. : Company ; &r= I neraey Ind & r 4PPHCatipq. intl tllii 1 Cade (u.B.C.) and all S APP_1CATION Q~~ • Phon : , ~93- ~{23 D3ltl/ ea-FF Co~sUuction Value if' Pertnit Fee [bns ~irig I Use Tax R o ~if'~ic 7~1r ~ ~ ~ se : gummEmm APProvaI : Zoning : Emma== APP►aval : APProval : Occupancy : Walls Roof : StoN , ElecUical License No Compan ~~~1 /~Plumbing License No : ny : Ecpiration Date : Expiraryon Date : APProval : Approval: Expiration Date : Approval : (1) Th4 Ydmil rna hwukotl. qIn (2) Th~oart:t aneX B~ a~~ ~ np+~~nnenn0~~eNbn and 4 wrt !K[ ~tlr Mw o11M SWa IX CdoraGe aM b Me Zminy +wneanaabra°~° N tlierak x'~'O~+oWkse~sonf~di eC (I) II Nis pwmv( axP~ j ~ qv~0 ~Y+. ~Y (~7) tlNS Gam k;w WM or (9) ua dip~q 0wnnixatl is ausoenoM or ~9^sI Phnf aM tpedllopqu~~ j~ Mn~ or ah~ a aN-MY tlq ampw0. ndnyly roG pay~ytl no dqnpe+have l~en w wp De nw0s N IM •■~.w. ans ro rav. ~w i... wn w p.a r« a nswp~Y ~^a ~"O~sEed ane (1I u0L I/ CNlqes en IroEa or if suel~bn a ap~ndpnmeM (5 (4) WM ) ~ ~ehM .w„. ~~~~~~tlM Ilpwn/xByr piuNy~ ~ proce.e~i, b__..' (6) 7M hs pux~ a1 a Oa+~~ta ~ii pqrY «+wNqs ra t a~a kr NI wriMen+vPMel on heaectbn uid ee~aa olMe 011~yq mdes a wy aMr ayYyrq. iwv. rW a ropyly~j~, s Nan na M mlpyyb b o a Poma br. nOran appfipyy of. wy wqlabOn o/IM pipyisipq BUILDING DEPqR : ONLY SIC : Sq. Ft. : Phone : 503 AGREEA EN7 Residential Units : Mechanical License No : Cwnpany : ~33 5. o, /2&, s'O '-6- W Chief Building InapeeMr OWNER/CONTRqCTOR SIGNATURE Of DEPARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number : 4574 BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE Date : 2/11/97 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 Property Owner : Property Address : 3615 TELLER ST Phone : 423-0341 Contractor License No. : Company : Phone : OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certiry that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application, and that I assume full responsibility for compliance with lhe Wheat Ridge Building Code (U.B.CJ and all other applicle Wftat Rjdge prQinances, for work under this permit. (OWNER)(CONTRACTOR)SIGN29:- 1'~l• DATE Construction Value : $100.00 Permit Fee : $22.00 Plan Review Fee : $0.00 Use Tax : $2.00 Total: $24.00 Description : 6' CHAIN LINK FENCE ON N SIDE OF HOUSE TO FRONT FACE BUILDING DEPARTMENT USE ONLY SIC: Sq. Ft.: Approval : 3M 2117197 6' CHAIN LINK TO BE BUILT IN LINE WITH HOUSE Zoning : R-3 Approval : 4 ,p"M "W"N"M Approval : Occupancy : Walls : Roof : Stories : Residential Units : Electrical License No : Company : Expiration Date : Approval : ~ - Plumbing License No : Company : Expiration Date : Approval: N Mechanical License No : Company: Expiration Date : Approval: F&F, (1) This permif was issued in accordance with the provisions set forth in yopur applicalion and is subject [o the laws of the State of Coloratlo antl to the Zoning Re9ulations and Buildiny Code ot Wheat Ridge, Colorado or any other applicable ordinances of the City. (2) This permit shall expire if (A) the work authonzetl is not commencetl within siuty (60) tlays from issue tlate or (B) [he builtling authorizetl is suspentletl or abandoned tor a periotl of 120 days. (3) If this permit expires, a new permit may be acquired for a fee ot one-half the amount normally required, provided no changes have been or will be made in the original plans and specifications antl any suspension or abandonment ha5 not exceeded one (1) year. If changes are made or if suspension or abandonment exceeds one (1) year, (ull fees shall be paid for a new pertnit. (4) No work of any manner shall be done that will change the naturel Flow of water causing a drainage problem. (5) Contrector shall notify the Builtling Inspector hventy-four (24) hours in advance for all inspections and shall receive written approval on inspection card before proceetliing with successive phases of the job. (6) The,issuance of a permit or the approval of drawings and specifications shall not be construed to be a permit for, nor an approval of, any violation of the provisions ot qio buildirg codes or a9yother orUin7rtFe, law, ruje or regulation. Building I JTHIS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR i CALL: 234-5933 24 HOURS PRIOR TO INSPECTION DEPARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number : BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE Date : 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 PropertyOwner: laLK-ET Property Address : 3~G V:;; 1Phone : Contractor License No. : Company :C~~~,~. Phone : ~-Z-~ - p s~r , f ) OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby certify that the setback distances proposed by this pertnit application are accurete, and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; thal all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions printed on this application, and that I assume full responsibility for comPliance with the Wheat Ridge Building Code (U.B.C.) and all other applicable Wheat Ridge ordinances, for work under this permit. (OWNER)(CONT,RACTOR) SIGNED DATE Construction Value : ,0C7_°7 Permit Fee : Plan Review Fee : Use Tax : Total : Description : A^~ BUILDING DEPARTMENT USE ONLY Zo--Ri~ SIC : Sq. Ft. : ~ ~t"s~ Z' I I • ~l ~ Approval:~ayv.. A'o 6t- w1tk li& sK42 Zoning : V.z~ Approval: Approval : Occupancy : Walls : Roof : Stories : Residentiai Units : Electrical License No : Company: Expiration Date : Approval: 1M lPffnNR~Of~7~l Plumbing License No : Company : Expiration Date : Approval: n IPMSEA0([6tlW Mechanical License No : Company : Expiration Date : Approvai: ■ raw. MA (1) This pertnit was issued in accortlance with ihe provisions set foM in yopur appliwlion and is sub'ecl to lhe laws ol the Slate of Colorado and to the Zoning Regulalions and Building Code of Wheat Ritlge, Colorado or any other apPliwble ortlinances of~e Ciry. (2) This pertnit shall expire d(A) the work authonzed is not wmmencetl within sixly (60) days from issue Oale or (8) Ne building authorized is suspended or abantlonetl for a period o1120 days. (3) If this permit evpires, a new permit may Ge acquired for a fee of one-half the amount noimally repuired, proviEed no changes have Oeen or will be made in the original plans and specifwtions and any suspension or abandonment has not exceeded one (1) year. II changes are made or if suspension or abandonment exceetls one (1) year, full fees shall Oe paid for a nev.• permit. (4) No work of any manner shall be done lhat will change the naWralOax olwater causing a dreinage Oroblem. (5) Contractor shall notiy ihe euilding Inspector hventy-four (24) hours in advance for all inspections and shall receive written approval on inspxtion wrd before proceetliing with successive phases of the7'ob. (6) The issuance of a pertnit or Ihe approval of tlrewings and specifcations shall not be construed to be a permit tor, nor an approval ot, any violation of the provisions ol the building codes or any olher ordinance, law, rule or regulation. Building Inspector For Mayor THIS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION ~ C~~ L L~- J2- 30 ' 46 1 v+tirn.)t DEPARTMENT OF GOMMUNITY DEVELOPMENT M94~19181 7500wEST29thAVENUE BUILJING INSPECTION DIVISION PERMIT N0. 234-5933 P.O. BOX838 CITY OF WHEAT RIDGE, COl.O. THIS PERMIT VALID ONLY WHEN SiGNEO BY TNE CHIEF BWLDING INSPECTOR AND RECEIPTEDBELOW. APPLfCATION FOR MISCELLANEOUS PERMIT JOB ADDRESS OWNER Th6rco CONTRACTOR ADDRESS p~,-~~ - ADDRESS i"Il10(Lob I pHONE 3.~ ZIPCODEUSdJ1~ I ~7 o CITY ZIP CODE '~~d3S t CONTRACT PRICE $ ~vO PHONE i qc0a'S LICENSE NO. DATE 3-~ /~-9 Y TYPE GrounA ❑ 1 Woll❑ Proiectinp❑ 01Mr S w D Face . 2. MATERIAL Tofal Spuon F"t $IGNS ILLUMINATION Yea❑ No❑ 3 T pe Etect Permif No . y . . 4. SET BACK FROM PROPERTV LINE N _ 5_ E _ W 2one_ Apprwed,ZOns Inspectw (Spscify whicA is front ) ❑ ❑ ❑ ❑ DisaDDrOVed I. TYPE SolidO More Than 80 % OpanO Lest Then 80% Oqn MATERIAL ? Heiphf FENCES . 3. SET BACK FROM PROPERTY LINE N _ S_ E _W Zons_ AppraW,Zons ImDsctw (SPecify which is }ront) ❑ ❑ ❑ ❑ Disopproved 1 --frob ou ~ a- ki lr fxn_ . 2 ~~17 ~i42L. OTHER 3 . DRAW SKETCH OR SHOW BELOW,THE FENCE,SIGN,OR OTHER STRUCTURE,GIVINu DISTANCES FROM PROPERTY LINES. (SETB4CK5 OR PROJECTIONS INCIUDED) i ~ r ¢ SPECIFY NORTN ~ N STREET N4ME SHOW DISTANCES FROM THE MAIN BUILDING TQADJOINING HOUSES, STREETS, AIdD PROPERTY LINES; ON IRREGULAR LATS, SNOW LFAST DISTANCE TO PROPERTY LINES, NOT MAXIMUM OR pVERAGE DISTANCE. APPLICATION FOR PLUMBING; ELECTRICAL; MECHANICAL PERMIT THIS APPLICATION WILL BECOME A PERMITTO PERFORM THE INDICATED WORK ONLY UPON VALIDATION BV THE BUILDING INSPECTION DIVISION. PERMIT WILL EXPIRE 180 DAYS FROM THE DATE OF ISSUANCE IF WORK IS NOT STARTED WITHIN THAT TIME. ELECTRICAL PERMIT STATE UCENSE N0. ALUMINUM VARE UNDERSIZE B ILLEGAL PLUMBING PERMIT STATE LICENSE N0. FLOOR BSM I5T 2ND 3RD 4TH MECHANICAL PERMIT N0. FUEUC'rtlaOrn GaiOIl ElseSdw Np, WATER CLASET FORCED AIR - BTU TEMPORARY METER WASH BOWL HOT WATER - BTU NEW SERVICE - AMPS BATM TUB STEAM - BTU CHANGE SERVICE-AMPS SHOWER AiR CONDITIONING-BTU L16HTING SINN OTHER HEATING GARBAGE DISP REFRIGERATION 5YSTEM POWER SUB-CIFCUITS WATER HEATER Refri aranf Cxoup UTIIITY(RANGE,DISPOSEF,ETC.) AUTO. WASHER PounEa CMr • FIXTURES DISH WASMER AUTOMATIC SPRINKLER SYSTEM WIRING MOTOFtS d CONTROLS FLDOR DRAIN EIEVATOR SIGNS URINAL TRANSFORMERS 9 RECTFIERS SEWERS ADDITION TO OLD WORK OTHER MOTORS OVER I HP TOTAI FI%TURES I hereby acknowledqe thal this ap0lica- tion ia torrecf and understand that I tannot sfart thif prolett unlil this oppli- ealion is approved. I sholl comply wifh the laws oi the Sfate of Colorodo and to the Zoninq Requlations ond Buildin0 Code of the Ci1y of Wheat Ridpe. Any viololion of the above terme will cause immediote revocation of Ihis Oermil PERMIT FEE J ?.oLC/ USE TAX O • 7oZ TOTAL FEE $ DI APPROVED ' ~~L~~ CHIEF BUILDING' NSPECTOR,CityofJWheaf Ridqe Date Issued 10T VALID UNLESS RECEIPTED t`[ ~ 6 44 ~ CALL2345933 24 HOURS IN ADVANCE FOR INSPECTIONS Ilrnu sio~ry~u d DEPARTMENT OF PLANNING AMD DEVELOPMENT Building Permit Number : 6033 BUtLDING INSPECTION DIVISION - 235-2855 GITY OF W6HEAT RIDGE Date : 10/13/97 7500 WEST29TH AVENUE WMEAT RIDGE, CO 80215 . Property Owner : Property Address : 3615 TELLER ST Phone 423-0341 ContractorLicense No. : 18351 Company : D& S Electric Contractors; Inc. OWNERlCONTRACTOR SIGNATl1RE OF UNDERSTANDING AND AGREEMENT 1 hereby certiy that the setDadc distancea proposed bY a!is Permft epplication are accurate, and.do not violate avplicebie ordlnancea, nil" w regulations of the Cny M Wheat Ridge or made erc axwate: that 1have reatlantlag ree to ebWe oy an condRions pnnteq on application., and that Y ascume futl rosporrsibility for compIianc wfth the WAest RidG Code (U.B.C.) and atlotlter applicatile VJhest fZd e ordf ~nan , kr work under thls (OWNER)(CONIR4CTOR) SIGNED ~ ~ DATE ~ Description : UPGRADE SERVICE TO 125 AMP Phone: 4250852 Construction value : - $1,200:00 Pertnit Fee; $45.00 Plan Review Fee : $0.00 Use Tax: $14.40 Tot01: $59.40 APprrnat : Zoning : Approval : Approval: BUILDING DEPARTMENT USE ONLY Occupancy : Walls : Roof : Stories SIC : Sq. Ft. : Residential Uniis : Elecfical License No : Piumbing License No : Mechanical License No : Company : Company : Company : Expiration Date : Approval : . (1) (a) RThis e0u1 '~a0oneeMB~uuedin~ e ~b~d~o adro~ra~~of~ f20 (3) : . If fNa.pBfmR axPkes. e riev! fe (b) (ej s or Expiration Date : Expiration Date ; Approval : Approval : r Yons eet torth in XoWr appi(catfon and ia su6kG lo the laws of the Stete ot CoWrsdo e~d to the Zaning xatlo a eny oMer appACable adinencea Mthe Ciq~. ,a commen~ea wro~m ekH (ea) aayc trom iswe daro «(e) u,a cwwxq aumohzea is ausaenaed w ror a tee otono-hel( me arrount namely reqWred, provided rw changm heve ti4lin a win ba mde in tlx i ar abantlonment hea rrot exceaAed oire (t) year. If cherqas are matlm a H aiqpenaion a aDandonment b e neWrol flaw of watar eaueln8 a tlwinage problam. . . futir (24) Mun in advence for atl inspeelions antl shall receive xMtten eppoval on inspectlai carO bekre a ana spacmceuons snau rwt be mneauea w oe a pemm ror, m en epproval a, " viaanon or me povisiona le or repuladon. THIS PERMI'f VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPfCTION DEPARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number : BUILDING INSPECTION DIVISION - 235-2855 CITY OF WHEAT RIDGE Date : 7500 WEST 29TH AVENUE WHEAT RIDGE, CO 80215 PropertyOwner : Property Address : ~~n ( s I~' ' Phone: Contractor License No. : 20 q t Company:-P..T 5 -x Llt~t12.ca L co"i-fe, inJ c- OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT I hereby ceAify that the setback distances proposed by this permit appliwtion are acwrate, and do not violate applicable ordinances, rules or regulations of the City o( VJheat Ridge or covenants, easements or restrictions of record; thal all measurements shown, and allegations made are accurate; that I have read and agree to abide by all conditions pnnted on this appiication, and that I assume full responsibility for compliance with the Wheat Ridge Buiiding Code (U.B.C.) and all other applicable Wheat Ridge nordinances, f"ork under this pertnit. (OWNER)(CONTRACTOR) SIGNED CX~>~~CC~VC1L~2t DATE 2/3 Description: sr- rzv,w, UPG2hA~ To /d,5/}~,0 V Phone : y a5~-~ ~yy-a Construction Value : ~ ~ ~r/ Permit Fee : Plan Review Fee : Use Tax : Total : BUILDING DEPARTMENT USE ONLY Zbi~'inriC al ff M-#ilts~ Approval: Zoning : Bu110ing Cb nne`n1s"`.a Approval: SIC : Sq. Ft. : Approval: Occupancy : Walls : Roof : Stories : Residential Units : Electrical License No : Plumbing License No : Mechanical License No : Company : Company : Company : Expiration Date : Expiration Date : Expiration Date : Approval : Approval : Approval : ig ePin-9~mr~a~f ~ RWMn~ 0 90xssRMM" (1) TTis pertnit was luued in axartlance wiN the prodsions set lorth in yopur applkaUon and is suq'ect to the laws of the SWte ol Cdorado and to the Zoniig Regulations aM Buikiny CoCe ol Wneal RiOge, Colo2Ea or any other aDWicabk ordinances ol the Ciry. (2) TTis pertnil shall expire d(A) the work authonzed is nol commenceA within siary (80) tlays hom issue Eate w(B) the EuilEing authorizeA is suspenEed or aCanCOned for a peiioE of 120 days. II this pertnrt expires, a new pertnit may he acQUired la a lee of one-haif the ertaunl nortnalty repuireC, proNOeO no changes have Ceen or vnll be maEe in the anginal plans anC spetiRCations and any suspenslon or aDantlonmenl tus nol e:ceeEed one (1) year. II Uanges are made or il zuspensbn a aDandonment exceeEa one (t) year, tull fees snall be paitl tor a new permit. (a) No work of any manner shall Oe Oaoe thal wili change the naWral Ilow of water rausing a 021nage pioblem. (5) Conlractor sAall rw(ify the Builtllnq Inspector nvenry-lour (24) hours in aEvance br all inspecibns anC shall receive written approval on inspec6on wN Celore proceeCiing witn successive pnases of IhaI'ob. (6) TTe issuance ol a permit or the approval of drawings and spedficalions shall nol be mnsWed lo be a pertnil lor, nor an approval of, any violation ol the provisions of the DuilOinq todes or any oNer otdinanca, law, fule or regulaUon. Chief Building Inspector For Mayor THIS PERMIT VALID ONLY WHEN SIGNED BY THE CHIEF BUILDING INSPECTOR AND MAYOR CALL: 234-5933 24 HOURS PRIOR TO INSPECTION