HomeMy WebLinkAbout2830 Reed Street�Structural Design
\ Calculations
APEX For
ENGINEERS,INC.
WEGHER PATIO
2830 Reed St.
2.15.2021
Balance Architecture
Digitally
signed by
RE�,s
Jared
a�
Lambrecht
Date:
Ss A
2021.02.15
16:18:22
-07'00'
Ta b I e of Contents
Design Loads 3-9
Gravity Design 10-18
Apex Engineers, Inc 2 of 18
Design Loads
Apex Engineers, Inc 3 of 18
Cover Page
Calculation page 1 of 6
PROJECT INFORMATION PAGE
Client
Name
Balance Architecture
Address
2830 Reed St.
Meat Ridge, CO 80033
Phone
303.587.2322
Email
Project Name and Address
Name MGHER PATIO
Address 2830 Reed St.
Meat Ridge, CO 80033
General Information
Building Code 2018 International Residential Code
Bldg. Dept. Meat Ridge, CO
Notes
w Apex-Engineers.com
Apex Engineers, Inc 4 o 18
Project Soils Design Information
Page 2 of 6
Project Soils Information
Foundation Overview
The foundation design provided is based off a minimum allowable presumptive load-bearing value as indicated by
2018 International Residential Code in lieu of a site geotechnical evaluation.
Type
Shallow Foundations
Sulfate Levels
Negligible Sulfate
Frost Depth
36 in
Site Class
C
Foundation Desian Information
Shallow Foundation
Isolated Footing Pressure:
1500 psf
Minimum Pad Dimension:
24 in
Continuous Footing Pressure:
1500 psf
Minimum Wall Footing Wdth:
18 in
Minimum Bearing Pressure:
0 psf
Horizontal Soil Design
Active Pressure: 40 psf/ft
At -Rest Pressure: 60 psf/ft
Passive Pressure: 0 psf/ft
Lateral Sliding Resistance Means: Coefficient of friction
Lateral Sliding Resistance p : 0.35
www.Apex-Engin eers.com
Apex En gin ears, Inc
5 of 18
Wind - Directional Procedure Load Development
Calculation page 3 of 6
WIND DESIGN LOADS -ASCE 7-16, CHAPTER 27 (MWFRS)
DIRECTIONAL PROCEDURE - PART 1, ALL HEIGHTS METHOD
Building 1
Wind Load Site Parameters
Risk Category = 11
Exposure Category = C (Section 26.73)
Topographic Factor, Kit = 1.00 (Section 26.8.2)
Elevation Reduction Factor, Ke = 1.00 (Table26.9-1)
Wind Load Building Parameters
Structure Type =
Directionality factor, Kd =
Gust Factor, G =
Enclosure Classification =
Internal Pressure Coefficient, GC, _
Ch. 27, Minimum Wall Pressure, Pmin. _
Basic Wind Speed, V =
Region Parameters
Region Length, L =
Region Width, W =
Mean Roof Height, H =
Roof Angle =
Edge Strip, a =
Velocity Pressure Exposure Coefficient, Kz _
Velocity Pressure, qct = 0.00256 KeKzKnKdV2=
Building Length / Building Width, US =
Building Height/Length, h/L =
Building HeightfWdth, hA/V =
Buildings
0.85
0.85
Enclosed Buildings
+0.18
16 psf
135 mph
Region 1
60.00 ft
25.00 ft
13.42 ft
18.43 °
3.00 ft
0.85
34 sf
2.40
0.22
0.54
�.Apex-Eng in eers. com
Apex Engineers, Inc
(Table 26.6-1)
(Table 26.13-1)
(Section 27.1.5)
(Section 26.5. 1)
(Figure28.3-1)
6 of 18
Project:
WEGHER PATIO
Client:
Balance Architecture
Engineer:
DCS
APEX
Date:
2/15/2021
v�•x„wz ��
Description:
Wind Load Development- Directional Procedure- Main Building
WIND DESIGN LOADS -ASCE 7-16, CHAPTER 27 (MWFRS)
DIRECTIONAL PROCEDURE - PART 1, ALL HEIGHTS METHOD
Building 1
Wind Load Site Parameters
Risk Category = 11
Exposure Category = C (Section 26.73)
Topographic Factor, Kit = 1.00 (Section 26.8.2)
Elevation Reduction Factor, Ke = 1.00 (Table26.9-1)
Wind Load Building Parameters
Structure Type =
Directionality factor, Kd =
Gust Factor, G =
Enclosure Classification =
Internal Pressure Coefficient, GC, _
Ch. 27, Minimum Wall Pressure, Pmin. _
Basic Wind Speed, V =
Region Parameters
Region Length, L =
Region Width, W =
Mean Roof Height, H =
Roof Angle =
Edge Strip, a =
Velocity Pressure Exposure Coefficient, Kz _
Velocity Pressure, qct = 0.00256 KeKzKnKdV2=
Building Length / Building Width, US =
Building Height/Length, h/L =
Building HeightfWdth, hA/V =
Buildings
0.85
0.85
Enclosed Buildings
+0.18
16 psf
135 mph
Region 1
60.00 ft
25.00 ft
13.42 ft
18.43 °
3.00 ft
0.85
34 sf
2.40
0.22
0.54
�.Apex-Eng in eers. com
Apex Engineers, Inc
(Table 26.6-1)
(Table 26.13-1)
(Section 27.1.5)
(Section 26.5. 1)
(Figure28.3-1)
6 of 18
Wind - Directional Procedure Load Development
Calculation page 4 of 6
Wind Loads: Main Wind Force Resisting System
Pressure, p=gGCp ± gi(GCpi)
Region 1 Region 1 Load Application Cases
Walls
Surface Cp gGCp ±gi(GCpi)
Windward
Project:
WEGHER PATIO
-0.28
Client:
Balance Architecture
Side
Engineer:
DCS
APEX
Date:
2/15/2021
>2h
Description:
Wind Load Development- Directional Procedure- Main Building
Wind Loads: Main Wind Force Resisting System
Pressure, p=gGCp ± gi(GCpi)
Region 1 Region 1 Load Application Cases
Walls
Surface Cp gGCp ±gi(GCpi)
Windward
0.80
Leeward LNV
-0.28
Leeward W/L
-0.50
Side
-0.70
Hip
18.43 °
Roof Pressures along Length
Surface
Cp
Windward Case 1
-0.36
Windward Case 2
0.14
Leeward
-0.57
Roof Pressures along Width
Surface
Cp Case 1
Cp Case 2
0 to h2
-0.93
-0.18
h2 to
-0.89
-0.18
h to 2h
-0.51
-0.18
>2h
-0.33
-0.18
Ref Table 6psf
-8.0 psf
6psf
-14.3 psf
6 psf
-20.0 psf
6 psf
Pext
-16.4psf
-2.1 psf
-22.3 psf
Pext Case 1 Pext Case 2
-32.7 psf 0.9 psf
-31.4 psf
0.9 psf
-20.8 psf
0.9 psf
-15.5psf
0.9 psf
Region 1
CASE 1 CASE 9E 3
.R
Yr -Alf lPo�,� an Yr-fl��)f ••0110. r1/"ll !!r`�'Yr-Ox+rPil 4 r�r�°folP'o'�)p r..
CASE 2 r r r CASE 4
rFr.Rr . •1 R � Il a, rR�
Sewnw YdROI .rvuv.
B1iF Mfl00F OWLp4M6
www.Apex-Eng in eers. com
Apex Engineers, Inc 7 of 18
Building Parameters
Windward Wall Pressures
Leeward Wall
Combined Wall
Level
Height
Wall Trib
Kz
qz
Pext
Pext
Pressure
Uniform Load
Base
0.00 ft
6.42 ft
0.85
33.7 psf
26.9 psf
-14.3 psf
41.2 psf
265 plf
Roof
12.83 ft
6.42 ft
0.85
33.7 psf
26.9 psf
-14.3 psf
41.2 psf
265 plf
Roof Proj.
14.00 ft
1.17 ft
0.85
33.7 psf
-0.7 psf
-7.1 psf
6.4 psf
8 plf
www.Apex-Eng in eers. com
Apex Engineers, Inc 7 of 18
Wind - Directional Procedure Load Development
Calculation page 5 of 6
�.Apex-Eng in eers. com
Apex Engineers, Inc 8 of 18
Project:
W GHER
Client:
Balance Architecture
Balance
Engineer:
DCS
APEX
Date:
2/15/2021
v,xFFwz ��
Description:
Wind Load Development- Directional Procedure- Main Building
�.Apex-Eng in eers. com
Apex Engineers, Inc 8 of 18
Wind - Directional Procedure Load Development
Calculation page 6 of 6
OIL
\Nheat
V 0". R/ m
O
Gq�Mg
D 5\c
�.Apex-Eng in eers. com
Apex Engineers, Inc
9 of 18
W GHER
AProject:
Client:
Balance Architecture
Balance
/{'/y��`\\
Engineer:
DCS
APEX
Date:
2/15/2021
v�,xFFwz ��
Description:
Wind Load Development- Directional Procedure- Main Building
OIL
\Nheat
V 0". R/ m
O
Gq�Mg
D 5\c
�.Apex-Eng in eers. com
Apex Engineers, Inc
9 of 18
Gravity Design
Apex Engineers, Inc 10 of 18
RESIDENTIAL
Address: 2830 Reed St
Lot Size: 17,776 (survey) sq. ft.
Property in the flood plain? NO
Subdivision: MORTENSEN
Related Cases:
Rev. 09/2017
Permit- Plan Review Worksheet
Zoning:
R-2
Lot Width: 150 ft.
If yes, notify PW Floodplain Administrator and add surveying condition FLD
Any conflict? (Y/N) Existing house spans over 2 lots
Type of project (applicable survey conditions in parenthesis):
Maximum Lot Coverage: 40 % 7,110.4 sq. ft.
Existing Improvements (footprints):
House: 1918 sq. ft.
Shed: 190 sq. ft.
Detached garage: sq ft.
Other: sq. ft.
Total Existing 2,108 sq. ft
Lot Coverage 11.9 %
Proposed Improvements (footprints):
House/addition: 2,340 sq. ft.
Shed: 190 sq. ft
Detached Garage: sq. ft.
Other: sq. ft.
Proposed+Existing 2,530 sq. ft
Lot Coverage 14.2 %
Required Setbacks: FR g5'S 5' S 5' R 1 p' S+S must equal 15' min
Provided Setbacks: FR 45' S 60' S 24' R 39'
For additions or new construction, is the structure within 2 feet of minimum setbacks? No
If yes, add surveying condition FND.
Maximum Height: 35 ft.
Maximum Size:
Proposed Height: 17'(tallest, exWing) Proposed Size:
sq. ft.
sq. ft.
Does the bulk plane apply? (Y/N) N
If yes, does it meet on all sides (Y/N): FR S S R
(See 26-642 and 26-120.C.1 -applies to all single-family structures (new, addition, accessory) in R-1 C and R-3)
Parkland Conditions
Does the permit result in a new dwelling unit (new structure or conversion from non -res use)? N
If yes, have parkland dedication fees already been paid (eg with a previous land use approval)?
If fees are owed, add condition PFEE, notify owner, notify building division, enter fee amount in ADG.
Rev. 09/2017
Streetscape Conditions
Does the permit result in any of the following conditions?
❑ Construction of new roads ❑ Platting of new lots
❑ New development ❑ Additions that increase gross floor area (not just the footprint) by
60% or more
(proposed floor area — existing floor area ) / existing floor area = °% increase
If any box above is checked...
For SF/DUPLEX-Is there existing ❑ Curb ❑ Gutter L]5 -ft+ sidewalk adjacent to the property?
If curb, gutter or sidewalk is missing, streetscape construction or fees -in -lieu will be required.
MULTIFAMILY Does the frontage meet current city standards?
If not, streetscape construction or fees -in -lieu will be required.
Fees -in -lieu of dedication or construction are due at the time the permit is issued.
Access Conditions (apply to all new driveways, garages, additions, or new homes/units)
J For one and two-family dwellings, the first 25' of driveway area from the existing edge of
pavement into the site shall be surfaced with concrete, asphalt, brick pavers or similar materials.
❑ For all uses other than one and two family dwellings, no vehicle entrances or exits may be closer
than 25' to any property line, except when used as joint access for two or more lots.
® In residential zone districts, curb cuts shall be at least 10 feet and not more than 24 feet in width.
❑ One and two-family dwellings may have horseshoe driveways, provided that the street accesses
are at least 30 feet apart, measured from the interior edges.
El For all uses, one access point per property is permitted.
Landscaping Conditions (apply to additions and new dwelling units)
® For one -and two-family dwellings, one tree for every 70 feet of street frontage is required.
Frontage of lot 150 - width of driveway 8 /70- 3 (round up for required trees)
Street trees required: 3 Street trees provided: 3
® 100% of the front yard and 25% of the entire lot must be landscaped prior to issuance of C.O.
® In the event that landscaping cannot be installed due to inclement weather prior to the issuance of
a C.O., an escrow agreement with financial guarantees may be allowed to ensure future
installation. 125% of the cost of the proposed improvements will be required with the agreement.
These funds will be reimbursed back to the property owner or contractor once the improvements
are in place.
Dwelling Unit
❑ Not approved as an independent dwelling unit.
SCHEDULE -WOOD FASTENING
IRC TABLE 602.3(1)
DESCRIPTION
NUMBER AND TYPE OF
SPACING AND
OF BUILDING
FASTENERA•"•C
FASTENERS
ELEMENTS
NUMBER AND TYPE OF FASTENERA"•C
EDGE" FIELDC•E
WOOD STRUCTURAL PANELS, SUBFLOOR, ROOF AND INTERIOR WALL
SHEATHING TO FRAMING AND PARTICLEBOARD WALL SHEATHING TO
FRAMING [SEE TABLE R602.3(3) FOR WOOD STRUCTURAL PANEL
EXTERIOR WALL SHEATHING TO WALL FRAMING]
30.3/8'-1/2'
6dCOMMON (2'x0.113')(SUBFLOOR AND WALL)
6"
12"E
(3) 8d COMMON (2-1/2'x0.131'); OR
8d COMMON (2 1/2'X0.131) (ROOF)
PLATE
(3) 10d BOX(Yx0.128')
31.19/52'-3/4'
8d COMMON (2-1/2'x0.131')
6"
12"E
32.7/8'-1-1/4'
10dCOMMON (3'x0.148')
6"
12"
OTHER WALL SHEATHINGc
33.1/2'
1-1/2' GALVANIZED ROOFING NAIL
3"
6"
STRUCTURAL
(7/16' HEAD DIAMETER)
FACE NAIL
TO PARALLEL RAFTER
CELLULOSIC
REBAR CONDITION
(HEEL JOINT)
FORMED SURFACES EXPOSED TO
GROUND OR WEATHER
FIBERBOARD
5. COLLAR TIE TO RAFTER,
(3)10d COMMON (3'x0.148'); OR
FACE NAIL
SHEATHING
(4)10d BOX (3'x0.128')
EA RAFTER
RIDGE STRAP TO RAFTER.
34.25/32'
1-3/4' GALVANIZED ROOFING NAIL
3"
6"
STRUCTURAL
(7/16' HEAD DIAMETER)
(3)16d BOX (3-1/2'x0.135'); OR
(1) EA SIDE'
CELLULOSIC
(4)10d BOX(3'x0.128')
3500 psi
7. ROOF RAFTERS TO RIDGE
FIBERBOARD
END NAIL
VALLEY OR HIP RAFTERS;
(3)10d BOX (3'x0.128')
SHEATHING
OR ROOF RAFTER TO 2'
(3)10d COMMON (3'x0.148'); OR
TOE NAIL
35.1/2'GYPSUM
1-1/2' GALVANIZED ROOFING NAIL (7/16'HEAD
7"
7"
SHEATHING
DIAMETER); OR 11/4'SCREWS TYPE WORS
24" OC, FACE NAIL
BRACED WALL PANELS)
36.5/8'GYPSUM
1-3/4' GALVANIZED ROOFING NAIL (7/16' HEAD
7"
7"
SHEATHING
DIAMETER); OR 15/8'SCREWSTYPEWORS
GLULAM BEAMS
DF/DF
WOOD STRUCTURAL PANELS, COMBINATION SUBFLOOR
UNDERLAYMENT TO FRAMING
37.YVAND 8dCOMMON (2-1/2k0.131') 6" 12"
LESS
38.7/8'-1' 8dCOMMON (2-1/2k0.131') 6" 12"
39.11/8'-11/4' 10d COMMON(Yx0.148') 6" 12"
NOTES:
A. NAILS ARE SMO OTH-COMMON, BOX OR DEFORMED SHANKS EXCEPT NM ERE
OTHERWISE STATED. NAILS USED FOR FRAMING AND SHEATHING CONNECTIONS
SHALL HAVE MIN MUM AVERAGE BENDING YIELD STRENGTHS AS SH OWN 80KSI
FOR SHANK DIAMETER OF 0.192 INCH (20D COMMON NAIL), 90 KSI FOR SHANK
DIAMETERS LARGER THAN 0.142 INCH BUT NOT LARGER THAN 0.177 INCH,AND
100 KSI FOR SHANK DIAMETERS OF 0.142 INCH OR LESS.
B. STAPLES ARE 16 GAGE WIRE AND HAVE AMINIMUM 7/16 -INCH ON DIAMETER
CROWN WIDTH.
C. NAILS SHALL BE SPACED AT NOT MORE THAN 6 INCHES ON CENTER ATALL
SUPPORTS WHERE SPANS ARE 48 INCHES OR GREATER.
D. FOUR -FOOT BY 8 -FOOT OR 4 -FOOT BY 9 -FOOT PANELS SHALL BE APPLIED
VERTICALLY.
E. SPACING OF FASTENERS NOT INCLUDED IN THIS TABLE SHALL BE BASED ON
TABLE R602.3(2).
F. WHERE THE ULTIMATE DESIGN WIND SPEED IS 130 MPH OR LESS, NAILS FOR
ATTACHING WOOD STRUCTURAL PANEL ROOF SHEATHING TO GABLE END WALL
FRAMING SHALL BE SPACED 6 INCHES ON CENTER. WHERE THE ULTIMATE
DESIGN WIND SPEED IS GREATER THAN 130 MPH, NAILS FOR ATTACHING PANEL
ROOF SHEATHING TO INTERMEDIATE SUPPORTS SHALL BE SPACED 61NCHES ON
CENTER FOR MINIMUM 48 -INCH DISTANCE FROM RIDGES, EAVES AND GABLE END
WALLS;AND 4 INCHES ON CENTER TO GABLE END WALL FRAMING.
G. GYPSUM SHEATHING SHALL CONFORM TO ASTM C 1396 AND SHALL BE INSTALLED
IN ACCORDANCE WITH GA 253. FIBERBOARD SHEATH ING SHALL CONFORM TO
ASTM C 208.
H. SPACING OF FASTENERS ON FLOOR SHEATHING PANEL EDGES APPLIES TO
PANEL EDGES SUPPORTED BY FRAMING MEMBERS AND REQUIRED BLOCKING
AND AT FLOOR PERIMETERS ONLY. SPACING OF FASTENERS ON ROOF
SHEATHING PANEL EDGES APPLIES TO PANEL EDGES SUPPORTED BY FRAMING
MEMBERS AND REQUIRED BLOCKING. BLOCKING OF ROOF OR FLOOR SHEATHING
PANEL EDGES PERPENDICULAR TO THE FRAMING MEMBERS NEED NOT BE
PROVIDED EXCEPTAS REQUIRED BY OTHER PROVISIONS OF THIS CODE. FLOOR
PERIMETER SHALL BE SUPPORTED BY FRAMING MEMBERS OR SOLID BLOCKING.
I. WHERE ARAFTER IS FASTENED TO AN ADJACENT PARALLEL CEILING JOIST IN
ACCORDANCE WUH THIS SCHEDULE, PROVIDE TWO TOE NAILS ON ONE SIDE OF
THE RAFTER AND TOE NAILS FROM THE CEILING JOIST TO TOP PLATE IN
ACCORDANCE WITH THIS SCHEDULE. THE TOE NAIL ON THE OPPOSITE SIDE OF
THE RAFTER SHALL NOT BE REQUIRED.
LENGTH EAJOINT
SCHEDULE - CONCRETE REBAR
DEVELOPMENT LENGTHS - La
Fc = 3000 PSI Fc = 4000 PSI
BAR STD.La CLASS B BAR STD. La CLASS B
SIZE T; P. TOP TYR. TOP SIZE TYR. TOP TYR. TOP
#4 22" 29" 29" 38" #4 19" 25" 25" 33"
#5 28" 36" 37" 47" #5 24" 31" 32" 41"
#6 33" 43" 43" 56" #6 29" 37" 38" 49"
#7 48" BY BY 82" #7 42" 54" 55" 71"
#8 55" 72" 72" 94" #8 48" 62" 63" 81"
#9 62" 81" 81" 106" #9 54" 70" 71" 91"
STANDARD HOOKS & BAR BENDS
f'c = 3000 PSI Fc = 4000 PSI
BAR
16" OC FACE NAIL
Le%' BAR Le.
(3)16d BOX (3-1/2'x0.135')
Lan
"Al'• Lan "W"
SIZE
180 90 SIZE 180 90
#4
6"
3" 2 1/2" 6" #4 6" 3" 2 1/2" 6"
#5
10"
3 3/4" 2 1/2" 7 1/2" #5 9" 3 3/4" 2 1/2" 7 1/2"
#6
12"
4 1/2" 3" 9" #6 10" 4 1/2" 3" 9"
#7
14"
5 1/4" 3 1/2" 10 1/2" #7 12" 5 1/4" 3 1/2" 10 1/2"
#8
16"
6" 4" 12" #8 14" 6" 4" 12"
#9
18"
9" 4 1/2" 13 1/2" #9 15" 9" 4 1/2" 13 1/2"
BAR BENDS
180 DEGREE HOOK
90 DEGREE HOOK
m
m
m
FACE NAIL
CORNERS AND
FIs Db
UIO Db
T
De
I
18. V BRACE TO EA STUD
Len+i
w
I
U I
I
Lan
Lan
STIRRUPS, TIES,
& HOOPS
BAR
O
Le,,
BAR O Le,,
90 135 1 180
SIZE
SIZE 90 135 180
#3
1 1/2"
3" 3" 2 1/2"
#6 41 9"
4 1/2"
3"
#4
2"
3" 3" 2 1/2"
#7 5 1/4" 10 1/2"
5 1/4"
3 1/2"
#5
2 1/2"
3 3/4" 3 3/4" 2 1/2"
#8 6" 12"
6"
4"
90 DEGREE HOOK
135 DEGREE HOOK
180 DEGREE HOOK
m
m
FACE NAIL
m
(2)8d COMMON (2-1/2'0.131'); OR
Db T
Db
Db
(2)16d BOX(3-1/2'x0.135'); OR
BLIND AND
OR GIRDER
(2)16d COMMON (3-1/2'x0.162')
FACE NAIL
25.2' PLANKS (PLANK &
RECTANGULAR
CIRCULAR
BAR
BAR
BEAM/COLUMN TIE
COLUMN/PIER TIE
CLEARANCE
SPLICE
RM JOIST
PJ
STD. La\
\y
27. BUILT-UP GIRDERSAND
20d COMMON (4'x 0.192')
NAIL EA LAYER AS
BEAM, 2' LUMBER LAYERS
FOLLOWS: 32' OC AT
Db
TOP AND BOTTOM
(3)
(4)
10d BOX (3'x0.128')
24' OC FACE NAIL AT
T
TOP AN D BOTTOM
STAGGERED ON
OPPOSITE SIDES
l-
I
Db
(2) 20d COMMON (4'x0.192'); OR
AT EA SPLICE,
(3) 10d BOX(3'x0.128')
FACE NAIL
NOTES:
1. USE THE ABOVE TABLE UNLESS NOTED OTHERSIZE ON PLAN OR IN
DETAILS.
2. PROVIDE 6" LAP ATALL WELDED WIRE FABRIC JOINTS.
3. PROVIDE 1 Db (1" MINIMUM) CLEARANCE BETWEEN ADJACENT BARS.
4. PROVIDE WIRE TIES AT EACH END OF BAR SPLICE.
SCHEDULE -WOOD FASTENING
IRC TABLE R602.3(l)
I1
DESCRIPTION OF
NUMBER AND TYPE OF
SPACINAND
BUILDING ELEMENTS
FASTENERA•"•C
I LOCATGION
ROOF
1. BLOCKING BETWEEN
(3) 8d COMMON (2-1/2'x0.171'); OR
TOE NAIL
CEILING JOISTS OR RAFTERS
(3)10d BOX(3'x0.128')
ANCHOR BOLTS HEX -HEAD UNO
TO TOP PLATE.
EPDXYANCHOR RODS
ASTM A36
2. CEILING JOISTTO TOP
(3) 8d COMMON (2-1/2'x0.131'); OR
PER JOIST,
PLATE
(3) 10d BOX(Yx0.128')
TOE NAIL
3. CEILING JOIST NOT
(3)16d COMMON (3-1/2'x0.162'); OR
FACE NAIL
ATTACHED TO PARALLEL
(4)10d BOX (3'x0.128')
WELDED WIRE FABRIC
RAFTER, LAPS OVER
PORTLAND CEMENT
ASTM C 150
PARTUIONS (NO THRUST)
ASTM C 618,15% MAX
CONCRETE AGGREGATES
4. CEILING JOISTATTACHED
PER TABLE R802.5.1(9)
FACE NAIL
TO PARALLEL RAFTER
HILTIHIT -HY200 ROR SIMPSONSETXP
REBAR CONDITION
(HEEL JOINT)
FORMED SURFACES EXPOSED TO
GROUND OR WEATHER
2
5. COLLAR TIE TO RAFTER,
(3)10d COMMON (3'x0.148'); OR
FACE NAIL
FACE NAIL OR 1 1/4'X20 GA.
(4)10d BOX (3'x0.128')
EA RAFTER
RIDGE STRAP TO RAFTER.
REQUIREMENTS
CONCRETE USE
6. RAFTER OR ROOF TRUSS
(3)10d COMMON (3'x0.148'); OR
(2) TOE NAIL,
TO TOP PLATE
(3)16d BOX (3-1/2'x0.135'); OR
(1) EA SIDE'
FOOTINGS
(4)10d BOX(3'x0.128')
3500 psi
7. ROOF RAFTERS TO RIDGE
(2)16d COMMON (3-1/2'x0.162'); OR
END NAIL
VALLEY OR HIP RAFTERS;
(3)10d BOX (3'x0.128')
I NW
OR ROOF RAFTER TO 2'
(3)10d COMMON (3'x0.148'); OR
TOE NAIL
RIDGE BEAM
(4)10d BOX(3'x0.128')
WOOD MATERIAL SPECIFICATIONS
WALL
S. STUD TO STUD (NOTAT
16d COMMON (3-1/2'x0.162'); OR
24" OC, FACE NAIL
BRACED WALL PANELS)
10d BOX(3'x0.128')
16" OC, FACE NAIL
9. STUD TO STUDAND
16d COMMON (3-1/2'x0.162'); OR
16" OC, FACE NAIL
ABUTTING STUDS AT
GLULAM BEAMS
DF/DF
INTERSECTION WALL
24F -V4
MULTI SPAN
16d BOX (3-1/2'0.135'); OR
12" OC, FACE NAIL
CORNERS (Al BRACED
WALL PANELS)
Fb = 1700 psi, E = 1.3 x 1OE6 psi
PARALLEL STRAND LUMBER, PSL
10. BUILT-UP HEADER (2' TO
16d COMMON (3-1/2'x0.162'); OR
16' OC EAEDGE,
2' HEADER WUH 1/2'
COMMON NAIL
FACE NAIL
SPACER)
16dBOX (3-1/2'x0.135')
12' OC EA EDGE,
LENGTH
8d
FACE NAIL
11. CONTINUOUS HEADER
(4) 8d COMMON (2-1/2'x0.131'); OR
TOE NAIL
TO STUD
(4)10d BOX(3'x0.128')
3"
12.TOP PLATE TO TOP
16d COMMON (3-1/2'0.128'); OR
16" OC FACE NAIL
PLATE
10d BOX 3'x0.128'
12" OC FACE NAIL
13. DOUBLE TOP PLATE
(8) 16d COMMON(3-1/2'x0.162'); OR
EASIDE OF END
SPLICE FOR SDCsA-D2
(12) 10d BOX(Yx0.128')
JOINT, FACE NAIL
WUH SEISMIC BRACED
(MIN 24' LAP SPLICE
WALL LINE SPACING Q5'
LENGTH EAJOINT
14. BOTTOM PLATE TO
16d COMMON (3-1/2'x0.135'); OR
16" OC FACE NAIL
JOIST, RIM JOIST, BAND
JOIST OR BLOCKING (NOT
16dBOX (3-1/2'x0.135')
12" OC FACE NAIL
AT BRACED WALL PANELS)
15. BOTTOM PLATE TO
(2)16d COMMON (3-1/2'x0.162'); OR
16" OC FACE NAIL
JOIST, RM JOIST, BAND
(3)16d BOX (3-1/2'x0.135')
JOIST OR BLOCKING (AT
BRACED WALL PANELS)
16. STUD TO TOP OR BOTTOM
(4) 8d BOX (21/2'x0.113'); OR
TOENAIL
PLATE
(3)16d BOX (31/2'x0.135'); OR
(4) 8d COMMON (2-1/2'x0.131'); OR
(4) 10d BOX ( 3'x0.128'); OR
(3)16d BOX (31/2'x0.135'); OR
ENDNAIL
(2)16d COMMON (3-1/2'x0.162'); OR
(3)10d BOX(3'x0.128')
17. TOP PLATE, LAPS AT
(2)16d COMMON (3-1/2'0.162'); OR
FACE NAIL
CORNERS AND
(3) 10d BOX(3'x0.128')
INTERSECTIONS
18. V BRACE TO EA STUD
(3) 8d BOX (21/2'X0.113'); OR
FACE NAIL
AND PLATE
(2)8d COMMON (2-1/2'x0.131'); OR
(2)10d BOX (3'X0.128')
19. 1'x6' SHEATHING TO EA
(3)8d BOX (21/2'X0.113'); OR
FACE NAIL
BEARING
(2)8d COMMON (2-1/2'0.131'); OR
(2)10d BOX (3'X0.128')
20. Vx8'AND WIDER
SHEATHING TO EABEARING
(3)8d COMMON (2-1/2'0.131'); OR
(3) 10d BOX(3'X0.128')
FACE NAIL
FLOOR
21. JOISTTO SILL TOP
4 8d BOX 21/2'X0.113';OR
TOENAIL
PLATE OR GIRDER(3)
3 8d COMMON (2-1/2'X0.1 31'); OR
3 10d BOX 3'X0.128'
O ( )
22. RM JOIST, BAND JOIST,
8d BOX (2-1/2'x0.113')
4" OC, TOE NAIL
OR BLOCKING TO SILL OR
TOP PLATE (ROOF
(3) 8d COMMON (2-1/2'x0.131'); OR
(3) 10d BOX(3'X0.128')
6" OC, TOE NAIL
APPLICATIONS ALSO)
23.1'x6' SUBFLOOR OR
(3) 8d COMMON (2-1/2'x0.131'); OR
FACE NAIL
LESS TO EAJOIST
(2)8d COMMON (2-1/2'0.131'); OR
(2)10d BOX(3'x0.128')
24. 2' SUBFLOOR TO JOIST
(2)16d BOX(3-1/2'x0.135'); OR
BLIND AND
OR GIRDER
(2)16d COMMON (3-1/2'x0.162')
FACE NAIL
25.2' PLANKS (PLANK &
(2)16d BOX (3-1/2'x0.135'); OR
EA BEARING,
BEAM -FLOOR&ROOF)
(2)16d COMMON(3-1/2'x0.162')
FACENAIL
26. JOISTTO BAND JOIST OR
(3)16d COMMON (3-1/2'x0.135'); OR
END NAIL
RM JOIST
(4)10d BOX(3'x0.128')
27. BUILT-UP GIRDERSAND
20d COMMON (4'x 0.192')
NAIL EA LAYER AS
BEAM, 2' LUMBER LAYERS
FOLLOWS: 32' OC AT
TOP AND BOTTOM
STAGGERED
10d BOX (3'x0.128')
24' OC FACE NAIL AT
TOP AN D BOTTOM
STAGGERED ON
OPPOSITE SIDES
AND:
AT ENDS AND
(2) 20d COMMON (4'x0.192'); OR
AT EA SPLICE,
(3) 10d BOX(3'x0.128')
FACE NAIL
28. LEDGER STRIP
316d BOX3-1/2'x0.135';OR
EAJOIST OR
SUPPORTING JOISTS OR
(3)16d COMMON (3-1/2'x0162'); OR
RAFTER, FACE NAIL
RAFTERS
(4)10d BOX(3'x0.128')
29. BRIDGING TO JOIST
(2)10d BOX (3'x0.128')
I EA END, TOE NAIL
NOTES -GENERAL
1. THESE DRAWINGS ARE INTENDED TO BE USED WITH ARCHITECTURAL
AND MECHANICAL DRAWINGS. CONTRACTOR IS RESPONSIBLE FOR
COORDINATING SUCH REQUIREMENTS INTOTHEIR SHOP DRAWINGS AND
WORK.
2. NO OPENING SHALL BE MADE IN ANYSTRUCTURAL MEMBER WITHOUT
THE WRITTEN APPROVAL OF THE ENGINEER.
3. NO CHANGE IN SIZE OR DIMENSION OF STRUCTURAL MEMBERS SHALL BE
MADE WITHOUT TH E WRITTEN APPROVAL OF THE ENGINEER.
4. THE CONTRACTOR IS RESPONSIBLE FOR LIMITING THE AMOUNT OF
CONSTRUCTION LOAD IMPOSED UPON STRUCTURAL FRAMING.
CONSTRUCTION LOADS SHALL NOT EXCEED THE DESIGN CAPACITY OF THE
FRAMING ATTHE TIME THE LOADS ARE IMPOSED.
5. THE STRUCTURE IS DESIGNED TO FUNCTION AS A UNIT UPON
COMPLETION. THE CONTRACTOR IS RESPONSIBLE FOR FURNISHING ALL
TEMPORARY BRACING AND/OR SUPPORT THAT MAY BE REQUIRED AS THE
RESULT OF THE CONTRACTOR'S CONSTRUCTION METHODS AND/OR
SEQUENCES.
6. UNLESS OTHERWISE NOTED, FIREPROOFING METHODS AND MATERIALS
FOR STRUCTURAL MEMBERS ARE NOT SHOWN ON STRUCTURAL
DRAWINGS. REFERENCE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS
FOR FIRE RATING REQUIREMENTS, FIREPROOFING METHODS AND
MATERIALS.
7. DO NOT SCALE THESE DRAWINGS. USE DIMENSIONS SHOWN ON PLANS.
8. THE CONTRACTOR SHALL INFORM THE ARCHITECT/ENGINEER OF ANY
DEVIATION FROM THE CONTRACT DOCUMENTS. THE CONTRACTOR SHALL
NOT BE RELIEVED OF THE RESPONSIBILITY FOR SUCH DEVIATION BYTHE
ARCHITECT/ENGINEER'S APPROVAL OF SHOP DRAWINGS, PRODUCT DATA,
ETC., UNLESS HE HAS SPECIFICALLY INFORMED THE ARCHITECT/ENGINEER
OF SUCH DEVIATION ATTHE TIME OF SUBMISSION, AND THE ARCHITECT/
ENGINEER HAS GIVEN WRITTEN APPROVAL TO THE SPECIFIC DEVIATION.
9. ALL THINGS WHICH, IN THE OPINION OF THE CONTRACTOR, APPEAR TO
BE DEFICIENCIES, OMISSIONS, CONTRADICTIONS, BE BROUGHT TO THE
ATTENTION OF THE ARCH ITECT/ENGINEER. PLANSAND/OR
SPECIFICATIONS WILL BE CORRECTED, OR WRITTEN INTERPRETATION OF
THE ALLEGED DEFICIENCY, OMISSION, CONTRADICTION OR AMBIGUITY WILL
BE MADE BY THE ARCHITECT/ENGINEER BEFORE THE AFFECTED WORK
PROCEEDS.
10. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL ERRORS OF
DETAILING, FABRICATION AND INSTALLATION. THE CONTRACTOR SHALL
MAKE ALL MEASUREMENTS IN THE FIELD NECESSARYTO VERIFYOR
SUPPLEMENT DIMENSIONS SHOWN ON THE CONTRACT DRAWINGS AND HE
SHALL VERIFYTHATALL DIMENSIONS SHOWN ON THE SHOP DRAWINGS
ARE COORDINATED WITH THE DIMENSIONS AND REQUIREMENTS OF THE
CONTRACT DRAWINGS. REVIEW OF THE SHOP DRAWINGS DOES NOT
RELIEVE THE CONTRACTOR OF RESPONSIBILITY FOR COMPLETING THE
WORK SUCCESSFULLY IN ACCORDANCE WITH THE CONTRACT DRAWINGS
AND SPECIFICATIONS.
11. SUBMIT PRINTS OR ELECTRONIC COPIES OF EACH SHOP DRAWINGS.
REPRODUCIBLE COPIES OF CONTRACT DOCUMENTS SHALL NOT BE USED
AS SHOP DRAWINGS. SHOP DRAWINGS SHALL BE REVIEWED BY
CONTRACTOR PRIOR TO SUBMISSION. CONTRACTOR STAMP SHOP
DRAWINGS ACCEPTING RESPONSIBILITY FOR COORDINATION OF
DIMENSIONS SHOWN IN THE CONTRACT DOCUMENTS, QUANTITIES AND
COORDINATION WITH OTHER TRADES. DRAWINGS NOT BEARING
CONTRACTOR'S STAMP MAY BE REJECTED AT THE DISCRETION OF THE
ARCHITECT OR STRUCTURAL ENGINEER.
12. REVIEW AND RETURN OF SHOP DRAWINGS SHALL BE BASED ON A
MINIMUM OFTEN 10 WORKING DAYS IN THE STRUCTURAL ENGINEER'S
OFFICE FROM RECEIPT OF SUBMISSION TO RETURN TO THE NEXT PARTY
FOR THEIR ACTION. SHOP DRAWINGS SHOULD BE SUBMITTED
INCREMENTALLYAS APPROPRIATE PACKAGES ARE PREPARED TO
EQUALIZE THE WORKLOAD FOR REVIEW OF THE DRAWINGS. SUBMISSION
OF A LARGE VOLUME OF SHOP DRAWINGS AT ONE TIME MAY RESULT IN
REVIEWTIMES WHICH WILL EXCEED THOSE NOTED ABOVE. DEFINITION OF
A "LARGE VOLUME" OF SHOP DRAWINGS IS SUBJECT TO INTERPRETATION.
NOTES -FOUNDATION
1. CONTRACTOR SHALL BE FULLY FAMILIAR WITH IBC CHAPTER 18 FOR USE
OF PRESUMPTIVE LOAD-BEARING CAPACITY.
2. CONTRACTOR SHALL USE IBC SPECIFICATIONS AND DETAILS FOR
PLACEMENT OF PERIMETER DRAINS, UNDER -SLAB DRAINS, AND ANY OTHER
SOILS RELATED ITEMS.
3. ALL FOUNDATIONS TO BEAR ON ORIGINAL, UNDISTURBED SOIL. REMOVE
ANY MUD, ORGANIC SILT, ORGANIC CLAYS, PEAT OR UNPREPARED FILL
PRIOR TO PLACING FOUNDATIONS.
4. ALL FOOTING EXCAVATIONS TO BE APPROVED BYA QUALIFIED
GEOTECHICAL ENGINEER PRIOR TO PLACING CONCRETE.
5. ALL FOOTINGS SHALL EXTEND BELOW FROST DEPTH, REFERENCE
DESIGN INFORMATION FOR FROST DEPTH.
NOTES -CONCRETE
1. ALL CONCRETE CONSTRUCTION TO CONFORM TO ACI "BUILDING CODE
REQUIREMENTS FOR REINFORCED CONCRETE", THE GOVERNING EDITION
OF THE ACI 318, AND ACI "SPECIFICATIONS FOR STRUCTURAL CONCRETE
FOR BUILDINGS" ACI 301, UNLESS NOTED OTHERWISE.
2. WATER REDUCING ADD MIXTURES ARE ALLOWED IN CONCRETE MIX
DESIGNS.
3. SYNTHETIC MICRO -FIBERS ARE NOT ALLOWED UNLESS SPECIFICALLY
NOTED IN THESE DRAWINGS.
4. UNLESS OTHERWISE SHOWN IN THE ARCHITECTURAL DRAWINGS,
PROVIDE 3/4" CHAMFERS ATTHE EDGES THATARE EXPOSED TO VIEW IN
THE FINISHED STRUCTURE.
5. REFERENCE ARCHITECTURAL DRAWINGS FOR DOOR AND WINDOW
OPENINGS, DRIP SLOTS, REGLETS, MASONRY, ANCHORS, BRICK LEDGE
ELEVATIONS AND FOR MISCELLANEOUS EMBEDDED PLATES, BOLTS,
ANCHORS, ANGLES, ETC.
6. REFERENCE ARCHITECTURAL DRAWINGS FOR CONCRETE FINISHES.
WHERE FINISH IS NOT SPECIFIED, CONFORM TO REQUIREMENTS OF ACI
301.
7. REFERENCE MECHANICAL PLUMBING AND ELECTRICAL DRAWINGS FOR
DRAINS SLEEVES OUTLET BOXES CONDUIT ANCHORS ETC.
8. CONTACT APEX ENGINEERS, INC. IF HOUSE KEEPING PADS OR INERTIA
BASES ARE REQUIRED BEYOND WHAT IS SHOWN IN THE STRUCTURAL
CONTRACT DOCUMENTS.
9. ALL REINFORCING STEEL TO BE DETAILED IN ACCORDANCE WITH ACI
"MANUAL OF STANDARD PRACTICE FOR DETAILING REINFORCED
CONCRETE STRUCTURES."
10. REINFORCING SHALL BE CONTINUOUS WHEREVER POSSIBLE. SPLICES
AND LAPS TO CONFORM TO ACI 318. REFER TO CONCRETE REBAR
SCHEDULE.
11. DOWELS IN FOOTING, WALLS, AND DRILLED PIERS MUST BE IN POSITION
BEFORE PLACING CONCRETE WHENEVER POSSIBLE.
12. REFERENCE TYPICAL FOUNDATION DETAILS FOR INFORMATION ON
REINFORCING REQUIREMENTS AT WALL AND SLAB OPENINGS.
13. REFERENCE TYPICAL FOUNDATION DETAILS FOR INFORMATION ON
REINFORCING REQUIREMENTS AT CORNER AND TEE INTERSECTIONS.
14. PROVIDE VERTICAL CONTROL JOINTS ON ALL POURED CONCRETE
WALLS AND BASEMENT WALLS. SPACE JOINTS AT 3 x WALL HEIGHT FOR
WALLS LESS THAN 10'-0" AND WALL HEIGHT FOR TALLER WALLS. PROVIDE
ADDITIONAL JOINT WITHIN 10'-0" OF CORNERS.
15. OPENINGS IN SLAB OF V-4" AND LESS ON A SIDE ARE GENERALLY NOT
SHOWN ON THE STRUCTURAL DRAWINGS. REFERENCE ARCHITECTURAL
AND MECHANICAL DRAWINGS FOR SUCH OPENINGS.
MATERIAL SPECIFICATIONS
STEEL MATERIAL SPECIFICATIONS
STEEL MEMBERS
MATERIAL
WIDE FLANGE SHAPES W
ASTM A992
CHANNELS C ANGLES L
ASTM A36
PLATES
ASTM A36
HOLLOW STRUCTURAL SHAPES HSS
ASTM A500, GRADE C
HIGH STRENGTH BOLTS
ASTM F3125, GRADE A325
ANCHOR BOLTS HEX -HEAD UNO
ASTM F1554 (55 ksi)"Si"
EPDXYANCHOR RODS
ASTM A36
STEEL DECK, PLAIN STEEL
ASTM A1008, 33 ksi
STEEL DECK, GALVANIZED
ASTM A653, 33 ksi
NON -SHRINK GROUT, COL. BASES
5000 psi 28 DAY STRENGTH
CONCRETE & REINFORCING STEEL SPECIFICATIONS
MATERIAL
SPECIFICATION
REINFORCING BARS
ASTM A615, GRADE 60
WELDED WIRE FABRIC
ASTM A1064
PORTLAND CEMENT
ASTM C 150
FLYASH
ASTM C 618,15% MAX
CONCRETE AGGREGATES
ASTM C 33,314" MAX AGG. SIZE.
EPDXY- THREADED ROD ANCHORS
HILTIHIT -HY200 AOR SIMPSON SET XP
EPDXY- REINFORCING BARS
HILTIHIT -HY200 ROR SIMPSONSETXP
REBAR CONDITION
MINIMUM CONCRETE COVER
FORMED SURFACES EXPOSED TO
GROUND OR WEATHER
2
UNFORMED SURFACE IN CONTACT
WITH THE GROUND
3„
WALLSAND SLABS NOT EXPOSED
TO GROUND OR WEATHER
1„
INTERIOR BEAMS AND COLUMNS
(TO TIES OF STIRRUPS)
1 1/2"
CONCRETE MIX DESIGN
REQUIREMENTS
CONCRETE USE
WEIGHT
28 DAY
Fc
CEMENT
TYPE
MAX
WIC
RATIO
SLUMP
(+/-1")
% AIR
FOOTINGS
NW
3500 psi
1/11
1 0.55
5"
6% MAX
FOUNDATION WALLS
I NW
1 3500 psi
1 1/11
1 0.50
1 4"
1 6%+/-1%
WOOD MATERIAL SPECIFICATIONS
Q
MEMBERS
MATERIAL SPECIFICATION
JOIST, RAFTERS, HEADERS, BEAMS
No. 2 DF/L
TREATED LUMBER
No. 2 So. Pine
STUDS, BEARING WALL
No. 2 HEM -FIR
SILL AND TOP PLATES
No. 2 HEM -FIR
GLULAM BEAMS
DF/DF
SINGLE SPAN
24F -V4
MULTI SPAN
24F -V8
LAMINATED VENEER LUMBER, LVL
Fb = 2600 psi, E= 2.0 x 1OE6 psi
LAMINATED STRAND LUMBER, LSL
Fb = 1700 psi, E = 1.3 x 1OE6 psi
PARALLEL STRAND LUMBER, PSL
Fb = 1700 psi, E = 1.3 x 1OE6 psi
BOLTS AND THREADED RODS
ASTM A307 (MIN.)
NAIL SIZE REFERENCE
COMMON NAIL
BOX NAIL
SIZE
DIAMETER LENGTH
SIZE DIAMETER
LENGTH
8d
0.131" 2 1/2"
8d 0.113"
2 1/2"
10d
0.148" 3"
10d 0.128"
3"
16d
0.162" 31/2"
16d 0.135" 1
31/2'.
NOTES - ROUGH CARPENTRY
1. CONTRACTOR IS RESPONSIBLE TO ADEQUATELY SHORE AND BRACE ALL
FLOOR AND ROOF FRAMINGAND WALLS DURING CONSTRUCTION.
2. NAILING: SHALL BE PER FASTENING SCHEDULE OF THE INTERNATIONAL
BUILDING CODE. FOR PREFABRICATED CONNECTORS USE ALL FASTENERS
AS PRESCRIBED BYTHE MANUFACTURER.
3. ALL POST AND JAMBS ARE TO BE BLOCKED SOLID WITH THE SAME
NUMBER OF PIECES AS THE POST OR JAMB WITHIN THE FLOOR SPACE AND
CONTINUOUS TO THE FOUNDATION LEVEL. BLOCKING IS TO ALIGN WITH
POST OR JAMBS.
4. SPECIES AND GRADES SHOWN IN SCHEDULE ARE THE MINIMUM
ACCEPTABLE. BETTER GRADES MAY BE SUBSTITUTED.
5. PRESSURE TREATED WOOD TO BE USED WHEN EXPOSED TO WEATHER
OR IN CONTACT WITH CONCRETE OR MASONRY.
6. WOOD STRUCTURAL PANELS TO BE A.P.A. RATED AND EXPOSURE 1.
PANELS TO BE MANUFACTURED PER U.S. DEP. OF COMMERCE PRODUCT
STANDARDS PS1 OR PS2.
7. ANY FASTENERS OR CONNECTORS TO AND THROUGH TREATED WOOD
SHALL BE FASTENED WITH ASTM A153 CLASS D HOT DIP GALVANIZED OR
STAINLESS STEEL FASTENERS.
8. WOOD FRAMING WILL HAVE SHRINKAGE. THE CONTRACTOR SHALL
COORDINATE REQUIREMENTS TO ACCOMMODATE SHRINKAGE WITH OTHER
TRADES.
9. BORED HOLES FOR HORIZONTAL PLUMBING PIPING SHALL BE PROVIDED
WITH FLEXIBLE JOINTS TO PERMIT MOVEMENT.
10. RIGID ELECTRICAL CONDUIT INSTALLED VERTICALLY SHALL BE
PROVIDED WITH FLEXIBLE JOINTS TO PERMIT MOVEMENT.
11. ALL DIMENSIONAL LUMBER SHALL BE GRADE STAMPED WITH MOISTURE
CONTENT NOT TO EXCEED 19%.
12. INCISED STRUCTURAL LUMBER NOT PERMITTED WITHOUT THE PRIOR
WRITTEN APPROVAL OF THE STRUCTURAL ENGINEER.
13. DIMENSIONAL LUMBER SIZES SHOWN ON PLANS ARE NOMINAL
DIMENSIONS. DRESSED SIZES PUBLISHED IN THE LATEST EDITION OF
AMERICAN SOFTWOOD LUMBER PS20 SHALL BE ACCEPTED AS MINIMUM
NET SIZES CONFORMING TO SUCH NOMINAL SIZES.
14. WOOD HEADERS SHALL HAVE A FULL 3" LENGTH OF BEARING AT EACH
END UNO.
15. ALL BEAMS AND JOISTS NOT BEARING ON SUPPORTING MEMBERS
SHALL BE FRAMED WITH PREFABRICATED METAL JOIST HANGERS FOR
REQUIRED CAPACITY. ALL PREFABRICATED METAL HARDWARE IS BY
SIM PSON STRONG -TIE COMPANY OR APPROVED EQUIVALENT.
CONNECTIONS IN CONTACT WITH PRESSURE TREATED WOOD SHALL HAVE
G185 GALVANIZED COATING PER ASTM A653 AND HOT DIPPED GALVANIZED
FASTENERS PER ASTM A153. ALTERNATE CORROSION RESISTANT
CONNECTIONS IN ACCORDANCE WITH IBC WILL BE CONSIDERED. PRIOR
WRITTEN APPROVAL BYTHE STRUCTURAL ENGINEER OF RECORD IS
REQUIRED.
16. WALL, FLOOR, AND ROOF SHEATHING NAILS SHALL HAVE FULL HEADS.
CLIPPED NAILS ARE NOTALLOWED IN THESE APPLICATIONS.
17. NAIL TYPE USED IN WALL, FLOOR, AND ROOF WSP SHEATHING SHALL BE
COMMON OR GALVANIZED BOX NAILS. SINKER NAILS, COOLER NAILS, ETC
ARE NOT PERMITTED IN THESE APPLICATIONS.
18. ALL SIDE LOADED LVL BEAMS TO BE FASTENED TOGETHER PER
MANUFACTURER REQUIREMENTS.
19. ALL MULTI -PLY BEAMS TO BE SUPPORTED BY STUD PACK WITH ONE
ADDITIONAL STUD THAN BEAM PLY'S.
SYMBOLS / ABBREVIATIONS
SYMBOL/TAG
DESCRIPTION
APPLIES TO
9
DETAIL ON SHEET
DETAILS, SECTIONS,
SHEET NUMBER
OCCUPANCY CATEGORY
&ELEVATIONS
T=XXX'-XX"
ELEVATION (TOP)
FOOTINGS AND
BBQ
ELEVATION BOTTOM
FOUNDATION WALLS
INTERNAL PRESSURE COEFFICIENT, GC
+/-0.18
SPOT
T.O.X.LEVELS,
ELEVATION MARK
ELEVATIONS, & PLAN
XXX -
SLOPE FACTOR, Cs 0.79
ELEVATIONS
T.O.S. = XXX' -XX"
TOP OF STEEL
PLAN VIEW NOTATIONS
0
ELEVATION
JST BRG= XXX -XX"
JOIST BEARING
PLAN VIEW NOTATIONS
ELEVATION
QREVISION
MARK
SHEET REVISIONS
ABV DEFINITION ABV DEFINITION
AB ANCHOR BOLT SIM SIMILAR CONDITION
CJ CONTRACTION JOINT STD STANDARD
CL CENTERLINE TOC TOP OF CONCRETE
DIA DIAMETER TOD TOP OF DECK
EOD EDGE OF DECK ANGLE TOL TOP OF LEDGE
EOS EDGE OF SLAB TOM TOP OF MASONRY
EXT EXTERIOR TOS TOP OF STEEL
GA GAUGE TOW TOP OF WALL
HAS H EADED ANCHOR STUDS TYP TYPICALCONDITION
OC ON CENTER UNO UNLESS NOTED OTHERWISE
PAF I POWDER ACTUATED FASTNRj WP WORKPOINT
WOOD FRAMING PLAN SYMBOLS
SYMBOL
DESCRIPTION
CONCEALED FLANGE HANGER REF SCHEDULE
JOIST HANGER REF SCHEDULE
�
JOIST BEARING LOCATION
2x POST TO BE MIN. WIDTH OF MEMBER IT IS
SUPPORTING, UNO (POSTS SUPPORTING MULTI -PLY
L
LVL BEAMS TO HAVE ONE ADDITIONAL STUD THAN
BEAM PLYS)
2x POST DOWN TO HEADER, MUST BE MIN. WIDTH OF
MEMBER IT IS SUPPORTING, UNO
Q
POST ABOVE. FRAMER MUST ENSURE THAT POST
®
BEARS ON BEAM BELOW OR IS CONTINUOUS DOWN
U
TO THE FOUNDATION LEVEL.
BASE PLATE TAG
�
BASE PLATE CALLOUT
NN'
BOTTOM OF BASE PLATE
PLAN COLUMN ELEVATION
0Q
0
PLATE SHOWN FOR CENTERLINES OF COLUMN
ORIENTATION GRID/DIMENSION LINES
COLUMN TAG
\� e- -CAP PLATE CALLOUT
3
COLUMN SIZEO15+
5
CONNECTION DETAIL
PLAN COLUMN
CENTERLINES OF COLUMN
GRID/DIMENSION
ENSISI ON LINES
FRAMING SYSTEM TAG
L
DIRECTION OF
[
FRAMING MEMBER
mm
EXPANSE OF FRAMING
SYSTEM MARK
BEAM LEGEND
EVENLYSPACED
STIFFENERS
CAMBER SIZE -WEB
# OF COMPOSITE STUDS COMMENTS
BEAM SIZE �j j DETAIL
1 1 1
XXK Wi 6X36(16)C=1"[8]{NOTE} X/SXXX
T.O.S. 118'-0"
DO
TOP OF STEEL
CONNECTION ELEVATION
MOMENT CONNECTION
2/15/2021 4:19:34 PM
REQUIRED ENGINEER OF RECORD OBSERVATIONS
1. FOOTING/PIER FORM WORK AND REINFORCEMENT. -
2. CONCRETE WALL FORM WORK AND REINFORCEMENT. -
3. FINAL FRAMING.b
a. E.O.R REQUIRES 48 HOUR NOTICE PRIOR TO OBSERVATION.
OBSERVATION TO OCCUR WHEN MAJORITY OF FORM WORK AND
REINFORCEMENT IS IN PLACE AND NO MORE THAN 24 HOURS BEFORE
CONCRETE POUR.
b. E.O.R. TO SIGN OFF ON ALL FRAMING PRIOR TO WRITING REPORT OF
COMPLETION FOR CERTIFICATION OF OCCUPANCY. G.C. TO INSTALL ALL
MEMBERS NOTED ON PLANS AND HAVE ALL CONNECTION AND
SUPPLEMENTAL HARDWARE INSTALLED PRIOR TO FINAL FRAMING
OBSERVATION UNLES PREVIOUSLY OBSERVED AND SIGNED OFF ON BY
E.O.R.
DESIGN INFORMATION
BUILDING CODE:
2018 INTERNATIONAL RESIDENTIAL CODE AS ADOPTED AND/OR
AMENDED BY LOCAL BUILDING CODES
SOILS INFORMATION:
THE FOUNDATION DESIGN PROVIDED IS BASED OFF OFA MINIMUM
ALLOWABLE PRESUMPTIVE LOAD-BEARING VALUE AS INDICATED BY IRC
TABLE R401.4.1 IN LIEU OF A SITE BASE GEOTECHNICAL EVALUATION. IT IS
RECOMMENDED THAT A QUALIFIED GEOTECHNICAL ENGINEER BE
RETAINED TO VERIFYTH ESE ASSUMPTIONS PRIOR TO CONSTRUCTION. BY
USE OF THIS FOUNDATION DESIGN WITHOUT PROVIDING SUCH
VERIFICATION, APEX WILL NOT BE LIABLE FOR THIS DESIGN PARAMETER,
AND THE OWNER SHALL ACCEPT ALL RISKS ASSOCIATED WITH DAMAGE T
THE STRUCTURE AS A RESULT OF EXPANSIVE, COMPRESSIBLE, SHIFTING
AND/OR OTHER QUESTIONABLE SOILS CHARACTERISTICS THAT MAYBE
PRESENT ON-SITE.
FROST DEPTH 36"
PRESUMPTIVE LOAD-BEARING PRESSURE 1500 psf
WIND DESIGN DATA: Main Building
OCCUPANCY CATEGORY
II
ULTIMATE WIND SPEED (3 SECOND GUST), V
135 mph
WIND EXPOSURE CATEGORY
C
VELOCITY PRESSURE, c,
23.0 psi
INTERNAL PRESSURE COEFFICIENT, GC
+/-0.18
ROOF SNOW LOAD DATA: Main Building
GROUND SNOW LOAD, P, 30 psi
SNOW LOAD IMPORTANCE FACTOR, k 1.00
SNOW EXPOSURE FACTOR, C¢ 1.00
THERMALFACTOR, G 1.00
SLOPE FACTOR, Cs 0.79
ROOF SNOW LOAD, Pr 30 psf
SHEET LIST - STRUCTURAL
SHEET NUMBERSHEET NAIVE
5100 GENERAL NOTES AND SPECIFICATIONS
S200 IFOUNDATION & FRAMING PLAN
S400 WALL SECTIONS
.�O Wheaj
O 011 W
BG xoc,
dIng pMs
APEX
ENGINEERS,INC.
2701 LAWRENCE ST. UNIT 19
DENVER, CO 80205
720.588.3222
w .apex-engineem.com
PROJECT #: 40273
DRAWN BY: DCS
CHECKED BY: Jared Lambrechl, P.E.
SUBMITTAL DATE. 2152021
U)
c+�
F
c+�
Lu
0
W
Y
O
O
O
�
QN
L
U)
Q
W
U
W
N
�
N [If
F
W
EE
[if
z
U
[
Q
LU
LLI
L
[
W
mm
J
U
O-
DO
2/15/2021 4:19:34 PM
PROJECT #: 40273
DRAWN BY: DCS
CHECKED BY: Jared Lambrechl, P.E.
SUBMITTAL DATE. 2152021
U)
F
Lu
W
O
U
W
F
Q
2/15/2021 4:19:34 PM
SHEET:
GENERAL NOTES AND
SPECIFICATIONS
S100
All work shall comply with the 2018 IRC, 2020
NEC and City Municipal Codes.
� VJ heat
� Ra
U m
SCHEDULE -WOOD HANGER
FACE MOUNT TOP FLANGE CONCEALED
BEAM HANGER HANGER HANGER
2x10 LUS210 LB210AZ N/A
(3) 1 3/4"x71/4" LVL HU68 WPU5.5017.25 HUC68
(2)2x6 LUS26-2 HUS26-2TF HUC26-2
NOTES:
1. ALL HANGERS ARE SIMPSON PRODUCTS UNO.
2. ALL EXTERIOR HANGERS TO BE ZMAX OR GALVANIZED.
3. INSTALL ALL HANGERS PER MANUFACTURERS RECOMMENDATIONS.
4. USE SCHEDULE LINO ON PLAN.
ROOF FRAMING PLAN
1/4" = V-0"
IFYALL
9ARCH
Ems
SCHEDULE - PAD FOOTING
MARK I LENGTH I WIDTH DEPTH REINFORCING
F1 1 2' - 0" 1 2' - 0" 0' - 10" (3) #4 EA. WAY
PLAN NOTES -FOUNDATIONS
1. PROVIDE CONTROL JOINTS (1/4 SLAB DEPTH) AT 10'-0" OC BOTH WAYS,
NOT SHOWN FOR CLARITY.
2. CONTRACTOR TO VERI BY ALL FOUNDATION ELEVATIONS AND STEPS PER
SITE CONDITIONS.
3. TOP OF SLAB ELEVATION SHOWN IN PLAN IS FOR REFERENCE ONLY.
4. REFERENCE ARCHITECTURAL DRAWINGS FOR WALL OPENING
DIMENSIONS, EXTERIOR FINISHES AND ADDITIONAL NOTES.
5. REFERENCE GENERAL NOTES SHEET FOR ADDITIONAL FOUNDATION
SPECIFICATIONS.
6. CONTRACTOR TO CONTACTAPEX ENGINEERS, INC AT LEAST48 HRS IN
ADVANCE OF ANYCONCRETE POUR.
G.C. TO FIELD VERIFYALL
DIMENSIONS WITH ARCH
30'-0 1/8"
17'-10 3/8" 12'-1 3/4"
— — — — — -'-- — — — — — — — — — — — — — — — --------------
------------- ,
0
I
I
I
I�
-------------
I I I
N
CHECKED BY: Jared Lambrechl, P.E.
iof.=b.4•
_TOCP-% 10 BOF b' -C'
I
Ie..
I
c+�
m
I
m
4"SLAB ON RE: ARCH FOR SLOPE I
GRADE RE: ARCH AND FINISH REOM'S
F1 OF 6
B 0 Fes' -C'
�
o I
-
I I
LPBP.=9B-10'
I
O_
FOUNDATION WALL PLAN
1/4" = 1'-0"
11'-10 7/8"
I m
I
— ABU66Z POST BASE
TYPICAL
I
C0 �4.
B 0F,%' -C'
I
------------� M
24'-0 5/8"
0 11
8" WIDE x 12" DEEP EDGE
BEAM W/#4 CONT BAR TOP
AND BOTTOM
12'-1 3/4"
APEX
ENGINEERS,INC.
2701 LAWRENCE ST. UNIT 19
DENVER, CO 80205
720.588.3222
W W W.apex-en gin eem.com
PROJECT #: 40273
DRAWN BY: DCS
CHECKED BY: Jared Lambrechl, P.E.
SUBMITTAL DATE 2152021
c+�
c+�
F
�
o
O_
O
<
d
_
U)
_
U) W
L
m
UQ
w
W
O
W�
LU
S
[if
z
U
[
LU
U
O
O L
�
w
J
U
LU
D_
m
/
PROJECT #: 40273
DRAWN BY: DCS
CHECKED BY: Jared Lambrechl, P.E.
SUBMITTAL DATE 2152021
F
LU
LU
O
U
LU
0
u
2/15/2021 4:19:34 PM
SHEET:
FOUNDATION & FRAMING
PLAN
S200
All work shall comply with the 2018 IRC,
2020 NEC and City Municipal Codes.
,jkT.O.1ST FLR PL
108'- 0 7/8"
RE: ARCH FOR
RAFTER TAIL
AND FASCIA
RE: ARCH FOR BEAM WRAP
#4x ry LAT 24"o.c.
2 0
jj4T.O. 1ST FLR PLY — — —
00' - 0"
T.O.PILASTER 98'-10" — —
(4)#5 DOWELS, (1)
IN EA CORNER
T.O.F. —w
96' 4" — U
y
Lu
K
RE: SCHED
ROOF RAFTERS
RE: PLAN
5/8" APA RATED ROOF
SHEATHING
/ H2.5TCLIPAT
EACH RAFTER
/q^ CEILING JOISTS
RE: PLAN
POST CAP
RE: PLAN
WOOD COLUMN
RE: PLAN
2x6 AT 16" o.c.
KNEE WALL
OVER WALL
BELOW
(E) OPENING
RE: ARCH —
2 PATIO SECTION
S400 1/2" = 1'-0"
SIMPSON ViCR CLIP
FROM EACH RAFTER
TO ROOF STRUCTURE
BELOW
2x6 AT 16" o.c.
KNEE WALL
OVER WALL
BELOW �
(E) OPENING
RE: ARCH —
BASE
4" SLAB ON GRADE
/POST
RE: PLAN
SUBMITTAL DATE 2152021
RE: ARCH FOR EXTENTS
c+�
AND FINISH REAM'S
WELDED WIRE FABRIC
SQUARE OR ROUND
REFER TO PLAN
PILASTER RE: PLAN
NOTES
#3 TIES AT 12" o.c. WITH
(3) AT TOP
FTG REINF _
_ _ _ _ _ _
RE: SCHEDULE
11 PATIO SECTION
S 400 1 1/2" = V-0"
FLUSH HEADER
OVER WINDOW.
POST DOWN TO
KING AND TRIMMER
STUDS BELOW
108'-0 7/8" FIELD VERIFY
108'-0 7/8" FIELD VERIFY .
VERIFY(E) HEADER
OR INSTALL (N)
HEADERAS
INDICATED ON PLAN
APEX
ENGINEERS,INC.
2701 LAWRENCE ST. UNIT 19
DENVER, CO 80205
720.588.3222
w .apex-engineem.com
PROJECT #: 40273
DRAWN BY: DCS
CHECKED BY: Jared Lambrecht, P.E.
SUBMITTAL DATE 2152021
c+�
c+�
0
z
W
Y
O
O
H
�
d
U
U) W
O
L
m
UQ
W
N
U
N D-'
W
S
[if
z
U
[
LU
L
�LLI
W
M
J
U
0-
Q
m
PROJECT #: 40273
DRAWN BY: DCS
CHECKED BY: Jared Lambrecht, P.E.
SUBMITTAL DATE 2152021
F
z
W
O
U
W
Q
2/15/2021 4:19:35 PM
SHEET:
WALL SECTIONS
S400
For Berry
Here are the required bnnsto complete the permit approval, per youremall below.
Pleaseletmeknowlt you need any atltlttlonal Info
Sincerely,
GW
From: Cemmoev Permit Imadho PermlesPdwheat idea .m.us]
Bent: Tuesday, June 08, 26213'.66 Go
To: Gary Wagner
6e: Commoev Permit
Subject RE'. Online Form Submtttal'. Addition to Existing Building
Good afternoon,
Your plan review is approved and final steps are all that IS left We will need to collect final tees
totaling $93620 torthe permit tee. I have attached a new payment authorization form for you to
complete and email back overto us We will also need to obtain your contractor information Or the
protect. If there will be an y electrical/mechanical/plumbing with this scope of work, a subcontractor
form Or that scope of work will need to be provided back over to usaswell . If you will be
cempletlngthe work yourself, you will need to complete a homeowner notarized form for usto
name yourself as the contractor of record
I have attached all files described above and a breakdown of fees below. Please let us know If
you have an y questions about them porous We are here to help.
There you and be sabot
Justin Bary
Building Division
OfficeFhooe 303-235-2855
Office Hours: rant
RD!Enw
Cp rMwlLrlge
From: not apt VS) d ATeattldge couarno replVS) d. AT eattldge co ua>
TO
wo up., Park
no. I Russ on to D
Mach.e.r..
21 of
4 21
KRIECAMNER
0 REED ST
.LEeONTnAshatt 0ROAT.enFARM 2830REEDST 0a,<,°of
For Berry
Here are the required bnnsto complete the permit approval, per youremall below.
Pleaseletmeknowlt you need any atltlttlonal Info
Sincerely,
GW
From: Cemmoev Permit Imadho PermlesPdwheat idea .m.us]
Bent: Tuesday, June 08, 26213'.66 Go
To: Gary Wagner
6e: Commoev Permit
Subject RE'. Online Form Submtttal'. Addition to Existing Building
Good afternoon,
Your plan review is approved and final steps are all that IS left We will need to collect final tees
totaling $93620 torthe permit tee. I have attached a new payment authorization form for you to
complete and email back overto us We will also need to obtain your contractor information Or the
protect. If there will be an y electrical/mechanical/plumbing with this scope of work, a subcontractor
form Or that scope of work will need to be provided back over to usaswell . If you will be
cempletlngthe work yourself, you will need to complete a homeowner notarized form for usto
name yourself as the contractor of record
I have attached all files described above and a breakdown of fees below. Please let us know If
you have an y questions about them porous We are here to help.
There you and be sabot
Justin Bary
Building Division
OfficeFhooe 303-235-2855
Office Hours: rant
RD!Enw
Cp rMwlLrlge
From: not apt VS) d ATeattldge couarno replVS) d. AT eattldge co ua>
Sent: Thursday, May 6, 20211:43 PM
To: CommDev Permits <Permits@ci.wheatridge.co.us>
Subject: Online Form Submittal: Addition to Existing Building
Addition to Existing Building
THIS APPLICATION DOES NOT CONSTITUTE A PERMIT. DO NOT BEGIN
WORK UNTIL PERMIT HAS BEEN ISSUED.
Is this Residential or
Residential - upload Proof of Submission to Sanitation District
Commercial?
and Water District
Upload Proof of Submission
Field not completed.
to Sanitation Department
Upload Proof of Submission
Field not completed.
to Water Department
PROPERTY INFORMATION
Property Address
2830 REED ST.
Property Owner Name
Gary E. Wegher / Celeste R. Lucero
Property Owner Phone
303-587-2322
Number (enter WITH
dashes, eg 303-123-4567)
Property Owner Email
aweaherObalance-architecture.com
Address
Attach City of Wheat Ridge
ELECTRONIC PAYMENT FORM - 2830 REED ST -
Electronic Payment Form -
05.06.21.Ddf
**DO NOT ATTACH A
PICTURE OF A CREDIT
CARD**
APPLICANT INFORMATION
Applicant Name
Gary E. Wegher
What is your role in the
Property Owner
project?
Contact Phone Number
303-587-2322
(enter WITH dashes, eg
303-123-4567)
Contact Email Address for aweaher()balance-architecture.com
Plan Review Comments
Retype Contact Email
Address
DESCRIPTION OF WORK
Detailed Scope of Work -
Provide use of addition (i.e.
master bedroom with
master bathroom); Indicate
mechanical, electrical,
plumbing scopes
Location of Work
new patio slab and covered roof
rear of home off dining/kitchen area
Square Footage of Addition 435
Asbestos Report ASBESTOS INSPECTION REPORT - 2830 REED ST. -
05 0621 Ddf
Engineering Letters, Energy STRUCTURAL CALCULATIONS - 2830 REED ST -
Calcs and Other Letter Size 05.06.21. Ddf
Attachments
Construction Plans scanned CONSTRUCTION DOCUMENT SET - 2830 REED ST. -
on 11'x17" or larger 05 0621 Ddf
Provide Passcode for Plans
if locked
Project Value (contract
value or cost of ALL
materials and labor)
Field not completed.
24,000
SIGNATURE OF UNDERSTANDING AND AGREEMENT
I assume full responsibility Yes
for compliance with
applicable City of Wheat
Ridge codes and ordinances
for work under any permit
issued based on this
application.
I understand that work may Yes
not begin on this property
until a permit has been
issued and posted on the
property.
I certify that I have been Yes
authorized by the legal
owner of the property to
submit this application and
to perform the work
described above.
Person Applying for Permit Gary E. Wegher
I attest that everything Yes
stated in this application is
true and correct and that
falsifying information in this
application is an act of
fraud and may be
punishable by fine,
imprisonment, or both.
Email not displaying correctly? View it in your browser.
� ► � i City of Wheat Ridge
Residential Addition PERMIT - 202100913
PERMIT NO: 202100913 ISSUED: 09/07/2021
JOB ADDRESS: 2830 Reed St EXPIRES: 09/07/2022
JOB DESCRIPTION: new patio slab and covered roof, rear of home off dining/kitchen area, 435
sq ft
*** CONTACTS ***
OWNER ( 3 0 3) 5 8 7- 2 3 2 2
WEGHER GARY
SUB (303)278-4044
LOUIS KARSTEN
022118 KARSTEN
ELECTRICAL SERVICES, L
*** PARCEL INFO ***
ZONE CODE:
UA / Unassigned
USE:
UA / Unassigned
SUBDIVISION CODE:
2405 / BARTHS,
COULEHAN GRANGE, WHEAT BLOCK/LOT#:
0 /
*** FEE SUMMARY ***
ESTIMATED PROJECT VALUATION:
24,000.00
FEES
Total Valuation
0.00
Plan Review Fee
277.03
Use Tax
504.00
Permit Fee
426.20
** TOTAL **
11207.23
*** COMMENTS ***
*** CONDITIONS ***
All roughs to be done at Framing Inspection.
A printed copy of the permit and city stamped on-site plans must be available on-site for
the first inspection.
Approved per plans and red -line notes on plans. Must comply with 2018 IRC, 2020 NEC and all
applicable City of Wheat Ridge Municipal Codes. Work is subject to field inspections.
Owner/Contractor is responsible for locating property lines and constructing improvements
according to the approved plan and required development standards. The City is not
responsible for inaccurate information submitted within the plan set and any construction
errors resulting from inaccurate information.
For one- or two-family dwellings, the first twenty-five feet (25') of driveway area
from the existing edge of pavement into the site shall be surfaced with concrete, asphalt,
brick pavers or similar materials. A right-of-way permit may be required; contact Public
Works Department at 303-235-2861.
In addition, no less than twenty-five percent (250) of the gross lot area and no less than
one hundred percent (1000) of the front yard shall be landscaped.
1* � 4 41'
PERMIT NO:
JOB ADDRESS:
JOB DESCRIPTION:
City of Wheat Ridge
Residential Addition PERMIT - 202100913
202100913 ISSUED: 09/07/2021
2830 Reed St EXPIRES: 09/07/2022
new patio slab and covered roof, rear of home off dining/kitchen area, 435
sq ft
I, by my signature, do hereby attest that the work to be performed shall comply with all accompanying approved plans and specifications,
applicable building codes, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized
by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with
this�permrt. I further attest that I am leg ally authorized to include all entities named within this document as parties to the work to be
performed and that all work to be performed is disclosed in this document and/or its' accompanying approved plans and specifications.
Signature of OWNER or CONTRACTOR (Circle one) Date
1, This permit was issued based on the information provided in the permit application and accompanying plans and specifications and is
subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures.
2. This.permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and
received prior to the date of expiration. An extension of no more than 180, days made be granted at the discretion of the Chief Building
Official and may be subject to a fee equal to one-half of the original permit fee.
3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard
requirements, fees and��procedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of
the Chief Building Official and is not guaranteed.
4. No work of any manner shall be performed that shall results in a change of the natural flow of water without prior and specific approval.
5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all requ�ired
inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services
Division.
6. The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, anviolation of any provision of any
�pplicabje code or any ordinance or regulation of this jurisdiction. Approval of work is subject to field inspection.
09/07/2021
Signature of Chief Building Official Date
REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY.
From: no-reolv(alci.wheatridae.m. us
To: CommDev Perm is
Subject: Online Form Submittal: Addition to Existing Building
Date: Thursday, May 6, 2021 1:42:52 PM
Addition to Existing Building
THIS APPLICATION DOES NOT CONSTITUTE A PERMIT. DO NOT BEGIN
WORK UNTIL PERMIT HAS BEEN ISSUED.
Is this Residential or
Residential - upload Proof of Submission to Sanitation District
Commercial?
and Water District
Upload Proof of
Field not completed.
Submission to
Sanitation Department
Upload Proof of
Field not completed.
Submission to Water
Department
PROPERTY INFORMATION
Property Address
2830 REED ST.
Property Owner Name
Gary E. Wegher / Celeste R. Lucero
Property Owner Phone
303-587-2322
Number (enter WITH
dashes, eg 303-123-
4567)
Property Owner Email
gwegher@balance-architecture.com
Address
Attach City of Wheat
ELECTRONIC PAYMENT FORM - 2830 REED ST -
Ridge Electronic
05 0621 Ddf
Payment Form - "DO
NOT ATTACH A
PICTURE OF A
CREDIT CARD"
APPLICANT INFORMATION
Applicant Name
Gary E. Wegher
What is your role in the
Property Owner
project?
Contact Phone Number 303-587-2322
(enter WITH dashes,
eg 303-123-4567)
Contact Email Address gwegher@balance-architecture.com
for Plan Review
Comments
Retype Contact Email
Address
DESCRIPTION OF WORK
Detailed Scope of
Work - Provide use of
addition (i.e. master
bedroom with master
bathroom); Indicate
mechanical, electrical,
plumbing scopes
gwegher@balance-architecture.com
new patio slab and covered roof
Location of Work rear of home off dining/kitchen area
Square Footage of 435
Addition
Asbestos Report
Engineering Letters,
Energy Calcs and
Other Letter Size
Attachments
Construction Plans
scanned on 11'x17" or
larger
Provide Passcode for
Plans if locked
Project Value (contract
value or cost of ALL
materials and labor)
STRUCTURAL CALCULATIONS - 2830 REED ST. -
05.06.21. Ddf
Field not completed.
24,000
SIGNATURE OF UNDERSTANDING AND AGREEMENT
I assume full Yes
responsibility for
compliance with
applicable City of
Wheat Ridge codes
and ordinances for
work under any permit
issued based on this
application.
I understand that work Yes
may not begin on this
property until a permit
has been issued and
posted on the property.
I certify that I have Yes
been authorized by the
legal owner of the
property to submit this
application and to
perform the work
described above.
Person Applying for Gary E. Wegher
Permit
I attest that everything Yes
stated in this
application is true and
correct and that
falsifying information in
this application is an
act of fraud and may
be punishable by fine,
imprisonment, or both.
Email not displaying correctly? View it in your browser.
i CITY OF WHEAT RIDGE
_:�9�Building Inspection Division
(303) 234-5933 Inspection line
(303) 235-2855 Office • (303) 237-8929 Fax
INSPECTION NOTICE
Inspection Type: �- �' . A V- 0 (1 :
Job Address: -2 Cl y- e < c sA
Permit Number: 00 1C-� G O `� -1 1
❑ No one available for inspection: Time AM/PM
Re -Inspection required: Yes No
When corrections have been made, call for re -inspection at 303-234-5933
Date: -c --S H \ Ct Inspector: �-
DO NOT REMOVE THIS NOTICE
t
i CITY OF WHEAT RIDGE
Building Inspection Division
(303) 234-5933 Inspection line
(303) 235-2855 Office • (303) 237-8929 Fax
INSPECTION NOTICE
Inspection Type: Yn k 0 UL F
Job Address: c 'r c.l s.
Permit Number: o c7 O U
❑ No one available for inspection: Time I `' AM/PM
Re -Inspection required: Yes No
When corrections have been made, call for re -inspection at 303 -234 -
Date: �= i Inspector:
DO NOT REMOVE THIS NOTICE
City of Wheat Ridge
Residential Roofing PERMIT - 201900577
PERMIT NO: 201900577 ISSUED: 04/02/2019
JOB ADDRESS: 2830 Reed St EXPIRES: 04/01/2020
JOB DESCRIPTION: Residential re -roof and re -deck with asphalt shingles. Squares: 25.33;
Pitch: 4/12.
*** CONTACTS ***
OWNER (303)465-4215
SUB (303)472-3655
WEGHER GARY
DANIEL MONTEZ
090249 TEAM CONSTRUCTION SERVICES INC
*** PARCEL INFO ***
ZONE CODE:
UA / Unassigned
USE: UA / Unassigned
SUBDIVISION CODE:
2405 / BARTHS,
COULEHAN GRANGE,
WHEAT BLOCK/LOT#: 0 /
*** FEE SUMMARY ***
ESTIMATED PROJECT VALUATION: 20,194.00
FEES
Total Valuation
0.00
Use Tax
424.07
Permit Fee
378.65
** TOTAL **
802.72
*** COMMENTS ***
*** CONDITIONS ***
Midroof & Final Roof inspections for ROOFS 6/12 PITCH & OVER: 3rd party inspection will be
required for both the midroof and final inspections. The 3rd party inspection report AND
THE ORIGINAL PERMIT CARD needs to be dropped off to the Permit Desk at the City of Wheat
Ridge. The report MUST BE SIGNED by the Homeowner.
REGARDING ROOF VENTILATION: Roof ventilation shall comply with IBC Sec. 1203.2 or IRC Sec.
R806. The installation of ridge venting requires the installation or existence of soffit
venting. For calculation purposes, one hat or turtle vent equal to one-half of one square
foot of opening.
Effective December 1, 2014, asphalt shingle installations require an approved midroof
inspection, conducted when 25-75% of the roof covering is installed, prior to final
approval. Installation of roof sheathing (new or overlay) is required on the entire roof
when spaced or board sheathing with ANY gap exceeding one half inch exists. Sheathing and
mid -roofs may be called in at the same time, one hundred percent of the sheathing must be
complete and 25-75% of the mid -roof may be complete. Asphalt shingles are required to be
fastened to the roof deck with a minimum of 6 nails per shingle. Ice and water shield is
required. Eave and rake metal is required. A ladder extending 3 feet above the roof eave
and secured in place is required to be provided for all roof inspections. Roof ventilation
is required to comply with applicable codes and/or manufacturer installation instructions,
whichever is more stringent. In order to pass a final inspection of elastomeric or similar
type roof coverings, a letter of inspection and approval from the manufacturer technical
representative stating that "the application of the roof at (project address) has been
applied in accordance with the installation instruction for (roof material brand name) roof
covering" is required to be on site at the time of final inspection.
'Alw- Ago -
PERMIT NO:
JOB ADDRESS:
JOB DESCRIPTION:
City of Wheat Ridge
Residential Roofing PERMIT - 201900577
201900577
2830 Reed St
ISSUED: 04/02/2019
EXPIRES: 04/01/2020
Residential re -roof and re -deck with asphalt shingles. Squares: 25.33;
Pitch: 4/12.
1, by my signature, do hereby attest that the work to be performed shall comply with all accompanying approved plans and specifications;
applicable building codes, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized
by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with
this er n - I further attest that I am legally authorized to include alt entities named within this document as partes to the work to be
performed and that all work to be performed is disclosed in this document and/or its' accompanying approved plans and specifications.
Signature of OWNER or CONTRACTOR (Circle one) Date
1. This permit was issued based on the information provided in the permit application and accompanying plans and specifications and is
subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures.
2. This. permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and
received prior to the date of expiration. An extension of no more than 180.days made be granted at the discretion of the Chief Building
Official and may be subject to a fee equal to one-half of the original pennit fee.
3, If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard
requirements, fees androcedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of
the Chief Building Official and is not guaranteed.
4, No work of any manner shall be performed that shall results in a changeof the natural flow of water without prior and specific approval.
5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all required
inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services
Divis'�p
5, The iss4ance or gran ± '' of a permit shall not be construed to be a permit for, or an approval of, any violation of any provision of any
app w. e , de ora ordinance or regulation of this jurisdiction. Approval of work is subject to field inspection.
Signature of Chief Building Official Date
REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY.
Dina Kemp
From: no-reply@ci.wheatridge.co.us
Sent: Tuesday, April 2, 2019 9:49 AM
To: CommDev Permits
Subject: Online Form Submittal: Residential Roofing Permit Application
Categories: Dina
Residential Roofing Permit Application
This application is exclusively for new RESIDENTIAL roofing permits and for
licensed contractors only. Permits are processed and issued in the order they are
received. You will be notified if your contractor's license or insurance has
expired. The license and insurance must be current before the permit will be
processed.
For all other requests:
Homeowners wishing to obtain a roofing permit must apply for the permit in
person at City Hall. Revisions to existing permits (for example, to add
redecking) must be completed in person at City Hall. The Building Division
permit counter is open from 7:30 am to 3:30 pm, Monday through Friday to
process these types of requests.
THIS APPLICATION DOES NOT CONSTITUTE A PERMIT. DO NOT BEGIN
REROOFING UNTIL PERMIT HAS BEEN ISSUED.
Is this application for a Yes
RESIDENTIAL reroof
permit?
How many dwelling units Single Family Home
are on the property?
PROPERTY INFORMATI72830
Property Address Rid Street, Wheat Ridge, CO 80033
Property Owner Name Gary Wegher
Property Owner Phone
Number (enter WITH
dashes, eg 303-123-4567)
Property Owner Email
Address
303-465-4215
gwegher@balance-architecture.com
Do you have a signed Yes
contract to reroof this
property?
CONTRACTOR INFORMATION
Contractor Business Team Construction Services
Name
Contractor's License 90249
Number
Contractor Phone 303-472-3655
Number (enter WITH
dashes, eg 303-123-4567)
Contractor Email Address dan@teamroofs.com
Retype Contractor Email dan@teamroofs.com
Address
Credit Card Authorization Team Credit -Card -Authorization -Form - Wegher.pdf
Form
DESCRIPTION OF WORK
TOTAL SQUARES of 25.33
the entire scope of work:
Project Value (contract 20194
value or cost of ALL
materials and labor)
Are you re -decking the Yes '
roof? L/'
Is the permit for a flat Pitched roof (2:12 pitch or greater)
roof, pitched roof, or
both? (check all that
apply)
What is the specific pitch 4/12 ✓
of the PITCHED roof?
How many squares are 25.33
part of the PITCHED
roof9
Describe the roofing Asphalt Shingles
materials for the
PITCHED roof:
Type of material for the Asphalt
PITCHED roof:
Provide any additional Roof tear -off, redeck, and reroof.
detail here on the
description of work. (Is
this for a house or
garage? Etc)
SIGNATURE OF UNDERSTANDING AND AGREEMENT
I assume full Yes
responsibility for
compliance with
applicable City of Wheat
Ridge codes and
ordinances for work
under any permit
issued based on this
application.
I understand that this Yes
application is NOT a
permit. I understand I will
be contacted by the City
to pay for and pick up the
permit for this property.
I understand that work Yes
may not begin on this
property until a permit
has been issued and
posted on the property.
I certify that I have been Yes
authorized by the legal
owner of the property to
submit this application
and to perform the work
described above.
I attest that everything Yes
stated in this application
is true and correct and
that falsifying
information in this
application is an act of
fraud and may be
punishable by fine,
imprisonment, or both.
3
Person Applying for Dan Montez
Permit
Email not displaying correctly? View it in your browser.
` DEP`ARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number : 13429
BUILDING INSPECTION LINE - 303-234-5933 Date : 2/15/02
CITY OF WHEAT RIDGE
7500 WEST 29TH AVENUE
WHEAT RIDGE, CO 80215 - (303-235-2855)
Property Owner:
Property Address : 2830 REED ST
Contractor License No. : 21176
Phone : 303-465-4215
Company : TYN-MAN ELECTRIC, INC. Phone : 303-810-7087
OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT
I hereby certify that the setback distances proposed by this permit application are accurate, and
do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or
covenants, easements or restrictions of record; that all measurements shown, and allegations
made are accurete; that I have read and agree to abide by all conditions printetl on this
application, and that I assume full responsibility for compliance with the Wheat Ridge Building
Code (U.B.C.) and all other applicable Wheat Ridge ances for work under this per it.
(OWNER)(CONTRACTOR) SIGNED DATE '9 Oa
Description : REMOVE SUB PANEL, WIRE FOR NEW CIRCUITS
Construction Value :
$1,200.00
Permit Fee
$44.85
Plan Review Fee :
$0.00
Use Tax :
$18.00
Total
$62.85
Use:
BUILDING DEPARTMENT USE ONLY !
SIC Sq Ft
Approval :
Zoning :
" 4, ~ *1°
Approval:
'"c'a.. ~Cl~so'.w`~iY~ q mP~~
Approval :
Occupancy : Walls : Roof : Stories : Residential Units :
Electrical License No :
Company :
Expiration Date :
Approval:
Plumbing License No :
Company :
Expiration Date :
Approval :
Mechanical License No :
Company :
Expiration Date :
Approval:
(1) This permit was issued in accordance with the provisions set forth in yopur application and is subject lo the laws of the State oF Coloratlo antl to the Zoning
Regulations and Building Code of Wheat Ritl9e, Colorado or any olher applicable ordinances of the City.
(2) This permit shall expire if (A) the work authorized is not commencetl within sixty (60) tlays fmm issue tlate or (B) the building authorizetl is suspentled or
abandoned for a period of 120 days.
(3) If this permil expires, a new permit may be acquired for a fee of one-half the amount normally reqwred. prowtletl no changes have been or win be made in me
orlginel plans and specifcations and any suspension or abantlonment has not exceetled one 11) year If changes are matle or dsuspenson oaoanoonme-r.
ezceeds one (1) year, full fees shall he paid for a new permit.
(4) No work of any manner shall be done that will change the natural Flow of wafer causin9 a drainage problem.
(5) Contractor shall notify the Building Inspector hventy-FOUr (24) hours in atlvance for all inspections and shall recerve written approval on inspection card before
proceetliing with successive phases of the job.
(6) The issuance of a permit or the approval of drawings and specificalions shall not be construed to be a permit for, nor an approval of, any violation of the
provisions of the building codes or any other ordinance, law, mle or regula[ion.
Chief Building Inspector
DEPARTMENT OF PLANNIlVG AND DEVELOPMENT
F W~E`° T BUILDING INSPECTION LINE - 303-234-5933
CITY OF WHEAT RIDGE
7500 WEST 29TH AVENUE
WHEAT RIDGE, CO 80215 - (303-235-2855)
cOLORA~~
~~~UCATp
i ON
Buitding Permit Nuinber:
Date:
PropertyOwner: EL£ST L V~C£iPD
Property Address: ~830 5-F,-
Contractor License No.: 81 1 7 (n
Phone : 416S 4a /5
Company: -Il'N-v''iAti f.LfC"i2)C, Phone: 3o3-910-7087
OWNER/CONTRACTOR SIGNA'I'[1RE OF LINDERS'CANDING AND AGREEhIENT
I hereby certify tha[ [he setback distances pmposed by [his pemit applica[ion are accurate,
and do no[violate applicable ordinances, rules or regula[ions of the City of Wheat Ridge or
covenants, euemenGS or resttictions ofrecord; Iha[ aIl meuurements shown, azid allegations
made aze accura[e; tha[ I have read and agree to abide 6y all condi[ions printed on this
application and that I assume fiill responsibility for compliance with the Wheat Ridoe
Building Code (U.B.C) and all other applicable Wheat Ri4ge Ordinances, for work under
this permit. /
(OWNER)(CONTRAGTOR):SIGNED ~PZUA7E
Description: (_,;pL rpp ,vFw C112CJIT-5
vV k'.uac ~ ,Qfa'YloUL 3u 3 ~~Ftn~t<:._
Construction Value:$ /r700°~
Permit Fee:$
Plan Review Fee:$
Use fax:$
TOt&1:$
i N 't-"TCr/CN
I , Z~ NN'N4 '2^ &&~
BUILDING DEPARTMENT USE ONLY
. SIC: Sq.Ft.:
ZONING COMMENTS: -
Approval:
Zoning:
BUILOING COMMENTS:
Approval:
PUBLIC WORKS COMMENTS:
Approval:
Occupancy: Walls: Roof: Stories: Residential Units:
Electrical License No: Plumbing License No: Mechanical License No:
Company: Company: Company:
Expuation Date: Expiration Date: Expiration Date:
Approval: Approval: Approval:
(l) 'ILis pennit was issued in accordance with the provisions se[ forth in yoiv applicatlon and is subject to [he laws of the Scate of Colorado and m the Zoning
Regidations and Bwlding Codes of Wheat Ridge, Colorado or any other applicable ordinances of Ne City.
(2) This pemit shall exp've if (A) the work anthorized is not commeviced witliin sixty (60) days Gom issoe date or (B) the building anthonzed is suspended or
abandoned for a pedod of 120 days.
(3) If tlils pemit exp'ues, a vew pemit may be acquired for a fce of one-half the amount normaliy reqnired, pmvided no changes have been ar will be made in
Ihe original plans and specif ca[ions avd any suspension or abandonment has mt exceeded one (1) year. Ifchrnees have been or if susprnsinn or nhm,dnnmenr
exmeds one (l) year, full fees shall be paid for a new permit.
(4) No work of any manner shall be done that will change die namral Ylow of water causing a drainage problem.
(5) CovtractorshallmtifyNeBuildiugInspectortwenty-four(24)honrsinadvanceforallinspectionsandshallreceivewrittenzppmvaloninspecnoncardbefore
praceeding witli snecessive pheses of tlmjob.
(6) The issaence of a permit or the apPmval of drawings and specificatlous shall not be construed eo be a pemit foq nor xn approval of, any violztion of the
pmvisions of tlie building codes or any other ordinancq law, mle or mgidafiov.
Chief Building Inspector
DEPARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number. : 13308
BUILDING INSPECTION LINE - 303-234-5933 Date : 1/2/02
CITY OF WHEAT RIDGE
7500 WEST 29TH AVENUE
WHEAT RIDGE, CO 80215 - (303-235-2855)
Property Owner: CELESTE LUECERO
Property Address : 2830 REED ST Phone : 465-4215
Contractor License No. : 21176
Company : TYN-MAN ELECTRIC, INC. Phone : 303-810-7087
OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT
I hereby certify that the setback distances proposed by this permit application are accurate, and
do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or
covenants, easements or restrictions of record; that all measurements shown, and allegations
made are accurate; that I have read and agree to abide by all conditions printed on this
application, and that I assume full responsibility for compliance wilh the Wheat Ridge Building
Code (U.B.C.) and all other applicable Wheat gidge ordinances, for work under this permit.
(OWNER)(CONTRACTOR)SIGNED// /I/i'J 4.;e/t- DATE /A9/0a
Description : SERVICE UPGRADE TO 200A
Construction Value :
$1,200.00
Permit Fee :
$41.80
Plan Review Fee :
$&00
Use Tax
$18 00
Total
$59,80
Use:
BUILDING DEPARTMENT USE ONLY
1 SIC : Sq. Ft. :
Approval :
Zoning :
Approval: BG
~VW
Approval :
Occupancy : Walis : Roof : Stories : Residential Units :
Electrical License No :
Company :
Plumbing License No :
Company :
Mechanical License No
Company
Expiration Date :
Approval :
Expiration Date :
Approval :
Expiration Date
Approval .
(1) This permil was issued in accortlance wiN the pmvisions set forth in yopur application and is subject to the laws of ihe State of Cobrado antl to ihe Zoning
Regulalions and Building Code of Wheat Ridge, Coloratlo or any other applicable ortlinances of the City.
(2) This permit shall expire if (A) the work authorizetl is not commenced within sixty (60) days from issue date or (B) the building authorized is suspended or
abantloned for a period of 120 days.
(3) If this permit expires, a new permit may be acquiretl For a fee of one-haB the amount normally requireQ pmvided no changes have been or will be made in the
original plans and specifcations and any suspension or abandonment has not exceeded one (1) year. If changes are made or if suspension or abandonment
exceetls one ('I) year, full tees shall 6e paitl for a new permit.
(4) No work of any manner shall be done thal will change the natural Flow of water causing a drainage problem.
(5) Conlrector shall notiry the Building Inspeclor twenry-four (24) hours in advance for all inspections antl shall receive written approval on inspection cartl before
proceediing with successive phases of the job.
(6) The issuance of a pertnit or the approval of tlrawin9s and specifrations shall not be constmetl to be a permit for, nor an approval of, any violation of the
provisions f the uildin codes or any other ordinance, law, rule or reguiation.
Chief Building Ins ctor
DEPARTMENT OF PLANDIING AND DEVELOPMENT Building Permit Number:
of wHE'r P BUILDING INSPECTION LINE - 303-234-5933 Date:
CITY OF WHEAT RIDGE
U m 7500 WEST 29TH AVENUE
WHEAT RIDGE, CO 80215 - (303-235-2855)
COC ORP00 j
~~~UCATi O~h
4 ♦
Property Owner. Cgc.8S7E LOr£-110
Property Address: d$SO R~E, s i.
Contractor License No.: A~
Phone :
CompanY: £LLC'IYLtc, ll,~2r Phone: 303-9J0-7097
OWNER/CONTRACTOR SIGNATURE OF ONDERSTAND WG AND AGREEMENT
I hercby certify [hat [he setback distances proposed by Ihis permit applicalion are accuratq
and do notviolate applicable ordinances, rules or regulations ofthe City of Wheat Ridge or
covenants, easements or restrictions ofrecord; that all measurements showq and allegations
made aze accurate; that I have read and agree to abide by all conditions printed on this
application and ffiat I assume full responsibility fot compliance with the Wheat Ridge
Building Code (U.B.C) and all other applicabte Wheat Ridge Ordinances, for work under
this permit.
(ownE[c)(conmwcroa):sicxED
Description: ~fgUiCZ. u'il &i2fllb L. _19) 13~ d:~~ r4 •
Construction Value:$
PermitFee:$ 1lJ.
Plan Review Fee:$
Use Taac:$
TOY31:$
BUILDING DEPARTMENT USE ONLY
SIC: Sq.Ft.:
ZONING COMMENTS:
Approval:
Zoning:
BUILDING COMMENTS: Approval: kG'_ r/~/~ 2
PUBLIC WORKS COMMENTS:
Approval:
Occupancy: Walls: Roof. Stories: ResidentialUnits:
Electrical License No: Plumbing License No: Mechanical License No:
Company: Company: Company:
Expiration Date: Expiration Date: Expiration Date:
Approval: Approval: Approval:
(t) Iltis pemit was issued in accordance with che provisions set foNi in yoia apPlicatlon and is subject to tlie laws of the Stam of Colorado and to the Zoning
Regulations and Huilding Codes of Whwt Ridgy Colocado or any other applica6le ordinances of the City.
(2) This pumit shall expire if (A) tlx work authorized is not commenced within sixty (60) days from issue date or (B) fie building authorized is suspended or
abandoued for a period of 120 days.
(3) If this peimit expires, a new peemit may be acqu'ved for a fee of one-haff the amomt nocmally required, provided no changes have been or will be made in
the originai plans and specificatlovs and any suspension or abandonmenthas not exceeded one (I) year. IIchaugu have been or if suspension or abandonment
exceeds one (1) yeaz, full fees shall be paid for a new pelmit.
(4) No work of any manner shffiI be done that will chauge the uanval flow of waror causing a draivage probiem.
(5) CovaacrorsfiallnofifytheBnildingIDspecrortwenty-fow(24)hoivsinadvanceforallinspatlonsandshallmceivewrittenapprovaloninspectlovcardbefore
proceeding wi[h successive phases of Nejob.
(6) The Issuance of a permit or the approval of drawings aud speci5catlons shall vot be coustrned ro be a permit foq nor an approval of, any riolatlon of the
provisious of the bwlding codes or avy other ordiuancy law, mle ar regulation.
/--~4 ~
Chnf Build' nspector
DEPARTMENT OF GOMMUNITY DEVELOPMENT
7500 WEST 29th AVENUE BUILDING INSPECTION DIVISION PERMIT N0. M94#19825
2345933 P.O. BOxe38 CITY OF WHEAT RIDGE, COLO.
THIS PERMIT VAUD ONLY WNEN 516NED BY THE CNIEF BUIIDING INSPECTOR AND RECEIPTEDBELOW.
APPLICATION FOR MISCELLANEOUS PERMIT
JOB ADDRESS 2830 Reed Street Lakewood 80215 OWNER Sh2t1 BOOtOn -
CONTRACTOR GL'OSS-RhOd2 EXt2r10Y5 IriC. ADDRESS Sd[~e
ADDRESS 10660 N. Flatiron Rd
CITY L1tt10tOI1 CO ZIP CODE $0124
PHONE 7 7-1777 LICENSE NO. 17618
PHONE 462-1865 ZIPCODE
CONTRACT PRICE $ l OQ9 nn
DATE 11/9/94
d❑
TVP
G
Woll❑
Proieclinp❑
Othar
SorDFOCe
SIGNS
roun
1.
E
2. MATERIAL
❑
❑
7
Total SQuors Faat
Eixf
Parmif No
No
3. ILLUMINATION Ysa
4. SET BACK FROM PROPERTY LINE N
(SDeti}y whith ia front)
ype
_
❑
S_ E
❑
_ W
❑ ❑
.
Zone_
.
ADDrwed,2onalnspeator
DisopprOVad
1. TYPE SolidO More Thon BO% OpsnO
1.ose Than BO% Open
Hoi
ht
fENCES
MATERIAL
3. SET BACK FROM PROPERTY LINE N
(SDeti}y whith ia front)
_
❑
S_ E
❑
_ W
❑ ❑
p
Zone_
ADVrwed,2ons Inspeetw
DiaopDrovsd
IriStdll 3-tab Fitwrql
acc
chinMa
c rn rr,r,f
OTHER
2
DRAW SKETCH OR SHOW BELOW, THE FENCE,SIfiN,OR OTHER S?RUCTURE, GIVIhG DISTANCES FROM PROPERTV LINES.
(SETBACK$ OR PROJECTIONS INCIUDED)
~
SPECIFV NORTN
STREET NAME
SHOW DISTANCES FROM THE M41N BUILDING TPADJOINING MOUSES, STREETS, AND PROPERTV LINES; ON IRREGULAR LATS, SHOW LEAST
DISTANCE TO PROPERTY IINES,NOT MA%IMUM OR AVERAGE D15T4NCE.
APPLICATION FOR PLUMBING; ELECTRICAL; MECHANICAL PERMIT
THIS APPLICATION WILL BECOME A PERMIT TO PERFORM THE INOICATED WORK ONLY UPON VALIDATION BY THE BUILDING INSPECTION DIVISION.
PERMIT WILL EXPIRE 180 DAYS FROM THE DATE OF ISSUANCE IF WOflK IS NOT STARTED WITHIN THAT TIME.
ELECTRICAL PERMIT
STATE IICENSE N0.
PLUMBING PERMIT
STATE LICENSE N0.
MECHANICAL PERMiT
ALUMINU~AWIREUNDERSIZE8ILLEGAL
FLOOR
BSM
IST
2ND
3RD
4TH
N0.
Fl1EUCirGaQMGaiOIlPropoM EI~CSoIO~
Np
WATER CIASET
FORCED AIR - BTU
TEMPORARY METER
WASH BOWL
IiOT WATER - BTU
NEW SERVICE - AMPS
BATH TUB
STEAM - BTU
CHANGE SERVICE-AMPS
SHOWER
AIR CONDITIONING-BTU
LIGHTING
SINK
OTMER
HEATING
GARBAGE DISP
REFRIGERATION SYSTEM
POWER SUB-GFCUITS
WATER HEATER
Retri eronf Gloup
UTIUTY(RANGE,DISPoSER,ETC)
AUTO. WASHER
Pa+nds CMr e
FI%TURES
DISH WASHER
AUTOMATIC SPRINKLER SYSTEM
WIRING MOTOFtS B CONTROLS
FLOOR DRAIN
ELEVATOR
SIGNS
URINAL
TRANSFORMERS 9 RECTFIERS
SEWERS
ADDITION TO OLD WORK
OTHER
MOTORS OVER I HP
TOTl+L FI%TURES
I Aoreby ocknowledqe thot this applica-
fion is conect and undersiand tnot I
connot frari tnie vroitlct until tnie oppli-
eotion if apOroved. 1 shall comply with
1M lows of the Slnte oi Colorado and to
fhe 2oninp Requlationa ond BuildinQ
Code ofthe City f Wneat RiEQe. Any
violalion ol t~e ove terme wdi couse
immediate revoc Ot on of this Dermit
PERMIT FEE .6--(/ i NOT VALID UNLESS RECEIPTED
UUSE TAX
13.11
TOTAL Et E
$ qqjrfi.,
APPROVE
D
~
DISAPPROVE
CHIEF BUILDING I
SPECTOR,C
ityof Wheat Ridge
CALL 234-5933
24 HOURS IN ADVANCE
FOR INSPECTIONS
Date Issued
Gross-Rhode, C.