B & B Heating and AC June 18, 2022
4892 Marshall Street
Wheat Ridge, CO 80033
Subject: Sun Company
Dear Tim,
The enclosed data is submitted as the final Test and Balance Report for the
Air Distribution System.
This project has been completed per specifications and mechanical plans in
accordance with the industry standards except where indicated in the general
notes.
If you have any questions concerning this report, please feel free to contact us.
Cordially,
Ran y J. Pa
Balance Technologies
2955 E. Otero Place, Centennial, CO, 80122, 720.350.9817
Balance Technolo
Instrumentation Used
Shorbidge Flow Hood (ADM -860-1)
Calibrated
0623/21
Serial No. M93015
Thermometer -Taylor (6076-10)
Calibrated
Manuf.
-40 to 120F SIN - BT015 & BT012
Thermometer -Taylor (6072-10)
Calibrated
Manuf.
0 to 220F SM - BT016 & BT014
Digital Volt, Ohm and Ampmeler, Fluke (32)
Calibrated
Manuf.
Serial No. 1121263
Shortridge Hydmdata(HDM-250-1)
Calibrated
06/0921
Serial No. WI1131
.:lla�ail.ce Plec%no.1 ® AIR APPARATUS
TEST REPORT
PROJECT SUN COMPANY SYSTEMAINIT RTU - 1
LOCATION ROOF
UNIT DATA
MOTOR DATA
Make
TRANE
Make/Frame
MARATHON/56
Model
GBC060A3EMB09
H. P. RPM
1./17
Serial Number
22142332PA
Volts/Phase/Hertz
28/3/60
F. L. Amps/S. F.
4.0/1.5
Discharge
DOWN DISCHARGE
Make Sheave
BROWNING
Make Sheave
BROWNING
Sheave Diam/Bore
1VP30/518"
Sheave Diam /Bore
5.0" 13/4"
Sheave Distance
15 1/2"
No. Be1Ls/maklame
1/ MATCHMAKER I AX40
No. Fillers/ype/s..
41 DISPOSE / 16X16X2
TEST DATA
DESIGN ACTUAL
TEST DATA
DESIGN
ACTUAL
Total CFM
1980 1958
Discharge S. P.
0.44
Total S. P.
N / G 1.08
Suction S. P.
-0.64
Fan RPM
N / G 1070
Cooling Coil S. P.
0.28
Motor Volts
208 215/213214
Preheat Coil S. P.
Motor Amps
4.0 3.0
Filters S. P.
0.28
3.2
3.2
Outside Air CFM
470 452
Rehm Air CFM
1510 1506
Out. Air Damp. Position
24%
23%
Ret. Air Damp. Position
78%
77%
REMARKS: -ACROSS FILTERS AND COOLING COIL.
FILE SC -1
TEST DATE JUNE 2022 READINGS BY R.P.
Balance Technologies
zfdl4rac T ,4tflwie ® AIR OUTLET TEST
REPORT
PROJECT SUN COMPANY SYSTEM RTU - 1
REMARKS: NONE
FILE SC -2
TEST DATE JUNE 2022 READINGS BY R
Balance Technologies
�II
,
m®®m
®®®®■■
®®
E__m
REMARKS: NONE
FILE SC -2
TEST DATE JUNE 2022 READINGS BY R
Balance Technologies
�OCT� O
PROJECT SUN COMPANY
FAN TEST REPORT
SYSTEM EXHAUST
FAN DATA
FAN NO. EF -1 FAN NO. FAN NO.
Service
PRINTER ROOM
Manufacturer
GREENHECK
Model Number
SP -A700
Senal Number
N/A
Motor H.P.
FRACTIONAL
TEST DATA
DESIGN JACTUAL DESIGN JACTUAL IDESIGN
JACTUAL
CFM
470 515
Fan RPM
DIR. DRIVE DIR. DRIVE
Voltage
115 122
Arnperage
N/A 2.5
FAN DATA FAN NO. FAN NO. FAN NO.
Service
Manufacturer
Model Number
Serial Number
Motor H.P.
TEST DATA IDESIGN JACTUAL DESIGN JACTUAL DESIGN JACTUAL
CFM
Fan RPM
Voltage
Amperage
REMARKS NONE
FILE SC -3
TEST DATE JUNE 2022 READINGS BY R.P.
Balance Technologies