11764 W. 45th Place
1?1_�. e3P.Ower May 12, 2021 11764 W 45th Place Wheat Ridge, Colorado 80033 Re: Blower Door Test for 11764 W45 th Place To whom it may concern: E3 Power performed a blower door test on the above-mentioned building on May 12, 2021, at 10:00 AM. The volume of the building was calculated to be 17,000 cubic feet. The final blower door number was 850 CFM @-50 pascals achieving an ACH of 3. The building meets the air tightness requirement and is compliant with code. Weather conditions: 48 degrees, Wind 3 MPH, no precipitation, 40% humidity. Site Conditions: 1. Exterior windows and doors, fireplace and stove doors were closed, but not sealed, beyond the intended weather stripping or other infiltration control measures; 2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers were closed, but not sealed beyond intended infiltration control measures; 3. Interior doors were open; 4. Heating and cooliing systems were turned off; and 5. Supply and return registers were fully open. Sincerely, Jessica W. Kurela (e3 power) 303-292-1233 Building Analyst (BPI) Jessica Digitally signed by Jessica W. Kurela W. KurelaDate: 2021.05.12 14:45:19 -06'00' 303.292.1233 120.281.0916 e3towulel officf 1AX Wf6 Energy Efficiency Certificate Indicate if the following stave been installed (an efficiency shall not be listed) electric furnace gas -fire unvented room heater baseboard electric heater Designer/builder Clear Creek Terrace, LLC Code Edition 2018 IRC Date Window U- 0.3 0.4 ;:�51Cy{ir.�ai3e ::.a++.� U- N/A NIA .. •;iFsr, U- N/A ar,:i+r CeilinglRoof R- 49 Vaulted R- N/A Walls Frame R- 21 Mass R- NIA Basement R- N/A Crawl Space R- N/A Floors Over Unconditioned Space R- 30 Slab Edge R- 10 Ducts Attic R- 8 Other R- N/A Blower Door 3 ACH/50 Pa. Duct Testing 4 CfM/100 ftz Indicate if the following stave been installed (an efficiency shall not be listed) electric furnace gas -fire unvented room heater baseboard electric heater Designer/builder Clear Creek Terrace, LLC Code Edition 2018 IRC Date Window U- 0.3 0.4 Opaque Door U- N/A NIA Skylight U- N/A N/A Heating System Gas Forced Air 92% AFUE Cooling System Central AC 13 SEER Water Heater Gas (Storage Type) 0.67 Indicate if the following stave been installed (an efficiency shall not be listed) electric furnace gas -fire unvented room heater baseboard electric heater Designer/builder Clear Creek Terrace, LLC Code Edition 2018 IRC Date � 3,power May 12, 2021 11758 W 45th Place Wheat Ridge, Colorado 80033 Re: Blower Door Test for 11758 W45 1h Place To whom it may concern: E3 Power performed a blower door test on the above-mentioned building on May 12, 2021, at 10:00 AM. The volume of the building was calculated to be 17,000 cubic feet. The final blower door number was 845 CFM @-50 pascals achieving an ACH of 3. The building meets the air tightness requirement and is compliant with code. Weather conditions. 48 degrees, Wind 3 MPH, no precipitation, 40% humidity. Site Conditions: 1. Exterior windows and doors, fireplace and stove doors were closed, but not sealed, beyond the intended weather stripping or other infiltration control measures; 2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers were closed, but not sealed beyond intended infiltration control measures; 3. Interior doors were open; 4. Heating and cooking systems were turned off; and 5. Supply and return registers were fully open. Sincerely, Jessica W. Kurela (e3 power) 303-292-1233 Building Analyst (BPI) Jessica W. Kurela Digitally signed by Jessica W. Kurela Date: 2021.05.12 14:47:45 -06'00' 303.292.1233 120.281.0946 e3pavef.eet , 0EEICE fax WEB t {aeoha ii t:i ��•.,rt+ z,8A-�3fl , A ir;: 1 N 4o e <+C •{e:^'t1{93{ :-.!+1�94L '�A 1� �� t " lu:pl� Window U- 0.3 Opaque Door U- N/A Skylight U- N/A Heating System Energy Efficiency Certificate Cooling System Central AC Water Heater Gas (Storage Type) f tF:+ii Y.ttile` .rs i:te=.e _.. . •;�7aic :Kt�l. Ceiling/Roof R- 49 Vaulted R- N/A Walls Frame R- 21 Mass R- N/A Basement R- N/A Crawl Space R- NIA Floors Over Unconditioned Space R- 30 Slab Edge R- 10 Ducts Attic R- 8 Other R- N/A Blower Door 3 ACH/50 Pa. e <+C •{e:^'t1{93{ :-.!+1�94L '�A 1� �� t " lu:pl� Window U- 0.3 Opaque Door U- N/A Skylight U- N/A Heating System Gas Forced Air Cooling System Central AC Water Heater Gas (Storage Type) Duct Testing 4 Cfm/100 ft' 0.4 N/A N/A 92% AFUE 13 SEER 0.67 Indicate if the following have been installed (an efficiency shall not be listed) electric furnace gas -fire unvented room heater baseboard electric heater Designer/builder Clear Creek Terrace, LLC ..�� Code Edition 2018 IRC Date 6y/6 /kal t � i May 12, 2021 11768 W 45th Place Wheat Ridge, Colorado 80033 Re: Blower Door Test for 11768 W45 1h Place To whom it may concern: E3 Power performed a blower door test on the above-mentioned building on May 12, 2021, at 10:00 AM. The volume of the building was calculated to be 19,050 cubic feet. The final blower door number was 952 CFM @-50 pascals achieving an ACH of 3. The building meets the air tightness requirement and is compliant with code. Weather conditions: 48 degrees, Wind 3 MPH, no precipitation, 40% humidity. Site Conditions: 1. Exterior windows and doors, fireplace and stove doors were closed, but not sealed, beyond the intended weather stripping or other infiltration control measures; 2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers were closed, but not sealed beyond intended infiltration control measures; 3. Interior doors were open; 4. Heating and cooling systems were turned off; and 5. Supply and return registers were fully open. Sincerely, Jessica W. Kurela (e3 power) 303-292-1233 Building Analyst (BPI) Jessica W. Kurela Digitally signed by Jessica W. Kurela Date: 2021.05.12 14:42:55 -06'00' 303.292.1233 120.281.0946 e3poweimt' OFFICE fAA WEB (al. ! <i' � . r_' 4'�. Energy Efficiency Certificate iariyfdFig(e!a rin�:� a1:�a ! ,3no Ceiling/Roof R- 49 Vaulted R- N/A Walls Frame R- 21 Mass R- N/A Basement R- N/A Crawl Space R N/A Floors Over Unconditioned Space R- 30 Slab Edge R- 10 Ducts Attic R- 8 Other R- NIA iF sz Blower Door 3 ACW50 Pa. Duct Testing 4 Cfin/100 ft' Window U- 0.3 0.4 Opaque Door U- N/A N/A Skylight U- N/A N/A Heating System Gas Forced Air 92% AFUE Cooling System Central AC 13 SEER Water Heater Gas (Storage Type) 0.67 Indicate if the following have been installed (an efficiency shall not be listed) electric furnace gas -fire unvented room heater baseboard electric heater Designerlbuilder Clear Creek Terrace, LLC Code Edition 2018 IRC J 6) lZa l Home Energy Rating Certificate Rating Date: 2021-05-07 Final Report Registry ID: 147920071 Ek,trope ID: yLojVPAv Your Home's Estimated Energy Use: Use JOBtul Annual Cost This home meets or exceeds the criteria of the following: Heating 13.3 5146 ENERGY STAR v3 Cooling 1.0 536 ENERGY STAR V3.1 Hot V-Jater 7.4 $64 2012 International Energy Conservation Code Lights; Appliances 15.1 $472 Service Charges so K 6K CF,'050 ::,95 A&f Generation 'e.g. Solar) 11A -$396 jc-, -cakage V)Gutsioe: Total: 36.9 $321 R - t0 Home Feature Summary: -Orae uni: inn - H- a i ng Sys r, -,: Fu race Natural Ga> - 96.5 A PUE N me A'. Co�,cirione! - Ueclnc - 1 31 SEER Heate, - � arura3 Gas - -Oise K 6K CF,'050 ::,95 A&f Vent:'atlon: - 7 C�A� - 15 ;,Vatts jc-, -cakage V)Gutsioe: 47 C ti» ti -5 9 C f,;, ..bo.._ G, i d E ',Va i i s: R - t0 ceillno: Alzic. R-50 T" N.M. Z.. E—g, -oundation z: t"i ;, Home Feature Summary: -Orae uni: inn - H- a i ng Sys r, -,: Fu race Natural Ga> - 96.5 A PUE Pzir.-,a-. Coo,inq Systcr,: A'. Co�,cirione! - Ueclnc - 1 31 SEER Heate, - � arura3 Gas - -Oise K 6K CF,'050 ::,95 A&f Vent:'atlon: - 7 C�A� - 15 ;,Vatts jc-, -cakage V)Gutsioe: 47 C ti» ti -5 9 C f,;, ..bo.._ G, i d E ',Va i i s: R - t0 ceillno: Alzic. R-50 ,Vindo,v Type: U-Vahue: 0.3, SGC: 0.33 -oundation z: t"i ;, Rating Completed by: Energy Rater: Qu ' R I �- ES' -..ET ID: 7, 5 -, � 8 3 Rating Company: EnElg"- -0c. C Rating Provider:cr PO Box N BerV,ou,-, F, 7r. y 7 V 41, a C v%'rea,' Rcce. CO 80(033 To.,ve Hone 6,ce-s 7 Ver'f,ec -c Ekotrope Version 3.2.=.2667) Builder Narne: Thrive Home Builders Rating Company: EnergyLogic Permit Date/Number: Rater ID (RTIN): 7592832 Home Address: 7807 W 43rd Cir, Wheat Ridge, CO Rating Date: 2021-05-07 80033 Version: 3.0 Thermal Enclosure System A compete thermal enclosure system that includes comprehensive air sealing, quality -installed insulation and high -performing windows to deliver improved comfort and lower utility bills. Air Infiltration Test 650 CFM50 (2.95 ACH50) Primar.e Insulation Levels Ceiling: R-50 Floor: R-68 slabs to Wall: R-30 Stab: R-5 Primary 'Ahndov,' Efficiency U -Value: 0.3 SHGC: 0.33 Heating, Cooling, and Ventilation System A high -efficiency heating, cooling system, and ventilation system that is designed and installed for Optimal performance. Total Duct Leakage Duct Leakage to Outdoors 47 CFM @ 25Pa (Rough -in. with 47 CFM CcV 25Pa (3.94; 100 111) Air Handler) Primary Heating (System Type =Fuel Ty pe - Efficiency'i- Furnace - Natural Gas - 96.5 AFUE Pfirnar,,, CGoling iSysterin Type - Fuel Type - Efficiency', Air Conditioner - Electric - 13 SEER Water Management System A comprehensive water management system to protect roofs, walls, and foundations, Flashing, a drainage plane, and site grading to move water tram the roof to the ground and then awav from the home. Water-resistant materials on below-gradevealts and underneath slabs to reduce the potential for water entering into the home, Management of moisture levels in building materials during construction Energy Efficient Lighting and Appliances Energy efficient products to help reduce utility bills, while providing high-lquality performance. I Il Y. ENERGY STAR Qualified Lighting: 100% ENERGY STAR Qualified Appliances and Fans Refrigerators: 0 Dishwashers: 0 Ceiling Fans: 0 Exhaust Fans: l Primary Water 'Heater (System Type - Fuel Type - Efficiencyl, Water Heater - Natural Gas - 0.96 Energy Factor - ------ ------ --- 7Ms crv6c2r.,ics amai,r ip Of'�C'Crcy ,crstruction HERS* Index 'Oa! 01"S OVII contilblml tIj it EIEPI:a eomrvj the F.NFPCY STAR zo, r�j, , Hoir., Erierfy aiir, I SystpnI RS -.ras oaf Err, ind tirvOu qh inppanap, - tic,, ar, d venftaE rn Zero Energy Reference Exi5ring peffxilied by a itair'o e = HVme Ergy r. a "nif".rin SUIP.El"E"M Of rl�' e +q Home Home Homes Note that t ,l a lr� faur. tov wndo.,reMCIC A",homaSmay hie ianrloruly l L_ 0 M Pram a sct or hemcs fcK leprescritauve jnsV_,Ctiom and titsnng, :n si�ch case,, the E—gy E—gy �eatwes tout in eats, horn. ftn the �et are rterided tiu?T'�ePL UI e'% -,•-ed the values presented On hs wit f—to Tne actuar valucs for your hcm.- may dff-ir but offbir �-quivljebt or bcftr pedorntincc Ih:5crrtiia-,zi)�waspr!-qc.,,Lt; ngEkottopl_,, ENERGY STAR V3 Home Report Property Organization 7807 W 43rd Cir EnergyLogic Wheat Ridge, CO 80033 Quinn Stedman Model: P1 I Community: Westridge Builder Thrive Home Builders 7807 W 43rd Cir Thrive Reports Mandatory Requirements Inspection Status 2021-05-07 Rater ID (RTIN): 7592832 RESNET Registered (Confirmed) ✓ Duct leakage at post construction better than or equal to ENERGY STAR v313.1 requirements. ✓ Envelope insulation levels meet or exceed ENERGY STAR v3/3.1 requirements. ✓ Slab on Grade Insulation must be > R-5, and at IECC 2009 Depth for Climate Zones 4 and above. ✓ Envelope insulation achieves RESNET Grade I installation, or Grade II with insulated sheathing. ✓ Windows meet the 2009 IECC Requirements - Table 402.1.1. ✓ Duct insulation meets the EPA minimum requirements of R-6. ✓ Mechanical ventilation system is installed in the home. ✓ ENERGY STAR Checklists fully verified and complete. HERS Index Target Reference Home HERS 72 SAF (Size Adjustment Factor) 1.00 SAF Adjusted HERS Target 72 As Designed Home HERS 28 As Designed Horne HERS w/o PV 51 Normalized, Modified End -Use Loads (M Btu f year) ENERGY STAR As Designed Heating 12.1 8.8 Cooling 2.3 2.8 Water Heating 8.4 2.0 Lights and Appliances 17.1 15.1 Total 39.8 28.7 This home MEETS or EXCEEDS the energy efficiency requirements for designation as an EPA ENERGY STAR Qualified Home under Version 3,0 Pollution Prevented Energy Cost Savings $/yr Type of Emissions Reduction Heating 36 Carbon Dioxide (CO2) - tons/yr 4.3 Cooling Water Heating 68 Lights & Appliances 67 Generation Savings 396 Total 562 The energy savings and pollution prevented are calculated by comparing the Rated Home to the ENERGY STAR Version 3.0 Reference Home as defined in the ENERGY STAR Qualified Homes HERS index Target Procedure for National Program Requirements, Version 3.0 promulgated by the Environmental Protection Agency (EPA). In accordance with the ANSI/RESNET/ICC 301-2014 Standard, building inputs affecting setpoints infiltration rates, window shading and the existence of mechanical systems may have been changed prior to calculating loads Ekotrope RATER - Version 3.2.4.2067 All results are based on data entered by Ekotrope users. Ekotrope disclaims all liability for the information shown on this report. I IECC 2012 Performance Compliance Property 7807 W 43rd Cir Wheat Ridge, CO 80033 Model: P1 I Community: Westridge 7807 W 43rd Cir Thrive Reports Organization EnergyLogic Quinn Stedman Builder Thrive Home Builders Design Heating Cooling Water Heating SubTotal - Used to determine compliance Lights &Appliances Onsite generation Total Inspection Status 2021-05-07 Rater ID (RTIN): 7592832 RESNET Registered (Confirmed) Annual Energy Cost IECC 2012 Performance $214 $42 $139 $395 $415 $o $809 Requirements As Designed $164 $53 $139 $356 $414 $0 $770 405.3 Performance-based compliance passes by 9,8% 402.4.1.2 Air 'Leakage Testing Air sealing is 2.95 ACH at 50 Pa. it must not exceed 3.00 ACH at 50 Pa. 402.5 Area -weighted average fenestration SHGC 402.5 Area -weighted average fenestration U -Factor 403-2.2 Duct Testino R4041 Lighting Equipment Efficiency R403-5.1 fAechanical Ventilation Efficacy Mandatory Checklist Mandatory code requirements that are not checked by Ekotrope must be met, R405.2 Duct Insulation Design exceeds requirements for IECC 2012 Performance compliance by 9.8%. As a 3rd party extension of the code jurisdiction utilizing :hese reports, I certify that this energy code compliance document has been created in accordance voth the requirements of Chapter 4 of the adopted International Energy Conservation Code based on Climate Zone 5 If rating is Projected. I certify that the building design described herein is consistent with the building plans. specifications. and other calculations submitted with the permit application. If rating is Confirmed. I certifier that the address referenced above has been inspected/tested and that the mandatory provisions of the JECChave been installed to meet or exceed the intent of the IECC or will be verified as such by another part=. Name: Organization: Quinn Stedman EnergyLogic Signature: Digitally signed: 5,7121 at 4:46 KI Ekotrope RATER - Version 3.2.4.2667 IECC 2012 Performance compliance results calculated using Ekotrope RATER's energy and code compliance algorithm, Ekotrope RATER is a RESNET Accredited HERS Rating Tool. All results are based on data entered by Ekotrope users Ekotrope disclaims all liability for the information shown on this report, 7807 W 43rd Cir Wheat Ridge, CO 80033 Builder: Thrive Home Builders Model: P1 1 Communitv: Westridae Ceiling Attic. R-50 Above Grade Walls R-30 Foundation Walls NIA Framed Floor R-68 Slab R-0.0 Perimeter, R-5.0 Under Infiltration 650 CFM50 (2.95 ACH50) Window U -Value: 0.3. SHGC: 0.33 Building Features Duct Supply R-0.0, Return R-0.0 Duct Leakage to Outside 47 CFM @ 25Pa (3.941 100 ft2) Total Duct Leakage 47 CFM @ 25Pa (Rough -In, with Air Handler) Heating Furnace • Natural Gas • 96.5AFUE Cooling Air Conditioner • Electric • 13 SEER Water Heating Water Heater • Natural Gas - 0.96 Energy Factor As a 3rC party extension of the code jurisdiction utilizing these reportsi certify that this energy code compliance Cocument has been created in accordance with the requireirents of Chapter 4 of the adopted international Energy Conservation Code based on Climate Zone 5. if rating is Projected. 1 certify that the building design described herein is consistent with the building plans. specifications_and ether calculations submitted with the perrrEt application.if rating is Confirmed. 1 certify that the address referenced above has been inspected>'tested and that the mandatory provisions or the €ECC have been installed to meet or exceed the inter; o` the ECC or wit€ be veri5ed as such by another K- . �� Name: Quinn Stedman Signature: t-tf/ Organization: EnergyLogic Digitally signed: 517!21 at 4:46 PM Ekotrope RATER - Version 3.2.4.2667 2012 IECC compliance results calculated using Ekotrape RATER's Ererar and code compliance algorithm Ekotrope RATER is a RESNET. Accredited HERS Rating Tool, All riisu!-i ars based an data entered by Ekotrope users Ekotrape disolaims ati 4iabirmi fen the information shown on this repod IECC 2012 Label 7807 W43rd Cir Model: P1 I Ekotrope RATER - Version: 3.2.4.2667 HERS(§) Index Score: 28 Building Envelope Specs Ceiling: R-50 Above Grade Walls: R-30 Foundation Walls: N/A Exposed Floor: R-68 Slab: R-5 Infiltration: 650 CFM50 (2.95 ACH50) Duct Insulation: Supply: RO, Return: RO Duct Lkg to Outdoors: 47 CFM @ 25Pa (194 100 ft2) Window & Door Specs U -Value: 0.3, SHGC: 0.33 Door: R-5 Mechanical Equipment Specs Heating: Furnace • Natural Gas • 96.5 AFUE Cooling: Air Conditioner - Electric - 13 SEER Hot Water: Water Heater • Natural Gas • 0.96 Energy Factor Average Mechanical Ventilation: 37 CFM Builder or Design Professional Signature: Air Leakage Report Property Organization Inspection Status 7887VV43vdCir EnergyLogio 2021'05-07 Wheat Ridge, CO8O033 Quinn Stedman Rater |D(RT|N):7582832 Model: P1| RESNETRaginV*nad Community:VVeothdga Builder (Confirmed) Thrive Home Builders 78D7VV43/dCir Thrive Reports General |DfO[Dl8tiOn Conditioned Floor Area [ft2] 1,193 Infiltration Volume [ft'] 13,234.27 Number of Bedrooms 2 Air Leakage Measured Infiltration .650 CFM50 (2.95 ACH50) ACH50 (Calculated) 2.95 ELA [sq. in.] (Calculated) ELA per 100 s.f. Shell Area (Calculated) 35.75 0.976 CFM50 (Calculated) 47.0 CFM50 / s.f. Shell Area (Calculated) 10.177 Duct Leakage Mechanical Ventilation Rate [CFM] System 1 Leakage to Outdoors 47 CFM @ 25Pa (3.94 / 100 ft2) Total Leakage Test Type Rough -In, with Air Handier Total L'eakage [CFM @ 25 Paj 47.0 Total Leakage [CFM25 / 100 s.f.] 3.9 Total Leakage [CFM25 / CFA] 0.039 Mechanical Ventilation Rate [CFM] 37 CFM Hours per day 24.0 Fan Power 15 Watts Recovery Efficiency % 0.0 Runs at least once every 3 hrs? true Average Rate [CFMj 37.0 CFM 2010 ASHRAE 62.2 Req. Cont. Ventilation 34.4 2013 ASHRAE 62.2 Req. Cont. Ventilation 58.3 Ekotrope RATER ' Version 3�4,20O7 IECC 2012 Emissions Comparison Property Organization Inspection Status 7807 W 43rd Cir EnergyLogic 2021-05-07 Wheat Ridge, CO 80033 Quinn Stedman Rater ID (RTIN): 7592832 Model: P1 I RESNET Registered Community: Westridge Builder (Confirmed) Thrive Home Builders 7807 W 43rd Cir Thrive Reports Annual Carbon Dioxide (CO.,) [tons/yr] 2012 IECC Rated Home Savings % Saved Heating 1.6 1.2 0.4 24.4% Cooling 0.4 0.5 -0.1 -25.9% Water Heating 0.9 0.9 0.0 0.1% Lights & Appliances 3.7 3.7 0.0 0.1% Photovoltaics -0.0 -0.0 0.0 0% TOTAL 6.6 6.3 0.3 4.5% Annual Sulfur Dioxide (SO2) [lbs/yr] 2012 IECC Rated Home Savings % Saved Heating 1.1 0.7 0.4 35.4% Cooling 0.6 0.8 -0.2 -25.9% Water Heating 0.0 0.0 0.0 0.1% Lights & Appliances 5.8 5.8 0.0 0.1% Photovoltaics -0.0 -0.0 0.0 0% TOTAL 7.6 7.3 0.2 2.9% Annual Nitrogen Oxide (NOx) [lbs/yr] 2012 IECC Rated Home Savings % Saved Heating 2.5 2.0 0.5 21.3% Cooling 0.4 0.4 -0.1 -25.9% Water Heating 1.9 1.9 0.0 0.1% Lights & Appliances 3.6 3.6 0.0 0.1% Photovoltaics -0,0 -0.0 0.0 0% TOTAL 8.4 7.9 0.5 5.5% Ekotrope RATER - Version 3.2.4.2667 All results are based on data entered by Ekotrope users. Ekotrope disclaims all liability for the information shown on this report, I -ECC 2012 Fuel Summary Comparison Property Organization Inspection Status 7807 W 43rd Cir EnergyLogic 2021-05-07 Wheat Ridge, CO 80033 Quinn Stedman Rater ID (RTIN): 7592832 Model: P1 I RESNET Registered Community: Westridge Builder (Confirmed) Thrive Home Builders 7807 W 43rd Cir Thrive Reports Annual Energy Cost [$/yr] 2012 IECC Rated Home Savings % Saved Natural Gas Electric Annual End -Use Cost [$/yr] $304 $505 2012 IECC $280 $491 Rated Home S24 $14 Savings 7.9% 2.8% % Saved Heating S214 $164 $50 23.4% Cooling 542 $53 _$11 -26.2% Water Heating $139 $139 so 0% Lights & Appliances $415 $414 S1 0.2% Onsite Generation _$0 _$0 so 0% Service Charges $0 $0 so 0% Total $809 $770 S39 4.8% Annual End -Use Consumption 2012 IECC Rated Home Savings % Saved Heating [Natural Gas Therms] 166.4 138.2 283 17% Heating [Electric kWh] 655.8 421.6 234.2 357% Cooling [Electric kWh] 390.9 492.2 -101.3 -25.9% Hot Water [Natural Gas Therms] 160.1 160.0 0.1 0.1% Lights & Appliances [Natural Gas Therms] 26.6 26.6 0.0 0% Lights & Appliances [Electric kWh] 3,650.2 3,645.9 4.3 0.1% Total [Natural Gas Therms] 353.2 324.8 28.4 8% Total [Electric kWh] 4,696.8 41559.7 137.1 2,9% Total Onsite Generation kWh 0.0 0.0 0.0 0% Peak Electric Consumption 2012 IECC Rated Home Savings % Saved Peak Winter kW 0.58 0.52 0.07 11.6% Peak Summer kW 0.81 0.84 -0.03 -4.3% Utility Rates Electricity A Colorado E 2021 02 Natural Gas A Colorado NG 2021 02 Ekotrop(-'.• RATER - Veis ion 3,2.4.2667 All results a based on data entered by Ekotrope users. Ekotrope disclaims all liability for the information shovin on this report RESNET HOME ENERGY RATING Standard Disclosure For home(s) located at: 7807 W 43rd Cir, Wheat Ridge, CO Check the applicable disclosure(s).- 1. The Rater or the Rater's employer is receiving a fee for providing the rating on this home. i 2. In addition to the rating, the Rater or the Rater's employer has also provided the following consulting services for this home: A. Mechanical system design B. Moisture control or indoor air quality consulting C. Performance testing and/or commissioning other than required for the rating itself D. Training for sales or construction personnel E. Other(specify) 3. The Rater or the Rater's employer is: A. The seller of this home or their agent B. The mortgagor for some portion of the financed payments on this home C. An employee, contractor, or consultant of the electric and/or natural gas utility serving this home A. The Rater or Rater's employer is a supplier or installer of products, which may include: Products Installed in this home by OR is in the business of HVAC systems Rater Employer Rater Employer Thermal insulation systems Rater Employer Rater Employer Air sealing of envelope or duct systems Rater Employer Rater Employer Energy efficient appliances Rater Employer Rater Employer Construction (builder, developer, construction contractor, etc) Rater Employer Rater Employer Other (specify).- Rater Employer Rater Employer 5. This home has been verified under the provisions of Chapter 6, Section 603 "Technical Requirements for Sampling" of the Mortgage Industry National Home Energy Rating Standard as set forth by the Residential Energy Services Network (RESNET). Rater Certification #: 7592832 Name: Quinn Stedman Signature: Organization: EnergyLogic Digitally signed: 5/7/21 at 4:46 PM I attest that the above information is true and correct to the best of my knowledge. As a Rater or Rating Provider I abide by the rating quality control provisions of the Mortgage Industry NationalHome Energy Rating Standard as set forth by the Residential Energy Services Network(RESNET). The national rating quality control provisions of the rating standard are contained in Chapter One 102.1 .4.6 of the standard and are posted at nttps:', siIrl cprds.res' � I LIS The Home Energy Rating Standard Disclosure for this home is available from the rating provider. RESNET Form 03001-2 - Amended March 20, 2017 rz u This home built at 7807 W 43rd Cir Wheat Ridge, CO 80033 was verified by EnergyLogic to meet Indoor airPLUS construction specifications as established by the U.S. Environmental Protection Agency. Indoor airPLUS qualified homes are designed to contribute to improved indoor air quality. 2021-05-07 .- da Indoor airPLUS Features - Moisture and .. Control • Radon Resistant Construction • Pest Barriers • Effective Heating, Ventilating, and Air -Conditioning Systems • Safe Combustion • Healthier Building Materials Not all features are required in all cases. To learn more eboirt indoor air quality features in your horse, ask your builder to review the Indoor aIrPLUS verification checklist with you, or visit o+,vvw. epa.aovl indoorar irp I us. 11, QIj/ �CI E D NA& Thrive Home Builders EnergyLogic 2021-05-07 s . YOUR HOME WAS DESIGNED, ENGINEERED, AN#, CONSTRUCTED IN CONFORMANCE TO US DEPARTMENT OF ENERGY (DOE) GUIDELINES FOR EXTRAORDINARY LEVELS OF EXCELLENC.I. AND QUALITY, ZERO FNERGY READY HOME Address: 7807 W 43rd Cir, Wheat Ridge, CO 80033 Builder: Thrive Home Builders Inspector: EnergyLogic Date: 2021-05-07 THIS HOME MEETS OR EXCEEDS THE MINIMUM CRITERIA FOR THE FOLLOI,,VING: ENERGY STAR V3 ENERGY STAR V3.1 2012 INTERN. ENERGY CONSERVATION CODE Existing Homes Reference Home Zero Energy Home SAM RASHKIN, CHIEF ARCHITECT BUILDING TECHNOLOGIES U.S, DEPARTMENT OF ENERGY Eke.trope RATER - Version 01.2,4.26,--7 , E— More Energy 150 140 1 116 100 90 80 70 W V) 2tai 0 -1ft This Home 10 0 Less Energy Component Loads Property Organization 7807 W 43rd Cir EnergyLogic Wheat Ridge, CO 80033 Quinn Stedman Model: P1 I Community: Westridge Builder Thrive Home Builders 7807 W 43rd Cir Thrive Reports 7 6 5 4 3 2 0 -1 -2 -3 -4 -5 Above -Grade Infiltration & Slabs & Walls Ventilation Floors Inspection Status 2021-05-07 Rater ID (RTIN): 7592832 RESNET Registered (Confirmed) Heating & Cooling Loads Roofs Ducts Windows & Foundation Internal Doors Walls Gains Heating Cooling Ekotrope RATER - Version 3.2,41667 All results are based on data entered by Ekotrope, users. Ekotrope disclaims all liability for the information shown on this report LEED for Homes Source Energy Budget Property Organization Inspection Status 7807 W 43rd Cir EnergyLogic 2021-05-07 Wheat Ridge, CO 80033 Quinn Stedman Rater ID (RTIN): 7592832 Model: P1 I RESNET Registered Community: Westridge Builder (Confirmed) Thrive Home Builders 7807 W 43rd Cir Thrive Reports This home will consume 72% less source energy than the LEED Source Energy Budget limit. Source Energy Consumption (MBtu / year)* -Source Energy is determined by multiplying site energy electric use by 3 2 and fosstl fuel use by 105 Note that if there are major energy consumers not included in this energy rating (e a pool pumps), they must be included separately Home Feature Summary: Home Type: Model: Community: Conditioned Floor Area: Number of Bedrooms: Primary Heating System: Primary Cooling System: Primary Water Heating. - House Tightness: Ventilation: Duct Leakage to Outside Above Grade Walls: Ceiling: Window Type: Foundation Walls. - Townhouse, inside unit Pi I Westridge 1,193 ft2 2 Furnace • Natural Gas - 96.5 AFUE Air Conditioner • Electric • 13 SEER Water Heater • Natural Gas • 0.96 Energy Factor 650 CFM50 (2.95 ACH50) 37 CFM • 15 Watts 47 CFM @ 25Pa (194 / 100 ft2) R-30 Attic, R-50 U -Value: 0.3, SHGC: 0.33 N/A Ekotrc)pe RATER - `11/etsion _3,2.4,2667 All results are based on data entered by Ekotrope users Ekotrops disclaims all liability for the information shown on this report LEED Reference As Designed Heating 48.6 16.7 Cooling 5.0 3.2 Hot Water 16,6 7,8 Lights and Appliances 54.8 42.6 Onsite Generation 0.0 -35.1 Total 124.9 35.2 -Source Energy is determined by multiplying site energy electric use by 3 2 and fosstl fuel use by 105 Note that if there are major energy consumers not included in this energy rating (e a pool pumps), they must be included separately Home Feature Summary: Home Type: Model: Community: Conditioned Floor Area: Number of Bedrooms: Primary Heating System: Primary Cooling System: Primary Water Heating. - House Tightness: Ventilation: Duct Leakage to Outside Above Grade Walls: Ceiling: Window Type: Foundation Walls. - Townhouse, inside unit Pi I Westridge 1,193 ft2 2 Furnace • Natural Gas - 96.5 AFUE Air Conditioner • Electric • 13 SEER Water Heater • Natural Gas • 0.96 Energy Factor 650 CFM50 (2.95 ACH50) 37 CFM • 15 Watts 47 CFM @ 25Pa (194 / 100 ft2) R-30 Attic, R-50 U -Value: 0.3, SHGC: 0.33 N/A Ekotrc)pe RATER - `11/etsion _3,2.4,2667 All results are based on data entered by Ekotrope users Ekotrops disclaims all liability for the information shown on this report 2005 EPAct Energy Efficient Home Tax Credit Property Organization Inspection Status 7807 W 43rd Cir EnergyLogic 2021-05-07 Wheat Ridge, CO 80033 Quinn Stedman Rater ID (RTIN): 7592832 Model: P1 I RESNET Registered Community: Westridge Builder (Confirmed) Thrive Home Builders 7807 W 43rd Cir Thrive Reports RESNET Confirmed Rating Normalized Modified End -Use Loads (MBtu / year) Category 2006 IECC 50% As Designed Target Heating 9.2 7.7 Cooling 1.5 2.8 Total 10.7 10.5 Building Features Envelope Loads (MBtu / year) Category 2006 IECC As Designed 90% Target Heating 16.5 9.7 Cooling 2.7 3.8 Total 19.2 13.5 Ceiling U: 0.02 Heating System: Furnace • Natural Gas • 96.5 Wall U: 0.044 AFUE Framed Floor U: 0.016 Cooling System: Air Conditioner - Electric - 13 Slab R: R-5 SEER Glazing Properties: U -Value: 0.3, SHGC: 0.33 Duct Leakage to Outside: 47 CFM @ 25Pa (3.94 t 100 ft.) This home meets the requirements for the residential energy efficiency tax credit under section 1332, Credit for Construction of New Energy Efficient Homes, of the Energy Policy Act of 2005. Builder should verify that the 45L Tax Credit is available for the year in which this home was built. The undersigned certifier verifies that: (1) The dwelling unit has a projected level of annual heating and cooling energy consumption that is at least 50 percent below the annual level of heating and cooling energy consumption of a reference dwelling unit in the same climate zone; (2) Building envelope component improvements alone account for a level of annual heating and cooling energy consumption that is at least 10 percent below the annual level of heating and cooling energy consumption of a reference dwelling unit in the same climate zone; and (3) Heating and cooling energy consumption have been calculated in the manner prescribed in section 2.03 of this notice. (4) Field inspections of the dwelling unit (or of other dwelling units under the ENERGY STARe for Homes Sampling Protocol Guidelines) performed by the eligible certifier during and after the completion of construction have confirmed that all features of the home affecting such heating and cooling energy consumption comply with the design specifications provided to the eligible certifier. "Under penalties of perjury, I declare that I have examined this certification, including accompanying documents, and to the best of my knowledge and belief, the facts presented in support of this certification are true, correct, and complete." Name: Quinn Stedman Organization: EnergyLogic Signature: Digitally signed: 5/7121 at 4:46 PM Ekotrope RATER - Version 3.2.4.2567 All results are based on data entered by Ekotrope users. Ekotrope disclaims all liability for the information shown on this report. A i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: 2�V S Job Address: 1176N w L� so-` Pi Permit Number: 702-00 © 277 ❑ No one available for inspection, Time `�-' 4 5- CAM/PM;- \ Re -Inspection required: Yes N When corrections are complete, schedule re -inspection online. Date: -1- Z4Z i Inspector: 4M DO NOT REMOVE THIS NOTICE i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Dw S Job Address: Permit Number: 7 a 2000 _M Al 0-1 ❑ No one available for inspection: Time du_ 10/13M Re -Inspection required: ` Yes No When corrections are complete, schedule re -inspection online. Date: Inspector: DO NOT REMOVE THIS NOTICE i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address: Permit Number: J No one available for inspection: Time AM/PM Re -Inspection required: Yes No "When corrections are complete, schedule re -inspection online. Date: Inspector: DO NOT REMOVE THIS NOTICE Inspection Type: Job Address: Permit Number: CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE =t No one available for inspection: Time AM/PM Re -Inspection required: Yes No When corrections are complete, schedule re -inspection online. Date: Inspector: DO NOT REMOVE THIS NOTICE i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type:,_Z-= Job Address: Ir Permit Number: ❑ No one available for inspection: Time PM Re -Inspection required: Yes No When corrections are complete, schedule -inspection online. Inspecto y�c T o w o r ECONOMIC ENERGY EEEICIENCY January 28, 2021 11764 W 45th Place Wheat Ridge CO 80033 Re: Duct leakage test for 11764 W 45th Place To whom it may concern: E3 Power performed a Duct leakage test on the above mentioned building on January 28, 2021 at 10:30 AM. The total duct leakage measurement was 44 CFM @-25 pascals. The duct system meets the air tightness requirement of 4 CFM per 100 square feet of area served and is compliant with code. Please let me know if I can be of further assistance to you. Sincerely, Jessica W. Kurela (e3 power) 303-292-1233 Building Analyst (BPI) Jessic Digitally signed by a W. Jessica W. Kurela Date: Kurela 2021.01.28 15.14:32 -07'00' 303,292.1233 120.201.0946 B3powor.BBt , OrrIOE [AM WEB i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address: Permit Number: U No one available for inspection: Time AM/PM Re -Inspection required: Yes No When corrections are complete, schedule re -inspection online. Date: Inspector: DO NOT REMOVE THIS NOTICE Inspection Type: Job Address: Permit Number: CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE No one available for inspection: Time // '30 &O/PM Re -Inspection required: Yes No When corrections are complete, schedule re -inspection online. Date: - Inspector DO NOT REMOVE THIS NOTICE A i CITY OF WHEAT RIDGE Building Inspection Division (303) 235-2855 Office INSPECTION NOTICE Inspection Type: Job Address: 11-7 i y W t°t' Permit Number: -7 n E600%77 J No one available for inspection: Time AM/PM Re -Inspection required: Yes No When corrections are complete, schedule re -inspection online. Date: Inspector:_ DO NOT REMOVE THIS NOTICE Z Cilvof � '' W heat I ic��c f.tIAt.tilliti[15 FOR OFFICE USE ONLY Approved by: Inspector Date City of Wheat Ridge Municipal Building 7500 W. 29`''Ave. Wheat Ridge, CO 80033-8001 P: 303.235.2846 F: 303.235.2857 FOUNDATION SETBACK AND ELEVATION CERTIFICATION For Commercial and Multi -Family Developments This form must be fully completed by a Professional Land Surveyor licensed in the State of Colorado. This form asst be accompanied by a Construction. Control Plan following the procedure found on the reverse side of this form. DATE: 12/22/2020 11764 W 45th P1 202000891 PERMIT# 202000891 ADDRESS: 11768. 11764. 11758.11752.11746. 11740 West 45th Place LOT 13-18 , BLOCK_L____,_Clear Creek Terrace SUBDIVISION SURVEYOR: I hereby certify that the elevations and distances shown on the attached sheets and as stated below for the recently formed or constructed structural foundation for the above property have been measured by me or directly under my supervision. The MINIMUM SETBACK DISTANCES from the property lines have been determined to be: FRONT: 5.5' REAR: 5.0' SIDE: 0' SIDE: 0' The foundation corner ELEVATIONS (NAVD88) have been determined to be: FRONT: 5413.10' REAR: 5413.14' SIDE: 5413.10' SIDE: 5413.10' All measurements have been determined on the following location: (Check only one): X Top of proposed foundation wall prior to placement of concrete Top of foundation wall subsequent to placement of concrete The setback and elevation measurements are included on the attached Construction Control Plan. Signed _ l mal Surveyor DPD 0 1_ /CFy Print Thomas M. Girard PLS 38151 8151 o 1/6 Date 01/06/2021 NAC L NO wNviv i.wbeatridhe.eo.us Rev 1112018 W W Z W J N � W a W N TOW DESIGN ELEV=5411.50- TOW DESIGN ELEV-5410.75 GRATE ELEV = 5411.20 BOW DESIGN ELEV=5407.50 BOW DESIGN ELE"-"^^ " INV IN (W) = 5408.29 Tow AB ELEV = 5411.43 i TOW AB ELEV = 5412.04 INV IN (S) - 5408.9 BOW AB ELEV = 5407.48 BOW AB ELEV = 5410.08 INV OUT GRATE = AB 5407.8' ELEV = 5411 91' OW DESIGN ELEV=5411.67 INV IN (W) AB = 54f1R R9 -'OW DESIGN ELF""` • ELEV = 5410.69 13 INV IN (S) AB = 5408.39 TOW AB ELEV = 5417 OF BOW AB ELEV = 5410.34 0 o d. GRATE AB ELFV = 541 n 67 Uj W _ 5408.05 e� e� INV OUT AB = 5408.33 oV o0 DESIGN = G' LU TOW utsicn tLjeV=5411.50 J D SIG13 = in'F d_ ao o= a A DIST 10' BOW DESIGN ELEV=5407.50 �CD W F o�Lq�o Tow AB ELEv = 5411.43 JH mWo Mo A3� 0 BOW AB ELEV = 5407.48 D BW ESIGIN EL BW B E EV 5411.56' v B ELEV 5411.53' W 541 DESIGN ELEV=5412.40 CUJ AB ELEV = CDLO z U GN DESIGN SETBACK Z DIST = 12' AB DISTANCE = 0' LU BW DESIGN ELE"-"'^^'- BW AB ELEV = 5412.89' FW AB ELEV = 5412.80' E • ELEV = 5410.69 13 N = 5408.34 F CA INV OUT = 5408." 0 o d. GRATE AB ELFV = 541 n 67 Uj W INV IN AB = con❑ p INV OUT AB = 5408.33 oV o0 DESIGN = G' LU AB DIST = 5.5' J D SIG13 = in'F d_ ao o= a A DIST 10' 7 7 D 7 A D \ o TOW DESIGN ELEV=5411.50- BOW DESIGN ELEV=5407.50 TOW AB ELEV = 5411.43 B LEV = 5407.56 - 541 J14 BW DESIGN ELE"-R"'n ee BW AB ELEV = 5412.98' FW AB ELEV = 5412.91' BW DESIGN ELEV=5412.86 BW AB ELEV -5412.86' FW AB ELEV = 5412.83' DESIGN ELE AA_G-F\i TOW DESIGN ELEV=5412.00- BOW DESIGN ELEV=5407.50 TOW AB ELEV = 5411.96 BOW AB ELEV = 5407.52 INV ELEV = 54m Sn INV AB ELEV = 5407.28 FL DESIGN ELEV=5411.01- rL AB ELEV 5410.35 rL DESIGN E V=5411.54 o rL AB ELEV 5411.53 °1 1 TOW DESIGN ELEV=5411.50 BOW DESIGN ELEV=5407.50 Tow AB ELEV = 5411.44 Bow AB ELEV = 5407.55_ ° rL AB ELEV = 5412.03 tGRA ELEV = 5411.60 TOW DESIGN ELEV=5411.50 = 5408.67 BOW DESIGN ELEV75407.58 T = 5408.6' " TOW AB ELEV= 5411.48 AB EI r" - Sd11 67 BOW AB EL V = AB = rAnR 77 _ 5407.50 T AB 5408.77 0 D p DSIGN= ° DIST BLDG. W \ D SIGN = in, 3 0� W J \ A DIST = 10' DESIGN FFE=5413.15 - a 0 5413.12' a 5'\ 16 \ BW DESIGN ELF" -"'^^' ° BW AB ELEV = 5413.03' \ �' FW AB ELEV = ^ 5413.01' I 9 z � o 0 \ rL DESIGN ELEV=5411.49 w \ o FL AB ELEV = 5411.77 o \ ° in c~i \ 17 Ir rn BW DESIGN ELE"-M"'Z'^ \ BW AB ELEV = 5413 03' p W \ FW AB ELEV = 5413.01' °a. D SIGN - in, F ` A DIJT - 10' a^ 0 GRATE ELEV - 5411.30 a INV OUT = 5408.91 GRATE AB ELEV\= 5411.33 INV OUT AB = 54Ub.91 18 DESIGN = mo% 7 TOW DESIGN ELEV--5411.50 AB DIST = BOW DESIGN ELEV=5407.50 5.5' DESIGN ELEV=5411.62 Tow AB ELEV = 5411.44 AB ELEV= 5411.64 D Bow AB ELE V = 5407.60 � \ I DESIGN ELEV-5412.09 DESIGN ELEV=5411.38 AB DISTANCE - 0' AB ELEV = AB ELEV = 5411.38 DIST = 12' DESIGN SETBAG.. 0' • p DES GN =5413.15 -J D AB LEV = h 5412 DEIGN AB ELE = 5411.35 D D rL PESIGN ELEV=S�tn_st D WA i171 n� 7D �I/ D FL AB ELEV 5410.80 o00 7 I BWDDESIENy LEv=sat9 to / AB 5412.08' FW AB ELEV = 5412.07' D IL DESIGN ELEV=5411.14 FL AB ELEV = 5411.09 BW DESIGN ELEV=5411.64 BW AB ELEV = FW AB ELEV = rL DESIGN ELEV=5411.05 rL DESIGN ELEV= 411.21 ITL AB ELEV = 5411.05 Li AB ELEV = 5 10.75 E DESIGN ELEV=5410.70 ITL AB ELEV = 5410.73 rL DESIGN EELEV=s4+noa FL AB ELEV, -5411 .10 -� D IGN ELEv=Sato 7-,; ITL B ELEV 5410.77 ---- i--\ -__ ELEV=54,.�-- ELEV - 5410.82 / MATCH LINE (SEE SHEET 6) TOW DESIGN ELEV=5411.50 BOW DESIGN ELEV=5407.50 Tow AB ELEV = 5411.46 BOW AB ELEV = 5407.54 TOW DESIGN ELEV-5412.00 BOW DESIGN ELEV=5407.50 TOW AB ELEV = 5412.04 BOW AB ELEV = 5407.48 TOW DESIGN ELEV=5412.00 BOW DESIGN ELEV=5407.50 TOW AB ELEV = 5412.00 BOW AB ELEV = 5407.49 TOW DESIGN ELEV=5411.50 BOW DESIGN ELEV=5407.50 TOW AB ELEV = 5411.44 Bow AB ELEV = 5407.58 TOW DESIGN ELEV=5412.00 BOW DESIGN ELEV=5407.50 TOW AB ELEV =5411.99 BOW AB ELEV =5407.43 10 0 10 10 20 ( IN FEET ) 1 inch = 10 M M Z O 00 Q W J CUJ W CDLO z U Z C LU J °3 rny E Ujd N aim a- F cc 0 o ACD Uj W C 0 3 p oV o0 W LU 3 0.)� J N d_ ao o= a Q �CD W F o�Lq�o JH mWo Mo A3� 0 o__EEE o ao (D cn 0 W Q O Y V m of Q mz WJ Qom W o _ 0o Cn co co_ W Z O Ui v ii J = O O O NOTES: Z O 00 Q W J CUJ W d z VJ Z rrj H CD LU J OAC WZ Ujd 2. ALL SHOTS ON SIDEWALKS SHALL BE COMPRISED OF TWO (2) SHOTS TAKEN F i V N Uj W Z p 0 W V F J N CROSS -SLOPE) AT APPROXIMATELY 100 -FOOT INTERVALS. Q � F JH p V N Q O J V SHOWN. Y V m of Q mz WJ Qom W o _ 0o Cn co co_ W Z O Ui v ii J = O O O NOTES: � D O 00 W CUJ 1. ALL ADA RAMPS SHALL BE SHOT AT THE TOP AND BOTTOM TO ENSURE J W v z GRADES MEET ADA REQUIREMENTS. rrj H CD LU I- ofc 2. ALL SHOTS ON SIDEWALKS SHALL BE COMPRISED OF TWO (2) SHOTS TAKEN 0 DIRECTLY ACROSS FROM ONE ANOTHER TO ASSURE ADA COMPLIANCE (G2% N CROSS -SLOPE) AT APPROXIMATELY 100 -FOOT INTERVALS. 3. ALL CURB AND GUTTER SHOTS SHALL BE IN THE FLOWLINE AT THE LOCATIONS Q _ J z SHOWN. F Q Q W ~ ~ o 4. ALL BUILDING FOUNDATIONS SHALL BE SHOT ON THE EXTERIOR CORNERS OF m m m .Q 0 THE FORMS, AND ONE FOUNDATION SETBACK AND ELEVATIONS CERTIFICATE � U) D � SHALL ACCOMPANY THE CCP FOR EACH BUILDING. Q o F o Z To request marking of underground facilities LL N U ,C/ Q U 0 1 ® z i W °' °' 1 2 Knowwhat's below. Call before you dig. 0 � 0 N C ( m ] Call 811 or visit cal1811.com N ? o U for more information CO 1-- 0 It is the contractor's responsibility to contact � N �o z UNCC a minimum of 2 days prior to the start construction operations. Dewberry J3 Engineers, Inc. claims no D ����n T�� PRELIMINARY � responsibility for the underground facilities 1^1W^lll depicted in this plan set. 1�\�I NOT rOR BASIS OF BEARINGS: BEARINGS DHOWN HEREON ARE BASED UPON THE EAST LINE OF THE NORTHEAST 1/4 OF SECTION 20, TOWNSHIP 3 SOUTH, RANGE 69 WEST OF THE 6TH P.M. WHICH BEARS N003120 W BETWEEN THE MONUMENTS SHOWN HEREON, SAID BEARINGS ARE BASED ON NAD 83, COLORADO STATE PLANE COORDINATES, CENTRAL ZONE. m LL SITE BENCHMARK: BENCH MARK "F 412" (PID KK57) m L LOCATED AT THE INTERSECTION OF KIPLING STREET AND WEST 32ND AVENUE, d p 0 AT THE NORTHWEST CORNER OF CROWN HILL PARK, 82.0 FEET SOUTH OF THE E N i; �, d CENTER OF THE AVENUE, 50.5 FT EAST OF THE CENTERLINE OF THE z O m m £ NORTHBOUND LANES OF THE STREET, 50.5 FEET NORTHWEST OF A FENCE, AND w O d m d 00 z 3.3 FEET SOUTHEAST OF THE SOUTHWEST LEG OF A PARK SIGN.m � u W F N Vi C) d C) d ELEVATION = 5557.34 FEET (NAVD 1988) Ii 0 j c a .. City of Wheat Ridge Single Family - New PERMIT - 202000777 PERMIT NO: 202000777 ISSUED: 10/08/2020 JOB ADDRESS: 11764 W 45th P1 EXPIRES: 10/08/2021 JOB DESCRIPTION: Clear Creek Terrace - New single family townhome with 2 car garage - 1,523 sq ft tectal (Bldg 3, B -unit) I, by my signature, do hereby attest that the work to be performed shall comply with all accompanying approved plans and specifications, applicable building codes, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with this permit. I further attest that I am legally authorized to include all entities named within this document as parties to the work to be performed and that all work to be performed is disclosed in this document and/or its' accompanying approved plans and specifications. Signature of OWNER or CONTRACTOR (Circle one) Date 1. This permit was issued based on the information provided in the permit application and accompanying plans and specifications and is subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures. 2. This permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and received prior to the date of expiration. An extension of no more than 180 days made be granted at the discretion of the Chief Building Official and may be subject to a fee equal to one-half of the originalpermit fee. 3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard requirements, fees and procedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of the Chief Building Official and is not guaranteed. 4. No work of any manner shall be performed that shall results in a change, of the natural flow of water without prior and specific approval. 5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all required inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services Division. 6. The issuance nti of a p it shall not be construed to be a permit for, or an approval of, an violation of any provision of any applicable cc&Z ani . rdina r re lation of this jurisdiction. Approval of work is subject to field inspection. Signature of Chief Building Official Date REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY. From: no-reolv(alci.wheatridae.m. us To: CommDev Farm is Subject: Online Form Submittal: New Single -Family TOWNHOME UNIT Date: Monday, April 27, 2020 3:41:10 PM New Single -Family TOWNHOME UNIT THIS APPLICATION DOES NOT CONSTITUTE A PERMIT. DO NOT BEGIN WORK UNTIL PERMIT HAS BEEN ISSUED. Has the Master Plan Yes been approved for this project? Name of Project CLEAR CREEK TERRACE PROPERTY INFORMATION Property Address - Only enter one unit on this application 11764 W 45TH PLACE Property Owner Name CLEAR CREEK TERRACE, LLC Property Owner Phone Number (enter WITH dashes, eg 303-123- 4567) Property Owner Email Address Attach City of Wheat Ridge Electronic Payment Form - "DO NOT ATTACH A PICTURE OF A CREDIT CARD" 7204719428 SSUNDBERG@CREEKSIDECOMMUN ITIES.COM CONTRACTOR INFORMATION Contractor or Architect CLEAR CREEK TERRACE, LLC Business Name Wheat Ridge Contractor's License Number (This is a 5 or 6 digit number for the City of Wheat Ridge) 202068 Contractor Phone 7204719428 Number (enter WITH dashes, eg 303-123- 4567) Contact Email Address SSUNDBERG@CREEKSIDECOMMUNITIES.COM for Questions/Comments Retype Contractor SSUNDBERG@CREEKSIDECOMMUNITIES.COM Email Address DESCRIPTION OF WORK Detailed Scope of NEW ATTACHED SINGLE FAMILY TOWNHOME WITH 2 CAR Work - Example: New GARAGE, MASTER PLAN B UNIT, BUILDING 3 single family townhome with 2 car garage - 1,525 sq ft total (Bldg 1, B -unit) Square Footage of New Construction Foundation Plans for Specific Building Elevations of Building Site Plan showing Unit Highlighted Floor plan of Unit Construction Plans scanned on 11'x17" or larger 1523 11764 ELEVATIONS.Ddf Field not completed. Project Value (contract 168566 value or cost of ALL $169,992 Valuation - Slight Increase materials and labor) SIGNATURE OF UNDERSTANDING AND AGREEMENT I assume full Yes responsibility for compliance with applicable City of Wheat Ridge codes and ordinances for work under any permit issued based on this application. I understand that work Yes may not begin on this property until a permit has been issued and posted on the property. I certify that I have Yes been authorized by the legal owner of the property to submit this application and to perform the work described above. I attest that everything Yes stated in this application is true and correct and that falsifying information in this application is an act of fraud and may be punishable by fine, imprisonment, or both. Person Applying for STEPHEN SUNDBERG Permit Email not displaying correctly? View it in your browser. Permit approved by Engineering , 04/28/2020 David F Brossman, Development Review Engineer A Grading Certification accompanied by an ILC or updated CCP shall be required prior to issuance of the last C.O. for the building. A . City of Wheat Ridge Single Family - New PERMIT - 202000777 PERMIT NO: 202000777 ISSUED: 10/08/2020 JOB ADDRESS: 11764 W 45th Pl EXPIRES: 10/08/2021 JOB DESCRIPTION: Clear Creek Terrace - New single family t.ownhome with 2 car garage - 1,523 sq ft total (Bldg 3, B -unit) *** CONTACTS *** OWNER (720)471-9428 CLEAR CREEK TERRACE, LLC GC (720)471-9428 BILL LYONS JR 202068 CLEAR CREEK TERRACE, LLC SUB (720)315-9026 SCOTT WILLIAMS/LESLIE WILLIAMS 080076 ONE CORE ELECTRIC, INC. SUB (303)888-5853 RICHARD KANSTEINER 019302 M&R PLUMBING, INC 6SUB (303)798-0500 JOE COLLIDA 170685 INDOOR AIR QUALITY INC *** PARCEL INFO *** ZONE CODE: UA / Unassigned USE: UA / Unassigned SUBDIVISION CODE: UA / Unassigned BLOCK/LOT#: / *** FEE SUMMARY *** ESTIMATED PROJECT VALUATION: 169,992.00 FEES Total Valuation 0.00 Plan Review Fee 120.00 Use Tax 3,569.83 Permit Fee 1,583.55 Engin. Review Fee 50.00 ** TOTAL ** 5,323.38 *** COMMENTS *** ** CONDITIONS *** All roughs to be done at Framing Inspection. A printed copy of the permit and city stamped on-site plans must be available on-site for the first inspection. Approved per plans and red -line notes on plans. Must comply with 2012 IRC, 2017 NEC and all applicable City of Wheat Ridge Municipal Codes. Work is subject to field inspections. No C.O. may be issued until public improvements are complete as identified in the Subdivision Improvement Agreement. All landscaping shall be in conformance with Section 26-502 of the Zoning and Development Code. All landscaping shall be installed in accordance with the approved landscape plan prior to C.O., a landscape escrow agreement with financial guarantee in the amount of 1250 of the cost of the installation shall be .required.