Loading...
HomeMy WebLinkAbout4060 Clear Creek Dr 201902581 B5 Insulation Certificate 05.20.214060 Clear Creek Dr 201902581 n/-�� /Ik� (-- (,/-o �) Assembly Serial # Test Date/ Time Tester Certification # ( _} 112,IAW� Assembly Test Results ® Pass 0 *Fall Under Suspension - Process Immediately Denver Water Backflow Assembly Test & Maintenance Report (please print with BLOCK LETTERING) Testing Company: Submit by e-mail (prefened) to CrossConnecfionControl@denverwater.org, type'Backflow Test Reports" in the subject line OR submit by Fax to (303) 794-8325. * FAILED test results must be reported to Denver Water within 24 hours of failure at (303) 628-5969. Facility Name: C© !.-9Vk Meter #: Facility Address: n City: U a Contact Person: Phone: c3 "YQ Make: Model. Type: RPt ❑ DC 13 PVB IJAIr Gap Tvoe of Use Protectionlentation '— Size: lnstatled:Domestic (>Containment Inlet Outlet l _Date New ❑ Existing ❑ Fire ❑ Glycol ❑ Containment by Isolation AZ- Horizontal L,_NEL_ a Previous Assembly#: {y� ❑ Irrigation ❑ Isolation ❑ Vertical Up ❑ Location: 'Cl Recycled ❑ Vertical Down ❑ Approved: YX N ❑ Line 0 Initial Test Results Repairs Re -Test Results Tightness 9 Differential Tightness Differential PSL Check Valve #1 ❑ Leak �y ❑ Leak (RP, DC, PVB) �KTight V02 ❑ Tight Check Valve #2 ❑ Leak ❑ Leak (RP, DC) Tight ❑Tight m Relief Valve - (RP) Buffer (RP) Air Inlet (PVB) Shutoff Valve #1: Wight ❑ Leaking ❑ Replaced Shutoff Valve #2: ht ❑ Leaking ❑ Replaced Backpressure: ❑ Yes Test Procedure: ❑ ABPA: ASSE: Comments: s e Alarm Company/Fire Department l WD w Person Notified: Contacted By: z' Tum Off Date/Time: Tum On Date/Time: � x Test Kit Make: G`.Y_<SP.�/.fr�"_ Model: j�� - J r Serial #: Last Calibration Date: Tester cedes this asse ly has bean tested with the above listed proved re and verifies the isolation valves were retumed to pre-test orientation. " 1 Testing Company. L� FTester Name: Phone: Signatur Certificate Expiration Date:=)� 1 Testing Company: Submit by e-mail (prefened) to CrossConnecfionControl@denverwater.org, type'Backflow Test Reports" in the subject line OR submit by Fax to (303) 794-8325. * FAILED test results must be reported to Denver Water within 24 hours of failure at (303) 628-5969. 4060 clear crk dr 201902581 buildina ONE consultina. Ilc July 12, 2021 Mr. Tom Harris Evergreen 1873 South Bellaire Street, Suite 1200 Denver, CO 80222 RE: Building Envelope Consulting Services Outlook Clear Creek W heatridge, Colorado Project Number 19 -1205 -CC Dear Mr. Harris Building One reviewed the Building Envelope at the Outlook Clear Creek property, specifically at the 4060 Clear Creek Drive address. The weather resistive barrier was observed at all exterior wall assemblies. Building One initially noted some inconsistencies, but it appears that all our concerns have been addressed. It is our understanding that the exterior wall assemblies are in general conformance with the construction documents and industry standards. If you have any questions, please do not hesitate to call. Sincerely, Building One Consulting, LLC Chad Stinnett, RA Associate ViaEmail. Tom Harris'. tharrisadevme.com denver I boston 3190 s. wadsworth blvd., suite 230 1 lakewood, co 80227 1 303.986.1400 COLORADO Colorado Department of Public Health and Environment 4060 Clear Creek Dr 8100 Lovely Blvd. Denver, co 80230 Tel: 303 682-3080 rax: 300-3444988 201902581 Analysis Report Workorder: 2262547 Environmental Microbiology, Wa Client: PLATTE RIVER PLUMBING Report To: LLOYD DECKER Profile: Environmental Microbiology, Water PLATTE RIVER PLUMBING Sampled By: MEGAN PO BOX 640 Henderson, CO 80640 Sample Summary Randy" Lab ID Sample ID Sample Type mNh Data Colleared Dale Received Reported 2101452012 201-]4 Water Total Cdiblm and E. wh Gr2FP2D2111:50 07M=02113:As 2 PA Scientific Director Note: The samples were tested as received from the customer and the results in this report relate only to the samples tested. WL wm� m➢6om.P, W, xlgnnF rai mlve3nim+ Mr Atr mWt•.vppm Report lo. 321]51] Thursday, July 22.20214:24:23 PM Page 1 ore HORIZON' COLORADO Colorado Department of Public Health and Environment 8100 Lowry Blvd. Denver, CO 80230 Tel: 303692-3090 Fax: 303-340.9989 Analysis Report Workorder: 2262547 Environmental Microbiology, Wa Sample Results Lab ID: 2101452042 Sample ID: 201-74 Sample Type: Water Data Collected' 07RN202111:50 Collection SRe: 4060 CLEAR CREEK DR WHEAT RIDGE CO 80401 Date Received 07RN20211346 Site Description: Description: 4080 CLEAR CREEK DR WHEAT RIDGE CO W401 Parameter Results Unlb MRL MCL OF PreWraE Analyzed Oual EPA 922M (T tel Col icarm and E. Call PIP) COLIFORM PIA ABSENT 1 07CV20211456 0]211202114:$ ` ACWFORM P/Aresullol"A9SEM'ugrsahae mlwddrykal0 sere sampN. CaVwm was Wsenlor NsS lMn ma(<i) Cd✓w lo E. COLI PIA ABSENT 1 OA21Y30211C(ya 2114:5 ' 55 O]I21 f20o An ECOLI P/A reaWlo('ASSENTiMr KS Me(EroX Casa NOT OElELTEO Additional Information wms Date Free Chlorine Total Chil Temperature at Collection: Temperature at Record 0 Ware,Type: LAV#Smi All - .l=owsnd not.arourr M,mr Ni witmAwmm. M,rur EFA s,`inrol Report IM 321]51] Thursday, July 22.20214:24:23 PM Page 2or2 HORIZON' 4060 clear crk dr 201902581 Property Address Permit Number Permit Issued Date The City of Wheat Ridge 7500 W. 29th Avenue, Wheat Ridge, CO 80033 Third Party Form Check List 7d 6t CI Lc Ar. C��Iz(or, Owner Information Property Owner Information Property Owner Address Inspection C Inspector N, - Inspector Contact into C; -H A 19 ..5-r "j n� r-C� 6A I c & ry 6 - o Ne', Cv.K Inspector Statement and Acknowledgement * I hearby acknowledge the roof I am inspecting is 6/12 or over. All roofs that are under 6/12 must be inspected by the City of Wheat Ridge Buiding Dept. * I hearby acknowledge the roofing system for the referenced building has been inspected and found to be in compliance with the minimum requirements of the 2012 IRC and 2012 IBC as well as all City of Wheat Ridge Policies and Procedure and Manufacturer's recommendatior�s�ar72i s ecifications. Inspector: {�- Date: 2//2Z 2/ Property Owner Statement of Acknowledgement *1 hearby acknowledge that I am the owner of the building referenced above and I give my consent for the listed third -party inspection company to perform my roof inspection in lieu of the City of Wheat Ridge Building Division inspection. Propery Owner/Agent: Date: This original document must be submitted to the Chief Building Official within seven days of the final inspection. Email to permits@ci.wheatridge.co.us Please add note to reverse side The City of Wheat Ridge 7500 W. 29th Avenue, Wheat Ridge, CO 80033 Third Party Form Check List Please add note to reverse side The City of Wheat Ridge Inspection Check List notes Mid -Roof PROPERTY ADDRESS y06o ('LCp2 CkEr-_p OR, I Roof Inspection ❑ N/A ❑ Pass ❑ Fail `Q N/A ❑ Pass ❑ Fail Structural roof components N/A ❑ Pass ❑ Fail Verify that no more than 2 layers of shingles exist N/A ❑ Pass ❑ Fail Flashing for roof and walls ❑ Pass ❑ Fail If new sheathing is installed verify that it is listed in the permit description (Valuation must be adjusted) ❑ N/A [ Pass ❑ Fail Verify sheathing nail pattern (See Policy & Procedures) ❑ N/A ® Pass ❑ Fail Crickets and saddles where needed 4 N/A ❑ Pass ❑ Fail Verify B vent must have boot same gauge as pipe 61 N/A ❑ Pass ❑ Fail Verify vent caps ❑ N/A ® Pass ❑ Fail Verify no flashings are damaged or rusted ® N/A ❑ Pass ❑ Fail Step flashing shall be min. of 4x4 piece per shingle ❑ N/A Q Pass ❑ Fail Verify scuppers allow for proper drainage ❑ N/A Pass ❑ Fail Ice and water shield 2' in heated wall spaces ❑ N/A] Pass ❑ Fail Underlayments must follow 2012 IRC / 2012 IBC ❑ N/A Pass ❑ Fail Verify roof slope for proper drainage ❑ N/A © Pass ❑ Fail Dripedge shall have min of 2" overlap ❑ N/A ® Pass ❑ Fail Dripedge should extend down min 2" past roof deck ❑ N/A © Pass ❑ Fail Dripedge shall be mechanicaly fastened 12" OC N N/A ❑ Pass ❑ Fail 90 LB roll roofing shall not be applied to roof slopes less than 2:12 slope: Exception, detached garages, patios, carports, open on three sides with min. slope of 1:12 ❑ N/A 0 Pass ❑ Fail Modified Bitumen, EPDM, TPO min slope 1/4:12 slope ❑ N/A © Pass ❑ Fail Above roof insulation R-25 ❑ N/A ] Pass ❑ Fail Below roof residential R-38 ❑ N/A Pass ❑ Fail Below roof commercial R-32 ❑ N/A Pass ❑ Fail Modified Bitumen, EPDM, TPO min slope 1/4:12 slope must be installed in accordance with the manufacturers specifications- Must have manufactures letter of warranty with the address on the letter for final inspection Metal Roof Shingles Requirements N/A 1 ❑ Pass ❑ Fail Metal roof shingles shall not be installed on slope less 3:12 [ N/A ❑ Pass ❑ Fail Metal valley flashing shall be the same material as roof N/A ❑ Pass ❑ Fail Metal valley flashing shall extend a min of 8" from the centerline with a min. of 3/4 " high splash diverter rib built-in at the flow line with sections overlapping a a min. of 4" Tile Roofs Requirements ® N/A ❑ Pass ❑ Fail Clay and concrete tile shall have a min. 2-1/2:12 slope Slopes 4:12 and under require double underlayment The City of Wheat Ridge Inspection Check List notes Mid -Roof Notes � Company Name: �� 01j Inspector signature: Date of Inspection:12 Zy/2o The City of Wheat Ridge Inspection Check List notes Final Roof PROPERTY ADDRESS: q (P� �'ii�Q,c Cn�e c DRQv� Roof Inspection ❑ N/A ❑ Pass ❑ Fail © N/A ❑ Pass ❑ Fail Structural roof components 0 N/A ❑ Pass ❑ Fail Verify that no more than 2 layers of shingles exist ❑ N/A Q Pass ❑ Fail Flashing for roof and walls ® Pass ❑ Fail If new sheathing is installed verify that it is listed in the permit description (Valuation must be adjusted) X❑ N/A ❑ Pass ❑ Fail Verify sheathing nail pattern (See Policy & Procedures) ❑ N/A Pass ❑ Fail Crickets and saddles where needed ❑ N/A ® Pass ❑ Fail Verify B vent must have boot same gauge as pipe ❑ N/Ar®/ Pass [:]Fail Verify vent caps ❑ N/A [X] Pass ❑ Fail Verify no flashings are damaged or rusted ❑ N/Ar1 Pass E] Fail Step flashing shall be min. of 4x4 piece per shingle E] N/A I^ 1 Pass ❑ Fail Verify scuppers allow for proper drainage ❑ N/A [K1 Pass ❑ Fail Ice and water shield 2' in heated wall spaces ❑ N/A 14 Pass ❑ Fail Underlayments must follow 2012 IRC / 2012 IBC ❑ N/A Pass ❑ Fail Verify roof slope for proper drainage ❑ N/A Pass ❑ Fail Dripedge shall have min of 2" overlap ❑ N/A [i Pass ❑ Fail Dripedge should extend down min 2" past roof deck ❑ N/A Pass ❑ Fail Dripedge shall be mechanicaly fastened 12" OC ® N/A ❑ Pass ❑ Fail 90 LB roll roofing shall not be applied to roof slopes less than 2:12 slope; Exception: detached garages, patios, carports, open on three sides with min. slope of 1:12 ❑ N/A ® Pass ❑ Fail Modified Bitumen, EPDM, TPO min slope 1/4:12 slope ❑ N/A ® Pass ❑ Fail Above roof insulation R-25 ❑ N/A ® Pass ❑ Fail Below roof residential R-38 ❑ N/A Pass ❑ Fail Below roof commercial R-32 ❑ N/A Pass ❑ Fail Modified Bitumen, EPDM, TPO min slope 1/4:12 slope must be installed in accordance with the manufacturer's specifications - Must have manufacturer's letter of warranty with the address on the letter for final inspection Metal Roof Shingles Requirements [ N/A ❑ Pass ❑ Fail Metal roof shingles shall not be installed on slope less 3:12 [] N/A ❑ Pass ❑ Fail Metal valley flashing shall be the same material as roof © N/A ❑ Pass ❑ Fail Metal valley flashing shall extend a min of 8" from the centerline with a min. of 3/4 " high splash diverter rib built-in at the flow line with sections overlapping a a min. of 4" Tile Roofs Requirements ® N/A ❑ Pass ❑ Fail Clay and concrete the shall have a min. 2-1/2:12 slope Slopes 4:12 and under require double underlayment The City of Wheat Ridge Inspection Check List notes Final Roof Notes lav 07ttatr Company Name: ,l'01,�c 00 fcrc, 6 Inspector signature: Date of Inspection: 6/11/21 7135 Ivy Street Commerce City, CO 80022 Design • Contracting • Service • Repairs • Inspections Phone: 303-761-7755 Fax: 303-789-0128 �T8 dip®i'�(�LIl®IIIb IIffi�° Email: Service@H2OFirelnc.com Assembly Serial # 113422 Test Date / Time 6/21/21 Tester Certification #6-784 ssembly Test Results W Pass ❑ Fail ❑ Under Suspension- Process Immediately Denver Water Backflow Assembly Test & Maintenance Report (please print with BLOCK LETTERING) -sting Company: Submit by e-mail (preferred) to CrossConnectionControl@denverwater.org, type "Backflow Test Reports" in the subject line OR submit by Fax to (303) 794-8325. * FAILED test results must be reported to Denver Water within 24 hours of failure at (303) 628-5969. Water Supplier: Consolidated District: Meter #- 0 Facility Address: 4060 Clear Creek Dr Bldg 5 City: Lakewood ST: CO Zip: 80401 a Contact Person: Phone: Make: Ames Model: Deringer 40 Type of Use Protection Orientation Type: RP ❑ DC ❑PVB ❑Air Gap , Date I nstalled. 6/2021� Size. 4 ❑ Domestic Containment Inlet Outlet E zNew ❑ Existing vFire ❑Glycol ❑Containment by Isolation v Horizontal v Previous Assembly #: N/A ❑Irrigation ❑ Isolation ❑ Vertical Up ❑ ❑Recycled ❑ Vertical Down ❑ Location: Riser room 4064 Approved: Y v N ❑ Line 75 Initial Test Results Repairs Re -Test Results Tightness Differential Tightness Differential PSI. Check Valve #1 ❑ Leak ❑ Leak (RP, DC, PVB) vTight 8.8 ❑Tight Check Valve #2 ❑ Leak ❑ Leak (RP, DC) vTight 2.2 ❑Tight Relief Valve (RP) 2.8 Buffer (RP) 6.0 Air Inlet (PVB) ~ Shutoff Valve #1: vTight ❑ Leaking ❑ Replaced JShutoff Valve #2: vTight ❑ Leaking ❑ Replaced Backpressure: ❑Yes ❑ No ITest Procedure: vABPA: ❑ASSET Comments: o Alarm Company/Fire Department: DFS Certification #: Person Notified: Contacted By - 0 Turn Off Date/Time: Turn On Date/Time: Y Test Kit Make: Midwest Model: 845-5 N Serial #: 02142752 Last Calibration Date: 4/19/21 Tester certifies this ssem y has been tested with the above listed procedure and verifies the isolation valves were returned to pre-test orientation. Testing Co Fire Protection, Inc. Tester a ar cCracken Phone: (303) 761-7755 Si tur4ei Certificate Expiration Date: 9/22/21 -sting Company: Submit by e-mail (preferred) to CrossConnectionControl@denverwater.org, type "Backflow Test Reports" in the subject line OR submit by Fax to (303) 794-8325. * FAILED test results must be reported to Denver Water within 24 hours of failure at (303) 628-5969. July 20, 2021 Evergreen Development 1873 South Bellaire Street, Suite 1200 Denver, CO 80222 Attn: Evergreen Development Re: Compliance Letter for Special Inspections Outlook Clear Creek, Permit No.: 201902581 4060 Clear Creek Drive, Building 5 Wheat Ridge, CO CGG Project Noe. 19.23.225 Cole Garner f-AmAt technical 1070 W. 124 t" Ave, Ste. 300 Westminster, C 111111111111) 802 34 303.996.2999 At your request, Cole Garner Geotechnical (CGG) was retained to provide construction special inspection and materials testing for the above-named project. Observation and special inspection services were performed as scheduled by the contractor during the construction of the following elements: Fairestoppoing - periodic visual special inspection of membrane penetrations to verify adherence with manufacturer recommendations for UL rating Wood Framing -visual inspection of shear and gravity systems including member size, grade and orientation including hardware and fasteners The results of our special inspections were noted to comply with the approved project plans, specifications and relevant sections of the International Building Code. We trust that the information presented herein satisfies your present needs. Sincerely, irner Geotechnica Thomas C. Cole, P.E. Principal I- 95 - 201902581 Assembly Serial # Test Date/ Time aiulv - Qd Tester Ceni#catipn# /old (Q vaso,' Assembly Test Results ® Pass ❑*Fall ❑ Under Suspension- Process Immediately Denver Water Backflow Assembly Test & Maintenance Report (ple se print with BLOCK LETTERING) p Facility Name: ® i..�a,r❑ rj Meter Ar wO Facility Address' City: Contact Person: Phone� 3 Make: Model. Type: Pt ❑DC ❑PVB ❑Air Can Two of Use Protection Orien tion ' Size Date Installed: �Q'� �f� Domestic Iprwntainment Inlet Outlet I kNew ❑ Existing D Fire O Glycol ❑ Containment by Isolation --Z Horizontal 2 Previous Assembly#: VO/L VO/L ❑ Irrigation ❑ Isolation ❑ Ver l Up ❑ Location: ❑ Recycled ❑ Vertical Down ❑ lai Approved: VgN❑ Line O Initial Test Results Repairs Re -Test Results Tightness Differential Tightness Differential PSI'. Check Vahre #1 ❑ Leakryry ❑ Leak (RP,DC,PVB) $Tight -D. - ❑Tight Check Valva#2 LI Leak ❑Leak 8 (RP, DC) 4ITight ❑Tight Relief Valve •� (RP) •p(_, — Buffer e (�) Air Inlet y PVB Shutoff Valve #1: Wight ❑ Leaking O Replaced Shutoff Valve #2: ffilalght ❑ Leaking ❑ Replaced Backpressure: ❑ Ves Test Procedure: ❑ ABPA: E: Comments: IA�IA o Alarm Company)Fire Department:l(�yt. x Person Notified: y Contacted By i Turn Off Datarri nxis Tum On DDaattenrini x Test Kit Make:( yp k� of 'n Moit IR, - i 3 S Serial#: Leet Calibration Date:p'/Q—,',Z( TelMe ryrwa rested wan tlreeWve Xefetl maM vermes fhe kdaGm valves werererumee ropre-test aienmrm. s Testieingng CCompompany: F ~ Tester Name: PhoneVol: 51 nature 9 Cerfifloete Fxpirabo r Date: !Kat 2a C/ Testing Cempeny: sui of e-mail (preferred) b Cres nredionCo i@denvarrebr.am. me'aaiTest Repwu• in Me aubjecl line OR wbmtl by Fax to(b3)T 1325, e FAILED test results must De repand to Denver Water m in 24 hours of failure at (303) saff.W69. 4060 Clear Creek Drive 201902581 GP INSULATION 7221 E 67PL COMMERCE CITY Installed Insulation Certificate We certify that the insulation material listed here was installed at the address listed below: Contractor GP INSULATION -Guillermo Passillas (Signature) Title MANAGER Print Certificate Other than loose fill only aluminum foil only Aluminum Foam aluminum for( Loose Fill Kraft Unfaced Foil open/closed BIBS® R -Value Thickness Attic ❑ ❑ X❑ ❑ ❑ ❑ R-49 Ceilings ❑ ❑ ❑X ❑ ❑ ❑ R-11 Floors ❑ ❑ 0 ❑ ❑ ❑ R-49 Batts Walls ❑ ❑ ❑X ❑ ❑ ❑ R-21 poly Basement E] ❑ ❑ ❑ ❑ ❑ Crawlspace ❑ ❑ ❑ ❑ ❑ ❑ Other ❑ ❑ ❑X 11 ❑ ❑ R-19 Int -wall Contractor GP INSULATION -Guillermo Passillas (Signature) Title MANAGER Print Certificate Address or Lot Number: 4060 CLEARCREEK DR BULDING -5 City, ST Zip: WHET RIDGE DR 80401 Date Installed: 06/20/20 Tr.OPS.FRM.010 Other than loose fill only aluminum foil only loose fill 8 aluminum for( Initial Installed & No.of Coverage Minimum Settled Air Spaces Direction of Pkgs Area (SF) Thickness No. /Thickness Heat Flow Celing Address or Lot Number: 4060 CLEARCREEK DR BULDING -5 City, ST Zip: WHET RIDGE DR 80401 Date Installed: 06/20/20 Tr.OPS.FRM.010