HomeMy WebLinkAbout11723 W. 45th Place*e3gower July 2, 2021 11723 W 45th Place Wheat Ridge, Colorado 80033 Re: Blower Door Test for 11723 W45 th Place To whom it may concern: E3 Power performed a blower door test on the above-mentioned building on July 20, 2021, at 10:30 AM. The volume of the building was calculated to be 19,050 cubic feet. The final blower door number was 930 CFM @-50 pascals achieving an ACH of 3. The building meets the air tightness requirement and is compliant with code. Weather conditions; 81 degrees, Wind 4 MPH, no precipitation, 32% humidity. Site Conditions: 1. Exterior windows and doors, fireplace and stove doors were closed, but not sealed, beyond the intended weather stripping or other infiltration control measures; 2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers were closed, but not sealed beyond intended infiltration control measures; 3. Interior doors were open; 4. Heating and coming systems were turned off; and 5. Supply and return registers were fully open. Sincerely, Digitally signed Jessica W. Kurela (e3 power) Jessica by Jessica W. 303-292-1233 Kurela Building Analyst (BPI) W. KurelaDate: 2021.07.20 13:33:59 -06'00' 303.292.1233 120.281.0916 dpufeef.e11 off lef fAX A18 Indicate if the following have been installed (an efficiency shall not be listed) electric furnace gas -fire unvented room heater baseboard electric heater Designer/builder Clear Creek Terrace, LLC Code Edition 2018 IRC Date �H�OI �ZOZf Energy Efficiency Certificate 3• 'jit¢'i�iyiatasi '4'i�iy. �:.- r�il+�e a .11�f•.. z Ceiling/Roof R- 49 Vaulted R- N/A Walls Frame R- 21 Mass R- N/A Basement R- N/A Crawl Space R- N/A Floors Over Unconditioned Space R- 30 Slab Edge R- 10 Ducts Attic R- 8 Other R- N/A Blower Door 3 ACH/50 Pa. Duct Testing 4 Cfm/100 ftZ � -�R, Z.;1 t ZS ,,,ixti.°.: \�� .'%;� a•fo1Y9i" Inti?.';<� a=Y�'7.. Window U- 0.3 0.4 Opaque Door U- N/A N/A Skylight U- N/A N/A all. FAa Heating System Gas Forced Air 92% AFUE Cooling System Central AC 13 SEER Water Heater Gas (Storage Type) 0.67 Indicate if the following have been installed (an efficiency shall not be listed) electric furnace gas -fire unvented room heater baseboard electric heater Designer/builder Clear Creek Terrace, LLC Code Edition 2018 IRC Date �H�OI �ZOZf �% Ak ORO 3power July 2, 2021 11701 W45 th Place Wheat Ridge, Colorado 80033 Re: Blower Door Test for 11701 W 45th Place To whom it may concern: E3 Power performed a blower door test on the above-mentioned building on July 20, 2021, at 10:30 AM. The volume of the building was calculated to be 19,050 cubic feet. The final blower door number was 890 CFM @-50 pascals achieving an ACH of 3. The building meets the air tightness requirement and is compliant with code. Weather conditions: 81 degrees, Wind 4 MPH, no precipitation, 32% humidity. Site Conditions: 1. Exterior windows and doors, fireplace and stove doors were closed, but not sealed, beyond the intended weather stripping or other infiltration control measures; 2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers were closed, but not sealed beyond intended infiltration control measures; 3. Interior doors were open; 4. Heating and cooling systems were turned off; and 5. Supply and return registers were fully open. Sincerely, Jessica W. Kurela (e3 power) Jessica Digitally signed 303-292-1233 by Jessica W. Building Analyst (DPI) W. Kurela Date: 2021.07.20 Kurela 13:36:58 -06'001 303.292.1233 120.201.0116 dpoietmf , Floors 494: qt R- 30 Slab Edge R- 10 Ducts tial: d� Energy Efficiency Certificate 3 ACH/50 Pa. Duct Testing 4 Cfm/l00 ft' �ir2t1lYe.IdOf, ir,If io i� \'.alejz .riiq; Ceiling/Roof R- 49 `faulted R- N/A Walls Frame R- 21 Mass R- N/A Basement R- NIA Crawl Space R- N/A Floors Over Unconditioned Space R- 30 Slab Edge R- 10 Ducts Attic R- 8 Other R- N/A Blower Door 3 ACH/50 Pa. Duct Testing 4 Cfm/l00 ft' • a+d,:'�ir•+5r is ".e = \� '•°�,-" 'r� isira� - `�° y+'C �'F. Window U- 0.3 0.4 Opaque Door U- N/A NIA Skylight U- NIA N/A Heating System Gas Forced Air 92% AFUE Cooling System Central AC 13 SEER Water Heater Gas (Storage Type) 0.67 Indicate if the following have been installed (an efficiency shall not be listed) electric furnace gas -fire unvented room heater baseboard electric heater Designer/builder Clear Creek Terrace, LLC � f Code Edition 2018 IRC Date e3P,,ower July 2, 2021 11707 W45 1h Place Wheat Ridge, Colorado 80033 Re: Blower Door Test for 11707 W 45th Place To whom it may corncern: E3 Power performed a blower door test on the above-mentioned building on July 20, 2021, at 10:30 AM. The volume of the building was calculated to be 17,000 cubic feet. The final blower door number was 850 CFM @-50 pascals achieving an ACH of 3. The building meets the air tightness requirement and is compliant with code. Weather conditions: 81 degrees, Wind 4 MPH, no precipitation, 32% humidity. Site Conditions: 1. Exterior windows and doors, fireplace and stove doors were closed, but not sealed, beyond the intended weather stripping or other infiltration control measures; 2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers were closed, but not sealed beyond iintended infiltration control measures; 3. Interior doors werre open; 4. Heating and coaling systems were turned off; and 5. Supply and return registers were fully open. Sincerely, Jessica W. Kurela �e3 power) 303-292-1233 Building Analyst (BPI) Digitally signed Jessica by Jessica W. Kurela W. KU re l a Date: 2021.07.20 13:40:31 -06'00' 03.292AD flpluiv 6FfIU 110 Ad Indicate if the following have been installed (an efficiency shall not be listed) electric furnace gas -fire unvented room heater baseboard electric heater Designer/builder Clear Creek Terrace, LLC Code Edition 2018 IRCDate bYIC, I lec'm Energy Efficiency Certificate Ceiling/Roof R- 49 Vaulted R- NIA Walls Frame R- 21 Mass R- N/A Basement R- N/A Crawl Space R- NIA Floors Over Unconditioned Space R- 30 Slab Edge R- 10 Ducts Attic R- 8 Other R- N/A Blower Door 3 ACH/50 Pa. Duct Testing 4 Cfm/100 R2 ?i VYI S81t 'fKaaz qf� i � � Window U- 0.3 0.4 Opaque Door U- N/A NIA Skylight U- N/A NIA Heating System Gas Forced Air 92% AFUE Cooling System Central AC 13 SEER Water Heater Gas (Storage Type) 0.67 Indicate if the following have been installed (an efficiency shall not be listed) electric furnace gas -fire unvented room heater baseboard electric heater Designer/builder Clear Creek Terrace, LLC Code Edition 2018 IRCDate bYIC, I lec'm July 2, 2021 11713 W 45th Place Wheat Ridge, Colorado 80033 Re: Blower Door Test for 11713 W 45th Place To whom it may concern: E3 Power performed a blower door test on the above-mentioned building on July 20, 2021, at 10:30 AM. The volume of the building was calculated to be 17,000 cubic feet. The final blower door number was 850 CFM @-50 pascals achieving an ACH of 3. The building meets the airtightness requirement and is compliant with code. Weather conditions: 81 degrees, Wind 4 MPH, no precipitation, 32% humidity. Site Conditions: 1. Exterior windows and doors, fireplace and stove doors were closed, but not sealed, beyond the intended weather stripping or other infiltration control measures; 2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers were closed, but not sealed beyond untended infiltration control measures; 3. Interior doors were open; 4. Heating and cooling systems were turned off; and 5. Supply and return registers were fully open. Sincerely, Jessica W. Kurela (e3 power) 303-292-1233 Building Analyst (BPI) Jessica Digitally signed by Jessica W. Kurela W. KurelaDate: 2021.07.20 13:45:23 -06'00' 303.252.1233 120.281.0916 e3jereiml off Iff 11N it aa�f s '�• Energy Efficiency Certificate ltitii•Yi%te)S lglac=. rxc- ^al(- t ..,a,�?f? Ceiling/Roof R- 49 Vaulted R- N/A Walls Frame R- 21 Mass R- N/A Basement R- N/A Crawl Space R- N/A Floors Over Unconditioned Space R- 30 Slab Edge R- 10 Ducts Attic R- 8 Other R- N/A Blower Door 3 ACH/50 Pa. Duct Testing 4 Cfm/100 fe Window U- 0.3 0.4 Opaque Boor U- N/A N/A Skylight U- N/A N/A tit{t"8;4�+its 1r 5 a f� iE:' :! t { {icj{•, Heating System Gas Forced Air 92% AFUE Cooling System Central AC 13 SEER Water Heater Gas (Storage Type) 0.67 Indicate if the following have been installed (an efficiency shall not be listed) electric furnace gas -fire unvented room heater baseboard electric heater Designer/builder Clear Creek Terrace, LLC Code Edition 2018 IRC Date 0y/dt/W7,1 July 2, 2021 11719 W 45th Place Wheat Ridge, Colorado 80033 Re: Blower Door Test for 11719 W 45th Place To whom it may concern: E3 Power performeid a blower door test on the above-mentioned building on July 20, 2021, at 10:30 AM. The volume of the building was calculated to be 19,050 cubic feet. The final blower door number was 950 CFM @-50 pascals achieving an ACH of 3. The building meets the air tightness requirement and is compliant with code. Weather conditions: 81 degrees, Wind 4 MPH, no precipitation, 32% humidity. Site Conditions: 1. Exterior windows and doors, fireplace and stove doors were closed, but not sealed, beyond the intended weather stripping or other infiltration control measures; 2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers were closed, but not sealed beyond intended infiltration control measures; 3. Interior doors were open; 4. Heating and cooling systems were turned off; and 5. Supply and return registers were fully open. Sincerely, Jessica W. Kurela (e3 power) Jessica Digitally signed 303-292-1233 by Jessica W. Building Analyst (BPI) W Kurela • Date: 2021.07.20 Kurela 13:58:38 -06100' 303.292.1233 120.201.0916 e3poreiiml OfIM FIX it indicate if the following have been installed (an efficiency shall not be listed) electric furnace gas -fire unvented room heater baseboard electric heater Designer/builder Clear Creek Terrace, LLC Code Edition 2018 tRC Date O'1�Q1%x021 Energy Efficiency Certificate Ceiling/Roof R- 49 Vaulted R- N/A Walls Frame R- 21 Mass R- NIA Basement R- N/A Crawl Space R- NIA Floors Over Unconditioned Space R- 30 Slab Edge R- 10 Ducts Attic R- 8 tither R- NIA IA Blower Door 3 ACW50 Pa. Duct Testing 4 Cfm/100 ft' (" Window U- 0.3 0.4 Opaque Door U- N/A N/A Skylight U- N/A N/A "� �a�fi melf{�-RRA �9in79txra;(t+:. i a:a ,9 f Y'L•iaRc�r. Heating System Gas Forced Air 92%AFUE Cooling System Central AC 13 SEER Water Heater Gas (Storage Type) 0.67 indicate if the following have been installed (an efficiency shall not be listed) electric furnace gas -fire unvented room heater baseboard electric heater Designer/builder Clear Creek Terrace, LLC Code Edition 2018 tRC Date O'1�Q1%x021 11723 W 45th PI 202001062 October 19, 2020 Mr. Dan Garcia Mr. Duane Cerniglia 6825 S. Galena Street Clear Creek Terrace, LLC. Suite 314 6143 South Willow Drive, Suite 300 Centennial, C080112 Greenwood Village, Colorado 80111 T. 303 377 6601 F. 303 377 6656 RE: Post -Tensioned Slab -On -Grade Tendon and Reinforcing Observation www ruvengineerin9^com 11723, 11729, 11731, 11737 West 45" Place Lots 22, 21, 20, 19 Wheat Ridge, Colorado Foundation Plans: Prepared by MNA, Inc. Project Number: CCTTBLDGI Dated February 20, 2020, Revised July 17, 2020 Structural Plans: Prepared by MNA, Inc. Project Number: 4440TSTH Dated September 10, 2018, Revised July 17, 2020 Attn.: At your request MNA, Inc. conducted several observations of the post -tensioned slab -on - grade foundation at the above referenced address. The foundation was observed on October 9 and 16, 2020. The soils must be verified by the Geotechnical Engineer of Record. The dimensions and locations of the foundation where not verified during the observation and are the responsibility of the contractor performing the work. The foundation reinforcing and tendons were observed to be in general compliance with the above referenced plans on October 16, 2020. This reportis based on the limited accessibility of the elements and components of the structure at the time of the observation. This report is based on accepted general practice and is limited to the data available to our office. We make no warranty either expressed or implied. No invasive testing or inspections were performed. MNA Inc does not accept responsibility for hidden structural deficiencies not evident during an investigation of this type. Should you have any additional questions or concerns, please do not hesitate to call me at 303-377-6601. Sincerely, MNA, Inc. Gabriel Andrews, P.E. Structural Project Manager Reviewed by: Naim G. Nassar, RE PresidentlCEG STRUCTURAL ENGINEERING- CIVIL ENGINEERING - PLANNING - ARCHITECTURE Naw Nassar ='ea^- i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address: f Permit Number:' { -�C= l Q (IFS fi ❑ No one available for inspection: Time~` AM/PM Re -Inspection required: Yes 691 When corrections are complete, schedu!, 67 -inspection online. � Date041nspecto . DO NOT R OVE THIS NOTICE N* i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: /0 Ls Job Address: I-1 3 VJ L� S Permit Number: 26 Zoo t OS ,!:T ❑ No one available for inspection: Time AM/I Re -Inspection required: Yes too When corrections are complete, schedule re -inspection online. Date; 1-1VI-oz 1 Inspector: W, DO NOT REMOVE THIS NOTICE ♦�A Inspection Type: Job Address: Permit Number: CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE No one available for inspection: Time AM/PM Re -Inspection required: Yes No When corrections are complete, schedule re -inspection online. Date: Inspector: DO NOT REMOVE THIS NOTICE 11723 w 45th pl October 19, 2020 I Mr. Dan Garcia Mr. Duane Cemiglia 6825 S. Galena Street Clear Creek Terrace, LLC. Suite 314 6143 South Willow Drive, Suite 300 Centennial, Co 80112 Greenwood Village, Colorado 80111 T: 303.377.6601 F: 303.377.6656 RE: Post -Tensioned Slab -On -Grade Tendon and Reinforcing Observation www.mnaengineering.com 11723, 11729, 11731, 11737 West 45th Place Lots 22, 21, 20, 19 Wheat Ridge, Colorado Foundation Plans: Prepared by MNA, Inc. Project Number: CCTTBLDGI Dated: February 20, 2020, Revised July 17, 2020 Structural Plans: Prepared by MNA, Inc. Project Number: 4440TSTH Dated: September 10, 2018, Revised July 17, 2020 Attn.: At your request MNA, Inc. conducted several observations of the post -tensioned slab -on - grade foundation at the above referenced address. The foundation was observed on October 9 and 16, 2020. The soils must be verified by the Geotechnical Engineer of Record. The dimensions and locations of the foundation where not verified during the observation and are the responsibility of the contractor performing the work. The foundation reinforcing and tendons were observed to be in general compliance with the above referenced plans on October 16, 2020. This report is based on the limited accessibility of the elements and components of the structure at the time of the observation. This report is based on accepted general practice and is limited to the data available to our office. We make no warranty either expressed or implied. No invasive testing or inspections were performed. MNA Inc does not accept responsibility for hidden structural deficiencies not evident during an investigation of this type. Should you have any additional questions or concerns, please do not hesitate to call me at 303-377-6601. Sincerely, MNA, Inc. Gabriel Andrews, P.E. Structural Project Manager Reviewed by: Naim G. Nassar, P. President/CEO STRUCTURAL ENGINEERING - CIVIL ENGINEERING - PLANNING - ARCHITECTURE Naim Nassar °•-m :/ {iIvof W haat � ic��c (�t�ti;t.;i�'�:111 fel°r"tli?('t41ti[ FOR OFFICE USE ONLY Approved by: Inspector Date City of Wheat Ridge Municipal Building 7500 W. 29`h Ave. Wheat Ridge, CO 80033-8001 P: 303.235.2846 F: 303.235.2857 FOUNDATION SETBACK AND ELEVATION CERTIFICATION For Commercial and Multi -Family Developments This form must be fully completed by a Professional Land Surveyor licensed in the State of Colorado. This form must be accompanied by a Construction Control Plan following the procedure found on the reverse side of this form. 11723 W 45th P1 DATE: 01/05/2021 202000892 PERMIT# 202000892 ADDRESS: _11723. 11729. 11731.11737 West 451 Place LOT 19-22 , BLOCK 1 , Clear Creek Terrace SUBDIVISION SURVEYOR: I hereby certify that the elevations and distances shown on the attached sheets and as stated below for the recently formed or constructed structural foundation for the above property have been measured by me or directly under my supervision. The MINIMUM SETBACK DISTANCES from the property lines have been determined to be: FRONT: 4.5' REAR: 4.2' SIDE: 0' SIDE: 0' The foundation corner ELEVATIONS (NAVD88) have been determined to be: FRONT: 5413.60' REAR: 5413.52' SIDE: 5413.51' SIDE: 5413.60' All measurements have been determined on the following location: (Check only one): X Top of proposed foundation wall prior to placement of concrete Top of foundation wall subsequent to placement of concrete The setback and elevation measurements are included on the attached Construction Control Plan. Signed ional Surveyor�QQ O �P •.�C�iji�, T Print Thomas M. Girard PLS 38151 8151 Date 01/05/2021 /5/2021 I NO wwwxi.wheatridge.co.us Rev 11/2018 W Z W J W N � W a W N DESIGN =,4.5' II t AS DISTj= 4,5' o DESIGN 9' IDIST ' • AS DIST = 9 - AS 1' / / / DESIGN ELEV=6412.84 b AB ELEV = 1 II 0 mU II FU Vl< \ 20 19 20 oEo a 01 7 S9\\ GN E V5412.84 LEV EL DESIGN ELEV=5412.86 FL AB ELEV = SEL DESIGN ELEV=5412.50 F n - EL DESIGN ELEV=5412.86 FL AB ELEV = p I 3. r (SEE SHEET 4) MATCH LINE ESI N E v= 411 a9 > UJ a 5412 = 5411.68 5412 DE IGN ELEV=Sall 57 Q d p' AB ELEV = 5411.61 DESIGN - Ala' C 0 ccJ AS DIST - 4.5' e o IGN_ a. o ASIGN 9' • DESIGN = 1' 1 0� DIST- AS DIST = 1 1' ° h� - - --- 0 0 rT p C oV OO o W E DESIGN ELE =5411.33 DESIGN ELEV=5411.08 DESIGN ELEV=5412.67 \\ D Li AB ELEV = 5411.41 AB ELEV = b 0 0 CD W F AB ELEV = o0 M WLo E \ 3 �m CS II O t p d Cn o E �� CDUco0w TO RESIGN ELEV=5411.50 w O BOW DE IGN ELEV-5407.50 V <v TOW AB ELEV X5411.53 DF AG. v1z ° BOW AB ELEV =� cJ7 21 22 02 n =5413.59 ¢ W \ = 5413.54 � a Z i � B DIS NCE 4' SIGN ETB - 11 E p D I DESIGN ELEV=5412.06 \ FL AB ELEV = \� ALLEY C TRACT B p \ \ \ \ \ \ c \ I- r \\ L II 23 � � 24 I° Z \ DESIGD N ¢ \ AB FFI Z N \ 20in \ ca \\ F-DEESIFGN ELEV=5413.59 = 10' DESIGN = 4 5' -4.55' 9 p p DESIGN ELE AB ELEV = J 25 561 3 59 5413.59 DE GN E V=5 12. AB LEV c p p o, 4 0 DESIGN ELE AB ELEV = z. p EL DESIGN E V=5411.16 FL AB ELEV 5411.27 g EL DEGN ELEV=5411.05 ITL AB ELEV = 5410.98 p N V) / °P rL DESIGN ELEV=5411.89 ZCle(W�IIDII rL AB ELE = 5411.84 SIGN ELEV=5411.50 4b W DESIGN ELEV=5411.65 OW AB ELEV = 5411.49 BOW AB ELEV = 5407.56 COESIGN ELEV=5411.93 / AB ELEV = / EL DESIGN ELEV=5411.62 FL AB ELEV = INV ELEV = 54 541 1.94INV AB ELEV - rL DESIGN ELEV=5411.90 FL AB ELEV = 5411.95 V = 5412.37 V LLLV = ELEV = DESIGN ELEv=5d19 A5 AB ELEV = 5412.84 26 5' WAI p � D iA p 0 EV=541299 = 5412.24 E E UEv-ad10 00 = 5412.29 BW DESIGN ELEV=5 12.1 IBW AB ELEV = FW AB ELEV = p 4' WALK IL DESIGN ELEv=5dt29n- �S, rL AB ELEV = 5412.29 �2 �5610 an � 5412.64 _ DESIGN L Ev-5410 Oil = 5412.18 DESI N E =S6 0 19 ° AB EV 5412.19 1u5ra< F D �DQSIGN = 1n' = 9' DESIGN = 0' AB DIST= 10' 5413 • of = 9' AS DIST = 9' DESIGN = d_s' - -5410--__ 1 =4.5CA10 p D 'D L4 _ -I I ID GRATE ELEV 5411.14 INV=5408.71 GRATE AB ELEV = INV OUT AB = GRATE ELEV = 5410.9& INV IN = 5408.47 INV OUT = 5407.97 GRATE AB ELEV = INV IN AB = INV OUT AB = DESIGN ELEV=5413.38-/ AB ELEV = TOW DESIGN ELEV=5412.16- BOW DESIGN ELE"` TOW AB ELEV = 5411.74 BOW AB ELEV = 5411.23 ESV=5d193',j1DESIGN ELEV=5412.73 ' = 5412.21 AB ELEV = 5412.69 LBW DESIGN ELEV--5412.04 BW AB ELEV = FW AB ELEV = N' V I TO DESIGN ELEV=5411.79 BO DESIGN ELF"-"" " TB 0)O AB ELEV - 5411.00 5411.83 D I LGRATE ELEV = 5410.10 `INV = 5407.53 -TOW DESIGN ELEV=5412.25 INV AB = BOW DESIGN ELF"-"" �' INV IN = 5407.67 TOW AB ELEV = rA11 7A INV OUT = 5407.64 BOW AB ELEV = 5411.23 GRATE AB ELEV = 5409.79 BW DESIGN ELEV=o+iv.io INV IN AB = INV OUT AB BW AB ELEV = = FW AB ELEV = TOW DESIGN ELEV=5412.00 BOW DESIGN ELEV=5407.50 TOW AB ELEV = 5411.95 BOW AB ELEV = 5407.57 rL DESIGN ELEV=5412.50 FL AB ELEV = 5412.53 10 0 10 10 20 ( 1N FEET ) 1 inch = 10 ft NOTES: 1. ALL ADA RAMPS SHALL BE SHOT AT THE TOP AND BOTTOM TO ENSURE GRADES MEET ADA REQUIREMENTS. 2. ALL SHOTS ON SIDEWALKS SHALL BE COMPRISED OF TWO (2) SHOTS TAKEN DIRECTLY ACROSS FROM ONE ANOTHER TO ASSURE ADA COMPLIANCE (<2% CROSS -SLOPE) AT APPROXIMATELY 100 -FOOT INTERVALS. 3. ALL CURB AND GUTTER SHOTS SHALL BE IN THE FLOWLINE AT THE LOCATIONS M Z > UJ a m W J f Q d z UCD Z C 0 ccJ U)U) e o to y E Ujd N d; t1 2 co Ow i V N rT 0 0 3 p C oV OO o W LU 3 � J � de ao co Q 0 0 CD W F o0 M WLo E 3 �m CS A 0 d Cn o E V CDUco0w CD w O Y Z > UJ a m W J f Q d z ,W+ V Z 0 ccJ U)U) W o W Z Ujd UID co Ow i V N Uj W Z p To request marking of underground facilities 0 W V F J :LN C� Q � F J F V N V Z CD w O V Y :.> > UJ p m W J f Q m z WJ 0o_ =) U)U) W o _ 0o Cn UID co Ow j - co Z o To request marking of underground facilities �,Tw W U)0 :LN C� 0 0 V H CD w ~ 0 � n SHOWN. 4. ALL BUILDING FOUNDATIONS SHALL BE SHOT ON THE EXTERIOR CORNERS OF J Z THE FORMS, AND ONE FOUNDATION SETBACK AND ELEVATIONS CERTIFICATE Q a Q W SHALL ACCOMPANY THE CCP FOR EACH BUILDING. F o °- 0 io J U)U) U N Z a o o To request marking of underground facilities :LN 0 0 ,C/ Q 0 1 Z i W ° ° 2 KnowwhaYs below.° Call before you dig. 0 � 0 N 0 � ( m ] Call 811 or visit cal1811.com N m U for more information CO N 0 It is the contractor's responsibility to contact C)N=zO UNCC a minimum of 2 days prior to the start construction operations. D Dewberry I J3 Engineers, Inc. claims no ����n T�� � PRELIMINARY responsibility for the underground facilities 1^1W^lll depicted in this plan set. NOT rOR 1V BASIS OF BEARINGS: BEARINGS DHOWN HEREON ARE BASED UPON THE EAST LINE OF THE NORTHEAST 1/4 OF SECTION 20, TOWNSHIP 3 SOUTH, RANGE 69 WEST OF THE 6TH P.M. WHICH BEARS N003120 W BETWEEN THE MONUMENTS SHOWN HEREON, SAID BEARINGS ARE BASED ON NAD 83, COLORADO STATE PLANE COORDINATES, CENTRAL ZONE. m LL. SITE BENCHMARK: BENCH MARK -F 412" (PID KK57) m (D LOCATED AT THE INTERSECTION OF KIPLING STREET AND WEST 32ND AVENUE, d p 0 AT THE NORTHWEST CORNER OF CROWN HILL PARK, 82.0 FEET SOUTH OF THE £ N i; �, d CENTER OF THE AVENUE, 50.5 FT EAST OF THE CENTERLINE OF THE z O m m £ NORTHBOUND LANES OF THE STREET, 50.5 FEET NORTHWEST OF A FENCE, AND w O d m d m z 3.3 FEET SOUTHEAST OF THE SOUTHWEST LEG OF A PARK SIGN.CV)m � u W p Nj Vi C) d C) d ELEVATION = 5557.34 FEET (NAVD 1988) d 0 c U) City of Wheat Ridge Single Family - New PERMIT - 202001059 PERMIT NO: 202001059 ISSUED: 12/17/2020 JOB ADDRESS: 11723 W 45th Pl EXPIRES: 12/17/2021 JOB DESCRIPTION: Clear Creek Terrace - New single family townhome with 2 car garage - 11736 sq ft total (Bldg 4, C -unit) *** CONTACTS *** OWNER (720)473-7019 CLEAR CREEK TERRACE LLC GC (720)471-9428 B ILL LYONS JR 202068 CLEAR CREEK TERRACE, LLC SUB (720)315-9026 SCOTT WILLIAMS/LESLIE WILLIAMS 080076 ONE CORE ELECTRIC, INC. SUB (303) 888-5853 RICHARD KANSTEINER 019302 M&R PLUMBING, INC SUB (303)798-0500 JOE COLLIDA 170685 INDOOR AIR QUALITY INC *** PARCEL INFO *** ZONE CODE: UA / Unassigned USE: UA / Unassigned SUBDIVISION CODE: UA / Unassigned BLOCK/LOT#: / *** FEE SUMMARY *** ESTIMATED PROJECT VALUATION: 195,469.00 FEES Total Valuation 0.00 Plan Review Fee 120.00 Use Tax 41104.85 Permit Fee 11751.25 Engin. Review Fee 50.00 ** TOTAL ** 61026.10 *** COMMENTS *** *** CONDITIONS *** All roughs to be done at Framing Inspection. A printed copy of the permit and city stamped on-site plans must be available on-site for the first inspection. Approved per plans and red -line notes on plans. Must comply with 2012 IRC, 2017 NEC and all applicable City of Wheat Ridge Municipal Codes. Work is subject to field inspections. No C.O. may be issued until public improvements are complete as identified in the Subdivision Improvement Agreement. All landscaping shall be in conformance with Section 26-502 of the Zoning and Development Code. All landscaping shall be installed in accordance with the approved landscape plan prior to C.O., a landscape escrow agreement with financial guarantee in the amount of 1250 of the cost of the installation shall be required. 1* � � i City of Wheat Ridge Single Family - New PERMIT - 202001059 PERMIT NO: 202001059 ISSUED: 12/17/2020 JOB ADDRESS: 11723 W 45th Pl EXPIRES: 12/17/2021 JOB DESCRIPTION: Clear Creek Terrace - New single family townhome with 2 car garage - 11736 sq ft total (Bldg 4, C -unit) I, by my signature, do hereby attest that the work to be performed shall comply with all accompanying approved plans and specifications, applicable building codes, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with this�permrt. I further attest that I am leg ally authorized to include all entities named within this document as parties to the work to be performed and that all work to be performed is disclosed in this document and/or its' accompanying approved plans and specifications. Signature of OWNER or CONTRACTOR (Circle one) Date 1, This permit was issued based on the information provided in the permit application and accompanying plans and specifications and is subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures. 2. This permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and received prior to the date of expiration. An extension of no more than 180, days made be granted at the discretion of the Chief Building Official and may be subject to a fee equal to one-half of the original permit fee. 3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard requirements, fees and��procedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of the Chief Building Official and is not guaranteed. 4. No work of any manner shall be performed that shall results in a change of the natural flow of water without prior and specific approval. 5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all requ�ired inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services Division. 6. The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, anviolation of any provision of any applicable code or any ordinance or regulation of this jurisdiction. Approval of work is subject to field inspection. Signature of Chief Building Official Date REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. From: no-reolv(alci.wheatridae.m. us To: CommDev Farm is Subject: Online Form Submittal: New Single -Family TOWNHOME UNIT Date: Tuesday, April 28, 2020 8:38:56 AM New Single -Family TOWNHOME UNIT THIS APPLICATION DOES NOT CONSTITUTE A PERMIT. DO NOT BEGIN WORK UNTIL PERMIT HAS BEEN ISSUED. Has the Master Plan Yes been approved for this project? Name of Project CLEAR CREEK TERRACE PROPERTY INFORMATION Property Address - Only enter one unit on this application 11723 W 45TH PLACE Property Owner Name CLEAR CREEK TERRACE, LLC Property Owner Phone Number (enter WITH dashes, eg 303-123- 4567) Property Owner Email Address Attach City of Wheat Ridge Electronic Payment Form - "DO NOT ATTACH A PICTURE OF A CREDIT CARD" 7204719428 SSUNDBERG@CREEKSIDECOMMUN ITIES.COM CONTRACTOR INFORMATION Contractor or Architect CLEAR CREEK TERRACE, LLC Business Name Wheat Ridge Contractor's License Number (This is a 5 or 6 digit number for the City of Wheat Ridge) 202068 Contractor Phone 7204719428 Number (enter WITH dashes, eg 303-123- 4567) Contact Email Address SSUNDBERG@CREEKSIDECOMMUNITIES.COM for Questions/Comments Retype Contractor SSUNDBERG@CREEKSIDECOMMUNITIES.COM Email Address DESCRIPTION OF WORK Detailed Scope of NEW ATTACHED SINGLE FAMILY TOWNHOME WITH 2 CAR Work - Example: New GARAGE, MASTER PLAN C UNIT, BUILDING 4 single family townhome with 2 car garage - 1,525 sq ft total (Bldg 1, B -unit) Square Footage of New Construction Foundation Plans for Specific Building Elevations of Building Site Plan showing Unit Highlighted Floor plan of Unit Construction Plans scanned on 11'x17" or larger 1736 11723 ELEVATIONS.Ddf Field not completed. Project Value (contract 195469 value or cost of ALL J$195,469 Valuation is OK materials and labor) SIGNATURE OF UNDERSTANDING AND AGREEMENT I assume full Yes responsibility for compliance with applicable City of Wheat Ridge codes and ordinances for work under any permit issued based on this application. I understand that work Yes may not begin on this property until a permit has been issued and posted on the property. I certify that I have Yes been authorized by the legal owner of the property to submit this application and to perform the work described above. I attest that everything Yes stated in this application is true and correct and that falsifying information in this application is an act of fraud and may be punishable by fine, imprisonment, or both. Person Applying for STEPHEN SUNDBERG Permit Email not displaying correctly? View it in your browser. i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: 7�� 5 Job Address: -77 Permit Number: ❑ No one available for inspection: Time AM/PM Re -Inspection required: Yes No When corrections have been made, schedule for re -inspection online at: http://www. ci. wheatridge.co. us/inspection Date: Inspector: DO NOT REMOVE THIS NOTICE 11723 W 45th Place - 202000892 11-6-2020 KM CTL I THOMPSON October 28, 2020 Creekside Communities 6143 South Willow Drive Suite 300 Greenwood Village, Colorado 80111 Attention: Dan Garcia Subject: Geotechnical Consultation — Radon Reduction System Clear Creek Terrace Townhomes Project No. DN49,465-120-L2 CTL I Thompson was requested to provide opinions with respect to soil condi- tions at the Clear Creek Terrace Townhomes project. We understand you are construct- ing post -tensioned slab (PTS) concrete foundations that include a passive radon reduc- tion system. The system was designed by others but includes a 10 -mil polyurethane sheet at the base of the slab, but above the soil gas collection pipe. The "box beams" of the PTS foundation are provided with openings between each bay so that soil gas may migrate to the system. We believe the native granular soil (clean to silty sand -gravel - cobble) at Clear Creek Terrace Townhomes qualifies as a gas -permeable layer as de- scribed in Appendix F, 2018 IRC. The soil gas retarder is also discussed in IRC. The design of the system incorporates later addition of a fan to create a negative pressure environment should testing after construction show a need. These, combined with the inherent tightness of concrete cracks should they form in a post -tensioned slab should support good performance of a Radon Reduction System. If you have questions about this letter, please contact me. Sincerely, CTL 1 THOMPSON, INC. David A. Glater, P.E., C.P.G Sr. Principal Geological Engineer dglater(a7ctlthompson.com David Allen Glater Oct 28 2020 3:50 PM DAG/nn Via e-mail: ssundbergCaDcreeksidecommunities.com dgarcia creeksidecommunities.com 1971 West 12th Avenue I Denver, Colorado 80204 1 Telephone: 303-825-0777 Fax: 303-825-4252 CTL IT PROJECT NO. DN49,465-120-L2 i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: 3?3 /ryt Job Address: /1,Zz_a /tf Permit Number: 2cr?U 32-3 - 19A- kon - to ' 56,141 _ LLS /Yc-y nL/ 12&-, 41--f,27,3, ,1 No one available for inspection: Time 7 AM/PM Re -Inspection required: ',Yes No When corrections have been made, schedule for re -inspection online at: http:Owww. ci. wheatridge. co. usli'nspection Date: ' Inspector: DO NOT REMOVE THIS NOTICE It � 4 i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address:t_z)C-41D 4S C,, Permit Number: �� 2 2 ❑ No one available for in Re -Inspection required: Yes When corrections have been made, http✓/www.ci. wheatridge.co, uslinspi Date M for re -inspection online at: i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address: I Permit Number: I — __ 611 - M ❑ No one available for inspection: Tim M/PM Re -Inspection required: Ye When corrections have been made,�c a le for re -inspection online at: hUp✓/www.ci.wheatridge.co.usrnspe tion Date:/0 -(1 / r) ctor: CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address:// 7 Z 3� tt' Z/S--- Permit Number: Z�J .,5�z 8>�- ❑ No one available for inspection: Time w',`or—) AK(/PM Re -Inspection required: Yes t When corrections have been made, schedule for re -inspection online at: h ttpAwww. ci. wheatridge. co. usrinspection Date: 9 Z,.3 �oc77C7 Inspector: 5 DO NOT REMOVE THIS NOTICE !� 2 ❑ No one available for inspection: Time w',`or—) AK(/PM Re -Inspection required: Yes t When corrections have been made, schedule for re -inspection online at: h ttpAwww. ci. wheatridge. co. usrinspection Date: 9 Z,.3 �oc77C7 Inspector: 5 DO NOT REMOVE THIS NOTICE i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address: Permit Number: ❑ No one available for inspection: Time AM/PM Re -Inspection required: Yes No When corrections have been made, schedule for re -inspection online at: http://www. ci. wheatridge.co. uslinspection Date: Inspector: DO NOT REMOVE THIS NOTICE I* � 4 i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address: Permit Number: cs U 0 Z ❑ No one available for inspection: Time kUO AM/PM Re -Inspection required: Yes No When corrections have been made, schedule for re -inspection online at: http://www.ci. wheatridge.co.usrnspection Date: ??' ,;; . (_,4!6 Inspector:b DO NOT REMOVE THIS NOTICE i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: SUC-) C Job Address: .37 ko 4S Permit Number: C)Dcy-) U bci a T G ❑ No one available for inspection: Time AM/PM Re -Inspection required: When corrections have been made, schedule for re -inspection online at. httpY www,ci.wheatridge.co.uslnspection Date: 'S• zo Inspector: 1D DO NOT REMOVE THIS NOTICE