Residential Solar PERMIT - 201901521
PERMIT NO: 201901521 ISSUED: 07/26/2019 ,
JOB ADDRESS: 10920 W 39th Ave EXPIRES: 07/25/2020
JOB DESCRIPTION: Residential installation of utility interactive PV solar system 5.4 kW.
*** CONTACTS ***
OWNER (970)462-6843 ROBERT NONAN JOHNSON TRUST
SUB (385)482-0045 LEE HATLEY 180271 BRS FIELD OPS, LLC
*** PARCEL INFO ***
ZONE CODE: UA / Unassigned USE: UA / Unassigned
SUBDIVISION CODE: 2403 / APPLEWOOD VILLAGES, PROSPECT V BLOCK/LOT#: 0 /
*** FEE SUMMARY *** ESTIMATED PROJECT VALUATION: 7,356.00
FEES
Total Valuation 0.00
Residential Solar 500.00
** TOTAL ** 500.00
*** COMMENTS ***
*** CONDITIONS ***
Approved per plans and red -line notes on plans. Must comply with 2012 IRC, 2017 NEC and all
applicable City of Wheat Ridge Municipal Codes. Work is subject to field inspections.
I, by rn signature, do
app ica le building co
by the legal owner of
thispermrt. I further a
perfo d an that all
by attest that the work to be performed shall comply with all accompanying approved plans and specifications,
and all applicable municipal codes, policies and procedures, and that I am t e legal owner or have been authorized
roperty and am authorized to obtain this permit and perform the work described and approved in conjunction with
that I am legally authorized to include all entities named within this document as parties to the work to be
kto be performed is disclosed in this document and/or its' accompanying approved plans and specifications.
Signature of OR or CONTRACTOR (Circle one) ate
1. This permit was issued based on the information provided in the permit application and accompanying plans and specifications and is
subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures.
2. This permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and
received prior to the date of expiration. An extension of no more than 180 days made be granted at the discretion of the Chief Building
Official and may be subject to a fee equal to one-half of the original permit fee.
3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard
requirements, fees and procedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of
the Chief Building Official and is not guaranteed.
4. No work of any manner shall be performed that shall results in a changeof the natural flow of water without prior and specific approval.
5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all required
inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services
Division.
6, The issuance or grant'g of a permit shall not be construed to be a permit for, or an approval of, an violation of any provision of any
app a code or anf rdmance or regulation of this jurisdiction. Approval of work is subject to field inspection.
Signature of Chief Building Official Date
REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY.
-�COMMUNiTy
City of
Wheatmidge DEVELOPMENT
Building & Inspection Services
7500 W. 29' Ave., Wheat Ridge, CO 80033
Office: 303-235-2855 * Fax: 303-237-8929
Inspection Line: 303-234-5933
Email: permits(d_)ci.wheatridge.co.us
FOR OFFICE USE ONLY
Date:
W/2q0//
Plan/Permit #
/59- l
Plan Review Fee:
Building Permit Application
*** Complete all applicable highlighted areas on both sides of this form.
Incomplete applications may not be processed. ***
Property Address:
10920 W 39th PI, WHEAT RIDGE, Colorado, 80033, United States
Property Owner (please print): Shane Stephenson Phone: 9704626843
Property Owner Email:
shanemmacole@gmail.com
Tenant Name (Commercial Projects Only)
Property Owner Mailing Address: (if different than property address)
Address:
City, State, Zip:
Arch itectlEngineer:
ArchitectlEngineer E-mail:
Contractor Name: BRS Field Ops LLC
City of Wheat Ridge License #:
180271
Phone:
Phone:
Contractor E-mail Address: permitting.department@blueravensolar.com
For Plan Review Questions & Comments (please print):
385-482-0045
CONTACT NAME (please print): Justin Mack Phone:
CONTACT EMAIL(p/ease print): permitting.department@blueravensolar.com
385-482-0045
Sub Contractors (Must provide Wheat Ridge License No & Signed Subcontractor Authorization form):
Electrical: Plumbing: Mechanical:
W.R. City License # W.R. City License # W.R. City License #
Other City Licensed Sub: Other City Licensed Sub:
City License # City License #
Complete all highlighted fields.
[—]COMMERCIAL D RESIDENTIAL
Provide description of work: For ALL projects, provide a detailed description of work to be
performed, including current use of areas, proposed uses, square footage, existing condition and
proposed new condition, appliance size and efficiency, type and amount of materials to be used, etc.
Residential Solar Rooftop PV System 5.4 kW
SCOPE OF WORK INSTALLATION OF UTILITY INTERACTIVE PHOTOVOLTAIC SOLAR SYSTEM 5.4 kW DC
PHOTOVOLTAIC SOLAR ARRAY ROOF TYPE: Comp Shingle MODULES: (18) Trinasolar 300 TSM-DD05A.05(II)
INVERTER(S): Enphase IQ7-60-2-US,---- RACKING: Unirac Sunframe Microrail
Sq. Ft./LF
BTUs
Gallons
Amps Squares For Solar: KW # of Panels Requires Structural
For Commercial Projects Only: Occupancy Type: Construction Type:
Occupancy Load: Square Footage:
Project Value: (Contract value or the cost of all materials and labor included in the entire project)
$ 7356
OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT
I hereby certify that the setback distances proposed by this permit application are accurate and do not violate applicable ordinances, rules or
regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown and allegations made are
accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full responsibility for compliance
with applicable City of Wheat Ridge codes and ordinances for work under any permit issued based on this application; that I am the legal owner
or have been authorized by the legal owner of the property to perform the described work and am also authorized by the legal owner of any
entity included on this application to list that entity on this application. I, the applicant for this building permit application. warrant the
truthfulness of the information provided on the application.
CIRCLE ONE: (OWNER) (CONTRACTOR) or (AUTHORIZED REPRESENTATIVE) of (OWNER) (CONTRACTOR)
Signature (first and last name): 'Z6, X'6 For BRS Field Ops LLC DATE: 07/24/2019
Justin Mack
Printed Name:
ZONING COMMMENTS:
Reviewer:
BUILD] DEPARTMENT COMMENTS:
Revi "k
PUBLIC WORKS COMMENTS:
Reviewer:
OCCUPANCY CLASSIFICATION:
CONSTRUCTION TYPE:
Building Division Valuation:
D0MU S
- NCaTNEERTNC I L L C
June 13, 2019
To: Blue Raven Solar
1403 North Research Way, Building
Orem, LIT. 84097
Subject: Certification Letter
Stephenson Residence
39th PI.
Wheat Ridge, CO. 80033
To Whom It May Concern,
EH -IVSD
Domus Structural Engineering, LLC
P.O. Box 6986
Broomfield, CO 80021
530-864-7055
Domusstructural@gmail.com
43019'
F
igitally signed
*�`• by John Calvert
Date: 2019. 06.13
06. 3
15:33:57 -06'00'
A jobsite observation of the condition of the existing framing system was performed by an audit team of Blue Raven Solar as a
request from Domus Structural Engineering. All review is based on these observations and the design criteria listed below and
only deemed valid if provided information is true and accurate.
On the above referenced project, the roof structural framing has been reviewed for additional loading due to the installation of
the solar PV addition to the roof. The structural review only applies to the section of the roof that is directly supporting the solar
PV system and its supporting elements. The observed roof framing is described below. If field conditions differ, contractor to
notify engineer prior to starting construction.
The roof structure of (All MP's) consists of composition shingle on roof plywood that is supported by 2x6 rafters @ 24"o.c. with
ceiling joists acting as rafter ties. The rafters have a max projected horizontal span of 11'-9", with a slope of 20 degrees. The
rafters are connected at the ridge to a ridge board and are supported at the eave by a load bearing wall.
The existing roof framing system of (All MP's) are judged to be inadequate to withstand the loading imposed by the installation of
the solar panels. Structural reinforcement is required. Sister upgrade is required for (Ail MP's) on all rafters that directly support
solar and that have spans more than 9'-4" PV. Stitch new 2x6 DF#2 (min) to existing member with Simpson SDW 22300 screws @
16"o.c. or 10d nails @ 6"o.c.. Lap as needed with 4'-0" minimum lap per attached detail.
The spacing of the solar standoffs should be kept at 72" o.c. for landscape and 48" o.c. for portrait orientation, with a staggered
pattern to ensure proper distribution of loads.
The scope of this report is strictly limited to an evaluation of the fastener attachment, underlying framing and supporting
structure only. The attachment's to the existing structure are required to be in a staggered pattern to ensure proper distribution
of loading. All panels, racking and hardware shall be installed per manufacturer specifications and within specified design
limitations. All waterproofing shall be provided by the manufacturer. Domus Structural Engineering assumes no responsibility for
misuse or improper installation of the solar PV panels or racking.
Note: Seismic check is not required since Ss<.4g and Seismic Design Category (SDC) < B
Design Criteria:
• Applicable Codes = 2012 IBC/IRC, ASCE 7-10
• Roof Dead Load = 9 psf (All MP's)
• Roof Live Load = 20 psf
• Wind Speed = 135 mph (Vult), Exposure C, Risk Category II
• Roof Snow Load = 30 psf
• Attachments: 1- 5/16" dia. lag screw with 2.5 inch min embedment depth, at spacing shown above.
Please contact me with any further questions or concerns regarding this project.
Sincerely, -00g. go / ?,C)15-2 /
John Calvert, P.E.
Project Engineer
Stephenson Residence, Wheat Ridge, CO 1
(E) RAFTERS
(E) RAFTERS
INSTALL END GROUP OF
FASTENERS WITHIN 6" OF
EACH END. (3) SCREWS MIN
1X DECKING OR SHEATHING
MINIMALLY NOTCH NEW (E) CEILING JOIST
SISTER RAFTER TO BEAR
DIRECTLY ON (E) TOP PLATE
OF WALL.
OPTION 1 - FULL LENGTH SISTER
SEE LETTER FOR UPGRADE LAP LENGTH AND SIZE.
INSTALL END GROUP OF
FASTENERS WITHIN 6" OF
EACH END. (3) SCREWS MIN
1X DECKING OR SHEATHING
'---MINIMALLY NOTCH NEW (E) CEILING JOIST
SISTER RAFTER TO BEAR
DIRECTLY ON (E) TOP PLATE
OF WALL.
OPTION 2 - OVERLAPPED SISTER
SEE LETTER FOR UPGRADE LAP LENGTH AND SIZE.
(N) SISTER RAFTER
L v-0
(N) SISTER RAFTER (E) RAFTER
(N) SISTER MEMBER TO BEAR
DIRECTLY ON RIDGE BOARD
OR INSTALL SIMPSON A34
CLIP.
(N) SISTER MEMBER TO BE FULL
LENGTH. ATTACH TO (E) RAFTER W/
SIMPSON SDW22300 SCREWS
STAGGERED TOP AND BOTTOM @
16" O.C.
(E) FLAT PURLIN, DOES
NOT COUNT AS
SUFFICIENT
BEARING.
(N) SISTER MEMBER TO BEAR
DIRECTLY ON RIDGE BOARD
OR INSTALL SIMPSON A34
CLIP.
(N) SISTER MEMBER TO BE FULL
LENGTH. ATTACH TO (E) RAFTER W/
SIMPSON SDW22300 SCREWS
STAGGERED TOP AND BOTTOM @
16" O.C.
(E) FLAT PURLIN, DOES
NOT COUNT AS
SUFFICIENT
BEARING.
e�
.- 43019 '
SECTION A -A Digitally sig
John Calvert
TC�006t�
SISTER UPGRADE OPTIONS Date: 2019.06.13 C"dI
5 03 :48 -06'00'
ALTERNATIVE FASTENER SCHEDULE: 10d NAILS STAGGERED TOP AND BOTTOMV4h b.F
PROJECT NAME: Purlin sister upgrade
Domus Structural Engineering, LLC.
P.O. BOX 6986
Broomfield, CO 80021
(530) 864-7055
Domusstructural@gmail.com
T*W1on
Scale: N.T.S.
Date: 5/21/19
Project Number: of PV
Purlin sister upgrade detail and Drawn By: JAC Drawing Name:
specifications. Revisions:
A P -SIS
B
Domus Structural Engineering, LLC
U m u s P.O. Box 6986
Broomfield, CO 80021
530-864-7055
N C I N E IE R T T-k G T, 1. Domusstructural@gmail.com
Gravity Loading
Roof Snow Load Calculations
p9 = Ground Snow Load = 30 psf
pf = 0.7 Ce Ct I p9 (ASCE7 - Eq 7-1)
Ce = Exposure Factor = 1 (ASCE7 - Table 7-2)
Ct = Thermal Factor = 1 (ASCE7 - Table 7-3)
1 = Importance Factor = 1
pf = Flat Roof Snow Load = 30.0 psf
PS = CSpf (ASCE7 - Eq 7-2)
Cs = Slope Factor = 1
ps = Sloped Roof Snow Load = 30.0 psf
PV Dead Load = 3 psf (Per Blue Raven Solar)
DL Adjusted to 20 Degree Slope
3.19 psf
PV System Weight
Weight of PV System (Per Blue Raven Solar)
3.0 psf
X Standoff Spacing =
4.00 ft
Y Standoff Spacing =
5.50 ft
Standoff Tributary Area =
22.00 sft
Point Loads of Standoffs
66 Ib
Note: PV standoffs are staggered to ensure proper distribution of loading
Roof Live Load = 20 psf
Note: Roof live load is removed in area's covered by PV array.
Roof Dead Load (All MP's)
Composition Shingle 4.00
Roof Plywood 2.00
Double 2x6 Rafters @ 24"o.c. 2.30
Vaulted Ceiling
0.00 (Ceiling Not Vaulted)
Miscellaneous 0.70
Total Roof DL (All MP's) 9.0 psf
DL Adjusted to 20 Degree Slope 9.6 psf
C:%w °1
WhgO6 V%dge
WOO"
aut!
Stephenson Residence. Wheat Ridoe. CO 2
omu 4
-TRC"CF (JR X11
E`NGTNEERING 1 T. r, C:
Wind Calculations
Per ASCE 7-10 Components and Cladding
Input Variables
Wind Speed
135 mph
Exposure Category
C
Roof Shape
Hip/Gable
Roof Slope
20 degrees
Mean Roof Height
20 ft
Effective Wind Area
19.3 ft
Design Wind Pressure Calculations
Domus Structural Engineering, LLC
P.O. Box 6986
Broomfield, CO 80021
530-864-7055
Domusstructural@gmail.com
Wind Pressure P = qh*G*Cn
qh = 0.00256 * Kz * Kzt * Kd * V^2
(Eq. 30.3-1)
Kz (Exposure Coefficient) = 0.9
(Table 30.3-1)
Kzt (topographic factor) = 1
(Fig. 26.8-1)
Kd (Wind Directionality Factor) = 0.85
(Table 26.6-1)
V (Design Wind Speed) = 135 mph
(Fig. 26.5-1A)
Risk Category = 11
(Table 1.5-1)
qh = 35.69
(Fig. 30.4-1)
0.6*qh= 21.42
-17.95 psf
Standoff Uplift Calculations -Portrait
Zone 1
Zone 2
Zone 3
Positive
GCp =
-0.84
-1.39
-2.23
0.38
(Fig. 30.4-1)
Uplift Pressure =
-17.95 psf
-29.77 psf -47.71
psf
13.4 psf
X Standoff Spacing =
4.00
4.00
2.67
Y Standoff Spacing =
5.50
2.75
2.75
Tributary Area =
22.00
11.00
7.33
Footing Uplift =
-395 Ib
-327 Ib
-350 Ib
Standoff Uplift Calculations -Landscape
Zone 1
Zone 2
Zone 3
Positive
GCp =
-0.84
-1.39
-2.23
0.38
(Fig. 30.4-1)
Uplift Pressure =
-17.95 psf
-29.77 psf -47.71
psf
10.0 psf
(Minimum)
X Standoff Spacing =
6.00
6.00
4.00
Y Standoff Spacing =
3.50
1.75
1.75
Tributary Area =
21.00
10.50
7.00
Footing Uplift =
-377 Ib
-313 Ib
-334 Ib
Standoff Uplift Check
Maximum Design Uplift = -395 Ib
Standoff Uplift Capacity = 450 Ib
450 Ib capacity > 395 Ib demand Therefore, OK
Fastener Capacity Check
Fastener = 1 - 5/16" dia. lag
Number of Fasteners = 1
Embedment Depth = 2.5
Pullout Capacity Per Inch = 250 Ib
Fastener Capacity = 625 Ib
w/ F.S. of 1.5 & DOL of 1.6= 667 Ib
667.2 Ib capacity > 395 Ib demand Therefore, OK
City of
Wheat Ridge
g itdin9 Division
w
Steohenson Residence. Wheat Ridoe. CO 3
Domus Structural Engineering, LLC
o m u s P.O. Box 6986
Broomfield, CO 80021
L" 530-864-7055
:: {I T N E E R I N C, 1, I. Domusstructural@gmail.com
Framing Check
(All MP's) PASS - With Framing Upgrades
w=86plf
Dead Load 9.6 psf
PV Load 3.2 psf
Snow Load 30.0 psf Double 2x6 Rafters @ 24"o.c.
® Q
Governing Load Combo = DL + SL Member Span = 11'- 9"
Total Load 42.8 psf
Member Properties • Based on Upgraded Section
Member Size S (in^3) I (in^4) Lumber Sp/Gr Member Spacing
Double 2x6 15.13 41.59 DF#2 @ 24"o.c.
Check Bendinc
Fb (psi) = fb x Cd x Cf x
900 x 1.15 x 1.3 x
Allowed Bending Stress =1547.3 psi
Stress
1.15
Maximum Moment = (wL12) / 8
= 1476.238 ft#
= 17714.85 in#
Actual Bending Stress = (Maximum Moment) / S
= 1171.3 psi
Allowed > Actual -- 75.7% Stressed -- Therefore, OK
Check Deflection
Allowed Deflection (Total Load) = L/180 (E = 1600000 psi Per NDS)
= 0.783 in
Deflection Criteria Based on = Continuous Span
Actual Deflection (Total Load) _ (w*L^4) / (185*E*I)
= 0.229 in
= L/616 > L/180 Therefore OK
Allowed Deflection (Live Load) =
Actual Deflection (Live Load) =
1-1240
0.587 in
(w*L^4) / (185*E*I)
0.161 in
U876 > U240 Therefore OK
ow of
Check Shear '01100%V%d9®
Member Area= 16.5 in^2 Fv (psi) = 180 psi (NDS Table 4A) DV15s'p°
Allowed Shear = Fv * A = 2970 Ib Max Shear (V) = w * L / 2 = 503 lb 5"`�din9
Allowed > Actual -- 17% Stressed -- Therefore, OK
Stephenson Residence. Wheat Ridae. CO 4
Domus
-TRUCTUR lS.
ENGINEER i N G LLC
June 13, 2019
To: Blue Raven Solar
1403 North Research Way, Building J
Orem, LIT. 84097
Subject: Certification Letter
Stephenson Residence
39th PI.
Wheat Ridge, CO. 80033
To Whom It May Concern,
R E C[Z-11f E®
Domus Structural Engineering, LLC
P.O. Box 6986
Broomfield, CO 80021
530-864-7055
Domusstructural@gmail.com
.--,43019
igitally signed
%Z.j#1.�� by John Calvert
Date: 2019.06.13
15:33:57 -0600'
A jobsite observation of the condition of the existing framing system was performed by an audit team of Blue Raven Solar as a
request from Domus Structural Engineering. All review is based on these observations and the design criteria listed below and
only deemed valid if provided information is true and accurate.
On the above referenced project, the roof structural framing has been reviewed for additional loading due to the installation of
the solar PV addition to the roof. The structural review only applies to the section of the roof that is directly supporting the solar
PV system and its supporting elements. The observed roof framing is described below. If field conditions differ, contractor to
notify engineer prior to starting construction.
The roof structure of (All MP's) consists of composition shingle on roof plywood that is supported by 2x6 rafters @ 24"o.c. with
ceiling joists acting as rafter ties. The rafters have a max projected horizontal span of 11'-9", with a slope of 20 degrees. The
rafters are connected at the ridge to a ridge board and are supported at the eave by a load bearing wall.
The existing roof framing system of (All MP's) are judged to be inadequate to withstand the loading imposed by the installation of
the solar panels. Structural reinforcement is required. Sister upgrade is required for (All MP's) on all rafters that directly support
solar and that have spans more than 9'-4" PV. Stitch new 2x6 DF#2 (min) to existing member with Simpson SDW 22300 screws @
16"o.c. or 10d nails @ 6"o.c.. Lap as needed with 4'-0" minimum lap per attached detail.
The spacing of the solar standoffs should be kept at 72" o.c. for landscape and 48" o.c. for portrait orientation, with a staggered
pattern to ensure proper distribution of loads.
The scope of this report is strictly limited to an evaluation of the fastener attachment, underlying framing and supporting
structure only. The attachment's to the existing structure are required to be in a staggered pattern to ensure proper distribution
of loading. All panels, racking and hardware shall be installed per manufacturer specifications and within specified design
limitations. All waterproofing shall be provided by the manufacturer. Domus Structural Engineering assumes no responsibility for
misuse or improper installation of the solar PV panels or racking.
Note: Seismic check is not required since Ss<.4g and Seismic Design Category (SDC) < B
Design Criteria:
• Applicable Codes = 2012 IBC/IRC, ASCE 7-10 City of
• Roof Dead Load = 9 psf (All MP's)
• Roof Live Load = 20 psf Whe°i V ge
• Wind Speed = 135 mph (Vult), Exposure C, Risk Category II
• Roof Snow Load = 30 psf adding Div►5i°l,
• Attachments: 1- 5/16" dia. lag screw with 2.5 inch min embedment depth, at spacing shown above.
Please contact me with any further questions or concerns regarding this project.
Sincerely, ,
John Calvert, P.E.
Project Engineer Stephenson Residence, Wheat Ridge, CO 1
INSTALL END GROUP OF
FASTENERS WITHIN 6" OF
EACH END. (3) SCREWS MIN
1X DECKING OR SHEATHING
(E) RAFTERS
MINIMALLY NOTCH NEW �— (E) CEILING JOIST
SISTER RAFTER TO BEAR
DIRECTLY ON (E) TOP PLATE
OF WALL.
OPTION 1 - FULL LENGTH SISTER
SEE LETTER FOR UPGRADE LAP LENGTH AND SIZE.
INSTALL END GROUP OF
FASTENERS WITHIN 6" OF
EACH END. (3) SCREWS MIN
1X DECKING OR SHEATHING
(E) RAFTERS
(N) SISTER MEMBER TO BEAR
DIRECTLY ON RIDGE BOARD
OR INSTALL SIMPSON A34
CLIP.
(N) SISTER MEMBER TO BE FULL
LENGTH. ATTACH TO (E) RAFTER W/
SIMPSON SDW22300 SCREWS
STAGGERED TOP AND BOTTOM @
16" 0. C.
(E) FLAT PURLIN, DOES
NOT COUNT AS
SUFFICIENT
BEARING .
(N) SISTER MEMBER TO BEAR
DIRECTLY ON RIDGE BOARD
OR INSTALL SIMPSON A34
CLIP.
(N) SISTER MEMBER TO BE FULL
LENGTH. ATTACH TO (E) RAFTER W/
SIMPSON SDW22300 SCREWS
STAGGERED TOP AND BOTTOM @
16" O.C.
/ (E) FLAT PURLIN, DOES
F71V \— NOT COUNT AS
SUFFICIENT
MINIMALLY NOTCH NEW (E) CEILING JOIST BEARING.
SISTER RAFTER TO BEAR
DIRECTLY ON (E) TOP PLATE
OF WALL.
OPTION 2 - OVERLAPPED SISTER"
SEE LETTER FOR UPGRADE LAP LENGTH AND SIZE.
(N) SISTER RAFTER
:° 43019 �
(N) SISTER RAFTER (E) RAFTER �.
SECTION A -A Digitally sig
John Calvert
SISTER UPGRADE OPTIONS Date: 2019.06.13
J:.5.3;415 -Uo UU
ALTERNATIVE FASTENER SCHEDULE: 10d NAILS STAGGERED TOP AND
of
vheot Ridge
D 6" O.;n
BM,161�1 *�
PROJECT NAME: Purlin sister upgrade Scale: N.T.S.
Domus Structural Engineering, LLC. Date: 5/21/19 V
P.O. BOX 6986 Project
/21/19Project Number: Solar PV
P.O. BOX 6986 Project Description: Purlin sister upgrade detail and Drawn By: JAC Drawing Name:
Broomfield, CO 80021
specifications. Revisions:
(530) 864-7055 AP -S S
Domusstructural@gmail.com e
Domus Structural Engineering, LLC
o m u s P.O. Box 6986
Broomfield, CO 80021
530-864-7055
-1�+- N fy f. N F E R T N C, T. T. f Domusstructural@gmail.com
Gravity Loading
Roof Snow Load Calculations
p9 = Ground Snow Load = 30 psf
pf = 0.7 Ce Ct l p9
Ce = Exposure Factor =
Ct = Thermal Factor =
I = Importance Factor =
pf = Flat Roof Snow Load =
PS = CSpf
Cs = Slope Factor =
(ASCE7 - Eq 7-1)
1 (ASCE7 - Table 7-2)
1 (ASCE7 - Table 7-3)
1
30.0 psf
(ASCE7 - Eq 7-2)
ps = Sloped Roof Snow Load = 30.0 psf
PV Dead Load = 3 psf (Per Blue Raven Solar)
DL Adjusted to 20 Degree Slope
3.19 psf
PV System Weight
4.00
Weight of PV System (Per Blue Raven Solar)
3.0 psf
X Standoff Spacing =
4.00 ft
Y Standoff Spacing =
5.50 ft
Standoff Tributary Area =
22.00 sft
Point Loads of Standoffs
66 Ib
Note: PV standoffs are staggered to ensure proper distribution of loading
Roof Live Load = 20 psf
Note: Roof live load is removed in area's covered by PV array.
Roof Dead Load (All MP's)
Composition Shingle
4.00
Roof Plywood
2.00
Double 2x6 Rafters @ 24"o.c.
2.30
Vaulted Ceiling
0.00 (Ceiling Not Vaulted)
Miscellaneous
0.70
Total Roof DL (All MP's)
9.0 psf
DL Adjusted to 20 Degree Slope
9.6 psf
City or
Wheat pidoe
9
Stephenson Residence. Wheat Ridoe. CO 2
omu s
= T Et 1_1 C, SUR 3,L
E: 1 NE E R T IrG T. T.0
Wind Calculations
Per ASCE 7-10 Components and Cladding
Input Variables
Wind Speed
135 mph
Exposure Category
C
Roof Shape
Hip/Gable
Roof Slope
20 degrees
Mean Roof Height
20 ft
Effective Wind Area
19.3 ft
Design Wind Pressure Calculations
Domus Structural Engineering, LLC
P.O. Box 6986
Broomfield, CO 80021
530-864-7055
Domusstructural@gmail.com
Wind Pressure P = qh*G*Cn
Zone 1 Zone 2
qh = 0.00256 * Kz * Kzt * Kd * V^2
(Eq. 30.3-1)
Kz (Exposure Coefficient) =
0.9
(Table 30.3-1)
Kzt (topographic factor) =
1
(Fig. 26.8-1)
Kd (Wind Directionality Factor) =
0.85
(Table 26.6-1)
V (Design Wind Speed) =
135 mph
(Fig. 26.5-1A)
Risk Category =
11
(Table 1.5-1)
qh =
35.69
0.6*qh=
21.42
Zone 1 Zone 2
Standoff Uplift Calculations -Portrait
Zone 1 Zone 2
Zone 3
Positive
GCp= -0.84 -1.39
-2.23
0.38 (Fig. 30.4-1)
Uplift Pressure = -17.95 psf -29.77 psf
-47.71 psf
13.4 psf
X Standoff Spacing = 4.00 4.00
2.67
Y Standoff Spacing = 5.50 2.75
2.75
Tributary Area = 22.00 11.00
7.33
Footing Uplift = -395 Ib -327 Ib
-350 Ib
Standoff Uplift Calculations -Landscape
Zone 1 Zone 2
Zone 3
Positive
GCp = -0.84 -1.39
-2.23
0.38 (Fig. 30.4-1)
Uplift Pressure = -17.95 psf -29.77 psf
-47.71 psf
10.0 psf (Minimum)
X Standoff Spacing = 6.00 6.00
4.00
Y Standoff Spacing = 3.50 1.75
1.75
Tributary Area = 21.00 10.50
7.00
Footing Uplift = -377 Ib -313 lb
-334 Ib
Standoff Uplift Check
Maximum Design Uplift = -395 Ib
`
GXVI o
Standoff Uplift Capacity = 450 Ib
450 Ib capacity > 395 Ib demand Therefore, OK
1169e
�rece
.000
Fastener Capacity Check
�.
Fastener = 1 - 5/16° dia. lag
Number of Fasteners = 1
Embedment Depth = 2.5
Pullout Capacity Per Inch = 250 Ib
Fastener Capacity = 625 Ib
w/ F.S. of 1.5 & DOL of 1.6= 667 Ib
667.2 Ib capacity > 395 Ib demand Therefore, OK
Stephenson Residence. Wheat Ridae. CO 3
Domus Structural Engineering, LLC
D 0 kl T f S P.O. Box 6986
Broomfield, CO 80021
T' E E.% T C I 530-864-7055
awl Cz T "ti E FR t N (, T. i. C2 Domusstructural@gmail.com
Framing Check
(All MP's) PASS - With Framing Upgrades
w = 86 plf
Dead Load 9.6 psf
PV Load 3.2 psf
Snow Load 30.0 psf Double 2x6 Rafters @ 24"o.c.
!� p
Governing Load Combo = DL + SL I Member Span = 11'- 9"
Total Load 42.8 psf
Member Properties - Based on Upgraded Section
Member Size S (in ^3) 1(in ^4) Lumber Sp/Gr Member Spacing
Double 2x6 15.13 41.59 DF#2 @ 24"o.c.
Check Be
Fb (psi) = fb x Cd x Cf
900 x 1.15 x 1.3
Allowed Bending Stress = 1547.3 psi
ig Stress
x Cr
x 1.15
Maximum Moment = (wL"2)/8
= 1476.238 ft#
= 17714.85 in#
Actual Bending Stress = (Maximum Moment) / S
= 1171.3 psi
Allowed > Actual -- 75.7% Stressed -- Therefore, OK
Check Deflection
Table 4.
Allowed Deflection (Total Load) = L/180 (E = 1600000 psi Per NDS)
= 0.783 in
Deflection Criteria Based on = Continuous Span
Actual Deflection (Total Load) _ (w*L^4) / (185*E*I)
= 0.229 in
= U616 > U180 Therefore OK
Allowed Deflection (Live Load) = L/240
0.587 in 0W of
Actual Deflection (Live Load) _ (w*L"4) / (185*E*I)
0.161 in wheot Ridge
U876 > L/240 Therefore OK
euild�ng pwis�p°
Check Shear
Member Area= 16.5 in"2 Fv (psi) = 180 psi (NDS T ble PA)'
Allowed Shear = Fv * A = 2970 Ib Max Shear (V) = w * L/2 = 5
Allowed > Actual --17% Stressed -- Therefore, OK
Stephenson Residence. Wheat Ridae. CO 4
GERERAL NOTES
CODES AND STANDARDS
1 ALL WORK SHALL COMPLY WITH 2017 NATIONAL ELECTRIC CODE (NEC), 2015
INTERNATIONAL RESIDENTIAL CODE (IRC), 2015 INTERNATIONAL BUILDING CODE (IBC), 2015
INTERNATIONAL PLUMBING CODE (IPC), AND ALL STATE AND LOCAL BUILDING, ELECTRICAL,
AND PLUMBING CODES
2. DRAWINGS HAVE BEEN DETAILED ACCORDING TO UL LISTING REQUIREMENTS.
3. TERMINALS AND LUGS WILL BE TIGHTENED TO MANUFACTURER TORQUE
SPECIFICATIONS (WHEN PROVIDED) IN ACCORDANCE WITH NEC CODE 110 14(D) ON ALL
ELECTRICAL CONNECTIONS.
SITE NOTES / OSHA REGULATION
1, A LADDER SHALL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA REGULATIONS
2, THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE AND THIS SYSTEM IS AN UTILITY
INTERACTIVE SYSTEM WITH NO STORAGE BATTERIES.
3. THE SOLAR PV INSTALLATION SHALL NOT OBSTRUCT ANY PLUMBING, MECHANICAL, OR
BUILDING ROOF VENTS
4, ROOF COVERINGS SHALL BE DESIGNED, INSTALLED, AND MAINTAINED IN ACCORDANCE WITH
THIS CODE AND THE APPROVED MANUFACTURER'S INSTRUCTIONS SUCH THAT THE ROOF
COVERING SHALL SERVE TO PROTECT THE BUILDING OR STRUCTURE.
SOLAR CONTRACTOR
1. MODULE CERTIFICATIONS WILL INCLUDE UL1703, IEC61646, IEC61730.
2. IF APPLICABLE, MODULE GROUNDING LUGS MUST BE INSTALLED AT THE MARKED GROUNDING
LUG HOLES PER THE MANUFACTURERS' INSTALLATION REQUIREMENTS -
3 AS INDICATED BY DESIGN, OTHER NRTL LISTED MODULE GROUNDING DEVICES MAY BE USED
IN PLACE OF STANDARD GROUNDING LUGS AS SHOWN IN MANUFACTURER DOCUMENTATION
AND APPROVED BY THE AHJ.
4. CONDUIT AND WIRE SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND
ARE NOT MEANT TO LIMIT UP-SIZING AS REQUIRED BY FIELD CONDITIONS.
5. CONDUIT POINT OF PENETRATION FROM EXTERIOR TO INTERIOR TO BE INSTALLED AND
SEALED WITH A SUITABLE SEALING COMPOUND.
6. DC WIRING LIMITED TO MODULE FOOTPRINT W/ ENPHASE AC SYSTEM.
7. ENPHASE WIRING SYSTEMS SHALL BE LOCATED AND SECURED UNDER THE ARRAY W/
SUITABLE WIRING CLIPS.
8 MAX DC VOLTAGE CALCULATED USING MANUFACTURER PROVIDED TEMP COEFFICIENT FOR
VOC UNLESS NOT AVAILABLE.
9 ALL INVERTERS, MOTOR GENERATORS, PHOTOVOLTAIC MODULES, PHOTOVOLTAIC PANELS,
AC PHOTOVOLTAIC MODULES, DC COMBINERS, DC -TO -DC CONVERTERS, SOURCE CIRCUIT
COMBINERS, AND CHARGE CONTROLLERS INTENDED FOR USE IN A PHOTOVOLTAIC POWER
SYSTEM WILL BE IDENTIFIED AND LISTED FOR THE APPLICATION PER 690.4 (B).
10 ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE.
EQUIPMENT LOCATIONS
1 PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED
ELECTRICAL EQUIPMENT WILL BE PROVIDED AS PER SECTION [NEC 110.26].
2 EQUIPMENT INSTALLED INDIRECT SUNLIGHT MUST BERATED FOR EXPECTED OPERATING
TEMPERATURE AS SPECIFIED BY [NEC 690.31 (A) -(B)] AND [NEC TABLE 310.15 (B)].
3. ADDITIONAL AC DISCONNECTS SHALL BE PROVIDED WHERE THE INVERTER IS NOT ADJACENT
TO THE UTILITY AC DISCONNECT, OR NOT WITHIN SIGHT OF THE UTILITY AC DISCONNECT.
4. ALL EQUIPMENT SHAL1.14EtMySTALLED l&g4IBLE TO QUALIFIED PERSONNEL ACCORDING
TO NEC APPLICABLE CO `"'''����
5. ALL COMPONENTS AR j IED FOR OUTDOOR USAGE
WHEN APPROPRIATE.
VIeved for Code Compliance
�
Plans f ~Joner Dat
L/slidity of olrmrtThe dsuarre of o permit a approval of pons speciAcW+OnO
and computations chaff not be a permit for, or on approval of any viabtiow to
PRY of the provisions of the building code at of airy City onflnop s. AtnMp
presuming to give authority to violate of cancel the provishm of Mt &AVxp
codes or other ordvwn ces of the City shoo not be voW.
0 201 9,o t,52,/
AERIAL VIEW
Notes:
1)Verify or provide supplemental ground rod or
rods per 2017 NEC Art. 250.53(A)(2).
2) Natural Gas piping to be bonded s per 2017 NEC
Art. 250.104(B).
3)Bond P/V panels to the building Grounding
DESIGN CRITERIA
ASCE 7 WIND SPEED: 120 MPH
GROUND SNOW LOAD: 30 PSF
EXPOSURE CATEGORY: C
SEISMIC DESIGN CATEGORY: B
SCOPE OF WORK
SITE SPECIFICATIONS
OCCUPANCY- R3
CONSTRUCTION - V -B
ZONING: RESIDENTIAL
INSTALLATION OF UTILITY INTERACTIVE PHOTOVOLTAIC SOLAR SYSTEM
5.4 kW DC PHOTOVOLTAIC SOLAR ARRAY
ROOF TYPE: Comp Shingle
MODULES: (18) Trinasolar 300 TSM-DD05A.05(II) A
INVERTER(S): Enphase IQ7-60-2-US,----
RACKING: Unirac Sunframe Microrail
El
SHEETINDEX
PV1 - COVER SHEET
PV2 - PROPERTY PLAN
PV3 - SITE PLAN
PV4 - EQUIPMENT & ATTACHMENT DETAIL
PV5 - ELECTRICAL SINGLE LINE DIAGRAM
PV6 - ELECTRICAL CALCULATIONS &
ELECTRICAL NOTES
PV7 - MAIN BREAKER DERATE CALCS.
(IF NEEDED)
PV8 - LABELS & LOCATIONS
PV9 - CUSTOM DIRECTORY PLACARD
(IF NEEDED - NEC 690.56(B))
1403 N RESEARCH WAY, BUILDING J
OREM, UT 84097
800-377-4480
�.. WWW.BLUERAVENSOLAR.COM
CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF
ANYONE EXCEPT
BLUERAVENSOLAR NOR SHALL IT
BE DISCLOSED IN WHOLE OR IN
PART TO OTHERS OUTSIDE
RECIPIENTS ORGANIZATION,
EXCEPT IN CONNECTION WITH THE
SALE AND USE OF THE RESPECTIVE
EQUIPMENT WITHOUT THE
WRITTEN PERMISSION OF
BLUERAVENSOLAR LLC.
NABCEP
CERTIFIED
PV INSTALLATION
PROFESSIONAL
Scott Gurney
# PV -011719-015866
CONTRACTOR:
BRS FIELD OPS
385.498.6700
M
�.4;1
*.
O
�
O
O
(6
Notes:
1)Verify or provide supplemental ground rod or
rods per 2017 NEC Art. 250.53(A)(2).
2) Natural Gas piping to be bonded s per 2017 NEC
Art. 250.104(B).
3)Bond P/V panels to the building Grounding
DESIGN CRITERIA
ASCE 7 WIND SPEED: 120 MPH
GROUND SNOW LOAD: 30 PSF
EXPOSURE CATEGORY: C
SEISMIC DESIGN CATEGORY: B
SCOPE OF WORK
SITE SPECIFICATIONS
OCCUPANCY- R3
CONSTRUCTION - V -B
ZONING: RESIDENTIAL
INSTALLATION OF UTILITY INTERACTIVE PHOTOVOLTAIC SOLAR SYSTEM
5.4 kW DC PHOTOVOLTAIC SOLAR ARRAY
ROOF TYPE: Comp Shingle
MODULES: (18) Trinasolar 300 TSM-DD05A.05(II) A
INVERTER(S): Enphase IQ7-60-2-US,----
RACKING: Unirac Sunframe Microrail
El
SHEETINDEX
PV1 - COVER SHEET
PV2 - PROPERTY PLAN
PV3 - SITE PLAN
PV4 - EQUIPMENT & ATTACHMENT DETAIL
PV5 - ELECTRICAL SINGLE LINE DIAGRAM
PV6 - ELECTRICAL CALCULATIONS &
ELECTRICAL NOTES
PV7 - MAIN BREAKER DERATE CALCS.
(IF NEEDED)
PV8 - LABELS & LOCATIONS
PV9 - CUSTOM DIRECTORY PLACARD
(IF NEEDED - NEC 690.56(B))
1403 N RESEARCH WAY, BUILDING J
OREM, UT 84097
800-377-4480
�.. WWW.BLUERAVENSOLAR.COM
CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF
ANYONE EXCEPT
BLUERAVENSOLAR NOR SHALL IT
BE DISCLOSED IN WHOLE OR IN
PART TO OTHERS OUTSIDE
RECIPIENTS ORGANIZATION,
EXCEPT IN CONNECTION WITH THE
SALE AND USE OF THE RESPECTIVE
EQUIPMENT WITHOUT THE
WRITTEN PERMISSION OF
BLUERAVENSOLAR LLC.
NABCEP
CERTIFIED
PV INSTALLATION
PROFESSIONAL
Scott Gurney
# PV -011719-015866
CONTRACTOR:
BRS FIELD OPS
385.498.6700
DRAWING BY
Quinn Everett
DATE
July 19, 2019
PROJECT NUMBER
62660967
SHEET NAME
COVER SHEET
PAGE NUMBER REVISION
PV1 A
M
O
�
O
O
(6
�
z
O
Q
O
Z
C/)
c
U)
O
in
E
M
O
rn
o
O
Cj
LLI
Q
z
3:in
L0
Li
D,
LLI
C/)
>_
DRAWING BY
Quinn Everett
DATE
July 19, 2019
PROJECT NUMBER
62660967
SHEET NAME
COVER SHEET
PAGE NUMBER REVISION
PV1 A
FAI
MIDI!
# OF MODULES: 5
AZI MUTH:270°
PITCH:20°
97'-5" TSRF:68%
DC SYSTEM SIZE: 5.4 kW DC
ROOF TYPE: Comp Shingle
(18) Trinasolar 300 TSM-DD05A.05(II)
Enphase IQ7-60-2-US,----INVERTER
10920 W 39th PI
;33'-2"
331-911 -
�r
FRONT OF HOME
MP2
# OF MODULES: 8
N AZIMUTH -O'
PITCH -200
TSRF:60%
AREA: 300 SQ. FT
Is 19 --V -V
JB 6 N
1
Im
JB O B
0 JB O p
0
59'-9"
MP3
# OF MODULES: 2
AZIMUTH:180°
PITCH:20°
TSRF:67%
AREA: 391 SQ. FT
# OF MODULES: 3 119'-9"
A7lMlJTH 9n°
LEGEND
INV INVERTER & DC DISCONNECT
SUB (E) SUBPANEL
LC (N) LOAD CENTER
AC AC DISCONNECT
❑M UTILITY METER / SERVICE PANEL
JB JUNCTION BOX
C❑ COMBINER BOX
PV PV REVENUE METER
® FIRE SETBACK
EMT CONDUIT RUN
(TO BE DETERMINED IN FIELD)
PV WIRE STRING
PROPERTY LINE
Now -
RAVEN
1403 N RESEARCH WAY, BUILDING J
OREM. UT 84097
800-377-4480
WWW.BLUERAVENSOLAR COM
CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF
ANYONE EXCEPT
BLUERAVENSOLAR NOR SHALL IT
BE DISCLOSED IN WHOLE OR IN
PART TO OTHERS OUTSIDE
RECIPIENTS ORGANIZATION,
EXCEPT IN CONNEC TION WITH THE
SALE AND USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE
WRITTEN PERMISSION OF
BLUERAVENSOLARLLC.
rNABCEP
CERTIFIED
PV INSTALLATION
PROFESSIONAL
Scott Gurney
# PV -011719-015866
SCALE: 1/16" = V-0" CONTRACTOR:
9 16 37 BRS FIELD OPS
385.498.6700
DATE
July 19, 2019
City of
PROJECT NUMBER
VIh,at Ridge 62660967
1EET NAME
PROPERTY PLAN
PAGE NUMBER REVISION
PV2 A
M
o
U
0
0
00
o
m
z
_o
►ri
O
c
O
U
LLJ
O
N
Q
c
W
O
M
ry
LtJ
z
Q
M
M
2
C)
DRAWING BY
Quinn
Everett
DATE
July 19, 2019
City of
PROJECT NUMBER
VIh,at Ridge 62660967
1EET NAME
PROPERTY PLAN
PAGE NUMBER REVISION
PV2 A
FRONT OF HOME
36'-6"
N
M P2
# OF MODUL
AZIMUTH -.00
PITCH. -200
TSRF:60%
V-10" AREA: 300 S
JB
O
M P 1 n 9C lic
# OF MODULES: 5 O
33' AZIMUTH:2700 JB
PITCH:200
JB O
TSRF:68%
AREA: 191 SQ. FT
4 � �
11'-7"
DC SYSTEM SIZE: 5.4 kW DC
ROOF TYPE: Comp Shingle
(18) Trinasolar 300 TSM-DD05A.05(II)
Enphase IQ7-60-2-US,----INVERTER
►' mQyC
OVERHEAD SERVICE LINE
35'-6"
MP3
# OF MODULES: 2
AZIMUTH:180°
PITCH:20°
TSRF:67%
AREA: 391 SQ. FT
25'
Structural upgrades required on all rafters that directly
support solar PV and that have spans more than 9'-4". (E )
Flat purlin does not count as a suffiient bearing and shall not
reduce span of rafters for upgrade purposes. 2x6 sister
upgrade required. See structural detail and calculations
package for additional info.
LEGEND
INV INVERTER & DC DISCONNECT
BLUE RAVEN
SUB (E) SUBPANEL
15:14:34 -06'00'
LC (N) LOAD CENTER
PAGE NUMBER
1403 N RESEARCH WAY, BUILDING J
OREM, UT 84097
AC AC DISCONNECT
800-377-4480
WWW, BLU ERAVENSOLAR.COM
❑M UTILITY METER / SERVICE PANEL
CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
JB JUNCTION BOX
E
USED FOR THE BENEFIT OF
ANYONE EXCEPT
BLUERAVENSOLAR NOR SHALL IT
BE DISCLOSED IN WHOLE OR IN
�C COMBINER BOX
PART TO OTHERS OUTSIDE
RECIPIENTS ORGANIZATION,
EXCEPT IN CONNEC TION WITH THE
PV PV REVENUE METER
S
SALE AND USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE
WRITTEN PERMISSION OF
® FIRE SETBACK
BLUERAVENSOLAR LLC.
EMT CONDUIT RUN
NABCEP
(TO BE DETERMINED IN FIELD)
CERTIFI_E_D
PV WIRE STRING
PV INSTALLATION
i
PROFESSIONAL
PROPERTY LINE
Scott Gurney
# PV -011719-015866
SCALE: 1/8" = 1'-0"
CONTRACTOR:
0 1 a e 16
BRS FIELD OPS
385.498.6700
co
M U
C:) 0
o Y
M
L
Sealed For
Z o In
O °
Existing Roof &
c
Q U) w N
Attachment Only
a
2 o
OM LU
z C) Qco
a�
to_
�,.
U) (no o
L
DRAWING BY
rn:
city of Quinn Everett
43019 -:
DATEd
+•�*e
4...•"�
eat Ri 9 A
July 19, 2019
�-
ision
C NUMBER
Digitally signed by
John Calvert
!HWT NAME
Date: 2019.07.19
SITE PLAN
15:14:34 -06'00'
PAGE NUMBER
REVISION
PV3
A
LL
LL
O
0
z
Q _
�o
W
O
H ch
0q)
m ca
U
J in
Lu
0
y
LL
W
O
0
z
Q
U)
EL O
Q _
H
w u
J
0 M
U
_J (n
Q
H
W
0
U
M= • I •J
PV MODULE COUNT: 18 MODULES
# OF ATTACHMENT POINTS: 41 A
ARRAY AREA: Module Count x 17.51ft2 = 315.2ft2
ROOF AREA: 1271.Oft2
% OF ARRAY/ROOF: 24.8%
ARRAY WEIGHT: Module Count x 50lbs = 900.Olbs
DISTRIBUTED LOAD: Array Weight - Array Area = 2.86 Ibs/ft2
POINT LOAD: Array Weight _ Attachments = 22.Olbs/attachment
'rame Microrail
IMRAIL
Trinasolar 300 TSM-DD05A.05(II)
PV MODULE
(E) ROOF
MEMBRANE
UNIRAC SLIDERS AND
TRIMRAIL ROOF ATTACHMENTS
FLASHING
5/16" STAINLESS STEEL LAG BOLT
WITH 2-1/2" MIN. EMBEDMENT
AND FLAT WASHER
(E) BUILDING
STRUCTURE
Url Sunframe Microrail
Trinasolar 300 TSM-DD05A.05(II)
PV MODULE
(E) ROOF
MEMBRANE
UNIRAC SLIDERS
FLASHING
5/16" STAINLESS STEEL LAG BOLT
WITH 2-1/2" MIN. EMBEDMENT
AND FLAT WASHER
(E) BUILDING
STRUCTURE
PV MODULE (BEHIND TRIM RAIL)
Unirac Sunframe Microrail TRIM RAIL
T48" MAX. r r
MAX.
SFM Raised Seal Flashing
RACKING ATTACHMENTS TO BE
STAGGERED BY SHIFTING EACH Unirac Sunframe Microrail FRAME
SUBSEQUENT ROW OF ATTACHMENTS
ONE RAFTER OVER. H,
G
PV4
PORTRAIT
-'11�4
w RAVEN
s
1403 N RESEARCH WAY, BUILDING J
OREM, UT 84097
LANDSCAPE
800-377-4480
WWW. BLU ERAVENSOLAR.COM
ARRAY DETAIL, FRONT VIEW
Scale: 3/8" = V-0"
ROOF TYPE: Comp Shingle
ROOF FRAMING TYPE: Rafter
RAFTER OR TOP CHORD(TRUSS) 2x6 @ 24"O.C.
CEILING JOIST OR BOTTOM CHORD(TRUSS) 2x6 @ 24"O.C.
PORTRAIT
LANDSCAPE
,AY DETAIL, SIDE VIEW
Scale: 3/8" = V-0"
Structural upgrades required on all rafters that directly
support solar PV and that have spans more than 9'4'. (E )
Flat purlin does not count as a suffiient bearing and shall not
reduce span of rafters for upgrade purposes. 2x6 sister
upgrade required. See structural detail and calculations
package for additional info.
Sealed For
Existing Roof &
Attachment Only
Digitally signed by
John Calvert
Date: 2019.07.19
15:14:45 -06'00'
GitY CA
Wh90t Ridge
/ .. �:an Divis►on
CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF
ANYONE EXCEPT
BLUERAVENSOLAR NOR SHALL IT
BE DISCLOSED IN WHOLE OR IN
PART TO OTHERS OUTSIDE
RECIPIENTS ORGANIZATION,
EXCEPT IN CONNEC TION WITH THE
SALE AND USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE
WRITTEN PERMISSION OF
BLUERAVENSOLARLLC
NABCEP
CERTIFIED
PV INSTALLATION
PROFESSIONAL
Scott Gurney
# PV -011719-015866
CONTRACTOR:
BRS FIELD OPS
385.498.6700
DATE
July 19, 2019
PROJECT NUMBER
62660967
SHEET NAME
EQUIP. DETAIL
PAGE NUMBER REVISION
PV4 A
M
o
U
00
o
m
L
�
Z
_O
O
C
O
U
til
o
Q
c
W
V)
Q
rn
D
O
M
LJJ
Z
C)
Q
a�
C)
M
2
:n
C)
r
DRAWING BY
Quinn
Everett
DATE
July 19, 2019
PROJECT NUMBER
62660967
SHEET NAME
EQUIP. DETAIL
PAGE NUMBER REVISION
PV4 A
(E) RAFTERS
INSTALL END GROUP OF
FASTENERS WITHIN 6" OF
EACH END. (3) SCREWS MIN
1X DECKING OR SHEATHING
MINIMALLY NOTCH NEW �- (E) CEILING JOIST
SISTER RAFTER TO BEAR
DIRECTLY ON (F) TOP PLATE
OF WALL,
RAVEN Ne -
BLUE
- (N) SISTER MEMBER TO BEAR
DIRECTLY ON RIDGE BOARD
OR INSTALL SIMPSON A34
CLIP.
(N) SISTER MEMBER TO BE FULL
1403 N RESEARCH WAY, BUILDING J
OREM, UT 84097
800-377-4480
WWW.BLUERAVENSOLAR.COM
LENGTH, ATTACH TO (E) RAFTER Wt
CONFIDENTIAL - THE INFORMATION
SIMPSON SDW223GO SCREWS
HEREIN CONTAINED SHALL NOT BE
STAGGERED TOP AND BOTTOM @
USED FOR THE BENEFIT OF
16" O.C.
ANYONE EXCEPT
BLUERAVENSOLAR NOR SHALL IT
(E) FLAT PURLIN, DOES
BE DISCLOSED IN WHOLE OR IN
NOT COUNT AS
PART TO OTHERS OUTSIDE
SUFFICIENT
RECIPIENTS ORGANIZATION,
BEARING
EXCEPT IN CONNEC TION WITH THE
FASTENERS WITHIN 6" OF
SALE AND USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE
WRITTEN PERMISSION OF
BLUERAVENSOLAR LLC.
OPTION 1 - FULL LENGTH SISTER
SEE LETTER FOR UPGRADE LAP LENGTH AND SIZE,
NABC E P
INSTALL END GROUP OF
FASTENERS WITHIN 6" OF
CERTIFIED
EACH END. (3) SCREWS MIN
PV INSTALLATION
1X DECKING OR SHEATHING
PROFESSIONAL
Scott Gurney
(N) SISTER MEMBER TO BEAR
# PV -011719-015866
DIRECTLY ON RIDGE BOARD
OR INSTALL SIMPSON A34
CONTRACTOR:
CLIP.
(F) RAFTERS (N) SISTER MEMBER TO BE FULL
BRS FIELD OPS
LENGTH. ATTACH TO (E) RAFTER W/
385.498.6700
SIMPSON ED TOP A0 SCREWS
STAGGERED TOP AND BOTTOM Ca
16" O.C.
(E) FLAT PURLIN, DOES
M
NOT COUNT AS
C
SUFFICIENT
MINIMALLY NOTCH NEW (F) CEILING JOIST BEARING
Q
Q
SISTER RAFTER TO BEAR
0
DIRECTLY ON (E) TOP PLATE
OF WALL.
7
Y
OPTION 2 - OVERLAPPED SISTER
M
°O
SEE (.ETTFR FOR UPGRADE LAP LENGTH AND S17F,
z
O
O
(N) SISTER RAFTER
Sealed For
�
C:
o U
w
Existing Roof &
2
= (D
IV
C/)
Attachment Only
ofQ
rn o_
(N) SISTER RAFTER (E) RAFTER
SECTION A -A
U-
z
C/)I--
F—
U)
m o Q
}
SISTER UPGRADE OPTIONS
M rn =
U
S1
o
ALTERNATIVE FASTENER SCHEDULE: 10d NAILS STAGGERED TOP AND BOTTOM AT 6" O.C.
4
••Y,'
DRAWING
BY
'•
•.
wh$aSRdg1n
Everett
(Structural upgrades required on all rafters that directly
support solar PV and that have spans more than 9'-4". (E)
E
(Flat purlin does not count as a suffiient bearing and shall not
43019
p;;vision
e� d'� 7, 2019
reduce span pf rafters for upgrade purposes. 2x6 sister
�
upgrade required. See structural detail and calculations
PRO
TN UMBER
pa.
62660967
package for additional info.
SHEET NAME
Digitally signed by John
Calvert EQUIP. DETAIL
Date: 2019.07.19 15:15:10
-06'00' PAGE NUMBER MO
N
PV4
1 . ALL CONDUIT TO BE RAN AT LEAST 7/8" ABOVE ROOF SURFACE WHERE EXPOSED TO SUNLIGHT.
2. TERMINALS AND LUGS WILL BE TIGHTENED TO MANUFACTURER TORQUE SPECIFICATIONS (WHEN
PROVIDED) IN ACCORDANCE WITH NEC CODE 110.14(D) ON ALL ELECTRICAL CONNECTIONS.
3. CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND
ARE NOT MEANT TO LIMIT UP-SIZING AS REQUIRED BY FIELD CONDITIONS.
(E)125A MAIN SERVICE PANEL
(E)125A/2P MAIN BREAKER
(E
(E)125A / 2P
L
L
(E)LOADS
(N)25A/2P
Enphase IQ Combiner 3
UTILITY PV REC PV AC DISCONNECT X-IQ-AM1-240-3
METER 200A NON-FUSED (SOLAR LOADS ONLY)
LEVER BYPASS LOCKABLE, VISIBLE OPEN
METER SOCKET 30A, 240V, 2 -POLE
I I I. rG EGC --
120/240 VACF
60HZ
TO UTILITY
GRID I I I
PV BREAKER TO BE LOCATED OPPOSITE
END OF BUSSING FROM MAIN BREAKER
MAIN SERVICE PANEL
ADDITIONAL GROUND ROD
(E) GROUNDING (N) J' COPPER GROUND
ELECTRODE (S) ROD, 8 FT LONG, AT
LEAST 6' APART FROM
(E) GROUND ROD.
GEC INSTALLED PER
NEC 250.64. 6 AWG
SOLID COPPER GEC
N
A — [ (N)20A/
N G
G I� G -
Notes:
1)Verify or provide supplemental ground rod or
rods per 2017 NEC Art. 250.53(A)(2).
2) Natural Gas piping to be bonded s per 2017 NEC
Art. 250.104(B).
3)Bond P/V panels to the building Grounding
Electrode Svstem oer 2017 NEC Art. 690(A)•
INTERCONNECTION NOTES
1. ONE OF THE METHODS THAT FOLLOWS SHALL BE USED TO DETERMINE THE RATINGS OF
BUSBARS AND PANELBOARDS. (a) THE SUM OF 125 PERCENT OF THE INVERTER(S) OUTPUT
CIRCUIT CURRENT AND THE RATING OF THE OVERCURRENT DEVICE PROTECTING THE
BUSBAR SHALL NOT EXCEED THE AMPACITY OF THE BUS BAR. (b) WHERE TWO SOURCES,
ONE THE UTILITY AND THE OTHER AN INVERTER ARE LOCATED AT OPPOSITE ENDS OF A
BUSBAR THAT CONTAINS LOADS, THE SUM OF 125 PERCENT OF THE INVERTER(S) OUTPUT
CIRCUIT CURRENT AND THE RATING OF THE OVERCURRENT DEVICE PROTECTING THE
BUSBAR SHALL NOT EXCEED 120 PERCENT OF THE AMPACITY OF THE BUSBAR [NEC 705.121.
s
JUNCTION BOX
"A
(1) 10 AWG THHN/THWN-2, CU., BLACK (Ll) 18.0 A AC(2)
12 - 2 OF -B W/G, THHN/THWN-2, SOLID CU. MAX 9.0 A A
(1) 12 - 2 OF -B W/G, THHN/THWN-2, SOLID CU. MAX 9.0 A A
(1) 12-2TC-ER,THHN/THWN-2, CU. MAX 9.0 A A
C
J
(1) 10 AWG THHN/THWN-2, CU., RED (L2) 240 V ACA
240 V A
240 V A
j (1) 6 AWG BARE, CU (EGC) 240 V AC
OF -B USED FOR
(1) 10 AWG THHN/THWN-2,CU.,WHITE(N)
ENTIRE HOMERUN
JUNCTION BOX
p
(1) 10 AWG THHN/THWN-2, CU., GREEN (EGC)
(1) 3/4 INCH EMT EXTERIOR
(1) 3/4 INCH EMT EXTERIOR
INTERIOR
EXTERIOR
1 . ALL CONDUIT TO BE RAN AT LEAST 7/8" ABOVE ROOF SURFACE WHERE EXPOSED TO SUNLIGHT.
2. TERMINALS AND LUGS WILL BE TIGHTENED TO MANUFACTURER TORQUE SPECIFICATIONS (WHEN
PROVIDED) IN ACCORDANCE WITH NEC CODE 110.14(D) ON ALL ELECTRICAL CONNECTIONS.
3. CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND
ARE NOT MEANT TO LIMIT UP-SIZING AS REQUIRED BY FIELD CONDITIONS.
(E)125A MAIN SERVICE PANEL
(E)125A/2P MAIN BREAKER
(E
(E)125A / 2P
L
L
(E)LOADS
(N)25A/2P
Enphase IQ Combiner 3
UTILITY PV REC PV AC DISCONNECT X-IQ-AM1-240-3
METER 200A NON-FUSED (SOLAR LOADS ONLY)
LEVER BYPASS LOCKABLE, VISIBLE OPEN
METER SOCKET 30A, 240V, 2 -POLE
I I I. rG EGC --
120/240 VACF
60HZ
TO UTILITY
GRID I I I
PV BREAKER TO BE LOCATED OPPOSITE
END OF BUSSING FROM MAIN BREAKER
MAIN SERVICE PANEL
ADDITIONAL GROUND ROD
(E) GROUNDING (N) J' COPPER GROUND
ELECTRODE (S) ROD, 8 FT LONG, AT
LEAST 6' APART FROM
(E) GROUND ROD.
GEC INSTALLED PER
NEC 250.64. 6 AWG
SOLID COPPER GEC
N
A — [ (N)20A/
N G
G I� G -
Notes:
1)Verify or provide supplemental ground rod or
rods per 2017 NEC Art. 250.53(A)(2).
2) Natural Gas piping to be bonded s per 2017 NEC
Art. 250.104(B).
3)Bond P/V panels to the building Grounding
Electrode Svstem oer 2017 NEC Art. 690(A)•
INTERCONNECTION NOTES
1. ONE OF THE METHODS THAT FOLLOWS SHALL BE USED TO DETERMINE THE RATINGS OF
BUSBARS AND PANELBOARDS. (a) THE SUM OF 125 PERCENT OF THE INVERTER(S) OUTPUT
CIRCUIT CURRENT AND THE RATING OF THE OVERCURRENT DEVICE PROTECTING THE
BUSBAR SHALL NOT EXCEED THE AMPACITY OF THE BUS BAR. (b) WHERE TWO SOURCES,
ONE THE UTILITY AND THE OTHER AN INVERTER ARE LOCATED AT OPPOSITE ENDS OF A
BUSBAR THAT CONTAINS LOADS, THE SUM OF 125 PERCENT OF THE INVERTER(S) OUTPUT
CIRCUIT CURRENT AND THE RATING OF THE OVERCURRENT DEVICE PROTECTING THE
BUSBAR SHALL NOT EXCEED 120 PERCENT OF THE AMPACITY OF THE BUSBAR [NEC 705.121.
s
JUNCTION BOX
"A
Q2
)
BLUE RAYEN
1403 N RESEARCH WAY, BUILDING J
OREM, UT 84097
800-377-4480
WWW.BLUERAVENSOLAR.COM
CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF
ANYONE EXCEPT
BLUERAVENSOLAR NOR SHALL IT
BE DISCLOSED IN WHOLE OR IN
PART TO OTHERS OUTSIDE
RECIPIENTS ORGANIZATION,
EXCEPT IN CONNEC TION WITH THE
SALE AND USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE
WRITTEN PERMISSION OF
BLUERAVENSOLARLLC.
NABCEP
CERTIFIED
PV INSTALLATION
PROFESSIONAL
Scott Gurney
# PV -011719-015866
CONTRACTOR:
BRS FIELD OPS
385.498.6700
(18) Trinasolar 300 TSM-DD05A.05(II)
`JUNCTION BOX(S)
UL 1703 COMPLIANT
FOR WIRE SPLICING
(18) Enphase IQ7-60-2-US MICRO INVERTERS
ONLY - OPTIONAL IF
UL 1741 COMPLIANT
Q -CABLE (TC -ER) OR
9 MODULES MAX FOR ALL SUB -BRANCH
OF -B USED FOR
CIRCUIT(S) TO COMPLY WITH VRISE CALCS
ENTIRE HOMERUN
JUNCTION BOX
(1) CIRCUIT
-:F
Ll A L,
LZ
G G
OF 9 MODULES?
Q2
)
BLUE RAYEN
1403 N RESEARCH WAY, BUILDING J
OREM, UT 84097
800-377-4480
WWW.BLUERAVENSOLAR.COM
CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF
ANYONE EXCEPT
BLUERAVENSOLAR NOR SHALL IT
BE DISCLOSED IN WHOLE OR IN
PART TO OTHERS OUTSIDE
RECIPIENTS ORGANIZATION,
EXCEPT IN CONNEC TION WITH THE
SALE AND USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE
WRITTEN PERMISSION OF
BLUERAVENSOLARLLC.
NABCEP
CERTIFIED
PV INSTALLATION
PROFESSIONAL
Scott Gurney
# PV -011719-015866
CONTRACTOR:
BRS FIELD OPS
385.498.6700
SHEET NAME
Y
1949 ELEC. 3 LINE DIAG.
=
... `. PAGE NUMBER REVISION
eP PV5 A
ce)
o
CU
O
00
O
Y
Z
_O
LO
O
c O
O U
Iii
I.-_
Q
c a- WC/)
OW
>M
z
N CD CD Q
>_
W
[—
N W
M O =_
C/)
Fn
co
DRAWING BY
Quinn Everett
City
Of
DATE
vt,p/a�q.
July 19, 2019
oil,
PROJECT NUMBER
PROJECT
62660967
SHEET NAME
Y
1949 ELEC. 3 LINE DIAG.
=
... `. PAGE NUMBER REVISION
eP PV5 A
MUUULtSNtC.IFILAIIUNS IrInasoiar:m I1 )IVI-UUUSA.US(II)
RATED POWER (STC)
300 W
MODULE VOC
39.8 V DC
MODULE VMP
32.6 V DC
MODULE IMP
9.19 A DC
MODULE ISC
9.77 A DC
VOC CORRECTION
-0.29 %/°C
VMP CORRECTION
-0.39 %/°C
SERIES FUSE RATING
15 A DC
ADJ. MODULE VOC @ ASHRAE LOW TEMP
44.3 V DC
ADJ. MODULE VMP @ ASHRAE 2% AVG. HIGH TEMP
27.5 V DC
NULKUnvVtKItKJFtLlf-ILAIIUIVJ
tnpnaseIQ/-bU-Z-UJ
POWER POINT TRACKING (MPPT) MIN/MAX
22 - 48 V DC
MAXIMUM INPUT VOLTAGE
48 V DC
MAXIMUM DC SHORT CIRCUIT CURRENT
15 A DC
MAXIMUM USABLE DC INPUT POWER
350 W
MAXIMUM OUTPUT CURRENT
1 AAC
AC OVERCURRENT PROTECTION
20 A
MAXIMUM OUTPUT POWER
240 W
CEC WEIGHTED EFFICIENCY
97 %
r_n>,�::.�cn•�•aeras►•unll�a►+ir_�aa►�n�u�.i:�::.a
NOMINAL OPERATING AC VOLTAGE
240 V AC
NOMINAL OPERATING AC FREQUENCY
47- 68 HZ AC
MAXIMUM AC POWER
240 VA AC
MAXIMUM AC CURRENT
1.0 A AC
MAXIMUM OCPD RATING FOR AC MODULE
20 A AC
DESIGN LOCATION AND TEMPERATURES
TEMPERATURE DATA SOURCE ASHRAE 2% AVG. HIGH TEMP
STATE Colorado
CITY WHEAT RI DGE
WEATHER STATION SALISBURY WICOMICO CO AP
ASHRAE EXTREME LOW TEMP (°C) -14
ASHRAE 2% AVG. HIGH TEMP (°C) 33
SYSTEM ELECTRICAL SPECIFICATIONS CIR 1 CIR 2 CIR 3 CIR 4 CIR 5 CIR 6
NUMBER OF MODULES PER MPPT
DC POWER RATING PER CIRCUIT (STC)
TOTAL MODULE NUMBER
STC RATING OF ARRAY
AC CURRENT @ MAX POWER POINT (IMP
MAX. CURRENT (IMP X 1.25)
OCPD CURRENT RATING PER CIRCUIT
MAX. COMB. ARRAY AC CURRENT(IMP)
MAX. ARRAY AC POWER
9
2700
9
2700
%VRISE IQ7-9
VRISE SEC. 1(MICRO TO 160X)
32.4
1.18 241.18
18 MODULES
5400W DC
9.0
11.25
20
9.0
11.25
20
0.4S%
VRISE SEC. 3 (COMBINER BOX TO POI)
10
0.46 240.46
18.0
4320W AC
AC VOLTAGE RISE CALCULATIONS
DIST (FT)
VRISE(V) VEND(V)
%VRISE IQ7-9
VRISE SEC. 1(MICRO TO 160X)
32.4
1.18 241.18
0.49%
VRISE SEC. 2 (1BOX TO COMBINER BOX)
30
1.09 241.09
0.4S%
VRISE SEC. 3 (COMBINER BOX TO POI)
10
0.46 240.46
0.19%
TOTAL VRISE
AMB. TEMP. AMP. CORRECTION =
0.96
1.14%
PHOTOVOLTAIC AC DISCONNECT OUTPUT LABEL (NEC 690.54)
AC OUTPUT CURRENT 18.0 A AC
NOMINAL AC VOLTAGE 240 V AC
GROUNDING NOTES
1. A GROUNDING ELECTRODE SYSTEM IN ACCORDANCE WITH [NEC 690-47] AND
[NEC 250-50] THROUGH [NEC 250-601 SHALL BE PROVIDED. PER NEC,
GROUNDING ELECTRODE SYSTEM OF EXISTING BUILDING MAY BE USED AND
BONDED TO AT THE SERVICE ENTRANCE. IF EXISTING SYSTEM IS INACCESSIBLE,
OR INADEQUATE, OR IS ONLY METALLIC WATER PIPING, A SUPPLEMENTAL
GROUNDING ELECTRODE WILL BE USED AT THE INVERTER LOCATION
CONSISTING OF A UL LISTED 8 FT GROUND ROD WITH ACORN CLAMP.
2. THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM PHYSICAL
DAMAGE BETWEEN THE GROUNDING ELECTRODE AND THE PANEL (OR INVERTER) IF
SMALLER THAN #6 AWG COPPER WIRE PER NEC 250-646. THE GROUNDING ELECTRODE
CONDUCTOR WILL BE CONTINUOUS, EXCEPT FOR SPLICES OR JOINTS AT BUSBARS
WITHIN LISTED EQUIPMENT PER [NEC 250.64C.].
3. GROUNDING ELECTRODE CONDUCTORS SHALL BE NO LESS THAN #8 AWG AND
NO GREATER THAN #6 AWG COPPER AND BONDED TO THE EXISTING GROUNDING
ELECTRODE TO PROVIDE FOR A COMPLETE SYSTEM.
4. PV SYSTEM SHALL BE GROUNDED IN ACCORDANCE TO [NEC 250.21], [NEC TABLE
250.122], AND ALL METAL PARTS OR MODULE FRAMES ACCORDING TO [NEC
690.46].
5. MODULE SOURCE CIRCUITS SHALL BE GROUNDED IN ACCORDANCE TO [NEC
690.42].
6. THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT
THE REMOVAL OF A MODULE DOES NOT INTERRUPT A GROUNDED CONDUCTOR
TO ANOTHER MODULE.
7. EACH MODULE WILL BE GROUNDED USING THE SUPPLIED CONNECTIONS POINTS
IDENTIFIED IN THE MANUFACTURER'S INSTALLATION INSTRUCTIONS.
8. ENCLOSURES SHALL BE PROPERLY PREPARED WITH REMOVAL OF PAINT/FINISH
AS APPROPRIATE WHEN GROUNDING EQUIPMENT WITH TERMINATION
GROUNDING LUGS.
9. GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE, AND
GROUNDING DEVISES EXPOSED TO THE ELEMENTS SHALL BE RATED FOR DIRECT BURIAL
10. GROUNDING AND BONDING CONDUCTORS SHALL BE COPPER, SOLID OR
STRANDED, AND BARE WHEN EXPOSED.
11. EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZE ACCORDING TO [NEC
690.45] AND BEA MINIMUM OF #10AWG WHEN NOT EXPOSED TO DAMAGE (#6AWG
SHALL BE USED WHEN EXPOSED TO DAMAGE).
12. GROUNDING AND BONDING CONDUCTORS, IF INSULATED, SHALL BE COLOR
CODED GREEN (OR MARKED GREEN IF #4 AWG OR LARGER)
13. ALL CONDUIT BETWEEN THE UTILITY AC DISCONNECT AND THE POINT OF
CONNECTION SHALL HAVE GROUNDED BUSHINGS AT BOTH ENDS.
14. SYSTEM GEC SIZED ACCORDING TO [NEC 690.47], [NEC TABLE 250.661, DC
SYSTEM GEC SIZED ACCORDING TO [NEC 250.166], MINIMUM #8AWG WHEN
INSULATED, #6AWG WHEN EXPOSED TO DAMAGE.
15. EXPOSED NON-CURRENT CARRYING METAL PARTS OF MODULE FRAMES,
EQUIPMENTS, AND CONDUCTOR ENCLOSURES SHALL BE GROUNDED IN
ACCORDANCE WITH 250.134 OR 250.136(A) REGARDLESS OF VOLTAGE.
WIRING & CONDUIT NOTES
1. ALL CONDUIT SIZES AND TYPES, SHALL BE LISTED FOR ITS PURPOSE AND
APPROVED FOR THE SITE APPLICATIONS
2. BOLTED CONNECTION REQUIRED IN DC DISCONNECTS ON THE WHITE GROUNDED
CONDUCTOR (USE POLARIS BLOCK OR NEUTRAL BAR)
3. ANY CONNECTION ABOVE LIVE PARTS MUST BE WATERTIGHT. REDUCING WASHERS
DISALLOWED ABOVE LIVE PARTS, MEYERS HUBS RECOMMENDED
4. UV RESISTANT CABLE TIES(NOT ZIP TIES) USED FOR PERMANENT WIRE MANAGEMENT
OFF THE ROOF SURFACE IN ACCORDANCE WITH NEC 110.2,110.3(A -B). 300.4
5. SOLADECK JUNCTION BOXES MOUNTED FLUSH W/ROOF SURFACE TO BE USED FOR
WIRE MANAGEMENT AND AS FLASHED ROOF PENETRATIONS FOR INTERIOR CONDUIT
RUNS.
6. ALL PV CABLES AND HOMERUN WIRES BE TYPE USE -2, AND SINGLE -CONDUCTOR
CABLE LISTED AND IDENTIFIED AS PV WIRE, TYPE TC -ER, OR EQUIVALENT; ROUTED TO
SOURCE CIRCUIT COMBINER BOXES AS REQUIRED
7. ALL CONDUCTORS AND OCPD SIZES AND TYPES SPECIFIED ACCORDING TO [NEC
CONDUCTOR SIZE CALCULATIONS
MICROINVERTERTO
MAX. SHORT CIRCUIT CURRRENT (ISC) =
9.0AAC
JUNCTION BOX (1)
MAX. CURRENT (ISC X1.25) =
11.3 A AC
CONDUCTOR (TC -ER, COPPER (90°C)) =
12 AWG
CONDUCTOR RATING =
30 A
AMB. TEMP. AMP. CORRECTION =
0.96
ADJUSTED AMP. =
28.8 >
11.3
JUNCTION BOX TO
MAX. SHORT CIRCUIT CURRRENT (ISC) =
9.0 A AC
JUNCTION BOX (2)
MAX. CURRENT (ISC X1.25) =
11.3 A AC
CONDUCTOR (UF -B, COPPER (60°C)) =
12 AWG
CONDUCTOR RATING =
20 A
CONDUIT FILL DERATE =
1
AMB. TEMP. AMP. CORRECTION =
0.96
ADJUSTED AMP. =
19.2 >
11.3
JUNCTION BOX TO
MAX. SHORT CIRCUIT CURRRENT (ISC) =
9.0 A AC
COMBINER BOX (3)
MAX. CURRENT (ISC X1.25) =
11.3 A AC
CONDUCTOR (UF -B, COPPER (60°C)) =
12 AWG
CONDUCTOR RATING =
20 A
CONDUIT FILL DERATE =
0.8
AMB. TEMP. AMP. CORRECTION =
0.96
ADJUSTED AMP. =
15.36 >
11.3
COMBINER BOX TO
INVERTER RATED AMPS =
18.0 A AC
MAIN PV OCPD (15)
MAX. CURRENT ( RATED AMPS X1.25) =
22.5 A AC
CONDUCTOR (THWN-2, COPPER (75-C TERM.)) =
10 AWG
CONDUCTOR RATING =
35 A
CONDUIT FILL DERATE =
1
AMB. TEMP. AMP. CORRECTION =
0.96
ADJUSTED AMP. =
33.6 >
22.5
FAI
690.8] FOR MULTIPLE CONDUCTORS
8. ALL PV DC CONDUCTORS IN CONDUIT EXPOSED TO SUNLIGHT SHALL BE INSTALLED
AT LEAST 7/8" ABOVE THE ROOF SURFACE AND DERATED ACCORDING TO [NEC TABLE
310.15 (13)(2)(a), NEC TABLE 310.15(B)(3)(a),& NEC 310.15(13)(3)(c)].
9. EXPOSED ROOF PV DC CONDUCTORS SHALL BE USE -2, 90°C RATED, WET AND UV
RESISTANT, AND UL LISTED RATED FOR 600V, UV RATED SPIRAL WRAP SHALL BE
USED TO PROTECT WIRE FROM SHARP EDGES
10. PHASE AND NEUTRAL CONDUCTORS SHALL BE DUAL RATED THHN/THWN-2
INSULATED, 90°C RATED, WET AND UV RESISTANT, RATED FOR 600V
11. 4 -WIRE DELTA CONNECTED SYSTEMS HAVE THE PHASE WITH THE HIGHER
VOLTAGE TO GROUND MARKED ORANGE OR IDENTIFIED BY OTHER EFFECTIVE MEANS.
12. ALL SOURCE CIRCUITS SHALL HAVE INDIVIDUAL SOURCE CIRCUIT PROTECTION
13. VOLTAGE DROP LIMITED TO 2% FOR DC CIRCUITS AND 3% FOR AC CIRCUITS
14. NEGATIVE GROUNDED SYSTEMS DC CONDUCTORS SHALL BE COLOR CODED AS
FOLLOWS: DC POSITIVE- RED (OR MARKED RED), DC NEGATIVE- GREY (OR MARKED GREY)
15. POSITIVE GROUNDED SYSTEMS DC CONDUCTORS COLOR CODED:
DC POSITIVE- GREY (OR MARKED GREY), DC NEGATIVE- BLACK (OR MARKED BLACK) Wh
16. AC CONDUCTORS >4AWG COLOR CODED OR MARKED:
PHASE A OR L1- BLACK, PHASE B OR L2- RED, PHASE C OR L3- BLUE, NEUTRAL- Uil
WHITE/GRAY
USE -2 IS NOT INDOOR RATED BUT PV CABLE IS RATED THWN/THWN-2 AND MAY
BE USED INSIDE
" USE -2 IS AVAILABLE AS UV WHITE
17. RIGID CONDUIT, IF INSTALLED, (AND/OR NIPPLES) MUST HAVE A PULL BUSHING TO
PROTECT WIRES.
18. IF CONDUIT DETERMINED TO BE RAN THROUGH ATTIC IN FIELD THEN CONDUIT WILL
BE EITHER EMT, FMC, OR MC CABLE IF DC CURRENT COMPLYING WITH NEC 690.31, NEC
250.118(10). DISCONNECTING MEANS SHALL COMPLY WITH 690.13 AND 690.15
19, CONDUIT RAN THROUGH ATTIC WILL BE AT LEAST 18" BELOW ROOF SURFACE
COMPLYING WITH NEC 230.6(4) AND SECURED NO GREATER THAN 6' APART PER NEC
330.30(B).
*11�4
LU E RAVEN
1403 N RESEARCH WAY, BUILDING J
OREM. UT 84097
800-377-4480
WWW.BLUERAVENSOLAR COM
CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF
ANYONE EXCEPT
BLUERAVENSOLAR NOR SHALL IT
BE DISCLOSED IN WHOLE OR IN
PART TO OTHERS OUTSIDE
RECIPIENTS ORGANIZATION,
EXCEPT IN CONNEC TION WITH THE
SALE AND USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE
WRITTEN PERMISSION OF
BLUERAVENSOLAR LLC.
Z
0
Q
o
LL
Z
LU
Im
W
NABCEP
CERTIFIED
PV INSTALLATION
PROFESSIONAL
Scott Gurney
# PV -011719-015866
CONTRACTOR:
BRS FIELD OPS
385.498.6700
C
O
Cn
c
ry
L
Q
CU
CO
C
m
U)
N
L
O
M
O
CV
CA
O
V_
M
M
O
O
00
O
C8
_O
O
U
W
0
W
2
DRAtllC.9 BY
Quinn Everett
Division
DATE
July 19, 2019
PROJECT NUMBER
62660967
U
Y
�t
Ln
W
N_
W
2
W
I-
W
W
U
0
SHEET NAME
ELEC. CALCS.
PAGE NUMBER REVISION
PV6 I
A
ELECTRIC SHOCK HAZARD
TERMINALS ON THE LINE AND
LOAD SIDES MAY BE ENERGIZED
,_ _ IN THE OPEN POSITION —
DIRECT CURRENT
MAXIMUM VOLTAGE VDC
MAX CIRCUIT CURRENT AMPS
PHOTOVOLTAIC SYSTEM
ji DISCONNECT
RATED AC OUTPUT CURRENT A
NOMINAL OPERATING AC VOLTAGE V
WARNING
DUAL POWER SUPPLY
SOURCES: UTILITY GRID AND
PV SOLAR ELECTRIC SYSTEM
IWARNING
INVERTER OUTPUT CONNECTION
DO NOT RELOCATE
THIS OVERCURRENT
DEVICE
A ''
THIS EQUIPMENT FED BY MULTIPLE
SOURCES. TOTAL RATING OF ALL
OVERCURRENT DEVICES, EXCLUDING
MAIN SUPPLY OVERCURRENT
DEVICE. SHALL NOT EXCEED
AMPACITY OF BUSBAR.
PHOTOVOLTAIC
SYSTEM CONNECTED
PV AC DISCONNECT
LABEL 1
FOR PV DISCONNECTING MEANS WHERE ALL
TERMINALS OF THE DISCONNECTING MEANS
MAY BE ENERGIZED IN THE OPEN POSITION.
[NEC 690.13(B), NEC 705.22]
LABEL 2
AT EACH DC DISCONNECTING MEANS,
INCLUDING THE DC DISCONNECT AT THE
INVERTER.
[NEC 690.53, NEC 690.13(B)]
LABEL 3
AT POINT OF INTERCONNECTION, MARKED AT
AC DISCONNECTING MEANS.
[NEC 690.54, NEC 690.13 (B)]
LABEL 4
AT POINT OF INTERCONNECTION FOR
EQUIPMENT CONTAINING OVERCURRENT
DEVICES IN CIRCUTS SUPPLYING POWER TO A
BUSBAR OR CONDUCTOR SUPPLIED FORM
MULTIPLE SOURCES, EACH SERVICE
EQUIPMENT AND ALL ELECTRIC POWER
PRODUCTION SOURCE LOCATIONS [NEC
705.12(B)(3)]
LABEL 5
PLACED ADJACENT TO THE BACK -FED BREAKER
FROM THE INVERTER IF TIE IN CONSISTS OF
LOAD SIDE CONNECTION TO BUSBAR.
[NEC 705 12(B)(2)(3)(b)]
LABEL 6
(ONLY IF 3 OR MORE SUPPLY SOURCES TO
A BUSBAR)
SIGN LOCATED AT LOAD CENTER IF IT
CONTAINS 3 OR MORE POWER SOURCES.
[NEC 7-05.12(B)(2)(3)(C)]
LABEL 10
SIGN LOCATED AT RAPID SHUT DOWN
DISCONNECT SWITCH [NEC 690.56(C)(3)].
LABEL 12
PLACARD TO BE PLACED AT THE MAIN
BILLING METER PER XCEL ENERGY.
LABEL 13
PLACARD TO BE PLACED AT AC
DISCONNECT PER XCEL ENERGY.
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
TURN RAPID SHUTDOWN
SWITCHTOTHE
'OFF' POSITION TO sawea^ttc
SHUT DOWN PV SYSTEM wnwas
AND REDUCE
SHOCK HAZARD
IN THEARRAY
TURN RAPID SHUTDOWN SWITCH
TO TNE'OFF POSITION
TO SHUT DOWN CONDUCTORS ------
OUTSIDE THE ARRAY
CONDUCTORS WITHIN
THEARRAYREMAIN
ENERGIZED M SUNLIGHT
NO DC WIRES PRESENT
RAPID SHUTDOWN TEST
NOT REQUIRED
LABELING NOTES
1 LABELS CALLED OUT ACCORDING TO ALL COMMON CONFIGURATIONS ELECTRICIAN TO
DETERMINE EXACT REQUIREMENTS IN THE FIELD PER CURRENT NEC AND LOCAL CODES AND
MAKE APPROPRIATE ADJUSTMENTS.
2 LABELING REQUIREMENTS BASED ON THE 2017 NATIONAL ELECTRIC CODE, OSHA STANDARD
19010.145, ANSI Z535.
3. MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION
4, LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED [NEC
110.21)
5. LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8", WHITE ON RED BACKGROUND; REFLECTIVE,
AND PERMANENTLY AFFIXED [IFC 605.11.1.1]
LABEL 7
AT DIRECT-CURRENT EXPOSED RACEWAYS, CABLE TRAYS, COVERS AND ENCLOSURES OF
JUNCTION BOXES, AND OTHER WIRING METHODS; SPACED AT MAXIMUM 1OFT SECTION OR
WHERE SEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS, OR FLOORS.
[NEC 690.31(G)(3&4)]
LABEL 8
FOR PV SYSTEMS THAT SHUT DOWN THE ARRAY
AND CONDUCTORS LEAVING THE ARRAY
SIGN TO BE LOCATED ON OR NO MORE THAN 3
FT AWAY FROM SERVICE DISCONNECTING
MEANS TO WHICH THE PV SYSTEMS ARE
CONNECTED AND SHALL INDICATE THE
LOCATION OF ALL IDENTIFIED RAPID SHUTDOWN
SWITCHES IF NOT AT THE SAME LOCATION.
[NEC 690.56(C)(1)(A)]
LABEL 9
FOR PV SYSTEMS THAT ONLY SHUT DOWN
CONDUCTORS LEAVING THE ARRAY:
SIGN TO BE LOCATED ON OR NO MORE THAN 3
FT AWAY FROM SERVICE DISCONNECTING
MEANS TO WHICH THE PV SYSTEMS ARE
CONNECTED AND SHALL INDICATE THE
LOCATION OF ALL IDENTIFIED RAPID SHUTDOWN
SWITCHES IF NOT AT THE SAME LOCATION
[NEC 690.56(C)(1)(B)]
LABEL 11
SIGN LOCATED AT AC COMBINER BOX FOR
ALL MICRO -INVERTER /AC MODULE
INSTALLS (IF APPLICABLE).
LABELING DIAGRAM FOR MICRO INV
MAIN SERVICE PANEL
& ARN9411ry'i
POWER TO THIS BUILDING IS ALSO
SUPPLIED FROM MAIN DISTRIBUTION
UTILITY DISCONNECT LOCATED
LABEL 16
PERMANENT DIRECTORY TO BE LOCATED AT
SOLAR ARRAY RAPID SHUTDOWN SWITCH
DENOTING THE LOCATION OF THE SERVICE
EQUIPMENT LOCATION IF SOLAR ARRAY RAPID
SHUT DOWN DISCONNECT SWITCH IS NOT
GROUPED AND WITHIN LINE OF SITE OF MAIN
SERVICE DISCONNECTING MEANS.
[NEC 705.10]
—
LABEL 15
!1� WARNING
PERMANENT DIRECTORY TO BE LOCATED AT MAIN
A WARNNG
PERMANENT DIRECTORY TO BE LOCATED AT
POWER TO THIS BUILDING IS ALSO SUPPLIED
MAIN SERVICE EQUIPMENT LOCATION IF ALL
MAIN DISTRIBLTnONUTILITY DISCONNECT(S)
ELECTRICAL POWER SOURCE DISCONNECTING
POWER TO THIS BUILDING IS ALSO SUPPLIED
MEANS SOLAR ARRAY RAPID SHUTDOWN
FROM A ROOF MOUNTED SOLAR ARRAY WITH
GROUPED AND WITHIN LINE OF SITE OF MAIN
A RAPID SHUTDOWN DISCONNECTING MEANS
SWITCH) ARE GROUPED AND IN LINE OF SITE OF
GROUPED AND LABELED WITHIN LINE OFSITE
MAIN SERVICE DISCONNECTING MEANS.
AND 10 W OF THIS LOCATION.
[NEC 690.56(C) & NEC 705.10].
& ARN9411ry'i
POWER TO THIS BUILDING IS ALSO
SUPPLIED FROM MAIN DISTRIBUTION
UTILITY DISCONNECT LOCATED
LABEL 16
PERMANENT DIRECTORY TO BE LOCATED AT
SOLAR ARRAY RAPID SHUTDOWN SWITCH
DENOTING THE LOCATION OF THE SERVICE
EQUIPMENT LOCATION IF SOLAR ARRAY RAPID
SHUT DOWN DISCONNECT SWITCH IS NOT
GROUPED AND WITHIN LINE OF SITE OF MAIN
SERVICE DISCONNECTING MEANS.
[NEC 705.10]
—
LABEL 17
!1� WARNING
PERMANENT DIRECTORY TO BE LOCATED AT MAIN
SERVICE EQUIPMENT DENOTING THE LOCATION
POWER TO THIS BUILDING IS ALSO SUPPLIED
OF THE PV RAPID SHUTDOWN SYSTEM
FROM ROOF MOUNTED SOLAR ARRAY. SOLAR
DISCONNECTING MEANS IF SOLAR ARRAY RAPID
ARRAY RAPID SHUTDOWN DISCONNECT IS
SHUT DOWN DISCONNECT SWITCH IS NOT
LOCATED OUTSIDE NEXT TO UTILITY METER.
GROUPED AND WITHIN LINE OF SITE OF MAIN
SERVICE DISCONNECTING MEANS. [NEC 705 10,
NEC 690.56(C)(1)]
EXISTING SUB PANEL PV COMBINER
OO (IF WHERE POINT OF SUBPANEL -
OO NTERCONNECTION AC DISCONNECT IF USED TO COMBINE AC JUNCTION BOX
12 13 IS MADE) (IF REQ. / INSTALLED) PV OUTPUT CIRCUITS OR AC COMBINER BOX
0 o O&O4 O O O O O
D D O IF BREAKER USED 13 10 O
15 OR 17
&
OR PLACARD O O4 16 O
O IF BREAKER USE ,o
° O(ONLY IF PV
INTERCONNECTION
CONSISTS OF LOA 11
SIDE BREAKER)
LABELING DIAGRAM FOR STRING INV. / DC OPTIMIZER INV..
MAIN SERVICE PANEL
EXISTING SUB PANEL PV COMBINER INVERTER (S)
O13 (IF WHERE POINT OF SUBPANEL -
INTERCONNECTION AC DISCONNECT IF USED TO COMBINE
O
12 IS MADE) (IF REQ. / INSTALLED) PV OUTPUT CIRCUITS
Q &O
a a IF BREAKER USED O lO O O
°oma gORn OgO 16 13 O
U 15 UUV7 IF BREAKER USE OR 17 ,
OR PLACARD O 2 of
5 O O
(ONLY IF PV6
(ONLY IF PV
INTERCONNECTION1 D O
INTERCONNECTION
CONSISTS OF LOA CONSISTS OF LOA
SIDE BREAKER) SIDE BREAKER)
INTEGRATED DC DISCONNECT
JUNCTION BOX
OR COMBINER BOX
7C—)]
city of
wheat Ridge
Division
`ELECTRICAL DIAGRAMS SHOWN ABOVE IS FOR LABELING PURPOSES ONLY. NOT AN ACTUAL REPRESENATION OF EQUIPMENT AND CONNECTIONS TO BE INSTALLED. LABEL LOCATIONS
PRESENTED MAY VERY DEPENDING ON TYPE OF INTERCONNECTION METHOD AND LOCATION PRESENTED ON PV5 OF 3 LINE DIAGRAM. PV5 LINE DIAGRAM TO REFLECT ACTUAL
REPRESENTATION OF PROPOSED SCOPE OF WORK.
Nor-
PLUE
RAVEN
1403 N RESEARCH WAY, BUILDING J
OREM, UT 84097
800-377-4480
WWW.BLUERAVENSOLAR.COM
CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF
ANYONE EXCEPT
BLUERAVENSOLAR NOR SHALL IT
BE DISCLOSED IN WHOLE OR IN
PART TO OTHERS OUTSIDE
RECIPIENTS ORGANIZATION,
EXCEPT IN CONNEC TION WITH THE
SALE AND USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE
WRITTEN PERMISSION OF
BLUERAVENSOLARLLC
NABCEP
CERTIFIED
PV INSTALLATION
PROFESSIONAL
Scott Gurney
# PV -011719-015866
(I BRS FIELD
385.498.6700 S
DRAWING BY
Quinn Everett
TE July 19, 2019
PROJECT NUMBER
62660967
SHEET NAME
LABELS
PAGE NUMBER REVISION
PV8 A
M
('7
CD
O
00
O
m
Z
O
Q
c
o
0
°
U
W
O
LL
z
Z
W
f=
U)
m
C
C/)
M
CVS
rn
O
()f
W
DRAWING BY
Quinn Everett
TE July 19, 2019
PROJECT NUMBER
62660967
SHEET NAME
LABELS
PAGE NUMBER REVISION
PV8 A
Enphase i+ icrcrinveriers
Enphase
a
To learn more abort Enphase offerings, visit enphase.corn
The high-powered smar_ grid -ready
Enpha> e IQ 7 ?v icro- aid Enphase IQ 7¢ MiCro—
dramatically simplify tie installation process while
achieving the highest system efficiency.
Part of tete Enphase IQ System, the Its 7 and
IQ 7-r Microinverters integrate with the Enphase
Ifs Envoy—, Enphase IQ Battery—, and the Enphase
Enlighten' mcr,steoring and analysis software.
IQ Series Microinverters extend the reliability
standards set forth by pCevious generations and
undergo over a millio,7 hours of power -on testing,
enabling Enphase to provide an industry-leading
warranty of up to 25 years -
Easy to Install
Lghtweight .and simple
Faster installation with improved, ighter two -wire cabling
Built-in rapid shutdown compliant (NEC 2014 & 2017)
apt rrized for high powered 6th-c,4l and?2-ceil$ modules
More than a rinkillion hours of testing
Class II double -insulated enclosure
UL listed
Smart Grad Ready
r « •s
freclluencyTide-through
Reimcte4y updates to respond to changing
grid requirements
Configarable for grid profiles
Meets CA Rule 21 (LIL 1741 -SA)
The IQ 7+ Mi cm vs regAiired to xuppan 72 -cell module-.
l�1/�*�4il�Zl�i"►1 �I
Enphase IQ 7 and IQ 7+ Microinverters
INPUT DATA (DC) IQ7-60-2-US / IQ7-60-B-US IQ7PLUS-72-2-US / IQ7PLUS-72-B-lJS
Commonly used module pairings"
235 W - 350 W +
235 W- 440 W +
Module compatibility
60 -cell PV modules only
60 -cell and 72 -cell PV modules
Maximum input DC voltage
48 V
60V
Peak power tracking voltage
27 V -37 V
27 V - 45 V
Operating range
16 V- 48 V
16V -60V
Min/ Max start voltage
22 V ! 48 V
22 V/ 60V
Max DC short circuit current (module Isc)
15A
15A
Overvottage class DC port
II
11
DC port backfeed current
0 A
0 A
PV array configuration
1 x 1 ungrounded array; No additional
DC side protection required:
AC side protection requires max 20A per branch circuit
OUTPUT DATA (AC)
IQ 7 Microinverter
IQ 7+ Microinverter
Peak output power
250 VA
295 VA
Maximum continuous output power
240 VA
Disconnecting means
290 VA
Nominal (L -L) voltage/range2
240V/
208V/
240V/ 208 V/
Compliance
211-264 V
183-229V
211-264V 183-229 V
Maximum continuous output current
1.0 A (240 V)
1.15 A (208 V)
1.21 A (240 V) 1.39 A (208 V)
Nominal frequency
60 Hz
60 Hz
Extended frequency range
47 - 68 Hz
47 - 68 Hz
AC short circuit fault current over 3 cycles
5.8 Arms
5.8 Arms
Maximum units per 20 A (L -L) branch circuit'
16 (240 VAC)
13 (208 VAC)
13 (240 VAC) 11 (208 VAC)
Overvoftage class AC port
III
III
AC port backfeed current
0 A
0 A
Power factor setting
1.0
1.0
Power factor (adjustable)
0.7 leading ...
0.7 lagging
0.7 leading ... 0.7 lagging
EFFICIENCY
@240 V
(„x1208 V
x1240 V1x208 V
Peak CEC efficiency
97.6 %
97.6 ;
9 7. 5 97.3 %
CEC weighted efficiency
97.0 `i
970 F-
970' 97.0 k
MECHANICAL DATA
Ambient temperature range -40°C to +65°C
Relative humidity range 4% to 100`ro (condensing)
Connectortype (IQ7-60-2-US& IQ7PLUS-72-2-US) MC4 (or Amphenol H4 UTX with additional Q -DCC -5 adapter)
Connector type (IQ7-60-B-US & IQ7PLUS-72-B-US) Friends PV2 (MC4 intermateable).
Adaptors for modules with MC4 or UTX connectors:
PV2 to MC4: order ECA -S20 -S22
PV2 to UTX: order ECA -S20 -S25
Dimensions (WxHxD) 212 mm x 175 mm x 30.2 mm (without bracket)
Weight 1.08 kg (2.38 lbs)
Cooling Natural convection - No fans
Approved for wet locations Yes
Pollution degree P D3
Nor -
BLUE RAVEN
1403 N RESEARCH WAY, BUILDING J
OREM. UT 84097
800-377-4480
WWW BLUERAVENSOLAR.COM
CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF
ANYONE EXCEPT BLUE RAVEN
SOLAR NOR SHALL IT BE
DISCLOSED IN WHOLE OR IN PART
TO OTHERS OUTSIDE RECIPIENTS
ORGANIZATION, EXCEPT IN
CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE
WRITTEN PERMISSION OF BLUE
RAVEN SOLAR LLC.
NABCEP
CERTIFIED
PV INSTALLATION
PROFESSIONAL
Scott Gurney
# PV -011719-015866
CONTRACTOR:
BRS FIELD OPS
385.498.6700
Enclosure
Class 11 double -insulated, corrosion resistant polymeric enclosure
Environmental category/ UV exposure rating
NEMA Type 6! outdoor
FEATURES
Communication
Power Line Communication (PLC)
City O
Monitoring
Enlighten Manager and M,yEnlighten monitoring options.
Both options require installation of an Enphase IQ Envov.
RI
Disconnecting means
The AC and DC connectors have been evaluated and approved by UL for use as the load -break
v4t,,ot
disconnect required by NEC 690.
Compliance
CA Rule 21 (UL 1741 -SA)
au r9ire9 pivtst
UL 62109-1, UL1741/IEEE1547, FCC Part 15 Class B, ICES -0003 Class B,
CAN/CSA-C22.2 NO. 107.1-01
This product is UL Listed as PV Rapid Shut Down Equipment and conforms with NEC -2014 and
NEC -2017 section 690.12 and C22.1-2015 Rule 64-218 Rapid Shutdown of PV Systems, for AC
and DC conductors, when installed according manufacturer's instructions.
1. No enforced w/AC rano. See the compatbiviv calculator at �t is/lenphase.com/en-us/Su0I)oi Vmodnle-compatibility.
2 Nominal �roliaye range ran be extended beyond norn:nai =f reyu=red b}'the ut,l�iy.
3. Limns may vary. Refer to local requirencwsto define the numbei of mlcroinverters pet branch n your area.
To learn more about Enphase offerings, visit enphase.com V EN PHAS E.
.:01n El Pa_�,,- F_)'.fi.� ifs ,yeroec.. !.xei a,l,o 1,:n z� 3te thl'_ry,_-; b.-��.
SHEET NAME
SPEC SHEET
PAGE NUMBER REVISION
SS 0
Enphase Networking
CombinerEnphase
IQ
(X-IQ-AM1-240-3)
4 Y+
IM
SI
U�
LISTED
To learn more about Enphase offerings, visit enphase.com
The Enphase IQ Combiner 3' With Enphase
IQ Envoy" conso' dates nterconnection
equipment nto a sing e enclosure and
stream' nes PV and storage insta' at ons by
prop/ d ng a consistent, pre -w red so!ut'on for
res'denta appcat':ons. It o-fers up to ?our
2 -pole input circuits and Eaton BR ser es
busbar assembly.
Smart
Includes IQ Envoy for communication
and control
Flexible networking supports Wi-Fi,
Ethernet, or cellular
Optional AC receptacle available for PLC
bridge
Provides production metering and optional
consumption monitoring
Simple
Reduced size from previous combiner
Centered mounting brackets support single
stud mounting
Supports back and side conduit entry
Up to four 2 -pole branch circuits for 240 VAC
plug-in breakers (not included)
80 Atotal PV or storage branch circuits
Reliable
DurableINRTL certified NEMAtype
3R enclosure
Five-year warranty
UL listed
n ENPHASE.
Enphase IQ Combiner 3
1403 N RESEARCH WAY, BUILDING J
MODEL NUMBER OREM, UT 84097
IQ Combiner 3 X-IQ-AM1-240-3 IQ Combiner 3 with Enphase IQ Envoy- printed circuit board for integrated revenue grade PV 800-377-4480
production metering (ANSI C12.20 +/-0.5 %) and optional* consumption monitoring (+/-2.5'x). VWVW.BLUERAVENSOLAR.COM
ACCESSORIES and REPLACEMENT PARTS (not included, order separately)
Enphase Mobile Connect CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
CELLMODEM-03 (4G / 12 -year data plan) Plug and play industrial grade cellular modem with data plan for systems up to 60 USED FOR THE BENEFIT OF
CELLMODEM-01 (3G / 5 -year data plan) microinverters. (Available in the US, Canada, Mexico, Puerto Rico, and the US Virgin Islands, ANYONE EXCEPT BLUE RAVEN
CELLMODEM-M1 (4G based LTE -M 15 -year data plan) where there is adequate cellular service in the installation area.) SOLAR NOR SHALL IT BE
Consumption Monitoring* CT DISCLOSED IN WHOLE OR IN PART
CT -200 -SPLIT Split core current transformers enable whole home consumption metering (+/- 2.5`m). TO OTHERS OUTSIDE RECIPIENTS
Circuit Breakers Supports Eaton BR210, BR215, BR220, BR230, BR240, BR250, and BR260 circuit breakers. ORGANIZATION, EXCEPT IN
CONNECTION WITH THE SALE AND
BRK 10A-2-240 Circuit breaker, 2 pole, 10A, Eaton BR210
BRK-15A-2-240 Circuit breaker, 2 pole, 15A, Eaton BR215 USE THE RESPECTIVE
BRK-20A-2P-240 Circuit breaker, 2 pole, 20A, Eaton BR220 EQUIPMENT, WITHOUT THE
WRITTEN PERMISSION OF BLUE
EPLC-01 Power line carrier (communication bridge pair), quantity 2 RAVEN SOLAR LLC.
XA-PLUG-120-3 Accessory receptacle for Power Line Carrier in IQ Combiner 3 (required for EPLC-01)
XA-ENV-PCBA-3 Replacement IQ Envoy printed circuit board (PCB) for Combiner 3 NABCEP
ELECTRICAL SPECIFICATIONS
_.v...
Rating Continuous duty CERTIFIED
System voltage 120, 240 VAC, 60 Hz PV INSTALLATION
Eaton BR series busbar rating 125 A PROFESSIONAL
Max. continuous current rating (output to grid) 65A Scott Gurney
# PV -011719-015866
Max. fuse/circuit rating (output) 90A
Branch circuits (solar and/or storage) Up to four 2 -pole Eaton BR series Distributed Generation (DG) breakers only (not included) CONTRACTOR:BRS FIELD OPS
Max. continuous current rating (input from PV) 64A
385.498.6700
Max. total branch circuit breaker rating (input) SOA of distributed generation / 90A with IQ Envoy breaker included
Production Metering CT 200 A solid core pre-installed and wired to IQ Envoy
MECHANICAL DATA
Dimensions (WxHxD) 49.5 x 37 5 x 16.8 cm ti19 5" x 14 75' x,5,63') Height is 21 06 53.5 cm with mounting brackets).
Weight 7.5 kg (16.5 lbs)
Ambient temperature range -40° C to +46° C (-400 to 115° F)
Cooling Natural convection, plus heat shield
Enclosure environmental rating Outdoor, NRTL-certified, NEMA type 3R, polycarbonate construction
'Vire sizes 20 A to 50 A breaker inputs: 14 to 4 AWG copper conductors
60 A breaker branch input: 4 to 1/0 AWG copper conductors
Main lug combined output: 10 to 2/0 AWG copper conductors
Neutral and ground: 14 to 1/0 copper conductors
Always follow local code requirements for conductor sizing.
Altitude To 2000 meters (6.560 feet)
INTERNET CONNECTION OPTIONS
Integrated wi-FI 802.11b/g/n
Ethernet Optional, 802.3, Cat5E (or Cat 6) UTP Ethernet cable (not included)
Cellular Optional, CELLMODEM-01 (3G) or CELLMODEM-03 (4G) or CELLMODEM-M1 (4G based LTE -M)
COMPLIANCE (not included)
City of
Compliance, Combiner UL 1741
CAN/CSA C22.2 No 107.1 VVheat Ridge
47 CFR, Part 15, Class B, ICES 003
Production metering: ANSI C12.20 accuracy class 0.5 (PV production) uii n9 Division
Compliance, IQ Envoy UL 60601-1/CANCSA 22.2 No. 61010-1
* Consumption monitoring is required for Enphase Storage Systems. y A �4m V 1VMWY6 � ^
To learn more about Enphase offerings, visit enphase.com
z ENPHASE.
SHEET NAME
SPEC SHEET
PAGE NUMBER REVISION
SS 0
'dlcmc Multi Solutions
•
0 CELL
!. • • k �i
i
19.2%
POVdERRANC:E
TSM-DD05A.08(II)
MAXIMUM EFFICIENCY
TSM-DD05A.05(II)
Maximize limited space with top -end efficiency
U;ARCNSiiiN50i F*l dfJGISL F;meNin<hes;
3511.36
Jr to '9;lM`n1power density
(A -A)
Peak "ower'aiatts-Fr"..,(Wp)'
_Ow'ITC ima1 coe('( -Jeri tS tufi greater energy produt t cr c"'I `'` "..
0 H + 5
285
pplating temperatures
POSITIVE POWER TOLERANCE
300
305
310
315
Highly reliable due to stringent quality control
Photovoltaic Technology Cable 4.Orrma (0-006 mches2),
Uvt-:i 3;' n lic(ae teats WV, I �, N ej
-fib irf )e'tt11t )t1 _ i 1-�1+{I tS 1 Y't d!i' ie 3ft.,.1
O_+5
,+ (?n . ,e rts_;r.j r__cps !>V0i beyond rRrtifitrition reguirFmentS
rtirrehtnsr.�scir,.nxispr�ci+� t�,�uiar en=;r
we bere�eclosecxeeratiar, With carparne s a
TEMPERATURE RATINGS
• HD reSh,,ant
iti(,.d to ,i-let,Trrm 1,A,ir now ?rOiwfr ii,".
31.4
100�1,';: Fi.. tlxiblE':Irs("}eo or
Prj (7i Cf tae l5 tc 0"" a1 cter the.
32.2
32.5
:vun't Trina i� aniP to provide Pxter onal wivic,
32.9
- Selective ernitter, advanced surface texturing
it?4-,1 Il ttel#JnIF3 t?L�i ITldrk{t anfl i;Ij;)+.t'mE'!11
Maximum Power Current -l- (A)
8.76
,:iw Ffi{;avattda. ralia0le pr�idud5 wl'th the-.',3ckmg
8,97
9.01
'.�# Trinq a a 5#rOng ik3r'LatY`e py'^t n -at. yJF are
�tr:rrnit[ �U )'xlitC�ii 1 ra„,K ,tttrt-,ally
9.19
Certified to withstand the most challenging
hfi coilab€tr, „bvttiirt,talles.de.-frtpGr�..
9.46
environmental conditions
and p cs Pa�-tner5,
38.4
38.5
38.9
39.6
4',i10 I jd w r;d r- I
40.0
40.2
4')0 P a' 'law 10aC
Comprehensive Products
9.24
3-j iTxn hdll StOneS dt ,� Kr -1,'
And System Certificates
9.66
9.68
it( .,'ILCI(I73Q1iJl.7Q31lEthl7(}3.1tEt.6?'I€�
9.85
9.94
15(;9001: i�u.�3itpMa��agementSyS#err.
Madule Efficiency rg-, (%)
16.8
15i314C0 Eavrc. n�eratalMaitagem�-r# Sj tem
17.4
111.7
(SOI=1 i�{,e t,reenh�uSP gaSr,Emi :ran, Ve ifitai+0l�
18.3
18.6
01-ISA<ii�Jt>1:01 :)at+anHecl-handSdfety
19.2
c. C 1 Ai E it'ilt7ftrm' CEH TP is 3 ',
Mare mert'�tem
NrjjL
LINEAR PERFORMANCE WARRANTY
+weal®. c�w n
Una
10 Year Product Warranty• 25 Year Linear Power Warrant,
-------_--
._. 'V' u[
In..
THnasolar
♦1L A l
PFUiEx,__
POVdERRANC:E
TSM-DD05A.08(II)
280-315W
TSM-DD05A.05(II)
'', 275-31OW
U;ARCNSiiiN50i F*l dfJGISL F;meNin<hes;
3511.36
Weight
(A -A)
Peak "ower'aiatts-Fr"..,(Wp)'
35.';3$ 992r39.7
Back Viiew
ELECTRICAL DATA (STC)
rd -k-
=t .
Monocrystalline 156 75 * 156.75 mm (6 inches)
Cell Orientation
60 cells (6 > 10)
Module Dimensions
3511.36
Weight
(A -A)
Peak "ower'aiatts-Fr"..,(Wp)'
275
2eO
285
290
295
300
305
310
315
Power Output Tolerance -P>~.,. (W)
Photovoltaic Technology Cable 4.Orrma (0-006 mches2),
1000 Irwin (39.4inches)
Connector
O_+5
Fire Type
Type 1 or Type 2
TEMPERATURE RATINGS
MAXIMUM RATINGS
Maximum Power Voltaire -v ' (V)
31.4
31.7
31.8
32.2
32.5
32.6
32.9
33.1
33.3
Maximum Power Current -l- (A)
8.76
8.84
8,97
9.01
9.08
9.19
9.28
9.37
9.46
Open Circuit Noltage-V,c(v)
38.4
38.4
38.5
38.9
39.6
39.8
40.0
40.2
405
Short Circuit CurrentdI (A.)
9.24
9.42
951
9.66
9.68
9.77
9.85
9.94
10.0
Madule Efficiency rg-, (%)
16.8
17.1
17.4
111.7
18.0
18.3
18.6
18.9
19.2
c. C 1 Ai E it'ilt7ftrm' CEH TP is 3 ',
°C AIF NMS
NrjjL
R�s...C� tt>eia sr. c3?s.
ELECTRICAL DATA (NOCT)
rd -k-
=t .
Monocrystalline 156 75 * 156.75 mm (6 inches)
Cell Orientation
60 cells (6 > 10)
Module Dimensions
3511.36
Weight
(A -A)
g Maximum Power Prr e('Np)
205
209
212
216
220
223
227
231:
235
i
Photovoltaic Technology Cable 4.Orrma (0-006 mches2),
1000 Irwin (39.4inches)
Connector
Trina T54
Fire Type
Type 1 or Type 2
TEMPERATURE RATINGS
MAXIMUM RATINGS
Maximum Power voltage -V (V)
29.1
29.4
295
29.9
30.1
302
30.5
30.7
30.9
Maximum Power Current+iA)
7.04
7.10
7.21
724
7.30
7.38
746
753
7,60
Open Circuit Voltage V:z(V)
357
35.7
35.8
36.2
36.8
37.0
37.2
37.4
37.6
ShortCtrcustCurrent-t, (A)
7.45
7.61
768
780
7.82
7.89
7.95
8-01
810
tai y,�tt�+a; I*',y '.. lft C Tf,nDe'"v'."vI
Q':,'Nirt�SiN'Pltrttr}
<t�u,rTs oP vc rr; i, rival
w
G
}
v'�iagx(Yi
I, VCURVES GP FV ti§vNUi.ES3ViS�'v';
All,
MECHANICAL )ATA
rd -k-
=t .
Monocrystalline 156 75 * 156.75 mm (6 inches)
Cell Orientation
60 cells (6 > 10)
Module Dimensions
3511.36
Weight
(A -A)
<t�u,rTs oP vc rr; i, rival
w
G
}
v'�iagx(Yi
I, VCURVES GP FV ti§vNUi.ES3ViS�'v';
All,
MECHANICAL )ATA
Solar Cells
Monocrystalline 156 75 * 156.75 mm (6 inches)
Cell Orientation
60 cells (6 > 10)
Module Dimensions
1650 . 992 x 35 mm (65.0 . 391 x 1-38 inches)
Weight
18.6 kg (41.0 lb)
Glass
3.2 mm (0.13 inches), High Transmission, AR Coated Tempered Glass
Backsheet
White [DDO5AO8(II)];
Black [DD05A 05(11)1
Frame
Black Anodized Aluminium Alloy [DDO5A 08(11), DOOSA.05(il)j
]-Box
IP 67 at IP 68 rated
Cables
Photovoltaic Technology Cable 4.Orrma (0-006 mches2),
1000 Irwin (39.4inches)
Connector
Trina T54
Fire Type
Type 1 or Type 2
TEMPERATURE RATINGS
MAXIMUM RATINGS
NOCT
44`(1±2`t) Operationallemperature-/0-+85`C
TemperaUxe Coefficient of P .x
039 F9 °C Maximum System Voltage 10OOV DC (IEC)
Ierr peratuie,'oeffi€ientofV,.
-0-29vIrl, 1000VDC(UL)
Temperature Coefficient of i
0,05%11C Max Series Fuse Rating ISA (Power _2aSAI)
20A Wower :'-e%W )
14c t -G. aw P o ... g,in
pa 31IE4 hKtgn,
WARRANTY
PACKAGING CONFIGURATION
10 year Product Workmanship Warranty ModuieS per box: 30 pieces
25 year Linear Power Warranty
Modules per 40' container: 840 pieces
'Fl!.icnlaf@'mPod' tw '.'rtf SOI r&ta')
'N'TON RFAD SIIFT ' III r TALi.ATIf"1INSTR ':TI"tNS 111111 11SI11 THE 1111 - 1
Trinasolar
f`` `v Trina SClar m.ed. Al rghtsreserv, d u-.f_a J3nS:nC:uoeo nihiSC-ataSnee Fe Sub,e�t t0 fharFi;2 wit"�DU3 YCti€e
_rs o nu-ae= TSM Ext 2+018 A www tc nasaiar :or
Nor-
13LUE RAVEN
1403 N RESEARCH WAY, BUILDING J
OREM. UT 84097
800-377-4480
WWW. BLU ERAVENSOLAR. COM
CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF
ANYONE EXCEPT BLUE RAVEN
SOLAR NOR SHALL IT BE
DISCLOSED IN WHOLE OR IN PART
TO OTHERS OUTSIDE RECIPIENTS
ORGANIZATION, EXCEPT IN
CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE
EQUIPMENT; WITHOUT THE
WRITTEN PERMISSION OF BLUE
RAVEN SOLAR LLC.
NADCEP
CERTIFIED
PV INSTALLATION
PROFESSIONAL
Scott Gurney
# PV -011719-015866
CONTRACTOR:
BRS FIELD OPS
385.498.6700
City of
Wheat Ridge
SHEET NAME
SPEC SHEET
PAGE NUIv16ER REViSSON
SS 0
S I c
amommomp�
FLASHED FV ROOF -MOUNT COMBINER/ENCLOSURE
Basic Features
Stamped Seamless Construction
• 18 Gauge Galvanized Steel
Powder Coated Surfaces
• Flashes into the roof deck
• 3 Roof deck knockouts .5", .75", 1"
• 5 Centering dimples for entry/exit
fittings or conduit
2 Position Ground lug installed
• Mounting Hardware Included
"Fuse holders and terminal blocks
added in the field must be UL listed or
recognized and meet 600 VDC 30 AMP
110C for fuse holders. 600V 50 AMP
90C for rail mounted terminal blocks
and 600 V 175 AMP 90C for Power
Distribution Blocks. Use Copper wire
Conductors.
SolaDeck Model SD 0783
SolaDeck UL50 Type 3R Enclosures
Available Models:
Model SD 0783 - (3" fixed Din Rail)
Model SD 0786 - (6" slotted Din Rail)
SolaDeck UL 1741 Combiner/Enclosures
Models SD 0783-41 and SD 0786-41 are labeled and ETL listed UL STD 1741
according to the UL STD 1741 for photovoltaic Combiner enclosures.
Max Rated - 60OVDC, 120AMPS
Model SD 0783-41 3" Fixed Din Rail fastened using Norlock System
"Typical System Configuration
4- Din Rail Mounted Fuse Holders 60OVDC 30 AMP
1- Power Distribution Block 60OVDC 175AMP
1- Bus Bar with UL lug
Model SD 078641 6" Slotted Din Rail fastened using steel studs
"Typical System Configuration
4- Din Rail Mounted Fuse Holders 60OVDC 30 AMP
4- Din Rail Mounted Terminal Blocks
Bus Bars with UL lug
conduit or fittings, base is
center dimpled for fitting
locations.
Model SD 078341, wired with Model SD 0786-41, wired with
Din Rail mounted fuse holders, Din Rail mounted fuse holders,
bus bar and power distribution terminal blocks and bus bars.
block.
RSTC Enterprises, Inc • 2219 Heimstead Road . Eau Cliare, WI 54703
For product information call 1(866) 367-7782
'14�
BLUE RAVEN
1403 N RESEARCH WAY, BUILDING J
OREM, UT 84097
800-377-4480
WWW.BLUERAVENSOLAR COM
CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF
ANYONE EXCEPT BLUE RAVEN
SOLAR NOR SHALL IT BE
DISCLOSED IN WHOLE OR IN PART
TO OTHERS OUTSIDE RECIPIENTS
ORGANIZATION, EXCEPT IN
CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE
WRITTEN PERMISSION OF BLUE
RAVEN SOLAR LLC
NABCEP
CERTIFIED
PV INSTALLATION
PROFESSIONAL
Scott Gurney
# PV -011719-015866
CONTRACTOR:
BRS FIELD OPS
385.498.6700
city of
*hoot V498
......cion
SHEET NAME
SPEC SHEET
PAGE NUM I REVISION
0
SYSTEM BONDING & GROUNDING
son R,
P A G E
S F M
TERKNALTORQUE,
Install Conductor and
torque to the folklowir
4-6 XvVG: 35in-lbs
8 AWG: 25 in -lbs
10-14 AWG: 20 in -lbs
TERMINALTORQUE,
Install Conductor and
torque to the following,
4-14 Al IG: 35in-Lbs
WEE LUG
Single Use C)n[v
TERMINAL TORQUE,
Install Conductor and
torque to the following:
6-14 AWG: 7ft-ibs
r r -r rf r,, , ?7 9 r rd p, y , r f ! r, "r";"`, ri t , 7 ! k,'? !- n, 11 17, -re-,me_10
11sco Lay -in Lug (GBL-4DBT) Ksco FLange Lug(SGB-4) Wiley WEEBLug (6.7)
• 10-32 mounting hardware 0 1/4" mounting hardware 1/4" mounting hardware
• Torque = 5 ft -Lb 0 Torque = 75 in -lb Torque = 10 ft -Lb
• AWG 4 -14 -Solid or Stranded a AWG 4 -14 -Solid or Stranded AWG b -14 -Solid or Stranded
NOTE: ISOLATE COPPER FROM ALUMINUM CONTACT TO PREVENT CORROSION
E -W BONDING PATH: E -W module to module bonding
is accomplished with 2 pre-installed bonding clips
which engage on the secure side of the Microrai tTM
and splice.
N -S BONDING PATH: N -S system bonding is
accomplished through a N -S bonding clip. Insert each
end of the N -S bonding clip onto a module frame
flange. Systern is bonded with a single array edge,
however it is recommended that N -S bonding clips
be installed on both edges for ease of maintenance
(see atso: Maintenance Page S)
System bonding is accomplished through modules. System grounding accomplished by attaching a ground Lug to any module
at a Location on the module specified by the module manufacturer.
'Nw
BLUE RAVEN
1403 N RESEARCH WAY, BUILDING J
OREM, UT 84097
800-377-4480
W\AW.BLUERAVENSOLAR,COM
CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF
ANYONE EXCEPT BLUE RAVEN
SOLAR NOR SHALL IT BE
DISCLOSED IN WHOLE OR IN PART
TO OTHERS OUTSIDE RECIPIENTS
ORGANIZATION, EXCEPT IN
CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE
WRITTEN PERMISSION OF BLUE
RAVEN SOLAR LLC.
NABCEP
LCERTIFIED
PV INSTALLATION
PROFESSIONAL
Scott Gurney
# PV -011719-015866
CONTRACTOR:
EIRS FIELD OPS
385.498.6700
city of
*heckt Ridge
.,i.inn
SHEET NAME
SPEC SHEET
PAGE NUM
S;R REVISION
0
AUTHORIZATION TO MARK
This authorizes the application of the Certification Mark(s) shown below to the models described in the Product(s)
Covered section when made in accordance with the conditions set forth in the Certification Agreement and Listing
Report. This authorization also applies to multiple listee model(s) identified on the correlation page of the Listing
Report.
This document is the property of Intertek Testing Services and is not transferable. The certification mark(s) may be
applied only at the location of the Party Authorized To Apply Mark.
Applicant: Unirac, Inc Manufacturer: Jiaxing Pacific Energy Equipment Corp.
No. 8 Haiwan Ave
1411 Broadway Blvd NE Hangzhou Bay Bdao New Area
Address: Albuquerque. NM 87102 Address: Hal Economic Development Area
Jiaxing City, Zhejiang Province
Country: USA Country: China
Klaus Nicolaedis Lill Zeng
Contact: Jason Mayfield Contact: George Huang
505-462-2190 510-979-1920
Phone: 505-400-2949 Phone: 650-79-0-7627
FAX: NA FAX: NA
klaus.nicolaedis@unirac.com Email: Izeng@ccmfg.com
Email: jasonm@unirac.com george@ccmfg.com
Party Authorized To Apply Mark: Same as Manufacturer
Report Issuing Office: Lake Forest, CA
Control Number: 5003278 Authorized by: 4,bW- X444"
for Dean Davidson, Certification Manager
US
OTT
Intertek
This document supersedes all previous Authorizations to Mark for the noted Report Number.
This Aurhurizaf, rto h1ark is for the exclus;e use of Intertek's r_li ..rt and is provided pursuant to the Certification agrcemert tet,reek Intertek anc its C!ient. I ritertelk's and liabilrb, are
hrroteJ tc the tears and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance mth the agreement, for any loss, expense or damage or;. asioned
by the use of this Autt-orizatlon to N4ark- 0ntt the Client as authorized to permit copying or distribution of this Authorization to h.4 ark and then nob/ in its entirety,. IJse of Iritertek s CertifeatLm mark s.s
restricted to the :undinns laid out rn the agreement and in this A ath orization to Nt ark. An. further use of the Intertek name for sale or a J ernsement oft -ie tested materia:, product or ser ice must
first be approved in nrt tino by Intertek:. Initial Factory Assessments and Folln a up Services are for the purpose of as uring apprornate usage of the Ce trf ration mark in aricoreance moth the
agreement, they are not for the purposes of production quality control and do lot relie— the L tient of their obli,gaLons in this respect.
Intertek Testing Services NA Inc.
545 East Algonquin Road, Arlington Heights, IL 60005
Telephone 800-345-3851 or 847-439-5667 Fax 312-283-1672
ATM for Report 102393982LAX-002 Page 1 of 2
ATM Issued: 2 -Mar -2017
E1,1n 31- 11-Ii1I--15j Mandatory
Nol
BLUE RAVEN
1403 N RESEARCH WAY, BUILDING J
OREM, UT 84097
800-377-4480
WWW.BLUERAVENSOLAR-COM
CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF
ANYONE EXCEPT BLUE RAVEN
SOLAR NOR SHALL IT BE
DISCLOSED IN WHOLE OR IN PART
TO OTHERS OUTSIDE RECIPIENTS
ORGANIZATION, EXCEPT IN
CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE
WRITTEN PERMISSION OF BLUE
RAVEN SOLAR LLC
NABCEP
CERTIFIED
PV INSTALLATION
PROFESSIONAL
Scott Gurney
# PV -011719-015866
CONTRACTOR:
BRS FIELD OPS
385.498.6700
city of
mgt Ridge
SHEET NAME
SPEC SHEET
PAGE NUMBER I REVISION
SS 0
UL 2703 Issued: 2015101128 Ed: 1 Mounting Systems.. Mounting Devices, Clamping/Retention Devices.
Standard(s):
and Ground Lugs for Use with Flat -Plate Photovoltaic Modules and Panels
Photovoltaic Mounting System. Sun Frame Micro Rail- Installed Using Unirac Installation Manual, Rev
Product:
PUB2017FEB16
Brand Name:
Unirac
Models:
Unirac SFM
ATM for Report 102393982LAX-002 Page 1 of 2
ATM Issued: 2 -Mar -2017
E1,1n 31- 11-Ii1I--15j Mandatory
Nol
BLUE RAVEN
1403 N RESEARCH WAY, BUILDING J
OREM, UT 84097
800-377-4480
WWW.BLUERAVENSOLAR-COM
CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF
ANYONE EXCEPT BLUE RAVEN
SOLAR NOR SHALL IT BE
DISCLOSED IN WHOLE OR IN PART
TO OTHERS OUTSIDE RECIPIENTS
ORGANIZATION, EXCEPT IN
CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE
WRITTEN PERMISSION OF BLUE
RAVEN SOLAR LLC
NABCEP
CERTIFIED
PV INSTALLATION
PROFESSIONAL
Scott Gurney
# PV -011719-015866
CONTRACTOR:
BRS FIELD OPS
385.498.6700
city of
mgt Ridge
SHEET NAME
SPEC SHEET
PAGE NUMBER I REVISION
SS 0
TABLE OF CONTENTS: PG
Tools & Assembly Details 1
Quick Steps for Installation 2
PUB2017JAN11
X80 SUNFRAME MICRORAIL
•■ L RAISED SEAL FLASHING
TOOLS REQUIRED OR RECOMMENDED FOR
LAYOUT & INSTALLATION:
• TAPE MEASURE
• CHALK LINE
• ROOFING CRAYON
• HAMMER
• COMPATIBLE SEALANTAND DISPENSER
• DRILL WITH EITHER 1B• BIT FOR GRK AND
• UNiRAC CUSTOM STRUCTURAL SCREW. OR 7/32 -
BIT FOR LAG BOLT
• IMPACT DRIVER WITH W SOCKET (OPTIONAL Y.'
HEX DRIVER FOR UNIRAC CUSTOM STRUCTURAL
SCREW)
SFM RAISED SEAL FLASHING COMPONENTS:
1. FASTENER
• LAG BOLT, 5/16'
• UNIRAC CUSTOM STRUCTURAL SCREW, 5/16-
GRK STRUCTURAL SCREW, 5/16"
2.5/16' ID EDPM SEALING WASHER
3. SFM MOUNTASSEMBLY(VARIOUS) WITH SLIDER
4- SFM RAISED SEAL FLASHING
S. COMP SHINGLE ROOF
TOOLS & ASSEMBLY DETAILS 12
TECHNICAL DATA SHEET L PAGE
--------------------------------------
INSTALLATION NOTES:
A. It is not necessaryor advisable to use nails or other fasteners to secure the perimeter of the flashing.
B. The SFM Raised Seal Flashing is made to work with standard and high-definition composition/asphalt and
wood shingle roofs with S" to 5-5/8"courses.
C. Mounts should not be installed in areas of the roof susceptible to ice damming. Ponding water can travel
upward under shingles and reach the bolt penetration.
D. Fastener length specification and capacity verification are the responsibility of the installer.
l
I WWi�t'AkL
met
NEI I � rA, I r I A I~T!
----------------------------------------------------------------
QUICK INSTALLATION STEP'S 2
PAGE
PREPARING SHINGLES: Use roofing
bar to break seals between 1st and
2nd, and 2nd and 3rd shingle courses.
Be sure to remove all nails to allow
correct placement of flas hing. See SFM
installation guide for proper flashing
placement.
DRILL PILOT HOLES: Holding the drip
square to the rafter chill 3" deep pilot
hole into center of rafter using 1J8"
aircraft extension bit for 5/16' GRK
or Unirac Custom Structural Screw, or
7/32" aircraft extension bit for 5/16"
lag.
ROOF SEALANT: Fill pilot hole with OPTIONAL SEALANT ON FLASHING:
appropriate sealant. Apply a circle shaped bead of sealant
around the attachment hardware hole
of the flashing before insertion. Do
not use excessive sealant.
POSITION FLASHING: Slide the
flashing up underneath the 2nd course
of shingles, so that the bottom edge
of the flashing does not overhang the
downstope edge of the 1st course of
shingles.
PLACE SLIDER: Place slider with
assembly over the flashing flute,
ensuring that the slider sits flat on the
flashing surface.
INSTALL FASTENER & TIGHTEN:
Install fastener with seating washer.
Swivel the slider to gauge proper
torque when driving the fastener.
Tighten until slider stops swiveling
easily.
COMPLETE FLASHING INSTALLATION:
Repeat previous steps to install all
mounts.
1";LUE RAVEN
1403 N RESEARCH WAY, BUILDING J
OREM, UT 84097
800-377-4480
W W W.BLUERAVENSOLAR.COM
CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF
ANYONE EXCEPT BLUE RAVEN
SOLAR NOR SHALL IT BE
DISCLOSED IN WHOLE OR IN PART
TO OTHERS OUTSIDE RECIPIENTS
ORGANIZATION, EXCEPT IN
CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE
WRITTEN PERMISSION OF BLUE
RAVEN SOLAR LLC.
NABCEP
CERTIFIED
PV INSTALLATION
PROFESSIONAL
Scott Gurney
# PV -011719-015866
CONTRACTOR:
BRS FIELD OPS
385.498 6700
C" d
VnItee 9099
SHEET NAME
SPEC SHEET
PAGE NUMBER REVISION
SS 0
♦ i CITY OF WHEAT RIDGE
Building Inspection Division
(303) 234-5933 Inspection line
(303) 235-2855 Office • (303) 235-2857 Far
INSPECTION NOTICE
Inspection Type: t ° I !
Job Address: } Q!3
Permit Number:4f~~q I?I
No one available for inspection: Time AM/PM
Re-Inspection required: Yes No
at 303-234-5933
"When (corrections have been made, call for J;77
Date: Inspector: DO NOT REMOVE THIS NOTICE
6 A 4' City of Wheat Ridge
Residential Roofing PERMIT - 091890
PERMIT NO: 091890`- -ISSUED: 09/02/2009
JOB ADDRESS': 10920-W 39TH AVE EXPIRES: 03/01/2010
DESCRIPTION: Reroof 15 sqs
***'.CONTACTS
owner 303/944-2996 Bob Johnson
sub 303/912-5829 Glen Newton. 09-0181 Specialty Contractors Inc.
PARCEL 'INFO
ZONE CODE: UA USE: UA
SUBDIVISION:. 0189: -BLOCK/LOT#: 0/:
FEE SUMMARY ESTIMATED PROJECT VALUATION: =.3,400.00
FEES
Permit Fee 126.50
Total Valuation .00
-71
Use Tax 61.20 4C~3U~
TOTAL .187.70
Conditions:
6 nail installation& mid roof inspection required. Board sheathing spaced more
than :a 1/2 of an inch apart requires plywood overlay on entire roof. Ice and
water. shield required from eave edge to 2'inside exterior -'walls.
Subject to field inspections.
I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable
ordinances, rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all
measurements shown, and 'allegations 'made are accurate; that I have read and agree to abide by all conditions printed on this
application and that I assume full responsibility for compliance with the Wheat Ridge Building Code -:(I.B.C) and all other "
applicable W a Ridg/e rdina ces, for work under this permit. Plans subject to field inspection.
-Z, 9-- 27001
Signature of contrac[ /owner date
1. This permit was issued in accordance with the'., provisions. set forth in your application and is subject to the laws of the
State of Colorado and to the zoning Regulations and Building Codes of Wheat. Ridge, Colorado or any. other applicable
ordinances ofthe city.
2 This permit shall expire180 days from the issue date. Requests for an extension must be received prior to expiration
date. An extension maybe granted. at the discretion ofthe Building Official.
3. If this permit expires, a new permit may be acquired fora fee of one-half the amount normally required, provided no
changes have been or will be made in the original plans and specifications and any suspension or abandonment has not
exceeded one '(1) year. If changes have been or if suspension or abandonment. exceeds one (1) year, full fees shall
be paid for anew permit.
4 No work of any. manner shall be done that will change the natural flow of water causing a. drainage :problem.
5. Contractor shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive
written approval on inspection card. before proceeding with successive phases of the job.
6. The'. issuance of a permit 'or the approval of 'drawings and. specifications shall not be construed to be a permit for, nor
an approval of, any violation of the provisions of the building codes or any, other ordinance, law, trule or regulation.
Allj; plan review is subject to field. inspections.
Signature of Ch" ding; Official :date
INSPECTIO, REQ ST LINE: (303)234-5933 BUILDING OFFICE.: (303)235-2855
REQUESTS MUST BE MADE BY '3PM' ANY BUSINESS:. DAY FOR INSPECTION THE 'FOLLOWING BUSINESS DAY.
F W"E?T City of Wheat Ridge Building Division Date: j I q
m 7500 W. 29th Ave., Wheat Ridge, CO 80033
Office: 303-235-2855 * Fax: 303-237-8929 Plan M
inspection Line: 303-234-5933
Permit
Building Permit Application
Property Addresi`. - V
Property Owner (please print): j0 45011 Phone 2 % ~tl
Mailing Address: (if different than property address)
Address:
City, State,
Cortractor: ~lJc'~ ~t't 1 ~~aLf~ e"e i,A °1 S -ZnC,
Contractor License fl"~l ^ Q Phone: 7 ^ s JZ6
Sub CgntractoIS
Electrical City License
Company:
Plumbing City License
Company
Mechanical City License
Company:
Exp. Date:
Exp. Date:
Exp. Date:
Use of space (description): Ikeo oo Construction Value: $
DeSCription of WVork'' /f (as calculated per the Building 1/at6ation Data sheet)
Plan Review (due at time of submittal): $
!L_ ct/ t J it ~r M/^Cd cT~C /O~~c r~
Sq. Ft./L.Ft added: Squares BTU's Gallons Amps
OWNERICONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT
I hereby certify that the setback distances proposed by this permit application are accurate, and do not violate applicable ordinances,
rules or regulations of the City of Wheat Ridge or covenants, easements or restrictions of record; that all measurements shown, and
allegations made are accurate; that I have read and agree to abide by all conditions printed on this application and that I assume full
responsibility for compliance with the Wheat Ridge Building Code (I.B.C) and all other applicable Wheat Ridge Ordinances, for work
under this permit. Plans subject to field inspection.
CIRLCE ONE:: (OWNE/~R`)-~'(bONTRAJPTOR) or PERSONAL REPRESENTA IV of (OWN 1) (CO TRATOR)
PRINT NAME: oCN 1l IVCLr.~~/t SIGNATURE: itr Date:
Bldg Valuation:
COMMUNITY DEVELOPMENT DEPARTMENT Building Permit Number : 15426
BUILDING INSPECTION LINE - 303-234-5933 Date : 4/29/2003
CITY OF WHEAT RIDGE
7500 WEST 29TH AVENUE
WHEAT RIDGE, CO 80215 - (303-235-2855)
Property Owner: CESAR LUCERO
Property Address : 10920 W 39TH AVE
Contractor License No. :
Phone : 893-3195
Company: Phone:
OW NER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT
I hereby certify that the setback distances proposed by this permit application are accurate, and
do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or
covenants, easements or restrictions of record; that all measurements shown, and allegations
made are accurate; that I have read and a9ree to abide by all conditions printed on this
application, and that I assume full responsibility for compliance with the Wheat Ridge Building
Code (U.B.C.) and all other applicable W heat Ridge ordinances, for work under this permit.
(OWNER)(CONTRACTOR) SIGNED . C L- N _DATE 4 IZ O
Description : BACK YARD FENCE. 6' PRIVACY
Construction Value :
$1,200.00
Permit Fee :
$58.34
Plan Review Fee :
$0.00
Use Tax :
$24.00
Total:
$$2•34
Use:
1 ~
BUILDING DEPARTMENT USE ONLY
Zoaing Com~entstx
SIC : Sq. Ft. :
Approval : MA
THE 6' FENCE MUST NOT EXTEND INTO THE 30' FRONT YARD
Zoning: R-1C
SETBACK. 4125103 plesseNote:
Building~Comme ~
Owner/conhacWr is responsible for locating property
4125103 lines and wnsWCting improvements according to the
Approval : BG
approved plan and required development standards.
The City is no[ responsible for inaccurate in;orrnation
Pubh `~Works~C~rltment~~~
su6miYted within the plan set znd any construction
Approval :
errors resulting from inacc!xetc'+rir~r~ ~2',ir:~.
Occupancy : Walls :
Roof : Stories : Residential Units :
Electrical License No :
Company :
Expiration Date :
Approval :
Plumbing License No :
Company :
Expiration Date :
Approval :
Mechanical License No :
Company :
Expiration Date :
Approval:
(1) This permit was issued in accordance wilh the provisions set foAh in yopur application and is subjed to the laws of the State of Colorado and to the Zoning
Regulations and Building Code of W heat Ridge, Coloredo or any other applicable ordinances of ihe City.
(2) This permit shall expire if (A) the work authorized is not commenced within sizty (80) days from issue date or (e) the building authonzed is suspended or
abandoned for a period of 120 tlays. (3) if this pertnit expires, a new permit may be acquired for a fee of one-half the amount nortnally required, provided no changes have been or will be made in the
onginal plans and specifications and any suspension or abandonment has not exceeded one (i) year. If changes are made or if suspension or abandonment
exceeds one (1) year, full fees shall be paid for a new permit. - (4) No work of any manner shall be done thatwill change lhe naturai Flow oFwater causing a drdinage pmblem. -
(5) Contrector shall notify the Building Inspector twenty-four (24) hours in advance for all inspections and shall receive written approvai on inspection card before
proceediing with successive phases of the job.
(6) The issuance of a pertnit or the approval of drewings and specifications shall not be constmed to be a permit for, nor an approval of, any violation of the pmvis' s f the buil ' g codes or any other ordinance, law, rule or regulation.
C ' f13uilding pector
COMMUNITY DEVELOPMENT DEPARTMENT Building Pemut Number:
~f WHE9T
; .p BTJII,DING INSPECTION LINE - 303-234-5933 Date:
~ n CITY OF WHEAT RIDGE
7500 WEST 29TH AVENiTE
~a oftpoo WHEAT RIDGE, CO 80215 -(303-235-285~
~~~UCATION
/ Property Owner: G'eSa t- r~J
/ V
Property Address: (Lle5.i- .FA '
lOQ'2~ 3q Av u~.heo~fklQ9C' Phone: 3G'j 6q3 3/ QS
\ Contractor License No.: CQ BQpy.j
CompanY: Phone: 12-0 30/ ZSb U'
'
O WNER/CON7RACTOR SIGNATURE
AND AGREEMENT
I hereby certify that the setback distances proposed by Ihis permit applicadon ate accmate,
and do not violate app7icable ordinances, mles or regutadons of the City of Wheat Ridge or
covenants, easements orres4ic6ons ofrecord; tUat all measurements shown, and allegations
made are accurate; that I have read and agree to abide by al] condidons printed on this
application and tUat I assume full responsibility for compliance with the Wheat Ridge
Building Code (U.B.C) and ali othet appticable VJheat Ridge Ordinances, for work under
this permiL
~ (OWN&R)(CONIRACTOR):SIGNED ,Ll bf (il~ DATb,4t 7$.n
DESCitIPTION:
L C
10 '
/k CC~ c-
"~l1YG-C~
BUII,DING DEPARTMENT USE ONLY
ZONINGCOMMENTS: t SIC;
Approval:
Zoning:
BUILDINGCOMMENTS:
Approval: ~5 L., y/;77~ Yf
PUBLIC WORKS COMMENTS:
Approval:
Occupancy: Walls: RooE Stories
Elechical License No:
Company:
Plumbing License No:
Company:
Construcrion Value:$ l~pQ
Pemut Fee:$
Plan Review Fee:$
Use Tax:$
Z'Ot31:$
Residential Units:
~~CM VED
A PR r~ 4 2;;8 3
Sq.Ft.:
Mechauical License No:
Company:
ExpuationDate: Expiration Date: Expiration Date:
Approval: Approval: Approval:
(1) ILis pumitwaz issued in accordance with the pmvisions setforth in your application and'u subju[ to tLe laws of the Sta@ ofColomdo and to tLe Zoning
Regulations andBwlding Codes ofVfieatRidgq Colomdo or any other applicable ord'mancu ofthe City.
(2) Tlus pvmit sLaIl ezpsse if (A) the work authorized is not commeuced within sixry (60) days from issue date ar (B) fhe bffiding autLorized is suspmded or
abandoned for a period of 320 days.
(3) IftLispecmitexpiru,anewpumitmaybeacqussedforafeeofone-halftheamountnolmallyroquired,pmvidednocLaageshavehernorwill6emadein
theoriginalplaosandtpecificationsandanysuspensionorabandonmeatLasnotexceededone(1)yeaz.IfchengaLavebeenorifswpensionorabando=ent
exceeds oae (1) year, full fees shall be paid for a new pemit
(4) NoworkofenymennersLallbedonethatw7lchangetLena4valflowofwatacausingadxainageproblem.
(5) ContracmrshallnotifytheBwldingInsp<c4rcwenty-fow(24)Louninadvanceforallinspectionsandshall receivewcitteuapprovaloninspectimcardbefore
pmceeding wittL succasive phua ofthejob.
(6) The issuance of a pumit or the approval of dmwings and speci5cations shall notbe conaSVed W be apermit fo; nor an appmval o( any tiolaGOn of the
protisions ofthe buuldin codu or any otha ordinancq ]aw, xule wregulation
/ ' . .
'efBuildingInspe or ~
t39.5`
7s A
13 7
.0
139 5 ~
6-A
6-B
.
, _31
5
w. 39 '
57, li
.
41 42 ,~---`~~_-J 43 44
4 -A
04~ z`
~ U
49
50
51 52
~
E)I( E
58" i f „ 1 „
58t
TFT F
4
f~ I a
55
I 2-~a ~ 5~-~a
a
DARRIN,
I HAD A COMPLAINT ABOUT "REMOVED LANDSCAPING" AT 10920 W. 39'~
AVENUE. I DROVE OUT THERE AND FOUND A VERY WEIRD SITUATION.
• all of the dirt in the front yazd has been dug up and pushed against the house
• there are no glass windows
• windows aze boarded up and painted to match the house
• spoke with a neighbor, who informed me the ladies name is Norma and she is a
schizophrenic
• neighbor said Norma is nice, just really odd & paranoid
• one previous "assist only" in 1997 history with police, she wouldn't let them in
• there's a scarf hooked to the outside porch lamp which then runs down to the doorknob
-my impression being it was securing the door
• neighbor said that Public Service came out a few years ago and tumed off the gas
(and it has been off ever since) . She believes that this is why she is moving the dirt (to
keep in the heat)
• Per Public Service- gas is off & the electric is on
• no previous code / building contact
• Jefferson Center for Mental Health said we should ask the police to do a welfare check on
her
• Per Consolidated Water, there is no water to the residence
I don't know what to do. Citing her far landscape requirements does not seem to be the most
appropriate thing. Any suggestions?
Thanks,
Claudia 1~
I~G':l s~iey,
a c~ -
d'✓.W' ) 32- ~~~C)
3o3-,2 71-a!731
rm , h„~ l
230_ c>NSl
NW bn ✓~%d,my ~e~'
S~w~ wcs~r'~sC
M~~1-9~IG7
.6.'//Pwl
f
OCT.12 '98 11:26RM
~
~
~
t r°
;
P.1
OCT.12 198 11:27RM
P.z
October 12,1998
Dear Ray,
On S8turtlay afternoon, a man (I ddn't catch his name. ) employed by Jonn, the
Cement sub-contractor, came by to discuss the carport slab. He wanted to rriske sure
that he got the job right. I was vary glatl that John had hirgd nim, fior ! was impressed
by his knowledge and thoroughness.
As you and ! had discussed last week, the foundation wall is not Yrigh enough by 4 1/2
to 5 inches_ The man hired by John agreeq with what you hatl told me about
correcting the problem wiYh a"thickened edge" to make the carpprt siab and driveway
Ievel with my current driveway. As I understand it, the siab itself Can only have a 2
inch drop-ofiF slOping to the east for run-off in order t0 pYOVide enough level Surfac2, so
people can stop in time given the steepness of the driveway. 7herefore, the thickness
of the slab neM to the garage wall wilf have to be anyuvhere from 9 1/2 to 10 inches,
gradually reducing in tMickness to 7 1/2 to 8 inches thick along the Eastern side.
Given that the original slab was designed to be 4 inches thick, ! consulted with my
architect about these changes. He said tha# the foundation wall could hold up the
thickened slab, but that the diR and/or road fill had to be compaCted enough to hold up
the extra weight to prevent the middle from sinking. .
A recommendation is that we tape up a copy of the architecturai drawings to the
ouGside of the garage window. In this way, the sub-contractors would have the exact
measurements and details, atong with a picture of the whole project. I woultl prefer
that you put up a copy with any necessary changes, rdther than mine which hds none.
Nowever, if that cannot tre arranged, t'tl be glad to have mine Copied and taped up
with a note to call yau befora proceeding to find out any changes.
After this weekend, I feel confiderrt that the problem of;he t00 short foundation wail
can be remedied. In the future, it is my wish, as I dm Sure it is yours, that this projeCt
moves forvuard as ptanned.
Talk to you soon.
Sincerely,
9A*U 440C~
cc: Bob Gaspar, Buiiding inspector for Whedtridge
BUILDING DEPARTMENT
(303) 235-2855
CITY OF WHEAT RIDGE
* *
Correction Notice
y ~
Job Located at ibq)O 'a'~ ~
I have this day inspected this structure and these premises and
have found the following violations of City and/or State laws gov-
erning same:
You are hereby notified to correct the foregoing violations.
When corrections have been made, call for inspection.
Date
' Inspector for Builtling Dept. ~ ,
~
DO NOT REMOVE THIS TAG
FORM WR6-22 . . . . .
. . . . . . . . . .
DARRIN,
I HAD A COMPLAINT ABOUT "REMOVED LANDSCAPING" AT 10920 W. 3911,
AVENUE. I DROVE OUT THERE AND FOUND A VERY WEIRD SITUATION.
• all of the dirt in the front yard has been dug up and pushed against the house
• there aze no glass windows
• windows aze boarded up and painted to match the house
• spoke with a neighbor, who informed me the ladies name is Norma and she is a
schizophrenic
• neighbor said Norma is nice, just really odd & pazanoid
• one previous "assist only" in 1997 history with police, she wouldn't let them in
• there's a scarf hooked to the outside porch lamp which then runs down to the doorlrnob
-my impression being it was securing the door
• neighbor said that Public Service came out a few years ago and turned off the gas
(and it has been off ever since) . She believes that this is why she is moving the dirt (to
keep in the heat)
• Per Public Service- gas is off & the electric is on
• no previous code / building contact
• Jefferson Center for Mental Health said we should ask the police to do a welfare check on
her
• Per Consolidated Water, there is no water to the residence
I don't know what to do. Citing her for landscape requirements does not seem to be the most
appropriate thing. Any suggestions?
Thanks,
Claudia
SUBJECT PROPERTYINFORMATION
12)
Property: 10920 W 39TH AVE, WHEAT RIDGE CO 80033-3913 C021
APN:
39-213-06-041
Use:
SFR
County:
JEFFERSON, CO
Tax Rate Area: 3141
Total Value:
$7,880
Census:
105.03
Prop Tax: $729.96
Land Value:
$1,820
RTSQ:
69W03S21SW
Exemptions:
Imprv Value:
$6,060
Map Loc:
15-L
Assd Yr:
1996
Subdiv:
WHEATRIDGE MANOR
% Improve:
76%
Owner:
WILSON THOMAS A
Phone:
3031424-9323
Mail: 10920 W 39TH AVE; WHEAT RIDGE CO 80033-3913 C021
SALES INFORMATION
LAST SALE
Transfer Date: 11116184
PRIOR SALE
IMPROVEMENTS
Bldg/Liv Area:
804
# Units:
# Bldgs:
# Stories:
1
$/SF:
YrbIUEff:
1955
Total Rms:
Bedrms:
Baths(F/H):
7
Fireplace:
0
Sale Price/Type:
Document#: 711582
Document Type:
1 st TD/Type:
Fim'ince:
Jun?or TD's:
Lender:
Seller:
Title Company:
Transfer Info:
SITE INFORMATION
Improve Type:
Zoning:
Site Influence:
County Use: 1112
Flood Panel:
Phys Chars:
Lot Size:
Lot Area:
Parking: ATTACHED
Park Spaces: 324
Bldg Class:
Legal: TR831400/ WHEATRIDGE
Comments: STATE USE:IMPROVED RESID
DWELLING;; PARKING-324; SCI
~\V
V
Pool:
Bsmt Area
Construct: WOOD FRAMEICB
Flooring:
Air Cond:
Heat Type: FORCED AIR
Quality:
Condition:
Other Rooms:
s6~C11429
BLD TYPE:SINGLE UNIT
269;LA 17600;IA 5 ~
Copyright OO 1996-97 Experian ~ Page: 1 of 1
eplace electrical service & upgrade mtenor wirmg oi
DEPARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number :
BUILDING INSPECTION DIVISION - 235-2855
CITY OF WHEAT RIDGE Date : 002s100
7500 WEST 29TH AVENUE
WHEAT RIDGE, CO 80215 p,PPLICATIo N
Property Owner :
°roperty Address : JOR ZO Phone :
Contractor License No. g~-(,~j 60033
Company: kin-rseyEQ.e-T-1ca4 ~onoT~=+q-ca~r~ Phone:6~03)3-732.,(o(j
OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT Construction Value :
42e5o0pO
1 hereby certify that the setback distances proposed by this pertnit application are accurete,
and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or
covenants, easements or restrictions of record; that all measurements shown, and allegations
made are accurate; that I have read and agree to abide by all conditions printed on this
application, and that I assume full responsibiliry for eompliance with the Wheat Ridge Building
Code (U.B.C.) and all other applicable Wheat Ridge ordinances, for work under this pertnit.
(OWNER)(CONTR4CTOR) SIGNED y~U'S46QAe~pTE / Z 00 /
Use:
Description
o-A -R~.5Tt~vl
Permit Fee :
Use Tax :
Total :
BUILDING DEPARTMENT USE ONLY
Approval:
Zoning :
n o
Approval:
Approval:
Occupancy : Walls
Roof : Stories
Sq. Ft
Residential Units :
Electrical License No :
Company :
Expiration Date :
Approval:
Plumbing License No
Company:
Expiration Date :
Approval :
SIC
Mechanical License No :
Company :
Expiration Date :
Approvai:
(7) This permit was issued in accordance with the provisians set torth in yopur appliration and is subject to the laws of the State of Coloredo antl to the .'.oning .
Regulations and Builtling Code of Wheat Ritlge, Colo2tlo or any other appliwble ortlinances of the Ciry.
(2) This pertnit shall expire it (A) the work authonzed is not commencetl within sinPj (80) days hom issue date or (B) the building authorized is suspendetl or
abantlonetl for a perio0 of 120 tlays.
(3) If this pertnit expires, a new pertnit may be acquired for a tee of one-half the amount nortnally required, provided no changes have been or will be matle in the
original plans antl specifirations and any suspension or ahantlonment has not exceetled one (1) year. If Uanges are matle or if suspension or abandonment
exceetls one (1) year, full fees shall be paitl Por a new pertnR (a) No work of any manner shall be tlone that will change the naWal flow of water causing a tl2inage pro6lem.
(5) ConVactor shall noGfy the Building Inspector twenry•four (24) hours in advance for all inspections and shall receive written approval on inspection prC beFOre
proceetliing with successive phases of the job.
(6) The issuance of a pertnit or the appmval of drawings anC sperifiraUons shall not be consWetl to be a peimit for, nor an approval of, any violation ot the pmvisions
of the builtling codes or any other ottlinance, law, tule ar regulation. .
Chief Buiiding Inspector
Property Owner
~ON/NER)(CONTR4CTOR) SIGNED
Description ' Repair/repipe portions of DW & V,repai~:
Bl11LD1NG DEPAF
; Approval:
~-Zoning :
Approval .
u~
°
~
-
.
.
Approval
+
'
'Occupancy . WaITs
Rdof ` _
~ Electrical License No :
Plumbing License l
, line `
DEPARTMENT OF PLANNING AND DEVELOPMENT Building Permit Number :
BUILDING INSPECTION DIVISION - 235-2855
CITY OF WHEAT RIDGE Date :
7500 WEST 29TH AVENUE
WHEAT RIDGE, CO 80215 APPLICATIo N
PropertyOwner: D
°roperty Address : rc qza c~ 3q ¢h Phone : (7j3 ) Ll)~_ t1/f-y~
Contractor License No. :-203.1 5
Company: f~Leve McLI'n~e✓N Phone:(3U3) 130
OWNER/CONTRACTOR SIGNATURE OF UNDERSTANDING AND AGREEMENT
I hereby certify that the setback distances proposed by this permit application are accurate,
and do not violate applicable ordinances, rules or regulations of the City of Wheat Ridge or
covenants, easements or restrictions of record; that all measurements shown, and allegations
made are accurate; that I have read and agree to abide by all conditions printetl on this
application, and that i assume full responsibility for compliance with the Wheat Ridge Building
Code (U.B.C.) and all other applieable Wheat Ridge ordnmances, for Work under this pertnit.
(OWNER)(CONTRACTOR) SIGNED 6ATE
Description
Construction Value : Z)3 yy -o
Permit Fee :
Use Tax : tp
Total :
Use:
BUILDING DEPARTMENT USE ONLY
m
-
Approval:
Zoning :
Approval :
. :
Approval:
Occupancy : Walis
Roof : Stories
SIC
Sq. Ft. :
Residential Units :
Electrical License No :
Company :
Expiration Date :
Approval:
Plumbing License No
Company :
Expiration Date :
Approval:
Mechanical License No :
Company :
Expiration Date :
Approval:
(7) This permit was issuetl in accortlance with the provisions set forth in yopur appliration and is subject ta the laws of the State ot Coloratlo antl to the:.oning
Regulations and euilding Code of WFeat Ridge, CobreOO or any oNer applirable ortfinances of the Ciry.
(2) This pertnit shall expire if (A) the work authonzed is not commenced within sixry (60) tlays from iuue tlate or (B) the building authorizetl is suspentletl or
abantloned far a penod of 720 tlays.
(3) It this pertnit expires, a new permit may be acquired for a fee of one-half the amount nortnally required, provitled no changes have been or will Oe matle in the
onginal plans and specfiptions and any suspension or abantlonment has not eacceetletl one (t) year. If changes are matle or if suspension or ahantlonment
exceeds one (1) year, full tees shall be paitl for a new pertnit
(4) Na work of any manner shall be aone Mat vrill change the naNal flow of water causing a tl2inage problem. (5) ConVactor shall notlfy the Building Inspector twenry-four (24) hours in atlvance for all inspeclions antl shall receive written approval on inspection pM betore
proceetliing with successive phases of the job.
(6) The issuance of a pertnit or the approval af tlrawings antl specifirations shall not be wnsW ed to be a pertnit for, nor an approval of, any violation of the piovisions
of the builtling codes or any oNer oNinance, law, rule or regula6oa Chief Building Inspector