Loading...
HomeMy WebLinkAbout4840 Van Gordon St Balance ReportBalance Technolo t PROJECT Sun Company, Inc. 4840 Van Gordon Street Unit 1200 Wheal Ridge, CO 80033 MECHANICAL CONTRACTOR B & B Heating and A/C 4892 Marshall Street Wheat Ridge, CO 80033 REFERENCE JOB NUMBER 04-0622-115 Balance Technolo IDI B & B Heating and AC June 18, 2022 4892 Marshall Street Wheat Ridge, CO 80033 Subject: Sun Company Dear Tim, The enclosed data is submitted as the final Test and Balance Report for the Air Distribution System. This project has been completed per specifications and mechanical plans in accordance with the industry standards except where indicated in the general notes. If you have any questions concerning this report, please feel free to contact us. Cordially, Ran y J. Pa Balance Technologies 2955 E. Otero Place, Centennial, CO, 80122, 720.350.9817 Balance Technolo Instrumentation Used Shorbidge Flow Hood (ADM -860-1) Calibrated 0623/21 Serial No. M93015 Thermometer -Taylor (6076-10) Calibrated Manuf. -40 to 120F SIN - BT015 & BT012 Thermometer -Taylor (6072-10) Calibrated Manuf. 0 to 220F SM - BT016 & BT014 Digital Volt, Ohm and Ampmeler, Fluke (32) Calibrated Manuf. Serial No. 1121263 Shortridge Hydmdata(HDM-250-1) Calibrated 06/0921 Serial No. WI1131 .:lla�ail.ce Plec%no.1 ® AIR APPARATUS TEST REPORT PROJECT SUN COMPANY SYSTEMAINIT RTU - 1 LOCATION ROOF UNIT DATA MOTOR DATA Make TRANE Make/Frame MARATHON/56 Model GBC060A3EMB09 H. P. RPM 1./17 Serial Number 22142332PA Volts/Phase/Hertz 28/3/60 F. L. Amps/S. F. 4.0/1.5 Discharge DOWN DISCHARGE Make Sheave BROWNING Make Sheave BROWNING Sheave Diam/Bore 1VP30/518" Sheave Diam /Bore 5.0" 13/4" Sheave Distance 15 1/2" No. Be1Ls/maklame 1/ MATCHMAKER I AX40 No. Fillers/ype/s.. 41 DISPOSE / 16X16X2 TEST DATA DESIGN ACTUAL TEST DATA DESIGN ACTUAL Total CFM 1980 1958 Discharge S. P. 0.44 Total S. P. N / G 1.08 Suction S. P. -0.64 Fan RPM N / G 1070 Cooling Coil S. P. 0.28 Motor Volts 208 215/213214 Preheat Coil S. P. Motor Amps 4.0 3.0 Filters S. P. 0.28 3.2 3.2 Outside Air CFM 470 452 Rehm Air CFM 1510 1506 Out. Air Damp. Position 24% 23% Ret. Air Damp. Position 78% 77% REMARKS: -ACROSS FILTERS AND COOLING COIL. FILE SC -1 TEST DATE JUNE 2022 READINGS BY R.P. Balance Technologies zfdl4rac T ,4tflwie ® AIR OUTLET TEST REPORT PROJECT SUN COMPANY SYSTEM RTU - 1 REMARKS: NONE FILE SC -2 TEST DATE JUNE 2022 READINGS BY R Balance Technologies �II , m®®m ®®®®■■ ®® E__m REMARKS: NONE FILE SC -2 TEST DATE JUNE 2022 READINGS BY R Balance Technologies �OCT� O PROJECT SUN COMPANY FAN TEST REPORT SYSTEM EXHAUST FAN DATA FAN NO. EF -1 FAN NO. FAN NO. Service PRINTER ROOM Manufacturer GREENHECK Model Number SP -A700 Senal Number N/A Motor H.P. FRACTIONAL TEST DATA DESIGN JACTUAL DESIGN JACTUAL IDESIGN JACTUAL CFM 470 515 Fan RPM DIR. DRIVE DIR. DRIVE Voltage 115 122 Arnperage N/A 2.5 FAN DATA FAN NO. FAN NO. FAN NO. Service Manufacturer Model Number Serial Number Motor H.P. TEST DATA IDESIGN JACTUAL DESIGN JACTUAL DESIGN JACTUAL CFM Fan RPM Voltage Amperage REMARKS NONE FILE SC -3 TEST DATE JUNE 2022 READINGS BY R.P. Balance Technologies