Residential Foundation Repair PERMIT - 202001956
PERMIT NO: 202001956 ISSUED: 09/30/2020
JOB ADDRESS: 3874 Parfet St EXPIRES: 09/30/2021
JOB DESCRIPTION: Stabilizing the northeast corner of the house with two (2) resistance piers
and the crawlspace access portal with one (1) helical pier.
*** CONTACTS ***
OWNER (303)668-4029
MARSHALL SUSAN
C
SUB (303)805-8751
RODNEY MARTIN
060125 COMPLETE
BASEMENT SYSTEMS
*** PARCEL INFO ***
ZONE CODE:
UA / Unassigned
USE:
UA / Unassigned
SUBDIVISION CODE:
2403 / APPLEWOOD
VILLAGES, PROSPECT V BLOCK/LOT#:
0 /
*** FEE SUMMARY ***
ESTIMATED PROJECT VALUATION:
41050.00
FEES
Total Valuation
0.00
Plan Review Fee
81.28
Use Tax
85.05
Permit Fee
125.05
** TOTAL **
291.38
*** COMMENTS ***
*** CONDITIONS ***
A printed copy of the permit and city stamped on-site plans must be available on-site for
the first inspection.
Approved per plans and red -line notes on plans. Must comply with 2018 IRC, 2020 NEC and all
applicable City of Wheat Ridge Municipal Codes. Work is subject to field inspections.
Inspection by Wheat Ridge Building Inspector required prior to backfill. Observation letter
from Engineer to be provided to Wheat Ridge Building Inspector at Final Inspection.
1* � � i City of Wheat Ridge
Residential Foundation Repair PERMIT - 202001956
PERMIT NO: 202001956 ISSUED: 09/30/2020
JOB ADDRESS: 3874 Parfet St EXPIRES: 09/30/2021
JOB DESCRIPTION: Stabilizing the northeast corner of the house with two (2) resistance piers
and the crawlspace access portal with one (1) helical pier.
I, by my signature, do hereby attest that the work to be performed shall comply with all accompanying approved plans and specifications,
applicable building codes, and all applicable municipal codes, policies and procedures, and that I am the legal owner or have been authorized
by the legal owner of the property and am authorized to obtain this permit and perform the work described and approved in conjunction with
this permit. I further attest that I am leg ally authorized to include alI entities named within this document as parties to the work to be
performed and that all work to be performed is disclosed in this document and/or its' accompanying approved plans and specifications.
Signature of OWNER or CONTRACTOR (Circle one) Date
1, This permit was issued based on the information provided in the permit application and accompanying plans and specifications and is
subject to the compliance with those documents, and all applicable statutes, ordinances, regulations, policies and procedures.
2. This.permit shall expire 365 days after the date of issuance regardless of activity. Requests for extension must be made in writing and
received prior to the date of expiration. An extension of no more than 180, days made be granted at the discretion of the Chief Building
Official and may be subject to a fee equal to one-half of the original permit fee.
3. If this permit expires, a new permit may be required to be obtained. Issuance of a new permit shall be subject to the standard
requirements, fees and��procedures for approval of any new permit. Re -issuance or extension of expired permits is at the sole discretion of
the Chief Building Official and is not guaranteed.
4. No work of any manner shall be performed that shall results in a change of the natural flow of water without prior and specific approval.
5. The permit holder shall notify the Building and Inspection Services Division in accordance with established policy of all requ�ired
inspections and shall not proceed or conceal work without written approval of such work from the Building and Inspection Services
Division.
6. The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, anviolation of any provision of any
applicable code or any ordinance or regulation of this jurisdiction. Approval of work is subject to field inspection.
Signature of Chief Building Official Date
REQUESTS MUST BE MADE BY 11:59PM ANY BUSINESS DAY FOR INSPECTION THE FOLLOWING BUSINESS DAY.
♦ A i CITY OF WHEAT RIDGE
Building Inspection Division
(303) 235-2855 Office
INSPECTION NOTICE
Inspection Type:
Job Address:
Permit Number: z4y 2. 0
❑ No one available for inspection jime 0'� f� / 40M
Re -Inspection required: Yes /Ao
When corrections have -been made, schedule for re -inspection online at:
httpY www.ci,wheatridge.co:uslinspection
Date: 49 — � 3" ;Ve'5 Inspector:`
DO NOT REMOVE THIS NOTICE
no change to valuation
From: no-reolv(alci.wheatridae.m. us
To: CommDev Perm is
Subject: Online Form Submittal: Foundation Repair
Date: Tuesday, September 29, 2020 8:48:44 AM
Foundation Repair
This application is exclusively for FOUNDATION REPAIRS.
YOU MUST ATTACH A VALID ELECTRONIC PAYMENT ORM IN ORDER FOR
THE PERMIT TO BE PROCESSED.
Your Permit will be emailed to the email address provided below once it is
processed.
THIS APPLICATION DOES NOT CONSTITUTE A PERMIT. DO NOT BEGIN
WORK UNTIL PERMIT HAS BEEN ISSUED.
Is this application for a Yes
Foundation Repair?
PROPERTY INFORMATION
Property Address 3874 Parfet Street
Property Owner Name Marshall, Susan
Property Owner Phone
Number (enter WITH
dashes, eg 303-123-
4567)
Property Owner Email
Address
Attach City of Wheat
Ridge Electronic
Payment Form - "DO
NOT ATTACH A
PICTURE OF A
CREDIT CARD"
(303) 668-4029
scm6331@gmail.com
Wheat Ridae Payment Form.Ddf
CONTRACTOR INFORMATION
Contractor Business
Name
Wheat Ridge
Contractor's License
Number (This is a 5 or
6 digit number for the
Complete Basement Systems
60125
City of Wheat Ridge)
Contractor Phone
Number (enter WITH
dashes, eg 303-123-
4567)
Contractor Email
Address
720-507-2711
cbs.permits@completebasementsystems.net
Retype Contractor cbs.permits@completebasementsystems.net
Email Address
DESCRIPTION OF WORK
Location of Work Stabilizing the northeast corner of the house with two (2)
resistance piers and the crawlspace access portal with one (1)
helical pier
How is repair being Piers
done? Piers, strips, etc.
# of Piers or Strips
Upload engineer letter
or pages on 8 1/2" x
11" only
Repair Plan Set on
11'x17" only - if
applicable
2 -push piers, 1 -helical pier
Project Value (contract 4050 ok bf 9/30/2020
value or cost of ALL
materials and labor)
SIGNATURE OF UNDERSTANDING AND AGREEMENT
I assume full Yes
responsibility for
compliance with
applicable City of
Wheat Ridge codes
and ordinances for
work under any permit
issued based on this
application.
I understand that work Yes
may not begin on this
property until a permit
has been issued and
posted on the property.
I certify that I have Yes
been authorized by the
legal owner of the
property to submit this
application and to
perform the work
described above.
Person Applying for Greg Knapp
Permit
I attest that everything Yes
stated in this
application is true and
correct and that
falsifying information in
this application is an
act of fraud and may
be punishable by fine,
imprisonment, or both.
Email not displaying correctly? View it in your browser.
ALL WORK SHALL COMPLY WITH
2018 IRC, 2018 IECC, 2020 NEC,
COLORADO PLUMBING CODE
GENERAL NOTES
city inspection is required prior to back fill.
engineer observation letter is required to
complete building final inspection
(1.0) All dimensions and slopes shall be verified by the
contractor prior to construction.
(1.1) The contractor shall ensure all OSHA requirements are satisfied during
excavation, and installation. The Lepetim Group shall not be
responsible for workshe safety.
(1.2) Contractor shall be responsible for obtaining all required permits.
(1.3) For purposes of this foundation repair, north is considered to be
as shown on the drawing.
(1.4) Contact this office to observe final installation, including installation logs.
(1.5) Contractor shall be responsible for locating all utilities before beginning work.
(1.6) Contractor shall verify soft soils, including loose coheshionless
soils, soft organic soils, or soft clays are not present.
(1.7) Contact this office if water table is found to be above the bottom of
foundation before installing the repairs.
(1.8) Concrete shall be min fcy = 4,000 psi.
(1.9) Structural steel shall be min fy =50 ksi
(1.10) Rebar shall be 60 ksi per ASTM A615
(2.0) Resistance piers shall be UES 531 certified 2 7/8" dia (or equiv).
Helical piers shall be in compliance with 2007 ICC AC358 2 7/8" dia (or equiv)
(2.1) Minimum required allowable axial load capacity = 24 k per pier, FSu = 2.0,
min pier depth = 25' or to capacity/refusal. Contractor shall ensure each pier achieves
minimum required capacity.
(2.2) Design assumed normalftypical foundation reiforcement per building code requirements.
(3.0) Design was performed in accordance with the 2018 IRC
as modified by the City of Wheat Ridge, Colorado
Ground and Roof Snow Load = 30 psf , E
Vult City of
Basic Wind Design
ed,Ca egory 135 mph Exp C r � 1 nc� t,� . gC
Seismic Design Category = B COMMUNnY UEVELOI'MENT
Frost Depth = 36" APPROVED
K Reviewed for Code Compliance
ON SITE PLANS BRANDON F 9/30/2020
MUST BE ON SITE FOR INSPECTION Plans Examiner Date
wIWM of xnne: rnearasne a/°Gr/wxw aYC'awl°rPbns •VwjlmNre
oMmmpamewm rM1"N rwt °e o pnmNfw. wan "pwaal a/, wry mra°on W
ALL PfeieCty are a.ry or me p.owsaas aJ me eunuH,y roc.wof ad asY warmwea a°rmro
$ubieet to Field Inspections w"""""90°a"'ourmm,-mwwaerwmnc«i rnepovwa,s arm.suNgxE
mcu wamnanbnawnorMa GTynwtl n°thwN0.
FOUNDATION REPAIR
FOR HOME AT
3874 PARFET ST
WHEAT RIDGE, COLORADO
PI AN VIFW
-E
ESISTANCE
ER DETAIL
? PLACES)
RTH
,•�
Digitally signed by
Gregory N. Lepetsos
By accepting and using these plans, the owner contractor agrees that the
shall assume sole andcompleteresponsibility for job site conditions duringtheTHE
course of construction, including safety of all persons and property, that this
requirement shall apply continuously and not be limited to normal working
LEPETSOS GROUP, INC
no�wumam morin
28)87 +
y�
? 1 /POS
Date: 2020.09.27
-06'00' 10:29:10
hours, and that the owner/contractor shall defend, indemnify, and hold the
engineer harmless from any and all liability, real or alleged, in conjunction with
the performance of work on this project, excepting for liability arising from the
sole negligence of the engineer. The client agrees to limit the engineers
erg
° °L
libility to the total fee collected for services rendered on this project.
FOUNDATION REPAIR
PREPARED FOR
COMPLETE BASEMENT SYSTEMS
rt-- ! a° x
° srDirt erc
FOUNDATION REPAIR
FOR HOME AT
DRIVEN PILE ASSY SHALL BE 3874 PARFET ST
PER GRIP TITE SPECIFICATION
AND MANUFACTURED BY WHEAT RIDGE, COLORADO
ICC/UES CERTIFIED FACILITY.
FS2888V PIER
BRACKET BRACKET MUST SUPPORT THE BOTTOM OF THE FOOTING
AND SHALL NOT RELY ON POST -INSTALLED ANCHORS FOR
GRAVITY SUPPORT. SECURE BRACKET TO FOUNDATION IN
ACCORDANCE WITH MANUFACTURERS INSTRUCTIONS. USE
TWO (2) J" DIA CONCRETE ANCHOR BOLTS WITH MIN 4"
EMBEDMENT.
CHIP OUT POCKET IN EXISTING 3Y2" DIA 30" LONG DIA GUIDE SLEEVE
FOOTING FLUSH WITH FOUNDATION
WALL. POCKET WIDTH SHALL 27%" DIA PILE SECTION. CONNECT
APPROXIMATELY MATCH BRACKET SECTIONS WITH 23g" DIA X 12"
WIDTH INTERNAL SLIP CONNECTION
CONTRACTOR SHALL ENSURE MINIMUM ALLOWABLE PIER
CAPACITY OF 24K IS ACHIEVED.
MIN DEPTH = 25 FEET OR TO DEPTH REQUIRED TO ACHIEVE
CAPACITY/REFUSAL
ON REDUCING COLLAR
DETAIL 1: FSI 288 RESISTANCE PIER / `*yof
p0 RFF/ w'
I\\I
ii
Digitally signed b
g y g y
a Gregory N. Lepetsos
By accepting and using these plans, the owner/contractor agrees that they
shall assume sole and complete responsibility for job site conditions during the
course of construction, including safety of all persons and property, that this
requirement shall apply continuously and not be limited to normal working
THE LEPETSOS GROUP, INC
ii wnN umnoNmmm
•. 28787 ,
L" M1os
Date: 2020.09.27
10:29:24-06'00'
hours, and that the owner/contractor shall defend, indemnify, and hold the
engineer harmless from any and all liability, real or alleged, in conjunction with
the performance of work on this project, excepting for liability arising from the
sole negligence of the engineer. The client agrees to limit the engineer's
libility to the total fee collected for services rendered on this project.
w x MMM
u M w mi Me
Wheat Ridge
FOUNDATION REPAIR
PREPARED FOR
COMPLETE BASEMENT SYSTEMS
®aF ms
FOUNDATION REPAIR
FOR HOME AT
3874 PARFET ST
CHIP OUT POCKET IN EXISTING WHEAT RIDGE, COLORADO
FOOTING FLUSH WITH FOUNDATION
WALL. POCKET WIDTH SHALL BRACKET MUST SUPPORT THE BOTTOM OF THE
APPROXIMATELY MATCH BRACKET FOOTING AND SHALL NOT RELY ON POST—INSTALLED
WIDTH ANCHORS FOR GRAVITY SUPPORT. SECURE BRACKET
TO FOUNDATION IN ACCORDANCE WITH
MANUFACTURERS INSTRUCTIONS. USE TWO (2) 8" DIA
CONCRETE ANCHOR BOLTS WITH MIN 4 z" EMBEDMENT.
IF COMPETENT FOUNDATION EDGE DOES
NOT EXIST, OR IF BOTTOM SURFACE IS
ROUGH ADD 8X8X % STEEL CHANNEL.
PILE BRACKETS WITH ADD WATER PROOF NON—SHRINK GROUT
_/SEAT,INSTALL PER BETWEEN ANGLE AND BOTTOM OF
MANUFACTURER FOUNDATION AS REQUIRED TO FILL GAPS.
INSTRUCTIONS
27/8" DIA SHAFT SECTION
TORQUE TO ACHIEVE MIN 24K
ALLOWABLE AXIAL LOAD
CAPACITY. MIN 25 FT DEPTH
OR TO CAPACITY/ REFUSAL. 8" HELIX LEAD SECTION OR AS
REQUIRED TO ACHIEVE REQUIRED
CAPACITY
Zo
DETAIL 2: HELICAL PIER
�sD ft'
•
Digitally signed by
Gregory N. Lepetsos
By accepting and using these plans, the owner/contractor agrees that they
shall assume sole and complete responsibility for job site conditions during the
of construction, including safety of all persons and property, that this
requirement shall apply continuously and not be limited to normal working
THE LEPETSOS GROUP, INC
n sa�N um m min
287P
Ethe
LpA OS
Date- 2020.09.27
hours, and that the owner/contractor shall defend, indemnify, and hold the
engineer harmless from any and all liability, real or alleged, in conjunction with
performance of work on this project, excepting for liability arising from the
rt �
u
t
q
10.29.41 -06'00'
sole negligence of the engineer. The client agrees to limit the engineers
libility to the total fee collected for services rendered on this project.
Wheat Ridge
FOUNDATION REPAIR
PREPARED FOR
COMPLETE BASEMENT SYSTEMS
rt- a me x
n rt Dirt
ElTHE LEPETSOS GROUP, INC.
September 27, 2020 Job #: LG 20 - 2076
Complete Basement Systems
11795 E 4511 Ave
Denver, CO. 80239
Attn: Lucas Farland
Subject: Visual Structural Foundation Evaluation for 3874 Parfet St. Wheat
Ridge, CO.
Dear Mr. Farland,
Per your request, I visited the home at the above referenced address
on September 19, 2020. The purposes of my visit were to observe the
foundation damage reported and provide repair recommendations as
required.
Please note: My investigation was based on observation of accessible,
visible items. Issues/concerns concealed by finishes, if any exist, were
not able to be observed, and were therefore not evaluated as part of
this investigation. Issues and repairs, if required, regarding other parts
of the home, were not part of the scope of this investigation, and are
specifically excluded from this report.
Observations
For purposes of this report, the front of the duplex house faced west.
This was the north unit of the two -unit duplex. The northeast corner of
the house and the crawlspace access portal were settled.
ON SITE PLANS
MUST BE ON SITE FOR INSPECTION
ALL Pro fr,1t are
99blact to Field Inanuy ions
city a
Wheat Ridge
3874 Parfet St., Wheat Ridge, Colorado
Recommendations
1) 1 recommend stabilizing the northeast corner of the house with two
(2) resistance piers and the crawlspace access portal with one (1)
helical pier per attached engineering drawings. The components
used in this repair shall be certified by the manufacturer for
corrosion resistance per the manufacturer's technical report.
2) If applicable, racked doors and windows should be reset, and
cosmetic repairs, can be made three (3) months after the structural
repairs are complete.
3) It is very important to maintain proper drainage away from the
house. I do not recommend irrigating within 5 -feet of the
foundation. Maintain a minimum 10 % slope away from the
structure, and direct surface water to an adequately sloped swale.
Grass, plants, trees, and shrubs with high watering requirements
should not be located within five feet of the foundation. All gutter
downspouts should have functioning downspout extensions, which
extend at least five feet away from the foundation and discharge in
a manner which allows effluent to flow safely away from the home
or discharge directly to an underground pipe system with an
appropriate daylight location. Perimeter drains, and sump pumps if
they exist, should function properly.
I observed the structural condition of the visible portions of the
foundation described above. Other unknown concerns may also exist.
The Lepetsos Group, Inc. makes no representations regarding the
suitability of other areas, including, but not limited to mechanical,
electrical, plumbing, previous foundation repairs, and other systems.
The homeowner should understand additional unforeseen and
unforeseeable issues related to soil heaving and or settlement, and
exposure to unwanted water may cause additional foundation
movement in the future. My evaluation and recommendations are
based on my education, experience and observations made on the
date of my visit. The Lepetsos Group, Inc. makes no representations
regarding the ability of the property to meet current or past building
code requirements. Please note it was not possible to observe every
structural detail. Contact this office if additional information becomes
available which could affect our observations and recommendations.
3874 Parfet St., Wheat Ridge, Colorado
Please contact me if you have any questions regarding these findings
or if I can be of service in any way.
Regards,
Gregory N. Lepetsos, P.E., M.S.C.E.
President, The Lepetsos Group, Inc.
Digital,*
Gregory N. by ;
L c
Lepetsos Date7Q2009
�
10:32:11 r46ro