Wheatridge Building Department 6/8/98
2900 W 29th Ave.
Wheatridge, Colorado 80033
RE: Tenant finish for Trudesign Design Wheel, 12300 W 49th Ave.
#2.
The following are our plan review comments;
1) All other exit doors in Group B, Occupancies shall be
openable from the inside without use of key or special knowledge.
UFC 94 1207.3.
2) Emergency lighting is subject to field inspection,
additional units may be required. UFC 94 1211.1.
3) Exit signs shall be subject to field inspection, additional
units may be required. UFC 94 1212.2.
4) Maximum storage height of products to
exceed (12) twelve feet from the floor due
construction of the fire sprinkler system.
information regarding commodities, storage
provided at the time of permit when requir
UFC 94 8101.3.2.
be stored shall not
to the design
Additional
arrangements, shall be
°d by the Fire Marshal.
5) Provide locks on circuit breakers supplyinq power to
emergency circuits such as exit lights, per the National
Electrical Code 1993 Edition.
6) Verify that sufficient electrical receptacles as extension
cords and multiple adapters are not permitted, nor shall flexible
cords pass through walls, ceilings, or doorways. UFC 94 8506.3.
7) Fire extinguishers shall be a 4-A rated 10-1b ABC dry
chemical type mounted not less than 3 feet nor more than 5 feet
from the floor to the top of the mounting bracket. The required
number of extinguishers and mounting information shall be
provided prior to final inspection. UFC 94 1002.1.
8) Carpeting shall be a minimum of a Class II Critical Radiant
Flux. Documentation shall be provided prior to installation.
UFC 94 Appendix IV-A.
9) Any code requirements arising from construction.
10) Twenty-four hours notice required for all tests and
inspections.