HomeMy WebLinkAbout4070 Clear Creek Drive4070 Clear Creek Dr 201902583 WHEATRIDGE BLDG DEPT Mr Randy Sulsser, Building Official 7500 W 29th Avenue Wheat Ridge, Colorado 80033 303-235-2803 rslusser(cDci.wheatridge.co.us Dear Mr Slusser, 3-24-2021 gEngineering 5eo rogerb@5280engineering.com 720-320-7744 www.DesianMEP.com Re:.OUTLOOK CLEARCREEK CROSSING(2017-045) 4070 Clear Creek Drive, PERMIT NUMBER: 2019-02-583 Regarding the above referenced apartment building, I understand there is a concern where carpet is installed potentially blocking return air from bedrooms. I understand bedroom doors have been undercut 1.25 )) above the wood floor as noted on mechanical plans. We additionally understand the clearance above the top of the carpet and the bottom of the bedroom door is 3/4", and not 1.25". view carpeting not to be a solid material as air is able to easily flow below the top of the carpet and thru the carpet, thus allowing for proper return airflow. We APPROVE the 3/4"clearance above the top of carpet to allow proper airflow. Please contact me if there are any outstanding concerns. Sincerely, Roger Blank, 3-24-2021 Outlook Clear Crk Crossing: Bed Door Undercut Page 1 of 1 3-24-2021 4070 Clear Creek Dr 201902583 GP INSULATION 7221 E 67 TH PL COMMERCE CITY CO.80022 Installed Insulation Certificate We certify that the insulation material listed here was installed at the address listed below: other than loose fill only aluminum foil only loose fill Ft aluminum foil Initial Installed & No.of Coverage Minimum Settled Air Spaces Direction of Aluminum Foam R Thickness Pkgs Area (SF) Thickness No. lThlckness Heat ow Loose Fill Kraft Unlaced Foil Open/Closod BIBS -Value El E]R - 49 16.75 Ceiling Attic F-1 11❑ Ceilings El El El ❑ ❑ R- 49 Ceiling Floors F]❑ ❑ E] E]R-11 3.5 -- Walls El❑ ❑ ❑ ❑ R-21 5.5 EXT _ --- ❑ 0 ❑ ❑ ❑ R-11 3.5 party _ walls Double RR=11_ Crawlspace ❑ ❑ ❑ ❑ ❑ EXI ❑ ❑ F] R-19 — 6.5 -- corrido walls other ❑ El Address or Lot Number: 4070 CLEARCREEK DR. BULDING if2 Contractor GP INSULATION (Signature) City, ST Zip: WEATH RIDGE 80401 Date Installed: 3 Title MANAGER TUPs.FRM.010 4070 Clear Creek Dr 201902583 buildina ONE consultina. Ilc March 22, 2021 Mr. Tom Harris Evergreen 1873 South Bellaire Street, Suite 1200, Denver, CO 80222 RE: Building Envelope Consulting Services Outlook Clear Creek W heatridge, Colorado Proposal Number 19 -1205 -CC Dear Mr. Harris Building One reviewed the Building Envelope at the Outlook Clear Creek property, specifically at the 4070 Clear Creek Drive address. The weather resistive barrier was observed at all exterior wall assemblies. Building One initially noted some inconsistencies, but it appears that all our concerns have been addressed. It is our understanding that the exterior wall assemblies are in general conformance with the construction documents and industry standards. If you have any questions, please do not hesitate to call. Sincerely, Building One Consulting, LLC Chad Stinnett, RA Associate ViaEmail. Tom Harris'. tharrisadevme.com denver I boston 3190 s. wadsworth blvd., suite 230 1 lakewood, co 80227 1 303.986.1400 4070 Clear Creek Dr 201902583 The City of Wheat Ridge 7500 W. 29th Avenue, Wheat Ridge, CO 80033 Third Party Form Check List Property Address �O70 0( 6 -Al , .?/ c VC - Permit Number Permit Issued Date Owner Information Property Owner Information Property Owner Address Inspection Company Inspector Name Inspector Contact info. Inspector Statement and Acknowledgement * I hearby acknowledge the roof I am inspecting is 6/12 or over. All roofs that are under 6/12 must be inspected by the City of Wheat Ridge Buiding Dept. * I hearby acknowledge the roofing system for the referenced building has been inspected and found to be in compliance with the minimum requirements of the 2012 IRC and 2012 IBC as well as all City of Wheat Ridge Policies and Procedure and Manufacturer's recommends 'onspecifications. C 5O'`"f- L' .r7' 3 Inspector: Date:2 Property Owner Statement of Acknowledgement *1 hearby acknowledge that I am the owner of the building referenced above and I give my consent for the listed third -party inspection company to perform my roof inspection in lieu of the City of Wheat Ridge Building Division inspection. Propery Owner/Agent: Date: This original document must be submitted to the Chief Building Official within seven days of the final inspection. Email to permits@ci.wheatridge.co.us Please add note to reverse side The City of Wheat Ridge 7500 W. 29th Avenue, Wheat Ridge, CO 80033 Third Party Form Check List Please add note to reverse side The City of Wheat Ridge Inspection Check List notes Mid-Roof PROPERTY ADDRESS qb-?o CLEAl. CR-CI<- 04UV6 Roof Inspection ❑ N/A ❑ Pass ❑ Fail KI N/A ❑ Pass ❑ Fail Structural roof components 0 N/A ❑ Pass ❑ Fail Verify that no more than 2 layers of shingles exist EKI N/A ❑ Pass ❑ Fail Flashing for roof and walls Q Pass ❑ Fail If new sheathing is installed verify that it is listed in the permit description (Valuation must be adjusted) ❑ N/A ® Pass ❑ Fail Verify sheathing nail pattern (See Policy & Procedures) ❑ N/A KI Pass ❑ Fail Crickets and saddles where needed 0 N/A ❑ Pass ❑ Fail Verify B vent must have boot same gauge as pipe R1 N/A ❑ Pass ❑ Fail Verify vent caps ❑ N/A E) Pass ❑ Fail Verify no flashings are damaged or rusted 0 N/A ❑ Pass ❑ Fail Step flashing shall be min. of 4x4 piece per shingle ❑ N/A KI Pass ❑ Fail Verify scuppers allow for proper drainage ❑ N/A N Pass ❑ Fail Ice and water shield 2' in heated wall spaces ❑ N/A Pass ❑ Fail Underlayments must follow 2012 IRC / 2012 IBC ❑ N/A Pass ❑ Fail Verify roof slope for proper drainage ❑ N/A Pass ❑ Fail Dripedge shall have min of 2" overlap ❑ N/A Q Pass ❑ Fail Dripedge should extend down min 2" past roof deck ❑ N/A Q Pass ❑ Fail Dripedge shall be mechanicaly fastened 12" OC Q N/A ❑ Pass ❑ Fail 90 LB roll roofing shall not be applied to roof slopes less than 2:12 slope: Exception, detached garages, patios, carports, open on three sides with min. slope of 1:12 ❑ N/A ® Pass ❑ Fail Modified Bitumen, EPDM, TPO min slope 1/4:12 slope ❑ N/A Q Pass ❑ Fail Above roof insulation R-25 ❑ N/A Q Pass ❑ Fail Below roof residential R-38 ❑ N/A R] Pass ❑ Fail Below roof commercial R-32 ❑ N/A El Pass ❑ Fail Modified Bitumen, EPDM, TPO min slope 1/4:12 slope must be installed in accordance with the manufacturers specifications- Must have manufactures letter of warranty with the address on the letter for final inspection Metal Roof Shingles Requirements N/A ❑ Pass ❑ Fail Metal roof shingles shall not be installed on slope less 3:12 ® N/A ❑ Pass ❑ Fail Metal valley flashing shall be the same material as roof [ N/A ❑ Pass ❑ Fail Metal valley flashing shall extend a min of 8" from the centerline with a min. of 3/4 " high splash diverter rib built-in at the flow line with sections overlapping a a min. of 4" Tile Roofs Requirements ERJ N/A ❑ Pass ❑ Fail Clay and concrete tile shall have a min. 2-1/2:12 slope Slopes 4:12 and under require double underlayment The City of Wheat Ridge Inspection Check List notes Mid -Roof Notes I jo Oe i,� ,k, ezD Arr E),JA L . 5TCL--cru r a L Company Name: e,,yuL'T-r.u6 Inspector signature: Date of Inspection:%/ 4 The City of Wheat Ridge Inspection Check List notes Final Roof PROPERTY ADDRESS: Roof Inspection ❑ N/A ❑ Pass ❑ Fail N/A ❑ Pass ❑ Fail Structural roof components K N/A ❑ Pass ❑ Fail Verify that no more than 2 layers of shingles exist ❑ N/A 4 Pass ❑ Fail Flashing for roof and walls Q Pass ❑ Fail If new sheathing is installed verify that it is listed in the permit description (Valuation must be adjusted) M N/A O Pass ❑ Fail Verify sheathing nail pattern (See Policy & Procedures) ❑ N/A Pass ❑ Fail Crickets and saddles where needed ❑ N/A Pass ❑ Fail Verify B vent must have boot same gauge as pipe ❑ N/A Q] Pass ❑ Fail Verify vent caps ❑ N/A Pass ❑ Fail Verify no flashings are damaged or rusted ❑ N/A [g] Pass ❑ Fail Step flashing shall be min. of 4x4 piece per shingle ❑ N/A W Pass ❑ Fail Verify scuppers allow for proper drainage ❑ N/A Pass ❑ Fail Ice and water shield 2' in heated wall spaces ❑ N/A Q Pass ❑ Fail Underlayments must follow 2012 IRC / 2012 IBC ❑ N/A 14 Pass ❑ Fail Verify roof slope for proper drainage ❑ N/A �4 Pass ❑ Fail Dripedge shall have min of 2" overlap ❑ N/A FA Pass ❑ Fail Dripedge should extend down min 2" past roof deck ❑ N/A 2 Pass ❑ Fail Dripedge shall be mechanicaly fastened 12" OC N/A ❑ Pass ❑ Fail 90 LB roll roofing shall not be applied to roof slopes less than 2:12 slope; Exception: detached garages, patios, carports, open on three sides with min. slope of 1:12 ❑ N/A ® Pass ❑ Fail Modified Bitumen, EPDM, TPO min slope 1/4:12 slope ❑ N/A ® Pass ❑ Fail Above roof insulation R-25 ❑ N/A 4 Pass ❑ Fail Below roof residential R-38 ❑ N/A] Pass ❑ Fail Below roof commercial R-32 ❑ N/A Pass ❑ Fail Modified Bitumen, EPDM, TPO min slope 1/4:12 slope must be installed in accordance with the manufacturer's specifications - Must have manufacturer's letter of warranty with the address on the letter for final inspection Metal Roof Shingles Requirements N/A ❑ Pass ❑ Fail Metal roof shingles shall not be installed on slope less 3:12 N/A ❑ Pass ❑ Fail Metal valley flashing shall be the same material as roof [] N/A ❑ Pass ❑ Fail Metal valley flashing shall extend a min of 8" from the centerline with a min. of 3/4 " high splash diverter rib built-in at the flow line with sections overlapping a a min. of 4" Tile Roofs Requirements [it N/A ❑ Pass ❑ Fail Clay and concrete the shall have a min. 2-1/2:12 slope Slopes 4:12 and under require double underlayment The City of Wheat Ridge Inspection Check List notes Final Roof Notes A L U-60- I F- r r 0 �' � 1`14 �Ee- g Company Name: 0�)jE c n% Inspector signature: Date of Inspection: /ZJ 14070 Clear Creek Dr KIWO$M:N December 4, 2020 Evergreen Development 1873 South Bellaire Street, Suite 1200 Denver, CO 80222 Attn: Evergreen Development Re: Compliance Letter for Special Inspections Outlook Clear Creek, Permit No.: 201902583 4070 Clear Creek Drive, Building 2 Wheat Ridge, CO CG Project Noe. 19.23.225 Cole Garner f-AmAt technical 1070 W. 124 t" Ave, Ste. 300 Westminster, CO 802 34 303.996.2999 At your request,, Cole Garner Geotechnical (CGG) was retained to provide construction special inspection and materials testing for the above-named project. Observation and special inspection services were performed as scheduled by the contractor during the construction of the following elements: Fairestoppoing - periodic visual special inspection of membrane penetrations to verify adherence with manufacturer recommendations for UL rating Wood Framing -visual inspection of shear and gravity systems including member size, grade and orientation including hardware and fasteners The results of our special inspections were noted to comply with the approved project plans, specifications and relevant sections of the International Building Code. We trust that the information presented herein satisfies your present needs. Sincerely, irner Geotechnica Thomas C. Cole, P.E. Principal _M� 4070 Clear Creek Dr Colorado Department of Public Health and Environment 201902583 Laboratory Services Division 8100 Lowry Blvd. Denver, CO 80230 Phone: 303-692-3090 Fax 303-344-9989 Analysis Report Work Order#: 1528164 (Environmental Microbiology, Wa) Chain of Custody #: Description: Client: PLATTE RIVER PLUMBING Report To: LLOYD DECKER Profile: Environmental Microbiology, Water PLATTE RIVER PLUMBING PO BOX 640 Henderson, CO 80640 Sampled By: MEGAN LLOYD.PLATTERIVER@HOTMAIL.COM Sample Summary Lab ID Sample ID Sample Type Test Method Date Date Analytes Collected Received Reported 2100691237 084-13 Water Total Coliform and E. coli 03/25/21 10:50 03/25/21 12:07 2 P/A 2100691238 084-14 Water Total Coliform and E. coli P/A AWin�l •lA_ Scientific Director 03/25/2111:00 03/25/2112:07 Note: The samples were tested as received from the customer and the results in this report relate only to the samples tested. Friday, March 26, 2021 7:00:15 PM Page 1 of 3 Report ID: 1528164 - 14484336 -ERED By MRL = Minimum Reporting Limit; BDL = Below Detection Limit, *= Comment applied HORIZON' MCL = Maximum Contaminant Limit per EPA regulations, 3004 o 0 mg/L - milligrams per liter (ppm), ug/L micrograms per liter (ppb); pCi - picoCuries Colorado Department of Public Health and Environment Laboratory Services Division 8100 Lowry Blvd. Denver, CO 80230 Phone: 303-692-3090 Fax 303-344-9989 Analysis Report Work Order#: 1528164 (Environmental Microbiology, Wa) Sample Results Chain of Custody #: Lab ID: 2100691237 Sample ID: 084-13 Sample Type: Water Date Collected: 3/252021 10:50 Collection Site: Date Received: 3/252021 12:07 Site Description: Description: BLDG 2-100 LAV EVERGREEN CLEAR CREEK 4070 CLEAR CREEK DR WHEAT RIDGE CO 80401 EPA 92238 (Total Coliform and E. coli P/A) Parameter Results Units MRL MCL DF Prepared Analyzed Qual COLIFORM P/A ABSENT 1 3/26/2021 15:06 E. COLI P/A ABSENT 1 3/26/2021 15:06 Additional information Water Type: UNKNOWN Analysis Result Comments Analyte: COLIFORM P/A • ACOLIFORM P/A result of "ABSENT' indicates a microbiologically safe sample , Coliform was absent or less than one (<1) Coliform per 100mL Analyte: E. COLI P/A • An E.COLI P/A result of "ABSENT' indicates that E.coli was NOT DETECTED. Friday, March 26, 2021 7:00:15 PM Page 2 of 3 Report ID: 1528164 - 14484336 POAE RED BY MRL=Minimum Reporting Limit ;BDL =Below Detection Limit, *= Comment applied HORIZO03004 7 0 MCL = Maximum Contaminant Limit per EPA regulations, mg/L -milligrams per liter (ppm); ug/L micrograms per liter (ppb); pCi - picoCuries Colorado Department of Public Health and Environment Laboratory Services Division 8100 Lowry Blvd. Denver, CO 80230 Phone: 303-692-3090 Fax 303-344-9989 Analysis Report Work Order#: 1528164 (Environmental Microbiology, Wa) Sample Results (cont.) Chain of Custody #: Lab ID: 2100691238 Sample ID: 084-14 Sample Type: Water Date Collected: 3/252021 11:00 Collection Site: Date Received: 3/252021 12:07 Site Description: Description: BLDG 3-203 LAV EVERGREEN CLEAR CREEK 4044 CLEAR CREEK DR WHEAT RIDGE CO 80401 EPA 92238 (Total Coliform and E. coli P/A) Parameter Results Units MRL MCL DF Prepared Analyzed Qual COLIFORM P/A ABSENT 1 3/26/2021 15:06 E. COLI P/A ABSENT 1 3/26/2021 15:06 Additional information Water Type: UNKNOWN Analysis Result Comments Analyte: COLIFORM P/A • ACOLIFORM P/A result of "ABSENT' indicates a microbiologically safe sample , Coliform was absent or less than one (<1) Coliform per 100mL Analyte: E. COLI P/A • An E.COLI P/A result of "ABSENT' indicates that E.coli was NOT DETECTED. Friday, March 26, 2021 7:00:15 PM Page 3 of 3 Report ID: 1528164 - 14484336 POAE RED BY MRL=Minimum Reporting Limit ;BDL =Below Detection Limit, *= Comment applied HORIZO03004 7 0 MCL = Maximum Contaminant Limit per EPA regulations, mg/L -milligrams per liter (ppm); ug/L micrograms per liter (ppb); pCi - picoCuries (DNSC)LIE:)ATEE) mutual water SOIL AMENDMENT INSPECTION WWW.CMWC.NET Date: 3/11/20211 Time: I 9:30AM Employee: Robert Hazel Address: 4070 Clear Creek Dr. Status: 201902583 APPROVED Comment: Ok to final. For Inspection or to re -schedule an appointment, please call 303-238-0451. 48h our notice must be given for appointment USE WATER WISELY - CONSERVEI 4070 Clear Creek Dr 201902583 TNU United Test and Balance /A\ 10440 BredfCORd. Unit C Littleton,C80127 Certified Testing, Adjusting, and Balancing Report Project Information Project Name Clear Creek Crossing: ReportResvion Information Building II Address: 4044 Clear Creek Drive Wheat Ridge, CO 80033 Elevation: 5,459 &. Certified ReportDate. March 24,2021 Contractor Information BalancingTechnician John Wilcox Mechanical Contractor CBA Mechanical Mechanical Engineer. 5280JEngineering 720-320-7744 mgem@5280engi nee ring com www.DesignMEP.com RBIank528olEngineering 3-29-2021 Outlook Clear Creek Crossing: ise see notes on respective pages FanCoil airflow is within +_10% of manufacturers reo- fended sinews and therefore acceptable. APPROVED as Noted Architect KEPHART community • planning • architecture 2555 WALNUT ST=T DENVFA COLORADO 80205 uuul greM1mm Company Certification Information a SDVOSB m '°s. .�'y Sengber Fidelis Veteran Owned and Operated United Test and Balance T U jA\B 10440 Bradford Rd. Unit C Littleton, CO 80127 Warranty Information Dear Customer, As we try to build our customer base and ensure your complete satisfaction on every project United Test and Balance would like to extend a 180 Day warranty policy for every project The terms of the warranty are listed below: United Test and Balance does hereby w arrant the before said completed project for a period of 180 Days from the date of the issued Certified Test and Balance Report Thatsaid w ork shall remain free from all defects in workmanship and material, and that it shall comply with all the specific requirements of the Specifications and other Contract Documents governing the Testing, Adjusting, and Balancing. It is understood and agreed upon that in the event of defects and the necessity of making repairs, the Owner and/or Contractor w ill immediately notify United Test and Balance in writing of its conditions and shall give the contractor reasonable time, 30 days, in which to makes aid repairs. If any person, firm, or corporation other than United Test and Balance has, since the completion of the above work, performed or attempted to perform any repairs to the Mechanical Systems then this warranty will become null and void. This warranty does not cover any repairs made by anyone other than United Test and Balance or one of its authorized representatives. Thank you for the opportunity to work with you on this project and we look forw ard to w orkingw ith you in the future Sincerely, e_� acem(/ Jeremy Merrill Owner T.A.B.B. Certified Supervisor Sengber Fidelis Veteran Owned and Operated United Test and Balance T U /AX 10440 Rd. Unit C Littleton, C CO 80127 Abbreviation Index AC Air Conditioning Unit KW Kilowatt AHU Air Handling Unit LAT Leaving Air Temperature AMC orA Ampere LB Pound APD Air Pressure Drop LWT Leaving Water Temperature ATMOS Atmosphere MA Mixed Air BHP Brake Horsepower MAX Maximum BTU British Thermal Unit MIN Minimum BTUH BTU per Hour MAU MakeUpAir CFM Cubic Feet per Minute N/A No Access CHW Chilled Water Nom.Eff Nom final Efficiency CHWR C hilled Water Return OSA Outside Air CHWS C hilled Water Supply ODIID OursideDiameter I Inside Diameter CT Cooling Tower P Pump CUH Cabinet Unit Heater PD Pressure Drop CWR Condenser Water Return PF Power Factor CWS Condenser Water Supply PFPB Parallel Fan Power Box DB Dry Bulb (Temperature) PH Phase DEG or Degree PSI Pounds per Square Inch DPorAP Differential Pressure RA Return Air AT Differential Temperature RET Return (E) Existing RG Return Grille EA Exhaust Air RH Relative Humidity EAT Entering Air Temperature RPM Revolutions per Minute EF Exhaust Fan RTU Roof -Top Unit ER Exhaust Register SA SupplyAir ERV Energy Recovery Ventilator SD Supp ly Diffuser ESP External Static Pressure SP Static Pressure EWT Entering Water Temperature SF Service Factor OF Fahrenheit HOT Series Fan Power Box FOR Fan Power Box sq It Square Feet FCU Fan Coil Unit T-1IT-2IT-3 Terminal 1 ITerminal 21 Terminal FLA Full Load Amps THEM or0 Temperature FPM Feet per Minute TSP Total Static Pressure OF Feet T-Stat Thermostat NO Head V Volts HE Horsepower VAV Variable Air Volume HWR Hot Water Return AND Variable Frequency Drive HWS Hot Water Supply VP Velocity Pressure HE Herts (Cycles per Second) WB Wet Bulb Temperature IN. Inches w . Water Column KEF Kitchen Exhaust Fan w . Water Gauge Sengber Fidelis Veteran Owned and Operated z CCC Building 11 Corridor orarmg United Ted and 2slenm United TesBeen)at and Balance T\u/s PA. Unit C /A\ umimrel.Coaom Table Of Contents PROJECT Cl... C ... k Curling 311111 DATE 3,24CO21LOCATION: Wheat Ridge CO CONTACT Joh, Wl,o,PROJECT B 21 2550 AUTHOR Table OF Contents 1 Nr Handing Unit 3 1.1 FCC 5T 1A Floor 3 12 FCC 5f 1 a Fl000SPMT a 13 FCC 5T 2nd Floor 5 14 FCC 1 5T 2nd Floor/SPP 01 6 z CCC Building 11 Corridor orarmg United Ted and 2slenm Air Handling Unit LOCATION: Wheat Ridge CO PROJECT d 21 2550 DATE 3P24,2021 CONTACT John degree, AUTHOR Pool, Be,, SYSFEM/ONIT FCC 1.51flint Floor United Tedhord Red. Unit C st and=Balance Lintl Tested By John Wilcox Date: 3/18/2021 D DI OTent Depan ESP Par.penal 650 RPMAnnual Afflo. Nan RPMAnnual puppy Afflo. 109 RPMDA D 3mper Poston 100%Depan R PM fired Nine RPMMNorVoB Tl 12 21OVoltMaterial Tl 101 Anne Tested By John Wilcox Date: 3/18/2021 United Ted and 2slenm Page 5 of 15 DI Depan ESP On Join in no United Ted and 2slenm Page 5 of 15 U Tr jAX Air Handling Unit PROJECT: Clear Creek Crossing: Building 11 LOCATION: Wheat Rltlge, CO PROJECT R 21-2550 SYSTEM/ONIT: FCC 15T FSA ROONSPPL1 United Test and Balance I0440 D,,, tl1I III LNlewu. CS, W127 DATE: 3CV2021 CONTACT: John Wilcox AUTHOR Aadd Boma Toand iBy: Jofn Wilcox Date: 3/18(2021 0.02 0.00 0.00 0.16 n O -0.02 0.00 0.00 0.00 0.1s Ar Loan For,,,l Fuel Fluor So In 0 02 in Sir, Fuel Fluor So Orm No fox, ... n Sir, � t7i) 285 143 Supply Fan So Out 016, Sir, Heading Coil So In No fox, ... n Sir, Heading Coil So Out No fox, ... n Sir, 0.02 0.00 0.00 0.16 n O -0.02 0.00 0.00 0.00 0.1s Ar � t7i) 285 United Test and Balance Page 6 0115 285 143 112 lub United Test and Balance Page 6 0115 Air Handling Unit LOCATION: Wheat Ridge CO PROJECT d 21 2550 DATE 3P24,2021 CONTACT John degree, AUTHOR Poor, Be,, tPrJEM/ONIT FCC L5T2ntl Floor United Tedhored Red. Unit C st and=Balance HINSPIND Lintl Tested By John Wilcox Date: 3/18/2021 D D OTeat Par.Derial 650 RPMApril four. Me RPMDerian Outide Murray 113 RPMApril future four. 120 RPMare D 3mper Proton 100%Mci Tl 12 211 VoltMap r Pern V Tl 100 Area Tested By John Wilcox Date: 3/18/2021 United Ted and 2alenm Page 7 of 15 D United Ted and 2alenm Page 7 of 15 U Tr jAX Air Handling Unit PROJECT: Clear Creek Crossing: Building 11 LOCATION: Wheat Rltlge, CO PROJECT R 21-2550 SYSTEM/ONIT: FCC 15T2nd Floor/SPP 01 United Test and Balance I0440 D,,, tl1I III LNlewu. CS, 80127 DATE: 3CV2021 CONTACT: John Wilcox AUTHOR Aadd Boma Toand iBy: Jofn Wilcox Date: 3/18(2021 0.02 0.00 0.00 0.10 n O -0.02 0.00 0.00 0.0( D.lD rrAA Loan For,,,l Fuel Fluor So In 0 02 in Sir, Fuel Fluor So put No fox, ... n Sir, � t7i) 288 144 Supply Fan So Out 010, Sir, 0.02 0.00 0.00 0.10 n O -0.02 0.00 0.00 0.0( D.lD rrAA � t7i) 288 United Test and Balance Page 8 0115 288 144 ex Ion United Test and Balance Page 8 0115 Air Handling Unit LOCATION: Wheat Ridge CO PROJECT d 21 2550 DATE 3P24CF021 CONTACT John Jadl,o, AUTHOR Soon Be,, SYSFEWUNR: FCC L5T 3N Floor United Tedpord No. Unit C st and=Balance Lintl Tested By: JohnWlcoz Date: 3/18/2021 D DI OTeat Par.DepanArflate 550 CFMRural Afflove 717 (See Not.) CF MDepan Outide Arrive 113 CFMRural Outage Afflove 115 CFMOR D 3mper Poston 100%Depan R Pop Filed Fine RPMMci T1 T2 SOVotMcAorAmpe T1 101 Ande Tested By: JohnWlcoz Date: 3/18/2021 Log: FCC -1mpit Foor Colonel John wuoo. Need subn no United Ted and 2alenm Page 9 of 15 DI Depan ESP On Seen in up Log: FCC -1mpit Foor Colonel John wuoo. Need subn no United Ted and 2alenm Page 9 of 15 U Tr jAX Air Handling Unit PROJECT: Clear Creek Crossing: Building 11 LOCATION: Wonder Rltlge, CO PROJECT R 21-2550 SYSTEMNNIT: FCC 15T3rd Floor/SPP 01 United Test and Balance I04408,,d tl1I Look C Curlew". CS, W127 DATE: 3CV2021 CONTACT: John Wilcox AUTHOR Aadd Boma Toand iBy: Jofn Wilcox Date: 3/18(2021 0.02 0.00 0.00 0.12 7TO 7 t7i) -0.02 0.00 0.00 0.0( D.12 PUT I Sun Bird Flinn Roper B.....re Tape For,,,l Fuel Fluor So In 0 02 in Sir, Fuel Fluor So Orm No Rod, ... n Sir, 288 144 Supply Fan So Out 012, Sir, Hoping Coil So In No Rod, ... n Sir, Hoping Coil So pop No Rod, ... n Sir, 0.02 0.00 0.00 0.12 7TO 7 t7i) -0.02 0.00 0.00 0.0( D.12 PUT I Sun Bird Flinn Roper B.....re r. u RBlank Notes 3-29-2021: A 15ton unit typically Is rated minimally at 400 CFM/ton or (300 CFM nominal. N altitude (500tt+), manufacturer recommends 450 CFM per ton or615 CFMfora l Ston ED cooling unit At+10%a normal maximum would be ]42CFM. The Final All of 717 is les and therefore acceptable United Test and Balance Page 10 0115 288 144 1 In r. u RBlank Notes 3-29-2021: A 15ton unit typically Is rated minimally at 400 CFM/ton or (300 CFM nominal. N altitude (500tt+), manufacturer recommends 450 CFM per ton or615 CFMfora l Ston ED cooling unit At+10%a normal maximum would be ]42CFM. The Final All of 717 is les and therefore acceptable United Test and Balance Page 10 0115 Air Handling Unit LOCATION: Wheat Ridge CO PROJECT d 21 2550 DATE 3P24CF021 CONTACT John Jadl,o, AUTHOR Soon Be,, SYSFEWIL NR: FCC L5T drM1 Floor United Test and=Balance ROPPIND Lintl Tested By: JohnWlcoz Date: 3/18/2021 RogerTed Captain. Log: FCC -1 mauFire yieemn John wuoo. speed sound no United Ted and 2slenm Page 11 of 5 D OTeat PartDeriansurfloney 700 CFMRural And. 613 (See Not.) CF MDerian Rupee Friday 113 CFMRural proud And. 104 CFMCat D order Proton 100%FCC 1 an 4th Restated, FainMci Tl 12 211 Volt Tested By: JohnWlcoz Date: 3/18/2021 RogerTed Captain. Log: FCC -1 mauFire yieemn John wuoo. speed sound no United Ted and 2slenm Page 11 of 5 SYSTEM/UNIT: FCC-15TAth Floor/SPPL1 Toand tl By: Jofn Wilcox Date: 3/18(2021 Loan For,,,l Fuel Fluor So In 0 04 in Sir, United Test and Balance T�\B 30,140tlfnrtl<n flr1I bank LNlewu. CS, W127 Air Handling Unit 021 in Sir, Heading Coil So In PROJECT: Clear Creek Crossing : Building 11 Heading Coil So Cox DATE: 3242021 LOCATION: Wheal Rltlge, CO CONTACT: John Wilcox PROJECT P. 21-2550 AUTHOR earth Boma SYSTEM/UNIT: FCC-15TAth Floor/SPPL1 Toand tl By: Jofn Wilcox Date: 3/18(2021 HE "i N 1113 29 2021 A 1 and n on it typ led HIS is rated in inintrally at 400 CFFNVton 60 C t to therefore acceptable United Test and Balance Page 12 of 15 Loan For,,,l Fuel Fluor So In 0 04 in Sir, Fuel Fluor So Orm No Rod, ... n Sir, Supply Fan So Out 021 in Sir, Heading Coil So In No fox, ... n Sir, Heading Coil So Cox No fox, ... n Sir, HE "i N 1113 29 2021 A 1 and n on it typ led HIS is rated in inintrally at 400 CFFNVton 60 C t to therefore acceptable United Test and Balance Page 12 of 15 MECHANICAL SPECIFICATIONS HVAC SPECIFIC: 1 CURBS. SUPPORTS. and ANCHORS shall be provided for Mechanical work. No chain, tape, or wire. 2 SHEET METAL shall be SMACNA and Code standard with 45 degree maximum reducing, 20 degree maximum expanding transitions. Ductboard shall not be used. Provide listed flex connectors at duct connection to each piece of equipment. 3 DUCT INSULATION: Ducts shall be insulated as per IMC and IECC model energy code. RESIDENTIAL HVAC supply and return ducts located inside building envelope and above ceiling with heated living unit above do not require any duct Insulation. Where in the attic or outside the building thermal envelope, internally line RECTANGULAR HVAC supply and return ducts with Schuller (or Certainteed Type300) ASTM C 1071 B=$ UL -181 Class -1 anti -microbial Fiberglas ductliner attached with Stic-Klips 15" OC each way and 100% coverage of flame proof adhesive. Increase sheetmetal duct to allow for internal clear inside dimension shown on plans. Insulate ROUND ducts in similar locations with R-8 ASTM C 553 type -1 UL -181 Class -1 covered fiberglass wired and taped in place. COMMERCIAL (Clubhouse) HVAC supply ducts within building thermal envelope shall be insulated to R_6: in attic shall be insulated to R-8. Elbows for rectangular duct shall be provided multi -blade turning vanes or 1.5 centerline radius. Provide Ruskin ELF -118 or equal storm louvers with 1/4" galv mesh and 0.12" max air friction. Exhaust ducts need no insulation. 4 SEAL DUCT JOINTS AND SEAMS with Childers, 3-M, Hard -Cast or equal per Code. SPIRAL DUCT: Use listed joint sealant with neat sealant edges (use and remove mask -tape). 5 FIRE DAMPERS (FD). RADIATION DAMPERS (RD): Use Listed damper as approved by UL listing of assembly. Verify Floor/Ceiling Assembly = U1 -L550: Verify Ceiling/Attic Assembly = UL -P522. 6 FIRE CAULK Fire Rated wall / ceiling / floor penetration openings with Hilti or equal listed Fire Caulk. 9 TEST and AIR BALANCE all Common area HVAC systems to attain within 1OX of CFM air flow as shown on plans. LIVING UNIT: Contractor shall provide an Air Test and Balance Report one of each Apartment Unit Type - attain f15X of CFM airflow rates shown at each supply air diffuser. Ceiling exhaust fans need no balancing. Air CFM flow rates base on 0.062#/CF at 5000ft altitude by independent company NEBB or CTAB certified. Balance with dampers at main with registers wide open. Motors to draw 95% max nameplate amps. Tabulate all motors, grilles, registers, and diffusers with full typewritten Test and Balance Report submitted to Engineer for approval prior to Final Payment by Owner. GENERAL: 1 LOCAL and STATE CODES/ORDINANCES and CONDITIONS of CONTRACT shall be followed. SUBMIT plans to Building Department for Plan Review. Follow correction requirements. Pay all Fees and attain all Permits. 2 ADOPTED ENERGY CODE shall be followed. All equipment, insulation, and controls shall conform. 3 VISIT SITE daily to ascertain existing conditions prior to ordering equipment or fabricating duct and piping. 4 MECHANICAL / PLUMBING DRAWINGS are schematic and not to be scaled. Refer to Architectural/Certified drawings and site measurements for dimensions. 5 AS -BUILT scale drawings shall be provided by Contractor and submitted to Division 15 Engineer at completion showing all piping, duct, and equipment changes. 6 EQUIPMENT SHOWN ON DRAWINGS and SPECIFICATIONS: Contractor shall order, purchase, receive, uncrate, assemble, and install all items in conformance to Manufacturer's recommendations. Additionally Contractor shall install and final connect Owner furnished items as indicated on drawings. Contractor shall insure all equipment for full replacement value. 7 SHOP DRAWINGS: Contractor shall check Shop Drawings for 10OX compliance with Contract Documents. Submit four (4) copies to Division 15 Engineer for review prior to ordering. 8 BASE BID on specified equipment as shown on plans and in specifications. 9 SUBSTITUTIONS will be processed as change -orders after Bidding with all electrical, building alterations, and dollar amounts are included and approved in writing by owner prior to ordering equipment or fabrication. 10 EXTRA COSTS or CHANGES allowed only if approved in writing by Engineer with dollar amount prior to ordering. 11 ELECTRICAL COORDINATION: Confirm voltage, phase, and ampacity with Electrical Contractor prior to ordering equipment. All 24v controls including interlock wiring for Mechanical equipment by Division 15 Contractor. Provide magnetic starters for all 3-phase motors with protection on all three leads. Control and heating/cooling equipment to automatically restart after power failure. All wire in conduit per NEC latest edition. 12 CURBS. SUPPORTS. and ANCHORS shall be provided for MECHANICAL PLUMBING work. No chain, tape, wire. 13 SLEEVES and COLLARS shall be provided for all ductwork and pipes thru walls, floors, and ceilings. Provide chrome plated escutcheons for exposed piping penetrations thru ceilings, floors, and walls in finished areas. All water, soil, waste, vent and trim including fittings to be chrome plated where exposed. 14 CONCEAL all work in finished areas. 15 CUT and PATCH to match adjacent areas. No structural member shall be cut or notched. 16 OPERATING MANUAL shall be provided Owner and Engineer for all systems and equipment including manufacturer's maintenance manuals. Include lubrication, filter types and sizes, starting and stopping procedures. List Contractor's telephone numbers. 17 ONLY CONTRACTORS WITH EXPERIENCE on at least 3 similar projects of this type may bid. 18 RFI (Request For Information) from Contractor shall include at least one proposed solution which complies with the intent of Contract Documents. 19 MOCK-UP CLAUSE: for each unit type, Contractor shall substantially complete the installation of all HVAC equipment, ductwork, grilles, flues, combustion air, etc, for full coordination with all other trades. Attain approval from Architect, Engineer, Building Department and owner prior to installations of similar units of the some type 20. GUARANTEE all labor and new equipment for one year from the date of acceptance by Owner. Page 13 of 15 26 GAGE DRYER DUCT SEAL DUCT OPENINGS USING CITY THRU TOP -PLATE APPROVED FIRE CAULK AROUND BOTTOM CEILING IN JOIST ` AND TOP OF TOP -PLATE PENETRATION SPACE OR ROOF TO PER MANUFACTURERS RECOMMENDATIONS APPROVED BACKDRAFT WITH NQ FIRE DAMPER. DAMPER ~ WHERE RETURN AIR IS DUCTED, SECONDARY TOP -PLATE OF WALL I I " 26 GAGE 4"0 BATH FAN EXHAUST DUCT I UP THRU 2x4 TOP PLATE. ROUTE ABOVE DRYERBOX MODEL I FIRE RATED CEILING IN JOIST SPACE OR 425: 22 GAGE I I I THROUGH ROOF TO OUTSIDE. ALUMINIZED STEEL, ay I I 12.5"WIDE, 21 "TALL, I I " " +. 5.25 DEEP, 4 0 BATHROOM EXHAUST FAN (VERIFY 28 GAGE STEEL TOP CONN 1 0 HOUSING MINIMUM, 12"02" I I I 1 MAXIMUM WALL OPENING I I BE LISTED I I NOTE: NO CHASE, PRE -ROC I t 12X6 INTERIOR PARTITION WALL OR ADDITIONAL PROTECTION OF I (NOT FIRE RATED UNIT JOISTS ABOVE CEILING OR IN ��� I SEPARATION OR CORRIDOR WALL) ATTIC SPACE REQUIRED PER FIRE DAMPER (U.L LISTED FOR "ENGINEERING JUDGMENTS" OF NONE FIRE CAULK MANUFACTURERS. RATED ASSEMBLY BEING DRYER DUCT & BATH FAN DETAIL 4 No E HYDRONIC/DX FAN COIL UNIT ABOVE CEILING IN UNION RETURN AIR PLENUM RS/RL to M SECONDARY DRAIN: LITTLE GIANT MODEL ACS -4 SAFETY OVERFLOW SWITCH 3/4 -PRIMARY CONDENSATE DRAIN; ROUTE TO AIRGAP FITTING WITH ACCESS FOR MAINTENANCE CLEANING RM RETURN FILTER -/ROUND DUCT BELOW GRILLE WITH OPENING FIRE RATED CEILING TO TO RETURN AIR PLENUM AR OR rQ (SEE PLAN) �� 3/4"CW PLUMBING FIXTURE BY PLBG CONTR 3/4" W 1LL VL BY PLBG CONTR 3/4"HWR & 3/4 -HWS BY a._ PLBG CONTR ATYPICAL ROUND DUCT ABOVE FIRE RATED CEILING TO Sp WITH $Q RADIATION DAMPER (SEE PLAN) SA DUCT ABOVE CEILING INBETWEEN CEILING JOISTS `1404 UP THRU FIRE RATED CEILING WITH DYNAMIC RATED *IM LISTED FOR CEILING UL RATING. SEE SPECIFICATIONS. CONDENSATE DRAINS: PIPE PRIMARY 3/4" DWV COPPER FROM M PER SHEET NOTE. WHEN UNIT DOESN'T OPERATE, THE PRIMARY IS PLUGGED AND NEEDS TO BE RODDED CLEAN). I HOT WATER DX FAN COIL DETAIL �5� NONE CONNECT FLEX TO CONNECT TO SUPPLY AIR DUCT RL/RS LINES WITH FIRE DAMPER AT CEILING PENETRATION ROUTE 3/4" PRIMARY DRAIN WITH P -TRAP OVER FLOOR DRAIN; VERIFY FLOOR DRAIN IS IN FANCOIL ROOM (WITH RETURN AIR DUCTED) OR IF FLOOR DRAIN IS IN ADJACENT ROOM. ROUTE 4"OSA DUCT FROM EXTERIOR INTO WALL OF FANCOIL CLOSET AND STUB DUCT INTO FANCOIL ROOM WITH VC -1. FANCOIL UNIT (AIR HANDLER) NOTE: SPACE IN FANCOIL CLOSET IS A RETURN AIR PLENUM. OPEN FLOOR DRAIN IS ALLOWED WITH TRAP PRIMER ON FLOOR DRAIN CONN GROMMIT FANCOIL MOUNTING DETAIL GROMMIT r -LAG BOLT WALL BRACKET UNIT WALL BRACKET APARTMENT MECHANICAL EQUIPMENT LIST FANCOIL UNITS: FC -1.5T FAN COIL UNIT: FIRST CO model 24CDXQ, horizontal uncased; 650 CFM at 0.4"ESP, 1/5 HP fan motor, 23MBH heating coil at 3GPM built-in pump. Provide Flow Control Module, freeze -stat, factory built-in DX coil rated for 2.0 ton rated AC (match with 1.5Ton condenser unit), non -louvered access panel. Provide Honeywell VisionPro2000 programmable thermostat; 3/4"primary condensate drain to airgap over waste; LittleGiant ACS -4 Secondary Overflow Safety Switch on secondary drain to stop cooling on detection of high pan water. Electrical - verify with E.C. prior to ordering materials: 120V-1ph, 3MCA, 15MOCP. FC-2.OT FAN COIL UNIT; some as )M above except First Cc model 31CDXQ, 800 CFM at 0.40"ESP, 1/4 HP fan motor, 27.3 MBH heating coil, 2.5 ton rated coil (match with 2.OTon. FC -2.5T FAN COIL UNIT: some as )M above except First Co model 37CDXQ, 1,000 CFM at 0.40"ESP, dual 1/5 HP fan motors, 31.6 MBH heating coil. 3.0 ton rated coil (match with 2.5Ton 9W. CONDENSING UNITS: CU -1,5T CONDENSING UNIT: Carrier model CA13NA018, 1.5 ton ARI rated split system, SEER=13. Locate on grade with Cladlite pad, hail guard, pad isolators. Provide long -length kit with crankcase heater for piping lengths over 50ft. Refrigeration piping shall be ACR pre -charged with no excess tubing coils. Size and route refrigerant piping for appropriate lengths per mfgrs installation instructions. Insulate RS piping with 1/2" thick Armoflex. Provide 5 -year Mfgrs guarantee. Electrical Data: 208v/240-1 ph: 11.8 MCA, 20 max fuse. COMMON AREA CU's shall have Low Ambient Control. CU-2,OT COND UNIT: Some as above except CA13NA024, 2.0 ton; 17.7 MCA, 25 MFS. 0_2"5T GOND UNIT: Some as above except CA13NA030, 2.5 ton; 16.8 MCA, 25 MFS. EXHAUST FANS: EF BATH EXHAUST FAN: Panasonic model FV-0510VS1; 50 CFM at 0.25"SP; 120V-1ph, 0.2A, 3.5"thick, Energy Star rated. Provide 4"0 duct to exterior to exhaust hood with backdroft damper. Fan shall be "ON" with lights. Provide Aircycler model SmartExhaust control. EFK-100 APARTMENT VENTILATION FAN: Panasonic model FV-051OVS1; 50 CFM at 0.25"SP; 120V, 0.2A, 3.5"thick, Energy Star rated. Provide 4"0 duct to exterior to exhaust hood with backdroft damper. Fan shall be "ON" continuously per 2015 IMC residential code requirements. RH-1 RANGE HOOD: SPECIFIED BY ARCHITECT: non -ducted recirculating with approved charcoal filter. ELECTRIC HEATERS: EB-2ft ELECTRICAL BASEBOARD: Berko model BKO, 500 watts, 28"actual length. Provide built-in quiet acting T -stat, thermal high limit cutout and safety controls, UL approval, enamel finish. Verify 120V with Electrical Contractor prior to ordering. EH-1.5KW ELECTRIC HEATER: Markel model E3313TSRPW, 150OWatts at 120v. Provide wall box for surface mounting. Provide built-in thermostat ON below 50F. GRILLES. REGISTERS DIFFUSERS: JQ CEILING DIFFUSER: Shoemaker model 950 or approved alternate with multi -shutter damper, individual front adjustable blades, size as shown on plans. Note: Stamped steel will not be approved. MR WALL REGISTER: Shoemaker model 950 or approved alternate with multi -shutter damper, individual front adjustable blades, size as shown on plans. Stamped steel will not be approved. fM FILTER RETURN GRILLE: Shoemaker model FG or approved alternate filter grille, 1" filter included, size as shown on plan. j W ELEVATOR HOOD: Penn Airette, 12"x36" (3.Osgft min) rectangular intake hood, 1/4"goly mesh screen, 12" roof curb. Provide spring -open motorized dampers to be powered shut during normal operation. Dampers shall OPEN when any of the following occurs: 1) Detection of smoke at top of shaft. 2) Loss of power. 3) Manual Key Switch on Main Level or on Fire Command Center 4) Motorized dampers shall OPEN when Thermostat inside at top of elevator shaft near elevator equipment sensing temperature greater than 85!F; dampers shall CLOSE below 85F. COMMON AREAS MECHANICAL EQUIPMENT LIST FANCOIL UNITS: FCC -1.5T FAN COIL UNIT ertican: First Company model 24UC-6 vertical wall mount; 650 CFM at 0.6"ESP, 1/6 HP fan motor. Provide factory built-in 6KW at 240V-1ph actually 4.5KW at 208V-1ph electric heating coil; DX coil rated minimum 1.5 ton AC (match with 1.5Ton condenser unit). Provide Honeywell VisionPro8000 Commercial programmable thermostat IN RETURN PLENUM programmed FAN -ON continuously; 3/4"primary condensate drain to airgap over waste; LittleGiant ACS -4 Secondary Overflow Safety Switch on secondary drain to stop cooling on detection of high pan water. Electrical: 208V-1ph, 29MCA, 30MOCP. CONDENSING UNITS: CCU -1.5T CONDENSING UNIT: Carrier model CA13-018, 1.5 ton ARI rated split system, SEER=13. Locate on roof with Cladlite pad, hail guard, spring vibration isolators. Provide long -length kit with crankcase heater for piping lengths over 50ft. Refrigeration piping shall be ACR pre -charged with no excess tubing coils. Size and route refrigerant piping for appropriate lengths per mfgrs installation instructions. Insulate RS piping with 1/2" thick Armoflex. Provide 5 -year Mfgrs guarantee. Electrical Data: 208v/240-1 ph: 11.8 MCA, 20 max fuse. COMMON AREA CU's shall have Low Ambient Control. a�xe�:�r�:►yrra:�� EH-1.5KW ELECTRIC HEATER; Markel model E3313TSRPW, 150OWatts at 120v. Provide wall box for surface mounting. Provide built-in thermostat ON below 50F. EH-3KW ELECTRICAL WALL HEATER: Markel model H3423T, 3.0 KW at 208V-1 ph, surface mount. Provide built-in quiet -action T -stat, thermal high limit cutout and safety controls, UL approval, 16 gage arch grille. Verify voltage and phase prior to ordering. GRILLES. REGISTERS DIFFUSERS: �Q CEILING DIFFUSER: Shoemaker model 950 or approved alternate with multi -shutter damper, individual front adjustable blades, size as shown on plans. Note: Stamped steel will not be approved. MR WALL REGISTER: Shoemaker model 950 or approved alternate with multi -shutter damper, individual front adjustable blades, size as shown on plans. Stamped steel will not be approved. fffi FILTER RETURN GRILLE: Shoemaker model FG or approved alternate filter grille, 1" filter included, size as shown on plan. fJA ELEVATOR HOOD: Penn Airette, 12"x36" (3.Osgft min) rectangular intake hood, 1/4"gals mesh screen, 12" roof curb. Provide spring -open motorized dampers to be powered shut during normal operation. Dampers shall OPEN when any of the following occurs: 1) Detection of smoke at top of shaft. 2) Loss of power. 3) Manual Key Switch on Main Level or on Fire Command Center 4) Motorized dampers shall OPEN when Thermostat inside at top of elevator shaft near elevator equipment sensing temperature greater than 85'F; dampers shall CLOSE below 85'F. MECHANICAL LEGEND SYMBOL DESCRIPTION m SUPPLY DUCT UP SUPPLY DUCT DOWN RETURN OR EXHAUST DUCT UP 77' RETURN OR EXHAUST DUCT DOWN O ROUND DUCT SECTION UP TRUNK DUCT ELBOW (TURNING VANES REQ'D) TRUNK DUCT ELBOW 'D).5) REQ _F (NO TURNING VANES REQ D) __ �VOLUME DAMPER A RECTANGULAR BRANCH DUCT TO SIDE OF MAIN DUCT T ROUND BRANCH DUCT TO SIDE OF MAIN DUCT ROUND BRANCH DUCT TO TOP/BOTTOM OF MAIN DUCT SITE GLASS ON COMMON RS PIPING SYMBOL DESCRIPTION MBH `Y-1 (OSA DAMPER WITH APRILAIRE E BUILDING TYPE A 37 PLEX M1-1.2 8126A VENTILATION CONTROLLER. ® THERMOSTAT/SENSOR M1-1.3 WHERE RETURN AIR IS DUCTED, SECONDARY M1-2.1 CONNECT TO RETURN AIR DUCT) CONDENSATE DRAIN TYPE B 51 PLEX M1-2.2 DENVER, COLORADO 80205 WITH SAFETY DAMPER (U.L. LISTED M1-1.3 PROVIDE MERV-8 FILTER OVERFLOW SWITCH FOR RATED ASSEMBLY BEING M2-1.0 INSIDE FANCOIL FILTER FRAME j MM- ALL PIPING, VALVES, AND FITTINGS SHALL BE LISTED FOR DOMESTIC POTABLE WATER. HOT WATER DX FAN COIL DETAIL SCALE Ed FIRE DAMPER (U.L LISTED FOR NONE FANCOIL UNIT (AIR HANDLER) NOTE: SPACE IN FANCOIL CLOSET IS A RETURN AIR PLENUM. OPEN FLOOR DRAIN IS ALLOWED WITH TRAP PRIMER ON FLOOR DRAIN CONN GROMMIT FANCOIL MOUNTING DETAIL GROMMIT r -LAG BOLT WALL BRACKET UNIT WALL BRACKET APARTMENT MECHANICAL EQUIPMENT LIST FANCOIL UNITS: FC -1.5T FAN COIL UNIT: FIRST CO model 24CDXQ, horizontal uncased; 650 CFM at 0.4"ESP, 1/5 HP fan motor, 23MBH heating coil at 3GPM built-in pump. Provide Flow Control Module, freeze -stat, factory built-in DX coil rated for 2.0 ton rated AC (match with 1.5Ton condenser unit), non -louvered access panel. Provide Honeywell VisionPro2000 programmable thermostat; 3/4"primary condensate drain to airgap over waste; LittleGiant ACS -4 Secondary Overflow Safety Switch on secondary drain to stop cooling on detection of high pan water. Electrical - verify with E.C. prior to ordering materials: 120V-1ph, 3MCA, 15MOCP. FC-2.OT FAN COIL UNIT; some as )M above except First Cc model 31CDXQ, 800 CFM at 0.40"ESP, 1/4 HP fan motor, 27.3 MBH heating coil, 2.5 ton rated coil (match with 2.OTon. FC -2.5T FAN COIL UNIT: some as )M above except First Co model 37CDXQ, 1,000 CFM at 0.40"ESP, dual 1/5 HP fan motors, 31.6 MBH heating coil. 3.0 ton rated coil (match with 2.5Ton 9W. CONDENSING UNITS: CU -1,5T CONDENSING UNIT: Carrier model CA13NA018, 1.5 ton ARI rated split system, SEER=13. Locate on grade with Cladlite pad, hail guard, pad isolators. Provide long -length kit with crankcase heater for piping lengths over 50ft. Refrigeration piping shall be ACR pre -charged with no excess tubing coils. Size and route refrigerant piping for appropriate lengths per mfgrs installation instructions. Insulate RS piping with 1/2" thick Armoflex. Provide 5 -year Mfgrs guarantee. Electrical Data: 208v/240-1 ph: 11.8 MCA, 20 max fuse. COMMON AREA CU's shall have Low Ambient Control. CU-2,OT COND UNIT: Some as above except CA13NA024, 2.0 ton; 17.7 MCA, 25 MFS. 0_2"5T GOND UNIT: Some as above except CA13NA030, 2.5 ton; 16.8 MCA, 25 MFS. EXHAUST FANS: EF BATH EXHAUST FAN: Panasonic model FV-0510VS1; 50 CFM at 0.25"SP; 120V-1ph, 0.2A, 3.5"thick, Energy Star rated. Provide 4"0 duct to exterior to exhaust hood with backdroft damper. Fan shall be "ON" with lights. Provide Aircycler model SmartExhaust control. EFK-100 APARTMENT VENTILATION FAN: Panasonic model FV-051OVS1; 50 CFM at 0.25"SP; 120V, 0.2A, 3.5"thick, Energy Star rated. Provide 4"0 duct to exterior to exhaust hood with backdroft damper. Fan shall be "ON" continuously per 2015 IMC residential code requirements. RH-1 RANGE HOOD: SPECIFIED BY ARCHITECT: non -ducted recirculating with approved charcoal filter. ELECTRIC HEATERS: EB-2ft ELECTRICAL BASEBOARD: Berko model BKO, 500 watts, 28"actual length. Provide built-in quiet acting T -stat, thermal high limit cutout and safety controls, UL approval, enamel finish. Verify 120V with Electrical Contractor prior to ordering. EH-1.5KW ELECTRIC HEATER: Markel model E3313TSRPW, 150OWatts at 120v. Provide wall box for surface mounting. Provide built-in thermostat ON below 50F. GRILLES. REGISTERS DIFFUSERS: JQ CEILING DIFFUSER: Shoemaker model 950 or approved alternate with multi -shutter damper, individual front adjustable blades, size as shown on plans. Note: Stamped steel will not be approved. MR WALL REGISTER: Shoemaker model 950 or approved alternate with multi -shutter damper, individual front adjustable blades, size as shown on plans. Stamped steel will not be approved. fM FILTER RETURN GRILLE: Shoemaker model FG or approved alternate filter grille, 1" filter included, size as shown on plan. j W ELEVATOR HOOD: Penn Airette, 12"x36" (3.Osgft min) rectangular intake hood, 1/4"goly mesh screen, 12" roof curb. Provide spring -open motorized dampers to be powered shut during normal operation. Dampers shall OPEN when any of the following occurs: 1) Detection of smoke at top of shaft. 2) Loss of power. 3) Manual Key Switch on Main Level or on Fire Command Center 4) Motorized dampers shall OPEN when Thermostat inside at top of elevator shaft near elevator equipment sensing temperature greater than 85!F; dampers shall CLOSE below 85F. COMMON AREAS MECHANICAL EQUIPMENT LIST FANCOIL UNITS: FCC -1.5T FAN COIL UNIT ertican: First Company model 24UC-6 vertical wall mount; 650 CFM at 0.6"ESP, 1/6 HP fan motor. Provide factory built-in 6KW at 240V-1ph actually 4.5KW at 208V-1ph electric heating coil; DX coil rated minimum 1.5 ton AC (match with 1.5Ton condenser unit). Provide Honeywell VisionPro8000 Commercial programmable thermostat IN RETURN PLENUM programmed FAN -ON continuously; 3/4"primary condensate drain to airgap over waste; LittleGiant ACS -4 Secondary Overflow Safety Switch on secondary drain to stop cooling on detection of high pan water. Electrical: 208V-1ph, 29MCA, 30MOCP. CONDENSING UNITS: CCU -1.5T CONDENSING UNIT: Carrier model CA13-018, 1.5 ton ARI rated split system, SEER=13. Locate on roof with Cladlite pad, hail guard, spring vibration isolators. Provide long -length kit with crankcase heater for piping lengths over 50ft. Refrigeration piping shall be ACR pre -charged with no excess tubing coils. Size and route refrigerant piping for appropriate lengths per mfgrs installation instructions. Insulate RS piping with 1/2" thick Armoflex. Provide 5 -year Mfgrs guarantee. Electrical Data: 208v/240-1 ph: 11.8 MCA, 20 max fuse. COMMON AREA CU's shall have Low Ambient Control. a�xe�:�r�:►yrra:�� EH-1.5KW ELECTRIC HEATER; Markel model E3313TSRPW, 150OWatts at 120v. Provide wall box for surface mounting. Provide built-in thermostat ON below 50F. EH-3KW ELECTRICAL WALL HEATER: Markel model H3423T, 3.0 KW at 208V-1 ph, surface mount. Provide built-in quiet -action T -stat, thermal high limit cutout and safety controls, UL approval, 16 gage arch grille. Verify voltage and phase prior to ordering. GRILLES. REGISTERS DIFFUSERS: �Q CEILING DIFFUSER: Shoemaker model 950 or approved alternate with multi -shutter damper, individual front adjustable blades, size as shown on plans. Note: Stamped steel will not be approved. MR WALL REGISTER: Shoemaker model 950 or approved alternate with multi -shutter damper, individual front adjustable blades, size as shown on plans. Stamped steel will not be approved. fffi FILTER RETURN GRILLE: Shoemaker model FG or approved alternate filter grille, 1" filter included, size as shown on plan. fJA ELEVATOR HOOD: Penn Airette, 12"x36" (3.Osgft min) rectangular intake hood, 1/4"gals mesh screen, 12" roof curb. Provide spring -open motorized dampers to be powered shut during normal operation. Dampers shall OPEN when any of the following occurs: 1) Detection of smoke at top of shaft. 2) Loss of power. 3) Manual Key Switch on Main Level or on Fire Command Center 4) Motorized dampers shall OPEN when Thermostat inside at top of elevator shaft near elevator equipment sensing temperature greater than 85'F; dampers shall CLOSE below 85'F. MECHANICAL LEGEND SYMBOL DESCRIPTION m SUPPLY DUCT UP SUPPLY DUCT DOWN RETURN OR EXHAUST DUCT UP 77' RETURN OR EXHAUST DUCT DOWN O ROUND DUCT SECTION UP TRUNK DUCT ELBOW (TURNING VANES REQ'D) TRUNK DUCT ELBOW 'D).5) REQ _F (NO TURNING VANES REQ D) __ �VOLUME DAMPER A RECTANGULAR BRANCH DUCT TO SIDE OF MAIN DUCT T ROUND BRANCH DUCT TO SIDE OF MAIN DUCT ROUND BRANCH DUCT TO TOP/BOTTOM OF MAIN DUCT SITE GLASS ON COMMON RS PIPING SYMBOL DESCRIPTION M1-1.1 K E P H A R T BUILDING TYPE A 37 PLEX M1-1.2 community ■ planning ■ architecture ® THERMOSTAT/SENSOR M1-1.3 ROOF MECHANICAL PLAN BUILDING TYPE A 37 PLEX M1-2.1 2555 WALNUT STREET BUILDING TYPE B 51 PLEX M1-2.2 DENVER, COLORADO 80205 ®RADIATION DAMPER (U.L. LISTED M1-1.3 www.kePhe .com PLEX FOR RATED ASSEMBLY BEING M2-1.0 ENLARGED UNIT MECHANICAL PLANS PENETRATED) M2-1.1 ENLARGED UNIT MECHANICAL PLANS FIRE/ SMOKE DAMPER (U.L /S LISTED FOR RATED ASSEMBLY BEING PENETRATED)52HOIEngineering FIRE DAMPER (U.L LISTED FOR 720-320-7744 RATED ASSEMBLY BEING rogerb@5280engineering.com PENETRATED) www.DesignMEP.com SD SMOKE DETECTOR (DUCT) ROUND GALV STEEL DUCT INSUL FLEX ROUND DUCT �\�\\VY/////g\N%�� EQUIPMENT TAG PARTIAL HEIGHT "ROOF WALL" FOR CONDENSING UNIT RS/RL PIPING, DISCONNECTS, ETC (SEE ARCH) -WEATHER HOOD (Re: ARCH) /-RS/RL PIPING TO RESPECTIVE S!1 ON ROOF RL RS FILTER DRY IRS� RL - in RL J o! it ACCUMULATOR ON COMMON / AMENITY / CORRIDOR RL PIPING ROOF STAN BY GEN CONTR (Re: ARCH) VIB ISOLATION PAD; ALL 4 CORNERS NOTES: 1) SIZE REFRIGERANT PIPING PER MFGRS DESIGN. IF �in REFRIGERANT PIPING LENGTH EXCEEDS 50 FT CONTRACTOR SHALL FOLLOW RECOMMENDATIONS IN LONG LINE APPLICATION GUIDE PUBLISHED BY MANUFACTURER 2) PROVIDE THE FOLLOWING ACCESSORIES: FREEZE -STAT, TXV, FILTER DRIER, SOLENOID VALVE, HARD START KIT RS (LONG LINE APPLICATIONS). CONDENSING UNIT ON ROOF DETAILLr �1.� NONE X-2" 4.83' I 4'-10" I11 1 3'-2" I .� BOX WALL DUCT CONNECTION REAR OF DRYER 6'-4" I WASHER/DRYER STACKED 1 SCALE 9 NONE I KITCHEN EXHAUST FANL;ALL NONE Building Codes: (Wheat Ridge, CO) 2012 IMC, 2012 IECC MECHANICAL PLAN INDEX: MO -0.0 MECHANICAL INDEX, SPECIFICATIONS, EQUIPMENT LIST AND LEGEND M1-1.1 FIRST & SECOND FLOOR MECHANICAL PLANS BUILDING TYPE A 37 PLEX M1-1.2 THIRD FLOOR & FOURTH MECHANICAL PLANS BUILDING TYPE A 37 PLEX M1-1.3 ROOF MECHANICAL PLAN BUILDING TYPE A 37 PLEX M1-2.1 FIRST & SECOND FLOOR MECHANICAL PLANS BUILDING TYPE B 51 PLEX M1-2.2 THIRD FLOOR & FOURTH MECHANICAL PLANS BUILDING TYPE B 51 PLEX M1-1.3 ROOF MECHANICAL PLAN BUILDING TYPE B 51 PLEX M2-1.0 ENLARGED UNIT MECHANICAL PLANS M2-1.1 ENLARGED UNIT MECHANICAL PLANS c� z Y W W U a LU J U \�p0�\ 0� 3 REGIS,, 1% von LS-0B(q 1 BFo 24341 O C) </� ce O O U L.I.J V C) NOTE: THIS IS AN ELECTRONIC STAMP AND SIGNATURE Nol Date I Issue 08.12.19 PERMIT SET 11.15.19 I ISSUE FOR CONSTRUCTION Project Engineer Roger Blank, PE Project Designer LT, RWB Date 11.15.2019 Job Number 2017-045 Drawn By LT, RWB Checked By RBlank Title MECHANICAL INDEX, SPECIFICATIONS, EQUIPMENT LIST & LEGEND yr�asonrrara; M0-0.0 18809gl 1880sgl SECOND FLOOR MECHANICAL PLAN BUILDING TYPE B (51 PLEX) SCALE 1/8' = 1'-0' Page 14 of 15 FIRST FLOOR MECHANICAL PLAN BUILDING TYPE B (51 PLEX) SCALE 1/8' = V-0' BUILDING HVAC SHEET NOTES: CORRIDOR FAN—COIL UNIT Mount on wall below Fire Rated ceiling. Connect RS/RL refrigerant piping. Route SA supply air duct below Fre Rated ceiling above cosmetic ceiling; no fire damper required. Provide 3/4'Primary condensate over FD floor drain (see Plumbing). Provide Auxiliary Safety Overflow Switch for 2ndary condensate drain to stop cooling if primary is plugged. 2 COMMON AREA OUTSIDE AIR INTAKE: Route 8'0 OSA duct to return air connection on corridor FanCoil Unit with volume damper; set for CFM intake as shown. Verify no penetration of Fire Rated walls (no Fire/Smoke damper required). No backdroft damper required as fan is ON continuously. 3 ELEVATOR RELIEF HOOD: Verify rooftop mounted intake hood auto motorized damper per ELH equipment. Verify 39gft FREE AREA with louver mfgr prior to ordering. Route duct from ceiling of ELEVATOR EOMT ROOM to the roof hood inside Fire—Rated Shaft (Shaft by Gen Contr). 4 DUCT ROUTING: Locate below Fire Rated Ceiling above soffit or drop ceiling. 5 CONDENSING UNITS ON ROOF: Route RS/RL piping from evap coil in fan coil unit to respective S& condensing unit. Verify routing with manufacturer and Architect. 6 DUCT ROUTING: Route duct above Fire Rated Ceiling. Provide Ceiling Radiation Damper at penetrations. 7 FIRE/SMOKE DAMPER: Verify Fire—Rated wall / ceiling membrane. Provide Fire/Smoke damper in rated ® ' membrane penetration. 8 ELECTRICAL DISCONNECTS: Coordinate with Elect Contr to maintain a clear width of 30" and 36in front of each electrical disconnect. 9 DUCT ROUTING: Locate near Garage Ceiling (inside Fire Rated Soffit Enclosure by Gen Contr). ' 10 DUCT ROUTING: Locate in Attic with R-8 insulation. KEPHART community Is planning Is architecture 2555 WALNUT STREET DENVER, COLORADO 80205 w .kephaaxom 528o Engineering 120-320-7744 0 rogerb@5280engineering.com www.DesignMEP.com-_ Y W W U a LU J U O U Z LU 2 CL 0 LULU 0 Z LU DC LU LU O 0 Q �c O J O U Li V 0 W of \\000.0 0 REGISTnp/pii�j// oo� o�ER B( F�Fel ' 24341 NMNAImnmNGO\0\\0\\\0 ,2p2� NOTE: THIS IS AN ELECTRONIC STAMP AND SIGNATURE No I Date I Issue 08.12.19 PERMIT SET 11.15.19 ISSUE FOR CONSTRUCTION 02.17.20 RFI -005 (S1 Unit CFM update) 03.09.20 ASI#1 08.31.20 RFI -060 Units A3 & 32 10.08.20 RFI -074 Carriage Stair Heaters 10.09.20 RFI -073 Elev Lobby Duct Routing 10.24.20 RFI -077 20x10 SA Duct in Corridor Project Engineer Roger Blank, PE Project Designer LT, RWB Date 11.15.2019 Job Number 2017-045 Drawn By LT, RWB Checked By RBlank Title 1st & 2nd FLOOR MECHANICAL PLANS BLDG TYPE -B (51 PLEX) Sheet Number M1-2.1 1880sg1 FOURTH FLOOR MECHANICAL PLAN BUILDING TYPE B (51 PLEX) SCALE: 1/8" = 1'-0" Page 15 of 15 THIRD FLOOR MECHANICAL PLAN BUILDING TYPE B (51 PLEX) SCALE: 1/8" = 1 0 BUILDING HVAC SHEET NOTES: CORRIDOR FAN—COIL UNIT Mount on wall below Fire Rated ceiling. Connect RS/RL refrigerant piping. Route SA supply air duct below Fire Rated ceiling above cosmetic ceiling; no fire damper required. Provide 3/ePrimary condensate over FD floor drain (see Plumbing). Provide Auxiliary Safety Overflow Switch for 2ndary condensate drain to stop cooling if primary is plugged. 2 COMMON AREA OUTSIDE NR INTAKE: Route 8"0 OSA duct to return air connection on corridor FanCoil Unit with volume damper, set for CFM intake as shown. Verify no penetration of Fire Rated walls (no Fire/Smoke damper required). No backdroft damper required as fan is ON continuously. 3 ELEVATOR RELIEF HOOD: Verify rooftop mounted intake hood auto motorized damper per &R equipment. Verify 3sgft FREE AREA with louver mfgr prior to ordering. Route duct from ceiling of ELEVATOR EQMT ROOM to the roof hood inside Fire—Rated Shaft (Shaft by Gen Contr). 4 DUCT ROUTING: Locate below Fire Rated Ceiling above soffit or drop ceiling. 5 CONDENSING UNITS ON ROOF: Route RS/RL piping from evap coil in fan coil unit to respective JW condensing unit. Verify routing with manufacturer and Architect. 6 DUCT ROUTING: Route duct above Fire Rated Ceiling. Provide Ceiling Radiation Damper at penetrations. 7 FIRE/SMOKE DAMPER: Verify Fire—Rated wall / ceiling membrane. Provide Fre/Smoke damper in rated membrane penetration. maintain a clear width of 30" and 36"in front of each electrical disconnect. 9 DUCT ROUTING: Locate near Garage Ceiling (inside Fire Rated Soffit Enclosure by Gen Contr). 10 DUCT ROUTING: Locate in Attic with R-8 insulation. KEPHART community Is planning Is architecture 2555 WALNUT STREET DENVER, COLORADO 80205 w .kephaaxom 528o Engineering 120-320-7744 0 rogerb@5280engineering.com www.DesignMEP.com-_ Y W W U a LU J U O U Z LU 2 CL 0 LULU 0 Z LU DC LU LU O 0 Q �c O J O U Li V 0 W of \\000.0 0 REGISTnp/pii�j// oo� o�ER B( F�Fel ' 24341 NMNAImnmNGO\0\\0\\\0 ,2p2� NOTE: THIS IS AN ELECTRONIC STAMP AND SIGNATURE No I Date I Issue 08.12.19 PERMIT SET 11.15.19 ISSUE FOR CONSTRUCTION 02.17.20 RFI -005 (S1 Unit CFM update) 03.09.20 ASI#1 08.31.20 RFI -060 Units A3 & 32 10.08.20 RFI -074 Carriage Stair Heaters 10.09.20 RFI -073 Elev Lobby Duct Routing 10.24.20 RFI -077 20x10 SA Duct in Corridor Project Engineer Roger Blank, PE Project Designer LT, RWB Date 11.15.2019 Job Number 2017-045 Drawn By LT, RWB Checked By RBlank Title 3rd & 4th FLOOR MECHANICAL PLANS BLDG TYPE -B (51 PLEX) Sheet Number M1 1111111112..2 i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: JobAddress: Permit Number: CD ' 4 ❑ No one available for inspection: Time/� AM/PM Re -Inspection required: Yes` When corrections are complete, schedule re -inspection online. D,aEd t Inspecto CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: t Job Address: Permit Number: ❑ No one available for inspection: Time ?AM/PM Re -Inspection required: Yes ("'No _r *V 1 City of Wheat Ridge Multi -Family - New PERMIT - 201902583 PERMIT NO: 201902583 ISSUED: 02/19/2020 JOB ADDRESS: 4070 Clear Creek Dr EXPIRES: 08/20/2021 JOB DESCRIPTION: Clear Creek Crossing - Four story building with tuck -under garages, 51 units - 57,383 sq ft total *** CONTACTS *** OWNER EVERGREEN CLEAR CREEK CROSSING GC (303) 757-0401 Ron Wolford 180393 Nexus Builders LLC SUB (303)795-6116 MONTE LOSAW 160078 LOSAW ELECTRIC INC. SUB (303)288-2308 WILLIUAM C COFFEY III 110081 PLATTE RIVER PLUMBING INC. SUB (720)373-4378 CORY JOHNSTON 190344 CBA MECHANICAL *** PARCEL INFO *** ZONE CODE: UA / Unassigned USE: UA / Unassigned SUBDIVISION CODE: UA / Unassigned BLOCK/LOT#: / *** FEE SUMMARY *** ESTIMATED PROJECT VALUATION:7,425,600.00 FEES Total Valuation 0.00 Plan Review Fee 120.00 Use Tax 155, 937.60 Permit Fee 32,808.65 Engin. Review Fee 100.00 ** TOTAL ** 188,966.25 *** COMMENTS *** *** CONDITIONS *** Approval from presiding fire department required prior to final building inspection sign -off. All roughs to be done at Framing Inspection. No C.O. may be issued until public improvements are complete as identified in the Subdivision Improvement Agreement. All landscaping shall be installed in accordance with the approved landscape plan (Case No. WZ-19-01) prior to C.O. and pursuant to the phasing identified in the Subdivision Improvement Agreement. Per the SIA, installation of landscaping, street trees, and irrigation is not required prior to Certificate of Occupancy if issuance of the C.O. occurs outside of the planting season, generally October to June. Architectural elevations shall match the approved master plan permit. 1* � 4 41' PERMIT NO: JOB ADDRESS: JOB DESCRIPTION: City of Wheat Ridge Multi -Family - New PERMIT - 201902583 201902583 ISSUED: 02/19/2020 4070 Clear Creek Dr EXPIRES: 08/20/2021 Clear Creek Crossing - Four story building with tuck -under garages, 51 units - 57,383 sq ft total I, by my signature, do hereby attest that the work to be performed shall comply with all accompanying approved plans and specifications, applicable building codes, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with this�permrt. I further attest that I am leg ally authorized to include all entities named within this document as parties to the work to be performed and that all work to be performed is disclosed in this document and/or its' accompanying approved plans and specifications. Signature of OWNER or CONTRACTOR (Circle one) Date 1, This permit was issued based on the information provided in the permit application and accompanying plans and specifications and is subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures. 2. This permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and received prior to the date of expiration. An extension of no more than 180, days made be granted at the discretion of the Chief Building Official and may be subject to a fee equal to one-half of the original permit fee. 3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard requirements, fees and��procedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of the Chief Building Official and is not guaranteed. 4. No work of any manner shall be performed that shall results in a change of the natural flow of water without prior and specific approval. 5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all requ�ired inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services Division. 6. The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, anviolation of any provision of any �pplicabje code or any ordinance or regulation of this jurisdiction. Approval of work is subject to field inspection. 02/19/2020 Signature of Chief Building Official Date REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. ♦� City of Wheatldge COMMUNITY DEVELOPMENT CityofWheat Ridge Municipal Building 7500 W. 20 Ave. Wheat Ridge, CO 80033-8001 P: 303.235.2855 F: 303.237.8929 Permit Extension Request Form Permits expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and received prior to the date of expiration. An extension of no more than 180 days may be granted at the discretion of the Chief Building Official and may be subject to a fee equal to one-half of the original permit fee. Re -issuance or extension of expired permits is at the sole discretion of the Chief Building Official and is not guaranteed. Please complete this form in its entirety and submit to the Building Division at permits(cilci.wheahidge.co.us or fax to 303-237-8929. Party requesting permit extension: Evergreen Clear Creek Crossing Permit # 201902583 Property Address: 4070 Clear Creek Dr. Phone# 720-272-8725 Email Address: adeckert@evgre.com Reason for extension request: Delayed construction start Number of days requested: 4/30/2021 Printed Name: Amy Deckert Signature:_z"—' Date: 02/22/2021 For office use only This request has been: XI Approved ❑ Denied Extended =it 8/20/2021 Approved by: Daze: 2/22/2021 www.ci.whealridgaco.us I ®®A ®_ CITY OF WHEAT RIDGE e Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: r I Job Address: /-/V 70 C_, %c ` Gr'` " Permit Number:�j� f-.. �r p� r'" -fir'= � .°�' .r' t'�/il�loi F f�C" (' f`• C.''t'F f a s ❑ No one available for inspection: Time AN/PMP Re -Inspection required: Yes No When corrections are complete, schedule re -inspection online. Date:—, `I– Z-/ Inspector: DO NOT REMOVE THIS NOTICE i CITY OF WHEAT RIDGE C - Building Inspection Division (303) 235-2855 Office r INSPECTION NOTICE Inspection Type: d R I Job Address: /17 Permit Number: 4 9r4 ❑ No one available for inspection: Time AM/PM Re -Inspection required: Yes No When corrections are complete, schedule re -inspection online. Date: Inspector: DO NOT REMOVE THIS NOTICE ®� ® CITY OF WHEAT RIDGE ® Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address: ` Ci�P-1, Permit Number:Q- ❑ No one available for inspection: Time AM/PM Re -Inspection required: Yes No When corrections are complete, schedule re -inspection online. Date: - — / Inspector: DO NOT REMOVE THIS NOTICE 41 CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address: Permit Number: ❑ No one available for inspection: Time AM/PM Re -Inspection required: Yes No When corrections are complete, schedule re -inspection online. Date: - 2-1 —Inspector: DO NOT REMOVE THIS NOTICE 4' CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE A? I Inspection Type: Job Address: _ZIC� 76-2 Permit Number: 9, 5 q O Ll No one available for inspection: Time ASPM', WtOW, Re -Inspection required: Yes No When corrections are complete, schedule re -inspection online. Date: Inspector: DO NOT REMOVE THIS NOTICE i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address: Permit Number:2gziiQ_�_,,,'2��M3 ❑ No one available for inspection: Tial -- I ` R/pm Re -Inspection required: Yps,f No/ When corrections are complete, schedule re -inspection online. Dat Insp or: � f DO NOT R 11OJ/E THIS NOTICE 41 CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: /L4 x, Job Address: Permit Number: - L ❑ No one available for inspectio-n—TiVe Re -Inspection required: Yes No When corrections are complete, schedule re -inspection online. Date: Inspector: DO NOT REMOVE THIS NOTICE CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address: '7 Permit Number: U No one available for inspection: Time AM/P'M Re -inspection required:,, Yes No When corrections are complete, schedule re -inspection online. Date:—/- 70 _47/ Inspector: -�� DO NOT REMOVE THIS NOTICE � � � ✓ .CITY OF WHEAT RIQCE-.... _ . Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: �_ &E,Ue9s Job Address: -= T Xi Permit Number: ❑ No one available for inspection: Tirn AM/PM Re -Inspection required: Yes When corrections are Date: / '/ 4• re -inspection online. i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office. INSPECTION NOTICE Inspection Type:'( Job Address:' Vd rY } Permit Number:". ww ❑ No one available for inspection: Time J�-SAM/PM Re -Inspection required: YesCO-) When corrections have been made, schedule for re -inspection online at: httpJ/www.ci.wheatridge.co.usfinspect a Date: ` Insp c K DO NOT RE40VE THIS NOTICE t,\ M i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: gn 4E2nr� 1 C Job Address: - :- Permit Number: tz,ot it ",Jw�i�t ❑ No one available for inspection: Time AM/PM Re -Inspection required: Yes No When corrections are complete, schedu% Date• • Inspects `1 I CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE j. Inspection Type: i° Job Address: Permit Number: , a I 1 K)(0/2r �'-- ❑ No one available for inspection: Time 7M/PM Re -Inspection required: Yes No ,} When corrections have been made, schedule for re -inspection line at: ,.W YAMw .ci.wheatridge.co.uslinspectio� ,of Date: 7 � Inspector: '--� DO NOT REMOV THIS NOTICE V i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address: -e, s°<.: c,%R: A- Permit Number: �C.�l`j• z ❑ No one available for inspection: Time � AM/PM Re -Inspection required: Yes >_No When corrections have been made, schedule for re -inspection online at: http://Www.ci.wheatridge.co.uslinspection Date. Inspector: DO NOT REMOVE THIS NOTICE A CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address: Permit Number: 'z-' J No one available for inspection: Time — AM/PM Re -Inspection required: Yes No When corrections have been made, schedule for re -inspection online at: http://Www.ci. wheatridge.co.uslinspection Date: ;?,"—Inspector: DO NOT REMOVE THIS NOTICE Inspection Type: Job Address: Permit Number: CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE ❑ No one available for inspection: Time AM/PM Re -Inspection required: "Yes No When corrections have been made, schedule for re -inspection online at: h ttp://www. ci. wheatridge. co. usirinspection Date: Inspector: DO NOT REMOVE THIS NOTICE 41 CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address: Permit Number: IJ No one available for inspection: Time AM/PM Re -inspection required: '_Yes No When corrections have been made, schedule for re -inspection online at: http://Www.ci.wheatridge.co.uslinspection Date:— ?(- I/- Z / Inspector: DO NOT REMOVE THIS NOTICE o s CITY OF WHEAT RIDGE T Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE ❑ No one available for inspection: Time AMIPM Re -Inspection required: Yes 'No When corrections have been made, schedule for re -inspection online at: http://www.ci. wheatridge.co. usdnspection Date: Inspector: DO NOT REMOVE THIS NOTICE o CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type: 1-3 VV Job Address: Al 0 7 Q C- ff Cfe-- C r Lc ,dig" Permit Number: 2-0 ( q �2 Z_ 58 3 a ❑ No one available for inspection: Time �': .xAmfpi M Re -Inspection required: Yes No When corrections have been made, call for re -inspection at 303-234-5933 Date:' `a- r'spector:'� DO NOT REMOVE TH/S NOTICE i CITY OF WHEAT RIDGE �/- Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address Permit Number: ❑ No one available for inspection: Time AM/PM Re -Inspection required: Yes No When corrections have been made, schedule for re -inspection online at: http.Ilt,vww.ci.wheatridge.co.uslinspection Date: L,)- /7_ Z2 Inspector: ,`), DO NOT REMOVE THIS NOTICE A CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: -3,- C, LY,,, Job Address: �,,,,7e,/ Permit Number: _7r ,ci IJ No one available for inspection: Time AMiPM-, Re -Inspection required: Yes No When corrections have been made, schedule for re -inspection online at: http://Www.ci.wheatridge.co.uslinspection Date: _/. - /-' - 7-. Inspector: I I DO NOT REMOVE THIS NOTICE i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: �. Job Address: Permit Number: ..� i T4 Piz - 77 ❑ No one available for inspection: Tim (i�ld'M Re -Inspection required: Yes No When corrections have been made, schedule for online at: http.lwww.ci.wheatridge.co.usfins ec on �. Date 2 In'spe 41 CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address: Permit Number: < ❑ No one available for inspection: Time AM/PM Re -Inspection required: Yes No When corrections have been made, schedule for re -inspection online at: http://Www.ci.wheatridge.co.uslinspection Date: Inspector: DO NOT REMOVE THIS NOTICE i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address: Permit Number: ❑ No one available for inspection: Time AM/PM' Re -Inspection required: Yes No When corrections have been made, schedule for re -inspection online at: http://Www.ci.wheatridge.co.uslinspection Date: Inspector: ®O NOT REMOVE THIS NOTICE A 4' CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address: M14-_ 7C, Permit Number: ❑ No one available for inspection: Time AM/PM Re -inspection required: Yes No When corrections have been made, schedule for re -inspection online at: http.,Ilwww.ci.wheatridge.co.uslinspection Date: Inspector: DO NOT REMOVE THIS NOTICE A i CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type:'�.� Job Address: PermitNumber: ❑ No one available for inspection: Time ,f ' AM/PM Re -Inspection required: Yes No When corrections have been made, call for re -inspection at 303-234-5933 Date://,- Z55'- Inspector: DO NOT REMOVE THIS NOTICE i CITY OF WHEAT RIDGE Building Inspection Division (303) 234-5933 Inspection line (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type: / /� Job Address:F, ?/�� 1-- Permit Number: /� Q ,t , ❑ No one available for inspection: Time "' f„mss AWPM Re -Inspection required: Yes No When corrections have been made, call for re -inspection at 303-234-5933 ®ate: y -z Yc ' Inspector: .�� DO NOT REMOVE THIS NOTICE ®® 4 s_ CITY OF WHEAT RIDGE ® e Building Inspection Division (303) 235-2855 Office • (303) 237-8929 Fax INSPECTION NOTICE Inspection Type: d /V S Job Address: -�/Q T Permit Number: e/ � C ❑ No one available for inspection: Time - AM/PM Re -Inspection required:No When corrections have been made, call for re -inspection at 303-234-5933 ®ate: Inspector:fi DO NOT REMOVE THIS NOTICE 4' CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address: Permit Number: Ve U_/ ❑ No one available for inspection: Time /0 AM/PM Re -inspection required: Yes No When corrections have been made, schedule for re -inspection, online at: http://Www.ci.wheatridge.co.uslinspection Date: Inspector: DO NOT REMOVE THIS NOTICE ®_ CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address: Permit Number: ❑ No one available for inspection: Time `AM/PM Re -Inspection required: Yes No., *When corrections have been made, schedule for re -inspection online at: http://www.ci. wheatridge.co.us/inspection Date: Inspector: DO NOT REMOVE THIS NOTICE ♦ i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: ��'' Job Address: 4, LL ,� Permit Number: , jr� > �7G � F ❑ No one available for inspection: Time AM/PM Re -Inspection required: Yes No When corrections have been made, schedule for re -inspection online at: http://Www.ci. wheatridge.co.us/inspection Date: Inspector. DO NOT REMOVE THIS NOTICE A i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address: Permit Number: I.J No one available for inspection: Time AM/PM Re -Inspection required: Yes No When corrections have been made, schedule for re -inspection online at: http://Www, cL wheatridge. co. uslinspection Date: Inspector: k, 171. DO NOT REMOVE THIS NOTICE r CITY OF WHEAT RIDGE - Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE i Inspection Type: f Job Address: �- Permit Number: r F P ❑ No one available for inspection: Tim -_''j 4M/PM Re -Inspection required: Yes No When corrections have been made, schedule for re -inspection online at: httpYAvww. ci. wheatridge. co. uslinsp7ctio Da nsp A 41 CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address: Permit Number: _7g -/-f7 ❑ No one available for inspection: Time ANJIM Re -inspection required: Yes No When corrections have been made, schedule for re -inspection online at: http://Www.ci.wheatridge.co.uslinspection Date: Inspector: DO NOT REMOVE THIS NOTICE CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address: Permit Number: 3 _Qy Tfa fTicc."' /n1i /�iLrnbrslmS j`e%'� ��, Tte zT✓�14. ❑ No one available for inspection: Time AM/PM, Re -Inspection required: Yes No When corrections have been made, schedule for re -inspection online at: http://www. ci. wheatridge.co. uslinspection Date: Inspector: DO NOT REMOVE THIS NOTICE i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address: - Permit Number: ❑ No one available for inspection: Time 'AM/PM Re -Inspection required: Yes No When corrections have been made, schedule for re -inspection online at: http://www. ci. wheatridge.co. uslinspection Date: Inspector DO NOT REMOVE THIS NOTICE i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address: Permit Number: ❑ No one available for inspection: Time AM/PM Re -Inspection required: Yes No When corrections have been made, schedule for re -inspection online at: http://www. ci. wheatridge. co. us/inspection Date: Inspector: DO NOT REMOVE THIS NOTICE i CITY OF WHEAT :RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address. D< Permit Number:", i -02 ❑ No one available for inspection: Ti M Re -Inspection required: Yes When corrections have been made,s ien ne at: http;//www ci.wheatridge.co.us�nspec n Date. . )spoctor: CITY OF WHEAT FRIDGE ® Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address:1 Permit Number: ❑ No one available for inspection: Time AM/PM Re -Inspection required: Yes No When corrections have been made, schedule for re -inspection online at: http✓/www. ci. wheatridge. co. us/inspection Date: ?' Inspector: DO NOT REMOVE THIS NOTICE i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address:G Permit Number: ❑ No one available for inspection: Time AM/PM Re -Inspection required: Yes No When corrections have been made, schedule for re -inspection online at: http://Www.ci.wheatridge.co.usl'inspection Date: /6- :Z-g� - Inspector: DO NOT REMOVE THIS NOTICE ®1 ®_ CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address: Permit Number: ❑ No one available for inspection: Time AM/PM Re -Inspection required: Yes No When corrections have been made, schedule for re -inspection online at: http✓/www. ci. wheatridge. co. us/inspection Date: Inspector: DO NOT REMOVE THIS NOTICE CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE ❑ No one available for inspection: Time AM/PM Re -Inspection required: Yes No When corrections have been made, schedule for re -inspection online at: http://www. ci. wheatridge. co. us/inspection Date: Inspector: DO NOT REMOVE THIS NOTICE CITY OF WHEAT RIDGE. Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: D/33 Job Address: <1c7v /-k Permit Number: 2/", xy Uz : Y 3 � 1-1 No one available for inspection: Time _��)%M/PIVI Re -inspection required: T'YesNo When corrections have been made, schedule for re -inspection online at: httpYlwww.ci.wheatridge.co.us/inspection Date: Inspector: DO NOT REMOVE THIS NOTICE i i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address: Permit Number: ❑ No one available for inspection: Time AM%PM Re -Inspection required: Yes No When corrections have been made, schedule for re -inspection online at: http✓/www.ci. wheatridge. co. uslinspection Date: Inspector: DO NOT REMOVE THIS NOTICE i i j 1 3 ❑ No one available for inspection: Time AM%PM Re -Inspection required: Yes No When corrections have been made, schedule for re -inspection online at: http✓/www.ci. wheatridge. co. uslinspection Date: Inspector: DO NOT REMOVE THIS NOTICE i CITY OF WHEAT RIDGE - Building Inspection Division (303) 235-2855 Office Inspection Type: Job Address: Permit Number: INSPECTION NOTICE t ❑ No one available for inspection: TirnO L_MIPM Re -Inspection required: Yes 60) When corrections have been made, http✓/www.ci. wheatridge.co. usfilnspi Date10 4All I n for inspection online at: i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: 3/_3 /'/y / ±�2/ 6;6{ Job Address: 6g27C) C ,rte Permit Number: ?G�i 2 I.W/a •)Tj ,. r% a. - 5r," rziz ❑ No one available for inspection: Time AM,/PM, Re -Inspection required: Yes No When corrections have been made, schedule for re -inspection online at: http://www.ci. wheatridge.co. us/inspection Date: lr Inspector: ` DO NOT REMOVE THIS NOTICE / f L )/13 ` D oz ~ a D »« }&3 / z£° [ 1 � ¥ �/ . 7. / /CD CDQ \ 2 \ § Cl) 7 <. �) �( Z / C/) —K§ _ / mƒ \ 0 , e q E -n m« § \ \ _ 2 � . : I \ : `«< ^ \ ƒ � ¥ � 0 ' CD ` C- / »« }&3 z£° � �/ . 7. # 2 Cl) 7 . �) C/) —K§ `® mƒ \ 0 , e q E -n m« § \ \ _ 2 m$) . � 0 \ \ - ^ \ w 0 ( \ k � § m \\\ Z2( CL -4 3(D t7 l< (D V) �(DO U) M\\ \\ � ♦ A i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address. Permit Number: LJ No one available for inspection: Time AM/PM Re -Inspection required: Yes No _ When corrections have been made, schedule for re -inspection online at: http.,Ilivww.ci.wheatridge.co.uslinspection Date: Inspector: DO NOT REMOVE THIS NOTICE ♦ i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address: Permit Number: ❑ No one available for inspection: Time AMIPM Re -Inspection required: Yes No When corrections have been made, schedule for re -inspection online at: http://www.ci. wheatridge.co. usrnspection Date: Inspector: DO NOT REMOVE THIS NOTICE A i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: � y Job Address: Permit Number:'1 s d ❑ No one available for inspection: Timer AM/PM Wil• Re -Inspection required: Yes (Ngo When corrections have been made, schedule for re -inspection online at: http✓/www.ci.wheatridge.co.us inspectiop -I- - i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address: 4C,72 Permit Number: z ❑ No one available for inspection: Time :.n` P_'M)PM Re -Inspection required: Yes (ICIo When corrections have been made, schedule for re -inspection online at. http:Owww. ci. wheatridge. co, usrnspection Date: L Inspector:_ DOMT REMOVE THIS NOTICE August 26, 2020 Evergreen Development 1873 South Bellaire Street, Suite 1200 Denver, CO 80222 Attn: Dan Scholtz arner ^- techniccb­ 1070 W. 124 t" Ave, Ste. 300 Westminster, CO 80234 303.996.2999 Re: Compliance Letter for Special Inspection and Materials Tests Outlook Clear Creek, Permit No.: 201902583 4070 Clear Creek Drive, Building 2 Wheat Ridge, CO CG Project Noe. 19.23.225 1permit # 2019 02583 14070 Clear Creek Drive At your request,, Cole Garner Geotechnical (CGG) was retained to provide construction observations and materials testing for the above-named project. Observation and special inspection services were performed as scheduled by the contractor during the construction of the following elements: Excavation Observation -observation prior to foundation construction to verify conformance to with geotechnical report Reinforced Concrete -inspection of reinforcing steel and concrete placement for foundations and slabs Concrete Encased Grounding Rod - inspection of placement of Ufer ground rod in foundation Post -Tensioned Concrete - inspection of tendon layout,, concrete placement operations subsequent stressing operations Structural Masonry - visual inspection of reinforcing steel and grout placement In addition, materials tests were periodically conducted for the following elements: Concrete - temperature, slump, air content,, unit weight and compressive strength Grout - compressive strength and The results of our materials tests and special inspections were noted to comply with the approved project plans, specifications and relevant sections of the International Building Code. We trust that the information presented herein satisfies your present needs. Sincerely, ..... .r Geotechnical Thomas C. Cole, P.E. Principal DO �P��isLr'ION �t&ewo wi 4251 0. -o '0 8�2 20goo 00 /ON A)kPF-ffi ENS\ _M� ® C 4 _ CD p o ID CD< �® o W my CD cc e� C CD nCb m o c(b _07. CD � �`�° 0 ® C8 z � O 3 (D C n ri m 5 CD L'a a 0. a CL Cr N -0 Z cnn O Z O 1 m e 1® CA) (in N "( _ Ul Ply. m Ln ® 0 <• CD y o m CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE i Inspection Type: L, —,. /ic Job Address: 4JC ' Permit Number: ? c: ; y 1•r • �" 7`i w-�: i:`131�✓� .�?,f_-G:�.�-�!'Ws-;• r� rl!?��. r, ❑ No one available for inspection: Time !c: Re -Inspection required: Yes N When corrections have been made, sc edule for re -inspection online at: http://www. ci. wheatridge. co. ushnspection Date: `7- °t Inspector: 0 DO NOT REMOVE THIS NOTICE Clear Creek Crossing Building 2 4070 Clear Creek Drive Permit No. 2019 02583 Cole Garner Geotechnical 1070 West 124th Ave Suite 300 Westminister, CO 80234 Phone: 303.996.2999 Report of Inspection or 2 ©M 0 Z,5V Observation Client: Evergreen Development 1873 S. Bellaire, Suite 1200 Denver, CO 80222 Details Project: 19.23.225 Outlook Clear Creek 4040 Clear Creek Drive Wheat Ridge, CO 80215 Activity Date: 03/10/2020 Weather: Partly cloudy Technician: Todd Womersley Temperature (°F): 60 Work Completed Type: Open Hole Location Details: Building 2 Grade Beams Discrepancy: No Field Notes: CGG observed the subgrade beneath the subject grade beams. The soil appeared firm and stable for concrete placement. Reported to: Jacob Contractor: GBC Concrete Page 1 of 1 Cole Garner Geotechnical 1070 West 124th Ave ReinforcedPTConcrete Client: Project: Zc) ( 1' 02,S83 Suite 300 Evergreen Development 19.23.225 Westminister, CO 80234 1873 S. Bellaire, Suite 1200 Outlook Clear Creek Phone: 303.996.2999 Denver, CO 80222 4040 Clear Creek Drive Wheat Ridge, CO 80215 Activity Date: 03/10/2020 Activity Number: 8 Technician: Todd Womersley City Of: Wheat Ridge Weather: Clear Temperature (°F): 45 Environmental Placement Conditions: Cold Weather Provisions Work Completed Scope of Inspection: Reinforcing Only Location Details: Building 2 Grade Beams excluding a section of North side of perimeter Frequency: Asynchronous Level/Floor: 1 Plans & Details Referenced: S1-1.0, SG -1.0, and S3-0.0:1, 3, 4, 5, 6, 9, 10,12 Tendon PlacementtSize/Grade: No Anchor Bolts/Holdowns: No Consolidation Adequate: No Field Notes: Garage Walls were corrected Inspection Results Communicated To: Jacob w/ GBC Concrete Approved Mix Design Verified: No Deformed Bar Placement/Size/Grade: No Form Condition/Cover/Clearance: Yes Penetrations: Acceptable Page 1 of 2 Cole Garner Geotechnical 1070 West 124th Ave Suite 300 Westminister, CO 80234 Phone: 303.996.2999 ReinforcedMoncrete Client: Evergreen Development 1873 S. Bellaire, Suite 1200 Denver, CO 80222 Project: 19.23.225 Outlook Clear Creek 4040 Clear Creek Drive Wheat Ridge, CO 80215 Upload Image Image Description Image Date Taken Photographer Page 2 of 2 Cole Garner Geotechnical 1070 West 124th Ave Suite 300 Westminister, CO 80234 Phone: 303.996.2999 ReinforcedMoncrete 2,0 gOUS-3 Client: Evergreen Development 1873 S. Bellaire, Suite 1200 Denver, CO 80222 Activity Date: 04/21/2020 Activity Number: 46 Technician: Arthur Watson City Of: Wheat Ridge Weather: Sunny Temperature (°F): 62 Environmental Placement Conditions: Normal Work Completed Project: 19.23.225 Outlook Clear Creek 4040 Clear Creek Drive Wheat Ridge, CO 80215 Scope of Inspection: Reinforcing and Tendons Only Location Details: Building 2 (Type B) PT slab on grade Pour 1 including previously excluded section of grade beams adjacent to elevator pit Frequency: Asynchronous Level/Floor: Foundation level Plans & Details Referenced: Structural drawings SO -0.2, S1-2.0, S3-0.0 Dated 11-15-19; Barton PT shops PT3 Date 11-15-19 Tendon Placement/Size/Grade: Yes Anchor Bolts/Holdowns: Yes Consolidation Adequate: No Field Notes: Approved Mix Design Verified: No Deformed Bar Placement/Size/Grade: Yes Vertical Bars for CMU Conform with Masonry Plans: Yes Form Condition/Cover/Clearance: Yes Penetrations: Acceptable Tendon Anchorage/Backer Bars/Stud Rails: Verified Tendon and rebar reinforcement placed comply with project installation requirements and detail specifications including tendon quantity and spacing with no excessive tendon drape and reverse curvatures. Hold down schedule on SO -0.1 was referenced and comply with hold down location, type, and size. Barton shop drawings R1.02 and PT3 were used for partial reference. Concrete was not placed at initial inspection. UFER installed in grade beams adjacent to elevator pit. This section will be poured monolithically with the slab. Inspection Results Communicated To: Irving with GBC Concrete Discrepancy: No Page 1 of 1 Cole Garner Geotechnical 1070 West 124th Ave Suite 300 Westminister, CO 80234 Phone: 303.996.2999 Activity Date: 05/08/2020 Technician: Arthur Watson Weather: Cloudy ReinforcedMoncrete 2DI 9 02- 5S j Client: Project: Evergreen Development 19.23.225 1873 S. Bellaire, Suite 1200 Outlook Clear Creek Denver, CO 80222 4040 Clear Creek Drive Wheat Ridge, CO 80215 Location: Building 2 (Type B) Location Details: PT Slab on Grade Pour 2 Level/Floor: Foundation Level 1 Scope of Inspection: Reinforcing and Tendons Only Frequency: Asynchronous Deformed Bar Placement/Size/Grade: Yes Tendon Placement/Size/Grade: Yes Anchor Bolts / Holdowns: Yes Tendon Anchorage/Backer Bars/Stud Rails: Verified Activity Number: 96 City Of: Wheat Ridge Temperature (°F): 45 Work Completed Plans & Details Referenced: SO -0.2, S1-2.0, S3-0.0, SO -0.1 (Holdown schedule) Date 3/9/2020 and Barton Shops PT3 Date 11-15-19 Vertical Bars for CMU Conform with Masonry Plans: Not Applicable Form Condition/Cover/Clearance: Yes Penetrations: Acceptable Field Notes: Reinforcing complies with detail specifications including reinforcement size, quantity, and spacing as well as hold-down rods size and location. PT tendons comply with project installation requirements with acceptable C.G.S/chair heights with not excessive tendon drape and curvatures at initial inspection. Inspection Results Communicated To: Irving with GBC Page 1 of 1 2-oMozs23 ANCHOR ENGINEERING STRUCTURAL ENGINEERS May 8, 2020 Kephart Architects Attn: Janet Grady 2555 Walnut Street Denver, CO 80205 RE: Outlook Clear Creek Building 2, Pour 1 4070 Clear Creek Drive Wheat Ridge, CO 80215 Dear Mrs. Grady, Per our contract, our office reviewed tendon elongation report dated April 30, 2020 and May 5, 2020 provided by Cole Garner Geotechnical for the above referenced project. The reports indicate that the special inspector from Cole Gamer observed as the tendons were stressed using the following equipment: Ram No. PT Jacks & Accessories 2018-020 (#210) Gauge No. McDaniel (#210), 10,000 PSI, 4" Pump No. SPX Power Team, S/N 376088 (#210) The equipment was last calibrated on April 15, 2020. The corresponding stressing gauge pressure is 5,440 pounds per square inch when applying 33 kips of tension to the tendon. A copy of the associated calibration curve was provided to our office for our records and review. Based on the Post -Tension Stressing Report it appears several of the tendons did not meet the code allowed plus or minus 10% deviation. The tendons have been fully stressed to 33 kips twice already. There is a real risk of breaking tendons if the tendons are fully stressed a third time, which would result in a more significant problem than our current situation. Per section 9.4, Recording of the Construction and Maintenance Manual for Post -Tensioned Slab -on -Ground Foundations. Number 5 indicates "If the measured elongations do not fall within the allowable variance, discontinue stressing until the cause has been identified and a solution resolved" Our office highly recommends the steps and procedures as outlined in the Construction and Maintenance Manual for Post -Tensioned Slab -on -Ground Foundations be followed. In this specific case, when the tendons were not achieving the specified elongations, stressing operations should have stopped so that the cause could be ascertained prior to stressing other tendons. Our office has re -analyzed the slab considering the non -conforming elongations. Based on our analysis, the foundation will support the code required dead and live loads. However, please note that as a result of lower than expected average total elongation there is a reduced ability to predict the performance of the foundation in this pour. Ownership should be prepared for cracks to develop within this portion of the Building 2, Pour 1. Should they occur, our office recommends they be monitored and injected with structural epoxy so that moisture will not infiltrate the slab. Our office recommends using a structural epoxy applied per the manufacturers' specification to repair all cracks. The manufacturer should be contacted directly to determine the appropriate product and the life span of this product including guarantees and warranties. Submittals indicating the materials to be used should be submitted to our office for review prior to installation. Based on our review of the stressing records provided by Cole Gamer Geotechnical it is our opinion that the tendons indicated in the stressing records have been properly stressed and can be burnt off to a distance of 1/4" inside the exterior surface of the concrete. Stressing pockets should be packed with grout as outlined in the contract documents. Sincerely, Aughor-Luaineering, Inc. Charles D. Pe :i x, P.E. Project Engineer :- 2535 17'" STREET, DENVER, CO 80211 ❖ 303-783-4797 •: 303-830-9133 FAX °: 2,P1 �0Zs1S 5 ANCHOR ENGINEERING STRUCTURAL ENGINEERS May 27, 2020 Kephart Architects Attn: Janet Grady 2555 Walnut Street Denver, CO 80205 RE: Outlook Clear Creek Building 2, Pour 2 4070 Clear Creek Drive Wheat Ridge, CO 80215 Dear Mrs. Grady, Per our contract, our office reviewed tendon elongation report dated May 14, 2020 (Revised May 26, 2020) provided by Cole Garner Geotechnical for the above referenced project. The reports indicate that the special inspector from Cole Garner observed as the tendons were stressed using the following equipment: Ram No. PT Puller #206 Gauge No. #206 McDaniels, 10,000 PSI, 4" Pump No. SPX Power Team, #206, S/N 371136 The equipment was last calibrated on February 14, 2020. The corresponding stressing gauge pressure is 5,385 pounds per square inch when applying 33 kips of tension to the tendon. A copy of the associated calibration curve was provided to our office for our records and review. Based on our review of the stressing records tendons #12A, #12C, #17A, #30A, #36A, #38B, #39B, #42B, #45A, #45B, #47A & #57B did not meet the code allowed minus 10% deviation and needs to be re -stressed. Please re -stress the tendons indicated above as outlined in the contract documents and provide our office with the re -stressing report. It is our opinion that all other tendons have been adequately stressed and can be burnt off to a distance of 3/4" inside the exterior surface of the concrete. Stressing pockets should be packed with grout as outlined in the contract documents. If you have any questions or need additional information, please contact our office. Sincerely, Anchor En ineering, Inc. Charles D. Petzmger, P.E. Project Engineer 2535 17TH STREET, DENVER, CO 80211 303-783-4797 303-830-9133 FAX ❖ ZO) q C) 17, SIR 3 ANCHOR ENGINEERING STRUCTURAL ENGINEERS June 1, 2020 Kephart Architects Attn: Janet Grady 2555 Walnut Street Denver, CO 80205 RE: Outlook Clear Creek Building 2, Pour 2 4070 Clear Creek Drive Wheat Ridge, CO 80215 Dear Mrs. Grady, Per our contract, our office reviewed tendon elongation reports dated May 14, 2020 (Revised May 26, 2020) and May 30, 2020 provided by Cole Garner Geotechnical for the above referenced project. The reports indicate that the special inspector from Cole Garner observed as the tendons were stressed using the following equipment: Ram No. PT Puller #206 & Jack & Associates #302 Gauge No. #206 McDaniels, 10,000 PSI, 4"&#302 McDaniel, 10,000 PSI, 4" Pump No. SPX Power Team, #206, S/N 371136 & Enerpac, #302, S/N 1403 The equipment #206 was last calibrated on February 14, 2020 and equipment #302 was last calibrated on May 15, 2020. The corresponding stressing gauge pressure is 5,385 & 5,460 pounds per square inch respectively when applying 33 kips of tension to the tendon. A copy of the associated calibration curve was provided to our office for our records and review. Reports dated May 14, 2020 (Revised May 26, 2020) was for all of the tendons in the pour. After review of this report tendons #12A, #12C, #17A, #30A, #36A, #38B, #39B, #42B, #45A, #45B, #47A & #57B did not meet the code allowed minus 10% deviation and needs to be re -stressed. Report dated May 30, 2020 was the elongation report for the tendons that needed to be re -stressed. Based on our review of the stressing records, calibration curve, PTI allowances of +/- 1/4" elongations for short tendons, and the knowledge of the measurements taken to the nearest 1/8", it is our opinion that all the tendons included in these reports have been adequately stressed and can be burnt off to a distance of 3/4" inside the exterior surface of the concrete. Stressing pockets should be packed with grout as outlined in the contract documents. If you have any questions or need additional information, please contact our office. Sincerely, Anchor Engineering, Inc. Charles D. Petzinger, P.E. Project Engineer 2535 17T" STREET, DENVER, CO 80211 ❖ 303-783-4797 303-830-9133 FAX •: i CITY OF WHEAT RIDGE Building Inspection Division 6t' (303) 235-2855 Office �. _1�9r INSPECTION NOTICE Inspection Type: . Job Address:14 Ll .. Permit Number: ❑ No one available for inspection: 4 Re -Inspection required: Yes/No,i When corrections have been mad , sc ule for httpY www.ci.wheatridge,.coo.u�nspectio 177Te. I specto . at. i ? P g r J CITY OF WHEAT RIDGE' Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: is�Y--`'`` Job Address: he'Z•?<J Permit Number: ?cS S -:? ❑ No one available for inspection: Time AM/PM Re -Inspection required: Yes No When corrections have been made, schedule for re -inspection online at. http://www.ci. wheatridge. co. usrnspection 7- ec - ?G% Date: F Inspector: DO NOT REMOVE THIS NOTICE ,a ❑ No one available for inspection: Time AM/PM Re -Inspection required: Yes No When corrections have been made, schedule for re -inspection online at. http://www.ci. wheatridge. co. usrnspection 7- ec - ?G% Date: F Inspector: DO NOT REMOVE THIS NOTICE i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: /C--- Job Address: !!5f�','7l� Permit Number: r� 7z 3 ❑ No one available for inspection: Time AM/PM Re -Inspection required: (YesNo When corrections have been made, schedule for re -inspection online at: h ttp ✓/www. ci. wheatridge. co. uarinspection Date: C- 3G 2 Inspector: , DO NOT REMOVE THIS NOTICE CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: :. 3"? 3 Job Address: 41&'70 Permit Number: <64`1 LJ No one available for inspection: Time AM/PM Re -Inspection required: Yes No When corrections have been made, schedule for re -inspection online at: http.11www.ci.wheatridge.co.uslinspection Date: 5-` Inspector: DO NOT REMOVE THIS NOTICE i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: '�>? _5 'n -r- .5 Job Address: 'I e'_ -7G Permit Number: C 61 41 C - s 5-s 3 /♦i / � ,' �"' iii'% f,�[v Il- 7 ;� .5. •.Ind `. r.�L1 �s �: r ._. ❑ No one available for inspection: Time 4 rAM/PM Re -Inspection required: Yes No When corrections have been made, schedule for re -inspection online at: http✓/www. ci. wheatridge. co. uslinspection Date: S' ,1- � c, Inspector: l f DO NOT REMOVE THIS NOTICE i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: /1-17:/ 3 Job Address: 'VO 76' Permit Number: i U Z S� 3 ❑ No one available for inspection: Time AMOM Re -Inspection required: Yes No When corrections have been made, schedule for re -inspection online at: http://www. ci. wheatridge. co. uslinspection Date Inspector: A' DO NOT REMOVE THIS NOTICE FOR OFFICE USE ONLY APpmved by /� City of ( Wheatl"ge Pa.2�/w � � 5n5i2o2o COMMUNITY DEVELOPMENT i etor Date City of Wheat Ridge Municipal Building 7500 W.29 -Ave. Wheat Ridge. CO 80033-8001 P:303.2352846 F: 303.235.2857 FOUNDATION SETBACK AND ELEVATION CERTIFICATION For Commercial and Multi -Family Developments This form must be fully completed by a Professional Land Surveyor licensed in the State of Colorado. This form must be accompanied by a Construction Control Plan following the procedure found on the reverse side of this form. DATE; APRIL 30, 2020 PERMIT# 201902583 ADDRESS: 4070 CLEAR CREEK DRIVE, WHEATRIDGE, CO LOT 'BLOCK 1 OUTLOOK AT CLEAR CREEK CROSSING SUBDIVISION SURVEYOR: 1 hereby certify that the elevations and distances shown on the attached sheets and as stated below for the recently formed or constructed structural foundation for the above property have been measured by me or directly under my supervision. See the attached Form Check and Sheets 14, 17, & 18 of the Construction Control Plan. All measurements have been determined on the following location: (Check only one): X Top of proposed foundation wall prior to placement of concrete Top of foundation wall subsequent to placement of concrete The setback and elevation measurements are included on the attache) Prof.mional Surveyor Print Aaron Murphy Date 5-12-20 'Ian. wwwsi.whealriJge.u,. u, R. 11nme THE LINEAR UNITS FOR THIS SURVEY ARE U.S. SURVEY FEET. 2. THE PURPOSE OF THIS FORM CHECK IS TO SHOW THE DELTAS BETWEEN THE AS MEASURED FORMS AND THE PROPOSED BUILDING LOCATION. 3. THIS EXHIBIT DOES NOT CONSTITUTE A TITLE SEARCH BY HARRIS KOCHER SMITH TO DETERMINE OWNERSHIP OR EASEMENTS OF RECORD. 4. THIS EXHIBIT DOES NOT REPRESENT A MONUMENTED LAND SURVEY. THE FIELD WORK WAS PERFORMED BETWEEN THE DATES OF APRIL 22, 2020 AND APRIL 29, 2020. 2. BENCHMARK: BASIS OF ELEVATION BASED ON NGS CONTROL POINT "F 412", A STAINLESS STEEL ROAD AT THE INTERSECTION OF KIPLING STREET AND WEST 32ND AVENUE WITH A NAVD88 ELEVATION OF 5,562.74. "F 412" IS A FIRST ORDER, SECOND CLASS CONTROL POINT. 3. FORM CHECK ELEVATIONS ARE MEASURED TO TOP OF FORM UNLESS OTHERWISE NOTED. LEGEND XX.X DENOTES THE DISTANCE BETWEEN THE AS -MEASURED AND THE PROPOSED LOCATION XXXX.XX ELEVATION FORM CHECK AS -MEASURED LOCATION C O.XX CUT TO PROPOSED ELEVATION (INDICATES FORM IS HIGH) F O.XX FILL TO PROPOSED ELEVATION (INDICATES FORM IS LOW) 3 NEj m3 o 30 0 30 60 SCALE: 1" = 30' OUTLOOK CLEAR CREEK CROSSING HARRIS DATE REV SI ON COMMEN 15 CHECKED BY JMu KOCHER OUTLOOK CLEAR CREEK CROSSING DFAWN BY KDW SMITH EVERGREEN DEVCO, INC. SHEET NO 1120 Lincoln Steel Suite 1000 FORM CHECK Denver Colorado 80203 BUILDING 2 P'. 303 6456500 F. 303 623 6311 rouslootheSmltltmm MATCHLINE - SEE SHEET 9 MATCHLINE - SEE SHEET 18 (PENAL WE' 11L Ll. 1.11 xw au 1..' ur ua WAXr RO med«uslw :aw, mL9d RIgK lQwliriin« 'F'9irvrt . miE n1m, e, xuq'c N%P tM N aRibXi nw{mnrry c�dudr5 m 4RIw nc muer eas xm m.«s_dr r uwNdrw,we vxkr ILI >o nE xero i rtN mu, .an. w.w rnxurm w wa m mm .rar;. svx«As a® ww .. mE qumlrnox a IF sxvn + u.:I us. am», svcw« III rR .. a a.wq im.r _ iw.om. m�xows.a a+suo-n m xs error �.�ry mxrw,ne «wm :Uxw_m 5 LENNIEAnON 1. a.— rmr, sry m.. ndHe� Y«AYIN mw.wmsMw HARRIS m,uEa.m.ian corwxra is �yy ygsgq =SMITHER Evergreen OUTLOOK CLEAR CREEK �L axc, m SMITH ¢8 a«sn.w�Wa.,ax�m CONSTRUCTION CONTROL PLAN M� maurnrrrwr,xwxNwcswn.w.mwuassn EVERGREEN CLEAR CREM CROSSING LLC CLEAR CREM CRMSNG SIIBOIVIAON RLING NO. 3 •m,.,,�,y�,„ Cal p do 1° °arc ° HARRIS KOCHER �exL�ra�ar (AVERAGE flan a =oRN = aoe 2B', I EVERGREEN CLEAR CREM CROSSING LLC CLEAR CREM CRMSNG SIIBOIVIAON RLING NO. 3 MATCHLINE — SEE SHEET 13 4 Evergreen oevaloyment i wo... I... ne• KEYMAP ® •m,.,,�,y�,„ Cal p do 1° °arc ° HARRIS KOCHER M FF=_ (AVERAGE flan a =oRN = aoe 2B', MATCHLINE — SEE SHEET 13 4 Evergreen oevaloyment i wo... I... ne• KEYMAP ® I FF.5A5&T] M FF=_ (AVERAGE flan a =oRN = aoe 2B', OUTLOOK CLEAR CREEK CONSTRUCTION CONTROL PLAN • I • z f IF .1I.Tl=a ... vxa..oE o s vrc. rzo .c camas a i,n rmu wen s m s m,a �,.... •E.s a.�a" ,u.s �m na ma� s tas ilrmllV.n . D 'A' nas.e wocr..n xwwnm .., IW BY➢M XRµ • F pp "-10_ Y Mf r IMPxRt NI�,(D � � ss V� • $ flYFN]FS CEFIpGBW • ugtX YumxS�I qfm� =xJE n uN19IgeM iN trl emria Ercnww�u, xw Sinai 1+.trot rau w[x o.0 vrso wu • atu%ingoa woxm gamin Rz.0 t • G'QZO L.mt wN�awr ✓P06MOF, f 17 OF MATCHLINE —SEE SHEET 14 • Co mwW.W.+csuu �• I �� E��j XEYMAP p rr' 1.��.iw. ..�..�..� �>m.�o:r °h.°•• . ":�".:.nTa �.. •i w�.. �..�.E�X 4 ���• edf•• . p4 S �J O C>m �— • 4 \ u L• FF=545S27 Iw .....•EWW. V AB f (nVFFHGE TW OF FOAM = 54562E) L"• �- •• • � � • M�msi[ Lr Ls� n •✓• I 0 •••.9Yr• 4 • j' � j w w • •4 •.w• ` °4 i • vii I _ w vI a • B •• O: / • ern °u`♦.vi':1°"�w rr S i' <t O O • urnn xartc iF�5456.OB � • Uwm p l°� TX• : / Q ®/ ^ Y'A P • E4ECRIL HOILS •}•••a a row 'f+..w•I '�/� .�• v auv�Xnw eAww s. >.0 _ � e _ Y .MXt P MF WfrAYO W P X x • .�',� raaselr LrW me.+e •� ,•* ,s FF=5456.09 �%/• •e O • •• ,,, ', f • • • �•� ° • shin w° X¢y .° �Xs wow a�wo aX¢ oX ,4' AB \, / e O .� ••t\ ow'Xo�vnnas .WL xuwXrn XO ParwuX { I % •••o. . I� • : O • suevEruus cEHnrsemw °uI..wrP .11,ro1.. s. � c • ••PWWti• •Ia `wswso"mi. rz.•w°"M r ••a -� / o • .e m•s XS Mu°WOK ulXw ux+w n �&t �Wa ®•w�e.W� •wX�•W ®. �...ewa�www�•we_ • •ia�aa��.. �. •1�\. �wmW� j�lo:•'� pT / ci\ c .• •.W4WWQ•j • 43 .41 tM 5�L2 M 1V�: g ' PL G.NIPHI Vl ¢ MATCHLINE - SEE SHEET 21 381 Zo p� ➢�{,�� �`�p i "'•"yy;,,,p, �..,° �,•P�-IwIa•/�`>3��o��.:�SHARRIS � isauEosrelanamgs siax KOCHER OUTLOOK CLEAR CREEK rcwaamE*xPrs nmsa �¢eirvo CONSTRUCTION �s [ •� — r g46g w vswm• w wWnn ... � .. sa of u A i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address: Permit Number: ❑ No one available for inspection: Time ?'.'/C- (M)�M Re -Inspection required: "Yes No When corrections have been made, schedule for re -inspection online at: http://www. ci. wheatridge. co. usfinspection Date: Inspector: DO NOT REMOVE THIS NOTICE CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: �G 7 _56j!,; Job Address: f16176) Permit Number: '?U/61 Z4 _X/C Z- 44 ;2 J No one available for inspection: Time No Re -inspection required: When corrections have been made, schedule for re -inspection online at: httpzlAvww.ci.wheatridge.co.us/inspection Date: `2/- Inspector: ' DO NOT REMOVE THIS NOTICE i CITY -OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type:�C���� Job Address:T� Permit Number: '�:4 ; ❑ No one available for inspection: Tim- /PM Re -Inspection required: Yes. When corrections have been made, schedule for re -inspection online at: http:Owww.ci, wheatridge. Co. ualinspectfon t - Datei� Insp DO NOT RE VE THIS NOTICE CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: 107 _52 Job Address: 4k,`7e'2 L4,'1 --x 2211' Permit Number: - L=:;9 J No one available for inspection: Time /(_'1?.'3'5_CQPM Re -Inspection required: r'res? No When corrections have been made, schedule for re -inspection online at: http✓/www.cLwheatridge.co.uslinspection Date:— Inspector: A-/ DO NOT REMOVE THIS NOTICE IV. � I s CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: /(--,,/7 Job Address: �Dul C4 -'71/Z Permit Number: 'S 4 1--i/V" � No one available for inspection: Time K - M Re -inspection required: No 4�" ­/ y, - 4, - When corrections have been made, schedule for re -inspection online at: http://Www.cL wheatridge. co. usAnspection Date Inspector: DO NOT REMOVE THIS NOTICE CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: 10 7 - .S Job Address: CZZ 6i? Permit Number: �c/�f G,< S55' ❑ No one available for inspection: Time Re -Inspection required: est No 61 When corrections have been made, schedule for re -inspection online at: http✓/www. ci. wheatridge. co. us!►nspection Date: /-/- �'��'` `�G.r Inspector: A- DO NOT REMOVE THIS NOTICE A i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: _ Job Address: `� j `--- Permit Number: t .� ❑ No one available for inspection: Time AM/PM Re -Inspection required: Yes No When corrections have been madf ,-schedule for re -inspection online at: http://www. cL wheatridge. co. uslinspect� Dater - Inspec o A AA w//1T ACA/I/1�fC -ruNc+ Ai^-ry^- I* � 4 i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: ZU24/ Job Address: '5e,7C--' Permit Number: � r2 S�s3 ❑ No one available for inspection: Time AM/PM Re -Inspection required: Yes No When corrections have been made, schedule for re -inspection online at: http✓/www. ci. wheatridge. co. uslinspection Date: `�/-/-- Inspector: A` DO NOT REMOVE THIS NOTICE 1* � 4 i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address: `'7C1 i-tt� ���1th" ✓'�/? Permit Number: n,-,,cl Z S4 t i a ❑ No one available for inspection: Time (AMS PM Re -Inspection required: Yes No When corrections have been made, schedule for re -inspection online at: http✓/www. ci. wheatridge. co. usli'nspection Date: r .`q,. y = Inspector: At •'''� DO NOT REMOVE THIS NOTICE i CITY.OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: 22� 4 07K; v Job Address: `- �25 V) C� Permit Number: (� ❑ No one available for inspection: TimeL:::— AMTM Re -Inspection required: Yes ' When corrections have been made, schegyle for re-insp io►ronli g at: httpYwww.ci.wheatridge.co.uslinspectiov," 1 Datz -2& hspector: Geotech Cole Garner Geotechnical 1070 West 124th Ave Suite 300 Westminister, CO 80234 Phone: 303.996.2999 Reinforced PTConcrete Client: Project: Evergreen Development 19.23.225 1873 S. Bellaire, Suite 1200 Outlook Clear Creek Denver, CO 80222 4040 Clear Creek Drive Wheat Ridge, CO 80215 /zRlrer 0 Activity Date: 03/10/2020 Activity Number: 8 Technician: Todd Womersley City Of: Wheat Ridge 00 Tl� � Weather: Clear Temperature (°F): 45 Environmental Placement Conditions: Cold Weather Provisions Work Completed Scope of Inspection: Reinforcing Only Location Details: Building 2 Grade Beams excluding a section of North side of perimeter Frequency: Asynchronous Level/Floor: 1 Plans & Details Referenced: S1-1.0, SG -1.0, and S3-0.0:1, 3, 4, 5, 6, 9, 10,12 Tendon Placement/Size/Grade: No Anchor Bolts/Holdowns: No Consolidation Adequate: No Field Notes: Garage Walls were corrected Inspection Results Communicated To: Jacob w/ GBC Concrete Approved Mix Design Verified: No Deformed Bar Placement/Size/Grade: No Form Condition/Cover/Clearance: Yes Penetrations: Acceptable Page 1 of 2 Upload Image Image Description Image Date Taken Photographer 2Mr 111l"i . Garage Walls upon first 03/09/2020 Todd Womersley ' inspection A .. .mss .. Page 1 of 2 Cole Garner Geotechnical 1070 West 124th Ave Suite 300 Westminister, CO 80234 Phone: 303.996.2999 Reinforced PTConcrete Client: Evergreen Development 1873 S. Bellaire, Suite 1200 Denver. CO 80222 Project: 19.23.225 Outlook Clear Creek 4040 Clear Creek Drive Wheat Ridge, CO 80215 Upload Image Image Description Image Date Taken Photographer Page 2 of 2 CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: /05 SrZn'► 9144-1 Mh. .4-rrAIC. Job Address: Y070 6(44 ?� /)%? Permit Number: 70/1 og 543 ❑ No one available for inspection: Time Re -Inspection required: Yes /No, When corrections have been made, schedule for re -inspection online at: httpYAvww.ci. wheatridge.Co. usfinspection Date: ,3 - c1 ZO Inspector: DO NOT REMOVE THIS NOTICE No C.O. may be issued until public improvements are complete as identified in the Subdivision Improvement Agreement. All landscaping shall be installed in accordance with the approved landscape plan (Case No. WZ-19-01) prior to C.O. and pursuant to the phasing identified in the Subdivision Improvement Agreement. Per the SIA, installation of landscaping, street trees, and irrigation is not required prior to Certificate of Occupancy if issuance of the C.O. occurs outside of the planting season, generally October to June. Reviewed for Zoning Compliance by the �► l f City of Wheat Ridge Planning Division APPROVED,,// � -5 � 4076 aoao By: 'LT DATE: tZJ201, COMMENTS: ^Architectural elevations shall match the approved master plan permit. �1 ADDRESS PLAN 30'-0' rMs p 611 '111111 pi ii"P!LWM FBI so SH -81"n M -r rMs ■ �Ell W 1, Ir 10.10.1.1 �,ApQiillM! ..s,.. \� 40" vie omp ian 1I 12)031R Plan YEArniner Date of resit: The istemnce of o perndt or q*vovW of piens spe Pwtom and wmputotrons shall not be o pe►mJt fo , or on approval 01 ony Mlobon to ony of the proWsiams of the bwiding code or of mi' City ordinam t. Permits prewevng to give malsority to V Wo# or c+encet the provrsions of the ttA&V Lodes or other or*mmn of the City shW1 mot be vebat IN !*7 ■ KEPHART Evergreen 4470 rcs' ADDRESS PLAN p U pi ii"P!LWM am SUBMW M -r E -M ■ �Ell W 1, Ir 10.10.1.1 �,ApQiillM! ..s,.. \� 40" vie omp ian 1I 12)031R Plan YEArniner Date of resit: The istemnce of o perndt or q*vovW of piens spe Pwtom and wmputotrons shall not be o pe►mJt fo , or on approval 01 ony Mlobon to ony of the proWsiams of the bwiding code or of mi' City ordinam t. Permits prewevng to give malsority to V Wo# or c+encet the provrsions of the ttA&V Lodes or other or*mmn of the City shW1 mot be vebat IN !*7 ■ KEPHART Evergreen 4470 rcs' ADDRESS PLAN City of W heat jjdge COMMUNITY DEVELOPMENT City of Wheat Ridge Municipal Building 7500 W. 29th Ave. Wheat Ridge, CO 80033-8001 P: 303.235.2846 F: 303.235.2857 August 27, 2019 OFFICIAL ADDRESS CHANGE NOTIFICATION is hereby given that the following address has been assigned to the property/properties as indicated below: NEW ADDRESS: See Page 2 FORMER ADDRESS: Vacant Land • Subdivision: Clear Creek Crossing Subdivision Filing No. 2, Block 1, Lot 2, Section Parcel #: 39-194-04- 009 NOTES: This is a courtesy notification. AUTHORIZED BY: l- � t� DATE: c1 r DISTRIBUTION: 1. Property Owner 2. Addressinggieffco.us Jefferson County Assessor: Data Control, Lacey Baker; Jefferson County Elections: Holly Roth; Jeffco IT Services (Mapping): Steve Mitchel 3. Jeffco Public Schools, ATTN: Communication Services, 1829 Denver West Dr., Bldg. 27, Golden, CO 80401 4. U.S. Post Office, 1100 Johnson Rd., Golden CO 80401 5. Email to erlinda i.martinez &usps.aov and arlene.a.vickrey(&,,usps.gov and sheena.l.abeytaAusps.gov 6. Xcel Energy, sandra.cardenas(iDxcelenergy.com 7. Century Link, Capacity Provisioning Specialist, 5325 Zuni St., Room 728, Denver, CO 80221 8. Comcast, Attn: Scott Moore, 6850 S. Tucson Way, Englewood, CO 80112 9. Consolidated Mutual Water District 10. Applewood Sanitation District 11. West Metro Fire District 12. Wheat Ridge Planning Division 13. Wheat Ridge Building Division 14. GIS Specialist 15. Log File NOTE: Please notify all other parties concerned. ADDRESS MAP UPDATED BY: www.ci.wheatridge.coms DATE: CLEAR CREEK Vicinity Map U95 A N